Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:36:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1448.63 | 693.02 | 693.02 |
Net Site Energy | 1448.63 | 693.02 | 693.02 |
Total Source Energy | 4587.81 | 2194.79 | 2194.79 |
Net Source Energy | 4587.81 | 2194.79 | 2194.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 655.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1448.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 655.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 139.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 655.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 139.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 407.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 693.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 407.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 693.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1448.629 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1448.629 | 100.00 |
Total On-Site and Utility Electric Sources | 1448.629 | 100.00 |
Total Electricity End Uses | 1448.629 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 5.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1032.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 105584.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14864.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3311.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 158081.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 105584.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14864.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3311.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2075.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 440.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4587.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 993.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 210.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2194.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 993.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 210.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2194.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.96 |
SMSTORE1 DIRECT AIR | 1.49 |
SMSTORE2 DIRECT AIR | 1.49 |
SMSTORE3 DIRECT AIR | 1.50 |
SMSTORE4 DIRECT AIR | 1.49 |
LGSTORE2 DIRECT AIR | 2.65 |
SMSTORE5 DIRECT AIR | 1.40 |
SMSTORE6 DIRECT AIR | 1.40 |
SMSTORE7 DIRECT AIR | 1.41 |
SMSTORE8 DIRECT AIR | 1.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.96 | 2.96 | 2.96 | 2.96 | 2.96 | 2.96 | 1.00 | 1.00 | 2.96 |
PSZ-AC_2:2 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_3:3 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_4:4 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.00 | 1.00 | 1.50 |
PSZ-AC_5:5 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_6:6 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 1.00 | 1.00 | 2.65 |
PSZ-AC_7:7 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
PSZ-AC_8:8 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
PSZ-AC_9:9 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
PSZ-AC_10:10 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.000000 | 1.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.96 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.50 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.65 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.40 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.40 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.41 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.68 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.96 | 3172.44 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1597.95 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1597.86 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.50 | 1601.33 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1593.07 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.65 | 2838.94 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1552.45 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1547.37 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1557.31 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1793.40 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.96 | 2.96 | 2.96 | 1.96 | 73342.59 | 73143.11 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.985606 | 36991.24 | 36209.21 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.985551 | 36989.90 | 36207.27 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.987693 | 37052.90 | 36281.43 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.982596 | 36903.76 | 36105.01 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.65 | 2.65 | 2.65 | 1.75 | 65882.68 | 65865.99 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 0.925445 | 34819.69 | 34686.27 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 0.922420 | 34705.89 | 34581.50 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 0.928344 | 34928.79 | 34822.39 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 40257.28 | 40940.75 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.96 | 1.48 | 1.98 | 73342.59 | 36671.29 | 0.703020 | 0.703020 |
PSZ-AC_2:2 COOLING COIL | 1.49 | 0.746671 | 0.995560 | 36991.24 | 18495.62 | 0.702690 | 0.702690 |
PSZ-AC_3:3 COOLING COIL | 1.49 | 0.746629 | 0.995507 | 36989.90 | 18494.95 | 0.702690 | 0.702690 |
PSZ-AC_4:4 COOLING COIL | 1.50 | 0.748252 | 0.997667 | 37052.90 | 18526.45 | 0.702800 | 0.702800 |
PSZ-AC_5:5 COOLING COIL | 1.49 | 0.744391 | 0.992520 | 36903.76 | 18451.88 | 0.701520 | 0.701520 |
PSZ-AC_6:6 COOLING COIL | 2.65 | 1.33 | 1.77 | 65882.68 | 32941.34 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.40 | 0.701095 | 0.934793 | 34819.69 | 17409.85 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.40 | 0.698803 | 0.931740 | 34705.89 | 17352.94 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.41 | 0.703291 | 0.937720 | 34928.79 | 17464.40 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.68 | 0.837999 | 1.12 | 40257.28 | 20128.64 | 0.711370 | 0.711370 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 73143.11 |
PSZ-AC_2:2 HEATING COIL | 36209.21 |
PSZ-AC_3:3 HEATING COIL | 36207.27 |
PSZ-AC_4:4 HEATING COIL | 36281.43 |
PSZ-AC_5:5 HEATING COIL | 36105.01 |
PSZ-AC_6:6 HEATING COIL | 65865.99 |
PSZ-AC_7:7 HEATING COIL | 34686.27 |
PSZ-AC_8:8 HEATING COIL | 34581.50 |
PSZ-AC_9:9 HEATING COIL | 34822.39 |
PSZ-AC_10:10 HEATING COIL | 40940.75 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 35 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.02458E-002 | 0.13126 | 0.64133 | 0.64133 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 33552.09613 | 40262.51536 | 2.47064 | 2.96477 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 9153.25517 | 10983.90621 | 0.37887 | 0.45464 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 16900.06845 | 20280.08215 | 1.24445 | 1.49334 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 4216.91151 | 5060.29381 | 0.18189 | 0.21827 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 16899.12339 | 20278.94807 | 1.24438 | 1.49326 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 4232.08919 | 5078.50703 | 0.18255 | 0.21906 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 16935.86547 | 20323.03856 | 1.24709 | 1.49650 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 4270.60139 | 5124.72167 | 0.18421 | 0.22105 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 16848.47589 | 20218.17107 | 1.24065 | 1.48878 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 4389.40598 | 5267.28718 | 0.18933 | 0.22720 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 30025.28522 | 36030.34226 | 2.21091 | 2.65310 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 8934.34244 | 10721.21093 | 0.36936 | 0.44323 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 15868.51058 | 19042.21270 | 1.16849 | 1.40219 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 4683.97835 | 5620.77402 | 0.19450 | 0.23340 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 15816.64648 | 18979.97577 | 1.16467 | 1.39761 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 4708.27476 | 5649.92971 | 0.19549 | 0.23459 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 15918.23271 | 19101.87925 | 1.17215 | 1.40658 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 5029.24538 | 6035.09446 | 0.20856 | 0.25027 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 18968.35958 | 22762.03150 | 1.39667 | 1.67600 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 42.31500 | 1.07810E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 5990.99508 | 7189.19409 | 0.25004 | 0.30005 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 49156.18 | 2.96477 | 2.96477 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 14592.89 | 0.45464 | 0.45464 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24727.74 | 1.49334 | 1.49334 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 7079.39 | 0.21827 | 0.21827 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 24726.62 | 1.49326 | 1.49326 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 7097.34 | 0.21906 | 0.21906 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 24769.46 | 1.49650 | 1.49650 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 7142.88 | 0.22105 | 0.22105 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 24665.97 | 1.48878 | 1.48878 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 7283.37 | 0.22720 | 0.22720 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 44979.83 | 2.65310 | 2.65310 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 14326.58 | 0.44323 | 0.44323 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 23503.11 | 1.40219 | 1.40219 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 7437.84 | 0.23340 | 0.23340 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 23441.57 | 1.39761 | 1.39761 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 7465.73 | 0.23459 | 0.23459 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 23560.50 | 1.40658 | 1.40658 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 7832.41 | 0.25027 | 0.25027 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 27057.15 | 1.67600 | 1.67600 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 8983.51 | 0.30005 | 0.30005 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.96477 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49334 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49326 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49650 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48878 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.65310 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40219 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39761 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40658 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67600 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.96477 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.96477 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.96477 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.96477 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.96477 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.96477 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49334 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49334 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49334 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49334 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49334 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49334 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49326 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49326 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49326 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49326 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49326 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49326 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49650 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49650 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49650 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49650 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49650 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49650 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48878 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48878 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48878 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48878 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48878 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48878 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.65310 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.65310 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.65310 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.65310 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.65310 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.65310 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40219 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40219 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40219 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40219 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40219 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40219 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39761 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39761 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39761 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39761 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39761 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39761 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40658 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40658 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40658 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40658 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40658 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40658 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67600 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67600 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67600 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67600 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67600 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67600 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.96477 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.49334 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.49326 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.49650 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.48878 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.65310 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.40219 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.39761 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.40658 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.67600 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.96477 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.96477 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3172.44104 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.96477 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.96477 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.96477 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.95675 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.96477 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.48238 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.97651 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 73342.59000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36671.29500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70302 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70302 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 73342.59000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73143.10636 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 73143.10636 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49334 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49334 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1597.94682 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49334 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49334 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49334 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98561 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49334 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74667 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99556 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36991.24000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18495.62000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70269 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70269 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36991.24000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36209.21258 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 36209.21258 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49326 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49326 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1597.85704 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49326 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49326 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49326 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98555 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49326 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74663 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99551 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36989.90000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18494.95000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70269 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70269 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36989.90000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36207.27208 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 36207.27208 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49650 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49650 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1601.33037 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49650 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49650 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49650 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98769 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49650 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74825 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99767 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37052.90000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18526.45000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70280 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70280 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37052.90000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36281.42674 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 36281.42674 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48878 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48878 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1593.06721 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48878 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48878 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48878 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98260 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48878 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74439 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99252 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36903.76000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18451.88000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70152 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70152 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36903.76000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36105.01025 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 36105.01025 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.65310 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.65310 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2838.93762 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.65310 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.65310 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.65310 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.75104 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.65310 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32655 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.76873 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 65882.68000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32941.34000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 65882.68000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65865.99453 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 65865.99453 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40219 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40219 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1552.44585 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40219 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40219 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40219 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92544 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40219 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70109 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93479 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34819.69000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17409.84500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34819.69000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34686.27047 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 34686.27047 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39761 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39761 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1547.37191 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39761 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39761 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39761 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92242 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39761 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69880 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93174 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34705.89000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17352.94500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34705.89000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34581.50130 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 34581.50130 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40658 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40658 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1557.30984 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40658 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40658 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40658 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92834 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40658 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70329 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93772 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34928.79000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17464.39500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34928.79000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34822.38659 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 34822.38659 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67600 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67600 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1793.39740 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67600 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67600 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67600 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10616 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67600 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83800 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11733 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40257.28000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20128.64000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71137 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71137 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40257.28000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40940.74527 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 40940.74527 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 71003.8 | 10.85 | 10.85 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 35813.2 | 11.94 | 11.94 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 35811.9 | 11.94 | 11.94 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 35872.4 | 11.94 | 11.94 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 35729.3 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 63789.6 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 33713.5 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 33603.3 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 33819.1 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 38935.9 | 11.71 | 11.71 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.22 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1366237046E-002 | 6.5069114980E-002 | Pass | Pass | 3.4396212387E-002 | 9.6208966172E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.8307682048E-002 | 6.9483485262E-002 | Pass | Pass | 3.2748726129E-002 | 9.3976745803E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.8790197528E-002 | 7.7149545208E-002 | Pass | Pass | 0.1351649829 | 1.1720266401 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.9310026419E-002 | 7.5347138758E-002 | Pass | Pass | 0.1452132115 | 1.2661485394 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.9744994186E-002 | 7.2313795365E-002 | Pass | Pass | 0.1634117519 | 1.4289192735 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4174420950E-002 | 4.9671746998E-002 | Pass | Pass | 0.1499145527 | 1.3098117584 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.3721250488E-002 | 4.7681435181E-002 | Pass | Pass | 0.3458146834 | 2.8308719924 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.4099974735E-002 | 4.7667382126E-002 | Pass | Pass | 0.6017403766 | 4.1546503083 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.5682191295E-002 | 4.7398972496E-002 | Pass | Pass | 0.5870075857 | 6.0396998291 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.2826047440E-002 | 5.0618452333E-002 | Pass | Pass | 0.3057007852 | 2.5756618397 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2259.36 | -416.1 | 0.00 | -985.4 | 3017.80 | 3875.68 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.826 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.826 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.85 | 41.85 | 3.58 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.85 | 62.85 | 32.38 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.85 | 55.85 | 24.19 | |
Exterior Lighting Total | 5507.06 | 60.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 73342.59 | 51561.31 | 21781.28 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36991.24 | 25993.37 | 10997.87 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36989.90 | 25992.43 | 10997.47 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37052.90 | 26040.78 | 11012.12 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36903.76 | 25888.73 | 11015.03 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 65882.68 | 46189.03 | 19693.65 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34819.69 | 24411.39 | 10408.30 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34705.89 | 24331.61 | 10374.28 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34928.79 | 24487.88 | 10440.91 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40257.28 | 28637.82 | 11619.46 | 0.71 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 71003.8 | 10.85 | 10.85 | ||||
PSZ-AC_2:2 COOLING COIL | 35813.2 | 11.94 | 11.94 | ||||
PSZ-AC_3:3 COOLING COIL | 35811.9 | 11.94 | 11.94 | ||||
PSZ-AC_4:4 COOLING COIL | 35872.4 | 11.94 | 11.94 | ||||
PSZ-AC_5:5 COOLING COIL | 35729.3 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 63789.6 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 33713.5 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 33603.3 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 33819.1 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 38935.9 | 11.71 | 11.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 73143.11 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 36209.21 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 36207.27 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 36281.43 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 36105.01 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 65865.99 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 34686.27 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 34581.50 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 34822.39 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 40940.75 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.96 | 3172.44 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1597.95 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1597.86 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1601.33 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1593.07 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.65 | 2838.94 | 1070.05 | 1.00 | 1.28 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.40 | 1552.45 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.40 | 1547.37 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1557.31 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1793.40 | 1070.05 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 33552.10 | 40262.52 | 115.57 | 2.471 | 2.965 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 23.89 | 23.89 | 0.00785 | 42.70 | 0.01078 | 0.411 | 0.00 |
SMSTORE1 | 16900.07 | 20280.08 | 116.42 | 1.244 | 1.493 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00787 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE2 | 16899.12 | 20278.95 | 116.42 | 1.244 | 1.493 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00787 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE3 | 16935.87 | 20323.04 | 116.67 | 1.247 | 1.497 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00787 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE4 | 16848.48 | 20218.17 | 116.07 | 1.241 | 1.489 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00788 | 42.72 | 0.01078 | 0.206 | 0.00 |
LGSTORE2 | 30025.29 | 36030.34 | 103.42 | 2.211 | 2.653 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00791 | 42.72 | 0.01078 | 0.411 | 0.00 |
SMSTORE5 | 15868.51 | 19042.21 | 109.32 | 1.168 | 1.402 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00792 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE6 | 15816.65 | 18979.98 | 108.96 | 1.165 | 1.398 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00792 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE7 | 15918.23 | 19101.88 | 109.66 | 1.172 | 1.407 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00792 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE8 | 18968.36 | 22762.03 | 130.67 | 1.397 | 1.676 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.89 | 0.00783 | 42.31 | 0.01078 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 9153.26 | 10983.91 | 31.53 | 0.379 | 0.455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00836 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE1 | 4216.91 | 5060.29 | 29.05 | 0.182 | 0.218 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE2 | 4232.09 | 5078.51 | 29.15 | 0.183 | 0.219 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00856 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE3 | 4270.60 | 5124.72 | 29.42 | 0.184 | 0.221 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE4 | 4389.41 | 5267.29 | 30.24 | 0.189 | 0.227 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
LGSTORE2 | 8934.34 | 10721.21 | 30.77 | 0.369 | 0.443 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE5 | 4683.98 | 5620.77 | 32.27 | 0.194 | 0.233 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE6 | 4708.27 | 5649.93 | 32.43 | 0.195 | 0.235 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE7 | 5029.25 | 6035.09 | 34.65 | 0.209 | 0.250 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE8 | 5991.00 | 7189.19 | 41.27 | 0.250 | 0.300 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00842 | 12.70 | 0.00915 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.96 | 2.96 | 0.45 | 0.45 | 2.9648 | 2.9648 | 2.9648 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.49 | 1.49 | 0.22 | 0.22 | 1.4933 | 1.4933 | 1.4933 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.49 | 1.49 | 0.22 | 0.22 | 1.4933 | 1.4933 | 1.4933 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.50 | 1.50 | 0.22 | 0.22 | 1.4965 | 1.4965 | 1.4965 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.49 | 1.49 | 0.23 | 0.23 | 1.4888 | 1.4888 | 1.4888 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.65 | 2.65 | 0.44 | 0.44 | 2.6531 | 2.6531 | 2.6531 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.40 | 1.40 | 0.23 | 0.23 | 1.4022 | 1.4022 | 1.4022 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.40 | 1.40 | 0.23 | 0.23 | 1.3976 | 1.3976 | 1.3976 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.41 | 1.41 | 0.25 | 0.25 | 1.4066 | 1.4066 | 1.4066 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.68 | 1.68 | 0.30 | 0.30 | 1.6760 | 1.6760 | 1.6760 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 73342.590 | 51561.308 | 2.964770 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 36671.29 | 31381.37 | 1.976513 | 27.38 | 17.35 | 0.00825443 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.8184 | 23.89 | 0.00784706 | 42.5576 | 33547.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 73143.106 | 73143.106 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 73143.11 | 73143.11 | 2.964767 | 19.60 | 14.75 | 0.00847184 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.8790 | 21.11 | 0.00836199 | 53.6356 | 9153.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36991.240 | 25993.374 | 1.493340 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18495.62 | 15789.93 | 0.995560 | 27.36 | 17.36 | 0.00827384 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.6657 | 23.89 | 0.00787311 | 42.6971 | 16900.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 36209.213 | 36209.213 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36209.21 | 36209.21 | 1.493342 | 19.95 | 15.03 | 0.00863588 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.7771 | 21.11 | 0.00855318 | 54.8441 | 4216.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 36989.900 | 25992.433 | 1.493260 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18494.95 | 15789.14 | 0.995507 | 27.36 | 17.36 | 0.00827397 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.6668 | 23.89 | 0.00787323 | 42.6977 | 16899.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 36207.272 | 36207.272 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36207.27 | 36207.27 | 1.493258 | 19.95 | 15.03 | 0.00863851 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.7779 | 21.11 | 0.00855623 | 54.8634 | 4232.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 37052.900 | 26040.778 | 1.496500 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18526.45 | 15819.38 | 0.997667 | 27.36 | 17.36 | 0.00827175 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.6221 | 23.89 | 0.00787165 | 42.6893 | 16935.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 36281.427 | 36281.427 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36281.43 | 36281.43 | 1.496504 | 19.95 | 15.03 | 0.00863634 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.7480 | 21.11 | 0.00855392 | 54.8487 | 4270.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 36903.760 | 25888.726 | 1.488780 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18451.88 | 15747.60 | 0.992520 | 27.37 | 17.37 | 0.00827715 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.7290 | 23.89 | 0.00787550 | 42.7099 | 16847.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 36105.010 | 36105.010 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36105.01 | 36105.01 | 1.488782 | 19.95 | 15.02 | 0.00862960 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.8193 | 21.11 | 0.00854560 | 54.7961 | 4389.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 65882.680 | 46189.029 | 2.653100 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32941.34 | 27935.08 | 1.768733 | 27.69 | 17.54 | 0.00835535 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 23.2640 | 23.89 | 0.00790989 | 42.8937 | 30022.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 65865.995 | 65865.995 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 65865.99 | 65865.99 | 2.653096 | 19.47 | 14.75 | 0.00852617 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.5094 | 21.11 | 0.00841102 | 53.9458 | 8934.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 34819.690 | 24411.388 | 1.402190 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17409.85 | 14772.85 | 0.934793 | 27.56 | 17.49 | 0.00834101 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.0091 | 23.89 | 0.00792123 | 42.9548 | 15866.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 34686.270 | 34686.270 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 34686.27 | 34686.27 | 1.402189 | 19.55 | 14.77 | 0.00852054 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.6727 | 21.11 | 0.00841170 | 53.9500 | 4683.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 34705.890 | 24331.605 | 1.397610 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17352.94 | 14719.72 | 0.931740 | 27.57 | 17.49 | 0.00834457 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.0812 | 23.89 | 0.00792378 | 42.9685 | 15814.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 34581.501 | 34581.501 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 34581.50 | 34581.50 | 1.397606 | 19.54 | 14.77 | 0.00852006 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.7208 | 21.11 | 0.00841072 | 53.9438 | 4708.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 34928.790 | 24487.876 | 1.406580 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17464.40 | 14823.63 | 0.937720 | 27.55 | 17.48 | 0.00833774 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.9404 | 23.89 | 0.00791889 | 42.9423 | 15914.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 34822.387 | 34822.387 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 34822.39 | 34822.39 | 1.406582 | 19.53 | 14.75 | 0.00850175 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.6269 | 21.11 | 0.00839009 | 53.8132 | 5029.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 40257.280 | 28637.821 | 1.676000 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 20128.64 | 17304.48 | 1.117333 | 27.02 | 17.18 | 0.00819122 | 12.80 | 10.55 | 0.00700000 | 42.31 | 0.01078097 | 23.73 | 18.4134 | 23.89 | 0.00782883 | 42.4604 | 18968.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 40940.745 | 40940.745 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 40940.75 | 40940.75 | 1.675998 | 19.80 | 14.86 | 0.00851218 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.2756 | 21.11 | 0.00842244 | 54.0172 | 5991.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 73342.590 | 51561.308 | 2.964770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1846 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.964767 | 3.56837891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 36671.29 | 31381.37 | 1.0000 | 2.37892153 | 1.976513 | 27.38 | 17.35 | 0.00825443 | 48578.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36671.29 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 20.8184 | 23.89 | 0.00784706 | 23.89 | 0.00784706 | 42.5576 | 33547.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73143.106 | 73143.106 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.964767 | 3.56837891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 73143.11 | 73143.11 | 1.0000 | 3.56837891 | 2.964767 | 19.60 | 14.75 | 0.00847184 | 41192.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73143.11 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 13.8790 | 20.71 | 0.00836199 | 21.11 | 0.00836199 | 53.6356 | 9153.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36991.240 | 25993.374 | 1.493340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2207 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.493342 | 1.79737926 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18495.62 | 15789.93 | 1.0000 | 1.19825102 | 0.995560 | 27.36 | 17.36 | 0.00827384 | 48608.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18495.62 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.6657 | 23.89 | 0.00787311 | 23.89 | 0.00787311 | 42.6971 | 16900.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36209.213 | 36209.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.493342 | 1.79737926 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36209.21 | 36209.21 | 1.0000 | 1.79737926 | 1.493342 | 19.95 | 15.03 | 0.00863588 | 41966.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36209.21 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.7771 | 21.11 | 0.00855318 | 21.11 | 0.00855318 | 54.8441 | 4216.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36989.900 | 25992.433 | 1.493260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2209 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.493258 | 1.79727828 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18494.95 | 15789.14 | 1.0000 | 1.19818683 | 0.995507 | 27.36 | 17.36 | 0.00827397 | 48608.7 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18494.95 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.6668 | 23.89 | 0.00787323 | 23.89 | 0.00787323 | 42.6977 | 16899.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36207.272 | 36207.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.493258 | 1.79727828 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36207.27 | 36207.27 | 1.0000 | 1.79727828 | 1.493258 | 19.95 | 15.03 | 0.00863851 | 41973.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36207.27 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.7779 | 21.11 | 0.00855623 | 21.11 | 0.00855623 | 54.8634 | 4232.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37052.900 | 26040.778 | 1.496500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2168 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.496504 | 1.80118509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18526.45 | 15819.38 | 1.0000 | 1.20078659 | 0.997667 | 27.36 | 17.36 | 0.00827175 | 48597.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18526.45 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.6221 | 23.89 | 0.00787165 | 23.89 | 0.00787165 | 42.6893 | 16935.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36281.427 | 36281.427 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.496504 | 1.80118509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36281.43 | 36281.43 | 1.0000 | 1.80118509 | 1.496504 | 19.95 | 15.03 | 0.00863634 | 41970.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36281.43 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.7480 | 21.11 | 0.00855392 | 21.11 | 0.00855392 | 54.8487 | 4270.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36903.760 | 25888.726 | 1.488780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2268 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.488782 | 1.79189065 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18451.88 | 15747.60 | 1.0000 | 1.19459209 | 0.992520 | 27.37 | 17.37 | 0.00827715 | 48624.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18451.88 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.7290 | 23.89 | 0.00787550 | 23.89 | 0.00787550 | 42.7099 | 16847.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36105.010 | 36105.010 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.488782 | 1.79189065 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36105.01 | 36105.01 | 1.0000 | 1.79189065 | 1.488782 | 19.95 | 15.02 | 0.00862960 | 41947.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36105.01 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.8193 | 21.11 | 0.00854560 | 21.11 | 0.00854560 | 54.7961 | 4389.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 65882.680 | 46189.029 | 2.653100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3722 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.653096 | 3.19325246 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 32941.34 | 27935.08 | 1.0000 | 2.12883856 | 1.768733 | 27.69 | 17.54 | 0.00835535 | 49150.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32941.34 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 23.2640 | 23.89 | 0.00790989 | 23.89 | 0.00790989 | 42.8937 | 30022.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65865.995 | 65865.995 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.653096 | 3.19325246 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 65865.99 | 65865.99 | 1.0000 | 3.19325246 | 2.653096 | 19.47 | 14.75 | 0.00852617 | 41199.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65865.99 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 15.5094 | 20.72 | 0.00841102 | 21.11 | 0.00841102 | 53.9458 | 8934.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34819.690 | 24411.388 | 1.402190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3455 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.402189 | 1.68766769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17409.85 | 14772.85 | 1.0000 | 1.12511256 | 0.934793 | 27.56 | 17.49 | 0.00834101 | 48983.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17409.85 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 22.0091 | 23.89 | 0.00792123 | 23.89 | 0.00792123 | 42.9548 | 15866.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34686.270 | 34686.270 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.402189 | 1.68766769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 34686.27 | 34686.27 | 1.0000 | 1.68766769 | 1.402189 | 19.55 | 14.77 | 0.00852054 | 41260.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34686.27 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.6727 | 20.72 | 0.00841170 | 21.11 | 0.00841170 | 53.9500 | 4683.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34705.890 | 24331.605 | 1.397610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3521 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.397606 | 1.68215180 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17352.94 | 14719.72 | 1.0000 | 1.12143759 | 0.931740 | 27.57 | 17.49 | 0.00834457 | 49002.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17352.94 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 22.0812 | 23.89 | 0.00792378 | 23.89 | 0.00792378 | 42.9685 | 15814.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34581.501 | 34581.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.397606 | 1.68215180 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 34581.50 | 34581.50 | 1.0000 | 1.68215180 | 1.397606 | 19.54 | 14.77 | 0.00852006 | 41253.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34581.50 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.7208 | 20.72 | 0.00841072 | 21.11 | 0.00841072 | 53.9438 | 4708.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34928.790 | 24487.876 | 1.406580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3394 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.406582 | 1.69295535 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17464.40 | 14823.63 | 1.0000 | 1.12863509 | 0.937720 | 27.55 | 17.48 | 0.00833774 | 48966.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17464.40 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.9404 | 23.89 | 0.00791889 | 23.89 | 0.00791889 | 42.9423 | 15914.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34822.387 | 34822.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.406582 | 1.69295535 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 34822.39 | 34822.39 | 1.0000 | 1.69295535 | 1.406582 | 19.53 | 14.75 | 0.00850175 | 41196.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34822.39 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.6269 | 20.70 | 0.00839009 | 21.11 | 0.00839009 | 53.8132 | 5029.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40257.280 | 28637.821 | 1.676000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0671 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675998 | 2.01722314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 20128.64 | 17304.48 | 1.0000 | 1.34481679 | 1.117333 | 27.02 | 17.18 | 0.00819122 | 48047.7 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20128.64 | 42.31 | 0.01078097 | 23.73 | 0.20573941 | 18.4134 | 23.89 | 0.00782883 | 23.89 | 0.00782883 | 42.4604 | 18968.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40940.745 | 40940.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675998 | 2.01722314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 40940.75 | 40940.75 | 1.0000 | 2.01722314 | 1.675998 | 19.80 | 14.86 | 0.00851218 | 41500.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40940.75 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.2756 | 20.80 | 0.00842244 | 21.11 | 0.00842244 | 54.0172 | 5991.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5274.33 | 791.50 | 706.33 |
SMSTORE1 | 5061.83 | 595.33 | 531.00 |
SMSTORE2 | 4013.33 | 720.83 | 673.67 |
SMSTORE3 | 4006.33 | 714.67 | 664.50 |
SMSTORE4 | 3969.17 | 735.17 | 674.67 |
LGSTORE2 | 3557.00 | 710.33 | 666.17 |
SMSTORE5 | 3449.50 | 718.50 | 666.83 |
SMSTORE6 | 3433.17 | 728.17 | 672.67 |
SMSTORE7 | 3426.67 | 725.50 | 659.17 |
SMSTORE8 | 3554.00 | 600.17 | 519.00 |
Facility | 5419.83 | 1187.00 | 1032.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 6.50 | 0.00 | 5.00 |
SMSTORE1 | 0.00 | 0.50 | 0.00 | 0.50 |
SMSTORE2 | 0.00 | 11.83 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 13.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 11.83 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 9.83 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 8.50 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 13.50 | 0.00 | 0.00 |
Facility | 0.00 | 26.67 | 0.00 | 5.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.848 | 0.341 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.688 | 0.378 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.849 | 0.465 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.848 | 0.549 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.040 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803567.38 | 0.00 | 8803567.38 | 3720417.12 | 12523984.50 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3587555.04 | 0.00 | 3587555.04 | 2005460.50 | 5593015.54 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525577.08 | 0.00 | 3525577.08 | 2030324.42 | 5555901.50 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525576.74 | 0.00 | 3525576.74 | 2030324.42 | 5555901.17 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525577.56 | 0.00 | 3525577.56 | 2030324.42 | 5555901.99 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510487.40 | 0.00 | 6510487.40 | 3601646.44 | 10112133.84 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255237.36 | 0.00 | 3255237.36 | 2036872.93 | 5292110.29 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255237.39 | 0.00 | 3255237.39 | 2036872.93 | 5292110.32 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255236.44 | 0.00 | 3255236.44 | 2036872.93 | 5292109.36 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255322.60 | 0.00 | 3255322.60 | 2265587.09 | 5520909.68 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 366.33 |
Total Facility | 42499374.99 | 0.00 | 42499374.99 | 23794703.20 | 66294078.18 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 731.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1654 | 0.5768 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1670 | 0.0000 | 0.1670 | 0.0918 | 0.2588 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2254 | 0.6369 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1330 | 0.3388 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4302 | 0.0000 | 2.4302 | 1.3622 | 3.7924 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5197019.04 | 0.00 | 5197019.04 | 6488198.17 | 4302.67 | 0.17 | 4457.17 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715771.92 | 0.00 | 4715771.92 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 366.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2419 | 0.0000 | 0.2419 | 0.2057 | 1485.67 | 0.17 | 4354.17 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
ElectricityNet:Plant | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1448.63 | 2102.83 | 01-JAN-07:10 | 158081.00 | 10-AUG-16:00 |
Electricity:HVAC | 794.51 | 0.00 | 01-JAN-00:10 | 121742.92 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 655.46 | 0.00 | 01-JAN-00:10 | 106631.09 | 10-AUG-16:10 |
General:Cooling:Electricity | 655.46 | 0.00 | 01-JAN-00:10 | 106631.09 | 10-AUG-16:10 |
Fans:Electricity | 139.05 | 0.00 | 01-JAN-00:10 | 15111.83 | 10-AUG-16:10 |
General:Fans:Electricity | 139.05 | 0.00 | 01-JAN-00:10 | 15111.83 | 10-AUG-16:10 |
ExteriorLights:Electricity | 60.14 | 0.00 | 01-JAN-07:10 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.14 | 0.00 | 01-JAN-07:10 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 57.48 | 1211.00 | 30-APR-16:20 | 13551.85 | 01-JAN-08:10 |
WaterSystems:Electricity | 57.48 | 1211.00 | 30-APR-16:20 | 13551.85 | 01-JAN-08:10 |
Water Heater:WaterSystems:Electricity | 57.48 | 1211.00 | 30-APR-16:20 | 13551.85 | 01-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3562.01 | 0.00 | 01-JAN-00:10 | 511961.18 | 10-AUG-16:10 |
EnergyTransfer:Building | 1199.68 | 0.00 | 01-JAN-00:10 | 158919.73 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 243.65 | 0.00 | 01-JAN-00:10 | 26258.21 | 04-AUG-13:00 |
Heating:EnergyTransfer | 8.72 | 0.00 | 01-JAN-00:10 | 35204.28 | 05-AUG-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 3776.11 | 29-APR-07:20 |
General:Heating:EnergyTransfer | 8.72 | 0.00 | 01-JAN-00:10 | 35204.28 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 3776.11 | 29-APR-07:20 |
Cooling:EnergyTransfer | 1190.96 | 0.00 | 01-JAN-00:10 | 158919.73 | 16-AUG-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 243.36 | 0.00 | 01-JAN-00:10 | 26258.21 | 04-AUG-13:00 |
General:Cooling:EnergyTransfer | 1190.96 | 0.00 | 01-JAN-00:10 | 158919.73 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 243.36 | 0.00 | 01-JAN-00:10 | 26258.21 | 04-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 125.78 | 0.00 | 01-JAN-00:10 | 13310.03 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 1895.59 | 04-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 1895.59 | 04-MAY-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 125.65 | 0.00 | 01-JAN-00:10 | 13310.03 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 125.65 | 0.00 | 01-JAN-00:10 | 13310.03 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE2 | 99.38 | 0.00 | 01-JAN-00:10 | 13396.01 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.59 | 0.00 | 01-JAN-00:10 | 4148.35 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.59 | 0.00 | 01-JAN-00:10 | 4148.35 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 97.79 | 0.00 | 01-JAN-00:10 | 13396.01 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 97.79 | 0.00 | 01-JAN-00:10 | 13396.01 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 99.88 | 0.00 | 01-JAN-00:10 | 13464.80 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.58 | 0.00 | 01-JAN-00:10 | 4146.21 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.58 | 0.00 | 01-JAN-00:10 | 4146.21 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 98.30 | 0.00 | 01-JAN-00:10 | 13464.80 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 98.30 | 0.00 | 01-JAN-00:10 | 13464.80 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 97.88 | 0.00 | 01-JAN-00:10 | 13348.96 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.60 | 0.00 | 01-JAN-00:10 | 4155.01 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.60 | 0.00 | 01-JAN-00:10 | 4155.01 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 96.28 | 0.00 | 01-JAN-00:10 | 13348.96 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 96.28 | 0.00 | 01-JAN-00:10 | 13348.96 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 166.78 | 0.00 | 01-JAN-00:10 | 24176.85 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 7866.21 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 7866.21 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 165.59 | 0.00 | 01-JAN-00:10 | 24176.85 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 165.59 | 0.00 | 01-JAN-00:10 | 24176.85 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE5 | 87.27 | 0.00 | 01-JAN-00:10 | 12922.94 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.60 | 0.00 | 01-JAN-00:10 | 3964.93 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.60 | 0.00 | 01-JAN-00:10 | 3964.93 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 86.67 | 0.00 | 01-JAN-00:10 | 12922.94 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 86.67 | 0.00 | 01-JAN-00:10 | 12922.94 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 86.78 | 0.00 | 01-JAN-00:10 | 12894.66 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.61 | 0.00 | 01-JAN-00:10 | 3966.96 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.61 | 0.00 | 01-JAN-00:10 | 3966.96 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 86.18 | 0.00 | 01-JAN-00:10 | 12894.66 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 86.18 | 0.00 | 01-JAN-00:10 | 12894.66 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 87.19 | 0.00 | 01-JAN-00:10 | 13071.79 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.60 | 0.00 | 01-JAN-00:10 | 3957.68 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.60 | 0.00 | 01-JAN-00:10 | 3957.68 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 86.59 | 0.00 | 01-JAN-00:10 | 13071.79 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 86.59 | 0.00 | 01-JAN-00:10 | 13071.79 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 105.07 | 0.00 | 01-JAN-00:10 | 16231.82 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.51 | 0.00 | 01-JAN-00:10 | 3761.68 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.51 | 0.00 | 01-JAN-00:10 | 3761.68 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.56 | 0.00 | 01-JAN-00:10 | 16231.82 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.56 | 0.00 | 01-JAN-00:10 | 16231.82 | 16-AUG-12:10 |
EnergyTransfer:HVAC | 2362.34 | 0.00 | 01-JAN-00:10 | 373241.93 | 20-JUL-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2362.34 | 0.00 | 01-JAN-00:10 | 373241.93 | 20-JUL-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.285 | -243.365 | 0.000 | 0.000 | 23.219 | 95.826 | 26.249 | 18.718 | 0.000 | 32.844 | 51.175 | 0.000 | -2.646 | 0.000 | -2.306 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.134 | -125.649 | 0.000 | 0.000 | 11.608 | 57.583 | 13.125 | 9.440 | 0.000 | 18.151 | 18.041 | 0.000 | -1.336 | 0.000 | -1.098 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.593 | -97.790 | 0.000 | 0.000 | 6.967 | 40.956 | 10.421 | 9.219 | 0.000 | 17.946 | 13.306 | 0.000 | -1.431 | 0.000 | -1.187 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.582 | -98.295 | 0.000 | 0.000 | 6.967 | 40.956 | 10.421 | 9.201 | 0.000 | 17.937 | 13.853 | 0.000 | -1.436 | 0.000 | -1.186 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.603 | -96.274 | 0.000 | 0.000 | 6.968 | 40.956 | 10.421 | 9.220 | 0.000 | 17.945 | 11.748 | 0.000 | -1.412 | 0.000 | -1.175 | -0.002 |
LGSTORE2 | 0.000 | 0.000 | 1.200 | -165.584 | 0.000 | 0.000 | 23.925 | 43.277 | 19.173 | 18.481 | 0.000 | 31.622 | 32.724 | 0.000 | -2.697 | 0.000 | -2.121 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.605 | -86.666 | 0.000 | 0.000 | 11.962 | 22.197 | 9.586 | 9.284 | 0.000 | 17.984 | 17.541 | 0.000 | -1.327 | 0.000 | -1.167 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.606 | -86.176 | 0.000 | 0.000 | 11.962 | 22.197 | 9.586 | 9.290 | 0.000 | 17.986 | 17.033 | 0.000 | -1.321 | 0.000 | -1.164 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.601 | -86.593 | 0.000 | 0.000 | 11.963 | 22.197 | 9.586 | 9.273 | 0.000 | 17.981 | 17.463 | 0.000 | -1.316 | 0.000 | -1.155 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.514 | -104.557 | 0.000 | 0.000 | 11.962 | 22.197 | 9.586 | 9.090 | 0.000 | 18.925 | 35.149 | 0.000 | -1.315 | 0.000 | -1.551 | -0.001 |
Total Facility | 0.000 | 0.000 | 8.722 | -1190.949 | 0.000 | 0.000 | 127.503 | 408.342 | 128.154 | 111.218 | 0.000 | 209.321 | 228.034 | 0.000 | -16.238 | 0.000 | -14.107 | -0.005 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -58819.40 | 0.00 | 0.00 | 161.83 | 75.00 | 74.62 | 375.42 | 0.00 | 342.60 | 57789.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -30341.71 | 0.00 | 0.00 | 81.31 | 37.50 | 37.31 | 190.08 | 0.00 | 197.16 | 29798.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -31311.38 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 31339.88 | 0.00 | -102.53 | 0.00 | -0.30 | 0.00 |
SMSTORE3 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -31413.57 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 31443.17 | 0.00 | -103.58 | 0.00 | -0.34 | 0.00 |
SMSTORE4 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -31081.37 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 31108.50 | 0.00 | -101.22 | 0.00 | -0.22 | 0.00 |
LGSTORE2 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -52721.94 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 668.01 | 0.00 | 417.49 | 51487.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -27764.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 336.89 | 0.00 | 241.77 | 27111.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -27666.27 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 337.04 | 0.00 | 241.90 | 27013.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -27919.77 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 334.72 | 0.00 | 239.77 | 27270.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -33051.42 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 320.70 | 0.00 | 237.70 | 32418.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -267434.47 | 0.00 | 0.00 | 538.65 | 450.00 | 1452.23 | 2353.54 | 0.00 | 2408.42 | 260231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 05-AUG-07:05 | 0.00 | 0.00 | 7495.13 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 558.68 | 0.00 | 840.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9043.30 |
SMSTORE1 | 05-AUG-07:04 | 0.00 | 0.00 | 4011.07 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 289.85 | 0.00 | 458.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4833.68 |
SMSTORE2 | 31-MAY-19:02 | 0.00 | 0.00 | 4599.19 | 0.00 | 0.00 | 0.00 | 98.50 | 1467.90 | 373.13 | 344.40 | 0.00 | 63.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6946.57 |
SMSTORE3 | 31-MAY-19:02 | 0.00 | 0.00 | 4597.95 | 0.00 | 0.00 | 0.00 | 98.50 | 1467.90 | 373.13 | 344.19 | 0.00 | 63.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6945.12 |
SMSTORE4 | 31-MAY-19:02 | 0.00 | 0.00 | 4602.94 | 0.00 | 0.00 | 0.00 | 98.50 | 1467.90 | 373.13 | 344.61 | 0.00 | 63.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6950.54 |
LGSTORE2 | 05-AUG-17:01 | 0.00 | 0.00 | 8862.12 | 0.00 | 0.00 | 0.00 | 433.43 | 1679.80 | 746.25 | 995.56 | 0.00 | 1167.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13884.29 |
SMSTORE5 | 05-AUG-17:01 | 0.00 | 0.00 | 4450.12 | 0.00 | 0.00 | 0.00 | 216.71 | 862.24 | 373.13 | 502.30 | 0.00 | 657.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7061.64 |
SMSTORE6 | 05-AUG-17:01 | 0.00 | 0.00 | 4451.04 | 0.00 | 0.00 | 0.00 | 216.71 | 862.24 | 373.13 | 502.51 | 0.00 | 657.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7062.80 |
SMSTORE7 | 05-AUG-17:01 | 0.00 | 0.00 | 4445.83 | 0.00 | 0.00 | 0.00 | 216.71 | 862.24 | 373.13 | 501.29 | 0.00 | 656.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7056.16 |
SMSTORE8 | 05-AUG-17:01 | 0.00 | 0.00 | 4327.88 | 0.00 | 0.00 | 0.00 | 216.71 | 862.24 | 373.13 | 487.78 | 0.00 | 754.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7022.59 |
Total Facility | 05-AUG-17:01 | -26296.18 | 26296.18 | 39749.01 | -26296.18 | 0.00 | 0.00 | 4550.99 | 17682.08 | 5373.00 | 5994.98 | 0.00 | 7838.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54892.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9648 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9648 | 0.1388 | 1.0000 | Not calculated | 0.4115 | 0.1388 | ||
PSZ-AC_2:2 | 1.4933 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4933 | 0.1378 | 1.0000 | Not calculated | 0.2057 | 0.1378 | ||
PSZ-AC_3:3 | 1.4933 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4933 | 0.1378 | 1.0000 | Not calculated | 0.2057 | 0.1378 | ||
PSZ-AC_4:4 | 1.4965 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4965 | 0.1375 | 1.0000 | Not calculated | 0.2057 | 0.1375 | ||
PSZ-AC_5:5 | 1.4888 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4888 | 0.1382 | 1.0000 | Not calculated | 0.2057 | 0.1382 | ||
PSZ-AC_6:6 | 2.6531 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6531 | 0.1551 | 1.0000 | Not calculated | 0.4115 | 0.1551 | ||
PSZ-AC_7:7 | 1.4022 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4022 | 0.1467 | 1.0000 | Not calculated | 0.2057 | 0.1467 | ||
PSZ-AC_8:8 | 1.3976 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3976 | 0.1472 | 1.0000 | Not calculated | 0.2057 | 0.1472 | ||
PSZ-AC_9:9 | 1.4066 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4066 | 0.1463 | 1.0000 | Not calculated | 0.2057 | 0.1463 | ||
PSZ-AC_10:10 | 1.6760 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6760 | 0.1228 | 1.0000 | Not calculated | 0.2057 | 0.1228 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9648 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9648 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1388 | ||
PSZ-AC_2:2 | 1.4933 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4933 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1378 | ||
PSZ-AC_3:3 | 1.4933 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4933 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1378 | ||
PSZ-AC_4:4 | 1.4965 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4965 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1375 | ||
PSZ-AC_5:5 | 1.4888 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4888 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1382 | ||
PSZ-AC_6:6 | 2.6531 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6531 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1551 | ||
PSZ-AC_7:7 | 1.4022 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4022 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1467 | ||
PSZ-AC_8:8 | 1.3976 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3976 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1472 | ||
PSZ-AC_9:9 | 1.4066 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4066 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1463 | ||
PSZ-AC_10:10 | 1.6760 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6760 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1228 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9648 | 2.9648 | 2.9648 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4933 | 1.4933 | 1.4933 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4933 | 1.4933 | 1.4933 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4965 | 1.4965 | 1.4965 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4888 | 1.4888 | 1.4888 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6531 | 2.6531 | 2.6531 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4022 | 1.4022 | 1.4022 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3976 | 1.3976 | 1.3976 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4066 | 1.4066 | 1.4066 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6760 | 1.6760 | 1.6760 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9648 | 2.9648 | 2.9648 | 2.9648 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4933 | 1.4933 | 1.4933 | 1.4933 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4933 | 1.4933 | 1.4933 | 1.4933 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4965 | 1.4965 | 1.4965 | 1.4965 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4888 | 1.4888 | 1.4888 | 1.4888 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6531 | 2.6531 | 2.6531 | 2.6531 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4022 | 1.4022 | 1.4022 | 1.4022 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3976 | 1.3976 | 1.3976 | 1.3976 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4066 | 1.4066 | 1.4066 | 1.4066 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6760 | 1.6760 | 1.6760 | 1.6760 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9648 | 2.9648 | 2.9648 | No | 0.4115 | 0.9051 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4933 | 1.4933 | 1.4933 | No | 0.2057 | 0.9426 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4933 | 1.4933 | 1.4933 | No | 0.2057 | 0.9392 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4965 | 1.4965 | 1.4965 | No | 0.2057 | 0.9307 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4888 | 1.4888 | 1.4888 | No | 0.2057 | 0.9055 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6531 | 2.6531 | 2.6531 | No | 0.4115 | 0.9284 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4022 | 1.4022 | 1.4022 | No | 0.2057 | 0.8815 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3976 | 1.3976 | 1.3976 | No | 0.2057 | 0.8770 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4066 | 1.4066 | 1.4066 | No | 0.2057 | 0.8221 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6760 | 1.6760 | 1.6760 | No | 0.2057 | 0.6857 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9648 | 2.9648 | 2.9648 | 2.9648 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4933 | 1.4933 | 1.4933 | 1.4933 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4933 | 1.4933 | 1.4933 | 1.4933 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4965 | 1.4965 | 1.4965 | 1.4965 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4888 | 1.4888 | 1.4888 | 1.4888 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6531 | 2.6531 | 2.6531 | 2.6531 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4022 | 1.4022 | 1.4022 | 1.4022 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3976 | 1.3976 | 1.3976 | 1.3976 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4066 | 1.4066 | 1.4066 | 1.4066 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6760 | 1.6760 | 1.6760 | 1.6760 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 5.00 |
Number of hours not met | 5.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 655.46 | 106631.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.14 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 139.05 | 15111.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.48 | 13551.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1448.63 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1448.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 313.57 |
Fans (All) | 66.52 |
Service Water Heating | 27.50 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 693.02 |
Subtotal | 693.02 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.19 |
Space Heating | 0.00 |
Space Cooling | 45.25 |
Fans (All) | 9.60 |
Service Water Heating | 3.97 |
Receptacle Equipment | 8.85 |
Miscellaneous | 4.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 7986.33 | 773.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8284.50 | 475.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6756.50 | 1970.83 | 32.67 | 0.00 | 0.00 |
SMSTORE3 | 6691.00 | 2023.67 | 45.33 | 0.00 | 0.00 |
SMSTORE4 | 6789.83 | 1925.50 | 44.67 | 0.00 | 0.00 |
LGSTORE2 | 7241.50 | 1472.33 | 46.17 | 0.00 | 0.00 |
SMSTORE5 | 7364.50 | 1349.17 | 46.33 | 0.00 | 0.00 |
SMSTORE6 | 7376.33 | 1337.50 | 46.17 | 0.00 | 0.00 |
SMSTORE7 | 7359.17 | 1353.50 | 47.33 | 0.00 | 0.00 |
SMSTORE8 | 6897.00 | 1689.83 | 173.17 | 0.00 | 0.00 |
Min | 6691.00 | 475.50 | 0.00 | 0.00 | 0.00 |
Max | 8284.50 | 2023.67 | 173.17 | 0.00 | 0.00 |
Average | 7274.67 | 1437.15 | 48.18 | 0.00 | 0.00 |
Sum | 72746.67 | 14371.50 | 481.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25320.00 | 152.33 | 2.67 | 0.00 | 0.00 |
SMSTORE3 | 25319.83 | 152.50 | 2.67 | 0.00 | 0.00 |
SMSTORE4 | 25321.83 | 150.67 | 2.50 | 0.00 | 0.00 |
LGSTORE2 | 92887.00 | 308.00 | 16.00 | 0.00 | 0.00 |
SMSTORE5 | 45750.00 | 153.50 | 8.50 | 0.00 | 0.00 |
SMSTORE6 | 45750.00 | 153.50 | 8.50 | 0.00 | 0.00 |
SMSTORE7 | 45750.00 | 154.00 | 8.00 | 0.00 | 0.00 |
SMSTORE8 | 45733.50 | 169.50 | 9.00 | 0.00 | 0.00 |
Min | 25319.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92887.00 | 308.00 | 16.00 | 0.00 | 0.00 |
Average | 48465.02 | 139.40 | 5.78 | 0.00 | 0.00 |
Sum | 484650.17 | 1394.00 | 57.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6476.33 | 2283.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7407.67 | 1352.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5046.17 | 3687.33 | 26.50 | 0.00 | 0.00 |
SMSTORE3 | 5059.17 | 3671.83 | 29.00 | 0.00 | 0.00 |
SMSTORE4 | 5087.83 | 3645.50 | 26.67 | 0.00 | 0.00 |
LGSTORE2 | 5263.50 | 3467.83 | 28.67 | 0.00 | 0.00 |
SMSTORE5 | 5318.00 | 3409.67 | 32.33 | 0.00 | 0.00 |
SMSTORE6 | 5317.50 | 3409.83 | 32.67 | 0.00 | 0.00 |
SMSTORE7 | 5354.17 | 3370.67 | 35.17 | 0.00 | 0.00 |
SMSTORE8 | 5341.33 | 3317.83 | 100.83 | 0.00 | 0.00 |
Min | 5046.17 | 1352.33 | 0.00 | 0.00 | 0.00 |
Max | 7407.67 | 3687.33 | 100.83 | 0.00 | 0.00 |
Average | 5567.17 | 3161.65 | 31.18 | 0.00 | 0.00 |
Sum | 55671.67 | 31616.50 | 311.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 80190.67 | 8850.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 39491.33 | 4285.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 22131.17 | 3343.33 | 0.50 | 0.00 | 0.00 |
SMSTORE3 | 22178.17 | 3296.33 | 0.50 | 0.00 | 0.00 |
SMSTORE4 | 22117.00 | 3357.50 | 0.50 | 0.00 | 0.00 |
LGSTORE2 | 78976.50 | 14231.50 | 3.00 | 0.00 | 0.00 |
SMSTORE5 | 38798.67 | 7111.83 | 1.50 | 0.00 | 0.00 |
SMSTORE6 | 38735.67 | 7174.83 | 1.50 | 0.00 | 0.00 |
SMSTORE7 | 38867.33 | 7043.17 | 1.50 | 0.00 | 0.00 |
SMSTORE8 | 40520.50 | 5390.00 | 1.50 | 0.00 | 0.00 |
Min | 22117.00 | 3296.33 | 0.00 | 0.00 | 0.00 |
Max | 80190.67 | 14231.50 | 3.00 | 0.00 | 0.00 |
Average | 42200.70 | 6408.45 | 1.05 | 0.00 | 0.00 |
Sum | 422007.00 | 64084.50 | 10.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108390E+11 | 17316.32 | 30-JAN-08:63 | 20.33 | 17.75 | 0.140785E+10 | 1685.99 | 22-JAN-13:00 | 20.33 | 17.75 |
February | 0.110975E+11 | 31226.67 | 09-FEB-08:62 | 22.17 | 19.26 | 0.127180E+10 | 1686.04 | 05-FEB-13:09 | 22.17 | 19.26 |
March | 0.143683E+11 | 55717.54 | 02-MAR-08:62 | 27.00 | 17.55 | 0.139709E+10 | 1686.02 | 26-MAR-17:00 | 31.00 | 18.89 |
April | 0.173950E+11 | 54091.81 | 29-APR-07:02 | 27.25 | 16.62 | 0.136160E+10 | 1686.04 | 15-APR-12:20 | 27.25 | 16.62 |
May | 0.237206E+11 | 58824.06 | 11-MAY-07:01 | 30.33 | 16.47 | 0.140188E+10 | 1686.05 | 07-MAY-17:49 | 30.33 | 16.47 |
June | 0.252010E+11 | 51416.47 | 01-JUN-07:01 | 30.17 | 21.35 | 0.135493E+10 | 1686.09 | 02-JUN-12:00 | 38.60 | 24.59 |
July | 0.287262E+11 | 57547.03 | 04-JUL-07:01 | 31.33 | 17.56 | 0.141322E+10 | 1686.16 | 04-JUL-12:20 | 39.90 | 23.87 |
August | 0.299141E+11 | 51768.79 | 06-AUG-07:01 | 35.08 | 22.69 | 0.139459E+10 | 1686.11 | 06-AUG-17:30 | 39.50 | 26.07 |
September | 0.262876E+11 | 48376.18 | 02-SEP-07:01 | 32.25 | 23.03 | 0.136557E+10 | 1686.11 | 15-SEP-12:09 | 37.12 | 24.73 |
October | 0.239899E+11 | 55908.34 | 20-OCT-07:02 | 23.25 | 15.43 | 0.141002E+10 | 1686.11 | 01-OCT-12:09 | 23.25 | 15.43 |
November | 0.184667E+11 | 55641.04 | 05-NOV-07:02 | 21.17 | 15.81 | 0.136323E+10 | 1686.07 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.133584E+11 | 46580.04 | 12-DEC-08:62 | 23.17 | 17.37 | 0.141633E+10 | 1686.06 | 01-DEC-13:00 | 23.17 | 17.37 |
Annual Sum or Average | 0.243364E+12 | 0.165581E+11 | ||||||||
Minimum of Months | 0.108390E+11 | 17316.32 | 20.33 | 15.43 | 0.127180E+10 | 1685.99 | 20.33 | 15.43 | ||
Maximum of Months | 0.299141E+11 | 58824.06 | 35.08 | 23.03 | 0.141633E+10 | 1686.16 | 39.90 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.615617E+10 | 10699.07 | 30-JAN-08:63 | 20.33 | 17.75 | 0.704286E+09 | 843.27 | 22-JAN-18:30 | 20.33 | 17.75 |
February | 0.620671E+10 | 18046.21 | 09-FEB-08:62 | 22.17 | 19.26 | 0.636076E+09 | 843.18 | 20-FEB-18:49 | 17.75 | 16.28 |
March | 0.785239E+10 | 28684.64 | 02-MAR-08:62 | 27.00 | 17.55 | 0.698654E+09 | 843.17 | 19-MAR-17:19 | 24.00 | 17.68 |
April | 0.924527E+10 | 28291.42 | 29-APR-07:02 | 27.25 | 16.62 | 0.680794E+09 | 843.15 | 02-APR-17:40 | 27.25 | 16.62 |
May | 0.121338E+11 | 30342.78 | 11-MAY-07:01 | 30.33 | 16.47 | 0.700919E+09 | 843.04 | 29-MAY-17:49 | 36.00 | 23.54 |
June | 0.127057E+11 | 28433.07 | 02-JUN-07:01 | 29.67 | 18.04 | 0.677437E+09 | 843.04 | 18-JUN-12:09 | 36.78 | 25.76 |
July | 0.143334E+11 | 30032.63 | 04-JUL-07:01 | 31.33 | 17.56 | 0.706568E+09 | 843.06 | 02-JUL-12:30 | 31.33 | 17.56 |
August | 0.147622E+11 | 27492.17 | 06-AUG-07:01 | 35.08 | 22.69 | 0.697242E+09 | 843.02 | 06-AUG-17:00 | 39.00 | 25.96 |
September | 0.131358E+11 | 27358.81 | 26-SEP-07:01 | 27.00 | 17.98 | 0.682748E+09 | 843.03 | 24-SEP-12:50 | 27.00 | 17.98 |
October | 0.121719E+11 | 30021.58 | 20-OCT-07:02 | 23.25 | 15.43 | 0.704986E+09 | 843.18 | 09-OCT-17:00 | 23.25 | 15.43 |
November | 0.960988E+10 | 29858.84 | 05-NOV-07:02 | 21.17 | 15.81 | 0.681595E+09 | 843.22 | 05-NOV-17:19 | 30.67 | 21.79 |
December | 0.733679E+10 | 26177.43 | 12-DEC-08:62 | 23.17 | 17.37 | 0.708243E+09 | 843.25 | 03-DEC-18:40 | 23.17 | 17.37 |
Annual Sum or Average | 0.125650E+12 | 0.827955E+10 | ||||||||
Minimum of Months | 0.615617E+10 | 10699.07 | 20.33 | 15.43 | 0.636076E+09 | 843.02 | 17.75 | 15.43 | ||
Maximum of Months | 0.147622E+11 | 30342.78 | 35.08 | 22.69 | 0.708243E+09 | 843.27 | 39.00 | 25.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429293E+10 | 10899.97 | 30-JAN-07:03 | 20.17 | 17.39 | 0.419245E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.446548E+10 | 18976.35 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381317E+09 | 842.90 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.586700E+10 | 31312.70 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431381E+09 | 843.00 | 25-MAR-12:50 | 24.00 | 14.40 |
April | 0.700729E+10 | 29081.61 | 29-APR-06:02 | 25.25 | 16.39 | 0.411231E+09 | 843.02 | 08-APR-12:39 | 25.25 | 16.39 |
May | 0.963478E+10 | 29657.55 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427188E+09 | 842.94 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.102474E+11 | 27980.11 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418160E+09 | 843.00 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.114565E+11 | 29318.12 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421615E+09 | 843.04 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.120846E+11 | 24223.02 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433231E+09 | 842.90 | 26-AUG-12:30 | 37.15 | 27.22 |
September | 0.105083E+11 | 22437.60 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412103E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.958497E+10 | 28471.93 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421488E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.737333E+10 | 28060.88 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406629E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.526888E+10 | 23976.81 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419559E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.977915E+11 | 0.500315E+10 | ||||||||
Minimum of Months | 0.429293E+10 | 10899.97 | 20.17 | 14.40 | 0.381317E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.120846E+11 | 31312.70 | 33.90 | 25.20 | 0.433231E+09 | 843.04 | 39.80 | 27.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422404E+10 | 10630.07 | 30-JAN-07:03 | 20.17 | 17.39 | 0.419165E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.442448E+10 | 18990.14 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381284E+09 | 842.90 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.584550E+10 | 31414.86 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431364E+09 | 843.00 | 25-MAR-12:50 | 24.00 | 14.40 |
April | 0.702565E+10 | 29195.69 | 29-APR-06:02 | 25.25 | 16.39 | 0.411231E+09 | 843.01 | 08-APR-12:30 | 25.25 | 16.39 |
May | 0.971635E+10 | 29776.10 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427194E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.103419E+11 | 28153.47 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418168E+09 | 843.00 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.115853E+11 | 29516.65 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421625E+09 | 843.05 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.122117E+11 | 24397.52 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433241E+09 | 842.90 | 26-AUG-12:09 | 37.05 | 27.29 |
September | 0.106129E+11 | 22785.82 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412111E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.966895E+10 | 28583.51 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421495E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.739959E+10 | 28175.64 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406629E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.524026E+10 | 24016.75 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419539E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.982966E+11 | 0.500305E+10 | ||||||||
Minimum of Months | 0.422404E+10 | 10630.07 | 20.17 | 14.40 | 0.381284E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.122117E+11 | 31414.86 | 33.90 | 25.20 | 0.433241E+09 | 843.05 | 39.80 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400453E+10 | 9433.05 | 30-JAN-07:03 | 20.17 | 17.39 | 0.418974E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.423460E+10 | 17558.96 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381191E+09 | 842.91 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.563643E+10 | 31082.84 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431292E+09 | 843.00 | 25-MAR-12:00 | 24.00 | 14.40 |
April | 0.684125E+10 | 28851.77 | 29-APR-06:02 | 25.25 | 16.39 | 0.411196E+09 | 843.01 | 22-APR-12:00 | 25.25 | 16.39 |
May | 0.955822E+10 | 29432.88 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427163E+09 | 842.94 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.101919E+11 | 27784.14 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418137E+09 | 843.00 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.114579E+11 | 29168.25 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421598E+09 | 843.05 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.120792E+11 | 24083.12 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433213E+09 | 842.90 | 26-AUG-12:30 | 37.15 | 27.22 |
September | 0.104788E+11 | 22603.84 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412083E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.952273E+10 | 28280.28 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421464E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.723040E+10 | 27899.92 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406597E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.503932E+10 | 23734.44 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419468E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.962753E+11 | 0.500238E+10 | ||||||||
Minimum of Months | 0.400453E+10 | 9433.05 | 20.17 | 14.40 | 0.381191E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.120792E+11 | 31082.84 | 33.90 | 25.20 | 0.433213E+09 | 843.05 | 39.80 | 27.22 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641290E+10 | 15657.25 | 29-JAN-09:03 | 23.22 | 19.02 | 0.143181E+10 | 2247.99 | 28-JAN-15:09 | 23.22 | 19.02 |
February | 0.694935E+10 | 30089.63 | 06-FEB-08:62 | 21.17 | 17.80 | 0.130513E+10 | 2247.97 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.945953E+10 | 47952.78 | 28-MAR-07:02 | 24.33 | 12.69 | 0.147913E+10 | 2247.80 | 11-MAR-15:00 | 24.33 | 12.69 |
April | 0.116573E+11 | 50648.96 | 29-APR-07:02 | 27.25 | 16.62 | 0.141071E+10 | 2247.91 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.165859E+11 | 52345.10 | 11-MAY-07:01 | 30.33 | 16.47 | 0.145949E+10 | 2247.89 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.177528E+11 | 48567.38 | 01-JUN-07:01 | 30.17 | 21.35 | 0.143151E+10 | 2247.81 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.200352E+11 | 52724.09 | 04-JUL-08:61 | 32.82 | 19.26 | 0.144093E+10 | 2247.81 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.212070E+11 | 43070.40 | 16-AUG-07:01 | 33.67 | 25.11 | 0.148205E+10 | 2247.81 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.182798E+11 | 42220.64 | 26-SEP-07:01 | 27.00 | 17.98 | 0.141221E+10 | 2248.17 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.165348E+11 | 51389.95 | 20-OCT-07:02 | 23.25 | 15.43 | 0.143711E+10 | 2247.97 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.123840E+11 | 49256.87 | 19-NOV-09:02 | 25.40 | 16.09 | 0.138297E+10 | 2247.98 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.832642E+10 | 43434.75 | 12-DEC-08:62 | 23.17 | 17.37 | 0.143684E+10 | 2247.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.165585E+12 | 0.171099E+11 | ||||||||
Minimum of Months | 0.641290E+10 | 15657.25 | 21.17 | 12.69 | 0.130513E+10 | 2247.80 | 21.17 | 12.69 | ||
Maximum of Months | 0.212070E+11 | 52724.09 | 33.67 | 25.11 | 0.148205E+10 | 2248.17 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324121E+10 | 7477.70 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715910E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.355170E+10 | 14865.78 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652553E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.488760E+10 | 24939.94 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739549E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.609863E+10 | 25622.32 | 29-APR-07:02 | 27.25 | 16.62 | 0.705322E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.873575E+10 | 27495.82 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729701E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.935486E+10 | 25593.45 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715708E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.105766E+11 | 27765.77 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720419E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.111747E+11 | 22683.12 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740985E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.962407E+10 | 22163.00 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706057E+09 | 1124.04 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.868373E+10 | 26947.05 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718518E+09 | 1123.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.646185E+10 | 25818.17 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691459E+09 | 1123.96 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.427571E+10 | 21834.47 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718411E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.866664E+11 | 0.855459E+10 | ||||||||
Minimum of Months | 0.324121E+10 | 7477.70 | 20.33 | 15.43 | 0.652553E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.111747E+11 | 27765.77 | 33.67 | 25.11 | 0.740985E+09 | 1124.04 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318531E+10 | 7176.72 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715836E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.350143E+10 | 14512.87 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652514E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.483335E+10 | 24827.97 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739528E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.605423E+10 | 25347.59 | 29-APR-07:02 | 27.25 | 16.62 | 0.705316E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.869822E+10 | 27388.20 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729697E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.932001E+10 | 25489.65 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715704E+09 | 1123.87 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.105468E+11 | 27667.45 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720415E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.111448E+11 | 22595.94 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740984E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.959376E+10 | 22075.30 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706052E+09 | 1124.04 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.864957E+10 | 26843.47 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718513E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.642166E+10 | 25719.96 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691454E+09 | 1123.96 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.422677E+10 | 21491.24 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718390E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.861759E+11 | 0.855440E+10 | ||||||||
Minimum of Months | 0.318531E+10 | 7176.72 | 20.33 | 15.43 | 0.652514E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.111448E+11 | 27667.45 | 33.67 | 25.11 | 0.740984E+09 | 1124.04 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306082E+10 | 6225.51 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715578E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.339567E+10 | 13398.08 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652371E+09 | 1123.96 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.473906E+10 | 24900.13 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739455E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.602824E+10 | 24983.95 | 29-APR-07:02 | 27.25 | 16.62 | 0.705313E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.877776E+10 | 27551.15 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729706E+09 | 1123.92 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.943685E+10 | 25673.91 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715714E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.107193E+11 | 27920.93 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720429E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.113522E+11 | 22874.35 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740993E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.974300E+10 | 22272.20 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706066E+09 | 1124.05 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.875393E+10 | 27016.48 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718523E+09 | 1123.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.644119E+10 | 25372.22 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691455E+09 | 1123.97 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.414489E+10 | 20674.74 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718325E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.865929E+11 | 0.855393E+10 | ||||||||
Minimum of Months | 0.306082E+10 | 6225.51 | 20.33 | 15.43 | 0.652371E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.113522E+11 | 27920.93 | 33.67 | 25.11 | 0.740993E+09 | 1124.05 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327734E+10 | 6111.71 | 28-JAN-14:00 | 28.00 | 13.07 | 0.715206E+09 | 1123.95 | 28-JAN-15:09 | 25.75 | 18.22 |
February | 0.368105E+10 | 10491.18 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652115E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.527577E+10 | 30465.40 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739300E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.707659E+10 | 25708.23 | 29-APR-07:02 | 27.25 | 16.62 | 0.705453E+09 | 1123.94 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.107566E+11 | 32284.76 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729882E+09 | 1123.93 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.116683E+11 | 29090.10 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715881E+09 | 1123.87 | 03-JUN-14:09 | 38.67 | 24.77 |
July | 0.133430E+11 | 33052.58 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720613E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.143263E+11 | 27327.20 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741133E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.121375E+11 | 25846.23 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706289E+09 | 1124.09 | 23-SEP-14:20 | 27.00 | 17.98 |
October | 0.107417E+11 | 30596.03 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718733E+09 | 1123.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.768486E+10 | 28936.84 | 05-NOV-08:62 | 24.50 | 17.35 | 0.691583E+09 | 1123.97 | 04-NOV-14:09 | 24.50 | 17.35 |
December | 0.458934E+10 | 20380.63 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718293E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.104558E+12 | 0.855448E+10 | ||||||||
Minimum of Months | 0.327734E+10 | 6111.71 | 21.17 | 13.07 | 0.652115E+09 | 1123.87 | 21.17 | 13.98 | ||
Maximum of Months | 0.143263E+11 | 33052.58 | 36.17 | 23.08 | 0.741133E+09 | 1124.09 | 38.67 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 729495.59 | 1115.18 | 29-JAN-08:07 | 22.17 |
February | 2818878.14 | 1662.21 | 09-FEB-08:05 | 22.17 |
March | 13807857.74 | 3531.92 | 27-MAR-07:05 | 26.50 |
April | 32522094.27 | 4729.06 | 29-APR-07:04 | 27.25 |
May | 51289981.08 | 5333.47 | 11-MAY-07:04 | 30.33 |
June | 36354157.50 | 5853.69 | 11-JUN-07:04 | 31.92 |
July | 22640074.38 | 6753.99 | 19-JUL-07:06 | 33.75 |
August | 23916235.86 | 7495.76 | 05-AUG-07:05 | 35.67 |
September | 29094503.48 | 6209.40 | 02-SEP-07:04 | 32.25 |
October | 37917823.61 | 4138.66 | 06-OCT-07:04 | 27.43 |
November | 30128308.41 | 3477.76 | 25-NOV-08:04 | 25.33 |
December | 3923141.45 | 2455.09 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.285143E+09 | |||
Minimum of Months | 729495.59 | 1115.18 | 22.17 | |
Maximum of Months | 51289981.08 | 7495.76 | 35.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 421792.73 | 706.18 | 29-JAN-08:07 | 22.17 |
February | 1505915.45 | 955.19 | 09-FEB-08:05 | 22.17 |
March | 7317710.06 | 2106.06 | 02-MAR-08:03 | 27.00 |
April | 17152786.09 | 2444.02 | 29-APR-07:04 | 27.25 |
May | 22474306.33 | 2591.03 | 11-MAY-07:04 | 30.33 |
June | 15346352.27 | 3571.29 | 05-JUN-07:04 | 34.50 |
July | 11879109.61 | 3510.58 | 19-JUL-07:04 | 33.75 |
August | 11229128.25 | 4011.12 | 05-AUG-07:04 | 35.67 |
September | 12258347.43 | 2938.33 | 04-SEP-07:04 | 31.55 |
October | 16267870.19 | 2093.33 | 06-OCT-07:04 | 27.43 |
November | 15764830.75 | 1859.66 | 25-NOV-08:04 | 25.33 |
December | 2181409.02 | 1378.68 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.133800E+09 | |||
Minimum of Months | 421792.73 | 706.18 | 22.17 | |
Maximum of Months | 22474306.33 | 4011.12 | 35.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1268354.45 | 689.09 | 29-JAN-08:07 | 22.17 |
February | 9926714.93 | 1932.34 | 05-FEB-17:12 | 31.00 |
March | 34245552.07 | 2188.04 | 27-MAR-19:12 | 31.67 |
April | 0.100469E+09 | 2589.97 | 29-APR-17:02 | 33.67 |
May | 0.220208E+09 | 4599.18 | 31-MAY-19:02 | 41.85 |
June | 0.230818E+09 | 3785.87 | 09-JUN-19:02 | 38.25 |
July | 0.262096E+09 | 4386.65 | 21-JUL-19:02 | 41.00 |
August | 0.269000E+09 | 4404.04 | 10-AUG-19:02 | 40.92 |
September | 0.205571E+09 | 4288.55 | 04-SEP-16:01 | 40.58 |
October | 0.174519E+09 | 3310.08 | 09-OCT-16:01 | 36.67 |
November | 74723516.00 | 2009.76 | 05-NOV-16:02 | 31.33 |
December | 10085953.29 | 1260.25 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.159293E+10 | |||
Minimum of Months | 1268354.45 | 689.09 | 22.17 | |
Maximum of Months | 0.269000E+09 | 4599.18 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1294805.36 | 672.12 | 29-JAN-08:07 | 22.17 |
February | 10005998.95 | 1934.79 | 05-FEB-17:12 | 31.00 |
March | 34352869.56 | 2189.05 | 27-MAR-19:12 | 31.67 |
April | 0.100333E+09 | 2589.44 | 29-APR-17:02 | 33.67 |
May | 0.218168E+09 | 4597.95 | 31-MAY-19:02 | 41.85 |
June | 0.229167E+09 | 3785.48 | 09-JUN-19:02 | 38.25 |
July | 0.259418E+09 | 4385.44 | 21-JUL-19:02 | 41.00 |
August | 0.267175E+09 | 4403.28 | 10-AUG-19:02 | 40.92 |
September | 0.203832E+09 | 4284.97 | 04-SEP-16:01 | 40.58 |
October | 0.173510E+09 | 3307.38 | 09-OCT-16:01 | 36.67 |
November | 74642126.24 | 2008.91 | 05-NOV-16:02 | 31.33 |
December | 10171330.94 | 1265.09 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.158207E+10 | |||
Minimum of Months | 1294805.36 | 672.12 | 22.17 | |
Maximum of Months | 0.267175E+09 | 4597.95 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1337803.94 | 597.52 | 29-JAN-08:07 | 22.17 |
February | 10244100.25 | 1938.28 | 05-FEB-17:12 | 31.00 |
March | 35158297.45 | 2192.56 | 27-MAR-19:12 | 31.67 |
April | 0.101976E+09 | 2596.50 | 29-APR-17:02 | 33.67 |
May | 0.221308E+09 | 4602.93 | 31-MAY-19:02 | 41.85 |
June | 0.231599E+09 | 3791.11 | 09-JUN-19:02 | 38.25 |
July | 0.262701E+09 | 4391.01 | 21-JUL-19:02 | 41.00 |
August | 0.270732E+09 | 4408.85 | 10-AUG-19:02 | 40.92 |
September | 0.206370E+09 | 4286.83 | 04-SEP-16:01 | 40.58 |
October | 0.174608E+09 | 3309.90 | 09-OCT-16:01 | 36.67 |
November | 76033644.47 | 2013.81 | 05-NOV-16:02 | 31.33 |
December | 10570784.84 | 1258.20 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.160264E+10 | |||
Minimum of Months | 1337803.94 | 597.52 | 22.17 | |
Maximum of Months | 0.270732E+09 | 4602.93 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2902640.48 | 1405.74 | 29-JAN-09:07 | 23.22 |
February | 16726907.56 | 3905.22 | 05-FEB-17:02 | 31.00 |
March | 33431654.11 | 4158.62 | 26-MAR-16:02 | 31.70 |
April | 0.116821E+09 | 5255.24 | 29-APR-17:02 | 33.67 |
May | 0.175258E+09 | 7118.91 | 21-MAY-16:01 | 37.42 |
June | 0.157175E+09 | 6924.44 | 04-JUN-16:01 | 36.83 |
July | 0.178778E+09 | 8450.93 | 29-JUL-17:01 | 40.00 |
August | 0.129764E+09 | 8861.07 | 05-AUG-17:01 | 40.83 |
September | 0.150759E+09 | 8633.65 | 04-SEP-16:01 | 40.58 |
October | 0.144448E+09 | 6672.88 | 09-OCT-16:01 | 36.67 |
November | 78352997.66 | 4085.84 | 05-NOV-16:02 | 31.33 |
December | 15337104.95 | 2140.66 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.119975E+10 | |||
Minimum of Months | 2902640.48 | 1405.74 | 23.17 | |
Maximum of Months | 0.178778E+09 | 8861.07 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1820859.65 | 743.38 | 29-JAN-09:07 | 23.22 |
February | 9003716.60 | 1963.41 | 05-FEB-17:02 | 31.00 |
March | 17863474.72 | 2085.95 | 26-MAR-16:02 | 31.70 |
April | 61133141.93 | 2648.46 | 29-APR-17:02 | 33.67 |
May | 84539817.73 | 3566.47 | 21-MAY-16:01 | 37.42 |
June | 76487702.62 | 3470.09 | 04-JUN-16:01 | 36.83 |
July | 91695058.34 | 4246.08 | 29-JUL-17:01 | 40.00 |
August | 64942609.21 | 4449.59 | 05-AUG-17:01 | 40.83 |
September | 74824315.69 | 4318.47 | 04-SEP-16:01 | 40.58 |
October | 71512497.34 | 3342.36 | 09-OCT-16:01 | 36.67 |
November | 41869275.56 | 2054.11 | 05-NOV-16:02 | 31.33 |
December | 8717448.01 | 1175.63 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.604410E+09 | |||
Minimum of Months | 1820859.65 | 743.38 | 23.17 | |
Maximum of Months | 91695058.34 | 4449.59 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1834337.66 | 725.08 | 29-JAN-09:07 | 23.22 |
February | 9018007.47 | 1965.26 | 05-FEB-17:02 | 31.00 |
March | 17865384.02 | 2087.64 | 26-MAR-16:02 | 31.70 |
April | 61066031.75 | 2649.82 | 29-APR-17:02 | 33.67 |
May | 84643116.07 | 3567.16 | 21-MAY-16:01 | 37.42 |
June | 76637798.01 | 3470.69 | 04-JUN-16:01 | 36.83 |
July | 91887877.35 | 4246.96 | 29-JUL-17:01 | 40.00 |
August | 65314433.61 | 4450.51 | 05-AUG-17:01 | 40.83 |
September | 75034886.69 | 4318.84 | 04-SEP-16:01 | 40.58 |
October | 71618915.47 | 3342.87 | 09-OCT-16:01 | 36.67 |
November | 41921009.57 | 2055.08 | 05-NOV-16:02 | 31.33 |
December | 8744816.41 | 1160.57 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.605587E+09 | |||
Minimum of Months | 1834337.66 | 725.08 | 23.17 | |
Maximum of Months | 91887877.35 | 4450.51 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1925418.40 | 669.06 | 29-JAN-09:07 | 23.22 |
February | 9042819.38 | 1968.88 | 05-FEB-17:02 | 31.00 |
March | 17871296.86 | 2088.78 | 26-MAR-16:02 | 31.70 |
April | 60594674.51 | 2648.27 | 29-APR-17:02 | 33.67 |
May | 83692502.25 | 3564.71 | 21-MAY-16:01 | 37.42 |
June | 77731150.87 | 3467.87 | 04-JUN-16:01 | 36.83 |
July | 89882094.77 | 4243.58 | 29-JUL-17:01 | 40.00 |
August | 63873375.87 | 4445.29 | 05-AUG-17:01 | 40.83 |
September | 74618165.28 | 4313.86 | 04-SEP-16:01 | 40.58 |
October | 70548977.31 | 3339.29 | 09-OCT-16:01 | 36.67 |
November | 41765728.70 | 2053.48 | 05-NOV-16:02 | 31.33 |
December | 8858289.15 | 1122.68 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.600404E+09 | |||
Minimum of Months | 1925418.40 | 669.06 | 23.17 | |
Maximum of Months | 89882094.77 | 4445.29 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1919290.13 | 686.98 | 29-JAN-09:07 | 23.22 |
February | 9412297.43 | 1985.89 | 05-FEB-17:12 | 31.00 |
March | 18446924.70 | 2439.98 | 02-MAR-08:03 | 27.00 |
April | 57536287.32 | 2576.23 | 29-APR-17:12 | 33.33 |
May | 72098458.82 | 3487.52 | 21-MAY-16:01 | 37.42 |
June | 62733633.75 | 3504.76 | 05-JUN-07:07 | 34.50 |
July | 71037979.65 | 4149.41 | 29-JUL-17:01 | 40.00 |
August | 48292335.50 | 4327.33 | 05-AUG-17:01 | 40.83 |
September | 62141314.95 | 4210.09 | 04-SEP-16:01 | 40.58 |
October | 59774029.04 | 3251.84 | 09-OCT-16:01 | 36.67 |
November | 41119135.87 | 2078.61 | 19-NOV-09:04 | 25.40 |
December | 9233046.12 | 1299.07 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.513745E+09 | |||
Minimum of Months | 1919290.13 | 686.98 | 23.17 | |
Maximum of Months | 72098458.82 | 4327.33 | 40.83 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75448323.21 | 0.830417E+09 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402043E+09 | 0.596745E+09 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104741E+10 | 0.258026E+09 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231281E+10 | 72741706.55 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410567E+10 | 8408524.30 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451237E+10 | 1872527.49 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525232E+10 | 0.00 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529114E+10 | 0.00 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431101E+10 | 1911859.56 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336254E+10 | 16468042.85 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177439E+10 | 76259378.82 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396520E+09 | 0.442844E+09 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328437E+11 | 0.230569E+10 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75448323.21 | 0.00 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529114E+10 | 0.830417E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42462730.47 | 0.419972E+09 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225293E+09 | 0.289889E+09 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583237E+09 | 0.119032E+09 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129002E+10 | 25468185.88 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227669E+10 | 2719246.72 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248384E+10 | 612745.96 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287939E+10 | 0.00 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289960E+10 | 0.00 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238135E+10 | 504328.96 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187372E+10 | 4767148.54 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992700E+09 | 24646519.28 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223072E+09 | 0.210068E+09 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181514E+11 | 0.109768E+10 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42462730.47 | 0.00 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289960E+10 | 0.419972E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41989850.37 | 0.443390E+09 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221124E+09 | 0.312136E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576030E+09 | 0.132050E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126670E+10 | 28291937.10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225317E+10 | 2926567.50 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246460E+10 | 646907.31 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285344E+10 | 0.00 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288304E+10 | 0.00 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235532E+10 | 606619.29 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184241E+10 | 5117038.65 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969980E+09 | 29876561.99 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218573E+09 | 0.231869E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179464E+11 | 0.118691E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41989850.37 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288304E+10 | 0.443390E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990986.30 | 0.442284E+09 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221119E+09 | 0.311533E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575992E+09 | 0.131806E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126648E+10 | 28471012.26 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225213E+10 | 3094474.31 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246309E+10 | 702081.10 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285123E+10 | 0.00 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288114E+10 | 0.00 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235371E+10 | 669282.77 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184145E+10 | 5453584.13 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969807E+09 | 30194271.43 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218578E+09 | 0.231520E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179367E+11 | 0.118573E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990986.30 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288114E+10 | 0.442284E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41992967.82 | 0.439653E+09 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221192E+09 | 0.309333E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576249E+09 | 0.130130E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126704E+10 | 27526089.34 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225309E+10 | 2856610.42 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246444E+10 | 616921.59 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285260E+10 | 0.00 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288243E+10 | 0.00 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235490E+10 | 597088.08 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184240E+10 | 5059010.28 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970254E+09 | 29133025.97 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218608E+09 | 0.229604E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179452E+11 | 0.117451E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41992967.82 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288243E+10 | 0.439653E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73648822.16 | 0.782992E+09 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388500E+09 | 0.555489E+09 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101406E+10 | 0.234880E+09 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222920E+10 | 53734383.38 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396574E+10 | 5654558.83 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434752E+10 | 1434085.31 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503468E+10 | 0.00 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508960E+10 | 0.00 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414829E+10 | 1330668.67 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324026E+10 | 11761594.05 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170644E+10 | 58191489.08 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383579E+09 | 0.415153E+09 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316215E+11 | 0.212062E+10 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73648822.16 | 0.00 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508960E+10 | 0.782992E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42001973.00 | 0.436643E+09 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221475E+09 | 0.306741E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577549E+09 | 0.128159E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127005E+10 | 27492751.11 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225659E+10 | 2762325.24 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247105E+10 | 694213.34 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285911E+10 | 0.00 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289025E+10 | 0.00 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235921E+10 | 620076.07 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184566E+10 | 5692647.90 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972710E+09 | 29373495.49 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218755E+09 | 0.228430E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179844E+11 | 0.116661E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42001973.00 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289025E+10 | 0.436643E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42002721.04 | 0.435796E+09 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221496E+09 | 0.306056E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577610E+09 | 0.127704E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127018E+10 | 27310001.24 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225676E+10 | 2732317.31 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247125E+10 | 684168.54 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285928E+10 | 0.00 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289039E+10 | 0.00 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235937E+10 | 612067.16 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184583E+10 | 5641573.33 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972827E+09 | 29192853.24 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218762E+09 | 0.227919E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179858E+11 | 0.116365E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42002721.04 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289039E+10 | 0.435796E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42003895.19 | 0.433046E+09 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221521E+09 | 0.303754E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577701E+09 | 0.126209E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127021E+10 | 26843577.65 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225640E+10 | 2701866.28 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247063E+10 | 685229.59 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285799E+10 | 0.00 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288913E+10 | 0.00 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235845E+10 | 635677.40 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184535E+10 | 5712684.27 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972795E+09 | 28963279.23 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218769E+09 | 0.226462E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179810E+11 | 0.115501E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42003895.19 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288913E+10 | 0.433046E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42982878.89 | 0.530314E+09 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227777E+09 | 0.395398E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600619E+09 | 0.174838E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131534E+10 | 52688018.31 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236493E+10 | 6693214.96 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261810E+10 | 1717362.09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304893E+10 | 0.00 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308383E+10 | 0.00 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248188E+10 | 2189217.15 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191415E+10 | 16425993.08 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100243E+10 | 64664313.78 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223751E+09 | 0.306095E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189247E+11 | 0.155102E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42982878.89 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308383E+10 | 0.530314E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.28 | 23-JAN-14:00 | 2423.02 | 18-JAN-17:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4040.62 | 06-FEB-15:00 | 2980.52 | 20-FEB-16:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6493.18 | 27-MAR-11:10 | 2863.31 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8034.01 | 28-APR-12:00 | 459.54 | 01-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7779.74 | 09-MAY-13:00 | 220.34 | 01-MAY-07:02 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8427.20 | 12-JUN-12:00 | 206.26 | 22-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9608.27 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7772.89 | 26-SEP-13:00 | 80.57 | 25-SEP-05:00 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6298.26 | 09-OCT-12:00 | 239.93 | 29-OCT-07:02 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4618.19 | 05-NOV-12:00 | 433.62 | 22-NOV-08:63 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2845.57 | 10-DEC-12:10 | 2919.28 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.28 | 0.00 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 2980.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1615.40 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.00 | 28-APR-12:00 | 256.37 | 01-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.34 | 09-MAY-13:00 | 117.88 | 01-MAY-07:02 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.23 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.20 | 26-SEP-13:00 | 25.45 | 25-SEP-07:01 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.70 | 09-OCT-12:00 | 129.93 | 29-OCT-07:02 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 235.99 | 22-NOV-08:63 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1636.05 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.99 | 28-APR-12:00 | 251.37 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.18 | 26-SEP-13:00 | 35.13 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 147.42 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 235.65 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1628.00 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.98 | 28-APR-12:00 | 251.15 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.17 | 26-SEP-13:00 | 38.44 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 149.57 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 235.62 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1609.36 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.00 | 28-APR-12:00 | 248.20 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.23 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.18 | 26-SEP-13:00 | 35.12 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 146.29 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 231.34 | 22-NOV-08:10 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 0.00 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.11 | 23-JAN-14:00 | 2382.77 | 18-JAN-17:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.45 | 06-FEB-15:00 | 2951.28 | 20-FEB-16:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6361.78 | 27-MAR-11:10 | 2702.25 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7976.60 | 28-APR-12:00 | 447.28 | 01-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7660.35 | 09-MAY-13:00 | 266.67 | 01-MAY-07:02 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8344.54 | 12-JUN-12:00 | 200.65 | 22-JUN-08:00 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9514.02 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7686.74 | 26-SEP-13:00 | 108.24 | 24-SEP-07:01 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6272.21 | 09-OCT-12:00 | 350.93 | 29-OCT-07:02 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.53 | 05-NOV-12:00 | 471.74 | 26-NOV-08:62 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.51 | 10-DEC-12:10 | 2850.43 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.11 | 0.00 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 2951.28 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.15 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1536.86 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.97 | 28-APR-12:00 | 254.34 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.29 | 09-MAY-13:00 | 149.00 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 59.29 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 196.03 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 261.45 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.15 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1531.37 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.97 | 28-APR-12:00 | 254.16 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.28 | 09-MAY-13:00 | 148.59 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 58.94 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 195.53 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 260.53 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1519.00 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.97 | 28-APR-12:00 | 253.56 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.28 | 09-MAY-13:00 | 147.38 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.21 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 60.36 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 195.52 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 257.49 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.78 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.94 | 23-JAN-14:00 | 1398.40 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.98 | 06-FEB-15:00 | 1713.40 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3755.26 | 27-MAR-11:10 | 1546.04 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.22 | 28-APR-12:00 | 250.39 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.50 | 09-MAY-13:00 | 149.52 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.53 | 12-JUN-12:00 | 119.77 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.42 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.02 | 26-SEP-13:00 | 77.17 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3608.81 | 09-OCT-12:00 | 225.73 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.66 | 05-NOV-12:00 | 314.51 | 23-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.21 | 10-DEC-12:10 | 1691.62 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.94 | 0.00 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 1713.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17316.32 | 30-JAN-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.70 |
February | 31226.67 | 09-FEB-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.64 |
March | 55717.54 | 02-MAR-08:62 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 195.18 | 0.00 |
April | 54091.81 | 29-APR-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 219.54 | 0.00 |
May | 58824.06 | 11-MAY-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 342.60 | 0.00 |
June | 51416.47 | 01-JUN-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.36 | 0.00 |
July | 57547.03 | 04-JUL-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 369.03 | 0.00 |
August | 51768.79 | 06-AUG-07:01 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 521.50 | 0.00 |
September | 48376.18 | 02-SEP-07:01 | 0.00 | 675.00 | 662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 435.49 | 0.00 |
October | 55908.34 | 20-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 |
November | 55641.04 | 05-NOV-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.19 |
December | 46580.04 | 12-DEC-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17316.32 | 0.00 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58824.06 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 521.50 | 267.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10699.07 | 30-JAN-08:63 | 506.24 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.57 |
February | 18046.21 | 09-FEB-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 |
March | 28684.64 | 02-MAR-08:62 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 102.69 | 0.00 |
April | 28291.42 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.34 | 0.00 |
May | 30342.78 | 11-MAY-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 197.16 | 0.00 |
June | 28433.07 | 02-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 | 0.00 |
July | 30032.63 | 04-JUL-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 210.19 | 0.00 |
August | 27492.17 | 06-AUG-07:01 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 306.21 | 0.00 |
September | 27358.81 | 26-SEP-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 72.63 | 0.00 |
October | 30021.58 | 20-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.46 |
November | 29858.84 | 05-NOV-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.69 |
December | 26177.43 | 12-DEC-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10699.07 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30342.78 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 306.21 | 148.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10899.97 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
February | 18976.35 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
March | 31312.70 | 28-MAR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
April | 29081.61 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
May | 29657.55 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
June | 27980.11 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
July | 29318.12 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 195.02 | 0.00 |
August | 24223.02 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 0.00 |
September | 22437.60 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 0.00 |
October | 28471.93 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
November | 28060.88 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.53 |
December | 23976.81 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10899.97 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31312.70 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 195.02 | 130.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10630.07 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
February | 18990.14 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
March | 31414.86 | 28-MAR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
April | 29195.69 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
May | 29776.10 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 0.00 |
June | 28153.47 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 0.00 |
July | 29516.65 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 190.62 | 0.00 |
August | 24397.52 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 0.00 |
September | 22785.82 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 0.00 |
October | 28583.51 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
November | 28175.64 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.73 |
December | 24016.75 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10630.07 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31414.86 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 190.62 | 132.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9433.05 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
February | 17558.96 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
March | 31082.84 | 28-MAR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
April | 28851.77 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
May | 29432.88 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
June | 27784.14 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
July | 29168.25 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 194.93 | 0.00 |
August | 24083.12 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
September | 22603.84 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
October | 28280.28 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 |
November | 27899.92 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.56 |
December | 23734.44 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9433.05 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31082.84 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 194.93 | 129.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15657.25 | 29-JAN-09:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.13 |
February | 30089.63 | 06-FEB-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.30 |
March | 47952.78 | 28-MAR-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 0.00 |
April | 50648.96 | 29-APR-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 210.28 | 0.00 |
May | 52345.10 | 11-MAY-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 341.29 | 0.00 |
June | 48567.38 | 01-JUN-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 296.66 | 0.00 |
July | 52724.09 | 04-JUL-08:61 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 417.49 | 0.00 |
August | 43070.40 | 16-AUG-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 502.53 | 0.00 |
September | 42220.64 | 26-SEP-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 | 0.00 |
October | 51389.95 | 20-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.68 |
November | 49256.87 | 19-NOV-09:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 0.00 |
December | 43434.75 | 12-DEC-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15657.25 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52724.09 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 502.53 | 207.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7477.70 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.03 |
February | 14865.78 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 |
March | 24939.94 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 110.43 | 0.00 |
April | 25622.32 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.34 | 0.00 |
May | 27495.82 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 199.88 | 0.00 |
June | 25593.45 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 174.21 | 0.00 |
July | 27765.77 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 241.77 | 0.00 |
August | 22683.12 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 288.20 | 0.00 |
September | 22163.00 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.60 | 0.00 |
October | 26947.05 | 20-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 |
November | 25818.17 | 19-NOV-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 0.00 |
December | 21834.47 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7477.70 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27765.77 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 288.20 | 147.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7176.72 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 |
February | 14512.87 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.26 |
March | 24827.97 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 111.42 | 0.00 |
April | 25347.59 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.46 | 0.00 |
May | 27388.20 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 200.39 | 0.00 |
June | 25489.65 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 174.65 | 0.00 |
July | 27667.45 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 241.90 | 0.00 |
August | 22595.94 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 288.35 | 0.00 |
September | 22075.30 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 | 0.00 |
October | 26843.47 | 20-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 |
November | 25719.96 | 19-NOV-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 | 0.00 |
December | 21491.24 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7176.72 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27667.45 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 288.35 | 146.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6225.51 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.50 |
February | 13398.08 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.77 |
March | 24900.13 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 | 0.00 |
April | 24983.95 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.65 | 0.00 |
May | 27551.15 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 200.89 | 0.00 |
June | 25673.91 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 174.38 | 0.00 |
July | 27920.93 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 239.77 | 0.00 |
August | 22874.35 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 284.57 | 0.00 |
September | 22272.20 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 | 0.00 |
October | 27016.48 | 20-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 |
November | 25372.22 | 19-NOV-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 0.00 |
December | 20674.74 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6225.51 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27920.93 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 284.57 | 146.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6111.71 | 28-JAN-14:00 | 2497.45 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.62 | 0.00 |
February | 10491.18 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 |
March | 30465.40 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 141.23 | 0.00 |
April | 25708.23 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.00 | 0.00 |
May | 32284.76 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 200.83 | 0.00 |
June | 29090.10 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 169.68 | 0.00 |
July | 33052.58 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 237.70 | 0.00 |
August | 27327.20 | 06-AUG-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 289.65 | 0.00 |
September | 25846.23 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 | 0.00 |
October | 30596.03 | 20-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
November | 28936.84 | 05-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 0.00 |
December | 20380.63 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6111.71 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33052.58 | 2497.45 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.62 | 127.25 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.843842E+11 | 75477.43 | 29-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.811511E+11 | 90300.73 | 07-FEB-12:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.972465E+11 | 95667.32 | 27-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.106163E+12 | 113689.55 | 28-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.130999E+12 | 127712.48 | 31-MAY-12:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.142104E+12 | 138279.07 | 12-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.160476E+12 | 152535.69 | 20-JUL-12:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.168736E+12 | 158081.00 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.145857E+12 | 144644.89 | 07-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.129819E+12 | 130285.35 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.108672E+12 | 108031.04 | 01-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.930209E+11 | 84554.92 | 05-DEC-17:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144863E+13 | 0.00 | ||||
Minimum of Months | 0.811511E+11 | 75477.43 | 0.00 | 0.00 | ||
Maximum of Months | 0.168736E+12 | 158081.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.595724E+10 | 0.108325E+11 | 0.00 | 0.109756E+11 | 0.00 | 0.00 | 0.170155E+11 | 0.00 | 0.00 | 0.00 | 0.507528E+10 | 0.00 |
February | 0.312534E+11 | 0.508826E+10 | 0.980803E+10 | 0.00 | 0.994432E+10 | 0.00 | 0.00 | 0.204916E+11 | 0.00 | 0.00 | 0.00 | 0.456542E+10 | 0.00 |
March | 0.350527E+11 | 0.520718E+10 | 0.110075E+11 | 0.00 | 0.111746E+11 | 0.00 | 0.00 | 0.298013E+11 | 0.00 | 0.00 | 0.00 | 0.500327E+10 | 0.00 |
April | 0.334898E+11 | 0.458600E+10 | 0.105079E+11 | 0.00 | 0.106898E+11 | 0.00 | 0.00 | 0.421674E+11 | 0.00 | 0.00 | 0.00 | 0.472190E+10 | 0.00 |
May | 0.347840E+11 | 0.437452E+10 | 0.109147E+11 | 0.00 | 0.113336E+11 | 0.00 | 0.00 | 0.648117E+11 | 0.00 | 0.00 | 0.00 | 0.478006E+10 | 0.00 |
June | 0.338757E+11 | 0.406393E+10 | 0.106386E+11 | 0.00 | 0.119179E+11 | 0.00 | 0.00 | 0.770434E+11 | 0.00 | 0.00 | 0.00 | 0.456511E+10 | 0.00 |
July | 0.344108E+11 | 0.426217E+10 | 0.107945E+11 | 0.00 | 0.135094E+11 | 0.00 | 0.00 | 0.928339E+11 | 0.00 | 0.00 | 0.00 | 0.466554E+10 | 0.00 |
August | 0.350409E+11 | 0.457607E+10 | 0.110006E+11 | 0.00 | 0.142620E+11 | 0.00 | 0.00 | 0.991337E+11 | 0.00 | 0.00 | 0.00 | 0.472269E+10 | 0.00 |
September | 0.335014E+11 | 0.484042E+10 | 0.105148E+11 | 0.00 | 0.122782E+11 | 0.00 | 0.00 | 0.800921E+11 | 0.00 | 0.00 | 0.00 | 0.463038E+10 | 0.00 |
October | 0.345281E+11 | 0.545170E+10 | 0.108325E+11 | 0.00 | 0.112981E+11 | 0.00 | 0.00 | 0.628318E+11 | 0.00 | 0.00 | 0.00 | 0.487705E+10 | 0.00 |
November | 0.334535E+11 | 0.566318E+10 | 0.104978E+11 | 0.00 | 0.107112E+11 | 0.00 | 0.00 | 0.435278E+11 | 0.00 | 0.00 | 0.00 | 0.481822E+10 | 0.00 |
December | 0.344233E+11 | 0.607289E+10 | 0.108050E+11 | 0.00 | 0.109573E+11 | 0.00 | 0.00 | 0.257119E+11 | 0.00 | 0.00 | 0.00 | 0.505045E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.601436E+11 | 0.128154E+12 | 0.00 | 0.139052E+12 | 0.00 | 0.00 | 0.655462E+12 | 0.00 | 0.00 | 0.00 | 0.574754E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.406393E+10 | 0.980803E+10 | 0.00 | 0.994432E+10 | 0.00 | 0.00 | 0.170155E+11 | 0.00 | 0.00 | 0.00 | 0.456511E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.607289E+10 | 0.110075E+11 | 0.00 | 0.142620E+11 | 0.00 | 0.00 | 0.991337E+11 | 0.00 | 0.00 | 0.00 | 0.507528E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 7540.84 | 09-JAN-12:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8324.28 | 09-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8946.83 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9156.83 | 18-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 10609.73 | 30-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 12014.78 | 09-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 14684.00 | 20-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 15111.83 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 13397.86 | 07-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 11615.91 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9228.02 | 07-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9068.46 | 12-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 7540.84 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 15111.83 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 30301.13 | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | 13551.85 | 01-JAN-08:09 | 0.00 |
February | 41617.64 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 9243.15 | 07-FEB-12:50 | 0.00 |
March | 49831.51 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 7550.81 | 14-MAR-12:30 | 0.00 |
April | 63936.07 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 7538.64 | 21-APR-13:39 | 0.00 |
May | 78199.47 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 9614.77 | 26-MAY-15:20 | 0.00 |
June | 87908.54 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7528.00 | 12-JUN-12:50 | 0.00 |
July | 100902.15 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7477.36 | 28-JUL-20:49 | 0.00 |
August | 106631.09 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7527.35 | 18-AUG-13:20 | 0.00 |
September | 91750.37 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 9377.36 | 13-SEP-12:00 | 0.00 |
October | 79631.51 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9654.58 | 23-OCT-13:39 | 0.00 |
November | 61912.34 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7552.47 | 27-NOV-14:50 | 0.00 |
December | 37672.28 | 05-DEC-15:39 | 0.00 | 0.00 | 0.00 | 7558.32 | 23-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30301.13 | 0.00 | 0.00 | 0.00 | 7477.36 | 0.00 | ||
Maximum of Months | 106631.09 | 0.00 | 0.00 | 0.00 | 13551.85 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 75477.43 | 29-JAN-15:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7540.84 | 0.00 | 0.00 | 30301.13 | 0.00 |
February | 90300.73 | 07-FEB-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7540.84 | 0.00 | 0.00 | 39195.94 | 0.00 |
March | 95667.32 | 27-MAR-13:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7540.84 | 0.00 | 0.00 | 48371.33 | 0.00 |
April | 113689.55 | 28-APR-11:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7906.24 | 0.00 | 0.00 | 63936.07 | 0.00 |
May | 127712.48 | 31-MAY-12:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 10504.29 | 0.00 | 0.00 | 77463.61 | 0.00 |
June | 138279.07 | 12-JUN-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11420.98 | 0.00 | 0.00 | 85009.30 | 0.00 |
July | 152535.69 | 20-JUL-12:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 14392.70 | 0.00 | 0.00 | 98401.41 | 0.00 |
August | 158081.00 | 10-AUG-15:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 14864.79 | 0.00 | 0.00 | 105584.39 | 0.00 |
September | 144644.89 | 07-SEP-13:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 13313.62 | 0.00 | 0.00 | 91585.82 | 0.00 |
October | 130285.35 | 07-OCT-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11615.91 | 0.00 | 0.00 | 79631.51 | 0.00 |
November | 108031.04 | 01-NOV-13:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8475.53 | 0.00 | 0.00 | 61912.34 | 0.00 |
December | 84554.92 | 05-DEC-17:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7540.84 | 0.00 | 0.00 | 33867.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 75477.43 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7540.84 | 0.00 | 0.00 | 30301.13 | 0.00 | |
Maximum of Months | 158081.00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 14864.79 | 0.00 | 0.00 | 105584.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.17 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.54 | 1.83 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.56 | 2.83 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.17 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 24.55 | 5.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.56 | 2.83 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.45 | 0.50 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.00 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.64 | 0.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 0.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 0.00 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.68 | 0.00 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.61 | 0.00 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.00 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 24.64 | 0.00 | 24.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.68 | 0.00 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.00 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 0.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.60 | 0.00 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.00 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 24.62 | 0.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.77 | 0.00 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.70 | 0.00 | 24.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.59 | 0.00 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.83 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.73 | 0.00 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.00 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.77 | 0.00 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.70 | 0.00 | 24.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 0.00 | 24.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.00 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.85 | 0.00 | 24.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.86 | 0.00 | 24.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.75 | 0.00 | 24.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.71 | 0.00 | 24.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.50 | 24.80 | 0.00 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.86 | 0.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.17 | 23.12 | 282.00 | 23.79 | 0.83 | 23.79 |
February | 18.33 | 23.21 | 353.67 | 23.86 | 0.00 | 23.86 |
March | 20.17 | 23.54 | 380.67 | 23.87 | 3.33 | 23.87 |
April | 4.83 | 23.88 | 436.33 | 23.89 | 4.83 | 23.89 |
May | 20.50 | 23.89 | 493.33 | 23.89 | 20.50 | 23.89 |
June | 114.00 | 23.90 | 481.00 | 23.89 | 114.00 | 23.89 |
July | 190.17 | 23.90 | 495.00 | 23.90 | 190.17 | 23.90 |
August | 181.17 | 23.90 | 497.00 | 23.90 | 181.17 | 23.90 |
September | 118.17 | 23.90 | 479.00 | 23.89 | 118.17 | 23.90 |
October | 59.83 | 23.90 | 492.83 | 23.89 | 59.83 | 23.89 |
November | 7.83 | 23.89 | 472.17 | 23.89 | 7.83 | 23.89 |
December | 16.33 | 23.59 | 411.33 | 23.88 | 5.67 | 23.88 |
Annual Sum or Average | 791.50 | 23.83 | 5274.33 | 23.88 | 706.33 | 23.88 |
Minimum of Months | 4.83 | 23.12 | 282.00 | 23.79 | 0.00 | 23.79 |
Maximum of Months | 190.17 | 23.90 | 497.00 | 23.90 | 190.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.83 | 23.32 | 251.50 | 23.83 | 0.83 | 23.83 |
February | 13.67 | 23.43 | 317.83 | 23.87 | 0.00 | 23.87 |
March | 12.00 | 23.62 | 345.83 | 23.88 | 0.00 | 23.88 |
April | 2.50 | 23.86 | 402.50 | 23.89 | 2.33 | 23.89 |
May | 12.67 | 23.89 | 481.83 | 23.89 | 12.67 | 23.89 |
June | 78.33 | 23.89 | 481.00 | 23.89 | 78.33 | 23.89 |
July | 141.50 | 23.89 | 495.00 | 23.89 | 141.50 | 23.89 |
August | 156.00 | 23.89 | 497.00 | 23.89 | 156.00 | 23.89 |
September | 90.33 | 23.89 | 479.00 | 23.89 | 90.33 | 23.89 |
October | 39.00 | 23.89 | 486.33 | 23.89 | 39.00 | 23.89 |
November | 6.50 | 23.89 | 447.50 | 23.89 | 6.50 | 23.89 |
December | 11.00 | 23.66 | 376.50 | 23.88 | 3.50 | 23.88 |
Annual Sum or Average | 595.33 | 23.84 | 5061.83 | 23.89 | 531.00 | 23.89 |
Minimum of Months | 2.50 | 23.32 | 251.50 | 23.83 | 0.00 | 23.83 |
Maximum of Months | 156.00 | 23.89 | 497.00 | 23.89 | 156.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.50 | 23.22 | 221.67 | 23.94 | 1.17 | 23.94 |
February | 9.50 | 23.32 | 277.00 | 23.99 | 0.17 | 24.00 |
March | 8.17 | 24.17 | 303.67 | 24.06 | 2.33 | 24.07 |
April | 8.17 | 26.25 | 318.17 | 24.17 | 8.17 | 24.22 |
May | 34.33 | 25.92 | 372.33 | 24.31 | 34.33 | 24.44 |
June | 98.33 | 24.80 | 366.00 | 24.31 | 98.33 | 24.39 |
July | 157.00 | 24.61 | 369.00 | 24.33 | 157.00 | 24.40 |
August | 174.67 | 24.55 | 379.00 | 24.32 | 174.67 | 24.37 |
September | 114.17 | 24.78 | 360.00 | 24.33 | 114.17 | 24.41 |
October | 58.00 | 25.04 | 363.17 | 24.28 | 58.00 | 24.37 |
November | 14.50 | 25.17 | 356.50 | 24.13 | 14.50 | 24.17 |
December | 15.50 | 24.20 | 326.83 | 24.03 | 10.83 | 24.05 |
Annual Sum or Average | 720.83 | 24.69 | 4013.33 | 24.21 | 673.67 | 24.28 |
Minimum of Months | 8.17 | 23.22 | 221.67 | 23.94 | 0.17 | 23.94 |
Maximum of Months | 174.67 | 26.25 | 379.00 | 24.33 | 174.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.83 | 23.19 | 218.67 | 23.93 | 1.17 | 23.93 |
February | 10.00 | 23.27 | 275.17 | 23.99 | 0.17 | 23.99 |
March | 8.67 | 24.12 | 301.33 | 24.06 | 2.33 | 24.07 |
April | 8.17 | 26.26 | 318.67 | 24.17 | 8.17 | 24.22 |
May | 34.33 | 25.95 | 372.33 | 24.31 | 34.33 | 24.44 |
June | 97.33 | 24.81 | 366.00 | 24.31 | 97.33 | 24.40 |
July | 153.33 | 24.63 | 369.00 | 24.34 | 153.33 | 24.40 |
August | 172.83 | 24.56 | 379.00 | 24.32 | 172.83 | 24.38 |
September | 112.33 | 24.80 | 360.00 | 24.33 | 112.33 | 24.42 |
October | 56.83 | 25.08 | 364.17 | 24.28 | 56.83 | 24.38 |
November | 14.33 | 25.23 | 356.50 | 24.13 | 14.33 | 24.17 |
December | 16.67 | 24.15 | 325.50 | 24.03 | 11.33 | 24.04 |
Annual Sum or Average | 714.67 | 24.70 | 4006.33 | 24.21 | 664.50 | 24.29 |
Minimum of Months | 8.17 | 23.19 | 218.67 | 23.93 | 0.17 | 23.93 |
Maximum of Months | 172.83 | 26.26 | 379.00 | 24.34 | 172.83 | 24.44 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 23.15 | 211.17 | 23.90 | 1.50 | 23.90 |
February | 12.67 | 23.26 | 270.17 | 23.98 | 0.17 | 23.98 |
March | 11.33 | 23.93 | 288.67 | 24.06 | 2.67 | 24.07 |
April | 8.33 | 26.16 | 314.83 | 24.16 | 8.33 | 24.21 |
May | 34.33 | 25.87 | 372.17 | 24.30 | 34.33 | 24.43 |
June | 98.67 | 24.79 | 366.00 | 24.30 | 98.67 | 24.39 |
July | 155.33 | 24.61 | 369.00 | 24.33 | 155.33 | 24.40 |
August | 173.50 | 24.55 | 379.00 | 24.31 | 173.50 | 24.37 |
September | 114.00 | 24.77 | 360.00 | 24.32 | 114.00 | 24.41 |
October | 58.17 | 25.01 | 363.00 | 24.27 | 58.17 | 24.36 |
November | 15.33 | 25.03 | 356.17 | 24.12 | 15.33 | 24.16 |
December | 19.33 | 24.05 | 319.00 | 24.02 | 12.67 | 24.03 |
Annual Sum or Average | 735.17 | 24.65 | 3969.17 | 24.21 | 674.67 | 24.28 |
Minimum of Months | 8.33 | 23.15 | 211.17 | 23.90 | 0.17 | 23.90 |
Maximum of Months | 173.50 | 26.16 | 379.00 | 24.33 | 173.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.33 | 23.28 | 178.00 | 23.84 | 2.67 | 23.84 |
February | 8.17 | 23.28 | 231.33 | 23.91 | 0.00 | 23.91 |
March | 9.67 | 23.88 | 240.83 | 23.94 | 4.00 | 23.94 |
April | 6.50 | 26.04 | 282.33 | 24.03 | 6.50 | 24.08 |
May | 25.17 | 24.98 | 340.33 | 24.06 | 25.17 | 24.12 |
June | 97.00 | 24.21 | 336.00 | 24.04 | 97.00 | 24.07 |
July | 159.00 | 24.18 | 338.00 | 24.08 | 159.00 | 24.10 |
August | 173.67 | 24.09 | 348.00 | 24.02 | 173.67 | 24.04 |
September | 113.67 | 24.24 | 330.00 | 24.07 | 113.67 | 24.10 |
October | 51.00 | 24.43 | 332.67 | 24.05 | 51.00 | 24.10 |
November | 14.17 | 24.12 | 326.33 | 23.97 | 14.17 | 23.97 |
December | 23.00 | 24.07 | 273.17 | 23.95 | 19.33 | 23.97 |
Annual Sum or Average | 710.33 | 24.18 | 3557.00 | 24.01 | 666.17 | 24.04 |
Minimum of Months | 6.50 | 23.28 | 178.00 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 173.67 | 26.04 | 348.00 | 24.08 | 173.67 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.50 | 23.35 | 162.67 | 23.83 | 2.83 | 23.83 |
February | 9.50 | 23.36 | 212.33 | 23.91 | 0.00 | 23.91 |
March | 11.67 | 23.82 | 209.67 | 23.94 | 3.83 | 23.94 |
April | 6.00 | 25.87 | 272.00 | 24.03 | 6.00 | 24.07 |
May | 25.17 | 24.97 | 334.33 | 24.06 | 25.17 | 24.12 |
June | 97.50 | 24.21 | 336.00 | 24.03 | 97.50 | 24.07 |
July | 159.00 | 24.18 | 338.00 | 24.08 | 159.00 | 24.10 |
August | 173.17 | 24.08 | 348.00 | 24.02 | 173.17 | 24.04 |
September | 115.50 | 24.23 | 330.00 | 24.07 | 115.50 | 24.10 |
October | 50.67 | 24.42 | 329.33 | 24.05 | 50.67 | 24.10 |
November | 13.67 | 24.09 | 320.33 | 23.97 | 13.67 | 23.97 |
December | 24.17 | 24.06 | 256.83 | 23.96 | 19.50 | 23.97 |
Annual Sum or Average | 718.50 | 24.17 | 3449.50 | 24.01 | 666.83 | 24.04 |
Minimum of Months | 6.00 | 23.35 | 162.67 | 23.83 | 0.00 | 23.83 |
Maximum of Months | 173.17 | 25.87 | 348.00 | 24.08 | 173.17 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.50 | 23.35 | 159.17 | 23.82 | 2.83 | 23.83 |
February | 10.33 | 23.35 | 207.50 | 23.91 | 0.00 | 23.91 |
March | 12.33 | 23.80 | 207.33 | 23.94 | 3.83 | 23.94 |
April | 6.17 | 25.81 | 270.33 | 24.03 | 6.17 | 24.07 |
May | 25.17 | 24.97 | 333.83 | 24.06 | 25.17 | 24.12 |
June | 98.50 | 24.20 | 336.00 | 24.03 | 98.50 | 24.07 |
July | 160.33 | 24.17 | 338.00 | 24.08 | 160.33 | 24.10 |
August | 174.33 | 24.08 | 348.00 | 24.02 | 174.33 | 24.04 |
September | 116.50 | 24.22 | 330.00 | 24.07 | 116.50 | 24.10 |
October | 51.17 | 24.41 | 329.00 | 24.05 | 51.17 | 24.09 |
November | 13.50 | 24.04 | 320.00 | 23.96 | 13.50 | 23.97 |
December | 25.33 | 24.05 | 254.00 | 23.95 | 20.33 | 23.97 |
Annual Sum or Average | 728.17 | 24.16 | 3433.17 | 24.01 | 672.67 | 24.04 |
Minimum of Months | 6.17 | 23.35 | 159.17 | 23.82 | 0.00 | 23.83 |
Maximum of Months | 174.33 | 25.81 | 348.00 | 24.08 | 174.33 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.83 | 23.32 | 155.67 | 23.80 | 3.00 | 23.81 |
February | 13.17 | 23.34 | 201.83 | 23.90 | 0.67 | 23.90 |
March | 14.83 | 23.75 | 205.83 | 23.93 | 4.17 | 23.94 |
April | 6.17 | 25.81 | 271.83 | 24.03 | 6.17 | 24.07 |
May | 25.17 | 24.97 | 335.50 | 24.06 | 25.17 | 24.12 |
June | 96.00 | 24.21 | 336.00 | 24.04 | 96.00 | 24.07 |
July | 154.83 | 24.19 | 338.00 | 24.08 | 154.83 | 24.11 |
August | 171.00 | 24.09 | 348.00 | 24.02 | 171.00 | 24.04 |
September | 112.67 | 24.24 | 330.00 | 24.07 | 112.67 | 24.10 |
October | 49.83 | 24.44 | 330.00 | 24.05 | 49.83 | 24.10 |
November | 14.00 | 24.12 | 321.17 | 23.97 | 14.00 | 23.97 |
December | 28.00 | 24.00 | 252.83 | 23.95 | 21.67 | 23.96 |
Annual Sum or Average | 725.50 | 24.15 | 3426.67 | 24.01 | 659.17 | 24.04 |
Minimum of Months | 6.17 | 23.32 | 155.67 | 23.80 | 0.67 | 23.81 |
Maximum of Months | 171.00 | 25.81 | 348.00 | 24.08 | 171.00 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.67 | 23.22 | 168.50 | 23.79 | 2.50 | 23.79 |
February | 17.83 | 23.27 | 220.50 | 23.88 | 1.17 | 23.89 |
March | 22.00 | 23.70 | 234.33 | 23.92 | 6.17 | 23.93 |
April | 8.83 | 25.89 | 298.17 | 24.04 | 8.67 | 24.09 |
May | 21.17 | 25.44 | 343.00 | 24.08 | 21.17 | 24.16 |
June | 71.17 | 24.37 | 336.00 | 24.06 | 71.17 | 24.11 |
July | 125.33 | 24.29 | 338.00 | 24.11 | 125.33 | 24.15 |
August | 130.83 | 24.18 | 348.00 | 24.05 | 130.83 | 24.07 |
September | 80.83 | 24.43 | 330.00 | 24.10 | 80.83 | 24.15 |
October | 37.17 | 24.80 | 338.50 | 24.08 | 37.17 | 24.15 |
November | 12.67 | 24.56 | 328.67 | 23.99 | 12.67 | 24.01 |
December | 28.67 | 23.96 | 270.33 | 23.95 | 21.33 | 23.96 |
Annual Sum or Average | 600.17 | 24.25 | 3554.00 | 24.02 | 519.00 | 24.07 |
Minimum of Months | 8.83 | 23.22 | 168.50 | 23.79 | 1.17 | 23.79 |
Maximum of Months | 130.83 | 25.89 | 348.00 | 24.11 | 130.83 | 24.16 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.82461 | 45.41826 | 0.43031 | 9.08713 |
February | 448.00000 | 23.85784 | 48.45896 | 0.47385 | 9.82786 |
March | 497.00000 | 23.87273 | 46.20822 | 0.47987 | 9.96142 |
April | 479.00000 | 23.88616 | 49.39087 | 0.53797 | 11.17476 |
May | 496.00000 | 23.89046 | 51.05811 | -0.2270 | 6.22203 |
June | 481.00000 | 23.89242 | 58.10359 | -0.1472 | 5.56444 |
July | 495.00000 | 23.89454 | 60.23679 | -0.0940 | 5.30995 |
August | 497.00000 | 23.89537 | 61.55068 | -0.0665 | 5.20207 |
September | 479.00000 | 23.89299 | 60.48541 | -0.1087 | 5.36362 |
October | 496.00000 | 23.89135 | 54.04501 | 0.63754 | 13.64090 |
November | 480.00000 | 23.88589 | 51.10841 | 0.57078 | 11.92405 |
December | 496.00000 | 23.87403 | 49.67456 | 0.49953 | 10.35412 |
Annual Sum or Average | 5840.00000 | 23.87994 | 52.99500 | 0.24739 | 8.62746 |
Minimum of Months | 448.00000 | 23.82461 | 45.41826 | -0.2270 | 5.20207 |
Maximum of Months | 497.00000 | 23.89537 | 61.55068 | 0.63754 | 13.64090 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.85122 | 43.46397 | 0.42695 | 8.96536 |
February | 448.00000 | 23.87277 | 45.93042 | 0.46069 | 9.54105 |
March | 497.00000 | 23.88100 | 44.12998 | 0.46326 | 9.60046 |
April | 479.00000 | 23.88538 | 46.78169 | 0.50715 | 10.49468 |
May | 496.00000 | 23.89014 | 48.96364 | -0.2805 | 6.77274 |
June | 481.00000 | 23.89191 | 55.68886 | -0.2120 | 6.05930 |
July | 495.00000 | 23.89316 | 58.31238 | -0.1645 | 5.69154 |
August | 497.00000 | 23.89369 | 59.83782 | -0.1422 | 5.53698 |
September | 479.00000 | 23.89208 | 58.11499 | -0.1788 | 5.79422 |
October | 496.00000 | 23.89091 | 51.69240 | 0.59139 | 12.45191 |
November | 480.00000 | 23.88487 | 48.97032 | 0.53732 | 11.15264 |
December | 496.00000 | 23.88028 | 47.11324 | 0.48022 | 9.94128 |
Annual Sum or Average | 5840.00000 | 23.88399 | 50.77102 | 0.20580 | 8.49286 |
Minimum of Months | 448.00000 | 23.85122 | 43.46397 | -0.2805 | 5.53698 |
Maximum of Months | 497.00000 | 23.89369 | 59.83782 | 0.59139 | 12.45191 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.92365 | 44.61636 | 0.44532 | 9.38064 |
February | 336.00000 | 23.97295 | 47.49355 | 0.48981 | 10.18920 |
March | 379.00000 | 24.01770 | 45.17236 | 0.49635 | 10.38761 |
April | 360.00000 | 24.08787 | 47.80123 | 0.55382 | 11.78795 |
May | 375.00000 | 24.16066 | 49.56345 | -0.1999 | 6.82280 |
June | 366.00000 | 24.17357 | 56.72063 | -0.1229 | 6.43362 |
July | 369.00000 | 24.21471 | 59.93265 | -0.0593 | 6.41970 |
August | 379.00000 | 24.20645 | 61.51319 | -0.0386 | 6.31266 |
September | 360.00000 | 24.18110 | 59.81859 | -0.0805 | 6.31469 |
October | 371.00000 | 24.15020 | 52.98418 | 0.65660 | 14.56038 |
November | 360.00000 | 24.08470 | 51.05546 | 0.59479 | 12.69508 |
December | 369.00000 | 24.00008 | 49.08602 | 0.51721 | 10.79236 |
Annual Sum or Average | 4395.00000 | 24.09866 | 52.17258 | 0.26859 | 9.32577 |
Minimum of Months | 336.00000 | 23.92365 | 44.61636 | -0.1999 | 6.31266 |
Maximum of Months | 379.00000 | 24.21471 | 61.51319 | 0.65660 | 14.56038 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.91672 | 44.68958 | 0.44170 | 9.32480 |
February | 336.00000 | 23.96957 | 47.54856 | 0.48779 | 10.15132 |
March | 379.00000 | 24.01608 | 45.19200 | 0.49537 | 10.36898 |
April | 360.00000 | 24.08785 | 47.78905 | 0.55431 | 11.79905 |
May | 375.00000 | 24.16146 | 49.50195 | -0.1969 | 6.80516 |
June | 366.00000 | 24.17461 | 56.62812 | -0.1195 | 6.42726 |
July | 369.00000 | 24.21593 | 59.81160 | -0.0550 | 6.42231 |
August | 379.00000 | 24.20761 | 61.39259 | -0.0345 | 6.31930 |
September | 360.00000 | 24.18217 | 59.70438 | -0.0769 | 6.31415 |
October | 371.00000 | 24.15111 | 52.89648 | 0.65852 | 14.61710 |
November | 360.00000 | 24.08478 | 51.03004 | 0.59542 | 12.71152 |
December | 369.00000 | 23.99807 | 49.12206 | 0.51600 | 10.76763 |
Annual Sum or Average | 4395.00000 | 24.09804 | 52.13433 | 0.26974 | 9.32024 |
Minimum of Months | 336.00000 | 23.91672 | 44.68958 | -0.1969 | 6.31415 |
Maximum of Months | 379.00000 | 24.21593 | 61.39259 | 0.65852 | 14.61710 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.90014 | 44.90402 | 0.43326 | 9.18785 |
February | 336.00000 | 23.95942 | 47.76810 | 0.48153 | 10.02765 |
March | 379.00000 | 24.00858 | 45.34831 | 0.48963 | 10.24974 |
April | 360.00000 | 24.08372 | 47.92104 | 0.54991 | 11.68832 |
May | 375.00000 | 24.15796 | 49.55413 | -0.2019 | 6.82393 |
June | 366.00000 | 24.17112 | 56.70443 | -0.1239 | 6.42173 |
July | 369.00000 | 24.21295 | 59.85706 | -0.0584 | 6.40118 |
August | 379.00000 | 24.20453 | 61.44477 | -0.0379 | 6.29254 |
September | 360.00000 | 24.17891 | 59.78974 | -0.0806 | 6.29842 |
October | 371.00000 | 24.14761 | 52.98514 | 0.65563 | 14.52681 |
November | 360.00000 | 24.08075 | 51.17133 | 0.59176 | 12.61071 |
December | 369.00000 | 23.99044 | 49.34079 | 0.51083 | 10.65633 |
Annual Sum or Average | 4395.00000 | 24.09224 | 52.25705 | 0.26504 | 9.25042 |
Minimum of Months | 336.00000 | 23.90014 | 44.90402 | -0.2019 | 6.29254 |
Maximum of Months | 379.00000 | 24.21295 | 61.44477 | 0.65563 | 14.52681 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.86062 | 46.56534 | 0.41801 | 8.85797 |
February | 308.00000 | 23.90145 | 49.30057 | 0.46472 | 9.62696 |
March | 348.00000 | 23.91849 | 46.90524 | 0.46932 | 9.75245 |
April | 330.00000 | 23.97103 | 49.36304 | 0.52818 | 11.07716 |
May | 344.00000 | 23.98933 | 51.11681 | -0.2407 | 6.74477 |
June | 336.00000 | 23.98621 | 58.25165 | -0.1653 | 6.16417 |
July | 338.00000 | 24.03026 | 61.40375 | -0.0941 | 5.95700 |
August | 348.00000 | 23.99114 | 63.09156 | -0.0801 | 5.70295 |
September | 330.00000 | 24.01106 | 61.25153 | -0.1147 | 5.94171 |
October | 340.00000 | 23.99397 | 54.14088 | 0.63216 | 13.70388 |
November | 330.00000 | 23.95992 | 52.59871 | 0.56990 | 11.95254 |
December | 338.00000 | 23.92721 | 50.99463 | 0.49486 | 10.26379 |
Annual Sum or Average | 4030.00000 | 23.96202 | 53.77453 | 0.23754 | 8.79632 |
Minimum of Months | 308.00000 | 23.86062 | 46.56534 | -0.2407 | 5.70295 |
Maximum of Months | 348.00000 | 24.03026 | 63.09156 | 0.63216 | 13.70388 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.86151 | 46.51485 | 0.40665 | 8.65800 |
February | 308.00000 | 23.90169 | 49.26689 | 0.45206 | 9.38039 |
March | 348.00000 | 23.91860 | 46.86124 | 0.45517 | 9.47261 |
April | 330.00000 | 23.97025 | 49.32152 | 0.51157 | 10.71062 |
May | 344.00000 | 23.98838 | 51.03072 | -0.2698 | 7.04561 |
June | 336.00000 | 23.98508 | 58.20082 | -0.1964 | 6.39168 |
July | 338.00000 | 24.02929 | 61.36923 | -0.1275 | 6.10842 |
August | 348.00000 | 23.99027 | 63.08568 | -0.1146 | 5.83756 |
September | 330.00000 | 24.00973 | 61.26454 | -0.1468 | 6.10667 |
October | 340.00000 | 23.99314 | 54.08814 | 0.61106 | 13.14952 |
November | 330.00000 | 23.95924 | 52.57963 | 0.55240 | 11.53588 |
December | 338.00000 | 23.92736 | 50.97585 | 0.48198 | 9.99722 |
Annual Sum or Average | 4030.00000 | 23.96151 | 53.73898 | 0.21525 | 8.68566 |
Minimum of Months | 308.00000 | 23.86151 | 46.51485 | -0.2698 | 5.83756 |
Maximum of Months | 348.00000 | 24.02929 | 63.08568 | 0.61106 | 13.14952 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.85788 | 46.58466 | 0.40379 | 8.61590 |
February | 308.00000 | 23.89962 | 49.34110 | 0.44977 | 9.33948 |
March | 348.00000 | 23.91765 | 46.91588 | 0.45320 | 9.43658 |
April | 330.00000 | 23.96991 | 49.36924 | 0.51014 | 10.67934 |
May | 344.00000 | 23.98816 | 51.06388 | -0.2715 | 7.06305 |
June | 336.00000 | 23.98489 | 58.24081 | -0.1979 | 6.40241 |
July | 338.00000 | 24.02910 | 61.40545 | -0.1287 | 6.11326 |
August | 348.00000 | 23.99015 | 63.12279 | -0.1158 | 5.84198 |
September | 330.00000 | 24.00951 | 61.30556 | -0.1481 | 6.11265 |
October | 340.00000 | 23.99290 | 54.12544 | 0.61009 | 13.12375 |
November | 330.00000 | 23.95894 | 52.62896 | 0.55120 | 11.50720 |
December | 338.00000 | 23.92637 | 51.04547 | 0.48028 | 9.96356 |
Annual Sum or Average | 4030.00000 | 23.96072 | 53.78796 | 0.21364 | 8.66962 |
Minimum of Months | 308.00000 | 23.85788 | 46.58466 | -0.2715 | 5.84198 |
Maximum of Months | 348.00000 | 24.02910 | 63.12279 | 0.61009 | 13.12375 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.84540 | 46.74301 | 0.39871 | 8.55720 |
February | 308.00000 | 23.89239 | 49.50380 | 0.44654 | 9.29097 |
March | 348.00000 | 23.91439 | 47.01356 | 0.45159 | 9.41475 |
April | 330.00000 | 23.96980 | 49.40743 | 0.51168 | 10.71472 |
May | 344.00000 | 23.98862 | 50.99835 | -0.2651 | 6.99775 |
June | 336.00000 | 23.98542 | 58.11369 | -0.1903 | 6.34759 |
July | 338.00000 | 24.02978 | 61.21820 | -0.1196 | 6.07342 |
August | 348.00000 | 23.99067 | 62.89487 | -0.1060 | 5.80304 |
September | 330.00000 | 24.01021 | 61.12220 | -0.1397 | 6.07128 |
October | 340.00000 | 23.99346 | 54.01506 | 0.61479 | 13.24810 |
November | 330.00000 | 23.95904 | 52.60911 | 0.55395 | 11.57291 |
December | 338.00000 | 23.92336 | 51.16516 | 0.47937 | 9.95124 |
Annual Sum or Average | 4030.00000 | 23.95887 | 53.75783 | 0.21698 | 8.65658 |
Minimum of Months | 308.00000 | 23.84540 | 46.74301 | -0.2651 | 5.80304 |
Maximum of Months | 348.00000 | 24.02978 | 62.89487 | 0.61479 | 13.24810 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.82890 | 46.66300 | 0.40332 | 8.71871 |
February | 308.00000 | 23.88056 | 49.48867 | 0.45583 | 9.52171 |
March | 348.00000 | 23.90823 | 46.95713 | 0.46853 | 9.80506 |
April | 330.00000 | 23.97795 | 49.11499 | 0.54964 | 11.60096 |
May | 344.00000 | 23.99749 | 50.25320 | -0.1802 | 6.29044 |
June | 336.00000 | 23.99389 | 56.80896 | -0.0994 | 5.87919 |
July | 338.00000 | 24.03965 | 59.58243 | -0.0181 | 5.87583 |
August | 348.00000 | 23.99776 | 60.93525 | 0.00161 | 5.65300 |
September | 330.00000 | 24.02149 | 59.40553 | -0.0432 | 5.82628 |
October | 340.00000 | 24.00423 | 52.90007 | 0.67187 | 14.83538 |
November | 330.00000 | 23.96639 | 51.87727 | 0.59416 | 12.57583 |
December | 338.00000 | 23.92322 | 50.92875 | 0.49520 | 10.30925 |
Annual Sum or Average | 4030.00000 | 23.96204 | 52.92791 | 0.27262 | 8.89116 |
Minimum of Months | 308.00000 | 23.82890 | 46.66300 | -0.1802 | 5.65300 |
Maximum of Months | 348.00000 | 24.03965 | 60.93525 | 0.67187 | 14.83538 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.135280E+11 | 0.401080E+10 | 448.44 | 0.103567E+11 | 0.317124E+10 | 0.00 | 0.78 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 28108.05 | 30-JAN-08:63 | 18223.18 | 30-JAN-08:63 | 9884.88 | 30-JAN-08:63 | 7114.63 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.157549E+11 | 0.468530E+10 | 424.03 | 0.118352E+11 | 0.391969E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 57675.36 | 09-FEB-08:62 | 35030.33 | 09-FEB-08:62 | 22645.03 | 09-FEB-08:62 | 13612.57 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.220371E+11 | 0.666299E+10 | 480.20 | 0.173021E+11 | 0.473504E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 73998.15 | 02-MAR-08:62 | 64263.94 | 02-MAR-08:62 | 20063.27 | 29-MAR-07:03 | 19155.37 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.310781E+11 | 0.948373E+10 | 477.34 | 0.236166E+11 | 0.746153E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 79995.18 | 30-APR-07:02 | 63447.44 | 29-APR-07:02 | 34669.68 | 30-APR-07:02 | 18683.41 | 18-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.460548E+11 | 0.143519E+11 | 500.94 | 0.347506E+11 | 0.113042E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 82273.05 | 30-MAY-07:01 | 68976.51 | 10-MAY-07:02 | 39460.33 | 30-MAY-07:02 | 20409.88 | 23-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.559804E+11 | 0.169575E+11 | 488.78 | 0.373330E+11 | 0.186474E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 83907.18 | 19-JUN-07:01 | 59766.79 | 01-JUN-07:01 | 44664.97 | 19-JUN-07:04 | 21628.27 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.671241E+11 | 0.204694E+11 | 503.59 | 0.432162E+11 | 0.239079E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 83835.75 | 26-JUL-07:01 | 66362.52 | 04-JUL-07:01 | 45901.06 | 18-JUL-07:04 | 21450.98 | 15-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.709636E+11 | 0.214996E+11 | 504.51 | 0.446033E+11 | 0.263604E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 83835.75 | 08-AUG-07:02 | 61220.65 | 06-AUG-07:01 | 51436.34 | 08-AUG-07:06 | 21957.35 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.603833E+11 | 0.177666E+11 | 487.82 | 0.379351E+11 | 0.224482E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 83669.16 | 11-SEP-07:01 | 56953.27 | 02-SEP-07:01 | 44011.46 | 11-SEP-07:12 | 20962.34 | 02-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.474850E+11 | 0.140351E+11 | 500.02 | 0.330554E+11 | 0.144296E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 83552.80 | 08-OCT-07:01 | 62586.93 | 20-OCT-07:02 | 43352.39 | 08-OCT-07:02 | 19814.12 | 06-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.328789E+11 | 0.966545E+10 | 478.33 | 0.236898E+11 | 0.918909E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 80034.10 | 03-NOV-07:02 | 61383.35 | 05-NOV-07:02 | 31830.71 | 03-NOV-07:02 | 19282.97 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.201438E+11 | 0.589691E+10 | 480.63 | 0.145065E+11 | 0.563725E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-01:05 | 77894.90 | 12-DEC-08:62 | 53251.39 | 12-DEC-08:62 | 24643.51 | 12-DEC-08:62 | 18695.13 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.483412E+12 | 0.145485E+12 | 5774.64 | 0.332200E+12 | 0.151211E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.135280E+11 | 0.401080E+10 | 424.03 | 0.103567E+11 | 0.317124E+10 | 0.00 | 0.78 | 0.00 | 28108.05 | 18223.18 | 9884.88 | 7114.63 | 0.00 | |||||||
Maximum of Months | 0.709636E+11 | 0.214996E+11 | 504.51 | 0.446033E+11 | 0.263604E+11 | 0.00 | 1.00 | 0.00 | 83907.18 | 68976.51 | 51436.34 | 21957.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.786093E+10 | 0.207253E+10 | 463.61 | 0.614853E+10 | 0.171239E+10 | 0.00 | 0.84 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 | 15115.39 | 29-JAN-08:63 | 11722.57 | 29-JAN-08:63 | 3505.15 | 29-JAN-14:00 | 3428.18 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.871942E+10 | 0.230900E+10 | 432.36 | 0.669612E+10 | 0.202330E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 28691.77 | 09-FEB-08:62 | 20241.80 | 09-FEB-08:62 | 8449.96 | 09-FEB-08:62 | 6128.40 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.115835E+11 | 0.312590E+10 | 485.67 | 0.925077E+10 | 0.233276E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 37029.84 | 02-MAR-08:62 | 33072.54 | 02-MAR-08:62 | 7410.74 | 29-MAR-07:03 | 8606.74 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.154089E+11 | 0.422286E+10 | 477.83 | 0.119801E+11 | 0.342883E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 38847.95 | 30-APR-07:02 | 33157.35 | 29-APR-07:02 | 11000.23 | 30-APR-07:02 | 8314.32 | 18-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.219697E+11 | 0.619380E+10 | 501.05 | 0.169232E+11 | 0.504647E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 39645.74 | 30-MAY-07:01 | 35319.06 | 10-MAY-07:02 | 13451.25 | 30-MAY-07:02 | 9139.85 | 23-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.263367E+11 | 0.725871E+10 | 488.61 | 0.180349E+11 | 0.830181E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 40597.90 | 19-JUN-07:01 | 33070.75 | 02-JUN-07:01 | 16590.83 | 19-JUN-07:02 | 9758.93 | 05-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.314827E+11 | 0.874259E+10 | 503.24 | 0.206703E+11 | 0.108124E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 40877.89 | 18-JUL-07:01 | 34592.34 | 04-JUL-07:01 | 17773.82 | 18-JUL-07:03 | 9667.81 | 15-JUL-07:03 | 0.00 | 01-JUL-00:03 |
August | 0.332775E+11 | 0.917425E+10 | 504.40 | 0.212691E+11 | 0.120085E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 41785.54 | 08-AUG-07:01 | 32454.94 | 06-AUG-07:01 | 21114.60 | 08-AUG-07:12 | 9853.33 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.282798E+11 | 0.757343E+10 | 487.69 | 0.182410E+11 | 0.100388E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 40431.25 | 10-SEP-07:01 | 31196.45 | 26-SEP-07:01 | 16217.52 | 10-SEP-07:03 | 9392.53 | 02-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.225681E+11 | 0.603853E+10 | 501.00 | 0.161042E+11 | 0.646393E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 40484.02 | 08-OCT-07:01 | 33625.09 | 20-OCT-07:02 | 16064.13 | 08-OCT-07:02 | 8906.17 | 02-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.162511E+11 | 0.428709E+10 | 478.49 | 0.119289E+11 | 0.432227E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 39049.47 | 02-NOV-07:02 | 32955.61 | 05-NOV-07:02 | 10880.93 | 02-NOV-07:02 | 8605.98 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.108291E+11 | 0.282874E+10 | 485.96 | 0.801274E+10 | 0.281632E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-01:05 | 38170.56 | 12-DEC-08:62 | 29869.02 | 12-DEC-08:62 | 8301.54 | 12-DEC-08:62 | 8291.13 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.234568E+12 | 0.638274E+11 | 5809.92 | 0.165260E+12 | 0.693078E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.786093E+10 | 0.207253E+10 | 432.36 | 0.614853E+10 | 0.171239E+10 | 0.00 | 0.84 | 0.00 | 15115.39 | 11722.57 | 3505.15 | 3428.18 | 0.00 | |||||||
Maximum of Months | 0.332775E+11 | 0.917425E+10 | 504.40 | 0.212691E+11 | 0.120085E+11 | 0.00 | 1.00 | 0.00 | 41785.54 | 35319.06 | 21114.60 | 9853.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.529948E+10 | 0.140306E+10 | 314.53 | 0.411033E+10 | 0.118915E+10 | 0.00 | 0.97 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 18969.45 | 30-JAN-07:03 | 11490.33 | 30-JAN-07:03 | 7479.12 | 30-JAN-07:03 | 4022.84 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.628227E+10 | 0.167022E+10 | 301.08 | 0.480348E+10 | 0.147879E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 36252.69 | 09-FEB-07:03 | 21858.26 | 09-FEB-07:03 | 14394.43 | 09-FEB-07:03 | 7641.01 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.882290E+10 | 0.239137E+10 | 350.95 | 0.705963E+10 | 0.176327E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 37747.04 | 02-MAR-07:02 | 35266.03 | 28-MAR-06:02 | 15661.37 | 29-MAR-06:03 | 8782.62 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.120631E+11 | 0.330803E+10 | 350.05 | 0.941063E+10 | 0.265250E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 40517.51 | 30-APR-07:02 | 33069.57 | 29-APR-06:02 | 17371.19 | 30-APR-07:02 | 8554.61 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.180098E+11 | 0.502980E+10 | 373.19 | 0.138457E+11 | 0.416403E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41910.68 | 01-MAY-06:02 | 33874.86 | 05-MAY-06:02 | 23168.92 | 01-MAY-06:02 | 9207.80 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.219401E+11 | 0.598096E+10 | 366.07 | 0.149334E+11 | 0.700676E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 42664.40 | 25-JUN-07:01 | 31617.40 | 01-JUN-06:01 | 25540.89 | 19-JUN-06:04 | 9575.98 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.263183E+11 | 0.718726E+10 | 372.36 | 0.169344E+11 | 0.938391E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 42382.01 | 06-JUL-06:01 | 33720.40 | 04-JUL-07:01 | 27566.18 | 31-JUL-06:04 | 9619.41 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.283780E+11 | 0.770205E+10 | 381.96 | 0.177780E+11 | 0.106000E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 42378.28 | 31-AUG-06:01 | 28667.33 | 16-AUG-06:01 | 26033.18 | 21-AUG-06:06 | 9842.94 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.234254E+11 | 0.618845E+10 | 361.15 | 0.149288E+11 | 0.849656E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 42702.26 | 25-SEP-06:01 | 25944.76 | 05-SEP-06:01 | 28716.59 | 11-SEP-06:04 | 9437.89 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.184852E+11 | 0.487596E+10 | 367.59 | 0.129851E+11 | 0.550013E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42692.78 | 07-OCT-06:01 | 31954.41 | 20-OCT-06:02 | 26564.64 | 08-OCT-07:04 | 8895.10 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.130696E+11 | 0.342383E+10 | 352.14 | 0.940835E+10 | 0.366127E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 41098.08 | 03-NOV-06:02 | 31073.06 | 19-NOV-08:62 | 18522.44 | 03-NOV-06:02 | 8631.81 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.789811E+10 | 0.206627E+10 | 339.45 | 0.576729E+10 | 0.213082E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 39154.50 | 12-DEC-07:02 | 27403.91 | 12-DEC-07:02 | 13935.03 | 11-DEC-07:03 | 8422.95 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.189992E+12 | 0.512273E+11 | 4230.53 | 0.131965E+12 | 0.580272E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.529948E+10 | 0.140306E+10 | 301.08 | 0.411033E+10 | 0.118915E+10 | 0.00 | 0.97 | 0.00 | 18969.45 | 11490.33 | 7479.12 | 4022.84 | 0.00 | |||||||
Maximum of Months | 0.283780E+11 | 0.770205E+10 | 381.96 | 0.177780E+11 | 0.106000E+11 | 0.00 | 1.00 | 0.00 | 42702.26 | 35266.03 | 28716.59 | 9842.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.522126E+10 | 0.138380E+10 | 313.44 | 0.404634E+10 | 0.117492E+10 | 0.00 | 0.95 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 18514.12 | 30-JAN-07:03 | 11204.33 | 30-JAN-07:03 | 7309.79 | 30-JAN-07:03 | 3951.00 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.623385E+10 | 0.165861E+10 | 300.75 | 0.476555E+10 | 0.146830E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 36285.07 | 09-FEB-07:03 | 21877.50 | 09-FEB-07:03 | 14407.57 | 09-FEB-07:03 | 7647.71 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.879973E+10 | 0.238625E+10 | 350.53 | 0.704075E+10 | 0.175899E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 37812.21 | 02-MAR-07:02 | 35378.08 | 28-MAR-06:02 | 15836.46 | 29-MAR-06:03 | 8797.67 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.120862E+11 | 0.331468E+10 | 350.02 | 0.943110E+10 | 0.265512E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 40598.21 | 30-APR-07:02 | 33192.29 | 29-APR-06:02 | 17335.19 | 30-APR-07:02 | 8569.84 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.181111E+11 | 0.505590E+10 | 373.36 | 0.139318E+11 | 0.417934E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41996.97 | 01-MAY-06:02 | 33999.49 | 05-MAY-06:02 | 23116.20 | 01-MAY-06:02 | 9223.73 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.220633E+11 | 0.601277E+10 | 366.15 | 0.150329E+11 | 0.703044E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 42737.10 | 25-JUN-07:01 | 31784.90 | 01-JUN-06:01 | 25470.62 | 19-JUN-06:05 | 9592.18 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.264870E+11 | 0.723168E+10 | 372.44 | 0.170707E+11 | 0.941635E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 42454.23 | 06-JUL-06:01 | 33909.54 | 04-JUL-07:01 | 27397.28 | 31-JUL-06:04 | 9635.87 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.285441E+11 | 0.774557E+10 | 382.07 | 0.179117E+11 | 0.106324E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 42450.49 | 31-AUG-06:01 | 28833.34 | 16-AUG-06:01 | 25951.67 | 27-AUG-07:05 | 9859.80 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.235640E+11 | 0.622370E+10 | 361.19 | 0.150390E+11 | 0.852501E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 42775.03 | 25-SEP-06:03 | 26258.68 | 05-SEP-06:01 | 28568.59 | 11-SEP-06:04 | 9453.99 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.185932E+11 | 0.490182E+10 | 367.81 | 0.130724E+11 | 0.552079E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42765.53 | 07-OCT-06:01 | 32078.70 | 20-OCT-06:02 | 26626.62 | 08-OCT-07:05 | 8910.30 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.131029E+11 | 0.343245E+10 | 352.31 | 0.943658E+10 | 0.366636E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 41178.99 | 03-NOV-06:02 | 31387.41 | 19-NOV-08:62 | 18494.57 | 03-NOV-06:02 | 8646.93 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.786432E+10 | 0.205853E+10 | 339.20 | 0.574141E+10 | 0.212291E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 39222.79 | 12-DEC-07:02 | 27456.61 | 12-DEC-07:02 | 13975.49 | 11-DEC-07:03 | 8437.47 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.190671E+12 | 0.514058E+11 | 4229.28 | 0.132520E+12 | 0.581509E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.522126E+10 | 0.138380E+10 | 300.75 | 0.404634E+10 | 0.117492E+10 | 0.00 | 0.95 | 0.00 | 18514.12 | 11204.33 | 7309.79 | 3951.00 | 0.00 | |||||||
Maximum of Months | 0.285441E+11 | 0.774557E+10 | 382.07 | 0.179117E+11 | 0.106324E+11 | 0.00 | 1.00 | 0.00 | 42775.03 | 35378.08 | 28568.59 | 9859.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.496223E+10 | 0.131880E+10 | 306.61 | 0.382963E+10 | 0.113261E+10 | 0.00 | 0.87 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 16462.77 | 30-JAN-07:03 | 9900.38 | 30-JAN-07:03 | 6562.38 | 30-JAN-07:03 | 3605.82 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.600172E+10 | 0.160087E+10 | 297.58 | 0.457516E+10 | 0.142656E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 33658.56 | 09-FEB-07:03 | 20068.58 | 09-FEB-07:03 | 13589.97 | 09-FEB-07:03 | 7097.93 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.855419E+10 | 0.232521E+10 | 348.03 | 0.682919E+10 | 0.172500E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 37629.17 | 02-MAR-07:02 | 35012.62 | 28-MAR-06:02 | 14948.74 | 29-MAR-06:03 | 8758.90 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.118682E+11 | 0.326072E+10 | 349.21 | 0.924163E+10 | 0.262660E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 40416.92 | 30-APR-07:02 | 32817.88 | 29-APR-06:02 | 17411.83 | 30-APR-07:02 | 8533.42 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.179352E+11 | 0.501055E+10 | 373.24 | 0.137667E+11 | 0.416846E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41815.50 | 01-MAY-06:02 | 33626.27 | 05-MAY-06:02 | 23141.28 | 01-MAY-06:02 | 9186.33 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.218858E+11 | 0.596615E+10 | 365.99 | 0.148752E+11 | 0.701065E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 42565.06 | 25-JUN-07:01 | 31411.67 | 01-JUN-06:01 | 25425.53 | 19-JUN-06:04 | 9553.75 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.263370E+11 | 0.719013E+10 | 372.30 | 0.169343E+11 | 0.940269E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 42283.34 | 06-JUL-06:01 | 33556.91 | 04-JUL-07:01 | 27366.99 | 31-JUL-06:04 | 9596.93 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.283870E+11 | 0.770223E+10 | 381.93 | 0.177698E+11 | 0.106172E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 42279.61 | 31-AUG-06:02 | 28515.15 | 16-AUG-06:01 | 25953.46 | 27-AUG-07:05 | 9820.33 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.234014E+11 | 0.618141E+10 | 361.11 | 0.148970E+11 | 0.850436E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 42602.84 | 25-SEP-06:01 | 26061.14 | 05-SEP-06:01 | 28538.95 | 11-SEP-06:04 | 9415.89 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.184236E+11 | 0.486026E+10 | 367.93 | 0.129210E+11 | 0.550267E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42593.38 | 07-OCT-06:01 | 31742.82 | 20-OCT-06:02 | 26529.50 | 08-OCT-07:04 | 8874.35 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.128998E+11 | 0.338395E+10 | 352.00 | 0.926283E+10 | 0.363701E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 40997.75 | 03-NOV-06:02 | 30715.11 | 05-NOV-07:02 | 18614.38 | 03-NOV-06:02 | 8610.66 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.761408E+10 | 0.199742E+10 | 336.78 | 0.553851E+10 | 0.207557E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 39043.32 | 12-DEC-07:02 | 27142.39 | 12-DEC-07:02 | 13271.27 | 11-DEC-07:03 | 8401.13 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.188270E+12 | 0.507977E+11 | 4212.71 | 0.130441E+12 | 0.578294E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.496223E+10 | 0.131880E+10 | 297.58 | 0.382963E+10 | 0.113261E+10 | 0.00 | 0.87 | 0.00 | 16462.77 | 9900.38 | 6562.38 | 3605.82 | 0.00 | |||||||
Maximum of Months | 0.283870E+11 | 0.770223E+10 | 381.93 | 0.177698E+11 | 0.106172E+11 | 0.00 | 1.00 | 0.00 | 42602.84 | 35012.62 | 28538.95 | 9820.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.830846E+10 | 0.225262E+10 | 306.36 | 0.626307E+10 | 0.204539E+10 | 0.00 | 0.82 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 26994.01 | 30-JAN-08:63 | 17584.39 | 29-JAN-09:03 | 11081.16 | 30-JAN-08:63 | 6126.31 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.103394E+11 | 0.280834E+10 | 293.81 | 0.772908E+10 | 0.261027E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 53818.03 | 09-FEB-08:62 | 32698.83 | 06-FEB-08:62 | 21559.90 | 09-FEB-08:62 | 11563.97 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.151788E+11 | 0.419500E+10 | 345.28 | 0.119128E+11 | 0.326602E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 67235.40 | 02-MAR-08:62 | 54664.37 | 02-MAR-08:62 | 21878.47 | 29-MAR-07:03 | 15766.17 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.214126E+11 | 0.596312E+10 | 339.68 | 0.164578E+11 | 0.495480E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 72450.77 | 30-APR-08:62 | 59084.51 | 29-APR-07:02 | 32355.20 | 30-APR-08:62 | 15735.72 | 28-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.328407E+11 | 0.927994E+10 | 363.86 | 0.249666E+11 | 0.787418E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 74662.05 | 01-MAY-07:02 | 60794.58 | 11-MAY-07:01 | 41778.91 | 01-MAY-07:02 | 17327.34 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.401600E+11 | 0.110863E+11 | 357.84 | 0.270472E+11 | 0.131127E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 75885.32 | 25-JUN-08:61 | 56139.68 | 01-JUN-07:01 | 45003.45 | 19-JUN-07:05 | 17737.37 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.482023E+11 | 0.133348E+11 | 360.81 | 0.307844E+11 | 0.174178E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 75250.44 | 18-JUL-07:01 | 60882.41 | 04-JUL-08:61 | 47531.53 | 31-JUL-07:04 | 18052.25 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.522670E+11 | 0.143663E+11 | 373.14 | 0.324486E+11 | 0.198185E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 75308.54 | 08-AUG-07:01 | 51019.81 | 16-AUG-07:01 | 46365.94 | 21-AUG-07:07 | 18110.18 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.429168E+11 | 0.114817E+11 | 350.76 | 0.270139E+11 | 0.159029E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 76041.24 | 25-SEP-07:02 | 48372.60 | 02-SEP-07:01 | 50991.52 | 11-SEP-07:04 | 17614.75 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.334568E+11 | 0.893853E+10 | 357.77 | 0.233064E+11 | 0.101503E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 75815.51 | 02-OCT-07:02 | 56910.38 | 20-OCT-07:02 | 47139.27 | 08-OCT-08:05 | 16416.43 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.232581E+11 | 0.618226E+10 | 342.92 | 0.164439E+11 | 0.681419E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 72133.68 | 03-NOV-07:02 | 56538.32 | 19-NOV-09:02 | 29962.91 | 03-NOV-07:02 | 15785.94 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.132418E+11 | 0.353249E+10 | 331.12 | 0.942779E+10 | 0.381402E+10 | 0.00 | 1.00 | 03-DEC-09:03 | 0.00 | 01-DEC-00:10 | 69303.36 | 12-DEC-08:62 | 49112.49 | 12-DEC-08:62 | 22053.86 | 11-DEC-08:62 | 15219.28 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.341583E+12 | 0.934215E+11 | 4123.34 | 0.233802E+12 | 0.107781E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.830846E+10 | 0.225262E+10 | 293.81 | 0.626307E+10 | 0.204539E+10 | 0.00 | 0.82 | 0.00 | 26994.01 | 17584.39 | 11081.16 | 6126.31 | 0.00 | |||||||
Maximum of Months | 0.522670E+11 | 0.143663E+11 | 373.14 | 0.324486E+11 | 0.198185E+11 | 0.00 | 1.00 | 0.00 | 76041.24 | 60882.41 | 50991.52 | 18110.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.428555E+10 | 0.114366E+10 | 306.36 | 0.323498E+10 | 0.105058E+10 | 0.00 | 0.77 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 13197.00 | 30-JAN-08:63 | 8504.59 | 29-JAN-09:03 | 5415.60 | 30-JAN-08:63 | 2987.91 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.534761E+10 | 0.143008E+10 | 292.89 | 0.400399E+10 | 0.134362E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 25875.86 | 09-FEB-08:62 | 16189.28 | 06-FEB-08:62 | 10398.88 | 09-FEB-08:62 | 5465.26 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.787004E+10 | 0.214225E+10 | 345.51 | 0.618464E+10 | 0.168540E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 35520.22 | 02-MAR-08:62 | 28864.74 | 02-MAR-08:62 | 10503.20 | 29-MAR-07:03 | 8184.87 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.111393E+11 | 0.305593E+10 | 339.97 | 0.856435E+10 | 0.257492E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 38316.38 | 30-APR-08:62 | 30032.01 | 29-APR-07:02 | 17194.42 | 30-APR-08:62 | 8124.18 | 17-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.171099E+11 | 0.476574E+10 | 364.02 | 0.130011E+11 | 0.410876E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 39512.11 | 01-MAY-07:02 | 32063.97 | 11-MAY-07:01 | 22211.15 | 01-MAY-07:02 | 8996.87 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.209062E+11 | 0.569170E+10 | 357.94 | 0.140787E+11 | 0.682742E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 40106.20 | 25-JUN-08:61 | 29694.90 | 01-JUN-07:01 | 23965.57 | 26-JUN-07:04 | 9210.35 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.251038E+11 | 0.685012E+10 | 360.63 | 0.160321E+11 | 0.907164E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39746.74 | 18-JUL-07:01 | 32137.95 | 04-JUL-08:61 | 25418.37 | 31-JUL-07:02 | 9373.94 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.271954E+11 | 0.737393E+10 | 373.16 | 0.168821E+11 | 0.103133E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39801.36 | 08-AUG-07:01 | 26930.27 | 16-AUG-07:01 | 24591.45 | 21-AUG-07:07 | 9402.36 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.223386E+11 | 0.589355E+10 | 350.73 | 0.140672E+11 | 0.827139E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 40188.60 | 25-SEP-07:01 | 25506.09 | 02-SEP-07:01 | 27175.46 | 11-SEP-07:02 | 9146.39 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.174131E+11 | 0.458651E+10 | 358.93 | 0.121416E+11 | 0.527156E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 40069.30 | 02-OCT-07:01 | 30078.46 | 20-OCT-07:02 | 25006.87 | 08-OCT-08:05 | 8524.17 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.120919E+11 | 0.316677E+10 | 343.05 | 0.855768E+10 | 0.353419E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 38096.54 | 03-NOV-07:02 | 29857.24 | 19-NOV-09:02 | 15748.32 | 03-NOV-07:02 | 8196.59 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.686514E+10 | 0.180318E+10 | 331.28 | 0.489474E+10 | 0.197039E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 34985.53 | 12-DEC-08:62 | 24799.44 | 12-DEC-08:62 | 10972.49 | 11-DEC-08:62 | 7549.97 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.177666E+12 | 0.479034E+11 | 4124.46 | 0.121643E+12 | 0.560232E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.428555E+10 | 0.114366E+10 | 292.89 | 0.323498E+10 | 0.105058E+10 | 0.00 | 0.77 | 0.00 | 13197.00 | 8504.59 | 5415.60 | 2987.91 | 0.00 | |||||||
Maximum of Months | 0.271954E+11 | 0.737393E+10 | 373.16 | 0.168821E+11 | 0.103133E+11 | 0.00 | 1.00 | 0.00 | 40188.60 | 32137.95 | 27175.46 | 9402.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.421413E+10 | 0.112537E+10 | 305.44 | 0.317798E+10 | 0.103615E+10 | 0.00 | 0.74 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 12658.93 | 30-JAN-08:63 | 8128.69 | 29-JAN-09:03 | 5204.81 | 30-JAN-08:63 | 2887.01 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.528094E+10 | 0.141306E+10 | 291.97 | 0.395207E+10 | 0.132888E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 25226.03 | 09-FEB-08:62 | 15761.65 | 06-FEB-08:62 | 10181.39 | 09-FEB-08:62 | 5328.53 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.780053E+10 | 0.212429E+10 | 344.59 | 0.612807E+10 | 0.167246E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 35400.67 | 02-MAR-08:62 | 28737.94 | 02-MAR-08:62 | 10312.38 | 29-MAR-07:03 | 8157.72 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.110813E+11 | 0.304050E+10 | 339.83 | 0.851741E+10 | 0.256387E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 38189.44 | 30-APR-08:62 | 29694.58 | 29-APR-07:02 | 17160.02 | 30-APR-08:62 | 8097.34 | 17-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.170614E+11 | 0.475139E+10 | 364.04 | 0.129609E+11 | 0.410046E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 39381.56 | 01-MAY-07:02 | 31940.88 | 11-MAY-07:01 | 22157.22 | 01-MAY-07:02 | 8967.47 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.208587E+11 | 0.567743E+10 | 357.94 | 0.140415E+11 | 0.681724E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39975.10 | 25-JUN-08:02 | 29577.59 | 01-JUN-07:01 | 23893.06 | 26-JUN-07:04 | 9180.21 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.250623E+11 | 0.683674E+10 | 360.67 | 0.160000E+11 | 0.906222E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39620.40 | 18-JUL-07:01 | 32026.32 | 04-JUL-08:61 | 25328.19 | 31-JUL-07:02 | 9343.25 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.271530E+11 | 0.736010E+10 | 373.14 | 0.168496E+11 | 0.103034E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39671.27 | 08-AUG-07:02 | 26831.38 | 16-AUG-07:01 | 24510.70 | 21-AUG-07:07 | 9371.82 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.222960E+11 | 0.588076E+10 | 350.73 | 0.140346E+11 | 0.826136E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 40057.24 | 25-SEP-07:01 | 25400.61 | 02-SEP-07:01 | 27087.25 | 11-SEP-07:02 | 9116.50 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.173672E+11 | 0.457339E+10 | 358.93 | 0.121048E+11 | 0.526238E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 39938.33 | 02-OCT-07:02 | 29959.87 | 20-OCT-07:02 | 24935.17 | 08-OCT-08:05 | 8496.31 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.120376E+11 | 0.315269E+10 | 343.05 | 0.851484E+10 | 0.352280E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 37974.19 | 03-NOV-07:02 | 29740.81 | 19-NOV-09:02 | 15733.01 | 03-NOV-07:02 | 8169.59 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.679844E+10 | 0.178637E+10 | 330.87 | 0.484356E+10 | 0.195488E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 34444.00 | 12-DEC-08:62 | 24380.48 | 12-DEC-08:62 | 10800.16 | 11-DEC-08:62 | 7433.65 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.177011E+12 | 0.477221E+11 | 4121.20 | 0.121125E+12 | 0.558861E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.421413E+10 | 0.112537E+10 | 291.97 | 0.317798E+10 | 0.103615E+10 | 0.00 | 0.74 | 0.00 | 12658.93 | 8128.69 | 5204.81 | 2887.01 | 0.00 | |||||||
Maximum of Months | 0.271530E+11 | 0.736010E+10 | 373.14 | 0.168496E+11 | 0.103034E+11 | 0.00 | 1.00 | 0.00 | 40057.24 | 32026.32 | 27087.25 | 9371.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.407064E+10 | 0.108933E+10 | 301.86 | 0.306382E+10 | 0.100682E+10 | 0.00 | 0.66 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 10970.08 | 30-JAN-08:63 | 7132.00 | 28-JAN-14:00 | 4532.35 | 30-JAN-08:63 | 2568.49 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.515341E+10 | 0.138182E+10 | 288.39 | 0.385367E+10 | 0.129974E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 23292.29 | 09-FEB-08:62 | 14418.59 | 06-FEB-08:62 | 9514.91 | 09-FEB-08:62 | 4922.54 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.769220E+10 | 0.209870E+10 | 342.51 | 0.604058E+10 | 0.165162E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 35617.44 | 02-MAR-08:62 | 28860.07 | 02-MAR-08:62 | 9729.51 | 29-MAR-07:03 | 8208.89 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.110532E+11 | 0.303660E+10 | 339.50 | 0.849660E+10 | 0.255655E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 38426.07 | 30-APR-08:62 | 29245.50 | 29-APR-07:02 | 17284.57 | 30-APR-08:62 | 8148.16 | 17-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.171635E+11 | 0.478146E+10 | 363.98 | 0.130466E+11 | 0.411684E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 39629.26 | 01-MAY-07:02 | 32148.26 | 11-MAY-07:01 | 22311.54 | 01-MAY-07:02 | 9025.02 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.210108E+11 | 0.572060E+10 | 357.70 | 0.141634E+11 | 0.684736E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 40231.88 | 25-JUN-08:02 | 29797.22 | 01-JUN-07:01 | 24007.64 | 26-JUN-07:04 | 9239.21 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.252923E+11 | 0.690237E+10 | 360.63 | 0.161834E+11 | 0.910894E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39864.21 | 18-JUL-07:01 | 32299.22 | 04-JUL-08:61 | 25364.03 | 31-JUL-07:02 | 9403.28 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.274300E+11 | 0.743801E+10 | 373.16 | 0.170688E+11 | 0.103612E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39926.09 | 08-AUG-07:01 | 27119.11 | 16-AUG-07:01 | 24599.08 | 21-AUG-07:07 | 9432.05 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.224965E+11 | 0.593551E+10 | 350.57 | 0.141917E+11 | 0.830473E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 40314.54 | 25-SEP-07:01 | 25658.66 | 02-SEP-07:01 | 27148.09 | 11-SEP-07:04 | 9175.05 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.175052E+11 | 0.461014E+10 | 359.19 | 0.122156E+11 | 0.528959E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 40194.87 | 02-OCT-07:01 | 30159.93 | 20-OCT-07:02 | 25066.66 | 08-OCT-08:05 | 8550.88 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.120676E+11 | 0.316255E+10 | 343.05 | 0.853933E+10 | 0.352826E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 38210.24 | 03-NOV-07:02 | 29308.73 | 19-NOV-09:02 | 15805.64 | 03-NOV-07:02 | 8221.47 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.669852E+10 | 0.176285E+10 | 328.53 | 0.476809E+10 | 0.193043E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 33146.86 | 12-DEC-08:62 | 23380.01 | 12-DEC-08:62 | 10347.22 | 11-DEC-08:62 | 7155.75 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.177634E+12 | 0.479200E+11 | 4109.07 | 0.121632E+12 | 0.560021E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.407064E+10 | 0.108933E+10 | 288.39 | 0.306382E+10 | 0.100682E+10 | 0.00 | 0.66 | 0.00 | 10970.08 | 7132.00 | 4532.35 | 2568.49 | 0.00 | |||||||
Maximum of Months | 0.274300E+11 | 0.743801E+10 | 373.16 | 0.170688E+11 | 0.103612E+11 | 0.00 | 1.00 | 0.00 | 40314.54 | 32299.22 | 27148.09 | 9432.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.444724E+10 | 0.121556E+10 | 299.08 | 0.340747E+10 | 0.103976E+10 | 0.00 | 0.56 | 29-JAN-16:00 | 0.00 | 01-JAN-00:10 | 10160.78 | 29-JAN-16:00 | 7854.94 | 28-JAN-14:00 | 3344.79 | 29-JAN-16:00 | 2672.25 | 29-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.558917E+10 | 0.153434E+10 | 284.67 | 0.425298E+10 | 0.133619E+10 | 0.00 | 0.91 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 | 19077.97 | 09-FEB-08:62 | 11295.57 | 06-FEB-15:10 | 8294.58 | 09-FEB-08:62 | 4222.69 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.840628E+10 | 0.234933E+10 | 338.54 | 0.670500E+10 | 0.170127E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 40418.95 | 02-MAR-08:62 | 35614.72 | 02-MAR-08:62 | 7790.25 | 29-MAR-07:03 | 9550.09 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.123667E+11 | 0.348121E+10 | 339.47 | 0.966375E+10 | 0.270296E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 44816.22 | 30-APR-08:62 | 30271.61 | 29-APR-07:02 | 21825.98 | 30-APR-08:62 | 9509.60 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.195927E+11 | 0.559129E+10 | 365.78 | 0.151618E+11 | 0.443087E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 46276.83 | 30-MAY-07:01 | 37859.98 | 11-MAY-07:01 | 25484.82 | 01-MAY-07:02 | 10592.69 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.239644E+11 | 0.669120E+10 | 359.17 | 0.165382E+11 | 0.742618E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 46369.35 | 25-JUN-08:61 | 33922.43 | 01-JUN-07:01 | 28517.12 | 19-JUN-07:05 | 10838.67 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.288542E+11 | 0.808885E+10 | 362.39 | 0.189752E+11 | 0.987897E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 46016.91 | 26-JUL-07:03 | 38131.59 | 04-JUL-08:61 | 30190.65 | 05-JUL-07:05 | 11023.04 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.314783E+11 | 0.877169E+10 | 375.39 | 0.202271E+11 | 0.112512E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 46016.91 | 08-AUG-07:02 | 32369.15 | 06-AUG-08:61 | 29721.80 | 21-AUG-07:07 | 11061.66 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.257271E+11 | 0.696688E+10 | 352.73 | 0.167337E+11 | 0.899337E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 46464.62 | 25-SEP-07:02 | 29845.73 | 26-SEP-07:01 | 31435.08 | 11-SEP-07:04 | 10763.39 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.200752E+11 | 0.541157E+10 | 360.81 | 0.143377E+11 | 0.573752E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 46326.69 | 02-OCT-07:01 | 34695.22 | 20-OCT-07:02 | 29581.42 | 08-OCT-08:05 | 10031.18 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.136838E+11 | 0.367073E+10 | 344.06 | 0.990229E+10 | 0.378153E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 44599.90 | 03-NOV-07:02 | 33741.11 | 05-NOV-08:62 | 19740.44 | 03-NOV-07:02 | 9675.18 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.734532E+10 | 0.197916E+10 | 325.70 | 0.533426E+10 | 0.201107E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 34222.29 | 12-DEC-08:62 | 23235.67 | 12-DEC-08:62 | 10986.62 | 12-DEC-08:62 | 7490.39 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.201530E+12 | 0.557518E+11 | 4107.79 | 0.141240E+12 | 0.602909E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.444724E+10 | 0.121556E+10 | 284.67 | 0.340747E+10 | 0.103976E+10 | 0.00 | 0.56 | 0.00 | 10160.78 | 7854.94 | 3344.79 | 2672.25 | 0.00 | |||||||
Maximum of Months | 0.314783E+11 | 0.877169E+10 | 375.39 | 0.202271E+11 | 0.112512E+11 | 0.00 | 1.00 | 0.00 | 46464.62 | 38131.59 | 31435.08 | 11061.66 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.31 | 35.17 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.16 | 29.64 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 22.65 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.62 | 13.68 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.79 | 3.40 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.65 | 0.90 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 99.52 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.08 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.47 | 1.63 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.76 | 6.04 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.27 | 15.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.84 | 29.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.90 | 13.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.62 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.76 | 35.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.31 | 35.17 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.16 | 29.64 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 22.65 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.62 | 13.68 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.79 | 3.40 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.65 | 0.90 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 99.52 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.08 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.47 | 1.63 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.76 | 6.04 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.27 | 15.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.84 | 29.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.90 | 13.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.62 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.76 | 35.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.31 | 35.17 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.16 | 29.64 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 22.65 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.62 | 13.68 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.79 | 3.40 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.65 | 0.90 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 99.52 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.08 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.47 | 1.63 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.76 | 6.04 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.27 | 15.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.84 | 29.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.90 | 13.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.62 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.76 | 35.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.31 | 35.17 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.16 | 29.64 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 22.65 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.62 | 13.68 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.79 | 3.40 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.65 | 0.90 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 99.52 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.08 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.47 | 1.63 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.76 | 6.04 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.27 | 15.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.84 | 29.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.90 | 13.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.62 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.76 | 35.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 100.25 | 41.95 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 99.99 | 35.38 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.76 | 27.12 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 85.65 | 16.46 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 96.08 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 100.43 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 118.14 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 130.79 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 132.86 | 2.00 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 139.58 | 7.32 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 129.83 | 19.23 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.57 | 34.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 110.99 | 15.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 85.65 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 139.58 | 41.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 100.25 | 41.95 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 99.99 | 35.38 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.76 | 27.12 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 85.65 | 16.46 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 96.08 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 100.43 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 118.14 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 130.79 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 132.86 | 2.00 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 139.58 | 7.32 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 129.83 | 19.23 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.57 | 34.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 110.99 | 15.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 85.65 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 139.58 | 41.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.84 | 35.87 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.84 | 30.25 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.41 | 23.08 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.96 | 13.89 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.95 | 3.36 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 86.29 | 0.81 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 101.64 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 112.48 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 113.12 | 1.48 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.74 | 5.78 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.59 | 15.83 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.63 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.70 | 13.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.96 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.74 | 35.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.84 | 35.87 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.84 | 30.25 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.41 | 23.08 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.96 | 13.89 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.95 | 3.36 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 86.29 | 0.81 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 101.64 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 112.48 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 113.12 | 1.48 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.74 | 5.78 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.59 | 15.83 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.63 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.70 | 13.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.96 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.74 | 35.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 99.72 | 42.77 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 99.64 | 36.10 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.71 | 27.63 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 86.06 | 16.71 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 97.44 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 102.34 | 1.02 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 120.62 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 133.61 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 134.82 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 140.77 | 7.03 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 130.23 | 19.05 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.35 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 111.94 | 15.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 86.06 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 140.77 | 42.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.93 | 36.79 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.84 | 31.41 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.22 | 24.46 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.13 | 15.54 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.89 | 4.14 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.49 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.67 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.73 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.14 | 1.88 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.47 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.24 | 17.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.66 | 31.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.68 | 14.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.13 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.47 | 36.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.93 | 36.79 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.84 | 31.41 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.22 | 24.46 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.13 | 15.54 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.89 | 4.14 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.49 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.67 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.73 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.14 | 1.88 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.47 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.24 | 17.98 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.66 | 31.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.68 | 14.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.13 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.47 | 36.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.28 | 43.60 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.10 | 37.24 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 90.99 | 29.08 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.64 | 18.56 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.38 | 5.00 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.39 | 1.44 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.18 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.35 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.47 | 2.30 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.40 | 8.75 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.13 | 21.46 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 104.81 | 36.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 108.99 | 16.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.64 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.40 | 43.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.01 | 36.57 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.88 | 31.27 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.24 | 24.41 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.10 | 15.65 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.66 | 4.31 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.13 | 1.27 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.07 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.13 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 108.76 | 2.01 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.33 | 7.53 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.21 | 18.11 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.69 | 30.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.49 | 14.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.33 | 36.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.01 | 36.57 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.88 | 31.27 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.24 | 24.41 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.10 | 15.65 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.66 | 4.31 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.13 | 1.27 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.07 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.13 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 108.76 | 2.01 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.33 | 7.53 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.21 | 18.11 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.69 | 30.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.49 | 14.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.33 | 36.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.38 | 43.33 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.15 | 37.07 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.01 | 29.02 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.61 | 18.69 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.10 | 5.21 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 96.97 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 113.47 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 126.65 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.02 | 2.47 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.25 | 9.09 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.09 | 21.62 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 104.84 | 36.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 108.78 | 16.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.61 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.25 | 43.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.20 | 36.12 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.03 | 30.86 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.37 | 24.03 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.23 | 15.32 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.88 | 4.15 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.41 | 1.18 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.36 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.45 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 108.98 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.46 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.32 | 17.80 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.82 | 30.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.68 | 14.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.23 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.46 | 36.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.20 | 36.12 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.03 | 30.86 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.37 | 24.03 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.23 | 15.32 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 78.88 | 4.15 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.41 | 1.18 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.36 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.45 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 108.98 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.46 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.32 | 17.80 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.82 | 30.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.68 | 14.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.23 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.46 | 36.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.60 | 42.81 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.33 | 36.60 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.18 | 28.57 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.76 | 18.30 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.36 | 5.02 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.29 | 1.48 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 113.82 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.02 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.28 | 2.35 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.39 | 8.82 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.22 | 21.26 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 104.99 | 36.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.00 | 16.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.76 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.39 | 42.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.64 | 34.96 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.36 | 29.76 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.61 | 22.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.09 | 3.75 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.67 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.50 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.72 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.16 | 1.72 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.52 | 6.76 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.30 | 16.84 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.04 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.88 | 13.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.52 | 34.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.64 | 34.96 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.36 | 29.76 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.61 | 22.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.09 | 3.75 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.67 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.50 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.72 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.16 | 1.72 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.52 | 6.76 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.30 | 16.84 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.04 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.88 | 13.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.52 | 34.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.64 | 34.96 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.36 | 29.76 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.61 | 22.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.09 | 3.75 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.67 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.50 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.72 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.16 | 1.72 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.52 | 6.76 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.30 | 16.84 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.04 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.88 | 13.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.52 | 34.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.64 | 34.96 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.36 | 29.76 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.61 | 22.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 14.41 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.09 | 3.75 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.67 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.50 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.72 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.16 | 1.72 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.52 | 6.76 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.30 | 16.84 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.04 | 29.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.88 | 13.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.52 | 34.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.10 | 41.45 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.70 | 35.30 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.45 | 27.31 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.87 | 17.20 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.64 | 4.53 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.64 | 1.22 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.04 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.40 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.51 | 2.10 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.46 | 8.15 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.18 | 20.12 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.23 | 35.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.25 | 15.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.87 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.46 | 41.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.10 | 41.45 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.70 | 35.30 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.45 | 27.31 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.87 | 17.20 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.64 | 4.53 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.64 | 1.22 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.04 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.40 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.51 | 2.10 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.46 | 8.15 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.18 | 20.12 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.23 | 35.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.25 | 15.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.87 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.46 | 41.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.49 | 34.80 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.25 | 29.54 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.62 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.52 | 14.06 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.80 | 3.54 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.66 | 0.85 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.66 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.93 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.97 | 1.57 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.89 | 6.40 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.38 | 16.45 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.95 | 29.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.32 | 13.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.89 | 34.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.49 | 34.80 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.25 | 29.54 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.62 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.52 | 14.06 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.80 | 3.54 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.66 | 0.85 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.66 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.93 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.97 | 1.57 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.89 | 6.40 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.38 | 16.45 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.95 | 29.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.32 | 13.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.89 | 34.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.96 | 41.24 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.61 | 35.04 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.48 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.11 | 16.80 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.45 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.77 | 1.07 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 115.36 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.78 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.44 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.90 | 7.74 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.30 | 19.66 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.17 | 34.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.76 | 15.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.11 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.90 | 41.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.57 | 34.66 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.32 | 29.42 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.68 | 22.55 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.57 | 13.98 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.86 | 3.51 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.73 | 0.83 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.72 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.99 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.02 | 1.56 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.93 | 6.37 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.42 | 16.39 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.00 | 29.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.38 | 13.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.93 | 34.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.57 | 34.66 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.32 | 29.42 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.68 | 22.55 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.57 | 13.98 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.86 | 3.51 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.73 | 0.83 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.72 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.99 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.02 | 1.56 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.93 | 6.37 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.42 | 16.39 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.00 | 29.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.38 | 13.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.93 | 34.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.06 | 41.09 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.68 | 34.89 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.55 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.17 | 16.71 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.52 | 4.25 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.85 | 1.05 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 115.43 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.85 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.50 | 1.91 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.95 | 7.69 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.35 | 19.59 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.23 | 34.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.83 | 15.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.17 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.95 | 41.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.74 | 34.32 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.11 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.75 | 22.33 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.54 | 13.92 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.63 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.38 | 0.89 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.15 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.36 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.60 | 1.65 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.74 | 6.53 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.36 | 16.43 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.07 | 29.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.21 | 13.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.54 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.74 | 34.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.74 | 34.32 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.11 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.75 | 22.33 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.54 | 13.92 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.63 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.38 | 0.89 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.15 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.36 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.60 | 1.65 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.74 | 6.53 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.36 | 16.43 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.07 | 29.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.21 | 13.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.54 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.74 | 34.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.26 | 40.69 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.83 | 34.54 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.63 | 26.57 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.14 | 16.64 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.25 | 4.33 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.43 | 1.12 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.75 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.09 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.00 | 2.01 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.71 | 7.89 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.28 | 19.64 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.31 | 34.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.63 | 15.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.14 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.71 | 40.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.82 | 33.22 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.42 | 28.05 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 21.58 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 70.68 | 13.88 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 77.37 | 3.98 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 80.35 | 1.24 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 92.87 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 103.64 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 106.32 | 2.24 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 113.83 | 7.65 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 107.41 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.90 | 28.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 90.39 | 13.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 70.68 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 113.83 | 33.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.82 | 33.22 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.42 | 28.05 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.47 | 21.58 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 70.68 | 13.88 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 77.37 | 3.98 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 80.35 | 1.24 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 92.87 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 103.64 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 106.32 | 2.24 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 113.83 | 7.65 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 107.41 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.90 | 28.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 90.39 | 13.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 70.68 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 113.83 | 33.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.35 | 39.40 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.80 | 33.29 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.29 | 25.69 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.11 | 16.59 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 91.54 | 4.81 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 94.83 | 1.55 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 109.66 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 122.48 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 126.12 | 2.75 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 135.44 | 9.22 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 128.14 | 20.39 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.10 | 33.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 107.46 | 15.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.11 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 135.44 | 39.40 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223149E+09 | 94210025.73 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201180E+09 | 71704976.13 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204815E+09 | 60675141.38 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185636E+09 | 35470385.81 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.216388E+09 | 9112718.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.219420E+09 | 2343373.48 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.266557E+09 | 61270.83 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294846E+09 | 41305.42 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.288934E+09 | 4221856.75 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.312722E+09 | 16165277.64 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280639E+09 | 41413872.63 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235276E+09 | 78303290.92 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292956E+10 | 0.413723E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185636E+09 | 41305.42 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.312722E+09 | 94210025.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223149E+09 | 94210025.73 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201180E+09 | 71704976.13 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204815E+09 | 60675141.38 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185636E+09 | 35470385.81 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.216388E+09 | 9112718.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.219420E+09 | 2343373.48 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.266557E+09 | 61270.83 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294846E+09 | 41305.42 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.288934E+09 | 4221856.75 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.312722E+09 | 16165277.64 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280639E+09 | 41413872.63 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235276E+09 | 78303290.92 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292956E+10 | 0.413723E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185636E+09 | 41305.42 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.312722E+09 | 94210025.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223149E+09 | 94210025.73 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201180E+09 | 71704976.13 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204815E+09 | 60675141.38 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185636E+09 | 35470385.81 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.216388E+09 | 9112718.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.219420E+09 | 2343373.48 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.266557E+09 | 61270.83 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294846E+09 | 41305.42 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.288934E+09 | 4221856.75 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.312722E+09 | 16165277.64 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280639E+09 | 41413872.63 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235276E+09 | 78303290.92 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292956E+10 | 0.413723E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185636E+09 | 41305.42 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.312722E+09 | 94210025.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223149E+09 | 94210025.73 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201180E+09 | 71704976.13 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204815E+09 | 60675141.38 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185636E+09 | 35470385.81 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.216388E+09 | 9112718.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.219420E+09 | 2343373.48 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.266557E+09 | 61270.83 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294846E+09 | 41305.42 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.288934E+09 | 4221856.75 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.312722E+09 | 16165277.64 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280639E+09 | 41413872.63 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235276E+09 | 78303290.92 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292956E+10 | 0.413723E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185636E+09 | 41305.42 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.312722E+09 | 94210025.73 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.268503E+09 | 0.112370E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.241903E+09 | 85595076.97 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.245772E+09 | 72650056.37 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.222012E+09 | 42660976.70 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.257344E+09 | 11073555.90 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.260324E+09 | 2937843.17 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.316419E+09 | 84516.45 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.350316E+09 | 55749.09 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.344383E+09 | 5173394.29 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.373862E+09 | 19605680.87 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.336516E+09 | 49836417.71 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282747E+09 | 93573523.37 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.350010E+10 | 0.495617E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.222012E+09 | 55749.09 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.373862E+09 | 0.112370E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.268503E+09 | 0.112370E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.241903E+09 | 85595076.97 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.245772E+09 | 72650056.37 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.222012E+09 | 42660976.70 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.257344E+09 | 11073555.90 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.260324E+09 | 2937843.17 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.316419E+09 | 84516.45 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.350316E+09 | 55749.09 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.344383E+09 | 5173394.29 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.373862E+09 | 19605680.87 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.336516E+09 | 49836417.71 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282747E+09 | 93573523.37 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.350010E+10 | 0.495617E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.222012E+09 | 55749.09 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.373862E+09 | 0.112370E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.221876E+09 | 96066813.18 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200403E+09 | 73191417.31 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204659E+09 | 61820615.55 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186522E+09 | 36011796.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.219491E+09 | 9010460.67 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.223662E+09 | 2101244.96 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.272240E+09 | 42705.33 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.301271E+09 | 18793.86 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.293220E+09 | 3840610.86 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.315354E+09 | 15490542.56 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281469E+09 | 41040475.97 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234718E+09 | 79195992.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.295488E+10 | 0.417831E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186522E+09 | 18793.86 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.315354E+09 | 96066813.18 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.221876E+09 | 96066813.18 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200403E+09 | 73191417.31 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204659E+09 | 61820615.55 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186522E+09 | 36011796.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.219491E+09 | 9010460.67 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.223662E+09 | 2101244.96 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.272240E+09 | 42705.33 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.301271E+09 | 18793.86 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.293220E+09 | 3840610.86 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.315354E+09 | 15490542.56 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281469E+09 | 41040475.97 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234718E+09 | 79195992.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.295488E+10 | 0.417831E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186522E+09 | 18793.86 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.315354E+09 | 96066813.18 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.267079E+09 | 0.114544E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.241050E+09 | 87335677.70 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.245636E+09 | 74006549.22 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.223070E+09 | 43312016.46 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.260972E+09 | 10962248.14 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.265266E+09 | 2650298.24 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.323077E+09 | 58557.24 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.357873E+09 | 28209.46 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.349447E+09 | 4711875.09 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.377025E+09 | 18816511.06 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.337558E+09 | 49388104.98 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282166E+09 | 94616462.71 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.353022E+10 | 0.500430E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.223070E+09 | 28209.46 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.377025E+09 | 0.114544E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222114E+09 | 98550878.62 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200404E+09 | 75979221.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204151E+09 | 65502318.83 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184362E+09 | 40291682.46 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211311E+09 | 11078590.74 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.213817E+09 | 2997482.42 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258916E+09 | 133660.36 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288535E+09 | 52783.05 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282901E+09 | 4879831.15 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309267E+09 | 19424300.42 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280569E+09 | 46599337.91 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234797E+09 | 83218859.31 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289114E+10 | 0.448709E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184362E+09 | 52783.05 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309267E+09 | 98550878.62 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222114E+09 | 98550878.62 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200404E+09 | 75979221.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204151E+09 | 65502318.83 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184362E+09 | 40291682.46 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211311E+09 | 11078590.74 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.213817E+09 | 2997482.42 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258916E+09 | 133660.36 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288535E+09 | 52783.05 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282901E+09 | 4879831.15 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309267E+09 | 19424300.42 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280569E+09 | 46599337.91 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234797E+09 | 83218859.31 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289114E+10 | 0.448709E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184362E+09 | 52783.05 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309267E+09 | 98550878.62 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.265906E+09 | 0.116779E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.239740E+09 | 90086557.99 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.243711E+09 | 77881915.14 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219384E+09 | 48108026.53 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.250103E+09 | 13388397.14 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.252432E+09 | 3743996.97 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.305819E+09 | 178026.44 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.341095E+09 | 71453.80 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.335592E+09 | 5971161.57 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.368020E+09 | 23447160.34 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.334706E+09 | 55634437.97 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.280712E+09 | 98756173.96 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.343722E+10 | 0.534046E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219384E+09 | 71453.80 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.368020E+09 | 0.116779E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222333E+09 | 97948372.84 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200513E+09 | 75642950.04 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204199E+09 | 65382243.50 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184297E+09 | 40572175.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.210689E+09 | 11543088.52 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.212890E+09 | 3294145.81 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.257317E+09 | 177972.88 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.286945E+09 | 66571.33 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.281907E+09 | 5222529.48 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.308913E+09 | 20180277.69 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280491E+09 | 46949305.33 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234868E+09 | 83014559.20 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.288536E+10 | 0.449994E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184297E+09 | 66571.33 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.308913E+09 | 97948372.84 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222333E+09 | 97948372.84 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200513E+09 | 75642950.04 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204199E+09 | 65382243.50 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184297E+09 | 40572175.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.210689E+09 | 11543088.52 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.212890E+09 | 3294145.81 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.257317E+09 | 177972.88 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.286945E+09 | 66571.33 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.281907E+09 | 5222529.48 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.308913E+09 | 20180277.69 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280491E+09 | 46949305.33 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234868E+09 | 83014559.20 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.288536E+10 | 0.449994E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184297E+09 | 66571.33 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.308913E+09 | 97948372.84 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.266168E+09 | 0.116067E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.239872E+09 | 89689810.46 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.243768E+09 | 77740231.86 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219307E+09 | 48440032.86 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.249372E+09 | 13944812.82 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.251348E+09 | 4108440.93 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.303928E+09 | 232945.57 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.339217E+09 | 91961.63 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.334427E+09 | 6390320.66 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.367604E+09 | 24344663.41 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.334613E+09 | 56048468.66 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.280798E+09 | 98514811.56 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.343042E+10 | 0.535614E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219307E+09 | 91961.63 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.367604E+09 | 0.116067E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222839E+09 | 96739786.34 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200871E+09 | 74662603.97 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204563E+09 | 64353838.23 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184622E+09 | 39716209.71 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211265E+09 | 11118577.56 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.213602E+09 | 3069236.12 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258096E+09 | 159922.42 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.287784E+09 | 54734.55 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282477E+09 | 4977931.35 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309237E+09 | 19576632.01 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280770E+09 | 46146261.87 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235213E+09 | 82017805.75 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289134E+10 | 0.442594E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184622E+09 | 54734.55 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309237E+09 | 96739786.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222839E+09 | 96739786.34 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200871E+09 | 74662603.97 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204563E+09 | 64353838.23 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184622E+09 | 39716209.71 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211265E+09 | 11118577.56 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.213602E+09 | 3069236.12 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258096E+09 | 159922.42 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.287784E+09 | 54734.55 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282477E+09 | 4977931.35 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309237E+09 | 19576632.01 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280770E+09 | 46146261.87 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235213E+09 | 82017805.75 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289134E+10 | 0.442594E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184622E+09 | 54734.55 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309237E+09 | 96739786.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.266775E+09 | 0.114649E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.240302E+09 | 88540105.39 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244205E+09 | 76532579.87 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219695E+09 | 47433477.55 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.250048E+09 | 13440590.27 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.252179E+09 | 3834080.31 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.304844E+09 | 210457.29 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.340201E+09 | 75568.74 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.335094E+09 | 6095178.70 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.367986E+09 | 23632885.41 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.334946E+09 | 55105408.25 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281214E+09 | 97344578.66 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.343749E+10 | 0.526894E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219695E+09 | 75568.74 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.367986E+09 | 0.114649E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224021E+09 | 93643185.63 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201667E+09 | 71997371.66 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205197E+09 | 61506740.82 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184862E+09 | 37339447.57 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211838E+09 | 10055647.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214274E+09 | 2531666.25 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258464E+09 | 128599.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288511E+09 | 28005.14 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282938E+09 | 4453433.61 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309403E+09 | 18105836.40 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280712E+09 | 43657077.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235797E+09 | 79196954.90 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289768E+10 | 0.422644E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184862E+09 | 28005.14 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309403E+09 | 93643185.63 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224021E+09 | 93643185.63 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201667E+09 | 71997371.66 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205197E+09 | 61506740.82 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184862E+09 | 37339447.57 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211838E+09 | 10055647.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214274E+09 | 2531666.25 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258464E+09 | 128599.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288511E+09 | 28005.14 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282938E+09 | 4453433.61 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309403E+09 | 18105836.40 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280712E+09 | 43657077.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235797E+09 | 79196954.90 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289768E+10 | 0.422644E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184862E+09 | 28005.14 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309403E+09 | 93643185.63 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224021E+09 | 93643185.63 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201667E+09 | 71997371.66 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205197E+09 | 61506740.82 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184862E+09 | 37339447.57 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211838E+09 | 10055647.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214274E+09 | 2531666.25 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258464E+09 | 128599.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288511E+09 | 28005.14 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282938E+09 | 4453433.61 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309403E+09 | 18105836.40 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280712E+09 | 43657077.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235797E+09 | 79196954.90 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289768E+10 | 0.422644E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184862E+09 | 28005.14 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309403E+09 | 93643185.63 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224021E+09 | 93643185.63 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201667E+09 | 71997371.66 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205197E+09 | 61506740.82 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184862E+09 | 37339447.57 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211838E+09 | 10055647.66 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214274E+09 | 2531666.25 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.258464E+09 | 128599.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.288511E+09 | 28005.14 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.282938E+09 | 4453433.61 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309403E+09 | 18105836.40 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280712E+09 | 43657077.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235797E+09 | 79196954.90 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289768E+10 | 0.422644E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184862E+09 | 28005.14 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309403E+09 | 93643185.63 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268105E+09 | 0.111014E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241189E+09 | 85406040.77 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244927E+09 | 73159279.70 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219988E+09 | 44590276.45 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.250811E+09 | 12141472.04 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.253090E+09 | 3159095.93 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.305442E+09 | 166654.76 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.341218E+09 | 40173.85 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.335694E+09 | 5436098.66 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.368159E+09 | 21826593.74 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.334845E+09 | 52139258.20 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281855E+09 | 94024673.23 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.344532E+10 | 0.503103E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219988E+09 | 40173.85 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.368159E+09 | 0.111014E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268105E+09 | 0.111014E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241189E+09 | 85406040.77 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244927E+09 | 73159279.70 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219988E+09 | 44590276.45 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.250811E+09 | 12141472.04 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.253090E+09 | 3159095.93 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.305442E+09 | 166654.76 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.341218E+09 | 40173.85 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.335694E+09 | 5436098.66 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.368159E+09 | 21826593.74 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.334845E+09 | 52139258.20 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281855E+09 | 94024673.23 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.344532E+10 | 0.503103E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219988E+09 | 40173.85 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.368159E+09 | 0.111014E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223628E+09 | 93195796.36 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201408E+09 | 71461373.09 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205228E+09 | 60700416.13 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185377E+09 | 36438395.96 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213731E+09 | 9481506.51 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.216856E+09 | 2191530.88 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.261581E+09 | 105435.32 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.291766E+09 | 11573.98 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285034E+09 | 4078581.98 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310406E+09 | 17152547.57 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280913E+09 | 42648117.20 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235568E+09 | 78524786.38 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291149E+10 | 0.415990E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185377E+09 | 11573.98 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310406E+09 | 93195796.36 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223628E+09 | 93195796.36 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201408E+09 | 71461373.09 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205228E+09 | 60700416.13 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185377E+09 | 36438395.96 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213731E+09 | 9481506.51 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.216856E+09 | 2191530.88 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.261581E+09 | 105435.32 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.291766E+09 | 11573.98 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285034E+09 | 4078581.98 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310406E+09 | 17152547.57 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280913E+09 | 42648117.20 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235568E+09 | 78524786.38 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291149E+10 | 0.415990E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185377E+09 | 11573.98 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310406E+09 | 93195796.36 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.267745E+09 | 0.110467E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.240966E+09 | 84762349.78 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245020E+09 | 72213398.41 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220602E+09 | 43547723.61 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.252962E+09 | 11475722.06 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.256008E+09 | 2761446.30 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.308987E+09 | 138623.16 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.344930E+09 | 19953.05 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.338099E+09 | 4986211.40 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369353E+09 | 20719856.21 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335144E+09 | 50967779.04 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281675E+09 | 93225156.77 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.346149E+10 | 0.495285E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220602E+09 | 19953.05 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369353E+09 | 0.110467E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223834E+09 | 92838042.59 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201566E+09 | 71161781.28 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205380E+09 | 60408674.86 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185502E+09 | 36237022.82 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213896E+09 | 9408948.06 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.217036E+09 | 2161358.26 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.261743E+09 | 105504.58 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.291922E+09 | 10436.81 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285175E+09 | 4049603.71 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310517E+09 | 17058741.54 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281021E+09 | 42481863.28 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235708E+09 | 78255585.64 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291330E+10 | 0.414178E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185502E+09 | 10436.81 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310517E+09 | 92838042.59 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223834E+09 | 92838042.59 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201566E+09 | 71161781.28 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205380E+09 | 60408674.86 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185502E+09 | 36237022.82 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213896E+09 | 9408948.06 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.217036E+09 | 2161358.26 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.261743E+09 | 105504.58 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.291922E+09 | 10436.81 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285175E+09 | 4049603.71 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310517E+09 | 17058741.54 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281021E+09 | 42481863.28 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235708E+09 | 78255585.64 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291330E+10 | 0.414178E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185502E+09 | 10436.81 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310517E+09 | 92838042.59 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.267992E+09 | 0.110045E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241156E+09 | 84408762.43 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245203E+09 | 71868050.75 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220753E+09 | 43309532.05 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.253158E+09 | 11388556.20 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.256221E+09 | 2724494.97 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.309180E+09 | 138571.27 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.345117E+09 | 18520.84 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.338267E+09 | 4950903.95 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369486E+09 | 20608368.11 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335274E+09 | 50770784.14 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281843E+09 | 92906713.41 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.346365E+10 | 0.493138E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220753E+09 | 18520.84 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369486E+09 | 0.110045E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224283E+09 | 91932644.98 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201871E+09 | 70428720.78 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205571E+09 | 59806672.43 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185443E+09 | 36071728.73 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213288E+09 | 9573616.48 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.216119E+09 | 2310908.52 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260213E+09 | 128375.69 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290221E+09 | 20517.89 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284079E+09 | 4265860.84 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309987E+09 | 17501643.20 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280871E+09 | 42593579.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235900E+09 | 77776180.02 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290784E+10 | 0.412410E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185443E+09 | 20517.89 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309987E+09 | 91932644.98 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224283E+09 | 91932644.98 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201871E+09 | 70428720.78 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205571E+09 | 59806672.43 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185443E+09 | 36071728.73 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213288E+09 | 9573616.48 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.216119E+09 | 2310908.52 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260213E+09 | 128375.69 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290221E+09 | 20517.89 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284079E+09 | 4265860.84 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309987E+09 | 17501643.20 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280871E+09 | 42593579.73 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235900E+09 | 77776180.02 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290784E+10 | 0.412410E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185443E+09 | 20517.89 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309987E+09 | 91932644.98 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268527E+09 | 0.108985E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241520E+09 | 83552050.77 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245430E+09 | 71164966.84 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220682E+09 | 43122374.71 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.252432E+09 | 11591068.56 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.255129E+09 | 2908346.24 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.307355E+09 | 167496.30 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.343089E+09 | 33274.02 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.336967E+09 | 5220121.16 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.368853E+09 | 21141451.62 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335093E+09 | 50911187.94 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.282073E+09 | 92349299.02 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.345715E+10 | 0.491146E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220682E+09 | 33274.02 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.368853E+09 | 0.108985E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224511E+09 | 88982283.51 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201809E+09 | 67848743.58 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204814E+09 | 57805745.53 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.183211E+09 | 35965446.28 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.207215E+09 | 10648458.50 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.208256E+09 | 3209944.63 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.248740E+09 | 305046.11 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.277584E+09 | 137168.55 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.275584E+09 | 5813320.76 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.304893E+09 | 20489916.58 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.278407E+09 | 44206882.03 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235436E+09 | 76557501.89 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.285046E+10 | 0.411970E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.183211E+09 | 137168.55 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.304893E+09 | 88982283.51 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224511E+09 | 88982283.51 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201809E+09 | 67848743.58 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204814E+09 | 57805745.53 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.183211E+09 | 35965446.28 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.207215E+09 | 10648458.50 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.208256E+09 | 3209944.63 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.248740E+09 | 305046.11 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.277584E+09 | 137168.55 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.275584E+09 | 5813320.76 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.304893E+09 | 20489916.58 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.278407E+09 | 44206882.03 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235436E+09 | 76557501.89 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.285046E+10 | 0.411970E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.183211E+09 | 137168.55 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.304893E+09 | 88982283.51 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268787E+09 | 0.105522E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241438E+09 | 80530310.01 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244515E+09 | 68817131.10 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.218005E+09 | 43010894.23 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.245189E+09 | 12883761.41 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.245787E+09 | 4009772.44 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.293709E+09 | 393571.65 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.328053E+09 | 184436.95 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.326891E+09 | 7116575.22 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.362763E+09 | 24700883.47 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.332140E+09 | 52841286.43 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281505E+09 | 90925065.84 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.338878E+10 | 0.490935E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.218005E+09 | 184436.95 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.362763E+09 | 0.105522E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.75 | 224.60 | 326.99 | 153.73 | 173.26 | 0.00 | 0.00 |
February | 532.62 | 189.32 | 307.06 | 125.60 | 181.46 | 0.00 | 0.00 |
March | 489.40 | 144.86 | 252.72 | 68.61 | 184.11 | 0.00 | 0.00 |
April | 457.78 | 87.66 | 198.66 | 21.06 | 177.60 | 0.00 | 0.00 |
May | 515.32 | 21.88 | 168.28 | 2.58 | 165.70 | 0.00 | 0.00 |
June | 539.48 | 5.88 | 158.48 | 0.20 | 158.28 | 0.00 | 0.00 |
July | 634.36 | 0.15 | 158.48 | 1.35 | 157.13 | 0.00 | 0.00 |
August | 701.92 | 0.10 | 183.82 | 13.02 | 170.80 | 0.00 | 0.00 |
September | 711.61 | 10.51 | 242.37 | 55.55 | 186.82 | 0.00 | 0.00 |
October | 746.19 | 38.78 | 317.31 | 126.15 | 191.16 | 0.00 | 0.00 |
November | 692.74 | 102.36 | 350.06 | 168.75 | 181.30 | 0.00 | 0.00 |
December | 562.50 | 186.81 | 324.96 | 160.52 | 164.44 | 0.00 | 0.00 |
Annual Sum or Average | 593.56 | 83.91 | 248.75 | 74.49 | 174.26 | 0.00 | 0.00 |
Minimum of Months | 457.78 | 0.10 | 158.48 | 0.20 | 157.13 | 0.00 | 0.00 |
Maximum of Months | 746.19 | 224.60 | 350.06 | 168.75 | 191.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.39 | 114.50 | 163.49 | 76.87 | 86.63 | 0.00 | 0.00 |
February | 265.32 | 96.61 | 153.53 | 62.80 | 90.73 | 0.00 | 0.00 |
March | 244.53 | 73.79 | 126.36 | 34.31 | 92.05 | 0.00 | 0.00 |
April | 229.98 | 44.50 | 99.33 | 10.53 | 88.80 | 0.00 | 0.00 |
May | 261.33 | 10.82 | 84.14 | 1.29 | 82.85 | 0.00 | 0.00 |
June | 274.92 | 2.64 | 79.24 | 0.10 | 79.14 | 0.00 | 0.00 |
July | 323.91 | 0.05 | 79.24 | 0.67 | 78.56 | 0.00 | 0.00 |
August | 358.58 | 0.02 | 91.91 | 6.51 | 85.40 | 0.00 | 0.00 |
September | 361.07 | 4.78 | 121.18 | 27.77 | 93.41 | 0.00 | 0.00 |
October | 376.24 | 18.59 | 158.65 | 63.07 | 95.58 | 0.00 | 0.00 |
November | 347.41 | 50.72 | 175.03 | 84.38 | 90.65 | 0.00 | 0.00 |
December | 280.62 | 94.46 | 162.48 | 80.26 | 82.22 | 0.00 | 0.00 |
Annual Sum or Average | 299.34 | 42.37 | 124.37 | 37.24 | 87.13 | 0.00 | 0.00 |
Minimum of Months | 229.98 | 0.02 | 79.24 | 0.10 | 78.56 | 0.00 | 0.00 |
Maximum of Months | 376.24 | 114.50 | 175.03 | 84.38 | 95.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.13 | 117.19 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 264.78 | 100.05 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 243.43 | 77.99 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 226.89 | 49.65 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 251.17 | 13.27 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 262.37 | 3.76 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 307.52 | 0.17 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 342.80 | 0.07 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 347.76 | 6.07 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 368.34 | 23.26 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 345.62 | 57.42 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.13 | 99.01 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 292.35 | 45.39 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 226.89 | 0.07 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 368.34 | 117.19 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.39 | 116.47 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 264.92 | 99.61 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 243.49 | 77.85 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 226.81 | 49.99 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 250.43 | 13.83 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 261.24 | 4.13 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 305.62 | 0.22 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 340.91 | 0.08 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 346.54 | 6.49 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 367.92 | 24.16 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 345.52 | 57.85 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.22 | 98.77 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 291.77 | 45.52 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 226.81 | 0.08 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 367.92 | 116.47 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.00 | 115.04 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 265.39 | 98.32 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 243.93 | 76.63 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 227.21 | 48.94 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 251.11 | 13.32 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 262.11 | 3.85 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 306.54 | 0.20 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 341.91 | 0.07 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 347.24 | 6.19 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 368.30 | 23.44 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 345.87 | 56.87 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.63 | 97.59 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 292.37 | 44.78 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 227.21 | 0.07 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 368.30 | 115.04 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 534.76 | 222.74 | 326.32 | 153.42 | 172.90 | 0.00 | 0.00 |
February | 532.84 | 189.65 | 306.43 | 125.34 | 181.08 | 0.00 | 0.00 |
March | 489.34 | 146.49 | 252.20 | 68.47 | 183.73 | 0.00 | 0.00 |
April | 455.02 | 92.03 | 198.25 | 21.02 | 177.23 | 0.00 | 0.00 |
May | 503.65 | 24.08 | 167.93 | 2.57 | 165.36 | 0.00 | 0.00 |
June | 525.96 | 6.34 | 158.16 | 0.20 | 157.96 | 0.00 | 0.00 |
July | 614.07 | 0.32 | 158.15 | 1.34 | 156.81 | 0.00 | 0.00 |
August | 685.66 | 0.07 | 183.44 | 13.00 | 170.45 | 0.00 | 0.00 |
September | 695.65 | 11.07 | 241.87 | 55.43 | 186.44 | 0.00 | 0.00 |
October | 736.98 | 43.34 | 316.66 | 125.89 | 190.77 | 0.00 | 0.00 |
November | 691.57 | 107.60 | 349.34 | 168.41 | 180.93 | 0.00 | 0.00 |
December | 562.61 | 188.48 | 324.29 | 160.19 | 164.10 | 0.00 | 0.00 |
Annual Sum or Average | 586.04 | 85.51 | 248.24 | 74.34 | 173.90 | 0.00 | 0.00 |
Minimum of Months | 455.02 | 0.07 | 158.15 | 0.20 | 156.81 | 0.00 | 0.00 |
Maximum of Months | 736.98 | 222.74 | 349.34 | 168.41 | 190.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.95 | 110.83 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.11 | 94.12 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 244.73 | 72.29 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 228.15 | 44.92 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 254.04 | 11.36 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 266.10 | 2.76 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 310.69 | 0.13 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 346.65 | 0.02 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 350.37 | 5.07 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 369.68 | 20.54 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.05 | 52.57 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.07 | 93.44 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 294.41 | 42.09 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 228.15 | 0.02 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 369.68 | 110.83 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 267.20 | 110.41 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.32 | 93.72 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 244.91 | 71.94 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 228.30 | 44.67 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 254.24 | 11.28 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 266.32 | 2.72 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 310.88 | 0.13 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 346.83 | 0.01 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 350.55 | 5.03 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 369.82 | 20.43 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.19 | 52.37 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.23 | 93.12 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 294.59 | 41.90 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 228.30 | 0.01 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 369.82 | 110.41 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 267.73 | 109.34 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.72 | 92.76 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 245.14 | 71.23 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 228.23 | 44.47 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 253.51 | 11.48 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 265.19 | 2.90 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 309.06 | 0.16 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 344.81 | 0.03 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 349.20 | 5.30 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 369.19 | 20.96 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.00 | 52.51 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.46 | 92.56 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 294.04 | 41.73 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 228.23 | 0.03 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 369.19 | 109.34 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.00 | 105.84 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.64 | 89.38 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 244.23 | 68.86 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 225.47 | 44.34 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 246.27 | 12.76 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 255.52 | 4.02 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 295.40 | 0.37 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 329.76 | 0.17 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 338.76 | 7.23 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 363.11 | 24.52 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 342.96 | 54.50 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.90 | 91.11 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 288.23 | 41.69 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 225.47 | 0.17 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 363.11 | 105.84 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142960E+10 | 0.601579E+09 | 0.875803E+09 | 0.411755E+09 | 0.464049E+09 | 0.00 | 0.00 |
February | 0.128852E+10 | 0.458009E+09 | 0.742828E+09 | 0.303849E+09 | 0.438979E+09 | 0.00 | 0.00 |
March | 0.131080E+10 | 0.388000E+09 | 0.676886E+09 | 0.183771E+09 | 0.493115E+09 | 0.00 | 0.00 |
April | 0.118657E+10 | 0.227202E+09 | 0.514919E+09 | 54591163.78 | 0.460328E+09 | 0.00 | 0.00 |
May | 0.138024E+10 | 58595949.81 | 0.450720E+09 | 6902333.46 | 0.443818E+09 | 0.00 | 0.00 |
June | 0.139833E+10 | 15245803.44 | 0.410782E+09 | 508358.34 | 0.410274E+09 | 0.00 | 0.00 |
July | 0.169907E+10 | 413213.45 | 0.424463E+09 | 3606644.05 | 0.420857E+09 | 0.00 | 0.00 |
August | 0.188002E+10 | 276563.02 | 0.492344E+09 | 34884546.30 | 0.457459E+09 | 0.00 | 0.00 |
September | 0.184450E+10 | 27230210.28 | 0.628220E+09 | 0.143975E+09 | 0.484245E+09 | 0.00 | 0.00 |
October | 0.199861E+10 | 0.103868E+09 | 0.849879E+09 | 0.337875E+09 | 0.512004E+09 | 0.00 | 0.00 |
November | 0.179558E+10 | 0.265320E+09 | 0.907344E+09 | 0.437407E+09 | 0.469937E+09 | 0.00 | 0.00 |
December | 0.150660E+10 | 0.500359E+09 | 0.870367E+09 | 0.429935E+09 | 0.440432E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187184E+11 | 0.264610E+10 | 0.784456E+10 | 0.234906E+10 | 0.549550E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118657E+10 | 276563.02 | 0.410782E+09 | 508358.34 | 0.410274E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199861E+10 | 0.601579E+09 | 0.907344E+09 | 0.437407E+09 | 0.512004E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710830E+09 | 0.306677E+09 | 0.437902E+09 | 0.205877E+09 | 0.232024E+09 | 0.00 | 0.00 |
February | 0.641856E+09 | 0.233718E+09 | 0.371414E+09 | 0.151925E+09 | 0.219489E+09 | 0.00 | 0.00 |
March | 0.654954E+09 | 0.197648E+09 | 0.338443E+09 | 91885413.74 | 0.246557E+09 | 0.00 | 0.00 |
April | 0.596112E+09 | 0.115334E+09 | 0.257460E+09 | 27295581.89 | 0.230164E+09 | 0.00 | 0.00 |
May | 0.699952E+09 | 28981330.95 | 0.225360E+09 | 3451166.73 | 0.221909E+09 | 0.00 | 0.00 |
June | 0.712589E+09 | 6851301.46 | 0.205391E+09 | 254179.17 | 0.205137E+09 | 0.00 | 0.00 |
July | 0.867556E+09 | 142955.12 | 0.212232E+09 | 1803322.02 | 0.210428E+09 | 0.00 | 0.00 |
August | 0.960414E+09 | 65781.82 | 0.246172E+09 | 17442273.15 | 0.228730E+09 | 0.00 | 0.00 |
September | 0.935884E+09 | 12390737.48 | 0.314110E+09 | 71987522.14 | 0.242123E+09 | 0.00 | 0.00 |
October | 0.100773E+10 | 49794686.49 | 0.424939E+09 | 0.168937E+09 | 0.256002E+09 | 0.00 | 0.00 |
November | 0.900495E+09 | 0.131468E+09 | 0.453672E+09 | 0.218704E+09 | 0.234968E+09 | 0.00 | 0.00 |
December | 0.751601E+09 | 0.253008E+09 | 0.435183E+09 | 0.214967E+09 | 0.220216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.943997E+10 | 0.133608E+10 | 0.392228E+10 | 0.117453E+10 | 0.274775E+10 | 0.00 | 0.00 |
Minimum of Months | 0.596112E+09 | 65781.82 | 0.205391E+09 | 254179.17 | 0.205137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100773E+10 | 0.306677E+09 | 0.453672E+09 | 0.218704E+09 | 0.256002E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710135E+09 | 0.313880E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.640548E+09 | 0.242044E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.652013E+09 | 0.208886E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.588108E+09 | 0.128691E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.672723E+09 | 35544065.76 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.680064E+09 | 9736827.27 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.823651E+09 | 444886.30 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.918164E+09 | 176688.23 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.901391E+09 | 15728228.51 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.986553E+09 | 62294568.10 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.895843E+09 | 0.148832E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.750306E+09 | 0.265194E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.921950E+10 | 0.143145E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.588108E+09 | 176688.23 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.986553E+09 | 0.313880E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710833E+09 | 0.311964E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.640897E+09 | 0.240975E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.652165E+09 | 0.208504E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.587899E+09 | 0.129584E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.670749E+09 | 37029884.22 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.677126E+09 | 10694888.13 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.818561E+09 | 588348.60 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.913106E+09 | 223595.44 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.898238E+09 | 16833336.38 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.985429E+09 | 64704209.69 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.895595E+09 | 0.149946E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.750533E+09 | 0.264544E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.920113E+10 | 0.143559E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.587899E+09 | 223595.44 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.985429E+09 | 0.311964E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.712452E+09 | 0.308128E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.642042E+09 | 0.237865E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.653329E+09 | 0.205240E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.588938E+09 | 0.126865E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.672577E+09 | 35676074.98 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.679381E+09 | 9969709.13 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.821036E+09 | 530091.10 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.915769E+09 | 184124.61 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.900045E+09 | 16048452.16 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.986460E+09 | 62785169.97 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.896485E+09 | 0.147397E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.751639E+09 | 0.261380E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.922015E+10 | 0.141207E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.588938E+09 | 184124.61 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.986460E+09 | 0.308128E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143229E+10 | 0.596600E+09 | 0.874007E+09 | 0.410910E+09 | 0.463097E+09 | 0.00 | 0.00 |
February | 0.128904E+10 | 0.458800E+09 | 0.741304E+09 | 0.303226E+09 | 0.438078E+09 | 0.00 | 0.00 |
March | 0.131064E+10 | 0.392345E+09 | 0.675497E+09 | 0.183394E+09 | 0.492103E+09 | 0.00 | 0.00 |
April | 0.117942E+10 | 0.238536E+09 | 0.513863E+09 | 54479171.23 | 0.459384E+09 | 0.00 | 0.00 |
May | 0.134897E+10 | 64503570.04 | 0.449796E+09 | 6888173.48 | 0.442908E+09 | 0.00 | 0.00 |
June | 0.136328E+10 | 16442153.14 | 0.409939E+09 | 507315.46 | 0.409432E+09 | 0.00 | 0.00 |
July | 0.164474E+10 | 847361.15 | 0.423593E+09 | 3599245.10 | 0.419993E+09 | 0.00 | 0.00 |
August | 0.183648E+10 | 191519.33 | 0.491334E+09 | 34812981.43 | 0.456521E+09 | 0.00 | 0.00 |
September | 0.180314E+10 | 28682184.24 | 0.626932E+09 | 0.143680E+09 | 0.483252E+09 | 0.00 | 0.00 |
October | 0.197393E+10 | 0.116074E+09 | 0.848135E+09 | 0.337182E+09 | 0.510954E+09 | 0.00 | 0.00 |
November | 0.179254E+10 | 0.278905E+09 | 0.905483E+09 | 0.436510E+09 | 0.468973E+09 | 0.00 | 0.00 |
December | 0.150690E+10 | 0.504836E+09 | 0.868581E+09 | 0.429053E+09 | 0.439528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184814E+11 | 0.269676E+10 | 0.782846E+10 | 0.234424E+10 | 0.548422E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117942E+10 | 191519.33 | 0.409939E+09 | 507315.46 | 0.409432E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197393E+10 | 0.596600E+09 | 0.905483E+09 | 0.436510E+09 | 0.510954E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.715000E+09 | 0.296859E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.643783E+09 | 0.227685E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.655475E+09 | 0.193614E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.591355E+09 | 0.116424E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.680423E+09 | 30437507.40 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.689719E+09 | 7142292.54 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.832148E+09 | 348808.95 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.928461E+09 | 43036.61 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.908165E+09 | 13141607.76 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.990164E+09 | 55024188.06 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.896969E+09 | 0.136263E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.752810E+09 | 0.250274E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.928447E+10 | 0.132726E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.591355E+09 | 43036.61 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.990164E+09 | 0.296859E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.715660E+09 | 0.295720E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.644288E+09 | 0.226731E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.655964E+09 | 0.192685E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.591758E+09 | 0.115783E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.680948E+09 | 30205181.01 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.690291E+09 | 7044828.34 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.832665E+09 | 348889.34 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.928961E+09 | 39188.32 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.908615E+09 | 13048180.50 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.990520E+09 | 54725081.25 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.897315E+09 | 0.135733E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.753258E+09 | 0.249418E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.929024E+10 | 0.132148E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.591758E+09 | 39188.32 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.990520E+09 | 0.295720E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.717092E+09 | 0.292849E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.645261E+09 | 0.224409E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.656572E+09 | 0.190778E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.591568E+09 | 0.115265E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.679007E+09 | 30737176.56 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.687365E+09 | 7528392.86 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.827781E+09 | 424176.51 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.923530E+09 | 73858.53 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.905121E+09 | 13748984.17 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.988827E+09 | 56143280.77 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.896835E+09 | 0.136097E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.753872E+09 | 0.247901E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.927283E+10 | 0.131596E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.591568E+09 | 73858.53 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.988827E+09 | 0.292849E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.717808E+09 | 0.283485E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.645056E+09 | 0.216227E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.654142E+09 | 0.184428E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.584427E+09 | 0.114941E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.659619E+09 | 34179788.28 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.662298E+09 | 10428036.62 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.791189E+09 | 1003263.93 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.883221E+09 | 458522.82 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.878057E+09 | 18740532.49 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.972548E+09 | 65679266.96 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.888951E+09 | 0.141252E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.752376E+09 | 0.244040E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.908969E+10 | 0.131486E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.584427E+09 | 458522.82 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.972548E+09 | 0.283485E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280587E+09 | -167383063.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113203744.7 | 58.99 | 0.00 | 0.00 |
February | 0.249665E+09 | -147681279.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101983659.9 | 58.99 | 0.00 | 0.00 |
March | 0.267121E+09 | -154562370.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112558243.7 | 58.99 | 0.00 | 0.00 |
April | 0.241100E+09 | -132629933.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108470502.7 | 58.99 | 0.00 | 0.00 |
May | 0.233294E+09 | -122092171.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111201368.4 | 58.99 | 0.00 | 0.00 |
June | 0.215875E+09 | -108671175.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107203819.4 | 58.99 | 0.00 | 0.00 |
July | 0.216799E+09 | -106576034.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110223430.5 | 58.99 | 0.00 | 0.00 |
August | 0.223813E+09 | -113793081.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110020376.0 | 58.99 | 0.00 | 0.00 |
September | 0.227420E+09 | -120423589.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106996590.6 | 58.99 | 0.00 | 0.00 |
October | 0.249731E+09 | -138692579.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111037947.8 | 58.99 | 0.00 | 0.00 |
November | 0.256440E+09 | -148293937.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108146111.6 | 58.99 | 0.00 | 0.00 |
December | 0.276980E+09 | -164401611.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112578485.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293883E+10 | -0.162520E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131362E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215875E+09 | -167383063.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113203744.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280587E+09 | -106576034.8 | 0.00 | 0.00 | 744.00 | 0.00 | -101983659.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280185E+09 | -167381828.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112802904.6 | 58.99 | 0.00 | 0.00 |
February | 0.249342E+09 | -147689511.8 | 0.00 | 0.00 | 672.00 | 0.00 | -101652910.8 | 58.99 | 0.00 | 0.00 |
March | 0.266855E+09 | -154577538.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112277400.0 | 58.99 | 0.00 | 0.00 |
April | 0.240941E+09 | -132634058.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108306459.9 | 58.99 | 0.00 | 0.00 |
May | 0.233289E+09 | -122096098.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111192914.7 | 58.99 | 0.00 | 0.00 |
June | 0.215980E+09 | -108684289.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107295438.2 | 58.99 | 0.00 | 0.00 |
July | 0.217001E+09 | -106569549.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110431551.5 | 58.99 | 0.00 | 0.00 |
August | 0.224091E+09 | -113792564.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110298586.1 | 58.99 | 0.00 | 0.00 |
September | 0.227568E+09 | -120414164.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107153494.1 | 58.99 | 0.00 | 0.00 |
October | 0.249804E+09 | -138703369.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111100781.6 | 58.99 | 0.00 | 0.00 |
November | 0.256373E+09 | -148296167.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108076358.2 | 58.99 | 0.00 | 0.00 |
December | 0.276751E+09 | -164403892.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112347488.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293818E+10 | -0.162524E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131294E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215980E+09 | -167381828.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112802904.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280185E+09 | -106569549.4 | 0.00 | 0.00 | 744.00 | 0.00 | -101652910.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259324E+09 | -147197881.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112126507.8 | 58.99 | 0.00 | 0.00 |
February | 0.230866E+09 | -130010454.7 | 0.00 | 0.00 | 672.00 | 0.00 | -100855226.2 | 58.98 | 0.00 | 0.00 |
March | 0.249052E+09 | -137926262.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111125612.0 | 58.99 | 0.00 | 0.00 |
April | 0.223217E+09 | -116653530.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106563749.2 | 58.99 | 0.00 | 0.00 |
May | 0.217013E+09 | -108313420.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108699419.3 | 58.99 | 0.00 | 0.00 |
June | 0.201525E+09 | -96753335.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104771468.4 | 59.00 | 0.00 | 0.00 |
July | 0.200501E+09 | -93181523.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107319535.4 | 58.98 | 0.00 | 0.00 |
August | 0.208995E+09 | -101673314.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107321374.5 | 58.98 | 0.00 | 0.00 |
September | 0.210306E+09 | -105876310.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104429648.5 | 58.99 | 0.00 | 0.00 |
October | 0.230600E+09 | -122003863.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108596557.4 | 58.99 | 0.00 | 0.00 |
November | 0.237277E+09 | -130941137.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106335875.3 | 58.98 | 0.00 | 0.00 |
December | 0.254774E+09 | -143541177.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111232842.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.272345E+10 | -0.143407E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128938E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.200501E+09 | -147197881.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112126507.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259324E+09 | -93181523.8 | 0.00 | 0.00 | 744.00 | 0.00 | -100855226.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259427E+09 | -147196920.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112230165.8 | 58.99 | 0.00 | 0.00 |
February | 0.230919E+09 | -130026364.8 | 0.00 | 0.00 | 672.00 | 0.00 | -100892783.7 | 58.98 | 0.00 | 0.00 |
March | 0.249073E+09 | -137923012.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111149831.0 | 58.99 | 0.00 | 0.00 |
April | 0.223162E+09 | -116634315.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106527725.4 | 58.99 | 0.00 | 0.00 |
May | 0.216862E+09 | -108330585.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108531649.1 | 58.99 | 0.00 | 0.00 |
June | 0.201354E+09 | -96769011.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104584847.6 | 58.99 | 0.00 | 0.00 |
July | 0.200278E+09 | -93175537.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107102125.9 | 58.99 | 0.00 | 0.00 |
August | 0.208753E+09 | -101619190.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107133671.3 | 58.99 | 0.00 | 0.00 |
September | 0.210110E+09 | -105849508.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104260098.2 | 59.00 | 0.00 | 0.00 |
October | 0.230440E+09 | -122004733.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108435764.5 | 58.99 | 0.00 | 0.00 |
November | 0.237215E+09 | -130919929.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106294745.1 | 58.99 | 0.00 | 0.00 |
December | 0.254810E+09 | -143547120.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111263156.9 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.272240E+10 | -0.143400E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128841E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.200278E+09 | -147196920.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112230165.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259427E+09 | -93175537.0 | 0.00 | 0.00 | 744.00 | 0.00 | -100892783.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252138E+09 | -139102439.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113035391.1 | 58.99 | 0.00 | 0.00 |
February | 0.224516E+09 | -122924605.1 | 0.00 | 0.00 | 672.00 | 0.00 | -101590975.8 | 58.99 | 0.00 | 0.00 |
March | 0.242419E+09 | -130508887.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111909788.9 | 58.99 | 0.00 | 0.00 |
April | 0.217605E+09 | -110379769.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107225581.2 | 58.99 | 0.00 | 0.00 |
May | 0.211690E+09 | -102448603.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109241429.5 | 58.99 | 0.00 | 0.00 |
June | 0.196817E+09 | -91582559.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105234706.1 | 58.99 | 0.00 | 0.00 |
July | 0.195729E+09 | -88112563.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107616014.0 | 58.99 | 0.00 | 0.00 |
August | 0.203899E+09 | -96149611.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107749222.0 | 58.99 | 0.00 | 0.00 |
September | 0.204976E+09 | -100207406.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104769038.7 | 58.99 | 0.00 | 0.00 |
October | 0.224370E+09 | -115311090.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109058533.9 | 58.99 | 0.00 | 0.00 |
November | 0.230591E+09 | -123656336.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106934335.4 | 58.99 | 0.00 | 0.00 |
December | 0.247681E+09 | -135720655.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111959908.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265243E+10 | -0.135610E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129632E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195729E+09 | -139102439.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113035391.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.252138E+09 | -88112563.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101590975.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252186E+09 | -139101914.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113084096.8 | 58.99 | 0.00 | 0.00 |
February | 0.224575E+09 | -122925383.4 | 0.00 | 0.00 | 672.00 | 0.00 | -101649165.5 | 58.99 | 0.00 | 0.00 |
March | 0.242496E+09 | -130502946.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111992805.9 | 59.00 | 0.00 | 0.00 |
April | 0.217710E+09 | -110395622.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107314500.1 | 58.99 | 0.00 | 0.00 |
May | 0.211829E+09 | -102429724.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109398960.8 | 58.99 | 0.00 | 0.00 |
June | 0.196998E+09 | -91583012.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105415258.9 | 58.99 | 0.00 | 0.00 |
July | 0.195940E+09 | -88115191.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107824562.3 | 58.99 | 0.00 | 0.00 |
August | 0.204117E+09 | -96179988.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107936557.2 | 58.98 | 0.00 | 0.00 |
September | 0.205144E+09 | -100148208.1 | 0.00 | 0.00 | 720.00 | 0.00 | -104995518.4 | 59.00 | 0.00 | 0.00 |
October | 0.224523E+09 | -115316261.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109206741.8 | 58.99 | 0.00 | 0.00 |
November | 0.230704E+09 | -123653600.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107050444.2 | 58.99 | 0.00 | 0.00 |
December | 0.247747E+09 | -135732251.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112015026.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265397E+10 | -0.135608E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129788E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195940E+09 | -139101914.8 | 0.00 | 0.00 | 672.00 | 0.00 | -113084096.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252186E+09 | -88115191.9 | 0.00 | 0.00 | 744.00 | 0.00 | -101649165.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252251E+09 | -139105811.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113144843.7 | 58.99 | 0.00 | 0.00 |
February | 0.224628E+09 | -122931811.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101695702.3 | 58.99 | 0.00 | 0.00 |
March | 0.242541E+09 | -130505287.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112035325.5 | 58.99 | 0.00 | 0.00 |
April | 0.217748E+09 | -110410551.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107337462.0 | 58.98 | 0.00 | 0.00 |
May | 0.211851E+09 | -102421181.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109430229.7 | 58.99 | 0.00 | 0.00 |
June | 0.197016E+09 | -91576130.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105440307.6 | 58.99 | 0.00 | 0.00 |
July | 0.195955E+09 | -88113079.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107842239.2 | 58.99 | 0.00 | 0.00 |
August | 0.204127E+09 | -96156499.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107970870.9 | 58.99 | 0.00 | 0.00 |
September | 0.205180E+09 | -100221397.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104958267.4 | 58.99 | 0.00 | 0.00 |
October | 0.224539E+09 | -115285731.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109253390.1 | 59.00 | 0.00 | 0.00 |
November | 0.230731E+09 | -123663247.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107067678.5 | 58.99 | 0.00 | 0.00 |
December | 0.247794E+09 | -135722061.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112072030.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265436E+10 | -0.135611E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129825E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195955E+09 | -139105811.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113144843.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252251E+09 | -88113079.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101695702.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.135280E+11 | 0.103567E+11 | 28108.05 | 30-JAN-08:63 | 18223.18 | 0.00 |
February | 0.00 | 0.00 | 0.157549E+11 | 0.118352E+11 | 57675.36 | 09-FEB-08:62 | 35030.33 | 0.00 |
March | 0.00 | 0.00 | 0.220371E+11 | 0.173021E+11 | 73998.15 | 02-MAR-08:62 | 64263.94 | 0.00 |
April | 0.00 | 0.00 | 0.310781E+11 | 0.236166E+11 | 79995.18 | 30-APR-07:02 | 45325.50 | 0.00 |
May | 0.00 | 0.00 | 0.460548E+11 | 0.347506E+11 | 82273.05 | 30-MAY-07:01 | 43268.20 | 0.00 |
June | 0.00 | 0.00 | 0.559804E+11 | 0.373330E+11 | 83907.18 | 19-JUN-07:01 | 39618.28 | 0.00 |
July | 0.00 | 0.00 | 0.671241E+11 | 0.432162E+11 | 83835.75 | 26-JUL-07:01 | 40741.43 | 0.00 |
August | 0.00 | 0.00 | 0.709636E+11 | 0.446033E+11 | 83835.75 | 08-AUG-07:02 | 33832.17 | 0.00 |
September | 0.00 | 0.00 | 0.603833E+11 | 0.379351E+11 | 83669.16 | 11-SEP-07:01 | 41726.82 | 0.00 |
October | 0.00 | 0.00 | 0.474850E+11 | 0.330554E+11 | 83552.80 | 08-OCT-07:01 | 40578.68 | 0.00 |
November | 0.00 | 0.00 | 0.328789E+11 | 0.236898E+11 | 80034.10 | 03-NOV-07:02 | 48203.39 | 0.00 |
December | 0.00 | 0.00 | 0.201438E+11 | 0.145065E+11 | 77894.90 | 12-DEC-08:62 | 53251.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.483412E+12 | 0.332200E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.135280E+11 | 0.103567E+11 | 28108.05 | 18223.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.709636E+11 | 0.446033E+11 | 83907.18 | 64263.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.786093E+10 | 0.614853E+10 | 15115.39 | 29-JAN-08:63 | 11722.57 | 0.00 |
February | 0.00 | 0.00 | 0.871942E+10 | 0.669612E+10 | 28691.77 | 09-FEB-08:62 | 20241.80 | 0.00 |
March | 0.00 | 0.00 | 0.115835E+11 | 0.925077E+10 | 37029.84 | 02-MAR-08:62 | 33072.54 | 0.00 |
April | 0.00 | 0.00 | 0.154089E+11 | 0.119801E+11 | 38847.95 | 30-APR-07:02 | 27847.72 | 0.00 |
May | 0.00 | 0.00 | 0.219697E+11 | 0.169232E+11 | 39645.74 | 30-MAY-07:01 | 26742.14 | 0.00 |
June | 0.00 | 0.00 | 0.263367E+11 | 0.180349E+11 | 40597.90 | 19-JUN-07:01 | 24378.60 | 0.00 |
July | 0.00 | 0.00 | 0.314827E+11 | 0.206703E+11 | 40877.89 | 18-JUL-07:01 | 24050.81 | 0.00 |
August | 0.00 | 0.00 | 0.332775E+11 | 0.212691E+11 | 41785.54 | 08-AUG-07:01 | 22044.46 | 0.00 |
September | 0.00 | 0.00 | 0.282798E+11 | 0.182410E+11 | 40431.25 | 10-SEP-07:01 | 25239.51 | 0.00 |
October | 0.00 | 0.00 | 0.225681E+11 | 0.161042E+11 | 40484.02 | 08-OCT-07:01 | 24896.35 | 0.00 |
November | 0.00 | 0.00 | 0.162511E+11 | 0.119289E+11 | 39049.47 | 02-NOV-07:02 | 28168.54 | 0.00 |
December | 0.00 | 0.00 | 0.108291E+11 | 0.801274E+10 | 38170.56 | 12-DEC-08:62 | 29869.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234568E+12 | 0.165260E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.786093E+10 | 0.614853E+10 | 15115.39 | 11722.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.332775E+11 | 0.212691E+11 | 41785.54 | 33072.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.529948E+10 | 0.411033E+10 | 18969.45 | 30-JAN-07:03 | 11490.33 | 0.00 |
February | 0.00 | 0.00 | 0.628227E+10 | 0.480348E+10 | 36252.69 | 09-FEB-07:03 | 21858.26 | 0.00 |
March | 0.00 | 0.00 | 0.882290E+10 | 0.705963E+10 | 37747.04 | 02-MAR-07:02 | 31168.96 | 0.00 |
April | 0.00 | 0.00 | 0.120631E+11 | 0.941063E+10 | 40517.51 | 30-APR-07:02 | 23146.32 | 0.00 |
May | 0.00 | 0.00 | 0.180098E+11 | 0.138457E+11 | 41910.68 | 01-MAY-06:02 | 18741.76 | 0.00 |
June | 0.00 | 0.00 | 0.219401E+11 | 0.149334E+11 | 42664.40 | 25-JUN-07:01 | 18631.70 | 0.00 |
July | 0.00 | 0.00 | 0.263183E+11 | 0.169344E+11 | 42382.01 | 06-JUL-06:01 | 18658.22 | 0.00 |
August | 0.00 | 0.00 | 0.283780E+11 | 0.177780E+11 | 42378.28 | 31-AUG-06:01 | 19381.52 | 0.00 |
September | 0.00 | 0.00 | 0.234254E+11 | 0.149288E+11 | 42702.26 | 25-SEP-06:01 | 17119.78 | 0.00 |
October | 0.00 | 0.00 | 0.184852E+11 | 0.129851E+11 | 42692.78 | 07-OCT-06:01 | 18602.62 | 0.00 |
November | 0.00 | 0.00 | 0.130696E+11 | 0.940835E+10 | 41098.08 | 03-NOV-06:02 | 22575.64 | 0.00 |
December | 0.00 | 0.00 | 0.789811E+10 | 0.576729E+10 | 39154.50 | 12-DEC-07:02 | 27403.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189992E+12 | 0.131965E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.529948E+10 | 0.411033E+10 | 18969.45 | 11490.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283780E+11 | 0.177780E+11 | 42702.26 | 31168.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.522126E+10 | 0.404634E+10 | 18514.12 | 30-JAN-07:03 | 11204.33 | 0.00 |
February | 0.00 | 0.00 | 0.623385E+10 | 0.476555E+10 | 36285.07 | 09-FEB-07:03 | 21877.50 | 0.00 |
March | 0.00 | 0.00 | 0.879973E+10 | 0.704075E+10 | 37812.21 | 02-MAR-07:02 | 31216.76 | 0.00 |
April | 0.00 | 0.00 | 0.120862E+11 | 0.943110E+10 | 40598.21 | 30-APR-07:02 | 23263.02 | 0.00 |
May | 0.00 | 0.00 | 0.181111E+11 | 0.139318E+11 | 41996.97 | 01-MAY-06:02 | 18880.78 | 0.00 |
June | 0.00 | 0.00 | 0.220633E+11 | 0.150329E+11 | 42737.10 | 25-JUN-07:01 | 18782.67 | 0.00 |
July | 0.00 | 0.00 | 0.264870E+11 | 0.170707E+11 | 42454.23 | 06-JUL-06:01 | 18830.88 | 0.00 |
August | 0.00 | 0.00 | 0.285441E+11 | 0.179117E+11 | 42450.49 | 31-AUG-06:01 | 19509.61 | 0.00 |
September | 0.00 | 0.00 | 0.235640E+11 | 0.150390E+11 | 42775.03 | 25-SEP-06:03 | 17179.39 | 0.00 |
October | 0.00 | 0.00 | 0.185932E+11 | 0.130724E+11 | 42765.53 | 07-OCT-06:01 | 18731.78 | 0.00 |
November | 0.00 | 0.00 | 0.131029E+11 | 0.943658E+10 | 41178.99 | 03-NOV-06:02 | 22684.42 | 0.00 |
December | 0.00 | 0.00 | 0.786432E+10 | 0.574141E+10 | 39222.79 | 12-DEC-07:02 | 27456.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190671E+12 | 0.132520E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.522126E+10 | 0.404634E+10 | 18514.12 | 11204.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.285441E+11 | 0.179117E+11 | 42775.03 | 31216.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.496223E+10 | 0.382963E+10 | 16462.77 | 30-JAN-07:03 | 9900.38 | 0.00 |
February | 0.00 | 0.00 | 0.600172E+10 | 0.457516E+10 | 33658.56 | 09-FEB-07:03 | 20068.58 | 0.00 |
March | 0.00 | 0.00 | 0.855419E+10 | 0.682919E+10 | 37629.17 | 02-MAR-07:02 | 30853.75 | 0.00 |
April | 0.00 | 0.00 | 0.118682E+11 | 0.924163E+10 | 40416.92 | 30-APR-07:02 | 23005.10 | 0.00 |
May | 0.00 | 0.00 | 0.179352E+11 | 0.137667E+11 | 41815.50 | 01-MAY-06:02 | 18674.22 | 0.00 |
June | 0.00 | 0.00 | 0.218858E+11 | 0.148752E+11 | 42565.06 | 25-JUN-07:01 | 18542.35 | 0.00 |
July | 0.00 | 0.00 | 0.263370E+11 | 0.169343E+11 | 42283.34 | 06-JUL-06:01 | 18584.05 | 0.00 |
August | 0.00 | 0.00 | 0.283870E+11 | 0.177698E+11 | 42279.61 | 31-AUG-06:02 | 19027.82 | 0.00 |
September | 0.00 | 0.00 | 0.234014E+11 | 0.148970E+11 | 42602.84 | 25-SEP-06:01 | 17133.71 | 0.00 |
October | 0.00 | 0.00 | 0.184236E+11 | 0.129210E+11 | 42593.38 | 07-OCT-06:01 | 18447.91 | 0.00 |
November | 0.00 | 0.00 | 0.128998E+11 | 0.926283E+10 | 40997.75 | 03-NOV-06:02 | 22383.37 | 0.00 |
December | 0.00 | 0.00 | 0.761408E+10 | 0.553851E+10 | 39043.32 | 12-DEC-07:02 | 27142.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188270E+12 | 0.130441E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.496223E+10 | 0.382963E+10 | 16462.77 | 9900.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283870E+11 | 0.177698E+11 | 42602.84 | 30853.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.830846E+10 | 0.626307E+10 | 26994.01 | 30-JAN-08:63 | 15912.84 | 0.00 |
February | 0.00 | 0.00 | 0.103394E+11 | 0.772908E+10 | 53818.03 | 09-FEB-08:62 | 32258.13 | 0.00 |
March | 0.00 | 0.00 | 0.151788E+11 | 0.119128E+11 | 67235.40 | 02-MAR-08:62 | 54664.37 | 0.00 |
April | 0.00 | 0.00 | 0.214126E+11 | 0.164578E+11 | 72450.77 | 30-APR-08:62 | 40095.57 | 0.00 |
May | 0.00 | 0.00 | 0.328407E+11 | 0.249666E+11 | 74662.05 | 01-MAY-07:02 | 32883.15 | 0.00 |
June | 0.00 | 0.00 | 0.401600E+11 | 0.270472E+11 | 75885.32 | 25-JUN-08:61 | 31684.25 | 0.00 |
July | 0.00 | 0.00 | 0.482023E+11 | 0.307844E+11 | 75250.44 | 18-JUL-07:01 | 37341.10 | 0.00 |
August | 0.00 | 0.00 | 0.522670E+11 | 0.324486E+11 | 75308.54 | 08-AUG-07:01 | 35575.42 | 0.00 |
September | 0.00 | 0.00 | 0.429168E+11 | 0.270139E+11 | 76041.24 | 25-SEP-07:02 | 30543.61 | 0.00 |
October | 0.00 | 0.00 | 0.334568E+11 | 0.233064E+11 | 75815.51 | 02-OCT-07:02 | 31513.65 | 0.00 |
November | 0.00 | 0.00 | 0.232581E+11 | 0.164439E+11 | 72133.68 | 03-NOV-07:02 | 42170.77 | 0.00 |
December | 0.00 | 0.00 | 0.132418E+11 | 0.942779E+10 | 69303.36 | 12-DEC-08:62 | 49112.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341583E+12 | 0.233802E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.830846E+10 | 0.626307E+10 | 26994.01 | 15912.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.522670E+11 | 0.324486E+11 | 76041.24 | 54664.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.428555E+10 | 0.323498E+10 | 13197.00 | 30-JAN-08:63 | 7781.41 | 0.00 |
February | 0.00 | 0.00 | 0.534761E+10 | 0.400399E+10 | 25875.86 | 09-FEB-08:62 | 15476.97 | 0.00 |
March | 0.00 | 0.00 | 0.787004E+10 | 0.618464E+10 | 35520.22 | 02-MAR-08:62 | 28864.74 | 0.00 |
April | 0.00 | 0.00 | 0.111393E+11 | 0.856435E+10 | 38316.38 | 30-APR-08:62 | 21121.97 | 0.00 |
May | 0.00 | 0.00 | 0.171099E+11 | 0.130011E+11 | 39512.11 | 01-MAY-07:02 | 17300.96 | 0.00 |
June | 0.00 | 0.00 | 0.209062E+11 | 0.140787E+11 | 40106.20 | 25-JUN-08:61 | 16652.32 | 0.00 |
July | 0.00 | 0.00 | 0.251038E+11 | 0.160321E+11 | 39746.74 | 18-JUL-07:01 | 19767.58 | 0.00 |
August | 0.00 | 0.00 | 0.271954E+11 | 0.168821E+11 | 39801.36 | 08-AUG-07:01 | 18869.70 | 0.00 |
September | 0.00 | 0.00 | 0.223386E+11 | 0.140672E+11 | 40188.60 | 25-SEP-07:01 | 16061.05 | 0.00 |
October | 0.00 | 0.00 | 0.174131E+11 | 0.121416E+11 | 40069.30 | 02-OCT-07:01 | 16588.38 | 0.00 |
November | 0.00 | 0.00 | 0.120919E+11 | 0.855768E+10 | 38096.54 | 03-NOV-07:02 | 22348.22 | 0.00 |
December | 0.00 | 0.00 | 0.686514E+10 | 0.489474E+10 | 34985.53 | 12-DEC-08:62 | 24799.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177666E+12 | 0.121643E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.428555E+10 | 0.323498E+10 | 13197.00 | 7781.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271954E+11 | 0.168821E+11 | 40188.60 | 28864.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.421413E+10 | 0.317798E+10 | 12658.93 | 30-JAN-08:63 | 7454.13 | 0.00 |
February | 0.00 | 0.00 | 0.528094E+10 | 0.395207E+10 | 25226.03 | 09-FEB-08:62 | 15044.64 | 0.00 |
March | 0.00 | 0.00 | 0.780053E+10 | 0.612807E+10 | 35400.67 | 02-MAR-08:62 | 28737.94 | 0.00 |
April | 0.00 | 0.00 | 0.110813E+11 | 0.851741E+10 | 38189.44 | 30-APR-08:62 | 21029.42 | 0.00 |
May | 0.00 | 0.00 | 0.170614E+11 | 0.129609E+11 | 39381.56 | 01-MAY-07:02 | 17224.34 | 0.00 |
June | 0.00 | 0.00 | 0.208587E+11 | 0.140415E+11 | 39975.10 | 25-JUN-08:02 | 16409.19 | 0.00 |
July | 0.00 | 0.00 | 0.250623E+11 | 0.160000E+11 | 39620.40 | 18-JUL-07:01 | 19685.48 | 0.00 |
August | 0.00 | 0.00 | 0.271530E+11 | 0.168496E+11 | 39671.27 | 08-AUG-07:02 | 18499.93 | 0.00 |
September | 0.00 | 0.00 | 0.222960E+11 | 0.140346E+11 | 40057.24 | 25-SEP-07:01 | 16003.93 | 0.00 |
October | 0.00 | 0.00 | 0.173672E+11 | 0.121048E+11 | 39938.33 | 02-OCT-07:02 | 16423.95 | 0.00 |
November | 0.00 | 0.00 | 0.120376E+11 | 0.851484E+10 | 37974.19 | 03-NOV-07:02 | 22241.19 | 0.00 |
December | 0.00 | 0.00 | 0.679844E+10 | 0.484356E+10 | 34444.00 | 12-DEC-08:62 | 24380.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177011E+12 | 0.121125E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.421413E+10 | 0.317798E+10 | 12658.93 | 7454.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271530E+11 | 0.168496E+11 | 40057.24 | 28737.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.407064E+10 | 0.306382E+10 | 10970.08 | 30-JAN-08:63 | 6437.73 | 0.00 |
February | 0.00 | 0.00 | 0.515341E+10 | 0.385367E+10 | 23292.29 | 09-FEB-08:62 | 13777.38 | 0.00 |
March | 0.00 | 0.00 | 0.769220E+10 | 0.604058E+10 | 35617.44 | 02-MAR-08:62 | 28860.07 | 0.00 |
April | 0.00 | 0.00 | 0.110532E+11 | 0.849660E+10 | 38426.07 | 30-APR-08:62 | 21141.50 | 0.00 |
May | 0.00 | 0.00 | 0.171635E+11 | 0.130466E+11 | 39629.26 | 01-MAY-07:02 | 17317.72 | 0.00 |
June | 0.00 | 0.00 | 0.210108E+11 | 0.141634E+11 | 40231.88 | 25-JUN-08:02 | 16542.01 | 0.00 |
July | 0.00 | 0.00 | 0.252923E+11 | 0.161834E+11 | 39864.21 | 18-JUL-07:01 | 19924.78 | 0.00 |
August | 0.00 | 0.00 | 0.274300E+11 | 0.170688E+11 | 39926.09 | 08-AUG-07:01 | 19045.04 | 0.00 |
September | 0.00 | 0.00 | 0.224965E+11 | 0.141917E+11 | 40314.54 | 25-SEP-07:01 | 16166.46 | 0.00 |
October | 0.00 | 0.00 | 0.175052E+11 | 0.122156E+11 | 40194.87 | 02-OCT-07:01 | 16699.09 | 0.00 |
November | 0.00 | 0.00 | 0.120676E+11 | 0.853933E+10 | 38210.24 | 03-NOV-07:02 | 22404.61 | 0.00 |
December | 0.00 | 0.00 | 0.669852E+10 | 0.476809E+10 | 33146.86 | 12-DEC-08:62 | 23380.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177634E+12 | 0.121632E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.407064E+10 | 0.306382E+10 | 10970.08 | 6437.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.274300E+11 | 0.170688E+11 | 40314.54 | 28860.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.444724E+10 | 0.340747E+10 | 10160.78 | 29-JAN-16:00 | 6816.00 | 0.00 |
February | 0.00 | 0.00 | 0.558917E+10 | 0.425298E+10 | 19077.97 | 09-FEB-08:62 | 10783.39 | 0.00 |
March | 0.00 | 0.00 | 0.840628E+10 | 0.670500E+10 | 40418.95 | 02-MAR-08:62 | 35614.72 | 0.00 |
April | 0.00 | 0.00 | 0.123667E+11 | 0.966375E+10 | 44816.22 | 30-APR-08:62 | 22990.24 | 0.00 |
May | 0.00 | 0.00 | 0.195927E+11 | 0.151618E+11 | 46276.83 | 30-MAY-07:01 | 22146.23 | 0.00 |
June | 0.00 | 0.00 | 0.239644E+11 | 0.165382E+11 | 46369.35 | 25-JUN-08:61 | 18305.83 | 0.00 |
July | 0.00 | 0.00 | 0.288542E+11 | 0.189752E+11 | 46016.91 | 26-JUL-07:03 | 19598.83 | 0.00 |
August | 0.00 | 0.00 | 0.314783E+11 | 0.202271E+11 | 46016.91 | 08-AUG-07:02 | 17195.22 | 0.00 |
September | 0.00 | 0.00 | 0.257271E+11 | 0.167337E+11 | 46464.62 | 25-SEP-07:02 | 18552.32 | 0.00 |
October | 0.00 | 0.00 | 0.200752E+11 | 0.143377E+11 | 46326.69 | 02-OCT-07:01 | 18806.80 | 0.00 |
November | 0.00 | 0.00 | 0.136838E+11 | 0.990229E+10 | 44599.90 | 03-NOV-07:02 | 24859.46 | 0.00 |
December | 0.00 | 0.00 | 0.734532E+10 | 0.533426E+10 | 34222.29 | 12-DEC-08:62 | 23235.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201530E+12 | 0.141240E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.444724E+10 | 0.340747E+10 | 10160.78 | 6816.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.314783E+11 | 0.202271E+11 | 46464.62 | 35614.72 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230243E+10 | 0.36 | 1268.98 | 01-JAN-23:20 | 0.53 |
February | 0.208348E+10 | 0.36 | 2150.26 | 09-FEB-08:62 | 0.72 |
March | 0.231211E+10 | 0.36 | 3172.44 | 02-MAR-08:62 | 0.87 |
April | 0.223105E+10 | 0.36 | 3172.44 | 18-APR-07:02 | 0.87 |
May | 0.232875E+10 | 0.36 | 3172.44 | 01-MAY-07:02 | 0.86 |
June | 0.239026E+10 | 0.37 | 3172.44 | 01-JUN-07:01 | 0.87 |
July | 0.268489E+10 | 0.39 | 3172.44 | 01-JUL-07:01 | 0.86 |
August | 0.278507E+10 | 0.40 | 3172.44 | 01-AUG-07:01 | 0.86 |
September | 0.246636E+10 | 0.38 | 3172.44 | 01-SEP-07:01 | 0.86 |
October | 0.233814E+10 | 0.36 | 3172.44 | 01-OCT-07:01 | 0.86 |
November | 0.223056E+10 | 0.36 | 3172.44 | 01-NOV-07:02 | 0.87 |
December | 0.231206E+10 | 0.36 | 3172.44 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.284652E+11 | 0.37 | |||
Minimum of Months | 0.208348E+10 | 0.36 | 1268.98 | 0.53 | |
Maximum of Months | 0.278507E+10 | 0.40 | 3172.44 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.936208E+09 | 0.37 | 639.18 | 18-JAN-17:20 | 0.53 |
February | 0.852443E+09 | 0.37 | 1098.51 | 09-FEB-08:62 | 0.73 |
March | 0.959800E+09 | 0.37 | 1597.95 | 02-MAR-08:62 | 0.87 |
April | 0.939826E+09 | 0.36 | 1597.95 | 18-APR-07:02 | 0.87 |
May | 0.101816E+10 | 0.36 | 1597.95 | 06-MAY-07:02 | 0.87 |
June | 0.107755E+10 | 0.38 | 1597.95 | 01-JUN-07:01 | 0.87 |
July | 0.123337E+10 | 0.39 | 1597.95 | 01-JUL-07:01 | 0.87 |
August | 0.128751E+10 | 0.40 | 1597.95 | 01-AUG-07:01 | 0.86 |
September | 0.111722E+10 | 0.38 | 1597.95 | 01-SEP-07:01 | 0.87 |
October | 0.102140E+10 | 0.37 | 1597.95 | 01-OCT-07:01 | 0.86 |
November | 0.943154E+09 | 0.36 | 1597.95 | 01-NOV-07:02 | 0.87 |
December | 0.945713E+09 | 0.37 | 1592.97 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.123323E+11 | 0.37 | |||
Minimum of Months | 0.852443E+09 | 0.36 | 639.18 | 0.53 | |
Maximum of Months | 0.128751E+10 | 0.40 | 1597.95 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.924967E+09 | 0.29 | 639.14 | 04-JAN-19:20 | 0.53 |
February | 0.837903E+09 | 0.29 | 1414.96 | 09-FEB-07:03 | 0.82 |
March | 0.944095E+09 | 0.29 | 1597.86 | 02-MAR-07:02 | 0.87 |
April | 0.899379E+09 | 0.29 | 1597.86 | 03-APR-06:02 | 0.87 |
May | 0.949016E+09 | 0.29 | 1597.86 | 01-MAY-06:02 | 0.86 |
June | 0.989568E+09 | 0.30 | 1597.86 | 01-JUN-06:01 | 0.87 |
July | 0.110952E+10 | 0.31 | 1597.86 | 01-JUL-06:01 | 0.86 |
August | 0.117571E+10 | 0.33 | 1597.86 | 01-AUG-06:01 | 0.86 |
September | 0.101183E+10 | 0.30 | 1597.86 | 01-SEP-06:01 | 0.86 |
October | 0.943817E+09 | 0.29 | 1597.86 | 01-OCT-07:01 | 0.86 |
November | 0.900723E+09 | 0.29 | 1597.86 | 01-NOV-06:02 | 0.87 |
December | 0.920981E+09 | 0.28 | 1597.86 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.116075E+11 | 0.30 | |||
Minimum of Months | 0.837903E+09 | 0.28 | 639.14 | 0.53 | |
Maximum of Months | 0.117571E+10 | 0.33 | 1597.86 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.926978E+09 | 0.29 | 640.53 | 08-JAN-12:20 | 0.53 |
February | 0.839727E+09 | 0.29 | 1416.58 | 09-FEB-07:03 | 0.82 |
March | 0.946153E+09 | 0.29 | 1601.33 | 02-MAR-07:02 | 0.87 |
April | 0.901378E+09 | 0.29 | 1601.33 | 03-APR-06:02 | 0.87 |
May | 0.951699E+09 | 0.29 | 1601.33 | 01-MAY-06:02 | 0.86 |
June | 0.993190E+09 | 0.30 | 1601.33 | 01-JUN-06:01 | 0.87 |
July | 0.111473E+10 | 0.31 | 1601.33 | 01-JUL-06:01 | 0.86 |
August | 0.118091E+10 | 0.33 | 1601.33 | 01-AUG-06:01 | 0.86 |
September | 0.101602E+10 | 0.30 | 1601.33 | 01-SEP-06:01 | 0.86 |
October | 0.946375E+09 | 0.29 | 1601.33 | 01-OCT-07:01 | 0.86 |
November | 0.902704E+09 | 0.29 | 1601.33 | 01-NOV-06:02 | 0.87 |
December | 0.922976E+09 | 0.28 | 1601.33 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.116428E+11 | 0.30 | |||
Minimum of Months | 0.839727E+09 | 0.28 | 640.53 | 0.53 | |
Maximum of Months | 0.118091E+10 | 0.33 | 1601.33 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.922195E+09 | 0.29 | 637.23 | 19-JAN-15:10 | 0.53 |
February | 0.835327E+09 | 0.29 | 1292.10 | 09-FEB-07:03 | 0.79 |
March | 0.941131E+09 | 0.29 | 1593.07 | 02-MAR-07:02 | 0.87 |
April | 0.896458E+09 | 0.29 | 1593.07 | 03-APR-06:02 | 0.87 |
May | 0.946450E+09 | 0.29 | 1593.07 | 01-MAY-06:02 | 0.86 |
June | 0.986618E+09 | 0.30 | 1593.07 | 01-JUN-06:01 | 0.87 |
July | 0.110800E+10 | 0.31 | 1593.07 | 01-JUL-06:01 | 0.86 |
August | 0.117385E+10 | 0.33 | 1593.07 | 01-AUG-06:01 | 0.86 |
September | 0.100940E+10 | 0.30 | 1593.07 | 01-SEP-06:01 | 0.86 |
October | 0.940886E+09 | 0.29 | 1593.07 | 01-OCT-07:01 | 0.86 |
November | 0.897820E+09 | 0.29 | 1593.07 | 01-NOV-06:02 | 0.87 |
December | 0.918068E+09 | 0.28 | 1593.07 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.115762E+11 | 0.30 | |||
Minimum of Months | 0.835327E+09 | 0.28 | 637.23 | 0.53 | |
Maximum of Months | 0.117385E+10 | 0.33 | 1593.07 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151667E+10 | 0.26 | 1135.58 | 02-JAN-13:40 | 0.53 |
February | 0.137402E+10 | 0.26 | 2018.81 | 09-FEB-08:62 | 0.74 |
March | 0.155001E+10 | 0.27 | 2838.94 | 02-MAR-08:62 | 0.87 |
April | 0.147407E+10 | 0.26 | 2838.94 | 03-APR-07:02 | 0.87 |
May | 0.157281E+10 | 0.27 | 2838.94 | 01-MAY-07:02 | 0.86 |
June | 0.168092E+10 | 0.29 | 2838.94 | 01-JUN-07:01 | 0.87 |
July | 0.191952E+10 | 0.30 | 2838.94 | 01-JUL-07:01 | 0.86 |
August | 0.204138E+10 | 0.31 | 2838.94 | 01-AUG-07:01 | 0.86 |
September | 0.173504E+10 | 0.29 | 2838.94 | 01-SEP-07:01 | 0.86 |
October | 0.156321E+10 | 0.27 | 2838.94 | 01-OCT-08:61 | 0.85 |
November | 0.147873E+10 | 0.26 | 2838.94 | 01-NOV-07:02 | 0.87 |
December | 0.150913E+10 | 0.26 | 2838.94 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.194155E+11 | 0.28 | |||
Minimum of Months | 0.137402E+10 | 0.26 | 1135.58 | 0.53 | |
Maximum of Months | 0.204138E+10 | 0.31 | 2838.94 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829379E+09 | 0.27 | 620.98 | 05-JAN-19:00 | 0.55 |
February | 0.751302E+09 | 0.27 | 977.41 | 09-FEB-08:62 | 0.71 |
March | 0.847535E+09 | 0.28 | 1552.45 | 02-MAR-08:62 | 0.90 |
April | 0.805875E+09 | 0.27 | 1552.45 | 03-APR-07:02 | 0.90 |
May | 0.858987E+09 | 0.28 | 1552.45 | 01-MAY-07:02 | 0.89 |
June | 0.916036E+09 | 0.29 | 1552.45 | 01-JUN-07:01 | 0.90 |
July | 0.104453E+10 | 0.31 | 1552.45 | 01-JUL-07:01 | 0.89 |
August | 0.110906E+10 | 0.32 | 1552.45 | 01-AUG-07:01 | 0.89 |
September | 0.944109E+09 | 0.30 | 1552.45 | 01-SEP-07:01 | 0.89 |
October | 0.853353E+09 | 0.28 | 1552.45 | 01-OCT-08:61 | 0.88 |
November | 0.808320E+09 | 0.27 | 1552.45 | 01-NOV-07:02 | 0.90 |
December | 0.825174E+09 | 0.27 | 1469.74 | 12-DEC-08:62 | 0.88 |
Annual Sum or Average | 0.105937E+11 | 0.28 | |||
Minimum of Months | 0.751302E+09 | 0.27 | 620.98 | 0.55 | |
Maximum of Months | 0.110906E+10 | 0.32 | 1552.45 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826668E+09 | 0.27 | 618.95 | 02-JAN-17:50 | 0.55 |
February | 0.748830E+09 | 0.27 | 946.29 | 09-FEB-08:62 | 0.70 |
March | 0.844750E+09 | 0.28 | 1547.37 | 02-MAR-08:62 | 0.90 |
April | 0.803204E+09 | 0.27 | 1547.37 | 03-APR-07:02 | 0.90 |
May | 0.856379E+09 | 0.28 | 1547.37 | 01-MAY-07:02 | 0.89 |
June | 0.913729E+09 | 0.29 | 1547.37 | 01-JUN-07:01 | 0.90 |
July | 0.104244E+10 | 0.31 | 1547.37 | 01-JUL-07:01 | 0.89 |
August | 0.110696E+10 | 0.32 | 1547.37 | 01-AUG-07:01 | 0.89 |
September | 0.942008E+09 | 0.30 | 1547.37 | 01-SEP-07:01 | 0.89 |
October | 0.850759E+09 | 0.28 | 1547.37 | 01-OCT-08:61 | 0.88 |
November | 0.805664E+09 | 0.27 | 1547.37 | 01-NOV-07:02 | 0.90 |
December | 0.822460E+09 | 0.27 | 1443.46 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.105639E+11 | 0.28 | |||
Minimum of Months | 0.748830E+09 | 0.27 | 618.95 | 0.55 | |
Maximum of Months | 0.110696E+10 | 0.32 | 1547.37 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.831977E+09 | 0.27 | 622.92 | 17-JAN-12:30 | 0.55 |
February | 0.753578E+09 | 0.27 | 849.07 | 09-FEB-08:62 | 0.66 |
March | 0.850129E+09 | 0.28 | 1557.31 | 02-MAR-08:62 | 0.90 |
April | 0.808241E+09 | 0.27 | 1557.31 | 17-APR-07:02 | 0.90 |
May | 0.861912E+09 | 0.28 | 1557.31 | 01-MAY-07:02 | 0.89 |
June | 0.920124E+09 | 0.29 | 1557.31 | 01-JUN-07:01 | 0.90 |
July | 0.105138E+10 | 0.31 | 1557.31 | 01-JUL-07:01 | 0.89 |
August | 0.111736E+10 | 0.32 | 1557.31 | 01-AUG-07:01 | 0.89 |
September | 0.949711E+09 | 0.30 | 1557.31 | 01-SEP-07:01 | 0.89 |
October | 0.856439E+09 | 0.28 | 1557.31 | 01-OCT-08:61 | 0.88 |
November | 0.810721E+09 | 0.27 | 1557.31 | 01-NOV-07:02 | 0.90 |
December | 0.827680E+09 | 0.27 | 1376.47 | 12-DEC-08:62 | 0.85 |
Annual Sum or Average | 0.106393E+11 | 0.28 | |||
Minimum of Months | 0.753578E+09 | 0.27 | 622.92 | 0.55 | |
Maximum of Months | 0.111736E+10 | 0.32 | 1557.31 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.958105E+09 | 0.26 | 717.36 | 14-JAN-12:00 | 0.53 |
February | 0.867717E+09 | 0.26 | 717.36 | 02-FEB-20:15 | 0.52 |
March | 0.978903E+09 | 0.27 | 1793.40 | 02-MAR-08:62 | 0.87 |
April | 0.930351E+09 | 0.26 | 1793.40 | 30-APR-08:62 | 0.86 |
May | 0.989420E+09 | 0.27 | 1793.40 | 01-MAY-07:02 | 0.86 |
June | 0.104987E+10 | 0.28 | 1793.40 | 01-JUN-07:01 | 0.87 |
July | 0.120102E+10 | 0.30 | 1793.40 | 01-JUL-07:01 | 0.86 |
August | 0.128414E+10 | 0.31 | 1793.40 | 01-AUG-07:01 | 0.86 |
September | 0.108653E+10 | 0.29 | 1793.40 | 01-SEP-07:01 | 0.86 |
October | 0.983677E+09 | 0.27 | 1793.40 | 01-OCT-08:61 | 0.85 |
November | 0.932808E+09 | 0.26 | 1793.40 | 01-NOV-07:02 | 0.86 |
December | 0.953044E+09 | 0.26 | 1368.00 | 12-DEC-08:62 | 0.76 |
Annual Sum or Average | 0.122156E+11 | 0.27 | |||
Minimum of Months | 0.867717E+09 | 0.26 | 717.36 | 0.52 | |
Maximum of Months | 0.128414E+10 | 0.31 | 1793.40 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.631323E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.676878E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.897510E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.117148E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166806E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.193478E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.231542E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.242846E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.202330E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.163732E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118960E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.820897E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173950E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.631323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.242846E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.300873E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.316144E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.408570E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.516269E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.721196E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.833625E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.997596E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104618E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.869065E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.705993E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.523025E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.377446E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.761598E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.300873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104618E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.232803E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.250812E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.333546E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.420741E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.597881E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.697053E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.829678E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.887776E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.720029E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.581977E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.432455E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.298725E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.628348E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.232803E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.887776E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.231077E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.249833E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.333240E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.421606E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.600760E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.700596E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.834641E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.892648E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.723971E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.584820E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.433515E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.298151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.630486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.231077E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.892648E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224100E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.243620E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.326634E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415718E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.595700E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.695277E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.829813E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.887608E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.719082E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.580115E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.428177E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.291549E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.623739E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.224100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.887608E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.376929E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.418235E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.574501E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.743719E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.108528E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127672E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.152544E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.164077E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.132168E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105017E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.766098E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.504161E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.112837E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.376929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164077E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.197304E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.218138E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.298978E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.386180E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.562472E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.660774E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.789466E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.848300E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.683766E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.543987E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.397509E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.262836E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.584971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.197304E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.848300E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.195203E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.216190E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.296904E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.384371E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.560777E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.659116E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.787918E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846706E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.682277E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.542414E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.395835E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.260883E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.582859E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.195203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846706E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.192131E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213539E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.294883E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.384484E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.564337E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664073E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.795375E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.855537E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.688522E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.546658E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.397327E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.259053E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.585592E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192131E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.855537E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.217366E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.240206E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.332823E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.441156E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.658071E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.774107E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.928988E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.100558E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.805341E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.639525E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.460354E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.293220E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.679674E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.217366E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100558E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.230243E+10 | 0.135280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208348E+10 | 0.157549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231211E+10 | 0.220371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223105E+10 | 0.310781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232875E+10 | 0.460548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239026E+10 | 0.559804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268489E+10 | 0.671241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.278507E+10 | 0.709636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.246636E+10 | 0.603833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233814E+10 | 0.474850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223056E+10 | 0.328789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231206E+10 | 0.201438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284652E+11 | 0.483412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208348E+10 | 0.135280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.278507E+10 | 0.709636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.936208E+09 | 0.786093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852443E+09 | 0.871942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959800E+09 | 0.115835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.939826E+09 | 0.154089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101816E+10 | 0.219697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107755E+10 | 0.263367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123337E+10 | 0.314827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128751E+10 | 0.332775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111722E+10 | 0.282798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102140E+10 | 0.225681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.943154E+09 | 0.162511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945713E+09 | 0.108291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123323E+11 | 0.234568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852443E+09 | 0.786093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128751E+10 | 0.332775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.924967E+09 | 0.529948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837903E+09 | 0.628227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944095E+09 | 0.882290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899379E+09 | 0.120631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949016E+09 | 0.180098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.989568E+09 | 0.219401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110952E+10 | 0.263183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117571E+10 | 0.283780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101183E+10 | 0.234254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943817E+09 | 0.184852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900723E+09 | 0.130696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.920981E+09 | 0.789811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116075E+11 | 0.189992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.837903E+09 | 0.529948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117571E+10 | 0.283780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.926978E+09 | 0.522126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.839727E+09 | 0.623385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.946153E+09 | 0.879973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901378E+09 | 0.120862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.951699E+09 | 0.181111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.993190E+09 | 0.220633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111473E+10 | 0.264870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118091E+10 | 0.285441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101602E+10 | 0.235640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.946375E+09 | 0.185932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902704E+09 | 0.131029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.922976E+09 | 0.786432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116428E+11 | 0.190671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.839727E+09 | 0.522126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118091E+10 | 0.285441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.922195E+09 | 0.496223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835327E+09 | 0.600172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.941131E+09 | 0.855419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.896458E+09 | 0.118682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946450E+09 | 0.179352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.986618E+09 | 0.218858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110800E+10 | 0.263370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117385E+10 | 0.283870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100940E+10 | 0.234014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.940886E+09 | 0.184236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897820E+09 | 0.128998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.918068E+09 | 0.761408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115762E+11 | 0.188270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835327E+09 | 0.496223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117385E+10 | 0.283870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151667E+10 | 0.830846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137402E+10 | 0.103394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155001E+10 | 0.151788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147407E+10 | 0.214126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157281E+10 | 0.328407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168092E+10 | 0.401600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191952E+10 | 0.482023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204138E+10 | 0.522670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173504E+10 | 0.429168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156321E+10 | 0.334568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147873E+10 | 0.232581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150913E+10 | 0.132418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194155E+11 | 0.341583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137402E+10 | 0.830846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204138E+10 | 0.522670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829379E+09 | 0.428555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751302E+09 | 0.534761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.847535E+09 | 0.787004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.805875E+09 | 0.111393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.858987E+09 | 0.171099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916036E+09 | 0.209062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104453E+10 | 0.251038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110906E+10 | 0.271954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.944109E+09 | 0.223386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853353E+09 | 0.174131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808320E+09 | 0.120919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825174E+09 | 0.686514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105937E+11 | 0.177666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751302E+09 | 0.428555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110906E+10 | 0.271954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826668E+09 | 0.421413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748830E+09 | 0.528094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844750E+09 | 0.780053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.803204E+09 | 0.110813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856379E+09 | 0.170614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913729E+09 | 0.208587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104244E+10 | 0.250623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110696E+10 | 0.271530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942008E+09 | 0.222960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.850759E+09 | 0.173672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.805664E+09 | 0.120376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822460E+09 | 0.679844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105639E+11 | 0.177011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.748830E+09 | 0.421413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110696E+10 | 0.271530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.831977E+09 | 0.407064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.753578E+09 | 0.515341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.850129E+09 | 0.769220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.808241E+09 | 0.110532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.861912E+09 | 0.171635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920124E+09 | 0.210108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105138E+10 | 0.252923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111736E+10 | 0.274300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.949711E+09 | 0.224965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.856439E+09 | 0.175052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810721E+09 | 0.120676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827680E+09 | 0.669852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106393E+11 | 0.177634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.753578E+09 | 0.407064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111736E+10 | 0.274300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.958105E+09 | 0.444724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867717E+09 | 0.558917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.978903E+09 | 0.840628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.930351E+09 | 0.123667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989420E+09 | 0.195927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104987E+10 | 0.239644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120102E+10 | 0.288542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128414E+10 | 0.314783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108653E+10 | 0.257271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.983677E+09 | 0.200752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.932808E+09 | 0.136838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.953044E+09 | 0.734532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122156E+11 | 0.201530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.867717E+09 | 0.444724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128414E+10 | 0.314783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.230243E+10 | 0.00 | 0.00 | 0.00 | 0.401080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208348E+10 | 0.00 | 0.00 | 0.00 | 0.468530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231211E+10 | 0.00 | 0.00 | 0.00 | 0.666299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223105E+10 | 0.00 | 0.00 | 0.00 | 0.948373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232875E+10 | 0.00 | 0.00 | 0.00 | 0.143519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239026E+10 | 0.00 | 0.00 | 0.00 | 0.169575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268489E+10 | 0.00 | 0.00 | 0.00 | 0.204694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.278507E+10 | 0.00 | 0.00 | 0.00 | 0.214996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.246636E+10 | 0.00 | 0.00 | 0.00 | 0.177666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233814E+10 | 0.00 | 0.00 | 0.00 | 0.140351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223056E+10 | 0.00 | 0.00 | 0.00 | 0.966545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231206E+10 | 0.00 | 0.00 | 0.00 | 0.589691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284652E+11 | 0.00 | 0.00 | 0.00 | 0.145485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208348E+10 | 0.00 | 0.00 | 0.00 | 0.401080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.278507E+10 | 0.00 | 0.00 | 0.00 | 0.214996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.936208E+09 | 0.00 | 0.00 | 0.00 | 0.207253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852443E+09 | 0.00 | 0.00 | 0.00 | 0.230900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959800E+09 | 0.00 | 0.00 | 0.00 | 0.312590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.939826E+09 | 0.00 | 0.00 | 0.00 | 0.422286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101816E+10 | 0.00 | 0.00 | 0.00 | 0.619380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107755E+10 | 0.00 | 0.00 | 0.00 | 0.725871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123337E+10 | 0.00 | 0.00 | 0.00 | 0.874259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128751E+10 | 0.00 | 0.00 | 0.00 | 0.917425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111722E+10 | 0.00 | 0.00 | 0.00 | 0.757343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102140E+10 | 0.00 | 0.00 | 0.00 | 0.603853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.943154E+09 | 0.00 | 0.00 | 0.00 | 0.428709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945713E+09 | 0.00 | 0.00 | 0.00 | 0.282874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123323E+11 | 0.00 | 0.00 | 0.00 | 0.638274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852443E+09 | 0.00 | 0.00 | 0.00 | 0.207253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128751E+10 | 0.00 | 0.00 | 0.00 | 0.917425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.924967E+09 | 0.00 | 0.00 | 0.00 | 0.140306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837903E+09 | 0.00 | 0.00 | 0.00 | 0.167022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944095E+09 | 0.00 | 0.00 | 0.00 | 0.239137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899379E+09 | 0.00 | 0.00 | 0.00 | 0.330803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949016E+09 | 0.00 | 0.00 | 0.00 | 0.502980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.989568E+09 | 0.00 | 0.00 | 0.00 | 0.598096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110952E+10 | 0.00 | 0.00 | 0.00 | 0.718726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117571E+10 | 0.00 | 0.00 | 0.00 | 0.770205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101183E+10 | 0.00 | 0.00 | 0.00 | 0.618845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943817E+09 | 0.00 | 0.00 | 0.00 | 0.487596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900723E+09 | 0.00 | 0.00 | 0.00 | 0.342383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.920981E+09 | 0.00 | 0.00 | 0.00 | 0.206627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116075E+11 | 0.00 | 0.00 | 0.00 | 0.512273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.837903E+09 | 0.00 | 0.00 | 0.00 | 0.140306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117571E+10 | 0.00 | 0.00 | 0.00 | 0.770205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.926978E+09 | 0.00 | 0.00 | 0.00 | 0.138380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.839727E+09 | 0.00 | 0.00 | 0.00 | 0.165861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.946153E+09 | 0.00 | 0.00 | 0.00 | 0.238625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901378E+09 | 0.00 | 0.00 | 0.00 | 0.331468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.951699E+09 | 0.00 | 0.00 | 0.00 | 0.505590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.993190E+09 | 0.00 | 0.00 | 0.00 | 0.601277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111473E+10 | 0.00 | 0.00 | 0.00 | 0.723168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118091E+10 | 0.00 | 0.00 | 0.00 | 0.774557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101602E+10 | 0.00 | 0.00 | 0.00 | 0.622370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.946375E+09 | 0.00 | 0.00 | 0.00 | 0.490182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902704E+09 | 0.00 | 0.00 | 0.00 | 0.343245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.922976E+09 | 0.00 | 0.00 | 0.00 | 0.205853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116428E+11 | 0.00 | 0.00 | 0.00 | 0.514058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.839727E+09 | 0.00 | 0.00 | 0.00 | 0.138380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118091E+10 | 0.00 | 0.00 | 0.00 | 0.774557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.922195E+09 | 0.00 | 0.00 | 0.00 | 0.131880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835327E+09 | 0.00 | 0.00 | 0.00 | 0.160087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.941131E+09 | 0.00 | 0.00 | 0.00 | 0.232521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.896458E+09 | 0.00 | 0.00 | 0.00 | 0.326072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946450E+09 | 0.00 | 0.00 | 0.00 | 0.501055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.986618E+09 | 0.00 | 0.00 | 0.00 | 0.596615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110800E+10 | 0.00 | 0.00 | 0.00 | 0.719013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117385E+10 | 0.00 | 0.00 | 0.00 | 0.770223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100940E+10 | 0.00 | 0.00 | 0.00 | 0.618141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.940886E+09 | 0.00 | 0.00 | 0.00 | 0.486026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897820E+09 | 0.00 | 0.00 | 0.00 | 0.338395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.918068E+09 | 0.00 | 0.00 | 0.00 | 0.199742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115762E+11 | 0.00 | 0.00 | 0.00 | 0.507977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835327E+09 | 0.00 | 0.00 | 0.00 | 0.131880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117385E+10 | 0.00 | 0.00 | 0.00 | 0.770223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151667E+10 | 0.00 | 0.00 | 0.00 | 0.225262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137402E+10 | 0.00 | 0.00 | 0.00 | 0.280834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155001E+10 | 0.00 | 0.00 | 0.00 | 0.419500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147407E+10 | 0.00 | 0.00 | 0.00 | 0.596312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157281E+10 | 0.00 | 0.00 | 0.00 | 0.927994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168092E+10 | 0.00 | 0.00 | 0.00 | 0.110863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191952E+10 | 0.00 | 0.00 | 0.00 | 0.133348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204138E+10 | 0.00 | 0.00 | 0.00 | 0.143663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173504E+10 | 0.00 | 0.00 | 0.00 | 0.114817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156321E+10 | 0.00 | 0.00 | 0.00 | 0.893853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147873E+10 | 0.00 | 0.00 | 0.00 | 0.618226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150913E+10 | 0.00 | 0.00 | 0.00 | 0.353249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194155E+11 | 0.00 | 0.00 | 0.00 | 0.934215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137402E+10 | 0.00 | 0.00 | 0.00 | 0.225262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204138E+10 | 0.00 | 0.00 | 0.00 | 0.143663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829379E+09 | 0.00 | 0.00 | 0.00 | 0.114366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751302E+09 | 0.00 | 0.00 | 0.00 | 0.143008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.847535E+09 | 0.00 | 0.00 | 0.00 | 0.214225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.805875E+09 | 0.00 | 0.00 | 0.00 | 0.305593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.858987E+09 | 0.00 | 0.00 | 0.00 | 0.476574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916036E+09 | 0.00 | 0.00 | 0.00 | 0.569170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104453E+10 | 0.00 | 0.00 | 0.00 | 0.685012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110906E+10 | 0.00 | 0.00 | 0.00 | 0.737393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.944109E+09 | 0.00 | 0.00 | 0.00 | 0.589355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853353E+09 | 0.00 | 0.00 | 0.00 | 0.458651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808320E+09 | 0.00 | 0.00 | 0.00 | 0.316677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825174E+09 | 0.00 | 0.00 | 0.00 | 0.180318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105937E+11 | 0.00 | 0.00 | 0.00 | 0.479034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751302E+09 | 0.00 | 0.00 | 0.00 | 0.114366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110906E+10 | 0.00 | 0.00 | 0.00 | 0.737393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826668E+09 | 0.00 | 0.00 | 0.00 | 0.112537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748830E+09 | 0.00 | 0.00 | 0.00 | 0.141306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844750E+09 | 0.00 | 0.00 | 0.00 | 0.212429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.803204E+09 | 0.00 | 0.00 | 0.00 | 0.304050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856379E+09 | 0.00 | 0.00 | 0.00 | 0.475139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913729E+09 | 0.00 | 0.00 | 0.00 | 0.567743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104244E+10 | 0.00 | 0.00 | 0.00 | 0.683674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110696E+10 | 0.00 | 0.00 | 0.00 | 0.736010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942008E+09 | 0.00 | 0.00 | 0.00 | 0.588076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.850759E+09 | 0.00 | 0.00 | 0.00 | 0.457339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.805664E+09 | 0.00 | 0.00 | 0.00 | 0.315269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822460E+09 | 0.00 | 0.00 | 0.00 | 0.178637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105639E+11 | 0.00 | 0.00 | 0.00 | 0.477221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.748830E+09 | 0.00 | 0.00 | 0.00 | 0.112537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110696E+10 | 0.00 | 0.00 | 0.00 | 0.736010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.831977E+09 | 0.00 | 0.00 | 0.00 | 0.108933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.753578E+09 | 0.00 | 0.00 | 0.00 | 0.138182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.850129E+09 | 0.00 | 0.00 | 0.00 | 0.209870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.808241E+09 | 0.00 | 0.00 | 0.00 | 0.303660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.861912E+09 | 0.00 | 0.00 | 0.00 | 0.478146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920124E+09 | 0.00 | 0.00 | 0.00 | 0.572060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105138E+10 | 0.00 | 0.00 | 0.00 | 0.690237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111736E+10 | 0.00 | 0.00 | 0.00 | 0.743801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.949711E+09 | 0.00 | 0.00 | 0.00 | 0.593551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.856439E+09 | 0.00 | 0.00 | 0.00 | 0.461014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810721E+09 | 0.00 | 0.00 | 0.00 | 0.316255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827680E+09 | 0.00 | 0.00 | 0.00 | 0.176285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106393E+11 | 0.00 | 0.00 | 0.00 | 0.479200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.753578E+09 | 0.00 | 0.00 | 0.00 | 0.108933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111736E+10 | 0.00 | 0.00 | 0.00 | 0.743801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.958105E+09 | 0.00 | 0.00 | 0.00 | 0.121556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867717E+09 | 0.00 | 0.00 | 0.00 | 0.153434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.978903E+09 | 0.00 | 0.00 | 0.00 | 0.234933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.930351E+09 | 0.00 | 0.00 | 0.00 | 0.348121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989420E+09 | 0.00 | 0.00 | 0.00 | 0.559129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104987E+10 | 0.00 | 0.00 | 0.00 | 0.669120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120102E+10 | 0.00 | 0.00 | 0.00 | 0.808885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128414E+10 | 0.00 | 0.00 | 0.00 | 0.877169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108653E+10 | 0.00 | 0.00 | 0.00 | 0.696688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.983677E+09 | 0.00 | 0.00 | 0.00 | 0.541157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.932808E+09 | 0.00 | 0.00 | 0.00 | 0.367073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.953044E+09 | 0.00 | 0.00 | 0.00 | 0.197916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122156E+11 | 0.00 | 0.00 | 0.00 | 0.557518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.867717E+09 | 0.00 | 0.00 | 0.00 | 0.121556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128414E+10 | 0.00 | 0.00 | 0.00 | 0.877169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.557657E+09 | 0.688599E+09 | 0.00 | 10500907.62 | 2734832.20 | 0.00 | 0.162503E+10 | 0.00 | 0.57 |
February | 0.259366E+09 | 0.175378E+10 | 0.00 | 6677169.61 | 5186373.11 | 0.00 | 0.914683E+09 | 0.00 | 0.57 |
March | 0.196008E+09 | 0.369626E+10 | 0.00 | 3920033.76 | 6023966.92 | 0.00 | 0.425533E+09 | 0.00 | 0.57 |
April | 56895990.72 | 0.855713E+10 | 0.00 | 761612.55 | 31798115.56 | 0.00 | 90302875.82 | 0.00 | 0.57 |
May | 2718282.91 | 0.159167E+11 | 0.00 | 907764.63 | 74295268.99 | 0.00 | 2848573.95 | 0.00 | 0.58 |
June | 1347439.68 | 0.223286E+11 | 0.00 | 358338.16 | 95260534.05 | 0.00 | 1241229.96 | 0.00 | 0.58 |
July | 0.00 | 0.278435E+11 | 0.00 | 241757.13 | 76214079.68 | 0.00 | 20543.91 | 0.00 | 0.58 |
August | 0.00 | 0.297147E+11 | 0.00 | 0.00 | 75291743.92 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 440168.71 | 0.244846E+11 | 0.00 | 175731.32 | 95864989.99 | 0.00 | 430232.26 | 0.00 | 0.58 |
October | 3669229.15 | 0.163291E+11 | 0.00 | 694718.36 | 0.117344E+09 | 0.00 | 13024084.45 | 0.00 | 0.57 |
November | 4821874.14 | 0.858729E+10 | 0.00 | 765982.74 | 65237917.07 | 0.00 | 12459195.98 | 0.00 | 0.57 |
December | 0.175722E+09 | 0.278856E+10 | 0.00 | 6455390.87 | 7657619.35 | 0.00 | 0.760484E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.125865E+10 | 0.162689E+12 | 0.00 | 31459406.76 | 0.652910E+09 | 0.00 | 0.384606E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.688599E+09 | 0.00 | 0.00 | 2734832.20 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.557657E+09 | 0.297147E+11 | 0.00 | 10500907.62 | 0.117344E+09 | 0.00 | 0.162503E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175158E+09 | 0.368063E+09 | 0.00 | 5387475.13 | 5096671.49 | 0.00 | 0.443401E+09 | 0.00 | 0.44 |
February | 52586389.69 | 0.840949E+09 | 0.00 | 2967364.65 | 10895889.51 | 0.00 | 0.210877E+09 | 0.00 | 0.45 |
March | 37634801.21 | 0.167142E+10 | 0.00 | 1769913.80 | 11509185.60 | 0.00 | 89470547.32 | 0.00 | 0.46 |
April | 5534237.18 | 0.360973E+10 | 0.00 | 322211.92 | 37831979.02 | 0.00 | 11127379.06 | 0.00 | 0.46 |
May | 0.00 | 0.662367E+10 | 0.00 | 65995.44 | 60527881.47 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.934383E+10 | 0.00 | 20049.36 | 59061224.03 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.118004E+11 | 0.00 | 0.00 | 57837742.43 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.127532E+11 | 0.00 | 0.00 | 56795869.59 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.102654E+11 | 0.00 | 0.00 | 64625454.82 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 2579.83 | 0.681628E+10 | 0.00 | 103808.26 | 81182648.75 | 0.00 | 770194.83 | 0.00 | 0.47 |
November | 56832.13 | 0.376744E+10 | 0.00 | 67541.34 | 65312729.04 | 0.00 | 457823.72 | 0.00 | 0.46 |
December | 36558632.27 | 0.132913E+10 | 0.00 | 3037984.91 | 16870874.90 | 0.00 | 0.151753E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.307532E+09 | 0.691896E+11 | 0.00 | 13742344.82 | 0.527548E+09 | 0.00 | 0.907857E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.368063E+09 | 0.00 | 0.00 | 5096671.49 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.175158E+09 | 0.127532E+11 | 0.00 | 5387475.13 | 81182648.75 | 0.00 | 0.443401E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460386E+09 | 0.309706E+09 | 0.00 | 3337500.79 | 6808226.79 | 0.00 | 0.479089E+09 | 0.00 | 0.45 |
February | 0.246896E+09 | 0.690806E+09 | 0.00 | 2134584.53 | 34147256.16 | 0.00 | 0.275340E+09 | 0.00 | 0.46 |
March | 0.155020E+09 | 0.141055E+10 | 0.00 | 1535007.90 | 80631854.18 | 0.00 | 0.197625E+09 | 0.00 | 0.47 |
April | 27550110.38 | 0.293130E+10 | 0.00 | 973978.13 | 0.211029E+09 | 0.00 | 0.114546E+09 | 0.00 | 0.46 |
May | 7149891.29 | 0.546475E+10 | 0.00 | 1138649.43 | 0.407833E+09 | 0.00 | 12060907.97 | 0.00 | 0.46 |
June | 1544628.90 | 0.765353E+10 | 0.00 | 680624.75 | 0.612318E+09 | 0.00 | 2362744.84 | 0.00 | 0.47 |
July | 546328.97 | 0.980225E+10 | 0.00 | 386553.81 | 0.663192E+09 | 0.00 | 2057987.18 | 0.00 | 0.46 |
August | 0.00 | 0.107202E+11 | 0.00 | 202539.07 | 0.737866E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 701854.62 | 0.825686E+10 | 0.00 | 727511.91 | 0.648616E+09 | 0.00 | 4342080.69 | 0.00 | 0.46 |
October | 2462979.97 | 0.562128E+10 | 0.00 | 568749.95 | 0.443715E+09 | 0.00 | 13218919.06 | 0.00 | 0.46 |
November | 8438301.24 | 0.319656E+10 | 0.00 | 772972.45 | 0.189154E+09 | 0.00 | 24415635.33 | 0.00 | 0.46 |
December | 0.176034E+09 | 0.104343E+10 | 0.00 | 2226586.19 | 60259965.20 | 0.00 | 0.261909E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.108673E+10 | 0.571012E+11 | 0.00 | 14685258.90 | 0.409557E+10 | 0.00 | 0.138697E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.309706E+09 | 0.00 | 202539.07 | 6808226.79 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.460386E+09 | 0.107202E+11 | 0.00 | 3337500.79 | 0.737866E+09 | 0.00 | 0.479089E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.467655E+09 | 0.306054E+09 | 0.00 | 3272628.32 | 6731528.91 | 0.00 | 0.473865E+09 | 0.00 | 0.45 |
February | 0.253030E+09 | 0.687810E+09 | 0.00 | 2113289.72 | 34025113.05 | 0.00 | 0.271380E+09 | 0.00 | 0.46 |
March | 0.158891E+09 | 0.140931E+10 | 0.00 | 1522035.62 | 80532211.52 | 0.00 | 0.194330E+09 | 0.00 | 0.47 |
April | 27487581.93 | 0.293330E+10 | 0.00 | 984220.74 | 0.211073E+09 | 0.00 | 0.114420E+09 | 0.00 | 0.46 |
May | 7075839.11 | 0.547685E+10 | 0.00 | 1195200.70 | 0.406869E+09 | 0.00 | 11864010.71 | 0.00 | 0.46 |
June | 1514685.46 | 0.767096E+10 | 0.00 | 710338.94 | 0.611971E+09 | 0.00 | 2328100.55 | 0.00 | 0.47 |
July | 194680.90 | 0.982909E+10 | 0.00 | 417048.89 | 0.659065E+09 | 0.00 | 2336175.93 | 0.00 | 0.46 |
August | 0.00 | 0.107499E+11 | 0.00 | 209317.55 | 0.731218E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 671114.89 | 0.828014E+10 | 0.00 | 782439.91 | 0.646150E+09 | 0.00 | 4247281.88 | 0.00 | 0.46 |
October | 2600451.29 | 0.563803E+10 | 0.00 | 588747.45 | 0.442714E+09 | 0.00 | 12847140.04 | 0.00 | 0.46 |
November | 8441342.45 | 0.320063E+10 | 0.00 | 788490.37 | 0.189408E+09 | 0.00 | 24400570.84 | 0.00 | 0.46 |
December | 0.181358E+09 | 0.104107E+10 | 0.00 | 2213355.55 | 59872037.25 | 0.00 | 0.258118E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.110892E+10 | 0.572231E+11 | 0.00 | 14797113.75 | 0.407963E+10 | 0.00 | 0.137014E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.306054E+09 | 0.00 | 209317.55 | 6731528.91 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.467655E+09 | 0.107499E+11 | 0.00 | 3272628.32 | 0.731218E+09 | 0.00 | 0.473865E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489950E+09 | 0.293790E+09 | 0.00 | 3082039.85 | 6533250.18 | 0.00 | 0.459126E+09 | 0.00 | 0.45 |
February | 0.267819E+09 | 0.672769E+09 | 0.00 | 2024934.01 | 33508968.53 | 0.00 | 0.265818E+09 | 0.00 | 0.46 |
March | 0.171481E+09 | 0.139370E+10 | 0.00 | 1441717.39 | 80207813.77 | 0.00 | 0.186853E+09 | 0.00 | 0.47 |
April | 29740352.16 | 0.291743E+10 | 0.00 | 916150.61 | 0.210564E+09 | 0.00 | 0.116200E+09 | 0.00 | 0.46 |
May | 7072553.91 | 0.546834E+10 | 0.00 | 1119076.84 | 0.408043E+09 | 0.00 | 12053153.40 | 0.00 | 0.46 |
June | 1525131.72 | 0.765828E+10 | 0.00 | 678627.99 | 0.612298E+09 | 0.00 | 2332735.59 | 0.00 | 0.47 |
July | 196873.42 | 0.981708E+10 | 0.00 | 392618.13 | 0.663791E+09 | 0.00 | 2362911.63 | 0.00 | 0.46 |
August | 0.00 | 0.107335E+11 | 0.00 | 201145.23 | 0.739075E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 698071.55 | 0.826507E+10 | 0.00 | 752049.72 | 0.647287E+09 | 0.00 | 4311877.90 | 0.00 | 0.46 |
October | 2623276.58 | 0.562518E+10 | 0.00 | 561628.03 | 0.442153E+09 | 0.00 | 13087485.59 | 0.00 | 0.46 |
November | 8717462.44 | 0.318112E+10 | 0.00 | 738342.27 | 0.189027E+09 | 0.00 | 25256175.32 | 0.00 | 0.46 |
December | 0.196904E+09 | 0.102115E+10 | 0.00 | 2088014.41 | 59192106.76 | 0.00 | 0.252601E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.117673E+10 | 0.570474E+11 | 0.00 | 13996344.47 | 0.409168E+10 | 0.00 | 0.134000E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.293790E+09 | 0.00 | 201145.23 | 6533250.18 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.489950E+09 | 0.107335E+11 | 0.00 | 3082039.85 | 0.739075E+09 | 0.00 | 0.459126E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603458E+09 | 0.395111E+09 | 0.00 | 6263038.84 | 10217066.37 | 0.00 | 0.103493E+10 | 0.00 | 0.42 |
February | 0.331402E+09 | 0.113839E+10 | 0.00 | 4349258.47 | 26386792.26 | 0.00 | 0.553563E+09 | 0.00 | 0.42 |
March | 0.211017E+09 | 0.256144E+10 | 0.00 | 2474349.13 | 40758679.89 | 0.00 | 0.258973E+09 | 0.00 | 0.43 |
April | 56216150.89 | 0.568864E+10 | 0.00 | 778021.08 | 0.158960E+09 | 0.00 | 73533023.87 | 0.00 | 0.42 |
May | 5838629.71 | 0.108324E+11 | 0.00 | 1184942.24 | 0.260944E+09 | 0.00 | 6882187.33 | 0.00 | 0.43 |
June | 979498.88 | 0.150958E+11 | 0.00 | 632391.95 | 0.373974E+09 | 0.00 | 902545.59 | 0.00 | 0.44 |
July | 307996.33 | 0.189630E+11 | 0.00 | 585547.51 | 0.424994E+09 | 0.00 | 721420.60 | 0.00 | 0.43 |
August | 0.00 | 0.210259E+11 | 0.00 | 21072.15 | 0.333428E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 862993.53 | 0.163144E+11 | 0.00 | 1320901.71 | 0.414999E+09 | 0.00 | 974093.53 | 0.00 | 0.43 |
October | 5638225.65 | 0.108926E+11 | 0.00 | 932116.83 | 0.340160E+09 | 0.00 | 18216285.32 | 0.00 | 0.42 |
November | 4920684.40 | 0.615861E+10 | 0.00 | 567009.46 | 0.128740E+09 | 0.00 | 9734694.03 | 0.00 | 0.42 |
December | 0.213514E+09 | 0.177453E+10 | 0.00 | 3972576.25 | 48159882.26 | 0.00 | 0.465656E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.143416E+10 | 0.110841E+12 | 0.00 | 23081225.63 | 0.256172E+10 | 0.00 | 0.242409E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.395111E+09 | 0.00 | 21072.15 | 10217066.37 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.603458E+09 | 0.210259E+11 | 0.00 | 6263038.84 | 0.424994E+09 | 0.00 | 0.103493E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307275E+09 | 0.196287E+09 | 0.00 | 3145923.81 | 4915837.70 | 0.00 | 0.504271E+09 | 0.00 | 0.42 |
February | 0.166692E+09 | 0.571283E+09 | 0.00 | 2171238.61 | 12770947.92 | 0.00 | 0.273257E+09 | 0.00 | 0.42 |
March | 0.104397E+09 | 0.128569E+10 | 0.00 | 1229954.63 | 19939157.96 | 0.00 | 0.128845E+09 | 0.00 | 0.43 |
April | 28015067.91 | 0.285058E+10 | 0.00 | 379438.84 | 79549193.43 | 0.00 | 36728089.68 | 0.00 | 0.42 |
May | 2905867.45 | 0.543091E+10 | 0.00 | 556020.64 | 0.131443E+09 | 0.00 | 3533706.01 | 0.00 | 0.43 |
June | 475341.46 | 0.755648E+10 | 0.00 | 311147.35 | 0.190752E+09 | 0.00 | 424569.72 | 0.00 | 0.44 |
July | 89711.92 | 0.948185E+10 | 0.00 | 312344.30 | 0.223820E+09 | 0.00 | 426077.21 | 0.00 | 0.43 |
August | 0.00 | 0.105198E+11 | 0.00 | 13787.63 | 0.167950E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 402892.76 | 0.816103E+10 | 0.00 | 651600.89 | 0.207561E+09 | 0.00 | 484788.09 | 0.00 | 0.43 |
October | 2616842.80 | 0.545861E+10 | 0.00 | 451283.75 | 0.167754E+09 | 0.00 | 9022672.40 | 0.00 | 0.42 |
November | 2381285.70 | 0.308282E+10 | 0.00 | 275385.40 | 64845490.22 | 0.00 | 4849586.97 | 0.00 | 0.42 |
December | 0.103910E+09 | 0.887095E+09 | 0.00 | 1989962.12 | 23403683.11 | 0.00 | 0.232421E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.719161E+09 | 0.554824E+11 | 0.00 | 11488087.96 | 0.129471E+10 | 0.00 | 0.119426E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.196287E+09 | 0.00 | 13787.63 | 4915837.70 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.307275E+09 | 0.105198E+11 | 0.00 | 3145923.81 | 0.223820E+09 | 0.00 | 0.504271E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.309862E+09 | 0.193250E+09 | 0.00 | 3099702.73 | 4901743.08 | 0.00 | 0.505636E+09 | 0.00 | 0.42 |
February | 0.169608E+09 | 0.566704E+09 | 0.00 | 2136067.83 | 12707266.08 | 0.00 | 0.274034E+09 | 0.00 | 0.42 |
March | 0.107697E+09 | 0.127968E+10 | 0.00 | 1208198.44 | 19860879.89 | 0.00 | 0.127126E+09 | 0.00 | 0.43 |
April | 28229484.68 | 0.284399E+10 | 0.00 | 374979.00 | 79400344.86 | 0.00 | 37172338.23 | 0.00 | 0.42 |
May | 2927108.16 | 0.542597E+10 | 0.00 | 552532.15 | 0.131148E+09 | 0.00 | 3545586.71 | 0.00 | 0.43 |
June | 481146.15 | 0.755102E+10 | 0.00 | 310443.40 | 0.189961E+09 | 0.00 | 431312.13 | 0.00 | 0.44 |
July | 90411.81 | 0.947276E+10 | 0.00 | 314632.35 | 0.227283E+09 | 0.00 | 427771.91 | 0.00 | 0.43 |
August | 0.00 | 0.105137E+11 | 0.00 | 14114.65 | 0.168164E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 407490.74 | 0.815499E+10 | 0.00 | 654768.74 | 0.207407E+09 | 0.00 | 489793.00 | 0.00 | 0.43 |
October | 2668386.56 | 0.545123E+10 | 0.00 | 448299.10 | 0.169380E+09 | 0.00 | 9036873.85 | 0.00 | 0.42 |
November | 2418206.31 | 0.307562E+10 | 0.00 | 270491.26 | 64713193.34 | 0.00 | 4915670.43 | 0.00 | 0.42 |
December | 0.108386E+09 | 0.880739E+09 | 0.00 | 1979780.21 | 23295696.82 | 0.00 | 0.231138E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.732775E+09 | 0.554096E+11 | 0.00 | 11364009.86 | 0.129822E+10 | 0.00 | 0.119395E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.193250E+09 | 0.00 | 14114.65 | 4901743.08 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.309862E+09 | 0.105137E+11 | 0.00 | 3099702.73 | 0.227283E+09 | 0.00 | 0.505636E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319064E+09 | 0.187605E+09 | 0.00 | 2982373.09 | 4927860.83 | 0.00 | 0.502349E+09 | 0.00 | 0.42 |
February | 0.178951E+09 | 0.558229E+09 | 0.00 | 2074468.85 | 12561606.90 | 0.00 | 0.271536E+09 | 0.00 | 0.42 |
March | 0.112194E+09 | 0.127041E+10 | 0.00 | 1149961.35 | 20023911.61 | 0.00 | 0.125353E+09 | 0.00 | 0.43 |
April | 30310366.20 | 0.283814E+10 | 0.00 | 348472.53 | 79706118.79 | 0.00 | 36750720.90 | 0.00 | 0.42 |
May | 3050131.08 | 0.544104E+10 | 0.00 | 537514.45 | 0.125656E+09 | 0.00 | 3436131.58 | 0.00 | 0.43 |
June | 482694.78 | 0.756868E+10 | 0.00 | 305805.43 | 0.191626E+09 | 0.00 | 431379.83 | 0.00 | 0.44 |
July | 90337.29 | 0.951539E+10 | 0.00 | 318485.42 | 0.215270E+09 | 0.00 | 423135.85 | 0.00 | 0.43 |
August | 0.00 | 0.105545E+11 | 0.00 | 15244.84 | 0.165960E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 388396.81 | 0.818595E+10 | 0.00 | 669591.37 | 0.205261E+09 | 0.00 | 459761.26 | 0.00 | 0.43 |
October | 2607089.37 | 0.547200E+10 | 0.00 | 454216.90 | 0.166380E+09 | 0.00 | 8990896.76 | 0.00 | 0.42 |
November | 2495154.28 | 0.307863E+10 | 0.00 | 261167.98 | 64330607.25 | 0.00 | 4997790.33 | 0.00 | 0.42 |
December | 0.117464E+09 | 0.871495E+09 | 0.00 | 1924804.15 | 23194721.67 | 0.00 | 0.227868E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.767097E+09 | 0.555421E+11 | 0.00 | 11042106.37 | 0.127490E+10 | 0.00 | 0.118260E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.187605E+09 | 0.00 | 15244.84 | 4927860.83 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.319064E+09 | 0.105545E+11 | 0.00 | 2982373.09 | 0.215270E+09 | 0.00 | 0.502349E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310501E+09 | 0.200487E+09 | 0.00 | 3052746.08 | 4413221.49 | 0.00 | 0.485757E+09 | 0.00 | 0.42 |
February | 0.186133E+09 | 0.563926E+09 | 0.00 | 2118704.26 | 10602215.19 | 0.00 | 0.255960E+09 | 0.00 | 0.42 |
March | 0.124429E+09 | 0.128584E+10 | 0.00 | 1106970.59 | 18458461.37 | 0.00 | 0.114132E+09 | 0.00 | 0.43 |
April | 39837296.07 | 0.286519E+10 | 0.00 | 323516.85 | 74233913.85 | 0.00 | 37152258.25 | 0.00 | 0.42 |
May | 2602805.10 | 0.553416E+10 | 0.00 | 772406.83 | 0.110739E+09 | 0.00 | 4593814.41 | 0.00 | 0.43 |
June | 806509.49 | 0.775075E+10 | 0.00 | 405743.72 | 0.152176E+09 | 0.00 | 823845.84 | 0.00 | 0.44 |
July | 70033.18 | 0.974051E+10 | 0.00 | 617092.14 | 0.173914E+09 | 0.00 | 142630.23 | 0.00 | 0.43 |
August | 0.00 | 0.108317E+11 | 0.00 | 177569.94 | 0.133767E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 407769.80 | 0.842022E+10 | 0.00 | 976711.13 | 0.172323E+09 | 0.00 | 497336.48 | 0.00 | 0.43 |
October | 2185811.54 | 0.561717E+10 | 0.00 | 617441.21 | 0.143111E+09 | 0.00 | 11295480.76 | 0.00 | 0.42 |
November | 3582586.57 | 0.316572E+10 | 0.00 | 301913.06 | 56645241.22 | 0.00 | 6572104.88 | 0.00 | 0.42 |
December | 0.126965E+09 | 0.903355E+09 | 0.00 | 1975120.51 | 23543973.36 | 0.00 | 0.214902E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.797520E+09 | 0.568790E+11 | 0.00 | 12445936.32 | 0.107393E+10 | 0.00 | 0.113183E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.200487E+09 | 0.00 | 177569.94 | 4413221.49 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.310501E+09 | 0.108317E+11 | 0.00 | 3052746.08 | 0.173914E+09 | 0.00 | 0.485757E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.133568E+12 | 0.199887E+10 | 0.00 | 0.353594E+11 | 0.792134E+11 |
February | 0.156179E+12 | -0.305252E+10 | 0.00 | 0.151698E+11 | 0.951942E+11 |
March | 0.202547E+12 | -0.102630E+11 | 0.00 | -0.280140E+10 | 0.136547E+12 |
April | 0.223658E+12 | -0.243190E+11 | 0.00 | -0.416003E+11 | 0.191725E+12 |
May | 0.244731E+12 | -0.423497E+11 | 0.00 | -0.104801E+12 | 0.290660E+12 |
June | 0.238821E+12 | -0.566701E+11 | 0.00 | -0.153784E+12 | 0.352150E+12 |
July | 0.241492E+12 | -0.712568E+11 | 0.00 | -0.202548E+12 | 0.423098E+12 |
August | 0.231105E+12 | -0.763690E+11 | 0.00 | -0.216617E+12 | 0.454208E+12 |
September | 0.195251E+12 | -0.616154E+11 | 0.00 | -0.164625E+12 | 0.374921E+12 |
October | 0.158049E+12 | -0.410995E+11 | 0.00 | -0.112399E+12 | 0.294204E+12 |
November | 0.119039E+12 | -0.242566E+11 | 0.00 | -0.472379E+11 | 0.204869E+12 |
December | 0.114920E+12 | -0.688130E+10 | 0.00 | 0.105003E+11 | 0.121011E+12 |
Annual Sum or Average | 0.225936E+13 | -0.416134E+12 | 0.00 | -0.985383E+12 | 0.301780E+13 |
Minimum of Months | 0.114920E+12 | -0.763690E+11 | 0.00 | -0.216617E+12 | 0.792134E+11 |
Maximum of Months | 0.244731E+12 | 0.199887E+10 | 0.00 | 0.353594E+11 | 0.454208E+12 |