Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:36:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1330.03 | 636.28 | 636.28 |
Net Site Energy | 1330.03 | 636.28 | 636.28 |
Total Source Energy | 3281.83 | 1570.01 | 1570.01 |
Net Source Energy | 3281.83 | 1570.01 | 1570.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 446.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 122.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 883.38 | 446.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 446.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 122.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 63.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 446.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 122.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 63.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 137.07 | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 422.60 | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 137.07 | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 422.60 | 213.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 883.379 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 883.379 | 100.00 |
Total On-Site and Utility Electric Sources | 883.379 | 100.00 |
Total Electricity End Uses | 883.379 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2354.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-12:00 | 06-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 231351.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49316.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8469.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5448.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 97554.40 | 231351.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 231351.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49316.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8469.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5448.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 484.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 386.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 318.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 201.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2797.66 | 484.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 231.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1338.39 | 231.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 231.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1338.39 | 231.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.00 |
SMSTORE1 DIRECT AIR | 1.06 |
SMSTORE2 DIRECT AIR | 1.08 |
SMSTORE3 DIRECT AIR | 1.07 |
SMSTORE4 DIRECT AIR | 1.07 |
LGSTORE2 DIRECT AIR | 1.89 |
SMSTORE5 DIRECT AIR | 0.984805 |
SMSTORE6 DIRECT AIR | 0.979763 |
SMSTORE7 DIRECT AIR | 0.976110 |
SMSTORE8 DIRECT AIR | 1.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ-AC_2:2 | 1.06 | 1.06 | 1.06 | 1.06 | 1.07 | 1.07 | 1.00 | 0.989208 | 1.07 |
PSZ-AC_3:3 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_4:4 | 1.07 | 1.07 | 1.07 | 1.07 | 1.08 | 1.08 | 1.00 | 0.994091 | 1.08 |
PSZ-AC_5:5 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
PSZ-AC_7:7 | 0.984805 | 0.984805 | 0.984805 | 0.984805 | 0.984805 | 0.984805 | 1.00 | 1.00 | 0.984805 |
PSZ-AC_8:8 | 0.979763 | 0.979763 | 0.979763 | 0.979763 | 0.979763 | 0.979763 | 1.00 | 1.00 | 0.979763 |
PSZ-AC_9:9 | 0.976110 | 0.976110 | 0.976110 | 0.976110 | 0.976516 | 0.976516 | 1.00 | 0.999585 | 0.976516 |
PSZ-AC_10:10 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 0.994203 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.00 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.08 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.08 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.89 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.984805 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.979763 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.976516 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.00 | 2142.40 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1186.90 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1196.33 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1196.07 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1188.79 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2025.50 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.984805 | 1090.33 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.979763 | 1084.75 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.976516 | 1081.16 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1186.08 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 1.32 | 45488.02 | 61581.92 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.707537 | 23912.76 | 32147.23 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.713157 | 24048.54 | 32606.20 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.713000 | 24023.29 | 32454.87 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.708661 | 23928.61 | 32450.54 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 43339.51 | 59083.80 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.984805 | 0.984805 | 0.984805 | 0.649971 | 22426.51 | 30418.44 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.979763 | 0.979763 | 0.979763 | 0.646644 | 22344.11 | 30303.24 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.976516 | 0.976516 | 0.976516 | 0.644500 | 22279.00 | 30219.77 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.707049 | 24030.32 | 32254.42 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.00 | 1.00 | 1.33 | 45488.02 | 22744.01 | 0.729880 | 0.729880 |
PSZ-AC_2:2 COOLING COIL | 1.07 | 0.536013 | 0.714687 | 23912.76 | 11956.38 | 0.735840 | 0.735840 |
PSZ-AC_3:3 COOLING COIL | 1.08 | 0.540270 | 0.720360 | 24048.54 | 12024.27 | 0.736450 | 0.736450 |
PSZ-AC_4:4 COOLING COIL | 1.08 | 0.540151 | 0.720200 | 24023.29 | 12011.65 | 0.736680 | 0.736680 |
PSZ-AC_5:5 COOLING COIL | 1.07 | 0.536865 | 0.715820 | 23928.61 | 11964.31 | 0.736090 | 0.736090 |
PSZ-AC_6:6 COOLING COIL | 1.89 | 0.946454 | 1.26 | 43339.51 | 21669.76 | 0.726810 | 0.726810 |
PSZ-AC_7:7 COOLING COIL | 0.984800 | 0.492402 | 0.656533 | 22426.51 | 11213.25 | 0.729250 | 0.729250 |
PSZ-AC_8:8 COOLING COIL | 0.979760 | 0.489881 | 0.653173 | 22344.11 | 11172.06 | 0.728860 | 0.728860 |
PSZ-AC_9:9 COOLING COIL | 0.976520 | 0.488258 | 0.651013 | 22279.00 | 11139.50 | 0.727760 | 0.727760 |
PSZ-AC_10:10 COOLING COIL | 1.07 | 0.535643 | 0.714193 | 24030.32 | 12015.16 | 0.734320 | 0.734320 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61581.92 |
PSZ-AC_2:2 HEATING COIL | 32147.23 |
PSZ-AC_3:3 HEATING COIL | 32606.20 |
PSZ-AC_4:4 HEATING COIL | 32454.87 |
PSZ-AC_5:5 HEATING COIL | 32450.54 |
PSZ-AC_6:6 HEATING COIL | 59083.80 |
PSZ-AC_7:7 HEATING COIL | 30418.44 |
PSZ-AC_8:8 HEATING COIL | 30303.24 |
PSZ-AC_9:9 HEATING COIL | 30219.77 |
PSZ-AC_10:10 HEATING COIL | 32254.42 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22719.88795 | 27263.86553 | 1.66846 | 2.00216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.41196E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 25537.99566 | 30645.59479 | 1.10125 | 1.32150 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12376.67113 | 14852.00535 | 0.88371 | 1.06046 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11786.82928 | 14144.19513 | 0.50829 | 0.60995 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12607.53508 | 15129.04209 | 0.90045 | 1.08054 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 11937.21528 | 14324.65833 | 0.51477 | 0.61773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12532.51164 | 15039.01397 | 0.89493 | 1.07392 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 12024.84753 | 14429.81704 | 0.51855 | 0.62226 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12529.82837 | 15035.79404 | 0.89477 | 1.07373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 12171.67274 | 14606.00728 | 0.52488 | 0.62986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21482.60006 | 25779.12007 | 1.57742 | 1.89291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 23406.49295 | 28087.79154 | 1.00938 | 1.21126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11513.62579 | 13816.35094 | 0.82067 | 0.98480 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12492.17986 | 14990.61583 | 0.53871 | 0.64645 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11456.14351 | 13747.37221 | 0.81647 | 0.97976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 12482.09862 | 14978.51834 | 0.53827 | 0.64593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11414.36000 | 13697.23200 | 0.81343 | 0.97611 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12691.64840 | 15229.97808 | 0.54731 | 0.65677 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12426.44923 | 14911.73908 | 0.88756 | 1.06508 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 15998.26396 | 19197.91676 | 0.68984 | 0.82781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30930.55 | 2.00216 | 2.00216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 46027.37 | 1.32150 | 1.32150 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16352.44 | 1.07203 | 1.07203 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21852.40 | 0.60995 | 0.60995 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16405.93 | 1.08054 | 1.08054 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 22030.24 | 0.61773 | 0.61773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16453.35 | 1.08030 | 1.08030 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 22133.87 | 0.62226 | 0.62226 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16330.83 | 1.07373 | 1.07373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 22307.50 | 0.62986 | 0.62986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29319.85 | 1.89291 | 1.89291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 43507.26 | 1.21126 | 1.21126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15104.55 | 0.98480 | 0.98480 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22686.51 | 0.64645 | 0.64645 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15031.70 | 0.97976 | 0.97976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22674.59 | 0.64593 | 0.64593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15011.65 | 0.97652 | 0.97652 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22922.39 | 0.65677 | 0.65677 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16222.00 | 1.07129 | 1.07129 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 26832.14 | 0.82781 | 0.82781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00216 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06046 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08054 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07392 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07373 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89291 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98480 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97976 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97611 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06508 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00216 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00216 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00216 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00216 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00216 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.00216 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06046 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06046 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06046 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06046 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07203 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07203 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98921 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08054 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08054 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08054 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08054 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08054 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08054 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07392 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07392 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07392 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07392 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08030 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08030 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.99409 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07373 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07373 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07373 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07373 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07373 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07373 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89291 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89291 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89291 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89291 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89291 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89291 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98480 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98480 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98480 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98480 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98480 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98480 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97976 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97976 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97976 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97976 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97976 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97976 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97611 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97611 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97611 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97611 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97652 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97652 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99959 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06508 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06508 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06508 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06508 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07129 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07129 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.99420 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.00216 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.07203 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.08054 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.08030 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.07373 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.89291 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.98480 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97976 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.97652 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.07129 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00216 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00216 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2142.40064 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00216 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00216 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00216 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32142 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00216 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00108 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33477 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45488.02000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22744.01000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72988 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72988 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45488.02000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61581.91798 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61581.91798 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07203 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07203 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1186.90196 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07203 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07203 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07203 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70754 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07203 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53601 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71469 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23912.76000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11956.38000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73584 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73584 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23912.76000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32147.22632 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32147.22632 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08054 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08054 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1196.33023 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08054 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08054 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08054 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71316 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08054 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54027 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72036 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24048.54000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12024.27000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73645 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73645 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24048.54000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32606.19824 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 32606.19824 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08030 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08030 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1196.06665 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08030 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08030 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08030 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71300 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08030 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54015 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72020 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24023.29000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12011.64500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73668 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73668 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24023.29000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32454.87277 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32454.87277 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07373 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07373 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1188.78905 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07373 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07373 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07373 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07373 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53686 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71582 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23928.61000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11964.30500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73609 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73609 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23928.61000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32450.53849 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 32450.53849 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89291 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89291 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2025.50068 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89291 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89291 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89291 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24932 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89291 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94645 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26194 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43339.51000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21669.75500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72681 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72681 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43339.51000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59083.80298 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 59083.80298 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98480 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98480 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1090.33495 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98480 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98480 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98480 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64997 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98480 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49240 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65653 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22426.51000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11213.25500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72925 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72925 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22426.51000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30418.44446 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30418.44446 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97976 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97976 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1084.75315 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97976 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97976 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97976 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64664 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97976 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48988 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65317 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22344.11000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11172.05500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72886 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72886 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22344.11000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30303.23723 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 30303.23723 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97652 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97652 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1081.15768 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97652 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97652 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97652 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64450 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97652 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48826 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65101 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22279.00000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11139.50000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72776 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72776 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22279.00000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30219.76530 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 30219.76530 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07129 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07129 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1186.08475 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07129 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07129 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07129 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70705 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07129 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53564 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71419 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24030.32000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12015.16000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73432 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73432 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24030.32000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32254.41871 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32254.41871 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 43911.1 | 11.61 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 23068.7 | 11.75 | 11.75 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 23197.8 | 11.75 | 11.75 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 23172.8 | 11.74 | 11.74 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 23083.2 | 11.75 | 11.75 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 41848.5 | 11.62 | 11.62 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21650.9 | 11.79 | 11.79 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 21572.4 | 11.79 | 11.79 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 21509.8 | 11.79 | 11.79 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 23186.8 | 11.76 | 11.76 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.6216230922E-002 | 0.3500360918 | Pass | Pass | 9.0682067343E-002 | 0.4775474262 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.4910108570E-002 | 0.2664837891 | Pass | Pass | 0.1178136174 | 0.3386775108 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.6691962245E-002 | 0.3485592475 | Pass | Pass | 3.5936933913E-002 | 0.1040686546 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 7.3905076802E-002 | 0.3834600332 | Pass | Pass | 3.3290641641E-002 | 9.7434104399E-002 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 7.8426025757E-002 | 0.4063490322 | Pass | Pass | 3.1240882962E-002 | 9.2892046786E-002 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 8.9748902289E-002 | 0.4224069399 | Pass | Pass | 3.2750456345E-002 | 0.1362181271 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 9.0559343858E-002 | 0.4206017715 | Pass | Pass | 2.3881916489E-002 | 7.9373903314E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 8.8952178727E-002 | 0.4219248472 | Pass | Pass | 2.3836459717E-002 | 7.9265549138E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.1002809571 | 0.4327198234 | Pass | Pass | 3.1675165746E-002 | 0.1243657127 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.2358043766 | 0.4715627009 | Pass | Pass | 0.2681568091 | 0.9043482914 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4100.96 | 169.92 | 0.00 | 383.96 | 710.81 | 5365.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.153 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.153 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.43 | 42.43 | 3.63 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.64 | 63.04 | 32.47 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.64 | 56.04 | 24.27 | |
Exterior Lighting Total | 5507.06 | 60.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45488.02 | 33200.80 | 12287.22 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23912.76 | 17595.97 | 6316.79 | 0.74 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24048.54 | 17710.55 | 6337.99 | 0.74 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24023.29 | 17697.48 | 6325.81 | 0.74 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23928.61 | 17613.61 | 6315.00 | 0.74 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43339.51 | 31499.59 | 11839.92 | 0.73 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22426.51 | 16354.53 | 6071.98 | 0.73 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22344.11 | 16285.73 | 6058.38 | 0.73 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22279.00 | 16213.77 | 6065.23 | 0.73 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24030.32 | 17645.94 | 6384.38 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 43911.1 | 11.61 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 23068.7 | 11.75 | 11.75 | ||||
PSZ-AC_3:3 COOLING COIL | 23197.8 | 11.75 | 11.75 | ||||
PSZ-AC_4:4 COOLING COIL | 23172.8 | 11.74 | 11.74 | ||||
PSZ-AC_5:5 COOLING COIL | 23083.2 | 11.75 | 11.75 | ||||
PSZ-AC_6:6 COOLING COIL | 41848.5 | 11.62 | 11.62 | ||||
PSZ-AC_7:7 COOLING COIL | 21650.9 | 11.79 | 11.79 | ||||
PSZ-AC_8:8 COOLING COIL | 21572.4 | 11.79 | 11.79 | ||||
PSZ-AC_9:9 COOLING COIL | 21509.8 | 11.79 | 11.79 | ||||
PSZ-AC_10:10 COOLING COIL | 23186.8 | 11.76 | 11.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61581.92 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32147.23 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 32606.20 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32454.87 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 32450.54 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 59083.80 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30418.44 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 30303.24 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 30219.77 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32254.42 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.00 | 2142.40 | 1070.05 | 1.00 | 1.31 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1186.90 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1196.33 | 1107.16 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1196.07 | 1107.16 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1188.79 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2025.50 | 1070.05 | 1.00 | 1.32 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1090.33 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1084.75 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1081.16 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1186.08 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22719.89 | 27263.87 | 78.26 | 1.668 | 2.002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.88 | 0.00978 | 32.10 | 0.01412 | 0.411 | 0.00 |
SMSTORE1 | 12376.67 | 14852.01 | 85.26 | 0.884 | 1.060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00932 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE2 | 12607.54 | 15129.04 | 86.85 | 0.900 | 1.081 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00953 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE3 | 12532.51 | 15039.01 | 86.34 | 0.895 | 1.074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00952 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE4 | 12529.83 | 15035.79 | 86.32 | 0.895 | 1.074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00955 | 28.03 | 0.01411 | 0.206 | 0.00 |
LGSTORE2 | 21482.60 | 25779.12 | 74.00 | 1.577 | 1.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00977 | 31.73 | 0.01412 | 0.411 | 0.00 |
SMSTORE5 | 11513.63 | 13816.35 | 79.32 | 0.821 | 0.985 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00948 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE6 | 11456.14 | 13747.37 | 78.92 | 0.816 | 0.980 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE7 | 11414.36 | 13697.23 | 78.63 | 0.813 | 0.976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00951 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE8 | 12426.45 | 14911.74 | 85.60 | 0.888 | 1.065 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 29.29 | 0.01411 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25538.00 | 30645.59 | 87.96 | 1.101 | 1.321 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE1 | 11786.83 | 14144.20 | 81.20 | 0.508 | 0.610 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00644 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE2 | 11937.22 | 14324.66 | 82.23 | 0.515 | 0.618 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE3 | 12024.85 | 14429.82 | 82.84 | 0.519 | 0.622 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE4 | 12171.67 | 14606.01 | 83.85 | 0.525 | 0.630 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -10.70 | 0.00150 | 0.206 | 0.00 |
LGSTORE2 | 23406.49 | 28087.79 | 80.62 | 1.009 | 1.211 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE5 | 12492.18 | 14990.62 | 86.06 | 0.539 | 0.646 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE6 | 12482.10 | 14978.52 | 85.99 | 0.538 | 0.646 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE7 | 12691.65 | 15229.98 | 87.43 | 0.547 | 0.657 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00652 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE8 | 15998.26 | 19197.92 | 110.21 | 0.690 | 0.828 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -10.70 | 0.00150 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 1.32 | 1.32 | 2.0022 | 2.0022 | 2.0022 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.07 | 1.07 | 0.61 | 0.61 | 1.0720 | 1.0605 | 1.0720 | 0.9892 | 1.0000 |
PSZ-AC_3:3 | 1.08 | 1.08 | 0.62 | 0.62 | 1.0805 | 1.0805 | 1.0805 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.08 | 1.08 | 0.62 | 0.62 | 1.0803 | 1.0739 | 1.0803 | 0.9941 | 1.0000 |
PSZ-AC_5:5 | 1.07 | 1.07 | 0.63 | 0.63 | 1.0737 | 1.0737 | 1.0737 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.21 | 1.21 | 1.8929 | 1.8929 | 1.8929 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.98 | 0.98 | 0.65 | 0.65 | 0.9848 | 0.9848 | 0.9848 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.98 | 0.98 | 0.65 | 0.65 | 0.9798 | 0.9798 | 0.9798 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.98 | 0.98 | 0.66 | 0.66 | 0.9765 | 0.9761 | 0.9765 | 0.9996 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.83 | 0.83 | 1.0713 | 1.0651 | 1.0713 | 0.9942 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 45488.020 | 33200.796 | 2.002160 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22744.01 | 16662.12 | 1.334773 | 26.44 | 18.98 | 0.01066942 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 30.8276 | 23.88 | 0.00977691 | 52.8627 | 22719.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61581.918 | 61581.918 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61581.92 | 61581.92 | 2.002155 | 14.57 | 9.68 | 0.00546251 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.5518 | 21.10 | 0.00648654 | 41.7479 | 25538.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23912.760 | 17595.965 | 1.072030 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11956.38 | 8863.50 | 0.714687 | 26.34 | 18.86 | 0.01055993 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01411942 | 23.10 | 28.7874 | 23.89 | 0.00971211 | 52.5173 | 12136.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32147.226 | 32147.226 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32147.23 | 32147.23 | 1.072025 | 15.00 | 9.90 | 0.00549072 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.1917 | 21.10 | 0.00643758 | 41.4348 | 11786.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 24048.540 | 17710.547 | 1.080540 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12024.27 | 8921.27 | 0.720360 | 26.32 | 18.85 | 0.01055066 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.5606 | 23.89 | 0.00970567 | 52.4829 | 12195.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32606.198 | 32606.198 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32606.20 | 32606.20 | 1.080541 | 15.05 | 9.94 | 0.00550930 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.0404 | 21.10 | 0.00645131 | 41.5223 | 11937.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 24023.290 | 17697.477 | 1.080300 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12011.65 | 8917.31 | 0.720200 | 26.32 | 18.85 | 0.01054514 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.5670 | 23.89 | 0.00970228 | 52.4649 | 12235.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32454.873 | 32454.873 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32454.87 | 32454.87 | 1.080303 | 15.05 | 9.95 | 0.00551528 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.0446 | 21.10 | 0.00645894 | 41.5710 | 12024.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23928.610 | 17613.611 | 1.073730 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11964.31 | 8868.20 | 0.715820 | 26.33 | 18.86 | 0.01055946 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.7418 | 23.89 | 0.00971108 | 52.5117 | 12131.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32450.538 | 32450.538 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32450.54 | 32450.54 | 1.073730 | 15.01 | 9.94 | 0.00551993 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.1612 | 21.10 | 0.00647185 | 41.6532 | 12171.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 43339.510 | 31499.589 | 1.892910 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 21669.76 | 15777.34 | 1.261940 | 26.50 | 19.05 | 0.01072876 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 32.6068 | 23.89 | 0.00978440 | 52.9018 | 21434.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 59083.803 | 59083.803 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59083.80 | 59083.80 | 1.892908 | 14.19 | 9.49 | 0.00544934 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.7379 | 21.10 | 0.00654522 | 42.1196 | 23406.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 22426.510 | 16354.532 | 0.984800 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11213.25 | 8175.96 | 0.656533 | 26.46 | 19.02 | 0.01071046 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.3372 | 23.89 | 0.00980316 | 53.0018 | 11092.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30418.444 | 30418.444 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30418.44 | 30418.44 | 0.984805 | 14.46 | 9.62 | 0.00545554 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.8914 | 21.10 | 0.00649911 | 41.8268 | 12492.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 22344.110 | 16285.728 | 0.979760 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11172.06 | 8137.45 | 0.653173 | 26.47 | 19.03 | 0.01072033 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.4984 | 23.89 | 0.00980925 | 53.0342 | 11031.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30303.237 | 30303.237 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30303.24 | 30303.24 | 0.979763 | 14.43 | 9.60 | 0.00544955 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.9989 | 21.10 | 0.00649832 | 41.8218 | 12482.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 22279.000 | 16213.765 | 0.976520 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11139.50 | 8111.41 | 0.651013 | 26.47 | 19.03 | 0.01072306 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.6029 | 23.89 | 0.00981094 | 53.0432 | 11013.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30219.765 | 30219.765 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30219.77 | 30219.77 | 0.976516 | 14.40 | 9.60 | 0.00545946 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.0687 | 21.10 | 0.00651530 | 41.9300 | 12691.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24030.320 | 17645.945 | 1.071290 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 12015.16 | 8812.51 | 0.714193 | 26.30 | 18.91 | 0.01063966 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01411898 | 23.03 | 28.8072 | 23.88 | 0.00980593 | 53.0173 | 12078.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32254.419 | 32254.419 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32254.42 | 32254.42 | 1.071287 | 15.00 | 9.96 | 0.00555012 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.2049 | 21.10 | 0.00651190 | 41.9122 | 15998.26 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45488.020 | 33200.796 | 2.002160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6739 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.002155 | 2.40978387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 22744.01 | 16662.12 | 1.0000 | 1.60652649 | 1.334773 | 26.44 | 18.98 | 0.01066942 | 53777.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22744.01 | 32.10 | 0.01411964 | 23.13 | 0.41147883 | 30.8276 | 23.89 | 0.00977691 | 23.88 | 0.00977691 | 52.8627 | 22719.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61581.918 | 61581.918 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.002155 | 2.40978387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 61581.92 | 61581.92 | 1.0000 | 2.40978387 | 2.002155 | 14.57 | 9.68 | 0.00546251 | 28448.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61581.92 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 20.5518 | 21.11 | 0.00648654 | 21.10 | 0.00648654 | 41.7479 | 25538.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23912.760 | 17595.965 | 1.072030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4704 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.072025 | 1.29028404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11956.38 | 8863.50 | 1.0000 | 0.86019329 | 0.714687 | 26.34 | 18.86 | 0.01055993 | 53394.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11956.38 | 31.98 | 0.01411942 | 23.10 | 0.20573941 | 28.7874 | 23.89 | 0.00971211 | 23.89 | 0.00971211 | 52.5173 | 12136.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32147.226 | 32147.226 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.072025 | 1.29028404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32147.23 | 32147.23 | 1.0000 | 1.29028404 | 1.072025 | 15.00 | 9.90 | 0.00549072 | 28959.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32147.23 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.1917 | 21.11 | 0.00643758 | 21.10 | 0.00643758 | 41.4348 | 11786.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24048.540 | 17710.547 | 1.080540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4531 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.080541 | 1.30053353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12024.27 | 8921.27 | 1.0000 | 0.86702168 | 0.720360 | 26.32 | 18.85 | 0.01055066 | 53350.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12024.27 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.5606 | 23.89 | 0.00970567 | 23.89 | 0.00970567 | 52.4829 | 12195.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32606.198 | 32606.198 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.080541 | 1.30053353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32606.20 | 32606.20 | 1.0000 | 1.30053353 | 1.080541 | 15.05 | 9.94 | 0.00550930 | 29055.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32606.20 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.0404 | 21.11 | 0.00645131 | 21.10 | 0.00645131 | 41.5223 | 11937.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24023.290 | 17697.477 | 1.080300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4429 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.080303 | 1.30024699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12011.65 | 8917.31 | 1.0000 | 0.86682911 | 0.720200 | 26.32 | 18.85 | 0.01054514 | 53331.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12011.65 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.5670 | 23.89 | 0.00970228 | 23.89 | 0.00970228 | 52.4649 | 12235.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32454.873 | 32454.873 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.080303 | 1.30024699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32454.87 | 32454.87 | 1.0000 | 1.30024699 | 1.080303 | 15.05 | 9.95 | 0.00551528 | 29069.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32454.87 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.0446 | 21.11 | 0.00645894 | 21.10 | 0.00645894 | 41.5710 | 12024.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23928.610 | 17613.611 | 1.073730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4695 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.073730 | 1.29233549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11964.31 | 8868.20 | 1.0000 | 0.86155736 | 0.715820 | 26.33 | 18.86 | 0.01055946 | 53381.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11964.31 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.7418 | 23.89 | 0.00971108 | 23.89 | 0.00971108 | 52.5117 | 12131.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32450.538 | 32450.538 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.073730 | 1.29233549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32450.54 | 32450.54 | 1.0000 | 1.29233549 | 1.073730 | 15.01 | 9.94 | 0.00551993 | 29043.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32450.54 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.1612 | 21.11 | 0.00647185 | 21.10 | 0.00647185 | 41.6532 | 12171.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43339.510 | 31499.589 | 1.892910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7842 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.892908 | 2.27829417 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 21669.76 | 15777.34 | 1.0000 | 1.51886465 | 1.261940 | 26.50 | 19.05 | 0.01072876 | 53991.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21669.76 | 31.92 | 0.01411931 | 23.08 | 0.41147883 | 32.6068 | 23.89 | 0.00978440 | 23.89 | 0.00978440 | 52.9018 | 21434.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59083.803 | 59083.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.892908 | 2.27829417 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 59083.80 | 59083.80 | 1.0000 | 2.27829417 | 1.892908 | 14.19 | 9.49 | 0.00544934 | 28033.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59083.80 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 21.7379 | 21.11 | 0.00654522 | 21.10 | 0.00654522 | 42.1196 | 23406.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22426.510 | 16354.532 | 0.984800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7502 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.984805 | 1.18530580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 11213.25 | 8175.96 | 1.0000 | 0.79020023 | 0.656533 | 26.46 | 19.02 | 0.01071046 | 53899.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11213.25 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.3372 | 23.89 | 0.00980316 | 23.89 | 0.00980316 | 53.0018 | 11092.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30418.444 | 30418.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.984805 | 1.18530580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30418.44 | 30418.44 | 1.0000 | 1.18530580 | 0.984805 | 14.46 | 9.62 | 0.00545554 | 28321.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30418.44 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 20.8914 | 21.11 | 0.00649911 | 21.10 | 0.00649911 | 41.8268 | 12492.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22344.110 | 16285.728 | 0.979760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7686 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979763 | 1.17923782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 11172.06 | 8137.45 | 1.0000 | 0.78615615 | 0.653173 | 26.47 | 19.03 | 0.01072033 | 53934.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.06 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.4984 | 23.89 | 0.00980925 | 23.89 | 0.00980925 | 53.0342 | 11031.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30303.237 | 30303.237 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979763 | 1.17923782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30303.24 | 30303.24 | 1.0000 | 1.17923782 | 0.979763 | 14.43 | 9.60 | 0.00544955 | 28271.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30303.24 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 20.9989 | 21.11 | 0.00649832 | 21.10 | 0.00649832 | 41.8218 | 12482.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22279.000 | 16213.765 | 0.976520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7736 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976516 | 1.17532916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 11139.50 | 8111.41 | 1.0000 | 0.78355638 | 0.651013 | 26.47 | 19.03 | 0.01072306 | 53943.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11139.50 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.6029 | 23.89 | 0.00981094 | 23.89 | 0.00981094 | 53.0432 | 11013.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30219.765 | 30219.765 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976516 | 1.17532916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30219.77 | 30219.77 | 1.0000 | 1.17532916 | 0.976516 | 14.40 | 9.60 | 0.00545946 | 28274.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30219.77 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.0687 | 21.11 | 0.00651530 | 21.10 | 0.00651530 | 41.9300 | 12691.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24030.320 | 17645.945 | 1.071290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6186 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071287 | 1.28939564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 12015.16 | 8812.51 | 1.0000 | 0.85959951 | 0.714193 | 26.30 | 18.91 | 0.01063966 | 53556.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12015.16 | 31.73 | 0.01411898 | 23.03 | 0.20573941 | 28.8072 | 23.89 | 0.00980593 | 23.88 | 0.00980593 | 53.0173 | 12078.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32254.419 | 32254.419 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071287 | 1.28939564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32254.42 | 32254.42 | 1.0000 | 1.28939564 | 1.071287 | 15.00 | 9.96 | 0.00555012 | 29104.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32254.42 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.2049 | 21.10 | 0.00651190 | 21.10 | 0.00651190 | 41.9122 | 15998.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.00 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.08 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.08 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.89 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.98 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.98 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.98 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3087.33 | 3570.50 | 1311.17 |
SMSTORE1 | 2429.33 | 3182.17 | 478.00 |
SMSTORE2 | 2077.83 | 2592.33 | 673.67 |
SMSTORE3 | 2122.00 | 2618.17 | 734.17 |
SMSTORE4 | 2172.00 | 2680.17 | 842.00 |
LGSTORE2 | 2222.83 | 2652.00 | 1174.17 |
SMSTORE5 | 2194.50 | 2692.83 | 1198.33 |
SMSTORE6 | 2215.33 | 2726.83 | 1245.00 |
SMSTORE7 | 2313.17 | 2795.17 | 1390.00 |
SMSTORE8 | 2674.00 | 2892.00 | 1789.17 |
Facility | 4004.67 | 4175.00 | 2354.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 6.50 | 0.00 | 2.00 | 0.00 |
SMSTORE1 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 22.50 | 0.00 | 0.00 | 0.00 |
Facility | 28.67 | 0.00 | 2.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.932 | 0.236 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.798 | 0.248 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.986 | 0.323 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.983 | 0.323 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.974 | 0.323 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.948 | 0.310 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.954 | 0.344 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.951 | 0.344 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.943 | 0.344 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.956 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9680184.62 | 0.00 | 9680184.62 | 2905267.86 | 12585452.47 | 12976396.34 | 3162.03 | 4639.67 | 958.30 | 13.85 |
SMSTORE1 | 4140142.69 | 0.00 | 4140142.69 | 1421541.01 | 5561683.70 | 6488198.17 | 4435.11 | 3316.17 | 1008.72 | 19.01 |
SMSTORE2 | 3894295.21 | 0.00 | 3894295.21 | 1467297.82 | 5361593.03 | 6488198.17 | 4343.48 | 3678.00 | 738.52 | 66.68 |
SMSTORE3 | 3879205.01 | 0.00 | 3879205.01 | 1467297.82 | 5346502.84 | 6488198.17 | 4344.72 | 3698.75 | 716.53 | 63.75 |
SMSTORE4 | 3839638.17 | 0.00 | 3839638.17 | 1467297.82 | 5306936.00 | 6488198.17 | 4346.36 | 3737.43 | 676.20 | 61.03 |
LGSTORE2 | 6851074.36 | 0.00 | 6851074.36 | 2708743.34 | 9559817.70 | 12976396.34 | 4712.89 | 3433.83 | 613.27 | 52.20 |
SMSTORE5 | 3448104.92 | 0.00 | 3448104.92 | 1479898.30 | 4928003.22 | 6488198.17 | 4712.54 | 3444.33 | 603.12 | 50.63 |
SMSTORE6 | 3434229.11 | 0.00 | 3434229.11 | 1479898.30 | 4914127.41 | 6488198.17 | 4712.58 | 3457.58 | 589.83 | 47.79 |
SMSTORE7 | 3404610.44 | 0.00 | 3404610.44 | 1479898.30 | 4884508.74 | 6488198.17 | 4714.79 | 3496.83 | 548.38 | 41.07 |
SMSTORE8 | 3453058.86 | 0.00 | 3453058.86 | 1880673.34 | 5333732.20 | 6488198.17 | 4713.56 | 3521.25 | 525.19 | 32.30 |
Total Facility | 46024543.38 | 0.00 | 46024543.38 | 17757813.92 | 63782357.30 | 77858378.04 | 4723.05 | 5194.83 | 1260.49 | 144.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4596 | 0.0000 | 0.4596 | 0.1164 | 0.5761 | 0.4115 | 246.39 | 4639.67 | 953.95 |
SMSTORE1 | 0.1965 | 0.0000 | 0.1965 | 0.0612 | 0.2578 | 0.2057 | 1518.23 | 3316.00 | 1005.77 |
SMSTORE2 | 0.2432 | 0.0000 | 0.2432 | 0.0797 | 0.3229 | 0.2057 | 0.00 | 3677.33 | 717.67 |
SMSTORE3 | 0.2423 | 0.0000 | 0.2423 | 0.0797 | 0.3220 | 0.2057 | 0.00 | 3698.58 | 696.42 |
SMSTORE4 | 0.2401 | 0.0000 | 0.2401 | 0.0797 | 0.3197 | 0.2057 | 0.00 | 3737.27 | 657.73 |
LGSTORE2 | 0.4675 | 0.0000 | 0.4675 | 0.1532 | 0.6206 | 0.4115 | 0.00 | 3433.83 | 596.17 |
SMSTORE5 | 0.2352 | 0.0000 | 0.2352 | 0.0850 | 0.3202 | 0.2057 | 0.00 | 3444.17 | 585.83 |
SMSTORE6 | 0.2344 | 0.0000 | 0.2344 | 0.0850 | 0.3193 | 0.2057 | 0.00 | 3457.08 | 572.92 |
SMSTORE7 | 0.2326 | 0.0000 | 0.2326 | 0.0850 | 0.3176 | 0.2057 | 0.00 | 3496.67 | 533.33 |
SMSTORE8 | 0.2359 | 0.0000 | 0.2359 | 0.0911 | 0.3269 | 0.2057 | 0.00 | 3520.83 | 509.17 |
Total Facility | 2.7873 | 0.0000 | 2.7873 | 0.9158 | 3.7032 | 2.4689 | 1625.03 | 5192.58 | 1236.09 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14023540.75 | 0.00 | 14023540.75 | 12976396.34 | 3154.87 | 0.58 | 5604.55 | 13.85 |
PSZ-AC_2:2 | 5997710.55 | 0.00 | 5997710.55 | 6488198.17 | 4361.52 | 3.33 | 4395.15 | 19.01 |
PSZ-AC_3:3 | 5641581.34 | 0.00 | 5641581.34 | 6488198.17 | 4335.06 | 0.50 | 4424.44 | 66.68 |
PSZ-AC_4:4 | 5619720.67 | 0.00 | 5619720.67 | 6488198.17 | 4335.44 | 0.50 | 4424.06 | 63.59 |
PSZ-AC_5:5 | 5562401.16 | 0.00 | 5562401.16 | 6488198.17 | 4338.66 | 0.50 | 4420.84 | 60.95 |
PSZ-AC_6:6 | 9925070.43 | 0.00 | 9925070.43 | 12976396.34 | 4706.94 | 0.50 | 4052.56 | 52.03 |
PSZ-AC_7:7 | 4995210.35 | 0.00 | 4995210.35 | 6488198.17 | 4706.57 | 0.33 | 4053.10 | 50.63 |
PSZ-AC_8:8 | 4975105.49 | 0.00 | 4975105.49 | 6488198.17 | 4708.38 | 0.33 | 4051.28 | 47.79 |
PSZ-AC_9:9 | 4932181.90 | 0.00 | 4932181.90 | 6488198.17 | 4711.73 | 0.17 | 4048.10 | 41.07 |
PSZ-AC_10:10 | 5002301.48 | 0.00 | 5002301.48 | 6488198.17 | 4710.81 | 0.33 | 4048.85 | 32.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6659 | 0.0000 | 0.6659 | 0.4115 | 240.30 | 0.42 | 5599.28 |
PSZ-AC_2:2 | 0.2847 | 0.0000 | 0.2847 | 0.2057 | 1446.47 | 3.33 | 4390.20 |
PSZ-AC_3:3 | 0.3523 | 0.0000 | 0.3523 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3511 | 0.0000 | 0.3511 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3478 | 0.0000 | 0.3478 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6772 | 0.0000 | 0.6772 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3408 | 0.0000 | 0.3408 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3396 | 0.0000 | 0.3396 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3370 | 0.0000 | 0.3370 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3417 | 0.0000 | 0.3417 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5187.49 | 446.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4279.77 | 721.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4116.28 | 345.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4128.90 | 329.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4147.30 | 308.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3838.80 | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3836.81 | 243.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3844.17 | 233.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3863.60 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3866.76 | 195.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6753 | 0.8914 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3253 | 0.3852 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3425 | 0.4919 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3416 | 0.4935 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3389 | 0.4919 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6657 | 0.9039 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3343 | 0.4653 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3333 | 0.4635 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3312 | 0.4666 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3347 | 0.4987 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
ElectricityPurchased:Plant | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
Cogeneration:ElectricityPurchased | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
General:Cogeneration:ElectricityPurchased | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
ElectricityNet:Plant | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
Cogeneration:ElectricityNet | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
General:Cogeneration:ElectricityNet | 883.38 | 2102.83 | 01-JAN-08:00 | 97554.40 | 16-AUG-13:00 |
Electricity:HVAC | 222.82 | 0.00 | 01-JAN-00:40 | 58119.88 | 08-JUL-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 122.12 | 0.00 | 01-JAN-00:10 | 49566.88 | 08-JUL-12:10 |
General:Cooling:Electricity | 122.12 | 0.00 | 01-JAN-00:10 | 49566.88 | 08-JUL-12:10 |
Fans:Electricity | 100.69 | 0.00 | 01-JAN-00:40 | 9320.04 | 06-FEB-08:10 |
General:Fans:Electricity | 100.69 | 0.00 | 01-JAN-00:40 | 9320.04 | 06-FEB-08:10 |
ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 63.69 | 1211.00 | 09-JAN-07:10 | 11858.70 | 04-JAN-13:50 |
WaterSystems:Electricity | 63.69 | 1211.00 | 09-JAN-07:10 | 11858.70 | 04-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 63.69 | 1211.00 | 09-JAN-07:10 | 11858.70 | 04-JAN-13:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 446.65 | 0.00 | 01-JAN-00:40 | 231351.00 | 06-FEB-08:10 |
NaturalGas:HVAC | 446.65 | 0.00 | 01-JAN-00:40 | 231351.00 | 06-FEB-08:10 |
Heating:NaturalGas | 446.65 | 0.00 | 01-JAN-00:40 | 231351.00 | 06-FEB-08:10 |
General:Heating:NaturalGas | 446.65 | 0.00 | 01-JAN-00:40 | 231351.00 | 06-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1375.86 | 0.00 | 01-JAN-00:40 | 348377.39 | 06-FEB-08:10 |
EnergyTransfer:Building | 519.18 | 0.00 | 01-JAN-00:40 | 163296.58 | 06-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 106.19 | 0.00 | 01-JAN-00:10 | 31131.86 | 06-FEB-08:10 |
Heating:EnergyTransfer | 103.97 | 0.00 | 01-JAN-00:40 | 163296.58 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 15.21 | 0.00 | 01-JAN-00:10 | 31131.86 | 06-FEB-08:10 |
General:Heating:EnergyTransfer | 103.97 | 0.00 | 01-JAN-00:40 | 163296.58 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 15.21 | 0.00 | 01-JAN-00:10 | 31131.86 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 415.22 | 0.00 | 01-JAN-00:10 | 94944.22 | 18-AUG-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 90.98 | 0.00 | 01-JAN-00:10 | 15891.24 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer | 415.22 | 0.00 | 01-JAN-00:10 | 94944.22 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 90.98 | 0.00 | 01-JAN-00:10 | 15891.24 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 55.05 | 0.00 | 01-JAN-00:10 | 11287.61 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.99 | 0.00 | 01-JAN-00:10 | 11287.61 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 3.99 | 0.00 | 01-JAN-00:10 | 11287.61 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 51.07 | 0.00 | 01-JAN-00:10 | 9373.38 | 22-AUG-22:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 51.07 | 0.00 | 01-JAN-00:10 | 9373.38 | 22-AUG-22:40 |
EnergyTransfer:Zone:SMSTORE2 | 43.39 | 0.00 | 01-JAN-00:10 | 13959.53 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.68 | 0.00 | 01-JAN-00:10 | 13959.53 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 5.68 | 0.00 | 01-JAN-00:10 | 13959.53 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 37.70 | 0.00 | 01-JAN-00:10 | 8221.24 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 37.70 | 0.00 | 01-JAN-00:10 | 8221.24 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 43.19 | 0.00 | 01-JAN-00:10 | 15532.84 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 6.36 | 0.00 | 01-JAN-00:10 | 15532.84 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 6.36 | 0.00 | 01-JAN-00:10 | 15532.84 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 36.83 | 0.00 | 01-JAN-00:10 | 8242.07 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 36.83 | 0.00 | 01-JAN-00:10 | 8242.07 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 42.25 | 0.00 | 01-JAN-00:10 | 16387.68 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 7.47 | 0.00 | 01-JAN-00:10 | 16387.68 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 7.47 | 0.00 | 01-JAN-00:10 | 16387.68 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 34.78 | 0.00 | 01-JAN-00:10 | 8108.20 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 34.78 | 0.00 | 01-JAN-00:10 | 8108.20 | 18-AUG-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 71.57 | 0.00 | 01-JAN-00:10 | 32662.57 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 15.50 | 0.00 | 01-JAN-00:10 | 32662.57 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 15.50 | 0.00 | 01-JAN-00:10 | 32662.57 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 56.07 | 0.00 | 01-JAN-00:10 | 14696.53 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 56.07 | 0.00 | 01-JAN-00:10 | 14696.53 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 37.33 | 0.00 | 01-JAN-00:10 | 16951.11 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 9.08 | 0.00 | 01-JAN-00:10 | 16951.11 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 9.08 | 0.00 | 01-JAN-00:10 | 16951.11 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 28.26 | 0.00 | 01-JAN-00:10 | 7637.51 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 28.26 | 0.00 | 01-JAN-00:10 | 7637.51 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE6 | 37.12 | 0.00 | 01-JAN-00:10 | 17623.37 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 9.46 | 0.00 | 01-JAN-00:10 | 17623.37 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 9.46 | 0.00 | 01-JAN-00:10 | 17623.37 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 27.66 | 0.00 | 01-JAN-00:10 | 7586.19 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 27.66 | 0.00 | 01-JAN-00:10 | 7586.19 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE7 | 37.43 | 0.00 | 01-JAN-00:10 | 16710.35 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 11.19 | 0.00 | 01-JAN-00:10 | 16710.35 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 11.19 | 0.00 | 01-JAN-00:10 | 16710.35 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 26.24 | 0.00 | 01-JAN-00:10 | 7577.74 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 26.24 | 0.00 | 01-JAN-00:10 | 7577.74 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 45.65 | 0.00 | 01-JAN-00:40 | 19697.59 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 20.03 | 0.00 | 01-JAN-00:40 | 19697.59 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 20.03 | 0.00 | 01-JAN-00:40 | 19697.59 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 25.62 | 0.00 | 01-JAN-00:10 | 8499.67 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 25.62 | 0.00 | 01-JAN-00:10 | 8499.67 | 18-AUG-13:00 |
EnergyTransfer:HVAC | 856.68 | 0.00 | 01-JAN-00:40 | 208412.06 | 08-JUL-12:20 |
HeatingCoils:EnergyTransfer | 357.32 | 0.00 | 01-JAN-00:40 | 185080.80 | 06-FEB-08:10 |
CoolingCoils:EnergyTransfer | 499.36 | 0.00 | 01-JAN-00:10 | 208412.06 | 08-JUL-12:20 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 15.210 | -90.983 | 0.000 | 0.000 | 25.135 | 95.826 | 26.249 | 22.403 | 0.000 | 2.348 | 0.006 | 0.000 | -8.878 | 0.000 | -34.270 | -53.041 |
SMSTORE1 | 0.000 | 0.000 | 3.986 | -51.066 | 0.000 | 0.000 | 12.386 | 57.583 | 13.125 | 11.114 | 0.000 | 1.258 | 0.000 | 0.000 | -4.681 | 0.000 | -16.533 | -27.172 |
SMSTORE2 | 0.000 | 0.000 | 5.682 | -37.704 | 0.000 | 0.000 | 7.534 | 40.956 | 10.421 | 11.100 | 0.000 | 1.241 | 0.000 | 0.000 | -4.625 | 0.000 | -17.104 | -17.499 |
SMSTORE3 | 0.000 | 0.000 | 6.361 | -36.833 | 0.000 | 0.000 | 7.542 | 40.956 | 10.421 | 11.112 | 0.000 | 1.240 | 0.000 | 0.000 | -4.574 | 0.000 | -17.035 | -19.190 |
SMSTORE4 | 0.000 | 0.000 | 7.469 | -34.784 | 0.000 | 0.000 | 7.554 | 40.956 | 10.421 | 11.134 | 0.000 | 1.241 | 0.001 | 0.000 | -4.517 | 0.000 | -16.945 | -22.528 |
LGSTORE2 | 0.000 | 0.000 | 15.500 | -56.068 | 0.000 | 0.000 | 25.976 | 43.277 | 19.173 | 22.368 | 0.000 | 2.242 | 0.010 | 0.000 | -8.737 | 0.000 | -31.170 | -32.560 |
SMSTORE5 | 0.000 | 0.000 | 9.077 | -28.257 | 0.000 | 0.000 | 12.994 | 22.197 | 9.586 | 11.171 | 0.000 | 1.245 | 0.005 | 0.000 | -4.365 | 0.000 | -16.923 | -16.726 |
SMSTORE6 | 0.000 | 0.000 | 9.464 | -27.655 | 0.000 | 0.000 | 13.003 | 22.197 | 9.586 | 11.182 | 0.000 | 1.245 | 0.004 | 0.000 | -4.343 | 0.000 | -16.888 | -17.791 |
SMSTORE7 | 0.000 | 0.000 | 11.190 | -26.241 | 0.000 | 0.000 | 13.023 | 22.197 | 9.586 | 11.209 | 0.000 | 1.246 | 0.001 | 0.000 | -4.271 | 0.000 | -16.781 | -21.159 |
SMSTORE8 | 0.000 | 0.000 | 20.027 | -25.624 | 0.000 | 0.000 | 13.056 | 22.197 | 9.586 | 11.278 | 0.000 | 1.328 | 0.001 | 0.000 | -3.998 | 0.000 | -21.647 | -26.204 |
Total Facility | 0.000 | 0.000 | 103.967 | -415.215 | 0.000 | 0.000 | 138.203 | 408.342 | 128.154 | 134.072 | 0.000 | 14.634 | 0.029 | 0.000 | -52.989 | 0.000 | -205.297 | -253.871 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -37709.54 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 404.12 | 0.00 | 0.00 | 37315.24 | 0.00 | -0.00 | 0.00 | -158.46 | 0.00 |
SMSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -20273.77 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 199.92 | 0.00 | 0.00 | 20077.83 | 0.00 | -0.00 | 0.00 | -78.30 | 0.00 |
SMSTORE2 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -22986.49 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23011.36 | 0.00 | -76.50 | 0.00 | -22.69 | 0.00 |
SMSTORE3 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23112.72 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23138.52 | 0.00 | -77.29 | 0.00 | -22.83 | 0.00 |
SMSTORE4 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -21713.68 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21737.42 | 0.00 | -75.40 | 0.00 | -22.66 | 0.00 |
LGSTORE2 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -35957.02 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 403.29 | 0.00 | 0.00 | 35547.64 | 0.00 | -0.00 | 0.00 | -142.55 | 0.00 |
SMSTORE5 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18542.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 203.06 | 0.00 | 0.00 | 18339.82 | 0.00 | -0.00 | 0.00 | -75.20 | 0.00 |
SMSTORE6 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18429.82 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 203.74 | 0.00 | 0.00 | 18226.15 | 0.00 | -0.00 | 0.00 | -74.39 | 0.00 |
SMSTORE7 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18264.57 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 204.66 | 0.00 | 0.00 | 18057.93 | 0.00 | -0.00 | 0.00 | -72.33 | 0.00 |
SMSTORE8 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19462.21 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 206.69 | 0.00 | 0.00 | 19264.78 | 0.00 | -0.00 | 0.00 | -83.58 | 0.00 |
Total Facility | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -176597.28 | 0.00 | 0.00 | 295.52 | 450.00 | 1450.75 | 2462.69 | 0.00 | 0.00 | 172793.20 | 0.00 | 0.00 | 0.00 | -854.87 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 61641.71 | 0.00 | 0.00 | 0.00 | 278.47 | 75.00 | 74.62 | 580.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1553.95 | -61095.98 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 32170.80 | 0.00 | 0.00 | 0.00 | 133.81 | 37.50 | 37.31 | 267.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -814.87 | -31831.88 |
SMSTORE2 | 08-JAN-08:61 | 0.00 | 0.00 | 32612.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -361.29 | 0.00 | -614.45 | -31711.98 |
SMSTORE3 | 08-JAN-08:61 | 0.00 | 0.00 | 32467.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -356.14 | 0.00 | -607.42 | -31578.71 |
SMSTORE4 | 08-JAN-08:61 | 0.00 | 0.00 | 32464.03 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.35 | 0.00 | -600.47 | -31587.02 |
LGSTORE2 | 02-JAN-08:12 | 0.00 | 0.00 | 59457.36 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 859.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1593.05 | -58872.52 |
SMSTORE5 | 02-JAN-08:12 | 0.00 | 0.00 | 30695.86 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 428.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -876.44 | -30322.17 |
SMSTORE6 | 02-JAN-08:12 | 0.00 | 0.00 | 30601.49 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 429.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -870.70 | -30234.35 |
SMSTORE7 | 02-JAN-08:12 | 0.00 | 0.00 | 30522.75 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 430.19 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -874.82 | -30152.44 |
SMSTORE8 | 02-JAN-08:12 | 0.00 | 0.00 | 32607.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 439.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1028.75 | -32092.68 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 296902.00 | 0.00 | 0.00 | 0.00 | 759.10 | 450.00 | 1452.23 | 3478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9551.74 | -293490.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0022 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0022 | 0.2055 | 1.0000 | Not calculated | 0.4115 | 0.2055 | ||
PSZ-AC_2:2 | 1.0605 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0720 | 0.1919 | 1.0000 | Not calculated | 0.2057 | 0.1919 | ||
PSZ-AC_3:3 | 1.0805 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0805 | 0.1904 | 1.0000 | Not calculated | 0.2057 | 0.1904 | ||
PSZ-AC_4:4 | 1.0739 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0803 | 0.1904 | 1.0000 | Not calculated | 0.2057 | 0.1904 | ||
PSZ-AC_5:5 | 1.0737 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0737 | 0.1916 | 1.0000 | Not calculated | 0.2057 | 0.1916 | ||
PSZ-AC_6:6 | 1.8929 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8929 | 0.2174 | 1.0000 | Not calculated | 0.4115 | 0.2174 | ||
PSZ-AC_7:7 | 0.9848 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9848 | 0.2089 | 1.0000 | Not calculated | 0.2057 | 0.2089 | ||
PSZ-AC_8:8 | 0.9798 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9798 | 0.2100 | 1.0000 | Not calculated | 0.2057 | 0.2100 | ||
PSZ-AC_9:9 | 0.9761 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9765 | 0.2107 | 1.0000 | Not calculated | 0.2057 | 0.2107 | ||
PSZ-AC_10:10 | 1.0651 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0713 | 0.1920 | 1.0000 | Not calculated | 0.2057 | 0.1920 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0022 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0022 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2055 | ||
PSZ-AC_2:2 | 1.0605 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0605 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1940 | ||
PSZ-AC_3:3 | 1.0805 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0805 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1904 | ||
PSZ-AC_4:4 | 1.0739 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0739 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1916 | ||
PSZ-AC_5:5 | 1.0737 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0737 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1916 | ||
PSZ-AC_6:6 | 1.8929 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8929 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2174 | ||
PSZ-AC_7:7 | 0.9848 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9848 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2089 | ||
PSZ-AC_8:8 | 0.9798 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9798 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2100 | ||
PSZ-AC_9:9 | 0.9761 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9761 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2108 | ||
PSZ-AC_10:10 | 1.0651 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0651 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1932 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0022 | 2.0022 | 2.0022 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0605 | 1.0605 | 1.0605 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0805 | 1.0805 | 1.0805 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0739 | 1.0739 | 1.0739 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0737 | 1.0737 | 1.0737 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8929 | 1.8929 | 1.8929 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9848 | 0.9848 | 0.9848 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9798 | 0.9798 | 0.9798 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9761 | 0.9761 | 0.9761 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0651 | 1.0651 | 1.0651 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0022 | 2.0022 | 2.0022 | 2.0022 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0605 | 1.0720 | 1.0605 | 1.0605 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0805 | 1.0805 | 1.0805 | 1.0805 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0739 | 1.0803 | 1.0739 | 1.0739 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0737 | 1.0737 | 1.0737 | 1.0737 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8929 | 1.8929 | 1.8929 | 1.8929 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9848 | 0.9848 | 0.9848 | 0.9848 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9798 | 0.9798 | 0.9798 | 0.9798 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9761 | 0.9765 | 0.9761 | 0.9761 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0651 | 1.0713 | 1.0651 | 1.0651 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0022 | 2.0022 | 2.0022 | No | 0.4115 | 0.3114 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0605 | 1.0605 | 1.0605 | No | 0.2057 | 0.3373 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0805 | 1.0805 | 1.0805 | No | 0.2057 | 0.3331 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0739 | 1.0739 | 1.0739 | No | 0.2057 | 0.3306 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0737 | 1.0737 | 1.0737 | No | 0.2057 | 0.3266 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8929 | 1.8929 | 1.8929 | No | 0.4115 | 0.3397 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9848 | 0.9848 | 0.9848 | No | 0.2057 | 0.3183 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9798 | 0.9798 | 0.9798 | No | 0.2057 | 0.3185 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9761 | 0.9761 | 0.9761 | No | 0.2057 | 0.3133 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0651 | 1.0651 | 1.0651 | No | 0.2057 | 0.2485 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0022 | 2.0022 | 2.0022 | 2.0022 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0605 | 1.0605 | 1.0605 | 1.0605 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0805 | 1.0805 | 1.0805 | 1.0805 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0739 | 1.0739 | 1.0739 | 1.0739 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0737 | 1.0737 | 1.0737 | 1.0737 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8929 | 1.8929 | 1.8929 | 1.8929 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9848 | 0.9848 | 0.9848 | 0.9848 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9798 | 0.9798 | 0.9798 | 0.9798 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9761 | 0.9761 | 0.9761 | 0.9761 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0651 | 1.0651 | 1.0651 | 1.0651 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 2.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 2.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 446.65 | 231351.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 122.12 | 49566.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.37 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 100.69 | 9320.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.69 | 11858.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 883.38 |
Natural Gas | 0.00 | 446.65 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1330.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 58.42 |
Fans (All) | 48.17 |
Service Water Heating | 30.47 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 422.60 |
Subtotal | 422.60 |
Natural Gas [MJ/m2] | |
Space Heating | 213.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 213.67 |
Subtotal | 213.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.70 |
Space Heating | 33.58 |
Space Cooling | 9.18 |
Fans (All) | 7.57 |
Service Water Heating | 4.79 |
Receptacle Equipment | 9.64 |
Miscellaneous | 4.54 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8658.00 | 102.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8644.00 | 116.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
Min | 8644.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 116.00 | 0.00 | 0.00 | 0.00 |
Average | 8717.55 | 42.45 | 0.00 | 0.00 | 0.00 |
Sum | 87175.50 | 424.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25463.50 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25463.50 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25464.00 | 11.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45901.50 | 10.50 | 0.00 | 0.00 | 0.00 |
Min | 25463.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 48600.80 | 9.40 | 0.00 | 0.00 | 0.00 |
Sum | 486008.00 | 94.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7777.17 | 982.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8374.67 | 385.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7383.83 | 1376.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7391.50 | 1368.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7390.50 | 1369.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7294.83 | 1465.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7301.83 | 1458.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7300.00 | 1460.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7313.50 | 1446.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7332.17 | 1427.83 | 0.00 | 0.00 | 0.00 |
Min | 7294.83 | 385.33 | 0.00 | 0.00 | 0.00 |
Max | 8374.67 | 1465.17 | 0.00 | 0.00 | 0.00 |
Average | 7486.00 | 1274.00 | 0.00 | 0.00 | 0.00 |
Sum | 74860.00 | 12740.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 84002.33 | 5038.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42039.50 | 1737.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 23933.17 | 1541.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 23929.17 | 1545.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 23808.83 | 1666.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 83894.50 | 9316.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 41169.17 | 4742.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 41078.83 | 4833.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 40922.83 | 4989.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 40832.50 | 5079.50 | 0.00 | 0.00 | 0.00 |
Min | 23808.83 | 1541.83 | 0.00 | 0.00 | 0.00 |
Max | 84002.33 | 9316.50 | 0.00 | 0.00 | 0.00 |
Average | 44561.08 | 4049.12 | 0.00 | 0.00 | 0.00 |
Sum | 445610.83 | 40491.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105231E+10 | 12158.35 | 11-JAN-20:12 | -6.1 | -8.9 | 0.106526E+10 | 1275.40 | 01-JAN-18:00 | -6.1 | -8.9 |
February | 0.976970E+09 | 11325.65 | 03-FEB-00:02 | -4.5 | -7.3 | 0.961555E+09 | 1275.40 | 05-FEB-18:00 | -8.9 | -11.0 |
March | 0.302202E+10 | 9946.54 | 17-MAR-23:03 | -1.7 | -1.9 | 0.107454E+10 | 1457.17 | 03-MAR-13:00 | -1.7 | -1.9 |
April | 0.482053E+10 | 7867.66 | 08-APR-13:00 | 22.80 | 16.08 | 0.115377E+10 | 1685.98 | 08-APR-12:30 | 22.80 | 16.08 |
May | 0.779853E+10 | 12552.41 | 30-MAY-07:03 | 23.17 | 16.07 | 0.135532E+10 | 1685.98 | 28-MAY-16:00 | 23.17 | 16.07 |
June | 0.123405E+11 | 32657.75 | 26-JUN-07:02 | 23.40 | 18.26 | 0.135448E+10 | 1686.01 | 18-JUN-17:30 | 23.40 | 18.26 |
July | 0.159590E+11 | 36677.09 | 11-JUL-07:02 | 22.30 | 16.06 | 0.141284E+10 | 1686.03 | 30-JUL-12:00 | 27.20 | 24.02 |
August | 0.169879E+11 | 35681.55 | 19-AUG-07:02 | 21.28 | 16.54 | 0.139410E+10 | 1686.03 | 18-AUG-12:00 | 21.28 | 16.54 |
September | 0.123971E+11 | 37714.01 | 02-SEP-07:02 | 21.70 | 16.23 | 0.136453E+10 | 1686.02 | 04-SEP-17:00 | 23.90 | 19.12 |
October | 0.968044E+10 | 14576.82 | 06-OCT-07:03 | 20.00 | 18.15 | 0.134977E+10 | 1685.95 | 15-OCT-12:20 | 20.20 | 13.39 |
November | 0.409915E+10 | 10764.66 | 24-NOV-00:02 | -3.3 | -5.8 | 0.108455E+10 | 1685.85 | 04-NOV-12:20 | -3.3 | -5.8 |
December | 0.184906E+10 | 10689.42 | 22-DEC-00:03 | -3.3 | -6.0 | 0.107086E+10 | 1306.79 | 17-DEC-13:00 | -3.3 | -6.0 |
Annual Sum or Average | 0.909836E+11 | 0.146416E+11 | ||||||||
Minimum of Months | 0.976970E+09 | 7867.66 | -6.1 | -8.9 | 0.961555E+09 | 1275.40 | -8.9 | -11.0 | ||
Maximum of Months | 0.169879E+11 | 37714.01 | 23.40 | 18.26 | 0.141284E+10 | 1686.03 | 27.20 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646468E+09 | 5297.94 | 10-JAN-10:43 | -3.3 | -5.4 | 0.548787E+09 | 767.33 | 29-JAN-18:00 | 0.00 | -2.5 |
February | 0.621139E+09 | 5770.42 | 05-FEB-10:42 | -5.1 | -7.7 | 0.496608E+09 | 783.84 | 19-FEB-18:00 | 3.30 | 0.63 |
March | 0.166152E+10 | 3949.17 | 22-MAR-14:53 | 2.20 | -3.4 | 0.567993E+09 | 842.90 | 26-MAR-17:00 | 10.00 | 9.08 |
April | 0.274590E+10 | 15501.63 | 16-APR-17:52 | 20.60 | 12.37 | 0.606156E+09 | 842.97 | 08-APR-12:00 | 20.60 | 12.37 |
May | 0.468704E+10 | 17089.11 | 27-MAY-22:43 | 18.40 | 10.63 | 0.691970E+09 | 842.97 | 29-MAY-16:49 | 23.17 | 17.15 |
June | 0.708427E+10 | 18399.50 | 26-JUN-07:02 | 23.40 | 18.26 | 0.676486E+09 | 842.98 | 18-JUN-16:10 | 23.40 | 18.26 |
July | 0.878766E+10 | 19863.41 | 11-JUL-07:02 | 22.30 | 16.06 | 0.706424E+09 | 843.00 | 30-JUL-12:50 | 27.02 | 23.90 |
August | 0.921243E+10 | 19356.02 | 19-AUG-07:02 | 21.28 | 16.54 | 0.696660E+09 | 843.02 | 27-AUG-17:19 | 25.60 | 22.81 |
September | 0.703770E+10 | 20274.98 | 02-SEP-07:02 | 21.70 | 16.23 | 0.681214E+09 | 842.98 | 08-SEP-12:09 | 24.90 | 19.74 |
October | 0.535099E+10 | 17971.22 | 25-OCT-20:54 | 17.20 | 7.68 | 0.692365E+09 | 842.95 | 20-OCT-12:00 | 17.20 | 7.68 |
November | 0.216151E+10 | 3652.51 | 04-NOV-13:00 | 17.80 | 12.74 | 0.578085E+09 | 842.91 | 04-NOV-12:00 | 17.80 | 12.74 |
December | 0.106973E+10 | 4217.78 | 09-DEC-09:32 | 1.33 | -0.5 | 0.559347E+09 | 824.63 | 17-DEC-18:00 | 7.80 | 3.53 |
Annual Sum or Average | 0.510664E+11 | 0.750210E+10 | ||||||||
Minimum of Months | 0.621139E+09 | 3652.51 | -5.1 | -7.7 | 0.496608E+09 | 767.33 | 0.00 | -2.5 | ||
Maximum of Months | 0.921243E+10 | 20274.98 | 23.40 | 18.26 | 0.706424E+09 | 843.02 | 27.02 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370184E+09 | 6002.53 | 11-JAN-19:32 | -6.1 | -8.9 | 0.317181E+09 | 637.68 | 14-JAN-13:09 | -6.7 | -7.4 |
February | 0.363711E+09 | 5433.26 | 13-FEB-19:23 | -3.9 | -6.6 | 0.288093E+09 | 637.68 | 04-FEB-13:09 | -3.9 | -6.6 |
March | 0.126360E+10 | 4030.61 | 29-MAR-07:01 | 3.07 | 1.14 | 0.333732E+09 | 702.44 | 27-MAR-16:40 | 3.07 | 1.14 |
April | 0.206209E+10 | 4614.47 | 08-APR-12:30 | 23.60 | 16.18 | 0.350084E+09 | 842.97 | 08-APR-12:00 | 22.80 | 16.08 |
May | 0.331649E+10 | 8914.80 | 30-MAY-06:03 | 20.47 | 15.45 | 0.416132E+09 | 842.93 | 27-MAY-12:30 | 20.47 | 15.45 |
June | 0.525307E+10 | 17851.70 | 23-JUN-06:03 | 21.38 | 17.00 | 0.416556E+09 | 842.95 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.653676E+10 | 20060.21 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419999E+09 | 842.98 | 22-JUL-12:00 | 26.70 | 23.40 |
August | 0.708309E+10 | 22989.57 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431709E+09 | 842.97 | 05-AUG-12:00 | 17.88 | 13.11 |
September | 0.511959E+10 | 20391.46 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410219E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.398879E+10 | 10727.93 | 06-OCT-06:03 | 19.50 | 17.97 | 0.407072E+09 | 842.96 | 14-OCT-12:20 | 18.67 | 16.24 |
November | 0.166398E+10 | 3563.28 | 18-NOV-08:23 | 3.85 | 2.44 | 0.328257E+09 | 842.90 | 04-NOV-12:00 | 3.85 | 2.44 |
December | 0.683501E+09 | 4043.20 | 06-DEC-09:53 | 1.70 | -1.1 | 0.316977E+09 | 637.68 | 02-DEC-13:39 | 1.70 | -1.1 |
Annual Sum or Average | 0.377049E+11 | 0.443601E+10 | ||||||||
Minimum of Months | 0.363711E+09 | 3563.28 | -6.1 | -8.9 | 0.288093E+09 | 637.68 | -6.7 | -7.4 | ||
Maximum of Months | 0.708309E+10 | 22989.57 | 23.60 | 17.97 | 0.431709E+09 | 842.98 | 27.80 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295667E+09 | 2149.36 | 19-JAN-18:10 | 6.60 | 1.81 | 0.317182E+09 | 637.68 | 14-JAN-13:09 | 6.60 | 1.81 |
February | 0.304025E+09 | 5747.57 | 03-FEB-09:52 | -5.0 | -7.6 | 0.288104E+09 | 637.68 | 04-FEB-13:20 | 2.60 | 1.96 |
March | 0.113398E+10 | 4788.67 | 18-MAR-08:23 | -1.1 | -1.6 | 0.332803E+09 | 702.43 | 27-MAR-16:30 | 21.65 | 15.87 |
April | 0.191766E+10 | 4472.17 | 08-APR-12:30 | 23.60 | 16.18 | 0.348676E+09 | 842.97 | 08-APR-12:00 | 22.80 | 16.08 |
May | 0.321041E+10 | 8580.44 | 30-MAY-06:03 | 20.47 | 15.45 | 0.414347E+09 | 842.92 | 27-MAY-12:30 | 20.47 | 15.45 |
June | 0.522769E+10 | 18062.27 | 23-JUN-06:03 | 21.38 | 17.00 | 0.416548E+09 | 842.95 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.654042E+10 | 20095.92 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419995E+09 | 842.99 | 22-JUL-12:00 | 26.70 | 23.40 |
August | 0.709974E+10 | 23115.81 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431707E+09 | 842.98 | 05-AUG-12:00 | 17.88 | 13.11 |
September | 0.509568E+10 | 20412.90 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410193E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.389822E+10 | 10605.63 | 06-OCT-06:03 | 19.50 | 17.97 | 0.405813E+09 | 842.96 | 21-OCT-12:20 | 19.07 | 15.73 |
November | 0.152137E+10 | 3518.92 | 18-NOV-08:33 | 4.03 | 2.54 | 0.326042E+09 | 842.89 | 04-NOV-12:20 | 4.03 | 2.54 |
December | 0.588339E+09 | 3726.60 | 23-DEC-09:33 | 3.13 | 2.49 | 0.316896E+09 | 637.68 | 16-DEC-13:09 | 3.13 | 2.49 |
Annual Sum or Average | 0.368332E+11 | 0.442831E+10 | ||||||||
Minimum of Months | 0.295667E+09 | 2149.36 | -5.0 | -7.6 | 0.288104E+09 | 637.68 | 2.60 | 1.81 | ||
Maximum of Months | 0.709974E+10 | 23115.81 | 23.60 | 17.97 | 0.431707E+09 | 842.99 | 27.80 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218571E+09 | 5311.81 | 31-JAN-20:23 | -3.3 | -6.1 | 0.317180E+09 | 637.68 | 07-JAN-13:30 | -3.3 | -6.1 |
February | 0.216889E+09 | 5551.51 | 07-FEB-18:03 | -4.4 | -6.9 | 0.288103E+09 | 637.68 | 11-FEB-13:00 | 6.10 | 2.34 |
March | 0.949102E+09 | 3388.02 | 29-MAR-17:20 | 5.73 | 4.14 | 0.331593E+09 | 702.42 | 27-MAR-16:30 | 5.73 | 4.14 |
April | 0.170590E+10 | 4178.06 | 08-APR-12:50 | 23.07 | 16.12 | 0.346460E+09 | 842.97 | 08-APR-12:50 | 23.07 | 16.12 |
May | 0.298354E+10 | 7238.68 | 31-MAY-06:03 | 18.35 | 16.38 | 0.411111E+09 | 842.92 | 27-MAY-12:39 | 18.35 | 16.38 |
June | 0.502843E+10 | 16607.99 | 26-JUN-06:02 | 21.97 | 17.81 | 0.416504E+09 | 842.94 | 24-JUN-12:00 | 21.97 | 17.81 |
July | 0.636334E+10 | 19880.84 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419962E+09 | 842.98 | 29-JUL-12:50 | 25.73 | 20.27 |
August | 0.691660E+10 | 21716.46 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431673E+09 | 843.00 | 12-AUG-12:09 | 17.88 | 13.11 |
September | 0.490365E+10 | 20180.49 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410092E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.370305E+10 | 9437.00 | 06-OCT-06:03 | 19.50 | 17.97 | 0.403640E+09 | 842.96 | 21-OCT-12:30 | 19.15 | 15.87 |
November | 0.134068E+10 | 3244.02 | 01-NOV-07:01 | 6.38 | 4.03 | 0.322975E+09 | 842.90 | 04-NOV-12:20 | 17.80 | 12.57 |
December | 0.454685E+09 | 4127.24 | 28-DEC-09:23 | 1.40 | -1.1 | 0.316824E+09 | 637.68 | 02-DEC-13:09 | 1.40 | -1.1 |
Annual Sum or Average | 0.347844E+11 | 0.441612E+10 | ||||||||
Minimum of Months | 0.216889E+09 | 3244.02 | -4.4 | -6.9 | 0.288103E+09 | 637.68 | -3.3 | -6.1 | ||
Maximum of Months | 0.691660E+10 | 21716.46 | 23.07 | 17.97 | 0.431673E+09 | 843.00 | 25.73 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143033E+09 | 8098.56 | 17-JAN-19:53 | 2.20 | 1.02 | 0.108441E+10 | 1700.53 | 07-JAN-15:00 | 2.20 | 1.02 |
February | 0.140147E+09 | 10561.32 | 03-FEB-18:42 | -2.8 | -5.0 | 0.987309E+09 | 1700.53 | 11-FEB-15:30 | 5.55 | 2.27 |
March | 0.121069E+10 | 5995.28 | 10-MAR-13:53 | 6.70 | 2.97 | 0.113167E+10 | 1994.90 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.251860E+10 | 6691.31 | 12-APR-08:63 | 5.78 | 0.39 | 0.117632E+10 | 2247.80 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.471557E+10 | 14124.57 | 30-MAY-07:03 | 23.17 | 16.07 | 0.138662E+10 | 2247.83 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.833012E+10 | 29791.60 | 23-JUN-07:03 | 23.45 | 17.63 | 0.142884E+10 | 2247.93 | 03-JUN-14:00 | 23.45 | 17.63 |
July | 0.108014E+11 | 35147.93 | 11-JUL-07:02 | 22.30 | 16.06 | 0.143779E+10 | 2248.01 | 22-JUL-14:00 | 26.70 | 23.40 |
August | 0.118484E+11 | 33918.12 | 19-AUG-07:02 | 21.28 | 16.54 | 0.147980E+10 | 2248.00 | 05-AUG-14:00 | 21.28 | 16.54 |
September | 0.809242E+10 | 35961.21 | 02-SEP-07:02 | 21.70 | 16.23 | 0.140778E+10 | 2248.00 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.601355E+10 | 14986.10 | 06-OCT-07:03 | 20.00 | 18.15 | 0.136672E+10 | 2247.95 | 14-OCT-14:20 | 18.30 | 16.20 |
November | 0.188766E+10 | 5176.14 | 15-NOV-15:15 | 8.13 | 3.74 | 0.108516E+10 | 2247.77 | 04-NOV-14:20 | 8.13 | 3.74 |
December | 0.366758E+09 | 9758.23 | 21-DEC-20:53 | -1.1 | -4.4 | 0.108625E+10 | 1700.53 | 30-DEC-15:20 | 1.50 | 0.56 |
Annual Sum or Average | 0.560684E+11 | 0.150587E+11 | ||||||||
Minimum of Months | 0.140147E+09 | 5176.14 | -2.8 | -5.0 | 0.987309E+09 | 1700.53 | 1.50 | 0.39 | ||
Maximum of Months | 0.118484E+11 | 35961.21 | 23.45 | 18.15 | 0.147980E+10 | 2248.01 | 26.70 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62984553.08 | 5121.04 | 31-JAN-18:03 | -2.3 | -6.3 | 0.542192E+09 | 850.24 | 07-JAN-15:09 | -2.3 | -6.3 |
February | 55330057.85 | 3864.18 | 10-FEB-18:53 | 2.80 | 0.51 | 0.493638E+09 | 850.24 | 04-FEB-15:09 | 2.80 | 0.51 |
March | 0.564723E+09 | 4850.11 | 17-MAR-18:12 | -1.1 | -1.9 | 0.565429E+09 | 997.42 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.118663E+10 | 3300.54 | 08-APR-12:30 | 23.60 | 16.18 | 0.586562E+09 | 1123.87 | 08-APR-14:09 | 20.78 | 15.22 |
May | 0.230416E+10 | 6464.89 | 30-MAY-07:03 | 23.17 | 16.07 | 0.690757E+09 | 1123.88 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.424757E+10 | 15096.76 | 26-JUN-07:02 | 23.40 | 18.26 | 0.714391E+09 | 1123.93 | 03-JUN-14:00 | 23.40 | 18.26 |
July | 0.556425E+10 | 18124.54 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718861E+09 | 1123.97 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.610051E+10 | 17480.85 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739864E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.412501E+10 | 18544.18 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703851E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.299081E+10 | 6920.55 | 06-OCT-07:03 | 20.00 | 18.15 | 0.682378E+09 | 1123.94 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.892490E+09 | 2932.59 | 18-NOV-15:15 | 6.50 | 3.17 | 0.541438E+09 | 1123.85 | 04-NOV-14:20 | 6.50 | 3.17 |
December | 0.162919E+09 | 4266.62 | 21-DEC-10:32 | 1.33 | -2.2 | 0.543109E+09 | 850.24 | 02-DEC-15:50 | 1.33 | -2.2 |
Annual Sum or Average | 0.282574E+11 | 0.752247E+10 | ||||||||
Minimum of Months | 55330057.85 | 2932.59 | -2.3 | -6.3 | 0.493638E+09 | 850.24 | -2.3 | -6.3 | ||
Maximum of Months | 0.610051E+10 | 18544.18 | 23.60 | 18.26 | 0.739864E+09 | 1123.97 | 25.60 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60867464.18 | 5637.89 | 31-JAN-11:32 | -4.5 | -7.9 | 0.542189E+09 | 850.24 | 07-JAN-15:09 | -4.5 | -7.9 |
February | 45997772.47 | 3254.14 | 02-FEB-10:33 | 5.40 | 0.82 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | 1.40 | 0.88 |
March | 0.526759E+09 | 3504.87 | 14-MAR-19:23 | 4.40 | 3.79 | 0.564951E+09 | 997.43 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.113112E+10 | 3257.24 | 12-APR-08:63 | 5.78 | 0.39 | 0.584824E+09 | 1123.87 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.221096E+10 | 5936.68 | 30-MAY-13:00 | 30.00 | 18.00 | 0.687689E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.417362E+10 | 14992.90 | 26-JUN-07:02 | 23.40 | 18.26 | 0.714375E+09 | 1123.93 | 03-JUN-14:00 | 23.40 | 18.26 |
July | 0.549894E+10 | 18014.95 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718853E+09 | 1123.97 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.603564E+10 | 17374.61 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739858E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.406073E+10 | 18432.00 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703759E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.291481E+10 | 6461.68 | 06-OCT-07:03 | 20.00 | 18.15 | 0.680517E+09 | 1123.94 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.848856E+09 | 4583.98 | 22-NOV-18:53 | 0.00 | -2.8 | 0.540047E+09 | 1123.08 | 04-NOV-14:00 | 0.00 | -2.8 |
December | 0.147335E+09 | 4757.26 | 21-DEC-20:33 | -0.7 | -4.0 | 0.543111E+09 | 850.24 | 02-DEC-15:09 | -0.7 | -4.0 |
Annual Sum or Average | 0.276556E+11 | 0.751382E+10 | ||||||||
Minimum of Months | 45997772.47 | 3254.14 | -4.5 | -7.9 | 0.493640E+09 | 850.24 | -4.5 | -7.9 | ||
Maximum of Months | 0.603564E+10 | 18432.00 | 30.00 | 18.26 | 0.739858E+09 | 1123.97 | 30.00 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30104674.21 | 3795.99 | 26-JAN-18:33 | 3.13 | 0.54 | 0.542193E+09 | 850.24 | 07-JAN-15:39 | 3.13 | 0.54 |
February | 25751405.45 | 3885.52 | 22-FEB-19:03 | 2.70 | -1.1 | 0.493639E+09 | 850.24 | 04-FEB-15:20 | 2.70 | -1.1 |
March | 0.407160E+09 | 4120.61 | 08-MAR-11:43 | 1.78 | 1.74 | 0.563738E+09 | 997.02 | 27-MAR-16:40 | 21.47 | 15.72 |
April | 0.953846E+09 | 3016.58 | 08-APR-13:10 | 22.43 | 15.95 | 0.580801E+09 | 1123.87 | 08-APR-14:20 | 20.97 | 15.19 |
May | 0.199714E+10 | 5779.55 | 30-MAY-13:00 | 30.00 | 18.00 | 0.680371E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.399421E+10 | 14771.39 | 26-JUN-07:02 | 23.40 | 18.26 | 0.714315E+09 | 1123.93 | 03-JUN-14:00 | 23.40 | 18.26 |
July | 0.539226E+10 | 17838.23 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718837E+09 | 1123.97 | 01-JUL-14:50 | 22.30 | 16.06 |
August | 0.595028E+10 | 17210.95 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739849E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.392577E+10 | 18266.76 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703390E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.274118E+10 | 5187.14 | 04-OCT-13:00 | 25.00 | 18.54 | 0.675874E+09 | 1123.93 | 14-OCT-14:00 | 18.30 | 16.20 |
November | 0.733694E+09 | 3808.49 | 25-NOV-11:43 | 3.12 | 1.25 | 0.537299E+09 | 1112.60 | 04-NOV-14:09 | 3.12 | 1.25 |
December | 89363951.27 | 4585.77 | 21-DEC-19:53 | 0.00 | -3.3 | 0.543108E+09 | 850.24 | 02-DEC-15:09 | 0.00 | -3.3 |
Annual Sum or Average | 0.262408E+11 | 0.749341E+10 | ||||||||
Minimum of Months | 25751405.45 | 3016.58 | 0.00 | -3.3 | 0.493639E+09 | 850.24 | 0.00 | -3.3 | ||
Maximum of Months | 0.595028E+10 | 18266.76 | 30.00 | 18.54 | 0.739849E+09 | 1123.97 | 30.00 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 713531.18 | 343.03 | 19-JAN-12:00 | 7.20 | 3.79 | 0.542193E+09 | 850.24 | 14-JAN-15:20 | 7.20 | 3.79 |
February | 381341.17 | 249.81 | 17-FEB-12:00 | 7.20 | 2.04 | 0.493640E+09 | 850.24 | 04-FEB-15:50 | 7.20 | 2.04 |
March | 0.174393E+09 | 3166.15 | 09-MAR-11:13 | 5.60 | 3.26 | 0.562033E+09 | 958.55 | 27-MAR-16:40 | 21.47 | 15.72 |
April | 0.637695E+09 | 3129.86 | 08-APR-12:20 | 23.87 | 16.21 | 0.575722E+09 | 1123.92 | 08-APR-14:09 | 20.78 | 15.22 |
May | 0.171998E+10 | 6130.98 | 30-MAY-13:00 | 30.00 | 18.00 | 0.667288E+09 | 1123.87 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.388862E+10 | 14653.66 | 20-JUN-07:02 | 23.17 | 19.56 | 0.714080E+09 | 1123.96 | 24-JUN-14:00 | 26.10 | 22.54 |
July | 0.571692E+10 | 17033.84 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718866E+09 | 1123.98 | 22-JUL-14:30 | 27.25 | 23.76 |
August | 0.647492E+10 | 16402.80 | 22-AUG-07:02 | 26.20 | 18.45 | 0.739888E+09 | 1123.98 | 26-AUG-14:50 | 25.60 | 19.31 |
September | 0.399170E+10 | 19465.25 | 02-SEP-07:02 | 21.70 | 16.23 | 0.701902E+09 | 1123.98 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.251137E+10 | 5527.00 | 04-OCT-13:00 | 25.00 | 18.54 | 0.667740E+09 | 1123.91 | 21-OCT-14:30 | 19.40 | 17.42 |
November | 0.496135E+09 | 2861.95 | 17-NOV-19:43 | 6.88 | 3.55 | 0.534163E+09 | 1099.67 | 04-NOV-14:09 | 6.88 | 3.55 |
December | 11125357.44 | 3698.89 | 09-DEC-11:03 | 3.30 | 0.87 | 0.543111E+09 | 850.24 | 02-DEC-15:00 | 3.30 | 0.87 |
Annual Sum or Average | 0.256240E+11 | 0.746062E+10 | ||||||||
Minimum of Months | 381341.17 | 249.81 | 3.30 | 0.87 | 0.493640E+09 | 850.24 | 3.30 | 0.87 | ||
Maximum of Months | 0.647492E+10 | 19465.25 | 30.00 | 19.56 | 0.739888E+09 | 1123.98 | 30.00 | 23.76 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473426E+10 | 61641.67 | 02-JAN-08:61 | -11.0 |
February | 0.443104E+10 | 61610.72 | 15-FEB-08:61 | -4.0 |
March | 0.173415E+10 | 61616.13 | 14-MAR-07:01 | -1.4 |
April | 0.552506E+09 | 61593.31 | 03-APR-07:01 | 3.68 |
May | 64885417.03 | 7010.99 | 01-MAY-07:01 | 10.37 |
June | 23158595.26 | 1700.06 | 22-JUN-07:05 | 23.98 |
July | 25449402.40 | 1736.52 | 11-JUL-07:04 | 22.30 |
August | 27881733.22 | 1723.95 | 31-AUG-07:05 | 22.30 |
September | 22667739.60 | 1673.09 | 13-SEP-07:05 | 21.70 |
October | 55053644.79 | 1313.36 | 06-OCT-07:07 | 20.00 |
November | 0.920271E+09 | 61626.90 | 24-NOV-08:61 | -3.5 |
December | 0.261892E+10 | 61619.00 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.152102E+11 | |||
Minimum of Months | 22667739.60 | 1313.36 | -11.0 | |
Maximum of Months | 0.473426E+10 | 61641.67 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138484E+10 | 32170.82 | 02-JAN-08:61 | -11.0 |
February | 0.126260E+10 | 32153.75 | 15-FEB-08:61 | -4.0 |
March | 0.327852E+09 | 32155.01 | 23-MAR-07:01 | -2.9 |
April | 93684142.05 | 32091.46 | 21-APR-07:01 | 6.10 |
May | 21542518.12 | 845.22 | 30-MAY-07:07 | 23.17 |
June | 14553159.53 | 1049.05 | 22-JUN-07:05 | 23.98 |
July | 13811524.11 | 1061.64 | 05-JUL-07:05 | 22.30 |
August | 15214587.79 | 1029.25 | 31-AUG-07:05 | 22.30 |
September | 12785057.40 | 1005.97 | 13-SEP-07:05 | 21.70 |
October | 23305477.47 | 844.76 | 06-OCT-07:07 | 20.00 |
November | 0.193003E+09 | 32154.58 | 24-NOV-08:61 | -3.5 |
December | 0.622548E+09 | 32156.10 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.398573E+10 | |||
Minimum of Months | 12785057.40 | 844.76 | -11.0 | |
Maximum of Months | 0.138484E+10 | 32170.82 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189532E+10 | 32612.90 | 08-JAN-08:61 | -4.3 |
February | 0.163937E+10 | 32596.75 | 26-FEB-08:61 | -6.1 |
March | 0.528319E+09 | 32302.39 | 20-MAR-06:01 | -0.6 |
April | 0.142078E+09 | 32290.31 | 02-APR-07:01 | 4.18 |
May | 23342799.23 | 795.99 | 30-MAY-06:07 | 20.47 |
June | 25758244.30 | 2030.21 | 19-JUN-19:03 | 31.42 |
July | 36050717.71 | 1610.46 | 16-JUL-16:03 | 29.90 |
August | 51684975.06 | 2501.85 | 04-AUG-19:02 | 33.12 |
September | 17144334.76 | 1007.78 | 03-SEP-07:05 | 19.27 |
October | 23100806.73 | 845.70 | 06-OCT-06:07 | 19.50 |
November | 0.344075E+09 | 32465.64 | 23-NOV-08:61 | -2.6 |
December | 0.955812E+09 | 32561.13 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.568205E+10 | |||
Minimum of Months | 17144334.76 | 795.99 | -6.1 | |
Maximum of Months | 0.189532E+10 | 32612.90 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208931E+10 | 32467.46 | 08-JAN-08:61 | -4.3 |
February | 0.179278E+10 | 32451.50 | 26-FEB-08:61 | -6.1 |
March | 0.621499E+09 | 32159.16 | 20-MAR-06:01 | -0.6 |
April | 0.172428E+09 | 32146.52 | 02-APR-07:01 | 4.18 |
May | 25193906.01 | 784.47 | 30-MAY-06:07 | 20.47 |
June | 25713994.37 | 2031.65 | 19-JUN-19:03 | 31.42 |
July | 35935645.99 | 1611.31 | 16-JUL-16:03 | 29.90 |
August | 51517607.86 | 2502.04 | 04-AUG-19:02 | 33.12 |
September | 17256082.81 | 1012.65 | 03-SEP-07:05 | 19.27 |
October | 24529608.80 | 841.07 | 06-OCT-06:07 | 19.50 |
November | 0.409171E+09 | 32320.80 | 23-NOV-08:61 | -2.6 |
December | 0.109532E+10 | 32416.26 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.636066E+10 | |||
Minimum of Months | 17256082.81 | 784.47 | -6.1 | |
Maximum of Months | 0.208931E+10 | 32467.46 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240812E+10 | 32464.03 | 08-JAN-08:61 | -4.3 |
February | 0.205143E+10 | 32448.20 | 26-FEB-08:61 | -6.1 |
March | 0.771181E+09 | 32158.15 | 20-MAR-06:01 | -0.6 |
April | 0.225222E+09 | 32144.81 | 02-APR-07:01 | 4.18 |
May | 29625307.22 | 895.08 | 01-MAY-07:06 | 10.37 |
June | 25139739.88 | 2037.48 | 19-JUN-19:03 | 31.42 |
July | 37266069.42 | 1617.28 | 16-JUL-16:03 | 29.90 |
August | 52363874.20 | 2506.63 | 04-AUG-19:02 | 33.12 |
September | 17100577.99 | 1004.37 | 01-SEP-19:03 | 27.12 |
October | 26723776.51 | 875.87 | 28-OCT-07:10 | 4.27 |
November | 0.511999E+09 | 32318.24 | 23-NOV-08:61 | -2.6 |
December | 0.131311E+10 | 32413.24 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.746927E+10 | |||
Minimum of Months | 17100577.99 | 875.87 | -6.1 | |
Maximum of Months | 0.240812E+10 | 32464.03 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500052E+10 | 59457.37 | 02-JAN-08:12 | -10.9 |
February | 0.423402E+10 | 59204.05 | 13-FEB-08:61 | -8.7 |
March | 0.166337E+10 | 59200.52 | 14-MAR-07:01 | -1.4 |
April | 0.482462E+09 | 59183.66 | 03-APR-07:01 | 3.68 |
May | 66985219.42 | 28340.40 | 01-MAY-07:01 | 10.37 |
June | 28130579.07 | 1658.69 | 23-JUN-07:05 | 23.45 |
July | 46807284.30 | 3255.99 | 16-JUL-16:03 | 29.90 |
August | 43058838.07 | 3285.56 | 13-AUG-16:02 | 29.90 |
September | 27044913.51 | 1668.81 | 03-SEP-08:05 | 21.38 |
October | 55551608.52 | 4329.12 | 29-OCT-08:62 | 6.88 |
November | 0.109914E+10 | 59201.48 | 24-NOV-08:61 | -3.5 |
December | 0.275254E+10 | 59196.66 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.154996E+11 | |||
Minimum of Months | 27044913.51 | 1658.69 | -10.9 | |
Maximum of Months | 0.500052E+10 | 59457.37 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285044E+10 | 30695.86 | 02-JAN-08:12 | -10.9 |
February | 0.244485E+10 | 30492.57 | 13-FEB-08:61 | -8.7 |
March | 0.102921E+10 | 30489.65 | 14-MAR-07:01 | -1.4 |
April | 0.298350E+09 | 30480.20 | 03-APR-07:01 | 3.68 |
May | 38955565.07 | 17212.11 | 01-MAY-07:01 | 10.37 |
June | 14104902.87 | 849.42 | 23-JUN-07:05 | 23.45 |
July | 25068348.15 | 1638.03 | 16-JUL-16:03 | 29.90 |
August | 22401014.38 | 1653.72 | 13-AUG-16:02 | 29.90 |
September | 14555512.00 | 852.23 | 13-SEP-07:05 | 21.70 |
October | 31415943.72 | 4071.51 | 29-OCT-08:62 | 6.88 |
November | 0.675762E+09 | 30489.57 | 24-NOV-08:61 | -3.5 |
December | 0.163216E+10 | 30487.91 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.907728E+10 | |||
Minimum of Months | 14104902.87 | 849.42 | -10.9 | |
Maximum of Months | 0.285044E+10 | 30695.86 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293550E+10 | 30601.49 | 02-JAN-08:12 | -10.9 |
February | 0.252527E+10 | 30380.75 | 13-FEB-08:61 | -8.7 |
March | 0.109530E+10 | 30377.54 | 14-MAR-07:01 | -1.4 |
April | 0.330818E+09 | 30367.86 | 03-APR-07:01 | 3.68 |
May | 42296454.59 | 21564.10 | 01-MAY-07:01 | 10.37 |
June | 13831444.20 | 830.42 | 23-JUN-07:05 | 23.45 |
July | 25327312.70 | 1639.69 | 16-JUL-16:03 | 29.90 |
August | 22520518.96 | 1655.00 | 13-AUG-16:02 | 29.90 |
September | 15642837.05 | 836.34 | 13-SEP-07:05 | 21.70 |
October | 32827468.57 | 6172.08 | 29-OCT-08:62 | 6.88 |
November | 0.713618E+09 | 30378.18 | 24-NOV-08:61 | -3.5 |
December | 0.171116E+10 | 30376.00 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.946412E+10 | |||
Minimum of Months | 13831444.20 | 830.42 | -10.9 | |
Maximum of Months | 0.293550E+10 | 30601.49 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332522E+10 | 30522.75 | 02-JAN-08:12 | -10.9 |
February | 0.292517E+10 | 30300.89 | 13-FEB-08:61 | -8.7 |
March | 0.138148E+10 | 30300.00 | 14-MAR-07:01 | -1.4 |
April | 0.448667E+09 | 30290.81 | 03-APR-07:01 | 3.68 |
May | 57969688.27 | 30018.50 | 01-MAY-07:01 | 10.37 |
June | 13626259.17 | 785.68 | 26-JUN-07:04 | 23.40 |
July | 25549222.09 | 1642.63 | 16-JUL-16:03 | 29.90 |
August | 22850997.96 | 1655.77 | 13-AUG-16:02 | 29.90 |
September | 18739001.33 | 818.75 | 04-SEP-08:04 | 22.98 |
October | 38703762.03 | 12305.81 | 29-OCT-08:62 | 6.88 |
November | 0.884768E+09 | 30300.79 | 24-NOV-08:61 | -3.5 |
December | 0.204702E+10 | 30297.60 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.111898E+11 | |||
Minimum of Months | 13626259.17 | 785.68 | -10.9 | |
Maximum of Months | 0.332522E+10 | 30522.75 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552685E+10 | 32607.28 | 02-JAN-08:12 | -10.9 |
February | 0.508234E+10 | 32460.03 | 27-FEB-08:12 | -1.1 |
March | 0.272900E+10 | 32296.17 | 22-MAR-07:01 | -2.7 |
April | 0.108315E+10 | 32259.14 | 03-APR-07:01 | 3.68 |
May | 0.148788E+09 | 31947.13 | 01-MAY-07:01 | 10.37 |
June | 21882264.18 | 835.84 | 20-JUN-07:04 | 23.17 |
July | 25751125.00 | 1636.54 | 16-JUL-16:03 | 29.90 |
August | 20789769.34 | 1643.31 | 13-AUG-16:02 | 29.90 |
September | 26150441.51 | 903.61 | 02-SEP-07:03 | 21.70 |
October | 87366539.73 | 30407.22 | 29-OCT-08:62 | 6.88 |
November | 0.164290E+10 | 32279.13 | 24-NOV-08:61 | -3.5 |
December | 0.363207E+10 | 32271.34 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.200270E+11 | |||
Minimum of Months | 20789769.34 | 835.84 | -10.9 | |
Maximum of Months | 0.552685E+10 | 32607.28 | 29.90 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622635E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579091E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454787E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12838901.59 | 0.284742E+10 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69857896.02 | 0.165297E+10 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350034E+09 | 0.521595E+09 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831604E+09 | 88520274.79 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917063E+09 | 0.147482E+09 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163311E+09 | 0.793077E+09 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2987794.57 | 0.221386E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403118E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540885E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234770E+10 | 0.342701E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88520274.79 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917063E+09 | 0.622635E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298752E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280531E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221596E+10 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6913283.70 | 0.139383E+10 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37811054.05 | 0.817199E+09 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187100E+09 | 0.222502E+09 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446049E+09 | 29974885.52 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490733E+09 | 50346415.83 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88056901.42 | 0.363490E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1611893.85 | 0.107577E+10 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195773E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261384E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125828E+10 | 0.165335E+11 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29974885.52 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490733E+09 | 0.298752E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308761E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288758E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227565E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913324.29 | 0.142102E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37631358.62 | 0.838314E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184887E+09 | 0.251392E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437274E+09 | 47438571.47 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485417E+09 | 65398212.68 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86917112.44 | 0.390986E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612060.34 | 0.111539E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201518E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270757E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124065E+10 | 0.171035E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47438571.47 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485417E+09 | 0.308761E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307969E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288214E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226689E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913325.75 | 0.141152E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37631492.88 | 0.829368E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184877E+09 | 0.251054E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437202E+09 | 47692515.32 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485320E+09 | 65783005.61 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86916828.68 | 0.390675E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612146.35 | 0.110841E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200082E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270087E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124047E+10 | 0.170349E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47692515.32 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485320E+09 | 0.307969E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307326E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287750E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225790E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913396.44 | 0.139948E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37631962.93 | 0.813815E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184956E+09 | 0.248644E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437491E+09 | 45727489.39 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485615E+09 | 63998978.14 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86925571.61 | 0.388451E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612306.04 | 0.109714E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198387E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269521E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124115E+10 | 0.169450E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45727489.39 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485615E+09 | 0.307326E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566703E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530814E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415756E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12449185.09 | 0.255940E+10 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67733066.41 | 0.146511E+10 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334385E+09 | 0.467215E+09 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789890E+09 | 85602382.76 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878050E+09 | 0.123698E+09 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156738E+09 | 0.723361E+09 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2904066.12 | 0.200504E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363753E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497077E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224215E+10 | 0.311705E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85602382.76 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878050E+09 | 0.566703E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308595E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289419E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226281E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913293.69 | 0.138714E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37637041.79 | 0.788624E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185539E+09 | 0.247551E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438747E+09 | 42604178.64 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487430E+09 | 62422528.48 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87065522.05 | 0.389481E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612975.70 | 0.108381E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197229E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270653E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124495E+10 | 0.169234E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42604178.64 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487430E+09 | 0.308595E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308429E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289260E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225990E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913380.28 | 0.138156E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37637677.99 | 0.780295E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185568E+09 | 0.246711E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438867E+09 | 42057005.60 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487531E+09 | 61945175.59 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87069719.23 | 0.388658E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613275.08 | 0.107821E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196729E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270464E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124520E+10 | 0.168882E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42057005.60 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487531E+09 | 0.308429E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307559E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288490E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224957E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6914077.04 | 0.136641E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37638583.67 | 0.759881E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185646E+09 | 0.243779E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439147E+09 | 40396807.40 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487748E+09 | 60672786.93 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87077876.99 | 0.385933E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613470.45 | 0.106351E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195433E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269611E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124578E+10 | 0.167811E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40396807.40 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487748E+09 | 0.307559E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395686E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366373E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285721E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7304904.69 | 0.174079E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39447923.55 | 0.949955E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199174E+09 | 0.365887E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466833E+09 | 78659107.26 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521787E+09 | 0.120073E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91783321.25 | 0.529761E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1699302.16 | 0.139159E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254581E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344682E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132803E+10 | 0.216472E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78659107.26 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521787E+09 | 0.395686E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10094.55 | 14-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 10603.06 | 06-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7447.13 | 17-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 852.12 | 07-APR-13:00 | 5351.90 | 01-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.64 | 30-MAY-13:00 | 3267.05 | 14-MAY-16:40 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.48 | 19-JUN-12:00 | 1780.44 | 03-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2906.84 | 07-JUL-12:00 | 517.63 | 23-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3038.31 | 24-AUG-15:00 | 859.38 | 06-AUG-12:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.58 | 01-SEP-14:00 | 2674.34 | 23-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 334.90 | 04-OCT-13:00 | 4160.78 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7248.14 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9103.48 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.63 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.48 | 10603.06 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.88 | 30-MAY-13:00 | 1828.39 | 14-MAY-16:30 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.80 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 282.21 | 23-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.72 | 24-AUG-15:00 | 467.21 | 06-AUG-12:00 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.34 | 01-SEP-14:00 | 1492.89 | 23-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.09 | 04-OCT-13:00 | 2374.79 | 08-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.21 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.88 | 30-MAY-13:00 | 1756.99 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.77 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 538.26 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.77 | 24-AUG-15:00 | 719.16 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.34 | 01-SEP-14:00 | 1500.29 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 04-OCT-13:00 | 2358.51 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.26 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.88 | 30-MAY-13:00 | 1742.50 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.77 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 537.97 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.77 | 24-AUG-15:00 | 719.61 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.34 | 01-SEP-14:00 | 1500.29 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 04-OCT-13:00 | 2340.89 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.97 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1715.39 | 11-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.76 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 528.34 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.79 | 24-AUG-15:00 | 709.83 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1495.16 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2307.83 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.34 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9675.69 | 14-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 10243.06 | 06-FEB-12:10 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7257.11 | 17-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.80 | 07-APR-13:00 | 5279.65 | 01-APR-12:00 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1792.98 | 30-MAY-13:00 | 2958.74 | 13-MAY-16:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.56 | 19-JUN-12:00 | 1723.22 | 03-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2861.50 | 07-JUL-12:00 | 890.52 | 23-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.18 | 24-AUG-15:00 | 1217.81 | 06-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.86 | 01-SEP-14:00 | 2662.09 | 23-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.47 | 04-OCT-13:00 | 4062.31 | 28-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6985.57 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8794.39 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.52 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.56 | 10243.06 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1634.73 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 488.61 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.65 | 24-AUG-15:00 | 666.84 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1477.68 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2249.49 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.61 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1618.56 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 485.26 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.66 | 24-AUG-15:00 | 663.44 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1475.03 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2236.84 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.26 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 30-MAY-13:00 | 1580.05 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 476.97 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.66 | 24-AUG-15:00 | 657.65 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1463.04 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2202.54 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.97 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5783.04 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6045.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4222.90 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.40 | 07-APR-13:00 | 3011.31 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 30-MAY-13:00 | 1602.85 | 11-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.91 | 19-JUN-12:00 | 1013.75 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.80 | 07-JUL-12:00 | 472.23 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1734.73 | 24-AUG-15:00 | 681.60 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.04 | 01-SEP-14:00 | 1443.35 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 04-OCT-13:00 | 2297.83 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4138.42 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5190.19 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.23 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.91 | 6045.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12158.35 | 11-JAN-20:12 | 10125.10 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.35 |
February | 11325.65 | 03-FEB-00:02 | 1687.52 | 1338.85 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.37 |
March | 9946.54 | 17-MAR-23:03 | 1350.01 | 10711.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.23 |
April | 7867.66 | 08-APR-13:00 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.41 |
May | 12552.41 | 30-MAY-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 |
June | 32657.75 | 26-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.15 |
July | 36677.09 | 11-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.95 |
August | 35681.55 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.76 |
September | 37714.01 | 02-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 |
October | 14576.82 | 06-OCT-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.89 |
November | 10764.66 | 24-NOV-00:02 | 1687.52 | 1338.85 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.84 |
December | 10689.42 | 22-DEC-00:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7867.66 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.15 | |
Maximum of Months | 37714.01 | 10125.10 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5297.94 | 10-JAN-10:43 | 1349.97 | 12246.74 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.10 |
February | 5770.42 | 05-FEB-10:42 | 1687.47 | 15308.43 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.46 |
March | 3949.17 | 22-MAR-14:53 | 2531.20 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.35 |
April | 15501.63 | 16-APR-17:52 | 18224.65 | 27555.17 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 |
May | 17089.11 | 27-MAY-22:43 | 4724.91 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 |
June | 18399.50 | 26-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
July | 19863.41 | 11-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 |
August | 19356.02 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 |
September | 20274.98 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.30 |
October | 17971.22 | 25-OCT-20:54 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
November | 3652.51 | 04-NOV-13:00 | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.18 |
December | 4217.78 | 09-DEC-09:32 | 674.99 | 6445.65 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3652.51 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | |
Maximum of Months | 20274.98 | 18224.65 | 27555.17 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6002.53 | 11-JAN-19:32 | 3374.94 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.98 |
February | 5433.26 | 13-FEB-19:23 | 2699.95 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.90 |
March | 4030.61 | 29-MAR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.76 |
April | 4614.47 | 08-APR-12:30 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 |
May | 8914.80 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
June | 17851.70 | 23-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
July | 20060.21 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 |
August | 22989.57 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.69 |
September | 20391.46 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
October | 10727.93 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 |
November | 3563.28 | 18-NOV-08:23 | 506.24 | 4403.69 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.19 |
December | 4043.20 | 06-DEC-09:53 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3563.28 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 22989.57 | 3374.94 | 13945.03 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2149.36 | 19-JAN-18:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.29 |
February | 5747.57 | 03-FEB-09:52 | 1687.47 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.91 |
March | 4788.67 | 18-MAR-08:23 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.51 |
April | 4472.17 | 08-APR-12:30 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 |
May | 8580.44 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
June | 18062.27 | 23-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
July | 20095.92 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
August | 23115.81 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 |
September | 20412.90 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 |
October | 10605.63 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
November | 3518.92 | 18-NOV-08:33 | 506.24 | 4403.69 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.69 |
December | 3726.60 | 23-DEC-09:33 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2149.36 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | |
Maximum of Months | 23115.81 | 2024.96 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5311.81 | 31-JAN-20:23 | 674.99 | 5871.59 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.69 |
February | 5551.51 | 07-FEB-18:03 | 6749.87 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.17 |
March | 3388.02 | 29-MAR-17:20 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.98 |
April | 4178.06 | 08-APR-12:50 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.97 |
May | 7238.68 | 31-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16607.99 | 26-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 |
July | 19880.84 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
August | 21716.46 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 |
September | 20180.49 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
October | 9437.00 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.58 |
November | 3244.02 | 01-NOV-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.91 |
December | 4127.24 | 28-DEC-09:23 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3244.02 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21716.46 | 6749.87 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8098.56 | 17-JAN-19:53 | 5265.05 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.79 |
February | 10561.32 | 03-FEB-18:42 | 9180.09 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.94 |
March | 5995.28 | 10-MAR-13:53 | 14377.64 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.08 |
April | 6691.31 | 12-APR-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.97 |
May | 14124.57 | 30-MAY-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.39 |
June | 29791.60 | 23-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 |
July | 35147.93 | 11-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.72 |
August | 33918.12 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.53 |
September | 35961.21 | 02-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.55 |
October | 14986.10 | 06-OCT-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 |
November | 5176.14 | 15-NOV-15:15 | 9315.09 | 6383.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4035.97 |
December | 9758.23 | 21-DEC-20:53 | 2970.03 | 6719.20 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5176.14 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 | |
Maximum of Months | 35961.21 | 14377.64 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5121.04 | 31-JAN-18:03 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.27 |
February | 3864.18 | 10-FEB-18:53 | 3442.43 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.35 |
March | 4850.11 | 17-MAR-18:12 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.74 |
April | 3300.54 | 08-APR-12:30 | 2497.45 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.23 |
May | 6464.89 | 30-MAY-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 |
June | 15096.76 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.14 |
July | 18124.54 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 |
August | 17480.85 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.62 |
September | 18544.18 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 |
October | 6920.55 | 06-OCT-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.01 |
November | 2932.59 | 18-NOV-15:15 | 5399.90 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2546.12 |
December | 4266.62 | 21-DEC-10:32 | 1484.97 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2932.59 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | |
Maximum of Months | 18544.18 | 5399.90 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2546.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5637.89 | 31-JAN-11:32 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.34 |
February | 3254.14 | 02-FEB-10:33 | 1113.73 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.95 |
March | 3504.87 | 14-MAR-19:23 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.79 |
April | 3257.24 | 12-APR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.09 |
May | 5936.68 | 30-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 0.00 |
June | 14992.90 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
July | 18014.95 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.11 |
August | 17374.61 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.84 |
September | 18432.00 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 |
October | 6461.68 | 06-OCT-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.91 |
November | 4583.98 | 22-NOV-18:53 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.15 |
December | 4757.26 | 21-DEC-20:33 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3254.14 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18432.00 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 745.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3795.99 | 26-JAN-18:33 | 3442.43 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.06 |
February | 3885.52 | 22-FEB-19:03 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.01 |
March | 4120.61 | 08-MAR-11:43 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.18 |
April | 3016.58 | 08-APR-13:10 | 2598.70 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.85 |
May | 5779.55 | 30-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 0.00 |
June | 14771.39 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.52 |
July | 17838.23 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 |
August | 17210.95 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.65 |
September | 18266.76 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 |
October | 5187.14 | 04-OCT-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 0.00 |
November | 3808.49 | 25-NOV-11:43 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.57 |
December | 4585.77 | 21-DEC-19:53 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3016.58 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18266.76 | 5872.39 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 554.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 343.03 | 19-JAN-12:00 | 1451.22 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.68 |
February | 249.81 | 17-FEB-12:00 | 1451.22 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.23 |
March | 3166.15 | 09-MAR-11:13 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.97 |
April | 3129.86 | 08-APR-12:20 | 2497.45 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
May | 6130.98 | 30-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 0.00 |
June | 14653.66 | 20-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 |
July | 17033.84 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
August | 16402.80 | 22-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 0.00 |
September | 19465.25 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 |
October | 5527.00 | 04-OCT-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 0.00 |
November | 2861.95 | 17-NOV-19:43 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.80 |
December | 3698.89 | 09-DEC-11:03 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 249.81 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19465.25 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 623.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.674387E+11 | 59278.70 | 04-JAN-16:40 | 0.118208E+12 | 226431.25 | 02-JAN-08:09 |
February | 0.605428E+11 | 56683.37 | 08-FEB-17:19 | 0.110985E+12 | 231351.00 | 06-FEB-08:09 |
March | 0.659229E+11 | 53345.62 | 03-MAR-18:40 | 0.635022E+11 | 141577.79 | 22-MAR-07:10 |
April | 0.623962E+11 | 65002.33 | 07-APR-12:50 | 0.218632E+11 | 105388.03 | 03-APR-07:10 |
May | 0.673152E+11 | 71959.47 | 30-MAY-13:20 | 0.621807E+09 | 27381.53 | 01-MAY-07:10 |
June | 0.829406E+11 | 94687.19 | 19-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.990652E+11 | 97209.63 | 08-JUL-12:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.998642E+11 | 97554.40 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.782186E+11 | 81743.88 | 07-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.690700E+11 | 71346.84 | 04-OCT-14:09 | 0.627474E+09 | 23228.18 | 29-OCT-08:09 |
November | 0.637327E+11 | 53645.85 | 15-NOV-16:00 | 0.421107E+11 | 129614.01 | 24-NOV-08:09 |
December | 0.668719E+11 | 56348.67 | 23-DEC-16:00 | 0.887290E+11 | 162675.59 | 31-DEC-17:00 |
Annual Sum or Average | 0.883379E+12 | 0.446648E+12 | ||||
Minimum of Months | 0.605428E+11 | 53345.62 | 0.00 | 0.00 | ||
Maximum of Months | 0.998642E+11 | 97554.40 | 0.118208E+12 | 231351.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.669409E+10 | 0.108325E+11 | 0.00 | 0.976514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561887E+10 | 0.00 |
February | 0.312534E+11 | 0.546825E+10 | 0.980803E+10 | 0.00 | 0.890917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510389E+10 | 0.00 |
March | 0.350527E+11 | 0.526005E+10 | 0.110075E+11 | 0.00 | 0.895602E+10 | 0.00 | 0.00 | 6022808.53 | 0.00 | 0.00 | 0.00 | 0.564062E+10 | 0.00 |
April | 0.334898E+11 | 0.429522E+10 | 0.105079E+11 | 0.00 | 0.793308E+10 | 0.00 | 0.00 | 0.840086E+09 | 0.00 | 0.00 | 0.00 | 0.533004E+10 | 0.00 |
May | 0.347840E+11 | 0.384977E+10 | 0.109147E+11 | 0.00 | 0.795026E+10 | 0.00 | 0.00 | 0.443563E+10 | 0.00 | 0.00 | 0.00 | 0.538076E+10 | 0.00 |
June | 0.338757E+11 | 0.343615E+10 | 0.106386E+11 | 0.00 | 0.776646E+10 | 0.00 | 0.00 | 0.221161E+11 | 0.00 | 0.00 | 0.00 | 0.510765E+10 | 0.00 |
July | 0.344108E+11 | 0.363884E+10 | 0.107945E+11 | 0.00 | 0.808358E+10 | 0.00 | 0.00 | 0.369709E+11 | 0.00 | 0.00 | 0.00 | 0.516656E+10 | 0.00 |
August | 0.350409E+11 | 0.412573E+10 | 0.110006E+11 | 0.00 | 0.832789E+10 | 0.00 | 0.00 | 0.361758E+11 | 0.00 | 0.00 | 0.00 | 0.519317E+10 | 0.00 |
September | 0.335014E+11 | 0.474129E+10 | 0.105148E+11 | 0.00 | 0.764824E+10 | 0.00 | 0.00 | 0.167732E+11 | 0.00 | 0.00 | 0.00 | 0.503968E+10 | 0.00 |
October | 0.345281E+11 | 0.572595E+10 | 0.108325E+11 | 0.00 | 0.788604E+10 | 0.00 | 0.00 | 0.480287E+10 | 0.00 | 0.00 | 0.00 | 0.529460E+10 | 0.00 |
November | 0.334535E+11 | 0.626785E+10 | 0.104978E+11 | 0.00 | 0.824376E+10 | 0.00 | 0.00 | 1858364.94 | 0.00 | 0.00 | 0.00 | 0.526787E+10 | 0.00 |
December | 0.344233E+11 | 0.686921E+10 | 0.108050E+11 | 0.00 | 0.922526E+10 | 0.00 | 0.00 | 20814.07 | 0.00 | 0.00 | 0.00 | 0.554906E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.603724E+11 | 0.128154E+12 | 0.00 | 0.100695E+12 | 0.00 | 0.00 | 0.122123E+12 | 0.00 | 0.00 | 0.00 | 0.636928E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.343615E+10 | 0.980803E+10 | 0.00 | 0.764824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503968E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.686921E+10 | 0.110075E+11 | 0.00 | 0.976514E+10 | 0.00 | 0.00 | 0.369709E+11 | 0.00 | 0.00 | 0.00 | 0.564062E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.118208E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.110985E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.635022E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218632E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.621807E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.627474E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.421107E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.887290E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.446648E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.118208E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9238.00 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9320.04 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7781.88 | 22-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7161.33 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 5823.39 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 7769.52 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 8560.06 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8469.52 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6600.31 | 13-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 5752.61 | 29-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7579.69 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8147.01 | 31-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 5752.61 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 9320.04 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11858.70 | 04-JAN-13:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11461.55 | 06-FEB-14:39 | 0.00 |
March | 1845.73 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 9084.31 | 06-MAR-14:09 | 0.00 |
April | 16070.17 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 9744.11 | 07-APR-12:50 | 0.00 |
May | 27670.81 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9386.80 | 18-MAY-17:49 | 0.00 |
June | 48712.28 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 9688.43 | 27-JUN-13:50 | 0.00 |
July | 49566.88 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 9688.62 | 01-JUL-12:50 | 0.00 |
August | 49316.07 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 7564.42 | 02-AUG-13:30 | 0.00 |
September | 36627.57 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9694.49 | 29-SEP-12:09 | 0.00 |
October | 24768.62 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9697.09 | 19-OCT-13:30 | 0.00 |
November | 388.85 | 03-NOV-23:10 | 0.00 | 0.00 | 0.00 | 9135.06 | 11-NOV-15:20 | 0.00 |
December | 17.88 | 17-DEC-21:30 | 0.00 | 0.00 | 0.00 | 9685.16 | 23-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7564.42 | 0.00 | ||
Maximum of Months | 49566.88 | 0.00 | 0.00 | 0.00 | 11858.70 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 59278.70 | 04-JAN-16:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7652.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56683.37 | 08-FEB-17:19 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7701.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53345.62 | 03-MAR-18:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 5365.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65002.33 | 07-APR-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5351.33 | 0.00 | 0.00 | 15586.10 | 0.00 |
May | 71959.47 | 30-MAY-13:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5351.33 | 0.00 | 0.00 | 26833.48 | 0.00 |
June | 94687.19 | 19-JUN-11:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7464.48 | 0.00 | 0.00 | 47464.47 | 0.00 |
July | 97209.63 | 08-JUL-12:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8491.36 | 0.00 | 0.00 | 48951.06 | 0.00 |
August | 97554.40 | 16-AUG-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8469.52 | 0.00 | 0.00 | 49316.07 | 0.00 |
September | 81743.88 | 07-SEP-13:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5995.68 | 0.00 | 0.00 | 35979.82 | 0.00 |
October | 71346.84 | 04-OCT-14:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5351.33 | 0.00 | 0.00 | 24121.81 | 0.00 |
November | 53645.85 | 15-NOV-16:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6263.33 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56348.67 | 23-DEC-16:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6835.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 53345.62 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5351.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97554.40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8491.36 | 0.00 | 0.00 | 49316.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 226431.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 231351.00 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 141577.79 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 105388.03 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 27381.53 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 23228.18 | 29-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 129614.01 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 162675.59 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 231351.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.44 | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 2.67 | 20.40 | 1.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 6.50 | 20.44 | 2.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.55 | 1.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
February | 0.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
February | 0.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 1.17 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 1.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 4.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
February | 7.50 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
March | 2.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
December | 3.33 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
Annual Sum or Average | 22.50 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.07 | 288.17 | 21.06 | 288.17 | 21.05 |
February | 448.00 | 21.06 | 306.17 | 21.05 | 306.17 | 21.05 |
March | 493.17 | 21.17 | 96.83 | 21.13 | 96.83 | 21.10 |
April | 407.00 | 21.70 | 46.17 | 21.76 | 23.83 | 21.72 |
May | 224.83 | 22.85 | 111.33 | 23.18 | 26.50 | 23.23 |
June | 99.00 | 23.88 | 422.00 | 23.89 | 92.17 | 23.89 |
July | 117.50 | 23.89 | 494.83 | 23.89 | 117.50 | 23.89 |
August | 51.50 | 23.89 | 472.83 | 23.89 | 51.50 | 23.89 |
September | 41.33 | 23.73 | 367.83 | 23.87 | 23.33 | 23.87 |
October | 228.17 | 22.71 | 223.33 | 23.29 | 27.33 | 23.32 |
November | 468.00 | 21.44 | 58.17 | 21.39 | 58.17 | 21.35 |
December | 496.00 | 21.07 | 199.67 | 21.05 | 199.67 | 21.04 |
Annual Sum or Average | 3570.50 | 21.66 | 3087.33 | 22.27 | 1311.17 | 22.19 |
Minimum of Months | 41.33 | 21.06 | 46.17 | 21.05 | 23.33 | 21.04 |
Maximum of Months | 496.00 | 23.89 | 494.83 | 23.89 | 306.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.40 | 138.33 | 21.34 | 138.33 | 21.30 |
February | 448.00 | 21.42 | 128.50 | 21.35 | 128.50 | 21.31 |
March | 489.67 | 21.75 | 16.17 | 21.73 | 16.17 | 21.71 |
April | 356.33 | 22.19 | 33.50 | 22.33 | 0.67 | 22.33 |
May | 142.83 | 23.37 | 141.33 | 23.62 | 24.50 | 23.64 |
June | 31.00 | 23.87 | 409.17 | 23.89 | 27.83 | 23.89 |
July | 54.17 | 23.89 | 492.00 | 23.89 | 54.17 | 23.89 |
August | 27.67 | 23.85 | 454.67 | 23.89 | 26.83 | 23.89 |
September | 23.33 | 23.74 | 349.17 | 23.88 | 13.17 | 23.88 |
October | 173.50 | 23.28 | 231.83 | 23.62 | 16.00 | 23.63 |
November | 443.67 | 22.06 | 10.17 | 22.05 | 7.33 | 22.04 |
December | 496.00 | 21.54 | 24.50 | 21.52 | 24.50 | 21.50 |
Annual Sum or Average | 3182.17 | 21.95 | 2429.33 | 22.64 | 478.00 | 22.59 |
Minimum of Months | 23.33 | 21.40 | 10.17 | 21.34 | 0.67 | 21.30 |
Maximum of Months | 496.00 | 23.89 | 492.00 | 23.89 | 138.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 156.33 | 21.11 | 156.33 | 21.11 |
February | 336.00 | 21.11 | 155.50 | 21.11 | 155.50 | 21.11 |
March | 374.00 | 21.25 | 33.00 | 21.24 | 33.00 | 21.23 |
April | 290.50 | 21.75 | 25.50 | 21.89 | 4.17 | 21.88 |
May | 138.83 | 23.08 | 102.33 | 23.46 | 23.67 | 23.50 |
June | 54.00 | 24.13 | 327.83 | 24.03 | 51.17 | 24.04 |
July | 92.50 | 24.24 | 369.00 | 24.09 | 92.50 | 24.11 |
August | 45.83 | 24.47 | 364.50 | 24.10 | 45.83 | 24.14 |
September | 31.17 | 23.92 | 287.17 | 24.00 | 20.83 | 24.01 |
October | 144.00 | 22.85 | 180.67 | 23.46 | 16.50 | 23.48 |
November | 345.50 | 21.58 | 19.00 | 21.57 | 17.17 | 21.55 |
December | 369.00 | 21.11 | 57.00 | 21.11 | 57.00 | 21.11 |
Annual Sum or Average | 2592.33 | 21.74 | 2077.83 | 22.49 | 673.67 | 22.46 |
Minimum of Months | 31.17 | 21.11 | 19.00 | 21.11 | 4.17 | 21.11 |
Maximum of Months | 374.00 | 24.47 | 369.00 | 24.10 | 156.33 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 167.33 | 21.11 | 167.33 | 21.11 |
February | 336.00 | 21.11 | 168.50 | 21.11 | 168.50 | 21.11 |
March | 376.50 | 21.25 | 39.83 | 21.23 | 39.83 | 21.22 |
April | 295.50 | 21.73 | 25.17 | 21.85 | 5.50 | 21.84 |
May | 148.17 | 22.99 | 94.83 | 23.37 | 23.67 | 23.42 |
June | 55.67 | 24.12 | 326.83 | 24.03 | 52.50 | 24.04 |
July | 92.17 | 24.24 | 369.00 | 24.09 | 92.17 | 24.11 |
August | 45.67 | 24.47 | 364.83 | 24.10 | 45.67 | 24.14 |
September | 31.83 | 23.90 | 286.17 | 24.00 | 21.00 | 24.01 |
October | 148.33 | 22.79 | 178.33 | 23.42 | 16.83 | 23.44 |
November | 348.33 | 21.53 | 23.83 | 21.50 | 23.83 | 21.48 |
December | 369.00 | 21.11 | 77.33 | 21.11 | 77.33 | 21.11 |
Annual Sum or Average | 2618.17 | 21.72 | 2122.00 | 22.45 | 734.17 | 22.42 |
Minimum of Months | 31.83 | 21.11 | 23.83 | 21.11 | 5.50 | 21.11 |
Maximum of Months | 376.50 | 24.47 | 369.00 | 24.10 | 168.50 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 185.67 | 21.11 | 185.67 | 21.11 |
February | 336.00 | 21.11 | 187.33 | 21.11 | 187.33 | 21.11 |
March | 379.00 | 21.24 | 51.33 | 21.22 | 51.33 | 21.21 |
April | 305.00 | 21.71 | 25.83 | 21.81 | 9.00 | 21.79 |
May | 162.17 | 22.84 | 78.83 | 23.20 | 23.67 | 23.27 |
June | 62.50 | 24.09 | 324.50 | 24.02 | 58.50 | 24.03 |
July | 102.33 | 24.20 | 369.00 | 24.08 | 102.33 | 24.10 |
August | 50.00 | 24.42 | 363.33 | 24.10 | 50.00 | 24.13 |
September | 35.67 | 23.85 | 281.67 | 23.99 | 22.33 | 24.00 |
October | 156.67 | 22.69 | 170.17 | 23.34 | 17.50 | 23.37 |
November | 350.83 | 21.46 | 31.67 | 21.43 | 31.67 | 21.40 |
December | 369.00 | 21.11 | 102.67 | 21.11 | 102.67 | 21.11 |
Annual Sum or Average | 2680.17 | 21.72 | 2172.00 | 22.41 | 842.00 | 22.37 |
Minimum of Months | 35.67 | 21.11 | 25.83 | 21.11 | 9.00 | 21.11 |
Maximum of Months | 379.00 | 24.42 | 369.00 | 24.10 | 187.33 | 24.13 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 235.67 | 21.11 | 235.67 | 21.11 |
February | 308.00 | 21.11 | 232.33 | 21.11 | 232.33 | 21.11 |
March | 348.00 | 21.20 | 79.67 | 21.18 | 79.67 | 21.17 |
April | 298.00 | 21.72 | 21.00 | 21.75 | 13.67 | 21.72 |
May | 193.17 | 22.76 | 63.17 | 23.03 | 25.50 | 23.10 |
June | 98.33 | 23.95 | 290.00 | 23.93 | 95.17 | 23.93 |
July | 132.00 | 24.00 | 338.00 | 23.96 | 132.00 | 23.97 |
August | 63.17 | 24.02 | 327.00 | 23.95 | 63.17 | 23.96 |
September | 48.67 | 23.77 | 247.83 | 23.90 | 33.00 | 23.90 |
October | 159.50 | 22.57 | 144.00 | 23.20 | 19.83 | 23.24 |
November | 325.17 | 21.34 | 53.17 | 21.31 | 53.17 | 21.29 |
December | 338.00 | 21.11 | 191.00 | 21.11 | 191.00 | 21.11 |
Annual Sum or Average | 2652.00 | 21.79 | 2222.83 | 22.30 | 1174.17 | 22.24 |
Minimum of Months | 48.67 | 21.11 | 21.00 | 21.11 | 13.67 | 21.11 |
Maximum of Months | 348.00 | 24.02 | 338.00 | 23.96 | 235.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 236.50 | 21.11 | 236.50 | 21.11 |
February | 308.00 | 21.11 | 234.50 | 21.11 | 234.50 | 21.11 |
March | 348.00 | 21.19 | 85.67 | 21.17 | 85.67 | 21.16 |
April | 302.67 | 21.73 | 21.83 | 21.74 | 15.67 | 21.72 |
May | 210.33 | 22.79 | 59.50 | 23.02 | 25.33 | 23.09 |
June | 102.50 | 23.94 | 281.67 | 23.93 | 97.33 | 23.93 |
July | 133.83 | 23.99 | 336.83 | 23.96 | 133.83 | 23.97 |
August | 65.67 | 24.02 | 318.17 | 23.95 | 65.67 | 23.96 |
September | 52.17 | 23.77 | 233.17 | 23.90 | 33.33 | 23.90 |
October | 165.67 | 22.59 | 136.00 | 23.18 | 19.83 | 23.22 |
November | 326.00 | 21.33 | 55.83 | 21.30 | 55.83 | 21.28 |
December | 338.00 | 21.11 | 194.83 | 21.11 | 194.83 | 21.11 |
Annual Sum or Average | 2692.83 | 21.81 | 2194.50 | 22.29 | 1198.33 | 22.23 |
Minimum of Months | 52.17 | 21.11 | 21.83 | 21.11 | 15.67 | 21.11 |
Maximum of Months | 348.00 | 24.02 | 336.83 | 23.96 | 236.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 241.00 | 21.11 | 241.00 | 21.11 |
February | 308.00 | 21.11 | 242.67 | 21.11 | 242.67 | 21.11 |
March | 348.00 | 21.18 | 93.00 | 21.17 | 93.00 | 21.16 |
April | 305.67 | 21.72 | 23.83 | 21.72 | 18.33 | 21.69 |
May | 221.00 | 22.76 | 57.17 | 22.98 | 25.33 | 23.05 |
June | 107.83 | 23.94 | 279.50 | 23.93 | 102.17 | 23.93 |
July | 138.17 | 23.99 | 336.67 | 23.96 | 138.17 | 23.97 |
August | 68.67 | 24.00 | 316.83 | 23.95 | 68.67 | 23.96 |
September | 54.67 | 23.76 | 229.50 | 23.90 | 34.50 | 23.90 |
October | 170.67 | 22.56 | 134.00 | 23.15 | 20.00 | 23.19 |
November | 326.17 | 21.31 | 58.17 | 21.28 | 58.17 | 21.26 |
December | 338.00 | 21.11 | 203.00 | 21.11 | 203.00 | 21.11 |
Annual Sum or Average | 2726.83 | 21.82 | 2215.33 | 22.28 | 1245.00 | 22.22 |
Minimum of Months | 54.67 | 21.11 | 23.83 | 21.11 | 18.33 | 21.11 |
Maximum of Months | 348.00 | 24.00 | 336.67 | 23.96 | 242.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 258.33 | 21.11 | 258.33 | 21.11 |
February | 308.00 | 21.11 | 264.17 | 21.11 | 264.17 | 21.11 |
March | 348.00 | 21.17 | 117.00 | 21.15 | 117.00 | 21.15 |
April | 311.50 | 21.69 | 31.50 | 21.67 | 27.67 | 21.63 |
May | 239.00 | 22.66 | 52.67 | 22.86 | 25.67 | 22.92 |
June | 122.17 | 23.93 | 274.67 | 23.92 | 115.17 | 23.93 |
July | 145.00 | 23.98 | 336.50 | 23.96 | 145.00 | 23.96 |
August | 70.50 | 24.00 | 316.17 | 23.95 | 70.50 | 23.96 |
September | 61.00 | 23.72 | 224.00 | 23.88 | 36.33 | 23.89 |
October | 184.50 | 22.50 | 130.83 | 23.08 | 22.83 | 23.13 |
November | 327.50 | 21.28 | 72.33 | 21.25 | 72.33 | 21.23 |
December | 338.00 | 21.11 | 235.00 | 21.11 | 235.00 | 21.11 |
Annual Sum or Average | 2795.17 | 21.83 | 2313.17 | 22.24 | 1390.00 | 22.18 |
Minimum of Months | 61.00 | 21.11 | 31.50 | 21.11 | 22.83 | 21.11 |
Maximum of Months | 348.00 | 24.00 | 336.50 | 23.96 | 264.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 303.33 | 21.11 | 303.33 | 21.11 |
February | 308.00 | 21.11 | 307.17 | 21.11 | 307.17 | 21.11 |
March | 348.00 | 21.15 | 210.33 | 21.13 | 210.33 | 21.13 |
April | 316.33 | 21.63 | 75.83 | 21.53 | 75.83 | 21.46 |
May | 276.83 | 22.54 | 53.17 | 22.69 | 26.00 | 22.71 |
June | 142.67 | 23.90 | 268.33 | 23.91 | 133.67 | 23.91 |
July | 150.50 | 23.98 | 337.17 | 23.96 | 150.50 | 23.96 |
August | 64.67 | 24.02 | 324.17 | 23.95 | 64.67 | 23.96 |
September | 74.83 | 23.60 | 218.50 | 23.85 | 41.00 | 23.85 |
October | 202.17 | 22.36 | 128.17 | 22.93 | 28.83 | 22.98 |
November | 330.00 | 21.25 | 131.83 | 21.21 | 131.83 | 21.19 |
December | 338.00 | 21.11 | 316.00 | 21.11 | 316.00 | 21.11 |
Annual Sum or Average | 2892.00 | 21.83 | 2674.00 | 22.15 | 1789.17 | 22.07 |
Minimum of Months | 64.67 | 21.11 | 53.17 | 21.11 | 26.00 | 21.11 |
Maximum of Months | 348.00 | 24.02 | 337.17 | 23.96 | 316.00 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.06895 | 23.05295 | -0.5699 | 12.16171 |
February | 448.00000 | 21.06184 | 17.74620 | -0.5996 | 12.82278 |
March | 497.00000 | 21.19038 | 29.40142 | -0.4283 | 9.41274 |
April | 479.00000 | 22.02365 | 36.76107 | -0.1495 | 7.65905 |
May | 496.00000 | 23.39914 | 43.74823 | -0.6714 | 16.05633 |
June | 481.00000 | 23.88683 | 54.81222 | -0.3393 | 7.61655 |
July | 495.00000 | 23.88979 | 60.35763 | -0.2482 | 6.37640 |
August | 497.00000 | 23.88843 | 53.59443 | -0.2775 | 6.80611 |
September | 479.00000 | 23.87190 | 48.66307 | -0.3796 | 8.32032 |
October | 496.00000 | 23.33258 | 41.84115 | 0.28676 | 8.51515 |
November | 480.00000 | 21.49991 | 32.02782 | -0.3079 | 8.16575 |
December | 496.00000 | 21.06739 | 22.78976 | -0.5259 | 10.96979 |
Annual Sum or Average | 5840.00000 | 22.52352 | 38.85664 | -0.3495 | 9.56500 |
Minimum of Months | 448.00000 | 21.06184 | 17.74620 | -0.6714 | 6.37640 |
Maximum of Months | 497.00000 | 23.88979 | 60.35763 | 0.28676 | 16.05633 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.39945 | 25.18889 | -0.4353 | 9.49222 |
February | 448.00000 | 21.41668 | 19.90032 | -0.4558 | 9.78643 |
March | 497.00000 | 21.77987 | 30.72310 | -0.2617 | 7.38094 |
April | 479.00000 | 22.62183 | 36.89209 | 0.00495 | 6.87654 |
May | 496.00000 | 23.71916 | 42.68204 | -0.5525 | 12.00557 |
June | 481.00000 | 23.87706 | 51.84569 | -0.3556 | 7.84664 |
July | 495.00000 | 23.88999 | 56.90151 | -0.2778 | 6.73746 |
August | 497.00000 | 23.87854 | 51.27095 | -0.3079 | 7.19812 |
September | 479.00000 | 23.86750 | 46.80767 | -0.3899 | 8.42224 |
October | 496.00000 | 23.66784 | 40.84335 | 0.35902 | 8.57935 |
November | 480.00000 | 22.19476 | 32.69880 | -0.1321 | 6.95191 |
December | 496.00000 | 21.53767 | 24.82468 | -0.3749 | 8.40902 |
Annual Sum or Average | 5840.00000 | 22.82876 | 38.49201 | -0.2640 | 8.30369 |
Minimum of Months | 448.00000 | 21.39945 | 19.90032 | -0.5525 | 6.73746 |
Maximum of Months | 497.00000 | 23.88999 | 56.90151 | 0.35902 | 12.00557 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10950 | 22.65837 | -0.5190 | 10.89909 |
February | 336.00000 | 21.10962 | 17.10791 | -0.5391 | 11.25181 |
March | 379.00000 | 21.28705 | 28.33733 | -0.3740 | 8.46974 |
April | 360.00000 | 22.16307 | 35.18759 | -0.0985 | 7.31195 |
May | 375.00000 | 23.60560 | 42.52624 | -0.5899 | 13.42857 |
June | 366.00000 | 23.99859 | 53.72108 | -0.3076 | 7.30164 |
July | 369.00000 | 24.04705 | 59.78109 | -0.2105 | 6.25640 |
August | 379.00000 | 24.05149 | 52.70027 | -0.2439 | 6.69924 |
September | 360.00000 | 23.97238 | 47.80037 | -0.3514 | 7.98011 |
October | 371.00000 | 23.50543 | 41.04194 | 0.33266 | 8.70732 |
November | 360.00000 | 21.67226 | 31.06643 | -0.2474 | 7.65306 |
December | 369.00000 | 21.11344 | 21.99094 | -0.4799 | 9.90047 |
Annual Sum or Average | 4395.00000 | 22.64820 | 37.98340 | -0.3012 | 8.81317 |
Minimum of Months | 336.00000 | 21.10950 | 17.10791 | -0.5899 | 6.25640 |
Maximum of Months | 379.00000 | 24.05149 | 59.78109 | 0.33266 | 13.42857 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11000 | 22.65748 | -0.5308 | 11.16493 |
February | 336.00000 | 21.10981 | 17.10749 | -0.5495 | 11.49576 |
March | 379.00000 | 21.26519 | 28.38276 | -0.3881 | 8.65712 |
April | 360.00000 | 22.11717 | 35.30566 | -0.1165 | 7.37267 |
May | 375.00000 | 23.54683 | 42.70852 | -0.6152 | 14.30152 |
June | 366.00000 | 23.99755 | 53.76127 | -0.3088 | 7.31699 |
July | 369.00000 | 24.04673 | 59.78440 | -0.2104 | 6.25478 |
August | 379.00000 | 24.05134 | 52.68675 | -0.2434 | 6.69337 |
September | 360.00000 | 23.96996 | 47.82485 | -0.3532 | 8.01543 |
October | 371.00000 | 23.46407 | 41.17145 | 0.32021 | 8.65278 |
November | 360.00000 | 21.60822 | 31.20215 | -0.2709 | 7.78542 |
December | 369.00000 | 21.11166 | 21.99256 | -0.4905 | 10.11692 |
Annual Sum or Average | 4395.00000 | 22.62839 | 38.03908 | -0.3120 | 8.97782 |
Minimum of Months | 336.00000 | 21.10981 | 17.10749 | -0.6152 | 6.25478 |
Maximum of Months | 379.00000 | 24.05134 | 59.78440 | 0.32021 | 14.30152 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10962 | 22.65822 | -0.5456 | 11.50450 |
February | 336.00000 | 21.10972 | 17.10805 | -0.5638 | 11.83699 |
March | 379.00000 | 21.23662 | 28.43905 | -0.4061 | 8.91734 |
April | 360.00000 | 22.04671 | 35.48758 | -0.1417 | 7.44536 |
May | 375.00000 | 23.44101 | 43.04810 | -0.6593 | 15.83363 |
June | 366.00000 | 23.99206 | 54.02149 | -0.3156 | 7.40234 |
July | 369.00000 | 24.04261 | 60.06849 | -0.2152 | 6.28205 |
August | 379.00000 | 24.04720 | 52.87716 | -0.2487 | 6.73503 |
September | 360.00000 | 23.96039 | 48.01016 | -0.3616 | 8.15626 |
October | 371.00000 | 23.39354 | 41.42379 | 0.29995 | 8.55210 |
November | 360.00000 | 21.52001 | 31.39349 | -0.3012 | 7.97336 |
December | 369.00000 | 21.11008 | 21.99414 | -0.5040 | 10.40010 |
Annual Sum or Average | 4395.00000 | 22.59583 | 38.20215 | -0.3291 | 9.24688 |
Minimum of Months | 336.00000 | 21.10962 | 17.10805 | -0.6593 | 6.28205 |
Maximum of Months | 379.00000 | 24.04720 | 60.06849 | 0.29995 | 15.83363 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10978 | 24.12589 | -0.5873 | 12.49074 |
February | 308.00000 | 21.10978 | 18.54464 | -0.6042 | 12.81969 |
March | 348.00000 | 21.19530 | 29.97543 | -0.4452 | 9.55858 |
April | 330.00000 | 21.93060 | 37.19059 | -0.1886 | 7.61999 |
May | 344.00000 | 23.25376 | 44.91472 | -0.7409 | 18.65107 |
June | 336.00000 | 23.91498 | 55.75798 | -0.3458 | 7.73377 |
July | 338.00000 | 23.95027 | 61.57923 | -0.2441 | 6.43468 |
August | 348.00000 | 23.93358 | 54.15374 | -0.2817 | 6.92950 |
September | 330.00000 | 23.89359 | 49.50283 | -0.3900 | 8.53144 |
October | 340.00000 | 23.25965 | 43.12881 | 0.26548 | 8.34600 |
November | 330.00000 | 21.38030 | 33.06280 | -0.3586 | 8.54700 |
December | 338.00000 | 21.10976 | 23.31999 | -0.5433 | 11.25996 |
Annual Sum or Average | 4030.00000 | 22.51483 | 39.76579 | -0.3709 | 9.90486 |
Minimum of Months | 308.00000 | 21.10976 | 18.54464 | -0.7409 | 6.43468 |
Maximum of Months | 348.00000 | 23.95027 | 61.57923 | 0.26548 | 18.65107 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10975 | 24.02781 | -0.5857 | 12.43933 |
February | 308.00000 | 21.10976 | 18.44676 | -0.6045 | 12.81900 |
March | 348.00000 | 21.19096 | 29.89520 | -0.4523 | 9.67723 |
April | 330.00000 | 21.90993 | 37.15465 | -0.2024 | 7.67230 |
May | 344.00000 | 23.21857 | 44.94368 | -0.7704 | 19.65919 |
June | 336.00000 | 23.91449 | 55.81823 | -0.3664 | 8.03601 |
July | 338.00000 | 23.94936 | 61.66630 | -0.2678 | 6.68206 |
August | 348.00000 | 23.93276 | 54.21373 | -0.3069 | 7.23186 |
September | 330.00000 | 23.89386 | 49.51166 | -0.4101 | 8.85352 |
October | 340.00000 | 23.24939 | 43.12461 | 0.24990 | 8.19742 |
November | 330.00000 | 21.36504 | 33.00137 | -0.3694 | 8.65067 |
December | 338.00000 | 21.10954 | 23.22366 | -0.5453 | 11.30279 |
Annual Sum or Average | 4030.00000 | 22.50746 | 39.74740 | -0.3850 | 10.09903 |
Minimum of Months | 308.00000 | 21.10954 | 18.44676 | -0.7704 | 6.68206 |
Maximum of Months | 348.00000 | 23.94936 | 61.66630 | 0.24990 | 19.65919 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10943 | 24.02843 | -0.5897 | 12.53523 |
February | 308.00000 | 21.10994 | 18.44689 | -0.6090 | 12.93576 |
March | 348.00000 | 21.18481 | 29.90883 | -0.4590 | 9.79558 |
April | 330.00000 | 21.88093 | 37.22400 | -0.2138 | 7.73411 |
May | 344.00000 | 23.16613 | 45.11403 | -0.7945 | 20.55578 |
June | 336.00000 | 23.91355 | 55.92688 | -0.3700 | 8.09399 |
July | 338.00000 | 23.94887 | 61.80099 | -0.2703 | 6.70839 |
August | 348.00000 | 23.93243 | 54.28663 | -0.3097 | 7.26688 |
September | 330.00000 | 23.89067 | 49.58582 | -0.4143 | 8.93744 |
October | 340.00000 | 23.21570 | 43.25091 | 0.23912 | 8.15959 |
November | 330.00000 | 21.34362 | 33.04688 | -0.3789 | 8.75777 |
December | 338.00000 | 21.10944 | 23.22391 | -0.5502 | 11.41616 |
Annual Sum or Average | 4030.00000 | 22.49505 | 39.81598 | -0.3924 | 10.23988 |
Minimum of Months | 308.00000 | 21.10943 | 18.44689 | -0.7945 | 6.70839 |
Maximum of Months | 348.00000 | 23.94887 | 61.80099 | 0.23912 | 20.55578 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10977 | 24.02770 | -0.6048 | 12.91622 |
February | 308.00000 | 21.10979 | 18.44685 | -0.6260 | 13.38096 |
March | 348.00000 | 21.16909 | 29.94420 | -0.4792 | 10.17543 |
April | 330.00000 | 21.81466 | 37.38179 | -0.2418 | 7.94387 |
May | 344.00000 | 23.03911 | 45.52544 | -0.8491 | 22.62141 |
June | 336.00000 | 23.91004 | 56.20329 | -0.3759 | 8.19925 |
July | 338.00000 | 23.94790 | 62.01015 | -0.2714 | 6.71783 |
August | 348.00000 | 23.93191 | 54.37170 | -0.3102 | 7.27612 |
September | 330.00000 | 23.87914 | 49.75633 | -0.4218 | 9.11744 |
October | 340.00000 | 23.13009 | 43.54117 | 0.21453 | 8.11891 |
November | 330.00000 | 21.30216 | 33.13121 | -0.4004 | 9.05283 |
December | 338.00000 | 21.10935 | 23.22408 | -0.5665 | 11.80096 |
Annual Sum or Average | 4030.00000 | 22.46545 | 39.96032 | -0.4102 | 10.61046 |
Minimum of Months | 308.00000 | 21.10935 | 18.44685 | -0.8491 | 6.71783 |
Maximum of Months | 348.00000 | 23.94790 | 62.01015 | 0.21453 | 22.62141 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 23.86232 | -0.6697 | 14.69355 |
February | 308.00000 | 21.11000 | 18.29345 | -0.6970 | 15.39038 |
March | 348.00000 | 21.14739 | 29.77725 | -0.5464 | 11.62539 |
April | 330.00000 | 21.72643 | 37.38856 | -0.3071 | 8.80649 |
May | 344.00000 | 22.81498 | 46.06587 | -0.9559 | 26.97317 |
June | 336.00000 | 23.89992 | 57.05330 | -0.3830 | 8.36616 |
July | 338.00000 | 23.94952 | 62.27977 | -0.2531 | 6.52812 |
August | 348.00000 | 23.93402 | 54.34419 | -0.2842 | 6.98413 |
September | 330.00000 | 23.84287 | 50.09604 | -0.4292 | 9.49501 |
October | 340.00000 | 22.97566 | 43.82934 | 0.16945 | 8.21845 |
November | 330.00000 | 21.25438 | 33.02270 | -0.4532 | 10.02846 |
December | 338.00000 | 21.10974 | 23.06802 | -0.6284 | 13.38241 |
Annual Sum or Average | 4030.00000 | 22.41685 | 40.08817 | -0.4521 | 11.70592 |
Minimum of Months | 308.00000 | 21.10974 | 18.29345 | -0.9559 | 6.52812 |
Maximum of Months | 348.00000 | 23.94952 | 62.27977 | 0.16945 | 26.97317 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 5652171.59 | 1615746.61 | 1.67 | 4151991.02 | 1500180.57 | 0.00 | 0.11 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1930.90 | 27-MAR-16:10 | 1410.91 | 27-MAR-16:10 | 519.98 | 27-MAR-16:10 | 549.10 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.597003E+09 | 0.163454E+09 | 38.33 | 0.519746E+09 | 77256789.03 | 0.00 | 0.54 | 07-APR-13:00 | 0.00 | 01-APR-00:05 | 10384.67 | 07-APR-13:00 | 9589.85 | 07-APR-13:00 | 1866.59 | 08-APR-13:00 | 2847.90 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.339031E+10 | 0.896144E+09 | 165.13 | 0.289148E+10 | 0.498828E+09 | 0.00 | 0.85 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 19087.78 | 31-MAY-14:00 | 15903.20 | 30-MAY-13:00 | 5718.16 | 31-MAY-13:30 | 4669.85 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.176542E+11 | 0.441412E+10 | 438.13 | 0.117531E+11 | 0.590116E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 50212.77 | 25-JUN-07:02 | 37031.30 | 26-JUN-07:02 | 25126.83 | 16-JUN-07:03 | 11205.39 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.316152E+11 | 0.764037E+10 | 496.96 | 0.194591E+11 | 0.121561E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 51478.60 | 22-JUL-07:02 | 36405.57 | 12-JUL-07:02 | 28318.13 | 15-JUL-07:03 | 11099.02 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.297632E+11 | 0.731927E+10 | 494.00 | 0.203991E+11 | 0.936409E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 50955.17 | 17-AUG-07:02 | 36632.42 | 22-AUG-07:02 | 24245.46 | 17-AUG-07:03 | 11128.08 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.135911E+11 | 0.340207E+10 | 381.83 | 0.968079E+10 | 0.391030E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 50203.74 | 14-SEP-07:02 | 37712.80 | 04-SEP-07:02 | 22273.63 | 13-SEP-07:03 | 10855.85 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.366940E+10 | 0.932966E+09 | 167.91 | 0.246583E+10 | 0.120357E+10 | 0.00 | 0.93 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 21967.29 | 06-OCT-07:03 | 12638.61 | 04-OCT-13:20 | 10770.60 | 06-OCT-07:03 | 4815.20 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.100286E+12 | 0.247700E+11 | 2183.96 | 0.671733E+11 | 0.331129E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.316152E+11 | 0.764037E+10 | 496.96 | 0.203991E+11 | 0.121561E+11 | 0.00 | 1.00 | 0.00 | 51478.60 | 37712.80 | 28318.13 | 11205.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 9903794.29 | 2736832.04 | 3.47 | 7619830.01 | 2283964.28 | 0.00 | 0.19 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1834.78 | 27-MAR-16:10 | 1356.94 | 27-MAR-16:10 | 477.84 | 27-MAR-16:10 | 501.67 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.460063E+09 | 0.119899E+09 | 46.59 | 0.401430E+09 | 58633546.35 | 0.00 | 1.00 | 07-APR-20:01 | 0.00 | 01-APR-00:05 | 23566.08 | 07-APR-20:01 | 21901.09 | 16-APR-17:01 | 4221.01 | 07-APR-20:40 | 5033.61 | 07-APR-20:01 | 0.00 | 01-APR-00:05 |
May | 0.238665E+10 | 0.600628E+09 | 183.46 | 0.207482E+10 | 0.311826E+09 | 0.00 | 1.00 | 09-MAY-20:01 | 0.00 | 01-MAY-00:10 | 24005.31 | 30-MAY-20:02 | 22503.39 | 20-MAY-19:10 | 6927.15 | 30-MAY-20:57 | 5109.66 | 30-MAY-20:02 | 0.00 | 01-MAY-00:10 |
June | 0.101753E+11 | 0.248753E+10 | 443.06 | 0.705500E+10 | 0.312030E+10 | 0.00 | 1.00 | 01-JUN-20:22 | 0.00 | 01-JUN-00:10 | 25496.86 | 27-JUN-07:02 | 21082.28 | 01-JUN-20:28 | 12154.36 | 11-JUN-18:04 | 5733.42 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.162647E+11 | 0.388747E+10 | 498.16 | 0.105228E+11 | 0.574189E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 26081.17 | 22-JUL-07:02 | 21442.79 | 12-JUL-07:02 | 9884.44 | 22-JUL-07:03 | 5695.60 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.154813E+11 | 0.375968E+10 | 490.06 | 0.110454E+11 | 0.443590E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25763.43 | 17-AUG-07:02 | 23094.66 | 24-AUG-21:47 | 8662.46 | 17-AUG-07:03 | 5719.16 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.790441E+10 | 0.192951E+10 | 383.20 | 0.584846E+10 | 0.205595E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 25586.02 | 14-SEP-07:02 | 22669.23 | 10-SEP-17:08 | 12309.95 | 22-SEP-20:22 | 5533.19 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.251040E+10 | 0.617032E+09 | 188.08 | 0.171566E+10 | 0.794736E+09 | 0.00 | 1.00 | 03-OCT-20:02 | 0.00 | 01-OCT-00:10 | 25158.98 | 23-OCT-20:10 | 22503.39 | 25-OCT-20:07 | 13900.03 | 23-OCT-20:10 | 5305.98 | 23-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 6507810.55 | 1800802.65 | 3.61 | 5676797.66 | 831012.88 | 0.00 | 0.28 | 11-NOV-18:17 | 0.00 | 01-NOV-00:10 | 2611.97 | 11-NOV-18:17 | 2196.65 | 11-NOV-18:17 | 415.32 | 11-NOV-18:17 | 690.92 | 11-NOV-18:17 | 0.00 | 01-NOV-00:10 |
December | 73768.35 | 20814.07 | 0.33 | 72404.89 | 1363.46 | 0.00 | 0.01 | 17-DEC-21:30 | 0.00 | 01-DEC-00:03 | 63.36 | 17-DEC-21:30 | 61.08 | 17-DEC-21:30 | 2.27 | 17-DEC-21:30 | 17.88 | 17-DEC-21:30 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.551992E+11 | 0.134063E+11 | 2240.01 | 0.386769E+11 | 0.165224E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.162647E+11 | 0.388747E+10 | 498.16 | 0.110454E+11 | 0.574189E+10 | 0.00 | 1.00 | 0.00 | 26081.17 | 23094.66 | 13900.03 | 5733.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 3113592.86 | 873117.26 | 1.50 | 2308394.52 | 805198.34 | 0.00 | 0.12 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1139.37 | 27-MAR-16:10 | 841.61 | 27-MAR-16:10 | 297.76 | 27-MAR-16:10 | 317.35 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.329876E+09 | 88022227.40 | 36.50 | 0.287631E+09 | 42244734.30 | 0.00 | 0.57 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 6020.54 | 08-APR-12:10 | 5223.93 | 07-APR-13:00 | 1083.54 | 09-APR-11:00 | 1532.05 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.158643E+10 | 0.412983E+09 | 149.69 | 0.139085E+10 | 0.195577E+09 | 0.00 | 0.88 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 10181.81 | 30-MAY-06:03 | 8624.78 | 30-MAY-13:00 | 3719.99 | 31-MAY-06:03 | 2404.24 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.775612E+10 | 0.190460E+10 | 345.60 | 0.529689E+10 | 0.245924E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 27131.92 | 25-JUN-07:02 | 20570.21 | 23-JUN-06:03 | 14677.95 | 16-JUN-06:03 | 5691.09 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.128540E+11 | 0.305332E+10 | 363.34 | 0.809521E+10 | 0.475876E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27236.70 | 21-JUL-06:02 | 20535.28 | 12-JUL-06:02 | 15090.32 | 24-JUL-06:03 | 5774.70 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.122569E+11 | 0.296714E+10 | 367.79 | 0.861123E+10 | 0.364567E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27412.88 | 06-AUG-07:02 | 21231.31 | 31-AUG-06:03 | 14197.63 | 06-AUG-07:03 | 5769.13 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.579391E+10 | 0.142264E+10 | 293.46 | 0.421710E+10 | 0.157681E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26765.72 | 14-SEP-06:02 | 21341.23 | 04-SEP-07:02 | 13782.82 | 22-SEP-06:03 | 5649.97 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.183815E+10 | 0.458493E+09 | 154.17 | 0.125614E+10 | 0.582012E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 16415.35 | 06-OCT-06:03 | 8483.72 | 06-OCT-06:03 | 7931.63 | 06-OCT-06:03 | 3460.56 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 203542.57 | 57562.29 | 0.67 | 163426.93 | 40115.64 | 0.00 | 0.02 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 130.95 | 04-NOV-13:00 | 104.67 | 04-NOV-13:00 | 26.28 | 04-NOV-13:00 | 37.01 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.424187E+11 | 0.103081E+11 | 1712.72 | 0.291575E+11 | 0.132612E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.128540E+11 | 0.305332E+10 | 367.79 | 0.861123E+10 | 0.475876E+10 | 0.00 | 1.00 | 0.00 | 27412.88 | 21341.23 | 15090.32 | 5774.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 1702601.18 | 480323.08 | 1.33 | 1260512.40 | 442088.78 | 0.00 | 0.09 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 839.20 | 27-MAR-16:10 | 619.17 | 27-MAR-16:10 | 220.03 | 27-MAR-16:10 | 235.60 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.307730E+09 | 82399155.30 | 34.67 | 0.268547E+09 | 39183564.92 | 0.00 | 0.56 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5857.87 | 08-APR-12:10 | 5047.46 | 07-APR-13:00 | 1003.01 | 08-APR-13:00 | 1496.19 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.154133E+10 | 0.401527E+09 | 143.36 | 0.135054E+10 | 0.190795E+09 | 0.00 | 0.85 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 9918.70 | 31-MAY-14:00 | 8588.20 | 30-MAY-13:00 | 3638.00 | 31-MAY-06:03 | 2395.38 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.772208E+10 | 0.189659E+10 | 345.24 | 0.527289E+10 | 0.244919E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 27103.04 | 25-JUN-07:02 | 20828.66 | 23-JUN-06:03 | 14664.42 | 16-JUN-06:03 | 5685.12 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.128565E+11 | 0.305338E+10 | 363.65 | 0.809893E+10 | 0.475761E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27213.85 | 21-JUL-06:02 | 20535.95 | 12-JUL-06:02 | 15073.12 | 24-JUL-06:03 | 5768.62 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.122757E+11 | 0.297085E+10 | 367.94 | 0.862790E+10 | 0.364784E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27388.51 | 06-AUG-07:02 | 21295.74 | 31-AUG-06:03 | 14146.89 | 06-AUG-07:03 | 5763.15 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.577626E+10 | 0.141817E+10 | 291.26 | 0.420439E+10 | 0.157188E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26739.00 | 14-SEP-06:02 | 21344.46 | 04-SEP-07:02 | 13773.17 | 22-SEP-06:03 | 5644.28 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.177881E+10 | 0.444210E+09 | 149.00 | 0.121474E+10 | 0.564063E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 16204.40 | 06-OCT-06:03 | 8369.26 | 06-OCT-06:03 | 7835.14 | 06-OCT-06:03 | 3416.22 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.422602E+11 | 0.102676E+11 | 1696.45 | 0.290392E+11 | 0.132210E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.128565E+11 | 0.305338E+10 | 367.94 | 0.862790E+10 | 0.475761E+10 | 0.00 | 1.00 | 0.00 | 27388.51 | 21344.46 | 15073.12 | 5768.62 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 728794.02 | 206961.22 | 0.83 | 537530.82 | 191263.20 | 0.00 | 0.06 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 507.35 | 27-MAR-16:10 | 373.45 | 27-MAR-16:10 | 133.90 | 27-MAR-16:10 | 143.70 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.270641E+09 | 72942939.54 | 32.17 | 0.236495E+09 | 34146109.31 | 0.00 | 0.54 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5526.80 | 08-APR-12:10 | 4745.60 | 07-APR-13:00 | 1015.22 | 08-APR-13:00 | 1422.06 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.143490E+10 | 0.374850E+09 | 133.53 | 0.125402E+10 | 0.180877E+09 | 0.00 | 0.83 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 9738.93 | 31-MAY-14:00 | 8432.55 | 30-MAY-13:00 | 2913.57 | 31-MAY-13:00 | 2360.59 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.748222E+10 | 0.184248E+10 | 341.14 | 0.509231E+10 | 0.238991E+10 | 0.00 | 1.00 | 15-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26982.09 | 25-JUN-07:02 | 18776.52 | 23-JUN-06:03 | 14653.69 | 16-JUN-06:03 | 5662.49 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.126177E+11 | 0.300192E+10 | 364.14 | 0.791726E+10 | 0.470044E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27094.52 | 21-JUL-06:02 | 20322.56 | 12-JUL-06:02 | 15050.81 | 24-JUL-06:03 | 5745.94 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.120514E+11 | 0.292083E+10 | 367.20 | 0.844193E+10 | 0.360943E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27268.66 | 06-AUG-07:02 | 19514.79 | 31-AUG-06:03 | 14222.06 | 06-AUG-07:03 | 5740.28 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.559234E+10 | 0.137624E+10 | 289.73 | 0.405828E+10 | 0.153406E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26624.56 | 14-SEP-06:02 | 21149.27 | 04-SEP-07:02 | 13771.30 | 22-SEP-06:03 | 5621.42 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.165104E+10 | 0.413449E+09 | 140.17 | 0.112669E+10 | 0.524347E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 14219.60 | 06-OCT-06:03 | 7287.39 | 06-OCT-06:03 | 6932.22 | 06-OCT-06:03 | 2999.21 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.411009E+11 | 0.100029E+11 | 1668.90 | 0.281275E+11 | 0.129734E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.126177E+11 | 0.300192E+10 | 367.20 | 0.844193E+10 | 0.470044E+10 | 0.00 | 1.00 | 0.00 | 27268.66 | 21149.27 | 15050.81 | 5745.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 336645.00 | 98043.97 | 0.50 | 241076.48 | 95568.52 | 0.00 | 0.02 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 282.14 | 27-MAR-16:00 | 201.46 | 27-MAR-16:00 | 80.68 | 27-MAR-16:00 | 82.24 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.420880E+09 | 0.116176E+09 | 29.50 | 0.362766E+09 | 58113940.63 | 0.00 | 0.50 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 9337.75 | 08-APR-12:00 | 8150.34 | 07-APR-13:00 | 1725.66 | 08-APR-13:00 | 2485.96 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.234244E+10 | 0.622741E+09 | 113.69 | 0.200271E+10 | 0.339729E+09 | 0.00 | 0.90 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 19220.41 | 31-MAY-07:03 | 15513.65 | 31-MAY-07:03 | 5862.56 | 31-MAY-13:00 | 4473.70 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.129642E+11 | 0.324596E+10 | 326.12 | 0.859102E+10 | 0.437317E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 48987.70 | 25-JUN-08:62 | 33782.02 | 23-JUN-07:03 | 25699.07 | 16-JUN-07:03 | 10683.49 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.224310E+11 | 0.541021E+10 | 350.76 | 0.136843E+11 | 0.874666E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 49013.06 | 09-JUL-08:62 | 36579.28 | 12-JUL-07:02 | 27892.22 | 24-JUL-07:03 | 10657.05 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.217524E+11 | 0.535643E+10 | 361.47 | 0.148849E+11 | 0.686757E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48468.36 | 06-AUG-08:62 | 34486.76 | 22-AUG-07:02 | 28438.25 | 06-AUG-08:62 | 10604.09 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.969317E+10 | 0.242548E+10 | 275.90 | 0.685042E+10 | 0.284275E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 47812.22 | 14-SEP-07:02 | 37245.99 | 04-SEP-08:62 | 20957.39 | 14-SEP-07:02 | 10360.50 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.269121E+10 | 0.686344E+09 | 124.00 | 0.178629E+10 | 0.904919E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 23026.49 | 06-OCT-07:03 | 11839.29 | 04-OCT-13:00 | 11235.78 | 06-OCT-07:03 | 4941.02 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.722957E+11 | 0.178634E+11 | 1581.94 | 0.481627E+11 | 0.241330E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.224310E+11 | 0.541021E+10 | 361.47 | 0.148849E+11 | 0.874666E+10 | 0.00 | 1.00 | 0.00 | 49013.06 | 37245.99 | 28438.25 | 10683.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 41055.52 | 11761.08 | 0.33 | 29570.40 | 11485.12 | 0.00 | 0.01 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 68.26 | 27-MAR-16:10 | 49.17 | 27-MAR-16:10 | 19.09 | 27-MAR-16:10 | 19.55 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.203970E+09 | 55465305.20 | 27.17 | 0.176517E+09 | 27452988.29 | 0.00 | 0.49 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4706.95 | 08-APR-12:00 | 4082.63 | 07-APR-13:00 | 855.70 | 08-APR-13:00 | 1230.46 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.117091E+10 | 0.306150E+09 | 109.36 | 0.100320E+10 | 0.167710E+09 | 0.00 | 0.84 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9319.25 | 31-MAY-14:10 | 7994.47 | 30-MAY-13:00 | 2986.59 | 31-MAY-13:00 | 2266.85 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.661227E+10 | 0.162944E+10 | 324.97 | 0.439833E+10 | 0.221393E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25353.62 | 25-JUN-08:62 | 16783.02 | 20-JUN-07:02 | 13212.98 | 25-JUN-08:62 | 5431.37 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.115033E+11 | 0.273089E+10 | 350.77 | 0.704652E+10 | 0.445679E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25372.82 | 09-JUL-08:62 | 18978.36 | 12-JUL-07:02 | 14417.09 | 24-JUL-07:03 | 5417.83 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.111517E+11 | 0.270269E+10 | 361.51 | 0.765858E+10 | 0.349317E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25084.70 | 06-AUG-08:62 | 17929.82 | 22-AUG-07:02 | 14707.09 | 06-AUG-08:62 | 5390.98 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.495310E+10 | 0.121929E+10 | 274.11 | 0.351409E+10 | 0.143901E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24731.15 | 14-SEP-07:02 | 19299.63 | 04-SEP-08:62 | 10800.96 | 14-SEP-07:02 | 5266.67 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.134889E+10 | 0.338176E+09 | 120.50 | 0.899275E+09 | 0.449616E+09 | 0.00 | 0.90 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 10283.39 | 06-OCT-07:03 | 6095.90 | 04-OCT-13:00 | 5011.61 | 06-OCT-07:03 | 2241.27 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.369442E+11 | 0.898211E+10 | 1568.72 | 0.246965E+11 | 0.122477E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.115033E+11 | 0.273089E+10 | 361.51 | 0.765858E+10 | 0.445679E+10 | 0.00 | 1.00 | 0.00 | 25372.82 | 19299.63 | 14707.09 | 5431.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 81.12 | 23.28 | 0.17 | 58.27 | 22.84 | 0.00 | 0.00 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.14 | 27-MAR-16:10 | 0.10 | 27-MAR-16:10 | 0.04 | 27-MAR-16:10 | 0.04 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.193904E+09 | 52836281.41 | 26.17 | 0.167739E+09 | 26165466.92 | 0.00 | 0.48 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4595.83 | 08-APR-12:00 | 3980.19 | 07-APR-13:00 | 834.07 | 08-APR-13:00 | 1204.36 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.112615E+10 | 0.294797E+09 | 105.86 | 0.962919E+09 | 0.163228E+09 | 0.00 | 0.84 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9236.21 | 31-MAY-14:10 | 7907.64 | 30-MAY-13:00 | 2967.85 | 31-MAY-13:00 | 2246.27 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.652139E+10 | 0.160825E+10 | 323.33 | 0.433155E+10 | 0.218984E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25256.53 | 25-JUN-08:62 | 16663.83 | 20-JUN-07:02 | 13209.29 | 25-JUN-08:62 | 5411.43 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.114081E+11 | 0.270909E+10 | 350.64 | 0.697534E+10 | 0.443274E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25277.01 | 09-JUL-08:62 | 18859.22 | 12-JUL-07:02 | 14378.01 | 24-JUL-07:03 | 5397.96 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.110689E+11 | 0.268325E+10 | 361.38 | 0.759104E+10 | 0.347789E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24991.85 | 06-AUG-08:62 | 17840.93 | 22-AUG-07:02 | 14665.01 | 06-AUG-08:62 | 5371.18 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.489059E+10 | 0.120458E+10 | 272.75 | 0.346509E+10 | 0.142550E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24641.16 | 14-SEP-07:02 | 19184.33 | 04-SEP-08:62 | 10816.75 | 14-SEP-07:02 | 5247.27 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.129825E+10 | 0.325848E+09 | 117.97 | 0.864579E+09 | 0.433674E+09 | 0.00 | 0.84 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 9404.94 | 06-OCT-07:03 | 6019.33 | 04-OCT-13:00 | 4588.26 | 06-OCT-07:03 | 2088.33 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.365073E+11 | 0.887865E+10 | 1558.27 | 0.243583E+11 | 0.121490E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114081E+11 | 0.270909E+10 | 361.38 | 0.759104E+10 | 0.443274E+10 | 0.00 | 1.00 | 0.00 | 25277.01 | 19184.33 | 14665.01 | 5411.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.169914E+09 | 46517375.69 | 24.67 | 0.146911E+09 | 23002353.14 | 0.00 | 0.46 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4356.76 | 08-APR-12:00 | 3769.79 | 07-APR-13:00 | 788.39 | 08-APR-13:00 | 1148.51 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.102888E+10 | 0.270153E+09 | 96.86 | 0.874905E+09 | 0.153978E+09 | 0.00 | 0.83 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9082.89 | 31-MAY-14:10 | 7749.16 | 30-MAY-13:00 | 2934.29 | 31-MAY-13:00 | 2211.58 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.630441E+10 | 0.155826E+10 | 317.36 | 0.417549E+10 | 0.212892E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25163.24 | 25-JUN-08:62 | 16464.54 | 20-JUN-07:02 | 13322.58 | 25-JUN-08:62 | 5395.68 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.112588E+11 | 0.267617E+10 | 351.34 | 0.686443E+10 | 0.439439E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 25187.97 | 09-JUL-08:62 | 18657.80 | 12-JUL-07:02 | 14384.59 | 24-JUL-07:03 | 5382.49 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.109654E+11 | 0.265921E+10 | 361.25 | 0.750285E+10 | 0.346251E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24915.52 | 06-AUG-08:62 | 17722.06 | 22-AUG-07:02 | 14649.57 | 06-AUG-08:62 | 5355.46 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.476941E+10 | 0.117597E+10 | 269.71 | 0.337139E+10 | 0.139802E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24563.91 | 14-SEP-07:02 | 19001.87 | 04-SEP-08:62 | 10932.34 | 14-SEP-07:02 | 5231.23 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.119512E+10 | 0.300526E+09 | 109.83 | 0.795162E+09 | 0.399955E+09 | 0.00 | 0.76 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 8115.44 | 04-OCT-13:00 | 5891.61 | 04-OCT-13:00 | 3239.70 | 06-OCT-07:03 | 1953.08 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.356919E+11 | 0.868681E+10 | 1531.02 | 0.237311E+11 | 0.119608E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112588E+11 | 0.267617E+10 | 361.25 | 0.750285E+10 | 0.439439E+10 | 0.00 | 1.00 | 0.00 | 25187.97 | 19001.87 | 14649.57 | 5395.68 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.153999E+09 | 42374647.47 | 20.17 | 0.133764E+09 | 20234601.22 | 0.00 | 0.45 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4559.36 | 08-APR-12:00 | 3912.25 | 07-APR-13:00 | 773.84 | 08-APR-12:50 | 1206.07 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.969371E+09 | 0.255654E+09 | 87.22 | 0.826423E+09 | 0.142948E+09 | 0.00 | 0.80 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 9195.56 | 31-MAY-14:10 | 8142.86 | 30-MAY-13:00 | 2949.40 | 31-MAY-13:00 | 2327.41 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.613054E+10 | 0.152887E+10 | 299.44 | 0.410217E+10 | 0.202837E+10 | 0.00 | 1.00 | 15-JUN-11:40 | 0.00 | 01-JUN-00:10 | 27254.39 | 25-JUN-08:62 | 16871.85 | 20-JUN-07:02 | 15151.03 | 25-JUN-08:62 | 5818.99 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.117468E+11 | 0.280811E+10 | 351.08 | 0.723260E+10 | 0.451418E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 27579.71 | 22-JUL-07:02 | 17846.85 | 12-JUL-07:02 | 15989.92 | 22-JUL-07:02 | 5802.82 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.116648E+11 | 0.283649E+10 | 361.74 | 0.806249E+10 | 0.360228E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27307.30 | 17-AUG-07:02 | 19232.83 | 22-AUG-07:02 | 16001.34 | 06-AUG-08:62 | 5776.72 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.485268E+10 | 0.119927E+10 | 255.95 | 0.347261E+10 | 0.138007E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 26858.09 | 14-SEP-07:02 | 19837.63 | 04-SEP-08:62 | 13586.92 | 14-SEP-07:02 | 5660.01 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.113508E+10 | 0.285829E+09 | 96.56 | 0.765523E+09 | 0.369554E+09 | 0.00 | 0.75 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 8537.78 | 04-OCT-13:00 | 6273.63 | 04-OCT-13:00 | 2753.98 | 24-OCT-12:50 | 2065.09 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.366532E+11 | 0.895660E+10 | 1472.15 | 0.245956E+11 | 0.120576E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.117468E+11 | 0.283649E+10 | 361.74 | 0.806249E+10 | 0.451418E+10 | 0.00 | 1.00 | 0.00 | 27579.71 | 19837.63 | 16001.34 | 5818.99 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.75 | 82.84 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.24 | 81.37 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.80 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.72 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.60 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.47 | 15.55 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.16 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.08 | 11.52 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.63 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.15 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.14 | 60.14 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.33 | 75.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.86 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.60 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.15 | 82.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.75 | 82.84 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.24 | 81.37 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.80 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.72 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.60 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.47 | 15.55 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.16 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.08 | 11.52 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.63 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.15 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.14 | 60.14 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.33 | 75.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.86 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.60 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.15 | 82.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.75 | 82.84 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.24 | 81.37 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.80 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.72 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.60 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.47 | 15.55 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.16 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.08 | 11.52 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.63 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.15 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.14 | 60.14 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.33 | 75.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.86 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.60 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.15 | 82.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.75 | 82.84 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.24 | 81.37 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.80 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.72 | 43.52 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.60 | 28.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.47 | 15.55 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.16 | 7.73 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.08 | 11.52 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.63 | 23.95 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.15 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.14 | 60.14 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.33 | 75.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.86 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.60 | 7.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.15 | 82.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 104.71 | 98.31 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 141.45 | 96.59 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 136.05 | 69.22 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 109.40 | 51.75 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 100.74 | 34.32 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.58 | 18.60 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 125.06 | 9.31 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 166.99 | 13.88 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.68 | 28.64 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 206.02 | 51.30 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 124.33 | 71.52 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 118.57 | 89.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 133.49 | 52.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 100.74 | 9.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 206.02 | 98.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 104.71 | 98.31 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 141.45 | 96.59 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 136.05 | 69.22 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 109.40 | 51.75 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 100.74 | 34.32 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.58 | 18.60 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 125.06 | 9.31 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 166.99 | 13.88 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.68 | 28.64 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 206.02 | 51.30 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 124.33 | 71.52 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 118.57 | 89.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 133.49 | 52.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 100.74 | 9.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 206.02 | 98.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.76 | 87.04 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.91 | 85.70 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.46 | 62.56 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.28 | 47.14 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.20 | 30.64 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.14 | 15.99 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.10 | 7.91 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.10 | 11.60 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.37 | 24.32 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.11 | 44.69 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.75 | 64.05 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.32 | 79.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.98 | 46.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.20 | 7.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.11 | 87.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.76 | 87.04 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.91 | 85.70 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.46 | 62.56 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.28 | 47.14 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.20 | 30.64 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.14 | 15.99 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.10 | 7.91 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.10 | 11.60 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.37 | 24.32 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.11 | 44.69 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.75 | 64.05 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.32 | 79.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.98 | 46.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.20 | 7.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.11 | 87.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 103.56 | 103.25 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 139.89 | 101.69 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 134.48 | 74.20 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 107.70 | 55.99 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 99.10 | 36.48 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.21 | 19.11 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 125.00 | 9.53 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 167.04 | 13.97 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.39 | 29.08 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 204.82 | 53.28 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 122.69 | 76.12 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 117.39 | 94.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 132.46 | 55.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 99.10 | 9.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 204.82 | 103.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.96 | 84.65 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.06 | 83.62 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.74 | 60.69 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.64 | 45.84 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.37 | 30.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.97 | 17.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.70 | 9.40 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.73 | 13.19 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.30 | 25.65 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.36 | 44.90 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.16 | 62.29 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.52 | 77.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.06 | 46.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.37 | 9.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.36 | 84.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.96 | 84.65 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.06 | 83.62 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.74 | 60.69 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.64 | 45.84 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.37 | 30.81 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.97 | 17.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.70 | 9.40 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.73 | 13.19 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.30 | 25.65 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.36 | 44.90 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.16 | 62.29 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.52 | 77.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.06 | 46.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.37 | 9.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.36 | 84.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.23 | 99.89 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.30 | 98.69 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.07 | 71.61 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 107.53 | 54.17 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 98.76 | 36.47 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.42 | 20.37 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.86 | 11.22 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.69 | 15.76 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.43 | 30.47 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.00 | 53.22 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 122.53 | 73.64 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 116.99 | 91.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 131.84 | 54.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 98.76 | 11.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.00 | 99.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.09 | 83.65 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.20 | 82.74 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.92 | 59.87 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.88 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.63 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.99 | 17.11 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.71 | 13.27 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.32 | 25.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.52 | 44.48 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.44 | 61.35 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.65 | 76.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.19 | 45.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.63 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.52 | 83.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.09 | 83.65 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.20 | 82.74 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.92 | 59.87 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.88 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.63 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.99 | 17.11 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.71 | 13.27 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.32 | 25.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.52 | 44.48 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.44 | 61.35 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.65 | 76.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.19 | 45.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.63 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.52 | 83.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.39 | 98.71 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.47 | 97.66 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.29 | 70.64 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 107.83 | 53.29 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 99.07 | 35.91 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.45 | 20.32 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.84 | 11.27 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.66 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.46 | 30.41 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.19 | 52.73 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 122.86 | 72.53 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.14 | 90.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 131.99 | 53.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 99.07 | 11.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.19 | 98.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.25 | 82.83 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.39 | 82.00 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.14 | 59.16 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.21 | 44.38 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.07 | 29.66 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.13 | 16.85 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.81 | 9.22 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.81 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.42 | 25.30 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.77 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.78 | 60.47 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.80 | 75.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.40 | 45.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.07 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.77 | 82.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.25 | 82.83 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.39 | 82.00 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.14 | 59.16 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.21 | 44.38 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.07 | 29.66 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.13 | 16.85 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.81 | 9.22 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.81 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.42 | 25.30 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.77 | 43.95 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.78 | 60.47 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.80 | 75.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.40 | 45.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.07 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.77 | 82.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.59 | 97.73 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.71 | 96.77 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.56 | 69.80 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.22 | 52.44 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 99.60 | 35.12 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.61 | 20.01 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.99 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.79 | 15.57 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.58 | 30.06 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.49 | 52.10 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.27 | 71.50 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.33 | 89.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.25 | 53.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 99.60 | 11.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.49 | 97.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.00 | 80.37 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 79.75 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.92 | 57.24 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.67 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.90 | 28.24 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 8.54 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.72 | 12.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.52 | 24.50 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.29 | 42.78 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.58 | 58.54 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.49 | 73.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.91 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.90 | 8.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.29 | 80.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.00 | 80.37 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 79.75 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.92 | 57.24 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.67 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.90 | 28.24 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 8.54 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.72 | 12.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.52 | 24.50 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.29 | 42.78 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.58 | 58.54 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.49 | 73.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.91 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.90 | 8.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.29 | 80.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.00 | 80.37 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 79.75 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.92 | 57.24 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.67 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.90 | 28.24 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 8.54 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.72 | 12.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.52 | 24.50 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.29 | 42.78 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.58 | 58.54 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.49 | 73.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.91 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.90 | 8.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.29 | 80.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.00 | 80.37 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 79.75 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.92 | 57.24 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.67 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.90 | 28.24 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.69 | 8.54 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.72 | 12.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.52 | 24.50 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.29 | 42.78 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.58 | 58.54 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.49 | 73.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.91 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.90 | 8.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.29 | 80.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.45 | 94.86 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.79 | 94.15 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.45 | 67.56 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 109.15 | 50.46 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.56 | 33.46 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.72 | 19.09 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.84 | 10.20 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.67 | 14.71 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.68 | 29.11 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.07 | 50.73 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.19 | 69.23 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 118.12 | 87.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.83 | 51.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.56 | 10.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.07 | 94.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.45 | 94.86 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.79 | 94.15 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.45 | 67.56 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 109.15 | 50.46 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.56 | 33.46 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.72 | 19.09 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.84 | 10.20 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.67 | 14.71 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.68 | 29.11 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.07 | 50.73 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.19 | 69.23 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 118.12 | 87.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.83 | 51.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.56 | 10.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.07 | 94.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.69 | 80.82 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.98 | 80.11 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.61 | 57.36 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.85 | 42.60 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.92 | 27.99 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 15.85 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.78 | 8.26 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.79 | 12.00 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.43 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.08 | 42.57 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.41 | 58.55 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.23 | 74.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.77 | 43.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.92 | 8.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.08 | 80.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.69 | 80.82 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.98 | 80.11 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.61 | 57.36 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.85 | 42.60 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.92 | 27.99 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.23 | 15.85 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.78 | 8.26 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.79 | 12.00 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.43 | 24.26 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.08 | 42.57 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.41 | 58.55 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.23 | 74.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.77 | 43.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.92 | 8.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.08 | 80.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.12 | 95.35 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.41 | 94.54 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.13 | 67.67 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.99 | 50.34 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.61 | 33.14 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.75 | 18.84 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.97 | 9.88 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.77 | 14.35 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.60 | 28.82 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.88 | 50.47 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.02 | 69.22 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.84 | 87.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.70 | 51.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.61 | 9.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.88 | 95.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.74 | 80.60 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.05 | 79.86 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.71 | 57.07 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.27 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.20 | 27.63 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.32 | 15.75 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.85 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.85 | 11.92 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.49 | 24.14 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.24 | 42.30 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.54 | 58.26 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.30 | 73.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.88 | 43.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.20 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.24 | 80.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.74 | 80.60 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.05 | 79.86 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.71 | 57.07 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.01 | 42.27 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.20 | 27.63 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.32 | 15.75 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.85 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.85 | 11.92 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.49 | 24.14 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.24 | 42.30 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.54 | 58.26 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.30 | 73.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.88 | 43.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.20 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.24 | 80.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.18 | 95.09 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.50 | 94.24 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.25 | 67.33 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 109.18 | 49.96 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.94 | 32.72 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.85 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.05 | 9.79 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.85 | 14.25 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.68 | 28.68 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.06 | 50.15 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.17 | 68.87 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.93 | 87.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.83 | 51.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.94 | 9.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.06 | 95.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.94 | 79.54 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 78.73 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 113.02 | 55.98 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.43 | 41.26 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.85 | 26.73 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.51 | 15.46 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.94 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.90 | 11.79 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.61 | 23.85 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.59 | 41.61 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.86 | 57.37 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.54 | 72.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.15 | 42.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.85 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.59 | 79.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.94 | 79.54 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.33 | 78.73 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 113.02 | 55.98 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.43 | 41.26 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.85 | 26.73 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.51 | 15.46 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.94 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.90 | 11.79 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.61 | 23.85 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.59 | 41.61 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.86 | 57.37 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.54 | 72.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.15 | 42.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.85 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.59 | 79.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.42 | 93.84 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.84 | 92.90 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.63 | 66.04 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 109.69 | 48.77 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 101.72 | 31.66 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 107.07 | 18.37 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.17 | 9.61 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.91 | 14.11 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.82 | 28.34 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.48 | 49.34 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.56 | 67.82 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 118.22 | 85.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 133.15 | 50.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 101.72 | 9.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.48 | 93.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.72 | 74.97 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 118.41 | 73.89 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 114.05 | 51.59 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 92.48 | 37.61 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 86.29 | 24.08 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.98 | 14.29 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.91 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.66 | 11.43 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.78 | 22.84 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 172.30 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 104.73 | 54.20 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 99.39 | 68.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.83 | 39.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 86.29 | 7.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 172.30 | 74.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.72 | 74.97 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 118.41 | 73.89 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 114.05 | 51.59 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 92.48 | 37.61 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 86.29 | 24.08 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.98 | 14.29 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.91 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.66 | 11.43 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.78 | 22.84 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 172.30 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 104.73 | 54.20 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 99.39 | 68.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.83 | 39.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 86.29 | 7.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 172.30 | 74.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 105.36 | 88.44 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 142.15 | 87.17 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 136.88 | 60.86 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 110.96 | 44.47 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 103.44 | 28.54 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 107.64 | 17.00 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.13 | 9.07 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.61 | 13.67 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 160.02 | 27.15 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 206.33 | 46.82 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 125.61 | 64.08 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 119.25 | 80.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 133.97 | 47.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 103.44 | 9.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 206.33 | 88.44 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232350E+09 | 0.221878E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283634E+09 | 0.196853E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302117E+09 | 0.156184E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235159E+09 | 0.112814E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223901E+09 | 77159193.51 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231906E+09 | 40316043.41 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278981E+09 | 20707625.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372505E+09 | 30865455.82 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346371E+09 | 62067315.03 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458396E+09 | 0.115180E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267340E+09 | 0.155871E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263356E+09 | 0.201790E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349602E+10 | 0.139168E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223901E+09 | 20707625.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458396E+09 | 0.221878E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232350E+09 | 0.221878E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283634E+09 | 0.196853E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302117E+09 | 0.156184E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235159E+09 | 0.112814E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223901E+09 | 77159193.51 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231906E+09 | 40316043.41 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278981E+09 | 20707625.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372505E+09 | 30865455.82 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346371E+09 | 62067315.03 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458396E+09 | 0.115180E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267340E+09 | 0.155871E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263356E+09 | 0.201790E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349602E+10 | 0.139168E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223901E+09 | 20707625.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458396E+09 | 0.221878E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232350E+09 | 0.221878E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283634E+09 | 0.196853E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302117E+09 | 0.156184E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235159E+09 | 0.112814E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223901E+09 | 77159193.51 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231906E+09 | 40316043.41 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278981E+09 | 20707625.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372505E+09 | 30865455.82 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346371E+09 | 62067315.03 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458396E+09 | 0.115180E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267340E+09 | 0.155871E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263356E+09 | 0.201790E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349602E+10 | 0.139168E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223901E+09 | 20707625.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458396E+09 | 0.221878E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232350E+09 | 0.221878E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283634E+09 | 0.196853E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302117E+09 | 0.156184E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235159E+09 | 0.112814E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223901E+09 | 77159193.51 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231906E+09 | 40316043.41 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278981E+09 | 20707625.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372505E+09 | 30865455.82 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346371E+09 | 62067315.03 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458396E+09 | 0.115180E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267340E+09 | 0.155871E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263356E+09 | 0.201790E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349602E+10 | 0.139168E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223901E+09 | 20707625.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458396E+09 | 0.221878E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.280462E+09 | 0.263313E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.342196E+09 | 0.233668E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.364393E+09 | 0.185392E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.283569E+09 | 0.134132E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.269814E+09 | 91931272.31 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.278860E+09 | 48214212.52 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334973E+09 | 24948303.64 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447263E+09 | 37166121.94 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.416481E+09 | 74222203.02 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.551804E+09 | 0.137392E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.322268E+09 | 0.185384E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.317572E+09 | 0.239700E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.420965E+10 | 0.165546E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.269814E+09 | 24948303.64 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.551804E+09 | 0.263313E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.280462E+09 | 0.263313E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.342196E+09 | 0.233668E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.364393E+09 | 0.185392E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.283569E+09 | 0.134132E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.269814E+09 | 91931272.31 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.278860E+09 | 48214212.52 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334973E+09 | 24948303.64 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447263E+09 | 37166121.94 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.416481E+09 | 74222203.02 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.551804E+09 | 0.137392E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.322268E+09 | 0.185384E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.317572E+09 | 0.239700E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.420965E+10 | 0.165546E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.269814E+09 | 24948303.64 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.551804E+09 | 0.263313E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229713E+09 | 0.233118E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280418E+09 | 0.207336E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.298536E+09 | 0.167561E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.231417E+09 | 0.122177E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220165E+09 | 82063122.70 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231052E+09 | 41442236.52 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278819E+09 | 21199317.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372579E+09 | 31075916.27 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345685E+09 | 63048027.74 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455611E+09 | 0.119692E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.263723E+09 | 0.166027E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260674E+09 | 0.213051E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346839E+10 | 0.146779E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220165E+09 | 21199317.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455611E+09 | 0.233118E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229713E+09 | 0.233118E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280418E+09 | 0.207336E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.298536E+09 | 0.167561E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.231417E+09 | 0.122177E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220165E+09 | 82063122.70 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231052E+09 | 41442236.52 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278819E+09 | 21199317.02 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372579E+09 | 31075916.27 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345685E+09 | 63048027.74 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455611E+09 | 0.119692E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.263723E+09 | 0.166027E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260674E+09 | 0.213051E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346839E+10 | 0.146779E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220165E+09 | 21199317.02 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455611E+09 | 0.233118E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.277367E+09 | 0.276549E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.338418E+09 | 0.246014E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.360181E+09 | 0.198744E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.279153E+09 | 0.145123E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.265421E+09 | 97708131.24 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.277881E+09 | 49543760.80 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334812E+09 | 25536297.98 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447400E+09 | 37424692.61 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.415732E+09 | 75380827.06 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.548601E+09 | 0.142692E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.318022E+09 | 0.197311E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.314426E+09 | 0.252946E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.417741E+10 | 0.174497E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.265421E+09 | 25536297.98 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.548601E+09 | 0.276549E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230226E+09 | 0.226728E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280762E+09 | 0.202285E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299271E+09 | 0.162556E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232336E+09 | 0.118828E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220631E+09 | 82523925.93 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230611E+09 | 44474553.02 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277748E+09 | 25175937.22 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371562E+09 | 35341449.96 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345508E+09 | 66496321.81 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456289E+09 | 0.120250E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.264811E+09 | 0.161445E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261198E+09 | 0.207340E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347095E+10 | 0.145344E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220631E+09 | 25175937.22 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456289E+09 | 0.226728E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230226E+09 | 0.226728E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280762E+09 | 0.202285E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299271E+09 | 0.162556E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232336E+09 | 0.118828E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220631E+09 | 82523925.93 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230611E+09 | 44474553.02 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277748E+09 | 25175937.22 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371562E+09 | 35341449.96 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345508E+09 | 66496321.81 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456289E+09 | 0.120250E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.264811E+09 | 0.161445E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261198E+09 | 0.207340E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347095E+10 | 0.145344E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220631E+09 | 25175937.22 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456289E+09 | 0.226728E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.276478E+09 | 0.267544E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.336993E+09 | 0.238749E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.359098E+09 | 0.191806E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.278727E+09 | 0.140416E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.264528E+09 | 97693077.13 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.275843E+09 | 52804055.74 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331738E+09 | 30050180.98 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443780E+09 | 42220306.22 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413254E+09 | 78985010.76 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.546404E+09 | 0.142540E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.317587E+09 | 0.190872E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.313345E+09 | 0.244878E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.415777E+10 | 0.171856E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.264528E+09 | 30050180.98 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.546404E+09 | 0.267544E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230586E+09 | 0.224061E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281107E+09 | 0.200175E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299755E+09 | 0.160350E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232971E+09 | 0.116891E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.221316E+09 | 81243641.96 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230669E+09 | 44356503.06 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277720E+09 | 25290412.31 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371508E+09 | 35530896.45 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345553E+09 | 66352390.27 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456711E+09 | 0.119147E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265524E+09 | 0.159011E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261537E+09 | 0.205013E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347496E+10 | 0.143742E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.221316E+09 | 25290412.31 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456711E+09 | 0.224061E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230586E+09 | 0.224061E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281107E+09 | 0.200175E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299755E+09 | 0.160350E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232971E+09 | 0.116891E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.221316E+09 | 81243641.96 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230669E+09 | 44356503.06 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277720E+09 | 25290412.31 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371508E+09 | 35530896.45 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345553E+09 | 66352390.27 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456711E+09 | 0.119147E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265524E+09 | 0.159011E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261537E+09 | 0.205013E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347496E+10 | 0.143742E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.221316E+09 | 25290412.31 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456711E+09 | 0.224061E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.276913E+09 | 0.264383E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.337413E+09 | 0.236249E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.359682E+09 | 0.189197E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.279487E+09 | 0.138129E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.265346E+09 | 96181921.94 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.275914E+09 | 52665887.87 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331705E+09 | 30185558.54 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443716E+09 | 42443484.15 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413308E+09 | 78815146.40 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.546907E+09 | 0.141236E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.318442E+09 | 0.187995E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.313756E+09 | 0.242121E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.416259E+10 | 0.169960E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.265346E+09 | 30185558.54 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.546907E+09 | 0.264383E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.231024E+09 | 0.221856E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281578E+09 | 0.198364E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.300354E+09 | 0.158445E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.233817E+09 | 0.115029E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.222505E+09 | 79445751.99 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231018E+09 | 43672286.81 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278036E+09 | 24683029.34 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371784E+09 | 34895039.68 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345827E+09 | 65578800.49 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457384E+09 | 0.117710E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266412E+09 | 0.156746E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261951E+09 | 0.203073E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.348169E+10 | 0.141950E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.222505E+09 | 24683029.34 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457384E+09 | 0.221856E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.231024E+09 | 0.221856E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281578E+09 | 0.198364E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.300354E+09 | 0.158445E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.233817E+09 | 0.115029E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.222505E+09 | 79445751.99 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231018E+09 | 43672286.81 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278036E+09 | 24683029.34 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371784E+09 | 34895039.68 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345827E+09 | 65578800.49 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457384E+09 | 0.117710E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266412E+09 | 0.156746E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261951E+09 | 0.203073E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.348169E+10 | 0.141950E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.222505E+09 | 24683029.34 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457384E+09 | 0.221856E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.277443E+09 | 0.261770E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.337986E+09 | 0.234106E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.360404E+09 | 0.186946E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.280499E+09 | 0.135936E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.266762E+09 | 94063281.23 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276334E+09 | 51863811.72 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332083E+09 | 29473643.63 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444048E+09 | 41696201.97 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413638E+09 | 77904261.46 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.547710E+09 | 0.139544E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.319504E+09 | 0.185321E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.314257E+09 | 0.239825E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.417067E+10 | 0.167845E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.266762E+09 | 29473643.63 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.547710E+09 | 0.261770E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.233031E+09 | 0.215255E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.192919E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302433E+09 | 0.153304E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235898E+09 | 0.110613E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224721E+09 | 75647637.97 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231284E+09 | 41649231.75 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277711E+09 | 22872722.84 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371552E+09 | 32972245.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346077E+09 | 63502092.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458779E+09 | 0.114583E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268488E+09 | 0.151731E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263796E+09 | 0.197543E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349763E+10 | 0.137259E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224721E+09 | 22872722.84 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458779E+09 | 0.215255E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.233031E+09 | 0.215255E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.192919E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302433E+09 | 0.153304E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235898E+09 | 0.110613E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224721E+09 | 75647637.97 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231284E+09 | 41649231.75 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277711E+09 | 22872722.84 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371552E+09 | 32972245.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346077E+09 | 63502092.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458779E+09 | 0.114583E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268488E+09 | 0.151731E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263796E+09 | 0.197543E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349763E+10 | 0.137259E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224721E+09 | 22872722.84 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458779E+09 | 0.215255E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.233031E+09 | 0.215255E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.192919E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302433E+09 | 0.153304E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235898E+09 | 0.110613E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224721E+09 | 75647637.97 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231284E+09 | 41649231.75 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277711E+09 | 22872722.84 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371552E+09 | 32972245.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346077E+09 | 63502092.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458779E+09 | 0.114583E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268488E+09 | 0.151731E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263796E+09 | 0.197543E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349763E+10 | 0.137259E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224721E+09 | 22872722.84 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458779E+09 | 0.215255E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.233031E+09 | 0.215255E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.192919E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302433E+09 | 0.153304E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235898E+09 | 0.110613E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224721E+09 | 75647637.97 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231284E+09 | 41649231.75 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277711E+09 | 22872722.84 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371552E+09 | 32972245.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346077E+09 | 63502092.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458779E+09 | 0.114583E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268488E+09 | 0.151731E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263796E+09 | 0.197543E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349763E+10 | 0.137259E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224721E+09 | 22872722.84 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458779E+09 | 0.215255E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279758E+09 | 0.254068E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340599E+09 | 0.227762E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362793E+09 | 0.180960E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282911E+09 | 0.130782E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.269336E+09 | 89607902.44 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276627E+09 | 49483798.13 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331693E+09 | 27328834.68 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443744E+09 | 39405158.52 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413882E+09 | 75452923.70 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.549262E+09 | 0.135881E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321893E+09 | 0.179451E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.316375E+09 | 0.233361E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418887E+10 | 0.162354E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.269336E+09 | 27328834.68 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.549262E+09 | 0.254068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279758E+09 | 0.254068E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340599E+09 | 0.227762E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362793E+09 | 0.180960E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282911E+09 | 0.130782E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.269336E+09 | 89607902.44 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276627E+09 | 49483798.13 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331693E+09 | 27328834.68 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443744E+09 | 39405158.52 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413882E+09 | 75452923.70 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.549262E+09 | 0.135881E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321893E+09 | 0.179451E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.316375E+09 | 0.233361E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418887E+10 | 0.162354E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.269336E+09 | 27328834.68 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.549262E+09 | 0.254068E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232202E+09 | 0.216478E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282991E+09 | 0.193813E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301612E+09 | 0.153632E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235476E+09 | 0.110410E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224760E+09 | 74958586.17 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231296E+09 | 41090234.42 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277957E+09 | 22136659.76 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371726E+09 | 32143000.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345841E+09 | 62880848.86 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458231E+09 | 0.114008E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268047E+09 | 0.151771E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263093E+09 | 0.198298E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349323E+10 | 0.137162E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224760E+09 | 22136659.76 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458231E+09 | 0.216478E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232202E+09 | 0.216478E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282991E+09 | 0.193813E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301612E+09 | 0.153632E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235476E+09 | 0.110410E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224760E+09 | 74958586.17 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231296E+09 | 41090234.42 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277957E+09 | 22136659.76 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371726E+09 | 32143000.78 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345841E+09 | 62880848.86 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458231E+09 | 0.114008E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268047E+09 | 0.151771E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263093E+09 | 0.198298E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349323E+10 | 0.137162E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224760E+09 | 22136659.76 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458231E+09 | 0.216478E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.278868E+09 | 0.255395E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.339688E+09 | 0.228710E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.361939E+09 | 0.181254E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282502E+09 | 0.130490E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.269468E+09 | 88766934.79 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276697E+09 | 48821301.36 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332030E+09 | 26468915.61 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444008E+09 | 38437107.08 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413686E+09 | 74711431.88 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.548740E+09 | 0.135170E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321465E+09 | 0.179427E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315634E+09 | 0.234152E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418473E+10 | 0.162180E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.269468E+09 | 26468915.61 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.548740E+09 | 0.255395E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232334E+09 | 0.215883E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283167E+09 | 0.193197E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301869E+09 | 0.152853E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235891E+09 | 0.109569E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.225509E+09 | 73995658.76 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231515E+09 | 40813633.00 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278152E+09 | 21916443.44 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371890E+09 | 31925404.84 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346002E+09 | 62569643.33 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458637E+09 | 0.113287E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268374E+09 | 0.150999E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263274E+09 | 0.197593E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349661E+10 | 0.136460E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.225509E+09 | 21916443.44 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458637E+09 | 0.215883E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232334E+09 | 0.215883E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283167E+09 | 0.193197E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301869E+09 | 0.152853E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235891E+09 | 0.109569E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.225509E+09 | 73995658.76 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231515E+09 | 40813633.00 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278152E+09 | 21916443.44 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371890E+09 | 31925404.84 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346002E+09 | 62569643.33 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458637E+09 | 0.113287E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268374E+09 | 0.150999E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263274E+09 | 0.197593E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349661E+10 | 0.136460E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.225509E+09 | 21916443.44 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458637E+09 | 0.215883E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279027E+09 | 0.254689E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.339901E+09 | 0.227979E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362251E+09 | 0.180332E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.283001E+09 | 0.129498E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.270363E+09 | 87631406.71 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276960E+09 | 48494559.09 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332265E+09 | 26208662.97 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444204E+09 | 38179707.45 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413880E+09 | 74342862.69 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.549225E+09 | 0.134318E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321856E+09 | 0.178514E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315853E+09 | 0.233315E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418879E+10 | 0.161350E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.270363E+09 | 26208662.97 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.549225E+09 | 0.254689E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232869E+09 | 0.213051E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.190473E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302707E+09 | 0.149941E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.236979E+09 | 0.106940E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.227260E+09 | 71592815.45 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231999E+09 | 40066179.17 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278405E+09 | 21510126.95 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372023E+09 | 31591093.10 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346306E+09 | 61820310.51 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.459594E+09 | 0.111453E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.269211E+09 | 0.148703E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263924E+09 | 0.194774E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.350513E+10 | 0.134192E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.227260E+09 | 21510126.95 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.459594E+09 | 0.213051E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232869E+09 | 0.213051E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283854E+09 | 0.190473E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302707E+09 | 0.149941E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.236979E+09 | 0.106940E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.227260E+09 | 71592815.45 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231999E+09 | 40066179.17 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278405E+09 | 21510126.95 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372023E+09 | 31591093.10 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346306E+09 | 61820310.51 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.459594E+09 | 0.111453E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.269211E+09 | 0.148703E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263924E+09 | 0.194774E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.350513E+10 | 0.134192E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.227260E+09 | 21510126.95 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.459594E+09 | 0.213051E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279675E+09 | 0.251335E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340731E+09 | 0.224754E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.363266E+09 | 0.176892E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.284307E+09 | 0.126402E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.272449E+09 | 84799957.66 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.277537E+09 | 47617383.86 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332566E+09 | 25733885.38 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444362E+09 | 37789197.12 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.414245E+09 | 73462754.47 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.550365E+09 | 0.132157E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.322857E+09 | 0.175799E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.316636E+09 | 0.229977E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.419900E+10 | 0.158672E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.272449E+09 | 25733885.38 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.550365E+09 | 0.251335E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.234942E+09 | 0.200812E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.286459E+09 | 0.178755E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.305464E+09 | 0.138177E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.239713E+09 | 97474770.53 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.231119E+09 | 64495705.94 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.233234E+09 | 37051609.53 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278326E+09 | 20276508.24 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371378E+09 | 30603615.52 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346748E+09 | 59203806.33 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.461491E+09 | 0.105711E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.271472E+09 | 0.140478E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.266218E+09 | 0.183234E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.352656E+10 | 0.125627E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.231119E+09 | 20276508.24 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.461491E+09 | 0.200812E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.234942E+09 | 0.200812E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.286459E+09 | 0.178755E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.305464E+09 | 0.138177E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.239713E+09 | 97474770.53 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.231119E+09 | 64495705.94 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.233234E+09 | 37051609.53 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278326E+09 | 20276508.24 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371378E+09 | 30603615.52 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346748E+09 | 59203806.33 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.461491E+09 | 0.105711E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.271472E+09 | 0.140478E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.266218E+09 | 0.183234E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.352656E+10 | 0.125627E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.231119E+09 | 20276508.24 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.461491E+09 | 0.200812E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.282185E+09 | 0.236866E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.343879E+09 | 0.210892E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.366607E+09 | 0.163015E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.287604E+09 | 0.115262E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.277051E+09 | 76440700.24 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.279008E+09 | 44072065.29 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332461E+09 | 24281088.29 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443578E+09 | 36626138.42 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.414767E+09 | 70380146.42 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.552626E+09 | 0.125399E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.325572E+09 | 0.166101E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.319403E+09 | 0.216350E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.422474E+10 | 0.148569E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.277051E+09 | 24281088.29 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.552626E+09 | 0.236866E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.42 | 527.98 | 541.46 | 354.55 | 186.91 | 0.00 | 0.00 |
February | 751.87 | 518.66 | 714.17 | 472.72 | 241.45 | 0.00 | 0.00 |
March | 723.29 | 371.68 | 644.31 | 357.61 | 286.71 | 0.00 | 0.00 |
April | 581.70 | 277.59 | 499.97 | 197.70 | 302.26 | 0.00 | 0.00 |
May | 535.85 | 183.88 | 438.15 | 91.39 | 346.76 | 0.00 | 0.00 |
June | 573.05 | 99.42 | 411.19 | 62.85 | 348.33 | 0.00 | 0.00 |
July | 666.77 | 49.55 | 431.01 | 74.87 | 356.14 | 0.00 | 0.00 |
August | 890.29 | 73.85 | 575.56 | 213.49 | 362.08 | 0.00 | 0.00 |
September | 855.88 | 153.05 | 624.50 | 323.01 | 301.48 | 0.00 | 0.00 |
October | 1096.62 | 274.61 | 855.51 | 536.46 | 319.04 | 0.00 | 0.00 |
November | 661.22 | 383.58 | 593.22 | 356.26 | 236.96 | 0.00 | 0.00 |
December | 630.44 | 480.35 | 586.86 | 416.63 | 170.23 | 0.00 | 0.00 |
Annual Sum or Average | 710.41 | 281.51 | 575.67 | 287.19 | 288.48 | 0.00 | 0.00 |
Minimum of Months | 535.85 | 49.55 | 411.19 | 62.85 | 170.23 | 0.00 | 0.00 |
Maximum of Months | 1096.62 | 527.98 | 855.51 | 536.46 | 362.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.09 | 277.32 | 270.73 | 177.28 | 93.45 | 0.00 | 0.00 |
February | 371.71 | 273.10 | 357.08 | 236.36 | 120.72 | 0.00 | 0.00 |
March | 357.40 | 199.32 | 322.16 | 178.80 | 143.35 | 0.00 | 0.00 |
April | 286.26 | 150.26 | 249.98 | 98.85 | 151.13 | 0.00 | 0.00 |
May | 263.50 | 97.76 | 219.07 | 45.70 | 173.38 | 0.00 | 0.00 |
June | 285.49 | 51.09 | 205.59 | 31.43 | 174.17 | 0.00 | 0.00 |
July | 333.20 | 25.36 | 215.50 | 37.43 | 178.07 | 0.00 | 0.00 |
August | 445.25 | 37.18 | 287.78 | 106.74 | 181.04 | 0.00 | 0.00 |
September | 427.12 | 77.73 | 312.25 | 161.51 | 150.74 | 0.00 | 0.00 |
October | 545.04 | 142.65 | 427.75 | 268.23 | 159.52 | 0.00 | 0.00 |
November | 326.18 | 204.23 | 296.61 | 178.13 | 118.48 | 0.00 | 0.00 |
December | 312.04 | 253.53 | 293.43 | 208.32 | 85.11 | 0.00 | 0.00 |
Annual Sum or Average | 352.43 | 148.42 | 287.84 | 143.60 | 144.24 | 0.00 | 0.00 |
Minimum of Months | 263.50 | 25.36 | 205.59 | 31.43 | 85.11 | 0.00 | 0.00 |
Maximum of Months | 545.04 | 277.32 | 427.75 | 268.23 | 181.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.14 | 269.19 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 371.41 | 265.92 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 357.54 | 192.99 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 286.80 | 145.86 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 263.51 | 98.10 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.36 | 54.69 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.25 | 30.02 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.14 | 42.15 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.03 | 81.78 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 544.72 | 143.01 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 326.85 | 198.21 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 312.03 | 246.25 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 351.97 | 146.67 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 263.51 | 30.02 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 544.72 | 269.19 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.57 | 266.02 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 371.87 | 263.14 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 358.12 | 190.37 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 287.59 | 143.48 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 264.33 | 96.58 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.43 | 54.54 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.22 | 30.15 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.08 | 42.38 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.09 | 81.60 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 545.22 | 141.70 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 327.73 | 195.22 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 312.44 | 243.48 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 352.37 | 145.05 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 264.33 | 30.15 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 545.22 | 266.02 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.09 | 263.40 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 372.49 | 260.76 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 358.84 | 188.11 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 288.63 | 141.20 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 265.75 | 94.44 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.87 | 53.71 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.60 | 29.44 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.40 | 41.62 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.42 | 80.66 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 546.03 | 140.00 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 328.83 | 192.44 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 312.93 | 241.18 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 353.06 | 143.25 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 265.75 | 29.44 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 546.03 | 263.40 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.91 | 511.18 | 540.35 | 353.82 | 186.53 | 0.00 | 0.00 |
February | 750.91 | 507.27 | 712.70 | 471.75 | 240.95 | 0.00 | 0.00 |
March | 722.56 | 364.07 | 642.99 | 356.87 | 286.12 | 0.00 | 0.00 |
April | 582.33 | 271.61 | 498.94 | 197.30 | 301.64 | 0.00 | 0.00 |
May | 536.72 | 179.89 | 437.25 | 91.20 | 346.04 | 0.00 | 0.00 |
June | 570.37 | 102.46 | 410.34 | 62.73 | 347.62 | 0.00 | 0.00 |
July | 662.42 | 54.57 | 430.12 | 74.71 | 355.41 | 0.00 | 0.00 |
August | 886.24 | 78.67 | 574.38 | 213.05 | 361.33 | 0.00 | 0.00 |
September | 853.42 | 156.22 | 623.21 | 322.35 | 300.86 | 0.00 | 0.00 |
October | 1095.30 | 272.59 | 853.75 | 535.36 | 318.39 | 0.00 | 0.00 |
November | 662.71 | 372.62 | 592.00 | 355.53 | 236.48 | 0.00 | 0.00 |
December | 630.20 | 469.27 | 585.66 | 415.78 | 169.88 | 0.00 | 0.00 |
Annual Sum or Average | 709.29 | 277.06 | 574.49 | 286.60 | 287.89 | 0.00 | 0.00 |
Minimum of Months | 536.72 | 54.57 | 410.34 | 62.73 | 169.88 | 0.00 | 0.00 |
Maximum of Months | 1095.30 | 511.18 | 853.75 | 535.36 | 361.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.51 | 257.00 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 374.37 | 254.77 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 360.35 | 182.39 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 290.68 | 135.54 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 268.44 | 89.11 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 285.22 | 50.54 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.52 | 26.41 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.35 | 38.35 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.45 | 77.34 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 547.04 | 135.60 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 330.85 | 186.33 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 314.30 | 235.49 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 354.24 | 138.41 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 268.44 | 26.41 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 547.04 | 257.00 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.66 | 256.29 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 374.60 | 253.96 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 360.66 | 181.47 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 291.20 | 134.50 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 269.33 | 87.97 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 285.49 | 50.20 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.75 | 26.15 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.54 | 38.09 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.65 | 76.96 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 547.53 | 134.74 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 331.25 | 185.38 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 314.52 | 234.65 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 354.58 | 137.71 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 269.33 | 26.15 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 547.53 | 256.29 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.31 | 252.93 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 375.51 | 250.37 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 361.66 | 178.01 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 292.54 | 131.28 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 271.42 | 85.12 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 286.09 | 49.29 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 332.05 | 25.67 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.70 | 37.70 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 427.03 | 76.04 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 548.67 | 132.56 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 332.28 | 182.56 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 315.29 | 231.30 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 355.44 | 135.42 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 271.42 | 25.67 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 548.67 | 252.93 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.79 | 238.38 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 378.97 | 234.95 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 364.97 | 164.04 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 295.92 | 119.68 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 276.02 | 76.70 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 287.61 | 45.59 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.96 | 24.21 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 442.93 | 36.53 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 427.57 | 72.83 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 550.93 | 125.75 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 335.08 | 172.48 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 318.04 | 217.60 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 357.62 | 126.78 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 276.02 | 24.21 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 550.93 | 238.38 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149032E+10 | 0.141414E+10 | 0.145025E+10 | 0.949633E+09 | 0.500616E+09 | 0.00 | 0.00 |
February | 0.181892E+10 | 0.125474E+10 | 0.172772E+10 | 0.114361E+10 | 0.584108E+09 | 0.00 | 0.00 |
March | 0.193725E+10 | 0.995515E+09 | 0.172573E+10 | 0.957812E+09 | 0.767921E+09 | 0.00 | 0.00 |
April | 0.150777E+10 | 0.719516E+09 | 0.129591E+10 | 0.512442E+09 | 0.783469E+09 | 0.00 | 0.00 |
May | 0.143523E+10 | 0.492499E+09 | 0.117353E+10 | 0.244780E+09 | 0.928750E+09 | 0.00 | 0.00 |
June | 0.148535E+10 | 0.257692E+09 | 0.106580E+10 | 0.162918E+09 | 0.902878E+09 | 0.00 | 0.00 |
July | 0.178587E+10 | 0.132725E+09 | 0.115441E+10 | 0.200520E+09 | 0.953886E+09 | 0.00 | 0.00 |
August | 0.238455E+10 | 0.197793E+09 | 0.154158E+10 | 0.571798E+09 | 0.969784E+09 | 0.00 | 0.00 |
September | 0.221844E+10 | 0.396714E+09 | 0.161869E+10 | 0.837253E+09 | 0.781438E+09 | 0.00 | 0.00 |
October | 0.293719E+10 | 0.735502E+09 | 0.229139E+10 | 0.143686E+10 | 0.854522E+09 | 0.00 | 0.00 |
November | 0.171389E+10 | 0.994250E+09 | 0.153763E+10 | 0.923418E+09 | 0.614208E+09 | 0.00 | 0.00 |
December | 0.168857E+10 | 0.128656E+10 | 0.157185E+10 | 0.111591E+10 | 0.455942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224034E+11 | 0.887765E+10 | 0.181545E+11 | 0.905696E+10 | 0.909752E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143523E+10 | 0.132725E+09 | 0.106580E+10 | 0.162918E+09 | 0.455942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293719E+10 | 0.141414E+10 | 0.229139E+10 | 0.143686E+10 | 0.969784E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.736790E+09 | 0.742784E+09 | 0.725124E+09 | 0.474816E+09 | 0.250308E+09 | 0.00 | 0.00 |
February | 0.899252E+09 | 0.660685E+09 | 0.863858E+09 | 0.571804E+09 | 0.292054E+09 | 0.00 | 0.00 |
March | 0.957252E+09 | 0.533863E+09 | 0.862866E+09 | 0.478906E+09 | 0.383961E+09 | 0.00 | 0.00 |
April | 0.741986E+09 | 0.389477E+09 | 0.647955E+09 | 0.256221E+09 | 0.391734E+09 | 0.00 | 0.00 |
May | 0.705749E+09 | 0.261834E+09 | 0.586765E+09 | 0.122390E+09 | 0.464375E+09 | 0.00 | 0.00 |
June | 0.739984E+09 | 0.132428E+09 | 0.532898E+09 | 81458926.08 | 0.451439E+09 | 0.00 | 0.00 |
July | 0.892448E+09 | 67933606.84 | 0.577203E+09 | 0.100260E+09 | 0.476943E+09 | 0.00 | 0.00 |
August | 0.119256E+10 | 99575352.42 | 0.770791E+09 | 0.285899E+09 | 0.484892E+09 | 0.00 | 0.00 |
September | 0.110710E+10 | 0.201477E+09 | 0.809346E+09 | 0.418627E+09 | 0.390719E+09 | 0.00 | 0.00 |
October | 0.145982E+10 | 0.382077E+09 | 0.114569E+10 | 0.718432E+09 | 0.427261E+09 | 0.00 | 0.00 |
November | 0.845468E+09 | 0.529363E+09 | 0.768813E+09 | 0.461709E+09 | 0.307104E+09 | 0.00 | 0.00 |
December | 0.835773E+09 | 0.679047E+09 | 0.785926E+09 | 0.557955E+09 | 0.227971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111142E+11 | 0.468054E+10 | 0.907724E+10 | 0.452848E+10 | 0.454876E+10 | 0.00 | 0.00 |
Minimum of Months | 0.705749E+09 | 67933606.84 | 0.532898E+09 | 81458926.08 | 0.227971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145982E+10 | 0.742784E+09 | 0.114569E+10 | 0.718432E+09 | 0.484892E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.736930E+09 | 0.720999E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.898514E+09 | 0.643316E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.957639E+09 | 0.516917E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.743395E+09 | 0.378069E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.705789E+09 | 0.262741E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.737064E+09 | 0.141753E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887233E+09 | 80401889.61 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118690E+10 | 0.112903E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110427E+10 | 0.211977E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.145898E+10 | 0.383039E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.847207E+09 | 0.513761E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.835740E+09 | 0.659557E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110997E+11 | 0.462543E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.705789E+09 | 80401889.61 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145898E+10 | 0.720999E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.738085E+09 | 0.712504E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.899625E+09 | 0.636598E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.959190E+09 | 0.509896E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.745427E+09 | 0.371909E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.707979E+09 | 0.258669E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.737252E+09 | 0.141378E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887145E+09 | 80766233.35 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118673E+10 | 0.113505E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110441E+10 | 0.211520E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146033E+10 | 0.379529E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.849487E+09 | 0.506016E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.836830E+09 | 0.652147E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111125E+11 | 0.457444E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.707979E+09 | 80766233.35 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146033E+10 | 0.712504E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.739489E+09 | 0.705481E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.901139E+09 | 0.630831E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.961110E+09 | 0.503833E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.748131E+09 | 0.365992E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.711772E+09 | 0.252954E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.738370E+09 | 0.139208E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.888154E+09 | 78839679.76 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118762E+10 | 0.111486E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110529E+10 | 0.209062E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146248E+10 | 0.374963E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.852327E+09 | 0.498810E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.838158E+09 | 0.645970E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111340E+11 | 0.451743E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711772E+09 | 78839679.76 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146248E+10 | 0.705481E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149164E+10 | 0.136915E+10 | 0.144727E+10 | 0.947684E+09 | 0.499589E+09 | 0.00 | 0.00 |
February | 0.181661E+10 | 0.122720E+10 | 0.172417E+10 | 0.114126E+10 | 0.582910E+09 | 0.00 | 0.00 |
March | 0.193531E+10 | 0.975132E+09 | 0.172219E+10 | 0.955847E+09 | 0.766346E+09 | 0.00 | 0.00 |
April | 0.150941E+10 | 0.704013E+09 | 0.129325E+10 | 0.511391E+09 | 0.781861E+09 | 0.00 | 0.00 |
May | 0.143756E+10 | 0.481805E+09 | 0.117112E+10 | 0.244278E+09 | 0.926844E+09 | 0.00 | 0.00 |
June | 0.147839E+10 | 0.265564E+09 | 0.106361E+10 | 0.162584E+09 | 0.901026E+09 | 0.00 | 0.00 |
July | 0.177423E+10 | 0.146148E+09 | 0.115204E+10 | 0.200109E+09 | 0.951929E+09 | 0.00 | 0.00 |
August | 0.237370E+10 | 0.210699E+09 | 0.153842E+10 | 0.570625E+09 | 0.967794E+09 | 0.00 | 0.00 |
September | 0.221207E+10 | 0.404914E+09 | 0.161537E+10 | 0.835536E+09 | 0.779835E+09 | 0.00 | 0.00 |
October | 0.293364E+10 | 0.730093E+09 | 0.228669E+10 | 0.143392E+10 | 0.852769E+09 | 0.00 | 0.00 |
November | 0.171774E+10 | 0.965826E+09 | 0.153447E+10 | 0.921523E+09 | 0.612948E+09 | 0.00 | 0.00 |
December | 0.168793E+10 | 0.125689E+10 | 0.156863E+10 | 0.111362E+10 | 0.455007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223682E+11 | 0.873744E+10 | 0.181172E+11 | 0.903837E+10 | 0.907886E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143756E+10 | 0.146148E+09 | 0.106361E+10 | 0.162584E+09 | 0.455007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293364E+10 | 0.136915E+10 | 0.228669E+10 | 0.143392E+10 | 0.967794E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743270E+09 | 0.688349E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.905667E+09 | 0.616336E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.965161E+09 | 0.488515E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.753453E+09 | 0.351309E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.718986E+09 | 0.238683E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.739288E+09 | 0.131002E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887944E+09 | 70742144.54 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118746E+10 | 0.102723E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110537E+10 | 0.200473E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146520E+10 | 0.363186E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.857558E+09 | 0.482968E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.841819E+09 | 0.630745E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111712E+11 | 0.436503E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.718986E+09 | 70742144.54 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146520E+10 | 0.688349E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743693E+09 | 0.686453E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.906234E+09 | 0.614371E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.965987E+09 | 0.486037E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.754781E+09 | 0.348633E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.721379E+09 | 0.235622E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.739990E+09 | 0.130122E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.888570E+09 | 70041470.89 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118798E+10 | 0.102030E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110588E+10 | 0.199482E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146650E+10 | 0.360891E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.858604E+09 | 0.480511E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.842401E+09 | 0.628499E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111820E+11 | 0.434269E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.721379E+09 | 70041470.89 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146650E+10 | 0.686453E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745413E+09 | 0.677437E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.908437E+09 | 0.605698E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.968677E+09 | 0.476770E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.758264E+09 | 0.340281E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.726968E+09 | 0.227985E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.741535E+09 | 0.127750E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.889375E+09 | 68753850.68 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118841E+10 | 0.100971E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110686E+10 | 0.197103E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146955E+10 | 0.355061E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.861279E+09 | 0.473204E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.844484E+09 | 0.619524E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112092E+11 | 0.427054E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.726968E+09 | 68753850.68 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146955E+10 | 0.677437E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752067E+09 | 0.638490E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.916797E+09 | 0.568402E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.977531E+09 | 0.439366E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.767026E+09 | 0.310209E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.739288E+09 | 0.205432E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.745477E+09 | 0.118175E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.889112E+09 | 64833773.10 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118633E+10 | 97833137.58 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110826E+10 | 0.188788E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.147561E+10 | 0.336820E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.868515E+09 | 0.447056E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.851835E+09 | 0.582814E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112779E+11 | 0.399822E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.739288E+09 | 64833773.10 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147561E+10 | 0.638490E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.365299E+09 | -240398501.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124900173.3 | 59.00 | 0.00 | 0.00 |
February | 0.333393E+09 | -220479297.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112914116.4 | 58.99 | 0.00 | 0.00 |
March | 0.366080E+09 | -242517828.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123562344.4 | 58.99 | 0.00 | 0.00 |
April | 0.336282E+09 | -219737810.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116544455.8 | 58.99 | 0.00 | 0.00 |
May | 0.326862E+09 | -211554721.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115306997.1 | 58.99 | 0.00 | 0.00 |
June | 0.300915E+09 | -191904386.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109010882.5 | 58.99 | 0.00 | 0.00 |
July | 0.295990E+09 | -184012038.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111977860.8 | 58.99 | 0.00 | 0.00 |
August | 0.297187E+09 | -185224416.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111962878.9 | 58.99 | 0.00 | 0.00 |
September | 0.291734E+09 | -182783032.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108951370.7 | 58.99 | 0.00 | 0.00 |
October | 0.314538E+09 | -199539956.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114998313.9 | 58.99 | 0.00 | 0.00 |
November | 0.325842E+09 | -207769827.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118072453.9 | 58.99 | 0.00 | 0.00 |
December | 0.354681E+09 | -230508175.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124173100.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.390880E+10 | -0.251643E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139237E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.291734E+09 | -242517828.8 | 0.00 | 0.00 | 672.00 | 0.00 | -124900173.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.366080E+09 | -182783032.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108951370.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363371E+09 | -240400102.3 | 0.00 | 0.00 | 744.00 | 0.00 | -122970592.3 | 58.99 | 0.00 | 0.00 |
February | 0.331522E+09 | -220486280.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111035789.2 | 58.99 | 0.00 | 0.00 |
March | 0.363525E+09 | -242524122.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121000956.6 | 58.99 | 0.00 | 0.00 |
April | 0.333869E+09 | -219728558.0 | 0.00 | 0.00 | 720.00 | 0.00 | -114140045.8 | 58.99 | 0.00 | 0.00 |
May | 0.325320E+09 | -211555508.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113764149.9 | 58.99 | 0.00 | 0.00 |
June | 0.300603E+09 | -191903007.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108699803.3 | 58.99 | 0.00 | 0.00 |
July | 0.295791E+09 | -184011938.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111778625.9 | 58.99 | 0.00 | 0.00 |
August | 0.297028E+09 | -185206033.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111821605.2 | 58.99 | 0.00 | 0.00 |
September | 0.291481E+09 | -182782688.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108698641.7 | 58.99 | 0.00 | 0.00 |
October | 0.313145E+09 | -199539568.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113605707.6 | 58.99 | 0.00 | 0.00 |
November | 0.323210E+09 | -207761697.3 | 0.00 | 0.00 | 720.00 | 0.00 | -115447865.3 | 59.00 | 0.00 | 0.00 |
December | 0.352454E+09 | -230504077.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121949780.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389132E+10 | -0.251640E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137491E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.291481E+09 | -242524122.0 | 0.00 | 0.00 | 672.00 | 0.00 | -122970592.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.363525E+09 | -182782688.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108698641.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.336212E+09 | -211390818.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124821207.8 | 59.00 | 0.00 | 0.00 |
February | 0.306601E+09 | -194032946.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112568292.7 | 59.00 | 0.00 | 0.00 |
March | 0.339123E+09 | -216456416.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122667016.7 | 58.99 | 0.00 | 0.00 |
April | 0.308662E+09 | -193250065.3 | 0.00 | 0.00 | 720.00 | 0.00 | -115411784.1 | 58.99 | 0.00 | 0.00 |
May | 0.301463E+09 | -187650397.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113813075.1 | 59.00 | 0.00 | 0.00 |
June | 0.278587E+09 | -170874802.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107712483.7 | 59.00 | 0.00 | 0.00 |
July | 0.271106E+09 | -160869496.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110236937.2 | 58.99 | 0.00 | 0.00 |
August | 0.275682E+09 | -165452526.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110229144.0 | 58.98 | 0.00 | 0.00 |
September | 0.268341E+09 | -160664181.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107676609.5 | 58.99 | 0.00 | 0.00 |
October | 0.289210E+09 | -175524209.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113685916.5 | 58.98 | 0.00 | 0.00 |
November | 0.300502E+09 | -183449378.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117052952.4 | 58.99 | 0.00 | 0.00 |
December | 0.324907E+09 | -201158662.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123748584.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360040E+10 | -0.222077E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137962E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.268341E+09 | -216456416.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124821207.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.339123E+09 | -160664181.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107676609.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.336635E+09 | -211394426.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125240356.5 | 59.00 | 0.00 | 0.00 |
February | 0.306941E+09 | -194050824.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112889690.3 | 58.99 | 0.00 | 0.00 |
March | 0.339533E+09 | -216443112.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123089522.1 | 58.99 | 0.00 | 0.00 |
April | 0.309081E+09 | -193259975.1 | 0.00 | 0.00 | 720.00 | 0.00 | -115820666.9 | 58.99 | 0.00 | 0.00 |
May | 0.301788E+09 | -187669710.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114118444.8 | 58.99 | 0.00 | 0.00 |
June | 0.278613E+09 | -170920948.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107692525.5 | 58.99 | 0.00 | 0.00 |
July | 0.271078E+09 | -160852846.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110224989.3 | 58.99 | 0.00 | 0.00 |
August | 0.275643E+09 | -165414338.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110228182.3 | 59.00 | 0.00 | 0.00 |
September | 0.268364E+09 | -160693813.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107669837.0 | 58.98 | 0.00 | 0.00 |
October | 0.289484E+09 | -175468539.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114015284.4 | 59.00 | 0.00 | 0.00 |
November | 0.301012E+09 | -183450534.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117561350.1 | 58.99 | 0.00 | 0.00 |
December | 0.325275E+09 | -201227937.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124046950.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.360344E+10 | -0.222085E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138260E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.268364E+09 | -216443112.5 | 0.00 | 0.00 | 672.00 | 0.00 | -125240356.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.339533E+09 | -160693813.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107669837.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326577E+09 | -199799160.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126777936.2 | 59.00 | 0.00 | 0.00 |
February | 0.297770E+09 | -183507872.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114262498.6 | 58.99 | 0.00 | 0.00 |
March | 0.329255E+09 | -204809842.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124445211.1 | 58.99 | 0.00 | 0.00 |
April | 0.300185E+09 | -182890041.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117294627.1 | 58.99 | 0.00 | 0.00 |
May | 0.293219E+09 | -177457099.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115762072.5 | 59.00 | 0.00 | 0.00 |
June | 0.270054E+09 | -161706437.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108347104.3 | 58.99 | 0.00 | 0.00 |
July | 0.262902E+09 | -152130852.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110770847.0 | 58.99 | 0.00 | 0.00 |
August | 0.267367E+09 | -156530343.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110836897.3 | 58.99 | 0.00 | 0.00 |
September | 0.260350E+09 | -152046875.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108302649.8 | 58.99 | 0.00 | 0.00 |
October | 0.281006E+09 | -165876530.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115129594.5 | 58.99 | 0.00 | 0.00 |
November | 0.292451E+09 | -173254375.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119196928.7 | 58.99 | 0.00 | 0.00 |
December | 0.315692E+09 | -190271177.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125421302.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349683E+10 | -0.210028E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139655E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260350E+09 | -204809842.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126777936.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.329255E+09 | -152046875.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108302649.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326502E+09 | -199800149.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126702217.8 | 59.00 | 0.00 | 0.00 |
February | 0.297726E+09 | -183502916.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114223370.5 | 58.99 | 0.00 | 0.00 |
March | 0.329276E+09 | -204806685.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124469006.9 | 58.99 | 0.00 | 0.00 |
April | 0.300276E+09 | -182887070.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117389427.0 | 58.99 | 0.00 | 0.00 |
May | 0.293419E+09 | -177464188.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115954776.4 | 58.99 | 0.00 | 0.00 |
June | 0.270139E+09 | -161711345.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108427358.4 | 58.99 | 0.00 | 0.00 |
July | 0.263026E+09 | -152129486.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110896794.1 | 58.99 | 0.00 | 0.00 |
August | 0.267501E+09 | -156535214.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110965349.6 | 58.99 | 0.00 | 0.00 |
September | 0.260434E+09 | -152046094.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108387910.7 | 58.99 | 0.00 | 0.00 |
October | 0.281130E+09 | -165876355.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115253275.0 | 58.99 | 0.00 | 0.00 |
November | 0.292536E+09 | -173258890.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119277393.1 | 58.99 | 0.00 | 0.00 |
December | 0.315657E+09 | -190270005.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125387375.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.349762E+10 | -0.210029E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139733E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260434E+09 | -204806685.6 | 0.00 | 0.00 | 672.00 | 0.00 | -126702217.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.329276E+09 | -152046094.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108387910.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326593E+09 | -199800374.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126792451.7 | 59.00 | 0.00 | 0.00 |
February | 0.297826E+09 | -183510201.0 | 0.00 | 0.00 | 672.00 | 0.00 | -114316231.7 | 58.99 | 0.00 | 0.00 |
March | 0.329409E+09 | -204815789.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124593113.5 | 58.99 | 0.00 | 0.00 |
April | 0.300472E+09 | -182878491.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117593219.1 | 58.99 | 0.00 | 0.00 |
May | 0.293692E+09 | -177456204.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116235926.7 | 59.00 | 0.00 | 0.00 |
June | 0.270210E+09 | -161703056.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108506800.0 | 59.00 | 0.00 | 0.00 |
July | 0.263081E+09 | -152128457.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110952083.3 | 58.99 | 0.00 | 0.00 |
August | 0.267551E+09 | -156532090.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111018881.4 | 58.99 | 0.00 | 0.00 |
September | 0.260500E+09 | -152043086.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108457053.0 | 58.99 | 0.00 | 0.00 |
October | 0.281317E+09 | -165873454.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115443211.8 | 58.99 | 0.00 | 0.00 |
November | 0.292693E+09 | -173253319.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119440142.9 | 59.00 | 0.00 | 0.00 |
December | 0.315776E+09 | -190265631.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125510634.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349912E+10 | -0.210026E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139886E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260500E+09 | -204815789.5 | 0.00 | 0.00 | 672.00 | 0.00 | -126792451.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.329409E+09 | -152043086.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108457053.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180218E+11 | 61581.92 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172316E+11 | 61581.92 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.950208E+10 | 61581.92 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317653E+10 | 61581.92 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11814190.95 | 6248.53 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58263393.09 | 7041.03 | 28-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613521E+10 | 61581.92 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135892E+11 | 61581.92 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180218E+11 | 61581.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.576952E+10 | 32147.23 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550787E+10 | 32147.23 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258171E+10 | 32147.23 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636103E+09 | 32147.23 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93777.04 | 156.30 | 28-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159486E+10 | 32147.23 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400782E+10 | 32147.23 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.576952E+10 | 32147.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694492E+10 | 32606.20 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.653812E+10 | 32606.20 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345232E+10 | 32606.20 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.999660E+09 | 32606.20 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 169095.77 | 187.50 | 01-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3966639.29 | 2569.32 | 29-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222741E+10 | 32606.20 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507697E+10 | 32606.20 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694492E+10 | 32606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.720846E+10 | 32454.87 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674711E+10 | 32454.87 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366018E+10 | 32454.87 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111291E+10 | 32454.87 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1824643.25 | 2391.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7829635.76 | 2527.96 | 29-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240124E+10 | 32454.87 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.530688E+10 | 32454.87 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.720846E+10 | 32454.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.760214E+10 | 32450.54 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709109E+10 | 32450.54 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398080E+10 | 32450.54 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128599E+10 | 32450.54 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6266676.92 | 3040.05 | 01-MAY-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17803821.56 | 4488.67 | 28-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.264156E+10 | 32450.54 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565621E+10 | 32450.54 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.760214E+10 | 32450.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148599E+11 | 59083.80 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137714E+11 | 59083.80 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.809777E+10 | 59083.80 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281734E+10 | 59083.80 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44782805.38 | 27924.91 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61675923.61 | 6597.11 | 28-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.550403E+10 | 59083.80 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112679E+11 | 59083.80 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148599E+11 | 59083.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.773396E+10 | 30418.44 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717822E+10 | 30418.44 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423532E+10 | 30418.44 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148438E+10 | 30418.44 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29797480.91 | 17041.84 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33513824.41 | 4002.38 | 28-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287783E+10 | 30418.44 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.585922E+10 | 30418.44 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.773396E+10 | 30418.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.782269E+10 | 30303.24 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.726921E+10 | 30303.24 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433817E+10 | 30303.24 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155198E+10 | 30303.24 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43789300.60 | 21504.61 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42008986.28 | 5910.40 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295269E+10 | 30303.24 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595515E+10 | 30303.24 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.782269E+10 | 30303.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823759E+10 | 30219.77 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768358E+10 | 30219.77 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473279E+10 | 30219.77 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179507E+10 | 30219.77 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91569840.05 | 30219.77 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71328658.46 | 12258.88 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322197E+10 | 30219.77 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.634395E+10 | 30219.77 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.823759E+10 | 30219.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103659E+11 | 32254.42 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.976971E+10 | 32254.42 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622060E+10 | 32254.42 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263055E+10 | 32254.42 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267431E+09 | 32254.42 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205494E+09 | 31395.86 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413177E+10 | 32254.42 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.791998E+10 | 32254.42 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103659E+11 | 32254.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 5652171.59 | 4151991.02 | 1930.90 | 27-MAR-16:10 | 1410.91 | 0.00 |
April | 0.00 | 0.00 | 0.597003E+09 | 0.519746E+09 | 10384.67 | 07-APR-13:00 | 9589.85 | 0.00 |
May | 0.00 | 0.00 | 0.339031E+10 | 0.289148E+10 | 19087.78 | 31-MAY-14:00 | 13463.72 | 0.00 |
June | 0.00 | 0.00 | 0.176542E+11 | 0.117531E+11 | 50212.77 | 25-JUN-07:02 | 27821.78 | 0.00 |
July | 0.00 | 0.00 | 0.316152E+11 | 0.194591E+11 | 51478.60 | 22-JUL-07:02 | 25074.08 | 0.00 |
August | 0.00 | 0.00 | 0.297632E+11 | 0.203991E+11 | 50955.17 | 17-AUG-07:02 | 26935.07 | 0.00 |
September | 0.00 | 0.00 | 0.135911E+11 | 0.968079E+10 | 50203.74 | 14-SEP-07:02 | 28473.95 | 0.00 |
October | 0.00 | 0.00 | 0.366940E+10 | 0.246583E+10 | 21967.29 | 06-OCT-07:03 | 11196.69 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100286E+12 | 0.671733E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.316152E+11 | 0.203991E+11 | 51478.60 | 28473.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 9903794.29 | 7619830.01 | 1834.78 | 27-MAR-16:10 | 1356.94 | 0.00 |
April | 0.00 | 0.00 | 0.460063E+09 | 0.401430E+09 | 23566.08 | 07-APR-20:01 | 19762.81 | 0.00 |
May | 0.00 | 0.00 | 0.238665E+10 | 0.207482E+10 | 24005.31 | 30-MAY-20:02 | 17206.54 | 0.00 |
June | 0.00 | 0.00 | 0.101753E+11 | 0.705500E+10 | 25496.86 | 27-JUN-07:02 | 18091.11 | 0.00 |
July | 0.00 | 0.00 | 0.162647E+11 | 0.105228E+11 | 26081.17 | 22-JUL-07:02 | 16445.00 | 0.00 |
August | 0.00 | 0.00 | 0.154813E+11 | 0.110454E+11 | 25763.43 | 17-AUG-07:02 | 17407.25 | 0.00 |
September | 0.00 | 0.00 | 0.790441E+10 | 0.584846E+10 | 25586.02 | 14-SEP-07:02 | 17977.14 | 0.00 |
October | 0.00 | 0.00 | 0.251040E+10 | 0.171566E+10 | 25158.98 | 23-OCT-20:10 | 11258.95 | 0.00 |
November | 0.00 | 0.00 | 6507810.55 | 5676797.66 | 2611.97 | 11-NOV-18:17 | 2196.65 | 0.00 |
December | 0.00 | 0.00 | 73768.35 | 72404.89 | 63.36 | 17-DEC-21:30 | 61.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.551992E+11 | 0.386769E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162647E+11 | 0.110454E+11 | 26081.17 | 19762.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3113592.86 | 2308394.52 | 1139.37 | 27-MAR-16:10 | 841.61 | 0.00 |
April | 0.00 | 0.00 | 0.329876E+09 | 0.287631E+09 | 6020.54 | 08-APR-12:10 | 5131.94 | 0.00 |
May | 0.00 | 0.00 | 0.158643E+10 | 0.139085E+10 | 10181.81 | 30-MAY-06:03 | 7447.93 | 0.00 |
June | 0.00 | 0.00 | 0.775612E+10 | 0.529689E+10 | 27131.92 | 25-JUN-07:02 | 13458.34 | 0.00 |
July | 0.00 | 0.00 | 0.128540E+11 | 0.809521E+10 | 27236.70 | 21-JUL-06:02 | 13582.19 | 0.00 |
August | 0.00 | 0.00 | 0.122569E+11 | 0.861123E+10 | 27412.88 | 06-AUG-07:02 | 13307.85 | 0.00 |
September | 0.00 | 0.00 | 0.579391E+10 | 0.421710E+10 | 26765.72 | 14-SEP-06:02 | 14789.83 | 0.00 |
October | 0.00 | 0.00 | 0.183815E+10 | 0.125614E+10 | 16415.35 | 06-OCT-06:03 | 8483.72 | 0.00 |
November | 0.00 | 0.00 | 203542.57 | 163426.93 | 130.95 | 04-NOV-13:00 | 104.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.424187E+11 | 0.291575E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128540E+11 | 0.861123E+10 | 27412.88 | 14789.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1702601.18 | 1260512.40 | 839.20 | 27-MAR-16:10 | 619.17 | 0.00 |
April | 0.00 | 0.00 | 0.307730E+09 | 0.268547E+09 | 5857.87 | 08-APR-12:10 | 4988.70 | 0.00 |
May | 0.00 | 0.00 | 0.154133E+10 | 0.135054E+10 | 9918.70 | 31-MAY-14:00 | 7101.24 | 0.00 |
June | 0.00 | 0.00 | 0.772208E+10 | 0.527289E+10 | 27103.04 | 25-JUN-07:02 | 13439.53 | 0.00 |
July | 0.00 | 0.00 | 0.128565E+11 | 0.809893E+10 | 27213.85 | 21-JUL-06:02 | 13595.92 | 0.00 |
August | 0.00 | 0.00 | 0.122757E+11 | 0.862790E+10 | 27388.51 | 06-AUG-07:02 | 13337.17 | 0.00 |
September | 0.00 | 0.00 | 0.577626E+10 | 0.420439E+10 | 26739.00 | 14-SEP-06:02 | 14767.68 | 0.00 |
October | 0.00 | 0.00 | 0.177881E+10 | 0.121474E+10 | 16204.40 | 06-OCT-06:03 | 8369.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422602E+11 | 0.290392E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128565E+11 | 0.862790E+10 | 27388.51 | 14767.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 728794.02 | 537530.82 | 507.35 | 27-MAR-16:10 | 373.45 | 0.00 |
April | 0.00 | 0.00 | 0.270641E+09 | 0.236495E+09 | 5526.80 | 08-APR-12:10 | 4687.89 | 0.00 |
May | 0.00 | 0.00 | 0.143490E+10 | 0.125402E+10 | 9738.93 | 31-MAY-14:00 | 6952.44 | 0.00 |
June | 0.00 | 0.00 | 0.748222E+10 | 0.509231E+10 | 26982.09 | 25-JUN-07:02 | 13229.83 | 0.00 |
July | 0.00 | 0.00 | 0.126177E+11 | 0.791726E+10 | 27094.52 | 21-JUL-06:02 | 13372.69 | 0.00 |
August | 0.00 | 0.00 | 0.120514E+11 | 0.844193E+10 | 27268.66 | 06-AUG-07:02 | 13127.73 | 0.00 |
September | 0.00 | 0.00 | 0.559234E+10 | 0.405828E+10 | 26624.56 | 14-SEP-06:02 | 14543.37 | 0.00 |
October | 0.00 | 0.00 | 0.165104E+10 | 0.112669E+10 | 14219.60 | 06-OCT-06:03 | 7287.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.411009E+11 | 0.281275E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126177E+11 | 0.844193E+10 | 27268.66 | 14543.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 336645.00 | 241076.48 | 282.14 | 27-MAR-16:00 | 201.46 | 0.00 |
April | 0.00 | 0.00 | 0.420880E+09 | 0.362766E+09 | 9337.75 | 08-APR-12:00 | 7806.68 | 0.00 |
May | 0.00 | 0.00 | 0.234244E+10 | 0.200271E+10 | 19220.41 | 31-MAY-07:03 | 15513.65 | 0.00 |
June | 0.00 | 0.00 | 0.129642E+11 | 0.859102E+10 | 48987.70 | 25-JUN-08:62 | 23516.90 | 0.00 |
July | 0.00 | 0.00 | 0.224310E+11 | 0.136843E+11 | 49013.06 | 09-JUL-08:62 | 23932.66 | 0.00 |
August | 0.00 | 0.00 | 0.217524E+11 | 0.148849E+11 | 48468.36 | 06-AUG-08:62 | 20030.11 | 0.00 |
September | 0.00 | 0.00 | 0.969317E+10 | 0.685042E+10 | 47812.22 | 14-SEP-07:02 | 26854.83 | 0.00 |
October | 0.00 | 0.00 | 0.269121E+10 | 0.178629E+10 | 23026.49 | 06-OCT-07:03 | 11790.71 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.722957E+11 | 0.481627E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224310E+11 | 0.148849E+11 | 49013.06 | 26854.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 41055.52 | 29570.40 | 68.26 | 27-MAR-16:10 | 49.17 | 0.00 |
April | 0.00 | 0.00 | 0.203970E+09 | 0.176517E+09 | 4706.95 | 08-APR-12:00 | 3950.17 | 0.00 |
May | 0.00 | 0.00 | 0.117091E+10 | 0.100320E+10 | 9319.25 | 31-MAY-14:10 | 6495.93 | 0.00 |
June | 0.00 | 0.00 | 0.661227E+10 | 0.439833E+10 | 25353.62 | 25-JUN-08:62 | 12140.63 | 0.00 |
July | 0.00 | 0.00 | 0.115033E+11 | 0.704652E+10 | 25372.82 | 09-JUL-08:62 | 12334.82 | 0.00 |
August | 0.00 | 0.00 | 0.111517E+11 | 0.765858E+10 | 25084.70 | 06-AUG-08:62 | 10377.60 | 0.00 |
September | 0.00 | 0.00 | 0.495310E+10 | 0.351409E+10 | 24731.15 | 14-SEP-07:02 | 13930.19 | 0.00 |
October | 0.00 | 0.00 | 0.134889E+10 | 0.899275E+09 | 10283.39 | 06-OCT-07:03 | 5271.78 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.369442E+11 | 0.246965E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115033E+11 | 0.765858E+10 | 25372.82 | 13930.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 81.12 | 58.27 | 0.14 | 27-MAR-16:10 | 0.10 | 0.00 |
April | 0.00 | 0.00 | 0.193904E+09 | 0.167739E+09 | 4595.83 | 08-APR-12:00 | 3854.22 | 0.00 |
May | 0.00 | 0.00 | 0.112615E+10 | 0.962919E+09 | 9236.21 | 31-MAY-14:10 | 6429.16 | 0.00 |
June | 0.00 | 0.00 | 0.652139E+10 | 0.433155E+10 | 25256.53 | 25-JUN-08:62 | 12047.24 | 0.00 |
July | 0.00 | 0.00 | 0.114081E+11 | 0.697534E+10 | 25277.01 | 09-JUL-08:62 | 12240.71 | 0.00 |
August | 0.00 | 0.00 | 0.110689E+11 | 0.759104E+10 | 24991.85 | 06-AUG-08:62 | 10326.84 | 0.00 |
September | 0.00 | 0.00 | 0.489059E+10 | 0.346509E+10 | 24641.16 | 14-SEP-07:02 | 13824.41 | 0.00 |
October | 0.00 | 0.00 | 0.129825E+10 | 0.864579E+09 | 9404.94 | 06-OCT-07:03 | 4816.68 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.365073E+11 | 0.243583E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114081E+11 | 0.759104E+10 | 25277.01 | 13824.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.169914E+09 | 0.146911E+09 | 4356.76 | 08-APR-12:00 | 3646.98 | 0.00 |
May | 0.00 | 0.00 | 0.102888E+10 | 0.874905E+09 | 9082.89 | 31-MAY-14:10 | 6304.29 | 0.00 |
June | 0.00 | 0.00 | 0.630441E+10 | 0.417549E+10 | 25163.24 | 25-JUN-08:62 | 11840.66 | 0.00 |
July | 0.00 | 0.00 | 0.112588E+11 | 0.686443E+10 | 25187.97 | 09-JUL-08:62 | 12070.34 | 0.00 |
August | 0.00 | 0.00 | 0.109654E+11 | 0.750285E+10 | 24915.52 | 06-AUG-08:62 | 10265.95 | 0.00 |
September | 0.00 | 0.00 | 0.476941E+10 | 0.337139E+10 | 24563.91 | 14-SEP-07:02 | 13631.58 | 0.00 |
October | 0.00 | 0.00 | 0.119512E+10 | 0.795162E+09 | 8115.44 | 04-OCT-13:00 | 5891.61 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.356919E+11 | 0.237311E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112588E+11 | 0.750285E+10 | 25187.97 | 13631.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.153999E+09 | 0.133764E+09 | 4559.36 | 08-APR-12:00 | 3852.43 | 0.00 |
May | 0.00 | 0.00 | 0.969371E+09 | 0.826423E+09 | 9195.56 | 31-MAY-14:10 | 6432.41 | 0.00 |
June | 0.00 | 0.00 | 0.613054E+10 | 0.410217E+10 | 27254.39 | 25-JUN-08:62 | 12103.37 | 0.00 |
July | 0.00 | 0.00 | 0.117468E+11 | 0.723260E+10 | 27579.71 | 22-JUL-07:02 | 11589.79 | 0.00 |
August | 0.00 | 0.00 | 0.116648E+11 | 0.806249E+10 | 27307.30 | 17-AUG-07:02 | 12643.33 | 0.00 |
September | 0.00 | 0.00 | 0.485268E+10 | 0.347261E+10 | 26858.09 | 14-SEP-07:02 | 13271.17 | 0.00 |
October | 0.00 | 0.00 | 0.113508E+10 | 0.765523E+09 | 8537.78 | 04-OCT-13:00 | 6273.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366532E+11 | 0.245956E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117468E+11 | 0.806249E+10 | 27579.71 | 13271.17 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193393E+10 | 0.42 | 2142.40 | 01-JAN-08:61 | 0.88 |
February | 0.176927E+10 | 0.43 | 2142.40 | 01-FEB-08:61 | 0.88 |
March | 0.176025E+10 | 0.39 | 2142.40 | 01-MAR-08:61 | 0.88 |
April | 0.157191E+10 | 0.37 | 2142.40 | 01-APR-07:01 | 0.88 |
May | 0.155512E+10 | 0.36 | 987.39 | 01-MAY-07:01 | 0.58 |
June | 0.152057E+10 | 0.36 | 2142.40 | 19-JUN-07:02 | 0.86 |
July | 0.159929E+10 | 0.36 | 2142.40 | 03-JUL-07:02 | 0.86 |
August | 0.161872E+10 | 0.36 | 2142.40 | 01-AUG-07:02 | 0.87 |
September | 0.151199E+10 | 0.36 | 2142.40 | 01-SEP-07:02 | 0.87 |
October | 0.155608E+10 | 0.36 | 1003.93 | 28-OCT-08:10 | 0.59 |
November | 0.163087E+10 | 0.38 | 2142.40 | 15-NOV-08:61 | 0.88 |
December | 0.184564E+10 | 0.41 | 2142.40 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.198736E+11 | 0.38 | |||
Minimum of Months | 0.151199E+10 | 0.36 | 987.39 | 0.58 | |
Maximum of Months | 0.193393E+10 | 0.43 | 2142.40 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.772774E+09 | 0.32 | 1186.90 | 01-JAN-08:61 | 0.91 |
February | 0.705419E+09 | 0.32 | 1186.90 | 01-FEB-08:61 | 0.91 |
March | 0.717342E+09 | 0.31 | 1186.90 | 01-MAR-08:61 | 0.91 |
April | 0.702393E+09 | 0.33 | 1186.90 | 02-APR-07:01 | 0.91 |
May | 0.798257E+09 | 0.37 | 515.70 | 30-MAY-07:03 | 0.58 |
June | 0.755166E+09 | 0.38 | 1186.90 | 19-JUN-07:02 | 0.90 |
July | 0.793989E+09 | 0.39 | 1186.90 | 03-JUL-07:02 | 0.90 |
August | 0.802840E+09 | 0.38 | 1186.90 | 01-AUG-07:02 | 0.90 |
September | 0.757341E+09 | 0.37 | 1186.90 | 01-SEP-07:02 | 0.90 |
October | 0.791792E+09 | 0.37 | 628.66 | 06-OCT-07:03 | 0.65 |
November | 0.689731E+09 | 0.33 | 1186.90 | 21-NOV-08:61 | 0.91 |
December | 0.729798E+09 | 0.30 | 1186.90 | 02-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.901684E+10 | 0.35 | |||
Minimum of Months | 0.689731E+09 | 0.30 | 515.70 | 0.58 | |
Maximum of Months | 0.802840E+09 | 0.39 | 1186.90 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.845418E+09 | 0.34 | 1196.33 | 01-JAN-08:61 | 0.91 |
February | 0.771000E+09 | 0.34 | 1196.33 | 01-FEB-07:01 | 0.91 |
March | 0.782313E+09 | 0.32 | 1196.33 | 01-MAR-07:02 | 0.91 |
April | 0.693866E+09 | 0.30 | 1196.33 | 02-APR-07:01 | 0.91 |
May | 0.699426E+09 | 0.30 | 482.66 | 01-MAY-07:40 | 0.55 |
June | 0.687016E+09 | 0.30 | 1196.33 | 15-JUN-06:03 | 0.89 |
July | 0.709675E+09 | 0.30 | 1196.33 | 02-JUL-07:03 | 0.90 |
August | 0.734339E+09 | 0.31 | 1196.33 | 01-AUG-06:02 | 0.89 |
September | 0.673704E+09 | 0.30 | 1196.33 | 01-SEP-06:02 | 0.89 |
October | 0.692661E+09 | 0.30 | 690.08 | 06-OCT-06:03 | 0.68 |
November | 0.720894E+09 | 0.31 | 1196.33 | 21-NOV-07:02 | 0.91 |
December | 0.800851E+09 | 0.33 | 1196.33 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.881116E+10 | 0.31 | |||
Minimum of Months | 0.673704E+09 | 0.30 | 482.66 | 0.55 | |
Maximum of Months | 0.845418E+09 | 0.34 | 1196.33 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.851772E+09 | 0.34 | 1196.07 | 01-JAN-08:61 | 0.91 |
February | 0.776122E+09 | 0.34 | 1196.07 | 01-FEB-07:01 | 0.91 |
March | 0.787091E+09 | 0.32 | 1196.07 | 01-MAR-07:02 | 0.91 |
April | 0.696320E+09 | 0.30 | 1196.07 | 02-APR-07:01 | 0.91 |
May | 0.699309E+09 | 0.30 | 531.31 | 01-MAY-07:10 | 0.59 |
June | 0.686831E+09 | 0.30 | 1196.07 | 15-JUN-06:03 | 0.89 |
July | 0.709674E+09 | 0.30 | 1196.07 | 02-JUL-07:03 | 0.90 |
August | 0.734576E+09 | 0.31 | 1196.07 | 01-AUG-06:02 | 0.89 |
September | 0.673565E+09 | 0.30 | 1196.07 | 01-SEP-06:02 | 0.89 |
October | 0.692592E+09 | 0.30 | 679.03 | 06-OCT-06:03 | 0.67 |
November | 0.724807E+09 | 0.31 | 1196.07 | 20-NOV-07:02 | 0.91 |
December | 0.806280E+09 | 0.33 | 1196.07 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.883894E+10 | 0.31 | |||
Minimum of Months | 0.673565E+09 | 0.30 | 531.31 | 0.59 | |
Maximum of Months | 0.851772E+09 | 0.34 | 1196.07 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.855264E+09 | 0.34 | 1188.79 | 01-JAN-08:61 | 0.91 |
February | 0.778980E+09 | 0.34 | 1188.79 | 01-FEB-07:01 | 0.91 |
March | 0.789360E+09 | 0.33 | 1188.79 | 01-MAR-07:02 | 0.91 |
April | 0.695890E+09 | 0.31 | 1188.79 | 02-APR-07:01 | 0.91 |
May | 0.695151E+09 | 0.30 | 542.34 | 01-MAY-07:06 | 0.60 |
June | 0.682227E+09 | 0.30 | 1188.79 | 16-JUN-06:03 | 0.89 |
July | 0.703721E+09 | 0.30 | 1188.79 | 02-JUL-07:03 | 0.89 |
August | 0.728144E+09 | 0.31 | 1188.79 | 01-AUG-06:02 | 0.89 |
September | 0.669198E+09 | 0.30 | 1188.79 | 01-SEP-06:02 | 0.89 |
October | 0.688576E+09 | 0.30 | 574.18 | 28-OCT-07:10 | 0.62 |
November | 0.725686E+09 | 0.31 | 1188.79 | 20-NOV-07:02 | 0.91 |
December | 0.809068E+09 | 0.33 | 1188.79 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.882127E+10 | 0.31 | |||
Minimum of Months | 0.669198E+09 | 0.30 | 542.34 | 0.60 | |
Maximum of Months | 0.855264E+09 | 0.34 | 1188.79 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138795E+10 | 0.31 | 2025.50 | 01-JAN-09:01 | 0.88 |
February | 0.126328E+10 | 0.31 | 2025.50 | 01-FEB-08:61 | 0.88 |
March | 0.127200E+10 | 0.30 | 2025.50 | 01-MAR-08:61 | 0.88 |
April | 0.110797E+10 | 0.27 | 2025.50 | 01-APR-07:01 | 0.87 |
May | 0.109469E+10 | 0.27 | 1384.59 | 01-MAY-07:01 | 0.73 |
June | 0.107665E+10 | 0.27 | 2025.50 | 16-JUN-07:03 | 0.86 |
July | 0.112027E+10 | 0.27 | 2025.50 | 02-JUL-08:62 | 0.86 |
August | 0.116418E+10 | 0.28 | 2025.50 | 01-AUG-07:02 | 0.87 |
September | 0.105346E+10 | 0.26 | 2025.50 | 01-SEP-07:02 | 0.86 |
October | 0.108337E+10 | 0.26 | 945.90 | 28-OCT-08:10 | 0.59 |
November | 0.116323E+10 | 0.28 | 2025.50 | 13-NOV-08:61 | 0.88 |
December | 0.130804E+10 | 0.30 | 2025.50 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.140951E+11 | 0.28 | |||
Minimum of Months | 0.105346E+10 | 0.26 | 945.90 | 0.59 | |
Maximum of Months | 0.138795E+10 | 0.31 | 2025.50 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.748901E+09 | 0.32 | 1090.33 | 01-JAN-09:01 | 0.91 |
February | 0.681928E+09 | 0.32 | 1090.33 | 01-FEB-08:61 | 0.91 |
March | 0.686149E+09 | 0.31 | 1090.33 | 01-MAR-08:61 | 0.91 |
April | 0.597154E+09 | 0.28 | 1090.33 | 01-APR-07:01 | 0.91 |
May | 0.589422E+09 | 0.28 | 802.65 | 01-MAY-07:01 | 0.78 |
June | 0.579312E+09 | 0.28 | 1090.33 | 19-JUN-07:02 | 0.89 |
July | 0.602071E+09 | 0.28 | 1090.33 | 02-JUL-08:62 | 0.89 |
August | 0.625571E+09 | 0.29 | 1090.33 | 01-AUG-07:02 | 0.90 |
September | 0.566954E+09 | 0.27 | 1090.33 | 01-SEP-07:02 | 0.89 |
October | 0.583221E+09 | 0.27 | 522.21 | 28-OCT-08:10 | 0.62 |
November | 0.627122E+09 | 0.29 | 1090.33 | 13-NOV-08:61 | 0.91 |
December | 0.705373E+09 | 0.31 | 1090.33 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.759318E+10 | 0.29 | |||
Minimum of Months | 0.566954E+09 | 0.27 | 522.21 | 0.62 | |
Maximum of Months | 0.748901E+09 | 0.32 | 1090.33 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.747620E+09 | 0.32 | 1084.75 | 01-JAN-09:01 | 0.91 |
February | 0.680975E+09 | 0.32 | 1084.75 | 01-FEB-08:61 | 0.91 |
March | 0.685190E+09 | 0.31 | 1084.75 | 01-MAR-08:61 | 0.91 |
April | 0.595669E+09 | 0.28 | 1084.75 | 01-APR-07:01 | 0.91 |
May | 0.586707E+09 | 0.28 | 895.78 | 01-MAY-07:01 | 0.83 |
June | 0.576187E+09 | 0.28 | 1084.75 | 19-JUN-07:02 | 0.89 |
July | 0.598597E+09 | 0.27 | 1084.75 | 02-JUL-08:62 | 0.89 |
August | 0.622020E+09 | 0.29 | 1084.75 | 01-AUG-07:02 | 0.90 |
September | 0.563994E+09 | 0.27 | 1084.75 | 01-SEP-07:02 | 0.89 |
October | 0.580421E+09 | 0.27 | 560.84 | 29-OCT-08:62 | 0.65 |
November | 0.625754E+09 | 0.29 | 1084.75 | 13-NOV-08:61 | 0.91 |
December | 0.704299E+09 | 0.31 | 1084.75 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.756743E+10 | 0.29 | |||
Minimum of Months | 0.563994E+09 | 0.27 | 560.84 | 0.65 | |
Maximum of Months | 0.747620E+09 | 0.32 | 1084.75 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.754617E+09 | 0.33 | 1081.16 | 01-JAN-09:01 | 0.91 |
February | 0.688118E+09 | 0.33 | 1081.16 | 01-FEB-08:61 | 0.91 |
March | 0.691646E+09 | 0.31 | 1081.16 | 01-MAR-08:61 | 0.91 |
April | 0.599005E+09 | 0.29 | 1081.16 | 01-APR-07:01 | 0.91 |
May | 0.585791E+09 | 0.28 | 1081.16 | 01-MAY-07:01 | 0.90 |
June | 0.573792E+09 | 0.28 | 1081.16 | 19-JUN-07:02 | 0.89 |
July | 0.595883E+09 | 0.27 | 1081.16 | 03-JUL-07:02 | 0.89 |
August | 0.619735E+09 | 0.29 | 1081.16 | 01-AUG-07:02 | 0.90 |
September | 0.562006E+09 | 0.27 | 1081.16 | 01-SEP-07:02 | 0.89 |
October | 0.579129E+09 | 0.27 | 695.61 | 29-OCT-08:62 | 0.73 |
November | 0.629635E+09 | 0.30 | 1081.16 | 13-NOV-08:61 | 0.91 |
December | 0.710662E+09 | 0.31 | 1081.16 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.759002E+10 | 0.29 | |||
Minimum of Months | 0.562006E+09 | 0.27 | 695.61 | 0.73 | |
Maximum of Months | 0.754617E+09 | 0.33 | 1081.16 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.866900E+09 | 0.37 | 1186.08 | 01-JAN-09:01 | 0.91 |
February | 0.794075E+09 | 0.37 | 1186.08 | 01-FEB-08:61 | 0.91 |
March | 0.784674E+09 | 0.32 | 1186.08 | 01-MAR-08:61 | 0.91 |
April | 0.672906E+09 | 0.29 | 1186.08 | 01-APR-07:01 | 0.91 |
May | 0.646386E+09 | 0.28 | 1186.08 | 01-MAY-07:01 | 0.90 |
June | 0.628705E+09 | 0.28 | 1186.08 | 19-JUN-07:02 | 0.89 |
July | 0.650409E+09 | 0.27 | 1186.08 | 03-JUL-07:02 | 0.89 |
August | 0.677760E+09 | 0.28 | 1186.08 | 01-AUG-07:02 | 0.89 |
September | 0.616026E+09 | 0.27 | 1186.08 | 01-SEP-07:02 | 0.89 |
October | 0.638188E+09 | 0.27 | 1167.14 | 29-OCT-08:62 | 0.90 |
November | 0.706028E+09 | 0.30 | 1186.08 | 01-NOV-07:01 | 0.91 |
December | 0.805250E+09 | 0.32 | 1186.08 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.848731E+10 | 0.30 | |||
Minimum of Months | 0.616026E+09 | 0.27 | 1167.14 | 0.89 | |
Maximum of Months | 0.866900E+09 | 0.37 | 1186.08 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193393E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176927E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.176187E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.245126E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.593469E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.923966E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.893799E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.491405E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.248905E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163087E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184564E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.446437E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.923966E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.772774E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.705419E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.720079E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.822292E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.139889E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.324270E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468146E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.456252E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268685E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140882E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.691532E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.729819E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224231E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.691532E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468146E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.845418E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.771000E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.783186E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.781888E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.111241E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.259162E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.376299E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.370148E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209635E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115115E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720951E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.800851E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.720951E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.376299E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.851772E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.776122E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.787572E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.778719E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110084E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258342E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.376305E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.370543E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209173E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113680E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.724807E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.806280E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191065E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.724807E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.376305E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.855264E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.778980E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.789567E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.768833E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107000E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.252471E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.370564E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364897E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204544E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110202E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.725686E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.809068E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188242E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.725686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.370564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.138795E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.126328E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127210E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.122415E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171743E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.432261E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.653048E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.652061E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.347894E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176972E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116323E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.130804E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.319585E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.653048E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.748901E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.681928E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.686161E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.652619E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.895572E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.220875E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.333296E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.332826E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178625E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.921397E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.627122E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.705373E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165753E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.627122E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.333296E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.747620E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.680975E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.685190E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.648506E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.881504E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.218444E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.330769E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.330527E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.176857E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.906269E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.625754E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.704299E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164461E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.625754E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.330769E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.754617E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.688118E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.691646E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.645522E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.855944E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213205E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.327205E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.327895E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173798E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.879655E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.629635E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.710662E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162768E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.629635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.327895E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.866900E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.794075E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.784674E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.715281E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.902040E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.215757E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.345852E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.351425E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181530E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.924016E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.706028E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.805250E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174439E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.706028E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.351425E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193393E+10 | 0.00 | 0.180218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176927E+10 | 0.00 | 0.172316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176025E+10 | 5652171.59 | 0.950208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157191E+10 | 0.597003E+09 | 0.317653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155512E+10 | 0.339031E+10 | 11814190.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152057E+10 | 0.176542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159929E+10 | 0.316152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161872E+10 | 0.297632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151199E+10 | 0.135911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155608E+10 | 0.366940E+10 | 58263393.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163087E+10 | 0.00 | 0.613521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184564E+10 | 0.00 | 0.135892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198736E+11 | 0.100286E+12 | 0.677265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193393E+10 | 0.316152E+11 | 0.180218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.772774E+09 | 0.00 | 0.576952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705419E+09 | 0.00 | 0.550787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.717342E+09 | 9903794.29 | 0.258171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702393E+09 | 0.447920E+09 | 0.636103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798257E+09 | 0.228364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.755166E+09 | 0.100985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.793989E+09 | 0.162647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802840E+09 | 0.154030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757341E+09 | 0.778775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791792E+09 | 0.247783E+10 | 93777.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689731E+09 | 6507810.55 | 0.159486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729798E+09 | 73768.35 | 0.400782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901684E+10 | 0.547798E+11 | 0.200980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.689731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802840E+09 | 0.162647E+11 | 0.576952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.845418E+09 | 0.00 | 0.694492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.771000E+09 | 0.00 | 0.653812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782313E+09 | 3113592.86 | 0.345232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693866E+09 | 0.329876E+09 | 0.999660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699426E+09 | 0.158643E+10 | 169095.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687016E+09 | 0.775612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709675E+09 | 0.128540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.734339E+09 | 0.122569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.673704E+09 | 0.579391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692661E+09 | 0.183815E+10 | 3966639.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720894E+09 | 203542.57 | 0.222741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800851E+09 | 0.00 | 0.507697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881116E+10 | 0.424187E+11 | 0.252435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845418E+09 | 0.128540E+11 | 0.694492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.851772E+09 | 0.00 | 0.720846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776122E+09 | 0.00 | 0.674711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.787091E+09 | 1702601.18 | 0.366018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.696320E+09 | 0.307730E+09 | 0.111291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699309E+09 | 0.154133E+10 | 1824643.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.686831E+09 | 0.772208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709674E+09 | 0.128565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.734576E+09 | 0.122757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.673565E+09 | 0.577626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692592E+09 | 0.177881E+10 | 7829635.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724807E+09 | 0.00 | 0.240124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.806280E+09 | 0.00 | 0.530688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883894E+10 | 0.422602E+11 | 0.264464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.851772E+09 | 0.128565E+11 | 0.720846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.855264E+09 | 0.00 | 0.760214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.778980E+09 | 0.00 | 0.709109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789360E+09 | 728794.02 | 0.398080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695890E+09 | 0.270641E+09 | 0.128599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695151E+09 | 0.143490E+10 | 6266676.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682227E+09 | 0.748222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.703721E+09 | 0.126177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728144E+09 | 0.120514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669198E+09 | 0.559234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688576E+09 | 0.165104E+10 | 17803821.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725686E+09 | 0.00 | 0.264156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.809068E+09 | 0.00 | 0.565621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882127E+10 | 0.411009E+11 | 0.282818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.855264E+09 | 0.126177E+11 | 0.760214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138795E+10 | 0.00 | 0.148599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126328E+10 | 0.00 | 0.137714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127200E+10 | 336645.00 | 0.809777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110797E+10 | 0.420880E+09 | 0.281734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109469E+10 | 0.234244E+10 | 44782805.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107665E+10 | 0.129642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112027E+10 | 0.224310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116418E+10 | 0.217524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105346E+10 | 0.969317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108337E+10 | 0.269121E+10 | 61675923.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116323E+10 | 0.00 | 0.550403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130804E+10 | 0.00 | 0.112679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140951E+11 | 0.722957E+11 | 0.564247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138795E+10 | 0.224310E+11 | 0.148599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.748901E+09 | 0.00 | 0.773396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681928E+09 | 0.00 | 0.717822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686149E+09 | 41055.52 | 0.423532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.597154E+09 | 0.203970E+09 | 0.148438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589422E+09 | 0.117091E+10 | 29797480.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.579312E+09 | 0.661227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602071E+09 | 0.115033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.625571E+09 | 0.111517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.566954E+09 | 0.495310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583221E+09 | 0.134889E+10 | 33513824.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627122E+09 | 0.00 | 0.287783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.705373E+09 | 0.00 | 0.585922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759318E+10 | 0.369442E+11 | 0.294322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.748901E+09 | 0.115033E+11 | 0.773396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.747620E+09 | 0.00 | 0.782269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680975E+09 | 0.00 | 0.726921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685190E+09 | 81.12 | 0.433817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595669E+09 | 0.193904E+09 | 0.155198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586707E+09 | 0.112615E+10 | 43789300.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576187E+09 | 0.652139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.598597E+09 | 0.114081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.622020E+09 | 0.110689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.563994E+09 | 0.489059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.580421E+09 | 0.129825E+10 | 42008986.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625754E+09 | 0.00 | 0.295269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704299E+09 | 0.00 | 0.595515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.756743E+10 | 0.365073E+11 | 0.299757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.563994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.747620E+09 | 0.114081E+11 | 0.782269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.754617E+09 | 0.00 | 0.823759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688118E+09 | 0.00 | 0.768358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691646E+09 | 0.00 | 0.473279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599005E+09 | 0.169914E+09 | 0.179507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.585791E+09 | 0.102888E+10 | 91569840.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573792E+09 | 0.630441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.595883E+09 | 0.112588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.619735E+09 | 0.109654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562006E+09 | 0.476941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.579129E+09 | 0.119512E+10 | 71328658.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.629635E+09 | 0.00 | 0.322197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.710662E+09 | 0.00 | 0.634395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759002E+10 | 0.356919E+11 | 0.321778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.754617E+09 | 0.112588E+11 | 0.823759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.866900E+09 | 0.00 | 0.103659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.794075E+09 | 0.00 | 0.976971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784674E+09 | 0.00 | 0.622060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672906E+09 | 0.153999E+09 | 0.263055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646386E+09 | 0.969371E+09 | 0.267431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.628705E+09 | 0.613054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650409E+09 | 0.117468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.677760E+09 | 0.116648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616026E+09 | 0.485268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638188E+09 | 0.113508E+10 | 0.205494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706028E+09 | 0.00 | 0.413177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805250E+09 | 0.00 | 0.791998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.848731E+10 | 0.366532E+11 | 0.415114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.616026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.866900E+09 | 0.117468E+11 | 0.103659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176025E+10 | 0.00 | 0.00 | 0.00 | 1615746.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157191E+10 | 0.00 | 0.00 | 0.00 | 0.163454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155512E+10 | 0.00 | 0.00 | 0.00 | 0.896144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152057E+10 | 0.00 | 0.00 | 0.00 | 0.441412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159929E+10 | 0.00 | 0.00 | 0.00 | 0.764037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161872E+10 | 0.00 | 0.00 | 0.00 | 0.731927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151199E+10 | 0.00 | 0.00 | 0.00 | 0.340207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155608E+10 | 0.00 | 0.00 | 0.00 | 0.932966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198736E+11 | 0.00 | 0.00 | 0.00 | 0.247700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193393E+10 | 0.00 | 0.00 | 0.00 | 0.764037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.772774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.717342E+09 | 0.00 | 0.00 | 0.00 | 2736832.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702393E+09 | 0.00 | 0.00 | 0.00 | 0.119899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798257E+09 | 0.00 | 0.00 | 0.00 | 0.600628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.755166E+09 | 0.00 | 0.00 | 0.00 | 0.248753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.793989E+09 | 0.00 | 0.00 | 0.00 | 0.388747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802840E+09 | 0.00 | 0.00 | 0.00 | 0.375968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757341E+09 | 0.00 | 0.00 | 0.00 | 0.192951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791792E+09 | 0.00 | 0.00 | 0.00 | 0.617032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689731E+09 | 0.00 | 0.00 | 0.00 | 1800802.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729798E+09 | 0.00 | 0.00 | 0.00 | 20814.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901684E+10 | 0.00 | 0.00 | 0.00 | 0.134063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.689731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802840E+09 | 0.00 | 0.00 | 0.00 | 0.388747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.845418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.771000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782313E+09 | 0.00 | 0.00 | 0.00 | 873117.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693866E+09 | 0.00 | 0.00 | 0.00 | 88022227.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699426E+09 | 0.00 | 0.00 | 0.00 | 0.412983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687016E+09 | 0.00 | 0.00 | 0.00 | 0.190460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709675E+09 | 0.00 | 0.00 | 0.00 | 0.305332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.734339E+09 | 0.00 | 0.00 | 0.00 | 0.296714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.673704E+09 | 0.00 | 0.00 | 0.00 | 0.142264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692661E+09 | 0.00 | 0.00 | 0.00 | 0.458493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720894E+09 | 0.00 | 0.00 | 0.00 | 57562.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881116E+10 | 0.00 | 0.00 | 0.00 | 0.103081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845418E+09 | 0.00 | 0.00 | 0.00 | 0.305332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.851772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.787091E+09 | 0.00 | 0.00 | 0.00 | 480323.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.696320E+09 | 0.00 | 0.00 | 0.00 | 82399155.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699309E+09 | 0.00 | 0.00 | 0.00 | 0.401527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.686831E+09 | 0.00 | 0.00 | 0.00 | 0.189659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709674E+09 | 0.00 | 0.00 | 0.00 | 0.305338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.734576E+09 | 0.00 | 0.00 | 0.00 | 0.297085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.673565E+09 | 0.00 | 0.00 | 0.00 | 0.141817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692592E+09 | 0.00 | 0.00 | 0.00 | 0.444210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.806280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883894E+10 | 0.00 | 0.00 | 0.00 | 0.102676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.851772E+09 | 0.00 | 0.00 | 0.00 | 0.305338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.855264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.778980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789360E+09 | 0.00 | 0.00 | 0.00 | 206961.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695890E+09 | 0.00 | 0.00 | 0.00 | 72942939.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695151E+09 | 0.00 | 0.00 | 0.00 | 0.374850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682227E+09 | 0.00 | 0.00 | 0.00 | 0.184248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.703721E+09 | 0.00 | 0.00 | 0.00 | 0.300192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728144E+09 | 0.00 | 0.00 | 0.00 | 0.292083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669198E+09 | 0.00 | 0.00 | 0.00 | 0.137624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688576E+09 | 0.00 | 0.00 | 0.00 | 0.413449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.809068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882127E+10 | 0.00 | 0.00 | 0.00 | 0.100029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.855264E+09 | 0.00 | 0.00 | 0.00 | 0.300192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127200E+10 | 0.00 | 0.00 | 0.00 | 98043.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110797E+10 | 0.00 | 0.00 | 0.00 | 0.116176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109469E+10 | 0.00 | 0.00 | 0.00 | 0.622741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107665E+10 | 0.00 | 0.00 | 0.00 | 0.324596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112027E+10 | 0.00 | 0.00 | 0.00 | 0.541021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116418E+10 | 0.00 | 0.00 | 0.00 | 0.535643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105346E+10 | 0.00 | 0.00 | 0.00 | 0.242548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108337E+10 | 0.00 | 0.00 | 0.00 | 0.686344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140951E+11 | 0.00 | 0.00 | 0.00 | 0.178634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138795E+10 | 0.00 | 0.00 | 0.00 | 0.541021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.748901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686149E+09 | 0.00 | 0.00 | 0.00 | 11761.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.597154E+09 | 0.00 | 0.00 | 0.00 | 55465305.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589422E+09 | 0.00 | 0.00 | 0.00 | 0.306150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.579312E+09 | 0.00 | 0.00 | 0.00 | 0.162944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602071E+09 | 0.00 | 0.00 | 0.00 | 0.273089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.625571E+09 | 0.00 | 0.00 | 0.00 | 0.270269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.566954E+09 | 0.00 | 0.00 | 0.00 | 0.121929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583221E+09 | 0.00 | 0.00 | 0.00 | 0.338176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.705373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759318E+10 | 0.00 | 0.00 | 0.00 | 0.898211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.748901E+09 | 0.00 | 0.00 | 0.00 | 0.273089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.747620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685190E+09 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595669E+09 | 0.00 | 0.00 | 0.00 | 52836281.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586707E+09 | 0.00 | 0.00 | 0.00 | 0.294797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576187E+09 | 0.00 | 0.00 | 0.00 | 0.160825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.598597E+09 | 0.00 | 0.00 | 0.00 | 0.270909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.622020E+09 | 0.00 | 0.00 | 0.00 | 0.268325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.563994E+09 | 0.00 | 0.00 | 0.00 | 0.120458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.580421E+09 | 0.00 | 0.00 | 0.00 | 0.325848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.756743E+10 | 0.00 | 0.00 | 0.00 | 0.887865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.563994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.747620E+09 | 0.00 | 0.00 | 0.00 | 0.270909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.754617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599005E+09 | 0.00 | 0.00 | 0.00 | 46517375.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.585791E+09 | 0.00 | 0.00 | 0.00 | 0.270153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573792E+09 | 0.00 | 0.00 | 0.00 | 0.155826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.595883E+09 | 0.00 | 0.00 | 0.00 | 0.267617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.619735E+09 | 0.00 | 0.00 | 0.00 | 0.265921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562006E+09 | 0.00 | 0.00 | 0.00 | 0.117597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.579129E+09 | 0.00 | 0.00 | 0.00 | 0.300526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.629635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.710662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759002E+10 | 0.00 | 0.00 | 0.00 | 0.868681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.754617E+09 | 0.00 | 0.00 | 0.00 | 0.267617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.866900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.794075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672906E+09 | 0.00 | 0.00 | 0.00 | 42374647.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646386E+09 | 0.00 | 0.00 | 0.00 | 0.255654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.628705E+09 | 0.00 | 0.00 | 0.00 | 0.152887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650409E+09 | 0.00 | 0.00 | 0.00 | 0.280811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.677760E+09 | 0.00 | 0.00 | 0.00 | 0.283649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616026E+09 | 0.00 | 0.00 | 0.00 | 0.119927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638188E+09 | 0.00 | 0.00 | 0.00 | 0.285829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.848731E+10 | 0.00 | 0.00 | 0.00 | 0.895660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.616026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.866900E+09 | 0.00 | 0.00 | 0.00 | 0.283649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.599349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110817E+11 | 0.00 | 0.00 | 0.52 |
February | 0.585149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103910E+11 | 0.00 | 0.00 | 0.53 |
March | 0.857892E+10 | 0.00 | 0.00 | 71400.94 | 0.00 | 0.467815E+10 | 93898469.90 | 0.00 | 0.53 |
April | 0.650797E+10 | 27376847.25 | 0.00 | 2245181.69 | 0.00 | 0.121317E+10 | 0.160738E+10 | 0.00 | 0.59 |
May | 0.270564E+10 | 0.308323E+09 | 0.00 | 9491552.86 | 0.00 | 0.00 | 0.465624E+10 | 0.00 | 0.74 |
June | 20081139.93 | 0.377993E+10 | 0.00 | 7915272.87 | 0.00 | 0.00 | 0.235094E+10 | 0.00 | 0.75 |
July | 0.00 | 0.102256E+11 | 0.00 | 129188.07 | 0.00 | 0.00 | 6493981.53 | 0.00 | 0.54 |
August | 457867.55 | 0.834606E+10 | 0.00 | 3165636.88 | 0.00 | 0.00 | 0.341676E+09 | 0.00 | 0.60 |
September | 0.177043E+09 | 0.218255E+10 | 0.00 | 13048835.82 | 0.00 | 0.00 | 0.425976E+10 | 0.00 | 0.84 |
October | 0.358719E+10 | 0.192864E+09 | 0.00 | 10556473.96 | 0.00 | 2435426.02 | 0.548428E+10 | 0.00 | 0.77 |
November | 0.862985E+10 | 0.00 | 0.00 | 300137.94 | 0.00 | 0.281237E+10 | 0.329374E+09 | 0.00 | 0.53 |
December | 0.844079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704365E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.504929E+11 | 0.250627E+11 | 0.00 | 46923681.03 | 0.00 | 0.372224E+11 | 0.191300E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.862985E+10 | 0.102256E+11 | 0.00 | 13048835.82 | 0.00 | 0.110817E+11 | 0.548428E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349760E+10 | 0.00 | 0.00 | 0.38 |
February | 0.264012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324552E+10 | 0.00 | 0.00 | 0.38 |
March | 0.379042E+10 | 0.00 | 0.00 | 126218.22 | 0.00 | 0.110243E+10 | 0.115067E+09 | 0.00 | 0.40 |
April | 0.239889E+10 | 14918319.55 | 0.00 | 2021803.86 | 0.00 | 0.226810E+09 | 0.137693E+10 | 0.00 | 0.53 |
May | 0.559875E+09 | 0.156049E+09 | 0.00 | 6261250.30 | 0.00 | 0.00 | 0.339361E+10 | 0.00 | 0.77 |
June | 14612.22 | 0.190296E+10 | 0.00 | 3523538.87 | 0.00 | 0.00 | 0.944061E+09 | 0.00 | 0.65 |
July | 0.00 | 0.465461E+10 | 0.00 | 46135.78 | 0.00 | 0.00 | 811765.13 | 0.00 | 0.44 |
August | 118055.30 | 0.381340E+10 | 0.00 | 973769.39 | 0.00 | 0.00 | 83280920.29 | 0.00 | 0.48 |
September | 32329136.62 | 0.106558E+10 | 0.00 | 6213058.86 | 0.00 | 0.00 | 0.207138E+10 | 0.00 | 0.77 |
October | 0.871385E+09 | 0.117261E+09 | 0.00 | 6679263.99 | 0.00 | 0.00 | 0.358539E+10 | 0.00 | 0.77 |
November | 0.339190E+10 | 0.00 | 0.00 | 731426.09 | 0.00 | 0.640225E+09 | 0.613734E+09 | 0.00 | 0.43 |
December | 0.336397E+10 | 0.00 | 0.00 | 1393.70 | 0.00 | 0.219960E+10 | 1115894.31 | 0.00 | 0.38 |
Annual Sum or Average | 0.197096E+11 | 0.117248E+11 | 0.00 | 26577859.06 | 0.00 | 0.109122E+11 | 0.121854E+11 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.379042E+10 | 0.465461E+10 | 0.00 | 6679263.99 | 0.00 | 0.349760E+10 | 0.358539E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440464E+10 | 0.00 | 0.00 | 0.41 |
February | 0.216370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403621E+10 | 0.00 | 0.00 | 0.41 |
March | 0.343823E+10 | 0.00 | 0.00 | 32000.66 | 0.00 | 0.169757E+10 | 39705578.51 | 0.00 | 0.42 |
April | 0.254344E+10 | 14618902.68 | 0.00 | 902990.37 | 0.00 | 0.336118E+09 | 0.659101E+09 | 0.00 | 0.48 |
May | 0.100947E+10 | 0.149297E+09 | 0.00 | 3240507.81 | 1442911.56 | 0.00 | 0.189380E+10 | 0.00 | 0.64 |
June | 60159231.38 | 0.158234E+10 | 0.00 | 2255113.01 | 66554181.55 | 0.00 | 0.694450E+09 | 0.00 | 0.59 |
July | 214008.44 | 0.385428E+10 | 0.00 | 379151.07 | 0.207694E+09 | 0.00 | 10476434.11 | 0.00 | 0.43 |
August | 5286269.12 | 0.321543E+10 | 0.00 | 1094897.05 | 0.176682E+09 | 0.00 | 0.168736E+09 | 0.00 | 0.49 |
September | 0.170181E+09 | 0.885033E+09 | 0.00 | 4068144.24 | 39309965.38 | 0.00 | 0.146362E+10 | 0.00 | 0.67 |
October | 0.128929E+10 | 0.100669E+09 | 0.00 | 3714743.00 | 408402.50 | 0.00 | 0.205368E+10 | 0.00 | 0.63 |
November | 0.318705E+10 | 0.00 | 0.00 | 220204.30 | 0.00 | 0.108514E+10 | 0.216596E+09 | 0.00 | 0.42 |
December | 0.294445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287679E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.188632E+11 | 0.980167E+10 | 0.00 | 15907751.51 | 0.492091E+09 | 0.144365E+11 | 0.720015E+10 | 0.00 | 0.50 |
Minimum of Months | 214008.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.343823E+10 | 0.385428E+10 | 0.00 | 4068144.24 | 0.207694E+09 | 0.440464E+10 | 0.205368E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464458E+10 | 0.00 | 0.00 | 0.41 |
February | 0.194193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425806E+10 | 0.00 | 0.00 | 0.41 |
March | 0.331216E+10 | 0.00 | 0.00 | 24101.89 | 0.00 | 0.181982E+10 | 33313383.03 | 0.00 | 0.42 |
April | 0.250766E+10 | 14317481.54 | 0.00 | 797368.02 | 0.00 | 0.384196E+09 | 0.606979E+09 | 0.00 | 0.47 |
May | 0.105705E+10 | 0.148879E+09 | 0.00 | 3041438.46 | 1436751.61 | 403088.45 | 0.178026E+10 | 0.00 | 0.63 |
June | 60312223.19 | 0.157888E+10 | 0.00 | 2241120.00 | 66343344.05 | 0.00 | 0.696748E+09 | 0.00 | 0.59 |
July | 230739.58 | 0.385426E+10 | 0.00 | 391038.90 | 0.207472E+09 | 0.00 | 10469477.97 | 0.00 | 0.42 |
August | 6657135.50 | 0.321782E+10 | 0.00 | 1106566.20 | 0.176590E+09 | 0.00 | 0.168108E+09 | 0.00 | 0.49 |
September | 0.171301E+09 | 0.884031E+09 | 0.00 | 4032690.50 | 39230352.66 | 0.00 | 0.145349E+10 | 0.00 | 0.67 |
October | 0.132066E+10 | 98718706.21 | 0.00 | 3559400.78 | 383512.84 | 0.00 | 0.198638E+10 | 0.00 | 0.63 |
November | 0.299859E+10 | 0.00 | 0.00 | 163495.55 | 0.00 | 0.128021E+10 | 0.177626E+09 | 0.00 | 0.42 |
December | 0.273611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308448E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.179246E+11 | 0.979691E+10 | 0.00 | 15357220.29 | 0.491456E+09 | 0.154718E+11 | 0.691338E+10 | 0.00 | 0.50 |
Minimum of Months | 230739.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.331216E+10 | 0.385426E+10 | 0.00 | 4032690.50 | 0.207472E+09 | 0.464458E+10 | 0.198638E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497286E+10 | 0.00 | 0.00 | 0.41 |
February | 0.156275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463724E+10 | 0.00 | 0.00 | 0.41 |
March | 0.294115E+10 | 0.00 | 0.00 | 16090.41 | 0.00 | 0.218696E+10 | 24982079.18 | 0.00 | 0.42 |
April | 0.243889E+10 | 13767614.56 | 0.00 | 632587.76 | 0.00 | 0.519440E+09 | 0.480961E+09 | 0.00 | 0.47 |
May | 0.111741E+10 | 0.146996E+09 | 0.00 | 2613237.60 | 1422783.75 | 2026376.92 | 0.158518E+10 | 0.00 | 0.61 |
June | 61503152.38 | 0.154770E+10 | 0.00 | 2103898.36 | 65472483.55 | 0.00 | 0.689354E+09 | 0.00 | 0.59 |
July | 236002.28 | 0.381373E+10 | 0.00 | 341939.48 | 0.205891E+09 | 0.00 | 10350723.36 | 0.00 | 0.42 |
August | 5181773.89 | 0.319129E+10 | 0.00 | 1048375.37 | 0.175831E+09 | 0.00 | 0.168558E+09 | 0.00 | 0.49 |
September | 0.185044E+09 | 0.868120E+09 | 0.00 | 3802588.76 | 38803516.46 | 0.00 | 0.140341E+10 | 0.00 | 0.66 |
October | 0.140897E+10 | 93683261.98 | 0.00 | 3203396.72 | 316289.44 | 1570008.46 | 0.181888E+10 | 0.00 | 0.62 |
November | 0.282090E+10 | 0.00 | 0.00 | 99944.08 | 0.00 | 0.148420E+10 | 0.105681E+09 | 0.00 | 0.42 |
December | 0.237261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344743E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.163982E+11 | 0.967528E+10 | 0.00 | 13862058.55 | 0.487737E+09 | 0.172517E+11 | 0.628737E+10 | 0.00 | 0.49 |
Minimum of Months | 236002.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.294115E+10 | 0.381373E+10 | 0.00 | 3802588.76 | 0.205891E+09 | 0.497286E+10 | 0.181888E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106302E+11 | 0.00 | 0.00 | 0.38 |
February | 0.150381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100336E+11 | 0.00 | 0.00 | 0.38 |
March | 0.457227E+10 | 0.00 | 0.00 | 11085.93 | 0.00 | 0.503603E+10 | 26376111.47 | 0.00 | 0.39 |
April | 0.455667E+10 | 16644592.80 | 0.00 | 784273.61 | 60876.31 | 0.114189E+10 | 0.649206E+09 | 0.00 | 0.41 |
May | 0.238731E+10 | 0.251350E+09 | 0.00 | 3527768.61 | 1579455.13 | 3896339.80 | 0.237913E+10 | 0.00 | 0.51 |
June | 36916176.81 | 0.271119E+10 | 0.00 | 3671454.63 | 36484868.20 | 0.00 | 0.134299E+10 | 0.00 | 0.53 |
July | 466206.77 | 0.699934E+10 | 0.00 | 428068.75 | 0.109719E+09 | 0.00 | 9876493.13 | 0.00 | 0.39 |
August | 3721083.17 | 0.600472E+10 | 0.00 | 1552250.55 | 77260637.15 | 0.00 | 0.204924E+09 | 0.00 | 0.43 |
September | 0.237673E+09 | 0.154636E+10 | 0.00 | 6537089.67 | 8304725.15 | 0.00 | 0.256173E+10 | 0.00 | 0.58 |
October | 0.267348E+10 | 0.127758E+09 | 0.00 | 5118239.56 | 0.00 | 3144327.10 | 0.304475E+10 | 0.00 | 0.53 |
November | 0.469883E+10 | 0.00 | 0.00 | 116519.52 | 0.00 | 0.333950E+10 | 0.134929E+09 | 0.00 | 0.38 |
December | 0.309583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781246E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.251983E+11 | 0.176574E+11 | 0.00 | 21746750.83 | 0.233409E+09 | 0.380007E+11 | 0.103539E+11 | 0.00 | 0.44 |
Minimum of Months | 466206.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.469883E+10 | 0.699934E+10 | 0.00 | 6537089.67 | 0.109719E+09 | 0.106302E+11 | 0.304475E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.645316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537382E+10 | 0.00 | 0.00 | 0.38 |
February | 0.577607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518051E+10 | 0.00 | 0.00 | 0.38 |
March | 0.207805E+10 | 0.00 | 0.00 | 3886.17 | 0.00 | 0.271425E+10 | 11437460.85 | 0.00 | 0.39 |
April | 0.217491E+10 | 8332672.19 | 0.00 | 346381.02 | 41497.33 | 0.696456E+09 | 0.284885E+09 | 0.00 | 0.41 |
May | 0.122721E+10 | 0.125079E+09 | 0.00 | 1667336.82 | 781653.88 | 2556389.61 | 0.113382E+10 | 0.00 | 0.52 |
June | 21673100.58 | 0.134866E+10 | 0.00 | 1838682.74 | 17852076.37 | 0.00 | 0.691266E+09 | 0.00 | 0.54 |
July | 260600.87 | 0.348875E+10 | 0.00 | 197109.49 | 54033047.25 | 0.00 | 4923482.86 | 0.00 | 0.39 |
August | 2198511.31 | 0.299445E+10 | 0.00 | 766312.62 | 38216515.20 | 0.00 | 0.105800E+09 | 0.00 | 0.44 |
September | 0.123786E+09 | 0.769854E+09 | 0.00 | 3297706.57 | 4031499.77 | 0.00 | 0.130452E+10 | 0.00 | 0.59 |
October | 0.135942E+10 | 62684623.64 | 0.00 | 2532315.47 | 0.00 | 840705.34 | 0.151518E+10 | 0.00 | 0.54 |
November | 0.220917E+10 | 0.00 | 0.00 | 44586.87 | 0.00 | 0.179764E+10 | 60888320.17 | 0.00 | 0.38 |
December | 0.133442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410816E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.117540E+11 | 0.879781E+10 | 0.00 | 10694317.76 | 0.114956E+09 | 0.198742E+11 | 0.511273E+10 | 0.00 | 0.44 |
Minimum of Months | 260600.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.220917E+10 | 0.348875E+10 | 0.00 | 3297706.57 | 54033047.25 | 0.537382E+10 | 0.151518E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.575637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544342E+10 | 0.00 | 0.00 | 0.38 |
February | 0.500388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525783E+10 | 0.00 | 0.00 | 0.38 |
March | 0.197420E+10 | 0.00 | 0.00 | 2856.83 | 0.00 | 0.281771E+10 | 9015314.14 | 0.00 | 0.39 |
April | 0.213283E+10 | 8150503.61 | 0.00 | 314044.26 | 101953.25 | 0.768752E+09 | 0.240571E+09 | 0.00 | 0.41 |
May | 0.128009E+10 | 0.124094E+09 | 0.00 | 1518933.32 | 781824.56 | 3008855.43 | 0.103409E+10 | 0.00 | 0.51 |
June | 25379475.23 | 0.133604E+10 | 0.00 | 1789409.25 | 17735136.57 | 0.00 | 0.683470E+09 | 0.00 | 0.54 |
July | 272703.19 | 0.346969E+10 | 0.00 | 202359.88 | 53824665.68 | 0.00 | 5096442.79 | 0.00 | 0.39 |
August | 2177440.36 | 0.298417E+10 | 0.00 | 748626.89 | 38129842.02 | 0.00 | 0.105813E+09 | 0.00 | 0.44 |
September | 0.127076E+09 | 0.763886E+09 | 0.00 | 3224804.51 | 3999134.20 | 0.00 | 0.128580E+10 | 0.00 | 0.59 |
October | 0.138445E+10 | 60797633.25 | 0.00 | 2420570.96 | 0.00 | 2341703.33 | 0.145981E+10 | 0.00 | 0.53 |
November | 0.211864E+10 | 0.00 | 0.00 | 34393.34 | 0.00 | 0.189079E+10 | 48999329.09 | 0.00 | 0.38 |
December | 0.124724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419533E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.113684E+11 | 0.874683E+10 | 0.00 | 10255999.23 | 0.114573E+09 | 0.203792E+11 | 0.487266E+10 | 0.00 | 0.44 |
Minimum of Months | 272703.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.213283E+10 | 0.346969E+10 | 0.00 | 3224804.51 | 53824665.68 | 0.544342E+10 | 0.145981E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.376306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564284E+10 | 0.00 | 0.00 | 0.38 |
February | 0.281806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547634E+10 | 0.00 | 0.00 | 0.38 |
March | 0.166473E+10 | 0.00 | 0.00 | 239.54 | 0.00 | 0.312639E+10 | 2615689.89 | 0.00 | 0.39 |
April | 0.192005E+10 | 7820548.85 | 0.00 | 264870.77 | 274016.50 | 0.994127E+09 | 0.197873E+09 | 0.00 | 0.41 |
May | 0.136397E+10 | 0.122126E+09 | 0.00 | 1208414.96 | 847846.58 | 16921664.11 | 0.837708E+09 | 0.00 | 0.49 |
June | 33513679.83 | 0.130496E+10 | 0.00 | 1645120.20 | 17639010.47 | 0.00 | 0.666105E+09 | 0.00 | 0.53 |
July | 301897.43 | 0.344010E+10 | 0.00 | 182689.21 | 53623042.15 | 0.00 | 6295788.45 | 0.00 | 0.39 |
August | 1121473.47 | 0.297198E+10 | 0.00 | 701907.88 | 38135339.97 | 0.00 | 0.106670E+09 | 0.00 | 0.43 |
September | 0.145790E+09 | 0.753128E+09 | 0.00 | 3022660.64 | 3973891.80 | 0.00 | 0.123002E+10 | 0.00 | 0.58 |
October | 0.143406E+10 | 57285410.98 | 0.00 | 2156558.26 | 0.00 | 3625477.05 | 0.134385E+10 | 0.00 | 0.52 |
November | 0.185455E+10 | 0.00 | 0.00 | 17722.62 | 0.00 | 0.215466E+10 | 33261381.67 | 0.00 | 0.38 |
December | 0.808913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463363E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.988512E+10 | 0.865741E+10 | 0.00 | 9200184.08 | 0.114493E+09 | 0.220485E+11 | 0.442440E+10 | 0.00 | 0.44 |
Minimum of Months | 301897.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.192005E+10 | 0.344010E+10 | 0.00 | 3022660.64 | 53623042.15 | 0.564284E+10 | 0.134385E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20256635.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597848E+10 | 0.00 | 0.00 | 0.38 |
February | 14813609.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572587E+10 | 0.00 | 0.00 | 0.38 |
March | 0.711280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404650E+10 | 0.00 | 0.00 | 0.39 |
April | 0.125762E+10 | 7624242.79 | 0.00 | 214491.82 | 803307.37 | 0.162335E+10 | 0.172073E+09 | 0.00 | 0.41 |
May | 0.134672E+10 | 0.120907E+09 | 0.00 | 898971.47 | 1302494.28 | 0.109515E+09 | 0.649988E+09 | 0.00 | 0.50 |
June | 52600572.85 | 0.121227E+10 | 0.00 | 1546135.91 | 18711946.87 | 0.00 | 0.684544E+09 | 0.00 | 0.55 |
July | 333469.11 | 0.339763E+10 | 0.00 | 227174.73 | 52552210.29 | 0.00 | 21316468.81 | 0.00 | 0.39 |
August | 1619310.92 | 0.297400E+10 | 0.00 | 765227.56 | 37882004.87 | 0.00 | 0.124991E+09 | 0.00 | 0.45 |
September | 0.217864E+09 | 0.723569E+09 | 0.00 | 2866211.71 | 3852784.42 | 0.00 | 0.116776E+10 | 0.00 | 0.60 |
October | 0.147093E+10 | 56761675.72 | 0.00 | 1917280.09 | 0.00 | 40367363.68 | 0.119806E+10 | 0.00 | 0.53 |
November | 0.121779E+10 | 0.00 | 0.00 | 6552.06 | 0.00 | 0.276879E+10 | 13618513.08 | 0.00 | 0.38 |
December | 96602142.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532651E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.640843E+10 | 0.849276E+10 | 0.00 | 8442045.35 | 0.115105E+09 | 0.256194E+11 | 0.403236E+10 | 0.00 | 0.44 |
Minimum of Months | 333469.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.147093E+10 | 0.339763E+10 | 0.00 | 2866211.71 | 52552210.29 | 0.597848E+10 | 0.119806E+10 | 0.00 | 0.60 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.110647E+12 | 0.392915E+11 | 0.00 | 0.815382E+11 | 0.236417E+11 |
February | 0.199588E+12 | 0.366182E+11 | 0.00 | 0.779276E+11 | 0.221970E+11 |
March | 0.365227E+12 | 0.292725E+11 | 0.00 | 0.647269E+11 | 0.127279E+11 |
April | 0.410450E+12 | 0.185427E+11 | 0.00 | 0.434765E+11 | 0.832070E+10 |
May | 0.543469E+12 | 0.104318E+11 | 0.00 | 0.319430E+11 | 0.215374E+11 |
June | 0.540997E+12 | -0.514336E+10 | 0.00 | -0.830719E+10 | 0.111439E+12 |
July | 0.533110E+12 | -0.186974E+11 | 0.00 | -0.473988E+11 | 0.191527E+12 |
August | 0.512402E+12 | -0.150967E+11 | 0.00 | -0.382238E+11 | 0.184608E+12 |
September | 0.346498E+12 | 0.474086E+09 | 0.00 | 0.928795E+10 | 0.845902E+11 |
October | 0.318924E+12 | 0.135817E+11 | 0.00 | 0.394491E+11 | 0.240447E+11 |
November | 0.138395E+12 | 0.260640E+11 | 0.00 | 0.556195E+11 | 0.843071E+10 |
December | 0.812501E+11 | 0.345801E+11 | 0.00 | 0.739231E+11 | 0.177459E+11 |
Annual Sum or Average | 0.410096E+13 | 0.169919E+12 | 0.00 | 0.383962E+12 | 0.710810E+12 |
Minimum of Months | 0.812501E+11 | -0.186974E+11 | 0.00 | -0.473988E+11 | 0.832070E+10 |
Maximum of Months | 0.543469E+12 | 0.392915E+11 | 0.00 | 0.815382E+11 | 0.191527E+12 |