Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:36:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1193.70 | 571.06 | 571.06 |
Net Site Energy | 1193.70 | 571.06 | 571.06 |
Total Source Energy | 3057.29 | 1462.59 | 1462.59 |
Net Source Energy | 3057.29 | 1462.59 | 1462.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 347.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 846.53 | 347.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 347.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 170.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 347.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 14.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 170.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.44 | 166.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 404.97 | 166.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.44 | 166.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 404.97 | 166.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 846.526 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 846.526 | 100.00 |
Total On-Site and Utility Electric Sources | 846.526 | 100.00 |
Total Electricity End Uses | 846.526 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1350.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-12:39 | 10-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 133627.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16777.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9945.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 9520.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 70564.92 | 133627.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 133627.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16777.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9945.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 9520.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 376.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 539.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 205.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2680.95 | 376.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 180.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 258.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1282.55 | 180.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 180.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 258.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1282.55 | 180.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.77 |
SMSTORE1 DIRECT AIR | 0.989866 |
SMSTORE2 DIRECT AIR | 0.982074 |
SMSTORE3 DIRECT AIR | 0.976556 |
SMSTORE4 DIRECT AIR | 0.974056 |
LGSTORE2 DIRECT AIR | 1.69 |
SMSTORE5 DIRECT AIR | 0.912298 |
SMSTORE6 DIRECT AIR | 0.905747 |
SMSTORE7 DIRECT AIR | 0.893499 |
SMSTORE8 DIRECT AIR | 0.907883 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.00 | 1.00 | 1.77 |
PSZ-AC_2:2 | 0.989866 | 0.989866 | 0.989866 | 0.989866 | 0.999836 | 0.999836 | 1.00 | 0.990028 | 0.999836 |
PSZ-AC_3:3 | 0.982074 | 0.982074 | 0.982074 | 0.982074 | 0.987645 | 0.987645 | 1.00 | 0.994359 | 0.987645 |
PSZ-AC_4:4 | 0.976556 | 0.976556 | 0.976556 | 0.976556 | 0.986042 | 0.986042 | 1.00 | 0.990381 | 0.986042 |
PSZ-AC_5:5 | 0.974056 | 0.974056 | 0.974056 | 0.974056 | 0.979807 | 0.979807 | 1.00 | 0.994131 | 0.979807 |
PSZ-AC_6:6 | 1.69 | 1.69 | 1.69 | 1.69 | 1.74 | 1.74 | 1.00 | 0.975269 | 1.74 |
PSZ-AC_7:7 | 0.912298 | 0.912298 | 0.912298 | 0.912298 | 0.922306 | 0.922306 | 1.00 | 0.989149 | 0.922306 |
PSZ-AC_8:8 | 0.905747 | 0.905747 | 0.905747 | 0.905747 | 0.916169 | 0.916169 | 1.00 | 0.988624 | 0.916169 |
PSZ-AC_9:9 | 0.893499 | 0.893499 | 0.893499 | 0.893499 | 0.905322 | 0.905322 | 1.00 | 0.986940 | 0.905322 |
PSZ-AC_10:10 | 0.907883 | 0.907883 | 0.907883 | 0.907883 | 0.929189 | 0.929189 | 1.00 | 0.977070 | 0.929189 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.77 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 0.999836 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 0.987645 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 0.986042 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 0.979807 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.74 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.922306 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.916169 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.905322 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.929189 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.77 | 1897.55 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.999836 | 1106.98 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.987645 | 1093.48 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.986042 | 1091.70 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.979807 | 1084.80 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.74 | 1857.43 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.922306 | 1021.14 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.916169 | 1014.34 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.905322 | 1002.34 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.929189 | 1028.76 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.77 | 1.77 | 1.77 | 1.17 | 29354.99 | 52623.71 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.999836 | 0.999836 | 0.999836 | 0.999836 | 16550.83 | 28645.94 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.987645 | 0.987645 | 0.987645 | 0.987645 | 16349.03 | 28469.71 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.986042 | 0.986042 | 0.986042 | 0.986042 | 16322.49 | 28344.93 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.979807 | 0.979807 | 0.979807 | 0.979807 | 16219.28 | 28288.37 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.74 | 1.74 | 1.74 | 1.15 | 28734.30 | 50804.53 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.922306 | 0.922306 | 0.922306 | 0.922306 | 15267.44 | 26891.58 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.916169 | 0.916169 | 0.916169 | 0.916169 | 15165.85 | 26743.40 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.905322 | 0.905322 | 0.905322 | 0.905322 | 14986.30 | 26466.39 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.929189 | 0.929189 | 0.929189 | 0.929189 | 15381.38 | 26791.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.77 | 0.886667 | 1.18 | 29354.99 | 14677.50 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 0.999840 | 0.499918 | 0.666560 | 16550.83 | 8275.42 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 0.987650 | 0.493823 | 0.658433 | 16349.03 | 8174.52 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 0.986040 | 0.493021 | 0.657360 | 16322.49 | 8161.24 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 0.979810 | 0.489903 | 0.653207 | 16219.28 | 8109.64 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 1.74 | 0.867920 | 1.16 | 28734.30 | 14367.15 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 0.922310 | 0.461153 | 0.614873 | 15267.44 | 7633.72 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 0.916170 | 0.458084 | 0.610780 | 15165.85 | 7582.93 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 0.905320 | 0.452661 | 0.603547 | 14986.30 | 7493.15 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 0.929190 | 0.464595 | 0.619460 | 15381.38 | 7690.69 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 52623.71 |
PSZ-AC_2:2 HEATING COIL | 28645.94 |
PSZ-AC_3:3 HEATING COIL | 28469.71 |
PSZ-AC_4:4 HEATING COIL | 28344.93 |
PSZ-AC_5:5 HEATING COIL | 28288.37 |
PSZ-AC_6:6 HEATING COIL | 50804.53 |
PSZ-AC_7:7 HEATING COIL | 26891.58 |
PSZ-AC_8:8 HEATING COIL | 26743.40 |
PSZ-AC_9:9 HEATING COIL | 26466.39 |
PSZ-AC_10:10 HEATING COIL | 26791.94 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 19924.61597 | 23909.53917 | 1.47778 | 1.77333 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18137.41198 | 21764.89437 | 0.79025 | 0.94830 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11454.42331 | 13745.30797 | 0.82489 | 0.98987 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8635.10909 | 10362.13091 | 0.37623 | 0.45148 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11367.33155 | 13640.79786 | 0.81839 | 0.98207 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8731.55178 | 10477.86213 | 0.38044 | 0.45652 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11305.53755 | 13566.64506 | 0.81380 | 0.97656 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8822.72774 | 10587.27329 | 0.38441 | 0.46129 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11277.19234 | 13532.63081 | 0.81171 | 0.97406 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8992.17272 | 10790.60727 | 0.39179 | 0.47015 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 19681.88597 | 23618.26317 | 1.41076 | 1.69291 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17385.31043 | 20862.37252 | 0.75749 | 0.90899 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10580.24483 | 12696.29379 | 0.76025 | 0.91230 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9276.68165 | 11132.01799 | 0.40419 | 0.48502 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10506.69709 | 12608.03651 | 0.75479 | 0.90575 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9281.76172 | 11138.11407 | 0.40441 | 0.48529 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10369.26688 | 12443.12026 | 0.74458 | 0.89350 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9576.98513 | 11492.38216 | 0.41727 | 0.50073 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10530.94855 | 12637.13825 | 0.75657 | 0.90788 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11519.74566 | 13823.69480 | 0.50191 | 0.60229 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24777.16 | 1.77333 | 1.77333 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33963.86 | 0.94830 | 0.94830 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 13582.91 | 0.99984 | 0.99984 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16469.18 | 0.45148 | 0.45148 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13657.46 | 0.98765 | 0.98765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16583.23 | 0.45652 | 0.45652 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13702.85 | 0.98604 | 0.98604 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16691.05 | 0.46129 | 0.46129 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 13574.88 | 0.97981 | 0.97981 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16891.42 | 0.47015 | 0.47015 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 23973.87 | 1.73584 | 1.73584 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 33074.55 | 0.90899 | 0.90899 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 12322.91 | 0.92231 | 0.92231 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17227.86 | 0.48502 | 0.48502 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12235.88 | 0.91617 | 0.91617 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17233.87 | 0.48529 | 0.48529 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12135.33 | 0.90532 | 0.90532 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17582.97 | 0.50073 | 0.50073 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 12348.26 | 0.92919 | 0.92919 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19880.27 | 0.60229 | 0.60229 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.77333 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98987 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98207 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97656 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97406 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.69291 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91230 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90575 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89350 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90788 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.77333 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.77333 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.77333 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.77333 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.77333 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.77333 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98987 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98987 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98987 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98987 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99984 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99984 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99003 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98207 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98207 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98207 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98207 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98765 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98765 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.99436 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97656 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97656 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97656 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97656 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98604 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98604 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.99038 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97406 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97406 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97406 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97406 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97981 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97981 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.99413 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.69291 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.69291 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.69291 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.69291 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.73584 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.73584 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97527 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.91230 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.91230 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.91230 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.91230 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92231 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92231 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98915 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90575 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90575 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90575 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90575 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91617 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91617 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98862 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89350 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89350 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89350 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89350 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90532 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90532 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98694 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90788 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90788 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90788 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90788 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92919 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92919 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97707 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.77333 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.99984 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.98765 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.98604 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97981 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.73584 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.92231 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.91617 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.90532 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.92919 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.77333 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.77333 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1897.55209 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.77333 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.77333 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.77333 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17040 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.77333 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.88667 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18222 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29354.99000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14677.49500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29354.99000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52623.70527 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 52623.70527 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99984 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99984 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1106.97701 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99984 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99984 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99984 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99984 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99984 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49992 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66656 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16550.83000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8275.41500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16550.83000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28645.94323 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28645.94323 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98765 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98765 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1093.47996 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98765 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98765 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98765 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98765 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98765 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49382 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65843 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16349.03000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8174.51500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16349.03000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28469.70798 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28469.70798 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98604 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98604 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1091.70447 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98604 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98604 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98604 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98604 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98604 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49302 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65736 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16322.49000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8161.24500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16322.49000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28344.92888 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28344.92888 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97981 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97981 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1084.80146 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97981 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97981 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97981 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97981 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97981 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48990 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65321 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16219.28000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8109.64000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16219.28000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28288.37060 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28288.37060 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.73584 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.73584 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1857.42992 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.73584 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.73584 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.73584 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14565 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.73584 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86792 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15723 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28734.30000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14367.15000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28734.30000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50804.53011 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 50804.53011 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92231 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92231 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1021.13896 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92231 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92231 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92231 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92231 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92231 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46115 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61487 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15267.44000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7633.72000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15267.44000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26891.58294 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26891.58294 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91617 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91617 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1014.34442 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91617 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91617 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91617 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91617 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91617 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45808 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61078 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15165.85000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7582.92500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15165.85000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26743.40236 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26743.40236 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90532 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90532 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1002.33528 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90532 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90532 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90532 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90532 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90532 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45266 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60355 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14986.30000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7493.15000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14986.30000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26466.38693 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26466.38693 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92919 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92919 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1028.75977 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92919 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92919 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92919 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92919 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92919 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46459 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61946 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15381.38000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7690.69000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15381.38000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26791.94277 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 26791.94277 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 27965.2 | 11.11 | 11.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 15767.2 | 11.83 | 11.83 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 15575.0 | 11.83 | 11.83 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 15549.7 | 11.83 | 11.83 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 15451.4 | 11.83 | 11.83 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 27373.9 | 11.11 | 11.11 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 14544.6 | 11.83 | 11.83 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 14447.8 | 11.83 | 11.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 14276.8 | 11.83 | 11.83 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 14653.2 | 11.83 | 11.83 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.3824481799E-002 | 0.1439299971 | Pass | Pass | 0.1186374006 | 0.2979581705 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.8995896407E-002 | 0.1086950706 | Pass | Pass | 0.4638246028 | 2.8312082088 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.0093872454E-002 | 0.1571661652 | Pass | Pass | 0.1114219117 | 0.4113177929 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 2.9872858783E-002 | 0.1601076993 | Pass | Pass | 6.3315381476E-002 | 0.1815240519 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.3195872520E-002 | 0.1697885355 | Pass | Pass | 0.1402586507 | 0.8321401765 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.1731131195E-002 | 0.2111010427 | Pass | Pass | 8.8718882079E-002 | 0.2936425853 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.2239882659E-002 | 0.2158725256 | Pass | Pass | 5.6841270802E-002 | 0.1675577870 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.3769660874E-002 | 0.2255590978 | Pass | Pass | 5.0586250299E-002 | 0.1470993706 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.9086231483E-002 | 0.2623539533 | Pass | Pass | 4.0509710137E-002 | 0.1135485644 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.9156660248E-002 | 0.3468408568 | Pass | Pass | 2.9367304298E-002 | 8.8478853021E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3494.42 | 227.52 | 0.00 | 642.51 | 145.94 | 4510.42 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.153 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.50 | 42.50 | 3.63 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.54 | 63.02 | 32.46 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.54 | 56.02 | 24.26 | |
Exterior Lighting Total | 5507.06 | 60.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29354.99 | 23503.37 | 5851.62 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16550.83 | 13251.59 | 3299.24 | 0.80 | 4.12 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16349.03 | 13090.01 | 3259.02 | 0.80 | 4.12 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16322.49 | 13068.76 | 3253.73 | 0.80 | 4.12 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16219.28 | 12986.13 | 3233.15 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28734.30 | 23006.40 | 5727.90 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15267.44 | 12224.03 | 3043.41 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15165.85 | 12142.69 | 3023.16 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14986.30 | 11998.93 | 2987.37 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15381.38 | 12315.26 | 3066.12 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 27965.2 | 11.11 | 11.11 | ||||
PSZ-AC_2:2 COOLING COIL | 15767.2 | 11.83 | 11.83 | ||||
PSZ-AC_3:3 COOLING COIL | 15575.0 | 11.83 | 11.83 | ||||
PSZ-AC_4:4 COOLING COIL | 15549.7 | 11.83 | 11.83 | ||||
PSZ-AC_5:5 COOLING COIL | 15451.4 | 11.83 | 11.83 | ||||
PSZ-AC_6:6 COOLING COIL | 27373.9 | 11.11 | 11.11 | ||||
PSZ-AC_7:7 COOLING COIL | 14544.6 | 11.83 | 11.83 | ||||
PSZ-AC_8:8 COOLING COIL | 14447.8 | 11.83 | 11.83 | ||||
PSZ-AC_9:9 COOLING COIL | 14276.8 | 11.83 | 11.83 | ||||
PSZ-AC_10:10 COOLING COIL | 14653.2 | 11.83 | 11.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 52623.71 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28645.94 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28469.71 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28344.93 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28288.37 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 50804.53 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26891.58 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26743.40 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26466.39 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 26791.94 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.77 | 1897.55 | 1070.05 | 1.00 | 1.33 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1106.98 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1093.48 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1091.70 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1084.80 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.74 | 1857.43 | 1070.05 | 1.00 | 1.34 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1021.14 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1014.34 | 1107.16 | 1.00 | 1.43 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1002.34 | 1107.16 | 1.00 | 1.43 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.93 | 1028.76 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19924.62 | 23909.54 | 68.63 | 1.478 | 1.773 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.89 | 0.00902 | 26.40 | 0.00841 | 0.411 | 0.00 |
SMSTORE1 | 11454.42 | 13745.31 | 78.91 | 0.825 | 0.990 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00926 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE2 | 11367.33 | 13640.80 | 78.31 | 0.818 | 0.982 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00948 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE3 | 11305.54 | 13566.65 | 77.88 | 0.814 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00946 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE4 | 11277.19 | 13532.63 | 77.69 | 0.812 | 0.974 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00949 | 21.39 | 0.00840 | 0.206 | 0.00 |
LGSTORE2 | 19681.89 | 23618.26 | 67.79 | 1.411 | 1.693 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00964 | 22.94 | 0.00840 | 0.411 | 0.00 |
SMSTORE5 | 10580.24 | 12696.29 | 72.89 | 0.760 | 0.912 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00948 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE6 | 10506.70 | 12608.04 | 72.38 | 0.755 | 0.906 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE7 | 10369.27 | 12443.12 | 71.43 | 0.745 | 0.893 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00951 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE8 | 10530.95 | 12637.14 | 72.55 | 0.757 | 0.908 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00946 | 22.94 | 0.00840 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18137.41 | 21764.89 | 62.47 | 0.790 | 0.948 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 8635.11 | 10362.13 | 59.49 | 0.376 | 0.451 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 8731.55 | 10477.86 | 60.15 | 0.380 | 0.457 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 8822.73 | 10587.27 | 60.78 | 0.384 | 0.461 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 8992.17 | 10790.61 | 61.95 | 0.392 | 0.470 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 17385.31 | 20862.37 | 59.88 | 0.757 | 0.909 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 9276.68 | 11132.02 | 63.91 | 0.404 | 0.485 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 9281.76 | 11138.11 | 63.94 | 0.404 | 0.485 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 9576.99 | 11492.38 | 65.97 | 0.417 | 0.501 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 11519.75 | 13823.69 | 79.36 | 0.502 | 0.602 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.77 | 1.77 | 0.95 | 0.95 | 1.7733 | 1.7733 | 1.7733 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.00 | 1.00 | 0.45 | 0.45 | 0.9998 | 0.9899 | 0.9998 | 0.9900 | 1.0000 |
PSZ-AC_3:3 | 0.99 | 0.99 | 0.46 | 0.46 | 0.9876 | 0.9821 | 0.9876 | 0.9944 | 1.0000 |
PSZ-AC_4:4 | 0.99 | 0.99 | 0.46 | 0.46 | 0.9860 | 0.9766 | 0.9860 | 0.9904 | 1.0000 |
PSZ-AC_5:5 | 0.98 | 0.98 | 0.47 | 0.47 | 0.9798 | 0.9741 | 0.9798 | 0.9941 | 1.0000 |
PSZ-AC_6:6 | 1.74 | 1.74 | 0.91 | 0.91 | 1.7358 | 1.6929 | 1.7358 | 0.9753 | 1.0000 |
PSZ-AC_7:7 | 0.92 | 0.92 | 0.49 | 0.49 | 0.9223 | 0.9123 | 0.9223 | 0.9891 | 1.0000 |
PSZ-AC_8:8 | 0.92 | 0.92 | 0.49 | 0.49 | 0.9162 | 0.9057 | 0.9162 | 0.9886 | 1.0000 |
PSZ-AC_9:9 | 0.91 | 0.91 | 0.50 | 0.50 | 0.9053 | 0.8935 | 0.9053 | 0.9869 | 1.0000 |
PSZ-AC_10:10 | 0.93 | 0.93 | 0.60 | 0.60 | 0.9292 | 0.9079 | 0.9292 | 0.9771 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 29354.990 | 23503.366 | 1.773330 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 14677.50 | 13743.09 | 1.182220 | 25.35 | 17.07 | 0.00887892 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 34.8056 | 23.89 | 0.00902148 | 48.3314 | 19924.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 52623.705 | 52623.705 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 52623.71 | 52623.71 | 1.773335 | 15.21 | 10.28 | 0.00583487 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 23.2037 | 21.11 | 0.00679487 | 43.2595 | 18137.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 16550.830 | 13251.588 | 0.999840 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8275.42 | 7779.14 | 0.666560 | 25.33 | 17.04 | 0.00885495 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 30.8659 | 23.89 | 0.00897448 | 48.0830 | 11454.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28645.943 | 28645.943 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28645.94 | 28645.94 | 0.999836 | 15.88 | 10.58 | 0.00584872 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.5773 | 21.11 | 0.00667550 | 42.5078 | 8635.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 16349.030 | 13090.014 | 0.987650 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 8174.52 | 7685.70 | 0.658433 | 25.32 | 17.04 | 0.00885379 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.2468 | 23.89 | 0.00897215 | 48.0706 | 11036.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28469.708 | 28469.708 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28469.71 | 28469.71 | 0.987645 | 15.81 | 10.55 | 0.00584480 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.8313 | 21.11 | 0.00668344 | 42.5579 | 8731.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 16322.490 | 13068.765 | 0.986040 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8161.24 | 7674.08 | 0.657360 | 25.32 | 17.04 | 0.00885309 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.2978 | 23.89 | 0.00897074 | 48.0632 | 11074.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28344.929 | 28344.929 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28344.93 | 28344.93 | 0.986042 | 15.81 | 10.55 | 0.00584974 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.8652 | 21.11 | 0.00669141 | 42.6081 | 8822.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 16219.280 | 12986.129 | 0.979810 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 8109.64 | 7623.16 | 0.653207 | 25.33 | 17.04 | 0.00885507 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.4968 | 23.89 | 0.00897473 | 48.0842 | 10966.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28288.371 | 28288.371 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28288.37 | 28288.37 | 0.979807 | 15.77 | 10.54 | 0.00585639 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.9980 | 21.11 | 0.00670660 | 42.7038 | 8992.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 28734.300 | 23006.405 | 1.735840 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 14367.15 | 13432.34 | 1.157227 | 25.37 | 17.09 | 0.00888842 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 35.5573 | 23.89 | 0.00904062 | 48.4324 | 19681.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 50804.530 | 50804.530 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 50804.53 | 50804.53 | 1.735839 | 15.08 | 10.20 | 0.00581294 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 23.7049 | 21.11 | 0.00679331 | 43.2493 | 17385.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 15267.440 | 12224.029 | 0.922310 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7633.72 | 7153.28 | 0.614873 | 25.38 | 17.08 | 0.00887521 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 33.4605 | 23.89 | 0.00901769 | 48.3111 | 10580.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26891.583 | 26891.583 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26891.58 | 26891.58 | 0.922306 | 15.44 | 10.36 | 0.00582193 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.3071 | 21.11 | 0.00673047 | 42.8543 | 9276.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 15165.850 | 12142.689 | 0.916170 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7582.93 | 7104.11 | 0.610780 | 25.39 | 17.08 | 0.00887665 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 33.6847 | 23.89 | 0.00902097 | 48.3284 | 10506.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26743.402 | 26743.402 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26743.40 | 26743.40 | 0.916169 | 15.40 | 10.34 | 0.00581623 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.4565 | 21.11 | 0.00673097 | 42.8574 | 9281.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 14986.300 | 11998.931 | 0.905320 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7493.15 | 7018.20 | 0.603547 | 25.39 | 17.09 | 0.00887832 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 34.0884 | 23.89 | 0.00902481 | 48.3487 | 10369.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26466.387 | 26466.387 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26466.39 | 26466.39 | 0.905322 | 15.33 | 10.32 | 0.00582351 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.7255 | 21.11 | 0.00675457 | 43.0061 | 9576.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 15381.380 | 12315.256 | 0.929190 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7690.69 | 7209.75 | 0.619460 | 25.29 | 17.04 | 0.00887018 | 12.80 | 12.00 | 0.00850000 | 26.02 | 0.00840648 | 16.91 | 33.2127 | 23.89 | 0.00900947 | 48.2677 | 10530.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 26791.943 | 26791.943 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26791.94 | 26791.94 | 0.929189 | 15.48 | 10.48 | 0.00591624 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.1418 | 21.11 | 0.00684296 | 43.5638 | 11519.75 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29354.990 | 23503.366 | 1.773330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3455 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.773335 | 2.11270147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 14677.50 | 13743.09 | 1.0000 | 1.40846382 | 1.182220 | 25.35 | 17.07 | 0.00887892 | 48097.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14677.50 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 34.8056 | 23.89 | 0.00902148 | 23.89 | 0.00902148 | 48.3314 | 19924.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52623.705 | 52623.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.773335 | 2.11270147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 52623.71 | 52623.71 | 1.0000 | 2.11270147 | 1.773335 | 15.21 | 10.28 | 0.00583487 | 30043.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52623.71 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 23.2037 | 21.11 | 0.00679487 | 21.11 | 0.00679487 | 43.2595 | 18137.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16550.830 | 13251.588 | 0.999840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3009 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.999836 | 1.19117646 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8275.42 | 7779.14 | 1.0000 | 0.79412093 | 0.666560 | 25.33 | 17.04 | 0.00885495 | 48012.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8275.42 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 30.8659 | 23.89 | 0.00897448 | 23.89 | 0.00897448 | 48.0830 | 11454.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28645.943 | 28645.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.999836 | 1.19117646 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28645.94 | 28645.94 | 1.0000 | 1.19117646 | 0.999836 | 15.88 | 10.58 | 0.00584872 | 30756.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28645.94 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.5773 | 21.11 | 0.00667550 | 21.11 | 0.00667550 | 42.5078 | 8635.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16349.030 | 13090.014 | 0.987650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2988 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.987645 | 1.17665279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | Sensible | 8174.52 | 7685.70 | 1.0000 | 0.78443904 | 0.658433 | 25.32 | 17.04 | 0.00885379 | 48006.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8174.52 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.2468 | 23.89 | 0.00897215 | 23.89 | 0.00897215 | 48.0706 | 11036.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28469.708 | 28469.708 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.987645 | 1.17665279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28469.71 | 28469.71 | 1.0000 | 1.17665279 | 0.987645 | 15.81 | 10.55 | 0.00584480 | 30680.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28469.71 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.8313 | 21.11 | 0.00668344 | 21.11 | 0.00668344 | 42.5579 | 8731.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16322.490 | 13068.765 | 0.986040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2974 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.986042 | 1.17474226 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8161.24 | 7674.08 | 1.0000 | 0.78316031 | 0.657360 | 25.32 | 17.04 | 0.00885309 | 48002.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8161.24 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.2978 | 23.89 | 0.00897074 | 23.89 | 0.00897074 | 48.0632 | 11074.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28344.929 | 28344.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.986042 | 1.17474226 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28344.93 | 28344.93 | 1.0000 | 1.17474226 | 0.986042 | 15.81 | 10.55 | 0.00584974 | 30684.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28344.93 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.8652 | 21.11 | 0.00669141 | 21.11 | 0.00669141 | 42.6081 | 8822.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16219.280 | 12986.129 | 0.979810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3011 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979807 | 1.16731418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | Sensible | 8109.64 | 7623.16 | 1.0000 | 0.77821214 | 0.653207 | 25.33 | 17.04 | 0.00885507 | 48013.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8109.64 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.4968 | 23.89 | 0.00897473 | 23.89 | 0.00897473 | 48.0842 | 10966.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28288.371 | 28288.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979807 | 1.16731418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28288.37 | 28288.37 | 1.0000 | 1.16731418 | 0.979807 | 15.77 | 10.54 | 0.00585639 | 30667.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28288.37 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.9980 | 21.11 | 0.00670660 | 21.11 | 0.00670660 | 42.7038 | 8992.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28734.300 | 23006.405 | 1.735840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3631 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.735839 | 2.06803015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 14367.15 | 13432.34 | 1.0000 | 1.37868746 | 1.157227 | 25.37 | 17.09 | 0.00888842 | 48142.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14367.15 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 35.5573 | 23.89 | 0.00904062 | 23.89 | 0.00904062 | 48.4324 | 19681.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50804.530 | 50804.530 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.735839 | 2.06803015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 50804.53 | 50804.53 | 1.0000 | 2.06803015 | 1.735839 | 15.08 | 10.20 | 0.00581294 | 29858.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50804.53 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 23.7049 | 21.11 | 0.00679331 | 21.11 | 0.00679331 | 43.2493 | 17385.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15267.440 | 12224.029 | 0.922310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3386 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.922306 | 1.09880936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7633.72 | 7153.28 | 1.0000 | 0.73254288 | 0.614873 | 25.38 | 17.08 | 0.00887521 | 48122.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7633.72 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 33.4605 | 23.89 | 0.00901769 | 23.89 | 0.00901769 | 48.3111 | 10580.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26891.583 | 26891.583 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.922306 | 1.09880936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26891.58 | 26891.58 | 1.0000 | 1.09880936 | 0.922306 | 15.44 | 10.36 | 0.00582193 | 30242.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26891.58 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 22.3071 | 21.11 | 0.00673047 | 21.11 | 0.00673047 | 42.8543 | 9276.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15165.850 | 12142.689 | 0.916170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3412 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.916169 | 1.09149800 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7582.93 | 7104.11 | 1.0000 | 0.72766620 | 0.610780 | 25.39 | 17.08 | 0.00887665 | 48130.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7582.93 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 33.6847 | 23.89 | 0.00902097 | 23.89 | 0.00902097 | 48.3284 | 10506.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26743.402 | 26743.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.916169 | 1.09149800 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26743.40 | 26743.40 | 1.0000 | 1.09149800 | 0.916169 | 15.40 | 10.34 | 0.00581623 | 30189.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26743.40 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 22.4565 | 21.11 | 0.00673097 | 21.11 | 0.00673097 | 42.8574 | 9281.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14986.300 | 11998.931 | 0.905320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3443 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.905322 | 1.07857542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7493.15 | 7018.20 | 1.0000 | 0.71904861 | 0.603547 | 25.39 | 17.09 | 0.00887832 | 48139.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7493.15 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 34.0884 | 23.89 | 0.00902481 | 23.89 | 0.00902481 | 48.3487 | 10369.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26466.387 | 26466.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.905322 | 1.07857542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26466.39 | 26466.39 | 1.0000 | 1.07857542 | 0.905322 | 15.33 | 10.32 | 0.00582351 | 30138.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26466.39 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 22.7255 | 21.11 | 0.00675457 | 21.11 | 0.00675457 | 43.0061 | 9576.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15381.380 | 12315.256 | 0.929190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3292 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.929189 | 1.10700982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7690.69 | 7209.75 | 1.0000 | 0.73800731 | 0.619460 | 25.29 | 17.04 | 0.00887018 | 48013.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7690.69 | 26.02 | 0.00840648 | 16.91 | 0.20573941 | 33.2127 | 23.89 | 0.00900947 | 23.89 | 0.00900947 | 48.2677 | 10530.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26791.943 | 26791.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.929189 | 1.10700982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26791.94 | 26791.94 | 1.0000 | 1.10700982 | 0.929189 | 15.48 | 10.48 | 0.00591624 | 30523.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26791.94 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 22.1418 | 21.11 | 0.00684296 | 21.11 | 0.00684296 | 43.5638 | 11519.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.77 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1227.33 | 4403.83 | 419.67 |
SMSTORE1 | 1125.00 | 3715.50 | 28.50 |
SMSTORE2 | 1009.00 | 2877.00 | 122.50 |
SMSTORE3 | 1015.67 | 2919.00 | 162.67 |
SMSTORE4 | 982.67 | 3023.00 | 220.50 |
LGSTORE2 | 900.50 | 3071.83 | 382.17 |
SMSTORE5 | 873.50 | 2964.50 | 388.17 |
SMSTORE6 | 882.33 | 2988.83 | 419.00 |
SMSTORE7 | 949.17 | 3096.00 | 533.33 |
SMSTORE8 | 1429.67 | 3252.50 | 1117.50 |
Facility | 2489.00 | 4814.00 | 1350.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 3.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 12.17 | 0.00 | 0.00 | 0.00 |
Facility | 15.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.906 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.980 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 1.152 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 1.144 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 1.117 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.941 | 0.304 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.832 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.831 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.79 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.02 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9420220.87 | 0.00 | 9420220.87 | 2543634.56 | 11963855.44 | 12976396.34 | 3179.35 | 4496.92 | 1083.74 | 8.31 |
SMSTORE1 | 5093500.18 | 0.00 | 5093500.18 | 1325656.62 | 6419156.80 | 6488198.17 | 4230.28 | 2743.49 | 1786.23 | 35.33 |
SMSTORE2 | 4542194.34 | 0.00 | 4542194.34 | 1347989.39 | 5890183.73 | 6488198.17 | 4357.40 | 3164.33 | 1238.26 | 111.15 |
SMSTORE3 | 4506016.37 | 0.00 | 4506016.37 | 1347989.39 | 5854005.76 | 6488198.17 | 4357.57 | 3194.67 | 1207.76 | 103.90 |
SMSTORE4 | 4396009.10 | 0.00 | 4396009.10 | 1347989.39 | 5743998.49 | 6488198.17 | 4359.15 | 3296.75 | 1104.10 | 89.65 |
LGSTORE2 | 6767017.53 | 0.00 | 6767017.53 | 2452525.89 | 9219543.41 | 12976396.34 | 4727.92 | 3313.00 | 719.08 | 43.08 |
SMSTORE5 | 2984867.42 | 0.00 | 2984867.42 | 1353368.44 | 4338235.87 | 6488198.17 | 4730.00 | 4030.00 | 0.00 | 0.00 |
SMSTORE6 | 2984867.42 | 0.00 | 2984867.42 | 1353368.44 | 4338235.87 | 6488198.17 | 4730.00 | 4030.00 | 0.00 | 0.00 |
SMSTORE7 | 2984867.42 | 0.00 | 2984867.42 | 1353368.44 | 4338235.87 | 6488198.17 | 4730.00 | 4030.00 | 0.00 | 0.00 |
SMSTORE8 | 2984867.42 | 0.00 | 2984867.42 | 1541468.51 | 4526335.94 | 6488198.17 | 4730.00 | 4030.00 | 0.00 | 0.00 |
Total Facility | 46664428.09 | 0.00 | 46664428.09 | 15967359.07 | 62631787.16 | 77858378.04 | 4730.00 | 5659.49 | 1848.99 | 178.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4479 | 0.0000 | 0.4479 | 0.1105 | 0.5583 | 0.4115 | 260.07 | 4496.92 | 1083.01 |
SMSTORE1 | 0.2416 | 0.0000 | 0.2416 | 0.0599 | 0.3014 | 0.2057 | 1313.75 | 2743.32 | 1782.92 |
SMSTORE2 | 0.2844 | 0.0000 | 0.2844 | 0.0785 | 0.3629 | 0.2057 | 0.00 | 3164.17 | 1230.83 |
SMSTORE3 | 0.2823 | 0.0000 | 0.2823 | 0.0785 | 0.3608 | 0.2057 | 0.00 | 3194.67 | 1200.33 |
SMSTORE4 | 0.2758 | 0.0000 | 0.2758 | 0.0785 | 0.3543 | 0.2057 | 0.00 | 3296.58 | 1098.42 |
LGSTORE2 | 0.4652 | 0.0000 | 0.4652 | 0.1507 | 0.6158 | 0.4115 | 0.00 | 3313.00 | 717.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.0838 | 0.2895 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.0838 | 0.2895 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.0838 | 0.2895 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.0866 | 0.2924 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.8201 | 0.0000 | 2.8201 | 0.8945 | 3.7146 | 2.4689 | 1422.45 | 5659.16 | 1842.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13371397.32 | 0.00 | 13371397.32 | 12976396.34 | 3177.85 | 0.00 | 5582.15 | 8.31 |
PSZ-AC_2:2 | 7229547.45 | 0.00 | 7229547.45 | 6488198.17 | 4181.64 | 7.48 | 4570.88 | 35.33 |
PSZ-AC_3:3 | 6447041.98 | 0.00 | 6447041.98 | 6488198.17 | 4345.24 | 0.83 | 4413.93 | 111.15 |
PSZ-AC_4:4 | 6395692.15 | 0.00 | 6395692.15 | 6488198.17 | 4347.24 | 1.83 | 4410.93 | 103.74 |
PSZ-AC_5:5 | 6239551.43 | 0.00 | 6239551.43 | 6488198.17 | 4354.40 | 0.67 | 4404.93 | 89.65 |
PSZ-AC_6:6 | 9605309.08 | 0.00 | 9605309.08 | 12976396.34 | 4726.50 | 0.17 | 4033.33 | 42.92 |
PSZ-AC_7:7 | 4236623.12 | 0.00 | 4236623.12 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 4236623.12 | 0.00 | 4236623.12 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 4236623.12 | 0.00 | 4236623.12 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 4236623.12 | 0.00 | 4236623.12 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6357 | 0.0000 | 0.6357 | 0.4115 | 258.90 | 0.00 | 5581.10 |
PSZ-AC_2:2 | 0.3429 | 0.0000 | 0.3429 | 0.2057 | 1268.20 | 6.48 | 4565.32 |
PSZ-AC_3:3 | 0.4037 | 0.0000 | 0.4037 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4007 | 0.0000 | 0.4007 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3915 | 0.0000 | 0.3915 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6603 | 0.0000 | 0.6603 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2920 | 0.0000 | 0.2920 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2920 | 0.0000 | 0.2920 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2920 | 0.0000 | 0.2920 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2920 | 0.0000 | 0.2920 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5033.82 | 584.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3209.18 | 1785.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3512.29 | 993.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3535.96 | 962.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3609.87 | 874.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3705.33 | 367.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6466 | 0.7958 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3748 | 0.4570 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3604 | 0.5764 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3583 | 0.5757 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3515 | 0.5758 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6431 | 0.8581 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
ElectricityPurchased:Plant | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
Cogeneration:ElectricityPurchased | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
General:Cogeneration:ElectricityPurchased | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
ElectricityNet:Plant | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
Cogeneration:ElectricityNet | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
General:Cogeneration:ElectricityNet | 846.53 | 2102.83 | 29-JAN-08:00 | 70564.92 | 21-JUL-12:40 |
Electricity:HVAC | 184.68 | 0.00 | 01-JAN-00:10 | 31671.80 | 22-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.22 | 0.00 | 01-JAN-00:10 | 21606.63 | 22-JUL-15:00 |
General:Cooling:Electricity | 14.22 | 0.00 | 01-JAN-00:10 | 21606.63 | 22-JUL-15:00 |
Fans:Electricity | 170.46 | 0.00 | 01-JAN-00:10 | 10689.94 | 10-JAN-08:10 |
General:Fans:Electricity | 170.46 | 0.00 | 01-JAN-00:10 | 10689.94 | 10-JAN-08:10 |
ExteriorLights:Electricity | 60.36 | 0.00 | 01-JAN-08:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.36 | 0.00 | 01-JAN-08:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 64.99 | 1211.00 | 08-JAN-08:10 | 11792.64 | 23-DEC-18:10 |
WaterSystems:Electricity | 64.99 | 1211.00 | 08-JAN-08:10 | 11792.64 | 23-DEC-18:10 |
Water Heater:WaterSystems:Electricity | 64.99 | 1211.00 | 08-JAN-08:10 | 11792.64 | 23-DEC-18:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 347.18 | 0.00 | 01-JAN-00:10 | 133627.48 | 10-JAN-08:10 |
NaturalGas:HVAC | 347.18 | 0.00 | 01-JAN-00:10 | 133627.48 | 10-JAN-08:10 |
Heating:NaturalGas | 347.18 | 0.00 | 01-JAN-00:10 | 133627.48 | 10-JAN-08:10 |
General:Heating:NaturalGas | 347.18 | 0.00 | 01-JAN-00:10 | 133627.48 | 10-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 673.13 | 0.00 | 01-JAN-00:10 | 201542.21 | 10-JAN-08:10 |
EnergyTransfer:Building | 333.11 | 0.00 | 01-JAN-00:10 | 94640.22 | 10-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 73.72 | 0.00 | 01-JAN-00:10 | 17117.16 | 30-DEC-08:10 |
Heating:EnergyTransfer | 73.28 | 0.00 | 01-JAN-00:10 | 94640.22 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 9.11 | 0.00 | 01-JAN-00:10 | 17117.16 | 30-DEC-08:10 |
General:Heating:EnergyTransfer | 73.28 | 0.00 | 01-JAN-00:10 | 94640.22 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 9.11 | 0.00 | 01-JAN-00:10 | 17117.16 | 30-DEC-08:10 |
Cooling:EnergyTransfer | 259.82 | 0.00 | 01-JAN-00:10 | 72215.23 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 64.62 | 0.00 | 01-JAN-00:10 | 12240.12 | 22-JUL-16:10 |
General:Cooling:EnergyTransfer | 259.82 | 0.00 | 01-JAN-00:10 | 72215.23 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 64.62 | 0.00 | 01-JAN-00:10 | 12240.12 | 22-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 37.28 | 0.00 | 01-JAN-00:10 | 9735.69 | 06-AUG-17:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.12 | 0.00 | 01-JAN-00:10 | 5378.54 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.12 | 0.00 | 01-JAN-00:10 | 5378.54 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 35.15 | 0.00 | 01-JAN-00:10 | 9735.69 | 06-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 35.15 | 0.00 | 01-JAN-00:10 | 9735.69 | 06-AUG-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 28.70 | 0.00 | 01-JAN-00:10 | 6567.67 | 22-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.32 | 0.00 | 01-JAN-00:10 | 6295.86 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.32 | 0.00 | 01-JAN-00:10 | 6295.86 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 25.38 | 0.00 | 01-JAN-00:10 | 6567.67 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 25.38 | 0.00 | 01-JAN-00:10 | 6567.67 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 28.00 | 0.00 | 01-JAN-00:10 | 7049.67 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.95 | 0.00 | 01-JAN-00:10 | 7049.67 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 3.95 | 0.00 | 01-JAN-00:10 | 7049.67 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 24.05 | 0.00 | 01-JAN-00:10 | 6547.60 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 24.05 | 0.00 | 01-JAN-00:10 | 6547.60 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 26.49 | 0.00 | 01-JAN-00:10 | 7822.29 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.99 | 0.00 | 01-JAN-00:10 | 7822.29 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 4.99 | 0.00 | 01-JAN-00:10 | 7822.29 | 10-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.50 | 0.00 | 01-JAN-00:10 | 6384.28 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.50 | 0.00 | 01-JAN-00:10 | 6384.28 | 22-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 45.42 | 0.00 | 01-JAN-00:10 | 18379.23 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 10.76 | 0.00 | 01-JAN-00:10 | 18379.23 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 10.76 | 0.00 | 01-JAN-00:10 | 18379.23 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 34.67 | 0.00 | 01-JAN-00:10 | 11583.49 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 34.67 | 0.00 | 01-JAN-00:10 | 11583.49 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 22.21 | 0.00 | 01-JAN-00:10 | 9409.82 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.74 | 0.00 | 01-JAN-00:10 | 9409.82 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 6.74 | 0.00 | 01-JAN-00:10 | 9409.82 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 15.47 | 0.00 | 01-JAN-00:10 | 6016.16 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 15.47 | 0.00 | 01-JAN-00:10 | 6016.16 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 22.13 | 0.00 | 01-JAN-00:10 | 9537.89 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 7.11 | 0.00 | 01-JAN-00:10 | 9537.89 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 7.11 | 0.00 | 01-JAN-00:10 | 9537.89 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 15.01 | 0.00 | 01-JAN-00:10 | 5958.08 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 15.01 | 0.00 | 01-JAN-00:10 | 5958.08 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 22.16 | 0.00 | 01-JAN-00:10 | 10850.55 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 8.82 | 0.00 | 01-JAN-00:10 | 10850.55 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 8.82 | 0.00 | 01-JAN-00:10 | 10850.55 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 13.34 | 0.00 | 01-JAN-00:10 | 5840.65 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 13.34 | 0.00 | 01-JAN-00:10 | 5840.65 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 27.00 | 0.00 | 01-JAN-00:10 | 15432.69 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 16.37 | 0.00 | 01-JAN-00:10 | 15432.69 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 16.37 | 0.00 | 01-JAN-00:10 | 15432.69 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 10.63 | 0.00 | 01-JAN-00:10 | 5952.05 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 10.63 | 0.00 | 01-JAN-00:10 | 5952.05 | 22-JUL-15:00 |
EnergyTransfer:HVAC | 340.02 | 0.00 | 01-JAN-00:10 | 106901.99 | 10-JAN-08:10 |
HeatingCoils:EnergyTransfer | 277.74 | 0.00 | 01-JAN-00:10 | 106901.99 | 10-JAN-08:10 |
CoolingCoils:EnergyTransfer | 62.28 | 0.00 | 01-JAN-00:10 | 97568.27 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 9.105 | -64.618 | 0.000 | 0.000 | 25.761 | 95.826 | 26.249 | 20.217 | 0.000 | 0.065 | 0.002 | 0.000 | -10.524 | 0.000 | -33.126 | -68.955 |
SMSTORE1 | 0.000 | 0.000 | 2.124 | -35.152 | 0.000 | 0.000 | 12.494 | 57.583 | 13.125 | 9.973 | 0.000 | 0.035 | 0.000 | 0.000 | -5.608 | 0.000 | -17.609 | -36.965 |
SMSTORE2 | 0.000 | 0.000 | 3.321 | -25.379 | 0.000 | 0.000 | 7.648 | 40.956 | 10.421 | 9.969 | 0.000 | 0.035 | 0.001 | 0.000 | -5.511 | 0.000 | -17.859 | -23.600 |
SMSTORE3 | 0.000 | 0.000 | 3.952 | -24.047 | 0.000 | 0.000 | 7.661 | 40.956 | 10.421 | 9.987 | 0.000 | 0.035 | 0.000 | 0.000 | -5.443 | 0.000 | -17.791 | -25.732 |
SMSTORE4 | 0.000 | 0.000 | 4.991 | -21.503 | 0.000 | 0.000 | 7.685 | 40.956 | 10.421 | 10.018 | 0.000 | 0.035 | 0.001 | 0.000 | -5.369 | 0.000 | -17.681 | -29.552 |
LGSTORE2 | 0.000 | 0.000 | 10.757 | -34.667 | 0.000 | 0.000 | 26.643 | 43.277 | 19.173 | 20.192 | 0.000 | 0.063 | 0.003 | 0.000 | -10.368 | 0.000 | -31.612 | -43.459 |
SMSTORE5 | 0.000 | 0.000 | 6.736 | -15.475 | 0.000 | 0.000 | 13.250 | 22.197 | 9.586 | 10.067 | 0.000 | 0.035 | 0.001 | 0.000 | -5.199 | 0.000 | -17.553 | -23.645 |
SMSTORE6 | 0.000 | 0.000 | 7.114 | -15.012 | 0.000 | 0.000 | 13.259 | 22.197 | 9.586 | 10.077 | 0.000 | 0.035 | 0.001 | 0.000 | -5.177 | 0.000 | -17.528 | -24.550 |
SMSTORE7 | 0.000 | 0.000 | 8.819 | -13.341 | 0.000 | 0.000 | 13.295 | 22.197 | 9.586 | 10.112 | 0.000 | 0.035 | 0.000 | 0.000 | -5.089 | 0.000 | -17.419 | -28.195 |
SMSTORE8 | 0.000 | 0.000 | 16.366 | -10.631 | 0.000 | 0.000 | 13.353 | 22.197 | 9.586 | 10.204 | 0.000 | 0.036 | 0.000 | 0.000 | -4.775 | 0.000 | -19.775 | -36.562 |
Total Facility | 0.000 | 0.000 | 73.285 | -259.825 | 0.000 | 0.000 | 141.049 | 408.342 | 128.154 | 120.817 | 0.000 | 0.409 | 0.012 | 0.000 | -63.062 | 0.000 | -207.953 | -341.216 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -17105.62 | 0.00 | 0.00 | 188.32 | 75.00 | 74.62 | 234.78 | 0.00 | 0.00 | 16791.38 | 0.00 | -0.00 | 0.00 | -258.49 | 0.00 |
SMSTORE1 | 29-APR-18:44 | 0.00 | 0.00 | 0.00 | -18497.62 | 0.00 | 0.00 | 1056.46 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 13872.09 | 0.00 | -55.43 | 0.00 | -108.80 | 0.00 |
SMSTORE2 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -15190.50 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 107.70 | 0.00 | 0.00 | 15143.17 | 0.00 | -0.00 | 0.00 | -135.17 | 0.00 |
SMSTORE3 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -15513.11 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 107.15 | 0.00 | 0.00 | 15466.38 | 0.00 | -0.00 | 0.00 | -135.23 | 0.00 |
SMSTORE4 | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13924.72 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 108.98 | 0.00 | 0.00 | 13875.89 | 0.00 | -0.00 | 0.00 | -134.96 | 0.00 |
LGSTORE2 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -18578.12 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 614.11 | 0.00 | 0.00 | 18020.39 | 0.00 | -0.00 | 0.00 | -205.02 | 0.00 |
SMSTORE5 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -8554.90 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 308.24 | 0.00 | 0.00 | 8285.77 | 0.00 | -0.00 | 0.00 | -113.43 | 0.00 |
SMSTORE6 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -8065.99 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 309.18 | 0.00 | 0.00 | 7795.80 | 0.00 | -0.00 | 0.00 | -113.30 | 0.00 |
SMSTORE7 | 23-JUL-08:63 | 0.00 | 0.00 | 0.00 | -6479.06 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 311.71 | 0.00 | 0.00 | 6205.93 | 0.00 | -0.00 | 0.00 | -112.90 | 0.00 |
SMSTORE8 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | -5952.16 | 0.00 | 0.00 | 1576.08 | 1638.25 | 671.63 | 1169.80 | 0.00 | 831.59 | 64.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-07:03 | 0.00 | 0.00 | 0.00 | -74513.42 | 0.00 | 0.00 | 280.00 | 450.00 | 444.79 | 1368.30 | 0.00 | 0.00 | 73921.00 | 0.00 | 0.00 | 0.00 | -1950.67 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-NOV-08:61 | 0.00 | 0.00 | 52918.27 | 0.00 | 0.00 | 0.00 | 249.98 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -597.52 | 0.00 | -798.41 | -51921.94 |
SMSTORE1 | 17-FEB-08:61 | 0.00 | 0.00 | 28762.82 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 375.40 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -526.21 | -28686.33 |
SMSTORE2 | 31-DEC-08:61 | 0.00 | 0.00 | 28347.12 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -364.52 | 0.00 | -480.85 | -27576.55 |
SMSTORE3 | 31-DEC-08:61 | 0.00 | 0.00 | 28228.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.25 | 0.00 | -474.24 | -27469.42 |
SMSTORE4 | 31-DEC-08:61 | 0.00 | 0.00 | 28174.93 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -354.32 | 0.00 | -467.62 | -27427.81 |
LGSTORE2 | 20-NOV-08:61 | 0.00 | 0.00 | 51147.39 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.23 | 0.00 | -760.81 | -49963.00 |
SMSTORE5 | 20-NOV-08:61 | 0.00 | 0.00 | 27062.87 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -285.61 | 0.00 | -424.01 | -26427.56 |
SMSTORE6 | 20-NOV-08:61 | 0.00 | 0.00 | 26918.50 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -283.71 | 0.00 | -421.64 | -26287.48 |
SMSTORE7 | 20-NOV-08:61 | 0.00 | 0.00 | 26650.81 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -276.19 | 0.00 | -411.61 | -26037.33 |
SMSTORE8 | 20-NOV-08:61 | 0.00 | 0.00 | 26977.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -250.53 | 0.00 | -386.68 | -26414.39 |
Total Facility | 10-JAN-08:61 | 0.00 | 0.00 | 249175.17 | 0.00 | 0.00 | 0.00 | 732.69 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1377.42 | 0.00 | -6820.58 | -243612.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7733 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7733 | 0.2320 | 1.0000 | Not calculated | 0.4115 | 0.2320 | ||
PSZ-AC_2:2 | 0.9899 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9998 | 0.2058 | 1.0000 | Not calculated | 0.2057 | 0.2058 | ||
PSZ-AC_3:3 | 0.9821 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9876 | 0.2083 | 1.0000 | Not calculated | 0.2057 | 0.2083 | ||
PSZ-AC_4:4 | 0.9766 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9860 | 0.2087 | 1.0000 | Not calculated | 0.2057 | 0.2087 | ||
PSZ-AC_5:5 | 0.9741 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9798 | 0.2100 | 1.0000 | Not calculated | 0.2057 | 0.2100 | ||
PSZ-AC_6:6 | 1.6929 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7358 | 0.2370 | 1.0000 | Not calculated | 0.4115 | 0.2370 | ||
PSZ-AC_7:7 | 0.9123 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9223 | 0.2231 | 1.0000 | Not calculated | 0.2057 | 0.2231 | ||
PSZ-AC_8:8 | 0.9057 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9162 | 0.2246 | 1.0000 | Not calculated | 0.2057 | 0.2246 | ||
PSZ-AC_9:9 | 0.8935 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9053 | 0.2273 | 1.0000 | Not calculated | 0.2057 | 0.2273 | ||
PSZ-AC_10:10 | 0.9079 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9292 | 0.2214 | 1.0000 | Not calculated | 0.2057 | 0.2214 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7733 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7733 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2320 | ||
PSZ-AC_2:2 | 0.9899 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9899 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2078 | ||
PSZ-AC_3:3 | 0.9821 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9821 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2095 | ||
PSZ-AC_4:4 | 0.9766 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9766 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2107 | ||
PSZ-AC_5:5 | 0.9741 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9741 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2112 | ||
PSZ-AC_6:6 | 1.6929 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.6929 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2431 | ||
PSZ-AC_7:7 | 0.9123 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9123 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2255 | ||
PSZ-AC_8:8 | 0.9057 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9057 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2271 | ||
PSZ-AC_9:9 | 0.8935 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8935 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2303 | ||
PSZ-AC_10:10 | 0.9079 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9079 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2266 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7733 | 1.7733 | 1.7733 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9899 | 0.9899 | 0.9899 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9821 | 0.9821 | 0.9821 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9766 | 0.9766 | 0.9766 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9741 | 0.9741 | 0.9741 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6929 | 1.6929 | 1.6929 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9123 | 0.9123 | 0.9123 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9057 | 0.9057 | 0.9057 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8935 | 0.8935 | 0.8935 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9079 | 0.9079 | 0.9079 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7733 | 1.7733 | 1.7733 | 1.7733 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9899 | 0.9998 | 0.9899 | 0.9899 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9821 | 0.9876 | 0.9821 | 0.9821 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9766 | 0.9860 | 0.9766 | 0.9766 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9741 | 0.9798 | 0.9741 | 0.9741 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.6929 | 1.7358 | 1.6929 | 1.6929 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9123 | 0.9223 | 0.9123 | 0.9123 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9057 | 0.9162 | 0.9057 | 0.9057 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8935 | 0.9053 | 0.8935 | 0.8935 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9079 | 0.9292 | 0.9079 | 0.9079 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7733 | 1.7733 | 1.7733 | No | 0.4115 | 0.4339 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9899 | 0.9899 | 0.9899 | No | 0.2057 | 0.4557 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9821 | 0.9821 | 0.9821 | No | 0.2057 | 0.4507 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9766 | 0.9766 | 0.9766 | No | 0.2057 | 0.4460 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9741 | 0.9741 | 0.9741 | No | 0.2057 | 0.4376 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6929 | 1.6929 | 1.6929 | No | 0.4115 | 0.4527 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9123 | 0.9123 | 0.9123 | No | 0.2057 | 0.4242 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9057 | 0.9057 | 0.9057 | No | 0.2057 | 0.4240 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8935 | 0.8935 | 0.8935 | No | 0.2057 | 0.4109 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9079 | 0.9079 | 0.9079 | No | 0.2057 | 0.3416 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7733 | 1.7733 | 1.7733 | 1.7733 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9899 | 0.9899 | 0.9899 | 0.9899 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9821 | 0.9821 | 0.9821 | 0.9821 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9766 | 0.9766 | 0.9766 | 0.9766 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9741 | 0.9741 | 0.9741 | 0.9741 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.6929 | 1.6929 | 1.6929 | 1.6929 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9123 | 0.9123 | 0.9123 | 0.9123 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9057 | 0.9057 | 0.9057 | 0.9057 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8935 | 0.8935 | 0.8935 | 0.8935 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9079 | 0.9079 | 0.9079 | 0.9079 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 347.18 | 133627.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 14.22 | 21606.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.36 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 170.46 | 10689.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.99 | 11792.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 846.53 |
Natural Gas | 0.00 | 347.18 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1193.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 6.80 |
Fans (All) | 81.55 |
Service Water Heating | 31.09 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 404.97 |
Subtotal | 404.97 |
Natural Gas [MJ/m2] | |
Space Heating | 166.09 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 166.09 |
Subtotal | 166.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.21 |
Space Heating | 29.08 |
Space Cooling | 1.19 |
Fans (All) | 14.28 |
Service Water Heating | 5.44 |
Receptacle Equipment | 10.74 |
Miscellaneous | 5.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Min | 8759.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Average | 8759.75 | 0.25 | 0.00 | 0.00 | 0.00 |
Sum | 87597.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45911.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 25474.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 48609.90 | 0.30 | 0.00 | 0.00 | 0.00 |
Sum | 486099.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8754.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 5.17 | 0.00 | 0.00 | 0.00 |
Average | 8758.63 | 1.37 | 0.00 | 0.00 | 0.00 |
Sum | 87586.33 | 13.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Average | 48610.02 | 0.18 | 0.00 | 0.00 | 0.00 |
Sum | 486100.17 | 1.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202504E+10 | 10019.44 | 10-JAN-11:13 | -1.7 | -1.7 | 0.106557E+10 | 1275.40 | 01-JAN-17:19 | -1.7 | -1.7 |
February | 0.192201E+10 | 9776.47 | 18-FEB-00:03 | -1.2 | -1.5 | 0.961839E+09 | 1275.40 | 03-FEB-13:09 | -1.2 | -1.5 |
March | 0.251384E+10 | 8507.33 | 03-MAR-00:03 | 1.55 | 0.95 | 0.105646E+10 | 1291.39 | 19-MAR-17:49 | 11.17 | 10.56 |
April | 0.630968E+10 | 9898.99 | 30-APR-16:07 | 24.00 | 13.04 | 0.111650E+10 | 1685.87 | 29-APR-12:00 | 24.00 | 13.04 |
May | 0.689075E+10 | 7694.78 | 23-MAY-17:10 | 18.00 | 13.65 | 0.117874E+10 | 1685.86 | 21-MAY-17:40 | 18.00 | 13.65 |
June | 0.796386E+10 | 10901.85 | 13-JUN-17:00 | 27.00 | 17.53 | 0.128816E+10 | 1685.91 | 25-JUN-17:30 | 21.50 | 17.05 |
July | 0.932021E+10 | 17107.02 | 23-JUL-07:03 | 18.17 | 14.53 | 0.138962E+10 | 1685.94 | 16-JUL-12:00 | 18.17 | 14.53 |
August | 0.948404E+10 | 10787.79 | 14-AUG-17:00 | 27.00 | 14.39 | 0.139131E+10 | 1685.95 | 18-AUG-12:20 | 21.00 | 16.54 |
September | 0.819846E+10 | 9665.07 | 13-SEP-16:10 | 23.00 | 16.14 | 0.133162E+10 | 1685.95 | 10-SEP-16:49 | 23.00 | 16.14 |
October | 0.569000E+10 | 7530.74 | 05-OCT-20:05 | 5.17 | 4.18 | 0.113464E+10 | 1667.31 | 07-OCT-12:00 | 17.00 | 9.21 |
November | 0.278679E+10 | 7335.96 | 03-NOV-23:03 | 4.00 | 2.72 | 0.103093E+10 | 1302.46 | 10-NOV-13:00 | 12.00 | 8.91 |
December | 0.151325E+10 | 10605.33 | 30-DEC-00:02 | -2.8 | -4.3 | 0.107072E+10 | 1275.40 | 17-DEC-18:00 | -2.8 | -4.3 |
Annual Sum or Average | 0.646179E+11 | 0.140161E+11 | ||||||||
Minimum of Months | 0.151325E+10 | 7335.96 | -2.8 | -4.3 | 0.961839E+09 | 1275.40 | -2.8 | -4.3 | ||
Maximum of Months | 0.948404E+10 | 17107.02 | 27.00 | 17.53 | 0.139131E+10 | 1685.95 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115007E+10 | 3444.62 | 22-JAN-09:01 | 1.17 | 0.40 | 0.559147E+09 | 784.26 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.115932E+10 | 3449.77 | 12-FEB-09:01 | 2.33 | 1.83 | 0.503848E+09 | 785.16 | 12-FEB-18:00 | 4.00 | 3.53 |
March | 0.143588E+10 | 3228.61 | 12-MAR-08:61 | 3.33 | 1.48 | 0.558507E+09 | 834.67 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.290013E+10 | 18497.82 | 29-APR-18:44 | 18.33 | 11.61 | 0.622695E+09 | 842.91 | 30-APR-17:00 | 24.00 | 13.13 |
May | 0.320741E+10 | 17519.86 | 21-MAY-17:07 | 20.00 | 12.86 | 0.652507E+09 | 842.90 | 14-MAY-17:00 | 20.00 | 12.86 |
June | 0.434197E+10 | 16198.48 | 25-JUN-19:57 | 17.00 | 13.49 | 0.672837E+09 | 842.91 | 25-JUN-17:10 | 17.00 | 13.49 |
July | 0.545428E+10 | 15557.24 | 21-JUL-20:36 | 18.33 | 14.39 | 0.704737E+09 | 842.94 | 23-JUL-17:10 | 21.00 | 16.54 |
August | 0.578237E+10 | 18409.38 | 14-AUG-21:16 | 17.47 | 11.81 | 0.695733E+09 | 842.94 | 18-AUG-12:50 | 21.00 | 16.54 |
September | 0.479233E+10 | 15833.50 | 24-SEP-18:20 | 17.33 | 13.71 | 0.680990E+09 | 842.94 | 10-SEP-16:10 | 17.33 | 13.71 |
October | 0.259060E+10 | 3901.94 | 03-OCT-20:10 | 7.17 | 6.10 | 0.635163E+09 | 842.90 | 01-OCT-17:00 | 7.17 | 6.10 |
November | 0.155071E+10 | 3220.32 | 05-NOV-08:61 | 3.50 | 2.51 | 0.549718E+09 | 836.68 | 05-NOV-17:00 | 6.00 | 5.05 |
December | 0.787355E+09 | 2724.10 | 31-DEC-13:55 | 4.00 | 2.70 | 0.558140E+09 | 771.65 | 24-DEC-18:00 | 4.00 | 2.70 |
Annual Sum or Average | 0.351524E+11 | 0.739402E+10 | ||||||||
Minimum of Months | 0.787355E+09 | 2724.10 | 1.17 | 0.40 | 0.503848E+09 | 771.65 | 4.00 | 2.70 | ||
Maximum of Months | 0.578237E+10 | 18497.82 | 20.00 | 14.39 | 0.704737E+09 | 842.94 | 24.00 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749457E+09 | 4525.62 | 11-JAN-09:43 | -3.2 | -4.6 | 0.317375E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.731869E+09 | 2987.13 | 10-FEB-08:61 | 4.33 | 4.19 | 0.288171E+09 | 647.99 | 04-FEB-13:00 | 4.33 | 4.19 |
March | 0.101236E+10 | 3686.79 | 21-MAR-07:01 | 1.33 | 0.86 | 0.326984E+09 | 710.85 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.232336E+10 | 5033.95 | 30-APR-15:00 | 24.00 | 13.13 | 0.357300E+09 | 842.90 | 29-APR-12:00 | 24.00 | 13.13 |
May | 0.258317E+10 | 4104.95 | 23-MAY-17:10 | 18.00 | 13.65 | 0.379121E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.306465E+10 | 5639.68 | 13-JUN-16:10 | 26.58 | 17.67 | 0.411186E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.374845E+10 | 15190.15 | 23-JUL-07:03 | 18.17 | 14.53 | 0.418179E+09 | 842.90 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.409623E+10 | 5621.21 | 14-AUG-16:10 | 26.17 | 15.64 | 0.430730E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.336442E+10 | 5162.11 | 13-SEP-14:00 | 23.00 | 16.22 | 0.408184E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.211420E+10 | 3485.59 | 12-OCT-07:02 | 3.67 | 3.67 | 0.360003E+09 | 842.89 | 07-OCT-12:20 | 3.67 | 3.67 |
November | 0.112137E+10 | 3677.93 | 04-NOV-07:01 | 1.33 | 0.86 | 0.308312E+09 | 660.59 | 25-NOV-13:50 | 10.00 | 5.58 |
December | 0.469621E+09 | 3274.80 | 29-DEC-10:33 | 2.00 | -0.2 | 0.316799E+09 | 637.68 | 02-DEC-13:00 | 2.00 | -0.2 |
Annual Sum or Average | 0.253792E+11 | 0.432234E+10 | ||||||||
Minimum of Months | 0.469621E+09 | 2987.13 | -3.2 | -4.6 | 0.288171E+09 | 637.68 | 2.00 | -0.2 | ||
Maximum of Months | 0.409623E+10 | 15190.15 | 26.58 | 17.67 | 0.430730E+09 | 842.93 | 24.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623957E+09 | 2967.43 | 26-JAN-08:61 | 4.27 | 3.77 | 0.317243E+09 | 637.68 | 21-JAN-13:09 | 4.27 | 3.77 |
February | 0.617076E+09 | 2968.60 | 10-FEB-08:61 | 4.33 | 4.19 | 0.288130E+09 | 643.15 | 04-FEB-13:00 | 4.33 | 4.19 |
March | 0.875158E+09 | 2994.81 | 29-MAR-07:01 | 4.17 | 3.69 | 0.326617E+09 | 704.27 | 25-MAR-12:00 | 4.17 | 3.69 |
April | 0.218745E+10 | 4941.01 | 30-APR-15:00 | 24.00 | 13.13 | 0.353468E+09 | 842.90 | 29-APR-12:00 | 24.00 | 13.13 |
May | 0.246995E+10 | 3979.11 | 23-MAY-17:10 | 18.00 | 13.65 | 0.375188E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.297105E+10 | 5575.70 | 13-JUN-16:10 | 26.58 | 17.67 | 0.410161E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.367588E+10 | 15512.82 | 23-JUL-07:03 | 18.17 | 14.53 | 0.417869E+09 | 842.90 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.403627E+10 | 5572.74 | 14-AUG-16:10 | 26.17 | 15.64 | 0.430694E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.327843E+10 | 5110.29 | 13-SEP-14:00 | 23.00 | 16.22 | 0.407953E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.195309E+10 | 3432.55 | 06-OCT-07:03 | 3.83 | 3.69 | 0.356898E+09 | 842.89 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.965304E+09 | 3232.23 | 16-NOV-08:61 | 3.17 | 2.71 | 0.307722E+09 | 650.51 | 25-NOV-13:50 | 10.00 | 5.58 |
December | 0.393294E+09 | 3175.48 | 27-DEC-11:23 | 2.50 | 2.06 | 0.316798E+09 | 637.68 | 02-DEC-13:09 | 2.50 | 2.06 |
Annual Sum or Average | 0.240469E+11 | 0.430874E+10 | ||||||||
Minimum of Months | 0.393294E+09 | 2967.43 | 2.50 | 2.06 | 0.288130E+09 | 637.68 | 2.50 | 2.06 | ||
Maximum of Months | 0.403627E+10 | 15512.82 | 26.58 | 17.67 | 0.430694E+09 | 842.93 | 24.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464906E+09 | 4500.32 | 11-JAN-20:53 | -3.0 | -4.5 | 0.317185E+09 | 637.68 | 14-JAN-13:30 | 9.00 | 6.15 |
February | 0.469280E+09 | 3040.25 | 25-FEB-18:43 | 3.17 | 3.09 | 0.288100E+09 | 637.68 | 11-FEB-13:50 | 3.17 | 3.09 |
March | 0.687482E+09 | 3296.27 | 15-MAR-09:23 | 2.00 | 1.57 | 0.326234E+09 | 692.44 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.196320E+10 | 4698.24 | 30-APR-15:00 | 24.00 | 13.13 | 0.347561E+09 | 842.90 | 29-APR-12:00 | 24.00 | 13.13 |
May | 0.224516E+10 | 3711.07 | 23-MAY-17:10 | 18.00 | 13.65 | 0.368874E+09 | 842.90 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.270222E+10 | 5368.26 | 13-JUN-16:10 | 26.58 | 17.67 | 0.406682E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.341495E+10 | 13924.16 | 23-JUL-07:03 | 18.17 | 14.53 | 0.416823E+09 | 842.90 | 22-JUL-12:09 | 18.17 | 14.53 |
August | 0.379446E+10 | 5407.76 | 14-AUG-16:10 | 26.17 | 15.64 | 0.430561E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.301496E+10 | 4928.00 | 13-SEP-14:00 | 23.00 | 16.22 | 0.407042E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.169542E+10 | 3358.22 | 06-OCT-07:03 | 3.83 | 3.69 | 0.351844E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.766577E+09 | 3033.15 | 29-NOV-11:03 | 3.17 | 1.54 | 0.307219E+09 | 639.98 | 25-NOV-13:50 | 3.17 | 1.54 |
December | 0.284481E+09 | 3061.50 | 30-DEC-11:03 | 3.00 | -0.6 | 0.316797E+09 | 637.68 | 09-DEC-13:39 | 3.00 | -0.6 |
Annual Sum or Average | 0.215031E+11 | 0.428492E+10 | ||||||||
Minimum of Months | 0.284481E+09 | 3033.15 | -3.0 | -4.5 | 0.288100E+09 | 637.68 | 3.00 | -0.6 | ||
Maximum of Months | 0.379446E+10 | 13924.16 | 26.58 | 17.67 | 0.430561E+09 | 842.93 | 24.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407595E+09 | 8249.67 | 07-JAN-18:03 | 2.17 | 1.60 | 0.108441E+10 | 1700.53 | 07-JAN-15:30 | 2.17 | 1.60 |
February | 0.418439E+09 | 6988.54 | 06-FEB-20:33 | 4.67 | 4.67 | 0.987304E+09 | 1700.53 | 11-FEB-15:20 | 7.00 | 4.98 |
March | 0.725795E+09 | 7745.43 | 15-MAR-19:03 | 3.00 | 2.22 | 0.111844E+10 | 1700.56 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.339691E+10 | 8483.44 | 30-APR-15:00 | 24.00 | 13.13 | 0.114016E+10 | 2247.81 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.399672E+10 | 6467.47 | 01-MAY-08:63 | 8.00 | 6.01 | 0.120338E+10 | 2189.87 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.496870E+10 | 9160.07 | 13-JUN-15:00 | 26.00 | 17.83 | 0.133016E+10 | 2247.85 | 24-JUN-14:20 | 18.67 | 13.47 |
July | 0.567765E+10 | 18577.82 | 23-JUL-08:63 | 19.17 | 15.34 | 0.140556E+10 | 2247.85 | 22-JUL-14:00 | 19.17 | 15.34 |
August | 0.609629E+10 | 9326.74 | 14-AUG-16:10 | 26.17 | 15.64 | 0.147576E+10 | 2247.91 | 19-AUG-14:39 | 19.67 | 15.02 |
September | 0.511612E+10 | 8884.14 | 13-SEP-14:20 | 23.00 | 16.22 | 0.136706E+10 | 2247.89 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.288717E+10 | 6911.29 | 03-OCT-19:00 | 6.00 | 5.05 | 0.114881E+10 | 2247.79 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.811792E+09 | 7221.37 | 28-NOV-10:33 | 4.13 | 2.27 | 0.104455E+10 | 1700.53 | 04-NOV-14:30 | 4.13 | 2.27 |
December | 0.163533E+09 | 9039.37 | 18-DEC-19:23 | 0.50 | 0.27 | 0.108625E+10 | 1700.53 | 02-DEC-15:50 | 0.50 | 0.27 |
Annual Sum or Average | 0.346667E+11 | 0.143918E+11 | ||||||||
Minimum of Months | 0.163533E+09 | 6467.47 | 0.50 | 0.27 | 0.987304E+09 | 1700.53 | 0.50 | 0.27 | ||
Maximum of Months | 0.609629E+10 | 18577.82 | 26.17 | 17.83 | 0.147576E+10 | 2247.91 | 24.00 | 15.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176012E+09 | 3154.85 | 21-JAN-18:53 | 3.00 | 2.55 | 0.542169E+09 | 850.24 | 07-JAN-15:39 | 3.00 | 2.55 |
February | 0.186822E+09 | 3962.56 | 23-FEB-20:43 | -0.7 | -0.7 | 0.493631E+09 | 850.24 | 11-FEB-15:20 | -0.7 | -0.7 |
March | 0.323101E+09 | 3381.07 | 15-MAR-10:23 | 2.00 | 1.57 | 0.559398E+09 | 870.42 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.143748E+10 | 4405.96 | 30-APR-15:00 | 24.00 | 13.13 | 0.579942E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.166404E+10 | 3053.11 | 22-MAY-15:00 | 24.00 | 16.08 | 0.614274E+09 | 1123.87 | 27-MAY-14:20 | 15.33 | 10.81 |
June | 0.209532E+10 | 4738.12 | 13-JUN-15:00 | 26.00 | 17.83 | 0.681926E+09 | 1123.89 | 24-JUN-14:30 | 18.50 | 13.33 |
July | 0.267293E+10 | 8554.93 | 23-JUL-08:63 | 19.17 | 15.34 | 0.709760E+09 | 1123.89 | 29-JUL-14:00 | 17.00 | 13.96 |
August | 0.300330E+10 | 4849.72 | 14-AUG-16:10 | 26.17 | 15.64 | 0.738983E+09 | 1123.90 | 26-AUG-14:20 | 17.67 | 14.64 |
September | 0.230888E+10 | 4583.58 | 13-SEP-14:20 | 23.00 | 16.22 | 0.694607E+09 | 1123.90 | 23-SEP-14:00 | 19.00 | 14.78 |
October | 0.116820E+10 | 2995.41 | 05-OCT-20:00 | 5.00 | 4.09 | 0.586004E+09 | 1123.87 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.362684E+09 | 2722.91 | 28-NOV-10:45 | 4.42 | 2.50 | 0.522438E+09 | 850.24 | 25-NOV-15:09 | 4.42 | 2.50 |
December | 75716060.24 | 2967.12 | 15-DEC-19:03 | 3.83 | 3.37 | 0.543106E+09 | 850.24 | 09-DEC-15:09 | 3.83 | 3.37 |
Annual Sum or Average | 0.154745E+11 | 0.726624E+10 | ||||||||
Minimum of Months | 75716060.24 | 2722.91 | -0.7 | -0.7 | 0.493631E+09 | 850.24 | -0.7 | -0.7 | ||
Maximum of Months | 0.300330E+10 | 8554.93 | 26.17 | 17.83 | 0.738983E+09 | 1123.90 | 24.00 | 14.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158358E+09 | 3123.41 | 21-JAN-18:43 | 3.17 | 2.71 | 0.542154E+09 | 850.24 | 07-JAN-15:30 | 3.17 | 2.71 |
February | 0.167940E+09 | 3902.50 | 16-FEB-19:33 | -0.3 | -0.5 | 0.493633E+09 | 850.24 | 04-FEB-15:09 | -0.3 | -0.5 |
March | 0.291591E+09 | 1743.03 | 23-MAR-09:25 | 9.00 | 6.40 | 0.559360E+09 | 866.34 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.139165E+10 | 4324.55 | 30-APR-15:00 | 24.00 | 13.13 | 0.578487E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.161266E+10 | 2975.26 | 22-MAY-15:00 | 24.00 | 16.08 | 0.612503E+09 | 1123.87 | 27-MAY-14:20 | 15.33 | 10.81 |
June | 0.205351E+10 | 4659.45 | 13-JUN-15:00 | 26.00 | 17.83 | 0.680028E+09 | 1123.89 | 24-JUN-14:30 | 18.50 | 13.33 |
July | 0.261355E+10 | 8066.02 | 23-JUL-08:63 | 19.17 | 15.34 | 0.709086E+09 | 1123.89 | 29-JUL-14:00 | 17.00 | 13.96 |
August | 0.293345E+10 | 4781.67 | 14-AUG-16:10 | 26.17 | 15.64 | 0.738910E+09 | 1123.90 | 26-AUG-14:20 | 17.67 | 14.64 |
September | 0.226201E+10 | 4518.57 | 13-SEP-14:20 | 23.00 | 16.22 | 0.693854E+09 | 1123.90 | 23-SEP-14:50 | 19.00 | 14.78 |
October | 0.113083E+10 | 2991.48 | 05-OCT-20:00 | 5.00 | 4.09 | 0.584441E+09 | 1123.87 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.332367E+09 | 3088.00 | 29-NOV-19:33 | 3.33 | 3.18 | 0.522371E+09 | 850.24 | 18-NOV-15:30 | 3.33 | 3.18 |
December | 63973579.38 | 3117.76 | 22-DEC-20:43 | 3.17 | 2.71 | 0.543109E+09 | 850.24 | 02-DEC-15:39 | 3.17 | 2.71 |
Annual Sum or Average | 0.150119E+11 | 0.725794E+10 | ||||||||
Minimum of Months | 63973579.38 | 1743.03 | -0.3 | -0.5 | 0.493633E+09 | 850.24 | -0.3 | -0.5 | ||
Maximum of Months | 0.293345E+10 | 8066.02 | 26.17 | 17.83 | 0.738910E+09 | 1123.90 | 24.00 | 14.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96737786.60 | 3180.50 | 05-JAN-18:03 | 2.98 | 2.54 | 0.542176E+09 | 850.24 | 14-JAN-15:39 | 7.00 | 5.29 |
February | 96781435.39 | 4063.30 | 17-FEB-19:33 | -1.0 | -1.4 | 0.493622E+09 | 850.24 | 04-FEB-15:30 | -1.0 | -1.4 |
March | 0.191258E+09 | 2399.88 | 16-MAR-19:25 | 6.00 | 4.60 | 0.559260E+09 | 851.96 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.121726E+10 | 4092.91 | 30-APR-15:00 | 24.00 | 13.13 | 0.573592E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.141679E+10 | 2739.68 | 22-MAY-15:00 | 24.00 | 16.08 | 0.605711E+09 | 1114.74 | 27-MAY-14:20 | 15.33 | 10.81 |
June | 0.189457E+10 | 4457.27 | 13-JUN-15:00 | 26.00 | 17.83 | 0.670651E+09 | 1123.89 | 24-JUN-14:30 | 18.50 | 13.33 |
July | 0.241188E+10 | 6479.07 | 23-JUL-08:63 | 19.17 | 15.34 | 0.705586E+09 | 1123.89 | 15-JUL-14:09 | 19.17 | 15.34 |
August | 0.270444E+10 | 4595.53 | 14-AUG-16:10 | 26.17 | 15.64 | 0.738548E+09 | 1123.90 | 19-AUG-14:09 | 19.17 | 14.84 |
September | 0.207294E+10 | 4349.81 | 13-SEP-14:30 | 23.00 | 16.22 | 0.689057E+09 | 1123.90 | 23-SEP-14:50 | 19.00 | 14.78 |
October | 0.977520E+09 | 2928.64 | 05-OCT-20:00 | 5.00 | 4.09 | 0.578033E+09 | 1123.87 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.229947E+09 | 1977.69 | 04-NOV-12:25 | 8.00 | 6.09 | 0.522246E+09 | 850.24 | 25-NOV-15:30 | 8.50 | 5.07 |
December | 31026844.02 | 3244.83 | 06-DEC-19:13 | 2.67 | 2.22 | 0.543110E+09 | 850.24 | 02-DEC-15:30 | 2.67 | 2.22 |
Annual Sum or Average | 0.133411E+11 | 0.722159E+10 | ||||||||
Minimum of Months | 31026844.02 | 1977.69 | -1.0 | -1.4 | 0.493622E+09 | 850.24 | -1.0 | -1.4 | ||
Maximum of Months | 0.270444E+10 | 6479.07 | 26.17 | 17.83 | 0.738548E+09 | 1123.90 | 24.00 | 15.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8845535.65 | 1020.13 | 21-JAN-12:00 | 7.00 | 5.55 | 0.542193E+09 | 850.24 | 07-JAN-15:20 | 7.00 | 5.55 |
February | 7638111.48 | 863.17 | 04-FEB-12:00 | 8.00 | 5.24 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | 8.00 | 6.08 |
March | 33630876.01 | 2522.57 | 10-MAR-18:55 | 5.30 | 3.64 | 0.559176E+09 | 850.25 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.889302E+09 | 3848.19 | 30-APR-15:00 | 24.00 | 13.13 | 0.569064E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.102385E+10 | 2548.28 | 22-MAY-15:00 | 24.00 | 16.08 | 0.596221E+09 | 1072.60 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.165777E+10 | 4363.49 | 13-JUN-15:00 | 26.00 | 17.83 | 0.653665E+09 | 1123.89 | 24-JUN-14:30 | 18.50 | 13.33 |
July | 0.214577E+10 | 5952.05 | 22-JUL-15:00 | 29.00 | 17.00 | 0.699318E+09 | 1123.89 | 15-JUL-14:09 | 29.00 | 17.00 |
August | 0.238613E+10 | 4395.24 | 14-AUG-15:00 | 25.00 | 16.02 | 0.736800E+09 | 1123.90 | 12-AUG-14:09 | 25.00 | 16.02 |
September | 0.180043E+10 | 4191.44 | 13-SEP-14:20 | 23.00 | 16.22 | 0.678731E+09 | 1123.90 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.627123E+09 | 2642.09 | 03-OCT-19:00 | 6.00 | 5.05 | 0.569375E+09 | 1123.87 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 49461534.50 | 3103.58 | 03-NOV-18:03 | 3.17 | 2.33 | 0.522239E+09 | 850.24 | 04-NOV-14:50 | 9.00 | 6.58 |
December | 1067909.39 | 376.16 | 06-DEC-12:00 | 8.00 | 5.65 | 0.543112E+09 | 850.24 | 02-DEC-15:20 | 8.00 | 5.65 |
Annual Sum or Average | 0.106310E+11 | 0.716353E+10 | ||||||||
Minimum of Months | 1067909.39 | 376.16 | 3.17 | 2.33 | 0.493640E+09 | 850.24 | 7.00 | 5.55 | ||
Maximum of Months | 0.238613E+10 | 5952.05 | 29.00 | 17.83 | 0.736800E+09 | 1123.90 | 29.00 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207242E+10 | 52910.56 | 31-JAN-08:61 | 1.17 |
February | 0.137675E+10 | 52913.23 | 17-FEB-08:61 | -2.3 |
March | 0.126409E+10 | 52914.26 | 03-MAR-08:61 | 3.17 |
April | 0.251771E+09 | 52716.13 | 01-APR-07:01 | 4.17 |
May | 0.142413E+09 | 52688.84 | 05-MAY-07:01 | 7.17 |
June | 61358612.80 | 3119.57 | 08-JUN-07:02 | 10.17 |
July | 45780732.44 | 1171.53 | 23-JUL-07:05 | 18.17 |
August | 42535156.64 | 712.06 | 30-AUG-07:05 | 12.33 |
September | 63835796.23 | 748.31 | 08-SEP-07:13 | 10.67 |
October | 0.233711E+09 | 52702.64 | 23-OCT-07:01 | 4.50 |
November | 0.935199E+09 | 52918.21 | 20-NOV-08:61 | 1.33 |
December | 0.261532E+10 | 52899.00 | 15-DEC-08:61 | 1.33 |
Annual Sum or Average | 0.910518E+10 | |||
Minimum of Months | 42535156.64 | 712.06 | -2.3 | |
Maximum of Months | 0.261532E+10 | 52918.21 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486415E+09 | 28759.67 | 31-JAN-08:61 | 1.17 |
February | 0.250159E+09 | 28762.89 | 17-FEB-08:61 | -2.3 |
March | 0.227441E+09 | 28752.32 | 04-MAR-08:61 | 4.00 |
April | 99949574.99 | 10610.42 | 01-APR-07:01 | 4.17 |
May | 90068017.09 | 1073.03 | 03-MAY-07:13 | 7.33 |
June | 26744563.01 | 1243.98 | 13-JUN-07:10 | 19.33 |
July | 16915784.35 | 1590.54 | 23-JUL-07:05 | 18.17 |
August | 5302590.56 | 1207.87 | 06-AUG-07:10 | 13.17 |
September | 29270230.49 | 1112.88 | 16-SEP-07:10 | 14.33 |
October | 0.106997E+09 | 2935.79 | 28-OCT-07:01 | 4.67 |
November | 0.189084E+09 | 28758.92 | 29-NOV-08:61 | -0.7 |
December | 0.595321E+09 | 28756.64 | 15-DEC-08:61 | 1.33 |
Annual Sum or Average | 0.212367E+10 | |||
Minimum of Months | 5302590.56 | 1073.03 | -2.3 | |
Maximum of Months | 0.595321E+09 | 28762.89 | 19.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.788169E+09 | 28337.71 | 10-JAN-07:01 | -4.3 |
February | 0.447123E+09 | 28199.24 | 19-FEB-08:61 | 1.17 |
March | 0.380492E+09 | 27455.68 | 06-MAR-07:02 | 4.33 |
April | 0.111918E+09 | 7069.71 | 01-APR-06:03 | 3.17 |
May | 87353946.13 | 2485.15 | 06-MAY-06:03 | 3.50 |
June | 28862938.03 | 1122.91 | 27-JUN-06:10 | 15.00 |
July | 23466148.09 | 2041.27 | 22-JUL-17:12 | 29.33 |
August | 5875873.97 | 1181.56 | 06-AUG-07:10 | 13.17 |
September | 32043315.02 | 957.03 | 02-SEP-06:10 | 13.17 |
October | 0.113807E+09 | 5065.57 | 23-OCT-06:03 | 4.00 |
November | 0.338494E+09 | 27993.66 | 20-NOV-07:02 | 1.00 |
December | 0.963552E+09 | 28347.12 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.332116E+10 | |||
Minimum of Months | 5875873.97 | 957.03 | -4.3 | |
Maximum of Months | 0.963552E+09 | 28347.12 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.921858E+09 | 28219.03 | 10-JAN-07:01 | -4.3 |
February | 0.547526E+09 | 28081.08 | 19-FEB-08:61 | 1.17 |
March | 0.475128E+09 | 27867.44 | 05-MAR-08:62 | 3.33 |
April | 0.128484E+09 | 10521.42 | 02-APR-07:03 | 5.17 |
May | 92298156.32 | 4833.67 | 06-MAY-06:03 | 3.50 |
June | 36703395.31 | 1055.54 | 27-JUN-06:10 | 15.00 |
July | 27579630.43 | 2041.23 | 22-JUL-17:12 | 29.33 |
August | 6633981.18 | 1121.87 | 06-AUG-07:10 | 13.17 |
September | 39416247.51 | 947.05 | 20-SEP-06:40 | 6.67 |
October | 0.124975E+09 | 8485.97 | 23-OCT-06:03 | 4.00 |
November | 0.428036E+09 | 27886.60 | 19-NOV-08:62 | 4.00 |
December | 0.112387E+10 | 28228.09 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.395250E+10 | |||
Minimum of Months | 6633981.18 | 947.05 | -4.3 | |
Maximum of Months | 0.112387E+10 | 28228.09 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112455E+10 | 28166.61 | 10-JAN-07:01 | -4.3 |
February | 0.723402E+09 | 28029.79 | 19-FEB-08:61 | 1.17 |
March | 0.640177E+09 | 27820.63 | 05-MAR-08:62 | 3.33 |
April | 0.153762E+09 | 14022.07 | 02-APR-07:03 | 5.17 |
May | 0.104838E+09 | 7625.24 | 06-MAY-06:03 | 3.50 |
June | 53268404.96 | 976.74 | 09-JUN-07:00 | 12.00 |
July | 35128941.67 | 2042.34 | 22-JUL-17:12 | 29.33 |
August | 10678818.54 | 838.50 | 24-AUG-06:10 | 8.83 |
September | 54314557.10 | 1016.09 | 21-SEP-07:00 | 7.00 |
October | 0.150918E+09 | 11349.82 | 23-OCT-06:03 | 4.00 |
November | 0.560991E+09 | 27836.94 | 19-NOV-08:62 | 4.00 |
December | 0.137901E+10 | 28174.93 | 31-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.499105E+10 | |||
Minimum of Months | 10678818.54 | 838.50 | -4.3 | |
Maximum of Months | 0.137901E+10 | 28174.93 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244708E+10 | 51138.48 | 31-JAN-08:61 | 1.17 |
February | 0.161496E+10 | 51136.57 | 17-FEB-08:61 | -2.3 |
March | 0.145169E+10 | 51136.98 | 03-MAR-08:61 | 3.17 |
April | 0.286063E+09 | 50948.66 | 01-APR-07:01 | 4.17 |
May | 0.153421E+09 | 50930.60 | 05-MAY-07:01 | 7.17 |
June | 61680792.86 | 3412.37 | 08-JUN-07:02 | 10.17 |
July | 53848065.47 | 2909.93 | 22-JUL-17:03 | 29.17 |
August | 40164932.36 | 769.73 | 17-AUG-07:10 | 15.17 |
September | 62556417.85 | 732.10 | 08-SEP-07:13 | 10.67 |
October | 0.340532E+09 | 50948.30 | 23-OCT-07:01 | 4.50 |
November | 0.126475E+10 | 51147.39 | 20-NOV-08:61 | 1.33 |
December | 0.298058E+10 | 51127.30 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.107573E+11 | |||
Minimum of Months | 40164932.36 | 732.10 | -2.3 | |
Maximum of Months | 0.298058E+10 | 51147.39 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145743E+10 | 27058.08 | 31-JAN-08:61 | 1.17 |
February | 0.100426E+10 | 27057.61 | 17-FEB-08:61 | -2.3 |
March | 0.912802E+09 | 27056.92 | 03-MAR-08:61 | 3.17 |
April | 0.204029E+09 | 26951.62 | 01-APR-07:01 | 4.17 |
May | 0.135244E+09 | 26942.93 | 05-MAY-07:01 | 7.17 |
June | 73573656.24 | 1443.41 | 08-JUN-07:02 | 10.17 |
July | 50495708.30 | 2022.20 | 22-JUL-17:12 | 29.33 |
August | 31976540.79 | 930.32 | 27-AUG-08:15 | 16.00 |
September | 71396445.90 | 1006.85 | 21-SEP-07:25 | 10.00 |
October | 0.235268E+09 | 26952.51 | 23-OCT-07:01 | 4.50 |
November | 0.788430E+09 | 27062.87 | 20-NOV-08:61 | 1.33 |
December | 0.177060E+10 | 27052.61 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.673552E+10 | |||
Minimum of Months | 31976540.79 | 930.32 | -2.3 | |
Maximum of Months | 0.177060E+10 | 27062.87 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153546E+10 | 26912.94 | 31-JAN-08:61 | 1.17 |
February | 0.107223E+10 | 26912.33 | 17-FEB-08:61 | -2.3 |
March | 0.970041E+09 | 26912.53 | 03-MAR-08:61 | 3.17 |
April | 0.219233E+09 | 26808.54 | 01-APR-07:01 | 4.17 |
May | 0.139721E+09 | 26799.46 | 05-MAY-07:01 | 7.17 |
June | 75703015.27 | 3035.75 | 08-JUN-07:02 | 10.17 |
July | 54363437.57 | 2018.06 | 22-JUL-17:12 | 29.33 |
August | 38326604.88 | 924.74 | 27-AUG-08:15 | 16.00 |
September | 74805951.73 | 1000.61 | 21-SEP-07:25 | 10.00 |
October | 0.254561E+09 | 26808.65 | 23-OCT-07:01 | 4.50 |
November | 0.839768E+09 | 26918.50 | 20-NOV-08:61 | 1.33 |
December | 0.183935E+10 | 26907.83 | 27-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.711356E+10 | |||
Minimum of Months | 38326604.88 | 924.74 | -2.3 | |
Maximum of Months | 0.183935E+10 | 26918.50 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186428E+10 | 26645.55 | 31-JAN-08:61 | 1.17 |
February | 0.135544E+10 | 26645.18 | 17-FEB-08:61 | -2.3 |
March | 0.124269E+10 | 26645.02 | 03-MAR-08:61 | 3.17 |
April | 0.285462E+09 | 26543.79 | 01-APR-07:01 | 4.17 |
May | 0.176925E+09 | 26533.33 | 05-MAY-07:01 | 7.17 |
June | 85149618.90 | 10088.20 | 08-JUN-07:02 | 10.17 |
July | 69128087.61 | 2012.57 | 22-JUL-17:12 | 29.33 |
August | 63536421.75 | 917.13 | 27-AUG-08:15 | 16.00 |
September | 86104489.80 | 989.21 | 21-SEP-07:25 | 10.00 |
October | 0.341687E+09 | 26543.08 | 23-OCT-07:01 | 4.50 |
November | 0.106271E+10 | 26650.81 | 20-NOV-08:61 | 1.33 |
December | 0.218579E+10 | 26639.76 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.881890E+10 | |||
Minimum of Months | 63536421.75 | 917.13 | -2.3 | |
Maximum of Months | 0.218579E+10 | 26650.81 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329914E+10 | 26977.07 | 10-JAN-08:13 | -5.3 |
February | 0.261900E+10 | 26971.08 | 17-FEB-08:61 | -2.3 |
March | 0.245789E+10 | 26970.40 | 03-MAR-08:61 | 3.17 |
April | 0.598461E+09 | 26865.12 | 01-APR-07:01 | 4.17 |
May | 0.408816E+09 | 26845.92 | 05-MAY-07:01 | 7.17 |
June | 0.108972E+09 | 26158.00 | 08-JUN-07:02 | 10.17 |
July | 96400679.24 | 8808.15 | 05-JUL-07:03 | 12.17 |
August | 92192073.43 | 959.48 | 08-AUG-08:00 | 17.00 |
September | 96308455.82 | 3806.80 | 20-SEP-07:03 | 7.67 |
October | 0.777782E+09 | 26861.31 | 23-OCT-07:01 | 4.50 |
November | 0.205424E+10 | 26977.28 | 20-NOV-08:61 | 1.33 |
December | 0.375683E+10 | 26963.31 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.163660E+11 | |||
Minimum of Months | 92192073.43 | 959.48 | -5.3 | |
Maximum of Months | 0.375683E+10 | 26977.28 | 17.00 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379000E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341661E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323488E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262326.57 | 0.233889E+10 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18090.27 | 0.282597E+10 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10780497.99 | 0.209986E+10 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47466109.68 | 0.181531E+10 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6334474.50 | 0.148201E+10 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185743E+10 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260818E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340836E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424874E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64861499.01 | 0.331262E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148201E+10 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47466109.68 | 0.424874E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205245E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180943E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175594E+10 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144850.99 | 0.134258E+10 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.45 | 0.151547E+10 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5884328.75 | 0.110506E+10 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25991769.94 | 0.907097E+09 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3452286.10 | 0.727024E+09 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957734E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145093E+10 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178801E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219712E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35483207.23 | 0.176089E+11 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727024E+09 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25991769.94 | 0.219712E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205881E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182599E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175827E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.133278E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.13 | 0.153402E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5843485.81 | 0.114909E+10 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25545747.12 | 0.954078E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452280.78 | 0.766102E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989599E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145222E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180354E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223470E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34920589.16 | 0.178592E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766102E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25545747.12 | 0.223470E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205725E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182431E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175643E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.131809E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9970.76 | 0.151646E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5843645.13 | 0.114370E+10 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25542609.81 | 0.951585E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452276.69 | 0.765330E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987662E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143946E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179893E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223137E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34917606.70 | 0.177906E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765330E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25542609.81 | 0.223137E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205614E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182272E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175488E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.129612E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9970.31 | 0.148966E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5844048.30 | 0.112783E+10 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25557646.49 | 0.944715E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452264.36 | 0.763209E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982287E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141994E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179538E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222841E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34933033.78 | 0.176813E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763209E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25557646.49 | 0.222841E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370726E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329974E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316325E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123960.25 | 0.225317E+10 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17875.18 | 0.261722E+10 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10511394.07 | 0.194969E+10 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46052710.83 | 0.168791E+10 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6206960.27 | 0.139649E+10 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174128E+10 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248368E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326020E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405224E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62912900.61 | 0.316121E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139649E+10 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46052710.83 | 0.405224E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205721E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182463E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175552E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.126550E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.31 | 0.145792E+10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845671.00 | 0.109785E+10 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25613145.83 | 0.934342E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452176.29 | 0.764064E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974761E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139151E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179755E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223198E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34990062.74 | 0.175528E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764064E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25613145.83 | 0.223198E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205680E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182409E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175517E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.126221E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.30 | 0.145303E+10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845830.10 | 0.109322E+10 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25617927.53 | 0.932064E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452172.81 | 0.763310E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972727E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138771E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179664E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223114E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34995000.05 | 0.175281E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763310E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25617927.53 | 0.223114E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205520E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182166E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175369E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.125105E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.20 | 0.143359E+10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846306.64 | 0.107036E+10 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25630289.03 | 0.920621E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452157.80 | 0.759915E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960363E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137182E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179313E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222711E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35007822.99 | 0.174185E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759915E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25630289.03 | 0.222711E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217490E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200015E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185837E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69520.41 | 0.135824E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10170.83 | 0.172958E+10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6048371.80 | 0.128837E+10 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26421180.18 | 0.115317E+10 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579445.00 | 0.950062E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114009E+10 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154268E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203061E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254873E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36128688.22 | 0.197750E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950062E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26421180.18 | 0.254873E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8006.93 | 11-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6020.31 | 24-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 30-APR-17:00 | 4388.34 | 10-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 | 22-MAY-15:00 | 4507.37 | 01-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 905.90 | 13-JUN-17:00 | 3677.58 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.92 | 22-JUL-15:00 | 3207.48 | 04-JUL-14:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 14-AUG-17:00 | 2483.37 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 3415.75 | 29-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3955.48 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6537.86 | 28-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7437.13 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2483.37 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.92 | 8006.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3320.75 | 24-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 30-APR-17:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2615.82 | 01-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.48 | 13-JUN-17:00 | 2214.55 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1980.79 | 04-JUL-14:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1981.01 | 30-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2196.23 | 21-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2610.14 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2211.67 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1952.12 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1986.52 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2601.95 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2185.70 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1931.44 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1985.44 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2568.67 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2118.03 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1877.22 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1976.92 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7953.76 | 11-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5964.69 | 24-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 30-APR-15:00 | 4338.71 | 10-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 22-MAY-15:00 | 4433.04 | 01-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.63 | 13-JUN-17:00 | 3607.27 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.92 | 22-JUL-15:00 | 3028.73 | 04-JUL-14:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 892.94 | 14-AUG-17:00 | 2418.33 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 3416.45 | 30-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3927.70 | 27-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6449.59 | 28-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7352.49 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.33 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.92 | 7953.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2526.64 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2017.38 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1758.09 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.86 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1959.09 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.86 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2517.03 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2010.40 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1748.03 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.86 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1956.84 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.86 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2476.45 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2006.47 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1702.89 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.86 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1932.97 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.86 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.13 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.03 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 30-APR-15:00 | 2465.64 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 22-MAY-15:00 | 2503.74 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.69 | 13-JUN-17:00 | 2076.78 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 22-JUL-15:00 | 1666.39 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.51 | 14-AUG-17:00 | 1408.86 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1918.57 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2215.69 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3678.60 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4178.83 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.86 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 4485.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10019.44 | 10-JAN-11:13 | 2700.03 | 20351.80 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1116.63 |
February | 9776.47 | 18-FEB-00:03 | 1350.01 | 10711.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 |
March | 8507.33 | 03-MAR-00:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9898.99 | 30-APR-16:07 | 12150.11 | 15263.85 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
May | 7694.78 | 23-MAY-17:10 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.66 |
June | 10901.85 | 13-JUN-17:00 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 905.90 | 0.00 |
July | 17107.02 | 23-JUL-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.49 |
August | 10787.79 | 14-AUG-17:00 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 0.00 |
September | 9665.07 | 13-SEP-16:10 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.03 |
October | 7530.74 | 05-OCT-20:05 | 4050.04 | 10175.90 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 |
November | 7335.96 | 03-NOV-23:03 | 1012.51 | 8033.58 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.50 |
December | 10605.33 | 30-DEC-00:02 | 1687.52 | 13389.30 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7335.96 | 1012.51 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17107.02 | 12150.11 | 20351.80 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.90 | 1116.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3444.62 | 22-JAN-09:01 | 1687.47 | 16114.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.55 |
February | 3449.77 | 12-FEB-09:01 | 1687.47 | 16114.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.01 |
March | 3228.61 | 12-MAR-08:61 | 1687.47 | 16114.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.31 |
April | 18497.82 | 29-APR-18:44 | 11812.27 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 |
May | 17519.86 | 21-MAY-17:07 | 18224.65 | 27555.17 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 |
June | 16198.48 | 25-JUN-19:57 | 5399.90 | 12246.74 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
July | 15557.24 | 21-JUL-20:36 | 5062.40 | 15308.43 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
August | 18409.38 | 14-AUG-21:16 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
September | 15833.50 | 24-SEP-18:20 | 4049.92 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 |
October | 3901.94 | 03-OCT-20:10 | 2024.96 | 6123.37 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 |
November | 3220.32 | 05-NOV-08:61 | 1687.47 | 16114.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.96 |
December | 2724.10 | 31-DEC-13:55 | 4049.92 | 6123.37 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2861.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2724.10 | 1687.47 | 6123.37 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | |
Maximum of Months | 18497.82 | 18224.65 | 27555.17 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2861.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4525.62 | 11-JAN-09:43 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.35 |
February | 2987.13 | 10-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.80 |
March | 3686.79 | 21-MAR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.09 |
April | 5033.95 | 30-APR-15:00 | 674.99 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 4104.95 | 23-MAY-17:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
June | 5639.68 | 13-JUN-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 0.00 |
July | 15190.15 | 23-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.17 |
August | 5621.21 | 14-AUG-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 5162.11 | 13-SEP-14:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 3485.59 | 12-OCT-07:02 | 843.73 | 187.50 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.20 |
November | 3677.93 | 04-NOV-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.28 |
December | 3274.80 | 29-DEC-10:33 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2987.13 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15190.15 | 1687.47 | 11156.02 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 580.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2967.43 | 26-JAN-08:61 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.40 |
February | 2968.60 | 10-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.77 |
March | 2994.81 | 29-MAR-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.89 |
April | 4941.01 | 30-APR-15:00 | 674.99 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 3979.11 | 23-MAY-17:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
June | 5575.70 | 13-JUN-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 0.00 |
July | 15512.82 | 23-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.23 |
August | 5572.74 | 14-AUG-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 5110.29 | 13-SEP-14:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 3432.55 | 06-OCT-07:03 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.59 |
November | 3232.23 | 16-NOV-08:61 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.54 |
December | 3175.48 | 27-DEC-11:23 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2967.43 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15512.82 | 1687.47 | 8367.02 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 460.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4500.32 | 11-JAN-20:53 | 674.99 | 5871.59 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
February | 3040.25 | 25-FEB-18:43 | 506.24 | 4403.69 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.89 |
March | 3296.27 | 15-MAR-09:23 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.10 |
April | 4698.24 | 30-APR-15:00 | 674.99 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 3711.07 | 23-MAY-17:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.62 |
June | 5368.26 | 13-JUN-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 0.00 |
July | 13924.16 | 23-JUL-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 |
August | 5407.76 | 14-AUG-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 4928.00 | 13-SEP-14:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 3358.22 | 06-OCT-07:03 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.49 |
November | 3033.15 | 29-NOV-11:03 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.90 |
December | 3061.50 | 30-DEC-11:03 | 2024.96 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3033.15 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13924.16 | 2024.96 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 433.20 | 446.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8249.67 | 07-JAN-18:03 | 2970.03 | 6719.20 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.98 |
February | 6988.54 | 06-FEB-20:33 | 2227.52 | 5039.40 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 |
March | 7745.43 | 15-MAR-19:03 | 2227.52 | 5039.40 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 |
April | 8483.44 | 30-APR-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 0.00 |
May | 6467.47 | 01-MAY-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.91 |
June | 9160.07 | 13-JUN-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 614.90 | 0.00 |
July | 18577.82 | 23-JUL-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.02 |
August | 9326.74 | 14-AUG-16:10 | 4792.55 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 658.97 | 0.00 |
September | 8884.14 | 13-SEP-14:20 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.99 |
October | 6911.29 | 03-OCT-19:00 | 1755.02 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.30 |
November | 7221.37 | 28-NOV-10:33 | 2227.52 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.24 |
December | 9039.37 | 18-DEC-19:23 | 7020.07 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6467.47 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18577.82 | 7020.07 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.97 | 855.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3154.85 | 21-JAN-18:53 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.90 |
February | 3962.56 | 23-FEB-20:43 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 |
March | 3381.07 | 15-MAR-10:23 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.93 |
April | 4405.96 | 30-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 3053.11 | 22-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 4738.12 | 13-JUN-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 341.90 | 0.00 |
July | 8554.93 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.43 |
August | 4849.72 | 14-AUG-16:10 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 4583.58 | 13-SEP-14:20 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 2995.41 | 05-OCT-20:00 | 371.24 | 862.24 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
November | 2722.91 | 28-NOV-10:45 | 742.49 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.62 |
December | 2967.12 | 15-DEC-19:03 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2722.91 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8554.93 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 424.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3123.41 | 21-JAN-18:43 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.90 |
February | 3902.50 | 16-FEB-19:33 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.22 |
March | 1743.03 | 23-MAR-09:25 | 742.49 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.77 |
April | 4324.55 | 30-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2975.26 | 22-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 4659.45 | 13-JUN-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 341.90 | 0.00 |
July | 8066.02 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.30 |
August | 4781.67 | 14-AUG-16:10 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 4518.57 | 13-SEP-14:20 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 2991.48 | 05-OCT-20:00 | 371.24 | 862.24 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 |
November | 3088.00 | 29-NOV-19:33 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.97 |
December | 3117.76 | 22-DEC-20:43 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1743.03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8066.02 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 512.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3180.50 | 05-JAN-18:03 | 3442.43 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.73 |
February | 4063.30 | 17-FEB-19:33 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.41 |
March | 2399.88 | 16-MAR-19:25 | 742.49 | 1724.48 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 |
April | 4092.91 | 30-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 2739.68 | 22-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 4457.27 | 13-JUN-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 341.90 | 0.00 |
July | 6479.07 | 23-JUL-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.90 |
August | 4595.53 | 14-AUG-16:10 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 4349.81 | 13-SEP-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 2928.64 | 05-OCT-20:00 | 371.24 | 862.24 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 |
November | 1977.69 | 04-NOV-12:25 | 4994.90 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2226.53 |
December | 3244.83 | 06-DEC-19:13 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1977.69 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6479.07 | 4994.90 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 2226.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1020.13 | 21-JAN-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.06 |
February | 863.17 | 04-FEB-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.65 |
March | 2522.57 | 10-MAR-18:55 | 2294.96 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.59 |
April | 3848.19 | 30-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
May | 2548.28 | 22-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
June | 4363.49 | 13-JUN-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 355.58 | 0.00 |
July | 5952.05 | 22-JUL-15:00 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 0.00 |
August | 4395.24 | 14-AUG-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 183.23 | 0.00 |
September | 4191.44 | 13-SEP-14:20 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
October | 2642.09 | 03-OCT-19:00 | 877.48 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.36 |
November | 3103.58 | 03-NOV-18:03 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.06 |
December | 376.16 | 06-DEC-12:00 | 1451.22 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.16 | 877.48 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5952.05 | 2699.95 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 512.06 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.726766E+11 | 59961.02 | 08-JAN-16:49 | 0.737602E+11 | 133627.48 | 10-JAN-08:09 |
February | 0.649889E+11 | 60903.39 | 09-FEB-17:00 | 0.593698E+11 | 114500.56 | 17-FEB-08:09 |
March | 0.716881E+11 | 59662.30 | 01-MAR-18:19 | 0.537658E+11 | 100139.48 | 15-MAR-11:00 |
April | 0.677326E+11 | 61737.17 | 30-APR-14:50 | 0.116509E+11 | 63932.70 | 01-APR-07:10 |
May | 0.693773E+11 | 63249.41 | 22-MAY-14:30 | 0.705937E+10 | 44373.04 | 06-MAY-07:10 |
June | 0.690873E+11 | 68278.61 | 13-JUN-16:49 | 0.232525E+09 | 14085.80 | 07-JUN-11:09 |
July | 0.722440E+11 | 70564.92 | 21-JUL-12:39 | 7308575.63 | 3616.35 | 05-JUL-07:10 |
August | 0.746805E+11 | 66950.34 | 14-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.704022E+11 | 66601.86 | 13-SEP-14:50 | 14607244.30 | 3184.06 | 08-SEP-08:00 |
October | 0.709828E+11 | 57349.90 | 17-OCT-17:00 | 0.142301E+11 | 62026.49 | 23-OCT-07:10 |
November | 0.699165E+11 | 59857.31 | 27-NOV-18:00 | 0.468258E+11 | 103495.09 | 29-NOV-08:09 |
December | 0.727490E+11 | 61418.13 | 14-DEC-17:49 | 0.802613E+11 | 120614.59 | 31-DEC-09:09 |
Annual Sum or Average | 0.846526E+12 | 0.347178E+12 | ||||
Minimum of Months | 0.649889E+11 | 57349.90 | 0.00 | 0.00 | ||
Maximum of Months | 0.746805E+11 | 70564.92 | 0.802613E+11 | 133627.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.718642E+10 | 0.108325E+11 | 0.00 | 0.145286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560105E+10 | 0.00 |
February | 0.312534E+11 | 0.573258E+10 | 0.980803E+10 | 0.00 | 0.131141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508079E+10 | 0.00 |
March | 0.350527E+11 | 0.530631E+10 | 0.110075E+11 | 0.00 | 0.146731E+11 | 0.00 | 0.00 | 69218.80 | 0.00 | 0.00 | 0.00 | 0.564840E+10 | 0.00 |
April | 0.334898E+11 | 0.408375E+10 | 0.105079E+11 | 0.00 | 0.138099E+11 | 0.00 | 0.00 | 0.458129E+09 | 0.00 | 0.00 | 0.00 | 0.538303E+10 | 0.00 |
May | 0.347840E+11 | 0.342792E+10 | 0.109147E+11 | 0.00 | 0.143771E+11 | 0.00 | 0.00 | 0.347329E+09 | 0.00 | 0.00 | 0.00 | 0.552626E+10 | 0.00 |
June | 0.338757E+11 | 0.293540E+10 | 0.106386E+11 | 0.00 | 0.141560E+11 | 0.00 | 0.00 | 0.218228E+10 | 0.00 | 0.00 | 0.00 | 0.529938E+10 | 0.00 |
July | 0.344108E+11 | 0.316576E+10 | 0.107945E+11 | 0.00 | 0.144002E+11 | 0.00 | 0.00 | 0.408119E+10 | 0.00 | 0.00 | 0.00 | 0.539153E+10 | 0.00 |
August | 0.350409E+11 | 0.381843E+10 | 0.110006E+11 | 0.00 | 0.147223E+11 | 0.00 | 0.00 | 0.467225E+10 | 0.00 | 0.00 | 0.00 | 0.542595E+10 | 0.00 |
September | 0.335014E+11 | 0.467851E+10 | 0.105148E+11 | 0.00 | 0.140091E+11 | 0.00 | 0.00 | 0.246069E+10 | 0.00 | 0.00 | 0.00 | 0.523772E+10 | 0.00 |
October | 0.345281E+11 | 0.591429E+10 | 0.108325E+11 | 0.00 | 0.142164E+11 | 0.00 | 0.00 | 20738949.42 | 0.00 | 0.00 | 0.00 | 0.547087E+10 | 0.00 |
November | 0.334535E+11 | 0.666766E+10 | 0.104978E+11 | 0.00 | 0.139432E+11 | 0.00 | 0.00 | 113972.95 | 0.00 | 0.00 | 0.00 | 0.535422E+10 | 0.00 |
December | 0.344233E+11 | 0.744085E+10 | 0.108050E+11 | 0.00 | 0.145088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557112E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.603579E+11 | 0.128154E+12 | 0.00 | 0.170459E+12 | 0.00 | 0.00 | 0.142228E+11 | 0.00 | 0.00 | 0.00 | 0.649903E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.293540E+10 | 0.980803E+10 | 0.00 | 0.131141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508079E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.744085E+10 | 0.110075E+11 | 0.00 | 0.147223E+11 | 0.00 | 0.00 | 0.467225E+10 | 0.00 | 0.00 | 0.00 | 0.564840E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.737602E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.593698E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.537658E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.116509E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.705937E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.232525E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 7308575.63 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 14607244.30 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142301E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.468258E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.802613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347178E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.802613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10689.94 | 10-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10603.32 | 17-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 10539.98 | 15-MAR-11:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10339.12 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 10227.16 | 06-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 10079.02 | 07-JUN-11:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-20:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 10069.15 | 23-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:49 | 8059.50 | 01-AUG-09:09 | 0.00 | 9945.53 | 01-AUG-09:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9974.17 | 08-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10278.90 | 23-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 10526.84 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10654.81 | 30-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 9945.53 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 10689.94 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11721.79 | 04-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11094.17 | 13-FEB-12:20 | 0.00 |
March | 60.51 | 19-MAR-19:10 | 0.00 | 0.00 | 0.00 | 9730.79 | 13-MAR-12:20 | 0.00 |
April | 14360.53 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 10803.59 | 10-APR-13:20 | 0.00 |
May | 12278.46 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9723.21 | 12-MAY-12:39 | 0.00 |
June | 18882.18 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9715.74 | 14-JUN-12:00 | 0.00 |
July | 21606.63 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9520.85 | 21-JUL-12:39 | 0.00 |
August | 17780.81 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 7585.54 | 30-AUG-12:39 | 0.00 |
September | 14799.98 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9708.88 | 29-SEP-13:20 | 0.00 |
October | 2179.34 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9719.40 | 30-OCT-12:30 | 0.00 |
November | 60.45 | 05-NOV-19:10 | 0.00 | 0.00 | 0.00 | 9756.01 | 27-NOV-18:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 11792.64 | 23-DEC-18:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7585.54 | 0.00 | ||
Maximum of Months | 21606.63 | 0.00 | 0.00 | 0.00 | 11792.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 59961.02 | 08-JAN-16:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10479.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60903.39 | 09-FEB-17:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10314.42 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59662.30 | 01-MAR-18:19 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10146.86 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61737.17 | 30-APR-14:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 14151.15 | 0.00 |
May | 63249.41 | 22-MAY-14:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 11415.58 | 0.00 |
June | 68278.61 | 13-JUN-16:49 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 18859.51 | 0.00 |
July | 70564.92 | 21-JUL-12:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 16777.74 | 0.00 |
August | 66950.34 | 14-AUG-16:10 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 17243.77 | 0.00 |
September | 66601.86 | 13-SEP-14:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 14769.29 | 0.00 |
October | 57349.90 | 17-OCT-17:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 9961.90 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 59857.31 | 27-NOV-18:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10273.44 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61418.13 | 14-DEC-17:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10365.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 57349.90 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9945.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70564.92 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10479.70 | 0.00 | 0.00 | 18859.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 133627.48 | 10-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 114500.56 | 17-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 100139.48 | 15-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 63932.70 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 44373.04 | 06-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 14085.80 | 07-JUN-11:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3616.35 | 05-JUL-07:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3184.06 | 08-SEP-08:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 62026.49 | 23-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 103495.09 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 120614.59 | 31-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 133627.48 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 1.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 3.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
February | 2.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 1.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 3.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 12.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.08 | 118.17 | 21.06 | 118.17 | 21.04 |
February | 448.00 | 21.07 | 60.50 | 21.04 | 60.50 | 21.01 |
March | 497.00 | 21.07 | 66.33 | 21.05 | 66.33 | 21.03 |
April | 437.33 | 21.49 | 11.33 | 21.48 | 10.17 | 21.46 |
May | 436.33 | 21.67 | 25.83 | 21.77 | 2.67 | 21.76 |
June | 246.17 | 22.59 | 101.67 | 22.97 | 0.00 | 22.97 |
July | 123.67 | 22.90 | 248.17 | 23.56 | 0.00 | 23.56 |
August | 70.67 | 23.41 | 296.33 | 23.80 | 0.00 | 23.80 |
September | 179.50 | 22.90 | 137.17 | 23.33 | 0.00 | 23.33 |
October | 493.17 | 21.55 | 2.83 | 21.54 | 2.83 | 21.53 |
November | 480.00 | 21.09 | 34.83 | 21.08 | 34.83 | 21.07 |
December | 496.00 | 21.07 | 124.17 | 21.04 | 124.17 | 21.02 |
Annual Sum or Average | 4403.83 | 21.48 | 1227.33 | 21.78 | 419.67 | 21.72 |
Minimum of Months | 70.67 | 21.07 | 2.83 | 21.04 | 0.00 | 21.01 |
Maximum of Months | 497.00 | 23.41 | 296.33 | 23.80 | 124.17 | 23.80 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.59 | 13.83 | 21.58 | 13.83 | 21.57 |
February | 448.00 | 21.58 | 0.17 | 21.58 | 0.17 | 21.58 |
March | 497.00 | 21.66 | 0.17 | 21.66 | 0.17 | 21.66 |
April | 390.17 | 22.65 | 6.67 | 22.67 | 0.00 | 22.67 |
May | 367.33 | 22.81 | 42.17 | 22.92 | 0.00 | 22.92 |
June | 74.33 | 23.37 | 214.50 | 23.75 | 0.00 | 23.75 |
July | 22.83 | 23.62 | 295.00 | 23.87 | 0.00 | 23.87 |
August | 13.50 | 23.82 | 333.50 | 23.88 | 0.00 | 23.88 |
September | 46.33 | 23.58 | 204.67 | 23.83 | 0.00 | 23.83 |
October | 384.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
November | 480.00 | 21.75 | 2.67 | 21.75 | 2.67 | 21.75 |
December | 496.00 | 21.53 | 11.67 | 21.52 | 11.67 | 21.51 |
Annual Sum or Average | 3715.50 | 22.01 | 1125.00 | 22.43 | 28.50 | 22.42 |
Minimum of Months | 13.50 | 21.53 | 0.00 | 21.52 | 0.00 | 21.51 |
Maximum of Months | 497.00 | 23.82 | 333.50 | 23.88 | 13.83 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 40.50 | 21.11 | 40.50 | 21.11 |
February | 336.00 | 21.11 | 16.17 | 21.11 | 16.17 | 21.11 |
March | 379.00 | 21.13 | 14.17 | 21.13 | 14.17 | 21.13 |
April | 299.67 | 22.00 | 7.83 | 22.06 | 0.50 | 22.05 |
May | 289.50 | 22.23 | 38.83 | 22.43 | 0.00 | 22.43 |
June | 72.67 | 23.12 | 170.83 | 23.70 | 0.00 | 23.70 |
July | 28.83 | 23.37 | 239.67 | 23.92 | 0.00 | 23.92 |
August | 17.33 | 23.57 | 272.33 | 23.96 | 0.00 | 23.96 |
September | 48.17 | 23.23 | 157.50 | 23.78 | 0.00 | 23.78 |
October | 305.83 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
November | 360.00 | 21.16 | 8.33 | 21.16 | 8.33 | 21.15 |
December | 369.00 | 21.11 | 42.83 | 21.11 | 42.83 | 21.11 |
Annual Sum or Average | 2877.00 | 21.52 | 1009.00 | 22.07 | 122.50 | 22.04 |
Minimum of Months | 17.33 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.57 | 272.33 | 23.96 | 42.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 52.17 | 21.11 | 52.17 | 21.11 |
February | 336.00 | 21.11 | 23.17 | 21.11 | 23.17 | 21.11 |
March | 379.00 | 21.13 | 20.67 | 21.13 | 20.67 | 21.12 |
April | 306.17 | 21.91 | 6.33 | 21.96 | 1.00 | 21.95 |
May | 299.17 | 22.14 | 35.17 | 22.33 | 0.00 | 22.33 |
June | 81.17 | 23.07 | 154.83 | 23.64 | 0.00 | 23.64 |
July | 35.17 | 23.34 | 234.67 | 23.89 | 0.00 | 23.89 |
August | 18.67 | 23.56 | 270.50 | 23.95 | 0.00 | 23.95 |
September | 51.67 | 23.21 | 152.50 | 23.76 | 0.00 | 23.76 |
October | 312.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
November | 360.00 | 21.14 | 12.67 | 21.14 | 12.67 | 21.14 |
December | 369.00 | 21.11 | 53.00 | 21.11 | 53.00 | 21.11 |
Annual Sum or Average | 2919.00 | 21.51 | 1015.67 | 22.03 | 162.67 | 21.99 |
Minimum of Months | 18.67 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.56 | 270.50 | 23.95 | 53.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 69.17 | 21.11 | 69.17 | 21.11 |
February | 336.00 | 21.11 | 30.67 | 21.11 | 30.67 | 21.11 |
March | 379.00 | 21.12 | 31.33 | 21.12 | 31.33 | 21.12 |
April | 318.33 | 21.80 | 5.50 | 21.82 | 2.67 | 21.81 |
May | 308.17 | 21.98 | 26.17 | 22.13 | 0.00 | 22.13 |
June | 113.83 | 22.97 | 117.67 | 23.47 | 0.00 | 23.47 |
July | 51.00 | 23.24 | 219.33 | 23.84 | 0.00 | 23.84 |
August | 23.50 | 23.52 | 258.00 | 23.93 | 0.00 | 23.93 |
September | 65.00 | 23.15 | 138.17 | 23.69 | 0.00 | 23.69 |
October | 328.17 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
November | 360.00 | 21.13 | 18.00 | 21.13 | 18.00 | 21.13 |
December | 369.00 | 21.11 | 68.67 | 21.11 | 68.67 | 21.11 |
Annual Sum or Average | 3023.00 | 21.51 | 982.67 | 21.95 | 220.50 | 21.91 |
Minimum of Months | 23.50 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.52 | 258.00 | 23.93 | 69.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 115.33 | 21.11 | 115.33 | 21.11 |
February | 308.00 | 21.11 | 47.17 | 21.11 | 47.17 | 21.11 |
March | 348.00 | 21.11 | 52.83 | 21.11 | 52.83 | 21.11 |
April | 308.17 | 21.47 | 4.50 | 21.48 | 3.67 | 21.47 |
May | 303.83 | 21.58 | 7.67 | 21.63 | 0.00 | 21.63 |
June | 200.50 | 22.50 | 54.00 | 22.80 | 0.00 | 22.80 |
July | 91.00 | 22.82 | 162.00 | 23.52 | 0.00 | 23.52 |
August | 37.17 | 23.31 | 206.33 | 23.82 | 0.00 | 23.82 |
September | 129.50 | 22.87 | 87.50 | 23.29 | 0.00 | 23.29 |
October | 337.67 | 21.51 | 0.17 | 21.51 | 0.17 | 21.51 |
November | 330.00 | 21.11 | 29.67 | 21.11 | 29.67 | 21.11 |
December | 338.00 | 21.11 | 133.33 | 21.11 | 133.33 | 21.11 |
Annual Sum or Average | 3071.83 | 21.48 | 900.50 | 21.76 | 382.17 | 21.70 |
Minimum of Months | 37.17 | 21.11 | 0.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.31 | 206.33 | 23.82 | 133.33 | 23.82 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 117.50 | 21.11 | 117.50 | 21.11 |
February | 308.00 | 21.11 | 49.33 | 21.11 | 49.33 | 21.11 |
March | 348.00 | 21.11 | 54.50 | 21.11 | 54.50 | 21.11 |
April | 307.50 | 21.63 | 5.83 | 21.64 | 4.50 | 21.63 |
May | 295.50 | 21.74 | 5.00 | 21.78 | 0.00 | 21.78 |
June | 162.33 | 22.78 | 53.17 | 23.06 | 0.00 | 23.06 |
July | 74.50 | 23.14 | 151.33 | 23.67 | 0.00 | 23.67 |
August | 28.00 | 23.61 | 189.67 | 23.88 | 0.00 | 23.88 |
September | 96.83 | 23.22 | 84.83 | 23.55 | 0.00 | 23.55 |
October | 335.83 | 21.69 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 330.00 | 21.11 | 30.33 | 21.11 | 30.33 | 21.11 |
December | 338.00 | 21.11 | 131.83 | 21.11 | 131.83 | 21.11 |
Annual Sum or Average | 2964.50 | 21.53 | 873.50 | 21.79 | 388.17 | 21.73 |
Minimum of Months | 28.00 | 21.11 | 0.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.61 | 189.67 | 23.88 | 131.83 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 122.50 | 21.11 | 122.50 | 21.11 |
February | 308.00 | 21.11 | 54.00 | 21.11 | 54.00 | 21.11 |
March | 348.00 | 21.11 | 60.50 | 21.11 | 60.50 | 21.11 |
April | 308.50 | 21.62 | 7.00 | 21.62 | 5.67 | 21.61 |
May | 297.50 | 21.72 | 4.83 | 21.76 | 0.00 | 21.76 |
June | 170.50 | 22.77 | 48.00 | 23.02 | 0.00 | 23.02 |
July | 78.17 | 23.12 | 146.17 | 23.65 | 0.00 | 23.65 |
August | 30.67 | 23.60 | 184.83 | 23.88 | 0.00 | 23.88 |
September | 102.67 | 23.21 | 78.17 | 23.52 | 0.00 | 23.52 |
October | 336.83 | 21.67 | 0.33 | 21.67 | 0.33 | 21.67 |
November | 330.00 | 21.11 | 35.00 | 21.11 | 35.00 | 21.11 |
December | 338.00 | 21.11 | 141.00 | 21.11 | 141.00 | 21.11 |
Annual Sum or Average | 2988.83 | 21.53 | 882.33 | 21.77 | 419.00 | 21.71 |
Minimum of Months | 30.67 | 21.11 | 0.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.60 | 184.83 | 23.88 | 141.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 140.50 | 21.11 | 140.50 | 21.11 |
February | 308.00 | 21.11 | 74.33 | 21.11 | 74.33 | 21.11 |
March | 348.00 | 21.11 | 85.00 | 21.11 | 85.00 | 21.11 |
April | 310.17 | 21.55 | 11.33 | 21.54 | 10.50 | 21.53 |
May | 306.33 | 21.67 | 4.33 | 21.70 | 0.17 | 21.70 |
June | 207.83 | 22.69 | 35.67 | 22.87 | 0.00 | 22.87 |
July | 95.67 | 23.01 | 135.50 | 23.55 | 0.00 | 23.55 |
August | 41.50 | 23.53 | 172.17 | 23.85 | 0.00 | 23.85 |
September | 130.50 | 23.10 | 67.50 | 23.38 | 0.00 | 23.38 |
October | 340.00 | 21.59 | 1.67 | 21.59 | 1.67 | 21.58 |
November | 330.00 | 21.11 | 49.50 | 21.11 | 49.50 | 21.11 |
December | 338.00 | 21.11 | 171.67 | 21.11 | 171.67 | 21.11 |
Annual Sum or Average | 3096.00 | 21.54 | 949.17 | 21.73 | 533.33 | 21.66 |
Minimum of Months | 41.50 | 21.11 | 1.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.53 | 172.17 | 23.85 | 171.67 | 23.85 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 223.67 | 21.11 | 223.67 | 21.11 |
February | 308.00 | 21.11 | 192.17 | 21.11 | 192.17 | 21.11 |
March | 348.00 | 21.11 | 213.00 | 21.11 | 213.00 | 21.11 |
April | 312.17 | 21.48 | 32.50 | 21.46 | 31.83 | 21.43 |
May | 319.33 | 21.59 | 12.33 | 21.59 | 10.00 | 21.58 |
June | 244.33 | 22.43 | 26.50 | 22.58 | 0.00 | 22.58 |
July | 125.17 | 22.85 | 104.67 | 23.35 | 0.00 | 23.35 |
August | 66.67 | 23.32 | 132.50 | 23.72 | 0.00 | 23.72 |
September | 180.83 | 22.89 | 45.50 | 23.09 | 0.00 | 23.09 |
October | 340.00 | 21.45 | 20.17 | 21.43 | 20.17 | 21.41 |
November | 330.00 | 21.11 | 126.67 | 21.11 | 126.67 | 21.11 |
December | 338.00 | 21.11 | 300.00 | 21.11 | 300.00 | 21.11 |
Annual Sum or Average | 3252.50 | 21.54 | 1429.67 | 21.60 | 1117.50 | 21.50 |
Minimum of Months | 66.67 | 21.11 | 12.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.32 | 300.00 | 23.72 | 300.00 | 23.72 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.07806 | 32.39316 | -0.4705 | 9.84816 |
February | 448.00000 | 21.06954 | 33.39866 | -0.4556 | 9.50815 |
March | 497.00000 | 21.07445 | 33.49665 | -0.4475 | 9.34126 |
April | 479.00000 | 21.69872 | 33.55119 | -0.2134 | 7.24491 |
May | 496.00000 | 21.93296 | 39.50266 | -1.1953 | 37.05416 |
June | 481.00000 | 23.16945 | 45.73368 | -0.7114 | 17.24963 |
July | 495.00000 | 23.61611 | 46.10164 | -0.5378 | 11.99343 |
August | 497.00000 | 23.80601 | 45.98923 | -0.4754 | 10.07326 |
September | 479.00000 | 23.46802 | 43.99706 | -0.6208 | 14.16609 |
October | 496.00000 | 21.56545 | 42.55491 | -0.2082 | 6.69014 |
November | 480.00000 | 21.09269 | 37.68106 | -0.4035 | 8.53912 |
December | 496.00000 | 21.06653 | 31.51002 | -0.4994 | 10.36906 |
Annual Sum or Average | 5840.00000 | 22.05779 | 38.85520 | -0.5208 | 12.70925 |
Minimum of Months | 448.00000 | 21.06653 | 31.51002 | -1.1953 | 6.69014 |
Maximum of Months | 497.00000 | 23.80601 | 46.10164 | -0.2082 | 37.05416 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.59209 | 35.07954 | -0.3040 | 7.50474 |
February | 448.00000 | 21.57783 | 35.84428 | -0.2938 | 7.23493 |
March | 497.00000 | 21.65718 | 35.65206 | -0.2742 | 7.15907 |
April | 479.00000 | 22.87835 | 33.23404 | 0.05254 | 6.15482 |
May | 496.00000 | 23.08675 | 38.08204 | -0.8397 | 21.48682 |
June | 481.00000 | 23.78835 | 43.97200 | -0.5131 | 10.90793 |
July | 495.00000 | 23.86113 | 45.26072 | -0.4499 | 9.44465 |
August | 497.00000 | 23.87727 | 45.58778 | -0.4352 | 9.11577 |
September | 479.00000 | 23.85232 | 42.76486 | -0.4885 | 10.26479 |
October | 496.00000 | 22.76493 | 41.71995 | 0.06380 | 6.16313 |
November | 480.00000 | 21.75421 | 39.40488 | -0.2227 | 6.69272 |
December | 496.00000 | 21.52709 | 33.93249 | -0.3412 | 7.84942 |
Annual Sum or Average | 5840.00000 | 22.68947 | 39.23264 | -0.3381 | 9.18822 |
Minimum of Months | 448.00000 | 21.52709 | 33.23404 | -0.8397 | 6.15482 |
Maximum of Months | 497.00000 | 23.87727 | 45.58778 | 0.06380 | 21.48682 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11364 | 31.99841 | -0.4244 | 8.91655 |
February | 336.00000 | 21.11121 | 33.22868 | -0.4052 | 8.51088 |
March | 379.00000 | 21.13312 | 32.56958 | -0.3998 | 8.43933 |
April | 360.00000 | 22.32867 | 31.42458 | -0.0630 | 6.58821 |
May | 375.00000 | 22.60876 | 37.39131 | -0.9676 | 26.96050 |
June | 366.00000 | 23.74027 | 43.60045 | -0.5246 | 11.40643 |
July | 369.00000 | 23.89862 | 45.04392 | -0.4383 | 9.38939 |
August | 379.00000 | 23.94088 | 45.38860 | -0.4163 | 8.85312 |
September | 360.00000 | 23.82214 | 42.54272 | -0.4929 | 10.56165 |
October | 371.00000 | 22.17732 | 40.61902 | -0.0572 | 6.39690 |
November | 360.00000 | 21.15639 | 37.09390 | -0.3597 | 7.84234 |
December | 369.00000 | 21.10978 | 30.98848 | -0.4502 | 9.31749 |
Annual Sum or Average | 4395.00000 | 22.35342 | 37.69501 | -0.4179 | 10.30256 |
Minimum of Months | 336.00000 | 21.10978 | 30.98848 | -0.9676 | 6.39690 |
Maximum of Months | 379.00000 | 23.94088 | 45.38860 | -0.0572 | 26.96050 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11077 | 32.00450 | -0.4367 | 9.13890 |
February | 336.00000 | 21.11049 | 33.23006 | -0.4158 | 8.69464 |
March | 379.00000 | 21.12593 | 32.58260 | -0.4115 | 8.63417 |
April | 360.00000 | 22.21854 | 31.62446 | -0.0950 | 6.70962 |
May | 375.00000 | 22.49553 | 37.63716 | -1.0116 | 28.89013 |
June | 366.00000 | 23.70580 | 43.70531 | -0.5412 | 11.87106 |
July | 369.00000 | 23.88575 | 45.08976 | -0.4462 | 9.57937 |
August | 379.00000 | 23.93716 | 45.40876 | -0.4203 | 8.92573 |
September | 360.00000 | 23.80964 | 42.59716 | -0.5016 | 10.77380 |
October | 371.00000 | 22.08921 | 40.84724 | -0.0847 | 6.49182 |
November | 360.00000 | 21.14111 | 37.12981 | -0.3740 | 8.05252 |
December | 369.00000 | 21.10977 | 30.98817 | -0.4614 | 9.53376 |
Annual Sum or Average | 4395.00000 | 22.31983 | 37.77506 | -0.4346 | 10.64844 |
Minimum of Months | 336.00000 | 21.10977 | 30.98817 | -1.0116 | 6.49182 |
Maximum of Months | 379.00000 | 23.93716 | 45.40876 | -0.0847 | 28.89013 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10982 | 32.00685 | -0.4509 | 9.40721 |
February | 336.00000 | 21.10952 | 33.23246 | -0.4291 | 8.93319 |
March | 379.00000 | 21.11908 | 32.59574 | -0.4258 | 8.88441 |
April | 360.00000 | 22.04713 | 31.95219 | -0.1431 | 6.86810 |
May | 375.00000 | 22.31413 | 38.04256 | -1.0812 | 31.93917 |
June | 366.00000 | 23.59311 | 44.05030 | -0.5903 | 13.31052 |
July | 369.00000 | 23.84391 | 45.24517 | -0.4704 | 10.17120 |
August | 379.00000 | 23.92413 | 45.48429 | -0.4331 | 9.17276 |
September | 360.00000 | 23.76638 | 42.77058 | -0.5272 | 11.42903 |
October | 371.00000 | 21.94528 | 41.22352 | -0.1274 | 6.58605 |
November | 360.00000 | 21.12795 | 37.16230 | -0.3894 | 8.29112 |
December | 369.00000 | 21.10975 | 30.98885 | -0.4761 | 9.82708 |
Annual Sum or Average | 4395.00000 | 22.25878 | 37.93498 | -0.4634 | 11.28070 |
Minimum of Months | 336.00000 | 21.10952 | 30.98885 | -1.0812 | 6.58605 |
Maximum of Months | 379.00000 | 23.92413 | 45.48429 | -0.1274 | 31.93917 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10968 | 33.62150 | -0.4894 | 10.16403 |
February | 308.00000 | 21.10968 | 34.77104 | -0.4654 | 9.60293 |
March | 348.00000 | 21.10999 | 34.12780 | -0.4632 | 9.56747 |
April | 330.00000 | 21.63462 | 34.24574 | -0.2422 | 7.41144 |
May | 344.00000 | 21.83604 | 40.65707 | -1.2394 | 39.07214 |
June | 336.00000 | 23.02311 | 47.06683 | -0.7689 | 19.19001 |
July | 338.00000 | 23.58559 | 47.23358 | -0.5601 | 12.66115 |
August | 348.00000 | 23.82546 | 46.86071 | -0.4779 | 10.05607 |
September | 330.00000 | 23.44749 | 45.15651 | -0.6328 | 14.43154 |
October | 340.00000 | 21.53045 | 43.74521 | -0.2321 | 6.88365 |
November | 330.00000 | 21.10959 | 38.78680 | -0.4278 | 8.92520 |
December | 338.00000 | 21.10989 | 32.56114 | -0.5189 | 10.71117 |
Annual Sum or Average | 4030.00000 | 22.04334 | 39.94334 | -0.5448 | 13.28161 |
Minimum of Months | 308.00000 | 21.10959 | 32.56114 | -1.2394 | 6.88365 |
Maximum of Months | 348.00000 | 23.82546 | 47.23358 | -0.2321 | 39.07214 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10935 | 33.51988 | -0.4908 | 10.18793 |
February | 308.00000 | 21.10936 | 34.66440 | -0.4683 | 9.65768 |
March | 348.00000 | 21.11157 | 34.02611 | -0.4666 | 9.63341 |
April | 330.00000 | 21.79471 | 33.95929 | -0.2243 | 7.35755 |
May | 344.00000 | 22.04405 | 40.10098 | -1.2037 | 37.51164 |
June | 336.00000 | 23.32584 | 46.15758 | -0.7096 | 16.99486 |
July | 338.00000 | 23.73245 | 46.56281 | -0.5420 | 11.87713 |
August | 348.00000 | 23.88346 | 46.51498 | -0.4816 | 10.04062 |
September | 330.00000 | 23.67758 | 44.50371 | -0.5893 | 12.92913 |
October | 340.00000 | 21.71338 | 43.25969 | -0.2071 | 6.89216 |
November | 330.00000 | 21.11192 | 38.66686 | -0.4311 | 8.98389 |
December | 338.00000 | 21.10937 | 32.44801 | -0.5189 | 10.70805 |
Annual Sum or Average | 4030.00000 | 22.15128 | 39.57126 | -0.5294 | 12.78802 |
Minimum of Months | 308.00000 | 21.10935 | 32.44801 | -1.2037 | 6.89216 |
Maximum of Months | 348.00000 | 23.88346 | 46.56281 | -0.2071 | 37.51164 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10907 | 33.52036 | -0.4957 | 10.28837 |
February | 308.00000 | 21.10927 | 34.66471 | -0.4734 | 9.75905 |
March | 348.00000 | 21.11147 | 34.02615 | -0.4714 | 9.72847 |
April | 330.00000 | 21.77179 | 34.00007 | -0.2328 | 7.43211 |
May | 344.00000 | 22.01534 | 40.16654 | -1.2172 | 38.14239 |
June | 336.00000 | 23.29331 | 46.25963 | -0.7232 | 17.46024 |
July | 338.00000 | 23.71841 | 46.63755 | -0.5502 | 12.10936 |
August | 348.00000 | 23.87944 | 46.57153 | -0.4870 | 10.15686 |
September | 330.00000 | 23.66147 | 44.56919 | -0.5977 | 13.16714 |
October | 340.00000 | 21.68901 | 43.31333 | -0.2158 | 6.94241 |
November | 330.00000 | 21.11114 | 38.66878 | -0.4361 | 9.07360 |
December | 338.00000 | 21.10965 | 32.44773 | -0.5230 | 10.79778 |
Annual Sum or Average | 4030.00000 | 22.13926 | 39.60995 | -0.5369 | 12.97931 |
Minimum of Months | 308.00000 | 21.10907 | 32.44773 | -1.2172 | 6.94241 |
Maximum of Months | 348.00000 | 23.87944 | 46.63755 | -0.2158 | 38.14239 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10924 | 33.51987 | -0.5115 | 10.62653 |
February | 308.00000 | 21.10947 | 34.66472 | -0.4901 | 10.09974 |
March | 348.00000 | 21.11048 | 34.02783 | -0.4875 | 10.05428 |
April | 330.00000 | 21.69478 | 34.13748 | -0.2603 | 7.68103 |
May | 344.00000 | 21.90521 | 40.41495 | -1.2661 | 40.41592 |
June | 336.00000 | 23.13105 | 46.73779 | -0.7851 | 19.67980 |
July | 338.00000 | 23.64823 | 46.94452 | -0.5827 | 13.13233 |
August | 348.00000 | 23.85992 | 46.77413 | -0.5036 | 10.55146 |
September | 330.00000 | 23.56229 | 44.90084 | -0.6400 | 14.49266 |
October | 340.00000 | 21.58773 | 43.52954 | -0.2496 | 7.12128 |
November | 330.00000 | 21.10957 | 38.67338 | -0.4513 | 9.35940 |
December | 338.00000 | 21.10987 | 32.44786 | -0.5378 | 11.13017 |
Annual Sum or Average | 4030.00000 | 22.08562 | 39.77140 | -0.5654 | 13.75630 |
Minimum of Months | 308.00000 | 21.10924 | 32.44786 | -1.2661 | 7.12128 |
Maximum of Months | 348.00000 | 23.85992 | 46.94452 | -0.2496 | 40.41592 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 33.46302 | -0.5743 | 12.09453 |
February | 308.00000 | 21.11000 | 34.54539 | -0.5548 | 11.54133 |
March | 348.00000 | 21.10974 | 33.94118 | -0.5490 | 11.41580 |
April | 330.00000 | 21.61781 | 34.15034 | -0.3111 | 8.33845 |
May | 344.00000 | 21.74913 | 40.58780 | -1.3620 | 45.07238 |
June | 336.00000 | 22.82852 | 47.38362 | -0.9079 | 24.55627 |
July | 338.00000 | 23.51260 | 47.32426 | -0.6493 | 15.34881 |
August | 348.00000 | 23.79067 | 47.02208 | -0.5506 | 11.83462 |
September | 330.00000 | 23.34058 | 45.30785 | -0.7362 | 17.85874 |
October | 340.00000 | 21.44976 | 43.63171 | -0.3221 | 7.85727 |
November | 330.00000 | 21.10953 | 38.49843 | -0.5075 | 10.51660 |
December | 338.00000 | 21.11000 | 32.27085 | -0.5996 | 12.63365 |
Annual Sum or Average | 4030.00000 | 21.99367 | 39.88569 | -0.6370 | 15.82107 |
Minimum of Months | 308.00000 | 21.10953 | 32.27085 | -1.3620 | 7.85727 |
Maximum of Months | 348.00000 | 23.79067 | 47.38362 | -0.3111 | 45.07238 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.371826E+09 | 92923117.02 | 23.50 | 0.368641E+09 | 3184355.11 | 0.00 | 0.81 | 30-APR-16:03 | 0.00 | 01-APR-00:05 | 10709.17 | 30-APR-16:03 | 10709.17 | 30-APR-16:03 | 299.98 | 30-APR-19:50 | 2549.11 | 30-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.229784E+09 | 59948533.75 | 23.33 | 0.194905E+09 | 34878730.21 | 0.00 | 0.65 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8566.94 | 22-MAY-15:00 | 7771.98 | 22-MAY-15:00 | 862.87 | 22-MAY-14:00 | 2124.85 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.157979E+10 | 0.384562E+09 | 75.75 | 0.129988E+10 | 0.279907E+09 | 0.00 | 0.99 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 14559.44 | 13-JUN-17:00 | 13207.42 | 13-JUN-17:00 | 6271.15 | 25-JUN-18:00 | 3392.30 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.292237E+10 | 0.729972E+09 | 169.74 | 0.245989E+10 | 0.462484E+09 | 0.00 | 1.00 | 21-JUL-16:20 | 0.00 | 01-JUL-00:10 | 16376.40 | 23-JUL-07:03 | 15654.23 | 22-JUL-16:10 | 4218.38 | 23-JUL-07:03 | 3817.33 | 22-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.290558E+10 | 0.736104E+09 | 225.75 | 0.236758E+10 | 0.537995E+09 | 0.00 | 0.94 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 13078.57 | 14-AUG-17:00 | 13078.57 | 14-AUG-17:00 | 2618.42 | 17-AUG-14:00 | 3148.57 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.152138E+10 | 0.380416E+09 | 101.67 | 0.126755E+10 | 0.253828E+09 | 0.00 | 0.81 | 13-SEP-16:10 | 0.00 | 01-SEP-00:05 | 11144.74 | 13-SEP-16:10 | 9531.30 | 13-SEP-16:10 | 2549.04 | 12-SEP-14:00 | 2595.89 | 13-SEP-16:10 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.953072E+10 | 0.238393E+10 | 619.74 | 0.795844E+10 | 0.157228E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292237E+10 | 0.736104E+09 | 225.75 | 0.245989E+10 | 0.537995E+09 | 0.00 | 1.00 | 0.00 | 16376.40 | 15654.23 | 6271.15 | 3817.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 281703.26 | 69218.80 | 0.50 | 231455.17 | 50248.09 | 0.00 | 0.04 | 19-MAR-19:10 | 0.00 | 01-MAR-00:10 | 246.68 | 19-MAR-19:10 | 186.01 | 19-MAR-19:10 | 60.67 | 19-MAR-19:10 | 60.51 | 19-MAR-19:10 | 0.00 | 01-MAR-00:10 |
April | 0.253907E+09 | 54849794.13 | 26.61 | 0.253230E+09 | 677026.99 | 0.00 | 1.00 | 29-APR-18:01 | 0.00 | 01-APR-00:05 | 15989.73 | 30-APR-19:07 | 15989.73 | 30-APR-19:07 | 812.60 | 30-APR-19:40 | 3228.45 | 30-APR-19:07 | 0.00 | 01-APR-00:05 |
May | 0.163647E+09 | 36061950.78 | 27.07 | 0.150482E+09 | 13165663.16 | 0.00 | 1.00 | 21-MAY-17:01 | 0.00 | 01-MAY-00:10 | 15987.04 | 21-MAY-18:40 | 15800.77 | 21-MAY-17:01 | 1229.04 | 21-MAY-18:40 | 3136.92 | 21-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 0.953293E+09 | 0.202384E+09 | 79.10 | 0.823347E+09 | 0.129946E+09 | 0.00 | 1.00 | 12-JUN-20:02 | 0.00 | 01-JUN-00:10 | 17625.46 | 25-JUN-18:00 | 14453.79 | 25-JUN-17:02 | 7124.62 | 25-JUN-18:00 | 3444.70 | 25-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 0.153649E+10 | 0.331726E+09 | 136.11 | 0.136251E+10 | 0.173982E+09 | 0.00 | 1.00 | 09-JUL-17:02 | 0.00 | 01-JUL-00:10 | 16958.43 | 23-JUL-17:02 | 14806.33 | 22-JUL-20:32 | 5710.70 | 23-JUL-19:33 | 3375.29 | 22-JUL-20:38 | 0.00 | 01-JUL-00:10 |
August | 0.146251E+10 | 0.318765E+09 | 188.14 | 0.126365E+10 | 0.198853E+09 | 0.00 | 1.00 | 06-AUG-17:01 | 0.00 | 01-AUG-00:10 | 16480.27 | 13-AUG-17:02 | 15758.91 | 14-AUG-20:08 | 4604.80 | 19-AUG-18:35 | 3238.00 | 13-AUG-17:02 | 0.00 | 01-AUG-00:10 |
September | 0.869904E+09 | 0.189150E+09 | 104.24 | 0.759834E+09 | 0.110069E+09 | 0.00 | 1.00 | 10-SEP-17:02 | 0.00 | 01-SEP-00:05 | 16846.26 | 10-SEP-17:02 | 13866.01 | 24-SEP-17:08 | 5754.72 | 10-SEP-18:23 | 3303.78 | 10-SEP-17:02 | 0.00 | 01-SEP-00:05 |
October | 10476313.66 | 2467588.95 | 6.92 | 9896354.59 | 579959.07 | 0.00 | 0.38 | 04-OCT-20:10 | 0.00 | 01-OCT-00:10 | 2725.57 | 04-OCT-20:10 | 2707.21 | 04-OCT-20:10 | 271.01 | 17-OCT-20:20 | 609.08 | 04-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 463013.83 | 113972.95 | 1.33 | 410606.86 | 52406.97 | 0.00 | 0.04 | 05-NOV-19:10 | 0.00 | 01-NOV-00:10 | 246.41 | 05-NOV-19:10 | 229.36 | 05-NOV-19:10 | 32.67 | 08-NOV-21:50 | 60.45 | 05-NOV-19:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.525097E+10 | 0.113559E+10 | 570.02 | 0.462359E+10 | 0.627375E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.153649E+10 | 0.331726E+09 | 188.14 | 0.136251E+10 | 0.198853E+09 | 0.00 | 1.00 | 0.00 | 17625.46 | 15989.73 | 7124.62 | 3444.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.132054E+09 | 29167826.08 | 16.50 | 0.131728E+09 | 326178.89 | 0.00 | 0.77 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 6154.43 | 30-APR-15:00 | 6154.43 | 30-APR-15:00 | 83.23 | 28-APR-15:00 | 1293.79 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 93493021.10 | 21039616.67 | 17.67 | 85086137.13 | 8406883.97 | 0.00 | 0.67 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5370.05 | 22-MAY-15:00 | 5095.96 | 22-MAY-15:00 | 335.32 | 22-MAY-14:00 | 1155.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.748965E+09 | 0.160555E+09 | 70.58 | 0.655561E+09 | 93404615.80 | 0.00 | 0.92 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 8048.07 | 13-JUN-16:30 | 7468.91 | 13-JUN-17:00 | 1591.98 | 26-JUN-17:10 | 1671.39 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.110086E+10 | 0.240932E+09 | 122.46 | 0.993576E+09 | 0.107283E+09 | 0.00 | 1.00 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 14874.60 | 23-JUL-07:03 | 11797.50 | 23-JUL-07:03 | 3077.10 | 23-JUL-07:03 | 2906.53 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.112967E+10 | 0.249896E+09 | 167.17 | 0.981848E+09 | 0.147824E+09 | 0.00 | 0.88 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 7399.37 | 14-AUG-17:00 | 7399.37 | 14-AUG-17:00 | 1261.35 | 17-AUG-14:00 | 1578.80 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.712993E+09 | 0.156695E+09 | 94.83 | 0.631107E+09 | 81885898.97 | 0.00 | 0.75 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 | 6241.17 | 13-SEP-14:00 | 5505.19 | 13-SEP-14:00 | 1189.51 | 12-SEP-14:00 | 1288.17 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 |
October | 356950.81 | 87040.73 | 1.17 | 356705.70 | 245.12 | 0.00 | 0.06 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 361.94 | 07-OCT-15:00 | 361.94 | 07-OCT-15:00 | 0.40 | 02-OCT-14:20 | 87.94 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.391839E+10 | 0.858371E+09 | 490.38 | 0.347926E+10 | 0.439130E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112967E+10 | 0.249896E+09 | 167.17 | 0.993576E+09 | 0.147824E+09 | 0.00 | 1.00 | 0.00 | 14874.60 | 11797.50 | 3077.10 | 2906.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.125968E+09 | 27867294.49 | 16.00 | 0.125677E+09 | 291727.92 | 0.00 | 0.76 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 6059.72 | 30-APR-15:00 | 6059.72 | 30-APR-15:00 | 75.91 | 28-APR-15:00 | 1277.26 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 81863074.01 | 18471791.85 | 15.67 | 74902023.89 | 6961050.12 | 0.00 | 0.64 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5126.36 | 22-MAY-15:00 | 4862.80 | 22-MAY-15:00 | 316.95 | 22-MAY-14:00 | 1111.17 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.729399E+09 | 0.156562E+09 | 69.58 | 0.638104E+09 | 91294310.52 | 0.00 | 0.92 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7979.84 | 13-JUN-16:30 | 7405.65 | 13-JUN-17:00 | 1573.42 | 26-JUN-17:10 | 1660.10 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.107973E+10 | 0.236337E+09 | 121.29 | 0.974960E+09 | 0.104767E+09 | 0.00 | 1.00 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 | 15304.67 | 23-JUL-07:03 | 12132.72 | 23-JUL-07:03 | 3171.94 | 23-JUL-07:03 | 2996.80 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.110292E+10 | 0.244127E+09 | 163.50 | 0.958765E+09 | 0.144151E+09 | 0.00 | 0.88 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 7348.52 | 14-AUG-17:00 | 7348.52 | 14-AUG-17:00 | 1252.20 | 17-AUG-14:00 | 1569.78 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.688753E+09 | 0.151576E+09 | 91.67 | 0.609979E+09 | 78774094.03 | 0.00 | 0.75 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 | 6182.24 | 13-SEP-14:00 | 5452.83 | 13-SEP-14:00 | 1169.69 | 12-SEP-14:00 | 1277.89 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 |
October | 198048.60 | 48479.51 | 1.67 | 198048.60 | -0.0 | 0.00 | 0.04 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 238.95 | 07-OCT-15:00 | 238.95 | 07-OCT-15:00 | 0.00 | 01-OCT-15:10 | 58.34 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.380882E+10 | 0.834989E+09 | 479.38 | 0.338259E+10 | 0.426239E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110292E+10 | 0.244127E+09 | 163.50 | 0.974960E+09 | 0.144151E+09 | 0.00 | 1.00 | 0.00 | 15304.67 | 12132.72 | 3171.94 | 2996.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.110157E+09 | 24446426.60 | 14.75 | 0.109951E+09 | 205559.11 | 0.00 | 0.74 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5810.06 | 30-APR-15:00 | 5810.06 | 30-APR-15:00 | 57.56 | 28-APR-15:00 | 1232.86 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 65095299.61 | 14742353.81 | 12.33 | 60198791.38 | 4896508.23 | 0.00 | 0.60 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4731.48 | 22-MAY-15:00 | 4485.40 | 22-MAY-15:00 | 287.47 | 22-MAY-14:00 | 1037.43 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.674799E+09 | 0.145423E+09 | 61.25 | 0.590033E+09 | 84766036.74 | 0.00 | 0.90 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7756.70 | 13-JUN-16:40 | 7196.61 | 13-JUN-17:00 | 1495.32 | 26-JUN-17:10 | 1622.20 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.998815E+09 | 0.219121E+09 | 112.35 | 0.904826E+09 | 93989501.39 | 0.00 | 1.00 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 | 13255.36 | 23-JUL-07:03 | 10534.34 | 23-JUL-07:03 | 2721.01 | 23-JUL-07:03 | 2569.49 | 23-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.100550E+10 | 0.223018E+09 | 149.08 | 0.876080E+09 | 0.129423E+09 | 0.00 | 0.87 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 7180.45 | 14-AUG-17:00 | 7180.45 | 14-AUG-17:00 | 1208.95 | 17-AUG-14:00 | 1539.53 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.620492E+09 | 0.137086E+09 | 81.00 | 0.550550E+09 | 69941666.02 | 0.00 | 0.73 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 | 5974.71 | 13-SEP-14:00 | 5268.41 | 13-SEP-14:00 | 1103.74 | 12-SEP-14:00 | 1241.33 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 |
October | 9059.36 | 2241.62 | 0.33 | 9059.36 | -0.0 | 0.00 | 0.00 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 | 15.08 | 04-OCT-15:30 | 15.08 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 | 3.73 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.347487E+10 | 0.763838E+09 | 431.10 | 0.309165E+10 | 0.383222E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100550E+10 | 0.223018E+09 | 149.08 | 0.904826E+09 | 0.129423E+09 | 0.00 | 1.00 | 0.00 | 13255.36 | 10534.34 | 2721.01 | 2569.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.180222E+09 | 46142431.62 | 14.00 | 0.177768E+09 | 2453114.74 | 0.00 | 0.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 9277.27 | 30-APR-15:00 | 9277.27 | 30-APR-15:00 | 263.55 | 28-APR-15:00 | 2261.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.103990E+09 | 27282097.71 | 10.50 | 90122006.33 | 13867998.10 | 0.00 | 0.59 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 7523.35 | 22-MAY-15:00 | 6695.53 | 22-MAY-15:00 | 827.83 | 22-MAY-15:00 | 1897.13 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.110665E+10 | 0.274799E+09 | 57.75 | 0.919238E+09 | 0.187408E+09 | 0.00 | 0.91 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 12855.69 | 13-JUN-15:00 | 11266.43 | 13-JUN-17:00 | 2895.99 | 26-JUN-16:40 | 3024.75 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.188693E+10 | 0.475032E+09 | 123.25 | 0.160658E+10 | 0.280347E+09 | 0.00 | 1.00 | 22-JUL-14:10 | 0.00 | 01-JUL-00:10 | 19102.22 | 23-JUL-08:63 | 14937.68 | 22-JUL-15:00 | 4452.96 | 23-JUL-08:63 | 4069.94 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.214610E+10 | 0.544862E+09 | 168.25 | 0.175494E+10 | 0.391163E+09 | 0.00 | 0.86 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 11682.85 | 14-AUG-14:50 | 11424.79 | 14-AUG-17:00 | 2579.14 | 17-AUG-14:40 | 2820.17 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.114393E+10 | 0.288798E+09 | 80.50 | 0.964889E+09 | 0.179043E+09 | 0.00 | 0.78 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 | 10425.98 | 13-SEP-14:20 | 8750.88 | 13-SEP-14:20 | 2304.51 | 12-SEP-14:10 | 2450.22 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 |
October | 641648.86 | 179333.42 | 0.50 | 641648.86 | -0.0 | 0.00 | 0.06 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 630.40 | 07-OCT-15:00 | 630.40 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 175.46 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.656846E+10 | 0.165709E+10 | 454.75 | 0.551418E+10 | 0.105428E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.214610E+10 | 0.544862E+09 | 168.25 | 0.175494E+10 | 0.391163E+09 | 0.00 | 1.00 | 0.00 | 19102.22 | 14937.68 | 4452.96 | 4069.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.230615E+09 | 51735654.22 | 33.50 | 0.230593E+09 | 22808.77 | 0.00 | 0.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5452.45 | 30-APR-15:00 | 5452.45 | 30-APR-15:00 | 9.81 | 28-APR-15:20 | 1158.42 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.224384E+09 | 51483208.04 | 47.17 | 0.199964E+09 | 24420026.38 | 0.00 | 0.60 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4442.92 | 22-MAY-15:00 | 4100.26 | 22-MAY-15:00 | 471.63 | 23-MAY-14:10 | 973.89 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.109930E+10 | 0.242162E+09 | 134.67 | 0.973664E+09 | 0.125636E+09 | 0.00 | 0.88 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7137.52 | 13-JUN-15:00 | 6440.78 | 13-JUN-17:00 | 1307.57 | 26-JUN-17:00 | 1486.48 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.233265E+10 | 0.515221E+09 | 261.53 | 0.205531E+10 | 0.277339E+09 | 0.00 | 1.00 | 22-JUL-14:40 | 0.00 | 01-JUL-00:10 | 10489.58 | 23-JUL-08:63 | 10473.57 | 23-JUL-08:63 | 1068.91 | 24-JUL-14:50 | 1997.53 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.296775E+10 | 0.655263E+09 | 332.42 | 0.260136E+10 | 0.366395E+09 | 0.00 | 0.84 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6595.72 | 14-AUG-14:50 | 6548.93 | 14-AUG-17:00 | 1125.40 | 17-AUG-13:00 | 1412.60 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.150650E+10 | 0.333085E+09 | 202.75 | 0.134753E+10 | 0.158968E+09 | 0.00 | 0.77 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 | 6077.60 | 13-SEP-14:40 | 5379.24 | 13-SEP-14:20 | 1047.95 | 12-SEP-14:10 | 1244.09 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 |
October | 27348554.07 | 6390906.46 | 9.17 | 27348554.07 | 0.00 | 0.00 | 0.35 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2281.24 | 07-OCT-15:00 | 2281.24 | 07-OCT-15:00 | 0.00 | 07-OCT-15:30 | 514.74 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.838855E+10 | 0.185534E+10 | 1021.19 | 0.743577E+10 | 0.952781E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.296775E+10 | 0.655263E+09 | 332.42 | 0.260136E+10 | 0.366395E+09 | 0.00 | 1.00 | 0.00 | 10489.58 | 10473.57 | 1307.57 | 1997.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.220635E+09 | 49550372.65 | 32.50 | 0.220611E+09 | 23675.19 | 0.00 | 0.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5364.27 | 30-APR-15:00 | 5364.27 | 30-APR-15:00 | 9.92 | 28-APR-15:20 | 1141.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.209486E+09 | 48107453.01 | 43.00 | 0.186427E+09 | 23059282.72 | 0.00 | 0.59 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4352.59 | 22-MAY-15:00 | 4015.65 | 22-MAY-15:00 | 459.05 | 23-MAY-14:10 | 956.06 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.105343E+10 | 0.232181E+09 | 126.00 | 0.932048E+09 | 0.121386E+09 | 0.00 | 0.87 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7043.99 | 13-JUN-15:00 | 6361.46 | 13-JUN-17:00 | 1291.15 | 26-JUN-17:00 | 1470.20 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.225565E+10 | 0.498636E+09 | 255.94 | 0.198661E+10 | 0.269035E+09 | 0.00 | 1.00 | 22-JUL-14:50 | 0.00 | 01-JUL-00:10 | 9938.59 | 23-JUL-08:63 | 9920.71 | 23-JUL-08:63 | 1055.83 | 24-JUL-14:50 | 1883.77 | 23-JUL-08:63 | 0.00 | 01-JUL-00:10 |
August | 0.287301E+10 | 0.635027E+09 | 328.42 | 0.251640E+10 | 0.356605E+09 | 0.00 | 0.84 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6514.41 | 14-AUG-14:50 | 6478.85 | 14-AUG-17:00 | 1114.75 | 17-AUG-14:50 | 1398.71 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.144626E+10 | 0.319914E+09 | 196.08 | 0.129256E+10 | 0.153705E+09 | 0.00 | 0.77 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 | 6000.16 | 13-SEP-14:40 | 5307.47 | 13-SEP-14:20 | 1035.95 | 12-SEP-14:10 | 1229.68 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 |
October | 24499794.91 | 5726170.10 | 7.67 | 24499794.91 | 0.00 | 0.00 | 0.34 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2202.50 | 07-OCT-15:00 | 2202.50 | 07-OCT-15:00 | 0.00 | 07-OCT-14:30 | 498.17 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.808297E+10 | 0.178914E+10 | 989.61 | 0.715916E+10 | 0.923814E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.287301E+10 | 0.635027E+09 | 328.42 | 0.251640E+10 | 0.356605E+09 | 0.00 | 1.00 | 0.00 | 9938.59 | 9920.71 | 1291.15 | 1883.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.190184E+09 | 42849053.44 | 29.58 | 0.190161E+09 | 22965.04 | 0.00 | 0.71 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5120.71 | 30-APR-15:00 | 5120.71 | 30-APR-15:00 | 9.58 | 28-APR-15:20 | 1096.62 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.167058E+09 | 38467095.34 | 33.17 | 0.148207E+09 | 18851563.67 | 0.00 | 0.57 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4088.06 | 22-MAY-15:00 | 3768.17 | 22-MAY-15:00 | 425.32 | 23-MAY-14:10 | 904.57 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.914660E+09 | 0.201906E+09 | 110.33 | 0.806463E+09 | 0.108197E+09 | 0.00 | 0.86 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6809.40 | 13-JUN-15:00 | 6162.28 | 13-JUN-17:00 | 1243.76 | 26-JUN-17:00 | 1430.95 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.201375E+10 | 0.446186E+09 | 236.97 | 0.177218E+10 | 0.241570E+09 | 0.00 | 1.00 | 22-JUL-14:50 | 0.00 | 01-JUL-00:10 | 8145.10 | 23-JUL-08:63 | 8145.10 | 23-JUL-08:63 | 1024.13 | 24-JUL-14:50 | 1717.36 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.257226E+10 | 0.570433E+09 | 311.17 | 0.224794E+10 | 0.324320E+09 | 0.00 | 0.83 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6294.29 | 14-AUG-15:00 | 6286.72 | 14-AUG-17:00 | 1089.45 | 17-AUG-14:50 | 1362.42 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.123846E+10 | 0.274290E+09 | 169.83 | 0.110308E+10 | 0.135375E+09 | 0.00 | 0.76 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 | 5804.39 | 13-SEP-14:40 | 5126.72 | 13-SEP-14:30 | 1002.91 | 12-SEP-14:10 | 1194.37 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 |
October | 15700562.40 | 3681513.57 | 5.50 | 15700562.40 | -0.0 | 0.00 | 0.29 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1881.38 | 07-OCT-15:00 | 1881.38 | 07-OCT-15:00 | 0.00 | 07-OCT-15:40 | 430.42 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.711207E+10 | 0.157781E+10 | 896.56 | 0.628374E+10 | 0.828337E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.257226E+10 | 0.570433E+09 | 311.17 | 0.224794E+10 | 0.324320E+09 | 0.00 | 1.00 | 0.00 | 8145.10 | 8145.10 | 1243.76 | 1717.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.170715E+09 | 38596596.58 | 26.83 | 0.170706E+09 | 8945.67 | 0.00 | 0.67 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4902.59 | 30-APR-15:00 | 4902.59 | 30-APR-15:00 | 6.46 | 28-APR-15:20 | 1062.50 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.137926E+09 | 31724768.36 | 23.17 | 0.122782E+09 | 15144020.30 | 0.00 | 0.53 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3910.49 | 22-MAY-15:00 | 3603.33 | 22-MAY-15:00 | 401.21 | 23-MAY-14:10 | 873.70 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.822151E+09 | 0.181748E+09 | 92.83 | 0.724863E+09 | 97288783.83 | 0.00 | 0.83 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6734.63 | 13-JUN-15:00 | 6037.44 | 13-JUN-17:00 | 1166.29 | 26-JUN-17:00 | 1417.04 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.174961E+10 | 0.388032E+09 | 199.89 | 0.154895E+10 | 0.200663E+09 | 0.00 | 1.00 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 | 8254.04 | 22-JUL-15:00 | 8253.97 | 22-JUL-15:00 | 984.74 | 24-JUL-13:00 | 1744.62 | 22-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.222174E+10 | 0.494760E+09 | 269.17 | 0.194387E+10 | 0.277869E+09 | 0.00 | 0.79 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6138.62 | 14-AUG-14:50 | 6097.65 | 14-AUG-17:00 | 1094.52 | 17-AUG-13:00 | 1336.65 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.103421E+10 | 0.229679E+09 | 134.83 | 0.919927E+09 | 0.114288E+09 | 0.00 | 0.72 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 | 5645.33 | 13-SEP-14:20 | 4995.01 | 13-SEP-14:20 | 975.51 | 12-SEP-14:10 | 1173.29 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 |
October | 9074722.72 | 2155675.07 | 3.33 | 9074722.72 | 0.00 | 0.00 | 0.22 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1410.26 | 07-OCT-15:00 | 1410.26 | 07-OCT-15:00 | 0.00 | 07-OCT-15:20 | 329.19 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.614543E+10 | 0.136670E+10 | 750.06 | 0.544017E+10 | 0.705261E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.222174E+10 | 0.494760E+09 | 269.17 | 0.194387E+10 | 0.277869E+09 | 0.00 | 1.00 | 0.00 | 8254.04 | 8253.97 | 1166.29 | 1744.62 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.43 | 69.92 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.81 | 67.30 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.31 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.24 | 47.86 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.69 | 41.90 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.27 | 34.21 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.57 | 32.50 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.27 | 35.81 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.64 | 45.00 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.37 | 54.18 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.44 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.35 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.06 | 52.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.31 | 32.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.64 | 79.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.43 | 69.92 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.81 | 67.30 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.31 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.24 | 47.86 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.69 | 41.90 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.27 | 34.21 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.57 | 32.50 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.27 | 35.81 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.64 | 45.00 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.37 | 54.18 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.44 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.35 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.06 | 52.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.31 | 32.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.64 | 79.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.43 | 69.92 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.81 | 67.30 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.31 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.24 | 47.86 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.69 | 41.90 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.27 | 34.21 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.57 | 32.50 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.27 | 35.81 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.64 | 45.00 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.37 | 54.18 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.44 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.35 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.06 | 52.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.31 | 32.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.64 | 79.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.43 | 69.92 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.81 | 67.30 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.31 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.24 | 47.86 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.69 | 41.90 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.27 | 34.21 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.57 | 32.50 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.27 | 35.81 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.64 | 45.00 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.37 | 54.18 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.44 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.35 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.06 | 52.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.31 | 32.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.64 | 79.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.79 | 56.83 | 30.96 | 90.84 | 83.29 | 0.00 | 0.00 | 0.00 |
February | 107.22 | 65.43 | 41.79 | 114.18 | 80.06 | 0.00 | 0.00 | 0.00 |
March | 66.29 | 19.30 | 46.99 | 58.30 | 66.99 | 0.00 | 0.00 | 0.00 |
April | 137.66 | 62.22 | 75.44 | 165.09 | 57.06 | 0.00 | 0.00 | 0.00 |
May | 113.86 | 37.07 | 76.79 | 127.28 | 49.83 | 0.00 | 0.00 | 0.00 |
June | 104.89 | 25.39 | 79.50 | 119.52 | 40.72 | 0.00 | 0.00 | 0.00 |
July | 113.64 | 35.59 | 78.05 | 137.82 | 38.70 | 0.00 | 0.00 | 0.00 |
August | 133.17 | 59.90 | 73.26 | 169.85 | 42.72 | 0.00 | 0.00 | 0.00 |
September | 157.37 | 92.19 | 65.18 | 199.18 | 53.66 | 0.00 | 0.00 | 0.00 |
October | 108.12 | 63.19 | 44.93 | 124.37 | 64.54 | 0.00 | 0.00 | 0.00 |
November | 76.66 | 46.63 | 30.02 | 80.02 | 76.57 | 0.00 | 0.00 | 0.00 |
December | 60.76 | 38.93 | 21.83 | 60.68 | 94.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 105.46 | 50.03 | 55.43 | 120.43 | 62.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.76 | 19.30 | 21.83 | 58.30 | 38.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.37 | 92.19 | 79.50 | 199.18 | 94.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.79 | 56.83 | 30.96 | 90.84 | 83.29 | 0.00 | 0.00 | 0.00 |
February | 107.22 | 65.43 | 41.79 | 114.18 | 80.06 | 0.00 | 0.00 | 0.00 |
March | 66.29 | 19.30 | 46.99 | 58.30 | 66.99 | 0.00 | 0.00 | 0.00 |
April | 137.66 | 62.22 | 75.44 | 165.09 | 57.06 | 0.00 | 0.00 | 0.00 |
May | 113.86 | 37.07 | 76.79 | 127.28 | 49.83 | 0.00 | 0.00 | 0.00 |
June | 104.89 | 25.39 | 79.50 | 119.52 | 40.72 | 0.00 | 0.00 | 0.00 |
July | 113.64 | 35.59 | 78.05 | 137.82 | 38.70 | 0.00 | 0.00 | 0.00 |
August | 133.17 | 59.90 | 73.26 | 169.85 | 42.72 | 0.00 | 0.00 | 0.00 |
September | 157.37 | 92.19 | 65.18 | 199.18 | 53.66 | 0.00 | 0.00 | 0.00 |
October | 108.12 | 63.19 | 44.93 | 124.37 | 64.54 | 0.00 | 0.00 | 0.00 |
November | 76.66 | 46.63 | 30.02 | 80.02 | 76.57 | 0.00 | 0.00 | 0.00 |
December | 60.76 | 38.93 | 21.83 | 60.68 | 94.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 105.46 | 50.03 | 55.43 | 120.43 | 62.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.76 | 19.30 | 21.83 | 58.30 | 38.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.37 | 92.19 | 79.50 | 199.18 | 94.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.59 | 73.93 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 93.81 | 71.36 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.24 | 60.12 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 134.80 | 52.32 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.03 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.28 | 36.50 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.45 | 33.89 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.62 | 36.84 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.40 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 101.56 | 59.33 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 65.65 | 68.65 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 49.79 | 83.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 98.71 | 55.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.24 | 33.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.40 | 83.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.59 | 73.93 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 93.81 | 71.36 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.24 | 60.12 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 134.80 | 52.32 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.03 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.28 | 36.50 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.45 | 33.89 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.62 | 36.84 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.40 | 47.01 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 101.56 | 59.33 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 65.65 | 68.65 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 49.79 | 83.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 98.71 | 55.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.24 | 33.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.40 | 83.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.79 | 56.83 | 30.96 | 89.84 | 88.05 | 0.00 | 0.00 | 0.00 |
February | 107.22 | 65.43 | 41.79 | 112.99 | 84.86 | 0.00 | 0.00 | 0.00 |
March | 66.29 | 19.30 | 46.99 | 57.02 | 71.62 | 0.00 | 0.00 | 0.00 |
April | 137.66 | 62.22 | 75.44 | 162.21 | 62.34 | 0.00 | 0.00 | 0.00 |
May | 113.86 | 37.07 | 76.79 | 124.14 | 54.78 | 0.00 | 0.00 | 0.00 |
June | 104.89 | 25.39 | 79.50 | 117.16 | 43.41 | 0.00 | 0.00 | 0.00 |
July | 113.64 | 35.59 | 78.05 | 136.51 | 40.34 | 0.00 | 0.00 | 0.00 |
August | 133.17 | 59.90 | 73.26 | 169.10 | 43.94 | 0.00 | 0.00 | 0.00 |
September | 157.37 | 92.19 | 65.18 | 197.73 | 56.03 | 0.00 | 0.00 | 0.00 |
October | 108.12 | 63.19 | 44.93 | 122.23 | 70.62 | 0.00 | 0.00 | 0.00 |
November | 76.66 | 46.63 | 30.02 | 79.08 | 81.66 | 0.00 | 0.00 | 0.00 |
December | 60.76 | 38.93 | 21.83 | 60.01 | 99.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 105.46 | 50.03 | 55.43 | 118.83 | 66.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.76 | 19.30 | 21.83 | 57.02 | 40.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.37 | 92.19 | 79.50 | 197.73 | 99.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.85 | 71.95 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.04 | 69.48 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.49 | 58.38 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 135.19 | 51.33 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.39 | 45.35 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.23 | 36.97 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.31 | 34.63 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.55 | 37.71 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.42 | 47.59 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 101.85 | 57.97 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 65.90 | 66.46 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 49.95 | 81.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 98.87 | 54.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.49 | 34.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.42 | 81.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.85 | 71.95 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.04 | 69.48 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.49 | 58.38 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 135.19 | 51.33 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.39 | 45.35 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.23 | 36.97 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.31 | 34.63 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.55 | 37.71 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.42 | 47.59 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 101.85 | 57.97 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 65.90 | 66.46 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 49.95 | 81.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 98.87 | 54.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.49 | 34.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.42 | 81.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 89.66 | 85.24 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 112.66 | 82.19 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 57.01 | 69.18 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 161.78 | 60.82 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 123.89 | 53.59 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 116.46 | 43.72 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 135.61 | 40.98 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.08 | 44.71 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 196.68 | 56.39 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 121.91 | 68.64 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 78.95 | 78.64 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 59.88 | 96.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 118.38 | 64.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 57.01 | 40.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 196.68 | 96.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.99 | 71.06 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.19 | 68.67 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.65 | 57.61 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 135.58 | 50.45 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.80 | 44.55 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.42 | 36.61 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.42 | 34.40 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.59 | 37.56 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.51 | 47.29 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 102.10 | 57.00 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.03 | 65.53 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.04 | 80.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.05 | 54.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.65 | 34.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.51 | 80.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 74.99 | 71.06 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.19 | 68.67 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.65 | 57.61 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 135.58 | 50.45 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 103.80 | 44.55 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.42 | 36.61 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.42 | 34.40 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.59 | 37.56 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.51 | 47.29 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 102.10 | 57.00 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.03 | 65.53 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.04 | 80.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.05 | 54.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.65 | 34.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.51 | 80.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 89.84 | 84.17 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 112.83 | 81.22 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 57.21 | 68.26 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 162.25 | 59.78 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 124.38 | 52.65 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 116.69 | 43.29 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 135.73 | 40.71 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.14 | 44.52 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 196.79 | 56.04 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 122.21 | 67.49 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.12 | 77.54 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 59.99 | 95.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 118.59 | 64.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 57.21 | 40.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 196.79 | 95.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.15 | 70.31 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.36 | 67.98 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.85 | 56.96 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 136.16 | 49.45 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 104.45 | 43.57 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.95 | 35.89 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.71 | 33.91 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.75 | 37.20 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.77 | 46.72 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 102.50 | 55.89 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.18 | 64.78 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.16 | 79.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.36 | 53.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.85 | 33.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.77 | 79.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.15 | 70.31 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.36 | 67.98 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 47.85 | 56.96 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 136.16 | 49.45 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 104.45 | 43.57 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 97.95 | 35.89 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 113.71 | 33.91 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.75 | 37.20 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 164.77 | 46.72 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 102.50 | 55.89 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.18 | 64.78 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.16 | 79.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.36 | 53.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 47.85 | 33.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 164.77 | 79.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.03 | 83.28 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.05 | 80.41 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 57.45 | 67.49 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 162.94 | 58.60 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 125.15 | 51.49 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 117.32 | 42.44 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 136.09 | 40.13 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.33 | 44.10 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 197.10 | 55.37 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 122.68 | 66.18 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.29 | 76.65 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.13 | 94.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 118.96 | 63.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 57.45 | 40.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 197.10 | 94.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.63 | 68.37 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.95 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.44 | 55.26 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.32 | 47.41 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.84 | 41.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.43 | 33.99 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.51 | 32.59 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.09 | 36.17 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.57 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.46 | 53.53 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.59 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.51 | 77.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.14 | 51.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.44 | 32.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.57 | 77.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.63 | 68.37 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.95 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.44 | 55.26 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.32 | 47.41 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.84 | 41.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.43 | 33.99 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.51 | 32.59 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.09 | 36.17 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.57 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.46 | 53.53 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.59 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.51 | 77.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.14 | 51.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.44 | 32.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.57 | 77.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.63 | 68.37 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.95 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.44 | 55.26 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.32 | 47.41 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.84 | 41.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.43 | 33.99 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.51 | 32.59 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.09 | 36.17 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.57 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.46 | 53.53 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.59 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.51 | 77.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.14 | 51.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.44 | 32.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.57 | 77.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.63 | 68.37 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.95 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.44 | 55.26 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.32 | 47.41 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.84 | 41.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.43 | 33.99 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.51 | 32.59 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.09 | 36.17 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.57 | 45.10 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.46 | 53.53 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.59 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.51 | 77.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.14 | 51.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.44 | 32.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.57 | 77.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.60 | 80.99 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.74 | 78.20 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 58.14 | 65.48 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 164.30 | 56.19 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 126.77 | 49.11 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 119.06 | 40.22 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 137.02 | 38.58 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.71 | 42.90 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 198.03 | 53.46 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 123.81 | 63.40 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.77 | 74.46 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.54 | 91.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 119.87 | 61.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 58.14 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 198.03 | 91.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.60 | 80.99 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.74 | 78.20 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 58.14 | 65.48 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 164.30 | 56.19 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 126.77 | 49.11 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 119.06 | 40.22 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 137.02 | 38.58 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.71 | 42.90 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 198.03 | 53.46 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 123.81 | 63.40 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.77 | 74.46 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.54 | 91.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 119.87 | 61.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 58.14 | 38.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 198.03 | 91.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.47 | 68.50 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.76 | 66.24 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.27 | 55.30 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 136.96 | 47.49 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.37 | 41.73 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 98.85 | 34.27 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.17 | 32.66 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.90 | 36.12 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.09 | 45.38 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.09 | 53.78 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.45 | 63.05 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.39 | 77.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.84 | 51.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.27 | 32.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.09 | 77.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.47 | 68.50 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.76 | 66.24 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.27 | 55.30 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 136.96 | 47.49 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.37 | 41.73 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 98.85 | 34.27 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.17 | 32.66 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.90 | 36.12 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.09 | 45.38 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.09 | 53.78 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.45 | 63.05 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.39 | 77.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.84 | 51.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.27 | 32.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.09 | 77.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.43 | 81.12 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.54 | 78.34 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 57.97 | 65.52 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 163.92 | 56.28 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 126.25 | 49.32 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 118.41 | 40.53 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 136.65 | 38.66 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.52 | 42.83 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 197.49 | 53.78 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 123.40 | 63.67 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.63 | 74.58 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.42 | 91.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 119.55 | 61.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 57.97 | 38.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 197.49 | 91.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.53 | 68.24 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.83 | 65.98 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.35 | 55.07 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.09 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.52 | 41.51 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.01 | 34.09 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.29 | 32.51 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.98 | 35.98 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.18 | 45.22 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.19 | 53.52 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.51 | 62.79 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.43 | 77.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.93 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.35 | 32.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.18 | 77.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.53 | 68.24 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 94.83 | 65.98 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.35 | 55.07 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.09 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 105.52 | 41.51 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.01 | 34.09 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.29 | 32.51 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 140.98 | 35.98 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.18 | 45.22 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.19 | 53.52 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.51 | 62.79 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.43 | 77.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 99.93 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.35 | 32.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.18 | 77.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.50 | 80.81 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.63 | 78.03 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 58.06 | 65.24 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 164.07 | 56.02 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 126.44 | 49.06 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 118.60 | 40.31 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 136.79 | 38.48 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.62 | 42.67 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 197.60 | 53.59 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 123.52 | 63.36 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.69 | 74.27 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.46 | 91.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 119.66 | 61.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 58.06 | 38.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 197.60 | 91.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.73 | 67.25 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 95.09 | 64.96 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.60 | 54.16 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.49 | 46.43 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 106.08 | 40.60 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.70 | 33.23 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.74 | 31.89 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.24 | 35.47 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.60 | 44.41 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.57 | 52.47 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.68 | 61.83 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.56 | 76.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.28 | 50.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.60 | 31.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.60 | 76.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 75.73 | 67.25 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 95.09 | 64.96 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 48.60 | 54.16 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 137.49 | 46.43 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 106.08 | 40.60 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 99.70 | 33.23 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 114.74 | 31.89 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.24 | 35.47 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 165.60 | 44.41 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 103.57 | 52.47 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 66.68 | 61.83 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 50.56 | 76.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 100.28 | 50.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 48.60 | 31.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 165.60 | 76.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 90.74 | 79.63 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 113.93 | 76.81 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 58.36 | 64.15 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 164.55 | 55.02 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 127.11 | 47.99 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 119.42 | 39.31 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 137.32 | 37.75 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 168.93 | 42.06 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 198.11 | 52.64 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 123.97 | 62.13 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 79.90 | 73.14 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 60.62 | 90.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 120.08 | 60.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 58.36 | 37.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 198.11 | 90.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 76.47 | 63.46 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 96.01 | 60.99 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 49.52 | 50.68 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 138.38 | 43.55 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 107.35 | 37.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 101.20 | 30.59 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 115.78 | 29.75 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.99 | 33.42 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 166.60 | 41.73 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 104.45 | 49.21 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 67.29 | 58.31 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 51.05 | 72.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 101.20 | 47.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 49.52 | 29.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 166.60 | 72.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.03 | 47.27 | 25.75 | 76.47 | 63.46 | 0.00 | 0.00 | 0.00 |
February | 89.19 | 54.43 | 34.77 | 96.01 | 60.99 | 0.00 | 0.00 | 0.00 |
March | 55.14 | 16.06 | 39.09 | 49.52 | 50.68 | 0.00 | 0.00 | 0.00 |
April | 114.51 | 51.76 | 62.75 | 138.38 | 43.55 | 0.00 | 0.00 | 0.00 |
May | 94.71 | 30.84 | 63.88 | 107.35 | 37.53 | 0.00 | 0.00 | 0.00 |
June | 87.25 | 21.12 | 66.13 | 101.20 | 30.59 | 0.00 | 0.00 | 0.00 |
July | 94.53 | 29.60 | 64.93 | 115.78 | 29.75 | 0.00 | 0.00 | 0.00 |
August | 110.77 | 49.83 | 60.94 | 141.99 | 33.42 | 0.00 | 0.00 | 0.00 |
September | 130.90 | 76.69 | 54.22 | 166.60 | 41.73 | 0.00 | 0.00 | 0.00 |
October | 89.94 | 52.56 | 37.37 | 104.45 | 49.21 | 0.00 | 0.00 | 0.00 |
November | 63.76 | 38.79 | 24.98 | 67.29 | 58.31 | 0.00 | 0.00 | 0.00 |
December | 50.54 | 32.38 | 18.16 | 51.05 | 72.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.72 | 41.61 | 46.11 | 101.20 | 47.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.54 | 16.06 | 18.16 | 49.52 | 29.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.90 | 76.69 | 66.13 | 166.60 | 72.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.31 | 56.52 | 30.79 | 91.63 | 75.13 | 0.00 | 0.00 | 0.00 |
February | 106.64 | 65.07 | 41.57 | 115.05 | 72.10 | 0.00 | 0.00 | 0.00 |
March | 65.93 | 19.20 | 46.73 | 59.48 | 60.03 | 0.00 | 0.00 | 0.00 |
April | 136.91 | 61.88 | 75.03 | 165.62 | 51.61 | 0.00 | 0.00 | 0.00 |
May | 113.24 | 36.87 | 76.37 | 128.63 | 44.38 | 0.00 | 0.00 | 0.00 |
June | 104.31 | 25.25 | 79.06 | 121.21 | 36.20 | 0.00 | 0.00 | 0.00 |
July | 113.02 | 35.39 | 77.63 | 138.57 | 35.22 | 0.00 | 0.00 | 0.00 |
August | 132.44 | 59.58 | 72.86 | 169.83 | 39.64 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 91.68 | 64.82 | 199.30 | 49.48 | 0.00 | 0.00 | 0.00 |
October | 107.53 | 62.84 | 44.68 | 125.02 | 58.27 | 0.00 | 0.00 | 0.00 |
November | 76.24 | 46.38 | 29.86 | 80.63 | 68.96 | 0.00 | 0.00 | 0.00 |
December | 60.42 | 38.71 | 21.71 | 61.22 | 85.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.88 | 49.75 | 55.13 | 121.18 | 56.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.42 | 19.20 | 21.71 | 59.48 | 35.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 156.51 | 91.68 | 79.06 | 199.30 | 85.36 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202026E+09 | 0.187271E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229353E+09 | 0.162803E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129395E+09 | 0.150551E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355716E+09 | 0.124046E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283080E+09 | 0.112216E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257318E+09 | 88674412.72 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306855E+09 | 87036368.03 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378371E+09 | 95901446.25 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429327E+09 | 0.116634E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276871E+09 | 0.145103E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172203E+09 | 0.166750E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134862E+09 | 0.212166E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315538E+10 | 0.164915E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129395E+09 | 87036368.03 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429327E+09 | 0.212166E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202026E+09 | 0.187271E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229353E+09 | 0.162803E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129395E+09 | 0.150551E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355716E+09 | 0.124046E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283080E+09 | 0.112216E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257318E+09 | 88674412.72 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306855E+09 | 87036368.03 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378371E+09 | 95901446.25 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429327E+09 | 0.116634E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276871E+09 | 0.145103E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172203E+09 | 0.166750E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134862E+09 | 0.212166E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315538E+10 | 0.164915E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129395E+09 | 87036368.03 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429327E+09 | 0.212166E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202026E+09 | 0.187271E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229353E+09 | 0.162803E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129395E+09 | 0.150551E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355716E+09 | 0.124046E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283080E+09 | 0.112216E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257318E+09 | 88674412.72 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306855E+09 | 87036368.03 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378371E+09 | 95901446.25 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429327E+09 | 0.116634E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276871E+09 | 0.145103E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172203E+09 | 0.166750E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134862E+09 | 0.212166E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315538E+10 | 0.164915E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129395E+09 | 87036368.03 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429327E+09 | 0.212166E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202026E+09 | 0.187271E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229353E+09 | 0.162803E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129395E+09 | 0.150551E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355716E+09 | 0.124046E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283080E+09 | 0.112216E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257318E+09 | 88674412.72 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306855E+09 | 87036368.03 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378371E+09 | 95901446.25 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429327E+09 | 0.116634E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276871E+09 | 0.145103E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172203E+09 | 0.166750E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134862E+09 | 0.212166E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315538E+10 | 0.164915E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129395E+09 | 87036368.03 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429327E+09 | 0.212166E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235143E+09 | 0.152218E+09 | 82925329.35 | 0.243318E+09 | 0.223095E+09 |
February | 0.259392E+09 | 0.158285E+09 | 0.101108E+09 | 0.276226E+09 | 0.193684E+09 |
March | 0.177556E+09 | 51696371.72 | 0.125860E+09 | 0.156161E+09 | 0.179414E+09 |
April | 0.356816E+09 | 0.161277E+09 | 0.195539E+09 | 0.427923E+09 | 0.147898E+09 |
May | 0.304957E+09 | 99284155.48 | 0.205673E+09 | 0.340915E+09 | 0.133469E+09 |
June | 0.271869E+09 | 65808007.20 | 0.206060E+09 | 0.309784E+09 | 0.105545E+09 |
July | 0.304383E+09 | 95321004.02 | 0.209062E+09 | 0.369145E+09 | 0.103658E+09 |
August | 0.356670E+09 | 0.160444E+09 | 0.196227E+09 | 0.454917E+09 | 0.114418E+09 |
September | 0.407895E+09 | 0.238952E+09 | 0.168943E+09 | 0.516285E+09 | 0.139080E+09 |
October | 0.289582E+09 | 0.169248E+09 | 0.120334E+09 | 0.333122E+09 | 0.172860E+09 |
November | 0.198690E+09 | 0.120868E+09 | 77821974.54 | 0.207408E+09 | 0.198458E+09 |
December | 0.162730E+09 | 0.104262E+09 | 58468028.78 | 0.162522E+09 | 0.252125E+09 |
Annual Sum or Average | 0.332568E+10 | 0.157766E+10 | 0.174802E+10 | 0.379773E+10 | 0.196370E+10 |
Minimum of Months | 0.162730E+09 | 51696371.72 | 58468028.78 | 0.156161E+09 | 0.103658E+09 |
Maximum of Months | 0.407895E+09 | 0.238952E+09 | 0.209062E+09 | 0.516285E+09 | 0.252125E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235143E+09 | 0.152218E+09 | 82925329.35 | 0.243318E+09 | 0.223095E+09 |
February | 0.259392E+09 | 0.158285E+09 | 0.101108E+09 | 0.276226E+09 | 0.193684E+09 |
March | 0.177556E+09 | 51696371.72 | 0.125860E+09 | 0.156161E+09 | 0.179414E+09 |
April | 0.356816E+09 | 0.161277E+09 | 0.195539E+09 | 0.427923E+09 | 0.147898E+09 |
May | 0.304957E+09 | 99284155.48 | 0.205673E+09 | 0.340915E+09 | 0.133469E+09 |
June | 0.271869E+09 | 65808007.20 | 0.206060E+09 | 0.309784E+09 | 0.105545E+09 |
July | 0.304383E+09 | 95321004.02 | 0.209062E+09 | 0.369145E+09 | 0.103658E+09 |
August | 0.356670E+09 | 0.160444E+09 | 0.196227E+09 | 0.454917E+09 | 0.114418E+09 |
September | 0.407895E+09 | 0.238952E+09 | 0.168943E+09 | 0.516285E+09 | 0.139080E+09 |
October | 0.289582E+09 | 0.169248E+09 | 0.120334E+09 | 0.333122E+09 | 0.172860E+09 |
November | 0.198690E+09 | 0.120868E+09 | 77821974.54 | 0.207408E+09 | 0.198458E+09 |
December | 0.162730E+09 | 0.104262E+09 | 58468028.78 | 0.162522E+09 | 0.252125E+09 |
Annual Sum or Average | 0.332568E+10 | 0.157766E+10 | 0.174802E+10 | 0.379773E+10 | 0.196370E+10 |
Minimum of Months | 0.162730E+09 | 51696371.72 | 58468028.78 | 0.156161E+09 | 0.103658E+09 |
Maximum of Months | 0.407895E+09 | 0.238952E+09 | 0.209062E+09 | 0.516285E+09 | 0.252125E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.199778E+09 | 0.198015E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.226933E+09 | 0.172628E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.126522E+09 | 0.161021E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.349392E+09 | 0.135618E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.275962E+09 | 0.123505E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252148E+09 | 94616129.11 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303861E+09 | 90778326.87 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376648E+09 | 98684419.53 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426117E+09 | 0.121846E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.272027E+09 | 0.158900E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.170152E+09 | 0.177930E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.133354E+09 | 0.224308E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.311289E+10 | 0.175785E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.126522E+09 | 90778326.87 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426117E+09 | 0.224308E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.199778E+09 | 0.198015E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.226933E+09 | 0.172628E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.126522E+09 | 0.161021E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.349392E+09 | 0.135618E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.275962E+09 | 0.123505E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252148E+09 | 94616129.11 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303861E+09 | 90778326.87 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376648E+09 | 98684419.53 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426117E+09 | 0.121846E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.272027E+09 | 0.158900E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.170152E+09 | 0.177930E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.133354E+09 | 0.224308E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.311289E+10 | 0.175785E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.126522E+09 | 90778326.87 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426117E+09 | 0.224308E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235143E+09 | 0.152218E+09 | 82925329.35 | 0.240633E+09 | 0.235839E+09 |
February | 0.259392E+09 | 0.158285E+09 | 0.101108E+09 | 0.273345E+09 | 0.205284E+09 |
March | 0.177556E+09 | 51696371.72 | 0.125860E+09 | 0.152722E+09 | 0.191827E+09 |
April | 0.356816E+09 | 0.161277E+09 | 0.195539E+09 | 0.420443E+09 | 0.161582E+09 |
May | 0.304957E+09 | 99284155.48 | 0.205673E+09 | 0.332499E+09 | 0.146726E+09 |
June | 0.271869E+09 | 65808007.20 | 0.206060E+09 | 0.303681E+09 | 0.112527E+09 |
July | 0.304383E+09 | 95321004.02 | 0.209062E+09 | 0.365630E+09 | 0.108047E+09 |
August | 0.356670E+09 | 0.160444E+09 | 0.196227E+09 | 0.452910E+09 | 0.117692E+09 |
September | 0.407895E+09 | 0.238952E+09 | 0.168943E+09 | 0.512529E+09 | 0.145221E+09 |
October | 0.289582E+09 | 0.169248E+09 | 0.120334E+09 | 0.327389E+09 | 0.189149E+09 |
November | 0.198690E+09 | 0.120868E+09 | 77821974.54 | 0.204974E+09 | 0.211651E+09 |
December | 0.162730E+09 | 0.104262E+09 | 58468028.78 | 0.160724E+09 | 0.266467E+09 |
Annual Sum or Average | 0.332568E+10 | 0.157766E+10 | 0.174802E+10 | 0.374748E+10 | 0.209201E+10 |
Minimum of Months | 0.162730E+09 | 51696371.72 | 58468028.78 | 0.152722E+09 | 0.108047E+09 |
Maximum of Months | 0.407895E+09 | 0.238952E+09 | 0.209062E+09 | 0.512529E+09 | 0.266467E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.200466E+09 | 0.192724E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.227501E+09 | 0.168093E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.127189E+09 | 0.156359E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.350402E+09 | 0.133040E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.276926E+09 | 0.121464E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252026E+09 | 95836967.82 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303501E+09 | 92765052.77 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376437E+09 | 0.101010E+09 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426175E+09 | 0.123359E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.272803E+09 | 0.155258E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.170811E+09 | 0.172267E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.133795E+09 | 0.218732E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.311803E+10 | 0.173091E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.127189E+09 | 92765052.77 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426175E+09 | 0.218732E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.200466E+09 | 0.192724E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.227501E+09 | 0.168093E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.127189E+09 | 0.156359E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.350402E+09 | 0.133040E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.276926E+09 | 0.121464E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252026E+09 | 95836967.82 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303501E+09 | 92765052.77 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376437E+09 | 0.101010E+09 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426175E+09 | 0.123359E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.272803E+09 | 0.155258E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.170811E+09 | 0.172267E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.133795E+09 | 0.218732E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.311803E+10 | 0.173091E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.127189E+09 | 92765052.77 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426175E+09 | 0.218732E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.240150E+09 | 0.228302E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.272541E+09 | 0.198827E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.152694E+09 | 0.185280E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.419343E+09 | 0.157651E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.331822E+09 | 0.143530E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.301876E+09 | 0.113320E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.363208E+09 | 0.109756E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.450188E+09 | 0.119747E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.509794E+09 | 0.146174E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.326519E+09 | 0.183833E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.204646E+09 | 0.203840E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.160381E+09 | 0.258459E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.373316E+10 | 0.204872E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.152694E+09 | 0.109756E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.509794E+09 | 0.258459E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.200852E+09 | 0.190318E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.227853E+09 | 0.166124E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.127624E+09 | 0.154303E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.351415E+09 | 0.130768E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.278027E+09 | 0.119330E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252515E+09 | 94899736.83 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303773E+09 | 92148036.42 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376565E+09 | 0.100587E+09 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426414E+09 | 0.122576E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.273469E+09 | 0.152671E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.171161E+09 | 0.169856E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134040E+09 | 0.216219E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.312371E+10 | 0.170980E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.127624E+09 | 92148036.42 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426414E+09 | 0.216219E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.200852E+09 | 0.190318E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.227853E+09 | 0.166124E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.127624E+09 | 0.154303E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.351415E+09 | 0.130768E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.278027E+09 | 0.119330E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.252515E+09 | 94899736.83 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.303773E+09 | 92148036.42 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376565E+09 | 0.100587E+09 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.426414E+09 | 0.122576E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.273469E+09 | 0.152671E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.171161E+09 | 0.169856E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134040E+09 | 0.216219E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.312371E+10 | 0.170980E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.127624E+09 | 92148036.42 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.426414E+09 | 0.216219E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.240617E+09 | 0.225438E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.272968E+09 | 0.196489E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.153219E+09 | 0.182833E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.420553E+09 | 0.154957E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.333138E+09 | 0.141014E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.302462E+09 | 0.112213E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.363535E+09 | 0.109029E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.450344E+09 | 0.119248E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.510082E+09 | 0.145249E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.327316E+09 | 0.180769E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.205068E+09 | 0.200977E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.160677E+09 | 0.255475E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.373998E+10 | 0.202369E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.153219E+09 | 0.109029E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.510082E+09 | 0.255475E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.201277E+09 | 0.188324E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.228274E+09 | 0.164469E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.128160E+09 | 0.152554E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.352917E+09 | 0.128177E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.279746E+09 | 0.116703E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.253879E+09 | 93018582.87 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.304573E+09 | 90827009.15 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376981E+09 | 99627630.80 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.427072E+09 | 0.121102E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.274529E+09 | 0.149701E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.171534E+09 | 0.167920E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134339E+09 | 0.213927E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.313328E+10 | 0.168635E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.128160E+09 | 90827009.15 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.427072E+09 | 0.213927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.201277E+09 | 0.188324E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.228274E+09 | 0.164469E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.128160E+09 | 0.152554E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.352917E+09 | 0.128177E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.279746E+09 | 0.116703E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.253879E+09 | 93018582.87 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.304573E+09 | 90827009.15 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.376981E+09 | 99627630.80 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.427072E+09 | 0.121102E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.274529E+09 | 0.149701E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.171534E+09 | 0.167920E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134339E+09 | 0.213927E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.313328E+10 | 0.168635E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.128160E+09 | 90827009.15 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.427072E+09 | 0.213927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.241132E+09 | 0.223066E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.273480E+09 | 0.194526E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.153867E+09 | 0.180754E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.422344E+09 | 0.151891E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.335190E+09 | 0.137922E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.304093E+09 | 0.110001E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.364496E+09 | 0.107475E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.450846E+09 | 0.118119E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.510872E+09 | 0.143510E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.328581E+09 | 0.177254E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.205519E+09 | 0.198680E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.161040E+09 | 0.252754E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.375146E+10 | 0.199595E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.153867E+09 | 0.107475E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.510872E+09 | 0.252754E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202571E+09 | 0.183122E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229706E+09 | 0.159910E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129733E+09 | 0.148015E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355941E+09 | 0.122881E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283469E+09 | 0.111241E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257730E+09 | 88096030.12 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306716E+09 | 87283893.05 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377888E+09 | 96888803.39 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429163E+09 | 0.116892E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277116E+09 | 0.143371E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172597E+09 | 0.163107E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135295E+09 | 0.207320E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315793E+10 | 0.162813E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129733E+09 | 87283893.05 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429163E+09 | 0.207320E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202571E+09 | 0.183122E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229706E+09 | 0.159910E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129733E+09 | 0.148015E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355941E+09 | 0.122881E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283469E+09 | 0.111241E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257730E+09 | 88096030.12 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306716E+09 | 87283893.05 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377888E+09 | 96888803.39 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429163E+09 | 0.116892E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277116E+09 | 0.143371E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172597E+09 | 0.163107E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135295E+09 | 0.207320E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315793E+10 | 0.162813E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129733E+09 | 87283893.05 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429163E+09 | 0.207320E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202571E+09 | 0.183122E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229706E+09 | 0.159910E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129733E+09 | 0.148015E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355941E+09 | 0.122881E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283469E+09 | 0.111241E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257730E+09 | 88096030.12 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306716E+09 | 87283893.05 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377888E+09 | 96888803.39 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429163E+09 | 0.116892E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277116E+09 | 0.143371E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172597E+09 | 0.163107E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135295E+09 | 0.207320E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315793E+10 | 0.162813E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129733E+09 | 87283893.05 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429163E+09 | 0.207320E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202571E+09 | 0.183122E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229706E+09 | 0.159910E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129733E+09 | 0.148015E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355941E+09 | 0.122881E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.283469E+09 | 0.111241E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.257730E+09 | 88096030.12 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306716E+09 | 87283893.05 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377888E+09 | 96888803.39 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429163E+09 | 0.116892E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277116E+09 | 0.143371E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172597E+09 | 0.163107E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135295E+09 | 0.207320E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315793E+10 | 0.162813E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129733E+09 | 87283893.05 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429163E+09 | 0.207320E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.242660E+09 | 0.216917E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.275156E+09 | 0.189171E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.155734E+09 | 0.175386E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.425878E+09 | 0.145653E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.339533E+09 | 0.131538E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.308601E+09 | 0.104242E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.366988E+09 | 0.103335E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.451879E+09 | 0.114910E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.513289E+09 | 0.138575E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.331612E+09 | 0.169810E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.206763E+09 | 0.193011E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.162163E+09 | 0.244998E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.378026E+10 | 0.192754E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.155734E+09 | 0.103335E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.513289E+09 | 0.244998E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.242660E+09 | 0.216917E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.275156E+09 | 0.189171E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.155734E+09 | 0.175386E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.425878E+09 | 0.145653E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.339533E+09 | 0.131538E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.308601E+09 | 0.104242E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.366988E+09 | 0.103335E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.451879E+09 | 0.114910E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.513289E+09 | 0.138575E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.331612E+09 | 0.169810E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.206763E+09 | 0.193011E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.162163E+09 | 0.244998E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.378026E+10 | 0.192754E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.155734E+09 | 0.103335E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.513289E+09 | 0.244998E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202144E+09 | 0.183461E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229243E+09 | 0.160257E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129290E+09 | 0.148127E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355011E+09 | 0.123106E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.282215E+09 | 0.111775E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.256224E+09 | 88831066.32 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.305806E+09 | 87488227.94 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377383E+09 | 96750463.14 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.427903E+09 | 0.117624E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276125E+09 | 0.144038E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172249E+09 | 0.163418E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134972E+09 | 0.208235E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.314856E+10 | 0.163311E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129290E+09 | 87488227.94 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.427903E+09 | 0.208235E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202144E+09 | 0.183461E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229243E+09 | 0.160257E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129290E+09 | 0.148127E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355011E+09 | 0.123106E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.282215E+09 | 0.111775E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.256224E+09 | 88831066.32 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.305806E+09 | 87488227.94 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377383E+09 | 96750463.14 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.427903E+09 | 0.117624E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276125E+09 | 0.144038E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172249E+09 | 0.163418E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.134972E+09 | 0.208235E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.314856E+10 | 0.163311E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129290E+09 | 87488227.94 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.427903E+09 | 0.208235E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.242200E+09 | 0.217266E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.274667E+09 | 0.189516E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.155258E+09 | 0.175481E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.424874E+09 | 0.145882E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.338160E+09 | 0.132109E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.306916E+09 | 0.105062E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.366004E+09 | 0.103537E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.451368E+09 | 0.114720E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.511898E+09 | 0.139395E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.330510E+09 | 0.170541E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.206395E+09 | 0.193315E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.161818E+09 | 0.245983E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.377007E+10 | 0.193281E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.155258E+09 | 0.103537E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.511898E+09 | 0.245983E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202301E+09 | 0.182774E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229421E+09 | 0.159621E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129488E+09 | 0.147499E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355334E+09 | 0.122536E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.282628E+09 | 0.111181E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.256641E+09 | 88350730.31 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306116E+09 | 87085510.26 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377595E+09 | 96380277.67 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.428139E+09 | 0.117209E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276389E+09 | 0.143342E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172388E+09 | 0.162742E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135066E+09 | 0.207572E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315151E+10 | 0.162629E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129488E+09 | 87085510.26 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.428139E+09 | 0.207572E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202301E+09 | 0.182774E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.229421E+09 | 0.159621E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.129488E+09 | 0.147499E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.355334E+09 | 0.122536E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.282628E+09 | 0.111181E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.256641E+09 | 88350730.31 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.306116E+09 | 87085510.26 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.377595E+09 | 96380277.67 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.428139E+09 | 0.117209E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.276389E+09 | 0.143342E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172388E+09 | 0.162742E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135066E+09 | 0.207572E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.315151E+10 | 0.162629E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.129488E+09 | 87085510.26 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.428139E+09 | 0.207572E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.242392E+09 | 0.216447E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.274882E+09 | 0.188759E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.155498E+09 | 0.174733E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.425261E+09 | 0.145204E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.338655E+09 | 0.131409E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.307415E+09 | 0.104495E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.366376E+09 | 0.103062E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.451626E+09 | 0.114283E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.512182E+09 | 0.138905E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.330826E+09 | 0.169716E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.206563E+09 | 0.192511E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.161931E+09 | 0.245195E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.377361E+10 | 0.192472E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.155498E+09 | 0.103062E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.512182E+09 | 0.245195E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202833E+09 | 0.180113E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.230031E+09 | 0.157148E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.130159E+09 | 0.145052E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.356386E+09 | 0.120347E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.284126E+09 | 0.108750E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.258422E+09 | 86131883.15 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.307311E+09 | 85416928.32 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378294E+09 | 95003641.66 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429241E+09 | 0.115122E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277410E+09 | 0.140541E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172839E+09 | 0.160274E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135418E+09 | 0.204792E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.316247E+10 | 0.159869E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.130159E+09 | 85416928.32 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429241E+09 | 0.204792E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.202833E+09 | 0.180113E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.230031E+09 | 0.157148E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.130159E+09 | 0.145052E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.356386E+09 | 0.120347E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.284126E+09 | 0.108750E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.258422E+09 | 86131883.15 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.307311E+09 | 85416928.32 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.378294E+09 | 95003641.66 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.429241E+09 | 0.115122E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.277410E+09 | 0.140541E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.172839E+09 | 0.160274E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.135418E+09 | 0.204792E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.316247E+10 | 0.159869E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.130159E+09 | 85416928.32 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.429241E+09 | 0.204792E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.243037E+09 | 0.213284E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.275620E+09 | 0.185825E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.156310E+09 | 0.171826E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.426524E+09 | 0.142614E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.340446E+09 | 0.128548E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.309535E+09 | 0.101882E+09 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.367804E+09 | 0.101100E+09 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.452466E+09 | 0.112663E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.513497E+09 | 0.136445E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.332046E+09 | 0.166402E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.207108E+09 | 0.189581E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.162357E+09 | 0.241897E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.378675E+10 | 0.189207E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.156310E+09 | 0.101100E+09 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.513497E+09 | 0.241897E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.204804E+09 | 0.169969E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.232268E+09 | 0.147542E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.132627E+09 | 0.135754E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.358687E+09 | 0.112893E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.287535E+09 | 0.100528E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.262320E+09 | 79298253.31 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.310108E+09 | 79670138.23 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.380293E+09 | 89499057.86 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.431834E+09 | 0.108161E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.279754E+09 | 0.131813E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.174407E+09 | 0.151141E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.136743E+09 | 0.193605E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.319138E+10 | 0.149987E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.132627E+09 | 79298253.31 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.431834E+09 | 0.193605E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195602E+09 | 0.126621E+09 | 68980623.73 | 0.204804E+09 | 0.169969E+09 |
February | 0.215773E+09 | 0.131668E+09 | 84105289.35 | 0.232268E+09 | 0.147542E+09 |
March | 0.147698E+09 | 43003120.92 | 0.104695E+09 | 0.132627E+09 | 0.135754E+09 |
April | 0.296814E+09 | 0.134156E+09 | 0.162657E+09 | 0.358687E+09 | 0.112893E+09 |
May | 0.253676E+09 | 82588553.16 | 0.171087E+09 | 0.287535E+09 | 0.100528E+09 |
June | 0.226151E+09 | 54741746.80 | 0.171409E+09 | 0.262320E+09 | 79298253.31 |
July | 0.253198E+09 | 79291844.40 | 0.173906E+09 | 0.310108E+09 | 79670138.23 |
August | 0.296693E+09 | 0.133463E+09 | 0.163229E+09 | 0.380293E+09 | 89499057.86 |
September | 0.339303E+09 | 0.198770E+09 | 0.140534E+09 | 0.431834E+09 | 0.108161E+09 |
October | 0.240886E+09 | 0.140787E+09 | 0.100099E+09 | 0.279754E+09 | 0.131813E+09 |
November | 0.165279E+09 | 0.100543E+09 | 64735447.97 | 0.174407E+09 | 0.151141E+09 |
December | 0.135365E+09 | 86729101.68 | 48636057.59 | 0.136743E+09 | 0.193605E+09 |
Annual Sum or Average | 0.276644E+10 | 0.131236E+10 | 0.145408E+10 | 0.319138E+10 | 0.149987E+10 |
Minimum of Months | 0.135365E+09 | 43003120.92 | 48636057.59 | 0.132627E+09 | 79298253.31 |
Maximum of Months | 0.339303E+09 | 0.198770E+09 | 0.173906E+09 | 0.431834E+09 | 0.193605E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233858E+09 | 0.151386E+09 | 82472185.48 | 0.245429E+09 | 0.201216E+09 |
February | 0.257975E+09 | 0.157420E+09 | 0.100555E+09 | 0.278333E+09 | 0.174432E+09 |
March | 0.176586E+09 | 51413877.89 | 0.125172E+09 | 0.159306E+09 | 0.160774E+09 |
April | 0.354866E+09 | 0.160395E+09 | 0.194471E+09 | 0.429298E+09 | 0.133783E+09 |
May | 0.303291E+09 | 98741619.11 | 0.204549E+09 | 0.344535E+09 | 0.118872E+09 |
June | 0.270383E+09 | 65448400.60 | 0.204934E+09 | 0.314182E+09 | 93840761.11 |
July | 0.302720E+09 | 94800124.22 | 0.207920E+09 | 0.371146E+09 | 94342795.10 |
August | 0.354721E+09 | 0.159567E+09 | 0.195154E+09 | 0.454861E+09 | 0.106178E+09 |
September | 0.405666E+09 | 0.237646E+09 | 0.168020E+09 | 0.516590E+09 | 0.128240E+09 |
October | 0.287999E+09 | 0.168323E+09 | 0.119677E+09 | 0.334863E+09 | 0.156069E+09 |
November | 0.197605E+09 | 0.120208E+09 | 77396717.84 | 0.209004E+09 | 0.178748E+09 |
December | 0.161841E+09 | 0.103692E+09 | 58148531.36 | 0.163963E+09 | 0.228635E+09 |
Annual Sum or Average | 0.330751E+10 | 0.156904E+10 | 0.173847E+10 | 0.382151E+10 | 0.177513E+10 |
Minimum of Months | 0.161841E+09 | 51413877.89 | 58148531.36 | 0.159306E+09 | 93840761.11 |
Maximum of Months | 0.405666E+09 | 0.237646E+09 | 0.207920E+09 | 0.516590E+09 | 0.228635E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 483.40 | 446.26 | 467.70 | 302.76 | 164.94 | 0.00 | 0.00 |
February | 607.58 | 429.31 | 571.21 | 348.56 | 222.65 | 0.00 | 0.00 |
March | 309.85 | 358.81 | 353.16 | 102.82 | 250.34 | 0.00 | 0.00 |
April | 879.13 | 305.55 | 733.37 | 331.47 | 401.89 | 0.00 | 0.00 |
May | 677.32 | 267.25 | 606.56 | 197.48 | 409.09 | 0.00 | 0.00 |
June | 636.13 | 218.28 | 558.77 | 135.26 | 423.52 | 0.00 | 0.00 |
July | 733.91 | 207.38 | 605.42 | 189.59 | 415.83 | 0.00 | 0.00 |
August | 904.76 | 228.66 | 709.42 | 319.12 | 390.30 | 0.00 | 0.00 |
September | 1060.91 | 287.31 | 838.35 | 491.12 | 347.23 | 0.00 | 0.00 |
October | 662.23 | 345.78 | 575.98 | 336.63 | 239.35 | 0.00 | 0.00 |
November | 425.78 | 410.46 | 408.37 | 248.42 | 159.95 | 0.00 | 0.00 |
December | 322.76 | 505.12 | 323.67 | 207.38 | 116.29 | 0.00 | 0.00 |
Annual Sum or Average | 641.08 | 333.71 | 561.81 | 266.51 | 295.29 | 0.00 | 0.00 |
Minimum of Months | 309.85 | 207.38 | 323.67 | 102.82 | 116.29 | 0.00 | 0.00 |
Maximum of Months | 1060.91 | 505.12 | 838.35 | 491.12 | 423.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.02 | 235.91 | 233.85 | 151.38 | 82.47 | 0.00 | 0.00 |
February | 300.60 | 227.57 | 285.61 | 174.28 | 111.33 | 0.00 | 0.00 |
March | 151.50 | 191.86 | 176.58 | 51.41 | 125.17 | 0.00 | 0.00 |
April | 431.80 | 166.98 | 366.68 | 165.74 | 200.95 | 0.00 | 0.00 |
May | 330.21 | 147.00 | 303.28 | 98.74 | 204.54 | 0.00 | 0.00 |
June | 311.72 | 116.42 | 279.39 | 67.63 | 211.76 | 0.00 | 0.00 |
July | 363.41 | 108.13 | 302.71 | 94.80 | 207.91 | 0.00 | 0.00 |
August | 450.35 | 117.63 | 354.71 | 159.56 | 195.15 | 0.00 | 0.00 |
September | 526.53 | 150.04 | 419.17 | 245.56 | 173.62 | 0.00 | 0.00 |
October | 325.36 | 189.27 | 287.99 | 168.32 | 119.67 | 0.00 | 0.00 |
November | 210.37 | 218.95 | 204.19 | 124.21 | 79.97 | 0.00 | 0.00 |
December | 159.58 | 266.98 | 161.84 | 103.69 | 58.15 | 0.00 | 0.00 |
Annual Sum or Average | 316.25 | 177.82 | 280.90 | 133.26 | 147.65 | 0.00 | 0.00 |
Minimum of Months | 151.50 | 108.13 | 161.84 | 51.41 | 58.15 | 0.00 | 0.00 |
Maximum of Months | 526.53 | 266.98 | 419.17 | 245.56 | 211.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.35 | 229.15 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 300.74 | 221.15 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 151.98 | 185.93 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 432.16 | 163.48 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 330.67 | 144.29 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 310.93 | 117.67 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 362.23 | 110.25 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 449.17 | 120.13 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 525.52 | 151.58 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 325.61 | 184.57 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 210.75 | 211.56 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 159.79 | 259.83 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 316.12 | 174.74 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 151.98 | 110.25 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 525.52 | 259.83 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.82 | 226.28 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 301.20 | 218.56 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 152.50 | 183.48 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 433.40 | 160.68 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 331.99 | 141.75 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 311.53 | 116.52 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 362.56 | 109.51 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 449.33 | 119.63 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 525.81 | 150.62 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 326.41 | 181.49 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 211.18 | 208.60 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 160.08 | 256.84 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 316.70 | 172.61 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 152.50 | 109.51 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 525.81 | 256.84 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 240.32 | 223.91 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 301.76 | 216.38 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 153.15 | 181.40 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 435.25 | 157.50 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 334.04 | 138.64 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 313.21 | 114.21 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 363.52 | 107.95 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 449.82 | 118.49 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 526.63 | 148.81 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 327.67 | 177.96 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 211.65 | 206.22 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 160.44 | 254.11 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 317.67 | 170.24 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 153.15 | 107.95 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 526.63 | 254.11 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 483.72 | 435.45 | 466.74 | 302.14 | 164.60 | 0.00 | 0.00 |
February | 607.28 | 420.79 | 570.04 | 347.85 | 222.19 | 0.00 | 0.00 |
March | 310.04 | 352.01 | 352.44 | 102.61 | 249.82 | 0.00 | 0.00 |
April | 877.90 | 302.02 | 731.86 | 330.79 | 401.07 | 0.00 | 0.00 |
May | 676.87 | 264.35 | 605.32 | 197.07 | 408.25 | 0.00 | 0.00 |
June | 635.85 | 216.38 | 557.63 | 134.98 | 422.65 | 0.00 | 0.00 |
July | 732.09 | 207.51 | 604.18 | 189.21 | 414.97 | 0.00 | 0.00 |
August | 901.77 | 230.50 | 707.97 | 318.47 | 389.50 | 0.00 | 0.00 |
September | 1058.35 | 287.31 | 836.63 | 490.11 | 346.52 | 0.00 | 0.00 |
October | 661.47 | 340.91 | 574.80 | 335.94 | 238.85 | 0.00 | 0.00 |
November | 425.89 | 400.64 | 407.53 | 247.91 | 159.62 | 0.00 | 0.00 |
December | 323.14 | 492.56 | 323.01 | 206.95 | 116.05 | 0.00 | 0.00 |
Annual Sum or Average | 640.29 | 328.75 | 560.65 | 265.97 | 294.69 | 0.00 | 0.00 |
Minimum of Months | 310.04 | 207.51 | 323.01 | 102.61 | 116.05 | 0.00 | 0.00 |
Maximum of Months | 1058.35 | 492.56 | 836.63 | 490.11 | 422.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 241.37 | 218.11 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 303.06 | 210.83 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 154.51 | 176.13 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 437.85 | 151.27 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 336.99 | 132.79 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 316.11 | 109.08 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 365.00 | 103.98 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 450.32 | 115.08 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 527.66 | 144.54 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 329.58 | 171.23 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 212.54 | 200.68 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 161.20 | 247.33 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 319.23 | 164.86 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 154.51 | 103.98 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 527.66 | 247.33 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 241.56 | 217.29 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 303.29 | 209.99 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 154.75 | 175.38 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 438.24 | 150.57 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 337.48 | 132.08 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 316.63 | 108.49 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 365.37 | 103.51 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 450.57 | 114.64 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 527.96 | 144.03 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 329.90 | 170.40 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 212.71 | 199.84 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 161.31 | 246.54 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 319.53 | 164.17 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 154.75 | 103.51 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 527.96 | 246.54 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.20 | 214.12 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 304.10 | 206.73 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 155.55 | 172.46 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 439.54 | 147.88 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 339.27 | 129.20 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 318.82 | 105.77 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 366.80 | 101.53 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 451.41 | 113.00 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 529.31 | 141.47 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 331.12 | 167.07 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 213.27 | 196.81 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 161.74 | 243.24 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 320.64 | 161.39 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 155.55 | 101.53 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 529.31 | 243.24 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.56 | 202.04 | 233.37 | 151.07 | 82.30 | 0.00 | 0.00 |
February | 307.07 | 194.08 | 285.02 | 173.92 | 111.10 | 0.00 | 0.00 |
March | 158.51 | 161.40 | 176.22 | 51.31 | 124.91 | 0.00 | 0.00 |
April | 442.39 | 138.72 | 365.93 | 165.40 | 200.53 | 0.00 | 0.00 |
May | 343.34 | 119.45 | 302.66 | 98.54 | 204.12 | 0.00 | 0.00 |
June | 323.62 | 97.39 | 278.81 | 67.49 | 211.32 | 0.00 | 0.00 |
July | 370.13 | 94.71 | 302.09 | 94.60 | 207.49 | 0.00 | 0.00 |
August | 453.80 | 106.47 | 353.98 | 159.23 | 194.75 | 0.00 | 0.00 |
September | 532.51 | 132.93 | 418.31 | 245.06 | 173.26 | 0.00 | 0.00 |
October | 333.92 | 156.70 | 287.40 | 167.97 | 119.43 | 0.00 | 0.00 |
November | 215.21 | 185.58 | 203.77 | 123.96 | 79.81 | 0.00 | 0.00 |
December | 163.32 | 229.93 | 161.50 | 103.48 | 58.03 | 0.00 | 0.00 |
Annual Sum or Average | 323.58 | 151.41 | 280.33 | 132.98 | 147.34 | 0.00 | 0.00 |
Minimum of Months | 158.51 | 94.71 | 161.50 | 51.31 | 58.03 | 0.00 | 0.00 |
Maximum of Months | 532.51 | 229.93 | 418.31 | 245.06 | 211.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129474E+10 | 0.119527E+10 | 0.125269E+10 | 0.810919E+09 | 0.441773E+09 | 0.00 | 0.00 |
February | 0.146986E+10 | 0.103858E+10 | 0.138188E+10 | 0.843239E+09 | 0.538636E+09 | 0.00 | 0.00 |
March | 0.829902E+09 | 0.961032E+09 | 0.945906E+09 | 0.275405E+09 | 0.670500E+09 | 0.00 | 0.00 |
April | 0.227871E+10 | 0.791981E+09 | 0.190089E+10 | 0.859179E+09 | 0.104171E+10 | 0.00 | 0.00 |
May | 0.181415E+10 | 0.715797E+09 | 0.162462E+10 | 0.528923E+09 | 0.109569E+10 | 0.00 | 0.00 |
June | 0.164884E+10 | 0.565786E+09 | 0.144834E+10 | 0.350583E+09 | 0.109776E+10 | 0.00 | 0.00 |
July | 0.196571E+10 | 0.555459E+09 | 0.162156E+10 | 0.507809E+09 | 0.111375E+10 | 0.00 | 0.00 |
August | 0.242332E+10 | 0.612441E+09 | 0.190011E+10 | 0.854741E+09 | 0.104537E+10 | 0.00 | 0.00 |
September | 0.274988E+10 | 0.744696E+09 | 0.217300E+10 | 0.127298E+10 | 0.900021E+09 | 0.00 | 0.00 |
October | 0.177373E+10 | 0.926131E+09 | 0.154271E+10 | 0.901643E+09 | 0.641064E+09 | 0.00 | 0.00 |
November | 0.110363E+10 | 0.106391E+10 | 0.105850E+10 | 0.643910E+09 | 0.414586E+09 | 0.00 | 0.00 |
December | 0.864490E+09 | 0.135291E+10 | 0.866920E+09 | 0.555440E+09 | 0.311480E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202170E+11 | 0.105240E+11 | 0.177171E+11 | 0.840477E+10 | 0.931234E+10 | 0.00 | 0.00 |
Minimum of Months | 0.829902E+09 | 0.555459E+09 | 0.866920E+09 | 0.275405E+09 | 0.311480E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274988E+10 | 0.135291E+10 | 0.217300E+10 | 0.127298E+10 | 0.111375E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640189E+09 | 0.631868E+09 | 0.626346E+09 | 0.405460E+09 | 0.220887E+09 | 0.00 | 0.00 |
February | 0.727210E+09 | 0.550538E+09 | 0.690938E+09 | 0.421620E+09 | 0.269318E+09 | 0.00 | 0.00 |
March | 0.405766E+09 | 0.513868E+09 | 0.472953E+09 | 0.137703E+09 | 0.335250E+09 | 0.00 | 0.00 |
April | 0.111923E+10 | 0.432817E+09 | 0.950444E+09 | 0.429589E+09 | 0.520854E+09 | 0.00 | 0.00 |
May | 0.884422E+09 | 0.393735E+09 | 0.812309E+09 | 0.264461E+09 | 0.547847E+09 | 0.00 | 0.00 |
June | 0.807976E+09 | 0.301758E+09 | 0.724171E+09 | 0.175292E+09 | 0.548879E+09 | 0.00 | 0.00 |
July | 0.973351E+09 | 0.289604E+09 | 0.810780E+09 | 0.253905E+09 | 0.556875E+09 | 0.00 | 0.00 |
August | 0.120621E+10 | 0.315061E+09 | 0.950056E+09 | 0.427370E+09 | 0.522685E+09 | 0.00 | 0.00 |
September | 0.136476E+10 | 0.388913E+09 | 0.108650E+10 | 0.636491E+09 | 0.450011E+09 | 0.00 | 0.00 |
October | 0.871442E+09 | 0.506949E+09 | 0.771354E+09 | 0.450821E+09 | 0.320532E+09 | 0.00 | 0.00 |
November | 0.545279E+09 | 0.567511E+09 | 0.529248E+09 | 0.321955E+09 | 0.207293E+09 | 0.00 | 0.00 |
December | 0.427432E+09 | 0.715083E+09 | 0.433460E+09 | 0.277720E+09 | 0.155740E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.997326E+10 | 0.560770E+10 | 0.885856E+10 | 0.420239E+10 | 0.465617E+10 | 0.00 | 0.00 |
Minimum of Months | 0.405766E+09 | 0.289604E+09 | 0.433460E+09 | 0.137703E+09 | 0.155740E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136476E+10 | 0.715083E+09 | 0.108650E+10 | 0.636491E+09 | 0.556875E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.641080E+09 | 0.613749E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.727541E+09 | 0.535011E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.407071E+09 | 0.497998E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.112015E+10 | 0.423731E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.885672E+09 | 0.386457E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.805926E+09 | 0.304992E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.970210E+09 | 0.295286E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120306E+10 | 0.321766E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.136214E+10 | 0.392892E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.872125E+09 | 0.494350E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.546268E+09 | 0.548374E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.427972E+09 | 0.695923E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.996922E+10 | 0.551053E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.407071E+09 | 0.295286E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136214E+10 | 0.695923E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.642321E+09 | 0.606074E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.728672E+09 | 0.528737E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.408466E+09 | 0.491438E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.112338E+10 | 0.416492E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.889190E+09 | 0.379672E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.807491E+09 | 0.302012E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.971079E+09 | 0.293324E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120347E+10 | 0.320422E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.136291E+10 | 0.390401E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.874255E+09 | 0.486112E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.547389E+09 | 0.540688E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.428757E+09 | 0.687914E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.998739E+10 | 0.544329E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.408466E+09 | 0.293324E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136291E+10 | 0.687914E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643686E+09 | 0.599714E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.730027E+09 | 0.523462E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.410186E+09 | 0.485861E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.112818E+10 | 0.408245E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.894680E+09 | 0.371327E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.811849E+09 | 0.296037E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.973641E+09 | 0.289128E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120481E+10 | 0.317374E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.136502E+10 | 0.385713E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.877639E+09 | 0.476656E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.548587E+09 | 0.534520E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.429718E+09 | 0.680608E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100180E+11 | 0.536865E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410186E+09 | 0.289128E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136502E+10 | 0.680608E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129560E+10 | 0.116632E+10 | 0.125012E+10 | 0.809256E+09 | 0.440867E+09 | 0.00 | 0.00 |
February | 0.146914E+10 | 0.101798E+10 | 0.137904E+10 | 0.841509E+09 | 0.537531E+09 | 0.00 | 0.00 |
March | 0.830400E+09 | 0.942829E+09 | 0.943965E+09 | 0.274840E+09 | 0.669125E+09 | 0.00 | 0.00 |
April | 0.227552E+10 | 0.782829E+09 | 0.189699E+10 | 0.857416E+09 | 0.103957E+10 | 0.00 | 0.00 |
May | 0.181294E+10 | 0.708036E+09 | 0.162128E+10 | 0.527837E+09 | 0.109345E+10 | 0.00 | 0.00 |
June | 0.164812E+10 | 0.560866E+09 | 0.144537E+10 | 0.349864E+09 | 0.109551E+10 | 0.00 | 0.00 |
July | 0.196084E+10 | 0.555804E+09 | 0.161823E+10 | 0.506768E+09 | 0.111146E+10 | 0.00 | 0.00 |
August | 0.241531E+10 | 0.617373E+09 | 0.189621E+10 | 0.852987E+09 | 0.104323E+10 | 0.00 | 0.00 |
September | 0.274323E+10 | 0.744717E+09 | 0.216854E+10 | 0.127037E+10 | 0.898175E+09 | 0.00 | 0.00 |
October | 0.177168E+10 | 0.913102E+09 | 0.153954E+10 | 0.899793E+09 | 0.639749E+09 | 0.00 | 0.00 |
November | 0.110391E+10 | 0.103845E+10 | 0.105632E+10 | 0.642589E+09 | 0.413735E+09 | 0.00 | 0.00 |
December | 0.865504E+09 | 0.131927E+10 | 0.865142E+09 | 0.554300E+09 | 0.310841E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.201922E+11 | 0.103676E+11 | 0.176808E+11 | 0.838753E+10 | 0.929324E+10 | 0.00 | 0.00 |
Minimum of Months | 0.830400E+09 | 0.555804E+09 | 0.865142E+09 | 0.274840E+09 | 0.310841E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274323E+10 | 0.131927E+10 | 0.216854E+10 | 0.127037E+10 | 0.111146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.646487E+09 | 0.584187E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.733154E+09 | 0.510031E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.413837E+09 | 0.471734E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.113490E+10 | 0.392094E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.902588E+09 | 0.355657E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.819362E+09 | 0.282723E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.977615E+09 | 0.278513E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120613E+10 | 0.308220E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.136770E+10 | 0.374643E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.882759E+09 | 0.458616E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.550893E+09 | 0.520152E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.431761E+09 | 0.662452E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100672E+11 | 0.519902E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.413837E+09 | 0.278513E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136770E+10 | 0.662452E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.646993E+09 | 0.581995E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.733725E+09 | 0.508000E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.414474E+09 | 0.469730E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.113593E+10 | 0.390276E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.903911E+09 | 0.353771E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.820696E+09 | 0.281196E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.978607E+09 | 0.277232E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120682E+10 | 0.307043E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.136846E+10 | 0.373323E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.883604E+09 | 0.456400E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.551338E+09 | 0.517995E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.432062E+09 | 0.660339E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100766E+11 | 0.517730E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.414474E+09 | 0.277232E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136846E+10 | 0.660339E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.648702E+09 | 0.573509E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.735681E+09 | 0.500121E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.416626E+09 | 0.461929E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.113930E+10 | 0.383307E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.908697E+09 | 0.346047E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.826378E+09 | 0.274145E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.982425E+09 | 0.271933E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.120905E+10 | 0.302670E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.137198E+10 | 0.366688E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.886866E+09 | 0.447483E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.552786E+09 | 0.510129E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.433192E+09 | 0.651482E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101117E+11 | 0.508944E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.416626E+09 | 0.271933E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137198E+10 | 0.651482E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655036E+09 | 0.541154E+09 | 0.625061E+09 | 0.404628E+09 | 0.220433E+09 | 0.00 | 0.00 |
February | 0.742869E+09 | 0.469515E+09 | 0.689520E+09 | 0.420755E+09 | 0.268766E+09 | 0.00 | 0.00 |
March | 0.424560E+09 | 0.432283E+09 | 0.471983E+09 | 0.137420E+09 | 0.334562E+09 | 0.00 | 0.00 |
April | 0.114667E+10 | 0.359568E+09 | 0.948494E+09 | 0.428708E+09 | 0.519786E+09 | 0.00 | 0.00 |
May | 0.919602E+09 | 0.319926E+09 | 0.810642E+09 | 0.263919E+09 | 0.546724E+09 | 0.00 | 0.00 |
June | 0.838823E+09 | 0.252437E+09 | 0.722685E+09 | 0.174932E+09 | 0.547753E+09 | 0.00 | 0.00 |
July | 0.991361E+09 | 0.253683E+09 | 0.809116E+09 | 0.253384E+09 | 0.555732E+09 | 0.00 | 0.00 |
August | 0.121545E+10 | 0.285176E+09 | 0.948107E+09 | 0.426494E+09 | 0.521613E+09 | 0.00 | 0.00 |
September | 0.138026E+10 | 0.344562E+09 | 0.108427E+10 | 0.635185E+09 | 0.449087E+09 | 0.00 | 0.00 |
October | 0.894369E+09 | 0.419693E+09 | 0.769771E+09 | 0.449897E+09 | 0.319875E+09 | 0.00 | 0.00 |
November | 0.557817E+09 | 0.481029E+09 | 0.528162E+09 | 0.321294E+09 | 0.206868E+09 | 0.00 | 0.00 |
December | 0.437449E+09 | 0.615844E+09 | 0.432571E+09 | 0.277150E+09 | 0.155421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102043E+11 | 0.477487E+10 | 0.884039E+10 | 0.419377E+10 | 0.464662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424560E+09 | 0.252437E+09 | 0.432571E+09 | 0.137420E+09 | 0.155421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138026E+10 | 0.615844E+09 | 0.108427E+10 | 0.635185E+09 | 0.555732E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362579E+09 | -238919074.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123659782.0 | 58.99 | 0.00 | 0.00 |
February | 0.330247E+09 | -218400926.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111845969.1 | 58.99 | 0.00 | 0.00 |
March | 0.367652E+09 | -244123127.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123528583.8 | 58.99 | 0.00 | 0.00 |
April | 0.345909E+09 | -228769059.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117140417.9 | 58.99 | 0.00 | 0.00 |
May | 0.350585E+09 | -230440624.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120143936.9 | 58.99 | 0.00 | 0.00 |
June | 0.331201E+09 | -219060180.4 | 0.00 | 0.00 | 720.00 | 0.00 | -112141069.8 | 58.99 | 0.00 | 0.00 |
July | 0.331395E+09 | -217092046.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114303374.5 | 58.99 | 0.00 | 0.00 |
August | 0.333561E+09 | -219928187.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113632916.4 | 58.99 | 0.00 | 0.00 |
September | 0.323262E+09 | -212066437.8 | 0.00 | 0.00 | 720.00 | 0.00 | -111195093.3 | 58.99 | 0.00 | 0.00 |
October | 0.342905E+09 | -221707949.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121196704.6 | 58.99 | 0.00 | 0.00 |
November | 0.339280E+09 | -220047621.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119232104.9 | 58.99 | 0.00 | 0.00 |
December | 0.358596E+09 | -234600879.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123995099.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411717E+10 | -0.270516E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141202E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.323262E+09 | -244123127.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123995099.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.367652E+09 | -212066437.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111195093.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.360361E+09 | -238918912.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121442295.7 | 58.99 | 0.00 | 0.00 |
February | 0.328178E+09 | -218404033.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109773917.9 | 58.99 | 0.00 | 0.00 |
March | 0.365230E+09 | -244120982.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121108856.0 | 58.99 | 0.00 | 0.00 |
April | 0.342038E+09 | -228764850.2 | 0.00 | 0.00 | 720.00 | 0.00 | -113272990.5 | 58.99 | 0.00 | 0.00 |
May | 0.346663E+09 | -230442230.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116221126.4 | 58.99 | 0.00 | 0.00 |
June | 0.328947E+09 | -219060213.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109886843.5 | 58.99 | 0.00 | 0.00 |
July | 0.330162E+09 | -217086892.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113075462.6 | 58.99 | 0.00 | 0.00 |
August | 0.332852E+09 | -219927041.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112925084.7 | 58.99 | 0.00 | 0.00 |
September | 0.321683E+09 | -212064567.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109617956.4 | 58.99 | 0.00 | 0.00 |
October | 0.338906E+09 | -221704808.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117200847.4 | 58.99 | 0.00 | 0.00 |
November | 0.336800E+09 | -220044523.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116755935.2 | 58.99 | 0.00 | 0.00 |
December | 0.356454E+09 | -234600024.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121854036.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.408827E+10 | -0.270514E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138314E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.321683E+09 | -244120982.7 | 0.00 | 0.00 | 672.00 | 0.00 | -121854036.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365230E+09 | -212064567.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109617956.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333292E+09 | -210099593.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123192404.3 | 58.99 | 0.00 | 0.00 |
February | 0.303499E+09 | -192210368.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111288803.1 | 58.99 | 0.00 | 0.00 |
March | 0.340651E+09 | -217869081.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122781979.8 | 59.00 | 0.00 | 0.00 |
April | 0.315690E+09 | -201190449.0 | 0.00 | 0.00 | 720.00 | 0.00 | -114499217.7 | 58.99 | 0.00 | 0.00 |
May | 0.321641E+09 | -204355494.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117285170.2 | 58.99 | 0.00 | 0.00 |
June | 0.304789E+09 | -195104938.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109683943.2 | 58.99 | 0.00 | 0.00 |
July | 0.302316E+09 | -189792592.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112523700.3 | 58.99 | 0.00 | 0.00 |
August | 0.308745E+09 | -196438680.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112306444.7 | 58.99 | 0.00 | 0.00 |
September | 0.295738E+09 | -186375947.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109362040.3 | 58.99 | 0.00 | 0.00 |
October | 0.313645E+09 | -194991479.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118653149.7 | 58.99 | 0.00 | 0.00 |
November | 0.312851E+09 | -194310466.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118540368.1 | 58.98 | 0.00 | 0.00 |
December | 0.328376E+09 | -204805930.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123570195.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378123E+10 | -0.238755E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139369E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295738E+09 | -217869081.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123570195.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340651E+09 | -186375947.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109362040.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333707E+09 | -210105710.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123601688.0 | 58.99 | 0.00 | 0.00 |
February | 0.303833E+09 | -192214197.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111618514.1 | 58.99 | 0.00 | 0.00 |
March | 0.341017E+09 | -217886593.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123130697.3 | 58.99 | 0.00 | 0.00 |
April | 0.316280E+09 | -201206811.0 | 0.00 | 0.00 | 720.00 | 0.00 | -115073410.1 | 58.99 | 0.00 | 0.00 |
May | 0.322211E+09 | -204350740.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117860337.1 | 58.99 | 0.00 | 0.00 |
June | 0.305028E+09 | -195108944.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109918725.4 | 58.99 | 0.00 | 0.00 |
July | 0.302461E+09 | -189794586.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112666311.9 | 58.99 | 0.00 | 0.00 |
August | 0.308828E+09 | -196439399.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112388695.5 | 58.99 | 0.00 | 0.00 |
September | 0.295899E+09 | -186383004.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109516426.3 | 58.99 | 0.00 | 0.00 |
October | 0.314207E+09 | -194971555.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119235201.7 | 58.99 | 0.00 | 0.00 |
November | 0.313265E+09 | -194297130.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118968002.6 | 58.99 | 0.00 | 0.00 |
December | 0.328767E+09 | -204777980.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123988934.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378550E+10 | -0.238754E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139797E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295899E+09 | -217886593.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123988934.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.341017E+09 | -186383004.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109516426.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323480E+09 | -198573978.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124905814.1 | 58.99 | 0.00 | 0.00 |
February | 0.294514E+09 | -181757102.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112756528.0 | 58.99 | 0.00 | 0.00 |
March | 0.330518E+09 | -206169069.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124348694.2 | 58.99 | 0.00 | 0.00 |
April | 0.307888E+09 | -190390906.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117497164.1 | 58.99 | 0.00 | 0.00 |
May | 0.313728E+09 | -193265395.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120462604.1 | 58.99 | 0.00 | 0.00 |
June | 0.296975E+09 | -184607429.2 | 0.00 | 0.00 | 720.00 | 0.00 | -112367480.9 | 58.99 | 0.00 | 0.00 |
July | 0.293647E+09 | -179513386.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114133911.2 | 58.98 | 0.00 | 0.00 |
August | 0.299190E+09 | -185853531.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113336913.7 | 59.00 | 0.00 | 0.00 |
September | 0.287527E+09 | -176374822.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111152303.6 | 58.99 | 0.00 | 0.00 |
October | 0.305928E+09 | -184288056.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121640392.7 | 58.99 | 0.00 | 0.00 |
November | 0.303641E+09 | -183506372.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120134587.6 | 58.99 | 0.00 | 0.00 |
December | 0.319061E+09 | -193682613.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125378579.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367610E+10 | -0.225798E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141811E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287527E+09 | -206169069.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125378579.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.330518E+09 | -176374822.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111152303.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323482E+09 | -198574227.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124907619.9 | 58.99 | 0.00 | 0.00 |
February | 0.294517E+09 | -181756744.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112760566.2 | 58.99 | 0.00 | 0.00 |
March | 0.330520E+09 | -206168816.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124351104.5 | 58.99 | 0.00 | 0.00 |
April | 0.307619E+09 | -190393697.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117225739.3 | 58.99 | 0.00 | 0.00 |
May | 0.313334E+09 | -193257250.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120076465.5 | 59.00 | 0.00 | 0.00 |
June | 0.296372E+09 | -184613166.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111758464.3 | 58.99 | 0.00 | 0.00 |
July | 0.293378E+09 | -179495938.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113882006.4 | 58.99 | 0.00 | 0.00 |
August | 0.299084E+09 | -185925416.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113158447.2 | 58.97 | 0.00 | 0.00 |
September | 0.287069E+09 | -176369441.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110699815.4 | 58.99 | 0.00 | 0.00 |
October | 0.305575E+09 | -184283833.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121291577.3 | 58.99 | 0.00 | 0.00 |
November | 0.303647E+09 | -183500551.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120146532.1 | 58.99 | 0.00 | 0.00 |
December | 0.319030E+09 | -193687362.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125342592.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367363E+10 | -0.225803E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141560E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287069E+09 | -206168816.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125342592.2 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.330520E+09 | -176369441.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110699815.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323591E+09 | -198578848.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125012180.0 | 58.99 | 0.00 | 0.00 |
February | 0.294626E+09 | -181740394.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112885958.5 | 59.00 | 0.00 | 0.00 |
March | 0.330626E+09 | -206165245.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124460576.1 | 58.99 | 0.00 | 0.00 |
April | 0.307763E+09 | -190389850.6 | 0.00 | 0.00 | 720.00 | 0.00 | -117373159.9 | 58.99 | 0.00 | 0.00 |
May | 0.313481E+09 | -193260302.7 | 0.00 | 0.00 | 744.00 | 0.00 | -120220874.0 | 58.99 | 0.00 | 0.00 |
June | 0.296535E+09 | -184609071.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111925525.4 | 58.99 | 0.00 | 0.00 |
July | 0.293489E+09 | -179492209.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113997102.4 | 58.99 | 0.00 | 0.00 |
August | 0.299178E+09 | -185848829.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113328785.6 | 59.00 | 0.00 | 0.00 |
September | 0.287167E+09 | -176379497.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110787798.9 | 58.99 | 0.00 | 0.00 |
October | 0.305730E+09 | -184297788.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121432616.7 | 58.99 | 0.00 | 0.00 |
November | 0.303748E+09 | -183507222.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120241199.7 | 58.99 | 0.00 | 0.00 |
December | 0.319126E+09 | -193684209.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125441648.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367506E+10 | -0.225795E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141711E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287167E+09 | -206165245.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125441648.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330626E+09 | -176379497.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110787798.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121917E+11 | 52623.71 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101885E+11 | 52623.71 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.919700E+10 | 52623.71 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218058E+10 | 52623.71 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138212E+10 | 52623.71 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31359957.49 | 3666.03 | 08-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 675427.05 | 637.43 | 08-SEP-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249903E+10 | 52623.71 | 21-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791423E+10 | 52623.71 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133461E+11 | 52623.71 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133461E+11 | 52623.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273066E+10 | 28645.94 | 03-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198480E+10 | 28645.94 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157520E+10 | 28645.94 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96578755.71 | 9906.92 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10241742.61 | 1350.33 | 05-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85848869.08 | 2064.41 | 28-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123352E+10 | 28645.94 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318106E+10 | 28645.94 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318106E+10 | 28645.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375333E+10 | 28469.71 | 04-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289594E+10 | 28469.71 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242946E+10 | 27936.48 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255293E+09 | 6746.37 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43085378.43 | 3622.27 | 06-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.297230E+09 | 5947.07 | 23-OCT-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203377E+10 | 28469.71 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418893E+10 | 28469.71 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418893E+10 | 28469.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.401501E+10 | 28344.93 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311397E+10 | 28344.93 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266156E+10 | 28344.93 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338290E+09 | 10294.61 | 02-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81558884.73 | 4279.65 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410224E+09 | 8319.25 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227679E+10 | 28344.93 | 19-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442937E+10 | 28344.93 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442937E+10 | 28344.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.438766E+10 | 28288.37 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344753E+10 | 28288.37 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302281E+10 | 28288.37 | 04-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470129E+09 | 14087.71 | 02-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174627E+09 | 7371.50 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586255E+09 | 11490.39 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261421E+10 | 28288.37 | 19-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480475E+10 | 28288.37 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480475E+10 | 28288.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104245E+11 | 50804.53 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.846947E+10 | 50804.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.799868E+10 | 50804.53 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210458E+10 | 50804.53 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139423E+10 | 50804.53 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45043956.73 | 3704.70 | 08-JUN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 129922.50 | 124.72 | 05-JUL-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 721250.91 | 676.63 | 08-SEP-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263074E+10 | 50804.53 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718201E+10 | 50804.53 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111474E+11 | 50804.53 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111474E+11 | 50804.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.472024E+10 | 26891.58 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376034E+10 | 26891.58 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342721E+10 | 26891.58 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.684851E+09 | 26891.58 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.389774E+09 | 26891.58 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4143116.22 | 1048.02 | 07-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.891000E+09 | 26891.58 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302678E+10 | 26891.58 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511895E+10 | 26891.58 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511895E+10 | 26891.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482531E+10 | 26743.40 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385570E+10 | 26743.40 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352550E+10 | 26743.40 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.737908E+09 | 26743.40 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.432392E+09 | 26743.40 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6341487.36 | 2209.81 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.946905E+09 | 26743.40 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311745E+10 | 26743.40 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.520887E+10 | 26743.40 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520887E+10 | 26743.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.523306E+10 | 26466.39 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422646E+10 | 26466.39 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391624E+10 | 26466.39 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.941520E+09 | 26466.39 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609729E+09 | 26466.39 | 05-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18628416.02 | 9710.40 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116505E+10 | 26466.39 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345962E+10 | 26466.39 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.560586E+10 | 26466.39 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.560586E+10 | 26466.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672671E+10 | 26791.94 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555315E+10 | 26791.94 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525902E+10 | 26791.94 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151102E+10 | 26791.94 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112973E+10 | 26791.94 | 03-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80502901.57 | 26791.94 | 08-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5716938.01 | 8679.24 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10289117.49 | 3158.08 | 20-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187182E+10 | 26791.94 | 11-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460225E+10 | 26791.94 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717772E+10 | 26791.94 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717772E+10 | 26791.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.371826E+09 | 0.368641E+09 | 10709.17 | 30-APR-16:03 | 10709.17 | 0.00 |
May | 0.00 | 0.00 | 0.229784E+09 | 0.194905E+09 | 8566.94 | 22-MAY-15:00 | 7771.98 | 0.00 |
June | 0.00 | 0.00 | 0.157979E+10 | 0.129988E+10 | 14559.44 | 13-JUN-17:00 | 13207.42 | 0.00 |
July | 0.00 | 0.00 | 0.292237E+10 | 0.245989E+10 | 16376.40 | 23-JUL-07:03 | 12158.02 | 0.00 |
August | 0.00 | 0.00 | 0.290558E+10 | 0.236758E+10 | 13078.57 | 14-AUG-17:00 | 13078.57 | 0.00 |
September | 0.00 | 0.00 | 0.152138E+10 | 0.126755E+10 | 11144.74 | 13-SEP-16:10 | 9531.30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.953072E+10 | 0.795844E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292237E+10 | 0.245989E+10 | 16376.40 | 13207.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 281703.26 | 231455.17 | 246.68 | 19-MAR-19:10 | 186.01 | 0.00 |
April | 0.00 | 0.00 | 0.253907E+09 | 0.253230E+09 | 15989.73 | 30-APR-19:07 | 15989.73 | 0.00 |
May | 0.00 | 0.00 | 0.163647E+09 | 0.150482E+09 | 15987.04 | 21-MAY-18:40 | 14757.99 | 0.00 |
June | 0.00 | 0.00 | 0.953293E+09 | 0.823347E+09 | 17625.46 | 25-JUN-18:00 | 10500.84 | 0.00 |
July | 0.00 | 0.00 | 0.153649E+10 | 0.136251E+10 | 16958.43 | 23-JUL-17:02 | 12332.30 | 0.00 |
August | 0.00 | 0.00 | 0.146251E+10 | 0.126365E+10 | 16480.27 | 13-AUG-17:02 | 12578.54 | 0.00 |
September | 0.00 | 0.00 | 0.869904E+09 | 0.759834E+09 | 16846.26 | 10-SEP-17:02 | 11298.41 | 0.00 |
October | 0.00 | 0.00 | 10476313.66 | 9896354.59 | 2725.57 | 04-OCT-20:10 | 2707.21 | 0.00 |
November | 0.00 | 0.00 | 463013.83 | 410606.86 | 246.41 | 05-NOV-19:10 | 229.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.525097E+10 | 0.462359E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153649E+10 | 0.136251E+10 | 17625.46 | 15989.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.132054E+09 | 0.131728E+09 | 6154.43 | 30-APR-15:00 | 6154.43 | 0.00 |
May | 0.00 | 0.00 | 93493021.10 | 85086137.13 | 5370.05 | 22-MAY-15:00 | 5095.96 | 0.00 |
June | 0.00 | 0.00 | 0.748965E+09 | 0.655561E+09 | 8048.07 | 13-JUN-16:30 | 7431.40 | 0.00 |
July | 0.00 | 0.00 | 0.110086E+10 | 0.993576E+09 | 14874.60 | 23-JUL-07:03 | 11797.50 | 0.00 |
August | 0.00 | 0.00 | 0.112967E+10 | 0.981848E+09 | 7399.37 | 14-AUG-17:00 | 7399.37 | 0.00 |
September | 0.00 | 0.00 | 0.712993E+09 | 0.631107E+09 | 6241.17 | 13-SEP-14:00 | 5505.19 | 0.00 |
October | 0.00 | 0.00 | 356950.81 | 356705.70 | 361.94 | 07-OCT-15:00 | 361.94 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.391839E+10 | 0.347926E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112967E+10 | 0.993576E+09 | 14874.60 | 11797.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125968E+09 | 0.125677E+09 | 6059.72 | 30-APR-15:00 | 6059.72 | 0.00 |
May | 0.00 | 0.00 | 81863074.01 | 74902023.89 | 5126.36 | 22-MAY-15:00 | 4862.80 | 0.00 |
June | 0.00 | 0.00 | 0.729399E+09 | 0.638104E+09 | 7979.84 | 13-JUN-16:30 | 7366.61 | 0.00 |
July | 0.00 | 0.00 | 0.107973E+10 | 0.974960E+09 | 15304.67 | 23-JUL-07:03 | 12132.72 | 0.00 |
August | 0.00 | 0.00 | 0.110292E+10 | 0.958765E+09 | 7348.52 | 14-AUG-17:00 | 7348.52 | 0.00 |
September | 0.00 | 0.00 | 0.688753E+09 | 0.609979E+09 | 6182.24 | 13-SEP-14:00 | 5452.83 | 0.00 |
October | 0.00 | 0.00 | 198048.60 | 198048.60 | 238.95 | 07-OCT-15:00 | 238.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.380882E+10 | 0.338259E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110292E+10 | 0.974960E+09 | 15304.67 | 12132.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.110157E+09 | 0.109951E+09 | 5810.06 | 30-APR-15:00 | 5810.06 | 0.00 |
May | 0.00 | 0.00 | 65095299.61 | 60198791.38 | 4731.48 | 22-MAY-15:00 | 4485.40 | 0.00 |
June | 0.00 | 0.00 | 0.674799E+09 | 0.590033E+09 | 7756.70 | 13-JUN-16:40 | 7165.22 | 0.00 |
July | 0.00 | 0.00 | 0.998815E+09 | 0.904826E+09 | 13255.36 | 23-JUL-07:03 | 10534.34 | 0.00 |
August | 0.00 | 0.00 | 0.100550E+10 | 0.876080E+09 | 7180.45 | 14-AUG-17:00 | 7180.45 | 0.00 |
September | 0.00 | 0.00 | 0.620492E+09 | 0.550550E+09 | 5974.71 | 13-SEP-14:00 | 5268.41 | 0.00 |
October | 0.00 | 0.00 | 9059.36 | 9059.36 | 15.08 | 04-OCT-15:30 | 15.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347487E+10 | 0.309165E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100550E+10 | 0.904826E+09 | 13255.36 | 10534.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.180222E+09 | 0.177768E+09 | 9277.27 | 30-APR-15:00 | 9277.27 | 0.00 |
May | 0.00 | 0.00 | 0.103990E+09 | 90122006.33 | 7523.35 | 22-MAY-15:00 | 6695.53 | 0.00 |
June | 0.00 | 0.00 | 0.110665E+10 | 0.919238E+09 | 12855.69 | 13-JUN-15:00 | 10950.67 | 0.00 |
July | 0.00 | 0.00 | 0.188693E+10 | 0.160658E+10 | 19102.22 | 23-JUL-08:63 | 14649.27 | 0.00 |
August | 0.00 | 0.00 | 0.214610E+10 | 0.175494E+10 | 11682.85 | 14-AUG-14:50 | 10491.76 | 0.00 |
September | 0.00 | 0.00 | 0.114393E+10 | 0.964889E+09 | 10425.98 | 13-SEP-14:20 | 8750.88 | 0.00 |
October | 0.00 | 0.00 | 641648.86 | 641648.86 | 630.40 | 07-OCT-15:00 | 630.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.656846E+10 | 0.551418E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214610E+10 | 0.175494E+10 | 19102.22 | 14649.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.230615E+09 | 0.230593E+09 | 5452.45 | 30-APR-15:00 | 5452.45 | 0.00 |
May | 0.00 | 0.00 | 0.224384E+09 | 0.199964E+09 | 4442.92 | 22-MAY-15:00 | 4100.26 | 0.00 |
June | 0.00 | 0.00 | 0.109930E+10 | 0.973664E+09 | 7137.52 | 13-JUN-15:00 | 6284.74 | 0.00 |
July | 0.00 | 0.00 | 0.233265E+10 | 0.205531E+10 | 10489.58 | 23-JUL-08:63 | 10473.57 | 0.00 |
August | 0.00 | 0.00 | 0.296775E+10 | 0.260136E+10 | 6595.72 | 14-AUG-14:50 | 6075.06 | 0.00 |
September | 0.00 | 0.00 | 0.150650E+10 | 0.134753E+10 | 6077.60 | 13-SEP-14:40 | 5373.89 | 0.00 |
October | 0.00 | 0.00 | 27348554.07 | 27348554.07 | 2281.24 | 07-OCT-15:00 | 2281.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.838855E+10 | 0.743577E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.296775E+10 | 0.260136E+10 | 10489.58 | 10473.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220635E+09 | 0.220611E+09 | 5364.27 | 30-APR-15:00 | 5364.27 | 0.00 |
May | 0.00 | 0.00 | 0.209486E+09 | 0.186427E+09 | 4352.59 | 22-MAY-15:00 | 4015.65 | 0.00 |
June | 0.00 | 0.00 | 0.105343E+10 | 0.932048E+09 | 7043.99 | 13-JUN-15:00 | 6199.30 | 0.00 |
July | 0.00 | 0.00 | 0.225565E+10 | 0.198661E+10 | 9938.59 | 23-JUL-08:63 | 9920.71 | 0.00 |
August | 0.00 | 0.00 | 0.287301E+10 | 0.251640E+10 | 6514.41 | 14-AUG-14:50 | 5998.55 | 0.00 |
September | 0.00 | 0.00 | 0.144626E+10 | 0.129256E+10 | 6000.16 | 13-SEP-14:40 | 5302.82 | 0.00 |
October | 0.00 | 0.00 | 24499794.91 | 24499794.91 | 2202.50 | 07-OCT-15:00 | 2202.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.808297E+10 | 0.715916E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287301E+10 | 0.251640E+10 | 9938.59 | 9920.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.190184E+09 | 0.190161E+09 | 5120.71 | 30-APR-15:00 | 5120.71 | 0.00 |
May | 0.00 | 0.00 | 0.167058E+09 | 0.148207E+09 | 4088.06 | 22-MAY-15:00 | 3768.17 | 0.00 |
June | 0.00 | 0.00 | 0.914660E+09 | 0.806463E+09 | 6809.40 | 13-JUN-15:00 | 5985.23 | 0.00 |
July | 0.00 | 0.00 | 0.201375E+10 | 0.177218E+10 | 8145.10 | 23-JUL-08:63 | 8145.10 | 0.00 |
August | 0.00 | 0.00 | 0.257226E+10 | 0.224794E+10 | 6294.29 | 14-AUG-15:00 | 5851.15 | 0.00 |
September | 0.00 | 0.00 | 0.123846E+10 | 0.110308E+10 | 5804.39 | 13-SEP-14:40 | 5123.47 | 0.00 |
October | 0.00 | 0.00 | 15700562.40 | 15700562.40 | 1881.38 | 07-OCT-15:00 | 1881.38 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.711207E+10 | 0.628374E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257226E+10 | 0.224794E+10 | 8145.10 | 8145.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.170715E+09 | 0.170706E+09 | 4902.59 | 30-APR-15:00 | 4902.59 | 0.00 |
May | 0.00 | 0.00 | 0.137926E+09 | 0.122782E+09 | 3910.49 | 22-MAY-15:00 | 3603.33 | 0.00 |
June | 0.00 | 0.00 | 0.822151E+09 | 0.724863E+09 | 6734.63 | 13-JUN-15:00 | 5918.01 | 0.00 |
July | 0.00 | 0.00 | 0.174961E+10 | 0.154895E+10 | 8254.04 | 22-JUL-15:00 | 8253.97 | 0.00 |
August | 0.00 | 0.00 | 0.222174E+10 | 0.194387E+10 | 6138.62 | 14-AUG-14:50 | 5642.24 | 0.00 |
September | 0.00 | 0.00 | 0.103421E+10 | 0.919927E+09 | 5645.33 | 13-SEP-14:20 | 4995.01 | 0.00 |
October | 0.00 | 0.00 | 9074722.72 | 9074722.72 | 1410.26 | 07-OCT-15:00 | 1410.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.614543E+10 | 0.544017E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222174E+10 | 0.194387E+10 | 8254.04 | 8253.97 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164155E+10 | 0.41 | 1897.55 | 01-JAN-08:62 | 0.89 |
February | 0.146675E+10 | 0.41 | 1897.55 | 01-FEB-08:61 | 0.88 |
March | 0.158191E+10 | 0.40 | 1897.55 | 01-MAR-08:61 | 0.89 |
April | 0.138063E+10 | 0.37 | 1897.55 | 01-APR-07:01 | 0.89 |
May | 0.140707E+10 | 0.37 | 1897.55 | 05-MAY-07:01 | 0.89 |
June | 0.133959E+10 | 0.36 | 838.34 | 08-JUN-08:15 | 0.57 |
July | 0.137805E+10 | 0.36 | 903.99 | 23-JUL-07:03 | 0.60 |
August | 0.137990E+10 | 0.36 | 759.02 | 04-AUG-16:20 | 0.53 |
September | 0.133619E+10 | 0.36 | 772.81 | 08-SEP-09:00 | 0.54 |
October | 0.143123E+10 | 0.37 | 1897.55 | 21-OCT-07:01 | 0.89 |
November | 0.150218E+10 | 0.39 | 1897.55 | 02-NOV-07:01 | 0.88 |
December | 0.167204E+10 | 0.41 | 1897.55 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.175171E+11 | 0.38 | |||
Minimum of Months | 0.133619E+10 | 0.36 | 759.02 | 0.53 | |
Maximum of Months | 0.167204E+10 | 0.41 | 1897.55 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150239E+10 | 0.46 | 1106.98 | 01-JAN-09:13 | 0.91 |
February | 0.135892E+10 | 0.46 | 1106.98 | 01-FEB-09:30 | 0.91 |
March | 0.152712E+10 | 0.48 | 1106.98 | 01-MAR-10:20 | 0.92 |
April | 0.155887E+10 | 0.59 | 1106.98 | 01-APR-08:50 | 0.92 |
May | 0.166711E+10 | 0.60 | 1106.98 | 04-MAY-16:00 | 0.91 |
June | 0.181669E+10 | 0.62 | 1106.98 | 09-JUN-16:30 | 0.91 |
July | 0.192403E+10 | 0.61 | 1106.98 | 06-JUL-12:00 | 0.91 |
August | 0.195380E+10 | 0.61 | 1106.98 | 01-AUG-12:50 | 0.91 |
September | 0.184864E+10 | 0.62 | 1106.98 | 01-SEP-09:20 | 0.91 |
October | 0.157146E+10 | 0.57 | 1106.98 | 04-OCT-18:40 | 0.91 |
November | 0.145921E+10 | 0.47 | 1106.98 | 01-NOV-09:20 | 0.92 |
December | 0.149442E+10 | 0.46 | 1106.98 | 01-DEC-13:30 | 0.92 |
Annual Sum or Average | 0.196827E+11 | 0.55 | |||
Minimum of Months | 0.135892E+10 | 0.46 | 1106.98 | 0.91 | |
Maximum of Months | 0.195380E+10 | 0.62 | 1106.98 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158248E+10 | 0.50 | 1093.48 | 01-JAN-08:62 | 0.92 |
February | 0.143290E+10 | 0.50 | 1093.48 | 01-FEB-08:06 | 0.92 |
March | 0.161398E+10 | 0.50 | 1093.48 | 01-MAR-07:03 | 0.92 |
April | 0.153525E+10 | 0.50 | 1093.48 | 01-APR-06:03 | 0.92 |
May | 0.159823E+10 | 0.50 | 1093.48 | 04-MAY-08:00 | 0.91 |
June | 0.155887E+10 | 0.50 | 1093.48 | 04-JUN-07:10 | 0.91 |
July | 0.157461E+10 | 0.49 | 1093.48 | 06-JUL-15:00 | 0.91 |
August | 0.161398E+10 | 0.50 | 1093.48 | 01-AUG-09:30 | 0.91 |
September | 0.153525E+10 | 0.49 | 1093.48 | 06-SEP-09:40 | 0.91 |
October | 0.158248E+10 | 0.49 | 1093.48 | 14-OCT-07:50 | 0.91 |
November | 0.153525E+10 | 0.50 | 1093.48 | 01-NOV-09:17 | 0.92 |
December | 0.157461E+10 | 0.49 | 1093.48 | 01-DEC-07:30 | 0.92 |
Annual Sum or Average | 0.187379E+11 | 0.50 | |||
Minimum of Months | 0.143290E+10 | 0.49 | 1093.48 | 0.91 | |
Maximum of Months | 0.161398E+10 | 0.50 | 1093.48 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157991E+10 | 0.50 | 1091.70 | 01-JAN-09:01 | 0.92 |
February | 0.143057E+10 | 0.50 | 1091.70 | 01-FEB-08:61 | 0.92 |
March | 0.161136E+10 | 0.50 | 1091.70 | 01-MAR-09:00 | 0.92 |
April | 0.153275E+10 | 0.50 | 1091.70 | 01-APR-07:01 | 0.92 |
May | 0.159564E+10 | 0.50 | 1091.70 | 04-MAY-12:00 | 0.91 |
June | 0.155633E+10 | 0.50 | 1091.70 | 09-JUN-15:00 | 0.91 |
July | 0.157205E+10 | 0.49 | 1091.70 | 06-JUL-09:20 | 0.91 |
August | 0.161136E+10 | 0.50 | 1091.70 | 02-AUG-12:00 | 0.91 |
September | 0.153275E+10 | 0.49 | 1091.70 | 01-SEP-08:10 | 0.91 |
October | 0.157991E+10 | 0.49 | 1091.70 | 04-OCT-17:00 | 0.91 |
November | 0.153275E+10 | 0.50 | 1091.70 | 01-NOV-08:00 | 0.92 |
December | 0.157205E+10 | 0.49 | 1091.70 | 01-DEC-08:07 | 0.92 |
Annual Sum or Average | 0.187074E+11 | 0.50 | |||
Minimum of Months | 0.143057E+10 | 0.49 | 1091.70 | 0.91 | |
Maximum of Months | 0.161136E+10 | 0.50 | 1091.70 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156992E+10 | 0.50 | 1084.80 | 01-JAN-08:03 | 0.92 |
February | 0.142152E+10 | 0.50 | 1084.80 | 01-FEB-08:02 | 0.92 |
March | 0.160117E+10 | 0.50 | 1084.80 | 01-MAR-09:10 | 0.92 |
April | 0.152306E+10 | 0.50 | 1084.80 | 01-APR-06:40 | 0.92 |
May | 0.158555E+10 | 0.50 | 1084.80 | 04-MAY-08:00 | 0.91 |
June | 0.154649E+10 | 0.50 | 1084.80 | 09-JUN-17:10 | 0.91 |
July | 0.156211E+10 | 0.49 | 1084.80 | 06-JUL-13:10 | 0.91 |
August | 0.160117E+10 | 0.50 | 1084.80 | 01-AUG-10:10 | 0.91 |
September | 0.152306E+10 | 0.49 | 1084.80 | 05-SEP-10:50 | 0.91 |
October | 0.156992E+10 | 0.49 | 1084.80 | 12-OCT-07:40 | 0.91 |
November | 0.152306E+10 | 0.50 | 1084.80 | 01-NOV-07:04 | 0.92 |
December | 0.156211E+10 | 0.49 | 1084.80 | 01-DEC-08:00 | 0.92 |
Annual Sum or Average | 0.185892E+11 | 0.50 | |||
Minimum of Months | 0.142152E+10 | 0.49 | 1084.80 | 0.91 | |
Maximum of Months | 0.160117E+10 | 0.50 | 1084.80 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122099E+10 | 0.30 | 1857.43 | 01-JAN-09:01 | 0.89 |
February | 0.108449E+10 | 0.30 | 1857.43 | 01-FEB-08:61 | 0.89 |
March | 0.118917E+10 | 0.30 | 1857.43 | 01-MAR-08:61 | 0.88 |
April | 0.100906E+10 | 0.28 | 1857.43 | 01-APR-07:01 | 0.89 |
May | 0.103360E+10 | 0.28 | 1857.43 | 05-MAY-07:01 | 0.88 |
June | 0.979928E+09 | 0.27 | 824.24 | 08-JUN-08:10 | 0.57 |
July | 0.987335E+09 | 0.26 | 1113.82 | 23-JUL-08:63 | 0.68 |
August | 0.101371E+10 | 0.27 | 742.97 | 01-AUG-17:10 | 0.53 |
September | 0.962907E+09 | 0.27 | 757.81 | 08-SEP-09:00 | 0.54 |
October | 0.105002E+10 | 0.28 | 1857.43 | 15-OCT-08:61 | 0.88 |
November | 0.112044E+10 | 0.29 | 1857.43 | 01-NOV-07:01 | 0.89 |
December | 0.123150E+10 | 0.31 | 1857.43 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.128831E+11 | 0.28 | |||
Minimum of Months | 0.962907E+09 | 0.26 | 742.97 | 0.53 | |
Maximum of Months | 0.123150E+10 | 0.31 | 1857.43 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136383E+10 | 0.46 | 1021.14 | 01-JAN-13:10 | 0.92 |
February | 0.123517E+10 | 0.46 | 1021.14 | 01-FEB-11:50 | 0.91 |
March | 0.139324E+10 | 0.47 | 1021.14 | 01-MAR-12:20 | 0.92 |
April | 0.132340E+10 | 0.46 | 1021.14 | 02-APR-12:50 | 0.92 |
May | 0.137854E+10 | 0.46 | 1021.14 | 03-MAY-13:10 | 0.91 |
June | 0.134545E+10 | 0.46 | 1021.14 | 08-JUN-09:20 | 0.91 |
July | 0.135648E+10 | 0.45 | 1021.14 | 06-JUL-10:50 | 0.91 |
August | 0.139324E+10 | 0.46 | 1021.14 | 04-AUG-18:40 | 0.91 |
September | 0.132340E+10 | 0.46 | 1021.14 | 01-SEP-12:40 | 0.91 |
October | 0.136383E+10 | 0.46 | 1021.14 | 05-OCT-14:40 | 0.92 |
November | 0.132340E+10 | 0.46 | 1021.14 | 01-NOV-11:10 | 0.91 |
December | 0.135648E+10 | 0.45 | 1021.14 | 01-DEC-12:30 | 0.92 |
Annual Sum or Average | 0.161565E+11 | 0.46 | |||
Minimum of Months | 0.123517E+10 | 0.45 | 1021.14 | 0.91 | |
Maximum of Months | 0.139324E+10 | 0.47 | 1021.14 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135476E+10 | 0.46 | 1014.34 | 05-JAN-08:50 | 0.92 |
February | 0.122695E+10 | 0.46 | 1014.34 | 04-FEB-15:50 | 0.92 |
March | 0.138397E+10 | 0.47 | 1014.34 | 08-MAR-11:10 | 0.92 |
April | 0.131459E+10 | 0.46 | 1014.34 | 01-APR-12:20 | 0.92 |
May | 0.136936E+10 | 0.46 | 1014.34 | 03-MAY-20:00 | 0.91 |
June | 0.133650E+10 | 0.46 | 1014.34 | 11-JUN-12:10 | 0.91 |
July | 0.134746E+10 | 0.45 | 1014.34 | 11-JUL-10:00 | 0.91 |
August | 0.138397E+10 | 0.46 | 1014.34 | 09-AUG-11:20 | 0.91 |
September | 0.131459E+10 | 0.46 | 1014.34 | 04-SEP-15:40 | 0.91 |
October | 0.135476E+10 | 0.46 | 1014.34 | 09-OCT-11:20 | 0.91 |
November | 0.131459E+10 | 0.46 | 1014.34 | 02-NOV-17:50 | 0.92 |
December | 0.134746E+10 | 0.45 | 1014.34 | 05-DEC-09:00 | 0.91 |
Annual Sum or Average | 0.160490E+11 | 0.46 | |||
Minimum of Months | 0.122695E+10 | 0.45 | 1014.34 | 0.91 | |
Maximum of Months | 0.138397E+10 | 0.47 | 1014.34 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133872E+10 | 0.46 | 1002.34 | 15-JAN-12:00 | 0.92 |
February | 0.121242E+10 | 0.46 | 1002.34 | 01-FEB-20:10 | 0.91 |
March | 0.136759E+10 | 0.47 | 1002.34 | 02-MAR-19:30 | 0.92 |
April | 0.129903E+10 | 0.46 | 1002.34 | 06-APR-13:00 | 0.92 |
May | 0.135315E+10 | 0.46 | 1002.34 | 10-MAY-19:10 | 0.92 |
June | 0.132068E+10 | 0.46 | 1002.34 | 02-JUN-15:50 | 0.91 |
July | 0.133150E+10 | 0.45 | 1002.34 | 29-JUL-07:50 | 0.91 |
August | 0.136759E+10 | 0.46 | 1002.34 | 21-AUG-07:20 | 0.91 |
September | 0.129903E+10 | 0.46 | 1002.34 | 01-SEP-07:50 | 0.91 |
October | 0.133872E+10 | 0.46 | 1002.34 | 19-OCT-10:20 | 0.91 |
November | 0.129903E+10 | 0.46 | 1002.34 | 07-NOV-08:50 | 0.91 |
December | 0.133150E+10 | 0.45 | 1002.34 | 02-DEC-09:00 | 0.92 |
Annual Sum or Average | 0.158589E+11 | 0.46 | |||
Minimum of Months | 0.121242E+10 | 0.45 | 1002.34 | 0.91 | |
Maximum of Months | 0.136759E+10 | 0.47 | 1002.34 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137401E+10 | 0.46 | 1028.76 | 01-JAN-09:01 | 0.92 |
February | 0.124439E+10 | 0.46 | 1028.76 | 01-FEB-08:61 | 0.92 |
March | 0.140364E+10 | 0.47 | 1028.76 | 01-MAR-08:61 | 0.92 |
April | 0.133327E+10 | 0.46 | 1028.76 | 01-APR-07:01 | 0.92 |
May | 0.138883E+10 | 0.46 | 1028.76 | 01-MAY-07:03 | 0.92 |
June | 0.135549E+10 | 0.46 | 1028.76 | 01-JUN-07:10 | 0.91 |
July | 0.136660E+10 | 0.45 | 1028.76 | 01-JUL-07:10 | 0.91 |
August | 0.140364E+10 | 0.46 | 1028.76 | 01-AUG-07:10 | 0.91 |
September | 0.133327E+10 | 0.46 | 1028.76 | 01-SEP-07:10 | 0.91 |
October | 0.137401E+10 | 0.46 | 1028.76 | 01-OCT-08:65 | 0.92 |
November | 0.133327E+10 | 0.46 | 1028.76 | 01-NOV-07:01 | 0.92 |
December | 0.136660E+10 | 0.45 | 1028.76 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.162770E+11 | 0.46 | |||
Minimum of Months | 0.124439E+10 | 0.45 | 1028.76 | 0.91 | |
Maximum of Months | 0.140364E+10 | 0.47 | 1028.76 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164155E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146675E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158191E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147355E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.146702E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172415E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210802E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.211600E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171661E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.143123E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150218E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167204E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.199010E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143123E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.211600E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150239E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135892E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152719E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161372E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170317E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.201907E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.225576E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.227256E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.203779E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157393E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145932E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149442E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135892E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227256E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158248E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143290E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161398E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156441E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161927E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171942E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.181554E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.186387E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169194E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158257E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153525E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195962E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143290E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186387E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157991E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143057E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161136E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156062E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161411E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171290E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180839E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.185548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168433E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157996E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153275E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157205E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195424E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143057E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185548E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156992E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142152E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160117E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154751E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160029E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169192E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178123E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166015E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156993E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152306E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156211E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142152E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182418E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122099E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108449E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118917E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.105520E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106088E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.125473E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146237E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155857E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125171E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105020E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112044E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123150E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105020E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.155857E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.136383E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.123517E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139324E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137513E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143002E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.158761E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.187170E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204850E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165648E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137022E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132340E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135648E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180118E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123517E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204850E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135476E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122695E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138397E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136414E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.141747E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.156868E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184609E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.201900E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.163450E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.136048E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131459E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134746E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122695E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201900E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133872E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121242E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136759E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.134188E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.139162E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.152258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.177769E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.193802E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.157332E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134240E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129903E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133150E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174368E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121242E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.193802E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137401E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124439E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.140364E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137187E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.142055E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.153724E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175464E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189840E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.156295E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137617E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.133327E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136660E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176437E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124439E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189840E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164155E+10 | 0.00 | 0.121917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146675E+10 | 0.00 | 0.101885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158191E+10 | 0.00 | 0.919700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138063E+10 | 0.371826E+09 | 0.218058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140707E+10 | 0.229784E+09 | 0.138212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133959E+10 | 0.157979E+10 | 31359957.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137805E+10 | 0.292237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137990E+10 | 0.290558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133619E+10 | 0.152138E+10 | 675427.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143123E+10 | 0.00 | 0.249903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150218E+10 | 0.00 | 0.791423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167204E+10 | 0.00 | 0.133461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175171E+11 | 0.953072E+10 | 0.589314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167204E+10 | 0.292237E+10 | 0.133461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150239E+10 | 0.00 | 0.273066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135892E+10 | 0.00 | 0.198480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152712E+10 | 281703.26 | 0.157520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155887E+10 | 0.253907E+09 | 96578755.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166711E+10 | 0.163647E+09 | 10241742.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181669E+10 | 0.953293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192403E+10 | 0.153649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195380E+10 | 0.146251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184864E+10 | 0.869904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157146E+10 | 10476313.66 | 85848869.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145921E+10 | 463013.83 | 0.123352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149442E+10 | 0.00 | 0.318106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196827E+11 | 0.525097E+10 | 0.108979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195380E+10 | 0.153649E+10 | 0.318106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158248E+10 | 0.00 | 0.375333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143290E+10 | 0.00 | 0.289594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161398E+10 | 0.00 | 0.242946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153525E+10 | 0.132054E+09 | 0.255293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159823E+10 | 93493021.10 | 43085378.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155887E+10 | 0.748965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157461E+10 | 0.110086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161398E+10 | 0.112967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153525E+10 | 0.712993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158248E+10 | 356950.81 | 0.297230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153525E+10 | 0.00 | 0.203377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157461E+10 | 0.00 | 0.418893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187379E+11 | 0.391839E+10 | 0.158970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161398E+10 | 0.112967E+10 | 0.418893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157991E+10 | 0.00 | 0.401501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143057E+10 | 0.00 | 0.311397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161136E+10 | 0.00 | 0.266156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153275E+10 | 0.125968E+09 | 0.338290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159564E+10 | 81863074.01 | 81558884.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155633E+10 | 0.729399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157205E+10 | 0.107973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161136E+10 | 0.110292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153275E+10 | 0.688753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157991E+10 | 198048.60 | 0.410224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153275E+10 | 0.00 | 0.227679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157205E+10 | 0.00 | 0.442937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187074E+11 | 0.380882E+10 | 0.173268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161136E+10 | 0.110292E+10 | 0.442937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156992E+10 | 0.00 | 0.438766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142152E+10 | 0.00 | 0.344753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160117E+10 | 0.00 | 0.302281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152306E+10 | 0.110157E+09 | 0.470129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158555E+10 | 65095299.61 | 0.174627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154649E+10 | 0.674799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156211E+10 | 0.998815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160117E+10 | 0.100550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152306E+10 | 0.620492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156992E+10 | 9059.36 | 0.586255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152306E+10 | 0.00 | 0.261421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156211E+10 | 0.00 | 0.480475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185892E+11 | 0.347487E+10 | 0.195080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160117E+10 | 0.100550E+10 | 0.480475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122099E+10 | 0.00 | 0.104245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108449E+10 | 0.00 | 0.846947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118917E+10 | 0.00 | 0.799868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100906E+10 | 0.180222E+09 | 0.210458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103360E+10 | 0.103990E+09 | 0.139423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979928E+09 | 0.110665E+10 | 45043956.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987335E+09 | 0.188693E+10 | 129922.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101371E+10 | 0.214610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.962907E+09 | 0.114393E+10 | 721250.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105002E+10 | 641648.86 | 0.263074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112044E+10 | 0.00 | 0.718201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123150E+10 | 0.00 | 0.111474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128831E+11 | 0.656846E+10 | 0.513975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123150E+10 | 0.214610E+10 | 0.111474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136383E+10 | 0.00 | 0.472024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123517E+10 | 0.00 | 0.376034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139324E+10 | 0.00 | 0.342721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132340E+10 | 0.230615E+09 | 0.684851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137854E+10 | 0.224384E+09 | 0.389774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134545E+10 | 0.109930E+10 | 4143116.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135648E+10 | 0.233265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139324E+10 | 0.296775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132340E+10 | 0.150650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136383E+10 | 27348554.07 | 0.891000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132340E+10 | 0.00 | 0.302678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135648E+10 | 0.00 | 0.511895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161565E+11 | 0.838855E+10 | 0.220233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139324E+10 | 0.296775E+10 | 0.511895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135476E+10 | 0.00 | 0.482531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122695E+10 | 0.00 | 0.385570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138397E+10 | 0.00 | 0.352550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131459E+10 | 0.220635E+09 | 0.737908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136936E+10 | 0.209486E+09 | 0.432392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133650E+10 | 0.105343E+10 | 6341487.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134746E+10 | 0.225565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138397E+10 | 0.287301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131459E+10 | 0.144626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135476E+10 | 24499794.91 | 0.946905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131459E+10 | 0.00 | 0.311745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134746E+10 | 0.00 | 0.520887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160490E+11 | 0.808297E+10 | 0.226564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138397E+10 | 0.287301E+10 | 0.520887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133872E+10 | 0.00 | 0.523306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121242E+10 | 0.00 | 0.422646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136759E+10 | 0.00 | 0.391624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129903E+10 | 0.190184E+09 | 0.941520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135315E+10 | 0.167058E+09 | 0.609729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132068E+10 | 0.914660E+09 | 18628416.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133150E+10 | 0.201375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136759E+10 | 0.257226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129903E+10 | 0.123846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133872E+10 | 15700562.40 | 0.116505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129903E+10 | 0.00 | 0.345962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133150E+10 | 0.00 | 0.560586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158589E+11 | 0.711207E+10 | 0.251762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136759E+10 | 0.257226E+10 | 0.560586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137401E+10 | 0.00 | 0.672671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124439E+10 | 0.00 | 0.555315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140364E+10 | 0.00 | 0.525902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133327E+10 | 0.170715E+09 | 0.151102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138883E+10 | 0.137926E+09 | 0.112973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135549E+10 | 0.822151E+09 | 80502901.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136660E+10 | 0.174961E+10 | 5716938.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140364E+10 | 0.222174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133327E+10 | 0.103421E+10 | 10289117.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137401E+10 | 9074722.72 | 0.187182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133327E+10 | 0.00 | 0.460225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136660E+10 | 0.00 | 0.717772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162770E+11 | 0.614543E+10 | 0.339279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140364E+10 | 0.222174E+10 | 0.717772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138063E+10 | 0.00 | 0.00 | 0.00 | 92923117.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140707E+10 | 0.00 | 0.00 | 0.00 | 59948533.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133959E+10 | 0.00 | 0.00 | 0.00 | 0.384562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137805E+10 | 0.00 | 0.00 | 0.00 | 0.729972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137990E+10 | 0.00 | 0.00 | 0.00 | 0.736104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133619E+10 | 0.00 | 0.00 | 0.00 | 0.380416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175171E+11 | 0.00 | 0.00 | 0.00 | 0.238393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167204E+10 | 0.00 | 0.00 | 0.00 | 0.736104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152712E+10 | 0.00 | 0.00 | 0.00 | 69218.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155887E+10 | 0.00 | 0.00 | 0.00 | 54849794.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166711E+10 | 0.00 | 0.00 | 0.00 | 36061950.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181669E+10 | 0.00 | 0.00 | 0.00 | 0.202384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192403E+10 | 0.00 | 0.00 | 0.00 | 0.331726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195380E+10 | 0.00 | 0.00 | 0.00 | 0.318765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184864E+10 | 0.00 | 0.00 | 0.00 | 0.189150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157146E+10 | 0.00 | 0.00 | 0.00 | 2467588.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145921E+10 | 0.00 | 0.00 | 0.00 | 113972.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196827E+11 | 0.00 | 0.00 | 0.00 | 0.113559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195380E+10 | 0.00 | 0.00 | 0.00 | 0.331726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153525E+10 | 0.00 | 0.00 | 0.00 | 29167826.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159823E+10 | 0.00 | 0.00 | 0.00 | 21039616.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155887E+10 | 0.00 | 0.00 | 0.00 | 0.160555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157461E+10 | 0.00 | 0.00 | 0.00 | 0.240932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 0.249896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153525E+10 | 0.00 | 0.00 | 0.00 | 0.156695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158248E+10 | 0.00 | 0.00 | 0.00 | 87040.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187379E+11 | 0.00 | 0.00 | 0.00 | 0.858371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 0.249896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153275E+10 | 0.00 | 0.00 | 0.00 | 27867294.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159564E+10 | 0.00 | 0.00 | 0.00 | 18471791.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155633E+10 | 0.00 | 0.00 | 0.00 | 0.156562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157205E+10 | 0.00 | 0.00 | 0.00 | 0.236337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161136E+10 | 0.00 | 0.00 | 0.00 | 0.244127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153275E+10 | 0.00 | 0.00 | 0.00 | 0.151576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157991E+10 | 0.00 | 0.00 | 0.00 | 48479.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187074E+11 | 0.00 | 0.00 | 0.00 | 0.834989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161136E+10 | 0.00 | 0.00 | 0.00 | 0.244127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152306E+10 | 0.00 | 0.00 | 0.00 | 24446426.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158555E+10 | 0.00 | 0.00 | 0.00 | 14742353.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154649E+10 | 0.00 | 0.00 | 0.00 | 0.145423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156211E+10 | 0.00 | 0.00 | 0.00 | 0.219121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160117E+10 | 0.00 | 0.00 | 0.00 | 0.223018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152306E+10 | 0.00 | 0.00 | 0.00 | 0.137086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156992E+10 | 0.00 | 0.00 | 0.00 | 2241.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185892E+11 | 0.00 | 0.00 | 0.00 | 0.763838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160117E+10 | 0.00 | 0.00 | 0.00 | 0.223018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100906E+10 | 0.00 | 0.00 | 0.00 | 46142431.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103360E+10 | 0.00 | 0.00 | 0.00 | 27282097.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979928E+09 | 0.00 | 0.00 | 0.00 | 0.274799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987335E+09 | 0.00 | 0.00 | 0.00 | 0.475032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101371E+10 | 0.00 | 0.00 | 0.00 | 0.544862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.962907E+09 | 0.00 | 0.00 | 0.00 | 0.288798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105002E+10 | 0.00 | 0.00 | 0.00 | 179333.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128831E+11 | 0.00 | 0.00 | 0.00 | 0.165709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123150E+10 | 0.00 | 0.00 | 0.00 | 0.544862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132340E+10 | 0.00 | 0.00 | 0.00 | 51735654.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137854E+10 | 0.00 | 0.00 | 0.00 | 51483208.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134545E+10 | 0.00 | 0.00 | 0.00 | 0.242162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135648E+10 | 0.00 | 0.00 | 0.00 | 0.515221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139324E+10 | 0.00 | 0.00 | 0.00 | 0.655263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132340E+10 | 0.00 | 0.00 | 0.00 | 0.333085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136383E+10 | 0.00 | 0.00 | 0.00 | 6390906.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161565E+11 | 0.00 | 0.00 | 0.00 | 0.185534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139324E+10 | 0.00 | 0.00 | 0.00 | 0.655263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131459E+10 | 0.00 | 0.00 | 0.00 | 49550372.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136936E+10 | 0.00 | 0.00 | 0.00 | 48107453.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133650E+10 | 0.00 | 0.00 | 0.00 | 0.232181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134746E+10 | 0.00 | 0.00 | 0.00 | 0.498636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138397E+10 | 0.00 | 0.00 | 0.00 | 0.635027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131459E+10 | 0.00 | 0.00 | 0.00 | 0.319914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135476E+10 | 0.00 | 0.00 | 0.00 | 5726170.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160490E+11 | 0.00 | 0.00 | 0.00 | 0.178914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138397E+10 | 0.00 | 0.00 | 0.00 | 0.635027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129903E+10 | 0.00 | 0.00 | 0.00 | 42849053.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135315E+10 | 0.00 | 0.00 | 0.00 | 38467095.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132068E+10 | 0.00 | 0.00 | 0.00 | 0.201906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133150E+10 | 0.00 | 0.00 | 0.00 | 0.446186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136759E+10 | 0.00 | 0.00 | 0.00 | 0.570433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129903E+10 | 0.00 | 0.00 | 0.00 | 0.274290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133872E+10 | 0.00 | 0.00 | 0.00 | 3681513.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158589E+11 | 0.00 | 0.00 | 0.00 | 0.157781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136759E+10 | 0.00 | 0.00 | 0.00 | 0.570433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133327E+10 | 0.00 | 0.00 | 0.00 | 38596596.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138883E+10 | 0.00 | 0.00 | 0.00 | 31724768.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135549E+10 | 0.00 | 0.00 | 0.00 | 0.181748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136660E+10 | 0.00 | 0.00 | 0.00 | 0.388032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140364E+10 | 0.00 | 0.00 | 0.00 | 0.494760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133327E+10 | 0.00 | 0.00 | 0.00 | 0.229679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137401E+10 | 0.00 | 0.00 | 0.00 | 2155675.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162770E+11 | 0.00 | 0.00 | 0.00 | 0.136670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140364E+10 | 0.00 | 0.00 | 0.00 | 0.494760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.869804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594427E+10 | 0.00 | 0.00 | 0.52 |
February | 0.840008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457260E+10 | 0.00 | 0.00 | 0.53 |
March | 0.873951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416320E+10 | 0.00 | 0.00 | 0.53 |
April | 0.878643E+10 | 0.00 | 0.00 | 1904778.57 | 2030231.57 | 0.394715E+09 | 0.955276E+09 | 0.00 | 0.56 |
May | 0.871692E+10 | 83633.82 | 0.00 | 1941600.77 | 0.00 | 86573748.72 | 0.141526E+10 | 0.00 | 0.56 |
June | 0.480454E+10 | 63034717.21 | 0.00 | 6049837.70 | 0.00 | 0.00 | 0.402310E+10 | 0.00 | 0.64 |
July | 0.206316E+10 | 94064935.19 | 0.00 | 12809815.64 | 0.00 | 0.00 | 0.694763E+10 | 0.00 | 0.76 |
August | 0.726574E+09 | 1108612.99 | 0.00 | 15974974.96 | 0.00 | 0.00 | 0.843421E+10 | 0.00 | 0.86 |
September | 0.316148E+10 | 0.00 | 0.00 | 9104770.81 | 0.00 | 0.00 | 0.591811E+10 | 0.00 | 0.70 |
October | 0.951718E+10 | 0.00 | 0.00 | 179888.29 | 0.00 | 0.514365E+09 | 0.256025E+09 | 0.00 | 0.53 |
November | 0.867542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338479E+10 | 0.00 | 0.00 | 0.52 |
December | 0.751990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724163E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.798092E+11 | 0.158292E+09 | 0.00 | 47965666.75 | 2030231.57 | 0.263021E+11 | 0.279496E+11 | 0.00 | 0.60 |
Minimum of Months | 0.726574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.951718E+10 | 94064935.19 | 0.00 | 15974974.96 | 2030231.57 | 0.724163E+10 | 0.843421E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171718E+10 | 0.00 | 0.00 | 0.38 |
February | 0.381017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851406E+09 | 0.00 | 0.00 | 0.39 |
March | 0.416375E+10 | 0.00 | 0.00 | 10246.07 | 0.00 | 0.613172E+09 | 10063612.73 | 0.00 | 0.39 |
April | 0.300069E+10 | 0.00 | 0.00 | 2212198.12 | 316948.78 | 3968714.60 | 0.168133E+10 | 0.00 | 0.53 |
May | 0.278605E+10 | 9202.83 | 0.00 | 2621940.57 | 0.00 | 0.00 | 0.231393E+10 | 0.00 | 0.57 |
June | 0.585004E+09 | 25069327.80 | 0.00 | 6391434.19 | 0.00 | 0.00 | 0.517323E+10 | 0.00 | 0.86 |
July | 0.148762E+09 | 42750324.93 | 0.00 | 8690027.51 | 392568.68 | 0.00 | 0.633270E+10 | 0.00 | 1.12 |
August | 24790381.84 | 183114.75 | 0.00 | 10038883.25 | 0.00 | 0.00 | 0.688154E+10 | 0.00 | 1.34 |
September | 0.256788E+09 | 0.00 | 0.00 | 7977116.16 | 0.00 | 0.00 | 0.606703E+10 | 0.00 | 1.02 |
October | 0.289974E+10 | 0.00 | 0.00 | 1740620.65 | 0.00 | 0.00 | 0.170143E+10 | 0.00 | 0.46 |
November | 0.407102E+10 | 0.00 | 0.00 | 9254.73 | 0.00 | 0.389656E+09 | 7743915.16 | 0.00 | 0.39 |
December | 0.290840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238150E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.283113E+11 | 68011970.31 | 0.00 | 39691721.24 | 709517.47 | 0.595688E+10 | 0.301690E+11 | 0.00 | 0.66 |
Minimum of Months | 24790381.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.416375E+10 | 42750324.93 | 0.00 | 10038883.25 | 392568.68 | 0.238150E+10 | 0.688154E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244049E+10 | 0.00 | 0.00 | 0.41 |
February | 0.313101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167870E+10 | 0.00 | 0.00 | 0.41 |
March | 0.348116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143112E+10 | 0.00 | 0.00 | 0.42 |
April | 0.319956E+10 | 0.00 | 0.00 | 984410.00 | 465293.33 | 84526330.72 | 0.828571E+09 | 0.00 | 0.50 |
May | 0.319118E+10 | 15788.86 | 0.00 | 1167898.07 | 0.00 | 2560833.83 | 0.108533E+10 | 0.00 | 0.51 |
June | 0.106362E+10 | 16596010.94 | 0.00 | 3607375.32 | 0.00 | 0.00 | 0.309865E+10 | 0.00 | 0.69 |
July | 0.551463E+09 | 32606612.37 | 0.00 | 5137880.81 | 1653939.29 | 0.00 | 0.400496E+10 | 0.00 | 0.88 |
August | 0.356695E+09 | 189109.19 | 0.00 | 6475724.87 | 0.00 | 0.00 | 0.457216E+10 | 0.00 | 1.08 |
September | 0.768330E+09 | 0.00 | 0.00 | 4870038.80 | 0.00 | 0.00 | 0.369314E+10 | 0.00 | 0.82 |
October | 0.318455E+10 | 0.00 | 0.00 | 816828.72 | 0.00 | 30102742.16 | 0.905597E+09 | 0.00 | 0.44 |
November | 0.342651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112388E+10 | 0.00 | 0.00 | 0.41 |
December | 0.240464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307640E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.278349E+11 | 49407521.36 | 0.00 | 23060156.59 | 2119232.62 | 0.986778E+10 | 0.181884E+11 | 0.00 | 0.58 |
Minimum of Months | 0.356695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.348116E+10 | 32606612.37 | 0.00 | 6475724.87 | 1653939.29 | 0.307640E+10 | 0.457216E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261081E+10 | 0.00 | 0.00 | 0.41 |
February | 0.290371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190573E+10 | 0.00 | 0.00 | 0.41 |
March | 0.324562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166382E+10 | 0.00 | 0.00 | 0.42 |
April | 0.316120E+10 | 0.00 | 0.00 | 880344.50 | 510060.49 | 0.135824E+09 | 0.746316E+09 | 0.00 | 0.49 |
May | 0.319374E+10 | 13569.91 | 0.00 | 1069874.41 | 0.00 | 5999058.21 | 0.100390E+10 | 0.00 | 0.51 |
June | 0.116774E+10 | 16366937.84 | 0.00 | 3387708.57 | 0.00 | 0.00 | 0.290641E+10 | 0.00 | 0.68 |
July | 0.596106E+09 | 32557877.58 | 0.00 | 4988000.94 | 1659196.10 | 0.00 | 0.389996E+10 | 0.00 | 0.87 |
August | 0.368483E+09 | 177006.55 | 0.00 | 6368325.91 | 0.00 | 0.00 | 0.452251E+10 | 0.00 | 1.07 |
September | 0.792288E+09 | 0.00 | 0.00 | 4707761.12 | 0.00 | 0.00 | 0.359491E+10 | 0.00 | 0.81 |
October | 0.314554E+10 | 0.00 | 0.00 | 717242.70 | 0.00 | 88177753.93 | 0.821102E+09 | 0.00 | 0.44 |
November | 0.315405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139082E+10 | 0.00 | 0.00 | 0.41 |
December | 0.215883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332216E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.267920E+11 | 49115391.88 | 0.00 | 22119258.14 | 2169256.58 | 0.111233E+11 | 0.174951E+11 | 0.00 | 0.58 |
Minimum of Months | 0.368483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.324562E+10 | 32557877.58 | 0.00 | 6368325.91 | 1659196.10 | 0.332216E+10 | 0.452251E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306080E+10 | 0.00 | 0.00 | 0.41 |
February | 0.249936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230980E+10 | 0.00 | 0.00 | 0.41 |
March | 0.278509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212179E+10 | 0.00 | 0.00 | 0.42 |
April | 0.313271E+10 | 0.00 | 0.00 | 681558.12 | 611038.41 | 0.223747E+09 | 0.570102E+09 | 0.00 | 0.48 |
May | 0.319273E+10 | 10004.67 | 0.00 | 867596.36 | 0.00 | 21398658.52 | 0.844920E+09 | 0.00 | 0.49 |
June | 0.144608E+10 | 15701227.20 | 0.00 | 2740749.92 | 0.00 | 0.00 | 0.237776E+10 | 0.00 | 0.64 |
July | 0.702018E+09 | 32262648.90 | 0.00 | 4487321.30 | 1700646.09 | 0.00 | 0.359014E+10 | 0.00 | 0.84 |
August | 0.418292E+09 | 139834.55 | 0.00 | 5939701.88 | 0.00 | 0.00 | 0.430970E+10 | 0.00 | 1.04 |
September | 0.862085E+09 | 0.00 | 0.00 | 4194030.40 | 0.00 | 0.00 | 0.329854E+10 | 0.00 | 0.77 |
October | 0.308516E+10 | 0.00 | 0.00 | 456861.05 | 0.00 | 0.235004E+09 | 0.611638E+09 | 0.00 | 0.43 |
November | 0.279104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174922E+10 | 0.00 | 0.00 | 0.41 |
December | 0.186368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361742E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.252327E+11 | 48113715.32 | 0.00 | 19367819.03 | 2311684.50 | 0.133392E+11 | 0.156028E+11 | 0.00 | 0.56 |
Minimum of Months | 0.418292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.319273E+10 | 32262648.90 | 0.00 | 5939701.88 | 1700646.09 | 0.361742E+10 | 0.430970E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714720E+10 | 0.00 | 0.00 | 0.38 |
February | 0.355514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546803E+10 | 0.00 | 0.00 | 0.38 |
March | 0.442874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480862E+10 | 0.00 | 0.00 | 0.39 |
April | 0.579013E+10 | 0.00 | 0.00 | 787277.42 | 1267341.34 | 0.489714E+09 | 0.545545E+09 | 0.00 | 0.40 |
May | 0.605448E+10 | 0.00 | 0.00 | 798609.23 | 0.00 | 0.106914E+09 | 0.802324E+09 | 0.00 | 0.40 |
June | 0.404071E+10 | 21112469.15 | 0.00 | 2823392.76 | 0.00 | 0.00 | 0.175990E+10 | 0.00 | 0.46 |
July | 0.161168E+10 | 43462510.14 | 0.00 | 6414260.57 | 2395648.11 | 0.00 | 0.422947E+10 | 0.00 | 0.54 |
August | 0.570987E+09 | 3533.16 | 0.00 | 9304296.79 | 0.00 | 0.00 | 0.554866E+10 | 0.00 | 0.63 |
September | 0.245853E+10 | 0.00 | 0.00 | 5006703.60 | 0.00 | 0.00 | 0.341633E+10 | 0.00 | 0.50 |
October | 0.609471E+10 | 0.00 | 0.00 | 109198.91 | 0.00 | 0.757319E+09 | 0.146776E+09 | 0.00 | 0.38 |
November | 0.444909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408371E+10 | 0.00 | 0.00 | 0.38 |
December | 0.192595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834849E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.441728E+11 | 64578512.45 | 0.00 | 25243739.27 | 3662989.45 | 0.312100E+11 | 0.164490E+11 | 0.00 | 0.43 |
Minimum of Months | 0.570987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.609471E+10 | 43462510.14 | 0.00 | 9304296.79 | 2395648.11 | 0.834849E+10 | 0.554866E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377453E+10 | 0.00 | 0.00 | 0.38 |
February | 0.159798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290172E+10 | 0.00 | 0.00 | 0.38 |
March | 0.196184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264526E+10 | 0.00 | 0.00 | 0.39 |
April | 0.283980E+10 | 0.00 | 0.00 | 436027.54 | 454761.84 | 0.301126E+09 | 0.240913E+09 | 0.00 | 0.38 |
May | 0.294703E+10 | 0.00 | 0.00 | 541525.25 | 0.00 | 61679159.02 | 0.449081E+09 | 0.00 | 0.38 |
June | 0.166746E+10 | 9387306.83 | 0.00 | 1734080.76 | 0.00 | 0.00 | 0.108056E+10 | 0.00 | 0.39 |
July | 0.629836E+09 | 19762233.09 | 0.00 | 3479893.87 | 1020120.11 | 0.00 | 0.156823E+10 | 0.00 | 0.38 |
August | 0.171718E+09 | 0.00 | 0.00 | 4895189.89 | 0.00 | 0.00 | 0.180660E+10 | 0.00 | 0.39 |
September | 0.865719E+09 | 0.00 | 0.00 | 2969517.93 | 0.00 | 0.00 | 0.166913E+10 | 0.00 | 0.38 |
October | 0.286920E+10 | 0.00 | 0.00 | 109515.00 | 0.00 | 0.511978E+09 | 0.155593E+09 | 0.00 | 0.38 |
November | 0.194377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231005E+10 | 0.00 | 0.00 | 0.38 |
December | 0.826259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429697E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.197035E+11 | 29149539.92 | 0.00 | 14165750.23 | 1474881.95 | 0.168033E+11 | 0.697010E+10 | 0.00 | 0.38 |
Minimum of Months | 0.171718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.294703E+10 | 19762233.09 | 0.00 | 4895189.89 | 1020120.11 | 0.429697E+10 | 0.180660E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389198E+10 | 0.00 | 0.00 | 0.38 |
February | 0.147402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302568E+10 | 0.00 | 0.00 | 0.38 |
March | 0.188447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272257E+10 | 0.00 | 0.00 | 0.39 |
April | 0.281642E+10 | 0.00 | 0.00 | 417644.94 | 481585.92 | 0.320981E+09 | 0.236684E+09 | 0.00 | 0.38 |
May | 0.293619E+10 | 0.00 | 0.00 | 509452.82 | 0.00 | 77869855.34 | 0.434593E+09 | 0.00 | 0.38 |
June | 0.172715E+10 | 9225630.75 | 0.00 | 1643768.72 | 0.00 | 0.00 | 0.101262E+10 | 0.00 | 0.39 |
July | 0.655591E+09 | 19664849.59 | 0.00 | 3369267.69 | 1036191.74 | 0.00 | 0.154352E+10 | 0.00 | 0.38 |
August | 0.184691E+09 | 0.00 | 0.00 | 4765289.01 | 0.00 | 0.00 | 0.179924E+10 | 0.00 | 0.39 |
September | 0.916052E+09 | 0.00 | 0.00 | 2855488.48 | 0.00 | 0.00 | 0.161730E+10 | 0.00 | 0.38 |
October | 0.279960E+10 | 0.00 | 0.00 | 95942.59 | 0.00 | 0.597748E+09 | 0.130919E+09 | 0.00 | 0.38 |
November | 0.187280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238078E+10 | 0.00 | 0.00 | 0.38 |
December | 0.780329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434303E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.193127E+11 | 28890480.34 | 0.00 | 13656854.25 | 1517777.67 | 0.173606E+11 | 0.677487E+10 | 0.00 | 0.38 |
Minimum of Months | 0.184691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.293619E+10 | 19664849.59 | 0.00 | 4765289.01 | 1036191.74 | 0.434303E+10 | 0.179924E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.899494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425791E+10 | 0.00 | 0.00 | 0.38 |
February | 0.104442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345537E+10 | 0.00 | 0.00 | 0.38 |
March | 0.144708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315958E+10 | 0.00 | 0.00 | 0.39 |
April | 0.269311E+10 | 0.00 | 0.00 | 356146.49 | 588947.97 | 0.447511E+09 | 0.207256E+09 | 0.00 | 0.38 |
May | 0.282522E+10 | 0.00 | 0.00 | 373052.51 | 0.00 | 0.213869E+09 | 0.373841E+09 | 0.00 | 0.38 |
June | 0.195657E+10 | 8805866.95 | 0.00 | 1307741.89 | 0.00 | 702879.61 | 0.735987E+09 | 0.00 | 0.39 |
July | 0.769033E+09 | 19415702.17 | 0.00 | 2984537.01 | 1072134.82 | 0.00 | 0.142540E+10 | 0.00 | 0.38 |
August | 0.251945E+09 | 0.00 | 0.00 | 4331003.50 | 0.00 | 0.00 | 0.174840E+10 | 0.00 | 0.39 |
September | 0.115309E+10 | 0.00 | 0.00 | 2392812.77 | 0.00 | 0.00 | 0.136049E+10 | 0.00 | 0.38 |
October | 0.266075E+10 | 0.00 | 0.00 | 53050.31 | 0.00 | 0.763084E+09 | 69102075.17 | 0.00 | 0.38 |
November | 0.150769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274541E+10 | 0.00 | 0.00 | 0.38 |
December | 0.431072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469243E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.176395E+11 | 28221569.12 | 0.00 | 11798344.48 | 1661082.78 | 0.197359E+11 | 0.592049E+10 | 0.00 | 0.38 |
Minimum of Months | 0.251945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.282522E+10 | 19415702.17 | 0.00 | 4331003.50 | 1072134.82 | 0.469243E+10 | 0.174840E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504195E+10 | 0.00 | 0.00 | 0.38 |
February | 96872886.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438910E+10 | 0.00 | 0.00 | 0.38 |
March | 0.317964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427671E+10 | 0.00 | 0.00 | 0.39 |
April | 0.220670E+10 | 0.00 | 0.00 | 310813.40 | 811539.46 | 0.908978E+09 | 0.190049E+09 | 0.00 | 0.38 |
May | 0.244035E+10 | 0.00 | 0.00 | 239630.48 | 0.00 | 0.695161E+09 | 0.202243E+09 | 0.00 | 0.38 |
June | 0.206229E+10 | 8921294.68 | 0.00 | 1045181.43 | 0.00 | 17721798.11 | 0.487675E+09 | 0.00 | 0.39 |
July | 0.921710E+09 | 20406816.10 | 0.00 | 2443337.28 | 1064050.25 | 662474.52 | 0.122975E+10 | 0.00 | 0.38 |
August | 0.376980E+09 | 0.00 | 0.00 | 3708677.50 | 0.00 | 0.00 | 0.160762E+10 | 0.00 | 0.39 |
September | 0.141513E+10 | 0.00 | 0.00 | 1836569.04 | 0.00 | 862809.52 | 0.100291E+10 | 0.00 | 0.38 |
October | 0.193055E+10 | 0.00 | 0.00 | 26041.52 | 0.00 | 0.145651E+10 | 32713639.18 | 0.00 | 0.38 |
November | 0.480445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375061E+10 | 0.00 | 0.00 | 0.38 |
December | 19304803.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508124E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.123769E+11 | 29328110.79 | 0.00 | 9610250.65 | 1875589.71 | 0.256195E+11 | 0.475296E+10 | 0.00 | 0.38 |
Minimum of Months | 19304803.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.244035E+10 | 20406816.10 | 0.00 | 3708677.50 | 1064050.25 | 0.508124E+10 | 0.160762E+10 | 0.00 | 0.39 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.721925E+11 | 0.257274E+11 | 0.00 | 0.702513E+11 | 0.147520E+11 |
February | 0.123854E+12 | 0.230285E+11 | 0.00 | 0.615650E+11 | 0.118740E+11 |
March | 0.163902E+12 | 0.222639E+11 | 0.00 | 0.623637E+11 | 0.107535E+11 |
April | 0.452695E+12 | 0.167152E+11 | 0.00 | 0.476425E+11 | 0.477460E+10 |
May | 0.548416E+12 | 0.194415E+11 | 0.00 | 0.488430E+11 | 0.323593E+10 |
June | 0.563024E+12 | 0.147421E+11 | 0.00 | 0.430370E+11 | 0.119112E+11 |
July | 0.572696E+12 | 0.123808E+11 | 0.00 | 0.431180E+11 | 0.219595E+11 |
August | 0.467696E+12 | 0.102358E+11 | 0.00 | 0.447735E+11 | 0.250593E+11 |
September | 0.339041E+12 | 0.132186E+11 | 0.00 | 0.443375E+11 | 0.132465E+11 |
October | 0.141340E+12 | 0.184782E+11 | 0.00 | 0.486566E+11 | 0.295507E+10 |
November | 0.456718E+11 | 0.230136E+11 | 0.00 | 0.578796E+11 | 0.936574E+10 |
December | 0.389651E+10 | 0.282758E+11 | 0.00 | 0.700379E+11 | 0.160523E+11 |
Annual Sum or Average | 0.349442E+13 | 0.227521E+12 | 0.00 | 0.642505E+12 | 0.145940E+12 |
Minimum of Months | 0.389651E+10 | 0.102358E+11 | 0.00 | 0.430370E+11 | 0.295507E+10 |
Maximum of Months | 0.572696E+12 | 0.282758E+11 | 0.00 | 0.702513E+11 | 0.250593E+11 |