Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:36:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1305.75 | 624.67 | 624.67 |
Net Site Energy | 1305.75 | 624.67 | 624.67 |
Total Source Energy | 4120.40 | 1971.18 | 1971.18 |
Net Source Energy | 4120.40 | 1971.18 | 1971.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 7.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 508.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1298.59 | 7.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 7.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 508.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 135.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 7.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 508.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 135.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 335.86 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 621.24 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 335.86 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 621.24 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1298.590 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1298.590 | 100.00 |
Total On-Site and Utility Electric Sources | 1298.590 | 100.00 |
Total Electricity End Uses | 1298.590 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1390.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 01-JUL-12:00 | 02-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 120561.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84682.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13455.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7529.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 139987.70 | 120561.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 120561.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 84682.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13455.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7529.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1609.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 428.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4112.63 | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 770.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1967.47 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 770.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1967.47 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.87 |
SMSTORE1 DIRECT AIR | 1.47 |
SMSTORE2 DIRECT AIR | 1.47 |
SMSTORE3 DIRECT AIR | 1.47 |
SMSTORE4 DIRECT AIR | 1.47 |
LGSTORE2 DIRECT AIR | 2.61 |
SMSTORE5 DIRECT AIR | 1.38 |
SMSTORE6 DIRECT AIR | 1.37 |
SMSTORE7 DIRECT AIR | 1.38 |
SMSTORE8 DIRECT AIR | 1.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 1.00 | 1.00 | 2.87 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
PSZ-AC_3:3 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
PSZ-AC_4:4 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
PSZ-AC_5:5 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
PSZ-AC_6:6 | 2.61 | 2.61 | 2.61 | 2.61 | 2.61 | 2.61 | 1.00 | 1.00 | 2.61 |
PSZ-AC_7:7 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_8:8 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_9:9 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_10:10 | 1.60 | 1.60 | 1.60 | 1.60 | 1.60 | 1.60 | 1.00 | 1.00 | 1.60 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.87 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.61 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.38 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.37 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.38 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.60 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.87 | 3074.92 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1574.11 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1574.47 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1578.02 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1569.21 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.61 | 2787.78 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1524.48 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1519.14 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1526.63 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.60 | 1717.39 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.87 | 2.87 | 2.87 | 1.90 | 66050.11 | 71216.77 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.970903 | 33726.79 | 36371.71 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.971123 | 33733.16 | 36379.16 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.973315 | 33794.62 | 36453.16 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.967881 | 33642.32 | 36269.71 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.61 | 2.61 | 2.61 | 1.72 | 61026.66 | 65237.64 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.908775 | 31982.20 | 34274.27 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.905592 | 31892.58 | 34166.80 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.910055 | 32018.62 | 34317.48 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.60 | 1.60 | 1.60 | 1.06 | 35944.29 | 39355.31 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.87 | 1.44 | 1.92 | 66050.11 | 33025.06 | 0.725780 | 0.725780 |
PSZ-AC_2:2 COOLING COIL | 1.47 | 0.735532 | 0.980707 | 33726.79 | 16863.40 | 0.726450 | 0.726450 |
PSZ-AC_3:3 COOLING COIL | 1.47 | 0.735699 | 0.980933 | 33733.16 | 16866.58 | 0.726460 | 0.726460 |
PSZ-AC_4:4 COOLING COIL | 1.47 | 0.737360 | 0.983147 | 33794.62 | 16897.31 | 0.726580 | 0.726580 |
PSZ-AC_5:5 COOLING COIL | 1.47 | 0.733243 | 0.977660 | 33642.32 | 16821.16 | 0.726290 | 0.726290 |
PSZ-AC_6:6 COOLING COIL | 2.61 | 1.30 | 1.74 | 61026.66 | 30513.33 | 0.719820 | 0.719820 |
PSZ-AC_7:7 COOLING COIL | 1.38 | 0.688466 | 0.917953 | 31982.20 | 15991.10 | 0.722020 | 0.722020 |
PSZ-AC_8:8 COOLING COIL | 1.37 | 0.686054 | 0.914740 | 31892.58 | 15946.29 | 0.721840 | 0.721840 |
PSZ-AC_9:9 COOLING COIL | 1.38 | 0.689436 | 0.919247 | 32018.62 | 16009.31 | 0.722090 | 0.722090 |
PSZ-AC_10:10 COOLING COIL | 1.60 | 0.802481 | 1.07 | 35944.29 | 17972.15 | 0.734750 | 0.734750 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 71216.77 |
PSZ-AC_2:2 HEATING COIL | 36371.71 |
PSZ-AC_3:3 HEATING COIL | 36379.16 |
PSZ-AC_4:4 HEATING COIL | 36453.16 |
PSZ-AC_5:5 HEATING COIL | 36269.71 |
PSZ-AC_6:6 HEATING COIL | 65237.64 |
PSZ-AC_7:7 HEATING COIL | 34274.27 |
PSZ-AC_8:8 HEATING COIL | 34166.80 |
PSZ-AC_9:9 HEATING COIL | 34317.48 |
PSZ-AC_10:10 HEATING COIL | 39355.31 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 35 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 31718.92600 | 38062.71120 | 2.39469 | 2.87363 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 15311.95795 | 18374.34955 | 0.67719 | 0.81262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 16237.55791 | 19485.06949 | 1.22589 | 1.47106 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7535.15742 | 9042.18890 | 0.33325 | 0.39990 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 16241.24578 | 19489.49493 | 1.22617 | 1.47140 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7603.64402 | 9124.37282 | 0.33628 | 0.40353 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 16277.90151 | 19533.48181 | 1.22893 | 1.47472 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7674.31345 | 9209.17614 | 0.33940 | 0.40728 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 16187.02869 | 19424.43443 | 1.22207 | 1.46649 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7823.04562 | 9387.65474 | 0.34598 | 0.41518 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 28757.12638 | 34508.55165 | 2.17107 | 2.60529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14843.63639 | 17812.36367 | 0.65648 | 0.78777 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 15198.53126 | 18238.23752 | 1.14744 | 1.37693 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8038.84710 | 9646.61652 | 0.35552 | 0.42663 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 15145.29688 | 18174.35626 | 1.14342 | 1.37211 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8042.15191 | 9650.58229 | 0.35567 | 0.42680 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 15219.93890 | 18263.92668 | 1.14906 | 1.37887 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8292.33038 | 9950.79645 | 0.36673 | 0.44008 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 17716.05619 | 21259.26742 | 1.33747 | 1.60496 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.15709E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9795.48758 | 11754.58509 | 0.43321 | 0.51985 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 46360.00 | 2.87363 | 2.87363 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 25294.01 | 0.81262 | 0.81262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23631.86 | 1.47106 | 1.47106 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12504.11 | 0.39990 | 0.39990 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 23636.23 | 1.47140 | 1.47140 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12585.09 | 0.40353 | 0.40353 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 23679.65 | 1.47472 | 1.47472 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12668.66 | 0.40728 | 0.40728 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 23572.00 | 1.46649 | 1.46649 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12844.54 | 0.41518 | 0.41518 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 42858.36 | 2.60529 | 2.60529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 24740.22 | 0.78777 | 0.78777 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 22399.74 | 1.37693 | 1.37693 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13099.73 | 0.42663 | 0.42663 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 22336.62 | 1.37211 | 1.37211 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13103.64 | 0.42680 | 0.42680 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 22424.16 | 1.37887 | 1.37887 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13399.48 | 0.44008 | 0.44008 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 25271.61 | 1.60496 | 1.60496 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15176.98 | 0.51985 | 0.51985 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.87363 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.47106 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.47140 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.47472 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46649 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.60529 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37693 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37211 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37887 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.60496 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87363 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87363 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.87363 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.87363 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.87363 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.87363 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.47106 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47106 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.47106 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47106 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.47106 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.47106 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.47140 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47140 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.47140 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47140 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.47140 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.47140 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.47472 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47472 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.47472 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47472 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.47472 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.47472 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46649 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46649 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46649 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46649 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46649 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46649 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60529 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.60529 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.60529 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.60529 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.60529 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.60529 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37693 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37693 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37693 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37693 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37693 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37693 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37211 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37211 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37211 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37211 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37211 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37211 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37887 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37887 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37887 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37887 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37887 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37887 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.60496 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60496 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.60496 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60496 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.60496 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.60496 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.87363 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.47106 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.47140 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.47472 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.46649 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.60529 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.37693 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.37211 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.37887 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.60496 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.87363 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.87363 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3074.91547 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.87363 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.87363 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.87363 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.89659 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.87363 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43681 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.91575 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66050.11000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33025.05500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72578 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72578 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66050.11000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71216.76534 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 71216.76534 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.47106 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.47106 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1574.10875 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.47106 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.47106 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.47106 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97090 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.47106 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73553 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98071 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33726.79000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16863.39500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72645 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72645 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33726.79000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36371.70526 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 36371.70526 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.47140 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.47140 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1574.46594 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.47140 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.47140 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.47140 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97112 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.47140 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73570 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98093 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33733.16000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16866.58000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72646 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72646 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33733.16000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36379.16023 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 36379.16023 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.47472 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.47472 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1578.01939 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.47472 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.47472 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.47472 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97331 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.47472 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73736 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98315 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33794.62000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16897.31000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72658 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72658 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33794.62000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36453.15659 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 36453.15659 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46649 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46649 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1569.20980 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46649 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46649 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46649 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96788 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46649 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73324 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97766 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33642.32000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16821.16000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72629 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72629 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33642.32000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36269.71144 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 36269.71144 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.60529 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.60529 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2787.77909 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.60529 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.60529 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.60529 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.71949 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.60529 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.30264 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.73686 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61026.66000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30513.33000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71982 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71982 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61026.66000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65237.64409 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 65237.64409 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37693 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37693 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1524.48207 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37693 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37693 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37693 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90877 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37693 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68847 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91795 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31982.20000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15991.10000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72202 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72202 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31982.20000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34274.26585 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 34274.26585 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37211 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37211 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1519.14245 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37211 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37211 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37211 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90559 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37211 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68605 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91474 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31892.58000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15946.29000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72184 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72184 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31892.58000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34166.80371 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 34166.80371 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37887 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37887 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1526.62909 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37887 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37887 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37887 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91005 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37887 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68944 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91925 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32018.62000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16009.31000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72209 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72209 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32018.62000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34317.47697 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 34317.47697 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.60496 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.60496 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1717.38567 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.60496 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.60496 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.60496 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05928 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.60496 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80248 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06997 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35944.29000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17972.14500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73475 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73475 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35944.29000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39355.31083 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 39355.31083 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 63786.4 | 11.63 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 32568.0 | 11.80 | 11.80 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 32574.1 | 11.80 | 11.80 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 32633.0 | 11.80 | 11.80 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 32487.1 | 11.80 | 11.80 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 58973.6 | 11.67 | 11.67 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 30897.3 | 11.83 | 11.83 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 30811.5 | 11.83 | 11.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 30932.2 | 11.83 | 11.83 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 34680.6 | 11.76 | 11.76 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.4658534398E-002 | 0.1169500398 | Pass | Pass | 7.6405191068E-002 | 0.1736243956 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.9038523835E-002 | 0.1023258986 | Pass | Pass | 9.8681187657E-002 | 0.3209871274 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.0577843468E-002 | 0.1055014600 | Pass | Pass | 0.1112890144 | 0.3935273604 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8771798629E-002 | 0.1463902737 | Pass | Pass | 0.1489563691 | 0.5207467165 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.5758679203E-002 | 0.1619656090 | Pass | Pass | 0.5183678219 | 3.4647229726 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.1765528308E-002 | 0.1994978505 | Pass | Pass | 0.5294477399 | 3.6821276895 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.3675461568E-002 | 0.2061419869 | Pass | Pass | 0.5378894922 | 2.8286163196 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.1961832759E-002 | 0.2096776535 | Pass | Pass | 0.6154778205 | 3.0869357184 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.9593035334E-002 | 0.2263567992 | Pass | Pass | 0.2713746459 | 1.1077586498 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.6862678957E-002 | 0.2830609383 | Pass | Pass | 0.1330308492 | 0.3106988739 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2601.15 | -286.2 | 0.00 | -621.6 | 2424.15 | 4117.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 3.235 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 3.235 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.75 | 41.75 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.75 | 62.75 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.75 | 55.75 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66050.11 | 47937.85 | 18112.26 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33726.79 | 24500.83 | 9225.96 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33733.16 | 24505.79 | 9227.37 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33794.62 | 24554.49 | 9240.13 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33642.32 | 24434.08 | 9208.24 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61026.66 | 43928.21 | 17098.45 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31982.20 | 23091.79 | 8890.41 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31892.58 | 23021.34 | 8871.24 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32018.62 | 23120.33 | 8898.29 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35944.29 | 26410.07 | 9534.22 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 63786.4 | 11.63 | 11.63 | ||||
PSZ-AC_2:2 COOLING COIL | 32568.0 | 11.80 | 11.80 | ||||
PSZ-AC_3:3 COOLING COIL | 32574.1 | 11.80 | 11.80 | ||||
PSZ-AC_4:4 COOLING COIL | 32633.0 | 11.80 | 11.80 | ||||
PSZ-AC_5:5 COOLING COIL | 32487.1 | 11.80 | 11.80 | ||||
PSZ-AC_6:6 COOLING COIL | 58973.6 | 11.67 | 11.67 | ||||
PSZ-AC_7:7 COOLING COIL | 30897.3 | 11.83 | 11.83 | ||||
PSZ-AC_8:8 COOLING COIL | 30811.5 | 11.83 | 11.83 | ||||
PSZ-AC_9:9 COOLING COIL | 30932.2 | 11.83 | 11.83 | ||||
PSZ-AC_10:10 COOLING COIL | 34680.6 | 11.76 | 11.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 71216.77 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 36371.71 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 36379.16 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 36453.16 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 36269.71 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 65237.64 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 34274.27 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 34166.80 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 34317.48 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 39355.31 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.87 | 3074.92 | 1070.05 | 1.00 | 1.27 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1574.11 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1574.47 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1578.02 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1569.21 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.61 | 2787.78 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1524.48 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1519.14 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1526.63 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.60 | 1717.39 | 1070.05 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 31718.93 | 38062.71 | 109.25 | 2.395 | 2.874 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 23.89 | 23.89 | 0.00764 | 41.90 | 0.00916 | 0.411 | 0.00 |
SMSTORE1 | 16237.56 | 19485.07 | 111.86 | 1.226 | 1.471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00765 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE2 | 16241.25 | 19489.49 | 111.88 | 1.226 | 1.471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00765 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE3 | 16277.90 | 19533.48 | 112.14 | 1.229 | 1.475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00764 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE4 | 16187.03 | 19424.43 | 111.51 | 1.222 | 1.466 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00765 | 42.00 | 0.00916 | 0.206 | 0.00 |
LGSTORE2 | 28757.13 | 34508.55 | 99.05 | 2.171 | 2.605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00769 | 41.92 | 0.00916 | 0.411 | 0.00 |
SMSTORE5 | 15198.53 | 18238.24 | 104.70 | 1.147 | 1.377 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00768 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE6 | 15145.30 | 18174.36 | 104.33 | 1.143 | 1.372 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00768 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE7 | 15219.94 | 18263.93 | 104.85 | 1.149 | 1.379 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00768 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE8 | 17716.06 | 21259.27 | 122.04 | 1.337 | 1.605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00761 | 41.52 | 0.00916 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15311.96 | 18374.35 | 52.74 | 0.677 | 0.813 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00736 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 7535.16 | 9042.19 | 51.91 | 0.333 | 0.400 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 7603.64 | 9124.37 | 52.38 | 0.336 | 0.404 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7674.31 | 9209.18 | 52.87 | 0.339 | 0.407 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7823.05 | 9387.65 | 53.89 | 0.346 | 0.415 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 14843.64 | 17812.36 | 51.13 | 0.656 | 0.788 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 8038.85 | 9646.62 | 55.38 | 0.356 | 0.427 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 8042.15 | 9650.58 | 55.40 | 0.356 | 0.427 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 8292.33 | 9950.80 | 57.13 | 0.367 | 0.440 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00733 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 9795.49 | 11754.59 | 67.48 | 0.433 | 0.520 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00738 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.87 | 2.87 | 0.81 | 0.81 | 2.8736 | 2.8736 | 2.8736 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.47 | 1.47 | 0.40 | 0.40 | 1.4711 | 1.4711 | 1.4711 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.47 | 1.47 | 0.40 | 0.40 | 1.4714 | 1.4714 | 1.4714 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.47 | 1.47 | 0.41 | 0.41 | 1.4747 | 1.4747 | 1.4747 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.47 | 1.47 | 0.42 | 0.42 | 1.4665 | 1.4665 | 1.4665 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.61 | 2.61 | 0.79 | 0.79 | 2.6053 | 2.6053 | 2.6053 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.38 | 1.38 | 0.43 | 0.43 | 1.3769 | 1.3769 | 1.3769 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.37 | 1.37 | 0.43 | 0.43 | 1.3721 | 1.3721 | 1.3721 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.38 | 1.38 | 0.44 | 0.44 | 1.3789 | 1.3789 | 1.3789 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.60 | 1.60 | 0.52 | 0.52 | 1.6050 | 1.6050 | 1.6050 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 66050.110 | 47937.849 | 2.873630 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 33025.06 | 29678.38 | 1.915753 | 27.38 | 16.76 | 0.00785547 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4787 | 23.89 | 0.00763776 | 40.4068 | 31712.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 71216.765 | 71216.765 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 71216.77 | 71216.77 | 2.873626 | 18.99 | 13.07 | 0.00717686 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3192 | 21.11 | 0.00736144 | 46.1276 | 15311.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33726.790 | 24500.827 | 1.471060 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16863.40 | 15147.15 | 0.980707 | 27.31 | 16.74 | 0.00785686 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.9787 | 23.89 | 0.00764531 | 40.4463 | 16237.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 36371.705 | 36371.705 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36371.71 | 36371.71 | 1.471065 | 19.04 | 13.03 | 0.00712217 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.9857 | 21.11 | 0.00729287 | 45.7031 | 7535.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 33733.160 | 24505.791 | 1.471400 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16866.58 | 15150.15 | 0.980933 | 27.31 | 16.74 | 0.00785675 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.9738 | 23.89 | 0.00764524 | 40.4459 | 16241.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 36379.160 | 36379.160 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36379.16 | 36379.16 | 1.471398 | 19.04 | 13.03 | 0.00712413 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.9826 | 21.11 | 0.00729511 | 45.7171 | 7603.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 33794.620 | 24554.495 | 1.474720 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16897.31 | 15180.06 | 0.983147 | 27.31 | 16.74 | 0.00785522 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.9266 | 23.89 | 0.00764402 | 40.4395 | 16277.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 36453.157 | 36453.157 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36453.16 | 36453.16 | 1.474719 | 19.04 | 13.04 | 0.00712736 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.9511 | 21.11 | 0.00729841 | 45.7375 | 7674.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 33642.320 | 24434.081 | 1.466490 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16821.16 | 15105.91 | 0.977660 | 27.32 | 16.74 | 0.00785905 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.0441 | 23.89 | 0.00764709 | 40.4556 | 16187.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 36269.711 | 36269.711 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36269.71 | 36269.71 | 1.466486 | 19.03 | 13.04 | 0.00713258 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.0294 | 21.11 | 0.00730560 | 45.7821 | 7823.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 61026.660 | 43928.210 | 2.605290 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 30513.33 | 27257.56 | 1.736860 | 27.64 | 16.90 | 0.00791867 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.6910 | 23.89 | 0.00768623 | 40.6601 | 28756.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 65237.644 | 65237.644 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 65237.64 | 65237.64 | 2.605286 | 18.77 | 12.96 | 0.00715173 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.7940 | 21.11 | 0.00735419 | 46.0825 | 14843.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 31982.200 | 23091.788 | 1.376930 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 15991.10 | 14301.20 | 0.917953 | 27.52 | 16.85 | 0.00790311 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.4128 | 23.89 | 0.00768266 | 40.6415 | 15197.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 34274.266 | 34274.266 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34274.27 | 34274.27 | 1.376932 | 18.90 | 12.98 | 0.00712963 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.9419 | 21.11 | 0.00731536 | 45.8426 | 8038.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 31892.580 | 23021.340 | 1.372110 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 15946.29 | 14257.70 | 0.914740 | 27.53 | 16.85 | 0.00790560 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.4916 | 23.89 | 0.00768469 | 40.6521 | 15144.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 34166.804 | 34166.804 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34166.80 | 34166.80 | 1.372109 | 18.89 | 12.98 | 0.00712913 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.9944 | 21.11 | 0.00731555 | 45.8437 | 8042.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 32018.620 | 23120.325 | 1.378870 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 16009.31 | 14318.80 | 0.919247 | 27.51 | 16.85 | 0.00790216 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.3813 | 23.89 | 0.00768190 | 40.6375 | 15218.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 34317.477 | 34317.477 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34317.48 | 34317.48 | 1.378871 | 18.90 | 12.99 | 0.00713938 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.9209 | 21.11 | 0.00732652 | 45.9117 | 8292.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 35944.290 | 26410.067 | 1.604960 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 17972.15 | 16211.89 | 1.069973 | 27.05 | 16.61 | 0.00780994 | 12.80 | 10.34 | 0.00700000 | 41.60 | 0.00915722 | 22.15 | 19.2285 | 23.89 | 0.00761169 | 40.2707 | 17704.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 39355.311 | 39355.311 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39355.31 | 39355.31 | 1.604962 | 19.21 | 13.18 | 0.00721026 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 12.8190 | 21.11 | 0.00737758 | 46.2283 | 9795.49 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66050.110 | 47937.849 | 2.873630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4429 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.873626 | 3.37302021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | Sensible | 33025.06 | 29678.38 | 1.0000 | 2.24868341 | 1.915753 | 27.38 | 16.76 | 0.00785547 | 47553.3 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33025.06 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 21.4787 | 23.89 | 0.00763776 | 23.89 | 0.00763776 | 40.4068 | 31712.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71216.765 | 71216.765 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.873626 | 3.37302021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 71216.77 | 71216.77 | 1.0000 | 3.37302021 | 2.873626 | 18.99 | 13.07 | 0.00717686 | 37282.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71216.77 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 14.3192 | 21.11 | 0.00736144 | 21.11 | 0.00736144 | 46.1276 | 15311.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33726.790 | 24500.827 | 1.471060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4455 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.471065 | 1.72671434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16863.40 | 15147.15 | 1.0000 | 1.15113923 | 0.980707 | 27.31 | 16.74 | 0.00785686 | 47494.8 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16863.40 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 20.9787 | 23.89 | 0.00764531 | 23.89 | 0.00764531 | 40.4463 | 16237.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36371.705 | 36371.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.471065 | 1.72671434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36371.71 | 36371.71 | 1.0000 | 1.72671434 | 1.471065 | 19.04 | 13.03 | 0.00712217 | 37194.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36371.71 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 13.9857 | 21.11 | 0.00729287 | 21.11 | 0.00729287 | 45.7031 | 7535.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33733.160 | 24505.791 | 1.471400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4453 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.471398 | 1.72710616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16866.58 | 15150.15 | 1.0000 | 1.15140528 | 0.980933 | 27.31 | 16.74 | 0.00785675 | 47493.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16866.58 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 20.9738 | 23.89 | 0.00764524 | 23.89 | 0.00764524 | 40.4459 | 16241.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36379.160 | 36379.160 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.471398 | 1.72710616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36379.16 | 36379.16 | 1.0000 | 1.72710616 | 1.471398 | 19.04 | 13.03 | 0.00712413 | 37199.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36379.16 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 13.9826 | 21.11 | 0.00729511 | 21.11 | 0.00729511 | 45.7171 | 7603.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33794.620 | 24554.495 | 1.474720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4425 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.474719 | 1.73100410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16897.31 | 15180.06 | 1.0000 | 1.15400326 | 0.983147 | 27.31 | 16.74 | 0.00785522 | 47484.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16897.31 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 20.9266 | 23.89 | 0.00764402 | 23.89 | 0.00764402 | 40.4395 | 16277.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36453.157 | 36453.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.474719 | 1.73100410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36453.16 | 36453.16 | 1.0000 | 1.73100410 | 1.474719 | 19.04 | 13.04 | 0.00712736 | 37212.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36453.16 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 13.9511 | 21.11 | 0.00729841 | 21.11 | 0.00729841 | 45.7375 | 7674.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33642.320 | 24434.081 | 1.466490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4496 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.466486 | 1.72134044 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16821.16 | 15105.91 | 1.0000 | 1.14756309 | 0.977660 | 27.32 | 16.74 | 0.00785905 | 47508.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16821.16 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.0441 | 23.89 | 0.00764709 | 23.89 | 0.00764709 | 40.4556 | 16187.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36269.711 | 36269.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.466486 | 1.72134044 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36269.71 | 36269.71 | 1.0000 | 1.72134044 | 1.466486 | 19.03 | 13.04 | 0.00713258 | 37213.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36269.71 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.0294 | 21.11 | 0.00730560 | 21.11 | 0.00730560 | 45.7821 | 7823.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61026.660 | 43928.210 | 2.605290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5604 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.605286 | 3.05804674 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 30513.33 | 27257.56 | 1.0000 | 2.03870101 | 1.736860 | 27.64 | 16.90 | 0.00791867 | 47986.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30513.33 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 23.6910 | 23.89 | 0.00768623 | 23.89 | 0.00768623 | 40.6601 | 28756.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65237.644 | 65237.644 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.605286 | 3.05804674 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 65237.64 | 65237.64 | 1.0000 | 3.05804674 | 2.605286 | 18.77 | 12.96 | 0.00715173 | 36996.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65237.64 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 15.7940 | 21.11 | 0.00735419 | 21.11 | 0.00735419 | 46.0825 | 14843.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31982.200 | 23091.788 | 1.376930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5315 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.376932 | 1.61622253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 15991.10 | 14301.20 | 1.0000 | 1.07748028 | 0.917953 | 27.52 | 16.85 | 0.00790311 | 47821.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15991.10 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.4128 | 23.89 | 0.00768266 | 23.89 | 0.00768266 | 40.6415 | 15197.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34274.266 | 34274.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.376932 | 1.61622253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34274.27 | 34274.27 | 1.0000 | 1.61622253 | 1.376932 | 18.90 | 12.98 | 0.00712963 | 37068.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34274.27 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.9419 | 21.11 | 0.00731536 | 21.11 | 0.00731536 | 45.8426 | 8038.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31892.580 | 23021.340 | 1.372110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5361 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.372109 | 1.61056157 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 15946.29 | 14257.70 | 1.0000 | 1.07370851 | 0.914740 | 27.53 | 16.85 | 0.00790560 | 47837.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15946.29 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.4916 | 23.89 | 0.00768469 | 23.89 | 0.00768469 | 40.6521 | 15144.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34166.804 | 34166.804 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.372109 | 1.61056157 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34166.80 | 34166.80 | 1.0000 | 1.61056157 | 1.372109 | 18.89 | 12.98 | 0.00712913 | 37059.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34166.80 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.9944 | 21.11 | 0.00731555 | 21.11 | 0.00731555 | 45.8437 | 8042.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32018.620 | 23120.325 | 1.378870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5297 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.378871 | 1.61849875 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 16009.31 | 14318.80 | 1.0000 | 1.07899837 | 0.919247 | 27.51 | 16.85 | 0.00790216 | 47814.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16009.31 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.3813 | 23.89 | 0.00768190 | 23.89 | 0.00768190 | 40.6375 | 15218.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34317.477 | 34317.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.378871 | 1.61849875 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34317.48 | 34317.48 | 1.0000 | 1.61849875 | 1.378871 | 18.90 | 12.99 | 0.00713938 | 37096.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34317.48 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.9209 | 21.11 | 0.00732652 | 21.11 | 0.00732652 | 45.9117 | 8292.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35944.290 | 26410.067 | 1.604960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3583 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.604962 | 1.88388157 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | Sensible | 17972.15 | 16211.89 | 1.0000 | 1.25591914 | 1.069973 | 27.05 | 16.61 | 0.00780994 | 47108.5 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17972.15 | 41.60 | 0.00915722 | 22.15 | 0.20573941 | 19.2285 | 23.89 | 0.00761169 | 23.89 | 0.00761169 | 40.2707 | 17704.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39355.311 | 39355.311 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.604962 | 1.88388157 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 39355.31 | 39355.31 | 1.0000 | 1.88388157 | 1.604962 | 19.21 | 13.18 | 0.00721026 | 37593.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39355.31 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 12.8190 | 21.11 | 0.00737758 | 21.11 | 0.00737758 | 46.2283 | 9795.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4199.50 | 1890.83 | 1177.33 |
SMSTORE1 | 4104.67 | 1397.67 | 909.83 |
SMSTORE2 | 3191.50 | 1454.00 | 1023.33 |
SMSTORE3 | 3167.67 | 1487.83 | 1015.67 |
SMSTORE4 | 3124.17 | 1565.17 | 1026.00 |
LGSTORE2 | 2762.17 | 1540.00 | 955.00 |
SMSTORE5 | 2688.33 | 1586.50 | 962.67 |
SMSTORE6 | 2676.83 | 1610.17 | 964.17 |
SMSTORE7 | 2670.33 | 1648.33 | 958.50 |
SMSTORE8 | 2756.83 | 1566.67 | 863.17 |
Facility | 4368.17 | 2482.67 | 1390.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 1.50 | 0.00 | 1.33 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 6.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 7.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 5.67 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 4.50 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 4.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 4.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 4.17 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 7.17 | 0.00 | 0.00 |
Facility | 0.00 | 14.17 | 0.00 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.848 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.684 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.848 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.848 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.775 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.775 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.774 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.80 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.06 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803557.28 | 0.00 | 8803557.28 | 3505960.47 | 12309517.75 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3563724.88 | 0.00 | 3563724.88 | 1952020.86 | 5515745.74 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525570.98 | 0.00 | 3525570.98 | 1960785.24 | 5486356.22 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525570.96 | 0.00 | 3525570.96 | 1960785.24 | 5486356.20 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525572.31 | 0.00 | 3525572.31 | 1960785.24 | 5486357.55 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510475.48 | 0.00 | 6510475.48 | 3452391.79 | 9962867.26 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255231.68 | 0.00 | 3255231.68 | 1964207.59 | 5219439.26 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255232.68 | 0.00 | 3255232.68 | 1964207.59 | 5219440.27 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255234.51 | 0.00 | 3255234.51 | 1964207.59 | 5219442.09 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255334.44 | 0.00 | 3255334.44 | 2060429.81 | 5315764.24 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 366.44 |
Total Facility | 42475505.20 | 0.00 | 42475505.20 | 22745781.39 | 65221286.59 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 731.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1614 | 0.5729 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1659 | 0.0000 | 0.1659 | 0.0910 | 0.2569 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2239 | 0.6354 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1299 | 0.3356 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4290 | 0.0000 | 2.4290 | 1.3490 | 3.7780 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12129228.48 | 0.00 | 12129228.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 4909972.35 | 0.00 | 4909972.35 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 8969873.66 | 0.00 | 8969873.66 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4485084.36 | 0.00 | 4485084.36 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 366.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2285 | 0.0000 | 0.2285 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5931.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4396.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5669 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2290 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
ElectricityPurchased:Plant | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
Cogeneration:ElectricityPurchased | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
General:Cogeneration:ElectricityPurchased | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
ElectricityNet:Plant | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
Cogeneration:ElectricityNet | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
General:Cogeneration:ElectricityNet | 1298.59 | 2102.83 | 01-JAN-07:40 | 139987.70 | 01-JUL-13:00 |
Electricity:HVAC | 643.40 | 0.00 | 01-JAN-00:10 | 100448.96 | 22-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 508.23 | 0.00 | 01-JAN-00:10 | 87259.27 | 10-JUN-16:00 |
General:Cooling:Electricity | 508.23 | 0.00 | 01-JAN-00:10 | 87259.27 | 10-JUN-16:00 |
Fans:Electricity | 135.17 | 0.00 | 01-JAN-00:10 | 13686.80 | 01-JUL-15:00 |
General:Fans:Electricity | 135.17 | 0.00 | 01-JAN-00:10 | 13686.80 | 01-JUL-15:00 |
ExteriorLights:Electricity | 60.04 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.04 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 58.65 | 1211.00 | 03-JAN-08:10 | 10441.96 | 21-JAN-12:50 |
WaterSystems:Electricity | 58.65 | 1211.00 | 03-JAN-08:10 | 10441.96 | 21-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 58.65 | 1211.00 | 03-JAN-08:10 | 10441.96 | 21-JAN-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 7.16 | 0.00 | 01-JAN-00:10 | 120561.66 | 02-JAN-08:10 |
NaturalGas:HVAC | 7.16 | 0.00 | 01-JAN-00:10 | 120561.66 | 02-JAN-08:10 |
Heating:NaturalGas | 7.16 | 0.00 | 01-JAN-00:10 | 120561.66 | 02-JAN-08:10 |
General:Heating:NaturalGas | 7.16 | 0.00 | 01-JAN-00:10 | 120561.66 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2961.76 | 0.00 | 01-JAN-00:10 | 451668.49 | 01-JUL-15:00 |
EnergyTransfer:Building | 1041.55 | 0.00 | 01-JAN-00:10 | 159548.65 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 212.53 | 0.00 | 01-JAN-00:10 | 27045.84 | 08-JUN-16:20 |
Heating:EnergyTransfer | 8.06 | 0.00 | 01-JAN-00:10 | 68346.26 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.31 | 0.00 | 01-JAN-00:10 | 10030.20 | 01-JAN-08:10 |
General:Heating:EnergyTransfer | 8.06 | 0.00 | 01-JAN-00:10 | 68346.26 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.31 | 0.00 | 01-JAN-00:10 | 10030.20 | 01-JAN-08:10 |
Cooling:EnergyTransfer | 1033.48 | 0.00 | 01-JAN-00:10 | 159548.65 | 12-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 212.22 | 0.00 | 01-JAN-00:10 | 27045.84 | 08-JUN-16:20 |
General:Cooling:EnergyTransfer | 1033.48 | 0.00 | 01-JAN-00:10 | 159548.65 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 212.22 | 0.00 | 01-JAN-00:10 | 27045.84 | 08-JUN-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 110.83 | 0.00 | 01-JAN-00:10 | 13164.21 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 1727.43 | 15-APR-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 1727.43 | 15-APR-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 110.72 | 0.00 | 01-JAN-00:10 | 13164.21 | 08-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 110.72 | 0.00 | 01-JAN-00:10 | 13164.21 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 87.19 | 0.00 | 01-JAN-00:10 | 13343.49 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.26 | 0.00 | 01-JAN-00:10 | 4824.93 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.26 | 0.00 | 01-JAN-00:10 | 4824.93 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 85.93 | 0.00 | 01-JAN-00:10 | 13343.49 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 85.93 | 0.00 | 01-JAN-00:10 | 13343.49 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 87.30 | 0.00 | 01-JAN-00:10 | 13462.58 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.26 | 0.00 | 01-JAN-00:10 | 6477.75 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.26 | 0.00 | 01-JAN-00:10 | 6477.75 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 86.03 | 0.00 | 01-JAN-00:10 | 13462.58 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 86.03 | 0.00 | 01-JAN-00:10 | 13462.58 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 85.22 | 0.00 | 01-JAN-00:10 | 13419.81 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.30 | 0.00 | 01-JAN-00:10 | 7028.90 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.30 | 0.00 | 01-JAN-00:10 | 7028.90 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 83.91 | 0.00 | 01-JAN-00:10 | 13419.81 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 83.91 | 0.00 | 01-JAN-00:10 | 13419.81 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 145.01 | 0.00 | 01-JAN-00:10 | 24939.51 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.13 | 0.00 | 01-JAN-00:10 | 15234.06 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.13 | 0.00 | 01-JAN-00:10 | 15234.06 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 143.88 | 0.00 | 01-JAN-00:10 | 24939.51 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 143.88 | 0.00 | 01-JAN-00:10 | 24939.51 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 75.50 | 0.00 | 01-JAN-00:10 | 13321.86 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.59 | 0.00 | 01-JAN-00:10 | 8078.13 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.59 | 0.00 | 01-JAN-00:10 | 8078.13 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 74.91 | 0.00 | 01-JAN-00:10 | 13321.86 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 74.91 | 0.00 | 01-JAN-00:10 | 13321.86 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE6 | 74.95 | 0.00 | 01-JAN-00:10 | 13297.38 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.60 | 0.00 | 01-JAN-00:10 | 8067.57 | 01-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.60 | 0.00 | 01-JAN-00:10 | 8067.57 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 74.35 | 0.00 | 01-JAN-00:10 | 13297.38 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 74.35 | 0.00 | 01-JAN-00:10 | 13297.38 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE7 | 74.85 | 0.00 | 01-JAN-00:10 | 13467.10 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.65 | 0.00 | 01-JAN-00:10 | 8760.95 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.65 | 0.00 | 01-JAN-00:10 | 8760.95 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 74.20 | 0.00 | 01-JAN-00:10 | 13467.10 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 74.20 | 0.00 | 01-JAN-00:10 | 13467.10 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 88.18 | 0.00 | 01-JAN-00:10 | 16368.06 | 12-JUN-12:20 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.86 | 0.00 | 01-JAN-00:10 | 11705.75 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.86 | 0.00 | 01-JAN-00:10 | 11705.75 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 87.33 | 0.00 | 01-JAN-00:10 | 16368.06 | 12-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 87.33 | 0.00 | 01-JAN-00:10 | 16368.06 | 12-JUN-12:20 |
EnergyTransfer:HVAC | 1920.21 | 0.00 | 01-JAN-00:10 | 325191.79 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 5.73 | 0.00 | 01-JAN-00:10 | 96449.33 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 1914.48 | 0.00 | 01-JAN-00:10 | 325191.79 | 01-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.309 | -212.218 | 0.000 | 0.000 | 23.336 | 95.826 | 26.249 | 22.410 | 0.000 | 25.287 | 28.627 | 0.000 | -4.866 | 0.000 | -4.960 | -0.003 |
SMSTORE1 | 0.000 | 0.000 | 0.107 | -110.721 | 0.000 | 0.000 | 11.633 | 57.583 | 13.125 | 11.238 | 0.000 | 14.230 | 8.074 | 0.000 | -2.506 | 0.000 | -2.763 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.258 | -85.931 | 0.000 | 0.000 | 6.998 | 40.956 | 10.421 | 11.058 | 0.000 | 14.028 | 6.556 | 0.000 | -2.565 | 0.000 | -2.778 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.264 | -86.033 | 0.000 | 0.000 | 7.001 | 40.956 | 10.421 | 11.049 | 0.000 | 14.023 | 6.634 | 0.000 | -2.554 | 0.000 | -2.760 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 1.303 | -83.911 | 0.000 | 0.000 | 7.007 | 40.956 | 10.421 | 11.073 | 0.000 | 14.028 | 4.368 | 0.000 | -2.516 | 0.000 | -2.728 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.127 | -143.877 | 0.000 | 0.000 | 24.071 | 43.277 | 19.173 | 22.240 | 0.000 | 24.617 | 18.930 | 0.000 | -4.836 | 0.000 | -4.721 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.590 | -74.907 | 0.000 | 0.000 | 12.039 | 22.197 | 9.586 | 11.157 | 0.000 | 14.041 | 10.352 | 0.000 | -2.397 | 0.000 | -2.659 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.600 | -74.345 | 0.000 | 0.000 | 12.042 | 22.197 | 9.586 | 11.166 | 0.000 | 14.042 | 9.742 | 0.000 | -2.385 | 0.000 | -2.647 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.650 | -74.201 | 0.000 | 0.000 | 12.051 | 22.197 | 9.586 | 11.163 | 0.000 | 14.041 | 9.489 | 0.000 | -2.362 | 0.000 | -2.614 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.858 | -87.324 | 0.000 | 0.000 | 12.055 | 22.197 | 9.586 | 11.035 | 0.000 | 14.370 | 22.345 | 0.000 | -2.300 | 0.000 | -2.822 | -0.002 |
Total Facility | 0.000 | 0.000 | 8.065 | -1033.466 | 0.000 | 0.000 | 128.234 | 408.342 | 128.154 | 133.588 | 0.000 | 162.705 | 125.116 | 0.000 | -29.286 | 0.000 | -31.452 | -0.009 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -55689.76 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 364.00 | 0.00 | 300.30 | 54876.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -28393.08 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 185.46 | 0.00 | 169.57 | 27963.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -29000.45 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 44.52 | 0.00 | 4.22 | 28877.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -29109.91 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 41.73 | 0.00 | 4.09 | 28989.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -28904.98 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 44.34 | 0.00 | 4.27 | 28782.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -51795.76 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 669.93 | 0.00 | 415.28 | 50561.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -27064.62 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 337.74 | 0.00 | 234.48 | 26418.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26990.21 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 337.82 | 0.00 | 234.50 | 26343.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -27109.73 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 335.90 | 0.00 | 233.15 | 26466.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -30974.32 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 319.39 | 0.00 | 265.81 | 30314.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -259741.92 | 0.00 | 0.00 | 295.51 | 450.00 | 1450.75 | 2273.97 | 0.00 | 2114.08 | 253157.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 64955.75 | 0.00 | 0.00 | 0.00 | 245.39 | 75.00 | 74.62 | 65.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -935.96 | -64479.83 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 8134.63 | 0.00 | 0.00 | 0.00 | 116.95 | 37.50 | 37.31 | 7.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -548.03 | -7785.60 |
SMSTORE2 | 01-JAN-08:62 | 0.00 | 0.00 | 22890.63 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.39 | 0.00 | -511.88 | -22432.17 |
SMSTORE3 | 01-JAN-08:62 | 0.00 | 0.00 | 31718.18 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9.58 | 0.00 | -510.13 | -31273.28 |
SMSTORE4 | 01-JAN-08:62 | 0.00 | 0.00 | 32459.71 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1.66 | 0.00 | -498.06 | -32034.80 |
LGSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 60662.19 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 668.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -717.02 | -60762.56 |
SMSTORE5 | 01-JAN-09:01 | 0.00 | 0.00 | 31978.33 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 335.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -408.83 | -31979.13 |
SMSTORE6 | 01-JAN-09:01 | 0.00 | 0.00 | 31893.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 337.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -405.68 | -31899.75 |
SMSTORE7 | 01-JAN-09:01 | 0.00 | 0.00 | 32102.42 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 343.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.74 | -32125.72 |
SMSTORE8 | 01-JAN-09:01 | 0.00 | 0.00 | 37010.73 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 363.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -371.08 | -37077.69 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 269985.56 | 0.00 | 0.00 | 0.00 | 709.16 | 450.00 | 1452.23 | 549.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5866.79 | -267279.70 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8736 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8736 | 0.1432 | 1.0000 | Not calculated | 0.4115 | 0.1432 | ||
PSZ-AC_2:2 | 1.4711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4711 | 0.1399 | 1.0000 | Not calculated | 0.2057 | 0.1399 | ||
PSZ-AC_3:3 | 1.4714 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4714 | 0.1398 | 1.0000 | Not calculated | 0.2057 | 0.1398 | ||
PSZ-AC_4:4 | 1.4747 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4747 | 0.1395 | 1.0000 | Not calculated | 0.2057 | 0.1395 | ||
PSZ-AC_5:5 | 1.4665 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4665 | 0.1403 | 1.0000 | Not calculated | 0.2057 | 0.1403 | ||
PSZ-AC_6:6 | 2.6053 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6053 | 0.1579 | 1.0000 | Not calculated | 0.4115 | 0.1579 | ||
PSZ-AC_7:7 | 1.3769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3769 | 0.1494 | 1.0000 | Not calculated | 0.2057 | 0.1494 | ||
PSZ-AC_8:8 | 1.3721 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3721 | 0.1499 | 1.0000 | Not calculated | 0.2057 | 0.1499 | ||
PSZ-AC_9:9 | 1.3789 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3789 | 0.1492 | 1.0000 | Not calculated | 0.2057 | 0.1492 | ||
PSZ-AC_10:10 | 1.6050 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6050 | 0.1282 | 1.0000 | Not calculated | 0.2057 | 0.1282 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8736 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8736 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1432 | ||
PSZ-AC_2:2 | 1.4711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4711 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1399 | ||
PSZ-AC_3:3 | 1.4714 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4714 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1398 | ||
PSZ-AC_4:4 | 1.4747 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4747 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1395 | ||
PSZ-AC_5:5 | 1.4665 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4665 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1403 | ||
PSZ-AC_6:6 | 2.6053 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6053 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1579 | ||
PSZ-AC_7:7 | 1.3769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3769 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1494 | ||
PSZ-AC_8:8 | 1.3721 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3721 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1499 | ||
PSZ-AC_9:9 | 1.3789 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3789 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1492 | ||
PSZ-AC_10:10 | 1.6050 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6050 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1282 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8736 | 2.8736 | 2.8736 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4711 | 1.4711 | 1.4711 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4714 | 1.4714 | 1.4714 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4747 | 1.4747 | 1.4747 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4665 | 1.4665 | 1.4665 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6053 | 2.6053 | 2.6053 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3769 | 1.3769 | 1.3769 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3721 | 1.3721 | 1.3721 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3789 | 1.3789 | 1.3789 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6050 | 1.6050 | 1.6050 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8736 | 2.8736 | 2.8736 | 2.8736 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4711 | 1.4711 | 1.4711 | 1.4711 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4714 | 1.4714 | 1.4714 | 1.4714 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4747 | 1.4747 | 1.4747 | 1.4747 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4665 | 1.4665 | 1.4665 | 1.4665 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6053 | 2.6053 | 2.6053 | 2.6053 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3769 | 1.3769 | 1.3769 | 1.3769 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3721 | 1.3721 | 1.3721 | 1.3721 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3789 | 1.3789 | 1.3789 | 1.3789 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6050 | 1.6050 | 1.6050 | 1.6050 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8736 | 2.8736 | 2.8736 | No | 0.4115 | 0.5064 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4711 | 1.4711 | 1.4711 | No | 0.2057 | 0.5145 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4714 | 1.4714 | 1.4714 | No | 0.2057 | 0.5098 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4747 | 1.4747 | 1.4747 | No | 0.2057 | 0.5052 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4665 | 1.4665 | 1.4665 | No | 0.2057 | 0.4955 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6053 | 2.6053 | 2.6053 | No | 0.4115 | 0.5223 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3769 | 1.3769 | 1.3769 | No | 0.2057 | 0.4822 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3721 | 1.3721 | 1.3721 | No | 0.2057 | 0.4820 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3789 | 1.3789 | 1.3789 | No | 0.2057 | 0.4675 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6050 | 1.6050 | 1.6050 | No | 0.2057 | 0.3958 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8736 | 2.8736 | 2.8736 | 2.8736 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4711 | 1.4711 | 1.4711 | 1.4711 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4714 | 1.4714 | 1.4714 | 1.4714 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4747 | 1.4747 | 1.4747 | 1.4747 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4665 | 1.4665 | 1.4665 | 1.4665 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6053 | 2.6053 | 2.6053 | 2.6053 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3769 | 1.3769 | 1.3769 | 1.3769 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3721 | 1.3721 | 1.3721 | 1.3721 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3789 | 1.3789 | 1.3789 | 1.3789 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6050 | 1.6050 | 1.6050 | 1.6050 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 1.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 7.16 | 120561.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 508.23 | 87259.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.04 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 135.17 | 13686.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.65 | 10441.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1298.59 |
Natural Gas | 0.00 | 7.16 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1305.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 243.14 |
Fans (All) | 64.66 |
Service Water Heating | 28.06 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 621.24 |
Subtotal | 621.24 |
Natural Gas [MJ/m2] | |
Space Heating | 3.43 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 3.43 |
Subtotal | 3.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.27 |
Space Heating | 0.55 |
Space Cooling | 38.92 |
Fans (All) | 10.35 |
Service Water Heating | 4.49 |
Receptacle Equipment | 9.81 |
Miscellaneous | 4.60 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8296.17 | 463.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8520.17 | 239.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7054.50 | 1700.67 | 4.83 | 0.00 | 0.00 |
SMSTORE3 | 6997.83 | 1754.50 | 7.67 | 0.00 | 0.00 |
SMSTORE4 | 7097.83 | 1655.33 | 6.83 | 0.00 | 0.00 |
LGSTORE2 | 7637.83 | 1117.50 | 4.67 | 0.00 | 0.00 |
SMSTORE5 | 7753.00 | 1001.67 | 5.33 | 0.00 | 0.00 |
SMSTORE6 | 7767.17 | 987.50 | 5.33 | 0.00 | 0.00 |
SMSTORE7 | 7756.33 | 997.33 | 6.33 | 0.00 | 0.00 |
SMSTORE8 | 7379.17 | 1346.17 | 34.67 | 0.00 | 0.00 |
Min | 6997.83 | 239.83 | 0.00 | 0.00 | 0.00 |
Max | 8520.17 | 1754.50 | 34.67 | 0.00 | 0.00 |
Average | 7626.00 | 1126.43 | 7.57 | 0.00 | 0.00 |
Sum | 76260.00 | 11264.33 | 75.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25339.67 | 134.00 | 1.33 | 0.00 | 0.00 |
SMSTORE3 | 25339.67 | 134.00 | 1.33 | 0.00 | 0.00 |
SMSTORE4 | 25341.00 | 132.67 | 1.33 | 0.00 | 0.00 |
LGSTORE2 | 92918.00 | 286.00 | 7.00 | 0.00 | 0.00 |
SMSTORE5 | 45765.50 | 142.50 | 4.00 | 0.00 | 0.00 |
SMSTORE6 | 45766.00 | 142.00 | 4.00 | 0.00 | 0.00 |
SMSTORE7 | 45766.50 | 141.50 | 4.00 | 0.00 | 0.00 |
SMSTORE8 | 45755.00 | 152.50 | 4.50 | 0.00 | 0.00 |
Min | 25339.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92918.00 | 286.00 | 7.00 | 0.00 | 0.00 |
Average | 48480.93 | 126.52 | 2.75 | 0.00 | 0.00 |
Sum | 484809.33 | 1265.17 | 27.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6645.50 | 2114.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7374.67 | 1385.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5830.00 | 2925.83 | 4.17 | 0.00 | 0.00 |
SMSTORE3 | 5824.33 | 2922.50 | 13.17 | 0.00 | 0.00 |
SMSTORE4 | 5837.67 | 2915.00 | 7.33 | 0.00 | 0.00 |
LGSTORE2 | 5938.17 | 2818.33 | 3.50 | 0.00 | 0.00 |
SMSTORE5 | 5959.17 | 2786.67 | 14.17 | 0.00 | 0.00 |
SMSTORE6 | 5961.33 | 2784.50 | 14.17 | 0.00 | 0.00 |
SMSTORE7 | 5976.33 | 2769.50 | 14.17 | 0.00 | 0.00 |
SMSTORE8 | 6002.67 | 2741.17 | 16.17 | 0.00 | 0.00 |
Min | 5824.33 | 1385.33 | 0.00 | 0.00 | 0.00 |
Max | 7374.67 | 2925.83 | 16.17 | 0.00 | 0.00 |
Average | 6134.98 | 2616.33 | 8.68 | 0.00 | 0.00 |
Sum | 61349.83 | 26163.33 | 86.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 75285.33 | 13755.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 37539.83 | 6237.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 20538.33 | 4936.50 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 20573.17 | 4901.67 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 20517.67 | 4957.17 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 73680.83 | 19529.17 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 36174.67 | 9736.83 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 36157.17 | 9754.33 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 36239.50 | 9672.00 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 37270.67 | 8640.83 | 0.50 | 0.00 | 0.00 |
Min | 20517.67 | 4901.67 | 0.00 | 0.00 | 0.00 |
Max | 75285.33 | 19529.17 | 1.00 | 0.00 | 0.00 |
Average | 39397.72 | 9212.13 | 0.35 | 0.00 | 0.00 |
Sum | 393977.17 | 92121.33 | 3.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581372E+10 | 7478.86 | 12-JAN-15:00 | 23.60 | 14.20 | 0.134299E+10 | 1685.93 | 08-JAN-18:49 | 23.60 | 14.20 |
February | 0.794079E+10 | 11752.20 | 22-FEB-15:00 | 27.10 | 16.20 | 0.125591E+10 | 1685.97 | 20-FEB-18:00 | 27.10 | 16.20 |
March | 0.141627E+11 | 28543.60 | 11-MAR-08:62 | 24.43 | 17.41 | 0.139632E+10 | 1686.05 | 12-MAR-17:00 | 29.10 | 19.27 |
April | 0.207683E+11 | 54087.24 | 28-APR-07:02 | 29.48 | 17.52 | 0.136170E+10 | 1686.13 | 16-APR-12:00 | 29.48 | 17.52 |
May | 0.258622E+11 | 55689.42 | 06-MAY-07:01 | 30.00 | 17.75 | 0.140197E+10 | 1686.20 | 07-MAY-12:00 | 40.90 | 21.35 |
June | 0.258909E+11 | 51781.43 | 07-JUN-07:01 | 34.92 | 19.62 | 0.135495E+10 | 1686.18 | 04-JUN-12:50 | 34.92 | 19.62 |
July | 0.252017E+11 | 43514.98 | 07-JUL-07:01 | 33.33 | 24.39 | 0.141317E+10 | 1686.09 | 04-JUL-17:49 | 33.33 | 24.39 |
August | 0.239803E+11 | 41696.06 | 03-AUG-07:01 | 28.70 | 23.41 | 0.139443E+10 | 1686.02 | 20-AUG-17:19 | 26.57 | 25.60 |
September | 0.216907E+11 | 44547.12 | 26-SEP-07:01 | 25.87 | 19.87 | 0.136546E+10 | 1686.13 | 30-SEP-12:00 | 34.20 | 23.67 |
October | 0.200223E+11 | 47796.17 | 05-OCT-07:02 | 23.83 | 18.71 | 0.140971E+10 | 1686.06 | 09-OCT-17:00 | 29.40 | 20.50 |
November | 0.134346E+11 | 15263.86 | 08-NOV-15:00 | 29.90 | 18.01 | 0.136171E+10 | 1686.03 | 05-NOV-17:10 | 29.90 | 18.01 |
December | 0.745077E+10 | 9439.76 | 01-DEC-14:00 | 23.50 | 13.07 | 0.138308E+10 | 1685.93 | 03-DEC-18:00 | 15.50 | 12.24 |
Annual Sum or Average | 0.212219E+12 | 0.164414E+11 | ||||||||
Minimum of Months | 0.581372E+10 | 7478.86 | 23.50 | 13.07 | 0.125591E+10 | 1685.93 | 15.50 | 12.24 | ||
Maximum of Months | 0.258909E+11 | 55689.42 | 34.92 | 24.39 | 0.141317E+10 | 1686.20 | 40.90 | 25.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317214E+10 | 4343.40 | 12-JAN-15:00 | 23.60 | 14.20 | 0.690448E+09 | 842.94 | 07-JAN-13:00 | 23.60 | 14.20 |
February | 0.461722E+10 | 6353.41 | 22-FEB-15:00 | 27.10 | 16.20 | 0.632547E+09 | 842.94 | 20-FEB-18:10 | 27.10 | 16.20 |
March | 0.787725E+10 | 16961.13 | 11-MAR-08:62 | 24.43 | 17.41 | 0.698487E+09 | 842.98 | 31-MAR-12:30 | 28.15 | 17.85 |
April | 0.108495E+11 | 27930.05 | 30-APR-07:02 | 24.20 | 14.19 | 0.680844E+09 | 843.21 | 02-APR-17:49 | 24.20 | 14.19 |
May | 0.132128E+11 | 28392.87 | 06-MAY-07:01 | 30.00 | 17.75 | 0.700962E+09 | 843.06 | 26-MAY-12:00 | 40.30 | 21.68 |
June | 0.130761E+11 | 27094.97 | 07-JUN-07:01 | 34.92 | 19.62 | 0.677442E+09 | 843.06 | 04-JUN-12:30 | 34.92 | 19.62 |
July | 0.127636E+11 | 24704.65 | 07-JUL-07:01 | 33.33 | 24.39 | 0.706548E+09 | 843.01 | 30-JUL-17:00 | 33.50 | 27.55 |
August | 0.121261E+11 | 23667.11 | 03-AUG-07:01 | 28.70 | 23.41 | 0.697182E+09 | 843.00 | 11-AUG-12:50 | 28.08 | 27.13 |
September | 0.110617E+11 | 25453.46 | 26-SEP-07:01 | 25.87 | 19.87 | 0.682705E+09 | 843.04 | 30-SEP-12:50 | 34.07 | 23.68 |
October | 0.104445E+11 | 26595.07 | 02-OCT-07:02 | 24.92 | 18.38 | 0.704850E+09 | 843.00 | 13-OCT-12:30 | 28.75 | 22.41 |
November | 0.734675E+10 | 9014.44 | 09-NOV-08:63 | 19.90 | 16.70 | 0.681189E+09 | 842.99 | 19-NOV-13:30 | 26.15 | 17.02 |
December | 0.417439E+10 | 5399.00 | 02-DEC-14:00 | 24.10 | 13.15 | 0.701300E+09 | 842.95 | 08-DEC-13:00 | 20.20 | 13.18 |
Annual Sum or Average | 0.110722E+12 | 0.825450E+10 | ||||||||
Minimum of Months | 0.317214E+10 | 4343.40 | 19.90 | 13.15 | 0.632547E+09 | 842.94 | 20.20 | 13.18 | ||
Maximum of Months | 0.132128E+11 | 28392.87 | 34.92 | 24.39 | 0.706548E+09 | 843.21 | 40.30 | 27.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222774E+10 | 3907.51 | 12-JAN-15:00 | 23.60 | 14.20 | 0.403201E+09 | 842.94 | 07-JAN-13:00 | 23.60 | 14.20 |
February | 0.329376E+10 | 6042.30 | 22-FEB-14:00 | 27.00 | 16.33 | 0.376681E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.593794E+10 | 18545.30 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431248E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.845894E+10 | 28825.03 | 20-APR-06:01 | 26.07 | 17.13 | 0.411765E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.106440E+11 | 28999.98 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427476E+09 | 843.00 | 27-MAY-12:00 | 40.90 | 20.29 |
June | 0.105626E+11 | 26085.26 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418361E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.999401E+10 | 21694.44 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421225E+09 | 843.01 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.964032E+10 | 19166.57 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432584E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.861281E+10 | 21906.71 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411664E+09 | 843.04 | 30-SEP-12:39 | 33.93 | 23.68 |
October | 0.804747E+10 | 25878.46 | 02-OCT-06:01 | 22.92 | 17.86 | 0.420967E+09 | 842.99 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.554915E+10 | 8494.64 | 09-NOV-07:03 | 18.42 | 16.27 | 0.405355E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.296422E+10 | 5211.79 | 02-DEC-14:00 | 24.10 | 13.15 | 0.410992E+09 | 842.94 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.859330E+11 | 0.497152E+10 | ||||||||
Minimum of Months | 0.222774E+10 | 3907.51 | 18.42 | 13.15 | 0.376681E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.106440E+11 | 28999.98 | 34.87 | 23.95 | 0.432584E+09 | 843.04 | 40.90 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207355E+10 | 3776.90 | 12-JAN-15:00 | 23.60 | 14.20 | 0.401176E+09 | 842.94 | 07-JAN-13:00 | 23.60 | 14.20 |
February | 0.319489E+10 | 5968.33 | 22-FEB-14:00 | 27.00 | 16.33 | 0.376339E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.591279E+10 | 18717.35 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431218E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.850858E+10 | 28946.59 | 20-APR-06:01 | 26.07 | 17.13 | 0.411768E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.107505E+11 | 29109.44 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427484E+09 | 843.00 | 27-MAY-12:00 | 40.90 | 20.29 |
June | 0.106645E+11 | 26413.94 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418368E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.101021E+11 | 21860.25 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421233E+09 | 842.92 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.971851E+10 | 19293.90 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432590E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.867630E+10 | 22018.60 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411669E+09 | 843.04 | 30-SEP-12:39 | 33.93 | 23.68 |
October | 0.808913E+10 | 26707.08 | 23-OCT-06:02 | 19.08 | 14.21 | 0.420969E+09 | 842.99 | 14-OCT-12:09 | 19.08 | 14.21 |
November | 0.550396E+10 | 8329.45 | 09-NOV-07:03 | 18.42 | 16.27 | 0.405306E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.284002E+10 | 5142.10 | 02-DEC-14:00 | 24.10 | 13.15 | 0.410335E+09 | 842.94 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.860349E+11 | 0.496846E+10 | ||||||||
Minimum of Months | 0.207355E+10 | 3776.90 | 18.42 | 13.15 | 0.376339E+09 | 842.90 | 19.08 | 12.78 | ||
Maximum of Months | 0.107505E+11 | 29109.44 | 34.87 | 23.95 | 0.432590E+09 | 843.04 | 40.90 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185128E+10 | 3634.10 | 03-JAN-07:05 | 5.50 | 5.17 | 0.398025E+09 | 842.93 | 07-JAN-13:00 | 20.90 | 13.29 |
February | 0.298923E+10 | 5788.24 | 22-FEB-14:00 | 27.00 | 16.33 | 0.375559E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.569917E+10 | 17266.17 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431095E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.833456E+10 | 28648.56 | 20-APR-06:01 | 26.07 | 17.13 | 0.411736E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.106028E+11 | 28904.51 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427454E+09 | 843.00 | 27-MAY-12:00 | 40.90 | 20.29 |
June | 0.105203E+11 | 26250.20 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418340E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.997084E+10 | 21568.37 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421205E+09 | 843.01 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.956782E+10 | 19013.24 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432559E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.852636E+10 | 21775.99 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411638E+09 | 843.05 | 30-SEP-12:50 | 34.07 | 23.68 |
October | 0.791950E+10 | 25883.72 | 02-OCT-06:01 | 22.92 | 17.86 | 0.420936E+09 | 842.99 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.531043E+10 | 7883.66 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405180E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.262083E+10 | 4962.61 | 02-DEC-14:00 | 24.10 | 13.15 | 0.409099E+09 | 842.93 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.839132E+11 | 0.496283E+10 | ||||||||
Minimum of Months | 0.185128E+10 | 3634.10 | 5.50 | 5.17 | 0.375559E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.106028E+11 | 28904.51 | 34.87 | 23.95 | 0.432559E+09 | 843.05 | 40.90 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286815E+10 | 7005.76 | 04-JAN-08:03 | 6.42 | 5.61 | 0.134804E+10 | 2247.83 | 28-JAN-15:30 | 18.30 | 11.46 |
February | 0.473391E+10 | 10327.28 | 22-FEB-15:10 | 27.00 | 16.16 | 0.128499E+10 | 2247.85 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.961526E+10 | 26963.08 | 11-MAR-08:62 | 24.43 | 17.41 | 0.147865E+10 | 2248.01 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.144017E+11 | 50640.78 | 20-APR-07:02 | 26.55 | 16.63 | 0.141152E+10 | 2248.06 | 15-APR-14:20 | 26.55 | 16.63 |
May | 0.184908E+11 | 51793.96 | 29-MAY-08:61 | 32.12 | 19.78 | 0.146006E+10 | 2248.17 | 27-MAY-14:20 | 32.12 | 19.78 |
June | 0.183922E+11 | 47500.50 | 07-JUN-07:01 | 34.92 | 19.62 | 0.143152E+10 | 2247.81 | 17-JUN-14:30 | 38.45 | 25.73 |
July | 0.173471E+11 | 41151.08 | 07-JUL-07:01 | 33.33 | 24.39 | 0.144042E+10 | 2247.81 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.166694E+11 | 37529.16 | 08-AUG-07:01 | 30.50 | 24.42 | 0.148124E+10 | 2248.04 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.147317E+11 | 41367.30 | 27-SEP-07:02 | 24.98 | 20.39 | 0.141131E+10 | 2247.81 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.137182E+11 | 45712.25 | 02-OCT-07:02 | 24.92 | 18.38 | 0.143660E+10 | 2247.98 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.884287E+10 | 14356.85 | 04-NOV-14:20 | 30.27 | 17.30 | 0.138068E+10 | 2247.91 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.406806E+10 | 8478.43 | 02-DEC-14:30 | 24.00 | 13.17 | 0.139892E+10 | 2247.86 | 09-DEC-15:00 | 18.80 | 13.15 |
Annual Sum or Average | 0.143879E+12 | 0.169640E+11 | ||||||||
Minimum of Months | 0.286815E+10 | 7005.76 | 6.42 | 5.61 | 0.128499E+10 | 2247.81 | 18.30 | 11.46 | ||
Maximum of Months | 0.184908E+11 | 51793.96 | 34.92 | 24.42 | 0.148124E+10 | 2248.17 | 38.45 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133657E+10 | 3491.07 | 04-JAN-08:03 | 6.42 | 5.61 | 0.671578E+09 | 1123.88 | 28-JAN-15:39 | 18.27 | 11.45 |
February | 0.235791E+10 | 5396.64 | 22-FEB-15:10 | 27.00 | 16.16 | 0.642014E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.497390E+10 | 12796.99 | 11-MAR-08:62 | 24.43 | 17.41 | 0.739299E+09 | 1123.97 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.756264E+10 | 26456.52 | 20-APR-07:02 | 26.55 | 16.63 | 0.705721E+09 | 1124.00 | 15-APR-14:30 | 26.55 | 16.63 |
May | 0.975349E+10 | 27063.70 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729987E+09 | 1124.07 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.968036E+10 | 24793.03 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715720E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.911008E+10 | 21506.18 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720162E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.872792E+10 | 19617.82 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740582E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.771388E+10 | 21576.99 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705611E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.716467E+10 | 23804.74 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718266E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.455814E+10 | 7558.50 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690331E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.196849E+10 | 4377.14 | 02-DEC-14:30 | 24.00 | 13.17 | 0.698560E+09 | 1123.90 | 09-DEC-15:00 | 18.80 | 13.15 |
Annual Sum or Average | 0.749080E+11 | 0.847783E+10 | ||||||||
Minimum of Months | 0.133657E+10 | 3491.07 | 6.42 | 5.61 | 0.642014E+09 | 1123.87 | 18.27 | 11.45 | ||
Maximum of Months | 0.975349E+10 | 27063.70 | 34.92 | 24.42 | 0.740582E+09 | 1124.07 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128969E+10 | 3530.61 | 04-JAN-08:03 | 6.42 | 5.61 | 0.669760E+09 | 1123.87 | 28-JAN-15:50 | 18.23 | 11.45 |
February | 0.229868E+10 | 5335.81 | 22-FEB-15:10 | 27.00 | 16.16 | 0.641470E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.491100E+10 | 12403.74 | 11-MAR-08:62 | 24.43 | 17.41 | 0.739246E+09 | 1123.97 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.751410E+10 | 26357.56 | 20-APR-07:02 | 26.55 | 16.63 | 0.705715E+09 | 1124.00 | 15-APR-14:30 | 26.55 | 16.63 |
May | 0.971198E+10 | 26989.29 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729983E+09 | 1124.07 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.963896E+10 | 24701.76 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715717E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.907482E+10 | 21419.13 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720157E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.869104E+10 | 19541.58 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740578E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.767720E+10 | 21483.52 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705606E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.711998E+10 | 23728.22 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718259E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.450353E+10 | 7511.89 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690289E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.191503E+10 | 4318.52 | 02-DEC-14:30 | 24.00 | 13.17 | 0.697559E+09 | 1123.90 | 09-DEC-15:50 | 18.98 | 13.15 |
Annual Sum or Average | 0.743460E+11 | 0.847434E+10 | ||||||||
Minimum of Months | 0.128969E+10 | 3530.61 | 6.42 | 5.61 | 0.641470E+09 | 1123.87 | 18.23 | 11.45 | ||
Maximum of Months | 0.971198E+10 | 26989.29 | 34.92 | 24.42 | 0.740578E+09 | 1124.07 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118124E+10 | 3493.08 | 04-JAN-08:03 | 6.42 | 5.61 | 0.665459E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.215130E+10 | 5222.08 | 22-FEB-15:10 | 27.00 | 16.16 | 0.639865E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.478473E+10 | 11069.22 | 30-MAR-07:03 | 21.65 | 17.03 | 0.739047E+09 | 1123.98 | 11-MAR-15:00 | 21.65 | 17.03 |
April | 0.751297E+10 | 26391.19 | 20-APR-07:02 | 26.55 | 16.63 | 0.705714E+09 | 1124.00 | 15-APR-14:20 | 26.55 | 16.63 |
May | 0.979525E+10 | 27108.81 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729988E+09 | 1124.07 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.973569E+10 | 24877.51 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715721E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.918675E+10 | 21617.25 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720167E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.879467E+10 | 19744.63 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740586E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.774687E+10 | 21600.51 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705613E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.713071E+10 | 23842.07 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718257E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.440391E+10 | 7467.91 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690142E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.177785E+10 | 4179.19 | 02-DEC-14:30 | 24.00 | 13.17 | 0.694881E+09 | 1123.90 | 09-DEC-15:39 | 19.17 | 13.14 |
Annual Sum or Average | 0.742019E+11 | 0.846544E+10 | ||||||||
Minimum of Months | 0.118124E+10 | 3493.08 | 6.42 | 5.61 | 0.639865E+09 | 1123.87 | 19.17 | 13.14 | ||
Maximum of Months | 0.979525E+10 | 27108.81 | 34.92 | 24.42 | 0.740586E+09 | 1124.07 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108075E+10 | 3735.13 | 05-JAN-08:03 | 6.10 | 5.59 | 0.664861E+09 | 1123.90 | 07-JAN-15:30 | 20.40 | 13.34 |
February | 0.220182E+10 | 5856.93 | 22-FEB-14:00 | 27.00 | 16.33 | 0.637800E+09 | 1123.88 | 18-FEB-15:00 | 27.00 | 16.33 |
March | 0.528788E+10 | 10075.57 | 28-MAR-15:00 | 35.60 | 18.50 | 0.738635E+09 | 1123.98 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.891313E+10 | 29529.19 | 30-APR-08:62 | 26.15 | 14.14 | 0.705831E+09 | 1124.01 | 15-APR-14:39 | 26.15 | 14.14 |
May | 0.118408E+11 | 30973.67 | 29-MAY-08:61 | 32.12 | 19.78 | 0.730103E+09 | 1124.12 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.117602E+11 | 29232.67 | 12-JUN-07:01 | 35.90 | 20.13 | 0.715828E+09 | 1123.87 | 17-JUN-14:00 | 38.50 | 25.76 |
July | 0.111262E+11 | 25314.60 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720352E+09 | 1123.96 | 22-JUL-14:00 | 29.50 | 26.90 |
August | 0.107046E+11 | 22320.48 | 09-AUG-07:01 | 30.30 | 25.37 | 0.740741E+09 | 1123.99 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.934256E+10 | 24851.57 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705788E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.844416E+10 | 27029.40 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718405E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.490274E+10 | 8355.78 | 04-NOV-14:10 | 30.28 | 17.23 | 0.689932E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.172091E+10 | 4468.34 | 01-DEC-14:00 | 23.50 | 13.07 | 0.693381E+09 | 1123.90 | 09-DEC-15:09 | 19.72 | 13.10 |
Annual Sum or Average | 0.873258E+11 | 0.846166E+10 | ||||||||
Minimum of Months | 0.108075E+10 | 3735.13 | 6.10 | 5.59 | 0.637800E+09 | 1123.87 | 19.72 | 13.10 | ||
Maximum of Months | 0.118408E+11 | 30973.67 | 35.90 | 25.37 | 0.740741E+09 | 1124.12 | 38.50 | 26.90 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76252620.61 | 64956.54 | 02-JAN-08:61 | 7.38 |
February | 2398422.66 | 2100.51 | 11-FEB-08:04 | 11.12 |
March | 3610514.25 | 2585.90 | 11-MAR-08:05 | 24.43 |
April | 48810710.56 | 4940.80 | 27-APR-07:05 | 30.20 |
May | 38344544.02 | 7372.42 | 04-MAY-07:04 | 34.62 |
June | 27676603.60 | 7233.75 | 12-JUN-07:05 | 35.90 |
July | 24800801.38 | 6362.13 | 08-JUL-07:05 | 33.13 |
August | 27648378.58 | 5018.80 | 08-AUG-07:05 | 30.50 |
September | 32794265.98 | 4312.80 | 22-SEP-07:04 | 28.37 |
October | 21756187.21 | 3011.12 | 03-OCT-07:04 | 24.75 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 4920885.91 | 8343.67 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.309014E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 76252620.61 | 64956.54 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6894834.68 | 8135.24 | 02-JAN-08:61 | 7.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 2107458.18 | 1433.73 | 11-MAR-08:05 | 24.43 |
April | 24326761.82 | 2361.09 | 27-APR-07:05 | 30.20 |
May | 15060958.02 | 3569.25 | 04-MAY-07:04 | 34.62 |
June | 10276689.47 | 3953.35 | 12-JUN-07:04 | 35.90 |
July | 10516134.91 | 3382.87 | 07-JUL-07:04 | 33.33 |
August | 10482644.05 | 2634.14 | 07-AUG-07:04 | 30.33 |
September | 15317702.27 | 2221.91 | 22-SEP-07:04 | 28.37 |
October | 11507139.78 | 1682.25 | 03-OCT-07:04 | 24.75 |
November | 22605.45 | 113.03 | 09-NOV-08:07 | 19.90 |
December | 39721.48 | 331.01 | 23-DEC-08:10 | 7.55 |
Annual Sum or Average | 0.106553E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 24326761.82 | 8135.24 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26585357.46 | 22891.53 | 01-JAN-08:62 | 8.17 |
February | 447137.75 | 326.86 | 20-FEB-17:03 | 24.33 |
March | 35980777.29 | 1865.88 | 12-MAR-16:12 | 31.07 |
April | 0.184766E+09 | 3814.83 | 16-APR-16:01 | 39.13 |
May | 0.230977E+09 | 4540.97 | 07-MAY-16:01 | 42.17 |
June | 0.239246E+09 | 4864.96 | 11-JUN-16:01 | 43.35 |
July | 0.178822E+09 | 4172.31 | 02-JUL-16:01 | 40.38 |
August | 0.150439E+09 | 3180.72 | 06-AUG-16:01 | 36.25 |
September | 0.131843E+09 | 2764.73 | 24-SEP-16:01 | 34.68 |
October | 72621458.84 | 2871.59 | 01-OCT-16:01 | 35.32 |
November | 6370522.20 | 1123.91 | 04-NOV-17:03 | 27.72 |
December | 67560.50 | 337.80 | 31-DEC-08:13 | 6.83 |
Annual Sum or Average | 0.125817E+10 | |||
Minimum of Months | 67560.50 | 326.86 | 6.83 | |
Maximum of Months | 0.239246E+09 | 22891.53 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42318867.28 | 31719.41 | 01-JAN-08:62 | 8.17 |
February | 482134.37 | 335.49 | 20-FEB-17:03 | 24.33 |
March | 36120232.81 | 1867.29 | 12-MAR-16:12 | 31.07 |
April | 0.184348E+09 | 3813.35 | 16-APR-16:01 | 39.13 |
May | 0.228364E+09 | 4538.75 | 07-MAY-16:01 | 42.17 |
June | 0.235469E+09 | 4862.44 | 11-JUN-16:01 | 43.35 |
July | 0.177502E+09 | 4170.19 | 02-JUL-16:01 | 40.38 |
August | 0.149281E+09 | 3178.79 | 06-AUG-16:01 | 36.25 |
September | 0.130341E+09 | 2763.26 | 24-SEP-16:01 | 34.68 |
October | 72352896.96 | 2870.33 | 01-OCT-16:01 | 35.32 |
November | 6408200.45 | 1125.91 | 04-NOV-17:03 | 27.72 |
December | 300426.72 | 748.58 | 23-DEC-07:10 | 6.25 |
Annual Sum or Average | 0.126329E+10 | |||
Minimum of Months | 300426.72 | 335.49 | 6.25 | |
Maximum of Months | 0.235469E+09 | 31719.41 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60062085.32 | 32460.97 | 01-JAN-08:62 | 8.17 |
February | 540929.65 | 349.77 | 20-FEB-17:03 | 24.33 |
March | 36890338.94 | 1870.00 | 12-MAR-16:12 | 31.07 |
April | 0.185582E+09 | 3817.10 | 16-APR-16:01 | 39.13 |
May | 0.232142E+09 | 4541.56 | 07-MAY-16:01 | 42.17 |
June | 0.240974E+09 | 4864.56 | 11-JUN-16:01 | 43.35 |
July | 0.180202E+09 | 4172.72 | 02-JUL-16:01 | 40.38 |
August | 0.152253E+09 | 3181.65 | 06-AUG-16:01 | 36.25 |
September | 0.132950E+09 | 2767.03 | 24-SEP-16:01 | 34.68 |
October | 73497040.23 | 2874.34 | 01-OCT-16:01 | 35.32 |
November | 6627448.04 | 1134.86 | 04-NOV-17:03 | 27.72 |
December | 613710.94 | 1112.64 | 31-DEC-08:10 | 6.52 |
Annual Sum or Average | 0.130233E+10 | |||
Minimum of Months | 540929.65 | 349.77 | 6.52 | |
Maximum of Months | 0.240974E+09 | 32460.97 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157901E+09 | 60663.26 | 01-JAN-09:01 | 9.20 |
February | 4674167.39 | 2648.42 | 02-FEB-08:05 | 8.07 |
March | 35269430.29 | 3816.34 | 12-MAR-16:02 | 31.18 |
April | 0.158183E+09 | 7705.64 | 16-APR-16:01 | 39.13 |
May | 0.151730E+09 | 9151.37 | 07-MAY-16:01 | 42.17 |
June | 0.128730E+09 | 9788.15 | 11-JUN-16:01 | 43.35 |
July | 0.139453E+09 | 8403.60 | 02-JUL-16:01 | 40.38 |
August | 0.105037E+09 | 6413.56 | 06-AUG-16:01 | 36.25 |
September | 0.123842E+09 | 5595.70 | 24-SEP-16:01 | 34.68 |
October | 0.102897E+09 | 5818.51 | 01-OCT-16:01 | 35.32 |
November | 13170554.70 | 2327.58 | 04-NOV-17:03 | 27.72 |
December | 5503437.64 | 9880.28 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.112639E+10 | |||
Minimum of Months | 4674167.39 | 2327.58 | 7.55 | |
Maximum of Months | 0.158183E+09 | 60663.26 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99778281.48 | 31978.87 | 01-JAN-09:01 | 9.20 |
February | 3413884.83 | 1704.04 | 02-FEB-08:05 | 8.07 |
March | 18939069.05 | 1915.16 | 12-MAR-16:02 | 31.18 |
April | 81422401.73 | 3855.36 | 16-APR-16:01 | 39.13 |
May | 75200830.07 | 4577.05 | 07-MAY-16:01 | 42.17 |
June | 63459610.16 | 4896.51 | 11-JUN-16:01 | 43.35 |
July | 70207294.91 | 4205.69 | 02-JUL-16:01 | 40.38 |
August | 50501758.53 | 3214.71 | 06-AUG-16:01 | 36.25 |
September | 62395370.02 | 2804.64 | 24-SEP-16:01 | 34.68 |
October | 53526739.22 | 2913.75 | 01-OCT-16:01 | 35.32 |
November | 7464038.55 | 1186.66 | 04-NOV-17:03 | 27.72 |
December | 3882100.09 | 5997.74 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.590191E+09 | |||
Minimum of Months | 3413884.83 | 1186.66 | 7.55 | |
Maximum of Months | 99778281.48 | 31978.87 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107453E+09 | 31894.41 | 01-JAN-09:01 | 9.20 |
February | 4177305.95 | 2374.02 | 02-FEB-09:00 | 9.90 |
March | 19018470.46 | 1916.97 | 12-MAR-16:02 | 31.18 |
April | 81667556.35 | 3856.39 | 16-APR-16:01 | 39.13 |
May | 75513147.19 | 4577.75 | 07-MAY-16:01 | 42.17 |
June | 62987347.02 | 4897.04 | 11-JUN-16:01 | 43.35 |
July | 70383343.44 | 4206.34 | 02-JUL-16:01 | 40.38 |
August | 51099694.51 | 3215.31 | 06-AUG-16:01 | 36.25 |
September | 62483730.37 | 2805.48 | 24-SEP-16:01 | 34.68 |
October | 53602851.08 | 2914.78 | 01-OCT-16:01 | 35.32 |
November | 7518472.08 | 1188.90 | 04-NOV-17:03 | 27.72 |
December | 4526825.98 | 7442.71 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.600432E+09 | |||
Minimum of Months | 4177305.95 | 1188.90 | 7.55 | |
Maximum of Months | 0.107453E+09 | 31894.41 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151261E+09 | 32102.96 | 01-JAN-09:01 | 9.20 |
February | 7912277.17 | 6965.32 | 11-FEB-08:62 | 11.12 |
March | 19462536.19 | 1919.09 | 12-MAR-16:02 | 31.18 |
April | 81595280.94 | 3854.35 | 16-APR-16:01 | 39.13 |
May | 75632764.72 | 4574.80 | 07-MAY-16:01 | 42.17 |
June | 62489918.50 | 4893.52 | 11-JUN-16:01 | 43.35 |
July | 70601682.19 | 4202.33 | 02-JUL-16:01 | 40.38 |
August | 50244483.61 | 3211.37 | 06-AUG-16:01 | 36.25 |
September | 61377717.72 | 2802.27 | 24-SEP-16:01 | 34.68 |
October | 53310784.89 | 2911.96 | 01-OCT-16:01 | 35.32 |
November | 7715703.99 | 1192.83 | 04-NOV-17:03 | 27.72 |
December | 8394214.09 | 12315.33 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.649998E+09 | |||
Minimum of Months | 7715703.99 | 1192.83 | 7.55 | |
Maximum of Months | 0.151261E+09 | 32102.96 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321353E+09 | 37011.35 | 01-JAN-09:01 | 9.20 |
February | 60586821.31 | 26648.21 | 11-FEB-08:62 | 11.12 |
March | 20212824.43 | 1902.92 | 12-MAR-16:12 | 31.07 |
April | 75260849.35 | 3778.21 | 16-APR-16:01 | 39.13 |
May | 60796920.80 | 4493.26 | 07-MAY-16:01 | 42.17 |
June | 54466680.48 | 4811.89 | 11-JUN-16:01 | 43.35 |
July | 60766520.20 | 4113.19 | 02-JUL-16:01 | 40.38 |
August | 42596702.91 | 3123.83 | 06-AUG-16:01 | 36.25 |
September | 53632442.40 | 2716.58 | 24-SEP-16:01 | 34.68 |
October | 50524098.33 | 2827.28 | 01-OCT-16:01 | 35.32 |
November | 7619940.02 | 1160.26 | 04-NOV-17:03 | 27.72 |
December | 50049962.76 | 28988.19 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.857867E+09 | |||
Minimum of Months | 7619940.02 | 1160.26 | 7.55 | |
Maximum of Months | 0.321353E+09 | 37011.35 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195099E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120651E+09 | 0.819922E+09 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122859E+10 | 0.199331E+09 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329533E+10 | 11061211.46 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466007E+10 | 3081563.77 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422911E+10 | 1558007.17 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340848E+10 | 868883.41 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288952E+10 | 1300368.28 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252434E+10 | 2831174.44 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218199E+10 | 37102542.60 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743415E+09 | 0.251861E+09 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5212737.80 | 0.168033E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252867E+11 | 0.496024E+10 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868883.41 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466007E+10 | 0.195099E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111444E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68407547.23 | 0.445912E+09 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695276E+09 | 93690394.32 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185720E+10 | 4391915.32 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261043E+10 | 969917.10 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237891E+10 | 469957.72 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190348E+10 | 249764.56 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162435E+10 | 361292.02 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142656E+10 | 784178.05 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123913E+10 | 18742441.82 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422970E+09 | 0.136203E+09 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2960873.47 | 0.946376E+09 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142297E+11 | 0.276259E+10 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249764.56 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261043E+10 | 0.111444E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109474E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68318271.01 | 0.458285E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683547E+09 | 0.103935E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183203E+10 | 5646703.87 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258132E+10 | 1248461.31 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235696E+10 | 602250.62 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187007E+10 | 313164.23 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160194E+10 | 1106573.70 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140146E+10 | 1556382.95 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121073E+10 | 19814994.33 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418185E+09 | 0.145256E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961133.28 | 0.945656E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140275E+11 | 0.277816E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313164.23 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258132E+10 | 0.109474E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108299E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68318890.35 | 0.456010E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683523E+09 | 0.103731E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183171E+10 | 5726708.09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258026E+10 | 1338927.27 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235626E+10 | 655478.22 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186891E+10 | 349169.67 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160136E+10 | 1181513.60 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140114E+10 | 1690337.52 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121052E+10 | 19858509.88 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418191E+09 | 0.144888E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961146.46 | 0.941500E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140232E+11 | 0.275992E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349169.67 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258026E+10 | 0.108299E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106606E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68319841.80 | 0.451246E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683732E+09 | 0.102359E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183215E+10 | 5513629.62 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258108E+10 | 1221061.39 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235687E+10 | 614638.92 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186986E+10 | 302313.90 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160201E+10 | 1055901.77 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140154E+10 | 1465345.18 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121087E+10 | 19727110.90 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418227E+09 | 0.143856E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961162.68 | 0.934418E+09 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140276E+11 | 0.272784E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302313.90 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258108E+10 | 0.106606E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182540E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119665E+09 | 0.786784E+09 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119929E+10 | 0.182971E+09 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321390E+10 | 10478777.67 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453358E+10 | 2376610.82 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413725E+10 | 1454319.10 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328600E+10 | 496784.44 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281164E+10 | 1724452.76 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245564E+10 | 2883481.49 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212229E+10 | 36791057.25 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732435E+09 | 0.251802E+09 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5186161.49 | 0.161806E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246169E+11 | 0.472123E+10 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496784.44 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453358E+10 | 0.182540E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102911E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68320843.22 | 0.441440E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684678E+09 | 99854303.70 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183352E+10 | 5472439.93 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258392E+10 | 1124382.13 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235933E+10 | 705194.11 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187223E+10 | 220984.88 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160366E+10 | 801938.51 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140177E+10 | 1311595.88 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121229E+10 | 20488041.56 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418366E+09 | 0.142145E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961924.99 | 0.916162E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140410E+11 | 0.265883E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220984.88 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258392E+10 | 0.102911E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102326E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68321190.94 | 0.439467E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684746E+09 | 99335993.64 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183366E+10 | 5423700.71 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258408E+10 | 1106457.32 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235947E+10 | 697304.19 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187241E+10 | 215760.65 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160378E+10 | 786532.09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140187E+10 | 1279636.23 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121239E+10 | 20439992.97 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418379E+09 | 0.141746E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961927.84 | 0.912809E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140421E+11 | 0.264657E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215760.65 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258408E+10 | 0.102326E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100937E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68322340.68 | 0.433491E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684851E+09 | 97504304.53 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183372E+10 | 5298009.41 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258386E+10 | 1071332.91 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235929E+10 | 698641.87 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187190E+10 | 212154.52 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160349E+10 | 801384.77 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140173E+10 | 1266988.15 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121232E+10 | 20365013.51 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418394E+09 | 0.140509E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962062.59 | 0.903906E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140408E+11 | 0.261449E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212154.52 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258386E+10 | 0.100937E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105673E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69155602.17 | 0.484814E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694443E+09 | 0.132416E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187358E+10 | 8556471.71 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266482E+10 | 2774107.21 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242025E+10 | 1707933.76 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193742E+10 | 729061.16 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164095E+10 | 2195070.36 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142320E+10 | 4115710.49 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122159E+10 | 25172914.98 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421161E+09 | 0.154087E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2989668.52 | 0.948921E+09 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143695E+11 | 0.282222E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729061.16 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266482E+10 | 0.105673E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4122.60 | 15-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.90 | 22-FEB-15:00 | 3640.28 | 10-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1577.45 | 18-MAR-17:00 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7285.36 | 15-APR-15:00 | 293.58 | 10-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8780.03 | 03-MAY-15:00 | 66.35 | 13-MAY-05:00 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.30 | 06-JUN-15:00 | 82.60 | 18-JUN-05:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7081.27 | 07-JUL-15:00 | 71.49 | 19-JUL-03:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868.59 | 07-AUG-15:00 | 76.37 | 16-AUG-07:01 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5404.42 | 29-SEP-13:00 | 59.95 | 07-SEP-07:02 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.48 | 02-OCT-14:00 | 505.76 | 11-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857.78 | 04-NOV-14:00 | 2233.32 | 30-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.63 | 28-DEC-14:00 | 4905.42 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.30 | 4905.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2425.76 | 15-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2200.16 | 10-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.78 | 15-APR-15:00 | 163.08 | 10-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.52 | 03-MAY-15:00 | 20.27 | 13-MAY-05:00 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 24.94 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 20.87 | 19-JUL-03:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 34.21 | 16-AUG-07:01 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.66 | 29-SEP-13:00 | 24.85 | 07-SEP-07:02 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.72 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.72 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2833.74 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2833.74 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2283.12 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2173.75 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.30 | 15-APR-15:00 | 173.37 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 24.12 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 29.01 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 22.68 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 197.29 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.75 | 29-SEP-13:00 | 111.67 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.72 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.72 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2752.72 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2752.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2257.50 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2155.17 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.30 | 15-APR-15:00 | 173.89 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 25.85 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 31.99 | 18-JUN-07:01 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 23.16 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 201.98 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.75 | 29-SEP-13:00 | 118.28 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.70 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.72 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2733.69 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2733.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2214.71 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2111.77 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.31 | 15-APR-15:00 | 168.96 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 24.80 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 29.40 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 22.27 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 189.93 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.77 | 29-SEP-13:00 | 106.83 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.70 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2693.50 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2693.50 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3811.12 | 01-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.87 | 22-FEB-15:00 | 3548.05 | 10-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1566.20 | 18-MAR-17:00 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7155.27 | 15-APR-15:00 | 286.75 | 10-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8712.14 | 03-MAY-15:00 | 46.59 | 15-MAY-03:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.03 | 07-JUN-16:00 | 114.07 | 18-JUN-07:01 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.44 | 07-JUL-15:00 | 40.98 | 19-JUL-03:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820.44 | 07-AUG-15:00 | 293.25 | 20-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5355.69 | 29-SEP-13:00 | 149.99 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5470.98 | 02-OCT-14:00 | 502.15 | 11-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.05 | 04-NOV-14:00 | 2227.75 | 30-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.09 | 28-DEC-14:00 | 4608.71 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.98 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.03 | 4608.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 2004.05 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.91 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 23.06 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 60.65 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.90 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 144.85 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 63.69 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.59 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2619.02 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2619.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 1986.50 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.76 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 22.94 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 59.91 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.76 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 141.99 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 61.11 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.59 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2606.42 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2606.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 1940.24 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.16 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 22.71 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 59.53 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.58 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 146.21 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.04 | 29-SEP-13:00 | 66.17 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.57 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2569.91 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2569.91 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.29 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.04 | 22-FEB-15:00 | 1847.53 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 905.42 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.94 | 15-APR-15:00 | 201.66 | 22-APR-18:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5040.73 | 03-MAY-15:00 | 58.09 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.35 | 06-JUN-15:00 | 74.38 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.93 | 07-JUL-15:00 | 50.84 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.53 | 07-AUG-15:00 | 257.05 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.82 | 29-SEP-13:00 | 161.88 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3151.78 | 02-OCT-14:00 | 290.29 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.40 | 04-NOV-14:00 | 1278.40 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.80 | 28-DEC-14:00 | 2548.75 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.84 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.35 | 2548.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7478.86 | 12-JAN-15:00 | 2700.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.41 |
February | 11752.20 | 22-FEB-15:00 | 2700.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.90 | 0.00 |
March | 28543.60 | 11-MAR-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 0.00 |
April | 54087.24 | 28-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 338.35 | 0.00 |
May | 55689.42 | 06-MAY-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 300.30 | 0.00 |
June | 51781.43 | 07-JUN-07:01 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 604.97 | 0.00 |
July | 43514.98 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 472.85 | 0.00 |
August | 41696.06 | 03-AUG-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 170.02 | 0.00 |
September | 44547.12 | 26-SEP-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 | 0.00 |
October | 47796.17 | 05-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 |
November | 15263.86 | 08-NOV-15:00 | 2700.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.96 | 0.00 |
December | 9439.76 | 01-DEC-14:00 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7478.86 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55689.42 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.96 | 181.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4343.40 | 12-JAN-15:00 | 1349.97 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 6353.41 | 22-FEB-15:00 | 1349.97 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 0.00 |
March | 16961.13 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 | 0.00 |
April | 27930.05 | 30-APR-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
May | 28392.87 | 06-MAY-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 169.57 | 0.00 |
June | 27094.97 | 07-JUN-07:01 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 330.80 | 0.00 |
July | 24704.65 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 266.81 | 0.00 |
August | 23667.11 | 03-AUG-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 0.00 |
September | 25453.46 | 26-SEP-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 0.00 |
October | 26595.07 | 02-OCT-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 |
November | 9014.44 | 09-NOV-08:63 | 506.24 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.40 |
December | 5399.00 | 02-DEC-14:00 | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4343.40 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28392.87 | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 156.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3907.51 | 12-JAN-15:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 6042.30 | 22-FEB-14:00 | 1349.97 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 0.00 |
March | 18545.30 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 28825.03 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
May | 28999.98 | 06-MAY-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
June | 26085.26 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 0.00 |
July | 21694.44 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
August | 19166.57 | 03-AUG-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 0.00 |
September | 21906.71 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 25878.46 | 02-OCT-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
November | 8494.64 | 09-NOV-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
December | 5211.79 | 02-DEC-14:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3907.51 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28999.98 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3776.90 | 12-JAN-15:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 5968.33 | 22-FEB-14:00 | 1349.97 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 0.00 |
March | 18717.35 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 28946.59 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
May | 29109.44 | 06-MAY-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
June | 26413.94 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 0.00 |
July | 21860.25 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 0.00 |
August | 19293.90 | 03-AUG-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
September | 22018.60 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
October | 26707.08 | 23-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
November | 8329.45 | 09-NOV-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
December | 5142.10 | 02-DEC-14:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3776.90 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29109.44 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3634.10 | 03-JAN-07:05 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 |
February | 5788.24 | 22-FEB-14:00 | 1349.97 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 17266.17 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 28648.56 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
May | 28904.51 | 06-MAY-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
June | 26250.20 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
July | 21568.37 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
August | 19013.24 | 03-AUG-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
September | 21775.99 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 25883.72 | 02-OCT-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
November | 7883.66 | 04-NOV-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 0.00 |
December | 4962.61 | 02-DEC-14:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3634.10 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28904.51 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 7.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7005.76 | 04-JAN-08:03 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.96 |
February | 10327.28 | 22-FEB-15:10 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.20 | 0.00 |
March | 26963.08 | 11-MAR-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 | 0.00 |
April | 50640.78 | 20-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 | 0.00 |
May | 51793.96 | 29-MAY-08:61 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 415.28 | 0.00 |
June | 47500.50 | 07-JUN-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 572.71 | 0.00 |
July | 41151.08 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 444.75 | 0.00 |
August | 37529.16 | 08-AUG-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 256.44 | 0.00 |
September | 41367.30 | 27-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
October | 45712.25 | 02-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
November | 14356.85 | 04-NOV-14:20 | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.63 | 0.00 |
December | 8478.43 | 02-DEC-14:30 | 5197.55 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7005.76 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51793.96 | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.63 | 1055.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3491.07 | 04-JAN-08:03 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.88 |
February | 5396.64 | 22-FEB-15:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 12796.99 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 0.00 |
April | 26456.52 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 | 0.00 |
May | 27063.70 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 234.48 | 0.00 |
June | 24793.03 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 328.82 | 0.00 |
July | 21506.18 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 257.24 | 0.00 |
August | 19617.82 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 149.53 | 0.00 |
September | 21576.99 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | 0.00 |
October | 23804.74 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
November | 7558.50 | 04-NOV-14:20 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 4377.14 | 02-DEC-14:30 | 2598.70 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3491.07 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27063.70 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 603.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3530.61 | 04-JAN-08:03 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.15 |
February | 5335.81 | 22-FEB-15:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 12403.74 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 | 0.00 |
April | 26357.56 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 | 0.00 |
May | 26989.29 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 234.50 | 0.00 |
June | 24701.76 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 329.21 | 0.00 |
July | 21419.13 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 257.56 | 0.00 |
August | 19541.58 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 149.77 | 0.00 |
September | 21483.52 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 0.00 |
October | 23728.22 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 7511.89 | 04-NOV-14:20 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 4318.52 | 02-DEC-14:30 | 2598.70 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3530.61 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26989.29 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 605.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3493.08 | 04-JAN-08:03 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.92 |
February | 5222.08 | 22-FEB-15:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 11069.22 | 30-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.22 |
April | 26391.19 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 85.12 | 0.00 |
May | 27108.81 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 233.15 | 0.00 |
June | 24877.51 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 327.14 | 0.00 |
July | 21617.25 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 255.27 | 0.00 |
August | 19744.63 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 | 0.00 |
September | 21600.51 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 0.00 |
October | 23842.07 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
November | 7467.91 | 04-NOV-14:20 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 4179.19 | 02-DEC-14:30 | 2598.70 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3493.08 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27108.81 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 596.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3735.13 | 05-JAN-08:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.61 |
February | 5856.93 | 22-FEB-14:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 801.68 | 0.00 |
March | 10075.57 | 28-MAR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 29529.19 | 30-APR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 0.00 |
May | 30973.67 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 265.81 | 0.00 |
June | 29232.67 | 12-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 327.94 | 0.00 |
July | 25314.60 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 256.66 | 0.00 |
August | 22320.48 | 09-AUG-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 135.45 | 0.00 |
September | 24851.57 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
October | 27029.40 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
November | 8355.78 | 04-NOV-14:10 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.33 | 0.00 |
December | 4468.34 | 01-DEC-14:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3735.13 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30973.67 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 610.61 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.699586E+11 | 61993.97 | 14-JAN-13:30 | 0.546001E+10 | 120561.66 | 02-JAN-08:09 |
February | 0.704621E+11 | 72202.82 | 21-FEB-15:20 | 0.723167E+09 | 36229.19 | 02-FEB-08:09 |
March | 0.940801E+11 | 91363.34 | 28-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.110391E+12 | 110834.79 | 16-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.135795E+12 | 126806.48 | 03-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.140033E+12 | 137601.03 | 22-JUN-16:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.142538E+12 | 139987.70 | 01-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.141557E+12 | 133574.05 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.124975E+12 | 120271.90 | 14-SEP-16:49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.108808E+12 | 105971.05 | 02-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.871279E+11 | 83962.17 | 04-NOV-13:00 | 851023.81 | 946.80 | 27-NOV-08:30 |
December | 0.728644E+11 | 65443.19 | 28-DEC-15:30 | 0.978422E+09 | 57602.46 | 23-DEC-08:09 |
Annual Sum or Average | 0.129859E+13 | 0.716245E+10 | ||||
Minimum of Months | 0.699586E+11 | 61993.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.142538E+12 | 139987.70 | 0.546001E+10 | 120561.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.606628E+10 | 0.108325E+11 | 0.00 | 0.108194E+11 | 0.00 | 0.00 | 0.248240E+10 | 0.00 | 0.00 | 0.00 | 0.522995E+10 | 0.00 |
February | 0.312534E+11 | 0.516426E+10 | 0.980803E+10 | 0.00 | 0.972784E+10 | 0.00 | 0.00 | 0.981386E+10 | 0.00 | 0.00 | 0.00 | 0.469473E+10 | 0.00 |
March | 0.350527E+11 | 0.520718E+10 | 0.110075E+11 | 0.00 | 0.109368E+11 | 0.00 | 0.00 | 0.267421E+11 | 0.00 | 0.00 | 0.00 | 0.513388E+10 | 0.00 |
April | 0.334898E+11 | 0.453974E+10 | 0.105079E+11 | 0.00 | 0.105788E+11 | 0.00 | 0.00 | 0.464514E+11 | 0.00 | 0.00 | 0.00 | 0.482302E+10 | 0.00 |
May | 0.347840E+11 | 0.425226E+10 | 0.109147E+11 | 0.00 | 0.119853E+11 | 0.00 | 0.00 | 0.689896E+11 | 0.00 | 0.00 | 0.00 | 0.486936E+10 | 0.00 |
June | 0.338757E+11 | 0.387889E+10 | 0.106386E+11 | 0.00 | 0.124140E+11 | 0.00 | 0.00 | 0.745921E+11 | 0.00 | 0.00 | 0.00 | 0.463397E+10 | 0.00 |
July | 0.344108E+11 | 0.413661E+10 | 0.107945E+11 | 0.00 | 0.127698E+11 | 0.00 | 0.00 | 0.757009E+11 | 0.00 | 0.00 | 0.00 | 0.472528E+10 | 0.00 |
August | 0.350409E+11 | 0.449016E+10 | 0.110006E+11 | 0.00 | 0.127768E+11 | 0.00 | 0.00 | 0.734648E+11 | 0.00 | 0.00 | 0.00 | 0.478373E+10 | 0.00 |
September | 0.335014E+11 | 0.482390E+10 | 0.105148E+11 | 0.00 | 0.112054E+11 | 0.00 | 0.00 | 0.602391E+11 | 0.00 | 0.00 | 0.00 | 0.469012E+10 | 0.00 |
October | 0.345281E+11 | 0.550456E+10 | 0.108325E+11 | 0.00 | 0.108310E+11 | 0.00 | 0.00 | 0.421527E+11 | 0.00 | 0.00 | 0.00 | 0.495879E+10 | 0.00 |
November | 0.334535E+11 | 0.575900E+10 | 0.104978E+11 | 0.00 | 0.104202E+11 | 0.00 | 0.00 | 0.220759E+11 | 0.00 | 0.00 | 0.00 | 0.492136E+10 | 0.00 |
December | 0.344233E+11 | 0.622158E+10 | 0.108050E+11 | 0.00 | 0.107038E+11 | 0.00 | 0.00 | 0.552811E+10 | 0.00 | 0.00 | 0.00 | 0.518259E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.600444E+11 | 0.128154E+12 | 0.00 | 0.135169E+12 | 0.00 | 0.00 | 0.508233E+12 | 0.00 | 0.00 | 0.00 | 0.586468E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.387889E+10 | 0.980803E+10 | 0.00 | 0.972784E+10 | 0.00 | 0.00 | 0.248240E+10 | 0.00 | 0.00 | 0.00 | 0.463397E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.622158E+10 | 0.110075E+11 | 0.00 | 0.127768E+11 | 0.00 | 0.00 | 0.757009E+11 | 0.00 | 0.00 | 0.00 | 0.522995E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.546001E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.723167E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 851023.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.978422E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.716245E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.546001E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9901.36 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8136.83 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7846.57 | 11-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9203.70 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 11336.69 | 17-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 13551.62 | 22-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 13686.80 | 01-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 13164.19 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11202.81 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9025.39 | 03-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7398.29 | 27-NOV-08:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8583.95 | 23-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 7398.29 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 13686.80 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 13633.30 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 10441.96 | 21-JAN-12:50 | 0.00 |
February | 24984.36 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9170.31 | 15-FEB-14:09 | 0.00 |
March | 44681.47 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7563.19 | 08-MAR-13:09 | 0.00 |
April | 63687.07 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 7553.74 | 08-APR-12:20 | 0.00 |
May | 77249.98 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7543.70 | 03-MAY-13:09 | 0.00 |
June | 87259.27 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 7534.02 | 14-JUN-12:20 | 0.00 |
July | 85368.12 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 8365.39 | 01-JUL-10:30 | 0.00 |
August | 80680.89 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 7534.00 | 23-AUG-12:00 | 0.00 |
September | 69717.93 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 9561.55 | 26-SEP-14:39 | 0.00 |
October | 56359.29 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 7869.76 | 07-OCT-16:19 | 0.00 |
November | 34709.83 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7560.86 | 28-NOV-14:50 | 0.00 |
December | 17704.60 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9441.89 | 21-DEC-10:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13633.30 | 0.00 | 0.00 | 0.00 | 7534.00 | 0.00 | ||
Maximum of Months | 87259.27 | 0.00 | 0.00 | 0.00 | 10441.96 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61993.97 | 14-JAN-13:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 10608.35 | 0.00 |
February | 72202.82 | 21-FEB-15:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 21775.76 | 0.00 |
March | 91363.34 | 28-MAR-14:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 44681.47 | 0.00 |
April | 110834.79 | 16-APR-15:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8880.49 | 0.00 | 0.00 | 62219.07 | 0.00 |
May | 126806.48 | 03-MAY-16:10 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11044.45 | 0.00 | 0.00 | 76018.97 | 0.00 |
June | 137601.03 | 22-JUN-16:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 13496.36 | 0.00 | 0.00 | 86471.23 | 0.00 |
July | 139987.70 | 01-JUL-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 13455.22 | 0.00 | 0.00 | 84682.24 | 0.00 |
August | 133574.05 | 27-AUG-14:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 13164.19 | 0.00 | 0.00 | 80680.89 | 0.00 |
September | 120271.90 | 14-SEP-16:49 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11104.84 | 0.00 | 0.00 | 69130.53 | 0.00 |
October | 105971.05 | 02-OCT-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8178.04 | 0.00 | 0.00 | 56137.67 | 0.00 |
November | 83962.17 | 04-NOV-13:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 34709.83 | 0.00 |
December | 65443.19 | 28-DEC-15:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 16886.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61993.97 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7378.46 | 0.00 | 0.00 | 10608.35 | 0.00 | |
Maximum of Months | 139987.70 | 26261.30 | 8059.50 | 0.00 | 0.00 | 13496.36 | 0.00 | 0.00 | 86471.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 120561.66 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 36229.19 | 02-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 946.80 | 27-NOV-08:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 57602.46 | 23-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 120561.66 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 0.83 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 24.51 | 1.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 0.83 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.49 | 0.00 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.61 | 0.00 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.52 | 0.00 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.64 | 0.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 0.00 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.00 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.64 | 0.00 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.64 | 0.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.57 | 0.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 24.58 | 0.00 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.64 | 0.00 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.78 | 0.00 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.72 | 0.00 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.72 | 0.00 | 24.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.78 | 0.00 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.75 | 0.00 | 24.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.74 | 0.00 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.75 | 0.00 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.76 | 0.00 | 24.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.74 | 0.00 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.76 | 0.00 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.62 | 0.00 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.75 | 0.00 | 24.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.75 | 0.00 | 24.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.75 | 0.00 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.18 | 0.00 | 26.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.29 | 0.00 | 25.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.76 | 0.00 | 24.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 25.21 | 0.00 | 25.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.18 | 0.00 | 26.18 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.17 | 22.54 | 11.50 | 22.59 | 0.00 | 22.59 |
February | 123.00 | 22.62 | 113.67 | 23.23 | 0.00 | 23.23 |
March | 32.33 | 23.25 | 322.00 | 23.83 | 0.00 | 23.83 |
April | 2.50 | 23.82 | 430.17 | 23.89 | 0.00 | 23.89 |
May | 23.33 | 23.90 | 496.00 | 23.89 | 23.33 | 23.89 |
June | 130.83 | 23.89 | 481.00 | 23.89 | 130.83 | 23.89 |
July | 360.17 | 23.90 | 495.00 | 23.89 | 360.17 | 23.89 |
August | 401.33 | 23.89 | 497.00 | 23.89 | 401.33 | 23.89 |
September | 256.17 | 23.89 | 479.00 | 23.89 | 256.17 | 23.89 |
October | 6.00 | 23.84 | 479.17 | 23.89 | 5.50 | 23.89 |
November | 35.17 | 23.20 | 329.67 | 23.82 | 0.00 | 23.82 |
December | 200.83 | 22.65 | 65.33 | 22.95 | 0.00 | 22.95 |
Annual Sum or Average | 1890.83 | 23.43 | 4199.50 | 23.75 | 1177.33 | 23.77 |
Minimum of Months | 2.50 | 22.54 | 11.50 | 22.59 | 0.00 | 22.59 |
Maximum of Months | 401.33 | 23.90 | 497.00 | 23.89 | 401.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 219.83 | 22.89 | 22.83 | 22.98 | 0.00 | 22.98 |
February | 80.83 | 22.89 | 113.33 | 23.47 | 0.00 | 23.47 |
March | 22.00 | 23.48 | 297.67 | 23.86 | 0.00 | 23.86 |
April | 1.33 | 23.78 | 405.83 | 23.89 | 0.00 | 23.89 |
May | 15.00 | 23.89 | 496.00 | 23.89 | 15.00 | 23.89 |
June | 105.33 | 23.89 | 481.00 | 23.89 | 105.33 | 23.89 |
July | 283.50 | 23.89 | 495.00 | 23.89 | 283.50 | 23.89 |
August | 313.67 | 23.89 | 497.00 | 23.89 | 313.67 | 23.89 |
September | 191.50 | 23.89 | 479.00 | 23.89 | 191.50 | 23.89 |
October | 1.50 | 23.72 | 456.00 | 23.89 | 0.83 | 23.89 |
November | 25.67 | 23.40 | 294.33 | 23.85 | 0.00 | 23.85 |
December | 137.50 | 23.01 | 66.67 | 23.30 | 0.00 | 23.30 |
Annual Sum or Average | 1397.67 | 23.57 | 4104.67 | 23.81 | 909.83 | 23.82 |
Minimum of Months | 1.33 | 22.89 | 22.83 | 22.98 | 0.00 | 22.98 |
Maximum of Months | 313.67 | 23.89 | 497.00 | 23.89 | 313.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 202.33 | 22.57 | 10.83 | 22.64 | 0.00 | 22.64 |
February | 74.00 | 22.65 | 88.17 | 23.41 | 0.00 | 23.41 |
March | 17.17 | 23.55 | 266.33 | 24.06 | 0.67 | 24.07 |
April | 8.17 | 28.27 | 322.33 | 24.27 | 8.00 | 24.37 |
May | 36.83 | 26.33 | 375.00 | 24.38 | 36.83 | 24.54 |
June | 130.17 | 24.68 | 366.00 | 24.32 | 130.17 | 24.40 |
July | 293.50 | 24.25 | 369.00 | 24.21 | 293.50 | 24.22 |
August | 329.33 | 24.18 | 379.00 | 24.16 | 329.33 | 24.17 |
September | 213.17 | 24.27 | 360.00 | 24.19 | 213.17 | 24.21 |
October | 11.67 | 26.03 | 361.67 | 24.16 | 11.67 | 24.22 |
November | 17.83 | 23.15 | 252.17 | 23.96 | 0.00 | 23.96 |
December | 119.83 | 22.72 | 41.00 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 1454.00 | 23.90 | 3191.50 | 24.06 | 1023.33 | 24.13 |
Minimum of Months | 8.17 | 22.57 | 10.83 | 22.64 | 0.00 | 22.64 |
Maximum of Months | 329.33 | 28.27 | 379.00 | 24.38 | 329.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 230.50 | 22.62 | 9.50 | 22.67 | 0.00 | 22.67 |
February | 77.33 | 22.63 | 76.83 | 23.34 | 0.00 | 23.34 |
March | 18.17 | 23.49 | 264.00 | 24.05 | 0.50 | 24.06 |
April | 8.17 | 28.28 | 323.17 | 24.27 | 8.00 | 24.37 |
May | 36.67 | 26.37 | 375.00 | 24.39 | 36.67 | 24.55 |
June | 129.17 | 24.69 | 366.00 | 24.32 | 129.17 | 24.40 |
July | 290.83 | 24.25 | 369.00 | 24.21 | 290.83 | 24.22 |
August | 327.00 | 24.18 | 379.00 | 24.16 | 327.00 | 24.17 |
September | 211.67 | 24.28 | 360.00 | 24.19 | 211.67 | 24.21 |
October | 11.83 | 26.05 | 362.33 | 24.16 | 11.83 | 24.22 |
November | 18.67 | 23.12 | 248.17 | 23.96 | 0.00 | 23.96 |
December | 127.83 | 22.70 | 34.67 | 22.97 | 0.00 | 22.97 |
Annual Sum or Average | 1487.83 | 23.87 | 3167.67 | 24.05 | 1015.67 | 24.12 |
Minimum of Months | 8.17 | 22.62 | 9.50 | 22.67 | 0.00 | 22.67 |
Maximum of Months | 327.00 | 28.28 | 379.00 | 24.39 | 327.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.17 | 22.64 | 7.83 | 22.67 | 0.17 | 22.67 |
February | 86.50 | 22.62 | 68.50 | 23.25 | 0.00 | 23.25 |
March | 21.00 | 23.44 | 253.17 | 24.04 | 0.50 | 24.05 |
April | 8.00 | 28.25 | 320.33 | 24.27 | 7.83 | 24.37 |
May | 37.17 | 26.30 | 375.00 | 24.38 | 37.17 | 24.54 |
June | 130.50 | 24.67 | 366.00 | 24.32 | 130.50 | 24.39 |
July | 293.17 | 24.25 | 369.00 | 24.21 | 293.17 | 24.22 |
August | 330.67 | 24.18 | 379.00 | 24.16 | 330.67 | 24.16 |
September | 214.17 | 24.27 | 360.00 | 24.18 | 214.17 | 24.21 |
October | 11.83 | 25.89 | 361.67 | 24.15 | 11.83 | 24.21 |
November | 22.00 | 23.11 | 237.83 | 23.94 | 0.00 | 23.94 |
December | 143.00 | 22.69 | 25.83 | 22.88 | 0.00 | 22.88 |
Annual Sum or Average | 1565.17 | 23.82 | 3124.17 | 24.03 | 1026.00 | 24.10 |
Minimum of Months | 8.00 | 22.62 | 7.83 | 22.67 | 0.00 | 22.67 |
Maximum of Months | 330.67 | 28.25 | 379.00 | 24.38 | 330.67 | 24.54 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.33 | 22.71 | 0.67 | 22.72 | 0.17 | 22.71 |
February | 98.67 | 22.89 | 45.00 | 23.22 | 0.00 | 23.22 |
March | 17.50 | 23.47 | 198.83 | 23.93 | 0.50 | 23.94 |
April | 4.33 | 28.41 | 284.17 | 24.07 | 4.17 | 24.14 |
May | 24.50 | 25.28 | 344.00 | 24.09 | 24.50 | 24.16 |
June | 118.17 | 24.15 | 336.00 | 24.03 | 118.17 | 24.06 |
July | 276.33 | 24.05 | 338.00 | 24.03 | 276.33 | 24.04 |
August | 321.50 | 23.98 | 348.00 | 23.97 | 321.50 | 23.97 |
September | 198.50 | 24.05 | 330.00 | 24.01 | 198.50 | 24.02 |
October | 11.17 | 25.21 | 332.17 | 24.02 | 11.17 | 24.06 |
November | 14.33 | 23.28 | 200.17 | 23.90 | 0.00 | 23.90 |
December | 162.67 | 22.86 | 5.17 | 22.89 | 0.00 | 22.89 |
Annual Sum or Average | 1540.00 | 23.62 | 2762.17 | 23.85 | 955.00 | 23.90 |
Minimum of Months | 4.33 | 22.71 | 0.67 | 22.72 | 0.00 | 22.71 |
Maximum of Months | 321.50 | 28.41 | 348.00 | 24.09 | 321.50 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.33 | 22.72 | 0.17 | 22.72 | 0.17 | 22.72 |
February | 112.33 | 22.98 | 34.50 | 23.22 | 0.00 | 23.22 |
March | 21.17 | 23.53 | 183.83 | 23.93 | 0.50 | 23.94 |
April | 4.17 | 28.38 | 268.33 | 24.08 | 4.00 | 24.15 |
May | 25.00 | 25.24 | 344.00 | 24.09 | 25.00 | 24.16 |
June | 118.83 | 24.15 | 336.00 | 24.03 | 118.83 | 24.05 |
July | 277.67 | 24.04 | 338.00 | 24.03 | 277.67 | 24.03 |
August | 321.67 | 23.98 | 348.00 | 23.97 | 321.67 | 23.97 |
September | 201.83 | 24.04 | 330.00 | 24.01 | 201.83 | 24.02 |
October | 13.00 | 24.83 | 328.00 | 24.02 | 13.00 | 24.05 |
November | 16.67 | 23.37 | 175.17 | 23.91 | 0.00 | 23.91 |
December | 173.83 | 22.91 | 2.33 | 22.93 | 0.00 | 22.93 |
Annual Sum or Average | 1586.50 | 23.61 | 2688.33 | 23.85 | 962.67 | 23.89 |
Minimum of Months | 4.17 | 22.72 | 0.17 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 321.67 | 28.38 | 348.00 | 24.09 | 321.67 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 303.83 | 22.70 | 0.17 | 22.69 | 0.17 | 22.69 |
February | 119.67 | 23.00 | 33.67 | 23.21 | 0.00 | 23.21 |
March | 22.83 | 23.52 | 180.83 | 23.93 | 0.50 | 23.94 |
April | 4.17 | 28.21 | 266.33 | 24.08 | 3.83 | 24.14 |
May | 25.17 | 25.23 | 344.00 | 24.09 | 25.17 | 24.16 |
June | 118.83 | 24.15 | 336.00 | 24.03 | 118.83 | 24.05 |
July | 277.83 | 24.04 | 338.00 | 24.03 | 277.83 | 24.03 |
August | 322.00 | 23.98 | 348.00 | 23.97 | 322.00 | 23.97 |
September | 202.17 | 24.04 | 330.00 | 24.01 | 202.17 | 24.02 |
October | 13.67 | 24.79 | 327.50 | 24.02 | 13.67 | 24.05 |
November | 18.17 | 23.38 | 172.00 | 23.90 | 0.00 | 23.90 |
December | 181.83 | 22.92 | 0.33 | 22.92 | 0.00 | 22.92 |
Annual Sum or Average | 1610.17 | 23.60 | 2676.83 | 23.84 | 964.17 | 23.89 |
Minimum of Months | 4.17 | 22.70 | 0.17 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 322.00 | 28.21 | 348.00 | 24.09 | 322.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.00 | 22.64 | 0.83 | 22.64 | 0.83 | 22.64 |
February | 135.00 | 23.00 | 31.67 | 23.19 | 0.00 | 23.19 |
March | 27.17 | 23.47 | 176.67 | 23.91 | 0.50 | 23.92 |
April | 4.33 | 28.20 | 269.00 | 24.08 | 4.00 | 24.14 |
May | 25.17 | 25.23 | 344.00 | 24.09 | 25.17 | 24.16 |
June | 118.67 | 24.15 | 336.00 | 24.03 | 118.67 | 24.05 |
July | 275.83 | 24.05 | 338.00 | 24.03 | 275.83 | 24.04 |
August | 319.00 | 23.98 | 348.00 | 23.97 | 319.00 | 23.97 |
September | 200.33 | 24.05 | 330.00 | 24.01 | 200.33 | 24.02 |
October | 14.17 | 24.76 | 327.33 | 24.02 | 14.17 | 24.05 |
November | 20.83 | 23.34 | 168.83 | 23.89 | 0.00 | 23.89 |
December | 195.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
Annual Sum or Average | 1648.33 | 23.57 | 2670.33 | 23.83 | 958.50 | 23.88 |
Minimum of Months | 4.33 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
Maximum of Months | 319.00 | 28.20 | 348.00 | 24.09 | 319.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.83 | 22.61 | 2.83 | 22.60 | 2.83 | 22.58 |
February | 138.17 | 22.89 | 31.17 | 23.09 | 0.00 | 23.09 |
March | 32.00 | 23.32 | 195.83 | 23.88 | 0.67 | 23.89 |
April | 5.83 | 27.93 | 299.33 | 24.08 | 5.00 | 24.16 |
May | 24.67 | 25.43 | 344.00 | 24.10 | 24.67 | 24.19 |
June | 101.83 | 24.22 | 336.00 | 24.05 | 101.83 | 24.08 |
July | 256.67 | 24.07 | 338.00 | 24.05 | 256.67 | 24.05 |
August | 281.67 | 24.00 | 348.00 | 23.99 | 281.67 | 23.99 |
September | 178.83 | 24.08 | 330.00 | 24.03 | 178.83 | 24.04 |
October | 11.33 | 25.70 | 331.33 | 24.05 | 11.00 | 24.10 |
November | 23.00 | 23.21 | 198.17 | 23.88 | 0.00 | 23.88 |
December | 199.83 | 22.81 | 2.17 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 1566.67 | 23.53 | 2756.83 | 23.83 | 863.17 | 23.88 |
Minimum of Months | 5.83 | 22.61 | 2.17 | 22.60 | 0.00 | 22.58 |
Maximum of Months | 312.83 | 27.93 | 348.00 | 24.10 | 281.67 | 24.19 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.01033 | 41.27147 | 0.13290 | 6.55775 |
February | 448.00000 | 23.53407 | 42.52254 | 0.30445 | 7.66113 |
March | 497.00000 | 23.84658 | 42.50614 | 0.44061 | 9.26620 |
April | 479.00000 | 23.88842 | 42.27633 | 0.52363 | 10.87490 |
May | 496.00000 | 23.89191 | 51.35737 | -0.1942 | 5.91536 |
June | 481.00000 | 23.89282 | 57.76281 | -0.1319 | 5.49059 |
July | 495.00000 | 23.89389 | 64.64645 | -0.0949 | 5.28307 |
August | 497.00000 | 23.89314 | 66.44345 | -0.0965 | 5.29989 |
September | 479.00000 | 23.89148 | 63.34534 | -0.1424 | 5.52972 |
October | 496.00000 | 23.88553 | 48.72137 | 0.56188 | 11.72135 |
November | 480.00000 | 23.83531 | 42.49840 | 0.43957 | 9.22727 |
December | 496.00000 | 23.37591 | 40.08823 | 0.24096 | 7.15608 |
Annual Sum or Average | 5840.00000 | 23.73674 | 50.33689 | 0.16412 | 7.49390 |
Minimum of Months | 448.00000 | 23.01033 | 40.08823 | -0.1942 | 5.28307 |
Maximum of Months | 497.00000 | 23.89389 | 66.44345 | 0.56188 | 11.72135 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.43631 | 40.60523 | 0.23635 | 6.92025 |
February | 448.00000 | 23.70721 | 40.88367 | 0.34442 | 7.87161 |
March | 497.00000 | 23.87030 | 40.96974 | 0.43579 | 9.09947 |
April | 479.00000 | 23.88789 | 41.35468 | 0.49759 | 10.28081 |
May | 496.00000 | 23.89166 | 49.86959 | -0.2477 | 6.38318 |
June | 481.00000 | 23.89217 | 55.95742 | -0.1938 | 5.90209 |
July | 495.00000 | 23.89272 | 62.44394 | -0.1559 | 5.61721 |
August | 497.00000 | 23.89229 | 64.07138 | -0.1574 | 5.65577 |
September | 479.00000 | 23.89121 | 60.59790 | -0.1999 | 5.97208 |
October | 496.00000 | 23.88576 | 46.47797 | 0.52776 | 10.94162 |
November | 480.00000 | 23.86246 | 40.68340 | 0.43055 | 8.99762 |
December | 496.00000 | 23.64508 | 38.85211 | 0.30238 | 7.41664 |
Annual Sum or Average | 5840.00000 | 23.81301 | 48.61458 | 0.15028 | 7.58347 |
Minimum of Months | 448.00000 | 23.43631 | 38.85211 | -0.2477 | 5.61721 |
Maximum of Months | 497.00000 | 23.89272 | 64.07138 | 0.52776 | 10.94162 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.15203 | 39.52597 | 0.16523 | 6.65890 |
February | 336.00000 | 23.66238 | 40.80033 | 0.33064 | 7.90849 |
March | 379.00000 | 24.00789 | 41.12925 | 0.46500 | 9.79375 |
April | 360.00000 | 24.14399 | 41.12131 | 0.54908 | 11.76384 |
May | 375.00000 | 24.19038 | 50.61560 | -0.1552 | 6.54951 |
June | 366.00000 | 24.19608 | 57.34190 | -0.0954 | 6.32822 |
July | 369.00000 | 24.17750 | 65.05137 | -0.0552 | 6.15017 |
August | 379.00000 | 24.14357 | 67.23373 | -0.0621 | 5.95943 |
September | 360.00000 | 24.13600 | 63.62180 | -0.1073 | 6.03681 |
October | 371.00000 | 24.09477 | 47.79311 | 0.58454 | 12.47108 |
November | 360.00000 | 23.94583 | 40.85319 | 0.45301 | 9.49240 |
December | 369.00000 | 23.51225 | 37.98123 | 0.26847 | 7.25673 |
Annual Sum or Average | 4395.00000 | 23.94869 | 49.50524 | 0.19332 | 8.02498 |
Minimum of Months | 336.00000 | 23.15203 | 37.98123 | -0.1552 | 5.95943 |
Maximum of Months | 379.00000 | 24.19608 | 67.23373 | 0.58454 | 12.47108 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.08803 | 39.72109 | 0.14359 | 6.57667 |
February | 336.00000 | 23.64160 | 40.90044 | 0.32197 | 7.82926 |
March | 379.00000 | 24.00534 | 41.14458 | 0.46358 | 9.77095 |
April | 360.00000 | 24.14447 | 41.09923 | 0.55055 | 11.80054 |
May | 375.00000 | 24.19140 | 50.55265 | -0.1513 | 6.53417 |
June | 366.00000 | 24.19699 | 57.25318 | -0.0918 | 6.32454 |
July | 369.00000 | 24.17852 | 64.92075 | -0.0518 | 6.15499 |
August | 379.00000 | 24.14434 | 67.12562 | -0.0597 | 5.96149 |
September | 360.00000 | 24.13668 | 63.53172 | -0.1051 | 6.03379 |
October | 371.00000 | 24.09505 | 47.75975 | 0.58560 | 12.49860 |
November | 360.00000 | 23.94114 | 40.88574 | 0.45044 | 9.45277 |
December | 369.00000 | 23.48122 | 38.10241 | 0.25674 | 7.18392 |
Annual Sum or Average | 4395.00000 | 23.93892 | 49.49848 | 0.19103 | 8.00470 |
Minimum of Months | 336.00000 | 23.08803 | 38.10241 | -0.1513 | 5.96149 |
Maximum of Months | 379.00000 | 24.19699 | 67.12562 | 0.58560 | 12.49860 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.98903 | 40.01327 | 0.11325 | 6.45837 |
February | 336.00000 | 23.59907 | 41.11624 | 0.30616 | 7.67902 |
March | 379.00000 | 23.99431 | 41.27750 | 0.45642 | 9.64081 |
April | 360.00000 | 24.14062 | 41.16445 | 0.54629 | 11.69237 |
May | 375.00000 | 24.18806 | 50.64965 | -0.1553 | 6.53217 |
June | 366.00000 | 24.19385 | 57.39361 | -0.0954 | 6.30893 |
July | 369.00000 | 24.17536 | 65.09443 | -0.0546 | 6.13504 |
August | 379.00000 | 24.14074 | 67.34495 | -0.0630 | 5.94247 |
September | 360.00000 | 24.13296 | 63.75748 | -0.1089 | 6.02510 |
October | 371.00000 | 24.09106 | 47.89961 | 0.58212 | 12.40506 |
November | 360.00000 | 23.92898 | 41.01753 | 0.44341 | 9.33116 |
December | 369.00000 | 23.42724 | 38.31819 | 0.23827 | 7.06852 |
Annual Sum or Average | 4395.00000 | 23.91876 | 49.66912 | 0.18241 | 7.93010 |
Minimum of Months | 336.00000 | 22.98903 | 38.31819 | -0.1553 | 5.94247 |
Maximum of Months | 379.00000 | 24.19385 | 67.34495 | 0.58212 | 12.40506 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.88014 | 41.67830 | 0.07134 | 6.18737 |
February | 308.00000 | 23.57822 | 42.29752 | 0.28734 | 7.35191 |
March | 348.00000 | 23.90802 | 42.25032 | 0.43391 | 9.14687 |
April | 330.00000 | 23.99149 | 42.21188 | 0.52148 | 10.98688 |
May | 344.00000 | 24.00484 | 51.97275 | -0.1946 | 6.34027 |
June | 336.00000 | 23.98847 | 58.77034 | -0.1398 | 5.90610 |
July | 338.00000 | 24.01970 | 66.40692 | -0.0885 | 5.85139 |
August | 348.00000 | 23.97056 | 68.76346 | -0.1019 | 5.64914 |
September | 330.00000 | 23.98761 | 65.05123 | -0.1440 | 5.88764 |
October | 340.00000 | 23.98105 | 48.79725 | 0.56371 | 11.86898 |
November | 330.00000 | 23.89998 | 41.82077 | 0.43169 | 9.04048 |
December | 338.00000 | 23.38890 | 39.94798 | 0.21738 | 6.81430 |
Annual Sum or Average | 4030.00000 | 23.80115 | 50.91643 | 0.15301 | 7.58090 |
Minimum of Months | 308.00000 | 22.88014 | 39.94798 | -0.1946 | 5.64914 |
Maximum of Months | 348.00000 | 24.01970 | 68.76346 | 0.56371 | 11.86898 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.85471 | 41.62050 | 0.05669 | 6.14009 |
February | 308.00000 | 23.57227 | 42.25541 | 0.27482 | 7.20834 |
March | 348.00000 | 23.90756 | 42.22427 | 0.41925 | 8.87588 |
April | 330.00000 | 23.99046 | 42.14931 | 0.50134 | 10.54300 |
May | 344.00000 | 24.00409 | 51.94791 | -0.2261 | 6.60417 |
June | 336.00000 | 23.98755 | 58.82681 | -0.1718 | 6.10258 |
July | 338.00000 | 24.01858 | 66.60241 | -0.1181 | 5.96429 |
August | 348.00000 | 23.96986 | 69.02296 | -0.1300 | 5.77727 |
September | 330.00000 | 23.98637 | 65.23867 | -0.1709 | 6.05295 |
October | 340.00000 | 23.98040 | 48.83129 | 0.54526 | 11.43051 |
November | 330.00000 | 23.90020 | 41.80092 | 0.41769 | 8.78386 |
December | 338.00000 | 23.38278 | 39.88019 | 0.20600 | 6.72443 |
Annual Sum or Average | 4030.00000 | 23.79748 | 50.95326 | 0.13179 | 7.51362 |
Minimum of Months | 308.00000 | 22.85471 | 39.88019 | -0.2261 | 5.77727 |
Maximum of Months | 348.00000 | 24.01858 | 69.02296 | 0.54526 | 11.43051 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.82325 | 41.70626 | 0.04640 | 6.12506 |
February | 308.00000 | 23.55778 | 42.32676 | 0.26847 | 7.15967 |
March | 348.00000 | 23.90496 | 42.26409 | 0.41634 | 8.82955 |
April | 330.00000 | 23.99014 | 42.16695 | 0.49963 | 10.50633 |
May | 344.00000 | 24.00392 | 51.97563 | -0.2279 | 6.61995 |
June | 336.00000 | 23.98737 | 58.86712 | -0.1735 | 6.11337 |
July | 338.00000 | 24.01833 | 66.65090 | -0.1195 | 5.96916 |
August | 348.00000 | 23.96967 | 69.07822 | -0.1314 | 5.78319 |
September | 330.00000 | 23.98609 | 65.29414 | -0.1724 | 6.06170 |
October | 340.00000 | 23.98006 | 48.86733 | 0.54385 | 11.39740 |
November | 330.00000 | 23.89803 | 41.83889 | 0.41512 | 8.74232 |
December | 338.00000 | 23.36126 | 39.95363 | 0.19834 | 6.68583 |
Annual Sum or Average | 4030.00000 | 23.79137 | 51.00225 | 0.12840 | 7.49608 |
Minimum of Months | 308.00000 | 22.82325 | 39.95363 | -0.2279 | 5.78319 |
Maximum of Months | 348.00000 | 24.01833 | 69.07822 | 0.54385 | 11.39740 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.74807 | 41.90904 | 0.02437 | 6.12826 |
February | 308.00000 | 23.51397 | 42.52426 | 0.25344 | 7.07740 |
March | 348.00000 | 23.89544 | 42.36744 | 0.41172 | 8.77407 |
April | 330.00000 | 23.99007 | 42.17740 | 0.50184 | 10.55685 |
May | 344.00000 | 24.00415 | 51.94215 | -0.2214 | 6.56320 |
June | 336.00000 | 23.98761 | 58.79718 | -0.1667 | 6.06956 |
July | 338.00000 | 24.01884 | 66.51185 | -0.1127 | 5.94555 |
August | 348.00000 | 23.97001 | 68.92573 | -0.1250 | 5.75489 |
September | 330.00000 | 23.98644 | 65.20458 | -0.1668 | 6.02729 |
October | 340.00000 | 23.98002 | 48.87606 | 0.54639 | 11.45915 |
November | 330.00000 | 23.89063 | 41.92801 | 0.41194 | 8.70439 |
December | 338.00000 | 23.30116 | 40.14612 | 0.18041 | 6.62338 |
Annual Sum or Average | 4030.00000 | 23.77534 | 51.02756 | 0.12634 | 7.47054 |
Minimum of Months | 308.00000 | 22.74807 | 40.14612 | -0.2214 | 5.75489 |
Maximum of Months | 348.00000 | 24.01884 | 68.92573 | 0.54639 | 11.45915 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.71411 | 42.00305 | 0.00693 | 6.24614 |
February | 308.00000 | 23.45680 | 42.72499 | 0.23960 | 7.15791 |
March | 348.00000 | 23.87617 | 42.51649 | 0.42418 | 9.11796 |
April | 330.00000 | 23.99638 | 42.09768 | 0.55074 | 11.69943 |
May | 344.00000 | 24.00969 | 51.44721 | -0.1345 | 6.00496 |
June | 336.00000 | 23.99284 | 57.87481 | -0.0823 | 5.71738 |
July | 338.00000 | 24.02816 | 64.94550 | -0.0363 | 5.85743 |
August | 348.00000 | 23.97795 | 67.02454 | -0.0528 | 5.59784 |
September | 330.00000 | 23.99580 | 63.72847 | -0.0992 | 5.76608 |
October | 340.00000 | 23.98815 | 48.47861 | 0.59061 | 12.57968 |
November | 330.00000 | 23.88117 | 41.98442 | 0.42957 | 9.09692 |
December | 338.00000 | 23.24814 | 40.24244 | 0.16505 | 6.69235 |
Annual Sum or Average | 4030.00000 | 23.76556 | 50.50078 | 0.16540 | 7.62300 |
Minimum of Months | 308.00000 | 22.71411 | 40.24244 | -0.1345 | 5.59784 |
Maximum of Months | 348.00000 | 24.02816 | 67.02454 | 0.59061 | 12.57968 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.188033E+10 | 0.522453E+09 | 170.67 | 0.168646E+10 | 0.193872E+09 | 0.00 | 0.35 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 9129.65 | 12-JAN-15:00 | 8564.15 | 12-JAN-15:00 | 1544.73 | 14-JAN-14:00 | 2510.97 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.737410E+10 | 0.202180E+10 | 311.92 | 0.641926E+10 | 0.954833E+09 | 0.00 | 0.57 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 15874.51 | 22-FEB-15:00 | 14554.87 | 22-FEB-15:00 | 4055.43 | 25-FEB-18:05 | 4358.96 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.195740E+11 | 0.541304E+10 | 462.92 | 0.168860E+11 | 0.268802E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 43303.06 | 11-MAR-08:62 | 32629.43 | 11-MAR-08:62 | 10673.63 | 11-MAR-08:62 | 9745.67 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.327014E+11 | 0.952307E+10 | 481.25 | 0.293362E+11 | 0.336512E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 68759.23 | 26-APR-07:02 | 63627.62 | 28-APR-07:02 | 17341.75 | 26-APR-07:02 | 16623.19 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.476491E+11 | 0.138891E+11 | 502.35 | 0.381644E+11 | 0.948464E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 72890.14 | 24-MAY-07:02 | 64126.72 | 06-MAY-07:01 | 31567.84 | 24-MAY-07:02 | 17500.91 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.539898E+11 | 0.151313E+11 | 489.09 | 0.381889E+11 | 0.158010E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 74286.90 | 26-JUN-07:01 | 61171.66 | 07-JUN-07:01 | 36484.59 | 26-JUN-07:03 | 17963.36 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.608267E+11 | 0.156228E+11 | 503.32 | 0.356309E+11 | 0.251958E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 75179.65 | 25-JUL-07:01 | 51758.91 | 07-JUL-07:01 | 38938.89 | 25-JUL-07:03 | 17572.40 | 05-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.600923E+11 | 0.148958E+11 | 503.95 | 0.328887E+11 | 0.272036E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 74770.17 | 10-AUG-07:01 | 47892.38 | 03-AUG-07:01 | 36476.86 | 10-AUG-07:03 | 16854.13 | 08-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.494814E+11 | 0.124578E+11 | 487.06 | 0.292260E+11 | 0.202553E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 74130.58 | 03-SEP-07:01 | 50669.01 | 26-SEP-07:01 | 34762.90 | 03-SEP-07:02 | 16423.33 | 22-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.319304E+11 | 0.860110E+10 | 491.47 | 0.251673E+11 | 0.676310E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 71348.87 | 12-OCT-07:02 | 54802.73 | 05-OCT-07:02 | 27505.28 | 12-OCT-07:02 | 15907.24 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.162246E+11 | 0.440837E+10 | 433.53 | 0.139400E+11 | 0.228461E+10 | 0.00 | 0.73 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 | 21491.56 | 09-NOV-14:10 | 19544.09 | 04-NOV-14:00 | 6229.52 | 09-NOV-08:63 | 5883.00 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.409493E+10 | 0.112909E+10 | 267.58 | 0.356264E+10 | 0.532288E+09 | 0.00 | 0.44 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 | 11803.17 | 28-DEC-15:00 | 10885.92 | 03-DEC-14:00 | 1780.96 | 16-DEC-14:00 | 3213.36 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.385819E+12 | 0.103616E+12 | 5105.10 | 0.271097E+12 | 0.114722E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.188033E+10 | 0.522453E+09 | 170.67 | 0.168646E+10 | 0.193872E+09 | 0.00 | 0.35 | 0.00 | 9129.65 | 8564.15 | 1544.73 | 2510.97 | 0.00 | |||||||
Maximum of Months | 0.608267E+11 | 0.156228E+11 | 503.95 | 0.381889E+11 | 0.272036E+11 | 0.00 | 1.00 | 0.00 | 75179.65 | 64126.72 | 38938.89 | 17963.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.203549E+10 | 0.552739E+09 | 312.36 | 0.177717E+10 | 0.258320E+09 | 0.00 | 0.39 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5207.54 | 12-JAN-15:00 | 4900.58 | 12-JAN-15:00 | 976.34 | 16-JAN-18:20 | 1392.92 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.495009E+10 | 0.132309E+10 | 371.58 | 0.430043E+10 | 0.649657E+09 | 0.00 | 0.59 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 8458.11 | 22-FEB-14:50 | 7769.20 | 22-FEB-15:00 | 2167.13 | 25-FEB-18:05 | 2267.85 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.106585E+11 | 0.288319E+10 | 475.67 | 0.928815E+10 | 0.137032E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 23176.71 | 11-MAR-08:62 | 19433.85 | 11-MAR-08:62 | 3742.86 | 11-MAR-08:62 | 5161.97 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.161775E+11 | 0.465038E+10 | 481.38 | 0.146144E+11 | 0.156314E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 34193.17 | 26-APR-07:02 | 32603.84 | 28-APR-07:02 | 5172.52 | 26-APR-07:02 | 8253.08 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.230292E+11 | 0.666700E+10 | 502.57 | 0.186517E+11 | 0.437748E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 36094.46 | 24-MAY-07:02 | 32737.27 | 06-MAY-07:01 | 11506.16 | 24-MAY-07:02 | 8749.14 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.257782E+11 | 0.719257E+10 | 488.95 | 0.184985E+11 | 0.727964E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 36351.78 | 26-JUN-07:01 | 32017.42 | 07-JUN-07:01 | 13020.77 | 26-JUN-07:03 | 8944.42 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.289891E+11 | 0.741939E+10 | 503.08 | 0.173613E+11 | 0.116278E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36838.11 | 25-JUL-07:01 | 29165.86 | 07-JUL-07:01 | 14537.00 | 25-JUL-07:03 | 8789.37 | 05-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.287257E+11 | 0.708617E+10 | 503.77 | 0.161175E+11 | 0.126082E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36749.07 | 10-AUG-07:01 | 27099.20 | 07-AUG-07:01 | 14153.20 | 10-AUG-07:03 | 8431.45 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.237203E+11 | 0.593507E+10 | 486.94 | 0.144049E+11 | 0.931547E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36496.52 | 03-SEP-07:01 | 28895.79 | 26-SEP-07:01 | 12860.91 | 03-SEP-07:02 | 8159.93 | 22-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.160472E+11 | 0.426091E+10 | 493.66 | 0.128850E+11 | 0.316218E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 35284.53 | 12-OCT-07:02 | 30297.68 | 02-OCT-07:02 | 9059.72 | 12-OCT-07:02 | 7868.93 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.924730E+10 | 0.245618E+10 | 453.11 | 0.801408E+10 | 0.123323E+10 | 0.00 | 0.75 | 09-NOV-08:63 | 0.00 | 01-NOV-00:10 | 11718.89 | 09-NOV-08:63 | 10320.25 | 04-NOV-14:00 | 2294.39 | 09-NOV-08:63 | 2988.99 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.355266E+10 | 0.956571E+09 | 389.33 | 0.305038E+10 | 0.502284E+09 | 0.00 | 0.47 | 03-DEC-14:00 | 0.00 | 01-DEC-01:05 | 6486.60 | 03-DEC-14:00 | 6165.83 | 03-DEC-14:00 | 1297.57 | 10-DEC-18:05 | 1721.48 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.192911E+12 | 0.513833E+11 | 5462.41 | 0.138964E+12 | 0.539477E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.203549E+10 | 0.552739E+09 | 312.36 | 0.177717E+10 | 0.258320E+09 | 0.00 | 0.39 | 0.00 | 5207.54 | 4900.58 | 976.34 | 1392.92 | 0.00 | |||||||
Maximum of Months | 0.289891E+11 | 0.741939E+10 | 503.77 | 0.186517E+11 | 0.126082E+11 | 0.00 | 1.00 | 0.00 | 36838.11 | 32737.27 | 14537.00 | 8944.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.925079E+09 | 0.251833E+09 | 149.17 | 0.843355E+09 | 81724005.22 | 0.00 | 0.35 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4731.86 | 12-JAN-15:00 | 4465.13 | 12-JAN-15:00 | 857.29 | 14-JAN-14:00 | 1276.93 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.322183E+10 | 0.866960E+09 | 230.83 | 0.285620E+10 | 0.365637E+09 | 0.00 | 0.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 8078.83 | 22-FEB-14:00 | 7434.89 | 22-FEB-14:00 | 1820.59 | 25-FEB-16:30 | 2176.99 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.811525E+10 | 0.220709E+10 | 337.83 | 0.711804E+10 | 0.997211E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 28891.07 | 11-MAR-07:03 | 20586.14 | 30-MAR-06:03 | 8603.92 | 11-MAR-07:03 | 6280.09 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.129992E+11 | 0.371748E+10 | 354.56 | 0.117468E+11 | 0.125242E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 35657.06 | 17-APR-06:01 | 32689.28 | 28-APR-06:01 | 9203.75 | 17-APR-06:01 | 8366.61 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.191959E+11 | 0.550556E+10 | 376.85 | 0.154382E+11 | 0.375773E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 38081.89 | 23-MAY-06:01 | 32948.17 | 06-MAY-06:01 | 19128.86 | 23-MAY-06:03 | 8595.55 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.216434E+11 | 0.594100E+10 | 369.03 | 0.152594E+11 | 0.638402E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 38787.26 | 26-JUN-06:01 | 30734.74 | 12-JUN-06:01 | 23345.86 | 26-JUN-06:04 | 8877.06 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.240240E+11 | 0.601670E+10 | 371.30 | 0.138789E+11 | 0.101451E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 38821.17 | 23-JUL-07:01 | 25163.54 | 01-JUL-06:01 | 23554.54 | 24-JUL-06:05 | 8785.37 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.242737E+11 | 0.588095E+10 | 379.21 | 0.131120E+11 | 0.111617E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38905.65 | 21-AUG-06:01 | 22127.64 | 03-AUG-06:01 | 24859.10 | 28-AUG-06:06 | 8418.07 | 08-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.195884E+11 | 0.481732E+10 | 359.35 | 0.114979E+11 | 0.809047E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38915.30 | 10-SEP-07:02 | 24741.49 | 27-SEP-06:02 | 24450.01 | 11-SEP-06:03 | 8166.55 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.127630E+11 | 0.338520E+10 | 361.43 | 0.101903E+11 | 0.257275E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 36707.56 | 12-OCT-06:02 | 28555.44 | 02-OCT-06:01 | 14804.92 | 12-OCT-06:02 | 7931.65 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.689855E+10 | 0.184519E+10 | 310.50 | 0.606943E+10 | 0.829126E+09 | 0.00 | 0.77 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 | 12619.32 | 09-NOV-07:03 | 10255.56 | 04-NOV-14:00 | 4150.00 | 09-NOV-07:03 | 2984.18 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.199132E+10 | 0.538584E+09 | 230.75 | 0.176406E+10 | 0.227260E+09 | 0.00 | 0.44 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5978.25 | 28-DEC-14:00 | 5891.53 | 02-DEC-14:00 | 965.80 | 16-DEC-14:00 | 1603.53 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.155640E+12 | 0.409739E+11 | 3830.82 | 0.109774E+12 | 0.458652E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.925079E+09 | 0.251833E+09 | 149.17 | 0.843355E+09 | 81724005.22 | 0.00 | 0.35 | 0.00 | 4731.86 | 4465.13 | 857.29 | 1276.93 | 0.00 | |||||||
Maximum of Months | 0.242737E+11 | 0.601670E+10 | 379.21 | 0.154382E+11 | 0.111617E+11 | 0.00 | 1.00 | 0.00 | 38915.30 | 32948.17 | 24859.10 | 8877.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.834442E+09 | 0.227556E+09 | 140.33 | 0.760311E+09 | 74131245.11 | 0.00 | 0.34 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4596.01 | 12-JAN-15:00 | 4335.98 | 12-JAN-15:00 | 837.85 | 14-JAN-14:00 | 1243.63 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.313062E+10 | 0.843904E+09 | 229.00 | 0.277571E+10 | 0.354907E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 8001.03 | 22-FEB-14:00 | 7362.37 | 22-FEB-14:00 | 1806.56 | 25-FEB-16:30 | 2159.51 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.809057E+10 | 0.220164E+10 | 337.33 | 0.709591E+10 | 0.994666E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 28946.60 | 11-MAR-07:03 | 20801.59 | 30-MAR-06:03 | 8619.80 | 11-MAR-07:03 | 6291.95 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.130559E+11 | 0.373242E+10 | 354.62 | 0.117988E+11 | 0.125706E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 35750.85 | 17-APR-06:01 | 32778.83 | 28-APR-06:01 | 9093.41 | 17-APR-06:03 | 8382.61 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.193238E+11 | 0.553939E+10 | 376.92 | 0.155509E+11 | 0.377288E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 38156.49 | 23-MAY-06:01 | 33043.17 | 06-MAY-06:01 | 19073.15 | 23-MAY-06:03 | 8612.52 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.217748E+11 | 0.597510E+10 | 369.24 | 0.153691E+11 | 0.640574E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 38857.93 | 26-JUN-06:01 | 31033.80 | 12-JUN-06:01 | 23280.73 | 26-JUN-06:04 | 8896.71 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.241716E+11 | 0.605242E+10 | 371.28 | 0.139926E+11 | 0.101789E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 38891.90 | 23-JUL-07:03 | 25391.07 | 05-JUL-06:01 | 23507.86 | 24-JUL-06:05 | 8801.40 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.243847E+11 | 0.590745E+10 | 379.36 | 0.131948E+11 | 0.111899E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38976.54 | 21-AUG-06:01 | 22251.38 | 03-AUG-06:01 | 24770.26 | 28-AUG-06:06 | 8440.69 | 08-AUG-06:13 | 0.00 | 01-AUG-00:10 |
September | 0.196778E+11 | 0.483849E+10 | 359.53 | 0.115654E+11 | 0.811237E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38986.20 | 10-SEP-07:02 | 24860.59 | 27-SEP-06:02 | 24453.92 | 11-SEP-06:03 | 8181.47 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.128144E+11 | 0.339820E+10 | 361.46 | 0.102343E+11 | 0.258015E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 36776.63 | 12-OCT-06:02 | 29320.25 | 23-OCT-06:02 | 14800.36 | 12-OCT-06:02 | 7946.72 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.685246E+10 | 0.183445E+10 | 309.25 | 0.602819E+10 | 0.824268E+09 | 0.00 | 0.76 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 | 12367.15 | 09-NOV-07:03 | 10238.62 | 04-NOV-14:00 | 4071.95 | 09-NOV-07:03 | 2982.25 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.187687E+10 | 0.508649E+09 | 226.67 | 0.166337E+10 | 0.213496E+09 | 0.00 | 0.43 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5836.62 | 28-DEC-14:00 | 5823.29 | 02-DEC-14:00 | 947.55 | 16-DEC-14:00 | 1569.86 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.155988E+12 | 0.410597E+11 | 3814.99 | 0.110030E+12 | 0.459585E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.834442E+09 | 0.227556E+09 | 140.33 | 0.760311E+09 | 74131245.11 | 0.00 | 0.34 | 0.00 | 4596.01 | 4335.98 | 837.85 | 1243.63 | 0.00 | |||||||
Maximum of Months | 0.243847E+11 | 0.605242E+10 | 379.36 | 0.155509E+11 | 0.111899E+11 | 0.00 | 1.00 | 0.00 | 38986.20 | 33043.17 | 24770.26 | 8896.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.690348E+09 | 0.188854E+09 | 123.50 | 0.627771E+09 | 62576327.05 | 0.00 | 0.33 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4329.10 | 12-JAN-15:00 | 4080.23 | 12-JAN-15:00 | 793.49 | 14-JAN-14:00 | 1176.85 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.292619E+10 | 0.791493E+09 | 223.25 | 0.259516E+10 | 0.331021E+09 | 0.00 | 0.55 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7807.80 | 22-FEB-14:00 | 7178.82 | 22-FEB-14:00 | 1741.83 | 25-FEB-16:30 | 2113.16 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.785011E+10 | 0.214169E+10 | 333.67 | 0.688125E+10 | 0.968861E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 26459.39 | 11-MAR-07:03 | 19014.81 | 30-MAR-06:03 | 8037.79 | 11-MAR-07:03 | 5755.24 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.128632E+11 | 0.368278E+10 | 354.53 | 0.116194E+11 | 0.124387E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 35577.90 | 17-APR-06:01 | 32579.39 | 28-APR-06:01 | 9119.61 | 17-APR-06:01 | 8342.73 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.191429E+11 | 0.549009E+10 | 377.02 | 0.153934E+11 | 0.374947E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 37975.33 | 23-MAY-06:01 | 32848.10 | 06-MAY-06:01 | 19128.96 | 23-MAY-06:03 | 8571.67 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.215831E+11 | 0.592397E+10 | 368.79 | 0.152126E+11 | 0.637049E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 38682.80 | 26-JUN-06:01 | 30853.53 | 12-JUN-06:01 | 23283.06 | 26-JUN-06:04 | 8856.23 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.239832E+11 | 0.600526E+10 | 371.23 | 0.138521E+11 | 0.101312E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 38716.61 | 23-JUL-07:01 | 25215.48 | 05-JUL-06:01 | 23498.22 | 24-JUL-06:05 | 8761.23 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.241645E+11 | 0.585403E+10 | 379.15 | 0.130341E+11 | 0.111304E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38800.87 | 21-AUG-06:01 | 21975.25 | 03-AUG-06:01 | 24760.44 | 28-AUG-06:06 | 8402.72 | 08-AUG-06:13 | 0.00 | 01-AUG-00:10 |
September | 0.194652E+11 | 0.478785E+10 | 359.31 | 0.114071E+11 | 0.805806E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38810.49 | 10-SEP-07:02 | 24596.66 | 27-SEP-06:02 | 24472.03 | 11-SEP-06:03 | 8144.55 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.126090E+11 | 0.334872E+10 | 360.49 | 0.100598E+11 | 0.254916E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 36603.25 | 12-OCT-06:02 | 28533.27 | 02-OCT-06:01 | 14896.02 | 12-OCT-06:02 | 7909.95 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.663681E+10 | 0.178118E+10 | 306.50 | 0.583509E+10 | 0.801720E+09 | 0.00 | 0.73 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 10947.82 | 09-NOV-13:40 | 10081.26 | 04-NOV-14:00 | 3517.02 | 09-NOV-07:03 | 2941.48 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.166279E+10 | 0.452050E+09 | 216.00 | 0.147473E+10 | 0.188063E+09 | 0.00 | 0.42 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5640.32 | 02-DEC-14:00 | 5640.32 | 02-DEC-14:00 | 908.89 | 16-DEC-14:00 | 1508.38 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.153577E+12 | 0.404480E+11 | 3773.43 | 0.107993E+12 | 0.455848E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.690348E+09 | 0.188854E+09 | 123.50 | 0.627771E+09 | 62576327.05 | 0.00 | 0.33 | 0.00 | 4329.10 | 4080.23 | 793.49 | 1176.85 | 0.00 | |||||||
Maximum of Months | 0.241645E+11 | 0.600526E+10 | 379.15 | 0.153934E+11 | 0.111304E+11 | 0.00 | 1.00 | 0.00 | 38810.49 | 32848.10 | 24760.44 | 8856.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.978653E+09 | 0.273210E+09 | 100.50 | 0.870127E+09 | 0.108526E+09 | 0.00 | 0.32 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7656.94 | 12-JAN-15:10 | 7026.80 | 12-JAN-15:10 | 1501.41 | 14-JAN-15:10 | 2121.19 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.485276E+10 | 0.134056E+10 | 216.33 | 0.422595E+10 | 0.626817E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 14423.26 | 22-FEB-14:00 | 12964.89 | 22-FEB-15:10 | 3639.91 | 25-FEB-16:00 | 3960.23 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.140288E+11 | 0.389976E+10 | 330.85 | 0.120900E+11 | 0.193876E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 42975.85 | 11-MAR-08:62 | 30743.17 | 11-MAR-08:62 | 12232.68 | 11-MAR-08:62 | 9632.45 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.233649E+11 | 0.681077E+10 | 344.19 | 0.209738E+11 | 0.239107E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 64378.71 | 17-APR-07:01 | 58557.38 | 28-APR-07:02 | 17711.90 | 17-APR-07:03 | 15393.19 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.350557E+11 | 0.102224E+11 | 367.64 | 0.279515E+11 | 0.710417E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 67558.89 | 21-MAY-08:61 | 59383.91 | 29-MAY-08:61 | 28693.06 | 21-MAY-08:04 | 16205.95 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.395854E+11 | 0.110472E+11 | 359.60 | 0.276558E+11 | 0.119296E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 70144.79 | 25-JUN-08:62 | 56254.44 | 07-JUN-07:01 | 42139.50 | 26-JUN-07:04 | 16592.02 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.436910E+11 | 0.110958E+11 | 359.89 | 0.248466E+11 | 0.188444E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 70130.57 | 23-JUL-08:61 | 48807.37 | 07-JUL-07:01 | 42381.37 | 23-JUL-08:04 | 16271.72 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.442691E+11 | 0.108676E+11 | 370.95 | 0.234135E+11 | 0.208557E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 70351.20 | 21-AUG-07:01 | 43568.23 | 08-AUG-07:01 | 44608.54 | 28-AUG-07:07 | 15571.82 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.353005E+11 | 0.880799E+10 | 348.25 | 0.203470E+11 | 0.149534E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 70383.10 | 04-SEP-08:61 | 46876.30 | 27-SEP-07:02 | 44346.63 | 11-SEP-07:03 | 15190.84 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.228882E+11 | 0.617181E+10 | 349.73 | 0.179815E+11 | 0.490678E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 65925.96 | 12-OCT-07:02 | 51358.51 | 02-OCT-07:02 | 25963.78 | 12-OCT-07:02 | 14661.92 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.116598E+11 | 0.318838E+10 | 308.86 | 0.100496E+11 | 0.161021E+10 | 0.00 | 0.75 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 20387.77 | 09-NOV-13:40 | 18599.29 | 04-NOV-14:10 | 5444.42 | 09-NOV-08:63 | 5563.48 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.244956E+10 | 0.678958E+09 | 179.08 | 0.213594E+10 | 0.313626E+09 | 0.00 | 0.40 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 9991.97 | 28-DEC-14:00 | 9654.48 | 02-DEC-14:20 | 1712.10 | 16-DEC-15:10 | 2749.56 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.278124E+12 | 0.744044E+11 | 3635.88 | 0.192541E+12 | 0.855830E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.978653E+09 | 0.273210E+09 | 100.50 | 0.870127E+09 | 0.108526E+09 | 0.00 | 0.32 | 0.00 | 7656.94 | 7026.80 | 1501.41 | 2121.19 | 0.00 | |||||||
Maximum of Months | 0.442691E+11 | 0.110958E+11 | 370.95 | 0.279515E+11 | 0.208557E+11 | 0.00 | 1.00 | 0.00 | 70383.10 | 59383.91 | 44608.54 | 16592.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.461459E+09 | 0.126777E+09 | 94.83 | 0.411404E+09 | 50055398.20 | 0.00 | 0.31 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3924.52 | 12-JAN-15:10 | 3620.18 | 12-JAN-15:10 | 743.03 | 14-JAN-15:10 | 1070.01 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.247368E+10 | 0.672430E+09 | 213.67 | 0.216457E+10 | 0.309114E+09 | 0.00 | 0.55 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7481.37 | 22-FEB-14:00 | 6767.73 | 22-FEB-15:10 | 1837.12 | 25-FEB-16:00 | 2021.15 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.726224E+10 | 0.198629E+10 | 330.01 | 0.628031E+10 | 0.981934E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 20433.62 | 11-MAR-08:62 | 14612.89 | 11-MAR-08:62 | 5820.73 | 11-MAR-08:62 | 4501.80 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.121391E+11 | 0.348273E+10 | 344.43 | 0.109153E+11 | 0.122375E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 33759.44 | 17-APR-07:01 | 30683.31 | 28-APR-07:02 | 9069.04 | 17-APR-07:03 | 7924.78 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.182379E+11 | 0.523948E+10 | 367.88 | 0.145649E+11 | 0.367299E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35411.48 | 21-MAY-08:61 | 31123.88 | 29-MAY-08:61 | 15077.92 | 21-MAY-08:04 | 8340.48 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.205685E+11 | 0.565766E+10 | 359.15 | 0.143952E+11 | 0.617332E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 36760.75 | 25-JUN-08:62 | 29441.75 | 07-JUN-07:01 | 22168.60 | 26-JUN-07:04 | 8542.98 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.227027E+11 | 0.568036E+10 | 359.72 | 0.129418E+11 | 0.976090E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36753.30 | 23-JUL-08:61 | 25591.43 | 07-JUL-07:01 | 22272.49 | 23-JUL-08:04 | 8378.90 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.229822E+11 | 0.555835E+10 | 371.01 | 0.121839E+11 | 0.107982E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36868.93 | 21-AUG-07:01 | 22877.75 | 08-AUG-07:01 | 23595.29 | 28-AUG-07:06 | 8017.46 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.183333E+11 | 0.450427E+10 | 348.38 | 0.105928E+11 | 0.774051E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36885.65 | 04-SEP-08:03 | 24647.11 | 27-SEP-07:02 | 23397.60 | 11-SEP-07:03 | 7821.51 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.118815E+11 | 0.315319E+10 | 350.14 | 0.936345E+10 | 0.251801E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 34530.16 | 12-OCT-07:02 | 26943.33 | 02-OCT-07:02 | 13461.00 | 12-OCT-07:02 | 7546.63 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.604082E+10 | 0.162494E+10 | 309.11 | 0.522696E+10 | 0.813861E+09 | 0.00 | 0.75 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10641.65 | 06-NOV-14:00 | 9730.96 | 04-NOV-14:20 | 2416.68 | 09-NOV-08:63 | 2854.21 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.121920E+10 | 0.332463E+09 | 173.50 | 0.106907E+10 | 0.150129E+09 | 0.00 | 0.40 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 5130.73 | 28-DEC-14:00 | 5015.20 | 02-DEC-14:20 | 858.08 | 16-DEC-15:10 | 1389.93 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144302E+12 | 0.380189E+11 | 3621.83 | 0.100110E+12 | 0.441928E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.461459E+09 | 0.126777E+09 | 94.83 | 0.411404E+09 | 50055398.20 | 0.00 | 0.31 | 0.00 | 3924.52 | 3620.18 | 743.03 | 1070.01 | 0.00 | |||||||
Maximum of Months | 0.229822E+11 | 0.568036E+10 | 371.01 | 0.145649E+11 | 0.107982E+11 | 0.00 | 1.00 | 0.00 | 36885.65 | 31123.88 | 23595.29 | 8542.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.433056E+09 | 0.119084E+09 | 91.67 | 0.385612E+09 | 47444061.72 | 0.00 | 0.31 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3854.91 | 12-JAN-15:10 | 3554.47 | 12-JAN-15:10 | 727.98 | 14-JAN-15:10 | 1052.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.241526E+10 | 0.657233E+09 | 212.58 | 0.211350E+10 | 0.301753E+09 | 0.00 | 0.55 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7411.04 | 22-FEB-14:00 | 6704.78 | 22-FEB-15:10 | 1813.44 | 25-FEB-16:00 | 2004.24 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.718945E+10 | 0.196767E+10 | 329.51 | 0.621558E+10 | 0.973876E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 19823.06 | 11-MAR-08:62 | 14137.27 | 11-MAR-08:62 | 5685.79 | 11-MAR-08:62 | 4367.98 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.120836E+11 | 0.346748E+10 | 344.29 | 0.108637E+11 | 0.121984E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 33663.43 | 17-APR-07:01 | 30589.69 | 28-APR-07:02 | 8984.16 | 17-APR-07:03 | 7902.38 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.181863E+11 | 0.522443E+10 | 367.91 | 0.145201E+11 | 0.366624E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35310.71 | 21-MAY-08:61 | 31036.20 | 29-MAY-08:61 | 15051.26 | 21-MAY-08:04 | 8316.99 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.205150E+11 | 0.564241E+10 | 359.22 | 0.143511E+11 | 0.616387E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 36657.73 | 25-JUN-08:62 | 29338.83 | 07-JUN-07:01 | 22123.15 | 26-JUN-07:04 | 8519.13 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.226522E+11 | 0.566661E+10 | 359.67 | 0.129035E+11 | 0.974872E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36650.30 | 23-JUL-08:04 | 25493.26 | 07-JUL-07:01 | 22226.58 | 23-JUL-08:04 | 8355.24 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.229274E+11 | 0.554389E+10 | 370.90 | 0.121435E+11 | 0.107840E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36765.60 | 21-AUG-07:01 | 22790.96 | 08-AUG-07:01 | 23533.83 | 28-AUG-07:06 | 7995.01 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.182806E+11 | 0.449077E+10 | 348.46 | 0.105533E+11 | 0.772727E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36782.27 | 04-SEP-08:03 | 24541.82 | 27-SEP-07:02 | 23354.38 | 11-SEP-07:03 | 7799.57 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.118255E+11 | 0.313889E+10 | 350.14 | 0.931586E+10 | 0.250964E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 34435.90 | 12-OCT-07:02 | 26849.82 | 02-OCT-07:02 | 13469.22 | 12-OCT-07:02 | 7525.61 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.597733E+10 | 0.160883E+10 | 307.94 | 0.517061E+10 | 0.806719E+09 | 0.00 | 0.74 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10588.34 | 06-NOV-14:00 | 9682.22 | 04-NOV-14:20 | 2281.98 | 09-NOV-08:63 | 2841.56 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.116967E+10 | 0.319229E+09 | 168.17 | 0.102620E+10 | 0.143478E+09 | 0.00 | 0.40 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 5053.45 | 28-DEC-14:00 | 4954.01 | 02-DEC-14:20 | 843.47 | 16-DEC-15:10 | 1370.65 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.143655E+12 | 0.378465E+11 | 3610.46 | 0.995625E+11 | 0.440928E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.433056E+09 | 0.119084E+09 | 91.67 | 0.385612E+09 | 47444061.72 | 0.00 | 0.31 | 0.00 | 3854.91 | 3554.47 | 727.98 | 1052.26 | 0.00 | |||||||
Maximum of Months | 0.229274E+11 | 0.566661E+10 | 370.90 | 0.145201E+11 | 0.107840E+11 | 0.00 | 1.00 | 0.00 | 36782.27 | 31036.20 | 23533.83 | 8519.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.377594E+09 | 0.104075E+09 | 83.50 | 0.335564E+09 | 42029913.07 | 0.00 | 0.29 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3701.01 | 12-JAN-15:10 | 3411.58 | 12-JAN-15:10 | 692.14 | 14-JAN-15:10 | 1013.66 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.228548E+10 | 0.623757E+09 | 207.08 | 0.200168E+10 | 0.283799E+09 | 0.00 | 0.54 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7290.27 | 22-FEB-15:10 | 6594.15 | 22-FEB-15:10 | 1760.59 | 25-FEB-16:00 | 1977.18 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.705205E+10 | 0.193429E+10 | 326.35 | 0.609685E+10 | 0.955192E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 17687.40 | 11-MAR-08:62 | 12514.18 | 11-MAR-08:62 | 5173.23 | 11-MAR-08:62 | 3900.36 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.120845E+11 | 0.346992E+10 | 344.60 | 0.108663E+11 | 0.121821E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 33791.41 | 17-APR-07:01 | 30698.02 | 28-APR-07:02 | 8929.23 | 17-APR-07:03 | 7932.96 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.182829E+11 | 0.525345E+10 | 367.77 | 0.146090E+11 | 0.367390E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35446.05 | 21-MAY-08:61 | 31168.59 | 29-MAY-08:61 | 15114.92 | 21-MAY-08:04 | 8350.24 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.206339E+11 | 0.567690E+10 | 359.21 | 0.144546E+11 | 0.617935E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 36802.61 | 25-JUN-08:62 | 29529.01 | 07-JUN-07:01 | 22243.46 | 26-JUN-07:04 | 8553.94 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.228032E+11 | 0.570621E+10 | 359.55 | 0.130222E+11 | 0.978095E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36795.15 | 23-JUL-08:61 | 25699.66 | 07-JUL-07:01 | 22324.04 | 23-JUL-08:04 | 8388.24 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.230755E+11 | 0.558128E+10 | 370.92 | 0.122544E+11 | 0.108211E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36910.91 | 21-AUG-07:01 | 23002.05 | 08-AUG-07:01 | 23566.88 | 28-AUG-07:06 | 8026.57 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.183771E+11 | 0.451589E+10 | 348.54 | 0.106289E+11 | 0.774821E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36927.65 | 04-SEP-08:03 | 24675.30 | 27-SEP-07:02 | 23484.80 | 11-SEP-07:03 | 7830.44 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.118392E+11 | 0.314369E+10 | 349.47 | 0.933073E+10 | 0.250849E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 34562.60 | 12-OCT-07:02 | 26982.13 | 02-OCT-07:02 | 13565.29 | 12-OCT-07:02 | 7554.42 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.586965E+10 | 0.158260E+10 | 304.94 | 0.507794E+10 | 0.791713E+09 | 0.00 | 0.74 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10545.31 | 09-NOV-13:50 | 9641.30 | 04-NOV-14:20 | 2065.97 | 08-NOV-18:00 | 2834.04 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.106430E+10 | 0.291148E+09 | 156.75 | 0.935534E+09 | 0.128766E+09 | 0.00 | 0.38 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4905.15 | 28-DEC-14:00 | 4816.67 | 02-DEC-14:20 | 810.01 | 16-DEC-15:10 | 1334.72 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.143745E+12 | 0.378832E+11 | 3578.69 | 0.996138E+11 | 0.441317E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.377594E+09 | 0.104075E+09 | 83.50 | 0.335564E+09 | 42029913.07 | 0.00 | 0.29 | 0.00 | 3701.01 | 3411.58 | 692.14 | 1013.66 | 0.00 | |||||||
Maximum of Months | 0.230755E+11 | 0.570621E+10 | 370.92 | 0.146090E+11 | 0.108211E+11 | 0.00 | 1.00 | 0.00 | 36927.65 | 31168.59 | 23566.88 | 8553.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.419570E+09 | 0.115823E+09 | 84.83 | 0.379433E+09 | 40137872.46 | 0.00 | 0.28 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3914.57 | 12-JAN-15:10 | 3667.78 | 12-JAN-15:10 | 674.97 | 14-JAN-15:10 | 1076.73 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.245686E+10 | 0.672637E+09 | 206.92 | 0.218702E+10 | 0.269841E+09 | 0.00 | 0.53 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7994.16 | 22-FEB-14:00 | 7306.06 | 22-FEB-14:00 | 1718.92 | 25-FEB-16:00 | 2174.75 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.764942E+10 | 0.210741E+10 | 322.31 | 0.670693E+10 | 0.942490E+09 | 0.00 | 0.87 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 14033.75 | 29-MAR-13:00 | 13637.00 | 28-MAR-15:00 | 3934.41 | 11-MAR-08:62 | 4011.17 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.136189E+11 | 0.391438E+10 | 345.12 | 0.123689E+11 | 0.125003E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 37992.71 | 17-APR-07:01 | 34559.31 | 28-APR-07:02 | 9817.71 | 17-APR-07:01 | 8906.74 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.206572E+11 | 0.595863E+10 | 368.84 | 0.167878E+11 | 0.386934E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 40114.89 | 24-MAY-07:02 | 35518.15 | 29-MAY-08:61 | 18883.58 | 24-MAY-07:02 | 9384.80 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.231120E+11 | 0.640396E+10 | 360.60 | 0.166103E+11 | 0.650172E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 41314.83 | 25-JUN-08:62 | 34341.34 | 12-JUN-07:01 | 25638.09 | 26-JUN-07:04 | 9607.99 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.254956E+11 | 0.643534E+10 | 361.60 | 0.150967E+11 | 0.103989E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 41306.46 | 23-JUL-08:04 | 29818.33 | 07-JUL-07:01 | 25509.66 | 23-JUL-08:04 | 9418.11 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.257829E+11 | 0.628936E+10 | 371.64 | 0.142932E+11 | 0.114896E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 41436.41 | 21-AUG-07:01 | 26107.20 | 09-AUG-07:01 | 26069.81 | 28-AUG-07:07 | 9010.79 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.205315E+11 | 0.508361E+10 | 349.44 | 0.123377E+11 | 0.819384E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 41455.20 | 04-SEP-08:03 | 28671.79 | 27-SEP-07:02 | 26165.96 | 11-SEP-07:03 | 8790.41 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.133644E+11 | 0.355099E+10 | 348.90 | 0.107450E+11 | 0.261942E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 38714.35 | 01-OCT-08:62 | 30953.69 | 02-OCT-07:02 | 14755.28 | 12-OCT-07:02 | 8476.73 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.645961E+10 | 0.174580E+10 | 301.97 | 0.567673E+10 | 0.782876E+09 | 0.00 | 0.73 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 11685.51 | 09-NOV-13:30 | 10609.64 | 04-NOV-14:10 | 2101.88 | 08-NOV-18:00 | 3113.84 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.117292E+10 | 0.321374E+09 | 158.33 | 0.104996E+10 | 0.122957E+09 | 0.00 | 0.36 | 02-DEC-14:10 | 0.00 | 01-DEC-00:10 | 5250.31 | 28-DEC-14:00 | 5118.94 | 02-DEC-14:10 | 814.46 | 16-DEC-14:30 | 1434.97 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.160721E+12 | 0.425993E+11 | 3580.51 | 0.114240E+12 | 0.464812E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.419570E+09 | 0.115823E+09 | 84.83 | 0.379433E+09 | 40137872.46 | 0.00 | 0.28 | 0.00 | 3914.57 | 3667.78 | 674.97 | 1076.73 | 0.00 | |||||||
Maximum of Months | 0.257829E+11 | 0.643534E+10 | 371.64 | 0.167878E+11 | 0.114896E+11 | 0.00 | 1.00 | 0.00 | 41455.20 | 35518.15 | 26165.96 | 9607.99 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.71 | 61.85 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.27 | 49.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.94 | 29.58 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.73 | 10.11 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 99.83 | 1.70 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 97.36 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 90.62 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 84.55 | 1.22 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.85 | 4.83 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.27 | 23.72 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.04 | 45.27 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.20 | 61.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.14 | 24.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 84.55 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.04 | 61.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.71 | 61.85 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.27 | 49.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.94 | 29.58 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.73 | 10.11 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 99.83 | 1.70 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 97.36 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 90.62 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 84.55 | 1.22 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.85 | 4.83 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.27 | 23.72 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.04 | 45.27 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.20 | 61.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.14 | 24.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 84.55 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.04 | 61.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.71 | 61.85 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.27 | 49.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.94 | 29.58 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.73 | 10.11 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 99.83 | 1.70 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 97.36 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 90.62 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 84.55 | 1.22 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.85 | 4.83 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.27 | 23.72 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.04 | 45.27 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.20 | 61.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.14 | 24.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 84.55 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.04 | 61.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.71 | 61.85 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.27 | 49.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.94 | 29.58 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.73 | 10.11 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 99.83 | 1.70 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 97.36 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 90.62 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 84.55 | 1.22 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.85 | 4.83 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.27 | 23.72 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.04 | 45.27 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.20 | 61.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.14 | 24.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 84.55 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.04 | 61.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 133.17 | 73.63 | 0.00 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 137.40 | 58.92 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 136.69 | 35.32 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 128.73 | 12.10 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 118.70 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 115.79 | 1.61 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 107.84 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 100.86 | 1.48 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 114.60 | 5.79 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 170.45 | 28.35 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 186.06 | 54.01 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 146.88 | 73.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 133.03 | 28.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 100.86 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 186.06 | 73.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 133.17 | 73.63 | 0.00 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 137.40 | 58.92 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 136.69 | 35.32 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 128.73 | 12.10 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 118.70 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 115.79 | 1.61 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 107.84 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 100.86 | 1.48 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 114.60 | 5.79 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 170.45 | 28.35 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 186.06 | 54.01 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 146.88 | 73.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 133.03 | 28.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 100.86 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 186.06 | 73.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.23 | 65.17 | 6.83 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.20 | 51.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.61 | 30.37 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 108.37 | 10.32 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 101.23 | 1.67 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 99.10 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 92.30 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 85.96 | 1.12 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 96.79 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.63 | 23.69 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.69 | 45.89 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.02 | 64.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.46 | 24.89 | 6.83 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 85.96 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.69 | 65.17 | 6.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.23 | 65.17 | 6.83 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.20 | 51.49 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.61 | 30.37 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 108.37 | 10.32 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 101.23 | 1.67 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 99.10 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 92.30 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 85.96 | 1.12 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 96.79 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.63 | 23.69 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.69 | 45.89 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.02 | 64.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 111.46 | 24.89 | 6.83 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 85.96 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.69 | 65.17 | 6.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 131.45 | 77.55 | 7.33 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 136.16 | 61.27 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 136.32 | 36.25 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 129.50 | 12.34 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 120.35 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 117.84 | 1.60 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 109.82 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 102.55 | 1.35 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 115.73 | 5.49 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 170.90 | 28.32 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 185.69 | 54.74 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 145.50 | 76.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 133.42 | 29.67 | 7.33 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 102.55 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 185.69 | 77.55 | 7.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.80 | 63.45 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.44 | 51.40 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.40 | 31.73 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.43 | 11.79 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.32 | 2.34 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.95 | 1.91 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.96 | 1.87 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.00 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.10 | 26.03 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.75 | 47.00 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.41 | 63.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.88 | 25.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.96 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.75 | 63.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.80 | 63.45 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.44 | 51.40 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.40 | 31.73 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.43 | 11.79 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.32 | 2.34 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.95 | 1.91 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.96 | 1.87 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.00 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.10 | 26.03 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.75 | 47.00 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.41 | 63.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.88 | 25.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.96 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.75 | 63.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 131.40 | 75.08 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 135.70 | 60.81 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 135.33 | 37.63 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 126.54 | 14.02 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 115.17 | 2.83 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 112.37 | 2.26 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 104.00 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 98.51 | 2.24 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.03 | 7.54 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.35 | 30.89 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 184.73 | 55.72 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 145.18 | 75.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 130.87 | 30.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 98.51 | 0.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 184.73 | 75.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.15 | 62.40 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.61 | 50.90 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.43 | 31.66 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.32 | 11.98 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 96.94 | 2.52 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.49 | 2.02 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.27 | 0.65 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.66 | 2.00 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 94.90 | 6.62 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.06 | 26.21 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.80 | 46.84 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.65 | 62.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.79 | 25.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.66 | 0.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.80 | 62.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.15 | 62.40 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.61 | 50.90 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.43 | 31.66 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.32 | 11.98 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 96.94 | 2.52 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.49 | 2.02 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.27 | 0.65 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.66 | 2.00 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 94.90 | 6.62 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.06 | 26.21 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.80 | 46.84 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.65 | 62.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.79 | 25.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.66 | 0.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.80 | 62.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 131.82 | 73.84 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 135.91 | 60.22 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 135.37 | 37.55 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 126.41 | 14.24 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 114.72 | 3.05 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 111.82 | 2.39 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 103.39 | 0.79 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 98.16 | 2.39 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 112.91 | 7.87 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.30 | 31.11 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 184.80 | 55.52 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 145.46 | 74.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 130.76 | 30.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 98.16 | 0.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 184.80 | 74.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.61 | 61.32 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.91 | 50.21 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.60 | 31.22 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.50 | 11.69 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.19 | 2.40 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.81 | 1.95 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.54 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.90 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.02 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.15 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.96 | 46.42 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.00 | 62.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.04 | 25.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.90 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.96 | 62.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.61 | 61.32 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.91 | 50.21 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.60 | 31.22 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.50 | 11.69 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.19 | 2.40 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.81 | 1.95 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.54 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.90 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.02 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.15 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.96 | 46.42 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.00 | 62.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.04 | 25.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.90 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.96 | 62.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 132.38 | 72.56 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.27 | 59.41 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 135.58 | 37.03 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 126.63 | 13.90 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 115.02 | 2.90 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 112.20 | 2.31 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 103.70 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 98.43 | 2.23 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.06 | 7.54 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.41 | 30.74 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 184.99 | 55.03 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 145.88 | 73.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 131.05 | 29.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 98.43 | 0.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 184.99 | 73.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.73 | 58.99 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.71 | 48.57 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.05 | 29.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.86 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.57 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 95.44 | 1.76 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.20 | 1.49 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.11 | 5.55 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.18 | 24.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.30 | 45.33 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.86 | 60.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.50 | 24.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.20 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.30 | 60.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.73 | 58.99 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.71 | 48.57 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.05 | 29.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.86 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.57 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 95.44 | 1.76 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.20 | 1.49 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.11 | 5.55 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.18 | 24.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.30 | 45.33 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.86 | 60.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.50 | 24.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.20 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.30 | 60.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.73 | 58.99 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.71 | 48.57 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.05 | 29.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.86 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.57 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 95.44 | 1.76 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.20 | 1.49 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.11 | 5.55 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.18 | 24.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.30 | 45.33 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.86 | 60.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.50 | 24.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.20 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.30 | 60.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.73 | 58.99 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.71 | 48.57 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.05 | 29.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 106.86 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 97.57 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 95.44 | 1.76 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 87.79 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.20 | 1.49 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.11 | 5.55 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.18 | 24.90 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.30 | 45.33 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.86 | 60.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.50 | 24.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.20 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.30 | 60.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.68 | 69.83 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.19 | 57.48 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.09 | 35.51 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 127.06 | 12.88 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 115.50 | 2.50 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 112.99 | 2.08 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 104.03 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 98.81 | 1.78 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.16 | 6.59 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.45 | 29.55 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.37 | 53.75 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.87 | 71.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 131.61 | 28.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 98.81 | 0.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.37 | 71.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.68 | 69.83 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.19 | 57.48 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.09 | 35.51 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 127.06 | 12.88 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 115.50 | 2.50 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 112.99 | 2.08 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 104.03 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 98.81 | 1.78 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.16 | 6.59 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.45 | 29.55 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.37 | 53.75 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.87 | 71.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 131.61 | 28.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 98.81 | 0.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.37 | 71.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.65 | 58.81 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.59 | 48.42 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.07 | 29.65 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.28 | 10.54 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.51 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.50 | 1.66 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.78 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.93 | 1.32 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.49 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.31 | 24.51 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.24 | 45.08 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.76 | 60.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.86 | 23.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.93 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.24 | 60.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.65 | 58.81 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.59 | 48.42 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.07 | 29.65 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.28 | 10.54 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.51 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.50 | 1.66 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.78 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.93 | 1.32 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.49 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.31 | 24.51 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.24 | 45.08 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.76 | 60.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.86 | 23.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.93 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.24 | 60.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.62 | 69.60 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.08 | 57.29 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.15 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 127.56 | 12.52 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 116.58 | 2.30 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 114.21 | 1.96 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 105.17 | 0.46 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 99.65 | 1.58 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.63 | 6.15 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.63 | 29.08 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.34 | 53.44 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.79 | 71.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 132.04 | 28.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 99.65 | 0.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.34 | 71.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.82 | 58.47 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.72 | 48.17 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.15 | 29.51 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.35 | 10.46 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.59 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.60 | 1.64 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.86 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.99 | 1.30 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.54 | 5.13 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.35 | 24.43 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.31 | 44.95 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.91 | 59.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.96 | 23.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.99 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.31 | 59.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.82 | 58.47 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.72 | 48.17 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.15 | 29.51 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.35 | 10.46 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.59 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.60 | 1.64 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.86 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.99 | 1.30 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.54 | 5.13 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.35 | 24.43 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.31 | 44.95 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.91 | 59.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.96 | 23.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.99 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.31 | 59.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.82 | 69.19 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.24 | 56.99 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.25 | 35.01 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 127.65 | 12.44 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 116.68 | 2.27 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 114.33 | 1.94 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 105.27 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 99.74 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.69 | 6.09 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.68 | 28.99 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.42 | 53.29 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.97 | 70.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 132.15 | 28.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 99.74 | 0.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.42 | 70.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.20 | 57.56 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.06 | 47.43 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.31 | 29.14 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.29 | 10.42 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.32 | 1.93 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.24 | 1.67 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.41 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.65 | 1.37 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.37 | 5.27 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.30 | 24.46 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.44 | 44.66 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.28 | 59.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.93 | 23.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.65 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.44 | 59.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.20 | 57.56 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.06 | 47.43 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.31 | 29.14 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 107.29 | 10.42 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 98.32 | 1.93 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 96.24 | 1.67 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.41 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 83.65 | 1.37 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 95.37 | 5.27 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 142.30 | 24.46 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.44 | 44.66 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.28 | 59.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 110.93 | 23.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 83.65 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.44 | 59.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.28 | 68.12 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.65 | 56.13 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.44 | 34.57 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 127.57 | 12.38 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 116.35 | 2.33 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 113.90 | 1.98 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 104.74 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 99.33 | 1.64 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 113.49 | 6.27 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 169.61 | 29.03 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.58 | 52.94 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 147.42 | 70.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 132.12 | 27.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 99.33 | 0.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.58 | 70.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.72 | 54.73 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.51 | 44.84 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.20 | 27.71 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 105.89 | 10.34 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.63 | 2.24 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 93.02 | 1.87 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.89 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.82 | 1.93 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.64 | 6.41 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 141.29 | 24.97 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.32 | 43.62 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.81 | 56.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.66 | 22.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.82 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.32 | 56.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.72 | 54.73 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.51 | 44.84 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 114.20 | 27.71 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 105.89 | 10.34 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.63 | 2.24 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 93.02 | 1.87 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.89 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.82 | 1.93 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.64 | 6.41 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 141.29 | 24.97 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 155.32 | 43.62 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.81 | 56.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.66 | 22.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.82 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 155.32 | 56.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.91 | 64.78 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 138.19 | 53.07 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 136.30 | 32.89 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 125.88 | 12.30 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 113.14 | 2.71 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 110.05 | 2.22 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 100.56 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 95.95 | 2.31 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 111.40 | 7.62 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 168.39 | 29.64 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 185.43 | 51.72 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 148.05 | 67.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 130.60 | 27.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 95.95 | 0.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 185.43 | 67.10 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296518E+09 | 0.165658E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276441E+09 | 0.119728E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305169E+09 | 79233655.42 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.279245E+09 | 26207967.73 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.267373E+09 | 4557344.76 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.252361E+09 | 3480950.45 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.242715E+09 | 1043017.44 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.226470E+09 | 3280180.78 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.248454E+09 | 12521900.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381060E+09 | 63523859.05 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401856E+09 | 0.117344E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327298E+09 | 0.165522E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.350496E+10 | 0.762101E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.226470E+09 | 1043017.44 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401856E+09 | 0.165658E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296518E+09 | 0.165658E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276441E+09 | 0.119728E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305169E+09 | 79233655.42 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.279245E+09 | 26207967.73 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.267373E+09 | 4557344.76 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.252361E+09 | 3480950.45 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.242715E+09 | 1043017.44 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.226470E+09 | 3280180.78 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.248454E+09 | 12521900.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381060E+09 | 63523859.05 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401856E+09 | 0.117344E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327298E+09 | 0.165522E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.350496E+10 | 0.762101E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.226470E+09 | 1043017.44 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401856E+09 | 0.165658E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296518E+09 | 0.165658E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276441E+09 | 0.119728E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305169E+09 | 79233655.42 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.279245E+09 | 26207967.73 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.267373E+09 | 4557344.76 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.252361E+09 | 3480950.45 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.242715E+09 | 1043017.44 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.226470E+09 | 3280180.78 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.248454E+09 | 12521900.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381060E+09 | 63523859.05 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401856E+09 | 0.117344E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327298E+09 | 0.165522E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.350496E+10 | 0.762101E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.226470E+09 | 1043017.44 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401856E+09 | 0.165658E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296518E+09 | 0.165658E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276441E+09 | 0.119728E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305169E+09 | 79233655.42 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.279245E+09 | 26207967.73 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.267373E+09 | 4557344.76 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.252361E+09 | 3480950.45 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.242715E+09 | 1043017.44 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.226470E+09 | 3280180.78 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.248454E+09 | 12521900.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381060E+09 | 63523859.05 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401856E+09 | 0.117344E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327298E+09 | 0.165522E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.350496E+10 | 0.762101E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.226470E+09 | 1043017.44 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401856E+09 | 0.165658E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.356687E+09 | 0.197200E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.332388E+09 | 0.142529E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.366103E+09 | 94609092.22 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.333673E+09 | 31364154.05 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.317937E+09 | 5539433.18 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.300127E+09 | 4162627.33 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.288846E+09 | 1275297.28 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.270156E+09 | 3962854.43 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.297030E+09 | 15001625.66 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.456526E+09 | 75931014.90 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.482263E+09 | 0.140000E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.393392E+09 | 0.197153E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.419513E+10 | 0.908728E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.270156E+09 | 1275297.28 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.482263E+09 | 0.197200E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.356687E+09 | 0.197200E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.332388E+09 | 0.142529E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.366103E+09 | 94609092.22 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.333673E+09 | 31364154.05 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.317937E+09 | 5539433.18 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.300127E+09 | 4162627.33 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.288846E+09 | 1275297.28 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.270156E+09 | 3962854.43 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.297030E+09 | 15001625.66 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.456526E+09 | 75931014.90 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.482263E+09 | 0.140000E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.393392E+09 | 0.197153E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.419513E+10 | 0.908728E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.270156E+09 | 1275297.28 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.482263E+09 | 0.197200E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.292573E+09 | 0.174561E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.273856E+09 | 0.124566E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.304297E+09 | 81340662.04 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.280904E+09 | 26738607.32 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.271132E+09 | 4483237.66 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.256856E+09 | 3473680.22 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.247206E+09 | 962262.31 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.230244E+09 | 2993887.76 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.250873E+09 | 11878046.62 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.382008E+09 | 63461989.85 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.400967E+09 | 0.118950E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.324141E+09 | 0.171665E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.351506E+10 | 0.785075E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.230244E+09 | 962262.31 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.400967E+09 | 0.174561E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.292573E+09 | 0.174561E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.273856E+09 | 0.124566E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.304297E+09 | 81340662.04 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.280904E+09 | 26738607.32 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.271132E+09 | 4483237.66 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.256856E+09 | 3473680.22 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.247206E+09 | 962262.31 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.230244E+09 | 2993887.76 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.250873E+09 | 11878046.62 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.382008E+09 | 63461989.85 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.400967E+09 | 0.118950E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.324141E+09 | 0.171665E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.351506E+10 | 0.785075E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.230244E+09 | 962262.31 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.400967E+09 | 0.174561E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.352073E+09 | 0.207709E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.329396E+09 | 0.148223E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.365130E+09 | 97098724.33 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.335666E+09 | 31996567.34 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.322344E+09 | 5455167.10 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.305434E+09 | 4152698.63 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.294151E+09 | 1178245.20 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.274669E+09 | 3618350.81 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.299966E+09 | 14234908.38 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.457729E+09 | 75842585.62 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.481298E+09 | 0.141892E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.389719E+09 | 0.204401E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.420757E+10 | 0.935801E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.274669E+09 | 1178245.20 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.481298E+09 | 0.207709E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.294078E+09 | 0.169940E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274422E+09 | 0.124352E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303727E+09 | 84996278.80 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.275875E+09 | 30569956.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.260653E+09 | 6272819.42 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.246100E+09 | 4944069.72 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235139E+09 | 1583465.43 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222196E+09 | 5007755.12 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246229E+09 | 16432781.63 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380591E+09 | 69708197.02 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401100E+09 | 0.121831E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325195E+09 | 0.169757E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.346530E+10 | 0.805396E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222196E+09 | 1583465.43 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401100E+09 | 0.169940E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.294078E+09 | 0.169940E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274422E+09 | 0.124352E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303727E+09 | 84996278.80 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.275875E+09 | 30569956.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.260653E+09 | 6272819.42 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.246100E+09 | 4944069.72 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235139E+09 | 1583465.43 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222196E+09 | 5007755.12 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246229E+09 | 16432781.63 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380591E+09 | 69708197.02 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401100E+09 | 0.121831E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325195E+09 | 0.169757E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.346530E+10 | 0.805396E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222196E+09 | 1583465.43 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401100E+09 | 0.169940E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.351951E+09 | 0.201099E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.328279E+09 | 0.147116E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.362477E+09 | 0.100801E+09 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.328003E+09 | 36330926.59 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.308460E+09 | 7584295.18 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.291253E+09 | 5862378.58 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.278561E+09 | 1935655.80 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.263838E+09 | 5989200.41 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.292978E+09 | 19538247.74 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.453583E+09 | 82731503.37 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.478826E+09 | 0.144426E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.388850E+09 | 0.200985E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.412706E+10 | 0.954399E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.263838E+09 | 1935655.80 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.478826E+09 | 0.201099E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.295019E+09 | 0.167131E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274848E+09 | 0.123137E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303805E+09 | 84796522.39 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.275586E+09 | 31055961.33 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.259637E+09 | 6745757.51 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.244911E+09 | 5233946.74 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.233753E+09 | 1739513.84 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.221406E+09 | 5345649.54 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.245969E+09 | 17149443.71 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380482E+09 | 70207470.23 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401245E+09 | 0.121403E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325833E+09 | 0.168028E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.346249E+10 | 0.801973E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.221406E+09 | 1739513.84 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401245E+09 | 0.168028E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.295019E+09 | 0.167131E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274848E+09 | 0.123137E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303805E+09 | 84796522.39 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.275586E+09 | 31055961.33 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.259637E+09 | 6745757.51 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.244911E+09 | 5233946.74 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.233753E+09 | 1739513.84 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.221406E+09 | 5345649.54 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.245969E+09 | 17149443.71 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380482E+09 | 70207470.23 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401245E+09 | 0.121403E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325833E+09 | 0.168028E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.346249E+10 | 0.801973E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.221406E+09 | 1739513.84 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401245E+09 | 0.168028E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.353076E+09 | 0.197773E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.328789E+09 | 0.145681E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.362571E+09 | 0.100565E+09 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.327659E+09 | 36907713.20 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.307269E+09 | 8157673.66 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.289845E+09 | 6207795.90 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.276928E+09 | 2125324.57 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.262907E+09 | 6394273.72 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.292667E+09 | 20387699.93 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.453452E+09 | 83323816.98 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.479000E+09 | 0.143919E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.389613E+09 | 0.198939E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.412377E+10 | 0.950381E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.262907E+09 | 2125324.57 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.479000E+09 | 0.198939E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296260E+09 | 0.164229E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275571E+09 | 0.121475E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.304273E+09 | 83611163.37 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276050E+09 | 30312741.53 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.260324E+09 | 6417442.86 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.245746E+09 | 5041846.94 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.234467E+09 | 1580519.71 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222031E+09 | 4990657.77 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246282E+09 | 16424600.15 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380735E+09 | 69359210.88 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401660E+09 | 0.120318E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326769E+09 | 0.166064E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.347017E+10 | 0.789823E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222031E+09 | 1580519.71 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401660E+09 | 0.166064E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296260E+09 | 0.164229E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275571E+09 | 0.121475E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.304273E+09 | 83611163.37 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276050E+09 | 30312741.53 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.260324E+09 | 6417442.86 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.245746E+09 | 5041846.94 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.234467E+09 | 1580519.71 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222031E+09 | 4990657.77 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246282E+09 | 16424600.15 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380735E+09 | 69359210.88 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.401660E+09 | 0.120318E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326769E+09 | 0.166064E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.347017E+10 | 0.789823E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222031E+09 | 1580519.71 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.401660E+09 | 0.166064E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.354558E+09 | 0.194345E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.329653E+09 | 0.143724E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.363134E+09 | 99169671.10 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.328214E+09 | 36031150.43 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.308072E+09 | 7762045.97 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.290829E+09 | 5980229.85 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.277763E+09 | 1932932.66 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.263640E+09 | 5972503.66 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.293042E+09 | 19535455.88 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.453757E+09 | 82322407.67 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.479499E+09 | 0.142639E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.390731E+09 | 0.196622E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.413289E+10 | 0.936036E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.263640E+09 | 1932932.66 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.479499E+09 | 0.196622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299270E+09 | 0.158007E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277517E+09 | 0.117507E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305467E+09 | 80177485.54 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276975E+09 | 28087076.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.261332E+09 | 5541674.99 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.247382E+09 | 4552911.68 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235148E+09 | 1178483.51 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222851E+09 | 3983116.99 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246513E+09 | 14382342.96 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380828E+09 | 66680013.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402534E+09 | 0.117507E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329063E+09 | 0.161546E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.348488E+10 | 0.759151E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222851E+09 | 1178483.51 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402534E+09 | 0.161546E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299270E+09 | 0.158007E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277517E+09 | 0.117507E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305467E+09 | 80177485.54 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276975E+09 | 28087076.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.261332E+09 | 5541674.99 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.247382E+09 | 4552911.68 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235148E+09 | 1178483.51 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222851E+09 | 3983116.99 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246513E+09 | 14382342.96 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380828E+09 | 66680013.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402534E+09 | 0.117507E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329063E+09 | 0.161546E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.348488E+10 | 0.759151E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222851E+09 | 1178483.51 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402534E+09 | 0.161546E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299270E+09 | 0.158007E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277517E+09 | 0.117507E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305467E+09 | 80177485.54 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276975E+09 | 28087076.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.261332E+09 | 5541674.99 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.247382E+09 | 4552911.68 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235148E+09 | 1178483.51 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222851E+09 | 3983116.99 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246513E+09 | 14382342.96 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380828E+09 | 66680013.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402534E+09 | 0.117507E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329063E+09 | 0.161546E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.348488E+10 | 0.759151E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222851E+09 | 1178483.51 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402534E+09 | 0.161546E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299270E+09 | 0.158007E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277517E+09 | 0.117507E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305467E+09 | 80177485.54 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.276975E+09 | 28087076.24 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.261332E+09 | 5541674.99 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.247382E+09 | 4552911.68 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.235148E+09 | 1178483.51 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.222851E+09 | 3983116.99 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.246513E+09 | 14382342.96 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.380828E+09 | 66680013.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402534E+09 | 0.117507E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329063E+09 | 0.161546E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.348488E+10 | 0.759151E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.222851E+09 | 1178483.51 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402534E+09 | 0.161546E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358053E+09 | 0.187021E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.331881E+09 | 0.139064E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.364508E+09 | 95116189.86 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.329337E+09 | 33374373.02 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.309362E+09 | 6691459.15 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.292866E+09 | 5386279.71 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.278645E+09 | 1438264.27 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.264643E+09 | 4759821.35 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.293317E+09 | 17088241.03 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.453844E+09 | 79138299.60 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.480474E+09 | 0.139313E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.393374E+09 | 0.191291E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.415030E+10 | 0.899683E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.264643E+09 | 1438264.27 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.480474E+09 | 0.191291E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358053E+09 | 0.187021E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.331881E+09 | 0.139064E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.364508E+09 | 95116189.86 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.329337E+09 | 33374373.02 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.309362E+09 | 6691459.15 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.292866E+09 | 5386279.71 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.278645E+09 | 1438264.27 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.264643E+09 | 4759821.35 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.293317E+09 | 17088241.03 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.453844E+09 | 79138299.60 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.480474E+09 | 0.139313E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.393374E+09 | 0.191291E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.415030E+10 | 0.899683E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.264643E+09 | 1438264.27 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.480474E+09 | 0.191291E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299034E+09 | 0.157518E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277210E+09 | 0.117144E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305517E+09 | 79423205.57 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278064E+09 | 27311708.72 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.263849E+09 | 5094592.58 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.250131E+09 | 4302356.62 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.237788E+09 | 997607.05 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224786E+09 | 3537630.73 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247512E+09 | 13420390.52 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381171E+09 | 65634912.26 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402371E+09 | 0.116856E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328797E+09 | 0.161213E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349623E+10 | 0.752453E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224786E+09 | 997607.05 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402371E+09 | 0.161213E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299034E+09 | 0.157518E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277210E+09 | 0.117144E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305517E+09 | 79423205.57 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278064E+09 | 27311708.72 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.263849E+09 | 5094592.58 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.250131E+09 | 4302356.62 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.237788E+09 | 997607.05 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224786E+09 | 3537630.73 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247512E+09 | 13420390.52 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381171E+09 | 65634912.26 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402371E+09 | 0.116856E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328797E+09 | 0.161213E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349623E+10 | 0.752453E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224786E+09 | 997607.05 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402371E+09 | 0.161213E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.357894E+09 | 0.186404E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.331634E+09 | 0.138602E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.364655E+09 | 94219393.42 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.330636E+09 | 32461886.79 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.312240E+09 | 6161624.20 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.296037E+09 | 5087347.69 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.281691E+09 | 1220421.42 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.266916E+09 | 4232763.64 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.294529E+09 | 15952632.05 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.454325E+09 | 77895449.47 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.480391E+09 | 0.138526E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.393172E+09 | 0.190861E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.416412E+10 | 0.891624E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.266916E+09 | 1220421.42 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.480391E+09 | 0.190861E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299486E+09 | 0.156594E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277535E+09 | 0.116532E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305742E+09 | 79034739.67 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278250E+09 | 27124888.32 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.264073E+09 | 5032205.91 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.250379E+09 | 4260366.03 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.238004E+09 | 976848.10 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224972E+09 | 3482152.37 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247641E+09 | 13287034.22 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381284E+09 | 65421718.89 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402556E+09 | 0.116514E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329199E+09 | 0.160502E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349912E+10 | 0.748762E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224972E+09 | 976848.10 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402556E+09 | 0.160502E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299486E+09 | 0.156594E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277535E+09 | 0.116532E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305742E+09 | 79034739.67 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278250E+09 | 27124888.32 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.264073E+09 | 5032205.91 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.250379E+09 | 4260366.03 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.238004E+09 | 976848.10 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224972E+09 | 3482152.37 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247641E+09 | 13287034.22 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381284E+09 | 65421718.89 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402556E+09 | 0.116514E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329199E+09 | 0.160502E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349912E+10 | 0.748762E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224972E+09 | 976848.10 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402556E+09 | 0.160502E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358436E+09 | 0.185313E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.332023E+09 | 0.137879E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.364925E+09 | 93759395.90 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.330859E+09 | 32239754.68 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.312504E+09 | 6085768.56 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.296331E+09 | 5037490.30 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.281947E+09 | 1194793.39 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.267138E+09 | 4166617.56 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.294684E+09 | 15793977.92 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.454462E+09 | 77641924.40 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.480613E+09 | 0.138120E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.393652E+09 | 0.190020E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.416757E+10 | 0.887253E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.267138E+09 | 1194793.39 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.480613E+09 | 0.190020E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300515E+09 | 0.154172E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.278349E+09 | 0.114750E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.306166E+09 | 78039777.09 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278084E+09 | 26997270.15 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.263338E+09 | 5158499.83 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.249453E+09 | 4334375.01 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.236809E+09 | 1029397.50 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224059E+09 | 3660241.39 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247205E+09 | 13660367.53 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381144E+09 | 65500770.17 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402904E+09 | 0.115747E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.330204E+09 | 0.158493E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349823E+10 | 0.741542E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224059E+09 | 1029397.50 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402904E+09 | 0.158493E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300515E+09 | 0.154172E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.278349E+09 | 0.114750E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.306166E+09 | 78039777.09 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.278084E+09 | 26997270.15 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.263338E+09 | 5158499.83 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.249453E+09 | 4334375.01 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.236809E+09 | 1029397.50 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.224059E+09 | 3660241.39 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.247205E+09 | 13660367.53 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.381144E+09 | 65500770.17 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402904E+09 | 0.115747E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.330204E+09 | 0.158493E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.349823E+10 | 0.741542E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.224059E+09 | 1029397.50 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402904E+09 | 0.158493E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.359665E+09 | 0.182458E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.332995E+09 | 0.135785E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.365430E+09 | 92591954.52 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.330658E+09 | 32094815.93 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.311630E+09 | 6244772.75 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.295221E+09 | 5127190.07 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.280524E+09 | 1261114.84 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.266048E+09 | 4383742.09 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.294160E+09 | 16245503.85 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.454292E+09 | 77744831.81 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.481028E+09 | 0.137218E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.394849E+09 | 0.187651E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.416650E+10 | 0.878806E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.266048E+09 | 1261114.84 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.481028E+09 | 0.187651E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.301898E+09 | 0.146589E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.279454E+09 | 0.108469E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305868E+09 | 74226783.69 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.274456E+09 | 26809876.16 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256137E+09 | 5994045.10 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.241101E+09 | 4850161.34 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.227379E+09 | 1526944.04 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.216473E+09 | 5171068.20 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242709E+09 | 16612964.05 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.378426E+09 | 66869359.98 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402600E+09 | 0.113062E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.331616E+09 | 0.151787E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.345812E+10 | 0.721969E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.216473E+09 | 1526944.04 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402600E+09 | 0.151787E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.301898E+09 | 0.146589E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.279454E+09 | 0.108469E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.305868E+09 | 74226783.69 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.274456E+09 | 26809876.16 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256137E+09 | 5994045.10 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.241101E+09 | 4850161.34 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.227379E+09 | 1526944.04 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.216473E+09 | 5171068.20 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242709E+09 | 16612964.05 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.378426E+09 | 66869359.98 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.402600E+09 | 0.113062E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.331616E+09 | 0.151787E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.345812E+10 | 0.721969E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.216473E+09 | 1526944.04 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.402600E+09 | 0.151787E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.361335E+09 | 0.173502E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.334311E+09 | 0.128385E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.365057E+09 | 88102842.61 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.326294E+09 | 31876446.62 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.303043E+09 | 7257563.59 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.285256E+09 | 5747919.21 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.269330E+09 | 1873823.15 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.257003E+09 | 6190194.62 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.288762E+09 | 19752225.35 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.451005E+09 | 79375557.03 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.480641E+09 | 0.134049E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.396532E+09 | 0.179729E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.411857E+10 | 0.855842E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.257003E+09 | 1873823.15 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.480641E+09 | 0.179729E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 709.17 | 394.65 | 495.17 | 300.88 | 194.29 | 0.00 | 0.00 |
February | 731.87 | 315.79 | 470.84 | 261.52 | 209.32 | 0.00 | 0.00 |
March | 729.12 | 188.98 | 402.58 | 177.82 | 224.76 | 0.00 | 0.00 |
April | 688.40 | 64.64 | 282.77 | 79.81 | 202.97 | 0.00 | 0.00 |
May | 636.71 | 10.94 | 203.35 | 15.05 | 188.30 | 0.00 | 0.00 |
June | 621.03 | 8.58 | 186.01 | 3.17 | 182.84 | 0.00 | 0.00 |
July | 578.16 | 2.51 | 194.03 | 2.67 | 191.36 | 0.00 | 0.00 |
August | 539.94 | 7.86 | 205.82 | 10.99 | 194.83 | 0.00 | 0.00 |
September | 612.61 | 30.90 | 275.92 | 71.62 | 204.31 | 0.00 | 0.00 |
October | 909.98 | 151.57 | 474.70 | 265.07 | 209.63 | 0.00 | 0.00 |
November | 992.27 | 289.11 | 592.93 | 391.91 | 201.01 | 0.00 | 0.00 |
December | 782.55 | 394.41 | 529.17 | 331.59 | 197.58 | 0.00 | 0.00 |
Annual Sum or Average | 710.62 | 154.30 | 358.80 | 158.75 | 200.05 | 0.00 | 0.00 |
Minimum of Months | 539.94 | 2.51 | 186.01 | 2.67 | 182.84 | 0.00 | 0.00 |
Maximum of Months | 992.27 | 394.65 | 592.93 | 391.91 | 224.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.92 | 207.90 | 247.59 | 150.44 | 97.15 | 0.00 | 0.00 |
February | 362.56 | 164.25 | 235.42 | 130.76 | 104.66 | 0.00 | 0.00 |
March | 363.55 | 96.99 | 201.29 | 88.91 | 112.38 | 0.00 | 0.00 |
April | 346.25 | 32.98 | 141.39 | 39.90 | 101.48 | 0.00 | 0.00 |
May | 322.81 | 5.38 | 101.68 | 7.53 | 94.15 | 0.00 | 0.00 |
June | 316.03 | 4.28 | 93.01 | 1.59 | 91.42 | 0.00 | 0.00 |
July | 294.42 | 1.16 | 97.02 | 1.33 | 95.68 | 0.00 | 0.00 |
August | 274.48 | 3.59 | 102.91 | 5.50 | 97.42 | 0.00 | 0.00 |
September | 309.30 | 14.66 | 137.96 | 35.81 | 102.15 | 0.00 | 0.00 |
October | 456.15 | 75.70 | 237.35 | 132.54 | 104.81 | 0.00 | 0.00 |
November | 495.07 | 146.52 | 296.46 | 195.96 | 100.51 | 0.00 | 0.00 |
December | 387.54 | 204.50 | 264.59 | 165.80 | 98.79 | 0.00 | 0.00 |
Annual Sum or Average | 356.34 | 79.46 | 179.40 | 79.38 | 100.02 | 0.00 | 0.00 |
Minimum of Months | 274.48 | 1.16 | 93.01 | 1.33 | 91.42 | 0.00 | 0.00 |
Maximum of Months | 495.07 | 207.90 | 296.46 | 195.96 | 112.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.00 | 201.98 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 362.57 | 163.62 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 362.13 | 101.10 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 339.41 | 37.60 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 309.80 | 7.51 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 302.26 | 6.08 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 279.58 | 1.90 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 264.42 | 5.98 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 303.02 | 20.22 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 453.54 | 82.94 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 494.22 | 149.73 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 388.01 | 201.80 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 350.64 | 81.34 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 264.42 | 1.90 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 494.22 | 201.98 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.12 | 198.64 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 363.13 | 162.02 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 362.22 | 100.87 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 339.05 | 38.20 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 308.59 | 8.08 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 300.80 | 6.43 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 277.94 | 2.09 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 263.49 | 6.38 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 302.70 | 21.10 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 453.41 | 83.53 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 494.40 | 149.20 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 388.77 | 199.74 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 350.35 | 81.00 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 263.49 | 2.09 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 494.40 | 199.74 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 353.60 | 195.19 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 364.08 | 159.84 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 362.78 | 99.46 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 339.63 | 37.29 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 309.41 | 7.69 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 301.82 | 6.20 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 278.78 | 1.90 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 264.23 | 5.96 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 303.09 | 20.21 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 453.71 | 82.53 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 494.91 | 147.87 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 389.89 | 197.41 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 351.13 | 79.77 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 264.23 | 1.90 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 494.91 | 197.41 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 714.30 | 375.62 | 494.16 | 300.26 | 193.90 | 0.00 | 0.00 |
February | 733.23 | 309.26 | 469.87 | 260.98 | 208.89 | 0.00 | 0.00 |
March | 728.38 | 190.76 | 401.75 | 177.45 | 224.30 | 0.00 | 0.00 |
April | 681.55 | 69.10 | 282.19 | 79.64 | 202.55 | 0.00 | 0.00 |
May | 621.28 | 13.27 | 202.93 | 15.02 | 187.91 | 0.00 | 0.00 |
June | 607.74 | 11.18 | 185.63 | 3.17 | 182.46 | 0.00 | 0.00 |
July | 559.24 | 2.83 | 193.63 | 2.66 | 190.97 | 0.00 | 0.00 |
August | 530.42 | 9.50 | 205.40 | 10.97 | 194.43 | 0.00 | 0.00 |
September | 606.75 | 35.38 | 275.36 | 71.47 | 203.89 | 0.00 | 0.00 |
October | 907.63 | 158.68 | 473.73 | 264.53 | 209.20 | 0.00 | 0.00 |
November | 991.93 | 288.83 | 591.71 | 391.11 | 200.60 | 0.00 | 0.00 |
December | 785.17 | 384.10 | 528.09 | 330.91 | 197.17 | 0.00 | 0.00 |
Annual Sum or Average | 705.23 | 153.35 | 358.06 | 158.43 | 199.64 | 0.00 | 0.00 |
Minimum of Months | 530.42 | 2.83 | 185.63 | 2.66 | 182.46 | 0.00 | 0.00 |
Maximum of Months | 991.93 | 384.10 | 591.71 | 391.11 | 224.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.91 | 187.22 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 366.26 | 154.14 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 364.28 | 94.48 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 342.12 | 33.60 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 313.60 | 6.10 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 307.21 | 5.28 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 282.73 | 1.20 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 267.51 | 4.22 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 304.61 | 16.51 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 454.25 | 78.09 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 495.81 | 143.61 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 392.31 | 191.64 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 353.77 | 75.99 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 267.51 | 1.20 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 495.81 | 191.64 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.45 | 186.12 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 366.69 | 153.33 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 364.55 | 94.02 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 342.35 | 33.37 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 313.86 | 6.03 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 307.52 | 5.23 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 282.99 | 1.18 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 267.73 | 4.16 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 304.77 | 16.35 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 454.39 | 77.84 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 496.04 | 143.19 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 392.79 | 190.79 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 354.07 | 75.62 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 267.73 | 1.18 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 496.04 | 190.79 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.68 | 183.24 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 367.76 | 150.99 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 365.05 | 92.84 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 342.14 | 33.21 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 312.99 | 6.18 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 306.38 | 5.32 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 281.56 | 1.24 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 266.64 | 4.37 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 304.23 | 16.81 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 454.22 | 77.94 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 496.46 | 142.25 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 393.99 | 188.41 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 353.97 | 74.89 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 266.64 | 1.24 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 496.46 | 188.41 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.34 | 174.24 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 369.22 | 142.74 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 364.69 | 88.32 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 337.66 | 32.98 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 304.40 | 7.18 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 296.09 | 5.96 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 270.34 | 1.84 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 257.60 | 6.17 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 298.68 | 20.44 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 450.96 | 79.57 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 496.08 | 138.96 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 395.67 | 180.44 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 349.91 | 72.93 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 257.60 | 1.84 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 496.08 | 180.44 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189945E+10 | 0.105703E+10 | 0.132628E+10 | 0.805880E+09 | 0.520397E+09 | 0.00 | 0.00 |
February | 0.177054E+10 | 0.763970E+09 | 0.113905E+10 | 0.632663E+09 | 0.506391E+09 | 0.00 | 0.00 |
March | 0.195288E+10 | 0.506151E+09 | 0.107827E+10 | 0.476262E+09 | 0.602006E+09 | 0.00 | 0.00 |
April | 0.178433E+10 | 0.167559E+09 | 0.732947E+09 | 0.206860E+09 | 0.526087E+09 | 0.00 | 0.00 |
May | 0.170536E+10 | 29305097.85 | 0.544655E+09 | 40319291.00 | 0.504336E+09 | 0.00 | 0.00 |
June | 0.160970E+10 | 22247994.61 | 0.482148E+09 | 8227718.08 | 0.473920E+09 | 0.00 | 0.00 |
July | 0.154855E+10 | 6721232.90 | 0.519690E+09 | 7147913.40 | 0.512542E+09 | 0.00 | 0.00 |
August | 0.144619E+10 | 21044489.71 | 0.551281E+09 | 29442577.15 | 0.521839E+09 | 0.00 | 0.00 |
September | 0.158787E+10 | 80089418.25 | 0.715197E+09 | 0.185631E+09 | 0.529566E+09 | 0.00 | 0.00 |
October | 0.243729E+10 | 0.405957E+09 | 0.127144E+10 | 0.709965E+09 | 0.561472E+09 | 0.00 | 0.00 |
November | 0.257195E+10 | 0.749376E+09 | 0.153686E+10 | 0.101583E+10 | 0.521029E+09 | 0.00 | 0.00 |
December | 0.209597E+10 | 0.105640E+10 | 0.141733E+10 | 0.888139E+09 | 0.529192E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224101E+11 | 0.486585E+10 | 0.113151E+11 | 0.500637E+10 | 0.630878E+10 | 0.00 | 0.00 |
Minimum of Months | 0.144619E+10 | 6721232.90 | 0.482148E+09 | 7147913.40 | 0.473920E+09 | 0.00 | 0.00 |
Maximum of Months | 0.257195E+10 | 0.105703E+10 | 0.153686E+10 | 0.101583E+10 | 0.602006E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.937219E+09 | 0.556831E+09 | 0.663138E+09 | 0.402940E+09 | 0.260198E+09 | 0.00 | 0.00 |
February | 0.877107E+09 | 0.397353E+09 | 0.569527E+09 | 0.316331E+09 | 0.253196E+09 | 0.00 | 0.00 |
March | 0.973723E+09 | 0.259780E+09 | 0.539134E+09 | 0.238131E+09 | 0.301003E+09 | 0.00 | 0.00 |
April | 0.897472E+09 | 85473453.08 | 0.366474E+09 | 0.103430E+09 | 0.263043E+09 | 0.00 | 0.00 |
May | 0.864606E+09 | 14420099.22 | 0.272328E+09 | 20159645.50 | 0.252168E+09 | 0.00 | 0.00 |
June | 0.819146E+09 | 11099298.67 | 0.241074E+09 | 4113859.04 | 0.236960E+09 | 0.00 | 0.00 |
July | 0.788563E+09 | 3102428.79 | 0.259845E+09 | 3573956.70 | 0.256271E+09 | 0.00 | 0.00 |
August | 0.735155E+09 | 9605008.12 | 0.275641E+09 | 14721288.57 | 0.260919E+09 | 0.00 | 0.00 |
September | 0.801712E+09 | 37990568.78 | 0.357599E+09 | 92815474.26 | 0.264783E+09 | 0.00 | 0.00 |
October | 0.122174E+10 | 0.202766E+09 | 0.635718E+09 | 0.354982E+09 | 0.280736E+09 | 0.00 | 0.00 |
November | 0.128323E+10 | 0.379791E+09 | 0.768431E+09 | 0.507917E+09 | 0.260515E+09 | 0.00 | 0.00 |
December | 0.103800E+10 | 0.547731E+09 | 0.708666E+09 | 0.444070E+09 | 0.264596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112377E+11 | 0.250594E+10 | 0.565757E+10 | 0.250319E+10 | 0.315439E+10 | 0.00 | 0.00 |
Minimum of Months | 0.735155E+09 | 3102428.79 | 0.241074E+09 | 3573956.70 | 0.236960E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128323E+10 | 0.556831E+09 | 0.768431E+09 | 0.507917E+09 | 0.301003E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.940106E+09 | 0.540978E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.877122E+09 | 0.395819E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.969930E+09 | 0.270793E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.879752E+09 | 97470293.60 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.829763E+09 | 20127210.53 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.783452E+09 | 15750086.42 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.748837E+09 | 5101346.51 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.708230E+09 | 16004112.89 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.785436E+09 | 52403622.03 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121476E+10 | 0.222148E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128102E+10 | 0.388088E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.103924E+10 | 0.540500E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110577E+11 | 0.256518E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.708230E+09 | 5101346.51 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128102E+10 | 0.540978E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943115E+09 | 0.532036E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.878484E+09 | 0.391954E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.970181E+09 | 0.270158E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.878831E+09 | 99019016.44 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.826539E+09 | 21646472.29 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.779666E+09 | 16675065.02 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.744433E+09 | 5603244.83 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.705719E+09 | 17085049.80 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.784605E+09 | 54686553.13 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121442E+10 | 0.223738E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128149E+10 | 0.386724E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104128E+10 | 0.534994E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110488E+11 | 0.255432E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.705719E+09 | 5603244.83 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128149E+10 | 0.534994E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.947076E+09 | 0.522801E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.880794E+09 | 0.386673E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.971679E+09 | 0.266391E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.880314E+09 | 96656264.18 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.828719E+09 | 20594960.33 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.782320E+09 | 16063289.99 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.746696E+09 | 5092661.11 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.707701E+09 | 15953184.32 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.785605E+09 | 52384492.19 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121523E+10 | 0.221041E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128282E+10 | 0.383276E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104427E+10 | 0.528749E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110732E+11 | 0.251568E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.707701E+09 | 5092661.11 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128282E+10 | 0.528749E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191318E+10 | 0.100607E+10 | 0.132356E+10 | 0.804226E+09 | 0.519329E+09 | 0.00 | 0.00 |
February | 0.177383E+10 | 0.748158E+09 | 0.113672E+10 | 0.631365E+09 | 0.505352E+09 | 0.00 | 0.00 |
March | 0.195088E+10 | 0.510942E+09 | 0.107606E+10 | 0.475285E+09 | 0.600771E+09 | 0.00 | 0.00 |
April | 0.176657E+10 | 0.179097E+09 | 0.731443E+09 | 0.206436E+09 | 0.525008E+09 | 0.00 | 0.00 |
May | 0.166405E+10 | 35547152.53 | 0.543538E+09 | 40236576.88 | 0.503301E+09 | 0.00 | 0.00 |
June | 0.157526E+10 | 28983082.54 | 0.481159E+09 | 8210839.10 | 0.472948E+09 | 0.00 | 0.00 |
July | 0.149788E+10 | 7589630.12 | 0.518624E+09 | 7133249.62 | 0.511491E+09 | 0.00 | 0.00 |
August | 0.142069E+10 | 25451279.80 | 0.550150E+09 | 29382176.36 | 0.520768E+09 | 0.00 | 0.00 |
September | 0.157269E+10 | 91705228.50 | 0.713730E+09 | 0.185250E+09 | 0.528480E+09 | 0.00 | 0.00 |
October | 0.243100E+10 | 0.424996E+09 | 0.126883E+10 | 0.708508E+09 | 0.560320E+09 | 0.00 | 0.00 |
November | 0.257108E+10 | 0.748656E+09 | 0.153371E+10 | 0.101375E+10 | 0.519960E+09 | 0.00 | 0.00 |
December | 0.210300E+10 | 0.102877E+10 | 0.141442E+10 | 0.886317E+09 | 0.528107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222401E+11 | 0.483596E+10 | 0.112919E+11 | 0.499610E+10 | 0.629583E+10 | 0.00 | 0.00 |
Minimum of Months | 0.142069E+10 | 7589630.12 | 0.481159E+09 | 7133249.62 | 0.472948E+09 | 0.00 | 0.00 |
Maximum of Months | 0.257108E+10 | 0.102877E+10 | 0.153371E+10 | 0.101375E+10 | 0.600771E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.955961E+09 | 0.501438E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.886054E+09 | 0.372890E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.975689E+09 | 0.253066E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.886763E+09 | 87085045.03 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.839935E+09 | 16348024.24 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.796299E+09 | 13691570.85 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.757265E+09 | 3214487.36 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.716486E+09 | 11307618.27 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.789552E+09 | 42793110.68 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121667E+10 | 0.209165E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128513E+10 | 0.372238E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105077E+10 | 0.513286E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111566E+11 | 0.239652E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.716486E+09 | 3214487.36 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128513E+10 | 0.513286E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.957406E+09 | 0.498500E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.887092E+09 | 0.370943E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.976409E+09 | 0.251828E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.887359E+09 | 86489291.31 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.840646E+09 | 16147422.16 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.797088E+09 | 13557750.36 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.757955E+09 | 3147464.94 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.717081E+09 | 11130467.95 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.789966E+09 | 42367808.13 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121703E+10 | 0.208485E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128573E+10 | 0.371148E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105205E+10 | 0.511023E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111658E+11 | 0.238477E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.717081E+09 | 3147464.94 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128573E+10 | 0.511023E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.960694E+09 | 0.490800E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.889691E+09 | 0.365285E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.977761E+09 | 0.248671E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.886826E+09 | 86088971.67 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.838304E+09 | 16560276.72 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.794127E+09 | 13795546.03 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.754142E+09 | 3318997.42 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.714165E+09 | 11703622.49 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.788569E+09 | 43565884.60 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.121658E+10 | 0.208746E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128684E+10 | 0.368712E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105526E+10 | 0.504638E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111630E+11 | 0.236188E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.714165E+09 | 3318997.42 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128684E+10 | 0.504638E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.965130E+09 | 0.466679E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.893217E+09 | 0.345322E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.976792E+09 | 0.236556E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.875205E+09 | 85495882.78 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.815315E+09 | 19243645.34 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.767456E+09 | 15447431.08 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.724087E+09 | 4926276.56 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.689949E+09 | 16531512.87 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.774179E+09 | 52977870.30 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.120786E+10 | 0.213114E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.128584E+10 | 0.360174E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105976E+10 | 0.483303E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110348E+11 | 0.229977E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.689949E+09 | 4926276.56 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128584E+10 | 0.483303E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304104E+09 | -186910200.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117193360.7 | 58.99 | 0.00 | 0.00 |
February | 0.269981E+09 | -166087925.1 | 0.00 | 0.00 | 672.00 | 0.00 | -103893064.6 | 58.99 | 0.00 | 0.00 |
March | 0.287576E+09 | -174461494.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113114923.0 | 58.99 | 0.00 | 0.00 |
April | 0.257776E+09 | -149516992.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108258844.3 | 58.99 | 0.00 | 0.00 |
May | 0.247540E+09 | -136567157.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110972607.6 | 58.99 | 0.00 | 0.00 |
June | 0.226983E+09 | -119855617.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107126902.6 | 58.99 | 0.00 | 0.00 |
July | 0.226195E+09 | -115657524.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110537086.2 | 58.99 | 0.00 | 0.00 |
August | 0.233010E+09 | -122282215.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110728190.5 | 58.99 | 0.00 | 0.00 |
September | 0.236867E+09 | -129350955.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107515989.3 | 58.99 | 0.00 | 0.00 |
October | 0.261983E+09 | -150068301.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111914612.2 | 58.99 | 0.00 | 0.00 |
November | 0.271730E+09 | -162154223.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109575300.3 | 58.99 | 0.00 | 0.00 |
December | 0.297417E+09 | -181754937.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115662264.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312116E+10 | -0.179467E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132649E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226195E+09 | -186910200.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117193360.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.304104E+09 | -115657524.5 | 0.00 | 0.00 | 744.00 | 0.00 | -103893064.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302322E+09 | -186914764.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115407663.4 | 58.99 | 0.00 | 0.00 |
February | 0.269066E+09 | -166085995.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102979851.9 | 58.99 | 0.00 | 0.00 |
March | 0.287156E+09 | -174473213.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112682656.8 | 58.99 | 0.00 | 0.00 |
April | 0.257645E+09 | -149531775.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108113343.0 | 58.99 | 0.00 | 0.00 |
May | 0.247572E+09 | -136552090.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111020281.1 | 58.99 | 0.00 | 0.00 |
June | 0.227061E+09 | -119838361.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107223024.7 | 58.99 | 0.00 | 0.00 |
July | 0.226356E+09 | -115698431.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110657542.6 | 58.99 | 0.00 | 0.00 |
August | 0.233136E+09 | -122279289.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110856599.9 | 58.99 | 0.00 | 0.00 |
September | 0.236937E+09 | -129354676.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107582619.2 | 58.99 | 0.00 | 0.00 |
October | 0.261897E+09 | -150063403.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111834029.8 | 58.99 | 0.00 | 0.00 |
November | 0.271370E+09 | -162144746.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109225666.8 | 58.99 | 0.00 | 0.00 |
December | 0.296153E+09 | -181750873.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114402578.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311667E+10 | -0.179469E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132199E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226356E+09 | -186914764.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115407663.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302322E+09 | -115698431.3 | 0.00 | 0.00 | 744.00 | 0.00 | -102979851.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280813E+09 | -164360865.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116451873.4 | 59.00 | 0.00 | 0.00 |
February | 0.249152E+09 | -146199261.7 | 0.00 | 0.00 | 672.00 | 0.00 | -102952569.2 | 58.99 | 0.00 | 0.00 |
March | 0.267257E+09 | -155691425.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111565801.3 | 58.99 | 0.00 | 0.00 |
April | 0.237469E+09 | -131499402.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105969820.7 | 58.99 | 0.00 | 0.00 |
May | 0.229453E+09 | -121178372.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108274178.9 | 58.99 | 0.00 | 0.00 |
June | 0.211276E+09 | -106761550.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104514110.5 | 58.98 | 0.00 | 0.00 |
July | 0.208969E+09 | -101119665.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107849299.8 | 58.99 | 0.00 | 0.00 |
August | 0.217691E+09 | -109232472.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108458932.5 | 58.99 | 0.00 | 0.00 |
September | 0.219065E+09 | -113714960.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105349732.3 | 59.00 | 0.00 | 0.00 |
October | 0.241938E+09 | -131999400.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109938356.7 | 58.99 | 0.00 | 0.00 |
November | 0.251644E+09 | -143143253.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108500503.3 | 58.99 | 0.00 | 0.00 |
December | 0.273518E+09 | -158634084.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114883745.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288824E+10 | -0.158353E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130471E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.208969E+09 | -164360865.9 | 0.00 | 0.00 | 672.00 | 0.00 | -116451873.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.280813E+09 | -101119665.9 | 0.00 | 0.00 | 744.00 | 0.00 | -102952569.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281267E+09 | -164366741.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116900205.6 | 58.99 | 0.00 | 0.00 |
February | 0.249352E+09 | -146183048.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103168747.7 | 58.99 | 0.00 | 0.00 |
March | 0.267282E+09 | -155703203.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111578982.5 | 58.99 | 0.00 | 0.00 |
April | 0.237373E+09 | -131524430.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105848864.3 | 58.99 | 0.00 | 0.00 |
May | 0.229250E+09 | -121152093.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108097521.8 | 58.99 | 0.00 | 0.00 |
June | 0.211076E+09 | -106686909.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104389395.3 | 59.00 | 0.00 | 0.00 |
July | 0.208766E+09 | -101117359.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107648899.4 | 58.99 | 0.00 | 0.00 |
August | 0.217538E+09 | -109233192.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108304673.1 | 58.99 | 0.00 | 0.00 |
September | 0.218934E+09 | -113722654.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105211240.9 | 58.99 | 0.00 | 0.00 |
October | 0.241859E+09 | -131989397.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109869912.0 | 58.99 | 0.00 | 0.00 |
November | 0.251706E+09 | -143144576.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108561624.1 | 58.99 | 0.00 | 0.00 |
December | 0.273805E+09 | -158644384.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115161067.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288821E+10 | -0.158347E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130474E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.208766E+09 | -164366741.4 | 0.00 | 0.00 | 672.00 | 0.00 | -116900205.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.281267E+09 | -101117359.3 | 0.00 | 0.00 | 744.00 | 0.00 | -103168747.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273884E+09 | -155354266.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118530153.8 | 58.99 | 0.00 | 0.00 |
February | 0.242354E+09 | -138252447.0 | 0.00 | 0.00 | 672.00 | 0.00 | -104101761.9 | 58.99 | 0.00 | 0.00 |
March | 0.259778E+09 | -147320922.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112457190.8 | 58.99 | 0.00 | 0.00 |
April | 0.231083E+09 | -124455545.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106627112.4 | 58.99 | 0.00 | 0.00 |
May | 0.223358E+09 | -114597271.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108760789.5 | 58.99 | 0.00 | 0.00 |
June | 0.206045E+09 | -101000098.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105045005.6 | 58.99 | 0.00 | 0.00 |
July | 0.203746E+09 | -95630243.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108115821.6 | 58.99 | 0.00 | 0.00 |
August | 0.212251E+09 | -103321563.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108929911.6 | 58.99 | 0.00 | 0.00 |
September | 0.213411E+09 | -107641404.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105769326.3 | 58.99 | 0.00 | 0.00 |
October | 0.235242E+09 | -124762902.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110479265.0 | 58.99 | 0.00 | 0.00 |
November | 0.244399E+09 | -135177460.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109221745.3 | 59.00 | 0.00 | 0.00 |
December | 0.266346E+09 | -150037805.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116308487.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281190E+10 | -0.149755E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131435E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203746E+09 | -155354266.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118530153.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.273884E+09 | -95630243.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104101761.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273986E+09 | -155357512.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118628719.2 | 58.99 | 0.00 | 0.00 |
February | 0.242408E+09 | -138249712.5 | 0.00 | 0.00 | 672.00 | 0.00 | -104158450.8 | 58.99 | 0.00 | 0.00 |
March | 0.259850E+09 | -147347179.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112503128.5 | 58.98 | 0.00 | 0.00 |
April | 0.231218E+09 | -124461715.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106756526.0 | 58.99 | 0.00 | 0.00 |
May | 0.223516E+09 | -114575189.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108940612.3 | 58.99 | 0.00 | 0.00 |
June | 0.206222E+09 | -100965577.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105256097.5 | 58.99 | 0.00 | 0.00 |
July | 0.203943E+09 | -95650090.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108293270.0 | 58.99 | 0.00 | 0.00 |
August | 0.212430E+09 | -103336234.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109093362.9 | 58.99 | 0.00 | 0.00 |
September | 0.213561E+09 | -107641236.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105919867.0 | 58.99 | 0.00 | 0.00 |
October | 0.235371E+09 | -124775106.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110595506.9 | 58.99 | 0.00 | 0.00 |
November | 0.244473E+09 | -135175819.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109296692.5 | 59.00 | 0.00 | 0.00 |
December | 0.266397E+09 | -150040014.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116357400.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281338E+10 | -0.149758E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131580E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203943E+09 | -155357512.4 | 0.00 | 0.00 | 672.00 | 0.00 | -118628719.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.273986E+09 | -95650090.7 | 0.00 | 0.00 | 744.00 | 0.00 | -104158450.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274152E+09 | -155359207.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118793260.4 | 58.99 | 0.00 | 0.00 |
February | 0.242512E+09 | -138244398.4 | 0.00 | 0.00 | 672.00 | 0.00 | -104267297.9 | 58.99 | 0.00 | 0.00 |
March | 0.259913E+09 | -147327214.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112585426.6 | 58.99 | 0.00 | 0.00 |
April | 0.231241E+09 | -124434506.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106806497.1 | 58.99 | 0.00 | 0.00 |
May | 0.223561E+09 | -114609730.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108951368.3 | 58.99 | 0.00 | 0.00 |
June | 0.206256E+09 | -100995402.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105260683.8 | 58.99 | 0.00 | 0.00 |
July | 0.203953E+09 | -95630215.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108322570.1 | 58.99 | 0.00 | 0.00 |
August | 0.212462E+09 | -103366104.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109095824.7 | 58.98 | 0.00 | 0.00 |
September | 0.213584E+09 | -107624321.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105960014.6 | 58.99 | 0.00 | 0.00 |
October | 0.235394E+09 | -124746814.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110647419.7 | 58.99 | 0.00 | 0.00 |
November | 0.244524E+09 | -135245458.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109278181.9 | 58.98 | 0.00 | 0.00 |
December | 0.266532E+09 | -150041438.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116490150.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281408E+10 | -0.149762E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131646E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203953E+09 | -155359207.7 | 0.00 | 0.00 | 672.00 | 0.00 | -118793260.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274152E+09 | -95630215.3 | 0.00 | 0.00 | 744.00 | 0.00 | -104267297.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565319E+09 | 71216.77 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74232361.18 | 5710.97 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102583E+09 | 13817.89 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565319E+09 | 71216.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102786E+09 | 10827.57 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2014836.02 | 1119.89 | 02-FEB-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12423561.80 | 2938.37 | 23-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102786E+09 | 10827.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250726E+09 | 26379.63 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18430776.38 | 1684.43 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30686443.35 | 2762.87 | 31-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.250726E+09 | 26379.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311770E+09 | 35894.76 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27428366.33 | 2239.37 | 02-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40057720.65 | 3613.87 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311770E+09 | 35894.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.387742E+09 | 36269.71 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41877703.51 | 2355.81 | 02-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54794611.60 | 3896.80 | 31-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387742E+09 | 36269.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.755055E+09 | 65237.64 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90904267.28 | 7675.53 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125561E+09 | 15471.05 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.755055E+09 | 65237.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.395907E+09 | 34274.27 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44235607.60 | 4170.99 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61702494.38 | 8777.70 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.395907E+09 | 34274.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416895E+09 | 34166.80 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50995979.59 | 4586.75 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68207084.93 | 10272.88 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416895E+09 | 34166.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489759E+09 | 34317.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72793181.20 | 8940.19 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94034160.33 | 15333.91 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489759E+09 | 34317.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.692052E+09 | 39355.31 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155621E+09 | 29862.06 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 680819.05 | 757.44 | 27-NOV-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192688E+09 | 33215.26 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.692052E+09 | 39355.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.188033E+10 | 0.168646E+10 | 9129.65 | 12-JAN-15:00 | 8564.15 | 0.00 |
February | 0.00 | 0.00 | 0.737410E+10 | 0.641926E+10 | 15874.51 | 22-FEB-15:00 | 14554.87 | 0.00 |
March | 0.00 | 0.00 | 0.195740E+11 | 0.168860E+11 | 43303.06 | 11-MAR-08:62 | 32629.43 | 0.00 |
April | 0.00 | 0.00 | 0.327014E+11 | 0.293362E+11 | 68759.23 | 26-APR-07:02 | 51417.49 | 0.00 |
May | 0.00 | 0.00 | 0.476491E+11 | 0.381644E+11 | 72890.14 | 24-MAY-07:02 | 41322.30 | 0.00 |
June | 0.00 | 0.00 | 0.539898E+11 | 0.381889E+11 | 74286.90 | 26-JUN-07:01 | 38299.04 | 0.00 |
July | 0.00 | 0.00 | 0.608267E+11 | 0.356309E+11 | 75179.65 | 25-JUL-07:01 | 36632.16 | 0.00 |
August | 0.00 | 0.00 | 0.600923E+11 | 0.328887E+11 | 74770.17 | 10-AUG-07:01 | 39416.58 | 0.00 |
September | 0.00 | 0.00 | 0.494814E+11 | 0.292260E+11 | 74130.58 | 03-SEP-07:01 | 39899.73 | 0.00 |
October | 0.00 | 0.00 | 0.319304E+11 | 0.251673E+11 | 71348.87 | 12-OCT-07:02 | 43843.59 | 0.00 |
November | 0.00 | 0.00 | 0.162246E+11 | 0.139400E+11 | 21491.56 | 09-NOV-14:10 | 18966.15 | 0.00 |
December | 0.00 | 0.00 | 0.409493E+10 | 0.356264E+10 | 11803.17 | 28-DEC-15:00 | 10575.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.385819E+12 | 0.271097E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.188033E+10 | 0.168646E+10 | 9129.65 | 8564.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.608267E+11 | 0.381889E+11 | 75179.65 | 51417.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203549E+10 | 0.177717E+10 | 5207.54 | 12-JAN-15:00 | 4900.58 | 0.00 |
February | 0.00 | 0.00 | 0.495009E+10 | 0.430043E+10 | 8458.11 | 22-FEB-14:50 | 7763.17 | 0.00 |
March | 0.00 | 0.00 | 0.106585E+11 | 0.928815E+10 | 23176.71 | 11-MAR-08:62 | 19433.85 | 0.00 |
April | 0.00 | 0.00 | 0.161775E+11 | 0.146144E+11 | 34193.17 | 26-APR-07:02 | 29020.65 | 0.00 |
May | 0.00 | 0.00 | 0.230292E+11 | 0.186517E+11 | 36094.46 | 24-MAY-07:02 | 24588.30 | 0.00 |
June | 0.00 | 0.00 | 0.257782E+11 | 0.184985E+11 | 36351.78 | 26-JUN-07:01 | 23905.71 | 0.00 |
July | 0.00 | 0.00 | 0.289891E+11 | 0.173613E+11 | 36838.11 | 25-JUL-07:01 | 22801.17 | 0.00 |
August | 0.00 | 0.00 | 0.287257E+11 | 0.161175E+11 | 36749.07 | 10-AUG-07:01 | 23697.84 | 0.00 |
September | 0.00 | 0.00 | 0.237203E+11 | 0.144049E+11 | 36496.52 | 03-SEP-07:01 | 24153.03 | 0.00 |
October | 0.00 | 0.00 | 0.160472E+11 | 0.128850E+11 | 35284.53 | 12-OCT-07:02 | 26224.82 | 0.00 |
November | 0.00 | 0.00 | 0.924730E+10 | 0.801408E+10 | 11718.89 | 09-NOV-08:63 | 9424.50 | 0.00 |
December | 0.00 | 0.00 | 0.355266E+10 | 0.305038E+10 | 6486.60 | 03-DEC-14:00 | 6165.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192911E+12 | 0.138964E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.203549E+10 | 0.177717E+10 | 5207.54 | 4900.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.289891E+11 | 0.186517E+11 | 36838.11 | 29020.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.925079E+09 | 0.843355E+09 | 4731.86 | 12-JAN-15:00 | 4465.13 | 0.00 |
February | 0.00 | 0.00 | 0.322183E+10 | 0.285620E+10 | 8078.83 | 22-FEB-14:00 | 7434.89 | 0.00 |
March | 0.00 | 0.00 | 0.811525E+10 | 0.711804E+10 | 28891.07 | 11-MAR-07:03 | 20287.14 | 0.00 |
April | 0.00 | 0.00 | 0.129992E+11 | 0.117468E+11 | 35657.06 | 17-APR-06:01 | 26453.30 | 0.00 |
May | 0.00 | 0.00 | 0.191959E+11 | 0.154382E+11 | 38081.89 | 23-MAY-06:01 | 19068.48 | 0.00 |
June | 0.00 | 0.00 | 0.216434E+11 | 0.152594E+11 | 38787.26 | 26-JUN-06:01 | 15849.13 | 0.00 |
July | 0.00 | 0.00 | 0.240240E+11 | 0.138789E+11 | 38821.17 | 23-JUL-07:01 | 15999.67 | 0.00 |
August | 0.00 | 0.00 | 0.242737E+11 | 0.131120E+11 | 38905.65 | 21-AUG-06:01 | 14646.36 | 0.00 |
September | 0.00 | 0.00 | 0.195884E+11 | 0.114979E+11 | 38915.30 | 10-SEP-07:02 | 15627.32 | 0.00 |
October | 0.00 | 0.00 | 0.127630E+11 | 0.101903E+11 | 36707.56 | 12-OCT-06:02 | 21902.64 | 0.00 |
November | 0.00 | 0.00 | 0.689855E+10 | 0.606943E+10 | 12619.32 | 09-NOV-07:03 | 8469.32 | 0.00 |
December | 0.00 | 0.00 | 0.199132E+10 | 0.176406E+10 | 5978.25 | 28-DEC-14:00 | 5439.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155640E+12 | 0.109774E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.925079E+09 | 0.843355E+09 | 4731.86 | 4465.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242737E+11 | 0.154382E+11 | 38915.30 | 26453.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.834442E+09 | 0.760311E+09 | 4596.01 | 12-JAN-15:00 | 4335.98 | 0.00 |
February | 0.00 | 0.00 | 0.313062E+10 | 0.277571E+10 | 8001.03 | 22-FEB-14:00 | 7362.37 | 0.00 |
March | 0.00 | 0.00 | 0.809057E+10 | 0.709591E+10 | 28946.60 | 11-MAR-07:03 | 20326.80 | 0.00 |
April | 0.00 | 0.00 | 0.130559E+11 | 0.117988E+11 | 35750.85 | 17-APR-06:01 | 26666.50 | 0.00 |
May | 0.00 | 0.00 | 0.193238E+11 | 0.155509E+11 | 38156.49 | 23-MAY-06:01 | 19207.13 | 0.00 |
June | 0.00 | 0.00 | 0.217748E+11 | 0.153691E+11 | 38857.93 | 26-JUN-06:01 | 16011.45 | 0.00 |
July | 0.00 | 0.00 | 0.241716E+11 | 0.139926E+11 | 38891.90 | 23-JUL-07:03 | 15938.21 | 0.00 |
August | 0.00 | 0.00 | 0.243847E+11 | 0.131948E+11 | 38976.54 | 21-AUG-06:01 | 14762.41 | 0.00 |
September | 0.00 | 0.00 | 0.196778E+11 | 0.115654E+11 | 38986.20 | 10-SEP-07:02 | 15675.07 | 0.00 |
October | 0.00 | 0.00 | 0.128144E+11 | 0.102343E+11 | 36776.63 | 12-OCT-06:02 | 21976.27 | 0.00 |
November | 0.00 | 0.00 | 0.685246E+10 | 0.602819E+10 | 12367.15 | 09-NOV-07:03 | 8295.21 | 0.00 |
December | 0.00 | 0.00 | 0.187687E+10 | 0.166337E+10 | 5836.62 | 28-DEC-14:00 | 5308.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155988E+12 | 0.110030E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.834442E+09 | 0.760311E+09 | 4596.01 | 4335.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.243847E+11 | 0.155509E+11 | 38986.20 | 26666.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.690348E+09 | 0.627771E+09 | 4329.10 | 12-JAN-15:00 | 4080.23 | 0.00 |
February | 0.00 | 0.00 | 0.292619E+10 | 0.259516E+10 | 7807.80 | 22-FEB-14:00 | 7178.82 | 0.00 |
March | 0.00 | 0.00 | 0.785011E+10 | 0.688125E+10 | 26459.39 | 11-MAR-07:03 | 18421.59 | 0.00 |
April | 0.00 | 0.00 | 0.128632E+11 | 0.116194E+11 | 35577.90 | 17-APR-06:01 | 26458.29 | 0.00 |
May | 0.00 | 0.00 | 0.191429E+11 | 0.153934E+11 | 37975.33 | 23-MAY-06:01 | 18960.22 | 0.00 |
June | 0.00 | 0.00 | 0.215831E+11 | 0.152126E+11 | 38682.80 | 26-JUN-06:01 | 15819.21 | 0.00 |
July | 0.00 | 0.00 | 0.239832E+11 | 0.138521E+11 | 38716.61 | 23-JUL-07:01 | 15911.61 | 0.00 |
August | 0.00 | 0.00 | 0.241645E+11 | 0.130341E+11 | 38800.87 | 21-AUG-06:01 | 14577.93 | 0.00 |
September | 0.00 | 0.00 | 0.194652E+11 | 0.114071E+11 | 38810.49 | 10-SEP-07:02 | 15435.99 | 0.00 |
October | 0.00 | 0.00 | 0.126090E+11 | 0.100598E+11 | 36603.25 | 12-OCT-06:02 | 21707.23 | 0.00 |
November | 0.00 | 0.00 | 0.663681E+10 | 0.583509E+10 | 10947.82 | 09-NOV-13:40 | 9571.52 | 0.00 |
December | 0.00 | 0.00 | 0.166279E+10 | 0.147473E+10 | 5640.32 | 02-DEC-14:00 | 5640.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153577E+12 | 0.107993E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.690348E+09 | 0.627771E+09 | 4329.10 | 4080.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241645E+11 | 0.153934E+11 | 38810.49 | 26458.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.978653E+09 | 0.870127E+09 | 7656.94 | 12-JAN-15:10 | 7026.80 | 0.00 |
February | 0.00 | 0.00 | 0.485276E+10 | 0.422595E+10 | 14423.26 | 22-FEB-14:00 | 12947.34 | 0.00 |
March | 0.00 | 0.00 | 0.140288E+11 | 0.120900E+11 | 42975.85 | 11-MAR-08:62 | 30743.17 | 0.00 |
April | 0.00 | 0.00 | 0.233649E+11 | 0.209738E+11 | 64378.71 | 17-APR-07:01 | 47527.17 | 0.00 |
May | 0.00 | 0.00 | 0.350557E+11 | 0.279515E+11 | 67558.89 | 21-MAY-08:61 | 39933.90 | 0.00 |
June | 0.00 | 0.00 | 0.395854E+11 | 0.276558E+11 | 70144.79 | 25-JUN-08:62 | 29955.69 | 0.00 |
July | 0.00 | 0.00 | 0.436910E+11 | 0.248466E+11 | 70130.57 | 23-JUL-08:61 | 28339.67 | 0.00 |
August | 0.00 | 0.00 | 0.442691E+11 | 0.234135E+11 | 70351.20 | 21-AUG-07:01 | 26293.19 | 0.00 |
September | 0.00 | 0.00 | 0.353005E+11 | 0.203470E+11 | 70383.10 | 04-SEP-08:61 | 28766.94 | 0.00 |
October | 0.00 | 0.00 | 0.228882E+11 | 0.179815E+11 | 65925.96 | 12-OCT-07:02 | 39962.17 | 0.00 |
November | 0.00 | 0.00 | 0.116598E+11 | 0.100496E+11 | 20387.77 | 09-NOV-13:40 | 17455.07 | 0.00 |
December | 0.00 | 0.00 | 0.244956E+10 | 0.213594E+10 | 9991.97 | 28-DEC-14:00 | 8831.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.278124E+12 | 0.192541E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.978653E+09 | 0.870127E+09 | 7656.94 | 7026.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.442691E+11 | 0.279515E+11 | 70383.10 | 47527.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.461459E+09 | 0.411404E+09 | 3924.52 | 12-JAN-15:10 | 3620.18 | 0.00 |
February | 0.00 | 0.00 | 0.247368E+10 | 0.216457E+10 | 7481.37 | 22-FEB-14:00 | 6740.39 | 0.00 |
March | 0.00 | 0.00 | 0.726224E+10 | 0.628031E+10 | 20433.62 | 11-MAR-08:62 | 14612.89 | 0.00 |
April | 0.00 | 0.00 | 0.121391E+11 | 0.109153E+11 | 33759.44 | 17-APR-07:01 | 24930.53 | 0.00 |
May | 0.00 | 0.00 | 0.182379E+11 | 0.145649E+11 | 35411.48 | 21-MAY-08:61 | 20911.03 | 0.00 |
June | 0.00 | 0.00 | 0.205685E+11 | 0.143952E+11 | 36760.75 | 25-JUN-08:62 | 15588.25 | 0.00 |
July | 0.00 | 0.00 | 0.227027E+11 | 0.129418E+11 | 36753.30 | 23-JUL-08:61 | 14775.18 | 0.00 |
August | 0.00 | 0.00 | 0.229822E+11 | 0.121839E+11 | 36868.93 | 21-AUG-07:01 | 13627.98 | 0.00 |
September | 0.00 | 0.00 | 0.183333E+11 | 0.105928E+11 | 36885.65 | 04-SEP-08:03 | 14809.72 | 0.00 |
October | 0.00 | 0.00 | 0.118815E+11 | 0.936345E+10 | 34530.16 | 12-OCT-07:02 | 21069.17 | 0.00 |
November | 0.00 | 0.00 | 0.604082E+10 | 0.522696E+10 | 10641.65 | 06-NOV-14:00 | 8845.25 | 0.00 |
December | 0.00 | 0.00 | 0.121920E+10 | 0.106907E+10 | 5130.73 | 28-DEC-14:00 | 4553.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144302E+12 | 0.100110E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.461459E+09 | 0.411404E+09 | 3924.52 | 3620.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229822E+11 | 0.145649E+11 | 36885.65 | 24930.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.433056E+09 | 0.385612E+09 | 3854.91 | 12-JAN-15:10 | 3554.47 | 0.00 |
February | 0.00 | 0.00 | 0.241526E+10 | 0.211350E+10 | 7411.04 | 22-FEB-14:00 | 6674.49 | 0.00 |
March | 0.00 | 0.00 | 0.718945E+10 | 0.621558E+10 | 19823.06 | 11-MAR-08:62 | 14137.27 | 0.00 |
April | 0.00 | 0.00 | 0.120836E+11 | 0.108637E+11 | 33663.43 | 17-APR-07:01 | 24839.42 | 0.00 |
May | 0.00 | 0.00 | 0.181863E+11 | 0.145201E+11 | 35310.71 | 21-MAY-08:61 | 20829.50 | 0.00 |
June | 0.00 | 0.00 | 0.205150E+11 | 0.143511E+11 | 36657.73 | 25-JUN-08:62 | 15508.05 | 0.00 |
July | 0.00 | 0.00 | 0.226522E+11 | 0.129035E+11 | 36650.30 | 23-JUL-08:04 | 14423.72 | 0.00 |
August | 0.00 | 0.00 | 0.229274E+11 | 0.121435E+11 | 36765.60 | 21-AUG-07:01 | 13570.02 | 0.00 |
September | 0.00 | 0.00 | 0.182806E+11 | 0.105533E+11 | 36782.27 | 04-SEP-08:03 | 14752.39 | 0.00 |
October | 0.00 | 0.00 | 0.118255E+11 | 0.931586E+10 | 34435.90 | 12-OCT-07:02 | 20966.68 | 0.00 |
November | 0.00 | 0.00 | 0.597733E+10 | 0.517061E+10 | 10588.34 | 06-NOV-14:00 | 8797.24 | 0.00 |
December | 0.00 | 0.00 | 0.116967E+10 | 0.102620E+10 | 5053.45 | 28-DEC-14:00 | 4483.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143655E+12 | 0.995625E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.433056E+09 | 0.385612E+09 | 3854.91 | 3554.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229274E+11 | 0.145201E+11 | 36782.27 | 24839.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.377594E+09 | 0.335564E+09 | 3701.01 | 12-JAN-15:10 | 3411.58 | 0.00 |
February | 0.00 | 0.00 | 0.228548E+10 | 0.200168E+10 | 7290.27 | 22-FEB-15:10 | 6594.15 | 0.00 |
March | 0.00 | 0.00 | 0.705205E+10 | 0.609685E+10 | 17687.40 | 11-MAR-08:62 | 12514.18 | 0.00 |
April | 0.00 | 0.00 | 0.120845E+11 | 0.108663E+11 | 33791.41 | 17-APR-07:01 | 24934.43 | 0.00 |
May | 0.00 | 0.00 | 0.182829E+11 | 0.146090E+11 | 35446.05 | 21-MAY-08:61 | 20911.28 | 0.00 |
June | 0.00 | 0.00 | 0.206339E+11 | 0.144546E+11 | 36802.61 | 25-JUN-08:62 | 15505.72 | 0.00 |
July | 0.00 | 0.00 | 0.228032E+11 | 0.130222E+11 | 36795.15 | 23-JUL-08:61 | 14775.44 | 0.00 |
August | 0.00 | 0.00 | 0.230755E+11 | 0.122544E+11 | 36910.91 | 21-AUG-07:01 | 13636.14 | 0.00 |
September | 0.00 | 0.00 | 0.183771E+11 | 0.106289E+11 | 36927.65 | 04-SEP-08:03 | 14826.65 | 0.00 |
October | 0.00 | 0.00 | 0.118392E+11 | 0.933073E+10 | 34562.60 | 12-OCT-07:02 | 20997.30 | 0.00 |
November | 0.00 | 0.00 | 0.586965E+10 | 0.507794E+10 | 10545.31 | 09-NOV-13:50 | 9078.18 | 0.00 |
December | 0.00 | 0.00 | 0.106430E+10 | 0.935534E+09 | 4905.15 | 28-DEC-14:00 | 4349.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143745E+12 | 0.996138E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377594E+09 | 0.335564E+09 | 3701.01 | 3411.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230755E+11 | 0.146090E+11 | 36927.65 | 24934.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.419570E+09 | 0.379433E+09 | 3914.57 | 12-JAN-15:10 | 3667.78 | 0.00 |
February | 0.00 | 0.00 | 0.245686E+10 | 0.218702E+10 | 7994.16 | 22-FEB-14:00 | 7306.06 | 0.00 |
March | 0.00 | 0.00 | 0.764942E+10 | 0.670693E+10 | 14033.75 | 29-MAR-13:00 | 11697.45 | 0.00 |
April | 0.00 | 0.00 | 0.136189E+11 | 0.123689E+11 | 37992.71 | 17-APR-07:01 | 28174.99 | 0.00 |
May | 0.00 | 0.00 | 0.206572E+11 | 0.167878E+11 | 40114.89 | 24-MAY-07:02 | 21231.30 | 0.00 |
June | 0.00 | 0.00 | 0.231120E+11 | 0.166103E+11 | 41314.83 | 25-JUN-08:62 | 17205.45 | 0.00 |
July | 0.00 | 0.00 | 0.254956E+11 | 0.150967E+11 | 41306.46 | 23-JUL-08:04 | 15796.80 | 0.00 |
August | 0.00 | 0.00 | 0.257829E+11 | 0.142932E+11 | 41436.41 | 21-AUG-07:01 | 15777.77 | 0.00 |
September | 0.00 | 0.00 | 0.205315E+11 | 0.123377E+11 | 41455.20 | 04-SEP-08:03 | 16813.24 | 0.00 |
October | 0.00 | 0.00 | 0.133644E+11 | 0.107450E+11 | 38714.35 | 01-OCT-08:62 | 26289.64 | 0.00 |
November | 0.00 | 0.00 | 0.645961E+10 | 0.567673E+10 | 11685.51 | 09-NOV-13:30 | 10150.86 | 0.00 |
December | 0.00 | 0.00 | 0.117292E+10 | 0.104996E+10 | 5250.31 | 28-DEC-14:00 | 4731.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160721E+12 | 0.114240E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.419570E+09 | 0.379433E+09 | 3914.57 | 3667.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257829E+11 | 0.167878E+11 | 41455.20 | 28174.99 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.224630E+10 | 0.37 | 3074.92 | 02-JAN-08:61 | 0.90 |
February | 0.202104E+10 | 0.37 | 1377.92 | 02-FEB-08:05 | 0.58 |
March | 0.224062E+10 | 0.37 | 1729.34 | 11-MAR-08:62 | 0.67 |
April | 0.217819E+10 | 0.37 | 3074.92 | 15-APR-07:02 | 0.89 |
May | 0.239577E+10 | 0.38 | 3074.92 | 01-MAY-07:01 | 0.89 |
June | 0.245821E+10 | 0.39 | 3074.92 | 01-JUN-07:02 | 0.89 |
July | 0.255069E+10 | 0.39 | 3074.92 | 01-JUL-07:01 | 0.89 |
August | 0.252344E+10 | 0.39 | 3074.92 | 01-AUG-07:01 | 0.88 |
September | 0.227527E+10 | 0.38 | 3074.92 | 01-SEP-07:01 | 0.88 |
October | 0.223702E+10 | 0.37 | 3074.92 | 01-OCT-07:02 | 0.89 |
November | 0.215638E+10 | 0.37 | 1229.97 | 26-NOV-21:40 | 0.54 |
December | 0.224316E+10 | 0.37 | 1587.93 | 23-DEC-08:62 | 0.64 |
Annual Sum or Average | 0.275261E+11 | 0.38 | |||
Minimum of Months | 0.202104E+10 | 0.37 | 1229.97 | 0.54 | |
Maximum of Months | 0.255069E+10 | 0.39 | 3074.92 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.894488E+09 | 0.39 | 910.80 | 02-JAN-08:61 | 0.68 |
February | 0.827662E+09 | 0.39 | 658.72 | 02-FEB-08:40 | 0.56 |
March | 0.954286E+09 | 0.39 | 967.84 | 11-MAR-08:62 | 0.70 |
April | 0.957504E+09 | 0.39 | 1574.11 | 15-APR-07:02 | 0.89 |
May | 0.110038E+10 | 0.39 | 1574.11 | 01-MAY-07:01 | 0.89 |
June | 0.114724E+10 | 0.40 | 1574.11 | 01-JUN-07:02 | 0.89 |
July | 0.119861E+10 | 0.40 | 1574.11 | 01-JUL-07:01 | 0.89 |
August | 0.118046E+10 | 0.40 | 1574.11 | 01-AUG-07:01 | 0.89 |
September | 0.103950E+10 | 0.39 | 1574.11 | 01-SEP-07:01 | 0.89 |
October | 0.977287E+09 | 0.38 | 1574.11 | 01-OCT-07:02 | 0.89 |
November | 0.907450E+09 | 0.39 | 629.64 | 02-NOV-07:05 | 0.54 |
December | 0.901133E+09 | 0.39 | 705.94 | 23-DEC-08:10 | 0.58 |
Annual Sum or Average | 0.120860E+11 | 0.39 | |||
Minimum of Months | 0.827662E+09 | 0.38 | 629.64 | 0.54 | |
Maximum of Months | 0.119861E+10 | 0.40 | 1574.11 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.917938E+09 | 0.29 | 1314.80 | 02-JAN-07:02 | 0.82 |
February | 0.825751E+09 | 0.29 | 673.53 | 02-FEB-07:30 | 0.57 |
March | 0.929903E+09 | 0.30 | 1220.51 | 11-MAR-07:03 | 0.79 |
April | 0.892512E+09 | 0.30 | 1574.47 | 02-APR-07:02 | 0.89 |
May | 0.100252E+10 | 0.31 | 1574.47 | 01-MAY-06:01 | 0.90 |
June | 0.103596E+10 | 0.32 | 1574.47 | 01-JUN-06:01 | 0.89 |
July | 0.105682E+10 | 0.31 | 1574.47 | 01-JUL-06:01 | 0.89 |
August | 0.106686E+10 | 0.32 | 1574.47 | 01-AUG-06:01 | 0.88 |
September | 0.936124E+09 | 0.30 | 1574.47 | 01-SEP-06:01 | 0.88 |
October | 0.914807E+09 | 0.29 | 1574.47 | 01-OCT-07:02 | 0.89 |
November | 0.884220E+09 | 0.29 | 629.79 | 16-NOV-09:50 | 0.54 |
December | 0.907689E+09 | 0.29 | 701.53 | 31-DEC-08:13 | 0.58 |
Annual Sum or Average | 0.113711E+11 | 0.30 | |||
Minimum of Months | 0.825751E+09 | 0.29 | 629.79 | 0.54 | |
Maximum of Months | 0.106686E+10 | 0.32 | 1574.47 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.921582E+09 | 0.29 | 1563.52 | 02-JAN-07:02 | 0.89 |
February | 0.827847E+09 | 0.29 | 689.37 | 02-FEB-07:15 | 0.57 |
March | 0.932017E+09 | 0.30 | 1223.32 | 11-MAR-07:03 | 0.79 |
April | 0.894699E+09 | 0.30 | 1578.02 | 02-APR-07:02 | 0.89 |
May | 0.100641E+10 | 0.31 | 1578.02 | 01-MAY-06:01 | 0.90 |
June | 0.104002E+10 | 0.32 | 1578.02 | 01-JUN-06:01 | 0.89 |
July | 0.106144E+10 | 0.31 | 1578.02 | 01-JUL-06:01 | 0.89 |
August | 0.107058E+10 | 0.32 | 1578.02 | 01-AUG-06:01 | 0.88 |
September | 0.938858E+09 | 0.30 | 1578.02 | 01-SEP-06:01 | 0.88 |
October | 0.917022E+09 | 0.29 | 1578.02 | 01-OCT-07:02 | 0.89 |
November | 0.886216E+09 | 0.29 | 631.21 | 03-NOV-07:40 | 0.54 |
December | 0.909980E+09 | 0.29 | 725.07 | 23-DEC-07:10 | 0.59 |
Annual Sum or Average | 0.114067E+11 | 0.30 | |||
Minimum of Months | 0.827847E+09 | 0.29 | 631.21 | 0.54 | |
Maximum of Months | 0.107058E+10 | 0.32 | 1578.02 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.918450E+09 | 0.30 | 1569.21 | 01-JAN-08:62 | 0.89 |
February | 0.823604E+09 | 0.29 | 688.84 | 02-FEB-07:15 | 0.58 |
March | 0.926721E+09 | 0.30 | 1093.15 | 11-MAR-07:03 | 0.75 |
April | 0.889048E+09 | 0.29 | 1569.21 | 02-APR-07:02 | 0.89 |
May | 0.999004E+09 | 0.31 | 1569.21 | 01-MAY-06:01 | 0.90 |
June | 0.103222E+10 | 0.32 | 1569.21 | 01-JUN-06:01 | 0.89 |
July | 0.105362E+10 | 0.31 | 1569.21 | 01-JUL-06:01 | 0.89 |
August | 0.106203E+10 | 0.32 | 1569.21 | 01-AUG-06:01 | 0.88 |
September | 0.931520E+09 | 0.30 | 1569.21 | 01-SEP-06:01 | 0.88 |
October | 0.911648E+09 | 0.29 | 1569.21 | 01-OCT-07:02 | 0.89 |
November | 0.881268E+09 | 0.29 | 627.68 | 06-NOV-09:40 | 0.54 |
December | 0.905287E+09 | 0.29 | 728.84 | 31-DEC-08:10 | 0.60 |
Annual Sum or Average | 0.113344E+11 | 0.30 | |||
Minimum of Months | 0.823604E+09 | 0.29 | 627.68 | 0.54 | |
Maximum of Months | 0.106203E+10 | 0.32 | 1569.21 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150870E+10 | 0.27 | 2787.78 | 01-JAN-09:01 | 0.89 |
February | 0.135117E+10 | 0.27 | 1311.91 | 02-FEB-08:05 | 0.60 |
March | 0.152160E+10 | 0.28 | 1704.82 | 11-MAR-08:62 | 0.70 |
April | 0.146405E+10 | 0.27 | 2787.78 | 02-APR-08:62 | 0.89 |
May | 0.167913E+10 | 0.29 | 2787.78 | 01-MAY-07:01 | 0.90 |
June | 0.174791E+10 | 0.30 | 2787.78 | 01-JUN-07:02 | 0.89 |
July | 0.179452E+10 | 0.30 | 2787.78 | 01-JUL-07:01 | 0.89 |
August | 0.180440E+10 | 0.30 | 2787.78 | 01-AUG-07:01 | 0.88 |
September | 0.156148E+10 | 0.28 | 2787.78 | 01-SEP-07:01 | 0.88 |
October | 0.149714E+10 | 0.27 | 2787.78 | 01-OCT-08:62 | 0.89 |
November | 0.144518E+10 | 0.27 | 1115.11 | 02-NOV-07:05 | 0.54 |
December | 0.148453E+10 | 0.27 | 1511.78 | 23-DEC-08:62 | 0.66 |
Annual Sum or Average | 0.188598E+11 | 0.28 | |||
Minimum of Months | 0.135117E+10 | 0.27 | 1115.11 | 0.54 | |
Maximum of Months | 0.180440E+10 | 0.30 | 2787.78 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.825005E+09 | 0.28 | 1524.48 | 01-JAN-09:01 | 0.93 |
February | 0.738786E+09 | 0.28 | 721.11 | 02-FEB-08:05 | 0.63 |
March | 0.832042E+09 | 0.29 | 818.55 | 11-MAR-08:62 | 0.67 |
April | 0.800807E+09 | 0.28 | 1524.48 | 02-APR-08:62 | 0.92 |
May | 0.920113E+09 | 0.30 | 1524.48 | 01-MAY-07:01 | 0.93 |
June | 0.956703E+09 | 0.31 | 1524.48 | 01-JUN-07:02 | 0.92 |
July | 0.980728E+09 | 0.31 | 1524.48 | 01-JUL-07:01 | 0.92 |
August | 0.985612E+09 | 0.31 | 1524.48 | 01-AUG-07:01 | 0.91 |
September | 0.853251E+09 | 0.29 | 1524.48 | 01-SEP-07:01 | 0.91 |
October | 0.818500E+09 | 0.28 | 1524.48 | 01-OCT-08:62 | 0.92 |
November | 0.790292E+09 | 0.28 | 609.79 | 05-NOV-11:00 | 0.56 |
December | 0.811695E+09 | 0.28 | 844.05 | 23-DEC-08:62 | 0.69 |
Annual Sum or Average | 0.103135E+11 | 0.29 | |||
Minimum of Months | 0.738786E+09 | 0.28 | 609.79 | 0.56 | |
Maximum of Months | 0.985612E+09 | 0.31 | 1524.48 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.822708E+09 | 0.28 | 1519.14 | 01-JAN-09:01 | 0.93 |
February | 0.736382E+09 | 0.28 | 730.02 | 02-FEB-09:00 | 0.63 |
March | 0.829119E+09 | 0.29 | 785.61 | 11-MAR-08:62 | 0.66 |
April | 0.797962E+09 | 0.28 | 1519.14 | 02-APR-08:62 | 0.92 |
May | 0.917123E+09 | 0.30 | 1519.14 | 01-MAY-07:01 | 0.93 |
June | 0.953634E+09 | 0.31 | 1519.14 | 01-JUN-07:02 | 0.92 |
July | 0.977814E+09 | 0.31 | 1519.14 | 01-JUL-07:01 | 0.92 |
August | 0.982575E+09 | 0.31 | 1519.14 | 01-AUG-07:01 | 0.91 |
September | 0.850393E+09 | 0.29 | 1519.14 | 01-SEP-07:01 | 0.91 |
October | 0.815611E+09 | 0.28 | 1519.14 | 01-OCT-08:62 | 0.92 |
November | 0.787523E+09 | 0.28 | 607.66 | 01-NOV-09:10 | 0.56 |
December | 0.809031E+09 | 0.28 | 881.71 | 23-DEC-08:62 | 0.71 |
Annual Sum or Average | 0.102799E+11 | 0.29 | |||
Minimum of Months | 0.736382E+09 | 0.28 | 607.66 | 0.56 | |
Maximum of Months | 0.982575E+09 | 0.31 | 1519.14 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.828659E+09 | 0.28 | 1526.63 | 01-JAN-09:01 | 0.93 |
February | 0.740587E+09 | 0.28 | 849.28 | 11-FEB-08:62 | 0.69 |
March | 0.833182E+09 | 0.29 | 669.12 | 11-MAR-08:62 | 0.59 |
April | 0.801882E+09 | 0.28 | 1526.63 | 02-APR-08:62 | 0.92 |
May | 0.922945E+09 | 0.30 | 1526.63 | 01-MAY-07:01 | 0.93 |
June | 0.959960E+09 | 0.31 | 1526.63 | 01-JUN-07:02 | 0.92 |
July | 0.985057E+09 | 0.31 | 1526.63 | 01-JUL-07:01 | 0.92 |
August | 0.989271E+09 | 0.31 | 1526.63 | 01-AUG-07:01 | 0.91 |
September | 0.855508E+09 | 0.29 | 1526.63 | 01-SEP-07:01 | 0.91 |
October | 0.819672E+09 | 0.28 | 1526.63 | 01-OCT-08:62 | 0.92 |
November | 0.791405E+09 | 0.28 | 610.65 | 02-NOV-17:50 | 0.56 |
December | 0.813700E+09 | 0.28 | 1019.93 | 23-DEC-08:62 | 0.76 |
Annual Sum or Average | 0.103418E+11 | 0.29 | |||
Minimum of Months | 0.740587E+09 | 0.28 | 610.65 | 0.56 | |
Maximum of Months | 0.989271E+09 | 0.31 | 1526.63 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.935616E+09 | 0.27 | 1717.39 | 01-JAN-09:01 | 0.89 |
February | 0.835014E+09 | 0.27 | 1468.83 | 11-FEB-08:62 | 0.83 |
March | 0.937280E+09 | 0.28 | 686.95 | 01-MAR-18:00 | 0.54 |
April | 0.902094E+09 | 0.27 | 1717.39 | 16-APR-08:61 | 0.89 |
May | 0.104193E+10 | 0.29 | 1717.39 | 01-MAY-07:01 | 0.90 |
June | 0.108213E+10 | 0.30 | 1717.39 | 01-JUN-07:02 | 0.89 |
July | 0.111048E+10 | 0.30 | 1717.39 | 01-JUL-07:01 | 0.88 |
August | 0.111163E+10 | 0.30 | 1717.39 | 01-AUG-07:01 | 0.88 |
September | 0.963544E+09 | 0.28 | 1717.39 | 01-SEP-07:01 | 0.88 |
October | 0.922287E+09 | 0.27 | 1717.39 | 01-OCT-08:62 | 0.89 |
November | 0.890311E+09 | 0.27 | 706.79 | 27-NOV-08:30 | 0.55 |
December | 0.917595E+09 | 0.27 | 1556.62 | 23-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.116499E+11 | 0.28 | |||
Minimum of Months | 0.835014E+09 | 0.27 | 686.95 | 0.54 | |
Maximum of Months | 0.111163E+10 | 0.30 | 1717.39 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.276875E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.404284E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.765366E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.117013E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162849E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175895E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.181735E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.174192E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.147331E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108381E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.656475E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.337225E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131142E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.276875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.181735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144723E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215075E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.383748E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.560788E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.776738E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.833981E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.861800E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.826663E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.697457E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.523820E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.336363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.185770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.634693E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144723E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.861800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.116977E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169271E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.313700E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.460999E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.650808E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.697696E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.707352E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.694781E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.575345E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.430000E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.272941E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.144627E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.523450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116977E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.707352E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114914E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.167175E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.313366E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.462712E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.654580E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.701512E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.711386E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.697803E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.577735E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.431522E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.272066E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141863E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.524663E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114914E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.711386E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110730E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161510E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.306841E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.457183E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.648909E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.695619E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.705887E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.691606E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.571937E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.426037E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.266244E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135734E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.517824E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110730E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.705887E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.178191E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.269173E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.542136E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.827483E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119015E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127951E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.128903E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.126720E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103695E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.766895E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.463357E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.932642E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.178191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128903E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.951782E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141122E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.281834E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.428354E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.615959E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.661436E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.666108E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.654396E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.535752E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.397169E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.241523E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114416E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.483325E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.951782E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.666108E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.941792E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139362E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.279679E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.426544E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.614155E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.659605E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.664443E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.652646E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.534116E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.395450E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.239635E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112826E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.481264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.941792E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.664443E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.932733E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136434E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.276747E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.427180E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.617639E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.663686E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.669127E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.657055E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.537140E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396336E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.237401E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110485E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.482250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.932733E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.669127E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105144E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150765E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.304469E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.481648E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.700055E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.748609E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.754582E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.740099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.604715E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.447327E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.263611E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123897E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.542492E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105144E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.754582E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.224630E+10 | 0.188033E+10 | 0.565319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202104E+10 | 0.737410E+10 | 74232361.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224062E+10 | 0.195740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217819E+10 | 0.327014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239577E+10 | 0.476491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245821E+10 | 0.539898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.255069E+10 | 0.608267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252344E+10 | 0.600923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227527E+10 | 0.494814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223702E+10 | 0.319304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215638E+10 | 0.162246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224316E+10 | 0.409493E+10 | 0.102583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275261E+11 | 0.385819E+12 | 0.742134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202104E+10 | 0.188033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255069E+10 | 0.608267E+11 | 0.565319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.894488E+09 | 0.203549E+10 | 0.102786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827662E+09 | 0.495009E+10 | 2014836.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.954286E+09 | 0.106585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.957504E+09 | 0.161775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110038E+10 | 0.230292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114724E+10 | 0.257782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119861E+10 | 0.289891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118046E+10 | 0.287257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103950E+10 | 0.237203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977287E+09 | 0.160472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.907450E+09 | 0.924730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.901133E+09 | 0.355266E+10 | 12423561.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120860E+11 | 0.192911E+12 | 0.117224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827662E+09 | 0.203549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119861E+10 | 0.289891E+11 | 0.102786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.917938E+09 | 0.925079E+09 | 0.250726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.825751E+09 | 0.322183E+10 | 18430776.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929903E+09 | 0.811525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892512E+09 | 0.129992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100252E+10 | 0.191959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103596E+10 | 0.216434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105682E+10 | 0.240240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106686E+10 | 0.242737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936124E+09 | 0.195884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914807E+09 | 0.127630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.884220E+09 | 0.689855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907689E+09 | 0.199132E+10 | 30686443.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113711E+11 | 0.155640E+12 | 0.299843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.825751E+09 | 0.925079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106686E+10 | 0.242737E+11 | 0.250726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.921582E+09 | 0.834442E+09 | 0.311770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827847E+09 | 0.313062E+10 | 27428366.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.932017E+09 | 0.809057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894699E+09 | 0.130559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100641E+10 | 0.193238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104002E+10 | 0.217748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106144E+10 | 0.241716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107058E+10 | 0.243847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938858E+09 | 0.196778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.917022E+09 | 0.128144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.886216E+09 | 0.685246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909980E+09 | 0.187687E+10 | 40057720.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114067E+11 | 0.155988E+12 | 0.379256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827847E+09 | 0.834442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107058E+10 | 0.243847E+11 | 0.311770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.918450E+09 | 0.690348E+09 | 0.387742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.823604E+09 | 0.292619E+10 | 41877703.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926721E+09 | 0.785011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.889048E+09 | 0.128632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999004E+09 | 0.191429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103222E+10 | 0.215831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105362E+10 | 0.239832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106203E+10 | 0.241645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.931520E+09 | 0.194652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911648E+09 | 0.126090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881268E+09 | 0.663681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905287E+09 | 0.166279E+10 | 54794611.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113344E+11 | 0.153577E+12 | 0.484414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823604E+09 | 0.690348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106203E+10 | 0.241645E+11 | 0.387742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150870E+10 | 0.978653E+09 | 0.755055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135117E+10 | 0.485276E+10 | 90904267.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152160E+10 | 0.140288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146405E+10 | 0.233649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167913E+10 | 0.350557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174791E+10 | 0.395854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179452E+10 | 0.436910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180440E+10 | 0.442691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156148E+10 | 0.353005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149714E+10 | 0.228882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144518E+10 | 0.116598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148453E+10 | 0.244956E+10 | 0.125561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188598E+11 | 0.278124E+12 | 0.971520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135117E+10 | 0.978653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180440E+10 | 0.442691E+11 | 0.755055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.825005E+09 | 0.461459E+09 | 0.395907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738786E+09 | 0.247368E+10 | 44235607.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832042E+09 | 0.726224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.800807E+09 | 0.121391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.920113E+09 | 0.182379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.956703E+09 | 0.205685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.980728E+09 | 0.227027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.985612E+09 | 0.229822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853251E+09 | 0.183333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818500E+09 | 0.118815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790292E+09 | 0.604082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.811695E+09 | 0.121920E+10 | 61702494.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103135E+11 | 0.144302E+12 | 0.501845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.738786E+09 | 0.461459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985612E+09 | 0.229822E+11 | 0.395907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.822708E+09 | 0.433056E+09 | 0.416895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736382E+09 | 0.241526E+10 | 50995979.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829119E+09 | 0.718945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797962E+09 | 0.120836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.917123E+09 | 0.181863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.953634E+09 | 0.205150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.977814E+09 | 0.226522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.982575E+09 | 0.229274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.850393E+09 | 0.182806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815611E+09 | 0.118255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787523E+09 | 0.597733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.809031E+09 | 0.116967E+10 | 68207084.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102799E+11 | 0.143655E+12 | 0.536098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.736382E+09 | 0.433056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.982575E+09 | 0.229274E+11 | 0.416895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.828659E+09 | 0.377594E+09 | 0.489759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740587E+09 | 0.228548E+10 | 72793181.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833182E+09 | 0.705205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801882E+09 | 0.120845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.922945E+09 | 0.182829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.959960E+09 | 0.206339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.985057E+09 | 0.228032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.989271E+09 | 0.230755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.855508E+09 | 0.183771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819672E+09 | 0.118392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791405E+09 | 0.586965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813700E+09 | 0.106430E+10 | 94034160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103418E+11 | 0.143745E+12 | 0.656586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740587E+09 | 0.377594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.989271E+09 | 0.230755E+11 | 0.489759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.935616E+09 | 0.419570E+09 | 0.692052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835014E+09 | 0.245686E+10 | 0.155621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.937280E+09 | 0.764942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.902094E+09 | 0.136189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104193E+10 | 0.206572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108213E+10 | 0.231120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111048E+10 | 0.254956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111163E+10 | 0.257829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.963544E+09 | 0.205315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922287E+09 | 0.133644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.890311E+09 | 0.645961E+10 | 680819.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.917595E+09 | 0.117292E+10 | 0.192688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116499E+11 | 0.160721E+12 | 0.104104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835014E+09 | 0.419570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111163E+10 | 0.257829E+11 | 0.692052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.224630E+10 | 0.00 | 0.00 | 0.00 | 0.522453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202104E+10 | 0.00 | 0.00 | 0.00 | 0.202180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224062E+10 | 0.00 | 0.00 | 0.00 | 0.541304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217819E+10 | 0.00 | 0.00 | 0.00 | 0.952307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239577E+10 | 0.00 | 0.00 | 0.00 | 0.138891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245821E+10 | 0.00 | 0.00 | 0.00 | 0.151313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.255069E+10 | 0.00 | 0.00 | 0.00 | 0.156228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252344E+10 | 0.00 | 0.00 | 0.00 | 0.148958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227527E+10 | 0.00 | 0.00 | 0.00 | 0.124578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223702E+10 | 0.00 | 0.00 | 0.00 | 0.860110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215638E+10 | 0.00 | 0.00 | 0.00 | 0.440837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224316E+10 | 0.00 | 0.00 | 0.00 | 0.112909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275261E+11 | 0.00 | 0.00 | 0.00 | 0.103616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202104E+10 | 0.00 | 0.00 | 0.00 | 0.522453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255069E+10 | 0.00 | 0.00 | 0.00 | 0.156228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.894488E+09 | 0.00 | 0.00 | 0.00 | 0.552739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827662E+09 | 0.00 | 0.00 | 0.00 | 0.132309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.954286E+09 | 0.00 | 0.00 | 0.00 | 0.288319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.957504E+09 | 0.00 | 0.00 | 0.00 | 0.465038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110038E+10 | 0.00 | 0.00 | 0.00 | 0.666700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114724E+10 | 0.00 | 0.00 | 0.00 | 0.719257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119861E+10 | 0.00 | 0.00 | 0.00 | 0.741939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118046E+10 | 0.00 | 0.00 | 0.00 | 0.708617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103950E+10 | 0.00 | 0.00 | 0.00 | 0.593507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977287E+09 | 0.00 | 0.00 | 0.00 | 0.426091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.907450E+09 | 0.00 | 0.00 | 0.00 | 0.245618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.901133E+09 | 0.00 | 0.00 | 0.00 | 0.956571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120860E+11 | 0.00 | 0.00 | 0.00 | 0.513833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827662E+09 | 0.00 | 0.00 | 0.00 | 0.552739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119861E+10 | 0.00 | 0.00 | 0.00 | 0.741939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.917938E+09 | 0.00 | 0.00 | 0.00 | 0.251833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.825751E+09 | 0.00 | 0.00 | 0.00 | 0.866960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929903E+09 | 0.00 | 0.00 | 0.00 | 0.220709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892512E+09 | 0.00 | 0.00 | 0.00 | 0.371748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100252E+10 | 0.00 | 0.00 | 0.00 | 0.550556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103596E+10 | 0.00 | 0.00 | 0.00 | 0.594100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105682E+10 | 0.00 | 0.00 | 0.00 | 0.601670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106686E+10 | 0.00 | 0.00 | 0.00 | 0.588095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936124E+09 | 0.00 | 0.00 | 0.00 | 0.481732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914807E+09 | 0.00 | 0.00 | 0.00 | 0.338520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.884220E+09 | 0.00 | 0.00 | 0.00 | 0.184519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907689E+09 | 0.00 | 0.00 | 0.00 | 0.538584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113711E+11 | 0.00 | 0.00 | 0.00 | 0.409739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.825751E+09 | 0.00 | 0.00 | 0.00 | 0.251833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106686E+10 | 0.00 | 0.00 | 0.00 | 0.601670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.921582E+09 | 0.00 | 0.00 | 0.00 | 0.227556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827847E+09 | 0.00 | 0.00 | 0.00 | 0.843904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.932017E+09 | 0.00 | 0.00 | 0.00 | 0.220164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894699E+09 | 0.00 | 0.00 | 0.00 | 0.373242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100641E+10 | 0.00 | 0.00 | 0.00 | 0.553939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104002E+10 | 0.00 | 0.00 | 0.00 | 0.597510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106144E+10 | 0.00 | 0.00 | 0.00 | 0.605242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107058E+10 | 0.00 | 0.00 | 0.00 | 0.590745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938858E+09 | 0.00 | 0.00 | 0.00 | 0.483849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.917022E+09 | 0.00 | 0.00 | 0.00 | 0.339820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.886216E+09 | 0.00 | 0.00 | 0.00 | 0.183445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909980E+09 | 0.00 | 0.00 | 0.00 | 0.508649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114067E+11 | 0.00 | 0.00 | 0.00 | 0.410597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827847E+09 | 0.00 | 0.00 | 0.00 | 0.227556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107058E+10 | 0.00 | 0.00 | 0.00 | 0.605242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.918450E+09 | 0.00 | 0.00 | 0.00 | 0.188854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.823604E+09 | 0.00 | 0.00 | 0.00 | 0.791493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926721E+09 | 0.00 | 0.00 | 0.00 | 0.214169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.889048E+09 | 0.00 | 0.00 | 0.00 | 0.368278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999004E+09 | 0.00 | 0.00 | 0.00 | 0.549009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103222E+10 | 0.00 | 0.00 | 0.00 | 0.592397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105362E+10 | 0.00 | 0.00 | 0.00 | 0.600526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106203E+10 | 0.00 | 0.00 | 0.00 | 0.585403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.931520E+09 | 0.00 | 0.00 | 0.00 | 0.478785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911648E+09 | 0.00 | 0.00 | 0.00 | 0.334872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881268E+09 | 0.00 | 0.00 | 0.00 | 0.178118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905287E+09 | 0.00 | 0.00 | 0.00 | 0.452050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113344E+11 | 0.00 | 0.00 | 0.00 | 0.404480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823604E+09 | 0.00 | 0.00 | 0.00 | 0.188854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106203E+10 | 0.00 | 0.00 | 0.00 | 0.600526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150870E+10 | 0.00 | 0.00 | 0.00 | 0.273210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135117E+10 | 0.00 | 0.00 | 0.00 | 0.134056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152160E+10 | 0.00 | 0.00 | 0.00 | 0.389976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146405E+10 | 0.00 | 0.00 | 0.00 | 0.681077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167913E+10 | 0.00 | 0.00 | 0.00 | 0.102224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174791E+10 | 0.00 | 0.00 | 0.00 | 0.110472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179452E+10 | 0.00 | 0.00 | 0.00 | 0.110958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180440E+10 | 0.00 | 0.00 | 0.00 | 0.108676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156148E+10 | 0.00 | 0.00 | 0.00 | 0.880799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149714E+10 | 0.00 | 0.00 | 0.00 | 0.617181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144518E+10 | 0.00 | 0.00 | 0.00 | 0.318838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148453E+10 | 0.00 | 0.00 | 0.00 | 0.678958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188598E+11 | 0.00 | 0.00 | 0.00 | 0.744044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135117E+10 | 0.00 | 0.00 | 0.00 | 0.273210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180440E+10 | 0.00 | 0.00 | 0.00 | 0.110958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.825005E+09 | 0.00 | 0.00 | 0.00 | 0.126777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738786E+09 | 0.00 | 0.00 | 0.00 | 0.672430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832042E+09 | 0.00 | 0.00 | 0.00 | 0.198629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.800807E+09 | 0.00 | 0.00 | 0.00 | 0.348273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.920113E+09 | 0.00 | 0.00 | 0.00 | 0.523948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.956703E+09 | 0.00 | 0.00 | 0.00 | 0.565766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.980728E+09 | 0.00 | 0.00 | 0.00 | 0.568036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.985612E+09 | 0.00 | 0.00 | 0.00 | 0.555835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853251E+09 | 0.00 | 0.00 | 0.00 | 0.450427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818500E+09 | 0.00 | 0.00 | 0.00 | 0.315319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790292E+09 | 0.00 | 0.00 | 0.00 | 0.162494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.811695E+09 | 0.00 | 0.00 | 0.00 | 0.332463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103135E+11 | 0.00 | 0.00 | 0.00 | 0.380189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.738786E+09 | 0.00 | 0.00 | 0.00 | 0.126777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985612E+09 | 0.00 | 0.00 | 0.00 | 0.568036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.822708E+09 | 0.00 | 0.00 | 0.00 | 0.119084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736382E+09 | 0.00 | 0.00 | 0.00 | 0.657233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829119E+09 | 0.00 | 0.00 | 0.00 | 0.196767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797962E+09 | 0.00 | 0.00 | 0.00 | 0.346748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.917123E+09 | 0.00 | 0.00 | 0.00 | 0.522443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.953634E+09 | 0.00 | 0.00 | 0.00 | 0.564241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.977814E+09 | 0.00 | 0.00 | 0.00 | 0.566661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.982575E+09 | 0.00 | 0.00 | 0.00 | 0.554389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.850393E+09 | 0.00 | 0.00 | 0.00 | 0.449077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815611E+09 | 0.00 | 0.00 | 0.00 | 0.313889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787523E+09 | 0.00 | 0.00 | 0.00 | 0.160883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.809031E+09 | 0.00 | 0.00 | 0.00 | 0.319229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102799E+11 | 0.00 | 0.00 | 0.00 | 0.378465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.736382E+09 | 0.00 | 0.00 | 0.00 | 0.119084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.982575E+09 | 0.00 | 0.00 | 0.00 | 0.566661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.828659E+09 | 0.00 | 0.00 | 0.00 | 0.104075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740587E+09 | 0.00 | 0.00 | 0.00 | 0.623757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833182E+09 | 0.00 | 0.00 | 0.00 | 0.193429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801882E+09 | 0.00 | 0.00 | 0.00 | 0.346992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.922945E+09 | 0.00 | 0.00 | 0.00 | 0.525345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.959960E+09 | 0.00 | 0.00 | 0.00 | 0.567690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.985057E+09 | 0.00 | 0.00 | 0.00 | 0.570621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.989271E+09 | 0.00 | 0.00 | 0.00 | 0.558128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.855508E+09 | 0.00 | 0.00 | 0.00 | 0.451589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819672E+09 | 0.00 | 0.00 | 0.00 | 0.314369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791405E+09 | 0.00 | 0.00 | 0.00 | 0.158260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813700E+09 | 0.00 | 0.00 | 0.00 | 0.291148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103418E+11 | 0.00 | 0.00 | 0.00 | 0.378832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740587E+09 | 0.00 | 0.00 | 0.00 | 0.104075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.989271E+09 | 0.00 | 0.00 | 0.00 | 0.570621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.935616E+09 | 0.00 | 0.00 | 0.00 | 0.115823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835014E+09 | 0.00 | 0.00 | 0.00 | 0.672637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.937280E+09 | 0.00 | 0.00 | 0.00 | 0.210741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.902094E+09 | 0.00 | 0.00 | 0.00 | 0.391438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104193E+10 | 0.00 | 0.00 | 0.00 | 0.595863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108213E+10 | 0.00 | 0.00 | 0.00 | 0.640396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111048E+10 | 0.00 | 0.00 | 0.00 | 0.643534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111163E+10 | 0.00 | 0.00 | 0.00 | 0.628936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.963544E+09 | 0.00 | 0.00 | 0.00 | 0.508361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922287E+09 | 0.00 | 0.00 | 0.00 | 0.355099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.890311E+09 | 0.00 | 0.00 | 0.00 | 0.174580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.917595E+09 | 0.00 | 0.00 | 0.00 | 0.321374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116499E+11 | 0.00 | 0.00 | 0.00 | 0.425993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.835014E+09 | 0.00 | 0.00 | 0.00 | 0.115823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111163E+10 | 0.00 | 0.00 | 0.00 | 0.643534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489106E+10 | 0.00 | 0.00 | 4485772.85 | 0.00 | 0.272122E+09 | 0.256199E+10 | 0.00 | 0.57 |
February | 0.181707E+10 | 0.150664E+09 | 0.00 | 8307907.79 | 0.00 | 16942872.22 | 0.209692E+10 | 0.00 | 0.57 |
March | 0.328895E+09 | 0.256844E+10 | 0.00 | 5681967.54 | 3737959.94 | 0.00 | 0.695528E+09 | 0.00 | 0.57 |
April | 4497331.29 | 0.806885E+10 | 0.00 | 470514.84 | 72467312.77 | 0.00 | 23565350.73 | 0.00 | 0.57 |
May | 0.00 | 0.159767E+11 | 0.00 | 101684.34 | 0.123799E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.205880E+11 | 0.00 | 0.00 | 0.138024E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.251239E+11 | 0.00 | 0.00 | 0.135458E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.250919E+11 | 0.00 | 0.00 | 0.153012E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.190642E+11 | 0.00 | 0.00 | 0.170356E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 32793397.82 | 0.716067E+10 | 0.00 | 1064024.47 | 54936713.41 | 0.00 | 0.104989E+09 | 0.00 | 0.57 |
November | 0.528539E+09 | 0.127397E+10 | 0.00 | 8356904.03 | 0.00 | 0.00 | 0.168637E+10 | 0.00 | 0.57 |
December | 0.331162E+10 | 5344886.08 | 0.00 | 8326981.14 | 0.00 | 30346651.63 | 0.358036E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.109145E+11 | 0.125073E+12 | 0.00 | 36795756.99 | 0.851790E+09 | 0.319411E+09 | 0.107497E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.489106E+10 | 0.251239E+11 | 0.00 | 8356904.03 | 0.170356E+09 | 0.272122E+09 | 0.358036E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123265E+10 | 0.00 | 0.00 | 3987821.40 | 0.00 | 64074667.73 | 0.136441E+10 | 0.00 | 0.43 |
February | 0.489963E+09 | 82526275.31 | 0.00 | 5299216.15 | 215796.67 | 0.00 | 0.678933E+09 | 0.00 | 0.44 |
March | 90658198.60 | 0.121322E+10 | 0.00 | 2922325.49 | 9990898.75 | 0.00 | 0.162346E+09 | 0.00 | 0.46 |
April | 957276.80 | 0.347176E+10 | 0.00 | 277620.35 | 49640291.57 | 0.00 | 4582136.40 | 0.00 | 0.47 |
May | 0.00 | 0.689210E+10 | 0.00 | 0.00 | 65371863.68 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.886627E+10 | 0.00 | 0.00 | 55374875.46 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.107786E+11 | 0.00 | 0.00 | 76511837.35 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.108574E+11 | 0.00 | 0.00 | 72870303.15 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.811489E+10 | 0.00 | 0.00 | 0.105190E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 1565826.23 | 0.321290E+10 | 0.00 | 171609.89 | 55055521.26 | 0.00 | 6005843.34 | 0.00 | 0.46 |
November | 0.127832E+09 | 0.662146E+09 | 0.00 | 4452178.78 | 2046449.05 | 0.00 | 0.342072E+09 | 0.00 | 0.45 |
December | 0.898864E+09 | 3098312.78 | 0.00 | 5933833.17 | 0.00 | 546229.09 | 0.125026E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.284249E+10 | 0.541549E+11 | 0.00 | 23044605.23 | 0.492267E+09 | 64620896.82 | 0.380861E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.123265E+10 | 0.108574E+11 | 0.00 | 5933833.17 | 0.105190E+09 | 64074667.73 | 0.136441E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176213E+10 | 18203.86 | 0.00 | 1904711.36 | 0.00 | 0.108394E+09 | 0.852949E+09 | 0.00 | 0.45 |
February | 0.832729E+09 | 83772510.22 | 0.00 | 2887650.30 | 351064.72 | 0.00 | 0.505689E+09 | 0.00 | 0.45 |
March | 0.204927E+09 | 0.105710E+10 | 0.00 | 1832154.29 | 56555644.75 | 0.00 | 0.202747E+09 | 0.00 | 0.46 |
April | 1646322.97 | 0.304602E+10 | 0.00 | 220726.53 | 0.214625E+09 | 0.00 | 7131990.49 | 0.00 | 0.46 |
May | 26563.76 | 0.597438E+10 | 0.00 | 137429.20 | 0.411298E+09 | 0.00 | 42809.61 | 0.00 | 0.47 |
June | 0.00 | 0.746602E+10 | 0.00 | 0.00 | 0.531831E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.887404E+10 | 0.00 | 0.00 | 0.601283E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.902359E+10 | 0.00 | 0.00 | 0.629616E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.668069E+10 | 0.00 | 24445.28 | 0.484888E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 11407312.57 | 0.271417E+10 | 0.00 | 747255.36 | 0.172861E+09 | 0.00 | 78073456.92 | 0.00 | 0.46 |
November | 0.372747E+09 | 0.621701E+09 | 0.00 | 2231097.74 | 10949468.27 | 0.00 | 0.338921E+09 | 0.00 | 0.46 |
December | 0.136495E+10 | 3439591.99 | 0.00 | 3374576.71 | 0.00 | 0.00 | 0.912171E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.455057E+10 | 0.455449E+11 | 0.00 | 13360046.75 | 0.311426E+10 | 0.108394E+09 | 0.289773E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 18203.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.176213E+10 | 0.902359E+10 | 0.00 | 3374576.71 | 0.629616E+09 | 0.108394E+09 | 0.912171E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179876E+10 | 11767.35 | 0.00 | 1698453.56 | 0.00 | 0.124650E+09 | 0.781187E+09 | 0.00 | 0.45 |
February | 0.858105E+09 | 82757854.58 | 0.00 | 2780175.80 | 347748.10 | 0.00 | 0.477718E+09 | 0.00 | 0.45 |
March | 0.209728E+09 | 0.105646E+10 | 0.00 | 1824169.69 | 56540707.52 | 0.00 | 0.197411E+09 | 0.00 | 0.46 |
April | 1642022.54 | 0.304890E+10 | 0.00 | 231304.20 | 0.215162E+09 | 0.00 | 7065090.98 | 0.00 | 0.46 |
May | 29797.79 | 0.599019E+10 | 0.00 | 144075.97 | 0.406525E+09 | 0.00 | 42753.02 | 0.00 | 0.47 |
June | 0.00 | 0.748408E+10 | 0.00 | 0.00 | 0.529643E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.889796E+10 | 0.00 | 0.00 | 0.601418E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.904367E+10 | 0.00 | 0.00 | 0.630082E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.670125E+10 | 0.00 | 28029.06 | 0.480484E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 11134565.71 | 0.271945E+10 | 0.00 | 758486.37 | 0.172886E+09 | 0.00 | 77995209.50 | 0.00 | 0.46 |
November | 0.378244E+09 | 0.620467E+09 | 0.00 | 2192617.00 | 10939071.19 | 0.00 | 0.333154E+09 | 0.00 | 0.46 |
December | 0.136872E+10 | 3343782.27 | 0.00 | 3194992.50 | 0.00 | 3809992.21 | 0.899891E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.462636E+10 | 0.456486E+11 | 0.00 | 12852304.15 | 0.310403E+10 | 0.128460E+09 | 0.277446E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 11767.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.179876E+10 | 0.904367E+10 | 0.00 | 3194992.50 | 0.630082E+09 | 0.124650E+09 | 0.899891E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183665E+10 | 5234.28 | 0.00 | 1382489.47 | 0.00 | 0.175207E+09 | 0.663833E+09 | 0.00 | 0.45 |
February | 0.875829E+09 | 80365776.15 | 0.00 | 2533525.30 | 330109.29 | 0.00 | 0.456904E+09 | 0.00 | 0.45 |
March | 0.222015E+09 | 0.104602E+10 | 0.00 | 1711887.57 | 56462943.32 | 0.00 | 0.187530E+09 | 0.00 | 0.46 |
April | 1664547.56 | 0.304060E+10 | 0.00 | 205269.82 | 0.214871E+09 | 0.00 | 7195631.30 | 0.00 | 0.46 |
May | 24932.73 | 0.597239E+10 | 0.00 | 132703.66 | 0.409068E+09 | 0.00 | 44526.23 | 0.00 | 0.47 |
June | 0.00 | 0.746305E+10 | 0.00 | 0.00 | 0.527691E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.886848E+10 | 0.00 | 0.00 | 0.601569E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.900578E+10 | 0.00 | 0.00 | 0.629866E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.665893E+10 | 0.00 | 25951.08 | 0.486070E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 12563607.13 | 0.270039E+10 | 0.00 | 715792.76 | 0.173164E+09 | 0.00 | 79252479.20 | 0.00 | 0.46 |
November | 0.397616E+09 | 0.612929E+09 | 0.00 | 2062972.36 | 10934638.41 | 0.00 | 0.316731E+09 | 0.00 | 0.46 |
December | 0.139723E+10 | 3191237.12 | 0.00 | 2834453.33 | 0.00 | 7559224.53 | 0.861760E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.474360E+10 | 0.454521E+11 | 0.00 | 11605045.35 | 0.311003E+10 | 0.182766E+09 | 0.257325E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 5234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.183665E+10 | 0.900578E+10 | 0.00 | 2834453.33 | 0.629866E+09 | 0.175207E+09 | 0.861760E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326642E+10 | 0.00 | 0.00 | 1915392.62 | 0.00 | 0.482907E+09 | 0.110297E+10 | 0.00 | 0.42 |
February | 0.133667E+10 | 95557895.67 | 0.00 | 4719217.98 | 218028.81 | 19909369.45 | 0.101499E+10 | 0.00 | 0.42 |
March | 0.284023E+09 | 0.196060E+10 | 0.00 | 3534165.07 | 41340228.04 | 0.00 | 0.321548E+09 | 0.00 | 0.43 |
April | 2146309.03 | 0.590437E+10 | 0.00 | 174058.74 | 0.198985E+09 | 0.00 | 6461924.29 | 0.00 | 0.42 |
May | 0.00 | 0.116542E+11 | 0.00 | 83349.32 | 0.281169E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.145858E+11 | 0.00 | 0.00 | 0.308876E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.170338E+11 | 0.00 | 0.00 | 0.447568E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.176392E+11 | 0.00 | 0.00 | 0.393679E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.128564E+11 | 0.00 | 47534.11 | 0.423028E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 24562220.63 | 0.524656E+10 | 0.00 | 633881.61 | 0.168155E+09 | 0.00 | 58957984.32 | 0.00 | 0.42 |
November | 0.442506E+09 | 0.102866E+10 | 0.00 | 3746666.02 | 16476290.20 | 0.00 | 0.631980E+09 | 0.00 | 0.42 |
December | 0.244591E+10 | 1472571.90 | 0.00 | 4245124.15 | 0.00 | 31530500.72 | 0.174837E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.780224E+10 | 0.880066E+11 | 0.00 | 19099389.62 | 0.227949E+10 | 0.534347E+09 | 0.488528E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.326642E+10 | 0.176392E+11 | 0.00 | 4719217.98 | 0.447568E+09 | 0.482907E+09 | 0.174837E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162381E+10 | 0.00 | 0.00 | 862589.69 | 0.00 | 0.276755E+09 | 0.499958E+09 | 0.00 | 0.42 |
February | 0.673113E+09 | 48669091.54 | 0.00 | 2290794.10 | 108702.44 | 18047948.26 | 0.486114E+09 | 0.00 | 0.42 |
March | 0.145117E+09 | 0.982242E+09 | 0.00 | 1759221.01 | 20392298.99 | 0.00 | 0.155435E+09 | 0.00 | 0.43 |
April | 1054483.89 | 0.296210E+10 | 0.00 | 85999.88 | 98540708.28 | 0.00 | 3222561.67 | 0.00 | 0.42 |
May | 0.00 | 0.584160E+10 | 0.00 | 36441.94 | 0.131550E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.729982E+10 | 0.00 | 0.00 | 0.141601E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.849584E+10 | 0.00 | 0.00 | 0.220482E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.878635E+10 | 0.00 | 0.00 | 0.194049E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.640636E+10 | 0.00 | 41685.58 | 0.208879E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 12139192.15 | 0.261955E+10 | 0.00 | 311390.68 | 82702694.24 | 0.00 | 30196351.01 | 0.00 | 0.42 |
November | 0.224148E+09 | 0.515005E+09 | 0.00 | 1891771.91 | 8094597.55 | 0.00 | 0.311188E+09 | 0.00 | 0.42 |
December | 0.123855E+10 | 791082.41 | 0.00 | 2034664.98 | 0.00 | 20371200.11 | 0.841362E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.391794E+10 | 0.439583E+11 | 0.00 | 9314559.77 | 0.110640E+10 | 0.315175E+09 | 0.232748E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.162381E+10 | 0.878635E+10 | 0.00 | 2290794.10 | 0.220482E+09 | 0.276755E+09 | 0.841362E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161360E+10 | 0.00 | 0.00 | 806297.55 | 0.00 | 0.300529E+09 | 0.477089E+09 | 0.00 | 0.42 |
February | 0.667298E+09 | 48201152.31 | 0.00 | 2232271.29 | 109649.63 | 28663167.40 | 0.480134E+09 | 0.00 | 0.42 |
March | 0.146081E+09 | 0.978914E+09 | 0.00 | 1733155.92 | 20429367.67 | 0.00 | 0.154858E+09 | 0.00 | 0.43 |
April | 1054747.02 | 0.295844E+10 | 0.00 | 84026.77 | 99627479.07 | 0.00 | 3246897.54 | 0.00 | 0.42 |
May | 0.00 | 0.583724E+10 | 0.00 | 36073.32 | 0.131497E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.729389E+10 | 0.00 | 0.00 | 0.141284E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.848776E+10 | 0.00 | 0.00 | 0.220947E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.877781E+10 | 0.00 | 0.00 | 0.193452E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.639814E+10 | 0.00 | 42123.65 | 0.208643E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 12958617.98 | 0.261404E+10 | 0.00 | 309764.24 | 83038146.11 | 0.00 | 29809390.45 | 0.00 | 0.42 |
November | 0.225325E+09 | 0.512666E+09 | 0.00 | 1852363.32 | 8105870.98 | 0.00 | 0.311303E+09 | 0.00 | 0.42 |
December | 0.126351E+10 | 759900.01 | 0.00 | 1938783.58 | 0.00 | 21540311.10 | 0.811105E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.392983E+10 | 0.439079E+11 | 0.00 | 9034859.64 | 0.110713E+10 | 0.350732E+09 | 0.226754E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.161360E+10 | 0.877781E+10 | 0.00 | 2232271.29 | 0.220947E+09 | 0.300529E+09 | 0.811105E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157655E+10 | 0.00 | 0.00 | 685922.77 | 0.00 | 0.360714E+09 | 0.431048E+09 | 0.00 | 0.42 |
February | 0.667150E+09 | 47125436.89 | 0.00 | 2073698.89 | 111726.26 | 47227126.03 | 0.455339E+09 | 0.00 | 0.42 |
March | 0.152451E+09 | 0.971370E+09 | 0.00 | 1658932.83 | 20908601.29 | 0.00 | 0.147750E+09 | 0.00 | 0.43 |
April | 1199760.93 | 0.295516E+10 | 0.00 | 81576.38 | 0.101079E+09 | 0.00 | 3177464.98 | 0.00 | 0.42 |
May | 0.00 | 0.584536E+10 | 0.00 | 35577.37 | 0.127741E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.730788E+10 | 0.00 | 0.00 | 0.137686E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.851810E+10 | 0.00 | 0.00 | 0.212654E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.880790E+10 | 0.00 | 0.00 | 0.188562E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.641313E+10 | 0.00 | 42245.79 | 0.207186E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 13063229.33 | 0.261375E+10 | 0.00 | 295018.64 | 82319336.66 | 0.00 | 30408226.62 | 0.00 | 0.42 |
November | 0.234148E+09 | 0.508024E+09 | 0.00 | 1761850.26 | 8124363.79 | 0.00 | 0.303526E+09 | 0.00 | 0.42 |
December | 0.131481E+10 | 689617.19 | 0.00 | 1719785.24 | 0.00 | 37240939.08 | 0.729801E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.395937E+10 | 0.439885E+11 | 0.00 | 8354608.15 | 0.108637E+10 | 0.445182E+09 | 0.210105E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.157655E+10 | 0.880790E+10 | 0.00 | 2073698.89 | 0.212654E+09 | 0.360714E+09 | 0.729801E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144464E+10 | 0.00 | 0.00 | 713479.51 | 0.00 | 0.479812E+09 | 0.429023E+09 | 0.00 | 0.42 |
February | 0.585981E+09 | 46144435.61 | 0.00 | 2236401.00 | 101813.85 | 0.108416E+09 | 0.450069E+09 | 0.00 | 0.42 |
March | 0.149766E+09 | 0.962274E+09 | 0.00 | 1777561.82 | 20814784.60 | 0.00 | 0.144311E+09 | 0.00 | 0.43 |
April | 1871654.41 | 0.296536E+10 | 0.00 | 89341.97 | 90485246.87 | 0.00 | 2964822.64 | 0.00 | 0.42 |
May | 0.00 | 0.591448E+10 | 0.00 | 40591.75 | 0.103856E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.743599E+10 | 0.00 | 29874.75 | 0.118580E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.874012E+10 | 0.00 | 0.00 | 0.180643E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.909777E+10 | 0.00 | 0.00 | 0.159051E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.662966E+10 | 0.00 | 67924.41 | 0.189842E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 17279613.57 | 0.266975E+10 | 0.00 | 270719.68 | 76561008.17 | 0.00 | 25975158.84 | 0.00 | 0.42 |
November | 0.234568E+09 | 0.507373E+09 | 0.00 | 1887444.92 | 7644555.99 | 0.00 | 0.293036E+09 | 0.00 | 0.42 |
December | 0.121296E+10 | 594927.62 | 0.00 | 1808411.19 | 0.00 | 0.143535E+09 | 0.690301E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.364707E+10 | 0.449695E+11 | 0.00 | 8921751.00 | 0.947580E+09 | 0.731763E+09 | 0.203568E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.144464E+10 | 0.909777E+10 | 0.00 | 2236401.00 | 0.189842E+09 | 0.479812E+09 | 0.690301E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149297E+12 | 0.145492E+11 | 0.00 | 0.810623E+11 | 0.126104E+11 |
February | 0.175235E+12 | 0.538401E+10 | 0.00 | 0.464894E+11 | 0.460454E+11 |
March | 0.246787E+12 | -0.789566E+10 | 0.00 | 0.300446E+10 | 0.124212E+12 |
April | 0.284647E+12 | -0.229529E+11 | 0.00 | -0.558306E+11 | 0.207540E+12 |
May | 0.307770E+12 | -0.419408E+11 | 0.00 | -0.114656E+12 | 0.307750E+12 |
June | 0.287413E+12 | -0.497039E+11 | 0.00 | -0.152905E+12 | 0.343776E+12 |
July | 0.235704E+12 | -0.611770E+11 | 0.00 | -0.180666E+12 | 0.375040E+12 |
August | 0.200548E+12 | -0.621263E+11 | 0.00 | -0.178802E+12 | 0.374143E+12 |
September | 0.209717E+12 | -0.471084E+11 | 0.00 | -0.134871E+12 | 0.302995E+12 |
October | 0.202770E+12 | -0.213497E+11 | 0.00 | -0.407638E+11 | 0.200116E+12 |
November | 0.168143E+12 | -0.410404E+10 | 0.00 | 0.285065E+11 | 0.103943E+12 |
December | 0.133116E+12 | 0.121775E+11 | 0.00 | 0.777956E+11 | 0.259780E+11 |
Annual Sum or Average | 0.260115E+13 | -0.286248E+12 | 0.00 | -0.621637E+12 | 0.242415E+13 |
Minimum of Months | 0.133116E+12 | -0.621263E+11 | 0.00 | -0.180666E+12 | 0.126104E+11 |
Maximum of Months | 0.307770E+12 | 0.145492E+11 | 0.00 | 0.810623E+11 | 0.375040E+12 |