Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:36:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1519.06 | 726.71 | 726.71 |
Net Site Energy | 1519.06 | 726.71 | 726.71 |
Total Source Energy | 3375.69 | 1614.92 | 1614.92 |
Net Source Energy | 3375.69 | 1614.92 | 1614.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 688.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 830.07 | 688.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 688.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 67.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 100.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 688.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 67.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 100.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.66 | 329.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.10 | 329.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.66 | 329.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.10 | 329.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 830.069 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 830.069 | 100.00 |
Total On-Site and Utility Electric Sources | 830.069 | 100.00 |
Total Electricity End Uses | 830.069 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2548.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-13:39 | 07-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 246829.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36306.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6276.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8316.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85220.10 | 246829.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 246829.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36306.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6276.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 8316.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 746.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 319.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2628.83 | 746.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 357.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 102.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1257.62 | 357.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 357.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 102.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1257.62 | 357.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.92 |
SMSTORE1 DIRECT AIR | 1.03 |
SMSTORE2 DIRECT AIR | 1.04 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.03 |
LGSTORE2 DIRECT AIR | 1.84 |
SMSTORE5 DIRECT AIR | 0.954580 |
SMSTORE6 DIRECT AIR | 0.948520 |
SMSTORE7 DIRECT AIR | 0.939195 |
SMSTORE8 DIRECT AIR | 0.980668 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.00 | 1.00 | 1.92 |
PSZ-AC_2:2 | 1.03 | 1.03 | 1.03 | 1.03 | 1.04 | 1.04 | 1.00 | 0.988440 | 1.04 |
PSZ-AC_3:3 | 1.04 | 1.04 | 1.04 | 1.04 | 1.05 | 1.05 | 1.00 | 0.988558 | 1.05 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.05 | 1.05 | 1.00 | 0.979474 | 1.05 |
PSZ-AC_5:5 | 1.03 | 1.03 | 1.03 | 1.03 | 1.04 | 1.04 | 1.00 | 0.987064 | 1.04 |
PSZ-AC_6:6 | 1.84 | 1.84 | 1.84 | 1.84 | 1.84 | 1.84 | 1.00 | 1.00 | 1.84 |
PSZ-AC_7:7 | 0.954580 | 0.954580 | 0.954580 | 0.954580 | 0.958524 | 0.958524 | 1.00 | 0.995886 | 0.958524 |
PSZ-AC_8:8 | 0.948520 | 0.948520 | 0.948520 | 0.948520 | 0.952904 | 0.952904 | 1.00 | 0.995399 | 0.952904 |
PSZ-AC_9:9 | 0.939195 | 0.939195 | 0.939195 | 0.939195 | 0.944854 | 0.944854 | 1.00 | 0.994010 | 0.944854 |
PSZ-AC_10:10 | 0.980668 | 0.980668 | 0.980668 | 0.980668 | 0.998219 | 0.998219 | 1.00 | 0.982418 | 0.998219 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.92 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.84 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.958524 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.952904 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.944854 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.998219 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.92 | 2058.30 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.46 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1162.23 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1166.47 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.76 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.84 | 1967.30 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.958524 | 1061.24 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.952904 | 1055.02 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.944854 | 1046.10 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.998219 | 1105.19 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.92 | 1.92 | 1.92 | 1.27 | 41155.01 | 61030.26 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.688792 | 21914.04 | 32070.03 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.692830 | 22016.05 | 32207.57 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.695356 | 22078.30 | 32078.57 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.688974 | 21922.80 | 32044.05 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.84 | 1.84 | 1.84 | 1.21 | 39626.29 | 59133.55 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.958524 | 0.958524 | 0.958524 | 0.632626 | 20594.32 | 30354.22 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.952904 | 0.952904 | 0.952904 | 0.628916 | 20505.83 | 30219.14 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.944854 | 0.944854 | 0.944854 | 0.623604 | 20359.84 | 30011.30 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.998219 | 0.998219 | 0.998219 | 0.658824 | 21179.10 | 30936.81 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.92 | 0.961781 | 1.28 | 41155.01 | 20577.51 | 0.750460 | 0.750460 |
PSZ-AC_2:2 COOLING COIL | 1.04 | 0.521812 | 0.695747 | 21914.04 | 10957.02 | 0.757840 | 0.757840 |
PSZ-AC_3:3 COOLING COIL | 1.05 | 0.524871 | 0.699827 | 22016.05 | 11008.02 | 0.758190 | 0.758190 |
PSZ-AC_4:4 COOLING COIL | 1.05 | 0.526785 | 0.702380 | 22078.30 | 11039.15 | 0.758420 | 0.758420 |
PSZ-AC_5:5 COOLING COIL | 1.04 | 0.521950 | 0.695933 | 21922.80 | 10961.40 | 0.757800 | 0.757800 |
PSZ-AC_6:6 COOLING COIL | 1.84 | 0.919259 | 1.23 | 39626.29 | 19813.15 | 0.748370 | 0.748370 |
PSZ-AC_7:7 COOLING COIL | 0.958520 | 0.479262 | 0.639013 | 20594.32 | 10297.16 | 0.749260 | 0.749260 |
PSZ-AC_8:8 COOLING COIL | 0.952900 | 0.476452 | 0.635267 | 20505.83 | 10252.92 | 0.748820 | 0.748820 |
PSZ-AC_9:9 COOLING COIL | 0.944850 | 0.472427 | 0.629900 | 20359.84 | 10179.92 | 0.748440 | 0.748440 |
PSZ-AC_10:10 COOLING COIL | 0.998220 | 0.499109 | 0.665480 | 21179.10 | 10589.55 | 0.753850 | 0.753850 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61030.26 |
PSZ-AC_2:2 HEATING COIL | 32070.03 |
PSZ-AC_3:3 HEATING COIL | 32207.57 |
PSZ-AC_4:4 HEATING COIL | 32078.57 |
PSZ-AC_5:5 HEATING COIL | 32044.05 |
PSZ-AC_6:6 HEATING COIL | 59133.55 |
PSZ-AC_7:7 HEATING COIL | 30354.22 |
PSZ-AC_8:8 HEATING COIL | 30219.14 |
PSZ-AC_9:9 HEATING COIL | 30011.30 |
PSZ-AC_10:10 HEATING COIL | 30936.81 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21290.68738 | 25548.82486 | 1.60297 | 1.92356 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 27863.31663 | 33435.97995 | 1.23189 | 1.47827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11749.83360 | 14099.80032 | 0.85963 | 1.03156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 13143.90280 | 15772.68336 | 0.58113 | 0.69736 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11817.92702 | 14181.51242 | 0.86478 | 1.03773 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 13289.22524 | 15947.07028 | 0.58755 | 0.70507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11754.00367 | 14104.80441 | 0.85995 | 1.03194 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 13367.65634 | 16041.18760 | 0.59102 | 0.70923 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11736.55808 | 14083.86970 | 0.85866 | 1.03040 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 13510.50566 | 16212.60680 | 0.59734 | 0.71681 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20350.13967 | 24420.16760 | 1.53210 | 1.83852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 25871.16329 | 31045.39594 | 1.14386 | 1.37263 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10893.56398 | 13072.27678 | 0.79548 | 0.95458 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 13841.07732 | 16609.29279 | 0.61196 | 0.73435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10826.22526 | 12991.47031 | 0.79043 | 0.94852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 13828.58591 | 16594.30309 | 0.61140 | 0.73368 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10722.70586 | 12867.24703 | 0.78266 | 0.93919 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 14039.54895 | 16847.45874 | 0.62073 | 0.74488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11182.02868 | 13418.43442 | 0.81722 | 0.98067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 17238.30557 | 20685.96669 | 0.76211 | 0.91453 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28267.36 | 1.92356 | 1.92356 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 51105.14 | 1.47827 | 1.47827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15191.95 | 1.04362 | 1.04362 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 24621.14 | 0.69736 | 0.69736 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15262.09 | 1.04974 | 1.04974 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 24792.98 | 0.70507 | 0.70507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15309.93 | 1.05357 | 1.05357 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 24885.73 | 0.70923 | 0.70923 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15184.17 | 1.04390 | 1.04390 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 25054.66 | 0.71681 | 0.71681 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27110.42 | 1.83852 | 1.83852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 48749.72 | 1.37263 | 1.37263 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13943.26 | 0.95852 | 0.95852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 25445.57 | 0.73435 | 0.73435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13863.33 | 0.95290 | 0.95290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 25430.80 | 0.73368 | 0.73368 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13795.93 | 0.94485 | 0.94485 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 25680.27 | 0.74488 | 0.74488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14497.99 | 0.99822 | 0.99822 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 29462.56 | 0.91453 | 0.91453 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.92356 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03156 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03773 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03194 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03040 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.83852 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95458 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94852 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93919 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98067 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.92356 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.92356 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.92356 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92356 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.92356 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.92356 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03156 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03156 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03156 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03156 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04362 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04362 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98844 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03773 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03773 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03773 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03773 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04974 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04974 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98856 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03194 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03194 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03194 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03194 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05357 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05357 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97947 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03040 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03040 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03040 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03040 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04390 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04390 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98706 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.83852 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.83852 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.83852 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.83852 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.83852 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.83852 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95458 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95458 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95458 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95458 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95852 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95852 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99589 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94852 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94852 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94852 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94852 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95290 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95290 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99540 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93919 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93919 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93919 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93919 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94485 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94485 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99401 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98067 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98067 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98067 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98067 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99822 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99822 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98242 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.92356 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.04362 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04974 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.05357 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.04390 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.83852 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.95852 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.95290 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.94485 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.99822 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.92356 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.92356 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2058.30257 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.92356 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.92356 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.92356 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26955 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.92356 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96178 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28237 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41155.01000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20577.50500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75046 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75046 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41155.01000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61030.26097 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61030.26097 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04362 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04362 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.45804 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04362 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04362 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04362 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68879 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04362 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52181 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69575 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21914.04000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10957.02000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75784 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75784 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21914.04000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32070.02757 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32070.02757 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04974 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04974 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1162.23187 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04974 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04974 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04974 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69283 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04974 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52487 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69983 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22016.05000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11008.02500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75819 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75819 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22016.05000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32207.57320 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 32207.57320 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05357 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05357 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1166.46892 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05357 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05357 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05357 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69536 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05357 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52678 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70238 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22078.30000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11039.15000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75842 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75842 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22078.30000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32078.56759 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32078.56759 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04390 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04390 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.76271 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04390 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04390 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04390 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68897 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04390 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52195 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69593 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21922.80000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10961.40000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75780 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75780 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21922.80000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32044.04993 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 32044.04993 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.83852 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.83852 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1967.30200 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.83852 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.83852 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.83852 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21342 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.83852 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91926 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22568 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39626.29000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19813.14500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74837 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74837 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39626.29000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59133.54736 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 59133.54736 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95852 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95852 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1061.23782 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95852 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95852 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95852 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.63263 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95852 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47926 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63901 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20594.32000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10297.16000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74926 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74926 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20594.32000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30354.22158 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30354.22158 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95290 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95290 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1055.01570 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95290 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95290 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95290 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62892 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95290 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47645 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63527 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20505.83000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10252.91500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74882 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74882 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20505.83000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30219.14421 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 30219.14421 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94485 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94485 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1046.10365 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94485 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94485 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94485 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62360 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94485 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47243 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62990 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20359.84000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10179.92000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74844 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74844 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20359.84000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30011.29846 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 30011.29846 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99822 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99822 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1105.18641 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99822 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99822 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99822 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65882 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99822 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49911 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66548 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21179.10000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10589.55000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75385 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75385 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21179.10000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30936.81138 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30936.81138 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 39641.6 | 11.50 | 11.50 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21093.2 | 11.63 | 11.63 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21190.4 | 11.63 | 11.63 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21249.7 | 11.63 | 11.63 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21101.8 | 11.63 | 11.63 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 38179.6 | 11.51 | 11.51 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19840.1 | 11.68 | 11.68 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19756.1 | 11.68 | 11.68 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 19616.4 | 11.68 | 11.68 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 20393.9 | 11.65 | 11.65 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.38 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.3141434092E-002 | 0.2349039050 | Pass | Pass | 0.6628141488 | 5.4266599629 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.7155819039E-002 | 0.1714548205 | Pass | Pass | 0.1127439530 | 0.5065411739 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.5180290987E-002 | 0.2374609379 | Pass | Pass | 9.4877035593E-002 | 0.6781429578 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.1254484145E-002 | 0.2724668887 | Pass | Pass | 9.9292579109E-002 | 0.7769289490 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.5712926545E-002 | 0.2999135942 | Pass | Pass | 8.3880441525E-002 | 0.6300977213 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.7488109926E-002 | 0.3442756257 | Pass | Pass | 2.8107556099E-002 | 9.6688366842E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.6849261330E-002 | 0.3429800943 | Pass | Pass | 2.6592724694E-002 | 8.6835147297E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.7950787744E-002 | 0.3483498843 | Pass | Pass | 2.6470999753E-002 | 8.6695501824E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.3039196467E-002 | 0.3769837341 | Pass | Pass | 2.5679028398E-002 | 8.5564178664E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1108279026 | 0.4324798156 | Pass | Pass | 0.3919935758 | 3.1109207977 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3978.45 | 262.78 | 0.00 | 589.22 | 478.96 | 5309.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.381 | 0.420 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.38 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.381 | 0.420 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.153 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.04 | 42.04 | 3.60 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.67 | 62.85 | 32.38 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.67 | 55.85 | 24.19 | |
Exterior Lighting Total | 5507.06 | 60.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41155.01 | 30885.19 | 10269.82 | 0.75 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21914.04 | 16607.34 | 5306.70 | 0.76 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22016.05 | 16692.35 | 5323.70 | 0.76 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22078.30 | 16744.62 | 5333.68 | 0.76 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21922.80 | 16613.10 | 5309.70 | 0.76 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39626.29 | 29655.13 | 9971.16 | 0.75 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20594.32 | 15430.50 | 5163.82 | 0.75 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20505.83 | 15355.18 | 5150.65 | 0.75 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20359.84 | 15238.12 | 5121.72 | 0.75 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21179.10 | 15965.86 | 5213.24 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 39641.6 | 11.50 | 11.50 | ||||
PSZ-AC_2:2 COOLING COIL | 21093.2 | 11.63 | 11.63 | ||||
PSZ-AC_3:3 COOLING COIL | 21190.4 | 11.63 | 11.63 | ||||
PSZ-AC_4:4 COOLING COIL | 21249.7 | 11.63 | 11.63 | ||||
PSZ-AC_5:5 COOLING COIL | 21101.8 | 11.63 | 11.63 | ||||
PSZ-AC_6:6 COOLING COIL | 38179.6 | 11.51 | 11.51 | ||||
PSZ-AC_7:7 COOLING COIL | 19840.1 | 11.68 | 11.68 | ||||
PSZ-AC_8:8 COOLING COIL | 19756.1 | 11.68 | 11.68 | ||||
PSZ-AC_9:9 COOLING COIL | 19616.4 | 11.68 | 11.68 | ||||
PSZ-AC_10:10 COOLING COIL | 20393.9 | 11.65 | 11.65 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61030.26 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32070.03 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 32207.57 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32078.57 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 32044.05 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 59133.55 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30354.22 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 30219.14 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 30011.30 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30936.81 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.92 | 2058.30 | 1070.05 | 1.00 | 1.32 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.46 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1162.23 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1166.47 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.76 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.84 | 1967.30 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1061.24 | 1107.16 | 1.00 | 1.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1055.02 | 1107.16 | 1.00 | 1.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1046.10 | 1107.16 | 1.00 | 1.42 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1105.19 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21290.69 | 25548.82 | 73.33 | 1.603 | 1.924 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00973 | 30.30 | 0.01337 | 0.411 | 0.00 |
SMSTORE1 | 11749.83 | 14099.80 | 80.94 | 0.860 | 1.032 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00936 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE2 | 11817.93 | 14181.51 | 81.41 | 0.865 | 1.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00951 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE3 | 11754.00 | 14104.80 | 80.97 | 0.860 | 1.032 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00950 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE4 | 11736.56 | 14083.87 | 80.85 | 0.859 | 1.030 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00953 | 25.18 | 0.01336 | 0.206 | 0.00 |
LGSTORE2 | 20350.14 | 24420.17 | 70.10 | 1.532 | 1.839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00972 | 30.07 | 0.01337 | 0.411 | 0.00 |
SMSTORE5 | 10893.56 | 13072.28 | 75.04 | 0.795 | 0.955 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00957 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE6 | 10826.23 | 12991.47 | 74.58 | 0.790 | 0.949 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00959 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE7 | 10722.71 | 12867.25 | 73.87 | 0.783 | 0.939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00962 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE8 | 11182.03 | 13418.43 | 77.03 | 0.817 | 0.981 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00963 | 26.77 | 0.01336 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 27863.32 | 33435.98 | 95.97 | 1.232 | 1.478 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE1 | 13143.90 | 15772.68 | 90.55 | 0.581 | 0.697 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE2 | 13289.23 | 15947.07 | 91.55 | 0.588 | 0.705 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE3 | 13367.66 | 16041.19 | 92.09 | 0.591 | 0.709 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE4 | 13510.51 | 16212.61 | 93.07 | 0.597 | 0.717 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -16.30 | 0.00092 | 0.206 | 0.00 |
LGSTORE2 | 25871.16 | 31045.40 | 89.11 | 1.144 | 1.373 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE5 | 13841.08 | 16609.29 | 95.35 | 0.612 | 0.734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE6 | 13828.59 | 16594.30 | 95.26 | 0.611 | 0.734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE7 | 14039.55 | 16847.46 | 96.72 | 0.621 | 0.745 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE8 | 17238.31 | 20685.97 | 118.75 | 0.762 | 0.915 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -16.30 | 0.00092 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.92 | 1.92 | 1.48 | 1.48 | 1.9236 | 1.9236 | 1.9236 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.04 | 1.04 | 0.70 | 0.70 | 1.0436 | 1.0316 | 1.0436 | 0.9884 | 1.0000 |
PSZ-AC_3:3 | 1.05 | 1.05 | 0.71 | 0.71 | 1.0497 | 1.0377 | 1.0497 | 0.9886 | 1.0000 |
PSZ-AC_4:4 | 1.05 | 1.05 | 0.71 | 0.71 | 1.0536 | 1.0319 | 1.0536 | 0.9795 | 1.0000 |
PSZ-AC_5:5 | 1.04 | 1.04 | 0.72 | 0.72 | 1.0439 | 1.0304 | 1.0439 | 0.9871 | 1.0000 |
PSZ-AC_6:6 | 1.84 | 1.84 | 1.37 | 1.37 | 1.8385 | 1.8385 | 1.8385 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.96 | 0.96 | 0.73 | 0.73 | 0.9585 | 0.9546 | 0.9585 | 0.9959 | 1.0000 |
PSZ-AC_8:8 | 0.95 | 0.95 | 0.73 | 0.73 | 0.9529 | 0.9485 | 0.9529 | 0.9954 | 1.0000 |
PSZ-AC_9:9 | 0.94 | 0.94 | 0.74 | 0.74 | 0.9449 | 0.9392 | 0.9449 | 0.9940 | 1.0000 |
PSZ-AC_10:10 | 1.00 | 1.00 | 0.91 | 0.91 | 0.9982 | 0.9807 | 0.9982 | 0.9824 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 41155.010 | 30885.189 | 1.923560 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 20577.51 | 15407.11 | 1.282373 | 26.15 | 18.49 | 0.01050611 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 32.0873 | 23.89 | 0.00972760 | 51.3023 | 21290.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61030.261 | 61030.261 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61030.26 | 61030.26 | 1.923562 | 13.10 | 8.68 | 0.00534695 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.3915 | 21.10 | 0.00655053 | 41.1172 | 27863.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 21914.040 | 16607.336 | 1.043620 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10957.02 | 8320.90 | 0.695747 | 26.07 | 18.37 | 0.01038441 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.5710 | 23.89 | 0.00965125 | 50.9054 | 11541.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32070.028 | 32070.028 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32070.03 | 32070.03 | 1.043625 | 13.73 | 9.01 | 0.00538223 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.7139 | 21.10 | 0.00647691 | 40.6592 | 13143.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22016.050 | 16692.349 | 1.049740 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11008.02 | 8367.10 | 0.699827 | 26.07 | 18.36 | 0.01037662 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.3986 | 23.89 | 0.00964622 | 50.8793 | 11600.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32207.573 | 32207.573 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32207.57 | 32207.57 | 1.049743 | 13.77 | 9.04 | 0.00539800 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.5990 | 21.10 | 0.00648858 | 40.7318 | 13289.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22078.300 | 16744.624 | 1.053570 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11039.15 | 8395.85 | 0.702380 | 26.06 | 18.36 | 0.01037133 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.2918 | 23.89 | 0.00964280 | 50.8615 | 11640.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32078.568 | 32078.568 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32078.57 | 32078.57 | 1.053570 | 13.80 | 9.06 | 0.00540689 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.5278 | 21.10 | 0.00649471 | 40.7698 | 13367.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 21922.800 | 16613.098 | 1.043900 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10961.40 | 8323.38 | 0.695933 | 26.07 | 18.37 | 0.01038530 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.5631 | 23.89 | 0.00965183 | 50.9084 | 11534.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32044.050 | 32044.050 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32044.05 | 32044.05 | 1.043900 | 13.73 | 9.03 | 0.00540581 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.7087 | 21.10 | 0.00650592 | 40.8395 | 13510.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 39626.290 | 29655.127 | 1.838520 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19813.15 | 14777.91 | 1.225680 | 26.21 | 18.54 | 0.01054579 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 33.5715 | 23.89 | 0.00973035 | 51.3160 | 20311.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 59133.547 | 59133.547 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59133.55 | 59133.55 | 1.838519 | 12.73 | 8.48 | 0.00531485 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.3810 | 21.10 | 0.00658090 | 41.3042 | 25871.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 20594.320 | 15430.500 | 0.958520 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10297.16 | 7688.76 | 0.639013 | 26.20 | 18.53 | 0.01053500 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 32.1964 | 23.89 | 0.00974920 | 51.4140 | 10484.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30354.222 | 30354.222 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30354.22 | 30354.22 | 0.958524 | 13.08 | 8.65 | 0.00532767 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.4642 | 21.10 | 0.00653119 | 40.9965 | 13841.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 20505.830 | 15355.176 | 0.952900 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10252.92 | 7646.94 | 0.635267 | 26.21 | 18.54 | 0.01054545 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 32.3863 | 23.89 | 0.00975604 | 51.4495 | 10416.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30219.144 | 30219.144 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30219.14 | 30219.14 | 0.952904 | 13.03 | 8.62 | 0.00531986 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.5908 | 21.10 | 0.00653028 | 40.9908 | 13828.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 20359.840 | 15238.119 | 0.944850 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10179.92 | 7585.11 | 0.629900 | 26.22 | 18.55 | 0.01055434 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 32.6622 | 23.89 | 0.00976186 | 51.4797 | 10359.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30011.298 | 30011.298 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30011.30 | 30011.30 | 0.944854 | 12.96 | 8.59 | 0.00532164 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.7747 | 21.10 | 0.00654574 | 41.0869 | 14039.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 21179.100 | 15965.865 | 0.998220 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 10589.55 | 7908.09 | 0.665480 | 26.03 | 18.46 | 0.01051162 | 12.80 | 11.87 | 0.00850000 | 29.84 | 0.01336614 | 21.70 | 30.9159 | 23.89 | 0.00977055 | 51.5254 | 11031.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30936.811 | 30936.811 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30936.81 | 30936.81 | 0.998219 | 13.40 | 8.89 | 0.00541621 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.6107 | 21.10 | 0.00658244 | 41.3179 | 17238.31 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41155.010 | 30885.189 | 1.923560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3703 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.923562 | 2.25811845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 20577.51 | 15407.11 | 1.0000 | 1.50541052 | 1.282373 | 26.15 | 18.49 | 0.01050611 | 53059.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20577.51 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 32.0873 | 23.89 | 0.00972760 | 23.89 | 0.00972760 | 51.3023 | 21290.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61030.261 | 61030.261 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.923562 | 2.25811845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 61030.26 | 61030.26 | 1.0000 | 2.25811845 | 1.923562 | 13.10 | 8.68 | 0.00534695 | 26669.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61030.26 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 21.3915 | 21.11 | 0.00655053 | 21.10 | 0.00655053 | 41.1172 | 27863.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21914.040 | 16607.336 | 1.043620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1441 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043625 | 1.22513728 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10957.02 | 8320.90 | 1.0000 | 0.81675462 | 0.695747 | 26.07 | 18.37 | 0.01038441 | 52672.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10957.02 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.5710 | 23.89 | 0.00965125 | 23.89 | 0.00965125 | 50.9054 | 11541.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32070.028 | 32070.028 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043625 | 1.22513728 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32070.03 | 32070.03 | 1.0000 | 1.22513728 | 1.043625 | 13.73 | 9.01 | 0.00538223 | 27396.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32070.03 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.7139 | 21.11 | 0.00647691 | 21.10 | 0.00647691 | 40.6592 | 13143.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22016.050 | 16692.349 | 1.049740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1296 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.049743 | 1.23231960 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11008.02 | 8367.10 | 1.0000 | 0.82154424 | 0.699827 | 26.07 | 18.36 | 0.01037662 | 52645.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11008.02 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.3986 | 23.89 | 0.00964622 | 23.89 | 0.00964622 | 50.8793 | 11600.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32207.573 | 32207.573 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.049743 | 1.23231960 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32207.57 | 32207.57 | 1.0000 | 1.23231960 | 1.049743 | 13.77 | 9.04 | 0.00539800 | 27479.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32207.57 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.5990 | 21.11 | 0.00648858 | 21.10 | 0.00648858 | 40.7318 | 13289.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22078.300 | 16744.624 | 1.053570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1198 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053570 | 1.23681216 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11039.15 | 8395.85 | 1.0000 | 0.82454166 | 0.702380 | 26.06 | 18.36 | 0.01037133 | 52627.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11039.15 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.2918 | 23.89 | 0.00964280 | 23.89 | 0.00964280 | 50.8615 | 11640.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32078.568 | 32078.568 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053570 | 1.23681216 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32078.57 | 32078.57 | 1.0000 | 1.23681216 | 1.053570 | 13.80 | 9.06 | 0.00540689 | 27528.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32078.57 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.5278 | 21.11 | 0.00649471 | 21.10 | 0.00649471 | 40.7698 | 13367.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21922.800 | 16613.098 | 1.043900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1458 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043900 | 1.22546032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10961.40 | 8323.38 | 1.0000 | 0.81697376 | 0.695933 | 26.07 | 18.37 | 0.01038530 | 52675.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10961.40 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.5631 | 23.89 | 0.00965183 | 23.89 | 0.00965183 | 50.9084 | 11534.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32044.050 | 32044.050 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043900 | 1.22546032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32044.05 | 32044.05 | 1.0000 | 1.22546032 | 1.043900 | 13.73 | 9.03 | 0.00540581 | 27457.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32044.05 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.7087 | 21.11 | 0.00650592 | 21.10 | 0.00650592 | 40.8395 | 13510.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39626.290 | 29655.127 | 1.838520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4441 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.838519 | 2.15828373 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 19813.15 | 14777.91 | 1.0000 | 1.43885678 | 1.225680 | 26.21 | 18.54 | 0.01054579 | 53228.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19813.15 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 33.5715 | 23.89 | 0.00973035 | 23.89 | 0.00973035 | 51.3160 | 20311.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59133.547 | 59133.547 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.838519 | 2.15828373 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 59133.55 | 59133.55 | 1.0000 | 2.15828373 | 1.838519 | 12.73 | 8.48 | 0.00531485 | 26213.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59133.55 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 22.3810 | 21.11 | 0.00658090 | 21.10 | 0.00658090 | 41.3042 | 25871.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20594.320 | 15430.500 | 0.958520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4240 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.958524 | 1.12523516 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10297.16 | 7688.76 | 1.0000 | 0.75015393 | 0.639013 | 26.20 | 18.53 | 0.01053500 | 53186.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10297.16 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 32.1964 | 23.89 | 0.00974920 | 23.89 | 0.00974920 | 51.4140 | 10484.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30354.222 | 30354.222 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.958524 | 1.12523516 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30354.22 | 30354.22 | 1.0000 | 1.12523516 | 0.958524 | 13.08 | 8.65 | 0.00532767 | 26593.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30354.22 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 21.4642 | 21.11 | 0.00653119 | 21.10 | 0.00653119 | 40.9965 | 13841.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20505.830 | 15355.176 | 0.952900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4435 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.952904 | 1.11863782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10252.92 | 7646.94 | 1.0000 | 0.74575562 | 0.635267 | 26.21 | 18.54 | 0.01054545 | 53222.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10252.92 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 32.3863 | 23.89 | 0.00975604 | 23.89 | 0.00975604 | 51.4495 | 10416.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30219.144 | 30219.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.952904 | 1.11863782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30219.14 | 30219.14 | 1.0000 | 1.11863782 | 0.952904 | 13.03 | 8.62 | 0.00531986 | 26526.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30219.14 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 21.5908 | 21.11 | 0.00653028 | 21.10 | 0.00653028 | 40.9908 | 13828.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20359.840 | 15238.119 | 0.944850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4600 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.944854 | 1.10918833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10179.92 | 7585.11 | 1.0000 | 0.73945556 | 0.629900 | 26.22 | 18.55 | 0.01055434 | 53253.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10179.92 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 32.6622 | 23.89 | 0.00976186 | 23.89 | 0.00976186 | 51.4797 | 10359.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30011.298 | 30011.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.944854 | 1.10918833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30011.30 | 30011.30 | 1.0000 | 1.10918833 | 0.944854 | 12.96 | 8.59 | 0.00532164 | 26460.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30011.30 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 21.7747 | 21.11 | 0.00654574 | 21.10 | 0.00654574 | 41.0869 | 14039.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21179.100 | 15965.865 | 0.998220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3806 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.998219 | 1.17183404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 10589.55 | 7908.09 | 1.0000 | 0.78122382 | 0.665480 | 26.03 | 18.46 | 0.01051162 | 52956.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10589.55 | 29.84 | 0.01336614 | 21.70 | 0.20573941 | 30.9159 | 23.89 | 0.00977055 | 23.89 | 0.00977055 | 51.5254 | 11031.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30936.811 | 30936.811 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.998219 | 1.17183404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30936.81 | 30936.81 | 1.0000 | 1.17183404 | 0.998219 | 13.40 | 8.89 | 0.00541621 | 27140.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30936.81 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.6107 | 21.10 | 0.00658244 | 21.10 | 0.00658244 | 41.3179 | 17238.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.92 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.84 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.94 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3083.50 | 4048.67 | 1850.33 |
SMSTORE1 | 2356.67 | 3689.83 | 998.33 |
SMSTORE2 | 2121.00 | 2929.83 | 1103.50 |
SMSTORE3 | 2164.50 | 2961.67 | 1161.17 |
SMSTORE4 | 2215.00 | 3017.33 | 1256.50 |
LGSTORE2 | 2189.17 | 2886.50 | 1425.00 |
SMSTORE5 | 2148.00 | 2931.67 | 1441.17 |
SMSTORE6 | 2165.33 | 2960.17 | 1475.33 |
SMSTORE7 | 2217.83 | 3011.67 | 1563.67 |
SMSTORE8 | 2457.67 | 3107.83 | 1843.83 |
Facility | 3821.33 | 4525.67 | 2548.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 14.50 | 0.00 | 5.50 | 0.00 |
SMSTORE1 | 2.33 | 0.00 | 0.33 | 0.00 |
SMSTORE2 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 3.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 44.17 | 0.00 | 0.00 | 0.00 |
Facility | 55.17 | 0.00 | 5.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.992 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.863 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.045 | 0.328 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.043 | 0.328 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.031 | 0.328 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.989 | 0.315 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.998 | 0.350 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.993 | 0.350 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.983 | 0.350 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.984 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10328978.14 | 0.00 | 10328978.14 | 2993858.48 | 13322836.62 | 12976396.34 | 3150.53 | 4223.00 | 1386.47 | 22.38 |
SMSTORE1 | 4493210.19 | 0.00 | 4493210.19 | 1454836.47 | 5948046.66 | 6488198.17 | 4328.37 | 3045.43 | 1386.20 | 26.96 |
SMSTORE2 | 4152699.29 | 0.00 | 4152699.29 | 1502250.16 | 5654949.44 | 6488198.17 | 4325.03 | 3434.25 | 1000.72 | 95.53 |
SMSTORE3 | 4141969.63 | 0.00 | 4141969.63 | 1502250.16 | 5644219.79 | 6488198.17 | 4325.17 | 3452.33 | 982.50 | 92.73 |
SMSTORE4 | 4090596.87 | 0.00 | 4090596.87 | 1502250.16 | 5592847.03 | 6488198.17 | 4327.07 | 3495.83 | 937.10 | 89.13 |
LGSTORE2 | 7190829.83 | 0.00 | 7190829.83 | 2777494.96 | 9968324.80 | 12976396.34 | 4698.10 | 3220.33 | 841.57 | 75.40 |
SMSTORE5 | 3631386.55 | 0.00 | 3631386.55 | 1515968.53 | 5147355.08 | 6488198.17 | 4696.65 | 3232.08 | 831.27 | 74.57 |
SMSTORE6 | 3611543.23 | 0.00 | 3611543.23 | 1515968.53 | 5127511.76 | 6488198.17 | 4698.26 | 3248.50 | 813.24 | 72.16 |
SMSTORE7 | 3566725.57 | 0.00 | 3566725.57 | 1515968.53 | 5082694.10 | 6488198.17 | 4701.49 | 3288.25 | 770.26 | 65.51 |
SMSTORE8 | 3558772.63 | 0.00 | 3558772.63 | 1946294.26 | 5505066.88 | 6488198.17 | 4711.44 | 3355.93 | 692.62 | 47.64 |
Total Facility | 48766711.93 | 0.00 | 48766711.93 | 18227140.23 | 66993852.16 | 77858378.04 | 4713.08 | 4763.36 | 1657.00 | 191.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4897 | 0.0000 | 0.4897 | 0.1189 | 0.6086 | 0.4115 | 240.21 | 4222.83 | 1376.95 |
SMSTORE1 | 0.2126 | 0.0000 | 0.2126 | 0.0623 | 0.2749 | 0.2057 | 1422.38 | 3045.43 | 1372.19 |
SMSTORE2 | 0.2577 | 0.0000 | 0.2577 | 0.0811 | 0.3388 | 0.2057 | 0.00 | 3434.08 | 960.92 |
SMSTORE3 | 0.2571 | 0.0000 | 0.2571 | 0.0811 | 0.3382 | 0.2057 | 0.00 | 3452.17 | 942.83 |
SMSTORE4 | 0.2543 | 0.0000 | 0.2543 | 0.0811 | 0.3353 | 0.2057 | 0.00 | 3495.25 | 899.75 |
LGSTORE2 | 0.4879 | 0.0000 | 0.4879 | 0.1559 | 0.6438 | 0.4115 | 0.00 | 3220.33 | 809.67 |
SMSTORE5 | 0.2463 | 0.0000 | 0.2463 | 0.0864 | 0.3327 | 0.2057 | 0.00 | 3231.75 | 798.25 |
SMSTORE6 | 0.2451 | 0.0000 | 0.2451 | 0.0864 | 0.3315 | 0.2057 | 0.00 | 3248.50 | 781.50 |
SMSTORE7 | 0.2425 | 0.0000 | 0.2425 | 0.0864 | 0.3289 | 0.2057 | 0.00 | 3287.75 | 742.25 |
SMSTORE8 | 0.2429 | 0.0000 | 0.2429 | 0.0931 | 0.3359 | 0.2057 | 0.00 | 3355.67 | 674.33 |
Total Facility | 2.9361 | 0.0000 | 2.9361 | 0.9327 | 3.8688 | 2.4689 | 1523.90 | 4761.51 | 1625.04 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14234810.23 | 0.00 | 14234810.23 | 12976396.34 | 3143.05 | 0.67 | 5616.29 | 22.38 |
PSZ-AC_2:2 | 6192238.06 | 0.00 | 6192238.06 | 6488198.17 | 4275.64 | 3.71 | 4480.65 | 26.96 |
PSZ-AC_3:3 | 5723003.24 | 0.00 | 5723003.24 | 6488198.17 | 4317.90 | 0.33 | 4441.76 | 95.36 |
PSZ-AC_4:4 | 5708212.87 | 0.00 | 5708212.87 | 6488198.17 | 4318.25 | 0.50 | 4441.25 | 92.40 |
PSZ-AC_5:5 | 5637415.67 | 0.00 | 5637415.67 | 6488198.17 | 4320.95 | 0.25 | 4438.80 | 89.05 |
PSZ-AC_6:6 | 9910027.11 | 0.00 | 9910027.11 | 12976396.34 | 4690.52 | 0.50 | 4068.98 | 75.40 |
PSZ-AC_7:7 | 5004566.61 | 0.00 | 5004566.61 | 6488198.17 | 4689.48 | 0.50 | 4070.02 | 74.41 |
PSZ-AC_8:8 | 4977217.32 | 0.00 | 4977217.32 | 6488198.17 | 4691.01 | 0.17 | 4068.82 | 72.16 |
PSZ-AC_9:9 | 4915438.20 | 0.00 | 4915438.20 | 6488198.17 | 4695.60 | 0.33 | 4064.06 | 65.51 |
PSZ-AC_10:10 | 4904413.23 | 0.00 | 4904413.23 | 6488198.17 | 4705.68 | 0.60 | 4053.72 | 47.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6749 | 0.0000 | 0.6749 | 0.4115 | 235.40 | 0.17 | 5604.44 |
PSZ-AC_2:2 | 0.2930 | 0.0000 | 0.2930 | 0.2057 | 1371.49 | 3.71 | 4464.80 |
PSZ-AC_3:3 | 0.3552 | 0.0000 | 0.3552 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3543 | 0.0000 | 0.3543 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3504 | 0.0000 | 0.3504 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6724 | 0.0000 | 0.6724 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3394 | 0.0000 | 0.3394 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3378 | 0.0000 | 0.3378 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3342 | 0.0000 | 0.3342 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3347 | 0.0000 | 0.3347 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5174.50 | 482.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4127.11 | 770.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4128.07 | 362.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4136.71 | 350.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4148.74 | 335.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3838.45 | 266.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3832.41 | 272.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3837.07 | 265.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3847.24 | 248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3860.42 | 217.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6882 | 0.8281 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3501 | 0.3590 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3470 | 0.4753 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3463 | 0.4758 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3426 | 0.4769 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6621 | 0.8618 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3336 | 0.4437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3321 | 0.4442 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3290 | 0.4383 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3291 | 0.4589 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
ElectricityPurchased:Plant | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
Cogeneration:ElectricityPurchased | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
General:Cogeneration:ElectricityPurchased | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
ElectricityNet:Plant | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
Cogeneration:ElectricityNet | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
General:Cogeneration:ElectricityNet | 830.07 | 2102.83 | 01-JAN-08:00 | 85220.10 | 21-JUL-13:40 |
Electricity:HVAC | 168.31 | 0.00 | 01-JAN-00:10 | 44349.07 | 15-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 67.50 | 0.00 | 01-JAN-00:10 | 37702.45 | 15-JUL-14:00 |
General:Cooling:Electricity | 67.50 | 0.00 | 01-JAN-00:10 | 37702.45 | 15-JUL-14:00 |
Fans:Electricity | 100.81 | 0.00 | 01-JAN-00:10 | 9306.96 | 06-FEB-12:10 |
General:Fans:Electricity | 100.81 | 0.00 | 01-JAN-00:10 | 9306.96 | 06-FEB-12:10 |
ExteriorLights:Electricity | 60.16 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.16 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 65.10 | 1211.00 | 06-JAN-00:20 | 11866.24 | 22-MAR-13:10 |
WaterSystems:Electricity | 65.10 | 1211.00 | 06-JAN-00:20 | 11866.24 | 22-MAR-13:10 |
Water Heater:WaterSystems:Electricity | 65.10 | 1211.00 | 06-JAN-00:20 | 11866.24 | 22-MAR-13:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 688.99 | 0.00 | 01-JAN-00:10 | 246829.25 | 07-FEB-08:10 |
NaturalGas:HVAC | 688.99 | 0.00 | 01-JAN-00:10 | 246829.25 | 07-FEB-08:10 |
Heating:NaturalGas | 688.99 | 0.00 | 01-JAN-00:10 | 246829.25 | 07-FEB-08:10 |
General:Heating:NaturalGas | 688.99 | 0.00 | 01-JAN-00:10 | 246829.25 | 07-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1324.04 | 0.00 | 01-JAN-00:10 | 371799.90 | 07-FEB-08:10 |
EnergyTransfer:Building | 499.19 | 0.00 | 01-JAN-00:10 | 174336.50 | 07-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 99.01 | 0.00 | 01-JAN-00:10 | 34339.26 | 07-FEB-08:10 |
Heating:EnergyTransfer | 188.78 | 0.00 | 01-JAN-00:10 | 174336.50 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 29.21 | 0.00 | 01-JAN-00:10 | 34339.26 | 07-FEB-08:10 |
General:Heating:EnergyTransfer | 188.78 | 0.00 | 01-JAN-00:10 | 174336.50 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 29.21 | 0.00 | 01-JAN-00:10 | 34339.26 | 07-FEB-08:10 |
Cooling:EnergyTransfer | 310.41 | 0.00 | 01-JAN-00:10 | 83268.17 | 21-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 69.80 | 0.00 | 01-JAN-00:10 | 13877.12 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer | 310.41 | 0.00 | 01-JAN-00:10 | 83268.17 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 69.80 | 0.00 | 01-JAN-00:10 | 13877.12 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 48.79 | 0.00 | 01-JAN-00:10 | 14078.16 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 8.99 | 0.00 | 01-JAN-00:10 | 14078.16 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 8.99 | 0.00 | 01-JAN-00:10 | 14078.16 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 39.80 | 0.00 | 01-JAN-00:10 | 9028.11 | 03-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 39.80 | 0.00 | 01-JAN-00:10 | 9028.11 | 03-JUN-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 40.14 | 0.00 | 01-JAN-00:10 | 15036.10 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 11.33 | 0.00 | 01-JAN-00:10 | 15036.10 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 11.33 | 0.00 | 01-JAN-00:10 | 15036.10 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 28.80 | 0.00 | 01-JAN-00:10 | 7281.81 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 28.80 | 0.00 | 01-JAN-00:10 | 7281.81 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE3 | 40.28 | 0.00 | 01-JAN-00:10 | 16082.77 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 12.30 | 0.00 | 01-JAN-00:10 | 16082.77 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 12.30 | 0.00 | 01-JAN-00:10 | 16082.77 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.98 | 0.00 | 01-JAN-00:10 | 7292.89 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.98 | 0.00 | 01-JAN-00:10 | 7292.89 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE4 | 40.06 | 0.00 | 01-JAN-00:10 | 16800.90 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 13.90 | 0.00 | 01-JAN-00:10 | 16800.90 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 13.90 | 0.00 | 01-JAN-00:10 | 16800.90 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 26.16 | 0.00 | 01-JAN-00:10 | 7158.84 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 26.16 | 0.00 | 01-JAN-00:10 | 7158.84 | 21-JUL-13:40 |
EnergyTransfer:Zone:LGSTORE2 | 70.19 | 0.00 | 01-JAN-00:10 | 33570.26 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 28.77 | 0.00 | 01-JAN-00:10 | 33570.26 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 28.77 | 0.00 | 01-JAN-00:10 | 33570.26 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 41.42 | 0.00 | 01-JAN-00:10 | 12932.30 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 41.42 | 0.00 | 01-JAN-00:10 | 12932.30 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 37.05 | 0.00 | 01-JAN-00:10 | 17835.59 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 16.39 | 0.00 | 01-JAN-00:10 | 17835.59 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 16.39 | 0.00 | 01-JAN-00:10 | 17835.59 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.66 | 0.00 | 01-JAN-00:10 | 6710.18 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.66 | 0.00 | 01-JAN-00:10 | 6710.18 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 36.94 | 0.00 | 01-JAN-00:10 | 17022.65 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 16.83 | 0.00 | 01-JAN-00:10 | 17022.65 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 16.83 | 0.00 | 01-JAN-00:10 | 17022.65 | 26-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 20.11 | 0.00 | 01-JAN-00:10 | 6659.25 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 20.11 | 0.00 | 01-JAN-00:10 | 6659.25 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 37.78 | 0.00 | 01-JAN-00:10 | 17505.12 | 11-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 19.07 | 0.00 | 01-JAN-00:10 | 17505.12 | 11-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 19.07 | 0.00 | 01-JAN-00:10 | 17505.12 | 11-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 18.71 | 0.00 | 01-JAN-00:10 | 6615.13 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 18.71 | 0.00 | 01-JAN-00:10 | 6615.13 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 48.94 | 0.00 | 01-JAN-00:10 | 20182.70 | 11-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 31.99 | 0.00 | 01-JAN-00:10 | 20182.70 | 11-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 31.99 | 0.00 | 01-JAN-00:10 | 20182.70 | 11-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.95 | 0.00 | 01-JAN-00:10 | 7260.02 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.95 | 0.00 | 01-JAN-00:10 | 7260.02 | 21-JUL-13:00 |
EnergyTransfer:HVAC | 824.85 | 0.00 | 01-JAN-00:10 | 197463.40 | 07-FEB-08:10 |
HeatingCoils:EnergyTransfer | 551.19 | 0.00 | 01-JAN-00:10 | 197463.40 | 07-FEB-08:10 |
CoolingCoils:EnergyTransfer | 273.66 | 0.00 | 01-JAN-00:10 | 159818.59 | 15-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 29.208 | -69.801 | 0.000 | 0.000 | 25.457 | 95.826 | 26.249 | 19.075 | 0.000 | 1.058 | 0.000 | 0.000 | -10.762 | 0.000 | -44.226 | -72.083 |
SMSTORE1 | 0.000 | 0.000 | 8.989 | -39.796 | 0.000 | 0.000 | 12.540 | 57.583 | 13.125 | 9.432 | 0.000 | 0.566 | 0.000 | 0.000 | -5.672 | 0.000 | -21.330 | -35.438 |
SMSTORE2 | 0.000 | 0.000 | 11.335 | -28.803 | 0.000 | 0.000 | 7.631 | 40.956 | 10.421 | 9.424 | 0.000 | 0.552 | 0.000 | 0.000 | -5.580 | 0.000 | -22.010 | -23.925 |
SMSTORE3 | 0.000 | 0.000 | 12.301 | -27.982 | 0.000 | 0.000 | 7.640 | 40.956 | 10.421 | 9.438 | 0.000 | 0.552 | 0.001 | 0.000 | -5.519 | 0.000 | -21.930 | -25.877 |
SMSTORE4 | 0.000 | 0.000 | 13.903 | -26.161 | 0.000 | 0.000 | 7.654 | 40.956 | 10.421 | 9.462 | 0.000 | 0.552 | 0.002 | 0.000 | -5.455 | 0.000 | -21.829 | -29.502 |
LGSTORE2 | 0.000 | 0.000 | 28.767 | -41.424 | 0.000 | 0.000 | 26.325 | 43.277 | 19.173 | 19.046 | 0.000 | 0.997 | 0.003 | 0.000 | -10.551 | 0.000 | -40.191 | -45.419 |
SMSTORE5 | 0.000 | 0.000 | 16.387 | -20.664 | 0.000 | 0.000 | 13.170 | 22.197 | 9.586 | 9.504 | 0.000 | 0.554 | 0.001 | 0.000 | -5.285 | 0.000 | -21.841 | -23.607 |
SMSTORE6 | 0.000 | 0.000 | 16.835 | -20.106 | 0.000 | 0.000 | 13.180 | 22.197 | 9.586 | 9.515 | 0.000 | 0.554 | 0.001 | 0.000 | -5.262 | 0.000 | -21.803 | -24.696 |
SMSTORE7 | 0.000 | 0.000 | 19.069 | -18.714 | 0.000 | 0.000 | 13.204 | 22.197 | 9.586 | 9.544 | 0.000 | 0.554 | 0.001 | 0.000 | -5.179 | 0.000 | -21.681 | -28.581 |
SMSTORE8 | 0.000 | 0.000 | 31.993 | -16.952 | 0.000 | 0.000 | 13.245 | 22.197 | 9.586 | 9.627 | 0.000 | 0.591 | 0.003 | 0.000 | -4.860 | 0.000 | -27.952 | -37.475 |
Total Facility | 0.000 | 0.000 | 188.786 | -310.403 | 0.000 | 0.000 | 140.047 | 408.342 | 128.154 | 114.067 | 0.000 | 6.529 | 0.013 | 0.000 | -64.125 | 0.000 | -264.794 | -346.603 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -34209.06 | 0.00 | 0.00 | 182.09 | 75.00 | 74.62 | 282.68 | 0.00 | 0.00 | 33772.12 | 0.00 | -0.00 | 0.00 | -177.46 | 0.00 |
SMSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18882.35 | 0.00 | 0.00 | 88.92 | 37.50 | 37.31 | 136.39 | 0.00 | 0.00 | 18675.35 | 0.00 | -0.00 | 0.00 | -93.12 | 0.00 |
SMSTORE2 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18922.50 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 132.90 | 0.00 | 0.00 | 18811.50 | 0.00 | -0.00 | 0.00 | -96.71 | 0.00 |
SMSTORE3 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -19006.68 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 132.41 | 0.00 | 0.00 | 18896.71 | 0.00 | -0.00 | 0.00 | -97.25 | 0.00 |
SMSTORE4 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18740.57 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 134.12 | 0.00 | 0.00 | 18626.34 | 0.00 | -0.00 | 0.00 | -94.71 | 0.00 |
LGSTORE2 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -31381.61 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 751.84 | 0.00 | 0.00 | 30574.39 | 0.00 | -0.00 | 0.00 | -93.25 | 0.00 |
SMSTORE5 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -15762.27 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 376.63 | 0.00 | 0.00 | 15360.59 | 0.00 | -0.00 | 0.00 | -49.28 | 0.00 |
SMSTORE6 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -15231.35 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 377.51 | 0.00 | 0.00 | 14828.67 | 0.00 | -0.00 | 0.00 | -49.14 | 0.00 |
SMSTORE7 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13658.24 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 123.40 | 0.00 | 0.00 | 13541.85 | 0.00 | -0.00 | 0.00 | -81.34 | 0.00 |
SMSTORE8 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13601.68 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 129.92 | 0.00 | 0.00 | 13487.28 | 0.00 | -0.00 | 0.00 | -89.84 | 0.00 |
Total Facility | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -131668.16 | 0.00 | 0.00 | 564.27 | 450.00 | 1452.23 | 1497.11 | 0.00 | 0.00 | 128657.14 | 0.00 | 0.00 | 0.00 | -952.59 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:12 | 0.00 | 0.00 | 61256.66 | 0.00 | 0.00 | 0.00 | 231.22 | 267.77 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1097.46 | 0.00 | -2519.21 | -58213.61 |
SMSTORE1 | 07-MAR-08:61 | 0.00 | 0.00 | 32102.12 | 0.00 | 0.00 | 0.00 | 131.47 | 37.50 | 37.31 | 250.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -826.63 | -31732.74 |
SMSTORE2 | 10-DEC-08:61 | 0.00 | 0.00 | 32226.15 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94.68 | 0.00 | -872.08 | -31334.20 |
SMSTORE3 | 10-DEC-08:61 | 0.00 | 0.00 | 32102.36 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.00 | 0.00 | -864.08 | -31224.09 |
SMSTORE4 | 10-DEC-08:61 | 0.00 | 0.00 | 32069.70 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.95 | 0.00 | -856.48 | -31204.09 |
LGSTORE2 | 06-FEB-08:12 | 0.00 | 0.00 | 59520.05 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1083.50 | 0.00 | -2087.11 | -56498.07 |
SMSTORE5 | 06-FEB-08:12 | 0.00 | 0.00 | 30641.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -544.53 | 0.00 | -1128.02 | -29043.02 |
SMSTORE6 | 06-FEB-08:12 | 0.00 | 0.00 | 30501.44 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -545.04 | 0.00 | -1133.63 | -28897.08 |
SMSTORE7 | 06-FEB-08:12 | 0.00 | 0.00 | 30336.60 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -542.30 | 0.00 | -1128.15 | -28740.47 |
SMSTORE8 | 06-FEB-08:12 | 0.00 | 0.00 | 31388.97 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -529.99 | 0.00 | -1546.52 | -29386.77 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 295896.62 | 0.00 | 0.00 | 0.00 | 772.62 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6374.73 | 0.00 | -12736.13 | -279460.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9236 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9236 | 0.2139 | 1.0000 | Not calculated | 0.4115 | 0.2139 | ||
PSZ-AC_2:2 | 1.0316 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0436 | 0.1971 | 1.0000 | Not calculated | 0.2057 | 0.1971 | ||
PSZ-AC_3:3 | 1.0377 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0497 | 0.1960 | 1.0000 | Not calculated | 0.2057 | 0.1960 | ||
PSZ-AC_4:4 | 1.0319 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0536 | 0.1953 | 1.0000 | Not calculated | 0.2057 | 0.1953 | ||
PSZ-AC_5:5 | 1.0304 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0439 | 0.1971 | 1.0000 | Not calculated | 0.2057 | 0.1971 | ||
PSZ-AC_6:6 | 1.8385 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8385 | 0.2238 | 1.0000 | Not calculated | 0.4115 | 0.2238 | ||
PSZ-AC_7:7 | 0.9546 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9585 | 0.2146 | 1.0000 | Not calculated | 0.2057 | 0.2146 | ||
PSZ-AC_8:8 | 0.9485 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9529 | 0.2159 | 1.0000 | Not calculated | 0.2057 | 0.2159 | ||
PSZ-AC_9:9 | 0.9392 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9449 | 0.2177 | 1.0000 | Not calculated | 0.2057 | 0.2177 | ||
PSZ-AC_10:10 | 0.9807 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9982 | 0.2061 | 1.0000 | Not calculated | 0.2057 | 0.2061 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9236 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9236 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2139 | ||
PSZ-AC_2:2 | 1.0316 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0316 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1994 | ||
PSZ-AC_3:3 | 1.0377 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0377 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1983 | ||
PSZ-AC_4:4 | 1.0319 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0319 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1994 | ||
PSZ-AC_5:5 | 1.0304 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0304 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1997 | ||
PSZ-AC_6:6 | 1.8385 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8385 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2238 | ||
PSZ-AC_7:7 | 0.9546 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9546 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2155 | ||
PSZ-AC_8:8 | 0.9485 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9485 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2169 | ||
PSZ-AC_9:9 | 0.9392 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9392 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2191 | ||
PSZ-AC_10:10 | 0.9807 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9807 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2098 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9236 | 1.9236 | 1.9236 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0316 | 1.0316 | 1.0316 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0377 | 1.0377 | 1.0377 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0319 | 1.0319 | 1.0319 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0304 | 1.0304 | 1.0304 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8385 | 1.8385 | 1.8385 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9546 | 0.9546 | 0.9546 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9485 | 0.9485 | 0.9485 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9392 | 0.9392 | 0.9392 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9807 | 0.9807 | 0.9807 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9236 | 1.9236 | 1.9236 | 1.9236 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0316 | 1.0436 | 1.0316 | 1.0316 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0377 | 1.0497 | 1.0377 | 1.0377 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0319 | 1.0536 | 1.0319 | 1.0319 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0304 | 1.0439 | 1.0304 | 1.0304 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8385 | 1.8385 | 1.8385 | 1.8385 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9546 | 0.9585 | 0.9546 | 0.9546 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9485 | 0.9529 | 0.9485 | 0.9485 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9392 | 0.9449 | 0.9392 | 0.9392 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9807 | 0.9982 | 0.9807 | 0.9807 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9236 | 1.9236 | 1.9236 | No | 0.4115 | 0.2784 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0316 | 1.0316 | 1.0316 | No | 0.2057 | 0.2950 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0377 | 1.0377 | 1.0377 | No | 0.2057 | 0.2918 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0319 | 1.0319 | 1.0319 | No | 0.2057 | 0.2901 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0304 | 1.0304 | 1.0304 | No | 0.2057 | 0.2870 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8385 | 1.8385 | 1.8385 | No | 0.4115 | 0.2998 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9546 | 0.9546 | 0.9546 | No | 0.2057 | 0.2802 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9485 | 0.9485 | 0.9485 | No | 0.2057 | 0.2804 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9392 | 0.9392 | 0.9392 | No | 0.2057 | 0.2762 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9807 | 0.9807 | 0.9807 | No | 0.2057 | 0.2250 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9236 | 1.9236 | 1.9236 | 1.9236 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0316 | 1.0316 | 1.0316 | 1.0316 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0377 | 1.0377 | 1.0377 | 1.0377 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0319 | 1.0319 | 1.0319 | 1.0319 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0304 | 1.0304 | 1.0304 | 1.0304 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8385 | 1.8385 | 1.8385 | 1.8385 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9546 | 0.9546 | 0.9546 | 0.9546 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9485 | 0.9485 | 0.9485 | 0.9485 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9392 | 0.9392 | 0.9392 | 0.9392 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9807 | 0.9807 | 0.9807 | 0.9807 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 5.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 5.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 688.99 | 246829.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 67.50 | 37702.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.16 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 100.81 | 9306.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.10 | 11866.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 830.07 |
Natural Gas | 0.00 | 688.99 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1519.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 32.29 |
Fans (All) | 48.23 |
Service Water Heating | 31.14 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 397.10 |
Subtotal | 397.10 |
Natural Gas [MJ/m2] | |
Space Heating | 329.61 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 329.61 |
Subtotal | 329.61 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.88 |
Space Heating | 45.36 |
Space Cooling | 4.44 |
Fans (All) | 6.64 |
Service Water Heating | 4.29 |
Receptacle Equipment | 8.44 |
Miscellaneous | 3.96 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Min | 8740.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 19.67 | 0.00 | 0.00 | 0.00 |
Average | 8752.52 | 7.48 | 0.00 | 0.00 | 0.00 |
Sum | 87525.17 | 74.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25471.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25471.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93198.00 | 13.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45906.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45907.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Min | 25471.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93198.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Average | 48605.48 | 4.72 | 0.00 | 0.00 | 0.00 |
Sum | 486054.83 | 47.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8248.00 | 512.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8545.00 | 215.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8080.83 | 679.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8080.00 | 680.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8079.67 | 680.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8074.50 | 685.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8077.00 | 683.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8075.67 | 684.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8076.00 | 684.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8096.00 | 664.00 | 0.00 | 0.00 | 0.00 |
Min | 8074.50 | 215.00 | 0.00 | 0.00 | 0.00 |
Max | 8545.00 | 685.50 | 0.00 | 0.00 | 0.00 |
Average | 8143.27 | 616.73 | 0.00 | 0.00 | 0.00 |
Sum | 81432.67 | 6167.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86591.00 | 2450.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43016.00 | 761.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24761.00 | 714.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24744.17 | 730.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24680.00 | 795.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89472.83 | 3738.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44008.00 | 1904.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 43970.67 | 1941.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 43873.50 | 2038.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43686.50 | 2225.50 | 0.00 | 0.00 | 0.00 |
Min | 24680.00 | 714.00 | 0.00 | 0.00 | 0.00 |
Max | 89472.83 | 3738.17 | 0.00 | 0.00 | 0.00 |
Average | 46880.37 | 1729.83 | 0.00 | 0.00 | 0.00 |
Sum | 468803.67 | 17298.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474115E+09 | 13692.93 | 06-JAN-00:02 | -10.0 | -10.7 | 0.106495E+10 | 1275.40 | 29-JAN-18:00 | -6.7 | -7.2 |
February | 0.445493E+09 | 13706.32 | 11-FEB-00:02 | -10.0 | -10.7 | 0.961255E+09 | 1275.40 | 20-FEB-18:00 | -1.1 | -2.5 |
March | 0.207670E+10 | 13437.26 | 04-MAR-00:02 | -9.4 | -10.8 | 0.108441E+10 | 1437.79 | 12-MAR-17:00 | 13.30 | 11.37 |
April | 0.368790E+10 | 8166.07 | 13-APR-23:03 | 1.78 | 0.76 | 0.108768E+10 | 1685.82 | 08-APR-12:00 | 1.78 | 0.76 |
May | 0.633951E+10 | 7342.50 | 14-MAY-15:00 | 26.10 | 17.84 | 0.130057E+10 | 1685.89 | 13-MAY-12:00 | 26.10 | 17.84 |
June | 0.102927E+11 | 21552.51 | 12-JUN-07:03 | 24.08 | 18.79 | 0.134760E+10 | 1686.00 | 17-JUN-12:00 | 26.10 | 21.79 |
July | 0.136946E+11 | 26174.24 | 26-JUL-07:03 | 20.87 | 17.48 | 0.141267E+10 | 1685.99 | 30-JUL-17:00 | 24.40 | 20.25 |
August | 0.133205E+11 | 34217.28 | 06-AUG-07:02 | 20.28 | 15.40 | 0.139344E+10 | 1686.04 | 13-AUG-12:50 | 29.82 | 22.72 |
September | 0.984975E+10 | 26246.48 | 17-SEP-07:02 | 22.12 | 19.56 | 0.135026E+10 | 1685.98 | 15-SEP-12:09 | 22.12 | 19.56 |
October | 0.596872E+10 | 7171.07 | 11-OCT-17:10 | 21.23 | 14.34 | 0.119127E+10 | 1685.93 | 22-OCT-12:00 | 21.70 | 14.82 |
November | 0.292686E+10 | 9757.76 | 24-NOV-00:03 | -1.8 | -2.5 | 0.105518E+10 | 1685.73 | 05-NOV-12:00 | -1.8 | -2.5 |
December | 0.725128E+09 | 13386.83 | 29-DEC-00:02 | -9.4 | -10.3 | 0.107029E+10 | 1275.40 | 10-DEC-18:00 | -9.4 | -10.3 |
Annual Sum or Average | 0.698020E+11 | 0.143196E+11 | ||||||||
Minimum of Months | 0.445493E+09 | 7171.07 | -10.0 | -10.8 | 0.961255E+09 | 1275.40 | -9.4 | -10.3 | ||
Maximum of Months | 0.136946E+11 | 34217.28 | 26.10 | 19.56 | 0.141267E+10 | 1686.04 | 29.82 | 22.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239633E+09 | 5145.97 | 10-JAN-11:32 | -3.2 | -5.6 | 0.543975E+09 | 755.10 | 16-JAN-18:00 | 3.90 | 1.26 |
February | 0.221628E+09 | 6000.62 | 10-FEB-11:02 | -6.6 | -7.8 | 0.489572E+09 | 731.44 | 19-FEB-18:00 | 2.20 | 1.05 |
March | 0.117777E+10 | 12934.02 | 15-MAR-20:09 | 20.73 | 14.37 | 0.564153E+09 | 842.90 | 12-MAR-17:00 | 20.73 | 14.37 |
April | 0.200056E+10 | 3805.69 | 10-APR-08:63 | 3.98 | 2.98 | 0.581797E+09 | 842.91 | 08-APR-12:00 | 3.98 | 2.98 |
May | 0.370326E+10 | 16098.07 | 21-MAY-17:08 | 17.62 | 10.45 | 0.678685E+09 | 842.94 | 13-MAY-12:00 | 17.62 | 10.45 |
June | 0.612754E+10 | 16208.82 | 03-JUN-18:08 | 17.80 | 10.05 | 0.673692E+09 | 842.98 | 25-JUN-17:40 | 26.87 | 18.30 |
July | 0.786583E+10 | 16318.78 | 26-JUL-07:03 | 20.87 | 17.48 | 0.704631E+09 | 843.14 | 02-JUL-17:30 | 20.87 | 17.48 |
August | 0.760432E+10 | 18885.01 | 06-AUG-07:02 | 20.28 | 15.40 | 0.694777E+09 | 842.99 | 13-AUG-17:30 | 26.95 | 22.39 |
September | 0.576031E+10 | 15874.21 | 10-SEP-17:08 | 16.10 | 10.54 | 0.678790E+09 | 842.96 | 09-SEP-12:00 | 16.10 | 10.54 |
October | 0.317459E+10 | 13129.05 | 22-OCT-20:59 | 18.90 | 14.02 | 0.631661E+09 | 842.94 | 22-OCT-12:00 | 18.90 | 14.02 |
November | 0.159255E+10 | 3971.52 | 29-NOV-09:47 | 1.70 | -0.5 | 0.556624E+09 | 842.90 | 05-NOV-17:00 | 1.70 | -0.5 |
December | 0.328218E+09 | 6645.65 | 28-DEC-18:52 | -9.4 | -10.3 | 0.549363E+09 | 744.59 | 24-DEC-18:40 | -9.4 | -10.3 |
Annual Sum or Average | 0.397962E+11 | 0.734772E+10 | ||||||||
Minimum of Months | 0.221628E+09 | 3805.69 | -9.4 | -10.3 | 0.489572E+09 | 731.44 | -9.4 | -10.3 | ||
Maximum of Months | 0.786583E+10 | 18885.01 | 20.87 | 17.48 | 0.704631E+09 | 843.14 | 26.95 | 22.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85190861.03 | 5143.98 | 05-JAN-11:32 | -3.2 | -4.6 | 0.317182E+09 | 637.68 | 14-JAN-13:50 | 3.98 | 3.16 |
February | 86695311.48 | 5974.42 | 10-FEB-11:12 | -6.5 | -7.7 | 0.288117E+09 | 637.68 | 04-FEB-13:30 | -6.5 | -7.7 |
March | 0.837452E+09 | 5172.85 | 24-MAR-09:53 | -3.3 | -5.1 | 0.336352E+09 | 702.45 | 15-MAR-17:00 | -3.3 | -5.1 |
April | 0.155389E+10 | 4160.09 | 17-APR-09:13 | 1.13 | -1.4 | 0.331830E+09 | 842.91 | 08-APR-12:00 | 1.13 | -1.4 |
May | 0.271113E+10 | 4140.09 | 27-MAY-13:00 | 21.70 | 12.35 | 0.402006E+09 | 842.93 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.439634E+10 | 14986.63 | 26-JUN-06:03 | 20.50 | 17.42 | 0.414767E+09 | 842.97 | 17-JUN-12:09 | 20.50 | 17.42 |
July | 0.565896E+10 | 16511.57 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419900E+09 | 842.96 | 15-JUL-12:20 | 20.60 | 17.13 |
August | 0.564031E+10 | 18926.62 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431257E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.410276E+10 | 14340.52 | 17-SEP-07:02 | 22.12 | 19.56 | 0.406847E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.242621E+10 | 4210.54 | 24-OCT-07:02 | 1.78 | 0.45 | 0.359160E+09 | 842.88 | 21-OCT-12:00 | 1.78 | 0.45 |
November | 0.115208E+10 | 4102.21 | 22-NOV-09:13 | 1.10 | -1.3 | 0.314557E+09 | 743.53 | 04-NOV-12:00 | 1.10 | -1.3 |
December | 0.152455E+09 | 6561.34 | 27-DEC-18:12 | -9.1 | -10.6 | 0.316800E+09 | 637.68 | 09-DEC-13:09 | -9.1 | -10.6 |
Annual Sum or Average | 0.288035E+11 | 0.433878E+10 | ||||||||
Minimum of Months | 85190861.03 | 4102.21 | -9.1 | -10.6 | 0.288117E+09 | 637.68 | -9.1 | -10.6 | ||
Maximum of Months | 0.565896E+10 | 18926.62 | 22.12 | 19.56 | 0.431257E+09 | 842.97 | 23.40 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61966214.81 | 6587.56 | 24-JAN-18:02 | -9.2 | -10.9 | 0.317181E+09 | 637.68 | 14-JAN-13:50 | -9.2 | -10.9 |
February | 71067282.19 | 5271.46 | 03-FEB-19:33 | -3.7 | -4.3 | 0.288104E+09 | 637.68 | 18-FEB-13:20 | 2.07 | 0.36 |
March | 0.751822E+09 | 6021.91 | 07-MAR-19:52 | -6.7 | -7.9 | 0.335926E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.141994E+10 | 3902.23 | 24-APR-07:01 | 3.17 | 1.61 | 0.329861E+09 | 842.91 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.257872E+10 | 4035.09 | 27-MAY-13:00 | 21.70 | 12.35 | 0.399222E+09 | 842.93 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.435347E+10 | 14949.62 | 26-JUN-06:03 | 20.50 | 17.42 | 0.414681E+09 | 842.97 | 17-JUN-12:00 | 20.50 | 17.42 |
July | 0.566201E+10 | 16563.01 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419897E+09 | 842.96 | 15-JUL-12:20 | 20.60 | 17.13 |
August | 0.564056E+10 | 19010.83 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431246E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.404819E+10 | 14379.91 | 17-SEP-07:02 | 22.12 | 19.56 | 0.406520E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.225871E+10 | 4162.47 | 24-OCT-07:02 | 1.78 | 0.45 | 0.356911E+09 | 842.89 | 21-OCT-12:00 | 1.78 | 0.45 |
November | 0.101541E+10 | 3585.00 | 02-NOV-07:01 | 4.40 | 3.64 | 0.313626E+09 | 736.90 | 04-NOV-12:00 | 16.70 | 13.41 |
December | 0.120320E+09 | 3444.41 | 02-DEC-09:43 | 3.98 | 1.87 | 0.316799E+09 | 637.68 | 02-DEC-13:50 | 2.80 | 1.49 |
Annual Sum or Average | 0.279822E+11 | 0.432997E+10 | ||||||||
Minimum of Months | 61966214.81 | 3444.41 | -9.2 | -10.9 | 0.288104E+09 | 637.68 | -9.2 | -10.9 | ||
Maximum of Months | 0.566201E+10 | 19010.83 | 22.12 | 19.56 | 0.431246E+09 | 842.97 | 23.90 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38401617.11 | 5247.34 | 06-JAN-19:23 | -3.6 | -5.5 | 0.317182E+09 | 637.68 | 07-JAN-13:20 | -0.9 | -2.9 |
February | 41935086.47 | 4843.25 | 28-FEB-11:13 | -1.8 | -4.0 | 0.288104E+09 | 637.68 | 18-FEB-13:20 | -1.8 | -4.0 |
March | 0.622945E+09 | 5431.81 | 07-MAR-11:53 | -4.4 | -7.0 | 0.335215E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.123140E+10 | 3858.90 | 17-APR-09:53 | 2.20 | 0.10 | 0.326969E+09 | 842.90 | 08-APR-12:00 | 2.20 | 0.10 |
May | 0.235389E+10 | 3752.67 | 27-MAY-13:00 | 21.70 | 12.35 | 0.394477E+09 | 842.92 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.414054E+10 | 13384.82 | 26-JUN-06:03 | 20.50 | 17.42 | 0.414303E+09 | 842.97 | 17-JUN-12:00 | 20.50 | 17.42 |
July | 0.546855E+10 | 15640.24 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419853E+09 | 842.96 | 29-JUL-12:09 | 25.68 | 21.35 |
August | 0.544132E+10 | 18744.66 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431162E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.385661E+10 | 14144.67 | 17-SEP-07:02 | 22.12 | 19.56 | 0.405691E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.203549E+10 | 3624.84 | 23-OCT-17:10 | 4.40 | 2.51 | 0.353536E+09 | 842.88 | 21-OCT-12:00 | 4.40 | 2.51 |
November | 0.841032E+09 | 3644.80 | 21-NOV-10:13 | 3.17 | 2.22 | 0.312532E+09 | 726.15 | 04-NOV-12:00 | 3.17 | 2.22 |
December | 89690949.37 | 6147.12 | 07-DEC-18:22 | -7.2 | -8.6 | 0.316799E+09 | 637.68 | 02-DEC-13:00 | -7.2 | -8.6 |
Annual Sum or Average | 0.261618E+11 | 0.431582E+10 | ||||||||
Minimum of Months | 38401617.11 | 3624.84 | -7.2 | -8.6 | 0.288104E+09 | 637.68 | -7.2 | -8.6 | ||
Maximum of Months | 0.546855E+10 | 18744.66 | 22.12 | 19.56 | 0.431162E+09 | 842.97 | 25.68 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2963845.94 | 757.56 | 21-JAN-12:00 | -0.6 | -3.2 | 0.108442E+10 | 1700.53 | 07-JAN-15:20 | -0.6 | -3.2 |
February | 11418405.20 | 9629.78 | 28-FEB-18:03 | -1.3 | -3.4 | 0.987309E+09 | 1700.53 | 11-FEB-15:50 | -1.3 | -3.4 |
March | 0.745998E+09 | 8246.53 | 25-MAR-17:23 | 1.70 | -1.6 | 0.114871E+10 | 1995.02 | 15-MAR-12:00 | 1.70 | -1.6 |
April | 0.176343E+10 | 6638.52 | 11-APR-09:13 | 5.00 | 3.28 | 0.110944E+10 | 2247.80 | 08-APR-14:09 | 5.00 | 3.28 |
May | 0.371896E+10 | 6213.88 | 27-MAY-14:30 | 21.70 | 12.26 | 0.132088E+10 | 2247.89 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.671287E+10 | 22097.87 | 26-JUN-07:03 | 20.28 | 17.94 | 0.141898E+10 | 2247.89 | 10-JUN-14:09 | 20.28 | 17.94 |
July | 0.915887E+10 | 26515.40 | 26-JUL-07:03 | 20.87 | 17.48 | 0.143757E+10 | 2247.99 | 01-JUL-14:39 | 20.87 | 17.48 |
August | 0.908040E+10 | 31388.43 | 06-AUG-08:62 | 22.07 | 16.34 | 0.147855E+10 | 2247.97 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.620381E+10 | 24813.11 | 17-SEP-08:62 | 21.70 | 19.45 | 0.138876E+10 | 2247.97 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.304906E+10 | 6562.54 | 14-OCT-08:63 | 6.10 | 5.58 | 0.118750E+10 | 2247.76 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.948339E+09 | 4662.85 | 01-NOV-10:40 | 10.03 | 5.69 | 0.106098E+10 | 2062.30 | 04-NOV-14:00 | 18.30 | 13.74 |
December | 28365232.50 | 2546.05 | 16-DEC-12:00 | 4.40 | 1.70 | 0.108625E+10 | 1700.53 | 09-DEC-15:50 | 4.40 | 1.70 |
Annual Sum or Average | 0.414245E+11 | 0.147093E+11 | ||||||||
Minimum of Months | 2963845.94 | 757.56 | -1.3 | -3.4 | 0.987309E+09 | 1700.53 | -1.3 | -3.4 | ||
Maximum of Months | 0.915887E+10 | 31388.43 | 22.07 | 19.45 | 0.147855E+10 | 2247.99 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1968475.82 | 2582.90 | 17-JAN-18:15 | 7.80 | 6.69 | 0.542192E+09 | 850.24 | 07-JAN-15:20 | 7.80 | 6.69 |
February | 3593370.03 | 466.27 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 04-FEB-15:50 | 1.10 | 0.02 |
March | 0.353322E+09 | 4990.58 | 24-MAR-10:53 | -2.2 | -4.5 | 0.574107E+09 | 997.48 | 15-MAR-12:00 | -2.2 | -4.5 |
April | 0.811017E+09 | 2901.28 | 02-APR-10:53 | 6.70 | 5.64 | 0.553319E+09 | 1123.85 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.177492E+10 | 3084.10 | 27-MAY-14:30 | 21.70 | 12.26 | 0.656957E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.337414E+10 | 10580.55 | 26-JUN-07:03 | 20.28 | 17.94 | 0.709201E+09 | 1123.91 | 10-JUN-14:20 | 20.28 | 17.94 |
July | 0.468475E+10 | 12987.66 | 30-JUL-08:62 | 20.97 | 18.75 | 0.718748E+09 | 1123.97 | 01-JUL-14:50 | 20.97 | 18.75 |
August | 0.463872E+10 | 15765.70 | 06-AUG-08:62 | 22.07 | 16.34 | 0.739223E+09 | 1123.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.312199E+10 | 12812.41 | 17-SEP-08:62 | 21.70 | 19.45 | 0.694048E+09 | 1123.95 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.144683E+10 | 3218.39 | 14-OCT-08:63 | 6.10 | 5.58 | 0.592194E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.439813E+09 | 4038.18 | 18-NOV-18:53 | 1.70 | 0.22 | 0.529999E+09 | 1021.48 | 04-NOV-14:00 | 1.70 | 0.22 |
December | 13274500.36 | 1235.98 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543098E+09 | 850.24 | 02-DEC-15:09 | 4.40 | 1.70 |
Annual Sum or Average | 0.206644E+11 | 0.734673E+10 | ||||||||
Minimum of Months | 1968475.82 | 466.27 | -2.2 | -4.5 | 0.493640E+09 | 850.24 | -2.2 | -4.5 | ||
Maximum of Months | 0.468475E+10 | 15765.70 | 22.07 | 19.45 | 0.739223E+09 | 1123.97 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 648057.27 | 251.92 | 21-JAN-12:00 | -0.6 | -3.2 | 0.542193E+09 | 850.24 | 07-JAN-15:30 | -0.6 | -3.2 |
February | 3003332.60 | 415.34 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 11-FEB-15:20 | 1.10 | 0.02 |
March | 0.327514E+09 | 3917.37 | 21-MAR-19:13 | 2.20 | 0.15 | 0.573804E+09 | 997.47 | 15-MAR-12:00 | 2.20 | 0.15 |
April | 0.763371E+09 | 2391.97 | 29-APR-09:15 | 8.67 | 7.77 | 0.551975E+09 | 1123.85 | 08-APR-14:20 | 8.67 | 7.77 |
May | 0.169241E+10 | 2954.80 | 27-MAY-14:40 | 21.70 | 12.23 | 0.652664E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.23 |
June | 0.328278E+10 | 10371.34 | 18-JUN-08:62 | 24.50 | 21.64 | 0.708671E+09 | 1123.91 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.461276E+10 | 12582.38 | 30-JUL-08:62 | 20.97 | 18.75 | 0.718736E+09 | 1123.95 | 01-JUL-14:00 | 20.97 | 18.75 |
August | 0.456871E+10 | 15234.58 | 06-AUG-08:62 | 22.07 | 16.34 | 0.739146E+09 | 1123.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.305314E+10 | 12718.09 | 17-SEP-08:62 | 21.70 | 19.45 | 0.693333E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.138333E+10 | 3207.93 | 16-OCT-09:03 | 5.37 | 3.93 | 0.590102E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.406451E+09 | 4091.67 | 28-NOV-20:53 | 1.70 | 0.01 | 0.529611E+09 | 1016.39 | 04-NOV-14:00 | 1.70 | 0.01 |
December | 11651003.90 | 3031.80 | 01-DEC-20:23 | 6.10 | 3.97 | 0.543104E+09 | 850.24 | 02-DEC-15:50 | 3.22 | 1.61 |
Annual Sum or Average | 0.201058E+11 | 0.733698E+10 | ||||||||
Minimum of Months | 648057.27 | 251.92 | -0.6 | -3.2 | 0.493640E+09 | 850.24 | -0.6 | -3.2 | ||
Maximum of Months | 0.461276E+10 | 15234.58 | 24.50 | 21.64 | 0.739146E+09 | 1123.96 | 25.37 | 21.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 433.69 | 7.23 | 15-JAN-09:04 | 0.87 | 0.15 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | 0.87 | 0.15 |
February | 1831442.91 | 4229.76 | 18-FEB-11:43 | 0.92 | -0.2 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | 0.92 | -0.2 |
March | 0.259227E+09 | 4495.34 | 23-MAR-10:43 | 0.00 | -2.3 | 0.572968E+09 | 997.43 | 14-MAR-16:10 | 0.00 | -2.3 |
April | 0.617258E+09 | 3474.50 | 17-APR-18:23 | 4.15 | -0.4 | 0.548655E+09 | 1123.86 | 08-APR-14:00 | 4.15 | -0.4 |
May | 0.149981E+10 | 2666.54 | 27-MAY-14:40 | 21.70 | 12.23 | 0.642364E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.23 |
June | 0.305769E+10 | 9577.94 | 18-JUN-08:62 | 24.50 | 21.64 | 0.706953E+09 | 1123.91 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.445449E+10 | 12200.90 | 19-JUL-07:02 | 22.20 | 20.31 | 0.718700E+09 | 1123.93 | 08-JUL-14:09 | 22.20 | 20.31 |
August | 0.441611E+10 | 13661.38 | 07-AUG-07:02 | 21.20 | 18.87 | 0.738885E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.287905E+10 | 12518.94 | 17-SEP-08:62 | 21.70 | 19.45 | 0.691194E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.121206E+10 | 3214.11 | 24-OCT-12:13 | 5.37 | 2.51 | 0.585558E+09 | 1123.85 | 21-OCT-14:30 | 5.37 | 2.51 |
November | 0.311192E+09 | 3583.79 | 30-NOV-18:03 | 3.72 | 2.02 | 0.528519E+09 | 1000.89 | 04-NOV-14:00 | 3.72 | 2.02 |
December | 5892751.91 | 987.80 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:00 | 4.40 | 1.70 |
Annual Sum or Average | 0.187146E+11 | 0.731274E+10 | ||||||||
Minimum of Months | 433.69 | 7.23 | 0.00 | -2.3 | 0.493640E+09 | 850.24 | 0.00 | -2.3 | ||
Maximum of Months | 0.445449E+10 | 13661.38 | 24.50 | 21.64 | 0.738885E+09 | 1123.96 | 25.37 | 21.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 14-JAN-15:00 | 3.30 | 2.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 04-FEB-15:09 | -5.6 | -7.0 |
March | 0.127633E+09 | 2435.30 | 16-MAR-17:10 | 9.50 | 8.92 | 0.571428E+09 | 997.43 | 14-MAR-16:10 | 9.50 | 8.92 |
April | 0.346049E+09 | 2925.99 | 11-APR-18:13 | 6.47 | 4.06 | 0.543703E+09 | 1112.94 | 08-APR-14:09 | 6.47 | 4.06 |
May | 0.109485E+10 | 2309.24 | 11-MAY-19:55 | 8.90 | 8.33 | 0.626003E+09 | 1123.89 | 13-MAY-14:00 | 22.80 | 14.76 |
June | 0.281052E+10 | 6181.22 | 27-JUN-13:00 | 30.60 | 23.75 | 0.702544E+09 | 1123.90 | 10-JUN-14:20 | 30.60 | 23.75 |
July | 0.445489E+10 | 11529.97 | 22-JUL-07:02 | 21.10 | 20.28 | 0.718671E+09 | 1123.96 | 08-JUL-14:30 | 21.10 | 20.28 |
August | 0.442264E+10 | 13606.12 | 07-AUG-07:02 | 21.20 | 18.87 | 0.737925E+09 | 1123.95 | 26-AUG-14:30 | 26.10 | 21.71 |
September | 0.268908E+10 | 10386.32 | 17-SEP-08:62 | 21.70 | 19.45 | 0.685978E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.873536E+09 | 3557.82 | 16-OCT-18:13 | 3.67 | 1.67 | 0.579533E+09 | 1123.86 | 21-OCT-14:00 | 19.40 | 11.82 |
November | 0.132475E+09 | 2545.30 | 15-NOV-19:55 | 7.80 | 4.62 | 0.526749E+09 | 969.11 | 04-NOV-14:00 | 7.80 | 4.62 |
December | 313221.89 | 308.19 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:00 | 4.40 | 1.70 |
Annual Sum or Average | 0.169520E+11 | 0.727148E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -5.6 | -7.0 | ||
Maximum of Months | 0.445489E+10 | 13606.12 | 30.60 | 23.75 | 0.737925E+09 | 1123.96 | 30.60 | 23.75 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803083E+10 | 61093.98 | 30-JAN-08:61 | -10.5 |
February | 0.779654E+10 | 61256.56 | 06-FEB-08:12 | -15.0 |
March | 0.354612E+10 | 61112.43 | 07-MAR-08:61 | -10.8 |
April | 0.104929E+10 | 61069.39 | 17-APR-07:01 | -2.9 |
May | 0.106909E+09 | 48957.05 | 01-MAY-07:01 | 6.05 |
June | 39159306.50 | 1410.49 | 12-JUN-07:05 | 24.08 |
July | 22941561.72 | 1550.66 | 26-JUL-07:05 | 20.87 |
August | 25509387.91 | 1622.69 | 06-AUG-07:04 | 20.28 |
September | 40034824.18 | 1447.63 | 14-SEP-07:05 | 20.60 |
October | 0.230405E+09 | 61066.66 | 17-OCT-07:01 | -2.4 |
November | 0.129522E+10 | 61072.88 | 22-NOV-08:61 | 1.10 |
December | 0.702464E+10 | 61110.53 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.292076E+11 | |||
Minimum of Months | 22941561.72 | 1410.49 | -15.0 | |
Maximum of Months | 0.803083E+10 | 61256.56 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263982E+10 | 32089.06 | 10-JAN-08:61 | -9.9 |
February | 0.258158E+10 | 32087.51 | 10-FEB-08:61 | -9.7 |
March | 0.899014E+09 | 32102.12 | 07-MAR-08:61 | -10.8 |
April | 0.185507E+09 | 32070.25 | 17-APR-07:01 | -2.9 |
May | 38198389.95 | 458.61 | 11-MAY-08:00 | 10.00 |
June | 12621599.09 | 897.63 | 12-JUN-07:05 | 24.08 |
July | 15088858.70 | 970.85 | 26-JUL-07:05 | 20.87 |
August | 14914317.98 | 959.43 | 11-AUG-07:05 | 18.40 |
September | 11625585.69 | 895.37 | 14-SEP-07:05 | 20.60 |
October | 50401462.18 | 24364.19 | 30-OCT-07:01 | 0.87 |
November | 0.246408E+09 | 32067.98 | 24-NOV-08:61 | -2.6 |
December | 0.229415E+10 | 32095.91 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.898933E+10 | |||
Minimum of Months | 11625585.69 | 458.61 | -14.8 | |
Maximum of Months | 0.263982E+10 | 32102.12 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323559E+10 | 32212.20 | 29-JAN-08:61 | -8.1 |
February | 0.308447E+10 | 32225.42 | 05-FEB-08:61 | -13.0 |
March | 0.120462E+10 | 32226.15 | 05-MAR-08:61 | -9.7 |
April | 0.301683E+09 | 32183.77 | 16-APR-07:01 | -3.7 |
May | 40678224.69 | 5968.40 | 01-MAY-06:03 | 2.35 |
June | 19511117.91 | 1396.69 | 17-JUN-17:03 | 28.80 |
July | 30581318.00 | 1658.78 | 16-JUL-16:02 | 30.03 |
August | 26089950.79 | 1369.27 | 13-AUG-16:03 | 29.03 |
September | 13337882.35 | 873.67 | 14-SEP-06:05 | 20.60 |
October | 79982066.02 | 27659.41 | 30-OCT-06:02 | -0.4 |
November | 0.460753E+09 | 31917.99 | 24-NOV-07:01 | -3.2 |
December | 0.283745E+10 | 32226.16 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.113348E+11 | |||
Minimum of Months | 13337882.35 | 873.67 | -13.0 | |
Maximum of Months | 0.323559E+10 | 32226.16 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347438E+10 | 32088.39 | 29-JAN-08:61 | -8.1 |
February | 0.329102E+10 | 32101.58 | 05-FEB-08:61 | -13.0 |
March | 0.133906E+10 | 32102.25 | 05-MAR-08:61 | -9.7 |
April | 0.358226E+09 | 32060.05 | 16-APR-07:01 | -3.7 |
May | 45175126.43 | 10568.62 | 01-MAY-06:03 | 2.35 |
June | 20298282.07 | 1399.55 | 17-JUN-17:03 | 28.80 |
July | 30604748.68 | 1659.94 | 16-JUL-16:02 | 30.03 |
August | 26122503.42 | 1370.52 | 13-AUG-16:03 | 29.03 |
September | 14721091.44 | 878.51 | 14-SEP-06:05 | 20.60 |
October | 97629294.34 | 31373.80 | 30-OCT-06:02 | -0.4 |
November | 0.558285E+09 | 31794.56 | 24-NOV-07:01 | -3.2 |
December | 0.304505E+10 | 32102.37 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.123006E+11 | |||
Minimum of Months | 14721091.44 | 878.51 | -13.0 | |
Maximum of Months | 0.347438E+10 | 32102.37 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386287E+10 | 32055.89 | 29-JAN-08:61 | -8.1 |
February | 0.363058E+10 | 32068.88 | 05-FEB-08:61 | -13.0 |
March | 0.157108E+10 | 32069.57 | 05-MAR-08:61 | -9.7 |
April | 0.452644E+09 | 32027.58 | 16-APR-07:01 | -3.7 |
May | 50654386.55 | 14257.26 | 01-MAY-06:03 | 2.35 |
June | 22250757.23 | 1406.55 | 17-JUN-17:03 | 28.80 |
July | 30969243.34 | 1664.21 | 16-JUL-16:02 | 30.03 |
August | 26004959.13 | 1376.45 | 13-AUG-16:03 | 29.03 |
September | 17223498.44 | 861.61 | 14-SEP-06:05 | 20.60 |
October | 0.125277E+09 | 31349.11 | 30-OCT-06:02 | -0.4 |
November | 0.707354E+09 | 31765.37 | 24-NOV-07:01 | -3.2 |
December | 0.340566E+10 | 32069.71 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.139026E+11 | |||
Minimum of Months | 17223498.44 | 861.61 | -13.0 | |
Maximum of Months | 0.386287E+10 | 32069.71 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.793190E+10 | 59262.68 | 10-JAN-08:61 | -9.9 |
February | 0.738526E+10 | 59520.07 | 06-FEB-08:12 | -15.0 |
March | 0.327336E+10 | 59283.46 | 07-MAR-08:61 | -10.8 |
April | 0.102564E+10 | 59236.24 | 17-APR-07:01 | -2.9 |
May | 0.126380E+09 | 58979.33 | 01-MAY-07:01 | 6.05 |
June | 50349914.57 | 2814.33 | 17-JUN-17:03 | 28.80 |
July | 40188672.72 | 3328.72 | 16-JUL-16:02 | 30.03 |
August | 40718093.05 | 2774.44 | 13-AUG-16:03 | 29.03 |
September | 41459464.81 | 1452.31 | 17-SEP-08:05 | 21.70 |
October | 0.316544E+09 | 59233.11 | 17-OCT-07:01 | -2.4 |
November | 0.153832E+10 | 59234.12 | 22-NOV-08:61 | 1.10 |
December | 0.699688E+10 | 59423.92 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.287670E+11 | |||
Minimum of Months | 40188672.72 | 1452.31 | -15.0 | |
Maximum of Months | 0.793190E+10 | 59520.07 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444124E+10 | 30435.94 | 10-JAN-08:61 | -9.9 |
February | 0.413607E+10 | 30641.26 | 06-FEB-08:12 | -15.0 |
March | 0.193536E+10 | 30447.00 | 07-MAR-08:61 | -10.8 |
April | 0.626619E+09 | 30420.95 | 17-APR-07:01 | -2.9 |
May | 76318088.87 | 30283.28 | 03-MAY-07:01 | 8.07 |
June | 28343619.32 | 1426.31 | 17-JUN-17:03 | 28.80 |
July | 20963018.86 | 1677.42 | 16-JUL-16:02 | 30.03 |
August | 21196548.12 | 1398.25 | 13-AUG-16:03 | 29.03 |
September | 24034551.58 | 774.48 | 17-SEP-08:05 | 21.70 |
October | 0.194945E+09 | 30419.14 | 17-OCT-07:01 | -2.4 |
November | 0.940656E+09 | 30418.24 | 22-NOV-08:61 | 1.10 |
December | 0.394142E+10 | 30577.28 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.163872E+11 | |||
Minimum of Months | 20963018.86 | 774.48 | -15.0 | |
Maximum of Months | 0.444124E+10 | 30641.26 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452366E+10 | 30304.63 | 10-JAN-08:61 | -9.9 |
February | 0.420715E+10 | 30501.45 | 06-FEB-08:12 | -15.0 |
March | 0.201241E+10 | 30315.63 | 07-MAR-08:61 | -10.8 |
April | 0.679986E+09 | 30289.28 | 17-APR-07:01 | -2.9 |
May | 83450580.62 | 30164.40 | 08-MAY-07:01 | 5.87 |
June | 29544045.92 | 1428.99 | 17-JUN-17:03 | 28.80 |
July | 20742523.94 | 1678.69 | 16-JUL-16:02 | 30.03 |
August | 21000236.33 | 1400.11 | 13-AUG-16:03 | 29.03 |
September | 25522659.73 | 768.00 | 17-SEP-08:05 | 21.70 |
October | 0.213948E+09 | 30287.85 | 17-OCT-07:01 | -2.4 |
November | 0.994162E+09 | 30287.23 | 22-NOV-08:61 | 1.10 |
December | 0.402287E+10 | 30459.37 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.168344E+11 | |||
Minimum of Months | 20742523.94 | 768.00 | -15.0 | |
Maximum of Months | 0.452366E+10 | 30501.45 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499007E+10 | 30187.16 | 29-JAN-09:12 | -7.0 |
February | 0.462581E+10 | 30336.61 | 06-FEB-08:12 | -15.0 |
March | 0.238426E+10 | 30114.35 | 07-MAR-08:61 | -10.8 |
April | 0.888544E+09 | 30091.28 | 17-APR-07:01 | -2.9 |
May | 0.118895E+09 | 29967.89 | 08-MAY-07:01 | 5.87 |
June | 33036683.61 | 1436.38 | 17-JUN-17:03 | 28.80 |
July | 19681028.46 | 1680.59 | 16-JUL-16:02 | 30.03 |
August | 21221132.97 | 1404.10 | 13-AUG-16:03 | 29.03 |
September | 31454798.12 | 2750.62 | 30-SEP-07:02 | 8.17 |
October | 0.279220E+09 | 30088.21 | 17-OCT-07:01 | -2.4 |
November | 0.122206E+10 | 30088.78 | 22-NOV-08:61 | 1.10 |
December | 0.445470E+10 | 30313.31 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.190690E+11 | |||
Minimum of Months | 19681028.46 | 1404.10 | -15.0 | |
Maximum of Months | 0.499007E+10 | 30336.61 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787772E+10 | 31270.24 | 04-JAN-08:12 | -12.9 |
February | 0.751073E+10 | 31388.96 | 06-FEB-08:12 | -15.0 |
March | 0.431484E+10 | 31177.79 | 28-MAR-07:12 | -0.9 |
April | 0.188043E+10 | 31028.81 | 17-APR-07:01 | -2.9 |
May | 0.323574E+09 | 30854.28 | 08-MAY-07:01 | 5.87 |
June | 40141115.37 | 5710.44 | 14-JUN-07:03 | 10.18 |
July | 22192584.61 | 1679.11 | 16-JUL-16:02 | 30.03 |
August | 26105578.37 | 1400.91 | 13-AUG-16:03 | 29.03 |
September | 46597892.30 | 24409.92 | 30-SEP-07:02 | 8.17 |
October | 0.634140E+09 | 30989.97 | 17-OCT-07:01 | -2.4 |
November | 0.226894E+10 | 30994.93 | 22-NOV-08:61 | 1.10 |
December | 0.704693E+10 | 31344.26 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.319923E+11 | |||
Minimum of Months | 22192584.61 | 1400.91 | -15.0 | |
Maximum of Months | 0.787772E+10 | 31388.96 | 30.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770500E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747110E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11413919.26 | 0.528267E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351377E+10 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366662.13 | 0.199378E+10 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184216E+09 | 0.104297E+10 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443614E+09 | 0.367967E+09 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372458E+09 | 0.545611E+09 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35643235.03 | 0.133415E+10 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313250E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427544E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756115E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105771E+10 | 0.442261E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367967E+09 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443614E+09 | 0.770500E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371737E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354976E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6181516.74 | 0.258300E+10 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172284E+10 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5593156.61 | 0.100884E+10 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97857344.52 | 0.475937E+09 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236770E+09 | 0.146529E+09 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200315E+09 | 0.230641E+09 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19255491.58 | 0.640501E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155576E+10 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207877E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361964E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565973E+09 | 0.213296E+11 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146529E+09 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236770E+09 | 0.371737E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382858E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366245E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181577.56 | 0.264903E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177480E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593737.41 | 0.103528E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94569375.79 | 0.502032E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230728E+09 | 0.171047E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195759E+09 | 0.255732E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19084757.60 | 0.668846E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158678E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212697E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374845E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551917E+09 | 0.220100E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171047E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230728E+09 | 0.382858E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382099E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365475E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181618.74 | 0.264241E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176243E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593737.05 | 0.102198E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94578154.70 | 0.501191E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230695E+09 | 0.171237E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195753E+09 | 0.255854E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19084965.49 | 0.666889E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157429E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211741E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374042E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551887E+09 | 0.219299E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171237E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230695E+09 | 0.382099E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381463E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364848E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181674.07 | 0.263533E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174743E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.64 | 0.100123E+10 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94642789.22 | 0.497489E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230853E+09 | 0.169023E+09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195820E+09 | 0.253714E+09 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086015.25 | 0.662026E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155828E+10 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210805E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373361E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552177E+09 | 0.218293E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169023E+09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230853E+09 | 0.381463E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703343E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675136E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11124764.08 | 0.484817E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320397E+10 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070361.65 | 0.179447E+10 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171092E+09 | 0.923492E+09 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417222E+09 | 0.320873E+09 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353206E+09 | 0.478476E+09 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34359331.15 | 0.121959E+10 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283951E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388082E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689732E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997075E+09 | 0.401915E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320873E+09 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417222E+09 | 0.703343E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383445E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367198E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182523.16 | 0.264482E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173769E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.07 | 0.966259E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94917377.00 | 0.495907E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231635E+09 | 0.167908E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196252E+09 | 0.253621E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19092321.26 | 0.660544E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154265E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211200E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375365E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553673E+09 | 0.218415E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167908E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231635E+09 | 0.383445E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383286E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367058E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182763.62 | 0.264252E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173262E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593734.88 | 0.954970E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94951448.00 | 0.493654E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231696E+09 | 0.167183E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196287E+09 | 0.252861E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19092867.26 | 0.658254E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153661E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210929E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375190E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553804E+09 | 0.218033E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167183E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231696E+09 | 0.383286E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382355E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366226E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6189040.27 | 0.263328E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171774E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593734.57 | 0.927031E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95040980.22 | 0.486350E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231846E+09 | 0.164886E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196361E+09 | 0.250480E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19093813.49 | 0.651150E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152195E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209983E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374221E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554125E+09 | 0.216807E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164886E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231846E+09 | 0.382355E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488445E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480692E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6560884.79 | 0.329925E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220467E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5954383.32 | 0.114907E+10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102608E+09 | 0.660559E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248358E+09 | 0.269131E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207238E+09 | 0.384701E+09 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20015923.22 | 0.843627E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192251E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267528E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485178E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590736E+09 | 0.279519E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269131E+09 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248358E+09 | 0.488445E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11393.74 | 31-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12700.39 | 06-FEB-17:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.70 | 15-MAR-14:00 | 10040.83 | 06-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 8058.18 | 16-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 14-MAY-15:00 | 3955.51 | 11-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.26 | 27-JUN-13:00 | 3947.51 | 13-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 21-JUL-14:00 | 1647.40 | 02-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.04 | 10-AUG-14:00 | 2777.59 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.75 | 16-SEP-13:00 | 3508.64 | 28-SEP-16:40 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5309.52 | 23-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6512.23 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11348.04 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.40 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 12700.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.89 | 14-MAY-15:00 | 2143.27 | 11-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2236.15 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.60 | 02-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.99 | 10-AUG-14:00 | 1535.53 | 31-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.89 | 16-SEP-13:00 | 2011.47 | 28-SEP-16:30 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.60 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2110.48 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2240.78 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.61 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.06 | 10-AUG-14:00 | 1533.90 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1997.49 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.61 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.79 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2238.82 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.61 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1532.58 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1988.84 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.61 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2217.38 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.59 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1525.19 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1966.02 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.59 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11118.18 | 31-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12216.69 | 06-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 641.12 | 15-MAR-14:00 | 9818.19 | 06-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7828.71 | 16-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 14-MAY-15:00 | 3797.45 | 11-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.06 | 27-JUN-13:00 | 3898.13 | 13-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.97 | 21-JUL-14:00 | 1609.10 | 02-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.77 | 10-AUG-14:00 | 2693.96 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 971.22 | 16-SEP-13:00 | 3422.26 | 28-SEP-16:30 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5204.75 | 23-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6438.11 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11218.88 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.10 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.97 | 12216.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2162.78 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1496.08 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1903.23 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2151.95 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.04 | 10-AUG-14:00 | 1496.08 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1892.77 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2117.70 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.04 | 10-AUG-14:00 | 1494.12 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1860.57 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6455.29 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7285.77 | 06-FEB-17:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.72 | 15-MAR-14:00 | 5681.40 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4578.11 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 | 14-MAY-15:00 | 2263.84 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 27-JUN-13:00 | 2112.01 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 15-JUL-15:00 | 932.71 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.39 | 10-AUG-14:00 | 1559.49 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 575.37 | 16-SEP-13:00 | 1841.09 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3011.82 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3659.14 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6376.32 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.71 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 7285.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13692.93 | 06-JAN-00:02 | 2025.02 | 1606.62 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.49 |
February | 13706.32 | 11-FEB-00:02 | 2025.02 | 16067.16 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.08 |
March | 13437.26 | 04-MAR-00:02 | 2025.02 | 16067.16 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.20 |
April | 8166.07 | 13-APR-23:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.65 |
May | 7342.50 | 14-MAY-15:00 | 2700.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 0.00 |
June | 21552.51 | 12-JUN-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 0.00 |
July | 26174.24 | 26-JUL-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.00 |
August | 34217.28 | 06-AUG-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.46 |
September | 26246.48 | 17-SEP-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.65 |
October | 7171.07 | 11-OCT-17:10 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 |
November | 9757.76 | 24-NOV-00:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.82 |
December | 13386.83 | 29-DEC-00:02 | 2025.02 | 1606.62 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7171.07 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34217.28 | 3375.03 | 16067.16 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 621.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5145.97 | 10-JAN-11:32 | 1349.97 | 12246.74 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.75 |
February | 6000.62 | 10-FEB-11:02 | 1687.47 | 15308.43 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.96 |
March | 12934.02 | 15-MAR-20:09 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 3805.69 | 10-APR-08:63 | 506.24 | 4834.24 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.78 |
May | 16098.07 | 21-MAY-17:08 | 12149.77 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.66 |
June | 16208.82 | 03-JUN-18:08 | 10124.81 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.59 |
July | 16318.78 | 26-JUL-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.06 |
August | 18885.01 | 06-AUG-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
September | 15874.21 | 10-SEP-17:08 | 10124.81 | 15308.43 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.70 |
October | 13129.05 | 22-OCT-20:59 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
November | 3971.52 | 29-NOV-09:47 | 506.24 | 4834.24 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.88 |
December | 6645.65 | 28-DEC-18:52 | 8437.34 | 15308.43 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3805.69 | 506.24 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | |
Maximum of Months | 18885.01 | 12149.77 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5143.98 | 05-JAN-11:32 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.34 |
February | 5974.42 | 10-FEB-11:12 | 1687.47 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.13 |
March | 5172.85 | 24-MAR-09:53 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.97 |
April | 4160.09 | 17-APR-09:13 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.67 |
May | 4140.09 | 27-MAY-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 14986.63 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 |
July | 16511.57 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
August | 18926.62 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.71 |
September | 14340.52 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.77 |
October | 4210.54 | 24-OCT-07:02 | 1012.48 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.57 |
November | 4102.21 | 22-NOV-09:13 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.18 |
December | 6561.34 | 27-DEC-18:12 | 8437.34 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4102.21 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | |
Maximum of Months | 18926.62 | 8437.34 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6587.56 | 24-JAN-18:02 | 8437.34 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.29 |
February | 5271.46 | 03-FEB-19:33 | 2699.95 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.72 |
March | 6021.91 | 07-MAR-19:52 | 3374.94 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.61 |
April | 3902.23 | 24-APR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.50 |
May | 4035.09 | 27-MAY-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 14949.62 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
July | 16563.01 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
August | 19010.83 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.25 |
September | 14379.91 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 |
October | 4162.47 | 24-OCT-07:02 | 1012.48 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.91 |
November | 3585.00 | 02-NOV-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.76 |
December | 3444.41 | 02-DEC-09:43 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3444.41 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | |
Maximum of Months | 19010.83 | 8437.34 | 13945.03 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5247.34 | 06-JAN-19:23 | 2699.95 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.00 |
February | 4843.25 | 28-FEB-11:13 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.20 |
March | 5431.81 | 07-MAR-11:53 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.76 |
April | 3858.90 | 17-APR-09:53 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.46 |
May | 3752.67 | 27-MAY-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 13384.82 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 |
July | 15640.24 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 |
August | 18744.66 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.71 |
September | 14144.67 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
October | 3624.84 | 23-OCT-17:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.62 |
November | 3644.80 | 21-NOV-10:13 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.20 |
December | 6147.12 | 07-DEC-18:22 | 8437.34 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3624.84 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 | |
Maximum of Months | 18744.66 | 8437.34 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 757.56 | 21-JAN-12:00 | 3915.04 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.69 |
February | 9629.78 | 28-FEB-18:03 | 9180.09 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.62 |
March | 8246.53 | 25-MAR-17:23 | 2970.03 | 6719.20 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.50 |
April | 6638.52 | 11-APR-09:13 | 2227.52 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.73 |
May | 6213.88 | 27-MAY-14:30 | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.10 |
June | 22097.87 | 26-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.29 |
July | 26515.40 | 26-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 |
August | 31388.43 | 06-AUG-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.25 |
September | 24813.11 | 17-SEP-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 |
October | 6562.54 | 14-OCT-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.82 |
November | 4662.85 | 01-NOV-10:40 | 2902.53 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.15 |
December | 2546.05 | 16-DEC-12:00 | 3915.04 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 757.56 | 0.00 | 225.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.25 | |
Maximum of Months | 31388.43 | 9180.09 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2582.90 | 17-JAN-18:15 | 2294.96 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.32 |
February | 466.27 | 18-FEB-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 4990.58 | 24-MAR-10:53 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.10 |
April | 2901.28 | 02-APR-10:53 | 1113.73 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.45 |
May | 3084.10 | 27-MAY-14:30 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 10580.55 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.97 |
July | 12987.66 | 30-JUL-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.21 |
August | 15765.70 | 06-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 |
September | 12812.41 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 |
October | 3218.39 | 14-OCT-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.24 |
November | 4038.18 | 18-NOV-18:53 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.49 |
December | 1235.98 | 16-DEC-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 466.27 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | |
Maximum of Months | 15765.70 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 251.92 | 21-JAN-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 |
February | 415.34 | 18-FEB-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 3917.37 | 21-MAR-19:13 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 |
April | 2391.97 | 29-APR-09:15 | 742.49 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.91 |
May | 2954.80 | 27-MAY-14:40 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.49 |
June | 10371.34 | 18-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 0.00 |
July | 12582.38 | 30-JUL-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 |
August | 15234.58 | 06-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.14 |
September | 12718.09 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.85 |
October | 3207.93 | 16-OCT-09:03 | 1113.73 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.20 |
November | 4091.67 | 28-NOV-20:53 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 |
December | 3031.80 | 01-DEC-20:23 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 251.92 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15234.58 | 2699.95 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 630.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7.23 | 15-JAN-09:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.60 |
February | 4229.76 | 18-FEB-11:43 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.76 |
March | 4495.34 | 23-MAR-10:43 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.54 |
April | 3474.50 | 17-APR-18:23 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.95 |
May | 2666.54 | 27-MAY-14:40 | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.49 |
June | 9577.94 | 18-JUN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 0.00 |
July | 12200.90 | 19-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
August | 13661.38 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.34 |
September | 12518.94 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 |
October | 3214.11 | 24-OCT-12:13 | 7188.61 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2670.76 |
November | 3583.79 | 30-NOV-18:03 | 3442.43 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.20 |
December | 987.80 | 16-DEC-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7.23 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13661.38 | 7188.61 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 2670.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.40 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.86 |
March | 2435.30 | 16-MAR-17:10 | 1147.48 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.49 |
April | 2925.99 | 11-APR-18:13 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.84 |
May | 2309.24 | 11-MAY-19:55 | 742.49 | 1724.48 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 |
June | 6181.22 | 27-JUN-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 0.00 |
July | 11529.97 | 22-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.61 |
August | 13606.12 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.84 |
September | 10386.32 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.54 |
October | 3557.82 | 16-OCT-18:13 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.18 |
November | 2545.30 | 15-NOV-19:55 | 1754.97 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.77 |
December | 308.19 | 16-DEC-12:00 | 1957.46 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13606.12 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 847.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.681688E+11 | 58439.90 | 07-JAN-17:19 | 0.166351E+12 | 220069.10 | 24-JAN-08:09 |
February | 0.611797E+11 | 57548.87 | 13-FEB-17:40 | 0.155446E+12 | 246829.25 | 07-FEB-08:09 |
March | 0.667745E+11 | 59829.07 | 15-MAR-13:50 | 0.947545E+11 | 199374.73 | 06-MAR-08:09 |
April | 0.616301E+11 | 53217.17 | 10-APR-18:49 | 0.394429E+11 | 145811.72 | 17-APR-07:10 |
May | 0.640388E+11 | 61550.48 | 14-MAY-14:39 | 0.280991E+10 | 56241.21 | 01-MAY-07:10 |
June | 0.725856E+11 | 82818.66 | 27-JUN-12:50 | 5577330.73 | 2337.95 | 14-JUN-07:10 |
July | 0.865169E+11 | 85220.10 | 21-JUL-13:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.835392E+11 | 79946.57 | 13-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.691235E+11 | 73177.35 | 16-SEP-13:09 | 68110598.42 | 11881.22 | 30-SEP-08:20 |
October | 0.646806E+11 | 53280.18 | 11-OCT-15:09 | 0.186838E+11 | 100115.16 | 30-OCT-07:10 |
November | 0.639120E+11 | 53562.39 | 07-NOV-17:19 | 0.584598E+11 | 133782.92 | 24-NOV-08:09 |
December | 0.679193E+11 | 56676.28 | 04-DEC-16:49 | 0.152964E+12 | 229187.25 | 11-DEC-08:09 |
Annual Sum or Average | 0.830069E+12 | 0.688986E+12 | ||||
Minimum of Months | 0.611797E+11 | 53217.17 | 0.00 | 0.00 | ||
Maximum of Months | 0.865169E+11 | 85220.10 | 0.166351E+12 | 246829.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.682956E+10 | 0.108325E+11 | 0.00 | 0.102667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571199E+10 | 0.00 |
February | 0.312534E+11 | 0.554424E+10 | 0.980803E+10 | 0.00 | 0.938336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519068E+10 | 0.00 |
March | 0.350527E+11 | 0.527657E+10 | 0.110075E+11 | 0.00 | 0.919751E+10 | 0.00 | 0.00 | 0.489547E+09 | 0.00 | 0.00 | 0.00 | 0.575065E+10 | 0.00 |
April | 0.334898E+11 | 0.423575E+10 | 0.105079E+11 | 0.00 | 0.793273E+10 | 0.00 | 0.00 | 7324528.88 | 0.00 | 0.00 | 0.00 | 0.545653E+10 | 0.00 |
May | 0.347840E+11 | 0.365953E+10 | 0.109147E+11 | 0.00 | 0.769607E+10 | 0.00 | 0.00 | 0.145932E+10 | 0.00 | 0.00 | 0.00 | 0.552512E+10 | 0.00 |
June | 0.338757E+11 | 0.323285E+10 | 0.106386E+11 | 0.00 | 0.747648E+10 | 0.00 | 0.00 | 0.121142E+11 | 0.00 | 0.00 | 0.00 | 0.524792E+10 | 0.00 |
July | 0.344108E+11 | 0.343030E+10 | 0.107945E+11 | 0.00 | 0.762983E+10 | 0.00 | 0.00 | 0.249498E+11 | 0.00 | 0.00 | 0.00 | 0.530167E+10 | 0.00 |
August | 0.350409E+11 | 0.403418E+10 | 0.110006E+11 | 0.00 | 0.773071E+10 | 0.00 | 0.00 | 0.204059E+11 | 0.00 | 0.00 | 0.00 | 0.532685E+10 | 0.00 |
September | 0.335014E+11 | 0.473138E+10 | 0.105148E+11 | 0.00 | 0.740698E+10 | 0.00 | 0.00 | 0.780982E+10 | 0.00 | 0.00 | 0.00 | 0.515913E+10 | 0.00 |
October | 0.345281E+11 | 0.578212E+10 | 0.108325E+11 | 0.00 | 0.784730E+10 | 0.00 | 0.00 | 0.266302E+09 | 0.00 | 0.00 | 0.00 | 0.542433E+10 | 0.00 |
November | 0.334535E+11 | 0.637028E+10 | 0.104978E+11 | 0.00 | 0.822779E+10 | 0.00 | 0.00 | 636172.61 | 0.00 | 0.00 | 0.00 | 0.536196E+10 | 0.00 |
December | 0.344233E+11 | 0.703773E+10 | 0.108050E+11 | 0.00 | 0.100139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563934E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.601645E+11 | 0.128154E+12 | 0.00 | 0.100809E+12 | 0.00 | 0.00 | 0.675028E+11 | 0.00 | 0.00 | 0.00 | 0.650962E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.323285E+10 | 0.980803E+10 | 0.00 | 0.740698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515913E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.703773E+10 | 0.110075E+11 | 0.00 | 0.102667E+11 | 0.00 | 0.00 | 0.249498E+11 | 0.00 | 0.00 | 0.00 | 0.575065E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.166351E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.155446E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.947545E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.394429E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.280991E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5577330.73 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 68110598.42 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.186838E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.584598E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.152964E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.688986E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.166351E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8855.31 | 24-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9306.96 | 06-FEB-12:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8509.11 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7614.72 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6117.26 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:49 | 8059.50 | 01-JUN-09:09 | 0.00 | 6544.37 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:00 | 8059.50 | 01-JUL-09:09 | 0.00 | 7062.95 | 21-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 6795.05 | 14-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6064.35 | 16-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6851.52 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7414.68 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9010.98 | 11-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 6064.35 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 9306.96 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11864.33 | 07-JAN-14:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11465.21 | 03-FEB-13:00 | 0.00 |
March | 13763.92 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 11866.24 | 22-MAR-13:09 | 0.00 |
April | 1398.23 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 9707.40 | 17-APR-11:09 | 0.00 |
May | 16911.54 | 14-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9722.09 | 18-MAY-12:09 | 0.00 |
June | 37256.00 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 8669.96 | 19-JUN-10:30 | 0.00 |
July | 37702.45 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9703.53 | 21-JUL-12:09 | 0.00 |
August | 36092.73 | 13-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7577.84 | 03-AUG-12:09 | 0.00 |
September | 27434.58 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 | 7583.92 | 30-SEP-12:39 | 0.00 |
October | 8869.60 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11802.14 | 18-OCT-11:09 | 0.00 |
November | 242.04 | 16-NOV-21:49 | 0.00 | 0.00 | 0.00 | 7599.41 | 24-NOV-13:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9729.57 | 04-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7577.84 | 0.00 | ||
Maximum of Months | 37702.45 | 0.00 | 0.00 | 0.00 | 11866.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58439.90 | 07-JAN-17:19 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7418.06 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57548.87 | 13-FEB-17:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8019.85 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59829.07 | 15-MAR-13:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5173.23 | 0.00 | 0.00 | 13437.46 | 0.00 |
April | 53217.17 | 10-APR-18:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 5828.82 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61550.48 | 14-MAY-14:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5173.23 | 0.00 | 0.00 | 16628.37 | 0.00 |
June | 82818.66 | 27-JUN-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6405.19 | 0.00 | 0.00 | 36633.66 | 0.00 |
July | 85220.10 | 21-JUL-13:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6276.95 | 0.00 | 0.00 | 36306.10 | 0.00 |
August | 79946.57 | 13-AUG-15:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5907.19 | 0.00 | 0.00 | 34295.24 | 0.00 |
September | 73177.35 | 16-SEP-13:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5173.23 | 0.00 | 0.00 | 26924.96 | 0.00 |
October | 53280.18 | 11-OCT-15:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5173.23 | 0.00 | 0.00 | 8347.86 | 0.00 |
November | 53562.39 | 07-NOV-17:19 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6171.14 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56676.28 | 04-DEC-16:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7166.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 53217.17 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5173.23 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85220.10 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8019.85 | 0.00 | 0.00 | 36633.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 220069.10 | 24-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 246829.25 | 07-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 199374.73 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 145811.72 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 56241.21 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2337.95 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 11881.22 | 30-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 100115.16 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 133782.92 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 229187.25 | 11-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 246829.25 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.41 | 2.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
February | 4.33 | 20.28 | 1.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 2.00 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
April | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 2.50 | 20.35 | 1.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 14.50 | 20.38 | 5.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.54 | 2.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 1.00 | 20.46 | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 2.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 0.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 1.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Annual Sum or Average | 1.83 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 1.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 3.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 2.67 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 0.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 7.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 2.50 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 0.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Annual Sum or Average | 7.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 2.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 7.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
February | 3.67 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
March | 1.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
April | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 11.50 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
February | 16.50 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
March | 5.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
April | 2.17 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
November | 0.67 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 8.83 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Annual Sum or Average | 44.17 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.06 | 437.17 | 21.05 | 437.17 | 21.05 |
February | 448.00 | 21.05 | 415.17 | 21.04 | 415.17 | 21.04 |
March | 476.67 | 21.17 | 229.00 | 21.12 | 229.00 | 21.09 |
April | 476.17 | 21.44 | 56.50 | 21.39 | 56.50 | 21.35 |
May | 336.83 | 22.39 | 35.83 | 22.51 | 2.17 | 22.50 |
June | 125.00 | 23.48 | 282.00 | 23.76 | 58.50 | 23.78 |
July | 107.17 | 23.89 | 467.67 | 23.89 | 106.67 | 23.89 |
August | 72.33 | 23.84 | 436.33 | 23.88 | 64.67 | 23.88 |
September | 114.83 | 23.20 | 263.17 | 23.68 | 33.33 | 23.70 |
October | 421.33 | 21.71 | 25.67 | 21.76 | 12.17 | 21.74 |
November | 478.33 | 21.25 | 62.17 | 21.21 | 62.17 | 21.18 |
December | 496.00 | 21.05 | 372.83 | 21.04 | 372.83 | 21.04 |
Annual Sum or Average | 4048.67 | 21.57 | 3083.50 | 21.94 | 1850.33 | 21.84 |
Minimum of Months | 72.33 | 21.05 | 25.67 | 21.04 | 2.17 | 21.04 |
Maximum of Months | 496.00 | 23.89 | 467.67 | 23.89 | 437.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.29 | 288.00 | 21.23 | 288.00 | 21.20 |
February | 448.00 | 21.27 | 267.67 | 21.21 | 267.67 | 21.19 |
March | 465.83 | 21.58 | 76.83 | 21.53 | 73.50 | 21.48 |
April | 456.17 | 22.09 | 8.50 | 22.07 | 8.50 | 22.06 |
May | 251.33 | 23.06 | 58.00 | 23.22 | 0.00 | 23.22 |
June | 76.50 | 23.61 | 277.50 | 23.81 | 34.67 | 23.82 |
July | 62.33 | 23.88 | 451.17 | 23.86 | 62.00 | 23.86 |
August | 32.83 | 23.85 | 410.33 | 23.87 | 30.67 | 23.87 |
September | 68.67 | 23.51 | 280.83 | 23.80 | 21.00 | 23.81 |
October | 365.83 | 22.29 | 25.67 | 22.40 | 0.17 | 22.40 |
November | 470.33 | 21.80 | 7.00 | 21.79 | 7.00 | 21.78 |
December | 496.00 | 21.35 | 205.17 | 21.28 | 205.17 | 21.25 |
Annual Sum or Average | 3689.83 | 21.87 | 2356.67 | 22.26 | 998.33 | 22.16 |
Minimum of Months | 32.83 | 21.27 | 7.00 | 21.21 | 0.00 | 21.19 |
Maximum of Months | 496.00 | 23.88 | 451.17 | 23.87 | 288.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 295.83 | 21.11 | 295.83 | 21.11 |
February | 336.00 | 21.11 | 259.50 | 21.11 | 259.50 | 21.11 |
March | 358.00 | 21.23 | 106.17 | 21.21 | 104.33 | 21.19 |
April | 352.67 | 21.57 | 15.50 | 21.55 | 15.50 | 21.53 |
May | 215.33 | 22.59 | 43.00 | 22.82 | 0.00 | 22.82 |
June | 74.67 | 23.60 | 232.50 | 23.93 | 37.33 | 23.94 |
July | 79.50 | 24.10 | 351.33 | 24.05 | 79.17 | 24.06 |
August | 42.00 | 24.15 | 345.17 | 24.04 | 38.83 | 24.05 |
September | 73.50 | 23.34 | 213.33 | 23.82 | 25.00 | 23.84 |
October | 300.50 | 21.78 | 14.00 | 21.84 | 3.33 | 21.84 |
November | 357.67 | 21.29 | 20.67 | 21.28 | 20.67 | 21.27 |
December | 369.00 | 21.11 | 224.00 | 21.11 | 224.00 | 21.11 |
Annual Sum or Average | 2929.83 | 21.62 | 2121.00 | 22.10 | 1103.50 | 22.01 |
Minimum of Months | 42.00 | 21.11 | 14.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.15 | 351.33 | 24.05 | 295.83 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 308.33 | 21.11 | 308.33 | 21.11 |
February | 336.00 | 21.11 | 268.83 | 21.11 | 268.83 | 21.11 |
March | 359.17 | 21.22 | 117.17 | 21.20 | 116.00 | 21.19 |
April | 355.83 | 21.54 | 20.17 | 21.52 | 20.17 | 21.50 |
May | 224.33 | 22.51 | 37.17 | 22.71 | 0.00 | 22.71 |
June | 77.17 | 23.60 | 231.67 | 23.92 | 38.33 | 23.93 |
July | 79.50 | 24.10 | 351.50 | 24.05 | 79.17 | 24.06 |
August | 42.33 | 24.14 | 344.83 | 24.03 | 39.00 | 24.05 |
September | 76.67 | 23.31 | 210.33 | 23.80 | 25.83 | 23.82 |
October | 310.67 | 21.77 | 13.50 | 21.82 | 4.50 | 21.81 |
November | 360.00 | 21.28 | 26.17 | 21.27 | 26.17 | 21.26 |
December | 369.00 | 21.11 | 234.83 | 21.11 | 234.83 | 21.11 |
Annual Sum or Average | 2961.67 | 21.62 | 2164.50 | 22.08 | 1161.17 | 21.98 |
Minimum of Months | 42.33 | 21.11 | 13.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.14 | 351.50 | 24.05 | 308.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 320.33 | 21.11 | 320.33 | 21.11 |
February | 336.00 | 21.11 | 285.67 | 21.11 | 285.67 | 21.11 |
March | 360.67 | 21.21 | 135.83 | 21.18 | 135.83 | 21.17 |
April | 357.17 | 21.47 | 27.50 | 21.45 | 27.50 | 21.42 |
May | 243.50 | 22.40 | 27.00 | 22.54 | 1.00 | 22.53 |
June | 84.17 | 23.55 | 225.67 | 23.89 | 41.33 | 23.91 |
July | 82.83 | 24.09 | 349.17 | 24.05 | 82.33 | 24.06 |
August | 44.83 | 24.11 | 340.50 | 24.03 | 40.33 | 24.04 |
September | 85.17 | 23.24 | 199.83 | 23.75 | 26.67 | 23.78 |
October | 323.00 | 21.73 | 13.67 | 21.77 | 5.67 | 21.76 |
November | 360.00 | 21.25 | 34.83 | 21.24 | 34.83 | 21.23 |
December | 369.00 | 21.11 | 255.00 | 21.11 | 255.00 | 21.11 |
Annual Sum or Average | 3017.33 | 21.61 | 2215.00 | 22.03 | 1256.50 | 21.94 |
Minimum of Months | 44.83 | 21.11 | 13.67 | 21.11 | 1.00 | 21.11 |
Maximum of Months | 371.00 | 24.11 | 349.17 | 24.05 | 320.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 319.50 | 21.11 | 319.50 | 21.11 |
February | 308.00 | 21.11 | 302.67 | 21.11 | 302.67 | 21.11 |
March | 341.17 | 21.27 | 170.33 | 21.21 | 170.33 | 21.19 |
April | 330.00 | 21.39 | 37.33 | 21.36 | 37.33 | 21.34 |
May | 266.33 | 22.34 | 11.00 | 22.38 | 4.67 | 22.38 |
June | 101.00 | 23.53 | 184.33 | 23.80 | 50.17 | 23.82 |
July | 78.17 | 23.98 | 318.17 | 23.96 | 78.00 | 23.96 |
August | 55.00 | 23.90 | 291.67 | 23.93 | 50.17 | 23.93 |
September | 88.83 | 23.15 | 168.67 | 23.65 | 31.83 | 23.67 |
October | 310.00 | 21.66 | 11.50 | 21.68 | 6.33 | 21.67 |
November | 330.00 | 21.22 | 74.67 | 21.20 | 74.67 | 21.19 |
December | 338.00 | 21.11 | 299.33 | 21.11 | 299.33 | 21.11 |
Annual Sum or Average | 2886.50 | 21.62 | 2189.17 | 21.95 | 1425.00 | 21.86 |
Minimum of Months | 55.00 | 21.11 | 11.00 | 21.11 | 4.67 | 21.11 |
Maximum of Months | 341.17 | 23.98 | 319.50 | 23.96 | 319.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 318.67 | 21.11 | 318.67 | 21.11 |
February | 308.00 | 21.11 | 302.67 | 21.11 | 302.67 | 21.11 |
March | 342.33 | 21.27 | 174.33 | 21.22 | 174.33 | 21.19 |
April | 330.00 | 21.38 | 41.50 | 21.35 | 41.50 | 21.32 |
May | 292.17 | 22.42 | 9.00 | 22.42 | 5.83 | 22.42 |
June | 106.00 | 23.54 | 169.67 | 23.79 | 51.17 | 23.81 |
July | 79.33 | 23.98 | 315.33 | 23.95 | 79.00 | 23.96 |
August | 57.83 | 23.89 | 278.33 | 23.93 | 51.33 | 23.93 |
September | 91.83 | 23.16 | 150.33 | 23.63 | 32.33 | 23.66 |
October | 316.17 | 21.68 | 11.17 | 21.69 | 7.33 | 21.68 |
November | 330.00 | 21.21 | 78.83 | 21.19 | 78.83 | 21.18 |
December | 338.00 | 21.11 | 298.17 | 21.11 | 298.17 | 21.11 |
Annual Sum or Average | 2931.67 | 21.65 | 2148.00 | 21.93 | 1441.17 | 21.85 |
Minimum of Months | 57.83 | 21.11 | 9.00 | 21.11 | 5.83 | 21.11 |
Maximum of Months | 342.33 | 23.98 | 318.67 | 23.95 | 318.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 320.00 | 21.11 | 320.00 | 21.11 |
February | 308.00 | 21.11 | 303.00 | 21.11 | 303.00 | 21.11 |
March | 343.33 | 21.28 | 180.33 | 21.22 | 180.33 | 21.19 |
April | 330.00 | 21.36 | 48.33 | 21.32 | 48.33 | 21.30 |
May | 304.17 | 22.39 | 8.33 | 22.39 | 6.83 | 22.38 |
June | 111.67 | 23.52 | 167.00 | 23.77 | 53.17 | 23.80 |
July | 80.00 | 23.98 | 313.67 | 23.95 | 79.50 | 23.96 |
August | 60.00 | 23.88 | 274.67 | 23.93 | 52.67 | 23.93 |
September | 95.00 | 23.14 | 147.50 | 23.61 | 32.50 | 23.64 |
October | 320.00 | 21.67 | 12.00 | 21.68 | 8.50 | 21.67 |
November | 330.00 | 21.21 | 88.50 | 21.19 | 88.50 | 21.17 |
December | 338.00 | 21.11 | 302.00 | 21.11 | 302.00 | 21.11 |
Annual Sum or Average | 2960.17 | 21.65 | 2165.33 | 21.92 | 1475.33 | 21.84 |
Minimum of Months | 60.00 | 21.11 | 8.33 | 21.11 | 6.83 | 21.11 |
Maximum of Months | 343.33 | 23.98 | 320.00 | 23.95 | 320.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 325.33 | 21.11 | 325.33 | 21.11 |
February | 308.00 | 21.11 | 303.83 | 21.11 | 303.83 | 21.11 |
March | 344.50 | 21.27 | 199.83 | 21.21 | 199.83 | 21.18 |
April | 330.00 | 21.31 | 63.83 | 21.28 | 63.83 | 21.25 |
May | 318.17 | 22.27 | 8.67 | 22.25 | 8.67 | 22.24 |
June | 122.67 | 23.44 | 162.00 | 23.72 | 56.17 | 23.75 |
July | 83.00 | 23.97 | 310.83 | 23.95 | 82.17 | 23.96 |
August | 65.83 | 23.85 | 267.50 | 23.92 | 56.67 | 23.92 |
September | 105.00 | 23.06 | 140.00 | 23.55 | 33.67 | 23.59 |
October | 326.50 | 21.64 | 13.83 | 21.64 | 11.33 | 21.62 |
November | 330.00 | 21.19 | 109.67 | 21.17 | 109.67 | 21.16 |
December | 338.00 | 21.11 | 312.50 | 21.11 | 312.50 | 21.11 |
Annual Sum or Average | 3011.67 | 21.64 | 2217.83 | 21.89 | 1563.67 | 21.81 |
Minimum of Months | 65.83 | 21.11 | 8.67 | 21.11 | 8.67 | 21.11 |
Maximum of Months | 344.50 | 23.97 | 325.33 | 23.95 | 325.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 335.17 | 21.11 | 335.17 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.27 | 265.83 | 21.20 | 265.83 | 21.17 |
April | 330.00 | 21.24 | 127.50 | 21.20 | 127.50 | 21.18 |
May | 339.50 | 22.10 | 19.33 | 22.05 | 19.33 | 22.01 |
June | 152.00 | 23.30 | 149.83 | 23.61 | 59.33 | 23.65 |
July | 89.00 | 23.96 | 310.33 | 23.95 | 86.83 | 23.95 |
August | 79.50 | 23.77 | 266.33 | 23.90 | 62.50 | 23.90 |
September | 122.50 | 22.89 | 128.83 | 23.41 | 33.33 | 23.47 |
October | 331.33 | 21.57 | 31.50 | 21.53 | 31.00 | 21.50 |
November | 330.00 | 21.17 | 186.33 | 21.15 | 186.33 | 21.14 |
December | 338.00 | 21.11 | 328.67 | 21.11 | 328.67 | 21.11 |
Annual Sum or Average | 3107.83 | 21.63 | 2457.67 | 21.84 | 1843.83 | 21.75 |
Minimum of Months | 79.50 | 21.11 | 19.33 | 21.11 | 19.33 | 21.11 |
Maximum of Months | 348.00 | 23.96 | 335.17 | 23.95 | 335.17 | 23.95 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.05560 | 16.66694 | -0.6616 | 14.48296 |
February | 448.00000 | 21.04678 | 16.61314 | -0.6672 | 14.63705 |
March | 497.00000 | 21.27874 | 25.78627 | -0.4692 | 11.06106 |
April | 479.00000 | 21.45734 | 31.62929 | -0.3381 | 8.30568 |
May | 496.00000 | 22.85823 | 36.60157 | -0.9314 | 25.70540 |
June | 481.00000 | 23.77818 | 46.64161 | -0.4663 | 10.34617 |
July | 495.00000 | 23.88735 | 55.77582 | -0.3160 | 7.23419 |
August | 497.00000 | 23.87702 | 50.62685 | -0.3608 | 7.92635 |
September | 479.00000 | 23.71195 | 46.74018 | -0.4912 | 10.98118 |
October | 496.00000 | 22.03100 | 36.68740 | -0.1181 | 7.22590 |
November | 480.00000 | 21.25595 | 29.44354 | -0.4076 | 9.11193 |
December | 496.00000 | 21.04959 | 20.18193 | -0.6212 | 13.40727 |
Annual Sum or Average | 5840.00000 | 22.28101 | 34.54861 | -0.4866 | 11.70055 |
Minimum of Months | 448.00000 | 21.04678 | 16.61314 | -0.9314 | 7.22590 |
Maximum of Months | 497.00000 | 23.88735 | 55.77582 | -0.1181 | 25.70540 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.29318 | 19.05287 | -0.5312 | 11.25629 |
February | 448.00000 | 21.26690 | 18.71681 | -0.5408 | 11.40712 |
March | 497.00000 | 21.72268 | 27.24259 | -0.3173 | 8.67643 |
April | 479.00000 | 22.17537 | 32.58878 | -0.1493 | 6.74025 |
May | 496.00000 | 23.45775 | 35.74111 | -0.7228 | 17.34963 |
June | 481.00000 | 23.81669 | 45.27900 | -0.4465 | 9.60258 |
July | 495.00000 | 23.84629 | 53.38963 | -0.3382 | 7.56649 |
August | 497.00000 | 23.84691 | 49.03478 | -0.3755 | 8.13429 |
September | 479.00000 | 23.81287 | 45.65677 | -0.4535 | 9.70661 |
October | 496.00000 | 22.70206 | 36.94011 | 0.04055 | 6.73937 |
November | 480.00000 | 21.83717 | 30.83975 | -0.2484 | 7.31695 |
December | 496.00000 | 21.34670 | 22.28012 | -0.4880 | 10.40909 |
Annual Sum or Average | 5840.00000 | 22.60107 | 34.81777 | -0.3802 | 9.57430 |
Minimum of Months | 448.00000 | 21.26690 | 18.71681 | -0.7228 | 6.73937 |
Maximum of Months | 497.00000 | 23.84691 | 53.38963 | 0.04055 | 17.34963 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10972 | 15.92148 | -0.6025 | 12.77446 |
February | 336.00000 | 21.11005 | 15.88555 | -0.6023 | 12.75998 |
March | 379.00000 | 21.37688 | 24.86141 | -0.4029 | 9.79692 |
April | 360.00000 | 21.61654 | 30.55604 | -0.2740 | 7.51728 |
May | 375.00000 | 23.15417 | 35.22336 | -0.8149 | 21.09328 |
June | 366.00000 | 23.90675 | 45.62079 | -0.4200 | 9.40581 |
July | 369.00000 | 24.03490 | 54.71874 | -0.2757 | 6.93255 |
August | 379.00000 | 24.00259 | 49.53980 | -0.3265 | 7.56068 |
September | 360.00000 | 23.81306 | 45.76904 | -0.4529 | 10.05906 |
October | 371.00000 | 22.17187 | 35.70726 | -0.0730 | 7.00758 |
November | 360.00000 | 21.30995 | 29.15444 | -0.3678 | 8.42236 |
December | 369.00000 | 21.10988 | 19.67698 | -0.5654 | 11.88275 |
Annual Sum or Average | 4395.00000 | 22.40424 | 33.67929 | -0.4308 | 10.43456 |
Minimum of Months | 336.00000 | 21.10972 | 15.88555 | -0.8149 | 6.93255 |
Maximum of Months | 379.00000 | 24.03490 | 54.71874 | -0.0730 | 21.09328 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10979 | 15.92128 | -0.6144 | 13.07722 |
February | 336.00000 | 21.10970 | 15.88574 | -0.6132 | 13.04106 |
March | 379.00000 | 21.36392 | 24.89921 | -0.4154 | 9.97834 |
April | 360.00000 | 21.56578 | 30.64474 | -0.2941 | 7.68078 |
May | 375.00000 | 23.06985 | 35.39004 | -0.8508 | 22.51808 |
June | 366.00000 | 23.90177 | 45.65841 | -0.4236 | 9.48995 |
July | 369.00000 | 24.03454 | 54.72382 | -0.2756 | 6.93092 |
August | 379.00000 | 24.00172 | 49.54877 | -0.3267 | 7.56505 |
September | 360.00000 | 23.80027 | 45.83615 | -0.4596 | 10.24151 |
October | 371.00000 | 22.10503 | 35.87285 | -0.0957 | 7.03071 |
November | 360.00000 | 21.28309 | 29.21343 | -0.3840 | 8.62208 |
December | 369.00000 | 21.10995 | 19.67697 | -0.5767 | 12.15742 |
Annual Sum or Average | 4395.00000 | 22.38234 | 33.73267 | -0.4434 | 10.69578 |
Minimum of Months | 336.00000 | 21.10970 | 15.88574 | -0.8508 | 6.93092 |
Maximum of Months | 379.00000 | 24.03454 | 54.72382 | -0.0957 | 22.51808 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10981 | 15.92166 | -0.6296 | 13.47975 |
February | 336.00000 | 21.10986 | 15.88584 | -0.6281 | 13.43566 |
March | 379.00000 | 21.34256 | 24.96136 | -0.4332 | 10.24577 |
April | 360.00000 | 21.49275 | 30.77197 | -0.3210 | 7.91915 |
May | 375.00000 | 22.92632 | 35.69144 | -0.9084 | 24.78783 |
June | 366.00000 | 23.88123 | 45.83937 | -0.4371 | 9.79847 |
July | 369.00000 | 24.02923 | 54.93115 | -0.2823 | 6.99927 |
August | 379.00000 | 23.99423 | 49.70157 | -0.3345 | 7.67276 |
September | 360.00000 | 23.76708 | 46.02745 | -0.4765 | 10.68947 |
October | 371.00000 | 22.00635 | 36.11969 | -0.1261 | 7.05903 |
November | 360.00000 | 21.25235 | 29.28401 | -0.4027 | 8.86960 |
December | 369.00000 | 21.10952 | 19.67795 | -0.5918 | 12.53282 |
Annual Sum or Average | 4395.00000 | 22.34588 | 33.86224 | -0.4636 | 11.12777 |
Minimum of Months | 336.00000 | 21.10952 | 15.88584 | -0.9084 | 6.99927 |
Maximum of Months | 379.00000 | 24.02923 | 54.93115 | -0.1261 | 24.78783 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.36775 | -0.6732 | 14.66343 |
February | 308.00000 | 21.10995 | 17.28988 | -0.6713 | 14.60346 |
March | 348.00000 | 21.31791 | 26.56704 | -0.4737 | 10.95234 |
April | 330.00000 | 21.39273 | 32.43991 | -0.3678 | 8.43492 |
May | 344.00000 | 22.68358 | 37.47680 | -1.0106 | 28.84694 |
June | 336.00000 | 23.80435 | 47.16782 | -0.4755 | 10.53172 |
July | 338.00000 | 23.94387 | 56.07284 | -0.3149 | 7.29576 |
August | 348.00000 | 23.91261 | 50.88322 | -0.3671 | 8.07537 |
September | 330.00000 | 23.69375 | 47.42561 | -0.5131 | 11.53955 |
October | 340.00000 | 21.85331 | 37.91435 | -0.1773 | 7.18062 |
November | 330.00000 | 21.21904 | 30.77617 | -0.4441 | 9.53397 |
December | 338.00000 | 21.11000 | 21.07251 | -0.6352 | 13.64541 |
Annual Sum or Average | 4030.00000 | 22.27297 | 35.33528 | -0.5098 | 12.11523 |
Minimum of Months | 308.00000 | 21.10995 | 17.28988 | -1.0106 | 7.18062 |
Maximum of Months | 348.00000 | 23.94387 | 56.07284 | -0.1773 | 28.84694 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10990 | 17.27181 | -0.6682 | 14.51767 |
February | 308.00000 | 21.11000 | 17.19309 | -0.6669 | 14.47344 |
March | 348.00000 | 21.31515 | 26.48280 | -0.4775 | 10.99844 |
April | 330.00000 | 21.37632 | 32.37633 | -0.3796 | 8.57603 |
May | 344.00000 | 22.63540 | 37.49645 | -1.0433 | 30.18598 |
June | 336.00000 | 23.79998 | 47.18253 | -0.4969 | 10.97950 |
July | 338.00000 | 23.94283 | 56.13639 | -0.3372 | 7.59203 |
August | 348.00000 | 23.91229 | 50.89320 | -0.3887 | 8.40653 |
September | 330.00000 | 23.69208 | 47.40905 | -0.5317 | 11.94893 |
October | 340.00000 | 21.83403 | 37.87059 | -0.1916 | 7.24078 |
November | 330.00000 | 21.21296 | 30.69563 | -0.4500 | 9.62062 |
December | 338.00000 | 21.10970 | 20.97589 | -0.6317 | 13.54294 |
Annual Sum or Average | 4030.00000 | 22.26450 | 35.29666 | -0.5215 | 12.35071 |
Minimum of Months | 308.00000 | 21.10970 | 17.19309 | -1.0433 | 7.24078 |
Maximum of Months | 348.00000 | 23.94283 | 56.13639 | -0.1916 | 30.18598 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.27182 | -0.6714 | 14.60850 |
February | 308.00000 | 21.11000 | 17.19336 | -0.6700 | 14.55809 |
March | 348.00000 | 21.31042 | 26.50011 | -0.4836 | 11.10656 |
April | 330.00000 | 21.35640 | 32.41146 | -0.3894 | 8.70589 |
May | 344.00000 | 22.56378 | 37.67038 | -1.0739 | 31.47659 |
June | 336.00000 | 23.78704 | 47.28707 | -0.5063 | 11.23457 |
July | 338.00000 | 23.94207 | 56.21033 | -0.3407 | 7.64192 |
August | 348.00000 | 23.91025 | 50.94831 | -0.3926 | 8.47545 |
September | 330.00000 | 23.67720 | 47.49425 | -0.5406 | 12.21332 |
October | 340.00000 | 21.80002 | 37.96188 | -0.2035 | 7.28794 |
November | 330.00000 | 21.20739 | 30.70967 | -0.4561 | 9.72214 |
December | 338.00000 | 21.10982 | 20.97571 | -0.6351 | 13.63313 |
Annual Sum or Average | 4030.00000 | 22.25051 | 35.35139 | -0.5299 | 12.56789 |
Minimum of Months | 308.00000 | 21.10982 | 17.19336 | -1.0739 | 7.28794 |
Maximum of Months | 348.00000 | 23.94207 | 56.21033 | -0.2035 | 31.47659 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.27203 | -0.6862 | 15.03406 |
February | 308.00000 | 21.10993 | 17.19371 | -0.6839 | 14.95890 |
March | 348.00000 | 21.29644 | 26.55126 | -0.5039 | 11.50898 |
April | 330.00000 | 21.30863 | 32.49478 | -0.4158 | 9.09655 |
May | 344.00000 | 22.39317 | 38.07493 | -1.1433 | 34.51142 |
June | 336.00000 | 23.74468 | 47.57526 | -0.5299 | 11.94421 |
July | 338.00000 | 23.93997 | 56.40538 | -0.3452 | 7.70926 |
August | 348.00000 | 23.90336 | 51.10279 | -0.3986 | 8.59948 |
September | 330.00000 | 23.63060 | 47.74485 | -0.5628 | 12.93451 |
October | 340.00000 | 21.72592 | 38.15907 | -0.2294 | 7.44231 |
November | 330.00000 | 21.19167 | 30.74918 | -0.4737 | 10.03736 |
December | 338.00000 | 21.11000 | 20.97548 | -0.6495 | 14.02594 |
Annual Sum or Average | 4030.00000 | 22.21517 | 35.49130 | -0.5516 | 13.16658 |
Minimum of Months | 308.00000 | 21.10993 | 17.19371 | -1.1433 | 7.44231 |
Maximum of Months | 348.00000 | 23.93997 | 56.40538 | -0.2294 | 34.51142 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.07172 | -0.7578 | 17.25300 |
February | 308.00000 | 21.11000 | 17.02955 | -0.7534 | 17.09605 |
March | 348.00000 | 21.27282 | 26.44557 | -0.5781 | 13.26948 |
April | 330.00000 | 21.23929 | 32.39811 | -0.4877 | 10.43198 |
May | 344.00000 | 22.12229 | 38.65088 | -1.2760 | 40.72301 |
June | 336.00000 | 23.63965 | 48.05929 | -0.5845 | 13.77322 |
July | 338.00000 | 23.93826 | 56.76022 | -0.3440 | 7.71566 |
August | 348.00000 | 23.88049 | 51.38565 | -0.4042 | 8.83215 |
September | 330.00000 | 23.51444 | 48.13859 | -0.6126 | 14.77822 |
October | 340.00000 | 21.62394 | 38.24930 | -0.2827 | 8.03343 |
November | 330.00000 | 21.16735 | 30.64142 | -0.5309 | 11.24791 |
December | 338.00000 | 21.11000 | 20.81315 | -0.7169 | 16.00654 |
Annual Sum or Average | 4030.00000 | 22.15336 | 35.60593 | -0.6104 | 14.94792 |
Minimum of Months | 308.00000 | 21.11000 | 17.02955 | -1.2760 | 7.71566 |
Maximum of Months | 348.00000 | 23.93826 | 56.76022 | -0.2827 | 40.72301 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.332848E+09 | 91770809.71 | 17.58 | 0.282388E+09 | 50460051.12 | 0.00 | 0.52 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 9054.45 | 15-MAR-14:00 | 8337.50 | 15-MAR-14:00 | 1670.25 | 14-MAR-13:30 | 2468.55 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 1263991.51 | 362841.02 | 1.33 | 1123893.19 | 140098.32 | 0.00 | 0.05 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 779.68 | 08-APR-13:00 | 703.09 | 08-APR-13:00 | 76.58 | 08-APR-13:00 | 222.43 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.103763E+10 | 0.280047E+09 | 76.25 | 0.920211E+09 | 0.117424E+09 | 0.00 | 0.63 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11715.00 | 14-MAY-15:00 | 9247.78 | 14-MAY-15:00 | 2739.51 | 14-MAY-16:10 | 3054.93 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.968329E+10 | 0.243624E+10 | 319.61 | 0.697662E+10 | 0.270668E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 45390.06 | 18-JUN-07:03 | 23718.71 | 12-JUN-07:03 | 22755.07 | 18-JUN-07:03 | 9717.48 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.206609E+11 | 0.506907E+10 | 476.98 | 0.137352E+11 | 0.692576E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 46383.58 | 21-JUL-07:02 | 27096.43 | 20-JUL-07:02 | 24655.57 | 22-JUL-07:02 | 9998.00 | 21-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.161819E+11 | 0.405229E+10 | 438.34 | 0.120287E+11 | 0.415322E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 45429.07 | 14-AUG-07:02 | 30889.52 | 06-AUG-07:02 | 22127.86 | 15-AUG-07:02 | 9719.33 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.620222E+10 | 0.157073E+10 | 262.43 | 0.430869E+10 | 0.189352E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 44164.95 | 17-SEP-07:02 | 24919.04 | 17-SEP-07:02 | 19245.91 | 17-SEP-07:02 | 9497.19 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.220356E+09 | 59707239.40 | 22.03 | 0.190702E+09 | 29654420.00 | 0.00 | 0.39 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 6507.33 | 11-OCT-16:10 | 5586.40 | 11-OCT-16:10 | 949.27 | 11-OCT-17:10 | 1715.16 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.543205E+11 | 0.135602E+11 | 1614.56 | 0.384436E+11 | 0.158768E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.206609E+11 | 0.506907E+10 | 476.98 | 0.137352E+11 | 0.692576E+10 | 0.00 | 1.00 | 0.00 | 46383.58 | 30889.52 | 24655.57 | 9998.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.245842E+09 | 64595805.33 | 21.15 | 0.209210E+09 | 36632378.79 | 0.00 | 1.00 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 | 21562.83 | 15-MAR-20:01 | 17966.21 | 15-MAR-20:09 | 4069.10 | 15-MAR-20:40 | 4591.56 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 |
April | 14241491.80 | 3896190.91 | 5.89 | 13006071.29 | 1235420.52 | 0.00 | 0.36 | 23-APR-17:10 | 0.00 | 01-APR-00:05 | 3050.75 | 23-APR-17:10 | 3050.75 | 23-APR-17:10 | 313.86 | 09-APR-20:10 | 785.76 | 23-APR-17:10 | 0.00 | 01-APR-00:05 |
May | 0.928966E+09 | 0.234782E+09 | 95.88 | 0.832853E+09 | 96112932.58 | 0.00 | 1.00 | 13-MAY-18:01 | 0.00 | 01-MAY-00:10 | 22177.41 | 14-MAY-17:55 | 20622.51 | 27-MAY-19:10 | 7519.62 | 14-MAY-17:55 | 4717.13 | 14-MAY-17:55 | 0.00 | 01-MAY-00:10 |
June | 0.637751E+10 | 0.153242E+10 | 324.19 | 0.469816E+10 | 0.167935E+10 | 0.00 | 1.00 | 01-JUN-20:02 | 0.00 | 01-JUN-00:10 | 24027.91 | 18-JUN-07:03 | 20947.93 | 10-JUN-18:02 | 12491.92 | 07-JUN-20:10 | 5076.30 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.125342E+11 | 0.295586E+10 | 444.82 | 0.853274E+10 | 0.400151E+10 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:05 | 23952.98 | 21-JUL-20:05 | 18923.62 | 06-JUL-20:01 | 12453.42 | 28-JUL-20:03 | 5218.11 | 21-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.996606E+10 | 0.239463E+10 | 415.46 | 0.747983E+10 | 0.248623E+10 | 0.00 | 1.00 | 01-AUG-20:02 | 0.00 | 01-AUG-00:10 | 23859.87 | 15-AUG-07:02 | 20161.72 | 03-AUG-20:02 | 12711.21 | 28-AUG-20:03 | 5040.89 | 15-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.413062E+10 | 0.999958E+09 | 267.66 | 0.291418E+10 | 0.121643E+10 | 0.00 | 1.00 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 | 23824.67 | 15-SEP-20:03 | 18810.09 | 07-SEP-20:01 | 12420.46 | 15-SEP-20:03 | 4996.86 | 15-SEP-20:03 | 0.00 | 01-SEP-00:10 |
October | 0.231440E+09 | 58901110.77 | 35.79 | 0.196374E+09 | 35066227.71 | 0.00 | 1.00 | 22-OCT-17:02 | 0.00 | 01-OCT-00:10 | 21550.43 | 22-OCT-17:02 | 17629.71 | 22-OCT-17:02 | 5195.94 | 22-OCT-18:30 | 4588.84 | 22-OCT-17:02 | 0.00 | 01-OCT-00:10 |
November | 2294584.69 | 636172.61 | 1.25 | 2017658.26 | 276926.43 | 0.00 | 0.17 | 05-NOV-17:20 | 0.00 | 01-NOV-00:10 | 1455.91 | 05-NOV-17:20 | 1122.82 | 05-NOV-17:20 | 333.09 | 05-NOV-17:20 | 396.19 | 05-NOV-17:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.344312E+11 | 0.824568E+10 | 1612.09 | 0.248784E+11 | 0.955285E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125342E+11 | 0.295586E+10 | 444.82 | 0.853274E+10 | 0.400151E+10 | 0.00 | 1.00 | 0.00 | 24027.91 | 20947.93 | 12711.21 | 5218.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.188728E+09 | 50826107.82 | 17.83 | 0.162108E+09 | 26619333.90 | 0.00 | 0.53 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4973.18 | 15-MAR-14:00 | 4645.06 | 15-MAR-14:00 | 959.14 | 14-MAR-13:00 | 1327.74 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 5149341.09 | 1426409.74 | 2.17 | 4596672.43 | 552668.66 | 0.00 | 0.14 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 1161.11 | 08-APR-13:00 | 1059.35 | 08-APR-13:00 | 101.76 | 08-APR-13:00 | 318.10 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.596123E+09 | 0.157000E+09 | 73.58 | 0.536084E+09 | 60038671.12 | 0.00 | 0.60 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5901.41 | 14-MAY-15:00 | 4754.66 | 10-MAY-14:00 | 1368.63 | 14-MAY-14:00 | 1527.01 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.423207E+10 | 0.104582E+10 | 257.22 | 0.312343E+10 | 0.110864E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24332.71 | 18-JUN-07:03 | 13484.42 | 26-JUN-06:03 | 12122.36 | 18-JUN-07:03 | 5109.62 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.856180E+10 | 0.206176E+10 | 348.58 | 0.584739E+10 | 0.271441E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24789.21 | 21-JUL-06:02 | 16028.77 | 15-JUL-06:02 | 13473.21 | 29-JUL-06:03 | 5227.37 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.691832E+10 | 0.170197E+10 | 333.18 | 0.530249E+10 | 0.161583E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24578.83 | 14-AUG-06:02 | 16904.62 | 06-AUG-07:02 | 13563.01 | 14-AUG-06:04 | 5091.83 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.282253E+10 | 0.700745E+09 | 224.60 | 0.201727E+10 | 0.805260E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23783.23 | 16-SEP-06:03 | 13464.30 | 17-SEP-07:02 | 11766.29 | 14-SEP-06:03 | 4995.25 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.108329E+09 | 28888429.97 | 22.08 | 95591668.47 | 12737096.33 | 0.00 | 0.38 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3383.24 | 11-OCT-15:00 | 3068.45 | 11-OCT-13:00 | 444.10 | 11-OCT-16:10 | 885.23 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.234331E+11 | 0.574844E+10 | 1279.24 | 0.170890E+11 | 0.634409E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.856180E+10 | 0.206176E+10 | 348.58 | 0.584739E+10 | 0.271441E+10 | 0.00 | 1.00 | 0.00 | 24789.21 | 16904.62 | 13563.01 | 5227.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.176590E+09 | 47801189.83 | 16.67 | 0.151872E+09 | 24718543.12 | 0.00 | 0.52 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4797.81 | 15-MAR-14:00 | 4479.02 | 15-MAR-14:00 | 902.19 | 14-MAR-13:00 | 1287.42 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 3572385.47 | 994578.41 | 2.00 | 3194446.53 | 377938.95 | 0.00 | 0.12 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 948.96 | 08-APR-13:00 | 865.71 | 08-APR-13:00 | 83.24 | 08-APR-13:00 | 261.69 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.554890E+09 | 0.146760E+09 | 71.08 | 0.499142E+09 | 55748191.69 | 0.00 | 0.58 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5668.49 | 14-MAY-15:00 | 4549.22 | 14-MAY-15:00 | 1319.15 | 14-MAY-14:00 | 1475.88 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.419517E+10 | 0.103758E+10 | 254.06 | 0.309448E+10 | 0.110069E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24400.89 | 18-JUN-07:03 | 13443.71 | 26-JUN-06:03 | 12160.71 | 18-JUN-07:03 | 5124.04 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.856559E+10 | 0.206356E+10 | 348.74 | 0.585005E+10 | 0.271554E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24864.69 | 21-JUL-06:02 | 16081.58 | 15-JUL-06:02 | 13513.02 | 29-JUL-06:03 | 5242.17 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.691910E+10 | 0.170292E+10 | 333.38 | 0.530417E+10 | 0.161494E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24649.33 | 14-AUG-06:02 | 16963.06 | 06-AUG-07:02 | 13595.08 | 14-AUG-06:04 | 5106.26 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.277380E+10 | 0.689236E+09 | 221.93 | 0.198043E+10 | 0.793369E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23851.04 | 16-SEP-06:03 | 13504.76 | 17-SEP-07:02 | 11805.08 | 14-SEP-06:03 | 5009.38 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 90653657.89 | 24298649.89 | 18.67 | 80284073.80 | 10369584.09 | 0.00 | 0.35 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3078.28 | 11-OCT-15:00 | 2768.86 | 11-OCT-13:00 | 406.20 | 11-OCT-16:10 | 812.59 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.232794E+11 | 0.571315E+10 | 1266.52 | 0.169636E+11 | 0.631575E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.856559E+10 | 0.206356E+10 | 348.74 | 0.585005E+10 | 0.271554E+10 | 0.00 | 1.00 | 0.00 | 24864.69 | 16963.06 | 13595.08 | 5242.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.159014E+09 | 43337631.12 | 15.92 | 0.136799E+09 | 22215256.29 | 0.00 | 0.49 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4500.46 | 15-MAR-14:00 | 4195.20 | 15-MAR-14:00 | 833.09 | 14-MAR-13:00 | 1216.25 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 1501730.92 | 421837.43 | 1.33 | 1345221.11 | 156509.81 | 0.00 | 0.07 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 590.84 | 08-APR-13:00 | 538.23 | 08-APR-13:00 | 52.61 | 08-APR-13:00 | 164.71 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.484314E+09 | 0.128932E+09 | 64.67 | 0.434920E+09 | 49394277.98 | 0.00 | 0.55 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5344.01 | 14-MAY-15:00 | 4272.55 | 14-MAY-15:00 | 1253.39 | 14-MAY-14:00 | 1401.33 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.401139E+10 | 0.994597E+09 | 245.06 | 0.295325E+10 | 0.105814E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24223.47 | 18-JUN-07:03 | 12173.26 | 27-JUN-06:03 | 12124.23 | 18-JUN-07:03 | 5087.70 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.831700E+10 | 0.200840E+10 | 346.96 | 0.567271E+10 | 0.264430E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24674.28 | 21-JUL-06:02 | 15917.24 | 15-JUL-06:02 | 13459.41 | 29-JUL-06:03 | 5205.19 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.670781E+10 | 0.165510E+10 | 330.26 | 0.514049E+10 | 0.156732E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24471.65 | 14-AUG-06:02 | 16801.15 | 06-AUG-07:02 | 13484.24 | 14-AUG-06:02 | 5070.16 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.261946E+10 | 0.652503E+09 | 212.52 | 0.186546E+10 | 0.753999E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23680.10 | 16-SEP-06:03 | 13369.43 | 17-SEP-07:02 | 11764.89 | 14-SEP-06:03 | 4973.66 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 73671776.99 | 19886712.95 | 13.42 | 65274603.70 | 8397173.29 | 0.00 | 0.31 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 2715.70 | 11-OCT-16:10 | 2407.30 | 11-OCT-13:00 | 361.34 | 11-OCT-16:10 | 721.68 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.223742E+11 | 0.550317E+10 | 1230.12 | 0.162703E+11 | 0.610391E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.831700E+10 | 0.200840E+10 | 346.96 | 0.567271E+10 | 0.264430E+10 | 0.00 | 1.00 | 0.00 | 24674.28 | 16801.15 | 13484.24 | 5205.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.252995E+09 | 70534241.75 | 14.67 | 0.211607E+09 | 41388483.34 | 0.00 | 0.48 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 7986.45 | 15-MAR-14:10 | 7227.50 | 15-MAR-14:10 | 1620.89 | 14-MAR-13:00 | 2196.91 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 773212.73 | 222671.37 | 1.17 | 677302.86 | 95909.86 | 0.00 | 0.02 | 08-APR-13:20 | 0.00 | 01-APR-00:05 | 276.28 | 08-APR-13:20 | 243.02 | 08-APR-13:20 | 34.85 | 08-APR-13:30 | 79.49 | 08-APR-13:20 | 0.00 | 01-APR-00:05 |
May | 0.743167E+09 | 0.202769E+09 | 57.08 | 0.656372E+09 | 86795839.52 | 0.00 | 0.58 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10208.27 | 14-MAY-15:00 | 7874.93 | 14-MAY-15:00 | 2485.42 | 14-MAY-14:20 | 2698.57 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.694136E+10 | 0.175256E+10 | 229.56 | 0.499705E+10 | 0.194431E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 43799.28 | 18-JUN-08:62 | 23849.78 | 18-JUN-08:62 | 20803.15 | 27-JUN-07:03 | 9453.28 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.147723E+11 | 0.363065E+10 | 338.86 | 0.988985E+10 | 0.488245E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:05 | 44342.39 | 16-JUL-08:62 | 26827.51 | 20-JUL-07:02 | 24564.92 | 29-JUL-07:03 | 9625.85 | 21-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.119063E+11 | 0.299236E+10 | 323.38 | 0.897447E+10 | 0.293182E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 44381.70 | 14-AUG-07:02 | 30968.80 | 06-AUG-08:62 | 21427.34 | 14-AUG-07:04 | 9380.63 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.438048E+10 | 0.111184E+10 | 196.08 | 0.306392E+10 | 0.131656E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 42564.04 | 17-SEP-08:62 | 23218.21 | 17-SEP-08:62 | 19345.83 | 17-SEP-08:62 | 9111.55 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.103463E+09 | 28614941.94 | 10.50 | 90267930.39 | 13195213.68 | 0.00 | 0.31 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4911.14 | 11-OCT-15:00 | 4270.09 | 11-OCT-15:00 | 641.06 | 11-OCT-15:00 | 1332.52 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.391008E+11 | 0.978955E+10 | 1171.29 | 0.278842E+11 | 0.112166E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.147723E+11 | 0.363065E+10 | 338.86 | 0.988985E+10 | 0.488245E+10 | 0.00 | 1.00 | 0.00 | 44381.70 | 30968.80 | 24564.92 | 9625.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.124433E+09 | 34182904.79 | 14.50 | 0.104477E+09 | 19955613.89 | 0.00 | 0.47 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4053.87 | 15-MAR-14:10 | 3675.15 | 15-MAR-14:10 | 784.02 | 14-MAR-13:00 | 1098.70 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.353967E+09 | 95213222.38 | 53.50 | 0.312831E+09 | 41135937.84 | 0.00 | 0.56 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5172.07 | 14-MAY-15:00 | 3991.02 | 14-MAY-15:00 | 1248.66 | 14-MAY-14:20 | 1348.13 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.351799E+10 | 0.874399E+09 | 225.85 | 0.253766E+10 | 0.980329E+09 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 22761.96 | 18-JUN-08:62 | 12366.26 | 18-JUN-08:62 | 10395.69 | 18-JUN-08:62 | 4826.84 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.755170E+10 | 0.182758E+10 | 337.27 | 0.506925E+10 | 0.248245E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:05 | 23048.05 | 16-JUL-08:62 | 13942.93 | 20-JUL-07:02 | 11934.17 | 22-JUL-07:02 | 4914.92 | 21-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.608769E+10 | 0.150620E+10 | 319.91 | 0.460050E+10 | 0.148718E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23072.25 | 14-AUG-07:02 | 15621.33 | 06-AUG-08:62 | 11039.80 | 14-AUG-07:02 | 4789.93 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.221693E+10 | 0.553494E+09 | 190.62 | 0.155214E+10 | 0.664791E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 22124.09 | 17-SEP-08:62 | 12085.43 | 17-SEP-08:62 | 10038.66 | 17-SEP-08:62 | 4652.70 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 49161462.44 | 13394442.40 | 10.33 | 42981705.32 | 6179757.12 | 0.00 | 0.30 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2459.30 | 11-OCT-15:00 | 2143.35 | 11-OCT-15:00 | 315.95 | 11-OCT-15:00 | 657.44 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.199019E+11 | 0.490446E+10 | 1151.99 | 0.142198E+11 | 0.568203E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.755170E+10 | 0.182758E+10 | 337.27 | 0.506925E+10 | 0.248245E+10 | 0.00 | 1.00 | 0.00 | 23072.25 | 15621.33 | 11934.17 | 4914.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.119733E+09 | 32954926.27 | 14.17 | 0.100492E+09 | 19240939.90 | 0.00 | 0.46 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3963.87 | 15-MAR-14:10 | 3589.86 | 15-MAR-14:10 | 758.94 | 14-MAR-13:00 | 1076.57 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.326727E+09 | 88178358.60 | 50.75 | 0.288122E+09 | 38605263.90 | 0.00 | 0.55 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5035.36 | 14-MAY-15:00 | 3877.46 | 14-MAY-15:00 | 1220.53 | 14-MAY-14:30 | 1316.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.343934E+10 | 0.855765E+09 | 222.64 | 0.247637E+10 | 0.962967E+09 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 22656.56 | 18-JUN-08:62 | 12241.96 | 18-JUN-08:62 | 10414.61 | 18-JUN-08:62 | 4805.83 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.746039E+10 | 0.180678E+10 | 337.35 | 0.500270E+10 | 0.245768E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:05 | 22944.71 | 16-JUL-08:62 | 13834.11 | 20-JUL-07:02 | 11897.01 | 22-JUL-07:02 | 4893.78 | 21-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.601246E+10 | 0.148869E+10 | 318.39 | 0.454106E+10 | 0.147140E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22968.38 | 14-AUG-07:02 | 15069.98 | 06-AUG-08:62 | 11032.97 | 14-AUG-07:02 | 4769.24 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.216531E+10 | 0.541031E+09 | 187.49 | 0.151358E+10 | 0.651727E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 22027.72 | 17-SEP-08:62 | 12019.39 | 17-SEP-08:62 | 10008.32 | 17-SEP-08:62 | 4632.57 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 45616307.34 | 12458969.79 | 9.83 | 39852004.98 | 5764302.36 | 0.00 | 0.29 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2351.07 | 11-OCT-15:00 | 2047.08 | 11-OCT-15:00 | 303.99 | 11-OCT-15:00 | 630.40 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.195696E+11 | 0.482585E+10 | 1140.61 | 0.139622E+11 | 0.560739E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.746039E+10 | 0.180678E+10 | 337.35 | 0.500270E+10 | 0.245768E+10 | 0.00 | 1.00 | 0.00 | 22968.38 | 15069.98 | 11897.01 | 4893.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.105798E+09 | 29299445.00 | 13.33 | 88871083.06 | 16926553.43 | 0.00 | 0.44 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3707.38 | 15-MAR-14:10 | 3352.97 | 15-MAR-14:10 | 670.08 | 14-MAR-13:00 | 1013.66 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.268398E+09 | 73010639.39 | 45.25 | 0.235527E+09 | 32871006.37 | 0.00 | 0.52 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4688.84 | 14-MAY-15:00 | 3595.53 | 14-MAY-15:00 | 1143.90 | 14-MAY-14:30 | 1236.15 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.324969E+10 | 0.810830E+09 | 213.06 | 0.233200E+10 | 0.917694E+09 | 0.00 | 1.00 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 | 21230.57 | 18-JUN-08:62 | 11261.98 | 18-JUN-08:62 | 9968.60 | 18-JUN-08:62 | 4508.52 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.725936E+10 | 0.176109E+10 | 334.25 | 0.486316E+10 | 0.239620E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:05 | 22765.24 | 16-JUL-08:62 | 13592.62 | 20-JUL-07:02 | 11843.16 | 22-JUL-07:02 | 4858.85 | 21-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.584989E+10 | 0.145063E+10 | 312.89 | 0.441962E+10 | 0.143027E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22786.83 | 14-AUG-07:02 | 13418.71 | 06-AUG-08:62 | 11079.72 | 14-AUG-07:02 | 4734.87 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.203832E+10 | 0.510276E+09 | 176.76 | 0.142068E+10 | 0.617637E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 21866.80 | 17-SEP-08:62 | 11902.17 | 17-SEP-08:62 | 9964.63 | 17-SEP-08:62 | 4599.16 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 38287774.60 | 10508874.25 | 9.50 | 33448274.93 | 4839499.67 | 0.00 | 0.27 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2130.22 | 11-OCT-15:00 | 1853.37 | 11-OCT-15:00 | 276.85 | 11-OCT-15:00 | 574.82 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.188097E+11 | 0.464565E+10 | 1105.04 | 0.133933E+11 | 0.541643E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.725936E+10 | 0.176109E+10 | 334.25 | 0.486316E+10 | 0.239620E+10 | 0.00 | 1.00 | 0.00 | 22786.83 | 13592.62 | 11843.16 | 4858.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 86546419.77 | 24244341.83 | 12.50 | 73417438.30 | 13128981.46 | 0.00 | 0.40 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3438.82 | 15-MAR-14:10 | 3123.77 | 15-MAR-14:10 | 526.93 | 14-MAR-13:00 | 951.51 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.190705E+09 | 52631861.86 | 38.33 | 0.166139E+09 | 24565402.48 | 0.00 | 0.46 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4194.63 | 14-MAY-15:00 | 3210.51 | 14-MAY-15:00 | 1017.96 | 14-MAY-14:30 | 1125.98 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.308558E+10 | 0.773950E+09 | 198.62 | 0.222049E+10 | 0.865097E+09 | 0.00 | 1.00 | 27-JUN-11:50 | 0.00 | 01-JUN-00:10 | 13253.06 | 27-JUN-13:00 | 8395.32 | 27-JUN-13:00 | 5341.76 | 18-JUN-08:62 | 3117.83 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.724618E+10 | 0.176507E+10 | 327.42 | 0.490067E+10 | 0.234551E+10 | 0.00 | 1.00 | 15-JUL-13:20 | 0.00 | 01-JUL-00:05 | 24070.25 | 21-JUL-07:02 | 12505.05 | 20-JUL-07:02 | 13102.03 | 21-JUL-07:03 | 5053.09 | 21-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.588224E+10 | 0.146108E+10 | 300.14 | 0.449348E+10 | 0.138876E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23818.78 | 14-AUG-07:02 | 12583.94 | 07-AUG-07:02 | 12391.80 | 14-AUG-07:02 | 4927.65 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.191288E+10 | 0.480012E+09 | 155.14 | 0.134109E+10 | 0.571784E+09 | 0.00 | 1.00 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18375.56 | 17-SEP-08:62 | 9775.52 | 17-SEP-08:62 | 8600.04 | 17-SEP-08:62 | 3864.55 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 35007573.50 | 9643032.01 | 8.83 | 30889993.02 | 4117580.47 | 0.00 | 0.24 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2025.11 | 11-OCT-15:00 | 1774.43 | 11-OCT-15:00 | 250.68 | 11-OCT-15:00 | 549.61 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.184391E+11 | 0.456663E+10 | 1040.98 | 0.132262E+11 | 0.521296E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.724618E+10 | 0.176507E+10 | 327.42 | 0.490067E+10 | 0.234551E+10 | 0.00 | 1.00 | 0.00 | 24070.25 | 12583.94 | 13102.03 | 5053.09 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.25 | 95.46 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.83 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.99 | 66.61 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.87 | 50.88 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.21 | 35.05 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.89 | 23.72 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.39 | 16.00 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.22 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.91 | 34.73 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.45 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.99 | 64.35 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 93.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.33 | 53.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.91 | 95.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.25 | 95.46 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.83 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.99 | 66.61 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.87 | 50.88 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.21 | 35.05 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.89 | 23.72 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.39 | 16.00 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.22 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.91 | 34.73 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.45 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.99 | 64.35 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 93.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.33 | 53.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.91 | 95.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.25 | 95.46 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.83 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.99 | 66.61 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.87 | 50.88 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.21 | 35.05 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.89 | 23.72 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.39 | 16.00 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.22 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.91 | 34.73 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.45 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.99 | 64.35 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 93.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.33 | 53.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.91 | 95.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.25 | 95.46 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.83 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.99 | 66.61 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.87 | 50.88 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.21 | 35.05 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.89 | 23.72 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.39 | 16.00 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.22 | 21.44 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.91 | 34.73 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.45 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.99 | 64.35 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 93.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.33 | 53.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.91 | 95.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.25 | 54.43 | 38.82 | 78.99 | 113.03 | 0.00 | 0.00 | 0.00 |
February | 106.47 | 51.34 | 55.13 | 89.58 | 109.21 | 0.00 | 0.00 | 0.00 |
March | 129.95 | 73.02 | 56.93 | 135.28 | 79.04 | 0.00 | 0.00 | 0.00 |
April | 107.62 | 43.01 | 64.62 | 118.10 | 60.39 | 0.00 | 0.00 | 0.00 |
May | 94.18 | 27.35 | 66.83 | 111.14 | 41.71 | 0.00 | 0.00 | 0.00 |
June | 91.51 | 19.39 | 72.12 | 117.83 | 28.31 | 0.00 | 0.00 | 0.00 |
July | 93.42 | 22.67 | 70.75 | 132.68 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 104.88 | 34.00 | 70.87 | 145.74 | 25.61 | 0.00 | 0.00 | 0.00 |
September | 121.94 | 59.39 | 62.55 | 156.31 | 41.43 | 0.00 | 0.00 | 0.00 |
October | 116.68 | 66.65 | 50.03 | 131.95 | 60.26 | 0.00 | 0.00 | 0.00 |
November | 83.56 | 47.17 | 36.39 | 83.32 | 76.33 | 0.00 | 0.00 | 0.00 |
December | 77.98 | 40.36 | 37.62 | 62.54 | 110.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.76 | 44.88 | 56.88 | 113.76 | 63.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.98 | 19.39 | 36.39 | 62.54 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.95 | 73.02 | 72.12 | 156.31 | 113.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.25 | 54.43 | 38.82 | 78.99 | 113.03 | 0.00 | 0.00 | 0.00 |
February | 106.47 | 51.34 | 55.13 | 89.58 | 109.21 | 0.00 | 0.00 | 0.00 |
March | 129.95 | 73.02 | 56.93 | 135.28 | 79.04 | 0.00 | 0.00 | 0.00 |
April | 107.62 | 43.01 | 64.62 | 118.10 | 60.39 | 0.00 | 0.00 | 0.00 |
May | 94.18 | 27.35 | 66.83 | 111.14 | 41.71 | 0.00 | 0.00 | 0.00 |
June | 91.51 | 19.39 | 72.12 | 117.83 | 28.31 | 0.00 | 0.00 | 0.00 |
July | 93.42 | 22.67 | 70.75 | 132.68 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 104.88 | 34.00 | 70.87 | 145.74 | 25.61 | 0.00 | 0.00 | 0.00 |
September | 121.94 | 59.39 | 62.55 | 156.31 | 41.43 | 0.00 | 0.00 | 0.00 |
October | 116.68 | 66.65 | 50.03 | 131.95 | 60.26 | 0.00 | 0.00 | 0.00 |
November | 83.56 | 47.17 | 36.39 | 83.32 | 76.33 | 0.00 | 0.00 | 0.00 |
December | 77.98 | 40.36 | 37.62 | 62.54 | 110.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.76 | 44.88 | 56.88 | 113.76 | 63.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.98 | 19.39 | 36.39 | 62.54 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.95 | 73.02 | 72.12 | 156.31 | 113.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.20 | 100.01 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.42 | 96.86 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.40 | 70.71 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.16 | 55.15 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 90.33 | 38.04 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.21 | 24.50 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.12 | 16.34 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.98 | 21.79 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.31 | 35.72 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.14 | 54.03 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.00 | 68.45 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.70 | 98.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.28 | 56.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.70 | 16.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.31 | 100.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.20 | 100.01 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.42 | 96.86 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.40 | 70.71 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.16 | 55.15 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 90.33 | 38.04 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.21 | 24.50 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.12 | 16.34 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.98 | 21.79 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.31 | 35.72 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.14 | 54.03 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.00 | 68.45 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.70 | 98.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.28 | 56.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.70 | 16.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.31 | 100.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.25 | 54.43 | 38.82 | 77.74 | 118.37 | 0.00 | 0.00 | 0.00 |
February | 106.47 | 51.34 | 55.13 | 87.92 | 114.51 | 0.00 | 0.00 | 0.00 |
March | 129.95 | 73.02 | 56.93 | 133.40 | 83.86 | 0.00 | 0.00 | 0.00 |
April | 107.62 | 43.01 | 64.62 | 116.08 | 65.40 | 0.00 | 0.00 | 0.00 |
May | 94.18 | 27.35 | 66.83 | 108.92 | 45.23 | 0.00 | 0.00 | 0.00 |
June | 91.51 | 19.39 | 72.12 | 117.03 | 29.22 | 0.00 | 0.00 | 0.00 |
July | 93.42 | 22.67 | 70.75 | 132.38 | 19.53 | 0.00 | 0.00 | 0.00 |
August | 104.88 | 34.00 | 70.87 | 145.47 | 26.03 | 0.00 | 0.00 | 0.00 |
September | 121.94 | 59.39 | 62.55 | 155.62 | 42.59 | 0.00 | 0.00 | 0.00 |
October | 116.68 | 66.65 | 50.03 | 130.42 | 64.20 | 0.00 | 0.00 | 0.00 |
November | 83.56 | 47.17 | 36.39 | 82.15 | 81.12 | 0.00 | 0.00 | 0.00 |
December | 77.98 | 40.36 | 37.62 | 61.48 | 116.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.76 | 44.88 | 56.88 | 112.53 | 66.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.98 | 19.39 | 36.39 | 61.48 | 19.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.95 | 73.02 | 72.12 | 155.62 | 118.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.37 | 97.66 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.60 | 94.57 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.61 | 68.93 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.53 | 53.40 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 90.66 | 37.53 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.03 | 25.52 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.67 | 17.78 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.72 | 23.23 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.32 | 36.54 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.56 | 52.62 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.31 | 66.38 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.86 | 96.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.39 | 55.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.86 | 17.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.32 | 97.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.37 | 97.66 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.60 | 94.57 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.61 | 68.93 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.53 | 53.40 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 90.66 | 37.53 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.03 | 25.52 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.67 | 17.78 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.72 | 23.23 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.32 | 36.54 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.56 | 52.62 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.31 | 66.38 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.86 | 96.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.39 | 55.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.86 | 17.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.32 | 97.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 77.53 | 114.96 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 87.66 | 111.20 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 132.92 | 81.31 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 115.89 | 63.00 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 108.72 | 44.38 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.18 | 30.25 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.14 | 21.11 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.37 | 27.56 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 154.78 | 43.31 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 130.21 | 62.19 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 82.07 | 78.26 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 61.34 | 113.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 112.04 | 65.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 61.34 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 154.78 | 114.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.49 | 96.64 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.75 | 93.62 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.80 | 68.14 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.80 | 52.53 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 91.01 | 36.81 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.08 | 25.42 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.66 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.72 | 23.25 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.38 | 36.35 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.84 | 51.78 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.49 | 65.47 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.96 | 95.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.54 | 55.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.96 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.38 | 96.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.49 | 96.64 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.75 | 93.62 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 110.80 | 68.14 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 96.80 | 52.53 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 91.01 | 36.81 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.08 | 25.42 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.66 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.72 | 23.25 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.38 | 36.35 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 108.84 | 51.78 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.49 | 65.47 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 50.96 | 95.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.54 | 55.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 50.96 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.38 | 96.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 77.67 | 113.76 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 87.84 | 110.09 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 133.15 | 80.37 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 116.22 | 61.98 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 109.13 | 43.54 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.24 | 30.13 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.13 | 21.14 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.37 | 27.58 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 154.86 | 43.08 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 130.54 | 61.20 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 82.29 | 77.18 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 61.47 | 111.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 112.22 | 64.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 61.47 | 21.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 154.86 | 113.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.65 | 95.78 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.95 | 92.82 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.06 | 67.42 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.15 | 51.74 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 91.54 | 35.94 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.27 | 25.09 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.79 | 17.55 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.83 | 22.97 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.54 | 35.95 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.19 | 50.99 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.70 | 64.71 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.10 | 94.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.77 | 54.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.10 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.54 | 95.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.65 | 95.78 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 72.95 | 92.82 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.06 | 67.42 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.15 | 51.74 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 91.54 | 35.94 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.27 | 25.09 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.79 | 17.55 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.83 | 22.97 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.54 | 35.95 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.19 | 50.99 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 68.70 | 64.71 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.10 | 94.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 93.77 | 54.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.10 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.54 | 95.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 77.87 | 112.74 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 88.09 | 109.14 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 133.47 | 79.53 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 116.63 | 61.05 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 109.77 | 42.51 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.47 | 29.74 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.28 | 20.85 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.50 | 27.26 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.05 | 42.61 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 130.95 | 60.27 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 82.54 | 76.29 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 61.64 | 110.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 112.50 | 64.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 61.64 | 20.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.05 | 112.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.34 | 92.89 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.94 | 90.00 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.09 | 65.30 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.03 | 49.83 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.59 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.87 | 16.77 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.91 | 22.13 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.83 | 34.97 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.96 | 49.35 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.33 | 62.72 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.73 | 91.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.39 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.73 | 16.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.83 | 92.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.34 | 92.89 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.94 | 90.00 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.09 | 65.30 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.03 | 49.83 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.59 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.87 | 16.77 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.91 | 22.13 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.83 | 34.97 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.96 | 49.35 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.33 | 62.72 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.73 | 91.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.39 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.73 | 16.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.83 | 92.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.34 | 92.89 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.94 | 90.00 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.09 | 65.30 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.03 | 49.83 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.59 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.87 | 16.77 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.91 | 22.13 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.83 | 34.97 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.96 | 49.35 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.33 | 62.72 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.73 | 91.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.39 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.73 | 16.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.83 | 92.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.34 | 92.89 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.94 | 90.00 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.09 | 65.30 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.03 | 49.83 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.59 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.87 | 16.77 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.91 | 22.13 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.83 | 34.97 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.96 | 49.35 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.33 | 62.72 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.73 | 91.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.39 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.73 | 16.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.83 | 92.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 78.68 | 109.40 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 89.22 | 105.88 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 134.65 | 77.07 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 117.66 | 58.83 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 110.97 | 40.40 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.84 | 28.64 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.36 | 19.93 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.59 | 26.27 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.37 | 41.46 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 131.85 | 58.36 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 83.28 | 73.98 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 62.37 | 107.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 113.21 | 62.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 62.37 | 19.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.37 | 109.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 78.68 | 109.40 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 89.22 | 105.88 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 134.65 | 77.07 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 117.66 | 58.83 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 110.97 | 40.40 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.84 | 28.64 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.36 | 19.93 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.59 | 26.27 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.37 | 41.46 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 131.85 | 58.36 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 83.28 | 73.98 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 62.37 | 107.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 113.21 | 62.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 62.37 | 19.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.37 | 109.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.98 | 93.59 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.43 | 90.71 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.67 | 65.53 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.79 | 49.84 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 33.86 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.56 | 23.96 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.88 | 16.55 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.87 | 21.90 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.70 | 34.79 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.78 | 49.25 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.11 | 62.92 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.40 | 92.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.18 | 52.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.40 | 16.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.70 | 93.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 64.98 | 93.59 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.43 | 90.71 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.67 | 65.53 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.79 | 49.84 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.58 | 33.86 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.56 | 23.96 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.88 | 16.55 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.87 | 21.90 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.70 | 34.79 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.78 | 49.25 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.11 | 62.92 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.40 | 92.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.18 | 52.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.40 | 16.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.70 | 93.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 78.28 | 110.16 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 88.67 | 106.66 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 134.21 | 77.30 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 117.42 | 58.81 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 111.01 | 40.05 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 116.82 | 28.41 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.40 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.56 | 25.99 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.25 | 41.24 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 131.67 | 58.22 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 83.04 | 74.17 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 62.01 | 108.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 113.00 | 62.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 62.01 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.25 | 110.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.02 | 93.38 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.48 | 90.53 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.77 | 65.26 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.94 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.89 | 33.41 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.71 | 23.77 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.96 | 16.44 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.93 | 21.79 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.80 | 34.60 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.93 | 48.93 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.19 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.44 | 91.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.29 | 52.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.44 | 16.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.80 | 93.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.02 | 93.38 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.48 | 90.53 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 111.77 | 65.26 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 97.94 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 92.89 | 33.41 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 97.71 | 23.77 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 109.96 | 16.44 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 120.93 | 21.79 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 129.80 | 34.60 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 109.93 | 48.93 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.19 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.44 | 91.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.29 | 52.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.44 | 16.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 129.80 | 93.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 78.33 | 109.91 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 88.73 | 106.44 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 134.33 | 76.98 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 117.59 | 58.42 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 111.38 | 39.53 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 117.00 | 28.19 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.50 | 19.54 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.64 | 25.86 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.37 | 41.02 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 131.84 | 57.84 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 83.14 | 73.85 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 62.05 | 108.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 113.13 | 61.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 62.05 | 19.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.37 | 109.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.20 | 92.26 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.70 | 89.51 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.11 | 64.15 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.35 | 48.41 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 93.61 | 32.28 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 98.09 | 23.25 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.10 | 16.20 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.05 | 21.53 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 130.04 | 34.08 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 110.27 | 48.09 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.42 | 61.69 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 90.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.58 | 51.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 130.04 | 92.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.20 | 92.26 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 73.70 | 89.51 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 112.11 | 64.15 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 98.35 | 48.41 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 93.61 | 32.28 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 98.09 | 23.25 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.10 | 16.20 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.05 | 21.53 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 130.04 | 34.08 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 110.27 | 48.09 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 69.42 | 61.69 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 51.59 | 90.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 94.58 | 51.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 51.59 | 16.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 130.04 | 92.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 78.54 | 108.59 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 88.99 | 105.24 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 134.74 | 75.67 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 118.09 | 57.12 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 112.24 | 38.20 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 117.45 | 27.58 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.67 | 19.25 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 144.78 | 25.56 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 155.66 | 40.40 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 132.25 | 56.85 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 83.42 | 72.72 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 62.24 | 106.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 113.48 | 60.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 62.24 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 155.66 | 108.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.98 | 87.36 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 74.65 | 84.89 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 113.34 | 59.56 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 99.54 | 44.25 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 95.17 | 28.98 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 99.03 | 21.40 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.36 | 15.25 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.26 | 20.53 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 130.60 | 32.27 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 111.04 | 45.40 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 70.15 | 58.11 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 52.25 | 85.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 95.40 | 48.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 52.25 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 130.60 | 87.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.57 | 45.28 | 32.29 | 65.98 | 87.36 | 0.00 | 0.00 | 0.00 |
February | 88.57 | 42.71 | 45.86 | 74.65 | 84.89 | 0.00 | 0.00 | 0.00 |
March | 108.10 | 60.74 | 47.36 | 113.34 | 59.56 | 0.00 | 0.00 | 0.00 |
April | 89.52 | 35.77 | 53.75 | 99.54 | 44.25 | 0.00 | 0.00 | 0.00 |
May | 78.34 | 22.75 | 55.59 | 95.17 | 28.98 | 0.00 | 0.00 | 0.00 |
June | 76.12 | 16.13 | 59.99 | 99.03 | 21.40 | 0.00 | 0.00 | 0.00 |
July | 77.71 | 18.85 | 58.85 | 110.36 | 15.25 | 0.00 | 0.00 | 0.00 |
August | 87.24 | 28.29 | 58.96 | 121.26 | 20.53 | 0.00 | 0.00 | 0.00 |
September | 101.44 | 49.41 | 52.03 | 130.60 | 32.27 | 0.00 | 0.00 | 0.00 |
October | 97.06 | 55.44 | 41.62 | 111.04 | 45.40 | 0.00 | 0.00 | 0.00 |
November | 69.51 | 39.24 | 30.27 | 70.15 | 58.11 | 0.00 | 0.00 | 0.00 |
December | 64.86 | 33.57 | 31.29 | 52.25 | 85.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.64 | 37.33 | 47.32 | 95.40 | 48.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.86 | 16.13 | 30.27 | 52.25 | 15.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.10 | 60.74 | 59.99 | 130.60 | 87.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.74 | 54.14 | 38.61 | 79.50 | 102.80 | 0.00 | 0.00 | 0.00 |
February | 105.89 | 51.06 | 54.83 | 90.16 | 99.78 | 0.00 | 0.00 | 0.00 |
March | 129.24 | 72.62 | 56.62 | 136.23 | 70.26 | 0.00 | 0.00 | 0.00 |
April | 107.03 | 42.77 | 64.26 | 119.52 | 52.22 | 0.00 | 0.00 | 0.00 |
May | 93.66 | 27.20 | 66.46 | 114.10 | 34.32 | 0.00 | 0.00 | 0.00 |
June | 91.01 | 19.29 | 71.73 | 118.58 | 25.40 | 0.00 | 0.00 | 0.00 |
July | 92.91 | 22.54 | 70.37 | 131.97 | 18.13 | 0.00 | 0.00 | 0.00 |
August | 104.30 | 33.82 | 70.49 | 145.03 | 24.38 | 0.00 | 0.00 | 0.00 |
September | 121.28 | 59.07 | 62.21 | 156.32 | 38.27 | 0.00 | 0.00 | 0.00 |
October | 116.04 | 66.29 | 49.76 | 133.18 | 53.69 | 0.00 | 0.00 | 0.00 |
November | 83.11 | 46.92 | 36.19 | 84.30 | 68.51 | 0.00 | 0.00 | 0.00 |
December | 77.55 | 40.14 | 37.41 | 63.05 | 101.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.20 | 44.63 | 56.57 | 114.47 | 57.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.55 | 19.29 | 36.19 | 63.05 | 18.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.24 | 72.62 | 71.73 | 156.32 | 102.80 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174762E+09 | 0.255673E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178609E+09 | 0.223373E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299967E+09 | 0.178399E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253677E+09 | 0.131869E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.246984E+09 | 93881747.26 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253737E+09 | 61485158.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295658E+09 | 42865762.36 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324688E+09 | 57417739.96 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336720E+09 | 90029506.32 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.293142E+09 | 0.135706E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178833E+09 | 0.166801E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138171E+09 | 0.251182E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297495E+10 | 0.168868E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138171E+09 | 42865762.36 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336720E+09 | 0.255673E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174762E+09 | 0.255673E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178609E+09 | 0.223373E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299967E+09 | 0.178399E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253677E+09 | 0.131869E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.246984E+09 | 93881747.26 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253737E+09 | 61485158.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295658E+09 | 42865762.36 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324688E+09 | 57417739.96 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336720E+09 | 90029506.32 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.293142E+09 | 0.135706E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178833E+09 | 0.166801E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138171E+09 | 0.251182E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297495E+10 | 0.168868E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138171E+09 | 42865762.36 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336720E+09 | 0.255673E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174762E+09 | 0.255673E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178609E+09 | 0.223373E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299967E+09 | 0.178399E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253677E+09 | 0.131869E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.246984E+09 | 93881747.26 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253737E+09 | 61485158.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295658E+09 | 42865762.36 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324688E+09 | 57417739.96 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336720E+09 | 90029506.32 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.293142E+09 | 0.135706E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178833E+09 | 0.166801E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138171E+09 | 0.251182E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297495E+10 | 0.168868E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138171E+09 | 42865762.36 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336720E+09 | 0.255673E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174762E+09 | 0.255673E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178609E+09 | 0.223373E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299967E+09 | 0.178399E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253677E+09 | 0.131869E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.246984E+09 | 93881747.26 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253737E+09 | 61485158.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295658E+09 | 42865762.36 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324688E+09 | 57417739.96 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336720E+09 | 90029506.32 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.293142E+09 | 0.135706E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178833E+09 | 0.166801E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138171E+09 | 0.251182E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297495E+10 | 0.168868E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138171E+09 | 42865762.36 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336720E+09 | 0.255673E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249766E+09 | 0.145796E+09 | 0.103970E+09 | 0.211573E+09 | 0.302743E+09 |
February | 0.257573E+09 | 0.124200E+09 | 0.133374E+09 | 0.216709E+09 | 0.264196E+09 |
March | 0.348069E+09 | 0.195578E+09 | 0.152491E+09 | 0.362333E+09 | 0.211697E+09 |
April | 0.278958E+09 | 0.111472E+09 | 0.167485E+09 | 0.306128E+09 | 0.156534E+09 |
May | 0.252250E+09 | 73263937.44 | 0.178986E+09 | 0.297682E+09 | 0.111722E+09 |
June | 0.237199E+09 | 50263599.25 | 0.186935E+09 | 0.305403E+09 | 73373773.43 |
July | 0.250213E+09 | 60709826.51 | 0.189503E+09 | 0.355383E+09 | 51268122.09 |
August | 0.280905E+09 | 91076491.96 | 0.189829E+09 | 0.390355E+09 | 68594997.21 |
September | 0.316073E+09 | 0.153951E+09 | 0.162122E+09 | 0.405145E+09 | 0.107381E+09 |
October | 0.312517E+09 | 0.178515E+09 | 0.134001E+09 | 0.353406E+09 | 0.161388E+09 |
November | 0.216598E+09 | 0.122277E+09 | 94321138.41 | 0.215968E+09 | 0.197846E+09 |
December | 0.208854E+09 | 0.108091E+09 | 0.100763E+09 | 0.167501E+09 | 0.297119E+09 |
Annual Sum or Average | 0.320897E+10 | 0.141519E+10 | 0.179378E+10 | 0.358759E+10 | 0.200386E+10 |
Minimum of Months | 0.208854E+09 | 50263599.25 | 94321138.41 | 0.167501E+09 | 51268122.09 |
Maximum of Months | 0.348069E+09 | 0.195578E+09 | 0.189829E+09 | 0.405145E+09 | 0.302743E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249766E+09 | 0.145796E+09 | 0.103970E+09 | 0.211573E+09 | 0.302743E+09 |
February | 0.257573E+09 | 0.124200E+09 | 0.133374E+09 | 0.216709E+09 | 0.264196E+09 |
March | 0.348069E+09 | 0.195578E+09 | 0.152491E+09 | 0.362333E+09 | 0.211697E+09 |
April | 0.278958E+09 | 0.111472E+09 | 0.167485E+09 | 0.306128E+09 | 0.156534E+09 |
May | 0.252250E+09 | 73263937.44 | 0.178986E+09 | 0.297682E+09 | 0.111722E+09 |
June | 0.237199E+09 | 50263599.25 | 0.186935E+09 | 0.305403E+09 | 73373773.43 |
July | 0.250213E+09 | 60709826.51 | 0.189503E+09 | 0.355383E+09 | 51268122.09 |
August | 0.280905E+09 | 91076491.96 | 0.189829E+09 | 0.390355E+09 | 68594997.21 |
September | 0.316073E+09 | 0.153951E+09 | 0.162122E+09 | 0.405145E+09 | 0.107381E+09 |
October | 0.312517E+09 | 0.178515E+09 | 0.134001E+09 | 0.353406E+09 | 0.161388E+09 |
November | 0.216598E+09 | 0.122277E+09 | 94321138.41 | 0.215968E+09 | 0.197846E+09 |
December | 0.208854E+09 | 0.108091E+09 | 0.100763E+09 | 0.167501E+09 | 0.297119E+09 |
Annual Sum or Average | 0.320897E+10 | 0.141519E+10 | 0.179378E+10 | 0.358759E+10 | 0.200386E+10 |
Minimum of Months | 0.208854E+09 | 50263599.25 | 94321138.41 | 0.167501E+09 | 51268122.09 |
Maximum of Months | 0.348069E+09 | 0.195578E+09 | 0.189829E+09 | 0.405145E+09 | 0.302743E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.171944E+09 | 0.267876E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.175202E+09 | 0.234316E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.295695E+09 | 0.189398E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.249242E+09 | 0.142936E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.241945E+09 | 0.101892E+09 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251962E+09 | 63495883.13 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294939E+09 | 43756872.67 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324022E+09 | 58368260.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335167E+09 | 92585633.47 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.289640E+09 | 0.144727E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.176253E+09 | 0.177429E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.135789E+09 | 0.263640E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294180E+10 | 0.178042E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.135789E+09 | 43756872.67 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335167E+09 | 0.267876E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.171944E+09 | 0.267876E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.175202E+09 | 0.234316E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.295695E+09 | 0.189398E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.249242E+09 | 0.142936E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.241945E+09 | 0.101892E+09 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251962E+09 | 63495883.13 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294939E+09 | 43756872.67 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324022E+09 | 58368260.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335167E+09 | 92585633.47 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.289640E+09 | 0.144727E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.176253E+09 | 0.177429E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.135789E+09 | 0.263640E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294180E+10 | 0.178042E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.135789E+09 | 43756872.67 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335167E+09 | 0.267876E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249766E+09 | 0.145796E+09 | 0.103970E+09 | 0.208225E+09 | 0.317050E+09 |
February | 0.257573E+09 | 0.124200E+09 | 0.133374E+09 | 0.212696E+09 | 0.277013E+09 |
March | 0.348069E+09 | 0.195578E+09 | 0.152491E+09 | 0.357302E+09 | 0.224599E+09 |
April | 0.278958E+09 | 0.111472E+09 | 0.167485E+09 | 0.300891E+09 | 0.169506E+09 |
May | 0.252250E+09 | 73263937.44 | 0.178986E+09 | 0.291738E+09 | 0.121145E+09 |
June | 0.237199E+09 | 50263599.25 | 0.186935E+09 | 0.303336E+09 | 75737573.52 |
July | 0.250213E+09 | 60709826.51 | 0.189503E+09 | 0.354572E+09 | 52317875.15 |
August | 0.280905E+09 | 91076491.96 | 0.189829E+09 | 0.389620E+09 | 69710895.97 |
September | 0.316073E+09 | 0.153951E+09 | 0.162122E+09 | 0.403363E+09 | 0.110383E+09 |
October | 0.312517E+09 | 0.178515E+09 | 0.134001E+09 | 0.349309E+09 | 0.171947E+09 |
November | 0.216598E+09 | 0.122277E+09 | 94321138.41 | 0.212928E+09 | 0.210275E+09 |
December | 0.208854E+09 | 0.108091E+09 | 0.100763E+09 | 0.164663E+09 | 0.311687E+09 |
Annual Sum or Average | 0.320897E+10 | 0.141519E+10 | 0.179378E+10 | 0.354864E+10 | 0.211137E+10 |
Minimum of Months | 0.208854E+09 | 50263599.25 | 94321138.41 | 0.164663E+09 | 52317875.15 |
Maximum of Months | 0.348069E+09 | 0.195578E+09 | 0.189829E+09 | 0.403363E+09 | 0.317050E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.172402E+09 | 0.261566E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.175643E+09 | 0.228774E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.296247E+09 | 0.184621E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.250198E+09 | 0.138407E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.242836E+09 | 0.100512E+09 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251505E+09 | 66148743.97 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.293742E+09 | 47618660.67 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323343E+09 | 62221771.30 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335195E+09 | 94722854.49 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.290776E+09 | 0.140925E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.177055E+09 | 0.172053E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136215E+09 | 0.257410E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294516E+10 | 0.175498E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136215E+09 | 47618660.67 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335195E+09 | 0.261566E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.172402E+09 | 0.261566E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.175643E+09 | 0.228774E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.296247E+09 | 0.184621E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.250198E+09 | 0.138407E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.242836E+09 | 0.100512E+09 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251505E+09 | 66148743.97 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.293742E+09 | 47618660.67 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323343E+09 | 62221771.30 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335195E+09 | 94722854.49 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.290776E+09 | 0.140925E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.177055E+09 | 0.172053E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136215E+09 | 0.257410E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294516E+10 | 0.175498E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136215E+09 | 47618660.67 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335195E+09 | 0.261566E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.207644E+09 | 0.307917E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.212071E+09 | 0.269022E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.356020E+09 | 0.217790E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.300392E+09 | 0.163296E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.291201E+09 | 0.118857E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.301141E+09 | 78407881.78 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351237E+09 | 56540453.97 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.386692E+09 | 73823179.72 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.401193E+09 | 0.112258E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.348753E+09 | 0.166558E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.212728E+09 | 0.202850E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.164287E+09 | 0.302695E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.353336E+10 | 0.207001E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.164287E+09 | 56540453.97 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.401193E+09 | 0.307917E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.172727E+09 | 0.258838E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.176002E+09 | 0.226497E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.296755E+09 | 0.182493E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.250899E+09 | 0.136156E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.243758E+09 | 98599989.60 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251633E+09 | 65887479.98 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.293722E+09 | 47696784.11 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323337E+09 | 62266095.78 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335358E+09 | 94219176.20 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.291514E+09 | 0.138694E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.177530E+09 | 0.169688E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136504E+09 | 0.254770E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294974E+10 | 0.173580E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136504E+09 | 47696784.11 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335358E+09 | 0.258838E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.172727E+09 | 0.258838E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.176002E+09 | 0.226497E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.296755E+09 | 0.182493E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.250899E+09 | 0.136156E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.243758E+09 | 98599989.60 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.251633E+09 | 65887479.98 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.293722E+09 | 47696784.11 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323337E+09 | 62266095.78 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335358E+09 | 94219176.20 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.291514E+09 | 0.138694E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.177530E+09 | 0.169688E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136504E+09 | 0.254770E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.294974E+10 | 0.173580E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136504E+09 | 47696784.11 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335358E+09 | 0.258838E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.208042E+09 | 0.304688E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.212508E+09 | 0.266330E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.356632E+09 | 0.215274E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.301233E+09 | 0.160641E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.292302E+09 | 0.116606E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.301295E+09 | 78099143.54 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351214E+09 | 56632450.11 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.386685E+09 | 73875103.08 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.401388E+09 | 0.111662E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.349635E+09 | 0.163925E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.213301E+09 | 0.200059E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.164642E+09 | 0.299577E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.353888E+10 | 0.204737E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.164642E+09 | 56632450.11 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.401388E+09 | 0.304688E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.173152E+09 | 0.256540E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.176486E+09 | 0.224556E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.297461E+09 | 0.180570E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.251803E+09 | 0.134121E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.245185E+09 | 96254966.62 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252125E+09 | 65023963.11 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294059E+09 | 47014833.86 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323633E+09 | 61535226.92 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335777E+09 | 93194153.86 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.292444E+09 | 0.136572E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178068E+09 | 0.167724E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136873E+09 | 0.252467E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.295707E+10 | 0.171557E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136873E+09 | 47014833.86 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335777E+09 | 0.256540E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.173152E+09 | 0.256540E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.176486E+09 | 0.224556E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.297461E+09 | 0.180570E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.251803E+09 | 0.134121E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.245185E+09 | 96254966.62 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252125E+09 | 65023963.11 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294059E+09 | 47014833.86 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323633E+09 | 61535226.92 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.335777E+09 | 93194153.86 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.292444E+09 | 0.136572E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.178068E+09 | 0.167724E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.136873E+09 | 0.252467E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.295707E+10 | 0.171557E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.136873E+09 | 47014833.86 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.335777E+09 | 0.256540E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.208565E+09 | 0.301973E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.213096E+09 | 0.264037E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.357484E+09 | 0.213005E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.302315E+09 | 0.158242E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.294001E+09 | 0.113846E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.301885E+09 | 77086273.85 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351618E+09 | 55833568.65 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387042E+09 | 73017242.67 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.401891E+09 | 0.110456E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.350745E+09 | 0.161427E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.213949E+09 | 0.197742E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.165098E+09 | 0.296856E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.354769E+10 | 0.202352E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.165098E+09 | 55833568.65 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.401891E+09 | 0.301973E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.175012E+09 | 0.248793E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178872E+09 | 0.217720E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300210E+09 | 0.174907E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254094E+09 | 0.129162E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247953E+09 | 91432135.00 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252963E+09 | 62601082.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294277E+09 | 44928625.21 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323851E+09 | 59264761.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336532E+09 | 90634540.89 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294521E+09 | 0.132187E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179706E+09 | 0.162561E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138546E+09 | 0.244705E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297654E+10 | 0.165890E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138546E+09 | 44928625.21 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336532E+09 | 0.248793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.175012E+09 | 0.248793E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178872E+09 | 0.217720E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300210E+09 | 0.174907E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254094E+09 | 0.129162E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247953E+09 | 91432135.00 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252963E+09 | 62601082.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294277E+09 | 44928625.21 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323851E+09 | 59264761.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336532E+09 | 90634540.89 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294521E+09 | 0.132187E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179706E+09 | 0.162561E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138546E+09 | 0.244705E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297654E+10 | 0.165890E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138546E+09 | 44928625.21 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336532E+09 | 0.248793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.175012E+09 | 0.248793E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178872E+09 | 0.217720E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300210E+09 | 0.174907E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254094E+09 | 0.129162E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247953E+09 | 91432135.00 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252963E+09 | 62601082.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294277E+09 | 44928625.21 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323851E+09 | 59264761.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336532E+09 | 90634540.89 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294521E+09 | 0.132187E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179706E+09 | 0.162561E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138546E+09 | 0.244705E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297654E+10 | 0.165890E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138546E+09 | 44928625.21 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336532E+09 | 0.248793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.175012E+09 | 0.248793E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178872E+09 | 0.217720E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300210E+09 | 0.174907E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254094E+09 | 0.129162E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247953E+09 | 91432135.00 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252963E+09 | 62601082.14 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294277E+09 | 44928625.21 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323851E+09 | 59264761.93 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336532E+09 | 90634540.89 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294521E+09 | 0.132187E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179706E+09 | 0.162561E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138546E+09 | 0.244705E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297654E+10 | 0.165890E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138546E+09 | 44928625.21 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336532E+09 | 0.248793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.210731E+09 | 0.293018E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.215850E+09 | 0.256153E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.360656E+09 | 0.206435E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.304967E+09 | 0.152477E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.297223E+09 | 0.108199E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.302838E+09 | 74247333.80 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351841E+09 | 53377604.14 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387260E+09 | 70350023.96 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.402728E+09 | 0.107454E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.353135E+09 | 0.156320E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.215850E+09 | 0.191748E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.167050E+09 | 0.287896E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.357013E+10 | 0.195768E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.167050E+09 | 53377604.14 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.402728E+09 | 0.293018E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.210731E+09 | 0.293018E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.215850E+09 | 0.256153E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.360656E+09 | 0.206435E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.304967E+09 | 0.152477E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.297223E+09 | 0.108199E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.302838E+09 | 74247333.80 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351841E+09 | 53377604.14 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387260E+09 | 70350023.96 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.402728E+09 | 0.107454E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.353135E+09 | 0.156320E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.215850E+09 | 0.191748E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.167050E+09 | 0.287896E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.357013E+10 | 0.195768E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.167050E+09 | 53377604.14 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.402728E+09 | 0.293018E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174039E+09 | 0.250669E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.177649E+09 | 0.219450E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299101E+09 | 0.175519E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253476E+09 | 0.129185E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247966E+09 | 90684668.64 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252868E+09 | 62093520.85 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294315E+09 | 44315765.48 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323732E+09 | 58650975.45 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336194E+09 | 90178118.98 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294028E+09 | 0.131910E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179141E+09 | 0.163079E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.137674E+09 | 0.246616E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297018E+10 | 0.166235E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.137674E+09 | 44315765.48 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336194E+09 | 0.250669E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174039E+09 | 0.250669E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.177649E+09 | 0.219450E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299101E+09 | 0.175519E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253476E+09 | 0.129185E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.247966E+09 | 90684668.64 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.252868E+09 | 62093520.85 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294315E+09 | 44315765.48 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323732E+09 | 58650975.45 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336194E+09 | 90178118.98 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294028E+09 | 0.131910E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179141E+09 | 0.163079E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.137674E+09 | 0.246616E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297018E+10 | 0.166235E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.137674E+09 | 44315765.48 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336194E+09 | 0.250669E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.209666E+09 | 0.295055E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.214514E+09 | 0.258026E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.359474E+09 | 0.207049E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.304341E+09 | 0.152427E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.297326E+09 | 0.107282E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.302799E+09 | 73633902.39 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.351952E+09 | 52650999.59 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387194E+09 | 69613709.77 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.402415E+09 | 0.106890E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.352654E+09 | 0.155929E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.215250E+09 | 0.192252E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.166089E+09 | 0.289955E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.356367E+10 | 0.196076E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.166089E+09 | 52650999.59 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.402415E+09 | 0.295055E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174142E+09 | 0.250113E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.177760E+09 | 0.219010E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299364E+09 | 0.174794E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253856E+09 | 0.128334E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.248803E+09 | 89480558.61 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253254E+09 | 61615629.34 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294523E+09 | 44043274.34 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323909E+09 | 58361358.34 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336444E+09 | 89695600.65 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294429E+09 | 0.131060E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179338E+09 | 0.162370E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.137767E+09 | 0.246033E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297359E+10 | 0.165491E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.137767E+09 | 44043274.34 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336444E+09 | 0.250113E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174142E+09 | 0.250113E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.177760E+09 | 0.219010E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.299364E+09 | 0.174794E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.253856E+09 | 0.128334E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.248803E+09 | 89480558.61 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.253254E+09 | 61615629.34 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294523E+09 | 44043274.34 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.323909E+09 | 58361358.34 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.336444E+09 | 89695600.65 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.294429E+09 | 0.131060E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179338E+09 | 0.162370E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.137767E+09 | 0.246033E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.297359E+10 | 0.165491E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.137767E+09 | 44043274.34 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.336444E+09 | 0.250113E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.209792E+09 | 0.294396E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.214650E+09 | 0.257506E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.359793E+09 | 0.206192E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.304797E+09 | 0.151422E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.298325E+09 | 0.105864E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.303261E+09 | 73070632.35 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.352203E+09 | 52329358.41 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387407E+09 | 69272127.84 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.402715E+09 | 0.106320E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.353131E+09 | 0.154925E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.215489E+09 | 0.191416E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.166204E+09 | 0.289266E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.356776E+10 | 0.195198E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.166204E+09 | 52329358.41 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.402715E+09 | 0.294396E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174621E+09 | 0.247118E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178283E+09 | 0.216548E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300279E+09 | 0.171808E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254920E+09 | 0.125473E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.250731E+09 | 86460501.25 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.254240E+09 | 60259542.71 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294900E+09 | 43378488.16 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324225E+09 | 57668049.33 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.337073E+09 | 88329988.69 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.295340E+09 | 0.128801E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179936E+09 | 0.159897E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138178E+09 | 0.243094E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.298273E+10 | 0.162884E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138178E+09 | 43378488.16 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.337073E+09 | 0.247118E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.174621E+09 | 0.247118E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.178283E+09 | 0.216548E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.300279E+09 | 0.171808E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.254920E+09 | 0.125473E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.250731E+09 | 86460501.25 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.254240E+09 | 60259542.71 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.294900E+09 | 43378488.16 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324225E+09 | 57668049.33 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.337073E+09 | 88329988.69 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.295340E+09 | 0.128801E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.179936E+09 | 0.159897E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.138178E+09 | 0.243094E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.298273E+10 | 0.162884E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.138178E+09 | 43378488.16 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.337073E+09 | 0.247118E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.210374E+09 | 0.290856E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.215286E+09 | 0.254601E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.360901E+09 | 0.202670E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.306078E+09 | 0.148051E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.300622E+09 | 0.102313E+09 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.304436E+09 | 71475500.81 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.352653E+09 | 51550740.09 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.387785E+09 | 68458299.15 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.403467E+09 | 0.104712E+09 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.354222E+09 | 0.152265E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.216213E+09 | 0.188501E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.166708E+09 | 0.285798E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.357875E+10 | 0.192125E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.166708E+09 | 51550740.09 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.403467E+09 | 0.290856E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.176725E+09 | 0.233984E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.180596E+09 | 0.205356E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.303568E+09 | 0.159517E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.257998E+09 | 0.114684E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.254911E+09 | 77617593.31 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.256693E+09 | 55455942.85 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295596E+09 | 40837268.64 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324774E+09 | 54976978.90 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.338512E+09 | 83636513.05 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.297409E+09 | 0.121601E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.181818E+09 | 0.150627E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.139942E+09 | 0.230241E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.300854E+10 | 0.152853E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.139942E+09 | 40837268.64 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.338512E+09 | 0.233984E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207766E+09 | 0.121279E+09 | 86486624.93 | 0.176725E+09 | 0.233984E+09 |
February | 0.214260E+09 | 0.103314E+09 | 0.110946E+09 | 0.180596E+09 | 0.205356E+09 |
March | 0.289538E+09 | 0.162690E+09 | 0.126848E+09 | 0.303568E+09 | 0.159517E+09 |
April | 0.232048E+09 | 92727114.54 | 0.139321E+09 | 0.257998E+09 | 0.114684E+09 |
May | 0.209831E+09 | 60943889.42 | 0.148888E+09 | 0.254911E+09 | 77617593.31 |
June | 0.197311E+09 | 41811283.17 | 0.155500E+09 | 0.256693E+09 | 55455942.85 |
July | 0.208137E+09 | 50500875.09 | 0.157636E+09 | 0.295596E+09 | 40837268.64 |
August | 0.233668E+09 | 75761088.58 | 0.157907E+09 | 0.324774E+09 | 54976978.90 |
September | 0.262922E+09 | 0.128063E+09 | 0.134860E+09 | 0.338512E+09 | 83636513.05 |
October | 0.259964E+09 | 0.148496E+09 | 0.111467E+09 | 0.297409E+09 | 0.121601E+09 |
November | 0.180175E+09 | 0.101715E+09 | 78460115.98 | 0.181818E+09 | 0.150627E+09 |
December | 0.173733E+09 | 89914808.66 | 83818373.18 | 0.139942E+09 | 0.230241E+09 |
Annual Sum or Average | 0.266935E+10 | 0.117722E+10 | 0.149214E+10 | 0.300854E+10 | 0.152853E+10 |
Minimum of Months | 0.173733E+09 | 41811283.17 | 78460115.98 | 0.139942E+09 | 40837268.64 |
Maximum of Months | 0.289538E+09 | 0.162690E+09 | 0.157907E+09 | 0.338512E+09 | 0.233984E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248401E+09 | 0.144999E+09 | 0.103402E+09 | 0.212941E+09 | 0.275336E+09 |
February | 0.256166E+09 | 0.123521E+09 | 0.132645E+09 | 0.218109E+09 | 0.241393E+09 |
March | 0.346167E+09 | 0.194509E+09 | 0.151658E+09 | 0.364889E+09 | 0.188185E+09 |
April | 0.277433E+09 | 0.110863E+09 | 0.166570E+09 | 0.309789E+09 | 0.135350E+09 |
May | 0.250871E+09 | 72863588.06 | 0.178008E+09 | 0.305617E+09 | 91916016.44 |
June | 0.235903E+09 | 49988934.77 | 0.185914E+09 | 0.307357E+09 | 65828798.65 |
July | 0.248846E+09 | 60378078.83 | 0.188467E+09 | 0.353481E+09 | 48564103.29 |
August | 0.279370E+09 | 90578806.21 | 0.188791E+09 | 0.388438E+09 | 65294121.96 |
September | 0.314346E+09 | 0.153110E+09 | 0.161236E+09 | 0.405183E+09 | 99184953.69 |
October | 0.310809E+09 | 0.177540E+09 | 0.133269E+09 | 0.356708E+09 | 0.143794E+09 |
November | 0.215414E+09 | 0.121609E+09 | 93805722.35 | 0.218496E+09 | 0.177588E+09 |
December | 0.207713E+09 | 0.107501E+09 | 0.100212E+09 | 0.168869E+09 | 0.270641E+09 |
Annual Sum or Average | 0.319144E+10 | 0.140746E+10 | 0.178398E+10 | 0.360988E+10 | 0.180307E+10 |
Minimum of Months | 0.207713E+09 | 49988934.77 | 93805722.35 | 0.168869E+09 | 48564103.29 |
Maximum of Months | 0.346167E+09 | 0.194509E+09 | 0.188791E+09 | 0.405183E+09 | 0.275336E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.98 | 607.89 | 496.79 | 289.99 | 206.80 | 0.00 | 0.00 |
February | 474.47 | 587.74 | 567.21 | 273.50 | 293.70 | 0.00 | 0.00 |
March | 718.54 | 424.50 | 692.31 | 389.01 | 303.31 | 0.00 | 0.00 |
April | 627.69 | 324.28 | 573.34 | 229.11 | 344.23 | 0.00 | 0.00 |
May | 591.14 | 223.63 | 501.73 | 145.72 | 356.00 | 0.00 | 0.00 |
June | 627.22 | 151.50 | 487.52 | 103.31 | 384.21 | 0.00 | 0.00 |
July | 706.91 | 102.30 | 497.68 | 120.75 | 376.92 | 0.00 | 0.00 |
August | 776.38 | 136.97 | 558.72 | 181.15 | 377.57 | 0.00 | 0.00 |
September | 832.24 | 221.79 | 649.63 | 316.42 | 333.21 | 0.00 | 0.00 |
October | 701.68 | 323.18 | 621.60 | 355.07 | 266.53 | 0.00 | 0.00 |
November | 442.62 | 410.07 | 445.18 | 251.32 | 193.86 | 0.00 | 0.00 |
December | 331.42 | 596.98 | 415.41 | 214.99 | 200.42 | 0.00 | 0.00 |
Annual Sum or Average | 604.86 | 341.27 | 542.09 | 239.07 | 303.02 | 0.00 | 0.00 |
Minimum of Months | 331.42 | 102.30 | 415.41 | 103.31 | 193.86 | 0.00 | 0.00 |
Maximum of Months | 832.24 | 607.89 | 692.31 | 389.01 | 384.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.13 | 318.40 | 248.39 | 144.99 | 103.40 | 0.00 | 0.00 |
February | 232.76 | 308.22 | 283.60 | 136.75 | 146.85 | 0.00 | 0.00 |
March | 354.20 | 225.28 | 346.16 | 194.50 | 151.65 | 0.00 | 0.00 |
April | 308.40 | 175.68 | 286.67 | 114.55 | 172.12 | 0.00 | 0.00 |
May | 289.59 | 121.31 | 250.86 | 72.86 | 178.00 | 0.00 | 0.00 |
June | 311.44 | 78.21 | 243.76 | 51.65 | 192.10 | 0.00 | 0.00 |
July | 352.62 | 52.21 | 248.84 | 60.38 | 188.46 | 0.00 | 0.00 |
August | 387.42 | 69.61 | 279.36 | 90.58 | 188.79 | 0.00 | 0.00 |
September | 414.23 | 114.03 | 324.81 | 158.21 | 166.61 | 0.00 | 0.00 |
October | 346.70 | 172.27 | 310.80 | 177.53 | 133.26 | 0.00 | 0.00 |
November | 218.14 | 218.03 | 222.59 | 125.66 | 96.93 | 0.00 | 0.00 |
December | 162.87 | 313.23 | 207.71 | 107.50 | 100.21 | 0.00 | 0.00 |
Annual Sum or Average | 299.09 | 179.86 | 271.05 | 119.53 | 151.51 | 0.00 | 0.00 |
Minimum of Months | 162.87 | 52.21 | 207.71 | 51.65 | 96.93 | 0.00 | 0.00 |
Maximum of Months | 414.23 | 318.40 | 346.16 | 194.50 | 192.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.26 | 310.28 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 232.87 | 300.33 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 354.13 | 219.17 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 308.95 | 169.79 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 290.05 | 119.43 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 310.24 | 81.29 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 350.48 | 56.67 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 385.82 | 74.02 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 413.42 | 116.40 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 347.34 | 167.42 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 218.69 | 211.02 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 163.05 | 305.22 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.82 | 176.94 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 163.05 | 56.67 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 413.42 | 310.28 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.65 | 307.03 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 233.35 | 297.34 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 354.74 | 216.64 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 309.81 | 167.03 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 291.15 | 117.16 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 310.40 | 80.97 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 350.45 | 56.76 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 385.81 | 74.08 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 413.62 | 115.78 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 348.22 | 164.77 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 219.27 | 208.11 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 163.40 | 302.09 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.29 | 175.00 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 163.40 | 56.76 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 413.62 | 307.03 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 207.16 | 304.30 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 233.99 | 294.79 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 355.59 | 214.36 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 310.93 | 164.54 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 292.85 | 114.38 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 311.01 | 79.91 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 350.86 | 55.95 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 386.17 | 73.21 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 414.14 | 114.52 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 349.32 | 162.25 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 219.94 | 205.70 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 163.84 | 299.35 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.03 | 172.97 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 163.84 | 55.95 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 414.14 | 304.30 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.72 | 590.35 | 495.77 | 289.39 | 206.37 | 0.00 | 0.00 |
February | 474.20 | 571.75 | 566.04 | 272.94 | 293.10 | 0.00 | 0.00 |
March | 717.65 | 415.36 | 690.89 | 388.21 | 302.68 | 0.00 | 0.00 |
April | 627.43 | 316.97 | 572.17 | 228.64 | 343.53 | 0.00 | 0.00 |
May | 592.24 | 217.34 | 500.70 | 145.42 | 355.27 | 0.00 | 0.00 |
June | 624.05 | 153.90 | 486.52 | 103.10 | 383.42 | 0.00 | 0.00 |
July | 702.21 | 106.96 | 496.65 | 120.50 | 376.15 | 0.00 | 0.00 |
August | 772.82 | 141.04 | 557.58 | 180.78 | 376.80 | 0.00 | 0.00 |
September | 830.09 | 222.78 | 648.30 | 315.77 | 332.53 | 0.00 | 0.00 |
October | 703.54 | 314.14 | 620.32 | 354.34 | 265.98 | 0.00 | 0.00 |
November | 443.87 | 398.82 | 444.26 | 250.80 | 193.46 | 0.00 | 0.00 |
December | 331.64 | 580.42 | 414.56 | 214.55 | 200.01 | 0.00 | 0.00 |
Annual Sum or Average | 603.96 | 334.57 | 540.98 | 238.58 | 302.40 | 0.00 | 0.00 |
Minimum of Months | 331.64 | 106.96 | 414.56 | 103.10 | 193.46 | 0.00 | 0.00 |
Maximum of Months | 830.09 | 590.35 | 690.89 | 388.21 | 383.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.24 | 297.34 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 235.53 | 288.08 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 357.55 | 208.37 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 313.00 | 158.49 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 296.17 | 107.77 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 311.93 | 76.32 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 351.17 | 52.75 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 386.30 | 69.79 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 414.66 | 110.82 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 351.22 | 156.72 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 221.27 | 200.00 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 164.81 | 292.41 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.37 | 167.60 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 164.81 | 52.75 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 414.66 | 297.34 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.36 | 296.68 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 235.68 | 287.50 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 357.87 | 207.50 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 313.47 | 157.44 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 297.17 | 106.34 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 312.41 | 75.73 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 351.42 | 52.43 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 386.51 | 69.44 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 414.97 | 110.23 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 351.70 | 155.71 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 221.51 | 199.13 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 164.92 | 291.71 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.72 | 166.85 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 164.92 | 52.43 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 414.97 | 296.68 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.94 | 293.12 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 236.38 | 284.26 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 358.97 | 203.96 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 314.78 | 153.93 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 299.46 | 102.76 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 313.62 | 74.07 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 351.87 | 51.64 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 386.89 | 68.62 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 415.75 | 108.55 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 352.79 | 153.03 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 222.25 | 196.10 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 165.42 | 288.22 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.64 | 164.22 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 165.42 | 51.64 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 415.75 | 293.12 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.46 | 277.52 | 247.88 | 144.70 | 103.19 | 0.00 | 0.00 |
February | 239.46 | 269.55 | 283.02 | 136.47 | 146.55 | 0.00 | 0.00 |
March | 362.91 | 189.37 | 345.45 | 194.10 | 151.34 | 0.00 | 0.00 |
April | 318.59 | 140.71 | 286.08 | 114.32 | 171.76 | 0.00 | 0.00 |
May | 304.45 | 92.28 | 250.35 | 72.71 | 177.64 | 0.00 | 0.00 |
June | 316.64 | 68.19 | 243.26 | 51.55 | 191.71 | 0.00 | 0.00 |
July | 352.70 | 48.63 | 248.33 | 60.25 | 188.07 | 0.00 | 0.00 |
August | 387.54 | 65.43 | 278.79 | 90.39 | 188.40 | 0.00 | 0.00 |
September | 417.52 | 102.80 | 324.15 | 157.88 | 166.26 | 0.00 | 0.00 |
October | 355.26 | 144.49 | 310.16 | 177.17 | 132.99 | 0.00 | 0.00 |
November | 224.59 | 184.74 | 222.13 | 125.40 | 96.73 | 0.00 | 0.00 |
December | 167.54 | 272.97 | 207.28 | 107.28 | 100.00 | 0.00 | 0.00 |
Annual Sum or Average | 305.27 | 154.11 | 270.49 | 119.29 | 151.20 | 0.00 | 0.00 |
Minimum of Months | 167.54 | 48.63 | 207.28 | 51.55 | 96.73 | 0.00 | 0.00 |
Maximum of Months | 417.52 | 277.52 | 345.45 | 194.10 | 191.71 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112219E+10 | 0.162817E+10 | 0.133059E+10 | 0.776707E+09 | 0.553887E+09 | 0.00 | 0.00 |
February | 0.114784E+10 | 0.142187E+10 | 0.137218E+10 | 0.661656E+09 | 0.710529E+09 | 0.00 | 0.00 |
March | 0.192453E+10 | 0.113698E+10 | 0.185429E+10 | 0.104191E+10 | 0.812376E+09 | 0.00 | 0.00 |
April | 0.162696E+10 | 0.840542E+09 | 0.148611E+10 | 0.593853E+09 | 0.892254E+09 | 0.00 | 0.00 |
May | 0.158330E+10 | 0.598970E+09 | 0.134383E+10 | 0.390303E+09 | 0.953522E+09 | 0.00 | 0.00 |
June | 0.162575E+10 | 0.392687E+09 | 0.126364E+10 | 0.267772E+09 | 0.995871E+09 | 0.00 | 0.00 |
July | 0.189340E+10 | 0.273998E+09 | 0.133297E+10 | 0.323423E+09 | 0.100955E+10 | 0.00 | 0.00 |
August | 0.207946E+10 | 0.366860E+09 | 0.149648E+10 | 0.485197E+09 | 0.101129E+10 | 0.00 | 0.00 |
September | 0.215717E+10 | 0.574878E+09 | 0.168384E+10 | 0.820153E+09 | 0.863683E+09 | 0.00 | 0.00 |
October | 0.187938E+10 | 0.865596E+09 | 0.166489E+10 | 0.951016E+09 | 0.713872E+09 | 0.00 | 0.00 |
November | 0.114726E+10 | 0.106289E+10 | 0.115390E+10 | 0.651413E+09 | 0.502483E+09 | 0.00 | 0.00 |
December | 0.887668E+09 | 0.159895E+10 | 0.111264E+10 | 0.575842E+09 | 0.536799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190749E+11 | 0.107624E+11 | 0.170954E+11 | 0.753925E+10 | 0.955611E+10 | 0.00 | 0.00 |
Minimum of Months | 0.887668E+09 | 0.273998E+09 | 0.111264E+10 | 0.267772E+09 | 0.502483E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215717E+10 | 0.162817E+10 | 0.185429E+10 | 0.104191E+10 | 0.101129E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.552107E+09 | 0.852795E+09 | 0.665297E+09 | 0.388354E+09 | 0.276943E+09 | 0.00 | 0.00 |
February | 0.563097E+09 | 0.745640E+09 | 0.686092E+09 | 0.330828E+09 | 0.355265E+09 | 0.00 | 0.00 |
March | 0.948691E+09 | 0.603394E+09 | 0.927145E+09 | 0.520957E+09 | 0.406188E+09 | 0.00 | 0.00 |
April | 0.799370E+09 | 0.455375E+09 | 0.743054E+09 | 0.296926E+09 | 0.446127E+09 | 0.00 | 0.00 |
May | 0.775627E+09 | 0.324928E+09 | 0.671913E+09 | 0.195152E+09 | 0.476761E+09 | 0.00 | 0.00 |
June | 0.807259E+09 | 0.202729E+09 | 0.631822E+09 | 0.133886E+09 | 0.497936E+09 | 0.00 | 0.00 |
July | 0.944450E+09 | 0.139831E+09 | 0.666487E+09 | 0.161712E+09 | 0.504775E+09 | 0.00 | 0.00 |
August | 0.103766E+10 | 0.186447E+09 | 0.748241E+09 | 0.242599E+09 | 0.505643E+09 | 0.00 | 0.00 |
September | 0.107370E+10 | 0.295554E+09 | 0.841918E+09 | 0.410077E+09 | 0.431841E+09 | 0.00 | 0.00 |
October | 0.928588E+09 | 0.461399E+09 | 0.832444E+09 | 0.475508E+09 | 0.356936E+09 | 0.00 | 0.00 |
November | 0.565431E+09 | 0.565130E+09 | 0.576948E+09 | 0.325706E+09 | 0.251241E+09 | 0.00 | 0.00 |
December | 0.436235E+09 | 0.838962E+09 | 0.556320E+09 | 0.287921E+09 | 0.268399E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.943222E+10 | 0.567219E+10 | 0.854768E+10 | 0.376963E+10 | 0.477806E+10 | 0.00 | 0.00 |
Minimum of Months | 0.436235E+09 | 0.139831E+09 | 0.556320E+09 | 0.133886E+09 | 0.251241E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107370E+10 | 0.852795E+09 | 0.927145E+09 | 0.520957E+09 | 0.505643E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.552441E+09 | 0.831043E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.563353E+09 | 0.726567E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.948513E+09 | 0.587031E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.800786E+09 | 0.440107E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.776872E+09 | 0.319879E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.804151E+09 | 0.210705E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.938721E+09 | 0.151778E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103338E+10 | 0.198267E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107158E+10 | 0.301703E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.930304E+09 | 0.448408E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.566834E+09 | 0.546951E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.436709E+09 | 0.817505E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.942365E+10 | 0.557994E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.436709E+09 | 0.151778E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107158E+10 | 0.831043E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.553488E+09 | 0.822357E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.564509E+09 | 0.719320E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.950139E+09 | 0.580258E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.803029E+09 | 0.432951E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.779816E+09 | 0.313805E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.804561E+09 | 0.209874E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.938657E+09 | 0.152026E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103336E+10 | 0.198407E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107210E+10 | 0.300100E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.932663E+09 | 0.441312E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.568357E+09 | 0.539431E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.437643E+09 | 0.809111E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.943833E+10 | 0.551895E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.437643E+09 | 0.152026E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107210E+10 | 0.822357E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.554861E+09 | 0.815046E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.566064E+09 | 0.713145E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.952403E+09 | 0.574141E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.805918E+09 | 0.426482E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.784370E+09 | 0.306356E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.806134E+09 | 0.207133E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.939736E+09 | 0.149863E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103431E+10 | 0.196087E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107345E+10 | 0.296844E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.935631E+09 | 0.434569E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.570081E+09 | 0.533186E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.438836E+09 | 0.801782E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.946179E+10 | 0.545463E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.438836E+09 | 0.149863E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107345E+10 | 0.815046E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112150E+10 | 0.158120E+10 | 0.132786E+10 | 0.775114E+09 | 0.552751E+09 | 0.00 | 0.00 |
February | 0.114717E+10 | 0.138317E+10 | 0.136937E+10 | 0.660298E+09 | 0.709072E+09 | 0.00 | 0.00 |
March | 0.192215E+10 | 0.111249E+10 | 0.185049E+10 | 0.103978E+10 | 0.810710E+09 | 0.00 | 0.00 |
April | 0.162631E+10 | 0.821598E+09 | 0.148306E+10 | 0.592635E+09 | 0.890424E+09 | 0.00 | 0.00 |
May | 0.158626E+10 | 0.582124E+09 | 0.134107E+10 | 0.389503E+09 | 0.951566E+09 | 0.00 | 0.00 |
June | 0.161753E+10 | 0.398898E+09 | 0.126105E+10 | 0.267223E+09 | 0.993828E+09 | 0.00 | 0.00 |
July | 0.188079E+10 | 0.286469E+09 | 0.133024E+10 | 0.322760E+09 | 0.100748E+10 | 0.00 | 0.00 |
August | 0.206992E+10 | 0.377759E+09 | 0.149341E+10 | 0.484202E+09 | 0.100921E+10 | 0.00 | 0.00 |
September | 0.215158E+10 | 0.577446E+09 | 0.168038E+10 | 0.818471E+09 | 0.861911E+09 | 0.00 | 0.00 |
October | 0.188435E+10 | 0.841387E+09 | 0.166147E+10 | 0.949065E+09 | 0.712407E+09 | 0.00 | 0.00 |
November | 0.115051E+10 | 0.103373E+10 | 0.115153E+10 | 0.650076E+09 | 0.501452E+09 | 0.00 | 0.00 |
December | 0.888270E+09 | 0.155460E+10 | 0.111036E+10 | 0.574661E+09 | 0.535697E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190463E+11 | 0.105509E+11 | 0.170603E+11 | 0.752378E+10 | 0.953651E+10 | 0.00 | 0.00 |
Minimum of Months | 0.888270E+09 | 0.286469E+09 | 0.111036E+10 | 0.267223E+09 | 0.501452E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215158E+10 | 0.158120E+10 | 0.185049E+10 | 0.103978E+10 | 0.100921E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.557741E+09 | 0.796389E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.569806E+09 | 0.696921E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.957674E+09 | 0.558086E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.811291E+09 | 0.410797E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.793256E+09 | 0.288650E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.808534E+09 | 0.197821E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.940581E+09 | 0.141282E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103466E+10 | 0.186915E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107480E+10 | 0.287245E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.940709E+09 | 0.419748E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.573526E+09 | 0.518405E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.441428E+09 | 0.783178E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950401E+10 | 0.528544E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441428E+09 | 0.141282E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107480E+10 | 0.796389E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.558072E+09 | 0.794619E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.570165E+09 | 0.695521E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.958518E+09 | 0.555777E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.812509E+09 | 0.408089E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.795930E+09 | 0.284824E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.809769E+09 | 0.196302E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.941248E+09 | 0.140415E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103522E+10 | 0.185995E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107560E+10 | 0.285710E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.941987E+09 | 0.417045E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.574160E+09 | 0.516150E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.441730E+09 | 0.781324E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.951492E+10 | 0.526177E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441730E+09 | 0.140415E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107560E+10 | 0.794619E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.559613E+09 | 0.785088E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.571847E+09 | 0.687693E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.961455E+09 | 0.546282E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.815917E+09 | 0.398996E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.802083E+09 | 0.275232E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.812916E+09 | 0.191994E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.942453E+09 | 0.138307E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103623E+10 | 0.183794E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.107761E+10 | 0.281372E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.944901E+09 | 0.409867E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.576079E+09 | 0.508289E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.443057E+09 | 0.771979E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.954417E+10 | 0.517889E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.443057E+09 | 0.138307E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107761E+10 | 0.785088E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.566387E+09 | 0.743298E+09 | 0.663932E+09 | 0.387557E+09 | 0.276375E+09 | 0.00 | 0.00 |
February | 0.579296E+09 | 0.652100E+09 | 0.684685E+09 | 0.330149E+09 | 0.354536E+09 | 0.00 | 0.00 |
March | 0.972023E+09 | 0.507215E+09 | 0.925243E+09 | 0.519888E+09 | 0.405355E+09 | 0.00 | 0.00 |
April | 0.825781E+09 | 0.364715E+09 | 0.741529E+09 | 0.296317E+09 | 0.445212E+09 | 0.00 | 0.00 |
May | 0.815439E+09 | 0.247151E+09 | 0.670534E+09 | 0.194751E+09 | 0.475783E+09 | 0.00 | 0.00 |
June | 0.820742E+09 | 0.176741E+09 | 0.630526E+09 | 0.133612E+09 | 0.496914E+09 | 0.00 | 0.00 |
July | 0.944673E+09 | 0.130238E+09 | 0.665120E+09 | 0.161380E+09 | 0.503740E+09 | 0.00 | 0.00 |
August | 0.103799E+10 | 0.175248E+09 | 0.746706E+09 | 0.242101E+09 | 0.504605E+09 | 0.00 | 0.00 |
September | 0.108221E+10 | 0.266457E+09 | 0.840191E+09 | 0.409235E+09 | 0.430956E+09 | 0.00 | 0.00 |
October | 0.951526E+09 | 0.386995E+09 | 0.830736E+09 | 0.474533E+09 | 0.356204E+09 | 0.00 | 0.00 |
November | 0.582127E+09 | 0.478836E+09 | 0.575764E+09 | 0.325038E+09 | 0.250726E+09 | 0.00 | 0.00 |
December | 0.448745E+09 | 0.731117E+09 | 0.555179E+09 | 0.287330E+09 | 0.267849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962693E+10 | 0.486011E+10 | 0.853015E+10 | 0.376189E+10 | 0.476825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448745E+09 | 0.130238E+09 | 0.555179E+09 | 0.133612E+09 | 0.250726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108221E+10 | 0.743298E+09 | 0.925243E+09 | 0.519888E+09 | 0.504605E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.379264E+09 | -253687573.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125576093.5 | 58.99 | 0.00 | 0.00 |
February | 0.347450E+09 | -233692892.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113756942.9 | 59.00 | 0.00 | 0.00 |
March | 0.383234E+09 | -259384945.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123848996.4 | 58.99 | 0.00 | 0.00 |
April | 0.356599E+09 | -237979362.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118619990.2 | 58.99 | 0.00 | 0.00 |
May | 0.349630E+09 | -232227914.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117402498.0 | 58.99 | 0.00 | 0.00 |
June | 0.322857E+09 | -213005372.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109851990.6 | 58.99 | 0.00 | 0.00 |
July | 0.317656E+09 | -205139074.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112516833.1 | 58.99 | 0.00 | 0.00 |
August | 0.318025E+09 | -205442576.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112582909.7 | 58.99 | 0.00 | 0.00 |
September | 0.310097E+09 | -200160746.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109936443.9 | 58.99 | 0.00 | 0.00 |
October | 0.334885E+09 | -215153270.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119732120.3 | 58.99 | 0.00 | 0.00 |
November | 0.340117E+09 | -221153893.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118963279.1 | 58.99 | 0.00 | 0.00 |
December | 0.368775E+09 | -243526123.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125248565.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.412859E+10 | -0.272055E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140804E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310097E+09 | -259384945.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125576093.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.383234E+09 | -200160746.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109851990.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.377458E+09 | -253680811.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123776837.2 | 58.99 | 0.00 | 0.00 |
February | 0.345777E+09 | -233701897.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112075011.0 | 58.99 | 0.00 | 0.00 |
March | 0.381001E+09 | -259383415.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121617370.3 | 59.00 | 0.00 | 0.00 |
April | 0.353794E+09 | -237978136.4 | 0.00 | 0.00 | 720.00 | 0.00 | -115816282.5 | 58.99 | 0.00 | 0.00 |
May | 0.347184E+09 | -232221764.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114962358.0 | 58.99 | 0.00 | 0.00 |
June | 0.322333E+09 | -213013995.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109318958.2 | 58.99 | 0.00 | 0.00 |
July | 0.317512E+09 | -205140804.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112371527.4 | 58.99 | 0.00 | 0.00 |
August | 0.317853E+09 | -205443439.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112409963.1 | 58.99 | 0.00 | 0.00 |
September | 0.309453E+09 | -200162384.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109290519.7 | 58.99 | 0.00 | 0.00 |
October | 0.332391E+09 | -215145135.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117246166.4 | 58.99 | 0.00 | 0.00 |
November | 0.337782E+09 | -221153517.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116628544.6 | 58.99 | 0.00 | 0.00 |
December | 0.366872E+09 | -243519651.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123352553.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.410941E+10 | -0.272054E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138887E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309453E+09 | -259383415.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123776837.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.381001E+09 | -200162384.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109290519.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.348656E+09 | -223081846.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125574300.7 | 58.99 | 0.00 | 0.00 |
February | 0.319348E+09 | -205668699.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113679443.5 | 58.99 | 0.00 | 0.00 |
March | 0.354645E+09 | -231510924.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123134338.1 | 58.99 | 0.00 | 0.00 |
April | 0.326761E+09 | -209298203.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117462799.8 | 58.99 | 0.00 | 0.00 |
May | 0.321621E+09 | -205973708.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115647187.0 | 59.00 | 0.00 | 0.00 |
June | 0.298114E+09 | -189702417.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108411654.1 | 58.99 | 0.00 | 0.00 |
July | 0.290121E+09 | -179329024.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110792450.7 | 58.99 | 0.00 | 0.00 |
August | 0.294590E+09 | -183514984.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111075331.6 | 58.99 | 0.00 | 0.00 |
September | 0.284650E+09 | -175958555.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108691080.0 | 58.98 | 0.00 | 0.00 |
October | 0.307884E+09 | -189227589.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118656211.7 | 58.99 | 0.00 | 0.00 |
November | 0.313624E+09 | -195264345.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118360071.5 | 58.99 | 0.00 | 0.00 |
December | 0.337715E+09 | -212553280.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125161620.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.379773E+10 | -0.240108E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139665E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284650E+09 | -231510924.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125574300.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.354645E+09 | -175958555.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108411654.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.349095E+09 | -223086318.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126008432.5 | 58.99 | 0.00 | 0.00 |
February | 0.319721E+09 | -205670684.5 | 0.00 | 0.00 | 672.00 | 0.00 | -114049969.2 | 58.99 | 0.00 | 0.00 |
March | 0.355028E+09 | -231498506.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123529507.0 | 58.99 | 0.00 | 0.00 |
April | 0.327236E+09 | -209282256.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117953969.3 | 59.00 | 0.00 | 0.00 |
May | 0.322109E+09 | -206004121.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116105018.5 | 58.99 | 0.00 | 0.00 |
June | 0.298166E+09 | -189703257.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108463133.9 | 58.99 | 0.00 | 0.00 |
July | 0.290111E+09 | -179344598.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110766458.2 | 58.99 | 0.00 | 0.00 |
August | 0.294580E+09 | -183505638.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111074437.6 | 58.99 | 0.00 | 0.00 |
September | 0.284754E+09 | -175935249.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108819237.0 | 58.99 | 0.00 | 0.00 |
October | 0.308379E+09 | -189231127.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119147753.9 | 58.99 | 0.00 | 0.00 |
November | 0.314044E+09 | -195267803.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118776205.3 | 58.99 | 0.00 | 0.00 |
December | 0.338129E+09 | -212559893.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125569194.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380135E+10 | -0.240109E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140026E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284754E+09 | -231498506.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126008432.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355028E+09 | -175935249.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108463133.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338540E+09 | -210851031.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127689233.8 | 58.99 | 0.00 | 0.00 |
February | 0.310088E+09 | -194482667.4 | 0.00 | 0.00 | 672.00 | 0.00 | -115605537.9 | 59.00 | 0.00 | 0.00 |
March | 0.344085E+09 | -219040418.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125044522.9 | 59.00 | 0.00 | 0.00 |
April | 0.317551E+09 | -198076063.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119474543.2 | 58.99 | 0.00 | 0.00 |
May | 0.312946E+09 | -194796273.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118149583.6 | 58.99 | 0.00 | 0.00 |
June | 0.288792E+09 | -179491854.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109299747.7 | 59.00 | 0.00 | 0.00 |
July | 0.281038E+09 | -169605949.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111432086.2 | 58.99 | 0.00 | 0.00 |
August | 0.285384E+09 | -173615701.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111768470.5 | 59.00 | 0.00 | 0.00 |
September | 0.276109E+09 | -166486311.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109623002.7 | 58.99 | 0.00 | 0.00 |
October | 0.299558E+09 | -178826256.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120732022.0 | 59.00 | 0.00 | 0.00 |
November | 0.304479E+09 | -184434149.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120044631.1 | 58.99 | 0.00 | 0.00 |
December | 0.328210E+09 | -201018949.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127190587.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368678E+10 | -0.227073E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141605E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276109E+09 | -219040418.0 | 0.00 | 0.00 | 672.00 | 0.00 | -127689233.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344085E+09 | -166486311.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109299747.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338423E+09 | -210847609.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127575837.2 | 58.99 | 0.00 | 0.00 |
February | 0.309988E+09 | -194478008.9 | 0.00 | 0.00 | 672.00 | 0.00 | -115510214.6 | 59.00 | 0.00 | 0.00 |
March | 0.344065E+09 | -219042851.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125022039.0 | 58.99 | 0.00 | 0.00 |
April | 0.317625E+09 | -198073311.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119552030.0 | 58.99 | 0.00 | 0.00 |
May | 0.313175E+09 | -194793248.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118382135.9 | 58.99 | 0.00 | 0.00 |
June | 0.288888E+09 | -179485629.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109402796.7 | 59.00 | 0.00 | 0.00 |
July | 0.281136E+09 | -169621411.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111514831.2 | 58.98 | 0.00 | 0.00 |
August | 0.285481E+09 | -173638154.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111842902.4 | 58.99 | 0.00 | 0.00 |
September | 0.276205E+09 | -166481252.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109723799.2 | 58.99 | 0.00 | 0.00 |
October | 0.299672E+09 | -178855622.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120816519.8 | 58.99 | 0.00 | 0.00 |
November | 0.304497E+09 | -184407481.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120089346.6 | 58.99 | 0.00 | 0.00 |
December | 0.328117E+09 | -201025749.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127091319.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368727E+10 | -0.227075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141652E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276205E+09 | -219042851.1 | 0.00 | 0.00 | 672.00 | 0.00 | -127575837.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344065E+09 | -166481252.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109402796.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338511E+09 | -210850403.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127660114.4 | 58.99 | 0.00 | 0.00 |
February | 0.310053E+09 | -194481883.9 | 0.00 | 0.00 | 672.00 | 0.00 | -115571565.8 | 59.00 | 0.00 | 0.00 |
March | 0.344197E+09 | -219043684.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125153354.4 | 59.00 | 0.00 | 0.00 |
April | 0.317793E+09 | -198068518.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119724534.5 | 58.99 | 0.00 | 0.00 |
May | 0.313525E+09 | -194802853.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118722121.6 | 58.99 | 0.00 | 0.00 |
June | 0.289000E+09 | -179514330.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109485850.4 | 58.99 | 0.00 | 0.00 |
July | 0.281214E+09 | -169597077.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111617007.5 | 58.99 | 0.00 | 0.00 |
August | 0.285544E+09 | -173616934.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111927332.1 | 59.00 | 0.00 | 0.00 |
September | 0.276311E+09 | -166487176.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109823460.5 | 58.99 | 0.00 | 0.00 |
October | 0.299871E+09 | -178854310.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121016781.0 | 58.99 | 0.00 | 0.00 |
November | 0.304616E+09 | -184417431.7 | 0.00 | 0.00 | 720.00 | 0.00 | -120198948.8 | 58.99 | 0.00 | 0.00 |
December | 0.328202E+09 | -201016377.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127185697.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368884E+10 | -0.227075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141809E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276311E+09 | -219043684.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127660114.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344197E+09 | -166487176.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109485850.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254221E+11 | 61030.26 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240077E+11 | 61030.26 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146115E+11 | 61030.26 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596246E+10 | 61030.26 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265329E+09 | 48859.80 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2901921.29 | 2129.17 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262411E+10 | 61030.26 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.854924E+10 | 61030.26 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234759E+11 | 61030.26 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254221E+11 | 61030.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.882027E+10 | 32070.03 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830569E+10 | 32070.03 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.453872E+10 | 32070.03 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137706E+10 | 32070.03 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7964407.58 | 1683.50 | 01-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.440944E+09 | 24187.98 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232765E+10 | 32070.03 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.804743E+10 | 32070.03 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.882027E+10 | 32070.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100664E+11 | 32207.57 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940938E+10 | 32207.57 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547814E+10 | 32207.57 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198341E+10 | 32207.57 | 05-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44647139.07 | 5764.24 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823189E+09 | 28160.74 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315137E+10 | 32207.57 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.921454E+10 | 32207.57 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100664E+11 | 32207.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103199E+11 | 32078.57 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962402E+10 | 32078.57 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567485E+10 | 32078.57 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214735E+10 | 32078.57 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67964559.16 | 10603.66 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.937034E+09 | 32078.57 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336941E+10 | 32078.57 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944646E+10 | 32078.57 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103199E+11 | 32078.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107321E+11 | 32044.05 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999303E+10 | 32044.05 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601150E+10 | 32044.05 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240225E+10 | 32044.05 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112822E+09 | 14511.93 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 360364.40 | 525.16 | 30-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110204E+10 | 32044.05 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368359E+10 | 32044.05 | 19-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.983824E+10 | 32044.05 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107321E+11 | 32044.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206950E+11 | 59133.55 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192028E+11 | 59133.55 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117782E+11 | 59133.55 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.499977E+10 | 59133.55 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.325556E+09 | 59133.55 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3074970.00 | 2346.72 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252857E+10 | 59133.55 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766542E+10 | 59133.55 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190577E+11 | 59133.55 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206950E+11 | 59133.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107619E+11 | 30354.22 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999170E+10 | 30354.22 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615197E+10 | 30354.22 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263300E+10 | 30354.22 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182582E+09 | 30354.22 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1505961.72 | 1608.81 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132344E+10 | 30354.22 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398980E+10 | 30354.22 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.991393E+10 | 30354.22 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107619E+11 | 30354.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108477E+11 | 30219.14 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100653E+11 | 30219.14 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625066E+10 | 30219.14 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272870E+10 | 30219.14 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211741E+09 | 30219.14 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2427053.63 | 1731.91 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138750E+10 | 30219.14 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407676E+10 | 30219.14 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.999906E+10 | 30219.14 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108477E+11 | 30219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113114E+11 | 30011.30 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104819E+11 | 30011.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667118E+10 | 30011.30 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.306572E+10 | 30011.30 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313304E+09 | 30011.30 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6819737.73 | 2478.32 | 30-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158406E+10 | 30011.30 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439449E+10 | 30011.30 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104337E+11 | 30011.30 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113114E+11 | 30011.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141041E+11 | 30936.81 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132757E+11 | 30936.81 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863684E+10 | 30936.81 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425457E+10 | 30936.81 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.716017E+09 | 30936.81 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4461864.59 | 5611.09 | 14-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37398469.97 | 24983.38 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219616E+10 | 30936.81 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556011E+10 | 30936.81 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129445E+11 | 30936.81 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.617298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141041E+11 | 30936.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.332848E+09 | 0.282388E+09 | 9054.45 | 15-MAR-14:00 | 8337.50 | 0.00 |
April | 0.00 | 0.00 | 1263991.51 | 1123893.19 | 779.68 | 08-APR-13:00 | 703.09 | 0.00 |
May | 0.00 | 0.00 | 0.103763E+10 | 0.920211E+09 | 11715.00 | 14-MAY-15:00 | 9247.78 | 0.00 |
June | 0.00 | 0.00 | 0.968329E+10 | 0.697662E+10 | 45390.06 | 18-JUN-07:03 | 22634.99 | 0.00 |
July | 0.00 | 0.00 | 0.206609E+11 | 0.137352E+11 | 46383.58 | 21-JUL-07:02 | 23342.95 | 0.00 |
August | 0.00 | 0.00 | 0.161819E+11 | 0.120287E+11 | 45429.07 | 14-AUG-07:02 | 25895.02 | 0.00 |
September | 0.00 | 0.00 | 0.620222E+10 | 0.430869E+10 | 44164.95 | 17-SEP-07:02 | 24919.04 | 0.00 |
October | 0.00 | 0.00 | 0.220356E+09 | 0.190702E+09 | 6507.33 | 11-OCT-16:10 | 5586.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.543205E+11 | 0.384436E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206609E+11 | 0.137352E+11 | 46383.58 | 25895.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.245842E+09 | 0.209210E+09 | 21562.83 | 15-MAR-20:01 | 17956.56 | 0.00 |
April | 0.00 | 0.00 | 14241491.80 | 13006071.29 | 3050.75 | 23-APR-17:10 | 3050.75 | 0.00 |
May | 0.00 | 0.00 | 0.928966E+09 | 0.832853E+09 | 22177.41 | 14-MAY-17:55 | 14657.79 | 0.00 |
June | 0.00 | 0.00 | 0.637751E+10 | 0.469816E+10 | 24027.91 | 18-JUN-07:03 | 12769.25 | 0.00 |
July | 0.00 | 0.00 | 0.125342E+11 | 0.853274E+10 | 23952.98 | 21-JUL-20:05 | 11841.30 | 0.00 |
August | 0.00 | 0.00 | 0.996606E+10 | 0.747983E+10 | 23859.87 | 15-AUG-07:02 | 13067.58 | 0.00 |
September | 0.00 | 0.00 | 0.413062E+10 | 0.291418E+10 | 23824.67 | 15-SEP-20:03 | 11404.21 | 0.00 |
October | 0.00 | 0.00 | 0.231440E+09 | 0.196374E+09 | 21550.43 | 22-OCT-17:02 | 17629.71 | 0.00 |
November | 0.00 | 0.00 | 2294584.69 | 2017658.26 | 1455.91 | 05-NOV-17:20 | 1122.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344312E+11 | 0.248784E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125342E+11 | 0.853274E+10 | 24027.91 | 17956.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188728E+09 | 0.162108E+09 | 4973.18 | 15-MAR-14:00 | 4645.06 | 0.00 |
April | 0.00 | 0.00 | 5149341.09 | 4596672.43 | 1161.11 | 08-APR-13:00 | 1059.35 | 0.00 |
May | 0.00 | 0.00 | 0.596123E+09 | 0.536084E+09 | 5901.41 | 14-MAY-15:00 | 4747.09 | 0.00 |
June | 0.00 | 0.00 | 0.423207E+10 | 0.312343E+10 | 24332.71 | 18-JUN-07:03 | 12210.36 | 0.00 |
July | 0.00 | 0.00 | 0.856180E+10 | 0.584739E+10 | 24789.21 | 21-JUL-06:02 | 13182.04 | 0.00 |
August | 0.00 | 0.00 | 0.691832E+10 | 0.530249E+10 | 24578.83 | 14-AUG-06:02 | 11064.78 | 0.00 |
September | 0.00 | 0.00 | 0.282253E+10 | 0.201727E+10 | 23783.23 | 16-SEP-06:03 | 12570.34 | 0.00 |
October | 0.00 | 0.00 | 0.108329E+09 | 95591668.47 | 3383.24 | 11-OCT-15:00 | 3010.93 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234331E+11 | 0.170890E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.856180E+10 | 0.584739E+10 | 24789.21 | 13182.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176590E+09 | 0.151872E+09 | 4797.81 | 15-MAR-14:00 | 4479.02 | 0.00 |
April | 0.00 | 0.00 | 3572385.47 | 3194446.53 | 948.96 | 08-APR-13:00 | 865.71 | 0.00 |
May | 0.00 | 0.00 | 0.554890E+09 | 0.499142E+09 | 5668.49 | 14-MAY-15:00 | 4549.22 | 0.00 |
June | 0.00 | 0.00 | 0.419517E+10 | 0.309448E+10 | 24400.89 | 18-JUN-07:03 | 12240.17 | 0.00 |
July | 0.00 | 0.00 | 0.856559E+10 | 0.585005E+10 | 24864.69 | 21-JUL-06:02 | 13256.38 | 0.00 |
August | 0.00 | 0.00 | 0.691910E+10 | 0.530417E+10 | 24649.33 | 14-AUG-06:02 | 11104.38 | 0.00 |
September | 0.00 | 0.00 | 0.277380E+10 | 0.198043E+10 | 23851.04 | 16-SEP-06:03 | 12604.08 | 0.00 |
October | 0.00 | 0.00 | 90653657.89 | 80284073.80 | 3078.28 | 11-OCT-15:00 | 2739.14 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232794E+11 | 0.169636E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.856559E+10 | 0.585005E+10 | 24864.69 | 13256.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.159014E+09 | 0.136799E+09 | 4500.46 | 15-MAR-14:00 | 4195.20 | 0.00 |
April | 0.00 | 0.00 | 1501730.92 | 1345221.11 | 590.84 | 08-APR-13:00 | 538.23 | 0.00 |
May | 0.00 | 0.00 | 0.484314E+09 | 0.434920E+09 | 5344.01 | 14-MAY-15:00 | 4272.55 | 0.00 |
June | 0.00 | 0.00 | 0.401139E+10 | 0.295325E+10 | 24223.47 | 18-JUN-07:03 | 12099.24 | 0.00 |
July | 0.00 | 0.00 | 0.831700E+10 | 0.567271E+10 | 24674.28 | 21-JUL-06:02 | 13007.46 | 0.00 |
August | 0.00 | 0.00 | 0.670781E+10 | 0.514049E+10 | 24471.65 | 14-AUG-06:02 | 10987.41 | 0.00 |
September | 0.00 | 0.00 | 0.261946E+10 | 0.186546E+10 | 23680.10 | 16-SEP-06:03 | 12466.45 | 0.00 |
October | 0.00 | 0.00 | 73671776.99 | 65274603.70 | 2715.70 | 11-OCT-16:10 | 2354.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223742E+11 | 0.162703E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.831700E+10 | 0.567271E+10 | 24674.28 | 13007.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.252995E+09 | 0.211607E+09 | 7986.45 | 15-MAR-14:10 | 7227.50 | 0.00 |
April | 0.00 | 0.00 | 773212.73 | 677302.86 | 276.28 | 08-APR-13:20 | 243.02 | 0.00 |
May | 0.00 | 0.00 | 0.743167E+09 | 0.656372E+09 | 10208.27 | 14-MAY-15:00 | 7874.93 | 0.00 |
June | 0.00 | 0.00 | 0.694136E+10 | 0.499705E+10 | 43799.28 | 18-JUN-08:62 | 23849.78 | 0.00 |
July | 0.00 | 0.00 | 0.147723E+11 | 0.988985E+10 | 44342.39 | 16-JUL-08:62 | 23005.75 | 0.00 |
August | 0.00 | 0.00 | 0.119063E+11 | 0.897447E+10 | 44381.70 | 14-AUG-07:02 | 23175.68 | 0.00 |
September | 0.00 | 0.00 | 0.438048E+10 | 0.306392E+10 | 42564.04 | 17-SEP-08:62 | 23218.21 | 0.00 |
October | 0.00 | 0.00 | 0.103463E+09 | 90267930.39 | 4911.14 | 11-OCT-15:00 | 4270.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.391008E+11 | 0.278842E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.147723E+11 | 0.988985E+10 | 44381.70 | 23849.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.124433E+09 | 0.104477E+09 | 4053.87 | 15-MAR-14:10 | 3675.15 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.353967E+09 | 0.312831E+09 | 5172.07 | 14-MAY-15:00 | 3991.02 | 0.00 |
June | 0.00 | 0.00 | 0.351799E+10 | 0.253766E+10 | 22761.96 | 18-JUN-08:62 | 12366.26 | 0.00 |
July | 0.00 | 0.00 | 0.755170E+10 | 0.506925E+10 | 23048.05 | 16-JUL-08:62 | 11928.34 | 0.00 |
August | 0.00 | 0.00 | 0.608769E+10 | 0.460050E+10 | 23072.25 | 14-AUG-07:02 | 12032.46 | 0.00 |
September | 0.00 | 0.00 | 0.221693E+10 | 0.155214E+10 | 22124.09 | 17-SEP-08:62 | 12085.43 | 0.00 |
October | 0.00 | 0.00 | 49161462.44 | 42981705.32 | 2459.30 | 11-OCT-15:00 | 2143.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199019E+11 | 0.142198E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.755170E+10 | 0.506925E+10 | 23072.25 | 12366.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.119733E+09 | 0.100492E+09 | 3963.87 | 15-MAR-14:10 | 3589.86 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.326727E+09 | 0.288122E+09 | 5035.36 | 14-MAY-15:00 | 3877.46 | 0.00 |
June | 0.00 | 0.00 | 0.343934E+10 | 0.247637E+10 | 22656.56 | 18-JUN-08:62 | 12241.96 | 0.00 |
July | 0.00 | 0.00 | 0.746039E+10 | 0.500270E+10 | 22944.71 | 16-JUL-08:62 | 11828.59 | 0.00 |
August | 0.00 | 0.00 | 0.601246E+10 | 0.454106E+10 | 22968.38 | 14-AUG-07:02 | 11935.41 | 0.00 |
September | 0.00 | 0.00 | 0.216531E+10 | 0.151358E+10 | 22027.72 | 17-SEP-08:62 | 12019.39 | 0.00 |
October | 0.00 | 0.00 | 45616307.34 | 39852004.98 | 2351.07 | 11-OCT-15:00 | 2047.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195696E+11 | 0.139622E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.746039E+10 | 0.500270E+10 | 22968.38 | 12241.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.105798E+09 | 88871083.06 | 3707.38 | 15-MAR-14:10 | 3352.97 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.268398E+09 | 0.235527E+09 | 4688.84 | 14-MAY-15:00 | 3595.53 | 0.00 |
June | 0.00 | 0.00 | 0.324969E+10 | 0.233200E+10 | 21230.57 | 18-JUN-08:62 | 11261.98 | 0.00 |
July | 0.00 | 0.00 | 0.725936E+10 | 0.486316E+10 | 22765.24 | 16-JUL-08:62 | 11602.38 | 0.00 |
August | 0.00 | 0.00 | 0.584989E+10 | 0.441962E+10 | 22786.83 | 14-AUG-07:02 | 11707.12 | 0.00 |
September | 0.00 | 0.00 | 0.203832E+10 | 0.142068E+10 | 21866.80 | 17-SEP-08:62 | 11902.17 | 0.00 |
October | 0.00 | 0.00 | 38287774.60 | 33448274.93 | 2130.22 | 11-OCT-15:00 | 1853.37 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188097E+11 | 0.133933E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.725936E+10 | 0.486316E+10 | 22786.83 | 11902.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 86546419.77 | 73417438.30 | 3438.82 | 15-MAR-14:10 | 3123.77 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.190705E+09 | 0.166139E+09 | 4194.63 | 14-MAY-15:00 | 3210.51 | 0.00 |
June | 0.00 | 0.00 | 0.308558E+10 | 0.222049E+10 | 13253.06 | 27-JUN-13:00 | 8395.32 | 0.00 |
July | 0.00 | 0.00 | 0.724618E+10 | 0.490067E+10 | 24070.25 | 21-JUL-07:02 | 11007.48 | 0.00 |
August | 0.00 | 0.00 | 0.588224E+10 | 0.449348E+10 | 23818.78 | 14-AUG-07:02 | 11426.99 | 0.00 |
September | 0.00 | 0.00 | 0.191288E+10 | 0.134109E+10 | 18375.56 | 17-SEP-08:62 | 9775.52 | 0.00 |
October | 0.00 | 0.00 | 35007573.50 | 30889993.02 | 2025.11 | 11-OCT-15:00 | 1774.43 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184391E+11 | 0.132262E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.724618E+10 | 0.490067E+10 | 24070.25 | 11426.99 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201214E+10 | 0.45 | 2058.30 | 01-JAN-08:61 | 0.90 |
February | 0.184156E+10 | 0.46 | 2058.30 | 01-FEB-08:61 | 0.90 |
March | 0.179747E+10 | 0.42 | 2058.30 | 01-MAR-08:61 | 0.90 |
April | 0.156768E+10 | 0.39 | 2058.30 | 01-APR-07:01 | 0.90 |
May | 0.149920E+10 | 0.37 | 1812.03 | 01-MAY-07:01 | 0.85 |
June | 0.145389E+10 | 0.37 | 2058.30 | 18-JUN-07:03 | 0.88 |
July | 0.150665E+10 | 0.37 | 2058.30 | 15-JUL-07:03 | 0.89 |
August | 0.150121E+10 | 0.37 | 2058.30 | 06-AUG-07:02 | 0.89 |
September | 0.144988E+10 | 0.37 | 2058.30 | 17-SEP-07:02 | 0.89 |
October | 0.154696E+10 | 0.38 | 2058.30 | 16-OCT-07:01 | 0.90 |
November | 0.161672E+10 | 0.40 | 2058.30 | 03-NOV-07:01 | 0.90 |
December | 0.197779E+10 | 0.45 | 2058.30 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.197711E+11 | 0.40 | |||
Minimum of Months | 0.144988E+10 | 0.37 | 1812.03 | 0.85 | |
Maximum of Months | 0.201214E+10 | 0.46 | 2058.30 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.819062E+09 | 0.36 | 1155.46 | 01-JAN-08:61 | 0.93 |
February | 0.748460E+09 | 0.37 | 1155.46 | 01-FEB-08:61 | 0.93 |
March | 0.745457E+09 | 0.33 | 1155.46 | 01-MAR-08:61 | 0.93 |
April | 0.666633E+09 | 0.33 | 1155.46 | 01-APR-07:01 | 0.93 |
May | 0.751340E+09 | 0.37 | 498.58 | 01-MAY-08:20 | 0.59 |
June | 0.742736E+09 | 0.37 | 1155.46 | 18-JUN-07:03 | 0.91 |
July | 0.746465E+09 | 0.36 | 1155.46 | 15-JUL-07:03 | 0.92 |
August | 0.754609E+09 | 0.36 | 1155.46 | 06-AUG-07:02 | 0.92 |
September | 0.765009E+09 | 0.37 | 1155.46 | 14-SEP-07:03 | 0.92 |
October | 0.702727E+09 | 0.35 | 985.07 | 30-OCT-07:01 | 0.86 |
November | 0.667406E+09 | 0.32 | 1155.46 | 24-NOV-08:61 | 0.93 |
December | 0.798682E+09 | 0.35 | 1155.46 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.890859E+10 | 0.35 | |||
Minimum of Months | 0.666633E+09 | 0.32 | 498.58 | 0.59 | |
Maximum of Months | 0.819062E+09 | 0.37 | 1155.46 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.890745E+09 | 0.36 | 1162.23 | 01-JAN-08:61 | 0.93 |
February | 0.812922E+09 | 0.37 | 1162.23 | 01-FEB-07:01 | 0.93 |
March | 0.804791E+09 | 0.34 | 1162.23 | 01-MAR-07:01 | 0.93 |
April | 0.695653E+09 | 0.32 | 1162.23 | 05-APR-06:01 | 0.93 |
May | 0.680454E+09 | 0.31 | 589.70 | 01-MAY-06:03 | 0.65 |
June | 0.663688E+09 | 0.31 | 1162.23 | 18-JUN-07:03 | 0.91 |
July | 0.676009E+09 | 0.30 | 1162.23 | 15-JUL-06:02 | 0.92 |
August | 0.688115E+09 | 0.31 | 1162.23 | 06-AUG-07:02 | 0.92 |
September | 0.653036E+09 | 0.30 | 1162.23 | 14-SEP-06:03 | 0.92 |
October | 0.690616E+09 | 0.31 | 1074.61 | 30-OCT-06:02 | 0.90 |
November | 0.720941E+09 | 0.33 | 1162.23 | 24-NOV-07:01 | 0.93 |
December | 0.868953E+09 | 0.36 | 1162.23 | 02-DEC-07:02 | 0.93 |
Annual Sum or Average | 0.884592E+10 | 0.33 | |||
Minimum of Months | 0.653036E+09 | 0.30 | 589.70 | 0.65 | |
Maximum of Months | 0.890745E+09 | 0.37 | 1162.23 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.900403E+09 | 0.37 | 1166.47 | 01-JAN-08:61 | 0.93 |
February | 0.821390E+09 | 0.37 | 1166.47 | 01-FEB-07:01 | 0.93 |
March | 0.812495E+09 | 0.34 | 1166.47 | 01-MAR-07:01 | 0.93 |
April | 0.701939E+09 | 0.32 | 1166.47 | 03-APR-06:02 | 0.93 |
May | 0.683447E+09 | 0.31 | 697.94 | 01-MAY-06:03 | 0.72 |
June | 0.666070E+09 | 0.31 | 1166.47 | 18-JUN-07:03 | 0.91 |
July | 0.678336E+09 | 0.30 | 1166.47 | 15-JUL-06:02 | 0.92 |
August | 0.690563E+09 | 0.31 | 1166.47 | 06-AUG-07:02 | 0.92 |
September | 0.655414E+09 | 0.30 | 1166.47 | 14-SEP-06:03 | 0.92 |
October | 0.695689E+09 | 0.31 | 1166.47 | 30-OCT-06:02 | 0.93 |
November | 0.728602E+09 | 0.33 | 1166.47 | 23-NOV-08:62 | 0.93 |
December | 0.877986E+09 | 0.36 | 1166.47 | 02-DEC-07:02 | 0.93 |
Annual Sum or Average | 0.891234E+10 | 0.33 | |||
Minimum of Months | 0.655414E+09 | 0.30 | 697.94 | 0.72 | |
Maximum of Months | 0.900403E+09 | 0.37 | 1166.47 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.901300E+09 | 0.37 | 1155.76 | 01-JAN-08:61 | 0.93 |
February | 0.822061E+09 | 0.37 | 1155.76 | 01-FEB-07:01 | 0.93 |
March | 0.812456E+09 | 0.35 | 1155.76 | 01-MAR-07:01 | 0.93 |
April | 0.701063E+09 | 0.32 | 1155.76 | 03-APR-06:02 | 0.93 |
May | 0.678147E+09 | 0.31 | 776.35 | 01-MAY-06:03 | 0.76 |
June | 0.659817E+09 | 0.31 | 1155.76 | 18-JUN-07:03 | 0.91 |
July | 0.671451E+09 | 0.30 | 1155.76 | 15-JUL-06:02 | 0.92 |
August | 0.683914E+09 | 0.31 | 1155.76 | 06-AUG-07:02 | 0.92 |
September | 0.649384E+09 | 0.30 | 1155.76 | 14-SEP-06:03 | 0.92 |
October | 0.692897E+09 | 0.31 | 1155.76 | 30-OCT-06:02 | 0.93 |
November | 0.728792E+09 | 0.33 | 1155.76 | 19-NOV-08:62 | 0.93 |
December | 0.878626E+09 | 0.36 | 1155.76 | 02-DEC-07:02 | 0.93 |
Annual Sum or Average | 0.887991E+10 | 0.33 | |||
Minimum of Months | 0.649384E+09 | 0.30 | 776.35 | 0.76 | |
Maximum of Months | 0.901300E+09 | 0.37 | 1155.76 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146411E+10 | 0.33 | 1967.30 | 01-JAN-09:01 | 0.90 |
February | 0.133564E+10 | 0.34 | 1967.30 | 01-FEB-08:61 | 0.90 |
March | 0.130878E+10 | 0.31 | 1967.30 | 01-MAR-08:61 | 0.90 |
April | 0.111965E+10 | 0.29 | 1967.30 | 01-APR-07:01 | 0.90 |
May | 0.106884E+10 | 0.27 | 1967.30 | 01-MAY-07:01 | 0.89 |
June | 0.103852E+10 | 0.28 | 1967.30 | 18-JUN-08:62 | 0.88 |
July | 0.105880E+10 | 0.27 | 1967.30 | 15-JUL-07:03 | 0.89 |
August | 0.107733E+10 | 0.28 | 1967.30 | 06-AUG-08:62 | 0.89 |
September | 0.102035E+10 | 0.27 | 1967.30 | 17-SEP-08:62 | 0.89 |
October | 0.110148E+10 | 0.28 | 1967.30 | 09-OCT-08:61 | 0.90 |
November | 0.117286E+10 | 0.30 | 1967.30 | 03-NOV-07:01 | 0.90 |
December | 0.142576E+10 | 0.33 | 1967.30 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.141921E+11 | 0.30 | |||
Minimum of Months | 0.102035E+10 | 0.27 | 1967.30 | 0.88 | |
Maximum of Months | 0.146411E+10 | 0.34 | 1967.30 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.792709E+09 | 0.35 | 1061.24 | 01-JAN-09:01 | 0.93 |
February | 0.723250E+09 | 0.35 | 1061.24 | 01-FEB-08:61 | 0.93 |
March | 0.708231E+09 | 0.33 | 1061.24 | 01-MAR-08:61 | 0.93 |
April | 0.605378E+09 | 0.30 | 1061.24 | 01-APR-07:01 | 0.93 |
May | 0.576898E+09 | 0.28 | 1061.24 | 01-MAY-07:01 | 0.93 |
June | 0.560098E+09 | 0.28 | 1061.24 | 18-JUN-08:62 | 0.91 |
July | 0.570461E+09 | 0.28 | 1061.24 | 16-JUL-08:62 | 0.91 |
August | 0.580896E+09 | 0.29 | 1061.24 | 07-AUG-07:02 | 0.92 |
September | 0.550382E+09 | 0.28 | 1061.24 | 17-SEP-08:62 | 0.92 |
October | 0.594718E+09 | 0.29 | 1061.24 | 09-OCT-08:61 | 0.93 |
November | 0.633840E+09 | 0.31 | 1061.24 | 03-NOV-07:01 | 0.93 |
December | 0.771865E+09 | 0.34 | 1061.24 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.766872E+10 | 0.31 | |||
Minimum of Months | 0.550382E+09 | 0.28 | 1061.24 | 0.91 | |
Maximum of Months | 0.792709E+09 | 0.35 | 1061.24 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.790861E+09 | 0.35 | 1055.02 | 01-JAN-09:01 | 0.93 |
February | 0.721531E+09 | 0.35 | 1055.02 | 01-FEB-08:61 | 0.93 |
March | 0.706720E+09 | 0.33 | 1055.02 | 01-MAR-08:61 | 0.93 |
April | 0.604079E+09 | 0.30 | 1055.02 | 01-APR-07:01 | 0.93 |
May | 0.574144E+09 | 0.28 | 1055.02 | 01-MAY-07:01 | 0.93 |
June | 0.556758E+09 | 0.28 | 1055.02 | 18-JUN-08:62 | 0.91 |
July | 0.566919E+09 | 0.28 | 1055.02 | 16-JUL-08:62 | 0.91 |
August | 0.577399E+09 | 0.29 | 1055.02 | 07-AUG-07:02 | 0.92 |
September | 0.547159E+09 | 0.28 | 1055.02 | 17-SEP-08:62 | 0.92 |
October | 0.592696E+09 | 0.29 | 1055.02 | 09-OCT-08:61 | 0.93 |
November | 0.632317E+09 | 0.31 | 1055.02 | 03-NOV-07:01 | 0.93 |
December | 0.770046E+09 | 0.34 | 1055.02 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.764063E+10 | 0.31 | |||
Minimum of Months | 0.547159E+09 | 0.28 | 1055.02 | 0.91 | |
Maximum of Months | 0.790861E+09 | 0.35 | 1055.02 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.795439E+09 | 0.35 | 1046.10 | 01-JAN-09:01 | 0.93 |
February | 0.725909E+09 | 0.36 | 1046.10 | 01-FEB-08:61 | 0.93 |
March | 0.710444E+09 | 0.33 | 1046.10 | 01-MAR-08:61 | 0.93 |
April | 0.606417E+09 | 0.30 | 1046.10 | 01-APR-07:01 | 0.93 |
May | 0.571448E+09 | 0.29 | 1046.10 | 01-MAY-07:01 | 0.93 |
June | 0.551886E+09 | 0.28 | 977.20 | 18-JUN-08:62 | 0.89 |
July | 0.561714E+09 | 0.28 | 1046.10 | 16-JUL-08:62 | 0.91 |
August | 0.572277E+09 | 0.28 | 1046.10 | 07-AUG-07:02 | 0.92 |
September | 0.542575E+09 | 0.28 | 1046.10 | 17-SEP-08:62 | 0.92 |
October | 0.592000E+09 | 0.29 | 1046.10 | 09-OCT-08:61 | 0.93 |
November | 0.634207E+09 | 0.31 | 1046.10 | 02-NOV-07:01 | 0.93 |
December | 0.774119E+09 | 0.34 | 1046.10 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.763844E+10 | 0.31 | |||
Minimum of Months | 0.542575E+09 | 0.28 | 977.20 | 0.89 | |
Maximum of Months | 0.795439E+09 | 0.36 | 1046.10 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.899948E+09 | 0.43 | 1105.19 | 01-JAN-09:01 | 0.93 |
February | 0.830637E+09 | 0.46 | 1105.19 | 01-FEB-08:61 | 0.93 |
March | 0.790668E+09 | 0.36 | 1105.19 | 01-MAR-08:61 | 0.94 |
April | 0.664235E+09 | 0.31 | 1105.19 | 01-APR-07:01 | 0.93 |
May | 0.612148E+09 | 0.29 | 1105.19 | 01-MAY-07:01 | 0.93 |
June | 0.583016E+09 | 0.28 | 562.34 | 14-JUN-07:03 | 0.66 |
July | 0.593027E+09 | 0.28 | 1105.19 | 16-JUL-08:62 | 0.91 |
August | 0.604395E+09 | 0.28 | 1105.19 | 07-AUG-07:02 | 0.92 |
September | 0.573791E+09 | 0.28 | 977.58 | 30-SEP-07:02 | 0.88 |
October | 0.637508E+09 | 0.29 | 1105.19 | 08-OCT-08:61 | 0.93 |
November | 0.692106E+09 | 0.32 | 1105.19 | 01-NOV-07:02 | 0.93 |
December | 0.870082E+09 | 0.40 | 1105.19 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.835156E+10 | 0.33 | |||
Minimum of Months | 0.573791E+09 | 0.28 | 562.34 | 0.66 | |
Maximum of Months | 0.899948E+09 | 0.46 | 1105.19 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201214E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.184156E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.188924E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156805E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177925E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.389012E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.657572E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.555351E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.302060E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160667E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.161672E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197779E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.333314E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.156805E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.657572E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.819062E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.748460E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.810053E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.670529E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.986122E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.227516E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.370233E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314924E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.176497E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.761628E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.668043E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.798682E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.668043E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.370233E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.890745E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.812922E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.855617E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.697080E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.837454E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170951E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.273777E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.239008E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.135378E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.719504E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720941E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.868953E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.697080E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.273777E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.900403E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.821390E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.860297E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.702934E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.830207E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170365E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274189E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.239349E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134465E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.719988E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.728602E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.877986E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146255E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.702934E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.274189E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.901300E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.822061E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.855793E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.701485E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.807078E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.165441E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267985E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.233901E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130189E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.712784E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.728792E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.878626E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143831E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.701485E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267985E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.146411E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133564E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137932E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111987E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127161E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.279108E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468945E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.406969E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213219E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113010E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117286E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142576E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.239817E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111987E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468945E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.792709E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.723250E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.742414E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.605378E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.672112E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.143450E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.239804E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208709E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110388E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.608112E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.633840E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.771865E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125732E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.605378E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.239804E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.790861E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.721531E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.739675E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.604079E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.662322E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.141252E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.237369E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.206609E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108819E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.605155E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.632317E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.770046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124665E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.604079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237369E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.795439E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.725909E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.739743E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.606417E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.644459E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136272E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.232280E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.202291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105285E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.602509E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.634207E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.774119E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122841E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.602509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232280E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.899948E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.830637E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.814913E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.664235E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.664780E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135697E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.235810E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.206548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105380E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.647151E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.692106E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.870082E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647151E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.235810E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201214E+10 | 0.00 | 0.254221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184156E+10 | 0.00 | 0.240077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179747E+10 | 0.332848E+09 | 0.146115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156768E+10 | 1263991.51 | 0.596246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149920E+10 | 0.103763E+10 | 0.265329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145389E+10 | 0.968329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150665E+10 | 0.206609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150121E+10 | 0.161819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144988E+10 | 0.620222E+10 | 2901921.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154696E+10 | 0.220356E+09 | 0.262411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161672E+10 | 0.00 | 0.854924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197779E+10 | 0.00 | 0.234759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197711E+11 | 0.543205E+11 | 0.104921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201214E+10 | 0.206609E+11 | 0.254221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.819062E+09 | 0.00 | 0.882027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748460E+09 | 0.00 | 0.830569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745457E+09 | 0.240932E+09 | 0.453872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666633E+09 | 14241491.80 | 0.137706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751340E+09 | 0.883617E+09 | 7964407.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742736E+09 | 0.601308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.746465E+09 | 0.118411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.754609E+09 | 0.947234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.765009E+09 | 0.395517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702727E+09 | 0.222626E+09 | 0.440944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667406E+09 | 2294584.69 | 0.232765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798682E+09 | 0.00 | 0.804743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890859E+10 | 0.326454E+11 | 0.338657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819062E+09 | 0.118411E+11 | 0.882027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.890745E+09 | 0.00 | 0.100664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812922E+09 | 0.00 | 0.940938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.804791E+09 | 0.188728E+09 | 0.547814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695653E+09 | 5149341.09 | 0.198341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.680454E+09 | 0.596123E+09 | 44647139.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.663688E+09 | 0.423207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676009E+09 | 0.856180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688115E+09 | 0.691832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.653036E+09 | 0.282253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690616E+09 | 0.108329E+09 | 0.823189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720941E+09 | 0.00 | 0.315137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868953E+09 | 0.00 | 0.921454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884592E+10 | 0.234331E+11 | 0.401711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.653036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.890745E+09 | 0.856180E+10 | 0.100664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.900403E+09 | 0.00 | 0.103199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821390E+09 | 0.00 | 0.962402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812495E+09 | 0.176590E+09 | 0.567485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701939E+09 | 3572385.47 | 0.214735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.683447E+09 | 0.554890E+09 | 67964559.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666070E+09 | 0.419517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678336E+09 | 0.856559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.690563E+09 | 0.691910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.655414E+09 | 0.277380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.695689E+09 | 90653657.89 | 0.937034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728602E+09 | 0.00 | 0.336941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877986E+09 | 0.00 | 0.944646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891234E+10 | 0.232794E+11 | 0.415870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.655414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900403E+09 | 0.856559E+10 | 0.103199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.901300E+09 | 0.00 | 0.107321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.822061E+09 | 0.00 | 0.999303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812456E+09 | 0.159014E+09 | 0.601150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701063E+09 | 1501730.92 | 0.240225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678147E+09 | 0.484314E+09 | 0.112822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659817E+09 | 0.401139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.671451E+09 | 0.831700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683914E+09 | 0.670781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649384E+09 | 0.261946E+10 | 360364.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692897E+09 | 73671776.99 | 0.110204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728792E+09 | 0.00 | 0.368359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878626E+09 | 0.00 | 0.983824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887991E+10 | 0.223742E+11 | 0.438760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901300E+09 | 0.831700E+10 | 0.107321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146411E+10 | 0.00 | 0.206950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133564E+10 | 0.00 | 0.192028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130878E+10 | 0.252995E+09 | 0.117782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111965E+10 | 773212.73 | 0.499977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106884E+10 | 0.743167E+09 | 0.325556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103852E+10 | 0.694136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105880E+10 | 0.147723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107733E+10 | 0.119063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102035E+10 | 0.438048E+10 | 3074970.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110148E+10 | 0.103463E+09 | 0.252857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117286E+10 | 0.00 | 0.766542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142576E+10 | 0.00 | 0.190577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141921E+11 | 0.391008E+11 | 0.862561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146411E+10 | 0.147723E+11 | 0.206950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.792709E+09 | 0.00 | 0.107619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.723250E+09 | 0.00 | 0.999170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708231E+09 | 0.124433E+09 | 0.615197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605378E+09 | 0.00 | 0.263300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576898E+09 | 0.353967E+09 | 0.182582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560098E+09 | 0.351799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570461E+09 | 0.755170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.580896E+09 | 0.608769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550382E+09 | 0.221693E+10 | 1505961.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594718E+09 | 49161462.44 | 0.132344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633840E+09 | 0.00 | 0.398980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.771865E+09 | 0.00 | 0.991393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766872E+10 | 0.199019E+11 | 0.449498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.550382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.792709E+09 | 0.755170E+10 | 0.107619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.790861E+09 | 0.00 | 0.108477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721531E+09 | 0.00 | 0.100653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706720E+09 | 0.119733E+09 | 0.625066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.604079E+09 | 0.00 | 0.272870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574144E+09 | 0.326727E+09 | 0.211741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.556758E+09 | 0.343934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566919E+09 | 0.746039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.577399E+09 | 0.601246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547159E+09 | 0.216531E+10 | 2427053.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592696E+09 | 45616307.34 | 0.138750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632317E+09 | 0.00 | 0.407676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770046E+09 | 0.00 | 0.999906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764063E+10 | 0.195696E+11 | 0.455698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.790861E+09 | 0.746039E+10 | 0.108477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.795439E+09 | 0.00 | 0.113114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725909E+09 | 0.00 | 0.104819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710444E+09 | 0.105798E+09 | 0.667118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.606417E+09 | 0.00 | 0.306572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571448E+09 | 0.268398E+09 | 0.313304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.551886E+09 | 0.324969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.561714E+09 | 0.725936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572277E+09 | 0.584989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542575E+09 | 0.203832E+10 | 6819737.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592000E+09 | 38287774.60 | 0.158406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634207E+09 | 0.00 | 0.439449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774119E+09 | 0.00 | 0.104337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.763844E+10 | 0.188097E+11 | 0.482626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.795439E+09 | 0.725936E+10 | 0.113114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.899948E+09 | 0.00 | 0.141041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830637E+09 | 0.00 | 0.132757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790668E+09 | 86546419.77 | 0.863684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664235E+09 | 0.00 | 0.425457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.612148E+09 | 0.190705E+09 | 0.716017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583016E+09 | 0.308558E+10 | 4461864.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.593027E+09 | 0.724618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.604395E+09 | 0.588224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573791E+09 | 0.191288E+10 | 37398469.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637508E+09 | 35007573.50 | 0.219616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692106E+09 | 0.00 | 0.556011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870082E+09 | 0.00 | 0.129445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835156E+10 | 0.184391E+11 | 0.617298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.899948E+09 | 0.724618E+10 | 0.141041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.201214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179747E+10 | 0.00 | 0.00 | 0.00 | 91770809.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156768E+10 | 0.00 | 0.00 | 0.00 | 362841.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149920E+10 | 0.00 | 0.00 | 0.00 | 0.280047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145389E+10 | 0.00 | 0.00 | 0.00 | 0.243624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150665E+10 | 0.00 | 0.00 | 0.00 | 0.506907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150121E+10 | 0.00 | 0.00 | 0.00 | 0.405229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144988E+10 | 0.00 | 0.00 | 0.00 | 0.157073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154696E+10 | 0.00 | 0.00 | 0.00 | 59707239.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197711E+11 | 0.00 | 0.00 | 0.00 | 0.135602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201214E+10 | 0.00 | 0.00 | 0.00 | 0.506907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.819062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745457E+09 | 0.00 | 0.00 | 0.00 | 64595805.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666633E+09 | 0.00 | 0.00 | 0.00 | 3896190.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751340E+09 | 0.00 | 0.00 | 0.00 | 0.234782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742736E+09 | 0.00 | 0.00 | 0.00 | 0.153242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.746465E+09 | 0.00 | 0.00 | 0.00 | 0.295586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.754609E+09 | 0.00 | 0.00 | 0.00 | 0.239463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.765009E+09 | 0.00 | 0.00 | 0.00 | 0.999958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702727E+09 | 0.00 | 0.00 | 0.00 | 58901110.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667406E+09 | 0.00 | 0.00 | 0.00 | 636172.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890859E+10 | 0.00 | 0.00 | 0.00 | 0.824568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819062E+09 | 0.00 | 0.00 | 0.00 | 0.295586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.890745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.804791E+09 | 0.00 | 0.00 | 0.00 | 50826107.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695653E+09 | 0.00 | 0.00 | 0.00 | 1426409.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.680454E+09 | 0.00 | 0.00 | 0.00 | 0.157000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.663688E+09 | 0.00 | 0.00 | 0.00 | 0.104582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676009E+09 | 0.00 | 0.00 | 0.00 | 0.206176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688115E+09 | 0.00 | 0.00 | 0.00 | 0.170197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.653036E+09 | 0.00 | 0.00 | 0.00 | 0.700745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690616E+09 | 0.00 | 0.00 | 0.00 | 28888429.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884592E+10 | 0.00 | 0.00 | 0.00 | 0.574844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.653036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.890745E+09 | 0.00 | 0.00 | 0.00 | 0.206176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.900403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812495E+09 | 0.00 | 0.00 | 0.00 | 47801189.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701939E+09 | 0.00 | 0.00 | 0.00 | 994578.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.683447E+09 | 0.00 | 0.00 | 0.00 | 0.146760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666070E+09 | 0.00 | 0.00 | 0.00 | 0.103758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678336E+09 | 0.00 | 0.00 | 0.00 | 0.206356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.690563E+09 | 0.00 | 0.00 | 0.00 | 0.170292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.655414E+09 | 0.00 | 0.00 | 0.00 | 0.689236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.695689E+09 | 0.00 | 0.00 | 0.00 | 24298649.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891234E+10 | 0.00 | 0.00 | 0.00 | 0.571315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.655414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900403E+09 | 0.00 | 0.00 | 0.00 | 0.206356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.901300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.822061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812456E+09 | 0.00 | 0.00 | 0.00 | 43337631.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701063E+09 | 0.00 | 0.00 | 0.00 | 421837.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678147E+09 | 0.00 | 0.00 | 0.00 | 0.128932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659817E+09 | 0.00 | 0.00 | 0.00 | 0.994597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.671451E+09 | 0.00 | 0.00 | 0.00 | 0.200840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683914E+09 | 0.00 | 0.00 | 0.00 | 0.165510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649384E+09 | 0.00 | 0.00 | 0.00 | 0.652503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692897E+09 | 0.00 | 0.00 | 0.00 | 19886712.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887991E+10 | 0.00 | 0.00 | 0.00 | 0.550317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901300E+09 | 0.00 | 0.00 | 0.00 | 0.200840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130878E+10 | 0.00 | 0.00 | 0.00 | 70534241.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111965E+10 | 0.00 | 0.00 | 0.00 | 222671.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106884E+10 | 0.00 | 0.00 | 0.00 | 0.202769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103852E+10 | 0.00 | 0.00 | 0.00 | 0.175256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105880E+10 | 0.00 | 0.00 | 0.00 | 0.363065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107733E+10 | 0.00 | 0.00 | 0.00 | 0.299236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102035E+10 | 0.00 | 0.00 | 0.00 | 0.111184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110148E+10 | 0.00 | 0.00 | 0.00 | 28614941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141921E+11 | 0.00 | 0.00 | 0.00 | 0.978955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146411E+10 | 0.00 | 0.00 | 0.00 | 0.363065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.792709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.723250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708231E+09 | 0.00 | 0.00 | 0.00 | 34182904.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576898E+09 | 0.00 | 0.00 | 0.00 | 95213222.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560098E+09 | 0.00 | 0.00 | 0.00 | 0.874399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570461E+09 | 0.00 | 0.00 | 0.00 | 0.182758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.580896E+09 | 0.00 | 0.00 | 0.00 | 0.150620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550382E+09 | 0.00 | 0.00 | 0.00 | 0.553494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594718E+09 | 0.00 | 0.00 | 0.00 | 13394442.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.771865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766872E+10 | 0.00 | 0.00 | 0.00 | 0.490446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.550382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.792709E+09 | 0.00 | 0.00 | 0.00 | 0.182758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.790861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706720E+09 | 0.00 | 0.00 | 0.00 | 32954926.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.604079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574144E+09 | 0.00 | 0.00 | 0.00 | 88178358.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.556758E+09 | 0.00 | 0.00 | 0.00 | 0.855765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566919E+09 | 0.00 | 0.00 | 0.00 | 0.180678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.577399E+09 | 0.00 | 0.00 | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547159E+09 | 0.00 | 0.00 | 0.00 | 0.541031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592696E+09 | 0.00 | 0.00 | 0.00 | 12458969.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764063E+10 | 0.00 | 0.00 | 0.00 | 0.482585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.790861E+09 | 0.00 | 0.00 | 0.00 | 0.180678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.795439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710444E+09 | 0.00 | 0.00 | 0.00 | 29299445.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.606417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571448E+09 | 0.00 | 0.00 | 0.00 | 73010639.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.551886E+09 | 0.00 | 0.00 | 0.00 | 0.810830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.561714E+09 | 0.00 | 0.00 | 0.00 | 0.176109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572277E+09 | 0.00 | 0.00 | 0.00 | 0.145063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542575E+09 | 0.00 | 0.00 | 0.00 | 0.510276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592000E+09 | 0.00 | 0.00 | 0.00 | 10508874.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.763844E+10 | 0.00 | 0.00 | 0.00 | 0.464565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.795439E+09 | 0.00 | 0.00 | 0.00 | 0.176109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.899948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790668E+09 | 0.00 | 0.00 | 0.00 | 24244341.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.612148E+09 | 0.00 | 0.00 | 0.00 | 52631861.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583016E+09 | 0.00 | 0.00 | 0.00 | 0.773950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.593027E+09 | 0.00 | 0.00 | 0.00 | 0.176507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.604395E+09 | 0.00 | 0.00 | 0.00 | 0.146108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573791E+09 | 0.00 | 0.00 | 0.00 | 0.480012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637508E+09 | 0.00 | 0.00 | 0.00 | 9643032.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835156E+10 | 0.00 | 0.00 | 0.00 | 0.456663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.899948E+09 | 0.00 | 0.00 | 0.00 | 0.176507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175320E+11 | 0.00 | 0.00 | 0.52 |
February | 0.249830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167127E+11 | 0.00 | 0.00 | 0.53 |
March | 0.626567E+10 | 13873938.48 | 0.00 | 323289.44 | 77205.01 | 0.901060E+10 | 0.151528E+09 | 0.00 | 0.54 |
April | 0.835139E+10 | 0.00 | 0.00 | 93760.48 | 0.00 | 0.251781E+10 | 0.141693E+09 | 0.00 | 0.53 |
May | 0.505805E+10 | 37471294.43 | 0.00 | 5030952.24 | 0.00 | 19825725.19 | 0.298526E+10 | 0.00 | 0.65 |
June | 0.825973E+09 | 0.157282E+10 | 0.00 | 12964462.10 | 265479.85 | 0.00 | 0.435003E+10 | 0.00 | 0.88 |
July | 8408172.43 | 0.445639E+10 | 0.00 | 9123928.76 | 371839.09 | 0.00 | 0.133159E+10 | 0.00 | 0.89 |
August | 0.114273E+09 | 0.258185E+10 | 0.00 | 14370459.28 | 232241.85 | 0.00 | 0.294535E+10 | 0.00 | 0.89 |
September | 0.126777E+10 | 0.626279E+09 | 0.00 | 13682775.01 | 178317.87 | 0.00 | 0.582850E+10 | 0.00 | 0.90 |
October | 0.876899E+10 | 0.00 | 0.00 | 2203092.16 | 0.00 | 0.362528E+09 | 0.150968E+10 | 0.00 | 0.58 |
November | 0.848583E+10 | 0.00 | 0.00 | 24915.52 | 0.00 | 0.410321E+10 | 31360803.41 | 0.00 | 0.53 |
December | 0.382929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161409E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.486253E+11 | 0.928868E+10 | 0.00 | 57817635.00 | 1125083.67 | 0.663996E+11 | 0.192750E+11 | 0.00 | 0.66 |
Minimum of Months | 8408172.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.876899E+10 | 0.445639E+10 | 0.00 | 14370459.28 | 371839.09 | 0.175320E+11 | 0.582850E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558341E+10 | 0.00 | 0.00 | 0.38 |
February | 0.167347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532038E+10 | 0.00 | 0.00 | 0.38 |
March | 0.285354E+10 | 8770812.61 | 0.00 | 270336.69 | 0.00 | 0.268630E+10 | 0.171753E+09 | 0.00 | 0.41 |
April | 0.315683E+10 | 0.00 | 0.00 | 537637.97 | 0.00 | 0.598421E+09 | 0.490217E+09 | 0.00 | 0.42 |
May | 0.132013E+10 | 22409187.87 | 0.00 | 4375715.05 | 2653.79 | 0.00 | 0.279887E+10 | 0.00 | 0.67 |
June | 0.227738E+09 | 0.864374E+09 | 0.00 | 5969628.29 | 3585923.49 | 0.00 | 0.235525E+10 | 0.00 | 0.85 |
July | 16016.86 | 0.238023E+10 | 0.00 | 2630212.52 | 193153.38 | 0.00 | 0.440618E+09 | 0.00 | 0.77 |
August | 11499114.76 | 0.133461E+10 | 0.00 | 5676919.75 | 99378.13 | 0.00 | 0.121252E+10 | 0.00 | 0.81 |
September | 0.258967E+09 | 0.376679E+09 | 0.00 | 7213558.00 | 286193.17 | 0.00 | 0.342372E+10 | 0.00 | 0.94 |
October | 0.294656E+10 | 0.00 | 0.00 | 2135582.02 | 0.00 | 14143934.92 | 0.155303E+10 | 0.00 | 0.52 |
November | 0.353049E+10 | 0.00 | 0.00 | 163824.62 | 0.00 | 0.102085E+10 | 0.162563E+09 | 0.00 | 0.40 |
December | 0.203655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518734E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.200278E+11 | 0.498707E+10 | 0.00 | 28973414.92 | 4167301.95 | 0.204108E+11 | 0.126085E+11 | 0.00 | 0.58 |
Minimum of Months | 16016.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.353049E+10 | 0.238023E+10 | 0.00 | 7213558.00 | 3585923.49 | 0.558341E+10 | 0.342372E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.946001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706412E+10 | 0.00 | 0.00 | 0.41 |
February | 0.942857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645597E+10 | 0.00 | 0.00 | 0.41 |
March | 0.258070E+10 | 8443739.21 | 0.00 | 95041.05 | 3133.78 | 0.333420E+10 | 38403427.69 | 0.00 | 0.43 |
April | 0.322723E+10 | 0.00 | 0.00 | 83241.22 | 0.00 | 0.816346E+09 | 93788264.45 | 0.00 | 0.42 |
May | 0.180053E+10 | 21182664.13 | 0.00 | 2066479.86 | 541122.44 | 8849327.96 | 0.132059E+10 | 0.00 | 0.55 |
June | 0.422245E+09 | 0.677171E+09 | 0.00 | 3540722.54 | 28592714.88 | 0.00 | 0.167476E+10 | 0.00 | 0.72 |
July | 24653699.44 | 0.178566E+10 | 0.00 | 2012929.44 | 83435524.91 | 0.00 | 0.488071E+09 | 0.00 | 0.68 |
August | 87945478.64 | 0.105944E+10 | 0.00 | 3504790.87 | 39046424.95 | 0.00 | 0.106960E+10 | 0.00 | 0.71 |
September | 0.606187E+09 | 0.289568E+09 | 0.00 | 4075081.64 | 5292960.28 | 0.00 | 0.207203E+10 | 0.00 | 0.76 |
October | 0.325923E+10 | 0.00 | 0.00 | 822995.64 | 0.00 | 0.137746E+09 | 0.603230E+09 | 0.00 | 0.47 |
November | 0.305373E+10 | 0.00 | 0.00 | 12878.46 | 0.00 | 0.168815E+10 | 19625219.24 | 0.00 | 0.42 |
December | 0.119997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640066E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.181513E+11 | 0.384146E+10 | 0.00 | 16214160.71 | 0.156912E+09 | 0.259060E+11 | 0.738010E+10 | 0.00 | 0.53 |
Minimum of Months | 24653699.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.325923E+10 | 0.178566E+10 | 0.00 | 4075081.64 | 83435524.91 | 0.706412E+10 | 0.207203E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725789E+10 | 0.00 | 0.00 | 0.41 |
February | 0.755553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664313E+10 | 0.00 | 0.00 | 0.41 |
March | 0.234162E+10 | 7921008.36 | 0.00 | 90888.68 | 15590.86 | 0.357260E+10 | 33452862.26 | 0.00 | 0.43 |
April | 0.310415E+10 | 0.00 | 0.00 | 57256.22 | 0.00 | 0.943709E+09 | 69192426.15 | 0.00 | 0.42 |
May | 0.183419E+10 | 20247627.58 | 0.00 | 1848547.94 | 524671.42 | 22123860.96 | 0.119905E+10 | 0.00 | 0.54 |
June | 0.430750E+09 | 0.674479E+09 | 0.00 | 3496820.41 | 28641127.96 | 0.00 | 0.165727E+10 | 0.00 | 0.72 |
July | 24692998.81 | 0.178785E+10 | 0.00 | 2010261.50 | 82182456.48 | 0.00 | 0.489814E+09 | 0.00 | 0.69 |
August | 90197252.56 | 0.105981E+10 | 0.00 | 3503680.02 | 38939554.99 | 0.00 | 0.106866E+10 | 0.00 | 0.71 |
September | 0.629377E+09 | 0.285924E+09 | 0.00 | 3986454.65 | 5248155.83 | 0.00 | 0.203753E+10 | 0.00 | 0.76 |
October | 0.325591E+10 | 0.00 | 0.00 | 696877.46 | 0.00 | 0.172369E+09 | 0.520139E+09 | 0.00 | 0.46 |
November | 0.293526E+10 | 0.00 | 0.00 | 2169.37 | 0.00 | 0.180723E+10 | 9205459.15 | 0.00 | 0.42 |
December | 0.106317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653748E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.172171E+11 | 0.383623E+10 | 0.00 | 15692956.26 | 0.155552E+09 | 0.269565E+11 | 0.708431E+10 | 0.00 | 0.53 |
Minimum of Months | 24692998.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.325591E+10 | 0.178785E+10 | 0.00 | 3986454.65 | 82182456.48 | 0.725789E+10 | 0.203753E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756468E+10 | 0.00 | 0.00 | 0.41 |
February | 0.511863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688691E+10 | 0.00 | 0.00 | 0.41 |
March | 0.195561E+10 | 7312384.34 | 0.00 | 76980.83 | 111185.93 | 0.395429E+10 | 28455300.25 | 0.00 | 0.43 |
April | 0.289028E+10 | 0.00 | 0.00 | 33170.75 | 0.00 | 0.116286E+10 | 35182834.57 | 0.00 | 0.42 |
May | 0.194517E+10 | 18814290.47 | 0.00 | 1468341.95 | 506047.44 | 31898382.83 | 0.950147E+09 | 0.00 | 0.52 |
June | 0.459235E+09 | 0.658518E+09 | 0.00 | 3251872.13 | 27258131.71 | 0.00 | 0.156664E+10 | 0.00 | 0.70 |
July | 29813682.52 | 0.174641E+10 | 0.00 | 1910768.69 | 82366606.18 | 0.00 | 0.481617E+09 | 0.00 | 0.68 |
August | 0.108483E+09 | 0.103909E+10 | 0.00 | 3323304.00 | 38865486.62 | 0.00 | 0.103042E+10 | 0.00 | 0.70 |
September | 0.690866E+09 | 0.270589E+09 | 0.00 | 3706216.60 | 5191472.72 | 0.00 | 0.190843E+10 | 0.00 | 0.75 |
October | 0.318674E+10 | 0.00 | 0.00 | 531934.02 | 0.00 | 0.286322E+09 | 0.399974E+09 | 0.00 | 0.45 |
November | 0.273621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200504E+10 | 0.00 | 0.00 | 0.42 |
December | 0.773149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682741E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.157329E+11 | 0.374074E+10 | 0.00 | 14302588.96 | 0.154299E+09 | 0.287194E+11 | 0.640086E+10 | 0.00 | 0.53 |
Minimum of Months | 29813682.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.318674E+10 | 0.174641E+10 | 0.00 | 3706216.60 | 82366606.18 | 0.756468E+10 | 0.190843E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148146E+11 | 0.00 | 0.00 | 0.38 |
February | 0.139541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136302E+11 | 0.00 | 0.00 | 0.38 |
March | 0.256602E+10 | 3893200.10 | 0.00 | 205159.49 | 629528.01 | 0.841341E+10 | 65913833.92 | 0.00 | 0.39 |
April | 0.491569E+10 | 0.00 | 0.00 | 45237.81 | 0.00 | 0.259454E+10 | 57323572.42 | 0.00 | 0.38 |
May | 0.385886E+10 | 22196234.72 | 0.00 | 1878384.03 | 5745915.09 | 55654141.21 | 0.132907E+10 | 0.00 | 0.45 |
June | 0.762558E+09 | 0.115136E+10 | 0.00 | 5250366.87 | 22512069.46 | 0.00 | 0.273006E+10 | 0.00 | 0.59 |
July | 10604549.25 | 0.310613E+10 | 0.00 | 2879033.04 | 42830710.84 | 0.00 | 0.755360E+09 | 0.00 | 0.58 |
August | 0.112136E+09 | 0.180718E+10 | 0.00 | 5775591.38 | 31648530.27 | 0.00 | 0.172223E+10 | 0.00 | 0.60 |
September | 0.111794E+10 | 0.370444E+09 | 0.00 | 6275879.51 | 6257383.71 | 0.00 | 0.338305E+10 | 0.00 | 0.63 |
October | 0.578074E+10 | 0.00 | 0.00 | 657493.67 | 0.00 | 0.695514E+09 | 0.580704E+09 | 0.00 | 0.40 |
November | 0.424124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468619E+10 | 0.00 | 0.00 | 0.38 |
December | 0.321924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138813E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.239275E+11 | 0.646121E+10 | 0.00 | 22967145.81 | 0.109624E+09 | 0.587714E+11 | 0.106237E+11 | 0.00 | 0.46 |
Minimum of Months | 10604549.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.578074E+10 | 0.310613E+10 | 0.00 | 6275879.51 | 42830710.84 | 0.148146E+11 | 0.338305E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36240127.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740969E+10 | 0.00 | 0.00 | 0.38 |
February | 48013482.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682644E+10 | 0.00 | 0.00 | 0.38 |
March | 0.115915E+10 | 2056077.95 | 0.00 | 92102.17 | 350151.11 | 0.432332E+10 | 28267679.19 | 0.00 | 0.39 |
April | 0.226783E+10 | 0.00 | 0.00 | 17939.77 | 0.00 | 0.147308E+10 | 25024648.96 | 0.00 | 0.38 |
May | 0.194240E+10 | 10757331.25 | 0.00 | 847943.05 | 3206271.94 | 42583504.97 | 0.602499E+09 | 0.00 | 0.45 |
June | 0.387377E+09 | 0.573141E+09 | 0.00 | 2611321.20 | 11732713.64 | 0.00 | 0.137171E+10 | 0.00 | 0.60 |
July | 5634143.65 | 0.155187E+10 | 0.00 | 1472595.76 | 21342256.28 | 0.00 | 0.394097E+09 | 0.00 | 0.59 |
August | 54486608.90 | 0.906419E+09 | 0.00 | 2908322.78 | 15678226.41 | 0.00 | 0.887858E+09 | 0.00 | 0.62 |
September | 0.560976E+09 | 0.184516E+09 | 0.00 | 3156405.14 | 3150659.85 | 0.00 | 0.171860E+10 | 0.00 | 0.64 |
October | 0.281444E+10 | 0.00 | 0.00 | 295740.21 | 0.00 | 0.422988E+09 | 0.267638E+09 | 0.00 | 0.40 |
November | 0.193612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251439E+10 | 0.00 | 0.00 | 0.38 |
December | 0.138387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695157E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.113511E+11 | 0.322876E+10 | 0.00 | 11402370.07 | 55460279.24 | 0.299641E+11 | 0.529569E+10 | 0.00 | 0.47 |
Minimum of Months | 5634143.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.281444E+10 | 0.155187E+10 | 0.00 | 3156405.14 | 21342256.28 | 0.740969E+10 | 0.171860E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22452637.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742354E+10 | 0.00 | 0.00 | 0.38 |
February | 44633253.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682985E+10 | 0.00 | 0.00 | 0.38 |
March | 0.107319E+10 | 2007879.24 | 0.00 | 88899.24 | 377511.77 | 0.440816E+10 | 27677183.83 | 0.00 | 0.39 |
April | 0.218146E+10 | 0.00 | 0.00 | 15401.99 | 0.00 | 0.155486E+10 | 21839331.43 | 0.00 | 0.38 |
May | 0.195606E+10 | 10265720.83 | 0.00 | 737768.28 | 3579152.47 | 48241786.15 | 0.541824E+09 | 0.00 | 0.45 |
June | 0.409518E+09 | 0.565061E+09 | 0.00 | 2501072.30 | 11891298.16 | 0.00 | 0.131916E+10 | 0.00 | 0.60 |
July | 7424698.06 | 0.153718E+10 | 0.00 | 1448898.00 | 21526632.55 | 0.00 | 0.389875E+09 | 0.00 | 0.59 |
August | 58517400.12 | 0.899345E+09 | 0.00 | 2839172.14 | 15652696.57 | 0.00 | 0.876397E+09 | 0.00 | 0.61 |
September | 0.567429E+09 | 0.179813E+09 | 0.00 | 3057229.53 | 3172329.79 | 0.00 | 0.168288E+10 | 0.00 | 0.64 |
October | 0.276228E+10 | 0.00 | 0.00 | 260562.21 | 0.00 | 0.479322E+09 | 0.244356E+09 | 0.00 | 0.40 |
November | 0.186134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258733E+10 | 0.00 | 0.00 | 0.38 |
December | 0.129434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696059E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.110737E+11 | 0.319367E+10 | 0.00 | 10949003.69 | 56199621.30 | 0.302919E+11 | 0.510401E+10 | 0.00 | 0.46 |
Minimum of Months | 7424698.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.276228E+10 | 0.153718E+10 | 0.00 | 3057229.53 | 21526632.55 | 0.742354E+10 | 0.168288E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744603E+10 | 0.00 | 0.00 | 0.38 |
February | 20645743.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685385E+10 | 0.00 | 0.00 | 0.38 |
March | 0.787736E+09 | 1847158.49 | 0.00 | 73571.24 | 554031.28 | 0.469387E+10 | 22597930.79 | 0.00 | 0.39 |
April | 0.189160E+10 | 0.00 | 0.00 | 9346.96 | 0.00 | 0.183274E+10 | 15054091.48 | 0.00 | 0.38 |
May | 0.198301E+10 | 9112765.27 | 0.00 | 526426.67 | 4340868.14 | 90696028.83 | 0.389323E+09 | 0.00 | 0.44 |
June | 0.457227E+09 | 0.545373E+09 | 0.00 | 2242297.40 | 13457734.31 | 0.00 | 0.119503E+10 | 0.00 | 0.58 |
July | 13877971.79 | 0.150124E+10 | 0.00 | 1376909.65 | 21379649.39 | 0.00 | 0.377762E+09 | 0.00 | 0.58 |
August | 91908266.51 | 0.881931E+09 | 0.00 | 2664770.86 | 15581505.23 | 0.00 | 0.824104E+09 | 0.00 | 0.60 |
September | 0.591156E+09 | 0.168122E+09 | 0.00 | 2804753.37 | 3251480.00 | 745080.60 | 0.158262E+10 | 0.00 | 0.62 |
October | 0.264808E+10 | 0.00 | 0.00 | 203048.52 | 0.00 | 0.610203E+09 | 0.189247E+09 | 0.00 | 0.40 |
November | 0.143582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300761E+10 | 0.00 | 0.00 | 0.38 |
December | 59315888.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703079E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.998037E+10 | 0.310763E+10 | 0.00 | 9901124.67 | 58565268.36 | 0.315665E+11 | 0.459573E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.264808E+10 | 0.150124E+10 | 0.00 | 2804753.37 | 21379649.39 | 0.744603E+10 | 0.158262E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742050E+10 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685586E+10 | 0.00 | 0.00 | 0.38 |
March | 0.261941E+09 | 1660433.57 | 0.00 | 50954.08 | 847987.34 | 0.519430E+10 | 16086227.03 | 0.00 | 0.39 |
April | 0.977317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270934E+10 | 0.00 | 0.00 | 0.38 |
May | 0.174139E+10 | 7451896.87 | 627649.81 | 354061.22 | 2551255.57 | 0.307817E+09 | 0.293696E+09 | 2368.72 | 0.43 |
June | 0.527373E+09 | 0.513635E+09 | 0.00 | 1859579.00 | 13599690.59 | 0.00 | 0.102532E+10 | 0.00 | 0.56 |
July | 15687384.98 | 0.142595E+10 | 0.00 | 1392969.24 | 21479072.86 | 0.00 | 0.398647E+09 | 0.00 | 0.59 |
August | 0.137053E+09 | 0.854737E+09 | 0.00 | 2439460.24 | 15172833.85 | 0.00 | 0.765942E+09 | 0.00 | 0.61 |
September | 0.660883E+09 | 0.155132E+09 | 0.00 | 2540323.46 | 3100750.52 | 8811183.11 | 0.144445E+10 | 0.00 | 0.62 |
October | 0.191979E+10 | 0.00 | 0.00 | 155328.68 | 0.00 | 0.131250E+10 | 0.150579E+09 | 0.00 | 0.39 |
November | 0.653281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376089E+10 | 0.00 | 0.00 | 0.38 |
December | 8048396.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706171E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.690276E+10 | 0.295857E+10 | 627649.81 | 8792675.92 | 56751590.73 | 0.346317E+11 | 0.409473E+10 | 2368.72 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.191979E+10 | 0.142595E+10 | 627649.81 | 2540323.46 | 21479072.86 | 0.742050E+10 | 0.144445E+10 | 2368.72 | 0.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.109865E+12 | 0.483230E+11 | 0.00 | 0.999717E+11 | 0.332702E+11 |
February | 0.201434E+12 | 0.463545E+11 | 0.00 | 0.923192E+11 | 0.310893E+11 |
March | 0.334156E+12 | 0.336436E+11 | 0.00 | 0.743537E+11 | 0.212330E+11 |
April | 0.421020E+12 | 0.229475E+11 | 0.00 | 0.516500E+11 | 0.792240E+10 |
May | 0.539192E+12 | 0.134199E+11 | 0.00 | 0.364166E+11 | 0.750620E+10 |
June | 0.596443E+12 | 0.343122E+10 | 0.00 | 0.162313E+11 | 0.608487E+11 |
July | 0.557938E+12 | -0.666306E+10 | 0.00 | -0.160632E+11 | 0.127879E+12 |
August | 0.468823E+12 | -0.183977E+10 | 0.00 | 0.664081E+09 | 0.102838E+12 |
September | 0.344141E+12 | 0.753341E+10 | 0.00 | 0.291554E+11 | 0.390860E+11 |
October | 0.214395E+12 | 0.207052E+11 | 0.00 | 0.486318E+11 | 0.499905E+10 |
November | 0.959537E+11 | 0.275214E+11 | 0.00 | 0.602890E+11 | 0.116949E+11 |
December | 0.950887E+11 | 0.474000E+11 | 0.00 | 0.955971E+11 | 0.305929E+11 |
Annual Sum or Average | 0.397845E+13 | 0.262777E+12 | 0.00 | 0.589217E+12 | 0.478959E+12 |
Minimum of Months | 0.950887E+11 | -0.666306E+10 | 0.00 | -0.160632E+11 | 0.499905E+10 |