Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1127.31 | 539.30 | 539.30 |
Net Site Energy | 1127.31 | 539.30 | 539.30 |
Total Source Energy | 3190.00 | 1526.09 | 1526.09 |
Net Source Energy | 3190.00 | 1526.09 | 1526.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 182.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 187.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 62.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 944.79 | 182.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 182.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 187.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 98.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 62.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 182.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 187.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 98.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 62.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.59 | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 451.98 | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.59 | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 451.98 | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 944.791 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 944.791 | 100.00 |
Total On-Site and Utility Electric Sources | 944.791 | 100.00 |
Total Electricity End Uses | 944.791 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1623.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 203522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51452.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8087.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5429.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 99289.72 | 203522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 203522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51452.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8087.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5429.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 197.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 593.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 313.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 196.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2992.15 | 197.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 94.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 283.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1431.43 | 94.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 94.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 283.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1431.43 | 94.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.06 |
SMSTORE1 DIRECT AIR | 1.09 |
SMSTORE2 DIRECT AIR | 1.10 |
SMSTORE3 DIRECT AIR | 1.10 |
SMSTORE4 DIRECT AIR | 1.09 |
LGSTORE2 DIRECT AIR | 1.92 |
SMSTORE5 DIRECT AIR | 0.996331 |
SMSTORE6 DIRECT AIR | 0.991311 |
SMSTORE7 DIRECT AIR | 0.991910 |
SMSTORE8 DIRECT AIR | 1.12 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 1.00 | 1.000000 | 2.06 |
PSZ-AC_2:2 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-AC_3:3 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.000000 | 1.10 |
PSZ-AC_4:4 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC_5:5 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-AC_6:6 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.00 | 1.00 | 1.92 |
PSZ-AC_7:7 | 0.996331 | 0.996331 | 0.996331 | 0.996331 | 0.996331 | 0.996331 | 1.00 | 1.00 | 0.996331 |
PSZ-AC_8:8 | 0.991311 | 0.991311 | 0.991311 | 0.991311 | 0.991311 | 0.991311 | 1.00 | 1.00 | 0.991311 |
PSZ-AC_9:9 | 0.991910 | 0.991910 | 0.991910 | 0.991910 | 0.991910 | 0.991910 | 1.00 | 1.00 | 0.991910 |
PSZ-AC_10:10 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.06 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.09 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.09 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.92 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.996331 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.991311 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.991910 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.12 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.06 | 2206.46 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1210.71 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1215.00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1218.94 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1208.03 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.92 | 2053.67 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.996331 | 1103.10 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.991311 | 1097.54 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.991910 | 1098.20 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1244.82 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.06 | 2.06 | 2.06 | 1.36 | 47463.56 | 58606.25 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.721728 | 24821.87 | 30680.73 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 0.724289 | 24888.35 | 30766.24 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 0.726638 | 24948.13 | 30844.68 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.720132 | 24783.85 | 30627.39 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.92 | 1.92 | 1.92 | 1.27 | 44916.73 | 55457.96 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.996331 | 0.996331 | 0.996331 | 0.657578 | 23197.06 | 28538.37 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.991311 | 0.991311 | 0.991311 | 0.654265 | 23112.44 | 28427.74 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.991910 | 0.991910 | 0.991910 | 0.654661 | 23123.23 | 28440.94 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.742065 | 25335.02 | 31360.93 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.06 | 1.03 | 1.37 | 47463.56 | 23731.78 | 0.725400 | 0.725400 |
PSZ-AC_2:2 COOLING COIL | 1.09 | 0.546764 | 0.729020 | 24821.87 | 12410.93 | 0.730120 | 0.730120 |
PSZ-AC_3:3 COOLING COIL | 1.10 | 0.548704 | 0.731607 | 24888.35 | 12444.17 | 0.730350 | 0.730350 |
PSZ-AC_4:4 COOLING COIL | 1.10 | 0.550483 | 0.733980 | 24948.13 | 12474.07 | 0.730580 | 0.730580 |
PSZ-AC_5:5 COOLING COIL | 1.09 | 0.545554 | 0.727407 | 24783.85 | 12391.92 | 0.729940 | 0.729940 |
PSZ-AC_6:6 COOLING COIL | 1.92 | 0.959615 | 1.28 | 44916.73 | 22458.37 | 0.720050 | 0.720050 |
PSZ-AC_7:7 COOLING COIL | 0.996330 | 0.498165 | 0.664220 | 23197.06 | 11598.53 | 0.721400 | 0.721400 |
PSZ-AC_8:8 COOLING COIL | 0.991310 | 0.495656 | 0.660873 | 23112.44 | 11556.22 | 0.721030 | 0.721030 |
PSZ-AC_9:9 COOLING COIL | 0.991910 | 0.495955 | 0.661273 | 23123.23 | 11561.61 | 0.721070 | 0.721070 |
PSZ-AC_10:10 COOLING COIL | 1.12 | 0.562171 | 0.749560 | 25335.02 | 12667.51 | 0.732090 | 0.732090 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58606.25 |
PSZ-AC_2:2 HEATING COIL | 30680.73 |
PSZ-AC_3:3 HEATING COIL | 30766.24 |
PSZ-AC_4:4 HEATING COIL | 30844.68 |
PSZ-AC_5:5 HEATING COIL | 30627.39 |
PSZ-AC_6:6 HEATING COIL | 55457.96 |
PSZ-AC_7:7 HEATING COIL | 28538.37 |
PSZ-AC_8:8 HEATING COIL | 28427.74 |
PSZ-AC_9:9 HEATING COIL | 28440.94 |
PSZ-AC_10:10 HEATING COIL | 31360.93 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 35 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22570.44475 | 27084.53370 | 1.71835 | 2.06202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 22012.04239 | 26414.45087 | 0.98412 | 1.18094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11969.67097 | 14363.60516 | 0.91127 | 1.09353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 10178.46856 | 12214.16227 | 0.45507 | 0.54608 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12012.14047 | 14414.56856 | 0.91451 | 1.09741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 10333.38289 | 12400.05947 | 0.46199 | 0.55439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12051.16595 | 14461.39914 | 0.91747 | 1.10097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 10441.67726 | 12530.01271 | 0.46684 | 0.56020 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11943.26462 | 14331.91755 | 0.90926 | 1.09111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 10607.95494 | 12729.54593 | 0.47427 | 0.56912 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21007.91355 | 25209.49626 | 1.59936 | 1.91923 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 20541.81547 | 24650.17856 | 0.91841 | 1.10209 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10905.84611 | 13087.01533 | 0.83028 | 0.99633 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 10932.93265 | 13119.51918 | 0.48880 | 0.58656 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10850.90670 | 13021.08804 | 0.82609 | 0.99131 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 10923.37803 | 13108.05363 | 0.48837 | 0.58605 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10857.46538 | 13028.95845 | 0.82659 | 0.99191 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 11145.81782 | 13374.98139 | 0.49832 | 0.59798 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12307.83893 | 14769.40671 | 0.93695 | 1.12434 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.92500 | 1.44724E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 13800.73487 | 16560.88185 | 0.61698 | 0.74038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31713.37 | 2.06202 | 2.06202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 39185.86 | 1.18094 | 1.18094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16665.04 | 1.09353 | 1.09353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 18614.42 | 0.54608 | 0.54608 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16711.29 | 1.09741 | 1.09741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 18797.61 | 0.55439 | 0.55439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16756.11 | 1.10097 | 1.10097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 18925.67 | 0.56020 | 0.56020 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16629.11 | 1.09111 | 1.09111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 19122.30 | 0.56912 | 0.56912 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29860.12 | 1.91923 | 1.91923 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 37447.55 | 1.10209 | 1.10209 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15401.51 | 0.99633 | 0.99633 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 19506.59 | 0.58656 | 0.58656 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15336.51 | 0.99131 | 0.99131 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 19495.30 | 0.58605 | 0.58605 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15342.89 | 0.99191 | 0.99191 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 19758.34 | 0.59798 | 0.59798 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16951.48 | 1.12434 | 1.12434 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 22897.59 | 0.74038 | 0.74038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.06202 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09353 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09741 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10097 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09111 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.91923 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99633 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99131 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99191 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12434 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.06202 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.06202 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.06202 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06202 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.06202 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.06202 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09353 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09353 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09353 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09353 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09353 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09353 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09741 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09741 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09741 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09741 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09741 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09741 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10097 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10097 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10097 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10097 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10097 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10097 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09111 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09111 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09111 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09111 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09111 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09111 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.91923 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.91923 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.91923 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.91923 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.91923 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.91923 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99633 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99633 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99633 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99633 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99633 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99633 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99131 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99131 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99131 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99131 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99131 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99131 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99191 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99191 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99191 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99191 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99191 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99191 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12434 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12434 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12434 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12434 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12434 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12434 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.06202 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.09353 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.09741 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.10097 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.09111 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.91923 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.99633 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.99131 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.99191 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.12434 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.06202 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.06202 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2206.46051 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.06202 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.06202 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.06202 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36093 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.06202 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.03101 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37468 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47463.56000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23731.78000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72540 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72540 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47463.56000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58606.25009 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58606.25009 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09353 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09353 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1210.70909 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09353 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09353 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09353 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72173 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09353 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54676 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72902 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24821.87000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12410.93500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73012 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73012 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24821.87000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30680.73217 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30680.73217 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09741 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09741 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1215.00440 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09741 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09741 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09741 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72429 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09741 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54870 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73161 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24888.35000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12444.17500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73035 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73035 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24888.35000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30766.23610 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30766.23610 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10097 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10097 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1218.94461 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10097 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10097 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10097 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72664 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10097 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55048 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73398 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24948.13000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12474.06500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73058 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73058 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24948.13000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30844.67638 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30844.67638 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09111 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09111 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1208.03028 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09111 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09111 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09111 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72013 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09111 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54555 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72741 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24783.85000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12391.92500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72994 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72994 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24783.85000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30627.39019 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30627.39019 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.91923 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.91923 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2053.66743 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.91923 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.91923 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.91923 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26669 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.91923 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95962 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.27949 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44916.73000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22458.36500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72005 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72005 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44916.73000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55457.95995 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 55457.95995 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99633 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99633 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1103.09602 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99633 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99633 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99633 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65758 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99633 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49817 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66422 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23197.06000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11598.53000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72140 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72140 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23197.06000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28538.36729 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28538.36729 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99131 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99131 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1097.53896 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99131 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99131 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99131 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65427 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99131 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49566 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66087 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23112.44000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11556.22000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72103 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72103 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23112.44000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28427.73795 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28427.73795 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99191 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99191 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1098.20210 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99191 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99191 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99191 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65466 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99191 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49596 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66127 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23123.23000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11561.61500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72107 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72107 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23123.23000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28440.93727 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28440.93727 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12434 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12434 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1244.82399 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12434 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12434 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12434 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74207 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12434 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56217 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74956 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25335.02000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12667.51000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73209 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73209 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25335.02000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31360.92612 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31360.92612 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 45839.2 | 11.63 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 23960.6 | 11.78 | 11.78 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 24024.1 | 11.78 | 11.78 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 24081.1 | 11.78 | 11.78 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 23924.5 | 11.78 | 11.78 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 43404.3 | 11.66 | 11.66 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 22412.0 | 11.83 | 11.83 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 22331.3 | 11.83 | 11.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 22341.6 | 11.83 | 11.83 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 24449.6 | 11.77 | 11.77 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_0.25 | N/A | 2.552 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.9916531631E-002 | 0.1235133173 | Pass | Pass | 0.2559905692 | 0.8935884432 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.7611549739E-002 | 9.7518426113E-002 | Pass | Pass | 0.1174473078 | 0.8113629049 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.3510721122E-002 | 0.1279995021 | Pass | Pass | 0.1807689073 | 0.7949152121 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.2415386844E-002 | 0.1805520625 | Pass | Pass | 0.1446652714 | 0.4977927258 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.1707300589E-002 | 0.1760355828 | Pass | Pass | 0.2910510927 | 1.1475002488 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.8164680844E-002 | 0.2045817115 | Pass | Pass | 0.1261525488 | 0.4875297129 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.7790288967E-002 | 0.2070121745 | Pass | Pass | 0.1037939717 | 0.4411208599 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.8807613308E-002 | 0.2094208275 | Pass | Pass | 0.1057366539 | 0.5159594147 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.2656438439E-002 | 0.2259407788 | Pass | Pass | 0.1013853022 | 0.6161373485 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.7429923303E-002 | 0.3075368346 | Pass | Pass | 9.6587933628E-002 | 0.6998970979 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2856.50 | 37.40 | 0.00 | 94.57 | 973.73 | 3962.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.552 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.552 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.552 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.449_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.552 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.552 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.552 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.77 | 41.77 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.77 | 62.77 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.77 | 55.77 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47463.56 | 34430.07 | 13033.49 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24821.87 | 18122.94 | 6698.93 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24888.35 | 18177.21 | 6711.14 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24948.13 | 18226.60 | 6721.53 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24783.85 | 18090.72 | 6693.13 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44916.73 | 32342.29 | 12574.44 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23197.06 | 16734.36 | 6462.70 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23112.44 | 16664.76 | 6447.68 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23123.23 | 16673.47 | 6449.76 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25335.02 | 18547.51 | 6787.51 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 45839.2 | 11.63 | 11.63 | ||||
PSZ-AC_2:2 COOLING COIL | 23960.6 | 11.78 | 11.78 | ||||
PSZ-AC_3:3 COOLING COIL | 24024.1 | 11.78 | 11.78 | ||||
PSZ-AC_4:4 COOLING COIL | 24081.1 | 11.78 | 11.78 | ||||
PSZ-AC_5:5 COOLING COIL | 23924.5 | 11.78 | 11.78 | ||||
PSZ-AC_6:6 COOLING COIL | 43404.3 | 11.66 | 11.66 | ||||
PSZ-AC_7:7 COOLING COIL | 22412.0 | 11.83 | 11.83 | ||||
PSZ-AC_8:8 COOLING COIL | 22331.3 | 11.83 | 11.83 | ||||
PSZ-AC_9:9 COOLING COIL | 22341.6 | 11.83 | 11.83 | ||||
PSZ-AC_10:10 COOLING COIL | 24449.6 | 11.77 | 11.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58606.25 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30680.73 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30766.24 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30844.68 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30627.39 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 55457.96 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28538.37 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28427.74 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28440.94 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31360.93 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.06 | 2206.46 | 1070.05 | 1.00 | 1.31 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1210.71 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1215.00 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1218.94 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1208.03 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.92 | 2053.67 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1103.10 | 1107.16 | 1.00 | 1.40 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1097.54 | 1107.16 | 1.00 | 1.40 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1098.20 | 1107.16 | 1.00 | 1.40 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1244.82 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22570.44 | 27084.53 | 77.74 | 1.718 | 2.062 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.88 | 0.00977 | 34.40 | 0.01447 | 0.411 | 0.00 |
SMSTORE1 | 11969.67 | 14363.61 | 82.46 | 0.911 | 1.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00973 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE2 | 12012.14 | 14414.57 | 82.75 | 0.915 | 1.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00973 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE3 | 12051.17 | 14461.40 | 83.02 | 0.917 | 1.101 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00972 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE4 | 11943.26 | 14331.92 | 82.28 | 0.909 | 1.091 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00973 | 34.24 | 0.01447 | 0.206 | 0.00 |
LGSTORE2 | 21007.91 | 25209.50 | 72.36 | 1.599 | 1.919 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00981 | 34.32 | 0.01447 | 0.411 | 0.00 |
SMSTORE5 | 10905.85 | 13087.02 | 75.13 | 0.830 | 0.996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00983 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE6 | 10850.91 | 13021.09 | 74.75 | 0.826 | 0.991 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00984 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE7 | 10857.47 | 13028.96 | 74.80 | 0.827 | 0.992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00984 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE8 | 12307.84 | 14769.41 | 84.79 | 0.937 | 1.124 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.00976 | 33.92 | 0.01447 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22012.04 | 26414.45 | 75.82 | 0.984 | 1.181 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE1 | 10178.47 | 12214.16 | 70.12 | 0.455 | 0.546 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00661 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE2 | 10333.38 | 12400.06 | 71.19 | 0.462 | 0.554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE3 | 10441.68 | 12530.01 | 71.93 | 0.467 | 0.560 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE4 | 10607.95 | 12729.55 | 73.08 | 0.474 | 0.569 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -6.30 | 0.00230 | 0.206 | 0.00 |
LGSTORE2 | 20541.82 | 24650.18 | 70.76 | 0.918 | 1.102 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE5 | 10932.93 | 13119.52 | 75.32 | 0.489 | 0.587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE6 | 10923.38 | 13108.05 | 75.25 | 0.488 | 0.586 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE7 | 11145.82 | 13374.98 | 76.78 | 0.498 | 0.598 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE8 | 13800.73 | 16560.88 | 95.07 | 0.617 | 0.740 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00671 | -6.30 | 0.00230 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 1.18 | 1.18 | 2.0620 | 2.0620 | 2.0620 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.09 | 1.09 | 0.55 | 0.55 | 1.0935 | 1.0935 | 1.0935 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.10 | 1.10 | 0.55 | 0.55 | 1.0974 | 1.0974 | 1.0974 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.10 | 1.10 | 0.56 | 0.56 | 1.1010 | 1.1010 | 1.1010 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.09 | 1.09 | 0.57 | 0.57 | 1.0911 | 1.0911 | 1.0911 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.92 | 1.92 | 1.10 | 1.10 | 1.9192 | 1.9192 | 1.9192 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.00 | 1.00 | 0.59 | 0.59 | 0.9963 | 0.9963 | 0.9963 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.99 | 0.99 | 0.59 | 0.59 | 0.9913 | 0.9913 | 0.9913 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.99 | 0.99 | 0.60 | 0.60 | 0.9919 | 0.9919 | 0.9919 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.12 | 1.12 | 0.74 | 0.74 | 1.1243 | 1.1243 | 1.1243 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 47463.560 | 34430.066 | 2.062020 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23731.78 | 17596.37 | 1.374680 | 26.88 | 18.76 | 0.01070912 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.9327 | 23.88 | 0.00977072 | 50.9594 | 22570.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58606.250 | 58606.250 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 58606.25 | 58606.25 | 2.062022 | 15.64 | 10.21 | 0.00580733 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.9551 | 21.11 | 0.00668226 | 41.4679 | 22012.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 24821.870 | 18122.944 | 1.093530 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12410.93 | 9284.37 | 0.729020 | 26.79 | 18.67 | 0.01062182 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.2214 | 23.88 | 0.00972925 | 50.7462 | 11969.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30680.732 | 30680.732 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30680.73 | 30680.73 | 1.093528 | 15.95 | 10.34 | 0.00580012 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.8143 | 21.11 | 0.00661176 | 41.0344 | 10178.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 24888.350 | 18177.206 | 1.097410 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12444.17 | 9314.60 | 0.731607 | 26.79 | 18.66 | 0.01061611 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.1216 | 23.89 | 0.00972580 | 50.7284 | 12008.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30766.236 | 30766.236 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30766.24 | 30766.24 | 1.097408 | 15.97 | 10.36 | 0.00581414 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.7478 | 21.11 | 0.00662548 | 41.1187 | 10333.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 24948.130 | 18226.605 | 1.100970 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12474.07 | 9342.20 | 0.733980 | 26.78 | 18.65 | 0.01061058 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.0307 | 23.89 | 0.00972246 | 50.7112 | 12046.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30844.676 | 30844.676 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30844.68 | 30844.68 | 1.100966 | 15.99 | 10.38 | 0.00582421 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.6872 | 21.11 | 0.00663464 | 41.1749 | 10441.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 24783.850 | 18090.723 | 1.091110 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12391.92 | 9265.92 | 0.727407 | 26.80 | 18.67 | 0.01062633 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.2840 | 23.89 | 0.00973201 | 50.7603 | 11939.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30627.390 | 30627.390 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30627.39 | 30627.39 | 1.091108 | 15.94 | 10.36 | 0.00582839 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.8560 | 21.11 | 0.00664882 | 41.2620 | 10607.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 44916.730 | 32342.291 | 1.919230 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 22458.37 | 16498.60 | 1.279487 | 27.04 | 18.89 | 0.01081104 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 32.1597 | 23.89 | 0.00981123 | 51.1669 | 21001.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 55457.960 | 55457.960 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 55457.96 | 55457.96 | 1.919231 | 15.23 | 10.00 | 0.00577655 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 21.4398 | 21.11 | 0.00672594 | 41.7348 | 20541.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 23197.060 | 16734.359 | 0.996330 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11598.53 | 8532.69 | 0.664220 | 26.99 | 18.86 | 0.01079144 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 30.9746 | 23.89 | 0.00983266 | 51.2771 | 10899.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28538.367 | 28538.367 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28538.37 | 28538.37 | 0.996331 | 15.45 | 10.09 | 0.00577133 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.6497 | 21.11 | 0.00667527 | 41.4244 | 10932.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 23112.440 | 16664.763 | 0.991310 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11556.22 | 8493.84 | 0.660873 | 27.00 | 18.87 | 0.01080089 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 31.1314 | 23.89 | 0.00983845 | 51.3068 | 10844.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28427.738 | 28427.738 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28427.74 | 28427.74 | 0.991311 | 15.42 | 10.07 | 0.00576619 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.7543 | 21.11 | 0.00667456 | 41.4201 | 10923.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 23123.230 | 16673.467 | 0.991910 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11561.61 | 8498.57 | 0.661273 | 27.00 | 18.87 | 0.01079996 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 31.1126 | 23.89 | 0.00983788 | 51.3039 | 10850.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28440.937 | 28440.937 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28440.94 | 28440.94 | 0.991910 | 15.42 | 10.09 | 0.00578047 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.7417 | 21.11 | 0.00669188 | 41.5265 | 11145.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 25335.020 | 18547.515 | 1.124340 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12667.51 | 9448.73 | 0.749560 | 26.67 | 18.63 | 0.01062969 | 12.80 | 11.77 | 0.00850000 | 34.00 | 0.01447253 | 23.44 | 27.4480 | 23.88 | 0.00976771 | 50.9443 | 12292.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31360.926 | 31360.926 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31360.93 | 31360.93 | 1.124341 | 16.09 | 10.51 | 0.00590202 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.2987 | 21.10 | 0.00670926 | 41.6358 | 13800.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47463.560 | 34430.066 | 2.062020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7477 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.062022 | 2.39395862 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 23731.78 | 17596.37 | 1.0000 | 1.59597123 | 1.374680 | 26.88 | 18.76 | 0.01070912 | 54330.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23731.78 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 29.9327 | 23.88 | 0.00977072 | 23.88 | 0.00977072 | 50.9594 | 22570.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58606.250 | 58606.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.062022 | 2.39395862 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 58606.25 | 58606.25 | 1.0000 | 2.39395862 | 2.062022 | 15.64 | 10.21 | 0.00580733 | 30405.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58606.25 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 19.9551 | 21.11 | 0.00668226 | 21.11 | 0.00668226 | 41.4679 | 22012.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24821.870 | 18122.944 | 1.093530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5854 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.093528 | 1.26956037 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12410.93 | 9284.37 | 1.0000 | 0.84637512 | 0.729020 | 26.79 | 18.67 | 0.01062182 | 54017.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12410.93 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.2214 | 23.89 | 0.00972925 | 23.88 | 0.00972925 | 50.7462 | 11969.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30680.732 | 30680.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.093528 | 1.26956037 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30680.73 | 30680.73 | 1.0000 | 1.26956037 | 1.093528 | 15.95 | 10.34 | 0.00580012 | 30705.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30680.73 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.8143 | 21.11 | 0.00661176 | 21.11 | 0.00661176 | 41.0344 | 10178.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24888.350 | 18177.206 | 1.097410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5748 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.097408 | 1.27406446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12444.17 | 9314.60 | 1.0000 | 0.84937818 | 0.731607 | 26.79 | 18.66 | 0.01061611 | 53996.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12444.17 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.1216 | 23.89 | 0.00972580 | 23.89 | 0.00972580 | 50.7284 | 12008.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30766.236 | 30766.236 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.097408 | 1.27406446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30766.24 | 30766.24 | 1.0000 | 1.27406446 | 1.097408 | 15.97 | 10.36 | 0.00581414 | 30759.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30766.24 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.7478 | 21.11 | 0.00662548 | 21.11 | 0.00662548 | 41.1187 | 10333.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24948.130 | 18226.605 | 1.100970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5645 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100966 | 1.27819620 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12474.07 | 9342.20 | 1.0000 | 0.85213356 | 0.733980 | 26.78 | 18.65 | 0.01061058 | 53975.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12474.07 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.0307 | 23.89 | 0.00972246 | 23.89 | 0.00972246 | 50.7112 | 12046.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30844.676 | 30844.676 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100966 | 1.27819620 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30844.68 | 30844.68 | 1.0000 | 1.27819620 | 1.100966 | 15.99 | 10.38 | 0.00582421 | 30801.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30844.68 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.6872 | 21.11 | 0.00663464 | 21.11 | 0.00663464 | 41.1749 | 10441.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24783.850 | 18090.723 | 1.091110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5938 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.091108 | 1.26675135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12391.92 | 9265.92 | 1.0000 | 0.84450208 | 0.727407 | 26.80 | 18.67 | 0.01062633 | 54034.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12391.92 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.2840 | 23.89 | 0.00973201 | 23.89 | 0.00973201 | 50.7603 | 11939.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30627.390 | 30627.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.091108 | 1.26675135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30627.39 | 30627.39 | 1.0000 | 1.26675135 | 1.091108 | 15.94 | 10.36 | 0.00582839 | 30765.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30627.39 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.8560 | 21.11 | 0.00664882 | 21.11 | 0.00664882 | 41.2620 | 10607.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44916.730 | 32342.291 | 1.919230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9372 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.919231 | 2.22818166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 22458.37 | 16498.60 | 1.0000 | 1.48545400 | 1.279487 | 27.04 | 18.89 | 0.01081104 | 54751.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22458.37 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 32.1597 | 23.89 | 0.00981123 | 23.89 | 0.00981123 | 51.1669 | 21001.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55457.960 | 55457.960 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.919231 | 2.22818166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 55457.96 | 55457.96 | 1.0000 | 2.22818166 | 1.919231 | 15.23 | 10.00 | 0.00577655 | 29915.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55457.96 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 21.4398 | 21.11 | 0.00672594 | 21.11 | 0.00672594 | 41.7348 | 20541.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23197.060 | 16734.359 | 0.996330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9007 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.996331 | 1.15671634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11598.53 | 8532.69 | 1.0000 | 0.77114384 | 0.664220 | 26.99 | 18.86 | 0.01079144 | 54648.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11598.53 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 30.9746 | 23.89 | 0.00983266 | 23.89 | 0.00983266 | 51.2771 | 10899.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28538.367 | 28538.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.996331 | 1.15671634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28538.37 | 28538.37 | 1.0000 | 1.15671634 | 0.996331 | 15.45 | 10.09 | 0.00577133 | 30121.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28538.37 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 20.6497 | 21.11 | 0.00667527 | 21.11 | 0.00667527 | 41.4244 | 10932.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23112.440 | 16664.763 | 0.991310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9183 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991311 | 1.15088916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11556.22 | 8493.84 | 1.0000 | 0.76725844 | 0.660873 | 27.00 | 18.87 | 0.01080089 | 54684.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11556.22 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 31.1314 | 23.89 | 0.00983845 | 23.89 | 0.00983845 | 51.3068 | 10844.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28427.738 | 28427.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991311 | 1.15088916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28427.74 | 28427.74 | 1.0000 | 1.15088916 | 0.991311 | 15.42 | 10.07 | 0.00576619 | 30079.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28427.74 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 20.7543 | 21.11 | 0.00667456 | 21.11 | 0.00667456 | 41.4201 | 10923.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23123.230 | 16673.467 | 0.991910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9166 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991910 | 1.15158453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11561.61 | 8498.57 | 1.0000 | 0.76772283 | 0.661273 | 27.00 | 18.87 | 0.01079996 | 54680.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11561.61 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 31.1126 | 23.89 | 0.00983788 | 23.89 | 0.00983788 | 51.3039 | 10850.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28440.937 | 28440.937 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991910 | 1.15158453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28440.94 | 28440.94 | 1.0000 | 1.15158453 | 0.991910 | 15.42 | 10.09 | 0.00578047 | 30119.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28440.94 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 20.7417 | 21.11 | 0.00669188 | 21.11 | 0.00669188 | 41.5265 | 11145.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25335.020 | 18547.515 | 1.124340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6001 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124341 | 1.30533356 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12667.51 | 9448.73 | 1.0000 | 0.87022158 | 0.749560 | 26.67 | 18.63 | 0.01062969 | 53910.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12667.51 | 34.00 | 0.01447253 | 23.44 | 0.20573941 | 27.4480 | 23.89 | 0.00976771 | 23.88 | 0.00976771 | 50.9443 | 12292.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31360.926 | 31360.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124341 | 1.30533356 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31360.93 | 31360.93 | 1.0000 | 1.30533356 | 1.124341 | 16.09 | 10.51 | 0.00590202 | 31106.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31360.93 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.2987 | 21.11 | 0.00670926 | 21.10 | 0.00670926 | 41.6358 | 13800.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.06 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.09 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.10 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.10 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.09 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.92 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.00 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.99 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.99 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.12 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3242.33 | 2938.50 | 936.50 |
SMSTORE1 | 2884.33 | 2461.33 | 350.83 |
SMSTORE2 | 2366.33 | 2148.67 | 589.50 |
SMSTORE3 | 2372.00 | 2178.50 | 610.50 |
SMSTORE4 | 2364.50 | 2269.67 | 680.17 |
LGSTORE2 | 2207.83 | 2277.83 | 866.00 |
SMSTORE5 | 2161.83 | 2318.83 | 879.50 |
SMSTORE6 | 2166.50 | 2354.33 | 911.67 |
SMSTORE7 | 2205.67 | 2416.33 | 992.83 |
SMSTORE8 | 2371.50 | 2460.50 | 1157.67 |
Facility | 3796.17 | 3594.83 | 1623.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 3.17 | 0.00 | 0.50 | 0.00 |
SMSTORE1 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 10.17 | 0.00 | 0.00 | 0.00 |
Facility | 12.83 | 0.00 | 0.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.950 | 0.227 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.820 | 0.241 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.003 | 0.314 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.000 | 0.314 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.989 | 0.314 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.962 | 0.302 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.967 | 0.335 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.963 | 0.335 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.956 | 0.335 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.972 | 0.355 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.75 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.88 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9851842.76 | 0.00 | 9851842.76 | 2731052.24 | 12582894.99 | 12976396.34 | 3173.27 | 4535.15 | 1051.58 | 15.83 |
SMSTORE1 | 4248639.26 | 0.00 | 4248639.26 | 1359523.50 | 5608162.76 | 6488198.17 | 4440.34 | 3278.17 | 1041.49 | 14.74 |
SMSTORE2 | 3952723.77 | 0.00 | 3952723.77 | 1395493.01 | 5348216.78 | 6488198.17 | 4344.38 | 3637.33 | 778.29 | 82.84 |
SMSTORE3 | 3938561.83 | 0.00 | 3938561.83 | 1395493.01 | 5334054.84 | 6488198.17 | 4345.31 | 3656.70 | 757.99 | 78.51 |
SMSTORE4 | 3891843.76 | 0.00 | 3891843.76 | 1395493.01 | 5287336.76 | 6488198.17 | 4347.88 | 3697.42 | 714.70 | 68.48 |
LGSTORE2 | 6907385.10 | 0.00 | 6907385.10 | 2566144.11 | 9473529.22 | 12976396.34 | 4722.31 | 3404.69 | 632.99 | 43.27 |
SMSTORE5 | 3472400.28 | 0.00 | 3472400.28 | 1406000.65 | 4878400.93 | 6488198.17 | 4721.64 | 3420.33 | 618.02 | 43.52 |
SMSTORE6 | 3456543.30 | 0.00 | 3456543.30 | 1406000.65 | 4862543.95 | 6488198.17 | 4722.64 | 3432.17 | 605.19 | 40.66 |
SMSTORE7 | 3428384.43 | 0.00 | 3428384.43 | 1406000.65 | 4834385.08 | 6488198.17 | 4724.97 | 3464.33 | 570.70 | 33.76 |
SMSTORE8 | 3488266.56 | 0.00 | 3488266.56 | 1733578.79 | 5221845.35 | 6488198.17 | 4721.64 | 3498.08 | 540.28 | 20.25 |
Total Facility | 46636591.04 | 0.00 | 46636591.04 | 16794779.62 | 63431370.67 | 77858378.04 | 4729.46 | 5159.44 | 1392.16 | 146.66 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4678 | 0.0000 | 0.4678 | 0.1116 | 0.5794 | 0.4115 | 256.77 | 4534.65 | 1048.58 |
SMSTORE1 | 0.2018 | 0.0000 | 0.2018 | 0.0593 | 0.2611 | 0.2057 | 1522.52 | 3278.17 | 1039.31 |
SMSTORE2 | 0.2468 | 0.0000 | 0.2468 | 0.0773 | 0.3242 | 0.2057 | 0.00 | 3636.50 | 758.50 |
SMSTORE3 | 0.2460 | 0.0000 | 0.2460 | 0.0773 | 0.3233 | 0.2057 | 0.00 | 3656.42 | 738.58 |
SMSTORE4 | 0.2434 | 0.0000 | 0.2434 | 0.0773 | 0.3207 | 0.2057 | 0.00 | 3697.17 | 697.83 |
LGSTORE2 | 0.4734 | 0.0000 | 0.4734 | 0.1485 | 0.6219 | 0.4115 | 0.00 | 3404.19 | 625.81 |
SMSTORE5 | 0.2379 | 0.0000 | 0.2379 | 0.0824 | 0.3204 | 0.2057 | 0.00 | 3420.33 | 609.67 |
SMSTORE6 | 0.2369 | 0.0000 | 0.2369 | 0.0824 | 0.3194 | 0.2057 | 0.00 | 3431.83 | 598.17 |
SMSTORE7 | 0.2352 | 0.0000 | 0.2352 | 0.0824 | 0.3177 | 0.2057 | 0.00 | 3464.33 | 565.67 |
SMSTORE8 | 0.2393 | 0.0000 | 0.2393 | 0.0873 | 0.3266 | 0.2057 | 0.00 | 3498.00 | 532.00 |
Total Facility | 2.8287 | 0.0000 | 2.8287 | 0.8860 | 3.7147 | 2.4689 | 1626.26 | 5157.90 | 1369.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13279138.81 | 0.00 | 13279138.81 | 12976396.34 | 3168.68 | 0.33 | 5590.98 | 15.83 |
PSZ-AC_2:2 | 5726641.75 | 0.00 | 5726641.75 | 6488198.17 | 4376.09 | 4.00 | 4379.91 | 14.74 |
PSZ-AC_3:3 | 5327801.26 | 0.00 | 5327801.26 | 6488198.17 | 4335.93 | 0.00 | 4424.07 | 82.67 |
PSZ-AC_4:4 | 5308712.04 | 0.00 | 5308712.04 | 6488198.17 | 4336.86 | 0.08 | 4423.05 | 77.84 |
PSZ-AC_5:5 | 5245741.61 | 0.00 | 5245741.61 | 6488198.17 | 4340.71 | 0.33 | 4418.95 | 68.39 |
PSZ-AC_6:6 | 9310347.33 | 0.00 | 9310347.33 | 12976396.34 | 4718.73 | 0.33 | 4040.94 | 43.27 |
PSZ-AC_7:7 | 4680382.35 | 0.00 | 4680382.35 | 6488198.17 | 4717.73 | 0.33 | 4041.94 | 43.52 |
PSZ-AC_8:8 | 4659006.03 | 0.00 | 4659006.03 | 6488198.17 | 4718.81 | 0.33 | 4040.86 | 40.58 |
PSZ-AC_9:9 | 4621037.00 | 0.00 | 4621037.00 | 6488198.17 | 4721.30 | 0.17 | 4038.53 | 33.76 |
PSZ-AC_10:10 | 4701714.30 | 0.00 | 4701714.30 | 6488198.17 | 4719.85 | 0.17 | 4039.99 | 20.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6306 | 0.0000 | 0.6306 | 0.4115 | 253.77 | 0.33 | 5585.90 |
PSZ-AC_2:2 | 0.2720 | 0.0000 | 0.2720 | 0.2057 | 1459.43 | 3.83 | 4376.73 |
PSZ-AC_3:3 | 0.3327 | 0.0000 | 0.3327 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3316 | 0.0000 | 0.3316 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3281 | 0.0000 | 0.3281 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6380 | 0.0000 | 0.6380 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3207 | 0.0000 | 0.3207 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3193 | 0.0000 | 0.3193 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3171 | 0.0000 | 0.3171 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3226 | 0.0000 | 0.3226 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5115.57 | 512.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4504.17 | 774.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4104.04 | 373.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4111.58 | 361.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4127.15 | 336.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3831.22 | 242.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3830.97 | 242.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3834.80 | 235.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3842.61 | 221.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3839.16 | 210.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6381 | 0.8438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2943 | 0.3460 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3230 | 0.4672 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3220 | 0.4679 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3190 | 0.4673 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6258 | 0.8750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3141 | 0.4491 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3130 | 0.4438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3108 | 0.4463 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3147 | 0.4818 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
ElectricityPurchased:Plant | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
Cogeneration:ElectricityPurchased | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
ElectricityNet:Plant | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
Cogeneration:ElectricityNet | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
General:Cogeneration:ElectricityNet | 944.79 | 2102.83 | 01-JAN-07:50 | 99289.72 | 08-JUL-14:50 |
Electricity:HVAC | 286.23 | 0.00 | 01-JAN-00:10 | 59932.35 | 08-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 187.29 | 0.00 | 01-JAN-00:10 | 51724.53 | 08-JUL-14:00 |
General:Cooling:Electricity | 187.29 | 0.00 | 01-JAN-00:10 | 51724.53 | 08-JUL-14:00 |
Fans:Electricity | 98.94 | 0.00 | 01-JAN-00:10 | 9229.12 | 12-FEB-09:10 |
General:Fans:Electricity | 98.94 | 0.00 | 01-JAN-00:10 | 9229.12 | 12-FEB-09:10 |
ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:50 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:50 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 62.00 | 1211.00 | 02-JAN-07:10 | 11839.76 | 09-JAN-14:10 |
WaterSystems:Electricity | 62.00 | 1211.00 | 02-JAN-07:10 | 11839.76 | 09-JAN-14:10 |
Water Heater:WaterSystems:Electricity | 62.00 | 1211.00 | 02-JAN-07:10 | 11839.76 | 09-JAN-14:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 182.52 | 0.00 | 01-JAN-00:10 | 203522.12 | 12-FEB-09:10 |
NaturalGas:HVAC | 182.52 | 0.00 | 01-JAN-00:10 | 203522.12 | 12-FEB-09:10 |
Heating:NaturalGas | 182.52 | 0.00 | 01-JAN-00:10 | 203522.12 | 12-FEB-09:10 |
General:Heating:NaturalGas | 182.52 | 0.00 | 01-JAN-00:10 | 203522.12 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1460.42 | 0.00 | 01-JAN-00:10 | 304968.70 | 13-FEB-08:10 |
EnergyTransfer:Building | 564.47 | 0.00 | 01-JAN-00:10 | 145001.52 | 13-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 119.22 | 0.00 | 01-JAN-00:10 | 31182.51 | 12-FEB-08:10 |
Heating:EnergyTransfer | 47.41 | 0.00 | 01-JAN-00:10 | 145001.52 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 6.60 | 0.00 | 01-JAN-00:10 | 31182.51 | 12-FEB-08:10 |
General:Heating:EnergyTransfer | 47.41 | 0.00 | 01-JAN-00:10 | 145001.52 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 6.60 | 0.00 | 01-JAN-00:10 | 31182.51 | 12-FEB-08:10 |
Cooling:EnergyTransfer | 517.07 | 0.00 | 01-JAN-00:10 | 95583.03 | 08-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 112.62 | 0.00 | 01-JAN-00:10 | 16340.63 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer | 517.07 | 0.00 | 01-JAN-00:10 | 95583.03 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 112.62 | 0.00 | 01-JAN-00:10 | 16340.63 | 08-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 64.24 | 0.00 | 01-JAN-00:10 | 10917.88 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.67 | 0.00 | 01-JAN-00:10 | 10917.88 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.67 | 0.00 | 01-JAN-00:10 | 10917.88 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 62.57 | 0.00 | 01-JAN-00:10 | 9457.91 | 11-OCT-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 62.57 | 0.00 | 01-JAN-00:10 | 9457.91 | 11-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 48.40 | 0.00 | 01-JAN-00:10 | 12782.90 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.67 | 0.00 | 01-JAN-00:10 | 12782.90 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.67 | 0.00 | 01-JAN-00:10 | 12782.90 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 45.73 | 0.00 | 01-JAN-00:10 | 8334.52 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 45.73 | 0.00 | 01-JAN-00:10 | 8334.52 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 48.03 | 0.00 | 01-JAN-00:10 | 13464.81 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.99 | 0.00 | 01-JAN-00:10 | 13464.81 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.99 | 0.00 | 01-JAN-00:10 | 13464.81 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 45.04 | 0.00 | 01-JAN-00:10 | 8372.04 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 45.04 | 0.00 | 01-JAN-00:10 | 8372.04 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 46.24 | 0.00 | 01-JAN-00:10 | 14177.64 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 3.50 | 0.00 | 01-JAN-00:10 | 14177.64 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 3.50 | 0.00 | 01-JAN-00:10 | 14177.64 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 42.74 | 0.00 | 01-JAN-00:10 | 8228.82 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 42.74 | 0.00 | 01-JAN-00:10 | 8228.82 | 08-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 76.99 | 0.00 | 01-JAN-00:10 | 29212.17 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.16 | 0.00 | 01-JAN-00:10 | 29212.17 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 7.16 | 0.00 | 01-JAN-00:10 | 29212.17 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 69.83 | 0.00 | 01-JAN-00:10 | 15099.58 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 69.83 | 0.00 | 01-JAN-00:10 | 15099.58 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 39.60 | 0.00 | 01-JAN-00:10 | 15251.26 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 4.16 | 0.00 | 01-JAN-00:10 | 15251.26 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 4.16 | 0.00 | 01-JAN-00:10 | 15251.26 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 35.44 | 0.00 | 01-JAN-00:10 | 7889.92 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 35.44 | 0.00 | 01-JAN-00:10 | 7889.92 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 39.16 | 0.00 | 01-JAN-00:10 | 15444.84 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 4.35 | 0.00 | 01-JAN-00:10 | 15444.84 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 4.35 | 0.00 | 01-JAN-00:10 | 15444.84 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 34.81 | 0.00 | 01-JAN-00:10 | 7850.52 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 34.81 | 0.00 | 01-JAN-00:10 | 7850.52 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 38.60 | 0.00 | 01-JAN-00:10 | 16409.90 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 5.15 | 0.00 | 01-JAN-00:10 | 16409.90 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 5.15 | 0.00 | 01-JAN-00:10 | 16409.90 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 33.45 | 0.00 | 01-JAN-00:10 | 7875.17 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 33.45 | 0.00 | 01-JAN-00:10 | 7875.17 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 44.00 | 0.00 | 01-JAN-00:10 | 18688.37 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 9.16 | 0.00 | 01-JAN-00:10 | 18688.37 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 9.16 | 0.00 | 01-JAN-00:10 | 18688.37 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 34.84 | 0.00 | 01-JAN-00:10 | 9003.18 | 08-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 34.84 | 0.00 | 01-JAN-00:10 | 9003.18 | 08-JUL-14:10 |
EnergyTransfer:HVAC | 895.95 | 0.00 | 01-JAN-00:10 | 194666.78 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 146.02 | 0.00 | 01-JAN-00:10 | 162817.70 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 749.93 | 0.00 | 01-JAN-00:10 | 194666.78 | 08-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 6.601 | -112.619 | 0.000 | 0.000 | 24.329 | 95.826 | 26.249 | 16.959 | 0.000 | 5.321 | 0.001 | 0.000 | -8.003 | 0.000 | -19.004 | -35.660 |
SMSTORE1 | 0.000 | 0.000 | 1.674 | -62.566 | 0.000 | 0.000 | 12.025 | 57.583 | 13.125 | 8.404 | 0.000 | 2.882 | 0.001 | 0.000 | -4.214 | 0.000 | -9.059 | -19.855 |
SMSTORE2 | 0.000 | 0.000 | 2.675 | -45.725 | 0.000 | 0.000 | 7.298 | 40.956 | 10.421 | 8.371 | 0.000 | 2.824 | 0.000 | 0.000 | -4.200 | 0.000 | -9.318 | -13.301 |
SMSTORE3 | 0.000 | 0.000 | 2.986 | -45.042 | 0.000 | 0.000 | 7.307 | 40.956 | 10.421 | 8.382 | 0.000 | 2.824 | 0.000 | 0.000 | -4.158 | 0.000 | -9.261 | -14.415 |
SMSTORE4 | 0.000 | 0.000 | 3.496 | -42.739 | 0.000 | 0.000 | 7.322 | 40.956 | 10.421 | 8.406 | 0.000 | 2.825 | 0.002 | 0.000 | -4.095 | 0.000 | -9.174 | -17.418 |
LGSTORE2 | 0.000 | 0.000 | 7.159 | -69.833 | 0.000 | 0.000 | 25.194 | 43.277 | 19.173 | 16.922 | 0.000 | 5.099 | 0.001 | 0.000 | -7.871 | 0.000 | -16.893 | -22.228 |
SMSTORE5 | 0.000 | 0.000 | 4.162 | -35.436 | 0.000 | 0.000 | 12.604 | 22.197 | 9.586 | 8.454 | 0.000 | 2.835 | 0.000 | 0.000 | -3.924 | 0.000 | -9.131 | -11.348 |
SMSTORE6 | 0.000 | 0.000 | 4.346 | -34.813 | 0.000 | 0.000 | 12.613 | 22.197 | 9.586 | 8.464 | 0.000 | 2.836 | 0.000 | 0.000 | -3.902 | 0.000 | -9.101 | -12.226 |
SMSTORE7 | 0.000 | 0.000 | 5.148 | -33.447 | 0.000 | 0.000 | 12.636 | 22.197 | 9.586 | 8.487 | 0.000 | 2.836 | 0.001 | 0.000 | -3.838 | 0.000 | -9.012 | -14.594 |
SMSTORE8 | 0.000 | 0.000 | 9.159 | -34.836 | 0.000 | 0.000 | 12.668 | 22.197 | 9.586 | 8.522 | 0.000 | 2.970 | 0.002 | 0.000 | -3.612 | 0.000 | -11.943 | -14.710 |
Total Facility | 0.000 | 0.000 | 47.406 | -517.054 | 0.000 | 0.000 | 133.998 | 408.342 | 128.154 | 101.370 | 0.000 | 33.253 | 0.010 | 0.000 | -47.817 | 0.000 | -111.896 | -175.756 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -33455.21 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 33468.65 | 0.00 | -71.35 | 0.00 | -90.73 | 0.00 |
SMSTORE1 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19190.29 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 19199.28 | 0.00 | -37.64 | 0.00 | -45.67 | 0.00 |
SMSTORE2 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -18080.30 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 18144.21 | 0.00 | -130.79 | 0.00 | -7.44 | 0.00 |
SMSTORE3 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -18152.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 18216.53 | 0.00 | -131.36 | 0.00 | -7.50 | 0.00 |
SMSTORE4 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -17901.46 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 17963.29 | 0.00 | -128.99 | 0.00 | -7.16 | 0.00 |
LGSTORE2 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -31433.05 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 31427.30 | 0.00 | -63.29 | 0.00 | -79.60 | 0.00 |
SMSTORE5 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16169.78 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16167.74 | 0.00 | -30.38 | 0.00 | -41.90 | 0.00 |
SMSTORE6 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16079.57 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16076.28 | 0.00 | -29.70 | 0.00 | -41.33 | 0.00 |
SMSTORE7 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -15615.92 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 15610.00 | 0.00 | -28.49 | 0.00 | -39.91 | 0.00 |
SMSTORE8 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15808.06 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 57.67 | 0.00 | 0.00 | 15730.94 | 0.00 | -0.00 | 0.00 | -54.87 | 0.00 |
Total Facility | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -151291.53 | 0.00 | 0.00 | 295.52 | 450.00 | 1450.75 | 0.00 | 0.00 | 0.00 | 149960.74 | 0.00 | -365.73 | 0.00 | -499.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 58757.29 | 0.00 | 0.00 | 0.00 | 284.42 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -441.15 | 0.00 | -1750.23 | -56999.95 |
SMSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 30754.77 | 0.00 | 0.00 | 0.00 | 134.34 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -259.40 | 0.00 | -881.77 | -29822.75 |
SMSTORE2 | 12-FEB-08:61 | 0.00 | 0.00 | 30847.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -247.16 | 0.00 | -865.69 | -29809.83 |
SMSTORE3 | 12-FEB-08:61 | 0.00 | 0.00 | 30924.39 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.29 | 0.00 | -858.29 | -29899.62 |
SMSTORE4 | 12-FEB-08:61 | 0.00 | 0.00 | 30714.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -235.91 | 0.00 | -850.74 | -29703.09 |
LGSTORE2 | 13-FEB-08:61 | 0.00 | 0.00 | 55710.01 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -176.36 | 0.00 | -1244.86 | -54437.42 |
SMSTORE5 | 13-FEB-08:61 | 0.00 | 0.00 | 28683.97 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.35 | 0.00 | -676.81 | -27991.13 |
SMSTORE6 | 13-FEB-08:61 | 0.00 | 0.00 | 28576.32 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88.48 | 0.00 | -674.20 | -27887.96 |
SMSTORE7 | 13-FEB-08:61 | 0.00 | 0.00 | 28589.74 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -80.34 | 0.00 | -662.60 | -27921.11 |
SMSTORE8 | 10-JAN-08:12 | 0.00 | 0.00 | 31632.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -410.15 | 0.00 | -771.58 | -30524.88 |
Total Facility | 13-FEB-08:61 | 0.00 | 0.00 | 277722.06 | 0.00 | 0.00 | 0.00 | 758.34 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1303.07 | 0.00 | -8848.84 | -270230.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0620 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0620 | 0.1996 | 1.0000 | Not calculated | 0.4115 | 0.1996 | ||
PSZ-AC_2:2 | 1.0935 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0935 | 0.1881 | 1.0000 | Not calculated | 0.2057 | 0.1881 | ||
PSZ-AC_3:3 | 1.0974 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0974 | 0.1875 | 1.0000 | Not calculated | 0.2057 | 0.1875 | ||
PSZ-AC_4:4 | 1.1010 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1010 | 0.1869 | 1.0000 | Not calculated | 0.2057 | 0.1869 | ||
PSZ-AC_5:5 | 1.0911 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0911 | 0.1886 | 1.0000 | Not calculated | 0.2057 | 0.1886 | ||
PSZ-AC_6:6 | 1.9192 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9192 | 0.2144 | 1.0000 | Not calculated | 0.4115 | 0.2144 | ||
PSZ-AC_7:7 | 0.9963 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9963 | 0.2065 | 1.0000 | Not calculated | 0.2057 | 0.2065 | ||
PSZ-AC_8:8 | 0.9913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9913 | 0.2075 | 1.0000 | Not calculated | 0.2057 | 0.2075 | ||
PSZ-AC_9:9 | 0.9919 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9919 | 0.2074 | 1.0000 | Not calculated | 0.2057 | 0.2074 | ||
PSZ-AC_10:10 | 1.1243 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1243 | 0.1830 | 1.0000 | Not calculated | 0.2057 | 0.1830 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0620 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0620 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1996 | ||
PSZ-AC_2:2 | 1.0935 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0935 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1881 | ||
PSZ-AC_3:3 | 1.0974 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0974 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1875 | ||
PSZ-AC_4:4 | 1.1010 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1010 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1869 | ||
PSZ-AC_5:5 | 1.0911 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0911 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1886 | ||
PSZ-AC_6:6 | 1.9192 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9192 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2144 | ||
PSZ-AC_7:7 | 0.9963 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9963 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2065 | ||
PSZ-AC_8:8 | 0.9913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9913 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2075 | ||
PSZ-AC_9:9 | 0.9919 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9919 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2074 | ||
PSZ-AC_10:10 | 1.1243 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1243 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1830 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0620 | 2.0620 | 2.0620 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0935 | 1.0935 | 1.0935 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0974 | 1.0974 | 1.0974 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1010 | 1.1010 | 1.1010 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0911 | 1.0911 | 1.0911 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9192 | 1.9192 | 1.9192 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9963 | 0.9963 | 0.9963 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9913 | 0.9913 | 0.9913 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9919 | 0.9919 | 0.9919 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1243 | 1.1243 | 1.1243 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0620 | 2.0620 | 2.0620 | 2.0620 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0935 | 1.0935 | 1.0935 | 1.0935 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0974 | 1.0974 | 1.0974 | 1.0974 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1010 | 1.1010 | 1.1010 | 1.1010 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0911 | 1.0911 | 1.0911 | 1.0911 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9192 | 1.9192 | 1.9192 | 1.9192 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9963 | 0.9963 | 0.9963 | 0.9963 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9913 | 0.9913 | 0.9913 | 0.9913 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9919 | 0.9919 | 0.9919 | 0.9919 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1243 | 1.1243 | 1.1243 | 1.1243 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0620 | 2.0620 | 2.0620 | No | 0.4115 | 0.3484 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0935 | 1.0935 | 1.0935 | No | 0.2057 | 0.3768 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0974 | 1.0974 | 1.0974 | No | 0.2057 | 0.3711 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1010 | 1.1010 | 1.1010 | No | 0.2057 | 0.3673 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0911 | 1.0911 | 1.0911 | No | 0.2057 | 0.3615 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9192 | 1.9192 | 1.9192 | No | 0.4115 | 0.3734 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9963 | 0.9963 | 0.9963 | No | 0.2057 | 0.3508 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9913 | 0.9913 | 0.9913 | No | 0.2057 | 0.3511 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9919 | 0.9919 | 0.9919 | No | 0.2057 | 0.3441 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1243 | 1.1243 | 1.1243 | No | 0.2057 | 0.2779 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0620 | 2.0620 | 2.0620 | 2.0620 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0935 | 1.0935 | 1.0935 | 1.0935 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0974 | 1.0974 | 1.0974 | 1.0974 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1010 | 1.1010 | 1.1010 | 1.1010 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0911 | 1.0911 | 1.0911 | 1.0911 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9192 | 1.9192 | 1.9192 | 1.9192 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9963 | 0.9963 | 0.9963 | 0.9963 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9913 | 0.9913 | 0.9913 | 0.9913 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9919 | 0.9919 | 0.9919 | 0.9919 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1243 | 1.1243 | 1.1243 | 1.1243 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 182.52 | 203522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 187.29 | 51724.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.06 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 98.94 | 9229.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62.00 | 11839.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 944.79 |
Natural Gas | 0.00 | 182.52 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1127.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 89.60 |
Fans (All) | 47.33 |
Service Water Heating | 29.66 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 451.98 |
Subtotal | 451.98 |
Natural Gas [MJ/m2] | |
Space Heating | 87.32 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 87.32 |
Subtotal | 87.32 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.22 |
Space Heating | 16.19 |
Space Cooling | 16.61 |
Fans (All) | 8.78 |
Service Water Heating | 5.50 |
Receptacle Equipment | 11.37 |
Miscellaneous | 5.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8535.33 | 224.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8502.83 | 257.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8564.33 | 195.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8649.33 | 110.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8670.33 | 89.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8634.17 | 125.83 | 0.00 | 0.00 | 0.00 |
Min | 8502.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 257.17 | 0.00 | 0.00 | 0.00 |
Average | 8640.70 | 119.30 | 0.00 | 0.00 | 0.00 |
Sum | 86407.00 | 1193.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25433.17 | 41.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25433.33 | 41.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25435.33 | 39.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93099.00 | 112.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45859.00 | 53.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45860.50 | 51.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45861.00 | 51.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45855.00 | 57.00 | 0.00 | 0.00 | 0.00 |
Min | 25433.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93099.00 | 112.00 | 0.00 | 0.00 | 0.00 |
Average | 48565.43 | 44.77 | 0.00 | 0.00 | 0.00 |
Sum | 485654.33 | 447.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7710.83 | 1049.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8548.33 | 211.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7057.00 | 1703.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7069.50 | 1690.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7081.17 | 1678.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7078.17 | 1681.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7107.50 | 1652.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7115.33 | 1644.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7137.00 | 1623.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7086.67 | 1673.33 | 0.00 | 0.00 | 0.00 |
Min | 7057.00 | 211.67 | 0.00 | 0.00 | 0.00 |
Max | 8548.33 | 1703.00 | 0.00 | 0.00 | 0.00 |
Average | 7299.15 | 1460.85 | 0.00 | 0.00 | 0.00 |
Sum | 72991.50 | 14608.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 85797.83 | 3243.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42826.17 | 950.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24489.67 | 985.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24482.17 | 992.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24373.83 | 1101.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 86482.00 | 6729.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 42523.67 | 3388.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 42450.83 | 3461.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 42410.83 | 3501.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 42610.33 | 3301.67 | 0.00 | 0.00 | 0.00 |
Min | 24373.83 | 950.83 | 0.00 | 0.00 | 0.00 |
Max | 86482.00 | 6729.00 | 0.00 | 0.00 | 0.00 |
Average | 45844.73 | 2765.47 | 0.00 | 0.00 | 0.00 |
Sum | 458447.33 | 27654.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186929E+10 | 10574.19 | 27-JAN-00:02 | -3.9 | -6.1 | 0.109125E+10 | 1478.14 | 20-JAN-13:00 | -3.9 | -6.1 |
February | 0.295013E+10 | 12098.31 | 11-FEB-20:32 | -7.0 | -8.8 | 0.106504E+10 | 1685.85 | 26-FEB-17:10 | 23.72 | 11.96 |
March | 0.592443E+10 | 10636.92 | 30-MAR-16:10 | 27.62 | 17.53 | 0.128872E+10 | 1685.97 | 11-MAR-13:50 | 27.62 | 17.53 |
April | 0.766847E+10 | 10644.16 | 17-APR-16:20 | 28.70 | 16.48 | 0.133089E+10 | 1685.96 | 14-APR-12:30 | 28.70 | 16.48 |
May | 0.109887E+11 | 12316.31 | 19-MAY-17:00 | 30.60 | 19.15 | 0.139999E+10 | 1686.00 | 29-MAY-17:00 | 29.40 | 20.07 |
June | 0.148299E+11 | 31661.54 | 15-JUN-07:02 | 22.20 | 18.87 | 0.135452E+10 | 1686.05 | 24-JUN-12:39 | 31.83 | 23.51 |
July | 0.168318E+11 | 31921.90 | 17-JUL-07:02 | 22.07 | 19.58 | 0.141278E+10 | 1686.04 | 30-JUL-17:10 | 30.60 | 23.73 |
August | 0.178208E+11 | 31187.91 | 27-AUG-07:02 | 21.38 | 19.77 | 0.139417E+10 | 1686.05 | 06-AUG-12:09 | 21.38 | 19.77 |
September | 0.135428E+11 | 33463.18 | 16-SEP-07:02 | 22.20 | 20.70 | 0.136501E+10 | 1686.06 | 09-SEP-12:39 | 22.20 | 20.70 |
October | 0.977075E+10 | 27047.31 | 19-OCT-07:03 | 19.40 | 19.12 | 0.136681E+10 | 1686.02 | 08-OCT-17:19 | 19.40 | 19.12 |
November | 0.640525E+10 | 9643.31 | 05-NOV-16:07 | 24.03 | 17.90 | 0.125429E+10 | 1685.86 | 11-NOV-13:09 | 21.10 | 11.68 |
December | 0.401776E+10 | 7944.37 | 01-DEC-00:03 | 1.80 | 1.51 | 0.112425E+10 | 1660.38 | 10-DEC-18:40 | 15.57 | 7.68 |
Annual Sum or Average | 0.112620E+12 | 0.154477E+11 | ||||||||
Minimum of Months | 0.186929E+10 | 7944.37 | -7.0 | -8.8 | 0.106504E+10 | 1478.14 | -3.9 | -6.1 | ||
Maximum of Months | 0.178208E+11 | 33463.18 | 30.60 | 20.70 | 0.141278E+10 | 1686.06 | 31.83 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103449E+10 | 3157.03 | 21-JAN-09:05 | 5.10 | 2.71 | 0.569796E+09 | 842.90 | 29-JAN-18:00 | 13.30 | 5.45 |
February | 0.168703E+10 | 17202.22 | 28-FEB-22:23 | 18.10 | 10.49 | 0.553970E+09 | 842.90 | 26-FEB-17:10 | 18.10 | 10.49 |
March | 0.345001E+10 | 18865.99 | 12-MAR-17:07 | 16.60 | 7.83 | 0.666499E+09 | 842.96 | 11-MAR-13:00 | 16.60 | 7.83 |
April | 0.468451E+10 | 16914.00 | 08-APR-20:17 | 19.67 | 9.78 | 0.671747E+09 | 843.10 | 16-APR-17:19 | 26.33 | 15.82 |
May | 0.646935E+10 | 15820.78 | 13-MAY-20:50 | 17.95 | 11.51 | 0.699702E+09 | 843.15 | 21-MAY-17:00 | 25.60 | 19.30 |
June | 0.816775E+10 | 18466.70 | 15-JUN-07:02 | 22.20 | 18.87 | 0.676413E+09 | 843.00 | 30-JUN-12:39 | 30.93 | 23.53 |
July | 0.906444E+10 | 18764.99 | 17-JUL-07:02 | 22.07 | 19.58 | 0.706353E+09 | 843.01 | 16-JUL-16:10 | 22.07 | 19.58 |
August | 0.945730E+10 | 18458.10 | 14-AUG-07:02 | 23.98 | 21.20 | 0.697081E+09 | 843.01 | 27-AUG-12:00 | 31.70 | 22.73 |
September | 0.745801E+10 | 19192.88 | 16-SEP-07:02 | 22.20 | 20.70 | 0.681978E+09 | 843.05 | 24-SEP-17:40 | 27.07 | 19.80 |
October | 0.546225E+10 | 17314.10 | 11-OCT-20:08 | 17.93 | 10.36 | 0.692526E+09 | 842.98 | 08-OCT-17:10 | 17.93 | 10.36 |
November | 0.358172E+10 | 12157.79 | 03-NOV-21:10 | 18.22 | 16.16 | 0.646685E+09 | 842.91 | 19-NOV-13:30 | 20.30 | 17.56 |
December | 0.204997E+10 | 4033.22 | 17-DEC-17:53 | 1.10 | -2.9 | 0.600357E+09 | 842.90 | 10-DEC-18:00 | 1.10 | -2.9 |
Annual Sum or Average | 0.625668E+11 | 0.786311E+10 | ||||||||
Minimum of Months | 0.103449E+10 | 3157.03 | 1.10 | -2.9 | 0.553970E+09 | 842.90 | 1.10 | -2.9 | ||
Maximum of Months | 0.945730E+10 | 19192.88 | 23.98 | 21.20 | 0.706353E+09 | 843.15 | 31.70 | 23.53 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659185E+09 | 4900.17 | 27-JAN-10:23 | -2.5 | -5.0 | 0.325856E+09 | 702.41 | 31-JAN-18:10 | 18.72 | 13.14 |
February | 0.116824E+10 | 4713.49 | 01-FEB-08:61 | -0.6 | -1.9 | 0.319931E+09 | 842.90 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.254586E+10 | 5586.87 | 30-MAR-16:10 | 27.62 | 17.53 | 0.398694E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.323222E+10 | 5638.02 | 17-APR-16:10 | 28.80 | 16.45 | 0.402399E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.458051E+10 | 9760.79 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425316E+09 | 842.98 | 06-MAY-12:39 | 16.57 | 15.54 |
June | 0.609442E+10 | 16904.06 | 05-JUN-06:03 | 19.60 | 16.99 | 0.417216E+09 | 842.96 | 03-JUN-12:09 | 19.60 | 16.99 |
July | 0.670643E+10 | 17139.05 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420471E+09 | 842.99 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.722825E+10 | 18084.30 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432139E+09 | 842.99 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.540537E+10 | 17537.20 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410720E+09 | 842.97 | 09-SEP-12:09 | 22.70 | 20.23 |
October | 0.389336E+10 | 14118.69 | 18-OCT-06:03 | 19.90 | 19.90 | 0.407994E+09 | 842.94 | 14-OCT-12:50 | 19.90 | 19.90 |
November | 0.260329E+10 | 4343.45 | 05-NOV-14:00 | 23.30 | 18.52 | 0.374214E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.160870E+10 | 4036.89 | 15-DEC-08:61 | 2.88 | 0.94 | 0.336916E+09 | 702.45 | 12-DEC-18:30 | 2.88 | 0.94 |
Annual Sum or Average | 0.457258E+11 | 0.467187E+10 | ||||||||
Minimum of Months | 0.659185E+09 | 4036.89 | -2.5 | -5.0 | 0.319931E+09 | 702.41 | 2.88 | 0.94 | ||
Maximum of Months | 0.722825E+10 | 18084.30 | 28.80 | 20.23 | 0.432139E+09 | 842.99 | 28.80 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562510E+09 | 5036.33 | 26-JAN-10:13 | -3.1 | -6.0 | 0.325112E+09 | 702.41 | 31-JAN-18:00 | 17.80 | 12.69 |
February | 0.107120E+10 | 4671.13 | 01-FEB-08:61 | -0.6 | -1.9 | 0.318340E+09 | 842.89 | 25-FEB-13:39 | 19.63 | 9.14 |
March | 0.242319E+10 | 5505.82 | 30-MAR-16:10 | 27.62 | 17.53 | 0.396715E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.316167E+10 | 5613.71 | 17-APR-16:10 | 28.80 | 16.45 | 0.401822E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.453986E+10 | 9785.33 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425275E+09 | 842.98 | 06-MAY-12:39 | 16.57 | 15.54 |
June | 0.611341E+10 | 17420.27 | 05-JUN-06:03 | 19.60 | 16.99 | 0.417216E+09 | 842.96 | 03-JUN-12:09 | 19.60 | 16.99 |
July | 0.674382E+10 | 17223.59 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420472E+09 | 842.99 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.726696E+10 | 18156.01 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432141E+09 | 842.99 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.540444E+10 | 17584.70 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410714E+09 | 842.97 | 09-SEP-12:09 | 22.70 | 20.23 |
October | 0.382557E+10 | 14123.55 | 18-OCT-06:03 | 19.90 | 19.90 | 0.407029E+09 | 842.94 | 14-OCT-12:50 | 19.90 | 19.90 |
November | 0.246529E+10 | 4241.39 | 05-NOV-14:00 | 23.30 | 18.52 | 0.372570E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.146534E+10 | 3991.86 | 15-DEC-08:61 | 2.88 | 0.94 | 0.335356E+09 | 702.44 | 12-DEC-18:30 | 2.88 | 0.94 |
Annual Sum or Average | 0.450433E+11 | 0.466276E+10 | ||||||||
Minimum of Months | 0.562510E+09 | 3991.86 | -3.1 | -6.0 | 0.318340E+09 | 702.41 | 2.88 | 0.94 | ||
Maximum of Months | 0.726696E+10 | 18156.01 | 28.80 | 20.23 | 0.432141E+09 | 842.99 | 28.80 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435617E+09 | 3445.90 | 16-JAN-11:03 | 3.68 | -0.8 | 0.324084E+09 | 702.40 | 31-JAN-18:00 | 17.80 | 12.69 |
February | 0.921705E+09 | 4924.99 | 03-FEB-20:33 | -2.6 | -5.8 | 0.315930E+09 | 842.89 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.220554E+10 | 5283.17 | 30-MAR-16:10 | 27.62 | 17.53 | 0.393184E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.295045E+10 | 5449.53 | 17-APR-16:10 | 28.80 | 16.45 | 0.400326E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.431175E+10 | 8429.34 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425100E+09 | 842.98 | 06-MAY-12:50 | 16.57 | 15.54 |
June | 0.591894E+10 | 16617.12 | 15-JUN-06:02 | 22.20 | 18.57 | 0.417170E+09 | 842.99 | 24-JUN-12:20 | 31.47 | 23.66 |
July | 0.656464E+10 | 16971.94 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420437E+09 | 842.98 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.708580E+10 | 17905.47 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432104E+09 | 842.98 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.521524E+10 | 17344.34 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410655E+09 | 843.00 | 09-SEP-12:20 | 22.70 | 20.23 |
October | 0.362775E+10 | 13554.34 | 18-OCT-06:03 | 19.90 | 19.90 | 0.405416E+09 | 842.94 | 14-OCT-12:00 | 19.90 | 19.90 |
November | 0.223767E+10 | 4015.59 | 05-NOV-15:00 | 23.90 | 18.46 | 0.369995E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.126472E+10 | 3930.16 | 18-DEC-10:13 | 1.50 | -2.3 | 0.333253E+09 | 702.44 | 12-DEC-17:40 | 1.50 | -2.3 |
Annual Sum or Average | 0.427398E+11 | 0.464766E+10 | ||||||||
Minimum of Months | 0.435617E+09 | 3445.90 | -2.6 | -5.8 | 0.315930E+09 | 702.40 | 1.50 | -2.3 | ||
Maximum of Months | 0.708580E+10 | 17905.47 | 28.80 | 20.23 | 0.432104E+09 | 843.00 | 31.47 | 23.66 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501387E+09 | 7398.18 | 25-JAN-20:43 | 2.98 | 0.71 | 0.110233E+10 | 1910.82 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.129861E+10 | 5609.26 | 28-FEB-15:30 | 24.15 | 13.12 | 0.107147E+10 | 2247.80 | 25-FEB-15:00 | 24.15 | 13.12 |
March | 0.339761E+10 | 8967.35 | 30-MAR-15:00 | 27.80 | 17.08 | 0.132812E+10 | 2247.80 | 04-MAR-15:09 | 27.80 | 17.08 |
April | 0.466501E+10 | 9596.92 | 17-APR-15:00 | 28.90 | 16.41 | 0.136670E+10 | 2247.85 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.699579E+10 | 11640.24 | 30-MAY-07:03 | 22.07 | 19.14 | 0.145510E+10 | 2248.01 | 06-MAY-14:09 | 22.07 | 19.14 |
June | 0.100349E+11 | 30195.72 | 15-JUN-07:02 | 22.20 | 18.87 | 0.143015E+10 | 2248.02 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.111762E+11 | 30449.72 | 25-JUL-07:03 | 21.20 | 18.27 | 0.143881E+10 | 2248.02 | 22-JUL-14:00 | 21.20 | 18.27 |
August | 0.121410E+11 | 28676.94 | 03-AUG-07:02 | 24.18 | 22.24 | 0.148063E+10 | 2248.06 | 12-AUG-14:09 | 30.68 | 23.13 |
September | 0.869336E+10 | 31440.33 | 16-SEP-07:02 | 22.20 | 20.70 | 0.140950E+10 | 2248.02 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.582760E+10 | 23243.19 | 19-OCT-07:03 | 19.40 | 19.12 | 0.137559E+10 | 2247.91 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.334517E+10 | 7365.12 | 05-NOV-15:00 | 23.90 | 18.46 | 0.124812E+10 | 2247.80 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.175761E+10 | 6768.50 | 17-DEC-15:13 | 4.40 | -0.9 | 0.113414E+10 | 1994.97 | 12-DEC-17:30 | 4.40 | -0.9 |
Annual Sum or Average | 0.698342E+11 | 0.158407E+11 | ||||||||
Minimum of Months | 0.501387E+09 | 5609.26 | 2.98 | -0.9 | 0.107147E+10 | 1910.82 | 4.40 | -0.9 | ||
Maximum of Months | 0.121410E+11 | 31440.33 | 28.90 | 22.24 | 0.148063E+10 | 2248.06 | 32.40 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231362E+09 | 4551.21 | 26-JAN-19:03 | -0.7 | -4.3 | 0.550622E+09 | 944.51 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.611086E+09 | 4403.14 | 02-FEB-10:53 | 0.00 | -2.2 | 0.534585E+09 | 1123.87 | 25-FEB-15:00 | 20.60 | 9.33 |
March | 0.163623E+10 | 4616.02 | 30-MAR-15:00 | 27.80 | 17.08 | 0.661851E+09 | 1123.87 | 04-MAR-15:20 | 27.80 | 17.08 |
April | 0.232098E+10 | 4989.91 | 17-APR-15:00 | 28.90 | 16.41 | 0.682330E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.356293E+10 | 5767.38 | 30-MAY-15:00 | 30.60 | 21.44 | 0.727430E+09 | 1123.97 | 06-MAY-14:09 | 30.60 | 21.44 |
June | 0.517485E+10 | 15530.05 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715029E+09 | 1123.98 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.577955E+10 | 15493.60 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719357E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.627862E+10 | 14744.95 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740269E+09 | 1123.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.447009E+10 | 16173.60 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704727E+09 | 1123.98 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.293029E+10 | 11100.50 | 19-OCT-07:03 | 19.40 | 19.12 | 0.687053E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.161763E+10 | 3788.42 | 05-NOV-15:00 | 23.90 | 18.46 | 0.622824E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.822796E+09 | 3989.28 | 02-DEC-10:43 | 1.52 | -2.3 | 0.566419E+09 | 997.45 | 12-DEC-17:30 | 20.85 | 15.83 |
Annual Sum or Average | 0.354364E+11 | 0.791250E+10 | ||||||||
Minimum of Months | 0.231362E+09 | 3788.42 | -0.7 | -4.3 | 0.534585E+09 | 944.51 | 19.40 | 9.33 | ||
Maximum of Months | 0.627862E+10 | 16173.60 | 30.60 | 22.24 | 0.740269E+09 | 1123.98 | 32.52 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214918E+09 | 4910.48 | 26-JAN-11:13 | -2.2 | -5.5 | 0.550184E+09 | 938.61 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.583879E+09 | 4849.37 | 03-FEB-11:43 | -2.0 | -5.4 | 0.533489E+09 | 1123.87 | 25-FEB-15:00 | 20.60 | 9.33 |
March | 0.156983E+10 | 4526.48 | 30-MAR-15:00 | 27.80 | 17.08 | 0.659631E+09 | 1123.87 | 04-MAR-15:20 | 27.80 | 17.08 |
April | 0.224655E+10 | 4910.29 | 17-APR-15:00 | 28.90 | 16.41 | 0.680948E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.348602E+10 | 5706.12 | 30-MAY-15:00 | 30.60 | 21.44 | 0.727262E+09 | 1123.97 | 06-MAY-14:09 | 30.60 | 21.44 |
June | 0.511862E+10 | 15437.64 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715020E+09 | 1123.98 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.572811E+10 | 15408.06 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719348E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.622740E+10 | 14658.47 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740264E+09 | 1124.00 | 12-AUG-14:09 | 30.68 | 23.13 |
September | 0.442107E+10 | 16083.38 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704705E+09 | 1123.96 | 09-SEP-14:39 | 22.20 | 20.70 |
October | 0.287267E+10 | 10699.40 | 19-OCT-07:03 | 19.40 | 19.12 | 0.685909E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.156038E+10 | 3714.57 | 05-NOV-15:00 | 23.90 | 18.46 | 0.621225E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.784706E+09 | 3925.79 | 02-DEC-18:13 | 1.83 | -2.5 | 0.565662E+09 | 997.45 | 12-DEC-17:30 | 20.85 | 15.83 |
Annual Sum or Average | 0.348142E+11 | 0.790365E+10 | ||||||||
Minimum of Months | 0.214918E+09 | 3714.57 | -2.2 | -5.5 | 0.533489E+09 | 938.61 | 19.40 | 9.33 | ||
Maximum of Months | 0.622740E+10 | 16083.38 | 30.60 | 22.24 | 0.740264E+09 | 1124.00 | 32.40 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161656E+09 | 3218.50 | 12-JAN-11:53 | 5.00 | 0.75 | 0.548961E+09 | 923.91 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.501208E+09 | 4552.07 | 03-FEB-18:03 | -0.7 | -4.8 | 0.530694E+09 | 1123.87 | 25-FEB-15:39 | 20.97 | 9.57 |
March | 0.138506E+10 | 4327.14 | 30-MAR-15:00 | 27.80 | 17.08 | 0.653994E+09 | 1123.87 | 04-MAR-15:30 | 27.80 | 17.08 |
April | 0.204502E+10 | 4721.09 | 17-APR-15:00 | 28.90 | 16.41 | 0.677037E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.329258E+10 | 5597.98 | 30-MAY-15:00 | 30.60 | 21.44 | 0.726668E+09 | 1123.97 | 06-MAY-14:39 | 30.60 | 21.44 |
June | 0.503439E+10 | 15375.39 | 15-JUN-07:02 | 22.20 | 18.87 | 0.714999E+09 | 1123.97 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.568388E+10 | 15365.79 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719335E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.620166E+10 | 14623.99 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740261E+09 | 1124.00 | 12-AUG-14:09 | 30.68 | 23.13 |
September | 0.434790E+10 | 15619.59 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704626E+09 | 1123.96 | 09-SEP-14:39 | 22.20 | 20.70 |
October | 0.273874E+10 | 9526.29 | 19-OCT-07:03 | 19.40 | 19.12 | 0.682965E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.141253E+10 | 3545.76 | 05-NOV-15:00 | 23.90 | 18.46 | 0.617217E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.643266E+09 | 3129.32 | 14-DEC-09:03 | 6.20 | 4.89 | 0.563744E+09 | 997.45 | 12-DEC-17:19 | 6.20 | 4.89 |
Annual Sum or Average | 0.334479E+11 | 0.788050E+10 | ||||||||
Minimum of Months | 0.161656E+09 | 3129.32 | -0.7 | -4.8 | 0.530694E+09 | 923.91 | 6.20 | 4.89 | ||
Maximum of Months | 0.620166E+10 | 15619.59 | 30.60 | 22.24 | 0.740261E+09 | 1124.00 | 32.40 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87399366.51 | 1918.14 | 24-JAN-11:35 | 10.20 | 5.16 | 0.547402E+09 | 906.89 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.357547E+09 | 2375.23 | 28-FEB-15:30 | 24.15 | 13.12 | 0.527281E+09 | 1123.86 | 25-FEB-15:00 | 24.15 | 13.12 |
March | 0.102276E+10 | 4412.23 | 30-MAR-15:00 | 27.80 | 17.08 | 0.646148E+09 | 1123.87 | 04-MAR-15:50 | 27.80 | 17.08 |
April | 0.179845E+10 | 4804.94 | 17-APR-14:30 | 28.90 | 16.52 | 0.670541E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.52 |
May | 0.333024E+10 | 6048.57 | 30-MAY-14:30 | 30.60 | 21.24 | 0.725328E+09 | 1123.98 | 06-MAY-14:09 | 30.60 | 21.24 |
June | 0.559717E+10 | 14345.26 | 14-JUN-07:02 | 22.30 | 20.01 | 0.715021E+09 | 1123.97 | 17-JUN-14:00 | 26.10 | 20.69 |
July | 0.646993E+10 | 15813.86 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719414E+09 | 1123.93 | 01-JUL-14:09 | 21.97 | 20.23 |
August | 0.709802E+10 | 15006.58 | 10-AUG-07:02 | 25.37 | 23.14 | 0.740366E+09 | 1124.00 | 05-AUG-14:39 | 25.37 | 23.14 |
September | 0.480571E+10 | 14819.40 | 27-SEP-07:02 | 21.70 | 20.20 | 0.704321E+09 | 1123.98 | 09-SEP-14:00 | 21.70 | 20.20 |
October | 0.272360E+10 | 6716.27 | 19-OCT-07:03 | 19.40 | 19.12 | 0.678800E+09 | 1123.91 | 14-OCT-14:20 | 19.40 | 19.12 |
November | 0.116724E+10 | 3531.77 | 05-NOV-15:00 | 23.90 | 18.46 | 0.612325E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.379141E+09 | 2280.89 | 19-DEC-19:45 | 8.48 | 3.27 | 0.561289E+09 | 997.44 | 12-DEC-17:10 | 8.48 | 3.27 |
Annual Sum or Average | 0.348372E+11 | 0.784824E+10 | ||||||||
Minimum of Months | 87399366.51 | 1918.14 | 8.48 | 3.27 | 0.527281E+09 | 906.89 | 8.48 | 3.27 | ||
Maximum of Months | 0.709802E+10 | 15813.86 | 30.60 | 23.14 | 0.740366E+09 | 1124.00 | 30.60 | 23.14 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304223E+10 | 58750.74 | 28-JAN-08:61 | -4.0 |
February | 0.187771E+10 | 58757.25 | 12-FEB-08:61 | -11.9 |
March | 0.253314E+09 | 58705.67 | 20-MAR-07:01 | 5.10 |
April | 0.120051E+09 | 58723.94 | 07-APR-07:01 | 3.53 |
May | 35065118.41 | 1144.72 | 31-MAY-07:07 | 19.50 |
June | 29974435.66 | 1708.63 | 28-JUN-07:05 | 23.17 |
July | 27781194.07 | 1723.53 | 20-JUL-07:05 | 22.07 |
August | 25569438.74 | 1676.89 | 26-AUG-07:05 | 22.30 |
September | 27079834.19 | 1767.47 | 09-SEP-07:05 | 22.67 |
October | 72969875.52 | 30318.03 | 26-OCT-07:01 | 2.57 |
November | 0.178445E+09 | 58697.99 | 22-NOV-08:61 | -2.2 |
December | 0.910783E+09 | 58737.81 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.660098E+10 | |||
Minimum of Months | 25569438.74 | 1144.72 | -11.9 | |
Maximum of Months | 0.304223E+10 | 58757.25 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.811175E+09 | 30748.41 | 28-JAN-08:61 | -4.0 |
February | 0.468558E+09 | 30754.76 | 12-FEB-08:61 | -11.9 |
March | 51198829.55 | 18329.39 | 23-MAR-07:01 | 6.20 |
April | 31688768.52 | 600.93 | 06-APR-08:10 | 5.37 |
May | 15296841.74 | 786.66 | 31-MAY-07:07 | 19.50 |
June | 15047352.22 | 1021.70 | 12-JUN-07:05 | 22.07 |
July | 15284087.61 | 1019.08 | 20-JUL-07:05 | 22.07 |
August | 12398921.70 | 992.09 | 26-AUG-07:05 | 22.30 |
September | 15269656.87 | 1040.22 | 09-SEP-07:05 | 22.67 |
October | 29392282.92 | 959.95 | 19-OCT-07:05 | 19.40 |
November | 52293462.86 | 30719.58 | 22-NOV-08:61 | -2.2 |
December | 0.156674E+09 | 30736.90 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.167428E+10 | |||
Minimum of Months | 12398921.70 | 600.93 | -11.9 | |
Maximum of Months | 0.811175E+09 | 30754.76 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114424E+10 | 30831.84 | 15-JAN-08:61 | -4.2 |
February | 0.647836E+09 | 30847.88 | 12-FEB-08:61 | -11.9 |
March | 63672774.86 | 12969.43 | 19-MAR-07:02 | 1.57 |
April | 36402750.37 | 2896.50 | 07-APR-07:03 | 3.53 |
May | 37403801.61 | 1599.74 | 29-MAY-16:03 | 30.00 |
June | 88165295.55 | 2421.35 | 25-JUN-16:02 | 33.22 |
July | 0.111041E+09 | 2678.28 | 08-JUL-17:02 | 34.40 |
August | 97908402.85 | 2301.98 | 06-AUG-16:02 | 32.70 |
September | 42663106.60 | 1657.27 | 03-SEP-16:02 | 30.00 |
October | 31448290.61 | 2693.33 | 26-OCT-07:06 | 2.57 |
November | 64559303.15 | 23755.02 | 22-NOV-07:02 | -3.2 |
December | 0.309125E+09 | 30715.28 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.267447E+10 | |||
Minimum of Months | 31448290.61 | 1599.74 | -11.9 | |
Maximum of Months | 0.114424E+10 | 30847.88 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128317E+10 | 30908.13 | 15-JAN-08:61 | -4.2 |
February | 0.720653E+09 | 30924.40 | 12-FEB-08:61 | -11.9 |
March | 75901889.69 | 17156.59 | 19-MAR-07:02 | 1.57 |
April | 39004712.51 | 2755.88 | 06-APR-07:03 | 2.25 |
May | 38616701.93 | 1602.98 | 29-MAY-16:03 | 30.00 |
June | 88031184.63 | 2421.50 | 25-JUN-16:02 | 33.22 |
July | 0.110756E+09 | 2677.88 | 08-JUL-17:02 | 34.40 |
August | 97342696.69 | 2302.29 | 06-AUG-16:02 | 32.70 |
September | 42757207.42 | 1659.18 | 03-SEP-16:02 | 30.00 |
October | 33111301.05 | 1054.03 | 09-OCT-16:03 | 27.62 |
November | 73607522.95 | 26217.66 | 22-NOV-07:02 | -3.2 |
December | 0.383078E+09 | 30790.93 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.298603E+10 | |||
Minimum of Months | 33111301.05 | 1054.03 | -11.9 | |
Maximum of Months | 0.128317E+10 | 30924.40 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150934E+10 | 30698.90 | 15-JAN-08:61 | -4.2 |
February | 0.849770E+09 | 30714.94 | 12-FEB-08:61 | -11.9 |
March | 97201103.79 | 21497.91 | 19-MAR-07:02 | 1.57 |
April | 46318412.60 | 3613.59 | 07-APR-06:05 | 2.80 |
May | 40488613.54 | 1610.33 | 29-MAY-16:03 | 30.00 |
June | 89296282.91 | 2425.03 | 25-JUN-16:02 | 33.22 |
July | 0.111675E+09 | 2682.69 | 08-JUL-17:02 | 34.40 |
August | 99339194.43 | 2305.56 | 06-AUG-16:02 | 32.70 |
September | 42998355.27 | 1663.91 | 03-SEP-16:02 | 30.00 |
October | 35415088.00 | 1777.09 | 26-OCT-07:04 | 2.57 |
November | 86438670.83 | 29052.47 | 22-NOV-07:02 | -3.2 |
December | 0.487625E+09 | 30583.56 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.349591E+10 | |||
Minimum of Months | 35415088.00 | 1610.33 | -11.9 | |
Maximum of Months | 0.150934E+10 | 30714.94 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320463E+10 | 55697.20 | 28-JAN-08:61 | -4.0 |
February | 0.182691E+10 | 55710.02 | 13-FEB-08:61 | -5.2 |
March | 0.254349E+09 | 55659.92 | 20-MAR-07:01 | 5.10 |
April | 0.109441E+09 | 55666.40 | 07-APR-07:01 | 3.53 |
May | 61118989.10 | 3242.43 | 29-MAY-16:03 | 30.00 |
June | 96322740.54 | 4845.71 | 25-JUN-16:02 | 33.22 |
July | 0.115264E+09 | 5375.64 | 08-JUL-17:02 | 34.40 |
August | 84426638.95 | 4605.33 | 06-AUG-16:02 | 32.70 |
September | 59105154.74 | 3325.86 | 03-SEP-16:02 | 30.00 |
October | 84648282.07 | 27321.70 | 26-OCT-07:01 | 2.57 |
November | 0.180752E+09 | 55656.75 | 22-NOV-08:61 | -2.2 |
December | 0.108149E+10 | 55690.47 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.715846E+10 | |||
Minimum of Months | 59105154.74 | 3242.43 | -5.2 | |
Maximum of Months | 0.320463E+10 | 55710.02 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186854E+10 | 28676.02 | 28-JAN-08:61 | -4.0 |
February | 0.106498E+10 | 28683.98 | 13-FEB-08:61 | -5.2 |
March | 0.151094E+09 | 28654.83 | 20-MAR-07:01 | 5.10 |
April | 61995008.99 | 28658.64 | 07-APR-07:01 | 3.53 |
May | 33469709.12 | 1631.93 | 29-MAY-16:03 | 30.00 |
June | 49906209.23 | 2434.47 | 25-JUN-16:02 | 33.22 |
July | 59233584.68 | 2702.10 | 08-JUL-17:02 | 34.40 |
August | 43210864.24 | 2314.39 | 06-AUG-16:02 | 32.70 |
September | 30873826.93 | 1675.39 | 03-SEP-16:02 | 30.00 |
October | 47291185.70 | 14798.07 | 26-OCT-07:01 | 2.57 |
November | 0.108415E+09 | 28654.40 | 22-NOV-08:61 | -2.2 |
December | 0.643445E+09 | 28672.30 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.416245E+10 | |||
Minimum of Months | 30873826.93 | 1631.93 | -5.2 | |
Maximum of Months | 0.186854E+10 | 28683.98 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193100E+10 | 28568.29 | 28-JAN-08:61 | -4.0 |
February | 0.111105E+10 | 28576.32 | 13-FEB-08:61 | -5.2 |
March | 0.168451E+09 | 28546.94 | 20-MAR-07:01 | 5.10 |
April | 65792596.69 | 28550.86 | 07-APR-07:01 | 3.53 |
May | 34620624.45 | 1634.25 | 29-MAY-16:03 | 30.00 |
June | 50159774.28 | 2435.17 | 25-JUN-16:02 | 33.22 |
July | 59494469.97 | 2703.09 | 08-JUL-17:02 | 34.40 |
August | 43343048.71 | 2315.06 | 06-AUG-16:02 | 32.70 |
September | 31127208.11 | 1676.20 | 03-SEP-16:02 | 30.00 |
October | 48391808.19 | 17185.56 | 26-OCT-07:01 | 2.57 |
November | 0.115341E+09 | 28546.88 | 22-NOV-08:61 | -2.2 |
December | 0.687244E+09 | 28564.52 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.434601E+10 | |||
Minimum of Months | 31127208.11 | 1634.25 | -5.2 | |
Maximum of Months | 0.193100E+10 | 28576.32 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225475E+10 | 28583.17 | 28-JAN-08:61 | -4.0 |
February | 0.131476E+10 | 28589.74 | 13-FEB-08:61 | -5.2 |
March | 0.227957E+09 | 28563.02 | 20-MAR-07:01 | 5.10 |
April | 82450068.46 | 28566.97 | 07-APR-07:01 | 3.53 |
May | 41292141.78 | 1641.75 | 29-MAY-16:03 | 30.00 |
June | 50790177.84 | 2436.30 | 25-JUN-16:02 | 33.22 |
July | 59357601.09 | 2702.55 | 08-JUL-17:02 | 34.40 |
August | 42658406.52 | 2315.12 | 06-AUG-16:02 | 32.70 |
September | 32274666.79 | 1678.84 | 03-SEP-16:02 | 30.00 |
October | 56706920.88 | 24856.78 | 26-OCT-07:01 | 2.57 |
November | 0.147691E+09 | 28561.11 | 22-NOV-08:61 | -2.2 |
December | 0.837493E+09 | 28579.94 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.514818E+10 | |||
Minimum of Months | 32274666.79 | 1641.75 | -5.2 | |
Maximum of Months | 0.225475E+10 | 28589.74 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380309E+10 | 31632.31 | 10-JAN-08:12 | -4.8 |
February | 0.238512E+10 | 31589.17 | 05-FEB-09:12 | -3.2 |
March | 0.543770E+09 | 31394.04 | 20-MAR-07:01 | 5.10 |
April | 0.179691E+09 | 31398.24 | 07-APR-07:01 | 3.53 |
May | 56987782.79 | 3143.08 | 11-MAY-07:03 | 10.28 |
June | 52753278.50 | 2429.67 | 25-JUN-16:02 | 33.22 |
July | 59793623.02 | 2674.58 | 08-JUL-17:02 | 34.40 |
August | 42177372.01 | 2299.74 | 06-AUG-16:02 | 32.70 |
September | 41174017.71 | 1681.34 | 03-SEP-16:02 | 30.00 |
October | 0.109389E+09 | 30912.70 | 26-OCT-07:01 | 2.57 |
November | 0.332834E+09 | 31385.02 | 22-NOV-08:61 | -2.2 |
December | 0.155176E+10 | 31413.26 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.915855E+10 | |||
Minimum of Months | 41174017.71 | 1681.34 | -5.0 | |
Maximum of Months | 0.380309E+10 | 31632.31 | 34.40 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457248E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234202.28 | 0.324207E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36077821.32 | 0.201573E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198148E+09 | 0.994726E+09 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469932E+09 | 0.483997E+09 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119478E+10 | 0.172814E+09 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139110E+10 | 0.154264E+09 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136685E+10 | 72148708.91 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551627E+09 | 0.307611E+09 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107571E+09 | 0.140067E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654805.39 | 0.218503E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340235E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532098E+10 | 0.190039E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72148708.91 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139110E+10 | 0.457248E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223799E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.155306E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19334488.32 | 0.985359E+09 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108511E+09 | 0.460921E+09 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256197E+09 | 0.196885E+09 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643980E+09 | 58030753.17 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753675E+09 | 61342259.72 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738992E+09 | 23520594.18 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300516E+09 | 0.129318E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58609909.61 | 0.659591E+09 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356330.17 | 0.104711E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164584E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288245E+10 | 0.905897E+10 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23520594.18 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753675E+09 | 0.223799E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228796E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.159228E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19306093.21 | 0.100401E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105952E+09 | 0.482299E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250364E+09 | 0.214538E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633116E+09 | 66296363.95 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738967E+09 | 67998764.27 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727398E+09 | 29021378.95 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291122E+09 | 0.141893E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55557543.70 | 0.682235E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.84 | 0.106875E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168053E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282441E+10 | 0.931782E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29021378.95 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738967E+09 | 0.228796E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227975E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.158170E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19306270.61 | 0.993104E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105958E+09 | 0.478920E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250375E+09 | 0.213984E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633011E+09 | 66638086.79 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738699E+09 | 68403674.47 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727187E+09 | 29564973.15 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291113E+09 | 0.141898E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55570340.62 | 0.677379E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.66 | 0.106001E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166969E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282385E+10 | 0.926104E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29564973.15 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738699E+09 | 0.227975E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227143E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.156849E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19307080.49 | 0.975965E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105987E+09 | 0.471221E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250492E+09 | 0.211488E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633328E+09 | 65030578.43 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739219E+09 | 67191944.84 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727597E+09 | 28210009.04 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291280E+09 | 0.140453E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55617430.69 | 0.669176E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.37 | 0.104795E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165789E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282545E+10 | 0.917449E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28210009.04 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739219E+09 | 0.227143E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417402E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4108878.01 | 0.288281E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34826915.30 | 0.177362E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190683E+09 | 0.865302E+09 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451251E+09 | 0.402845E+09 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114343E+10 | 0.129854E+09 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133461E+10 | 0.129617E+09 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131424E+10 | 55561759.64 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525163E+09 | 0.266488E+09 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100315E+09 | 0.123309E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617736.36 | 0.192089E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305853E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509925E+10 | 0.168926E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55561759.64 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133461E+10 | 0.417402E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227665E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.81 | 0.156210E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19328928.75 | 0.955458E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106145E+09 | 0.462206E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251074E+09 | 0.211939E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635362E+09 | 65557155.09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742093E+09 | 67603618.71 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730563E+09 | 27442095.96 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292216E+09 | 0.141272E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55807597.24 | 0.663765E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343471.78 | 0.103792E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165893E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283522E+10 | 0.913083E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27442095.96 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742093E+09 | 0.227665E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227439E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.93 | 0.155817E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19329289.81 | 0.949034E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106168E+09 | 0.458231E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251133E+09 | 0.210853E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635463E+09 | 65162627.60 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742235E+09 | 67315433.06 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730670E+09 | 27176625.16 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292266E+09 | 0.140920E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55829248.97 | 0.660600E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343471.82 | 0.103349E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165577E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283572E+10 | 0.910112E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27176625.16 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742235E+09 | 0.227439E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226530E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281999.54 | 0.154589E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19330015.00 | 0.931536E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106263E+09 | 0.446402E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251286E+09 | 0.206990E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635614E+09 | 63992992.53 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742361E+09 | 66555367.10 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730728E+09 | 26576717.66 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292344E+09 | 0.139831E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55874329.00 | 0.651977E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343473.22 | 0.102167E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164569E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283643E+10 | 0.901242E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26576717.66 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742361E+09 | 0.226530E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283959E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2407329.06 | 0.202477E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20566835.72 | 0.121112E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109614E+09 | 0.615111E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260501E+09 | 0.326986E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670830E+09 | 0.131435E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777846E+09 | 0.112627E+09 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766968E+09 | 58968455.18 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302718E+09 | 0.218538E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57860649.22 | 0.891659E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357243.13 | 0.135700E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215538E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296967E+10 | 0.119432E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58968455.18 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777846E+09 | 0.283959E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8886.97 | 07-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.89 | 28-FEB-15:00 | 9043.12 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.87 | 30-MAR-16:00 | 5360.18 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.80 | 12-APR-14:00 | 4287.32 | 05-APR-11:05 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.04 | 19-MAY-16:00 | 1880.38 | 10-MAY-11:10 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.53 | 06-JUN-15:00 | 781.61 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 08-JUL-15:00 | 1533.81 | 28-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3186.20 | 01-AUG-17:00 | 327.81 | 31-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.52 | 07-SEP-15:00 | 2035.79 | 28-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.24 | 10-OCT-16:00 | 3810.95 | 25-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 | 19-NOV-15:00 | 5549.45 | 20-NOV-12:10 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6436.76 | 17-DEC-17:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.81 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 9043.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2421.74 | 05-APR-11:05 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.28 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2168.48 | 25-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2996.47 | 20-NOV-12:05 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.03 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2415.69 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.15 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2142.74 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2977.38 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2403.47 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.32 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.15 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2126.50 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2368.09 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1073.34 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.32 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.17 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 10-OCT-16:00 | 2095.30 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8548.36 | 07-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.02 | 28-FEB-15:00 | 8665.12 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.13 | 30-MAR-16:00 | 5188.45 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.30 | 12-APR-14:00 | 4136.20 | 05-APR-11:05 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.18 | 19-MAY-16:00 | 1908.80 | 10-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.16 | 06-JUN-15:00 | 760.14 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 08-JUL-15:00 | 1487.64 | 28-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3102.80 | 01-AUG-17:00 | 319.23 | 31-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2166.53 | 07-SEP-15:00 | 1982.48 | 28-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.25 | 10-OCT-16:00 | 3683.23 | 25-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 | 19-NOV-15:00 | 5361.03 | 20-NOV-12:10 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6294.04 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.23 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 8665.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.95 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2288.40 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1050.85 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.19 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2044.64 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.95 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2270.58 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1041.92 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.19 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2043.02 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.94 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2240.33 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.35 | 19-MAY-16:00 | 1014.15 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.19 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.22 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2039.50 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5080.22 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.56 | 28-FEB-15:00 | 5181.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 655.64 | 30-MAR-16:00 | 3052.26 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.78 | 12-APR-14:00 | 2434.73 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.18 | 19-MAY-16:00 | 1052.50 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.44 | 06-JUN-15:00 | 474.02 | 07-JUN-07:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 08-JUL-15:00 | 872.25 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.51 | 01-AUG-17:00 | 197.21 | 25-AUG-05:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.32 | 07-SEP-15:00 | 1154.91 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.70 | 10-OCT-16:00 | 2168.30 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.41 | 19-NOV-15:00 | 3163.92 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3642.11 | 17-DEC-17:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.21 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 5181.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10574.19 | 27-JAN-00:02 | 1687.52 | 1338.85 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.88 |
February | 12098.31 | 11-FEB-20:32 | 10125.10 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.61 |
March | 10636.92 | 30-MAR-16:10 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.34 | 0.00 |
April | 10644.16 | 17-APR-16:20 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1345.13 | 0.00 |
May | 12316.31 | 19-MAY-17:00 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.64 | 0.00 |
June | 31661.54 | 15-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.34 |
July | 31921.90 | 17-JUL-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.41 |
August | 31187.91 | 27-AUG-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.89 |
September | 33463.18 | 16-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.73 |
October | 27047.31 | 19-OCT-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.45 |
November | 9643.31 | 05-NOV-16:07 | 12150.11 | 15263.85 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
December | 7944.37 | 01-DEC-00:03 | 1012.51 | 803.31 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7944.37 | 0.00 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33463.18 | 12150.11 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.64 | 585.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3157.03 | 21-JAN-09:05 | 337.49 | 75.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.15 |
February | 17202.22 | 28-FEB-22:23 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
March | 18865.99 | 12-MAR-17:07 | 14174.73 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.44 |
April | 16914.00 | 08-APR-20:17 | 6074.88 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
May | 15820.78 | 13-MAY-20:50 | 3037.44 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 |
June | 18466.70 | 15-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 |
July | 18764.99 | 17-JUL-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.28 |
August | 18458.10 | 14-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
September | 19192.88 | 16-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
October | 17314.10 | 11-OCT-20:08 | 6074.88 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 |
November | 12157.79 | 03-NOV-21:10 | 3037.44 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
December | 4033.22 | 17-DEC-17:53 | 6074.88 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3437.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3157.03 | 0.00 | 75.00 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | |
Maximum of Months | 19192.88 | 14174.73 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3437.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4900.17 | 27-JAN-10:23 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.93 |
February | 4713.49 | 01-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.83 |
March | 5586.87 | 30-MAR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5638.02 | 17-APR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 9760.79 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 16904.06 | 05-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
July | 17139.05 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
August | 18084.30 | 26-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 |
September | 17537.20 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
October | 14118.69 | 18-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
November | 4343.45 | 05-NOV-14:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
December | 4036.89 | 15-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4036.89 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18084.30 | 1687.47 | 11156.02 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 647.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5036.33 | 26-JAN-10:13 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.77 |
February | 4671.13 | 01-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.80 |
March | 5505.82 | 30-MAR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5613.71 | 17-APR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 9785.33 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 17420.27 | 05-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 |
July | 17223.59 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
August | 18156.01 | 26-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
September | 17584.70 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
October | 14123.55 | 18-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 |
November | 4241.39 | 05-NOV-14:00 | 1012.48 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
December | 3991.86 | 15-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3991.86 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18156.01 | 1687.47 | 11156.02 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 685.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3445.90 | 16-JAN-11:03 | 2024.96 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.46 |
February | 4924.99 | 03-FEB-20:33 | 674.99 | 5871.59 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 |
March | 5283.17 | 30-MAR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5449.53 | 17-APR-16:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 8429.34 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 16617.12 | 15-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
July | 16971.94 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
August | 17905.47 | 26-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
September | 17344.34 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
October | 13554.34 | 18-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
November | 4015.59 | 05-NOV-15:00 | 674.99 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3930.16 | 18-DEC-10:13 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3445.90 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17905.47 | 2024.96 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 474.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7398.18 | 25-JAN-20:43 | 2227.52 | 5039.40 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.08 |
February | 5609.26 | 28-FEB-15:30 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 0.00 |
March | 8967.35 | 30-MAR-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.79 | 0.00 |
April | 9596.92 | 17-APR-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.70 | 0.00 |
May | 11640.24 | 30-MAY-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 |
June | 30195.72 | 15-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.58 |
July | 30449.72 | 25-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.89 |
August | 28676.94 | 03-AUG-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
September | 31440.33 | 16-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
October | 23243.19 | 19-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.58 |
November | 7365.12 | 05-NOV-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
December | 6768.50 | 17-DEC-15:13 | 13972.63 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5142.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5609.26 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31440.33 | 13972.63 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.70 | 5142.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4551.21 | 26-JAN-19:03 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.91 |
February | 4403.14 | 02-FEB-10:53 | 1484.97 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.71 |
March | 4616.02 | 30-MAR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.27 | 0.00 |
April | 4989.91 | 17-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5767.38 | 30-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 0.00 |
June | 15530.05 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.41 |
July | 15493.60 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 |
August | 14744.95 | 03-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 |
September | 16173.60 | 16-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 |
October | 11100.50 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 |
November | 3788.42 | 05-NOV-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3989.28 | 02-DEC-10:43 | 1113.73 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3788.42 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16173.60 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 578.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4910.48 | 26-JAN-11:13 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.61 |
February | 4849.37 | 03-FEB-11:43 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.94 |
March | 4526.48 | 30-MAR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.27 | 0.00 |
April | 4910.29 | 17-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5706.12 | 30-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 0.00 |
June | 15437.64 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.69 |
July | 15408.06 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 |
August | 14658.47 | 03-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
September | 16083.38 | 16-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 |
October | 10699.40 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 |
November | 3714.57 | 05-NOV-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3925.79 | 02-DEC-18:13 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3714.57 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16083.38 | 5804.89 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 658.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3218.50 | 12-JAN-11:53 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.83 |
February | 4552.07 | 03-FEB-18:03 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.95 |
March | 4327.14 | 30-MAR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.26 | 0.00 |
April | 4721.09 | 17-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5597.98 | 30-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.11 | 0.00 |
June | 15375.39 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 |
July | 15365.79 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 |
August | 14623.99 | 03-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
September | 15619.59 | 16-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
October | 9526.29 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 |
November | 3545.76 | 05-NOV-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3129.32 | 14-DEC-09:03 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3129.32 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15619.59 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.11 | 579.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1918.14 | 24-JAN-11:35 | 2902.44 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.13 |
February | 2375.23 | 28-FEB-15:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
March | 4412.23 | 30-MAR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 651.55 | 0.00 |
April | 4804.94 | 17-APR-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 790.11 | 0.00 |
May | 6048.57 | 30-MAY-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.02 | 0.00 |
June | 14345.26 | 14-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 |
July | 15813.86 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.87 |
August | 15006.58 | 10-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 0.00 |
September | 14819.40 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 |
October | 6716.27 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.30 |
November | 3531.77 | 05-NOV-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 2280.89 | 19-DEC-19:45 | 1754.97 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1918.14 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15813.86 | 2902.44 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.02 | 349.70 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.665999E+11 | 56789.84 | 09-JAN-18:49 | 0.821091E+11 | 182387.17 | 09-JAN-08:09 |
February | 0.599971E+11 | 57644.25 | 26-FEB-16:10 | 0.465290E+11 | 203522.12 | 12-FEB-09:09 |
March | 0.676539E+11 | 69756.06 | 30-MAR-15:20 | 0.755451E+10 | 84507.00 | 19-MAR-08:09 |
April | 0.701334E+11 | 70344.36 | 17-APR-14:00 | 0.109128E+10 | 60803.64 | 07-APR-07:10 |
May | 0.821585E+11 | 77789.02 | 31-MAY-14:09 | 2490318.71 | 1187.99 | 11-MAY-07:10 |
June | 0.952025E+11 | 87925.80 | 27-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.103101E+12 | 99289.72 | 08-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.108365E+12 | 94298.41 | 19-AUG-13:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.877673E+11 | 90039.48 | 06-SEP-13:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.735803E+11 | 77287.63 | 10-OCT-13:50 | 0.115448E+10 | 47512.30 | 26-OCT-08:09 |
November | 0.644263E+11 | 64697.92 | 05-NOV-14:39 | 0.828830E+10 | 102180.25 | 22-NOV-08:09 |
December | 0.658058E+11 | 55952.13 | 12-DEC-13:50 | 0.357909E+11 | 136498.75 | 18-DEC-08:09 |
Annual Sum or Average | 0.944791E+12 | 0.182520E+12 | ||||
Minimum of Months | 0.599971E+11 | 55952.13 | 0.00 | 0.00 | ||
Maximum of Months | 0.108365E+12 | 99289.72 | 0.821091E+11 | 203522.12 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.631741E+10 | 0.108325E+11 | 0.00 | 0.942152E+10 | 0.00 | 0.00 | 543782.38 | 0.00 | 0.00 | 0.00 | 0.549985E+10 | 0.00 |
February | 0.312534E+11 | 0.527990E+10 | 0.980803E+10 | 0.00 | 0.806067E+10 | 0.00 | 0.00 | 0.627919E+09 | 0.00 | 0.00 | 0.00 | 0.496714E+10 | 0.00 |
March | 0.350527E+11 | 0.522701E+10 | 0.110075E+11 | 0.00 | 0.826531E+10 | 0.00 | 0.00 | 0.264633E+10 | 0.00 | 0.00 | 0.00 | 0.545507E+10 | 0.00 |
April | 0.334898E+11 | 0.444061E+10 | 0.105079E+11 | 0.00 | 0.777872E+10 | 0.00 | 0.00 | 0.876907E+10 | 0.00 | 0.00 | 0.00 | 0.514730E+10 | 0.00 |
May | 0.347840E+11 | 0.405070E+10 | 0.109147E+11 | 0.00 | 0.805545E+10 | 0.00 | 0.00 | 0.191452E+11 | 0.00 | 0.00 | 0.00 | 0.520845E+10 | 0.00 |
June | 0.338757E+11 | 0.368394E+10 | 0.106386E+11 | 0.00 | 0.796288E+10 | 0.00 | 0.00 | 0.340868E+11 | 0.00 | 0.00 | 0.00 | 0.495476E+10 | 0.00 |
July | 0.344108E+11 | 0.389540E+10 | 0.107945E+11 | 0.00 | 0.838998E+10 | 0.00 | 0.00 | 0.405845E+11 | 0.00 | 0.00 | 0.00 | 0.502550E+10 | 0.00 |
August | 0.350409E+11 | 0.434478E+10 | 0.110006E+11 | 0.00 | 0.866244E+10 | 0.00 | 0.00 | 0.442567E+11 | 0.00 | 0.00 | 0.00 | 0.505967E+10 | 0.00 |
September | 0.335014E+11 | 0.479086E+10 | 0.105148E+11 | 0.00 | 0.783453E+10 | 0.00 | 0.00 | 0.262016E+11 | 0.00 | 0.00 | 0.00 | 0.492414E+10 | 0.00 |
October | 0.345281E+11 | 0.559047E+10 | 0.108325E+11 | 0.00 | 0.804822E+10 | 0.00 | 0.00 | 0.939448E+10 | 0.00 | 0.00 | 0.00 | 0.518660E+10 | 0.00 |
November | 0.334535E+11 | 0.597047E+10 | 0.104978E+11 | 0.00 | 0.791110E+10 | 0.00 | 0.00 | 0.145517E+10 | 0.00 | 0.00 | 0.00 | 0.513817E+10 | 0.00 |
December | 0.344233E+11 | 0.646940E+10 | 0.108050E+11 | 0.00 | 0.854983E+10 | 0.00 | 0.00 | 0.125336E+09 | 0.00 | 0.00 | 0.00 | 0.543292E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.600610E+11 | 0.128154E+12 | 0.00 | 0.989406E+11 | 0.00 | 0.00 | 0.187293E+12 | 0.00 | 0.00 | 0.00 | 0.619996E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.368394E+10 | 0.980803E+10 | 0.00 | 0.777872E+10 | 0.00 | 0.00 | 543782.38 | 0.00 | 0.00 | 0.00 | 0.492414E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.646940E+10 | 0.110075E+11 | 0.00 | 0.942152E+10 | 0.00 | 0.00 | 0.442567E+11 | 0.00 | 0.00 | 0.00 | 0.549985E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.821091E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.465290E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.755451E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109128E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2490318.71 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115448E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.828830E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.357909E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182520E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.821091E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8836.10 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9229.12 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7029.71 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6591.39 | 07-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 5485.23 | 11-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7059.60 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8207.82 | 08-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 7672.17 | 19-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6883.32 | 06-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6497.61 | 19-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7357.32 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7992.62 | 18-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 5485.23 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 9229.12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 188.21 | 31-JAN-23:10 | 0.00 | 0.00 | 0.00 | 11839.76 | 09-JAN-14:09 | 0.00 |
February | 12745.91 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 9694.79 | 09-FEB-12:09 | 0.00 |
March | 23443.11 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9714.08 | 06-MAR-13:50 | 0.00 |
April | 23080.39 | 17-APR-16:10 | 0.00 | 0.00 | 0.00 | 9679.75 | 12-APR-11:20 | 0.00 |
May | 32625.05 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7570.67 | 02-MAY-13:30 | 0.00 |
June | 42173.24 | 23-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7611.42 | 09-JUN-12:00 | 0.00 |
July | 51724.53 | 08-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9672.19 | 06-JUL-12:50 | 0.00 |
August | 47742.44 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 9671.21 | 26-AUG-12:09 | 0.00 |
September | 42152.82 | 07-SEP-16:10 | 0.00 | 0.00 | 0.00 | 9870.69 | 29-SEP-11:00 | 0.00 |
October | 32442.15 | 10-OCT-16:10 | 0.00 | 0.00 | 0.00 | 11795.72 | 04-OCT-13:00 | 0.00 |
November | 19738.44 | 05-NOV-14:00 | 0.00 | 0.00 | 0.00 | 9669.55 | 28-NOV-13:30 | 0.00 |
December | 9618.64 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 10609.62 | 12-DEC-10:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 188.21 | 0.00 | 0.00 | 0.00 | 7570.67 | 0.00 | ||
Maximum of Months | 51724.53 | 0.00 | 0.00 | 0.00 | 11839.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56789.84 | 09-JAN-18:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6736.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57644.25 | 26-FEB-16:10 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 10325.13 | 0.00 |
March | 69756.06 | 30-MAR-15:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 22422.00 | 0.00 |
April | 70344.36 | 17-APR-14:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 23004.98 | 0.00 |
May | 77789.02 | 31-MAY-14:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 30841.48 | 0.00 |
June | 87925.80 | 27-JUN-13:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6375.71 | 0.00 | 0.00 | 40936.23 | 0.00 |
July | 99289.72 | 08-JUL-14:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8087.25 | 0.00 | 0.00 | 51452.32 | 0.00 |
August | 94298.41 | 19-AUG-13:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7539.72 | 0.00 | 0.00 | 46999.07 | 0.00 |
September | 90039.48 | 06-SEP-13:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6642.27 | 0.00 | 0.00 | 41519.94 | 0.00 |
October | 77287.63 | 10-OCT-13:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 32057.87 | 0.00 |
November | 64697.92 | 05-NOV-14:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 19493.25 | 0.00 |
December | 55952.13 | 12-DEC-13:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 8585.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 55952.13 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5462.59 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99289.72 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8087.25 | 0.00 | 0.00 | 51452.32 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 182387.17 | 09-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 203522.12 | 12-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 84507.00 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 60803.64 | 07-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1187.99 | 11-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 47512.30 | 26-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 102180.25 | 22-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 136498.75 | 18-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 203522.12 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.17 | 20.43 | 0.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 3.17 | 20.46 | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 0.50 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 1.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 3.83 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 10.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.24 | 229.50 | 21.19 | 229.50 | 21.16 |
February | 430.17 | 21.76 | 146.33 | 21.58 | 146.33 | 21.47 |
March | 363.17 | 22.32 | 65.83 | 22.49 | 11.00 | 22.45 |
April | 209.17 | 22.89 | 176.67 | 23.31 | 25.00 | 23.32 |
May | 101.00 | 23.68 | 374.00 | 23.84 | 71.83 | 23.84 |
June | 45.00 | 23.87 | 421.83 | 23.89 | 38.33 | 23.89 |
July | 93.00 | 23.89 | 494.00 | 23.89 | 93.00 | 23.89 |
August | 101.00 | 23.89 | 496.83 | 23.89 | 101.00 | 23.89 |
September | 73.33 | 23.86 | 454.50 | 23.88 | 69.17 | 23.89 |
October | 209.17 | 22.78 | 198.17 | 23.31 | 46.00 | 23.37 |
November | 350.00 | 22.34 | 91.83 | 22.60 | 25.00 | 22.61 |
December | 467.50 | 21.32 | 92.83 | 21.36 | 80.33 | 21.34 |
Annual Sum or Average | 2938.50 | 22.19 | 3242.33 | 22.86 | 936.50 | 22.80 |
Minimum of Months | 45.00 | 21.24 | 65.83 | 21.19 | 11.00 | 21.16 |
Maximum of Months | 496.00 | 23.89 | 496.83 | 23.89 | 229.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.00 | 21.67 | 87.83 | 21.62 | 87.83 | 21.58 |
February | 392.00 | 22.12 | 50.67 | 22.03 | 45.83 | 21.95 |
March | 334.33 | 22.91 | 67.33 | 23.07 | 0.67 | 23.07 |
April | 145.83 | 23.20 | 172.17 | 23.57 | 4.00 | 23.58 |
May | 43.33 | 23.70 | 348.83 | 23.87 | 19.67 | 23.87 |
June | 15.17 | 23.65 | 410.17 | 23.88 | 7.17 | 23.88 |
July | 50.67 | 23.89 | 490.00 | 23.89 | 50.67 | 23.89 |
August | 42.50 | 23.89 | 495.00 | 23.89 | 42.50 | 23.89 |
September | 35.83 | 23.86 | 435.83 | 23.89 | 34.33 | 23.89 |
October | 152.50 | 23.13 | 192.50 | 23.55 | 30.00 | 23.58 |
November | 296.00 | 22.81 | 91.00 | 23.05 | 7.33 | 23.05 |
December | 462.17 | 22.02 | 43.00 | 22.10 | 20.83 | 22.10 |
Annual Sum or Average | 2461.33 | 22.46 | 2884.33 | 23.15 | 350.83 | 23.13 |
Minimum of Months | 15.17 | 21.67 | 43.00 | 21.62 | 0.67 | 21.58 |
Maximum of Months | 491.00 | 23.89 | 495.00 | 23.89 | 87.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.31 | 117.17 | 21.27 | 117.17 | 21.24 |
February | 313.83 | 21.83 | 66.50 | 21.70 | 66.50 | 21.61 |
March | 259.50 | 22.41 | 65.50 | 22.70 | 3.67 | 22.68 |
April | 124.83 | 22.93 | 142.17 | 23.53 | 9.17 | 23.54 |
May | 61.67 | 23.79 | 293.83 | 24.00 | 45.83 | 24.00 |
June | 28.33 | 24.66 | 327.67 | 24.14 | 24.33 | 24.19 |
July | 84.50 | 24.45 | 369.00 | 24.16 | 84.50 | 24.21 |
August | 98.00 | 24.48 | 378.83 | 24.18 | 98.00 | 24.23 |
September | 60.50 | 24.21 | 347.17 | 24.07 | 57.67 | 24.09 |
October | 154.33 | 22.89 | 149.17 | 23.45 | 35.67 | 23.51 |
November | 245.67 | 22.38 | 62.83 | 22.67 | 12.83 | 22.69 |
December | 346.50 | 21.44 | 46.50 | 21.54 | 34.17 | 21.55 |
Annual Sum or Average | 2148.67 | 22.33 | 2366.33 | 23.10 | 589.50 | 23.10 |
Minimum of Months | 28.33 | 21.31 | 46.50 | 21.27 | 3.67 | 21.24 |
Maximum of Months | 371.00 | 24.66 | 378.83 | 24.18 | 117.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.29 | 129.33 | 21.25 | 129.33 | 21.22 |
February | 319.67 | 21.81 | 71.17 | 21.68 | 71.17 | 21.59 |
March | 268.17 | 22.38 | 63.67 | 22.65 | 4.50 | 22.63 |
April | 130.33 | 22.92 | 137.33 | 23.50 | 9.83 | 23.51 |
May | 63.00 | 23.78 | 291.83 | 23.99 | 46.50 | 24.00 |
June | 27.00 | 24.70 | 327.50 | 24.15 | 23.33 | 24.19 |
July | 83.67 | 24.47 | 369.00 | 24.17 | 83.67 | 24.21 |
August | 94.83 | 24.51 | 378.83 | 24.18 | 94.83 | 24.24 |
September | 60.17 | 24.21 | 347.33 | 24.07 | 57.33 | 24.09 |
October | 157.17 | 22.84 | 147.17 | 23.42 | 36.17 | 23.47 |
November | 255.83 | 22.36 | 60.17 | 22.63 | 14.33 | 22.65 |
December | 347.67 | 21.41 | 48.67 | 21.48 | 39.50 | 21.49 |
Annual Sum or Average | 2178.50 | 22.31 | 2372.00 | 23.07 | 610.50 | 23.07 |
Minimum of Months | 27.00 | 21.29 | 48.67 | 21.25 | 4.50 | 21.22 |
Maximum of Months | 371.00 | 24.70 | 378.83 | 24.18 | 129.33 | 24.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.26 | 144.00 | 21.23 | 144.00 | 21.20 |
February | 326.67 | 21.78 | 78.17 | 21.65 | 78.17 | 21.56 |
March | 278.17 | 22.30 | 58.50 | 22.54 | 5.83 | 22.52 |
April | 145.67 | 22.88 | 124.67 | 23.41 | 12.33 | 23.42 |
May | 68.67 | 23.73 | 288.33 | 23.98 | 48.83 | 23.98 |
June | 34.00 | 24.51 | 326.33 | 24.14 | 29.67 | 24.17 |
July | 90.50 | 24.40 | 369.00 | 24.15 | 90.50 | 24.19 |
August | 105.00 | 24.42 | 378.83 | 24.17 | 105.00 | 24.21 |
September | 66.83 | 24.18 | 345.67 | 24.06 | 63.67 | 24.08 |
October | 165.67 | 22.77 | 143.50 | 23.35 | 38.17 | 23.41 |
November | 268.33 | 22.32 | 53.17 | 22.54 | 15.83 | 22.56 |
December | 349.17 | 21.37 | 54.33 | 21.42 | 48.17 | 21.42 |
Annual Sum or Average | 2269.67 | 22.30 | 2364.50 | 23.02 | 680.17 | 23.02 |
Minimum of Months | 34.00 | 21.26 | 53.17 | 21.23 | 5.83 | 21.20 |
Maximum of Months | 371.00 | 24.51 | 378.83 | 24.17 | 144.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.23 | 196.50 | 21.19 | 196.50 | 21.17 |
February | 306.17 | 21.75 | 105.33 | 21.58 | 105.33 | 21.49 |
March | 269.33 | 22.22 | 33.33 | 22.33 | 7.83 | 22.30 |
April | 158.33 | 22.95 | 89.67 | 23.30 | 17.00 | 23.32 |
May | 77.00 | 23.73 | 254.67 | 23.89 | 57.33 | 23.89 |
June | 50.83 | 24.11 | 295.50 | 23.98 | 47.00 | 24.00 |
July | 102.50 | 24.14 | 338.00 | 24.02 | 102.50 | 24.04 |
August | 119.83 | 24.04 | 347.83 | 23.98 | 119.83 | 23.99 |
September | 89.50 | 24.03 | 309.17 | 23.97 | 87.00 | 23.98 |
October | 159.83 | 22.68 | 127.33 | 23.24 | 37.50 | 23.30 |
November | 275.33 | 22.35 | 41.00 | 22.50 | 18.83 | 22.53 |
December | 329.17 | 21.37 | 69.50 | 21.39 | 69.33 | 21.39 |
Annual Sum or Average | 2277.83 | 22.33 | 2207.83 | 22.89 | 866.00 | 22.87 |
Minimum of Months | 50.83 | 21.23 | 33.33 | 21.19 | 7.83 | 21.17 |
Maximum of Months | 340.00 | 24.14 | 347.83 | 24.02 | 196.50 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.22 | 197.00 | 21.19 | 197.00 | 21.17 |
February | 307.50 | 21.74 | 106.17 | 21.58 | 106.17 | 21.48 |
March | 277.50 | 22.24 | 28.33 | 22.31 | 9.17 | 22.27 |
April | 170.67 | 22.99 | 75.50 | 23.27 | 18.33 | 23.29 |
May | 81.67 | 23.72 | 246.67 | 23.88 | 57.67 | 23.88 |
June | 51.67 | 24.07 | 291.17 | 23.98 | 46.83 | 23.99 |
July | 103.67 | 24.13 | 338.00 | 24.01 | 103.67 | 24.03 |
August | 122.00 | 24.03 | 347.67 | 23.97 | 122.00 | 23.99 |
September | 90.17 | 24.02 | 296.67 | 23.97 | 87.00 | 23.98 |
October | 163.17 | 22.69 | 120.67 | 23.22 | 37.50 | 23.29 |
November | 281.17 | 22.37 | 39.67 | 22.50 | 19.83 | 22.53 |
December | 329.67 | 21.37 | 74.33 | 21.38 | 74.33 | 21.38 |
Annual Sum or Average | 2318.83 | 22.34 | 2161.83 | 22.88 | 879.50 | 22.85 |
Minimum of Months | 51.67 | 21.22 | 28.33 | 21.19 | 9.17 | 21.17 |
Maximum of Months | 340.00 | 24.13 | 347.67 | 24.01 | 197.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.22 | 204.00 | 21.18 | 204.00 | 21.16 |
February | 308.00 | 21.72 | 109.67 | 21.56 | 109.67 | 21.47 |
March | 283.67 | 22.23 | 27.83 | 22.29 | 10.17 | 22.25 |
April | 178.00 | 22.97 | 71.00 | 23.24 | 20.17 | 23.26 |
May | 84.83 | 23.71 | 244.17 | 23.88 | 58.67 | 23.87 |
June | 54.00 | 24.06 | 289.83 | 23.98 | 48.67 | 23.99 |
July | 107.17 | 24.12 | 338.00 | 24.01 | 107.17 | 24.03 |
August | 126.17 | 24.03 | 347.67 | 23.97 | 126.17 | 23.99 |
September | 92.50 | 24.01 | 295.83 | 23.97 | 88.67 | 23.98 |
October | 165.83 | 22.67 | 119.83 | 23.20 | 37.83 | 23.27 |
November | 284.17 | 22.35 | 38.67 | 22.48 | 20.50 | 22.50 |
December | 330.00 | 21.36 | 80.00 | 21.37 | 80.00 | 21.37 |
Annual Sum or Average | 2354.33 | 22.34 | 2166.50 | 22.86 | 911.67 | 22.84 |
Minimum of Months | 54.00 | 21.22 | 27.83 | 21.18 | 10.17 | 21.16 |
Maximum of Months | 340.00 | 24.12 | 347.67 | 24.01 | 204.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.20 | 227.17 | 21.17 | 227.17 | 21.15 |
February | 308.00 | 21.68 | 122.50 | 21.51 | 122.50 | 21.42 |
March | 292.00 | 22.17 | 28.83 | 22.19 | 15.17 | 22.14 |
April | 193.83 | 22.91 | 65.17 | 23.14 | 24.50 | 23.17 |
May | 93.33 | 23.65 | 239.83 | 23.85 | 61.33 | 23.85 |
June | 59.50 | 24.04 | 289.33 | 23.97 | 53.33 | 23.99 |
July | 109.00 | 24.11 | 338.00 | 24.01 | 109.00 | 24.03 |
August | 128.67 | 24.03 | 347.67 | 23.97 | 128.67 | 23.99 |
September | 96.83 | 24.00 | 294.83 | 23.96 | 91.33 | 23.98 |
October | 173.83 | 22.62 | 117.83 | 23.14 | 38.50 | 23.21 |
November | 290.67 | 22.30 | 37.17 | 22.40 | 24.00 | 22.43 |
December | 330.67 | 21.34 | 97.33 | 21.34 | 97.33 | 21.34 |
Annual Sum or Average | 2416.33 | 22.33 | 2205.67 | 22.81 | 992.83 | 22.78 |
Minimum of Months | 59.50 | 21.20 | 28.83 | 21.17 | 15.17 | 21.15 |
Maximum of Months | 340.00 | 24.11 | 347.67 | 24.01 | 227.17 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.18 | 269.00 | 21.15 | 269.00 | 21.14 |
February | 308.00 | 21.61 | 155.33 | 21.45 | 155.33 | 21.36 |
March | 304.67 | 22.08 | 43.67 | 22.02 | 36.67 | 21.94 |
April | 219.83 | 22.80 | 55.00 | 22.96 | 37.83 | 23.01 |
May | 105.50 | 23.51 | 234.00 | 23.78 | 63.00 | 23.77 |
June | 61.00 | 24.06 | 295.17 | 23.98 | 55.33 | 24.00 |
July | 98.67 | 24.16 | 338.00 | 24.02 | 98.67 | 24.05 |
August | 120.00 | 24.07 | 347.83 | 23.99 | 120.00 | 24.00 |
September | 91.83 | 23.98 | 302.67 | 23.96 | 83.50 | 23.97 |
October | 179.00 | 22.49 | 120.17 | 23.04 | 39.50 | 23.11 |
November | 296.00 | 22.22 | 48.50 | 22.28 | 36.67 | 22.27 |
December | 336.00 | 21.34 | 162.17 | 21.31 | 162.17 | 21.29 |
Annual Sum or Average | 2460.50 | 22.27 | 2371.50 | 22.71 | 1157.67 | 22.65 |
Minimum of Months | 61.00 | 21.18 | 43.67 | 21.15 | 36.67 | 21.14 |
Maximum of Months | 340.00 | 24.16 | 347.83 | 24.02 | 269.00 | 24.05 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.24314 | 24.90732 | -0.4904 | 11.05412 |
February | 448.00000 | 21.84513 | 27.94930 | -0.3020 | 9.32060 |
March | 497.00000 | 22.73870 | 33.66708 | 0.01316 | 7.09036 |
April | 479.00000 | 23.44672 | 42.30182 | 0.26495 | 7.86101 |
May | 496.00000 | 23.84354 | 50.60564 | -0.4285 | 9.31673 |
June | 481.00000 | 23.88670 | 52.64371 | -0.3245 | 7.44694 |
July | 495.00000 | 23.88839 | 58.93658 | -0.2521 | 6.42218 |
August | 497.00000 | 23.89052 | 59.14902 | -0.2317 | 6.21129 |
September | 479.00000 | 23.88251 | 54.87437 | -0.3248 | 7.39570 |
October | 496.00000 | 23.41656 | 45.67645 | 0.31747 | 8.39177 |
November | 480.00000 | 22.75882 | 34.51416 | 0.04269 | 7.34821 |
December | 496.00000 | 21.46250 | 30.05948 | -0.3431 | 9.01585 |
Annual Sum or Average | 5840.00000 | 23.02972 | 43.02736 | -0.1715 | 8.06862 |
Minimum of Months | 448.00000 | 21.24314 | 24.90732 | -0.4904 | 6.21129 |
Maximum of Months | 497.00000 | 23.89052 | 59.14902 | 0.31747 | 11.05412 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.69326 | 26.85170 | -0.3428 | 8.70957 |
February | 448.00000 | 22.33650 | 28.60122 | -0.1550 | 7.86129 |
March | 497.00000 | 23.22738 | 32.91934 | 0.13562 | 6.74478 |
April | 479.00000 | 23.66190 | 40.44079 | 0.32095 | 7.86800 |
May | 496.00000 | 23.86542 | 47.49773 | -0.4276 | 9.12882 |
June | 481.00000 | 23.87372 | 50.22487 | -0.3498 | 7.80988 |
July | 495.00000 | 23.88763 | 55.85360 | -0.2858 | 6.82757 |
August | 497.00000 | 23.89067 | 56.28143 | -0.2696 | 6.63520 |
September | 479.00000 | 23.87705 | 52.10698 | -0.3496 | 7.73887 |
October | 496.00000 | 23.64293 | 44.09719 | 0.36312 | 8.40839 |
November | 480.00000 | 23.21328 | 33.75995 | 0.14885 | 7.06268 |
December | 496.00000 | 22.14900 | 31.40981 | -0.1684 | 7.20992 |
Annual Sum or Average | 5840.00000 | 23.28005 | 41.74927 | -0.1153 | 7.66579 |
Minimum of Months | 448.00000 | 21.69326 | 26.85170 | -0.4276 | 6.63520 |
Maximum of Months | 497.00000 | 23.89067 | 56.28143 | 0.36312 | 9.12882 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.30715 | 24.63000 | -0.4406 | 9.97269 |
February | 336.00000 | 21.96495 | 27.03578 | -0.2470 | 8.50726 |
March | 379.00000 | 22.89624 | 33.48685 | 0.06958 | 7.04890 |
April | 360.00000 | 23.62101 | 40.52873 | 0.30894 | 8.14182 |
May | 375.00000 | 23.97513 | 49.99728 | -0.3849 | 8.66098 |
June | 366.00000 | 24.07520 | 52.37267 | -0.2808 | 7.26479 |
July | 369.00000 | 24.09706 | 58.89592 | -0.2073 | 6.46419 |
August | 379.00000 | 24.09840 | 59.08973 | -0.1919 | 6.33325 |
September | 360.00000 | 24.03056 | 54.47849 | -0.2931 | 7.23689 |
October | 371.00000 | 23.52530 | 44.56115 | 0.33954 | 8.63035 |
November | 360.00000 | 22.86961 | 33.18234 | 0.07344 | 7.23557 |
December | 369.00000 | 21.59246 | 29.25303 | -0.2918 | 8.31606 |
Annual Sum or Average | 4395.00000 | 23.17936 | 42.41935 | -0.1288 | 7.81202 |
Minimum of Months | 336.00000 | 21.30715 | 24.63000 | -0.4406 | 6.33325 |
Maximum of Months | 379.00000 | 24.09840 | 59.08973 | 0.33954 | 9.97269 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.28871 | 24.67766 | -0.4556 | 10.19122 |
February | 336.00000 | 21.91361 | 27.15283 | -0.2675 | 8.62421 |
March | 379.00000 | 22.83776 | 33.63115 | 0.05041 | 7.06996 |
April | 360.00000 | 23.59796 | 40.62581 | 0.30073 | 8.09055 |
May | 375.00000 | 23.97168 | 50.04775 | -0.3878 | 8.71858 |
June | 366.00000 | 24.07525 | 52.34600 | -0.2801 | 7.25735 |
July | 369.00000 | 24.09733 | 58.84346 | -0.2060 | 6.45515 |
August | 379.00000 | 24.09872 | 59.02889 | -0.1906 | 6.32554 |
September | 360.00000 | 24.02991 | 54.48499 | -0.2933 | 7.24061 |
October | 371.00000 | 23.49419 | 44.68351 | 0.32995 | 8.59099 |
November | 360.00000 | 22.81316 | 33.33655 | 0.05454 | 7.23806 |
December | 369.00000 | 21.55332 | 29.32271 | -0.3098 | 8.51263 |
Annual Sum or Average | 4395.00000 | 23.15612 | 42.47450 | -0.1378 | 7.85359 |
Minimum of Months | 336.00000 | 21.28871 | 24.67766 | -0.4556 | 6.32554 |
Maximum of Months | 379.00000 | 24.09872 | 59.02889 | 0.32995 | 10.19122 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.26348 | 24.74653 | -0.4744 | 10.48383 |
February | 336.00000 | 21.83911 | 27.31747 | -0.2960 | 8.82436 |
March | 379.00000 | 22.73321 | 33.89891 | 0.01882 | 7.10024 |
April | 360.00000 | 23.53774 | 40.87135 | 0.28060 | 7.95463 |
May | 375.00000 | 23.95679 | 50.28471 | -0.3999 | 8.95166 |
June | 366.00000 | 24.06991 | 52.58196 | -0.2867 | 7.32491 |
July | 369.00000 | 24.09310 | 59.19613 | -0.2105 | 6.47163 |
August | 379.00000 | 24.09446 | 59.30946 | -0.1954 | 6.34101 |
September | 360.00000 | 24.02327 | 54.75464 | -0.3001 | 7.32030 |
October | 371.00000 | 23.43685 | 44.97009 | 0.31245 | 8.48430 |
November | 360.00000 | 22.72497 | 33.57971 | 0.02686 | 7.23176 |
December | 369.00000 | 21.50106 | 29.42100 | -0.3323 | 8.76123 |
Annual Sum or Average | 4395.00000 | 23.11491 | 42.70422 | -0.1545 | 7.93118 |
Minimum of Months | 336.00000 | 21.26348 | 24.74653 | -0.4744 | 6.34101 |
Maximum of Months | 379.00000 | 24.09446 | 59.30946 | 0.31245 | 10.48383 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.23046 | 26.29932 | -0.5172 | 11.25682 |
February | 308.00000 | 21.75826 | 28.89593 | -0.3457 | 9.34431 |
March | 348.00000 | 22.59640 | 35.56962 | -0.0311 | 7.06547 |
April | 330.00000 | 23.45339 | 42.31853 | 0.24613 | 7.60406 |
May | 344.00000 | 23.88765 | 51.58183 | -0.4377 | 9.50792 |
June | 336.00000 | 23.95204 | 54.00339 | -0.3257 | 7.60380 |
July | 338.00000 | 23.97732 | 60.73594 | -0.2446 | 6.57764 |
August | 348.00000 | 23.95648 | 60.65542 | -0.2350 | 6.42817 |
September | 330.00000 | 23.93818 | 56.21874 | -0.3325 | 7.63535 |
October | 340.00000 | 23.34253 | 46.46730 | 0.28196 | 8.23599 |
November | 330.00000 | 22.60813 | 35.09594 | -0.0188 | 7.21801 |
December | 338.00000 | 21.43876 | 31.03661 | -0.3734 | 9.26803 |
Annual Sum or Average | 4030.00000 | 23.02048 | 44.20206 | -0.1942 | 8.13741 |
Minimum of Months | 308.00000 | 21.23046 | 26.29932 | -0.5172 | 6.42817 |
Maximum of Months | 348.00000 | 23.97732 | 60.73594 | 0.28196 | 11.25682 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.22419 | 26.21230 | -0.5195 | 11.27122 |
February | 308.00000 | 21.74309 | 28.83611 | -0.3534 | 9.37751 |
March | 348.00000 | 22.57071 | 35.54368 | -0.0468 | 7.08811 |
April | 330.00000 | 23.43909 | 42.31055 | 0.23161 | 7.48062 |
May | 344.00000 | 23.88500 | 51.57368 | -0.4565 | 9.85633 |
June | 336.00000 | 23.95064 | 53.98848 | -0.3485 | 7.91031 |
July | 338.00000 | 23.97577 | 60.76720 | -0.2686 | 6.81869 |
August | 348.00000 | 23.95511 | 60.66274 | -0.2601 | 6.67356 |
September | 330.00000 | 23.93787 | 56.22143 | -0.3525 | 7.90772 |
October | 340.00000 | 23.33768 | 46.43149 | 0.26916 | 8.08670 |
November | 330.00000 | 22.59573 | 35.05666 | -0.0310 | 7.22019 |
December | 338.00000 | 21.43174 | 30.95697 | -0.3807 | 9.35771 |
Annual Sum or Average | 4030.00000 | 23.01277 | 44.17587 | -0.2096 | 8.24712 |
Minimum of Months | 308.00000 | 21.22419 | 26.21230 | -0.5195 | 6.67356 |
Maximum of Months | 348.00000 | 23.97577 | 60.76720 | 0.26916 | 11.27122 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.21795 | 26.22835 | -0.5249 | 11.37040 |
February | 308.00000 | 21.72369 | 28.87621 | -0.3622 | 9.46550 |
March | 348.00000 | 22.53488 | 35.63805 | -0.0594 | 7.12958 |
April | 330.00000 | 23.41091 | 42.42778 | 0.22098 | 7.43102 |
May | 344.00000 | 23.87952 | 51.67414 | -0.4626 | 9.99621 |
June | 336.00000 | 23.95009 | 54.06536 | -0.3512 | 7.95008 |
July | 338.00000 | 23.97524 | 60.85551 | -0.2708 | 6.84104 |
August | 348.00000 | 23.95481 | 60.74646 | -0.2621 | 6.69368 |
September | 330.00000 | 23.93680 | 56.29644 | -0.3551 | 7.94785 |
October | 340.00000 | 23.31731 | 46.52752 | 0.26206 | 8.05640 |
November | 330.00000 | 22.56614 | 35.13726 | -0.0413 | 7.23942 |
December | 338.00000 | 21.42089 | 30.98357 | -0.3873 | 9.44324 |
Annual Sum or Average | 4030.00000 | 22.99964 | 44.25073 | -0.2160 | 8.29008 |
Minimum of Months | 308.00000 | 21.21795 | 26.22835 | -0.5249 | 6.69368 |
Maximum of Months | 348.00000 | 23.97524 | 60.85551 | 0.26206 | 11.37040 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.20095 | 26.27041 | -0.5426 | 11.73459 |
February | 308.00000 | 21.67513 | 28.97735 | -0.3856 | 9.76709 |
March | 348.00000 | 22.44316 | 35.87686 | -0.0900 | 7.26757 |
April | 330.00000 | 23.32865 | 42.77785 | 0.19349 | 7.33245 |
May | 344.00000 | 23.85968 | 51.99630 | -0.4767 | 10.36402 |
June | 336.00000 | 23.94893 | 54.19741 | -0.3520 | 7.97037 |
July | 338.00000 | 23.97449 | 60.96948 | -0.2694 | 6.82703 |
August | 348.00000 | 23.95469 | 60.81357 | -0.2599 | 6.67097 |
September | 330.00000 | 23.93331 | 56.42881 | -0.3563 | 7.98203 |
October | 340.00000 | 23.26221 | 46.76678 | 0.24593 | 8.02274 |
November | 330.00000 | 22.49178 | 35.33579 | -0.0651 | 7.31447 |
December | 338.00000 | 21.39491 | 31.04615 | -0.4051 | 9.70314 |
Annual Sum or Average | 4030.00000 | 22.96477 | 44.41769 | -0.2300 | 8.40556 |
Minimum of Months | 308.00000 | 21.20095 | 26.27041 | -0.5426 | 6.67097 |
Maximum of Months | 348.00000 | 23.97449 | 60.96948 | 0.24593 | 11.73459 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.17860 | 26.15447 | -0.6023 | 13.21085 |
February | 308.00000 | 21.61442 | 28.85871 | -0.4451 | 10.89393 |
March | 348.00000 | 22.30390 | 36.15012 | -0.1529 | 7.72740 |
April | 330.00000 | 23.17936 | 43.36332 | 0.13878 | 7.25984 |
May | 344.00000 | 23.81021 | 52.34527 | -0.4995 | 11.14820 |
June | 336.00000 | 23.95073 | 54.25488 | -0.3223 | 7.61769 |
July | 338.00000 | 23.97914 | 60.63228 | -0.2309 | 6.49723 |
August | 348.00000 | 23.96023 | 60.45852 | -0.2173 | 6.29873 |
September | 330.00000 | 23.92563 | 56.32455 | -0.3353 | 7.80949 |
October | 340.00000 | 23.17646 | 46.95321 | 0.22320 | 8.21185 |
November | 330.00000 | 22.39567 | 35.40053 | -0.1057 | 7.62083 |
December | 338.00000 | 21.35994 | 30.89492 | -0.4531 | 10.60528 |
Annual Sum or Average | 4030.00000 | 22.91212 | 44.44582 | -0.2496 | 8.73029 |
Minimum of Months | 308.00000 | 21.17860 | 26.15447 | -0.6023 | 6.29873 |
Maximum of Months | 348.00000 | 23.97914 | 60.63228 | 0.22320 | 13.21085 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.460531E+09 | 0.127402E+09 | 32.67 | 0.460061E+09 | 470021.41 | 0.00 | 0.43 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 8052.95 | 26-FEB-15:10 | 8052.95 | 26-FEB-15:10 | 75.31 | 28-FEB-20:00 | 2222.12 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.203730E+10 | 0.549386E+09 | 102.42 | 0.162560E+10 | 0.411693E+09 | 0.00 | 0.72 | 30-MAR-16:10 | 0.00 | 01-MAR-00:10 | 15420.71 | 30-MAR-16:10 | 13329.62 | 30-MAR-16:10 | 3505.26 | 30-MAR-12:10 | 4057.51 | 30-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.643716E+10 | 0.173426E+10 | 248.24 | 0.525786E+10 | 0.117930E+10 | 0.00 | 0.70 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 14560.01 | 17-APR-16:40 | 13909.45 | 17-APR-16:10 | 4799.39 | 23-APR-13:00 | 3964.06 | 17-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.150505E+11 | 0.391717E+10 | 409.06 | 0.110285E+11 | 0.402199E+10 | 0.00 | 0.90 | 29-MAY-16:50 | 0.00 | 01-MAY-00:10 | 21490.88 | 30-MAY-17:00 | 16460.41 | 19-MAY-17:00 | 7505.04 | 31-MAY-13:10 | 5395.54 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.271493E+11 | 0.689903E+10 | 471.23 | 0.188807E+11 | 0.826867E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 51593.58 | 26-JUN-07:02 | 36064.77 | 15-JUN-07:02 | 21459.83 | 27-JUN-07:03 | 11162.20 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.336550E+11 | 0.842096E+10 | 492.47 | 0.218511E+11 | 0.118038E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 52611.67 | 27-JUL-07:02 | 35939.23 | 17-JUL-07:02 | 24776.31 | 27-JUL-07:02 | 11357.74 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.368170E+11 | 0.906616E+10 | 497.95 | 0.232031E+11 | 0.136139E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 52713.74 | 20-AUG-07:02 | 35528.05 | 27-AUG-07:02 | 29260.26 | 23-AUG-07:02 | 11446.77 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.219565E+11 | 0.546396E+10 | 435.54 | 0.145273E+11 | 0.742917E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 52375.71 | 17-SEP-07:02 | 38035.08 | 16-SEP-07:02 | 24435.71 | 28-SEP-07:03 | 11146.48 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.784455E+10 | 0.198265E+10 | 236.75 | 0.543289E+10 | 0.241166E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 51216.08 | 19-OCT-07:03 | 21864.34 | 19-OCT-07:03 | 29351.74 | 19-OCT-07:03 | 10868.18 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.129933E+10 | 0.346066E+09 | 89.33 | 0.926655E+09 | 0.372672E+09 | 0.00 | 0.67 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 | 14618.74 | 05-NOV-16:07 | 10582.64 | 05-NOV-16:03 | 4712.95 | 05-NOV-13:30 | 3647.81 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 |
December | 97448152.63 | 26876352.14 | 13.17 | 69211145.42 | 28237007.22 | 0.00 | 0.34 | 12-DEC-14:30 | 0.00 | 01-DEC-00:03 | 6825.51 | 12-DEC-14:20 | 4904.04 | 12-DEC-14:40 | 2098.14 | 12-DEC-14:00 | 1840.64 | 12-DEC-14:30 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.152805E+12 | 0.385339E+11 | 3028.83 | 0.103263E+12 | 0.495416E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.368170E+11 | 0.906616E+10 | 497.95 | 0.232031E+11 | 0.136139E+11 | 0.00 | 1.00 | 0.00 | 52713.74 | 38035.08 | 29351.74 | 11446.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1946053.88 | 543780.50 | 2.00 | 1598120.41 | 347933.47 | 0.00 | 0.09 | 30-JAN-21:20 | 0.00 | 01-JAN-00:10 | 857.41 | 30-JAN-21:20 | 770.74 | 30-JAN-21:20 | 216.02 | 19-JAN-21:10 | 237.53 | 30-JAN-21:20 | 0.00 | 01-JAN-00:10 |
February | 0.392513E+09 | 0.101526E+09 | 41.03 | 0.390370E+09 | 2143222.33 | 0.00 | 1.00 | 26-FEB-18:01 | 0.00 | 01-FEB-00:10 | 23358.93 | 26-FEB-18:50 | 23358.93 | 26-FEB-18:35 | 1281.56 | 28-FEB-23:00 | 5027.92 | 26-FEB-18:01 | 0.00 | 01-FEB-00:10 |
March | 0.153204E+10 | 0.393571E+09 | 124.50 | 0.124662E+10 | 0.285430E+09 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:10 | 24738.29 | 04-MAR-19:38 | 23358.93 | 12-MAR-17:07 | 6646.48 | 04-MAR-21:19 | 5354.71 | 11-MAR-19:07 | 0.00 | 01-MAR-00:10 |
April | 0.464323E+10 | 0.118547E+10 | 273.54 | 0.379898E+10 | 0.844252E+09 | 0.00 | 1.00 | 08-APR-18:01 | 0.00 | 01-APR-00:10 | 25843.85 | 22-APR-18:02 | 23389.72 | 08-APR-18:08 | 11789.85 | 22-APR-18:02 | 5467.59 | 22-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.901403E+10 | 0.228612E+10 | 442.13 | 0.677999E+10 | 0.223405E+10 | 0.00 | 1.00 | 04-MAY-20:02 | 0.00 | 01-MAY-00:10 | 25902.97 | 24-MAY-20:02 | 23796.24 | 13-MAY-18:11 | 12357.71 | 24-MAY-21:04 | 5559.58 | 14-MAY-17:38 | 0.00 | 01-MAY-00:10 |
June | 0.142316E+11 | 0.356033E+10 | 466.76 | 0.102469E+11 | 0.398467E+10 | 0.00 | 1.00 | 02-JUN-20:32 | 0.00 | 01-JUN-00:10 | 26118.32 | 29-JUN-07:03 | 23568.27 | 10-JUN-19:28 | 7064.25 | 27-JUN-07:03 | 5650.62 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.170961E+11 | 0.423897E+10 | 494.23 | 0.114534E+11 | 0.564278E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 26578.38 | 27-JUL-07:02 | 21253.74 | 04-JUL-07:02 | 14062.14 | 28-JUL-20:25 | 5746.64 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.183602E+11 | 0.448875E+10 | 500.23 | 0.120026E+11 | 0.635756E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26666.73 | 20-AUG-07:02 | 21037.69 | 27-AUG-07:02 | 8913.10 | 29-AUG-07:02 | 5812.39 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.117293E+11 | 0.287413E+10 | 439.40 | 0.805890E+10 | 0.367042E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 26515.42 | 17-SEP-07:02 | 21883.26 | 16-SEP-07:02 | 13558.56 | 21-SEP-20:02 | 5659.90 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.468669E+10 | 0.115323E+10 | 249.89 | 0.338109E+10 | 0.130559E+10 | 0.00 | 1.00 | 02-OCT-21:32 | 0.00 | 01-OCT-00:10 | 26578.50 | 19-OCT-07:03 | 22290.48 | 11-OCT-20:08 | 14133.21 | 19-OCT-07:03 | 5567.19 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.108377E+10 | 0.277358E+09 | 113.06 | 0.788100E+09 | 0.295665E+09 | 0.00 | 1.00 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 | 25579.95 | 04-NOV-18:02 | 14789.76 | 03-NOV-21:10 | 11136.89 | 04-NOV-18:24 | 5425.08 | 04-NOV-18:02 | 0.00 | 01-NOV-00:10 |
December | 99247641.08 | 26668912.19 | 20.92 | 70105208.92 | 29142432.16 | 0.00 | 0.43 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 4558.32 | 12-DEC-14:00 | 3251.09 | 12-DEC-14:30 | 1375.31 | 12-DEC-14:00 | 1178.57 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.828707E+11 | 0.205867E+11 | 3167.69 | 0.582187E+11 | 0.246520E+11 | 0.00 | ||||||||||||||
Minimum of Months | 1946053.88 | 543780.50 | 2.00 | 1598120.41 | 347933.47 | 0.00 | 0.09 | 0.00 | 857.41 | 770.74 | 216.02 | 237.53 | 0.00 | |||||||
Maximum of Months | 0.183602E+11 | 0.448875E+10 | 500.23 | 0.120026E+11 | 0.635756E+10 | 0.00 | 1.00 | 0.00 | 26666.73 | 23796.24 | 14133.21 | 5812.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.244463E+09 | 66199197.12 | 31.58 | 0.244405E+09 | 58376.28 | 0.00 | 0.45 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4468.93 | 28-FEB-15:10 | 4468.93 | 28-FEB-15:10 | 21.09 | 28-FEB-20:00 | 1200.28 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.937140E+09 | 0.247523E+09 | 86.75 | 0.753633E+09 | 0.183507E+09 | 0.00 | 0.73 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 8222.33 | 30-MAR-14:00 | 6978.32 | 30-MAR-16:10 | 1905.25 | 30-MAR-12:10 | 2119.82 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.294442E+10 | 0.777087E+09 | 201.50 | 0.246472E+10 | 0.479699E+09 | 0.00 | 0.70 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7606.41 | 17-APR-14:00 | 7316.04 | 17-APR-16:10 | 2513.84 | 04-APR-14:00 | 2040.42 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.629028E+10 | 0.160734E+10 | 321.11 | 0.468134E+10 | 0.160894E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 15737.67 | 31-MAY-06:03 | 8403.57 | 19-MAY-16:10 | 8387.70 | 31-MAY-06:03 | 3305.82 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.111537E+11 | 0.278227E+10 | 352.05 | 0.781908E+10 | 0.333464E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 27300.88 | 26-JUN-06:02 | 18291.91 | 12-JUN-06:02 | 15156.58 | 19-JUN-06:03 | 5755.75 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.133927E+11 | 0.329089E+10 | 363.41 | 0.871345E+10 | 0.467923E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27831.63 | 27-JUL-06:02 | 18970.46 | 04-JUL-07:02 | 15924.96 | 31-JUL-06:03 | 5799.16 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.147858E+11 | 0.358082E+10 | 373.54 | 0.939650E+10 | 0.538928E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 28221.65 | 21-AUG-06:02 | 18669.62 | 27-AUG-07:02 | 15269.94 | 23-AUG-06:03 | 5832.50 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.874289E+10 | 0.214119E+10 | 325.83 | 0.587650E+10 | 0.286639E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 28156.63 | 17-SEP-07:02 | 20082.04 | 16-SEP-06:02 | 15433.10 | 03-SEP-07:03 | 5764.27 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.317547E+10 | 0.790687E+09 | 191.04 | 0.224492E+10 | 0.930553E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 27216.93 | 19-OCT-06:03 | 11794.44 | 18-OCT-06:03 | 16069.75 | 19-OCT-06:03 | 5638.89 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.556063E+09 | 0.146657E+09 | 81.83 | 0.416547E+09 | 0.139516E+09 | 0.00 | 0.61 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6986.41 | 05-NOV-14:00 | 4810.35 | 05-NOV-15:00 | 2363.39 | 05-NOV-13:20 | 1716.00 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 57131029.48 | 15456681.66 | 14.42 | 40421228.81 | 16709800.66 | 0.00 | 0.37 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3907.51 | 12-DEC-14:00 | 2721.60 | 12-DEC-14:00 | 1185.91 | 12-DEC-14:00 | 1026.10 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.622800E+11 | 0.154461E+11 | 2343.07 | 0.426515E+11 | 0.196285E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.147858E+11 | 0.358082E+10 | 373.54 | 0.939650E+10 | 0.538928E+10 | 0.00 | 1.00 | 0.00 | 28221.65 | 20082.04 | 16069.75 | 5832.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.222607E+09 | 60544838.64 | 29.42 | 0.222567E+09 | 40010.57 | 0.00 | 0.43 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4315.83 | 28-FEB-15:10 | 4315.83 | 28-FEB-15:10 | 18.35 | 28-FEB-20:00 | 1163.94 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.890325E+09 | 0.235830E+09 | 84.17 | 0.715780E+09 | 0.174545E+09 | 0.00 | 0.72 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 8123.87 | 30-MAR-14:00 | 6898.91 | 30-MAR-16:10 | 1883.24 | 30-MAR-12:10 | 2099.78 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.288456E+10 | 0.762790E+09 | 198.67 | 0.241485E+10 | 0.469708E+09 | 0.00 | 0.70 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7583.20 | 17-APR-14:00 | 7293.32 | 17-APR-16:10 | 2466.29 | 04-APR-14:00 | 2036.13 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.624545E+10 | 0.159766E+10 | 319.36 | 0.464774E+10 | 0.159771E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 15637.31 | 31-MAY-06:03 | 8396.45 | 19-MAY-16:10 | 8337.87 | 31-MAY-06:03 | 3284.83 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.111793E+11 | 0.278904E+10 | 351.92 | 0.783906E+10 | 0.334020E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 27378.82 | 26-JUN-06:02 | 18382.31 | 12-JUN-06:02 | 15185.91 | 19-JUN-06:03 | 5770.28 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.134416E+11 | 0.330266E+10 | 363.60 | 0.875289E+10 | 0.468873E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27901.41 | 27-JUL-06:02 | 19045.03 | 04-JUL-07:02 | 15960.13 | 31-JUL-06:03 | 5813.50 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.148394E+11 | 0.359347E+10 | 373.96 | 0.943776E+10 | 0.540162E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 28297.88 | 21-AUG-06:02 | 18754.57 | 27-AUG-07:02 | 15298.65 | 23-AUG-06:03 | 5846.62 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.874266E+10 | 0.214193E+10 | 325.99 | 0.587771E+10 | 0.286495E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 28223.87 | 17-SEP-07:02 | 20140.98 | 16-SEP-06:02 | 15472.18 | 03-SEP-07:03 | 5778.11 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.313208E+10 | 0.780809E+09 | 188.62 | 0.221130E+10 | 0.920788E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 27282.46 | 19-OCT-06:03 | 11815.10 | 18-OCT-06:03 | 16114.12 | 19-OCT-06:03 | 5652.45 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.501916E+09 | 0.132733E+09 | 76.17 | 0.375810E+09 | 0.126106E+09 | 0.00 | 0.60 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6850.99 | 05-NOV-14:00 | 4712.81 | 05-NOV-15:00 | 2318.02 | 05-NOV-13:20 | 1688.16 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 44541335.96 | 12085704.95 | 12.58 | 31706352.35 | 12834983.61 | 0.00 | 0.34 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3579.93 | 12-DEC-14:00 | 2490.44 | 12-DEC-14:00 | 1089.49 | 12-DEC-14:00 | 947.59 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.621244E+11 | 0.154095E+11 | 2324.46 | 0.425272E+11 | 0.195972E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.148394E+11 | 0.359347E+10 | 373.96 | 0.943776E+10 | 0.540162E+10 | 0.00 | 1.00 | 0.00 | 28297.88 | 20140.98 | 16114.12 | 5846.62 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 6.63 | 1.89 | 0.17 | 5.87 | 0.77 | 0.00 | 0.00 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 0.01 | 31-JAN-14:50 | 0.01 | 31-JAN-14:50 | 0.00 | 31-JAN-14:50 | 0.00 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 |
February | 0.192025E+09 | 52569149.30 | 26.92 | 0.191994E+09 | 30785.06 | 0.00 | 0.41 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4022.56 | 28-FEB-15:10 | 4022.56 | 28-FEB-15:10 | 14.54 | 28-FEB-20:00 | 1092.15 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.798888E+09 | 0.212664E+09 | 78.42 | 0.642171E+09 | 0.156717E+09 | 0.00 | 0.70 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 7845.00 | 30-MAR-14:00 | 6672.00 | 30-MAR-16:10 | 1832.08 | 30-MAR-12:10 | 2037.51 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.270675E+10 | 0.719088E+09 | 190.58 | 0.226591E+10 | 0.440849E+09 | 0.00 | 0.69 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7394.26 | 17-APR-14:00 | 7124.79 | 17-APR-16:10 | 2365.89 | 23-APR-13:00 | 1991.69 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.600055E+10 | 0.153989E+10 | 310.86 | 0.445821E+10 | 0.154234E+10 | 0.00 | 1.00 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 | 13344.21 | 31-MAY-06:03 | 8245.34 | 19-MAY-16:10 | 7175.12 | 31-MAY-06:03 | 2804.85 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.109377E+11 | 0.273307E+10 | 351.70 | 0.764573E+10 | 0.329202E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 27184.55 | 26-JUN-06:02 | 18129.86 | 12-JUN-06:02 | 15119.47 | 19-JUN-06:03 | 5731.49 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.131686E+11 | 0.323917E+10 | 363.10 | 0.855138E+10 | 0.461721E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27707.47 | 27-JUL-06:02 | 18777.68 | 04-JUL-07:02 | 15890.28 | 31-JUL-06:03 | 5774.57 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.145917E+11 | 0.353615E+10 | 373.69 | 0.924841E+10 | 0.534333E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 28102.58 | 21-AUG-06:02 | 20448.01 | 26-AUG-06:02 | 15216.63 | 23-AUG-06:02 | 5807.94 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.851422E+10 | 0.208990E+10 | 324.38 | 0.570614E+10 | 0.280808E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 28028.39 | 17-SEP-07:02 | 19849.05 | 16-SEP-06:02 | 15412.45 | 03-SEP-07:03 | 5739.96 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.298717E+10 | 0.746613E+09 | 180.83 | 0.209945E+10 | 0.887716E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 27100.17 | 19-OCT-06:03 | 11368.09 | 18-OCT-06:03 | 16056.13 | 19-OCT-06:03 | 5615.01 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.420260E+09 | 0.111592E+09 | 69.25 | 0.313663E+09 | 0.106597E+09 | 0.00 | 0.58 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6559.28 | 05-NOV-14:00 | 4496.31 | 05-NOV-15:00 | 2239.18 | 05-NOV-13:30 | 1624.53 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 33367880.61 | 9101674.11 | 9.00 | 23935127.72 | 9432752.88 | 0.00 | 0.31 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3143.39 | 12-DEC-14:00 | 2181.53 | 12-DEC-14:00 | 961.85 | 12-DEC-14:00 | 840.31 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.603513E+11 | 0.149898E+11 | 2278.89 | 0.411470E+11 | 0.192043E+11 | 0.00 | ||||||||||||||
Minimum of Months | 6.63 | 1.89 | 0.17 | 5.87 | 0.77 | 0.00 | 0.00 | 0.00 | 0.01 | 0.01 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.145917E+11 | 0.353615E+10 | 373.69 | 0.924841E+10 | 0.534333E+10 | 0.00 | 1.00 | 0.00 | 28102.58 | 20448.01 | 16056.13 | 5807.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.292632E+09 | 82080579.65 | 25.17 | 0.292557E+09 | 74857.32 | 0.00 | 0.41 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7253.17 | 28-FEB-15:10 | 7253.17 | 28-FEB-15:10 | 17.79 | 28-FEB-19:20 | 2004.97 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.133971E+10 | 0.365361E+09 | 71.58 | 0.105154E+10 | 0.288173E+09 | 0.00 | 0.70 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 14274.12 | 30-MAR-14:10 | 11678.81 | 30-MAR-15:00 | 3529.72 | 30-MAR-12:20 | 3767.51 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.462905E+10 | 0.125735E+10 | 183.42 | 0.378518E+10 | 0.843876E+09 | 0.00 | 0.70 | 17-APR-14:40 | 0.00 | 01-APR-00:10 | 13851.52 | 17-APR-14:30 | 12843.88 | 17-APR-15:00 | 4601.59 | 04-APR-14:10 | 3774.38 | 17-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.105866E+11 | 0.277026E+10 | 303.67 | 0.768414E+10 | 0.290243E+10 | 0.00 | 0.94 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 21127.12 | 30-MAY-15:00 | 15143.94 | 30-MAY-15:00 | 8559.91 | 31-MAY-07:03 | 5314.06 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.198663E+11 | 0.504192E+10 | 342.29 | 0.135868E+11 | 0.627948E+10 | 0.00 | 1.00 | 04-JUN-08:63 | 0.00 | 01-JUN-00:10 | 49313.04 | 26-JUN-07:02 | 34217.96 | 15-JUN-07:02 | 27138.95 | 19-JUN-07:03 | 10594.01 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.237212E+11 | 0.592590E+10 | 348.22 | 0.151120E+11 | 0.860926E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 49921.81 | 31-JUL-07:03 | 34960.64 | 25-JUL-07:03 | 30124.59 | 31-JUL-07:03 | 10870.36 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.265203E+11 | 0.653079E+10 | 364.05 | 0.164418E+11 | 0.100785E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 50981.96 | 20-AUG-08:62 | 32232.24 | 03-AUG-07:02 | 27671.35 | 23-AUG-07:02 | 10802.08 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.151577E+11 | 0.377874E+10 | 311.09 | 0.990244E+10 | 0.525522E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 50834.19 | 17-SEP-08:62 | 35564.79 | 16-SEP-07:02 | 27980.27 | 17-SEP-08:62 | 10649.22 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.521747E+10 | 0.132696E+10 | 169.39 | 0.354776E+10 | 0.166972E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 43860.21 | 19-OCT-07:03 | 18583.13 | 19-OCT-07:03 | 25277.08 | 19-OCT-07:03 | 9311.16 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.620144E+09 | 0.168164E+09 | 56.50 | 0.458423E+09 | 0.161722E+09 | 0.00 | 0.60 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 12324.47 | 05-NOV-15:00 | 8178.42 | 05-NOV-15:00 | 4267.17 | 05-NOV-14:10 | 3115.02 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 49900333.74 | 13928485.06 | 4.83 | 35247964.54 | 14652369.19 | 0.00 | 0.28 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 5156.42 | 12-DEC-14:00 | 3507.67 | 12-DEC-14:00 | 1648.75 | 12-DEC-14:00 | 1412.80 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.108001E+12 | 0.272615E+11 | 2180.22 | 0.718978E+11 | 0.361031E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.265203E+11 | 0.653079E+10 | 364.05 | 0.164418E+11 | 0.100785E+11 | 0.00 | 1.00 | 0.00 | 50981.96 | 35564.79 | 30124.59 | 10870.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.141912E+09 | 39181593.53 | 23.83 | 0.141886E+09 | 26016.60 | 0.00 | 0.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3690.55 | 28-FEB-15:10 | 3690.55 | 28-FEB-15:10 | 7.69 | 28-FEB-19:30 | 1003.83 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.663459E+09 | 0.178014E+09 | 68.75 | 0.522297E+09 | 0.141162E+09 | 0.00 | 0.70 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7305.57 | 30-MAR-14:10 | 6002.26 | 30-MAR-15:00 | 1786.03 | 30-MAR-12:30 | 1897.58 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.233992E+10 | 0.625241E+09 | 178.92 | 0.191915E+10 | 0.420765E+09 | 0.00 | 0.70 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 7147.81 | 17-APR-14:40 | 6643.94 | 17-APR-15:00 | 2326.00 | 04-APR-14:10 | 1914.27 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.541186E+10 | 0.139258E+10 | 300.58 | 0.393720E+10 | 0.147466E+10 | 0.00 | 0.94 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10923.72 | 30-MAY-15:00 | 7842.50 | 30-MAY-15:00 | 3989.43 | 31-MAY-13:00 | 2699.98 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.101970E+11 | 0.254620E+10 | 342.13 | 0.698864E+10 | 0.320841E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25477.12 | 26-JUN-07:02 | 17686.74 | 15-JUN-07:02 | 14009.72 | 19-JUN-07:03 | 5375.84 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.121787E+11 | 0.299371E+10 | 348.14 | 0.778030E+10 | 0.439840E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25789.34 | 31-JUL-07:03 | 17627.57 | 18-JUL-07:02 | 15556.81 | 31-JUL-07:03 | 5515.72 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.136264E+11 | 0.330249E+10 | 365.19 | 0.847226E+10 | 0.515415E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26337.01 | 20-AUG-08:62 | 16653.71 | 03-AUG-07:02 | 14269.67 | 23-AUG-07:02 | 5480.07 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.778601E+10 | 0.190865E+10 | 310.77 | 0.510206E+10 | 0.268395E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 26256.72 | 17-SEP-08:62 | 18388.24 | 16-SEP-07:02 | 14466.27 | 17-SEP-08:62 | 5403.35 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.266646E+10 | 0.666465E+09 | 167.47 | 0.181705E+10 | 0.849408E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 20776.35 | 19-OCT-07:03 | 8794.69 | 19-OCT-07:03 | 11981.66 | 19-OCT-07:03 | 4334.47 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.297705E+09 | 79338354.03 | 53.25 | 0.220379E+09 | 77325668.09 | 0.00 | 0.60 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6349.21 | 05-NOV-15:00 | 4225.41 | 05-NOV-15:00 | 2176.69 | 05-NOV-14:10 | 1577.25 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 23382089.70 | 6435200.74 | 4.50 | 16569280.43 | 6812809.27 | 0.00 | 0.26 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2473.63 | 12-DEC-14:00 | 1685.28 | 12-DEC-14:00 | 788.36 | 12-DEC-14:00 | 669.14 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.553329E+11 | 0.137383E+11 | 2163.54 | 0.369178E+11 | 0.184151E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.136264E+11 | 0.330249E+10 | 365.19 | 0.847226E+10 | 0.515415E+10 | 0.00 | 1.00 | 0.00 | 26337.01 | 18388.24 | 15556.81 | 5515.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.133797E+09 | 37020013.91 | 22.75 | 0.133775E+09 | 21093.16 | 0.00 | 0.39 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3591.98 | 28-FEB-15:10 | 3591.98 | 28-FEB-15:10 | 6.95 | 28-FEB-19:20 | 979.30 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.636392E+09 | 0.171065E+09 | 66.42 | 0.500801E+09 | 0.135592E+09 | 0.00 | 0.69 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7200.63 | 30-MAR-14:10 | 5910.60 | 30-MAR-15:00 | 1757.97 | 30-MAR-12:30 | 1873.68 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.227395E+10 | 0.608777E+09 | 177.33 | 0.186592E+10 | 0.408032E+09 | 0.00 | 0.70 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 7064.18 | 17-APR-14:40 | 6562.15 | 17-APR-15:00 | 2264.02 | 04-APR-14:10 | 1894.52 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.532099E+10 | 0.137068E+10 | 298.08 | 0.386862E+10 | 0.145237E+10 | 0.00 | 0.93 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10846.16 | 30-MAY-15:00 | 7779.09 | 30-MAY-15:00 | 3970.40 | 31-MAY-13:00 | 2682.61 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.101241E+11 | 0.252848E+10 | 342.15 | 0.693045E+10 | 0.319362E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25381.15 | 26-JUN-07:02 | 17578.16 | 15-JUN-07:02 | 13970.26 | 19-JUN-07:03 | 5356.07 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.121069E+11 | 0.297610E+10 | 347.64 | 0.772689E+10 | 0.437999E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25694.33 | 31-JUL-07:03 | 17525.93 | 18-JUL-07:02 | 15510.79 | 31-JUL-07:03 | 5495.54 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.135548E+11 | 0.328508E+10 | 364.99 | 0.841754E+10 | 0.513727E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26238.51 | 20-AUG-08:62 | 16551.88 | 03-AUG-07:02 | 14230.88 | 23-AUG-07:02 | 5460.01 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.772561E+10 | 0.189432E+10 | 310.10 | 0.505662E+10 | 0.266899E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 26159.05 | 17-SEP-08:62 | 18281.19 | 16-SEP-07:02 | 14447.95 | 17-SEP-08:62 | 5383.63 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.262341E+10 | 0.656167E+09 | 165.47 | 0.178437E+10 | 0.839038E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 19975.07 | 19-OCT-07:03 | 8432.93 | 19-OCT-07:03 | 11542.13 | 19-OCT-07:03 | 4167.71 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.279529E+09 | 74572467.59 | 50.83 | 0.206320E+09 | 73208694.63 | 0.00 | 0.59 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6247.84 | 05-NOV-15:00 | 4149.45 | 05-NOV-15:00 | 2145.74 | 05-NOV-14:10 | 1554.80 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 21765090.68 | 6003867.28 | 4.50 | 15418512.61 | 6346578.07 | 0.00 | 0.25 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2363.20 | 12-DEC-14:00 | 1608.69 | 12-DEC-14:00 | 754.51 | 12-DEC-14:00 | 640.96 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.548012E+11 | 0.136083E+11 | 2150.27 | 0.365067E+11 | 0.182945E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.135548E+11 | 0.328508E+10 | 364.99 | 0.841754E+10 | 0.513727E+10 | 0.00 | 1.00 | 0.00 | 26238.51 | 18281.19 | 15510.79 | 5495.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.115956E+09 | 32262946.30 | 21.00 | 0.115945E+09 | 10427.88 | 0.00 | 0.37 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3369.14 | 28-FEB-15:10 | 3369.14 | 28-FEB-15:10 | 4.21 | 28-FEB-19:20 | 924.24 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.572462E+09 | 0.154682E+09 | 60.00 | 0.450582E+09 | 0.121881E+09 | 0.00 | 0.67 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 6967.04 | 30-MAR-14:10 | 5711.81 | 30-MAR-15:00 | 1697.77 | 30-MAR-12:40 | 1822.91 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.209949E+10 | 0.565507E+09 | 170.58 | 0.172914E+10 | 0.370346E+09 | 0.00 | 0.68 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 6864.07 | 17-APR-14:40 | 6373.39 | 17-APR-15:00 | 2100.94 | 04-APR-14:10 | 1850.07 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.508844E+10 | 0.131542E+10 | 287.17 | 0.369712E+10 | 0.139132E+10 | 0.00 | 0.92 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10711.07 | 30-MAY-15:00 | 7671.49 | 30-MAY-15:00 | 3936.24 | 31-MAY-13:00 | 2656.82 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.100188E+11 | 0.250478E+10 | 342.96 | 0.684941E+10 | 0.316943E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25378.83 | 26-JUN-07:02 | 17500.99 | 15-JUN-07:02 | 13095.57 | 19-JUN-07:03 | 5357.80 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.120413E+11 | 0.296151E+10 | 346.44 | 0.768546E+10 | 0.435588E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25702.40 | 31-JUL-07:03 | 17476.77 | 18-JUL-07:02 | 15547.95 | 31-JUL-07:03 | 5497.76 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.135187E+11 | 0.327762E+10 | 366.92 | 0.839284E+10 | 0.512589E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26243.11 | 20-AUG-08:62 | 16512.59 | 03-AUG-07:02 | 14254.70 | 23-AUG-07:02 | 5461.98 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.764317E+10 | 0.187578E+10 | 307.49 | 0.499956E+10 | 0.264361E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 26160.77 | 17-SEP-08:62 | 17723.70 | 16-SEP-07:02 | 14546.41 | 17-SEP-08:62 | 5386.10 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.252942E+10 | 0.634060E+09 | 160.36 | 0.171463E+10 | 0.814791E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 17560.59 | 19-OCT-07:03 | 7717.66 | 10-OCT-16:10 | 10205.55 | 19-OCT-07:03 | 3665.51 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.238833E+09 | 63896189.57 | 44.50 | 0.175103E+09 | 63730239.90 | 0.00 | 0.57 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6021.28 | 05-NOV-15:00 | 3981.23 | 05-NOV-15:00 | 2083.36 | 05-NOV-14:10 | 1506.22 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 17848685.66 | 4952863.25 | 4.33 | 12652692.24 | 5195993.42 | 0.00 | 0.22 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2095.57 | 12-DEC-14:00 | 1424.68 | 12-DEC-14:00 | 670.89 | 12-DEC-14:00 | 572.39 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.538845E+11 | 0.133905E+11 | 2111.75 | 0.358224E+11 | 0.180621E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.135187E+11 | 0.327762E+10 | 366.92 | 0.839284E+10 | 0.512589E+10 | 0.00 | 1.00 | 0.00 | 26243.11 | 17723.70 | 15547.95 | 5497.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.103861E+09 | 29132159.43 | 17.67 | 0.103861E+09 | -0.0 | 0.00 | 0.34 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3362.76 | 28-FEB-15:10 | 3362.76 | 28-FEB-15:10 | 0.00 | 28-FEB-14:00 | 930.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.506058E+09 | 0.138234E+09 | 53.67 | 0.404162E+09 | 0.101895E+09 | 0.00 | 0.63 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7127.20 | 30-MAR-14:10 | 5856.22 | 30-MAR-15:00 | 1712.15 | 30-MAR-12:40 | 1886.04 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.195688E+10 | 0.533507E+09 | 156.83 | 0.165596E+10 | 0.300915E+09 | 0.00 | 0.64 | 17-APR-14:10 | 0.00 | 01-APR-00:10 | 7018.37 | 17-APR-14:10 | 6516.68 | 17-APR-14:30 | 1893.24 | 04-APR-15:00 | 1912.75 | 17-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.517709E+10 | 0.134805E+10 | 271.08 | 0.382478E+10 | 0.135231E+10 | 0.00 | 0.90 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11234.25 | 30-MAY-15:00 | 8181.06 | 30-MAY-14:30 | 4034.33 | 31-MAY-13:00 | 2819.42 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.107604E+11 | 0.270163E+10 | 341.58 | 0.746949E+10 | 0.329088E+10 | 0.00 | 1.00 | 06-JUN-12:10 | 0.00 | 01-JUN-00:10 | 28143.97 | 26-JUN-07:02 | 16535.86 | 14-JUN-07:02 | 13050.49 | 26-JUN-07:02 | 5885.61 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.131128E+11 | 0.323461E+10 | 338.32 | 0.854963E+10 | 0.456322E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 28392.07 | 27-JUL-07:02 | 18228.68 | 18-JUL-07:02 | 15092.16 | 09-JUL-08:62 | 6028.31 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.147760E+11 | 0.359532E+10 | 365.61 | 0.936539E+10 | 0.541062E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29062.15 | 20-AUG-08:62 | 17366.39 | 27-AUG-08:62 | 16440.56 | 20-AUG-08:03 | 6018.44 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.826137E+10 | 0.203299E+10 | 298.73 | 0.553166E+10 | 0.272971E+10 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:05 | 28622.73 | 17-SEP-08:62 | 17160.11 | 27-SEP-07:02 | 15919.63 | 17-SEP-08:62 | 5901.07 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.261093E+10 | 0.656836E+09 | 151.97 | 0.179719E+10 | 0.813742E+09 | 0.00 | 0.92 | 10-OCT-14:10 | 0.00 | 01-OCT-00:10 | 11615.37 | 10-OCT-14:10 | 8351.59 | 10-OCT-14:10 | 6788.58 | 19-OCT-07:03 | 2835.00 | 10-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.203647E+09 | 54789951.74 | 39.50 | 0.148802E+09 | 54844325.57 | 0.00 | 0.53 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6026.28 | 05-NOV-15:00 | 4026.55 | 05-NOV-15:00 | 2036.72 | 05-NOV-14:10 | 1526.18 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 13673481.34 | 3825857.24 | 4.00 | 9853417.50 | 3820063.84 | 0.00 | 0.18 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 1820.42 | 12-DEC-14:00 | 1252.57 | 12-DEC-14:00 | 567.85 | 12-DEC-14:00 | 503.01 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.574827E+11 | 0.143289E+11 | 2038.96 | 0.388608E+11 | 0.186220E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.147760E+11 | 0.359532E+10 | 365.61 | 0.936539E+10 | 0.541062E+10 | 0.00 | 1.00 | 0.00 | 29062.15 | 18228.68 | 16440.56 | 6028.31 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 78.11 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.30 | 66.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.71 | 45.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 38.07 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 25.27 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.74 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.32 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.22 | 9.25 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 21.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.61 | 56.84 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.43 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 39.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 78.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 78.11 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.30 | 66.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.71 | 45.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 38.07 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 25.27 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.74 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.32 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.22 | 9.25 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 21.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.61 | 56.84 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.43 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 39.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 78.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 78.11 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.30 | 66.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.71 | 45.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 38.07 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 25.27 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.74 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.32 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.22 | 9.25 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 21.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.61 | 56.84 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.43 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 39.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 78.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 78.11 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.30 | 66.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.71 | 45.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 38.07 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 25.27 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.74 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.32 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.22 | 9.25 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 21.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.61 | 56.84 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.43 | 66.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 39.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 78.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 107.46 | 92.58 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 108.94 | 78.78 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 106.95 | 54.05 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 88.28 | 45.31 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.58 | 30.13 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.13 | 18.92 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.57 | 13.13 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 104.47 | 11.11 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.95 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 123.02 | 53.05 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 119.97 | 67.60 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 112.73 | 79.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.98 | 47.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.58 | 11.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 123.02 | 92.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 107.46 | 92.58 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 108.94 | 78.78 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 106.95 | 54.05 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 88.28 | 45.31 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.58 | 30.13 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.13 | 18.92 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.57 | 13.13 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 104.47 | 11.11 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.95 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 123.02 | 53.05 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 119.97 | 67.60 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 112.73 | 79.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.98 | 47.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.58 | 11.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 123.02 | 92.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.64 | 82.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.78 | 70.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.04 | 48.75 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.16 | 40.17 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.62 | 26.23 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 16.14 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.55 | 11.20 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.53 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 22.10 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.52 | 46.24 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.31 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.96 | 71.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.20 | 41.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.62 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.52 | 82.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.64 | 82.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.78 | 70.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.04 | 48.75 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.16 | 40.17 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.62 | 26.23 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 16.14 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.55 | 11.20 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.53 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 22.10 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.52 | 46.24 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.31 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.96 | 71.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.20 | 41.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.62 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.52 | 82.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 105.86 | 98.00 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 107.16 | 84.10 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 105.00 | 57.92 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 86.89 | 47.77 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.04 | 31.27 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.19 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.84 | 13.42 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 104.84 | 11.21 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.91 | 26.42 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 122.20 | 55.00 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 118.46 | 70.99 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 111.01 | 84.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.10 | 49.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.04 | 11.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 122.20 | 98.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.95 | 80.17 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.09 | 69.07 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.32 | 47.90 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.06 | 40.54 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.33 | 27.28 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.10 | 17.75 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.35 | 12.72 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.57 | 10.97 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.20 | 23.63 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.50 | 46.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.68 | 58.81 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.37 | 68.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.03 | 41.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.33 | 10.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.50 | 80.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.95 | 80.17 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.09 | 69.07 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.32 | 47.90 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.06 | 40.54 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.33 | 27.28 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.10 | 17.75 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.35 | 12.72 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.57 | 10.97 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.20 | 23.63 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.50 | 46.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.68 | 58.81 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.37 | 68.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.03 | 41.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.33 | 10.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.50 | 80.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 105.65 | 94.45 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 106.95 | 81.41 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 104.75 | 56.61 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.30 | 47.94 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.30 | 32.32 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.94 | 21.10 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.99 | 15.13 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.17 | 13.08 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.97 | 28.05 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.51 | 55.02 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.24 | 69.51 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.89 | 81.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.37 | 49.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.30 | 13.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.51 | 94.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.15 | 79.08 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.35 | 68.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.59 | 47.14 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.19 | 40.18 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.37 | 27.17 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.07 | 17.84 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.29 | 12.86 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.52 | 11.12 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.20 | 23.65 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.60 | 46.13 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.93 | 58.04 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.61 | 67.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 41.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.37 | 11.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.60 | 79.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.15 | 79.08 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.35 | 68.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.59 | 47.14 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.19 | 40.18 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.37 | 27.17 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.07 | 17.84 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.29 | 12.86 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.52 | 11.12 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.20 | 23.65 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.60 | 46.13 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.93 | 58.04 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.61 | 67.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 41.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.37 | 11.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.60 | 79.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 105.90 | 93.17 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 107.26 | 80.16 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 105.08 | 55.71 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.45 | 47.52 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.35 | 32.18 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.91 | 21.21 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.92 | 15.29 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.12 | 13.27 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.97 | 28.08 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.62 | 54.56 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.55 | 68.61 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 111.18 | 79.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.51 | 48.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.35 | 13.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.62 | 93.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.41 | 78.16 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.69 | 66.94 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.03 | 46.21 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.49 | 39.53 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.55 | 26.76 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.21 | 17.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.42 | 12.58 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 10.84 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.31 | 23.32 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.81 | 45.51 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.29 | 57.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.90 | 66.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.38 | 40.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.55 | 10.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.81 | 78.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.41 | 78.16 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.69 | 66.94 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.03 | 46.21 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.49 | 39.53 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.55 | 26.76 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.21 | 17.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.42 | 12.58 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 10.84 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.31 | 23.32 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.81 | 45.51 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.29 | 57.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.90 | 66.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.38 | 40.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.55 | 10.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.81 | 78.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 106.21 | 92.08 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 107.67 | 78.90 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 105.60 | 54.62 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.81 | 46.75 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.57 | 31.70 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.07 | 20.84 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.07 | 14.96 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.25 | 12.94 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.10 | 27.69 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.87 | 53.83 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.98 | 67.59 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 111.53 | 78.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.79 | 48.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.57 | 12.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.87 | 92.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.38 | 75.47 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.70 | 64.26 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.06 | 44.17 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.24 | 37.92 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.89 | 25.59 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.28 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.48 | 11.78 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.67 | 10.01 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.44 | 22.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.31 | 44.11 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.14 | 55.28 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.84 | 64.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.94 | 39.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.89 | 10.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.31 | 75.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.38 | 75.47 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.70 | 64.26 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.06 | 44.17 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.24 | 37.92 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.89 | 25.59 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.28 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.48 | 11.78 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.67 | 10.01 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.44 | 22.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.31 | 44.11 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.14 | 55.28 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.84 | 64.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.94 | 39.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.89 | 10.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.31 | 75.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.38 | 75.47 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.70 | 64.26 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.06 | 44.17 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.24 | 37.92 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.89 | 25.59 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.28 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.48 | 11.78 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.67 | 10.01 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.44 | 22.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.31 | 44.11 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.14 | 55.28 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.84 | 64.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.94 | 39.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.89 | 10.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.31 | 75.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.38 | 75.47 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.70 | 64.26 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.06 | 44.17 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.24 | 37.92 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.89 | 25.59 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.28 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.48 | 11.78 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.67 | 10.01 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.44 | 22.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.31 | 44.11 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.14 | 55.28 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.84 | 64.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.94 | 39.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.89 | 10.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.31 | 75.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.33 | 88.96 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.83 | 75.78 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.79 | 52.24 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.68 | 44.88 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.96 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.16 | 19.67 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.14 | 14.01 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.29 | 11.95 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.25 | 26.60 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.44 | 52.19 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.96 | 65.37 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.61 | 76.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.43 | 46.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.96 | 11.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.44 | 88.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.33 | 88.96 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.83 | 75.78 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.79 | 52.24 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.68 | 44.88 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.96 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.16 | 19.67 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.14 | 14.01 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.29 | 11.95 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.25 | 26.60 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.44 | 52.19 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.96 | 65.37 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.61 | 76.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.43 | 46.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.96 | 11.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.44 | 88.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 75.83 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.41 | 64.43 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.89 | 44.01 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.16 | 37.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.90 | 25.40 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.45 | 16.26 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.68 | 11.49 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.85 | 9.68 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.45 | 22.13 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.15 | 43.98 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.96 | 55.21 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.52 | 64.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.85 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.90 | 9.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.15 | 75.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.00 | 75.83 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.41 | 64.43 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.89 | 44.01 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.16 | 37.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.90 | 25.40 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.45 | 16.26 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.68 | 11.49 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.85 | 9.68 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.45 | 22.13 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.15 | 43.98 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.96 | 55.21 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.52 | 64.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.85 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.90 | 9.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.15 | 75.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 106.93 | 89.34 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.53 | 75.94 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.63 | 52.03 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.62 | 44.66 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.99 | 30.09 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.36 | 19.34 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.39 | 13.67 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.51 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.28 | 26.28 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.29 | 52.01 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.79 | 65.26 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.28 | 76.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.36 | 46.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.99 | 11.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.29 | 89.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.08 | 75.56 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.53 | 64.09 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.08 | 43.63 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 37.43 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.00 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.51 | 16.17 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.74 | 11.41 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.90 | 9.60 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.49 | 22.04 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 43.74 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.11 | 54.90 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.62 | 64.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 38.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.00 | 9.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 75.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.08 | 75.56 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.53 | 64.09 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.08 | 43.63 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.34 | 37.43 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.00 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.51 | 16.17 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.74 | 11.41 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.90 | 9.60 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.49 | 22.04 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.24 | 43.74 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.11 | 54.90 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.62 | 64.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.95 | 38.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.00 | 9.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.24 | 75.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.03 | 89.02 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.68 | 75.54 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.86 | 51.58 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.83 | 44.28 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.11 | 29.89 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.44 | 19.23 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.46 | 13.58 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.57 | 11.47 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.33 | 26.17 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.40 | 51.74 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.96 | 64.90 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.40 | 76.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.48 | 45.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.11 | 11.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.40 | 89.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.37 | 74.41 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.87 | 62.92 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.55 | 42.53 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.80 | 36.48 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.26 | 24.71 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.56 | 16.00 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.74 | 11.33 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.88 | 9.56 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.53 | 21.88 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.46 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.46 | 54.07 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.92 | 63.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.18 | 38.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.26 | 9.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.46 | 74.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.37 | 74.41 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.87 | 62.92 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.55 | 42.53 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.80 | 36.48 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.26 | 24.71 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.56 | 16.00 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.74 | 11.33 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.88 | 9.56 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.53 | 21.88 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.46 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.46 | 54.07 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.92 | 63.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.18 | 38.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.26 | 9.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.46 | 74.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.37 | 87.66 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 109.08 | 74.16 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.42 | 50.30 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.38 | 43.16 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.42 | 29.29 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.50 | 19.04 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.46 | 13.49 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.54 | 11.42 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.37 | 25.98 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.65 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.39 | 63.92 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.76 | 74.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.76 | 45.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.42 | 11.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.65 | 87.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.31 | 69.66 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.73 | 58.55 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 90.59 | 38.89 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.79 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.74 | 22.82 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.22 | 15.44 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.13 | 11.17 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.18 | 9.66 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.23 | 21.44 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.74 | 41.26 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.15 | 51.48 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.78 | 59.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.53 | 36.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.74 | 9.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.74 | 69.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.31 | 69.66 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.73 | 58.55 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 90.59 | 38.89 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.79 | 33.22 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.74 | 22.82 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.22 | 15.44 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.13 | 11.17 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.18 | 9.66 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.23 | 21.44 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.74 | 41.26 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.15 | 51.48 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.78 | 59.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.53 | 36.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.74 | 9.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.74 | 69.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.50 | 82.06 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 110.13 | 69.02 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 108.67 | 46.01 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 89.56 | 39.33 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 75.00 | 27.07 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.09 | 18.38 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.72 | 13.30 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.70 | 11.55 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.02 | 25.47 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.99 | 48.82 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 121.21 | 60.87 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.81 | 70.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 101.17 | 42.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 75.00 | 11.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.99 | 82.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.209204E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218452E+09 | 0.160746E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237595E+09 | 0.121728E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190096E+09 | 98671869.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166279E+09 | 67685095.11 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175592E+09 | 40966472.49 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193711E+09 | 29358315.81 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233619E+09 | 24762387.54 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211493E+09 | 56609931.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273841E+09 | 0.119374E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258184E+09 | 0.147326E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250238E+09 | 0.178261E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264749E+10 | 0.125469E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166279E+09 | 24762387.54 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273841E+09 | 0.209204E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.209204E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218452E+09 | 0.160746E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237595E+09 | 0.121728E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190096E+09 | 98671869.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166279E+09 | 67685095.11 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175592E+09 | 40966472.49 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193711E+09 | 29358315.81 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233619E+09 | 24762387.54 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211493E+09 | 56609931.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273841E+09 | 0.119374E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258184E+09 | 0.147326E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250238E+09 | 0.178261E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264749E+10 | 0.125469E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166279E+09 | 24762387.54 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273841E+09 | 0.209204E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.209204E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218452E+09 | 0.160746E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237595E+09 | 0.121728E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190096E+09 | 98671869.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166279E+09 | 67685095.11 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175592E+09 | 40966472.49 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193711E+09 | 29358315.81 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233619E+09 | 24762387.54 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211493E+09 | 56609931.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273841E+09 | 0.119374E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258184E+09 | 0.147326E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250238E+09 | 0.178261E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264749E+10 | 0.125469E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166279E+09 | 24762387.54 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273841E+09 | 0.209204E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.209204E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218452E+09 | 0.160746E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237595E+09 | 0.121728E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190096E+09 | 98671869.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166279E+09 | 67685095.11 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175592E+09 | 40966472.49 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193711E+09 | 29358315.81 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233619E+09 | 24762387.54 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211493E+09 | 56609931.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273841E+09 | 0.119374E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258184E+09 | 0.147326E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250238E+09 | 0.178261E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264749E+10 | 0.125469E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166279E+09 | 24762387.54 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273841E+09 | 0.209204E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.287812E+09 | 0.247956E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.263555E+09 | 0.190593E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.286447E+09 | 0.144765E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.228811E+09 | 0.117440E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.199758E+09 | 80713459.61 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210278E+09 | 49051443.32 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.231877E+09 | 35172245.52 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.279810E+09 | 29767871.67 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253879E+09 | 67674040.17 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.329485E+09 | 0.142078E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.310960E+09 | 0.175210E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.301928E+09 | 0.211593E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.318460E+10 | 0.149201E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.199758E+09 | 29767871.67 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.329485E+09 | 0.247956E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.287812E+09 | 0.247956E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.263555E+09 | 0.190593E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.286447E+09 | 0.144765E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.228811E+09 | 0.117440E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.199758E+09 | 80713459.61 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210278E+09 | 49051443.32 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.231877E+09 | 35172245.52 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.279810E+09 | 29767871.67 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253879E+09 | 67674040.17 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.329485E+09 | 0.142078E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.310960E+09 | 0.175210E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.301928E+09 | 0.211593E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.318460E+10 | 0.149201E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.199758E+09 | 29767871.67 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.329485E+09 | 0.247956E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.234725E+09 | 0.221618E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214782E+09 | 0.171722E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233136E+09 | 0.130574E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187042E+09 | 0.104113E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165051E+09 | 70259787.48 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175728E+09 | 41842660.48 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194307E+09 | 30004619.78 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234440E+09 | 24985491.64 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211385E+09 | 57295892.47 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271919E+09 | 0.123847E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.254828E+09 | 0.154847E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246318E+09 | 0.190647E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262366E+10 | 0.132176E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165051E+09 | 24985491.64 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271919E+09 | 0.221618E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.234725E+09 | 0.221618E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214782E+09 | 0.171722E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233136E+09 | 0.130574E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187042E+09 | 0.104113E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165051E+09 | 70259787.48 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175728E+09 | 41842660.48 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194307E+09 | 30004619.78 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234440E+09 | 24985491.64 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211385E+09 | 57295892.47 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271919E+09 | 0.123847E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.254828E+09 | 0.154847E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246318E+09 | 0.190647E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262366E+10 | 0.132176E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165051E+09 | 24985491.64 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271919E+09 | 0.221618E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.283527E+09 | 0.262494E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.259251E+09 | 0.203453E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.281222E+09 | 0.155137E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.225220E+09 | 0.123830E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.198318E+09 | 83743398.68 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210440E+09 | 50086779.33 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.232591E+09 | 35935850.04 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.280812E+09 | 30035473.97 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253794E+09 | 68476538.69 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.327288E+09 | 0.147305E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.307049E+09 | 0.184016E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.297338E+09 | 0.226058E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.315685E+10 | 0.157057E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.198318E+09 | 30035473.97 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.327288E+09 | 0.262494E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.235555E+09 | 0.214716E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215538E+09 | 0.167097E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233878E+09 | 0.128289E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.186780E+09 | 0.105087E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164275E+09 | 73075513.31 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173920E+09 | 46016079.96 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191092E+09 | 34066137.95 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231859E+09 | 29371605.08 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210483E+09 | 61246973.78 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271861E+09 | 0.124615E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255766E+09 | 0.152439E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.247405E+09 | 0.184126E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.261841E+10 | 0.132014E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164275E+09 | 29371605.08 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271861E+09 | 0.214716E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.235555E+09 | 0.214716E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215538E+09 | 0.167097E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233878E+09 | 0.128289E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.186780E+09 | 0.105087E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164275E+09 | 73075513.31 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173920E+09 | 46016079.96 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191092E+09 | 34066137.95 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231859E+09 | 29371605.08 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210483E+09 | 61246973.78 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271861E+09 | 0.124615E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255766E+09 | 0.152439E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.247405E+09 | 0.184126E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.261841E+10 | 0.132014E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164275E+09 | 29371605.08 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271861E+09 | 0.214716E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.282977E+09 | 0.252985E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.258742E+09 | 0.196935E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.280571E+09 | 0.151616E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.223687E+09 | 0.124272E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.196332E+09 | 86554265.95 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207203E+09 | 54696224.29 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227626E+09 | 40524106.33 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.276324E+09 | 35043629.79 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251359E+09 | 72713589.28 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325440E+09 | 0.147371E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.306490E+09 | 0.180177E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.297018E+09 | 0.217215E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.313377E+10 | 0.156010E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.196332E+09 | 35043629.79 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325440E+09 | 0.252985E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236113E+09 | 0.211810E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.216152E+09 | 0.164537E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234610E+09 | 0.126250E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187105E+09 | 0.104152E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164384E+09 | 72777248.59 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173856E+09 | 46242441.43 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190954E+09 | 34435355.73 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231743E+09 | 29791560.68 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210476E+09 | 61295587.62 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272118E+09 | 0.123561E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.256426E+09 | 0.150448E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.248050E+09 | 0.181381E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262199E+10 | 0.130668E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164384E+09 | 29791560.68 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272118E+09 | 0.211810E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236113E+09 | 0.211810E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.216152E+09 | 0.164537E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234610E+09 | 0.126250E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187105E+09 | 0.104152E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164384E+09 | 72777248.59 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173856E+09 | 46242441.43 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190954E+09 | 34435355.73 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231743E+09 | 29791560.68 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210476E+09 | 61295587.62 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272118E+09 | 0.123561E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.256426E+09 | 0.150448E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.248050E+09 | 0.181381E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262199E+10 | 0.130668E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164384E+09 | 29791560.68 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272118E+09 | 0.211810E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.283648E+09 | 0.249552E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.259478E+09 | 0.193917E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.281443E+09 | 0.149215E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.224075E+09 | 0.123172E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.196463E+09 | 86202311.05 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207127E+09 | 54963509.45 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227463E+09 | 40960071.82 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.276186E+09 | 35540783.15 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251351E+09 | 72771680.30 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325749E+09 | 0.146127E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.307279E+09 | 0.177828E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.297795E+09 | 0.213977E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.313806E+10 | 0.154423E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.196463E+09 | 35540783.15 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325749E+09 | 0.249552E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236796E+09 | 0.209340E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.216983E+09 | 0.161947E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235774E+09 | 0.123761E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187895E+09 | 0.102450E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164868E+09 | 71674195.83 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174203E+09 | 45428088.98 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191283E+09 | 33685605.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232047E+09 | 29032552.62 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210757E+09 | 60436376.63 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272677E+09 | 0.121898E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.257357E+09 | 0.148214E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.248828E+09 | 0.179045E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262947E+10 | 0.128691E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164868E+09 | 29032552.62 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272677E+09 | 0.209340E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236796E+09 | 0.209340E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.216983E+09 | 0.161947E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235774E+09 | 0.123761E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187895E+09 | 0.102450E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164868E+09 | 71674195.83 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174203E+09 | 45428088.98 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191283E+09 | 33685605.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232047E+09 | 29032552.62 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210757E+09 | 60436376.63 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272677E+09 | 0.121898E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.257357E+09 | 0.148214E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.248828E+09 | 0.179045E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262947E+10 | 0.128691E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164868E+09 | 29032552.62 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272677E+09 | 0.209340E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.284471E+09 | 0.246636E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.260473E+09 | 0.190867E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.282831E+09 | 0.146291E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.225021E+09 | 0.121174E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.197044E+09 | 84906436.88 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207543E+09 | 54007032.38 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227856E+09 | 40080284.13 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.276549E+09 | 34647960.17 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251690E+09 | 71760976.62 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.326416E+09 | 0.144170E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.308389E+09 | 0.175196E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.298730E+09 | 0.211228E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.314702E+10 | 0.152097E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.197044E+09 | 34647960.17 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.326416E+09 | 0.246636E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239401E+09 | 0.202140E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219420E+09 | 0.155461E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238534E+09 | 0.118300E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189834E+09 | 98296417.80 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165758E+09 | 68548623.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174398E+09 | 42879695.26 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191444E+09 | 31550396.45 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232144E+09 | 26823020.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211101E+09 | 58056601.89 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274039E+09 | 0.118154E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259566E+09 | 0.143275E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251342E+09 | 0.173135E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264698E+10 | 0.123662E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165758E+09 | 26823020.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274039E+09 | 0.202140E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239401E+09 | 0.202140E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219420E+09 | 0.155461E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238534E+09 | 0.118300E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189834E+09 | 98296417.80 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165758E+09 | 68548623.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174398E+09 | 42879695.26 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191444E+09 | 31550396.45 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232144E+09 | 26823020.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211101E+09 | 58056601.89 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274039E+09 | 0.118154E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259566E+09 | 0.143275E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251342E+09 | 0.173135E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264698E+10 | 0.123662E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165758E+09 | 26823020.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274039E+09 | 0.202140E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239401E+09 | 0.202140E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219420E+09 | 0.155461E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238534E+09 | 0.118300E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189834E+09 | 98296417.80 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165758E+09 | 68548623.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174398E+09 | 42879695.26 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191444E+09 | 31550396.45 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232144E+09 | 26823020.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211101E+09 | 58056601.89 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274039E+09 | 0.118154E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259566E+09 | 0.143275E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251342E+09 | 0.173135E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264698E+10 | 0.123662E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165758E+09 | 26823020.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274039E+09 | 0.202140E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239401E+09 | 0.202140E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219420E+09 | 0.155461E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238534E+09 | 0.118300E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189834E+09 | 98296417.80 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165758E+09 | 68548623.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174398E+09 | 42879695.26 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191444E+09 | 31550396.45 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232144E+09 | 26823020.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211101E+09 | 58056601.89 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274039E+09 | 0.118154E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259566E+09 | 0.143275E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251342E+09 | 0.173135E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264698E+10 | 0.123662E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165758E+09 | 26823020.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274039E+09 | 0.202140E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.287469E+09 | 0.238282E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.263283E+09 | 0.183326E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.286014E+09 | 0.139913E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.227269E+09 | 0.116317E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198087E+09 | 81239639.77 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207782E+09 | 50990316.93 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228043E+09 | 37536680.45 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.276649E+09 | 32011953.49 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252073E+09 | 68943496.07 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327951E+09 | 0.139798E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310927E+09 | 0.169430E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.301617E+09 | 0.204368E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316716E+10 | 0.146216E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198087E+09 | 32011953.49 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327951E+09 | 0.238282E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.287469E+09 | 0.238282E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.263283E+09 | 0.183326E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.286014E+09 | 0.139913E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.227269E+09 | 0.116317E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198087E+09 | 81239639.77 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207782E+09 | 50990316.93 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228043E+09 | 37536680.45 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.276649E+09 | 32011953.49 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252073E+09 | 68943496.07 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327951E+09 | 0.139798E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310927E+09 | 0.169430E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.301617E+09 | 0.204368E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316716E+10 | 0.146216E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198087E+09 | 32011953.49 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327951E+09 | 0.238282E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.203108E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218715E+09 | 0.155873E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238080E+09 | 0.117873E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189634E+09 | 97861297.03 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165783E+09 | 68021218.20 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174822E+09 | 42148413.46 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191992E+09 | 30773455.32 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232612E+09 | 25919276.67 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211107E+09 | 57368386.10 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273594E+09 | 0.117788E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259103E+09 | 0.143102E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250486E+09 | 0.173473E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264432E+10 | 0.123331E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165783E+09 | 25919276.67 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273594E+09 | 0.203108E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238386E+09 | 0.203108E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218715E+09 | 0.155873E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238080E+09 | 0.117873E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189634E+09 | 97861297.03 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165783E+09 | 68021218.20 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174822E+09 | 42148413.46 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.191992E+09 | 30773455.32 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232612E+09 | 25919276.67 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211107E+09 | 57368386.10 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273594E+09 | 0.117788E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259103E+09 | 0.143102E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250486E+09 | 0.173473E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264432E+10 | 0.123331E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165783E+09 | 25919276.67 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273594E+09 | 0.203108E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.286399E+09 | 0.239287E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.262564E+09 | 0.183715E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.285597E+09 | 0.139360E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.227111E+09 | 0.115767E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198167E+09 | 80600902.30 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208297E+09 | 50133009.94 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228704E+09 | 36623197.71 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.277230E+09 | 30952471.44 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252138E+09 | 68124483.77 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327532E+09 | 0.139313E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310491E+09 | 0.169159E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.300737E+09 | 0.204660E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316497E+10 | 0.145770E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198167E+09 | 30952471.44 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327532E+09 | 0.239287E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238603E+09 | 0.202378E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219009E+09 | 0.155046E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238595E+09 | 0.116846E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190093E+09 | 97024759.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166067E+09 | 67555122.64 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174985E+09 | 41910231.82 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192149E+09 | 30565285.00 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232751E+09 | 25721593.30 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211227E+09 | 57120287.94 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273847E+09 | 0.117159E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259483E+09 | 0.142296E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250756E+09 | 0.172712E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264757E+10 | 0.122633E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166067E+09 | 25721593.30 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273847E+09 | 0.202378E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238603E+09 | 0.202378E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219009E+09 | 0.155046E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238595E+09 | 0.116846E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190093E+09 | 97024759.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166067E+09 | 67555122.64 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174985E+09 | 41910231.82 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192149E+09 | 30565285.00 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232751E+09 | 25721593.30 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211227E+09 | 57120287.94 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273847E+09 | 0.117159E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259483E+09 | 0.142296E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250756E+09 | 0.172712E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264757E+10 | 0.122633E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166067E+09 | 25721593.30 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273847E+09 | 0.202378E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.286661E+09 | 0.238424E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.262916E+09 | 0.182740E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.286213E+09 | 0.138152E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.227659E+09 | 0.114783E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198508E+09 | 80051618.64 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208493E+09 | 49850612.73 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228891E+09 | 36377103.54 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.277396E+09 | 30718251.46 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252283E+09 | 67831262.11 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327835E+09 | 0.138571E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310946E+09 | 0.168208E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.301063E+09 | 0.203762E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316886E+10 | 0.144947E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198508E+09 | 30718251.46 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327835E+09 | 0.238424E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239360E+09 | 0.199290E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219825E+09 | 0.152212E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.239860E+09 | 0.113922E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191287E+09 | 94551435.32 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166754E+09 | 66188217.21 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175125E+09 | 41482498.07 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192154E+09 | 30340883.61 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232689E+09 | 25613429.90 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211314E+09 | 56702593.79 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274417E+09 | 0.115535E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260405E+09 | 0.140146E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251555E+09 | 0.170091E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265474E+10 | 0.120607E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166754E+09 | 25613429.90 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274417E+09 | 0.199290E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239360E+09 | 0.199290E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219825E+09 | 0.152212E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.239860E+09 | 0.113922E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191287E+09 | 94551435.32 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166754E+09 | 66188217.21 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175125E+09 | 41482498.07 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192154E+09 | 30340883.61 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232689E+09 | 25613429.90 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211314E+09 | 56702593.79 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274417E+09 | 0.115535E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260405E+09 | 0.140146E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251555E+09 | 0.170091E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265474E+10 | 0.120607E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166754E+09 | 25613429.90 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274417E+09 | 0.199290E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.287574E+09 | 0.234781E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.263895E+09 | 0.179401E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.287721E+09 | 0.134713E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.229085E+09 | 0.111876E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.199331E+09 | 78448144.20 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208659E+09 | 49352127.82 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228897E+09 | 36118826.75 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.277321E+09 | 30597876.67 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252387E+09 | 67343528.48 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.328517E+09 | 0.136661E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.312044E+09 | 0.165676E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.302024E+09 | 0.200675E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.317745E+10 | 0.142564E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.199331E+09 | 30597876.67 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.328517E+09 | 0.234781E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241875E+09 | 0.186568E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221918E+09 | 0.141656E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.242644E+09 | 0.104158E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.193851E+09 | 86105095.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.168055E+09 | 61124596.62 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174244E+09 | 40022282.37 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190504E+09 | 29912362.72 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230812E+09 | 25883537.49 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210555E+09 | 55577852.42 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275168E+09 | 0.110519E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.262185E+09 | 0.133437E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253866E+09 | 0.160176E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266568E+10 | 0.113514E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.168055E+09 | 25883537.49 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275168E+09 | 0.186568E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241875E+09 | 0.186568E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221918E+09 | 0.141656E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.242644E+09 | 0.104158E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.193851E+09 | 86105095.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.168055E+09 | 61124596.62 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174244E+09 | 40022282.37 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190504E+09 | 29912362.72 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230812E+09 | 25883537.49 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210555E+09 | 55577852.42 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275168E+09 | 0.110519E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.262185E+09 | 0.133437E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253866E+09 | 0.160176E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266568E+10 | 0.113514E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.168055E+09 | 25883537.49 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275168E+09 | 0.186568E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.290619E+09 | 0.219793E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.266423E+09 | 0.166976E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.291059E+09 | 0.123236E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.232147E+09 | 0.101949E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.200881E+09 | 72491244.65 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207599E+09 | 47638701.67 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226917E+09 | 35621833.62 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.275069E+09 | 30927262.89 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251469E+09 | 66025122.00 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.329410E+09 | 0.130762E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.314172E+09 | 0.157778E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.304817E+09 | 0.189014E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.319058E+10 | 0.134221E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.200881E+09 | 30927262.89 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.329410E+09 | 0.219793E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 570.92 | 497.58 | 474.14 | 330.57 | 143.57 | 0.00 | 0.00 |
February | 579.08 | 423.35 | 442.53 | 296.64 | 145.89 | 0.00 | 0.00 |
March | 568.72 | 289.89 | 397.99 | 207.41 | 190.58 | 0.00 | 0.00 |
April | 469.91 | 242.89 | 298.07 | 97.03 | 201.04 | 0.00 | 0.00 |
May | 397.49 | 161.35 | 240.83 | 27.99 | 212.83 | 0.00 | 0.00 |
June | 433.23 | 101.07 | 222.67 | 12.39 | 210.28 | 0.00 | 0.00 |
July | 462.44 | 70.11 | 225.11 | 16.79 | 208.33 | 0.00 | 0.00 |
August | 557.83 | 59.21 | 268.77 | 50.21 | 218.56 | 0.00 | 0.00 |
September | 522.27 | 139.58 | 295.58 | 109.94 | 185.64 | 0.00 | 0.00 |
October | 654.99 | 284.37 | 428.51 | 277.59 | 150.92 | 0.00 | 0.00 |
November | 638.37 | 362.55 | 461.00 | 305.91 | 155.09 | 0.00 | 0.00 |
December | 599.17 | 424.22 | 467.37 | 328.80 | 138.57 | 0.00 | 0.00 |
Annual Sum or Average | 537.77 | 253.77 | 351.49 | 171.19 | 180.30 | 0.00 | 0.00 |
Minimum of Months | 397.49 | 59.21 | 222.67 | 12.39 | 138.57 | 0.00 | 0.00 |
Maximum of Months | 654.99 | 497.58 | 474.14 | 330.57 | 218.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.13 | 263.49 | 237.07 | 165.29 | 71.79 | 0.00 | 0.00 |
February | 284.73 | 226.06 | 221.27 | 148.32 | 72.95 | 0.00 | 0.00 |
March | 279.08 | 155.42 | 198.99 | 103.70 | 95.29 | 0.00 | 0.00 |
April | 231.21 | 128.11 | 149.03 | 48.51 | 100.52 | 0.00 | 0.00 |
May | 197.29 | 83.73 | 120.41 | 14.00 | 106.42 | 0.00 | 0.00 |
June | 216.78 | 51.61 | 111.33 | 6.20 | 105.14 | 0.00 | 0.00 |
July | 231.93 | 35.82 | 112.56 | 8.39 | 104.16 | 0.00 | 0.00 |
August | 279.90 | 29.87 | 134.38 | 25.10 | 109.28 | 0.00 | 0.00 |
September | 261.02 | 70.63 | 147.79 | 54.97 | 92.82 | 0.00 | 0.00 |
October | 325.24 | 147.48 | 214.25 | 138.79 | 75.46 | 0.00 | 0.00 |
November | 315.09 | 190.47 | 230.50 | 152.95 | 77.54 | 0.00 | 0.00 |
December | 294.94 | 226.76 | 233.69 | 164.40 | 69.29 | 0.00 | 0.00 |
Annual Sum or Average | 266.49 | 133.63 | 175.75 | 85.59 | 90.15 | 0.00 | 0.00 |
Minimum of Months | 197.29 | 29.87 | 111.33 | 6.20 | 69.29 | 0.00 | 0.00 |
Maximum of Months | 325.24 | 263.49 | 237.07 | 165.29 | 109.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.54 | 254.79 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 285.14 | 219.55 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 279.39 | 152.40 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 230.42 | 129.03 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 195.97 | 86.88 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.14 | 56.61 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.68 | 40.57 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 276.30 | 35.02 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.38 | 75.31 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 324.51 | 148.07 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 315.59 | 187.14 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 295.63 | 218.59 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 265.43 | 133.19 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 195.97 | 35.02 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 324.51 | 254.79 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 282.21 | 251.33 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 285.95 | 216.18 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 280.26 | 149.98 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 230.82 | 127.88 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.10 | 86.53 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.06 | 56.89 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.51 | 41.01 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 276.16 | 35.51 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.38 | 75.37 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 324.82 | 146.82 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 316.41 | 184.69 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 296.41 | 215.33 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 265.79 | 131.84 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.10 | 35.51 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 324.82 | 251.33 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 283.03 | 248.40 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 287.05 | 212.78 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 281.65 | 147.03 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 231.79 | 125.80 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.68 | 85.22 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.49 | 55.89 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.91 | 40.12 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 276.52 | 34.61 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.72 | 74.32 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 325.48 | 144.85 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 317.55 | 181.95 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 297.34 | 212.56 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 266.55 | 129.84 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.68 | 34.61 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 325.48 | 248.40 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 572.18 | 479.81 | 473.17 | 329.89 | 143.28 | 0.00 | 0.00 |
February | 580.46 | 408.60 | 441.63 | 296.03 | 145.59 | 0.00 | 0.00 |
March | 569.80 | 281.15 | 397.17 | 206.98 | 190.19 | 0.00 | 0.00 |
April | 468.31 | 241.44 | 297.45 | 96.83 | 200.63 | 0.00 | 0.00 |
May | 395.46 | 163.04 | 240.33 | 27.93 | 212.40 | 0.00 | 0.00 |
June | 429.46 | 105.52 | 222.21 | 12.37 | 209.85 | 0.00 | 0.00 |
July | 456.19 | 75.15 | 224.65 | 16.75 | 207.90 | 0.00 | 0.00 |
August | 553.27 | 63.96 | 268.22 | 50.10 | 218.11 | 0.00 | 0.00 |
September | 520.27 | 142.79 | 294.97 | 109.71 | 185.26 | 0.00 | 0.00 |
October | 654.14 | 280.84 | 427.63 | 277.02 | 150.61 | 0.00 | 0.00 |
November | 640.48 | 351.83 | 460.05 | 305.28 | 154.77 | 0.00 | 0.00 |
December | 600.58 | 411.17 | 466.41 | 328.13 | 138.29 | 0.00 | 0.00 |
Annual Sum or Average | 536.60 | 249.58 | 350.77 | 170.84 | 179.93 | 0.00 | 0.00 |
Minimum of Months | 395.46 | 63.96 | 222.21 | 12.37 | 138.29 | 0.00 | 0.00 |
Maximum of Months | 654.14 | 479.81 | 473.17 | 329.89 | 218.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.93 | 241.00 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 289.35 | 204.80 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 284.41 | 140.05 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 233.94 | 120.17 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 197.78 | 80.89 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.25 | 51.86 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 228.75 | 36.65 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 277.20 | 30.91 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.17 | 70.55 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 326.58 | 139.97 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 319.71 | 175.68 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 299.32 | 205.94 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 268.06 | 124.44 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 197.78 | 30.91 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 326.58 | 241.00 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.19 | 240.13 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 289.74 | 203.72 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 285.02 | 138.83 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 234.51 | 119.15 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 198.12 | 80.33 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.46 | 51.57 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 228.94 | 36.41 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 277.37 | 30.68 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.32 | 70.24 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 326.88 | 139.22 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 320.18 | 174.69 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 299.65 | 205.04 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 268.39 | 123.74 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 198.12 | 30.68 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 326.88 | 240.13 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.10 | 236.47 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 290.82 | 199.99 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 286.53 | 135.36 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 235.98 | 116.12 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 198.94 | 78.71 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.63 | 51.05 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 228.94 | 36.14 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 277.29 | 30.55 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.42 | 69.73 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 327.57 | 137.29 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 321.32 | 172.06 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 300.60 | 201.93 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 269.12 | 121.70 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 198.94 | 30.55 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 327.57 | 236.47 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.11 | 221.37 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 293.59 | 186.13 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 289.85 | 123.79 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 239.14 | 105.77 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 200.49 | 72.71 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.54 | 49.26 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 226.97 | 35.64 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 275.05 | 30.87 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.48 | 68.36 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 328.46 | 131.35 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 323.51 | 163.83 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 303.37 | 190.17 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 270.23 | 114.55 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 200.49 | 30.87 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 328.46 | 221.37 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152916E+10 | 0.133272E+10 | 0.126994E+10 | 0.885401E+09 | 0.384543E+09 | 0.00 | 0.00 |
February | 0.140092E+10 | 0.102417E+10 | 0.107058E+10 | 0.717638E+09 | 0.352940E+09 | 0.00 | 0.00 |
March | 0.152327E+10 | 0.776443E+09 | 0.106597E+10 | 0.555521E+09 | 0.510449E+09 | 0.00 | 0.00 |
April | 0.121800E+10 | 0.629564E+09 | 0.772587E+09 | 0.251494E+09 | 0.521094E+09 | 0.00 | 0.00 |
May | 0.106463E+10 | 0.432167E+09 | 0.645026E+09 | 74969553.42 | 0.570057E+09 | 0.00 | 0.00 |
June | 0.112292E+10 | 0.261969E+09 | 0.577156E+09 | 32116473.97 | 0.545040E+09 | 0.00 | 0.00 |
July | 0.123859E+10 | 0.187775E+09 | 0.602944E+09 | 44958910.78 | 0.557985E+09 | 0.00 | 0.00 |
August | 0.149409E+10 | 0.158584E+09 | 0.719872E+09 | 0.134475E+09 | 0.585397E+09 | 0.00 | 0.00 |
September | 0.135373E+10 | 0.361787E+09 | 0.766144E+09 | 0.284966E+09 | 0.481178E+09 | 0.00 | 0.00 |
October | 0.175433E+10 | 0.761651E+09 | 0.114771E+10 | 0.743490E+09 | 0.404223E+09 | 0.00 | 0.00 |
November | 0.165466E+10 | 0.939724E+09 | 0.119490E+10 | 0.792917E+09 | 0.401985E+09 | 0.00 | 0.00 |
December | 0.160481E+10 | 0.113623E+10 | 0.125181E+10 | 0.880660E+09 | 0.371153E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169591E+11 | 0.800278E+10 | 0.110846E+11 | 0.539860E+10 | 0.568604E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106463E+10 | 0.158584E+09 | 0.577156E+09 | 32116473.97 | 0.352940E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175433E+10 | 0.133272E+10 | 0.126994E+10 | 0.885401E+09 | 0.585397E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752975E+09 | 0.705729E+09 | 0.634972E+09 | 0.442700E+09 | 0.192272E+09 | 0.00 | 0.00 |
February | 0.688814E+09 | 0.546894E+09 | 0.535289E+09 | 0.358819E+09 | 0.176470E+09 | 0.00 | 0.00 |
March | 0.747495E+09 | 0.416284E+09 | 0.532985E+09 | 0.277760E+09 | 0.255225E+09 | 0.00 | 0.00 |
April | 0.599304E+09 | 0.332055E+09 | 0.386294E+09 | 0.125747E+09 | 0.260547E+09 | 0.00 | 0.00 |
May | 0.528419E+09 | 0.224263E+09 | 0.322513E+09 | 37484776.71 | 0.285028E+09 | 0.00 | 0.00 |
June | 0.561895E+09 | 0.133771E+09 | 0.288578E+09 | 16058236.99 | 0.272520E+09 | 0.00 | 0.00 |
July | 0.621203E+09 | 95944220.53 | 0.301472E+09 | 22479455.39 | 0.278992E+09 | 0.00 | 0.00 |
August | 0.749692E+09 | 80005495.89 | 0.359936E+09 | 67237285.33 | 0.292699E+09 | 0.00 | 0.00 |
September | 0.676565E+09 | 0.183068E+09 | 0.383072E+09 | 0.142483E+09 | 0.240589E+09 | 0.00 | 0.00 |
October | 0.871125E+09 | 0.394997E+09 | 0.573857E+09 | 0.371745E+09 | 0.202112E+09 | 0.00 | 0.00 |
November | 0.816704E+09 | 0.493710E+09 | 0.597451E+09 | 0.396458E+09 | 0.200992E+09 | 0.00 | 0.00 |
December | 0.789972E+09 | 0.607350E+09 | 0.625907E+09 | 0.440330E+09 | 0.185577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.840416E+10 | 0.421407E+10 | 0.554232E+10 | 0.269930E+10 | 0.284302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.528419E+09 | 80005495.89 | 0.288578E+09 | 16058236.99 | 0.176470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.871125E+09 | 0.705729E+09 | 0.634972E+09 | 0.442700E+09 | 0.292699E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754086E+09 | 0.682416E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.689816E+09 | 0.531127E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.748327E+09 | 0.408193E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.597246E+09 | 0.334445E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.524882E+09 | 0.232705E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.555044E+09 | 0.146728E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.609810E+09 | 0.108656E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.740041E+09 | 93786432.80 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672324E+09 | 0.195207E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.869160E+09 | 0.396600E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.818021E+09 | 0.485055E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.791826E+09 | 0.585464E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.837058E+10 | 0.420038E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524882E+09 | 93786432.80 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.869160E+09 | 0.682416E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755874E+09 | 0.673171E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.691779E+09 | 0.522987E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.750661E+09 | 0.401714E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.598285E+09 | 0.331476E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.525230E+09 | 0.231757E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.554838E+09 | 0.147448E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.609371E+09 | 0.109830E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.739672E+09 | 95123178.07 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672302E+09 | 0.195363E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.869985E+09 | 0.393248E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.820131E+09 | 0.478723E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.793892E+09 | 0.576734E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.838202E+10 | 0.415757E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.525230E+09 | 95123178.07 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.869985E+09 | 0.673171E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.758061E+09 | 0.665314E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.694437E+09 | 0.514759E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.754377E+09 | 0.393812E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.600809E+09 | 0.326073E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.526781E+09 | 0.228255E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.555949E+09 | 0.144863E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.610423E+09 | 0.107451E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.740643E+09 | 92712412.37 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.673204E+09 | 0.192633E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.871770E+09 | 0.387966E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.823101E+09 | 0.471622E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.796382E+09 | 0.569315E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.840594E+10 | 0.409478E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.526781E+09 | 92712412.37 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.871770E+09 | 0.665314E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.153254E+10 | 0.128512E+10 | 0.126734E+10 | 0.883584E+09 | 0.383754E+09 | 0.00 | 0.00 |
February | 0.140424E+10 | 0.988493E+09 | 0.106838E+10 | 0.716166E+09 | 0.352216E+09 | 0.00 | 0.00 |
March | 0.152616E+10 | 0.753022E+09 | 0.106378E+10 | 0.554381E+09 | 0.509402E+09 | 0.00 | 0.00 |
April | 0.121387E+10 | 0.625818E+09 | 0.771002E+09 | 0.250978E+09 | 0.520025E+09 | 0.00 | 0.00 |
May | 0.105921E+10 | 0.436673E+09 | 0.643703E+09 | 74815755.05 | 0.568887E+09 | 0.00 | 0.00 |
June | 0.111316E+10 | 0.273499E+09 | 0.575972E+09 | 32050587.74 | 0.543922E+09 | 0.00 | 0.00 |
July | 0.122186E+10 | 0.201274E+09 | 0.601707E+09 | 44866678.58 | 0.556840E+09 | 0.00 | 0.00 |
August | 0.148187E+10 | 0.171314E+09 | 0.718395E+09 | 0.134199E+09 | 0.584196E+09 | 0.00 | 0.00 |
September | 0.134855E+10 | 0.370113E+09 | 0.764572E+09 | 0.284381E+09 | 0.480191E+09 | 0.00 | 0.00 |
October | 0.175205E+10 | 0.752209E+09 | 0.114536E+10 | 0.741965E+09 | 0.403394E+09 | 0.00 | 0.00 |
November | 0.166012E+10 | 0.911956E+09 | 0.119245E+10 | 0.791290E+09 | 0.401160E+09 | 0.00 | 0.00 |
December | 0.160860E+10 | 0.110127E+10 | 0.124925E+10 | 0.878853E+09 | 0.370392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169222E+11 | 0.787077E+10 | 0.110619E+11 | 0.538753E+10 | 0.567438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105921E+10 | 0.171314E+09 | 0.575972E+09 | 32050587.74 | 0.352216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175205E+10 | 0.128512E+10 | 0.126734E+10 | 0.883584E+09 | 0.584196E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.763170E+09 | 0.645502E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.699993E+09 | 0.495460E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.761754E+09 | 0.375103E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.606377E+09 | 0.311489E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.529733E+09 | 0.216643E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.557940E+09 | 0.134429E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.612689E+09 | 98169471.98 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.742454E+09 | 82790026.04 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.674352E+09 | 0.182861E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.874719E+09 | 0.374889E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.828696E+09 | 0.455362E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.801707E+09 | 0.551602E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.845358E+10 | 0.392430E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529733E+09 | 82790026.04 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.874719E+09 | 0.645502E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.763866E+09 | 0.643178E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.700932E+09 | 0.492828E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.763401E+09 | 0.371842E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.607844E+09 | 0.308831E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.530642E+09 | 0.215162E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.558463E+09 | 0.133670E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.613188E+09 | 97507285.14 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.742897E+09 | 82160672.74 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.674738E+09 | 0.182072E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.875527E+09 | 0.372889E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.829912E+09 | 0.452799E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.802573E+09 | 0.549184E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.846398E+10 | 0.390212E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.530642E+09 | 82160672.74 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.875527E+09 | 0.643178E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766291E+09 | 0.633359E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.703544E+09 | 0.483823E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.767440E+09 | 0.362556E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.611658E+09 | 0.300979E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.532838E+09 | 0.210824E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.558908E+09 | 0.132316E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.613205E+09 | 96800162.42 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.742698E+09 | 81823922.73 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.675015E+09 | 0.180748E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.877350E+09 | 0.367730E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.832854E+09 | 0.445967E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.805132E+09 | 0.540855E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.848693E+10 | 0.383778E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.532838E+09 | 81823922.73 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.877350E+09 | 0.633359E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.774365E+09 | 0.592926E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.710258E+09 | 0.450285E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.776345E+09 | 0.331551E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.619848E+09 | 0.274159E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.536990E+09 | 0.194740E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.556087E+09 | 0.127683E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.607925E+09 | 95446109.82 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.736694E+09 | 82693982.84 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672579E+09 | 0.177180E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.879746E+09 | 0.351799E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.838541E+09 | 0.424652E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.812546E+09 | 0.509362E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.852192E+10 | 0.361248E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.536990E+09 | 82693982.84 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.879746E+09 | 0.592926E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346187E+09 | -222157697.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124029126.2 | 58.99 | 0.00 | 0.00 |
February | 0.312137E+09 | -202138072.4 | 0.00 | 0.00 | 672.00 | 0.00 | -109998498.5 | 58.99 | 0.00 | 0.00 |
March | 0.337736E+09 | -219833389.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117902833.5 | 58.99 | 0.00 | 0.00 |
April | 0.308166E+09 | -196554071.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111611625.6 | 58.99 | 0.00 | 0.00 |
May | 0.300287E+09 | -186946132.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113340630.9 | 58.99 | 0.00 | 0.00 |
June | 0.277059E+09 | -168311033.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108748204.8 | 58.99 | 0.00 | 0.00 |
July | 0.273540E+09 | -161587120.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111952705.1 | 58.99 | 0.00 | 0.00 |
August | 0.276120E+09 | -164384276.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111736148.7 | 58.99 | 0.00 | 0.00 |
September | 0.273578E+09 | -164895348.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108682230.0 | 58.99 | 0.00 | 0.00 |
October | 0.297426E+09 | -182722364.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114703252.8 | 59.00 | 0.00 | 0.00 |
November | 0.305881E+09 | -192113675.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113767494.9 | 58.99 | 0.00 | 0.00 |
December | 0.336167E+09 | -213748685.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122418512.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.364428E+10 | -0.227539E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136889E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273540E+09 | -222157697.7 | 0.00 | 0.00 | 672.00 | 0.00 | -124029126.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.346187E+09 | -161587120.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108682230.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.344019E+09 | -222150325.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121868362.5 | 58.99 | 0.00 | 0.00 |
February | 0.310076E+09 | -202135924.8 | 0.00 | 0.00 | 672.00 | 0.00 | -107939909.5 | 58.99 | 0.00 | 0.00 |
March | 0.335653E+09 | -219833395.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115819748.1 | 58.99 | 0.00 | 0.00 |
April | 0.306952E+09 | -196549856.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110402310.2 | 58.99 | 0.00 | 0.00 |
May | 0.299759E+09 | -186948157.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112810362.9 | 58.99 | 0.00 | 0.00 |
June | 0.276855E+09 | -168314997.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108540117.6 | 58.99 | 0.00 | 0.00 |
July | 0.273362E+09 | -161573703.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111788313.3 | 58.99 | 0.00 | 0.00 |
August | 0.276000E+09 | -164395498.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111604288.6 | 58.99 | 0.00 | 0.00 |
September | 0.273400E+09 | -164890509.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108509560.1 | 58.99 | 0.00 | 0.00 |
October | 0.296377E+09 | -182734703.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113642396.5 | 58.99 | 0.00 | 0.00 |
November | 0.304090E+09 | -192109388.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111980654.9 | 58.99 | 0.00 | 0.00 |
December | 0.333508E+09 | -213732808.5 | 0.00 | 0.00 | 744.00 | 0.00 | -119775445.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.363005E+10 | -0.227537E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135468E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273362E+09 | -222150325.2 | 0.00 | 0.00 | 672.00 | 0.00 | -121868362.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344019E+09 | -161573703.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107939909.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.318990E+09 | -195342904.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123646708.4 | 59.00 | 0.00 | 0.00 |
February | 0.287079E+09 | -177906638.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109171933.3 | 58.99 | 0.00 | 0.00 |
March | 0.312717E+09 | -196193547.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116523563.6 | 58.99 | 0.00 | 0.00 |
April | 0.282928E+09 | -172877772.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110050183.5 | 58.99 | 0.00 | 0.00 |
May | 0.277640E+09 | -165860744.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111779007.3 | 58.98 | 0.00 | 0.00 |
June | 0.256800E+09 | -149886813.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106913025.8 | 58.99 | 0.00 | 0.00 |
July | 0.251075E+09 | -141248390.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109826831.7 | 58.99 | 0.00 | 0.00 |
August | 0.256542E+09 | -146813402.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109728768.9 | 59.00 | 0.00 | 0.00 |
September | 0.252116E+09 | -144930719.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107185508.2 | 59.00 | 0.00 | 0.00 |
October | 0.274115E+09 | -160703829.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113411367.7 | 59.00 | 0.00 | 0.00 |
November | 0.282338E+09 | -169610762.6 | 0.00 | 0.00 | 720.00 | 0.00 | -112726744.3 | 58.99 | 0.00 | 0.00 |
December | 0.308165E+09 | -186571599.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121592913.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.336050E+10 | -0.200795E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135256E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.251075E+09 | -196193547.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123646708.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.318990E+09 | -141248390.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106913025.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319444E+09 | -195350439.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124093133.8 | 59.00 | 0.00 | 0.00 |
February | 0.287529E+09 | -177900608.5 | 0.00 | 0.00 | 672.00 | 0.00 | -109627901.1 | 58.99 | 0.00 | 0.00 |
March | 0.313117E+09 | -196191564.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116925669.7 | 58.99 | 0.00 | 0.00 |
April | 0.283110E+09 | -172886792.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110223054.3 | 58.99 | 0.00 | 0.00 |
May | 0.277694E+09 | -165850013.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111844268.0 | 58.99 | 0.00 | 0.00 |
June | 0.256751E+09 | -149890944.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106860338.1 | 58.99 | 0.00 | 0.00 |
July | 0.250997E+09 | -141266060.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109731228.8 | 58.99 | 0.00 | 0.00 |
August | 0.256461E+09 | -146812887.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109647902.3 | 59.00 | 0.00 | 0.00 |
September | 0.252105E+09 | -144930735.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107174259.3 | 59.00 | 0.00 | 0.00 |
October | 0.274311E+09 | -160702344.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113608489.8 | 59.00 | 0.00 | 0.00 |
November | 0.282721E+09 | -169639368.6 | 0.00 | 0.00 | 720.00 | 0.00 | -113081561.7 | 58.98 | 0.00 | 0.00 |
December | 0.308621E+09 | -186567560.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122053763.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.336286E+10 | -0.200799E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135487E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.250997E+09 | -196191564.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124093133.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.319444E+09 | -141266060.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106860338.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310319E+09 | -184643475.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125675765.6 | 58.99 | 0.00 | 0.00 |
February | 0.279488E+09 | -168231889.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111255882.1 | 58.99 | 0.00 | 0.00 |
March | 0.304280E+09 | -185656751.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118623636.1 | 58.98 | 0.00 | 0.00 |
April | 0.275110E+09 | -163585764.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111523970.6 | 58.99 | 0.00 | 0.00 |
May | 0.269579E+09 | -156846805.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112732054.8 | 58.99 | 0.00 | 0.00 |
June | 0.249462E+09 | -141866013.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107596019.3 | 58.98 | 0.00 | 0.00 |
July | 0.244029E+09 | -133589035.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110439480.5 | 58.99 | 0.00 | 0.00 |
August | 0.249281E+09 | -138937052.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110343879.8 | 58.99 | 0.00 | 0.00 |
September | 0.244976E+09 | -137153079.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107822502.9 | 59.00 | 0.00 | 0.00 |
October | 0.266560E+09 | -151906485.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114653663.2 | 58.99 | 0.00 | 0.00 |
November | 0.274786E+09 | -160205527.8 | 0.00 | 0.00 | 720.00 | 0.00 | -114580187.2 | 58.99 | 0.00 | 0.00 |
December | 0.299959E+09 | -176451948.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123507022.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.326783E+10 | -0.189907E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136875E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244029E+09 | -185656751.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125675765.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310319E+09 | -133589035.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107596019.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310285E+09 | -184643847.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125641363.3 | 58.99 | 0.00 | 0.00 |
February | 0.279516E+09 | -168230056.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111285789.5 | 58.99 | 0.00 | 0.00 |
March | 0.304393E+09 | -185660531.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118732056.7 | 58.98 | 0.00 | 0.00 |
April | 0.275204E+09 | -163573080.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111631015.2 | 59.00 | 0.00 | 0.00 |
May | 0.269663E+09 | -156841619.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112821342.8 | 58.99 | 0.00 | 0.00 |
June | 0.249567E+09 | -141812714.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107753977.3 | 59.00 | 0.00 | 0.00 |
July | 0.244144E+09 | -133584849.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110559148.5 | 58.99 | 0.00 | 0.00 |
August | 0.249419E+09 | -138947090.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110471820.4 | 58.99 | 0.00 | 0.00 |
September | 0.245057E+09 | -137165632.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107891470.5 | 58.99 | 0.00 | 0.00 |
October | 0.266645E+09 | -151901900.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114742699.4 | 58.99 | 0.00 | 0.00 |
November | 0.274862E+09 | -160202864.9 | 0.00 | 0.00 | 720.00 | 0.00 | -114658967.0 | 58.99 | 0.00 | 0.00 |
December | 0.299981E+09 | -176448200.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123532311.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.326873E+10 | -0.189901E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136972E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244144E+09 | -185660531.4 | 0.00 | 0.00 | 672.00 | 0.00 | -125641363.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310285E+09 | -133584849.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107753977.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310398E+09 | -184641410.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125756837.2 | 58.99 | 0.00 | 0.00 |
February | 0.279659E+09 | -168236947.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111422239.6 | 58.99 | 0.00 | 0.00 |
March | 0.304613E+09 | -185627610.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118985174.7 | 59.00 | 0.00 | 0.00 |
April | 0.275373E+09 | -163602467.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111770346.7 | 58.99 | 0.00 | 0.00 |
May | 0.269748E+09 | -156834356.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112913718.6 | 58.99 | 0.00 | 0.00 |
June | 0.249617E+09 | -141872347.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107744919.8 | 58.98 | 0.00 | 0.00 |
July | 0.244195E+09 | -133593435.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110601342.1 | 58.99 | 0.00 | 0.00 |
August | 0.249453E+09 | -138932871.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110520142.6 | 58.99 | 0.00 | 0.00 |
September | 0.245102E+09 | -137199953.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107902371.2 | 58.98 | 0.00 | 0.00 |
October | 0.266758E+09 | -151906317.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114852155.6 | 58.99 | 0.00 | 0.00 |
November | 0.275033E+09 | -160198232.4 | 0.00 | 0.00 | 720.00 | 0.00 | -114835039.7 | 58.99 | 0.00 | 0.00 |
December | 0.300105E+09 | -176450070.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123654958.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327006E+10 | -0.189910E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137096E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244195E+09 | -185627610.0 | 0.00 | 0.00 | 672.00 | 0.00 | -125756837.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310398E+09 | -133593435.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107744919.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123745E+11 | 58606.25 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705386E+10 | 58606.25 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977709E+09 | 58606.25 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162662E+09 | 58606.25 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87794338.00 | 30045.85 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112150E+10 | 58606.25 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532126E+10 | 58606.25 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123745E+11 | 58606.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373929E+10 | 30680.73 | 03-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210076E+10 | 30680.73 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181321E+09 | 18025.68 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14046507.15 | 3807.04 | 06-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6907778.43 | 3122.39 | 26-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188873E+09 | 30680.73 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113446E+10 | 30680.73 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373929E+10 | 30680.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473954E+10 | 30766.24 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262186E+10 | 30766.24 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298269E+09 | 12921.12 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36360660.51 | 6503.65 | 07-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24020915.29 | 6529.22 | 26-OCT-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351238E+09 | 24337.18 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181553E+10 | 30766.24 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473954E+10 | 30766.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495886E+10 | 30844.68 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273833E+10 | 30844.68 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342578E+09 | 17313.69 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40936809.16 | 6661.78 | 06-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31742587.81 | 4640.91 | 26-OCT-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403817E+09 | 26965.02 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199517E+10 | 30844.68 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495886E+10 | 30844.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.530026E+10 | 30627.39 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294803E+10 | 30627.39 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420301E+09 | 21893.23 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52917892.98 | 6432.05 | 06-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51679174.86 | 5643.47 | 26-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492537E+09 | 29990.79 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225835E+10 | 30627.39 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.530026E+10 | 30627.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103915E+11 | 55457.96 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582013E+10 | 55457.96 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.942295E+09 | 55457.96 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102869E+09 | 55457.96 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168214E+09 | 26959.11 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113115E+10 | 55457.96 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467908E+10 | 55457.96 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103915E+11 | 55457.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542856E+10 | 28538.37 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304791E+10 | 28538.37 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500755E+09 | 28538.37 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55366372.58 | 28538.37 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89062493.63 | 14615.72 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.588892E+09 | 28538.37 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244750E+10 | 28538.37 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542856E+10 | 28538.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550719E+10 | 28427.74 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310598E+10 | 28427.74 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.541183E+09 | 28427.74 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63097246.05 | 28427.74 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99437274.04 | 17068.38 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618306E+09 | 28427.74 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252380E+10 | 28427.74 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550719E+10 | 28427.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.587146E+10 | 28440.94 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334901E+10 | 28440.94 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677433E+09 | 28440.94 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94811769.94 | 28440.94 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130232E+09 | 24992.29 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715044E+09 | 28440.94 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279394E+10 | 28440.94 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.587146E+10 | 28440.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737613E+10 | 31360.93 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.443729E+10 | 31360.93 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116176E+10 | 31360.93 | 02-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249959E+09 | 31360.93 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1992254.97 | 2851.18 | 11-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234494E+09 | 31360.93 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101929E+10 | 31360.93 | 14-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366361E+10 | 31360.93 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737613E+10 | 31360.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.460531E+09 | 0.460061E+09 | 8052.95 | 26-FEB-15:10 | 8052.95 | 0.00 |
March | 0.00 | 0.00 | 0.203730E+10 | 0.162560E+10 | 15420.71 | 30-MAR-16:10 | 13329.62 | 0.00 |
April | 0.00 | 0.00 | 0.643716E+10 | 0.525786E+10 | 14560.01 | 17-APR-16:40 | 13716.18 | 0.00 |
May | 0.00 | 0.00 | 0.150505E+11 | 0.110285E+11 | 21490.88 | 30-MAY-17:00 | 14154.72 | 0.00 |
June | 0.00 | 0.00 | 0.271493E+11 | 0.188807E+11 | 51593.58 | 26-JUN-07:02 | 31429.52 | 0.00 |
July | 0.00 | 0.00 | 0.336550E+11 | 0.218511E+11 | 52611.67 | 27-JUL-07:02 | 27835.37 | 0.00 |
August | 0.00 | 0.00 | 0.368170E+11 | 0.232031E+11 | 52713.74 | 20-AUG-07:02 | 28600.16 | 0.00 |
September | 0.00 | 0.00 | 0.219565E+11 | 0.145273E+11 | 52375.71 | 17-SEP-07:02 | 28673.34 | 0.00 |
October | 0.00 | 0.00 | 0.784455E+10 | 0.543289E+10 | 51216.08 | 19-OCT-07:03 | 21864.34 | 0.00 |
November | 0.00 | 0.00 | 0.129933E+10 | 0.926655E+09 | 14618.74 | 05-NOV-16:07 | 10582.57 | 0.00 |
December | 0.00 | 0.00 | 97448152.63 | 69211145.42 | 6825.51 | 12-DEC-14:20 | 4830.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152805E+12 | 0.103263E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.368170E+11 | 0.232031E+11 | 52713.74 | 31429.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1946053.88 | 1598120.41 | 857.41 | 30-JAN-21:20 | 770.74 | 0.00 |
February | 0.00 | 0.00 | 0.392513E+09 | 0.390370E+09 | 23358.93 | 26-FEB-18:50 | 23358.93 | 0.00 |
March | 0.00 | 0.00 | 0.153204E+10 | 0.124662E+10 | 24738.29 | 04-MAR-19:38 | 18753.04 | 0.00 |
April | 0.00 | 0.00 | 0.464323E+10 | 0.379898E+10 | 25843.85 | 22-APR-18:02 | 14054.00 | 0.00 |
May | 0.00 | 0.00 | 0.901403E+10 | 0.677999E+10 | 25902.97 | 24-MAY-20:02 | 13586.23 | 0.00 |
June | 0.00 | 0.00 | 0.142316E+11 | 0.102469E+11 | 26118.32 | 29-JUN-07:03 | 19164.35 | 0.00 |
July | 0.00 | 0.00 | 0.170961E+11 | 0.114534E+11 | 26578.38 | 27-JUL-07:02 | 18019.08 | 0.00 |
August | 0.00 | 0.00 | 0.183602E+11 | 0.120026E+11 | 26666.73 | 20-AUG-07:02 | 18022.33 | 0.00 |
September | 0.00 | 0.00 | 0.117293E+11 | 0.805890E+10 | 26515.42 | 17-SEP-07:02 | 18075.94 | 0.00 |
October | 0.00 | 0.00 | 0.468669E+10 | 0.338109E+10 | 26578.50 | 19-OCT-07:03 | 12445.29 | 0.00 |
November | 0.00 | 0.00 | 0.108377E+10 | 0.788100E+09 | 25579.95 | 04-NOV-18:02 | 14537.23 | 0.00 |
December | 0.00 | 0.00 | 99247641.08 | 70105208.92 | 4558.32 | 12-DEC-14:00 | 3183.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.828707E+11 | 0.582187E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1946053.88 | 1598120.41 | 857.41 | 770.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183602E+11 | 0.120026E+11 | 26666.73 | 23358.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.244463E+09 | 0.244405E+09 | 4468.93 | 28-FEB-15:10 | 4468.93 | 0.00 |
March | 0.00 | 0.00 | 0.937140E+09 | 0.753633E+09 | 8222.33 | 30-MAR-14:00 | 6811.65 | 0.00 |
April | 0.00 | 0.00 | 0.294442E+10 | 0.246472E+10 | 7606.41 | 17-APR-14:00 | 7119.62 | 0.00 |
May | 0.00 | 0.00 | 0.629028E+10 | 0.468134E+10 | 15737.67 | 31-MAY-06:03 | 7349.97 | 0.00 |
June | 0.00 | 0.00 | 0.111537E+11 | 0.781908E+10 | 27300.88 | 26-JUN-06:02 | 16617.64 | 0.00 |
July | 0.00 | 0.00 | 0.133927E+11 | 0.871345E+10 | 27831.63 | 27-JUL-06:02 | 14461.39 | 0.00 |
August | 0.00 | 0.00 | 0.147858E+11 | 0.939650E+10 | 28221.65 | 21-AUG-06:02 | 13612.33 | 0.00 |
September | 0.00 | 0.00 | 0.874289E+10 | 0.587650E+10 | 28156.63 | 17-SEP-07:02 | 13290.85 | 0.00 |
October | 0.00 | 0.00 | 0.317547E+10 | 0.224492E+10 | 27216.93 | 19-OCT-06:03 | 11147.18 | 0.00 |
November | 0.00 | 0.00 | 0.556063E+09 | 0.416547E+09 | 6986.41 | 05-NOV-14:00 | 4678.43 | 0.00 |
December | 0.00 | 0.00 | 57131029.48 | 40421228.81 | 3907.51 | 12-DEC-14:00 | 2721.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.622800E+11 | 0.426515E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.147858E+11 | 0.939650E+10 | 28221.65 | 16617.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.222607E+09 | 0.222567E+09 | 4315.83 | 28-FEB-15:10 | 4315.83 | 0.00 |
March | 0.00 | 0.00 | 0.890325E+09 | 0.715780E+09 | 8123.87 | 30-MAR-14:00 | 6724.45 | 0.00 |
April | 0.00 | 0.00 | 0.288456E+10 | 0.241485E+10 | 7583.20 | 17-APR-14:00 | 7097.87 | 0.00 |
May | 0.00 | 0.00 | 0.624545E+10 | 0.464774E+10 | 15637.31 | 31-MAY-06:03 | 7299.44 | 0.00 |
June | 0.00 | 0.00 | 0.111793E+11 | 0.783906E+10 | 27378.82 | 26-JUN-06:02 | 16738.71 | 0.00 |
July | 0.00 | 0.00 | 0.134416E+11 | 0.875289E+10 | 27901.41 | 27-JUL-06:02 | 14512.19 | 0.00 |
August | 0.00 | 0.00 | 0.148394E+11 | 0.943776E+10 | 28297.88 | 21-AUG-06:02 | 13715.74 | 0.00 |
September | 0.00 | 0.00 | 0.874266E+10 | 0.587771E+10 | 28223.87 | 17-SEP-07:02 | 13318.13 | 0.00 |
October | 0.00 | 0.00 | 0.313208E+10 | 0.221130E+10 | 27282.46 | 19-OCT-06:03 | 11168.34 | 0.00 |
November | 0.00 | 0.00 | 0.501916E+09 | 0.375810E+09 | 6850.99 | 05-NOV-14:00 | 4578.14 | 0.00 |
December | 0.00 | 0.00 | 44541335.96 | 31706352.35 | 3579.93 | 12-DEC-14:00 | 2490.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.621244E+11 | 0.425272E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148394E+11 | 0.943776E+10 | 28297.88 | 16738.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6.63 | 5.87 | 0.01 | 31-JAN-14:50 | 0.01 | 0.00 |
February | 0.00 | 0.00 | 0.192025E+09 | 0.191994E+09 | 4022.56 | 28-FEB-15:10 | 4022.56 | 0.00 |
March | 0.00 | 0.00 | 0.798888E+09 | 0.642171E+09 | 7845.00 | 30-MAR-14:00 | 6473.84 | 0.00 |
April | 0.00 | 0.00 | 0.270675E+10 | 0.226591E+10 | 7394.26 | 17-APR-14:00 | 6914.34 | 0.00 |
May | 0.00 | 0.00 | 0.600055E+10 | 0.445821E+10 | 13344.21 | 31-MAY-06:03 | 6169.09 | 0.00 |
June | 0.00 | 0.00 | 0.109377E+11 | 0.764573E+10 | 27184.55 | 26-JUN-06:02 | 16511.17 | 0.00 |
July | 0.00 | 0.00 | 0.131686E+11 | 0.855138E+10 | 27707.47 | 27-JUL-06:02 | 14264.39 | 0.00 |
August | 0.00 | 0.00 | 0.145917E+11 | 0.924841E+10 | 28102.58 | 21-AUG-06:02 | 13517.91 | 0.00 |
September | 0.00 | 0.00 | 0.851422E+10 | 0.570614E+10 | 28028.39 | 17-SEP-07:02 | 13075.70 | 0.00 |
October | 0.00 | 0.00 | 0.298717E+10 | 0.209945E+10 | 27100.17 | 19-OCT-06:03 | 11044.04 | 0.00 |
November | 0.00 | 0.00 | 0.420260E+09 | 0.313663E+09 | 6559.28 | 05-NOV-14:00 | 4347.69 | 0.00 |
December | 0.00 | 0.00 | 33367880.61 | 23935127.72 | 3143.39 | 12-DEC-14:00 | 2181.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.603513E+11 | 0.411470E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.63 | 5.87 | 0.01 | 0.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145917E+11 | 0.924841E+10 | 28102.58 | 16511.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.292632E+09 | 0.292557E+09 | 7253.17 | 28-FEB-15:10 | 7253.17 | 0.00 |
March | 0.00 | 0.00 | 0.133971E+10 | 0.105154E+10 | 14274.12 | 30-MAR-14:10 | 11557.25 | 0.00 |
April | 0.00 | 0.00 | 0.462905E+10 | 0.378518E+10 | 13851.52 | 17-APR-14:30 | 12794.27 | 0.00 |
May | 0.00 | 0.00 | 0.105866E+11 | 0.768414E+10 | 21127.12 | 30-MAY-15:00 | 15143.94 | 0.00 |
June | 0.00 | 0.00 | 0.198663E+11 | 0.135868E+11 | 49313.04 | 26-JUN-07:02 | 29060.22 | 0.00 |
July | 0.00 | 0.00 | 0.237212E+11 | 0.151120E+11 | 49921.81 | 31-JUL-07:03 | 19797.22 | 0.00 |
August | 0.00 | 0.00 | 0.265203E+11 | 0.164418E+11 | 50981.96 | 20-AUG-08:62 | 24169.89 | 0.00 |
September | 0.00 | 0.00 | 0.151577E+11 | 0.990244E+10 | 50834.19 | 17-SEP-08:62 | 22853.92 | 0.00 |
October | 0.00 | 0.00 | 0.521747E+10 | 0.354776E+10 | 43860.21 | 19-OCT-07:03 | 18583.13 | 0.00 |
November | 0.00 | 0.00 | 0.620144E+09 | 0.458423E+09 | 12324.47 | 05-NOV-15:00 | 8178.42 | 0.00 |
December | 0.00 | 0.00 | 49900333.74 | 35247964.54 | 5156.42 | 12-DEC-14:00 | 3507.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108001E+12 | 0.718978E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.265203E+11 | 0.164418E+11 | 50981.96 | 29060.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.141912E+09 | 0.141886E+09 | 3690.55 | 28-FEB-15:10 | 3690.55 | 0.00 |
March | 0.00 | 0.00 | 0.663459E+09 | 0.522297E+09 | 7305.57 | 30-MAR-14:10 | 5921.43 | 0.00 |
April | 0.00 | 0.00 | 0.233992E+10 | 0.191915E+10 | 7147.81 | 17-APR-14:40 | 6625.64 | 0.00 |
May | 0.00 | 0.00 | 0.541186E+10 | 0.393720E+10 | 10923.72 | 30-MAY-15:00 | 7842.50 | 0.00 |
June | 0.00 | 0.00 | 0.101970E+11 | 0.698864E+10 | 25477.12 | 26-JUN-07:02 | 15004.81 | 0.00 |
July | 0.00 | 0.00 | 0.121787E+11 | 0.778030E+10 | 25789.34 | 31-JUL-07:03 | 10232.53 | 0.00 |
August | 0.00 | 0.00 | 0.136264E+11 | 0.847226E+10 | 26337.01 | 20-AUG-08:62 | 12446.48 | 0.00 |
September | 0.00 | 0.00 | 0.778601E+10 | 0.510206E+10 | 26256.72 | 17-SEP-08:62 | 11790.45 | 0.00 |
October | 0.00 | 0.00 | 0.266646E+10 | 0.181705E+10 | 20776.35 | 19-OCT-07:03 | 8794.69 | 0.00 |
November | 0.00 | 0.00 | 0.297705E+09 | 0.220379E+09 | 6349.21 | 05-NOV-15:00 | 4225.41 | 0.00 |
December | 0.00 | 0.00 | 23382089.70 | 16569280.43 | 2473.63 | 12-DEC-14:00 | 1685.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553329E+11 | 0.369178E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136264E+11 | 0.847226E+10 | 26337.01 | 15004.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.133797E+09 | 0.133775E+09 | 3591.98 | 28-FEB-15:10 | 3591.98 | 0.00 |
March | 0.00 | 0.00 | 0.636392E+09 | 0.500801E+09 | 7200.63 | 30-MAR-14:10 | 5829.34 | 0.00 |
April | 0.00 | 0.00 | 0.227395E+10 | 0.186592E+10 | 7064.18 | 17-APR-14:40 | 6545.27 | 0.00 |
May | 0.00 | 0.00 | 0.532099E+10 | 0.386862E+10 | 10846.16 | 30-MAY-15:00 | 7779.09 | 0.00 |
June | 0.00 | 0.00 | 0.101241E+11 | 0.693045E+10 | 25381.15 | 26-JUN-07:02 | 14918.76 | 0.00 |
July | 0.00 | 0.00 | 0.121069E+11 | 0.772689E+10 | 25694.33 | 31-JUL-07:03 | 10183.54 | 0.00 |
August | 0.00 | 0.00 | 0.135548E+11 | 0.841754E+10 | 26238.51 | 20-AUG-08:62 | 12372.13 | 0.00 |
September | 0.00 | 0.00 | 0.772561E+10 | 0.505662E+10 | 26159.05 | 17-SEP-08:62 | 11711.10 | 0.00 |
October | 0.00 | 0.00 | 0.262341E+10 | 0.178437E+10 | 19975.07 | 19-OCT-07:03 | 8432.93 | 0.00 |
November | 0.00 | 0.00 | 0.279529E+09 | 0.206320E+09 | 6247.84 | 05-NOV-15:00 | 4149.45 | 0.00 |
December | 0.00 | 0.00 | 21765090.68 | 15418512.61 | 2363.20 | 12-DEC-14:00 | 1608.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.548012E+11 | 0.365067E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135548E+11 | 0.841754E+10 | 26238.51 | 14918.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115956E+09 | 0.115945E+09 | 3369.14 | 28-FEB-15:10 | 3369.14 | 0.00 |
March | 0.00 | 0.00 | 0.572462E+09 | 0.450582E+09 | 6967.04 | 30-MAR-14:10 | 5626.38 | 0.00 |
April | 0.00 | 0.00 | 0.209949E+10 | 0.172914E+10 | 6864.07 | 17-APR-14:40 | 6354.97 | 0.00 |
May | 0.00 | 0.00 | 0.508844E+10 | 0.369712E+10 | 10711.07 | 30-MAY-15:00 | 7671.49 | 0.00 |
June | 0.00 | 0.00 | 0.100188E+11 | 0.684941E+10 | 25378.83 | 26-JUN-07:02 | 14839.75 | 0.00 |
July | 0.00 | 0.00 | 0.120413E+11 | 0.768546E+10 | 25702.40 | 31-JUL-07:03 | 10154.45 | 0.00 |
August | 0.00 | 0.00 | 0.135187E+11 | 0.839284E+10 | 26243.11 | 20-AUG-08:62 | 12334.44 | 0.00 |
September | 0.00 | 0.00 | 0.764317E+10 | 0.499956E+10 | 26160.77 | 17-SEP-08:62 | 11614.36 | 0.00 |
October | 0.00 | 0.00 | 0.252942E+10 | 0.171463E+10 | 17560.59 | 19-OCT-07:03 | 7355.04 | 0.00 |
November | 0.00 | 0.00 | 0.238833E+09 | 0.175103E+09 | 6021.28 | 05-NOV-15:00 | 3981.23 | 0.00 |
December | 0.00 | 0.00 | 17848685.66 | 12652692.24 | 2095.57 | 12-DEC-14:00 | 1424.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.538845E+11 | 0.358224E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135187E+11 | 0.839284E+10 | 26243.11 | 14839.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103861E+09 | 0.103861E+09 | 3362.76 | 28-FEB-15:10 | 3362.76 | 0.00 |
March | 0.00 | 0.00 | 0.506058E+09 | 0.404162E+09 | 7127.20 | 30-MAR-14:10 | 5807.14 | 0.00 |
April | 0.00 | 0.00 | 0.195688E+10 | 0.165596E+10 | 7018.37 | 17-APR-14:10 | 6504.11 | 0.00 |
May | 0.00 | 0.00 | 0.517709E+10 | 0.382478E+10 | 11234.25 | 30-MAY-15:00 | 8165.01 | 0.00 |
June | 0.00 | 0.00 | 0.107604E+11 | 0.746949E+10 | 28143.97 | 26-JUN-07:02 | 15093.49 | 0.00 |
July | 0.00 | 0.00 | 0.131128E+11 | 0.854963E+10 | 28392.07 | 27-JUL-07:02 | 13358.44 | 0.00 |
August | 0.00 | 0.00 | 0.147760E+11 | 0.936539E+10 | 29062.15 | 20-AUG-08:62 | 12630.62 | 0.00 |
September | 0.00 | 0.00 | 0.826137E+10 | 0.553166E+10 | 28622.73 | 17-SEP-08:62 | 12703.10 | 0.00 |
October | 0.00 | 0.00 | 0.261093E+10 | 0.179719E+10 | 11615.37 | 10-OCT-14:10 | 8351.59 | 0.00 |
November | 0.00 | 0.00 | 0.203647E+09 | 0.148802E+09 | 6026.28 | 05-NOV-15:00 | 4026.55 | 0.00 |
December | 0.00 | 0.00 | 13673481.34 | 9853417.50 | 1820.42 | 12-DEC-14:00 | 1252.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.574827E+11 | 0.388608E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.147760E+11 | 0.936539E+10 | 29062.15 | 15093.49 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188241E+10 | 0.42 | 2206.46 | 02-JAN-08:61 | 0.91 |
February | 0.160913E+10 | 0.40 | 2206.46 | 01-FEB-08:61 | 0.91 |
March | 0.162984E+10 | 0.38 | 2206.46 | 18-MAR-07:01 | 0.91 |
April | 0.155420E+10 | 0.37 | 2206.46 | 06-APR-07:01 | 0.91 |
May | 0.160136E+10 | 0.37 | 882.58 | 05-MAY-17:10 | 0.55 |
June | 0.157416E+10 | 0.37 | 2206.46 | 14-JUN-07:02 | 0.90 |
July | 0.167048E+10 | 0.38 | 2206.46 | 04-JUL-07:02 | 0.90 |
August | 0.169443E+10 | 0.38 | 2206.46 | 01-AUG-07:02 | 0.89 |
September | 0.156462E+10 | 0.37 | 2206.46 | 03-SEP-07:03 | 0.89 |
October | 0.160369E+10 | 0.37 | 2201.01 | 19-OCT-07:03 | 0.89 |
November | 0.157272E+10 | 0.38 | 2206.46 | 21-NOV-08:61 | 0.91 |
December | 0.172829E+10 | 0.39 | 2206.46 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.196853E+11 | 0.38 | |||
Minimum of Months | 0.155420E+10 | 0.37 | 882.58 | 0.55 | |
Maximum of Months | 0.188241E+10 | 0.42 | 2206.46 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.753777E+09 | 0.33 | 1210.71 | 03-JAN-08:61 | 0.94 |
February | 0.696447E+09 | 0.35 | 1210.71 | 02-FEB-08:61 | 0.94 |
March | 0.771097E+09 | 0.37 | 911.08 | 23-MAR-07:01 | 0.82 |
April | 0.742862E+09 | 0.37 | 574.42 | 06-APR-08:10 | 0.64 |
May | 0.762182E+09 | 0.38 | 511.04 | 31-MAY-07:03 | 0.58 |
June | 0.755818E+09 | 0.38 | 1210.71 | 14-JUN-07:02 | 0.93 |
July | 0.815189E+09 | 0.39 | 1210.71 | 04-JUL-07:02 | 0.93 |
August | 0.832199E+09 | 0.39 | 1210.71 | 01-AUG-07:02 | 0.93 |
September | 0.756319E+09 | 0.38 | 1210.71 | 03-SEP-07:03 | 0.93 |
October | 0.791337E+09 | 0.38 | 1210.71 | 19-OCT-07:03 | 0.93 |
November | 0.749484E+09 | 0.37 | 1210.71 | 22-NOV-08:61 | 0.94 |
December | 0.703259E+09 | 0.32 | 1210.71 | 02-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.912997E+10 | 0.37 | |||
Minimum of Months | 0.696447E+09 | 0.32 | 511.04 | 0.58 | |
Maximum of Months | 0.832199E+09 | 0.39 | 1210.71 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.815645E+09 | 0.34 | 1215.00 | 02-JAN-07:01 | 0.94 |
February | 0.698981E+09 | 0.33 | 1215.00 | 03-FEB-07:01 | 0.95 |
March | 0.724406E+09 | 0.32 | 792.17 | 19-MAR-07:02 | 0.77 |
April | 0.683208E+09 | 0.31 | 640.10 | 07-APR-07:03 | 0.68 |
May | 0.710370E+09 | 0.31 | 623.07 | 31-MAY-06:03 | 0.66 |
June | 0.700446E+09 | 0.31 | 1215.00 | 12-JUN-06:02 | 0.93 |
July | 0.730115E+09 | 0.31 | 1215.00 | 01-JUL-06:03 | 0.93 |
August | 0.756372E+09 | 0.32 | 1215.00 | 01-AUG-06:02 | 0.92 |
September | 0.687124E+09 | 0.31 | 1215.00 | 01-SEP-06:03 | 0.93 |
October | 0.704130E+09 | 0.31 | 1215.00 | 18-OCT-06:03 | 0.92 |
November | 0.690669E+09 | 0.31 | 1062.67 | 22-NOV-07:02 | 0.89 |
December | 0.742861E+09 | 0.32 | 1215.00 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.864433E+10 | 0.31 | |||
Minimum of Months | 0.683208E+09 | 0.31 | 623.07 | 0.66 | |
Maximum of Months | 0.815645E+09 | 0.34 | 1215.00 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.823204E+09 | 0.34 | 1218.94 | 01-JAN-08:62 | 0.94 |
February | 0.703851E+09 | 0.33 | 1218.94 | 03-FEB-07:01 | 0.95 |
March | 0.727788E+09 | 0.32 | 898.11 | 19-MAR-07:02 | 0.82 |
April | 0.685530E+09 | 0.31 | 645.54 | 06-APR-07:03 | 0.68 |
May | 0.712670E+09 | 0.31 | 617.53 | 31-MAY-06:03 | 0.65 |
June | 0.702600E+09 | 0.31 | 1218.94 | 12-JUN-06:02 | 0.93 |
July | 0.732426E+09 | 0.31 | 1218.94 | 01-JUL-06:03 | 0.93 |
August | 0.758665E+09 | 0.32 | 1218.94 | 01-AUG-06:02 | 0.92 |
September | 0.689279E+09 | 0.31 | 1218.94 | 01-SEP-06:03 | 0.93 |
October | 0.706595E+09 | 0.31 | 1218.94 | 18-OCT-06:03 | 0.92 |
November | 0.694134E+09 | 0.31 | 1126.95 | 22-NOV-07:02 | 0.91 |
December | 0.749420E+09 | 0.32 | 1218.94 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.868616E+10 | 0.32 | |||
Minimum of Months | 0.685530E+09 | 0.31 | 617.53 | 0.65 | |
Maximum of Months | 0.823204E+09 | 0.34 | 1218.94 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.824739E+09 | 0.34 | 1208.03 | 01-JAN-08:62 | 0.94 |
February | 0.702968E+09 | 0.33 | 1208.03 | 03-FEB-07:01 | 0.95 |
March | 0.723168E+09 | 0.32 | 1001.33 | 19-MAR-07:02 | 0.87 |
April | 0.679682E+09 | 0.31 | 635.43 | 06-APR-07:02 | 0.68 |
May | 0.706265E+09 | 0.31 | 492.49 | 31-MAY-06:03 | 0.57 |
June | 0.695400E+09 | 0.31 | 1208.03 | 12-JUN-06:02 | 0.93 |
July | 0.724090E+09 | 0.31 | 1208.03 | 01-JUL-06:03 | 0.93 |
August | 0.749560E+09 | 0.32 | 1208.03 | 01-AUG-06:02 | 0.92 |
September | 0.682698E+09 | 0.31 | 1208.03 | 03-SEP-07:03 | 0.92 |
October | 0.700739E+09 | 0.31 | 1208.03 | 19-OCT-06:03 | 0.92 |
November | 0.690086E+09 | 0.31 | 1192.96 | 22-NOV-07:02 | 0.94 |
December | 0.749271E+09 | 0.32 | 1208.03 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.862867E+10 | 0.32 | |||
Minimum of Months | 0.679682E+09 | 0.31 | 492.49 | 0.57 | |
Maximum of Months | 0.824739E+09 | 0.34 | 1208.03 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132804E+10 | 0.31 | 2053.67 | 01-JAN-09:01 | 0.91 |
February | 0.112296E+10 | 0.30 | 2053.67 | 01-FEB-08:61 | 0.91 |
March | 0.114175E+10 | 0.28 | 2053.67 | 18-MAR-07:01 | 0.91 |
April | 0.106691E+10 | 0.27 | 2053.67 | 06-APR-07:01 | 0.91 |
May | 0.110898E+10 | 0.28 | 821.47 | 01-MAY-15:20 | 0.54 |
June | 0.110176E+10 | 0.28 | 2053.67 | 12-JUN-07:03 | 0.90 |
July | 0.115736E+10 | 0.28 | 2053.67 | 01-JUL-07:03 | 0.90 |
August | 0.120490E+10 | 0.29 | 2053.67 | 01-AUG-07:02 | 0.90 |
September | 0.107535E+10 | 0.27 | 2053.67 | 04-SEP-08:62 | 0.89 |
October | 0.110113E+10 | 0.27 | 1816.49 | 19-OCT-07:03 | 0.85 |
November | 0.108975E+10 | 0.28 | 2053.67 | 21-NOV-08:61 | 0.91 |
December | 0.119520E+10 | 0.29 | 2053.67 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.136941E+11 | 0.28 | |||
Minimum of Months | 0.106691E+10 | 0.27 | 821.47 | 0.54 | |
Maximum of Months | 0.132804E+10 | 0.31 | 2053.67 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.715216E+09 | 0.32 | 1103.10 | 01-JAN-09:01 | 0.94 |
February | 0.604409E+09 | 0.31 | 1103.10 | 01-FEB-08:61 | 0.94 |
March | 0.613639E+09 | 0.29 | 1103.10 | 18-MAR-07:01 | 0.94 |
April | 0.573129E+09 | 0.28 | 1103.10 | 06-APR-07:01 | 0.94 |
May | 0.595672E+09 | 0.28 | 441.24 | 13-MAY-09:40 | 0.57 |
June | 0.591770E+09 | 0.29 | 1103.10 | 12-JUN-07:03 | 0.93 |
July | 0.621885E+09 | 0.29 | 1103.10 | 05-JUL-07:02 | 0.93 |
August | 0.647175E+09 | 0.30 | 1103.10 | 01-AUG-07:02 | 0.93 |
September | 0.577512E+09 | 0.28 | 1103.10 | 04-SEP-08:62 | 0.92 |
October | 0.591483E+09 | 0.28 | 877.17 | 19-OCT-07:03 | 0.83 |
November | 0.585502E+09 | 0.29 | 1103.10 | 21-NOV-08:61 | 0.94 |
December | 0.642903E+09 | 0.30 | 1103.10 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.736030E+10 | 0.29 | |||
Minimum of Months | 0.573129E+09 | 0.28 | 441.24 | 0.57 | |
Maximum of Months | 0.715216E+09 | 0.32 | 1103.10 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.713922E+09 | 0.32 | 1097.54 | 01-JAN-09:01 | 0.94 |
February | 0.602983E+09 | 0.31 | 1097.54 | 01-FEB-08:61 | 0.94 |
March | 0.611529E+09 | 0.29 | 1097.54 | 18-MAR-07:01 | 0.94 |
April | 0.570426E+09 | 0.28 | 1097.54 | 06-APR-07:01 | 0.94 |
May | 0.592671E+09 | 0.28 | 439.02 | 14-MAY-10:00 | 0.57 |
June | 0.588551E+09 | 0.29 | 1097.54 | 12-JUN-07:03 | 0.93 |
July | 0.618557E+09 | 0.29 | 1097.54 | 05-JUL-07:02 | 0.93 |
August | 0.643703E+09 | 0.30 | 1097.54 | 01-AUG-07:02 | 0.93 |
September | 0.574527E+09 | 0.28 | 1097.54 | 04-SEP-08:62 | 0.92 |
October | 0.588738E+09 | 0.28 | 834.65 | 19-OCT-07:03 | 0.81 |
November | 0.583287E+09 | 0.29 | 1097.54 | 21-NOV-08:61 | 0.94 |
December | 0.641652E+09 | 0.30 | 1097.54 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.733055E+10 | 0.29 | |||
Minimum of Months | 0.570426E+09 | 0.28 | 439.02 | 0.57 | |
Maximum of Months | 0.713922E+09 | 0.32 | 1097.54 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.722734E+09 | 0.32 | 1098.20 | 01-JAN-09:01 | 0.94 |
February | 0.608944E+09 | 0.31 | 1098.20 | 01-FEB-08:61 | 0.94 |
March | 0.615050E+09 | 0.29 | 1098.20 | 06-MAR-08:61 | 0.94 |
April | 0.571505E+09 | 0.28 | 1098.20 | 06-APR-07:01 | 0.94 |
May | 0.593029E+09 | 0.28 | 439.28 | 30-MAY-11:50 | 0.56 |
June | 0.588085E+09 | 0.29 | 1098.20 | 14-JUN-07:02 | 0.93 |
July | 0.618577E+09 | 0.29 | 1098.20 | 05-JUL-07:02 | 0.93 |
August | 0.643928E+09 | 0.30 | 1098.20 | 01-AUG-07:02 | 0.93 |
September | 0.574755E+09 | 0.28 | 1098.20 | 04-SEP-08:62 | 0.92 |
October | 0.589764E+09 | 0.28 | 1018.30 | 26-OCT-07:01 | 0.91 |
November | 0.585874E+09 | 0.29 | 1098.20 | 21-NOV-08:61 | 0.94 |
December | 0.648271E+09 | 0.30 | 1098.20 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.736051E+10 | 0.29 | |||
Minimum of Months | 0.571505E+09 | 0.28 | 439.28 | 0.56 | |
Maximum of Months | 0.722734E+09 | 0.32 | 1098.20 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.841838E+09 | 0.34 | 1244.82 | 01-JAN-09:01 | 0.94 |
February | 0.709993E+09 | 0.33 | 1244.82 | 01-FEB-08:61 | 0.94 |
March | 0.707044E+09 | 0.30 | 1244.82 | 02-MAR-08:62 | 0.94 |
April | 0.651270E+09 | 0.29 | 1244.82 | 06-APR-07:01 | 0.94 |
May | 0.672252E+09 | 0.28 | 565.83 | 11-MAY-07:03 | 0.62 |
June | 0.664290E+09 | 0.29 | 1244.82 | 25-JUN-08:62 | 0.93 |
July | 0.701301E+09 | 0.29 | 1244.82 | 05-JUL-07:02 | 0.92 |
August | 0.731500E+09 | 0.30 | 1244.82 | 01-AUG-07:02 | 0.92 |
September | 0.652343E+09 | 0.28 | 1244.82 | 05-SEP-07:02 | 0.92 |
October | 0.670620E+09 | 0.28 | 1244.82 | 26-OCT-07:01 | 0.94 |
November | 0.669592E+09 | 0.29 | 1244.82 | 14-NOV-08:62 | 0.94 |
December | 0.748703E+09 | 0.31 | 1244.82 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.842074E+10 | 0.30 | |||
Minimum of Months | 0.651270E+09 | 0.28 | 565.83 | 0.62 | |
Maximum of Months | 0.841838E+09 | 0.34 | 1244.82 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173654E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.217923E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.328845E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.551853E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.847319E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100914E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107606E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.702858E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.358634E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.191879E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175517E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.582193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.173654E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107606E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.754320E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.797973E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116467E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192833E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.304830E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.431614E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.505416E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.532095E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.363045E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.194457E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102684E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.729928E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297166E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.729928E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.532095E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.815645E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.765181E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.971930E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146030E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.231771E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348272E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.402100E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.433719E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.282831E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149482E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.837326E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.758318E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.240904E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.758318E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.433719E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.823204E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.764396E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.963618E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144832E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.231033E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349164E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.403508E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.435214E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.283120E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148740E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.826867E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.761506E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.240957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.761506E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.435214E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.824739E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.755537E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.935832E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.139877E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224615E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.342847E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.396326E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.428571E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.277259E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.144735E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.801678E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.758373E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.236185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.755537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.428571E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132804E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.120504E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150711E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.232426E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.387924E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.614368E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.708326E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.773569E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.485409E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.242809E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.125792E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120913E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.409555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120504E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.773569E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.715216E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.643590E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.791653E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119837E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198825E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.313797E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.361559E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.394967E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.248616E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125795E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.664841E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.649338E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.210986E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.643590E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.394967E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.713922E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.640003E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.782594E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.117920E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196335E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.311703E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.359466E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.392879E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246885E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124490E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.657860E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.647656E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.640003E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.392879E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.722734E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.641207E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.769732E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113701E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190845E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.309287E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.358009E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.392155E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.245053E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122382E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.649770E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.653224E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.641207E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.392155E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.841838E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.739125E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.845278E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118478E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.202030E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.336592E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.393591E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.432682E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268533E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.132746E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.724382E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.752528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.724382E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.432682E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.188241E+10 | 0.00 | 0.123745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160913E+10 | 0.460531E+09 | 0.705386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162984E+10 | 0.203730E+10 | 0.977709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155420E+10 | 0.643716E+10 | 0.162662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160136E+10 | 0.150505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157416E+10 | 0.271493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167048E+10 | 0.336550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169443E+10 | 0.368170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156462E+10 | 0.219565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160369E+10 | 0.784455E+10 | 87794338.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157272E+10 | 0.129933E+10 | 0.112150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172829E+10 | 97448152.63 | 0.532126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196853E+11 | 0.152805E+12 | 0.270993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188241E+10 | 0.368170E+11 | 0.123745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.753777E+09 | 1946053.88 | 0.373929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696447E+09 | 0.373098E+09 | 0.210076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771097E+09 | 0.148139E+10 | 0.181321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742862E+09 | 0.448005E+10 | 14046507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762182E+09 | 0.894354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.755818E+09 | 0.141482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.815189E+09 | 0.170900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.832199E+09 | 0.183602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.756319E+09 | 0.116582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791337E+09 | 0.460428E+10 | 6907778.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749484E+09 | 0.107247E+10 | 0.188873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703259E+09 | 99247641.08 | 0.113446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912997E+10 | 0.823126E+11 | 0.736566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696447E+09 | 1946053.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.832199E+09 | 0.183602E+11 | 0.373929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.815645E+09 | 0.00 | 0.473954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698981E+09 | 0.244463E+09 | 0.262186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724406E+09 | 0.937140E+09 | 0.298269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683208E+09 | 0.294442E+10 | 36360660.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.710370E+09 | 0.629028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.700446E+09 | 0.111537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.730115E+09 | 0.133927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.756372E+09 | 0.147858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687124E+09 | 0.874289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704130E+09 | 0.317547E+10 | 24020915.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690669E+09 | 0.556063E+09 | 0.351238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.742861E+09 | 57131029.48 | 0.181553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864433E+10 | 0.622800E+11 | 0.988682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.683208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.815645E+09 | 0.147858E+11 | 0.473954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.823204E+09 | 0.00 | 0.495886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703851E+09 | 0.222607E+09 | 0.273833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727788E+09 | 0.890325E+09 | 0.342578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.685530E+09 | 0.288456E+10 | 40936809.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712670E+09 | 0.624545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.702600E+09 | 0.111793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.732426E+09 | 0.134416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.758665E+09 | 0.148394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.689279E+09 | 0.874266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706595E+09 | 0.313208E+10 | 31742587.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.694134E+09 | 0.501916E+09 | 0.403817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749420E+09 | 44541335.96 | 0.199517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868616E+10 | 0.621244E+11 | 0.105114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.685530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.823204E+09 | 0.148394E+11 | 0.495886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.824739E+09 | 6.63 | 0.530026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.702968E+09 | 0.192025E+09 | 0.294803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723168E+09 | 0.798888E+09 | 0.420301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679682E+09 | 0.270675E+10 | 52917892.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.706265E+09 | 0.600055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695400E+09 | 0.109377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.724090E+09 | 0.131686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749560E+09 | 0.145917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682698E+09 | 0.851422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700739E+09 | 0.298717E+10 | 51679174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690086E+09 | 0.420260E+09 | 0.492537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749271E+09 | 33367880.61 | 0.225835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862867E+10 | 0.603513E+11 | 0.115241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679682E+09 | 6.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.824739E+09 | 0.145917E+11 | 0.530026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132804E+10 | 0.00 | 0.103915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112296E+10 | 0.292632E+09 | 0.582013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114175E+10 | 0.133971E+10 | 0.942295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106691E+10 | 0.462905E+10 | 0.102869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110898E+10 | 0.105866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110176E+10 | 0.198663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115736E+10 | 0.237212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120490E+10 | 0.265203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107535E+10 | 0.151577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110113E+10 | 0.521747E+10 | 0.168214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108975E+10 | 0.620144E+09 | 0.113115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119520E+10 | 49900333.74 | 0.467908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136941E+11 | 0.108001E+12 | 0.232352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132804E+10 | 0.265203E+11 | 0.103915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.715216E+09 | 0.00 | 0.542856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604409E+09 | 0.141912E+09 | 0.304791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.613639E+09 | 0.663459E+09 | 0.500755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573129E+09 | 0.233992E+10 | 55366372.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.595672E+09 | 0.541186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591770E+09 | 0.101970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.621885E+09 | 0.121787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647175E+09 | 0.136264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577512E+09 | 0.778601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591483E+09 | 0.266646E+10 | 89062493.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585502E+09 | 0.297705E+09 | 0.588892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642903E+09 | 23382089.70 | 0.244750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736030E+10 | 0.553329E+11 | 0.121580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715216E+09 | 0.136264E+11 | 0.542856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.713922E+09 | 0.00 | 0.550719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602983E+09 | 0.133797E+09 | 0.310598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611529E+09 | 0.636392E+09 | 0.541183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570426E+09 | 0.227395E+10 | 63097246.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592671E+09 | 0.532099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588551E+09 | 0.101241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.618557E+09 | 0.121069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643703E+09 | 0.135548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.574527E+09 | 0.772561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.588738E+09 | 0.262341E+10 | 99437274.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.583287E+09 | 0.279529E+09 | 0.618306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641652E+09 | 21765090.68 | 0.252380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733055E+10 | 0.548012E+11 | 0.124590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.570426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.713922E+09 | 0.135548E+11 | 0.550719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.722734E+09 | 0.00 | 0.587146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608944E+09 | 0.115956E+09 | 0.334901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615050E+09 | 0.572462E+09 | 0.677433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571505E+09 | 0.209949E+10 | 94811769.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593029E+09 | 0.508844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588085E+09 | 0.100188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.618577E+09 | 0.120413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643928E+09 | 0.135187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.574755E+09 | 0.764317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.589764E+09 | 0.252942E+10 | 0.130232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585874E+09 | 0.238833E+09 | 0.715044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648271E+09 | 17848685.66 | 0.279394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736051E+10 | 0.538845E+11 | 0.136319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.571505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722734E+09 | 0.135187E+11 | 0.587146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.841838E+09 | 0.00 | 0.737613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709993E+09 | 0.103861E+09 | 0.443729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707044E+09 | 0.506058E+09 | 0.116176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.651270E+09 | 0.195688E+10 | 0.249959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672252E+09 | 0.517709E+10 | 1992254.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664290E+09 | 0.107604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.701301E+09 | 0.131128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.731500E+09 | 0.147760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652343E+09 | 0.826137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670620E+09 | 0.261093E+10 | 0.234494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669592E+09 | 0.203647E+09 | 0.101929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748703E+09 | 13673481.34 | 0.366361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842074E+10 | 0.574827E+11 | 0.181445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.651270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.841838E+09 | 0.147760E+11 | 0.737613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.188241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160913E+10 | 0.00 | 0.00 | 0.00 | 0.127402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162984E+10 | 0.00 | 0.00 | 0.00 | 0.549386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155420E+10 | 0.00 | 0.00 | 0.00 | 0.173426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160136E+10 | 0.00 | 0.00 | 0.00 | 0.391717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157416E+10 | 0.00 | 0.00 | 0.00 | 0.689903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167048E+10 | 0.00 | 0.00 | 0.00 | 0.842096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169443E+10 | 0.00 | 0.00 | 0.00 | 0.906616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156462E+10 | 0.00 | 0.00 | 0.00 | 0.546396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160369E+10 | 0.00 | 0.00 | 0.00 | 0.198265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157272E+10 | 0.00 | 0.00 | 0.00 | 0.346066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172829E+10 | 0.00 | 0.00 | 0.00 | 26876352.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196853E+11 | 0.00 | 0.00 | 0.00 | 0.385339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188241E+10 | 0.00 | 0.00 | 0.00 | 0.906616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.753777E+09 | 0.00 | 0.00 | 0.00 | 543780.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696447E+09 | 0.00 | 0.00 | 0.00 | 0.101526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771097E+09 | 0.00 | 0.00 | 0.00 | 0.393571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742862E+09 | 0.00 | 0.00 | 0.00 | 0.118547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762182E+09 | 0.00 | 0.00 | 0.00 | 0.228612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.755818E+09 | 0.00 | 0.00 | 0.00 | 0.356033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.815189E+09 | 0.00 | 0.00 | 0.00 | 0.423897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.832199E+09 | 0.00 | 0.00 | 0.00 | 0.448875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.756319E+09 | 0.00 | 0.00 | 0.00 | 0.287413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791337E+09 | 0.00 | 0.00 | 0.00 | 0.115323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749484E+09 | 0.00 | 0.00 | 0.00 | 0.277358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703259E+09 | 0.00 | 0.00 | 0.00 | 26668912.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912997E+10 | 0.00 | 0.00 | 0.00 | 0.205867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696447E+09 | 0.00 | 0.00 | 0.00 | 543780.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.832199E+09 | 0.00 | 0.00 | 0.00 | 0.448875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.815645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698981E+09 | 0.00 | 0.00 | 0.00 | 66199197.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724406E+09 | 0.00 | 0.00 | 0.00 | 0.247523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683208E+09 | 0.00 | 0.00 | 0.00 | 0.777087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.710370E+09 | 0.00 | 0.00 | 0.00 | 0.160734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.700446E+09 | 0.00 | 0.00 | 0.00 | 0.278227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.730115E+09 | 0.00 | 0.00 | 0.00 | 0.329089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.756372E+09 | 0.00 | 0.00 | 0.00 | 0.358082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687124E+09 | 0.00 | 0.00 | 0.00 | 0.214119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704130E+09 | 0.00 | 0.00 | 0.00 | 0.790687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690669E+09 | 0.00 | 0.00 | 0.00 | 0.146657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.742861E+09 | 0.00 | 0.00 | 0.00 | 15456681.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864433E+10 | 0.00 | 0.00 | 0.00 | 0.154461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.683208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.815645E+09 | 0.00 | 0.00 | 0.00 | 0.358082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.823204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703851E+09 | 0.00 | 0.00 | 0.00 | 60544838.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727788E+09 | 0.00 | 0.00 | 0.00 | 0.235830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.685530E+09 | 0.00 | 0.00 | 0.00 | 0.762790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712670E+09 | 0.00 | 0.00 | 0.00 | 0.159766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.702600E+09 | 0.00 | 0.00 | 0.00 | 0.278904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.732426E+09 | 0.00 | 0.00 | 0.00 | 0.330266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.758665E+09 | 0.00 | 0.00 | 0.00 | 0.359347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.689279E+09 | 0.00 | 0.00 | 0.00 | 0.214193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706595E+09 | 0.00 | 0.00 | 0.00 | 0.780809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.694134E+09 | 0.00 | 0.00 | 0.00 | 0.132733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749420E+09 | 0.00 | 0.00 | 0.00 | 12085704.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868616E+10 | 0.00 | 0.00 | 0.00 | 0.154095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.685530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.823204E+09 | 0.00 | 0.00 | 0.00 | 0.359347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.824739E+09 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.702968E+09 | 0.00 | 0.00 | 0.00 | 52569149.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723168E+09 | 0.00 | 0.00 | 0.00 | 0.212664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679682E+09 | 0.00 | 0.00 | 0.00 | 0.719088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.706265E+09 | 0.00 | 0.00 | 0.00 | 0.153989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695400E+09 | 0.00 | 0.00 | 0.00 | 0.273307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.724090E+09 | 0.00 | 0.00 | 0.00 | 0.323917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749560E+09 | 0.00 | 0.00 | 0.00 | 0.353615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682698E+09 | 0.00 | 0.00 | 0.00 | 0.208990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700739E+09 | 0.00 | 0.00 | 0.00 | 0.746613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690086E+09 | 0.00 | 0.00 | 0.00 | 0.111592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749271E+09 | 0.00 | 0.00 | 0.00 | 9101674.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862867E+10 | 0.00 | 0.00 | 0.00 | 0.149898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679682E+09 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.824739E+09 | 0.00 | 0.00 | 0.00 | 0.353615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112296E+10 | 0.00 | 0.00 | 0.00 | 82080579.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114175E+10 | 0.00 | 0.00 | 0.00 | 0.365361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106691E+10 | 0.00 | 0.00 | 0.00 | 0.125735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110898E+10 | 0.00 | 0.00 | 0.00 | 0.277026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110176E+10 | 0.00 | 0.00 | 0.00 | 0.504192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115736E+10 | 0.00 | 0.00 | 0.00 | 0.592590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120490E+10 | 0.00 | 0.00 | 0.00 | 0.653079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107535E+10 | 0.00 | 0.00 | 0.00 | 0.377874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110113E+10 | 0.00 | 0.00 | 0.00 | 0.132696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108975E+10 | 0.00 | 0.00 | 0.00 | 0.168164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119520E+10 | 0.00 | 0.00 | 0.00 | 13928485.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136941E+11 | 0.00 | 0.00 | 0.00 | 0.272615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132804E+10 | 0.00 | 0.00 | 0.00 | 0.653079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.715216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604409E+09 | 0.00 | 0.00 | 0.00 | 39181593.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.613639E+09 | 0.00 | 0.00 | 0.00 | 0.178014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573129E+09 | 0.00 | 0.00 | 0.00 | 0.625241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.595672E+09 | 0.00 | 0.00 | 0.00 | 0.139258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591770E+09 | 0.00 | 0.00 | 0.00 | 0.254620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.621885E+09 | 0.00 | 0.00 | 0.00 | 0.299371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647175E+09 | 0.00 | 0.00 | 0.00 | 0.330249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577512E+09 | 0.00 | 0.00 | 0.00 | 0.190865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591483E+09 | 0.00 | 0.00 | 0.00 | 0.666465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585502E+09 | 0.00 | 0.00 | 0.00 | 79338354.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642903E+09 | 0.00 | 0.00 | 0.00 | 6435200.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736030E+10 | 0.00 | 0.00 | 0.00 | 0.137383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715216E+09 | 0.00 | 0.00 | 0.00 | 0.330249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.713922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602983E+09 | 0.00 | 0.00 | 0.00 | 37020013.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611529E+09 | 0.00 | 0.00 | 0.00 | 0.171065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570426E+09 | 0.00 | 0.00 | 0.00 | 0.608777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592671E+09 | 0.00 | 0.00 | 0.00 | 0.137068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588551E+09 | 0.00 | 0.00 | 0.00 | 0.252848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.618557E+09 | 0.00 | 0.00 | 0.00 | 0.297610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643703E+09 | 0.00 | 0.00 | 0.00 | 0.328508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.574527E+09 | 0.00 | 0.00 | 0.00 | 0.189432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.588738E+09 | 0.00 | 0.00 | 0.00 | 0.656167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.583287E+09 | 0.00 | 0.00 | 0.00 | 74572467.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641652E+09 | 0.00 | 0.00 | 0.00 | 6003867.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733055E+10 | 0.00 | 0.00 | 0.00 | 0.136083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.570426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.713922E+09 | 0.00 | 0.00 | 0.00 | 0.328508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.722734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608944E+09 | 0.00 | 0.00 | 0.00 | 32262946.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615050E+09 | 0.00 | 0.00 | 0.00 | 0.154682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571505E+09 | 0.00 | 0.00 | 0.00 | 0.565507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593029E+09 | 0.00 | 0.00 | 0.00 | 0.131542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588085E+09 | 0.00 | 0.00 | 0.00 | 0.250478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.618577E+09 | 0.00 | 0.00 | 0.00 | 0.296151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.643928E+09 | 0.00 | 0.00 | 0.00 | 0.327762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.574755E+09 | 0.00 | 0.00 | 0.00 | 0.187578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.589764E+09 | 0.00 | 0.00 | 0.00 | 0.634060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585874E+09 | 0.00 | 0.00 | 0.00 | 63896189.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648271E+09 | 0.00 | 0.00 | 0.00 | 4952863.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736051E+10 | 0.00 | 0.00 | 0.00 | 0.133905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.571505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722734E+09 | 0.00 | 0.00 | 0.00 | 0.327762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.841838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709993E+09 | 0.00 | 0.00 | 0.00 | 29132159.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707044E+09 | 0.00 | 0.00 | 0.00 | 0.138234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.651270E+09 | 0.00 | 0.00 | 0.00 | 0.533507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672252E+09 | 0.00 | 0.00 | 0.00 | 0.134805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664290E+09 | 0.00 | 0.00 | 0.00 | 0.270163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.701301E+09 | 0.00 | 0.00 | 0.00 | 0.323461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.731500E+09 | 0.00 | 0.00 | 0.00 | 0.359532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652343E+09 | 0.00 | 0.00 | 0.00 | 0.203299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670620E+09 | 0.00 | 0.00 | 0.00 | 0.656836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669592E+09 | 0.00 | 0.00 | 0.00 | 54789951.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748703E+09 | 0.00 | 0.00 | 0.00 | 3825857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842074E+10 | 0.00 | 0.00 | 0.00 | 0.143289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.651270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.841838E+09 | 0.00 | 0.00 | 0.00 | 0.359532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.663717E+10 | 0.00 | 0.00 | 51861.66 | 0.00 | 0.716266E+10 | 83930539.46 | 0.00 | 0.52 |
February | 0.505827E+10 | 1188254.82 | 0.00 | 1859790.28 | 0.00 | 0.413242E+10 | 0.881976E+09 | 0.00 | 0.59 |
March | 0.449392E+10 | 0.162421E+09 | 0.00 | 4464736.21 | 9164.39 | 0.402629E+09 | 0.257689E+10 | 0.00 | 0.67 |
April | 0.188350E+10 | 0.533972E+09 | 0.00 | 7679853.51 | 2797834.60 | 43295822.27 | 0.263004E+10 | 0.00 | 0.74 |
May | 0.252862E+09 | 0.264721E+10 | 0.00 | 5569418.90 | 0.00 | 0.00 | 0.187230E+10 | 0.00 | 0.73 |
June | 12509224.18 | 0.833294E+10 | 0.00 | 3026993.55 | 0.00 | 0.00 | 0.465032E+09 | 0.00 | 0.60 |
July | 0.00 | 0.118220E+11 | 0.00 | 838654.96 | 0.00 | 0.00 | 0.357931E+09 | 0.00 | 0.56 |
August | 0.00 | 0.132795E+11 | 0.00 | 138946.56 | 0.00 | 0.00 | 15821554.63 | 0.00 | 0.54 |
September | 52609419.03 | 0.580600E+10 | 0.00 | 4735760.75 | 0.00 | 0.00 | 0.158012E+10 | 0.00 | 0.66 |
October | 0.259954E+10 | 0.125285E+10 | 0.00 | 8591832.56 | 0.00 | 10873941.00 | 0.382685E+10 | 0.00 | 0.74 |
November | 0.522085E+10 | 26776585.54 | 0.00 | 5072341.90 | 2171631.25 | 0.167288E+09 | 0.327525E+10 | 0.00 | 0.70 |
December | 0.824136E+10 | 0.00 | 0.00 | 701512.59 | 0.00 | 0.207185E+10 | 0.591800E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.344526E+11 | 0.438649E+11 | 0.00 | 42731703.42 | 4978630.24 | 0.139910E+11 | 0.181579E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 51861.66 | 0.00 | 0.00 | 15821554.63 | 0.00 | 0.52 |
Maximum of Months | 0.824136E+10 | 0.132795E+11 | 0.00 | 8591832.56 | 2797834.60 | 0.716266E+10 | 0.382685E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287351E+10 | 0.00 | 0.00 | 140173.47 | 0.00 | 0.207101E+10 | 0.153330E+09 | 0.00 | 0.39 |
February | 0.181830E+10 | 647878.25 | 0.00 | 1542231.81 | 0.00 | 0.129103E+10 | 0.917742E+09 | 0.00 | 0.52 |
March | 0.155632E+10 | 88369912.24 | 0.00 | 3060580.84 | 0.00 | 30213740.10 | 0.192529E+10 | 0.00 | 0.63 |
April | 0.561318E+09 | 0.298211E+09 | 0.00 | 3553623.46 | 214446.26 | 1264441.95 | 0.136008E+10 | 0.00 | 0.66 |
May | 41052359.58 | 0.140304E+10 | 0.00 | 2308833.64 | 0.00 | 0.00 | 0.735430E+09 | 0.00 | 0.59 |
June | 597167.38 | 0.386504E+10 | 0.00 | 1060820.06 | 0.00 | 0.00 | 0.180761E+09 | 0.00 | 0.50 |
July | 0.00 | 0.533678E+10 | 0.00 | 306874.68 | 0.00 | 0.00 | 85683951.77 | 0.00 | 0.46 |
August | 0.00 | 0.593921E+10 | 0.00 | 14939.47 | 0.00 | 0.00 | 68938.32 | 0.00 | 0.45 |
September | 5663047.69 | 0.267735E+10 | 0.00 | 2049772.08 | 0.00 | 0.00 | 0.655817E+09 | 0.00 | 0.57 |
October | 0.859487E+09 | 0.620415E+09 | 0.00 | 4805637.03 | 0.00 | 0.00 | 0.227647E+10 | 0.00 | 0.71 |
November | 0.164363E+10 | 22486849.19 | 0.00 | 3709104.79 | 1174655.57 | 9856902.58 | 0.229856E+10 | 0.00 | 0.66 |
December | 0.324891E+10 | 0.00 | 0.00 | 641887.02 | 0.00 | 0.322686E+09 | 0.461379E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.126088E+11 | 0.202516E+11 | 0.00 | 23194478.34 | 1389101.83 | 0.372606E+10 | 0.110506E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 14939.47 | 0.00 | 0.00 | 68938.32 | 0.00 | 0.39 |
Maximum of Months | 0.324891E+10 | 0.593921E+10 | 0.00 | 4805637.03 | 1174655.57 | 0.207101E+10 | 0.229856E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233601E+10 | 0.00 | 0.00 | 33603.63 | 0.00 | 0.288873E+10 | 40216135.91 | 0.00 | 0.41 |
February | 0.187925E+10 | 768861.17 | 0.00 | 610084.42 | 0.00 | 0.159400E+10 | 0.327447E+09 | 0.00 | 0.48 |
March | 0.187498E+10 | 72048057.38 | 0.00 | 1397036.74 | 3592670.08 | 0.123902E+09 | 0.948879E+09 | 0.00 | 0.55 |
April | 0.830817E+09 | 0.254302E+09 | 0.00 | 1544240.01 | 9985303.49 | 6412258.29 | 0.780805E+09 | 0.00 | 0.57 |
May | 0.149656E+09 | 0.109678E+10 | 0.00 | 1880248.74 | 49159319.16 | 0.00 | 0.709951E+09 | 0.00 | 0.60 |
June | 20174350.07 | 0.327962E+10 | 0.00 | 763446.10 | 0.190468E+09 | 0.00 | 0.166655E+09 | 0.00 | 0.48 |
July | 4511167.97 | 0.435618E+10 | 0.00 | 535845.12 | 0.286820E+09 | 0.00 | 81696790.43 | 0.00 | 0.44 |
August | 34476.28 | 0.489367E+10 | 0.00 | 214609.01 | 0.318134E+09 | 0.00 | 23439766.42 | 0.00 | 0.44 |
September | 55828229.20 | 0.213181E+10 | 0.00 | 1482371.10 | 0.125418E+09 | 0.00 | 0.558568E+09 | 0.00 | 0.53 |
October | 0.116228E+10 | 0.473987E+09 | 0.00 | 2772936.76 | 30986882.21 | 3564539.91 | 0.133084E+10 | 0.00 | 0.61 |
November | 0.201447E+10 | 10276397.92 | 0.00 | 1967225.25 | 5336772.80 | 64296955.68 | 0.124684E+10 | 0.00 | 0.58 |
December | 0.299515E+10 | 0.00 | 0.00 | 301616.26 | 0.00 | 0.805335E+09 | 0.208348E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.133232E+11 | 0.165694E+11 | 0.00 | 13503263.14 | 0.101990E+10 | 0.548624E+10 | 0.642368E+10 | 0.00 | 0.51 |
Minimum of Months | 34476.28 | 0.00 | 0.00 | 33603.63 | 0.00 | 0.00 | 23439766.42 | 0.00 | 0.41 |
Maximum of Months | 0.299515E+10 | 0.489367E+10 | 0.00 | 2772936.76 | 0.318134E+09 | 0.288873E+10 | 0.133084E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213216E+10 | 0.00 | 0.00 | 21760.65 | 0.00 | 0.308937E+10 | 33037553.36 | 0.00 | 0.41 |
February | 0.183403E+10 | 771709.85 | 0.00 | 523624.33 | 0.00 | 0.167762E+10 | 0.260461E+09 | 0.00 | 0.47 |
March | 0.186967E+10 | 70341580.51 | 0.00 | 1271491.78 | 3495435.82 | 0.148391E+09 | 0.882604E+09 | 0.00 | 0.54 |
April | 0.843501E+09 | 0.249951E+09 | 0.00 | 1490033.68 | 9743483.88 | 6905000.85 | 0.751582E+09 | 0.00 | 0.57 |
May | 0.150708E+09 | 0.109235E+10 | 0.00 | 1854544.38 | 48969401.93 | 0.00 | 0.706407E+09 | 0.00 | 0.60 |
June | 20154967.99 | 0.328385E+10 | 0.00 | 770446.30 | 0.190400E+09 | 0.00 | 0.167351E+09 | 0.00 | 0.48 |
July | 4538160.78 | 0.436477E+10 | 0.00 | 547295.08 | 0.286753E+09 | 0.00 | 82441829.23 | 0.00 | 0.44 |
August | 20534.85 | 0.490355E+10 | 0.00 | 220395.43 | 0.318109E+09 | 0.00 | 23412411.23 | 0.00 | 0.44 |
September | 55925558.62 | 0.213198E+10 | 0.00 | 1481713.60 | 0.125292E+09 | 0.00 | 0.559074E+09 | 0.00 | 0.53 |
October | 0.116652E+10 | 0.470227E+09 | 0.00 | 2690466.72 | 30791696.75 | 4781635.81 | 0.130173E+10 | 0.00 | 0.61 |
November | 0.203922E+10 | 9552586.74 | 0.00 | 1808261.01 | 5756784.28 | 75592414.56 | 0.116798E+10 | 0.00 | 0.57 |
December | 0.289604E+10 | 0.00 | 0.00 | 263808.68 | 0.00 | 0.904317E+09 | 0.187679E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.130125E+11 | 0.165773E+11 | 0.00 | 12943841.65 | 0.101931E+10 | 0.590698E+10 | 0.612376E+10 | 0.00 | 0.51 |
Minimum of Months | 20534.85 | 0.00 | 0.00 | 21760.65 | 0.00 | 0.00 | 23412411.23 | 0.00 | 0.41 |
Maximum of Months | 0.289604E+10 | 0.490355E+10 | 0.00 | 2690466.72 | 0.318109E+09 | 0.308937E+10 | 0.130173E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180508E+10 | 0.00 | 0.00 | 7179.15 | 0.00 | 0.342433E+10 | 13524069.12 | 0.00 | 0.41 |
February | 0.167253E+10 | 765708.90 | 0.00 | 422711.23 | 0.00 | 0.186153E+10 | 0.196869E+09 | 0.00 | 0.47 |
March | 0.189379E+10 | 66951840.00 | 0.00 | 1042649.98 | 3329986.06 | 0.171376E+09 | 0.748913E+09 | 0.00 | 0.53 |
April | 0.890597E+09 | 0.240883E+09 | 0.00 | 1318482.85 | 9380834.33 | 24615649.60 | 0.631954E+09 | 0.00 | 0.56 |
May | 0.168961E+09 | 0.106864E+10 | 0.00 | 1681744.52 | 48490649.13 | 0.00 | 0.660901E+09 | 0.00 | 0.59 |
June | 22190512.46 | 0.325153E+10 | 0.00 | 706102.08 | 0.189791E+09 | 0.00 | 0.160734E+09 | 0.00 | 0.48 |
July | 4617890.17 | 0.432345E+10 | 0.00 | 572670.50 | 0.285728E+09 | 0.00 | 0.105898E+09 | 0.00 | 0.44 |
August | 24242.09 | 0.486226E+10 | 0.00 | 197703.11 | 0.317015E+09 | 0.00 | 24283150.89 | 0.00 | 0.44 |
September | 68478780.10 | 0.210061E+10 | 0.00 | 1376295.57 | 0.124436E+09 | 0.00 | 0.534871E+09 | 0.00 | 0.53 |
October | 0.120103E+10 | 0.456520E+09 | 0.00 | 2462417.38 | 30297588.59 | 6444496.13 | 0.119982E+10 | 0.00 | 0.59 |
November | 0.207482E+10 | 8271075.11 | 0.00 | 1529043.29 | 6214948.10 | 89432162.26 | 0.103558E+10 | 0.00 | 0.56 |
December | 0.266213E+10 | 0.00 | 0.00 | 208775.66 | 0.00 | 0.112281E+10 | 0.169360E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.124643E+11 | 0.163799E+11 | 0.00 | 11525775.32 | 0.101468E+10 | 0.670055E+10 | 0.548271E+10 | 0.00 | 0.50 |
Minimum of Months | 24242.09 | 0.00 | 0.00 | 7179.15 | 0.00 | 0.00 | 13524069.12 | 0.00 | 0.41 |
Maximum of Months | 0.266213E+10 | 0.486226E+10 | 0.00 | 2462417.38 | 0.317015E+09 | 0.342433E+10 | 0.119982E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724843E+10 | 0.00 | 0.00 | 0.38 |
February | 0.251875E+10 | 74358.17 | 0.00 | 663689.01 | 0.00 | 0.393530E+10 | 0.363562E+09 | 0.00 | 0.42 |
March | 0.342420E+10 | 0.102365E+09 | 0.00 | 1499480.68 | 0.00 | 0.402050E+09 | 0.113610E+10 | 0.00 | 0.46 |
April | 0.145807E+10 | 0.330288E+09 | 0.00 | 2225670.21 | 13817121.18 | 37838806.66 | 0.107712E+10 | 0.00 | 0.50 |
May | 0.175722E+09 | 0.191404E+10 | 0.00 | 2565391.47 | 39958108.65 | 0.00 | 0.109763E+10 | 0.00 | 0.51 |
June | 17099542.02 | 0.625329E+10 | 0.00 | 958915.37 | 0.101366E+09 | 0.00 | 0.230349E+09 | 0.00 | 0.43 |
July | 245431.71 | 0.825640E+10 | 0.00 | 871359.08 | 0.193886E+09 | 0.00 | 0.261630E+09 | 0.00 | 0.40 |
August | 0.00 | 0.938104E+10 | 0.00 | 141820.16 | 0.140528E+09 | 0.00 | 11507254.37 | 0.00 | 0.40 |
September | 64047568.28 | 0.386979E+10 | 0.00 | 2057452.59 | 99705844.55 | 0.00 | 0.882481E+09 | 0.00 | 0.46 |
October | 0.195619E+10 | 0.825045E+09 | 0.00 | 3922553.99 | 17212612.14 | 25625406.46 | 0.215247E+10 | 0.00 | 0.52 |
November | 0.382502E+10 | 7275765.25 | 0.00 | 2082155.61 | 12809908.06 | 0.201830E+09 | 0.166288E+10 | 0.00 | 0.48 |
December | 0.468784E+10 | 0.00 | 30288.71 | 223681.75 | 0.00 | 0.231082E+10 | 0.218363E+09 | 1266.87 | 0.39 |
Annual Sum or Average | 0.205795E+11 | 0.309396E+11 | 30288.71 | 17212169.91 | 0.619284E+09 | 0.141619E+11 | 0.909408E+10 | 1266.87 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.468784E+10 | 0.938104E+10 | 30288.71 | 3922553.99 | 0.193886E+09 | 0.724843E+10 | 0.215247E+10 | 1266.87 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375233E+10 | 0.00 | 0.00 | 0.38 |
February | 0.116454E+10 | 42617.57 | 0.00 | 308277.39 | 0.00 | 0.205585E+10 | 0.172249E+09 | 0.00 | 0.42 |
March | 0.170718E+10 | 51540088.20 | 0.00 | 690689.70 | 4961.69 | 0.218590E+09 | 0.533581E+09 | 0.00 | 0.46 |
April | 0.734755E+09 | 0.166665E+09 | 0.00 | 1072837.61 | 7080736.78 | 22206323.40 | 0.523282E+09 | 0.00 | 0.51 |
May | 97551051.06 | 0.957305E+09 | 0.00 | 1252260.79 | 20092573.30 | 0.00 | 0.546342E+09 | 0.00 | 0.51 |
June | 8426044.43 | 0.312886E+10 | 0.00 | 467844.62 | 50864656.37 | 0.00 | 0.116275E+09 | 0.00 | 0.43 |
July | 122327.37 | 0.412918E+10 | 0.00 | 436364.20 | 96638381.41 | 0.00 | 0.144093E+09 | 0.00 | 0.41 |
August | 0.00 | 0.469068E+10 | 0.00 | 68445.69 | 70045717.31 | 0.00 | 6231457.17 | 0.00 | 0.40 |
September | 33754177.36 | 0.193474E+10 | 0.00 | 1037933.09 | 49512307.21 | 0.00 | 0.448924E+09 | 0.00 | 0.47 |
October | 0.991041E+09 | 0.412407E+09 | 0.00 | 1955141.98 | 8565048.08 | 17338435.67 | 0.106573E+10 | 0.00 | 0.52 |
November | 0.186611E+10 | 3556409.35 | 0.00 | 990302.01 | 6500616.52 | 0.154363E+09 | 0.814964E+09 | 0.00 | 0.48 |
December | 0.220192E+10 | 0.00 | 12540.99 | 98519.30 | 0.00 | 0.128701E+10 | 0.102707E+09 | 809.28 | 0.39 |
Annual Sum or Average | 0.988905E+10 | 0.154750E+11 | 12540.99 | 8378616.38 | 0.309305E+09 | 0.750768E+10 | 0.447438E+10 | 809.28 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.220192E+10 | 0.469068E+10 | 12540.99 | 1955141.98 | 96638381.41 | 0.375233E+10 | 0.106573E+10 | 809.28 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.999312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383454E+10 | 0.00 | 0.00 | 0.38 |
February | 0.109800E+10 | 40490.38 | 0.00 | 285277.32 | 5060.27 | 0.212312E+10 | 0.162006E+09 | 0.00 | 0.42 |
March | 0.170124E+10 | 50424064.45 | 0.00 | 632929.01 | 20724.39 | 0.236306E+09 | 0.498437E+09 | 0.00 | 0.46 |
April | 0.741948E+09 | 0.162702E+09 | 0.00 | 1000816.06 | 7579968.70 | 22197592.04 | 0.499821E+09 | 0.00 | 0.50 |
May | 0.106386E+09 | 0.948958E+09 | 0.00 | 1215949.61 | 20068287.31 | 0.00 | 0.532253E+09 | 0.00 | 0.51 |
June | 8780969.87 | 0.311835E+10 | 0.00 | 457638.64 | 50835705.22 | 0.00 | 0.114590E+09 | 0.00 | 0.43 |
July | 122958.47 | 0.411751E+10 | 0.00 | 428440.47 | 96491098.51 | 0.00 | 0.144455E+09 | 0.00 | 0.41 |
August | 0.00 | 0.467836E+10 | 0.00 | 66677.09 | 69979195.11 | 0.00 | 6290788.11 | 0.00 | 0.40 |
September | 38022193.52 | 0.192607E+10 | 0.00 | 1012932.16 | 49369302.50 | 0.00 | 0.440062E+09 | 0.00 | 0.47 |
October | 0.100430E+10 | 0.408286E+09 | 0.00 | 1885761.71 | 8510317.55 | 20639224.31 | 0.103268E+10 | 0.00 | 0.52 |
November | 0.186224E+10 | 3326576.17 | 0.00 | 924021.85 | 6768761.39 | 0.179035E+09 | 0.772283E+09 | 0.00 | 0.47 |
December | 0.215395E+10 | 0.00 | 12546.63 | 88030.45 | 0.00 | 0.133612E+10 | 95237015.67 | 897.31 | 0.39 |
Annual Sum or Average | 0.971431E+10 | 0.154140E+11 | 12546.63 | 7998474.36 | 0.309628E+09 | 0.775196E+10 | 0.429811E+10 | 897.31 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.215395E+10 | 0.467836E+10 | 12546.63 | 1885761.71 | 96491098.51 | 0.383454E+10 | 0.103268E+10 | 897.31 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.717458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411058E+10 | 0.00 | 0.00 | 0.38 |
February | 0.909227E+09 | 41210.90 | 0.00 | 235084.69 | 122507.17 | 0.231151E+10 | 0.139816E+09 | 0.00 | 0.42 |
March | 0.166273E+10 | 47683084.65 | 0.00 | 497865.96 | 92865.82 | 0.304584E+09 | 0.415604E+09 | 0.00 | 0.45 |
April | 0.775691E+09 | 0.152214E+09 | 0.00 | 840224.89 | 8911687.96 | 29066531.10 | 0.421783E+09 | 0.00 | 0.49 |
May | 0.117411E+09 | 0.919977E+09 | 0.00 | 1118702.39 | 21535259.85 | 0.00 | 0.507823E+09 | 0.00 | 0.51 |
June | 9267838.25 | 0.310023E+10 | 0.00 | 432982.88 | 50817827.50 | 0.00 | 0.110462E+09 | 0.00 | 0.43 |
July | 4578985.29 | 0.410341E+10 | 0.00 | 401572.38 | 96327198.78 | 0.00 | 0.142546E+09 | 0.00 | 0.41 |
August | 0.00 | 0.466810E+10 | 0.00 | 62170.47 | 70004881.30 | 0.00 | 6397276.47 | 0.00 | 0.40 |
September | 45174354.62 | 0.191282E+10 | 0.00 | 945616.66 | 49198742.74 | 0.00 | 0.421678E+09 | 0.00 | 0.46 |
October | 0.104637E+10 | 0.398640E+09 | 0.00 | 1730183.54 | 8498950.27 | 33968538.71 | 0.940819E+09 | 0.00 | 0.51 |
November | 0.182175E+10 | 2734470.61 | 0.00 | 780241.04 | 7485391.74 | 0.260687E+09 | 0.683222E+09 | 0.00 | 0.47 |
December | 0.195552E+10 | 0.00 | 12480.00 | 66168.80 | 0.00 | 0.154342E+10 | 72097370.60 | 1243.99 | 0.38 |
Annual Sum or Average | 0.906517E+10 | 0.153059E+11 | 12480.00 | 7110813.69 | 0.312995E+09 | 0.859381E+10 | 0.386225E+10 | 1243.99 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.195552E+10 | 0.466810E+10 | 12480.00 | 1730183.54 | 96327198.78 | 0.411058E+10 | 0.940819E+09 | 1243.99 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450752E+10 | 0.00 | 0.00 | 0.38 |
February | 0.597120E+09 | 95441.65 | 0.00 | 187926.86 | 150732.59 | 0.258550E+10 | 0.126868E+09 | 0.00 | 0.42 |
March | 0.146428E+10 | 43866761.08 | 0.00 | 320782.79 | 287472.81 | 0.544170E+09 | 0.304858E+09 | 0.00 | 0.45 |
April | 0.733180E+09 | 0.137311E+09 | 0.00 | 735035.79 | 11050268.33 | 67330779.89 | 0.396385E+09 | 0.00 | 0.52 |
May | 0.132028E+09 | 0.906554E+09 | 0.00 | 996972.51 | 21490915.26 | 0.00 | 0.493030E+09 | 0.00 | 0.52 |
June | 15371624.86 | 0.307902E+10 | 0.00 | 474335.79 | 50315021.49 | 0.00 | 0.110888E+09 | 0.00 | 0.44 |
July | 8748305.43 | 0.414869E+10 | 0.00 | 361116.80 | 96138671.41 | 0.00 | 0.159886E+09 | 0.00 | 0.41 |
August | 135258.36 | 0.470737E+10 | 0.00 | 121470.50 | 69951536.40 | 0.00 | 13907635.59 | 0.00 | 0.40 |
September | 54781783.25 | 0.193053E+10 | 0.00 | 940610.23 | 48723126.26 | 0.00 | 0.405913E+09 | 0.00 | 0.47 |
October | 0.976426E+09 | 0.395201E+09 | 0.00 | 1735702.90 | 8161041.69 | 0.111252E+09 | 0.964280E+09 | 0.00 | 0.54 |
November | 0.156382E+10 | 2326555.47 | 759014.30 | 681384.48 | 3994135.36 | 0.534149E+09 | 0.626698E+09 | 342.84 | 0.48 |
December | 0.123898E+10 | 0.00 | 0.00 | 48493.72 | 0.00 | 0.223049E+10 | 59323251.46 | 0.00 | 0.38 |
Annual Sum or Average | 0.707547E+10 | 0.153510E+11 | 759014.30 | 6603832.38 | 0.310263E+09 | 0.105804E+11 | 0.366204E+10 | 342.84 | 0.45 |
Minimum of Months | 135258.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.156382E+10 | 0.470737E+10 | 759014.30 | 1735702.90 | 96138671.41 | 0.450752E+10 | 0.964280E+09 | 342.84 | 0.54 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148078E+12 | 0.294787E+11 | 0.00 | 0.660563E+11 | 0.164243E+11 |
February | 0.157462E+12 | 0.208781E+11 | 0.00 | 0.469215E+11 | 0.122340E+11 |
March | 0.252652E+12 | 0.130681E+11 | 0.00 | 0.336528E+11 | 0.140710E+11 |
April | 0.300532E+12 | 0.491427E+10 | 0.00 | 0.163006E+11 | 0.419027E+11 |
May | 0.342810E+12 | -0.354046E+10 | 0.00 | -0.390859E+10 | 0.933314E+11 |
June | 0.341361E+12 | -0.157382E+11 | 0.00 | -0.395805E+11 | 0.169705E+12 |
July | 0.330705E+12 | -0.212755E+11 | 0.00 | -0.547434E+11 | 0.204499E+12 |
August | 0.304572E+12 | -0.238856E+11 | 0.00 | -0.632128E+11 | 0.225647E+12 |
September | 0.225939E+12 | -0.926252E+10 | 0.00 | -0.201043E+11 | 0.132461E+12 |
October | 0.202451E+12 | 0.628026E+10 | 0.00 | 0.235065E+11 | 0.470990E+11 |
November | 0.133154E+12 | 0.142038E+11 | 0.00 | 0.394854E+11 | 0.861402E+10 |
December | 0.116782E+12 | 0.222744E+11 | 0.00 | 0.501926E+11 | 0.774182E+10 |
Annual Sum or Average | 0.285650E+13 | 0.373954E+11 | 0.00 | 0.945661E+11 | 0.973731E+12 |
Minimum of Months | 0.116782E+12 | -0.238856E+11 | 0.00 | -0.632128E+11 | 0.774182E+10 |