Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:36:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1143.26 | 546.93 | 546.93 |
Net Site Energy | 1143.26 | 546.93 | 546.93 |
Total Source Energy | 3584.74 | 1714.92 | 1714.92 |
Net Source Energy | 3584.74 | 1714.92 | 1714.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 364.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 105.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1125.99 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 364.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 105.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 59.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 364.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 105.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.30 | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 538.67 | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.30 | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 538.67 | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1125.994 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1125.994 | 100.00 |
Total On-Site and Utility Electric Sources | 1125.994 | 100.00 |
Total Electricity End Uses | 1125.994 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1874.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-12:09 | 05-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 99641.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72380.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5413.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 123501.72 | 99641.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 99641.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72380.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5413.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1152.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 334.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3566.02 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 551.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1705.97 | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 551.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1705.97 | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.22 |
SMSTORE1 DIRECT AIR | 1.17 |
SMSTORE2 DIRECT AIR | 1.17 |
SMSTORE3 DIRECT AIR | 1.18 |
SMSTORE4 DIRECT AIR | 1.17 |
LGSTORE2 DIRECT AIR | 2.05 |
SMSTORE5 DIRECT AIR | 1.08 |
SMSTORE6 DIRECT AIR | 1.07 |
SMSTORE7 DIRECT AIR | 1.07 |
SMSTORE8 DIRECT AIR | 1.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 1.00 | 1.00 | 2.22 |
PSZ-AC_2:2 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
PSZ-AC_3:3 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
PSZ-AC_4:4 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.00 | 1.000000 | 1.18 |
PSZ-AC_5:5 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
PSZ-AC_6:6 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 1.00 | 1.00 | 2.05 |
PSZ-AC_7:7 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.000000 | 1.08 |
PSZ-AC_8:8 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_9:9 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_10:10 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.000000 | 1.23 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.22 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.17 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.17 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.18 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.17 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.05 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.08 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.23 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.22 | 2373.40 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1295.73 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1298.71 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1302.46 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1292.24 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.05 | 2195.82 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1191.13 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1185.90 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1189.36 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1364.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.22 | 2.22 | 2.22 | 1.46 | 55078.92 | 58873.29 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.772410 | 29061.79 | 30836.92 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.774190 | 29128.74 | 30898.50 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.776425 | 29212.83 | 30975.85 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.770330 | 28983.53 | 30764.93 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.05 | 2.05 | 2.05 | 1.35 | 50957.95 | 55082.67 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.710058 | 26715.81 | 28679.12 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.706937 | 26598.37 | 28571.10 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.709001 | 26676.03 | 28642.53 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.813326 | 30259.16 | 32253.14 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.22 | 1.11 | 1.48 | 55078.92 | 27539.46 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.17 | 0.585159 | 0.780213 | 29061.79 | 14530.90 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.17 | 0.586507 | 0.782007 | 29128.74 | 14564.37 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.18 | 0.588200 | 0.784267 | 29212.83 | 14606.42 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.17 | 0.583583 | 0.778113 | 28983.53 | 14491.76 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.05 | 1.03 | 1.37 | 50957.95 | 25478.97 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.08 | 0.537923 | 0.717233 | 26715.81 | 13357.91 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.07 | 0.535558 | 0.714080 | 26598.37 | 13299.18 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.07 | 0.537122 | 0.716160 | 26676.03 | 13338.01 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.23 | 0.616156 | 0.821540 | 30259.16 | 15129.58 | 0.704850 | 0.704850 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58873.29 |
PSZ-AC_2:2 HEATING COIL | 30836.92 |
PSZ-AC_3:3 HEATING COIL | 30898.50 |
PSZ-AC_4:4 HEATING COIL | 30975.85 |
PSZ-AC_5:5 HEATING COIL | 30764.93 |
PSZ-AC_6:6 HEATING COIL | 55082.67 |
PSZ-AC_7:7 HEATING COIL | 28679.12 |
PSZ-AC_8:8 HEATING COIL | 28571.10 |
PSZ-AC_9:9 HEATING COIL | 28642.53 |
PSZ-AC_10:10 HEATING COIL | 32253.14 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7374 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.122 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.30765797E-12 | 0.12488460E-14 | -0.98016509E-13 | 0.16213517E-15 |
23 | 6 | 0.29136061E-07 | 0.20843390E-09 | 0.66705746E-08 | -0.13769473E-12 |
24 | 5 | -0.19246395E-03 | 0.17782628E-05 | -0.98963596E-04 | 0.65927994E-08 |
25 | 4 | 0.29490032 | 0.86304157E-03 | 0.10067388 | -0.33959898E-04 |
26 | 3 | -7.3208521 | 0.26669396E-01 | -2.3550924 | 0.29276239E-01 |
27 | 2 | 41.050957 | 0.94592451E-01 | 15.331444 | -0.33534308 |
28 | 1 | -80.683573 | 0.42595651E-01 | -29.201163 | 1.0815555 |
29 | 0 | 46.824338 | 0.85510937E-03 | 16.289814 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 35 | 1 | VerySmooth | 3.053 | 3.053 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.38652E-002 | 0.16139 | 0.60641 | 0.60641 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.79195E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 25154.31526 | 30185.17831 | 1.84836 | 2.21803 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 16085.96145 | 19303.15374 | 0.69402 | 0.83282 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 13272.20948 | 15926.65138 | 0.97527 | 1.17032 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7968.75949 | 9562.51139 | 0.34381 | 0.41257 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13302.83148 | 15963.39777 | 0.97751 | 1.17301 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8034.47194 | 9641.36633 | 0.34664 | 0.41597 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13341.23469 | 16009.48163 | 0.98033 | 1.17640 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8101.68032 | 9722.01639 | 0.34954 | 0.41945 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13236.52126 | 15883.82551 | 0.97264 | 1.16717 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8246.00946 | 9895.21135 | 0.35577 | 0.42692 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 23272.86806 | 27927.44168 | 1.71006 | 2.05208 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 15528.80251 | 18634.56301 | 0.66998 | 0.80398 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 12200.93017 | 14641.11621 | 0.89654 | 1.07585 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8446.09650 | 10135.31581 | 0.36440 | 0.43728 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 12147.30017 | 14576.76020 | 0.89260 | 1.07112 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8451.07115 | 10141.28538 | 0.36461 | 0.43754 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 12182.90792 | 14619.48950 | 0.89520 | 1.07424 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8695.16309 | 10434.19570 | 0.37515 | 0.45017 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13977.84490 | 16773.41388 | 1.02693 | 1.23231 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65356E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 10225.14950 | 12270.17940 | 0.44115 | 0.52938 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 34702.08 | 2.21803 | 2.21803 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 27234.53 | 0.83282 | 0.83282 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18172.24 | 1.17032 | 1.17032 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13529.48 | 0.41257 | 0.41257 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18205.29 | 1.17301 | 1.17301 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13607.19 | 0.41597 | 0.41597 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18249.90 | 1.17640 | 1.17640 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13686.67 | 0.41945 | 0.41945 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18126.42 | 1.16717 | 1.16717 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13857.34 | 0.42692 | 0.42692 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 32472.17 | 2.05208 | 2.05208 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 26575.73 | 0.80398 | 0.80398 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16902.12 | 1.07585 | 1.07585 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 14093.94 | 0.43728 | 0.43728 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16838.70 | 1.07112 | 1.07112 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 14099.83 | 0.43754 | 0.43754 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16878.52 | 1.07424 | 1.07424 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 14388.47 | 0.45017 | 0.45017 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18907.14 | 1.23231 | 1.23231 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 16197.66 | 0.52938 | 0.52938 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.21803 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17032 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17301 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17640 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16717 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.05208 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07585 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07112 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07424 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23231 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.21803 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.21803 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.21803 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.21803 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.21803 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.21803 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17032 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17032 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17032 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17032 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17032 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17032 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17301 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17301 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17301 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17301 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17301 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17301 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17640 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17640 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17640 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17640 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17640 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17640 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16717 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16717 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16717 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16717 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16717 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16717 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05208 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05208 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05208 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05208 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05208 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.05208 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07585 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07585 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07585 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07585 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07585 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07585 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07112 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07112 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07112 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07112 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07112 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07112 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07424 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07424 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07424 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07424 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07424 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07424 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23231 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23231 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23231 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23231 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23231 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23231 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.21803 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.17032 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.17301 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.17640 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.16717 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.05208 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.07585 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.07112 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.07424 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.23231 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.21803 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.21803 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2373.39508 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.21803 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.21803 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.21803 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46390 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.21803 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.10901 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.47869 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 55078.92000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27539.46000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55078.92000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58873.29416 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58873.29416 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17032 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17032 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1295.72825 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17032 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17032 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17032 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77241 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17032 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58516 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78021 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29061.79000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14530.89500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29061.79000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30836.92135 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30836.92135 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17301 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17301 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1298.71314 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17301 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17301 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17301 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77419 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17301 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58651 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78201 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29128.74000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14564.37000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29128.74000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30898.50234 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30898.50234 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17640 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17640 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1302.46244 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17640 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17640 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17640 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77642 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17640 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58820 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78427 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29212.83000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14606.41500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29212.83000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30975.84913 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30975.84913 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16717 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16717 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1292.23876 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16717 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16717 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16717 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77033 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16717 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58358 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77811 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28983.53000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14491.76500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28983.53000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30764.92918 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30764.92918 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05208 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.05208 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2195.81905 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.05208 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.05208 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.05208 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35437 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.05208 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02604 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36805 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50957.95000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25478.97500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50957.95000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55082.67431 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 55082.67431 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07585 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07585 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1191.13179 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07585 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07585 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07585 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71006 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07585 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53792 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71723 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26715.81000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13357.90500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26715.81000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28679.11934 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28679.11934 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07112 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07112 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1185.89583 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07112 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07112 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07112 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70694 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07112 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53556 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71408 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26598.37000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13299.18500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26598.37000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28571.10089 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28571.10089 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07424 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07424 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1189.35845 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07424 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07424 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07424 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70900 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07424 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53712 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71616 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26676.03000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13338.01500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26676.03000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28642.52714 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28642.52714 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23231 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23231 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1364.36448 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23231 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23231 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23231 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81333 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23231 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61616 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82154 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30259.16000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15129.58000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70485 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70485 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30259.16000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32253.13858 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32253.13858 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 53329.1 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 28138.5 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 28203.3 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 28284.8 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 28062.7 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 49339.0 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 25867.1 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 25753.3 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 25828.5 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 29287.2 | 11.93 | 11.93 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_0.25 | N/A | 3.053 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.7922566768E-002 | 7.3750595895E-002 | Pass | Pass | 3.3741008260E-002 | 8.8970878066E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4545618888E-002 | 0.1092367635 | Pass | Pass | 3.5646793475E-002 | 9.6098940642E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9268383509E-002 | 0.1330374045 | Pass | Pass | 0.1645459771 | 1.5438186670 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8863868712E-002 | 0.1310195053 | Pass | Pass | 0.1664615370 | 1.5650912263 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7089992466E-002 | 0.1214161257 | Pass | Pass | 0.1688117249 | 1.5932433163 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4989456635E-002 | 0.1063326696 | Pass | Pass | 0.1382484666 | 1.2450255991 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.4158921667E-002 | 0.1017063228 | Pass | Pass | 0.1717639079 | 1.5921043510 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.3579374412E-002 | 9.8211302894E-002 | Pass | Pass | 0.1737920055 | 1.6018557561 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.2035925511E-002 | 8.8876069255E-002 | Pass | Pass | 0.1835788889 | 1.6570020960 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.2359627361E-002 | 8.3045915282E-002 | Pass | Pass | 0.2120006450 | 2.0975109675 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3150.18 | -211.2 | 0.00 | -318.2 | 1859.33 | 4480.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.053 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.053 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.053 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.537_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.053 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 3.053 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 3.053 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.73 | 41.73 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.73 | 62.73 | 32.31 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.73 | 55.73 | 24.13 | |
Exterior Lighting Total | 5507.06 | 60.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 55078.92 | 38614.73 | 16464.19 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29061.79 | 20374.64 | 8687.15 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29128.74 | 20421.58 | 8707.16 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29212.83 | 20480.53 | 8732.30 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28983.53 | 20319.77 | 8663.76 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50957.95 | 35725.60 | 15232.35 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26715.81 | 18729.92 | 7985.89 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26598.37 | 18647.59 | 7950.78 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26676.03 | 18702.03 | 7974.00 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30259.16 | 21328.17 | 8930.99 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 53329.1 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 28138.5 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 28203.3 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 28284.8 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 28062.7 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 49339.0 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 25867.1 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 25753.3 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 25828.5 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 29287.2 | 11.93 | 11.93 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58873.29 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30836.92 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30898.50 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30975.85 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30764.93 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 55082.67 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28679.12 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28571.10 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28642.53 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32253.14 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.22 | 2373.40 | 1070.05 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1295.73 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1298.71 | 1107.16 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1302.46 | 1107.16 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1292.24 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.05 | 2195.82 | 1070.05 | 1.00 | 1.31 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1191.13 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1185.90 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1189.36 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1364.36 | 1107.16 | 1.00 | 1.35 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25154.32 | 30185.18 | 86.64 | 1.848 | 2.218 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 23.89 | 23.88 | 0.01031 | 33.90 | 0.01654 | 0.411 | 0.00 |
SMSTORE1 | 13272.21 | 15926.65 | 91.43 | 0.975 | 1.170 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.01034 | 33.90 | 0.01654 | 0.206 | 0.00 |
SMSTORE2 | 13302.83 | 15963.40 | 91.64 | 0.978 | 1.173 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01033 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE3 | 13341.23 | 16009.48 | 91.91 | 0.980 | 1.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01033 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE4 | 13236.52 | 15883.83 | 91.19 | 0.973 | 1.167 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01034 | 33.83 | 0.01654 | 0.206 | 0.00 |
LGSTORE2 | 23272.87 | 27927.44 | 80.16 | 1.710 | 2.052 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01039 | 33.83 | 0.01654 | 0.411 | 0.00 |
SMSTORE5 | 12200.93 | 14641.12 | 84.05 | 0.897 | 1.076 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01047 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE6 | 12147.30 | 14576.76 | 83.68 | 0.893 | 1.071 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01047 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE7 | 12182.91 | 14619.49 | 83.93 | 0.895 | 1.074 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01047 | 33.77 | 0.01654 | 0.206 | 0.00 |
SMSTORE8 | 13977.84 | 16773.41 | 96.29 | 1.027 | 1.232 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01032 | 33.50 | 0.01654 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16085.96 | 19303.15 | 55.41 | 0.694 | 0.833 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00704 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 7968.76 | 9562.51 | 54.90 | 0.344 | 0.413 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 8034.47 | 9641.37 | 55.35 | 0.347 | 0.416 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 8101.68 | 9722.02 | 55.81 | 0.350 | 0.419 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 8246.01 | 9895.21 | 56.81 | 0.356 | 0.427 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00699 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 15528.80 | 18634.56 | 53.49 | 0.670 | 0.804 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8446.10 | 10135.32 | 58.18 | 0.364 | 0.437 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8451.07 | 10141.29 | 58.22 | 0.365 | 0.438 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8695.16 | 10434.20 | 59.90 | 0.375 | 0.450 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00702 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 10225.15 | 12270.18 | 70.44 | 0.441 | 0.529 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00706 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.22 | 2.22 | 0.83 | 0.83 | 2.2180 | 2.2180 | 2.2180 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.17 | 1.17 | 0.41 | 0.41 | 1.1703 | 1.1703 | 1.1703 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.17 | 1.17 | 0.42 | 0.42 | 1.1730 | 1.1730 | 1.1730 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.18 | 1.18 | 0.42 | 0.42 | 1.1764 | 1.1764 | 1.1764 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.17 | 1.17 | 0.43 | 0.43 | 1.1672 | 1.1672 | 1.1672 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.05 | 2.05 | 0.80 | 0.80 | 2.0521 | 2.0521 | 2.0521 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.08 | 1.08 | 0.44 | 0.44 | 1.0758 | 1.0758 | 1.0758 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.07 | 1.07 | 0.44 | 0.44 | 1.0711 | 1.0711 | 1.0711 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.07 | 1.07 | 0.45 | 0.45 | 1.0742 | 1.0742 | 1.0742 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.23 | 1.23 | 0.53 | 0.53 | 1.2323 | 1.2323 | 1.2323 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 55078.920 | 38614.729 | 2.218030 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 27539.46 | 18439.03 | 1.478687 | 26.61 | 19.64 | 0.01146689 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.8273 | 23.88 | 0.01031221 | 55.6992 | 25154.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58873.294 | 58873.294 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 58873.29 | 58873.29 | 2.218028 | 18.05 | 12.46 | 0.00671079 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.5516 | 21.11 | 0.00704189 | 45.2553 | 16085.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 29061.790 | 20374.640 | 1.170320 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 14530.90 | 9758.35 | 0.780213 | 26.54 | 19.59 | 0.01142698 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.3696 | 23.88 | 0.01033717 | 55.8324 | 13272.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30836.921 | 30836.921 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30836.92 | 30836.92 | 1.170318 | 18.21 | 12.48 | 0.00666817 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.5798 | 21.11 | 0.00696913 | 44.7932 | 7968.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 29128.740 | 20421.577 | 1.173010 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14564.37 | 9785.34 | 0.782007 | 26.54 | 19.59 | 0.01142217 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.3092 | 23.88 | 0.01033411 | 55.8162 | 13300.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30898.502 | 30898.502 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30898.50 | 30898.50 | 1.173014 | 18.21 | 12.49 | 0.00667249 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.5394 | 21.11 | 0.00697353 | 44.8212 | 8034.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 29212.830 | 20480.531 | 1.176400 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14606.42 | 9819.77 | 0.784267 | 26.53 | 19.58 | 0.01141560 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.2333 | 23.88 | 0.01032988 | 55.7937 | 13337.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30975.849 | 30975.849 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30975.85 | 30975.85 | 1.176401 | 18.22 | 12.50 | 0.00667723 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.4889 | 21.11 | 0.00697822 | 44.8511 | 8101.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28983.530 | 20319.773 | 1.167170 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14491.76 | 9725.62 | 0.778113 | 26.55 | 19.60 | 0.01143390 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.4408 | 23.88 | 0.01034169 | 55.8564 | 13233.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30764.929 | 30764.929 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30764.93 | 30764.93 | 1.167167 | 18.20 | 12.50 | 0.00668350 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.6273 | 21.11 | 0.00698873 | 44.9178 | 8246.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 50957.950 | 35725.600 | 2.052080 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 25478.97 | 16817.57 | 1.368053 | 26.76 | 19.81 | 0.01162673 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.0777 | 23.88 | 0.01039496 | 56.1382 | 23266.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 55082.674 | 55082.674 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 55082.67 | 55082.67 | 2.052077 | 17.80 | 12.34 | 0.00668872 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.0518 | 21.11 | 0.00704777 | 45.2924 | 15528.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 26715.810 | 18729.920 | 1.075850 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13357.91 | 8802.85 | 0.717233 | 26.69 | 19.79 | 0.01162856 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.6851 | 23.88 | 0.01046766 | 56.5254 | 12197.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28679.119 | 28679.119 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28679.12 | 28679.12 | 1.075846 | 17.95 | 12.38 | 0.00666747 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.1235 | 21.11 | 0.00700094 | 44.9955 | 8446.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 26598.370 | 18647.585 | 1.071120 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13299.18 | 8755.52 | 0.714080 | 26.70 | 19.80 | 0.01163935 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.8118 | 23.88 | 0.01047465 | 56.5625 | 12143.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28571.101 | 28571.101 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28571.10 | 28571.10 | 1.071116 | 17.94 | 12.37 | 0.00666634 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.2079 | 21.11 | 0.00700137 | 44.9983 | 8451.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 26676.030 | 18702.031 | 1.074240 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 13338.01 | 8786.50 | 0.716160 | 26.70 | 19.80 | 0.01163259 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.7281 | 23.88 | 0.01047028 | 56.5393 | 12177.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28642.527 | 28642.527 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28642.53 | 28642.53 | 1.074244 | 17.95 | 12.39 | 0.00668039 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.1520 | 21.11 | 0.00701754 | 45.1011 | 8695.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 30259.160 | 21328.169 | 1.232310 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 15129.58 | 10205.55 | 0.821540 | 26.39 | 19.49 | 0.01135839 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01653563 | 25.03 | 25.0431 | 23.88 | 0.01032079 | 55.7457 | 13977.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32253.139 | 32253.139 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32253.14 | 32253.14 | 1.232312 | 18.35 | 12.64 | 0.00676292 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.6954 | 21.11 | 0.00706470 | 45.4015 | 10225.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55078.920 | 38614.729 | 2.218030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1564 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.218028 | 2.66865817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 27539.46 | 18439.03 | 1.0000 | 1.77910685 | 1.478687 | 26.61 | 19.64 | 0.01146689 | 55981.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27539.46 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 27.8273 | 23.88 | 0.01031221 | 23.88 | 0.01031221 | 55.6992 | 25154.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58873.294 | 58873.294 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.218028 | 2.66865817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 58873.29 | 58873.29 | 1.0000 | 2.66865817 | 2.218028 | 18.05 | 12.46 | 0.00671079 | 35141.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58873.29 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 18.5516 | 21.11 | 0.00704189 | 21.11 | 0.00704189 | 45.2553 | 16085.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29061.790 | 20374.640 | 1.170320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0822 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.170318 | 1.40808836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 14530.90 | 9758.35 | 1.0000 | 0.93872685 | 0.780213 | 26.54 | 19.59 | 0.01142698 | 55810.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14530.90 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.3696 | 23.88 | 0.01033717 | 23.88 | 0.01033717 | 55.8324 | 13272.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30836.921 | 30836.921 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.170318 | 1.40808836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30836.92 | 30836.92 | 1.0000 | 1.40808836 | 1.170318 | 18.21 | 12.48 | 0.00666817 | 35196.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30836.92 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.5798 | 21.11 | 0.00696913 | 21.11 | 0.00696913 | 44.7932 | 7968.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29128.740 | 20421.577 | 1.173010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0732 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.173014 | 1.41133210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14564.37 | 9785.34 | 1.0000 | 0.94088453 | 0.782007 | 26.54 | 19.59 | 0.01142217 | 55794.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14564.37 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.3092 | 23.88 | 0.01033411 | 23.88 | 0.01033411 | 55.8162 | 13300.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30898.502 | 30898.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.173014 | 1.41133210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30898.50 | 30898.50 | 1.0000 | 1.41133210 | 1.173014 | 18.21 | 12.49 | 0.00667249 | 35214.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30898.50 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.5394 | 21.11 | 0.00697353 | 21.11 | 0.00697353 | 44.8212 | 8034.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29212.830 | 20480.531 | 1.176400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0610 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.176401 | 1.41540652 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14606.42 | 9819.77 | 1.0000 | 0.94360369 | 0.784267 | 26.53 | 19.58 | 0.01141560 | 55772.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14606.42 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.2333 | 23.88 | 0.01032988 | 23.88 | 0.01032988 | 55.7937 | 13337.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30975.849 | 30975.849 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.176401 | 1.41540652 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30975.85 | 30975.85 | 1.0000 | 1.41540652 | 1.176401 | 18.22 | 12.50 | 0.00667723 | 35234.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30975.85 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.4889 | 21.11 | 0.00697822 | 21.11 | 0.00697822 | 44.8511 | 8101.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28983.530 | 20319.773 | 1.167170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0950 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167167 | 1.40429629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14491.76 | 9725.62 | 1.0000 | 0.93620020 | 0.778113 | 26.55 | 19.60 | 0.01143390 | 55833.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14491.76 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.4408 | 23.88 | 0.01034169 | 23.88 | 0.01034169 | 55.8564 | 13233.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30764.929 | 30764.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167167 | 1.40429629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30764.93 | 30764.93 | 1.0000 | 1.40429629 | 1.167167 | 18.20 | 12.50 | 0.00668350 | 35227.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30764.93 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.6273 | 21.11 | 0.00698873 | 21.11 | 0.00698873 | 44.9178 | 8246.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50957.950 | 35725.600 | 2.052080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4535 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.052077 | 2.46899073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 25478.97 | 16817.57 | 1.0000 | 1.64599648 | 1.368053 | 26.76 | 19.81 | 0.01162673 | 56543.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25478.97 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 30.0777 | 23.88 | 0.01039496 | 23.88 | 0.01039496 | 56.1382 | 23266.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55082.674 | 55082.674 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.052077 | 2.46899073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 55082.67 | 55082.67 | 1.0000 | 2.46899073 | 2.052077 | 17.80 | 12.34 | 0.00668872 | 34833.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55082.67 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 20.0518 | 21.11 | 0.00704777 | 21.11 | 0.00704777 | 45.2924 | 15528.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26715.810 | 18729.920 | 1.075850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4569 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.075846 | 1.29442174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13357.91 | 8802.85 | 1.0000 | 0.86295140 | 0.717233 | 26.69 | 19.79 | 0.01162856 | 56483.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13357.91 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 28.6851 | 23.88 | 0.01046766 | 23.88 | 0.01046766 | 56.5254 | 12197.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28679.119 | 28679.119 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.075846 | 1.29442174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28679.12 | 28679.12 | 1.0000 | 1.29442174 | 1.075846 | 17.95 | 12.38 | 0.00666747 | 34935.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28679.12 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.1235 | 21.11 | 0.00700094 | 21.11 | 0.00700094 | 44.9955 | 8446.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26598.370 | 18647.585 | 1.071120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4770 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071116 | 1.28873174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13299.18 | 8755.52 | 1.0000 | 0.85915742 | 0.714080 | 26.70 | 19.80 | 0.01163935 | 56519.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13299.18 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 28.8118 | 23.88 | 0.01047465 | 23.88 | 0.01047465 | 56.5625 | 12143.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28571.101 | 28571.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071116 | 1.28873174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28571.10 | 28571.10 | 1.0000 | 1.28873174 | 1.071116 | 17.94 | 12.37 | 0.00666634 | 34918.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28571.10 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.2079 | 21.11 | 0.00700137 | 21.11 | 0.00700137 | 44.9983 | 8451.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26676.030 | 18702.031 | 1.074240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4644 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.074244 | 1.29249462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 13338.01 | 8786.50 | 1.0000 | 0.86166000 | 0.716160 | 26.70 | 19.80 | 0.01163259 | 56497.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13338.01 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 28.7281 | 23.88 | 0.01047028 | 23.88 | 0.01047028 | 56.5393 | 12177.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28642.527 | 28642.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.074244 | 1.29249462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28642.53 | 28642.53 | 1.0000 | 1.29249462 | 1.074244 | 17.95 | 12.39 | 0.00668039 | 34963.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28642.53 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.1520 | 21.11 | 0.00701754 | 21.11 | 0.00701754 | 45.1011 | 8695.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30259.160 | 21328.169 | 1.232310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9547 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.232312 | 1.48267645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 15129.58 | 10205.55 | 1.0000 | 0.98844973 | 0.821540 | 26.39 | 19.49 | 0.01135839 | 55478.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15129.58 | 33.50 | 0.01653563 | 25.03 | 0.20573941 | 25.0431 | 23.88 | 0.01032079 | 23.88 | 0.01032079 | 55.7457 | 13977.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32253.139 | 32253.139 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.232312 | 1.48267645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32253.14 | 32253.14 | 1.0000 | 1.48267645 | 1.232312 | 18.35 | 12.64 | 0.00676292 | 35585.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32253.14 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 16.6954 | 21.11 | 0.00706470 | 21.11 | 0.00706470 | 45.4015 | 10225.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.22 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.17 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.17 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.18 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.17 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.05 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.08 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.23 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4412.83 | 2090.33 | 1140.50 |
SMSTORE1 | 4305.50 | 1452.33 | 673.50 |
SMSTORE2 | 3340.67 | 1728.33 | 1059.00 |
SMSTORE3 | 3320.33 | 1748.50 | 1050.83 |
SMSTORE4 | 3288.83 | 1878.33 | 1130.33 |
LGSTORE2 | 2957.33 | 2117.00 | 1346.67 |
SMSTORE5 | 2927.33 | 2172.50 | 1369.67 |
SMSTORE6 | 2919.00 | 2213.67 | 1395.83 |
SMSTORE7 | 2908.83 | 2271.00 | 1421.33 |
SMSTORE8 | 2936.00 | 2079.00 | 1226.00 |
Facility | 4585.17 | 3101.67 | 1874.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 0.17 | 0.50 | 0.00 | 0.00 |
Facility | 0.17 | 0.83 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.940 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.821 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.985 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.982 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.974 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.951 | 0.472 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.957 | 0.538 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.954 | 0.538 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.951 | 0.538 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.969 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.81 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.09 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9709217.24 | 0.00 | 9709217.24 | 3838649.30 | 13547866.54 | 12976396.34 | 3171.44 | 4695.50 | 893.06 | 13.82 |
SMSTORE1 | 4241589.74 | 0.00 | 4241589.74 | 2068521.06 | 6310110.80 | 6488198.17 | 4417.43 | 3440.42 | 902.16 | 15.86 |
SMSTORE2 | 3866046.99 | 0.00 | 3866046.99 | 2094113.03 | 5960160.02 | 6488198.17 | 4344.63 | 3781.70 | 633.67 | 73.13 |
SMSTORE3 | 3852125.75 | 0.00 | 3852125.75 | 2094113.03 | 5946238.78 | 6488198.17 | 4345.59 | 3799.78 | 614.62 | 69.63 |
SMSTORE4 | 3816187.45 | 0.00 | 3816187.45 | 2094113.03 | 5910300.48 | 6488198.17 | 4348.78 | 3828.67 | 582.55 | 67.93 |
LGSTORE2 | 6819151.79 | 0.00 | 6819151.79 | 3717029.21 | 10536181.00 | 12976396.34 | 4718.06 | 3514.17 | 527.78 | 47.86 |
SMSTORE5 | 3430149.37 | 0.00 | 3430149.37 | 2101897.61 | 5532046.98 | 6488198.17 | 4717.61 | 3524.50 | 517.89 | 46.87 |
SMSTORE6 | 3418873.61 | 0.00 | 3418873.61 | 2101897.61 | 5520771.22 | 6488198.17 | 4718.19 | 3532.75 | 509.06 | 45.17 |
SMSTORE7 | 3401800.80 | 0.00 | 3401800.80 | 2101897.61 | 5503698.41 | 6488198.17 | 4720.87 | 3549.33 | 489.80 | 39.69 |
SMSTORE8 | 3464514.38 | 0.00 | 3464514.38 | 2340335.64 | 5804850.03 | 6488198.17 | 4721.80 | 3563.00 | 475.20 | 21.21 |
Total Facility | 46019657.13 | 0.00 | 46019657.13 | 24552567.14 | 70572224.26 | 77858378.04 | 4724.99 | 5231.17 | 1178.45 | 143.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4614 | 0.0000 | 0.4614 | 0.1689 | 0.6303 | 0.4115 | 252.76 | 4695.50 | 891.74 |
SMSTORE1 | 0.2015 | 0.0000 | 0.2015 | 0.0942 | 0.2957 | 0.2057 | 1498.82 | 3440.42 | 900.77 |
SMSTORE2 | 0.2415 | 0.0000 | 0.2415 | 0.1236 | 0.3650 | 0.2057 | 0.00 | 3781.20 | 613.80 |
SMSTORE3 | 0.2407 | 0.0000 | 0.2407 | 0.1236 | 0.3643 | 0.2057 | 0.00 | 3799.28 | 595.72 |
SMSTORE4 | 0.2387 | 0.0000 | 0.2387 | 0.1236 | 0.3623 | 0.2057 | 0.00 | 3828.50 | 566.50 |
LGSTORE2 | 0.4665 | 0.0000 | 0.4665 | 0.2310 | 0.6975 | 0.4115 | 0.00 | 3513.50 | 516.50 |
SMSTORE5 | 0.2346 | 0.0000 | 0.2346 | 0.1317 | 0.3663 | 0.2057 | 0.00 | 3524.42 | 505.58 |
SMSTORE6 | 0.2339 | 0.0000 | 0.2339 | 0.1317 | 0.3656 | 0.2057 | 0.00 | 3532.75 | 497.25 |
SMSTORE7 | 0.2330 | 0.0000 | 0.2330 | 0.1317 | 0.3647 | 0.2057 | 0.00 | 3549.33 | 480.67 |
SMSTORE8 | 0.2377 | 0.0000 | 0.2377 | 0.1354 | 0.3731 | 0.2057 | 0.00 | 3563.00 | 467.00 |
Total Facility | 2.7894 | 0.0000 | 2.7894 | 1.3954 | 4.1847 | 2.4689 | 1605.51 | 5229.67 | 1160.05 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14055121.37 | 0.00 | 14055121.37 | 12976396.34 | 3163.02 | 0.33 | 5596.65 | 13.82 |
PSZ-AC_2:2 | 6140149.71 | 0.00 | 6140149.71 | 6488198.17 | 4352.13 | 3.47 | 4404.40 | 15.86 |
PSZ-AC_3:3 | 5596511.11 | 0.00 | 5596511.11 | 6488198.17 | 4332.76 | 0.50 | 4426.74 | 72.80 |
PSZ-AC_4:4 | 5576359.11 | 0.00 | 5576359.11 | 6488198.17 | 4334.26 | 0.50 | 4425.24 | 69.30 |
PSZ-AC_5:5 | 5524333.81 | 0.00 | 5524333.81 | 6488198.17 | 4338.45 | 0.17 | 4421.38 | 67.93 |
PSZ-AC_6:6 | 9871430.01 | 0.00 | 9871430.01 | 12976396.34 | 4713.67 | 0.17 | 4046.17 | 47.69 |
PSZ-AC_7:7 | 4965501.59 | 0.00 | 4965501.59 | 6488198.17 | 4712.94 | 0.17 | 4046.89 | 46.87 |
PSZ-AC_8:8 | 4949177.05 | 0.00 | 4949177.05 | 6488198.17 | 4714.02 | 0.42 | 4045.56 | 45.17 |
PSZ-AC_9:9 | 4924457.03 | 0.00 | 4924457.03 | 6488198.17 | 4716.79 | 0.42 | 4042.80 | 39.52 |
PSZ-AC_10:10 | 5015238.49 | 0.00 | 5015238.49 | 6488198.17 | 4719.97 | 0.00 | 4040.03 | 21.05 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6679 | 0.0000 | 0.6679 | 0.4115 | 245.34 | 0.33 | 5594.33 |
PSZ-AC_2:2 | 0.2917 | 0.0000 | 0.2917 | 0.2057 | 1434.35 | 3.47 | 4402.17 |
PSZ-AC_3:3 | 0.3496 | 0.0000 | 0.3496 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3485 | 0.0000 | 0.3485 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3456 | 0.0000 | 0.3456 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6753 | 0.0000 | 0.6753 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3396 | 0.0000 | 0.3396 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3386 | 0.0000 | 0.3386 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3373 | 0.0000 | 0.3373 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3441 | 0.0000 | 0.3441 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5107.45 | 527.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4823.29 | 736.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4127.17 | 340.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4136.84 | 327.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4155.51 | 307.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3834.83 | 242.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3830.98 | 245.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3834.28 | 240.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3839.24 | 230.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3828.06 | 222.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6678 | 0.9531 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2925 | 0.4068 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3382 | 0.5217 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3374 | 0.5241 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3354 | 0.5193 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6601 | 0.9706 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3312 | 0.4988 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3305 | 0.4950 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3294 | 0.4954 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3340 | 0.5351 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
ElectricityPurchased:Plant | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
Cogeneration:ElectricityPurchased | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
General:Cogeneration:ElectricityPurchased | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
ElectricityNet:Plant | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
Cogeneration:ElectricityNet | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
General:Cogeneration:ElectricityNet | 1125.99 | 2102.83 | 01-JAN-07:30 | 123501.72 | 10-SEP-12:10 |
Electricity:HVAC | 469.66 | 0.00 | 01-JAN-00:10 | 84235.87 | 10-SEP-13:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 364.06 | 0.00 | 01-JAN-00:10 | 72850.37 | 10-SEP-14:10 |
General:Cooling:Electricity | 364.06 | 0.00 | 01-JAN-00:10 | 72850.37 | 10-SEP-14:10 |
Fans:Electricity | 105.60 | 0.00 | 01-JAN-00:10 | 11486.69 | 10-SEP-13:00 |
General:Fans:Electricity | 105.60 | 0.00 | 01-JAN-00:10 | 11486.69 | 10-SEP-13:00 |
ExteriorLights:Electricity | 60.01 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.01 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 59.82 | 1211.00 | 05-JAN-08:10 | 11639.66 | 01-JAN-08:30 |
WaterSystems:Electricity | 59.82 | 1211.00 | 05-JAN-08:10 | 11639.66 | 01-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 59.82 | 1211.00 | 05-JAN-08:10 | 11639.66 | 01-JAN-08:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 17.26 | 0.00 | 01-JAN-00:10 | 99641.90 | 05-FEB-09:10 |
NaturalGas:HVAC | 17.26 | 0.00 | 01-JAN-00:10 | 99641.90 | 05-FEB-09:10 |
Heating:NaturalGas | 17.26 | 0.00 | 01-JAN-00:10 | 99641.90 | 05-FEB-09:10 |
General:Heating:NaturalGas | 17.26 | 0.00 | 01-JAN-00:10 | 99641.90 | 05-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2304.61 | 0.00 | 01-JAN-00:10 | 409716.03 | 10-SEP-13:00 |
EnergyTransfer:Building | 798.98 | 0.00 | 01-JAN-00:10 | 121330.40 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 166.76 | 0.00 | 01-JAN-00:10 | 20018.16 | 10-SEP-15:00 |
Heating:EnergyTransfer | 8.32 | 0.00 | 01-JAN-00:10 | 55448.02 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.81 | 0.00 | 01-JAN-00:10 | 13693.38 | 05-FEB-08:10 |
General:Heating:EnergyTransfer | 8.32 | 0.00 | 01-JAN-00:10 | 55448.02 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.81 | 0.00 | 01-JAN-00:10 | 13693.38 | 05-FEB-08:10 |
Cooling:EnergyTransfer | 790.66 | 0.00 | 01-JAN-00:10 | 121330.40 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 165.95 | 0.00 | 01-JAN-00:10 | 20018.16 | 10-SEP-15:00 |
General:Cooling:EnergyTransfer | 790.66 | 0.00 | 01-JAN-00:10 | 121330.40 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 165.95 | 0.00 | 01-JAN-00:10 | 20018.16 | 10-SEP-15:00 |
EnergyTransfer:Zone:SMSTORE1 | 89.82 | 0.00 | 01-JAN-00:10 | 10425.68 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 2755.10 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 2755.10 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 89.53 | 0.00 | 01-JAN-00:10 | 10425.68 | 10-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 89.53 | 0.00 | 01-JAN-00:10 | 10425.68 | 10-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 68.21 | 0.00 | 01-JAN-00:10 | 10282.92 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.75 | 0.00 | 01-JAN-00:10 | 4273.13 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.75 | 0.00 | 01-JAN-00:10 | 4273.13 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.45 | 0.00 | 01-JAN-00:10 | 10282.92 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.45 | 0.00 | 01-JAN-00:10 | 10282.92 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 67.90 | 0.00 | 01-JAN-00:10 | 10326.69 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.78 | 0.00 | 01-JAN-00:10 | 4886.87 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.78 | 0.00 | 01-JAN-00:10 | 4886.87 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 67.12 | 0.00 | 01-JAN-00:10 | 10326.69 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 67.12 | 0.00 | 01-JAN-00:10 | 10326.69 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 65.72 | 0.00 | 01-JAN-00:10 | 10223.86 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.83 | 0.00 | 01-JAN-00:10 | 5506.99 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.83 | 0.00 | 01-JAN-00:10 | 5506.99 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 64.89 | 0.00 | 01-JAN-00:10 | 10223.86 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 64.89 | 0.00 | 01-JAN-00:10 | 10223.86 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 110.24 | 0.00 | 01-JAN-00:10 | 18862.88 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.22 | 0.00 | 01-JAN-00:10 | 12271.05 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.22 | 0.00 | 01-JAN-00:10 | 12271.05 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 109.02 | 0.00 | 01-JAN-00:10 | 18862.88 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 109.02 | 0.00 | 01-JAN-00:10 | 18862.88 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 56.92 | 0.00 | 01-JAN-00:10 | 10020.90 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.69 | 0.00 | 01-JAN-00:10 | 6557.82 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.69 | 0.00 | 01-JAN-00:10 | 6557.82 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 56.23 | 0.00 | 01-JAN-00:10 | 10020.90 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 56.23 | 0.00 | 01-JAN-00:10 | 10020.90 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 56.31 | 0.00 | 01-JAN-00:10 | 9988.97 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.73 | 0.00 | 01-JAN-00:10 | 6735.37 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.73 | 0.00 | 01-JAN-00:10 | 6735.37 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 55.59 | 0.00 | 01-JAN-00:10 | 9988.97 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 55.59 | 0.00 | 01-JAN-00:10 | 9988.97 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 55.49 | 0.00 | 01-JAN-00:10 | 10073.27 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.84 | 0.00 | 01-JAN-00:10 | 7615.69 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.84 | 0.00 | 01-JAN-00:10 | 7615.69 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 54.66 | 0.00 | 01-JAN-00:10 | 10073.27 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 54.66 | 0.00 | 01-JAN-00:10 | 10073.27 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 61.61 | 0.00 | 01-JAN-00:10 | 12466.84 | 05-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.37 | 0.00 | 01-JAN-00:10 | 12465.95 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.37 | 0.00 | 01-JAN-00:10 | 12465.95 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 60.24 | 0.00 | 01-JAN-00:10 | 11711.05 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 60.24 | 0.00 | 01-JAN-00:10 | 11711.05 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1505.63 | 0.00 | 01-JAN-00:10 | 290994.33 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 13.81 | 0.00 | 01-JAN-00:10 | 79713.52 | 05-FEB-09:10 |
CoolingCoils:EnergyTransfer | 1491.82 | 0.00 | 01-JAN-00:10 | 290994.33 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.813 | -165.943 | 0.000 | 0.000 | 23.557 | 95.826 | 26.249 | 19.493 | 0.000 | 14.165 | 1.953 | 0.000 | -5.451 | 0.000 | -10.662 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.293 | -89.526 | 0.000 | 0.000 | 11.713 | 57.583 | 13.125 | 9.714 | 0.000 | 7.951 | 0.001 | 0.000 | -2.828 | 0.000 | -5.557 | -2.468 |
SMSTORE2 | 0.000 | 0.000 | 0.754 | -67.450 | 0.000 | 0.000 | 7.069 | 40.956 | 10.421 | 9.663 | 0.000 | 7.803 | 0.001 | 0.000 | -2.909 | 0.000 | -5.673 | -0.634 |
SMSTORE3 | 0.000 | 0.000 | 0.780 | -67.118 | 0.000 | 0.000 | 7.075 | 40.956 | 10.421 | 9.669 | 0.000 | 7.802 | 0.001 | 0.000 | -2.892 | 0.000 | -5.637 | -1.055 |
SMSTORE4 | 0.000 | 0.000 | 0.833 | -64.888 | 0.000 | 0.000 | 7.084 | 40.956 | 10.421 | 9.690 | 0.000 | 7.805 | 0.001 | 0.000 | -2.842 | 0.000 | -5.567 | -3.491 |
LGSTORE2 | 0.000 | 0.000 | 1.222 | -109.014 | 0.000 | 0.000 | 24.348 | 43.277 | 19.173 | 19.458 | 0.000 | 13.703 | 3.111 | 0.000 | -5.433 | 0.000 | -9.846 | -0.003 |
SMSTORE5 | 0.000 | 0.000 | 0.693 | -56.225 | 0.000 | 0.000 | 12.182 | 22.197 | 9.586 | 9.735 | 0.000 | 7.816 | 2.166 | 0.000 | -2.687 | 0.000 | -5.463 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.726 | -55.588 | 0.000 | 0.000 | 12.187 | 22.197 | 9.586 | 9.745 | 0.000 | 7.817 | 1.438 | 0.000 | -2.670 | 0.000 | -5.438 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.835 | -54.657 | 0.000 | 0.000 | 12.200 | 22.197 | 9.586 | 9.757 | 0.000 | 7.818 | 0.275 | 0.000 | -2.636 | 0.000 | -5.377 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 1.367 | -60.239 | 0.000 | 0.000 | 12.212 | 22.197 | 9.586 | 9.734 | 0.000 | 8.018 | 6.163 | 0.000 | -2.536 | 0.000 | -6.503 | -0.001 |
Total Facility | 0.000 | 0.000 | 8.317 | -790.648 | 0.000 | 0.000 | 129.627 | 408.342 | 128.154 | 116.659 | 0.000 | 90.698 | 15.110 | 0.000 | -32.885 | 0.000 | -65.723 | -7.654 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -47723.70 | 0.00 | 0.00 | 173.83 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 47705.68 | 0.00 | -112.38 | 0.00 | -193.05 | 0.00 |
SMSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -25809.45 | 0.00 | 0.00 | 86.15 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 25807.02 | 0.00 | -57.58 | 0.00 | -100.96 | 0.00 |
SMSTORE2 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24557.20 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24628.58 | 0.00 | -129.89 | 0.00 | -15.82 | 0.00 |
SMSTORE3 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24645.84 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24717.80 | 0.00 | -130.37 | 0.00 | -15.90 | 0.00 |
SMSTORE4 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24309.23 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24378.31 | 0.00 | -128.11 | 0.00 | -15.28 | 0.00 |
LGSTORE2 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -43695.98 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 43834.76 | 0.00 | -106.54 | 0.00 | -180.88 | 0.00 |
SMSTORE5 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22762.98 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22837.82 | 0.00 | -51.73 | 0.00 | -97.43 | 0.00 |
SMSTORE6 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22638.65 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22712.13 | 0.00 | -51.13 | 0.00 | -96.68 | 0.00 |
SMSTORE7 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22654.97 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22726.32 | 0.00 | -50.78 | 0.00 | -94.89 | 0.00 |
SMSTORE8 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -23100.68 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23181.90 | 0.00 | -50.87 | 0.00 | -104.67 | 0.00 |
Total Facility | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -215602.22 | 0.00 | 0.00 | 555.49 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 214882.67 | 0.00 | -605.94 | 0.00 | -1132.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:61 | 0.00 | 0.00 | 59006.88 | 0.00 | 0.00 | 0.00 | 247.50 | 75.00 | 74.62 | 116.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1258.25 | -58262.39 |
SMSTORE1 | 21-DEC-08:61 | 0.00 | 0.00 | 15414.02 | 0.00 | 0.00 | 0.00 | 118.38 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -332.99 | 0.00 | -775.95 | -14498.27 |
SMSTORE2 | 05-FEB-08:62 | 0.00 | 0.00 | 22854.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.07 | 0.00 | -1151.13 | -21713.52 |
SMSTORE3 | 05-FEB-08:62 | 0.00 | 0.00 | 26583.40 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.17 | 0.00 | -1150.47 | -25447.57 |
SMSTORE4 | 05-FEB-08:62 | 0.00 | 0.00 | 30141.05 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55.95 | 0.00 | -1149.67 | -29010.24 |
LGSTORE2 | 06-FEB-08:61 | 0.00 | 0.00 | 55342.95 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 128.06 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1186.36 | -54433.28 |
SMSTORE5 | 06-FEB-08:61 | 0.00 | 0.00 | 28817.82 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 63.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -673.15 | -28282.79 |
SMSTORE6 | 06-FEB-08:61 | 0.00 | 0.00 | 28712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 66.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -669.16 | -28183.53 |
SMSTORE7 | 06-FEB-08:61 | 0.00 | 0.00 | 28785.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 75.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -652.28 | -28282.52 |
SMSTORE8 | 06-FEB-08:61 | 0.00 | 0.00 | 32272.93 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 109.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -636.87 | -31820.10 |
Total Facility | 21-DEC-08:61 | 0.00 | 0.00 | 251003.04 | 0.00 | 0.00 | 0.00 | 713.51 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3753.23 | 0.00 | -8810.66 | -241054.90 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2180 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2180 | 0.1855 | 1.0000 | Not calculated | 0.4115 | 0.1855 | ||
PSZ-AC_2:2 | 1.1703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1703 | 0.1758 | 1.0000 | Not calculated | 0.2057 | 0.1758 | ||
PSZ-AC_3:3 | 1.1730 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1730 | 0.1754 | 1.0000 | Not calculated | 0.2057 | 0.1754 | ||
PSZ-AC_4:4 | 1.1764 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1764 | 0.1749 | 1.0000 | Not calculated | 0.2057 | 0.1749 | ||
PSZ-AC_5:5 | 1.1672 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1672 | 0.1763 | 1.0000 | Not calculated | 0.2057 | 0.1763 | ||
PSZ-AC_6:6 | 2.0521 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0521 | 0.2005 | 1.0000 | Not calculated | 0.4115 | 0.2005 | ||
PSZ-AC_7:7 | 1.0758 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0758 | 0.1912 | 1.0000 | Not calculated | 0.2057 | 0.1912 | ||
PSZ-AC_8:8 | 1.0711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0711 | 0.1921 | 1.0000 | Not calculated | 0.2057 | 0.1921 | ||
PSZ-AC_9:9 | 1.0742 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0742 | 0.1915 | 1.0000 | Not calculated | 0.2057 | 0.1915 | ||
PSZ-AC_10:10 | 1.2323 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2323 | 0.1670 | 1.0000 | Not calculated | 0.2057 | 0.1670 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2180 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2180 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1855 | ||
PSZ-AC_2:2 | 1.1703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1703 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1758 | ||
PSZ-AC_3:3 | 1.1730 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1730 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1754 | ||
PSZ-AC_4:4 | 1.1764 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1764 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1749 | ||
PSZ-AC_5:5 | 1.1672 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1672 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1763 | ||
PSZ-AC_6:6 | 2.0521 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0521 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2005 | ||
PSZ-AC_7:7 | 1.0758 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0758 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1912 | ||
PSZ-AC_8:8 | 1.0711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0711 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1921 | ||
PSZ-AC_9:9 | 1.0742 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0742 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1915 | ||
PSZ-AC_10:10 | 1.2323 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2323 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1670 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2180 | 2.2180 | 2.2180 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1703 | 1.1703 | 1.1703 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1730 | 1.1730 | 1.1730 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1764 | 1.1764 | 1.1764 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1672 | 1.1672 | 1.1672 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0521 | 2.0521 | 2.0521 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0758 | 1.0758 | 1.0758 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0711 | 1.0711 | 1.0711 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0742 | 1.0742 | 1.0742 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2323 | 1.2323 | 1.2323 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2180 | 2.2180 | 2.2180 | 2.2180 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1703 | 1.1703 | 1.1703 | 1.1703 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1730 | 1.1730 | 1.1730 | 1.1730 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1764 | 1.1764 | 1.1764 | 1.1764 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1672 | 1.1672 | 1.1672 | 1.1672 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0521 | 2.0521 | 2.0521 | 2.0521 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0758 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0711 | 1.0711 | 1.0711 | 1.0711 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0742 | 1.0742 | 1.0742 | 1.0742 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2323 | 1.2323 | 1.2323 | 1.2323 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2180 | 2.2180 | 2.2180 | No | 0.4115 | 0.4941 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1703 | 1.1703 | 1.1703 | No | 0.2057 | 0.4987 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1730 | 1.1730 | 1.1730 | No | 0.2057 | 0.4946 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1764 | 1.1764 | 1.1764 | No | 0.2057 | 0.4905 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1672 | 1.1672 | 1.1672 | No | 0.2057 | 0.4819 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0521 | 2.0521 | 2.0521 | No | 0.4115 | 0.5118 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0758 | 1.0758 | 1.0758 | No | 0.2057 | 0.4705 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0711 | 1.0711 | 1.0711 | No | 0.2057 | 0.4702 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0742 | 1.0742 | 1.0742 | No | 0.2057 | 0.4570 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2323 | 1.2323 | 1.2323 | No | 0.2057 | 0.3886 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2180 | 2.2180 | 2.2180 | 2.2180 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1703 | 1.1703 | 1.1703 | 1.1703 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1730 | 1.1730 | 1.1730 | 1.1730 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1764 | 1.1764 | 1.1764 | 1.1764 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1672 | 1.1672 | 1.1672 | 1.1672 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0521 | 2.0521 | 2.0521 | 2.0521 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0758 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0711 | 1.0711 | 1.0711 | 1.0711 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0742 | 1.0742 | 1.0742 | 1.0742 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2323 | 1.2323 | 1.2323 | 1.2323 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 17.26 | 99641.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 364.06 | 72850.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.01 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 105.60 | 11486.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.82 | 11639.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1125.99 |
Natural Gas | 0.00 | 17.26 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1143.26 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 174.16 |
Fans (All) | 50.52 |
Service Water Heating | 28.62 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 538.67 |
Subtotal | 538.67 |
Natural Gas [MJ/m2] | |
Space Heating | 8.26 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 8.26 |
Subtotal | 8.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.72 |
Space Heating | 1.51 |
Space Cooling | 31.84 |
Fans (All) | 9.24 |
Service Water Heating | 5.23 |
Receptacle Equipment | 11.21 |
Miscellaneous | 5.25 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7973.33 | 786.50 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 7874.83 | 885.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 8080.83 | 679.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 8341.17 | 418.50 | 0.33 | 0.00 | 0.00 |
SMSTORE5 | 8370.50 | 389.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8380.50 | 379.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8394.67 | 365.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8309.67 | 450.17 | 0.17 | 0.00 | 0.00 |
Min | 7874.83 | 5.67 | 0.00 | 0.00 | 0.00 |
Max | 8754.33 | 885.00 | 0.33 | 0.00 | 0.00 |
Average | 8323.30 | 436.60 | 0.10 | 0.00 | 0.00 |
Sum | 83233.00 | 4366.00 | 1.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25399.50 | 75.33 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 25399.83 | 75.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 25404.00 | 70.83 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 93020.00 | 190.00 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 45816.50 | 95.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45817.00 | 95.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45817.50 | 94.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45806.00 | 105.50 | 0.50 | 0.00 | 0.00 |
Min | 25399.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93020.00 | 190.00 | 1.00 | 0.00 | 0.00 |
Average | 48529.83 | 80.17 | 0.20 | 0.00 | 0.00 |
Sum | 485298.33 | 801.67 | 2.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5662.67 | 3097.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7471.83 | 1288.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4678.33 | 4081.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4702.17 | 4057.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4642.50 | 4117.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4383.83 | 4376.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4398.17 | 4361.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4381.83 | 4378.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4387.83 | 4372.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4620.83 | 4139.17 | 0.00 | 0.00 | 0.00 |
Min | 4381.83 | 1288.17 | 0.00 | 0.00 | 0.00 |
Max | 7471.83 | 4378.17 | 0.00 | 0.00 | 0.00 |
Average | 4933.00 | 3827.00 | 0.00 | 0.00 | 0.00 |
Sum | 49330.00 | 38270.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 71933.00 | 17108.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 36497.33 | 7279.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 19095.67 | 6379.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 19120.33 | 6354.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18744.00 | 6731.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 59825.33 | 33385.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29080.33 | 16831.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28891.17 | 17020.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28746.67 | 17165.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 31602.50 | 14309.50 | 0.00 | 0.00 | 0.00 |
Min | 18744.00 | 6354.67 | 0.00 | 0.00 | 0.00 |
Max | 71933.00 | 33385.67 | 0.00 | 0.00 | 0.00 |
Average | 34353.63 | 14256.57 | 0.00 | 0.00 | 0.00 |
Sum | 343536.33 | 142565.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.788269E+10 | 12582.24 | 01-JAN-14:00 | 26.00 | 17.88 | 0.128212E+10 | 1685.93 | 15-JAN-17:10 | 20.45 | 13.98 |
February | 0.747306E+10 | 14929.15 | 28-FEB-08:63 | 19.50 | 18.32 | 0.120005E+10 | 1685.91 | 19-FEB-13:30 | 19.50 | 18.32 |
March | 0.863807E+10 | 14008.48 | 07-MAR-08:63 | 21.47 | 19.93 | 0.133586E+10 | 1686.01 | 26-MAR-12:00 | 29.40 | 20.20 |
April | 0.114582E+11 | 29977.40 | 30-APR-07:02 | 21.50 | 20.38 | 0.136044E+10 | 1686.04 | 22-APR-12:39 | 21.50 | 20.38 |
May | 0.172074E+11 | 35136.22 | 07-MAY-07:02 | 24.60 | 22.15 | 0.140171E+10 | 1686.08 | 19-MAY-12:50 | 32.70 | 23.70 |
June | 0.179600E+11 | 36205.08 | 11-JUN-07:02 | 23.58 | 20.40 | 0.135470E+10 | 1686.04 | 30-JUN-12:20 | 30.97 | 24.54 |
July | 0.190257E+11 | 35283.88 | 09-JUL-07:01 | 28.48 | 25.79 | 0.141294E+10 | 1686.06 | 02-JUL-16:10 | 28.48 | 25.79 |
August | 0.198766E+11 | 38139.86 | 31-AUG-07:02 | 25.45 | 23.81 | 0.139425E+10 | 1686.06 | 12-AUG-12:50 | 25.45 | 23.81 |
September | 0.178592E+11 | 34252.55 | 22-SEP-07:02 | 21.97 | 19.93 | 0.136536E+10 | 1686.07 | 23-SEP-12:30 | 30.80 | 24.15 |
October | 0.176946E+11 | 47755.63 | 26-OCT-07:02 | 21.83 | 13.09 | 0.140945E+10 | 1686.08 | 09-OCT-12:20 | 21.83 | 13.09 |
November | 0.114748E+11 | 32876.26 | 01-NOV-07:02 | 23.38 | 22.59 | 0.135708E+10 | 1686.05 | 05-NOV-16:10 | 27.02 | 19.59 |
December | 0.939495E+10 | 38826.02 | 17-DEC-08:62 | 19.83 | 15.88 | 0.134561E+10 | 1686.03 | 10-DEC-13:30 | 19.83 | 15.88 |
Annual Sum or Average | 0.165945E+12 | 0.162196E+11 | ||||||||
Minimum of Months | 0.747306E+10 | 12582.24 | 19.50 | 13.09 | 0.120005E+10 | 1685.91 | 19.50 | 13.09 | ||
Maximum of Months | 0.198766E+11 | 47755.63 | 28.48 | 25.79 | 0.141294E+10 | 1686.08 | 32.70 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403191E+10 | 15181.14 | 29-JAN-19:23 | 19.00 | 15.30 | 0.667945E+09 | 843.19 | 01-JAN-18:30 | 19.00 | 15.30 |
February | 0.412211E+10 | 13095.69 | 20-FEB-18:50 | 19.08 | 17.46 | 0.614353E+09 | 842.99 | 24-FEB-13:39 | 27.37 | 21.42 |
March | 0.485918E+10 | 16870.44 | 04-MAR-19:08 | 21.42 | 13.84 | 0.679926E+09 | 843.02 | 05-MAR-18:00 | 21.10 | 17.83 |
April | 0.652640E+10 | 18594.12 | 30-APR-07:02 | 21.50 | 20.38 | 0.679643E+09 | 843.00 | 23-APR-17:30 | 21.50 | 20.38 |
May | 0.938502E+10 | 21705.95 | 30-MAY-07:02 | 26.28 | 23.33 | 0.700852E+09 | 843.02 | 19-MAY-12:39 | 26.28 | 23.33 |
June | 0.964367E+10 | 22479.06 | 26-JUN-07:02 | 25.68 | 23.94 | 0.677351E+09 | 843.12 | 11-JUN-17:49 | 25.68 | 23.94 |
July | 0.101509E+11 | 21778.11 | 09-JUL-07:01 | 28.48 | 25.79 | 0.706463E+09 | 843.02 | 09-JUL-17:40 | 30.20 | 24.85 |
August | 0.104092E+11 | 22562.02 | 31-AUG-07:02 | 25.45 | 23.81 | 0.697113E+09 | 843.01 | 12-AUG-12:50 | 25.45 | 23.81 |
September | 0.944568E+10 | 21722.06 | 02-SEP-07:02 | 25.97 | 24.31 | 0.682668E+09 | 843.00 | 23-SEP-12:20 | 30.70 | 24.24 |
October | 0.941872E+10 | 25822.25 | 26-OCT-07:02 | 21.83 | 13.09 | 0.704345E+09 | 843.06 | 08-OCT-17:00 | 21.83 | 13.09 |
November | 0.640617E+10 | 21842.78 | 03-NOV-07:02 | 21.47 | 21.47 | 0.679512E+09 | 843.16 | 05-NOV-17:19 | 25.73 | 19.70 |
December | 0.512870E+10 | 22102.59 | 17-DEC-08:62 | 19.83 | 15.88 | 0.684493E+09 | 843.00 | 10-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.895277E+11 | 0.817467E+10 | ||||||||
Minimum of Months | 0.403191E+10 | 13095.69 | 19.00 | 13.09 | 0.614353E+09 | 842.99 | 19.00 | 13.09 | ||
Maximum of Months | 0.104092E+11 | 25822.25 | 28.48 | 25.79 | 0.706463E+09 | 843.19 | 30.70 | 24.85 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303153E+10 | 10340.66 | 02-JAN-07:03 | 15.83 | 15.23 | 0.385523E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.300023E+10 | 9955.39 | 28-FEB-07:03 | 18.90 | 18.08 | 0.362204E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.354966E+10 | 9877.16 | 30-MAR-06:03 | 20.50 | 19.29 | 0.413388E+09 | 842.93 | 04-MAR-13:09 | 20.50 | 19.29 |
April | 0.468975E+10 | 16879.15 | 28-APR-06:03 | 23.22 | 22.07 | 0.410030E+09 | 842.99 | 22-APR-12:39 | 23.22 | 22.07 |
May | 0.716908E+10 | 18475.98 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426370E+09 | 843.00 | 27-MAY-12:09 | 31.28 | 24.76 |
June | 0.747504E+10 | 19166.52 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417355E+09 | 842.98 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.773626E+10 | 17341.67 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420488E+09 | 843.01 | 01-JUL-12:00 | 26.88 | 24.44 |
August | 0.813434E+10 | 19135.27 | 31-AUG-06:02 | 24.00 | 23.17 | 0.432045E+09 | 843.01 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.715823E+10 | 18002.65 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411131E+09 | 843.01 | 23-SEP-12:20 | 30.70 | 24.24 |
October | 0.712307E+10 | 24576.32 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420498E+09 | 842.99 | 14-OCT-12:09 | 22.00 | 13.53 |
November | 0.465460E+10 | 18040.42 | 08-NOV-07:02 | 19.50 | 18.38 | 0.404214E+09 | 842.95 | 25-NOV-13:09 | 20.42 | 14.33 |
December | 0.373027E+10 | 20953.26 | 17-DEC-08:62 | 19.83 | 15.88 | 0.397405E+09 | 842.99 | 02-DEC-13:30 | 19.83 | 15.88 |
Annual Sum or Average | 0.674521E+11 | 0.490065E+10 | ||||||||
Minimum of Months | 0.300023E+10 | 9877.16 | 15.83 | 13.53 | 0.362204E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.813434E+10 | 24576.32 | 26.88 | 24.44 | 0.432045E+09 | 843.01 | 31.28 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290782E+10 | 10150.70 | 02-JAN-07:03 | 15.83 | 15.23 | 0.383272E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.289778E+10 | 9608.63 | 28-FEB-07:03 | 18.90 | 18.08 | 0.361097E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.345878E+10 | 9700.89 | 30-MAR-06:03 | 20.50 | 19.29 | 0.412617E+09 | 842.93 | 04-MAR-13:09 | 20.50 | 19.29 |
April | 0.464510E+10 | 16899.52 | 28-APR-06:03 | 23.22 | 22.07 | 0.409980E+09 | 842.99 | 22-APR-12:39 | 23.22 | 22.07 |
May | 0.718641E+10 | 18557.54 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426368E+09 | 843.00 | 27-MAY-12:09 | 31.28 | 24.76 |
June | 0.750469E+10 | 19261.91 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417356E+09 | 842.98 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.778146E+10 | 17428.49 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420490E+09 | 843.00 | 01-JUL-12:00 | 26.88 | 24.44 |
August | 0.817167E+10 | 19226.36 | 31-AUG-06:02 | 24.00 | 23.17 | 0.432046E+09 | 843.00 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.719045E+10 | 18071.63 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411132E+09 | 843.01 | 23-SEP-12:20 | 30.70 | 24.24 |
October | 0.714270E+10 | 24665.09 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420493E+09 | 842.99 | 14-OCT-12:09 | 22.00 | 13.53 |
November | 0.459796E+10 | 18098.27 | 08-NOV-07:02 | 19.50 | 18.38 | 0.404079E+09 | 842.95 | 25-NOV-13:00 | 20.00 | 14.21 |
December | 0.363566E+10 | 21001.52 | 17-DEC-08:62 | 19.83 | 15.88 | 0.396461E+09 | 842.96 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.671205E+11 | 0.489539E+10 | ||||||||
Minimum of Months | 0.289778E+10 | 9608.63 | 15.83 | 13.53 | 0.361097E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.817167E+10 | 24665.09 | 26.88 | 24.44 | 0.432046E+09 | 843.01 | 31.28 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271014E+10 | 9093.25 | 02-JAN-07:03 | 15.83 | 15.23 | 0.380018E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.270268E+10 | 8317.81 | 28-FEB-07:03 | 18.90 | 18.08 | 0.359171E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.324789E+10 | 8382.24 | 30-MAR-06:03 | 20.50 | 19.29 | 0.410988E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.443473E+10 | 15626.06 | 30-APR-07:02 | 21.50 | 20.38 | 0.409831E+09 | 842.99 | 22-APR-12:39 | 21.50 | 20.38 |
May | 0.700538E+10 | 18292.33 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426334E+09 | 842.99 | 27-MAY-12:09 | 31.28 | 24.76 |
June | 0.733226E+10 | 18969.93 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417323E+09 | 842.97 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.761692E+10 | 17123.12 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420458E+09 | 843.00 | 01-JUL-12:00 | 26.88 | 24.44 |
August | 0.800113E+10 | 18943.92 | 31-AUG-06:02 | 24.00 | 23.17 | 0.432013E+09 | 843.00 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.703165E+10 | 17815.41 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411102E+09 | 843.01 | 23-SEP-12:30 | 30.80 | 24.15 |
October | 0.697199E+10 | 24328.17 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420434E+09 | 843.00 | 21-OCT-12:20 | 22.00 | 13.53 |
November | 0.439992E+10 | 17815.68 | 08-NOV-07:02 | 19.50 | 18.38 | 0.403726E+09 | 842.95 | 25-NOV-13:50 | 20.08 | 14.24 |
December | 0.343535E+10 | 20714.92 | 17-DEC-08:62 | 19.83 | 15.88 | 0.394918E+09 | 842.96 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.648900E+11 | 0.488631E+10 | ||||||||
Minimum of Months | 0.270268E+10 | 8317.81 | 15.83 | 13.53 | 0.359171E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.800113E+10 | 24328.17 | 26.88 | 24.44 | 0.432013E+09 | 843.01 | 31.28 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437106E+10 | 14698.94 | 01-JAN-09:03 | 19.17 | 15.96 | 0.128595E+10 | 2247.90 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.434165E+10 | 12551.81 | 28-FEB-08:63 | 19.50 | 18.32 | 0.121927E+10 | 2247.80 | 11-FEB-15:00 | 19.50 | 18.32 |
March | 0.520377E+10 | 11006.73 | 26-MAR-14:10 | 28.97 | 20.05 | 0.140037E+10 | 2247.88 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.725610E+10 | 27322.34 | 29-APR-07:03 | 24.08 | 22.45 | 0.140730E+10 | 2248.07 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.119018E+11 | 33095.11 | 12-MAY-07:02 | 23.98 | 20.89 | 0.145817E+10 | 2248.08 | 06-MAY-14:39 | 23.98 | 20.89 |
June | 0.125430E+11 | 34420.32 | 14-JUN-07:02 | 26.88 | 23.48 | 0.143033E+10 | 2248.08 | 03-JUN-14:50 | 26.88 | 23.48 |
July | 0.129872E+11 | 32249.15 | 19-JUL-07:02 | 28.07 | 25.39 | 0.143894E+10 | 2248.04 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.137335E+11 | 35450.39 | 31-AUG-07:02 | 25.45 | 23.81 | 0.148046E+10 | 2248.08 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.119967E+11 | 32145.36 | 23-SEP-07:02 | 23.08 | 21.03 | 0.141084E+10 | 2248.04 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.119052E+11 | 43727.21 | 26-OCT-07:02 | 21.83 | 13.09 | 0.143507E+10 | 2248.00 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.718765E+10 | 31835.85 | 07-NOV-08:62 | 22.47 | 20.72 | 0.137419E+10 | 2248.04 | 04-NOV-14:30 | 22.47 | 20.72 |
December | 0.558794E+10 | 30752.74 | 17-DEC-09:02 | 19.00 | 14.29 | 0.134524E+10 | 2248.04 | 09-DEC-15:30 | 19.00 | 14.29 |
Annual Sum or Average | 0.109016E+12 | 0.166861E+11 | ||||||||
Minimum of Months | 0.434165E+10 | 11006.73 | 19.00 | 13.09 | 0.121927E+10 | 2247.80 | 19.00 | 13.09 | ||
Maximum of Months | 0.137335E+11 | 43727.21 | 28.97 | 25.39 | 0.148046E+10 | 2248.08 | 30.00 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212722E+10 | 6853.42 | 01-JAN-09:03 | 19.17 | 15.96 | 0.640354E+09 | 1123.92 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.214202E+10 | 5714.48 | 28-FEB-08:63 | 19.50 | 18.32 | 0.607754E+09 | 1123.87 | 11-FEB-15:00 | 19.50 | 18.32 |
March | 0.259507E+10 | 5755.70 | 26-MAR-14:10 | 28.97 | 20.05 | 0.698561E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.371888E+10 | 13050.69 | 29-APR-07:03 | 24.08 | 22.45 | 0.703560E+09 | 1124.00 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.622659E+10 | 17250.64 | 12-MAY-07:02 | 23.98 | 20.89 | 0.729056E+09 | 1123.99 | 06-MAY-14:30 | 23.98 | 20.89 |
June | 0.656693E+10 | 17964.54 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715130E+09 | 1124.01 | 03-JUN-14:50 | 26.88 | 23.48 |
July | 0.679854E+10 | 16828.56 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719433E+09 | 1123.99 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.718016E+10 | 18492.69 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740196E+09 | 1124.00 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.625394E+10 | 16756.31 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705384E+09 | 1123.98 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.618273E+10 | 22779.96 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717507E+09 | 1123.96 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.365432E+10 | 15753.25 | 03-NOV-07:02 | 21.47 | 21.47 | 0.686819E+09 | 1123.93 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.277949E+10 | 14779.83 | 17-DEC-09:02 | 19.00 | 14.29 | 0.671426E+09 | 1123.99 | 09-DEC-15:20 | 19.00 | 14.29 |
Annual Sum or Average | 0.562259E+11 | 0.833518E+10 | ||||||||
Minimum of Months | 0.212722E+10 | 5714.48 | 19.00 | 13.09 | 0.607754E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.718016E+10 | 22779.96 | 28.97 | 25.39 | 0.740196E+09 | 1124.01 | 30.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206950E+10 | 6370.76 | 01-JAN-09:03 | 19.17 | 15.96 | 0.638693E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.208820E+10 | 5487.00 | 24-FEB-14:00 | 27.20 | 21.39 | 0.606433E+09 | 1123.87 | 11-FEB-15:00 | 27.20 | 21.39 |
March | 0.253512E+10 | 5682.81 | 26-MAR-14:10 | 28.97 | 20.05 | 0.697438E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.365795E+10 | 12607.95 | 29-APR-07:03 | 24.08 | 22.45 | 0.703455E+09 | 1124.00 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.617416E+10 | 17151.57 | 12-MAY-07:02 | 23.98 | 20.89 | 0.729050E+09 | 1123.99 | 06-MAY-14:30 | 23.98 | 20.89 |
June | 0.651764E+10 | 17858.69 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715125E+09 | 1124.01 | 03-JUN-14:50 | 26.88 | 23.48 |
July | 0.675349E+10 | 16726.35 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719426E+09 | 1123.99 | 29-JUL-14:30 | 27.20 | 25.17 |
August | 0.713519E+10 | 18387.48 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740192E+09 | 1124.00 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.621070E+10 | 16659.71 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705378E+09 | 1123.98 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.613147E+10 | 22655.51 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717481E+09 | 1123.96 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.359585E+10 | 15636.08 | 03-NOV-07:02 | 21.47 | 21.47 | 0.686558E+09 | 1123.93 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.271967E+10 | 14341.57 | 17-DEC-09:02 | 19.00 | 14.29 | 0.670328E+09 | 1123.98 | 16-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.555889E+11 | 0.832956E+10 | ||||||||
Minimum of Months | 0.206950E+10 | 5487.00 | 19.00 | 13.09 | 0.606433E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.713519E+10 | 22655.51 | 28.97 | 25.39 | 0.740192E+09 | 1124.01 | 30.00 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193134E+10 | 5549.83 | 01-JAN-15:10 | 25.00 | 18.55 | 0.635227E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.195580E+10 | 5373.20 | 24-FEB-14:00 | 27.20 | 21.39 | 0.603490E+09 | 1123.87 | 11-FEB-15:00 | 27.20 | 21.39 |
March | 0.239087E+10 | 5577.05 | 26-MAR-14:10 | 28.97 | 20.05 | 0.694736E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.351804E+10 | 11199.24 | 29-APR-07:03 | 24.08 | 22.45 | 0.703062E+09 | 1123.99 | 29-APR-14:00 | 30.00 | 23.99 |
May | 0.611579E+10 | 17129.83 | 12-MAY-07:02 | 23.98 | 20.89 | 0.729043E+09 | 1124.00 | 06-MAY-14:39 | 23.98 | 20.89 |
June | 0.648559E+10 | 17836.12 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715121E+09 | 1124.01 | 03-JUN-14:00 | 26.88 | 23.48 |
July | 0.674932E+10 | 16733.64 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719425E+09 | 1123.98 | 29-JUL-14:30 | 27.20 | 25.17 |
August | 0.714842E+10 | 18418.76 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740192E+09 | 1124.00 | 26-AUG-14:39 | 25.45 | 23.81 |
September | 0.620356E+10 | 16667.56 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705379E+09 | 1123.98 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.609422E+10 | 22671.91 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717400E+09 | 1123.96 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.347994E+10 | 15602.43 | 03-NOV-07:02 | 21.47 | 21.47 | 0.685901E+09 | 1123.92 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.258513E+10 | 13066.57 | 17-DEC-09:02 | 19.00 | 14.29 | 0.667696E+09 | 1123.98 | 16-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.546580E+11 | 0.831667E+10 | ||||||||
Minimum of Months | 0.193134E+10 | 5373.20 | 19.00 | 13.09 | 0.603490E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.714842E+10 | 22671.91 | 28.97 | 25.39 | 0.740192E+09 | 1124.01 | 30.00 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178338E+10 | 5847.50 | 01-JAN-15:10 | 25.00 | 18.55 | 0.633420E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.186659E+10 | 5820.89 | 24-FEB-13:50 | 27.28 | 21.41 | 0.600291E+09 | 1123.87 | 11-FEB-15:00 | 27.28 | 21.41 |
March | 0.237927E+10 | 6121.43 | 26-MAR-14:10 | 28.97 | 20.05 | 0.691841E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.369481E+10 | 8108.44 | 28-APR-15:00 | 33.30 | 23.06 | 0.702460E+09 | 1123.96 | 22-APR-14:09 | 33.30 | 23.06 |
May | 0.683665E+10 | 17891.16 | 31-MAY-07:02 | 24.87 | 22.53 | 0.729110E+09 | 1123.99 | 27-MAY-14:00 | 24.87 | 22.53 |
June | 0.739496E+10 | 18438.69 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715211E+09 | 1123.96 | 24-JUN-14:00 | 27.20 | 23.27 |
July | 0.780556E+10 | 18066.60 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719567E+09 | 1124.00 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.832607E+10 | 21142.12 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740316E+09 | 1124.02 | 26-AUG-14:00 | 25.45 | 23.81 |
September | 0.711954E+10 | 18690.66 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705521E+09 | 1124.02 | 23-SEP-14:09 | 30.22 | 24.09 |
October | 0.688831E+10 | 23116.02 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717328E+09 | 1123.96 | 21-OCT-14:50 | 21.83 | 13.09 |
November | 0.365062E+10 | 17124.64 | 03-NOV-07:02 | 21.47 | 21.47 | 0.685341E+09 | 1123.90 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.249456E+10 | 9317.35 | 17-DEC-09:02 | 19.00 | 14.29 | 0.664790E+09 | 1124.00 | 16-DEC-15:30 | 19.00 | 14.29 |
Annual Sum or Average | 0.602403E+11 | 0.830520E+10 | ||||||||
Minimum of Months | 0.178338E+10 | 5820.89 | 19.00 | 13.09 | 0.600291E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.832607E+10 | 23116.02 | 33.30 | 25.39 | 0.740316E+09 | 1124.02 | 33.30 | 25.39 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116064E+09 | 58482.89 | 10-JAN-08:61 | 4.17 |
February | 0.142135E+09 | 59006.89 | 06-FEB-08:61 | 4.87 |
March | 0.190698E+09 | 51434.33 | 11-MAR-08:61 | 7.52 |
April | 41518429.65 | 1858.04 | 29-APR-07:05 | 24.08 |
May | 31456841.80 | 1909.63 | 15-MAY-07:05 | 25.28 |
June | 28095663.60 | 1891.76 | 08-JUN-07:05 | 23.58 |
July | 26304301.68 | 1895.73 | 19-JUL-07:05 | 28.07 |
August | 25601193.78 | 1903.66 | 03-AUG-07:05 | 26.88 |
September | 24765088.41 | 1879.69 | 22-SEP-07:04 | 21.97 |
October | 30659696.29 | 2239.76 | 26-OCT-07:04 | 21.83 |
November | 46826751.22 | 1951.70 | 07-NOV-08:05 | 22.47 |
December | 0.109050E+09 | 58766.25 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.813175E+09 | |||
Minimum of Months | 24765088.41 | 1858.04 | 3.50 | |
Maximum of Months | 0.190698E+09 | 59006.89 | 28.07 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41629001.18 | 2857.36 | 05-JAN-08:61 | 1.00 |
February | 38182166.54 | 13993.84 | 05-FEB-08:62 | -2.9 |
March | 50103928.49 | 4620.49 | 12-MAR-07:02 | 6.97 |
April | 20002327.04 | 1105.04 | 29-APR-07:05 | 24.08 |
May | 17740510.41 | 1147.48 | 31-MAY-07:04 | 24.87 |
June | 14814762.20 | 1137.25 | 16-JUN-07:04 | 27.48 |
July | 12555069.32 | 1134.34 | 14-JUL-07:04 | 24.82 |
August | 13557273.17 | 1136.68 | 19-AUG-07:04 | 24.58 |
September | 13744231.42 | 1146.80 | 22-SEP-07:04 | 21.97 |
October | 16012404.21 | 1260.47 | 26-OCT-07:04 | 21.83 |
November | 17234495.86 | 1151.45 | 03-NOV-07:04 | 21.47 |
December | 37920594.89 | 15414.02 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.293497E+09 | |||
Minimum of Months | 12555069.32 | 1105.04 | -2.9 | |
Maximum of Months | 50103928.49 | 15414.02 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46246215.66 | 4451.29 | 10-JAN-07:03 | 3.17 |
February | 54277031.55 | 22854.93 | 05-FEB-08:62 | -2.9 |
March | 58726941.53 | 14326.48 | 12-MAR-07:02 | 6.97 |
April | 29489507.26 | 1713.37 | 22-APR-17:03 | 30.13 |
May | 86572349.02 | 2529.07 | 28-MAY-16:02 | 33.43 |
June | 0.103675E+09 | 2349.53 | 25-JUN-16:02 | 32.70 |
July | 0.106114E+09 | 2837.96 | 22-JUL-17:02 | 34.63 |
August | 89719393.10 | 2567.97 | 27-AUG-16:02 | 33.67 |
September | 63986370.65 | 3276.78 | 09-SEP-17:02 | 36.18 |
October | 52227581.31 | 1851.63 | 08-OCT-16:02 | 30.67 |
November | 21465914.07 | 1092.90 | 07-NOV-07:05 | 20.78 |
December | 41844090.61 | 7175.06 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.754344E+09 | |||
Minimum of Months | 21465914.07 | 1092.90 | -2.9 | |
Maximum of Months | 0.106114E+09 | 22854.93 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50679051.66 | 7016.57 | 10-JAN-07:03 | 3.17 |
February | 62910714.94 | 26583.43 | 05-FEB-08:62 | -2.9 |
March | 68509990.12 | 18382.06 | 12-MAR-07:02 | 6.97 |
April | 30402775.22 | 1714.91 | 22-APR-17:03 | 30.13 |
May | 86470073.03 | 2530.01 | 28-MAY-16:02 | 33.43 |
June | 0.103458E+09 | 2349.77 | 25-JUN-16:02 | 32.70 |
July | 0.105762E+09 | 2838.15 | 22-JUL-17:02 | 34.63 |
August | 89245802.24 | 2567.62 | 27-AUG-16:02 | 33.67 |
September | 63531947.14 | 3277.55 | 09-SEP-17:02 | 36.18 |
October | 52125491.56 | 1851.22 | 08-OCT-16:02 | 30.67 |
November | 23012946.48 | 1097.67 | 07-NOV-07:05 | 20.78 |
December | 44048705.78 | 8569.38 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.780157E+09 | |||
Minimum of Months | 23012946.48 | 1097.67 | -2.9 | |
Maximum of Months | 0.105762E+09 | 26583.43 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59029657.49 | 9477.95 | 10-JAN-07:03 | 3.17 |
February | 72404200.75 | 30141.09 | 05-FEB-08:62 | -2.9 |
March | 82563728.30 | 22099.82 | 12-MAR-07:02 | 6.97 |
April | 31384270.07 | 1721.80 | 22-APR-17:03 | 30.13 |
May | 88184344.60 | 2534.18 | 28-MAY-16:02 | 33.43 |
June | 0.105459E+09 | 2353.72 | 25-JUN-16:02 | 32.70 |
July | 0.107185E+09 | 2843.22 | 22-JUL-17:02 | 34.63 |
August | 90853873.59 | 2571.41 | 27-AUG-16:02 | 33.67 |
September | 64582142.49 | 3281.34 | 09-SEP-17:02 | 36.18 |
October | 53978171.28 | 1854.38 | 08-OCT-16:02 | 30.67 |
November | 25464386.08 | 1049.61 | 07-NOV-07:05 | 20.78 |
December | 51946594.21 | 10302.76 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.833035E+09 | |||
Minimum of Months | 25464386.08 | 1049.61 | -2.9 | |
Maximum of Months | 0.107185E+09 | 30141.09 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133933E+09 | 54885.13 | 10-JAN-08:61 | 4.17 |
February | 0.156064E+09 | 55342.98 | 06-FEB-08:61 | 4.87 |
March | 0.171710E+09 | 55278.04 | 12-MAR-08:61 | 9.18 |
April | 62821492.11 | 3460.27 | 22-APR-17:03 | 30.13 |
May | 90625803.72 | 5083.90 | 28-MAY-16:02 | 33.43 |
June | 94724080.10 | 4721.16 | 25-JUN-16:02 | 32.70 |
July | 0.114349E+09 | 5699.99 | 22-JUL-17:02 | 34.63 |
August | 75221303.85 | 5162.53 | 27-AUG-16:02 | 33.67 |
September | 93172624.88 | 6556.78 | 09-SEP-17:02 | 36.18 |
October | 66426187.30 | 3713.02 | 08-OCT-16:02 | 30.67 |
November | 49842546.55 | 1865.85 | 05-NOV-16:03 | 27.02 |
December | 0.112861E+09 | 55132.58 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.122175E+10 | |||
Minimum of Months | 49842546.55 | 1865.85 | 3.50 | |
Maximum of Months | 0.171710E+09 | 55342.98 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81020181.88 | 28570.58 | 10-JAN-08:61 | 4.17 |
February | 99553664.24 | 28817.84 | 06-FEB-08:61 | 4.87 |
March | 0.105293E+09 | 28782.19 | 12-MAR-08:61 | 9.18 |
April | 34537360.70 | 1746.63 | 22-APR-17:03 | 30.13 |
May | 46900603.31 | 2548.10 | 28-MAY-16:02 | 33.43 |
June | 48051204.19 | 2367.58 | 25-JUN-16:02 | 32.70 |
July | 58600343.22 | 2864.51 | 22-JUL-17:02 | 34.63 |
August | 38791705.04 | 2586.04 | 27-AUG-16:02 | 33.67 |
September | 48404974.12 | 3294.70 | 09-SEP-17:02 | 36.18 |
October | 34646894.29 | 1865.73 | 08-OCT-16:02 | 30.67 |
November | 27970757.45 | 952.03 | 07-NOV-08:05 | 22.47 |
December | 69491194.05 | 28704.53 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.693262E+09 | |||
Minimum of Months | 27970757.45 | 952.03 | 3.50 | |
Maximum of Months | 0.105293E+09 | 28817.84 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90075560.29 | 28467.43 | 10-JAN-08:61 | 4.17 |
February | 0.110342E+09 | 28712.26 | 06-FEB-08:61 | 4.87 |
March | 0.112265E+09 | 28677.76 | 12-MAR-08:61 | 9.18 |
April | 35327207.88 | 1748.17 | 22-APR-17:03 | 30.13 |
May | 47005198.76 | 2549.04 | 28-MAY-16:02 | 33.43 |
June | 48141025.97 | 2368.45 | 25-JUN-16:02 | 32.70 |
July | 58675622.28 | 2865.60 | 22-JUL-17:02 | 34.63 |
August | 38795246.49 | 2586.86 | 27-AUG-16:02 | 33.67 |
September | 48386240.24 | 3295.46 | 09-SEP-17:02 | 36.18 |
October | 34835645.75 | 1866.63 | 08-OCT-16:02 | 30.67 |
November | 28441149.09 | 945.11 | 05-NOV-16:03 | 27.02 |
December | 73689629.18 | 28600.42 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.725980E+09 | |||
Minimum of Months | 28441149.09 | 945.11 | 3.50 | |
Maximum of Months | 0.112265E+09 | 28712.26 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119359E+09 | 28538.15 | 10-JAN-08:61 | 4.17 |
February | 0.138917E+09 | 28785.13 | 06-FEB-08:61 | 4.87 |
March | 0.138637E+09 | 28745.92 | 12-MAR-08:61 | 9.18 |
April | 38782559.99 | 1751.29 | 22-APR-17:03 | 30.13 |
May | 47781455.26 | 2550.47 | 28-MAY-16:02 | 33.43 |
June | 48370244.60 | 2369.23 | 25-JUN-16:02 | 32.70 |
July | 58835150.30 | 2865.17 | 22-JUL-17:02 | 34.63 |
August | 38734892.29 | 2586.26 | 27-AUG-16:02 | 33.67 |
September | 48323142.94 | 3295.52 | 09-SEP-17:02 | 36.18 |
October | 35503524.60 | 1866.26 | 08-OCT-16:02 | 30.67 |
November | 30256317.42 | 948.26 | 05-NOV-16:03 | 27.02 |
December | 91683625.61 | 28671.35 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.835184E+09 | |||
Minimum of Months | 30256317.42 | 948.26 | 3.50 | |
Maximum of Months | 0.138917E+09 | 28785.13 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268292E+09 | 31959.49 | 10-JAN-08:61 | 4.17 |
February | 0.268599E+09 | 32272.95 | 06-FEB-08:61 | 4.87 |
March | 0.272934E+09 | 32227.00 | 12-MAR-08:61 | 9.18 |
April | 46995246.95 | 1748.53 | 22-APR-17:03 | 30.13 |
May | 49894283.99 | 2538.22 | 28-MAY-16:02 | 33.43 |
June | 48383018.14 | 2353.20 | 25-JUN-16:02 | 32.70 |
July | 57608192.07 | 2830.55 | 22-JUL-17:02 | 34.63 |
August | 36820287.67 | 2555.50 | 27-AUG-16:02 | 33.67 |
September | 46824360.63 | 3272.01 | 09-SEP-17:02 | 36.18 |
October | 38438748.97 | 1843.76 | 08-OCT-16:02 | 30.67 |
November | 37521075.97 | 1190.35 | 16-NOV-08:65 | 11.88 |
December | 0.194305E+09 | 32128.01 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.136661E+10 | |||
Minimum of Months | 36820287.67 | 1190.35 | 3.50 | |
Maximum of Months | 0.272934E+09 | 32272.95 | 36.18 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559400.04 | 0.259370E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 0.188716E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266934E+09 | 0.165652E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755967E+09 | 0.585194E+09 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217043E+10 | 26436778.95 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234803E+10 | 21504556.07 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228137E+10 | 14410151.41 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233740E+10 | 34426815.54 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166158E+10 | 68440753.20 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153536E+10 | 0.367451E+09 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373075E+09 | 0.117723E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242260E+09 | 0.222994E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141650E+11 | 0.106624E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559400.04 | 14410151.41 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234803E+10 | 0.259370E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886309.45 | 0.139899E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878454.40 | 0.100890E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150067E+09 | 0.866848E+09 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426542E+09 | 0.291227E+09 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121911E+10 | 9139494.44 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132135E+10 | 6944416.23 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127897E+10 | 6273687.90 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131003E+10 | 11245198.59 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929083E+09 | 26776128.16 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858977E+09 | 0.160835E+09 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210862E+09 | 0.600165E+09 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137008E+09 | 0.116963E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795076E+10 | 0.555697E+10 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886309.45 | 6273687.90 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132135E+10 | 0.139899E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887467.50 | 0.139775E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805971.96 | 0.101805E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147657E+09 | 0.882855E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421286E+09 | 0.307290E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119582E+10 | 13378345.26 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130136E+10 | 10371598.01 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125024E+10 | 8028469.09 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129146E+10 | 19383316.16 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904610E+09 | 37171388.87 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837711E+09 | 0.177646E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207875E+09 | 0.616456E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136537E+09 | 0.118424E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780325E+10 | 0.567263E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887467.50 | 8028469.09 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130136E+10 | 0.139775E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.08 | 0.138245E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805966.50 | 0.100985E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147663E+09 | 0.876745E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421287E+09 | 0.306640E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119563E+10 | 13678918.14 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130113E+10 | 10679063.16 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124976E+10 | 8353745.78 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129114E+10 | 19873972.44 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904253E+09 | 37701396.86 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837627E+09 | 0.178243E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207878E+09 | 0.615132E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136538E+09 | 0.117730E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780160E+10 | 0.563665E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.08 | 8353745.78 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130113E+10 | 0.138245E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887457.58 | 0.136169E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805959.07 | 0.996949E+09 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147677E+09 | 0.864863E+09 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421364E+09 | 0.304487E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119624E+10 | 12395033.47 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130164E+10 | 9773215.83 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125062E+10 | 7652293.22 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129169E+10 | 18575221.20 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904723E+09 | 36306788.76 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837923E+09 | 0.176138E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207894E+09 | 0.611668E+09 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136541E+09 | 0.116666E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780501E+10 | 0.556715E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887457.58 | 7652293.22 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130164E+10 | 0.136169E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893203.66 | 0.239038E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120601E+09 | 0.175017E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259116E+09 | 0.152571E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738973E+09 | 0.546350E+09 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210018E+10 | 21370071.78 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228484E+10 | 17368734.51 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219576E+10 | 12792237.62 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226881E+10 | 32582792.63 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158837E+10 | 65735676.76 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147272E+10 | 0.327933E+09 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364510E+09 | 0.109269E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239256E+09 | 0.206308E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137030E+11 | 0.984618E+10 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893203.66 | 12792237.62 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228484E+10 | 0.239038E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887455.05 | 0.133013E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807038.54 | 0.974673E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147754E+09 | 0.844623E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421749E+09 | 0.302805E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119803E+10 | 10262134.90 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130359E+10 | 8325865.14 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125242E+10 | 6565508.43 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129369E+10 | 15929979.03 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905529E+09 | 33798253.85 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839708E+09 | 0.176796E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208018E+09 | 0.608702E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136548E+09 | 0.115054E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781572E+10 | 0.546315E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887455.05 | 6565508.43 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130359E+10 | 0.133013E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.33 | 0.132347E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807281.17 | 0.969410E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147764E+09 | 0.840038E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421779E+09 | 0.301900E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119825E+10 | 10018445.38 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130376E+10 | 8174599.29 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125268E+10 | 6471670.94 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129383E+10 | 15719587.37 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905670E+09 | 33551807.88 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839809E+09 | 0.176242E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208027E+09 | 0.607152E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136550E+09 | 0.114594E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781683E+10 | 0.543809E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.33 | 6471670.94 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130376E+10 | 0.132347E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887447.71 | 0.130876E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807767.11 | 0.956945E+09 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147783E+09 | 0.828277E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421826E+09 | 0.298675E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119876E+10 | 9265560.10 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130405E+10 | 7782302.57 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125296E+10 | 6253149.32 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129388E+10 | 15397108.35 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905644E+09 | 33061404.57 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839869E+09 | 0.174895E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208036E+09 | 0.603000E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136551E+09 | 0.113454E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781805E+10 | 0.537685E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887447.71 | 6253149.32 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130405E+10 | 0.130876E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553948.63 | 0.153851E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70151018.51 | 0.110937E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151445E+09 | 0.100182E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429369E+09 | 0.369319E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123010E+10 | 19018918.67 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133379E+10 | 17891677.14 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128654E+10 | 10789495.21 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132953E+10 | 35898750.49 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932814E+09 | 63079073.74 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863946E+09 | 0.265932E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211461E+09 | 0.731906E+09 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138741E+09 | 0.133910E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801845E+10 | 0.650263E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553948.63 | 10789495.21 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133379E+10 | 0.153851E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 16-JAN-15:00 | 7668.65 | 04-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 02-FEB-13:00 | 8462.73 | 04-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.25 | 26-MAR-14:00 | 7632.19 | 11-MAR-12:10 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.46 | 28-APR-15:00 | 3429.04 | 02-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.64 | 07-MAY-14:00 | 524.52 | 31-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.35 | 14-JUN-14:00 | 534.24 | 01-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.73 | 22-JUL-16:00 | 529.81 | 12-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.88 | 30-AUG-16:00 | 1008.29 | 16-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 09-SEP-17:00 | 1979.94 | 07-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.30 | 05-OCT-15:00 | 3395.48 | 27-OCT-16:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.24 | 01-NOV-14:00 | 6095.01 | 15-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.43 | 13-DEC-15:00 | 8685.40 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 524.52 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 8685.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.89 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.26 | 28-APR-15:00 | 1970.34 | 02-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.45 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.88 | 01-NOV-14:00 | 3517.71 | 15-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.26 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.33 | 28-APR-15:00 | 1959.10 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.08 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.03 | 01-NOV-14:00 | 3479.38 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.21 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.34 | 28-APR-15:00 | 1954.30 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.09 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.05 | 01-NOV-14:00 | 3463.27 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.20 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.84 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.34 | 28-APR-15:00 | 1942.30 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.11 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.06 | 01-NOV-14:00 | 3428.56 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.20 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 16-JAN-15:00 | 7613.97 | 04-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.02 | 02-FEB-13:00 | 8324.27 | 04-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.79 | 26-MAR-14:00 | 7527.14 | 11-MAR-12:10 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322.50 | 28-APR-15:00 | 3272.84 | 01-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.82 | 07-MAY-14:00 | 520.08 | 31-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.04 | 14-JUN-14:00 | 525.36 | 01-JUN-13:00 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.73 | 22-JUL-16:00 | 523.91 | 12-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.65 | 30-AUG-16:00 | 1000.01 | 16-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 09-SEP-17:00 | 1964.22 | 07-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.19 | 05-OCT-15:00 | 3357.64 | 27-OCT-16:00 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.75 | 01-NOV-14:00 | 5853.52 | 15-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.09 | 13-DEC-15:00 | 8649.42 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 520.08 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 8649.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.84 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.08 | 28-APR-15:00 | 1864.25 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.63 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.99 | 01-NOV-14:00 | 3324.83 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.08 | 28-APR-15:00 | 1864.25 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.63 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.99 | 01-NOV-14:00 | 3309.63 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.87 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.11 | 28-APR-15:00 | 1862.69 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.03 | 01-NOV-14:00 | 3277.52 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.21 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 16-JAN-15:00 | 4401.62 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 02-FEB-13:00 | 4883.41 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.54 | 26-MAR-14:00 | 4397.55 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 28-APR-15:00 | 1921.79 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.02 | 07-MAY-14:00 | 301.30 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.27 | 14-JUN-14:00 | 308.33 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.61 | 22-JUL-16:00 | 304.80 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.30 | 30-AUG-16:00 | 579.09 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 09-SEP-17:00 | 1136.97 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.14 | 05-OCT-15:00 | 1953.45 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 01-NOV-14:00 | 3244.88 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.38 | 13-DEC-15:00 | 4976.57 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 301.30 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 4976.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12582.24 | 01-JAN-14:00 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 987.53 | 0.00 |
February | 14929.15 | 28-FEB-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.14 |
March | 14008.48 | 07-MAR-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.63 |
April | 29977.40 | 30-APR-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.13 |
May | 35136.22 | 07-MAY-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 | 0.00 |
June | 36205.08 | 11-JUN-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.45 |
July | 35283.88 | 09-JUL-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 222.14 | 0.00 |
August | 38139.86 | 31-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 0.00 |
September | 34252.55 | 22-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.46 |
October | 47755.63 | 26-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.05 |
November | 32876.26 | 01-NOV-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.90 |
December | 38826.02 | 17-DEC-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12582.24 | 0.00 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47755.63 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 987.53 | 364.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15181.14 | 29-JAN-19:23 | 9449.82 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.90 |
February | 13095.69 | 20-FEB-18:50 | 12149.77 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.95 |
March | 16870.44 | 04-MAR-19:08 | 13499.74 | 24493.48 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.53 |
April | 18594.12 | 30-APR-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.77 |
May | 21705.95 | 30-MAY-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 62.75 | 0.00 |
June | 22479.06 | 26-JUN-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37.15 | 0.00 |
July | 21778.11 | 09-JUL-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 0.00 |
August | 22562.02 | 31-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.86 | 0.00 |
September | 21722.06 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 0.00 |
October | 25822.25 | 26-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.96 |
November | 21842.78 | 03-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 |
December | 22102.59 | 17-DEC-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13095.69 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25822.25 | 13499.74 | 24493.48 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 189.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10340.66 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 |
February | 9955.39 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
March | 9877.16 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
April | 16879.15 | 28-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
May | 18475.98 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
June | 19166.52 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
July | 17341.67 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 0.00 |
August | 19135.27 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18002.65 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
October | 24576.32 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 |
November | 18040.42 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 |
December | 20953.26 | 17-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9877.16 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24576.32 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 194.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10150.70 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 |
February | 9608.63 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
March | 9700.89 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
April | 16899.52 | 28-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
May | 18557.54 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 |
June | 19261.91 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 0.00 |
July | 17428.49 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
August | 19226.36 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18071.63 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
October | 24665.09 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
November | 18098.27 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
December | 21001.52 | 17-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9608.63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24665.09 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 194.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9093.25 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 |
February | 8317.81 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
March | 8382.24 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 15626.06 | 30-APR-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.37 |
May | 18292.33 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
June | 18969.93 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
July | 17123.12 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
August | 18943.92 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17815.41 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
October | 24328.17 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
November | 17815.68 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 |
December | 20714.92 | 17-DEC-08:62 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8317.81 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24328.17 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 190.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14698.94 | 01-JAN-09:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.21 |
February | 12551.81 | 28-FEB-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.36 |
March | 11006.73 | 26-MAR-14:10 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.10 | 0.00 |
April | 27322.34 | 29-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
May | 33095.11 | 12-MAY-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 |
June | 34420.32 | 14-JUN-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 137.34 | 0.00 |
July | 32249.15 | 19-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 205.97 | 0.00 |
August | 35450.39 | 31-AUG-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 38.22 | 0.00 |
September | 32145.36 | 23-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 |
October | 43727.21 | 26-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.88 |
November | 31835.85 | 07-NOV-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 |
December | 30752.74 | 17-DEC-09:02 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11006.73 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43727.21 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.10 | 400.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6853.42 | 01-JAN-09:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.50 |
February | 5714.48 | 28-FEB-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.33 |
March | 5755.70 | 26-MAR-14:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.14 | 0.00 |
April | 13050.69 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 0.00 |
May | 17250.64 | 12-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
June | 17964.54 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 81.95 | 0.00 |
July | 16828.56 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 120.98 | 0.00 |
August | 18492.69 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 0.00 |
September | 16756.31 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.94 |
October | 22779.96 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.43 |
November | 15753.25 | 03-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.10 |
December | 14779.83 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5714.48 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22779.96 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.14 | 224.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6370.76 | 01-JAN-09:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.33 |
February | 5487.00 | 24-FEB-14:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 882.60 | 0.00 |
March | 5682.81 | 26-MAR-14:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.14 | 0.00 |
April | 12607.95 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 0.00 |
May | 17151.57 | 12-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
June | 17858.69 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 | 0.00 |
July | 16726.35 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.68 | 0.00 |
August | 18387.48 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 0.00 |
September | 16659.71 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 |
October | 22655.51 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.68 |
November | 15636.08 | 03-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.22 |
December | 14341.57 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5487.00 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22655.51 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.14 | 224.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5549.83 | 01-JAN-15:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 5373.20 | 24-FEB-14:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 882.60 | 0.00 |
March | 5577.05 | 26-MAR-14:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.40 | 0.00 |
April | 11199.24 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
May | 17129.83 | 12-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
June | 17836.12 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 86.35 | 0.00 |
July | 16733.64 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.86 | 0.00 |
August | 18418.76 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 0.00 |
September | 16667.56 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 |
October | 22671.91 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
November | 15602.43 | 03-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.54 |
December | 13066.57 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5373.20 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22671.91 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.40 | 223.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5847.50 | 01-JAN-15:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 299.48 | 0.00 |
February | 5820.89 | 24-FEB-13:50 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 919.21 | 0.00 |
March | 6121.43 | 26-MAR-14:10 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1369.70 | 0.00 |
April | 8108.44 | 28-APR-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 0.00 |
May | 17891.16 | 31-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 0.00 |
June | 18438.69 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 94.50 | 0.00 |
July | 18066.60 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 131.60 | 0.00 |
August | 21142.12 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 | 0.00 |
September | 18690.66 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 0.00 |
October | 23116.02 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.67 |
November | 17124.64 | 03-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 |
December | 9317.35 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5820.89 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23116.02 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 266.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.711774E+11 | 74858.64 | 31-JAN-15:30 | 0.460627E+10 | 63873.00 | 10-JAN-08:09 |
February | 0.668992E+11 | 77628.68 | 02-FEB-13:20 | 0.494165E+10 | 99641.90 | 05-FEB-09:09 |
March | 0.769343E+11 | 80538.41 | 30-MAR-12:30 | 0.357240E+10 | 85191.19 | 11-MAR-12:09 |
April | 0.832052E+11 | 94106.72 | 28-APR-15:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.109801E+12 | 97461.97 | 24-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.111154E+12 | 105267.37 | 28-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.117546E+12 | 113865.78 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.119211E+12 | 107163.14 | 03-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.109087E+12 | 123501.72 | 10-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.105319E+12 | 112919.93 | 07-OCT-13:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.797157E+11 | 92464.21 | 03-NOV-12:50 | 530839.06 | 478.76 | 16-NOV-08:09 |
December | 0.759437E+11 | 86589.11 | 16-DEC-13:09 | 0.414148E+10 | 76272.46 | 20-DEC-17:00 |
Annual Sum or Average | 0.112599E+13 | 0.172623E+11 | ||||
Minimum of Months | 0.668992E+11 | 74858.64 | 0.00 | 0.00 | ||
Maximum of Months | 0.119211E+12 | 123501.72 | 0.494165E+10 | 99641.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.605968E+10 | 0.108325E+11 | 0.00 | 0.867114E+10 | 0.00 | 0.00 | 0.584304E+10 | 0.00 | 0.00 | 0.00 | 0.524297E+10 | 0.00 |
February | 0.312534E+11 | 0.514443E+10 | 0.980803E+10 | 0.00 | 0.789232E+10 | 0.00 | 0.00 | 0.807291E+10 | 0.00 | 0.00 | 0.00 | 0.472809E+10 | 0.00 |
March | 0.350527E+11 | 0.520057E+10 | 0.110075E+11 | 0.00 | 0.881598E+10 | 0.00 | 0.00 | 0.116430E+11 | 0.00 | 0.00 | 0.00 | 0.521453E+10 | 0.00 |
April | 0.334898E+11 | 0.455295E+10 | 0.105079E+11 | 0.00 | 0.837504E+10 | 0.00 | 0.00 | 0.213427E+11 | 0.00 | 0.00 | 0.00 | 0.493676E+10 | 0.00 |
May | 0.347840E+11 | 0.427208E+10 | 0.109147E+11 | 0.00 | 0.884957E+10 | 0.00 | 0.00 | 0.459610E+11 | 0.00 | 0.00 | 0.00 | 0.502010E+10 | 0.00 |
June | 0.338757E+11 | 0.389871E+10 | 0.106386E+11 | 0.00 | 0.888290E+10 | 0.00 | 0.00 | 0.490483E+11 | 0.00 | 0.00 | 0.00 | 0.481002E+10 | 0.00 |
July | 0.344108E+11 | 0.415313E+10 | 0.107945E+11 | 0.00 | 0.947307E+10 | 0.00 | 0.00 | 0.538104E+11 | 0.00 | 0.00 | 0.00 | 0.490392E+10 | 0.00 |
August | 0.350409E+11 | 0.450338E+10 | 0.110006E+11 | 0.00 | 0.958917E+10 | 0.00 | 0.00 | 0.541286E+11 | 0.00 | 0.00 | 0.00 | 0.494845E+10 | 0.00 |
September | 0.335014E+11 | 0.483051E+10 | 0.105148E+11 | 0.00 | 0.890126E+10 | 0.00 | 0.00 | 0.465253E+11 | 0.00 | 0.00 | 0.00 | 0.481399E+10 | 0.00 |
October | 0.345281E+11 | 0.549465E+10 | 0.108325E+11 | 0.00 | 0.905512E+10 | 0.00 | 0.00 | 0.403682E+11 | 0.00 | 0.00 | 0.00 | 0.504065E+10 | 0.00 |
November | 0.334535E+11 | 0.573587E+10 | 0.104978E+11 | 0.00 | 0.841100E+10 | 0.00 | 0.00 | 0.166550E+11 | 0.00 | 0.00 | 0.00 | 0.496245E+10 | 0.00 |
December | 0.344233E+11 | 0.616872E+10 | 0.108050E+11 | 0.00 | 0.868436E+10 | 0.00 | 0.00 | 0.106617E+11 | 0.00 | 0.00 | 0.00 | 0.520068E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.600147E+11 | 0.128154E+12 | 0.00 | 0.105601E+12 | 0.00 | 0.00 | 0.364060E+12 | 0.00 | 0.00 | 0.00 | 0.598226E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.389871E+10 | 0.980803E+10 | 0.00 | 0.789232E+10 | 0.00 | 0.00 | 0.584304E+10 | 0.00 | 0.00 | 0.00 | 0.472809E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.616872E+10 | 0.110075E+11 | 0.00 | 0.958917E+10 | 0.00 | 0.00 | 0.541286E+11 | 0.00 | 0.00 | 0.00 | 0.524297E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.460627E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.494165E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.357240E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 530839.06 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.414148E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172623E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.494165E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 7144.11 | 10-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7853.37 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7563.87 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7162.68 | 28-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7885.22 | 22-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 8803.73 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 10004.28 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8811.73 | 07-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11486.69 | 10-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10228.36 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7222.20 | 07-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7387.87 | 20-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 7144.11 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 11486.69 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 30688.69 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11639.66 | 01-JAN-08:30 | 0.00 |
February | 32921.13 | 24-FEB-13:09 | 0.00 | 0.00 | 0.00 | 9029.69 | 10-FEB-14:30 | 0.00 |
March | 36261.03 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7570.83 | 11-MAR-13:50 | 0.00 |
April | 48957.35 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 7558.88 | 28-APR-12:09 | 0.00 |
May | 52112.52 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 8824.28 | 29-MAY-15:50 | 0.00 |
June | 58344.66 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 | 8789.28 | 06-JUN-18:19 | 0.00 |
July | 66224.09 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 9127.67 | 11-JUL-12:30 | 0.00 |
August | 58740.72 | 03-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7544.24 | 11-AUG-13:00 | 0.00 |
September | 72850.37 | 10-SEP-14:09 | 0.00 | 0.00 | 0.00 | 7550.54 | 26-SEP-13:30 | 0.00 |
October | 64660.16 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7560.54 | 27-OCT-12:30 | 0.00 |
November | 46694.24 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 9664.70 | 27-NOV-12:30 | 0.00 |
December | 39366.51 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9687.87 | 21-DEC-14:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30688.69 | 0.00 | 0.00 | 0.00 | 7544.24 | 0.00 | ||
Maximum of Months | 72850.37 | 0.00 | 0.00 | 0.00 | 11639.66 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 74858.64 | 31-JAN-15:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5875.64 | 0.00 | 0.00 | 27108.49 | 0.00 |
February | 77628.68 | 02-FEB-13:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5875.64 | 0.00 | 0.00 | 31981.29 | 0.00 |
March | 80538.41 | 30-MAR-12:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5875.64 | 0.00 | 0.00 | 34895.88 | 0.00 |
April | 94106.72 | 28-APR-15:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6695.59 | 0.00 | 0.00 | 46880.31 | 0.00 |
May | 97461.97 | 24-MAY-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7704.05 | 0.00 | 0.00 | 52112.52 | 0.00 |
June | 105267.37 | 28-JUN-13:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8440.05 | 0.00 | 0.00 | 55991.42 | 0.00 |
July | 113865.78 | 22-JUL-15:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 10004.28 | 0.00 | 0.00 | 66224.09 | 0.00 |
August | 107163.14 | 03-AUG-16:10 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8687.46 | 0.00 | 0.00 | 58732.56 | 0.00 |
September | 123501.72 | 10-SEP-12:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11386.52 | 0.00 | 0.00 | 72380.61 | 0.00 |
October | 112919.93 | 07-OCT-13:39 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9935.76 | 0.00 | 0.00 | 63225.06 | 0.00 |
November | 92464.21 | 03-NOV-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6520.16 | 0.00 | 0.00 | 44269.24 | 0.00 |
December | 86589.11 | 16-DEC-13:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5875.64 | 0.00 | 0.00 | 38077.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 74858.64 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5875.64 | 0.00 | 0.00 | 27108.49 | 0.00 | |
Maximum of Months | 123501.72 | 26261.30 | 8059.50 | 0.00 | 0.00 | 11386.52 | 0.00 | 0.00 | 72380.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 63873.00 | 10-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 99641.90 | 05-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 85191.19 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 478.76 | 16-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 76272.46 | 20-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 99641.90 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.68 | 0.00 | 24.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.62 | 0.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.68 | 0.00 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.77 | 0.00 | 24.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.53 | 0.00 | 20.53 | 0.50 | 23.63 | 0.00 | 23.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.53 | 0.00 | 20.53 | 0.33 | 24.77 | 0.00 | 24.77 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 332.83 | 22.16 | 158.17 | 22.68 | 38.83 | 22.74 |
February | 259.67 | 22.63 | 224.17 | 23.17 | 76.33 | 23.22 |
March | 228.67 | 22.57 | 223.33 | 23.19 | 43.33 | 23.22 |
April | 84.33 | 23.71 | 365.83 | 23.85 | 53.33 | 23.86 |
May | 114.83 | 23.89 | 496.00 | 23.89 | 114.83 | 23.89 |
June | 109.33 | 23.89 | 481.00 | 23.89 | 109.33 | 23.89 |
July | 225.33 | 23.89 | 495.00 | 23.89 | 225.33 | 23.89 |
August | 137.50 | 23.89 | 497.00 | 23.89 | 137.50 | 23.89 |
September | 162.17 | 23.89 | 479.00 | 23.89 | 162.17 | 23.89 |
October | 113.83 | 23.85 | 447.17 | 23.88 | 104.50 | 23.88 |
November | 98.33 | 23.48 | 321.83 | 23.79 | 39.67 | 23.80 |
December | 223.50 | 22.40 | 224.33 | 23.13 | 35.33 | 23.17 |
Annual Sum or Average | 2090.33 | 23.13 | 4412.83 | 23.63 | 1140.50 | 23.66 |
Minimum of Months | 84.33 | 22.16 | 158.17 | 22.68 | 35.33 | 22.74 |
Maximum of Months | 332.83 | 23.89 | 497.00 | 23.89 | 225.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.00 | 22.75 | 152.50 | 23.15 | 14.83 | 23.17 |
February | 182.33 | 22.92 | 211.33 | 23.43 | 35.17 | 23.46 |
March | 168.83 | 22.90 | 211.33 | 23.45 | 11.67 | 23.46 |
April | 34.67 | 23.74 | 337.00 | 23.87 | 14.00 | 23.87 |
May | 61.33 | 23.89 | 488.67 | 23.89 | 61.33 | 23.89 |
June | 62.67 | 23.89 | 477.17 | 23.89 | 62.67 | 23.89 |
July | 152.17 | 23.89 | 494.67 | 23.89 | 152.17 | 23.89 |
August | 85.67 | 23.89 | 496.00 | 23.89 | 85.67 | 23.89 |
September | 112.33 | 23.89 | 476.33 | 23.89 | 112.33 | 23.89 |
October | 84.67 | 23.85 | 432.17 | 23.88 | 76.83 | 23.88 |
November | 61.83 | 23.68 | 306.83 | 23.85 | 25.33 | 23.85 |
December | 175.83 | 22.77 | 221.50 | 23.39 | 21.50 | 23.42 |
Annual Sum or Average | 1452.33 | 23.29 | 4305.50 | 23.74 | 673.50 | 23.75 |
Minimum of Months | 34.67 | 22.75 | 152.50 | 23.15 | 11.67 | 23.17 |
Maximum of Months | 270.00 | 23.89 | 496.00 | 23.89 | 152.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.83 | 22.31 | 118.33 | 22.84 | 23.33 | 22.89 |
February | 164.00 | 22.63 | 169.33 | 23.28 | 36.17 | 23.32 |
March | 158.33 | 22.66 | 169.17 | 23.35 | 26.83 | 23.40 |
April | 64.17 | 23.90 | 279.67 | 23.99 | 44.83 | 24.01 |
May | 103.00 | 24.32 | 375.00 | 24.13 | 103.00 | 24.16 |
June | 114.83 | 24.38 | 366.00 | 24.16 | 114.83 | 24.20 |
July | 215.50 | 24.22 | 369.00 | 24.14 | 215.50 | 24.16 |
August | 144.67 | 24.28 | 379.00 | 24.14 | 144.67 | 24.17 |
September | 170.17 | 24.22 | 360.00 | 24.12 | 170.17 | 24.15 |
October | 107.50 | 24.18 | 335.00 | 24.10 | 101.17 | 24.13 |
November | 77.67 | 23.73 | 249.33 | 23.93 | 43.50 | 23.96 |
December | 170.67 | 22.53 | 170.83 | 23.24 | 35.00 | 23.31 |
Annual Sum or Average | 1728.33 | 23.48 | 3340.67 | 23.85 | 1059.00 | 23.91 |
Minimum of Months | 64.17 | 22.31 | 118.33 | 22.84 | 23.33 | 22.89 |
Maximum of Months | 237.83 | 24.38 | 379.00 | 24.16 | 215.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.17 | 22.24 | 117.67 | 22.78 | 24.67 | 22.83 |
February | 171.67 | 22.61 | 167.00 | 23.24 | 37.50 | 23.29 |
March | 166.67 | 22.66 | 165.50 | 23.32 | 27.67 | 23.38 |
April | 66.33 | 23.89 | 276.00 | 23.99 | 45.33 | 24.01 |
May | 102.33 | 24.32 | 375.00 | 24.13 | 102.33 | 24.16 |
June | 112.83 | 24.39 | 366.00 | 24.16 | 112.83 | 24.20 |
July | 211.67 | 24.22 | 369.00 | 24.15 | 211.67 | 24.17 |
August | 142.33 | 24.29 | 379.00 | 24.14 | 142.33 | 24.17 |
September | 167.00 | 24.23 | 360.00 | 24.12 | 167.00 | 24.15 |
October | 106.83 | 24.18 | 334.83 | 24.10 | 100.50 | 24.13 |
November | 79.50 | 23.70 | 246.00 | 23.92 | 43.33 | 23.95 |
December | 178.17 | 22.51 | 164.33 | 23.20 | 35.67 | 23.27 |
Annual Sum or Average | 1748.50 | 23.45 | 3320.33 | 23.84 | 1050.83 | 23.90 |
Minimum of Months | 66.33 | 22.24 | 117.67 | 22.78 | 24.67 | 22.83 |
Maximum of Months | 243.17 | 24.39 | 379.00 | 24.16 | 211.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.83 | 22.20 | 116.17 | 22.71 | 30.17 | 22.78 |
February | 184.33 | 22.57 | 163.67 | 23.18 | 40.33 | 23.23 |
March | 186.00 | 22.69 | 158.67 | 23.28 | 34.00 | 23.34 |
April | 74.17 | 23.85 | 271.17 | 23.98 | 50.00 | 23.99 |
May | 109.17 | 24.30 | 375.00 | 24.12 | 109.17 | 24.16 |
June | 123.67 | 24.34 | 366.00 | 24.15 | 123.67 | 24.19 |
July | 223.83 | 24.20 | 369.00 | 24.14 | 223.83 | 24.15 |
August | 152.17 | 24.26 | 379.00 | 24.13 | 152.17 | 24.16 |
September | 178.83 | 24.20 | 360.00 | 24.12 | 178.83 | 24.14 |
October | 110.33 | 24.16 | 333.33 | 24.09 | 103.33 | 24.12 |
November | 87.17 | 23.66 | 236.67 | 23.90 | 46.33 | 23.93 |
December | 191.83 | 22.51 | 160.17 | 23.16 | 38.50 | 23.24 |
Annual Sum or Average | 1878.33 | 23.42 | 3288.83 | 23.81 | 1130.33 | 23.88 |
Minimum of Months | 74.17 | 22.20 | 116.17 | 22.71 | 30.17 | 22.78 |
Maximum of Months | 256.83 | 24.34 | 379.00 | 24.15 | 223.83 | 24.19 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 261.67 | 22.20 | 97.67 | 22.63 | 42.00 | 22.72 |
February | 190.50 | 22.55 | 148.67 | 23.09 | 47.67 | 23.14 |
March | 207.50 | 22.75 | 132.00 | 23.20 | 42.17 | 23.28 |
April | 92.00 | 23.82 | 241.83 | 23.90 | 58.00 | 23.92 |
May | 119.33 | 24.05 | 344.00 | 23.98 | 119.33 | 24.00 |
June | 149.33 | 24.02 | 336.00 | 23.98 | 149.33 | 23.99 |
July | 248.00 | 24.01 | 338.00 | 23.99 | 248.00 | 24.00 |
August | 195.17 | 23.98 | 348.00 | 23.96 | 195.17 | 23.97 |
September | 227.83 | 24.01 | 330.00 | 23.99 | 227.83 | 24.00 |
October | 119.17 | 24.00 | 304.50 | 23.98 | 112.00 | 23.99 |
November | 106.33 | 23.61 | 197.50 | 23.81 | 58.33 | 23.83 |
December | 200.17 | 22.53 | 139.17 | 23.08 | 46.83 | 23.17 |
Annual Sum or Average | 2117.00 | 23.37 | 2957.33 | 23.70 | 1346.67 | 23.75 |
Minimum of Months | 92.00 | 22.20 | 97.67 | 22.63 | 42.00 | 22.72 |
Maximum of Months | 261.67 | 24.05 | 348.00 | 23.99 | 248.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.00 | 22.20 | 94.17 | 22.60 | 42.50 | 22.70 |
February | 196.33 | 22.54 | 148.67 | 23.07 | 49.67 | 23.11 |
March | 215.50 | 22.76 | 130.17 | 23.19 | 45.50 | 23.26 |
April | 97.67 | 23.82 | 237.00 | 23.90 | 58.33 | 23.91 |
May | 119.50 | 24.05 | 344.00 | 23.98 | 119.50 | 23.99 |
June | 151.33 | 24.02 | 336.00 | 23.98 | 151.33 | 23.99 |
July | 249.83 | 24.01 | 338.00 | 23.99 | 249.83 | 24.00 |
August | 200.50 | 23.98 | 348.00 | 23.96 | 200.50 | 23.97 |
September | 230.50 | 24.01 | 330.00 | 23.99 | 230.50 | 24.00 |
October | 122.67 | 24.00 | 300.33 | 23.97 | 113.50 | 23.99 |
November | 115.67 | 23.62 | 185.67 | 23.81 | 60.67 | 23.83 |
December | 206.00 | 22.55 | 135.33 | 23.07 | 47.83 | 23.16 |
Annual Sum or Average | 2172.50 | 23.36 | 2927.33 | 23.69 | 1369.67 | 23.75 |
Minimum of Months | 97.67 | 22.20 | 94.17 | 22.60 | 42.50 | 22.70 |
Maximum of Months | 267.00 | 24.05 | 348.00 | 23.99 | 249.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.17 | 22.18 | 93.17 | 22.58 | 44.33 | 22.68 |
February | 199.50 | 22.52 | 148.50 | 23.04 | 51.17 | 23.09 |
March | 220.67 | 22.75 | 130.00 | 23.17 | 48.67 | 23.25 |
April | 100.83 | 23.81 | 235.83 | 23.90 | 59.83 | 23.91 |
May | 122.33 | 24.05 | 344.00 | 23.98 | 122.33 | 23.99 |
June | 154.17 | 24.01 | 336.00 | 23.97 | 154.17 | 23.98 |
July | 253.33 | 24.01 | 338.00 | 23.99 | 253.33 | 24.00 |
August | 203.33 | 23.98 | 348.00 | 23.96 | 203.33 | 23.97 |
September | 234.33 | 24.01 | 330.00 | 23.99 | 234.33 | 23.99 |
October | 124.17 | 23.99 | 299.33 | 23.97 | 113.83 | 23.99 |
November | 119.50 | 23.61 | 182.17 | 23.80 | 61.83 | 23.82 |
December | 211.33 | 22.55 | 134.00 | 23.06 | 48.67 | 23.15 |
Annual Sum or Average | 2213.67 | 23.36 | 2919.00 | 23.68 | 1395.83 | 23.74 |
Minimum of Months | 100.83 | 22.18 | 93.17 | 22.58 | 44.33 | 22.68 |
Maximum of Months | 270.17 | 24.05 | 348.00 | 23.99 | 253.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 277.67 | 22.16 | 92.50 | 22.55 | 47.33 | 22.66 |
February | 205.67 | 22.47 | 148.67 | 22.99 | 56.00 | 23.04 |
March | 231.17 | 22.73 | 129.33 | 23.14 | 54.67 | 23.22 |
April | 108.50 | 23.78 | 233.83 | 23.88 | 63.83 | 23.90 |
May | 125.17 | 24.04 | 344.00 | 23.98 | 125.17 | 23.99 |
June | 156.67 | 24.01 | 336.00 | 23.97 | 156.67 | 23.98 |
July | 251.67 | 24.01 | 338.00 | 23.99 | 251.67 | 24.00 |
August | 203.17 | 23.98 | 348.00 | 23.96 | 203.17 | 23.97 |
September | 234.33 | 24.01 | 330.00 | 23.99 | 234.33 | 23.99 |
October | 126.00 | 23.99 | 298.83 | 23.97 | 113.83 | 23.98 |
November | 126.33 | 23.58 | 178.33 | 23.78 | 63.67 | 23.81 |
December | 224.67 | 22.54 | 131.33 | 23.02 | 51.00 | 23.11 |
Annual Sum or Average | 2271.00 | 23.33 | 2908.83 | 23.67 | 1421.33 | 23.73 |
Minimum of Months | 108.50 | 22.16 | 92.50 | 22.55 | 47.33 | 22.66 |
Maximum of Months | 277.67 | 24.04 | 348.00 | 23.99 | 251.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 279.17 | 22.12 | 97.67 | 22.50 | 50.33 | 22.59 |
February | 210.83 | 22.39 | 153.50 | 22.89 | 64.17 | 22.91 |
March | 228.00 | 22.61 | 138.33 | 23.02 | 56.00 | 23.07 |
April | 114.83 | 23.70 | 229.67 | 23.85 | 66.00 | 23.87 |
May | 112.83 | 24.07 | 344.00 | 23.99 | 112.83 | 24.00 |
June | 124.00 | 24.06 | 336.00 | 23.99 | 124.00 | 24.00 |
July | 205.17 | 24.05 | 338.00 | 24.01 | 205.17 | 24.02 |
August | 147.83 | 24.03 | 348.00 | 23.98 | 147.83 | 23.99 |
September | 188.67 | 24.05 | 330.00 | 24.01 | 188.67 | 24.02 |
October | 114.83 | 23.99 | 300.50 | 23.97 | 101.83 | 23.99 |
November | 122.33 | 23.51 | 184.00 | 23.76 | 54.83 | 23.79 |
December | 230.50 | 22.48 | 136.33 | 22.95 | 54.33 | 23.03 |
Annual Sum or Average | 2079.00 | 23.24 | 2936.00 | 23.63 | 1226.00 | 23.68 |
Minimum of Months | 112.83 | 22.12 | 97.67 | 22.50 | 50.33 | 22.59 |
Maximum of Months | 279.17 | 24.07 | 348.00 | 24.01 | 205.17 | 24.02 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.72208 | 43.88787 | 0.12444 | 7.94034 |
February | 448.00000 | 23.15245 | 47.75844 | 0.25560 | 9.06598 |
March | 497.00000 | 23.27169 | 46.15795 | 0.27012 | 8.80529 |
April | 479.00000 | 23.85501 | 53.06156 | 0.49365 | 10.42431 |
May | 496.00000 | 23.88904 | 61.15799 | -0.2455 | 6.32436 |
June | 481.00000 | 23.88951 | 61.02880 | -0.2248 | 6.14276 |
July | 495.00000 | 23.89037 | 64.68993 | -0.1871 | 5.80604 |
August | 497.00000 | 23.89072 | 62.63988 | -0.1871 | 5.81915 |
September | 479.00000 | 23.89075 | 63.42428 | -0.1980 | 5.92677 |
October | 496.00000 | 23.87913 | 55.98658 | 0.59051 | 12.61594 |
November | 480.00000 | 23.80041 | 47.94908 | 0.45720 | 9.92904 |
December | 496.00000 | 23.20657 | 45.79820 | 0.27190 | 8.85441 |
Annual Sum or Average | 5840.00000 | 23.61244 | 54.49400 | 0.11710 | 8.13035 |
Minimum of Months | 448.00000 | 22.72208 | 43.88787 | -0.2455 | 5.80604 |
Maximum of Months | 497.00000 | 23.89075 | 64.68993 | 0.59051 | 12.61594 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.25761 | 42.34308 | 0.23662 | 7.73796 |
February | 448.00000 | 23.47760 | 46.03321 | 0.32346 | 8.84254 |
March | 497.00000 | 23.53951 | 44.14788 | 0.32555 | 8.52216 |
April | 479.00000 | 23.86904 | 49.85176 | 0.47941 | 10.04312 |
May | 496.00000 | 23.88858 | 57.28751 | -0.2821 | 6.77945 |
June | 481.00000 | 23.89004 | 57.48387 | -0.2654 | 6.60865 |
July | 495.00000 | 23.89050 | 61.04367 | -0.2312 | 6.24721 |
August | 497.00000 | 23.89038 | 59.46801 | -0.2351 | 6.29430 |
September | 479.00000 | 23.89055 | 59.87634 | -0.2433 | 6.39940 |
October | 496.00000 | 23.87844 | 53.06921 | 0.55793 | 11.80417 |
November | 480.00000 | 23.84955 | 46.04198 | 0.45653 | 9.70089 |
December | 496.00000 | 23.48379 | 44.30103 | 0.32686 | 8.67932 |
Annual Sum or Average | 5840.00000 | 23.73430 | 51.77374 | 0.11924 | 8.13171 |
Minimum of Months | 448.00000 | 23.25761 | 42.34308 | -0.2821 | 6.24721 |
Maximum of Months | 497.00000 | 23.89055 | 61.04367 | 0.55793 | 11.80417 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.88338 | 41.91571 | 0.15988 | 7.87481 |
February | 336.00000 | 23.28528 | 46.54518 | 0.29049 | 9.15625 |
March | 379.00000 | 23.39774 | 44.94581 | 0.30115 | 8.92743 |
April | 360.00000 | 23.95905 | 52.30887 | 0.51294 | 10.92233 |
May | 375.00000 | 24.07704 | 60.91962 | -0.2052 | 6.32661 |
June | 366.00000 | 24.09080 | 61.17752 | -0.1832 | 6.23931 |
July | 369.00000 | 24.10052 | 65.21845 | -0.1427 | 6.01256 |
August | 379.00000 | 24.08749 | 63.36558 | -0.1520 | 5.99464 |
September | 360.00000 | 24.07698 | 64.08607 | -0.1614 | 6.07093 |
October | 371.00000 | 24.04984 | 55.84469 | 0.61466 | 13.45380 |
November | 360.00000 | 23.89183 | 47.29849 | 0.47597 | 10.32287 |
December | 369.00000 | 23.27529 | 44.99953 | 0.29129 | 9.01269 |
Annual Sum or Average | 4395.00000 | 23.76674 | 54.10562 | 0.14795 | 8.34564 |
Minimum of Months | 336.00000 | 22.88338 | 41.91571 | -0.2052 | 5.99464 |
Maximum of Months | 379.00000 | 24.10052 | 65.21845 | 0.61466 | 13.45380 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.81909 | 42.12476 | 0.14018 | 7.84776 |
February | 336.00000 | 23.24537 | 46.71544 | 0.27682 | 9.08161 |
March | 379.00000 | 23.37090 | 45.05097 | 0.29127 | 8.89439 |
April | 360.00000 | 23.95495 | 52.35556 | 0.51059 | 10.88457 |
May | 375.00000 | 24.07700 | 60.88940 | -0.2047 | 6.32282 |
June | 366.00000 | 24.09098 | 61.12606 | -0.1822 | 6.23377 |
July | 369.00000 | 24.10088 | 65.13731 | -0.1414 | 6.00830 |
August | 379.00000 | 24.08772 | 63.30169 | -0.1509 | 5.99006 |
September | 360.00000 | 24.07713 | 64.02471 | -0.1604 | 6.06763 |
October | 371.00000 | 24.04946 | 55.80977 | 0.61486 | 13.46239 |
November | 360.00000 | 23.88458 | 47.35425 | 0.47252 | 10.27541 |
December | 369.00000 | 23.24211 | 45.10026 | 0.27999 | 8.97189 |
Annual Sum or Average | 4395.00000 | 23.75227 | 54.13504 | 0.14340 | 8.32331 |
Minimum of Months | 336.00000 | 22.81909 | 42.12476 | -0.2047 | 5.99006 |
Maximum of Months | 379.00000 | 24.10088 | 65.13731 | 0.61486 | 13.46239 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.72681 | 42.50463 | 0.11382 | 7.82367 |
February | 336.00000 | 23.17716 | 47.06279 | 0.25552 | 8.95526 |
March | 379.00000 | 23.31564 | 45.37968 | 0.27340 | 8.81218 |
April | 360.00000 | 23.94232 | 52.67849 | 0.50408 | 10.76787 |
May | 375.00000 | 24.07292 | 61.20360 | -0.2094 | 6.34446 |
June | 366.00000 | 24.08698 | 61.42006 | -0.1868 | 6.24724 |
July | 369.00000 | 24.09706 | 65.44300 | -0.1452 | 6.00903 |
August | 379.00000 | 24.08386 | 63.59679 | -0.1549 | 5.99416 |
September | 360.00000 | 24.07326 | 64.33708 | -0.1642 | 6.07585 |
October | 371.00000 | 24.04348 | 56.05225 | 0.61151 | 13.37805 |
November | 360.00000 | 23.86564 | 47.59781 | 0.46453 | 10.15853 |
December | 369.00000 | 23.18733 | 45.35037 | 0.26250 | 8.89596 |
Annual Sum or Average | 4395.00000 | 23.72516 | 54.43787 | 0.13330 | 8.27596 |
Minimum of Months | 336.00000 | 22.72681 | 42.50463 | -0.2094 | 5.99416 |
Maximum of Months | 379.00000 | 24.09706 | 65.44300 | 0.61151 | 13.37805 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.59015 | 44.18751 | 0.07184 | 7.74274 |
February | 308.00000 | 23.06125 | 48.70527 | 0.21803 | 8.64409 |
March | 348.00000 | 23.21663 | 46.95711 | 0.23897 | 8.54201 |
April | 330.00000 | 23.88182 | 53.91264 | 0.48257 | 10.28503 |
May | 344.00000 | 23.95619 | 62.79409 | -0.2457 | 6.49088 |
June | 336.00000 | 23.95682 | 62.95381 | -0.2246 | 6.32475 |
July | 338.00000 | 23.98090 | 67.06386 | -0.1773 | 6.01684 |
August | 348.00000 | 23.95157 | 65.15645 | -0.1899 | 6.00365 |
September | 330.00000 | 23.97501 | 66.07123 | -0.1908 | 6.15538 |
October | 340.00000 | 23.94346 | 57.53715 | 0.59407 | 12.84436 |
November | 330.00000 | 23.80752 | 48.95203 | 0.44516 | 9.76150 |
December | 338.00000 | 23.08443 | 46.86875 | 0.23006 | 8.67879 |
Annual Sum or Average | 4030.00000 | 23.61949 | 55.98383 | 0.10216 | 8.11306 |
Minimum of Months | 308.00000 | 22.59015 | 44.18751 | -0.2457 | 6.00365 |
Maximum of Months | 348.00000 | 23.98090 | 67.06386 | 0.59407 | 12.84436 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.55940 | 44.20881 | 0.05433 | 7.71728 |
February | 308.00000 | 23.03514 | 48.75025 | 0.20121 | 8.53174 |
March | 348.00000 | 23.19803 | 46.99473 | 0.22401 | 8.41962 |
April | 330.00000 | 23.87999 | 53.94002 | 0.46981 | 10.02572 |
May | 344.00000 | 23.95570 | 62.85579 | -0.2679 | 6.72632 |
June | 336.00000 | 23.95603 | 63.03393 | -0.2484 | 6.55353 |
July | 338.00000 | 23.98004 | 67.21119 | -0.2012 | 6.19797 |
August | 348.00000 | 23.95076 | 65.28845 | -0.2148 | 6.20680 |
September | 330.00000 | 23.97396 | 66.24051 | -0.2141 | 6.33987 |
October | 340.00000 | 23.94309 | 57.63074 | 0.57748 | 12.42271 |
November | 330.00000 | 23.80442 | 48.97908 | 0.43197 | 9.51861 |
December | 338.00000 | 23.07005 | 46.86171 | 0.21523 | 8.54347 |
Annual Sum or Average | 4030.00000 | 23.61132 | 56.05364 | 0.08339 | 8.09072 |
Minimum of Months | 308.00000 | 22.55940 | 44.20881 | -0.2679 | 6.19797 |
Maximum of Months | 348.00000 | 23.98004 | 67.21119 | 0.57748 | 12.42271 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.53358 | 44.31806 | 0.04540 | 7.73016 |
February | 308.00000 | 23.00922 | 48.89202 | 0.19224 | 8.50854 |
March | 348.00000 | 23.17824 | 47.10072 | 0.21655 | 8.39423 |
April | 330.00000 | 23.87580 | 54.03947 | 0.46669 | 9.97700 |
May | 344.00000 | 23.95540 | 62.95552 | -0.2700 | 6.74770 |
June | 336.00000 | 23.95575 | 63.12564 | -0.2504 | 6.57209 |
July | 338.00000 | 23.97969 | 67.30358 | -0.2029 | 6.20995 |
August | 348.00000 | 23.95052 | 65.37239 | -0.2165 | 6.22020 |
September | 330.00000 | 23.97363 | 66.33274 | -0.2158 | 6.35277 |
October | 340.00000 | 23.94192 | 57.71062 | 0.57588 | 12.38689 |
November | 330.00000 | 23.79742 | 49.06150 | 0.42830 | 9.47327 |
December | 338.00000 | 23.04854 | 46.96248 | 0.20762 | 8.51834 |
Annual Sum or Average | 4030.00000 | 23.60251 | 56.15164 | 0.07920 | 8.08160 |
Minimum of Months | 308.00000 | 22.53358 | 44.31806 | -0.2700 | 6.20995 |
Maximum of Months | 348.00000 | 23.97969 | 67.30358 | 0.57588 | 12.38689 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.47870 | 44.53125 | 0.02803 | 7.78467 |
February | 308.00000 | 22.94908 | 49.17498 | 0.17318 | 8.49112 |
March | 348.00000 | 23.12906 | 47.35817 | 0.20051 | 8.37784 |
April | 330.00000 | 23.86061 | 54.26703 | 0.46029 | 9.90096 |
May | 344.00000 | 23.95501 | 63.08378 | -0.2689 | 6.73372 |
June | 336.00000 | 23.95557 | 63.19569 | -0.2483 | 6.55071 |
July | 338.00000 | 23.97963 | 67.32688 | -0.1998 | 6.18506 |
August | 348.00000 | 23.95055 | 65.35966 | -0.2129 | 6.19006 |
September | 330.00000 | 23.97367 | 66.36449 | -0.2129 | 6.33120 |
October | 340.00000 | 23.93873 | 57.76779 | 0.57622 | 12.41309 |
November | 330.00000 | 23.77817 | 49.23448 | 0.42193 | 9.42380 |
December | 338.00000 | 22.99530 | 47.18918 | 0.19147 | 8.50868 |
Annual Sum or Average | 4030.00000 | 23.58143 | 56.29036 | 0.07361 | 8.06514 |
Minimum of Months | 308.00000 | 22.47870 | 44.53125 | -0.2689 | 6.18506 |
Maximum of Months | 348.00000 | 23.97963 | 67.32688 | 0.57622 | 12.41309 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.44061 | 44.47696 | 0.00817 | 8.02357 |
February | 308.00000 | 22.87324 | 49.28432 | 0.14469 | 8.63145 |
March | 348.00000 | 23.06438 | 47.30850 | 0.17690 | 8.56273 |
April | 330.00000 | 23.83151 | 54.28522 | 0.45685 | 9.97150 |
May | 344.00000 | 23.95864 | 62.49728 | -0.2363 | 6.41890 |
June | 336.00000 | 23.96029 | 62.22002 | -0.2081 | 6.21010 |
July | 338.00000 | 23.98740 | 66.02829 | -0.1550 | 5.93126 |
August | 348.00000 | 23.95705 | 64.06190 | -0.1647 | 5.87379 |
September | 330.00000 | 23.98158 | 65.27352 | -0.1721 | 6.09719 |
October | 340.00000 | 23.93638 | 57.02193 | 0.59800 | 13.06655 |
November | 330.00000 | 23.75692 | 48.99698 | 0.42143 | 9.57446 |
December | 338.00000 | 22.93068 | 47.27653 | 0.16869 | 8.71711 |
Annual Sum or Average | 4030.00000 | 23.55966 | 55.77457 | 0.08471 | 8.07968 |
Minimum of Months | 308.00000 | 22.44061 | 44.47696 | -0.2363 | 5.87379 |
Maximum of Months | 348.00000 | 23.98740 | 66.02829 | 0.59800 | 13.06655 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.473751E+10 | 0.120855E+10 | 133.76 | 0.298421E+10 | 0.175331E+10 | 0.00 | 0.81 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 | 22223.74 | 19-JAN-15:00 | 14575.29 | 01-JAN-14:00 | 9333.58 | 19-JAN-15:00 | 5270.73 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.612500E+10 | 0.155583E+10 | 165.49 | 0.384964E+10 | 0.227536E+10 | 0.00 | 0.84 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 23059.10 | 24-FEB-14:00 | 14646.23 | 24-FEB-14:00 | 11478.92 | 28-FEB-08:63 | 5614.31 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.904135E+10 | 0.231903E+10 | 239.04 | 0.586679E+10 | 0.317456E+10 | 0.00 | 0.89 | 07-MAR-08:63 | 0.00 | 01-MAR-00:05 | 25716.01 | 07-MAR-08:63 | 16827.75 | 26-MAR-14:00 | 13601.59 | 07-MAR-08:63 | 5986.15 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.167677E+11 | 0.429163E+10 | 379.66 | 0.109912E+11 | 0.577650E+10 | 0.00 | 1.00 | 23-APR-07:03 | 0.00 | 01-APR-00:05 | 60226.31 | 29-APR-07:03 | 33038.85 | 29-APR-07:03 | 32277.05 | 30-APR-07:02 | 12996.72 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.373058E+11 | 0.931994E+10 | 496.27 | 0.227152E+11 | 0.145906E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 61497.22 | 24-MAY-07:02 | 40088.32 | 07-MAY-07:02 | 30225.90 | 24-MAY-07:02 | 13402.60 | 27-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.397598E+11 | 0.987104E+10 | 482.93 | 0.240048E+11 | 0.157550E+11 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 60787.82 | 19-JUN-07:02 | 40795.35 | 11-JUN-07:02 | 28133.22 | 19-JUN-07:02 | 13709.16 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.452241E+11 | 0.110194E+11 | 497.46 | 0.253492E+11 | 0.198748E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 61806.93 | 02-JUL-07:02 | 39503.43 | 09-JUL-07:01 | 30768.28 | 02-JUL-07:03 | 13646.57 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.446404E+11 | 0.109004E+11 | 498.77 | 0.259144E+11 | 0.187260E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 61517.04 | 10-AUG-07:02 | 42889.75 | 31-AUG-07:02 | 29277.42 | 16-AUG-07:02 | 13449.86 | 22-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.396392E+11 | 0.959631E+10 | 482.96 | 0.223518E+11 | 0.172874E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 62361.57 | 05-SEP-07:02 | 39157.72 | 22-SEP-07:02 | 32572.62 | 05-SEP-07:03 | 14241.70 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.337396E+11 | 0.824100E+10 | 459.43 | 0.204688E+11 | 0.132707E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 61701.38 | 25-OCT-07:02 | 46340.88 | 26-OCT-07:02 | 30196.61 | 15-OCT-07:02 | 13491.00 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.133344E+11 | 0.332624E+10 | 304.08 | 0.839660E+10 | 0.493780E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 59994.97 | 02-NOV-07:02 | 38155.86 | 07-NOV-08:62 | 29383.67 | 04-NOV-07:03 | 12903.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.860120E+10 | 0.215218E+10 | 197.23 | 0.538104E+10 | 0.322017E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 59027.82 | 15-DEC-08:62 | 34764.57 | 11-DEC-08:62 | 24660.69 | 15-DEC-08:62 | 12553.88 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.298916E+12 | 0.738015E+11 | 4337.09 | 0.178274E+12 | 0.120642E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.473751E+10 | 0.120855E+10 | 133.76 | 0.298421E+10 | 0.175331E+10 | 0.00 | 0.81 | 0.00 | 22223.74 | 14575.29 | 9333.58 | 5270.73 | 0.00 | |||||||
Maximum of Months | 0.452241E+11 | 0.110194E+11 | 498.77 | 0.259144E+11 | 0.198748E+11 | 0.00 | 1.00 | 0.00 | 62361.57 | 46340.88 | 32572.62 | 14241.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.294724E+10 | 0.734283E+09 | 148.65 | 0.192255E+10 | 0.102469E+10 | 0.00 | 1.00 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 | 30383.42 | 01-JAN-18:02 | 19730.86 | 29-JAN-18:07 | 13915.63 | 01-JAN-18:02 | 6420.53 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 |
February | 0.386132E+10 | 0.960410E+09 | 189.97 | 0.249123E+10 | 0.137010E+10 | 0.00 | 1.00 | 11-FEB-19:02 | 0.00 | 01-FEB-00:05 | 30708.85 | 28-FEB-21:20 | 16628.13 | 20-FEB-18:08 | 15992.52 | 28-FEB-21:20 | 6466.75 | 28-FEB-21:20 | 0.00 | 01-FEB-00:05 |
March | 0.543208E+10 | 0.136046E+10 | 251.02 | 0.365412E+10 | 0.177795E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:05 | 30433.22 | 07-MAR-21:02 | 24462.53 | 04-MAR-19:01 | 15107.32 | 07-MAR-21:02 | 6427.90 | 07-MAR-21:02 | 0.00 | 01-MAR-00:05 |
April | 0.951175E+10 | 0.238829E+10 | 395.09 | 0.646673E+10 | 0.304502E+10 | 0.00 | 1.00 | 02-APR-17:02 | 0.00 | 01-APR-00:05 | 30895.54 | 30-APR-07:02 | 25341.19 | 17-APR-20:01 | 15861.47 | 15-APR-18:10 | 6516.01 | 30-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.188908E+11 | 0.467908E+10 | 496.65 | 0.119541E+11 | 0.693671E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 31235.18 | 22-MAY-07:02 | 24627.42 | 07-MAY-07:02 | 10983.85 | 22-MAY-07:02 | 6897.84 | 22-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.199036E+11 | 0.491019E+10 | 483.71 | 0.124533E+11 | 0.745027E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 30542.50 | 05-JUN-07:02 | 25305.76 | 26-JUN-07:02 | 9798.65 | 29-JUN-17:00 | 6994.73 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.223775E+11 | 0.543350E+10 | 498.38 | 0.130494E+11 | 0.932807E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 31254.67 | 03-JUL-07:02 | 24328.28 | 09-JUL-07:01 | 10808.90 | 02-JUL-07:02 | 6984.57 | 04-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.220468E+11 | 0.535791E+10 | 498.96 | 0.132371E+11 | 0.880969E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31453.52 | 16-AUG-07:02 | 25391.67 | 31-AUG-07:02 | 11599.79 | 16-AUG-07:02 | 6897.03 | 10-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.197210E+11 | 0.474388E+10 | 483.27 | 0.115554E+11 | 0.816562E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 31742.23 | 05-SEP-07:02 | 24772.24 | 02-SEP-07:02 | 12262.36 | 05-SEP-07:02 | 7365.78 | 10-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.171619E+11 | 0.415761E+10 | 463.63 | 0.108188E+11 | 0.634315E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 31349.78 | 08-OCT-07:01 | 25376.46 | 26-OCT-20:01 | 11001.38 | 24-OCT-13:30 | 6933.96 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.749222E+10 | 0.183543E+10 | 319.39 | 0.488968E+10 | 0.260254E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 30712.13 | 29-NOV-21:02 | 24912.60 | 03-NOV-07:02 | 15787.50 | 29-NOV-21:02 | 6553.91 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.478099E+10 | 0.117707E+10 | 211.82 | 0.311594E+10 | 0.166505E+10 | 0.00 | 1.00 | 08-DEC-21:02 | 0.00 | 01-DEC-00:10 | 30214.76 | 08-DEC-21:55 | 20120.37 | 11-DEC-08:62 | 14413.63 | 08-DEC-21:40 | 6394.76 | 08-DEC-21:55 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.154127E+12 | 0.377381E+11 | 4440.54 | 0.956083E+11 | 0.585189E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.294724E+10 | 0.734283E+09 | 148.65 | 0.192255E+10 | 0.102469E+10 | 0.00 | 1.00 | 0.00 | 30214.76 | 16628.13 | 9798.65 | 6394.76 | 0.00 | |||||||
Maximum of Months | 0.223775E+11 | 0.543350E+10 | 498.96 | 0.132371E+11 | 0.932807E+10 | 0.00 | 1.00 | 0.00 | 31742.23 | 25391.67 | 15992.52 | 7365.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.213007E+10 | 0.535225E+09 | 108.67 | 0.137173E+10 | 0.758345E+09 | 0.00 | 0.93 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 | 13899.10 | 20-JAN-07:03 | 7530.85 | 01-JAN-14:00 | 7657.47 | 20-JAN-07:03 | 3004.58 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.292858E+10 | 0.731828E+09 | 146.00 | 0.186403E+10 | 0.106455E+10 | 0.00 | 0.98 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 | 14896.43 | 28-FEB-07:03 | 7784.59 | 02-FEB-13:30 | 7587.00 | 28-FEB-07:03 | 3165.75 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.408136E+10 | 0.102742E+10 | 192.72 | 0.268658E+10 | 0.139477E+10 | 0.00 | 1.00 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 19205.49 | 07-MAR-07:03 | 10748.04 | 07-MAR-07:03 | 8610.76 | 30-MAR-06:03 | 3986.89 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.719993E+10 | 0.181386E+10 | 301.89 | 0.481428E+10 | 0.238565E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 32213.34 | 29-APR-06:03 | 19819.54 | 28-APR-06:03 | 17651.89 | 30-APR-07:02 | 6724.29 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.154537E+11 | 0.379058E+10 | 369.06 | 0.948677E+10 | 0.596692E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 33004.38 | 21-MAY-07:02 | 21224.73 | 12-MAY-06:02 | 17360.47 | 21-MAY-07:02 | 6958.38 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.165214E+11 | 0.402777E+10 | 359.16 | 0.100070E+11 | 0.651441E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 33487.28 | 19-JUN-06:02 | 21733.29 | 14-JUN-06:02 | 19096.91 | 19-JUN-06:02 | 7087.52 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.183523E+11 | 0.439147E+10 | 364.26 | 0.102783E+11 | 0.807398E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33586.88 | 03-JUL-06:01 | 19585.71 | 19-JUL-06:01 | 19125.09 | 31-JUL-06:02 | 7128.16 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.184574E+11 | 0.442853E+10 | 374.34 | 0.106767E+11 | 0.778067E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33576.23 | 14-AUG-06:03 | 21687.11 | 31-AUG-06:02 | 19581.70 | 14-AUG-06:03 | 6947.50 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.160452E+11 | 0.380499E+10 | 355.26 | 0.899634E+10 | 0.704884E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33624.04 | 05-SEP-06:01 | 20712.19 | 23-SEP-06:02 | 19024.84 | 05-SEP-06:01 | 7397.08 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.137166E+11 | 0.328985E+10 | 340.81 | 0.834136E+10 | 0.537527E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 33462.23 | 08-OCT-07:01 | 23408.47 | 26-OCT-06:02 | 18108.99 | 08-OCT-07:03 | 6983.44 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.582739E+10 | 0.143177E+10 | 261.38 | 0.373330E+10 | 0.209409E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 32282.36 | 02-NOV-06:02 | 20808.78 | 07-NOV-07:03 | 17340.67 | 04-NOV-06:02 | 6747.61 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.374362E+10 | 0.920936E+09 | 164.14 | 0.237334E+10 | 0.137028E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 31911.03 | 12-DEC-07:03 | 18751.19 | 15-DEC-07:03 | 18002.83 | 16-DEC-07:03 | 6604.32 | 12-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124458E+12 | 0.301942E+11 | 3337.70 | 0.746297E+11 | 0.498278E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.213007E+10 | 0.535225E+09 | 108.67 | 0.137173E+10 | 0.758345E+09 | 0.00 | 0.93 | 0.00 | 13899.10 | 7530.85 | 7587.00 | 3004.58 | 0.00 | |||||||
Maximum of Months | 0.184574E+11 | 0.442853E+10 | 374.34 | 0.106767E+11 | 0.807398E+10 | 0.00 | 1.00 | 0.00 | 33624.04 | 23408.47 | 19581.70 | 7397.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.206310E+10 | 0.519512E+09 | 104.75 | 0.132384E+10 | 0.739260E+09 | 0.00 | 0.90 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 | 13307.48 | 20-JAN-07:03 | 7502.05 | 01-JAN-14:00 | 7336.38 | 20-JAN-07:03 | 2907.41 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.285890E+10 | 0.715653E+09 | 143.25 | 0.181529E+10 | 0.104360E+10 | 0.00 | 0.94 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 | 14178.66 | 28-FEB-07:03 | 7734.09 | 02-FEB-13:30 | 7227.25 | 28-FEB-07:03 | 3051.25 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.401633E+10 | 0.101244E+10 | 190.64 | 0.263719E+10 | 0.137913E+10 | 0.00 | 1.00 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 18363.26 | 07-MAR-07:03 | 10226.15 | 07-MAR-07:03 | 8450.93 | 30-MAR-06:03 | 3812.94 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.715626E+10 | 0.180438E+10 | 299.64 | 0.478064E+10 | 0.237562E+10 | 0.00 | 1.00 | 22-APR-06:03 | 0.00 | 01-APR-00:05 | 32308.06 | 29-APR-06:03 | 19847.73 | 28-APR-06:03 | 17729.47 | 24-APR-06:03 | 6743.79 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.154795E+11 | 0.379796E+10 | 368.80 | 0.950603E+10 | 0.597351E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 33100.21 | 21-MAY-07:02 | 21323.52 | 12-MAY-06:02 | 17408.80 | 21-MAY-07:02 | 6978.47 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.165639E+11 | 0.403879E+10 | 359.13 | 0.100387E+11 | 0.652527E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 33590.50 | 19-JUN-06:02 | 21842.63 | 14-JUN-06:02 | 19111.90 | 19-JUN-06:02 | 7108.00 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.184185E+11 | 0.440758E+10 | 364.41 | 0.103261E+11 | 0.809238E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33683.81 | 03-JUL-06:01 | 19684.56 | 19-JUL-06:01 | 19126.96 | 31-JUL-06:02 | 7148.72 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.185117E+11 | 0.444192E+10 | 374.33 | 0.107165E+11 | 0.779524E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33673.14 | 14-AUG-06:01 | 21792.64 | 31-AUG-06:02 | 19568.77 | 14-AUG-06:03 | 6967.29 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.160935E+11 | 0.381691E+10 | 355.36 | 0.903114E+10 | 0.706238E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33721.09 | 05-SEP-06:01 | 20797.74 | 23-SEP-06:02 | 19002.98 | 05-SEP-06:03 | 7418.48 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.137452E+11 | 0.329722E+10 | 340.75 | 0.836251E+10 | 0.538268E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 33567.68 | 08-OCT-07:01 | 23480.36 | 26-OCT-06:02 | 18123.88 | 08-OCT-07:04 | 7003.47 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.577399E+10 | 0.141932E+10 | 258.88 | 0.369313E+10 | 0.208087E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 32377.47 | 02-NOV-06:02 | 20874.58 | 07-NOV-07:03 | 17388.86 | 04-NOV-06:02 | 6767.17 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.369832E+10 | 0.910270E+09 | 161.81 | 0.233957E+10 | 0.135875E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 32004.24 | 12-DEC-07:03 | 18792.19 | 15-DEC-07:03 | 18058.14 | 16-DEC-07:03 | 6623.48 | 12-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124379E+12 | 0.301819E+11 | 3321.75 | 0.745706E+11 | 0.498087E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.206310E+10 | 0.519512E+09 | 104.75 | 0.132384E+10 | 0.739260E+09 | 0.00 | 0.90 | 0.00 | 13307.48 | 7502.05 | 7227.25 | 2907.41 | 0.00 | |||||||
Maximum of Months | 0.185117E+11 | 0.444192E+10 | 374.33 | 0.107165E+11 | 0.809238E+10 | 0.00 | 1.00 | 0.00 | 33721.09 | 23480.36 | 19568.77 | 7418.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.192697E+10 | 0.486823E+09 | 100.75 | 0.122956E+10 | 0.697413E+09 | 0.00 | 0.77 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 11128.18 | 19-JAN-14:00 | 7355.39 | 01-JAN-14:00 | 5717.54 | 20-JAN-07:03 | 2617.84 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.270631E+10 | 0.679290E+09 | 138.67 | 0.171063E+10 | 0.995677E+09 | 0.00 | 0.81 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 | 11591.51 | 28-FEB-07:03 | 7554.94 | 02-FEB-13:30 | 5927.60 | 28-FEB-07:03 | 2801.37 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.382140E+10 | 0.965772E+09 | 186.31 | 0.249544E+10 | 0.132596E+10 | 0.00 | 0.99 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 15521.61 | 07-MAR-07:03 | 8506.95 | 07-MAR-07:03 | 7165.49 | 30-MAR-06:03 | 3238.21 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.689906E+10 | 0.174253E+10 | 294.52 | 0.459645E+10 | 0.230261E+10 | 0.00 | 1.00 | 23-APR-07:03 | 0.00 | 01-APR-00:05 | 32046.48 | 29-APR-06:03 | 17877.27 | 28-APR-06:03 | 17591.49 | 30-APR-07:02 | 6690.47 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.152213E+11 | 0.373763E+10 | 368.90 | 0.931830E+10 | 0.590304E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32820.86 | 21-MAY-07:02 | 21006.03 | 12-MAY-06:02 | 17408.07 | 21-MAY-07:02 | 6923.70 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.163193E+11 | 0.398049E+10 | 358.91 | 0.985865E+10 | 0.646066E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 33313.69 | 19-JUN-06:02 | 21503.60 | 14-JUN-06:02 | 19078.31 | 19-JUN-06:02 | 7052.17 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.181761E+11 | 0.435021E+10 | 364.67 | 0.101540E+11 | 0.802203E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33419.40 | 03-JUL-06:01 | 19346.87 | 19-JUL-06:01 | 19077.68 | 31-JUL-06:02 | 7092.62 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.182646E+11 | 0.438321E+10 | 374.79 | 0.105379E+11 | 0.772669E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33408.80 | 14-AUG-06:01 | 21463.41 | 31-AUG-06:02 | 19523.96 | 14-AUG-06:03 | 6913.00 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.158589E+11 | 0.376281E+10 | 355.38 | 0.886605E+10 | 0.699286E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33456.37 | 05-SEP-06:01 | 20490.30 | 23-SEP-06:02 | 18921.74 | 05-SEP-06:01 | 7360.00 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.135278E+11 | 0.324614E+10 | 338.76 | 0.820140E+10 | 0.532638E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 33291.81 | 08-OCT-07:01 | 23251.16 | 26-OCT-06:02 | 18059.21 | 08-OCT-07:03 | 6948.64 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.557102E+10 | 0.137038E+10 | 253.67 | 0.354321E+10 | 0.202781E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 32112.55 | 02-NOV-06:02 | 19541.37 | 07-NOV-07:03 | 17304.58 | 04-NOV-06:02 | 6713.60 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.356524E+10 | 0.878567E+09 | 156.31 | 0.224317E+10 | 0.132207E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 31708.40 | 15-DEC-07:03 | 18472.28 | 15-DEC-07:03 | 17628.25 | 16-DEC-07:03 | 6570.79 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121858E+12 | 0.295838E+11 | 3291.64 | 0.727548E+11 | 0.491032E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.192697E+10 | 0.486823E+09 | 100.75 | 0.122956E+10 | 0.697413E+09 | 0.00 | 0.77 | 0.00 | 11128.18 | 7355.39 | 5717.54 | 2617.84 | 0.00 | |||||||
Maximum of Months | 0.182646E+11 | 0.438321E+10 | 374.79 | 0.105379E+11 | 0.802203E+10 | 0.00 | 1.00 | 0.00 | 33456.37 | 23251.16 | 19523.96 | 7360.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.311468E+10 | 0.799251E+09 | 95.06 | 0.194282E+10 | 0.117186E+10 | 0.00 | 0.80 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 20420.15 | 19-JAN-14:00 | 12654.52 | 01-JAN-14:10 | 8943.24 | 19-JAN-14:00 | 4836.77 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.455547E+10 | 0.116031E+10 | 128.86 | 0.281134E+10 | 0.174412E+10 | 0.00 | 0.83 | 24-FEB-13:50 | 0.00 | 01-FEB-00:05 | 21186.63 | 24-FEB-13:50 | 13576.08 | 02-FEB-13:30 | 8515.84 | 28-FEB-08:63 | 5169.72 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.647606E+10 | 0.165993E+10 | 178.92 | 0.413433E+10 | 0.234174E+10 | 0.00 | 0.90 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 23476.38 | 30-MAR-13:00 | 14816.08 | 26-MAR-14:00 | 9731.99 | 07-MAR-08:63 | 5730.13 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.120444E+11 | 0.308309E+10 | 283.31 | 0.788713E+10 | 0.415724E+10 | 0.00 | 1.00 | 23-APR-08:63 | 0.00 | 01-APR-00:05 | 55653.09 | 29-APR-07:03 | 31821.19 | 29-APR-07:03 | 23831.90 | 29-APR-07:03 | 12074.45 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.270145E+11 | 0.670345E+10 | 358.59 | 0.162980E+11 | 0.107164E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 57798.94 | 21-MAY-08:62 | 37568.45 | 12-MAY-07:02 | 31128.70 | 21-MAY-08:62 | 12544.81 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.291795E+11 | 0.719587E+10 | 350.96 | 0.173827E+11 | 0.117968E+11 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 58467.15 | 19-JUN-07:02 | 38594.09 | 14-JUN-07:02 | 33710.69 | 19-JUN-07:02 | 12668.86 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.323142E+11 | 0.781927E+10 | 351.47 | 0.177657E+11 | 0.145485E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 58803.69 | 03-JUL-07:02 | 36257.62 | 19-JUL-07:02 | 34359.17 | 02-JUL-08:03 | 12860.47 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.326906E+11 | 0.794093E+10 | 364.44 | 0.185945E+11 | 0.140960E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 58718.85 | 14-AUG-07:01 | 39692.00 | 31-AUG-07:02 | 34459.07 | 14-AUG-07:03 | 12617.95 | 06-AUG-08:05 | 0.00 | 01-AUG-00:10 |
September | 0.280724E+11 | 0.672680E+10 | 344.21 | 0.153792E+11 | 0.126932E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 58815.35 | 05-SEP-07:02 | 36540.98 | 23-SEP-07:02 | 33467.47 | 05-SEP-07:02 | 13352.60 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.242235E+11 | 0.588125E+10 | 329.17 | 0.144549E+11 | 0.976868E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 58523.69 | 08-OCT-08:62 | 42266.07 | 26-OCT-07:02 | 32181.14 | 08-OCT-08:03 | 12468.68 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.970093E+10 | 0.241173E+10 | 233.09 | 0.603552E+10 | 0.366541E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 55439.84 | 02-NOV-07:02 | 36749.86 | 07-NOV-08:62 | 28400.11 | 04-NOV-07:03 | 11937.69 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.617801E+10 | 0.153767E+10 | 142.78 | 0.380317E+10 | 0.237484E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 55234.29 | 11-DEC-08:62 | 31096.27 | 15-DEC-08:62 | 30631.18 | 11-DEC-08:62 | 11691.58 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.215564E+12 | 0.529195E+11 | 3160.84 | 0.126489E+12 | 0.890749E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.311468E+10 | 0.799251E+09 | 95.06 | 0.194282E+10 | 0.117186E+10 | 0.00 | 0.80 | 0.00 | 20420.15 | 12654.52 | 8515.84 | 4836.77 | 0.00 | |||||||
Maximum of Months | 0.326906E+11 | 0.794093E+10 | 364.44 | 0.185945E+11 | 0.145485E+11 | 0.00 | 1.00 | 0.00 | 58815.35 | 42266.07 | 34459.07 | 13352.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.158545E+10 | 0.400380E+09 | 93.33 | 0.989180E+09 | 0.596266E+09 | 0.00 | 0.79 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10547.00 | 19-JAN-14:00 | 6582.92 | 01-JAN-14:10 | 4622.60 | 19-JAN-14:00 | 2461.52 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.232372E+10 | 0.582425E+09 | 125.94 | 0.143427E+10 | 0.889446E+09 | 0.00 | 0.82 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10990.31 | 24-FEB-14:00 | 7047.35 | 02-FEB-13:30 | 4178.36 | 24-FEB-13:10 | 2640.15 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.331413E+10 | 0.835893E+09 | 176.67 | 0.211348E+10 | 0.120065E+10 | 0.00 | 0.89 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 12269.93 | 30-MAR-13:00 | 7728.00 | 26-MAR-14:00 | 4966.87 | 07-MAR-13:40 | 2945.56 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.621204E+10 | 0.156475E+10 | 280.14 | 0.407111E+10 | 0.214093E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:05 | 26615.36 | 29-APR-07:03 | 15203.33 | 29-APR-07:03 | 11412.03 | 29-APR-07:03 | 5677.39 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.140307E+11 | 0.342854E+10 | 358.90 | 0.847416E+10 | 0.555650E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 30311.12 | 21-MAY-08:62 | 19692.50 | 12-MAY-07:02 | 16377.14 | 21-MAY-08:62 | 6461.23 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.151563E+11 | 0.368155E+10 | 352.12 | 0.903740E+10 | 0.611894E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 30688.77 | 19-JUN-07:02 | 20234.19 | 14-JUN-07:02 | 17798.87 | 19-JUN-07:02 | 6524.65 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.167875E+11 | 0.400222E+10 | 352.12 | 0.924100E+10 | 0.754645E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30829.09 | 03-JUL-07:02 | 19009.63 | 19-JUL-07:02 | 18139.88 | 02-JUL-08:03 | 6624.29 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.169726E+11 | 0.406151E+10 | 364.59 | 0.966479E+10 | 0.730783E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30784.62 | 14-AUG-07:03 | 20807.09 | 31-AUG-07:02 | 18192.93 | 14-AUG-07:03 | 6482.66 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.145677E+11 | 0.343731E+10 | 344.60 | 0.799174E+10 | 0.657599E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30840.78 | 05-SEP-07:02 | 19151.35 | 23-SEP-07:02 | 17601.64 | 05-SEP-07:02 | 6877.71 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.125609E+11 | 0.300225E+10 | 327.96 | 0.750151E+10 | 0.505937E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 30692.49 | 08-OCT-08:62 | 22176.45 | 26-OCT-07:02 | 16945.31 | 08-OCT-08:03 | 6422.00 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.498610E+10 | 0.121927E+10 | 229.81 | 0.310064E+10 | 0.188546E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 29047.51 | 02-NOV-07:02 | 18063.52 | 03-NOV-07:02 | 13407.17 | 04-NOV-07:03 | 6147.36 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.317939E+10 | 0.778384E+09 | 139.69 | 0.195678E+10 | 0.122261E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 26534.57 | 11-DEC-08:62 | 14775.31 | 15-DEC-08:62 | 14749.77 | 11-DEC-08:62 | 5518.79 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.111676E+12 | 0.269945E+11 | 3145.87 | 0.655761E+11 | 0.461004E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.158545E+10 | 0.400380E+09 | 93.33 | 0.989180E+09 | 0.596266E+09 | 0.00 | 0.79 | 0.00 | 10547.00 | 6582.92 | 4178.36 | 2461.52 | 0.00 | |||||||
Maximum of Months | 0.169726E+11 | 0.406151E+10 | 364.59 | 0.966479E+10 | 0.754645E+10 | 0.00 | 1.00 | 0.00 | 30840.78 | 22176.45 | 18192.93 | 6877.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.154727E+10 | 0.391016E+09 | 91.92 | 0.964159E+09 | 0.583111E+09 | 0.00 | 0.78 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10455.00 | 19-JAN-14:00 | 6521.17 | 01-JAN-14:10 | 4592.16 | 19-JAN-14:00 | 2441.78 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.227528E+10 | 0.570645E+09 | 123.64 | 0.140187E+10 | 0.873404E+09 | 0.00 | 0.82 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10900.67 | 24-FEB-13:50 | 6986.20 | 02-FEB-13:30 | 4164.00 | 24-FEB-13:10 | 2622.08 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.325709E+10 | 0.822011E+09 | 175.50 | 0.207228E+10 | 0.118481E+10 | 0.00 | 0.89 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 12205.30 | 30-MAR-13:00 | 7655.13 | 26-MAR-14:00 | 4930.88 | 07-MAR-13:40 | 2930.10 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.613722E+10 | 0.154637E+10 | 279.25 | 0.401748E+10 | 0.211974E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:05 | 25771.21 | 29-APR-07:03 | 14658.57 | 29-APR-07:03 | 11112.63 | 29-APR-07:03 | 5497.53 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.139524E+11 | 0.340915E+10 | 358.93 | 0.841878E+10 | 0.553364E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 30173.85 | 21-MAY-08:62 | 19573.28 | 12-MAY-07:02 | 16335.99 | 21-MAY-08:62 | 6432.89 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.150839E+11 | 0.366328E+10 | 352.12 | 0.898525E+10 | 0.609862E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 30551.21 | 19-JUN-07:02 | 20111.00 | 14-JUN-07:02 | 17749.13 | 19-JUN-07:02 | 6496.03 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.167186E+11 | 0.398489E+10 | 352.12 | 0.919321E+10 | 0.752542E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30693.57 | 03-JUL-07:02 | 18890.57 | 19-JUL-07:02 | 18086.95 | 02-JUL-08:03 | 6595.17 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.169053E+11 | 0.404449E+10 | 364.61 | 0.961714E+10 | 0.728816E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30649.29 | 14-AUG-07:03 | 20682.57 | 31-AUG-07:02 | 18128.97 | 14-AUG-07:03 | 6454.17 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.145012E+11 | 0.342104E+10 | 344.66 | 0.794611E+10 | 0.655511E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30705.21 | 05-SEP-07:02 | 19037.30 | 23-SEP-07:02 | 17540.39 | 05-SEP-07:02 | 6847.38 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.124929E+11 | 0.298555E+10 | 327.38 | 0.745207E+10 | 0.504079E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 30555.50 | 08-OCT-08:62 | 22067.59 | 26-OCT-07:02 | 16889.53 | 08-OCT-08:62 | 6393.78 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.492608E+10 | 0.120451E+10 | 228.22 | 0.305665E+10 | 0.186943E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 28923.47 | 02-NOV-07:02 | 17928.17 | 03-NOV-07:02 | 13061.87 | 04-NOV-07:03 | 6120.62 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.313784E+10 | 0.768380E+09 | 138.19 | 0.192697E+10 | 0.121087E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 25395.36 | 11-DEC-08:62 | 14296.58 | 15-DEC-08:62 | 14140.64 | 11-DEC-08:62 | 5282.62 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.110935E+12 | 0.268113E+11 | 3136.54 | 0.650520E+11 | 0.458831E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.154727E+10 | 0.391016E+09 | 91.92 | 0.964159E+09 | 0.583111E+09 | 0.00 | 0.78 | 0.00 | 10455.00 | 6521.17 | 4164.00 | 2441.78 | 0.00 | |||||||
Maximum of Months | 0.169053E+11 | 0.404449E+10 | 364.61 | 0.961714E+10 | 0.752542E+10 | 0.00 | 1.00 | 0.00 | 30705.21 | 22067.59 | 18128.97 | 6847.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.147877E+10 | 0.374750E+09 | 89.39 | 0.919490E+09 | 0.559283E+09 | 0.00 | 0.78 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10333.15 | 19-JAN-14:00 | 6422.35 | 01-JAN-14:10 | 4549.34 | 19-JAN-14:00 | 2419.86 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.217875E+10 | 0.548073E+09 | 119.31 | 0.133875E+10 | 0.840006E+09 | 0.00 | 0.81 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10744.99 | 24-FEB-14:00 | 6868.05 | 02-FEB-13:30 | 4124.13 | 24-FEB-13:10 | 2592.43 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.313622E+10 | 0.793472E+09 | 170.42 | 0.198563E+10 | 0.115060E+10 | 0.00 | 0.89 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 12091.15 | 30-MAR-13:00 | 7539.20 | 26-MAR-14:00 | 4872.89 | 07-MAR-13:40 | 2910.22 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.597648E+10 | 0.150906E+10 | 273.14 | 0.390334E+10 | 0.207313E+10 | 0.00 | 1.00 | 28-APR-07:03 | 0.00 | 01-APR-00:05 | 22998.67 | 29-APR-07:03 | 12926.04 | 29-APR-07:03 | 10072.63 | 29-APR-07:03 | 4909.22 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.138666E+11 | 0.339132E+10 | 358.95 | 0.836011E+10 | 0.550652E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 30244.78 | 21-MAY-08:62 | 19548.73 | 12-MAY-07:02 | 16481.10 | 21-MAY-08:62 | 6451.95 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.150390E+11 | 0.365445E+10 | 352.76 | 0.895336E+10 | 0.608560E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 30623.10 | 19-JUN-07:02 | 20102.85 | 14-JUN-07:02 | 17899.91 | 19-JUN-07:02 | 6514.34 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.167108E+11 | 0.398471E+10 | 352.43 | 0.918950E+10 | 0.752132E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30783.24 | 03-JUL-07:02 | 18913.24 | 19-JUL-07:02 | 18185.06 | 02-JUL-08:03 | 6614.39 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.169252E+11 | 0.405039E+10 | 365.65 | 0.963180E+10 | 0.729342E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30738.83 | 14-AUG-07:01 | 20720.67 | 31-AUG-07:02 | 18219.83 | 14-AUG-07:03 | 6473.54 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.144908E+11 | 0.342017E+10 | 345.37 | 0.794036E+10 | 0.655041E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30794.91 | 05-SEP-07:02 | 19046.07 | 23-SEP-07:02 | 17613.82 | 05-SEP-07:02 | 6867.34 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.124543E+11 | 0.297774E+10 | 326.39 | 0.742444E+10 | 0.502983E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 30639.09 | 08-OCT-08:62 | 22119.84 | 26-OCT-07:02 | 16980.41 | 22-OCT-08:62 | 6412.17 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.481555E+10 | 0.117828E+10 | 221.56 | 0.297515E+10 | 0.184040E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 29004.92 | 02-NOV-07:02 | 17892.32 | 03-NOV-07:02 | 12131.86 | 04-NOV-07:03 | 6133.39 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.305851E+10 | 0.750322E+09 | 134.44 | 0.187133E+10 | 0.118718E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 22933.88 | 11-DEC-08:62 | 13488.98 | 11-DEC-08:62 | 9444.90 | 11-DEC-08:62 | 4771.62 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.110131E+12 | 0.266327E+11 | 3109.79 | 0.644932E+11 | 0.456377E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.147877E+10 | 0.374750E+09 | 89.39 | 0.919490E+09 | 0.559283E+09 | 0.00 | 0.78 | 0.00 | 10333.15 | 6422.35 | 4124.13 | 2419.86 | 0.00 | |||||||
Maximum of Months | 0.169252E+11 | 0.405039E+10 | 365.65 | 0.963180E+10 | 0.752132E+10 | 0.00 | 1.00 | 0.00 | 30794.91 | 22119.84 | 18219.83 | 6867.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.153886E+10 | 0.393254E+09 | 85.64 | 0.968343E+09 | 0.570518E+09 | 0.00 | 0.75 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 11238.27 | 19-JAN-14:00 | 6874.02 | 01-JAN-14:00 | 4798.73 | 19-JAN-14:00 | 2658.05 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.223581E+10 | 0.568446E+09 | 113.25 | 0.138984E+10 | 0.845964E+09 | 0.00 | 0.78 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 | 11579.64 | 24-FEB-13:10 | 7315.94 | 02-FEB-13:20 | 4339.99 | 24-FEB-13:10 | 2831.92 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.331719E+10 | 0.846577E+09 | 166.08 | 0.212349E+10 | 0.119370E+10 | 0.00 | 0.85 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 12943.96 | 30-MAR-13:00 | 8182.37 | 26-MAR-14:00 | 5163.16 | 07-MAR-13:30 | 3164.17 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.626926E+10 | 0.159873E+10 | 264.60 | 0.414674E+10 | 0.212252E+10 | 0.00 | 1.00 | 28-APR-14:20 | 0.00 | 01-APR-00:05 | 17257.39 | 28-APR-16:10 | 11042.03 | 28-APR-15:00 | 7803.47 | 29-APR-07:03 | 4140.73 | 28-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.149920E+11 | 0.370332E+10 | 358.52 | 0.916285E+10 | 0.582911E+10 | 0.00 | 1.00 | 01-MAY-14:30 | 0.00 | 01-MAY-00:10 | 34445.15 | 21-MAY-08:62 | 20743.76 | 31-MAY-07:02 | 19410.72 | 21-MAY-08:62 | 7308.71 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.164195E+11 | 0.402483E+10 | 353.86 | 0.994440E+10 | 0.647515E+10 | 0.00 | 1.00 | 02-JUN-07:02 | 0.00 | 01-JUN-00:10 | 34813.13 | 19-JUN-07:02 | 21169.39 | 16-JUN-07:02 | 20905.03 | 19-JUN-07:02 | 7403.82 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.183641E+11 | 0.441713E+10 | 353.28 | 0.103345E+11 | 0.802965E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 34918.03 | 03-JUL-07:02 | 20662.60 | 19-JUL-07:02 | 21521.43 | 02-JUL-08:03 | 7498.01 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.187534E+11 | 0.451933E+10 | 366.94 | 0.109022E+11 | 0.785115E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 34869.16 | 07-AUG-07:02 | 23981.84 | 31-AUG-07:02 | 20887.58 | 14-AUG-07:04 | 7341.03 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.159516E+11 | 0.379505E+10 | 345.88 | 0.894135E+10 | 0.701029E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 34931.27 | 05-SEP-07:02 | 21584.26 | 01-SEP-07:02 | 20365.09 | 05-SEP-07:03 | 7769.59 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.136655E+11 | 0.328963E+10 | 324.20 | 0.828920E+10 | 0.537628E+10 | 0.00 | 1.00 | 03-OCT-07:02 | 0.00 | 01-OCT-00:10 | 34881.24 | 08-OCT-08:62 | 22552.39 | 26-OCT-07:02 | 20116.85 | 22-OCT-08:62 | 7280.98 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.509672E+10 | 0.125810E+10 | 212.93 | 0.318834E+10 | 0.190838E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 33300.37 | 02-NOV-07:02 | 19783.63 | 03-NOV-07:02 | 14985.54 | 02-NOV-07:02 | 6983.09 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.316926E+10 | 0.787912E+09 | 131.26 | 0.195682E+10 | 0.121244E+10 | 0.00 | 0.99 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 | 16401.58 | 15-DEC-08:62 | 8857.29 | 13-DEC-15:10 | 8443.92 | 11-DEC-08:62 | 3431.11 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.119773E+12 | 0.292023E+11 | 3076.45 | 0.713481E+11 | 0.484252E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.153886E+10 | 0.393254E+09 | 85.64 | 0.968343E+09 | 0.570518E+09 | 0.00 | 0.75 | 0.00 | 11238.27 | 6874.02 | 4339.99 | 2658.05 | 0.00 | |||||||
Maximum of Months | 0.187534E+11 | 0.451933E+10 | 366.94 | 0.109022E+11 | 0.802965E+10 | 0.00 | 1.00 | 0.00 | 34931.27 | 23981.84 | 21521.43 | 7769.59 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.67 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 44.49 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.99 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.79 | 6.45 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.77 | 4.23 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.27 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.68 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.55 | 18.36 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.23 | 39.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 52.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.56 | 27.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.23 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.67 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 44.49 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.99 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.79 | 6.45 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.77 | 4.23 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.27 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.68 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.55 | 18.36 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.23 | 39.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 52.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.56 | 27.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.23 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.67 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 44.49 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.99 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.79 | 6.45 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.77 | 4.23 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.27 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.68 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.55 | 18.36 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.23 | 39.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 52.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.56 | 27.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.23 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.22 | 57.46 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.67 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 44.49 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.99 | 29.17 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.79 | 6.45 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.77 | 4.23 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.27 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.68 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.55 | 18.36 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.23 | 39.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 52.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.56 | 27.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.23 | 57.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 160.43 | 68.27 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 147.69 | 59.54 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.30 | 52.87 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.29 | 34.78 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 76.29 | 8.89 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 77.41 | 7.77 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 80.95 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 94.83 | 8.35 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 105.06 | 11.97 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 149.48 | 21.94 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.55 | 47.56 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 161.76 | 61.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.94 | 32.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 76.29 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.55 | 68.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 160.43 | 68.27 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 147.69 | 59.54 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.30 | 52.87 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.29 | 34.78 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 76.29 | 8.89 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 77.41 | 7.77 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 80.95 | 5.12 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 94.83 | 8.35 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 105.06 | 11.97 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 149.48 | 21.94 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.55 | 47.56 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 161.76 | 61.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.94 | 32.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 76.29 | 5.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.55 | 68.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 131.54 | 60.91 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.34 | 52.60 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 79.79 | 46.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.63 | 29.96 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.96 | 7.61 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 65.13 | 6.58 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 68.23 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.81 | 6.84 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 88.01 | 9.89 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.63 | 18.45 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.66 | 40.65 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.44 | 54.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.23 | 28.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.96 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.66 | 60.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 131.54 | 60.91 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.34 | 52.60 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 79.79 | 46.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.63 | 29.96 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.96 | 7.61 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 65.13 | 6.58 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 68.23 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.81 | 6.84 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 88.01 | 9.89 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.63 | 18.45 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.66 | 40.65 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.44 | 54.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.23 | 28.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.96 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.66 | 60.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 158.48 | 72.29 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 146.16 | 62.49 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 96.13 | 55.70 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 78.88 | 35.71 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 76.49 | 9.15 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 77.81 | 7.92 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 81.49 | 5.17 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 95.47 | 8.23 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 105.48 | 11.89 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 149.62 | 22.04 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 161.92 | 48.42 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 160.60 | 64.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.57 | 33.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 76.49 | 5.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 161.92 | 72.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.07 | 59.71 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.71 | 51.96 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 79.95 | 46.68 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.50 | 30.96 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.28 | 9.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.40 | 8.47 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.73 | 5.79 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.78 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.30 | 11.85 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.21 | 20.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.75 | 41.54 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.76 | 53.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.91 | 28.98 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.28 | 5.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.75 | 59.71 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.07 | 59.71 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.71 | 51.96 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 79.95 | 46.68 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.50 | 30.96 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.28 | 9.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.40 | 8.47 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.73 | 5.79 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.78 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.30 | 11.85 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.21 | 20.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.75 | 41.54 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.76 | 53.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.91 | 28.98 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.28 | 5.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.75 | 59.71 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 158.25 | 70.48 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 145.81 | 61.39 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 95.80 | 55.12 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.30 | 36.67 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.28 | 11.09 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.54 | 10.09 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.33 | 6.94 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 93.78 | 10.19 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.09 | 14.12 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.31 | 24.24 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.14 | 49.17 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.10 | 63.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.58 | 34.29 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.28 | 6.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.14 | 70.48 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.40 | 58.84 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.97 | 51.28 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.12 | 46.15 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.55 | 30.80 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.25 | 9.42 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.35 | 8.62 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.64 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.73 | 8.73 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.25 | 12.01 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.19 | 20.56 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.82 | 41.33 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.94 | 53.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 28.80 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.25 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.82 | 58.84 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.40 | 58.84 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.97 | 51.28 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.12 | 46.15 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.55 | 30.80 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.25 | 9.42 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.35 | 8.62 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.64 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.73 | 8.73 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.25 | 12.01 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.19 | 20.56 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.82 | 41.33 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.94 | 53.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 28.80 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.25 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.82 | 58.84 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 158.64 | 69.46 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.12 | 60.59 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 95.99 | 54.50 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.36 | 36.48 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.25 | 11.22 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.49 | 10.27 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.23 | 7.16 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 93.72 | 10.41 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.03 | 14.30 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.29 | 24.38 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.23 | 48.92 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.32 | 63.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.66 | 34.09 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.25 | 7.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.23 | 69.46 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.83 | 57.92 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.35 | 50.49 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.42 | 45.42 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.72 | 30.34 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.39 | 9.09 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.48 | 8.31 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.79 | 5.71 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.85 | 8.43 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.36 | 11.71 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.29 | 20.22 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.01 | 40.87 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.22 | 52.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.18 | 28.31 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.39 | 5.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.01 | 57.92 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.83 | 57.92 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.35 | 50.49 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.42 | 45.42 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.72 | 30.34 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.39 | 9.09 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.48 | 8.31 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.79 | 5.71 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.85 | 8.43 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.36 | 11.71 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.29 | 20.22 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.01 | 40.87 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.22 | 52.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.18 | 28.31 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.39 | 5.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.01 | 57.92 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.15 | 68.38 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.57 | 59.65 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.35 | 53.63 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.56 | 35.94 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.42 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.65 | 9.90 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.41 | 6.84 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 93.87 | 10.05 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.15 | 13.95 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.42 | 23.99 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.45 | 48.39 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.65 | 62.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.90 | 33.51 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.42 | 6.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.45 | 68.38 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.89 | 55.95 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.38 | 48.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 43.60 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 29.11 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.44 | 8.13 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.44 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.81 | 4.95 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.88 | 7.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.32 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 19.28 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 51.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.58 | 27.06 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.44 | 4.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.50 | 55.95 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.89 | 55.95 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.38 | 48.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 43.60 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 29.11 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.44 | 8.13 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.44 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.81 | 4.95 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.88 | 7.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.32 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 19.28 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 51.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.58 | 27.06 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.44 | 4.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.50 | 55.95 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.89 | 55.95 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.38 | 48.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 43.60 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 29.11 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.44 | 8.13 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.44 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.81 | 4.95 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.88 | 7.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.32 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 19.28 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 51.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.58 | 27.06 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.44 | 4.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.50 | 55.95 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.89 | 55.95 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.38 | 48.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 43.60 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 29.11 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.44 | 8.13 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.44 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.81 | 4.95 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.88 | 7.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.32 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 19.28 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 51.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.58 | 27.06 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.44 | 4.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.50 | 55.95 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.36 | 66.09 | 1.83 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.74 | 57.53 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.28 | 51.51 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.07 | 34.48 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.49 | 9.69 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.61 | 8.71 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.43 | 5.94 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 93.90 | 9.01 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.10 | 12.91 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.59 | 22.88 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.00 | 46.99 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.48 | 60.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.35 | 32.03 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.49 | 5.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.00 | 66.09 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.36 | 66.09 | 1.83 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.74 | 57.53 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.28 | 51.51 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.07 | 34.48 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.49 | 9.69 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.61 | 8.71 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.43 | 5.94 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 93.90 | 9.01 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.10 | 12.91 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.59 | 22.88 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.00 | 46.99 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.48 | 60.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.35 | 32.03 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.49 | 5.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.00 | 66.09 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.69 | 55.75 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.21 | 48.44 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.13 | 43.40 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 28.86 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.70 | 7.79 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.75 | 6.96 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.19 | 4.63 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.16 | 7.18 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.46 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 18.92 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.36 | 39.44 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.77 | 50.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.63 | 26.76 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.70 | 4.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.36 | 55.75 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.69 | 55.75 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.21 | 48.44 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.13 | 43.40 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.16 | 28.86 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.70 | 7.79 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.75 | 6.96 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.19 | 4.63 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.16 | 7.18 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.46 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.47 | 18.92 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.36 | 39.44 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.77 | 50.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.63 | 26.76 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.70 | 4.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.36 | 55.75 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.19 | 65.81 | 1.83 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.61 | 57.24 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.21 | 51.25 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.10 | 34.18 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.79 | 9.29 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.98 | 8.30 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.88 | 5.57 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 94.24 | 8.57 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.29 | 12.44 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.64 | 22.45 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.88 | 46.70 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.32 | 60.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.44 | 31.68 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.79 | 5.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.88 | 65.81 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.86 | 55.43 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 48.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.26 | 43.11 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.25 | 28.69 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.77 | 7.70 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.82 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.26 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.21 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.51 | 10.35 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.53 | 18.82 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 39.28 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.90 | 50.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.72 | 26.60 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.77 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 55.43 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.86 | 55.43 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 48.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.26 | 43.11 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.25 | 28.69 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.77 | 7.70 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.82 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.26 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.21 | 7.11 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.51 | 10.35 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.53 | 18.82 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 39.28 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.90 | 50.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.72 | 26.60 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.77 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 55.43 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.39 | 65.44 | 1.83 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.82 | 56.87 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.37 | 50.91 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.20 | 33.98 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.88 | 9.19 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 77.06 | 8.21 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.97 | 5.49 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 94.30 | 8.49 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.35 | 12.34 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.70 | 22.33 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.99 | 46.50 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.47 | 59.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.55 | 31.48 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.88 | 5.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.99 | 65.44 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.21 | 54.67 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.79 | 47.31 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.42 | 28.21 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.58 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.81 | 6.81 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.20 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.14 | 7.14 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.46 | 10.35 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.53 | 18.73 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.64 | 38.89 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.19 | 49.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.85 | 26.25 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.64 | 54.67 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.21 | 54.67 | 1.83 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.79 | 47.31 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.42 | 28.21 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.80 | 7.58 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.81 | 6.81 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.20 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 79.14 | 7.14 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 87.46 | 10.35 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 124.53 | 18.73 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.64 | 38.89 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.19 | 49.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.85 | 26.25 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.80 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.64 | 54.67 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.80 | 64.55 | 2.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.30 | 55.91 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.72 | 49.99 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.41 | 33.43 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.92 | 9.05 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 77.05 | 8.13 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 79.90 | 5.49 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 94.21 | 8.53 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 104.29 | 12.34 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 148.71 | 22.22 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.22 | 46.05 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.82 | 58.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.71 | 31.08 | 2.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.92 | 5.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.22 | 64.55 | 2.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.74 | 52.14 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.49 | 44.60 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.92 | 39.62 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.56 | 26.51 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.25 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.02 | 6.82 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.11 | 4.87 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.02 | 7.71 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.57 | 10.76 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.93 | 18.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.79 | 37.66 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.68 | 47.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.62 | 25.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.25 | 4.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.79 | 52.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.74 | 52.14 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.49 | 44.60 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.92 | 39.62 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.56 | 26.51 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 63.25 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 64.02 | 6.82 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.11 | 4.87 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.02 | 7.71 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.57 | 10.76 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.93 | 18.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.79 | 37.66 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.68 | 47.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.62 | 25.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 63.25 | 4.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.79 | 52.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.43 | 61.57 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.13 | 52.73 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.16 | 46.81 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.57 | 31.43 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 75.26 | 8.81 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 76.10 | 8.15 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 78.59 | 5.85 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.87 | 9.20 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 103.22 | 12.83 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.98 | 22.19 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.40 | 44.60 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.41 | 56.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.43 | 29.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 75.26 | 5.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.41 | 61.57 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356822E+09 | 0.153913E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296758E+09 | 0.121140E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216413E+09 | 0.119164E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171057E+09 | 75620950.09 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170873E+09 | 19790448.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167929E+09 | 16723742.66 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.181513E+09 | 11332314.04 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212324E+09 | 18597640.02 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.227275E+09 | 25800584.70 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333584E+09 | 49177981.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350507E+09 | 0.103449E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360144E+09 | 0.139376E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304520E+10 | 0.854085E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167929E+09 | 11332314.04 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360144E+09 | 0.153913E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356822E+09 | 0.153913E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296758E+09 | 0.121140E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216413E+09 | 0.119164E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171057E+09 | 75620950.09 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170873E+09 | 19790448.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167929E+09 | 16723742.66 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.181513E+09 | 11332314.04 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212324E+09 | 18597640.02 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.227275E+09 | 25800584.70 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333584E+09 | 49177981.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350507E+09 | 0.103449E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360144E+09 | 0.139376E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304520E+10 | 0.854085E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167929E+09 | 11332314.04 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360144E+09 | 0.153913E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356822E+09 | 0.153913E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296758E+09 | 0.121140E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216413E+09 | 0.119164E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171057E+09 | 75620950.09 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170873E+09 | 19790448.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167929E+09 | 16723742.66 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.181513E+09 | 11332314.04 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212324E+09 | 18597640.02 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.227275E+09 | 25800584.70 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333584E+09 | 49177981.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350507E+09 | 0.103449E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360144E+09 | 0.139376E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304520E+10 | 0.854085E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167929E+09 | 11332314.04 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360144E+09 | 0.153913E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356822E+09 | 0.153913E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296758E+09 | 0.121140E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216413E+09 | 0.119164E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171057E+09 | 75620950.09 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170873E+09 | 19790448.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167929E+09 | 16723742.66 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.181513E+09 | 11332314.04 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212324E+09 | 18597640.02 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.227275E+09 | 25800584.70 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333584E+09 | 49177981.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350507E+09 | 0.103449E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360144E+09 | 0.139376E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304520E+10 | 0.854085E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167929E+09 | 11332314.04 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360144E+09 | 0.153913E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.429687E+09 | 0.182849E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.357302E+09 | 0.144031E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.260596E+09 | 0.141617E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205525E+09 | 90162712.22 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.204335E+09 | 23806959.58 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.200638E+09 | 20129419.71 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.216816E+09 | 13716368.16 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.253994E+09 | 22372944.90 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.272325E+09 | 31014303.41 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.400355E+09 | 58770905.55 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421325E+09 | 0.123266E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.433269E+09 | 0.165698E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.365617E+10 | 0.101743E+10 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.200638E+09 | 13716368.16 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.433269E+09 | 0.182849E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.429687E+09 | 0.182849E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.357302E+09 | 0.144031E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.260596E+09 | 0.141617E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205525E+09 | 90162712.22 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.204335E+09 | 23806959.58 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.200638E+09 | 20129419.71 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.216816E+09 | 13716368.16 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.253994E+09 | 22372944.90 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.272325E+09 | 31014303.41 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.400355E+09 | 58770905.55 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421325E+09 | 0.123266E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.433269E+09 | 0.165698E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.365617E+10 | 0.101743E+10 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.200638E+09 | 13716368.16 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.433269E+09 | 0.182849E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.352313E+09 | 0.163139E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.293543E+09 | 0.127257E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.213708E+09 | 0.125626E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170125E+09 | 77656279.66 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.171318E+09 | 20379125.72 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.168822E+09 | 17059837.38 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.182734E+09 | 11439583.52 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.213751E+09 | 18325553.10 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.228131E+09 | 25627916.08 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333816E+09 | 49406661.26 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349045E+09 | 0.105370E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.357412E+09 | 0.145211E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303472E+10 | 0.886497E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.168822E+09 | 11439583.52 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.357412E+09 | 0.163139E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.352313E+09 | 0.163139E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.293543E+09 | 0.127257E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.213708E+09 | 0.125626E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170125E+09 | 77656279.66 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.171318E+09 | 20379125.72 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.168822E+09 | 17059837.38 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.182734E+09 | 11439583.52 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.213751E+09 | 18325553.10 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.228131E+09 | 25627916.08 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333816E+09 | 49406661.26 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349045E+09 | 0.105370E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.357412E+09 | 0.145211E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303472E+10 | 0.886497E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.168822E+09 | 11439583.52 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.357412E+09 | 0.163139E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.424483E+09 | 0.193627E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.353600E+09 | 0.151185E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.257467E+09 | 0.149191E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.204464E+09 | 92550978.12 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.204869E+09 | 24512079.39 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.201694E+09 | 20533358.15 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.218263E+09 | 13849455.38 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.255720E+09 | 22046449.92 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.273399E+09 | 30809750.68 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.400739E+09 | 59022296.85 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.419707E+09 | 0.125503E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.430156E+09 | 0.172511E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.364456E+10 | 0.105534E+10 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.201694E+09 | 13849455.38 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.430156E+09 | 0.193627E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.353731E+09 | 0.159930E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.294451E+09 | 0.125701E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214145E+09 | 0.125019E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169788E+09 | 80259216.12 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169483E+09 | 24925886.97 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.166914E+09 | 21949917.19 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178718E+09 | 15519233.73 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211003E+09 | 22901390.56 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226291E+09 | 30716938.02 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332678E+09 | 54744746.94 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349269E+09 | 0.107671E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358254E+09 | 0.144495E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302472E+10 | 0.913833E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.166914E+09 | 15519233.73 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358254E+09 | 0.159930E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.353731E+09 | 0.159930E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.294451E+09 | 0.125701E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214145E+09 | 0.125019E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169788E+09 | 80259216.12 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169483E+09 | 24925886.97 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.166914E+09 | 21949917.19 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178718E+09 | 15519233.73 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211003E+09 | 22901390.56 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226291E+09 | 30716938.02 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332678E+09 | 54744746.94 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349269E+09 | 0.107671E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358254E+09 | 0.144495E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302472E+10 | 0.913833E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.166914E+09 | 15519233.73 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358254E+09 | 0.159930E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.423846E+09 | 0.188785E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.352744E+09 | 0.148505E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.256581E+09 | 0.147621E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.202961E+09 | 95044637.94 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.201643E+09 | 29696637.50 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.198400E+09 | 26148196.73 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.212470E+09 | 18594846.84 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.251179E+09 | 27305144.88 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.269791E+09 | 36588285.71 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.397245E+09 | 64924066.23 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417679E+09 | 0.127458E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.428805E+09 | 0.170685E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361334E+10 | 0.108136E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.198400E+09 | 18594846.84 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.428805E+09 | 0.188785E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.354617E+09 | 0.157608E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295073E+09 | 0.124067E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214583E+09 | 0.123619E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169909E+09 | 79836628.93 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169416E+09 | 25220857.18 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.166806E+09 | 22350602.51 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178497E+09 | 15997857.62 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.210868E+09 | 23377566.23 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226162E+09 | 31125400.14 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332626E+09 | 55056207.04 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349461E+09 | 0.107122E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358750E+09 | 0.142985E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302677E+10 | 0.908366E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.166806E+09 | 15997857.62 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358750E+09 | 0.157608E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.354617E+09 | 0.157608E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295073E+09 | 0.124067E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214583E+09 | 0.123619E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169909E+09 | 79836628.93 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169416E+09 | 25220857.18 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.166806E+09 | 22350602.51 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178497E+09 | 15997857.62 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.210868E+09 | 23377566.23 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226162E+09 | 31125400.14 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332626E+09 | 55056207.04 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349461E+09 | 0.107122E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358750E+09 | 0.142985E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302677E+10 | 0.908366E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.166806E+09 | 15997857.62 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358750E+09 | 0.157608E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.424904E+09 | 0.186051E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.353487E+09 | 0.146580E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.257105E+09 | 0.145970E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203107E+09 | 94545754.87 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.201562E+09 | 30044560.93 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.198271E+09 | 26621173.95 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.212215E+09 | 19167574.69 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.251020E+09 | 27868819.45 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.269638E+09 | 37070925.59 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.397183E+09 | 65291754.10 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417909E+09 | 0.126808E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.429397E+09 | 0.168905E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361580E+10 | 0.107492E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.198271E+09 | 19167574.69 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.429397E+09 | 0.186051E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355767E+09 | 0.155139E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295997E+09 | 0.122135E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215386E+09 | 0.121642E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170351E+09 | 78647808.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169781E+09 | 24344317.24 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167145E+09 | 21528475.65 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178891E+09 | 15284438.36 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211197E+09 | 22573546.24 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226429E+09 | 30346243.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332902E+09 | 54165592.43 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349939E+09 | 0.105940E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359501E+09 | 0.141081E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303329E+10 | 0.892827E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167145E+09 | 15284438.36 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359501E+09 | 0.155139E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355767E+09 | 0.155139E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295997E+09 | 0.122135E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215386E+09 | 0.121642E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170351E+09 | 78647808.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169781E+09 | 24344317.24 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167145E+09 | 21528475.65 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178891E+09 | 15284438.36 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211197E+09 | 22573546.24 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226429E+09 | 30346243.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.332902E+09 | 54165592.43 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349939E+09 | 0.105940E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359501E+09 | 0.141081E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303329E+10 | 0.892827E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167145E+09 | 15284438.36 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359501E+09 | 0.155139E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.426272E+09 | 0.183148E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.354591E+09 | 0.144310E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.258065E+09 | 0.143647E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203638E+09 | 93149359.16 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.202000E+09 | 29018142.77 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.198677E+09 | 25657035.92 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.212681E+09 | 18327650.16 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.251413E+09 | 26926996.83 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.269957E+09 | 36157284.96 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.397515E+09 | 64248906.72 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418482E+09 | 0.125419E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.430294E+09 | 0.166666E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362358E+10 | 0.105667E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.198677E+09 | 18327650.16 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.430294E+09 | 0.183148E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358622E+09 | 0.149863E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298482E+09 | 0.117744E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217552E+09 | 0.116788E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171495E+09 | 75441098.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169927E+09 | 21768096.65 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167020E+09 | 18933487.55 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178931E+09 | 13267312.20 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211270E+09 | 20227838.99 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226326E+09 | 28075923.47 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333368E+09 | 51651755.24 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351208E+09 | 0.102844E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361466E+09 | 0.136604E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304567E+10 | 0.853208E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167020E+09 | 13267312.20 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361466E+09 | 0.149863E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358622E+09 | 0.149863E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298482E+09 | 0.117744E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217552E+09 | 0.116788E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171495E+09 | 75441098.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169927E+09 | 21768096.65 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167020E+09 | 18933487.55 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178931E+09 | 13267312.20 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211270E+09 | 20227838.99 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226326E+09 | 28075923.47 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333368E+09 | 51651755.24 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351208E+09 | 0.102844E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361466E+09 | 0.136604E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304567E+10 | 0.853208E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167020E+09 | 13267312.20 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361466E+09 | 0.149863E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358622E+09 | 0.149863E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298482E+09 | 0.117744E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217552E+09 | 0.116788E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171495E+09 | 75441098.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169927E+09 | 21768096.65 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167020E+09 | 18933487.55 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178931E+09 | 13267312.20 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211270E+09 | 20227838.99 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226326E+09 | 28075923.47 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333368E+09 | 51651755.24 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351208E+09 | 0.102844E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361466E+09 | 0.136604E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304567E+10 | 0.853208E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167020E+09 | 13267312.20 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361466E+09 | 0.149863E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358622E+09 | 0.149863E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298482E+09 | 0.117744E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217552E+09 | 0.116788E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171495E+09 | 75441098.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169927E+09 | 21768096.65 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167020E+09 | 18933487.55 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178931E+09 | 13267312.20 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211270E+09 | 20227838.99 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226326E+09 | 28075923.47 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333368E+09 | 51651755.24 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351208E+09 | 0.102844E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361466E+09 | 0.136604E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304567E+10 | 0.853208E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167020E+09 | 13267312.20 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361466E+09 | 0.149863E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429507E+09 | 0.177007E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357424E+09 | 0.139186E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260553E+09 | 0.137977E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204957E+09 | 89379662.42 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.202193E+09 | 25957658.39 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.198569E+09 | 22572310.75 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.212754E+09 | 15911570.02 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.251495E+09 | 24132040.38 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.269820E+09 | 33459398.82 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.397982E+09 | 61275471.57 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419895E+09 | 0.121787E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432500E+09 | 0.161444E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.363765E+10 | 0.101009E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.198569E+09 | 15911570.02 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432500E+09 | 0.177007E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429507E+09 | 0.177007E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357424E+09 | 0.139186E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260553E+09 | 0.137977E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204957E+09 | 89379662.42 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.202193E+09 | 25957658.39 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.198569E+09 | 22572310.75 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.212754E+09 | 15911570.02 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.251495E+09 | 24132040.38 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.269820E+09 | 33459398.82 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.397982E+09 | 61275471.57 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419895E+09 | 0.121787E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432500E+09 | 0.161444E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.363765E+10 | 0.101009E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.198569E+09 | 15911570.02 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432500E+09 | 0.177007E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358077E+09 | 0.149308E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298081E+09 | 0.117184E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217288E+09 | 0.116230E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171487E+09 | 74793982.63 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170606E+09 | 20852800.49 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167834E+09 | 18031197.16 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179959E+09 | 12410842.99 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212019E+09 | 19218502.16 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226706E+09 | 27034687.65 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333387E+09 | 50687185.80 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350842E+09 | 0.102240E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360967E+09 | 0.136052E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304725E+10 | 0.844042E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167834E+09 | 12410842.99 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360967E+09 | 0.149308E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358077E+09 | 0.149308E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298081E+09 | 0.117184E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217288E+09 | 0.116230E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171487E+09 | 74793982.63 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170606E+09 | 20852800.49 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167834E+09 | 18031197.16 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179959E+09 | 12410842.99 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212019E+09 | 19218502.16 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226706E+09 | 27034687.65 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333387E+09 | 50687185.80 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350842E+09 | 0.102240E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360967E+09 | 0.136052E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304725E+10 | 0.844042E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167834E+09 | 12410842.99 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360967E+09 | 0.149308E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429045E+09 | 0.176274E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357096E+09 | 0.138475E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260355E+09 | 0.137265E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205018E+09 | 88599096.94 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.203008E+09 | 24887419.04 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.199530E+09 | 21513680.68 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.213961E+09 | 14906111.74 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.252407E+09 | 22948806.73 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.270322E+09 | 32239422.64 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.398115E+09 | 60132470.56 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419597E+09 | 0.121043E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432069E+09 | 0.160726E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.364052E+10 | 0.999011E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.199530E+09 | 14906111.74 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432069E+09 | 0.176274E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358523E+09 | 0.148469E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298510E+09 | 0.116420E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217656E+09 | 0.115457E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171710E+09 | 74353190.61 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170792E+09 | 20616923.32 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.168004E+09 | 17824240.34 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.180146E+09 | 12246202.93 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212166E+09 | 19037772.04 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226829E+09 | 26830318.92 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333532E+09 | 50415041.51 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351085E+09 | 0.101808E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361317E+09 | 0.135299E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.305027E+10 | 0.838777E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.168004E+09 | 12246202.93 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361317E+09 | 0.148469E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358523E+09 | 0.148469E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298510E+09 | 0.116420E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217656E+09 | 0.115457E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171710E+09 | 74353190.61 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170792E+09 | 20616923.32 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.168004E+09 | 17824240.34 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.180146E+09 | 12246202.93 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.212166E+09 | 19037772.04 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226829E+09 | 26830318.92 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333532E+09 | 50415041.51 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351085E+09 | 0.101808E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361317E+09 | 0.135299E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.305027E+10 | 0.838777E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.168004E+09 | 12246202.93 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361317E+09 | 0.148469E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429576E+09 | 0.175286E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357609E+09 | 0.137576E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260796E+09 | 0.136354E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205285E+09 | 88079705.22 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.203229E+09 | 24608147.54 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.199733E+09 | 21268803.10 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.214182E+09 | 14709869.81 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.252582E+09 | 22734981.57 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.270469E+09 | 31997925.98 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.398290E+09 | 59810993.85 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419889E+09 | 0.120533E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432488E+09 | 0.159839E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.364413E+10 | 0.992798E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.199733E+09 | 14709869.81 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432488E+09 | 0.175286E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359460E+09 | 0.146428E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299476E+09 | 0.114449E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218448E+09 | 0.113366E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172169E+09 | 73133147.71 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170880E+09 | 20306173.33 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167985E+09 | 17652811.23 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179990E+09 | 12240903.68 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211961E+09 | 19126095.00 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226695E+09 | 26821140.32 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333541E+09 | 50156663.87 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351580E+09 | 0.100807E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362102E+09 | 0.133413E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.305429E+10 | 0.827901E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167985E+09 | 12240903.68 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362102E+09 | 0.146428E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359460E+09 | 0.146428E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299476E+09 | 0.114449E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218448E+09 | 0.113366E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172169E+09 | 73133147.71 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.170880E+09 | 20306173.33 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.167985E+09 | 17652811.23 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179990E+09 | 12240903.68 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.211961E+09 | 19126095.00 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.226695E+09 | 26821140.32 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.333541E+09 | 50156663.87 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351580E+09 | 0.100807E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362102E+09 | 0.133413E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.305429E+10 | 0.827901E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.167985E+09 | 12240903.68 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362102E+09 | 0.146428E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.430692E+09 | 0.172886E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.358760E+09 | 0.135260E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261740E+09 | 0.133896E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205834E+09 | 86649577.83 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.203331E+09 | 24249085.26 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.199708E+09 | 21073970.84 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.213995E+09 | 14710553.77 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.252336E+09 | 22848624.22 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.270309E+09 | 31995294.52 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.398299E+09 | 59514768.98 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420477E+09 | 0.119358E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433421E+09 | 0.157621E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.364890E+10 | 0.980064E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.199708E+09 | 14710553.77 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433421E+09 | 0.172886E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360877E+09 | 0.139649E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301164E+09 | 0.107892E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219421E+09 | 0.106122E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172526E+09 | 68719288.95 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169420E+09 | 19742504.38 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165953E+09 | 17689586.87 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177059E+09 | 13031553.22 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208962E+09 | 20644689.77 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224390E+09 | 27884040.39 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.331925E+09 | 50063320.42 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351973E+09 | 97621042.83 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363415E+09 | 0.127329E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304709E+10 | 0.796388E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165953E+09 | 13031553.22 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363415E+09 | 0.139649E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360877E+09 | 0.139649E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301164E+09 | 0.107892E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219421E+09 | 0.106122E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172526E+09 | 68719288.95 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.169420E+09 | 19742504.38 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165953E+09 | 17689586.87 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177059E+09 | 13031553.22 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208962E+09 | 20644689.77 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224390E+09 | 27884040.39 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.331925E+09 | 50063320.42 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351973E+09 | 97621042.83 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363415E+09 | 0.127329E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.304709E+10 | 0.796388E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165953E+09 | 13031553.22 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363415E+09 | 0.139649E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.432387E+09 | 0.164913E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.360776E+09 | 0.127553E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262907E+09 | 0.125379E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.206256E+09 | 81459413.98 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.201574E+09 | 23588300.02 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.197264E+09 | 21121786.91 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.210501E+09 | 15665441.95 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.248741E+09 | 24650748.98 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.267546E+09 | 33258964.06 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.396355E+09 | 59420466.36 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420932E+09 | 0.115611E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.434986E+09 | 0.150464E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.364022E+10 | 0.943086E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.197264E+09 | 15665441.95 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.434986E+09 | 0.164913E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 853.74 | 366.39 | 575.55 | 410.47 | 165.08 | 0.00 | 0.00 |
February | 786.06 | 319.37 | 522.00 | 337.88 | 184.12 | 0.00 | 0.00 |
March | 517.79 | 283.71 | 333.25 | 150.40 | 182.86 | 0.00 | 0.00 |
April | 422.56 | 186.27 | 247.00 | 57.88 | 189.12 | 0.00 | 0.00 |
May | 407.77 | 47.33 | 188.73 | 8.02 | 180.71 | 0.00 | 0.00 |
June | 413.96 | 41.34 | 186.43 | 1.74 | 184.69 | 0.00 | 0.00 |
July | 432.97 | 27.16 | 195.16 | 3.59 | 191.58 | 0.00 | 0.00 |
August | 506.75 | 44.48 | 229.60 | 27.56 | 202.04 | 0.00 | 0.00 |
September | 560.86 | 63.75 | 275.48 | 72.60 | 202.88 | 0.00 | 0.00 |
October | 797.13 | 117.33 | 427.41 | 222.64 | 204.77 | 0.00 | 0.00 |
November | 866.00 | 254.76 | 543.91 | 374.49 | 169.42 | 0.00 | 0.00 |
December | 861.38 | 331.88 | 562.39 | 403.88 | 158.51 | 0.00 | 0.00 |
Annual Sum or Average | 618.12 | 172.86 | 356.37 | 171.74 | 184.63 | 0.00 | 0.00 |
Minimum of Months | 407.77 | 27.16 | 186.43 | 1.74 | 158.51 | 0.00 | 0.00 |
Maximum of Months | 866.00 | 366.39 | 575.55 | 410.47 | 204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 421.56 | 194.11 | 287.78 | 205.24 | 82.54 | 0.00 | 0.00 |
February | 388.84 | 167.70 | 261.00 | 168.94 | 92.06 | 0.00 | 0.00 |
March | 255.71 | 149.51 | 166.63 | 75.20 | 91.43 | 0.00 | 0.00 |
April | 210.15 | 95.63 | 123.50 | 28.94 | 94.56 | 0.00 | 0.00 |
May | 204.41 | 24.37 | 94.36 | 4.01 | 90.35 | 0.00 | 0.00 |
June | 208.08 | 21.08 | 93.22 | 0.87 | 92.35 | 0.00 | 0.00 |
July | 217.94 | 13.71 | 97.58 | 1.79 | 95.79 | 0.00 | 0.00 |
August | 255.09 | 21.91 | 114.80 | 13.78 | 101.02 | 0.00 | 0.00 |
September | 281.50 | 31.66 | 137.74 | 36.30 | 101.44 | 0.00 | 0.00 |
October | 398.88 | 58.93 | 213.71 | 111.32 | 102.39 | 0.00 | 0.00 |
November | 431.25 | 129.72 | 271.95 | 187.24 | 84.71 | 0.00 | 0.00 |
December | 427.49 | 172.84 | 281.19 | 201.94 | 79.26 | 0.00 | 0.00 |
Annual Sum or Average | 308.03 | 89.69 | 178.19 | 85.87 | 92.32 | 0.00 | 0.00 |
Minimum of Months | 204.41 | 13.71 | 93.22 | 0.87 | 79.26 | 0.00 | 0.00 |
Maximum of Months | 431.25 | 194.11 | 287.78 | 205.24 | 102.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 422.38 | 189.91 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 389.24 | 165.31 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 255.70 | 148.47 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.31 | 98.60 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 201.84 | 29.70 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 205.33 | 27.02 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 212.78 | 18.53 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 251.34 | 27.30 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 278.69 | 37.82 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 396.73 | 65.12 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.64 | 132.25 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 427.61 | 171.62 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.40 | 92.24 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 201.84 | 18.53 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.64 | 189.91 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 423.44 | 187.15 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 390.06 | 163.16 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 256.22 | 146.81 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.46 | 98.08 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 201.76 | 30.05 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 205.20 | 27.52 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 212.52 | 19.10 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 251.18 | 27.86 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 278.53 | 38.32 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 396.67 | 65.49 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.88 | 131.58 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 428.20 | 169.83 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.61 | 91.69 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 201.76 | 19.10 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.88 | 187.15 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.81 | 184.22 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 391.28 | 160.62 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 257.18 | 144.46 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.01 | 96.62 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 202.20 | 29.01 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 205.62 | 26.51 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 212.99 | 18.26 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 251.57 | 26.91 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 278.86 | 37.36 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 397.00 | 64.43 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.47 | 130.13 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 429.10 | 167.57 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.27 | 90.13 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 202.20 | 18.26 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.47 | 184.22 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 856.29 | 355.98 | 574.37 | 409.63 | 164.75 | 0.00 | 0.00 |
February | 789.01 | 309.75 | 520.92 | 337.19 | 183.74 | 0.00 | 0.00 |
March | 519.46 | 277.44 | 332.57 | 150.09 | 182.48 | 0.00 | 0.00 |
April | 422.80 | 185.39 | 246.50 | 57.76 | 188.74 | 0.00 | 0.00 |
May | 404.75 | 51.89 | 188.34 | 8.00 | 180.34 | 0.00 | 0.00 |
June | 410.96 | 46.63 | 186.05 | 1.73 | 184.31 | 0.00 | 0.00 |
July | 426.09 | 31.69 | 194.76 | 3.58 | 191.18 | 0.00 | 0.00 |
August | 503.31 | 48.23 | 229.13 | 27.50 | 201.63 | 0.00 | 0.00 |
September | 557.46 | 69.14 | 274.92 | 72.45 | 202.46 | 0.00 | 0.00 |
October | 795.04 | 122.89 | 426.53 | 222.18 | 204.35 | 0.00 | 0.00 |
November | 865.98 | 252.68 | 542.79 | 373.72 | 169.07 | 0.00 | 0.00 |
December | 862.78 | 324.56 | 561.23 | 403.05 | 158.19 | 0.00 | 0.00 |
Annual Sum or Average | 617.01 | 172.28 | 355.64 | 171.39 | 184.25 | 0.00 | 0.00 |
Minimum of Months | 404.75 | 31.69 | 186.05 | 1.73 | 158.19 | 0.00 | 0.00 |
Maximum of Months | 865.98 | 355.98 | 574.37 | 409.63 | 204.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 427.57 | 177.30 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 394.04 | 154.12 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 259.46 | 138.04 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.42 | 91.89 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 203.19 | 24.86 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 206.48 | 22.21 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 214.26 | 14.83 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 252.56 | 22.92 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 279.22 | 33.30 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 397.58 | 60.30 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.59 | 125.59 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 430.85 | 161.60 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 308.70 | 85.21 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 203.19 | 14.83 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.59 | 177.30 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 428.10 | 176.31 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 394.61 | 153.11 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 259.90 | 137.12 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.69 | 91.35 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 203.41 | 24.58 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 206.69 | 21.96 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 214.48 | 14.64 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 252.73 | 22.70 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 279.37 | 33.05 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 397.76 | 59.98 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.89 | 125.06 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 431.27 | 160.71 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 309.00 | 84.68 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 203.41 | 14.64 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.89 | 176.31 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 429.22 | 173.89 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 395.88 | 150.53 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 260.84 | 134.64 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.26 | 89.86 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 203.51 | 24.22 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 206.67 | 21.75 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 214.30 | 14.63 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 252.49 | 22.81 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 279.21 | 33.04 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 397.77 | 59.67 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.50 | 123.83 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 432.21 | 158.47 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 309.41 | 83.58 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 203.51 | 14.63 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.50 | 173.89 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 430.91 | 165.85 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 398.11 | 141.92 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 262.00 | 126.05 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.70 | 84.45 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 201.77 | 23.55 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 204.15 | 21.80 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 210.80 | 15.58 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 248.90 | 24.62 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 276.36 | 34.35 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 395.84 | 59.57 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.98 | 119.93 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 433.77 | 151.25 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 308.68 | 80.41 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 201.77 | 15.58 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.98 | 165.85 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228666E+10 | 0.981345E+09 | 0.154157E+10 | 0.109940E+10 | 0.442162E+09 | 0.00 | 0.00 |
February | 0.190163E+10 | 0.772619E+09 | 0.126281E+10 | 0.817396E+09 | 0.445415E+09 | 0.00 | 0.00 |
March | 0.138684E+10 | 0.759889E+09 | 0.892585E+09 | 0.402825E+09 | 0.489760E+09 | 0.00 | 0.00 |
April | 0.109528E+10 | 0.482809E+09 | 0.640232E+09 | 0.150022E+09 | 0.490210E+09 | 0.00 | 0.00 |
May | 0.109216E+10 | 0.126775E+09 | 0.505490E+09 | 21482596.50 | 0.484007E+09 | 0.00 | 0.00 |
June | 0.107299E+10 | 0.107153E+09 | 0.483230E+09 | 4504165.10 | 0.478725E+09 | 0.00 | 0.00 |
July | 0.115968E+10 | 72756443.96 | 0.522725E+09 | 9607631.05 | 0.513117E+09 | 0.00 | 0.00 |
August | 0.135728E+10 | 0.119133E+09 | 0.614958E+09 | 73813531.21 | 0.541145E+09 | 0.00 | 0.00 |
September | 0.145375E+10 | 0.165230E+09 | 0.714045E+09 | 0.188181E+09 | 0.525864E+09 | 0.00 | 0.00 |
October | 0.213504E+10 | 0.314252E+09 | 0.114478E+10 | 0.596320E+09 | 0.548456E+09 | 0.00 | 0.00 |
November | 0.224468E+10 | 0.660328E+09 | 0.140981E+10 | 0.970667E+09 | 0.439140E+09 | 0.00 | 0.00 |
December | 0.230711E+10 | 0.888898E+09 | 0.150630E+10 | 0.108174E+10 | 0.424555E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194931E+11 | 0.545119E+10 | 0.112385E+11 | 0.541597E+10 | 0.582256E+10 | 0.00 | 0.00 |
Minimum of Months | 0.107299E+10 | 72756443.96 | 0.483230E+09 | 4504165.10 | 0.424555E+09 | 0.00 | 0.00 |
Maximum of Months | 0.230711E+10 | 0.981345E+09 | 0.154157E+10 | 0.109940E+10 | 0.548456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112911E+10 | 0.519904E+09 | 0.770783E+09 | 0.549702E+09 | 0.221081E+09 | 0.00 | 0.00 |
February | 0.940684E+09 | 0.405698E+09 | 0.631406E+09 | 0.408698E+09 | 0.222707E+09 | 0.00 | 0.00 |
March | 0.684882E+09 | 0.400442E+09 | 0.446293E+09 | 0.201412E+09 | 0.244880E+09 | 0.00 | 0.00 |
April | 0.544714E+09 | 0.247863E+09 | 0.320116E+09 | 75011096.64 | 0.245105E+09 | 0.00 | 0.00 |
May | 0.547504E+09 | 65269684.50 | 0.252745E+09 | 10741298.25 | 0.242003E+09 | 0.00 | 0.00 |
June | 0.539338E+09 | 54652060.05 | 0.241615E+09 | 2252082.55 | 0.239363E+09 | 0.00 | 0.00 |
July | 0.583729E+09 | 36726989.97 | 0.261363E+09 | 4803815.53 | 0.256559E+09 | 0.00 | 0.00 |
August | 0.683222E+09 | 58696814.31 | 0.307479E+09 | 36906765.60 | 0.270572E+09 | 0.00 | 0.00 |
September | 0.729661E+09 | 82065140.18 | 0.357023E+09 | 94090626.76 | 0.262932E+09 | 0.00 | 0.00 |
October | 0.106837E+10 | 0.157835E+09 | 0.572388E+09 | 0.298160E+09 | 0.274228E+09 | 0.00 | 0.00 |
November | 0.111780E+10 | 0.336242E+09 | 0.704904E+09 | 0.485334E+09 | 0.219570E+09 | 0.00 | 0.00 |
December | 0.114498E+10 | 0.462931E+09 | 0.753148E+09 | 0.540871E+09 | 0.212277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971399E+10 | 0.282833E+10 | 0.561926E+10 | 0.270798E+10 | 0.291128E+10 | 0.00 | 0.00 |
Minimum of Months | 0.539338E+09 | 36726989.97 | 0.241615E+09 | 2252082.55 | 0.212277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114498E+10 | 0.519904E+09 | 0.770783E+09 | 0.549702E+09 | 0.274228E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113131E+10 | 0.508644E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.941645E+09 | 0.399907E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.684870E+09 | 0.397657E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.542537E+09 | 0.255563E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.540609E+09 | 79548275.21 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.532227E+09 | 70047881.24 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.569905E+09 | 49631436.98 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.673184E+09 | 73107588.58 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.722372E+09 | 98021390.79 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106260E+10 | 0.174412E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111622E+10 | 0.342800E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114531E+10 | 0.459674E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966278E+10 | 0.290901E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.532227E+09 | 49631436.98 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114531E+10 | 0.508644E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113414E+10 | 0.501266E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.943632E+09 | 0.394713E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.686270E+09 | 0.393206E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.542925E+09 | 0.254219E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.540393E+09 | 80486259.84 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.531881E+09 | 71322048.27 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.569208E+09 | 51162261.46 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.672754E+09 | 74623795.17 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.721962E+09 | 99321048.93 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106243E+10 | 0.175403E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111683E+10 | 0.341051E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114690E+10 | 0.454875E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966932E+10 | 0.289165E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.531881E+09 | 51162261.46 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114690E+10 | 0.501266E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113780E+10 | 0.493425E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.946585E+09 | 0.388579E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.688836E+09 | 0.386930E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.544340E+09 | 0.250445E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.541561E+09 | 77706635.84 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.532966E+09 | 68713887.24 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.570462E+09 | 48895203.41 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.673807E+09 | 72073715.88 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.722813E+09 | 96849368.86 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106332E+10 | 0.172580E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111836E+10 | 0.337299E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114930E+10 | 0.448828E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.969015E+10 | 0.284232E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.532966E+09 | 48895203.41 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114930E+10 | 0.493425E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229350E+10 | 0.953466E+09 | 0.153840E+10 | 0.109715E+10 | 0.441255E+09 | 0.00 | 0.00 |
February | 0.190877E+10 | 0.749348E+09 | 0.126022E+10 | 0.815720E+09 | 0.444501E+09 | 0.00 | 0.00 |
March | 0.139131E+10 | 0.743105E+09 | 0.890754E+09 | 0.401998E+09 | 0.488756E+09 | 0.00 | 0.00 |
April | 0.109589E+10 | 0.480523E+09 | 0.638919E+09 | 0.149714E+09 | 0.489204E+09 | 0.00 | 0.00 |
May | 0.108409E+10 | 0.138987E+09 | 0.504453E+09 | 21438525.43 | 0.483014E+09 | 0.00 | 0.00 |
June | 0.106522E+10 | 0.120878E+09 | 0.482238E+09 | 4494924.91 | 0.477743E+09 | 0.00 | 0.00 |
July | 0.114123E+10 | 84889896.40 | 0.521653E+09 | 9587921.21 | 0.512065E+09 | 0.00 | 0.00 |
August | 0.134807E+10 | 0.129175E+09 | 0.613697E+09 | 73662104.40 | 0.540035E+09 | 0.00 | 0.00 |
September | 0.144495E+10 | 0.179222E+09 | 0.712581E+09 | 0.187795E+09 | 0.524785E+09 | 0.00 | 0.00 |
October | 0.212944E+10 | 0.329157E+09 | 0.114243E+10 | 0.595097E+09 | 0.547331E+09 | 0.00 | 0.00 |
November | 0.224462E+10 | 0.654948E+09 | 0.140692E+10 | 0.968676E+09 | 0.438239E+09 | 0.00 | 0.00 |
December | 0.231086E+10 | 0.869301E+09 | 0.150321E+10 | 0.107952E+10 | 0.423684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194579E+11 | 0.543300E+10 | 0.112155E+11 | 0.540485E+10 | 0.581061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106522E+10 | 84889896.40 | 0.482238E+09 | 4494924.91 | 0.423684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231086E+10 | 0.953466E+09 | 0.153840E+10 | 0.109715E+10 | 0.547331E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114520E+10 | 0.474889E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.953257E+09 | 0.372842E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.694931E+09 | 0.369725E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.547992E+09 | 0.238187E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.544220E+09 | 66592798.30 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.535198E+09 | 57575694.22 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.573878E+09 | 39727221.45 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.676444E+09 | 61385126.59 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.723733E+09 | 86308229.34 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106489E+10 | 0.161506E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112128E+10 | 0.325522E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115400E+10 | 0.432828E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973502E+10 | 0.268709E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.535198E+09 | 39727221.45 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115400E+10 | 0.474889E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114662E+10 | 0.472225E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.954629E+09 | 0.370415E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.696106E+09 | 0.367267E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.548704E+09 | 0.236786E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.544813E+09 | 65841371.57 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.535740E+09 | 56917097.43 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.574472E+09 | 39200498.24 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.676914E+09 | 60809717.08 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.724128E+09 | 85658199.28 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106535E+10 | 0.160641E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112206E+10 | 0.324149E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115512E+10 | 0.430436E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.974466E+10 | 0.267034E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.535740E+09 | 39200498.24 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115512E+10 | 0.472225E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114961E+10 | 0.465741E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.957711E+09 | 0.364158E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.698636E+09 | 0.360629E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.550172E+09 | 0.232915E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.545092E+09 | 64860985.82 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.535678E+09 | 56379393.75 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.573975E+09 | 39191423.45 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.676257E+09 | 61100219.65 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.723700E+09 | 85637295.58 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106538E+10 | 0.159827E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112364E+10 | 0.320972E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115762E+10 | 0.424447E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975747E+10 | 0.263586E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.535678E+09 | 39191423.45 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115762E+10 | 0.465741E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115414E+10 | 0.444211E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.963104E+09 | 0.343337E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.701748E+09 | 0.337622E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.551308E+09 | 0.218898E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.540414E+09 | 63072998.47 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.529169E+09 | 56500651.75 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.564618E+09 | 41727857.36 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.666664E+09 | 65939440.44 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.716327E+09 | 89026891.38 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.106021E+10 | 0.159547E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112488E+10 | 0.310853E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.116182E+10 | 0.405121E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973439E+10 | 0.253586E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529169E+09 | 41727857.36 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116182E+10 | 0.444211E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.306611E+09 | -189184728.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117425952.2 | 58.99 | 0.00 | 0.00 |
February | 0.275101E+09 | -170373687.4 | 0.00 | 0.00 | 672.00 | 0.00 | -104727561.4 | 58.99 | 0.00 | 0.00 |
March | 0.299878E+09 | -184437507.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115440607.9 | 58.99 | 0.00 | 0.00 |
April | 0.274681E+09 | -165331193.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109349334.9 | 58.99 | 0.00 | 0.00 |
May | 0.270875E+09 | -158997239.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111877590.2 | 58.99 | 0.00 | 0.00 |
June | 0.253963E+09 | -145807446.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108155768.2 | 58.99 | 0.00 | 0.00 |
July | 0.254330E+09 | -142829663.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111499945.0 | 58.99 | 0.00 | 0.00 |
August | 0.258866E+09 | -147431931.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111434517.0 | 58.99 | 0.00 | 0.00 |
September | 0.256282E+09 | -148321060.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107961388.6 | 58.99 | 0.00 | 0.00 |
October | 0.274922E+09 | -163011817.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111910437.2 | 58.99 | 0.00 | 0.00 |
November | 0.278341E+09 | -168883335.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109457194.6 | 58.99 | 0.00 | 0.00 |
December | 0.300288E+09 | -184812819.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115475551.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.330414E+10 | -0.196942E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133472E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.253963E+09 | -189184728.4 | 0.00 | 0.00 | 672.00 | 0.00 | -117425952.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.306611E+09 | -142829663.5 | 0.00 | 0.00 | 744.00 | 0.00 | -104727561.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304574E+09 | -189190724.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115382829.7 | 58.99 | 0.00 | 0.00 |
February | 0.273827E+09 | -170364362.1 | 0.00 | 0.00 | 672.00 | 0.00 | -103462652.3 | 58.99 | 0.00 | 0.00 |
March | 0.298633E+09 | -184432850.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114200620.2 | 58.99 | 0.00 | 0.00 |
April | 0.274325E+09 | -165330256.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108994844.5 | 58.99 | 0.00 | 0.00 |
May | 0.270707E+09 | -158990455.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111716588.3 | 58.99 | 0.00 | 0.00 |
June | 0.253834E+09 | -145807726.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108026326.6 | 58.99 | 0.00 | 0.00 |
July | 0.254250E+09 | -142829159.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111420683.0 | 58.99 | 0.00 | 0.00 |
August | 0.258833E+09 | -147432277.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111400593.6 | 58.99 | 0.00 | 0.00 |
September | 0.256229E+09 | -148332133.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107897229.3 | 58.99 | 0.00 | 0.00 |
October | 0.274795E+09 | -163005316.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111790119.3 | 58.99 | 0.00 | 0.00 |
November | 0.277918E+09 | -168887390.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109030907.4 | 58.99 | 0.00 | 0.00 |
December | 0.299079E+09 | -184820161.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114259291.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.329701E+10 | -0.196942E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132758E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.253834E+09 | -189190724.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115382829.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.304574E+09 | -142829159.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103462652.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282554E+09 | -166361550.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116192678.7 | 58.99 | 0.00 | 0.00 |
February | 0.253759E+09 | -149934146.5 | 0.00 | 0.00 | 672.00 | 0.00 | -103825160.5 | 59.00 | 0.00 | 0.00 |
March | 0.278862E+09 | -164589975.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114272376.5 | 58.99 | 0.00 | 0.00 |
April | 0.253552E+09 | -145393848.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108158270.2 | 59.00 | 0.00 | 0.00 |
May | 0.251056E+09 | -141033918.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110022461.3 | 58.99 | 0.00 | 0.00 |
June | 0.236102E+09 | -129853647.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106247990.9 | 58.99 | 0.00 | 0.00 |
July | 0.234228E+09 | -124866769.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109361031.8 | 58.99 | 0.00 | 0.00 |
August | 0.241196E+09 | -131700371.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109495913.6 | 58.99 | 0.00 | 0.00 |
September | 0.236499E+09 | -130369840.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106128991.3 | 58.99 | 0.00 | 0.00 |
October | 0.253490E+09 | -143397160.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110092889.8 | 58.98 | 0.00 | 0.00 |
November | 0.257517E+09 | -149103434.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108413674.0 | 58.99 | 0.00 | 0.00 |
December | 0.275746E+09 | -161317395.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114428161.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305456E+10 | -0.173792E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131664E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234228E+09 | -166361550.3 | 0.00 | 0.00 | 672.00 | 0.00 | -116192678.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282554E+09 | -124866769.4 | 0.00 | 0.00 | 744.00 | 0.00 | -103825160.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282967E+09 | -166345711.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116621003.5 | 59.00 | 0.00 | 0.00 |
February | 0.254044E+09 | -149961513.8 | 0.00 | 0.00 | 672.00 | 0.00 | -104082309.6 | 58.99 | 0.00 | 0.00 |
March | 0.279086E+09 | -164588664.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114497649.9 | 58.99 | 0.00 | 0.00 |
April | 0.253615E+09 | -145420711.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108194768.2 | 58.99 | 0.00 | 0.00 |
May | 0.251006E+09 | -141029188.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109977096.9 | 58.99 | 0.00 | 0.00 |
June | 0.236016E+09 | -129843408.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106172827.9 | 58.99 | 0.00 | 0.00 |
July | 0.234136E+09 | -124881716.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109254334.2 | 58.99 | 0.00 | 0.00 |
August | 0.241118E+09 | -131683279.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109434821.5 | 58.99 | 0.00 | 0.00 |
September | 0.236419E+09 | -130382391.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106036616.4 | 58.99 | 0.00 | 0.00 |
October | 0.253440E+09 | -143340665.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110099217.8 | 59.00 | 0.00 | 0.00 |
November | 0.257608E+09 | -149115392.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108492750.7 | 58.99 | 0.00 | 0.00 |
December | 0.276004E+09 | -161316804.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114687265.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305546E+10 | -0.173791E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131755E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234136E+09 | -166345711.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116621003.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.282967E+09 | -124881716.0 | 0.00 | 0.00 | 744.00 | 0.00 | -104082309.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275247E+09 | -157238050.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118009439.4 | 58.99 | 0.00 | 0.00 |
February | 0.247068E+09 | -141792006.1 | 0.00 | 0.00 | 672.00 | 0.00 | -105276367.7 | 59.00 | 0.00 | 0.00 |
March | 0.271412E+09 | -155731241.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115680689.0 | 58.99 | 0.00 | 0.00 |
April | 0.246569E+09 | -137610124.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108959223.8 | 58.99 | 0.00 | 0.00 |
May | 0.243995E+09 | -133377122.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110618138.9 | 58.99 | 0.00 | 0.00 |
June | 0.229702E+09 | -122880532.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106821727.3 | 58.99 | 0.00 | 0.00 |
July | 0.227926E+09 | -118105051.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109820910.2 | 58.99 | 0.00 | 0.00 |
August | 0.234666E+09 | -124606350.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110059816.8 | 58.99 | 0.00 | 0.00 |
September | 0.229896E+09 | -123372671.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106523595.8 | 58.99 | 0.00 | 0.00 |
October | 0.246167E+09 | -135516015.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110650537.4 | 58.99 | 0.00 | 0.00 |
November | 0.250042E+09 | -140818517.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109223971.8 | 58.99 | 0.00 | 0.00 |
December | 0.268319E+09 | -152574331.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115744971.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297101E+10 | -0.164362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132739E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.227926E+09 | -157238050.4 | 0.00 | 0.00 | 672.00 | 0.00 | -118009439.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275247E+09 | -118105051.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105276367.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275398E+09 | -157242647.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118155435.3 | 58.99 | 0.00 | 0.00 |
February | 0.247183E+09 | -141791911.9 | 0.00 | 0.00 | 672.00 | 0.00 | -105391009.6 | 58.99 | 0.00 | 0.00 |
March | 0.271517E+09 | -155744989.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115771852.4 | 58.99 | 0.00 | 0.00 |
April | 0.246650E+09 | -137580845.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109069598.4 | 59.00 | 0.00 | 0.00 |
May | 0.244105E+09 | -133384044.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110721303.6 | 58.99 | 0.00 | 0.00 |
June | 0.229817E+09 | -122865310.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106951665.4 | 58.99 | 0.00 | 0.00 |
July | 0.228054E+09 | -118094742.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109958759.5 | 58.99 | 0.00 | 0.00 |
August | 0.234795E+09 | -124594161.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110201170.1 | 58.99 | 0.00 | 0.00 |
September | 0.230024E+09 | -123383155.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106640712.6 | 58.99 | 0.00 | 0.00 |
October | 0.246275E+09 | -135527082.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110747797.2 | 58.99 | 0.00 | 0.00 |
November | 0.250130E+09 | -140834066.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109295447.8 | 58.99 | 0.00 | 0.00 |
December | 0.268432E+09 | -152573173.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115858849.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297238E+10 | -0.164362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132876E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228054E+09 | -157242647.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118155435.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275398E+09 | -118094742.3 | 0.00 | 0.00 | 744.00 | 0.00 | -105391009.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275554E+09 | -157239061.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118314683.3 | 58.99 | 0.00 | 0.00 |
February | 0.247322E+09 | -141806035.9 | 0.00 | 0.00 | 672.00 | 0.00 | -105516453.4 | 58.99 | 0.00 | 0.00 |
March | 0.271656E+09 | -155751475.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115904061.5 | 58.99 | 0.00 | 0.00 |
April | 0.246703E+09 | -137624672.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109078384.2 | 58.98 | 0.00 | 0.00 |
May | 0.244157E+09 | -133376433.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110780976.2 | 58.99 | 0.00 | 0.00 |
June | 0.229853E+09 | -122873745.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106979268.6 | 58.99 | 0.00 | 0.00 |
July | 0.228095E+09 | -118107018.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109987940.3 | 58.99 | 0.00 | 0.00 |
August | 0.234829E+09 | -124624019.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110204621.4 | 58.99 | 0.00 | 0.00 |
September | 0.230057E+09 | -123370562.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106686377.7 | 58.99 | 0.00 | 0.00 |
October | 0.246318E+09 | -135509065.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110808885.1 | 58.99 | 0.00 | 0.00 |
November | 0.250194E+09 | -140831802.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109362329.5 | 58.99 | 0.00 | 0.00 |
December | 0.268572E+09 | -152565827.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116006518.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297331E+10 | -0.164368E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132963E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228095E+09 | -157239061.9 | 0.00 | 0.00 | 672.00 | 0.00 | -118314683.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275554E+09 | -118107018.2 | 0.00 | 0.00 | 744.00 | 0.00 | -105516453.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.514667E+09 | 58873.29 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716552E+09 | 58873.29 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473154E+09 | 51913.45 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511631E+09 | 58873.29 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.716552E+09 | 58873.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 40588746.77 | 2984.36 | 10-JAN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125221E+09 | 13843.79 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109838E+09 | 5117.36 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101631E+09 | 15073.38 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125221E+09 | 15073.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156313E+09 | 7733.80 | 05-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220179E+09 | 23080.26 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163281E+09 | 14354.89 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173168E+09 | 7156.84 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220179E+09 | 23080.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196586E+09 | 6986.93 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248849E+09 | 27006.75 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180824E+09 | 18636.60 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193404E+09 | 8662.08 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248849E+09 | 27006.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260264E+09 | 9643.09 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293516E+09 | 30764.93 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211970E+09 | 22581.69 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234822E+09 | 10537.24 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.293516E+09 | 30764.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.624349E+09 | 55082.67 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.621440E+09 | 55082.67 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436743E+09 | 55082.67 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543125E+09 | 55082.67 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.624349E+09 | 55082.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342474E+09 | 28679.12 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342970E+09 | 28679.12 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238946E+09 | 28679.12 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299835E+09 | 28679.12 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342970E+09 | 28679.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372968E+09 | 28571.10 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362727E+09 | 28571.10 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252711E+09 | 28571.10 | 12-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318954E+09 | 28571.10 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372968E+09 | 28571.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.463114E+09 | 28642.53 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421852E+09 | 28642.53 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304124E+09 | 28642.53 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375736E+09 | 28642.53 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.463114E+09 | 28642.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.713694E+09 | 32253.14 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.600013E+09 | 32253.14 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486326E+09 | 32253.14 | 09-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 424671.25 | 766.02 | 16-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.560874E+09 | 32253.14 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.713694E+09 | 32253.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.473751E+10 | 0.298421E+10 | 22223.74 | 19-JAN-15:00 | 12890.16 | 0.00 |
February | 0.00 | 0.00 | 0.612500E+10 | 0.384964E+10 | 23059.10 | 24-FEB-14:00 | 14646.23 | 0.00 |
March | 0.00 | 0.00 | 0.904135E+10 | 0.586679E+10 | 25716.01 | 07-MAR-08:63 | 12114.41 | 0.00 |
April | 0.00 | 0.00 | 0.167677E+11 | 0.109912E+11 | 60226.31 | 29-APR-07:03 | 33038.85 | 0.00 |
May | 0.00 | 0.00 | 0.373058E+11 | 0.227152E+11 | 61497.22 | 24-MAY-07:02 | 31271.32 | 0.00 |
June | 0.00 | 0.00 | 0.397598E+11 | 0.240048E+11 | 60787.82 | 19-JUN-07:02 | 32654.59 | 0.00 |
July | 0.00 | 0.00 | 0.452241E+11 | 0.253492E+11 | 61806.93 | 02-JUL-07:02 | 31206.18 | 0.00 |
August | 0.00 | 0.00 | 0.446404E+11 | 0.259144E+11 | 61517.04 | 10-AUG-07:02 | 32526.18 | 0.00 |
September | 0.00 | 0.00 | 0.396392E+11 | 0.223518E+11 | 62361.57 | 05-SEP-07:02 | 29875.19 | 0.00 |
October | 0.00 | 0.00 | 0.337396E+11 | 0.204688E+11 | 61701.38 | 25-OCT-07:02 | 32555.76 | 0.00 |
November | 0.00 | 0.00 | 0.133344E+11 | 0.839660E+10 | 59994.97 | 02-NOV-07:02 | 36198.34 | 0.00 |
December | 0.00 | 0.00 | 0.860120E+10 | 0.538104E+10 | 59027.82 | 15-DEC-08:62 | 34367.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.298916E+12 | 0.178274E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.473751E+10 | 0.298421E+10 | 22223.74 | 12114.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.452241E+11 | 0.259144E+11 | 62361.57 | 36198.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.294724E+10 | 0.192255E+10 | 30383.42 | 01-JAN-18:02 | 16467.80 | 0.00 |
February | 0.00 | 0.00 | 0.386132E+10 | 0.249123E+10 | 30708.85 | 28-FEB-21:20 | 14716.33 | 0.00 |
March | 0.00 | 0.00 | 0.543208E+10 | 0.365412E+10 | 30433.22 | 07-MAR-21:02 | 15325.90 | 0.00 |
April | 0.00 | 0.00 | 0.951175E+10 | 0.646673E+10 | 30895.54 | 30-APR-07:02 | 21349.80 | 0.00 |
May | 0.00 | 0.00 | 0.188908E+11 | 0.119541E+11 | 31235.18 | 22-MAY-07:02 | 20251.33 | 0.00 |
June | 0.00 | 0.00 | 0.199036E+11 | 0.124533E+11 | 30542.50 | 05-JUN-07:02 | 22242.93 | 0.00 |
July | 0.00 | 0.00 | 0.223775E+11 | 0.130494E+11 | 31254.67 | 03-JUL-07:02 | 20863.23 | 0.00 |
August | 0.00 | 0.00 | 0.220468E+11 | 0.132371E+11 | 31453.52 | 16-AUG-07:02 | 19853.74 | 0.00 |
September | 0.00 | 0.00 | 0.197210E+11 | 0.115554E+11 | 31742.23 | 05-SEP-07:02 | 19479.86 | 0.00 |
October | 0.00 | 0.00 | 0.171619E+11 | 0.108188E+11 | 31349.78 | 08-OCT-07:01 | 20962.08 | 0.00 |
November | 0.00 | 0.00 | 0.749222E+10 | 0.488968E+10 | 30712.13 | 29-NOV-21:02 | 14924.63 | 0.00 |
December | 0.00 | 0.00 | 0.478099E+10 | 0.311594E+10 | 30214.76 | 08-DEC-21:55 | 15898.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154127E+12 | 0.956083E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.294724E+10 | 0.192255E+10 | 30214.76 | 14716.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223775E+11 | 0.132371E+11 | 31742.23 | 22242.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213007E+10 | 0.137173E+10 | 13899.10 | 20-JAN-07:03 | 6241.63 | 0.00 |
February | 0.00 | 0.00 | 0.292858E+10 | 0.186403E+10 | 14896.43 | 28-FEB-07:03 | 7309.43 | 0.00 |
March | 0.00 | 0.00 | 0.408136E+10 | 0.268658E+10 | 19205.49 | 07-MAR-07:03 | 10748.04 | 0.00 |
April | 0.00 | 0.00 | 0.719993E+10 | 0.481428E+10 | 32213.34 | 29-APR-06:03 | 17731.27 | 0.00 |
May | 0.00 | 0.00 | 0.154537E+11 | 0.948677E+10 | 33004.38 | 21-MAY-07:02 | 15643.90 | 0.00 |
June | 0.00 | 0.00 | 0.165214E+11 | 0.100070E+11 | 33487.28 | 19-JUN-06:02 | 14390.37 | 0.00 |
July | 0.00 | 0.00 | 0.183523E+11 | 0.102783E+11 | 33586.88 | 03-JUL-06:01 | 14637.23 | 0.00 |
August | 0.00 | 0.00 | 0.184574E+11 | 0.106767E+11 | 33576.23 | 14-AUG-06:03 | 13994.53 | 0.00 |
September | 0.00 | 0.00 | 0.160452E+11 | 0.899634E+10 | 33624.04 | 05-SEP-06:01 | 14599.20 | 0.00 |
October | 0.00 | 0.00 | 0.137166E+11 | 0.834136E+10 | 33462.23 | 08-OCT-07:01 | 15385.51 | 0.00 |
November | 0.00 | 0.00 | 0.582739E+10 | 0.373330E+10 | 32282.36 | 02-NOV-06:02 | 17870.32 | 0.00 |
December | 0.00 | 0.00 | 0.374362E+10 | 0.237334E+10 | 31911.03 | 12-DEC-07:03 | 18474.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124458E+12 | 0.746297E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.213007E+10 | 0.137173E+10 | 13899.10 | 6241.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184574E+11 | 0.106767E+11 | 33624.04 | 18474.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206310E+10 | 0.132384E+10 | 13307.48 | 20-JAN-07:03 | 5971.10 | 0.00 |
February | 0.00 | 0.00 | 0.285890E+10 | 0.181529E+10 | 14178.66 | 28-FEB-07:03 | 6951.42 | 0.00 |
March | 0.00 | 0.00 | 0.401633E+10 | 0.263719E+10 | 18363.26 | 07-MAR-07:03 | 10226.15 | 0.00 |
April | 0.00 | 0.00 | 0.715626E+10 | 0.478064E+10 | 32308.06 | 29-APR-06:03 | 17777.45 | 0.00 |
May | 0.00 | 0.00 | 0.154795E+11 | 0.950603E+10 | 33100.21 | 21-MAY-07:02 | 15691.41 | 0.00 |
June | 0.00 | 0.00 | 0.165639E+11 | 0.100387E+11 | 33590.50 | 19-JUN-06:02 | 14478.61 | 0.00 |
July | 0.00 | 0.00 | 0.184185E+11 | 0.103261E+11 | 33683.81 | 03-JUL-06:01 | 14755.03 | 0.00 |
August | 0.00 | 0.00 | 0.185117E+11 | 0.107165E+11 | 33673.14 | 14-AUG-06:01 | 14218.34 | 0.00 |
September | 0.00 | 0.00 | 0.160935E+11 | 0.903114E+10 | 33721.09 | 05-SEP-06:01 | 14726.47 | 0.00 |
October | 0.00 | 0.00 | 0.137452E+11 | 0.836251E+10 | 33567.68 | 08-OCT-07:01 | 15489.99 | 0.00 |
November | 0.00 | 0.00 | 0.577399E+10 | 0.369313E+10 | 32377.47 | 02-NOV-06:02 | 17909.00 | 0.00 |
December | 0.00 | 0.00 | 0.369832E+10 | 0.233957E+10 | 32004.24 | 12-DEC-07:03 | 18503.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124379E+12 | 0.745706E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.206310E+10 | 0.132384E+10 | 13307.48 | 5971.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.185117E+11 | 0.107165E+11 | 33721.09 | 18503.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192697E+10 | 0.122956E+10 | 11128.18 | 19-JAN-14:00 | 6434.92 | 0.00 |
February | 0.00 | 0.00 | 0.270631E+10 | 0.171063E+10 | 11591.51 | 28-FEB-07:03 | 5663.91 | 0.00 |
March | 0.00 | 0.00 | 0.382140E+10 | 0.249544E+10 | 15521.61 | 07-MAR-07:03 | 8506.95 | 0.00 |
April | 0.00 | 0.00 | 0.689906E+10 | 0.459645E+10 | 32046.48 | 29-APR-06:03 | 17461.64 | 0.00 |
May | 0.00 | 0.00 | 0.152213E+11 | 0.931830E+10 | 32820.86 | 21-MAY-07:02 | 15412.79 | 0.00 |
June | 0.00 | 0.00 | 0.163193E+11 | 0.985865E+10 | 33313.69 | 19-JUN-06:02 | 14235.38 | 0.00 |
July | 0.00 | 0.00 | 0.181761E+11 | 0.101540E+11 | 33419.40 | 03-JUL-06:01 | 14523.42 | 0.00 |
August | 0.00 | 0.00 | 0.182646E+11 | 0.105379E+11 | 33408.80 | 14-AUG-06:01 | 13988.71 | 0.00 |
September | 0.00 | 0.00 | 0.158589E+11 | 0.886605E+10 | 33456.37 | 05-SEP-06:01 | 14534.64 | 0.00 |
October | 0.00 | 0.00 | 0.135278E+11 | 0.820140E+10 | 33291.81 | 08-OCT-07:01 | 15261.17 | 0.00 |
November | 0.00 | 0.00 | 0.557102E+10 | 0.354321E+10 | 32112.55 | 02-NOV-06:02 | 17586.86 | 0.00 |
December | 0.00 | 0.00 | 0.356524E+10 | 0.224317E+10 | 31708.40 | 15-DEC-07:03 | 18472.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121858E+12 | 0.727548E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.192697E+10 | 0.122956E+10 | 11128.18 | 5663.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182646E+11 | 0.105379E+11 | 33456.37 | 18472.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.311468E+10 | 0.194282E+10 | 20420.15 | 19-JAN-14:00 | 11476.91 | 0.00 |
February | 0.00 | 0.00 | 0.455547E+10 | 0.281134E+10 | 21186.63 | 24-FEB-13:50 | 13217.94 | 0.00 |
March | 0.00 | 0.00 | 0.647606E+10 | 0.413433E+10 | 23476.38 | 30-MAR-13:00 | 14223.93 | 0.00 |
April | 0.00 | 0.00 | 0.120444E+11 | 0.788713E+10 | 55653.09 | 29-APR-07:03 | 31821.19 | 0.00 |
May | 0.00 | 0.00 | 0.270145E+11 | 0.162980E+11 | 57798.94 | 21-MAY-08:62 | 26670.24 | 0.00 |
June | 0.00 | 0.00 | 0.291795E+11 | 0.173827E+11 | 58467.15 | 19-JUN-07:02 | 24756.45 | 0.00 |
July | 0.00 | 0.00 | 0.323142E+11 | 0.177657E+11 | 58803.69 | 03-JUL-07:02 | 25274.45 | 0.00 |
August | 0.00 | 0.00 | 0.326906E+11 | 0.185945E+11 | 58718.85 | 14-AUG-07:01 | 24423.07 | 0.00 |
September | 0.00 | 0.00 | 0.280724E+11 | 0.153792E+11 | 58815.35 | 05-SEP-07:02 | 25347.88 | 0.00 |
October | 0.00 | 0.00 | 0.242235E+11 | 0.144549E+11 | 58523.69 | 08-OCT-08:62 | 26355.26 | 0.00 |
November | 0.00 | 0.00 | 0.970093E+10 | 0.603552E+10 | 55439.84 | 02-NOV-07:02 | 33132.24 | 0.00 |
December | 0.00 | 0.00 | 0.617801E+10 | 0.380317E+10 | 55234.29 | 11-DEC-08:62 | 24603.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.215564E+12 | 0.126489E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.311468E+10 | 0.194282E+10 | 20420.15 | 11476.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.326906E+11 | 0.185945E+11 | 58815.35 | 33132.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158545E+10 | 0.989180E+09 | 10547.00 | 19-JAN-14:00 | 5924.40 | 0.00 |
February | 0.00 | 0.00 | 0.232372E+10 | 0.143427E+10 | 10990.31 | 24-FEB-14:00 | 6854.24 | 0.00 |
March | 0.00 | 0.00 | 0.331413E+10 | 0.211348E+10 | 12269.93 | 30-MAR-13:00 | 7425.32 | 0.00 |
April | 0.00 | 0.00 | 0.621204E+10 | 0.407111E+10 | 26615.36 | 29-APR-07:03 | 15203.33 | 0.00 |
May | 0.00 | 0.00 | 0.140307E+11 | 0.847416E+10 | 30311.12 | 21-MAY-08:62 | 13933.99 | 0.00 |
June | 0.00 | 0.00 | 0.151563E+11 | 0.903740E+10 | 30688.77 | 19-JUN-07:02 | 12889.90 | 0.00 |
July | 0.00 | 0.00 | 0.167875E+11 | 0.924100E+10 | 30829.09 | 03-JUL-07:02 | 13169.36 | 0.00 |
August | 0.00 | 0.00 | 0.169726E+11 | 0.966479E+10 | 30784.62 | 14-AUG-07:03 | 12591.68 | 0.00 |
September | 0.00 | 0.00 | 0.145677E+11 | 0.799174E+10 | 30840.78 | 05-SEP-07:02 | 13239.14 | 0.00 |
October | 0.00 | 0.00 | 0.125609E+11 | 0.750151E+10 | 30692.49 | 08-OCT-08:62 | 13748.22 | 0.00 |
November | 0.00 | 0.00 | 0.498610E+10 | 0.310064E+10 | 29047.51 | 02-NOV-07:02 | 17393.35 | 0.00 |
December | 0.00 | 0.00 | 0.317939E+10 | 0.195678E+10 | 26534.57 | 11-DEC-08:62 | 11784.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111676E+12 | 0.655761E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.158545E+10 | 0.989180E+09 | 10547.00 | 5924.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169726E+11 | 0.966479E+10 | 30840.78 | 17393.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154727E+10 | 0.964159E+09 | 10455.00 | 19-JAN-14:00 | 5862.84 | 0.00 |
February | 0.00 | 0.00 | 0.227528E+10 | 0.140187E+10 | 10900.67 | 24-FEB-13:50 | 6788.62 | 0.00 |
March | 0.00 | 0.00 | 0.325709E+10 | 0.207228E+10 | 12205.30 | 30-MAR-13:00 | 7378.99 | 0.00 |
April | 0.00 | 0.00 | 0.613722E+10 | 0.401748E+10 | 25771.21 | 29-APR-07:03 | 14658.57 | 0.00 |
May | 0.00 | 0.00 | 0.139524E+11 | 0.841878E+10 | 30173.85 | 21-MAY-08:62 | 13837.86 | 0.00 |
June | 0.00 | 0.00 | 0.150839E+11 | 0.898525E+10 | 30551.21 | 19-JUN-07:02 | 12802.07 | 0.00 |
July | 0.00 | 0.00 | 0.167186E+11 | 0.919321E+10 | 30693.57 | 03-JUL-07:02 | 13093.39 | 0.00 |
August | 0.00 | 0.00 | 0.169053E+11 | 0.961714E+10 | 30649.29 | 14-AUG-07:03 | 12520.32 | 0.00 |
September | 0.00 | 0.00 | 0.145012E+11 | 0.794611E+10 | 30705.21 | 05-SEP-07:02 | 13164.82 | 0.00 |
October | 0.00 | 0.00 | 0.124929E+11 | 0.745207E+10 | 30555.50 | 08-OCT-08:62 | 13665.97 | 0.00 |
November | 0.00 | 0.00 | 0.492608E+10 | 0.305665E+10 | 28923.47 | 02-NOV-07:02 | 17268.14 | 0.00 |
December | 0.00 | 0.00 | 0.313784E+10 | 0.192697E+10 | 25395.36 | 11-DEC-08:62 | 11254.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110935E+12 | 0.650520E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.154727E+10 | 0.964159E+09 | 10455.00 | 5862.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169053E+11 | 0.961714E+10 | 30705.21 | 17268.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147877E+10 | 0.919490E+09 | 10333.15 | 19-JAN-14:00 | 5783.80 | 0.00 |
February | 0.00 | 0.00 | 0.217875E+10 | 0.133875E+10 | 10744.99 | 24-FEB-14:00 | 6676.60 | 0.00 |
March | 0.00 | 0.00 | 0.313622E+10 | 0.198563E+10 | 12091.15 | 30-MAR-13:00 | 7297.97 | 0.00 |
April | 0.00 | 0.00 | 0.597648E+10 | 0.390334E+10 | 22998.67 | 29-APR-07:03 | 12926.04 | 0.00 |
May | 0.00 | 0.00 | 0.138666E+11 | 0.836011E+10 | 30244.78 | 21-MAY-08:62 | 13763.68 | 0.00 |
June | 0.00 | 0.00 | 0.150390E+11 | 0.895336E+10 | 30623.10 | 19-JUN-07:02 | 12723.19 | 0.00 |
July | 0.00 | 0.00 | 0.167108E+11 | 0.918950E+10 | 30783.24 | 03-JUL-07:02 | 13081.10 | 0.00 |
August | 0.00 | 0.00 | 0.169252E+11 | 0.963180E+10 | 30738.83 | 14-AUG-07:01 | 12597.38 | 0.00 |
September | 0.00 | 0.00 | 0.144908E+11 | 0.794036E+10 | 30794.91 | 05-SEP-07:02 | 13181.09 | 0.00 |
October | 0.00 | 0.00 | 0.124543E+11 | 0.742444E+10 | 30639.09 | 08-OCT-08:62 | 13677.41 | 0.00 |
November | 0.00 | 0.00 | 0.481555E+10 | 0.297515E+10 | 29004.92 | 02-NOV-07:02 | 17210.19 | 0.00 |
December | 0.00 | 0.00 | 0.305851E+10 | 0.187133E+10 | 22933.88 | 11-DEC-08:62 | 13488.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110131E+12 | 0.644932E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.147877E+10 | 0.919490E+09 | 10333.15 | 5783.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169252E+11 | 0.963180E+10 | 30794.91 | 17210.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153886E+10 | 0.968343E+09 | 11238.27 | 19-JAN-14:00 | 6439.54 | 0.00 |
February | 0.00 | 0.00 | 0.223581E+10 | 0.138984E+10 | 11579.64 | 24-FEB-13:10 | 7239.65 | 0.00 |
March | 0.00 | 0.00 | 0.331719E+10 | 0.212349E+10 | 12943.96 | 30-MAR-13:00 | 7923.78 | 0.00 |
April | 0.00 | 0.00 | 0.626926E+10 | 0.414674E+10 | 17257.39 | 28-APR-16:10 | 10226.29 | 0.00 |
May | 0.00 | 0.00 | 0.149920E+11 | 0.916285E+10 | 34445.15 | 21-MAY-08:62 | 15034.42 | 0.00 |
June | 0.00 | 0.00 | 0.164195E+11 | 0.994440E+10 | 34813.13 | 19-JUN-07:02 | 13908.10 | 0.00 |
July | 0.00 | 0.00 | 0.183641E+11 | 0.103345E+11 | 34918.03 | 03-JUL-07:02 | 14178.25 | 0.00 |
August | 0.00 | 0.00 | 0.187534E+11 | 0.109022E+11 | 34869.16 | 07-AUG-07:02 | 14990.34 | 0.00 |
September | 0.00 | 0.00 | 0.159516E+11 | 0.894135E+10 | 34931.27 | 05-SEP-07:02 | 14586.86 | 0.00 |
October | 0.00 | 0.00 | 0.136655E+11 | 0.828920E+10 | 34881.24 | 08-OCT-08:62 | 15286.75 | 0.00 |
November | 0.00 | 0.00 | 0.509672E+10 | 0.318834E+10 | 33300.37 | 02-NOV-07:02 | 18314.83 | 0.00 |
December | 0.00 | 0.00 | 0.316926E+10 | 0.195682E+10 | 16401.58 | 15-DEC-08:62 | 8642.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119773E+12 | 0.713481E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.153886E+10 | 0.968343E+09 | 11238.27 | 6439.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187534E+11 | 0.109022E+11 | 34931.27 | 18314.83 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173496E+10 | 0.36 | 2373.40 | 10-JAN-08:61 | 0.88 |
February | 0.157580E+10 | 0.36 | 2373.40 | 05-FEB-08:62 | 0.88 |
March | 0.174080E+10 | 0.36 | 2205.05 | 11-MAR-08:61 | 0.85 |
April | 0.167015E+10 | 0.36 | 2373.40 | 30-APR-07:02 | 0.86 |
May | 0.174910E+10 | 0.36 | 2373.40 | 03-MAY-07:02 | 0.87 |
June | 0.173803E+10 | 0.36 | 2373.40 | 02-JUN-07:02 | 0.86 |
July | 0.186099E+10 | 0.37 | 2373.40 | 01-JUL-07:02 | 0.86 |
August | 0.186039E+10 | 0.37 | 2373.40 | 01-AUG-07:02 | 0.86 |
September | 0.176210E+10 | 0.37 | 2373.40 | 01-SEP-07:02 | 0.86 |
October | 0.179375E+10 | 0.36 | 2373.40 | 03-OCT-07:02 | 0.87 |
November | 0.166895E+10 | 0.36 | 2373.40 | 01-NOV-07:02 | 0.87 |
December | 0.174274E+10 | 0.36 | 2373.40 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.208978E+11 | 0.36 | |||
Minimum of Months | 0.157580E+10 | 0.36 | 2205.05 | 0.85 | |
Maximum of Months | 0.186099E+10 | 0.37 | 2373.40 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.797187E+09 | 0.36 | 593.53 | 10-JAN-09:20 | 0.60 |
February | 0.750215E+09 | 0.36 | 867.31 | 05-FEB-08:62 | 0.75 |
March | 0.830405E+09 | 0.37 | 647.31 | 11-MAR-12:10 | 0.63 |
April | 0.811847E+09 | 0.37 | 1295.73 | 30-APR-07:02 | 0.90 |
May | 0.840807E+09 | 0.38 | 1295.73 | 03-MAY-07:02 | 0.90 |
June | 0.843312E+09 | 0.39 | 1295.73 | 02-JUN-07:02 | 0.90 |
July | 0.911530E+09 | 0.39 | 1295.73 | 01-JUL-07:02 | 0.90 |
August | 0.909040E+09 | 0.39 | 1295.73 | 01-AUG-07:02 | 0.90 |
September | 0.851733E+09 | 0.39 | 1295.73 | 01-SEP-07:02 | 0.90 |
October | 0.866755E+09 | 0.38 | 1295.73 | 03-OCT-07:02 | 0.90 |
November | 0.841554E+09 | 0.37 | 1295.73 | 01-NOV-07:02 | 0.90 |
December | 0.841071E+09 | 0.37 | 1295.73 | 17-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.100955E+11 | 0.38 | |||
Minimum of Months | 0.750215E+09 | 0.36 | 593.53 | 0.60 | |
Maximum of Months | 0.911530E+09 | 0.39 | 1295.73 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.755741E+09 | 0.30 | 714.52 | 05-JAN-08:03 | 0.67 |
February | 0.686286E+09 | 0.30 | 1101.55 | 05-FEB-08:62 | 0.85 |
March | 0.770924E+09 | 0.30 | 881.50 | 12-MAR-07:02 | 0.75 |
April | 0.730608E+09 | 0.30 | 1298.71 | 29-APR-06:03 | 0.89 |
May | 0.770727E+09 | 0.30 | 1298.71 | 01-MAY-06:03 | 0.89 |
June | 0.771420E+09 | 0.31 | 1298.71 | 01-JUN-06:03 | 0.90 |
July | 0.814128E+09 | 0.31 | 1298.71 | 01-JUL-06:02 | 0.89 |
August | 0.827852E+09 | 0.31 | 1298.71 | 01-AUG-06:02 | 0.89 |
September | 0.768394E+09 | 0.30 | 1298.71 | 01-SEP-06:02 | 0.89 |
October | 0.783785E+09 | 0.30 | 1298.71 | 03-OCT-06:02 | 0.90 |
November | 0.731286E+09 | 0.30 | 1298.71 | 01-NOV-06:02 | 0.89 |
December | 0.753174E+09 | 0.30 | 1298.71 | 11-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.916432E+10 | 0.30 | |||
Minimum of Months | 0.686286E+09 | 0.30 | 714.52 | 0.67 | |
Maximum of Months | 0.827852E+09 | 0.31 | 1298.71 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.758929E+09 | 0.30 | 697.26 | 10-JAN-07:03 | 0.66 |
February | 0.688977E+09 | 0.30 | 1202.33 | 05-FEB-08:62 | 0.88 |
March | 0.773569E+09 | 0.30 | 991.16 | 12-MAR-07:02 | 0.80 |
April | 0.732641E+09 | 0.30 | 1302.46 | 29-APR-06:03 | 0.89 |
May | 0.772525E+09 | 0.30 | 1302.46 | 01-MAY-06:03 | 0.89 |
June | 0.773247E+09 | 0.31 | 1302.46 | 01-JUN-06:03 | 0.90 |
July | 0.816394E+09 | 0.31 | 1302.46 | 01-JUL-06:02 | 0.89 |
August | 0.829804E+09 | 0.31 | 1302.46 | 01-AUG-06:02 | 0.89 |
September | 0.770498E+09 | 0.30 | 1302.46 | 01-SEP-06:02 | 0.89 |
October | 0.785783E+09 | 0.30 | 1302.46 | 03-OCT-06:02 | 0.90 |
November | 0.733301E+09 | 0.30 | 1302.46 | 01-NOV-06:02 | 0.89 |
December | 0.755840E+09 | 0.30 | 1302.46 | 11-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.919151E+10 | 0.30 | |||
Minimum of Months | 0.688977E+09 | 0.30 | 697.26 | 0.66 | |
Maximum of Months | 0.829804E+09 | 0.31 | 1302.46 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.754610E+09 | 0.30 | 759.92 | 10-JAN-07:03 | 0.70 |
February | 0.684737E+09 | 0.30 | 1292.24 | 05-FEB-08:62 | 0.91 |
March | 0.768280E+09 | 0.30 | 1086.00 | 12-MAR-07:02 | 0.84 |
April | 0.726701E+09 | 0.30 | 1292.24 | 29-APR-06:03 | 0.89 |
May | 0.765647E+09 | 0.30 | 1292.24 | 01-MAY-06:03 | 0.89 |
June | 0.765842E+09 | 0.31 | 1292.24 | 02-JUN-06:02 | 0.89 |
July | 0.808774E+09 | 0.31 | 1292.24 | 01-JUL-06:02 | 0.89 |
August | 0.821762E+09 | 0.31 | 1292.24 | 01-AUG-06:02 | 0.89 |
September | 0.763596E+09 | 0.30 | 1292.24 | 01-SEP-06:02 | 0.89 |
October | 0.778749E+09 | 0.30 | 1292.24 | 03-OCT-06:02 | 0.90 |
November | 0.727358E+09 | 0.30 | 1292.24 | 01-NOV-06:02 | 0.89 |
December | 0.750921E+09 | 0.30 | 1292.24 | 11-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.911698E+10 | 0.30 | |||
Minimum of Months | 0.684737E+09 | 0.30 | 759.92 | 0.70 | |
Maximum of Months | 0.821762E+09 | 0.31 | 1292.24 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118803E+10 | 0.27 | 2195.82 | 10-JAN-08:61 | 0.88 |
February | 0.107729E+10 | 0.27 | 2195.82 | 05-FEB-09:01 | 0.88 |
March | 0.120884E+10 | 0.27 | 2195.82 | 12-MAR-08:61 | 0.88 |
April | 0.114173E+10 | 0.26 | 2195.82 | 29-APR-07:03 | 0.86 |
May | 0.122100E+10 | 0.27 | 2195.82 | 01-MAY-07:03 | 0.86 |
June | 0.123486E+10 | 0.28 | 2195.82 | 02-JUN-07:02 | 0.86 |
July | 0.131764E+10 | 0.28 | 2195.82 | 01-JUL-07:02 | 0.86 |
August | 0.134178E+10 | 0.29 | 2195.82 | 01-AUG-07:02 | 0.86 |
September | 0.123127E+10 | 0.27 | 2195.82 | 01-SEP-07:02 | 0.87 |
October | 0.125135E+10 | 0.27 | 2195.82 | 03-OCT-07:02 | 0.87 |
November | 0.114362E+10 | 0.26 | 2195.82 | 01-NOV-07:02 | 0.87 |
December | 0.118065E+10 | 0.26 | 2195.82 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.145381E+11 | 0.27 | |||
Minimum of Months | 0.107729E+10 | 0.26 | 2195.82 | 0.86 | |
Maximum of Months | 0.134178E+10 | 0.29 | 2195.82 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.644885E+09 | 0.28 | 1191.13 | 10-JAN-08:61 | 0.91 |
February | 0.584864E+09 | 0.28 | 1191.13 | 05-FEB-09:01 | 0.91 |
March | 0.656027E+09 | 0.28 | 1191.13 | 12-MAR-08:61 | 0.91 |
April | 0.619233E+09 | 0.27 | 1066.96 | 29-APR-07:03 | 0.85 |
May | 0.662479E+09 | 0.28 | 1191.13 | 01-MAY-07:03 | 0.89 |
June | 0.669563E+09 | 0.29 | 1191.13 | 02-JUN-07:02 | 0.89 |
July | 0.714403E+09 | 0.29 | 1191.13 | 01-JUL-07:02 | 0.89 |
August | 0.727273E+09 | 0.29 | 1191.13 | 01-AUG-07:02 | 0.89 |
September | 0.667156E+09 | 0.28 | 1191.13 | 01-SEP-07:02 | 0.90 |
October | 0.677701E+09 | 0.28 | 1191.13 | 03-OCT-07:02 | 0.90 |
November | 0.620137E+09 | 0.27 | 1191.13 | 01-NOV-07:02 | 0.90 |
December | 0.640765E+09 | 0.27 | 1191.13 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.788449E+10 | 0.28 | |||
Minimum of Months | 0.584864E+09 | 0.27 | 1066.96 | 0.85 | |
Maximum of Months | 0.727273E+09 | 0.29 | 1191.13 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.642841E+09 | 0.28 | 1185.90 | 10-JAN-08:61 | 0.91 |
February | 0.582817E+09 | 0.28 | 1185.90 | 05-FEB-09:01 | 0.91 |
March | 0.653508E+09 | 0.28 | 1185.90 | 12-MAR-08:61 | 0.91 |
April | 0.616488E+09 | 0.27 | 1026.69 | 29-APR-07:03 | 0.84 |
May | 0.659598E+09 | 0.28 | 1185.90 | 03-MAY-07:02 | 0.90 |
June | 0.666766E+09 | 0.29 | 1185.90 | 02-JUN-07:02 | 0.89 |
July | 0.711665E+09 | 0.29 | 1185.90 | 01-JUL-07:02 | 0.89 |
August | 0.724538E+09 | 0.30 | 1185.90 | 01-AUG-07:02 | 0.89 |
September | 0.664506E+09 | 0.28 | 1185.90 | 01-SEP-07:02 | 0.90 |
October | 0.674857E+09 | 0.28 | 1185.90 | 03-OCT-07:02 | 0.90 |
November | 0.617375E+09 | 0.27 | 1185.90 | 01-NOV-07:02 | 0.90 |
December | 0.638421E+09 | 0.27 | 1185.90 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.785338E+10 | 0.28 | |||
Minimum of Months | 0.582817E+09 | 0.27 | 1026.69 | 0.84 | |
Maximum of Months | 0.724538E+09 | 0.30 | 1185.90 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.646941E+09 | 0.28 | 1189.36 | 05-JAN-08:61 | 0.91 |
February | 0.585969E+09 | 0.28 | 1189.36 | 05-FEB-09:01 | 0.91 |
March | 0.656681E+09 | 0.28 | 1189.36 | 11-MAR-08:61 | 0.91 |
April | 0.618047E+09 | 0.27 | 891.05 | 29-APR-07:03 | 0.78 |
May | 0.660317E+09 | 0.28 | 1189.36 | 03-MAY-07:02 | 0.90 |
June | 0.667497E+09 | 0.29 | 1189.36 | 02-JUN-07:02 | 0.89 |
July | 0.712981E+09 | 0.29 | 1189.36 | 01-JUL-07:02 | 0.89 |
August | 0.726283E+09 | 0.29 | 1189.36 | 01-AUG-07:02 | 0.89 |
September | 0.666114E+09 | 0.28 | 1189.36 | 01-SEP-07:02 | 0.90 |
October | 0.676201E+09 | 0.28 | 1189.36 | 03-OCT-07:02 | 0.90 |
November | 0.618886E+09 | 0.27 | 1189.36 | 02-NOV-07:02 | 0.89 |
December | 0.641566E+09 | 0.27 | 1189.36 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.787749E+10 | 0.28 | |||
Minimum of Months | 0.585969E+09 | 0.27 | 891.05 | 0.78 | |
Maximum of Months | 0.726283E+09 | 0.29 | 1189.36 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.747012E+09 | 0.28 | 1364.36 | 05-JAN-08:61 | 0.91 |
February | 0.675363E+09 | 0.28 | 1364.36 | 05-FEB-09:01 | 0.91 |
March | 0.756959E+09 | 0.28 | 1364.36 | 09-MAR-08:62 | 0.91 |
April | 0.707594E+09 | 0.27 | 604.93 | 28-APR-16:10 | 0.58 |
May | 0.747363E+09 | 0.28 | 1364.36 | 06-MAY-07:02 | 0.89 |
June | 0.752362E+09 | 0.28 | 1364.36 | 03-JUN-07:02 | 0.89 |
July | 0.804560E+09 | 0.29 | 1364.36 | 01-JUL-07:02 | 0.89 |
August | 0.820440E+09 | 0.29 | 1364.36 | 01-AUG-07:02 | 0.89 |
September | 0.755887E+09 | 0.28 | 1364.36 | 01-SEP-07:02 | 0.90 |
October | 0.766193E+09 | 0.28 | 1364.36 | 04-OCT-07:02 | 0.89 |
November | 0.708542E+09 | 0.27 | 1364.36 | 02-NOV-07:02 | 0.89 |
December | 0.739204E+09 | 0.27 | 1364.36 | 20-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.898148E+10 | 0.28 | |||
Minimum of Months | 0.675363E+09 | 0.27 | 604.93 | 0.58 | |
Maximum of Months | 0.820440E+09 | 0.29 | 1364.36 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.294351E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.313162E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.405983E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.596178E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110690E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116091E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.128804E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.127608E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113584E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.100347E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.499518E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.389492E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.946993E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.294351E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128804E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153147E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171063E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.219087E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.320014E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.551988E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.575350E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.634503E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.626695E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.559562E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.502436E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267699E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201814E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.478336E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153147E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.634503E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.129097E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141811E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179835E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.254447E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.456131E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.479919E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.520559E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.525638E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.457339E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.407364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216305E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167411E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.393586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129097E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.525638E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127844E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140463E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.178601E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.253702E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.457049E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.481203E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.522398E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.527173E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.458741E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.408300E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215262E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.393735E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127844E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.527173E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124143E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136403E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173405E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.246923E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.450328E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.474633E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.515898E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.520497E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.452640E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.402489E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209774E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.162949E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.387008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124143E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520497E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.198728E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223760E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.286877E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.422482E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.792445E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.843074E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.913691E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.928271E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.795807E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.713260E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.355535E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.271832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.674576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.198728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.928271E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104526E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116729E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218398E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.409102E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.435111E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.471662E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.478878E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.410447E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.367995E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.183940E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.348790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.478878E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.103386E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115346E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147552E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.216286E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.406875E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.433005E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.469656E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.476902E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408554E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.366041E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182189E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.140680E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.346647E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103386E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.476902E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102169E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113404E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145015E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.212711E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.405164E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.432195E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.469769E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.477667E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408628E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.365394E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179717E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.345102E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102169E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.477667E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114027E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124381E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160354E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230633E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.445069E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.477720E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.522169E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.533977E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.455094E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.405582E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.196664E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.381838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114027E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.533977E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173496E+10 | 0.473751E+10 | 0.514667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157580E+10 | 0.612500E+10 | 0.716552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174080E+10 | 0.904135E+10 | 0.473154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167015E+10 | 0.167677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174910E+10 | 0.373058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173803E+10 | 0.397598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186099E+10 | 0.452241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186039E+10 | 0.446404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176210E+10 | 0.396392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179375E+10 | 0.337396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166895E+10 | 0.133344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174274E+10 | 0.860120E+10 | 0.511631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208978E+11 | 0.298916E+12 | 0.221600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157580E+10 | 0.473751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186099E+10 | 0.452241E+11 | 0.716552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.797187E+09 | 0.292842E+10 | 40588746.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750215E+09 | 0.384076E+10 | 0.125221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830405E+09 | 0.540329E+10 | 0.109838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811847E+09 | 0.944264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840807E+09 | 0.188908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843312E+09 | 0.199036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.911530E+09 | 0.223775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.909040E+09 | 0.220468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.851733E+09 | 0.197210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.866755E+09 | 0.171237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.841554E+09 | 0.741339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841071E+09 | 0.476501E+10 | 0.101631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100955E+11 | 0.153857E+12 | 0.377279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.750215E+09 | 0.292842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.911530E+09 | 0.223775E+11 | 0.125221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.755741E+09 | 0.213007E+10 | 0.156313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686286E+09 | 0.292858E+10 | 0.220179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770924E+09 | 0.408136E+10 | 0.163281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.730608E+09 | 0.719993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.770727E+09 | 0.154537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771420E+09 | 0.165214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.814128E+09 | 0.183523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.827852E+09 | 0.184574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768394E+09 | 0.160452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783785E+09 | 0.137166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.731286E+09 | 0.582739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753174E+09 | 0.374362E+10 | 0.173168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916432E+10 | 0.124458E+12 | 0.712941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686286E+09 | 0.213007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.827852E+09 | 0.184574E+11 | 0.220179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.758929E+09 | 0.206310E+10 | 0.196586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688977E+09 | 0.285890E+10 | 0.248849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773569E+09 | 0.401633E+10 | 0.180824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732641E+09 | 0.715626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772525E+09 | 0.154795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773247E+09 | 0.165639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.816394E+09 | 0.184185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.829804E+09 | 0.185117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.770498E+09 | 0.160935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785783E+09 | 0.137452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733301E+09 | 0.577399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755840E+09 | 0.369832E+10 | 0.193404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919151E+10 | 0.124379E+12 | 0.819662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.688977E+09 | 0.206310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829804E+09 | 0.185117E+11 | 0.248849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.754610E+09 | 0.192697E+10 | 0.260264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684737E+09 | 0.270631E+10 | 0.293516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768280E+09 | 0.382140E+10 | 0.211970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.726701E+09 | 0.689906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765647E+09 | 0.152213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.765842E+09 | 0.163193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808774E+09 | 0.181761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.821762E+09 | 0.182646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763596E+09 | 0.158589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.778749E+09 | 0.135278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727358E+09 | 0.557102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750921E+09 | 0.356524E+10 | 0.234822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911698E+10 | 0.121858E+12 | 0.100057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.684737E+09 | 0.192697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821762E+09 | 0.182646E+11 | 0.293516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118803E+10 | 0.311468E+10 | 0.624349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107729E+10 | 0.455547E+10 | 0.621440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120884E+10 | 0.647606E+10 | 0.436743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114173E+10 | 0.120444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122100E+10 | 0.270145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123486E+10 | 0.291795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131764E+10 | 0.323142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134178E+10 | 0.326906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123127E+10 | 0.280724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125135E+10 | 0.242235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114362E+10 | 0.970093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118065E+10 | 0.617801E+10 | 0.543125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145381E+11 | 0.215564E+12 | 0.222566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107729E+10 | 0.311468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134178E+10 | 0.326906E+11 | 0.624349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.644885E+09 | 0.158545E+10 | 0.342474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584864E+09 | 0.232372E+10 | 0.342970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656027E+09 | 0.331413E+10 | 0.238946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619233E+09 | 0.621204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662479E+09 | 0.140307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669563E+09 | 0.151563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714403E+09 | 0.167875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727273E+09 | 0.169726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667156E+09 | 0.145677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.677701E+09 | 0.125609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620137E+09 | 0.498610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.640765E+09 | 0.317939E+10 | 0.299835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788449E+10 | 0.111676E+12 | 0.122423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.584864E+09 | 0.158545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.727273E+09 | 0.169726E+11 | 0.342970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.642841E+09 | 0.154727E+10 | 0.372968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582817E+09 | 0.227528E+10 | 0.362727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.653508E+09 | 0.325709E+10 | 0.252711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.616488E+09 | 0.613722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.659598E+09 | 0.139524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666766E+09 | 0.150839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711665E+09 | 0.167186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724538E+09 | 0.169053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664506E+09 | 0.145012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674857E+09 | 0.124929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617375E+09 | 0.492608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638421E+09 | 0.313784E+10 | 0.318954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785338E+10 | 0.110935E+12 | 0.130736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.582817E+09 | 0.154727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724538E+09 | 0.169053E+11 | 0.372968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.646941E+09 | 0.147877E+10 | 0.463114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585969E+09 | 0.217875E+10 | 0.421852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656681E+09 | 0.313622E+10 | 0.304124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618047E+09 | 0.597648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.660317E+09 | 0.138666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667497E+09 | 0.150390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712981E+09 | 0.167108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726283E+09 | 0.169252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.666114E+09 | 0.144908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.676201E+09 | 0.124543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618886E+09 | 0.481555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641566E+09 | 0.305851E+10 | 0.375736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787749E+10 | 0.110131E+12 | 0.156483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.585969E+09 | 0.147877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.726283E+09 | 0.169252E+11 | 0.463114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.747012E+09 | 0.153886E+10 | 0.713694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675363E+09 | 0.223581E+10 | 0.600013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756959E+09 | 0.331719E+10 | 0.486326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707594E+09 | 0.626926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747363E+09 | 0.149920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752362E+09 | 0.164195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.804560E+09 | 0.183641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820440E+09 | 0.187534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755887E+09 | 0.159516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766193E+09 | 0.136655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708542E+09 | 0.509672E+10 | 424671.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739204E+09 | 0.316926E+10 | 0.560874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.898148E+10 | 0.119773E+12 | 0.236133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.675363E+09 | 0.153886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820440E+09 | 0.187534E+11 | 0.713694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173496E+10 | 0.00 | 0.00 | 0.00 | 0.120855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157580E+10 | 0.00 | 0.00 | 0.00 | 0.155583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174080E+10 | 0.00 | 0.00 | 0.00 | 0.231903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167015E+10 | 0.00 | 0.00 | 0.00 | 0.429163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174910E+10 | 0.00 | 0.00 | 0.00 | 0.931994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173803E+10 | 0.00 | 0.00 | 0.00 | 0.987104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186099E+10 | 0.00 | 0.00 | 0.00 | 0.110194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186039E+10 | 0.00 | 0.00 | 0.00 | 0.109004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176210E+10 | 0.00 | 0.00 | 0.00 | 0.959631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179375E+10 | 0.00 | 0.00 | 0.00 | 0.824100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166895E+10 | 0.00 | 0.00 | 0.00 | 0.332624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174274E+10 | 0.00 | 0.00 | 0.00 | 0.215218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208978E+11 | 0.00 | 0.00 | 0.00 | 0.738015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157580E+10 | 0.00 | 0.00 | 0.00 | 0.120855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186099E+10 | 0.00 | 0.00 | 0.00 | 0.110194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.797187E+09 | 0.00 | 0.00 | 0.00 | 0.734283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750215E+09 | 0.00 | 0.00 | 0.00 | 0.960410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830405E+09 | 0.00 | 0.00 | 0.00 | 0.136046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811847E+09 | 0.00 | 0.00 | 0.00 | 0.238829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840807E+09 | 0.00 | 0.00 | 0.00 | 0.467908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843312E+09 | 0.00 | 0.00 | 0.00 | 0.491019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.911530E+09 | 0.00 | 0.00 | 0.00 | 0.543350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.909040E+09 | 0.00 | 0.00 | 0.00 | 0.535791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.851733E+09 | 0.00 | 0.00 | 0.00 | 0.474388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.866755E+09 | 0.00 | 0.00 | 0.00 | 0.415761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.841554E+09 | 0.00 | 0.00 | 0.00 | 0.183543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841071E+09 | 0.00 | 0.00 | 0.00 | 0.117707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100955E+11 | 0.00 | 0.00 | 0.00 | 0.377381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.750215E+09 | 0.00 | 0.00 | 0.00 | 0.734283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.911530E+09 | 0.00 | 0.00 | 0.00 | 0.543350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.755741E+09 | 0.00 | 0.00 | 0.00 | 0.535225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686286E+09 | 0.00 | 0.00 | 0.00 | 0.731828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770924E+09 | 0.00 | 0.00 | 0.00 | 0.102742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.730608E+09 | 0.00 | 0.00 | 0.00 | 0.181386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.770727E+09 | 0.00 | 0.00 | 0.00 | 0.379058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771420E+09 | 0.00 | 0.00 | 0.00 | 0.402777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.814128E+09 | 0.00 | 0.00 | 0.00 | 0.439147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.827852E+09 | 0.00 | 0.00 | 0.00 | 0.442853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768394E+09 | 0.00 | 0.00 | 0.00 | 0.380499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783785E+09 | 0.00 | 0.00 | 0.00 | 0.328985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.731286E+09 | 0.00 | 0.00 | 0.00 | 0.143177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753174E+09 | 0.00 | 0.00 | 0.00 | 0.920936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916432E+10 | 0.00 | 0.00 | 0.00 | 0.301942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686286E+09 | 0.00 | 0.00 | 0.00 | 0.535225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.827852E+09 | 0.00 | 0.00 | 0.00 | 0.442853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.758929E+09 | 0.00 | 0.00 | 0.00 | 0.519512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688977E+09 | 0.00 | 0.00 | 0.00 | 0.715653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773569E+09 | 0.00 | 0.00 | 0.00 | 0.101244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732641E+09 | 0.00 | 0.00 | 0.00 | 0.180438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772525E+09 | 0.00 | 0.00 | 0.00 | 0.379796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773247E+09 | 0.00 | 0.00 | 0.00 | 0.403879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.816394E+09 | 0.00 | 0.00 | 0.00 | 0.440758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.829804E+09 | 0.00 | 0.00 | 0.00 | 0.444192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.770498E+09 | 0.00 | 0.00 | 0.00 | 0.381691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785783E+09 | 0.00 | 0.00 | 0.00 | 0.329722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733301E+09 | 0.00 | 0.00 | 0.00 | 0.141932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755840E+09 | 0.00 | 0.00 | 0.00 | 0.910270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919151E+10 | 0.00 | 0.00 | 0.00 | 0.301819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.688977E+09 | 0.00 | 0.00 | 0.00 | 0.519512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829804E+09 | 0.00 | 0.00 | 0.00 | 0.444192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.754610E+09 | 0.00 | 0.00 | 0.00 | 0.486823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684737E+09 | 0.00 | 0.00 | 0.00 | 0.679290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768280E+09 | 0.00 | 0.00 | 0.00 | 0.965772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.726701E+09 | 0.00 | 0.00 | 0.00 | 0.174253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765647E+09 | 0.00 | 0.00 | 0.00 | 0.373763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.765842E+09 | 0.00 | 0.00 | 0.00 | 0.398049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808774E+09 | 0.00 | 0.00 | 0.00 | 0.435021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.821762E+09 | 0.00 | 0.00 | 0.00 | 0.438321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763596E+09 | 0.00 | 0.00 | 0.00 | 0.376281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.778749E+09 | 0.00 | 0.00 | 0.00 | 0.324614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727358E+09 | 0.00 | 0.00 | 0.00 | 0.137038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750921E+09 | 0.00 | 0.00 | 0.00 | 0.878567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911698E+10 | 0.00 | 0.00 | 0.00 | 0.295838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.684737E+09 | 0.00 | 0.00 | 0.00 | 0.486823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821762E+09 | 0.00 | 0.00 | 0.00 | 0.438321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.118803E+10 | 0.00 | 0.00 | 0.00 | 0.799251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107729E+10 | 0.00 | 0.00 | 0.00 | 0.116031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120884E+10 | 0.00 | 0.00 | 0.00 | 0.165993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114173E+10 | 0.00 | 0.00 | 0.00 | 0.308309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122100E+10 | 0.00 | 0.00 | 0.00 | 0.670345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123486E+10 | 0.00 | 0.00 | 0.00 | 0.719587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131764E+10 | 0.00 | 0.00 | 0.00 | 0.781927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134178E+10 | 0.00 | 0.00 | 0.00 | 0.794093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123127E+10 | 0.00 | 0.00 | 0.00 | 0.672680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125135E+10 | 0.00 | 0.00 | 0.00 | 0.588125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114362E+10 | 0.00 | 0.00 | 0.00 | 0.241173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118065E+10 | 0.00 | 0.00 | 0.00 | 0.153767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145381E+11 | 0.00 | 0.00 | 0.00 | 0.529195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107729E+10 | 0.00 | 0.00 | 0.00 | 0.799251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134178E+10 | 0.00 | 0.00 | 0.00 | 0.794093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.644885E+09 | 0.00 | 0.00 | 0.00 | 0.400380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584864E+09 | 0.00 | 0.00 | 0.00 | 0.582425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656027E+09 | 0.00 | 0.00 | 0.00 | 0.835893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619233E+09 | 0.00 | 0.00 | 0.00 | 0.156475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662479E+09 | 0.00 | 0.00 | 0.00 | 0.342854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669563E+09 | 0.00 | 0.00 | 0.00 | 0.368155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714403E+09 | 0.00 | 0.00 | 0.00 | 0.400222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727273E+09 | 0.00 | 0.00 | 0.00 | 0.406151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667156E+09 | 0.00 | 0.00 | 0.00 | 0.343731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.677701E+09 | 0.00 | 0.00 | 0.00 | 0.300225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620137E+09 | 0.00 | 0.00 | 0.00 | 0.121927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.640765E+09 | 0.00 | 0.00 | 0.00 | 0.778384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.788449E+10 | 0.00 | 0.00 | 0.00 | 0.269945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.584864E+09 | 0.00 | 0.00 | 0.00 | 0.400380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.727273E+09 | 0.00 | 0.00 | 0.00 | 0.406151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.642841E+09 | 0.00 | 0.00 | 0.00 | 0.391016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582817E+09 | 0.00 | 0.00 | 0.00 | 0.570645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.653508E+09 | 0.00 | 0.00 | 0.00 | 0.822011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.616488E+09 | 0.00 | 0.00 | 0.00 | 0.154637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.659598E+09 | 0.00 | 0.00 | 0.00 | 0.340915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666766E+09 | 0.00 | 0.00 | 0.00 | 0.366328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711665E+09 | 0.00 | 0.00 | 0.00 | 0.398489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724538E+09 | 0.00 | 0.00 | 0.00 | 0.404449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664506E+09 | 0.00 | 0.00 | 0.00 | 0.342104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674857E+09 | 0.00 | 0.00 | 0.00 | 0.298555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617375E+09 | 0.00 | 0.00 | 0.00 | 0.120451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638421E+09 | 0.00 | 0.00 | 0.00 | 0.768380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785338E+10 | 0.00 | 0.00 | 0.00 | 0.268113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.582817E+09 | 0.00 | 0.00 | 0.00 | 0.391016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724538E+09 | 0.00 | 0.00 | 0.00 | 0.404449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.646941E+09 | 0.00 | 0.00 | 0.00 | 0.374750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585969E+09 | 0.00 | 0.00 | 0.00 | 0.548073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656681E+09 | 0.00 | 0.00 | 0.00 | 0.793472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618047E+09 | 0.00 | 0.00 | 0.00 | 0.150906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.660317E+09 | 0.00 | 0.00 | 0.00 | 0.339132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667497E+09 | 0.00 | 0.00 | 0.00 | 0.365445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712981E+09 | 0.00 | 0.00 | 0.00 | 0.398471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726283E+09 | 0.00 | 0.00 | 0.00 | 0.405039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.666114E+09 | 0.00 | 0.00 | 0.00 | 0.342017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.676201E+09 | 0.00 | 0.00 | 0.00 | 0.297774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618886E+09 | 0.00 | 0.00 | 0.00 | 0.117828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641566E+09 | 0.00 | 0.00 | 0.00 | 0.750322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787749E+10 | 0.00 | 0.00 | 0.00 | 0.266327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.585969E+09 | 0.00 | 0.00 | 0.00 | 0.374750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.726283E+09 | 0.00 | 0.00 | 0.00 | 0.405039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.747012E+09 | 0.00 | 0.00 | 0.00 | 0.393254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675363E+09 | 0.00 | 0.00 | 0.00 | 0.568446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756959E+09 | 0.00 | 0.00 | 0.00 | 0.846577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707594E+09 | 0.00 | 0.00 | 0.00 | 0.159873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747363E+09 | 0.00 | 0.00 | 0.00 | 0.370332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752362E+09 | 0.00 | 0.00 | 0.00 | 0.402483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.804560E+09 | 0.00 | 0.00 | 0.00 | 0.441713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820440E+09 | 0.00 | 0.00 | 0.00 | 0.451933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755887E+09 | 0.00 | 0.00 | 0.00 | 0.379505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766193E+09 | 0.00 | 0.00 | 0.00 | 0.328963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708542E+09 | 0.00 | 0.00 | 0.00 | 0.125810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739204E+09 | 0.00 | 0.00 | 0.00 | 0.787912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.898148E+10 | 0.00 | 0.00 | 0.00 | 0.292023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.675363E+09 | 0.00 | 0.00 | 0.00 | 0.393254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820440E+09 | 0.00 | 0.00 | 0.00 | 0.451933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573111E+10 | 0.689438E+09 | 0.00 | 3284230.39 | 2700067.17 | 57463920.43 | 0.162387E+10 | 0.00 | 0.63 |
February | 0.344958E+10 | 0.888250E+09 | 0.00 | 4282829.23 | 0.00 | 0.203781E+09 | 0.234207E+10 | 0.00 | 0.69 |
March | 0.259782E+10 | 0.166770E+10 | 0.00 | 4824750.70 | 387081.96 | 0.240188E+09 | 0.237147E+10 | 0.00 | 0.68 |
April | 0.220918E+09 | 0.394135E+10 | 0.00 | 6230761.88 | 2876378.72 | 0.00 | 0.271749E+10 | 0.00 | 0.74 |
May | 0.00 | 0.131665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.146914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.176095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.164084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.138103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 84022815.63 | 0.105619E+11 | 0.00 | 3780534.56 | 0.00 | 0.00 | 0.123737E+10 | 0.00 | 0.63 |
November | 0.741422E+09 | 0.309363E+10 | 0.00 | 8947716.48 | 2466919.93 | 0.00 | 0.462301E+10 | 0.00 | 0.81 |
December | 0.324553E+10 | 0.186161E+10 | 0.00 | 4795150.87 | 7138324.24 | 0.117859E+09 | 0.343002E+10 | 0.00 | 0.67 |
Annual Sum or Average | 0.160704E+11 | 0.983900E+11 | 0.00 | 36145974.12 | 15568772.02 | 0.619292E+09 | 0.183453E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.689438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.573111E+10 | 0.176095E+11 | 0.00 | 8947716.48 | 7138324.24 | 0.240188E+09 | 0.462301E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178444E+10 | 0.382398E+09 | 0.00 | 2147566.41 | 146158.72 | 0.00 | 0.127951E+10 | 0.00 | 0.55 |
February | 0.987445E+09 | 0.507860E+09 | 0.00 | 2605965.49 | 0.00 | 25438092.64 | 0.149999E+10 | 0.00 | 0.63 |
March | 0.805079E+09 | 0.903868E+09 | 0.00 | 2787788.49 | 0.00 | 56215131.42 | 0.146626E+10 | 0.00 | 0.61 |
April | 53102665.63 | 0.192113E+10 | 0.00 | 2856635.91 | 236534.93 | 0.00 | 0.124960E+10 | 0.00 | 0.65 |
May | 0.00 | 0.581584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.646468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.763725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.719328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.605481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 28107519.82 | 0.467404E+10 | 0.00 | 1596797.39 | 0.00 | 0.00 | 0.539329E+09 | 0.00 | 0.53 |
November | 0.149630E+09 | 0.145660E+10 | 0.00 | 4821861.49 | 0.00 | 0.00 | 0.249171E+10 | 0.00 | 0.78 |
December | 0.106482E+10 | 0.916720E+09 | 0.00 | 3340264.63 | 204011.72 | 15967632.84 | 0.217410E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.487262E+10 | 0.439285E+11 | 0.00 | 20156879.81 | 586705.37 | 97620856.89 | 0.107005E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.382398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.178444E+10 | 0.763725E+10 | 0.00 | 4821861.49 | 236534.93 | 56215131.42 | 0.249171E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208528E+10 | 0.304502E+09 | 0.00 | 818226.29 | 9825708.72 | 35243112.31 | 0.481785E+09 | 0.00 | 0.49 |
February | 0.120837E+10 | 0.418435E+09 | 0.00 | 1222228.82 | 6512947.54 | 81121053.81 | 0.697339E+09 | 0.00 | 0.54 |
March | 0.105717E+10 | 0.749435E+09 | 0.00 | 1393321.61 | 15199535.84 | 84581990.80 | 0.746717E+09 | 0.00 | 0.55 |
April | 0.161946E+09 | 0.153507E+10 | 0.00 | 1739548.09 | 76407030.27 | 0.00 | 0.762775E+09 | 0.00 | 0.59 |
May | 0.00 | 0.492488E+10 | 0.00 | 25735.09 | 0.306541E+09 | 0.00 | 148313.10 | 0.00 | 0.43 |
June | 4267.24 | 0.552439E+10 | 0.00 | 44361.50 | 0.354195E+09 | 0.00 | 638605.08 | 0.00 | 0.43 |
July | 0.00 | 0.636213E+10 | 0.00 | 0.00 | 0.406500E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.616994E+10 | 0.00 | 0.00 | 0.351921E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 678359.31 | 0.505231E+10 | 0.00 | 42696.51 | 0.282323E+09 | 0.00 | 125430.90 | 0.00 | 0.42 |
October | 70587505.43 | 0.394074E+10 | 0.00 | 1480163.33 | 0.217750E+09 | 0.00 | 0.484308E+09 | 0.00 | 0.50 |
November | 0.388827E+09 | 0.122231E+10 | 0.00 | 2869057.55 | 61965434.61 | 0.00 | 0.146033E+10 | 0.00 | 0.66 |
December | 0.135842E+10 | 0.773643E+09 | 0.00 | 1687574.59 | 31164184.72 | 47009993.16 | 0.101089E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.633128E+10 | 0.369778E+11 | 0.00 | 11322913.37 | 0.212031E+10 | 0.247956E+09 | 0.564506E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.304502E+09 | 0.00 | 0.00 | 6512947.54 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208528E+10 | 0.636213E+10 | 0.00 | 2869057.55 | 0.406500E+09 | 84581990.80 | 0.146033E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208599E+10 | 0.296024E+09 | 0.00 | 751399.73 | 10090258.87 | 45308125.42 | 0.436490E+09 | 0.00 | 0.49 |
February | 0.123823E+10 | 0.411496E+09 | 0.00 | 1124805.62 | 6435188.48 | 90477969.22 | 0.632474E+09 | 0.00 | 0.53 |
March | 0.104759E+10 | 0.744533E+09 | 0.00 | 1296718.75 | 14983605.39 | 0.101168E+09 | 0.713351E+09 | 0.00 | 0.55 |
April | 0.165559E+09 | 0.153173E+10 | 0.00 | 1700629.72 | 76167351.04 | 0.00 | 0.752531E+09 | 0.00 | 0.59 |
May | 0.00 | 0.492997E+10 | 0.00 | 25845.86 | 0.306466E+09 | 0.00 | 151134.43 | 0.00 | 0.43 |
June | 5383.03 | 0.553255E+10 | 0.00 | 44793.32 | 0.354195E+09 | 0.00 | 645127.94 | 0.00 | 0.43 |
July | 0.00 | 0.637496E+10 | 0.00 | 0.00 | 0.406620E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.618038E+10 | 0.00 | 0.00 | 0.351960E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 678047.09 | 0.506191E+10 | 0.00 | 46380.82 | 0.282352E+09 | 0.00 | 129461.44 | 0.00 | 0.42 |
October | 68443065.49 | 0.394660E+10 | 0.00 | 1492481.00 | 0.217719E+09 | 0.00 | 0.487152E+09 | 0.00 | 0.50 |
November | 0.409535E+09 | 0.121938E+10 | 0.00 | 2798088.60 | 62066095.40 | 0.00 | 0.142988E+10 | 0.00 | 0.66 |
December | 0.136996E+10 | 0.771029E+09 | 0.00 | 1567464.65 | 31560794.62 | 54393963.88 | 0.956257E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.638599E+10 | 0.370006E+11 | 0.00 | 10848608.07 | 0.212062E+10 | 0.291348E+09 | 0.540906E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.296024E+09 | 0.00 | 0.00 | 6435188.48 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208599E+10 | 0.637496E+10 | 0.00 | 2798088.60 | 0.406620E+09 | 0.101168E+09 | 0.142988E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208239E+10 | 0.280614E+09 | 0.00 | 667011.17 | 10369503.98 | 64126761.57 | 0.377924E+09 | 0.00 | 0.48 |
February | 0.127179E+10 | 0.396226E+09 | 0.00 | 963992.63 | 6170141.73 | 0.114111E+09 | 0.531845E+09 | 0.00 | 0.52 |
March | 0.108570E+10 | 0.724242E+09 | 0.00 | 1113568.36 | 14261801.31 | 0.108963E+09 | 0.621866E+09 | 0.00 | 0.54 |
April | 0.178907E+09 | 0.149964E+10 | 0.00 | 1564760.13 | 76289846.28 | 0.00 | 0.728600E+09 | 0.00 | 0.58 |
May | 0.00 | 0.488381E+10 | 0.00 | 23606.56 | 0.304713E+09 | 0.00 | 146946.89 | 0.00 | 0.43 |
June | 0.00 | 0.549050E+10 | 0.00 | 40970.33 | 0.352612E+09 | 0.00 | 602206.92 | 0.00 | 0.43 |
July | 0.00 | 0.633093E+10 | 0.00 | 0.00 | 0.404798E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.613677E+10 | 0.00 | 0.00 | 0.350266E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 710103.63 | 0.501810E+10 | 0.00 | 36448.18 | 0.280508E+09 | 0.00 | 122682.61 | 0.00 | 0.42 |
October | 76325716.48 | 0.391449E+10 | 0.00 | 1418645.27 | 0.216498E+09 | 0.00 | 0.465923E+09 | 0.00 | 0.50 |
November | 0.455108E+09 | 0.119912E+10 | 0.00 | 2591111.72 | 61543849.73 | 0.00 | 0.134462E+10 | 0.00 | 0.65 |
December | 0.137996E+10 | 0.755129E+09 | 0.00 | 1341990.49 | 31610480.40 | 80686998.47 | 0.853372E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.653089E+10 | 0.366296E+11 | 0.00 | 9762104.83 | 0.210964E+10 | 0.367888E+09 | 0.492502E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.280614E+09 | 0.00 | 0.00 | 6170141.73 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208239E+10 | 0.633093E+10 | 0.00 | 2591111.72 | 0.404798E+09 | 0.114111E+09 | 0.134462E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384252E+10 | 0.442700E+09 | 0.00 | 1163768.25 | 21243177.03 | 93949444.26 | 0.662090E+09 | 0.00 | 0.44 |
February | 0.240259E+10 | 0.655051E+09 | 0.00 | 1483767.77 | 9773129.22 | 0.199512E+09 | 0.796298E+09 | 0.00 | 0.47 |
March | 0.198014E+10 | 0.125046E+10 | 0.00 | 1580497.20 | 14979177.65 | 0.246845E+09 | 0.952789E+09 | 0.00 | 0.47 |
April | 0.263396E+09 | 0.271923E+10 | 0.00 | 2364568.32 | 59197985.03 | 0.00 | 0.118827E+10 | 0.00 | 0.50 |
May | 0.00 | 0.912021E+10 | 0.00 | 0.00 | 0.162714E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.103750E+11 | 0.00 | 0.00 | 0.165490E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.118113E+11 | 0.00 | 0.00 | 0.283174E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.115720E+11 | 0.00 | 0.00 | 0.158047E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.925518E+10 | 0.00 | 127077.34 | 0.217401E+09 | 0.00 | 33504398.92 | 0.00 | 0.39 |
October | 80972162.46 | 0.737082E+10 | 0.00 | 2389525.95 | 0.122095E+09 | 0.00 | 0.747399E+09 | 0.00 | 0.45 |
November | 0.674854E+09 | 0.221830E+10 | 0.00 | 4228572.70 | 31546697.06 | 0.00 | 0.236585E+10 | 0.00 | 0.56 |
December | 0.262357E+10 | 0.133781E+10 | 0.00 | 1850138.87 | 30565265.57 | 0.156293E+09 | 0.128998E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.118680E+11 | 0.681281E+11 | 0.00 | 15187916.40 | 0.127623E+10 | 0.696599E+09 | 0.803618E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.442700E+09 | 0.00 | 0.00 | 9773129.22 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.384252E+10 | 0.118113E+11 | 0.00 | 4228572.70 | 0.283174E+09 | 0.246845E+09 | 0.236585E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188720E+10 | 0.217304E+09 | 0.00 | 547582.55 | 10622149.11 | 78982162.45 | 0.312215E+09 | 0.00 | 0.45 |
February | 0.115376E+10 | 0.322041E+09 | 0.00 | 719408.17 | 5209229.88 | 0.146972E+09 | 0.390555E+09 | 0.00 | 0.47 |
March | 0.101235E+10 | 0.616067E+09 | 0.00 | 737280.40 | 7280016.33 | 0.125600E+09 | 0.437392E+09 | 0.00 | 0.48 |
April | 0.134831E+09 | 0.135586E+10 | 0.00 | 1148311.54 | 29244864.67 | 0.00 | 0.598997E+09 | 0.00 | 0.51 |
May | 0.00 | 0.455245E+10 | 0.00 | 0.00 | 80232914.38 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.517748E+10 | 0.00 | 0.00 | 81787301.08 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.588762E+10 | 0.00 | 0.00 | 0.139194E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.576845E+10 | 0.00 | 0.00 | 77678449.45 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.460743E+10 | 0.00 | 68420.57 | 0.106813E+09 | 0.00 | 19758953.48 | 0.00 | 0.39 |
October | 42492570.94 | 0.367272E+10 | 0.00 | 1182512.75 | 59729662.12 | 0.00 | 0.376876E+09 | 0.00 | 0.45 |
November | 0.344168E+09 | 0.110271E+10 | 0.00 | 2086610.97 | 15333595.76 | 0.00 | 0.119521E+10 | 0.00 | 0.57 |
December | 0.131419E+10 | 0.665285E+09 | 0.00 | 874954.73 | 15342803.47 | 0.100134E+09 | 0.607384E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.588898E+10 | 0.339454E+11 | 0.00 | 7365081.68 | 0.628467E+09 | 0.451688E+09 | 0.393839E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.217304E+09 | 0.00 | 0.00 | 5209229.88 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.188720E+10 | 0.588762E+10 | 0.00 | 2086610.97 | 0.139194E+09 | 0.146972E+09 | 0.119521E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187914E+10 | 0.212223E+09 | 0.00 | 525074.55 | 12114666.50 | 86562641.44 | 0.301919E+09 | 0.00 | 0.44 |
February | 0.114127E+10 | 0.315540E+09 | 0.00 | 690052.88 | 5334723.50 | 0.161828E+09 | 0.377048E+09 | 0.00 | 0.47 |
March | 0.103130E+10 | 0.608873E+09 | 0.00 | 691359.23 | 7358227.99 | 0.127063E+09 | 0.404268E+09 | 0.00 | 0.47 |
April | 0.140969E+09 | 0.134594E+10 | 0.00 | 1109582.75 | 29279238.33 | 0.00 | 0.585507E+09 | 0.00 | 0.51 |
May | 0.00 | 0.453794E+10 | 0.00 | 0.00 | 80105776.25 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.516442E+10 | 0.00 | 0.00 | 81684773.43 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.587454E+10 | 0.00 | 0.00 | 0.139013E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.575615E+10 | 0.00 | 0.00 | 77573329.50 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.459478E+10 | 0.00 | 67745.43 | 0.106665E+09 | 0.00 | 19939008.59 | 0.00 | 0.39 |
October | 44500188.18 | 0.366230E+10 | 0.00 | 1160040.09 | 59620182.87 | 0.00 | 0.371275E+09 | 0.00 | 0.45 |
November | 0.357363E+09 | 0.109598E+10 | 0.00 | 2030068.75 | 15658375.85 | 0.00 | 0.116767E+10 | 0.00 | 0.56 |
December | 0.131216E+10 | 0.659501E+09 | 0.00 | 821743.95 | 15636601.23 | 0.113284E+09 | 0.579664E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.590670E+10 | 0.338282E+11 | 0.00 | 7095667.62 | 0.630043E+09 | 0.488738E+09 | 0.380728E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.212223E+09 | 0.00 | 0.00 | 5334723.50 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.187914E+10 | 0.587454E+10 | 0.00 | 2030068.75 | 0.139013E+09 | 0.161828E+09 | 0.116767E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183944E+10 | 0.206083E+09 | 0.00 | 471208.74 | 14341703.65 | 0.132383E+09 | 0.275747E+09 | 0.00 | 0.44 |
February | 0.110136E+10 | 0.305151E+09 | 0.00 | 616242.30 | 6168466.42 | 0.204665E+09 | 0.347130E+09 | 0.00 | 0.46 |
March | 0.104283E+10 | 0.591798E+09 | 0.00 | 606737.74 | 7959731.89 | 0.143342E+09 | 0.349562E+09 | 0.00 | 0.47 |
April | 0.164151E+09 | 0.132460E+10 | 0.00 | 1035050.29 | 30959169.54 | 0.00 | 0.545381E+09 | 0.00 | 0.50 |
May | 0.00 | 0.451864E+10 | 0.00 | 0.00 | 80018439.64 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.515383E+10 | 0.00 | 0.00 | 81685155.73 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.587063E+10 | 0.00 | 0.00 | 0.139100E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.575764E+10 | 0.00 | 0.00 | 77650926.21 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.458994E+10 | 0.00 | 67581.10 | 0.106765E+09 | 0.00 | 20141256.84 | 0.00 | 0.39 |
October | 47478170.67 | 0.365614E+10 | 0.00 | 1114639.73 | 59657805.61 | 0.00 | 0.361564E+09 | 0.00 | 0.45 |
November | 0.377269E+09 | 0.108516E+10 | 0.00 | 1930268.42 | 15849806.44 | 0.00 | 0.111992E+10 | 0.00 | 0.56 |
December | 0.130562E+10 | 0.647747E+09 | 0.00 | 710970.07 | 17002510.46 | 0.154685E+09 | 0.510122E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.587815E+10 | 0.337073E+11 | 0.00 | 6552698.39 | 0.637159E+09 | 0.635074E+09 | 0.352957E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.206083E+09 | 0.00 | 0.00 | 6168466.42 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.183944E+10 | 0.587063E+10 | 0.00 | 1930268.42 | 0.139100E+09 | 0.204665E+09 | 0.111992E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169502E+10 | 0.210239E+09 | 0.00 | 457313.65 | 12858715.48 | 0.250744E+09 | 0.282787E+09 | 0.00 | 0.45 |
February | 0.952494E+09 | 0.308980E+09 | 0.00 | 605432.03 | 7755406.91 | 0.330655E+09 | 0.352375E+09 | 0.00 | 0.48 |
March | 0.904675E+09 | 0.596286E+09 | 0.00 | 607307.27 | 10221928.67 | 0.241323E+09 | 0.360743E+09 | 0.00 | 0.48 |
April | 0.172205E+09 | 0.132935E+10 | 0.00 | 943430.71 | 32929076.03 | 0.00 | 0.558453E+09 | 0.00 | 0.51 |
May | 0.00 | 0.459321E+10 | 0.00 | 0.00 | 80230097.51 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.528232E+10 | 0.00 | 9745.93 | 82519841.50 | 0.00 | 63033.01 | 0.00 | 0.39 |
July | 0.00 | 0.604272E+10 | 0.00 | 0.00 | 0.141631E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.593506E+10 | 0.00 | 0.00 | 79296275.25 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.472868E+10 | 0.00 | 66968.72 | 0.108424E+09 | 0.00 | 19989510.47 | 0.00 | 0.39 |
October | 57866811.99 | 0.375152E+10 | 0.00 | 1060998.22 | 60724788.04 | 0.00 | 0.354027E+09 | 0.00 | 0.46 |
November | 0.371482E+09 | 0.110738E+10 | 0.00 | 1894876.30 | 15811119.50 | 0.00 | 0.114617E+10 | 0.00 | 0.59 |
December | 0.114224E+10 | 0.637580E+09 | 0.00 | 687990.10 | 14743103.63 | 0.329945E+09 | 0.476614E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.529598E+10 | 0.345233E+11 | 0.00 | 6334062.92 | 0.647145E+09 | 0.115267E+10 | 0.355122E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.210239E+09 | 0.00 | 0.00 | 7755406.91 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.169502E+10 | 0.604272E+10 | 0.00 | 1894876.30 | 0.141631E+09 | 0.330655E+09 | 0.114617E+10 | 0.00 | 0.59 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.205781E+12 | 0.149082E+11 | 0.00 | 0.287407E+11 | 0.298342E+11 |
February | 0.229669E+12 | 0.858340E+10 | 0.00 | 0.200829E+11 | 0.411104E+11 |
March | 0.262709E+12 | 0.505624E+10 | 0.00 | 0.141528E+11 | 0.582507E+11 |
April | 0.308377E+12 | -0.903002E+10 | 0.00 | -0.753837E+10 | 0.105517E+12 |
May | 0.314857E+12 | -0.368071E+11 | 0.00 | -0.624439E+11 | 0.232168E+12 |
June | 0.317193E+12 | -0.399618E+11 | 0.00 | -0.704087E+11 | 0.248994E+12 |
July | 0.326192E+12 | -0.468372E+11 | 0.00 | -0.818617E+11 | 0.277254E+12 |
August | 0.302025E+12 | -0.458418E+11 | 0.00 | -0.784024E+11 | 0.278297E+12 |
September | 0.253773E+12 | -0.390404E+11 | 0.00 | -0.641484E+11 | 0.241467E+12 |
October | 0.255648E+12 | -0.290679E+11 | 0.00 | -0.441100E+11 | 0.207656E+12 |
November | 0.187729E+12 | -0.177407E+10 | 0.00 | 0.757688E+10 | 0.841795E+11 |
December | 0.186222E+12 | 0.865183E+10 | 0.00 | 0.201234E+11 | 0.546023E+11 |
Annual Sum or Average | 0.315018E+13 | -0.211160E+12 | 0.00 | -0.318237E+12 | 0.185933E+13 |
Minimum of Months | 0.186222E+12 | -0.468372E+11 | 0.00 | -0.818617E+11 | 0.298342E+11 |
Maximum of Months | 0.326192E+12 | 0.149082E+11 | 0.00 | 0.287407E+11 | 0.278297E+12 |