Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 09:02:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9447.17 | 832.70 | 832.70 |
Net Site Energy | 9447.17 | 832.70 | 832.70 |
Total Source Energy | 21252.20 | 1873.22 | 1873.22 |
Net Source Energy | 21252.20 | 1873.22 | 1873.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1093.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 758.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 603.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 567.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 94.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 506.37 | 1278.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5286.35 | 4160.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1093.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 758.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 603.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 567.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 94.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 1278.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 415.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1093.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 758.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 603.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 567.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 94.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 168.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 506.37 | 1278.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.85 | 209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 227.58 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.95 | 366.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.85 | 209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 227.58 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.95 | 366.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5286.351 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5286.351 | 100.00 |
Total On-Site and Utility Electric Sources | 5286.351 | 100.00 |
Total Electricity End Uses | 5286.351 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 63.91 | 1.81 |
Air to Air Heat Recovery for Heating | 3469.72 | 98.19 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3533.64 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 56.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7392.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-18:19 | 21-DEC-19:10 | - | - | - | - | - | - | - | - | - | - | 20-APR-20:40 |
Heating | 0.00 | 290988.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 162335.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 40755.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 78653.57 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31364.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36943.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4249.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 40393.69 | 130980.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1667.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 406303.07 | 509588.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 290988.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 162335.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 40755.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 48978.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1060.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 36943.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4249.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4603.95 | 130980.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 788.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 651.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1185.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2402.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1909.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 551.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1797.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 299.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 534.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1603.68 | 1385.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16741.87 | 4510.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 104.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 141.35 | 122.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1475.67 | 397.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 104.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 141.35 | 122.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1475.67 | 397.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.47 | 0.609887 | 0.456000 | 1.13 | 1.00 | 0.500000 | 0.000625 | 0.000051 | 1.13 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.434071 | 0.117742 | 0.456000 | 0.197936 | 0.456000 | 0.500000 | 0.003236 | 0.000034 | 0.197936 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.265600 | 0.222830 | 0.456000 | 0.121114 | 0.594214 | 0.500000 | 0.001710 | 0.000013 | 0.121114 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.217502 | 0.575412 | 0.456000 | 0.099181 | 1.00 | 0.500000 | 0.000662 | 0.000020 | 0.099181 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.118203 | 0.610868 | 0.456000 | 0.053901 | 1.00 | 0.500000 | 0.000624 | 0.000013 | 0.064273 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.01 | 0.058872 | 0.456000 | 1.83 | 0.456000 | 0.500000 | 0.025681 | 0.000089 | 1.83 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.86 | 0.077554 | 0.456000 | 0.846179 | 0.456000 | 0.500000 | 0.004913 | 0.000099 | 0.846179 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.73 | 0.174023 | 0.456000 | 2.61 | 0.464062 | 0.500000 | 0.002189 | 0.000256 | 2.61 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.50 | 0.789149 | 0.456000 | 0.685838 | 1.00 | 0.500000 | 0.000483 | 0.000122 | 0.685838 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.65 | 0.095455 | 0.456000 | 1.21 | 0.456000 | 0.500000 | 0.003991 | 0.000108 | 1.21 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.78 | 0.090953 | 0.456000 | 1.27 | 0.456000 | 0.500000 | 0.004189 | 0.000112 | 1.27 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.69 | 0.052731 | 0.456000 | 1.22 | 0.456000 | 0.500000 | 0.012996 | 0.000075 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.886253 | 0.354345 | 0.456000 | 0.404131 | 0.944919 | 0.500000 | 0.001075 | 0.000082 | 0.404131 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5856.70 | 0.000051 | 123.49 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3895.76 | 0.000034 | 100.36 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1525.58 | 0.000013 | 35.41 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2274.16 | 0.000020 | 61.76 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1492.55 | 0.000013 | 40.73 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10224.23 | 0.000089 | 216.64 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11349.34 | 0.000099 | 266.45 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29280.56 | 0.000256 | 666.94 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6833.80 | 0.000060 | 195.25 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6839.12 | 0.000060 | 195.40 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 39380.27 | 0.000345 | 1125.13 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 39495.42 | 0.000346 | 1128.42 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6833.80 | 0.000060 | 195.25 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6839.12 | 0.000060 | 195.40 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13920.85 | 0.000122 | 362.12 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2146.83 | 0.000019 | 61.34 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2146.73 | 0.000019 | 61.33 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10327.44 | 0.000090 | 295.06 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12354.15 | 0.000108 | 277.74 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12774.02 | 0.000112 | 286.61 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8616.00 | 0.000075 | 185.88 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9319.97 | 0.000082 | 253.67 |
VAV WITH REHEAT HEATING COIL | 259564.70 | 0.002271 | 4026.65 |
FLR_3_DOAS HEATING COIL | 20913.38 | 0.000183 | 324.43 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.39 | 0.000060 | 0.000452 |
ROOM_2_FLR_3 FAN COIL | 1.35 | 0.000060 | 0.000441 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.43 | 0.000345 | 0.002386 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.67 | 0.000346 | 0.002289 |
ROOM_5_FLR_3 FAN COIL | 1.21 | 0.000060 | 0.000396 |
ROOM_6_FLR_3 FAN COIL | 1.18 | 0.000060 | 0.000387 |
ROOM_1_FLR_6 FAN COIL | 0.370530 | 0.000019 | 0.000121 |
ROOM_2_FLR_6 FAN COIL | 0.360088 | 0.000019 | 0.000117 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.59 | 0.000090 | 0.000527 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.39 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.35 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.43 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.67 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.21 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.18 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.370530 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.360088 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.59 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008554 | 12.80 | 0.008500 | 0.000452 | 1.39 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008555 | 12.80 | 0.008500 | 0.000441 | 1.35 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008488 | 12.80 | 0.008488 | 0.002386 | 7.43 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008745 | 12.80 | 0.008500 | 0.002289 | 6.67 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008561 | 12.80 | 0.008500 | 0.000396 | 1.21 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008563 | 12.80 | 0.008500 | 0.000387 | 1.18 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008550 | 12.80 | 0.008500 | 0.000121 | 0.370530 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008552 | 12.80 | 0.008500 | 0.000117 | 0.360088 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008617 | 12.80 | 0.008500 | 0.000527 | 1.59 | |
VAV WITH REHEAT COOLING COIL | 28.53 | 6.70 | 0.007766 | 10.55 | 0.007766 | 0.016288 | 25.46 | 456017.42 |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.005475 | 11.72 | 0.005475 | 0.001612 | 2.05 | 45136.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.80 | 11.67 | 25.60 | 11.67 | 25.46 | 25.46 | 0.300000 | 0.458534 | 25.46 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 25.46 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 25.46 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016288 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002271 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001612 | 0.000295 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000183 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025015 | 5103.62 | |
HEATSYS1 PUMP | 0.004586 | 1367.42 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004586 | 0.550316 |
COOLSYS1 | 0.025015 | 3.00 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 524204.46 | 524204.46 | 0.004586 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025015 | 3533.41 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025015 | 700352.10 | 701033.47 | 79.92 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.048 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17638513E-14 | 0.32473881E-16 | -0.15472737E-09 | 0.39084990E-16 |
29 | 8 | 0.22578286E-07 | 0.11136169E-12 | 0.38514655E-03 | -0.25672286E-09 |
30 | 7 | -0.12460867E-01 | 0.57383191E-08 | -0.23401545E-01 | 0.14168460E-03 |
31 | 6 | 0.41130930 | 0.19934685E-05 | 0.47716306 | -0.48180040E-02 |
32 | 5 | -5.2487139 | 0.74343025E-04 | -4.4802041 | 0.63904887E-01 |
33 | 4 | 33.260058 | 0.60748543E-03 | 21.592533 | -0.42553784 |
34 | 3 | -111.77343 | 0.13226915E-02 | -55.924898 | 1.5231004 |
35 | 2 | 197.67353 | 0.74337769E-03 | 78.150831 | -2.9093300 |
36 | 1 | -171.36487 | 0.79295509E-04 | -55.335031 | 2.7490988 |
37 | 0 | 57.057407 | 0.45097929E-06 | 15.545453 | |
38 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
39 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
40 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
41 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
42 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
43 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
44 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
45 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
46 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
47 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
48 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
49 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
50 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
51 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
52 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
53 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
54 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
55 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
56 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
57 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
58 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
59 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
60 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
61 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
62 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
63 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
64 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
65 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
66 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
67 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
68 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
69 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
70 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
71 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
72 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
73 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
74 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
75 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
76 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
77 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3672_SHGC_0.38 | 37 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.3672_SHGC_0.38 | 38 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.29373 | 0.49994 | 0.49994 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.29373 | 0.49994 | 0.49994 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 71719.3 | 48.891 | 1.6513 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 59494.4 | 4.605 | 9.4770 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 49203.460 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1388 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.2113E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1561 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.1531E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.9208E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9051E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.9974E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3280E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1581 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.7051E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1784 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.8164E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1098 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.8842E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.4888E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8161E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.4050E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9656E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6106E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4795E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5212E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0083E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9348E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3953E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.4050E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9656E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6106E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4795E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5212E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0083E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9348E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3953E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 27620.26604 | 27620.26604 | 2.47237 | 2.47237 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 26.77133 | 5.46440E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1025.45500 | 1025.45500 | 5.41497E-002 | 0.85446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4848.82133 | 4848.82133 | 0.43407 | 0.43407 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3047.70774 | 3047.70774 | 0.16093 | 0.16093 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2966.81304 | 2966.81304 | 0.26560 | 0.26560 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 32.61733 | 5.47329E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1006.66519 | 1006.66519 | 5.31571E-002 | 9.17347E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2430.14355 | 2430.14355 | 0.21750 | 0.21750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 26.50000 | 5.46399E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1849.24609 | 1849.24609 | 9.76495E-002 | 9.76495E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1320.66714 | 1320.66714 | 0.11820 | 0.11820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.34800 | 5.46981E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1217.17455 | 1217.17455 | 6.42730E-002 | 6.42730E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44779.44808 | 44779.44808 | 4.00822 | 4.00822 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2394.38346 | 2394.38346 | 0.12643 | 0.12643 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20709.80448 | 20709.80448 | 1.85566 | 1.85566 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7723.75428 | 7723.75428 | 0.40785 | 0.67639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63965.20075 | 63965.20075 | 5.72818 | 5.72818 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 18088.82417 | 18088.82417 | 0.95518 | 1.89399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11499.43905 | 11499.43905 | 1.38701 | 1.38701 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6833.80332 | 6833.80332 | 0.36297 | 0.36297 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11202.84064 | 11202.84064 | 1.35123 | 1.35123 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6839.11997 | 6839.11997 | 0.36326 | 0.36326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 61567.23947 | 61567.23947 | 7.42562 | 7.42562 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 39380.26990 | 39380.26990 | 2.09169 | 2.09169 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 55336.22638 | 55336.22638 | 6.67468 | 6.67468 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.23800 | 5.46812E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 39495.42030 | 39495.42030 | 2.09781 | 2.09781 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10041.27591 | 10041.27591 | 1.21113 | 1.21113 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.43733 | 5.46540E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6833.80332 | 6833.80332 | 0.36297 | 0.36297 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9809.04762 | 9809.04762 | 1.18312 | 1.18312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6839.11997 | 6839.11997 | 0.36326 | 0.36326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16802.88830 | 16802.88830 | 1.50403 | 1.50403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90000 | 5.47527E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10982.01918 | 10982.01918 | 0.57991 | 0.57991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3072.00127 | 3072.00127 | 0.37053 | 0.37053 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2146.82502 | 2146.82502 | 0.11403 | 0.11403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2985.42854 | 2985.42854 | 0.36009 | 0.36009 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2146.72556 | 2146.72556 | 0.11402 | 0.11402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13167.10330 | 13167.10330 | 1.58820 | 1.58820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 10327.43638 | 10327.43638 | 0.54854 | 0.54854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29538.03292 | 29538.03292 | 2.64756 | 2.64756 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7180.82229 | 7180.82229 | 0.37918 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31000.59254 | 31000.59254 | 2.77860 | 2.77860 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7344.62021 | 7344.62021 | 0.38783 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29912.14307 | 29912.14307 | 2.68501 | 2.68501 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3374.19007 | 3374.19007 | 0.17816 | 0.36735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9901.26152 | 9901.26152 | 0.88625 | 0.88625 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.47527E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7588.16967 | 7588.16967 | 0.40070 | 0.40070 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 393219.00 | 25.45976 | 25.45976 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 261314.22 | 7.68941 | 7.68941 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42510.28 | 20.04304 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69708.81 | 6.41855 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47237 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60989 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.12740 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.24706E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.12370E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12740 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5856.69860 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.12370E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 123.49010 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.43407 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11774 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19794 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23589E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.40818E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19794 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3895.75585 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.40818E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 100.35784 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26560 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22283 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12111 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59421 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70982E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33465E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12111 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1525.58402 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33465E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 35.41260 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21750 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57541 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.91810E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.62134E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98953E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.91810E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2274.15991 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98953E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 61.76093 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11820 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61087 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.39007E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.23703E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30574E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.42730E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1492.54589 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30574E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.73474 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.00822 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.88724E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.82775 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56807E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.94461E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82775 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10224.23311 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.94461E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.64084 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85566 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.75535E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84618 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.91273E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.92889E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84618 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11349.33654 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.92889E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 266.45423 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.72818 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17402 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.61205 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46406 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18936E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.56159E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61205 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29280.55682 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56159E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 666.93521 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38701 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.38701 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.97851E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52184E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81592 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55366E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52184E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.38701 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6833.80332 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97851E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.24795 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.35123 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.35123 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.98316E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.40681E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81592 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55499E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.40681E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.35123 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6839.11997 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.98316E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.39984 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.42562 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.42562 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.44516E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.38557E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81637 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48840E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48840E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.38557E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.42562 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 39380.26990 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44516E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1125.12668 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.67468 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.67468 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.45523E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.28945E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81532 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74541E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.28945E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.67468 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 39495.42030 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.45523E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1128.41643 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21113 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21113 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.97851E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.95661E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81591 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56125E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.95661E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21113 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6833.80332 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97851E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.24795 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18312 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.18312 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.98316E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.86643E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81591 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56252E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86643E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.18312 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6839.11997 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.98316E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.39984 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50403 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78915 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68584 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.82798E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21786E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68584 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13920.84593 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21786E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.12288 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.37053 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.37053 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.87814E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.20687E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81593 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55028E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.20687E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.37053 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2146.82502 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87814E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 61.33584 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.36009 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.36009 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.87805E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.17330E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81593 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55166E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.17330E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.36009 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2146.72556 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87805E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 61.33300 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.58820 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.58820 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.03489E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.26683E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81559 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61700E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.26683E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.58820 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 10327.43638 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.03489E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 295.05950 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64756 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.54550E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20729 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99141E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08080E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20729 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12354.15480 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08080E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.74328 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.77860 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.09534E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.26704 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18896E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11753E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.26704 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12774.02046 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11753E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 286.60783 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.68501 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.27314E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22436 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45600 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29956E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.53765E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22436 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8616.00079 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.53765E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 185.87953 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88625 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35434 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45600 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40413 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94492 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07522E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.15352E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40413 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9319.96861 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.15352E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 253.67375 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.80063 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67418 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.60126 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67418 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.45976 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 25.45976 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45853 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 25.45976 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.45976 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.52920 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.55099 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.76551E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.76551E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 456017.41974 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62879E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 25.45976 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 259564.69825 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27079E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4026.65480 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 25.45976 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62879E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.92359E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27079E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.72145 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45136.60304 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61217E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20913.37763 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82959E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.43145 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.61217E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.95371E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82959E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.50150E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5103.61872 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.58597E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.55032 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.58597E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1367.41838 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 524204.46097 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 524204.46000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.58597E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.50150E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.00179 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.50150E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3533.40738 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.50150E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 700352.09569 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 701033.47000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 79.91782 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5887.31 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3913.19 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1533.02 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2284.03 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1499.01 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10277.52 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11404.35 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29424.90 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7363.13 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7368.86 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 42430.58 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 42554.65 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7363.13 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7368.86 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13982.76 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2313.09 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2312.99 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11127.28 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12415.54 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12837.57 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8660.47 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9360.38 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 170904.16 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 13769.91 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 23816.76 | 17189.63 | 6627.13 | 0.72 | 5845.83 | 59.29 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 23207.98 | 16748.00 | 6459.98 | 0.72 | 5692.73 | 57.74 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 126413.01 | 91699.98 | 34713.04 | 0.73 | 32217.44 | 326.77 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 118458.07 | 83938.03 | 34520.04 | 0.71 | 26839.94 | 272.23 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 20824.81 | 15018.75 | 5806.06 | 0.72 | 5092.80 | 51.65 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 20347.78 | 14672.85 | 5674.93 | 0.72 | 4973.12 | 50.44 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6358.66 | 4590.90 | 1767.76 | 0.72 | 1563.30 | 15.86 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6180.99 | 4462.00 | 1718.99 | 0.72 | 1518.60 | 15.40 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27579.37 | 19780.16 | 7799.21 | 0.72 | 6580.14 | 66.74 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 703707.12 | 410621.66 | 293085.46 | 0.58 | 175666.22 | 1781.70 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 46146.10 | 28462.74 | 17683.36 | 0.62 | 4499.01 | 45.63 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6532368106E-002 | 2.4846528439E-002 | Pass | Pass | 6.5845944988E-003 | 1.4835222992E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7628615629E-002 | 9.6060312876E-002 | Pass | Pass | 3.2725761241E-002 | 3.8020136441E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6217812223E-002 | 2.8404447412E-002 | Pass | Pass | 7.5085218688E-003 | 1.4432770785E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3355758369E-002 | 1.4589856551E-002 | Pass | Pass | 8.2941872836E-003 | 1.8371650175E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0380373802E-002 | 9.1561840876E-003 | Pass | Pass | 9.7962810289E-003 | 1.9002800781E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3541941058E-002 | 0.1392525993 | Pass | Pass | 1.9824057746E-002 | 5.3589898710E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.2768633586E-002 | 7.6617463516E-002 | Pass | Pass | 1.7828487093E-002 | 2.4474743029E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3193528874E-002 | 4.0004834430E-002 | Pass | Pass | 1.1733337353E-002 | 2.1926199261E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8193557311E-002 | 0.1976309310 | Pass | Pass | 0.1556982868 | 0.4310990270 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.8185517675E-002 | 0.2137103480 | Pass | Pass | 0.1815023407 | 0.7977160347 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2597244311E-002 | 2.9611610381E-002 | Pass | Pass | 0.1030285966 | 0.5021754217 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0571927886E-002 | 6.2416524702E-002 | Pass | Pass | 0.7518573596 | 6.8801741539 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4999491952E-002 | 0.2748200923 | Pass | Pass | 0.4071333113 | 1.7483527534 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.0968491770E-002 | 0.2000490411 | Pass | Pass | 9.5052075305E-002 | 0.3158331340 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4573315543E-002 | 1.4062583938E-002 | Pass | Pass | 8.3494900993E-003 | 1.6652256855E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6349959270E-002 | 0.1838892775 | Pass | Pass | 1.6945094572 | 18.9638266342 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1010317052 | 0.2851972706 | Pass | Pass | 8.3822087562E-002 | 0.2652181369 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1303530041E-002 | 0.3154120070 | Pass | Pass | 0.1622187304 | 0.3729445443 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5552029848E-002 | 6.2305385044E-002 | Pass | Pass | 1.5284728682E-002 | 4.5056809287E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6216315459E-002 | 4.2398350762E-002 | Pass | Pass | 1.5745613994E-002 | 4.4190542742E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1110676437E-002 | 5.9263356191E-002 | Pass | Pass | 2.1980431931E-002 | 4.3634235063E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8292485171E-002 | 2.3949192260E-002 | Pass | Pass | 3.0763050349E-002 | 3.7358154374E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4775.26 | 36.83 | 1517.59 | 8042.73 | 3615.95 | 17988.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.086 | 0.381 | 0.381 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.086 | 0.381 | 0.381 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.086 | 0.381 | 0.381 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.086 | 0.381 | 0.381 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.086 | 0.381 | 0.381 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.086 | 0.381 | 0.381 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.381 | 0.381 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.381 | 0.381 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.086 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 432.95 | 2.086 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.086 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.11 | 0.0000 | Y | 12.84 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.28 | 0.0000 | Y | 122.74 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.00 | 0.0000 | Y | 28.24 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.00 | 0.0000 | Y | 28.24 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 388.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.67 | 83.67 | 174.28 | |
Exterior Lighting Total | 11096.45 | 174.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 524204.46 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 701033.47 | 2.96 | 701156.69 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12660.18 | 23816.76 | 17189.63 | 6627.13 | 0.72 | - | 5845.83 | 59.29 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12338.12 | 23207.98 | 16748.00 | 6459.98 | 0.72 | - | 5692.73 | 57.74 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 66790.87 | 126413.01 | 91699.98 | 34713.04 | 0.73 | - | 32217.44 | 326.77 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64099.82 | 118458.07 | 83938.03 | 34520.04 | 0.71 | - | 26839.94 | 272.23 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11077.65 | 20824.81 | 15018.75 | 5806.06 | 0.72 | - | 5092.80 | 51.65 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10825.18 | 20347.78 | 14672.85 | 5674.93 | 0.72 | - | 4973.12 | 50.44 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3378.98 | 6358.66 | 4590.90 | 1767.76 | 0.72 | - | 1563.30 | 15.86 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3284.99 | 6180.99 | 4462.00 | 1718.99 | 0.72 | - | 1518.60 | 15.40 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14746.00 | 27579.37 | 19780.16 | 7799.21 | 0.72 | - | 6580.14 | 66.74 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 456017.42 | 703707.12 | 410621.66 | 293085.46 | 0.58 | - | 175666.22 | 1781.70 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45136.60 | 46146.10 | 28462.74 | 17683.36 | 0.62 | - | 4499.01 | 45.63 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5856.70 | 5887.31 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3895.76 | 3913.19 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1525.58 | 1533.02 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2274.16 | 2284.03 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1492.55 | 1499.01 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10224.23 | 10277.52 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11349.34 | 11404.35 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29280.56 | 29424.90 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6833.80 | 7363.13 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6839.12 | 7368.86 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 39380.27 | 42430.58 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 39495.42 | 42554.65 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6833.80 | 7363.13 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6839.12 | 7368.86 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13920.85 | 13982.76 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2146.83 | 2313.09 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2146.73 | 2312.99 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 10327.44 | 11127.28 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12354.15 | 12415.54 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12774.02 | 12837.57 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8616.00 | 8660.47 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9319.97 | 9360.38 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 259564.70 | 170904.16 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20913.38 | 13769.91 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.39 | 975.95 | 703.64 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.35 | 950.78 | 703.64 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.43 | 5224.93 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.67 | 4696.55 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.21 | 852.20 | 703.64 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 832.49 | 703.64 | 1.00 | 1.16 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.37 | 260.72 | 703.64 | 1.00 | 1.58 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.36 | 253.37 | 703.64 | 1.00 | 1.60 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.59 | 1117.52 | 703.64 | 1.00 | 1.10 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 25.46 | 57046.12 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025015 | 5103.62 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004586 | 1367.42 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025015 | 3533.41 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 71719.34 | 0.80 | 48.89 | 1.65 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 59494.48 | 0.80 | 4.61 | 9.48 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 27620.27 | 27620.27 | 13.96 | 2.472 | 2.472 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 24.00 | 24.00 | 0.00937 | 26.77 | 0.00546 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4848.82 | 4848.82 | 72.29 | 0.434 | 0.434 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00899 | 33.41 | 0.00547 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2966.81 | 2966.81 | 38.20 | 0.266 | 0.266 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00944 | 32.62 | 0.00547 | 0.092 | 0.00 |
MECH_FLR_1 | 2430.14 | 2430.14 | 14.80 | 0.218 | 0.218 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00872 | 26.50 | 0.00546 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1320.67 | 1320.67 | 13.94 | 0.118 | 0.118 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00882 | 30.35 | 0.00547 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44779.45 | 44779.45 | 573.81 | 4.008 | 4.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00854 | 33.90 | 0.00548 | 0.000 | 0.00 |
CAFE_FLR_1 | 20709.80 | 20709.80 | 109.66 | 1.856 | 1.856 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01004 | 33.41 | 0.00547 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63965.20 | 63965.20 | 48.90 | 5.728 | 5.728 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00998 | 33.53 | 0.00547 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11499.44 | 11499.44 | 294.69 | 1.387 | 1.387 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00855 | 32.03 | 0.00547 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11202.84 | 11202.84 | 287.12 | 1.351 | 1.351 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00855 | 31.83 | 0.00547 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 61567.24 | 61567.24 | 2510.51 | 7.426 | 7.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00849 | 33.53 | 0.00547 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 55336.23 | 55336.23 | 2255.81 | 6.675 | 6.675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 21.11 | 21.11 | 0.00875 | 29.24 | 0.00547 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10041.28 | 10041.28 | 257.32 | 1.211 | 1.211 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00856 | 27.44 | 0.00547 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9809.05 | 9809.05 | 251.40 | 1.183 | 1.183 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00856 | 26.18 | 0.00546 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16802.89 | 16802.89 | 43.15 | 1.504 | 1.504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00962 | 33.90 | 0.00548 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3072.00 | 3072.00 | 78.72 | 0.371 | 0.371 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00855 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2985.43 | 2985.43 | 76.52 | 0.360 | 0.360 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00855 | 31.83 | 0.00547 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13167.10 | 13167.10 | 536.76 | 1.588 | 1.588 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00862 | 33.65 | 0.00547 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29538.03 | 29538.03 | 89.06 | 2.648 | 2.648 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01041 | 33.90 | 0.00548 | 1.188 | 0.00 |
DINING_FLR_6 | 31000.59 | 31000.59 | 93.47 | 2.779 | 2.779 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01032 | 33.90 | 0.00548 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29912.14 | 29912.14 | 289.55 | 2.685 | 2.685 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 32.57 | 0.00547 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9901.26 | 9901.26 | 24.02 | 0.886 | 0.886 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00900 | 33.90 | 0.00548 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1025.45 | 1025.45 | 0.52 | 0.054 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3047.71 | 3047.71 | 45.44 | 0.161 | 0.161 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1006.67 | 1006.67 | 12.96 | 0.053 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -17.90 | 0.00096 | 0.092 | 0.00 |
MECH_FLR_1 | 1849.25 | 1849.25 | 11.26 | 0.098 | 0.098 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1217.17 | 1217.17 | 12.84 | 0.064 | 0.064 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2394.38 | 2394.38 | 30.68 | 0.126 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 7723.75 | 7723.75 | 40.90 | 0.408 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 18088.82 | 18088.82 | 13.83 | 0.955 | 1.894 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6833.80 | 6833.80 | 175.13 | 0.363 | 0.363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6839.12 | 6839.12 | 175.28 | 0.363 | 0.363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 39380.27 | 39380.27 | 1605.80 | 2.092 | 2.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 39495.42 | 39495.42 | 1610.05 | 2.098 | 2.098 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6833.80 | 6833.80 | 175.13 | 0.363 | 0.363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6839.12 | 6839.12 | 175.28 | 0.363 | 0.363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -17.90 | 0.00096 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10982.02 | 10982.02 | 28.20 | 0.580 | 0.580 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2146.83 | 2146.83 | 55.02 | 0.114 | 0.114 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2146.73 | 2146.73 | 55.02 | 0.114 | 0.114 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10327.44 | 10327.44 | 421.00 | 0.549 | 0.549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7180.82 | 7180.82 | 21.65 | 0.379 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 1.188 | 0.00 |
DINING_FLR_6 | 7344.62 | 7344.62 | 22.15 | 0.388 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3374.19 | 3374.19 | 32.66 | 0.178 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00760 | -17.90 | 0.00096 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7588.17 | 7588.17 | 18.41 | 0.401 | 0.401 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 21.00 | 21.00 | 0.00794 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 25.46 | 25.46 | 7.69 | 7.69 | 25.4598 | 11.6742 | 25.4598 | 0.4585 | 0.3000 |
FLR_3_DOAS | 20.04 | 2.05 | 6.42 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5856.699 | 5856.699 | 1.127402 | 0.00005124 | 123.490 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5856.70 | 5856.70 | 1.127402 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00793171 | 41.6258 | 1025.45 | 0.00 | 5889.49 | 5889.49 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3895.756 | 3895.756 | 0.197936 | 0.00003408 | 100.358 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3895.76 | 3895.76 | 0.197936 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787910 | 41.3543 | 3047.71 | 0.00 | 3915.43 | 3915.43 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1525.584 | 1525.584 | 0.121114 | 0.00001335 | 35.413 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1525.58 | 1525.58 | 0.121114 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785912 | 41.2500 | 1006.67 | 0.00 | 1533.74 | 1533.74 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2274.160 | 2274.160 | 0.099181 | 0.00001990 | 61.761 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2274.16 | 2274.16 | 0.099181 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00781978 | 41.0462 | 1849.25 | 0.00 | 2285.45 | 2285.45 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1492.546 | 1492.546 | 0.064273 | 0.00001306 | 40.735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1492.55 | 1492.55 | 0.064273 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784153 | 41.1589 | 1217.17 | 0.00 | 1499.95 | 1499.95 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10224.233 | 10224.233 | 1.827750 | 0.00008945 | 216.641 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10224.23 | 10224.23 | 1.827750 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00781021 | 40.9973 | 2394.38 | 0.00 | 10281.38 | 10281.38 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11349.337 | 11349.337 | 0.846179 | 0.00009929 | 266.454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11349.34 | 11349.34 | 0.846179 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789431 | 41.4329 | 7723.75 | 0.00 | 11409.82 | 11409.82 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29280.557 | 29280.557 | 2.612051 | 0.00025616 | 666.935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 29280.56 | 29280.56 | 2.612051 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787148 | 41.3141 | 18088.82 | 0.00 | 29438.13 | 29438.13 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12660.185 | -999.000 | 1.387007 | 0.00045218 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12660.18 | 12534.56 | 1.387007 | 21.82 | 13.55 | 0.00855366 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00855366 | 44.5416 | 11499.44 | 0.00 | 15925.38 | 14765.59 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6833.803 | 6833.803 | 0.362974 | 0.00005979 | 195.248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6833.80 | 6833.80 | 0.362974 | 21.11 | 12.73 | 0.00787561 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00787561 | 41.0553 | 6833.80 | 0.00 | 7367.03 | 7367.03 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12338.119 | -999.000 | 1.351233 | 0.00044068 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12338.12 | 12212.68 | 1.351233 | 21.82 | 13.56 | 0.00855499 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00855499 | 44.5485 | 11202.84 | 0.00 | 15519.53 | 14384.90 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6839.120 | 6839.120 | 0.363257 | 0.00005983 | 195.400 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6839.12 | 6839.12 | 0.363257 | 21.11 | 12.73 | 0.00787571 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00787571 | 41.0559 | 6839.12 | 0.00 | 7372.76 | 7372.76 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 66790.869 | -999.000 | 7.425616 | 0.00238557 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 66790.87 | 66790.87 | 7.425616 | 21.82 | 13.50 | 0.00848840 | 12.80 | 10.20 | 0.00848840 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00848840 | 44.2054 | 61567.24 | 0.00 | 84197.85 | 79127.65 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 39380.270 | 39380.270 | 2.091693 | 0.00034452 | 1125.127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39380.27 | 39380.27 | 2.091693 | 21.11 | 12.74 | 0.00788540 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00788540 | 41.1051 | 39380.27 | 0.00 | 42453.19 | 42453.19 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64099.820 | -999.000 | 6.674677 | 0.00228945 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | unknown | 7/21 18:30:00 | 64099.82 | 61290.35 | 6.674677 | 21.82 | 13.71 | 0.00874541 | 12.80 | 10.21 | 0.00850000 | 29.24 | 0.00546812 | 13.51 | 0.0000 | 21.11 | 0.00874541 | 45.5273 | 55336.23 | 0.00 | 80136.89 | 71175.51 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 39495.420 | 39495.420 | 2.097809 | 0.00034552 | 1128.416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39495.42 | 39495.42 | 2.097809 | 21.11 | 12.74 | 0.00788570 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00788570 | 41.1067 | 39495.42 | 0.00 | 42577.33 | 42577.33 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11077.649 | -999.000 | 1.211131 | 0.00039566 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11077.65 | 10952.36 | 1.211131 | 21.82 | 13.56 | 0.00856125 | 12.80 | 10.21 | 0.00850000 | 27.44 | 0.00546540 | 12.88 | 0.0000 | 21.11 | 0.00856125 | 44.5806 | 10041.28 | 0.00 | 13931.02 | 12894.04 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6833.803 | 6833.803 | 0.362974 | 0.00005979 | 195.248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6833.80 | 6833.80 | 0.362974 | 21.11 | 12.73 | 0.00787561 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00787561 | 41.0553 | 6833.80 | 0.00 | 7367.03 | 7367.03 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10825.183 | -999.000 | 1.183121 | 0.00038664 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 10825.18 | 10700.24 | 1.183121 | 21.82 | 13.56 | 0.00856252 | 12.80 | 10.21 | 0.00850000 | 26.18 | 0.00546350 | 12.44 | 0.0000 | 21.11 | 0.00856252 | 44.5871 | 9809.05 | 0.00 | 13612.92 | 12595.96 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6839.120 | 6839.120 | 0.363257 | 0.00005983 | 195.400 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6839.12 | 6839.12 | 0.363257 | 21.11 | 12.73 | 0.00787571 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00787571 | 41.0559 | 6839.12 | 0.00 | 7372.76 | 7372.76 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13920.846 | 13920.846 | 0.685838 | 0.00012179 | 362.123 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13920.85 | 13920.85 | 0.685838 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790544 | 41.4899 | 10982.02 | 0.00 | 13990.88 | 13990.88 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3378.978 | -999.000 | 0.370530 | 0.00012069 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3378.98 | 3347.54 | 0.370530 | 21.82 | 13.55 | 0.00855028 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00855028 | 44.5243 | 3072.00 | 0.00 | 4250.95 | 3944.43 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2146.825 | 2146.825 | 0.114028 | 0.00001878 | 61.336 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2146.83 | 2146.83 | 0.114028 | 21.11 | 12.76 | 0.00790063 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00790063 | 41.1841 | 2146.83 | 0.00 | 2314.34 | 2314.34 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3284.989 | -999.000 | 0.360088 | 0.00011733 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3284.99 | 3253.59 | 0.360088 | 21.82 | 13.55 | 0.00855166 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00855166 | 44.5314 | 2985.43 | 0.00 | 4132.51 | 3833.31 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2146.726 | 2146.726 | 0.114022 | 0.00001878 | 61.333 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2146.73 | 2146.73 | 0.114022 | 21.11 | 12.76 | 0.00790063 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00790063 | 41.1841 | 2146.73 | 0.00 | 2314.23 | 2314.23 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14746.002 | -999.000 | 1.588201 | 0.00052668 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 14746.00 | 14430.64 | 1.588201 | 21.82 | 13.61 | 0.00861700 | 12.80 | 10.21 | 0.00850000 | 33.65 | 0.00547489 | 14.99 | 0.0000 | 21.11 | 0.00861700 | 44.8677 | 13167.10 | 0.00 | 18511.39 | 16916.85 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 10327.436 | 10327.436 | 0.548540 | 0.00009035 | 295.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10327.44 | 10327.44 | 0.548540 | 21.11 | 12.76 | 0.00790482 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00790482 | 41.2055 | 10327.44 | 0.00 | 11133.28 | 11133.28 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12354.155 | 12354.155 | 1.207288 | 0.00010808 | 277.743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | 12354.15 | 12354.15 | 1.207288 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00792676 | 41.6006 | 7180.82 | 0.00 | 12420.96 | 12420.96 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12774.020 | 12774.020 | 1.267042 | 0.00011175 | 286.608 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 12774.02 | 12774.02 | 1.267042 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00792837 | 41.6090 | 7344.62 | 0.00 | 12843.15 | 12843.15 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8616.001 | 8616.001 | 1.224363 | 0.00007538 | 185.880 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 8616.00 | 8616.00 | 1.224363 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00759683 | 39.8931 | 3374.19 | 0.00 | 8663.88 | 8663.88 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9319.969 | 9319.969 | 0.404131 | 0.00008154 | 253.674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 9319.97 | 9319.97 | 0.404131 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00793916 | 41.6647 | 7588.17 | 0.00 | 9366.22 | 9366.22 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 456017.420 | -999.000 | 25.459758 | 0.01628789 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 456017.42 | 456017.42 | 25.459758 | 28.53 | 15.15 | 0.00776551 | 10.55 | 8.60 | 0.00776551 | 33.90 | 0.00547527 | 15.07 | 45.8035 | 23.99 | 0.00969040 | 42.2843 | 284140.46 | 0.00 | 541271.50 | 497884.29 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 259564.698 | 259564.698 | 7.637927 | 0.00227079 | 4026.655 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 259564.70 | 259564.70 | 7.637927 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 152.6783 | 21.00 | 0.00789116 | 41.4162 | 72304.65 | 0.00 | 206535.31 | 206535.31 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 45136.60 | 45136.60 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 11.72 | 6.72 | 0.00547527 | 33.90 | 0.00547527 | 15.07 | 99.9965 | 21.11 | 0.00861188 | 44.8406 | 166173.24 | 0.00 | 45179.60 | 45179.60 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20913.38 | 20913.38 | 0.615395 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3216 | 21.11 | 0.00788568 | 41.1066 | 120842.52 | 0.00 | 16640.75 | 16640.75 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 45857.262 | 33750.945 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 36243.804 | 26675.439 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5856.699 | 5856.699 | 1.127402 | 0.00005124 | 123.490 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.0952 | 1.117255 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5856.70 | 5856.70 | 1.0000 | 1.10196509 | 1.127402 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05123173 | 60.00 | 32.22 | 27.78 | 0.000 | 5856.70 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00793171 | 21.00 | 0.00793171 | 41.6258 | 1025.45 | 0.00 | 5889.49 | 5889.49 | 1.10196509 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.84 | 15.17 | 0.00800000 | 42279.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3895.756 | 3895.756 | 0.197936 | 0.00003408 | 100.358 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.7285 | 0.743175 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3895.76 | 3895.76 | 1.0000 | 0.19347025 | 0.197936 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.03407829 | 60.00 | 32.22 | 27.78 | 0.000 | 3895.76 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00787910 | 21.00 | 0.00787910 | 41.3543 | 3047.71 | 0.00 | 3915.43 | 3915.43 | 0.19347025 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.45 | 20.11 | 0.00800000 | 57172.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1525.584 | 1525.584 | 0.121114 | 0.00001335 | 35.413 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.2853 | 0.291028 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1525.58 | 1525.58 | 1.0000 | 0.11838101 | 0.121114 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01334511 | 60.00 | 32.22 | 27.78 | 0.000 | 1525.58 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00785912 | 21.00 | 0.00785912 | 41.2500 | 1006.67 | 0.00 | 1533.74 | 1533.74 | 0.11838101 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.31 | 17.80 | 0.00800000 | 49890.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2274.160 | 2274.160 | 0.099181 | 0.00001990 | 61.761 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.4253 | 0.433831 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2274.16 | 2274.16 | 1.0000 | 0.09694322 | 0.099181 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01989331 | 60.00 | 32.22 | 27.78 | 0.000 | 2274.16 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00781978 | 21.00 | 0.00781978 | 41.0462 | 1849.25 | 0.00 | 2285.45 | 2285.45 | 0.09694322 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.72 | 21.10 | 0.00800000 | 60509.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1492.546 | 1492.546 | 0.064273 | 0.00001306 | 40.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.2791 | 0.284726 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1492.55 | 1492.55 | 1.0000 | 0.06282284 | 0.064273 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01305611 | 60.00 | 32.22 | 27.78 | 0.000 | 1492.55 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00784153 | 21.00 | 0.00784153 | 41.1589 | 1217.17 | 0.00 | 1499.95 | 1499.95 | 0.06282284 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10224.233 | 10224.233 | 1.827750 | 0.00008945 | 216.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.9119 | 1.950428 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10224.23 | 10224.23 | 1.0000 | 1.78651159 | 1.827750 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08943693 | 60.00 | 32.22 | 27.78 | 0.000 | 10224.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00781021 | 21.00 | 0.00781021 | 40.9973 | 2394.38 | 0.00 | 10281.38 | 10281.38 | 1.78651159 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.24 | 15.31 | 0.00800000 | 42689.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11349.337 | 11349.337 | 0.846179 | 0.00009929 | 266.454 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 2.1223 | 2.165059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11349.34 | 11349.34 | 1.0000 | 0.82708763 | 0.846179 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09927882 | 60.00 | 32.22 | 27.78 | 0.000 | 11349.34 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00789431 | 21.00 | 0.00789431 | 41.4329 | 7723.75 | 0.00 | 11409.82 | 11409.82 | 0.82708763 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.13 | 18.08 | 0.00800000 | 50729.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29280.557 | 29280.557 | 2.612051 | 0.00025616 | 666.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 5.4755 | 5.585713 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 29280.56 | 29280.56 | 1.0000 | 2.55311734 | 2.612051 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.25613295 | 60.00 | 32.22 | 27.78 | 0.000 | 29280.56 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00787148 | 21.00 | 0.00787148 | 41.3141 | 18088.82 | 0.00 | 29438.13 | 29438.13 | 2.55311734 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.91 | 17.33 | 0.00800000 | 48465.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12660.185 | -999.000 | 1.387007 | 0.00045218 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7408 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.387007 | 1.35571285 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 1.8077 | 1.807655 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12660.18 | 12534.56 | 1.0000 | 1.35571285 | 1.387007 | 21.82 | 13.55 | 0.00855366 | 43660.6 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.45213789 | 6.70 | 13.37 | 6.67 | 0.000 | 12660.18 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00855366 | 21.11 | 0.00855366 | 44.5416 | 11499.44 | 0.00 | 15925.38 | 14765.59 | 1.35571285 | 21.82 | 15.65 | 0.00855366 | 43660.6 | 11.15 | 11.11 | 0.00821440 | 31913.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6833.803 | 6833.803 | 0.362974 | 0.00005979 | 195.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.387007 | 1.35571285 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.2779 | 1.303652 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6833.80 | 6833.80 | 1.0000 | 0.35478466 | 0.362974 | 21.11 | 12.73 | 0.00787561 | 41218.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05977899 | 60.00 | 32.22 | 27.78 | 0.000 | 6833.80 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787561 | 21.11 | 0.00787561 | 41.0553 | 6833.80 | 0.00 | 7367.03 | 7367.03 | 0.35478466 | 16.60 | 13.03 | 0.00787561 | 36619.8 | 36.97 | 20.18 | 0.00787561 | 57384.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12338.119 | -999.000 | 1.351233 | 0.00044068 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7433 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.351233 | 1.32074603 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 1.7617 | 1.761669 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12338.12 | 12212.68 | 1.0000 | 1.32074603 | 1.351233 | 21.82 | 13.56 | 0.00855499 | 43664.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.44063583 | 6.70 | 13.37 | 6.67 | 0.000 | 12338.12 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00855499 | 21.11 | 0.00855499 | 44.5485 | 11202.84 | 0.00 | 15519.53 | 14384.90 | 1.32074603 | 21.82 | 15.65 | 0.00855499 | 43664.0 | 11.15 | 11.11 | 0.00821431 | 31913.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6839.120 | 6839.120 | 0.363257 | 0.00005983 | 195.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.351233 | 1.32074603 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.2789 | 1.304666 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6839.12 | 6839.12 | 1.0000 | 0.35506068 | 0.363257 | 21.11 | 12.73 | 0.00787571 | 41218.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05982550 | 60.00 | 32.22 | 27.78 | 0.000 | 6839.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787571 | 21.11 | 0.00787571 | 41.0559 | 6839.12 | 0.00 | 7372.76 | 7372.76 | 0.35506068 | 16.60 | 13.03 | 0.00787571 | 36620.1 | 36.97 | 20.18 | 0.00787571 | 57384.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66790.869 | -999.000 | 7.425616 | 0.00238557 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6195 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.425616 | 7.25807603 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 9.5368 | 9.536578 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 66790.87 | 66790.87 | 1.0000 | 7.25807603 | 7.425616 | 21.82 | 13.50 | 0.00848840 | 43495.2 | 12.80 | 10.20 | 0.00848840 | 34292.9 | 2.38532718 | 6.70 | 13.37 | 6.67 | 0.000 | 66790.87 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00848840 | 21.11 | 0.00848840 | 44.2054 | 61567.24 | 0.00 | 84197.85 | 79127.65 | 7.25807603 | 21.82 | 15.59 | 0.00848840 | 43495.2 | 11.13 | 11.11 | 0.00821137 | 31894.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39380.270 | 39380.270 | 2.091693 | 0.00034452 | 1125.127 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.425616 | 7.25807603 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 7.3642 | 7.512387 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 39380.27 | 39380.27 | 1.0000 | 2.04449943 | 2.091693 | 21.11 | 12.74 | 0.00788540 | 41243.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.34448064 | 60.00 | 32.22 | 27.78 | 0.000 | 39380.27 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00788540 | 21.11 | 0.00788540 | 41.1051 | 39380.27 | 0.00 | 42453.19 | 42453.19 | 2.04449943 | 16.60 | 13.04 | 0.00788540 | 36644.6 | 36.97 | 20.18 | 0.00788540 | 57409.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64099.820 | -999.000 | 6.674677 | 0.00228945 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0973 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.674677 | 6.52408003 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 9.1525 | 9.152343 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | unknown | unknown | unknown | 7/21 18:30:00 | Sensible | 64099.82 | 61290.35 | 1.0000 | 6.52408003 | 6.674677 | 21.82 | 13.71 | 0.00874541 | 44147.3 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 2.28922075 | 6.70 | 13.37 | 6.67 | 0.000 | 64099.82 | 29.24 | 0.00546812 | 13.51 | 0.00000000 | 0.0000 | 21.11 | 0.00874541 | 21.11 | 0.00874541 | 45.5273 | 55336.23 | 0.00 | 80136.89 | 71175.51 | 6.52408003 | 21.82 | 15.82 | 0.00874541 | 44147.3 | 11.13 | 11.09 | 0.00820069 | 31864.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39495.420 | 39495.420 | 2.097809 | 0.00034552 | 1128.416 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.674677 | 6.52408003 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 7.3857 | 7.534354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 39495.42 | 39495.42 | 1.0000 | 2.05047768 | 2.097809 | 21.11 | 12.74 | 0.00788570 | 41244.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.34548792 | 60.00 | 32.22 | 27.78 | 0.000 | 39495.42 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00788570 | 21.11 | 0.00788570 | 41.1067 | 39495.42 | 0.00 | 42577.33 | 42577.33 | 2.05047768 | 16.60 | 13.04 | 0.00788570 | 36645.4 | 36.97 | 20.18 | 0.00788570 | 57409.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11077.649 | -999.000 | 1.211131 | 0.00039566 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7549 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.211131 | 1.18380487 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 1.5817 | 1.581696 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11077.65 | 10952.36 | 1.0000 | 1.18380487 | 1.211131 | 21.82 | 13.56 | 0.00856125 | 43679.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.39562020 | 6.70 | 13.37 | 6.67 | 0.000 | 11077.65 | 27.44 | 0.00546540 | 12.88 | 0.00000000 | 0.0000 | 21.11 | 0.00856125 | 21.11 | 0.00856125 | 44.5806 | 10041.28 | 0.00 | 13931.02 | 12894.04 | 1.18380487 | 21.82 | 15.66 | 0.00856125 | 43679.9 | 11.15 | 11.11 | 0.00821387 | 31911.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6833.803 | 6833.803 | 0.362974 | 0.00005979 | 195.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.211131 | 1.18380487 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.2779 | 1.303652 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6833.80 | 6833.80 | 1.0000 | 0.35478466 | 0.362974 | 21.11 | 12.73 | 0.00787561 | 41218.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05977899 | 60.00 | 32.22 | 27.78 | 0.000 | 6833.80 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787561 | 21.11 | 0.00787561 | 41.0553 | 6833.80 | 0.00 | 7367.03 | 7367.03 | 0.35478466 | 16.60 | 13.03 | 0.00787561 | 36619.8 | 36.97 | 20.18 | 0.00787561 | 57384.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10825.183 | -999.000 | 1.183121 | 0.00038664 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7573 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.183121 | 1.15642687 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 1.5457 | 1.545648 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 10825.18 | 10700.24 | 1.0000 | 1.15642687 | 1.183121 | 21.82 | 13.56 | 0.00856252 | 43683.1 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.38660378 | 6.70 | 13.37 | 6.67 | 0.000 | 10825.18 | 26.18 | 0.00546350 | 12.44 | 0.00000000 | 0.0000 | 21.11 | 0.00856252 | 21.11 | 0.00856252 | 44.5871 | 9809.05 | 0.00 | 13612.92 | 12595.96 | 1.15642687 | 21.82 | 15.66 | 0.00856252 | 43683.1 | 11.15 | 11.11 | 0.00821378 | 31911.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6839.120 | 6839.120 | 0.363257 | 0.00005983 | 195.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.183121 | 1.15642687 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.2789 | 1.304666 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6839.12 | 6839.12 | 1.0000 | 0.35506068 | 0.363257 | 21.11 | 12.73 | 0.00787571 | 41218.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05982550 | 60.00 | 32.22 | 27.78 | 0.000 | 6839.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787571 | 21.11 | 0.00787571 | 41.0559 | 6839.12 | 0.00 | 7372.76 | 7372.76 | 0.35506068 | 16.60 | 13.03 | 0.00787571 | 36620.1 | 36.97 | 20.18 | 0.00787571 | 57384.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13920.846 | 13920.846 | 0.685838 | 0.00012179 | 362.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 2.6032 | 2.655614 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13920.85 | 13920.85 | 1.0000 | 0.67036423 | 0.685838 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.12177321 | 60.00 | 32.22 | 27.78 | 0.000 | 13920.85 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00790544 | 21.00 | 0.00790544 | 41.4899 | 10982.02 | 0.00 | 13990.88 | 13990.88 | 0.67036423 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.07 | 20.30 | 0.00800000 | 57805.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3378.978 | -999.000 | 0.370530 | 0.00012069 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7345 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.370530 | 0.36216979 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 0.4825 | 0.482459 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3378.98 | 3347.54 | 1.0000 | 0.36216979 | 0.370530 | 21.82 | 13.55 | 0.00855028 | 43652.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.12067471 | 6.70 | 13.37 | 6.67 | 0.000 | 3378.98 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00855028 | 21.11 | 0.00855028 | 44.5243 | 3072.00 | 0.00 | 4250.95 | 3944.43 | 0.36216979 | 21.82 | 15.65 | 0.00855028 | 43652.0 | 11.15 | 11.12 | 0.00821464 | 31914.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2146.825 | 2146.825 | 0.114028 | 0.00001878 | 61.336 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.370530 | 0.36216979 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.4015 | 0.409540 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2146.83 | 2146.83 | 1.0000 | 0.11145497 | 0.114028 | 21.11 | 12.76 | 0.00790063 | 41281.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01877945 | 60.00 | 32.22 | 27.78 | 0.000 | 2146.83 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790063 | 21.11 | 0.00790063 | 41.1841 | 2146.83 | 0.00 | 2314.34 | 2314.34 | 0.11145497 | 16.60 | 13.05 | 0.00790063 | 36683.1 | 36.97 | 20.19 | 0.00790063 | 57447.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3284.989 | -999.000 | 0.360088 | 0.00011733 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7371 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.360088 | 0.35196349 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 0.4690 | 0.469039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3284.99 | 3253.59 | 1.0000 | 0.35196349 | 0.360088 | 21.82 | 13.55 | 0.00855166 | 43655.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.11731802 | 6.70 | 13.37 | 6.67 | 0.000 | 3284.99 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00855166 | 21.11 | 0.00855166 | 44.5314 | 2985.43 | 0.00 | 4132.51 | 3833.31 | 0.35196349 | 21.82 | 15.65 | 0.00855166 | 43655.5 | 11.15 | 11.11 | 0.00821455 | 31914.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2146.726 | 2146.726 | 0.114022 | 0.00001878 | 61.333 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.360088 | 0.35196349 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 0.4014 | 0.409521 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2146.73 | 2146.73 | 1.0000 | 0.11144980 | 0.114022 | 21.11 | 12.76 | 0.00790063 | 41281.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01877858 | 60.00 | 32.22 | 27.78 | 0.000 | 2146.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790063 | 21.11 | 0.00790063 | 41.1841 | 2146.73 | 0.00 | 2314.23 | 2314.23 | 0.11144980 | 16.60 | 13.05 | 0.00790063 | 36683.1 | 36.97 | 20.19 | 0.00790063 | 57447.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14746.002 | -999.000 | 1.588201 | 0.00052668 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8586 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.588201 | 1.55236736 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 2.1055 | 2.105473 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 14746.00 | 14430.64 | 1.0000 | 1.55236736 | 1.588201 | 21.82 | 13.61 | 0.00861700 | 43821.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.52662947 | 6.70 | 13.37 | 6.67 | 0.000 | 14746.00 | 33.65 | 0.00547489 | 14.99 | 0.00000000 | 0.0000 | 21.11 | 0.00861700 | 21.11 | 0.00861700 | 44.8677 | 13167.10 | 0.00 | 18511.39 | 16916.85 | 1.55236736 | 21.82 | 15.71 | 0.00861700 | 43821.2 | 11.14 | 11.11 | 0.00820966 | 31896.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10327.436 | 10327.436 | 0.548540 | 0.00009035 | 295.059 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.588201 | 1.55236736 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.9312 | 1.970116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10327.44 | 10327.44 | 1.0000 | 0.53616375 | 0.548540 | 21.11 | 12.76 | 0.00790482 | 41292.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09033970 | 60.00 | 32.22 | 27.78 | 0.000 | 10327.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790482 | 21.11 | 0.00790482 | 41.2055 | 10327.44 | 0.00 | 11133.28 | 11133.28 | 0.53616375 | 16.60 | 13.06 | 0.00790482 | 36693.8 | 36.97 | 20.20 | 0.00790482 | 57458.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12354.155 | 12354.155 | 1.207288 | 0.00010808 | 277.743 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 2.3102 | 2.356744 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | Sensible | 12354.15 | 12354.15 | 1.0000 | 1.18004823 | 1.207288 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.10806851 | 60.00 | 32.22 | 27.78 | 0.000 | 12354.15 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00792676 | 21.00 | 0.00792676 | 41.6006 | 7180.82 | 0.00 | 12420.96 | 12420.96 | 1.18004823 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.92 | 16.99 | 0.00800000 | 47460.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12774.020 | 12774.020 | 1.267042 | 0.00011175 | 286.608 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 2.3888 | 2.436839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | Sensible | 12774.02 | 12774.02 | 1.0000 | 1.23845403 | 1.267042 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11174130 | 60.00 | 32.22 | 27.78 | 0.000 | 12774.02 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00792837 | 21.00 | 0.00792837 | 41.6090 | 7344.62 | 0.00 | 12843.15 | 12843.15 | 1.23845403 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.77 | 16.94 | 0.00800000 | 47305.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8616.001 | 8616.001 | 1.224363 | 0.00007538 | 185.880 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.6112 | 1.643634 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 8616.00 | 8616.00 | 1.0000 | 1.19673834 | 1.224363 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07536884 | 60.00 | 32.22 | 27.78 | 0.000 | 8616.00 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.70 | 0.00759683 | 21.00 | 0.00759683 | 39.8931 | 3374.19 | 0.00 | 8663.88 | 8663.88 | 1.19673834 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.70 | 15.85 | 0.00800000 | 44174.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9319.969 | 9319.969 | 0.404131 | 0.00008154 | 253.674 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 1.7429 | 1.777926 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | Sensible | 9319.97 | 9319.97 | 1.0000 | 0.39501312 | 0.404131 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08152683 | 60.00 | 32.22 | 27.78 | 0.000 | 9319.97 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00793916 | 21.00 | 0.00793916 | 41.6647 | 7588.17 | 0.00 | 9366.22 | 9366.22 | 0.39501312 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.85 | 21.14 | 0.00800000 | 60645.9 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 456017.420 | -999.000 | 25.459758 | 0.01628789 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2757 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.459758 | 24.88532539 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 65.1126 | 65.112594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 456017.42 | 456017.42 | 1.0000 | 24.88532539 | 25.459758 | 28.53 | 15.15 | 0.00776551 | 48500.2 | 10.55 | 8.60 | 0.00776551 | 30175.5 | 16.28622410 | 6.70 | 13.37 | 6.67 | 57046.117 | 398971.30 | 33.90 | 0.00547527 | 15.07 | 11.66146000 | 45.8035 | 23.99 | 0.00970207 | 23.99 | 0.00969040 | 42.2843 | 284140.46 | 0.00 | 541271.50 | 497884.29 | 24.88532539 | 28.53 | 17.35 | 0.00776551 | 48500.2 | 8.90 | 8.89 | 0.00707296 | 26749.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 259564.698 | 259564.698 | 7.637927 | 0.00227079 | 4026.655 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.459758 | 24.88532539 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 48.5391 | 49.515927 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 259564.70 | 259564.70 | 1.0000 | 7.46559762 | 7.637927 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 2.27055357 | 60.00 | 32.22 | 27.78 | 0.000 | 259564.70 | -17.90 | 0.00095524 | -17.90 | 11.66146000 | 152.6783 | 20.99 | 0.00788958 | 21.00 | 0.00789116 | 41.4162 | 72304.65 | 0.00 | 206535.31 | 206535.31 | 7.46559762 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.0183 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 25.01240235 | 13.37 | 6.70 | 6.67 | 700352.10 | 6.4448 | 6.444844 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 45136.60 | 45136.60 | 1.0000 | 2.00503462 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 48102.5 | 11.72 | 6.72 | 0.00547527 | 25590.8 | 1.61201042 | 6.70 | 13.37 | 6.67 | 2195.006 | 42941.60 | 33.90 | 0.00547527 | 15.07 | 2.05124512 | 99.9965 | 21.11 | 0.00860349 | 21.11 | 0.00861188 | 44.8406 | 166173.24 | 0.00 | 45179.60 | 45179.60 | 2.00503462 | 33.90 | 17.27 | 0.00547527 | 48102.5 | 11.70 | 8.38 | 0.00547527 | 25569.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 4.58550149 | 54.44 | 82.22 | 27.78 | 534754.28 | 3.9108 | 3.989546 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 20913.38 | 20913.38 | 1.0000 | 0.60151039 | 0.615395 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 0.18294069 | 60.00 | 32.22 | 27.78 | 0.000 | 20913.38 | -17.90 | 0.00095524 | -17.90 | 2.05124512 | 333.3216 | 21.11 | 0.00788550 | 21.11 | 0.00788568 | 41.1066 | 120842.52 | 0.00 | 16640.75 | 16640.75 | 0.60151039 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 45857.262 | 33750.945 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 0.9774 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 4.79294988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 36243.804 | 26675.439 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 0.9774 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 3.78519513 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 25.46 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 493.33 | 7455.00 | 372.33 |
RETAIL_1_FLR_1 | 2664.33 | 6145.00 | 1098.83 |
RETAIL_2_FLR_1 | 1167.67 | 6205.33 | 434.50 |
MECH_FLR_1 | 964.50 | 7419.67 | 635.33 |
STORAGE_FLR_1 | 986.00 | 7785.33 | 788.17 |
LAUNDRY_FLR_1 | 7740.17 | 3115.67 | 2758.50 |
CAFE_FLR_1 | 3771.50 | 3830.33 | 725.17 |
LOBBY_FLR_1 | 1967.83 | 3716.83 | 490.83 |
ROOM_1_FLR_3 | 1140.00 | 8040.67 | 988.17 |
ROOM_2_FLR_3 | 2067.00 | 7892.67 | 1743.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 875.50 | 8716.50 | 860.33 |
ROOM_5_FLR_3 | 1080.50 | 7952.67 | 999.67 |
ROOM_6_FLR_3 | 2040.00 | 7794.83 | 1772.33 |
CORRIDOR_FLR_3 | 970.50 | 7627.00 | 763.33 |
ROOM_1_FLR_6 | 1841.00 | 7928.17 | 1586.17 |
ROOM_2_FLR_6 | 2896.67 | 7822.83 | 2501.00 |
ROOM_3_MULT9_FLR_6 | 1130.33 | 7620.17 | 703.00 |
BANQUET_FLR_6 | 3315.50 | 2802.83 | 499.33 |
DINING_FLR_6 | 4086.17 | 1712.67 | 484.17 |
KITCHEN_FLR_6 | 8355.67 | 6260.83 | 6125.83 |
CORRIDOR_FLR_6 | 1259.67 | 7153.83 | 860.50 |
Facility | 8752.17 | 8760.00 | 7392.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 2.83 | 0.00 | 2.83 |
ROOM_2_FLR_3 | 0.00 | 3.50 | 0.00 | 3.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.17 | 19.83 | 0.17 | 19.83 |
ROOM_5_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_6_FLR_3 | 0.00 | 24.33 | 0.00 | 24.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 4.17 | 0.00 | 4.17 |
ROOM_2_FLR_6 | 0.00 | 4.67 | 0.00 | 4.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 10.33 | 0.00 | 10.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 56.67 | 0.17 | 56.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.917 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.988 | 0.035 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.533 | 0.012 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.569 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.525 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 26.841 | 0.037 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 4.647 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 2.066 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.045 | 0.000 | 0.053 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.050 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.020 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.045 | 0.000 | 0.053 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.052 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.533 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.045 | 0.000 | 0.063 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.056 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.037 | 0.000 | 0.101 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.648 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 6.132 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 25.376 | 0.037 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.198 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.498 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.669 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.150 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.470 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.416 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 15.080 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.772 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.473 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.403 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.255 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.472 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.661 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.805 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38156539.99 | 0.00 | 38156539.99 | 0.00 | 38156539.99 | 26946214.98 | 49.28 | 1.83 | 8708.89 | 0.00 |
RETAIL_1_FLR_1 | 6879106.53 | 0.00 | 6879106.53 | 79984.20 | 6959090.73 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4071478.97 | 0.00 | 4071478.97 | 30874.00 | 4102352.97 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3208720.92 | 0.00 | 3208720.92 | 72967.80 | 3281688.72 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1708662.58 | 0.00 | 1708662.58 | 42098.40 | 1750760.98 | 1821682.01 | 8500.73 | 48.56 | 210.71 | 0.00 |
LAUNDRY_FLR_1 | 71663833.62 | 0.00 | 71663833.62 | 99633.80 | 71763467.42 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29979787.31 | 0.00 | 29979787.31 | 176809.60 | 30156596.91 | 21330615.53 | 18.84 | 3.39 | 8737.77 | 0.00 |
LOBBY_FLR_1 | 92213565.82 | 0.00 | 92213565.82 | 505185.42 | 92718751.23 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 55041.98 | 1515198.70 | 46425.31 | 1561624.01 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 51635.76 | 1511621.40 | 46421.77 | 1558043.17 | 1946647.51 | 2190.00 | 6051.08 | 518.92 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 12953.18 | 1112865.15 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 56272.20 | 19860101.49 | 12956.73 | 19873058.22 | 26405105.73 | 2190.00 | 5995.29 | 574.71 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 55146.25 | 1515302.96 | 46425.31 | 1561728.28 | 1946875.62 | 2189.00 | 5988.83 | 582.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 53223.58 | 1513209.21 | 46421.77 | 1559630.98 | 1946647.51 | 2190.00 | 6008.66 | 561.34 | 0.00 |
CORRIDOR_FLR_3 | 21890203.73 | 0.00 | 21890203.73 | 56137.54 | 21946341.27 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 65683.45 | 430722.63 | 46435.09 | 477157.72 | 486718.90 | 2039.03 | 5990.72 | 730.24 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 57925.59 | 422922.00 | 46431.55 | 469353.55 | 486661.88 | 2064.28 | 6071.32 | 624.40 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 65650.94 | 2410841.25 | 23757.82 | 2434599.07 | 3126920.42 | 2190.00 | 5989.50 | 580.50 | 0.00 |
BANQUET_FLR_6 | 49115784.08 | 0.00 | 49115784.08 | 113382.82 | 49229166.91 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 53320623.94 | 0.00 | 53320623.94 | 113382.82 | 53434006.76 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 68811611.03 | 0.00 | 68811611.03 | 101503.92 | 68913114.94 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 13043899.28 | 0.00 | 13043899.28 | 99346.37 | 13143245.65 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.22E+10 | 5851344.93 | 0.22E+10 | 4678336.06 | 0.22E+10 | 0.43E+10 | 8760.00 | 6474.88 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2099 | 0.0000 | 1.2099 | 0.0000 | 1.2099 | 0.8545 | 49.28 | 1.83 | 8708.89 |
RETAIL_1_FLR_1 | 0.2181 | 0.0000 | 0.2181 | 0.0025 | 0.2207 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1291 | 0.0000 | 0.1291 | 0.0010 | 0.1301 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1017 | 0.0000 | 0.1017 | 0.0023 | 0.1041 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0542 | 0.0000 | 0.0542 | 0.0013 | 0.0555 | 0.0578 | 8500.73 | 48.56 | 210.71 |
LAUNDRY_FLR_1 | 2.2724 | 0.0000 | 2.2724 | 0.0032 | 2.2756 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9507 | 0.0000 | 0.9507 | 0.0056 | 0.9563 | 0.6764 | 18.84 | 3.39 | 8737.77 |
LOBBY_FLR_1 | 2.9241 | 0.0000 | 2.9241 | 0.0160 | 2.9401 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0015 | 0.0495 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0015 | 0.0494 | 0.0617 | 2190.00 | 6051.08 | 518.92 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0004 | 0.6302 | 0.8373 | 2190.00 | 5995.29 | 574.71 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0015 | 0.0495 | 0.0617 | 2189.00 | 5988.83 | 582.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0015 | 0.0495 | 0.0617 | 2190.00 | 6008.66 | 561.34 |
CORRIDOR_FLR_3 | 0.6941 | 0.0000 | 0.6941 | 0.0018 | 0.6959 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0015 | 0.0151 | 0.0154 | 2039.03 | 5990.72 | 730.24 |
ROOM_2_FLR_6 | 0.0116 | 0.0018 | 0.0134 | 0.0015 | 0.0149 | 0.0154 | 2064.28 | 6071.32 | 624.40 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0764 | 0.0008 | 0.0772 | 0.0992 | 2190.00 | 5989.50 | 580.50 |
BANQUET_FLR_6 | 1.5575 | 0.0000 | 1.5575 | 0.0036 | 1.5610 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 1.6908 | 0.0000 | 1.6908 | 0.0036 | 1.6944 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.1820 | 0.0000 | 2.1820 | 0.0032 | 2.1852 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4136 | 0.0000 | 0.4136 | 0.0032 | 0.4168 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 65.6400 | 0.1855 | 65.8256 | 0.1171 | 65.9427 | 73.9670 | 8760.00 | 6474.88 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.43E+09 | 0.00 | 0.43E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 28488844.65 | 460579.75 | 28949424.40 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.7559 | 0.0000 | 13.7559 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 0.9034 | 0.0146 | 0.9180 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3904.82 | 0.00 | 0.00 | 0.00 | 4855.18 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.2571 | 0.0000 | 0.0000 | 0.0000 | 13.3557 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
Electricity:Building | 2338.28 | 30592.37 | 27-MAY-05:00 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2331.19 | 30451.23 | 27-MAY-05:00 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 603.05 | 5169.05 | 27-MAY-05:00 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 603.05 | 5169.05 | 27-MAY-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 603.05 | 5169.05 | 27-MAY-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 603.05 | 5169.05 | 27-MAY-05:00 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.18 | 277.88 | 27-MAY-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.84 | 74.67 | 27-MAY-05:00 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.84 | 74.67 | 27-MAY-05:00 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.74 | 3216.99 | 27-MAY-05:00 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.74 | 1105.57 | 27-MAY-05:00 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.74 | 1105.57 | 27-MAY-05:00 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.09 | 2433.51 | 27-MAY-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.24 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.24 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.09 | 2433.51 | 27-MAY-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.24 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.24 | 184.21 | 27-MAY-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.66 | 732.74 | 06-JUN-22:30 | 2786.82 | 30-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1395.92 | 2160.81 | 13-OCT-01:20 | 208417.98 | 26-JUN-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.75 | 0.00 | 01-JAN-11:10 | 1308.20 | 05-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.82 | 603.46 | 22-DEC-04:10 | 715.64 | 28-JUL-13:10 |
WaterSystems:Electricity | 506.37 | 1086.56 | 15-JUL-03:00 | 42166.26 | 01-SEP-20:50 |
Electricity:HVAC | 758.83 | 11696.78 | 25-DEC-14:50 | 58236.40 | 16-AUG-21:10 |
Fans:Electricity | 567.65 | 10966.90 | 31-OCT-10:10 | 47460.41 | 16-AUG-21:10 |
General:Fans:Electricity | 567.65 | 10966.90 | 31-OCT-10:10 | 47460.41 | 16-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.38 | 10-JUN-05:00 | 1283.34 | 23-MAY-20:10 |
ElectricityPurchased:Facility | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
ElectricityPurchased:Plant | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
Cogeneration:ElectricityPurchased | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
General:Cogeneration:ElectricityPurchased | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
ElectricityNet:Plant | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
Cogeneration:ElectricityNet | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
General:Cogeneration:ElectricityNet | 5286.35 | 68333.26 | 09-JAN-02:50 | 406303.07 | 26-JUN-18:20 |
ExteriorLights:Electricity | 174.28 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.28 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 168.73 | 0.00 | 01-JAN-11:40 | 9938.94 | 17-MAY-09:00 |
General:HeatRecovery:Electricity | 168.73 | 0.00 | 01-JAN-11:40 | 9938.94 | 17-MAY-09:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 19-SEP-00:50 | 4738.74 | 15-JUN-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 758.46 | 0.00 | 01-JAN-01:20 | 165990.25 | 26-JUN-15:10 |
General:Cooling:Electricity | 758.46 | 0.00 | 01-JAN-01:20 | 165990.25 | 26-JUN-15:10 |
Pumps:Electricity | 94.53 | 47.91 | 30-JAN-15:30 | 4996.53 | 14-JUN-20:10 |
General:Pumps:Electricity | 94.53 | 47.91 | 30-JAN-15:30 | 4996.53 | 14-JUN-20:10 |
WIRED_LTG_ELECTRICITY | 21.23 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4160.82 | 29270.80 | 05-MAY-03:10 | 509588.33 | 21-DEC-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2371.98 | 15908.90 | 10-JAN-11:10 | 421968.56 | 21-DEC-19:10 |
WaterSystems:NaturalGas | 1278.38 | 15908.90 | 01-JAN-16:10 | 141634.32 | 15-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 1278.38 | 15908.90 | 01-JAN-16:10 | 141634.32 | 15-FEB-22:00 |
Heating:NaturalGas | 1093.60 | 0.00 | 01-JAN-09:00 | 314751.84 | 21-DEC-09:10 |
Boiler:Heating:NaturalGas | 1093.60 | 0.00 | 01-JAN-09:00 | 314751.84 | 21-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2309.39 | 0.00 | 01-JAN-01:20 | 450118.45 | 26-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 2309.39 | 0.00 | 01-JAN-01:20 | 450118.45 | 26-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2309.39 | 0.00 | 01-JAN-01:20 | 450118.45 | 26-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:40 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 20038.01 | 138130.56 | 01-MAY-14:40 | 2093832.60 | 26-JUN-18:20 |
EnergyTransfer:Building | 5013.55 | 75999.68 | 06-FEB-11:10 | 353602.11 | 26-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 693.24 | 8882.30 | 22-DEC-04:00 | 35427.54 | 05-AUG-10:40 |
Refrigeration:EnergyTransfer | 179.58 | 4015.72 | 06-JUN-22:30 | 10360.58 | 28-JUL-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.79 | 2007.86 | 06-JUN-22:30 | 5180.29 | 28-JUL-06:30 |
General:Refrigeration:EnergyTransfer | 89.79 | 2007.86 | 06-JUN-22:30 | 5180.29 | 28-JUL-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.79 | 2007.86 | 06-JUN-22:30 | 5180.29 | 28-JUL-06:30 |
EnergyTransfer:Plant | 7217.37 | 17186.34 | 13-OCT-01:20 | 1105084.64 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.51 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.28 | 1769.17 | 22-DEC-04:10 | 2552.15 | 28-JUL-13:10 |
EnergyTransfer:HVAC | 7807.09 | 3839.69 | 04-MAY-07:10 | 795492.65 | 21-DEC-20:00 |
CoolingCoils:EnergyTransfer | 3475.87 | 0.00 | 01-JAN-01:50 | 579058.06 | 26-JUN-18:20 |
EnergyTransfer:Zone:BASEMENT | 312.42 | 7214.79 | 26-MAR-15:00 | 18570.26 | 20-OCT-21:00 |
Heating:EnergyTransfer | 142.04 | 0.00 | 01-JAN-08:10 | 102159.60 | 20-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 142.04 | 0.00 | 01-JAN-08:10 | 102159.60 | 20-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4781.72 | 59926.90 | 20-DEC-15:00 | 350120.60 | 26-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 312.42 | 7214.79 | 26-MAR-15:00 | 18570.26 | 20-OCT-21:00 |
General:Cooling:EnergyTransfer | 4781.72 | 59926.90 | 20-DEC-15:00 | 350120.60 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 312.42 | 7214.79 | 26-MAR-15:00 | 18570.26 | 20-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.64 | 0.05 | 04-FEB-21:30 | 4917.22 | 07-NOV-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.14 | 0.00 | 01-JAN-00:10 | 2027.03 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.14 | 0.00 | 01-JAN-00:10 | 2027.03 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.51 | 0.00 | 03-JAN-07:10 | 4917.22 | 07-NOV-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.51 | 0.00 | 03-JAN-07:10 | 4917.22 | 07-NOV-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.94 | 136.92 | 21-DEC-10:10 | 2171.27 | 16-AUG-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.94 | 136.92 | 21-DEC-10:10 | 2171.27 | 16-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.94 | 136.92 | 21-DEC-10:10 | 2171.27 | 16-AUG-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 22.63 | 0.05 | 12-FEB-15:20 | 1846.05 | 17-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 713.16 | 22-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 713.16 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 22.43 | 0.00 | 05-JAN-03:20 | 1846.05 | 17-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 22.43 | 0.00 | 05-JAN-03:20 | 1846.05 | 17-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.47 | 0.01 | 03-APR-02:30 | 830.25 | 26-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.32 | 0.00 | 01-JAN-00:10 | 609.36 | 21-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.32 | 0.00 | 01-JAN-00:10 | 609.36 | 21-DEC-11:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.15 | 0.00 | 04-JAN-11:50 | 830.25 | 26-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.15 | 0.00 | 04-JAN-11:50 | 830.25 | 26-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.05 | 8809.60 | 22-DEC-05:00 | 39226.26 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.05 | 8809.60 | 22-DEC-05:00 | 39226.26 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.05 | 8809.60 | 22-DEC-05:00 | 39226.26 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 243.61 | 0.49 | 20-DEC-13:20 | 17855.52 | 18-FEB-13:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2379.10 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2379.10 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 243.58 | 0.00 | 05-JAN-09:10 | 17855.52 | 18-FEB-13:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 243.58 | 0.00 | 05-JAN-09:10 | 17855.52 | 18-FEB-13:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 777.47 | 7776.59 | 21-DEC-09:30 | 43264.55 | 16-AUG-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 777.47 | 7776.59 | 21-DEC-09:30 | 43264.55 | 16-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 777.47 | 7776.59 | 21-DEC-09:30 | 43264.55 | 16-AUG-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.07 | 0.00 | 01-JAN-08:10 | 13159.03 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.33 | 0.00 | 01-JAN-08:10 | 7703.24 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.33 | 0.00 | 01-JAN-08:10 | 7703.24 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 55.73 | 0.00 | 01-JAN-00:10 | 13159.03 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 55.73 | 0.00 | 01-JAN-00:10 | 13159.03 | 28-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.75 | 0.00 | 01-JAN-08:10 | 12812.06 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.95 | 0.00 | 01-JAN-08:10 | 7786.13 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.95 | 0.00 | 01-JAN-08:10 | 7786.13 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.80 | 0.00 | 01-JAN-00:10 | 12812.06 | 01-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.80 | 0.00 | 01-JAN-00:10 | 12812.06 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.81 | 0.00 | 01-JAN-00:40 | 66479.78 | 20-JAN-12:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.81 | 0.00 | 01-JAN-00:40 | 66479.78 | 20-JAN-12:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 388.81 | 0.00 | 01-JAN-00:40 | 66479.78 | 20-JAN-12:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 354.81 | 0.00 | 01-JAN-08:10 | 75753.80 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 44.03 | 0.00 | 01-JAN-08:10 | 51030.31 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 44.03 | 0.00 | 01-JAN-08:10 | 51030.31 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 310.79 | 0.00 | 01-JAN-00:10 | 75753.80 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 310.79 | 0.00 | 01-JAN-00:10 | 75753.80 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.18 | 0.00 | 01-JAN-08:10 | 12267.97 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.73 | 0.00 | 01-JAN-07:50 | 7690.48 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.73 | 0.00 | 01-JAN-07:50 | 7690.48 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 59.45 | 0.00 | 01-JAN-00:10 | 12267.97 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 59.45 | 0.00 | 01-JAN-00:10 | 12267.97 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 60.57 | 0.00 | 01-JAN-08:10 | 15006.87 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 19.32 | 0.00 | 01-JAN-08:10 | 8023.92 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 19.32 | 0.00 | 01-JAN-08:10 | 8023.92 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 41.25 | 0.00 | 01-JAN-00:10 | 15006.87 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 41.25 | 0.00 | 01-JAN-00:10 | 15006.87 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 150.35 | 1.15 | 31-OCT-04:00 | 11383.75 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.86 | 0.00 | 01-JAN-00:10 | 6479.64 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.86 | 0.00 | 01-JAN-00:10 | 6479.64 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 148.50 | 0.00 | 04-JAN-12:20 | 11383.75 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 148.50 | 0.00 | 04-JAN-12:20 | 11383.75 | 26-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.14 | 0.00 | 01-JAN-08:10 | 3546.14 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.64 | 0.00 | 01-JAN-08:10 | 2461.14 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.64 | 0.00 | 01-JAN-08:10 | 2461.14 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.50 | 0.00 | 01-JAN-00:10 | 3546.14 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.50 | 0.00 | 01-JAN-00:10 | 3546.14 | 28-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.93 | 0.00 | 01-JAN-08:10 | 3436.08 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.63 | 0.00 | 01-JAN-08:10 | 2482.75 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.63 | 0.00 | 01-JAN-08:10 | 2482.75 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.30 | 0.00 | 01-JAN-00:10 | 3436.08 | 01-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.30 | 0.00 | 01-JAN-00:10 | 3436.08 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 114.06 | 0.00 | 01-JAN-08:10 | 18379.05 | 05-NOV-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 13.50 | 0.00 | 01-JAN-00:10 | 10968.69 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 13.50 | 0.00 | 01-JAN-00:10 | 10968.69 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 100.56 | 0.00 | 01-JAN-02:30 | 18379.05 | 05-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 100.56 | 0.00 | 01-JAN-02:30 | 18379.05 | 05-NOV-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 424.05 | 6711.79 | 20-DEC-15:00 | 23264.80 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 424.05 | 6711.79 | 20-DEC-15:00 | 23264.80 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 424.05 | 6711.79 | 20-DEC-15:00 | 23264.80 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 463.47 | 7623.21 | 20-DEC-15:00 | 24469.22 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 463.47 | 7623.21 | 20-DEC-15:00 | 24469.22 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 463.47 | 7623.21 | 20-DEC-15:00 | 24469.22 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 603.45 | 6872.01 | 22-DEC-04:00 | 30348.03 | 05-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 603.45 | 6872.01 | 22-DEC-04:00 | 30348.03 | 05-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.88 | 0.11 | 03-APR-00:20 | 6967.49 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.35 | 0.00 | 01-JAN-00:10 | 4052.51 | 22-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.35 | 0.00 | 01-JAN-00:10 | 4052.51 | 22-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 82.53 | 0.00 | 03-JAN-06:10 | 6967.49 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 82.53 | 0.00 | 03-JAN-06:10 | 6967.49 | 16-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 3171.57 | 9703.00 | 16-AUG-01:20 | 379909.09 | 21-DEC-19:10 |
PlantLoopHeatingDemand:Plant | 2373.98 | 9703.00 | 16-AUG-01:20 | 213031.36 | 01-JUN-20:20 |
WaterSystems:PlantLoopHeatingDemand | 2373.98 | 9703.00 | 16-AUG-01:20 | 213031.36 | 01-JUN-20:20 |
General:WaterSystems:PlantLoopHeatingDemand | 802.11 | 9698.83 | 16-AUG-00:10 | 58965.67 | 01-MAR-07:10 |
HeatingCoils:EnergyTransfer | 797.59 | 0.00 | 01-JAN-09:00 | 255795.56 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 797.59 | 0.00 | 01-JAN-09:00 | 255795.56 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 797.59 | 0.00 | 01-JAN-09:00 | 255795.56 | 21-DEC-09:10 |
HeatRecoveryForHeating:EnergyTransfer | 3469.72 | 0.00 | 01-JAN-11:40 | 514150.39 | 21-DEC-22:00 |
HeatRecoveryForCooling:EnergyTransfer | 63.91 | 0.00 | 01-JAN-00:10 | 153975.36 | 16-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1571.87 | 0.00 | 01-JAN-00:10 | 172899.29 | 01-JUL-21:30 |
WaterSystems:EnergyTransfer | 802.11 | 9698.83 | 16-AUG-00:10 | 58965.67 | 01-MAR-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 802.11 | 9698.83 | 16-AUG-00:10 | 58965.67 | 01-MAR-07:10 |
Boilers:EnergyTransfer | 789.90 | 0.00 | 01-JAN-09:00 | 257561.22 | 21-DEC-09:10 |
Chillers:EnergyTransfer | 2388.56 | 0.00 | 01-JAN-01:20 | 452708.25 | 26-JUN-18:10 |
HeatRejection:EnergyTransfer | 3147.01 | 0.00 | 01-JAN-01:20 | 616806.10 | 26-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 3147.01 | 0.00 | 01-JAN-01:20 | 616806.10 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -312.426 | 0.000 | 0.000 | 138.327 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.376 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.138 | -45.505 | 0.000 | 0.000 | 15.118 | 6.265 | 10.186 | 34.588 | 0.000 | 0.040 | 0.001 | 0.000 | -12.650 | 0.000 | -1.055 | -8.123 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -32.938 | 0.000 | 0.000 | 16.375 | 7.255 | 11.795 | 0.000 | 0.000 | 0.016 | 0.000 | 0.000 | 0.000 | 0.000 | -0.433 | -2.069 |
MECH_FLR_1 | 0.000 | 0.000 | 0.201 | -22.433 | 0.000 | 0.000 | 3.635 | 8.366 | 12.471 | 0.000 | 0.000 | 0.038 | 0.000 | 0.000 | 0.000 | 0.000 | -0.969 | -1.309 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.321 | -11.152 | 0.000 | 0.000 | 2.826 | 1.866 | 3.598 | 0.000 | 0.000 | 0.022 | 3.071 | 0.000 | 0.000 | 0.000 | -0.552 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -597.051 | 0.000 | 0.000 | 10.995 | 4.900 | 658.131 | 0.000 | 0.000 | 0.054 | 0.000 | 0.000 | 0.000 | 0.000 | -1.417 | -75.611 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.034 | -243.581 | 0.000 | 0.000 | 185.420 | 12.836 | 14.341 | 96.362 | 0.000 | 0.089 | 0.003 | 0.000 | -37.674 | 0.000 | -2.492 | -25.334 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -777.474 | 0.000 | 0.000 | 540.066 | 122.744 | 148.998 | 127.302 | 0.000 | 0.255 | 0.000 | 0.000 | -50.581 | 0.000 | -7.258 | -104.051 |
ROOM_1_FLR_3 | 16.176 | -49.436 | 0.000 | -9.135 | 0.000 | 0.000 | 9.690 | 6.171 | 12.292 | 61.432 | 0.000 | 0.194 | 0.000 | 0.000 | -27.839 | 0.000 | -2.867 | -16.679 |
ROOM_2_FLR_3 | 22.472 | -31.759 | 0.000 | -9.558 | 0.000 | 0.000 | 9.572 | 6.170 | 12.291 | 40.342 | 0.000 | 0.136 | 0.000 | 0.000 | -28.746 | 0.000 | -3.231 | -17.689 |
ROOM_3_MULT19_FLR_3 | 0.000 | -376.044 | 0.000 | -12.759 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 397.892 | 0.000 | 0.241 | 0.006 | 0.000 | -192.100 | 0.000 | -16.104 | -103.565 |
ROOM_4_MULT19_FLR_3 | 76.468 | -216.200 | 0.000 | -127.025 | 0.000 | 0.000 | 182.963 | 73.705 | 228.817 | 97.979 | 0.000 | 0.960 | 0.000 | 0.000 | -158.924 | 0.000 | -27.161 | -131.582 |
ROOM_5_FLR_3 | 16.577 | -53.150 | 0.000 | -9.139 | 0.000 | 0.000 | 9.681 | 6.171 | 12.292 | 64.447 | 0.000 | 0.194 | 0.003 | 0.000 | -27.429 | 0.000 | -2.883 | -16.760 |
ROOM_6_FLR_3 | 22.769 | -35.138 | 0.000 | -9.562 | 0.000 | 0.000 | 9.574 | 6.170 | 12.291 | 43.086 | 0.000 | 0.136 | 0.000 | 0.000 | -28.097 | 0.000 | -3.274 | -17.954 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 1.859 | -148.497 | 0.000 | 0.000 | 115.537 | 56.739 | 0.000 | 57.474 | 0.000 | 0.113 | 0.001 | 0.000 | -36.327 | 0.000 | -2.972 | -43.927 |
ROOM_1_FLR_6 | 6.494 | -12.076 | 0.000 | -2.282 | 0.000 | 0.000 | 2.426 | 1.543 | 3.073 | 15.293 | 0.000 | 0.051 | 0.000 | 0.000 | -6.906 | 0.000 | -0.740 | -6.876 |
ROOM_2_FLR_6 | 8.610 | -7.889 | 0.000 | -2.388 | 0.000 | 0.000 | 2.395 | 1.543 | 3.073 | 10.050 | 0.000 | 0.034 | 0.000 | 0.000 | -7.132 | 0.000 | -0.826 | -7.470 |
ROOM_3_MULT9_FLR_6 | 16.935 | -89.269 | 0.000 | -14.716 | 0.000 | 0.000 | 21.753 | 8.728 | 27.097 | 90.838 | 0.000 | 0.314 | 0.001 | 0.000 | -32.462 | 0.000 | -4.125 | -25.094 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -424.052 | 0.000 | 0.000 | 315.680 | 28.238 | 175.857 | 10.010 | 0.000 | 0.054 | 0.000 | 0.000 | -21.314 | 0.000 | -1.661 | -82.812 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -463.475 | 0.000 | 0.000 | 314.852 | 28.238 | 175.857 | 9.829 | 0.000 | 0.054 | 0.000 | 0.000 | -21.800 | 0.000 | -1.670 | -41.885 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -603.437 | 0.000 | 0.000 | 28.222 | 13.339 | 540.650 | 29.459 | 0.000 | 0.049 | 7.695 | 0.000 | -14.483 | 0.000 | -1.493 | -0.003 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 2.352 | -82.529 | 0.000 | 0.000 | 30.917 | 15.012 | 0.000 | 28.679 | 0.000 | 0.048 | 22.984 | 0.000 | -16.158 | 0.000 | -1.306 | -0.001 |
Total Facility | 186.501 | -870.961 | 5.904 | -3961.115 | 0.000 | 0.000 | 1966.025 | 603.052 | 2434.967 | 1215.061 | 0.000 | 3.092 | 33.766 | 0.000 | -720.620 | 0.000 | -84.488 | -811.171 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18570.18 | 0.00 | 0.00 | 5924.48 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4720.96 |
RETAIL_1_FLR_1 | 07-NOV-12:40 | 0.00 | 0.00 | 0.00 | -4916.43 | 0.00 | 0.00 | 147.86 | 142.31 | 252.59 | 7607.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10.47 | -3223.80 |
RETAIL_2_FLR_1 | 16-AUG-20:10 | 0.00 | 0.00 | 0.00 | -2171.09 | 0.00 | 0.00 | 697.63 | 527.34 | 752.15 | 0.00 | 0.00 | 4.11 | 189.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 17-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1846.29 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 12.93 | 180.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 26-JUN-19:10 | 0.00 | 0.00 | 0.00 | -830.33 | 0.00 | 0.00 | 99.29 | 152.61 | 242.16 | 0.00 | 0.00 | 13.47 | 322.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39228.80 | 0.00 | 0.00 | 408.85 | 400.68 | 44299.38 | 0.00 | 0.00 | 25.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5905.42 |
CAFE_FLR_1 | 18-FEB-13:10 | 0.00 | 0.00 | 0.00 | -17855.57 | 0.00 | 0.00 | 2968.79 | 96.16 | 355.63 | 21007.18 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.55 | -6550.63 |
LOBBY_FLR_1 | 16-AUG-20:10 | 0.00 | 0.00 | 0.00 | -43261.23 | 0.00 | 0.00 | 23502.87 | 9462.56 | 9501.36 | 290.04 | 0.00 | 67.23 | 437.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 28-SEP-15:01 | 0.00 | -17337.94 | 0.00 | -594.09 | 0.00 | 0.00 | 235.27 | 132.99 | 273.93 | 12730.93 | 0.00 | 38.37 | 4520.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-08:61 | 0.00 | -18723.36 | 0.00 | -707.15 | 0.00 | 0.00 | 110.84 | 265.95 | 653.15 | 1634.43 | 0.00 | 8.90 | 16757.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-JAN-12:40 | 0.00 | -66479.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 96524.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -180.89 | -36550.26 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -93540.52 | 0.00 | -9531.18 | 0.00 | 0.00 | 2235.61 | 3176.85 | 12159.85 | 9182.28 | 0.00 | 48.65 | 76268.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:61 | 0.00 | -15385.63 | 0.00 | -611.40 | 0.00 | 0.00 | 130.71 | 265.98 | 653.23 | 11294.77 | 0.00 | 17.53 | 3634.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 27-JUN-08:32 | 0.00 | -17961.76 | 0.00 | -825.28 | 0.00 | 0.00 | 58.93 | 208.96 | 452.99 | 9531.29 | 0.00 | 0.00 | 8544.28 | 0.00 | -0.00 | 0.00 | -9.40 | 0.00 |
CORRIDOR_FLR_3 | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -11384.53 | 0.00 | 0.00 | 4080.25 | 4124.45 | 0.00 | 3435.70 | 0.00 | 81.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -337.32 |
ROOM_1_FLR_6 | 28-SEP-15:01 | 0.00 | -4624.58 | 0.00 | -148.24 | 0.00 | 0.00 | 58.82 | 33.25 | 68.48 | 3169.03 | 0.00 | 9.54 | 1433.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 01-JUL-08:61 | 0.00 | -4926.26 | 0.00 | -173.73 | 0.00 | 0.00 | 28.00 | 66.49 | 163.29 | 412.38 | 0.00 | 2.41 | 4427.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 28-SEP-15:01 | 0.00 | -20256.73 | 0.00 | -976.92 | 0.00 | 0.00 | 529.38 | 188.10 | 603.86 | 9208.40 | 0.00 | 42.39 | 10661.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23266.57 | 0.00 | 0.00 | 15610.97 | 1842.08 | 6747.90 | 6.07 | 0.00 | 11.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -951.96 |
DINING_FLR_6 | 26-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24471.24 | 0.00 | 0.00 | 15603.48 | 1842.08 | 6747.90 | 0.00 | 0.00 | 11.49 | 272.27 | 0.00 | -5.99 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 05-AUG-10:40 | 0.00 | 0.00 | 0.00 | -30349.15 | 0.00 | 0.00 | 464.26 | 303.01 | 23951.61 | 3759.19 | 0.00 | 14.66 | 1856.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 | -6973.65 | 0.00 | 0.00 | 771.11 | 341.02 | 0.00 | 2345.92 | 0.00 | 34.67 | 3480.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-SEP-15:01 | 0.00 | -228198.64 | 0.00 | -163023.39 | 0.00 | 0.00 | 52595.40 | 12682.34 | 76844.13 | 133718.08 | 0.00 | 771.36 | 114610.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 21-DEC-08:02 | 0.00 | 0.00 | 2037.00 | 0.00 | 0.00 | 0.00 | 357.98 | 227.69 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1921.40 | 0.00 | -113.89 | -948.23 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 22-DEC-05:00 | 0.00 | 0.00 | 713.19 | 0.00 | 0.00 | 0.00 | 197.29 | 76.02 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -107.20 | -1056.04 |
STORAGE_FLR_1 | 21-DEC-11:03 | 0.00 | 0.00 | 609.41 | 0.00 | 0.00 | 0.00 | 33.72 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -56.56 | -718.19 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-09:30 | 0.00 | 0.00 | 2378.82 | 0.00 | 0.00 | 0.00 | 2351.74 | 231.52 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3833.59 | 0.00 | -252.41 | -1384.12 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-DEC-19:01 | 10776.98 | 251.71 | 0.00 | -251.71 | 0.00 | 0.00 | 419.20 | 422.72 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3874.24 | 0.00 | -259.02 | -8001.90 |
ROOM_2_FLR_3 | 21-DEC-19:01 | 10807.94 | 248.04 | 0.00 | -248.04 | 0.00 | 0.00 | 419.22 | 422.67 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3824.69 | 0.00 | -258.61 | -8082.73 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:01 | 60226.79 | 3141.89 | 0.00 | -3141.89 | 0.00 | 0.00 | 5585.73 | 1588.43 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16975.99 | 0.00 | -1269.79 | -54254.45 |
ROOM_5_FLR_3 | 21-DEC-19:01 | 10530.74 | 248.45 | 0.00 | -248.45 | 0.00 | 0.00 | 419.20 | 422.72 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3913.98 | 0.00 | -258.67 | -7716.27 |
ROOM_6_FLR_3 | 21-DEC-16:01 | 10558.59 | 244.43 | 0.00 | -244.43 | 0.00 | 0.00 | 293.99 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3122.90 | 0.00 | -240.74 | -7895.81 |
CORRIDOR_FLR_3 | 21-DEC-09:03 | 0.00 | 0.00 | 6480.20 | 0.00 | 0.00 | 0.00 | 1385.69 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4125.90 | 0.00 | -320.77 | -5481.44 |
ROOM_1_FLR_6 | 21-DEC-19:01 | 3267.69 | 63.54 | 0.00 | -63.54 | 0.00 | 0.00 | 104.80 | 105.68 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -969.01 | 0.00 | -64.93 | -2573.30 |
ROOM_2_FLR_6 | 21-DEC-19:01 | 3269.76 | 62.56 | 0.00 | -62.56 | 0.00 | 0.00 | 104.80 | 105.67 | 129.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.23 | 0.00 | -64.82 | -2589.23 |
ROOM_3_MULT9_FLR_6 | 21-DEC-09:02 | 15200.10 | 407.72 | 0.00 | -407.72 | 0.00 | 0.00 | 244.99 | 295.59 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3679.19 | 0.00 | -295.74 | -12764.44 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-DEC-08:02 | 0.00 | 0.00 | 4097.91 | 0.00 | 0.00 | 0.00 | 733.22 | 545.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2443.49 | 0.00 | -141.81 | -2791.47 |
Total Facility | 21-DEC-09:02 | 56253.48 | 71840.45 | 15571.04 | -71840.45 | 0.00 | 0.00 | 23855.73 | 20832.59 | 87870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74260.93 | 0.00 | -6500.24 | -123622.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.6013 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 25.4598 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.8006 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6742 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4724 | 2.4724 | 1.1274 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4341 | 0.4341 | 0.1979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2656 | 0.2656 | 0.1211 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2175 | 0.2175 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1182 | 0.1182 | 0.0539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0082 | 4.0082 | 1.8277 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8557 | 1.8557 | 0.8462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7282 | 5.7282 | 2.6121 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5040 | 1.5040 | 0.6858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6476 | 2.6476 | 1.2073 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7786 | 2.7786 | 1.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6850 | 2.6850 | 1.2244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8863 | 0.8863 | 0.4041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.6013 | 25.4598 | 25.6013 | 11.6742 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2362 | 1.2362 | 1.1274 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2170 | 0.2170 | 0.1979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1328 | 0.1328 | 0.1211 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1088 | 0.1088 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0591 | 0.0591 | 0.0539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0041 | 2.0041 | 1.8277 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9278 | 0.9278 | 0.8462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8641 | 2.8641 | 2.6121 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7520 | 0.7520 | 0.6858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3238 | 1.3238 | 1.2073 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3893 | 1.3893 | 1.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3425 | 1.3425 | 1.2244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4431 | 0.4431 | 0.4041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.8006 | 11.6742 | 11.6742 | 11.6742 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 56.67 |
Number of hours not met | 56.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1093.60 | 314751.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 758.46 | 165990.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 603.05 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.28 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 567.65 | 47460.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 94.53 | 4996.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 168.73 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.74 | 1278.38 | 141634.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 37427.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.75 | 1308.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.82 | 715.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.80 | 5286.35 |
Natural Gas | 1788.84 | 4160.82 |
Additional | 0.00 | 0.00 |
Total | 3560.64 | 9447.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.15 |
Space Heating | 0.00 |
Space Cooling | 66.85 |
Fans (All) | 50.03 |
Service Water Heating | 44.63 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 465.95 |
Subtotal | 465.95 |
Natural Gas [MJ/m2] | |
Space Heating | 96.39 |
Service Water Heating | 112.68 |
Miscellaneous (All) | 366.74 |
Subtotal | 366.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.38 |
Space Heating | 11.58 |
Space Cooling | 8.03 |
Fans (All) | 6.01 |
Service Water Heating | 18.89 |
Receptacle Equipment | 37.23 |
Miscellaneous | 11.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8705.50 | 54.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8705.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 54.50 | 0.00 | 0.00 | 0.00 |
Average | 8755.11 | 4.89 | 0.00 | 0.00 | 0.00 |
Sum | 192612.33 | 107.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.50 | 2.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4145.83 | 8.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 8.17 | 0.00 | 0.00 | 0.00 |
Average | 288886.56 | 0.48 | 0.00 | 0.00 | 0.00 |
Sum | 6355504.33 | 10.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8681.50 | 78.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8726.50 | 33.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8690.00 | 70.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8711.17 | 48.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8710.50 | 49.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8681.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 78.50 | 0.00 | 0.00 | 0.00 |
Average | 8742.76 | 17.24 | 0.00 | 0.00 | 0.00 |
Sum | 192340.67 | 379.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59114.83 | 41.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 700825.00 | 9592.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2099143.50 | 16285.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4140.17 | 13.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4145.83 | 8.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100233.00 | 125.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4129.83 | 24.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1235035.33 | 10679.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1237246.00 | 8469.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108265.33 | 3.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2099143.50 | 16285.50 | 0.00 | 0.00 | 0.00 |
Average | 286830.58 | 2056.47 | 0.00 | 0.00 | 0.00 |
Sum | 6310272.67 | 45242.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244366E+11 | 12231.56 | 27-JAN-22:00 | 3.00 | 3.00 | 0.793960E+10 | 4837.02 | 18-JAN-22:19 | 3.00 | 3.00 |
February | 0.208659E+11 | 10940.85 | 18-FEB-12:20 | 18.67 | 7.14 | 0.693644E+10 | 4836.91 | 01-FEB-22:19 | 18.67 | 7.14 |
March | 0.221046E+11 | 10375.12 | 12-MAR-10:33 | 15.67 | 5.64 | 0.739441E+10 | 4722.53 | 01-MAR-22:10 | 15.67 | 5.64 |
April | 0.215367E+11 | 10165.84 | 21-APR-10:33 | 13.33 | 5.84 | 0.717989E+10 | 4631.74 | 14-APR-21:10 | 13.33 | 5.84 |
May | 0.225908E+11 | 10343.60 | 31-MAY-18:10 | 25.50 | 14.26 | 0.737845E+10 | 4573.01 | 19-MAY-21:19 | 25.50 | 14.26 |
June | 0.238806E+11 | 11377.99 | 26-JUN-18:10 | 37.33 | 15.09 | 0.743826E+10 | 4776.27 | 16-JUN-22:10 | 37.33 | 15.09 |
July | 0.251715E+11 | 11549.60 | 23-JUL-10:33 | 29.67 | 15.92 | 0.778653E+10 | 4837.07 | 28-JUL-22:10 | 16.17 | 15.40 |
August | 0.281741E+11 | 15379.67 | 18-AUG-21:00 | 19.00 | 9.02 | 0.815670E+10 | 4837.29 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.313984E+11 | 18436.00 | 21-SEP-21:00 | 1.10 | -0.6 | 0.795385E+10 | 4837.56 | 01-SEP-01:10 | 1.10 | -0.6 |
October | 0.323101E+11 | 18570.26 | 20-OCT-21:00 | 10.00 | 1.41 | 0.821992E+10 | 4837.17 | 27-OCT-01:10 | 5.00 | 5.00 |
November | 0.305366E+11 | 18244.71 | 17-NOV-22:00 | 6.00 | 2.21 | 0.794699E+10 | 4837.08 | 09-NOV-02:20 | 6.00 | 2.21 |
December | 0.294179E+11 | 17259.95 | 01-DEC-22:00 | 6.00 | 1.10 | 0.820338E+10 | 4837.06 | 22-DEC-00:20 | -20.3 | -20.4 |
Annual Sum or Average | 0.312424E+12 | 0.925344E+11 | ||||||||
Minimum of Months | 0.208659E+11 | 10165.84 | 1.10 | -0.6 | 0.693644E+10 | 4573.01 | -20.3 | -20.4 | ||
Maximum of Months | 0.323101E+11 | 18570.26 | 37.33 | 15.92 | 0.821992E+10 | 4837.56 | 37.33 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358948E+10 | 4878.19 | 20-JAN-13:10 | 21.00 | 6.97 | 0.669274E+09 | 457.18 | 20-JAN-22:30 | 7.50 | 1.84 |
February | 0.295551E+10 | 4862.09 | 18-FEB-13:20 | 20.00 | 7.74 | 0.604488E+09 | 445.12 | 17-FEB-22:30 | 20.00 | 7.74 |
March | 0.314351E+10 | 4579.47 | 14-MAR-12:40 | 23.33 | 7.71 | 0.680665E+09 | 483.54 | 15-MAR-21:30 | 12.50 | 3.03 |
April | 0.243745E+10 | 3221.33 | 07-APR-12:30 | 20.50 | 8.13 | 0.636837E+09 | 458.86 | 07-APR-21:30 | 11.50 | 6.33 |
May | 0.359216E+10 | 2335.46 | 05-MAY-13:00 | 22.00 | 10.96 | 0.691146E+09 | 466.86 | 31-MAY-21:30 | 17.65 | 11.72 |
June | 0.451178E+10 | 2924.98 | 26-JUN-12:40 | 36.43 | 15.33 | 0.753621E+09 | 491.84 | 06-JUN-22:10 | 36.43 | 15.33 |
July | 0.471109E+10 | 3196.34 | 23-JUL-12:00 | 32.00 | 15.97 | 0.778653E+09 | 491.84 | 21-JUL-22:10 | 32.00 | 15.97 |
August | 0.508742E+10 | 3937.07 | 26-AUG-12:40 | 31.67 | 13.33 | 0.783883E+09 | 491.87 | 25-AUG-22:10 | 31.67 | 13.33 |
September | 0.496666E+10 | 4806.22 | 28-SEP-12:50 | 30.42 | 11.32 | 0.745531E+09 | 491.84 | 08-SEP-22:10 | 30.42 | 11.32 |
October | 0.398123E+10 | 4835.39 | 10-OCT-12:40 | 23.67 | 7.92 | 0.700923E+09 | 491.33 | 10-OCT-21:19 | 13.67 | 4.16 |
November | 0.363356E+10 | 4917.22 | 07-NOV-12:40 | 20.00 | 7.20 | 0.655999E+09 | 460.96 | 07-NOV-22:30 | 7.00 | 2.01 |
December | 0.289548E+10 | 4636.24 | 17-DEC-13:00 | 18.00 | 5.78 | 0.655780E+09 | 425.44 | 01-DEC-22:30 | 18.00 | 5.78 |
Annual Sum or Average | 0.455053E+11 | 0.835680E+10 | ||||||||
Minimum of Months | 0.243745E+10 | 2335.46 | 18.00 | 5.78 | 0.604488E+09 | 425.44 | 7.00 | 1.84 | ||
Maximum of Months | 0.508742E+10 | 4917.22 | 36.43 | 15.97 | 0.783883E+09 | 491.87 | 36.43 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246073E+10 | 1507.70 | 20-JAN-22:00 | 8.00 | 2.08 | 0.890869E+09 | 569.52 | 25-JAN-23:30 | 1.00 | -0.7 |
February | 0.214112E+10 | 1414.52 | 27-FEB-22:00 | 2.00 | -0.8 | 0.791257E+09 | 569.52 | 22-FEB-22:19 | 2.00 | -0.8 |
March | 0.251263E+10 | 1780.72 | 15-MAR-21:00 | 13.00 | 3.08 | 0.891896E+09 | 569.55 | 14-MAR-21:10 | 13.00 | 3.08 |
April | 0.235935E+10 | 1555.79 | 07-APR-21:00 | 12.00 | 6.33 | 0.856426E+09 | 569.53 | 12-APR-22:19 | 9.00 | 3.76 |
May | 0.276146E+10 | 1722.80 | 31-MAY-21:00 | 18.00 | 12.50 | 0.933430E+09 | 569.55 | 30-MAY-21:30 | 18.00 | 12.50 |
June | 0.329933E+10 | 2164.57 | 26-JUN-20:50 | 29.45 | 11.64 | 0.935736E+09 | 569.59 | 07-JUN-21:10 | 29.45 | 11.64 |
July | 0.338462E+10 | 2072.36 | 17-JUL-21:00 | 29.00 | 13.54 | 0.963727E+09 | 569.55 | 12-JUL-22:10 | 29.00 | 13.54 |
August | 0.341333E+10 | 2171.27 | 16-AUG-20:10 | 28.50 | 11.68 | 0.968404E+09 | 569.59 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.316463E+10 | 2044.01 | 12-SEP-20:04 | 23.72 | 13.29 | 0.931536E+09 | 569.63 | 01-SEP-01:10 | 23.72 | 13.29 |
October | 0.271575E+10 | 1859.80 | 11-OCT-20:10 | 10.83 | 5.03 | 0.918146E+09 | 569.53 | 11-OCT-00:20 | 10.83 | 5.03 |
November | 0.244221E+10 | 1622.45 | 07-NOV-21:10 | 7.00 | 1.69 | 0.867769E+09 | 569.53 | 08-NOV-01:19 | 7.00 | 1.61 |
December | 0.228211E+10 | 1361.83 | 04-DEC-22:00 | 7.00 | 0.68 | 0.859342E+09 | 569.51 | 01-DEC-22:19 | 7.00 | 0.68 |
Annual Sum or Average | 0.329373E+11 | 0.108085E+11 | ||||||||
Minimum of Months | 0.214112E+10 | 1361.83 | 2.00 | -0.8 | 0.791257E+09 | 569.51 | 1.00 | -0.8 | ||
Maximum of Months | 0.341333E+10 | 2171.27 | 29.45 | 13.54 | 0.968404E+09 | 569.63 | 29.45 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147686E+10 | 882.72 | 20-JAN-14:00 | 21.00 | 6.96 | 0.162257E+09 | 108.39 | 24-JAN-22:10 | 3.00 | 0.25 |
February | 0.112849E+10 | 874.94 | 18-FEB-13:50 | 20.00 | 7.73 | 0.144658E+09 | 108.71 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.158735E+10 | 943.19 | 15-MAR-10:33 | 15.67 | 4.43 | 0.166674E+09 | 116.47 | 15-MAR-21:19 | 12.67 | 3.04 |
April | 0.158057E+10 | 898.75 | 21-APR-10:33 | 13.33 | 5.84 | 0.161862E+09 | 112.55 | 21-APR-21:10 | 6.00 | 4.11 |
May | 0.203088E+10 | 1052.02 | 17-MAY-21:00 | 17.00 | 8.20 | 0.186183E+09 | 120.45 | 17-MAY-21:00 | 18.00 | 9.24 |
June | 0.253627E+10 | 1817.05 | 26-JUN-20:00 | 32.70 | 13.66 | 0.196520E+09 | 120.46 | 07-JUN-21:10 | 32.70 | 13.66 |
July | 0.268118E+10 | 1846.05 | 17-JUL-20:00 | 30.00 | 13.88 | 0.203249E+09 | 120.46 | 15-JUL-00:10 | 30.00 | 13.88 |
August | 0.255093E+10 | 1700.23 | 16-AUG-20:00 | 29.00 | 11.91 | 0.203157E+09 | 120.46 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.227951E+10 | 1577.81 | 11-SEP-20:00 | 19.40 | 11.27 | 0.191979E+09 | 120.46 | 20-SEP-21:10 | 15.32 | 11.76 |
October | 0.182292E+10 | 993.99 | 11-OCT-13:00 | 26.00 | 9.45 | 0.177138E+09 | 119.66 | 11-OCT-21:19 | 9.33 | 4.48 |
November | 0.152495E+10 | 925.17 | 07-NOV-12:00 | 20.00 | 7.57 | 0.160772E+09 | 114.06 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 0.123316E+10 | 843.84 | 03-DEC-13:00 | 17.20 | 6.28 | 0.159590E+09 | 108.59 | 04-DEC-22:10 | 7.17 | 0.72 |
Annual Sum or Average | 0.224331E+11 | 0.211404E+10 | ||||||||
Minimum of Months | 0.112849E+10 | 843.84 | 13.33 | 4.43 | 0.144658E+09 | 108.39 | 2.00 | -0.8 | ||
Maximum of Months | 0.268118E+10 | 1846.05 | 32.70 | 13.88 | 0.203249E+09 | 120.46 | 32.70 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.711017E+09 | 481.62 | 20-JAN-14:00 | 21.00 | 6.96 | 0.121930E+09 | 79.32 | 20-JAN-22:40 | 7.33 | 1.76 |
February | 0.506897E+09 | 479.28 | 18-FEB-13:50 | 20.00 | 7.73 | 0.109372E+09 | 79.44 | 27-FEB-22:40 | 2.00 | -0.8 |
March | 0.757299E+09 | 504.95 | 15-MAR-10:33 | 15.67 | 4.43 | 0.125288E+09 | 85.75 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.778833E+09 | 480.41 | 21-APR-10:33 | 13.33 | 5.84 | 0.121381E+09 | 83.03 | 20-APR-22:10 | 13.33 | 5.84 |
May | 0.106897E+10 | 531.10 | 18-MAY-10:33 | 22.00 | 11.41 | 0.139473E+09 | 90.01 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.127640E+10 | 830.25 | 26-JUN-19:10 | 35.03 | 14.34 | 0.149747E+09 | 92.66 | 07-JUN-21:10 | 35.03 | 14.34 |
July | 0.134226E+10 | 823.63 | 17-JUL-21:00 | 29.00 | 13.54 | 0.155245E+09 | 92.66 | 15-JUL-00:10 | 29.00 | 13.54 |
August | 0.128406E+10 | 737.71 | 16-AUG-20:10 | 28.50 | 11.68 | 0.154704E+09 | 92.66 | 10-AUG-21:10 | 28.50 | 11.68 |
September | 0.116671E+10 | 632.24 | 12-SEP-21:00 | 23.30 | 12.99 | 0.145122E+09 | 92.66 | 08-SEP-21:00 | 23.30 | 12.99 |
October | 0.924252E+09 | 540.00 | 11-OCT-13:05 | 26.17 | 9.50 | 0.132585E+09 | 87.92 | 11-OCT-21:30 | 9.00 | 4.40 |
November | 0.758970E+09 | 503.38 | 07-NOV-14:00 | 22.00 | 7.34 | 0.120522E+09 | 83.70 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.576095E+09 | 456.50 | 03-DEC-13:00 | 17.20 | 6.28 | 0.120488E+09 | 79.74 | 04-DEC-23:10 | 7.83 | 0.81 |
Annual Sum or Average | 0.111518E+11 | 0.159586E+10 | ||||||||
Minimum of Months | 0.506897E+09 | 456.50 | 13.33 | 4.43 | 0.109372E+09 | 79.32 | 2.00 | -0.8 | ||
Maximum of Months | 0.134226E+10 | 830.25 | 35.03 | 14.34 | 0.155245E+09 | 92.66 | 35.03 | 14.34 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490595E+11 | 37699.63 | 20-JAN-21:00 | 7.00 | 1.60 | 0.607751E+09 | 381.79 | 18-JAN-22:10 | 7.00 | 1.60 |
February | 0.440626E+11 | 37735.05 | 27-FEB-21:00 | 4.00 | 0.39 | 0.547966E+09 | 381.74 | 27-FEB-22:10 | 2.00 | -0.8 |
March | 0.497420E+11 | 38292.78 | 14-MAR-20:00 | 16.00 | 5.00 | 0.610673E+09 | 381.81 | 16-MAR-21:10 | 10.00 | 4.14 |
April | 0.480241E+11 | 38340.42 | 20-APR-20:00 | 15.00 | 7.97 | 0.590948E+09 | 381.81 | 07-APR-21:10 | 15.00 | 7.97 |
May | 0.514022E+11 | 38652.73 | 16-MAY-20:00 | 19.00 | 9.69 | 0.615394E+09 | 381.86 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.515528E+11 | 39226.26 | 26-JUN-20:00 | 32.70 | 13.66 | 0.600302E+09 | 381.94 | 27-JUN-21:10 | 23.43 | 12.33 |
July | 0.530361E+11 | 39213.42 | 17-JUL-20:00 | 30.00 | 13.88 | 0.618826E+09 | 381.86 | 28-JUL-21:10 | 16.00 | 15.35 |
August | 0.531632E+11 | 39158.38 | 16-AUG-20:00 | 29.00 | 11.91 | 0.619803E+09 | 381.99 | 25-AUG-21:10 | 24.00 | 14.43 |
September | 0.506578E+11 | 38846.51 | 08-SEP-20:00 | 22.20 | 9.52 | 0.597876E+09 | 381.93 | 08-SEP-21:10 | 21.60 | 10.29 |
October | 0.502151E+11 | 38238.51 | 11-OCT-20:00 | 11.00 | 5.10 | 0.610740E+09 | 381.87 | 04-OCT-21:10 | 11.00 | 5.10 |
November | 0.478736E+11 | 37909.26 | 09-NOV-21:00 | 9.00 | 7.27 | 0.588562E+09 | 381.82 | 06-NOV-22:10 | 9.00 | 7.27 |
December | 0.482588E+11 | 37515.45 | 04-DEC-21:00 | 7.00 | 0.68 | 0.605121E+09 | 381.77 | 28-DEC-22:10 | 7.17 | 1.69 |
Annual Sum or Average | 0.597048E+12 | 0.721396E+10 | ||||||||
Minimum of Months | 0.440626E+11 | 37515.45 | 4.00 | 0.39 | 0.547966E+09 | 381.74 | 2.00 | -0.8 | ||
Maximum of Months | 0.531632E+11 | 39226.26 | 32.70 | 13.88 | 0.619803E+09 | 381.99 | 24.00 | 15.35 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203360E+11 | 17403.08 | 20-JAN-13:00 | 21.00 | 6.97 | 0.102568E+11 | 6461.76 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.175077E+11 | 17855.52 | 18-FEB-13:10 | 20.00 | 7.74 | 0.912450E+10 | 6461.74 | 18-FEB-02:20 | 20.00 | 7.74 |
March | 0.190676E+11 | 16451.52 | 11-MAR-13:00 | 17.00 | 5.47 | 0.101717E+11 | 6462.59 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.164391E+11 | 12131.59 | 07-APR-12:30 | 20.50 | 8.13 | 0.968026E+10 | 6461.86 | 01-APR-01:19 | 20.50 | 8.13 |
May | 0.190549E+11 | 9997.91 | 10-MAY-21:10 | 20.33 | 7.92 | 0.105818E+11 | 6462.68 | 15-MAY-21:40 | 13.33 | 9.13 |
June | 0.217015E+11 | 11674.56 | 26-JUN-21:10 | 28.17 | 11.17 | 0.105792E+11 | 6462.73 | 06-JUN-22:10 | 28.17 | 11.17 |
July | 0.226382E+11 | 11727.39 | 17-JUL-21:10 | 28.50 | 13.44 | 0.108992E+11 | 6462.69 | 03-JUL-22:10 | 28.50 | 13.44 |
August | 0.239596E+11 | 13662.13 | 26-AUG-12:40 | 31.67 | 13.33 | 0.109622E+11 | 6462.72 | 11-AUG-22:10 | 31.67 | 13.33 |
September | 0.233645E+11 | 15999.24 | 28-SEP-12:50 | 30.42 | 11.32 | 0.105435E+11 | 6462.71 | 01-SEP-00:49 | 30.42 | 11.32 |
October | 0.210574E+11 | 16482.08 | 08-OCT-12:00 | 21.00 | 8.76 | 0.103988E+11 | 6461.84 | 21-OCT-01:19 | 3.67 | -1.7 |
November | 0.200919E+11 | 17800.76 | 05-NOV-12:00 | 20.00 | 5.63 | 0.994516E+10 | 6461.79 | 18-NOV-02:20 | 5.33 | 2.19 |
December | 0.183605E+11 | 17155.57 | 17-DEC-12:50 | 17.67 | 5.69 | 0.990536E+10 | 6461.74 | 02-DEC-02:20 | 17.67 | 5.69 |
Annual Sum or Average | 0.243579E+12 | 0.123048E+12 | ||||||||
Minimum of Months | 0.164391E+11 | 9997.91 | 17.00 | 5.47 | 0.912450E+10 | 6461.74 | 3.67 | -1.7 | ||
Maximum of Months | 0.239596E+11 | 17855.52 | 31.67 | 13.44 | 0.109622E+11 | 6462.73 | 31.67 | 13.44 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.600082E+11 | 35980.42 | 20-JAN-22:10 | 7.83 | 2.00 | 0.316818E+11 | 19184.91 | 21-JAN-02:20 | 6.00 | 0.98 |
February | 0.524164E+11 | 34282.22 | 17-FEB-22:10 | 7.00 | 3.16 | 0.282119E+11 | 19184.96 | 25-FEB-02:20 | -0.3 | -1.6 |
March | 0.602282E+11 | 38256.49 | 15-MAR-21:10 | 12.83 | 3.06 | 0.314717E+11 | 19185.99 | 14-MAR-21:10 | 12.83 | 3.06 |
April | 0.560734E+11 | 35143.87 | 07-APR-21:10 | 11.83 | 6.33 | 0.302511E+11 | 19185.21 | 01-APR-01:19 | 11.83 | 6.33 |
May | 0.654368E+11 | 37440.17 | 17-MAY-21:10 | 17.17 | 8.37 | 0.321995E+11 | 19186.11 | 15-MAY-21:40 | 17.17 | 8.37 |
June | 0.737587E+11 | 42812.80 | 26-JUN-20:10 | 32.05 | 13.25 | 0.315765E+11 | 19186.51 | 01-JUN-01:10 | 32.05 | 13.25 |
July | 0.766243E+11 | 42710.18 | 17-JUL-21:10 | 28.50 | 13.44 | 0.325316E+11 | 19186.21 | 12-JUL-22:10 | 28.50 | 13.44 |
August | 0.777789E+11 | 43264.55 | 16-AUG-20:10 | 28.50 | 11.68 | 0.327016E+11 | 19186.64 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.735694E+11 | 42030.33 | 12-SEP-21:10 | 22.93 | 12.81 | 0.315571E+11 | 19188.16 | 01-SEP-01:10 | 22.93 | 12.81 |
October | 0.654310E+11 | 39404.65 | 11-OCT-20:10 | 10.83 | 5.03 | 0.319195E+11 | 19185.10 | 21-OCT-01:19 | 3.67 | -1.7 |
November | 0.596762E+11 | 36749.37 | 07-NOV-22:10 | 7.00 | 2.01 | 0.306917E+11 | 19185.15 | 10-NOV-05:19 | 6.67 | 5.25 |
December | 0.564640E+11 | 33770.13 | 04-DEC-22:10 | 7.17 | 0.72 | 0.308663E+11 | 19185.24 | 18-DEC-05:19 | 2.00 | -2.3 |
Annual Sum or Average | 0.777466E+12 | 0.375660E+12 | ||||||||
Minimum of Months | 0.524164E+11 | 33770.13 | 7.00 | 0.72 | 0.282119E+11 | 19184.91 | -0.3 | -2.3 | ||
Maximum of Months | 0.777789E+11 | 43264.55 | 32.05 | 13.44 | 0.327016E+11 | 19188.16 | 32.05 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369199E+09 | 4051.46 | 23-JAN-16:01 | 18.17 | 6.14 | 96862314.03 | 56.69 | 06-JAN-04:19 | 18.17 | 6.14 |
February | 0.381963E+09 | 4006.51 | 26-FEB-16:01 | 17.67 | 5.08 | 87154699.57 | 56.69 | 07-FEB-04:19 | 17.67 | 5.08 |
March | 0.711002E+09 | 4309.42 | 13-MAR-15:01 | 23.00 | 6.97 | 96795552.98 | 56.69 | 16-MAR-00:00 | 10.00 | 1.96 |
April | 0.500589E+09 | 4195.71 | 07-APR-15:01 | 21.00 | 7.80 | 93369192.53 | 56.69 | 07-APR-23:10 | 10.00 | 5.38 |
May | 0.118463E+10 | 4313.94 | 10-MAY-15:01 | 25.00 | 8.98 | 98645599.82 | 56.69 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.240821E+10 | 4459.62 | 27-JUN-15:01 | 33.38 | 14.35 | 95945114.39 | 56.69 | 20-JUN-23:10 | 33.38 | 14.35 |
July | 0.233044E+10 | 4463.23 | 01-JUL-18:01 | 27.67 | 10.47 | 99054001.96 | 56.69 | 25-JUL-23:10 | 19.83 | 14.74 |
August | 0.236835E+10 | 4463.45 | 17-AUG-15:01 | 31.00 | 12.21 | 99128935.05 | 56.69 | 20-AUG-01:30 | 20.00 | 15.91 |
September | 0.197156E+10 | 4483.06 | 28-SEP-15:01 | 29.50 | 11.04 | 95714133.74 | 56.69 | 01-SEP-02:39 | 29.50 | 11.04 |
October | 0.984345E+09 | 4439.63 | 11-OCT-15:01 | 25.67 | 9.32 | 97316091.21 | 56.69 | 10-OCT-00:40 | 25.67 | 9.32 |
November | 0.492225E+09 | 4192.14 | 05-NOV-15:01 | 20.67 | 6.59 | 93932527.66 | 56.69 | 09-NOV-05:19 | 8.33 | 4.83 |
December | 0.230161E+09 | 3944.11 | 02-DEC-16:01 | 17.33 | 5.85 | 95797500.00 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.139327E+11 | 0.114972E+10 | ||||||||
Minimum of Months | 0.230161E+09 | 3944.11 | 17.33 | 5.08 | 87154699.57 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.240821E+10 | 4483.06 | 33.38 | 14.35 | 99128935.05 | 56.69 | 33.38 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72204427.13 | 3877.45 | 23-JAN-16:01 | 18.17 | 6.14 | 94871887.81 | 56.69 | 13-JAN-04:19 | 18.17 | 6.14 |
February | 99127904.56 | 3847.11 | 26-FEB-16:01 | 17.67 | 5.08 | 85654399.45 | 56.69 | 07-FEB-04:19 | 17.67 | 5.08 |
March | 0.312378E+09 | 4392.82 | 08-MAR-17:11 | 14.33 | 3.92 | 97538598.96 | 75.10 | 13-MAR-18:10 | 17.33 | 4.68 |
April | 0.275874E+09 | 4476.34 | 08-APR-18:01 | 13.50 | 4.30 | 94433618.05 | 78.93 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.879561E+09 | 4421.40 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103443E+09 | 82.16 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.210778E+10 | 4607.49 | 27-JUN-08:51 | 25.00 | 10.85 | 0.102913E+09 | 84.24 | 22-JUN-18:10 | 25.00 | 10.85 |
July | 0.197454E+10 | 4857.68 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106389E+09 | 88.16 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.184714E+10 | 4545.94 | 18-AUG-08:11 | 26.33 | 11.15 | 0.106362E+09 | 82.54 | 03-AUG-21:10 | 26.33 | 11.15 |
September | 0.130517E+10 | 4434.98 | 11-SEP-08:51 | 25.00 | 12.16 | 0.102505E+09 | 78.88 | 12-SEP-21:10 | 22.93 | 12.81 |
October | 0.424341E+09 | 4282.76 | 14-OCT-16:11 | 14.00 | 3.81 | 98336705.51 | 64.64 | 10-OCT-20:40 | 14.00 | 3.81 |
November | 0.115555E+09 | 3999.52 | 05-NOV-15:01 | 20.67 | 6.59 | 92508586.78 | 56.69 | 06-NOV-22:10 | 7.83 | 1.71 |
December | 35326323.00 | 3789.11 | 02-DEC-16:01 | 17.33 | 5.85 | 94166653.70 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.944899E+10 | 0.117912E+10 | ||||||||
Minimum of Months | 35326323.00 | 3789.11 | 13.50 | 3.81 | 85654399.45 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.210778E+10 | 4857.68 | 26.33 | 12.16 | 0.106389E+09 | 88.16 | 26.33 | 12.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442660E+09 | 874.73 | 20-JAN-12:40 | 20.67 | 7.18 | 0.00 | 0.00 | 01-JAN-00:10 | 20.67 | 7.18 |
February | 0.312962E+09 | 836.91 | 18-FEB-13:00 | 20.00 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.74 |
March | 0.316140E+09 | 756.74 | 11-MAR-13:00 | 17.00 | 5.47 | 0.00 | 0.00 | 01-MAR-00:10 | 17.00 | 5.47 |
April | 0.123898E+09 | 469.01 | 08-APR-13:00 | 16.00 | 5.15 | 0.00 | 0.00 | 01-APR-00:10 | 16.00 | 5.15 |
May | 0.285079E+09 | 367.98 | 05-MAY-13:10 | 22.17 | 10.95 | 0.00 | 0.00 | 01-MAY-00:10 | 22.17 | 10.95 |
June | 0.533367E+09 | 441.50 | 14-JUN-13:30 | 34.95 | 13.21 | 0.00 | 0.00 | 01-JUN-00:10 | 34.95 | 13.21 |
July | 0.580582E+09 | 477.92 | 23-JUL-13:00 | 34.00 | 16.01 | 0.00 | 0.00 | 01-JUL-00:10 | 34.00 | 16.01 |
August | 0.661739E+09 | 608.16 | 31-AUG-12:50 | 30.00 | 12.10 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 12.10 |
September | 0.672521E+09 | 779.63 | 28-SEP-13:00 | 30.50 | 11.31 | 0.00 | 0.00 | 01-SEP-00:10 | 30.50 | 11.31 |
October | 0.497393E+09 | 811.84 | 10-OCT-12:30 | 23.50 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 23.50 | 7.91 |
November | 0.416601E+09 | 869.34 | 07-NOV-12:20 | 20.00 | 7.38 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.38 |
December | 0.272979E+09 | 787.51 | 17-DEC-13:30 | 18.00 | 5.77 | 0.00 | 0.00 | 01-DEC-00:10 | 18.00 | 5.77 |
Annual Sum or Average | 0.511592E+10 | 0.00 | ||||||||
Minimum of Months | 0.123898E+09 | 367.98 | 16.00 | 5.15 | 0.00 | 0.00 | 16.00 | 5.15 | ||
Maximum of Months | 0.672521E+09 | 874.73 | 34.95 | 16.01 | 0.00 | 0.00 | 34.95 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57829939.21 | 1006.12 | 21-JAN-09:01 | 13.00 | 3.75 | 95196737.06 | 56.69 | 06-JAN-04:19 | 13.00 | 3.75 |
February | 48976337.39 | 1023.17 | 18-FEB-16:01 | 17.83 | 7.37 | 85901694.91 | 56.69 | 10-FEB-04:19 | 17.83 | 7.37 |
March | 0.150341E+09 | 1172.57 | 14-MAR-15:01 | 22.83 | 7.50 | 96548325.87 | 63.51 | 14-MAR-20:49 | 13.50 | 4.00 |
April | 0.202721E+09 | 1151.10 | 27-APR-15:01 | 20.83 | 10.41 | 93932971.13 | 64.75 | 20-APR-20:40 | 20.83 | 10.41 |
May | 0.482101E+09 | 1234.88 | 17-MAY-15:01 | 26.83 | 11.93 | 0.101094E+09 | 75.59 | 30-MAY-21:10 | 14.00 | 11.46 |
June | 0.772628E+09 | 1314.20 | 12-JUN-08:61 | 26.97 | 12.63 | 0.100541E+09 | 79.15 | 22-JUN-21:49 | 16.52 | 14.01 |
July | 0.792671E+09 | 1356.22 | 01-JUL-08:61 | 26.00 | 9.47 | 0.104098E+09 | 80.31 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.698845E+09 | 1259.27 | 01-AUG-21:51 | 21.00 | 10.09 | 0.103702E+09 | 78.14 | 03-AUG-21:19 | 21.33 | 15.95 |
September | 0.534861E+09 | 1259.36 | 10-SEP-08:51 | 26.60 | 13.23 | 99452510.44 | 75.68 | 11-SEP-21:49 | 17.20 | 10.39 |
October | 0.218845E+09 | 1217.53 | 11-OCT-15:01 | 25.67 | 9.32 | 96985034.91 | 62.60 | 10-OCT-20:40 | 25.67 | 9.32 |
November | 86315113.45 | 1076.93 | 06-NOV-16:01 | 20.50 | 6.17 | 92587951.53 | 56.69 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 43167133.93 | 994.46 | 02-DEC-16:01 | 17.33 | 5.85 | 94783775.17 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.408930E+10 | 0.116482E+10 | ||||||||
Minimum of Months | 43167133.93 | 994.46 | 13.00 | 3.75 | 85901694.91 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.792671E+09 | 1356.22 | 26.97 | 13.23 | 0.104098E+09 | 80.31 | 25.67 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355791E+09 | 3519.24 | 23-JAN-16:01 | 18.17 | 6.14 | 97103119.04 | 56.69 | 21-JAN-02:20 | 18.17 | 6.14 |
February | 0.418568E+09 | 3496.60 | 18-FEB-16:01 | 17.83 | 7.37 | 87408667.07 | 56.69 | 10-FEB-04:19 | 17.83 | 7.37 |
March | 0.754252E+09 | 3747.29 | 13-MAR-15:01 | 23.00 | 6.97 | 97138914.53 | 56.69 | 15-MAR-02:20 | 13.00 | 4.41 |
April | 0.583998E+09 | 3646.59 | 07-APR-15:01 | 21.00 | 7.80 | 93753563.44 | 56.69 | 07-APR-22:19 | 10.67 | 6.02 |
May | 0.128233E+10 | 3787.92 | 04-MAY-15:01 | 24.83 | 10.09 | 98929802.74 | 56.69 | 30-MAY-21:19 | 14.00 | 11.37 |
June | 0.254697E+10 | 3890.03 | 27-JUN-15:01 | 33.38 | 14.35 | 96022839.64 | 56.69 | 17-JUN-23:49 | 33.38 | 14.35 |
July | 0.259005E+10 | 3999.30 | 01-JUL-08:61 | 26.00 | 9.47 | 99119175.97 | 56.69 | 31-JUL-22:49 | 18.55 | 17.15 |
August | 0.260644E+10 | 3890.83 | 17-AUG-15:01 | 31.00 | 12.21 | 99223630.06 | 56.69 | 20-AUG-04:19 | 19.33 | 14.57 |
September | 0.207158E+10 | 3894.64 | 28-SEP-15:01 | 29.50 | 11.04 | 95854385.60 | 56.69 | 01-SEP-00:00 | 29.50 | 11.04 |
October | 0.945054E+09 | 3853.47 | 11-OCT-15:01 | 25.67 | 9.32 | 97506382.18 | 56.69 | 10-OCT-00:10 | 25.67 | 9.32 |
November | 0.474066E+09 | 3645.12 | 05-NOV-15:01 | 20.67 | 6.59 | 93996596.37 | 56.69 | 06-NOV-22:19 | 7.67 | 1.63 |
December | 0.232883E+09 | 3453.50 | 02-DEC-16:01 | 17.33 | 5.85 | 95945996.71 | 56.69 | 26-DEC-04:19 | 1.00 | -2.4 |
Annual Sum or Average | 0.148620E+11 | 0.115200E+10 | ||||||||
Minimum of Months | 0.232883E+09 | 3453.50 | 17.33 | 5.85 | 87408667.07 | 56.69 | 1.00 | -2.4 | ||
Maximum of Months | 0.260644E+10 | 3999.30 | 33.38 | 14.35 | 99223630.06 | 56.69 | 33.38 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76508825.12 | 3320.69 | 20-JAN-09:01 | 10.67 | 3.20 | 94650529.22 | 56.69 | 24-JAN-04:19 | 3.00 | -1.4 |
February | 0.130387E+09 | 3373.92 | 18-FEB-16:01 | 17.83 | 7.37 | 85775770.23 | 56.69 | 11-FEB-02:20 | 17.83 | 7.37 |
March | 0.367705E+09 | 3614.70 | 14-MAR-15:01 | 22.83 | 7.50 | 97032941.25 | 65.50 | 14-MAR-20:40 | 14.00 | 4.22 |
April | 0.375309E+09 | 4120.11 | 19-APR-08:51 | 18.00 | 8.66 | 94190571.01 | 65.17 | 20-APR-20:30 | 14.50 | 7.98 |
May | 0.100327E+10 | 4223.18 | 10-MAY-08:51 | 20.00 | 9.05 | 0.102718E+09 | 76.54 | 16-MAY-21:40 | 16.33 | 9.88 |
June | 0.217018E+10 | 4696.79 | 27-JUN-08:32 | 24.60 | 10.38 | 0.104122E+09 | 81.92 | 22-JUN-21:40 | 24.60 | 10.38 |
July | 0.217204E+10 | 4579.24 | 01-JUL-07:42 | 25.50 | 9.48 | 0.107357E+09 | 83.43 | 05-JUL-21:10 | 14.50 | 9.06 |
August | 0.202061E+10 | 4235.46 | 02-AUG-08:51 | 20.00 | 10.42 | 0.107109E+09 | 81.77 | 03-AUG-21:19 | 21.33 | 15.95 |
September | 0.140806E+10 | 4344.57 | 07-SEP-08:51 | 22.70 | 11.26 | 0.101866E+09 | 78.23 | 08-SEP-21:30 | 21.60 | 10.66 |
October | 0.415486E+09 | 4119.84 | 11-OCT-08:51 | 20.20 | 7.65 | 97731782.93 | 63.38 | 10-OCT-20:40 | 20.20 | 7.65 |
November | 0.128065E+09 | 3475.95 | 07-NOV-16:01 | 20.00 | 7.03 | 92221244.02 | 56.69 | 01-NOV-04:19 | 20.00 | 7.03 |
December | 45623030.90 | 3290.00 | 03-DEC-09:01 | 9.50 | 2.25 | 93973569.57 | 56.69 | 23-DEC-02:20 | -20.1 | -20.3 |
Annual Sum or Average | 0.103132E+11 | 0.117875E+10 | ||||||||
Minimum of Months | 45623030.90 | 3290.00 | 9.50 | 2.25 | 85775770.23 | 56.69 | -20.1 | -20.3 | ||
Maximum of Months | 0.217204E+10 | 4696.79 | 25.50 | 11.26 | 0.107357E+09 | 83.43 | 24.60 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251032E+10 | 1584.45 | 24-JAN-13:20 | 17.33 | 5.98 | 0.126628E+10 | 824.09 | 24-JAN-22:40 | 3.00 | 0.25 |
February | 0.192360E+10 | 1613.75 | 18-FEB-13:50 | 20.00 | 7.73 | 0.113910E+10 | 824.66 | 27-FEB-22:40 | 2.00 | -0.8 |
March | 0.260842E+10 | 1700.45 | 15-MAR-12:50 | 20.33 | 5.94 | 0.131077E+10 | 918.91 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.251725E+10 | 1511.96 | 21-APR-10:33 | 13.33 | 5.84 | 0.124258E+10 | 832.76 | 12-APR-21:40 | 13.33 | 5.84 |
May | 0.338546E+10 | 1681.43 | 18-MAY-10:33 | 22.00 | 11.41 | 0.142640E+10 | 910.57 | 17-MAY-22:10 | 22.00 | 11.41 |
June | 0.415793E+10 | 2845.94 | 26-JUN-18:30 | 36.60 | 14.84 | 0.154674E+10 | 951.89 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.437885E+10 | 2572.28 | 01-JUL-18:30 | 27.00 | 10.29 | 0.160588E+10 | 951.85 | 15-JUL-00:10 | 21.83 | 14.36 |
August | 0.429356E+10 | 2592.58 | 11-AUG-18:17 | 30.33 | 11.29 | 0.160935E+10 | 951.88 | 10-AUG-21:19 | 30.33 | 11.29 |
September | 0.390586E+10 | 2344.45 | 12-SEP-18:03 | 27.33 | 13.46 | 0.152411E+10 | 951.91 | 01-SEP-01:10 | 27.33 | 13.46 |
October | 0.306125E+10 | 1823.40 | 11-OCT-13:05 | 26.17 | 9.50 | 0.139815E+10 | 928.16 | 11-OCT-21:40 | 8.67 | 4.30 |
November | 0.250669E+10 | 1663.84 | 07-NOV-14:00 | 22.00 | 7.34 | 0.124513E+10 | 850.94 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.187476E+10 | 1489.08 | 17-DEC-13:00 | 18.00 | 5.78 | 0.123036E+10 | 790.66 | 04-DEC-22:49 | 18.00 | 5.78 |
Annual Sum or Average | 0.371239E+11 | 0.165449E+11 | ||||||||
Minimum of Months | 0.187476E+10 | 1489.08 | 13.33 | 5.78 | 0.113910E+10 | 790.66 | 2.00 | -0.8 | ||
Maximum of Months | 0.437885E+10 | 2845.94 | 36.60 | 14.84 | 0.160935E+10 | 951.91 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320413E+09 | 4311.12 | 23-JAN-16:01 | 18.17 | 6.14 | 96337444.08 | 56.70 | 25-JAN-22:10 | 2.67 | 0.07 |
February | 0.345092E+09 | 4251.32 | 26-FEB-16:01 | 17.67 | 5.08 | 86793409.24 | 56.69 | 21-FEB-05:19 | 17.67 | 5.08 |
March | 0.676360E+09 | 4587.83 | 13-MAR-15:01 | 23.00 | 6.97 | 96439139.90 | 56.69 | 13-MAR-22:49 | 10.83 | 2.24 |
April | 0.491306E+09 | 4460.14 | 07-APR-15:01 | 21.00 | 7.80 | 93011149.26 | 56.69 | 20-APR-22:30 | 13.50 | 7.80 |
May | 0.113230E+10 | 4585.56 | 10-MAY-15:01 | 25.00 | 8.98 | 98500762.79 | 56.70 | 05-MAY-03:30 | 25.00 | 8.98 |
June | 0.244522E+10 | 4750.09 | 27-JUN-15:01 | 33.38 | 14.35 | 95903781.45 | 56.69 | 20-JUN-21:00 | 33.38 | 14.35 |
July | 0.232514E+10 | 4749.02 | 01-JUL-18:01 | 27.67 | 10.47 | 99002683.54 | 56.70 | 25-JUL-21:00 | 20.00 | 15.92 |
August | 0.236697E+10 | 4749.44 | 17-AUG-15:01 | 31.00 | 12.21 | 99073762.08 | 56.69 | 04-AUG-21:49 | 31.00 | 12.21 |
September | 0.187759E+10 | 4772.88 | 28-SEP-15:01 | 29.50 | 11.04 | 95571940.31 | 56.69 | 20-SEP-21:30 | 29.50 | 11.04 |
October | 0.881862E+09 | 4720.09 | 11-OCT-15:01 | 25.67 | 9.32 | 96993395.23 | 56.70 | 08-OCT-04:10 | 25.67 | 9.32 |
November | 0.439449E+09 | 4466.30 | 05-NOV-15:01 | 20.67 | 6.59 | 93529478.05 | 56.69 | 09-NOV-23:40 | 8.00 | 7.22 |
December | 0.200343E+09 | 4200.43 | 02-DEC-16:01 | 17.33 | 5.85 | 95268807.70 | 56.69 | 20-DEC-05:19 | -19.0 | -19.2 |
Annual Sum or Average | 0.135020E+11 | 0.114643E+10 | ||||||||
Minimum of Months | 0.200343E+09 | 4200.43 | 17.33 | 5.08 | 86793409.24 | 56.69 | -19.0 | -19.2 | ||
Maximum of Months | 0.244522E+10 | 4772.88 | 33.38 | 14.35 | 99073762.08 | 56.70 | 33.38 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54669965.76 | 4095.62 | 23-JAN-16:01 | 18.17 | 6.14 | 94235727.08 | 56.69 | 12-JAN-05:19 | 18.17 | 6.14 |
February | 80700327.96 | 4061.21 | 26-FEB-16:01 | 17.67 | 5.08 | 85260173.49 | 56.69 | 08-FEB-05:19 | 17.67 | 5.08 |
March | 0.279652E+09 | 4767.60 | 08-MAR-17:11 | 14.33 | 3.92 | 97381243.75 | 82.58 | 31-MAR-18:10 | 14.33 | 7.61 |
April | 0.261559E+09 | 4833.25 | 08-APR-18:01 | 13.50 | 4.30 | 94343361.03 | 86.23 | 07-APR-18:10 | 13.50 | 4.30 |
May | 0.832137E+09 | 4754.82 | 27-MAY-16:11 | 14.33 | 8.19 | 0.103861E+09 | 89.22 | 09-MAY-18:10 | 14.33 | 8.19 |
June | 0.218824E+10 | 4910.08 | 27-JUN-08:51 | 25.00 | 10.85 | 0.102931E+09 | 89.88 | 22-JUN-21:10 | 25.00 | 10.85 |
July | 0.201838E+10 | 5100.03 | 01-JUL-08:61 | 26.00 | 9.47 | 0.106307E+09 | 92.34 | 03-JUL-21:10 | 16.00 | 9.77 |
August | 0.188477E+10 | 4807.99 | 13-AUG-21:51 | 16.00 | 8.07 | 0.106351E+09 | 87.02 | 03-AUG-21:10 | 16.00 | 8.07 |
September | 0.123934E+10 | 4638.00 | 11-SEP-08:51 | 25.00 | 12.16 | 0.102401E+09 | 79.04 | 15-SEP-18:10 | 18.35 | 8.17 |
October | 0.339750E+09 | 4667.19 | 08-OCT-18:11 | 13.33 | 7.54 | 98148628.97 | 66.06 | 05-OCT-18:10 | 13.33 | 7.54 |
November | 93309811.44 | 4234.47 | 05-NOV-15:01 | 20.67 | 6.59 | 92025051.31 | 56.69 | 01-NOV-04:19 | 20.67 | 6.59 |
December | 27106968.53 | 4009.97 | 02-DEC-16:01 | 17.33 | 5.85 | 93662053.50 | 56.69 | 20-DEC-05:19 | -19.0 | -19.2 |
Annual Sum or Average | 0.929961E+10 | 0.117691E+10 | ||||||||
Minimum of Months | 27106968.53 | 4009.97 | 13.33 | 3.92 | 85260173.49 | 56.69 | -19.0 | -19.2 | ||
Maximum of Months | 0.218824E+10 | 5100.03 | 26.00 | 12.16 | 0.106351E+09 | 92.34 | 25.00 | 10.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.845222E+09 | 2160.70 | 23-JAN-16:01 | 18.17 | 6.14 | 98038426.77 | 56.69 | 24-JAN-23:49 | 2.17 | 0.13 |
February | 0.681848E+09 | 2118.06 | 18-FEB-16:01 | 17.83 | 7.37 | 88103672.36 | 56.69 | 22-FEB-22:10 | 2.83 | 2.42 |
March | 0.714423E+09 | 2283.46 | 13-MAR-15:01 | 23.00 | 6.97 | 97266790.42 | 56.69 | 16-MAR-23:19 | 9.00 | 4.09 |
April | 0.395457E+09 | 2195.35 | 07-APR-15:01 | 21.00 | 7.80 | 93649293.82 | 56.69 | 27-APR-22:10 | 10.83 | 8.18 |
May | 0.684651E+09 | 2182.83 | 10-MAY-18:01 | 22.50 | 8.71 | 98559235.93 | 56.69 | 30-MAY-21:40 | 14.00 | 11.18 |
June | 0.122965E+10 | 2303.86 | 12-JUN-08:61 | 26.97 | 12.63 | 95864417.34 | 56.69 | 18-JUN-00:10 | 19.30 | 15.52 |
July | 0.131049E+10 | 2290.70 | 01-JUL-08:61 | 26.00 | 9.47 | 98992780.68 | 56.69 | 24-JUL-01:00 | 18.00 | 14.77 |
August | 0.144679E+10 | 2229.24 | 18-AUG-08:61 | 26.17 | 11.05 | 99063497.02 | 56.69 | 20-AUG-02:00 | 20.00 | 14.78 |
September | 0.138186E+10 | 2359.32 | 28-SEP-15:01 | 29.50 | 11.04 | 95719961.39 | 56.70 | 12-SEP-21:10 | 29.50 | 11.04 |
October | 0.987423E+09 | 2343.62 | 11-OCT-15:01 | 25.67 | 9.32 | 97650274.19 | 56.69 | 20-OCT-00:20 | 7.00 | 2.64 |
November | 0.878650E+09 | 2247.82 | 05-NOV-15:01 | 20.67 | 6.59 | 94893789.01 | 56.69 | 09-NOV-23:10 | 8.00 | 6.96 |
December | 0.616591E+09 | 2111.18 | 02-DEC-16:01 | 17.33 | 5.85 | 97392960.78 | 56.69 | 22-DEC-04:19 | -21.7 | -21.7 |
Annual Sum or Average | 0.111731E+11 | 0.115520E+10 | ||||||||
Minimum of Months | 0.395457E+09 | 2111.18 | 17.33 | 5.85 | 88103672.36 | 56.69 | -21.7 | -21.7 | ||
Maximum of Months | 0.144679E+10 | 2359.32 | 29.50 | 12.63 | 99063497.02 | 56.70 | 29.50 | 15.52 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304751E+11 | 18169.27 | 20-JAN-23:00 | 7.00 | 1.59 | 0.190230E+11 | 11347.59 | 09-JAN-05:19 | 7.00 | 1.59 |
February | 0.273031E+11 | 17975.64 | 27-FEB-22:10 | 2.00 | -0.8 | 0.171865E+11 | 11347.48 | 10-FEB-04:19 | 2.00 | -0.8 |
March | 0.328667E+11 | 20061.03 | 14-MAR-22:00 | 13.00 | 4.05 | 0.192170E+11 | 11348.77 | 14-MAR-21:10 | 13.00 | 4.05 |
April | 0.324713E+11 | 20179.53 | 20-APR-22:00 | 14.00 | 7.96 | 0.185963E+11 | 11347.40 | 04-APR-03:20 | 14.00 | 7.96 |
May | 0.384930E+11 | 21376.14 | 31-MAY-21:52 | 17.30 | 10.94 | 0.193342E+11 | 11349.00 | 15-MAY-21:40 | 17.30 | 10.94 |
June | 0.424960E+11 | 23264.80 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187609E+11 | 11391.60 | 30-JUN-21:19 | 26.13 | 11.13 |
July | 0.437929E+11 | 23161.44 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193099E+11 | 11388.54 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.430008E+11 | 22923.21 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193908E+11 | 11409.93 | 18-AUG-21:19 | 18.67 | 8.73 |
September | 0.391976E+11 | 22086.03 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187018E+11 | 11380.85 | 12-SEP-21:19 | 22.57 | 12.63 |
October | 0.341701E+11 | 20119.92 | 10-OCT-21:10 | 13.83 | 4.11 | 0.191874E+11 | 11347.47 | 24-OCT-03:20 | -2.0 | -2.0 |
November | 0.305277E+11 | 19114.06 | 09-NOV-23:00 | 8.00 | 6.87 | 0.184720E+11 | 11347.57 | 10-NOV-05:19 | 6.67 | 5.25 |
December | 0.292527E+11 | 18204.33 | 04-DEC-23:00 | 8.00 | 0.89 | 0.188476E+11 | 11347.48 | 19-DEC-04:19 | -16.1 | -16.3 |
Annual Sum or Average | 0.424047E+12 | 0.226027E+12 | ||||||||
Minimum of Months | 0.273031E+11 | 17975.64 | 2.00 | -0.8 | 0.171865E+11 | 11347.40 | -16.1 | -16.3 | ||
Maximum of Months | 0.437929E+11 | 23264.80 | 28.00 | 13.33 | 0.193908E+11 | 11409.93 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340296E+11 | 19827.11 | 20-JAN-22:10 | 7.83 | 2.00 | 0.191646E+11 | 11347.73 | 09-JAN-05:19 | 7.83 | 2.00 |
February | 0.305118E+11 | 19636.55 | 27-FEB-22:10 | 2.00 | -0.8 | 0.173177E+11 | 11347.50 | 03-FEB-04:19 | 2.00 | -0.8 |
March | 0.364902E+11 | 21457.61 | 14-MAR-21:05 | 13.00 | 3.83 | 0.193153E+11 | 11348.78 | 14-MAR-21:10 | 13.00 | 3.83 |
April | 0.361603E+11 | 21746.57 | 20-APR-21:10 | 14.00 | 7.96 | 0.186719E+11 | 11347.48 | 04-APR-03:20 | 14.00 | 7.96 |
May | 0.420372E+11 | 22726.49 | 31-MAY-21:10 | 17.88 | 12.24 | 0.193468E+11 | 11349.01 | 15-MAY-21:40 | 17.88 | 12.24 |
June | 0.453309E+11 | 24469.22 | 26-JUN-21:20 | 27.53 | 11.08 | 0.187616E+11 | 11402.66 | 29-JUN-21:19 | 20.70 | 11.71 |
July | 0.466733E+11 | 24361.45 | 17-JUL-21:20 | 28.00 | 13.33 | 0.193106E+11 | 11401.34 | 07-JUL-21:19 | 28.00 | 13.33 |
August | 0.458809E+11 | 24119.48 | 16-AUG-21:20 | 25.33 | 11.70 | 0.193920E+11 | 11423.49 | 18-AUG-21:19 | 18.67 | 8.73 |
September | 0.420976E+11 | 23276.99 | 12-SEP-21:20 | 22.57 | 12.63 | 0.187086E+11 | 11392.95 | 12-SEP-21:19 | 22.57 | 12.63 |
October | 0.375610E+11 | 21458.36 | 10-OCT-21:10 | 13.83 | 4.11 | 0.192503E+11 | 11347.54 | 24-OCT-03:20 | -2.0 | -2.0 |
November | 0.339691E+11 | 20609.86 | 09-NOV-22:10 | 8.00 | 6.42 | 0.185747E+11 | 11347.65 | 10-NOV-05:19 | 6.67 | 5.25 |
December | 0.327279E+11 | 19922.02 | 04-DEC-23:00 | 8.00 | 0.89 | 0.190418E+11 | 11347.58 | 22-DEC-00:20 | -20.3 | -20.4 |
Annual Sum or Average | 0.463470E+12 | 0.226856E+12 | ||||||||
Minimum of Months | 0.305118E+11 | 19636.55 | 2.00 | -0.8 | 0.173177E+11 | 11347.48 | -20.3 | -20.4 | ||
Maximum of Months | 0.466733E+11 | 24469.22 | 28.00 | 13.33 | 0.193920E+11 | 11423.49 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476718E+11 | 27120.11 | 20-JAN-11:40 | 19.33 | 7.26 | 0.188268E+11 | 11319.57 | 21-JAN-18:19 | 7.33 | 3.18 |
February | 0.429210E+11 | 27647.84 | 18-FEB-11:40 | 17.67 | 6.73 | 0.170018E+11 | 11319.72 | 25-FEB-18:19 | 7.67 | 3.07 |
March | 0.492862E+11 | 28780.81 | 15-MAR-10:33 | 15.67 | 4.43 | 0.188435E+11 | 11319.56 | 11-MAR-18:19 | 15.67 | 4.43 |
April | 0.479306E+11 | 28473.66 | 20-APR-10:33 | 19.33 | 8.37 | 0.182346E+11 | 11319.67 | 08-APR-17:19 | 19.33 | 8.37 |
May | 0.528543E+11 | 29062.89 | 16-MAY-10:33 | 24.67 | 11.32 | 0.188602E+11 | 11319.68 | 06-MAY-17:19 | 24.67 | 11.32 |
June | 0.547399E+11 | 30048.22 | 26-JUN-10:33 | 32.70 | 15.62 | 0.182651E+11 | 11319.65 | 17-JUN-17:19 | 32.70 | 15.62 |
July | 0.563351E+11 | 30257.73 | 23-JUL-10:40 | 29.67 | 15.92 | 0.188673E+11 | 11319.67 | 29-JUL-17:19 | 23.00 | 18.17 |
August | 0.561871E+11 | 30361.71 | 05-AUG-10:37 | 29.00 | 17.63 | 0.188745E+11 | 11319.65 | 05-AUG-17:19 | 21.33 | 16.54 |
September | 0.526434E+11 | 29663.30 | 04-SEP-10:33 | 26.83 | 13.23 | 0.182569E+11 | 11319.65 | 09-SEP-17:19 | 27.00 | 12.94 |
October | 0.499255E+11 | 28729.30 | 07-OCT-10:33 | 20.33 | 9.02 | 0.188446E+11 | 11319.70 | 21-OCT-17:10 | 11.67 | 4.94 |
November | 0.467342E+11 | 27886.41 | 05-NOV-10:40 | 18.00 | 5.62 | 0.182224E+11 | 11319.58 | 18-NOV-18:19 | 3.00 | 3.00 |
December | 0.462230E+11 | 26849.15 | 02-DEC-11:50 | 19.50 | 6.90 | 0.188158E+11 | 11319.64 | 23-DEC-18:19 | -17.0 | -17.3 |
Annual Sum or Average | 0.603452E+12 | 0.221913E+12 | ||||||||
Minimum of Months | 0.429210E+11 | 26849.15 | 15.67 | 4.43 | 0.170018E+11 | 11319.56 | -17.0 | -17.3 | ||
Maximum of Months | 0.563351E+11 | 30361.71 | 32.70 | 17.63 | 0.188745E+11 | 11319.72 | 32.70 | 18.17 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474617E+10 | 4000.95 | 20-JAN-14:00 | 21.00 | 6.96 | 0.130571E+10 | 847.09 | 20-JAN-22:40 | 7.33 | 1.76 |
February | 0.385773E+10 | 4052.28 | 18-FEB-13:50 | 20.00 | 7.73 | 0.118296E+10 | 830.29 | 27-FEB-22:30 | 2.00 | -0.8 |
March | 0.530623E+10 | 4523.11 | 15-MAR-14:10 | 20.83 | 6.19 | 0.136225E+10 | 948.22 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.541593E+10 | 3773.89 | 21-APR-10:33 | 13.33 | 5.84 | 0.130372E+10 | 899.10 | 20-APR-21:40 | 13.33 | 5.84 |
May | 0.789842E+10 | 4081.31 | 18-MAY-10:33 | 22.00 | 11.41 | 0.149241E+10 | 963.41 | 17-MAY-21:40 | 22.00 | 11.41 |
June | 0.101033E+11 | 6704.69 | 26-JUN-14:10 | 37.98 | 15.29 | 0.161852E+10 | 1007.47 | 07-JUN-21:10 | 37.98 | 15.29 |
July | 0.104827E+11 | 6674.74 | 23-JUL-13:00 | 34.00 | 16.01 | 0.167249E+10 | 1007.41 | 14-JUL-23:40 | 34.00 | 16.01 |
August | 0.104061E+11 | 6973.59 | 16-AUG-15:02 | 36.17 | 16.19 | 0.167051E+10 | 1007.45 | 25-AUG-22:10 | 23.67 | 16.10 |
September | 0.907897E+10 | 6524.96 | 09-SEP-12:50 | 32.62 | 13.01 | 0.155886E+10 | 1007.40 | 08-SEP-21:00 | 32.62 | 13.01 |
October | 0.646751E+10 | 4639.12 | 11-OCT-14:10 | 26.83 | 9.68 | 0.141754E+10 | 954.90 | 10-OCT-21:30 | 26.83 | 9.68 |
November | 0.513405E+10 | 4191.28 | 07-NOV-13:40 | 21.33 | 7.25 | 0.128735E+10 | 880.60 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.363108E+10 | 3661.83 | 03-DEC-13:00 | 17.20 | 6.28 | 0.129103E+10 | 818.50 | 04-DEC-22:40 | 7.67 | 0.83 |
Annual Sum or Average | 0.825282E+11 | 0.171633E+11 | ||||||||
Minimum of Months | 0.363108E+10 | 3661.83 | 13.33 | 5.84 | 0.118296E+10 | 818.50 | 2.00 | -0.8 | ||
Maximum of Months | 0.104827E+11 | 6973.59 | 37.98 | 16.19 | 0.167249E+10 | 1007.47 | 37.98 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94720371.52 | 1220.15 | 05-JAN-09:04 | -17.0 |
February | 0.241771E+09 | 1075.80 | 05-FEB-17:00 | -7.0 |
March | 0.126076E+09 | 1176.13 | 19-MAR-08:03 | -13.0 |
April | 83381906.38 | 703.27 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.137716E+09 | 992.64 | 31-OCT-15:00 | -8.0 |
November | 95095086.04 | 897.41 | 30-NOV-07:10 | -11.3 |
December | 0.359137E+09 | 2037.07 | 21-DEC-08:02 | -20.0 |
Annual Sum or Average | 0.113790E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.359137E+09 | 2037.07 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12723658.85 | 305.11 | 06-JAN-05:00 | -8.0 |
February | 23516654.98 | 269.03 | 06-FEB-14:10 | -2.8 |
March | 1309888.49 | 95.34 | 19-MAR-14:30 | 0.00 |
April | 3087.32 | 2.05 | 03-APR-11:20 | -1.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 3715278.74 | 164.49 | 31-OCT-14:00 | -7.0 |
November | 1854394.84 | 120.22 | 30-NOV-05:00 | -13.0 |
December | 0.157742E+09 | 713.16 | 22-DEC-05:00 | -21.0 |
Annual Sum or Average | 0.200865E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.157742E+09 | 713.16 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30211092.17 | 332.44 | 05-JAN-18:00 | -18.0 |
February | 60595191.27 | 301.06 | 06-FEB-14:10 | -2.8 |
March | 8550321.44 | 173.49 | 19-MAR-14:20 | 0.00 |
April | 3041474.58 | 104.72 | 03-APR-10:04 | -2.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 14891131.89 | 263.11 | 31-OCT-15:00 | -8.0 |
November | 18376001.09 | 194.62 | 30-NOV-04:50 | -13.2 |
December | 0.185133E+09 | 609.42 | 21-DEC-11:03 | -17.8 |
Annual Sum or Average | 0.320799E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.185133E+09 | 609.42 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 785958.30 | 472.32 | 05-JAN-09:03 | -17.0 |
February | 2370254.73 | 358.43 | 05-FEB-16:00 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 1430066.71 | 243.65 | 31-OCT-14:00 | -7.0 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 29059550.74 | 2379.10 | 21-DEC-09:30 | -20.0 |
Annual Sum or Average | 33645830.48 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 29059550.74 | 2379.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443140E+09 | 2672.71 | 05-JAN-09:01 | -17.0 |
February | 0.557999E+09 | 2665.42 | 05-FEB-16:01 | -6.2 |
March | 0.424554E+09 | 2667.78 | 19-MAR-08:61 | -13.0 |
April | 0.340109E+09 | 2621.60 | 03-APR-08:61 | -4.8 |
May | 23755789.99 | 1574.32 | 02-MAY-08:62 | 3.35 |
June | 871609.32 | 736.92 | 09-JUN-08:04 | 14.77 |
July | 952742.13 | 770.59 | 15-JUL-08:03 | 26.50 |
August | 1013785.77 | 888.93 | 30-AUG-08:03 | 19.50 |
September | 9273446.87 | 1742.63 | 22-SEP-08:62 | 2.57 |
October | 0.296164E+09 | 2674.28 | 31-OCT-15:01 | -8.0 |
November | 0.385711E+09 | 2653.41 | 29-NOV-09:01 | -9.0 |
December | 0.850191E+09 | 2694.30 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.333373E+10 | |||
Minimum of Months | 871609.32 | 736.92 | -20.2 | |
Maximum of Months | 0.850191E+09 | 2694.30 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791317E+09 | 2667.18 | 05-JAN-09:01 | -17.0 |
February | 0.812254E+09 | 2656.89 | 05-FEB-16:01 | -6.2 |
March | 0.527167E+09 | 2657.71 | 19-MAR-08:61 | -13.0 |
April | 0.372626E+09 | 2612.27 | 03-APR-08:61 | -4.8 |
May | 26945849.02 | 1700.19 | 02-MAY-08:62 | 3.35 |
June | 1063297.04 | 1387.86 | 10-JUN-08:53 | 17.20 |
July | 1179652.43 | 1247.76 | 08-JUL-21:53 | 20.00 |
August | 1749632.94 | 1489.30 | 02-AUG-08:53 | 20.00 |
September | 12452737.54 | 1907.91 | 22-SEP-08:62 | 2.57 |
October | 0.350617E+09 | 2664.65 | 31-OCT-15:01 | -8.0 |
November | 0.615874E+09 | 2646.13 | 29-NOV-09:01 | -9.0 |
December | 0.122431E+10 | 2702.04 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.473756E+10 | |||
Minimum of Months | 1063297.04 | 1247.76 | -20.2 | |
Maximum of Months | 0.122431E+10 | 2702.04 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108663E+09 | 787.00 | 05-JAN-16:01 | -15.2 |
February | 0.124260E+09 | 778.11 | 12-FEB-16:01 | -6.2 |
March | 40975720.98 | 763.13 | 04-MAR-16:01 | -9.0 |
April | 16598005.26 | 750.15 | 02-APR-15:01 | -4.0 |
May | 449890.25 | 438.58 | 10-MAY-08:53 | 20.00 |
June | 42377.64 | 202.25 | 17-JUN-18:06 | 24.72 |
July | 39578.13 | 280.48 | 13-JUL-08:54 | 23.00 |
August | 150063.35 | 258.02 | 17-AUG-08:54 | 18.00 |
September | 340660.72 | 415.40 | 27-SEP-08:53 | 20.00 |
October | 28942992.64 | 780.33 | 31-OCT-15:01 | -8.0 |
November | 65601987.24 | 777.34 | 29-NOV-16:01 | -9.3 |
December | 0.193216E+09 | 792.47 | 21-DEC-16:01 | -17.8 |
Annual Sum or Average | 0.579279E+09 | |||
Minimum of Months | 39578.13 | 202.25 | -17.8 | |
Maximum of Months | 0.193216E+09 | 792.47 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474474E+09 | 2602.91 | 05-JAN-09:01 | -17.0 |
February | 0.595708E+09 | 2598.12 | 05-FEB-16:01 | -6.2 |
March | 0.420192E+09 | 2599.56 | 19-MAR-08:61 | -13.0 |
April | 0.329413E+09 | 2558.74 | 03-APR-08:61 | -4.8 |
May | 23079624.85 | 1030.42 | 02-MAY-18:03 | 6.83 |
June | 155309.78 | 672.62 | 17-JUN-08:04 | 17.28 |
July | 203094.05 | 635.55 | 28-JUL-18:04 | 18.00 |
August | 250361.14 | 827.04 | 15-AUG-08:04 | 14.17 |
September | 7636933.50 | 1232.32 | 22-SEP-18:03 | 14.22 |
October | 0.296934E+09 | 2605.01 | 31-OCT-15:01 | -8.0 |
November | 0.416965E+09 | 2587.55 | 29-NOV-09:01 | -9.0 |
December | 0.868649E+09 | 2632.74 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.343366E+10 | |||
Minimum of Months | 155309.78 | 635.55 | -20.2 | |
Maximum of Months | 0.868649E+09 | 2632.74 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824398E+09 | 2608.41 | 05-JAN-16:01 | -15.2 |
February | 0.839983E+09 | 2589.50 | 05-FEB-16:01 | -6.2 |
March | 0.509634E+09 | 2589.50 | 19-MAR-08:61 | -13.0 |
April | 0.366932E+09 | 2549.13 | 03-APR-08:61 | -4.8 |
May | 25959249.34 | 1447.39 | 09-MAY-20:33 | 13.67 |
June | 305539.97 | 766.26 | 14-JUN-06:54 | 28.30 |
July | 262856.05 | 602.84 | 28-JUL-08:54 | 18.00 |
August | 285345.38 | 731.27 | 15-AUG-08:04 | 14.17 |
September | 10420634.70 | 1316.58 | 22-SEP-15:03 | 16.18 |
October | 0.356241E+09 | 2595.10 | 31-OCT-15:01 | -8.0 |
November | 0.661628E+09 | 2587.76 | 29-NOV-16:01 | -9.3 |
December | 0.123378E+10 | 2639.70 | 21-DEC-16:01 | -17.8 |
Annual Sum or Average | 0.482983E+10 | |||
Minimum of Months | 262856.05 | 602.84 | -17.8 | |
Maximum of Months | 0.123378E+10 | 2639.70 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26197803.18 | 880.81 | 05-JAN-09:03 | -17.0 |
February | 0.123429E+09 | 1039.65 | 05-FEB-16:00 | -6.0 |
March | 8974170.68 | 212.95 | 21-MAR-08:20 | 0.73 |
April | 9445881.13 | 468.64 | 03-APR-08:03 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 53680461.90 | 994.91 | 31-OCT-14:00 | -7.0 |
November | 31860976.67 | 809.44 | 01-NOV-08:15 | -2.0 |
December | 0.211107E+09 | 1620.11 | 21-DEC-09:03 | -20.0 |
Annual Sum or Average | 0.464696E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.211107E+09 | 1620.11 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.807689E+09 | 3240.25 | 05-JAN-09:01 | -17.0 |
February | 0.906978E+09 | 3227.98 | 05-FEB-16:01 | -6.2 |
March | 0.708416E+09 | 3230.37 | 19-MAR-08:61 | -13.0 |
April | 0.582475E+09 | 3170.34 | 03-APR-08:61 | -4.8 |
May | 61861646.84 | 2550.41 | 02-MAY-08:62 | 3.35 |
June | 893613.86 | 1066.10 | 10-JUN-08:03 | 16.28 |
July | 1022513.52 | 984.47 | 28-JUL-08:03 | 18.00 |
August | 955135.43 | 886.69 | 02-AUG-08:03 | 20.00 |
September | 27815950.70 | 2988.06 | 22-SEP-08:62 | 2.57 |
October | 0.523234E+09 | 3238.05 | 31-OCT-15:01 | -8.0 |
November | 0.684712E+09 | 3210.55 | 29-NOV-09:01 | -9.0 |
December | 0.133197E+10 | 3267.75 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.563802E+10 | |||
Minimum of Months | 893613.86 | 886.69 | -20.2 | |
Maximum of Months | 0.133197E+10 | 3267.75 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129727E+10 | 3227.88 | 05-JAN-09:01 | -17.0 |
February | 0.125873E+10 | 3212.47 | 05-FEB-16:01 | -6.2 |
March | 0.856964E+09 | 3212.87 | 19-MAR-08:61 | -13.0 |
April | 0.628903E+09 | 3154.07 | 03-APR-08:61 | -4.8 |
May | 63220001.01 | 2569.68 | 02-MAY-08:62 | 3.35 |
June | 1301243.71 | 1584.12 | 14-JUN-06:53 | 28.30 |
July | 1406691.83 | 1385.90 | 02-JUL-08:53 | 20.00 |
August | 2017822.01 | 1686.29 | 18-AUG-08:13 | 26.33 |
September | 33466798.02 | 2980.08 | 22-SEP-08:62 | 2.57 |
October | 0.633873E+09 | 3220.95 | 31-OCT-15:01 | -8.0 |
November | 0.103474E+10 | 3198.96 | 28-NOV-16:01 | -7.2 |
December | 0.182029E+10 | 3269.82 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.763218E+10 | |||
Minimum of Months | 1301243.71 | 1385.90 | -20.2 | |
Maximum of Months | 0.182029E+10 | 3269.82 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148148E+09 | 1679.58 | 05-JAN-09:01 | -17.0 |
February | 0.251991E+09 | 1682.20 | 05-FEB-16:01 | -6.2 |
March | 0.226485E+09 | 1674.29 | 19-MAR-08:61 | -13.0 |
April | 0.195414E+09 | 1651.23 | 03-APR-08:61 | -4.8 |
May | 15143010.51 | 749.77 | 02-MAY-08:62 | 3.35 |
June | 968929.93 | 788.48 | 12-JUN-08:03 | 26.97 |
July | 794418.60 | 796.54 | 01-JUL-08:03 | 26.00 |
August | 786211.14 | 421.08 | 07-AUG-08:04 | 23.50 |
September | 5095453.81 | 929.67 | 22-SEP-08:62 | 2.57 |
October | 0.163714E+09 | 1688.04 | 31-OCT-15:01 | -8.0 |
November | 0.152521E+09 | 1668.11 | 29-NOV-09:01 | -9.0 |
December | 0.339446E+09 | 1688.97 | 21-DEC-09:02 | -20.0 |
Annual Sum or Average | 0.150051E+10 | |||
Minimum of Months | 786211.14 | 421.08 | -20.0 | |
Maximum of Months | 0.339446E+09 | 1688.97 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293278E+09 | 2741.09 | 05-JAN-09:03 | -17.0 |
February | 0.459109E+09 | 2329.04 | 12-FEB-05:40 | -19.3 |
March | 99632017.51 | 1487.09 | 05-MAR-06:00 | -12.0 |
April | 46719883.77 | 1120.81 | 03-APR-06:10 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.178605E+09 | 1726.77 | 31-OCT-14:00 | -7.0 |
November | 0.187287E+09 | 2129.07 | 30-NOV-07:10 | -11.3 |
December | 0.108753E+10 | 4098.05 | 21-DEC-08:02 | -20.0 |
Annual Sum or Average | 0.235216E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.108753E+10 | 4098.05 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123165E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.107672E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.112464E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.101369E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.950429E+09 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.864829E+09 | 1573.46 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.909252E+09 | 1573.46 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.100761E+10 | 1573.46 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.104330E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.119115E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.117841E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.124422E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.128359E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.864829E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.124422E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105727E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.950941E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104886E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100301E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102811E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.990439E+10 | 10645.38 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102012E+11 | 10645.38 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103614E+11 | 10645.38 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100616E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105306E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.102396E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105629E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122744E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.950941E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.105727E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257341E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226827E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243622E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226895E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.224769E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.211220E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.219541E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230568E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230655E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.249841E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246088E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256420E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.282379E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.211220E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257341E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257341E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226827E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243622E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.226895E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.224769E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.211220E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.219541E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230568E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230655E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.249841E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.246088E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256420E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.282379E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.211220E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257341E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147229E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140600E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118254E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103326E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 862495.19 | 57548466.75 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11920718.27 | 19720633.40 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12638339.64 | 17322247.38 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10028545.26 | 21259544.04 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4907212.72 | 35722265.81 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98726.19 | 0.104770E+09 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127844E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161617E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40456037.28 | 0.105521E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17322247.38 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12638339.64 | 0.161617E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59350197.63 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56133986.47 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807.90 | 47960026.33 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42830218.43 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368324.14 | 25523144.18 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4625817.98 | 9042159.71 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4910159.13 | 8106978.68 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3953812.88 | 9615028.50 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1963343.61 | 15372694.28 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47153.99 | 42950247.30 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51698442.51 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64548502.35 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15869419.62 | 0.433132E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8106978.68 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4910159.13 | 64548502.35 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131432E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125045E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21337.87 | 0.106290E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.11 | 95220498.30 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1076276.50 | 57314052.84 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10904063.71 | 21102014.71 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11437492.53 | 19015750.97 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9428367.56 | 22420981.92 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4917729.49 | 35050598.07 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 183170.57 | 96182546.69 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 0.114632E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.16 | 0.145112E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37975235.12 | 0.968818E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19015750.97 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11437492.53 | 0.145112E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75129067.99 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71699478.21 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12407.06 | 60647461.58 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 605.96 | 54185647.13 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 638376.04 | 32248765.38 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6343570.88 | 11909378.83 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6631577.62 | 10757109.62 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5488729.15 | 12624461.10 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2876053.45 | 19688450.82 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 107216.72 | 54625651.48 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65372530.97 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2492.46 | 83176291.68 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22101029.34 | 0.552064E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10757109.62 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6631577.62 | 83176291.68 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195019E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185681E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 15137.37 | 0.158922E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143090E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1073794.13 | 82817412.03 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 15493223.02 | 27091313.40 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 16515843.18 | 24039544.86 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 13457070.94 | 28697499.88 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 7048667.73 | 47631384.87 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 290662.15 | 0.139868E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 584.33 | 0.169588E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214780E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 53894982.86 | 0.141723E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24039544.86 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16515843.18 | 0.214780E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.123165E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343632E+09 |
February | 0.236489E+11 | 0.107672E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325353E+09 |
March | 0.262800E+11 | 0.112464E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276156E+09 |
April | 0.253579E+11 | 0.101369E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244593E+09 |
May | 0.262123E+11 | 0.950429E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1642844.43 | 0.145479E+09 |
June | 0.254132E+11 | 0.864829E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26152947.97 | 50780570.98 |
July | 0.261570E+11 | 0.909252E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27833610.81 | 45541327.45 |
August | 0.262677E+11 | 0.100761E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22013354.64 | 54214517.78 |
September | 0.253456E+11 | 0.104330E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10814819.70 | 87502953.23 |
October | 0.261693E+11 | 0.119115E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219205.72 | 0.245830E+09 |
November | 0.253025E+11 | 0.117841E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298840E+09 |
December | 0.261570E+11 | 0.124422E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373701E+09 |
Annual Sum or Average | 0.308468E+12 | 0.128359E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88676783.27 | 0.249162E+10 |
Minimum of Months | 0.236489E+11 | 0.864829E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45541327.45 |
Maximum of Months | 0.262800E+11 | 0.124422E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27833610.81 | 0.373701E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.105727E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996967E+09 |
February | 0.702046E+11 | 0.950941E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942467E+09 |
March | 0.780153E+11 | 0.104886E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805580E+09 |
April | 0.752779E+11 | 0.100301E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720432E+09 |
May | 0.778146E+11 | 0.102811E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5256082.44 | 0.427812E+09 |
June | 0.754422E+11 | 0.990439E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75042682.71 | 0.148372E+09 |
July | 0.776503E+11 | 0.102012E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79513635.65 | 0.133217E+09 |
August | 0.779788E+11 | 0.103614E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63278581.49 | 0.157987E+09 |
September | 0.752414E+11 | 0.100616E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31121633.03 | 0.254199E+09 |
October | 0.776868E+11 | 0.105306E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 625956.38 | 0.717629E+09 |
November | 0.751137E+11 | 0.102396E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868449E+09 |
December | 0.776503E+11 | 0.105629E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108520E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122744E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254839E+09 | 0.725831E+10 |
Minimum of Months | 0.702046E+11 | 0.950941E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133217E+09 |
Maximum of Months | 0.780153E+11 | 0.105727E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79513635.65 | 0.108520E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83035026.18 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79202712.97 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24570.03 | 66021585.22 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58675056.92 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 816819.02 | 31954795.75 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9289503.63 | 8321099.40 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9955943.90 | 6832821.10 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8122138.56 | 8641222.57 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4277886.13 | 16667382.62 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 146234.18 | 57465004.80 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71522057.96 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91527775.34 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32633095.45 | 0.579867E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6832821.10 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9955943.90 | 91527775.34 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81403892.75 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77916636.72 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4513.90 | 65835333.92 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58788683.59 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 747502.93 | 33410402.51 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8847382.43 | 10093591.27 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9513140.94 | 8836710.22 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7751670.08 | 10596534.57 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4031933.60 | 18529647.80 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133523.59 | 57530796.41 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70349768.53 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90191575.25 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31029667.47 | 0.583484E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8836710.22 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9513140.94 | 90191575.25 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28427739.45 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25761206.94 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22249406.48 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20598842.55 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16107.18 | 13914553.81 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1013896.84 | 5762548.31 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1053155.65 | 5374992.43 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 789510.91 | 6145390.26 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 302839.07 | 8848713.20 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.75 | 20898135.73 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24658946.85 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29253392.81 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3175631.39 | 0.211894E+09 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5374992.43 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1053155.65 | 29253392.81 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22772023.94 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21790218.19 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.45 | 18328523.95 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16430044.80 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220036.19 | 9101572.82 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2493945.62 | 2632498.20 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2674764.68 | 2275932.82 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2193374.51 | 2734193.15 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158487.95 | 4900173.65 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46437.90 | 15935611.15 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 791.13 | 19644081.13 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.72 | 25280062.01 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8794765.15 | 0.161825E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2275932.82 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2674764.68 | 25280062.01 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83181778.43 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79375220.51 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24581.12 | 66321095.00 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59005796.87 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 811149.47 | 32163080.83 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9279814.92 | 8379918.01 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9934209.95 | 6871763.27 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8119717.64 | 8715857.44 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4276211.83 | 16755311.66 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 147480.47 | 57599942.22 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71571949.42 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91603018.02 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32593165.40 | 0.581545E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6871763.27 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9934209.95 | 91603018.02 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81255652.89 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78009714.58 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4861.14 | 65950802.49 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59016426.68 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734404.45 | 33408470.08 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8804868.39 | 10808192.46 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9452438.57 | 9366843.64 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7695290.13 | 11172199.15 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3999020.13 | 18549736.98 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 132029.48 | 57519592.64 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70161678.04 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3660.64 | 90022216.14 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30826572.93 | 0.585242E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9366843.64 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9452438.57 | 90022216.14 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100990E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96438956.91 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2091.53 | 81934268.29 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.93 | 72331185.92 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836507.57 | 42988225.47 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8243960.90 | 16139776.22 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8614735.00 | 14674597.57 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6959518.46 | 17349878.38 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3499184.22 | 27225712.26 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92679.27 | 74271831.35 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87718668.64 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.90 | 0.110943E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28250361.79 | 0.743005E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14674597.57 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8614735.00 | 0.110943E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82945544.35 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79187747.97 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23235.06 | 66013227.81 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58658673.07 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 794050.94 | 32082538.62 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9185780.65 | 8418044.40 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9846910.97 | 6925336.32 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8020132.08 | 8738643.17 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4214729.76 | 16749411.73 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 140879.93 | 57494272.45 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71495977.66 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91409640.09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32225719.40 | 0.580119E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6925336.32 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9846910.97 | 91409640.09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81179960.96 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77849207.54 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4056.03 | 65864730.96 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58853840.70 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 726709.63 | 33702686.38 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8759404.96 | 10190886.65 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9423345.35 | 8895263.77 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7665951.09 | 10679256.05 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3986782.05 | 18599870.02 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 130500.93 | 57556777.75 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70242440.98 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90063969.00 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30696750.03 | 0.583679E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8895263.77 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9423345.35 | 90063969.00 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42993195.60 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40961835.38 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11759.06 | 34097040.04 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30281144.61 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 405282.63 | 16459146.26 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4707015.88 | 4301181.69 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5038643.16 | 3541441.76 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4106303.81 | 4475402.70 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2152220.78 | 8617475.07 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68039.91 | 29637947.96 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37052985.00 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47556653.45 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16489265.22 | 0.299975E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3541441.76 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5038643.16 | 47556653.45 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257341E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225623E+09 |
February | 0.415303E+11 | 0.226827E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214722E+09 |
March | 0.461508E+11 | 0.243622E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 737.91 | 0.185495E+09 |
April | 0.445315E+11 | 0.226895E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167643E+09 |
May | 0.460320E+11 | 0.224769E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 887792.64 | 99440431.76 |
June | 0.446286E+11 | 0.211220E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15923579.92 | 34261931.14 |
July | 0.459349E+11 | 0.219541E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16942936.86 | 30735419.92 |
August | 0.461292E+11 | 0.230568E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13622310.79 | 36391514.66 |
September | 0.445099E+11 | 0.230655E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6735107.32 | 58083224.92 |
October | 0.459565E+11 | 0.249841E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159666.37 | 0.163945E+09 |
November | 0.444343E+11 | 0.246088E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197130E+09 |
December | 0.459349E+11 | 0.256420E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247177E+09 |
Annual Sum or Average | 0.541708E+12 | 0.282379E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 54272131.80 | 0.166065E+10 |
Minimum of Months | 0.415303E+11 | 0.211220E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30735419.92 |
Maximum of Months | 0.461508E+11 | 0.257341E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16942936.86 | 0.247177E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257341E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227090E+09 |
February | 0.415303E+11 | 0.226827E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216098E+09 |
March | 0.461508E+11 | 0.243622E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 | 0.186619E+09 |
April | 0.445315E+11 | 0.226895E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168547E+09 |
May | 0.460320E+11 | 0.224769E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 885073.82 | 99620263.44 |
June | 0.446286E+11 | 0.211220E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15921549.53 | 34266371.71 |
July | 0.459349E+11 | 0.219541E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16939486.14 | 30738381.15 |
August | 0.461292E+11 | 0.230568E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13616103.95 | 36397682.36 |
September | 0.445099E+11 | 0.230655E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6711296.64 | 58152434.88 |
October | 0.459565E+11 | 0.249841E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148349.14 | 0.164719E+09 |
November | 0.444343E+11 | 0.246088E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198290E+09 |
December | 0.459349E+11 | 0.256420E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248981E+09 |
Annual Sum or Average | 0.541708E+12 | 0.282379E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 54221990.08 | 0.166952E+10 |
Minimum of Months | 0.415303E+11 | 0.211220E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30738381.15 |
Maximum of Months | 0.461508E+11 | 0.257341E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16939486.14 | 0.248981E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203278E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193338E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166748E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150360E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 796086.20 | 88780049.41 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 14280360.57 | 30629088.30 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 15191090.92 | 27476745.26 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12209417.62 | 32537547.48 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6018310.85 | 51897043.08 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 117276.03 | 0.147339E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177366E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223424E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 48612542.19 | 0.149317E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27476745.26 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 15191090.92 | 0.223424E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177811E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170344E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 0.144676E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128324E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054458.18 | 75929746.39 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14072679.62 | 28018891.09 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14946928.94 | 25126888.95 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12030307.04 | 29638418.89 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5999491.14 | 46120383.66 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122321.90 | 0.129062E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154618E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196593E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48226251.99 | 0.130626E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25126888.95 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14946928.94 | 0.196593E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 109.83 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 114.69 | 12-FEB-05:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 100.14 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 77.85 | 17-APR-03:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 17-MAY-13:00 | 57.28 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 26-JUN-15:00 | 39.19 | 09-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 16-JUL-13:00 | 33.07 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 16-AUG-16:00 | 30.09 | 12-AUG-23:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 09-SEP-13:00 | 59.69 | 22-SEP-05:50 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 11-OCT-14:00 | 83.55 | 30-OCT-06:30 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 98.04 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 124.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 124.08 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 42.94 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 45.42 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 14-MAR-13:00 | 39.51 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31.01 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 17-MAY-13:00 | 24.07 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 26-JUN-15:00 | 17.14 | 09-JUN-04:07 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 | 16-JUL-13:00 | 14.61 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 16-AUG-16:00 | 12.64 | 12-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 10-SEP-13:00 | 25.31 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 11-OCT-14:00 | 33.44 | 30-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.44 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 47.90 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 47.90 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 100.19 | 05-JAN-19:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 104.61 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 14-MAR-13:00 | 91.36 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 19-APR-13:00 | 71.01 | 17-APR-03:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | 17-MAY-13:00 | 53.91 | 03-MAY-02:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 26-JUN-15:00 | 39.90 | 09-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 16-JUL-13:00 | 34.41 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 | 16-AUG-16:00 | 29.88 | 12-AUG-23:40 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 09-SEP-13:00 | 58.57 | 22-SEP-05:50 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 11-OCT-14:00 | 76.28 | 30-OCT-06:30 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 06-NOV-13:00 | 89.61 | 29-NOV-21:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 01-DEC-14:00 | 113.19 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.88 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 113.19 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 57.80 | 05-JAN-19:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 60.36 | 12-FEB-05:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 14-MAR-13:00 | 52.71 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 19-APR-13:00 | 40.97 | 17-APR-03:00 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | 17-MAY-13:00 | 30.75 | 03-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 26-JUN-15:00 | 22.72 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 16-JUL-13:00 | 19.58 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 16-AUG-16:00 | 16.97 | 12-AUG-23:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 09-SEP-13:00 | 33.20 | 22-SEP-05:20 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 11-OCT-14:00 | 43.97 | 30-OCT-06:40 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 51.60 | 29-NOV-21:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 01-DEC-14:00 | 65.31 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 65.31 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 147.05 | 05-JAN-19:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 152.26 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 4.54 | 14-MAR-13:00 | 134.94 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 106.98 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 15.86 | 17-MAY-13:00 | 76.80 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 45.72 | 26-JUN-15:20 | 53.56 | 09-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 40.30 | 16-JUL-13:00 | 45.49 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 40.31 | 16-AUG-16:00 | 40.81 | 12-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 28.72 | 10-SEP-13:00 | 84.15 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 13.55 | 11-OCT-14:00 | 114.13 | 30-OCT-07:20 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.26 | 07-NOV-14:00 | 132.29 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 161.14 | 23-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.81 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 45.72 | 161.14 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 242.77 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 254.40 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 221.41 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 177.66 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 17-MAY-13:00 | 138.68 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.10 | 26-JUN-15:00 | 98.15 | 09-JUN-04:10 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 16-JUL-13:00 | 81.34 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 16-AUG-16:00 | 72.39 | 12-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 10-SEP-13:00 | 144.27 | 22-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 11-OCT-14:00 | 190.58 | 30-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 220.19 | 29-NOV-21:10 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 274.31 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.39 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 78.10 | 274.31 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 712.17 | 05-JAN-19:10 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 753.93 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 659.15 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 525.00 | 17-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 17-MAY-13:00 | 407.52 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.12 | 26-JUN-15:00 | 280.45 | 09-JUN-04:07 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.79 | 16-JUL-13:00 | 239.06 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.66 | 16-AUG-16:00 | 206.87 | 12-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.95 | 10-SEP-13:00 | 426.69 | 22-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 | 11-OCT-14:00 | 564.01 | 30-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 656.13 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 803.12 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.87 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 223.12 | 803.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.39 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.81 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 13-MAR-16:00 | 58.37 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.42 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 31-MAY-15:10 | 33.47 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 26-JUN-15:10 | 21.56 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 16-JUL-15:10 | 17.80 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 16-AUG-16:00 | 14.85 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 10-SEP-16:00 | 34.87 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 11-OCT-15:10 | 48.73 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.14 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72.27 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 72.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.38 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.80 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 13-MAR-15:07 | 58.36 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.42 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 31-MAY-15:10 | 33.47 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 26-JUN-15:10 | 21.56 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 16-JUL-15:10 | 17.80 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 16-AUG-16:00 | 16.19 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 10-SEP-16:00 | 34.87 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 11-OCT-15:09 | 48.72 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.14 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72.27 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 72.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18.64 | 14-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 19.36 | 12-FEB-05:00 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 16.59 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 12.91 | 11-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 17-MAY-13:00 | 10.79 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 26-JUN-15:00 | 8.29 | 09-JUN-04:30 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 16-JUL-13:00 | 7.24 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 16-AUG-16:00 | 6.41 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 10-SEP-13:00 | 11.63 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 11-OCT-14:00 | 14.56 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 16.94 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 18.98 | 21-DEC-17:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 19.36 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 17.69 | 05-JAN-19:06 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 18.65 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 14-MAR-13:00 | 16.29 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 12.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 31-MAY-15:09 | 9.34 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 26-JUN-15:10 | 6.02 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 16-JUL-15:10 | 4.97 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 | 16-AUG-16:00 | 4.14 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 10-SEP-16:00 | 9.73 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 11-OCT-15:10 | 13.60 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 07-NOV-14:00 | 15.95 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 01-DEC-14:00 | 20.17 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 20.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.39 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.81 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 13-MAR-15:16 | 58.37 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.42 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 31-MAY-15:09 | 33.47 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 26-JUN-15:10 | 21.56 | 09-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 16-JUL-15:10 | 17.80 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 16-AUG-16:00 | 15.83 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 10-SEP-16:00 | 34.87 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 11-OCT-15:07 | 48.73 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.14 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72.27 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 72.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.38 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.80 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 13-MAR-15:09 | 58.36 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.42 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 31-MAY-15:10 | 33.47 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 26-JUN-15:10 | 21.56 | 09-JUN-04:30 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 16-JUL-15:10 | 17.80 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 16-AUG-16:00 | 15.94 | 12-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 10-SEP-16:00 | 34.87 | 22-SEP-05:50 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 11-OCT-15:09 | 48.72 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.14 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 01-DEC-14:00 | 72.27 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 72.27 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 77.16 | 05-JAN-19:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 80.57 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 14-MAR-13:00 | 70.37 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 19-APR-13:00 | 54.72 | 17-APR-03:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 17-MAY-13:00 | 40.86 | 03-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 26-JUN-15:00 | 30.71 | 09-JUN-04:03 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 16-JUL-13:00 | 26.22 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 16-AUG-16:00 | 22.90 | 12-AUG-23:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 10-SEP-13:00 | 45.12 | 22-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 11-OCT-14:00 | 58.72 | 30-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 68.89 | 29-NOV-21:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 01-DEC-14:00 | 87.17 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.90 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 87.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.49 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.92 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 13-MAR-16:00 | 58.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.52 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 31-MAY-15:10 | 33.57 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 | 26-JUN-15:10 | 21.65 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 | 16-JUL-15:10 | 17.89 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 16-AUG-16:00 | 14.94 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 10-SEP-16:00 | 34.97 | 22-SEP-05:10 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 11-OCT-15:10 | 48.83 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.25 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72.38 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 | 72.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 63.49 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 66.92 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 13-MAR-15:07 | 58.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45.52 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 31-MAY-15:10 | 33.57 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 26-JUN-15:10 | 21.65 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 | 16-JUL-15:10 | 17.89 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 16-AUG-16:00 | 16.76 | 12-AUG-20:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 10-SEP-16:00 | 34.97 | 22-SEP-05:10 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 11-OCT-15:07 | 48.83 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 57.24 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72.38 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 72.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 32.49 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 34.24 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 13-MAR-16:00 | 29.92 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23.29 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 31-MAY-15:07 | 17.18 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26-JUN-15:10 | 11.08 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | 16-JUL-15:10 | 9.15 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 16-AUG-16:00 | 7.64 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 10-SEP-16:00 | 17.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 11-OCT-15:10 | 24.98 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 29.29 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 37.03 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 37.03 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 165.58 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 173.47 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 14-MAR-13:00 | 153.97 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 122.12 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 17-MAY-13:00 | 92.61 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 26-JUN-15:00 | 63.30 | 09-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 16-JUL-13:00 | 54.01 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 16-AUG-16:00 | 46.78 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 | 10-SEP-13:00 | 96.15 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 11-OCT-14:00 | 130.25 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 150.92 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 186.17 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 186.17 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 166.27 | 05-JAN-19:09 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 174.42 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 14-MAR-13:00 | 153.97 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 122.12 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 17-MAY-13:00 | 92.61 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 26-JUN-15:00 | 63.30 | 09-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 16-JUL-13:00 | 54.01 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 16-AUG-16:00 | 46.78 | 12-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 | 10-SEP-13:00 | 96.15 | 22-SEP-05:10 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 11-OCT-14:00 | 130.25 | 30-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 150.92 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 187.15 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 187.15 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 150.12 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 156.50 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 137.81 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 109.31 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 14.73 | 17-MAY-13:00 | 79.67 | 03-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 44.57 | 26-JUN-15:00 | 56.67 | 09-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 38.05 | 16-JUL-13:00 | 48.35 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 37.86 | 16-AUG-16:00 | 41.88 | 12-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 25.64 | 10-SEP-13:00 | 86.07 | 22-SEP-05:07 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 8.74 | 11-OCT-14:00 | 116.61 | 30-OCT-07:07 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 135.08 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 165.15 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 44.57 | 165.15 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 136.76 | 05-JAN-19:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 142.80 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 14-MAR-13:00 | 124.74 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 97.03 | 17-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 17-MAY-13:00 | 71.47 | 03-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 26-JUN-15:00 | 52.55 | 09-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 16-JUL-13:00 | 44.60 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 16-AUG-16:00 | 39.57 | 12-AUG-23:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 10-SEP-13:00 | 75.66 | 22-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 11-OCT-14:00 | 104.11 | 30-OCT-06:50 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 122.12 | 29-NOV-21:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 154.48 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 154.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12231.56 | 27-JAN-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10940.85 | 18-FEB-12:20 | 3833.96 | 2575.37 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10375.12 | 12-MAR-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10165.84 | 21-APR-10:33 | 7667.93 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10343.60 | 31-MAY-18:10 | 62621.41 | 57687.79 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11377.99 | 26-JUN-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11549.60 | 23-JUL-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15379.67 | 18-AUG-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18436.00 | 21-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18570.26 | 20-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18244.71 | 17-NOV-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17259.95 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10165.84 | 3833.96 | 2575.37 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18570.26 | 62621.41 | 57687.79 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4878.19 | 20-JAN-13:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 |
February | 4862.09 | 18-FEB-13:20 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
March | 4579.47 | 14-MAR-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
April | 3221.33 | 07-APR-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
May | 2335.46 | 05-MAY-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 |
June | 2924.98 | 26-JUN-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 0.00 |
July | 3196.34 | 23-JUL-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
August | 3937.07 | 26-AUG-12:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 | 0.00 |
September | 4806.22 | 28-SEP-12:50 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 0.00 |
October | 4835.39 | 10-OCT-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
November | 4917.22 | 07-NOV-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 |
December | 4636.24 | 17-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2335.46 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4917.22 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 14.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1507.70 | 20-JAN-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
February | 1414.52 | 27-FEB-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 |
March | 1780.72 | 15-MAR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
April | 1555.79 | 07-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 |
May | 1722.80 | 31-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
June | 2164.57 | 26-JUN-20:50 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
July | 2072.36 | 17-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.00 |
August | 2171.27 | 16-AUG-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
September | 2044.01 | 12-SEP-20:04 | 6019.20 | 2636.71 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 1859.80 | 11-OCT-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 |
November | 1622.45 | 07-NOV-21:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 |
December | 1361.83 | 04-DEC-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1361.83 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2171.27 | 6019.20 | 2636.71 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 21.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 882.72 | 20-JAN-14:00 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
February | 874.94 | 18-FEB-13:50 | 95.47 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
March | 943.19 | 15-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 |
April | 898.75 | 21-APR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
May | 1052.02 | 17-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 |
June | 1817.05 | 26-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
July | 1846.05 | 17-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 0.00 |
August | 1700.23 | 16-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 | 0.00 |
September | 1577.81 | 11-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
October | 993.99 | 11-OCT-13:00 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 0.00 |
November | 925.17 | 07-NOV-12:00 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
December | 843.84 | 03-DEC-13:00 | 95.47 | 228.06 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 843.84 | 63.65 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1846.05 | 254.59 | 684.18 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 20.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 481.62 | 20-JAN-14:00 | 48.96 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
February | 479.28 | 18-FEB-13:50 | 73.44 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
March | 504.95 | 15-MAR-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
April | 480.41 | 21-APR-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 |
May | 531.10 | 18-MAY-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
June | 830.25 | 26-JUN-19:10 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 0.00 |
July | 823.63 | 17-JUL-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
August | 737.71 | 16-AUG-20:10 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 0.00 |
September | 632.24 | 12-SEP-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
October | 540.00 | 11-OCT-13:05 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
November | 503.38 | 07-NOV-14:00 | 48.96 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 456.50 | 03-DEC-13:00 | 73.44 | 50.87 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 456.50 | 48.96 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 830.25 | 195.84 | 152.61 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 11.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37699.63 | 20-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 |
February | 37735.05 | 27-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 63.23 |
March | 38292.78 | 14-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 |
April | 38340.42 | 20-APR-20:00 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 |
May | 38652.73 | 16-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 |
June | 39226.26 | 26-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 25.31 | 0.00 |
July | 39213.42 | 17-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 17.65 | 0.00 |
August | 39158.38 | 16-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 |
September | 38846.51 | 08-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
October | 38238.51 | 11-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 |
November | 37909.26 | 09-NOV-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.52 |
December | 37515.45 | 04-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37515.45 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39226.26 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 25.31 | 63.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17403.08 | 20-JAN-13:00 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
February | 17855.52 | 18-FEB-13:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 |
March | 16451.52 | 11-MAR-13:00 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
April | 12131.59 | 07-APR-12:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
May | 9997.91 | 10-MAY-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 |
June | 11674.56 | 26-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 | 0.00 |
July | 11727.39 | 17-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
August | 13662.13 | 26-AUG-12:40 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 0.00 |
September | 15999.24 | 28-SEP-12:50 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 0.00 |
October | 16482.08 | 08-OCT-12:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
November | 17800.76 | 05-NOV-12:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.59 |
December | 17155.57 | 17-DEC-12:50 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9997.91 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17855.52 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 37.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35980.42 | 20-JAN-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.39 |
February | 34282.22 | 17-FEB-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.84 |
March | 38256.49 | 15-MAR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.35 |
April | 35143.87 | 07-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.96 |
May | 37440.17 | 17-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.26 |
June | 42812.80 | 26-JUN-20:10 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 118.97 | 0.00 |
July | 42710.18 | 17-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 0.00 |
August | 43264.55 | 16-AUG-20:10 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 | 0.00 |
September | 42030.33 | 12-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
October | 39404.65 | 11-OCT-20:10 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.27 |
November | 36749.37 | 07-NOV-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.52 |
December | 33770.13 | 04-DEC-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33770.13 | 40553.76 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43264.55 | 45622.98 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 118.97 | 273.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4051.46 | 23-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
February | 4006.51 | 26-FEB-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
March | 4309.42 | 13-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
April | 4195.71 | 07-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
May | 4313.94 | 10-MAY-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
June | 4459.62 | 27-JUN-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 |
July | 4463.23 | 01-JUL-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 0.00 |
August | 4463.45 | 17-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
September | 4483.06 | 28-SEP-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
October | 4439.63 | 11-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
November | 4192.14 | 05-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
December | 3944.11 | 02-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3944.11 | 378.00 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4483.06 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 6.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3877.45 | 23-JAN-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
February | 3847.11 | 26-FEB-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
March | 4392.82 | 08-MAR-17:11 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
April | 4476.34 | 08-APR-18:01 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 |
May | 4421.40 | 27-MAY-16:11 | 954.00 | 391.81 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
June | 4607.49 | 27-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
July | 4857.68 | 01-JUL-08:61 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
August | 4545.94 | 18-AUG-08:11 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
September | 4434.98 | 11-SEP-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
October | 4282.76 | 14-OCT-16:11 | 954.00 | 391.81 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
November | 3999.52 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 |
December | 3789.11 | 02-DEC-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3789.11 | 360.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4857.68 | 1170.00 | 1187.26 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 15.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 874.73 | 20-JAN-12:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
February | 836.91 | 18-FEB-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
March | 756.74 | 11-MAR-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
April | 469.01 | 08-APR-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
May | 367.98 | 05-MAY-13:10 | 0.00 | 41.79 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
June | 441.50 | 14-JUN-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 0.00 |
July | 477.92 | 23-JUL-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
August | 608.16 | 31-AUG-12:50 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
September | 779.63 | 28-SEP-13:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
October | 811.84 | 10-OCT-12:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
November | 869.34 | 07-NOV-12:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
December | 787.51 | 17-DEC-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 367.98 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 874.73 | 0.00 | 41.79 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 4.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1006.12 | 21-JAN-09:01 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
February | 1023.17 | 18-FEB-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
March | 1172.57 | 14-MAR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 0.00 |
April | 1151.10 | 27-APR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 1234.88 | 17-MAY-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
June | 1314.20 | 12-JUN-08:61 | 360.00 | 328.43 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
July | 1356.22 | 01-JUL-08:61 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 0.00 |
August | 1259.27 | 01-AUG-21:51 | 1800.00 | 500.12 | 903.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 1259.36 | 10-SEP-08:51 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
October | 1217.53 | 11-OCT-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
November | 1076.93 | 06-NOV-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 994.46 | 02-DEC-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 994.46 | 360.00 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1356.22 | 1800.00 | 500.12 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 3.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3519.24 | 23-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
February | 3496.60 | 18-FEB-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
March | 3747.29 | 13-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
April | 3646.59 | 07-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
May | 3787.92 | 04-MAY-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
June | 3890.03 | 27-JUN-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 |
July | 3999.30 | 01-JUL-08:61 | 540.00 | 664.94 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 0.00 |
August | 3890.83 | 17-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 0.00 |
September | 3894.64 | 28-SEP-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 0.00 |
October | 3853.47 | 11-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 0.00 |
November | 3645.12 | 05-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
December | 3453.50 | 02-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3453.50 | 378.00 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3999.30 | 680.40 | 664.94 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 6.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3320.69 | 20-JAN-09:01 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
February | 3373.92 | 18-FEB-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 |
March | 3614.70 | 14-MAR-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
April | 4120.11 | 19-APR-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 |
May | 4223.18 | 10-MAY-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
June | 4696.79 | 27-JUN-08:32 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
July | 4579.24 | 01-JUL-07:42 | 572.40 | 398.92 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
August | 4235.46 | 02-AUG-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
September | 4344.57 | 07-SEP-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 |
October | 4119.84 | 11-OCT-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
November | 3475.95 | 07-NOV-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
December | 3290.00 | 03-DEC-09:01 | 378.00 | 465.41 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3290.00 | 216.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4696.79 | 680.40 | 522.40 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 18.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1584.45 | 24-JAN-13:20 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
February | 1613.75 | 18-FEB-13:50 | 754.45 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
March | 1700.45 | 15-MAR-12:50 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
April | 1511.96 | 21-APR-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 |
May | 1681.43 | 18-MAY-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
June | 2845.94 | 26-JUN-18:30 | 1760.39 | 1031.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 |
July | 2572.28 | 01-JUL-18:30 | 1508.90 | 902.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
August | 2592.58 | 11-AUG-18:17 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 0.00 |
September | 2344.45 | 12-SEP-18:03 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
October | 1823.40 | 11-OCT-13:05 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
November | 1663.84 | 07-NOV-14:00 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
December | 1489.08 | 17-DEC-13:00 | 754.45 | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1489.08 | 502.97 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2845.94 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 15.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4311.12 | 23-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
February | 4251.32 | 26-FEB-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 |
March | 4587.83 | 13-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
April | 4460.14 | 07-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
May | 4585.56 | 10-MAY-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 0.00 |
June | 4750.09 | 27-JUN-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 |
July | 4749.02 | 01-JUL-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
August | 4749.44 | 17-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
September | 4772.88 | 28-SEP-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 0.00 |
October | 4720.09 | 11-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 0.00 |
November | 4466.30 | 05-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 |
December | 4200.43 | 02-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4200.43 | 378.00 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4772.88 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 6.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4095.62 | 23-JAN-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
February | 4061.21 | 26-FEB-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 |
March | 4767.60 | 08-MAR-17:11 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
April | 4833.25 | 08-APR-18:01 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 |
May | 4754.82 | 27-MAY-16:11 | 954.00 | 391.81 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
June | 4910.08 | 27-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
July | 5100.03 | 01-JUL-08:61 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
August | 4807.99 | 13-AUG-21:51 | 1386.00 | 1009.18 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 |
September | 4638.00 | 11-SEP-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
October | 4667.19 | 08-OCT-18:11 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
November | 4234.47 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 |
December | 4009.97 | 02-DEC-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4009.97 | 360.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5100.03 | 1386.00 | 1187.26 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 16.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2160.70 | 23-JAN-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
February | 2118.06 | 18-FEB-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
March | 2283.46 | 13-MAR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 0.00 |
April | 2195.35 | 07-APR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
May | 2182.83 | 10-MAY-18:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
June | 2303.86 | 12-JUN-08:61 | 360.00 | 328.43 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
July | 2290.70 | 01-JUL-08:61 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
August | 2229.24 | 18-AUG-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
September | 2359.32 | 28-SEP-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 0.00 |
October | 2343.62 | 11-OCT-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
November | 2247.82 | 05-NOV-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
December | 2111.18 | 02-DEC-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2111.18 | 252.00 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2359.32 | 970.20 | 465.04 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 3.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18169.27 | 20-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 |
February | 17975.64 | 27-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 |
March | 20061.03 | 14-MAR-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
April | 20179.53 | 20-APR-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
May | 21376.14 | 31-MAY-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
June | 23264.80 | 26-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 0.00 |
July | 23161.44 | 17-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 | 0.00 |
August | 22923.21 | 16-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 0.00 |
September | 22086.03 | 12-SEP-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
October | 20119.92 | 10-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
November | 19114.06 | 09-NOV-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 |
December | 18204.33 | 04-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17975.64 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23264.80 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 | 79.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19827.11 | 20-JAN-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 |
February | 19636.55 | 27-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 |
March | 21457.61 | 14-MAR-21:05 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 |
April | 21746.57 | 20-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 |
May | 22726.49 | 31-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
June | 24469.22 | 26-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 0.00 |
July | 24361.45 | 17-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 0.00 |
August | 24119.48 | 16-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
September | 23276.99 | 12-SEP-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
October | 21458.36 | 10-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
November | 20609.86 | 09-NOV-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 |
December | 19922.02 | 04-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19636.55 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24469.22 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 79.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27120.11 | 20-JAN-11:40 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
February | 27647.84 | 18-FEB-11:40 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
March | 28780.81 | 15-MAR-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
April | 28473.66 | 20-APR-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 |
May | 29062.89 | 16-MAY-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
June | 30048.22 | 26-JUN-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
July | 30257.73 | 23-JUL-10:40 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 16.64 | 0.00 |
August | 30361.71 | 05-AUG-10:37 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 |
September | 29663.30 | 04-SEP-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 8.33 | 0.00 |
October | 28729.30 | 07-OCT-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
November | 27886.41 | 05-NOV-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 |
December | 26849.15 | 02-DEC-11:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26849.15 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30361.71 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.62 | 26.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4000.95 | 20-JAN-14:00 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
February | 4052.28 | 18-FEB-13:50 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
March | 4523.11 | 15-MAR-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 |
April | 3773.89 | 21-APR-10:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 |
May | 4081.31 | 18-MAY-10:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
June | 6704.69 | 26-JUN-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 0.00 |
July | 6674.74 | 23-JUL-13:00 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 0.00 |
August | 6973.59 | 16-AUG-15:02 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 0.00 |
September | 6524.96 | 09-SEP-12:50 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 0.00 |
October | 4639.12 | 11-OCT-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 0.00 |
November | 4191.28 | 07-NOV-13:40 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
December | 3661.83 | 03-DEC-13:00 | 798.48 | 409.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3661.83 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6973.59 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 28.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.409037E+12 | 270323.25 | 24-JAN-20:30 | 0.426846E+12 | 477748.20 | 05-JAN-19:10 |
February | 0.365300E+12 | 269087.52 | 27-FEB-20:10 | 0.412271E+12 | 415175.54 | 11-FEB-19:10 |
March | 0.404424E+12 | 285935.95 | 13-MAR-19:30 | 0.402254E+12 | 382714.61 | 03-MAR-18:00 |
April | 0.382623E+12 | 280229.90 | 20-APR-20:40 | 0.373091E+12 | 395349.11 | 25-APR-17:40 |
May | 0.428991E+12 | 322874.34 | 31-MAY-18:10 | 0.341015E+12 | 320148.36 | 02-MAY-17:00 |
June | 0.516380E+12 | 406303.07 | 26-JUN-18:19 | 0.235265E+12 | 180246.47 | 09-JUN-05:49 |
July | 0.543369E+12 | 385685.86 | 17-JUL-19:40 | 0.237708E+12 | 171360.70 | 01-JUL-17:00 |
August | 0.532325E+12 | 390556.23 | 16-AUG-19:19 | 0.237702E+12 | 170744.82 | 12-AUG-21:00 |
September | 0.480730E+12 | 368675.97 | 12-SEP-19:10 | 0.266341E+12 | 261092.26 | 22-SEP-20:00 |
October | 0.420676E+12 | 298859.38 | 10-OCT-19:10 | 0.361354E+12 | 363706.39 | 31-OCT-18:10 |
November | 0.398432E+12 | 279908.45 | 07-NOV-20:30 | 0.372706E+12 | 413235.53 | 29-NOV-19:10 |
December | 0.404065E+12 | 270120.91 | 04-DEC-20:40 | 0.494265E+12 | 509588.33 | 21-DEC-19:10 |
Annual Sum or Average | 0.528635E+13 | 0.416082E+13 | ||||
Minimum of Months | 0.365300E+12 | 269087.52 | 0.235265E+12 | 170744.82 | ||
Maximum of Months | 0.543369E+12 | 406303.07 | 0.494265E+12 | 509588.33 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518763E+11 | 0.179030E+11 | 0.146779E+12 | 0.544822E+11 | 0.432269E+11 | 0.669539E+10 | 0.00 | 0.179570E+11 | 0.00 | 0.00 | 0.208990E+11 | 0.455223E+11 | 0.00 |
February | 0.466598E+11 | 0.150734E+11 | 0.132565E+12 | 0.492098E+11 | 0.387356E+11 | 0.546080E+10 | 0.00 | 0.134453E+11 | 0.00 | 0.00 | 0.192314E+11 | 0.415862E+11 | 0.00 |
March | 0.513459E+11 | 0.151400E+11 | 0.146789E+12 | 0.544839E+11 | 0.437352E+11 | 0.647870E+10 | 0.00 | 0.219014E+11 | 0.00 | 0.00 | 0.165935E+11 | 0.442605E+11 | 0.00 |
April | 0.493664E+11 | 0.130827E+11 | 0.142011E+12 | 0.527241E+11 | 0.408328E+11 | 0.645758E+10 | 0.00 | 0.174517E+11 | 0.00 | 0.00 | 0.148477E+11 | 0.422709E+11 | 0.00 |
May | 0.506233E+11 | 0.121573E+11 | 0.146789E+12 | 0.544825E+11 | 0.468043E+11 | 0.968770E+10 | 0.00 | 0.568466E+11 | 0.00 | 0.00 | 0.637269E+10 | 0.415109E+11 | 0.00 |
June | 0.487436E+11 | 0.110454E+11 | 0.142058E+12 | 0.527256E+11 | 0.541019E+11 | 0.985227E+10 | 0.00 | 0.146152E+12 | 0.00 | 0.00 | 0.983565E+10 | 0.382464E+11 | 0.00 |
July | 0.504345E+11 | 0.117378E+11 | 0.146742E+12 | 0.544805E+11 | 0.557364E+11 | 0.102663E+11 | 0.00 | 0.160317E+12 | 0.00 | 0.00 | 0.104154E+11 | 0.395130E+11 | 0.00 |
August | 0.508480E+11 | 0.129163E+11 | 0.146800E+12 | 0.544836E+11 | 0.564026E+11 | 0.102528E+11 | 0.00 | 0.148159E+12 | 0.00 | 0.00 | 0.898495E+10 | 0.397363E+11 | 0.00 |
September | 0.495142E+11 | 0.139682E+11 | 0.142022E+12 | 0.527243E+11 | 0.534694E+11 | 0.970063E+10 | 0.00 | 0.109115E+12 | 0.00 | 0.00 | 0.715600E+10 | 0.394614E+11 | 0.00 |
October | 0.516342E+11 | 0.160521E+11 | 0.146768E+12 | 0.544821E+11 | 0.476673E+11 | 0.758807E+10 | 0.00 | 0.341778E+11 | 0.00 | 0.00 | 0.147615E+11 | 0.438431E+11 | 0.00 |
November | 0.501349E+11 | 0.169176E+11 | 0.142074E+12 | 0.527252E+11 | 0.438045E+11 | 0.665275E+10 | 0.00 | 0.200118E+11 | 0.00 | 0.00 | 0.190132E+11 | 0.435230E+11 | 0.00 |
December | 0.518708E+11 | 0.182892E+11 | 0.146742E+12 | 0.544814E+11 | 0.431318E+11 | 0.543198E+10 | 0.00 | 0.129219E+11 | 0.00 | 0.00 | 0.206145E+11 | 0.468992E+11 | 0.00 |
Annual Sum or Average | 0.603052E+12 | 0.174283E+12 | 0.172814E+13 | 0.641485E+12 | 0.567649E+12 | 0.945250E+11 | 0.00 | 0.758456E+12 | 0.00 | 0.00 | 0.168725E+12 | 0.506373E+12 | 0.00 |
Minimum of Months | 0.466598E+11 | 0.110454E+11 | 0.132565E+12 | 0.492098E+11 | 0.387356E+11 | 0.543198E+10 | 0.00 | 0.129219E+11 | 0.00 | 0.00 | 0.637269E+10 | 0.382464E+11 | 0.00 |
Maximum of Months | 0.518763E+11 | 0.182892E+11 | 0.146800E+12 | 0.544839E+11 | 0.564026E+11 | 0.102663E+11 | 0.00 | 0.160317E+12 | 0.00 | 0.00 | 0.208990E+11 | 0.468992E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.142966E+12 | 0.00 | 0.131962E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.151786E+12 | 0.00 | 0.123282E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.123989E+12 | 0.00 | 0.126242E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.111519E+12 | 0.00 | 0.114616E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.874659E+11 | 0.00 | 0.101571E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.595497E+10 | 0.00 | 0.821963E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.567710E+10 | 0.00 | 0.802102E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.577204E+10 | 0.00 | 0.798908E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.349441E+11 | 0.00 | 0.844264E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.102763E+12 | 0.00 | 0.106688E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.111321E+12 | 0.00 | 0.114295E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.209445E+12 | 0.00 | 0.132999E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.109360E+13 | 0.00 | 0.127838E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.567710E+10 | 0.00 | 0.798908E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.209445E+12 | 0.00 | 0.132999E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 32111.96 | 20-JAN-22:10 | 4249.60 | 15-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 29481.65 | 17-FEB-22:10 | 4226.69 | 15-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 37014.90 | 15-MAR-21:10 | 4157.14 | 23-MAR-06:30 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.39 | 03-APR-06:19 | 35509.35 | 20-APR-21:10 | 4120.89 | 10-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39154.21 | 19-MAY-06:19 | 36221.04 | 31-MAY-21:00 | 4512.08 | 31-MAY-18:49 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:19 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39154.26 | 16-JUN-06:19 | 44284.74 | 30-JUN-21:10 | 4996.53 | 14-JUN-20:10 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:30 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39154.28 | 28-JUL-06:19 | 44031.56 | 17-JUL-21:10 | 4967.73 | 17-JUL-19:40 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39154.31 | 18-AUG-06:19 | 47460.41 | 16-AUG-21:10 | 4881.84 | 10-AUG-19:19 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.06 | 19-SEP-06:19 | 47069.21 | 12-SEP-21:10 | 4836.42 | 12-SEP-18:49 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 03-OCT-06:19 | 43243.85 | 10-OCT-21:10 | 4173.67 | 25-OCT-08:39 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 36214.44 | 06-NOV-22:10 | 4193.81 | 14-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 01-DEC-07:19 | 32309.13 | 04-DEC-22:10 | 4328.14 | 22-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39154.21 | 29481.65 | 4120.89 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 47460.41 | 4996.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 62587.42 | 20-JAN-13:20 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 38283.35 | 03-JAN-19:00 | 0.00 |
February | 58720.94 | 18-FEB-13:30 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 37681.30 | 28-FEB-19:00 | 0.00 |
March | 81374.52 | 13-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 38577.05 | 30-MAR-18:00 | 0.00 |
April | 64486.21 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 39541.68 | 26-APR-18:10 | 0.00 |
May | 91717.48 | 31-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 40860.45 | 31-MAY-18:40 | 0.00 |
June | 165990.25 | 26-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUN-12:09 | 41366.50 | 30-JUN-20:49 | 0.00 |
July | 134572.71 | 16-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:09 | 41915.00 | 28-JUL-20:49 | 0.00 |
August | 151426.58 | 16-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 02-AUG-09:00 | 42047.42 | 07-AUG-17:49 | 0.00 |
September | 119198.96 | 10-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-12:09 | 42166.26 | 01-SEP-20:49 | 0.00 |
October | 95337.18 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-20:10 | 41875.12 | 03-OCT-18:00 | 0.00 |
November | 66466.64 | 07-NOV-13:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 40707.30 | 01-NOV-18:40 | 0.00 |
December | 58781.22 | 02-DEC-13:20 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 39120.49 | 01-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 58720.94 | 0.00 | 0.00 | 9938.94 | 37681.30 | 0.00 | |||
Maximum of Months | 165990.25 | 0.00 | 0.00 | 9938.94 | 42166.26 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 270323.25 | 24-JAN-20:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 25187.59 | 3620.35 | 0.00 | 11915.64 | 0.00 |
February | 269087.52 | 27-FEB-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 25254.96 | 3613.81 | 0.00 | 10753.62 | 0.00 |
March | 285935.95 | 13-MAR-19:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 30731.42 | 3729.56 | 0.00 | 32675.40 | 0.00 |
April | 280229.90 | 20-APR-20:40 | 44879.15 | 88373.09 | 11096.45 | 24006.45 | 32010.96 | 3704.63 | 0.00 | 34644.96 | 0.00 |
May | 322874.34 | 31-MAY-18:10 | 40749.24 | 78653.57 | 0.00 | 31357.17 | 27559.53 | 4363.32 | 0.00 | 90052.83 | 0.00 |
June | 406303.07 | 26-JUN-18:19 | 40755.77 | 78653.57 | 0.00 | 31364.44 | 36943.57 | 4249.47 | 0.00 | 162335.71 | 0.00 |
July | 385685.86 | 17-JUL-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 35257.46 | 4967.73 | 0.00 | 114271.29 | 0.00 |
August | 390556.23 | 16-AUG-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 37452.02 | 4127.25 | 0.00 | 117132.73 | 0.00 |
September | 368675.97 | 12-SEP-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 38485.52 | 4794.42 | 0.00 | 92786.80 | 0.00 |
October | 298859.38 | 10-OCT-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 31401.36 | 3706.44 | 0.00 | 44760.09 | 0.00 |
November | 279908.45 | 07-NOV-20:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 28796.75 | 3637.72 | 0.00 | 15605.53 | 0.00 |
December | 270120.91 | 04-DEC-20:40 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 26404.90 | 3616.32 | 0.00 | 9540.38 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 269087.52 | 40749.24 | 78653.57 | 0.00 | 24006.45 | 25187.59 | 3613.81 | 0.00 | 9540.38 | 0.00 | |
Maximum of Months | 406303.07 | 50471.22 | 88373.09 | 11096.45 | 31577.78 | 38485.52 | 4967.73 | 0.00 | 162335.71 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 259316.77 | 05-JAN-19:10 | 0.00 | 134233.71 | 30-JAN-18:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 233615.39 | 12-FEB-07:10 | 0.00 | 141634.32 | 15-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 210947.26 | 19-MAR-08:09 | 0.00 | 127256.78 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 183537.30 | 10-APR-08:00 | 0.00 | 119032.28 | 03-APR-21:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 170345.21 | 14-MAY-02:49 | 0.00 | 95818.84 | 01-MAY-17:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 128095.08 | 09-JUN-03:09 | 0.00 | 74087.57 | 01-JUN-18:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 97584.97 | 02-JUL-04:00 | 0.00 | 67112.38 | 01-JUL-17:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 82098.07 | 23-AUG-04:00 | 0.00 | 64721.00 | 31-AUG-19:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 170356.34 | 24-SEP-04:00 | 0.00 | 76171.64 | 30-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 205987.64 | 31-OCT-15:09 | 0.00 | 101586.01 | 31-OCT-22:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 209609.40 | 29-NOV-19:10 | 0.00 | 119269.87 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 314751.84 | 21-DEC-09:09 | 0.00 | 139655.46 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 82098.07 | 0.00 | 64721.00 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 314751.84 | 0.00 | 141634.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.78 | 1.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 21.77 | 2.83 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.80 | 1.33 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.72 | 1.67 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 21.72 | 3.50 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.73 | 1.67 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.82 | 2.17 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.83 | 6.83 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.83 | 5.83 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Annual Sum or Average | 0.17 | 20.55 | 0.17 | 20.55 | 19.83 | 21.80 | 19.83 | 21.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.17 | 20.55 | 6.83 | 21.83 | 6.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.75 | 3.17 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.02 | 1.17 | 22.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.19 | 6.33 | 22.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.13 | 5.83 | 22.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.23 | 7.50 | 22.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.10 | 3.17 | 22.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.33 | 22.16 | 24.33 | 22.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.23 | 7.50 | 22.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 21.80 | 4.17 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 21.77 | 4.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.99 | 3.00 | 21.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.86 | 1.67 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 21.86 | 10.33 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.99 | 3.00 | 21.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.00 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
February | 672.00 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
March | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
April | 720.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
May | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
June | 712.67 | 23.11 | 95.17 | 23.13 | 94.83 | 23.15 |
July | 708.17 | 23.27 | 166.00 | 23.30 | 164.17 | 23.32 |
August | 432.33 | 23.68 | 203.83 | 23.76 | 113.00 | 23.78 |
September | 378.67 | 23.91 | 28.33 | 23.91 | 0.33 | 23.91 |
October | 484.83 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
November | 407.50 | 23.91 | 0.00 | 23.91 | 0.00 | 23.91 |
December | 711.83 | 23.92 | 0.00 | 23.92 | 0.00 | 23.92 |
Annual Sum or Average | 7455.00 | 23.31 | 493.33 | 23.33 | 372.33 | 23.34 |
Minimum of Months | 378.67 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 744.00 | 23.93 | 203.83 | 23.93 | 164.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 580.33 | 21.51 | 183.00 | 21.80 | 78.67 | 21.72 |
February | 530.67 | 21.51 | 224.33 | 21.65 | 151.17 | 21.54 |
March | 614.50 | 21.63 | 151.17 | 21.71 | 100.00 | 21.63 |
April | 661.83 | 21.48 | 125.67 | 21.44 | 115.00 | 21.39 |
May | 663.33 | 21.97 | 20.33 | 22.00 | 4.83 | 22.00 |
June | 336.00 | 22.73 | 298.17 | 23.20 | 59.17 | 23.19 |
July | 354.33 | 22.82 | 392.67 | 23.22 | 131.67 | 23.17 |
August | 318.50 | 22.77 | 386.67 | 23.28 | 86.83 | 23.25 |
September | 344.17 | 22.55 | 221.17 | 23.10 | 0.83 | 23.10 |
October | 551.17 | 21.78 | 211.33 | 22.03 | 93.50 | 21.92 |
November | 558.67 | 21.63 | 176.67 | 21.93 | 65.00 | 21.86 |
December | 631.50 | 21.42 | 273.17 | 21.50 | 212.17 | 21.40 |
Annual Sum or Average | 6145.00 | 21.86 | 2664.33 | 22.19 | 1098.83 | 22.11 |
Minimum of Months | 318.50 | 21.42 | 20.33 | 21.44 | 0.83 | 21.39 |
Maximum of Months | 663.33 | 22.82 | 392.67 | 23.28 | 212.17 | 23.25 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 704.83 | 22.93 | 3.00 | 22.92 | 3.00 | 22.91 |
February | 643.50 | 22.74 | 12.67 | 22.71 | 12.67 | 22.68 |
March | 730.67 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
April | 674.33 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
May | 537.83 | 23.23 | 26.00 | 23.26 | 0.00 | 23.26 |
June | 201.33 | 23.73 | 268.17 | 23.84 | 97.50 | 23.85 |
July | 246.17 | 23.76 | 336.83 | 23.83 | 167.00 | 23.83 |
August | 202.50 | 23.80 | 378.67 | 23.89 | 120.17 | 23.90 |
September | 228.33 | 23.63 | 108.67 | 23.75 | 1.67 | 23.75 |
October | 631.83 | 23.16 | 0.67 | 23.16 | 0.00 | 23.16 |
November | 661.50 | 22.98 | 0.50 | 22.98 | 0.00 | 22.98 |
December | 742.50 | 22.61 | 32.50 | 22.54 | 32.50 | 22.48 |
Annual Sum or Average | 6205.33 | 23.02 | 1167.67 | 23.14 | 434.50 | 23.17 |
Minimum of Months | 201.33 | 22.61 | 0.00 | 22.54 | 0.00 | 22.48 |
Maximum of Months | 742.50 | 23.80 | 378.67 | 23.89 | 167.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.58 | 56.17 | 21.54 | 56.17 | 21.50 |
February | 672.00 | 21.46 | 126.83 | 21.39 | 126.83 | 21.33 |
March | 744.00 | 21.77 | 19.83 | 21.75 | 19.83 | 21.73 |
April | 720.00 | 21.83 | 14.83 | 21.81 | 14.83 | 21.79 |
May | 741.50 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
June | 359.67 | 23.73 | 116.83 | 23.77 | 18.50 | 23.78 |
July | 335.67 | 23.79 | 218.67 | 23.81 | 104.00 | 23.79 |
August | 337.17 | 23.74 | 164.50 | 23.80 | 48.33 | 23.80 |
September | 557.67 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
October | 744.00 | 22.41 | 18.33 | 22.38 | 18.33 | 22.35 |
November | 720.00 | 21.81 | 34.00 | 21.77 | 34.00 | 21.74 |
December | 744.00 | 21.43 | 194.50 | 21.34 | 194.50 | 21.29 |
Annual Sum or Average | 7419.67 | 22.28 | 964.50 | 22.30 | 635.33 | 22.26 |
Minimum of Months | 335.67 | 21.43 | 0.00 | 21.34 | 0.00 | 21.29 |
Maximum of Months | 744.00 | 23.79 | 218.67 | 23.81 | 194.50 | 23.80 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 74.33 | 21.35 | 74.33 | 21.32 |
February | 672.00 | 21.33 | 155.67 | 21.26 | 155.67 | 21.22 |
March | 744.00 | 21.58 | 35.17 | 21.56 | 35.17 | 21.53 |
April | 720.00 | 21.61 | 25.50 | 21.59 | 25.50 | 21.57 |
May | 744.00 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
June | 456.17 | 23.66 | 82.50 | 23.68 | 32.67 | 23.68 |
July | 416.17 | 23.72 | 199.50 | 23.72 | 113.50 | 23.70 |
August | 437.33 | 23.65 | 122.00 | 23.68 | 60.00 | 23.68 |
September | 643.67 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
October | 744.00 | 22.17 | 27.33 | 22.13 | 27.33 | 22.09 |
November | 720.00 | 21.59 | 46.50 | 21.56 | 46.50 | 21.52 |
December | 744.00 | 21.28 | 217.50 | 21.22 | 217.50 | 21.18 |
Annual Sum or Average | 7785.33 | 22.17 | 986.00 | 22.17 | 788.17 | 22.13 |
Minimum of Months | 416.17 | 21.28 | 0.00 | 21.22 | 0.00 | 21.18 |
Maximum of Months | 744.00 | 23.72 | 217.50 | 23.72 | 217.50 | 23.70 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.67 | 23.39 | 622.83 | 23.60 | 162.50 | 23.67 |
February | 199.17 | 23.26 | 543.33 | 23.58 | 141.67 | 23.65 |
March | 212.00 | 23.43 | 624.00 | 23.61 | 163.67 | 23.68 |
April | 210.83 | 23.60 | 621.33 | 23.65 | 178.00 | 23.71 |
May | 265.00 | 23.89 | 681.50 | 23.71 | 252.50 | 23.77 |
June | 336.67 | 23.96 | 702.50 | 23.69 | 336.67 | 23.75 |
July | 388.83 | 23.89 | 732.17 | 23.67 | 388.83 | 23.73 |
August | 374.67 | 23.90 | 728.50 | 23.66 | 374.67 | 23.72 |
September | 270.67 | 23.95 | 670.50 | 23.72 | 265.33 | 23.78 |
October | 219.17 | 23.66 | 636.67 | 23.65 | 189.50 | 23.72 |
November | 210.17 | 23.45 | 616.67 | 23.60 | 165.33 | 23.67 |
December | 214.83 | 23.12 | 560.17 | 23.57 | 139.83 | 23.63 |
Annual Sum or Average | 3115.67 | 23.68 | 7740.17 | 23.65 | 2758.50 | 23.71 |
Minimum of Months | 199.17 | 23.12 | 543.33 | 23.57 | 139.83 | 23.63 |
Maximum of Months | 388.83 | 23.96 | 732.17 | 23.72 | 388.83 | 23.78 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.83 | 22.68 | 188.83 | 23.02 | 15.00 | 22.97 |
February | 386.67 | 22.44 | 191.50 | 22.74 | 40.83 | 22.63 |
March | 438.50 | 22.36 | 130.17 | 22.67 | 11.83 | 22.64 |
April | 487.33 | 22.28 | 91.00 | 22.51 | 8.17 | 22.48 |
May | 297.83 | 22.91 | 187.83 | 23.29 | 10.83 | 23.30 |
June | 167.83 | 23.79 | 593.17 | 23.85 | 155.83 | 23.85 |
July | 207.50 | 23.75 | 654.50 | 23.85 | 196.67 | 23.84 |
August | 188.33 | 23.84 | 642.67 | 23.90 | 178.33 | 23.89 |
September | 76.50 | 23.13 | 475.50 | 23.85 | 4.33 | 23.85 |
October | 301.17 | 22.32 | 238.67 | 22.92 | 24.33 | 22.84 |
November | 345.50 | 22.53 | 197.33 | 23.02 | 8.33 | 22.99 |
December | 520.33 | 22.42 | 180.33 | 22.53 | 70.67 | 22.39 |
Annual Sum or Average | 3830.33 | 22.68 | 3771.50 | 23.23 | 725.17 | 23.22 |
Minimum of Months | 76.50 | 22.28 | 91.00 | 22.51 | 4.33 | 22.39 |
Maximum of Months | 520.33 | 23.84 | 654.50 | 23.90 | 196.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 379.17 | 23.22 | 5.67 | 23.23 | 0.00 | 23.23 |
February | 412.67 | 23.05 | 1.33 | 23.05 | 0.00 | 23.05 |
March | 499.50 | 23.10 | 2.50 | 23.11 | 0.00 | 23.11 |
April | 498.17 | 23.01 | 32.00 | 23.07 | 0.00 | 23.07 |
May | 279.50 | 23.31 | 144.50 | 23.54 | 4.83 | 23.54 |
June | 145.00 | 23.88 | 433.67 | 23.91 | 134.33 | 23.91 |
July | 186.33 | 23.90 | 499.67 | 23.92 | 186.00 | 23.92 |
August | 164.33 | 23.95 | 522.50 | 23.95 | 157.83 | 23.95 |
September | 36.00 | 23.50 | 264.83 | 23.92 | 2.50 | 23.92 |
October | 245.33 | 22.95 | 39.00 | 23.09 | 0.00 | 23.09 |
November | 321.67 | 23.14 | 16.83 | 23.18 | 0.00 | 23.18 |
December | 549.17 | 23.02 | 5.33 | 23.00 | 5.33 | 22.98 |
Annual Sum or Average | 3716.83 | 23.20 | 1967.83 | 23.46 | 490.83 | 23.49 |
Minimum of Months | 36.00 | 22.95 | 1.33 | 23.00 | 0.00 | 22.98 |
Maximum of Months | 549.17 | 23.95 | 522.50 | 23.95 | 186.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 721.83 | 21.34 | 103.50 | 21.26 | 103.50 | 21.20 |
February | 650.33 | 21.25 | 189.33 | 21.13 | 187.50 | 21.05 |
March | 722.67 | 21.26 | 113.33 | 21.13 | 112.50 | 21.04 |
April | 710.67 | 21.26 | 107.17 | 21.16 | 107.17 | 21.08 |
May | 703.83 | 21.56 | 5.83 | 21.56 | 3.17 | 21.56 |
June | 590.83 | 21.39 | 43.17 | 21.53 | 0.83 | 21.53 |
July | 606.17 | 21.38 | 27.83 | 21.46 | 2.83 | 21.46 |
August | 605.50 | 21.38 | 40.00 | 21.50 | 0.83 | 21.50 |
September | 615.50 | 21.44 | 25.33 | 21.52 | 0.00 | 21.52 |
October | 696.33 | 21.29 | 104.00 | 21.21 | 91.33 | 21.13 |
November | 683.17 | 21.30 | 85.17 | 21.22 | 83.17 | 21.16 |
December | 733.83 | 21.17 | 295.33 | 21.04 | 295.33 | 20.96 |
Annual Sum or Average | 8040.67 | 21.33 | 1140.00 | 21.29 | 988.17 | 21.22 |
Minimum of Months | 590.83 | 21.17 | 5.83 | 21.04 | 0.00 | 20.96 |
Maximum of Months | 733.83 | 21.56 | 295.33 | 21.56 | 295.33 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 261.83 | 20.87 | 261.83 | 20.80 |
February | 672.00 | 20.97 | 318.17 | 20.85 | 318.17 | 20.78 |
March | 720.67 | 21.14 | 181.50 | 21.08 | 166.83 | 20.97 |
April | 706.00 | 21.23 | 131.17 | 21.18 | 121.33 | 21.09 |
May | 653.83 | 21.75 | 39.83 | 21.92 | 6.00 | 21.94 |
June | 522.00 | 21.79 | 120.33 | 22.25 | 34.67 | 22.37 |
July | 552.50 | 21.88 | 119.50 | 22.32 | 63.00 | 22.48 |
August | 566.17 | 21.88 | 101.50 | 22.28 | 38.33 | 22.41 |
September | 583.33 | 21.85 | 48.17 | 22.10 | 0.83 | 22.11 |
October | 708.50 | 21.29 | 110.17 | 21.24 | 97.67 | 21.14 |
November | 719.67 | 21.10 | 170.17 | 20.98 | 170.17 | 20.90 |
December | 744.00 | 20.87 | 464.67 | 20.77 | 464.67 | 20.72 |
Annual Sum or Average | 7892.67 | 21.35 | 2067.00 | 21.37 | 1743.50 | 21.29 |
Minimum of Months | 522.00 | 20.87 | 39.83 | 20.77 | 0.83 | 20.72 |
Maximum of Months | 744.00 | 21.88 | 464.67 | 22.32 | 464.67 | 22.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 159.83 | 20.96 | 159.83 | 20.92 |
February | 672.00 | 21.00 | 182.50 | 20.92 | 182.50 | 20.86 |
March | 744.00 | 21.23 | 34.00 | 21.20 | 34.00 | 21.17 |
April | 720.00 | 21.33 | 10.17 | 21.32 | 10.17 | 21.31 |
May | 743.83 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
June | 704.67 | 22.09 | 28.00 | 22.15 | 22.00 | 22.19 |
July | 728.83 | 22.14 | 56.67 | 22.24 | 53.67 | 22.31 |
August | 731.17 | 22.07 | 27.50 | 22.12 | 21.33 | 22.15 |
September | 720.00 | 21.99 | 0.00 | 21.99 | 0.00 | 21.99 |
October | 744.00 | 21.32 | 29.33 | 21.28 | 29.33 | 21.24 |
November | 720.00 | 21.10 | 73.50 | 21.05 | 73.50 | 21.00 |
December | 744.00 | 20.96 | 274.00 | 20.87 | 274.00 | 20.83 |
Annual Sum or Average | 8716.50 | 21.51 | 875.50 | 21.46 | 860.33 | 21.41 |
Minimum of Months | 672.00 | 20.96 | 0.00 | 20.87 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 22.14 | 274.00 | 22.24 | 274.00 | 22.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.43 | 100.67 | 21.35 | 100.67 | 21.28 |
February | 665.33 | 21.35 | 200.83 | 21.21 | 200.83 | 21.12 |
March | 720.50 | 21.33 | 106.83 | 21.20 | 106.83 | 21.09 |
April | 705.50 | 21.33 | 101.17 | 21.24 | 100.67 | 21.16 |
May | 700.83 | 21.61 | 4.33 | 21.60 | 4.33 | 21.60 |
June | 539.83 | 21.23 | 15.17 | 21.29 | 0.33 | 21.29 |
July | 564.17 | 21.25 | 23.17 | 21.33 | 1.67 | 21.34 |
August | 563.50 | 21.26 | 37.33 | 21.38 | 0.00 | 21.38 |
September | 590.00 | 21.39 | 6.00 | 21.41 | 0.00 | 21.41 |
October | 700.00 | 21.34 | 89.00 | 21.23 | 88.33 | 21.14 |
November | 715.17 | 21.41 | 94.50 | 21.31 | 94.50 | 21.24 |
December | 744.00 | 21.22 | 301.50 | 21.08 | 301.50 | 21.01 |
Annual Sum or Average | 7952.67 | 21.35 | 1080.50 | 21.29 | 999.67 | 21.22 |
Minimum of Months | 539.83 | 21.22 | 4.33 | 21.08 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.61 | 301.50 | 21.60 | 301.50 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 262.83 | 20.84 | 262.83 | 20.78 |
February | 672.00 | 20.99 | 311.83 | 20.87 | 311.83 | 20.80 |
March | 743.50 | 21.31 | 145.00 | 21.16 | 145.00 | 21.06 |
April | 715.67 | 21.37 | 115.67 | 21.26 | 114.33 | 21.17 |
May | 694.67 | 21.92 | 15.33 | 21.97 | 5.50 | 21.97 |
June | 468.50 | 21.86 | 129.83 | 22.59 | 52.00 | 22.86 |
July | 487.00 | 21.86 | 148.50 | 22.55 | 73.33 | 22.79 |
August | 483.83 | 21.84 | 118.33 | 22.47 | 45.83 | 22.71 |
September | 580.50 | 21.91 | 31.33 | 22.08 | 1.00 | 22.09 |
October | 741.17 | 21.43 | 95.17 | 21.31 | 94.50 | 21.22 |
November | 720.00 | 21.05 | 189.67 | 20.93 | 189.67 | 20.86 |
December | 744.00 | 20.82 | 476.50 | 20.75 | 476.50 | 20.71 |
Annual Sum or Average | 7794.83 | 21.39 | 2040.00 | 21.42 | 1772.33 | 21.36 |
Minimum of Months | 468.50 | 20.82 | 15.33 | 20.75 | 1.00 | 20.71 |
Maximum of Months | 744.00 | 21.92 | 476.50 | 22.59 | 476.50 | 22.86 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.51 | 30.50 | 21.49 | 30.50 | 21.47 |
February | 672.00 | 21.47 | 69.17 | 21.43 | 69.17 | 21.39 |
March | 744.00 | 21.77 | 1.83 | 21.77 | 1.83 | 21.76 |
April | 720.00 | 21.58 | 6.67 | 21.58 | 6.67 | 21.57 |
May | 744.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
June | 483.00 | 23.72 | 155.67 | 23.74 | 120.33 | 23.75 |
July | 414.33 | 23.83 | 263.83 | 23.83 | 169.00 | 23.82 |
August | 372.50 | 23.83 | 206.67 | 23.84 | 134.50 | 23.84 |
September | 525.17 | 23.57 | 4.83 | 23.58 | 0.00 | 23.58 |
October | 744.00 | 22.44 | 25.17 | 22.39 | 25.17 | 22.35 |
November | 720.00 | 21.67 | 22.67 | 21.65 | 22.67 | 21.63 |
December | 744.00 | 21.25 | 183.50 | 21.20 | 183.50 | 21.17 |
Annual Sum or Average | 7627.00 | 22.25 | 970.50 | 22.32 | 763.33 | 22.33 |
Minimum of Months | 372.50 | 21.25 | 0.00 | 21.20 | 0.00 | 21.17 |
Maximum of Months | 744.00 | 23.83 | 263.83 | 23.84 | 183.50 | 23.84 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 720.33 | 21.24 | 192.17 | 21.14 | 191.33 | 21.08 |
February | 648.17 | 21.18 | 253.00 | 21.06 | 249.83 | 20.99 |
March | 714.83 | 21.17 | 212.83 | 21.04 | 210.33 | 20.95 |
April | 700.50 | 21.16 | 171.83 | 21.03 | 171.67 | 20.93 |
May | 688.33 | 21.49 | 24.67 | 21.51 | 13.50 | 21.51 |
June | 570.33 | 21.33 | 68.50 | 21.53 | 5.83 | 21.53 |
July | 592.00 | 21.33 | 81.33 | 21.49 | 29.17 | 21.48 |
August | 587.17 | 21.32 | 75.33 | 21.50 | 16.17 | 21.50 |
September | 607.00 | 21.39 | 40.83 | 21.51 | 1.00 | 21.51 |
October | 692.00 | 21.22 | 142.17 | 21.15 | 125.50 | 21.05 |
November | 678.83 | 21.22 | 170.00 | 21.12 | 163.50 | 21.04 |
December | 728.67 | 21.06 | 408.33 | 20.93 | 408.33 | 20.87 |
Annual Sum or Average | 7928.17 | 21.25 | 1841.00 | 21.21 | 1586.17 | 21.14 |
Minimum of Months | 570.33 | 21.06 | 24.67 | 20.93 | 1.00 | 20.87 |
Maximum of Months | 728.67 | 21.49 | 408.33 | 21.53 | 408.33 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 394.50 | 20.75 | 394.50 | 20.70 |
February | 672.00 | 20.88 | 382.17 | 20.77 | 382.17 | 20.72 |
March | 720.17 | 21.08 | 317.50 | 21.02 | 302.83 | 20.93 |
April | 702.67 | 21.18 | 205.33 | 21.10 | 195.50 | 21.00 |
May | 635.17 | 21.71 | 69.00 | 21.96 | 18.67 | 21.99 |
June | 504.00 | 21.76 | 142.17 | 22.29 | 38.67 | 22.43 |
July | 546.50 | 21.87 | 147.83 | 22.35 | 72.67 | 22.52 |
August | 551.00 | 21.86 | 120.83 | 22.29 | 49.83 | 22.45 |
September | 581.83 | 21.82 | 59.17 | 22.11 | 5.50 | 22.14 |
October | 702.50 | 21.19 | 179.00 | 21.14 | 161.50 | 21.04 |
November | 719.00 | 21.00 | 283.67 | 20.88 | 283.67 | 20.80 |
December | 744.00 | 20.77 | 595.50 | 20.70 | 595.50 | 20.68 |
Annual Sum or Average | 7822.83 | 21.28 | 2896.67 | 21.30 | 2501.00 | 21.22 |
Minimum of Months | 504.00 | 20.77 | 59.17 | 20.70 | 5.50 | 20.68 |
Maximum of Months | 744.00 | 21.87 | 595.50 | 22.35 | 595.50 | 22.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 631.17 | 21.27 | 129.17 | 21.41 | 58.83 | 21.36 |
February | 581.00 | 21.20 | 170.17 | 21.23 | 127.83 | 21.14 |
March | 674.33 | 21.21 | 109.50 | 21.14 | 93.33 | 21.05 |
April | 684.33 | 21.26 | 100.33 | 21.17 | 100.33 | 21.10 |
May | 699.33 | 21.55 | 4.33 | 21.54 | 4.33 | 21.54 |
June | 605.33 | 21.42 | 2.67 | 21.42 | 2.67 | 21.43 |
July | 620.67 | 21.41 | 14.00 | 21.43 | 11.67 | 21.43 |
August | 603.83 | 21.36 | 59.67 | 21.53 | 3.50 | 21.53 |
September | 596.67 | 21.39 | 66.50 | 21.58 | 0.00 | 21.58 |
October | 640.83 | 21.18 | 154.00 | 21.28 | 85.50 | 21.19 |
November | 611.50 | 21.26 | 127.83 | 21.40 | 60.67 | 21.35 |
December | 671.17 | 21.28 | 192.17 | 21.29 | 154.33 | 21.22 |
Annual Sum or Average | 7620.17 | 21.32 | 1130.33 | 21.36 | 703.00 | 21.31 |
Minimum of Months | 581.00 | 21.18 | 2.67 | 21.14 | 0.00 | 21.05 |
Maximum of Months | 699.33 | 21.55 | 192.17 | 21.58 | 154.33 | 21.58 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.33 | 23.39 | 16.67 | 23.42 | 0.00 | 23.42 |
February | 396.83 | 23.42 | 13.83 | 23.44 | 0.00 | 23.44 |
March | 285.17 | 23.44 | 26.00 | 23.48 | 0.00 | 23.48 |
April | 197.00 | 23.47 | 142.50 | 23.69 | 0.00 | 23.69 |
May | 21.67 | 23.52 | 452.83 | 23.97 | 2.83 | 23.97 |
June | 137.50 | 24.00 | 679.50 | 24.00 | 137.50 | 24.00 |
July | 192.00 | 24.00 | 724.33 | 24.00 | 192.00 | 24.00 |
August | 164.17 | 24.00 | 700.50 | 24.00 | 164.17 | 24.00 |
September | 9.00 | 23.61 | 430.17 | 23.99 | 2.83 | 23.99 |
October | 175.83 | 23.34 | 102.50 | 23.58 | 0.00 | 23.58 |
November | 287.50 | 23.34 | 26.67 | 23.40 | 0.00 | 23.40 |
December | 531.83 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 2802.83 | 23.49 | 3315.50 | 23.77 | 499.33 | 23.78 |
Minimum of Months | 9.00 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
Maximum of Months | 531.83 | 24.00 | 724.33 | 24.00 | 192.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 252.67 | 23.50 | 114.00 | 23.66 | 0.00 | 23.66 |
February | 220.33 | 23.47 | 64.67 | 23.58 | 0.00 | 23.58 |
March | 140.50 | 23.50 | 96.33 | 23.70 | 0.00 | 23.70 |
April | 64.67 | 23.47 | 241.17 | 23.88 | 0.00 | 23.88 |
May | 6.00 | 23.81 | 536.00 | 23.99 | 2.50 | 23.99 |
June | 132.50 | 24.00 | 704.83 | 24.00 | 132.50 | 24.00 |
July | 188.33 | 24.00 | 732.17 | 24.00 | 188.33 | 24.00 |
August | 158.00 | 24.00 | 726.33 | 24.00 | 158.00 | 24.00 |
September | 3.67 | 23.89 | 531.33 | 23.99 | 2.83 | 23.99 |
October | 61.67 | 23.23 | 200.00 | 23.81 | 0.00 | 23.81 |
November | 139.67 | 23.35 | 139.33 | 23.67 | 0.00 | 23.67 |
December | 344.67 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 1712.67 | 23.59 | 4086.17 | 23.88 | 484.17 | 23.88 |
Minimum of Months | 3.67 | 23.23 | 0.00 | 23.38 | 0.00 | 23.38 |
Maximum of Months | 344.67 | 24.00 | 732.17 | 24.00 | 188.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 503.00 | 23.92 | 683.00 | 23.91 | 478.50 | 23.93 |
February | 456.33 | 23.89 | 595.17 | 23.91 | 426.67 | 23.93 |
March | 500.83 | 23.96 | 694.83 | 23.94 | 491.17 | 23.95 |
April | 496.00 | 23.97 | 686.50 | 23.94 | 489.67 | 23.95 |
May | 537.33 | 23.99 | 740.17 | 23.97 | 537.33 | 23.97 |
June | 560.17 | 23.99 | 720.00 | 23.99 | 560.17 | 23.99 |
July | 603.17 | 23.99 | 744.00 | 23.99 | 603.17 | 23.99 |
August | 607.00 | 23.99 | 744.00 | 23.99 | 607.00 | 23.99 |
September | 520.83 | 23.99 | 718.17 | 23.98 | 520.83 | 23.98 |
October | 502.17 | 23.97 | 723.33 | 23.94 | 497.17 | 23.95 |
November | 491.33 | 23.94 | 670.17 | 23.92 | 476.83 | 23.94 |
December | 482.67 | 23.82 | 636.33 | 23.89 | 437.33 | 23.92 |
Annual Sum or Average | 6260.83 | 23.95 | 8355.67 | 23.95 | 6125.83 | 23.96 |
Minimum of Months | 456.33 | 23.82 | 595.17 | 23.89 | 426.67 | 23.92 |
Maximum of Months | 607.00 | 23.99 | 744.00 | 23.99 | 607.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.35 | 83.67 | 21.31 | 83.67 | 21.28 |
February | 672.00 | 21.37 | 128.17 | 21.31 | 128.17 | 21.27 |
March | 744.00 | 21.67 | 40.67 | 21.64 | 40.67 | 21.61 |
April | 720.00 | 21.57 | 20.33 | 21.55 | 20.33 | 21.54 |
May | 730.83 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
June | 275.50 | 23.47 | 157.00 | 23.60 | 58.17 | 23.61 |
July | 293.00 | 23.52 | 284.33 | 23.63 | 135.33 | 23.61 |
August | 284.83 | 23.44 | 225.33 | 23.60 | 84.17 | 23.59 |
September | 483.83 | 23.12 | 10.17 | 23.13 | 0.00 | 23.13 |
October | 741.83 | 22.10 | 40.67 | 22.05 | 40.67 | 21.99 |
November | 720.00 | 21.54 | 47.83 | 21.50 | 47.83 | 21.47 |
December | 744.00 | 21.22 | 221.50 | 21.17 | 221.50 | 21.14 |
Annual Sum or Average | 7153.83 | 21.99 | 1259.67 | 22.06 | 860.50 | 22.04 |
Minimum of Months | 275.50 | 21.22 | 0.00 | 21.17 | 0.00 | 21.14 |
Maximum of Months | 744.00 | 23.52 | 284.33 | 23.63 | 221.50 | 23.61 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.51439 | 25.46433 | 0.09904 | 5.35673 |
February | 672.00000 | 23.14917 | 24.16857 | -0.0017 | 5.18296 |
March | 744.00000 | 22.71546 | 23.80519 | -0.1114 | 5.44493 |
April | 720.00000 | 22.78675 | 28.01304 | -0.0680 | 5.29526 |
May | 744.00000 | 22.72215 | 32.04059 | -1.1026 | 30.83417 |
June | 720.00000 | 23.11640 | 39.70040 | -0.9096 | 22.82258 |
July | 744.00000 | 23.29720 | 41.96530 | -0.8300 | 19.91480 |
August | 744.00000 | 23.76938 | 40.39719 | -0.6642 | 14.58565 |
September | 720.00000 | 23.93709 | 28.75216 | -0.6659 | 14.44007 |
October | 744.00000 | 23.95345 | 24.22674 | 0.22217 | 6.09790 |
November | 720.00000 | 23.94976 | 25.30969 | 0.22646 | 6.13159 |
December | 744.00000 | 23.92131 | 19.34864 | 0.17189 | 5.67812 |
Annual Sum or Average | 8760.00000 | 23.40430 | 29.46484 | -0.3047 | 11.86600 |
Minimum of Months | 672.00000 | 22.71546 | 19.34864 | -1.1026 | 5.18296 |
Maximum of Months | 744.00000 | 23.95345 | 41.96530 | 0.22646 | 30.83417 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.04884 | 25.30904 | -0.1790 | 8.82085 |
February | 672.00000 | 22.03280 | 23.44044 | -0.2193 | 9.43105 |
March | 744.00000 | 22.04043 | 22.82680 | -0.2205 | 8.83009 |
April | 720.00000 | 21.67691 | 27.73695 | -0.3004 | 8.73559 |
May | 744.00000 | 22.15592 | 31.01114 | -1.1555 | 34.88889 |
June | 720.00000 | 23.28944 | 37.37822 | -0.6576 | 15.54624 |
July | 744.00000 | 23.32967 | 39.99175 | -0.6233 | 14.59978 |
August | 744.00000 | 23.36379 | 39.36610 | -0.5965 | 14.13470 |
September | 720.00000 | 23.24839 | 28.47284 | -0.7082 | 18.44094 |
October | 744.00000 | 22.34481 | 25.16086 | -0.0932 | 8.41577 |
November | 720.00000 | 22.15270 | 26.50473 | -0.1401 | 8.61401 |
December | 744.00000 | 21.81199 | 19.79592 | -0.3141 | 10.21181 |
Annual Sum or Average | 8760.00000 | 22.46000 | 28.94911 | -0.4356 | 13.42776 |
Minimum of Months | 672.00000 | 21.67691 | 19.79592 | -1.1555 | 8.41577 |
Maximum of Months | 744.00000 | 23.36379 | 39.99175 | -0.0932 | 34.88889 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.98536 | 26.37639 | 0.00272 | 5.58476 |
February | 672.00000 | 22.79513 | 24.80471 | -0.0579 | 6.01748 |
March | 744.00000 | 22.91005 | 24.03916 | -0.0302 | 5.74117 |
April | 720.00000 | 22.82940 | 28.30622 | -0.0256 | 5.79007 |
May | 744.00000 | 23.41722 | 31.19442 | -0.8067 | 19.38970 |
June | 720.00000 | 23.85864 | 37.85796 | -0.5687 | 11.99865 |
July | 744.00000 | 23.87394 | 40.44487 | -0.5468 | 11.45893 |
August | 744.00000 | 23.88170 | 40.00399 | -0.5457 | 11.46460 |
September | 720.00000 | 23.85168 | 29.50001 | -0.6355 | 13.80711 |
October | 744.00000 | 23.28415 | 26.12919 | 0.08526 | 5.91263 |
November | 720.00000 | 23.05959 | 27.55275 | 0.03112 | 5.69440 |
December | 744.00000 | 22.61283 | 21.32502 | -0.1277 | 6.38030 |
Annual Sum or Average | 8760.00000 | 23.28265 | 29.82451 | -0.2702 | 9.12628 |
Minimum of Months | 672.00000 | 22.61283 | 21.32502 | -0.8067 | 5.58476 |
Maximum of Months | 744.00000 | 23.88170 | 40.44487 | 0.08526 | 19.38970 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.38646 | 21.21197 | 0.67055 | 16.48412 |
February | 672.00000 | 23.36837 | 19.49721 | 0.64780 | 15.95974 |
March | 744.00000 | 23.38946 | 18.66898 | 0.66873 | 16.39017 |
April | 720.00000 | 23.41957 | 22.81025 | 0.70226 | 17.39909 |
May | 744.00000 | 23.48936 | 26.39399 | 0.10575 | 9.03976 |
June | 720.00000 | 23.52202 | 34.33105 | 0.23294 | 9.79471 |
July | 744.00000 | 23.53035 | 37.02191 | 0.24966 | 9.81148 |
August | 744.00000 | 23.51003 | 36.54176 | 0.23936 | 9.80554 |
September | 720.00000 | 23.51233 | 25.71621 | 0.14437 | 9.06209 |
October | 744.00000 | 23.40680 | 21.25149 | 0.70395 | 17.36110 |
November | 720.00000 | 23.38518 | 22.41405 | 0.68729 | 16.98428 |
December | 744.00000 | 23.34265 | 16.00403 | 0.60602 | 14.90430 |
Annual Sum or Average | 8760.00000 | 23.43889 | 25.18901 | 0.47043 | 13.56649 |
Minimum of Months | 672.00000 | 23.34265 | 16.00403 | 0.10575 | 9.03976 |
Maximum of Months | 744.00000 | 23.53035 | 37.02191 | 0.70395 | 17.39909 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.23753 | 28.91188 | 0.17822 | 7.66180 |
February | 672.00000 | 23.07926 | 27.35764 | 0.10947 | 8.08037 |
March | 744.00000 | 23.01501 | 26.82945 | 0.08824 | 7.43174 |
April | 720.00000 | 22.79011 | 31.46221 | 0.03420 | 6.92673 |
May | 744.00000 | 23.40503 | 34.39724 | -0.6731 | 15.61015 |
June | 720.00000 | 23.81252 | 41.02080 | -0.4006 | 8.74086 |
July | 744.00000 | 23.83371 | 43.55064 | -0.3700 | 8.28836 |
August | 744.00000 | 23.86838 | 42.75524 | -0.3383 | 7.91407 |
September | 720.00000 | 23.84692 | 32.24375 | -0.4190 | 9.76003 |
October | 744.00000 | 23.28558 | 28.87435 | 0.20390 | 8.29467 |
November | 720.00000 | 23.25315 | 30.08551 | 0.19674 | 7.94309 |
December | 744.00000 | 22.88120 | 23.99729 | 0.02272 | 7.82131 |
Annual Sum or Average | 8760.00000 | 23.36060 | 32.65529 | -0.1154 | 8.71522 |
Minimum of Months | 672.00000 | 22.79011 | 23.99729 | -0.6731 | 6.92673 |
Maximum of Months | 744.00000 | 23.86838 | 43.55064 | 0.20390 | 15.61015 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.57819 | 28.21676 | 0.18690 | 6.23084 |
February | 672.00000 | 23.39772 | 26.75456 | 0.12545 | 6.22059 |
March | 744.00000 | 23.39164 | 25.98549 | 0.12459 | 5.94231 |
April | 720.00000 | 23.29965 | 30.25350 | 0.12356 | 5.99019 |
May | 744.00000 | 23.67699 | 33.03381 | -0.6581 | 14.55360 |
June | 720.00000 | 23.88567 | 39.84140 | -0.4902 | 10.19995 |
July | 744.00000 | 23.90811 | 42.35675 | -0.4627 | 9.64848 |
August | 744.00000 | 23.93265 | 41.81204 | -0.4537 | 9.45717 |
September | 720.00000 | 23.94256 | 31.33483 | -0.5293 | 11.06024 |
October | 744.00000 | 23.63179 | 27.93671 | 0.21595 | 6.63845 |
November | 720.00000 | 23.59461 | 29.31513 | 0.20356 | 6.39022 |
December | 744.00000 | 23.26972 | 23.38667 | 0.06704 | 6.11910 |
Annual Sum or Average | 8760.00000 | 23.62705 | 31.71520 | -0.1305 | 8.21831 |
Minimum of Months | 672.00000 | 23.26972 | 23.38667 | -0.6581 | 5.94231 |
Maximum of Months | 744.00000 | 23.94256 | 42.35675 | 0.21595 | 14.55360 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39467 | 41.19026 | -0.3749 | 9.31076 |
February | 672.00000 | 21.32068 | 39.60488 | -0.4112 | 10.21005 |
March | 744.00000 | 21.31827 | 38.12786 | -0.3827 | 9.49917 |
April | 720.00000 | 21.28796 | 42.29682 | -0.3764 | 9.18860 |
May | 744.00000 | 21.65199 | 42.59647 | -1.3131 | 42.20254 |
June | 720.00000 | 21.73650 | 44.77393 | -1.1238 | 33.34392 |
July | 744.00000 | 21.73665 | 45.49585 | -1.1331 | 33.71078 |
August | 744.00000 | 21.73323 | 45.49290 | -1.1324 | 33.77937 |
September | 720.00000 | 21.71266 | 39.78636 | -1.2089 | 37.50704 |
October | 744.00000 | 21.42062 | 40.38121 | -0.3067 | 8.74765 |
November | 720.00000 | 21.40606 | 42.50124 | -0.3479 | 9.03241 |
December | 744.00000 | 21.20046 | 36.14487 | -0.4961 | 11.68265 |
Annual Sum or Average | 8760.00000 | 21.49427 | 41.53972 | -0.7193 | 20.75332 |
Minimum of Months | 672.00000 | 21.20046 | 36.14487 | -1.3131 | 8.74765 |
Maximum of Months | 744.00000 | 21.73665 | 45.49585 | -0.3067 | 42.20254 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98378 | 42.15287 | -0.5322 | 11.65157 |
February | 672.00000 | 20.96614 | 40.32131 | -0.5493 | 12.29336 |
March | 744.00000 | 21.28236 | 38.34170 | -0.4357 | 10.60954 |
April | 720.00000 | 21.32251 | 42.39948 | -0.3919 | 9.67246 |
May | 744.00000 | 22.05353 | 41.81163 | -1.2174 | 38.61366 |
June | 720.00000 | 22.34089 | 44.01718 | -0.9586 | 27.41555 |
July | 744.00000 | 22.38087 | 45.04281 | -0.9581 | 27.52759 |
August | 744.00000 | 22.34581 | 45.18431 | -0.9843 | 28.64822 |
September | 720.00000 | 22.28571 | 39.03382 | -1.0983 | 33.38266 |
October | 744.00000 | 21.44515 | 40.26464 | -0.3551 | 9.39034 |
November | 720.00000 | 21.10086 | 43.23368 | -0.4795 | 10.69739 |
December | 744.00000 | 20.86605 | 36.82278 | -0.6274 | 14.10982 |
Annual Sum or Average | 8760.00000 | 21.61818 | 41.55552 | -0.7168 | 19.55159 |
Minimum of Months | 672.00000 | 20.86605 | 36.82278 | -1.2174 | 9.39034 |
Maximum of Months | 744.00000 | 22.38087 | 45.18431 | -0.3551 | 38.61366 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02648 | 38.06812 | -0.5137 | 10.69760 |
February | 672.00000 | 21.00480 | 36.37076 | -0.5319 | 11.13968 |
March | 744.00000 | 21.22696 | 34.15617 | -0.4618 | 9.61986 |
April | 720.00000 | 21.33464 | 38.37051 | -0.3967 | 8.57766 |
May | 744.00000 | 21.83194 | 38.87378 | -1.3523 | 43.61129 |
June | 720.00000 | 22.13604 | 43.46904 | -1.1592 | 34.56845 |
July | 744.00000 | 22.18249 | 44.76001 | -1.1357 | 33.63038 |
August | 744.00000 | 22.10636 | 44.77343 | -1.1804 | 35.45537 |
September | 720.00000 | 21.98850 | 36.75783 | -1.2981 | 40.98772 |
October | 744.00000 | 21.31628 | 36.51978 | -0.4111 | 8.81313 |
November | 720.00000 | 21.10331 | 39.28973 | -0.4772 | 9.92438 |
December | 744.00000 | 20.95650 | 32.51597 | -0.5743 | 12.20889 |
Annual Sum or Average | 8760.00000 | 21.52073 | 38.67036 | -0.7927 | 21.66792 |
Minimum of Months | 672.00000 | 20.95650 | 32.51597 | -1.3523 | 8.57766 |
Maximum of Months | 744.00000 | 22.18249 | 44.77343 | -0.3967 | 43.61129 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43126 | 41.19963 | -0.3698 | 9.20819 |
February | 672.00000 | 21.36831 | 39.57018 | -0.3988 | 10.12755 |
March | 744.00000 | 21.39325 | 38.09082 | -0.3590 | 9.32687 |
April | 720.00000 | 21.37454 | 42.10212 | -0.3464 | 8.96074 |
May | 744.00000 | 21.70712 | 42.27112 | -1.2819 | 40.73861 |
June | 720.00000 | 21.75508 | 44.46397 | -1.1016 | 32.39513 |
July | 744.00000 | 21.75267 | 45.15298 | -1.1020 | 32.43066 |
August | 744.00000 | 21.75328 | 45.00643 | -1.1019 | 32.54761 |
September | 720.00000 | 21.73660 | 39.71943 | -1.1884 | 36.60275 |
October | 744.00000 | 21.45433 | 40.32687 | -0.3002 | 8.72453 |
November | 720.00000 | 21.41902 | 42.47070 | -0.3494 | 9.01201 |
December | 744.00000 | 21.21903 | 36.17959 | -0.4922 | 11.53152 |
Annual Sum or Average | 8760.00000 | 21.53126 | 41.38549 | -0.7013 | 20.19846 |
Minimum of Months | 672.00000 | 21.21903 | 36.17959 | -1.2819 | 8.72453 |
Maximum of Months | 744.00000 | 21.75508 | 45.15298 | -0.3002 | 40.73861 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94460 | 42.21331 | -0.5430 | 11.71850 |
February | 672.00000 | 20.99184 | 40.18679 | -0.5412 | 12.16357 |
March | 744.00000 | 21.30801 | 38.13814 | -0.4223 | 9.92831 |
April | 720.00000 | 21.38071 | 42.09234 | -0.3686 | 9.18115 |
May | 744.00000 | 22.05561 | 41.56636 | -1.2019 | 37.38684 |
June | 720.00000 | 22.54762 | 43.72599 | -0.8801 | 26.48873 |
July | 744.00000 | 22.53736 | 44.70643 | -0.8844 | 26.02398 |
August | 744.00000 | 22.51208 | 44.46556 | -0.9103 | 27.16495 |
September | 720.00000 | 22.30024 | 38.82254 | -1.0799 | 32.40607 |
October | 744.00000 | 21.44049 | 40.14518 | -0.3578 | 9.05939 |
November | 720.00000 | 21.05035 | 43.28041 | -0.4941 | 10.85697 |
December | 744.00000 | 20.82041 | 36.85303 | -0.6370 | 14.20602 |
Annual Sum or Average | 8760.00000 | 21.66114 | 41.35232 | -0.6945 | 18.92793 |
Minimum of Months | 672.00000 | 20.82041 | 36.85303 | -1.2019 | 9.05939 |
Maximum of Months | 744.00000 | 22.54762 | 44.70643 | -0.3578 | 37.38684 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30812 | 42.11206 | -0.4293 | 10.43693 |
February | 672.00000 | 21.25240 | 40.46243 | -0.4602 | 11.34520 |
March | 744.00000 | 21.25371 | 39.00654 | -0.4232 | 10.47604 |
April | 720.00000 | 21.22160 | 43.33971 | -0.4114 | 10.10664 |
May | 744.00000 | 21.62992 | 43.25151 | -1.3335 | 43.44754 |
June | 720.00000 | 21.73231 | 45.13725 | -1.1209 | 33.54290 |
July | 744.00000 | 21.73093 | 45.99526 | -1.1343 | 34.04339 |
August | 744.00000 | 21.72671 | 46.17618 | -1.1331 | 34.13686 |
September | 720.00000 | 21.69216 | 40.14647 | -1.2315 | 38.88240 |
October | 744.00000 | 21.36722 | 41.21129 | -0.3477 | 9.64271 |
November | 720.00000 | 21.33608 | 43.46867 | -0.3940 | 10.03748 |
December | 744.00000 | 21.10638 | 36.89607 | -0.5565 | 13.23536 |
Annual Sum or Average | 8760.00000 | 21.44752 | 42.27350 | -0.7499 | 21.67872 |
Minimum of Months | 672.00000 | 21.10638 | 36.89607 | -1.3335 | 9.64271 |
Maximum of Months | 744.00000 | 21.73231 | 46.17618 | -0.3477 | 43.44754 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86250 | 43.27159 | -0.5984 | 13.30952 |
February | 672.00000 | 20.88269 | 41.28312 | -0.6056 | 13.74695 |
March | 744.00000 | 21.22764 | 39.27287 | -0.4758 | 11.83514 |
April | 720.00000 | 21.27833 | 43.46085 | -0.4224 | 10.69605 |
May | 744.00000 | 22.07397 | 42.40481 | -1.2211 | 39.49965 |
June | 720.00000 | 22.33236 | 44.15993 | -0.9524 | 27.65633 |
July | 744.00000 | 22.36093 | 45.30421 | -0.9591 | 28.04793 |
August | 744.00000 | 22.33108 | 45.64869 | -0.9835 | 29.21954 |
September | 720.00000 | 22.25686 | 39.41108 | -1.1197 | 34.88060 |
October | 744.00000 | 21.39048 | 41.24139 | -0.3987 | 10.49668 |
November | 720.00000 | 21.00914 | 44.33269 | -0.5352 | 12.02121 |
December | 744.00000 | 20.76818 | 37.64444 | -0.6917 | 15.97361 |
Annual Sum or Average | 8760.00000 | 21.56842 | 42.28847 | -0.7480 | 20.66407 |
Minimum of Months | 672.00000 | 20.76818 | 37.64444 | -1.2211 | 10.49668 |
Maximum of Months | 744.00000 | 22.36093 | 45.64869 | -0.3987 | 39.49965 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57989 | 41.57307 | -0.2506 | 8.51605 |
February | 672.00000 | 21.49198 | 40.18232 | -0.3068 | 9.48849 |
March | 744.00000 | 21.41232 | 38.42481 | -0.3369 | 9.31565 |
April | 720.00000 | 21.35883 | 42.30444 | -0.3616 | 9.18249 |
May | 744.00000 | 21.65276 | 42.67792 | -1.3525 | 44.25315 |
June | 720.00000 | 21.72525 | 45.35397 | -1.2016 | 36.93441 |
July | 744.00000 | 21.72967 | 45.96533 | -1.1896 | 36.39782 |
August | 744.00000 | 21.72734 | 45.76221 | -1.1717 | 35.81795 |
September | 720.00000 | 21.71922 | 39.82448 | -1.2175 | 38.32171 |
October | 744.00000 | 21.47885 | 40.53827 | -0.2654 | 8.76956 |
November | 720.00000 | 21.57489 | 42.76056 | -0.2384 | 8.41066 |
December | 744.00000 | 21.48517 | 36.70749 | -0.3525 | 9.91139 |
Annual Sum or Average | 8760.00000 | 21.57854 | 41.84529 | -0.6895 | 21.35229 |
Minimum of Months | 672.00000 | 21.35883 | 36.70749 | -1.3525 | 8.41066 |
Maximum of Months | 744.00000 | 21.72967 | 45.96533 | -0.2384 | 44.25315 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.66112 | 29.29523 | 0.19464 | 6.17694 |
February | 672.00000 | 23.64850 | 27.68351 | 0.17750 | 6.10534 |
March | 744.00000 | 23.76978 | 26.30227 | 0.23178 | 6.36518 |
April | 720.00000 | 23.83219 | 30.14927 | 0.28258 | 6.93321 |
May | 744.00000 | 23.97105 | 32.77172 | -0.4683 | 9.77603 |
June | 720.00000 | 23.99588 | 39.81964 | -0.3231 | 7.30085 |
July | 744.00000 | 23.99582 | 42.42924 | -0.3059 | 7.08830 |
August | 744.00000 | 23.99484 | 42.04905 | -0.3224 | 7.29569 |
September | 720.00000 | 23.98213 | 31.92383 | -0.4360 | 9.16723 |
October | 744.00000 | 23.81958 | 28.59090 | 0.27773 | 6.90916 |
November | 720.00000 | 23.72149 | 30.26280 | 0.23089 | 6.45128 |
December | 744.00000 | 23.52195 | 24.49084 | 0.11093 | 5.98231 |
Annual Sum or Average | 8760.00000 | 23.82703 | 32.17428 | -0.0305 | 7.13405 |
Minimum of Months | 672.00000 | 23.52195 | 24.49084 | -0.4683 | 5.98231 |
Maximum of Months | 744.00000 | 23.99588 | 42.42924 | 0.28258 | 9.77603 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.81169 | 28.33853 | 0.27102 | 6.77170 |
February | 672.00000 | 23.80354 | 26.72892 | 0.25524 | 6.63286 |
March | 744.00000 | 23.88611 | 25.42984 | 0.29869 | 6.98965 |
April | 720.00000 | 23.92888 | 29.27167 | 0.34600 | 7.66395 |
May | 744.00000 | 23.99036 | 32.15672 | -0.4109 | 8.66621 |
June | 720.00000 | 23.99661 | 39.42057 | -0.2836 | 6.80719 |
July | 744.00000 | 23.99651 | 42.03616 | -0.2671 | 6.63120 |
August | 744.00000 | 23.99619 | 41.63622 | -0.2830 | 6.80008 |
September | 720.00000 | 23.99239 | 31.43885 | -0.3908 | 8.35522 |
October | 744.00000 | 23.90049 | 27.81397 | 0.33250 | 7.49273 |
November | 720.00000 | 23.84506 | 29.33204 | 0.29969 | 7.07860 |
December | 744.00000 | 23.70333 | 23.57747 | 0.19564 | 6.30135 |
Annual Sum or Average | 8760.00000 | 23.90469 | 31.46016 | 0.02884 | 7.18386 |
Minimum of Months | 672.00000 | 23.70333 | 23.57747 | -0.4109 | 6.30135 |
Maximum of Months | 744.00000 | 23.99661 | 42.03616 | 0.34600 | 8.66621 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.81211 | 27.24738 | 0.91753 | 25.10111 |
February | 672.00000 | 23.79153 | 25.64938 | 0.89764 | 24.51635 |
March | 744.00000 | 23.85110 | 24.67788 | 0.94490 | 26.01022 |
April | 720.00000 | 23.86693 | 28.59288 | 0.98028 | 27.38232 |
May | 744.00000 | 23.94305 | 31.87220 | 0.52784 | 15.04605 |
June | 720.00000 | 23.98736 | 39.37204 | 0.70443 | 19.33604 |
July | 744.00000 | 23.98835 | 41.90749 | 0.71650 | 19.65410 |
August | 744.00000 | 23.98817 | 41.40461 | 0.70652 | 19.21624 |
September | 720.00000 | 23.97151 | 31.27846 | 0.58138 | 16.16035 |
October | 744.00000 | 23.88807 | 27.15956 | 0.98496 | 27.42863 |
November | 720.00000 | 23.82975 | 28.37682 | 0.94359 | 26.03004 |
December | 744.00000 | 23.76328 | 22.52468 | 0.84132 | 22.60810 |
Annual Sum or Average | 8760.00000 | 23.89065 | 30.86958 | 0.81165 | 22.35813 |
Minimum of Months | 672.00000 | 23.76328 | 22.52468 | 0.52784 | 15.04605 |
Maximum of Months | 744.00000 | 23.98835 | 41.90749 | 0.98496 | 27.42863 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38675 | 25.24479 | -0.4188 | 8.94862 |
February | 672.00000 | 21.32502 | 23.33266 | -0.4544 | 9.62575 |
March | 744.00000 | 21.58214 | 22.39153 | -0.3883 | 8.55962 |
April | 720.00000 | 21.60942 | 26.80308 | -0.3536 | 8.01884 |
May | 744.00000 | 22.65278 | 29.24314 | -1.1231 | 32.04523 |
June | 720.00000 | 23.72297 | 35.61582 | -0.7032 | 15.57498 |
July | 744.00000 | 23.80776 | 37.96873 | -0.6567 | 14.20829 |
August | 744.00000 | 23.71287 | 37.88669 | -0.6931 | 15.30524 |
September | 720.00000 | 23.41606 | 27.37931 | -0.8678 | 21.55536 |
October | 744.00000 | 22.17027 | 24.50532 | -0.2278 | 6.62879 |
November | 720.00000 | 21.59274 | 26.37143 | -0.3598 | 8.06053 |
December | 744.00000 | 21.28441 | 19.40860 | -0.4911 | 10.32987 |
Annual Sum or Average | 8760.00000 | 22.36121 | 28.03977 | -0.5623 | 13.26742 |
Minimum of Months | 672.00000 | 21.28441 | 19.40860 | -1.1231 | 6.62879 |
Maximum of Months | 744.00000 | 23.80776 | 37.96873 | -0.2278 | 32.04523 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51148 | 29.04458 | -0.3801 | 8.31797 |
February | 672.00000 | 21.47330 | 27.14041 | -0.4082 | 8.88701 |
March | 744.00000 | 21.76787 | 26.24469 | -0.3363 | 7.98324 |
April | 720.00000 | 21.58319 | 30.85005 | -0.3532 | 7.96425 |
May | 744.00000 | 22.61063 | 33.39290 | -1.1364 | 32.73051 |
June | 720.00000 | 23.78796 | 39.59408 | -0.6804 | 14.91686 |
July | 744.00000 | 23.88753 | 41.83092 | -0.6294 | 13.42711 |
August | 744.00000 | 23.86213 | 41.71318 | -0.6405 | 13.74808 |
September | 720.00000 | 23.66609 | 31.22506 | -0.7811 | 18.36755 |
October | 744.00000 | 22.44123 | 28.33477 | -0.1560 | 6.36284 |
November | 720.00000 | 21.66837 | 30.26143 | -0.3350 | 7.74798 |
December | 744.00000 | 21.24730 | 23.41433 | -0.4884 | 10.18836 |
Annual Sum or Average | 8760.00000 | 22.46464 | 31.94818 | -0.5279 | 12.58695 |
Minimum of Months | 672.00000 | 21.24730 | 23.41433 | -1.1364 | 6.36284 |
Maximum of Months | 744.00000 | 23.88753 | 41.83092 | -0.1560 | 32.73051 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34691 | 26.24662 | -0.4186 | 9.02211 |
February | 672.00000 | 21.37207 | 24.24091 | -0.4321 | 9.35466 |
March | 744.00000 | 21.67312 | 23.22361 | -0.3521 | 8.34293 |
April | 720.00000 | 21.56775 | 27.81070 | -0.3462 | 8.05490 |
May | 744.00000 | 22.59021 | 30.23722 | -1.0993 | 31.29345 |
June | 720.00000 | 23.72812 | 36.40358 | -0.6366 | 13.84755 |
July | 744.00000 | 23.76338 | 38.93019 | -0.6068 | 13.03127 |
August | 744.00000 | 23.70942 | 38.61615 | -0.6289 | 13.64748 |
September | 720.00000 | 23.37641 | 28.32319 | -0.8243 | 20.47976 |
October | 744.00000 | 22.10893 | 25.52995 | -0.2222 | 6.98961 |
November | 720.00000 | 21.53717 | 27.41003 | -0.3596 | 8.24948 |
December | 744.00000 | 21.21940 | 20.41276 | -0.5033 | 10.63176 |
Annual Sum or Average | 8760.00000 | 22.33823 | 28.97606 | -0.5366 | 12.77424 |
Minimum of Months | 672.00000 | 21.21940 | 20.41276 | -1.0993 | 6.98961 |
Maximum of Months | 744.00000 | 23.76338 | 38.93019 | -0.2222 | 31.29345 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57991 | 24.47078 | -0.3746 | 8.31199 |
February | 672.00000 | 21.46071 | 22.65404 | -0.4209 | 9.12427 |
March | 744.00000 | 21.77066 | 21.66607 | -0.3448 | 7.97377 |
April | 720.00000 | 21.82603 | 25.97399 | -0.3048 | 7.42548 |
May | 744.00000 | 22.89015 | 28.33489 | -1.0474 | 28.75809 |
June | 720.00000 | 23.81806 | 34.82753 | -0.6665 | 14.51250 |
July | 744.00000 | 23.87894 | 37.22622 | -0.6270 | 13.40057 |
August | 744.00000 | 23.81695 | 37.10914 | -0.6538 | 14.19762 |
September | 720.00000 | 23.58505 | 26.57035 | -0.8104 | 19.46472 |
October | 744.00000 | 22.41225 | 23.65484 | -0.1731 | 6.24019 |
November | 720.00000 | 21.81085 | 25.53922 | -0.3107 | 7.45044 |
December | 744.00000 | 21.43370 | 18.75025 | -0.4548 | 9.71511 |
Annual Sum or Average | 8760.00000 | 22.52975 | 27.25814 | -0.5164 | 12.23998 |
Minimum of Months | 672.00000 | 21.43370 | 18.75025 | -1.0474 | 6.24019 |
Maximum of Months | 744.00000 | 23.87894 | 37.22622 | -0.1731 | 28.75809 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.179570E+11 | 62587.42 | 20-JAN-13:20 | 465.44 | 0.570760E+11 | 0.00 | 0.750330E+11 | 1.99 | 3.77 | 23-JAN-16:01 | 0.00 | 0.00 |
February | 0.134453E+11 | 59245.19 | 18-FEB-16:01 | 368.65 | 0.426834E+11 | 0.00 | 0.561287E+11 | 1.75 | 3.80 | 18-FEB-16:01 | 0.00 | 0.00 |
March | 0.219014E+11 | 94156.84 | 13-MAR-15:03 | 454.99 | 0.692516E+11 | 0.00 | 0.911530E+11 | 1.94 | 4.08 | 15-MAR-15:03 | 0.00 | 0.00 |
April | 0.174517E+11 | 75890.37 | 07-APR-15:03 | 460.26 | 0.529270E+11 | 0.00 | 0.703787E+11 | 2.00 | 3.94 | 07-APR-15:03 | 0.00 | 0.00 |
May | 0.568466E+11 | 102344.07 | 31-MAY-15:03 | 717.35 | 0.173799E+12 | 0.00 | 0.230646E+12 | 2.99 | 3.89 | 12-MAY-15:01 | 0.00 | 0.00 |
June | 0.146152E+12 | 171646.09 | 26-JUN-15:03 | 720.00 | 0.456621E+12 | 0.00 | 0.602773E+12 | 3.11 | 3.98 | 18-JUN-08:52 | 0.00 | 0.00 |
July | 0.160317E+12 | 139988.07 | 16-JUL-15:03 | 744.00 | 0.507091E+12 | 0.00 | 0.667408E+12 | 3.14 | 4.33 | 30-JUL-21:52 | 0.00 | 0.00 |
August | 0.148159E+12 | 155939.90 | 16-AUG-15:02 | 744.00 | 0.469750E+12 | 0.00 | 0.617908E+12 | 3.14 | 4.19 | 05-AUG-15:03 | 0.00 | 0.00 |
September | 0.109115E+12 | 128422.65 | 28-SEP-15:03 | 714.36 | 0.346071E+12 | 0.00 | 0.455186E+12 | 3.12 | 4.02 | 15-SEP-15:03 | 0.00 | 0.00 |
October | 0.341778E+11 | 107868.87 | 11-OCT-15:03 | 547.91 | 0.109018E+12 | 0.00 | 0.143196E+12 | 2.34 | 3.99 | 20-OCT-15:01 | 0.00 | 0.00 |
November | 0.200118E+11 | 73344.63 | 05-NOV-15:01 | 471.18 | 0.637803E+11 | 0.00 | 0.837921E+11 | 2.08 | 3.99 | 07-NOV-16:01 | 0.00 | 0.00 |
December | 0.129219E+11 | 58781.22 | 02-DEC-13:20 | 350.55 | 0.404872E+11 | 0.00 | 0.534091E+11 | 1.49 | 3.66 | 02-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.758456E+12 | 6758.69 | 0.238856E+13 | 0.00 | 0.314701E+13 | 2.43 | 0.00 | 0.00 | ||||
Minimum of Months | 0.129219E+11 | 58781.22 | 350.55 | 0.404872E+11 | 0.00 | 0.534091E+11 | 1.49 | 3.66 | 0.00 | 0.00 | ||
Maximum of Months | 0.160317E+12 | 171646.09 | 744.00 | 0.507091E+12 | 0.00 | 0.667408E+12 | 3.14 | 4.33 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.101747E+12 | 0.00 | 688.65 | 254259.73 | 05-JAN-19:03 | 0.00 | 49.98 | 78.33 | 0.27 | 0.00 | 0.07 | 0.49 | 05-JAN-19:03 |
February | 0.108044E+12 | 0.00 | 629.40 | 214287.84 | 11-FEB-19:01 | 0.00 | 48.34 | 78.50 | 0.31 | 0.00 | 0.09 | 0.41 | 11-FEB-19:01 |
March | 0.872988E+11 | 0.00 | 630.30 | 218321.14 | 19-MAR-08:61 | 0.00 | 44.06 | 72.87 | 0.22 | 0.00 | 0.06 | 0.42 | 19-MAR-08:61 |
April | 0.795262E+11 | 0.00 | 602.90 | 182093.39 | 03-APR-08:61 | 0.00 | 42.73 | 72.19 | 0.20 | 0.00 | 0.06 | 0.35 | 03-APR-08:61 |
May | 0.657938E+11 | 0.00 | 425.91 | 122279.54 | 19-MAY-08:04 | 0.00 | 30.29 | 57.37 | 0.12 | 0.00 | 0.05 | 0.23 | 19-MAY-08:04 |
June | 0.466394E+10 | 0.00 | 61.16 | 101161.44 | 09-JUN-03:10 | 0.00 | 28.36 | 32.85 | 0.01 | 0.00 | 0.00 | 0.19 | 09-JUN-03:10 |
July | 0.443811E+10 | 0.00 | 43.55 | 74569.15 | 02-JUL-05:00 | 0.00 | 33.49 | 36.53 | 0.01 | 0.00 | 0.00 | 0.14 | 02-JUL-05:00 |
August | 0.446107E+10 | 0.00 | 58.32 | 55575.04 | 17-AUG-08:54 | 0.00 | 33.90 | 37.93 | 0.01 | 0.00 | 0.00 | 0.11 | 17-AUG-08:54 |
September | 0.265663E+11 | 0.00 | 197.70 | 120991.12 | 21-SEP-14:10 | 0.00 | 29.22 | 42.73 | 0.05 | 0.00 | 0.02 | 0.23 | 21-SEP-14:10 |
October | 0.746003E+11 | 0.00 | 561.16 | 206744.77 | 30-OCT-08:61 | 0.00 | 40.57 | 68.06 | 0.17 | 0.00 | 0.05 | 0.39 | 30-OCT-08:61 |
November | 0.790826E+11 | 0.00 | 634.06 | 221650.20 | 29-NOV-19:01 | 0.00 | 49.16 | 75.72 | 0.22 | 0.00 | 0.06 | 0.42 | 29-NOV-19:01 |
December | 0.153679E+12 | 0.00 | 698.35 | 280389.06 | 21-DEC-09:03 | 0.00 | 48.82 | 78.91 | 0.39 | 0.00 | 0.11 | 0.53 | 21-DEC-09:03 |
Annual Sum or Average | 0.789900E+12 | 0.00 | 5231.48 | 0.00 | 39.87 | 60.91 | 0.16 | 0.00 | 0.05 | ||||
Minimum of Months | 0.443811E+10 | 0.00 | 43.55 | 55575.04 | 0.00 | 28.36 | 32.85 | 0.01 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.153679E+12 | 0.00 | 698.35 | 280389.06 | 0.00 | 49.98 | 78.91 | 0.39 | 0.00 | 0.11 | 0.53 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.552645E+11 | 0.00 | 485.46 | 0.552645E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-06:20 | 0.00 | 01-JAN-00:10 | 36499.35 | 31-JAN-13:15 | 36499.35 | 31-JAN-06:50 | 0.00 | 04-JAN-10:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.494870E+11 | 0.00 | 450.86 | 0.494870E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-05:15 | 0.00 | 01-FEB-00:05 | 34539.93 | 13-FEB-09:40 | 34539.93 | 13-FEB-07:05 | 0.00 | 05-FEB-11:25 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.571029E+11 | 0.00 | 465.95 | 0.571029E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-05:15 | 0.00 | 01-MAR-00:10 | 40662.05 | 01-MAR-08:55 | 40662.05 | 01-MAR-07:05 | 0.00 | 14-MAR-21:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.538670E+11 | 0.00 | 430.71 | 0.538670E+11 | 0.00 | 0.00 | 1.00 | 01-APR-01:07 | 0.00 | 01-APR-00:20 | 51466.19 | 30-APR-23:05 | 51466.19 | 30-APR-23:05 | 0.00 | 08-APR-08:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.550836E+11 | 0.00 | 410.52 | 0.550836E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-04:07 | 0.00 | 01-MAY-00:05 | 51440.52 | 01-MAY-04:07 | 51440.52 | 01-MAY-20:50 | 0.00 | 03-MAY-06:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.519701E+11 | 0.00 | 370.05 | 0.519701E+11 | -0.0 | 0.00 | 1.00 | 01-JUN-05:05 | 0.00 | 01-JUN-00:05 | 59922.39 | 01-JUN-06:52 | 59922.39 | 01-JUN-07:02 | 0.00 | 02-JUN-05:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.510809E+11 | 0.00 | 379.18 | 0.510809E+11 | -0.0 | 0.00 | 1.00 | 01-JUL-05:16 | 0.00 | 01-JUL-00:10 | 59935.94 | 01-JUL-05:37 | 59935.94 | 01-JUL-05:55 | 0.00 | 06-JUL-08:15 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.499677E+11 | 0.00 | 379.33 | 0.499677E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-05:05 | 0.00 | 01-AUG-00:05 | 58661.28 | 31-AUG-06:15 | 58661.28 | 31-AUG-04:07 | 0.00 | 20-AUG-18:15 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.483531E+11 | 0.00 | 371.93 | 0.483531E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-04:07 | 0.00 | 01-SEP-00:05 | 54313.31 | 30-SEP-05:08 | 54313.31 | 30-SEP-06:50 | 0.00 | 17-SEP-09:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.490022E+11 | 0.00 | 422.06 | 0.490022E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-05:05 | 0.00 | 01-OCT-00:20 | 42506.53 | 31-OCT-17:13 | 42506.53 | 31-OCT-17:05 | 0.00 | 03-OCT-17:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.491509E+11 | 0.00 | 434.43 | 0.491509E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-04:07 | 0.00 | 01-NOV-00:05 | 38642.11 | 30-NOV-07:30 | 38642.11 | 30-NOV-08:25 | 0.00 | 02-NOV-09:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.506870E+11 | 0.00 | 495.34 | 0.506870E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-05:15 | 0.00 | 01-DEC-00:05 | 32524.19 | 31-DEC-02:10 | 32524.19 | 31-DEC-06:20 | 0.00 | 03-DEC-13:40 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.621017E+12 | 0.00 | 5095.81 | 0.621017E+12 | -0.0 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.483531E+11 | 0.00 | 370.05 | 0.483531E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 32524.19 | 32524.19 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.571029E+11 | 0.00 | 495.34 | 0.571029E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 59935.94 | 59935.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.367945E+11 | 0.00 | 381.33 | 0.367945E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 46180.85 | 31-JAN-17:40 | 46180.85 | 31-JAN-22:40 | 0.00 | 22-JAN-23:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.315378E+11 | 0.00 | 345.93 | 0.315378E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:10 | 43699.76 | 13-FEB-17:10 | 43699.76 | 13-FEB-17:10 | 0.00 | 25-FEB-17:40 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.409868E+11 | 0.00 | 382.44 | 0.409868E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:20 | 51451.80 | 01-MAR-17:10 | 51451.80 | 01-MAR-17:20 | 0.00 | 19-MAR-16:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.417712E+11 | 0.00 | 372.89 | 0.417712E+11 | -0.0 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:20 | 54394.27 | 01-APR-16:05 | 54394.27 | 01-APR-22:30 | 0.00 | 03-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.515300E+11 | 0.00 | 359.93 | 0.515300E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 65099.89 | 01-MAY-16:10 | 65099.89 | 01-MAY-21:50 | 0.00 | 02-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.580431E+11 | 0.00 | 336.99 | 0.580431E+11 | -0.0 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 75839.93 | 01-JUN-20:30 | 75839.93 | 01-JUN-16:10 | 0.00 | 19-JUN-18:01 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.601298E+11 | 0.00 | 349.87 | 0.601298E+11 | -0.0 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 75857.10 | 01-JUL-16:40 | 75857.10 | 01-JUL-19:41 | 0.00 | 01-JUL-19:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.590752E+11 | 0.00 | 348.10 | 0.590752E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 74243.08 | 31-AUG-18:02 | 74243.08 | 31-AUG-18:00 | 0.00 | 02-AUG-16:50 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.527665E+11 | 0.00 | 341.52 | 0.527665E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 68737.51 | 30-SEP-16:10 | 68737.51 | 30-SEP-17:50 | 0.00 | 02-SEP-16:50 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.426211E+11 | 0.00 | 380.75 | 0.426211E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 53787.35 | 31-OCT-17:13 | 53787.35 | 31-OCT-17:40 | 0.00 | 04-OCT-17:25 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.374922E+11 | 0.00 | 369.09 | 0.374922E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 48894.08 | 30-NOV-17:30 | 48894.08 | 30-NOV-19:01 | 0.00 | 08-NOV-20:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.327076E+11 | 0.00 | 382.03 | 0.327076E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 41147.35 | 31-DEC-17:10 | 41147.35 | 31-DEC-17:20 | 0.00 | 05-DEC-17:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.545456E+12 | 0.00 | 4350.88 | 0.545456E+12 | -0.0 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.315378E+11 | 0.00 | 336.99 | 0.315378E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 41147.35 | 41147.35 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.601298E+11 | 0.00 | 382.44 | 0.601298E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 75857.10 | 75857.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.524877E+10 | 0.00 | 31.83 | 0.524877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122125.75 | 20-JAN-13:00 | 122125.75 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.292967E+10 | 0.00 | 19.17 | 0.292967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111316.39 | 18-FEB-13:00 | 111316.39 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.179758E+11 | 0.00 | 95.50 | 0.179758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150135.01 | 14-MAR-13:00 | 150135.01 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.187099E+11 | 0.00 | 104.33 | 0.187099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105930.83 | 19-APR-10:50 | 105930.83 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 |
May | 0.872258E+11 | 0.00 | 308.56 | 0.872258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198801.08 | 31-MAY-18:04 | 198801.08 | 31-MAY-18:04 | 0.00 | 0.00 | 0.00 |
June | 0.284455E+12 | 0.00 | 659.83 | 0.281651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277260.42 | 26-JUN-18:03 | 277260.42 | 26-JUN-18:03 | 0.00 | 0.00 | 0.00 |
July | 0.325480E+12 | 0.00 | 704.00 | 0.310129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264758.22 | 30-JUL-10:33 | 252018.19 | 17-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.290742E+12 | 0.00 | 689.00 | 0.285411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263634.77 | 16-AUG-18:03 | 263634.77 | 16-AUG-18:03 | 0.00 | 0.00 | 0.00 |
September | 0.201647E+12 | 0.00 | 523.92 | 0.201647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231640.91 | 12-SEP-18:20 | 231640.91 | 12-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.332039E+11 | 0.00 | 145.83 | 0.332039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174884.76 | 11-OCT-15:10 | 174884.76 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.106256E+11 | 0.00 | 51.00 | 0.106256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134883.75 | 06-NOV-13:00 | 134883.75 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.710187E+10 | 0.00 | 38.00 | 0.710187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115794.83 | 02-DEC-13:00 | 115794.83 | 02-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128535E+13 | 0.00 | 3370.97 | 0.126186E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.292967E+10 | 0.00 | 19.17 | 0.292967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105930.83 | 105930.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.325480E+12 | 0.00 | 704.00 | 0.310129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277260.42 | 277260.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.192282E+09 | 0.00 | 14.67 | 0.192282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11112.34 | 20-JAN-14:00 | 11112.34 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.70 | 18-FEB-14:00 | 9344.70 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.893177E+09 | 0.00 | 49.33 | 0.893177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13509.75 | 13-MAR-15:01 | 13509.75 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.105845E+10 | 0.00 | 59.33 | 0.105845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12344.04 | 20-APR-13:00 | 12344.04 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.511985E+10 | 0.00 | 201.17 | 0.511985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15683.30 | 17-MAY-13:00 | 15683.30 | 17-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.171378E+11 | 0.00 | 514.67 | 0.166872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20243.38 | 18-JUN-08:54 | 18834.60 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.208898E+11 | 0.00 | 551.83 | 0.190245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26068.81 | 30-JUL-15:27 | 18130.15 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.181610E+11 | 0.00 | 538.50 | 0.171216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21107.72 | 05-AUG-15:08 | 17902.50 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.117068E+11 | 0.00 | 387.83 | 0.117068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16830.63 | 10-SEP-13:00 | 16830.63 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.173134E+10 | 0.00 | 82.00 | 0.173134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14668.04 | 11-OCT-15:01 | 14668.04 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.497142E+09 | 0.00 | 28.33 | 0.497142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12328.01 | 06-NOV-13:50 | 12328.01 | 06-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.275114E+09 | 0.00 | 17.83 | 0.275114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11662.93 | 01-DEC-14:00 | 11662.93 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.777862E+11 | 0.00 | 2454.83 | 0.744310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123483E+09 | 0.00 | 9.33 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9344.70 | 9344.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.208898E+11 | 0.00 | 551.83 | 0.190245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26068.81 | 18834.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132532E+10 | 0.00 | 216.65 | 0.109856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18135.30 | 23-JAN-16:01 | 18135.30 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.139609E+10 | 0.00 | 197.08 | 0.124479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18028.95 | 18-FEB-16:01 | 18028.95 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.266399E+10 | 0.00 | 300.16 | 0.263282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18847.95 | 13-MAR-15:01 | 18847.95 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.179336E+10 | 0.00 | 263.93 | 0.162002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18530.39 | 07-APR-15:01 | 18530.39 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.439414E+10 | 0.00 | 590.14 | 0.318514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19216.84 | 10-MAY-15:01 | 19216.84 | 10-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.977833E+10 | 0.00 | 687.28 | 0.665523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19500.04 | 07-JUN-15:01 | 19500.04 | 07-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.952804E+10 | 0.00 | 711.52 | 0.598235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19495.21 | 01-JUL-18:01 | 19495.21 | 01-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.971260E+10 | 0.00 | 709.84 | 0.642349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19503.64 | 18-AUG-15:01 | 19503.64 | 18-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.765305E+10 | 0.00 | 655.81 | 0.602379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19489.44 | 26-SEP-15:01 | 19489.44 | 26-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.370220E+10 | 0.00 | 420.75 | 0.337751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19352.93 | 11-OCT-15:01 | 19352.93 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.178901E+10 | 0.00 | 271.80 | 0.140264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18512.05 | 05-NOV-15:01 | 18512.05 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.807624E+09 | 0.00 | 144.37 | 0.789101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17990.78 | 02-DEC-16:01 | 17990.78 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545438E+11 | 0.00 | 5169.32 | 0.404354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.807624E+09 | 0.00 | 144.37 | 0.789101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17990.78 | 17990.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.977833E+10 | 0.00 | 711.52 | 0.665523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19503.64 | 19503.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.213146E+09 | 0.00 | 51.25 | 0.184373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17666.20 | 23-JAN-16:01 | 17666.20 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.315885E+09 | 0.00 | 63.14 | 0.288852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17560.42 | 18-FEB-16:01 | 17560.42 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.103043E+10 | 0.00 | 178.46 | 0.101651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19533.13 | 15-MAR-18:31 | 19533.13 | 15-MAR-18:31 | 0.00 | 0.00 | 0.00 |
April | 0.860514E+09 | 0.00 | 173.39 | 0.747009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19794.28 | 08-APR-18:01 | 19794.28 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.303897E+10 | 0.00 | 464.34 | 0.198078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19616.34 | 27-MAY-16:11 | 19616.34 | 27-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.837136E+10 | 0.00 | 543.08 | 0.587820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20287.38 | 27-JUN-08:51 | 20287.38 | 27-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.780856E+10 | 0.00 | 545.00 | 0.502993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21405.94 | 01-JUL-08:61 | 21405.94 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.731677E+10 | 0.00 | 543.76 | 0.480662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20494.24 | 05-AUG-08:51 | 20079.70 | 18-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.473816E+10 | 0.00 | 478.14 | 0.347597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19582.95 | 11-SEP-08:51 | 19582.95 | 11-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.138938E+10 | 0.00 | 246.54 | 0.123228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19028.70 | 14-OCT-16:11 | 19028.70 | 14-OCT-16:11 | 0.00 | 0.00 | 0.00 |
November | 0.347636E+09 | 0.00 | 83.55 | 0.290121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18033.31 | 05-NOV-15:01 | 18033.31 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 89981088.23 | 0.00 | 28.84 | 88231980.61 | 0.00 | 0.00 | 0.00 | 0.00 | 17525.30 | 02-DEC-16:01 | 17525.30 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355208E+11 | 0.00 | 3399.48 | 0.250189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 89981088.23 | 0.00 | 28.84 | 88231980.61 | 0.00 | 0.00 | 0.00 | 0.00 | 17525.30 | 17525.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.837136E+10 | 0.00 | 545.00 | 0.587820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21405.94 | 21405.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.340511E+11 | 0.00 | 420.51 | 0.340511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69262.27 | 20-JAN-12:40 | 69262.27 | 20-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.239549E+11 | 0.00 | 304.78 | 0.239549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66293.56 | 18-FEB-13:00 | 66293.56 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.241002E+11 | 0.00 | 331.61 | 0.241002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60028.14 | 11-MAR-13:00 | 60028.14 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.885509E+10 | 0.00 | 200.82 | 0.856980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37061.14 | 08-APR-13:00 | 37061.14 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.215258E+11 | 0.00 | 537.45 | 0.155049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29045.21 | 05-MAY-13:10 | 29045.21 | 05-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.416812E+11 | 0.00 | 713.96 | 0.215976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34855.24 | 14-JUN-13:30 | 30367.82 | 14-JUN-16:30 | 0.00 | 0.00 | 0.00 |
July | 0.455196E+11 | 0.00 | 742.83 | 0.231954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38544.79 | 23-JUL-12:50 | 30272.11 | 15-JUL-15:03 | 0.00 | 0.00 | 0.00 |
August | 0.520098E+11 | 0.00 | 742.92 | 0.329870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48364.57 | 31-AUG-12:40 | 47813.96 | 31-AUG-12:40 | 0.00 | 0.00 | 0.00 |
September | 0.522749E+11 | 0.00 | 692.46 | 0.432437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61664.90 | 28-SEP-13:00 | 61664.90 | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.383849E+11 | 0.00 | 465.16 | 0.373379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65003.14 | 10-OCT-12:30 | 62967.24 | 11-OCT-12:50 | 0.00 | 0.00 | 0.00 |
November | 0.320176E+11 | 0.00 | 396.31 | 0.320176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68853.58 | 07-NOV-12:20 | 68853.58 | 07-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 0.207072E+11 | 0.00 | 267.04 | 0.207072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62435.68 | 17-DEC-13:30 | 62435.68 | 17-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395082E+12 | 0.00 | 5815.85 | 0.317267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.885509E+10 | 0.00 | 200.82 | 0.856980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29045.21 | 29045.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.522749E+11 | 0.00 | 742.92 | 0.432437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69262.27 | 69262.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.137844E+10 | 0.00 | 90.32 | 0.120292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79969.52 | 21-JAN-09:01 | 79969.52 | 21-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.132256E+10 | 0.00 | 85.09 | 0.117135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80663.54 | 18-FEB-16:01 | 80663.54 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.618218E+10 | 0.00 | 218.12 | 0.596902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90193.12 | 14-MAR-15:01 | 90193.12 | 14-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.902718E+10 | 0.00 | 301.10 | 0.731802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88874.13 | 20-APR-15:01 | 88874.13 | 20-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.284454E+11 | 0.00 | 461.57 | 0.233171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94419.21 | 17-MAY-15:01 | 94419.21 | 17-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.520100E+11 | 0.00 | 511.13 | 0.415015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100570.87 | 30-JUN-07:41 | 100570.87 | 30-JUN-07:41 | 0.00 | 0.00 | 0.00 |
July | 0.534331E+11 | 0.00 | 519.14 | 0.409239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102046.47 | 01-JUL-08:61 | 102046.47 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.465686E+11 | 0.00 | 499.68 | 0.342803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96071.19 | 05-AUG-08:51 | 94636.85 | 18-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.314171E+11 | 0.00 | 438.36 | 0.269023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95228.04 | 09-SEP-08:51 | 95228.04 | 09-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.955957E+10 | 0.00 | 322.74 | 0.863193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93604.61 | 11-OCT-15:01 | 93604.61 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.270285E+10 | 0.00 | 146.36 | 0.229474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83520.31 | 06-NOV-16:01 | 83520.31 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.951667E+09 | 0.00 | 66.14 | 0.951667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78898.25 | 02-DEC-16:01 | 78898.25 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242999E+12 | 0.00 | 3659.76 | 0.194465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.951667E+09 | 0.00 | 66.14 | 0.951667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78898.25 | 78898.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.534331E+11 | 0.00 | 519.14 | 0.415015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102046.47 | 102046.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.128690E+10 | 0.00 | 208.88 | 0.110484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15841.88 | 23-JAN-16:01 | 15841.88 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.155289E+10 | 0.00 | 215.93 | 0.135426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15748.02 | 18-FEB-16:01 | 15748.02 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.284058E+10 | 0.00 | 326.43 | 0.276609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16465.55 | 13-MAR-15:01 | 16465.55 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.214905E+10 | 0.00 | 295.38 | 0.188459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16188.13 | 07-APR-15:01 | 16188.13 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.481674E+10 | 0.00 | 627.14 | 0.355845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16773.97 | 04-MAY-15:01 | 16773.97 | 04-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.103990E+11 | 0.00 | 707.45 | 0.738049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17030.43 | 07-JUN-15:01 | 17030.43 | 07-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.106624E+11 | 0.00 | 728.64 | 0.732551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17026.78 | 01-JUL-18:01 | 17026.78 | 01-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.107572E+11 | 0.00 | 728.64 | 0.758676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17034.06 | 18-AUG-15:01 | 17034.06 | 18-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.808545E+10 | 0.00 | 672.79 | 0.654617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17021.79 | 26-SEP-15:01 | 17021.79 | 26-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.356116E+10 | 0.00 | 414.38 | 0.315403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16902.53 | 11-OCT-15:01 | 16902.53 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.173150E+10 | 0.00 | 260.94 | 0.136809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16171.77 | 05-NOV-15:01 | 16171.77 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.818863E+09 | 0.00 | 145.26 | 0.800028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.62 | 02-DEC-16:01 | 15714.62 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586618E+11 | 0.00 | 5331.87 | 0.448293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.818863E+09 | 0.00 | 145.26 | 0.800028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.62 | 15714.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107572E+11 | 0.00 | 728.64 | 0.758676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17034.06 | 17034.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.221783E+09 | 0.00 | 45.95 | 0.166848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15055.14 | 24-JAN-09:01 | 15055.14 | 24-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.431738E+09 | 0.00 | 73.01 | 0.357905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15372.71 | 18-FEB-16:01 | 15372.71 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.126064E+10 | 0.00 | 205.54 | 0.121316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16084.27 | 13-MAR-15:01 | 16084.27 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.128807E+10 | 0.00 | 216.55 | 0.109200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17882.34 | 19-APR-08:51 | 17882.34 | 19-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.358593E+10 | 0.00 | 506.99 | 0.250271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18221.65 | 10-MAY-08:51 | 18221.65 | 10-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.866718E+10 | 0.00 | 560.11 | 0.613852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20801.54 | 27-JUN-08:32 | 20801.54 | 27-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.869000E+10 | 0.00 | 559.99 | 0.599707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20897.54 | 01-JUL-07:42 | 20897.54 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.811224E+10 | 0.00 | 564.88 | 0.552269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20393.75 | 05-AUG-08:32 | 18260.75 | 02-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.519598E+10 | 0.00 | 507.62 | 0.395064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18604.22 | 07-SEP-08:51 | 18604.22 | 07-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.138905E+10 | 0.00 | 253.99 | 0.117070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17837.17 | 11-OCT-08:51 | 17837.17 | 11-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.394909E+09 | 0.00 | 76.24 | 0.297095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15721.69 | 07-NOV-16:01 | 15721.69 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.123287E+09 | 0.00 | 27.32 | 0.114237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15017.04 | 03-DEC-09:01 | 15017.04 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393608E+11 | 0.00 | 3598.19 | 0.285236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123287E+09 | 0.00 | 27.32 | 0.114237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15017.04 | 15017.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.869000E+10 | 0.00 | 564.88 | 0.613852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20897.54 | 20897.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.298197E+09 | 0.00 | 159.20 | 0.251142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.71 | 23-JAN-16:01 | 4844.71 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.325169E+09 | 0.00 | 152.74 | 0.291577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4816.28 | 18-FEB-16:01 | 4816.28 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.645529E+09 | 0.00 | 250.17 | 0.638957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5034.98 | 13-MAR-15:01 | 5034.98 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.455590E+09 | 0.00 | 223.87 | 0.412903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4950.25 | 07-APR-15:01 | 4950.25 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.106317E+10 | 0.00 | 512.96 | 0.788407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5133.63 | 10-MAY-15:01 | 5133.63 | 10-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.248225E+10 | 0.00 | 685.00 | 0.169780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5208.58 | 07-JUN-15:01 | 5208.58 | 07-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.237291E+10 | 0.00 | 708.20 | 0.148481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5207.70 | 01-JUL-18:01 | 5207.70 | 01-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.242167E+10 | 0.00 | 703.51 | 0.160549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5209.89 | 18-AUG-15:01 | 5209.89 | 18-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.181711E+10 | 0.00 | 633.31 | 0.141453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5206.23 | 26-SEP-15:01 | 5206.23 | 26-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.845292E+09 | 0.00 | 333.48 | 0.764742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5169.93 | 11-OCT-15:01 | 5169.93 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.412700E+09 | 0.00 | 207.72 | 0.328164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4945.28 | 05-NOV-15:01 | 4945.28 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.180676E+09 | 0.00 | 115.00 | 0.176470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.71 | 02-DEC-16:01 | 4805.71 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133203E+11 | 0.00 | 4685.16 | 0.985499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.180676E+09 | 0.00 | 115.00 | 0.176470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.71 | 4805.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.248225E+10 | 0.00 | 708.20 | 0.169780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5209.89 | 5209.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 42055091.56 | 0.00 | 30.83 | 36738673.69 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.25 | 23-JAN-16:01 | 4708.25 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 67845853.11 | 0.00 | 43.74 | 60500362.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4679.73 | 18-FEB-16:01 | 4679.73 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.235782E+09 | 0.00 | 141.61 | 0.232892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5323.15 | 08-MAR-17:11 | 5323.15 | 08-MAR-17:11 | 0.00 | 0.00 | 0.00 |
April | 0.213442E+09 | 0.00 | 145.71 | 0.187907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5354.24 | 08-APR-18:01 | 5354.24 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.724679E+09 | 0.00 | 412.18 | 0.482287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5322.47 | 25-MAY-17:11 | 5322.47 | 25-MAY-17:11 | 0.00 | 0.00 | 0.00 |
June | 0.217855E+10 | 0.00 | 543.89 | 0.153608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5442.35 | 27-JUN-08:51 | 5442.35 | 27-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.199808E+10 | 0.00 | 545.62 | 0.128056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5665.00 | 01-JUL-08:61 | 5665.00 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.186664E+10 | 0.00 | 542.10 | 0.123533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5508.07 | 05-AUG-08:51 | 5362.27 | 13-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.111790E+10 | 0.00 | 463.01 | 0.805269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5210.35 | 09-SEP-08:51 | 5210.35 | 09-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.282819E+09 | 0.00 | 175.45 | 0.251208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5224.13 | 08-OCT-18:11 | 5224.13 | 08-OCT-18:11 | 0.00 | 0.00 | 0.00 |
November | 74017479.01 | 0.00 | 57.91 | 62359334.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.76 | 05-NOV-15:01 | 4805.76 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 18790485.35 | 0.00 | 17.78 | 18336407.93 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.38 | 02-DEC-16:01 | 4670.38 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882060E+10 | 0.00 | 3119.83 | 0.618946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 18790485.35 | 0.00 | 17.78 | 18336407.93 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.38 | 4670.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.217855E+10 | 0.00 | 545.62 | 0.153608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5665.00 | 5665.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.741705E+10 | 0.00 | 408.61 | 0.674993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20821.43 | 23-JAN-16:01 | 20821.43 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.598237E+10 | 0.00 | 336.70 | 0.550618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20696.33 | 18-FEB-16:01 | 20696.33 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.613433E+10 | 0.00 | 388.54 | 0.602727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21635.78 | 13-MAR-15:01 | 21635.78 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.317148E+10 | 0.00 | 310.22 | 0.284639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21268.65 | 07-APR-15:01 | 21268.65 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.550310E+10 | 0.00 | 577.31 | 0.404635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21618.98 | 10-MAY-18:01 | 21618.98 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.109597E+11 | 0.00 | 679.99 | 0.714343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22371.98 | 14-JUN-08:61 | 22371.98 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.118832E+11 | 0.00 | 705.45 | 0.759786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22203.25 | 01-JUL-08:61 | 22203.25 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.132206E+11 | 0.00 | 706.80 | 0.920070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22223.38 | 18-AUG-08:61 | 22223.38 | 18-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.120301E+11 | 0.00 | 661.46 | 0.100830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22369.17 | 26-SEP-15:01 | 22369.17 | 26-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.858827E+10 | 0.00 | 481.20 | 0.803084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22210.27 | 11-OCT-15:01 | 22210.27 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.771745E+10 | 0.00 | 433.60 | 0.669640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21249.90 | 05-NOV-15:01 | 21249.90 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.534551E+10 | 0.00 | 313.81 | 0.528505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20651.96 | 02-DEC-16:01 | 20651.96 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979532E+11 | 0.00 | 6003.68 | 0.792134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.317148E+10 | 0.00 | 310.22 | 0.284639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20651.96 | 20651.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132206E+11 | 0.00 | 706.80 | 0.100830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22371.98 | 22371.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1327.33 | 1092.65 | 234.67 | 1522.89 | 605.31 | 0.00 | 0.00 | 0.00 |
February | 1255.98 | 998.64 | 257.34 | 1428.56 | 633.33 | 0.00 | 0.00 | 0.00 |
March | 943.45 | 623.53 | 319.92 | 1085.55 | 501.81 | 0.00 | 0.00 | 0.00 |
April | 617.77 | 255.57 | 362.20 | 653.96 | 447.22 | 0.00 | 0.00 | 0.00 |
May | 561.37 | 107.95 | 453.41 | 661.15 | 257.93 | 0.00 | 0.00 | 0.00 |
June | 510.38 | 92.13 | 418.25 | 744.56 | 139.26 | 0.00 | 0.00 | 0.00 |
July | 527.16 | 89.81 | 437.35 | 772.31 | 124.18 | 0.00 | 0.00 | 0.00 |
August | 670.74 | 275.95 | 394.79 | 980.77 | 145.72 | 0.00 | 0.00 | 0.00 |
September | 881.07 | 495.25 | 385.82 | 1202.78 | 229.85 | 0.00 | 0.00 | 0.00 |
October | 1040.04 | 736.90 | 303.14 | 1264.79 | 488.71 | 0.00 | 0.00 | 0.00 |
November | 1274.79 | 1016.81 | 257.98 | 1500.78 | 567.32 | 0.00 | 0.00 | 0.00 |
December | 1216.57 | 984.85 | 231.72 | 1366.09 | 688.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 900.20 | 561.69 | 338.52 | 1096.77 | 401.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.38 | 89.81 | 231.72 | 653.96 | 124.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1327.33 | 1092.65 | 453.41 | 1522.89 | 688.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3737.67 | 3076.84 | 660.83 | 4250.27 | 1798.23 | 0.00 | 0.00 | 0.00 |
February | 3536.75 | 2812.11 | 724.64 | 3986.11 | 1868.15 | 0.00 | 0.00 | 0.00 |
March | 2656.69 | 1755.81 | 900.88 | 3023.79 | 1492.05 | 0.00 | 0.00 | 0.00 |
April | 1739.60 | 719.67 | 1019.93 | 1807.17 | 1350.64 | 0.00 | 0.00 | 0.00 |
May | 1580.77 | 303.98 | 1276.78 | 1811.54 | 801.62 | 0.00 | 0.00 | 0.00 |
June | 1437.19 | 259.44 | 1177.75 | 2070.74 | 414.72 | 0.00 | 0.00 | 0.00 |
July | 1484.44 | 252.89 | 1231.56 | 2148.94 | 372.62 | 0.00 | 0.00 | 0.00 |
August | 1888.76 | 777.06 | 1111.70 | 2735.90 | 434.88 | 0.00 | 0.00 | 0.00 |
September | 2481.05 | 1394.59 | 1086.46 | 3360.65 | 681.97 | 0.00 | 0.00 | 0.00 |
October | 2928.68 | 2075.07 | 853.61 | 3533.52 | 1450.23 | 0.00 | 0.00 | 0.00 |
November | 3589.72 | 2863.26 | 726.46 | 4191.86 | 1685.20 | 0.00 | 0.00 | 0.00 |
December | 3425.79 | 2773.28 | 652.52 | 3811.30 | 2029.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2534.91 | 1581.67 | 953.24 | 3055.61 | 1194.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1437.19 | 252.89 | 652.52 | 1807.17 | 372.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3737.67 | 3076.84 | 1276.78 | 4250.27 | 2029.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4855.45 | 3996.99 | 858.45 | 5600.61 | 2403.97 | 0.00 | 0.00 | 0.00 |
February | 4594.44 | 3653.09 | 941.35 | 5260.70 | 2506.52 | 0.00 | 0.00 | 0.00 |
March | 3451.19 | 2280.90 | 1170.29 | 3993.18 | 2021.15 | 0.00 | 0.00 | 0.00 |
April | 2259.84 | 934.90 | 1324.95 | 2385.58 | 1852.32 | 0.00 | 0.00 | 0.00 |
May | 2053.51 | 394.89 | 1658.62 | 2394.68 | 1081.36 | 0.00 | 0.00 | 0.00 |
June | 1866.99 | 337.03 | 1529.97 | 2753.78 | 547.98 | 0.00 | 0.00 | 0.00 |
July | 1928.38 | 328.51 | 1599.86 | 2856.03 | 491.59 | 0.00 | 0.00 | 0.00 |
August | 2453.61 | 1009.44 | 1444.17 | 3628.70 | 568.86 | 0.00 | 0.00 | 0.00 |
September | 3223.02 | 1811.65 | 1411.37 | 4445.53 | 895.50 | 0.00 | 0.00 | 0.00 |
October | 3804.52 | 2695.63 | 1108.89 | 4659.74 | 1950.43 | 0.00 | 0.00 | 0.00 |
November | 4663.25 | 3719.54 | 943.71 | 5525.83 | 2259.26 | 0.00 | 0.00 | 0.00 |
December | 4450.30 | 3602.64 | 847.66 | 5021.13 | 2727.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3292.99 | 2054.68 | 1238.31 | 4036.70 | 1603.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1866.99 | 328.51 | 847.66 | 2385.58 | 491.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4855.45 | 3996.99 | 1658.62 | 5600.61 | 2727.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 305.77 | 118.14 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 285.75 | 125.31 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 217.06 | 98.73 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 130.26 | 89.18 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 131.80 | 49.83 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 152.68 | 22.16 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.90 | 18.86 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 199.61 | 22.51 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 243.07 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 253.71 | 94.16 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 301.12 | 110.54 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 273.10 | 136.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 220.69 | 76.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 130.26 | 18.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 305.77 | 136.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 159.88 | 243.17 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 190.75 | 249.83 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 240.43 | 187.05 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 218.80 | 162.73 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 323.54 | 90.51 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 473.92 | 41.13 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 390.96 | 35.07 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 399.07 | 41.46 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 337.57 | 73.60 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 233.75 | 180.69 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 171.09 | 218.73 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 120.59 | 277.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 272.05 | 149.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 120.59 | 35.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 473.92 | 277.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.97 | 134.40 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 7.14 | 138.80 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 22.08 | 103.92 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 33.66 | 88.34 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 76.49 | 47.30 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 123.34 | 22.15 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 119.26 | 19.49 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 90.52 | 23.56 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.96 | 41.62 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 23.65 | 97.91 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 9.43 | 119.77 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.94 | 154.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 48.85 | 82.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.94 | 19.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 123.34 | 154.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 166.51 | 237.37 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 197.64 | 244.97 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 244.53 | 185.31 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 220.67 | 162.31 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 322.06 | 92.47 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 470.93 | 44.36 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 387.50 | 38.10 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 397.72 | 44.71 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 338.25 | 76.73 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 237.55 | 178.98 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 177.57 | 214.07 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 126.23 | 272.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 274.25 | 148.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 126.23 | 38.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 470.93 | 272.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.91 | 172.79 | 37.11 | 233.13 | 118.28 | 0.00 | 0.00 | 0.00 |
February | 198.62 | 157.93 | 40.70 | 218.83 | 118.86 | 0.00 | 0.00 | 0.00 |
March | 149.20 | 98.61 | 50.59 | 165.43 | 96.19 | 0.00 | 0.00 | 0.00 |
April | 97.70 | 40.42 | 57.28 | 96.46 | 91.96 | 0.00 | 0.00 | 0.00 |
May | 88.78 | 17.07 | 71.70 | 93.61 | 57.77 | 0.00 | 0.00 | 0.00 |
June | 80.71 | 14.57 | 66.14 | 109.36 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 14.20 | 69.16 | 113.79 | 29.54 | 0.00 | 0.00 | 0.00 |
August | 106.07 | 43.64 | 62.43 | 147.42 | 33.66 | 0.00 | 0.00 | 0.00 |
September | 139.34 | 78.32 | 61.02 | 182.81 | 49.35 | 0.00 | 0.00 | 0.00 |
October | 164.47 | 116.54 | 47.94 | 193.84 | 97.35 | 0.00 | 0.00 | 0.00 |
November | 201.60 | 160.80 | 40.80 | 231.17 | 110.93 | 0.00 | 0.00 | 0.00 |
December | 192.39 | 155.75 | 36.65 | 210.00 | 128.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 142.36 | 88.83 | 53.53 | 166.01 | 80.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.71 | 14.20 | 36.65 | 93.61 | 29.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.91 | 172.79 | 71.70 | 233.13 | 128.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.83 | 0.00 | 21.83 | 4.63 | 110.10 | 0.00 | 0.00 | 0.00 |
February | 27.44 | 0.00 | 27.44 | 5.80 | 113.23 | 0.00 | 0.00 | 0.00 |
March | 37.34 | 0.00 | 37.34 | 18.46 | 83.91 | 0.00 | 0.00 | 0.00 |
April | 46.94 | 0.31 | 46.64 | 27.72 | 71.97 | 0.00 | 0.00 | 0.00 |
May | 64.13 | 2.15 | 61.98 | 63.95 | 37.23 | 0.00 | 0.00 | 0.00 |
June | 70.31 | 7.86 | 62.45 | 103.23 | 16.04 | 0.00 | 0.00 | 0.00 |
July | 66.69 | 4.55 | 62.14 | 99.51 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 53.10 | 1.44 | 51.66 | 76.52 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 44.46 | 0.04 | 44.42 | 56.83 | 31.18 | 0.00 | 0.00 | 0.00 |
October | 31.81 | 0.00 | 31.81 | 20.22 | 78.56 | 0.00 | 0.00 | 0.00 |
November | 24.15 | 0.00 | 24.15 | 7.61 | 97.76 | 0.00 | 0.00 | 0.00 |
December | 20.42 | 0.00 | 20.42 | 3.73 | 127.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.46 | 1.37 | 41.10 | 40.88 | 66.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.42 | 0.00 | 20.42 | 3.73 | 14.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.31 | 7.86 | 62.45 | 103.23 | 127.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 140.35 | 239.18 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 199.73 | 248.90 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 260.35 | 183.72 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 263.31 | 159.29 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 359.32 | 85.40 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 520.36 | 37.51 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 478.58 | 33.05 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 476.03 | 40.04 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 374.75 | 69.72 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 220.14 | 177.13 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 150.08 | 217.39 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 115.79 | 276.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 297.03 | 146.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 115.79 | 33.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 520.36 | 276.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 305.21 | 117.63 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 284.75 | 124.74 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 215.59 | 98.24 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 128.74 | 89.03 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 130.55 | 49.63 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.40 | 21.73 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 157.48 | 18.71 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 198.18 | 22.37 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 242.08 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 253.09 | 93.69 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 300.75 | 109.96 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 272.59 | 136.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 219.66 | 76.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 128.74 | 18.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 305.21 | 136.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 5.62 | 133.77 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 6.30 | 138.38 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 20.80 | 103.41 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 32.18 | 88.08 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 75.25 | 46.82 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 120.79 | 21.73 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 116.84 | 19.34 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 87.98 | 23.31 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 65.54 | 40.98 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 22.80 | 96.94 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 8.82 | 118.88 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 4.58 | 153.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 47.52 | 81.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 4.58 | 19.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 120.79 | 153.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.00 | 97.25 | 61.75 | 144.99 | 230.48 | 0.00 | 0.00 | 0.00 |
February | 213.16 | 134.91 | 78.25 | 204.46 | 241.60 | 0.00 | 0.00 | 0.00 |
March | 256.77 | 149.88 | 106.89 | 264.47 | 181.29 | 0.00 | 0.00 | 0.00 |
April | 262.12 | 127.66 | 134.45 | 265.35 | 158.50 | 0.00 | 0.00 | 0.00 |
May | 307.29 | 128.64 | 178.65 | 358.41 | 87.15 | 0.00 | 0.00 | 0.00 |
June | 373.91 | 196.24 | 177.67 | 514.82 | 40.89 | 0.00 | 0.00 | 0.00 |
July | 339.39 | 161.28 | 178.12 | 473.19 | 36.19 | 0.00 | 0.00 | 0.00 |
August | 343.18 | 189.07 | 154.10 | 472.66 | 43.34 | 0.00 | 0.00 | 0.00 |
September | 286.01 | 155.47 | 130.54 | 374.85 | 72.27 | 0.00 | 0.00 | 0.00 |
October | 206.97 | 113.51 | 93.46 | 224.17 | 174.79 | 0.00 | 0.00 | 0.00 |
November | 160.61 | 90.51 | 70.10 | 154.98 | 210.51 | 0.00 | 0.00 | 0.00 |
December | 139.29 | 80.27 | 59.02 | 119.86 | 269.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.13 | 135.32 | 118.81 | 298.12 | 144.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.29 | 80.27 | 59.02 | 119.86 | 36.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.91 | 196.24 | 178.65 | 514.82 | 269.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 6.07 | 183.59 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 7.39 | 187.64 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 26.81 | 139.99 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 42.96 | 118.27 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 98.41 | 64.30 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 155.34 | 32.62 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 149.29 | 30.25 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 112.99 | 36.14 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 83.01 | 60.38 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 28.04 | 135.53 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 10.13 | 163.61 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 5.06 | 209.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 60.76 | 113.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 5.06 | 30.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 155.34 | 209.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.74 | 0.00 | 12.74 | 2.24 | 67.68 | 0.00 | 0.00 | 0.00 |
February | 16.01 | 0.00 | 16.01 | 2.72 | 69.17 | 0.00 | 0.00 | 0.00 |
March | 21.79 | 0.00 | 21.79 | 9.88 | 51.61 | 0.00 | 0.00 | 0.00 |
April | 27.39 | 0.18 | 27.21 | 15.84 | 43.60 | 0.00 | 0.00 | 0.00 |
May | 37.42 | 1.25 | 36.16 | 36.28 | 23.71 | 0.00 | 0.00 | 0.00 |
June | 41.03 | 4.59 | 36.44 | 57.27 | 12.03 | 0.00 | 0.00 | 0.00 |
July | 38.91 | 2.66 | 36.26 | 55.03 | 11.15 | 0.00 | 0.00 | 0.00 |
August | 30.98 | 0.84 | 30.14 | 41.65 | 13.32 | 0.00 | 0.00 | 0.00 |
September | 25.94 | 0.02 | 25.92 | 30.60 | 22.26 | 0.00 | 0.00 | 0.00 |
October | 18.56 | 0.00 | 18.56 | 10.34 | 49.96 | 0.00 | 0.00 | 0.00 |
November | 14.09 | 0.00 | 14.09 | 3.74 | 60.31 | 0.00 | 0.00 | 0.00 |
December | 11.92 | 0.00 | 11.92 | 1.87 | 77.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.78 | 0.80 | 23.98 | 22.40 | 41.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.92 | 0.00 | 11.92 | 1.87 | 11.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.03 | 4.59 | 36.44 | 57.27 | 77.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.45 | 100.80 | 21.65 | 143.45 | 57.32 | 0.00 | 0.00 | 0.00 |
February | 115.87 | 92.13 | 23.74 | 134.17 | 60.89 | 0.00 | 0.00 | 0.00 |
March | 87.04 | 57.52 | 29.51 | 101.85 | 48.68 | 0.00 | 0.00 | 0.00 |
April | 56.99 | 23.58 | 33.41 | 61.33 | 43.86 | 0.00 | 0.00 | 0.00 |
May | 51.79 | 9.96 | 41.83 | 61.88 | 25.60 | 0.00 | 0.00 | 0.00 |
June | 47.08 | 8.50 | 38.59 | 70.39 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 48.63 | 8.28 | 40.35 | 72.82 | 11.92 | 0.00 | 0.00 | 0.00 |
August | 61.88 | 25.46 | 36.42 | 92.23 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 81.28 | 45.69 | 35.59 | 112.82 | 21.90 | 0.00 | 0.00 | 0.00 |
October | 95.95 | 67.98 | 27.97 | 118.59 | 47.59 | 0.00 | 0.00 | 0.00 |
November | 117.60 | 93.80 | 23.80 | 141.32 | 54.00 | 0.00 | 0.00 | 0.00 |
December | 112.23 | 90.86 | 21.38 | 127.91 | 66.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 51.82 | 31.23 | 103.05 | 38.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.08 | 8.28 | 21.38 | 61.33 | 11.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.45 | 100.80 | 41.83 | 143.45 | 66.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 332.36 | 273.60 | 58.76 | 389.36 | 155.57 | 0.00 | 0.00 | 0.00 |
February | 314.49 | 250.06 | 64.44 | 364.17 | 165.26 | 0.00 | 0.00 | 0.00 |
March | 236.24 | 156.13 | 80.11 | 276.45 | 132.11 | 0.00 | 0.00 | 0.00 |
April | 154.69 | 63.99 | 90.69 | 166.47 | 119.04 | 0.00 | 0.00 | 0.00 |
May | 140.56 | 27.03 | 113.53 | 167.97 | 69.48 | 0.00 | 0.00 | 0.00 |
June | 127.80 | 23.07 | 104.73 | 191.05 | 35.87 | 0.00 | 0.00 | 0.00 |
July | 132.00 | 22.49 | 109.51 | 197.66 | 32.35 | 0.00 | 0.00 | 0.00 |
August | 167.95 | 69.10 | 98.86 | 250.33 | 37.48 | 0.00 | 0.00 | 0.00 |
September | 220.62 | 124.01 | 96.61 | 306.22 | 59.45 | 0.00 | 0.00 | 0.00 |
October | 260.42 | 184.52 | 75.90 | 321.89 | 129.16 | 0.00 | 0.00 | 0.00 |
November | 319.20 | 254.60 | 64.60 | 383.57 | 146.57 | 0.00 | 0.00 | 0.00 |
December | 304.63 | 246.60 | 58.02 | 347.18 | 179.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.41 | 140.64 | 84.76 | 279.70 | 104.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.80 | 22.49 | 58.02 | 166.47 | 32.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.36 | 273.60 | 113.53 | 389.36 | 179.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 305.13 | 117.38 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 284.50 | 125.09 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 216.02 | 98.24 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 129.46 | 88.74 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 130.91 | 49.50 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 151.82 | 21.62 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 158.18 | 18.29 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 198.55 | 21.91 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 242.10 | 38.31 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 252.87 | 93.33 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 300.14 | 109.93 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 272.17 | 136.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 219.78 | 76.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 129.46 | 18.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 305.13 | 136.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 159.37 | 240.99 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 189.65 | 248.89 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 239.12 | 185.87 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 217.41 | 161.75 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 321.53 | 89.76 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 471.72 | 40.15 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 389.29 | 34.01 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 397.19 | 40.37 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 336.37 | 72.03 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 232.82 | 178.86 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 170.29 | 217.13 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 120.23 | 276.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 270.77 | 148.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 120.23 | 34.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 471.72 | 276.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 6.25 | 132.81 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 7.26 | 137.96 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 22.12 | 103.38 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 33.38 | 88.00 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 75.68 | 47.30 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 122.67 | 21.97 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 118.79 | 19.25 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 90.04 | 23.27 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 66.97 | 41.07 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 23.86 | 97.08 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 9.62 | 118.58 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 5.17 | 153.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 48.72 | 81.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 5.17 | 19.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 122.67 | 153.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.84 | 107.64 | 62.20 | 166.92 | 234.96 | 0.00 | 0.00 | 0.00 |
February | 205.18 | 127.28 | 77.90 | 197.27 | 243.90 | 0.00 | 0.00 | 0.00 |
March | 239.27 | 131.80 | 107.47 | 243.51 | 184.25 | 0.00 | 0.00 | 0.00 |
April | 225.68 | 95.60 | 130.08 | 219.28 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 275.93 | 97.45 | 178.48 | 319.65 | 92.32 | 0.00 | 0.00 | 0.00 |
June | 336.87 | 161.95 | 174.92 | 468.62 | 43.85 | 0.00 | 0.00 | 0.00 |
July | 274.17 | 100.11 | 174.07 | 385.80 | 37.45 | 0.00 | 0.00 | 0.00 |
August | 287.10 | 141.88 | 145.22 | 395.83 | 44.05 | 0.00 | 0.00 | 0.00 |
September | 255.45 | 122.90 | 132.55 | 337.21 | 75.58 | 0.00 | 0.00 | 0.00 |
October | 213.91 | 122.27 | 91.65 | 237.08 | 177.18 | 0.00 | 0.00 | 0.00 |
November | 175.65 | 106.68 | 68.97 | 177.48 | 212.20 | 0.00 | 0.00 | 0.00 |
December | 141.66 | 83.65 | 58.01 | 126.43 | 271.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.46 | 116.46 | 117.01 | 273.24 | 147.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.66 | 83.65 | 58.01 | 126.43 | 37.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 336.87 | 161.95 | 178.48 | 468.62 | 271.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.89 | 316.84 | 68.05 | 440.16 | 178.56 | 0.00 | 0.00 | 0.00 |
February | 364.20 | 289.58 | 74.62 | 410.87 | 189.20 | 0.00 | 0.00 | 0.00 |
March | 273.57 | 180.80 | 92.77 | 313.13 | 147.27 | 0.00 | 0.00 | 0.00 |
April | 179.14 | 74.11 | 105.03 | 187.89 | 132.29 | 0.00 | 0.00 | 0.00 |
May | 162.78 | 31.30 | 131.48 | 192.85 | 72.18 | 0.00 | 0.00 | 0.00 |
June | 148.00 | 26.72 | 121.28 | 226.49 | 29.99 | 0.00 | 0.00 | 0.00 |
July | 152.86 | 26.04 | 126.82 | 234.81 | 25.65 | 0.00 | 0.00 | 0.00 |
August | 194.50 | 80.02 | 114.48 | 293.01 | 31.05 | 0.00 | 0.00 | 0.00 |
September | 255.49 | 143.61 | 111.88 | 354.63 | 56.04 | 0.00 | 0.00 | 0.00 |
October | 301.58 | 213.68 | 87.90 | 367.74 | 140.44 | 0.00 | 0.00 | 0.00 |
November | 369.65 | 294.84 | 74.81 | 434.03 | 167.18 | 0.00 | 0.00 | 0.00 |
December | 352.77 | 285.58 | 67.19 | 391.31 | 207.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.03 | 162.87 | 98.16 | 320.05 | 114.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.00 | 26.04 | 67.19 | 187.89 | 25.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.89 | 316.84 | 131.48 | 440.16 | 207.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 25.35 | 1094.61 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 30.97 | 1128.90 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 124.14 | 851.67 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 198.66 | 739.63 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 495.05 | 388.52 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 839.55 | 184.80 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 810.55 | 170.68 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 611.73 | 202.00 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 447.14 | 338.98 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 140.93 | 798.55 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 45.31 | 984.04 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 20.20 | 1257.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 317.41 | 675.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 20.20 | 170.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 839.55 | 1257.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.98 | 0.00 | 190.98 | 22.40 | 1119.39 | 0.00 | 0.00 | 0.00 |
February | 240.04 | 0.00 | 240.04 | 27.98 | 1154.83 | 0.00 | 0.00 | 0.00 |
March | 326.71 | 0.02 | 326.69 | 117.38 | 871.03 | 0.00 | 0.00 | 0.00 |
April | 410.70 | 2.69 | 408.01 | 190.39 | 756.96 | 0.00 | 0.00 | 0.00 |
May | 561.03 | 18.82 | 542.22 | 485.67 | 396.45 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 68.79 | 546.32 | 832.20 | 189.47 | 0.00 | 0.00 | 0.00 |
July | 583.42 | 39.82 | 543.59 | 803.45 | 175.49 | 0.00 | 0.00 | 0.00 |
August | 464.51 | 12.57 | 451.94 | 605.21 | 207.55 | 0.00 | 0.00 | 0.00 |
September | 388.93 | 0.31 | 388.62 | 440.95 | 346.50 | 0.00 | 0.00 | 0.00 |
October | 278.26 | 0.00 | 278.26 | 135.27 | 814.57 | 0.00 | 0.00 | 0.00 |
November | 211.23 | 0.00 | 211.23 | 42.04 | 1006.59 | 0.00 | 0.00 | 0.00 |
December | 178.68 | 0.00 | 178.68 | 17.99 | 1286.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.48 | 11.95 | 359.53 | 311.67 | 691.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.68 | 0.00 | 178.68 | 17.99 | 175.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 615.11 | 68.79 | 546.32 | 832.20 | 1286.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.28 | 0.00 | 27.28 | 8.27 | 134.03 | 0.00 | 0.00 | 0.00 |
February | 34.29 | 0.00 | 34.29 | 9.26 | 141.41 | 0.00 | 0.00 | 0.00 |
March | 46.67 | 0.00 | 46.67 | 27.43 | 107.25 | 0.00 | 0.00 | 0.00 |
April | 58.67 | 0.38 | 58.29 | 40.81 | 93.76 | 0.00 | 0.00 | 0.00 |
May | 80.15 | 2.69 | 77.46 | 94.65 | 51.83 | 0.00 | 0.00 | 0.00 |
June | 87.88 | 9.83 | 78.05 | 148.32 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 83.35 | 5.69 | 77.66 | 143.95 | 23.77 | 0.00 | 0.00 | 0.00 |
August | 66.36 | 1.80 | 64.56 | 113.96 | 26.81 | 0.00 | 0.00 | 0.00 |
September | 55.56 | 0.04 | 55.52 | 86.01 | 42.75 | 0.00 | 0.00 | 0.00 |
October | 39.75 | 0.00 | 39.75 | 31.38 | 99.22 | 0.00 | 0.00 | 0.00 |
November | 30.18 | 0.00 | 30.18 | 12.92 | 120.41 | 0.00 | 0.00 | 0.00 |
December | 25.53 | 0.00 | 25.53 | 6.23 | 158.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.07 | 1.71 | 51.36 | 60.56 | 85.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.53 | 0.00 | 25.53 | 6.23 | 23.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.88 | 9.83 | 78.05 | 148.32 | 158.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.98 | 194.49 | 123.49 | 309.21 | 467.92 | 0.00 | 0.00 | 0.00 |
February | 426.28 | 269.79 | 156.49 | 427.44 | 500.34 | 0.00 | 0.00 | 0.00 |
March | 513.51 | 299.74 | 213.77 | 560.60 | 381.22 | 0.00 | 0.00 | 0.00 |
April | 524.20 | 255.31 | 268.89 | 566.46 | 341.68 | 0.00 | 0.00 | 0.00 |
May | 614.54 | 257.27 | 357.27 | 789.52 | 192.68 | 0.00 | 0.00 | 0.00 |
June | 747.77 | 392.46 | 355.32 | 1131.57 | 96.85 | 0.00 | 0.00 | 0.00 |
July | 678.74 | 322.53 | 356.21 | 1047.48 | 89.06 | 0.00 | 0.00 | 0.00 |
August | 686.30 | 378.12 | 308.19 | 1042.90 | 99.93 | 0.00 | 0.00 | 0.00 |
September | 571.97 | 310.91 | 261.06 | 830.55 | 154.87 | 0.00 | 0.00 | 0.00 |
October | 413.90 | 227.00 | 186.90 | 486.81 | 361.56 | 0.00 | 0.00 | 0.00 |
November | 321.19 | 181.00 | 140.18 | 331.76 | 431.02 | 0.00 | 0.00 | 0.00 |
December | 278.56 | 160.52 | 118.04 | 251.82 | 559.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 508.22 | 270.61 | 237.60 | 649.09 | 305.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.56 | 160.52 | 118.04 | 251.82 | 89.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 747.77 | 392.46 | 357.27 | 1131.57 | 559.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.44 | 216.04 | 46.40 | 318.08 | 118.05 | 0.00 | 0.00 | 0.00 |
February | 248.33 | 197.45 | 50.88 | 296.20 | 127.96 | 0.00 | 0.00 | 0.00 |
March | 186.54 | 123.28 | 63.25 | 227.67 | 102.34 | 0.00 | 0.00 | 0.00 |
April | 122.14 | 50.53 | 71.61 | 139.45 | 94.46 | 0.00 | 0.00 | 0.00 |
May | 110.99 | 21.34 | 89.65 | 149.48 | 55.13 | 0.00 | 0.00 | 0.00 |
June | 100.91 | 18.22 | 82.70 | 175.76 | 27.67 | 0.00 | 0.00 | 0.00 |
July | 104.23 | 17.76 | 86.47 | 181.59 | 24.80 | 0.00 | 0.00 | 0.00 |
August | 132.62 | 54.56 | 78.06 | 222.38 | 27.39 | 0.00 | 0.00 | 0.00 |
September | 174.20 | 97.92 | 76.28 | 263.55 | 42.64 | 0.00 | 0.00 | 0.00 |
October | 205.63 | 145.70 | 59.94 | 267.16 | 95.85 | 0.00 | 0.00 | 0.00 |
November | 252.05 | 201.04 | 51.01 | 313.10 | 111.00 | 0.00 | 0.00 | 0.00 |
December | 240.54 | 194.72 | 45.82 | 281.23 | 139.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.99 | 111.06 | 66.93 | 235.96 | 80.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 17.76 | 45.82 | 139.45 | 24.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.44 | 216.04 | 89.65 | 318.08 | 139.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.55 | 0.00 | 34.55 | 5.36 | 184.80 | 0.00 | 0.00 | 0.00 |
February | 43.43 | 0.00 | 43.43 | 6.32 | 189.94 | 0.00 | 0.00 | 0.00 |
March | 59.11 | 0.00 | 59.11 | 24.58 | 141.13 | 0.00 | 0.00 | 0.00 |
April | 74.31 | 0.49 | 73.82 | 40.23 | 120.04 | 0.00 | 0.00 | 0.00 |
May | 101.51 | 3.40 | 98.10 | 94.61 | 65.38 | 0.00 | 0.00 | 0.00 |
June | 111.29 | 12.45 | 98.84 | 151.78 | 33.51 | 0.00 | 0.00 | 0.00 |
July | 105.56 | 7.21 | 98.35 | 146.29 | 30.99 | 0.00 | 0.00 | 0.00 |
August | 84.04 | 2.27 | 81.77 | 110.14 | 36.75 | 0.00 | 0.00 | 0.00 |
September | 70.37 | 0.06 | 70.31 | 81.00 | 59.92 | 0.00 | 0.00 | 0.00 |
October | 50.34 | 0.00 | 50.34 | 26.47 | 134.99 | 0.00 | 0.00 | 0.00 |
November | 38.22 | 0.00 | 38.22 | 8.84 | 165.14 | 0.00 | 0.00 | 0.00 |
December | 32.33 | 0.00 | 32.33 | 4.28 | 212.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.21 | 2.16 | 65.05 | 58.62 | 114.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.33 | 0.00 | 32.33 | 4.28 | 30.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.29 | 12.45 | 98.84 | 151.78 | 212.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.91 | 0.00 | 30.91 | 4.80 | 165.32 | 0.00 | 0.00 | 0.00 |
February | 38.86 | 0.00 | 38.86 | 5.66 | 169.94 | 0.00 | 0.00 | 0.00 |
March | 52.89 | 0.00 | 52.88 | 21.99 | 126.27 | 0.00 | 0.00 | 0.00 |
April | 66.48 | 0.44 | 66.05 | 35.99 | 107.40 | 0.00 | 0.00 | 0.00 |
May | 90.82 | 3.05 | 87.77 | 84.65 | 58.50 | 0.00 | 0.00 | 0.00 |
June | 99.57 | 11.13 | 88.44 | 135.80 | 29.98 | 0.00 | 0.00 | 0.00 |
July | 94.44 | 6.45 | 87.99 | 130.89 | 27.73 | 0.00 | 0.00 | 0.00 |
August | 75.19 | 2.03 | 73.16 | 98.54 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 62.96 | 0.05 | 62.91 | 72.47 | 53.61 | 0.00 | 0.00 | 0.00 |
October | 45.04 | 0.00 | 45.04 | 23.69 | 120.78 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 0.00 | 34.19 | 7.91 | 147.75 | 0.00 | 0.00 | 0.00 |
December | 28.92 | 0.00 | 28.92 | 3.83 | 190.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.13 | 1.93 | 58.20 | 52.45 | 102.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.92 | 0.00 | 28.92 | 3.83 | 27.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.57 | 11.13 | 88.44 | 135.80 | 190.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 979.75 | 806.53 | 173.22 | 1138.06 | 459.53 | 0.00 | 0.00 | 0.00 |
February | 927.09 | 737.13 | 189.95 | 1061.56 | 491.63 | 0.00 | 0.00 | 0.00 |
March | 696.40 | 460.25 | 236.15 | 803.87 | 392.86 | 0.00 | 0.00 | 0.00 |
April | 456.00 | 188.65 | 267.36 | 480.48 | 356.94 | 0.00 | 0.00 | 0.00 |
May | 414.37 | 79.68 | 334.68 | 483.14 | 208.92 | 0.00 | 0.00 | 0.00 |
June | 376.73 | 68.01 | 308.73 | 552.01 | 108.62 | 0.00 | 0.00 | 0.00 |
July | 389.12 | 66.29 | 322.83 | 573.01 | 97.69 | 0.00 | 0.00 | 0.00 |
August | 495.10 | 203.69 | 291.41 | 727.62 | 112.43 | 0.00 | 0.00 | 0.00 |
September | 650.36 | 365.56 | 284.79 | 893.84 | 174.39 | 0.00 | 0.00 | 0.00 |
October | 767.69 | 543.93 | 223.76 | 941.09 | 379.49 | 0.00 | 0.00 | 0.00 |
November | 940.97 | 750.54 | 190.43 | 1119.69 | 434.70 | 0.00 | 0.00 | 0.00 |
December | 898.00 | 726.96 | 171.04 | 1012.19 | 536.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.48 | 414.60 | 249.87 | 814.12 | 311.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.73 | 66.29 | 171.04 | 480.48 | 97.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 979.75 | 806.53 | 334.68 | 1138.06 | 536.01 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.407892E+10 | 0.162126E+10 |
February | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.345598E+10 | 0.153215E+10 |
March | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.290753E+10 | 0.134405E+10 |
April | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.169506E+10 | 0.115919E+10 |
May | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.177082E+10 | 0.690844E+09 |
June | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.192990E+10 | 0.360960E+09 |
July | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.206855E+10 | 0.332603E+09 |
August | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.262689E+10 | 0.390291E+09 |
September | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.311760E+10 | 0.595773E+09 |
October | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.338762E+10 | 0.130897E+10 |
November | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.389002E+10 | 0.147049E+10 |
December | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.365894E+10 | 0.184384E+10 |
Annual Sum or Average | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.345878E+11 | 0.126504E+11 |
Minimum of Months | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.169506E+10 | 0.332603E+09 |
Maximum of Months | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.407892E+10 | 0.184384E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.113839E+11 | 0.481637E+10 |
February | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.964320E+10 | 0.451943E+10 |
March | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.809893E+10 | 0.399630E+10 |
April | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.468418E+10 | 0.350086E+10 |
May | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.485203E+10 | 0.214705E+10 |
June | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.536736E+10 | 0.107496E+10 |
July | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.575573E+10 | 0.998018E+09 |
August | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.732782E+10 | 0.116479E+10 |
September | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.871081E+10 | 0.176768E+10 |
October | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.946417E+10 | 0.388429E+10 |
November | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.108653E+11 | 0.436803E+10 |
December | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.102082E+11 | 0.543605E+10 |
Annual Sum or Average | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.963617E+11 | 0.376738E+11 |
Minimum of Months | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.468418E+10 | 0.998018E+09 |
Maximum of Months | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.113839E+11 | 0.543605E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.150007E+11 | 0.643879E+10 |
February | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.127267E+11 | 0.606377E+10 |
March | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.106953E+11 | 0.541345E+10 |
April | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.618342E+10 | 0.480121E+10 |
May | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.641392E+10 | 0.289632E+10 |
June | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.713780E+10 | 0.142038E+10 |
July | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.764958E+10 | 0.131667E+10 |
August | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.971911E+10 | 0.152363E+10 |
September | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.115228E+11 | 0.232115E+10 |
October | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.124806E+11 | 0.522404E+10 |
November | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.143229E+11 | 0.585600E+10 |
December | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.134486E+11 | 0.730534E+10 |
Annual Sum or Average | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.127302E+12 | 0.505808E+11 |
Minimum of Months | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.618342E+10 | 0.131667E+10 |
Maximum of Months | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.150007E+11 | 0.730534E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.818969E+09 | 0.316434E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.691290E+09 | 0.303158E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.581362E+09 | 0.264451E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.337634E+09 | 0.231163E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.353005E+09 | 0.133468E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.395740E+09 | 57434169.94 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.425595E+09 | 50524538.30 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.534636E+09 | 60282649.52 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.630048E+09 | 0.101396E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.679545E+09 | 0.252199E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.780515E+09 | 0.286513E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.731464E+09 | 0.365568E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.695980E+10 | 0.242259E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.337634E+09 | 50524538.30 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.818969E+09 | 0.365568E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.428217E+09 | 0.651300E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.461459E+09 | 0.604379E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.643975E+09 | 0.500990E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.567120E+09 | 0.421795E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.866582E+09 | 0.242423E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122839E+10 | 0.106606E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104714E+10 | 93925748.11 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106887E+10 | 0.111059E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.874970E+09 | 0.190764E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.626065E+09 | 0.483960E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.443470E+09 | 0.566942E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.322981E+09 | 0.743982E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.857924E+10 | 0.471813E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.322981E+09 | 93925748.11 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122839E+10 | 0.743982E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 15984649.15 | 0.359967E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 17271863.24 | 0.335783E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 59127810.46 | 0.278343E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 87234608.06 | 0.228976E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.204870E+09 | 0.126682E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.319688E+09 | 57410724.82 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.319425E+09 | 52206508.80 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.242446E+09 | 63097494.89 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.173566E+09 | 0.107889E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 63351475.78 | 0.262253E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 24449071.05 | 0.310453E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 13231880.44 | 0.413732E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.154065E+10 | 0.259679E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 13231880.44 | 52206508.80 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.319688E+09 | 0.413732E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.445975E+09 | 0.635761E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.478129E+09 | 0.592620E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.654962E+09 | 0.496325E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.571974E+09 | 0.420714E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.862600E+09 | 0.247663E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122064E+10 | 0.114990E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103787E+10 | 0.102053E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106524E+10 | 0.119763E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.876749E+09 | 0.198891E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.636250E+09 | 0.479377E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.460255E+09 | 0.554869E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.338101E+09 | 0.730522E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.864875E+10 | 0.469355E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.338101E+09 | 0.102053E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122064E+10 | 0.730522E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.624422E+09 | 0.316807E+09 |
February | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.529386E+09 | 0.287536E+09 |
March | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.443099E+09 | 0.257646E+09 |
April | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.250014E+09 | 0.238373E+09 |
May | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.250734E+09 | 0.154731E+09 |
June | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.283450E+09 | 82825256.58 |
July | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.304775E+09 | 79107940.72 |
August | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.394851E+09 | 90143615.31 |
September | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.473839E+09 | 0.127909E+09 |
October | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.519190E+09 | 0.260743E+09 |
November | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.599205E+09 | 0.287533E+09 |
December | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.562451E+09 | 0.344271E+09 |
Annual Sum or Average | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.523541E+10 | 0.252763E+10 |
Minimum of Months | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.250014E+09 | 79107940.72 |
Maximum of Months | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.624422E+09 | 0.344271E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58468616.74 | 0.00 | 58468616.74 | 12408198.11 | 0.294893E+09 |
February | 66376345.10 | 0.00 | 66376345.10 | 14026536.60 | 0.273927E+09 |
March | 0.100024E+09 | 5161.40 | 0.100019E+09 | 49435409.84 | 0.224731E+09 |
April | 0.121681E+09 | 797247.66 | 0.120884E+09 | 71846604.99 | 0.186536E+09 |
May | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.171280E+09 | 99709424.77 |
June | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.267572E+09 | 41578359.73 |
July | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.266532E+09 | 37959497.52 |
August | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.204941E+09 | 45597587.10 |
September | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.147291E+09 | 80818812.77 |
October | 85190674.52 | 0.00 | 85190674.52 | 54158222.31 | 0.210423E+09 |
November | 62584379.74 | 0.00 | 62584379.74 | 19723137.46 | 0.253397E+09 |
December | 54704647.81 | 0.00 | 54704647.81 | 9981825.51 | 0.341534E+09 |
Annual Sum or Average | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.128919E+10 | 0.209111E+10 |
Minimum of Months | 54704647.81 | 0.00 | 54704647.81 | 9981825.51 | 37959497.52 |
Maximum of Months | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.267572E+09 | 0.341534E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.375926E+09 | 0.640611E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.483187E+09 | 0.602131E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.697324E+09 | 0.492084E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.682496E+09 | 0.412875E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.962394E+09 | 0.228727E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.134876E+10 | 97229337.54 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.128183E+10 | 88526908.38 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.127499E+10 | 0.107247E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.971364E+09 | 0.180709E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.589623E+09 | 0.474417E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.389007E+09 | 0.563477E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.310129E+09 | 0.740568E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.936703E+10 | 0.462860E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.310129E+09 | 88526908.38 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.134876E+10 | 0.740568E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.817471E+09 | 0.315071E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.688866E+09 | 0.301782E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.577424E+09 | 0.263126E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.333694E+09 | 0.230779E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.349668E+09 | 0.132918E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.392438E+09 | 56333946.44 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.421783E+09 | 50109115.46 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.530797E+09 | 59902887.43 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.627465E+09 | 0.100672E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.677875E+09 | 0.250932E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.779534E+09 | 0.285010E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.730110E+09 | 0.364461E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.692712E+10 | 0.241110E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.333694E+09 | 50109115.46 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.817471E+09 | 0.364461E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 15056204.48 | 0.358300E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 15233090.10 | 0.334758E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 55710422.04 | 0.276984E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 83400332.08 | 0.228297E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.201539E+09 | 0.125397E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.313087E+09 | 56334769.74 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.312945E+09 | 51801701.00 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.235657E+09 | 62436975.32 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.169882E+09 | 0.106226E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 61064978.21 | 0.259657E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 22865058.44 | 0.308130E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 12257731.68 | 0.412159E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.149870E+10 | 0.258048E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 12257731.68 | 51801701.00 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.313087E+09 | 0.412159E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425875E+09 | 0.260481E+09 | 0.165394E+09 | 0.388336E+09 | 0.617312E+09 |
February | 0.515669E+09 | 0.326363E+09 | 0.189306E+09 | 0.494625E+09 | 0.584474E+09 |
March | 0.687736E+09 | 0.401434E+09 | 0.286302E+09 | 0.708359E+09 | 0.485560E+09 |
April | 0.679412E+09 | 0.330906E+09 | 0.348505E+09 | 0.687800E+09 | 0.410844E+09 |
May | 0.823047E+09 | 0.344559E+09 | 0.478488E+09 | 0.959974E+09 | 0.233429E+09 |
June | 0.969184E+09 | 0.508660E+09 | 0.460524E+09 | 0.133441E+10 | 0.105980E+09 |
July | 0.909035E+09 | 0.431962E+09 | 0.477073E+09 | 0.126740E+10 | 96940052.92 |
August | 0.919162E+09 | 0.506410E+09 | 0.412753E+09 | 0.126596E+10 | 0.116070E+09 |
September | 0.741328E+09 | 0.402965E+09 | 0.338362E+09 | 0.971607E+09 | 0.187311E+09 |
October | 0.554336E+09 | 0.304019E+09 | 0.250317E+09 | 0.600409E+09 | 0.468157E+09 |
November | 0.416289E+09 | 0.234599E+09 | 0.181690E+09 | 0.401720E+09 | 0.545649E+09 |
December | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.321045E+09 | 0.720737E+09 |
Annual Sum or Average | 0.801415E+10 | 0.426734E+10 | 0.374681E+10 | 0.940164E+10 | 0.457246E+10 |
Minimum of Months | 0.373075E+09 | 0.214985E+09 | 0.158090E+09 | 0.321045E+09 | 96940052.92 |
Maximum of Months | 0.969184E+09 | 0.508660E+09 | 0.478488E+09 | 0.133441E+10 | 0.720737E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 16245973.18 | 0.491728E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 17873728.37 | 0.453933E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 71795780.94 | 0.374944E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.111348E+09 | 0.306559E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.263585E+09 | 0.172233E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.402644E+09 | 84557173.93 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.399861E+09 | 81028728.07 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.302628E+09 | 96807237.46 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.215157E+09 | 0.156499E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 75096585.38 | 0.363016E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 26262990.16 | 0.424076E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 13557918.37 | 0.561421E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.191606E+10 | 0.356680E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 13557918.37 | 81028728.07 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.402644E+09 | 0.561421E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34116379.75 | 0.00 | 34116379.75 | 5988938.41 | 0.181271E+09 |
February | 38730531.38 | 0.00 | 38730531.38 | 6588996.37 | 0.167339E+09 |
March | 58364136.20 | 3011.67 | 58361124.52 | 26466897.68 | 0.138220E+09 |
April | 71000608.82 | 465193.22 | 70535415.60 | 41047663.82 | 0.113010E+09 |
May | 0.100224E+09 | 3361308.60 | 96862221.74 | 97168268.20 | 63492178.85 |
June | 0.106339E+09 | 11891705.58 | 94447236.21 | 0.148431E+09 | 31171275.55 |
July | 0.104222E+09 | 7114228.39 | 97107710.86 | 0.147405E+09 | 29870544.30 |
August | 82980016.94 | 2245617.48 | 80734399.46 | 0.111561E+09 | 35687156.20 |
September | 67238296.50 | 53699.58 | 67184596.92 | 79315774.80 | 57691893.73 |
October | 49708673.90 | 0.00 | 49708673.90 | 27683710.87 | 0.133822E+09 |
November | 36517923.36 | 0.00 | 36517923.36 | 9681625.64 | 0.156332E+09 |
December | 31920107.62 | 0.00 | 31920107.62 | 4998010.10 | 0.206963E+09 |
Annual Sum or Average | 0.781361E+09 | 25134764.53 | 0.756226E+09 | 0.706338E+09 | 0.131487E+10 |
Minimum of Months | 31920107.62 | 0.00 | 31920107.62 | 4998010.10 | 29870544.30 |
Maximum of Months | 0.106339E+09 | 11891705.58 | 97107710.86 | 0.148431E+09 | 0.206963E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327974E+09 | 0.269987E+09 | 57987003.41 | 0.384223E+09 | 0.153513E+09 |
February | 0.280311E+09 | 0.222878E+09 | 57433344.00 | 0.324593E+09 | 0.147294E+09 |
March | 0.233121E+09 | 0.154069E+09 | 79051433.12 | 0.272802E+09 | 0.130372E+09 |
April | 0.147724E+09 | 61112968.53 | 86610767.13 | 0.158979E+09 | 0.113681E+09 |
May | 0.138711E+09 | 26674072.02 | 0.112037E+09 | 0.165750E+09 | 68566117.77 |
June | 0.122044E+09 | 22030990.58 | 0.100013E+09 | 0.182446E+09 | 34257067.51 |
July | 0.130258E+09 | 22190312.50 | 0.108068E+09 | 0.195051E+09 | 31919816.37 |
August | 0.165737E+09 | 68185376.53 | 97551239.88 | 0.247025E+09 | 36986232.73 |
September | 0.210685E+09 | 0.118425E+09 | 92260125.35 | 0.292434E+09 | 56769464.67 |
October | 0.256987E+09 | 0.182083E+09 | 74903651.52 | 0.317642E+09 | 0.127458E+09 |
November | 0.304831E+09 | 0.243141E+09 | 61689551.46 | 0.366296E+09 | 0.139973E+09 |
December | 0.300608E+09 | 0.243350E+09 | 57257659.68 | 0.342597E+09 | 0.177349E+09 |
Annual Sum or Average | 0.261899E+10 | 0.163413E+10 | 0.984863E+09 | 0.324984E+10 | 0.121814E+10 |
Minimum of Months | 0.122044E+09 | 22030990.58 | 57257659.68 | 0.158979E+09 | 31919816.37 |
Maximum of Months | 0.327974E+09 | 0.269987E+09 | 0.112037E+09 | 0.384223E+09 | 0.177349E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.890190E+09 | 0.732801E+09 | 0.157389E+09 | 0.104286E+10 | 0.416665E+09 |
February | 0.760821E+09 | 0.604935E+09 | 0.155886E+09 | 0.881011E+09 | 0.399787E+09 |
March | 0.632738E+09 | 0.418176E+09 | 0.214562E+09 | 0.740441E+09 | 0.353855E+09 |
April | 0.400952E+09 | 0.165873E+09 | 0.235079E+09 | 0.431501E+09 | 0.308554E+09 |
May | 0.376489E+09 | 72398887.53 | 0.304090E+09 | 0.449880E+09 | 0.186102E+09 |
June | 0.331253E+09 | 59796614.77 | 0.271456E+09 | 0.495197E+09 | 92980688.36 |
July | 0.353548E+09 | 60229047.04 | 0.293319E+09 | 0.529409E+09 | 86636910.68 |
August | 0.449843E+09 | 0.185069E+09 | 0.264774E+09 | 0.670476E+09 | 0.100388E+09 |
September | 0.571844E+09 | 0.321431E+09 | 0.250413E+09 | 0.793727E+09 | 0.154084E+09 |
October | 0.697515E+09 | 0.494211E+09 | 0.203304E+09 | 0.862147E+09 | 0.345947E+09 |
November | 0.827373E+09 | 0.659935E+09 | 0.167438E+09 | 0.994203E+09 | 0.379916E+09 |
December | 0.815911E+09 | 0.660502E+09 | 0.155409E+09 | 0.929878E+09 | 0.481362E+09 |
Annual Sum or Average | 0.710848E+10 | 0.443536E+10 | 0.267312E+10 | 0.882073E+10 | 0.330628E+10 |
Minimum of Months | 0.331253E+09 | 59796614.77 | 0.155409E+09 | 0.431501E+09 | 86636910.68 |
Maximum of Months | 0.890190E+09 | 0.732801E+09 | 0.304090E+09 | 0.104286E+10 | 0.481362E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.817252E+09 | 0.314399E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.688255E+09 | 0.302623E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.578599E+09 | 0.263114E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.335549E+09 | 0.230024E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.350640E+09 | 0.132585E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.393508E+09 | 56047184.25 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.423680E+09 | 48984041.33 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.531794E+09 | 58693470.89 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.627516E+09 | 99307791.02 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.677287E+09 | 0.249987E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.777958E+09 | 0.284928E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.728969E+09 | 0.364687E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.693101E+10 | 0.240538E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.335549E+09 | 48984041.33 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.817252E+09 | 0.364687E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.426847E+09 | 0.645457E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.458808E+09 | 0.602116E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.640462E+09 | 0.497839E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.563536E+09 | 0.419258E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.861195E+09 | 0.240420E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.122271E+10 | 0.104068E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.104268E+10 | 91080127.45 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106384E+10 | 0.108118E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.871866E+09 | 0.186697E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.623583E+09 | 0.479067E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.441382E+09 | 0.562795E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.322016E+09 | 0.740473E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.853892E+10 | 0.467739E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.322016E+09 | 91080127.45 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.122271E+10 | 0.740473E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 16728324.09 | 0.355726E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 17573820.48 | 0.333763E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 59237122.57 | 0.276880E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 86532682.26 | 0.228094E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.202689E+09 | 0.126677E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.317955E+09 | 56953564.74 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.318172E+09 | 51555784.76 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.241170E+09 | 62338753.05 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.173594E+09 | 0.106459E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 63919670.31 | 0.260015E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 24935234.10 | 0.307359E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 13843561.70 | 0.411056E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.153635E+10 | 0.257688E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 13843561.70 | 51555784.76 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.318172E+09 | 0.411056E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454908E+09 | 0.288304E+09 | 0.166604E+09 | 0.447068E+09 | 0.629317E+09 |
February | 0.496369E+09 | 0.307906E+09 | 0.188463E+09 | 0.477233E+09 | 0.590038E+09 |
March | 0.640872E+09 | 0.353023E+09 | 0.287849E+09 | 0.652212E+09 | 0.493503E+09 |
April | 0.584971E+09 | 0.247796E+09 | 0.337175E+09 | 0.568361E+09 | 0.418741E+09 |
May | 0.739057E+09 | 0.261015E+09 | 0.478041E+09 | 0.856138E+09 | 0.247258E+09 |
June | 0.873178E+09 | 0.419781E+09 | 0.453397E+09 | 0.121467E+10 | 0.113656E+09 |
July | 0.734347E+09 | 0.268122E+09 | 0.466225E+09 | 0.103333E+10 | 0.100293E+09 |
August | 0.768972E+09 | 0.380005E+09 | 0.388968E+09 | 0.106019E+10 | 0.117979E+09 |
September | 0.662115E+09 | 0.318550E+09 | 0.343565E+09 | 0.874050E+09 | 0.195911E+09 |
October | 0.572943E+09 | 0.327477E+09 | 0.245466E+09 | 0.634990E+09 | 0.474547E+09 |
November | 0.455288E+09 | 0.276523E+09 | 0.178766E+09 | 0.460036E+09 | 0.550017E+09 |
December | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.338619E+09 | 0.726819E+09 |
Annual Sum or Average | 0.736245E+10 | 0.367255E+10 | 0.368990E+10 | 0.861690E+10 | 0.465808E+10 |
Minimum of Months | 0.379433E+09 | 0.224048E+09 | 0.155385E+09 | 0.338619E+09 | 0.100293E+09 |
Maximum of Months | 0.873178E+09 | 0.419781E+09 | 0.478041E+09 | 0.121467E+10 | 0.726819E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.117892E+10 | 0.478248E+09 |
February | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.993977E+09 | 0.457721E+09 |
March | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.838688E+09 | 0.394447E+09 |
April | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.487001E+09 | 0.342907E+09 |
May | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.516523E+09 | 0.193335E+09 |
June | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.587051E+09 | 77726514.31 |
July | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.628912E+09 | 68708825.17 |
August | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.784805E+09 | 83168175.92 |
September | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.919206E+09 | 0.145251E+09 |
October | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.984963E+09 | 0.376158E+09 |
November | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.112501E+10 | 0.433321E+09 |
December | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.104808E+10 | 0.555854E+09 |
Annual Sum or Average | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.100931E+11 | 0.360685E+10 |
Minimum of Months | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.487001E+09 | 68708825.17 |
Maximum of Months | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.117892E+10 | 0.555854E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 67908257.07 | 0.293181E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 74921344.65 | 0.273103E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.332496E+09 | 0.228112E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.514916E+09 | 0.191712E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.132595E+10 | 0.104062E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.217612E+10 | 0.478998E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.217098E+10 | 0.457141E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.163845E+10 | 0.541026E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.115898E+10 | 0.878637E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.377471E+09 | 0.213885E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.117450E+09 | 0.255062E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 54097466.30 | 0.336718E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.100098E+11 | 0.213141E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 54097466.30 | 0.457141E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.217612E+10 | 0.336718E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511513E+09 | 0.00 | 0.511513E+09 | 59990541.84 | 0.299818E+10 |
February | 0.580694E+09 | 0.00 | 0.580694E+09 | 67687771.57 | 0.279376E+10 |
March | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.314394E+09 | 0.233296E+10 |
April | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.493482E+09 | 0.196205E+10 |
May | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.130081E+10 | 0.106185E+10 |
June | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.215706E+10 | 0.491097E+09 |
July | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.215195E+10 | 0.470046E+09 |
August | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.162100E+10 | 0.555893E+09 |
September | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.114295E+10 | 0.898124E+09 |
October | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.362320E+09 | 0.218175E+10 |
November | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.108959E+09 | 0.260909E+10 |
December | 0.478584E+09 | 0.00 | 0.478584E+09 | 48179103.90 | 0.344484E+10 |
Annual Sum or Average | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.982878E+10 | 0.217996E+11 |
Minimum of Months | 0.478584E+09 | 0.00 | 0.478584E+09 | 48179103.90 | 0.470046E+09 |
Maximum of Months | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.215706E+10 | 0.344484E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73076084.28 | 0.00 | 73076084.28 | 22141853.78 | 0.358987E+09 |
February | 82959434.63 | 0.00 | 82959434.63 | 22397100.31 | 0.342093E+09 |
March | 0.125014E+09 | 6450.90 | 0.125007E+09 | 73470256.75 | 0.287264E+09 |
April | 0.152081E+09 | 996427.49 | 0.151084E+09 | 0.105787E+09 | 0.243029E+09 |
May | 0.214675E+09 | 7199804.69 | 0.207475E+09 | 0.253500E+09 | 0.138825E+09 |
June | 0.227774E+09 | 25471614.68 | 0.202303E+09 | 0.384435E+09 | 67031530.42 |
July | 0.223240E+09 | 15238426.74 | 0.208001E+09 | 0.385558E+09 | 63666774.05 |
August | 0.177740E+09 | 4810033.59 | 0.172930E+09 | 0.305229E+09 | 71815231.15 |
September | 0.144022E+09 | 115022.61 | 0.143907E+09 | 0.222926E+09 | 0.110819E+09 |
October | 0.106474E+09 | 0.00 | 0.106474E+09 | 84052919.98 | 0.265744E+09 |
November | 78220106.15 | 0.00 | 78220106.15 | 33498791.74 | 0.312115E+09 |
December | 68371746.70 | 0.00 | 68371746.70 | 16692677.15 | 0.423425E+09 |
Annual Sum or Average | 0.167365E+10 | 53837780.70 | 0.161981E+10 | 0.190969E+10 | 0.268481E+10 |
Minimum of Months | 68371746.70 | 0.00 | 68371746.70 | 16692677.15 | 63666774.05 |
Maximum of Months | 0.227774E+09 | 25471614.68 | 0.208001E+09 | 0.385558E+09 | 0.423425E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851689E+09 | 0.520925E+09 | 0.330764E+09 | 0.828175E+09 | 0.125328E+10 |
February | 0.103127E+10 | 0.652680E+09 | 0.378585E+09 | 0.103407E+10 | 0.121042E+10 |
March | 0.137538E+10 | 0.802812E+09 | 0.572564E+09 | 0.150151E+10 | 0.102107E+10 |
April | 0.135873E+10 | 0.661766E+09 | 0.696961E+09 | 0.146826E+10 | 0.885631E+09 |
May | 0.164598E+10 | 0.689069E+09 | 0.956909E+09 | 0.211466E+10 | 0.516082E+09 |
June | 0.193823E+10 | 0.101725E+10 | 0.920982E+09 | 0.293304E+10 | 0.251044E+09 |
July | 0.181794E+10 | 0.863862E+09 | 0.954079E+09 | 0.280556E+10 | 0.238528E+09 |
August | 0.183819E+10 | 0.101275E+10 | 0.825447E+09 | 0.279330E+10 | 0.267649E+09 |
September | 0.148255E+10 | 0.805873E+09 | 0.676677E+09 | 0.215279E+10 | 0.401411E+09 |
October | 0.110859E+10 | 0.607994E+09 | 0.500598E+09 | 0.130388E+10 | 0.968400E+09 |
November | 0.832518E+09 | 0.469164E+09 | 0.363353E+09 | 0.859925E+09 | 0.111720E+10 |
December | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.674475E+09 | 0.149757E+10 |
Annual Sum or Average | 0.160272E+11 | 0.853408E+10 | 0.749308E+10 | 0.204696E+11 | 0.962828E+10 |
Minimum of Months | 0.746097E+09 | 0.429939E+09 | 0.316158E+09 | 0.674475E+09 | 0.238528E+09 |
Maximum of Months | 0.193823E+10 | 0.101725E+10 | 0.956909E+09 | 0.293304E+10 | 0.149757E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702909E+09 | 0.578632E+09 | 0.124277E+09 | 0.851953E+09 | 0.316196E+09 |
February | 0.600757E+09 | 0.477667E+09 | 0.123090E+09 | 0.716569E+09 | 0.309550E+09 |
March | 0.499620E+09 | 0.330199E+09 | 0.169422E+09 | 0.609784E+09 | 0.274108E+09 |
April | 0.316599E+09 | 0.130976E+09 | 0.185623E+09 | 0.361446E+09 | 0.244849E+09 |
May | 0.297282E+09 | 57167386.18 | 0.240115E+09 | 0.400372E+09 | 0.147667E+09 |
June | 0.261563E+09 | 47216418.44 | 0.214346E+09 | 0.455578E+09 | 71727107.16 |
July | 0.279167E+09 | 47557874.28 | 0.231609E+09 | 0.486377E+09 | 66414126.19 |
August | 0.355204E+09 | 0.146134E+09 | 0.209070E+09 | 0.595614E+09 | 73353114.49 |
September | 0.451537E+09 | 0.253807E+09 | 0.197730E+09 | 0.683112E+09 | 0.110511E+09 |
October | 0.550770E+09 | 0.390238E+09 | 0.160532E+09 | 0.715551E+09 | 0.256737E+09 |
November | 0.653308E+09 | 0.521096E+09 | 0.132212E+09 | 0.811554E+09 | 0.287704E+09 |
December | 0.644257E+09 | 0.521543E+09 | 0.122714E+09 | 0.753256E+09 | 0.372950E+09 |
Annual Sum or Average | 0.561297E+10 | 0.350223E+10 | 0.211074E+10 | 0.744117E+10 | 0.253177E+10 |
Minimum of Months | 0.261563E+09 | 47216418.44 | 0.122714E+09 | 0.361446E+09 | 66414126.19 |
Maximum of Months | 0.702909E+09 | 0.578632E+09 | 0.240115E+09 | 0.851953E+09 | 0.372950E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92546249.89 | 0.00 | 92546249.89 | 14356545.21 | 0.494977E+09 |
February | 0.105063E+09 | 0.00 | 0.105063E+09 | 15300409.27 | 0.459496E+09 |
March | 0.158322E+09 | 8169.66 | 0.158314E+09 | 65838432.40 | 0.377999E+09 |
April | 0.192601E+09 | 1261912.55 | 0.191339E+09 | 0.104266E+09 | 0.311155E+09 |
May | 0.271873E+09 | 9118098.35 | 0.262755E+09 | 0.253413E+09 | 0.175127E+09 |
June | 0.288462E+09 | 32258192.82 | 0.256204E+09 | 0.393416E+09 | 86862133.22 |
July | 0.282719E+09 | 19298505.98 | 0.263421E+09 | 0.391833E+09 | 83010332.72 |
August | 0.225097E+09 | 6091604.04 | 0.219005E+09 | 0.295004E+09 | 98437329.18 |
September | 0.182395E+09 | 145668.87 | 0.182249E+09 | 0.209945E+09 | 0.155306E+09 |
October | 0.134843E+09 | 0.00 | 0.134843E+09 | 70909903.10 | 0.361570E+09 |
November | 99060829.03 | 0.00 | 99060829.03 | 22906808.76 | 0.428052E+09 |
December | 86588503.18 | 0.00 | 86588503.18 | 11464173.13 | 0.569230E+09 |
Annual Sum or Average | 0.211957E+10 | 68182152.28 | 0.205139E+10 | 0.184865E+10 | 0.360122E+10 |
Minimum of Months | 86588503.18 | 0.00 | 86588503.18 | 11464173.13 | 83010332.72 |
Maximum of Months | 0.288462E+09 | 32258192.82 | 0.263421E+09 | 0.393416E+09 | 0.569230E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82801480.44 | 0.00 | 82801480.44 | 12844855.39 | 0.442785E+09 |
February | 94000165.32 | 0.00 | 94000165.32 | 13689334.15 | 0.411118E+09 |
March | 0.141652E+09 | 7309.43 | 0.141644E+09 | 58905894.93 | 0.338197E+09 |
April | 0.172321E+09 | 1129037.94 | 0.171192E+09 | 93286975.54 | 0.278392E+09 |
May | 0.243246E+09 | 8157997.15 | 0.235088E+09 | 0.226730E+09 | 0.156687E+09 |
June | 0.258088E+09 | 28861527.34 | 0.229226E+09 | 0.351991E+09 | 77715879.71 |
July | 0.252950E+09 | 17266446.42 | 0.235683E+09 | 0.350574E+09 | 74269659.21 |
August | 0.201395E+09 | 5450181.22 | 0.195945E+09 | 0.263941E+09 | 88072251.39 |
September | 0.163189E+09 | 130330.49 | 0.163059E+09 | 0.187838E+09 | 0.138953E+09 |
October | 0.120644E+09 | 0.00 | 0.120644E+09 | 63443358.98 | 0.323498E+09 |
November | 88630099.07 | 0.00 | 88630099.07 | 20494808.59 | 0.382969E+09 |
December | 77471061.88 | 0.00 | 77471061.88 | 10257039.14 | 0.509249E+09 |
Annual Sum or Average | 0.189639E+10 | 61002829.99 | 0.183538E+10 | 0.165400E+10 | 0.322191E+10 |
Minimum of Months | 77471061.88 | 0.00 | 77471061.88 | 10257039.14 | 74269659.21 |
Maximum of Months | 0.258088E+09 | 28861527.34 | 0.235683E+09 | 0.351991E+09 | 0.509249E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262417E+10 | 0.216021E+10 | 0.463962E+09 | 0.304818E+10 | 0.123079E+10 |
February | 0.224281E+10 | 0.178327E+10 | 0.459532E+09 | 0.256812E+10 | 0.118934E+10 |
March | 0.186523E+10 | 0.123273E+10 | 0.632501E+09 | 0.215308E+10 | 0.105223E+10 |
April | 0.118196E+10 | 0.488973E+09 | 0.692985E+09 | 0.124540E+10 | 0.925183E+09 |
May | 0.110984E+10 | 0.213423E+09 | 0.896420E+09 | 0.129404E+10 | 0.559563E+09 |
June | 0.976492E+09 | 0.176273E+09 | 0.800219E+09 | 0.143082E+10 | 0.281547E+09 |
July | 0.104221E+10 | 0.177548E+09 | 0.864667E+09 | 0.153474E+10 | 0.261656E+09 |
August | 0.132608E+10 | 0.545560E+09 | 0.780521E+09 | 0.194885E+10 | 0.301146E+09 |
September | 0.168572E+10 | 0.947538E+09 | 0.738186E+09 | 0.231685E+10 | 0.452017E+09 |
October | 0.205619E+10 | 0.145687E+10 | 0.599314E+09 | 0.252060E+10 | 0.101642E+10 |
November | 0.243899E+10 | 0.194541E+10 | 0.493587E+09 | 0.290222E+10 | 0.112675E+10 |
December | 0.240520E+10 | 0.194708E+10 | 0.458126E+09 | 0.271106E+10 | 0.143564E+10 |
Annual Sum or Average | 0.209549E+11 | 0.130749E+11 | 0.788002E+10 | 0.256740E+11 | 0.983229E+10 |
Minimum of Months | 0.976492E+09 | 0.176273E+09 | 0.458126E+09 | 0.124540E+10 | 0.261656E+09 |
Maximum of Months | 0.262417E+10 | 0.216021E+10 | 0.896420E+09 | 0.304818E+10 | 0.143564E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1522.89 | 605.31 | 1327.33 | 1092.65 | 234.67 | 0.00 | 0.00 |
February | 1428.56 | 633.33 | 1255.98 | 998.64 | 257.34 | 0.00 | 0.00 |
March | 1085.55 | 501.81 | 943.45 | 623.53 | 319.92 | 0.00 | 0.00 |
April | 653.96 | 447.22 | 617.77 | 255.57 | 362.20 | 0.00 | 0.00 |
May | 661.15 | 257.93 | 561.37 | 107.95 | 453.41 | 0.00 | 0.00 |
June | 744.56 | 139.26 | 510.38 | 92.13 | 418.25 | 0.00 | 0.00 |
July | 772.31 | 124.18 | 527.16 | 89.81 | 437.35 | 0.00 | 0.00 |
August | 980.77 | 145.72 | 670.74 | 275.95 | 394.79 | 0.00 | 0.00 |
September | 1202.78 | 229.85 | 881.07 | 495.25 | 385.82 | 0.00 | 0.00 |
October | 1264.79 | 488.71 | 1040.04 | 736.90 | 303.14 | 0.00 | 0.00 |
November | 1500.78 | 567.32 | 1274.79 | 1016.81 | 257.98 | 0.00 | 0.00 |
December | 1366.09 | 688.41 | 1216.57 | 984.85 | 231.72 | 0.00 | 0.00 |
Annual Sum or Average | 1096.77 | 401.14 | 900.20 | 561.69 | 338.52 | 0.00 | 0.00 |
Minimum of Months | 653.96 | 124.18 | 510.38 | 89.81 | 231.72 | 0.00 | 0.00 |
Maximum of Months | 1522.89 | 688.41 | 1327.33 | 1092.65 | 453.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4250.27 | 1798.23 | 3737.67 | 3076.84 | 660.83 | 0.00 | 0.00 |
February | 3986.11 | 1868.15 | 3536.75 | 2812.11 | 724.64 | 0.00 | 0.00 |
March | 3023.79 | 1492.05 | 2656.69 | 1755.81 | 900.88 | 0.00 | 0.00 |
April | 1807.17 | 1350.64 | 1739.60 | 719.67 | 1019.93 | 0.00 | 0.00 |
May | 1811.54 | 801.62 | 1580.77 | 303.98 | 1276.78 | 0.00 | 0.00 |
June | 2070.74 | 414.72 | 1437.19 | 259.44 | 1177.75 | 0.00 | 0.00 |
July | 2148.94 | 372.62 | 1484.44 | 252.89 | 1231.56 | 0.00 | 0.00 |
August | 2735.90 | 434.88 | 1888.76 | 777.06 | 1111.70 | 0.00 | 0.00 |
September | 3360.65 | 681.97 | 2481.05 | 1394.59 | 1086.46 | 0.00 | 0.00 |
October | 3533.52 | 1450.23 | 2928.68 | 2075.07 | 853.61 | 0.00 | 0.00 |
November | 4191.86 | 1685.20 | 3589.72 | 2863.26 | 726.46 | 0.00 | 0.00 |
December | 3811.30 | 2029.59 | 3425.79 | 2773.28 | 652.52 | 0.00 | 0.00 |
Annual Sum or Average | 3055.61 | 1194.63 | 2534.91 | 1581.67 | 953.24 | 0.00 | 0.00 |
Minimum of Months | 1807.17 | 372.62 | 1437.19 | 252.89 | 652.52 | 0.00 | 0.00 |
Maximum of Months | 4250.27 | 2029.59 | 3737.67 | 3076.84 | 1276.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5600.61 | 2403.97 | 4855.45 | 3996.99 | 858.45 | 0.00 | 0.00 |
February | 5260.70 | 2506.52 | 4594.44 | 3653.09 | 941.35 | 0.00 | 0.00 |
March | 3993.18 | 2021.15 | 3451.19 | 2280.90 | 1170.29 | 0.00 | 0.00 |
April | 2385.58 | 1852.32 | 2259.84 | 934.90 | 1324.95 | 0.00 | 0.00 |
May | 2394.68 | 1081.36 | 2053.51 | 394.89 | 1658.62 | 0.00 | 0.00 |
June | 2753.78 | 547.98 | 1866.99 | 337.03 | 1529.97 | 0.00 | 0.00 |
July | 2856.03 | 491.59 | 1928.38 | 328.51 | 1599.86 | 0.00 | 0.00 |
August | 3628.70 | 568.86 | 2453.61 | 1009.44 | 1444.17 | 0.00 | 0.00 |
September | 4445.53 | 895.50 | 3223.02 | 1811.65 | 1411.37 | 0.00 | 0.00 |
October | 4659.74 | 1950.43 | 3804.52 | 2695.63 | 1108.89 | 0.00 | 0.00 |
November | 5525.83 | 2259.26 | 4663.25 | 3719.54 | 943.71 | 0.00 | 0.00 |
December | 5021.13 | 2727.50 | 4450.30 | 3602.64 | 847.66 | 0.00 | 0.00 |
Annual Sum or Average | 4036.70 | 1603.91 | 3292.99 | 2054.68 | 1238.31 | 0.00 | 0.00 |
Minimum of Months | 2385.58 | 491.59 | 1866.99 | 328.51 | 847.66 | 0.00 | 0.00 |
Maximum of Months | 5600.61 | 2727.50 | 4855.45 | 3996.99 | 1658.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 448.67 | 344.33 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 463.57 | 362.21 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 452.17 | 280.47 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 346.48 | 249.34 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 454.32 | 139.32 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 626.46 | 63.15 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 549.76 | 53.84 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 598.37 | 63.66 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 579.97 | 112.04 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 484.52 | 271.91 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 463.34 | 320.39 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 376.33 | 396.90 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 487.00 | 220.69 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 346.48 | 53.84 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 626.46 | 396.90 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.39 | 364.67 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 197.28 | 376.26 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 262.62 | 285.24 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 252.35 | 248.68 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 397.00 | 138.22 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 592.35 | 64.60 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 505.52 | 56.36 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 487.69 | 67.73 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 404.62 | 117.76 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 259.27 | 274.96 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 182.31 | 329.15 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 124.37 | 420.42 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 319.81 | 227.88 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 124.37 | 56.36 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 592.35 | 420.42 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.13 | 118.28 | 209.91 | 172.79 | 37.11 | 0.00 | 0.00 |
February | 218.83 | 118.86 | 198.62 | 157.93 | 40.70 | 0.00 | 0.00 |
March | 165.43 | 96.19 | 149.20 | 98.61 | 50.59 | 0.00 | 0.00 |
April | 96.46 | 91.96 | 97.70 | 40.42 | 57.28 | 0.00 | 0.00 |
May | 93.61 | 57.77 | 88.78 | 17.07 | 71.70 | 0.00 | 0.00 |
June | 109.36 | 31.95 | 80.71 | 14.57 | 66.14 | 0.00 | 0.00 |
July | 113.79 | 29.54 | 83.37 | 14.20 | 69.16 | 0.00 | 0.00 |
August | 147.42 | 33.66 | 106.07 | 43.64 | 62.43 | 0.00 | 0.00 |
September | 182.81 | 49.35 | 139.34 | 78.32 | 61.02 | 0.00 | 0.00 |
October | 193.84 | 97.35 | 164.47 | 116.54 | 47.94 | 0.00 | 0.00 |
November | 231.17 | 110.93 | 201.60 | 160.80 | 40.80 | 0.00 | 0.00 |
December | 210.00 | 128.54 | 192.39 | 155.75 | 36.65 | 0.00 | 0.00 |
Annual Sum or Average | 166.01 | 80.15 | 142.36 | 88.83 | 53.53 | 0.00 | 0.00 |
Minimum of Months | 93.61 | 29.54 | 80.71 | 14.20 | 36.65 | 0.00 | 0.00 |
Maximum of Months | 233.13 | 128.54 | 209.91 | 172.79 | 71.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.63 | 110.10 | 21.83 | 0.00 | 21.83 | 0.00 | 0.00 |
February | 5.80 | 113.23 | 27.44 | 0.00 | 27.44 | 0.00 | 0.00 |
March | 18.46 | 83.91 | 37.34 | 0.00 | 37.34 | 0.00 | 0.00 |
April | 27.72 | 71.97 | 46.94 | 0.31 | 46.64 | 0.00 | 0.00 |
May | 63.95 | 37.23 | 64.13 | 2.15 | 61.98 | 0.00 | 0.00 |
June | 103.23 | 16.04 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
July | 99.51 | 14.17 | 66.69 | 4.55 | 62.14 | 0.00 | 0.00 |
August | 76.52 | 17.02 | 53.10 | 1.44 | 51.66 | 0.00 | 0.00 |
September | 56.83 | 31.18 | 44.46 | 0.04 | 44.42 | 0.00 | 0.00 |
October | 20.22 | 78.56 | 31.81 | 0.00 | 31.81 | 0.00 | 0.00 |
November | 7.61 | 97.76 | 24.15 | 0.00 | 24.15 | 0.00 | 0.00 |
December | 3.73 | 127.51 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Annual Sum or Average | 40.88 | 66.31 | 42.46 | 1.37 | 41.10 | 0.00 | 0.00 |
Minimum of Months | 3.73 | 14.17 | 20.42 | 0.00 | 20.42 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 127.51 | 70.31 | 7.86 | 62.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 429.56 | 340.80 | 421.44 | 313.29 | 108.15 | 0.00 | 0.00 |
February | 471.68 | 360.85 | 461.49 | 332.35 | 129.13 | 0.00 | 0.00 |
March | 472.54 | 278.57 | 443.31 | 273.16 | 170.15 | 0.00 | 0.00 |
April | 388.45 | 244.73 | 384.26 | 178.20 | 206.07 | 0.00 | 0.00 |
May | 486.51 | 131.67 | 418.28 | 149.99 | 268.30 | 0.00 | 0.00 |
June | 670.18 | 57.66 | 474.83 | 214.46 | 260.37 | 0.00 | 0.00 |
July | 635.10 | 50.80 | 443.62 | 179.03 | 264.59 | 0.00 | 0.00 |
August | 673.30 | 61.50 | 475.79 | 243.63 | 232.16 | 0.00 | 0.00 |
September | 615.37 | 107.10 | 460.21 | 253.38 | 206.83 | 0.00 | 0.00 |
October | 471.48 | 269.06 | 412.60 | 259.21 | 153.39 | 0.00 | 0.00 |
November | 441.82 | 318.34 | 412.65 | 291.55 | 121.10 | 0.00 | 0.00 |
December | 373.30 | 397.49 | 379.83 | 274.99 | 104.84 | 0.00 | 0.00 |
Annual Sum or Average | 510.90 | 217.44 | 432.11 | 246.37 | 185.74 | 0.00 | 0.00 |
Minimum of Months | 373.30 | 50.80 | 379.83 | 149.99 | 104.84 | 0.00 | 0.00 |
Maximum of Months | 673.30 | 397.49 | 475.79 | 332.35 | 268.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.93 | 354.57 | 186.29 | 97.25 | 89.03 | 0.00 | 0.00 |
February | 201.99 | 371.21 | 247.45 | 134.91 | 112.54 | 0.00 | 0.00 |
March | 279.44 | 278.87 | 303.45 | 149.88 | 153.57 | 0.00 | 0.00 |
April | 294.26 | 243.31 | 320.79 | 128.05 | 192.74 | 0.00 | 0.00 |
May | 432.62 | 132.93 | 387.44 | 131.33 | 256.11 | 0.00 | 0.00 |
June | 635.34 | 62.35 | 461.79 | 206.07 | 255.72 | 0.00 | 0.00 |
July | 589.87 | 55.37 | 422.74 | 166.97 | 255.78 | 0.00 | 0.00 |
August | 560.21 | 66.22 | 409.54 | 190.87 | 218.67 | 0.00 | 0.00 |
September | 438.39 | 111.25 | 341.57 | 155.51 | 186.06 | 0.00 | 0.00 |
October | 243.78 | 268.55 | 246.72 | 113.51 | 133.21 | 0.00 | 0.00 |
November | 158.17 | 323.75 | 190.78 | 90.51 | 100.27 | 0.00 | 0.00 |
December | 115.43 | 413.96 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Annual Sum or Average | 341.56 | 222.73 | 307.20 | 137.02 | 170.17 | 0.00 | 0.00 |
Minimum of Months | 115.43 | 55.37 | 164.82 | 80.27 | 84.55 | 0.00 | 0.00 |
Maximum of Months | 635.34 | 413.96 | 461.79 | 206.07 | 256.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 509.20 | 432.24 | 502.10 | 374.40 | 127.70 | 0.00 | 0.00 |
February | 484.56 | 459.05 | 489.80 | 342.18 | 147.62 | 0.00 | 0.00 |
March | 409.78 | 367.18 | 404.18 | 213.66 | 190.52 | 0.00 | 0.00 |
April | 286.21 | 324.38 | 313.38 | 88.24 | 225.14 | 0.00 | 0.00 |
May | 362.63 | 181.18 | 331.28 | 41.65 | 289.63 | 0.00 | 0.00 |
June | 471.04 | 90.73 | 327.20 | 48.60 | 278.60 | 0.00 | 0.00 |
July | 472.89 | 83.75 | 325.10 | 40.63 | 284.47 | 0.00 | 0.00 |
August | 496.59 | 100.15 | 344.85 | 97.67 | 247.19 | 0.00 | 0.00 |
September | 532.12 | 163.45 | 398.21 | 169.77 | 228.44 | 0.00 | 0.00 |
October | 474.12 | 357.51 | 425.27 | 252.50 | 172.77 | 0.00 | 0.00 |
November | 520.75 | 406.49 | 489.11 | 348.41 | 140.70 | 0.00 | 0.00 |
December | 450.01 | 500.81 | 461.11 | 337.46 | 123.65 | 0.00 | 0.00 |
Annual Sum or Average | 455.63 | 287.98 | 400.44 | 195.42 | 205.02 | 0.00 | 0.00 |
Minimum of Months | 286.21 | 83.75 | 313.38 | 40.63 | 123.65 | 0.00 | 0.00 |
Maximum of Months | 532.12 | 500.81 | 502.10 | 374.40 | 289.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 448.08 | 341.96 | 432.28 | 323.68 | 108.60 | 0.00 | 0.00 |
February | 461.51 | 361.34 | 453.51 | 324.72 | 128.78 | 0.00 | 0.00 |
March | 449.89 | 278.86 | 425.81 | 255.09 | 170.73 | 0.00 | 0.00 |
April | 344.27 | 247.89 | 347.83 | 146.13 | 201.70 | 0.00 | 0.00 |
May | 451.40 | 138.22 | 386.92 | 118.80 | 268.13 | 0.00 | 0.00 |
June | 623.40 | 61.63 | 437.79 | 180.17 | 257.62 | 0.00 | 0.00 |
July | 547.38 | 52.20 | 378.40 | 117.86 | 260.54 | 0.00 | 0.00 |
August | 595.43 | 61.96 | 419.72 | 196.44 | 223.28 | 0.00 | 0.00 |
September | 577.81 | 109.69 | 429.65 | 220.82 | 208.83 | 0.00 | 0.00 |
October | 482.92 | 269.43 | 419.55 | 267.96 | 151.58 | 0.00 | 0.00 |
November | 461.82 | 318.45 | 427.70 | 307.72 | 119.98 | 0.00 | 0.00 |
December | 375.42 | 395.65 | 382.20 | 278.37 | 103.83 | 0.00 | 0.00 |
Annual Sum or Average | 484.95 | 219.00 | 411.45 | 227.51 | 183.94 | 0.00 | 0.00 |
Minimum of Months | 344.27 | 52.20 | 347.83 | 117.86 | 103.83 | 0.00 | 0.00 |
Maximum of Months | 623.40 | 395.65 | 453.51 | 324.72 | 268.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 166.30 | 360.91 | 197.13 | 107.64 | 89.49 | 0.00 | 0.00 |
February | 197.10 | 374.43 | 239.47 | 127.28 | 112.20 | 0.00 | 0.00 |
March | 261.54 | 283.55 | 285.95 | 131.81 | 154.14 | 0.00 | 0.00 |
April | 250.62 | 247.51 | 284.36 | 95.98 | 188.37 | 0.00 | 0.00 |
May | 393.75 | 138.04 | 356.08 | 100.14 | 255.94 | 0.00 | 0.00 |
June | 589.45 | 63.98 | 424.75 | 171.78 | 252.97 | 0.00 | 0.00 |
July | 503.41 | 55.51 | 357.52 | 105.79 | 251.73 | 0.00 | 0.00 |
August | 485.33 | 66.78 | 353.46 | 143.67 | 209.79 | 0.00 | 0.00 |
September | 403.55 | 116.02 | 311.01 | 122.94 | 188.07 | 0.00 | 0.00 |
October | 258.95 | 272.26 | 253.67 | 122.27 | 131.40 | 0.00 | 0.00 |
November | 182.49 | 326.17 | 205.83 | 106.68 | 99.15 | 0.00 | 0.00 |
December | 124.98 | 418.22 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 318.70 | 226.16 | 286.53 | 118.16 | 168.37 | 0.00 | 0.00 |
Minimum of Months | 124.98 | 55.51 | 167.19 | 83.65 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 589.45 | 418.22 | 424.75 | 171.78 | 255.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 440.16 | 178.56 | 384.89 | 316.84 | 68.05 | 0.00 | 0.00 |
February | 410.87 | 189.20 | 364.20 | 289.58 | 74.62 | 0.00 | 0.00 |
March | 313.13 | 147.27 | 273.57 | 180.80 | 92.77 | 0.00 | 0.00 |
April | 187.89 | 132.29 | 179.14 | 74.11 | 105.03 | 0.00 | 0.00 |
May | 192.85 | 72.18 | 162.78 | 31.30 | 131.48 | 0.00 | 0.00 |
June | 226.49 | 29.99 | 148.00 | 26.72 | 121.28 | 0.00 | 0.00 |
July | 234.81 | 25.65 | 152.86 | 26.04 | 126.82 | 0.00 | 0.00 |
August | 293.01 | 31.05 | 194.50 | 80.02 | 114.48 | 0.00 | 0.00 |
September | 354.63 | 56.04 | 255.49 | 143.61 | 111.88 | 0.00 | 0.00 |
October | 367.74 | 140.44 | 301.58 | 213.68 | 87.90 | 0.00 | 0.00 |
November | 434.03 | 167.18 | 369.65 | 294.84 | 74.81 | 0.00 | 0.00 |
December | 391.31 | 207.53 | 352.77 | 285.58 | 67.19 | 0.00 | 0.00 |
Annual Sum or Average | 320.05 | 114.37 | 261.03 | 162.87 | 98.16 | 0.00 | 0.00 |
Minimum of Months | 187.89 | 25.65 | 148.00 | 26.04 | 67.19 | 0.00 | 0.00 |
Maximum of Months | 440.16 | 207.53 | 384.89 | 316.84 | 131.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.35 | 1094.61 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 30.97 | 1128.90 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 124.14 | 851.67 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 198.66 | 739.63 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 495.05 | 388.52 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 839.55 | 184.80 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 810.55 | 170.68 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 611.73 | 202.00 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 447.14 | 338.98 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 140.93 | 798.55 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 45.31 | 984.04 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 20.20 | 1257.16 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 317.41 | 675.87 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 170.68 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 839.55 | 1257.16 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.40 | 1119.39 | 190.98 | 0.00 | 190.98 | 0.00 | 0.00 |
February | 27.98 | 1154.83 | 240.04 | 0.00 | 240.04 | 0.00 | 0.00 |
March | 117.38 | 871.03 | 326.71 | 0.02 | 326.69 | 0.00 | 0.00 |
April | 190.39 | 756.96 | 410.70 | 2.69 | 408.01 | 0.00 | 0.00 |
May | 485.67 | 396.45 | 561.03 | 18.82 | 542.22 | 0.00 | 0.00 |
June | 832.20 | 189.47 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
July | 803.45 | 175.49 | 583.42 | 39.82 | 543.59 | 0.00 | 0.00 |
August | 605.21 | 207.55 | 464.51 | 12.57 | 451.94 | 0.00 | 0.00 |
September | 440.95 | 346.50 | 388.93 | 0.31 | 388.62 | 0.00 | 0.00 |
October | 135.27 | 814.57 | 278.26 | 0.00 | 278.26 | 0.00 | 0.00 |
November | 42.04 | 1006.59 | 211.23 | 0.00 | 211.23 | 0.00 | 0.00 |
December | 17.99 | 1286.16 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Annual Sum or Average | 311.67 | 691.26 | 371.48 | 11.95 | 359.53 | 0.00 | 0.00 |
Minimum of Months | 17.99 | 175.49 | 178.68 | 0.00 | 178.68 | 0.00 | 0.00 |
Maximum of Months | 832.20 | 1286.16 | 615.11 | 68.79 | 546.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 603.38 | 687.83 | 607.70 | 410.53 | 197.18 | 0.00 | 0.00 |
February | 706.30 | 743.10 | 708.90 | 467.24 | 241.66 | 0.00 | 0.00 |
March | 807.92 | 583.04 | 746.72 | 423.02 | 323.70 | 0.00 | 0.00 |
April | 740.79 | 523.98 | 705.02 | 306.23 | 398.79 | 0.00 | 0.00 |
May | 1029.74 | 295.74 | 805.68 | 281.30 | 524.38 | 0.00 | 0.00 |
June | 1453.77 | 148.50 | 936.56 | 420.50 | 516.06 | 0.00 | 0.00 |
July | 1371.99 | 136.59 | 866.32 | 345.97 | 520.34 | 0.00 | 0.00 |
August | 1378.23 | 153.12 | 885.28 | 434.47 | 450.81 | 0.00 | 0.00 |
September | 1177.66 | 237.81 | 801.74 | 408.87 | 392.87 | 0.00 | 0.00 |
October | 781.62 | 552.90 | 659.29 | 372.70 | 286.59 | 0.00 | 0.00 |
November | 640.65 | 645.30 | 603.41 | 382.04 | 221.37 | 0.00 | 0.00 |
December | 504.34 | 821.51 | 544.63 | 355.24 | 189.38 | 0.00 | 0.00 |
Annual Sum or Average | 934.13 | 459.25 | 739.28 | 383.38 | 355.90 | 0.00 | 0.00 |
Minimum of Months | 504.34 | 136.59 | 544.63 | 281.30 | 189.38 | 0.00 | 0.00 |
Maximum of Months | 1453.77 | 821.51 | 936.56 | 467.24 | 524.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1100.39 | 761.82 | 1045.22 | 806.53 | 238.69 | 0.00 | 0.00 |
February | 1036.96 | 814.93 | 1009.37 | 737.13 | 272.24 | 0.00 | 0.00 |
March | 842.29 | 652.10 | 808.39 | 460.25 | 348.14 | 0.00 | 0.00 |
April | 556.07 | 583.76 | 596.79 | 189.57 | 407.22 | 0.00 | 0.00 |
May | 659.23 | 329.63 | 606.69 | 86.13 | 520.56 | 0.00 | 0.00 |
June | 833.79 | 166.32 | 587.59 | 91.59 | 496.01 | 0.00 | 0.00 |
July | 846.52 | 152.75 | 589.11 | 79.94 | 509.17 | 0.00 | 0.00 |
August | 935.19 | 180.95 | 654.34 | 208.00 | 446.34 | 0.00 | 0.00 |
September | 1046.56 | 287.17 | 783.68 | 365.67 | 418.01 | 0.00 | 0.00 |
October | 984.23 | 628.25 | 863.08 | 543.93 | 319.15 | 0.00 | 0.00 |
November | 1108.76 | 719.93 | 1013.38 | 750.54 | 262.84 | 0.00 | 0.00 |
December | 972.20 | 890.56 | 959.25 | 726.96 | 232.30 | 0.00 | 0.00 |
Annual Sum or Average | 909.40 | 512.36 | 791.82 | 418.70 | 373.12 | 0.00 | 0.00 |
Minimum of Months | 556.07 | 152.75 | 587.59 | 79.94 | 232.30 | 0.00 | 0.00 |
Maximum of Months | 1108.76 | 890.56 | 1045.22 | 806.53 | 520.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.407892E+10 | 0.162126E+10 | 0.355512E+10 | 0.292657E+10 | 0.628553E+09 | 0.00 | 0.00 |
February | 0.345598E+10 | 0.153215E+10 | 0.303846E+10 | 0.241591E+10 | 0.622550E+09 | 0.00 | 0.00 |
March | 0.290753E+10 | 0.134405E+10 | 0.252694E+10 | 0.167006E+10 | 0.856880E+09 | 0.00 | 0.00 |
April | 0.169506E+10 | 0.115919E+10 | 0.160126E+10 | 0.662442E+09 | 0.938820E+09 | 0.00 | 0.00 |
May | 0.177082E+10 | 0.690844E+09 | 0.150356E+10 | 0.289137E+09 | 0.121442E+10 | 0.00 | 0.00 |
June | 0.192990E+10 | 0.360960E+09 | 0.132290E+10 | 0.238808E+09 | 0.108409E+10 | 0.00 | 0.00 |
July | 0.206855E+10 | 0.332603E+09 | 0.141194E+10 | 0.240535E+09 | 0.117141E+10 | 0.00 | 0.00 |
August | 0.262689E+10 | 0.390291E+09 | 0.179651E+10 | 0.739105E+09 | 0.105741E+10 | 0.00 | 0.00 |
September | 0.311760E+10 | 0.595773E+09 | 0.228374E+10 | 0.128369E+10 | 0.100006E+10 | 0.00 | 0.00 |
October | 0.338762E+10 | 0.130897E+10 | 0.278564E+10 | 0.197372E+10 | 0.811921E+09 | 0.00 | 0.00 |
November | 0.389002E+10 | 0.147049E+10 | 0.330425E+10 | 0.263556E+10 | 0.668687E+09 | 0.00 | 0.00 |
December | 0.365894E+10 | 0.184384E+10 | 0.325847E+10 | 0.263783E+10 | 0.620648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345878E+11 | 0.126504E+11 | 0.283888E+11 | 0.177134E+11 | 0.106754E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169506E+10 | 0.332603E+09 | 0.132290E+10 | 0.238808E+09 | 0.620648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.407892E+10 | 0.184384E+10 | 0.355512E+10 | 0.292657E+10 | 0.121442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113839E+11 | 0.481637E+10 | 0.100110E+11 | 0.824102E+10 | 0.176996E+10 | 0.00 | 0.00 |
February | 0.964320E+10 | 0.451943E+10 | 0.855611E+10 | 0.680305E+10 | 0.175306E+10 | 0.00 | 0.00 |
March | 0.809893E+10 | 0.399630E+10 | 0.711568E+10 | 0.470277E+10 | 0.241292E+10 | 0.00 | 0.00 |
April | 0.468418E+10 | 0.350086E+10 | 0.450905E+10 | 0.186539E+10 | 0.264366E+10 | 0.00 | 0.00 |
May | 0.485203E+10 | 0.214705E+10 | 0.423393E+10 | 0.814191E+09 | 0.341974E+10 | 0.00 | 0.00 |
June | 0.536736E+10 | 0.107496E+10 | 0.372520E+10 | 0.672467E+09 | 0.305273E+10 | 0.00 | 0.00 |
July | 0.575573E+10 | 0.998018E+09 | 0.397593E+10 | 0.677330E+09 | 0.329860E+10 | 0.00 | 0.00 |
August | 0.732782E+10 | 0.116479E+10 | 0.505886E+10 | 0.208127E+10 | 0.297759E+10 | 0.00 | 0.00 |
September | 0.871081E+10 | 0.176768E+10 | 0.643087E+10 | 0.361478E+10 | 0.281609E+10 | 0.00 | 0.00 |
October | 0.946417E+10 | 0.388429E+10 | 0.784417E+10 | 0.555786E+10 | 0.228632E+10 | 0.00 | 0.00 |
November | 0.108653E+11 | 0.436803E+10 | 0.930455E+10 | 0.742157E+10 | 0.188298E+10 | 0.00 | 0.00 |
December | 0.102082E+11 | 0.543605E+10 | 0.917565E+10 | 0.742794E+10 | 0.174770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.963617E+11 | 0.376738E+11 | 0.799410E+11 | 0.498796E+11 | 0.300613E+11 | 0.00 | 0.00 |
Minimum of Months | 0.468418E+10 | 0.998018E+09 | 0.372520E+10 | 0.672467E+09 | 0.174770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113839E+11 | 0.543605E+10 | 0.100110E+11 | 0.824102E+10 | 0.341974E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150007E+11 | 0.643879E+10 | 0.130048E+11 | 0.107055E+11 | 0.229928E+10 | 0.00 | 0.00 |
February | 0.127267E+11 | 0.606377E+10 | 0.111149E+11 | 0.883755E+10 | 0.227732E+10 | 0.00 | 0.00 |
March | 0.106953E+11 | 0.541345E+10 | 0.924368E+10 | 0.610916E+10 | 0.313452E+10 | 0.00 | 0.00 |
April | 0.618342E+10 | 0.480121E+10 | 0.585751E+10 | 0.242325E+10 | 0.343426E+10 | 0.00 | 0.00 |
May | 0.641392E+10 | 0.289632E+10 | 0.550012E+10 | 0.105768E+10 | 0.444243E+10 | 0.00 | 0.00 |
June | 0.713780E+10 | 0.142038E+10 | 0.483925E+10 | 0.873573E+09 | 0.396567E+10 | 0.00 | 0.00 |
July | 0.764958E+10 | 0.131667E+10 | 0.516496E+10 | 0.879891E+09 | 0.428507E+10 | 0.00 | 0.00 |
August | 0.971911E+10 | 0.152363E+10 | 0.657175E+10 | 0.270369E+10 | 0.386806E+10 | 0.00 | 0.00 |
September | 0.115228E+11 | 0.232115E+10 | 0.835407E+10 | 0.469580E+10 | 0.365826E+10 | 0.00 | 0.00 |
October | 0.124806E+11 | 0.522404E+10 | 0.101900E+11 | 0.721997E+10 | 0.297005E+10 | 0.00 | 0.00 |
November | 0.143229E+11 | 0.585600E+10 | 0.120871E+11 | 0.964104E+10 | 0.244610E+10 | 0.00 | 0.00 |
December | 0.134486E+11 | 0.730534E+10 | 0.119197E+11 | 0.964932E+10 | 0.227037E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127302E+12 | 0.505808E+11 | 0.103848E+12 | 0.647965E+11 | 0.390514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.618342E+10 | 0.131667E+10 | 0.483925E+10 | 0.873573E+09 | 0.227037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.150007E+11 | 0.730534E+10 | 0.130048E+11 | 0.107055E+11 | 0.444243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120171E+10 | 0.922260E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.112148E+10 | 0.876266E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.121110E+10 | 0.751206E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.898082E+09 | 0.646287E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.121684E+10 | 0.373143E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.162378E+10 | 0.163691E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.147248E+10 | 0.144201E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.160268E+10 | 0.170513E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.150327E+10 | 0.290417E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.129773E+10 | 0.728278E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.120098E+10 | 0.830454E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.100795E+10 | 0.106305E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153581E+11 | 0.695977E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.898082E+09 | 0.144201E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162378E+10 | 0.106305E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.442967E+09 | 0.976736E+09 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.477254E+09 | 0.910256E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.703405E+09 | 0.763982E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.654103E+09 | 0.644584E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.106334E+10 | 0.370211E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.153537E+10 | 0.167449E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.135399E+10 | 0.150947E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.130623E+10 | 0.181398E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104878E+10 | 0.305245E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.694423E+09 | 0.736452E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.472547E+09 | 0.853165E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.333124E+09 | 0.112604E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100855E+11 | 0.718647E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.333124E+09 | 0.150947E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153537E+10 | 0.112604E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.624422E+09 | 0.316807E+09 | 0.562215E+09 | 0.462814E+09 | 99401584.82 | 0.00 | 0.00 |
February | 0.529386E+09 | 0.287536E+09 | 0.480510E+09 | 0.382058E+09 | 98452499.34 | 0.00 | 0.00 |
March | 0.443099E+09 | 0.257646E+09 | 0.399617E+09 | 0.264106E+09 | 0.135510E+09 | 0.00 | 0.00 |
April | 0.250014E+09 | 0.238373E+09 | 0.253229E+09 | 0.104760E+09 | 0.148469E+09 | 0.00 | 0.00 |
May | 0.250734E+09 | 0.154731E+09 | 0.237778E+09 | 45724815.51 | 0.192054E+09 | 0.00 | 0.00 |
June | 0.283450E+09 | 82825256.58 | 0.209209E+09 | 37765624.19 | 0.171443E+09 | 0.00 | 0.00 |
July | 0.304775E+09 | 79107940.72 | 0.223289E+09 | 38038734.55 | 0.185251E+09 | 0.00 | 0.00 |
August | 0.394851E+09 | 90143615.31 | 0.284106E+09 | 0.116884E+09 | 0.167223E+09 | 0.00 | 0.00 |
September | 0.473839E+09 | 0.127909E+09 | 0.361158E+09 | 0.203005E+09 | 0.158153E+09 | 0.00 | 0.00 |
October | 0.519190E+09 | 0.260743E+09 | 0.440528E+09 | 0.312128E+09 | 0.128400E+09 | 0.00 | 0.00 |
November | 0.599205E+09 | 0.287533E+09 | 0.522542E+09 | 0.416794E+09 | 0.105749E+09 | 0.00 | 0.00 |
December | 0.562451E+09 | 0.344271E+09 | 0.515303E+09 | 0.417152E+09 | 98151340.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.523541E+10 | 0.252763E+10 | 0.448949E+10 | 0.280123E+10 | 0.168826E+10 | 0.00 | 0.00 |
Minimum of Months | 0.250014E+09 | 79107940.72 | 0.209209E+09 | 37765624.19 | 98151340.49 | 0.00 | 0.00 |
Maximum of Months | 0.624422E+09 | 0.344271E+09 | 0.562215E+09 | 0.462814E+09 | 0.192054E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12408198.11 | 0.294893E+09 | 58468616.74 | 0.00 | 58468616.74 | 0.00 | 0.00 |
February | 14026536.60 | 0.273927E+09 | 66376345.10 | 0.00 | 66376345.10 | 0.00 | 0.00 |
March | 49435409.84 | 0.224731E+09 | 0.100024E+09 | 5161.40 | 0.100019E+09 | 0.00 | 0.00 |
April | 71846604.99 | 0.186536E+09 | 0.121681E+09 | 797247.66 | 0.120884E+09 | 0.00 | 0.00 |
May | 0.171280E+09 | 99709424.77 | 0.171763E+09 | 5760607.25 | 0.166002E+09 | 0.00 | 0.00 |
June | 0.267572E+09 | 41578359.73 | 0.182244E+09 | 20379992.87 | 0.161864E+09 | 0.00 | 0.00 |
July | 0.266532E+09 | 37959497.52 | 0.178615E+09 | 12192357.35 | 0.166423E+09 | 0.00 | 0.00 |
August | 0.204941E+09 | 45597587.10 | 0.142211E+09 | 3848536.95 | 0.138363E+09 | 0.00 | 0.00 |
September | 0.147291E+09 | 80818812.77 | 0.115233E+09 | 92030.28 | 0.115141E+09 | 0.00 | 0.00 |
October | 54158222.31 | 0.210423E+09 | 85190674.52 | 0.00 | 85190674.52 | 0.00 | 0.00 |
November | 19723137.46 | 0.253397E+09 | 62584379.74 | 0.00 | 62584379.74 | 0.00 | 0.00 |
December | 9981825.51 | 0.341534E+09 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Annual Sum or Average | 0.128919E+10 | 0.209111E+10 | 0.133910E+10 | 43075933.76 | 0.129602E+10 | 0.00 | 0.00 |
Minimum of Months | 9981825.51 | 37959497.52 | 54704647.81 | 0.00 | 54704647.81 | 0.00 | 0.00 |
Maximum of Months | 0.267572E+09 | 0.341534E+09 | 0.182244E+09 | 20379992.87 | 0.166423E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115052E+10 | 0.912810E+09 | 0.112878E+10 | 0.839113E+09 | 0.289670E+09 | 0.00 | 0.00 |
February | 0.114110E+10 | 0.872961E+09 | 0.111643E+10 | 0.804030E+09 | 0.312396E+09 | 0.00 | 0.00 |
March | 0.126566E+10 | 0.746126E+09 | 0.118736E+10 | 0.731633E+09 | 0.455724E+09 | 0.00 | 0.00 |
April | 0.100687E+10 | 0.634329E+09 | 0.996011E+09 | 0.461883E+09 | 0.534128E+09 | 0.00 | 0.00 |
May | 0.130308E+10 | 0.352660E+09 | 0.112033E+10 | 0.401726E+09 | 0.718603E+09 | 0.00 | 0.00 |
June | 0.173710E+10 | 0.149460E+09 | 0.123075E+10 | 0.555877E+09 | 0.674870E+09 | 0.00 | 0.00 |
July | 0.170105E+10 | 0.136070E+09 | 0.118820E+10 | 0.479520E+09 | 0.708683E+09 | 0.00 | 0.00 |
August | 0.180336E+10 | 0.164722E+09 | 0.127437E+10 | 0.652543E+09 | 0.621823E+09 | 0.00 | 0.00 |
September | 0.159505E+10 | 0.277598E+09 | 0.119287E+10 | 0.656772E+09 | 0.536093E+09 | 0.00 | 0.00 |
October | 0.126281E+10 | 0.720662E+09 | 0.110511E+10 | 0.694257E+09 | 0.410849E+09 | 0.00 | 0.00 |
November | 0.114519E+10 | 0.825135E+09 | 0.106960E+10 | 0.755695E+09 | 0.313902E+09 | 0.00 | 0.00 |
December | 0.999846E+09 | 0.106464E+10 | 0.101733E+10 | 0.736528E+09 | 0.280804E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161116E+11 | 0.685717E+10 | 0.136271E+11 | 0.776958E+10 | 0.585754E+10 | 0.00 | 0.00 |
Minimum of Months | 0.999846E+09 | 0.136070E+09 | 0.996011E+09 | 0.401726E+09 | 0.280804E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180336E+10 | 0.106464E+10 | 0.127437E+10 | 0.839113E+09 | 0.718603E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.377460E+09 | 0.949680E+09 | 0.498951E+09 | 0.260481E+09 | 0.238470E+09 | 0.00 | 0.00 |
February | 0.488659E+09 | 0.898033E+09 | 0.598629E+09 | 0.326363E+09 | 0.272266E+09 | 0.00 | 0.00 |
March | 0.748441E+09 | 0.746915E+09 | 0.812750E+09 | 0.401441E+09 | 0.411310E+09 | 0.00 | 0.00 |
April | 0.762724E+09 | 0.630665E+09 | 0.831493E+09 | 0.331903E+09 | 0.499590E+09 | 0.00 | 0.00 |
May | 0.115872E+10 | 0.356031E+09 | 0.103772E+10 | 0.351759E+09 | 0.685964E+09 | 0.00 | 0.00 |
June | 0.164680E+10 | 0.161621E+09 | 0.119696E+10 | 0.534132E+09 | 0.662827E+09 | 0.00 | 0.00 |
July | 0.157990E+10 | 0.148303E+09 | 0.113227E+10 | 0.447200E+09 | 0.685075E+09 | 0.00 | 0.00 |
August | 0.150048E+10 | 0.177367E+09 | 0.109690E+10 | 0.511220E+09 | 0.585683E+09 | 0.00 | 0.00 |
September | 0.113631E+10 | 0.288357E+09 | 0.885350E+09 | 0.403080E+09 | 0.482270E+09 | 0.00 | 0.00 |
October | 0.652933E+09 | 0.719273E+09 | 0.660810E+09 | 0.304019E+09 | 0.356791E+09 | 0.00 | 0.00 |
November | 0.409974E+09 | 0.839168E+09 | 0.494509E+09 | 0.234599E+09 | 0.259910E+09 | 0.00 | 0.00 |
December | 0.309164E+09 | 0.110876E+10 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107716E+11 | 0.702417E+10 | 0.968780E+10 | 0.432118E+10 | 0.536662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.309164E+09 | 0.148303E+09 | 0.441447E+09 | 0.214985E+09 | 0.226462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164680E+10 | 0.110876E+10 | 0.119696E+10 | 0.534132E+09 | 0.685964E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136384E+10 | 0.115770E+10 | 0.134483E+10 | 0.100279E+10 | 0.342038E+09 | 0.00 | 0.00 |
February | 0.117225E+10 | 0.111054E+10 | 0.118493E+10 | 0.827813E+09 | 0.357113E+09 | 0.00 | 0.00 |
March | 0.109756E+10 | 0.983443E+09 | 0.108254E+10 | 0.572256E+09 | 0.510288E+09 | 0.00 | 0.00 |
April | 0.741861E+09 | 0.840789E+09 | 0.812278E+09 | 0.228713E+09 | 0.583564E+09 | 0.00 | 0.00 |
May | 0.971264E+09 | 0.485275E+09 | 0.887296E+09 | 0.111552E+09 | 0.775744E+09 | 0.00 | 0.00 |
June | 0.122093E+10 | 0.235182E+09 | 0.848098E+09 | 0.125978E+09 | 0.722120E+09 | 0.00 | 0.00 |
July | 0.126660E+10 | 0.224328E+09 | 0.870747E+09 | 0.108832E+09 | 0.761915E+09 | 0.00 | 0.00 |
August | 0.133007E+10 | 0.268249E+09 | 0.923657E+09 | 0.261592E+09 | 0.662065E+09 | 0.00 | 0.00 |
September | 0.137926E+10 | 0.423668E+09 | 0.103216E+10 | 0.440055E+09 | 0.592107E+09 | 0.00 | 0.00 |
October | 0.126989E+10 | 0.957567E+09 | 0.113905E+10 | 0.676295E+09 | 0.462759E+09 | 0.00 | 0.00 |
November | 0.134978E+10 | 0.105363E+10 | 0.126778E+10 | 0.903077E+09 | 0.364706E+09 | 0.00 | 0.00 |
December | 0.120530E+10 | 0.134136E+10 | 0.123503E+10 | 0.903852E+09 | 0.331175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143686E+11 | 0.908173E+10 | 0.126284E+11 | 0.616280E+10 | 0.646559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.741861E+09 | 0.224328E+09 | 0.812278E+09 | 0.108832E+09 | 0.331175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137926E+10 | 0.134136E+10 | 0.134483E+10 | 0.100279E+10 | 0.775744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120014E+10 | 0.915900E+09 | 0.115782E+10 | 0.866936E+09 | 0.290881E+09 | 0.00 | 0.00 |
February | 0.111649E+10 | 0.874164E+09 | 0.109713E+10 | 0.785573E+09 | 0.311553E+09 | 0.00 | 0.00 |
March | 0.120500E+10 | 0.746890E+09 | 0.114049E+10 | 0.683221E+09 | 0.457271E+09 | 0.00 | 0.00 |
April | 0.892345E+09 | 0.642542E+09 | 0.901570E+09 | 0.378772E+09 | 0.522798E+09 | 0.00 | 0.00 |
May | 0.120903E+10 | 0.370197E+09 | 0.103634E+10 | 0.318183E+09 | 0.718156E+09 | 0.00 | 0.00 |
June | 0.161585E+10 | 0.159749E+09 | 0.113474E+10 | 0.466997E+09 | 0.667743E+09 | 0.00 | 0.00 |
July | 0.146609E+10 | 0.139802E+09 | 0.101351E+10 | 0.315680E+09 | 0.697834E+09 | 0.00 | 0.00 |
August | 0.159479E+10 | 0.165965E+09 | 0.112418E+10 | 0.526138E+09 | 0.598038E+09 | 0.00 | 0.00 |
September | 0.149769E+10 | 0.284310E+09 | 0.111365E+10 | 0.572357E+09 | 0.541296E+09 | 0.00 | 0.00 |
October | 0.129346E+10 | 0.721643E+09 | 0.112371E+10 | 0.717715E+09 | 0.405998E+09 | 0.00 | 0.00 |
November | 0.119703E+10 | 0.825418E+09 | 0.110860E+10 | 0.797619E+09 | 0.310977E+09 | 0.00 | 0.00 |
December | 0.100553E+10 | 0.105970E+10 | 0.102369E+10 | 0.745592E+09 | 0.278098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152934E+11 | 0.690628E+10 | 0.129754E+11 | 0.717478E+10 | 0.580064E+10 | 0.00 | 0.00 |
Minimum of Months | 0.892345E+09 | 0.139802E+09 | 0.901570E+09 | 0.315680E+09 | 0.278098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161585E+10 | 0.105970E+10 | 0.115782E+10 | 0.866936E+09 | 0.718156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.445412E+09 | 0.966659E+09 | 0.527984E+09 | 0.288304E+09 | 0.239680E+09 | 0.00 | 0.00 |
February | 0.476824E+09 | 0.905817E+09 | 0.579329E+09 | 0.307906E+09 | 0.271423E+09 | 0.00 | 0.00 |
March | 0.700521E+09 | 0.759455E+09 | 0.765886E+09 | 0.353029E+09 | 0.412856E+09 | 0.00 | 0.00 |
April | 0.649595E+09 | 0.641536E+09 | 0.737052E+09 | 0.248792E+09 | 0.488260E+09 | 0.00 | 0.00 |
May | 0.105461E+10 | 0.369716E+09 | 0.953732E+09 | 0.268215E+09 | 0.685517E+09 | 0.00 | 0.00 |
June | 0.152785E+10 | 0.165837E+09 | 0.110095E+10 | 0.445253E+09 | 0.655699E+09 | 0.00 | 0.00 |
July | 0.134834E+10 | 0.148687E+09 | 0.957587E+09 | 0.283361E+09 | 0.674226E+09 | 0.00 | 0.00 |
August | 0.129991E+10 | 0.178866E+09 | 0.946712E+09 | 0.384815E+09 | 0.561898E+09 | 0.00 | 0.00 |
September | 0.104599E+10 | 0.300719E+09 | 0.806137E+09 | 0.318665E+09 | 0.487473E+09 | 0.00 | 0.00 |
October | 0.693566E+09 | 0.729218E+09 | 0.679417E+09 | 0.327477E+09 | 0.351940E+09 | 0.00 | 0.00 |
November | 0.473024E+09 | 0.845429E+09 | 0.533508E+09 | 0.276523E+09 | 0.256986E+09 | 0.00 | 0.00 |
December | 0.334755E+09 | 0.112017E+10 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100504E+11 | 0.713211E+10 | 0.903610E+10 | 0.372639E+10 | 0.530971E+10 | 0.00 | 0.00 |
Minimum of Months | 0.334755E+09 | 0.148687E+09 | 0.447805E+09 | 0.224048E+09 | 0.223756E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152785E+10 | 0.112017E+10 | 0.110095E+10 | 0.445253E+09 | 0.685517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117892E+10 | 0.478248E+09 | 0.103088E+10 | 0.848620E+09 | 0.182264E+09 | 0.00 | 0.00 |
February | 0.993977E+09 | 0.457721E+09 | 0.881068E+09 | 0.700545E+09 | 0.180523E+09 | 0.00 | 0.00 |
March | 0.838688E+09 | 0.394447E+09 | 0.732741E+09 | 0.484268E+09 | 0.248473E+09 | 0.00 | 0.00 |
April | 0.487001E+09 | 0.342907E+09 | 0.464323E+09 | 0.192089E+09 | 0.272233E+09 | 0.00 | 0.00 |
May | 0.516523E+09 | 0.193335E+09 | 0.435993E+09 | 83841458.20 | 0.352151E+09 | 0.00 | 0.00 |
June | 0.587051E+09 | 77726514.31 | 0.383607E+09 | 69247409.02 | 0.314360E+09 | 0.00 | 0.00 |
July | 0.628912E+09 | 68708825.17 | 0.409426E+09 | 69748186.78 | 0.339677E+09 | 0.00 | 0.00 |
August | 0.784805E+09 | 83168175.92 | 0.520940E+09 | 0.214319E+09 | 0.306621E+09 | 0.00 | 0.00 |
September | 0.919206E+09 | 0.145251E+09 | 0.662223E+09 | 0.372232E+09 | 0.289990E+09 | 0.00 | 0.00 |
October | 0.984963E+09 | 0.376158E+09 | 0.807757E+09 | 0.572321E+09 | 0.235436E+09 | 0.00 | 0.00 |
November | 0.112501E+10 | 0.433321E+09 | 0.958139E+09 | 0.764237E+09 | 0.193901E+09 | 0.00 | 0.00 |
December | 0.104808E+10 | 0.555854E+09 | 0.944865E+09 | 0.764893E+09 | 0.179971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100931E+11 | 0.360685E+10 | 0.823196E+10 | 0.513636E+10 | 0.309560E+10 | 0.00 | 0.00 |
Minimum of Months | 0.487001E+09 | 68708825.17 | 0.383607E+09 | 69247409.02 | 0.179971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117892E+10 | 0.555854E+09 | 0.103088E+10 | 0.848620E+09 | 0.352151E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 67908257.07 | 0.293181E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 74921344.65 | 0.273103E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.332496E+09 | 0.228112E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.514916E+09 | 0.191712E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.132595E+10 | 0.104062E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.217612E+10 | 0.478998E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.217098E+10 | 0.457141E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.163845E+10 | 0.541026E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.115898E+10 | 0.878637E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.377471E+09 | 0.213885E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.117450E+09 | 0.255062E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 54097466.30 | 0.336718E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100098E+11 | 0.213141E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 54097466.30 | 0.457141E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217612E+10 | 0.336718E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59990541.84 | 0.299818E+10 | 0.511513E+09 | 0.00 | 0.511513E+09 | 0.00 | 0.00 |
February | 67687771.57 | 0.279376E+10 | 0.580694E+09 | 0.00 | 0.580694E+09 | 0.00 | 0.00 |
March | 0.314394E+09 | 0.233296E+10 | 0.875064E+09 | 45154.60 | 0.875019E+09 | 0.00 | 0.00 |
April | 0.493482E+09 | 0.196205E+10 | 0.106453E+10 | 6974728.30 | 0.105755E+10 | 0.00 | 0.00 |
May | 0.130081E+10 | 0.106185E+10 | 0.150267E+10 | 50396724.07 | 0.145227E+10 | 0.00 | 0.00 |
June | 0.215706E+10 | 0.491097E+09 | 0.159436E+10 | 0.178295E+09 | 0.141606E+10 | 0.00 | 0.00 |
July | 0.215195E+10 | 0.470046E+09 | 0.156262E+10 | 0.106665E+09 | 0.145595E+10 | 0.00 | 0.00 |
August | 0.162100E+10 | 0.555893E+09 | 0.124413E+10 | 33668959.93 | 0.121047E+10 | 0.00 | 0.00 |
September | 0.114295E+10 | 0.898124E+09 | 0.100812E+10 | 805127.75 | 0.100731E+10 | 0.00 | 0.00 |
October | 0.362320E+09 | 0.218175E+10 | 0.745291E+09 | 0.00 | 0.745291E+09 | 0.00 | 0.00 |
November | 0.108959E+09 | 0.260909E+10 | 0.547520E+09 | 0.00 | 0.547520E+09 | 0.00 | 0.00 |
December | 48179103.90 | 0.344484E+10 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.982878E+10 | 0.217996E+11 | 0.117151E+11 | 0.376850E+09 | 0.113382E+11 | 0.00 | 0.00 |
Minimum of Months | 48179103.90 | 0.470046E+09 | 0.478584E+09 | 0.00 | 0.478584E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215706E+10 | 0.344484E+10 | 0.159436E+10 | 0.178295E+09 | 0.145595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161609E+10 | 0.184228E+10 | 0.162767E+10 | 0.109956E+10 | 0.528117E+09 | 0.00 | 0.00 |
February | 0.170868E+10 | 0.179771E+10 | 0.171498E+10 | 0.113035E+10 | 0.584635E+09 | 0.00 | 0.00 |
March | 0.216393E+10 | 0.156161E+10 | 0.200001E+10 | 0.113302E+10 | 0.866993E+09 | 0.00 | 0.00 |
April | 0.192014E+10 | 0.135816E+10 | 0.182741E+10 | 0.793739E+09 | 0.103367E+10 | 0.00 | 0.00 |
May | 0.275806E+10 | 0.792097E+09 | 0.215794E+10 | 0.753436E+09 | 0.140450E+10 | 0.00 | 0.00 |
June | 0.376817E+10 | 0.384922E+09 | 0.242757E+10 | 0.108994E+10 | 0.133763E+10 | 0.00 | 0.00 |
July | 0.367474E+10 | 0.365855E+09 | 0.232035E+10 | 0.926658E+09 | 0.139369E+10 | 0.00 | 0.00 |
August | 0.369145E+10 | 0.410125E+09 | 0.237114E+10 | 0.116369E+10 | 0.120745E+10 | 0.00 | 0.00 |
September | 0.305249E+10 | 0.616397E+09 | 0.207811E+10 | 0.105980E+10 | 0.101831E+10 | 0.00 | 0.00 |
October | 0.209349E+10 | 0.148089E+10 | 0.176584E+10 | 0.998232E+09 | 0.767605E+09 | 0.00 | 0.00 |
November | 0.166056E+10 | 0.167261E+10 | 0.156405E+10 | 0.990260E+09 | 0.573786E+09 | 0.00 | 0.00 |
December | 0.135082E+10 | 0.220034E+10 | 0.145873E+10 | 0.951482E+09 | 0.507244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294586E+11 | 0.144830E+11 | 0.233138E+11 | 0.120902E+11 | 0.112236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135082E+10 | 0.365855E+09 | 0.145873E+10 | 0.753436E+09 | 0.507244E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376817E+10 | 0.220034E+10 | 0.242757E+10 | 0.116369E+10 | 0.140450E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294729E+10 | 0.204047E+10 | 0.279952E+10 | 0.216021E+10 | 0.639310E+09 | 0.00 | 0.00 |
February | 0.250862E+10 | 0.197147E+10 | 0.244187E+10 | 0.178327E+10 | 0.658595E+09 | 0.00 | 0.00 |
March | 0.225599E+10 | 0.174659E+10 | 0.216521E+10 | 0.123275E+10 | 0.932460E+09 | 0.00 | 0.00 |
April | 0.144134E+10 | 0.151312E+10 | 0.154688E+10 | 0.491364E+09 | 0.105551E+10 | 0.00 | 0.00 |
May | 0.176569E+10 | 0.882884E+09 | 0.162496E+10 | 0.230699E+09 | 0.139426E+10 | 0.00 | 0.00 |
June | 0.216120E+10 | 0.431099E+09 | 0.152304E+10 | 0.237393E+09 | 0.128565E+10 | 0.00 | 0.00 |
July | 0.226733E+10 | 0.409117E+09 | 0.157788E+10 | 0.214113E+09 | 0.136377E+10 | 0.00 | 0.00 |
August | 0.250480E+10 | 0.484664E+09 | 0.175257E+10 | 0.557102E+09 | 0.119547E+10 | 0.00 | 0.00 |
September | 0.271269E+10 | 0.744342E+09 | 0.203131E+10 | 0.947814E+09 | 0.108349E+10 | 0.00 | 0.00 |
October | 0.263616E+10 | 0.168269E+10 | 0.231168E+10 | 0.145687E+10 | 0.854802E+09 | 0.00 | 0.00 |
November | 0.287391E+10 | 0.186606E+10 | 0.262668E+10 | 0.194541E+10 | 0.681277E+09 | 0.00 | 0.00 |
December | 0.260393E+10 | 0.238527E+10 | 0.256926E+10 | 0.194708E+10 | 0.622186E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286790E+11 | 0.161578E+11 | 0.249709E+11 | 0.132041E+11 | 0.117668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144134E+10 | 0.409117E+09 | 0.152304E+10 | 0.214113E+09 | 0.622186E+09 | 0.00 | 0.00 |
Maximum of Months | 0.294729E+10 | 0.238527E+10 | 0.279952E+10 | 0.216021E+10 | 0.139426E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770470E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161907146.3 | 81.21 | 0.00 | 0.00 |
February | 0.696226E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146289587.0 | 81.21 | 0.00 | 0.00 |
March | 0.770326E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161798652.3 | 81.21 | 0.00 | 0.00 |
April | 0.746512E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156537049.0 | 81.21 | 0.00 | 0.00 |
May | 0.770433E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161545696.5 | 81.21 | 0.00 | 0.00 |
June | 0.745675E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156217053.5 | 81.21 | 0.00 | 0.00 |
July | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161421521.2 | 81.21 | 0.00 | 0.00 |
August | 0.770423E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161421938.2 | 81.21 | 0.00 | 0.00 |
September | 0.746619E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156259234.5 | 81.21 | 0.00 | 0.00 |
October | 0.770313E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161695732.8 | 81.21 | 0.00 | 0.00 |
November | 0.744907E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156637558.9 | 81.21 | 0.00 | 0.00 |
December | 0.771290E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162043296.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907442E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190377E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696226E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162043296.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771290E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146289587.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.708593E+11 | -0.121775E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -882033270.7 | 81.67 | 0.00 | 0.00 |
February | 0.668284E+11 | -0.110948E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -804533493.8 | 81.67 | 0.00 | 0.00 |
March | 0.662887E+11 | -0.121560E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -852206695.2 | 81.67 | 0.00 | 0.00 |
April | 0.583887E+11 | -0.114382E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -815033966.7 | 81.67 | 0.00 | 0.00 |
May | 0.467872E+11 | -0.113619E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -783784211.3 | 81.67 | 0.00 | 0.00 |
June | 0.322562E+11 | -0.105552E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -694864199.6 | 81.68 | 0.00 | 0.00 |
July | 0.295255E+11 | -0.105779E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -714318814.2 | 81.68 | 0.00 | 0.00 |
August | 0.292795E+11 | -0.104622E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -721795285.4 | 81.68 | 0.00 | 0.00 |
September | 0.341152E+11 | -0.102528E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -722639080.2 | 81.68 | 0.00 | 0.00 |
October | 0.510472E+11 | -0.109372E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -834873986.9 | 81.67 | 0.00 | 0.00 |
November | 0.582076E+11 | -0.110288E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -837954064.3 | 81.67 | 0.00 | 0.00 |
December | 0.714278E+11 | -0.118489E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -896942168.1 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.615011E+12 | -0.133891E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.956098E+10 | 81.67 | 0.00 | 0.00 |
Minimum of Months | 0.292795E+11 | -0.121775E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -896942168.1 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.714278E+11 | -0.102528E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -694864199.6 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -924099523.7 | -0.749936E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.144395E+10 | 59.15 | 0.00 | 0.00 |
February | -203123086.2 | -0.685702E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.132086E+10 | 59.06 | 0.00 | 0.00 |
March | -0.144419E+10 | -0.749418E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137148E+10 | 59.13 | 0.00 | 0.00 |
April | -0.184197E+10 | -0.697026E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.130611E+10 | 59.21 | 0.00 | 0.00 |
May | -0.253101E+10 | -0.681420E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.121143E+10 | 59.29 | 0.00 | 0.00 |
June | -0.268930E+10 | -0.621855E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.102030E+10 | 59.32 | 0.00 | 0.00 |
July | -0.263282E+10 | -0.613578E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104660E+10 | 59.36 | 0.00 | 0.00 |
August | -0.251030E+10 | -0.604213E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.106501E+10 | 59.37 | 0.00 | 0.00 |
September | -0.238532E+10 | -0.595422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.108792E+10 | 59.35 | 0.00 | 0.00 |
October | -0.188618E+10 | -0.644183E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.133514E+10 | 59.31 | 0.00 | 0.00 |
November | -0.148699E+10 | -0.661332E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.136224E+10 | 59.24 | 0.00 | 0.00 |
December | -272780953.0 | -0.721405E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147919E+10 | 59.12 | 0.00 | 0.00 |
Annual Sum or Average | -0.208081E+11 | -0.802549E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.150502E+11 | 59.24 | 0.00 | 0.00 |
Minimum of Months | -0.268930E+10 | -0.749936E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.147919E+10 | 59.06 | 0.00 | 0.00 |
Maximum of Months | -203123086.2 | -0.595422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102030E+10 | 59.37 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.87 | 0.86 | 01-JAN-07:49 | 8556.16 | 39.57 | 274.00 | 269.00 | 3259.12 | 33.58 | 227.00 | 257.50 |
February | 245.50 | 0.86 | 0.86 | 01-FEB-10:39 | 11661.86 | 38.95 | 238.17 | 264.33 | 988.76 | 25.83 | 152.83 | 230.50 |
March | 296.17 | 0.87 | 0.86 | 01-MAR-06:00 | 4160.48 | 25.50 | 122.83 | 329.67 | 600.28 | 22.14 | 202.33 | 261.17 |
April | 296.67 | 0.87 | 0.86 | 03-APR-09:39 | 1325.88 | 20.15 | 54.83 | 340.17 | 532.61 | 21.86 | 209.50 | 266.67 |
May | 415.33 | 0.87 | 0.86 | 01-MAY-06:30 | 1252.13 | 19.78 | 58.83 | 391.50 | 490.68 | 21.50 | 275.00 | 328.83 |
June | 421.50 | 0.87 | 0.86 | 01-JUN-06:10 | 964.86 | 19.83 | 18.50 | 391.67 | 405.95 | 21.61 | 289.83 | 312.67 |
July | 430.33 | 0.87 | 0.86 | 01-JUL-08:09 | 1120.98 | 19.66 | 38.33 | 394.83 | 448.08 | 21.41 | 271.17 | 323.67 |
August | 394.50 | 0.87 | 0.86 | 01-AUG-06:19 | 1119.02 | 19.91 | 56.50 | 371.33 | 467.23 | 21.65 | 275.33 | 305.67 |
September | 354.00 | 0.87 | 0.86 | 01-SEP-06:00 | 1386.75 | 20.16 | 63.67 | 333.00 | 570.02 | 21.95 | 248.50 | 284.33 |
October | 262.67 | 0.87 | 0.86 | 01-OCT-06:49 | 9141.27 | 34.89 | 221.33 | 300.17 | 763.56 | 23.82 | 224.83 | 250.00 |
November | 257.67 | 0.87 | 0.86 | 01-NOV-08:39 | 9878.56 | 39.45 | 254.00 | 265.33 | 1800.09 | 30.04 | 195.50 | 238.17 |
December | 251.17 | 0.86 | 0.86 | 01-DEC-07:40 | 7930.33 | 39.98 | 250.83 | 258.50 | 4855.28 | 38.09 | 236.00 | 241.67 |
Annual Sum or Average | 3902.00 | 0.87 | 4134.83 | 26.51 | 1651.83 | 3909.50 | 1106.45 | 24.55 | 2807.83 | 3300.83 | ||
Minimum of Months | 245.50 | 0.86 | 0.86 | 964.86 | 19.66 | 18.50 | 258.50 | 405.95 | 21.41 | 152.83 | 230.50 | |
Maximum of Months | 430.33 | 0.87 | 0.86 | 11661.86 | 39.98 | 274.00 | 394.83 | 4855.28 | 38.09 | 289.83 | 328.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.24 | 0.22 | 01-JAN-07:40 | 9151.56 | 39.63 | 274.00 | 275.17 | 3853.94 | 33.18 | 222.83 | 267.50 |
February | 245.50 | 0.23 | 0.22 | 01-FEB-10:39 | 12257.64 | 39.03 | 238.17 | 271.50 | 1583.34 | 25.08 | 121.33 | 252.67 |
March | 296.17 | 0.24 | 0.22 | 01-MAR-06:00 | 4590.56 | 25.52 | 123.50 | 338.50 | 1029.03 | 21.93 | 170.67 | 307.00 |
April | 296.67 | 0.26 | 0.22 | 03-APR-09:39 | 1610.91 | 20.51 | 80.17 | 351.50 | 816.79 | 22.07 | 208.17 | 317.83 |
May | 415.33 | 0.26 | 0.22 | 01-MAY-05:00 | 1463.01 | 20.40 | 139.33 | 404.17 | 700.81 | 21.93 | 306.83 | 372.17 |
June | 421.50 | 0.26 | 0.22 | 01-JUN-05:40 | 1155.36 | 20.46 | 100.33 | 408.50 | 595.90 | 22.03 | 318.33 | 368.67 |
July | 430.33 | 0.26 | 0.22 | 01-JUL-05:00 | 1316.87 | 20.31 | 123.17 | 413.67 | 643.30 | 21.86 | 306.67 | 372.83 |
August | 394.50 | 0.26 | 0.22 | 01-AUG-05:00 | 1377.73 | 20.31 | 91.33 | 381.00 | 725.28 | 21.89 | 275.50 | 351.33 |
September | 354.00 | 0.25 | 0.22 | 01-SEP-06:19 | 1733.36 | 20.32 | 91.17 | 345.67 | 915.74 | 21.96 | 231.17 | 316.83 |
October | 262.67 | 0.24 | 0.22 | 01-OCT-06:40 | 9666.63 | 34.86 | 217.50 | 308.67 | 1287.31 | 23.41 | 172.67 | 286.17 |
November | 257.67 | 0.24 | 0.22 | 01-NOV-08:39 | 10491.31 | 39.51 | 254.00 | 272.67 | 2410.42 | 29.40 | 174.33 | 255.33 |
December | 251.17 | 0.24 | 0.22 | 01-DEC-07:40 | 8531.88 | 40.03 | 250.83 | 263.50 | 5455.23 | 37.95 | 230.50 | 256.00 |
Annual Sum or Average | 3902.00 | 0.25 | 4505.60 | 26.81 | 1983.50 | 4034.50 | 1476.21 | 24.56 | 2739.00 | 3724.33 | ||
Minimum of Months | 245.50 | 0.23 | 0.22 | 1155.36 | 20.31 | 80.17 | 263.50 | 595.90 | 21.86 | 121.33 | 252.67 | |
Maximum of Months | 430.33 | 0.26 | 0.22 | 12257.64 | 40.03 | 274.00 | 413.67 | 5455.23 | 37.95 | 318.33 | 372.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.68 | 0.60 | 01-JAN-09:00 | 317.44 | 13.89 | 0.00 | 213.50 | 167.40 | 17.59 | 0.00 | 77.83 |
February | 245.50 | 0.64 | 0.60 | 01-FEB-10:39 | 358.97 | 15.24 | 0.00 | 247.83 | 194.41 | 18.86 | 0.17 | 66.33 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 495.42 | 16.52 | 0.00 | 325.17 | 247.76 | 19.88 | 9.17 | 226.83 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 701.12 | 17.68 | 0.00 | 352.17 | 319.31 | 20.86 | 76.67 | 289.17 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-05:00 | 894.17 | 18.01 | 0.00 | 410.67 | 377.99 | 21.67 | 211.33 | 380.67 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 949.46 | 18.71 | 11.00 | 419.67 | 406.73 | 23.97 | 257.17 | 405.83 |
July | 430.33 | 0.61 | 0.60 | 01-JUL-04:00 | 923.57 | 18.15 | 1.83 | 424.00 | 389.65 | 22.55 | 231.33 | 395.67 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 694.73 | 17.67 | 0.00 | 387.83 | 315.04 | 20.92 | 120.83 | 343.83 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:19 | 555.48 | 16.93 | 0.00 | 336.50 | 270.53 | 20.21 | 26.00 | 259.33 |
October | 262.67 | 0.63 | 0.60 | 01-OCT-06:00 | 450.88 | 16.29 | 0.00 | 289.50 | 240.34 | 19.76 | 0.00 | 195.00 |
November | 257.67 | 0.65 | 0.60 | 01-NOV-08:50 | 350.02 | 14.70 | 0.00 | 237.00 | 190.46 | 18.36 | 0.00 | 85.83 |
December | 251.17 | 0.66 | 0.60 | 01-DEC-08:50 | 332.69 | 14.31 | 0.00 | 221.67 | 177.44 | 18.02 | 0.00 | 73.00 |
Annual Sum or Average | 3902.00 | 0.63 | 631.10 | 16.79 | 12.83 | 3865.50 | 290.89 | 20.56 | 932.67 | 2799.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 317.44 | 13.89 | 0.00 | 213.50 | 167.40 | 17.59 | 0.00 | 66.33 | |
Maximum of Months | 430.33 | 0.68 | 0.60 | 949.46 | 18.71 | 11.00 | 424.00 | 406.73 | 23.97 | 257.17 | 405.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.68 | 0.60 | 01-JAN-09:00 | 317.44 | 13.89 | 0.00 | 213.50 | 167.40 | 17.59 | 0.00 | 77.83 |
February | 245.50 | 0.64 | 0.60 | 01-FEB-10:39 | 358.97 | 15.24 | 0.00 | 247.83 | 194.41 | 18.86 | 0.17 | 66.33 |
March | 296.17 | 0.63 | 0.60 | 01-MAR-07:30 | 495.42 | 16.52 | 0.00 | 325.17 | 247.76 | 19.88 | 9.17 | 226.83 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 701.12 | 17.68 | 0.00 | 352.17 | 319.31 | 20.86 | 76.83 | 289.17 |
May | 415.33 | 0.62 | 0.60 | 01-MAY-05:00 | 894.17 | 18.01 | 0.00 | 410.67 | 377.99 | 21.67 | 211.33 | 380.67 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 949.46 | 18.71 | 11.00 | 419.67 | 406.73 | 23.97 | 257.17 | 405.83 |
July | 430.33 | 0.61 | 0.60 | 01-JUL-04:00 | 923.57 | 18.15 | 1.83 | 424.00 | 389.65 | 22.55 | 231.33 | 395.67 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 694.73 | 17.67 | 0.00 | 387.83 | 315.04 | 20.92 | 120.83 | 343.83 |
September | 354.00 | 0.63 | 0.60 | 01-SEP-06:19 | 555.48 | 16.93 | 0.00 | 336.50 | 270.53 | 20.21 | 26.00 | 259.33 |
October | 262.67 | 0.63 | 0.60 | 01-OCT-06:00 | 450.88 | 16.29 | 0.00 | 289.50 | 240.34 | 19.76 | 0.00 | 195.00 |
November | 257.67 | 0.65 | 0.60 | 01-NOV-08:50 | 350.02 | 14.70 | 0.00 | 237.00 | 190.46 | 18.36 | 0.00 | 85.83 |
December | 251.17 | 0.66 | 0.60 | 01-DEC-08:50 | 332.69 | 14.31 | 0.00 | 221.67 | 177.44 | 18.02 | 0.00 | 73.00 |
Annual Sum or Average | 3902.00 | 0.63 | 631.10 | 16.79 | 12.83 | 3865.50 | 290.89 | 20.56 | 932.83 | 2799.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 317.44 | 13.89 | 0.00 | 213.50 | 167.40 | 17.59 | 0.00 | 66.33 | |
Maximum of Months | 430.33 | 0.68 | 0.60 | 949.46 | 18.71 | 11.00 | 424.00 | 406.73 | 23.97 | 257.17 | 405.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.677892E+11 | 134672.14 | 15-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.682229E+11 | 137073.98 | 19-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636856E+11 | 139428.73 | 29-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.630459E+11 | 120348.57 | 04-APR-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.651365E+11 | 117458.80 | 08-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.466777E+10 | 101376.65 | 09-JUN-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.441652E+10 | 74708.23 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.447289E+10 | 54619.90 | 12-AUG-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.263313E+11 | 120240.11 | 21-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584325E+11 | 136952.46 | 22-OCT-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.528218E+11 | 132794.24 | 23-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.964374E+11 | 138849.29 | 21-DEC-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.441652E+10 | 54619.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.964374E+11 | 139428.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694904E+09 | 2273.41 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100246E+10 | 2132.31 | 05-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993629E+09 | 2230.40 | 19-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.947192E+09 | 1759.77 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96243864.97 | 846.36 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23242525.29 | 777.62 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687036E+09 | 2048.59 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663578E+09 | 1952.05 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132553E+10 | 3088.46 | 21-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132553E+10 | 3088.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1817867.17 | 155.03 | 05-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20115280.51 | 366.57 | 06-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6583314.67 | 265.47 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 829022.76 | 105.84 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6955563.21 | 299.23 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 534595.70 | 134.10 | 01-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27145616.68 | 507.71 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63981260.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27145616.68 | 507.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155427E+09 | 836.06 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326328E+09 | 798.49 | 06-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107101E+09 | 626.34 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66473423.68 | 556.01 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60743217.91 | 693.60 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117556E+09 | 650.14 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493752E+09 | 1242.50 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493752E+09 | 1242.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171776E+09 | 619.36 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314019E+09 | 588.78 | 06-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144544E+09 | 462.07 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89389974.72 | 396.17 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77822126.03 | 550.49 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120891E+09 | 482.60 | 30-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440478E+09 | 895.29 | 21-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440478E+09 | 895.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1324383.69 | 417.22 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1363528.59 | 327.00 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 56873.07 | 47.43 | 20-MAR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28952.17 | 48.25 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86415.91 | 95.77 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 400273.08 | 189.37 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15785153.37 | 937.25 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19045579.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15785153.37 | 937.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172744E+09 | 4978.14 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.493236E+09 | 4876.65 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.457234E+09 | 4092.56 | 19-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332802E+09 | 3803.85 | 03-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 752735.50 | 1083.36 | 02-MAY-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.457020E+09 | 4760.58 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181445E+09 | 4068.00 | 29-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.495512E+09 | 6880.03 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495512E+09 | 6880.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148498E+09 | 4665.14 | 06-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14761565.01 | 2430.29 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40643162.32 | 3564.38 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101262E+09 | 6148.59 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148498E+09 | 6148.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115343E+10 | 7163.88 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272840E+10 | 7814.28 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132170E+10 | 4562.88 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.945259E+09 | 5531.49 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4327593.22 | 1264.26 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104261E+10 | 7635.16 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120984E+10 | 6899.94 | 01-NOV-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386715E+10 | 10108.94 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386715E+10 | 10108.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189682E+10 | 4889.45 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234795E+10 | 4482.88 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159334E+10 | 3645.04 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107515E+10 | 3278.99 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52164060.51 | 1049.52 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105398E+10 | 3882.41 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145492E+10 | 4280.96 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362067E+10 | 6241.03 | 21-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362067E+10 | 6241.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164337E+10 | 8285.29 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176170E+10 | 6775.61 | 12-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704506E+09 | 5423.74 | 04-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.319628E+09 | 2462.60 | 03-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16367.27 | 0.36 | 16-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24906.53 | 0.36 | 18-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31248.98 | 0.36 | 30-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31215.27 | 0.36 | 12-AUG-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 948450.02 | 188.59 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505998E+09 | 5140.68 | 30-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820374E+09 | 5507.71 | 29-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308690E+10 | 8856.67 | 20-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16367.27 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.308690E+10 | 8856.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208450E+10 | 11042.98 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248331E+10 | 11043.10 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193177E+10 | 11042.55 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160178E+10 | 10992.49 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144549E+09 | 6669.01 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4313886.13 | 3097.76 | 05-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4901190.70 | 3359.79 | 15-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5105003.87 | 3761.80 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54388087.42 | 7322.57 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134198E+10 | 11042.82 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179825E+10 | 11043.50 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370892E+10 | 11041.38 | 19-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4313886.13 | 3097.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370892E+10 | 11043.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353672E+10 | 10990.98 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355226E+10 | 10991.08 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238269E+10 | 10990.57 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175695E+10 | 10940.72 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157978E+09 | 7198.48 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5016964.41 | 5640.51 | 10-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5699203.70 | 5140.08 | 08-JUL-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8231095.12 | 6093.85 | 02-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70125370.84 | 8040.44 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162367E+10 | 10990.78 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281102E+10 | 10991.45 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522906E+10 | 10990.89 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5016964.41 | 5140.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.522906E+10 | 10991.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136314E+11 | 61304.77 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145072E+11 | 60857.38 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.654067E+10 | 60372.73 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328252E+10 | 59594.14 | 02-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111933E+09 | 37230.32 | 10-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10048586.90 | 21215.09 | 17-JUN-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7446350.17 | 26952.38 | 13-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22314317.56 | 24126.49 | 17-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60752532.90 | 36512.90 | 27-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394208E+10 | 61098.26 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.942322E+10 | 60968.70 | 29-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204663E+11 | 61303.73 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7446350.17 | 21215.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204663E+11 | 61304.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222739E+10 | 10727.86 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263616E+10 | 10728.00 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191847E+10 | 10727.45 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156397E+10 | 10678.94 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137798E+09 | 4243.26 | 02-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 907731.41 | 2915.09 | 17-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1136858.12 | 2790.28 | 28-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1344503.81 | 3451.23 | 15-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48189166.58 | 5002.42 | 22-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136693E+10 | 10727.70 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193710E+10 | 10728.39 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379682E+10 | 10725.94 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 907731.41 | 2790.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379682E+10 | 10728.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367379E+10 | 10677.41 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365926E+10 | 10677.53 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231646E+10 | 10676.97 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173894E+10 | 10628.72 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151836E+09 | 5838.88 | 09-MAY-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1597396.38 | 3369.92 | 14-JUN-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1452503.75 | 2652.92 | 28-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1660840.40 | 3077.92 | 15-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63070289.81 | 5360.17 | 22-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166559E+10 | 10677.22 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.299124E+10 | 10677.96 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527983E+10 | 10675.42 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1452503.75 | 2652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527983E+10 | 10677.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.887233E+09 | 3349.97 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.969882E+09 | 3350.08 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769705E+09 | 3349.91 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647765E+09 | 3334.79 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89545506.73 | 2760.98 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1265328.51 | 1087.07 | 10-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1397080.50 | 1021.68 | 28-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1427125.91 | 926.83 | 02-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35131905.65 | 3260.25 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.577045E+09 | 3350.02 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.755074E+09 | 3350.12 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140127E+10 | 3349.55 | 19-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1265328.51 | 926.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140127E+10 | 3350.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137851E+10 | 3327.66 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132629E+10 | 3327.79 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.924481E+09 | 3327.69 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697543E+09 | 3312.62 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87396439.37 | 2830.21 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1472409.47 | 1627.08 | 14-JUN-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1657330.64 | 1430.40 | 02-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2412346.69 | 1726.49 | 18-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41039005.44 | 3243.28 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.699364E+09 | 3327.73 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111519E+10 | 3327.86 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188823E+10 | 3327.66 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.816357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1472409.47 | 1430.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188823E+10 | 3327.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168921E+10 | 15673.96 | 04-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261381E+10 | 15673.48 | 05-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238758E+10 | 15673.15 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214697E+10 | 15602.78 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236367E+09 | 7251.77 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11981487.91 | 7564.50 | 12-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10158227.75 | 7629.75 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8845377.95 | 4366.72 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72487815.08 | 8876.58 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169841E+10 | 15673.66 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166428E+10 | 15674.81 | 28-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348755E+10 | 15670.78 | 21-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8845377.95 | 4366.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348755E+10 | 15674.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.552645E+11 | 0.552645E+11 | 36499.35 | 31-JAN-13:15 | 36499.35 | 0.00 |
February | 0.00 | 0.00 | 0.494870E+11 | 0.494870E+11 | 34539.93 | 13-FEB-09:40 | 34539.93 | 0.00 |
March | 0.00 | 0.00 | 0.571029E+11 | 0.571029E+11 | 40662.05 | 01-MAR-08:55 | 40662.05 | 0.00 |
April | 0.00 | 0.00 | 0.538670E+11 | 0.538670E+11 | 51466.19 | 30-APR-23:05 | 51466.19 | 0.00 |
May | 0.00 | 0.00 | 0.550836E+11 | 0.550836E+11 | 51440.52 | 01-MAY-04:07 | 51440.52 | 0.00 |
June | 0.00 | 0.00 | 0.519701E+11 | 0.519701E+11 | 59922.39 | 01-JUN-06:52 | 59922.39 | 0.00 |
July | 0.00 | 0.00 | 0.510809E+11 | 0.510809E+11 | 59935.94 | 01-JUL-05:37 | 59935.94 | 0.00 |
August | 0.00 | 0.00 | 0.499677E+11 | 0.499677E+11 | 58661.28 | 31-AUG-06:15 | 58661.28 | 0.00 |
September | 0.00 | 0.00 | 0.483531E+11 | 0.483531E+11 | 54313.31 | 30-SEP-05:08 | 54313.31 | 0.00 |
October | 0.00 | 0.00 | 0.490022E+11 | 0.490022E+11 | 42506.53 | 31-OCT-17:13 | 42506.53 | 0.00 |
November | 0.00 | 0.00 | 0.491509E+11 | 0.491509E+11 | 38642.11 | 30-NOV-07:30 | 38642.11 | 0.00 |
December | 0.00 | 0.00 | 0.506870E+11 | 0.506870E+11 | 32524.19 | 31-DEC-02:10 | 32524.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.621017E+12 | 0.621017E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.483531E+11 | 0.483531E+11 | 32524.19 | 32524.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.571029E+11 | 0.571029E+11 | 59935.94 | 59935.94 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.367945E+11 | 0.367945E+11 | 46180.85 | 31-JAN-17:40 | 46180.85 | 0.00 |
February | 0.00 | 0.00 | 0.315378E+11 | 0.315378E+11 | 43699.76 | 13-FEB-17:10 | 43699.76 | 0.00 |
March | 0.00 | 0.00 | 0.409868E+11 | 0.409868E+11 | 51451.80 | 01-MAR-17:10 | 51451.80 | 0.00 |
April | 0.00 | 0.00 | 0.417712E+11 | 0.417712E+11 | 54394.27 | 01-APR-16:05 | 54394.27 | 0.00 |
May | 0.00 | 0.00 | 0.515300E+11 | 0.515300E+11 | 65099.89 | 01-MAY-16:10 | 65099.89 | 0.00 |
June | 0.00 | 0.00 | 0.580431E+11 | 0.580431E+11 | 75839.93 | 01-JUN-20:30 | 75839.93 | 0.00 |
July | 0.00 | 0.00 | 0.601298E+11 | 0.601298E+11 | 75857.10 | 01-JUL-16:40 | 75857.10 | 0.00 |
August | 0.00 | 0.00 | 0.590752E+11 | 0.590752E+11 | 74243.08 | 31-AUG-18:02 | 74243.08 | 0.00 |
September | 0.00 | 0.00 | 0.527665E+11 | 0.527665E+11 | 68737.51 | 30-SEP-16:10 | 68737.51 | 0.00 |
October | 0.00 | 0.00 | 0.426211E+11 | 0.426211E+11 | 53787.35 | 31-OCT-17:13 | 53787.35 | 0.00 |
November | 0.00 | 0.00 | 0.374922E+11 | 0.374922E+11 | 48894.08 | 30-NOV-17:30 | 48894.08 | 0.00 |
December | 0.00 | 0.00 | 0.327076E+11 | 0.327076E+11 | 41147.35 | 31-DEC-17:10 | 41147.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.545456E+12 | 0.545456E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.315378E+11 | 0.315378E+11 | 41147.35 | 41147.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.601298E+11 | 0.601298E+11 | 75857.10 | 75857.10 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.524877E+10 | 0.524877E+10 | 122125.75 | 20-JAN-13:00 | 122125.75 | 0.00 |
February | 0.00 | 0.00 | 0.292967E+10 | 0.292967E+10 | 111316.39 | 18-FEB-13:00 | 111316.39 | 0.00 |
March | 0.00 | 0.00 | 0.179758E+11 | 0.179758E+11 | 150135.01 | 14-MAR-13:00 | 150135.01 | 0.00 |
April | 0.00 | 0.00 | 0.187099E+11 | 0.187099E+11 | 105930.83 | 19-APR-10:50 | 105930.83 | 0.00 |
May | 0.00 | 0.00 | 0.872258E+11 | 0.872258E+11 | 198801.08 | 31-MAY-18:04 | 198801.08 | 0.04 |
June | 0.00 | 0.00 | 0.284455E+12 | 0.281651E+12 | 277260.42 | 26-JUN-18:03 | 277260.42 | 0.39 |
July | 0.00 | 0.00 | 0.325480E+12 | 0.310129E+12 | 264758.22 | 30-JUL-10:33 | 153448.27 | 0.47 |
August | 0.00 | 0.00 | 0.290742E+12 | 0.285411E+12 | 263634.77 | 16-AUG-18:03 | 263634.77 | 0.50 |
September | 0.00 | 0.00 | 0.201647E+12 | 0.201647E+12 | 231640.91 | 12-SEP-18:20 | 231640.91 | 0.10 |
October | 0.00 | 0.00 | 0.332039E+11 | 0.332039E+11 | 174884.76 | 11-OCT-15:10 | 174884.76 | 0.00 |
November | 0.00 | 0.00 | 0.106256E+11 | 0.106256E+11 | 134883.75 | 06-NOV-13:00 | 134883.75 | 0.00 |
December | 0.00 | 0.00 | 0.710187E+10 | 0.710187E+10 | 115794.83 | 02-DEC-13:00 | 115794.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128535E+13 | 0.126186E+13 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.292967E+10 | 0.292967E+10 | 105930.83 | 105930.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.325480E+12 | 0.310129E+12 | 277260.42 | 277260.42 | 0.50 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192282E+09 | 0.192282E+09 | 11112.34 | 20-JAN-14:00 | 11112.34 | 0.00 |
February | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.70 | 18-FEB-14:00 | 9344.70 | 0.00 |
March | 0.00 | 0.00 | 0.893177E+09 | 0.893177E+09 | 13509.75 | 13-MAR-15:01 | 13509.75 | 0.00 |
April | 0.00 | 0.00 | 0.105845E+10 | 0.105845E+10 | 12344.04 | 20-APR-13:00 | 12344.04 | 0.00 |
May | 0.00 | 0.00 | 0.511985E+10 | 0.511985E+10 | 15683.30 | 17-MAY-13:00 | 15683.30 | 0.03 |
June | 0.00 | 0.00 | 0.171378E+11 | 0.166872E+11 | 20243.38 | 18-JUN-08:54 | 12052.06 | 0.32 |
July | 0.00 | 0.00 | 0.208898E+11 | 0.190245E+11 | 26068.81 | 30-JUL-15:27 | 13795.85 | 0.40 |
August | 0.00 | 0.00 | 0.181610E+11 | 0.171216E+11 | 21107.72 | 05-AUG-15:08 | 9827.30 | 0.45 |
September | 0.00 | 0.00 | 0.117068E+11 | 0.117068E+11 | 16830.63 | 10-SEP-13:00 | 16830.63 | 0.09 |
October | 0.00 | 0.00 | 0.173134E+10 | 0.173134E+10 | 14668.04 | 11-OCT-15:01 | 14668.04 | 0.00 |
November | 0.00 | 0.00 | 0.497142E+09 | 0.497142E+09 | 12328.01 | 06-NOV-13:50 | 12328.01 | 0.00 |
December | 0.00 | 0.00 | 0.275114E+09 | 0.275114E+09 | 11662.93 | 01-DEC-14:00 | 11662.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.777862E+11 | 0.744310E+11 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.123483E+09 | 0.123483E+09 | 9344.70 | 9344.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208898E+11 | 0.190245E+11 | 26068.81 | 16830.63 | 0.45 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132532E+10 | 0.109856E+10 | 18135.30 | 23-JAN-16:01 | 18135.30 | 0.11 |
February | 0.00 | 0.00 | 0.139609E+10 | 0.124479E+10 | 18028.95 | 18-FEB-16:01 | 18028.95 | 0.08 |
March | 0.00 | 0.00 | 0.266399E+10 | 0.263282E+10 | 18847.95 | 13-MAR-15:01 | 18847.95 | 0.02 |
April | 0.00 | 0.00 | 0.179336E+10 | 0.162002E+10 | 18530.39 | 07-APR-15:01 | 18530.39 | 0.09 |
May | 0.00 | 0.00 | 0.439414E+10 | 0.318514E+10 | 19216.84 | 10-MAY-15:01 | 19216.84 | 0.46 |
June | 0.00 | 0.00 | 0.977833E+10 | 0.665523E+10 | 19500.04 | 07-JUN-15:01 | 19500.04 | 0.81 |
July | 0.00 | 0.00 | 0.952804E+10 | 0.598235E+10 | 19495.21 | 01-JUL-18:01 | 19495.21 | 0.84 |
August | 0.00 | 0.00 | 0.971260E+10 | 0.642349E+10 | 19503.64 | 18-AUG-15:01 | 19503.64 | 0.80 |
September | 0.00 | 0.00 | 0.765305E+10 | 0.602379E+10 | 19489.44 | 26-SEP-15:01 | 19489.44 | 0.47 |
October | 0.00 | 0.00 | 0.370220E+10 | 0.337751E+10 | 19352.93 | 11-OCT-15:01 | 19352.93 | 0.14 |
November | 0.00 | 0.00 | 0.178901E+10 | 0.140264E+10 | 18512.05 | 05-NOV-15:01 | 18512.05 | 0.18 |
December | 0.00 | 0.00 | 0.807624E+09 | 0.789101E+09 | 17990.78 | 02-DEC-16:01 | 17990.78 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.545438E+11 | 0.404354E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.807624E+09 | 0.789101E+09 | 17990.78 | 17990.78 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.977833E+10 | 0.665523E+10 | 19503.64 | 19503.64 | 0.84 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213146E+09 | 0.184373E+09 | 17666.20 | 23-JAN-16:01 | 17666.20 | 0.01 |
February | 0.00 | 0.00 | 0.315885E+09 | 0.288852E+09 | 17560.42 | 18-FEB-16:01 | 17560.42 | 0.01 |
March | 0.00 | 0.00 | 0.103043E+10 | 0.101651E+10 | 19533.13 | 15-MAR-18:31 | 19533.13 | 0.01 |
April | 0.00 | 0.00 | 0.860514E+09 | 0.747009E+09 | 19794.28 | 08-APR-18:01 | 19794.28 | 0.07 |
May | 0.00 | 0.00 | 0.303897E+10 | 0.198078E+10 | 19616.34 | 27-MAY-16:11 | 19616.34 | 0.40 |
June | 0.00 | 0.00 | 0.837136E+10 | 0.587820E+10 | 20287.38 | 27-JUN-08:51 | 20287.38 | 0.66 |
July | 0.00 | 0.00 | 0.780856E+10 | 0.502993E+10 | 21405.94 | 01-JUL-08:61 | 21405.94 | 0.66 |
August | 0.00 | 0.00 | 0.731677E+10 | 0.480662E+10 | 20494.24 | 05-AUG-08:51 | 14940.55 | 0.62 |
September | 0.00 | 0.00 | 0.473816E+10 | 0.347597E+10 | 19582.95 | 11-SEP-08:51 | 19582.95 | 0.37 |
October | 0.00 | 0.00 | 0.138938E+10 | 0.123228E+10 | 19028.70 | 14-OCT-16:11 | 19028.70 | 0.08 |
November | 0.00 | 0.00 | 0.347636E+09 | 0.290121E+09 | 18033.31 | 05-NOV-15:01 | 18033.31 | 0.04 |
December | 0.00 | 0.00 | 89981088.23 | 88231980.61 | 17525.30 | 02-DEC-16:01 | 17525.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.355208E+11 | 0.250189E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 89981088.23 | 88231980.61 | 17525.30 | 14940.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.837136E+10 | 0.587820E+10 | 21405.94 | 21405.94 | 0.66 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.340511E+11 | 0.340511E+11 | 69262.27 | 20-JAN-12:40 | 69262.27 | 0.00 |
February | 0.00 | 0.00 | 0.239549E+11 | 0.239549E+11 | 66293.56 | 18-FEB-13:00 | 66293.56 | 0.00 |
March | 0.00 | 0.00 | 0.241002E+11 | 0.241002E+11 | 60028.14 | 11-MAR-13:00 | 60028.14 | 0.00 |
April | 0.00 | 0.00 | 0.885509E+10 | 0.856980E+10 | 37061.14 | 08-APR-13:00 | 37061.14 | 0.02 |
May | 0.00 | 0.00 | 0.215258E+11 | 0.155049E+11 | 29045.21 | 05-MAY-13:10 | 29045.21 | 0.29 |
June | 0.00 | 0.00 | 0.416812E+11 | 0.215976E+11 | 34855.24 | 14-JUN-13:30 | 26311.71 | 0.85 |
July | 0.00 | 0.00 | 0.455196E+11 | 0.231954E+11 | 38544.79 | 23-JUL-12:50 | 29748.63 | 0.90 |
August | 0.00 | 0.00 | 0.520098E+11 | 0.329870E+11 | 48364.57 | 31-AUG-12:40 | 47813.96 | 0.81 |
September | 0.00 | 0.00 | 0.522749E+11 | 0.432437E+11 | 61664.90 | 28-SEP-13:00 | 61664.90 | 0.40 |
October | 0.00 | 0.00 | 0.383849E+11 | 0.373379E+11 | 65003.14 | 10-OCT-12:30 | 62267.44 | 0.05 |
November | 0.00 | 0.00 | 0.320176E+11 | 0.320176E+11 | 68853.58 | 07-NOV-12:20 | 68853.58 | 0.00 |
December | 0.00 | 0.00 | 0.207072E+11 | 0.207072E+11 | 62435.68 | 17-DEC-13:30 | 62435.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395082E+12 | 0.317267E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.885509E+10 | 0.856980E+10 | 29045.21 | 26311.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.522749E+11 | 0.432437E+11 | 69262.27 | 69262.27 | 0.90 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137844E+10 | 0.120292E+10 | 79969.52 | 21-JAN-09:01 | 79969.52 | 0.03 |
February | 0.00 | 0.00 | 0.132256E+10 | 0.117135E+10 | 80663.54 | 18-FEB-16:01 | 80663.54 | 0.03 |
March | 0.00 | 0.00 | 0.618218E+10 | 0.596902E+10 | 90193.12 | 14-MAR-15:01 | 90193.12 | 0.03 |
April | 0.00 | 0.00 | 0.902718E+10 | 0.731802E+10 | 88874.13 | 20-APR-15:01 | 88874.13 | 0.16 |
May | 0.00 | 0.00 | 0.284454E+11 | 0.233171E+11 | 94419.21 | 17-MAY-15:01 | 94419.21 | 0.30 |
June | 0.00 | 0.00 | 0.520100E+11 | 0.415015E+11 | 100570.87 | 30-JUN-07:41 | 100570.87 | 0.54 |
July | 0.00 | 0.00 | 0.534331E+11 | 0.409239E+11 | 102046.47 | 01-JUL-08:61 | 102046.47 | 0.57 |
August | 0.00 | 0.00 | 0.465686E+11 | 0.342803E+11 | 96071.19 | 05-AUG-08:51 | 77141.11 | 0.53 |
September | 0.00 | 0.00 | 0.314171E+11 | 0.269023E+11 | 95228.04 | 09-SEP-08:51 | 95228.04 | 0.26 |
October | 0.00 | 0.00 | 0.955957E+10 | 0.863193E+10 | 93604.61 | 11-OCT-15:01 | 93604.61 | 0.09 |
November | 0.00 | 0.00 | 0.270285E+10 | 0.229474E+10 | 83520.31 | 06-NOV-16:01 | 83520.31 | 0.06 |
December | 0.00 | 0.00 | 0.951667E+09 | 0.951667E+09 | 78898.25 | 02-DEC-16:01 | 78898.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242999E+12 | 0.194465E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.951667E+09 | 0.951667E+09 | 78898.25 | 77141.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.534331E+11 | 0.415015E+11 | 102046.47 | 102046.47 | 0.57 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128690E+10 | 0.110484E+10 | 15841.88 | 23-JAN-16:01 | 15841.88 | 0.11 |
February | 0.00 | 0.00 | 0.155289E+10 | 0.135426E+10 | 15748.02 | 18-FEB-16:01 | 15748.02 | 0.10 |
March | 0.00 | 0.00 | 0.284058E+10 | 0.276609E+10 | 16465.55 | 13-MAR-15:01 | 16465.55 | 0.03 |
April | 0.00 | 0.00 | 0.214905E+10 | 0.188459E+10 | 16188.13 | 07-APR-15:01 | 16188.13 | 0.14 |
May | 0.00 | 0.00 | 0.481674E+10 | 0.355845E+10 | 16773.97 | 04-MAY-15:01 | 16773.97 | 0.49 |
June | 0.00 | 0.00 | 0.103990E+11 | 0.738049E+10 | 17030.43 | 07-JUN-15:01 | 17030.43 | 0.84 |
July | 0.00 | 0.00 | 0.106624E+11 | 0.732551E+10 | 17026.78 | 01-JUL-18:01 | 17026.78 | 0.86 |
August | 0.00 | 0.00 | 0.107572E+11 | 0.758676E+10 | 17034.06 | 18-AUG-15:01 | 17034.06 | 0.82 |
September | 0.00 | 0.00 | 0.808545E+10 | 0.654617E+10 | 17021.79 | 26-SEP-15:01 | 17021.79 | 0.49 |
October | 0.00 | 0.00 | 0.356116E+10 | 0.315403E+10 | 16902.53 | 11-OCT-15:01 | 16902.53 | 0.16 |
November | 0.00 | 0.00 | 0.173150E+10 | 0.136809E+10 | 16171.77 | 05-NOV-15:01 | 16171.77 | 0.18 |
December | 0.00 | 0.00 | 0.818863E+09 | 0.800028E+09 | 15714.62 | 02-DEC-16:01 | 15714.62 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.586618E+11 | 0.448293E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.818863E+09 | 0.800028E+09 | 15714.62 | 15714.62 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.107572E+11 | 0.758676E+10 | 17034.06 | 17034.06 | 0.86 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.221783E+09 | 0.166848E+09 | 15055.14 | 24-JAN-09:01 | 15055.14 | 0.02 |
February | 0.00 | 0.00 | 0.431738E+09 | 0.357905E+09 | 15372.71 | 18-FEB-16:01 | 15372.71 | 0.03 |
March | 0.00 | 0.00 | 0.126064E+10 | 0.121316E+10 | 16084.27 | 13-MAR-15:01 | 16084.27 | 0.02 |
April | 0.00 | 0.00 | 0.128807E+10 | 0.109200E+10 | 17882.34 | 19-APR-08:51 | 17882.34 | 0.11 |
May | 0.00 | 0.00 | 0.358593E+10 | 0.250271E+10 | 18221.65 | 10-MAY-08:51 | 18221.65 | 0.44 |
June | 0.00 | 0.00 | 0.866718E+10 | 0.613852E+10 | 20801.54 | 27-JUN-08:32 | 20801.54 | 0.69 |
July | 0.00 | 0.00 | 0.869000E+10 | 0.599707E+10 | 20897.54 | 01-JUL-07:42 | 20897.54 | 0.68 |
August | 0.00 | 0.00 | 0.811224E+10 | 0.552269E+10 | 20393.75 | 05-AUG-08:32 | 16426.06 | 0.65 |
September | 0.00 | 0.00 | 0.519598E+10 | 0.395064E+10 | 18604.22 | 07-SEP-08:51 | 18604.22 | 0.40 |
October | 0.00 | 0.00 | 0.138905E+10 | 0.117070E+10 | 17837.17 | 11-OCT-08:51 | 17837.17 | 0.11 |
November | 0.00 | 0.00 | 0.394909E+09 | 0.297095E+09 | 15721.69 | 07-NOV-16:01 | 15721.69 | 0.05 |
December | 0.00 | 0.00 | 0.123287E+09 | 0.114237E+09 | 15017.04 | 03-DEC-09:01 | 15017.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393608E+11 | 0.285236E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.123287E+09 | 0.114237E+09 | 15017.04 | 15017.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.869000E+10 | 0.613852E+10 | 20897.54 | 20897.54 | 0.69 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.298197E+09 | 0.251142E+09 | 4844.71 | 23-JAN-16:01 | 4844.71 | 0.07 |
February | 0.00 | 0.00 | 0.325169E+09 | 0.291577E+09 | 4816.28 | 18-FEB-16:01 | 4816.28 | 0.07 |
March | 0.00 | 0.00 | 0.645529E+09 | 0.638957E+09 | 5034.98 | 13-MAR-15:01 | 5034.98 | 0.01 |
April | 0.00 | 0.00 | 0.455590E+09 | 0.412903E+09 | 4950.25 | 07-APR-15:01 | 4950.25 | 0.08 |
May | 0.00 | 0.00 | 0.106317E+10 | 0.788407E+09 | 5133.63 | 10-MAY-15:01 | 5133.63 | 0.40 |
June | 0.00 | 0.00 | 0.248225E+10 | 0.169780E+10 | 5208.58 | 07-JUN-15:01 | 5208.58 | 0.81 |
July | 0.00 | 0.00 | 0.237291E+10 | 0.148481E+10 | 5207.70 | 01-JUL-18:01 | 5207.70 | 0.83 |
August | 0.00 | 0.00 | 0.242167E+10 | 0.160549E+10 | 5209.89 | 18-AUG-15:01 | 5209.89 | 0.79 |
September | 0.00 | 0.00 | 0.181711E+10 | 0.141453E+10 | 5206.23 | 26-SEP-15:01 | 5206.23 | 0.46 |
October | 0.00 | 0.00 | 0.845292E+09 | 0.764742E+09 | 5169.93 | 11-OCT-15:01 | 5169.93 | 0.13 |
November | 0.00 | 0.00 | 0.412700E+09 | 0.328164E+09 | 4945.28 | 05-NOV-15:01 | 4945.28 | 0.14 |
December | 0.00 | 0.00 | 0.180676E+09 | 0.176470E+09 | 4805.71 | 02-DEC-16:01 | 4805.71 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.133203E+11 | 0.985499E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.180676E+09 | 0.176470E+09 | 4805.71 | 4805.71 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.248225E+10 | 0.169780E+10 | 5209.89 | 5209.89 | 0.83 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 42055091.56 | 36738673.69 | 4708.25 | 23-JAN-16:01 | 4708.25 | 0.01 |
February | 0.00 | 0.00 | 67845853.11 | 60500362.26 | 4679.73 | 18-FEB-16:01 | 4679.73 | 0.01 |
March | 0.00 | 0.00 | 0.235782E+09 | 0.232892E+09 | 5323.15 | 08-MAR-17:11 | 5323.15 | 0.01 |
April | 0.00 | 0.00 | 0.213442E+09 | 0.187907E+09 | 5354.24 | 08-APR-18:01 | 5354.24 | 0.06 |
May | 0.00 | 0.00 | 0.724679E+09 | 0.482287E+09 | 5322.47 | 25-MAY-17:11 | 5322.47 | 0.36 |
June | 0.00 | 0.00 | 0.217855E+10 | 0.153608E+10 | 5442.35 | 27-JUN-08:51 | 5442.35 | 0.66 |
July | 0.00 | 0.00 | 0.199808E+10 | 0.128056E+10 | 5665.00 | 01-JUL-08:61 | 5665.00 | 0.66 |
August | 0.00 | 0.00 | 0.186664E+10 | 0.123533E+10 | 5508.07 | 05-AUG-08:51 | 3977.54 | 0.62 |
September | 0.00 | 0.00 | 0.111790E+10 | 0.805269E+09 | 5210.35 | 09-SEP-08:51 | 5210.35 | 0.37 |
October | 0.00 | 0.00 | 0.282819E+09 | 0.251208E+09 | 5224.13 | 08-OCT-18:11 | 5224.13 | 0.06 |
November | 0.00 | 0.00 | 74017479.01 | 62359334.46 | 4805.76 | 05-NOV-15:01 | 4805.76 | 0.02 |
December | 0.00 | 0.00 | 18790485.35 | 18336407.93 | 4670.38 | 02-DEC-16:01 | 4670.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.882060E+10 | 0.618946E+10 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 18790485.35 | 18336407.93 | 4670.38 | 3977.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217855E+10 | 0.153608E+10 | 5665.00 | 5665.00 | 0.66 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.741705E+10 | 0.674993E+10 | 20821.43 | 23-JAN-16:01 | 20821.43 | 0.22 |
February | 0.00 | 0.00 | 0.598237E+10 | 0.550618E+10 | 20696.33 | 18-FEB-16:01 | 20696.33 | 0.17 |
March | 0.00 | 0.00 | 0.613433E+10 | 0.602727E+10 | 21635.78 | 13-MAR-15:01 | 21635.78 | 0.05 |
April | 0.00 | 0.00 | 0.317148E+10 | 0.284639E+10 | 21268.65 | 07-APR-15:01 | 21268.65 | 0.13 |
May | 0.00 | 0.00 | 0.550310E+10 | 0.404635E+10 | 21618.98 | 10-MAY-18:01 | 21618.98 | 0.44 |
June | 0.00 | 0.00 | 0.109597E+11 | 0.714343E+10 | 22371.98 | 14-JUN-08:61 | 22371.98 | 0.80 |
July | 0.00 | 0.00 | 0.118832E+11 | 0.759786E+10 | 22203.25 | 01-JUL-08:61 | 22203.25 | 0.83 |
August | 0.00 | 0.00 | 0.132206E+11 | 0.920070E+10 | 22223.38 | 18-AUG-08:61 | 22223.38 | 0.80 |
September | 0.00 | 0.00 | 0.120301E+11 | 0.100830E+11 | 22369.17 | 26-SEP-15:01 | 22369.17 | 0.48 |
October | 0.00 | 0.00 | 0.858827E+10 | 0.803084E+10 | 22210.27 | 11-OCT-15:01 | 22210.27 | 0.19 |
November | 0.00 | 0.00 | 0.771745E+10 | 0.669640E+10 | 21249.90 | 05-NOV-15:01 | 21249.90 | 0.35 |
December | 0.00 | 0.00 | 0.534551E+10 | 0.528505E+10 | 20651.96 | 02-DEC-16:01 | 20651.96 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.979532E+11 | 0.792134E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.317148E+10 | 0.284639E+10 | 20651.96 | 20651.96 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.132206E+11 | 0.100830E+11 | 22371.98 | 22371.98 | 0.83 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 37987.90 | 254259.73 | 05-JAN-19:03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 44660.85 | 214287.84 | 11-FEB-19:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 32593.63 | 218321.14 | 19-MAR-08:61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30681.42 | 182093.39 | 03-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24564.59 | 122279.54 | 19-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 1799.37 | 101161.44 | 09-JUN-03:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1657.01 | 74569.15 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1665.58 | 55575.04 | 17-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10249.37 | 120991.12 | 21-SEP-14:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27852.57 | 206744.77 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 30510.24 | 221650.20 | 29-NOV-19:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57377.11 | 280389.06 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 25047.58 | ||||
Minimum of Months | 0.00 | 0.00 | 1657.01 | 55575.04 | ||
Maximum of Months | 0.00 | 0.00 | 57377.11 | 280389.06 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21309.73 | 224162.22 | 23-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17643.61 | 224910.59 | 18-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 25855.58 | 373704.55 | 13-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20419.37 | 298811.44 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 64889.27 | 377779.37 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 176165.54 | 474456.29 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 189326.25 | 436639.61 | 17-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 175384.49 | 475943.75 | 25-AUG-18:04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 133515.21 | 439989.72 | 28-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 40702.62 | 404845.49 | 11-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24606.60 | 291456.62 | 07-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 15116.18 | 202086.77 | 02-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 75740.63 | 0.00 | ||||
Minimum of Months | 15116.18 | 202086.77 | 0.00 | 0.00 | ||
Maximum of Months | 189326.25 | 475943.75 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 28133.30 | 59402.76 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 28488.38 | 59501.57 | 13-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28071.71 | 59253.41 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26959.03 | 57414.25 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25470.61 | 54801.07 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24006.64 | 51424.35 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22922.25 | 48573.73 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22573.49 | 47215.64 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22990.65 | 48776.90 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24096.22 | 51764.36 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25588.10 | 54960.15 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 27080.62 | 57639.67 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 25514.52 | ||||
Minimum of Months | 0.00 | 0.00 | 22573.49 | 47215.64 | ||
Maximum of Months | 0.00 | 0.00 | 28488.38 | 59501.57 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.861838E+09 | 0.08 | 553.22 | 01-JAN-06:20 | 0.12 |
February | 0.811327E+09 | 0.09 | 553.22 | 01-FEB-05:15 | 0.12 |
March | 0.804197E+09 | 0.08 | 553.22 | 01-MAR-05:15 | 0.12 |
April | 0.723324E+09 | 0.08 | 553.22 | 01-APR-01:07 | 0.12 |
May | 0.629454E+09 | 0.07 | 553.22 | 01-MAY-04:07 | 0.12 |
June | 0.517263E+09 | 0.07 | 553.22 | 01-JUN-05:05 | 0.12 |
July | 0.510424E+09 | 0.07 | 553.22 | 01-JUL-05:16 | 0.12 |
August | 0.508204E+09 | 0.07 | 553.22 | 01-AUG-05:05 | 0.12 |
September | 0.528628E+09 | 0.07 | 553.22 | 01-SEP-04:07 | 0.12 |
October | 0.673372E+09 | 0.07 | 553.22 | 01-OCT-05:05 | 0.12 |
November | 0.734306E+09 | 0.08 | 553.22 | 01-NOV-04:07 | 0.12 |
December | 0.888119E+09 | 0.08 | 553.22 | 01-DEC-05:15 | 0.12 |
Annual Sum or Average | 0.819046E+10 | 0.08 | |||
Minimum of Months | 0.508204E+09 | 0.07 | 553.22 | 0.12 | |
Maximum of Months | 0.888119E+09 | 0.09 | 553.22 | 0.12 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.562726E+09 | 0.07 | 700.51 | 01-JAN-17:10 | 0.12 |
February | 0.508437E+09 | 0.07 | 700.51 | 01-FEB-17:10 | 0.12 |
March | 0.562663E+09 | 0.07 | 700.51 | 01-MAR-17:10 | 0.12 |
April | 0.543792E+09 | 0.07 | 700.51 | 01-APR-16:05 | 0.12 |
May | 0.561131E+09 | 0.07 | 700.51 | 01-MAY-16:10 | 0.12 |
June | 0.541875E+09 | 0.06 | 700.51 | 01-JUN-16:10 | 0.12 |
July | 0.559888E+09 | 0.06 | 700.51 | 01-JUL-16:10 | 0.12 |
August | 0.560010E+09 | 0.06 | 700.51 | 01-AUG-16:10 | 0.12 |
September | 0.542422E+09 | 0.07 | 700.51 | 01-SEP-16:10 | 0.12 |
October | 0.561695E+09 | 0.07 | 700.51 | 01-OCT-16:10 | 0.12 |
November | 0.543819E+09 | 0.07 | 700.51 | 01-NOV-16:10 | 0.12 |
December | 0.563393E+09 | 0.07 | 700.51 | 01-DEC-17:10 | 0.12 |
Annual Sum or Average | 0.661185E+10 | 0.07 | |||
Minimum of Months | 0.508437E+09 | 0.06 | 700.51 | 0.12 | |
Maximum of Months | 0.563393E+09 | 0.07 | 700.51 | 0.12 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.85 | 1299.30 | 01-JAN-01:20 | 1.08 |
February | 0.244774E+10 | 0.85 | 1299.30 | 01-FEB-09:40 | 1.08 |
March | 0.271000E+10 | 0.85 | 1299.30 | 01-MAR-00:30 | 1.07 |
April | 0.262258E+10 | 0.85 | 1299.30 | 01-APR-01:07 | 1.08 |
May | 0.271000E+10 | 0.85 | 1299.30 | 07-MAY-20:40 | 1.08 |
June | 0.262258E+10 | 0.85 | 1299.30 | 01-JUN-19:10 | 1.07 |
July | 0.271000E+10 | 0.85 | 1299.30 | 01-JUL-08:08 | 1.08 |
August | 0.271000E+10 | 0.85 | 1299.30 | 07-AUG-09:15 | 1.07 |
September | 0.262258E+10 | 0.85 | 1299.30 | 07-SEP-22:30 | 1.08 |
October | 0.271000E+10 | 0.85 | 1299.30 | 01-OCT-01:10 | 1.08 |
November | 0.262258E+10 | 0.85 | 1299.30 | 01-NOV-09:35 | 1.08 |
December | 0.271000E+10 | 0.86 | 1299.30 | 06-DEC-16:03 | 1.08 |
Annual Sum or Average | 0.319080E+11 | 0.85 | |||
Minimum of Months | 0.244774E+10 | 0.85 | 1299.30 | 1.07 | |
Maximum of Months | 0.271000E+10 | 0.86 | 1299.30 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.337110E+11 | 0.91 | 27351.96 | 20-JAN-22:10 | 1.43 |
February | 0.301534E+11 | 0.91 | 25050.70 | 17-FEB-22:10 | 1.35 |
March | 0.348057E+11 | 0.93 | 30989.72 | 15-MAR-21:10 | 1.55 |
April | 0.331665E+11 | 0.92 | 28826.35 | 20-APR-21:10 | 1.47 |
May | 0.375263E+11 | 0.96 | 31705.24 | 17-MAY-21:10 | 1.56 |
June | 0.416971E+11 | 1.03 | 36842.16 | 30-JUN-21:10 | 1.71 |
July | 0.431400E+11 | 1.03 | 36890.03 | 17-JUL-21:10 | 1.71 |
August | 0.439956E+11 | 1.04 | 40193.28 | 16-AUG-21:10 | 1.80 |
September | 0.423024E+11 | 1.04 | 42298.51 | 12-SEP-21:10 | 1.86 |
October | 0.381572E+11 | 0.97 | 36658.99 | 10-OCT-21:10 | 1.72 |
November | 0.348399E+11 | 0.94 | 31215.60 | 06-NOV-22:10 | 1.55 |
December | 0.337001E+11 | 0.91 | 27913.24 | 04-DEC-22:10 | 1.45 |
Annual Sum or Average | 0.447195E+12 | 0.97 | |||
Minimum of Months | 0.301534E+11 | 0.91 | 25050.70 | 1.35 | |
Maximum of Months | 0.439956E+11 | 1.04 | 42298.51 | 1.86 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:10 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:05 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:10 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:10 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:05 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:10 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:05 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:10 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:05 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:05 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.33 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.33 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.33 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.33 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.33 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:03 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.33 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.33 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.33 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229602E+09 | 0.58 | 975.95 | 01-JAN-16:01 | 0.70 |
February | 0.245892E+09 | 0.59 | 975.95 | 01-FEB-09:01 | 0.71 |
March | 0.285602E+09 | 0.59 | 975.95 | 02-MAR-16:01 | 0.71 |
April | 0.224201E+09 | 0.57 | 975.95 | 02-APR-08:61 | 0.70 |
May | 0.269430E+09 | 0.62 | 975.95 | 01-MAY-15:02 | 0.71 |
June | 0.522898E+09 | 0.67 | 975.95 | 01-JUN-08:62 | 0.70 |
July | 0.489341E+09 | 0.67 | 975.95 | 01-JUL-08:61 | 0.71 |
August | 0.509814E+09 | 0.67 | 975.95 | 01-AUG-08:62 | 0.71 |
September | 0.424547E+09 | 0.66 | 975.95 | 01-SEP-08:62 | 0.70 |
October | 0.306103E+09 | 0.62 | 975.95 | 01-OCT-08:61 | 0.70 |
November | 0.232509E+09 | 0.59 | 975.95 | 01-NOV-08:61 | 0.70 |
December | 0.277271E+09 | 0.58 | 975.95 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.401721E+10 | 0.62 | |||
Minimum of Months | 0.224201E+09 | 0.57 | 975.95 | 0.70 | |
Maximum of Months | 0.522898E+09 | 0.67 | 975.95 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245207E+09 | 0.53 | 950.78 | 01-JAN-09:01 | 0.70 |
February | 0.242209E+09 | 0.55 | 950.78 | 01-FEB-09:01 | 0.71 |
March | 0.222131E+09 | 0.53 | 950.78 | 01-MAR-09:01 | 0.70 |
April | 0.180187E+09 | 0.51 | 950.78 | 02-APR-08:61 | 0.70 |
May | 0.193042E+09 | 0.50 | 950.78 | 01-MAY-18:02 | 0.71 |
June | 0.453653E+09 | 0.53 | 950.78 | 01-JUN-08:51 | 0.70 |
July | 0.402199E+09 | 0.52 | 950.78 | 01-JUL-08:61 | 0.71 |
August | 0.382942E+09 | 0.52 | 950.78 | 01-AUG-08:51 | 0.71 |
September | 0.266776E+09 | 0.49 | 950.78 | 01-SEP-08:51 | 0.70 |
October | 0.197273E+09 | 0.53 | 950.78 | 01-OCT-08:61 | 0.70 |
November | 0.213297E+09 | 0.54 | 950.78 | 01-NOV-08:61 | 0.70 |
December | 0.313111E+09 | 0.56 | 950.78 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.331203E+10 | 0.53 | |||
Minimum of Months | 0.180187E+09 | 0.49 | 950.78 | 0.70 | |
Maximum of Months | 0.453653E+09 | 0.56 | 950.78 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142356E+10 | 0.40 | 2782.49 | 20-JAN-12:40 | 0.71 |
February | 0.997815E+09 | 0.32 | 2690.27 | 18-FEB-12:50 | 0.71 |
March | 0.994157E+09 | 0.32 | 2515.84 | 11-MAR-13:00 | 0.71 |
April | 0.377444E+09 | 0.20 | 1416.67 | 08-APR-13:00 | 0.71 |
May | 0.929807E+09 | 0.51 | 1126.14 | 06-MAY-13:50 | 0.71 |
June | 0.167171E+10 | 0.70 | 1301.59 | 14-JUN-13:30 | 0.71 |
July | 0.180855E+10 | 0.70 | 1368.17 | 23-JUL-13:00 | 0.71 |
August | 0.203075E+10 | 0.70 | 1719.80 | 31-AUG-12:40 | 0.71 |
September | 0.209483E+10 | 0.68 | 2623.83 | 17-SEP-12:30 | 0.71 |
October | 0.160968E+10 | 0.44 | 3303.33 | 10-OCT-12:30 | 0.71 |
November | 0.133355E+10 | 0.39 | 2783.54 | 07-NOV-12:20 | 0.71 |
December | 0.862756E+09 | 0.25 | 2605.82 | 17-DEC-12:10 | 0.71 |
Annual Sum or Average | 0.161346E+11 | 0.47 | |||
Minimum of Months | 0.377444E+09 | 0.20 | 1126.14 | 0.71 | |
Maximum of Months | 0.209483E+10 | 0.70 | 3303.33 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.961727E+09 | 0.50 | 4696.55 | 01-JAN-16:01 | 0.71 |
February | 0.968143E+09 | 0.50 | 4696.55 | 01-FEB-09:01 | 0.71 |
March | 0.850949E+09 | 0.48 | 4696.55 | 04-MAR-16:01 | 0.71 |
April | 0.811788E+09 | 0.47 | 4696.55 | 01-APR-08:62 | 0.71 |
May | 0.166095E+10 | 0.45 | 4696.55 | 01-MAY-15:02 | 0.71 |
June | 0.292984E+10 | 0.50 | 4696.55 | 01-JUN-08:51 | 0.70 |
July | 0.293070E+10 | 0.49 | 4696.55 | 01-JUL-08:61 | 0.71 |
August | 0.246970E+10 | 0.47 | 4696.55 | 01-AUG-08:51 | 0.71 |
September | 0.179779E+10 | 0.44 | 4696.55 | 01-SEP-08:51 | 0.70 |
October | 0.859830E+09 | 0.47 | 4696.55 | 01-OCT-08:61 | 0.71 |
November | 0.820841E+09 | 0.49 | 4696.55 | 01-NOV-08:61 | 0.71 |
December | 0.122970E+10 | 0.51 | 4696.55 | 02-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.182920E+11 | 0.48 | |||
Minimum of Months | 0.811788E+09 | 0.44 | 4696.55 | 0.70 | |
Maximum of Months | 0.293070E+10 | 0.51 | 4696.55 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223525E+09 | 0.59 | 852.20 | 01-JAN-09:01 | 0.70 |
February | 0.248619E+09 | 0.61 | 852.20 | 01-FEB-09:01 | 0.71 |
March | 0.283897E+09 | 0.61 | 852.20 | 01-MAR-09:01 | 0.70 |
April | 0.233340E+09 | 0.59 | 852.20 | 02-APR-08:61 | 0.70 |
May | 0.286927E+09 | 0.65 | 852.20 | 02-MAY-15:01 | 0.71 |
June | 0.548272E+09 | 0.69 | 852.20 | 01-JUN-08:62 | 0.70 |
July | 0.548867E+09 | 0.69 | 852.20 | 01-JUL-08:61 | 0.71 |
August | 0.556064E+09 | 0.69 | 852.20 | 01-AUG-08:62 | 0.71 |
September | 0.446489E+09 | 0.68 | 852.20 | 01-SEP-08:62 | 0.70 |
October | 0.294743E+09 | 0.64 | 852.20 | 01-OCT-08:61 | 0.70 |
November | 0.228289E+09 | 0.59 | 852.20 | 01-NOV-08:61 | 0.70 |
December | 0.261597E+09 | 0.57 | 852.20 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.416063E+10 | 0.63 | |||
Minimum of Months | 0.223525E+09 | 0.57 | 852.20 | 0.70 | |
Maximum of Months | 0.556064E+09 | 0.69 | 852.20 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229579E+09 | 0.52 | 832.49 | 01-JAN-09:01 | 0.70 |
February | 0.230613E+09 | 0.55 | 832.49 | 01-FEB-09:01 | 0.71 |
March | 0.218360E+09 | 0.54 | 832.49 | 01-MAR-09:01 | 0.70 |
April | 0.193507E+09 | 0.54 | 832.49 | 02-APR-08:61 | 0.70 |
May | 0.220015E+09 | 0.54 | 832.49 | 03-MAY-08:62 | 0.70 |
June | 0.460671E+09 | 0.55 | 832.49 | 01-JUN-08:51 | 0.70 |
July | 0.450667E+09 | 0.53 | 832.49 | 01-JUL-07:42 | 0.71 |
August | 0.417133E+09 | 0.54 | 832.49 | 01-AUG-08:51 | 0.71 |
September | 0.290140E+09 | 0.52 | 832.49 | 01-SEP-08:51 | 0.70 |
October | 0.192752E+09 | 0.55 | 832.49 | 01-OCT-08:61 | 0.70 |
November | 0.205405E+09 | 0.52 | 832.49 | 01-NOV-08:61 | 0.70 |
December | 0.289097E+09 | 0.55 | 832.49 | 02-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.339794E+10 | 0.54 | |||
Minimum of Months | 0.192752E+09 | 0.52 | 832.49 | 0.70 | |
Maximum of Months | 0.460671E+09 | 0.55 | 832.49 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 71600636.06 | 0.58 | 260.72 | 01-JAN-16:01 | 0.70 |
February | 74559110.34 | 0.59 | 260.72 | 01-FEB-09:01 | 0.70 |
March | 82902156.41 | 0.61 | 260.72 | 01-MAR-19:01 | 0.71 |
April | 67870079.72 | 0.59 | 260.72 | 02-APR-08:61 | 0.70 |
May | 69343803.71 | 0.62 | 260.72 | 01-MAY-18:02 | 0.71 |
June | 0.134259E+09 | 0.67 | 260.72 | 01-JUN-08:62 | 0.70 |
July | 0.122756E+09 | 0.67 | 260.72 | 01-JUL-08:61 | 0.71 |
August | 0.128370E+09 | 0.67 | 260.72 | 01-AUG-15:01 | 0.71 |
September | 0.102999E+09 | 0.66 | 260.72 | 01-SEP-15:01 | 0.70 |
October | 84442753.09 | 0.63 | 260.72 | 01-OCT-08:61 | 0.70 |
November | 70053289.72 | 0.60 | 260.72 | 01-NOV-08:61 | 0.70 |
December | 86007225.36 | 0.59 | 260.72 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.109516E+10 | 0.62 | |||
Minimum of Months | 67870079.72 | 0.58 | 260.72 | 0.70 | |
Maximum of Months | 0.134259E+09 | 0.67 | 260.72 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 79473784.69 | 0.55 | 253.37 | 01-JAN-09:01 | 0.70 |
February | 76133939.67 | 0.57 | 253.37 | 01-FEB-09:01 | 0.70 |
March | 67865681.19 | 0.55 | 253.37 | 01-MAR-09:01 | 0.70 |
April | 56316751.31 | 0.53 | 253.37 | 02-APR-08:61 | 0.70 |
May | 49462602.53 | 0.50 | 253.37 | 01-MAY-18:02 | 0.71 |
June | 0.119163E+09 | 0.53 | 253.37 | 01-JUN-08:51 | 0.70 |
July | 0.103658E+09 | 0.52 | 253.37 | 01-JUL-08:61 | 0.71 |
August | 98365986.52 | 0.52 | 253.37 | 01-AUG-08:51 | 0.71 |
September | 64858949.88 | 0.49 | 253.37 | 01-SEP-08:51 | 0.70 |
October | 59607011.25 | 0.54 | 253.37 | 01-OCT-15:01 | 0.70 |
November | 69299456.13 | 0.55 | 253.37 | 01-NOV-08:61 | 0.70 |
December | 97981563.31 | 0.58 | 253.37 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.942186E+09 | 0.53 | |||
Minimum of Months | 49462602.53 | 0.49 | 253.37 | 0.70 | |
Maximum of Months | 0.119163E+09 | 0.58 | 253.37 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.549104E+09 | 0.63 | 1117.52 | 01-JAN-09:01 | 0.70 |
February | 0.495038E+09 | 0.64 | 1117.52 | 01-FEB-09:01 | 0.71 |
March | 0.478692E+09 | 0.62 | 1117.52 | 01-MAR-09:01 | 0.70 |
April | 0.308011E+09 | 0.59 | 1117.52 | 02-APR-08:61 | 0.70 |
May | 0.330427E+09 | 0.63 | 1117.52 | 01-MAY-15:02 | 0.71 |
June | 0.558686E+09 | 0.67 | 1117.52 | 01-JUN-08:62 | 0.70 |
July | 0.591356E+09 | 0.67 | 1117.52 | 01-JUL-08:61 | 0.71 |
August | 0.667600E+09 | 0.67 | 1117.52 | 01-AUG-15:01 | 0.71 |
September | 0.661001E+09 | 0.67 | 1117.52 | 01-SEP-08:62 | 0.70 |
October | 0.592579E+09 | 0.64 | 1117.52 | 01-OCT-08:61 | 0.70 |
November | 0.566725E+09 | 0.64 | 1117.52 | 01-NOV-08:61 | 0.70 |
December | 0.484604E+09 | 0.62 | 1117.52 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.628383E+10 | 0.64 | |||
Minimum of Months | 0.308011E+09 | 0.59 | 1117.52 | 0.70 | |
Maximum of Months | 0.667600E+09 | 0.67 | 1117.52 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.613040E+09 | 0.557253E+09 | 842.43 | 05-JAN-19:01 | 765.77 | 765.77 | 38.11 | 1.37 |
February | 0.629134E+09 | 0.571883E+09 | 767.18 | 12-FEB-07:10 | 697.37 | 697.37 | 44.89 | 1.16 |
March | 0.507746E+09 | 0.461541E+09 | 773.61 | 19-MAR-08:61 | 703.21 | 703.21 | 37.74 | 1.17 |
April | 0.442525E+09 | 0.402256E+09 | 682.70 | 03-APR-08:61 | 620.57 | 620.57 | 36.75 | 0.96 |
May | 0.287430E+09 | 0.261274E+09 | 618.66 | 03-MAY-08:03 | 562.36 | 562.36 | 55.77 | 0.83 |
June | 19520773.34 | 17744382.97 | 416.76 | 09-JUN-03:10 | 378.84 | 378.84 | 31.88 | 0.50 |
July | 18586250.12 | 16894901.36 | 310.33 | 02-JUL-05:00 | 282.09 | 282.09 | 29.79 | 0.36 |
August | 18870556.73 | 17153336.06 | 224.75 | 12-AUG-23:00 | 204.30 | 204.30 | 27.22 | 0.25 |
September | 0.115170E+09 | 0.104689E+09 | 527.24 | 22-SEP-09:25 | 479.26 | 479.26 | 56.33 | 0.67 |
October | 0.397204E+09 | 0.361058E+09 | 742.40 | 30-OCT-08:61 | 674.84 | 674.84 | 37.17 | 1.10 |
November | 0.493342E+09 | 0.448448E+09 | 762.40 | 29-NOV-19:01 | 693.02 | 693.02 | 35.99 | 1.15 |
December | 0.821226E+09 | 0.746494E+09 | 893.36 | 21-DEC-09:03 | 812.07 | 812.07 | 38.56 | 1.54 |
Annual Sum or Average | 0.436379E+10 | 0.396669E+10 | ||||||
Minimum of Months | 18586250.12 | 16894901.36 | 224.75 | 204.30 | 204.30 | 27.22 | 0.25 | |
Maximum of Months | 0.821226E+09 | 0.746494E+09 | 893.36 | 812.07 | 812.07 | 56.33 | 1.54 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 33482377.58 | 30435481.22 | 302.32 | 23-JAN-16:01 | 274.81 | 274.81 | 7.93 | 7.54 |
February | 26495821.10 | 24084701.38 | 344.47 | 18-FEB-16:01 | 313.13 | 313.13 | 8.05 | 8.01 |
March | 54994623.76 | 49990112.99 | 465.86 | 14-MAR-15:01 | 423.46 | 423.46 | 7.30 | 9.18 |
April | 36209584.95 | 32914512.72 | 399.63 | 07-APR-15:01 | 363.26 | 363.26 | 7.59 | 8.57 |
May | 0.147107E+09 | 0.133720E+09 | 938.79 | 31-MAY-18:03 | 853.36 | 853.36 | 6.89 | 12.48 |
June | 0.549981E+09 | 0.499933E+09 | 1512.16 | 15-JUN-18:02 | 1374.55 | 1374.55 | 6.73 | 15.27 |
July | 0.655548E+09 | 0.595893E+09 | 1386.41 | 17-JUL-19:40 | 1260.25 | 1260.25 | 6.73 | 14.73 |
August | 0.641760E+09 | 0.583360E+09 | 1373.28 | 25-AUG-18:15 | 1248.31 | 1248.31 | 6.73 | 14.67 |
September | 0.374418E+09 | 0.340346E+09 | 1255.11 | 12-SEP-18:50 | 1140.89 | 1140.89 | 6.85 | 14.12 |
October | 92965171.68 | 84505341.06 | 492.33 | 11-OCT-15:01 | 447.53 | 447.53 | 6.85 | 9.41 |
November | 41683958.21 | 37890718.01 | 460.91 | 07-NOV-16:01 | 418.97 | 418.97 | 7.64 | 9.14 |
December | 23409854.32 | 21279557.58 | 301.81 | 02-DEC-16:01 | 274.35 | 274.35 | 8.08 | 7.54 |
Annual Sum or Average | 0.267805E+10 | 0.243435E+10 | ||||||
Minimum of Months | 23409854.32 | 21279557.58 | 301.81 | 274.35 | 274.35 | 6.73 | 7.54 | |
Maximum of Months | 0.655548E+09 | 0.595893E+09 | 1512.16 | 1374.55 | 1374.55 | 8.08 | 15.27 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.592055E+10 | 0.538178E+10 | 3533.41 | 01-JAN-00:10 | 3211.87 | 3211.87 | 8.42 | 25.01 |
February | 0.468927E+10 | 0.426255E+10 | 3533.41 | 01-FEB-09:03 | 3211.87 | 3211.87 | 8.48 | 25.01 |
March | 0.578764E+10 | 0.526097E+10 | 3533.41 | 01-MAR-07:05 | 3211.87 | 3211.87 | 8.40 | 25.01 |
April | 0.585467E+10 | 0.532189E+10 | 3533.41 | 01-APR-00:10 | 3211.87 | 3211.87 | 8.48 | 25.01 |
May | 0.912485E+10 | 0.829449E+10 | 3533.41 | 01-MAY-05:03 | 3211.87 | 3211.87 | 8.42 | 25.01 |
June | 0.915859E+10 | 0.832516E+10 | 3533.41 | 01-JUN-00:05 | 3211.87 | 3211.87 | 8.97 | 25.01 |
July | 0.946388E+10 | 0.860267E+10 | 3533.41 | 01-JUL-00:10 | 3211.87 | 3211.87 | 9.25 | 25.01 |
August | 0.946388E+10 | 0.860267E+10 | 3533.41 | 01-AUG-00:05 | 3211.87 | 3211.87 | 9.29 | 25.01 |
September | 0.908686E+10 | 0.825996E+10 | 3533.41 | 01-SEP-00:05 | 3211.87 | 3211.87 | 9.13 | 25.01 |
October | 0.696959E+10 | 0.633535E+10 | 3533.41 | 01-OCT-00:10 | 3211.87 | 3211.87 | 8.62 | 25.01 |
November | 0.599355E+10 | 0.544814E+10 | 3533.41 | 01-NOV-08:04 | 3211.87 | 3211.87 | 8.43 | 25.01 |
December | 0.445903E+10 | 0.405326E+10 | 3533.41 | 01-DEC-07:50 | 3211.87 | 3211.87 | 8.41 | 25.01 |
Annual Sum or Average | 0.859724E+11 | 0.781489E+11 | ||||||
Minimum of Months | 0.445903E+10 | 0.405326E+10 | 3533.41 | 3211.87 | 3211.87 | 8.40 | 25.01 | |
Maximum of Months | 0.946388E+10 | 0.860267E+10 | 3533.41 | 3211.87 | 3211.87 | 9.29 | 25.01 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 48.52 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.07 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 49.34 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.15 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.30 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.77 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.36 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.37 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.35 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.52 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.71 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 49.86 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.52 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.37 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.57 | 81.00 | 37987.90 | 254259.73 | 05-JAN-19:03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.79 | 81.96 | 44660.85 | 214287.84 | 11-FEB-19:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 61.93 | 81.26 | 32593.63 | 218321.14 | 19-MAR-08:61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30.91 | 80.09 | 30681.42 | 182093.39 | 03-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 62.77 | 80.17 | 24564.59 | 122279.54 | 19-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 29.64 | 29.64 | 1799.37 | 101161.44 | 09-JUN-03:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.45 | 29.45 | 1657.01 | 74569.15 | 02-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 51.93 | 51.93 | 1665.58 | 55575.04 | 17-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 30.79 | 30.79 | 10249.37 | 120991.12 | 21-SEP-14:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.36 | 79.40 | 27852.57 | 206744.77 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.23 | 82.03 | 30510.24 | 221650.20 | 29-NOV-19:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 61.30 | 80.62 | 57377.11 | 280389.06 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 25047.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.36 | 29.45 | 1657.01 | 55575.04 | ||
Maximum of Months | 0.00 | 0.00 | 62.77 | 82.03 | 57377.11 | 280389.06 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21309.73 | 224162.22 | 23-JAN-16:01 | 10.12 | 7.98 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 17643.61 | 224910.59 | 18-FEB-16:01 | 10.18 | 8.03 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 25855.58 | 373704.55 | 13-MAR-15:03 | 10.82 | 7.26 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20419.37 | 298811.44 | 07-APR-15:03 | 10.41 | 7.56 | 0.00 | 0.00 | 01-APR-00:10 |
May | 64889.27 | 377779.37 | 31-MAY-18:03 | 10.48 | 6.88 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 176165.54 | 474456.29 | 26-JUN-18:03 | 11.23 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 189326.25 | 436639.61 | 17-JUL-18:03 | 10.87 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 175384.49 | 475943.75 | 25-AUG-18:04 | 11.24 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 133515.21 | 439989.72 | 28-SEP-15:03 | 10.90 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 40702.62 | 404845.49 | 11-OCT-15:03 | 10.72 | 6.86 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24606.60 | 291456.62 | 07-NOV-16:01 | 10.49 | 7.71 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 15116.18 | 202086.77 | 02-DEC-16:01 | 10.04 | 8.11 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 75740.63 | 0.00 | ||||||
Minimum of Months | 15116.18 | 202086.77 | 10.04 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 189326.25 | 475943.75 | 11.24 | 8.11 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 48.52 | 59.99 | 28133.30 | 59402.76 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.07 | 59.99 | 28488.38 | 59501.57 | 13-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 49.34 | 59.99 | 28071.71 | 59253.41 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.15 | 59.96 | 26959.03 | 57414.25 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.30 | 59.97 | 25470.61 | 54801.07 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.77 | 59.99 | 24006.64 | 51424.35 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.36 | 59.99 | 22922.25 | 48573.73 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.37 | 59.99 | 22573.49 | 47215.64 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.35 | 59.97 | 22990.65 | 48776.90 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.52 | 59.96 | 24096.22 | 51764.36 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.71 | 59.96 | 25588.10 | 54960.15 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.86 | 59.99 | 27080.62 | 57639.67 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 25514.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.52 | 59.96 | 22573.49 | 47215.64 | ||
Maximum of Months | 0.00 | 0.00 | 53.37 | 59.99 | 28488.38 | 59501.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.720375E+11 | 0.00 | 0.524877E+10 | 0.337110E+11 | 0.00 | 0.00 |
February | 0.756053E+11 | 0.00 | 0.292967E+10 | 0.301534E+11 | 0.00 | 0.00 |
March | 0.683246E+11 | 0.00 | 0.179758E+11 | 0.348057E+11 | 0.00 | 0.00 |
April | 0.665031E+11 | 0.00 | 0.187099E+11 | 0.331665E+11 | 0.00 | 0.00 |
May | 0.652900E+11 | 0.00 | 0.872258E+11 | 0.375263E+11 | 0.00 | 0.00 |
June | 0.466777E+10 | 0.00 | 0.284455E+12 | 0.416971E+11 | 0.00 | 0.00 |
July | 0.441652E+10 | 0.00 | 0.325480E+12 | 0.431400E+11 | 0.00 | 0.00 |
August | 0.447289E+10 | 0.00 | 0.290742E+12 | 0.439956E+11 | 0.00 | 0.00 |
September | 0.263546E+11 | 0.00 | 0.201647E+12 | 0.423024E+11 | 0.00 | 0.00 |
October | 0.618594E+11 | 0.00 | 0.332039E+11 | 0.381572E+11 | 0.00 | 0.00 |
November | 0.565710E+11 | 0.00 | 0.106256E+11 | 0.348399E+11 | 0.00 | 0.00 |
December | 0.106825E+12 | 0.00 | 0.710187E+10 | 0.337001E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.612927E+12 | 0.00 | 0.128535E+13 | 0.447195E+12 | 0.00 | 0.00 |
Minimum of Months | 0.441652E+10 | 0.00 | 0.292967E+10 | 0.301534E+11 | 0.00 | 0.00 |
Maximum of Months | 0.106825E+12 | 0.00 | 0.325480E+12 | 0.439956E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.164337E+10 | 0.00 | 0.192282E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.176170E+10 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.704506E+09 | 0.00 | 0.893177E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.319628E+09 | 0.00 | 0.105845E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 16367.27 | 0.00 | 0.511985E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 24906.53 | 0.00 | 0.171378E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 31248.98 | 0.00 | 0.208898E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 31215.27 | 0.00 | 0.181610E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 948450.02 | 0.00 | 0.117068E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.505998E+09 | 0.00 | 0.173134E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.820374E+09 | 0.00 | 0.497142E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.308690E+10 | 0.00 | 0.275114E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.884353E+10 | 0.00 | 0.777862E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 16367.27 | 0.00 | 0.123483E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.308690E+10 | 0.00 | 0.208898E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.337110E+11 | 0.524877E+10 | 0.720375E+11 | 0.532104E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301534E+11 | 0.292967E+10 | 0.756053E+11 | 0.508681E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348057E+11 | 0.179758E+11 | 0.683246E+11 | 0.374602E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331665E+11 | 0.187099E+11 | 0.665031E+11 | 0.311390E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375263E+11 | 0.872258E+11 | 0.652900E+11 | 0.578347E+11 | 0.399880E+09 | 0.00 | 0.00 | 0.00 |
June | 0.416971E+11 | 0.284455E+12 | 0.466777E+10 | 0.804015E+10 | 0.192538E+11 | 0.00 | 0.00 | 0.00 |
July | 0.431400E+11 | 0.325480E+12 | 0.441652E+10 | 0.731363E+10 | 0.203379E+11 | 0.00 | 0.00 | 0.00 |
August | 0.439956E+11 | 0.290742E+12 | 0.447289E+10 | 0.700793E+10 | 0.145310E+11 | 0.00 | 0.00 | 0.00 |
September | 0.423024E+11 | 0.201647E+12 | 0.263546E+11 | 0.244876E+11 | 0.539858E+10 | 0.00 | 0.00 | 0.00 |
October | 0.381572E+11 | 0.332039E+11 | 0.618594E+11 | 0.303714E+12 | 9582581.26 | 0.00 | 0.00 | 0.00 |
November | 0.348399E+11 | 0.106256E+11 | 0.565710E+11 | 0.456091E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337001E+11 | 0.710187E+10 | 0.106825E+12 | 0.566909E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447195E+12 | 0.128535E+13 | 0.612927E+12 | 0.315818E+13 | 0.599308E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301534E+11 | 0.292967E+10 | 0.441652E+10 | 0.700793E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.439956E+11 | 0.325480E+12 | 0.106825E+12 | 0.566909E+12 | 0.203379E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.192282E+09 | 0.164337E+10 | 0.487470E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.123483E+09 | 0.176170E+10 | 0.466021E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.893177E+09 | 0.704506E+09 | 0.373314E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.105845E+10 | 0.319628E+09 | 0.325617E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.511985E+10 | 16367.27 | 0.128125E+11 | 22022053.75 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.171378E+11 | 24906.53 | 0.149339E+10 | 0.118214E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.208898E+11 | 31248.98 | 0.114800E+10 | 0.161833E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.181610E+11 | 31215.27 | 0.112232E+10 | 0.961467E+09 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.117068E+11 | 948450.02 | 0.535840E+10 | 0.199503E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.173134E+10 | 0.505998E+09 | 0.305008E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.497142E+09 | 0.820374E+09 | 0.418279E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.275114E+09 | 0.308690E+10 | 0.520403E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.777862E+11 | 0.884353E+10 | 0.311546E+12 | 0.398347E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.123483E+09 | 16367.27 | 0.112232E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.208898E+11 | 0.308690E+10 | 0.520403E+11 | 0.161833E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.337110E+11 | 0.720375E+11 | 0.524877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301534E+11 | 0.756053E+11 | 0.292967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348057E+11 | 0.683246E+11 | 0.179758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331665E+11 | 0.665031E+11 | 0.187099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375263E+11 | 0.652900E+11 | 0.872258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.416971E+11 | 0.466777E+10 | 0.284455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.431400E+11 | 0.441652E+10 | 0.325480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.439956E+11 | 0.447289E+10 | 0.290742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423024E+11 | 0.263546E+11 | 0.201647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.381572E+11 | 0.618594E+11 | 0.332039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348399E+11 | 0.565710E+11 | 0.106256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337001E+11 | 0.106825E+12 | 0.710187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447195E+12 | 0.612927E+12 | 0.128535E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301534E+11 | 0.441652E+10 | 0.292967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.439956E+11 | 0.106825E+12 | 0.325480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.164337E+10 | 0.192282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.176170E+10 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.704506E+09 | 0.893177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.319628E+09 | 0.105845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 16367.27 | 0.511985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 24906.53 | 0.171378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 31248.98 | 0.208898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 31215.27 | 0.181610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 948450.02 | 0.117068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.505998E+09 | 0.173134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.820374E+09 | 0.497142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.308690E+10 | 0.275114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.884353E+10 | 0.777862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 16367.27 | 0.123483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.308690E+10 | 0.208898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261214E+11 | 0.00 | 0.00 | 8698198.46 | 0.00 | 0.00 | 0.155108E+11 | 0.00 | 0.87 |
February | 0.334978E+11 | 0.00 | 0.00 | 1482648.90 | 0.00 | 0.00 | 0.422890E+10 | 0.00 | 0.86 |
March | 0.393835E+11 | 0.00 | 0.00 | 90162.29 | 0.00 | 0.00 | 0.428316E+09 | 0.00 | 0.86 |
April | 0.383158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
May | 0.355858E+11 | 0.00 | 0.00 | 0.00 | 2276306.47 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 0.159765E+11 | 870949.80 | 0.00 | 1160945.98 | 0.394204E+09 | 0.00 | 0.137258E+10 | 0.00 | 0.84 |
July | 0.129275E+11 | 1154514.45 | 0.00 | 3833373.98 | 0.472779E+09 | 0.00 | 0.264804E+10 | 0.00 | 0.83 |
August | 0.261072E+10 | 10297342.56 | 0.00 | 36161778.56 | 0.264712E+09 | 0.00 | 0.169919E+11 | 0.00 | 0.90 |
September | 0.311513E+09 | 51990952.33 | 0.00 | 67329173.80 | 3973518.94 | 0.00 | 0.310674E+11 | 0.00 | 1.04 |
October | 0.376173E+09 | 0.00 | 0.00 | 65250107.35 | 0.00 | 0.00 | 0.487916E+11 | 0.00 | 1.06 |
November | 0.525877E+09 | 0.00 | 0.00 | 59771946.59 | 0.00 | 0.00 | 0.470048E+11 | 0.00 | 1.05 |
December | 0.191284E+10 | 0.00 | 0.00 | 52523311.80 | 0.00 | 0.00 | 0.480950E+11 | 0.00 | 0.99 |
Annual Sum or Average | 0.207546E+12 | 64313759.14 | 0.00 | 0.296302E+09 | 0.113794E+10 | 0.00 | 0.216139E+12 | 0.00 | 0.92 |
Minimum of Months | 0.311513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Maximum of Months | 0.393835E+11 | 51990952.33 | 0.00 | 67329173.80 | 0.472779E+09 | 0.00 | 0.487916E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.483737E+10 | 0.00 | 0.00 | 4252198.15 | 0.00 | 0.671246E+09 | 0.271033E+10 | 0.00 | 3.14 |
February | 0.366289E+10 | 0.00 | 0.00 | 3683713.68 | 0.00 | 0.130777E+10 | 0.255952E+10 | 0.00 | 3.10 |
March | 0.431895E+10 | 0.00 | 0.00 | 3877712.30 | 0.00 | 0.105515E+10 | 0.209251E+10 | 0.00 | 3.00 |
April | 0.529175E+10 | 0.00 | 0.00 | 1058339.80 | 0.00 | 0.837942E+09 | 0.673902E+09 | 0.00 | 2.77 |
May | 0.575707E+10 | 436098.18 | 0.00 | 895420.51 | 0.00 | 0.00 | 0.494225E+09 | 0.00 | 2.72 |
June | 0.194400E+10 | 91106576.95 | 0.00 | 3711815.45 | 116091.88 | 0.00 | 0.111068E+10 | 0.00 | 2.80 |
July | 0.170618E+10 | 0.102793E+09 | 0.00 | 3816893.50 | 2278267.69 | 0.00 | 0.103637E+10 | 0.00 | 2.81 |
August | 0.187918E+10 | 75539670.77 | 0.00 | 5980691.42 | 0.00 | 0.00 | 0.143269E+10 | 0.00 | 3.04 |
September | 0.261302E+10 | 17318147.52 | 0.00 | 7564219.27 | 0.00 | 0.00 | 0.184008E+10 | 0.00 | 3.16 |
October | 0.388645E+10 | 0.00 | 0.00 | 5752324.85 | 0.00 | 0.865715E+09 | 0.285049E+10 | 0.00 | 3.16 |
November | 0.431247E+10 | 0.00 | 0.00 | 4529305.53 | 0.00 | 0.648448E+09 | 0.281654E+10 | 0.00 | 3.16 |
December | 0.470592E+10 | 0.00 | 0.00 | 3102977.00 | 0.00 | 0.166127E+10 | 0.189790E+10 | 0.00 | 3.01 |
Annual Sum or Average | 0.449153E+11 | 0.287193E+09 | 0.00 | 48225611.46 | 2394359.57 | 0.704754E+10 | 0.215152E+11 | 0.00 | 2.99 |
Minimum of Months | 0.170618E+10 | 0.00 | 0.00 | 895420.51 | 0.00 | 0.00 | 0.494225E+09 | 0.00 | 2.72 |
Maximum of Months | 0.575707E+10 | 0.102793E+09 | 0.00 | 7564219.27 | 2278267.69 | 0.166127E+10 | 0.285049E+10 | 0.00 | 3.16 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322072E+10 | 0.00 | 0.00 | 769861.16 | 0.00 | 0.00 | 0.126158E+10 | 0.00 | 1.46 |
February | 0.300112E+10 | 0.00 | 0.00 | 645423.71 | 0.00 | 0.00 | 0.108602E+10 | 0.00 | 1.45 |
March | 0.274682E+10 | 0.00 | 0.00 | 1545263.05 | 0.00 | 0.00 | 0.166205E+10 | 0.00 | 1.48 |
April | 0.291209E+10 | 0.00 | 0.00 | 870802.60 | 0.00 | 0.00 | 0.125465E+10 | 0.00 | 1.46 |
May | 0.141823E+10 | 142097.69 | 0.00 | 2302176.87 | 102439.51 | 0.00 | 0.254999E+10 | 0.00 | 1.49 |
June | 86486018.38 | 43035332.64 | 0.00 | 6153086.26 | 634101.87 | 0.00 | 0.215638E+10 | 0.00 | 1.66 |
July | 43162685.29 | 47513597.54 | 0.00 | 6244263.59 | 3816884.46 | 0.00 | 0.197070E+10 | 0.00 | 1.64 |
August | 91300353.92 | 30896552.67 | 0.00 | 6489248.80 | 267489.98 | 0.00 | 0.227280E+10 | 0.00 | 1.68 |
September | 0.254314E+09 | 6093717.47 | 0.00 | 6118009.62 | 323.84 | 0.00 | 0.280228E+10 | 0.00 | 1.65 |
October | 0.185943E+10 | 0.00 | 0.00 | 2563829.96 | 0.00 | 0.00 | 0.255338E+10 | 0.00 | 1.51 |
November | 0.268333E+10 | 0.00 | 0.00 | 1067709.15 | 0.00 | 0.00 | 0.154034E+10 | 0.00 | 1.47 |
December | 0.380592E+10 | 0.00 | 0.00 | 470656.41 | 0.00 | 0.00 | 0.836325E+09 | 0.00 | 1.44 |
Annual Sum or Average | 0.221229E+11 | 0.127681E+09 | 0.00 | 35240331.18 | 4821239.65 | 0.00 | 0.219465E+11 | 0.00 | 1.53 |
Minimum of Months | 43162685.29 | 0.00 | 0.00 | 470656.41 | 0.00 | 0.00 | 0.836325E+09 | 0.00 | 1.44 |
Maximum of Months | 0.380592E+10 | 47513597.54 | 0.00 | 6489248.80 | 3816884.46 | 0.00 | 0.280228E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140702E+09 | 0.00 | 0.00 | 0.56 |
February | 0.304776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270837E+09 | 0.00 | 0.00 | 0.55 |
March | 0.348343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18936874.05 | 0.00 | 0.00 | 0.56 |
April | 0.337008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 676909.04 | 0.00 | 0.00 | 0.56 |
May | 0.304992E+10 | 0.00 | 0.00 | 68993.92 | 200253.61 | 0.00 | 82766716.62 | 0.00 | 0.55 |
June | 0.469377E+09 | 32800103.43 | 0.00 | 3432402.06 | 2952391.07 | 0.00 | 0.120255E+10 | 0.00 | 0.60 |
July | 0.235985E+09 | 32259847.10 | 0.00 | 4284054.86 | 10416570.91 | 0.00 | 0.130203E+10 | 0.00 | 0.61 |
August | 0.492289E+09 | 19003634.26 | 0.00 | 3097859.08 | 5402234.60 | 0.00 | 0.125350E+10 | 0.00 | 0.60 |
September | 0.129222E+10 | 3022735.30 | 0.00 | 1827406.30 | 1886039.72 | 0.00 | 0.938386E+09 | 0.00 | 0.58 |
October | 0.335747E+10 | 0.00 | 0.00 | 14240.57 | 0.00 | 40352139.30 | 36362709.70 | 0.00 | 0.55 |
November | 0.335411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47486782.00 | 0.00 | 0.00 | 0.56 |
December | 0.306080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727679E+09 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.287079E+11 | 87086320.08 | 0.00 | 12724956.78 | 20857489.90 | 0.124667E+10 | 0.481559E+10 | 0.00 | 0.57 |
Minimum of Months | 0.235985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.349443E+10 | 32800103.43 | 0.00 | 4284054.86 | 10416570.91 | 0.727679E+09 | 0.130203E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178610E+09 | 0.00 | 0.00 | 0.52 |
February | 0.142580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377711E+09 | 0.00 | 0.00 | 0.52 |
March | 0.181590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87488211.20 | 0.00 | 0.00 | 0.52 |
April | 0.177279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59077359.56 | 0.00 | 0.00 | 0.52 |
May | 0.170134E+10 | 0.00 | 0.00 | 0.00 | 108829.34 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.482040E+09 | 16973427.75 | 0.00 | 989658.46 | 2689298.59 | 0.00 | 0.367861E+09 | 0.00 | 0.53 |
July | 0.297286E+09 | 17478366.84 | 0.00 | 1314181.27 | 6163701.16 | 0.00 | 0.474266E+09 | 0.00 | 0.54 |
August | 0.540894E+09 | 9872612.48 | 0.00 | 689492.82 | 3269984.45 | 0.00 | 0.354042E+09 | 0.00 | 0.53 |
September | 0.976394E+09 | 1632677.36 | 0.00 | 304610.89 | 1035033.67 | 0.00 | 0.196573E+09 | 0.00 | 0.52 |
October | 0.177521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91133738.89 | 0.00 | 0.00 | 0.52 |
November | 0.167564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172984E+09 | 0.00 | 0.00 | 0.52 |
December | 0.155125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507629E+09 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.158115E+11 | 45957084.44 | 0.00 | 3297943.43 | 13266847.21 | 0.147463E+10 | 0.139274E+10 | 0.00 | 0.53 |
Minimum of Months | 0.297286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.181590E+10 | 17478366.84 | 0.00 | 1314181.27 | 6163701.16 | 0.507629E+09 | 0.474266E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46640150.44 | 0.00 | 0.00 | 0.106932E+09 | 0.00 | 0.00 | 0.837498E+11 | 0.00 | 27.11 |
February | 81646754.46 | 0.00 | 0.00 | 95557654.75 | 0.00 | 0.00 | 0.759983E+11 | 0.00 | 26.96 |
March | 43349163.02 | 0.00 | 0.00 | 0.110859E+09 | 0.00 | 0.00 | 0.812381E+11 | 0.00 | 27.10 |
April | 25943779.93 | 0.00 | 0.00 | 0.105068E+09 | 0.00 | 0.00 | 0.775584E+11 | 0.00 | 26.99 |
May | 0.00 | 3690360.02 | 0.00 | 0.126329E+09 | 0.00 | 0.00 | 0.729711E+11 | 0.00 | 27.02 |
June | 0.00 | 0.658999E+09 | 0.00 | 0.134389E+09 | 0.00 | 0.00 | 0.345658E+11 | 0.00 | 26.34 |
July | 0.00 | 0.788785E+09 | 0.00 | 0.127426E+09 | 0.00 | 0.00 | 0.310199E+11 | 0.00 | 26.13 |
August | 0.00 | 0.458922E+09 | 0.00 | 0.138107E+09 | 0.00 | 0.00 | 0.371814E+11 | 0.00 | 26.73 |
September | 0.00 | 91703381.06 | 0.00 | 0.131845E+09 | 0.00 | 0.00 | 0.502097E+11 | 0.00 | 26.89 |
October | 29411900.58 | 0.00 | 0.00 | 0.113837E+09 | 0.00 | 0.00 | 0.800292E+11 | 0.00 | 26.96 |
November | 14248211.19 | 0.00 | 0.00 | 0.104215E+09 | 0.00 | 0.00 | 0.784412E+11 | 0.00 | 27.08 |
December | 89139536.09 | 0.00 | 0.00 | 0.105148E+09 | 0.00 | 0.00 | 0.867811E+11 | 0.00 | 26.78 |
Annual Sum or Average | 0.330379E+09 | 0.200210E+10 | 0.00 | 0.139971E+10 | 0.00 | 0.00 | 0.789744E+12 | 0.00 | 26.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 95557654.75 | 0.00 | 0.00 | 0.310199E+11 | 0.00 | 26.13 |
Maximum of Months | 89139536.09 | 0.788785E+09 | 0.00 | 0.138107E+09 | 0.00 | 0.00 | 0.867811E+11 | 0.00 | 27.11 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.709180E+10 | 0.00 | 0.00 | 32352778.08 | 0.00 | 29145313.11 | 0.280139E+11 | 0.00 | 4.78 |
February | 0.779518E+10 | 0.00 | 0.00 | 27217475.95 | 0.00 | 0.171928E+09 | 0.241962E+11 | 0.00 | 4.72 |
March | 0.867220E+10 | 0.00 | 0.00 | 30351503.71 | 0.00 | 0.00 | 0.238658E+11 | 0.00 | 4.61 |
April | 0.110374E+11 | 0.00 | 0.00 | 18175644.85 | 0.00 | 0.00 | 0.183845E+11 | 0.00 | 4.27 |
May | 0.400425E+10 | 1861982.30 | 0.00 | 26490081.97 | 0.00 | 0.00 | 0.233158E+11 | 0.00 | 4.24 |
June | 0.616174E+09 | 0.342186E+09 | 0.00 | 39127141.88 | 444936.42 | 0.00 | 0.141073E+11 | 0.00 | 4.54 |
July | 0.357632E+09 | 0.403562E+09 | 0.00 | 39686067.93 | 94803.99 | 0.00 | 0.129666E+11 | 0.00 | 4.56 |
August | 0.596700E+09 | 0.278980E+09 | 0.00 | 47365295.54 | 0.00 | 0.00 | 0.153324E+11 | 0.00 | 4.86 |
September | 0.814858E+09 | 61501661.08 | 0.00 | 52350876.28 | 0.00 | 0.00 | 0.202372E+11 | 0.00 | 4.99 |
October | 0.674502E+10 | 0.00 | 0.00 | 40184585.34 | 0.00 | 0.140218E+09 | 0.262581E+11 | 0.00 | 4.83 |
November | 0.635807E+10 | 0.00 | 0.00 | 33319057.86 | 0.00 | 0.00 | 0.269696E+11 | 0.00 | 4.81 |
December | 0.116545E+11 | 0.00 | 0.00 | 24328199.10 | 0.00 | 0.538223E+09 | 0.230848E+11 | 0.00 | 4.57 |
Annual Sum or Average | 0.657438E+11 | 0.108809E+10 | 0.00 | 0.410949E+09 | 539740.41 | 0.879514E+09 | 0.256732E+12 | 0.00 | 4.65 |
Minimum of Months | 0.357632E+09 | 0.00 | 0.00 | 18175644.85 | 0.00 | 0.00 | 0.129666E+11 | 0.00 | 4.24 |
Maximum of Months | 0.116545E+11 | 0.403562E+09 | 0.00 | 52350876.28 | 444936.42 | 0.538223E+09 | 0.280139E+11 | 0.00 | 4.99 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225566E+11 | 0.00 | 0.00 | 81171436.43 | 0.00 | 0.00 | 0.782716E+11 | 0.00 | 1.96 |
February | 0.269862E+11 | 0.00 | 0.00 | 62645089.56 | 0.00 | 0.00 | 0.644781E+11 | 0.00 | 1.94 |
March | 0.295153E+11 | 0.00 | 0.00 | 79309027.26 | 0.00 | 0.00 | 0.696557E+11 | 0.00 | 1.98 |
April | 0.338317E+11 | 0.00 | 0.00 | 54019166.22 | 0.00 | 0.00 | 0.593986E+11 | 0.00 | 1.93 |
May | 0.130263E+11 | 5273921.65 | 0.00 | 94702151.69 | 0.00 | 0.00 | 0.796867E+11 | 0.00 | 2.04 |
June | 0.958011E+09 | 0.936402E+09 | 0.00 | 0.149194E+09 | 6329968.39 | 0.00 | 0.516606E+11 | 0.00 | 2.21 |
July | 0.451464E+09 | 0.109634E+10 | 0.00 | 0.153369E+09 | 23020170.79 | 0.00 | 0.473212E+11 | 0.00 | 2.21 |
August | 0.842045E+09 | 0.700058E+09 | 0.00 | 0.163843E+09 | 1010680.04 | 0.00 | 0.548715E+11 | 0.00 | 2.27 |
September | 0.138853E+10 | 0.143091E+09 | 0.00 | 0.170140E+09 | 0.00 | 0.00 | 0.706516E+11 | 0.00 | 2.26 |
October | 0.169308E+11 | 0.00 | 0.00 | 0.117670E+09 | 0.00 | 0.00 | 0.846310E+11 | 0.00 | 2.07 |
November | 0.196193E+11 | 0.00 | 0.00 | 89248678.00 | 0.00 | 0.00 | 0.766025E+11 | 0.00 | 1.99 |
December | 0.418023E+11 | 0.00 | 0.00 | 59698388.74 | 0.00 | 0.00 | 0.615540E+11 | 0.00 | 1.92 |
Annual Sum or Average | 0.207908E+12 | 0.288117E+10 | 0.00 | 0.127501E+10 | 30360819.22 | 0.00 | 0.798783E+12 | 0.00 | 2.07 |
Minimum of Months | 0.451464E+09 | 0.00 | 0.00 | 54019166.22 | 0.00 | 0.00 | 0.473212E+11 | 0.00 | 1.92 |
Maximum of Months | 0.418023E+11 | 0.109634E+10 | 0.00 | 0.170140E+09 | 23020170.79 | 0.00 | 0.846310E+11 | 0.00 | 2.27 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26883376.10 | 0.00 | 0.00 | 3854474.78 | 0.00 | 0.968665E+09 | 0.487499E+09 | 0.00 | 0.36 |
February | 22981913.21 | 0.00 | 0.00 | 3727322.24 | 0.00 | 0.874253E+09 | 0.449638E+09 | 0.00 | 0.36 |
March | 38808234.99 | 0.00 | 0.00 | 7842944.02 | 0.00 | 0.734583E+09 | 0.637039E+09 | 0.00 | 0.36 |
April | 41945540.93 | 0.00 | 0.00 | 5821183.86 | 0.00 | 0.674517E+09 | 0.612604E+09 | 0.00 | 0.36 |
May | 17676655.19 | 19060.73 | 0.00 | 13312896.44 | 0.00 | 99229724.48 | 0.106123E+10 | 0.00 | 0.35 |
June | 0.00 | 12641331.94 | 0.00 | 19378170.04 | 0.00 | 734855.80 | 0.578837E+09 | 0.00 | 0.35 |
July | 0.00 | 39349150.03 | 1322.64 | 16008935.17 | 0.00 | 532074.66 | 0.459921E+09 | 746.24 | 0.35 |
August | 0.00 | 39086151.60 | 18375.77 | 18594410.59 | 0.00 | 1059461.04 | 0.524192E+09 | 1126.04 | 0.35 |
September | 3327908.30 | 399939.32 | 0.00 | 18646111.76 | 0.00 | 39443771.59 | 0.833260E+09 | 0.00 | 0.35 |
October | 14755987.25 | 0.00 | 0.00 | 10670427.75 | 0.00 | 0.463773E+09 | 0.885286E+09 | 0.00 | 0.35 |
November | 22828013.97 | 0.00 | 0.00 | 4790014.78 | 0.00 | 0.755847E+09 | 0.610583E+09 | 0.00 | 0.36 |
December | 40576172.76 | 0.00 | 0.00 | 2194145.16 | 0.00 | 0.119506E+10 | 0.315782E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.229784E+09 | 91495633.62 | 19698.41 | 0.124841E+09 | 0.00 | 0.580769E+10 | 0.745587E+10 | 1872.28 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2194145.16 | 0.00 | 532074.66 | 0.315782E+09 | 0.00 | 0.35 |
Maximum of Months | 41945540.93 | 39349150.03 | 18375.77 | 19378170.04 | 0.00 | 0.119506E+10 | 0.106123E+10 | 1126.04 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 81291532.93 | 0.00 | 0.00 | 1257794.31 | 0.00 | 0.126751E+10 | 0.136672E+09 | 0.00 | 0.36 |
February | 67584779.12 | 0.00 | 0.00 | 1398554.60 | 0.00 | 0.110530E+10 | 0.176158E+09 | 0.00 | 0.36 |
March | 0.104416E+09 | 0.00 | 0.00 | 3833262.37 | 0.00 | 0.874688E+09 | 0.435170E+09 | 0.00 | 0.36 |
April | 0.124079E+09 | 0.00 | 0.00 | 3458238.92 | 0.00 | 0.738494E+09 | 0.468701E+09 | 0.00 | 0.36 |
May | 0.187250E+09 | 19058.50 | 0.00 | 9361645.95 | 0.00 | 0.109066E+09 | 0.885627E+09 | 0.00 | 0.35 |
June | 0.137562E+09 | 10801581.70 | 7348.17 | 15620071.06 | 1826113.88 | 743078.64 | 0.444955E+09 | 4807.07 | 0.35 |
July | 0.133916E+09 | 31578915.34 | 9120.87 | 11970855.30 | 7754255.94 | 516601.09 | 0.330003E+09 | 4316.18 | 0.35 |
August | 0.152746E+09 | 35653447.95 | 34765.89 | 13273282.76 | 3407656.76 | 903798.56 | 0.376858E+09 | 5201.01 | 0.35 |
September | 0.199194E+09 | 310673.45 | 0.00 | 11974394.35 | 89219.01 | 47703005.68 | 0.635701E+09 | 0.00 | 0.35 |
October | 0.132434E+09 | 0.00 | 0.00 | 4903348.56 | 0.00 | 0.616457E+09 | 0.620530E+09 | 0.00 | 0.35 |
November | 79908247.73 | 0.00 | 0.00 | 1610555.18 | 0.00 | 0.106578E+10 | 0.246582E+09 | 0.00 | 0.36 |
December | 63225819.25 | 0.00 | 0.00 | 616743.23 | 0.00 | 0.141226E+10 | 77326460.83 | 0.00 | 0.35 |
Annual Sum or Average | 0.146361E+10 | 78363676.95 | 51234.93 | 79278746.59 | 13077245.60 | 0.723942E+10 | 0.483428E+10 | 14324.26 | 0.35 |
Minimum of Months | 63225819.25 | 0.00 | 0.00 | 616743.23 | 0.00 | 516601.09 | 77326460.83 | 0.00 | 0.35 |
Maximum of Months | 0.199194E+09 | 35653447.95 | 34765.89 | 15620071.06 | 7754255.94 | 0.141226E+10 | 0.885627E+09 | 5201.01 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198078E+09 | 0.00 | 0.00 | 5905611.12 | 0.00 | 0.00 | 0.134179E+10 | 0.00 | 0.02 |
February | 0.223931E+09 | 0.00 | 0.00 | 3835052.79 | 0.00 | 0.00 | 0.107697E+10 | 0.00 | 0.02 |
March | 0.406933E+09 | 0.00 | 0.00 | 3730007.17 | 0.00 | 0.00 | 0.951182E+09 | 0.00 | 0.02 |
April | 0.704644E+09 | 0.00 | 0.00 | 1455845.32 | 0.00 | 0.00 | 0.598757E+09 | 0.00 | 0.02 |
May | 0.120885E+09 | 0.00 | 0.00 | 2927902.79 | 0.00 | 0.00 | 0.104718E+10 | 0.00 | 0.02 |
June | 0.00 | 40641161.65 | 0.00 | 3580278.45 | 0.00 | 0.00 | 0.240109E+09 | 0.00 | 0.02 |
July | 0.00 | 0.111896E+09 | 0.00 | 3026595.93 | 0.00 | 0.00 | 0.168939E+09 | 0.00 | 0.02 |
August | 0.00 | 75073260.96 | 0.00 | 4558013.97 | 0.00 | 0.00 | 0.242979E+09 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.00 | 6454489.92 | 0.00 | 0.00 | 0.634659E+09 | 0.00 | 0.02 |
October | 0.356625E+09 | 0.00 | 0.00 | 5849556.22 | 0.00 | 0.00 | 0.109513E+10 | 0.00 | 0.02 |
November | 0.247808E+09 | 0.00 | 0.00 | 4638734.81 | 0.00 | 0.00 | 0.119246E+10 | 0.00 | 0.02 |
December | 0.460180E+09 | 0.00 | 0.00 | 3666224.49 | 0.00 | 0.00 | 0.976512E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.271908E+10 | 0.227610E+09 | 0.00 | 49628312.98 | 0.00 | 0.00 | 0.956667E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1455845.32 | 0.00 | 0.00 | 0.168939E+09 | 0.00 | 0.02 |
Maximum of Months | 0.704644E+09 | 0.111896E+09 | 0.00 | 6454489.92 | 0.00 | 0.00 | 0.134179E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118456E+10 | 0.00 | 0.00 | 10765635.65 | 0.00 | 0.114550E+11 | 0.751622E+10 | 0.00 | 0.41 |
February | 0.108773E+10 | 0.00 | 0.00 | 9448690.12 | 0.00 | 0.117467E+11 | 0.547409E+10 | 0.00 | 0.40 |
March | 0.166047E+10 | 0.00 | 0.00 | 33109054.39 | 0.00 | 0.636486E+10 | 0.111773E+11 | 0.00 | 0.40 |
April | 0.175906E+10 | 0.00 | 0.00 | 44914147.83 | 0.00 | 0.324448E+10 | 0.130564E+11 | 0.00 | 0.40 |
May | 0.291015E+10 | 258517.10 | 0.00 | 0.120890E+09 | 0.00 | 30487411.91 | 0.130978E+11 | 0.00 | 0.40 |
June | 0.188552E+10 | 0.145646E+09 | 220859.67 | 0.160826E+09 | 25569486.21 | 2531336.16 | 0.607457E+10 | 15350.46 | 0.40 |
July | 0.183643E+10 | 0.428508E+09 | 18558.17 | 0.124893E+09 | 0.105182E+09 | 975688.08 | 0.449986E+10 | 4364.50 | 0.40 |
August | 0.214271E+10 | 0.481055E+09 | 427585.97 | 0.129570E+09 | 48868785.75 | 2434360.81 | 0.510137E+10 | 30900.49 | 0.40 |
September | 0.286779E+10 | 3922755.20 | 288884.52 | 0.124619E+09 | 1210202.32 | 17662508.79 | 0.912427E+10 | 2459.32 | 0.40 |
October | 0.206141E+10 | 0.00 | 0.00 | 48273935.12 | 0.00 | 0.307817E+10 | 0.134540E+11 | 0.00 | 0.40 |
November | 0.129545E+10 | 0.00 | 0.00 | 17139216.72 | 0.00 | 0.848868E+10 | 0.910594E+10 | 0.00 | 0.40 |
December | 0.104055E+10 | 0.00 | 0.00 | 7754332.61 | 0.00 | 0.142320E+11 | 0.579103E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.217318E+11 | 0.105939E+10 | 955888.34 | 0.832204E+09 | 0.180830E+09 | 0.586639E+11 | 0.103473E+12 | 53074.77 | 0.40 |
Minimum of Months | 0.104055E+10 | 0.00 | 0.00 | 7754332.61 | 0.00 | 975688.08 | 0.449986E+10 | 0.00 | 0.40 |
Maximum of Months | 0.291015E+10 | 0.481055E+09 | 427585.97 | 0.160826E+09 | 0.105182E+09 | 0.142320E+11 | 0.134540E+11 | 30900.49 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29183533.00 | 0.00 | 0.00 | 4211577.91 | 0.00 | 0.982738E+09 | 0.470768E+09 | 0.00 | 0.36 |
February | 22753270.40 | 0.00 | 0.00 | 4451993.20 | 0.00 | 0.861537E+09 | 0.461858E+09 | 0.00 | 0.36 |
March | 31324160.98 | 0.00 | 0.00 | 7834835.47 | 0.00 | 0.715712E+09 | 0.663402E+09 | 0.00 | 0.36 |
April | 34509966.74 | 0.00 | 0.00 | 6250541.07 | 0.00 | 0.668984E+09 | 0.625143E+09 | 0.00 | 0.36 |
May | 9274106.31 | 19060.73 | 0.00 | 14082702.56 | 0.00 | 85476130.02 | 0.108261E+10 | 0.00 | 0.35 |
June | 0.00 | 12628667.04 | 12171.83 | 22146983.85 | 0.00 | 125235.13 | 0.576678E+09 | 493.07 | 0.35 |
July | 0.00 | 39313193.24 | 36393.40 | 18136606.21 | 0.00 | 186863.34 | 0.458138E+09 | 1632.27 | 0.35 |
August | 0.00 | 39105653.42 | 0.00 | 21707254.77 | 0.00 | 332186.14 | 0.521806E+09 | 0.00 | 0.35 |
September | 3327908.30 | 399939.32 | 0.00 | 19610369.43 | 0.00 | 38567466.16 | 0.833172E+09 | 0.00 | 0.35 |
October | 13141465.57 | 0.00 | 0.00 | 9769248.62 | 0.00 | 0.491773E+09 | 0.859802E+09 | 0.00 | 0.35 |
November | 24810878.09 | 0.00 | 0.00 | 5096518.20 | 0.00 | 0.780827E+09 | 0.583314E+09 | 0.00 | 0.36 |
December | 40376070.43 | 0.00 | 0.00 | 2627686.62 | 0.00 | 0.118867E+10 | 0.321934E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.208701E+09 | 91466513.75 | 48565.22 | 0.135926E+09 | 0.00 | 0.581493E+10 | 0.745863E+10 | 2125.33 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2627686.62 | 0.00 | 125235.13 | 0.321934E+09 | 0.00 | 0.35 |
Maximum of Months | 40376070.43 | 39313193.24 | 36393.40 | 22146983.85 | 0.00 | 0.118867E+10 | 0.108261E+10 | 1632.27 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 78708067.18 | 0.00 | 0.00 | 1126928.62 | 0.00 | 0.122603E+10 | 0.180867E+09 | 0.00 | 0.36 |
February | 65598074.22 | 0.00 | 0.00 | 1733892.07 | 0.00 | 0.105855E+10 | 0.224560E+09 | 0.00 | 0.36 |
March | 97958410.86 | 0.00 | 0.00 | 4158071.69 | 0.00 | 0.843981E+09 | 0.472009E+09 | 0.00 | 0.36 |
April | 0.104162E+09 | 0.00 | 0.00 | 4222661.36 | 0.00 | 0.736481E+09 | 0.489866E+09 | 0.00 | 0.36 |
May | 0.170529E+09 | 19058.50 | 0.00 | 10531107.41 | 0.00 | 91604864.31 | 0.918640E+09 | 0.00 | 0.35 |
June | 0.131476E+09 | 10795525.63 | 22881.88 | 16980921.40 | 1820827.30 | 268013.56 | 0.450155E+09 | 616.01 | 0.35 |
July | 0.131206E+09 | 31550347.92 | 42183.14 | 12904275.09 | 7750552.21 | 266489.82 | 0.332030E+09 | 3525.07 | 0.35 |
August | 0.145022E+09 | 35691361.48 | 1759.95 | 15369168.33 | 3407656.76 | 353172.61 | 0.383037E+09 | 293.42 | 0.35 |
September | 0.191302E+09 | 289673.65 | 20654.00 | 12970686.61 | 89219.01 | 45997241.54 | 0.644303E+09 | 345.80 | 0.35 |
October | 0.124129E+09 | 0.00 | 0.00 | 4933672.72 | 0.00 | 0.649133E+09 | 0.596129E+09 | 0.00 | 0.35 |
November | 83233947.55 | 0.00 | 0.00 | 1807405.54 | 0.00 | 0.105476E+10 | 0.254088E+09 | 0.00 | 0.36 |
December | 64363879.99 | 0.00 | 0.00 | 680680.14 | 0.00 | 0.137664E+10 | 0.111746E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.138769E+10 | 78345967.17 | 87478.97 | 87419470.97 | 13068255.29 | 0.708405E+10 | 0.505743E+10 | 4780.30 | 0.35 |
Minimum of Months | 64363879.99 | 0.00 | 0.00 | 680680.14 | 0.00 | 266489.82 | 0.111746E+09 | 0.00 | 0.35 |
Maximum of Months | 0.191302E+09 | 35691361.48 | 42183.14 | 16980921.40 | 7750552.21 | 0.137664E+10 | 0.918640E+09 | 3525.07 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110606E+10 | 0.00 | 0.00 | 0.53 |
February | 0.199170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303109E+10 | 0.00 | 0.00 | 0.53 |
March | 0.235910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627943E+09 | 0.00 | 0.00 | 0.53 |
April | 0.227929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515941E+09 | 0.00 | 0.00 | 0.53 |
May | 0.216481E+11 | 0.00 | 0.00 | 0.00 | 1384757.51 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.448408E+10 | 0.264120E+09 | 0.00 | 15894185.34 | 8812462.54 | 0.00 | 0.642206E+10 | 0.00 | 0.55 |
July | 0.251257E+10 | 0.259663E+09 | 0.00 | 20876588.51 | 58924321.85 | 0.00 | 0.738617E+10 | 0.00 | 0.55 |
August | 0.413344E+10 | 0.189440E+09 | 0.00 | 18009921.14 | 3899768.22 | 0.00 | 0.742345E+10 | 0.00 | 0.55 |
September | 0.893705E+10 | 37131300.79 | 0.00 | 13127041.03 | 1790725.87 | 0.00 | 0.611604E+10 | 0.00 | 0.54 |
October | 0.227272E+11 | 0.00 | 0.00 | 10240.42 | 0.00 | 0.100404E+10 | 16372359.75 | 0.00 | 0.53 |
November | 0.221340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138805E+10 | 0.00 | 0.00 | 0.53 |
December | 0.206211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557636E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.197529E+12 | 0.750354E+09 | 0.00 | 67917976.45 | 74812035.99 | 0.132495E+11 | 0.273641E+11 | 0.00 | 0.53 |
Minimum of Months | 0.251257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.240310E+11 | 0.264120E+09 | 0.00 | 20876588.51 | 58924321.85 | 0.557636E+10 | 0.742345E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8463818.18 | 0.00 | 0.00 | 863023.05 | 0.00 | 0.283032E+09 | 79366637.18 | 0.00 | 0.36 |
February | 6357241.47 | 0.00 | 0.00 | 834224.10 | 0.00 | 0.250624E+09 | 79834958.47 | 0.00 | 0.36 |
March | 7515547.33 | 0.00 | 0.00 | 1896165.13 | 0.00 | 0.217036E+09 | 0.128121E+09 | 0.00 | 0.36 |
April | 8740653.02 | 0.00 | 0.00 | 1435235.00 | 0.00 | 0.208631E+09 | 0.114915E+09 | 0.00 | 0.36 |
May | 4707226.38 | 4765.18 | 0.00 | 3187915.08 | 0.00 | 57990845.39 | 0.231975E+09 | 0.00 | 0.35 |
June | 0.00 | 3160332.98 | 0.00 | 4689050.29 | 0.00 | 371250.22 | 0.144677E+09 | 0.00 | 0.35 |
July | 0.00 | 9837287.51 | 273.05 | 3794294.59 | 0.00 | 128180.27 | 0.115193E+09 | 244.17 | 0.35 |
August | 0.00 | 9771537.90 | 4703.02 | 4478458.48 | 0.00 | 245041.98 | 0.131238E+09 | 172.43 | 0.35 |
September | 1075911.93 | 99984.83 | 0.00 | 4373523.06 | 0.00 | 17880600.19 | 0.200339E+09 | 0.00 | 0.35 |
October | 3428199.04 | 0.00 | 0.00 | 2463374.99 | 0.00 | 0.171070E+09 | 0.166660E+09 | 0.00 | 0.35 |
November | 4569083.42 | 0.00 | 0.00 | 1057575.31 | 0.00 | 0.236745E+09 | 0.106141E+09 | 0.00 | 0.36 |
December | 8079686.80 | 0.00 | 0.00 | 468882.60 | 0.00 | 0.324373E+09 | 55480550.09 | 0.00 | 0.35 |
Annual Sum or Average | 52937367.56 | 22873908.41 | 4976.07 | 29541721.68 | 0.00 | 0.176813E+10 | 0.155394E+10 | 416.60 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 468882.60 | 0.00 | 128180.27 | 55480550.09 | 0.00 | 0.35 |
Maximum of Months | 8740653.02 | 9837287.51 | 4703.02 | 4689050.29 | 0.00 | 0.324373E+09 | 0.231975E+09 | 244.17 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18734526.50 | 0.00 | 0.00 | 250022.68 | 0.00 | 0.333287E+09 | 19410641.95 | 0.00 | 0.36 |
February | 14878175.51 | 0.00 | 0.00 | 293182.38 | 0.00 | 0.297369E+09 | 25070082.89 | 0.00 | 0.36 |
March | 23881243.86 | 0.00 | 0.00 | 896371.56 | 0.00 | 0.246866E+09 | 82882802.84 | 0.00 | 0.36 |
April | 27830340.86 | 0.00 | 0.00 | 840676.96 | 0.00 | 0.219696E+09 | 85315462.27 | 0.00 | 0.36 |
May | 46264204.14 | 4764.62 | 0.00 | 2217644.85 | 0.00 | 53379881.82 | 0.195965E+09 | 0.00 | 0.35 |
June | 34254172.96 | 2700395.43 | 2191.32 | 3881945.95 | 456528.47 | 187439.83 | 0.111396E+09 | 847.49 | 0.35 |
July | 33381877.82 | 7894512.58 | 2672.62 | 2916462.58 | 1938563.99 | 146695.01 | 82656485.31 | 902.90 | 0.35 |
August | 37854065.82 | 8916215.62 | 5907.05 | 3260634.92 | 851914.19 | 230536.75 | 94600244.33 | 1231.05 | 0.35 |
September | 49725631.43 | 77668.36 | 0.00 | 2777883.97 | 22304.75 | 19213553.44 | 0.151926E+09 | 0.00 | 0.35 |
October | 33107693.24 | 0.00 | 0.00 | 1053659.74 | 0.00 | 0.210229E+09 | 99191054.45 | 0.00 | 0.35 |
November | 18876059.36 | 0.00 | 0.00 | 349066.49 | 0.00 | 0.296775E+09 | 32470720.89 | 0.00 | 0.36 |
December | 13741395.41 | 0.00 | 0.00 | 124464.78 | 0.00 | 0.364949E+09 | 9541790.21 | 0.00 | 0.35 |
Annual Sum or Average | 0.352529E+09 | 19593556.61 | 10771.00 | 18862016.86 | 3269311.40 | 0.204233E+10 | 0.990426E+09 | 2981.43 | 0.35 |
Minimum of Months | 13741395.41 | 0.00 | 0.00 | 124464.78 | 0.00 | 146695.01 | 9541790.21 | 0.00 | 0.35 |
Maximum of Months | 49725631.43 | 8916215.62 | 5907.05 | 3881945.95 | 1938563.99 | 0.364949E+09 | 0.195965E+09 | 1231.05 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12176471.86 | 0.00 | 0.00 | 15352022.83 | 0.00 | 0.943431E+09 | 0.141719E+10 | 0.00 | 0.41 |
February | 7770435.06 | 0.00 | 0.00 | 11940685.19 | 0.00 | 0.105363E+10 | 0.109588E+10 | 0.00 | 0.40 |
March | 29208457.70 | 0.00 | 0.00 | 14595974.47 | 0.00 | 0.989661E+09 | 0.124446E+10 | 0.00 | 0.40 |
April | 41399863.06 | 0.00 | 0.00 | 8873080.24 | 0.00 | 0.990089E+09 | 0.110363E+10 | 0.00 | 0.40 |
May | 11065568.24 | 30613.87 | 0.00 | 16970739.16 | 0.00 | 0.158910E+09 | 0.172666E+10 | 0.00 | 0.40 |
June | 0.00 | 20303525.58 | 0.00 | 23191312.50 | 0.00 | 3038942.51 | 0.935757E+09 | 0.00 | 0.40 |
July | 0.00 | 63139856.70 | 57844.49 | 20135715.88 | 0.00 | 997693.39 | 0.744123E+09 | 5170.43 | 0.40 |
August | 0.00 | 62808463.40 | 0.00 | 25018457.88 | 0.00 | 1994956.28 | 0.846469E+09 | 0.00 | 0.40 |
September | 1887112.45 | 642351.48 | 0.00 | 28268879.77 | 0.00 | 55244728.96 | 0.135156E+10 | 0.00 | 0.40 |
October | 19357072.14 | 0.00 | 0.00 | 20840130.46 | 0.00 | 0.621189E+09 | 0.154621E+10 | 0.00 | 0.40 |
November | 17905403.77 | 0.00 | 0.00 | 15893922.37 | 0.00 | 0.779008E+09 | 0.142620E+10 | 0.00 | 0.40 |
December | 31108098.48 | 0.00 | 0.00 | 10300168.95 | 0.00 | 0.137980E+10 | 0.107408E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.171878E+09 | 0.146925E+09 | 57844.49 | 0.211381E+09 | 0.00 | 0.697700E+10 | 0.145122E+11 | 5170.43 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8873080.24 | 0.00 | 997693.39 | 0.744123E+09 | 0.00 | 0.40 |
Maximum of Months | 41399863.06 | 63139856.70 | 57844.49 | 28268879.77 | 0.00 | 0.137980E+10 | 0.172666E+10 | 5170.43 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242621E+10 | 0.00 | 0.00 | 53314411.16 | 0.00 | 0.00 | 0.482254E+11 | 0.00 | 5.05 |
February | 0.267623E+10 | 0.00 | 0.00 | 47330973.23 | 0.00 | 0.00 | 0.433838E+11 | 0.00 | 5.01 |
March | 0.934259E+09 | 0.00 | 0.00 | 66097406.64 | 0.00 | 0.00 | 0.510515E+11 | 0.00 | 5.32 |
April | 0.550049E+09 | 0.00 | 0.00 | 66661724.87 | 0.00 | 0.00 | 0.504122E+11 | 0.00 | 5.40 |
May | 31698887.42 | 3156339.45 | 0.00 | 95456071.35 | 0.00 | 0.00 | 0.535272E+11 | 0.00 | 5.97 |
June | 0.00 | 0.568176E+09 | 0.00 | 0.107687E+09 | 0.00 | 0.00 | 0.300331E+11 | 0.00 | 6.48 |
July | 0.00 | 0.656641E+09 | 0.00 | 0.103642E+09 | 0.00 | 0.00 | 0.270771E+11 | 0.00 | 6.44 |
August | 0.00 | 0.394842E+09 | 0.00 | 0.109314E+09 | 0.00 | 0.00 | 0.308949E+11 | 0.00 | 6.42 |
September | 5220871.67 | 74430849.57 | 0.00 | 0.100152E+09 | 0.00 | 0.00 | 0.389691E+11 | 0.00 | 6.16 |
October | 0.125927E+10 | 0.00 | 0.00 | 73087913.45 | 0.00 | 0.00 | 0.511483E+11 | 0.00 | 5.43 |
November | 0.197121E+10 | 0.00 | 0.00 | 56576156.66 | 0.00 | 0.00 | 0.465851E+11 | 0.00 | 5.15 |
December | 0.576035E+10 | 0.00 | 0.00 | 46979278.64 | 0.00 | 0.00 | 0.457863E+11 | 0.00 | 4.92 |
Annual Sum or Average | 0.156145E+11 | 0.169725E+10 | 0.00 | 0.926299E+09 | 0.00 | 0.00 | 0.517094E+12 | 0.00 | 5.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 46979278.64 | 0.00 | 0.00 | 0.270771E+11 | 0.00 | 4.92 |
Maximum of Months | 0.576035E+10 | 0.656641E+09 | 0.00 | 0.109314E+09 | 0.00 | 0.00 | 0.535272E+11 | 0.00 | 6.48 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.916138E+09 | 0.00 | 0.00 | 68025661.88 | 0.00 | 0.00 | 0.547662E+11 | 0.00 | 5.55 |
February | 0.573410E+09 | 0.00 | 0.00 | 60289125.69 | 0.00 | 0.00 | 0.500434E+11 | 0.00 | 5.50 |
March | 0.183405E+09 | 0.00 | 0.00 | 80099076.72 | 0.00 | 0.00 | 0.568742E+11 | 0.00 | 5.83 |
April | 89910878.44 | 0.00 | 0.00 | 79867507.30 | 0.00 | 0.00 | 0.560894E+11 | 0.00 | 5.95 |
May | 0.00 | 3452543.53 | 0.00 | 0.105793E+09 | 0.00 | 0.00 | 0.581772E+11 | 0.00 | 6.51 |
June | 0.00 | 0.610714E+09 | 0.00 | 0.115148E+09 | 0.00 | 0.00 | 0.318089E+11 | 0.00 | 6.91 |
July | 0.00 | 0.708268E+09 | 0.00 | 0.110648E+09 | 0.00 | 0.00 | 0.286284E+11 | 0.00 | 6.86 |
August | 0.00 | 0.424129E+09 | 0.00 | 0.117106E+09 | 0.00 | 0.00 | 0.327712E+11 | 0.00 | 6.85 |
September | 0.00 | 80146824.57 | 0.00 | 0.108697E+09 | 0.00 | 0.00 | 0.416817E+11 | 0.00 | 6.61 |
October | 0.271446E+09 | 0.00 | 0.00 | 85068549.69 | 0.00 | 0.00 | 0.568955E+11 | 0.00 | 5.92 |
November | 0.664974E+09 | 0.00 | 0.00 | 69793968.07 | 0.00 | 0.00 | 0.527007E+11 | 0.00 | 5.65 |
December | 0.333829E+10 | 0.00 | 0.00 | 61179339.43 | 0.00 | 0.00 | 0.531058E+11 | 0.00 | 5.39 |
Annual Sum or Average | 0.603758E+10 | 0.182671E+10 | 0.00 | 0.106171E+10 | 0.00 | 0.00 | 0.573543E+12 | 0.00 | 6.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 60289125.69 | 0.00 | 0.00 | 0.286284E+11 | 0.00 | 5.39 |
Maximum of Months | 0.333829E+10 | 0.708268E+09 | 0.00 | 0.117106E+09 | 0.00 | 0.00 | 0.581772E+11 | 0.00 | 6.91 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.114943E+09 | 0.00 | 0.00 | 0.770399E+11 | 0.00 | 24.71 |
February | 0.00 | 0.00 | 0.00 | 0.103109E+09 | 0.00 | 0.00 | 0.702046E+11 | 0.00 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.121937E+09 | 0.00 | 0.00 | 0.744667E+11 | 0.00 | 25.10 |
April | 0.00 | 0.00 | 0.00 | 0.115192E+09 | 0.00 | 0.00 | 0.717365E+11 | 0.00 | 25.24 |
May | 0.00 | 5406774.24 | 0.00 | 0.141393E+09 | 0.00 | 0.00 | 0.655004E+11 | 0.00 | 26.04 |
June | 0.00 | 0.939600E+09 | 0.00 | 0.144573E+09 | 0.00 | 0.00 | 0.298793E+11 | 0.00 | 26.31 |
July | 0.00 | 0.112692E+10 | 0.00 | 0.137022E+09 | 0.00 | 0.00 | 0.263238E+11 | 0.00 | 26.11 |
August | 0.00 | 0.651679E+09 | 0.00 | 0.152506E+09 | 0.00 | 0.00 | 0.326757E+11 | 0.00 | 26.43 |
September | 0.00 | 0.129476E+09 | 0.00 | 0.144836E+09 | 0.00 | 0.00 | 0.433757E+11 | 0.00 | 26.13 |
October | 0.00 | 0.00 | 0.00 | 0.126725E+09 | 0.00 | 0.00 | 0.730732E+11 | 0.00 | 24.99 |
November | 0.00 | 0.00 | 0.00 | 0.112615E+09 | 0.00 | 0.00 | 0.721361E+11 | 0.00 | 24.74 |
December | 28480145.27 | 0.00 | 0.00 | 0.111230E+09 | 0.00 | 0.00 | 0.783136E+11 | 0.00 | 24.03 |
Annual Sum or Average | 28480145.27 | 0.285308E+10 | 0.00 | 0.152608E+10 | 0.00 | 0.00 | 0.714725E+12 | 0.00 | 25.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103109E+09 | 0.00 | 0.00 | 0.263238E+11 | 0.00 | 24.03 |
Maximum of Months | 28480145.27 | 0.112692E+10 | 0.00 | 0.152506E+09 | 0.00 | 0.00 | 0.783136E+11 | 0.00 | 26.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199099E+10 | 0.00 | 0.00 | 1.18 |
February | 0.103623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315992E+10 | 0.00 | 0.00 | 1.17 |
March | 0.129823E+11 | 0.00 | 0.00 | 507766.20 | 0.00 | 0.108704E+10 | 0.203683E+09 | 0.00 | 1.17 |
April | 0.130869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647894E+09 | 0.00 | 0.00 | 1.17 |
May | 0.126114E+11 | 815970.42 | 0.00 | 328142.19 | 0.00 | 0.00 | 0.144596E+09 | 0.00 | 1.17 |
June | 0.331326E+10 | 0.209731E+09 | 0.00 | 11315742.33 | 66208.74 | 0.00 | 0.297317E+10 | 0.00 | 1.26 |
July | 0.257841E+10 | 0.227988E+09 | 0.00 | 11456104.89 | 2903529.11 | 0.00 | 0.306716E+10 | 0.00 | 1.26 |
August | 0.355517E+10 | 0.148052E+09 | 0.00 | 11827454.68 | 18942.16 | 0.00 | 0.314740E+10 | 0.00 | 1.27 |
September | 0.663988E+10 | 28385314.91 | 0.00 | 7265168.43 | 0.00 | 0.00 | 0.215496E+10 | 0.00 | 1.22 |
October | 0.124875E+11 | 0.00 | 0.00 | 665058.81 | 0.00 | 0.120044E+10 | 0.305627E+09 | 0.00 | 1.17 |
November | 0.124959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136448E+10 | 0.00 | 0.00 | 1.17 |
December | 0.111516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428522E+10 | 0.00 | 0.00 | 1.17 |
Annual Sum or Average | 0.114086E+12 | 0.614972E+09 | 0.00 | 43365437.54 | 2988680.01 | 0.137360E+11 | 0.119966E+11 | 0.00 | 1.20 |
Minimum of Months | 0.257841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 |
Maximum of Months | 0.130869E+11 | 0.227988E+09 | 0.00 | 11827454.68 | 2903529.11 | 0.428522E+10 | 0.314740E+10 | 0.00 | 1.27 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.233202E+12 | 0.459689E+10 | 0.206211E+12 | 0.103863E+13 | 0.129224E+12 |
February | 0.318592E+12 | 0.436096E+10 | 0.193677E+12 | 0.969792E+12 | 0.111566E+12 |
March | 0.424005E+12 | 0.390673E+10 | 0.171074E+12 | 0.872399E+12 | 0.140937E+12 |
April | 0.474977E+12 | 0.360452E+10 | 0.155045E+12 | 0.787612E+12 | 0.114798E+12 |
May | 0.532418E+12 | 0.260869E+10 | 0.906596E+11 | 0.519590E+12 | 0.266413E+12 |
June | 0.575381E+12 | 0.111809E+10 | 0.302217E+11 | 0.221096E+12 | 0.619943E+12 |
July | 0.549521E+12 | 0.958646E+09 | 0.258047E+11 | 0.191086E+12 | 0.684355E+12 |
August | 0.512144E+12 | 0.119055E+10 | 0.360702E+11 | 0.237402E+12 | 0.635269E+12 |
September | 0.384516E+12 | 0.189598E+10 | 0.563403E+11 | 0.356768E+12 | 0.478073E+12 |
October | 0.317155E+12 | 0.358296E+10 | 0.150427E+12 | 0.811470E+12 | 0.184700E+12 |
November | 0.251287E+12 | 0.406630E+10 | 0.181754E+12 | 0.944935E+12 | 0.128535E+12 |
December | 0.202061E+12 | 0.493861E+10 | 0.220309E+12 | 0.109171E+13 | 0.122131E+12 |
Annual Sum or Average | 0.477526E+13 | 0.368289E+11 | 0.151759E+13 | 0.804249E+13 | 0.361594E+13 |
Minimum of Months | 0.202061E+12 | 0.958646E+09 | 0.258047E+11 | 0.191086E+12 | 0.111566E+12 |
Maximum of Months | 0.575381E+12 | 0.493861E+10 | 0.220309E+12 | 0.109171E+13 | 0.684355E+12 |