Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2023-10-16 09:02:45


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 13449.05 1185.43 1185.43
Net Site Energy 13449.05 1185.43 1185.43
Total Source Energy 24226.25 2135.36 2135.36
Net Source Energy 24226.25 2135.36 2135.36


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 4924.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 353.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 543.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 173.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 526.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 89.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 210.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 322.88 2104.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4631.53 8817.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 4924.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 353.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 543.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 173.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 952.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 22.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 526.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 89.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 210.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 2104.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
  Other 232.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 20.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 4924.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 353.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 543.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 173.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 526.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 89.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 210.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 322.88 2104.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 113.92 619.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 231.19 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 408.23 777.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 113.92 619.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 231.19 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 408.23 777.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4631.532 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4631.532 100.00
     
Total On-Site and Utility Electric Sources 4631.532 100.00
Total Electricity End Uses 4631.532 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1.45 0.02
Air to Air Heat Recovery for Heating 6323.03 99.98
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 6324.48 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 78.83
Time Setpoint Not Met During Occupied Cooling 74.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 7813.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 5.9798 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 8.7295 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 8.7295 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.1656 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.6813 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.1344 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 8.3313 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.1375 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.9719 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 3.9719 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.5594 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.9719 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.9798 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 8.7295 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 8.7295 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.1656 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.6813 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.1344 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 8.3313 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.1375 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 3.9719 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 3.9719 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 3.9719 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 3.9719 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.9719 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 3.9719 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 3.9719 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 3.9719 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 8.3313 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 8.3313 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.5594 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.9719 18.58 0.0000  
Total 11345.29             5.2589 3.54 41.0437  
Conditioned Total 11345.29             5.2589 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.3293 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 20-JUN-19:19 12-JAN-19:19 - - - - - - - - - - 03-JAN-21:00
Heating 0.00 1065187.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 96934.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41114.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 87982.85 87619.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31569.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29846.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7219.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35373.25 186966.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1333.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 341313.13 1339773.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1065187.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 96934.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 41114.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58308.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1266.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 29846.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7219.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3938.56 186966.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 429.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 662.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 5337.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1117.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1719.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 547.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5473.02 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2031.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1668.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 283.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 665.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1022.57 2281.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 137.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 14668.06 9558.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 470.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 98.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 147.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 25.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 58.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.13 201.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1292.88 842.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 470.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 98.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 147.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 25.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 58.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.13 201.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1292.88 842.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 1.99 0.758010 0.528000 1.05 1.00 0.500000 0.000503 0.000080 1.05 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.498002 0.102627 0.528000 0.262945 0.528000 0.500000 0.003712 0.000044 0.262945 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.220806 0.268035 0.528000 0.116585 0.714760 0.500000 0.001421 0.000015 0.116585 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.170024 0.736093 0.528000 0.089773 1.00 0.500000 0.000518 0.000021 0.089773 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.091568 0.788559 0.528000 0.048348 1.00 0.500000 0.000483 0.000015 0.062193 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.31 0.071273 0.528000 1.75 0.528000 0.500000 0.021213 0.000102 1.75 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.94 0.074103 0.528000 1.03 0.528000 0.500000 0.005142 0.000129 1.03 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.19 0.191976 0.528000 2.74 0.528000 0.500000 0.001985 0.000304 2.74 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.38 0.860815 0.528000 0.728015 1.00 0.500000 0.000443 0.000143 0.728015 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.08 0.121288 0.528000 1.10 0.528000 0.500000 0.003141 0.000129 1.10 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.19 0.115570 0.528000 1.15 0.528000 0.500000 0.003297 0.000133 1.15 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.26 0.062616 0.528000 1.19 0.528000 0.500000 0.010944 0.000092 1.19 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.751230 0.418033 0.528000 0.396650 1.00 0.500000 0.000911 0.000104 0.422275 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 9144.34 0.000080 197.63
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4991.84 0.000044 121.00
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1717.82 0.000015 39.63
MECH_FLR_1 VAV BOX REHEAT COIL 2384.02 0.000021 63.64
STORAGE_FLR_1 VAV BOX REHEAT COIL 1751.55 0.000015 47.80
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11625.55 0.000102 246.00
CAFE_FLR_1 VAV BOX REHEAT COIL 14701.85 0.000129 337.66
LOBBY_FLR_1 VAV BOX REHEAT COIL 34796.24 0.000304 784.70
ROOM_1_FLR_3 FAN COIL HEATING COIL 8228.87 0.000072 235.11
ROOM_2_FLR_3 FAN COIL HEATING COIL 8220.80 0.000072 234.88
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 46821.06 0.000410 1337.74
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 46702.53 0.000409 1334.35
ROOM_5_FLR_3 FAN COIL HEATING COIL 8213.91 0.000072 234.68
ROOM_6_FLR_3 FAN COIL HEATING COIL 8205.83 0.000072 234.45
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16348.48 0.000143 413.62
ROOM_1_FLR_6 FAN COIL HEATING COIL 2656.84 0.000023 75.91
ROOM_2_FLR_6 FAN COIL HEATING COIL 2654.05 0.000023 75.83
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 12794.04 0.000112 365.54
BANQUET_FLR_6 VAV BOX REHEAT COIL 14785.70 0.000129 336.20
DINING_FLR_6 VAV BOX REHEAT COIL 15247.25 0.000133 345.80
KITCHEN_FLR_6 VAV BOX REHEAT COIL 10553.29 0.000092 228.40
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 11893.18 0.000104 324.59
VAV WITH REHEAT HEATING COIL 459648.76 0.004021 6038.21
FLR_3_DOAS HEATING COIL 42957.20 0.000376 564.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.17 0.000072 0.000456
ROOM_2_FLR_3 FAN COIL 1.05 0.000072 0.000410
ROOM_3_MULT19_FLR_3 FAN COIL 8.68 0.000410 0.003336
ROOM_4_MULT19_FLR_3 FAN COIL 5.41 0.000409 0.002229
ROOM_5_FLR_3 FAN COIL 1.10 0.000072 0.000431
ROOM_6_FLR_3 FAN COIL 0.999387 0.000072 0.000391
ROOM_1_FLR_6 FAN COIL 0.305479 0.000023 0.000119
ROOM_2_FLR_6 FAN COIL 0.271079 0.000023 0.000106
ROOM_3_MULT9_FLR_6 FAN COIL 1.83 0.000112 0.000721
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.17
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.05
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.68
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.41
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.10
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.999387
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.305479
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.271079
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.83
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008557 12.80 0.008500 0.000456 1.17  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008563 12.80 0.008500 0.000410 1.05  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008495 12.80 0.008495 0.003336 8.68  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008754 12.80 0.008500 0.002229 5.41  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008560 12.80 0.008500 0.000431 1.10  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008567 12.80 0.008500 0.000391 0.999387  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008555 12.80 0.008500 0.000119 0.305479  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008561 12.80 0.008500 0.000106 0.271079  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008587 12.80 0.008500 0.000721 1.83  
VAV WITH REHEAT COOLING COIL 25.80 6.70 0.008246 10.95 0.008246 0.014083 21.95 394291.27
FLR_3_DOAS COOLING COIL 27.40 6.70 0.007007 11.91 0.007007 0.001369 2.05 38332.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 22.08 11.66 21.95 21.95 0.300000 0.531061 21.95
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.95  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.95
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.014083 0.000034
VAV WITH REHEAT_HEATC_CONTROLLER 0.004021  
FLR_3_DOAS_COOLC_CONTROLLER 0.001369 0.000348
FLR_3_DOAS_HEATC_CONTROLLER 0.000376  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:WaterHeating:AirToWaterHeatPump:Pumped

Design Size Rated Evaporator Air Flow Rate [m3/s] Design Size Rated Condenser Water Flow Rate [m3/s]
SWHSYSLAUNDRY HPWH DXCOIL 4.90 0.004370
SWHSYS1 HPWH DXCOIL 3.87 0.003451
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
SWHSYSLAUNDRY HPWH FAN 4.90 700.51
SWHSYS1 HPWH FAN 3.87 553.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:PumpedCondenser

Condenser water flow rate [m3/s] Evaporator air flow rate [m3/s]
SWHSYS1 HPWH 0.003451 3.87
SWHSYSLAUNDRY HPWH 0.004370 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.023651 4825.41  
HEATSYS1 PUMP 0.006973 2079.14 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.006973 0.836748
COOLSYS1 0.023651 2.84
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 797044.99 797044.99 0.006973
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.023651 3340.80
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.023651 662174.77 662787.61 75.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Use Side Design Flow Rate [m3/s]
SWHSYS1 HPWH TANK 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -3.10 -17.70 -19.30 -17.60 -15.40 -10.30 0.70 10.60 16.00 16.90 14.20 6.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 133.00 99737 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA -1.53 36.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 5.980 5.380 0.000 0.000 0.000 0.000 11.360 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.166 5.380 0.000 0.000 0.000 0.000 9.546 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.681 2.690 0.000 0.000 0.000 0.000 6.371 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.134 61.680 535.850 0.000 0.000 0.000 602.664 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 8.331 5.380 0.000 0.000 0.000 0.000 13.711 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.138 8.070 0.000 0.000 0.000 0.000 16.208 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.559 512.243 2419.260 0.000 0.000 0.000 2942.062 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 11832.934 5.980 111.108 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11832.934
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 585.501 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 585.501
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 678.012 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 678.012
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 684.177 4.166 257.985 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 684.177
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 348.833 3.681 170.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 348.833
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 400.685 5.134 47.701 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 400.685
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1573.457 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1573.457
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10645.380 8.138 25.200 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10645.380
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 97.406 3.972 64.937 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.406
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1546.669 3.972 73.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1546.669
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1090.832 10.559 49.053 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1090.832
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1636.910 3.972 73.801 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1636.910


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1625 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.4612 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 0.7186 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 0.7793 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 0.7186 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 0.7793 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1593 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1593 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.001
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.224
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.116
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.224
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.116
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 6.019
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 6.019
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.628
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 3.628
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.628
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.628
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
21 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
22 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
23 0 21.355302 0.61958938E-01 5.3791822  
24 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
25 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
26 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
27 0 21.355302 0.61958938E-01 5.3791822  
28 9 0.25591529E-14 -0.24546362E-15 -0.17137767E-09 -0.37498604E-16
29 8 0.24911362E-07 0.63119435E-13 0.40899073E-03 -0.28325075E-09
30 7 -0.13170143E-01 0.31867977E-08 -0.24422099E-01 0.14974934E-03
31 6 0.43057861 0.10968744E-05 0.49352007 -0.50451440E-02
32 5 -5.4367214 0.40580651E-04 -4.6055917 0.66236131E-01
33 4 34.091430 0.32920396E-03 22.082094 -0.43657653
34 3 -113.54160 0.71214000E-03 -56.892505 1.5486472
35 2 199.42519 0.39791500E-03 79.039217 -2.9371477
36 1 -172.01159 0.42217157E-04 -55.595148 2.7604334
37 0 57.057407 0.23866585E-06 15.503950  
38 9 -0.21110570E-14 0.25818275E-16 -0.15956385E-09 0.44477997E-16
39 8 0.23256408E-07 0.97708352E-13 0.39215884E-03 -0.26443334E-09
40 7 -0.12669733E-01 0.50004454E-08 -0.23702159E-01 0.14405949E-03
41 6 0.41698408 0.17322868E-05 0.48198684 -0.48848961E-02
42 5 -5.3040865 0.64447408E-04 -4.5172119 0.64591488E-01
43 4 33.504945 0.52547767E-03 21.737094 -0.42878933
44 3 -112.29434 0.11419067E-02 -56.210653 1.5306265
45 2 198.18968 0.64065682E-03 78.413072 -2.9175266
46 1 -171.55547 0.68228399E-04 -55.411591 2.7524393
47 0 57.057407 0.38731579E-06 15.533056  
48 9 -0.39522740E-14 0.27297438E-16 -0.15675654E-09 0.81247232E-16
49 8 0.22861200E-07 0.10569610E-12 0.38808057E-03 -0.25993968E-09
50 7 -0.12548287E-01 0.54308815E-08 -0.23527375E-01 0.14267860E-03
51 6 0.41368451 0.18844470E-05 0.47918278 -0.48460020E-02
52 5 -5.2718908 0.70206097E-04 -4.4957024 0.64192273E-01
53 4 33.362562 0.57315507E-03 21.653080 -0.42689883
54 3 -111.99148 0.12469212E-02 -56.044585 1.5262507
55 2 197.88960 0.70028077E-03 78.260657 -2.9127612
56 1 -171.44467 0.74647904E-04 -55.367071 2.7504973
57 0 57.057407 0.42420572E-06 15.540246  
58 9 -0.21110570E-14 0.25818275E-16 -0.15956385E-09 0.44477997E-16
59 8 0.23256408E-07 0.97708352E-13 0.39215884E-03 -0.26443334E-09
60 7 -0.12669733E-01 0.50004454E-08 -0.23702159E-01 0.14405949E-03
61 6 0.41698408 0.17322868E-05 0.48198684 -0.48848961E-02
62 5 -5.3040865 0.64447408E-04 -4.5172119 0.64591488E-01
63 4 33.504945 0.52547767E-03 21.737094 -0.42878933
64 3 -112.29434 0.11419067E-02 -56.210653 1.5306265
65 2 198.18968 0.64065682E-03 78.413072 -2.9175266
66 1 -171.55547 0.68228399E-04 -55.411591 2.7524393
67 0 57.057407 0.38731579E-06 15.533056  
68 9 -0.39522740E-14 0.27297438E-16 -0.15675654E-09 0.81247232E-16
69 8 0.22861200E-07 0.10569610E-12 0.38808057E-03 -0.25993968E-09
70 7 -0.12548287E-01 0.54308815E-08 -0.23527375E-01 0.14267860E-03
71 6 0.41368451 0.18844470E-05 0.47918278 -0.48460020E-02
72 5 -5.2718908 0.70206097E-04 -4.4957024 0.64192273E-01
73 4 33.362562 0.57315507E-03 21.653080 -0.42689883
74 3 -111.99148 0.12469212E-02 -56.044585 1.5262507
75 2 197.88960 0.70028077E-03 78.260657 -2.9127612
76 1 -171.44467 0.74647904E-04 -55.367071 2.7504973
77 0 57.057407 0.42420572E-06 15.540246  
78 7 -0.19147387E-14 -0.13717675E-16 -0.22389416E-13 0.54853152E-15
79 6 0.20210758E-10 0.18951096E-11 0.52387441E-09 -0.18662741E-10
80 5 -0.57595736E-07 0.92592455E-08 -0.21946623E-05 0.17180500E-06
81 4 0.51775713E-04 0.34884876E-05 0.17695789E-02 -0.28269358E-03
82 3 -0.72897754E-02 0.12323952E-03 -0.21573936 0.43368638E-01
83 2 0.10317303 0.53116266E-03 2.9018940 -0.61935487
84 1 -0.26095493 0.34096303E-03 -7.1391298 1.5699863
85 0 0.16602045 0.17146927E-05 4.4522066  
86 7 -0.22389416E-13 -0.13717675E-16 -0.19147387E-14 0.54853152E-15
87 6 0.52387441E-09 0.18951096E-11 0.20210758E-10 -0.18662741E-10
88 5 -0.21946623E-05 0.92592455E-08 -0.57595736E-07 0.17180500E-06
89 4 0.17695789E-02 0.34884876E-05 0.51775713E-04 -0.28269358E-03
90 3 -0.21573936 0.12323952E-03 -0.72897754E-02 0.43368638E-01
91 2 2.9018940 0.53116266E-03 0.10317303 -0.61935487
92 1 -7.1391298 0.34096303E-03 -0.26095493 1.5699863
93 0 4.4522066 0.17146927E-05 0.16602045  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
103 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
104 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
105 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
106 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
107 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
108 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
109 0 0.27512533 0.13606908E-04 60.838472  
110 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
111 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
112 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
113 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
114 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
115 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
116 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
117 0 0.27512533 0.13606908E-04 60.838472  
118 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
119 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
120 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
121 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
122 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
123 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
124 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
125 0 0.27512533 0.13606908E-04 60.838472  
126 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
127 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
128 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
129 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
130 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
131 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
132 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
133 0 0.27512533 0.13606908E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.2648_SHGC_0.4 37 1 VerySmooth 1.504 1.504 1.000 0.401    
2 RESWINDOW_U_0.2648_SHGC_0.4 38 1 VerySmooth 1.504 1.504 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.45658E-002 0.31435 0.49128 0.49128 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.09678E-002 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   4.45658E-002 0.31435 0.49128 0.49128 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.09678E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473


Heat Pump Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH 1.1400 77279.0 48.891 1.7251 76621  
2 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH 2.8400 62811.3 4.643 9.4092 53264  


Water Heater Stratified Node Information

Node Number Height {m} Volume {m3} Maximum Capacity {W} Off-Cycle UA {W/K} On-Cycle UA {W/K} Number Of Inlets Number Of Outlets
1 1 0.2683 0.4733 0.000 2.4569 2.4569 0 1
2 2 0.2683 0.4733 93813.000 1.5573 1.5573 0 0
3 3 0.2683 0.4733 0.000 1.5573 1.5573 0 0
4 4 0.2683 0.4733 0.000 1.5573 1.5573 0 0
5 5 0.2683 0.4733 0.000 1.5573 1.5573 0 1
6 6 0.2683 0.4733 0.000 2.4569 2.4569 2 0


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 9.802E-003 1.461E-004 7.212E-005 0.133 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 3.784E-003 4.872E-005 1.327E-004 4.426E-002 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 8.942E-003 5.445E-005 1.424E-004 4.947E-002 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 5.159E-003 5.445E-005 1.182E-004 4.947E-002 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 1.221E-002 1.565E-004 1.392E-004 0.142 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 2.167E-002 1.147E-004 6.318E-005 0.104 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 6.191E-002 4.733E-005 9.051E-005 4.300E-002 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 5.689E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 5.688E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.587E-003 6.472E-005 1.424E-004 7.644E-002 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.588E-003 6.472E-005 1.424E-004 7.644E-002 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 5.689E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 5.688E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 6.879E-003 1.766E-005 1.424E-004 2.086E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 5.689E-003 1.458E-004 7.203E-005 0.172 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 5.688E-003 1.458E-004 7.203E-005 0.172 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.910E-003 1.186E-004 6.472E-005 0.140 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 1.389E-002 4.188E-005 3.236E-005 4.947E-002 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 1.389E-002 4.188E-005 3.236E-005 4.947E-002 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 1.243E-002 1.204E-004 6.523E-005 0.142 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 1.217E-002 2.953E-005 2.446E-005 3.488E-002 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1484
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 9.0897E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1754
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1106
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.1388E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.3320E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.2003E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3948E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1656
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1086
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1956
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1315
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.0045E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.1905E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.7151E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.9061E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.8864E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.7906E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.8983E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.2006E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.3418E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3128E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1343E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4653E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.8864E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.7906E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.8983E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.2006E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.3418E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3128E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1343E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4653E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 26952.53364 26952.53364 1.98925 1.98925 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 23.23500 7.00086E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 3684.91068 3684.91068 0.16044 0.85446 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6746.99877 6746.99877 0.49800 0.49800 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 3625.65408 3625.65408 0.15786 0.15786 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2991.40165 2991.40165 0.22081 0.22081 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 26.99200 7.00652E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 1112.06840 1112.06840 4.84190E-002 9.17347E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2303.92771 2303.92771 0.17002 0.17002 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 27.19600 7.00683E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1917.64506 1917.64506 8.34934E-002 8.34934E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1240.78928 1240.78928 9.15678E-002 9.15678E-002 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 27.29800 7.00699E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1428.41587 1428.41587 6.21926E-002 6.21926E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44859.99852 44859.99852 3.31085 3.31085 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 27.40000 7.00714E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2544.80233 2544.80233 0.11080 0.11080 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 26290.46501 26290.46501 1.94207 1.94207 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 9373.75289 9373.75289 0.40812 0.67639 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 70327.33695 70327.33695 5.19250 5.19250 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 20550.74038 20550.74038 0.89477 1.89399 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11749.46858 11749.46858 1.16850 1.16850 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 8228.87148 8228.87148 0.36038 0.36038 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10541.79873 10541.79873 1.04840 1.04840 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95200 7.00344E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 8220.79651 8220.79651 0.36003 0.36003 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 87286.87554 87286.87554 8.68045 8.68045 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 46821.06207 46821.06207 2.05054 2.05054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 54443.26328 54443.26328 5.41467 5.41467 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 20.92300 6.99743E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 46702.52641 46702.52641 2.04535 2.04535 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 11091.40700 11091.40700 1.10306 1.10306 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 24.54400 7.00282E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 8213.90820 8213.90820 0.35972 0.35972 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10048.97886 10048.97886 0.99939 0.99939 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 22.36800 6.99957E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 8205.83432 8205.83432 0.35937 0.35937 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 18682.24000 18682.24000 1.37882 1.37882 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 12565.30312 12565.30312 0.54709 0.54709 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3071.63590 3071.63590 0.30548 0.30548 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46200 7.00420E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2656.84397 2656.84397 0.11636 0.11636 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2725.73646 2725.73646 0.27108 0.27108 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.69700 7.00305E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2654.04864 2654.04864 0.11623 0.11623 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 18418.69522 18418.69522 1.83181 1.83181 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 12794.03728 12794.03728 0.56031 0.56031 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28197.29377 28197.29377 2.08366 2.08366 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 9068.35542 9068.35542 0.39483 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29592.78696 29592.78696 2.18675 2.18675 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40000 7.00714E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 9247.02823 9247.02823 0.40261 1.18780 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30558.18283 30558.18283 2.26115 2.26115 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 26.48200 7.00575E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 4355.05815 4355.05815 0.18960 0.36735 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -41.90000 6.45023E-005 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10178.88996 10178.88996 0.75123 0.75123 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40000 7.00714E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 9698.61125 9698.61125 0.42228 0.42228 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90000 6.45023E-005 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 339931.11 21.94942 21.94942 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 533529.62 7.64323 7.64323 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 35674.24 18.87691 2.05125 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 143185.63 6.32829 2.05125 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.98925
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.75801
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.05032
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.02632E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.99987E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.05032
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9144.34345
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.99987E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 197.63057
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.49800
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10263
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26295
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.71248E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.36708E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26295
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4991.84305
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.36708E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 120.99668
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22081
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26804
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11659
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71476
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.42146E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50282E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11659
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1717.82109
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50282E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 39.63031
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17002
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.73609
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.97725E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.17598E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.08565E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.97725E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2384.02109
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.08565E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 63.64146
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.15678E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78856
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.83478E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.83160E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.53233E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.21926E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1751.54603
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.53233E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 47.80311
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.31085
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.12729E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.74813
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12126E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01705E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.74813
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11625.54926
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01705E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 245.99818
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.94207
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.41028E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.02541
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.14150E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.28618E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.02541
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14701.84752
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.28618E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 337.65962
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.19250
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19198
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.74164
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.98462E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.04413E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.74164
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34796.24390
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.04413E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 784.69533
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.16850
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.16850
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.19898E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.56190E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69218
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55703E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.56190E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.16850
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8228.87148
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.19898E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 235.11019
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04840
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04840
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.19191E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.10007E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69216
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56330E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.10007E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04840
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8220.79651
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.19191E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 234.87950
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.68045
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.68045
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.09611E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.33575E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69259
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49502E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49502E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.33575E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.68045
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 46821.06207
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.09611E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1337.73918
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.41467
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.41467
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.08574E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.22873E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69166
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75430E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.22873E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.41467
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 46702.52641
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.08574E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1334.35277
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.10306
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.10306
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.18589E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.31033E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69217
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56034E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.31033E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.10306
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8213.90820
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.18589E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 234.68271
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99939
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99939
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.17882E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.91184E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69216
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56650E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.91184E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99939
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8205.83432
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.17882E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 234.45205
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.37882
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.86082
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.72801
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.42604E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.43024E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72801
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16348.47664
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.43024E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 413.62044
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30548
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30548
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.32432E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.19179E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69218
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55455E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.19179E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30548
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2656.84397
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.32432E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 75.90817
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27108
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.27108
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.32188E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.05959E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69217
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56145E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.05959E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27108
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2654.04864
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.32188E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 75.82831
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.83181
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.83181
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.11928E-004
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.21005E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69194
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58683E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.21005E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.83181
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 12794.03728
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.11928E-004
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 365.53532
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.08366
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12129
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.10017
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.14129E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.29352E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10017
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14785.69773
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.29352E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 336.19744
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.18675
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11557
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.15460
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.29670E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.33390E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.15460
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15247.24537
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.33390E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 345.79543
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.26115
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.26161E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19389
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09441E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.23248E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19389
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10553.28807
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.23248E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 228.39830
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.75123
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41803
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39665
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.11411E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04047E-004
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42228
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11893.17660
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04047E-004
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 324.59368
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65648
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65648
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.07667
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65648
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.94942
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.94942
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.53106
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.94942
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.94942
338 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.80121
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94724
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.24626E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.24626E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 394291.27207
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.40832E-002
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.94942
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 459648.76358
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.02121E-003
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 6038.20739
350 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.94942
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.40832E-002
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.38127E-005
353 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.02121E-003
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
356 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.40000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91318
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00714E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 38332.29647
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.36914E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 42957.20027
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.75808E-004
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 564.31020
368 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.36914E-003
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.47802E-004
371 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.75808E-004
372 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 4.90359
373 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 4.36989E-003
374 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 4.90359
375 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Electric Power Consumption [W] 700.51236
376 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 3.87257
377 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 3.45109E-003
378 Fan:SystemModel SWHSYS1 HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 3.87257
379 Fan:SystemModel SWHSYS1 HPWH FAN Design Electric Power Consumption [W] 553.22422
380 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Condenser water flow rate [m3/s] 3.45109E-003
381 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Evaporator air flow rate [m3/s] 3.87257
382 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.36513E-002
383 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 4825.41224
384 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 6.97290E-003
385 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.83675
386 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 6.97290E-003
387 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 2079.13906
388 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
389 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 797044.99254
390 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 797044.99000
391 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 6.97290E-003
392 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.36513E-002
393 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.83816
394 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.36513E-002
395 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3340.79565
396 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.36513E-002
397 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 662174.77459
398 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 662787.61000
399 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 75.55779
400 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
401 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
402 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
403 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
404 WaterHeater:Stratified SWHSYS1 HPWH TANK Use Side Design Flow Rate [m3/s] 3.75036E-004
405 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Condenser water flow rate [m3/s] 4.36989E-003
406 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Evaporator air flow rate [m3/s] 4.90359


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 9190.11
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 5013.55
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1725.78
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2393.27
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1758.19
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11684.85
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 14770.22
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 34961.01
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 8862.39
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 8853.69
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 50425.80
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 50298.14
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 8846.28
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 8837.58
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16416.58
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2861.35
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2858.34
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 13778.86
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 14855.14
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 15319.04
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 10606.05
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 11938.31
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 244148.45
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 22817.28


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19278.34 15552.83 3725.51 0.81 2215.77 22.47
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 17316.37 13963.76 3352.60 0.81 1989.90 20.18
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 141778.63 114851.96 26926.67 0.81 16335.06 165.68
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 92449.79 73584.28 18865.51 0.80 10570.17 107.21
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 18209.48 14687.05 3522.43 0.81 2092.72 21.23
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16516.37 13315.61 3200.76 0.81 1897.79 19.25
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5037.64 4064.84 972.80 0.81 579.05 5.87
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4475.91 3609.81 866.10 0.81 514.38 5.22
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 30383.48 24460.25 5923.23 0.81 3489.13 35.39
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 516358.10 368262.06 148096.04 0.71 66438.35 673.85
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 52427.63 36468.44 15959.19 0.70 7931.52 80.45


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.270 0.259   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.270 0.259   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.270 0.259   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.461 0.431   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.719 0.649   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.719 0.649   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.719 0.649   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.719 0.649   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.719 0.649   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.159 0.155   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.779 0.698   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.779 0.698   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.779 0.698   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.779 0.698   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.779 0.698   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.163 0.158   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.779 0.698   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.2648_SHGC_0.4 N/A 1.504 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.159 0.153   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.6023602003E-002 2.0205626143E-002 Pass Pass 2.7654570399E-003 4.3658960982E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.8573474247E-003 1.5009402197E-003 Pass Pass 2.0289102067E-002 4.1616365968E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 6.8807046290E-003 1.5000648758E-002 Pass Pass 3.5870005916E-002 0.1010748325 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 4.3155936051E-004 3.4546160005E-004 Pass Pass 0.2096012244 1.1949934550 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 4.3102853624E-004 3.4164926397E-004 Pass Pass 1.6870311388E-002 3.0510913681E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 6.6773574660E-002 0.2168539989 Pass Pass 1.8896563185E-002 5.2403181249E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 2.5401625808E-003 1.8013830636E-003 Pass Pass 0.1059466795 0.4437996285 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 1.7553872651E-002 3.1757249291E-002 Pass Pass 2.2992498333E-002 7.6263897451E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2641443214E-002 0.3475489574 Pass Pass 0.1014939815 0.3459495611 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2634160308E-002 0.3466754661 Pass Pass 9.9939165784E-002 0.3219138354 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.0627085320E-005 4.9807810124E-005 Pass Pass 3.6630815217E-002 9.5616371389E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.4992611461E-002 0.1862588535 Pass Pass 8.8393174792E-002 0.2638120784 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2643178371E-002 0.3466114184 Pass Pass 0.1036678957 0.3615246255 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2623868055E-002 0.3458392591 Pass Pass 0.1052650996 0.3396538393 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.7120922529E-004 3.5758876078E-004 Pass Pass 4.5379588843E-002 0.1269718333 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2625380490E-002 0.3712304804 Pass Pass 9.2055569136E-002 0.3181733453 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2710008415E-002 0.3705965285 Pass Pass 9.1600397068E-002 0.3188453237 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2632431229E-002 0.3478640230 Pass Pass 0.2191643905 1.3822379817 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.1865975572E-002 9.9330987259E-002 Pass Pass 8.9775914332E-003 2.2626490298E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 4.2795988077E-002 7.8883957782E-002 Pass Pass 9.8270932218E-003 2.9623450624E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.7225429868E-002 0.1155857855 Pass Pass 2.2147161776E-002 3.8985035052E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 7.7985656333E-004 6.1213958410E-004 Pass Pass 1.6697451970E-002 2.5938290415E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2459.69 68.24 3076.54 13448.97 2725.10 21778.55



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.261 0.270 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.261 0.270 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.261 0.270 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.431 0.461 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.431 0.461 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.431 0.461 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.431 0.461 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.159 0.163 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.431 0.461 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.431 0.461 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.649 0.719 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.649 0.719 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.649 0.719 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.649 0.719 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.649 0.719 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.649 0.719 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.649 0.719 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.649 0.719 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.649 0.719 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.649 0.719 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.649 0.719 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.649 0.719 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.649 0.719 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.649 0.719 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.698 0.779 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.698 0.779 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.698 0.779 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.698 0.779 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.698 0.779 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.159 0.163 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.698 0.779 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.159 0.163 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.698 0.779 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.159 0.163 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.159 0.163 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.153 0.159 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.153 0.159 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.153 0.159 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.153 0.159 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.153 0.159 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.153 0.159 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.153 0.159 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.153 0.159 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.153 0.159 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.153 0.159 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.153 0.159 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.154 0.159 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.151 0.159 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.154 0.159 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.151 0.159 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.151 0.159 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.151 0.159 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.154 0.159 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.154 0.159 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.154 0.159 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.151 0.159 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 1.504 0.401 0.401             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 1.504 0.401 0.401             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 1.504 0.401 0.401             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 1.504 0.401 0.401             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 1.504 0.401 0.401             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 1.504 0.401 0.401             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 1.504 0.401 0.401             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 1.504 0.401 0.401             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 1.504 0.401 0.401             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 1.504 0.401 0.401             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 1.504 0.401 0.401             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 1.504 0.401 0.401             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 1.504 0.401 0.401             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 1.504 0.401 0.401             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 1.504 0.401 0.401             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 1.504 0.401 0.401             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 1.504 0.401 0.401             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 1.504 0.401 0.401             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 1.504 0.401 0.401             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 1.504 0.401 0.401             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 1.504 0.401 0.401             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.2648_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 1.504 0.401 0.401             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 1.504 0.401 0.401             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 1.504 0.401 0.401             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 1.504 0.401 0.401             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 1.504 0.401 0.401             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 1.504 0.401 0.401             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 1.504 0.401 0.401             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 1.504 0.401 0.401             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.2648_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 1.504 0.401 0.401             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 1.504 0.401 0.401                      
North Total or Average             432.95 1.504 0.401 0.401                      
Non-North Total or Average             780.84 1.504 0.401 0.401                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.9798 1978.83 11832.93 LightsWired LTG_SCH_BASEMENT 45.99 168.00 45.94 0.0000 Y 102.03
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 8.7295 67.07 585.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 5.64
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 8.7295 77.67 678.01 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.53
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.1656 164.24 684.18 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 7.53
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.6813 94.76 348.83 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 1.68
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.1344 78.04 400.68 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.41
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 8.3313 188.86 1573.46 LightsWired LTG_SCH_DINING 58.69 168.00 39.29 0.0000 Y 11.61
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.1375 1308.19 10645.38 LightsWired LTG_SCH_LOBBY 58.69 168.00 55.39 0.0000 Y 110.69
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 3.9719 1863.81 7402.84 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.32
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 3.9719 1864.32 7404.86 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.33
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.9719 1557.62 6186.67 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 51.06
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 3.9719 39.02 154.99 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 3.9719 39.02 154.97 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 3.9719 220.77 876.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 7.86
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.06 0.0000 Y 25.45
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.06 0.0000 Y 25.45
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.5594 103.30 1090.83 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.00
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.9719 412.12 1636.91 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 13.51
Interior Lighting Total       5.2589 11345.29 59663.90               350.24


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 11096.45 AstronomicalClock -   83.06 83.06 173.00
Exterior Lighting Total 11096.45           173.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 797044.99 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 662787.61 2.96 662904.11 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12772.34 19278.34 15552.83 3725.51 0.81 - 2215.77 22.47
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11479.32 17316.37 13963.76 3352.60 0.81 - 1989.90 20.18
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 93393.96 141778.63 114851.96 26926.67 0.81 - 16335.06 165.68
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 62399.55 92449.79 73584.28 18865.51 0.80 - 10570.17 107.21
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12067.99 18209.48 14687.05 3522.43 0.81 - 2092.72 21.23
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10952.32 16516.37 13315.61 3200.76 0.81 - 1897.79 19.25
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3336.76 5037.64 4064.84 972.80 0.81 - 579.05 5.87
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2966.64 4475.91 3609.81 866.10 0.81 - 514.38 5.22
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 20186.60 30383.48 24460.25 5923.23 0.81 - 3489.13 35.39
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 394291.27 516358.10 368262.06 148096.04 0.71 - 66438.35 673.85
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 38332.30 52427.63 36468.44 15959.19 0.70 - 7931.52 80.45
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 9144.34 9190.11 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4991.84 5013.55 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1717.82 1725.78 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2384.02 2393.27 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1751.55 1758.19 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11625.55 11684.85 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 14701.85 14770.22 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 34796.24 34961.01 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8228.87 8862.39 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8220.80 8853.69 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 46821.06 50425.80 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 46702.53 50298.14 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8213.91 8846.28 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 8205.83 8837.58 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 16348.48 16416.58 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2656.84 2861.35 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2654.05 2858.34 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 12794.04 13778.86 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 14785.70 14855.14 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 15247.25 15319.04 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10553.29 10606.05 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11893.18 11938.31 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 459648.76 244148.45 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 42957.20 22817.28 -
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   75921.46 3.40
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   54370.95 3.40
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.17 822.20 703.64 1.00 1.16 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.05 737.69 703.64 1.00 1.19 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 8.68 6107.88 703.64 1.00 0.94 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.41 3809.96 703.64 1.00 0.97 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.10 776.15 703.64 1.00 1.17 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.00 703.21 703.64 1.00 1.20 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.31 214.95 703.64 1.00 1.70 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 190.74 703.64 1.00 1.79 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.83 1288.93 703.64 1.00 1.08 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.95 49180.71 2240.64 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 0.70 100.00 4.90 700.51 142.86 0.00 2.78 General    
SWHSYS1 HPWH FAN Fan:SystemModel 0.70 100.00 3.87 553.22 142.86 0.00 2.84 General    


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.023651 4825.41 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.006973 2079.14 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.023651 3340.80 141251.80 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWHSYSLAUNDRY HPWH WaterHeater:HeatPump:PumpedCondenser 1.14 77279.00 0.80 48.89 1.73
SWHSYS1 HPWH WaterHeater:HeatPump:PumpedCondenser 2.84 62811.31 0.80 4.64 9.41



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 26952.53 26952.53 13.62 1.989 1.989 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 24.00 24.00 0.00940 23.23 0.00700 0.854 0.00
RETAIL_1_FLR_1 6747.00 6747.00 100.59 0.498 0.498 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00885 27.40 0.00701 0.079 0.00
RETAIL_2_FLR_1 2991.40 2991.40 38.51 0.221 0.221 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 24.00 24.00 0.00944 26.99 0.00701 0.092 0.00
MECH_FLR_1 2303.93 2303.93 14.03 0.170 0.170 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00874 27.20 0.00701 0.000 0.00
STORAGE_FLR_1 1240.79 1240.79 13.09 0.092 0.092 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00885 27.30 0.00701 0.058 0.00
LAUNDRY_FLR_1 44860.00 44860.00 574.84 3.311 3.311 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00854 27.40 0.00701 0.000 0.00
CAFE_FLR_1 26290.47 26290.47 139.20 1.942 1.942 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 23.99 0.00972 27.40 0.00701 0.676 0.00
LOBBY_FLR_1 70327.34 70327.34 53.76 5.193 5.193 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00985 27.40 0.00701 1.894 0.00
ROOM_1_FLR_3 11749.47 11749.47 301.10 1.169 1.169 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00856 25.46 0.00700 0.062 0.00
ROOM_2_FLR_3 10541.80 10541.80 270.18 1.048 1.048 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00856 24.95 0.00700 0.062 0.00
ROOM_3_MULT19_FLR_3 87286.88 87286.88 3559.27 8.680 8.680 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00850 27.40 0.00701 0.837 0.00
ROOM_4_MULT19_FLR_3 54443.26 54443.26 2219.41 5.415 5.415 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 21.11 21.11 0.00875 20.92 0.00700 0.837 0.00
ROOM_5_FLR_3 11091.41 11091.41 284.23 1.103 1.103 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00856 24.54 0.00700 0.062 0.00
ROOM_6_FLR_3 10048.98 10048.98 257.55 0.999 0.999 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 21.11 21.11 0.00857 22.37 0.00700 0.062 0.00
CORRIDOR_FLR_3 18682.24 18682.24 47.98 1.379 1.379 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00952 27.40 0.00701 0.475 0.00
ROOM_1_FLR_6 3071.64 3071.64 78.72 0.305 0.305 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 21.11 21.11 0.00855 25.46 0.00700 0.015 0.00
ROOM_2_FLR_6 2725.74 2725.74 69.86 0.271 0.271 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 21.11 21.11 0.00856 24.70 0.00700 0.015 0.00
ROOM_3_MULT9_FLR_6 18418.70 18418.70 750.85 1.832 1.832 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00859 27.40 0.00701 0.099 0.00
BANQUET_FLR_6 28197.29 28197.29 85.02 2.084 2.084 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.98 0.01050 27.40 0.00701 1.188 0.00
DINING_FLR_6 29592.79 29592.79 89.23 2.187 2.187 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.98 0.01040 27.40 0.00701 1.188 0.00
KITCHEN_FLR_6 30558.18 30558.18 295.81 2.261 2.261 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01008 26.48 0.00701 0.367 0.00
CORRIDOR_FLR_6 10178.89 10178.89 24.70 0.751 0.751 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00899 27.40 0.00701 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 3684.91 3684.91 1.86 0.160 0.854 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00800 -41.90 0.00006 0.854 0.00
RETAIL_1_FLR_1 3625.65 3625.65 54.06 0.158 0.158 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00785 -41.90 0.00006 0.079 0.00
RETAIL_2_FLR_1 1112.07 1112.07 14.32 0.048 0.092 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00781 -41.90 0.00006 0.092 0.00
MECH_FLR_1 1917.65 1917.65 11.68 0.083 0.083 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00774 -41.90 0.00006 0.000 0.00
STORAGE_FLR_1 1428.42 1428.42 15.07 0.062 0.062 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00780 -41.90 0.00006 0.058 0.00
LAUNDRY_FLR_1 2544.80 2544.80 32.61 0.111 0.111 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00773 -41.90 0.00006 0.000 0.00
CAFE_FLR_1 9373.75 9373.75 49.63 0.408 0.676 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00787 -41.90 0.00006 0.676 0.00
LOBBY_FLR_1 20550.74 20550.74 15.71 0.895 1.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00783 -41.90 0.00006 1.894 0.00
ROOM_1_FLR_3 8228.87 8228.87 210.88 0.360 0.360 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 -41.90 0.00006 0.062 0.00
ROOM_2_FLR_3 8220.80 8220.80 210.70 0.360 0.360 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 -41.90 0.00006 0.062 0.00
ROOM_3_MULT19_FLR_3 46821.06 46821.06 1909.21 2.051 2.051 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00785 -41.90 0.00006 0.837 0.00
ROOM_4_MULT19_FLR_3 46702.53 46702.53 1903.85 2.045 2.045 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00785 -41.90 0.00006 0.837 0.00
ROOM_5_FLR_3 8213.91 8213.91 210.49 0.360 0.360 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 -41.90 0.00006 0.062 0.00
ROOM_6_FLR_3 8205.83 8205.83 210.31 0.359 0.359 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00784 -41.90 0.00006 0.062 0.00
CORRIDOR_FLR_3 12565.30 12565.30 32.27 0.547 0.547 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00788 -41.90 0.00006 0.475 0.00
ROOM_1_FLR_6 2656.84 2656.84 68.09 0.116 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00788 -41.90 0.00006 0.015 0.00
ROOM_2_FLR_6 2654.05 2654.05 68.02 0.116 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00788 -41.90 0.00006 0.015 0.00
ROOM_3_MULT9_FLR_6 12794.04 12794.04 521.56 0.560 0.560 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00788 -41.90 0.00006 0.099 0.00
BANQUET_FLR_6 9068.36 9068.36 27.34 0.395 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00791 -41.90 0.00006 1.188 0.00
DINING_FLR_6 9247.03 9247.03 27.88 0.403 1.188 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00791 -41.90 0.00006 1.188 0.00
KITCHEN_FLR_6 4355.06 4355.06 42.16 0.190 0.367 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00756 -41.90 0.00006 0.367 0.00
CORRIDOR_FLR_6 9698.61 9698.61 23.53 0.422 0.422 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00793 -41.90 0.00006 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.95 21.95 7.64 7.64 21.9494 11.6565 21.9494 0.5311 0.3000
FLR_3_DOAS 18.88 2.05 6.33 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 9144.343 9144.343 1.050322 0.00008000 197.631 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9144.34 9144.34 1.050322 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799993 50.9126 3684.91 0.00 9195.13 9195.13
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4991.843 4991.843 0.262945 0.00004367 120.997 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4991.84 4991.84 0.262945 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00784686 49.9524 3625.65 0.00 5017.85 5017.85
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1717.821 1717.821 0.116585 0.00001503 39.630 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1717.82 1717.82 0.116585 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00780823 49.7084 1112.07 0.00 1727.03 1727.03
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2384.021 2384.021 0.089773 0.00002086 63.641 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2384.02 2384.02 0.089773 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00773950 49.2763 1917.65 0.00 2395.91 2395.91
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1751.546 1751.546 0.062193 0.00001532 47.803 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1751.55 1751.55 0.062193 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00779673 49.6362 1428.42 0.00 1760.23 1760.23
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11625.549 11625.549 1.748127 0.00010171 245.998 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11625.55 11625.55 1.748127 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00773222 49.2317 2544.80 0.00 11690.55 11690.55
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 14701.848 14701.848 1.025412 0.00012862 337.660 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 14701.85 14701.85 1.025412 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00786870 50.0893 9373.75 0.00 14780.74 14780.74
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 34796.244 34796.244 2.741641 0.00030441 784.695 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 34796.24 34796.24 2.741641 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00782973 49.8436 20550.74 0.00 34984.18 34984.18
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12772.343 -999.000 1.168503 0.00045619 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 12772.34 12599.16 1.168503 21.69 15.45 0.00855703 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00855703 54.0412 11749.47 0.00 12965.74 12563.88
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 8228.871 8228.871 0.360379 0.00007199 235.110 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8228.87 8228.87 0.360379 21.11 14.60 0.00784431 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00784431 49.5972 8228.87 0.00 8870.92 8870.92
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11479.319 -999.000 1.048399 0.00041001 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 11479.32 11306.83 1.048399 21.69 15.46 0.00856330 12.80 11.96 0.00850000 24.95 0.00700344 15.26 0.0000 21.11 0.00856330 54.0803 10541.80 0.00 11652.98 11275.58
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 8220.797 8220.797 0.360025 0.00007192 234.879 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8220.80 8220.80 0.360025 21.11 14.60 0.00784417 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00784417 49.5963 8220.80 0.00 8862.22 8862.22
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 93393.963 -999.000 8.680452 0.00333575 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 93393.96 93393.96 8.680452 21.69 15.40 0.00849502 12.80 11.95 0.00849502 27.40 0.00700714 16.15 0.0000 21.11 0.00849502 53.6537 87286.88 0.00 94803.83 93158.11
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 46821.062 46821.062 2.050541 0.00040961 1337.739 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 46821.06 46821.06 2.050541 21.11 14.61 0.00785475 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00785475 49.6613 46821.06 0.00 50474.54 50474.54
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 62399.555 -999.000 5.414674 0.00222873 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 unknown 7/21 21:30:00 62399.55 58795.72 5.414674 21.69 15.62 0.00875430 12.80 11.96 0.00850000 20.92 0.00699743 13.74 0.0000 21.11 0.00875430 55.2708 54443.26 0.00 63319.47 58696.42
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 46702.526 46702.526 2.045349 0.00040857 1334.353 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 46702.53 46702.53 2.045349 21.11 14.61 0.00785435 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00785435 49.6588 46702.53 0.00 50346.75 50346.75
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12067.994 -999.000 1.103058 0.00043103 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 12067.99 11894.99 1.103058 21.69 15.45 0.00856034 12.80 11.96 0.00850000 24.54 0.00700282 15.11 0.0000 21.11 0.00856034 54.0619 11091.41 0.00 12250.64 11861.91
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8213.908 8213.908 0.359724 0.00007186 234.683 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8213.91 8213.91 0.359724 21.11 14.60 0.00784403 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00784403 49.5954 8213.91 0.00 8854.79 8854.79
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10952.324 -999.000 0.999387 0.00039118 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown 7/21 09:20:00 10952.32 10779.54 0.999387 21.69 15.46 0.00856650 12.80 11.96 0.00850000 22.37 0.00699957 14.30 0.0000 21.11 0.00856650 54.1003 10048.98 0.00 11117.94 10749.95
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8205.834 8205.834 0.359370 0.00007179 234.452 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8205.83 8205.83 0.359370 21.11 14.60 0.00784389 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00784389 49.5946 8205.83 0.00 8846.09 8846.09
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 16348.477 16348.477 0.728015 0.00014302 413.620 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 16348.48 16348.48 0.728015 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00787548 50.1308 12565.30 0.00 16432.46 16432.46
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3336.763 -999.000 0.305479 0.00011918 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown 7/21 17:30:00 3336.76 3293.46 0.305479 21.69 15.45 0.00855455 12.80 11.96 0.00850000 25.46 0.00700420 15.45 0.0000 21.11 0.00855455 54.0258 3071.64 0.00 3387.30 3284.19
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2656.844 2656.844 0.116355 0.00002324 75.908 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2656.84 2656.84 0.116355 21.11 14.63 0.00787888 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00787888 49.8129 2656.84 0.00 2864.14 2864.14
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2966.637 -999.000 0.271079 0.00010596 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 2966.64 2923.34 0.271079 21.69 15.45 0.00856145 12.80 11.96 0.00850000 24.70 0.00700305 15.17 0.0000 21.11 0.00856145 54.0687 2725.74 0.00 3011.53 2915.23
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2654.049 2654.049 0.116233 0.00002322 75.828 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2654.05 2654.05 0.116233 21.11 14.63 0.00787876 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00787876 49.8122 2654.05 0.00 2861.13 2861.13
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 20186.596 -999.000 1.831812 0.00072100 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 20186.60 19772.78 1.831812 21.69 15.48 0.00858683 12.80 11.96 0.00850000 27.40 0.00700714 16.15 0.0000 21.11 0.00858683 54.2275 18418.70 0.00 20491.00 19720.83
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12794.037 12794.037 0.560312 0.00011193 365.535 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12794.04 12794.04 0.560312 21.11 14.63 0.00788410 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.11 0.00788410 49.8452 12794.04 0.00 13792.32 13792.32
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 14785.698 14785.698 1.100173 0.00012935 336.197 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 14785.70 14785.70 1.100173 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00791247 50.3637 9068.36 0.00 14865.32 14865.32
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 15247.245 15247.245 1.154602 0.00013339 345.795 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 15247.25 15247.25 1.154602 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00791414 50.3742 9247.03 0.00 15329.43 15329.43
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10553.288 10553.288 1.193887 0.00009232 228.398 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 10553.29 10553.29 1.193887 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00756231 48.1661 4355.06 0.00 10611.88 10611.88
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 11893.177 11893.177 0.422275 0.00010405 324.594 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11893.18 11893.18 0.422275 16.70 13.04 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00792815 50.4620 9698.61 0.00 11952.16 11952.16
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 394291.272 -999.000 21.949415 0.01408317 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 394291.27 394291.26 21.949415 25.80 16.64 0.00824626 10.95 10.93 0.00824626 27.40 0.00700714 16.15 53.1288 23.99 0.00963050 50.9674 297203.00 0.00 399432.65 384628.49
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 459648.764 459648.764 6.584825 0.00402121 6038.207 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 459648.76 459648.76 6.584825 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 177.0960 21.00 0.00786144 50.0429 88222.39 0.00 294762.27 294762.27
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 38332.296 -999.000 2.051317 0.00136914 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38332.30 38332.30 2.051317 27.40 16.15 0.00700714 11.91 10.04 0.00700714 27.40 0.00700714 16.15 99.9965 21.11 0.00859868 54.3003 189811.32 0.00 38851.60 38851.60
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 42957.200 42957.200 0.615395 0.00037581 564.310 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 42957.20 42957.20 0.615395 -41.90 -41.90 0.00006450 16.70 13.04 0.00800000 -41.90 0.00006450 -41.90 333.3216 21.11 0.00785484 49.6619 144497.93 0.00 27547.47 27547.47
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 54035.880 39770.408 4.903586 -999.0 -999.000 unknown unknown unknown unknown 75921.46 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 42290.343 31125.692 3.872570 -999.0 -999.000 unknown unknown unknown unknown 54370.95 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 9144.343 9144.343 1.050322 0.00008000 197.631 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.1246 1.147281 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9144.34 9144.34 1.0000 1.24509293 1.050322 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.07999054 60.00 32.22 27.78 0.000 9144.34 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00799993 21.00 0.00799993 50.9126 3684.91 0.00 9195.13 9195.13 1.24509293 16.60 13.15 0.00800000 36934.7 23.84 15.90 0.00800000 44319.8
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4991.843 4991.843 0.262945 0.00004367 120.997 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.6139 0.626294 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4991.84 4991.84 1.0000 0.31170567 0.262945 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.04366637 60.00 32.22 27.78 0.000 4991.84 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00784686 21.00 0.00784686 49.9524 3625.65 0.00 5017.85 5017.85 0.31170567 16.60 13.15 0.00800000 36934.7 32.39 18.82 0.00800000 53032.8
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1717.821 1717.821 0.116585 0.00001503 39.630 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.2113 0.215524 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1717.82 1717.82 1.0000 0.13820501 0.116585 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.01502672 60.00 32.22 27.78 0.000 1717.82 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00780823 21.00 0.00780823 49.7084 1112.07 0.00 1727.03 1727.03 0.13820501 16.60 13.15 0.00800000 36934.7 28.85 17.65 0.00800000 49430.8
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2384.021 2384.021 0.089773 0.00002086 63.641 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.2932 0.299107 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2384.02 2384.02 1.0000 0.10641989 0.089773 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.02085433 60.00 32.22 27.78 0.000 2384.02 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00773950 21.00 0.00773950 49.2763 1917.65 0.00 2395.91 2395.91 0.10641989 16.60 13.15 0.00800000 36934.7 38.68 20.79 0.00800000 59448.5
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1751.546 1751.546 0.062193 0.00001532 47.803 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.2154 0.219755 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1751.55 1751.55 1.0000 0.07372554 0.062193 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.01532173 60.00 32.22 27.78 0.000 1751.55 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00779673 21.00 0.00779673 49.6362 1428.42 0.00 1760.23 1760.23 0.07372554 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60810.2
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11625.549 11625.549 1.748127 0.00010171 245.998 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.4298 1.458581 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11625.55 11625.55 1.0000 2.07229888 1.748127 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.10169500 60.00 32.22 27.78 0.000 11625.55 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00773222 21.00 0.00773222 49.2317 2544.80 0.00 11690.55 11690.55 2.07229888 16.60 13.15 0.00800000 36934.7 22.13 15.27 0.00800000 42576.1
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 14701.848 14701.848 1.025412 0.00012862 337.660 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.8082 1.844544 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 14701.85 14701.85 1.0000 1.21556384 1.025412 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.12860506 60.00 32.22 27.78 0.000 14701.85 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00786870 21.00 0.00786870 50.0893 9373.75 0.00 14780.74 14780.74 1.21556384 16.60 13.15 0.00800000 36934.7 28.52 17.54 0.00800000 49094.3
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 34796.244 34796.244 2.741641 0.00030441 784.695 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 4.2795 4.365656 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 34796.24 34796.24 1.0000 3.25004861 2.741641 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.30438167 60.00 32.22 27.78 0.000 34796.24 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00782973 21.00 0.00782973 49.8436 20550.74 0.00 34984.18 34984.18 3.25004861 16.60 13.15 0.00800000 36934.7 27.16 17.07 0.00800000 47698.9
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12772.343 -999.000 1.168503 0.00045619 -999.000 -999.0000 1.00000 1.00000 1020.7471 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.168503 1.38518906   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 1.9288 1.928812 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 12772.34 12599.16 1.0000 1.38518906 1.168503 21.69 15.45 0.00855703 43542.8 12.80 11.96 0.00850000 34322.2 0.45614345 6.70 13.37 6.67 0.000 12772.34 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00855703 21.11 0.00855703 54.0412 11749.47 0.00 12965.74 12563.88 1.38518906 21.69 15.61 0.00855703 43542.8 12.81 12.04 0.00844212 34182.6
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 8228.871 8228.871 0.360379 0.00007199 235.110 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.168503 1.38518906   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.0121 1.032422 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8228.87 8228.87 1.0000 0.42720734 0.360379 21.11 14.60 0.00784431 41138.5 40.00 21.00 0.00800000 60796.0 0.07198241 60.00 32.22 27.78 0.000 8228.87 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00784431 21.11 0.00784431 49.5972 8228.87 0.00 8870.92 8870.92 0.42720734 16.60 13.00 0.00784431 36540.5 36.97 20.15 0.00784431 57305.5
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11479.319 -999.000 1.048399 0.00041001 -999.000 -999.0000 1.00000 1.00000 1020.7587 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.048399 1.24281348   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 1.7336 1.733546 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 11479.32 11306.83 1.0000 1.24281348 1.048399 21.69 15.46 0.00856330 43558.8 12.80 11.96 0.00850000 34322.2 0.40996518 6.70 13.37 6.67 0.000 11479.32 24.95 0.00700344 15.26 0.00000000 0.0000 21.11 0.00856330 21.11 0.00856330 54.0803 10541.80 0.00 11652.98 11275.58 1.24281348 21.69 15.61 0.00856330 43558.8 12.80 12.04 0.00844302 34182.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 8220.797 8220.797 0.360025 0.00007192 234.879 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.048399 1.24281348   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.0111 1.031409 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8220.80 8220.80 1.0000 0.42678812 0.360025 21.11 14.60 0.00784417 41138.1 40.00 21.00 0.00800000 60796.0 0.07191178 60.00 32.22 27.78 0.000 8220.80 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00784417 21.11 0.00784417 49.5963 8220.80 0.00 8862.22 8862.22 0.42678812 16.60 13.00 0.00784417 36540.2 36.97 20.15 0.00784417 57305.1
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 93393.963 -999.000 8.680452 0.00333575 -999.000 -999.0000 1.00000 1.00000 1020.6318 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.680452 10.29014885   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 14.1041 14.103862 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 93393.96 93393.96 1.0000 10.29014885 8.680452 21.69 15.40 0.00849502 43385.7 12.80 11.95 0.00849502 34309.6 3.33541338 6.70 13.37 6.67 0.000 93393.96 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00849502 21.11 0.00849502 53.6537 87286.88 0.00 94803.83 93158.11 10.29014885 21.69 15.55 0.00849502 43385.7 12.82 12.04 0.00843167 34172.6
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 46821.062 46821.062 2.050541 0.00040961 1337.739 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.680452 10.29014885   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 5.7584 5.874331 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 46821.06 46821.06 1.0000 2.43079151 2.050541 21.11 14.61 0.00785475 41165.4 40.00 21.00 0.00800000 60796.0 0.40956929 60.00 32.22 27.78 0.000 46821.06 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00785475 21.11 0.00785475 49.6613 46821.06 0.00 50474.54 50474.54 2.43079151 16.60 13.01 0.00785475 36567.0 36.97 20.16 0.00785475 57331.6
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 62399.555 -999.000 5.414674 0.00222873 -999.000 -999.0000 1.00000 1.00000 1021.1138 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.414674 6.41876734   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 9.4234 9.423251 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 unknown unknown unknown 7/21 21:30:00 Sensible 62399.55 58795.72 1.0000 6.41876734 5.414674 21.69 15.62 0.00875430 44043.6 12.80 11.96 0.00850000 34322.2 2.22849854 6.70 13.37 6.67 0.000 62399.55 20.92 0.00699743 13.74 0.00000000 0.0000 21.11 0.00875430 21.11 0.00875430 55.2708 54443.26 0.00 63319.47 58696.42 6.41876734 21.69 15.78 0.00875430 44043.6 12.74 12.04 0.00846901 34178.9
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 46702.526 46702.526 2.045349 0.00040857 1334.353 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.414674 6.41876734   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 5.7439 5.859459 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 46702.53 46702.53 1.0000 2.42463753 2.045349 21.11 14.61 0.00785435 41164.3 40.00 21.00 0.00800000 60796.0 0.40853240 60.00 32.22 27.78 0.000 46702.53 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00785435 21.11 0.00785435 49.6588 46702.53 0.00 50346.75 50346.75 2.42463753 16.60 13.01 0.00785435 36566.0 36.97 20.16 0.00785435 57330.6
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12067.994 -999.000 1.103058 0.00043103 -999.000 -999.0000 1.00000 1.00000 1020.7532 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.103058 1.30760789   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 1.8225 1.822445 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 12067.99 11894.99 1.0000 1.30760789 1.103058 21.69 15.45 0.00856034 43551.3 12.80 11.96 0.00850000 34322.2 0.43098878 6.70 13.37 6.67 0.000 12067.99 24.54 0.00700282 15.11 0.00000000 0.0000 21.11 0.00856034 21.11 0.00856034 54.0619 11091.41 0.00 12250.64 11861.91 1.30760789 21.69 15.61 0.00856034 43551.3 12.81 12.04 0.00844260 34182.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8213.908 8213.908 0.359724 0.00007186 234.683 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.103058 1.30760789   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.0102 1.030545 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8213.91 8213.91 1.0000 0.42643051 0.359724 21.11 14.60 0.00784403 41137.8 40.00 21.00 0.00800000 60796.0 0.07185152 60.00 32.22 27.78 0.000 8213.91 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00784403 21.11 0.00784403 49.5954 8213.91 0.00 8854.79 8854.79 0.42643051 16.60 13.00 0.00784403 36539.8 36.97 20.15 0.00784403 57304.8
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10952.324 -999.000 0.999387 0.00039118 -999.000 -999.0000 1.00000 1.00000 1020.7647 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.999387 1.18471286   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 1.6540 1.653962 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown unknown unknown 7/21 09:20:00 Sensible 10952.32 10779.54 1.0000 1.18471286 0.999387 21.69 15.46 0.00856650 43566.9 12.80 11.96 0.00850000 34322.2 0.39114441 6.70 13.37 6.67 0.000 10952.32 22.37 0.00699957 14.30 0.00000000 0.0000 21.11 0.00856650 21.11 0.00856650 54.1003 10048.98 0.00 11117.94 10749.95 1.18471286 21.69 15.62 0.00856650 43566.9 12.80 12.04 0.00844347 34182.4
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8205.834 8205.834 0.359370 0.00007179 234.452 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.999387 1.18471286   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.0092 1.029532 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8205.83 8205.83 1.0000 0.42601134 0.359370 21.11 14.60 0.00784389 41137.4 40.00 21.00 0.00800000 60796.0 0.07178090 60.00 32.22 27.78 0.000 8205.83 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00784389 21.11 0.00784389 49.5946 8205.83 0.00 8846.09 8846.09 0.42601134 16.60 13.00 0.00784389 36539.5 36.97 20.15 0.00784389 57304.4
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 16348.477 16348.477 0.728015 0.00014302 413.620 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 2.0107 2.051136 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 16348.48 16348.48 1.0000 0.86301711 0.728015 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.14300902 60.00 32.22 27.78 0.000 16348.48 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00787548 21.00 0.00787548 50.1308 12565.30 0.00 16432.46 16432.46 0.86301711 16.60 13.15 0.00800000 36934.7 35.27 19.74 0.00800000 55975.4
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3336.763 -999.000 0.305479 0.00011918 -999.000 -999.0000 1.00000 1.00000 1020.7425 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.305479 0.36212661   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 0.5039 0.503900 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 unknown unknown unknown 7/21 17:30:00 Sensible 3336.76 3293.46 1.0000 0.36212661 0.305479 21.69 15.45 0.00855455 43536.6 12.80 11.96 0.00850000 34322.2 0.11916706 6.70 13.37 6.67 0.000 3336.76 25.46 0.00700420 15.45 0.00000000 0.0000 21.11 0.00855455 21.11 0.00855455 54.0258 3071.64 0.00 3387.30 3284.19 0.36212661 21.69 15.61 0.00855455 43536.6 12.81 12.04 0.00844177 34182.6
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2656.844 2656.844 0.116355 0.00002324 75.908 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.305479 0.36212661   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.3268 0.333337 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2656.84 2656.84 1.0000 0.13793201 0.116355 21.11 14.63 0.00787888 41226.3 40.00 21.00 0.00800000 60796.0 0.02324086 60.00 32.22 27.78 0.000 2656.84 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00787888 21.11 0.00787888 49.8129 2656.84 0.00 2864.14 2864.14 0.13793201 16.60 13.03 0.00787888 36628.1 36.97 20.18 0.00787888 57393.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2966.637 -999.000 0.271079 0.00010596 -999.000 -999.0000 1.00000 1.00000 1020.7553 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271079 0.32134748   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 0.4480 0.448006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 2966.64 2923.34 1.0000 0.32134748 0.271079 21.69 15.45 0.00856145 43554.1 12.80 11.96 0.00850000 34322.2 0.10594862 6.70 13.37 6.67 0.000 2966.64 24.70 0.00700305 15.17 0.00000000 0.0000 21.11 0.00856145 21.11 0.00856145 54.0687 2725.74 0.00 3011.53 2915.23 0.32134748 21.69 15.61 0.00856145 43554.1 12.80 12.04 0.00844275 34182.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2654.049 2654.049 0.116233 0.00002322 75.828 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271079 0.32134748   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 0.3264 0.332986 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2654.05 2654.05 1.0000 0.13778689 0.116233 21.11 14.63 0.00787876 41226.0 40.00 21.00 0.00800000 60796.0 0.02321641 60.00 32.22 27.78 0.000 2654.05 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00787876 21.11 0.00787876 49.8122 2654.05 0.00 2861.13 2861.13 0.13778689 16.60 13.03 0.00787876 36627.8 36.97 20.18 0.00787876 57392.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 20186.596 -999.000 1.831812 0.00072100 -999.000 -999.0000 1.00000 1.00000 1020.8025 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.831812 2.17150213   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 3.0485 3.048473 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 20186.60 19772.78 1.0000 2.17150213 1.831812 21.69 15.48 0.00858683 43618.3 12.80 11.96 0.00850000 34322.2 0.72093141 6.70 13.37 6.67 0.000 20186.60 27.40 0.00700714 16.15 0.00000000 0.0000 21.11 0.00858683 21.11 0.00858683 54.2275 18418.70 0.00 20491.00 19720.83 2.17150213 21.69 15.63 0.00858683 43618.3 12.80 12.04 0.00844635 34182.0
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12794.037 12794.037 0.560312 0.00011193 365.535 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.831812 2.17150213   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.5735 1.605184 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 12794.04 12794.04 1.0000 0.66421626 0.560312 21.11 14.63 0.00788410 41239.7 40.00 21.00 0.00800000 60796.0 0.11191640 60.00 32.22 27.78 0.000 12794.04 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.11 0.00788410 21.11 0.00788410 49.8452 12794.04 0.00 13792.32 13792.32 0.66421626 16.60 13.04 0.00788410 36641.3 36.97 20.18 0.00788410 57406.1
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 14785.698 14785.698 1.100173 0.00012935 336.197 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.8185 1.855064 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 14785.70 14785.70 1.0000 1.30418863 1.100173 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.12933854 60.00 32.22 27.78 0.000 14785.70 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00791247 21.00 0.00791247 50.3637 9068.36 0.00 14865.32 14865.32 1.30418863 16.60 13.15 0.00800000 36934.7 27.78 17.28 0.00800000 48332.9
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 15247.245 15247.245 1.154602 0.00013339 345.795 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.8752 1.912972 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 15247.25 15247.25 1.0000 1.36871113 1.154602 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.13337595 60.00 32.22 27.78 0.000 15247.25 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00791414 21.00 0.00791414 50.3742 9247.03 0.00 15329.43 15329.43 1.36871113 16.60 13.15 0.00800000 36934.7 27.58 17.22 0.00800000 48134.6
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 10553.288 10553.288 1.193887 0.00009232 228.398 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.2979 1.324052 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 10553.29 10553.29 1.0000 1.41528018 1.193887 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.09231535 60.00 32.22 27.78 0.000 10553.29 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.77 0.00756231 21.00 0.00756231 48.1661 4355.06 0.00 10611.88 10611.88 1.41528018 16.60 13.15 0.00800000 36934.7 23.95 15.94 0.00800000 44432.8
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 11893.177 11893.177 0.422275 0.00010405 324.594 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 1.4627 1.492159 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11893.18 11893.18 1.0000 0.50058183 0.422275 16.70 13.04 0.00800000 37036.7 40.00 21.00 0.00800000 60796.0 0.10403608 60.00 32.22 27.78 0.000 11893.18 -41.90 0.00006450 -41.90 0.00000000 0.0000 21.00 0.00792815 21.00 0.00792815 50.4620 9698.61 0.00 11952.16 11952.16 0.50058183 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60811.3
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 394291.272 -999.000 21.949415 0.01408317 -999.000 -999.0000 1.00000 1.00000 1020.1694 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 21.949415 26.01969948   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 59.5449 59.544895 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 394291.27 394291.26 1.0000 26.01969948 21.949415 25.80 16.64 0.00824626 46945.0 10.95 10.93 0.00824626 31791.4 14.08173403 6.70 13.37 6.67 49180.708 345110.56 27.40 0.00700714 16.15 11.66146000 53.1288 23.99 0.00965082 23.99 0.00963050 50.9674 297203.00 0.00 399432.65 384628.49 26.01969948 25.80 16.81 0.00824626 46945.0 11.31 10.98 0.00802066 31593.9
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 459648.764 459648.764 6.584825 0.00402121 6038.207 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV WITH REHEAT FAN Fan:VariableVolume 21.949415 26.01969948   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 56.5314 57.669111 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 459648.76 459648.76 1.0000 7.80590984 6.584825 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 4.02079770 60.00 32.22 27.78 0.000 459648.76 -41.90 0.00006450 -41.90 11.66146000 177.0960 20.98 0.00786520 21.00 0.00786144 50.0429 88222.39 0.00 294762.27 294762.27 7.80590984 2.80 -4.37 0.00006450 2975.2 40.38 14.79 0.00006450 40736.6
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 38332.296 -999.000 2.051317 0.00136914 -999.000 -999.0000 1.00000 1.00000 1017.8659 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 23.64893600 13.37 6.70 6.67 662174.77 5.7888 5.788849 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 38332.30 38332.30 1.0000 2.43171206 2.051317 27.40 16.15 0.00700714 45414.0 11.91 10.04 0.00700714 29650.5 1.36900115 6.70 13.37 6.67 2195.006 36137.29 27.40 0.00700714 16.15 2.05124512 99.9965 21.11 0.00859503 21.11 0.00859868 54.3003 189811.32 0.00 38851.60 38851.60 2.43171206 27.40 16.31 0.00700714 45414.0 11.70 10.08 0.00700714 29436.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 42957.200 42957.200 0.615395 0.00037581 564.310 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43162656   4197.9300 999.8980 6.97218599 54.44 82.22 27.78 813085.84 5.2832 5.389558 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 42957.20 42957.20 1.0000 0.72951362 0.615395 -41.90 -41.90 0.00006450 -41946.5 16.70 13.04 0.00800000 37036.7 0.37576999 60.00 32.22 27.78 0.000 42957.20 -41.90 0.00006450 -41.90 2.05124512 333.3216 21.11 0.00785568 21.11 0.00785484 49.6619 144497.93 0.00 27547.47 27547.47 0.72951362 2.80 -4.37 0.00006450 2975.2 40.38 14.79 0.00006450 40736.6
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 54035.880 39770.408 4.903586 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.1854 SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 4.903586 5.81290412   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 75921.46 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 75921.46 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 42290.343 31125.692 3.872570 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.1854 SWHSYS1 HPWH FAN Fan:SystemModel 3.872570 4.59069611   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 54370.95 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 54370.95 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 21.95 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 613.00 8644.50 612.33
RETAIL_1_FLR_1 4106.00 8151.00 3785.17
RETAIL_2_FLR_1 2017.67 8196.17 1893.67
MECH_FLR_1 3640.00 8660.33 3640.00
STORAGE_FLR_1 3946.67 8752.33 3946.67
LAUNDRY_FLR_1 5578.00 3712.67 2096.00
CAFE_FLR_1 3527.50 7369.17 2765.17
LOBBY_FLR_1 1852.00 7082.50 1281.33
ROOM_1_FLR_3 4078.50 8475.33 4063.17
ROOM_2_FLR_3 4774.50 8307.50 4505.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 3756.83 8714.33 3751.67
ROOM_5_FLR_3 3895.00 8282.67 3835.33
ROOM_6_FLR_3 4376.00 8183.83 4213.50
CORRIDOR_FLR_3 3770.00 8729.17 3770.00
ROOM_1_FLR_6 4491.50 8435.33 4454.83
ROOM_2_FLR_6 5135.00 8292.00 4880.17
ROOM_3_MULT9_FLR_6 3774.17 8206.17 3619.83
BANQUET_FLR_6 2591.50 4776.33 481.00
DINING_FLR_6 2951.00 3985.00 277.17
KITCHEN_FLR_6 7470.17 6108.67 5249.00
CORRIDOR_FLR_6 3899.67 8461.33 3865.00
Facility 8726.33 8760.00 7813.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.83 0.00 0.83 0.00
RETAIL_1_FLR_1 72.17 0.00 72.17 0.00
RETAIL_2_FLR_1 12.00 0.00 12.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 5.17 0.00 5.17 0.00
CAFE_FLR_1 48.50 0.00 48.50 0.00
LOBBY_FLR_1 23.67 0.00 23.67 0.00
ROOM_1_FLR_3 0.00 3.17 0.00 3.17
ROOM_2_FLR_3 0.00 11.17 0.00 11.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4.83 41.00 4.83 41.00
ROOM_5_FLR_3 0.00 12.00 0.00 12.00
ROOM_6_FLR_3 0.00 32.00 0.00 32.00
CORRIDOR_FLR_3 3.50 0.00 3.50 0.00
ROOM_1_FLR_6 0.00 3.67 0.00 3.67
ROOM_2_FLR_6 0.00 13.83 0.00 13.83
ROOM_3_MULT9_FLR_6 0.00 5.50 0.00 5.50
BANQUET_FLR_6 1.00 0.00 1.00 0.00
DINING_FLR_6 0.67 0.00 0.67 0.00
KITCHEN_FLR_6 0.50 0.00 0.50 0.00
CORRIDOR_FLR_6 1.33 0.00 1.33 0.00
Facility 78.83 74.33 78.83 74.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.803 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.637 0.036 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.394 0.012 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.505 0.013 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.471 0.013 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 23.785 0.039 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 5.045 0.028 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.957 0.012 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.357 0.047 0.000 0.031
ROOM_2_FLR_3 0.95 1.50 118.93 0.357 0.047 0.000 0.025
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.405 0.021 0.000 0.055
ROOM_5_FLR_3 0.95 1.50 118.94 0.357 0.047 0.000 0.031
ROOM_6_FLR_3 0.95 1.50 118.93 0.357 0.047 0.000 0.035
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.562 0.006 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.357 0.047 0.000 0.037
ROOM_2_FLR_6 0.95 1.50 118.93 0.357 0.047 0.000 0.027
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.405 0.038 0.000 0.058
BANQUET_FLR_6 144.96 249.90 1010.89 4.562 0.014 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 4.929 0.014 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.891 0.039 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.157 0.010 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.772 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.505 0.001 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.342 0.000 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.489 0.000 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.456 0.000 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 19.867 0.001 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 4.852 0.000 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.874 0.000 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.000 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.543 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.001 0.000 0.000
BANQUET_FLR_6 144.96 249.90 1010.89 3.857 0.000 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 4.047 0.000 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 13.469 0.001 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.119 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.78 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.55 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.05 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.11 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 33285380.23 0.00 33285380.23 0.00 33285380.23 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 8337872.91 0.00 8337872.91 82845.47 8420718.39 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3686508.16 0.00 3686508.16 31978.46 3718486.62 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 2831401.31 0.00 2831401.31 75578.08 2906979.38 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1524695.41 0.00 1524695.41 43604.39 1568299.79 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 63113306.46 0.00 63113306.46 103198.00 63216504.46 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 32475714.49 0.00 32475714.49 183134.61 32658849.11 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 87040861.61 0.00 87040861.61 523257.42 87564119.03 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1460156.71 31947.24 1492103.95 48086.42 1540190.37 1946875.62 2190.00 6169.00 401.00 0.00
ROOM_2_FLR_3 1459985.63 25694.84 1485680.47 48082.75 1533763.22 1946647.51 2190.00 6294.92 275.08 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 13416.65 1113328.62 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19803829.30 35073.08 19838902.37 13420.32 19852322.69 26405105.73 2190.00 6178.38 391.62 0.00
ROOM_5_FLR_3 1460156.71 31952.22 1492108.94 48086.42 1540195.35 1946875.62 2190.00 6169.00 401.00 0.00
ROOM_6_FLR_3 1459985.63 35482.70 1495468.34 48082.75 1543551.08 1946647.51 2190.00 6177.51 392.49 0.00
CORRIDOR_FLR_3 22958668.37 0.00 22958668.37 58146.15 23016814.53 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 37456.40 402495.58 48097.01 450592.58 486718.90 2105.05 6170.46 484.49 0.00
ROOM_2_FLR_6 364996.41 27768.11 392764.52 48093.34 440857.86 486661.88 2131.72 6315.56 312.72 0.00
ROOM_3_MULT9_FLR_6 2345190.31 37432.41 2382622.72 24608.11 2407230.84 3126920.42 2190.00 6168.50 401.50 0.00
BANQUET_FLR_6 39408491.13 0.00 39408491.13 117440.80 39525931.94 37458366.31 5335.83 173.48 3250.69 0.00
DINING_FLR_6 42562144.07 0.00 42562144.07 117440.80 42679584.88 37458366.31 4095.17 192.98 4471.84 0.00
KITCHEN_FLR_6 56178079.74 0.00 56178079.74 105136.75 56283216.49 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12515611.79 0.00 12515611.79 102901.98 12618513.77 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 3567978.09 0.21E+10 4845727.63 0.21E+10 0.43E+10 8760.00 6778.13 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.0555 0.0000 1.0555 0.0000 1.0555 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.2644 0.0000 0.2644 0.0026 0.2670 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1169 0.0000 0.1169 0.0010 0.1179 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.0898 0.0000 0.0898 0.0024 0.0922 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0483 0.0000 0.0483 0.0014 0.0497 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 2.0013 0.0000 2.0013 0.0033 2.0046 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 1.0298 0.0000 1.0298 0.0058 1.0356 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 2.7600 0.0000 2.7600 0.0166 2.7766 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0463 0.0010 0.0473 0.0015 0.0488 0.0617 2190.00 6169.00 401.00
ROOM_2_FLR_3 0.0463 0.0008 0.0471 0.0015 0.0486 0.0617 2190.00 6294.92 275.08
ROOM_4_MULT19_FLR_3 0.6280 0.0011 0.6291 0.0004 0.6295 0.8373 2190.00 6178.38 391.62
ROOM_5_FLR_3 0.0463 0.0010 0.0473 0.0015 0.0488 0.0617 2190.00 6169.00 401.00
ROOM_6_FLR_3 0.0463 0.0011 0.0474 0.0015 0.0489 0.0617 2190.00 6177.51 392.49
CORRIDOR_FLR_3 0.7280 0.0000 0.7280 0.0018 0.7299 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0012 0.0128 0.0015 0.0143 0.0154 2105.05 6170.46 484.49
ROOM_2_FLR_6 0.0116 0.0009 0.0125 0.0015 0.0140 0.0154 2131.72 6315.56 312.72
ROOM_3_MULT9_FLR_6 0.0744 0.0012 0.0756 0.0008 0.0763 0.0992 2190.00 6168.50 401.50
BANQUET_FLR_6 1.2496 0.0000 1.2496 0.0037 1.2534 1.1878 5335.83 173.48 3250.69
DINING_FLR_6 1.3496 0.0000 1.3496 0.0037 1.3534 1.1878 4095.17 192.98 4471.84
KITCHEN_FLR_6 1.7814 0.0000 1.7814 0.0033 1.7847 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3969 0.0000 0.3969 0.0033 0.4001 0.1256 0.00 0.00 8760.00
Total Facility 64.2150 0.1131 64.3281 0.1213 64.4494 73.9670 8760.00 6778.13 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.57E+09 0.00 0.57E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 41903990.31 262807.00 42166797.31 64690340.46 8755.94 3.89 0.17 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 18.0880 0.0000 18.0880 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 1.3288 0.0083 1.3371 2.0513 8755.94 3.89 0.17


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 2759.84 0.00 0.00 0.00 6000.16 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 18.8787 0.0000 0.0000 0.0000 17.7274 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6784 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1363
Defaulted Fields 1208
Fields with Defaults 4115
Autosized Fields 353
Autosizable Fields 407
Autocalculated Fields 289
Autocalculatable Fields 549



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
Electricity:Building 2278.33 29981.50 10-JUN-05:00 133648.28 02-JAN-20:10
Electricity:Zone:BASEMENT 245.14 2955.01 02-JAN-02:10 17976.64 02-JAN-20:10
Electricity:SpaceType:GENERAL 2271.24 29840.36 10-JUN-05:00 133406.95 02-JAN-20:10
InteriorLights:Electricity 543.10 4558.18 10-JUN-05:00 45424.10 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 543.10 4558.18 10-JUN-05:00 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity 543.10 4558.18 10-JUN-05:00 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 543.10 4558.18 10-JUN-05:00 45424.10 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 15.82 195.57 02-JAN-02:10 1146.69 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 18.32 226.47 02-JAN-02:10 1327.87 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.00 245.14 02-JAN-02:10 1455.21 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.28 66.24 02-JAN-02:10 379.51 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.35 1002.76 02-JAN-02:10 4933.42 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 25.95 237.83 20-MAY-05:00 2381.38 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 11.61 34.62 20-MAY-05:00 1416.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 11.61 34.62 20-MAY-05:00 1416.11 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.70 3045.05 10-JUN-05:00 19610.05 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.70 933.64 10-JUN-05:00 9580.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.70 933.64 10-JUN-05:00 9580.84 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 295.07 4482.89 01-JAN-02:10 20504.95 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 295.15 4484.12 01-JAN-02:10 20510.57 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.46 64.43 01-JAN-02:10 296.90 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.46 64.43 01-JAN-02:10 296.87 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 34.95 531.01 01-JAN-02:10 2428.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 201.31 2415.09 06-MAY-04:50 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.45 165.79 06-MAY-04:50 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.45 165.79 06-MAY-04:50 2486.81 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 201.31 2415.09 06-MAY-04:50 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 25.45 165.79 06-MAY-04:50 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 25.45 165.79 06-MAY-04:50 2486.81 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 443.12 5932.71 02-JAN-02:10 18599.73 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorEquipment:Electricity 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.38 695.18 11-JAN-23:30 2785.70 13-AUG-10:10
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 801.79 815.98 30-MAR-03:00 153899.60 29-JUL-18:20
LowTempRefrigeration:Refrigeration:Electricity 15.60 0.00 01-JAN-11:10 1310.47 22-JUL-10:50
MedTempRefrigeration:Refrigeration:Electricity 20.68 555.86 12-JAN-04:10 714.05 25-JUL-14:00
WaterSystems:Electricity 322.88 -166.94 23-MAR-01:20 37466.90 05-SEP-18:50
Electricity:HVAC 759.38 13070.90 06-OCT-14:00 43814.51 21-JUN-21:00
Fans:Electricity 526.95 10959.46 20-FEB-08:10 33044.04 12-JUL-22:00
General:Fans:Electricity 526.95 10959.46 20-FEB-08:10 33044.04 12-JUL-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorEquipment:Electricity 641.45 9451.07 17-JUN-03:00 39153.57 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 22.42 386.23 10-JUN-05:00 1279.09 02-JAN-21:10
ElectricityPurchased:Facility 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
ElectricityPurchased:Plant 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
Cogeneration:ElectricityPurchased 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
General:Cogeneration:ElectricityPurchased 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
ElectricityNet:Plant 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
Cogeneration:ElectricityNet 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
General:Cogeneration:ElectricityNet 4631.53 67301.13 26-JUN-02:30 341313.13 20-JUN-19:20
ExteriorLights:Electricity 173.00 0.00 01-JAN-11:20 11096.45 01-JAN-00:10
General:ExteriorLights:Electricity 173.00 0.00 01-JAN-11:20 11096.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 210.00 0.00 05-APR-17:10 9938.94 01-JAN-00:10
General:HeatRecovery:Electricity 210.00 0.00 05-APR-17:10 9938.94 01-JAN-00:10
Water Heater:WaterSystems:Electricity 90.75 1086.58 05-AUG-00:20 4740.06 15-DEC-07:10
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 353.00 0.00 01-JAN-00:10 115436.70 29-JUL-15:20
General:Cooling:Electricity 353.00 0.00 01-JAN-00:10 115436.70 29-JUL-15:20
Pumps:Electricity 89.62 47.91 27-MAY-14:40 7361.44 20-JUL-18:50
General:Pumps:Electricity 89.62 47.91 27-MAY-14:40 7361.44 20-JUL-18:50
WIRED_LTG_ELECTRICITY 19.12 0.00 01-JAN-00:10 1598.93 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 8817.52 29270.80 10-MAY-01:10 1339773.95 12-JAN-19:20
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 7028.68 15908.90 10-MAY-15:10 1252154.17 12-JAN-19:20
WaterSystems:NaturalGas 2104.44 15908.90 03-APR-15:10 203106.66 21-MAR-21:30
Water Heater:WaterSystems:NaturalGas 2104.44 15908.90 03-APR-15:10 203106.66 21-MAR-21:30
Heating:NaturalGas 4924.24 0.00 06-APR-18:30 1123356.46 12-JAN-09:10
Boiler:Heating:NaturalGas 4924.24 0.00 06-APR-18:30 1123356.46 12-JAN-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 1072.02 0.00 01-JAN-00:10 393284.34 29-JUL-18:10
PlantLoopCoolingDemand:HVAC 1072.02 0.00 01-JAN-00:10 393284.34 29-JUL-18:10
CoolingCoils:PlantLoopCoolingDemand 1072.02 0.00 01-JAN-00:10 393284.34 29-JUL-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-22:00
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 12-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 12-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 24497.59 156211.88 19-SEP-14:40 2100744.83 12-JAN-09:10
EnergyTransfer:Building 4839.54 69881.08 28-FEB-11:10 326645.36 11-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 669.90 8632.13 13-JAN-04:00 36151.63 22-JUL-10:40
Refrigeration:EnergyTransfer 177.59 3320.53 12-JAN-04:00 10320.38 25-JUL-06:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 88.79 1660.27 12-JAN-04:00 5160.19 25-JUL-06:30
General:Refrigeration:EnergyTransfer 88.79 1660.27 12-JAN-04:00 5160.19 25-JUL-06:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 88.79 1660.27 12-JAN-04:00 5160.19 25-JUL-06:30
EnergyTransfer:Plant 7585.83 20952.50 02-OCT-02:00 962612.51 12-JAN-09:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.46 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 67.34 1436.89 12-JAN-04:10 2541.06 25-JUL-14:00
EnergyTransfer:HVAC 12072.23 1088.87 19-SEP-14:40 927901.35 12-JAN-09:10
CoolingCoils:EnergyTransfer 1865.76 0.00 01-JAN-00:10 524277.35 29-JUL-18:20
EnergyTransfer:Zone:BASEMENT 290.90 3051.98 27-FEB-16:00 19199.68 11-JAN-22:00
Heating:EnergyTransfer 597.78 0.00 09-FEB-18:10 153272.42 15-DEC-16:20
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 597.78 0.00 09-FEB-18:10 153272.42 15-DEC-16:20
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4152.96 42241.59 13-JAN-15:00 323989.38 11-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 290.90 3051.98 27-FEB-16:00 19199.68 11-JAN-22:00
General:Cooling:EnergyTransfer 4152.96 42241.59 13-JAN-15:00 323989.38 11-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 290.90 3051.98 27-FEB-16:00 19199.68 11-JAN-22:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 41.49 0.14 30-SEP-06:50 4635.84 25-AUG-13:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 9.11 0.00 16-JAN-12:30 2555.12 13-JAN-15:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 9.11 0.00 16-JAN-12:30 2555.12 13-JAN-15:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 32.38 0.00 01-JAN-00:10 4635.84 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 32.38 0.00 01-JAN-00:10 4635.84 25-AUG-13:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 27.91 0.15 14-DEC-12:40 1688.28 21-JUN-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 273.46 13-JAN-13:00
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 273.46 13-JAN-13:00
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 27.91 0.00 13-JAN-08:50 1688.28 21-JUN-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 27.91 0.00 13-JAN-08:50 1688.28 21-JUN-21:00
EnergyTransfer:Zone:MECH_FLR_1 17.39 0.01 08-JAN-04:10 1177.66 12-JUL-21:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 1.99 0.00 01-JAN-19:10 989.34 12-JAN-16:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 1.99 0.00 01-JAN-19:10 989.34 12-JAN-16:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 15.40 0.00 01-JAN-00:10 1177.66 12-JUL-21:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 15.40 0.00 01-JAN-00:10 1177.66 12-JUL-21:00
EnergyTransfer:Zone:STORAGE_FLR_1 10.91 0.02 13-FEB-20:10 904.14 13-JAN-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 3.87 0.00 06-JAN-23:00 904.14 13-JAN-10:40
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 3.87 0.00 06-JAN-23:00 904.14 13-JAN-10:40
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 7.04 0.00 01-JAN-00:10 609.95 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 7.04 0.00 01-JAN-00:10 609.95 23-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 588.64 8663.53 14-JAN-06:00 38710.36 21-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 588.64 8663.53 14-JAN-06:00 38710.36 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 588.64 8663.53 14-JAN-06:00 38710.36 21-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 211.93 0.04 15-JAN-12:10 15848.52 25-AUG-14:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 1.60 0.00 01-JAN-00:10 4082.63 13-JAN-14:40
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 1.60 0.00 01-JAN-00:10 4082.63 13-JAN-14:40
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 210.33 0.00 01-JAN-13:10 15848.52 25-AUG-14:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 210.33 0.00 01-JAN-13:10 15848.52 25-AUG-14:10
EnergyTransfer:Zone:LOBBY_FLR_1 716.82 57.54 13-JAN-12:50 39052.68 11-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 1057.95 13-JAN-13:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 1057.95 13-JAN-13:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 716.81 0.00 13-JAN-12:50 39052.68 11-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 716.81 0.00 13-JAN-12:50 39052.68 11-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 79.64 0.00 01-JAN-08:10 11578.49 11-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 46.08 0.00 01-JAN-08:10 9589.72 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 46.08 0.00 01-JAN-08:10 9589.72 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 33.56 0.00 01-JAN-00:10 11578.49 11-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 33.56 0.00 01-JAN-00:10 11578.49 11-JUL-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 73.30 0.00 01-JAN-08:10 11521.16 06-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 51.33 0.00 01-JAN-08:10 9723.51 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 51.33 0.00 01-JAN-08:10 9723.51 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 21.97 0.00 01-JAN-00:10 11521.16 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 21.97 0.00 01-JAN-00:10 11521.16 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 363.30 0.00 07-JAN-08:30 64720.11 25-AUG-13:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 97.34 0.00 07-JAN-08:30 28877.00 12-JAN-04:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 97.34 0.00 07-JAN-08:30 28877.00 12-JAN-04:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 265.96 0.00 01-JAN-00:10 64720.11 25-AUG-13:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 265.96 0.00 01-JAN-00:10 64720.11 25-AUG-13:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 382.05 0.00 01-JAN-08:10 65656.90 22-JUN-22:00
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 151.26 0.00 01-JAN-08:10 57177.83 13-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 151.26 0.00 01-JAN-08:10 57177.83 13-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 230.79 0.00 01-JAN-00:10 65656.90 22-JUN-22:00
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 230.79 0.00 01-JAN-00:10 65656.90 22-JUN-22:00
EnergyTransfer:Zone:ROOM_5_FLR_3 83.82 0.00 01-JAN-08:10 11395.39 22-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 43.97 0.00 01-JAN-08:10 9524.84 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 43.97 0.00 01-JAN-08:10 9524.84 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 39.85 0.00 01-JAN-00:10 11395.39 22-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 39.85 0.00 01-JAN-00:10 11395.39 22-JUL-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 77.10 0.00 01-JAN-08:10 12081.27 11-JUL-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 48.79 0.00 01-JAN-08:10 9660.34 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 48.79 0.00 01-JAN-08:10 9660.34 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 28.31 0.00 01-JAN-00:10 12081.27 11-JUL-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 28.31 0.00 01-JAN-00:10 12081.27 11-JUL-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 135.67 0.32 24-NOV-06:00 9319.43 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 24.01 0.00 04-JAN-21:40 8687.22 13-JAN-15:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 24.01 0.00 04-JAN-21:40 8687.22 13-JAN-15:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 111.67 0.00 01-JAN-00:10 9319.43 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 111.67 0.00 01-JAN-00:10 9319.43 23-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 25.01 0.00 07-JAN-08:10 3097.30 12-JAN-16:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 17.08 0.00 07-JAN-08:10 3097.30 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 17.08 0.00 07-JAN-08:10 3097.30 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.93 0.00 01-JAN-00:10 3076.49 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.93 0.00 01-JAN-00:10 3076.49 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 23.95 0.00 07-JAN-08:10 3126.19 12-JAN-16:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 18.81 0.00 07-JAN-08:10 3126.19 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 18.81 0.00 07-JAN-08:10 3126.19 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.14 0.00 01-JAN-00:10 3063.05 06-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.14 0.00 01-JAN-00:10 3063.05 06-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 119.86 0.00 01-JAN-08:10 19280.10 25-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 57.80 0.00 01-JAN-08:10 14269.95 15-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 57.80 0.00 01-JAN-08:10 14269.95 15-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.06 0.00 01-JAN-00:10 19280.10 25-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 62.06 0.00 01-JAN-00:10 19280.10 25-AUG-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 389.41 4090.41 13-JAN-11:00 22776.91 11-JUL-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 389.41 4090.41 13-JAN-11:00 22776.91 11-JUL-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 389.41 4090.41 13-JAN-11:00 22776.91 11-JUL-21:10
EnergyTransfer:Zone:DINING_FLR_6 429.46 5004.52 13-JAN-10:30 24083.28 11-JUL-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 429.46 5004.52 13-JAN-10:30 24083.28 11-JUL-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 429.46 5004.52 13-JAN-10:30 24083.28 11-JUL-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 581.10 6819.43 13-JAN-04:00 31081.36 22-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 581.10 6819.43 13-JAN-04:00 31081.36 22-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 81.08 0.23 07-MAR-11:00 6246.83 13-JAN-10:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 24.73 0.00 21-JAN-20:20 6246.83 13-JAN-10:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 24.73 0.00 21-JAN-20:20 6246.83 13-JAN-10:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 56.35 0.00 01-JAN-00:10 5996.52 23-JUL-13:50
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 56.35 0.00 01-JAN-00:10 5996.52 23-JUL-13:50
PlantLoopHeatingDemand:Facility 5889.00 12611.67 29-AUG-01:50 967034.05 12-JAN-09:10
PlantLoopHeatingDemand:Plant 2007.01 12602.84 05-SEP-00:20 219910.64 03-JUL-20:20
WaterSystems:PlantLoopHeatingDemand 2007.01 12602.84 05-SEP-00:20 219910.64 03-JUL-20:20
General:WaterSystems:PlantLoopHeatingDemand 986.50 12596.13 05-SEP-00:30 68017.24 14-APR-07:00
HeatingCoils:EnergyTransfer 3881.99 0.00 06-APR-18:30 927901.35 12-JAN-09:10
PlantLoopHeatingDemand:HVAC 3881.99 0.00 06-APR-18:30 927901.35 12-JAN-09:10
HeatingCoils:PlantLoopHeatingDemand 3881.99 0.00 06-APR-18:30 927901.35 12-JAN-09:10
HeatRecoveryForHeating:EnergyTransfer 6323.03 0.00 03-JAN-07:40 588647.89 07-NOV-06:40
HeatRecoveryForCooling:EnergyTransfer 1.45 0.00 01-JAN-00:10 52682.75 29-JUL-16:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 1020.51 0.00 01-JAN-00:10 168892.25 01-JUL-21:50
WaterSystems:EnergyTransfer 986.50 12596.13 05-SEP-00:30 68017.24 14-APR-07:00
WaterUse:WaterSystems:EnergyTransfer 986.50 12596.13 05-SEP-00:30 68017.24 14-APR-07:00
Boilers:EnergyTransfer 3860.29 0.00 06-APR-18:30 921019.90 12-JAN-09:10
Chillers:EnergyTransfer 1148.62 0.00 01-JAN-00:10 397887.37 29-JUL-18:10
HeatRejection:EnergyTransfer 1501.62 0.00 01-JAN-00:10 507656.17 29-JUL-18:10
General:HeatRejection:EnergyTransfer 1501.62 0.00 01-JAN-00:10 507656.17 29-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -290.901 0.000 0.000 146.726 102.033 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -100.963
RETAIL_1_FLR_1 0.000 0.000 9.113 -32.375 0.000 0.000 15.966 5.638 10.186 23.950 0.000 0.003 0.000 0.000 -16.185 0.000 -2.342 -13.953
RETAIL_2_FLR_1 0.000 0.000 0.006 -27.907 0.000 0.000 17.498 6.529 11.795 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -0.933 -6.989
MECH_FLR_1 0.000 0.000 1.991 -15.400 0.000 0.000 3.779 7.530 12.471 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -2.181 -8.193
STORAGE_FLR_1 0.000 0.000 3.868 -7.037 0.000 0.000 2.931 1.680 3.598 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -1.251 -3.790
LAUNDRY_FLR_1 0.000 0.000 0.000 -588.646 0.000 0.000 11.378 4.410 658.131 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -3.100 -82.176
CAFE_FLR_1 0.000 0.000 1.599 -210.334 0.000 0.000 202.749 11.606 14.341 66.939 0.000 0.005 0.000 0.000 -45.832 0.000 -5.278 -35.793
LOBBY_FLR_1 0.000 0.000 0.007 -716.816 0.000 0.000 577.949 110.697 148.998 87.616 0.000 0.013 0.000 0.000 -62.575 0.000 -15.449 -130.439
ROOM_1_FLR_3 52.443 -28.774 0.000 -11.153 0.000 0.000 9.782 5.554 12.292 36.646 0.000 0.048 0.000 0.000 -37.732 0.000 -5.855 -33.250
ROOM_2_FLR_3 58.034 -17.095 0.000 -11.571 0.000 0.000 9.666 5.553 12.291 22.943 0.000 0.013 0.000 0.000 -39.893 0.000 -6.084 -33.858
ROOM_3_MULT19_FLR_3 97.358 -255.887 0.041 -10.124 0.000 0.000 0.000 66.316 228.754 275.604 0.000 0.002 0.000 0.000 -203.210 0.000 -30.052 -168.802
ROOM_4_MULT19_FLR_3 226.856 -152.224 0.000 -154.169 0.000 0.000 184.425 66.334 228.817 69.587 0.000 0.168 0.000 0.000 -221.825 0.000 -41.619 -206.349
ROOM_5_FLR_3 50.153 -34.852 0.000 -11.179 0.000 0.000 9.767 5.554 12.292 45.263 0.000 0.048 0.000 0.000 -37.177 0.000 -5.870 -33.998
ROOM_6_FLR_3 55.322 -23.338 0.000 -11.504 0.000 0.000 9.689 5.553 12.291 31.269 0.000 0.013 0.000 0.000 -38.971 0.000 -6.259 -34.065
CORRIDOR_FLR_3 0.000 0.000 24.006 -111.668 0.000 0.000 120.303 51.065 0.000 38.381 0.000 0.006 0.000 0.000 -47.316 0.000 -6.691 -68.087
ROOM_1_FLR_6 18.779 -6.844 0.000 -2.784 0.000 0.000 2.449 1.388 3.073 9.150 0.000 0.013 0.000 0.000 -9.357 0.000 -1.483 -14.384
ROOM_2_FLR_6 20.581 -4.006 0.000 -2.901 0.000 0.000 2.416 1.388 3.073 5.720 0.000 0.003 0.000 0.000 -9.901 0.000 -1.538 -14.836
ROOM_3_MULT9_FLR_6 67.143 -53.384 0.000 -18.013 0.000 0.000 21.945 7.855 27.097 62.111 0.000 0.107 0.000 0.000 -43.049 0.000 -7.446 -64.366
BANQUET_FLR_6 0.000 0.000 0.000 -389.409 0.000 0.000 323.754 25.449 175.857 7.487 0.000 0.002 0.000 0.000 -26.744 0.000 -3.608 -112.788
DINING_FLR_6 0.000 0.000 0.000 -429.466 0.000 0.000 321.494 25.449 175.857 7.345 0.000 0.002 0.000 0.000 -27.247 0.000 -3.631 -69.803
KITCHEN_FLR_6 0.000 0.000 0.000 -581.085 0.000 0.000 28.908 12.005 540.650 23.077 0.000 0.002 0.004 0.000 -16.294 0.000 -3.269 -3.994
CORRIDOR_FLR_6 0.000 0.000 24.730 -56.354 0.000 0.000 32.018 13.511 0.000 19.302 0.000 0.002 0.000 0.000 -20.843 0.000 -2.958 -9.408
Total Facility 646.669 -576.403 65.362 -3690.796 0.000 0.000 2055.590 543.097 2434.967 832.390 0.000 0.459 0.004 0.000 -904.151 0.000 -156.898 -1250.285


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 11-JAN-22:00 0.00 0.00 0.00 -19200.22 0.00 0.00 7042.49 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4384.82
RETAIL_1_FLR_1 25-AUG-13:30 0.00 0.00 0.00 -4636.38 0.00 0.00 150.60 128.08 252.59 7210.59 0.00 0.00 0.00 0.00 -0.00 0.00 -6.74 -3098.73
RETAIL_2_FLR_1 21-JUN-21:00 0.00 0.00 0.00 -1688.39 0.00 0.00 697.61 474.61 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.11 -235.85
MECH_FLR_1 12-JUL-21:00 0.00 0.00 0.00 -1177.66 0.00 0.00 147.52 547.34 795.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -13.57 -298.90
STORAGE_FLR_1 23-JUL-10:33 0.00 0.00 0.00 -611.13 0.00 0.00 44.66 45.78 101.96 0.00 0.00 0.00 420.26 0.00 -0.00 0.00 -1.54 0.00
LAUNDRY_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -38712.60 0.00 0.00 408.80 360.62 44299.38 0.00 0.00 3.51 0.00 0.00 -0.00 0.00 0.00 -6359.70
CAFE_FLR_1 25-AUG-14:10 0.00 0.00 0.00 -15851.39 0.00 0.00 2968.49 86.54 355.63 17826.36 0.00 0.00 0.00 0.00 -0.00 0.00 -7.21 -5378.42
LOBBY_FLR_1 11-AUG-21:10 0.00 0.00 0.00 -39046.78 0.00 0.00 26438.95 6372.41 7389.94 0.00 0.00 0.00 0.00 0.00 -412.59 0.00 -30.36 -711.58
ROOM_1_FLR_3 22-JUN-18:02 0.00 -12903.18 0.00 -733.25 0.00 0.00 335.49 380.45 516.26 7087.18 0.00 61.26 5255.78 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 06-JUL-17:32 0.00 -13768.96 0.00 0.00 0.00 0.00 158.86 286.37 537.27 10134.72 0.00 0.00 2669.53 0.00 -0.00 0.00 -17.80 0.00
ROOM_3_MULT19_FLR_3 25-AUG-13:30 0.00 -64721.20 0.00 0.00 0.00 0.00 0.00 1429.19 5097.90 86320.40 0.00 0.00 0.00 0.00 -0.00 0.00 -180.58 -27945.71
ROOM_4_MULT19_FLR_3 22-JUN-21:51 0.00 -66356.85 0.00 -10654.84 0.00 0.00 7681.66 3420.82 6864.43 1176.11 0.00 0.00 58042.20 0.00 -0.00 0.00 -173.53 0.00
ROOM_5_FLR_3 22-JUN-18:02 0.00 -11943.68 0.00 -719.60 0.00 0.00 335.50 380.45 516.26 1200.47 0.00 83.16 10147.44 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 11-JUL-08:32 0.00 -13364.41 0.00 -1050.03 0.00 0.00 58.84 188.06 452.99 10934.08 0.00 0.00 2824.84 0.00 -0.00 0.00 -44.38 0.00
CORRIDOR_FLR_3 23-JUL-10:33 0.00 0.00 0.00 -9333.00 0.00 0.00 1819.27 1392.00 0.00 8172.17 0.00 0.00 0.00 0.00 -0.00 0.00 -9.67 -2040.76
ROOM_1_FLR_6 10-AUG-18:02 0.00 -3380.29 0.00 -184.74 0.00 0.00 83.87 95.11 129.07 2108.31 0.00 0.00 1155.11 0.00 -0.00 0.00 -6.45 0.00
ROOM_2_FLR_6 09-MAY-19:42 0.00 -3549.44 0.00 -208.32 0.00 0.00 57.21 106.85 173.82 1063.73 0.00 0.00 2377.68 0.00 -0.00 0.00 -21.54 0.00
ROOM_3_MULT9_FLR_6 23-JUL-15:02 0.00 -19689.96 0.00 -1194.47 0.00 0.00 294.10 199.53 673.54 10686.45 0.00 20.95 9009.86 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 11-JUL-21:10 0.00 0.00 0.00 -22777.19 0.00 0.00 15643.86 994.72 6747.90 1887.65 0.00 0.00 0.00 0.00 -0.00 0.00 -9.30 -2487.65
DINING_FLR_6 11-JUL-21:10 0.00 0.00 0.00 -24083.79 0.00 0.00 15643.75 994.72 6747.90 1878.02 0.00 0.00 0.00 0.00 -0.00 0.00 -9.30 -1171.31
KITCHEN_FLR_6 22-JUL-10:40 0.00 0.00 0.00 -31122.08 0.00 0.00 464.20 272.71 23951.61 5162.09 0.00 0.00 1273.57 0.00 -0.00 0.00 -2.09 0.00
CORRIDOR_FLR_6 23-JUL-13:50 0.00 0.00 0.00 -5995.86 0.00 0.00 308.46 245.54 0.00 5077.14 0.00 3.19 361.54 0.00 -0.00 0.00 0.00 0.00
Total Facility 11-JUL-18:02 0.00 -163747.98 0.00 -189637.79 0.00 0.00 75795.05 36448.72 121562.63 50891.30 0.00 376.28 68336.25 0.00 0.00 0.00 -24.46 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 13-JAN-15:20 0.00 0.00 2555.24 0.00 0.00 0.00 269.99 128.08 252.59 0.00 0.00 0.00 0.00 0.00 -1302.10 0.00 -159.35 -1744.44
RETAIL_2_FLR_1 13-JAN-13:00 0.00 0.00 273.47 0.00 0.00 0.00 207.94 148.32 292.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -67.64 -854.58
MECH_FLR_1 12-JAN-16:00 0.00 0.00 989.34 0.00 0.00 0.00 65.86 171.04 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -186.78 -1348.74
STORAGE_FLR_1 13-JAN-11:08 0.00 0.00 906.21 0.00 0.00 0.00 33.72 38.16 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -96.00 -971.31
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 13-JAN-14:40 0.00 0.00 4082.69 0.00 0.00 0.00 2355.80 388.02 355.63 0.00 0.00 0.00 0.00 0.00 -3761.79 0.00 -360.79 -3059.56
LOBBY_FLR_1 13-JAN-13:10 0.00 0.00 1057.97 0.00 0.00 0.00 7010.61 2370.93 3694.97 0.00 0.00 0.00 0.00 0.00 -3185.29 0.00 -1097.19 -9851.99
ROOM_1_FLR_3 26-NOV-16:01 12409.34 301.53 0.00 -301.53 0.00 0.00 163.33 141.07 305.54 0.00 0.00 0.00 0.00 0.00 -2828.77 0.00 -338.32 -9852.19
ROOM_2_FLR_3 26-NOV-16:01 12142.00 298.24 0.00 -298.24 0.00 0.00 163.33 141.05 305.51 0.00 0.00 0.00 0.00 0.00 -2821.65 0.00 -337.94 -9592.29
ROOM_3_MULT19_FLR_3 12-JAN-04:10 28876.98 0.00 0.00 0.00 0.00 0.00 0.00 561.43 3921.46 0.00 0.00 0.00 0.00 0.00 -19393.30 0.00 -2378.23 -11588.34
ROOM_4_MULT19_FLR_3 26-NOV-16:01 66828.37 3783.27 0.00 -3783.27 0.00 0.00 3103.17 1684.90 5687.67 0.00 0.00 0.00 0.00 0.00 -15268.75 0.00 -1781.27 -60254.09
ROOM_5_FLR_3 26-NOV-16:01 12245.68 300.49 0.00 -300.49 0.00 0.00 163.33 141.07 305.54 0.00 0.00 0.00 0.00 0.00 -2828.16 0.00 -338.20 -9689.25
ROOM_6_FLR_3 26-NOV-16:01 11992.92 297.30 0.00 -297.30 0.00 0.00 163.32 141.05 305.51 0.00 0.00 0.00 0.00 0.00 -2821.09 0.00 -337.84 -9443.87
CORRIDOR_FLR_3 13-JAN-15:00 0.00 0.00 8687.29 0.00 0.00 0.00 1385.82 1160.00 0.00 0.00 0.00 0.00 0.00 0.00 -3803.25 0.00 -454.39 -6975.48
ROOM_1_FLR_6 13-JAN-16:02 3803.77 76.23 0.00 -76.23 0.00 0.00 73.50 29.92 68.48 0.00 0.00 0.00 0.00 0.00 -693.01 0.00 -86.73 -3195.94
ROOM_2_FLR_6 26-NOV-16:01 3695.35 75.30 0.00 -75.30 0.00 0.00 40.83 35.26 76.38 0.00 0.00 0.00 0.00 0.00 -696.29 0.00 -84.70 -3066.83
ROOM_3_MULT9_FLR_6 13-JAN-16:02 19168.65 491.28 0.00 -491.28 0.00 0.00 661.48 169.29 603.86 0.00 0.00 0.00 0.00 0.00 -3232.29 0.00 -399.47 -16971.53
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 13-JAN-10:30 0.00 0.00 6246.75 0.00 0.00 0.00 366.68 306.92 0.00 0.00 0.00 0.00 0.00 0.00 -1875.90 0.00 -228.31 -4816.14
Total Facility 13-JAN-16:02 112006.08 58546.89 16968.45 -58546.89 0.00 0.00 62654.25 12646.14 76844.13 0.00 0.00 0.00 0.00 0.00 -64203.65 0.00 -8649.70 -208265.70



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.0767 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.9494 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6565 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6565 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9892 1.9892 1.0503 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4980 0.4980 0.2629 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2208 0.2208 0.1166 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1700 0.1700 0.0898 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0916 0.0916 0.0483 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3108 3.3108 1.7481 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9421 1.9421 1.0254 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1925 5.1925 2.7416 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3788 1.3788 0.7280 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0837 2.0837 1.1002 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1867 2.1867 1.1546 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2611 2.2611 1.1939 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7512 0.7512 0.3966 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.0767 21.9494 22.0767 11.6565 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0503 1.0503 1.0503 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2629 0.2629 0.2629 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1166 0.1166 0.1166 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0898 0.0898 0.0898 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0483 0.0483 0.0483 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7481 1.7481 1.7481 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0254 1.0254 1.0254 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7416 2.7416 2.7416 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7280 0.7280 0.7280 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1002 1.1002 1.1002 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1546 1.1546 1.1546 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1939 1.1939 1.1939 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3966 0.3966 0.3966 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6565 11.6565 11.6565 11.6565 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 78.83
Number of hours cooling loads not met 74.33
Number of hours not met 153.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 4924.24 1123356.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 353.00 115436.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 543.10 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 173.00 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 952.41 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 22.42 1279.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 526.95 33044.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 89.62 7361.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 210.00 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4740.06 2104.44 203106.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 0.00 32726.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.60 1310.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 20.68 714.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1771.52 4631.53
Natural Gas 1788.84 8817.52
Additional 0.00 0.00
Total 3560.36 13449.05


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 47.87
Space Heating 0.00
Space Cooling 31.11
Fans (All) 46.45
Service Water Heating 28.46
Receptacle Equipment 152.32
Miscellaneous (All) 408.23
Subtotal 408.23


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 434.03
Service Water Heating 185.49
Miscellaneous (All) 777.20
Subtotal 777.20


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 4.04
Space Heating 36.61
Space Cooling 2.62
Fans (All) 3.92
Service Water Heating 18.05
Receptacle Equipment 26.15
Miscellaneous 8.61


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2398. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8705.17 54.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8459.00 301.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8747.00 13.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8661.33 98.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8459.00 0.00 0.00 0.00 0.00
Max 8760.00 301.00 0.00 0.00 0.00
Average 8738.75 21.25 0.00 0.00 0.00
Sum 192252.50 467.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4127.50 26.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4098.83 55.17 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 55.17 0.00 0.00 0.00
Average 288883.33 3.71 0.00 0.00 0.00
Sum 6355433.33 81.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8746.33 13.67 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8700.00 60.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8294.83 465.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8740.83 19.17 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8653.50 106.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8745.67 14.33 0.00 0.00 0.00
DINING_FLR_6 8750.33 9.67 0.00 0.00 0.00
KITCHEN_FLR_6 8759.50 0.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8294.83 0.00 0.00 0.00 0.00
Max 8760.00 465.17 0.00 0.00 0.00
Average 8728.68 31.32 0.00 0.00 0.00
Sum 192031.00 689.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2110476.50 4952.50 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4115.50 38.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4149.67 4.33 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4080.50 73.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1242787.67 2927.33 0.00 0.00 0.00
DINING_FLR_6 1243799.67 1915.33 0.00 0.00 0.00
KITCHEN_FLR_6 108263.50 5.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2110476.50 4952.50 0.00 0.00 0.00
Average 288436.27 450.77 0.00 0.00 0.00
Sum 6345598.00 9917.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:45

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238846E+11 19199.68 11-JAN-22:00 -34.4 -34.5 0.680244E+10 4390.85 25-JAN-22:10 -23.3 -23.5
February 0.183824E+11 13675.86 28-FEB-22:00 -29.6 -29.8 0.577891E+10 4132.21 01-FEB-22:10 -29.6 -29.8
March 0.197106E+11 12385.60 01-MAR-21:53 -23.9 -24.5 0.642257E+10 4011.58 30-MAR-22:10 -18.0 -19.1
April 0.202569E+11 10205.32 22-APR-10:33 11.87 5.55 0.633560E+10 4074.84 14-APR-22:10 11.87 5.55
May 0.219585E+11 10602.56 14-MAY-10:33 16.83 8.94 0.662640E+10 4124.39 26-MAY-22:10 2.12 0.59
June 0.226013E+11 11087.66 29-JUN-10:33 21.83 15.68 0.662622E+10 4246.30 15-JUN-22:10 21.83 15.68
July 0.257503E+11 12222.00 23-JUL-10:33 22.23 15.22 0.729806E+10 4565.02 28-JUL-22:10 17.02 13.67
August 0.279321E+11 12924.96 26-AUG-10:33 15.93 12.30 0.788200E+10 4837.10 31-AUG-21:00 8.20 4.88
September 0.280049E+11 14747.31 20-SEP-21:00 8.30 7.74 0.781456E+10 4837.01 19-SEP-21:19 8.30 7.74
October 0.285860E+11 14934.50 06-OCT-21:00 7.80 3.59 0.808162E+10 4837.01 06-OCT-21:19 7.60 3.54
November 0.279112E+11 15977.81 28-NOV-23:00 -28.9 -29.1 0.748058E+10 4839.25 07-NOV-22:49 -28.9 -29.1
December 0.259217E+11 16418.80 13-DEC-01:00 -30.0 -30.2 0.698619E+10 4587.29 26-DEC-22:10 -21.9 -22.1
                     
Annual Sum or Average 0.290901E+12         0.841352E+11        
Minimum of Months 0.183824E+11 10205.32   -34.4 -34.5 0.577891E+10 4011.58   -29.6 -29.8
Maximum of Months 0.285860E+11 19199.68   22.23 15.68 0.808162E+10 4839.25   21.83 15.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 26864050.59 1098.90 30-JAN-12:30 -23.9 -24.3 0.610578E+09 364.23 26-JAN-00:49 -23.9 -24.3
February 0.412857E+09 2141.94 15-FEB-13:40 -8.7 -9.6 0.559723E+09 364.36 18-FEB-04:49 -24.0 -24.3
March 0.173170E+10 2950.45 27-MAR-14:10 -5.0 -8.3 0.630833E+09 364.35 03-MAR-01:39 -5.0 -8.3
April 0.397084E+10 4378.13 22-APR-13:30 15.30 6.96 0.628242E+09 415.93 21-APR-21:30 15.30 6.96
May 0.499941E+10 4157.26 12-MAY-13:30 20.60 9.86 0.651529E+09 420.61 31-MAY-21:30 16.00 9.64
June 0.542741E+10 3671.52 29-JUN-14:10 25.68 16.21 0.648005E+09 431.61 21-JUN-21:19 25.68 16.21
July 0.560863E+10 4378.24 23-JUL-13:30 25.00 15.26 0.665445E+09 434.38 21-JUL-21:19 25.00 15.26
August 0.530643E+10 4635.84 25-AUG-13:30 21.70 14.78 0.661072E+09 437.49 11-AUG-21:30 21.70 14.78
September 0.338483E+10 3968.31 09-SEP-13:30 13.35 8.71 0.612853E+09 391.60 08-SEP-21:30 13.35 8.71
October 0.142776E+10 3048.49 03-OCT-13:30 10.85 6.24 0.622626E+09 366.01 03-OCT-21:30 7.20 2.97
November 78115846.03 1809.77 08-NOV-13:30 -13.6 -14.4 0.599289E+09 364.24 07-NOV-22:49 -13.6 -14.4
December 160570.13 45.16 24-DEC-22:00 -5.0 -5.4 0.618373E+09 364.25 19-DEC-00:00 -5.0 -5.4
                     
Annual Sum or Average 0.323750E+11         0.750857E+10        
Minimum of Months 160570.13 45.16   -23.9 -24.3 0.559723E+09 364.23   -24.0 -24.3
Maximum of Months 0.560863E+10 4635.84   25.68 16.21 0.665445E+09 437.49   25.68 16.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147558E+10 1184.30 30-JAN-19:25 -23.9 -24.3 0.728025E+09 470.24 23-JAN-23:10 -23.9 -24.3
February 0.164103E+10 1312.76 21-FEB-19:53 -23.9 -24.1 0.670115E+09 494.17 09-FEB-23:10 -23.9 -24.1
March 0.221620E+10 1362.84 01-MAR-21:53 -23.9 -24.5 0.778302E+09 520.45 22-MAR-22:10 1.42 -0.3
April 0.260695E+10 1428.72 21-APR-20:10 11.83 4.93 0.830929E+09 569.52 21-APR-21:49 7.67 2.50
May 0.292786E+10 1464.32 10-MAY-21:00 14.40 6.20 0.893625E+09 569.55 11-MAY-21:40 12.20 6.17
June 0.301612E+10 1688.28 21-JUN-21:00 23.90 13.75 0.892807E+09 569.56 02-JUN-21:40 23.90 13.75
July 0.312389E+10 1674.12 12-JUL-21:00 18.90 11.72 0.917018E+09 569.56 21-JUL-23:10 19.72 15.53
August 0.303826E+10 1663.20 11-AUG-21:00 22.80 14.12 0.914286E+09 569.55 03-AUG-22:10 22.80 14.12
September 0.261372E+10 1310.94 10-SEP-10:33 13.87 7.59 0.831561E+09 566.13 08-SEP-21:40 13.87 7.59
October 0.232184E+10 1204.47 03-OCT-20:00 6.10 2.72 0.795488E+09 539.48 03-OCT-22:10 7.30 3.10
November 0.160209E+10 1386.55 08-NOV-20:53 -23.9 -24.2 0.709359E+09 477.69 01-NOV-22:10 -23.9 -24.2
December 0.132310E+10 1340.78 27-DEC-20:13 -24.1 -24.3 0.723693E+09 459.91 26-DEC-23:10 -24.1 -24.3
                     
Annual Sum or Average 0.279067E+11         0.968521E+10        
Minimum of Months 0.132310E+10 1184.30   -24.1 -24.5 0.670115E+09 459.91   -24.1 -24.3
Maximum of Months 0.312389E+10 1688.28   23.90 14.12 0.917018E+09 569.56   23.90 15.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146744E+09 625.33 23-JAN-22:00 -15.6 -16.0 0.151695E+09 89.14 26-JAN-02:00 -24.4 -24.6
February 0.284127E+09 706.07 09-FEB-21:00 -8.9 -9.2 0.137246E+09 92.52 09-FEB-22:10 -9.6 -9.9
March 0.774074E+09 761.17 22-MAR-20:00 2.80 0.30 0.153255E+09 96.48 22-MAR-21:10 2.12 0.08
April 0.164209E+10 956.27 22-APR-10:33 11.87 5.55 0.158179E+09 107.78 21-APR-21:19 11.87 5.55
May 0.213609E+10 1058.66 14-MAY-10:33 16.83 8.94 0.180053E+09 114.49 12-MAY-21:19 16.83 8.94
June 0.228136E+10 1128.87 22-JUN-21:00 20.60 12.02 0.185931E+09 120.45 22-JUN-22:10 19.22 11.60
July 0.239167E+10 1177.66 12-JUL-21:00 18.90 11.72 0.192876E+09 120.45 14-JUL-21:49 16.28 14.14
August 0.228680E+10 1084.73 01-AUG-10:33 15.93 12.83 0.189610E+09 120.01 02-AUG-21:10 20.40 14.60
September 0.188776E+10 971.06 10-SEP-10:33 13.87 7.59 0.166434E+09 110.72 01-SEP-21:10 13.87 7.59
October 0.128943E+10 829.53 04-OCT-20:00 3.30 1.48 0.156448E+09 102.62 04-OCT-21:10 3.30 1.41
November 0.186478E+09 665.24 02-NOV-20:00 -9.4 -9.7 0.146749E+09 89.89 02-NOV-21:10 -9.3 -9.5
December 92956000.07 598.40 24-DEC-21:00 -7.2 -7.4 0.151697E+09 89.14 09-DEC-01:10 -7.2 -7.4
                     
Annual Sum or Average 0.153996E+11         0.197017E+10        
Minimum of Months 92956000.07 598.40   -15.6 -16.0 0.137246E+09 89.14   -24.4 -24.6
Maximum of Months 0.239167E+10 1177.66   20.60 12.83 0.192876E+09 120.45   20.40 14.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 565534.42 51.81 21-JAN-21:50 -2.5 -3.6 0.116660E+09 68.57 26-JAN-01:49 -23.9 -24.2
February 16801146.60 203.45 09-FEB-22:00 -9.4 -9.7 0.105502E+09 68.57 21-FEB-01:19 -23.9 -24.1
March 0.130358E+09 380.59 22-MAR-20:00 2.80 0.30 0.117278E+09 70.74 22-MAR-22:10 1.42 -0.3
April 0.744183E+09 502.52 22-APR-10:33 11.87 5.55 0.118281E+09 79.35 21-APR-21:40 11.87 5.55
May 0.110979E+10 560.24 14-MAY-10:33 16.83 8.94 0.134619E+09 84.77 12-MAY-21:40 16.83 8.94
June 0.119887E+10 589.75 22-JUN-10:33 21.33 12.72 0.140164E+09 90.43 22-JUN-21:49 19.60 11.77
July 0.125557E+10 611.14 23-JUL-10:33 22.23 15.22 0.145308E+09 90.73 12-JUL-21:40 22.23 15.22
August 0.119172E+10 574.87 01-AUG-10:33 15.93 12.83 0.142031E+09 89.11 02-AUG-22:10 19.22 14.18
September 0.948422E+09 509.88 10-SEP-10:33 13.87 7.59 0.123345E+09 81.33 01-SEP-22:10 13.87 7.59
October 0.438488E+09 410.37 04-OCT-20:00 3.30 1.48 0.117989E+09 74.53 04-OCT-22:10 3.30 1.07
November 2130327.49 81.15 01-NOV-21:00 -8.9 -9.5 0.112879E+09 68.57 08-NOV-02:30 -24.1 -24.4
December 439429.46 54.63 24-DEC-22:00 -5.0 -5.4 0.116692E+09 68.57 19-DEC-01:39 -5.0 -5.4
                     
Annual Sum or Average 0.703733E+10         0.149075E+10        
Minimum of Months 439429.46 51.81   -9.4 -9.7 0.105502E+09 68.57   -24.1 -24.4
Maximum of Months 0.125557E+10 611.14   22.23 15.22 0.145308E+09 90.73   22.23 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472666E+11 36248.61 20-JAN-21:00 -13.3 -13.4 0.555951E+09 381.59 06-JAN-22:10 -13.3 -13.4
February 0.432031E+11 36794.18 09-FEB-21:00 -8.9 -9.2 0.508762E+09 381.59 02-FEB-22:10 -8.9 -9.2
March 0.489643E+11 37385.98 22-MAR-20:00 2.80 0.30 0.580244E+09 381.59 22-MAR-21:10 2.12 0.08
April 0.489321E+11 38048.19 21-APR-20:00 12.20 5.22 0.568928E+09 381.65 28-APR-21:10 3.53 1.78
May 0.521718E+11 38460.06 31-MAY-20:00 17.20 10.12 0.591368E+09 381.70 17-MAY-21:10 17.20 10.12
June 0.512468E+11 38634.16 29-JUN-20:00 25.00 16.66 0.574269E+09 381.80 16-JUN-21:10 25.00 16.66
July 0.528367E+11 38710.36 21-JUL-20:00 25.00 16.11 0.591951E+09 381.68 12-JUL-21:10 25.00 16.11
August 0.525956E+11 38583.89 11-AUG-20:00 24.40 14.81 0.593313E+09 381.73 23-AUG-21:10 18.43 14.55
September 0.493727E+11 37970.16 01-SEP-20:00 12.20 9.06 0.570717E+09 381.71 08-SEP-21:10 7.20 5.85
October 0.493672E+11 37597.35 03-OCT-20:00 6.10 2.72 0.585842E+09 381.60 19-OCT-21:10 -1.7 -1.7
November 0.459273E+11 36363.20 01-NOV-20:00 -8.9 -9.5 0.548371E+09 383.63 07-NOV-22:49 -23.8 -24.0
December 0.467599E+11 36015.14 26-DEC-21:00 -21.1 -21.5 0.561536E+09 382.76 08-DEC-22:30 -21.1 -21.5
                     
Annual Sum or Average 0.588644E+12         0.683125E+10        
Minimum of Months 0.432031E+11 36015.14   -21.1 -21.5 0.508762E+09 381.59   -23.8 -24.0
Maximum of Months 0.528367E+11 38710.36   25.00 16.66 0.593313E+09 383.63   25.00 16.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.795756E+10 7074.48 06-JAN-23:10 -3.0 -4.1 0.808938E+10 4944.37 06-JAN-23:10 -3.0 -4.1
February 0.107175E+11 8570.05 20-FEB-13:00 -18.3 -18.9 0.741862E+10 5193.19 09-FEB-22:40 -18.3 -18.9
March 0.174062E+11 12095.74 27-MAR-15:03 -4.9 -8.2 0.862640E+10 5721.80 22-MAR-21:40 -4.9 -8.2
April 0.221410E+11 15780.72 22-APR-13:30 15.30 6.96 0.909617E+10 6336.35 21-APR-21:30 15.30 6.96
May 0.245165E+11 14777.08 13-MAY-13:10 18.98 8.91 0.965625E+10 6382.57 31-MAY-21:40 15.77 9.56
June 0.247237E+11 13734.39 20-JUN-15:03 25.10 14.57 0.964100E+10 6387.11 20-JUN-21:40 21.67 13.58
July 0.256239E+11 15027.60 23-JUL-13:30 25.00 15.26 0.987819E+10 6462.66 21-JUL-22:10 25.00 15.26
August 0.250948E+11 15848.52 25-AUG-14:10 22.88 15.43 0.983767E+10 6462.76 10-AUG-22:10 22.88 15.43
September 0.205576E+11 14752.39 09-SEP-13:30 13.35 8.71 0.889734E+10 6150.83 08-SEP-21:40 13.35 8.71
October 0.163453E+11 11240.88 03-OCT-13:30 10.85 6.24 0.855532E+10 5924.14 03-OCT-21:40 7.20 3.00
November 0.859755E+10 7374.66 08-NOV-13:30 -13.6 -14.4 0.788707E+10 5046.79 01-NOV-21:40 -13.6 -14.4
December 0.665055E+10 6825.55 19-DEC-23:10 -8.7 -9.2 0.813612E+10 4847.83 19-DEC-23:10 -8.7 -9.2
                     
Annual Sum or Average 0.210332E+12         0.105720E+12        
Minimum of Months 0.665055E+10 6825.55   -18.3 -18.9 0.741862E+10 4847.83   -18.3 -18.9
Maximum of Months 0.256239E+11 15848.52   25.10 15.43 0.987819E+10 6462.76   25.00 15.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.434805E+11 29613.07 30-JAN-22:05 -25.8 -26.1 0.254310E+11 16842.71 20-JAN-23:10 -25.8 -26.1
February 0.455445E+11 31931.20 21-FEB-19:53 -23.9 -24.1 0.234495E+11 17595.57 09-FEB-22:49 -23.9 -24.1
March 0.578282E+11 33353.56 01-MAR-21:53 -23.9 -24.5 0.275778E+11 18576.07 22-MAR-22:10 1.42 -0.3
April 0.646577E+11 34384.75 21-APR-21:10 9.53 3.30 0.291049E+11 19184.85 21-APR-23:19 4.80 1.11
May 0.720505E+11 35850.61 31-MAY-21:10 16.47 9.79 0.310880E+11 19186.24 11-MAY-21:40 16.47 9.79
June 0.736719E+11 38343.74 21-JUN-21:03 23.53 13.66 0.307359E+11 19186.29 02-JUN-21:40 23.53 13.66
July 0.764041E+11 38929.12 21-JUL-21:10 22.70 14.59 0.315998E+11 19186.72 01-JUL-00:10 22.70 14.59
August 0.746003E+11 39052.68 11-AUG-21:10 22.33 14.00 0.316275E+11 19186.27 01-AUG-22:10 22.33 14.00
September 0.645385E+11 32532.47 10-SEP-10:33 13.87 7.59 0.291635E+11 19184.58 01-SEP-21:19 13.87 7.59
October 0.584624E+11 29365.00 03-OCT-20:00 6.10 2.72 0.281175E+11 19177.05 03-OCT-22:10 7.30 3.10
November 0.448195E+11 33419.15 08-NOV-20:53 -23.9 -24.2 0.248194E+11 17151.67 01-NOV-22:10 -23.9 -24.2
December 0.407531E+11 32566.36 27-DEC-20:13 -24.1 -24.3 0.250627E+11 16535.05 19-DEC-23:10 -24.1 -24.3
                     
Annual Sum or Average 0.716811E+12         0.337778E+12        
Minimum of Months 0.407531E+11 29365.00   -25.8 -26.1 0.234495E+11 16535.05   -25.8 -26.1
Maximum of Months 0.764041E+11 39052.68   23.53 14.59 0.316275E+11 19186.72   23.53 14.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 900055.13 926.10 22-JAN-09:04 -6.2 -6.5 92318884.36 56.69 10-JAN-04:19 -6.2 -6.5
February 5522401.23 1104.71 11-FEB-19:04 -3.0 -3.9 83674806.61 56.69 07-FEB-04:19 -3.0 -3.9
March 75471428.14 3020.71 31-MAR-15:01 -9.9 -12.2 94572145.22 56.69 05-MAR-02:20 -9.9 -12.2
April 0.811193E+09 3164.62 21-APR-18:01 14.22 5.92 94415532.09 56.69 21-APR-22:19 6.47 1.92
May 0.145145E+10 3289.41 31-MAY-18:02 21.13 10.92 98713972.25 56.69 11-MAY-21:10 21.13 10.92
June 0.205294E+10 3409.14 22-JUN-18:02 23.22 12.45 95840082.08 56.70 19-JUN-21:10 23.22 12.45
July 0.197756E+10 3239.77 06-JUL-18:01 24.40 15.16 98918770.47 56.70 24-JUL-21:49 18.98 14.94
August 0.153960E+10 3108.31 17-AUG-18:01 17.88 10.69 98805609.03 56.70 02-AUG-21:40 17.88 10.69
September 0.439846E+09 3085.96 02-SEP-18:02 16.52 10.34 93963893.66 56.69 01-SEP-01:00 16.52 10.34
October 33858519.41 2910.15 13-OCT-15:02 1.70 -2.0 93979170.51 56.69 15-OCT-23:19 -0.8 -1.2
November 1189307.77 790.66 04-NOV-08:04 -8.3 -9.8 89404508.08 56.69 10-NOV-04:19 -18.9 -19.3
December 525399.18 949.08 24-DEC-19:04 -4.0 -4.2 92229385.86 56.69 29-DEC-04:19 -15.8 -16.2
                     
Annual Sum or Average 0.839006E+10         0.112684E+10        
Minimum of Months 525399.18 790.66   -9.9 -12.2 83674806.61 56.69   -18.9 -19.3
Maximum of Months 0.205294E+10 3409.14   24.40 15.16 98918770.47 56.70   23.22 14.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 637445.58 1014.68 22-JAN-09:04 -6.2 -6.5 92312686.38 56.69 27-JAN-04:19 -14.8 -15.1
February 2008665.33 1193.95 08-FEB-19:04 0.22 -1.6 83421134.23 56.69 20-FEB-02:20 -18.7 -19.0
March 14287470.47 2227.06 27-MAR-18:01 -7.2 -9.8 93158705.65 56.69 03-MAR-00:20 -7.2 -9.8
April 0.442817E+09 2851.78 21-APR-18:01 14.22 5.92 93038607.69 56.69 21-APR-21:30 8.60 2.92
May 0.949512E+09 3330.00 09-MAY-20:01 13.35 5.95 0.103257E+09 89.83 10-MAY-21:10 14.13 6.05
June 0.148517E+10 3232.01 26-JUN-21:51 19.40 13.93 0.107910E+09 103.81 28-JUN-21:10 19.72 14.76
July 0.142475E+10 3442.23 06-JUL-17:32 24.23 15.21 0.108445E+09 91.25 11-JUL-21:30 21.10 13.07
August 0.949049E+09 3064.05 02-AUG-21:51 19.40 14.21 0.105961E+09 92.29 10-AUG-21:10 17.93 10.68
September 0.211650E+09 2886.78 02-SEP-19:41 13.27 9.27 93300601.73 56.69 01-SEP-01:19 13.27 9.27
October 10590748.85 1929.36 03-OCT-15:02 12.62 6.83 93208660.44 56.69 24-OCT-03:20 -4.4 -4.6
November 405836.84 858.45 04-NOV-08:04 -8.3 -9.8 89378448.58 56.69 17-NOV-04:19 -20.6 -20.8
December 411384.28 867.16 24-DEC-19:04 -4.0 -4.2 92229193.27 56.69 17-DEC-02:20 -4.0 -4.2
                     
Annual Sum or Average 0.549130E+10         0.115562E+10        
Minimum of Months 405836.84 858.45   -8.3 -9.8 83421134.23 56.69   -20.6 -20.8
Maximum of Months 0.148517E+10 3442.23   24.23 15.21 0.108445E+09 103.81   21.10 14.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 64164.02 11.33 25-JAN-15:20 -19.3 -19.6 0.00 0.00 01-JAN-00:10 -19.3 -19.6
February 2851208.93 84.94 15-FEB-15:20 -7.2 -8.6 0.00 0.00 01-FEB-00:10 -7.2 -8.6
March 64963163.67 517.10 31-MAR-13:20 -11.5 -13.4 0.00 0.00 01-MAR-00:10 -11.5 -13.4
April 0.457551E+09 804.77 22-APR-13:20 15.20 6.93 0.00 0.00 01-APR-00:10 15.20 6.93
May 0.588920E+09 766.95 12-MAY-13:15 20.60 9.86 0.00 0.00 01-MAY-00:10 20.60 9.86
June 0.661599E+09 678.42 30-JUN-12:30 26.15 17.75 0.00 0.00 01-JUN-00:10 26.15 17.75
July 0.689610E+09 807.73 23-JUL-13:30 25.00 15.26 0.00 0.00 01-JUL-00:10 25.00 15.26
August 0.640980E+09 851.58 25-AUG-13:30 21.70 14.78 0.00 0.00 01-AUG-00:10 21.70 14.78
September 0.318637E+09 757.41 09-SEP-13:10 12.98 8.62 0.00 0.00 01-SEP-00:10 12.98 8.62
October 73742497.36 601.57 03-OCT-12:50 9.63 5.75 0.00 0.00 01-OCT-00:10 9.63 5.75
November 533368.96 44.64 08-NOV-15:20 -14.6 -15.2 0.00 0.00 01-NOV-00:10 -14.6 -15.2
December 0.00 0.00 01-DEC-00:03 -25.8 -26.0 0.00 0.00 01-DEC-00:10 -25.8 -26.0
                     
Annual Sum or Average 0.349945E+10         0.00        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.00 0.00   -25.8 -26.0
Maximum of Months 0.689610E+09 851.58   26.15 17.75 0.00 0.00   26.15 17.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 3611699.38 376.29 09-JAN-09:04 -18.9 -19.1 93377305.08 56.69 03-JAN-22:10 -18.9 -19.1
February 6666512.80 440.79 12-FEB-16:04 -3.9 -5.1 84622440.23 56.69 23-FEB-00:20 -22.8 -23.0
March 26958233.65 762.84 22-MAR-18:02 2.98 0.38 94675159.82 56.69 22-MAR-23:19 -0.2 -1.5
April 0.198791E+09 845.39 30-APR-18:02 9.72 3.97 93216591.99 56.69 27-APR-21:10 9.72 3.97
May 0.516276E+09 939.03 31-MAY-15:02 21.28 10.75 99740394.52 74.62 11-MAY-21:10 21.28 10.75
June 0.695087E+09 1013.31 22-JUN-21:51 19.40 11.71 0.101011E+09 79.78 19-JUN-21:19 19.40 11.71
July 0.702403E+09 958.02 29-JUL-18:02 27.12 18.22 0.104191E+09 78.80 10-JUL-21:49 27.12 18.22
August 0.531161E+09 950.70 02-AUG-21:51 19.40 14.21 0.102236E+09 75.66 02-AUG-21:40 19.40 14.21
September 0.272813E+09 832.11 07-SEP-18:01 14.13 7.59 93761228.70 56.69 20-SEP-21:10 8.30 7.74
October 76332899.45 777.26 03-OCT-18:01 9.72 4.62 95102720.29 56.69 05-OCT-21:10 7.30 3.88
November 4347745.94 409.91 14-NOV-19:04 -15.0 -15.4 90449267.12 56.69 10-NOV-04:19 -15.0 -15.4
December 2327295.90 456.99 24-DEC-09:01 0.18 -1.3 93205534.50 56.69 19-DEC-04:19 0.18 -1.3
                     
Annual Sum or Average 0.303678E+10         0.114559E+10        
Minimum of Months 2327295.90 376.29   -18.9 -19.1 84622440.23 56.69   -22.8 -23.0
Maximum of Months 0.702403E+09 1013.31   27.12 18.22 0.104191E+09 79.78   27.12 18.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 874361.60 942.63 22-JAN-09:04 -6.2 -6.5 92332621.14 56.69 10-JAN-04:19 -6.2 -6.5
February 7533562.07 1122.34 07-FEB-19:04 -1.1 -2.8 83851225.51 56.69 07-FEB-04:19 -1.1 -2.8
March 0.131688E+09 2868.95 31-MAR-15:01 -9.9 -12.2 95729466.76 56.69 14-MAR-03:20 -9.9 -12.2
April 0.783111E+09 2950.90 20-APR-15:01 13.80 6.27 94894222.92 56.69 28-APR-21:30 2.80 1.37
May 0.191433E+10 3111.00 12-MAY-15:01 20.00 9.30 99054396.77 56.69 13-MAY-23:00 12.20 5.89
June 0.229481E+10 3165.85 22-JUN-18:02 23.22 12.45 95950308.79 56.69 30-JUN-21:00 17.60 14.01
July 0.237473E+10 3093.71 29-JUL-18:02 27.12 18.22 99057114.12 56.70 24-JUL-21:00 27.12 18.22
August 0.180396E+10 3040.70 23-AUG-18:02 24.90 15.24 99053219.20 56.70 04-AUG-21:10 24.90 15.24
September 0.579545E+09 2871.95 07-SEP-18:01 14.13 7.59 94514460.96 56.69 01-SEP-00:30 14.13 7.59
October 69648986.16 2784.33 04-OCT-08:62 7.88 2.97 94524578.97 56.69 01-OCT-01:19 7.88 2.97
November 981601.25 834.13 04-NOV-08:04 -8.3 -9.8 89412544.91 56.69 10-NOV-04:19 -18.9 -19.3
December 464058.39 897.79 24-DEC-09:04 0.18 -1.3 92229783.98 56.69 29-DEC-04:19 -15.8 -16.2
                     
Annual Sum or Average 0.996168E+10         0.113060E+10        
Minimum of Months 464058.39 834.13   -9.9 -12.2 83851225.51 56.69   -18.9 -19.3
Maximum of Months 0.237473E+10 3165.85   27.12 18.22 99057114.12 56.70   27.12 18.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 558920.58 899.36 22-JAN-09:04 -6.2 -6.5 92317543.64 56.69 27-JAN-04:19 -14.8 -15.1
February 2346392.99 1059.53 11-FEB-19:04 -3.0 -3.9 83485879.49 56.69 20-FEB-02:20 -18.7 -19.0
March 41292874.34 2420.17 27-MAR-08:61 -14.4 -15.8 94108114.05 56.69 07-MAR-04:19 -14.4 -15.8
April 0.385066E+09 2653.33 23-APR-08:62 6.97 1.91 93850291.49 56.69 28-APR-21:10 3.53 1.78
May 0.143638E+10 2908.13 14-MAY-20:41 13.68 7.57 0.101710E+09 78.07 12-MAY-21:10 13.68 7.57
June 0.179997E+10 3114.95 29-JUN-08:51 18.90 14.54 0.103646E+09 82.12 22-JUN-21:40 18.90 14.54
July 0.181707E+10 3603.63 11-JUL-08:32 20.53 14.32 0.107360E+09 85.54 07-JUL-21:10 20.53 14.32
August 0.124837E+10 2916.59 10-AUG-21:51 16.10 9.68 0.104178E+09 79.26 02-AUG-21:19 16.10 9.68
September 0.320077E+09 2592.32 07-SEP-18:01 14.13 7.59 94025096.02 56.69 01-SEP-01:19 14.13 7.59
October 25248175.73 2449.01 04-OCT-08:62 7.88 2.97 93715161.53 56.69 01-OCT-01:19 7.88 2.97
November 308263.30 827.04 04-NOV-08:04 -8.3 -9.8 89383278.27 56.69 12-NOV-02:20 -20.2 -20.5
December 371214.59 901.86 24-DEC-19:04 -4.0 -4.2 92229478.13 56.69 17-DEC-02:20 -4.0 -4.2
                     
Annual Sum or Average 0.707706E+10         0.115001E+10        
Minimum of Months 308263.30 827.04   -14.4 -15.8 83485879.49 56.69   -20.2 -20.5
Maximum of Months 0.181707E+10 3603.63   20.53 14.54 0.107360E+09 85.54   20.53 14.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 41848602.27 377.10 23-JAN-22:10 -15.9 -16.2 0.119782E+10 704.47 26-JAN-01:00 -23.9 -24.2
February 0.260423E+09 818.16 09-FEB-22:10 -9.6 -9.9 0.108387E+10 704.46 27-FEB-03:49 -34.5 -34.6
March 0.138346E+10 1424.17 22-MAR-18:07 2.98 0.38 0.120543E+10 723.26 22-MAR-21:49 1.78 0.04
April 0.323414E+10 1967.89 22-APR-10:33 11.87 5.55 0.123680E+10 826.06 21-APR-21:40 11.87 5.55
May 0.432405E+10 2191.28 14-MAY-10:33 16.83 8.94 0.141396E+10 892.60 12-MAY-21:40 16.83 8.94
June 0.463888E+10 2300.42 13-JUN-10:33 21.83 12.30 0.146804E+10 945.22 22-JUN-21:40 19.80 11.82
July 0.477898E+10 2333.29 23-JUL-10:33 22.23 15.22 0.150235E+10 943.62 12-JUL-21:40 22.23 15.22
August 0.446169E+10 2194.78 01-AUG-10:33 15.93 12.83 0.145001E+10 923.01 02-AUG-21:40 19.80 14.37
September 0.328144E+10 1917.46 10-SEP-10:33 13.87 7.59 0.123504E+10 830.68 01-SEP-00:10 13.87 7.59
October 0.144746E+10 1551.08 03-OCT-10:33 5.37 3.67 0.120163E+10 733.97 03-OCT-22:10 7.30 3.10
November 52927219.12 514.65 01-NOV-21:10 -8.9 -9.5 0.115966E+10 704.48 16-NOV-23:00 -23.9 -24.1
December 11519967.43 380.26 24-DEC-22:00 -5.0 -5.4 0.119875E+10 704.48 22-DEC-00:00 -5.0 -5.4
                     
Annual Sum or Average 0.279168E+11         0.153534E+11        
Minimum of Months 11519967.43 377.10   -15.9 -16.2 0.108387E+10 704.46   -34.5 -34.6
Maximum of Months 0.477898E+10 2333.29   22.23 15.22 0.150235E+10 945.22   22.23 15.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 261921.01 374.55 22-JAN-09:04 -6.2 -6.5 92281510.87 56.69 27-JAN-04:19 -14.8 -15.1
February 2054239.11 831.40 09-FEB-19:04 -7.5 -7.8 83415197.75 56.69 05-FEB-02:20 -7.5 -7.8
March 55927854.09 3100.61 27-MAR-18:01 -7.2 -9.8 93816344.01 56.69 07-MAR-04:19 -7.2 -9.8
April 0.759108E+09 3311.69 21-APR-18:01 14.22 5.92 93952705.21 56.69 12-APR-22:30 14.22 5.92
May 0.134164E+10 3430.62 31-MAY-18:02 21.13 10.92 98540534.26 56.69 11-MAY-21:10 21.13 10.92
June 0.200662E+10 3549.12 22-JUN-18:02 23.22 12.45 95757666.74 56.70 29-JUN-22:40 20.53 15.75
July 0.193417E+10 3402.66 11-JUL-18:02 26.02 15.10 98835527.26 56.70 07-JUL-21:19 26.02 15.10
August 0.144999E+10 3565.09 10-AUG-18:02 22.62 12.07 98647074.47 56.70 01-AUG-21:00 22.62 12.07
September 0.356252E+09 3217.53 02-SEP-18:02 16.52 10.34 93478591.39 56.69 08-SEP-23:00 4.40 3.92
October 22230779.05 2866.30 13-OCT-15:02 1.70 -2.0 93346917.39 56.69 01-OCT-01:19 1.70 -2.0
November 282648.75 374.18 08-NOV-16:04 -16.5 -16.8 89354082.25 56.69 23-NOV-02:20 -18.5 -18.8
December 207459.85 630.66 24-DEC-09:04 0.18 -1.3 92205826.98 56.69 16-DEC-00:20 0.18 -1.3
                     
Annual Sum or Average 0.792875E+10         0.112363E+10        
Minimum of Months 207459.85 374.18   -16.5 -16.8 83415197.75 56.69   -18.5 -18.8
Maximum of Months 0.200662E+10 3565.09   26.02 15.10 98835527.26 56.70   26.02 15.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 273707.93 449.84 22-JAN-09:04 -6.2 -6.5 92280492.47 56.69 17-JAN-04:19 -6.2 -6.5
February 1034994.54 734.38 09-FEB-16:04 0.13 -0.8 83360459.24 56.69 14-FEB-04:19 -15.7 -16.0
March 6496507.66 1455.39 28-MAR-15:03 -5.5 -8.7 92810932.81 56.69 05-MAR-02:20 -5.5 -8.7
April 0.389188E+09 2949.83 21-APR-18:01 14.22 5.92 92500970.39 56.69 20-APR-21:19 14.22 5.92
May 0.833300E+09 3757.76 09-MAY-19:42 14.27 6.45 0.103605E+09 97.79 10-MAY-21:10 14.13 6.05
June 0.147615E+10 3593.42 28-JUN-21:32 18.87 14.85 0.109181E+09 115.42 28-JUN-21:10 18.87 14.85
July 0.140893E+10 3552.52 06-JUL-17:32 24.23 15.21 0.109299E+09 94.86 06-JUL-21:30 20.55 14.54
August 0.870661E+09 3180.35 02-AUG-21:51 19.40 14.21 0.106600E+09 101.19 10-AUG-21:10 17.93 10.68
September 0.143502E+09 3048.75 02-SEP-19:41 13.27 9.27 92672079.18 56.69 01-SEP-03:20 13.27 9.27
October 7497992.50 1428.78 05-OCT-15:03 10.68 5.71 92762788.51 56.69 20-OCT-03:20 -0.4 -0.6
November 172586.82 398.68 04-NOV-08:04 -8.3 -9.8 89353074.96 56.69 24-NOV-04:19 -9.4 -10.0
December 207900.88 600.45 24-DEC-09:04 0.18 -1.3 92206701.29 56.69 01-DEC-04:19 0.18 -1.3
                     
Annual Sum or Average 0.513742E+10         0.115663E+10        
Minimum of Months 172586.82 398.68   -8.3 -9.8 83360459.24 56.69   -15.7 -16.0
Maximum of Months 0.147615E+10 3757.76   24.23 15.21 0.109299E+09 115.42   20.55 14.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2928529.84 598.75 22-JAN-19:04 -6.7 -7.0 92496909.17 56.69 14-JAN-00:20 -6.7 -7.0
February 38713252.43 2102.16 15-FEB-16:01 -7.3 -8.7 85158432.60 56.69 06-FEB-00:20 -7.3 -8.7
March 0.290666E+09 2187.98 15-MAR-15:01 -10.6 -12.6 96492955.44 56.69 22-MAR-23:19 -0.2 -1.5
April 0.827192E+09 2238.11 20-APR-15:01 13.80 6.27 95042118.78 56.69 20-APR-21:00 5.60 1.90
May 0.110278E+10 2286.80 10-MAY-15:01 18.90 9.17 98789384.45 56.69 11-MAY-22:19 10.73 5.23
June 0.129343E+10 2303.50 22-JUN-18:02 23.22 12.45 95785023.32 56.69 29-JUN-21:30 23.05 16.39
July 0.136467E+10 2320.49 23-JUL-15:02 25.60 15.39 98885192.46 56.70 10-JUL-21:19 25.60 15.39
August 0.122638E+10 2306.41 10-AUG-18:02 22.62 12.07 98869028.30 56.70 24-AUG-21:49 14.97 12.21
September 0.583218E+09 2117.98 07-SEP-18:01 14.13 7.59 94737768.06 56.69 01-SEP-01:49 14.13 7.59
October 0.158857E+09 2146.98 13-OCT-15:02 1.70 -2.0 95498810.43 56.69 01-OCT-23:19 1.70 -2.0
November 6156304.47 1996.45 08-NOV-16:01 -16.5 -16.8 89847255.54 56.69 05-NOV-23:19 -16.5 -16.8
December 510622.18 590.80 24-DEC-19:04 -4.0 -4.2 92252232.03 56.69 19-DEC-04:19 -4.0 -4.2
                     
Annual Sum or Average 0.689549E+10         0.113386E+10        
Minimum of Months 510622.18 590.80   -16.5 -16.8 85158432.60 56.69   -16.5 -16.8
Maximum of Months 0.136467E+10 2320.49   25.60 15.39 98885192.46 56.70   25.60 16.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.267293E+11 16995.61 11-JAN-22:40 -35.2 -35.3 0.174215E+11 11347.89 19-JAN-00:20 -9.2 -9.3
February 0.251730E+11 16363.52 28-FEB-22:10 -29.6 -29.7 0.158230E+11 11347.94 10-FEB-00:20 -29.6 -29.7
March 0.292958E+11 17388.83 22-MAR-22:00 1.70 0.03 0.184171E+11 11347.93 12-MAR-23:19 1.70 0.03
April 0.322445E+11 19132.88 21-APR-21:10 9.53 3.30 0.184308E+11 11347.96 09-APR-23:19 9.53 3.30
May 0.381949E+11 20953.76 31-MAY-21:52 15.30 9.39 0.192701E+11 11349.18 11-MAY-21:40 15.30 9.39
June 0.404833E+11 22498.82 21-JUN-21:03 23.53 13.66 0.187355E+11 11349.18 15-JUN-22:10 23.53 13.66
July 0.416004E+11 22776.91 11-JUL-21:10 21.83 13.37 0.192833E+11 11349.22 10-JUL-22:10 21.83 13.37
August 0.392548E+11 21547.80 02-AUG-21:52 19.40 14.21 0.193253E+11 11349.22 01-AUG-22:10 19.40 14.21
September 0.334733E+11 19207.74 01-SEP-22:00 10.00 8.27 0.185155E+11 11347.98 10-SEP-23:19 7.60 6.01
October 0.305786E+11 17931.77 06-OCT-22:00 7.20 3.44 0.188033E+11 11347.95 15-OCT-23:19 -0.8 -1.2
November 0.260168E+11 16030.67 28-NOV-23:00 -28.9 -29.1 0.168920E+11 11367.58 07-NOV-22:49 -28.9 -29.1
December 0.263612E+11 16708.36 14-DEC-24:00 -30.0 -30.1 0.170362E+11 11347.85 26-DEC-00:20 -10.9 -11.3
                     
Annual Sum or Average 0.389406E+12         0.217954E+12        
Minimum of Months 0.251730E+11 16030.67   -35.2 -35.3 0.158230E+11 11347.85   -29.6 -29.7
Maximum of Months 0.416004E+11 22776.91   23.53 14.21 0.193253E+11 11367.58   23.53 14.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.298302E+11 18391.62 11-JAN-22:30 -35.0 -35.1 0.177841E+11 11347.97 19-JAN-00:20 -9.2 -9.3
February 0.280696E+11 18109.23 08-FEB-23:00 -1.1 -2.8 0.161135E+11 11348.01 13-FEB-00:20 -14.3 -14.6
March 0.327573E+11 19404.36 22-MAR-22:00 1.70 0.03 0.186829E+11 11347.99 26-MAR-23:19 -17.1 -18.1
April 0.358484E+11 20815.18 21-APR-21:10 9.53 3.30 0.185730E+11 11348.00 09-APR-23:19 9.53 3.30
May 0.418489E+11 22387.14 31-MAY-21:52 15.30 9.39 0.193197E+11 11349.19 11-MAY-21:40 15.30 9.39
June 0.436548E+11 23757.13 21-JUN-21:03 23.53 13.66 0.187541E+11 11366.01 15-JUN-21:19 23.53 13.66
July 0.448479E+11 24083.28 11-JUL-21:10 21.83 13.37 0.193021E+11 11365.23 27-JUL-21:19 17.97 13.68
August 0.426742E+11 22846.66 02-AUG-21:20 20.20 14.52 0.193640E+11 11373.05 25-AUG-21:19 17.60 13.41
September 0.372607E+11 20940.96 01-SEP-22:00 10.00 8.27 0.186209E+11 11348.00 10-SEP-23:19 7.60 6.01
October 0.343194E+11 19974.74 06-OCT-22:00 7.20 3.44 0.190214E+11 11348.01 29-OCT-23:19 -11.3 -12.1
November 0.290419E+11 17036.98 28-NOV-23:00 -28.9 -29.1 0.172567E+11 11369.69 07-NOV-22:49 -28.9 -29.1
December 0.293096E+11 17746.52 14-DEC-24:00 -30.0 -30.1 0.174216E+11 11347.95 27-DEC-00:20 -22.4 -22.7
                     
Annual Sum or Average 0.429463E+12         0.220214E+12        
Minimum of Months 0.280696E+11 17036.98   -35.0 -35.1 0.161135E+11 11347.95   -28.9 -29.1
Maximum of Months 0.448479E+11 24083.28   23.53 14.52 0.193640E+11 11373.05   23.53 13.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.428777E+11 23847.08 22-JAN-11:50 -6.6 -6.9 0.187155E+11 11319.68 14-JAN-18:19 -6.6 -6.9
February 0.400966E+11 25243.48 09-FEB-11:50 -2.0 -2.3 0.169196E+11 11319.68 25-FEB-18:19 -23.2 -23.7
March 0.472502E+11 27432.78 22-MAR-10:33 2.43 0.50 0.187712E+11 11319.65 04-MAR-18:19 2.43 0.50
April 0.492996E+11 29469.86 22-APR-10:50 12.33 5.78 0.182008E+11 11319.67 22-APR-17:19 13.87 6.05
May 0.546753E+11 30028.59 12-MAY-10:33 17.43 8.33 0.188341E+11 11319.61 20-MAY-17:19 13.30 6.36
June 0.545354E+11 30522.26 29-JUN-10:45 22.02 15.69 0.182443E+11 11319.67 10-JUN-17:19 22.02 15.69
July 0.564196E+11 31130.64 22-JUL-10:40 23.67 16.46 0.188451E+11 11319.68 29-JUL-17:19 29.07 18.36
August 0.548379E+11 30286.61 10-AUG-10:33 18.87 11.69 0.188446E+11 11319.68 26-AUG-17:19 20.93 13.69
September 0.496968E+11 29051.07 10-SEP-10:33 13.87 7.59 0.182135E+11 11319.65 09-SEP-17:19 13.87 7.59
October 0.475950E+11 27381.66 03-OCT-10:33 5.37 3.67 0.187951E+11 11319.62 21-OCT-17:19 -11.3 -11.8
November 0.416895E+11 23653.41 02-NOV-18:03 -8.9 -9.2 0.181274E+11 11319.69 25-NOV-18:19 -21.3 -21.6
December 0.421300E+11 23917.98 24-DEC-11:50 1.60 -0.2 0.187166E+11 11319.68 16-DEC-18:19 1.60 -0.2
                     
Annual Sum or Average 0.581104E+12         0.221228E+12        
Minimum of Months 0.400966E+11 23653.41   -8.9 -9.2 0.169196E+11 11319.61   -23.2 -23.7
Maximum of Months 0.564196E+11 31130.64   23.67 16.46 0.188451E+11 11319.69   29.07 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2077390.50 263.82 21-JAN-21:50 -2.5 -3.6 0.126818E+10 745.69 26-JAN-02:09 -24.0 -24.3
February 0.197147E+09 2104.21 09-FEB-13:30 -0.3 -1.5 0.114714E+10 745.81 18-FEB-05:19 -23.5 -23.8
March 0.181985E+10 3159.56 22-MAR-17:13 4.67 1.29 0.127573E+10 756.96 22-MAR-21:40 1.87 0.05
April 0.611369E+10 4247.17 22-APR-10:33 11.87 5.55 0.128222E+10 864.02 21-APR-21:30 11.87 5.55
May 0.905575E+10 4747.29 14-MAY-10:33 16.83 8.94 0.144503E+10 933.15 31-MAY-21:40 15.77 9.56
June 0.998615E+10 5234.84 21-JUN-15:30 25.30 14.00 0.152820E+10 1001.55 21-JUN-21:19 23.17 13.57
July 0.103782E+11 5996.52 23-JUL-13:50 25.00 15.26 0.157070E+10 998.46 11-JUL-21:30 25.00 15.26
August 0.950952E+10 4836.56 02-AUG-17:15 23.13 14.52 0.150217E+10 970.79 02-AUG-21:40 19.80 14.37
September 0.669932E+10 4135.31 10-SEP-10:33 13.87 7.59 0.127665E+10 836.46 01-SEP-21:40 13.87 7.59
October 0.258718E+10 3380.26 03-OCT-10:33 5.37 3.67 0.127056E+10 770.84 03-OCT-21:40 7.20 3.00
November 1786739.32 168.34 01-NOV-21:20 -8.9 -9.5 0.122735E+10 745.69 08-NOV-02:30 -24.1 -24.4
December 3071151.26 345.50 24-DEC-22:50 -3.6 -4.0 0.126881E+10 745.75 19-DEC-01:49 -3.6 -4.0
                     
Annual Sum or Average 0.563538E+11         0.160627E+11        
Minimum of Months 1786739.32 168.34   -8.9 -9.5 0.114714E+10 745.69   -24.1 -24.4
Maximum of Months 0.103782E+11 5996.52   25.30 15.26 0.157070E+10 1001.55   25.00 15.26



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242005E+10 2555.12 13-JAN-15:20 -25.0
February 0.109393E+10 1512.42 28-FEB-08:07 -25.6
March 0.276863E+09 1554.34 01-MAR-08:04 -28.1
April 7807039.54 397.24 03-APR-06:15 -21.3
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 244.85 0.41 30-SEP-07:00 -5.0
October 0.202067E+09 1044.83 30-OCT-08:30 -16.7
November 0.198525E+10 1937.93 30-NOV-10:10 -28.4
December 0.312690E+10 2061.59 15-DEC-18:35 -27.9
         
Annual Sum or Average 0.911287E+10      
Minimum of Months 0.00 0.00   -28.4
Maximum of Months 0.312690E+10 2555.12   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4830500.03 273.46 13-JAN-13:00 -28.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 1208908.90 158.35 15-DEC-15:40 -30.2
         
Annual Sum or Average 6039408.93      
Minimum of Months 0.00 0.00   -30.2
Maximum of Months 4830500.03 273.46   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.537054E+09 989.34 12-JAN-16:00 -35.6
February 0.315214E+09 639.47 27-FEB-11:03 -33.0
March 87214387.94 583.99 01-MAR-05:00 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 2916030.62 79.25 31-OCT-10:03 -16.5
November 0.338760E+09 652.82 30-NOV-11:38 -27.8
December 0.710100E+09 805.00 15-DEC-14:50 -30.9
         
Annual Sum or Average 0.199126E+10      
Minimum of Months 0.00 0.00   -35.6
Maximum of Months 0.710100E+09 989.34   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.961457E+09 906.21 13-JAN-11:08 -30.6
February 0.638396E+09 687.54 27-FEB-11:03 -33.0
March 0.259675E+09 603.42 01-MAR-05:00 -28.3
April 9857727.49 155.68 03-APR-09:07 -13.6
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 86160083.65 285.64 31-OCT-09:40 -16.9
November 0.787838E+09 714.62 30-NOV-11:20 -28.3
December 0.112484E+10 841.98 15-DEC-14:20 -31.7
         
Annual Sum or Average 0.386822E+10      
Minimum of Months 0.00 0.00   -33.0
Maximum of Months 0.112484E+10 906.21   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.427593E+09 4082.63 13-JAN-14:40 -26.0
February 14715567.83 1027.05 01-FEB-09:50 -17.0
March 3630.20 40.83 01-MAR-08:03 -28.1
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 608739.56 332.97 30-OCT-08:40 -16.7
November 0.214769E+09 2539.20 27-NOV-10:20 -27.2
December 0.941544E+09 2940.39 06-DEC-10:40 -27.4
         
Annual Sum or Average 0.159923E+10      
Minimum of Months 0.00 0.00   -28.1
Maximum of Months 0.941544E+09 4082.63   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6579807.42 1057.95 13-JAN-13:10 -28.5
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 6579807.42      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 6579807.42 1057.95   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.252001E+10 3100.22 13-JAN-16:02 -23.6
February 0.172397E+10 3080.78 25-FEB-16:01 -21.8
March 0.104475E+10 3045.42 15-MAR-08:61 -22.4
April 0.177561E+09 3026.54 03-APR-08:61 -17.1
May 4448481.12 978.02 28-MAY-08:03 6.57
June 1959461.94 1081.32 24-JUN-18:04 12.12
July 2463052.21 1028.75 25-JUL-08:04 13.90
August 3058973.52 1151.26 29-AUG-15:04 15.50
September 0.113173E+09 2929.44 29-SEP-08:61 -4.4
October 0.905145E+09 3063.10 30-OCT-08:61 -16.7
November 0.224460E+10 3102.38 26-NOV-16:01 -22.4
December 0.277787E+10 3090.98 12-DEC-09:01 -22.1
         
Annual Sum or Average 0.115190E+11      
Minimum of Months 1959461.94 978.02   -23.6
Maximum of Months 0.277787E+10 3102.38   15.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.261599E+10 3031.24 30-JAN-16:01 -22.9
February 0.200515E+10 3018.12 25-FEB-16:01 -21.8
March 0.141238E+10 3006.57 03-MAR-09:01 -21.0
April 0.293927E+09 2970.91 03-APR-08:61 -17.1
May 5685411.92 1081.50 25-MAY-18:04 9.82
June 560726.10 852.38 25-JUN-15:05 12.48
July 1064328.84 817.36 26-JUL-08:04 12.38
August 3313149.64 1001.67 19-AUG-15:04 12.80
September 0.169964E+09 2900.60 29-SEP-08:61 -4.4
October 0.111336E+10 2998.03 31-OCT-15:01 -11.6
November 0.240375E+10 3035.55 26-NOV-16:01 -22.4
December 0.280821E+10 3018.89 28-DEC-19:01 -19.3
         
Annual Sum or Average 0.128334E+11      
Minimum of Months 560726.10 817.36   -22.9
Maximum of Months 0.280821E+10 3035.55   12.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.398156E+09 379.96 12-JAN-04:10 -37.3
February 85571720.87 261.24 26-FEB-06:00 -25.6
March 6556487.85 229.92 01-MAR-05:00 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.263983E+09 302.28 29-NOV-05:00 -28.9
December 0.526549E+09 357.29 15-DEC-05:00 -33.3
         
Annual Sum or Average 0.128082E+10      
Minimum of Months 0.00 0.00   -37.3
Maximum of Months 0.526549E+09 379.96   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.442017E+09 878.93 30-JAN-16:01 -22.9
February 0.326137E+09 877.46 28-FEB-16:01 -22.4
March 0.196981E+09 875.86 01-MAR-16:01 -12.8
April 25608709.26 839.86 03-APR-15:01 -5.5
May 137177.96 148.66 06-MAY-15:07 16.70
June 17907.93 71.07 18-JUN-15:08 13.68
July 13473.99 58.81 25-JUL-15:07 15.78
August 83728.24 269.05 31-AUG-15:05 14.08
September 1240449.97 317.82 26-SEP-08:03 0.60
October 97814864.19 870.52 31-OCT-15:01 -11.6
November 0.405675E+09 879.33 26-NOV-16:01 -22.4
December 0.494478E+09 874.19 28-DEC-16:02 -21.5
         
Annual Sum or Average 0.199020E+10      
Minimum of Months 13473.99 58.81   -22.9
Maximum of Months 0.494478E+09 879.33   16.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248842E+10 3058.27 13-JAN-16:02 -23.6
February 0.160474E+10 3042.86 25-FEB-16:01 -21.8
March 0.831401E+09 3003.07 01-MAR-19:01 -19.7
April 0.176072E+09 2953.44 04-APR-08:61 -8.0
May 2842383.68 985.33 03-MAY-18:04 13.03
June 773183.58 986.63 27-JUN-08:04 13.40
July 956363.33 1067.38 01-JUL-08:04 12.80
August 1978366.55 1133.32 14-AUG-08:04 11.88
September 85629515.36 2530.01 27-SEP-15:01 3.40
October 0.788969E+09 3022.09 30-OCT-08:61 -16.7
November 0.223880E+10 3061.47 26-NOV-16:01 -22.4
December 0.277153E+10 3049.68 12-DEC-09:01 -22.1
         
Annual Sum or Average 0.109921E+11      
Minimum of Months 773183.58 985.33   -23.6
Maximum of Months 0.277153E+10 3061.47   13.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258089E+10 2991.57 13-JAN-16:02 -23.6
February 0.186977E+10 2986.21 25-FEB-16:01 -21.8
March 0.114517E+10 2959.58 01-MAR-19:01 -19.7
April 0.298358E+09 2914.12 04-APR-08:61 -8.0
May 3678660.37 902.23 26-MAY-15:04 5.92
June 404508.71 857.98 25-JUN-15:05 12.48
July 254809.49 420.29 26-JUL-08:04 12.38
August 2349776.12 960.85 20-AUG-15:04 17.02
September 0.129365E+09 2778.87 27-SEP-15:01 3.40
October 0.967568E+09 2959.18 27-OCT-08:61 -18.2
November 0.239824E+10 2998.27 26-NOV-16:01 -22.4
December 0.280116E+10 2981.32 28-DEC-19:01 -19.3
         
Annual Sum or Average 0.121972E+11      
Minimum of Months 254809.49 420.29   -23.6
Maximum of Months 0.280116E+10 2998.27   17.02



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167430E+10 2171.81 13-JAN-15:00 -25.6
February 0.686788E+09 1315.16 27-FEB-15:00 -28.3
March 82455206.52 1073.55 01-MAR-08:03 -28.1
April 2360668.47 215.30 03-APR-08:03 -17.1
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.124180E+09 908.44 30-OCT-08:03 -16.7
November 0.130894E+10 1654.43 29-NOV-10:20 -29.4
December 0.212267E+10 1853.23 15-DEC-16:00 -30.0
         
Annual Sum or Average 0.600170E+10      
Minimum of Months 0.00 0.00   -30.0
Maximum of Months 0.212267E+10 2171.81   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.357319E+10 3803.84 13-JAN-16:02 -23.6
February 0.255349E+10 3771.82 25-FEB-16:01 -21.8
March 0.166558E+10 3735.57 03-MAR-09:01 -21.0
April 0.373462E+09 3699.85 03-APR-08:61 -17.1
May 22966594.07 952.51 07-MAY-08:04 12.88
June 2111495.45 972.64 05-JUN-08:04 13.58
July 2313580.72 952.66 13-JUL-08:04 13.17
August 12507657.71 1399.04 30-AUG-08:62 2.07
September 0.272016E+09 3623.33 30-SEP-08:61 -5.0
October 0.146457E+10 3748.68 27-OCT-08:61 -18.2
November 0.324681E+10 3802.36 26-NOV-16:01 -22.4
December 0.389019E+10 3786.28 28-DEC-19:01 -19.3
         
Annual Sum or Average 0.170792E+11      
Minimum of Months 2111495.45 952.51   -23.6
Maximum of Months 0.389019E+10 3803.84   13.58



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.368048E+10 3692.23 13-JAN-16:02 -23.6
February 0.288797E+10 3672.93 25-FEB-16:01 -21.8
March 0.214869E+10 3658.36 03-MAR-09:01 -21.0
April 0.564415E+09 3610.70 03-APR-08:61 -17.1
May 31504314.86 979.06 08-MAY-15:04 14.90
June 847128.27 882.04 15-JUN-08:04 11.28
July 1242469.74 969.58 03-JUL-08:04 14.50
August 17868629.21 1947.36 31-AUG-08:62 2.48
September 0.387022E+09 3553.08 30-SEP-08:61 -5.0
October 0.173851E+10 3646.74 31-OCT-15:01 -11.6
November 0.343057E+10 3695.41 26-NOV-16:01 -22.4
December 0.392347E+10 3673.42 28-DEC-19:01 -19.3
         
Annual Sum or Average 0.188126E+11      
Minimum of Months 847128.27 882.04   -23.6
Maximum of Months 0.392347E+10 3695.41   14.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154608E+10 2129.90 13-JAN-16:02 -23.6
February 0.850323E+09 2111.72 01-FEB-16:01 -12.2
March 0.417006E+09 2073.70 13-MAR-08:61 -23.0
April 62178930.53 2054.88 03-APR-08:61 -17.1
May 2383993.11 582.81 26-MAY-08:03 6.88
June 1217391.01 536.29 16-JUN-08:04 12.77
July 1242364.06 531.04 10-JUL-08:04 15.97
August 1343466.83 574.06 18-AUG-15:04 13.22
September 32582351.02 1473.70 28-SEP-08:61 -2.0
October 0.393050E+09 2091.19 30-OCT-08:61 -16.7
November 0.131598E+10 2119.20 26-NOV-16:01 -22.4
December 0.179934E+10 2119.45 28-DEC-16:02 -21.5
         
Annual Sum or Average 0.642273E+10      
Minimum of Months 1217391.01 531.04   -23.6
Maximum of Months 0.179934E+10 2129.90   15.97



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:05 -10.0
December 0.00 0.00 01-DEC-00:03 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.629813E+10 6246.83 13-JAN-10:30 -30.9
February 0.351107E+10 5142.92 27-FEB-07:05 -34.9
March 0.107953E+10 4585.12 01-MAR-08:06 -28.1
April 60756288.11 1611.54 03-APR-06:05 -21.5
May 0.00 0.00 01-MAY-00:05 6.70
June 0.00 0.00 01-JUN-00:05 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:05 8.08
October 0.512580E+09 2314.73 27-OCT-08:15 -18.5
November 0.557858E+10 5402.97 29-NOV-10:20 -29.4
December 0.768941E+10 5864.76 15-DEC-11:09 -33.3
         
Annual Sum or Average 0.247301E+11      
Minimum of Months 0.00 0.00   -34.9
Maximum of Months 0.768941E+10 6246.83   16.35



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.866285E+10 8344.11 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.782177E+10 8344.11 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.868956E+10 8344.11 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.836914E+10 8344.11 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.867788E+10 8344.11 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.840753E+10 8344.11 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.863949E+10 8344.11 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.869290E+10 8344.11 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.837248E+10 8344.11 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.865952E+10 8344.11 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.840085E+10 8344.11 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.863949E+10 8344.11 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.102033E+12     0.143105E+12    
Minimum of Months 0.782177E+10 8344.11   0.109726E+11 9632.53  
Maximum of Months 0.869290E+10 8344.11   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.478695E+09 461.08 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.432218E+09 461.08 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.480171E+09 461.08 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.462465E+09 461.08 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.479525E+09 461.08 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.464586E+09 461.08 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.477404E+09 461.08 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.480355E+09 461.08 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.462650E+09 461.08 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.478511E+09 461.08 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.464217E+09 461.08 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.477404E+09 461.08 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.563820E+10     0.101856E+11    
Minimum of Months 0.432218E+09 461.08   0.780982E+09 685.60  
Maximum of Months 0.480355E+09 461.08   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554331E+09 533.93 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.500510E+09 533.93 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.556040E+09 533.93 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.535537E+09 533.93 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.555292E+09 533.93 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.537993E+09 533.93 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.552836E+09 533.93 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.556253E+09 533.93 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.535750E+09 533.93 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.554117E+09 533.93 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.537566E+09 533.93 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.552836E+09 533.93 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.652906E+10     0.117950E+11    
Minimum of Months 0.500510E+09 533.93   0.904380E+09 793.93  
Maximum of Months 0.556253E+09 533.93   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639281E+09 615.76 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.577212E+09 615.76 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.641251E+09 615.76 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.617606E+09 615.76 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.640389E+09 615.76 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.620439E+09 615.76 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.637557E+09 615.76 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.641498E+09 615.76 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.617853E+09 615.76 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.639035E+09 615.76 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.619946E+09 615.76 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.637557E+09 615.76 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.752962E+10     0.124712E+11    
Minimum of Months 0.577212E+09 615.76   0.956227E+09 839.45  
Maximum of Months 0.641498E+09 615.76   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142601E+09 137.35 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.128756E+09 137.35 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.143041E+09 137.35 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.137766E+09 137.35 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.142848E+09 137.35 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.138398E+09 137.35 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.142217E+09 137.35 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.143096E+09 137.35 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.137821E+09 137.35 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.142546E+09 137.35 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.138288E+09 137.35 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.142217E+09 137.35 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.167960E+10     0.359760E+10    
Minimum of Months 0.128756E+09 137.35   0.275845E+09 242.16  
Maximum of Months 0.143096E+09 137.35   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.374392E+09 360.62 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.338042E+09 360.62 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.375546E+09 360.62 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.361698E+09 360.62 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.375041E+09 360.62 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.363357E+09 360.62 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.373382E+09 360.62 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.375690E+09 360.62 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.361842E+09 360.62 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.374247E+09 360.62 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.363068E+09 360.62 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.373382E+09 360.62 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.440969E+10     0.679355E+11    
Minimum of Months 0.338042E+09 360.62   0.520895E+10 4572.80  
Maximum of Months 0.375690E+09 360.62   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135983E+10 1416.11 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.109633E+10 1416.11 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.105043E+10 1416.11 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.742971E+09 1416.11 03-APR-19:40 0.117692E+10 965.27 03-APR-19:10
May 0.658255E+09 1258.77 04-MAY-20:30 0.121917E+10 965.27 01-MAY-19:10
June 0.541148E+09 1106.77 02-JUN-20:00 0.118076E+10 965.27 01-JUN-19:10
July 0.602043E+09 1147.23 28-JUL-20:00 0.121533E+10 965.27 03-JUL-19:10
August 0.761890E+09 1416.11 29-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.949323E+09 1416.11 01-SEP-19:30 0.117729E+10 965.27 01-SEP-19:10
October 0.116678E+10 1416.11 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.125833E+10 1416.11 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.141852E+10 1416.11 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.116058E+11     0.143405E+11    
Minimum of Months 0.541148E+09 1106.77   0.109956E+10 965.27  
Maximum of Months 0.141852E+10 1416.11   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.982886E+10 9580.84 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.871198E+10 9580.84 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.948314E+10 9580.84 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.884142E+10 9580.84 03-APR-19:40 0.122282E+11 10029.21 03-APR-19:10
May 0.904633E+10 9388.46 02-MAY-19:00 0.126672E+11 10029.21 01-MAY-19:10
June 0.865456E+10 9231.95 02-JUN-19:00 0.122682E+11 10029.21 01-JUN-19:10
July 0.894915E+10 9186.25 28-JUL-19:00 0.126273E+11 10029.21 03-JUL-19:10
August 0.918033E+10 9580.84 29-AUG-19:30 0.126824E+11 10029.21 01-AUG-19:10
September 0.907498E+10 9580.84 01-SEP-19:30 0.122320E+11 10029.21 01-SEP-19:10
October 0.959021E+10 9580.84 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.945882E+10 9580.84 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.987693E+10 9580.84 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110697E+12     0.148998E+12    
Minimum of Months 0.865456E+10 9186.25   0.114244E+11 10029.21  
Maximum of Months 0.987693E+10 9580.84   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74229181.22 67.16 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 67036196.95 67.16 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 73639243.64 67.16 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 71920171.51 67.16 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 73934212.43 67.16 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 71349576.37 67.16 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 74514478.79 67.16 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 73639243.64 67.16 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 71939513.95 67.16 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 74219510.00 67.16 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 71634873.94 67.16 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 74524150.01 67.16 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.872580E+09     0.300992E+10    
Minimum of Months 67036196.95 67.16   0.230956E+09 232.19  
Maximum of Months 74524150.01 67.16   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.108388E+10 1044.00 02-JAN-20:10 0.00 0.00
February 0.978647E+09 1044.00 01-FEB-20:10 0.00 0.00
March 0.108722E+10 1044.00 01-MAR-20:10 0.00 0.00
April 0.104713E+10 1044.00 03-APR-19:10 0.00 0.00
May 0.108576E+10 1044.00 01-MAY-19:10 0.00 0.00
June 0.105194E+10 1044.00 01-JUN-19:10 0.00 0.00
July 0.108096E+10 1044.00 03-JUL-19:10 0.00 0.00
August 0.108764E+10 1044.00 01-AUG-19:10 0.00 0.00
September 0.104755E+10 1044.00 01-SEP-19:10 0.00 0.00
October 0.108346E+10 1044.00 02-OCT-19:10 0.00 0.00
November 0.105110E+10 1044.00 01-NOV-19:10 0.00 0.00
December 0.108096E+10 1044.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.127663E+11     0.00 0.00
Minimum of Months 0.978647E+09 1044.00   0.00 0.00
Maximum of Months 0.108764E+10 1044.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.253350E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.217769E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.224613E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.188146E+10 2486.81 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.180463E+10 2210.50 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.166014E+10 2130.81 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.175715E+10 2115.71 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.193996E+10 2486.81 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.210682E+10 2486.81 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.236109E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.242018E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.256026E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.254490E+11     0.175857E+12    
Minimum of Months 0.166014E+10 2115.71   0.134904E+11 6747.90  
Maximum of Months 0.256026E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.253350E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.217769E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.224613E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.188146E+10 2486.81 03-APR-19:40 0.144540E+11 6747.90 01-APR-06:10
May 0.180463E+10 2210.50 04-MAY-20:30 0.149358E+11 6747.90 01-MAY-06:10
June 0.166014E+10 2130.81 02-JUN-19:00 0.144540E+11 6747.90 01-JUN-06:10
July 0.175715E+10 2115.71 26-JUL-20:00 0.149358E+11 6747.90 01-JUL-06:10
August 0.193993E+10 2486.81 29-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.210682E+10 2486.81 01-SEP-19:30 0.144540E+11 6747.90 01-SEP-06:10
October 0.236109E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.242018E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.256026E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.254490E+11     0.175857E+12    
Minimum of Months 0.166014E+10 2115.71   0.134904E+11 6747.90  
Maximum of Months 0.256026E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101925E+10 981.75 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.920291E+09 981.75 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.102239E+10 981.75 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.984694E+09 981.75 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.102102E+10 981.75 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.989210E+09 981.75 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.101650E+10 981.75 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.102279E+10 981.75 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.985086E+09 981.75 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.101886E+10 981.75 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.988424E+09 981.75 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.101650E+10 981.75 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.120050E+11     0.424019E+12    
Minimum of Months 0.920291E+09 981.75   0.325275E+11 16179.04  
Maximum of Months 0.102279E+10 981.75   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.114712E+10 1104.91 02-JAN-20:10 0.00 0.00
February 0.103575E+10 1104.91 01-FEB-20:10 0.00 0.00
March 0.115066E+10 1104.91 01-MAR-20:10 0.00 0.00
April 0.110823E+10 1104.91 03-APR-19:10 0.00 0.00
May 0.114911E+10 1104.91 01-MAY-19:10 0.00 0.00
June 0.111331E+10 1104.91 01-JUN-19:10 0.00 0.00
July 0.114403E+10 1104.91 03-JUL-19:10 0.00 0.00
August 0.115110E+10 1104.91 01-AUG-19:10 0.00 0.00
September 0.110867E+10 1104.91 01-SEP-19:10 0.00 0.00
October 0.114668E+10 1104.91 02-OCT-19:10 0.00 0.00
November 0.111243E+10 1104.91 01-NOV-19:10 0.00 0.00
December 0.114403E+10 1104.91 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.135111E+11     0.00 0.00
Minimum of Months 0.103575E+10 1104.91   0.00 0.00
Maximum of Months 0.115110E+10 1104.91   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.866285E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.868956E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.836914E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.867788E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.840753E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.837248E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.865952E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.840085E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.102033E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.478695E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.343398E+09
February 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.294598E+09
March 0.199990E+10 0.480171E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.276772E+09
April 0.192973E+10 0.462465E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.00 0.169670E+09
May 0.199475E+10 0.479525E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.00 89617917.42
June 0.193394E+10 0.464586E+09 0.838659E+09 0.00 0.00 0.00 0.00 765222.80 46426066.81
July 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 1669583.84 41276309.64
August 0.199896E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 227791.61 60985057.39
September 0.192879E+10 0.462650E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.00 0.115877E+09
October 0.199148E+10 0.478511E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.206303E+09
November 0.192552E+10 0.464217E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.334856E+09
December 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.362222E+09
                   
Annual Sum or Average 0.234744E+11 0.563820E+10 0.101856E+11 0.00 0.00 0.00 0.00 2662598.25 0.234200E+10
Minimum of Months 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 41276309.64
Maximum of Months 0.199990E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 1669583.84 0.362222E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.554331E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.133349E+09
February 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.114381E+09
March 0.231589E+10 0.556040E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.107942E+09
April 0.223463E+10 0.535537E+09 0.968011E+09 0.00 0.00 0.00 0.00 0.00 68339681.91
May 0.230993E+10 0.555292E+09 0.100276E+10 0.00 0.00 0.00 0.00 0.00 38664450.71
June 0.223950E+10 0.537993E+09 0.971170E+09 0.00 0.00 0.00 0.00 259600.23 22100655.86
July 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 605874.41 20301609.86
August 0.231480E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 77214.53 28044654.70
September 0.223354E+10 0.535750E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.00 48557856.37
October 0.230614E+10 0.554117E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 81963473.29
November 0.222975E+10 0.537566E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.129723E+09
December 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.140100E+09
                   
Annual Sum or Average 0.271834E+11 0.652906E+10 0.117950E+11 0.00 0.00 0.00 0.00 942689.17 0.933467E+09
Minimum of Months 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 20301609.86
Maximum of Months 0.231589E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 605874.41 0.140100E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.639281E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.314546E+09
February 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.268738E+09
March 0.489771E+09 0.641251E+09 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.250897E+09
April 0.472586E+09 0.617606E+09 0.102351E+10 0.00 0.00 0.00 0.00 0.00 0.154781E+09
May 0.488511E+09 0.640389E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.00 88553636.22
June 0.473617E+09 0.620439E+09 0.102685E+10 0.00 0.00 0.00 0.00 624884.83 51911320.31
July 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 1417969.89 48313081.92
August 0.489542E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 254709.43 65648769.97
September 0.472357E+09 0.617853E+09 0.102382E+10 0.00 0.00 0.00 0.00 0.00 0.111600E+09
October 0.487709E+09 0.639035E+09 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.189381E+09
November 0.471555E+09 0.619946E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.305474E+09
December 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.330660E+09
                   
Annual Sum or Average 0.574883E+10 0.752962E+10 0.124712E+11 0.00 0.00 0.00 0.00 2297564.14 0.218050E+10
Minimum of Months 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 48313081.92
Maximum of Months 0.489771E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 1417969.89 0.330660E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.142601E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.181455E+09
February 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.155029E+09
March 0.376747E+09 0.143041E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.144596E+09
April 0.363528E+09 0.137766E+09 0.295253E+09 0.00 0.00 0.00 0.00 0.00 88285276.95
May 0.375778E+09 0.142848E+09 0.305852E+09 0.00 0.00 0.00 0.00 0.00 49974644.43
June 0.364321E+09 0.138398E+09 0.296217E+09 0.00 0.00 0.00 0.00 383418.35 29182958.68
July 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 868238.69 27093875.67
August 0.376571E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 163667.38 36804454.04
September 0.363352E+09 0.137821E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.00 62949940.94
October 0.375161E+09 0.142546E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.108561E+09
November 0.362735E+09 0.138288E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.176241E+09
December 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.190773E+09
                   
Annual Sum or Average 0.442217E+10 0.167960E+10 0.359760E+10 0.00 0.00 0.00 0.00 1415324.42 0.125095E+10
Minimum of Months 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 27093875.67
Maximum of Months 0.376747E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 868238.69 0.190773E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.374392E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.444163E+09
February 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.382071E+09
March 0.155131E+10 0.375546E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.361876E+09
April 0.149688E+10 0.361698E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.00 0.224986E+09
May 0.154732E+10 0.375041E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 213.60 0.125388E+09
June 0.150015E+10 0.363357E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 1054946.30 69257975.10
July 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 2514915.08 63880390.83
August 0.155059E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 418763.07 89354027.04
September 0.149615E+10 0.361842E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.00 0.161289E+09
October 0.154478E+10 0.374247E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.276643E+09
November 0.149361E+10 0.363068E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.433834E+09
December 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.467546E+09
                   
Annual Sum or Average 0.182090E+11 0.440969E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 3988838.05 0.310029E+10
Minimum of Months 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 63880390.83
Maximum of Months 0.155131E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 2514915.08 0.467546E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.135983E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.760143E+09
February 0.236489E+11 0.109633E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.652285E+09
March 0.262800E+11 0.105043E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.617256E+09
April 0.253579E+11 0.742971E+09 0.117692E+10 0.00 0.00 0.00 0.00 0.00 0.387527E+09
May 0.262123E+11 0.658255E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.00 0.213975E+09
June 0.254132E+11 0.541148E+09 0.118076E+10 0.00 0.00 0.00 0.00 1388832.01 0.118119E+09
July 0.261570E+11 0.602043E+09 0.121533E+10 0.00 0.00 0.00 0.00 3176265.36 0.106825E+09
August 0.262677E+11 0.761890E+09 0.122063E+10 0.00 0.00 0.00 0.00 368047.92 0.151016E+09
September 0.253456E+11 0.949323E+09 0.117729E+10 0.00 0.00 0.00 0.00 0.00 0.268447E+09
October 0.261693E+11 0.116678E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.461489E+09
November 0.253025E+11 0.125833E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.740395E+09
December 0.261570E+11 0.141852E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.800861E+09
                   
Annual Sum or Average 0.308468E+12 0.116058E+11 0.143405E+11 0.00 0.00 0.00 0.00 4933145.29 0.527834E+10
Minimum of Months 0.236489E+11 0.541148E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.106825E+09
Maximum of Months 0.262800E+11 0.141852E+10 0.122063E+10 0.00 0.00 0.00 0.00 3176265.36 0.800861E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.982886E+10 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.219435E+10
February 0.702046E+11 0.871198E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.188503E+10
March 0.780153E+11 0.948314E+10 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.178971E+10
April 0.752779E+11 0.884142E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.00 0.113711E+10
May 0.778146E+11 0.904633E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.00 0.648096E+09
June 0.754422E+11 0.865456E+10 0.122682E+11 0.00 0.00 0.00 0.00 3833117.95 0.370911E+09
July 0.776503E+11 0.894915E+10 0.126273E+11 0.00 0.00 0.00 0.00 8697914.54 0.341508E+09
August 0.779788E+11 0.918033E+10 0.126824E+11 0.00 0.00 0.00 0.00 940013.25 0.471138E+09
September 0.752414E+11 0.907498E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.00 0.811690E+09
October 0.776868E+11 0.959021E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.136114E+10
November 0.751137E+11 0.945882E+10 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.213607E+10
December 0.776503E+11 0.987693E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.230229E+10
                   
Annual Sum or Average 0.915726E+12 0.110697E+12 0.148998E+12 0.00 0.00 0.00 0.00 13471045.74 0.154490E+11
Minimum of Months 0.702046E+11 0.865456E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.341508E+09
Maximum of Months 0.780153E+11 0.987693E+10 0.126824E+11 0.00 0.00 0.00 0.00 8697914.54 0.230229E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.197694E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.169130E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.159206E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 97978386.74
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 7308.36 52372806.19
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 802760.23 26988434.20
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 1637552.58 24442108.09
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 413736.61 35757956.24
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 67855170.15
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.118606E+09
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.192024E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.207897E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 2861357.78 0.134995E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 24442108.09
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1637552.58 0.207897E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.197664E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.168794E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.157623E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 96508808.07
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 47.14 53825207.64
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 617412.50 30927319.61
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 1216760.83 27455614.19
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 259023.54 37989226.48
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 67028475.51
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.117775E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.191968E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.207878E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 2093244.01 0.135544E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 27455614.19
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1216760.83 0.207878E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 74229181.22 0.255708E+09 0.00 0.00 0.00 0.00 0.00 48127108.83
February 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 42491042.65
March 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 0.00 47120166.80
April 0.00 71920171.51 0.247516E+09 0.00 0.00 0.00 0.00 0.00 33841983.97
May 0.00 73934212.43 0.255532E+09 0.00 0.00 0.00 0.00 0.00 21113612.56
June 0.00 71349576.37 0.247163E+09 0.00 0.00 0.00 0.00 2510.87 13462209.29
July 0.00 74514478.79 0.255885E+09 0.00 0.00 0.00 0.00 25123.25 12723289.89
August 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 0.00 16347355.59
September 0.00 71939513.95 0.247516E+09 0.00 0.00 0.00 0.00 0.00 25483767.20
October 0.00 74219510.00 0.255708E+09 0.00 0.00 0.00 0.00 0.00 36899415.36
November 0.00 71634873.94 0.247340E+09 0.00 0.00 0.00 0.00 0.00 46941354.55
December 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 0.00 50864626.97
                   
Annual Sum or Average 0.00 0.872580E+09 0.300992E+10 0.00 0.00 0.00 0.00 27634.12 0.395416E+09
Minimum of Months 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 12723289.89
Maximum of Months 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 25123.25 50864626.97



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 0.00 55413448.65
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 0.00 47407645.91
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 0.00 44408127.40
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 0.00 27036773.98
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 17.68 14640330.75
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 175543.86 7975088.67
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 356032.28 7251736.45
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 77861.12 10217387.32
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 0.00 18871926.57
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 0.00 33350928.29
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 0.00 53829427.96
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 0.00 58238535.90
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 609454.93 0.378641E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 0.00 7251736.45
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 356032.28 58238535.90



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.197715E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.169361E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.160547E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 98497429.97
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 7905.56 52665786.77
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 808752.04 27098352.40
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 1640891.96 24574923.51
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 419823.52 35977029.92
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 68383825.30
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.119204E+09
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.192036E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.207897E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 2877373.09 0.135396E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 24574923.51
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1640891.96 0.207897E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.197673E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.168884E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.158816E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 97585208.29
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 62.79 53645197.65
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 622662.72 29782539.61
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 1217379.01 27469370.37
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 263353.06 37664902.12
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 67895760.14
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.118346E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.191977E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.207878E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 2103457.58 0.135762E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 27469370.37
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1217379.01 0.207878E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.108388E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.242187E+09
February 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.206974E+09
March 0.387034E+10 0.108722E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.193113E+09
April 0.373454E+10 0.104713E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.118950E+09
May 0.386038E+10 0.108576E+10 0.00 0.00 0.00 0.00 0.00 0.00 68239323.01
June 0.374269E+10 0.105194E+10 0.00 0.00 0.00 0.00 0.00 420030.71 40186625.37
July 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 984795.85 36625572.74
August 0.386853E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 188779.28 49001679.36
September 0.373273E+10 0.104755E+10 0.00 0.00 0.00 0.00 0.00 0.00 82906373.18
October 0.385404E+10 0.108346E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.144623E+09
November 0.372639E+10 0.105110E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.235278E+09
December 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.254656E+09
                   
Annual Sum or Average 0.454292E+11 0.127663E+11 0.00 0.00 0.00 0.00 0.00 1593605.85 0.167274E+10
Minimum of Months 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 0.00 36625572.74
Maximum of Months 0.387034E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 984795.85 0.254656E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.197985E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.169136E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.158723E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 97837958.41
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 5983.42 52528310.42
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 777467.67 27176990.38
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 1593718.50 24621941.68
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 398256.41 35906597.54
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 67701670.01
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.118312E+09
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.192282E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.208208E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 2775426.00 0.135042E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 24621941.68
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1593718.50 0.208208E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.197963E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.169036E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.157643E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 96299500.87
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 19.06 54103216.73
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 603461.97 31512657.08
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 1186814.92 27927745.38
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 251740.72 38354065.37
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 66738665.61
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.117695E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.192257E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.208189E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 2042036.67 0.135772E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 27927745.38
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1186814.92 0.208189E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.101456E+09
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 0.00 87542055.27
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 0.00 82653242.87
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 0.00 50599722.15
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 3281.06 26981739.53
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 401610.42 13920572.96
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 817435.93 12621658.37
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 205390.08 18469835.24
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 0.00 35224000.34
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 0.00 61613468.06
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 0.00 98703019.14
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.106562E+09
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 1427717.50 0.696347E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 0.00 12621658.37
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 817435.93 0.106562E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.253350E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.509120E+09
February 0.415303E+11 0.217769E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.437077E+09
March 0.461508E+11 0.224613E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.416918E+09
April 0.445315E+11 0.188146E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.264895E+09
May 0.460320E+11 0.180463E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.153857E+09
June 0.446286E+11 0.166014E+10 0.144540E+11 0.00 0.00 0.00 0.00 580003.76 89554759.13
July 0.459349E+11 0.175715E+10 0.149358E+11 0.00 0.00 0.00 0.00 1376933.51 82855014.89
August 0.461292E+11 0.193996E+10 0.149358E+11 0.00 0.00 0.00 0.00 137252.98 0.112412E+09
September 0.445099E+11 0.210682E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.192724E+09
October 0.459565E+11 0.236109E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.321674E+09
November 0.444343E+11 0.242018E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.495018E+09
December 0.459349E+11 0.256026E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.532137E+09
                   
Annual Sum or Average 0.541708E+12 0.254490E+11 0.175857E+12 0.00 0.00 0.00 0.00 2094190.25 0.360824E+10
Minimum of Months 0.415303E+11 0.166014E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 82855014.89
Maximum of Months 0.461508E+11 0.256026E+10 0.149358E+11 0.00 0.00 0.00 0.00 1376933.51 0.532137E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.253350E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.512348E+09
February 0.415303E+11 0.217769E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.439839E+09
March 0.461508E+11 0.224613E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.419759E+09
April 0.445315E+11 0.188146E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.266667E+09
May 0.460320E+11 0.180463E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.154649E+09
June 0.446286E+11 0.166014E+10 0.144540E+11 0.00 0.00 0.00 0.00 578623.89 89864376.22
July 0.459349E+11 0.175715E+10 0.149358E+11 0.00 0.00 0.00 0.00 1369336.40 83164422.72
August 0.461292E+11 0.193993E+10 0.149358E+11 0.00 0.00 0.00 0.00 137238.95 0.113056E+09
September 0.445099E+11 0.210682E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.194180E+09
October 0.459565E+11 0.236109E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.324188E+09
November 0.444343E+11 0.242018E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.498302E+09
December 0.459349E+11 0.256026E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.535344E+09
                   
Annual Sum or Average 0.541708E+12 0.254490E+11 0.175857E+12 0.00 0.00 0.00 0.00 2085199.24 0.363136E+10
Minimum of Months 0.415303E+11 0.166014E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 83164422.72
Maximum of Months 0.461508E+11 0.256026E+10 0.149358E+11 0.00 0.00 0.00 0.00 1369336.40 0.535344E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.101925E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.463337E+09
February 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.398484E+09
March 0.410691E+10 0.102239E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.377501E+09
April 0.396281E+10 0.984694E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.237804E+09
May 0.409635E+10 0.102102E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.137210E+09
June 0.397146E+10 0.989210E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 521058.02 79588444.07
July 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 1230707.52 73545466.38
August 0.410499E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 124319.71 0.100274E+09
September 0.396089E+10 0.985086E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.172970E+09
October 0.408962E+10 0.101886E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.290582E+09
November 0.395417E+10 0.988424E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.451493E+09
December 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.486516E+09
                   
Annual Sum or Average 0.482060E+11 0.120050E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 1876085.25 0.326931E+10
Minimum of Months 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 73545466.38
Maximum of Months 0.410691E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 1230707.52 0.486516E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.114712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.429324E+09
February 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.366882E+09
March 0.409620E+10 0.115066E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.342437E+09
April 0.395248E+10 0.110823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.209717E+09
May 0.408566E+10 0.114911E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.118544E+09
June 0.396110E+10 0.111331E+10 0.00 0.00 0.00 0.00 0.00 549406.93 70435600.03
July 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 1342599.77 64327956.02
August 0.409429E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 223780.12 85557503.59
September 0.395056E+10 0.110867E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.145522E+09
October 0.407896E+10 0.114668E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.256537E+09
November 0.394385E+10 0.111243E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.417018E+09
December 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.451357E+09
                   
Annual Sum or Average 0.480803E+11 0.135111E+11 0.00 0.00 0.00 0.00 0.00 2115786.82 0.295766E+10
Minimum of Months 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 0.00 64327956.02
Maximum of Months 0.409620E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 1342599.77 0.451357E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 8344.11 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 8344.11 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 8344.11 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 8344.11 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 8344.11 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 8344.11 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 8344.11 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 8344.11 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 8344.11 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 8344.11 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 8344.11 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 8344.11 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 461.08 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 206.81 12-JAN-06:00
February 1169.53 01-FEB-00:10 461.08 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 199.67 27-FEB-05:03
March 1169.53 01-MAR-00:10 461.08 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 176.36 01-MAR-07:00
April 1169.53 01-APR-00:10 461.08 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 145.14 03-APR-06:00
May 1169.53 01-MAY-00:10 461.08 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 65.62 28-MAY-02:00
June 1169.53 01-JUN-00:10 461.08 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 12.22 30-JUN-15:00 55.50 02-JUN-04:00
July 1169.53 01-JUL-00:10 461.08 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 19.65 29-JUL-17:00 42.82 31-JUL-03:40
August 1169.53 01-AUG-00:10 461.08 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 7.99 11-AUG-18:00 72.53 31-AUG-06:00
September 1169.53 01-SEP-00:10 461.08 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 83.67 30-SEP-09:00
October 1169.53 01-OCT-23:10 461.08 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 141.94 22-OCT-06:40
November 1169.53 01-NOV-00:10 461.08 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 178.05 29-NOV-10:00
December 1169.53 01-DEC-00:10 461.08 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 192.71 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 0.00   42.82  
Maximum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 19.65   206.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 533.93 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 83.32 12-JAN-06:00
February 1354.32 01-FEB-00:10 533.93 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 78.91 27-FEB-05:00
March 1354.32 01-MAR-00:10 533.93 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 68.08 01-MAR-07:00
April 1354.32 01-APR-00:10 533.93 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 57.17 03-APR-06:00
May 1354.32 01-MAY-00:10 533.93 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 27.08 27-MAY-04:00
June 1354.32 01-JUN-00:10 533.93 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 5.43 30-JUN-15:00 24.03 02-JUN-04:00
July 1354.32 01-JUL-00:10 533.93 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 7.44 29-JUL-16:00 19.45 31-JUL-05:00
August 1354.32 01-AUG-00:10 533.93 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 2.42 11-AUG-17:00 30.52 31-AUG-06:00
September 1354.32 01-SEP-00:10 533.93 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 33.70 29-SEP-07:00
October 1354.32 01-OCT-23:10 533.93 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 55.31 22-OCT-07:00
November 1354.32 01-NOV-00:10 533.93 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 69.20 29-NOV-10:00
December 1354.32 01-DEC-00:10 533.93 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 76.31 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 0.00   19.45  
Maximum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 7.44   83.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 615.76 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 198.45 12-JAN-07:40
February 286.42 01-FEB-00:10 615.76 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 186.49 27-FEB-05:00
March 286.42 01-MAR-00:10 615.76 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 160.88 01-MAR-07:00
April 286.42 01-APR-00:10 615.76 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 132.41 03-APR-06:00
May 286.42 01-MAY-00:10 615.76 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 62.73 27-MAY-07:00
June 286.42 01-JUN-00:10 615.76 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 12.88 30-JUN-15:00 55.62 02-JUN-04:00
July 286.42 01-JUL-00:10 615.76 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 17.58 29-JUL-17:00 45.34 31-JUL-05:00
August 286.42 01-AUG-00:10 615.76 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 6.47 11-AUG-17:00 70.81 31-AUG-06:00
September 286.42 01-SEP-00:10 615.76 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 77.76 29-SEP-07:00
October 286.42 01-OCT-23:10 615.76 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 129.48 22-OCT-06:20
November 286.42 01-NOV-00:10 615.76 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 163.53 29-NOV-10:00
December 286.42 01-DEC-00:10 615.76 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 180.34 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 0.00   45.34  
Maximum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 17.58   198.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 137.35 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 114.49 12-JAN-06:50
February 220.32 01-FEB-00:10 137.35 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 107.59 27-FEB-06:00
March 220.32 01-MAR-00:10 137.35 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 92.82 01-MAR-07:00
April 220.32 01-APR-00:10 137.35 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 76.39 03-APR-06:00
May 220.32 01-MAY-00:10 137.35 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 35.70 27-MAY-04:00
June 220.32 01-JUN-00:10 137.35 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 7.46 30-JUN-15:00 31.91 02-JUN-04:00
July 220.32 01-JUL-00:10 137.35 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 10.13 29-JUL-17:00 25.99 31-JUL-05:00
August 220.32 01-AUG-00:10 137.35 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 3.80 11-AUG-17:00 40.20 31-AUG-06:00
September 220.32 01-SEP-00:10 137.35 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 44.03 30-SEP-09:00
October 220.32 01-OCT-23:10 137.35 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 74.70 22-OCT-07:00
November 220.32 01-NOV-00:10 137.35 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 94.35 29-NOV-10:00
December 220.32 01-DEC-00:10 137.35 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 104.05 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 0.00   25.99  
Maximum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 10.13   114.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 360.62 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 263.90 12-JAN-21:00
February 907.20 01-FEB-00:10 360.62 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 246.86 27-FEB-07:10
March 907.20 01-MAR-00:10 360.62 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:05 219.68 01-MAR-07:00
April 907.20 01-APR-00:10 360.62 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 0.00 01-APR-00:10 193.37 03-APR-06:00
May 907.20 01-MAY-00:10 360.62 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 0.26 31-MAY-16:00 92.01 27-MAY-07:10
June 907.20 01-JUN-00:10 360.62 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 19.44 30-JUN-15:00 71.49 02-JUN-04:10
July 907.20 01-JUL-00:10 360.62 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 28.85 29-JUL-17:00 62.61 31-JUL-05:10
August 907.20 01-AUG-00:10 360.62 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 12.93 11-AUG-17:00 102.25 31-AUG-06:00
September 907.20 01-SEP-00:10 360.62 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 0.00 01-SEP-00:05 116.23 30-SEP-09:00
October 907.20 01-OCT-23:10 360.62 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 189.51 22-OCT-07:00
November 907.20 01-NOV-00:10 360.62 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 228.95 30-NOV-21:00
December 907.20 01-DEC-00:10 360.62 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 246.24 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 0.00   62.61  
Maximum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 28.85   263.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1416.11 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 471.51 12-JAN-06:00
February 15368.40 01-FEB-00:10 1416.11 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 451.92 27-FEB-05:30
March 15368.40 01-MAR-00:10 1416.11 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 389.91 01-MAR-07:00
April 15368.40 01-APR-00:10 1416.11 03-APR-19:40 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 320.86 03-APR-06:00
May 15368.40 01-MAY-00:10 1258.77 04-MAY-20:30 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 151.89 27-MAY-05:00
June 15368.40 01-JUN-00:10 1106.77 02-JUN-20:00 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 27.45 30-JUN-15:00 134.67 02-JUN-04:00
July 15368.40 01-JUL-00:10 1147.23 28-JUL-20:00 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 41.59 29-JUL-17:00 107.95 31-JUL-05:00
August 15368.40 01-AUG-00:10 1416.11 29-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 16.60 11-AUG-18:00 167.34 31-AUG-06:00
September 15368.40 01-SEP-00:10 1416.11 01-SEP-19:30 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 185.74 30-SEP-06:00
October 15368.40 01-OCT-23:10 1416.11 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 313.79 22-OCT-06:00
November 15368.40 01-NOV-00:10 1416.11 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 391.59 29-NOV-10:00
December 15368.40 01-DEC-00:10 1416.11 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 432.04 15-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1106.77   965.27   0.00 0.00 0.00 0.00 0.00   107.95  
Maximum of Months 15368.40   1416.11   965.27   0.00 0.00 0.00 0.00 41.59   471.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9580.84 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1370.13 12-JAN-06:00
February 45622.98 01-FEB-00:10 9580.84 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1291.14 27-FEB-06:00
March 45622.98 01-MAR-00:10 9580.84 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1113.88 01-MAR-07:00
April 45622.98 01-APR-00:10 9580.84 03-APR-19:40 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 944.61 03-APR-06:00
May 45622.98 01-MAY-00:10 9388.46 02-MAY-19:00 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 456.31 27-MAY-04:00
June 45622.98 01-JUN-00:10 9231.95 02-JUN-19:00 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 86.19 30-JUN-15:00 404.07 02-JUN-04:00
July 45622.98 01-JUL-00:10 9186.25 28-JUL-19:00 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 118.62 29-JUL-16:00 328.01 31-JUL-05:00
August 45622.98 01-AUG-00:10 9580.84 29-AUG-19:30 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 37.16 11-AUG-17:00 506.63 31-AUG-06:00
September 45622.98 01-SEP-00:10 9580.84 01-SEP-19:30 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 559.84 30-SEP-06:00
October 45622.98 01-OCT-23:10 9580.84 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 915.48 22-OCT-07:00
November 45622.98 01-NOV-00:10 9580.84 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 1132.29 29-NOV-10:00
December 45622.98 01-DEC-00:10 9580.84 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 1247.10 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9186.25   10029.21   0.00 0.00 0.00 0.00 0.00   328.01  
Maximum of Months 45622.98   9580.84   10029.21   0.00 0.00 0.00 0.00 118.62   1370.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.59 12-JAN-06:06
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 118.97 27-FEB-05:10
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.68 01-MAR-07:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.55 03-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 1.75 31-MAY-16:00 38.36 28-MAY-02:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 10.26 30-JUN-15:10 32.49 02-JUN-04:00
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 14.51 29-JUL-16:30 25.12 31-JUL-03:50
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 7.37 11-AUG-16:00 42.38 31-AUG-06:00
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 48.85 30-SEP-09:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.68 22-OCT-06:10
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.36 29-NOV-10:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.06 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 0.00   25.12  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 14.51   126.59  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.58 12-JAN-06:06
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 118.96 27-FEB-05:10
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.67 01-MAR-07:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.54 03-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.21 31-MAY-15:10 38.36 28-MAY-02:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 10.25 30-JUN-15:08 32.49 02-JUN-04:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 14.51 29-JUL-16:00 25.12 31-JUL-03:10
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 7.37 11-AUG-16:10 42.37 31-AUG-06:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 48.84 30-SEP-09:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.67 22-OCT-06:10
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.35 29-NOV-10:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.05 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 0.00   25.12  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 14.51   126.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 67.16 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 32.02 12-JAN-08:00
February 0.00 01-FEB-00:10 67.16 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 29.97 27-FEB-05:10
March 0.00 01-MAR-00:10 67.16 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 28.57 31-MAR-06:00
April 0.00 01-APR-00:10 67.16 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 25.70 03-APR-06:00
May 0.00 01-MAY-00:10 67.16 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 13.42 27-MAY-07:00
June 0.00 01-JUN-00:10 67.16 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 0.73 30-JUN-15:00 11.89 02-JUN-04:00
July 0.00 01-JUL-00:10 67.16 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 1.51 29-JUL-16:10 9.80 31-JUL-03:30
August 0.00 01-AUG-00:10 67.16 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:05 14.70 31-AUG-06:00
September 0.00 01-SEP-00:10 67.16 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 16.52 30-SEP-09:00
October 0.00 01-OCT-00:10 67.16 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 22.86 22-OCT-09:00
November 0.00 01-NOV-00:10 67.16 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 25.96 29-NOV-10:00
December 0.00 01-DEC-00:10 67.16 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 28.87 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 0.00   9.80  
Maximum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 1.51   32.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 35.33 12-JAN-06:10
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 33.20 27-FEB-05:10
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 28.66 01-MAR-07:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 23.60 03-APR-06:00
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 0.06 31-MAY-15:10 11.21 27-MAY-07:30
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 2.86 30-JUN-15:10 9.07 02-JUN-04:00
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 4.05 29-JUL-16:10 7.01 31-JUL-03:10
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 2.06 11-AUG-16:00 11.83 31-AUG-06:00
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 13.94 30-SEP-08:00
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 23.08 22-OCT-06:10
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 29.13 29-NOV-10:00
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 32.11 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 0.00   7.01  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 4.05   35.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.59 12-JAN-06:06
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 118.97 27-FEB-05:10
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.68 01-MAR-07:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.55 03-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 1.75 31-MAY-16:00 39.12 27-MAY-07:20
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 10.26 30-JUN-15:10 32.49 02-JUN-04:00
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 14.51 29-JUL-16:20 25.12 31-JUL-03:10
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 7.37 11-AUG-16:00 43.33 31-AUG-07:10
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 51.88 30-SEP-08:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.68 22-OCT-06:10
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.36 29-NOV-10:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.06 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 0.00   25.12  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 14.51   126.59  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.58 12-JAN-06:06
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 118.96 27-FEB-05:10
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.67 01-MAR-07:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.54 03-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.21 31-MAY-15:08 39.05 27-MAY-07:20
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 10.25 30-JUN-15:10 32.49 02-JUN-04:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 14.51 29-JUL-17:00 25.12 31-JUL-04:07
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 7.37 11-AUG-16:00 43.33 31-AUG-07:10
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 51.06 30-SEP-08:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.67 22-OCT-06:10
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.35 29-NOV-10:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.05 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 0.00   25.12  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 14.51   126.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1044.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 152.56 12-JAN-06:00
February 2263.36 01-FEB-00:10 1044.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 143.58 27-FEB-05:50
March 2263.36 01-MAR-00:10 1044.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 123.89 01-MAR-07:00
April 2263.36 01-APR-00:10 1044.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 101.97 03-APR-06:00
May 2263.36 01-MAY-00:10 1044.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 48.13 27-MAY-04:00
June 2263.36 01-JUN-00:10 1044.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 9.47 30-JUN-15:00 42.95 02-JUN-04:00
July 2263.36 01-JUL-00:10 1044.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 13.08 29-JUL-17:00 34.89 31-JUL-05:00
August 2263.36 01-AUG-00:10 1044.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 4.58 23-AUG-18:00 53.90 31-AUG-06:00
September 2263.36 01-SEP-00:10 1044.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 58.82 30-SEP-09:00
October 2263.36 01-OCT-23:10 1044.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 99.72 22-OCT-07:00
November 2263.36 01-NOV-00:10 1044.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 125.93 29-NOV-10:00
December 2263.36 01-DEC-00:10 1044.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 138.86 15-DEC-08:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 0.00   34.89  
Maximum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 13.08   152.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.75 12-JAN-06:08
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 119.12 27-FEB-05:10
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.82 01-MAR-07:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.68 03-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 1.58 31-MAY-16:00 38.48 28-MAY-02:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 10.16 30-JUN-15:10 32.60 02-JUN-04:00
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 14.42 29-JUL-16:30 25.24 31-JUL-03:10
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 7.27 11-AUG-16:00 42.50 31-AUG-06:00
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 48.97 30-SEP-09:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.82 22-OCT-06:10
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.51 29-NOV-10:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.21 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 0.00   25.24  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 14.42   126.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 126.74 12-JAN-06:08
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 119.11 27-FEB-05:10
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 102.82 01-MAR-07:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 84.68 03-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 0.11 31-MAY-15:10 38.47 28-MAY-02:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 10.16 30-JUN-15:10 32.60 02-JUN-04:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 14.42 29-JUL-16:00 25.24 31-JUL-03:40
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 7.27 11-AUG-16:00 42.49 31-AUG-06:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 48.96 30-SEP-09:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.81 22-OCT-06:10
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.50 29-NOV-10:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 115.21 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 0.00   25.24  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 14.42   126.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 64.85 12-JAN-06:10
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 60.95 27-FEB-05:10
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 52.61 01-MAR-07:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 43.33 03-APR-06:00
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 0.84 31-MAY-16:00 19.80 27-MAY-07:20
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 5.20 30-JUN-15:10 16.68 02-JUN-04:00
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 7.38 29-JUL-16:10 12.91 31-JUL-03:10
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 3.72 11-AUG-16:00 21.74 31-AUG-06:00
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 25.05 30-SEP-09:00
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 42.37 22-OCT-06:10
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 53.47 29-NOV-10:00
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 58.95 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 0.00   12.91  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 7.38   64.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 308.94 12-JAN-08:00
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 290.32 27-FEB-05:20
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 251.71 01-MAR-00:05
April 26988.77 01-APR-00:10 2486.81 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 219.68 03-APR-06:00
May 26988.77 01-MAY-00:10 2210.50 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 106.73 28-MAY-02:00
June 26988.77 01-JUN-00:10 2130.81 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 16.83 30-JUN-15:00 92.42 02-JUN-04:00
July 26988.77 01-JUL-00:10 2115.71 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 23.64 29-JUL-17:00 74.31 31-JUL-04:10
August 26988.77 01-AUG-00:10 2486.81 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 6.06 11-AUG-16:00 116.83 31-AUG-06:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 132.46 30-SEP-06:00
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 216.11 22-OCT-07:00
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 254.66 29-NOV-10:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 280.79 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2115.71   6747.90   0.00 0.00 0.00 0.00 0.00   74.31  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 23.64   308.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 308.93 12-JAN-07:40
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 290.31 27-FEB-05:00
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 252.37 01-MAR-00:05
April 26988.77 01-APR-00:10 2486.81 03-APR-19:40 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 220.67 03-APR-06:00
May 26988.77 01-MAY-00:10 2210.50 04-MAY-20:30 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 106.73 28-MAY-02:00
June 26988.77 01-JUN-00:10 2130.81 02-JUN-19:00 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 16.83 30-JUN-15:00 92.42 02-JUN-04:00
July 26988.77 01-JUL-00:10 2115.71 26-JUL-20:00 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 23.64 29-JUL-17:00 74.31 31-JUL-04:10
August 26988.77 01-AUG-00:10 2486.81 29-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 6.06 11-AUG-16:00 116.83 31-AUG-06:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:30 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 132.61 30-SEP-07:13
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 216.17 22-OCT-06:10
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 254.64 29-NOV-10:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 280.77 15-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2115.71   6747.90   0.00 0.00 0.00 0.00 0.00   74.31  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 23.64   308.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 981.75 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 276.52 12-JAN-08:00
February 2401.70 01-FEB-00:10 981.75 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 257.55 27-FEB-06:20
March 2401.70 01-MAR-00:10 981.75 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:05 224.38 01-MAR-00:05
April 2401.70 01-APR-00:10 981.75 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 197.53 03-APR-06:00
May 2401.70 01-MAY-00:10 981.75 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:05 94.97 27-MAY-07:00
June 2401.70 01-JUN-00:10 981.75 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 15.10 30-JUN-15:00 82.74 02-JUN-04:00
July 2401.70 01-JUL-00:10 981.75 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 21.21 29-JUL-17:00 66.49 31-JUL-05:00
August 2401.70 01-AUG-00:10 981.75 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 5.47 11-AUG-16:00 104.57 31-AUG-06:00
September 2401.70 01-SEP-00:10 981.75 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:05 118.80 30-SEP-09:00
October 2401.70 01-OCT-23:10 981.75 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 193.51 22-OCT-06:10
November 2401.70 01-NOV-00:10 981.75 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 231.48 29-NOV-20:00
December 2401.70 01-DEC-00:10 981.75 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 251.32 15-DEC-08:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 0.00   66.49  
Maximum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 21.21   276.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1104.91 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 269.84 12-JAN-06:00
February 2395.44 01-FEB-00:10 1104.91 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 254.38 27-FEB-05:20
March 2395.44 01-MAR-00:10 1104.91 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 219.51 01-MAR-07:00
April 2395.44 01-APR-00:10 1104.91 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 180.71 03-APR-06:00
May 2395.44 01-MAY-00:10 1104.91 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 82.21 27-MAY-04:00
June 2395.44 01-JUN-00:10 1104.91 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 14.74 30-JUN-15:00 74.39 02-JUN-04:00
July 2395.44 01-JUL-00:10 1104.91 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 21.42 29-JUL-17:00 60.11 31-JUL-05:00
August 2395.44 01-AUG-00:10 1104.91 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 7.30 11-AUG-18:00 91.74 31-AUG-06:00
September 2395.44 01-SEP-00:10 1104.91 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 104.33 30-SEP-09:00
October 2395.44 01-OCT-23:10 1104.91 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 176.73 22-OCT-06:30
November 2395.44 01-NOV-00:10 1104.91 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 223.11 29-NOV-10:00
December 2395.44 01-DEC-00:10 1104.91 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 246.02 15-DEC-08:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 0.00   60.11  
Maximum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 21.42   269.84  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19199.68 11-JAN-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
February 13675.86 28-FEB-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
March 12385.60 01-MAR-21:53 30671.71 22251.00 27376.66 0.00 0.00 0.00 0.00 0.00 0.00
April 10205.32 22-APR-10:33 11501.89 6953.51 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
May 10602.56 14-MAY-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
June 11087.66 29-JUN-10:33 7667.93 6953.51 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
July 12222.00 23-JUL-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
August 12924.96 26-AUG-10:33 11501.89 6953.51 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
September 14747.31 20-SEP-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 14934.50 06-OCT-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 15977.81 28-NOV-23:00 11501.89 5562.78 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
December 16418.80 13-DEC-01:00 11501.89 1854.22 3041.85 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10205.32   7667.93 1854.22 3041.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19199.68   30671.71 22251.00 27376.66 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1098.90 30-JAN-12:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 151.60
February 2141.94 15-FEB-13:40 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 101.31
March 2950.45 27-MAR-14:10 389.84 128.08 252.59 0.00 0.00 0.00 0.00 0.00 92.06
April 4378.13 22-APR-13:30 389.84 128.08 252.59 0.00 0.00 0.00 0.00 0.00 25.50
May 4157.26 12-MAY-13:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 9.81
June 3671.52 29-JUN-14:10 389.84 128.08 252.59 0.00 0.00 0.00 0.00 4.79 0.00
July 4378.24 23-JUL-13:30 259.90 102.46 216.51 0.00 0.00 0.00 0.00 2.86 0.00
August 4635.84 25-AUG-13:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 6.74
September 3968.31 09-SEP-13:30 389.84 128.08 252.59 0.00 0.00 0.00 0.00 0.00 31.83
October 3048.49 03-OCT-13:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 39.48
November 1809.77 08-NOV-13:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 114.22
December 45.16 24-DEC-22:00 1039.58 307.39 505.18 0.00 0.00 0.00 0.00 0.00 81.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 45.16   259.90 102.46 216.51 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4635.84   1039.58 307.39 505.18 0.00 0.00 0.00 0.00 4.79 151.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1184.30 30-JAN-19:25 2106.72 949.22 1504.29 0.00 0.00 0.00 0.00 0.00 58.39
February 1312.76 21-FEB-19:53 3160.08 1423.83 2256.44 0.00 0.00 0.00 0.00 0.00 60.11
March 1362.84 01-MAR-21:53 3611.52 1423.83 2256.44 0.00 0.00 0.00 0.00 0.00 60.69
April 1428.72 21-APR-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 14.01
May 1464.32 10-MAY-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 10.91
June 1688.28 21-JUN-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 0.11
July 1674.12 12-JUL-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 5.74
August 1663.20 11-AUG-21:00 2407.68 949.22 1504.29 0.00 0.00 0.00 0.00 0.00 1.34
September 1310.94 10-SEP-10:33 1354.32 533.93 1002.86 0.00 0.00 0.00 0.00 0.00 9.99
October 1204.47 03-OCT-20:00 1053.36 533.93 793.93 0.00 0.00 0.00 0.00 0.00 20.00
November 1386.55 08-NOV-20:53 3160.08 1601.80 2381.79 0.00 0.00 0.00 0.00 0.00 59.77
December 1340.78 27-DEC-20:13 3160.08 1601.80 2381.79 0.00 0.00 0.00 0.00 0.00 61.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1184.30   1053.36 474.61 752.15 0.00 0.00 0.00 0.00 0.00 0.11
Maximum of Months 1688.28   3611.52 1601.80 2381.79 0.00 0.00 0.00 0.00 0.00 61.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 625.33 23-JAN-22:00 254.59 547.34 795.27 0.00 0.00 0.00 0.00 0.00 108.48
February 706.07 09-FEB-21:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 90.06
March 761.17 22-MAR-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 53.52
April 956.27 22-APR-10:33 286.42 513.13 927.81 0.00 0.00 0.00 0.00 0.00 27.54
May 1058.66 14-MAY-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 0.00 15.93
June 1128.87 22-JUN-21:00 254.59 547.34 795.27 0.00 0.00 0.00 0.00 0.00 9.09
July 1177.66 12-JUL-21:00 254.59 547.34 795.27 0.00 0.00 0.00 0.00 0.00 13.57
August 1084.73 01-AUG-10:33 190.94 513.13 927.81 0.00 0.00 0.00 0.00 0.00 19.62
September 971.06 10-SEP-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 0.00 22.67
October 829.53 04-OCT-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 52.81
November 665.24 02-NOV-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 88.60
December 598.40 24-DEC-21:00 190.94 547.34 795.27 0.00 0.00 0.00 0.00 0.00 81.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 598.40   190.94 513.13 795.27 0.00 0.00 0.00 0.00 0.00 9.09
Maximum of Months 1177.66   286.42 615.76 1060.35 0.00 0.00 0.00 0.00 0.00 108.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 51.81 21-JAN-21:50 171.36 106.83 203.92 0.00 0.00 0.00 0.00 0.00 38.48
February 203.45 09-FEB-22:00 195.84 122.09 229.41 0.00 0.00 0.00 0.00 0.00 52.44
March 380.59 22-MAR-20:00 171.36 137.35 242.16 0.00 0.00 0.00 0.00 0.00 30.05
April 502.52 22-APR-10:33 220.32 114.47 267.65 0.00 0.00 0.00 0.00 0.00 15.55
May 560.24 14-MAY-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 0.00 8.92
June 589.75 22-JUN-10:33 146.88 114.47 267.65 0.00 0.00 0.00 0.00 0.00 2.92
July 611.14 23-JUL-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 0.00 1.54
August 574.87 01-AUG-10:33 146.88 114.47 267.65 0.00 0.00 0.00 0.00 0.00 11.06
September 509.88 10-SEP-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 0.00 12.73
October 410.37 04-OCT-20:00 171.36 137.35 242.16 0.00 0.00 0.00 0.00 0.00 29.46
November 81.15 01-NOV-21:00 195.84 122.09 229.41 0.00 0.00 0.00 0.00 0.00 49.54
December 54.63 24-DEC-22:00 195.84 91.57 178.43 0.00 0.00 0.00 0.00 0.00 42.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 51.81   146.88 91.57 178.43 0.00 0.00 0.00 0.00 0.00 1.54
Maximum of Months 611.14   220.32 137.35 305.88 0.00 0.00 0.00 0.00 0.00 52.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36248.61 20-JAN-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 152.55
February 36794.18 09-FEB-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 134.06
March 37385.98 22-MAR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 82.18
April 38048.19 21-APR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 43.79
May 38460.06 31-MAY-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 24.87
June 38634.16 29-JUN-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 3.54 0.00
July 38710.36 21-JUL-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 3.51 0.00
August 38583.89 11-AUG-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 1.41 0.00
September 37970.16 01-SEP-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 43.87
October 37597.35 03-OCT-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 67.82
November 36363.20 01-NOV-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 129.00
December 36015.14 26-DEC-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 191.84
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36015.14   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38710.36   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 3.54 191.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7074.48 06-JAN-23:10 15368.40 472.04 406.43 0.00 0.00 0.00 0.00 0.00 164.23
February 8570.05 20-FEB-13:00 5122.80 103.85 406.43 0.00 0.00 0.00 0.00 0.00 303.79
March 12095.74 27-MAR-15:03 51228.00 519.24 2133.76 0.00 0.00 0.00 0.00 0.00 202.55
April 15780.72 22-APR-13:30 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 56.37
May 14777.08 13-MAY-13:10 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 32.28
June 13734.39 20-JUN-15:03 51228.00 519.24 2133.76 0.00 0.00 0.00 0.00 6.94 0.00
July 15027.60 23-JUL-13:30 3415.20 69.23 304.82 0.00 0.00 0.00 0.00 6.32 0.00
August 15848.52 25-AUG-14:10 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 7.21
September 14752.39 09-SEP-13:30 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 70.36
October 11240.88 03-OCT-13:30 3415.20 86.54 355.63 0.00 0.00 0.00 0.00 0.00 87.26
November 7374.66 08-NOV-13:30 3415.20 86.54 355.63 0.00 0.00 0.00 0.00 0.00 254.34
December 6825.55 19-DEC-23:10 15368.40 472.04 406.43 0.00 0.00 0.00 0.00 0.00 205.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6825.55   3415.20 69.23 304.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15848.52   51228.00 519.24 2133.76 0.00 0.00 0.00 0.00 6.94 303.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29613.07 30-JAN-22:05 91245.96 12774.46 14779.89 0.00 0.00 0.00 0.00 0.00 1003.32
February 31931.20 21-FEB-19:53 106453.62 25548.91 28504.07 0.00 0.00 0.00 0.00 0.00 990.51
March 33353.56 01-MAR-21:53 121661.28 25548.91 28504.07 0.00 0.00 0.00 0.00 0.00 1001.48
April 34384.75 21-APR-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 274.73
May 35850.61 31-MAY-21:10 91245.96 12567.80 14779.89 0.00 0.00 0.00 0.00 0.00 140.03
June 38343.74 21-JUN-21:03 273737.88 36460.67 44339.66 0.00 0.00 0.00 0.00 0.00 8.56
July 38929.12 21-JUL-21:10 91245.96 12550.85 14779.89 0.00 0.00 0.00 0.00 0.00 23.50
August 39052.68 11-AUG-21:10 45622.98 6372.41 7389.94 0.00 0.00 0.00 0.00 0.00 30.36
September 32532.47 10-SEP-10:33 45622.98 8239.52 12668.47 0.00 0.00 0.00 0.00 0.00 172.99
October 29365.00 03-OCT-20:00 35484.54 9580.84 10029.21 0.00 0.00 0.00 0.00 0.00 333.07
November 33419.15 08-NOV-20:53 106453.62 28742.53 30087.63 0.00 0.00 0.00 0.00 0.00 983.19
December 32566.36 27-DEC-20:13 106453.62 28742.53 30087.63 0.00 0.00 0.00 0.00 0.00 1007.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 29365.00   35484.54 6372.41 7389.94 0.00 0.00 0.00 0.00 0.00 8.56
Maximum of Months 39052.68   273737.88 36460.67 44339.66 0.00 0.00 0.00 0.00 0.00 1007.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 926.10 22-JAN-09:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 49.77
February 1104.71 11-FEB-19:04 819.00 748.06 903.46 0.00 0.00 0.00 0.00 0.00 44.96
March 3020.71 31-MAR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 61.19
April 3164.62 21-APR-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 14.84
May 3289.41 31-MAY-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 0.00 2.37
June 3409.14 22-JUN-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 0.86 0.00
July 3239.77 06-JUL-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 2.50 0.00
August 3108.31 17-AUG-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 7.85
September 3085.96 02-SEP-18:02 702.00 641.20 774.39 0.00 0.00 0.00 0.00 0.00 10.41
October 2910.15 13-OCT-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 36.90
November 790.66 04-NOV-08:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 54.85
December 949.08 24-DEC-19:04 819.00 748.06 903.46 0.00 0.00 0.00 0.00 0.00 45.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 790.66   378.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3409.14   970.20 748.06 1143.15 0.00 0.00 0.00 0.00 2.50 61.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1014.68 22-JAN-09:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 49.77
February 1193.95 08-FEB-19:04 970.20 665.70 903.35 0.00 0.00 0.00 0.00 0.00 37.75
March 2227.06 27-MAR-18:01 970.20 665.70 903.35 0.00 0.00 0.00 0.00 0.00 52.65
April 2851.78 21-APR-18:01 970.20 665.70 903.35 0.00 0.00 0.00 0.00 0.00 14.83
May 3330.00 09-MAY-20:01 1602.00 951.00 1843.57 0.00 0.00 0.00 0.00 0.00 20.14
June 3232.01 26-JUN-21:51 1800.00 715.93 921.79 0.00 0.00 0.00 0.00 0.00 9.90
July 3442.23 06-JUL-17:32 583.20 429.56 805.91 0.00 0.00 0.00 0.00 0.00 4.45
August 3064.05 02-AUG-21:51 1800.00 715.93 921.79 0.00 0.00 0.00 0.00 0.00 8.13
September 2886.78 02-SEP-19:41 936.00 854.83 1390.58 0.00 0.00 0.00 0.00 0.00 17.26
October 1929.36 03-OCT-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 15.07
November 858.45 04-NOV-08:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 54.85
December 867.16 24-DEC-19:04 819.00 747.98 903.35 0.00 0.00 0.00 0.00 0.00 45.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 858.45   378.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 4.45
Maximum of Months 3442.23   1800.00 951.00 1843.57 0.00 0.00 0.00 0.00 0.00 54.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11.33 25-JAN-15:20 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 19.34
February 84.94 15-FEB-15:20 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 15.30
March 517.10 31-MAR-13:20 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 20.28
April 804.77 22-APR-13:20 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 5.47
May 766.95 12-MAY-13:15 0.00 37.61 134.16 0.00 0.00 0.00 0.00 0.00 2.85
June 678.42 30-JUN-12:30 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 0.26
July 807.73 23-JUL-13:30 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 0.79
August 851.58 25-AUG-13:30 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 2.38
September 757.41 09-SEP-13:10 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 6.66
October 601.57 03-OCT-12:50 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 8.34
November 44.64 08-NOV-15:20 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 17.81
December 0.00 01-DEC-00:03 0.00 44.33 154.79 0.00 0.00 0.00 0.00 0.00 22.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 851.58   0.00 44.33 154.79 0.00 0.00 0.00 0.00 0.00 22.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 376.29 09-JAN-09:04 252.00 206.91 776.76 0.00 0.00 0.00 0.00 0.00 20.96
February 440.79 12-FEB-16:04 378.00 155.19 523.86 0.00 0.00 0.00 0.00 0.00 13.05
March 762.84 22-MAR-18:02 831.60 358.74 758.70 0.00 0.00 0.00 0.00 0.00 9.29
April 845.39 30-APR-18:02 702.00 403.08 758.70 0.00 0.00 0.00 0.00 0.00 6.40
May 939.03 31-MAY-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.74
June 1013.31 22-JUN-21:51 1800.00 450.11 903.21 0.00 0.00 0.00 0.00 0.00 2.28
July 958.02 29-JUL-18:02 702.00 403.08 758.70 0.00 0.00 0.00 0.00 1.95 0.00
August 950.70 02-AUG-21:51 1800.00 450.11 903.21 0.00 0.00 0.00 0.00 0.00 2.07
September 832.11 07-SEP-18:01 970.20 418.53 885.15 0.00 0.00 0.00 0.00 0.00 4.01
October 777.26 03-OCT-18:01 970.20 418.53 885.15 0.00 0.00 0.00 0.00 0.00 5.81
November 409.91 14-NOV-19:04 970.20 418.53 885.15 0.00 0.00 0.00 0.00 0.00 19.04
December 456.99 24-DEC-09:01 378.00 263.34 1119.99 0.00 0.00 0.00 0.00 0.00 10.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 376.29   252.00 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1013.31   1800.00 450.11 1119.99 0.00 0.00 0.00 0.00 1.95 20.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 942.63 22-JAN-09:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 49.77
February 1122.34 07-FEB-19:04 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 40.07
March 2868.95 31-MAR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 61.24
April 2950.90 20-APR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 15.40
May 3111.00 12-MAY-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 4.49
June 3165.85 22-JUN-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 1.17 0.00
July 3093.71 29-JUL-18:02 702.00 641.20 774.39 0.00 0.00 0.00 0.00 7.55 0.00
August 3040.70 23-AUG-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 4.05 0.00
September 2871.95 07-SEP-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 14.45
October 2784.33 04-OCT-08:62 216.00 282.13 679.57 0.00 0.00 0.00 0.00 0.00 24.97
November 834.13 04-NOV-08:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 54.85
December 897.79 24-DEC-09:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 37.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 834.13   216.00 209.46 479.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3165.85   970.20 665.78 1143.15 0.00 0.00 0.00 0.00 7.55 61.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 899.36 22-JAN-09:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 49.77
February 1059.53 11-FEB-19:04 819.00 747.98 903.35 0.00 0.00 0.00 0.00 0.00 44.96
March 2420.17 27-MAR-08:61 252.00 329.11 792.74 0.00 0.00 0.00 0.00 0.00 68.79
April 2653.33 23-APR-08:62 324.00 359.03 979.73 0.00 0.00 0.00 0.00 0.00 27.25
May 2908.13 14-MAY-20:41 1386.00 1068.54 1843.57 0.00 0.00 0.00 0.00 0.00 17.26
June 3114.95 29-JUN-08:51 288.00 376.12 905.99 0.00 0.00 0.00 0.00 0.00 11.07
July 3603.63 11-JUL-08:32 216.00 282.09 679.49 0.00 0.00 0.00 0.00 0.00 11.10
August 2916.59 10-AUG-21:51 1800.00 715.93 921.79 0.00 0.00 0.00 0.00 0.00 13.03
September 2592.32 07-SEP-18:01 970.20 665.70 903.35 0.00 0.00 0.00 0.00 0.00 14.19
October 2449.01 04-OCT-08:62 216.00 282.09 679.49 0.00 0.00 0.00 0.00 0.00 24.14
November 827.04 04-NOV-08:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 54.85
December 901.86 24-DEC-19:04 819.00 747.98 903.35 0.00 0.00 0.00 0.00 0.00 45.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 827.04   216.00 282.09 679.49 0.00 0.00 0.00 0.00 0.00 11.07
Maximum of Months 3603.63   1800.00 1068.54 1843.57 0.00 0.00 0.00 0.00 0.00 68.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 377.10 23-JAN-22:10 2263.36 696.00 0.00 0.00 0.00 0.00 0.00 0.00 84.25
February 818.16 09-FEB-22:10 2263.36 696.00 0.00 0.00 0.00 0.00 0.00 0.00 70.54
March 1424.17 22-MAR-18:07 10562.33 5568.01 0.00 0.00 0.00 0.00 0.00 0.00 39.43
April 1967.89 22-APR-10:33 2263.36 870.00 0.00 0.00 0.00 0.00 0.00 0.00 21.54
May 2191.28 14-MAY-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 0.00 12.74
June 2300.42 13-JUN-10:33 1508.90 870.00 0.00 0.00 0.00 0.00 0.00 0.00 3.09
July 2333.29 23-JUL-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 0.00 2.42
August 2194.78 01-AUG-10:33 1508.90 870.00 0.00 0.00 0.00 0.00 0.00 0.00 15.12
September 1917.46 10-SEP-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 0.00 17.03
October 1551.08 03-OCT-10:33 1508.90 870.00 0.00 0.00 0.00 0.00 0.00 0.00 33.76
November 514.65 01-NOV-21:10 2263.36 696.00 0.00 0.00 0.00 0.00 0.00 0.00 66.16
December 380.26 24-DEC-22:00 2011.87 696.00 0.00 0.00 0.00 0.00 0.00 0.00 57.12
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 377.10   1508.90 696.00 0.00 0.00 0.00 0.00 0.00 0.00 2.42
Maximum of Months 2333.29   10562.33 5568.01 0.00 0.00 0.00 0.00 0.00 0.00 84.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 374.55 22-JAN-09:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 49.89
February 831.40 09-FEB-19:04 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 54.22
March 3100.61 27-MAR-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 54.78
April 3311.69 21-APR-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 0.00 14.99
May 3430.62 31-MAY-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 0.00 2.47
June 3549.12 22-JUN-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 0.78 0.00
July 3402.66 11-JUL-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 5.17 0.00
August 3565.09 10-AUG-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 0.00 0.37
September 3217.53 02-SEP-18:02 702.00 641.20 774.39 0.00 0.00 0.00 0.00 0.00 10.51
October 2866.30 13-OCT-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 35.76
November 374.18 08-NOV-16:04 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 72.19
December 630.66 24-DEC-09:04 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 0.00 37.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 374.18   378.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3565.09   970.20 665.78 1143.15 0.00 0.00 0.00 0.00 5.17 72.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 449.84 22-JAN-09:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 49.89
February 734.38 09-FEB-16:04 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 38.69
March 1455.39 28-MAR-15:03 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 49.16
April 2949.83 21-APR-18:01 970.20 665.70 903.35 0.00 0.00 0.00 0.00 0.00 14.96
May 3757.76 09-MAY-19:42 831.60 641.12 1042.94 0.00 0.00 0.00 0.00 0.00 21.54
June 3593.42 28-JUN-21:32 1080.00 429.56 553.07 0.00 0.00 0.00 0.00 0.00 13.63
July 3552.52 06-JUL-17:32 583.20 429.56 805.91 0.00 0.00 0.00 0.00 0.00 4.67
August 3180.35 02-AUG-21:51 1800.00 715.93 921.79 0.00 0.00 0.00 0.00 0.00 9.13
September 3048.75 02-SEP-19:41 936.00 854.83 1390.58 0.00 0.00 0.00 0.00 0.00 17.94
October 1428.78 05-OCT-15:03 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 18.25
November 398.68 04-NOV-08:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 54.98
December 600.45 24-DEC-09:04 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 37.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 398.68   378.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 4.67
Maximum of Months 3757.76   1800.00 854.83 1390.58 0.00 0.00 0.00 0.00 0.00 54.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 598.75 22-JAN-19:04 819.00 470.26 885.15 0.00 0.00 0.00 0.00 0.00 25.99
February 2102.16 15-FEB-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 28.63
March 2187.98 15-MAR-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 32.48
April 2238.11 20-APR-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 8.12
May 2286.80 10-MAY-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 3.37
June 2303.50 22-JUN-18:02 831.60 358.74 758.70 0.00 0.00 0.00 0.00 0.67 0.00
July 2320.49 23-JUL-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 2.33 0.00
August 2306.41 10-AUG-18:02 831.60 358.74 758.70 0.00 0.00 0.00 0.00 0.10 0.00
September 2117.98 07-SEP-18:01 970.20 418.53 885.15 0.00 0.00 0.00 0.00 0.00 7.42
October 2146.98 13-OCT-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 19.41
November 1996.45 08-NOV-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 37.59
December 590.80 24-DEC-19:04 819.00 470.26 885.15 0.00 0.00 0.00 0.00 0.00 23.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 590.80   324.00 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2320.49   970.20 470.26 885.15 0.00 0.00 0.00 0.00 2.33 37.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16995.61 11-JAN-22:40 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 288.96
February 16363.52 28-FEB-22:10 80966.30 4973.62 20243.71 0.00 0.00 0.00 0.00 0.00 255.17
March 17388.83 22-MAR-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 99.49
April 19132.88 21-APR-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 62.08
May 20953.76 31-MAY-21:52 242898.91 14777.55 60731.12 0.00 0.00 0.00 0.00 0.00 36.87
June 22498.82 21-JUN-21:03 161932.61 5968.35 40487.42 0.00 0.00 0.00 0.00 0.00 2.33
July 22776.91 11-JUL-21:10 26988.77 994.72 6747.90 0.00 0.00 0.00 0.00 0.00 9.30
August 21547.80 02-AUG-21:52 269887.68 16578.74 67479.03 0.00 0.00 0.00 0.00 0.00 19.63
September 19207.74 01-SEP-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 60.29
October 17931.77 06-OCT-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 70.59
November 16030.67 28-NOV-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 250.81
December 16708.36 14-DEC-24:00 26988.77 828.94 6747.90 0.00 0.00 0.00 0.00 0.00 259.24
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16030.67   26988.77 828.94 6747.90 0.00 0.00 0.00 0.00 0.00 2.33
Maximum of Months 22776.91   269887.68 16578.74 67479.03 0.00 0.00 0.00 0.00 0.00 288.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18391.62 11-JAN-22:30 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 287.69
February 18109.23 08-FEB-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 111.94
March 19404.36 22-MAR-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 99.50
April 20815.18 21-APR-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 62.08
May 22387.14 31-MAY-21:52 242898.91 14777.55 60731.12 0.00 0.00 0.00 0.00 0.00 36.87
June 23757.13 21-JUN-21:03 161932.61 5968.35 40487.42 0.00 0.00 0.00 0.00 0.00 2.33
July 24083.28 11-JUL-21:10 26988.77 994.72 6747.90 0.00 0.00 0.00 0.00 0.00 9.30
August 22846.66 02-AUG-21:20 26988.77 1642.02 6747.90 0.00 0.00 0.00 0.00 0.00 16.25
September 20940.96 01-SEP-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 60.29
October 19974.74 06-OCT-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 70.59
November 17036.98 28-NOV-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 251.58
December 17746.52 14-DEC-24:00 26988.77 828.94 6747.90 0.00 0.00 0.00 0.00 0.00 260.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17036.98   26988.77 828.94 6747.90 0.00 0.00 0.00 0.00 0.00 2.33
Maximum of Months 24083.28   242898.91 14777.55 60731.12 0.00 0.00 0.00 0.00 0.00 287.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23847.08 22-JAN-11:50 1601.14 654.50 29209.11 37488.05 0.00 0.00 0.00 0.00 122.19
February 25243.48 09-FEB-11:50 1067.42 545.42 29209.11 37488.05 0.00 0.00 0.00 0.00 105.33
March 27432.78 22-MAR-10:33 1601.14 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 85.40
April 29469.86 22-APR-10:50 800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 44.30
May 30028.59 12-MAY-10:33 1601.14 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 24.65
June 30522.26 29-JUN-10:45 1067.42 545.42 29209.11 37488.05 0.00 0.00 0.00 0.00 7.62
July 31130.64 22-JUL-10:40 2401.70 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 2.09
August 30286.61 10-AUG-10:33 1601.14 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 19.63
September 29051.07 10-SEP-10:33 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 0.00 38.19
October 27381.66 03-OCT-10:33 1601.14 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 72.85
November 23653.41 02-NOV-18:03 13075.94 6108.66 102231.89 104966.55 0.00 0.00 0.00 0.00 133.34
December 23917.98 24-DEC-11:50 800.57 327.25 14604.56 18744.03 0.00 0.00 0.00 0.00 86.61
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 23653.41   800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 2.09
Maximum of Months 31130.64   13075.94 6108.66 102231.89 104966.55 0.00 0.00 0.00 0.00 133.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 263.82 21-JAN-21:50 1863.12 859.38 0.00 0.00 0.00 0.00 0.00 0.00 91.21
February 2104.21 09-FEB-13:30 532.32 306.92 0.00 0.00 0.00 0.00 0.00 0.00 84.17
March 3159.56 22-MAR-17:13 3992.40 2209.83 0.00 0.00 0.00 0.00 0.00 0.00 63.79
April 4247.17 22-APR-10:33 2395.44 920.76 0.00 0.00 0.00 0.00 0.00 0.00 38.06
May 4747.29 14-MAY-10:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 0.00 22.58
June 5234.84 21-JUN-15:30 1330.80 306.92 0.00 0.00 0.00 0.00 0.00 4.26 0.00
July 5996.52 23-JUL-13:50 532.32 245.54 0.00 0.00 0.00 0.00 0.00 3.19 0.00
August 4836.56 02-AUG-17:15 2661.60 1473.22 0.00 0.00 0.00 0.00 0.00 0.00 2.47
September 4135.31 10-SEP-10:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 0.00 30.05
October 3380.26 03-OCT-10:33 1596.96 920.76 0.00 0.00 0.00 0.00 0.00 0.00 59.99
November 168.34 01-NOV-21:20 2395.44 736.61 0.00 0.00 0.00 0.00 0.00 0.00 117.35
December 345.50 24-DEC-22:50 2129.28 613.84 0.00 0.00 0.00 0.00 0.00 0.00 95.32
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 168.34   532.32 245.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5996.52   3992.40 2209.83 0.00 0.00 0.00 0.00 0.00 4.26 117.35



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.352094E+12 211533.29 26-JAN-20:10 0.137033E+13 1339773.95 12-JAN-19:19
February 0.312925E+12 211356.29 22-FEB-20:19 0.113873E+13 1181842.67 27-FEB-09:09
March 0.347039E+12 222240.04 22-MAR-19:10 0.890886E+12 1086225.60 01-MAR-00:20
April 0.390552E+12 260824.27 20-APR-20:40 0.419271E+12 402539.57 18-APR-17:00
May 0.419378E+12 277996.98 30-MAY-19:10 0.351312E+12 360679.01 27-MAY-17:00
June 0.439821E+12 341313.13 20-JUN-19:19 0.309050E+12 296298.18 24-JUN-20:00
July 0.464499E+12 338232.73 11-JUL-19:30 0.311426E+12 284690.51 04-JUL-21:00
August 0.437738E+12 331789.31 11-AUG-19:19 0.339784E+12 337645.13 30-AUG-19:40
September 0.385551E+12 261069.47 18-SEP-19:10 0.354309E+12 366705.82 05-SEP-17:00
October 0.389417E+12 259255.53 03-OCT-19:40 0.543013E+12 494473.99 30-OCT-18:10
November 0.338336E+12 211440.69 16-NOV-20:19 0.127708E+13 1189471.76 30-NOV-17:00
December 0.354182E+12 212430.65 06-DEC-20:40 0.151233E+13 1250979.35 15-DEC-17:10
             
Annual Sum or Average 0.463153E+13     0.881752E+13    
Minimum of Months 0.312925E+12 211356.29   0.309050E+12 284690.51  
Maximum of Months 0.464499E+12 341313.13   0.151233E+13 1339773.95  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.476883E+11 0.238751E+11 0.146779E+12 0.544798E+11 0.411857E+11 0.942819E+09 0.00 29344882.70 0.00 0.00 0.257713E+11 0.770634E+10 0.00
February 0.425471E+11 0.178631E+11 0.132565E+12 0.492074E+11 0.357527E+11 0.120189E+10 0.00 0.254488E+09 0.00 0.00 0.232773E+11 0.696354E+10 0.00
March 0.464000E+11 0.155861E+11 0.146789E+12 0.544811E+11 0.432693E+11 0.333037E+10 0.00 0.333107E+10 0.00 0.00 0.257713E+11 0.441749E+10 0.00
April 0.437536E+11 0.109722E+11 0.142011E+12 0.527208E+11 0.430900E+11 0.918330E+10 0.00 0.215652E+11 0.00 0.00 0.206562E+11 0.430423E+11 0.00
May 0.447206E+11 0.717053E+10 0.146789E+12 0.544790E+11 0.483561E+11 0.139332E+11 0.00 0.487784E+11 0.00 0.00 0.104637E+11 0.409864E+11 0.00
June 0.428909E+11 0.399472E+10 0.142058E+12 0.527221E+11 0.502424E+11 0.150434E+11 0.00 0.876661E+11 0.00 0.00 0.358614E+10 0.380009E+11 0.00
July 0.445054E+11 0.555266E+10 0.146742E+12 0.544770E+11 0.511049E+11 0.157338E+11 0.00 0.990996E+11 0.00 0.00 0.460646E+10 0.389412E+11 0.00
August 0.452030E+11 0.958067E+10 0.146800E+12 0.544803E+11 0.489453E+11 0.146924E+11 0.00 0.699217E+11 0.00 0.00 0.451427E+10 0.398606E+11 0.00
September 0.446546E+11 0.133224E+11 0.142022E+12 0.527215E+11 0.426805E+11 0.100446E+11 0.00 0.187577E+11 0.00 0.00 0.165492E+11 0.412041E+11 0.00
October 0.469032E+11 0.179696E+11 0.146768E+12 0.544794E+11 0.418370E+11 0.354997E+10 0.00 0.353312E+10 0.00 0.00 0.240966E+11 0.465941E+11 0.00
November 0.459732E+11 0.215515E+11 0.142074E+12 0.527228E+11 0.391989E+11 0.857320E+09 0.00 46433127.00 0.00 0.00 0.249400E+11 0.745066E+10 0.00
December 0.478577E+11 0.255662E+11 0.146742E+12 0.544790E+11 0.412917E+11 0.110422E+10 0.00 18810348.00 0.00 0.00 0.257713E+11 0.771442E+10 0.00
                           
Annual Sum or Average 0.543097E+12 0.173005E+12 0.172814E+13 0.641450E+12 0.526955E+12 0.896173E+11 0.00 0.353002E+12 0.00 0.00 0.210004E+12 0.322882E+12 0.00
Minimum of Months 0.425471E+11 0.399472E+10 0.132565E+12 0.492074E+11 0.357527E+11 0.857320E+09 0.00 18810348.00 0.00 0.00 0.358614E+10 0.441749E+10 0.00
Maximum of Months 0.478577E+11 0.255662E+11 0.146800E+12 0.544811E+11 0.511049E+11 0.157338E+11 0.00 0.990996E+11 0.00 0.00 0.257713E+11 0.465941E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.964005E+12 0.00 0.254407E+12 0.00 0.00
February 0.137204E+12 0.00 0.771380E+12 0.00 0.230143E+12 0.00 0.00
March 0.152024E+12 0.00 0.481318E+12 0.00 0.257544E+12 0.00 0.00
April 0.146956E+12 0.00 0.134889E+12 0.00 0.137426E+12 0.00 0.00
May 0.151978E+12 0.00 0.662549E+11 0.00 0.133078E+12 0.00 0.00
June 0.147114E+12 0.00 0.481338E+11 0.00 0.113802E+12 0.00 0.00
July 0.151820E+12 0.00 0.492185E+11 0.00 0.110387E+12 0.00 0.00
August 0.152039E+12 0.00 0.756532E+11 0.00 0.112092E+12 0.00 0.00
September 0.146971E+12 0.00 0.860489E+11 0.00 0.121289E+12 0.00 0.00
October 0.151903E+12 0.00 0.249838E+12 0.00 0.141271E+12 0.00 0.00
November 0.147091E+12 0.00 0.889984E+12 0.00 0.240008E+12 0.00 0.00
December 0.151820E+12 0.00 0.110752E+13 0.00 0.252988E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.492424E+13 0.00 0.210444E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.481338E+11 0.00 0.110387E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.110752E+13 0.00 0.257544E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 45424.10 02-JAN-20:10 11096.45 01-JAN-00:10 88863.15 02-JAN-07:10 39153.57 02-JAN-07:19 21853.94 30-JAN-19:10 2002.96 12-JAN-09:20 0.00 01-JAN-00:10
February 45424.10 01-FEB-20:10 11096.45 01-FEB-00:10 88863.15 01-FEB-07:10 39153.57 01-FEB-07:19 21621.64 01-FEB-19:10 3943.62 15-FEB-16:10 0.00 01-FEB-00:10
March 45424.10 01-MAR-20:10 11096.45 01-MAR-00:10 88863.15 01-MAR-07:10 39153.57 01-MAR-07:19 22576.02 22-MAR-20:19 5487.99 29-MAR-15:09 0.00 01-MAR-00:10
April 45424.10 03-APR-19:40 11096.45 01-APR-00:10 88863.15 03-APR-06:10 39153.57 03-APR-06:19 28736.51 21-APR-21:10 6527.89 22-APR-16:10 0.00 01-APR-00:10
May 44407.70 02-MAY-19:00 11096.45 01-MAY-00:10 88863.15 01-MAY-06:10 39151.64 16-MAY-06:19 31741.99 10-MAY-21:40 6918.30 31-MAY-15:09 0.00 01-MAY-00:10
June 43938.34 02-JUN-19:00 11096.45 01-JUN-00:10 88863.15 01-JUN-06:10 39151.62 27-JUN-06:19 32603.36 21-JUN-20:00 7308.15 21-JUN-19:00 0.00 01-JUN-00:10
July 43629.83 26-JUL-19:00 11096.45 01-JUL-00:10 88863.15 03-JUL-06:10 39151.89 25-JUL-06:19 33044.04 12-JUL-21:00 7361.44 20-JUL-18:49 0.00 01-JUL-00:10
August 45424.10 29-AUG-19:30 11096.45 01-AUG-00:10 88863.15 01-AUG-06:10 39151.88 29-AUG-06:19 32347.66 10-AUG-21:00 7282.36 11-AUG-15:20 0.00 01-AUG-00:10
September 45424.10 01-SEP-19:30 11096.45 01-SEP-00:10 88863.15 01-SEP-06:10 39153.57 13-SEP-06:19 27658.35 08-SEP-21:10 6500.97 02-SEP-15:09 0.00 01-SEP-00:10
October 45424.10 02-OCT-19:10 11096.45 01-OCT-00:10 88863.15 02-OCT-06:10 39153.57 02-OCT-06:19 24358.78 03-OCT-21:10 5639.56 03-OCT-15:09 0.00 01-OCT-00:10
November 45424.10 01-NOV-19:10 11096.45 01-NOV-00:10 88863.15 01-NOV-06:10 39153.57 01-NOV-06:19 21798.44 15-NOV-19:10 3636.67 08-NOV-16:10 0.00 01-NOV-00:10
December 45424.10 01-DEC-20:10 11096.45 01-DEC-00:10 88863.15 01-DEC-07:10 39153.57 01-DEC-07:19 21900.62 06-DEC-19:10 1866.76 15-DEC-10:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 43629.83   11096.45   88863.15   39151.62   21621.64   1866.76   0.00  
Maximum of Months 45424.10   11096.45   88863.15   39153.57   33044.04   7361.44   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 1847.21 22-JAN-19:10 0.00 0.00 9938.94 01-JAN-00:10 4739.88 12-JAN-19:00 0.00
February 4344.38 15-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4739.97 27-FEB-07:30 0.00
March 21813.24 29-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:10 31259.53 31-MAR-23:10 0.00
April 44427.54 22-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 34464.21 26-APR-18:10 0.00
May 73981.27 31-MAY-15:09 0.00 0.00 9938.94 01-MAY-00:10 35580.17 31-MAY-18:00 0.00
June 101658.74 20-JUN-18:19 0.00 0.00 9938.94 01-JUN-02:49 36280.77 28-JUN-18:19 0.00
July 115436.70 29-JUL-15:20 0.00 0.00 9938.94 05-JUL-01:39 37031.83 28-JUL-18:19 0.00
August 95381.85 11-AUG-18:10 0.00 0.00 9938.94 02-AUG-16:40 37460.01 30-AUG-18:10 0.00
September 47586.18 02-SEP-15:09 0.00 0.00 9938.94 01-SEP-00:20 37466.90 05-SEP-18:49 0.00
October 24844.42 03-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 36467.29 02-OCT-18:00 0.00
November 1903.76 08-NOV-16:10 0.00 0.00 9938.94 01-NOV-00:10 4739.75 28-NOV-07:10 0.00
December 2282.25 24-DEC-19:10 0.00 0.00 9938.94 01-DEC-00:20 4740.06 15-DEC-07:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 1847.21   0.00 0.00 9938.94   4739.75   0.00
Maximum of Months 115436.70   0.00 0.00 9938.94   37466.90   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 211533.29 26-JAN-20:10 45424.10 87982.85 11096.45 31569.36 19681.97 96.99 0.00 0.00 0.00
February 211356.29 22-FEB-20:19 45424.10 87982.85 11096.45 31573.56 19139.72 806.88 0.00 0.00 0.00
March 222240.04 22-MAR-19:10 45424.10 87982.85 11096.45 31569.27 21988.25 4464.85 0.00 5520.85 0.00
April 260824.27 20-APR-20:40 40391.24 88373.09 11096.45 24002.42 25880.08 5858.85 0.00 20118.77 0.00
May 277996.98 30-MAY-19:10 41184.17 87982.85 0.00 31566.16 24727.11 6191.25 0.00 50353.70 0.00
June 341313.13 20-JUN-19:19 41114.58 87982.85 0.00 31569.86 29846.68 7219.52 0.00 96934.45 0.00
July 338232.73 11-JUL-19:30 41231.65 87982.85 0.00 31570.02 30957.40 7179.68 0.00 92395.45 0.00
August 331789.31 11-AUG-19:19 41914.73 87982.85 0.00 31570.37 28567.87 7162.39 0.00 86975.26 0.00
September 261069.47 18-SEP-19:10 45424.10 87982.85 11096.45 31569.36 24487.22 5563.97 0.00 15546.64 0.00
October 259255.53 03-OCT-19:40 45424.10 87982.85 11096.45 31573.56 22395.86 4833.52 0.00 8898.48 0.00
November 211440.69 16-NOV-20:19 45424.10 87982.85 11096.45 31573.56 19653.59 99.43 0.00 0.00 0.00
December 212430.65 06-DEC-20:40 45424.10 87982.85 11096.45 31573.56 19943.32 1073.77 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 211356.29   40391.24 87982.85 0.00 24002.42 19139.72 96.99 0.00 0.00 0.00
Maximum of Months 341313.13   45424.10 88373.09 11096.45 31573.56 30957.40 7219.52 0.00 96934.45 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 1123356.46 12-JAN-09:09 0.00 200852.03 18-JAN-22:30 0.00
February 104248.32 01-FEB-18:10 0.00 1038561.70 27-FEB-05:19 0.00 200348.60 21-FEB-22:40 0.00
March 104248.32 01-MAR-18:10 0.00 904264.70 01-MAR-04:00 0.00 203106.66 21-MAR-21:30 0.00
April 104248.32 01-APR-17:10 0.00 280515.16 03-APR-08:09 0.00 147434.04 13-APR-18:10 0.00
May 104248.32 01-MAY-17:10 0.00 163874.65 26-MAY-10:00 0.00 137112.53 09-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 145943.93 01-JUN-06:19 0.00 115804.54 01-JUN-17:19 0.00
July 104248.32 01-JUL-17:10 0.00 163251.98 05-JUL-06:00 0.00 105673.14 01-JUL-17:10 0.00
August 104248.32 01-AUG-17:10 0.00 162338.81 22-AUG-07:30 0.00 106749.99 01-AUG-16:00 0.00
September 104248.32 01-SEP-17:10 0.00 176111.95 21-SEP-09:09 0.00 126777.29 26-SEP-20:00 0.00
October 104248.32 02-OCT-17:10 0.00 308500.56 27-OCT-08:09 0.00 145498.58 20-OCT-17:00 0.00
November 104248.32 01-NOV-17:10 0.00 992464.22 29-NOV-09:09 0.00 197783.63 30-NOV-22:30 0.00
December 104248.32 01-DEC-18:10 0.00 1070016.27 15-DEC-09:09 0.00 200601.75 08-DEC-22:40 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 145943.93   0.00 105673.14   0.00
Maximum of Months 104248.32   0.00 1123356.46   0.00 203106.66   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.44 0.50 20.44 0.00 20.44 0.00 20.44
February 0.33 20.44 0.33 20.44 0.00 20.44 0.00 20.44
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 20.44 0.83 20.44 0.00 20.44 0.00 20.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.44 0.50 20.44 0.00 20.44 0.00 20.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 51.00 18.91 51.00 18.91 0.00 18.91 0.00 18.91
February 6.50 19.85 6.50 19.85 0.00 19.85 0.00 19.85
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 14.67 19.79 14.67 19.79 0.00 19.79 0.00 19.79
                 
Annual Sum or Average 72.17 19.17 72.17 19.17 0.00 19.17 0.00 19.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51.00 19.85 51.00 19.85 0.00 19.85 0.00 19.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.00 19.77 12.00 19.77 0.00 19.77 0.00 19.77
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12.00 19.77 12.00 19.77 0.00 19.77 0.00 19.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.00 19.77 12.00 19.77 0.00 19.77 0.00 19.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 16.41 4.83 16.41 0.00 16.41 0.00 16.41
February 0.17 16.80 0.17 16.80 0.00 16.80 0.00 16.80
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.51 0.17 19.51 0.00 19.51 0.00 19.51
                 
Annual Sum or Average 5.17 16.52 5.17 16.52 0.00 16.52 0.00 16.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.83 19.51 4.83 19.51 0.00 19.51 0.00 19.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 36.33 19.06 36.33 19.06 0.00 19.06 0.00 19.06
February 2.67 20.10 2.67 20.10 0.00 20.10 0.00 20.10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.39 0.50 20.39 0.00 20.39 0.00 20.39
December 9.00 19.36 9.00 19.36 0.00 19.36 0.00 19.36
                 
Annual Sum or Average 48.50 19.18 48.50 19.18 0.00 19.18 0.00 19.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36.33 20.39 36.33 20.39 0.00 20.39 0.00 20.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 18.17 19.67 18.17 19.67 0.00 19.67 0.00 19.67
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 5.50 20.18 5.50 20.18 0.00 20.18 0.00 20.18
                 
Annual Sum or Average 23.67 19.79 23.67 19.79 0.00 19.79 0.00 19.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18.17 20.18 18.17 20.18 0.00 20.18 0.00 20.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
June 0.00 0.00 0.00 0.00 1.33 21.77 1.33 21.77
July 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
August 0.00 0.00 0.00 0.00 1.00 21.89 1.00 21.89
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 21.80 3.17 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.89 1.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 21.97 1.67 21.97
June 0.00 0.00 0.00 0.00 4.83 22.05 4.83 22.05
July 0.00 0.00 0.00 0.00 3.83 21.94 3.83 21.94
August 0.00 0.00 0.00 0.00 0.83 21.90 0.83 21.90
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   11.17 21.99 11.17 21.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 22.05 4.83 22.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 20.44 2.00 20.44 0.00 20.44 0.00 20.44
February 0.33 20.49 0.33 20.49 0.00 20.49 0.00 20.49
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.00 21.76 4.00 21.76
June 0.00 0.00 0.00 0.00 14.83 21.90 14.83 21.90
July 0.00 0.00 0.00 0.00 15.50 21.89 15.50 21.89
August 0.00 0.00 0.00 0.00 6.67 21.81 6.67 21.81
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.44 0.67 20.44 0.00 20.44 0.00 20.44
December 1.83 20.48 1.83 20.48 0.00 20.48 0.00 20.48
                 
Annual Sum or Average 4.83 20.46 4.83 20.46 41.00 21.60 41.00 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.49 2.00 20.49 15.50 21.90 15.50 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.91 0.17 21.91
May 0.00 0.00 0.00 0.00 5.00 21.91 5.00 21.91
June 0.00 0.00 0.00 0.00 2.67 21.90 2.67 21.90
July 0.00 0.00 0.00 0.00 2.50 21.89 2.50 21.89
August 0.00 0.00 0.00 0.00 1.67 21.83 1.67 21.83
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.00 21.89 12.00 21.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 21.91 5.00 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.89 0.17 21.89
May 0.00 0.00 0.00 0.00 7.17 21.96 7.17 21.96
June 0.00 0.00 0.00 0.00 10.83 22.06 10.83 22.06
July 0.00 0.00 0.00 0.00 11.00 22.31 11.00 22.31
August 0.00 0.00 0.00 0.00 2.83 21.87 2.83 21.87
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   32.00 22.11 32.00 22.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.00 22.31 11.00 22.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 20.41 3.50 20.41 0.00 20.41 0.00 20.41
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.50 20.41 3.50 20.41 0.00 20.41 0.00 20.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 20.41 3.50 20.41 0.00 20.41 0.00 20.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.50 21.81 0.50 21.81
June 0.00 0.00 0.00 0.00 1.50 21.81 1.50 21.81
July 0.00 0.00 0.00 0.00 0.67 21.71 0.67 21.71
August 0.00 0.00 0.00 0.00 1.00 21.83 1.00 21.83
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.67 21.79 3.67 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.83 1.50 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.17 22.09 2.17 22.09
June 0.00 0.00 0.00 0.00 6.00 22.21 6.00 22.21
July 0.00 0.00 0.00 0.00 4.33 22.06 4.33 22.06
August 0.00 0.00 0.00 0.00 1.33 21.98 1.33 21.98
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   13.83 22.12 13.83 22.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 22.21 6.00 22.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 21.90 1.00 21.90
May 0.00 0.00 0.00 0.00 0.83 21.81 0.83 21.81
June 0.00 0.00 0.00 0.00 0.67 21.72 0.67 21.72
July 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
August 0.00 0.00 0.00 0.00 1.17 21.85 1.17 21.85
September 0.00 0.00 0.00 0.00 1.33 21.82 1.33 21.82
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.50 21.82 5.50 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.90 1.33 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 20.20 1.00 20.20 0.00 20.20 0.00 20.20
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.00 20.20 1.00 20.20 0.00 20.20 0.00 20.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.20 1.00 20.20 0.00 20.20 0.00 20.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 20.36 0.67 20.36 0.00 20.36 0.00 20.36
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.67 20.36 0.67 20.36 0.00 20.36 0.00 20.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 20.36 0.67 20.36 0.00 20.36 0.00 20.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 18.32 0.50 18.32 0.00 18.32 0.00 18.32
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 18.32 0.50 18.32 0.00 18.32 0.00 18.32
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 18.32 0.50 18.32 0.00 18.32 0.00 18.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 20.40 1.33 20.40 0.00 20.40 0.00 20.40
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.40 1.33 20.40 0.00 20.40 0.00 20.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 20.40 1.33 20.40 0.00 20.40 0.00 20.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.94 89.50 21.84 89.50 21.76
February 672.00 21.36 233.00 21.27 233.00 21.22
March 744.00 21.35 208.00 21.28 208.00 21.23
April 720.00 21.55 26.17 21.53 26.17 21.52
May 744.00 21.65 0.00 21.65 0.00 21.65
June 720.00 21.96 0.00 21.96 0.00 21.96
July 744.00 22.63 0.00 22.63 0.00 22.63
August 680.17 23.35 0.67 23.35 0.00 23.35
September 669.67 23.68 0.00 23.68 0.00 23.68
October 742.67 23.72 0.00 23.72 0.00 23.72
November 720.00 23.24 17.50 23.19 17.50 23.14
December 744.00 22.21 38.17 22.16 38.17 22.10
             
Annual Sum or Average 8644.50 22.38 613.00 22.29 612.33 22.21
Minimum of Months 669.67 21.35 0.00 21.27 0.00 21.22
Maximum of Months 744.00 23.72 233.00 23.72 233.00 23.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.86 740.17 20.86 740.17 20.86
February 672.00 21.01 612.33 21.00 612.33 21.00
March 720.67 21.16 493.17 21.09 493.17 21.07
April 629.83 21.31 138.17 21.39 103.17 21.35
May 657.50 21.37 40.33 21.52 0.00 21.52
June 609.33 21.54 56.83 21.73 0.00 21.73
July 610.17 21.45 87.50 21.73 0.00 21.73
August 633.17 21.37 77.00 21.64 0.00 21.64
September 677.17 21.15 33.00 21.23 11.50 21.23
October 733.17 21.05 375.00 21.04 372.33 21.03
November 720.00 21.00 708.50 21.00 708.50 21.00
December 744.00 20.98 744.00 20.98 744.00 20.98
             
Annual Sum or Average 8151.00 21.17 4106.00 21.18 3785.17 21.13
Minimum of Months 609.33 20.86 33.00 20.86 0.00 20.86
Maximum of Months 744.00 21.54 744.00 21.73 744.00 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.08 454.50 21.04 454.50 21.01
February 672.00 21.22 305.50 21.16 305.50 21.12
March 744.00 21.57 116.33 21.49 116.33 21.44
April 720.00 22.53 0.00 22.53 0.00 22.53
May 739.17 22.94 0.00 22.94 0.00 22.94
June 566.33 23.09 16.00 23.11 0.00 23.11
July 494.33 22.98 79.83 23.11 0.00 23.11
August 589.67 22.99 28.17 23.03 0.00 23.03
September 718.67 22.55 0.00 22.55 0.00 22.55
October 744.00 21.81 31.00 21.78 31.00 21.75
November 720.00 21.14 412.67 21.09 412.67 21.07
December 744.00 21.06 573.67 21.03 573.67 21.03
             
Annual Sum or Average 8196.17 22.02 2017.67 21.85 1893.67 21.72
Minimum of Months 494.33 21.06 0.00 21.03 0.00 21.01
Maximum of Months 744.00 23.09 573.67 23.11 573.67 23.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 721.17 21.00 721.17 21.00
February 672.00 21.00 589.00 21.00 589.00 21.00
March 744.00 21.04 536.83 21.02 536.83 21.02
April 720.00 21.62 126.17 21.53 126.17 21.46
May 744.00 22.56 0.00 22.56 0.00 22.56
June 709.50 23.20 0.00 23.20 0.00 23.20
July 671.17 23.23 0.00 23.23 0.00 23.23
August 727.67 23.05 0.00 23.05 0.00 23.05
September 720.00 22.12 0.00 22.12 0.00 22.12
October 744.00 21.25 224.67 21.19 224.67 21.15
November 720.00 21.00 717.50 21.00 717.50 21.00
December 744.00 21.00 724.67 21.00 724.67 21.00
             
Annual Sum or Average 8660.33 21.83 3640.00 21.58 3640.00 21.45
Minimum of Months 671.17 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.23 724.67 23.23 724.67 23.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 744.00 21.00 744.00 21.00
February 672.00 21.00 641.00 21.00 641.00 21.00
March 744.00 21.00 619.17 21.00 619.17 21.00
April 720.00 21.38 184.83 21.30 184.83 21.25
May 744.00 22.30 0.00 22.30 0.00 22.30
June 718.33 23.01 0.00 23.01 0.00 23.01
July 738.00 23.08 0.00 23.08 0.00 23.08
August 744.00 22.81 0.00 22.81 0.00 22.81
September 720.00 21.77 0.00 21.77 0.00 21.77
October 744.00 21.08 293.67 21.06 293.67 21.05
November 720.00 21.00 720.00 21.00 720.00 21.00
December 744.00 21.00 744.00 21.00 744.00 21.00
             
Annual Sum or Average 8752.33 21.71 3946.67 21.49 3946.67 21.37
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.08 744.00 23.08 744.00 23.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 396.50 21.77 302.50 22.46 125.83 22.52
February 338.50 22.04 273.33 22.78 106.00 22.92
March 278.67 22.52 363.50 23.20 128.50 23.34
April 232.17 22.93 461.17 23.36 144.17 23.47
May 259.00 23.28 586.83 23.35 193.33 23.47
June 295.67 23.74 633.33 23.40 269.17 23.54
July 305.00 23.87 675.50 23.40 292.00 23.54
August 303.83 23.72 653.00 23.40 274.17 23.53
September 263.67 23.31 597.00 23.33 201.17 23.46
October 242.67 22.84 462.83 23.33 142.17 23.44
November 350.83 22.09 283.67 22.87 106.17 23.03
December 446.17 21.98 285.33 22.68 113.33 22.84
             
Annual Sum or Average 3712.67 22.75 5578.00 23.16 2096.00 23.30
Minimum of Months 232.17 21.77 273.33 22.46 106.00 22.52
Maximum of Months 446.17 23.87 675.50 23.40 292.00 23.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.91 679.50 20.90 679.50 20.90
February 672.00 21.07 429.83 21.04 429.83 21.03
March 695.33 21.38 153.83 21.36 139.67 21.31
April 593.83 22.03 81.33 22.23 7.50 22.22
May 597.50 22.29 68.17 22.45 0.00 22.45
June 404.00 22.33 141.67 22.65 0.00 22.65
July 351.33 22.11 248.50 22.67 3.50 22.67
August 466.50 22.15 175.00 22.55 3.17 22.56
September 653.33 21.85 40.50 21.96 0.00 21.96
October 727.33 21.33 125.67 21.31 118.50 21.27
November 720.00 21.01 658.33 21.01 658.33 21.01
December 744.00 20.98 725.17 20.98 725.17 20.98
             
Annual Sum or Average 7369.17 21.53 3527.50 21.53 2765.17 21.42
Minimum of Months 351.33 20.91 40.50 20.90 0.00 20.90
Maximum of Months 744.00 22.33 725.17 22.67 725.17 22.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.31 332.67 21.19 332.67 21.12
February 672.00 21.49 199.33 21.38 199.33 21.31
March 744.00 22.00 32.83 21.96 32.83 21.92
April 681.83 22.85 0.00 22.85 0.00 22.85
May 596.17 23.08 0.00 23.08 0.00 23.08
June 292.00 22.95 96.50 23.19 0.00 23.19
July 212.33 22.84 300.17 23.45 11.33 23.46
August 300.83 22.88 191.17 23.28 5.83 23.29
September 631.83 22.77 0.00 22.77 0.00 22.77
October 743.50 22.18 0.17 22.18 0.17 22.18
November 720.00 21.39 278.50 21.28 278.50 21.22
December 744.00 21.23 420.67 21.15 420.67 21.11
             
Annual Sum or Average 7082.50 22.10 1852.00 22.06 1281.33 21.93
Minimum of Months 212.33 21.23 0.00 21.15 0.00 21.11
Maximum of Months 744.00 23.08 420.67 23.45 420.67 23.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.48 744.00 20.48 744.00 20.48
February 672.00 20.56 664.33 20.56 664.33 20.56
March 744.00 20.91 577.33 20.85 577.33 20.82
April 709.00 21.44 115.33 21.37 115.33 21.31
May 720.50 21.62 0.00 21.62 0.00 21.62
June 638.50 21.51 6.33 21.53 0.00 21.53
July 644.50 21.47 7.33 21.49 0.00 21.49
August 678.83 21.52 1.67 21.53 0.00 21.53
September 716.00 21.38 29.17 21.35 29.17 21.32
October 744.00 20.82 469.00 20.73 469.00 20.70
November 720.00 20.49 720.00 20.49 720.00 20.49
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 8475.33 21.04 4078.50 20.89 4063.17 20.81
Minimum of Months 638.50 20.48 0.00 20.48 0.00 20.48
Maximum of Months 744.00 21.62 744.00 21.62 744.00 21.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.48 744.00 20.48 744.00 20.48
February 672.00 20.49 672.00 20.49 672.00 20.49
March 744.00 20.60 696.67 20.58 696.67 20.57
April 719.00 21.15 230.67 21.04 230.67 20.97
May 686.67 21.70 38.17 21.94 2.33 21.96
June 586.50 22.16 107.67 22.81 31.83 23.04
July 572.00 21.86 110.33 22.42 8.00 22.48
August 658.17 21.86 60.50 22.19 6.83 22.25
September 717.17 21.20 77.00 21.13 76.00 21.07
October 744.00 20.65 573.50 20.59 573.50 20.57
November 720.00 20.48 720.00 20.48 720.00 20.48
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 8307.50 21.05 4774.50 20.98 4505.83 20.88
Minimum of Months 572.00 20.48 38.17 20.48 2.33 20.48
Maximum of Months 744.00 22.16 744.00 22.81 744.00 23.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.65 731.83 20.65 731.83 20.65
February 672.00 20.72 599.33 20.70 599.33 20.69
March 744.00 20.89 553.50 20.86 553.50 20.84
April 720.00 21.23 131.67 21.18 131.67 21.15
May 744.00 21.69 0.00 21.69 0.00 21.69
June 710.00 22.09 0.67 22.09 0.00 22.09
July 713.67 22.05 4.50 22.06 0.00 22.06
August 738.67 21.88 0.00 21.88 0.00 21.88
September 720.00 21.33 2.67 21.33 2.67 21.33
October 744.00 21.00 287.83 20.92 287.83 20.88
November 720.00 20.66 720.00 20.66 720.00 20.66
December 744.00 20.63 724.83 20.62 724.83 20.62
             
Annual Sum or Average 8714.33 21.24 3756.83 21.07 3751.67 20.98
Minimum of Months 672.00 20.63 0.00 20.62 0.00 20.62
Maximum of Months 744.00 22.09 731.83 22.09 731.83 22.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.49 744.00 20.49 744.00 20.49
February 672.00 20.61 645.67 20.60 645.67 20.60
March 744.00 21.18 452.33 21.07 452.33 21.02
April 706.33 21.55 104.33 21.48 104.33 21.43
May 657.67 21.53 0.33 21.53 0.00 21.53
June 585.33 21.38 16.67 21.43 0.00 21.43
July 605.17 21.38 29.50 21.47 0.00 21.47
August 652.83 21.50 13.17 21.54 0.00 21.54
September 707.33 21.47 13.00 21.46 13.00 21.44
October 744.00 20.94 412.00 20.83 412.00 20.79
November 720.00 20.49 720.00 20.49 720.00 20.49
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 8282.67 21.06 3895.00 20.92 3835.33 20.84
Minimum of Months 585.33 20.48 0.33 20.48 0.00 20.48
Maximum of Months 744.00 21.55 744.00 21.54 744.00 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.48 744.00 20.48 744.00 20.48
February 672.00 20.51 670.33 20.51 670.33 20.51
March 744.00 20.83 587.67 20.78 587.67 20.76
April 720.00 21.39 193.17 21.28 193.17 21.22
May 707.17 21.87 1.33 21.87 0.00 21.87
June 518.17 21.79 43.83 22.04 2.33 22.06
July 503.00 21.77 113.67 22.36 11.83 22.46
August 647.50 21.87 17.83 21.95 0.00 21.95
September 720.00 21.40 36.50 21.37 36.50 21.34
October 744.00 20.76 503.67 20.69 503.67 20.66
November 720.00 20.48 720.00 20.48 720.00 20.48
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 8183.83 21.09 4376.00 20.97 4213.50 20.87
Minimum of Months 503.00 20.48 1.33 20.48 0.00 20.48
Maximum of Months 744.00 21.87 744.00 22.36 744.00 22.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.99 724.33 20.99 724.33 20.99
February 672.00 21.00 618.33 21.00 618.33 21.00
March 744.00 21.01 567.17 21.01 567.17 21.01
April 720.00 21.55 116.33 21.48 116.33 21.42
May 744.00 22.54 0.00 22.54 0.00 22.54
June 718.00 23.22 0.00 23.22 0.00 23.22
July 715.17 23.15 0.00 23.15 0.00 23.15
August 744.00 22.76 0.00 22.76 0.00 22.76
September 720.00 21.54 0.00 21.54 0.00 21.54
October 744.00 21.01 287.33 21.01 287.33 21.01
November 720.00 21.00 720.00 21.00 720.00 21.00
December 744.00 21.00 736.50 21.00 736.50 21.00
             
Annual Sum or Average 8729.17 21.73 3770.00 21.51 3770.00 21.39
Minimum of Months 672.00 20.99 0.00 20.99 0.00 20.99
Maximum of Months 744.00 23.22 736.50 23.22 736.50 23.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.47 744.00 20.47 744.00 20.47
February 672.00 20.49 672.00 20.49 672.00 20.49
March 744.00 20.75 656.17 20.71 656.17 20.69
April 706.83 21.34 209.00 21.22 209.00 21.15
May 713.50 21.57 4.17 21.57 3.33 21.57
June 625.67 21.47 13.00 21.50 0.00 21.50
July 634.00 21.42 14.50 21.47 0.00 21.47
August 672.50 21.48 8.33 21.50 0.00 21.50
September 714.83 21.28 111.17 21.20 111.17 21.14
October 744.00 20.69 595.17 20.64 595.17 20.62
November 720.00 20.47 720.00 20.47 720.00 20.47
December 744.00 20.47 744.00 20.47 744.00 20.47
             
Annual Sum or Average 8435.33 20.98 4491.50 20.83 4454.83 20.76
Minimum of Months 625.67 20.47 4.17 20.47 0.00 20.47
Maximum of Months 744.00 21.57 744.00 21.57 744.00 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.47 744.00 20.47 744.00 20.47
February 672.00 20.47 672.00 20.47 672.00 20.47
March 744.00 20.53 724.83 20.52 724.83 20.52
April 718.17 21.04 328.83 20.92 328.83 20.86
May 688.50 21.71 47.00 21.99 13.67 22.05
June 585.33 22.31 117.67 23.04 48.50 23.38
July 559.17 21.89 118.17 22.54 17.67 22.67
August 656.33 21.89 71.00 22.28 20.33 22.41
September 716.50 21.07 170.33 20.97 169.17 20.90
October 744.00 20.56 677.17 20.54 677.17 20.53
November 720.00 20.47 720.00 20.47 720.00 20.47
December 744.00 20.47 744.00 20.47 744.00 20.47
             
Annual Sum or Average 8292.00 21.03 5135.00 20.97 4880.17 20.88
Minimum of Months 559.17 20.47 47.00 20.47 13.67 20.47
Maximum of Months 744.00 22.31 744.00 23.04 744.00 23.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.53 738.50 20.53 738.50 20.53
February 672.00 20.92 579.33 20.83 579.33 20.80
March 720.50 21.24 422.50 21.12 422.50 21.07
April 650.33 21.42 86.67 21.41 75.00 21.37
May 660.17 21.48 14.17 21.52 0.00 21.52
June 615.67 21.44 31.00 21.53 0.00 21.53
July 630.50 21.42 40.17 21.54 0.00 21.54
August 644.83 21.45 43.83 21.57 0.00 21.57
September 673.83 21.42 20.00 21.44 8.83 21.43
October 730.33 21.08 350.50 20.98 348.17 20.92
November 720.00 20.60 703.50 20.58 703.50 20.58
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 8206.17 21.10 3774.17 20.99 3619.83 20.91
Minimum of Months 615.67 20.48 14.17 20.48 0.00 20.48
Maximum of Months 744.00 21.48 744.00 21.57 744.00 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.54 120.17 22.32 120.17 22.16
February 659.33 22.60 80.17 22.43 80.17 22.29
March 676.00 23.05 25.83 22.97 25.83 22.90
April 384.33 23.35 0.00 23.35 0.00 23.35
May 82.00 23.35 56.67 23.61 0.00 23.61
June 0.83 23.24 630.67 23.98 0.00 23.98
July 8.83 23.99 721.00 23.97 8.83 23.97
August 25.17 23.44 579.50 23.95 8.00 23.95
September 205.17 23.18 139.50 23.51 0.00 23.51
October 526.67 23.20 0.00 23.20 0.00 23.20
November 720.00 22.58 93.50 22.40 93.50 22.25
December 744.00 22.36 144.50 22.14 144.50 21.98
             
Annual Sum or Average 4776.33 22.78 2591.50 23.02 481.00 22.90
Minimum of Months 0.83 22.36 0.00 22.14 0.00 21.98
Maximum of Months 744.00 23.99 721.00 23.98 144.50 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 699.33 22.72 67.33 22.57 67.33 22.44
February 594.67 22.73 43.00 22.61 43.00 22.51
March 564.00 23.17 10.83 23.13 10.83 23.09
April 234.17 23.44 9.33 23.47 0.00 23.47
May 1.50 23.25 220.50 23.99 0.00 23.99
June 0.00 0.00 694.33 23.99 0.00 23.99
July 4.50 23.99 742.67 23.98 4.50 23.98
August 17.33 23.57 674.17 23.96 6.17 23.96
September 63.83 23.26 313.67 23.87 0.00 23.87
October 373.67 23.31 29.83 23.36 0.00 23.36
November 702.50 22.82 61.33 22.67 61.33 22.55
December 729.50 22.58 84.00 22.42 84.00 22.29
             
Annual Sum or Average 3985.00 22.89 2951.00 23.24 277.17 23.16
Minimum of Months 0.00 0.00 9.33 22.42 0.00 22.29
Maximum of Months 729.50 23.99 742.67 23.99 84.00 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 472.00 23.03 522.50 23.45 298.83 23.54
February 454.67 23.25 490.67 23.58 318.17 23.67
March 554.67 23.53 569.00 23.75 438.50 23.81
April 507.00 23.88 610.67 23.90 475.50 23.93
May 542.83 23.99 721.67 23.92 542.83 23.94
June 543.17 23.99 720.00 23.94 543.17 23.95
July 568.17 23.99 744.00 23.94 568.17 23.95
August 554.83 23.99 738.83 23.92 554.83 23.94
September 503.67 23.99 691.00 23.90 503.17 23.92
October 509.67 23.80 619.17 23.87 457.83 23.90
November 463.00 23.17 518.33 23.56 296.33 23.66
December 435.00 22.95 524.33 23.47 251.67 23.58
             
Annual Sum or Average 6108.67 23.66 7470.17 23.78 5249.00 23.84
Minimum of Months 435.00 22.95 490.67 23.45 251.67 23.54
Maximum of Months 568.17 23.99 744.00 23.94 568.17 23.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.99 744.00 20.99 744.00 20.99
February 672.00 21.00 649.00 21.00 649.00 21.00
March 744.00 21.01 574.83 21.01 574.83 21.00
April 720.00 21.42 133.00 21.35 133.00 21.30
May 744.00 22.26 0.00 22.26 0.00 22.26
June 641.83 23.03 9.00 23.04 0.00 23.04
July 570.00 22.92 24.67 22.96 0.00 22.96
August 697.50 22.52 1.00 22.53 0.00 22.53
September 720.00 21.36 0.00 21.36 0.00 21.36
October 744.00 21.01 300.17 21.01 300.17 21.01
November 720.00 21.00 720.00 21.00 720.00 21.00
December 744.00 21.00 744.00 21.00 744.00 21.00
             
Annual Sum or Average 8461.33 21.59 3899.67 21.41 3865.00 21.31
Minimum of Months 570.00 20.99 0.00 20.99 0.00 20.99
Maximum of Months 744.00 23.03 744.00 23.04 744.00 23.04



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.94172 15.56873 -0.3409 7.82253
February 672.00000 21.36168 16.84926 -0.4807 10.09081
March 744.00000 21.34820 19.06413 -0.4731 9.84751
April 720.00000 21.54892 23.42799 -0.3967 8.46361
May 744.00000 21.65460 28.82620 -1.4844 50.08570
June 720.00000 21.95585 42.71006 -1.2923 40.01942
July 744.00000 22.63334 50.42128 -1.0007 26.42207
August 744.00000 23.38865 43.58887 -0.7749 17.90175
September 720.00000 23.69910 33.16430 -0.7320 16.46223
October 744.00000 23.71894 24.33884 0.15517 5.61705
November 720.00000 23.23750 14.34007 -0.0258 5.65418
December 744.00000 22.21395 13.87564 -0.2804 7.07843
           
Annual Sum or Average 8760.00000 22.39794 27.25273 -0.5946 17.17412
Minimum of Months 672.00000 21.34820 13.87564 -1.4844 5.61705
Maximum of Months 744.00000 23.71894 50.42128 0.15517 50.08570



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.85612 13.26037 -0.8176 19.61637
February 672.00000 21.00798 14.20164 -0.6961 15.60047
March 744.00000 21.24004 16.32933 -0.5177 11.96492
April 720.00000 21.62451 20.57040 -0.2743 8.76710
May 744.00000 21.64429 26.05570 -1.2729 41.19751
June 720.00000 21.83950 40.30475 -1.0804 31.92927
July 744.00000 21.80434 49.91477 -1.0346 30.30852
August 744.00000 21.71117 44.58481 -1.1205 34.49182
September 720.00000 21.29905 34.49979 -1.4378 48.88059
October 744.00000 21.08605 24.51888 -0.5211 11.33058
November 720.00000 21.00141 12.54757 -0.7683 17.56935
December 744.00000 20.97580 11.61480 -0.8315 19.72857
           
Annual Sum or Average 8760.00000 21.34249 25.78071 -0.8655 24.32600
Minimum of Months 672.00000 20.85612 11.61480 -1.4378 8.76710
Maximum of Months 744.00000 21.83950 49.91477 -0.2743 48.88059



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.08025 16.19327 -0.5657 11.93045
February 672.00000 21.22471 17.08232 -0.5060 10.64751
March 744.00000 21.57032 19.06107 -0.3917 8.60981
April 720.00000 22.53276 22.68526 -0.1174 5.91055
May 744.00000 22.94283 27.49720 -0.9796 25.77478
June 720.00000 23.25271 40.34316 -0.7776 18.25346
July 744.00000 23.23923 49.08675 -0.7237 16.59309
August 744.00000 23.15922 44.24285 -0.7893 18.78646
September 720.00000 22.55223 35.29418 -1.0767 30.11273
October 744.00000 21.80886 26.60940 -0.2849 7.21808
November 720.00000 21.14408 15.49440 -0.5431 11.33251
December 744.00000 21.05685 14.57753 -0.5899 12.41483
           
Annual Sum or Average 8760.00000 22.13515 27.41952 -0.6128 14.81523
Minimum of Months 672.00000 21.05685 14.57753 -1.0767 5.91055
Maximum of Months 744.00000 23.25271 49.08675 -0.1174 30.11273



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.35890 10.60940 0.31768 11.54890
February 672.00000 22.52950 11.40475 0.37696 11.61472
March 744.00000 22.82247 13.35266 0.48437 12.96091
April 720.00000 22.97361 17.46660 0.58555 14.84151
May 744.00000 23.00663 22.46700 -0.0557 10.21575
June 720.00000 23.01635 35.87839 0.05995 10.30939
July 744.00000 23.01756 44.74463 0.11793 10.55626
August 744.00000 23.02759 39.55880 0.07542 10.41140
September 720.00000 23.01735 29.65872 -0.0415 10.24451
October 744.00000 22.95394 20.56384 0.57219 14.57949
November 720.00000 22.56648 9.94009 0.36558 11.10375
December 744.00000 22.45243 9.10244 0.31869 10.70619
           
Annual Sum or Average 8760.00000 22.81333 22.13701 0.26409 11.59050
Minimum of Months 672.00000 22.35890 9.10244 -0.0557 10.21575
Maximum of Months 744.00000 23.02759 44.74463 0.58555 14.84151



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.90529 17.62183 -0.7033 15.89121
February 672.00000 21.06822 18.58437 -0.5696 12.25284
March 744.00000 21.52393 20.61350 -0.3421 8.89470
April 720.00000 22.32386 24.38532 -0.0266 6.87120
May 744.00000 22.52956 29.48774 -0.8912 23.76848
June 720.00000 22.76437 42.95333 -0.6952 16.69333
July 744.00000 22.71967 51.98480 -0.6512 15.81835
August 744.00000 22.62697 46.99777 -0.7325 18.82492
September 720.00000 22.00235 37.71737 -1.0999 32.51469
October 744.00000 21.38222 28.55857 -0.3466 8.38461
November 720.00000 21.01106 16.93664 -0.6585 14.28418
December 744.00000 20.98301 16.00686 -0.7298 16.40922
           
Annual Sum or Average 8760.00000 21.82397 29.39601 -0.6210 15.89512
Minimum of Months 672.00000 20.90529 16.00686 -1.0999 6.87120
Maximum of Months 744.00000 22.76437 51.98480 -0.0266 32.51469



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.30625 18.14861 -0.4871 10.50290
February 672.00000 21.49185 19.04429 -0.4103 9.10078
March 744.00000 21.99838 20.99798 -0.2503 6.93702
April 720.00000 22.90310 24.62724 0.02259 5.63171
May 744.00000 23.24495 29.37978 -0.7999 19.05635
June 720.00000 23.45160 42.12184 -0.6251 13.70146
July 744.00000 23.44936 50.69888 -0.5668 12.30551
August 744.00000 23.40585 45.89267 -0.6233 13.83973
September 720.00000 22.89462 37.00355 -0.8951 22.90894
October 744.00000 22.18248 28.41337 -0.1580 6.28510
November 720.00000 21.39357 17.47380 -0.4587 9.81985
December 744.00000 21.23412 16.59733 -0.5245 11.08316
           
Annual Sum or Average 8760.00000 22.41787 29.27129 -0.4819 11.77256
Minimum of Months 672.00000 21.23412 16.59733 -0.8951 5.63171
Maximum of Months 744.00000 23.45160 50.69888 0.02259 22.90894



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.48360 29.82465 -0.8509 20.88864
February 672.00000 20.56023 30.60005 -0.7827 18.44908
March 744.00000 20.90984 32.64950 -0.6158 13.59902
April 720.00000 21.47009 36.49130 -0.3185 8.45190
May 744.00000 21.67237 39.05810 -1.2913 41.14256
June 720.00000 21.71957 48.25188 -1.1434 34.09969
July 744.00000 21.71546 53.96143 -1.1267 33.29050
August 744.00000 21.68130 52.59651 -1.1970 36.57220
September 720.00000 21.38784 48.36667 -1.4781 50.30933
October 744.00000 20.81574 41.30112 -0.5896 12.91820
November 720.00000 20.48926 29.24418 -0.8386 20.35813
December 744.00000 20.47843 27.70713 -0.8810 21.99549
           
Annual Sum or Average 8760.00000 21.11821 39.22596 -0.9271 26.04315
Minimum of Months 672.00000 20.47843 27.70713 -1.4781 8.45190
Maximum of Months 744.00000 21.71957 53.96143 -0.3185 50.30933



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.48070 29.82427 -0.8588 21.21145
February 672.00000 20.48966 30.72954 -0.8243 19.95242
March 744.00000 20.59543 33.16089 -0.7250 16.64986
April 720.00000 21.15499 37.00263 -0.4367 9.94406
May 744.00000 21.99473 38.76491 -1.2434 40.34340
June 720.00000 22.65851 46.83915 -0.8948 28.04158
July 744.00000 22.47371 52.70004 -0.9331 27.66965
August 744.00000 22.20471 51.92760 -1.0888 33.60534
September 720.00000 21.20869 48.80476 -1.5777 55.26853
October 744.00000 20.64580 41.70520 -0.6502 14.44209
November 720.00000 20.48102 29.24196 -0.8533 20.94274
December 744.00000 20.47779 27.69923 -0.8834 22.09480
           
Annual Sum or Average 8760.00000 21.24347 39.08583 -0.9146 25.86600
Minimum of Months 672.00000 20.47779 27.69923 -1.5777 9.94406
Maximum of Months 744.00000 22.65851 52.70004 -0.4367 55.26853



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.65251 25.38433 -0.7182 16.39227
February 672.00000 20.72045 26.14564 -0.6880 15.43886
March 744.00000 20.89274 28.64275 -0.6109 13.16592
April 720.00000 21.22930 33.03358 -0.4550 9.59570
May 744.00000 21.69358 35.18547 -1.4128 46.53420
June 720.00000 22.12031 45.22545 -1.1623 34.48931
July 744.00000 22.13517 52.17176 -1.1199 32.74405
August 744.00000 21.89796 49.31269 -1.2548 38.80151
September 720.00000 21.33412 44.86762 -1.5311 52.66011
October 744.00000 20.99788 37.12764 -0.5183 10.91075
November 720.00000 20.66077 24.78893 -0.7169 16.29194
December 744.00000 20.63015 23.22819 -0.7418 17.12474
           
Annual Sum or Average 8760.00000 21.25043 35.48543 -0.9120 25.39528
Minimum of Months 672.00000 20.63015 23.22819 -1.5311 9.59570
Maximum of Months 744.00000 22.13517 52.17176 -0.4550 52.66011



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.48763 29.81715 -0.8476 20.75973
February 672.00000 20.60987 30.49103 -0.7604 17.75920
March 744.00000 21.17704 32.19510 -0.5274 11.82558
April 720.00000 21.57992 36.34868 -0.2914 8.24651
May 744.00000 21.73460 38.98482 -1.2175 38.00163
June 720.00000 21.74264 47.98065 -1.1085 32.78857
July 744.00000 21.74360 52.88103 -1.0816 31.58097
August 744.00000 21.72611 51.59258 -1.1560 34.90773
September 720.00000 21.50216 47.96713 -1.4155 47.30066
October 744.00000 20.93845 41.00779 -0.5459 12.06065
November 720.00000 20.49164 29.23021 -0.8376 20.33185
December 744.00000 20.47849 27.70235 -0.8806 21.97767
           
Annual Sum or Average 8760.00000 21.18748 38.90179 -0.8900 24.82690
Minimum of Months 672.00000 20.47849 27.70235 -1.4155 8.24651
Maximum of Months 744.00000 21.74360 52.88103 -0.2914 47.30066



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.48252 29.81833 -0.8559 21.09398
February 672.00000 20.50911 30.67303 -0.8082 19.38397
March 744.00000 20.83404 32.70141 -0.6431 14.29733
April 720.00000 21.38651 36.56943 -0.3869 9.24782
May 744.00000 21.95253 38.48203 -1.1996 37.02191
June 720.00000 22.39610 46.78801 -0.9466 26.68548
July 744.00000 22.47575 51.91567 -0.8940 26.06029
August 744.00000 22.13017 50.99953 -1.0829 31.79549
September 720.00000 21.39701 48.23385 -1.4937 51.01639
October 744.00000 20.76445 41.37703 -0.6076 13.37003
November 720.00000 20.48285 29.22997 -0.8525 20.91905
December 744.00000 20.47784 27.69676 -0.8829 22.07468
           
Annual Sum or Average 8760.00000 21.27881 38.75670 -0.8881 24.42723
Minimum of Months 672.00000 20.47784 27.69676 -1.4937 9.24782
Maximum of Months 744.00000 22.47575 51.91567 -0.3869 51.01639



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.47157 30.34555 -0.9181 23.43003
February 672.00000 20.49269 31.24644 -0.8592 21.14778
March 744.00000 20.74624 33.49431 -0.7000 16.01329
April 720.00000 21.37661 37.34246 -0.3636 9.38759
May 744.00000 21.64431 39.72000 -1.3191 42.68622
June 720.00000 21.70713 48.82194 -1.1525 34.70629
July 744.00000 21.70396 55.03384 -1.1324 33.72207
August 744.00000 21.65577 53.70929 -1.2166 37.66893
September 720.00000 21.29207 49.79616 -1.5423 53.63321
October 744.00000 20.68980 42.52049 -0.6598 14.84483
November 720.00000 20.47226 29.74248 -0.9078 22.94455
December 744.00000 20.46920 28.16347 -0.9488 24.63577
           
Annual Sum or Average 8760.00000 21.06313 40.05092 -0.9775 27.93239
Minimum of Months 672.00000 20.46920 28.16347 -1.5423 9.38759
Maximum of Months 744.00000 21.70713 55.03384 -0.3636 53.63321



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.47012 30.34494 -0.9251 23.73938
February 672.00000 20.47349 31.28609 -0.8898 22.36318
March 744.00000 20.53120 33.87632 -0.7922 18.86424
April 720.00000 21.04585 37.92073 -0.4908 11.21672
May 744.00000 21.99342 39.45152 -1.2635 42.11606
June 720.00000 22.73356 47.25131 -0.8689 28.75986
July 744.00000 22.52359 53.39406 -0.9150 28.01130
August 744.00000 22.22479 52.96884 -1.0912 34.77399
September 720.00000 21.08265 50.35072 -1.6566 59.28851
October 744.00000 20.56260 42.85323 -0.7132 16.32915
November 720.00000 20.47022 29.74510 -0.9206 23.49003
December 744.00000 20.46874 28.16664 -0.9509 24.73062
           
Annual Sum or Average 8760.00000 21.21982 39.85416 -0.9567 27.82008
Minimum of Months 672.00000 20.46874 28.16664 -1.6566 11.21672
Maximum of Months 744.00000 22.73356 53.39406 -0.4908 59.28851



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.53278 30.71375 -0.8295 20.10237
February 672.00000 20.91739 31.20494 -0.6643 15.46682
March 744.00000 21.30876 33.15717 -0.4667 11.19956
April 720.00000 21.60216 37.23849 -0.2563 8.20399
May 744.00000 21.68848 39.52674 -1.2848 41.40195
June 720.00000 21.71216 48.25224 -1.1784 36.11419
July 744.00000 21.71325 53.94868 -1.1429 34.43010
August 744.00000 21.69596 52.20982 -1.1859 36.59731
September 720.00000 21.54107 48.08627 -1.3872 46.21972
October 744.00000 21.12140 41.25027 -0.4848 11.09002
November 720.00000 20.59951 30.09716 -0.7975 19.01933
December 744.00000 20.48275 28.69014 -0.8782 21.88751
           
Annual Sum or Average 8760.00000 21.24433 39.58454 -0.8812 25.19935
Minimum of Months 672.00000 20.48275 28.69014 -1.3872 8.20399
Maximum of Months 744.00000 21.71325 53.94868 -0.2563 46.21972



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.53868 20.88065 -0.1932 7.55421
February 672.00000 22.62839 21.66608 -0.1491 7.23166
March 744.00000 23.13489 23.28361 0.00825 6.23098
April 720.00000 23.64618 26.19242 0.20862 6.37657
May 744.00000 23.87888 29.88077 -0.5231 10.88888
June 720.00000 23.95591 41.82659 -0.3545 7.73359
July 744.00000 23.95472 50.22454 -0.2996 6.98009
August 744.00000 23.89623 45.91033 -0.3899 8.46042
September 720.00000 23.73307 37.50739 -0.5850 12.72475
October 744.00000 23.42790 29.77906 0.14235 6.22797
November 720.00000 22.57569 20.30712 -0.1854 7.32068
December 744.00000 22.35637 19.57044 -0.2541 7.86081
           
Annual Sum or Average 8760.00000 23.31435 30.64950 -0.2149 7.96564
Minimum of Months 672.00000 22.35637 19.57044 -0.5850 6.22797
Maximum of Months 744.00000 23.95591 50.22454 0.20862 12.72475



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.79751 20.09339 -0.0886 6.94766
February 672.00000 22.87237 20.81659 -0.0491 6.78132
March 744.00000 23.36587 22.30399 0.10492 6.29799
April 720.00000 23.80145 25.22370 0.28493 6.98426
May 744.00000 23.94878 29.06838 -0.4477 9.26125
June 720.00000 23.98449 41.20362 -0.3006 6.96905
July 744.00000 23.98312 49.59281 -0.2460 6.34051
August 744.00000 23.95259 45.13911 -0.3230 7.36717
September 720.00000 23.86318 36.44421 -0.4815 10.15090
October 744.00000 23.63715 28.66975 0.23528 6.71467
November 720.00000 22.84561 19.51449 -0.0783 6.72300
December 744.00000 22.61094 18.88659 -0.1514 7.06577
           
Annual Sum or Average 8760.00000 23.47519 29.81047 -0.1289 7.30011
Minimum of Months 672.00000 22.61094 18.88659 -0.4815 6.29799
Maximum of Months 744.00000 23.98449 49.59281 0.28493 10.15090



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.21167 19.60280 0.62090 17.76642
February 672.00000 23.33504 20.07646 0.68814 19.48751
March 744.00000 23.52391 20.95136 0.80192 22.60150
April 720.00000 23.71590 24.22446 0.94775 26.83844
May 744.00000 23.83129 28.57149 0.52386 15.81821
June 720.00000 23.89716 40.88974 0.67630 18.86587
July 744.00000 23.89389 49.10951 0.73108 20.73958
August 744.00000 23.86233 44.44265 0.64103 18.37784
September 720.00000 23.77888 35.45911 0.45106 14.28620
October 744.00000 23.66989 27.46387 0.88784 24.41388
November 720.00000 23.33253 18.94593 0.65126 18.01961
December 744.00000 23.24356 18.53088 0.60451 17.11840
           
Annual Sum or Average 8760.00000 23.60945 29.08649 0.68549 19.52840
Minimum of Months 672.00000 23.21167 18.53088 0.45106 14.28620
Maximum of Months 744.00000 23.89716 49.10951 0.94775 26.83844



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.99578 13.23602 -0.6633 14.31500
February 672.00000 21.00020 14.21153 -0.6430 13.77158
March 744.00000 21.00215 16.35376 -0.6014 12.66205
April 720.00000 21.37641 20.59977 -0.4460 9.47480
May 744.00000 22.29702 25.08337 -1.2647 38.60125
June 720.00000 23.01058 37.57112 -0.9364 23.71061
July 744.00000 23.08885 46.33438 -0.8511 20.54244
August 744.00000 22.80805 41.83225 -0.9805 25.68912
September 720.00000 21.77048 33.45024 -1.3950 45.41921
October 744.00000 21.08346 24.42500 -0.5112 10.62075
November 720.00000 21.00022 12.55926 -0.6583 14.14869
December 744.00000 21.00023 11.54992 -0.6794 14.75558
           
Annual Sum or Average 8760.00000 21.70761 24.83997 -0.8032 20.33144
Minimum of Months 672.00000 20.99578 11.54992 -1.3950 9.47480
Maximum of Months 744.00000 23.08885 46.33438 -0.4460 45.41921



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.98854 16.63338 -0.6373 13.59190
February 672.00000 21.00052 17.64684 -0.6132 12.94982
March 744.00000 21.00786 19.82035 -0.5712 11.88453
April 720.00000 21.55263 23.92578 -0.3902 8.59968
May 744.00000 22.53868 28.34676 -1.1766 34.34998
June 720.00000 23.22209 40.80078 -0.8564 20.68276
July 744.00000 23.16828 49.70748 -0.8162 19.35571
August 744.00000 22.75808 45.55562 -0.9899 26.15268
September 720.00000 21.54113 37.34253 -1.4711 49.46450
October 744.00000 21.01404 27.95428 -0.5246 10.82867
November 720.00000 21.00057 15.97137 -0.6344 13.48361
December 744.00000 20.99895 14.95718 -0.6499 13.91806
           
Annual Sum or Average 8760.00000 21.73757 28.29466 -0.7783 19.62203
Minimum of Months 672.00000 20.98854 14.95718 -1.4711 8.59968
Maximum of Months 744.00000 23.22209 49.70748 -0.3902 49.46450



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.99376 13.97082 -0.6884 15.06371
February 672.00000 21.00059 14.94077 -0.6555 14.13637
March 744.00000 21.01156 17.13529 -0.5914 12.44014
April 720.00000 21.41593 21.39136 -0.4122 9.01471
May 744.00000 22.26183 25.89222 -1.2214 36.75095
June 720.00000 23.11494 38.15625 -0.8358 20.22890
July 744.00000 23.10396 46.99434 -0.7806 18.46998
August 744.00000 22.59816 42.98102 -0.9925 26.73344
September 720.00000 21.35994 34.99934 -1.4999 51.00142
October 744.00000 21.01118 25.29261 -0.5321 11.03052
November 720.00000 21.00063 13.27465 -0.6860 14.95516
December 744.00000 21.00068 12.30614 -0.7089 15.64780
           
Annual Sum or Average 8760.00000 21.66075 25.68421 -0.8009 20.47139
Minimum of Months 672.00000 20.99376 12.30614 -1.4999 9.01471
Maximum of Months 744.00000 23.11494 46.99434 -0.4122 51.00142



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.99985 12.69225 -0.6392 13.64070
February 672.00000 21.00456 13.65547 -0.6199 13.15469
March 744.00000 21.03737 15.76751 -0.5757 12.04167
April 720.00000 21.61697 19.77307 -0.3879 8.55769
May 744.00000 22.55958 24.14877 -1.1792 34.42267
June 720.00000 23.20597 36.56988 -0.8720 21.27450
July 744.00000 23.28816 45.20505 -0.7852 18.27983
August 744.00000 23.06452 40.63956 -0.8962 22.34752
September 720.00000 22.11539 32.24840 -1.2828 39.68295
October 744.00000 21.24526 23.62960 -0.4627 9.73455
November 720.00000 21.00042 12.01095 -0.6337 13.47334
December 744.00000 21.00012 11.00588 -0.6566 14.10623
           
Annual Sum or Average 8760.00000 21.85022 24.01690 -0.7498 18.41028
Minimum of Months 672.00000 20.99985 11.00588 -1.2828 8.55769
Maximum of Months 744.00000 23.28816 45.20505 -0.3879 39.68295



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 29344882.70 8702.43 05-JAN-09:04 1.70 93505573.91 0.00 0.122850E+09 0.01 3.19 02-JAN-09:04 0.00 0.00
February 0.254488E+09 14143.42 08-FEB-16:04 37.33 0.810909E+09 0.00 0.106540E+10 0.18 3.19 15-FEB-15:00 0.00 0.00
March 0.333107E+10 28430.72 22-MAR-15:01 213.03 0.106142E+11 0.00 0.139453E+11 0.91 3.19 21-MAR-08:06 0.00 0.00
April 0.215652E+11 49865.01 22-APR-15:03 537.50 0.686887E+11 0.00 0.902539E+11 2.38 3.77 22-APR-15:03 0.00 0.00
May 0.487784E+11 79400.03 31-MAY-15:03 742.33 0.154437E+12 0.00 0.203215E+12 3.16 4.09 10-MAY-15:03 0.00 0.00
June 0.876661E+11 110197.45 20-JUN-18:03 719.00 0.286963E+12 0.00 0.374629E+12 3.20 4.08 30-JUN-18:03 0.00 0.00
July 0.990996E+11 122075.07 29-JUL-15:03 744.00 0.329041E+12 0.00 0.428141E+12 3.23 4.31 03-JUL-15:03 0.00 0.00
August 0.699217E+11 103852.21 11-AUG-18:03 742.67 0.227330E+12 0.00 0.297252E+12 3.18 4.09 26-AUG-15:03 0.00 0.00
September 0.187577E+11 54313.67 02-SEP-15:03 622.82 0.591785E+11 0.00 0.779362E+11 2.75 3.83 02-SEP-15:03 0.00 0.00
October 0.353312E+10 37153.36 03-OCT-15:02 241.66 0.112564E+11 0.00 0.147895E+11 1.03 3.19 09-OCT-18:30 0.00 0.00
November 46433127.00 9514.37 15-NOV-09:04 5.30 0.147956E+09 0.00 0.194389E+09 0.02 3.19 25-NOV-19:04 0.00 0.00
December 18810348.00 9585.94 24-DEC-16:04 1.16 59937959.33 0.00 78748307.33 0.00 3.19 02-DEC-09:04 0.00 0.00
                         
Annual Sum or Average 0.353002E+12     4608.51 0.114862E+13 0.00 0.150162E+13 1.68     0.00 0.00
Minimum of Months 18810348.00 8702.43   1.16 59937959.33 0.00 78748307.33 0.00 3.19   0.00 0.00
Maximum of Months 0.990996E+11 122075.07   744.00 0.329041E+12 0.00 0.428141E+12 3.23 4.31   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.775131E+12 0.00 744.00 938714.21 12-JAN-09:03 0.00 47.03 82.18 2.08 0.00 0.36 1.18 12-JAN-09:03
February 0.612265E+12 0.00 672.00 883773.62 27-FEB-09:03 0.00 45.87 82.07 1.82 0.00 0.32 1.11 27-FEB-09:03
March 0.361263E+12 0.00 744.00 781255.58 01-MAR-09:03 0.00 45.03 81.96 0.92 0.00 0.17 0.98 01-MAR-09:03
April 0.927687E+11 0.00 631.55 315578.24 03-APR-08:61 0.00 44.12 75.78 0.23 0.00 0.04 0.40 03-APR-08:61
May 0.493566E+11 0.00 514.98 125559.00 19-MAY-07:00 0.00 30.91 63.54 0.09 0.00 0.02 0.16 19-MAY-07:00
June 0.364046E+11 0.00 284.85 114100.81 02-JUN-06:20 0.00 26.89 47.40 0.07 0.00 0.02 0.14 02-JUN-06:20
July 0.367405E+11 0.00 294.18 127725.82 04-JUL-08:04 0.00 27.29 47.76 0.06 0.00 0.02 0.16 04-JUL-08:04
August 0.547432E+11 0.00 416.00 139165.60 29-AUG-08:05 0.00 28.81 56.46 0.10 0.00 0.03 0.17 29-AUG-08:05
September 0.596773E+11 0.00 663.90 136273.35 04-SEP-08:04 0.00 43.82 76.25 0.14 0.00 0.03 0.17 04-SEP-08:04
October 0.173698E+12 0.00 742.83 308500.13 27-OCT-08:03 0.00 47.96 81.26 0.44 0.00 0.08 0.39 27-OCT-08:03
November 0.710296E+12 0.00 720.00 843159.59 29-NOV-09:03 0.00 46.32 82.20 1.96 0.00 0.34 1.06 29-NOV-09:03
December 0.897946E+12 0.00 744.00 898377.12 15-DEC-09:03 0.00 47.61 82.15 2.45 0.00 0.42 1.13 15-DEC-09:03
                           
Annual Sum or Average 0.386029E+13 0.00 7172.29     0.00 40.09 71.51 0.86 0.00 0.15    
Minimum of Months 0.364046E+11 0.00 284.85 114100.81   0.00 26.89 47.40 0.06 0.00 0.02 0.14  
Maximum of Months 0.897946E+12 0.00 744.00 938714.21   0.00 47.96 82.20 2.45 0.00 0.42 1.18  



Table of Contents

Report: DXReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 01-JAN-00:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 01-FEB-00:03
March 0.197241E+10 0.00 744.00 0.197241E+10 -0.0 0.00 1.00 01-MAR-00:05 1.00 01-MAR-00:05 36539.74 31-MAR-23:03 36539.74 31-MAR-23:30 0.00 31-MAR-23:03 0.00 0.00 01-MAR-00:05
April 0.620987E+11 0.00 515.10 0.620987E+11 0.00 0.00 1.00 01-APR-01:07 0.00 01-APR-00:20 50421.70 30-APR-23:20 50421.70 30-APR-23:20 0.00 01-APR-03:10 0.00 0.00 01-APR-00:10
May 0.714947E+11 0.00 465.41 0.714947E+11 0.00 0.00 1.00 01-MAY-03:10 0.00 01-MAY-00:10 58188.26 31-MAY-23:05 58188.26 31-MAY-23:05 0.00 16-MAY-18:13 0.00 0.00 01-MAY-00:05
June 0.691695E+11 0.00 418.00 0.691624E+11 7151675.65 0.00 1.00 01-JUN-05:15 0.00 01-JUN-00:05 58643.99 01-JUN-05:15 58643.99 01-JUN-06:30 5973.25 30-JUN-23:05 0.00 0.00 01-JUN-00:05
July 0.690349E+11 0.00 417.44 0.618016E+11 0.723325E+10 0.00 1.00 01-JUL-05:13 0.00 01-JUL-00:10 60476.66 01-JUL-05:13 53994.40 01-JUL-21:50 6537.05 29-JUL-08:13 0.00 0.00 01-JUL-00:10
August 0.661186E+11 0.00 419.95 0.626988E+11 0.341982E+10 0.00 1.00 01-AUG-04:07 0.00 01-AUG-00:05 56481.89 01-AUG-07:00 53596.81 02-AUG-17:50 3251.20 02-AUG-17:25 0.00 0.00 01-AUG-00:05
September 0.602229E+11 0.00 441.34 0.602229E+11 -0.0 0.00 1.00 01-SEP-03:07 0.00 01-SEP-00:10 45764.68 30-SEP-05:15 45764.68 30-SEP-05:50 0.00 18-SEP-19:10 0.00 0.00 01-SEP-00:05
October 0.551998E+11 0.00 532.63 0.551998E+11 0.00 0.00 1.00 01-OCT-01:07 0.00 01-OCT-00:20 31633.74 31-OCT-05:30 31633.74 31-OCT-10:00 0.00 04-OCT-08:40 0.00 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 0.00 01-NOV-00:05
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.455311E+12 0.00 3953.87 0.444651E+12 0.106602E+11 0.00                     0.00    
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00 0.00  
Maximum of Months 0.714947E+11 0.00 744.00 0.714947E+11 0.723325E+10 0.00 1.00   1.00   60476.66   58643.99   6537.05   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 01-JAN-00:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 01-FEB-00:03
March 0.228861E+10 0.00 743.50 0.228861E+10 -0.0 0.00 1.00 01-MAR-00:05 0.00 31-MAR-23:30 46231.99 31-MAR-23:03 46231.99 31-MAR-23:03 0.00 31-MAR-23:15 0.00 0.00 01-MAR-00:05
April 0.358380E+11 0.00 371.09 0.358380E+11 -0.0 0.00 1.00 01-APR-16:05 0.00 01-APR-00:10 63809.82 30-APR-23:03 63809.82 30-APR-23:03 0.00 03-APR-16:10 0.00 0.00 01-APR-00:10
May 0.505395E+11 0.00 361.77 0.505395E+11 0.00 0.00 1.00 01-MAY-16:10 0.00 01-MAY-00:05 63809.82 01-MAY-17:23 63809.82 01-MAY-20:30 0.00 03-MAY-19:10 0.00 0.00 01-MAY-00:05
June 0.565989E+11 0.00 341.36 0.565976E+11 1352081.76 0.00 1.00 01-JUN-16:10 0.00 01-JUN-00:05 74221.18 01-JUN-16:10 74221.18 01-JUN-16:10 4337.07 30-JUN-23:05 0.00 0.00 01-JUN-00:05
July 0.603495E+11 0.00 348.01 0.540421E+11 0.630738E+10 0.00 1.00 01-JUL-16:10 0.00 01-JUL-00:20 76541.78 01-JUL-20:10 68357.45 01-JUL-22:00 8252.87 31-JUL-18:40 0.00 0.00 01-JUL-00:10
August 0.565249E+11 0.00 355.93 0.536150E+11 0.290995E+10 0.00 1.00 01-AUG-16:10 0.00 01-AUG-00:05 71483.46 01-AUG-16:10 67850.84 02-AUG-17:50 4104.15 02-AUG-17:35 0.00 0.00 01-AUG-00:05
September 0.444114E+11 0.00 372.12 0.444114E+11 -0.0 0.00 1.00 01-SEP-16:10 0.00 01-SEP-00:10 57912.94 30-SEP-16:05 57912.94 30-SEP-16:05 0.00 19-SEP-21:40 0.00 0.00 01-SEP-00:05
October 0.318854E+11 0.00 387.34 0.318854E+11 0.00 0.00 1.00 01-OCT-16:10 0.00 01-OCT-00:20 40019.83 31-OCT-16:40 40019.83 31-OCT-21:50 0.00 01-OCT-16:50 0.00 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 0.00 01-NOV-00:05
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.338436E+12 0.00 3281.12 0.329218E+12 0.921868E+10 0.00                     0.00    
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00 0.00  
Maximum of Months 0.603495E+11 0.00 743.50 0.565976E+11 0.630738E+10 0.00 1.00   0.00   76541.78   74221.18   8252.87   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 0.00 0.00
April 0.478836E+09 0.00 11.17 0.478836E+09 0.00 0.00 0.00 0.00 21907.64 22-APR-16:10 21907.64 22-APR-16:10 0.00 0.00 0.00
May 0.332680E+11 0.00 204.33 0.332680E+11 0.00 0.00 0.00 0.00 147431.63 31-MAY-18:03 147431.63 31-MAY-18:03 0.00 0.00 0.00
June 0.126537E+12 0.00 441.17 0.125554E+12 0.00 0.00 0.00 0.00 217466.52 29-JUN-20:00 217158.33 20-JUN-19:10 0.00 0.00 0.00
July 0.159515E+12 0.00 481.67 0.157099E+12 0.00 0.00 0.00 0.00 244676.48 29-JUL-18:03 216645.99 29-JUL-17:15 0.00 0.00 0.00
August 0.933007E+11 0.00 354.50 0.931520E+11 0.00 0.00 0.00 0.00 205710.39 11-AUG-19:10 205710.39 11-AUG-19:10 0.00 0.00 0.00
September 0.438856E+10 0.00 55.83 0.438856E+10 0.00 0.00 0.00 0.00 57277.58 02-SEP-18:00 57277.58 02-SEP-18:00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.417488E+12 0.00 1548.67 0.413940E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.159515E+12 0.00 481.67 0.157099E+12 0.00 0.00 0.00 0.00 244676.48   217158.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 0.00 0.00
April 2616979.37 0.00 2.17 2616979.37 0.00 0.00 0.00 0.00 594.90 22-APR-14:20 594.90 22-APR-14:20 0.00 0.00 0.00
May 0.187749E+10 0.00 116.83 0.187749E+10 0.00 0.00 0.00 0.00 14984.27 31-MAY-16:00 14984.27 31-MAY-16:00 0.00 0.00 0.00
June 0.875150E+10 0.00 318.17 0.866818E+10 0.00 0.00 0.00 0.00 20268.27 30-JUN-12:20 18265.07 30-JUN-15:02 0.00 0.00 0.00
July 0.107248E+11 0.00 351.67 0.105096E+11 0.00 0.00 0.00 0.00 19576.59 03-JUL-15:10 19046.08 29-JUL-15:02 0.00 0.00 0.00
August 0.644682E+10 0.00 251.67 0.640249E+10 0.00 0.00 0.00 0.00 17539.91 11-AUG-18:02 17539.91 11-AUG-18:02 0.00 0.00 0.00
September 0.192142E+09 0.00 30.83 0.192142E+09 0.00 0.00 0.00 0.00 4990.98 07-SEP-16:00 4990.98 07-SEP-16:00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.279954E+11 0.00 1071.33 0.276525E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.107248E+11 0.00 351.67 0.105096E+11 0.00 0.00 0.00 0.00 20268.27   19046.08   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3002826.45 0.00 0.48 3002826.45 0.00 0.00 0.00 0.00 3456.20 22-JAN-09:04 3456.20 22-JAN-09:04 0.00 0.00 0.00
February 10943996.63 0.00 1.17 10705249.52 0.00 0.00 0.00 0.00 4196.49 11-FEB-19:04 4196.49 11-FEB-19:04 0.00 0.00 0.00
March 0.235378E+09 0.00 30.10 0.231857E+09 0.00 0.00 0.00 0.00 13665.12 28-MAR-15:02 13665.12 28-MAR-15:02 0.00 0.00 0.00
April 0.298456E+10 0.00 337.30 0.292097E+10 0.00 0.00 0.00 0.00 13681.20 18-APR-15:02 13681.20 18-APR-15:02 0.00 0.00 0.00
May 0.534421E+10 0.00 631.06 0.493939E+10 0.00 0.00 0.00 0.00 14437.85 31-MAY-18:02 14437.85 31-MAY-18:02 0.00 0.00 0.00
June 0.797876E+10 0.00 668.91 0.585427E+10 0.00 0.00 0.00 0.00 14672.94 22-JUN-18:02 14672.94 22-JUN-18:02 0.00 0.00 0.00
July 0.790830E+10 0.00 687.31 0.492802E+10 0.00 0.00 0.00 0.00 14962.95 26-JUL-15:01 14241.88 07-JUL-18:02 0.00 0.00 0.00
August 0.586013E+10 0.00 645.33 0.370601E+10 0.00 0.00 0.00 0.00 14967.68 13-AUG-15:02 13969.58 17-AUG-18:01 0.00 0.00 0.00
September 0.141209E+10 0.00 275.34 0.944702E+09 0.00 0.00 0.00 0.00 13813.49 02-SEP-18:02 13813.49 02-SEP-18:02 0.00 0.00 0.00
October 77209575.93 0.00 18.45 59470141.29 0.00 0.00 0.00 0.00 13431.40 13-OCT-15:02 13431.40 13-OCT-15:02 0.00 0.00 0.00
November 3119513.88 0.00 0.52 3119513.88 0.00 0.00 0.00 0.00 2880.83 04-NOV-08:04 2880.83 04-NOV-08:04 0.00 0.00 0.00
December 1837285.95 0.00 0.24 1688269.36 0.00 0.00 0.00 0.00 3548.55 24-DEC-19:04 3548.55 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.318195E+11 0.00 3296.21 0.236032E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1837285.95 0.00 0.24 1688269.36 0.00 0.00 0.00 0.00 2880.83   2880.83   0.00 0.00 0.00
Maximum of Months 0.797876E+10 0.00 687.31 0.585427E+10 0.00 0.00 0.00 0.00 14967.68   14672.94   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2102655.24 0.00 0.33 2102655.24 0.00 0.00 0.00 0.00 3819.93 22-JAN-09:04 3819.93 22-JAN-09:04 0.00 0.00 0.00
February 7024243.77 0.00 0.76 6896742.40 0.00 0.00 0.00 0.00 4565.01 08-FEB-19:04 4565.01 08-FEB-19:04 0.00 0.00 0.00
March 31823022.88 0.00 11.21 30988473.96 0.00 0.00 0.00 0.00 9984.54 27-MAR-18:01 9984.54 27-MAR-18:01 0.00 0.00 0.00
April 0.153260E+10 0.00 200.51 0.150840E+10 0.00 0.00 0.00 0.00 12283.60 28-APR-15:02 12283.60 28-APR-15:02 0.00 0.00 0.00
May 0.315291E+10 0.00 480.23 0.286982E+10 0.00 0.00 0.00 0.00 14150.08 09-MAY-20:01 14150.08 09-MAY-20:01 0.00 0.00 0.00
June 0.539385E+10 0.00 507.75 0.374820E+10 0.00 0.00 0.00 0.00 15446.04 28-JUN-21:51 13650.09 26-JUN-21:51 0.00 0.00 0.00
July 0.537998E+10 0.00 520.48 0.329496E+10 0.00 0.00 0.00 0.00 15953.38 06-JUL-17:32 15953.38 06-JUL-17:32 0.00 0.00 0.00
August 0.321582E+10 0.00 457.94 0.177348E+10 0.00 0.00 0.00 0.00 14134.02 01-AUG-21:51 13010.83 02-AUG-21:51 0.00 0.00 0.00
September 0.542942E+09 0.00 141.56 0.341978E+09 0.00 0.00 0.00 0.00 12677.01 02-SEP-19:41 12677.01 02-SEP-19:41 0.00 0.00 0.00
October 20797425.83 0.00 4.55 16424974.39 0.00 0.00 0.00 0.00 8895.12 03-OCT-15:02 8895.12 03-OCT-15:02 0.00 0.00 0.00
November 1226373.41 0.00 0.29 1226373.41 0.00 0.00 0.00 0.00 3159.45 04-NOV-08:04 3159.45 04-NOV-08:04 0.00 0.00 0.00
December 1391987.19 0.00 0.21 1281709.54 0.00 0.00 0.00 0.00 3195.98 24-DEC-19:04 3195.98 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.192825E+11 0.00 2325.83 0.135957E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1226373.41 0.00 0.21 1226373.41 0.00 0.00 0.00 0.00 3159.45   3159.45   0.00 0.00 0.00
Maximum of Months 0.539385E+10 0.00 520.48 0.374820E+10 0.00 0.00 0.00 0.00 15953.38   15953.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.422028E+10 0.00 83.58 0.422028E+10 0.00 0.00 0.00 0.00 40899.66 31-MAR-13:20 40899.66 31-MAR-13:20 0.00 0.00 0.00
April 0.351867E+11 0.00 499.90 0.351867E+11 0.00 0.00 0.00 0.00 64181.56 22-APR-13:20 64181.56 22-APR-13:20 0.00 0.00 0.00
May 0.455757E+11 0.00 691.23 0.454764E+11 0.00 0.00 0.00 0.00 61116.90 12-MAY-13:15 61116.90 12-MAY-13:15 0.00 0.00 0.00
June 0.514512E+11 0.00 716.58 0.325493E+11 0.00 0.00 0.00 0.00 56929.73 30-JUN-12:30 51683.09 08-JUN-12:40 0.00 0.00 0.00
July 0.539631E+11 0.00 739.08 0.295432E+11 0.00 0.00 0.00 0.00 64460.04 23-JUL-13:30 57444.72 21-JUL-13:05 0.00 0.00 0.00
August 0.499388E+11 0.00 722.45 0.291545E+11 0.00 0.00 0.00 0.00 67963.16 25-AUG-13:30 59864.54 31-AUG-13:20 0.00 0.00 0.00
September 0.242808E+11 0.00 501.96 0.198310E+11 0.00 0.00 0.00 0.00 61022.06 09-SEP-13:10 53768.74 09-SEP-15:03 0.00 0.00 0.00
October 0.494406E+10 0.00 144.14 0.494406E+10 0.00 0.00 0.00 0.00 47516.46 03-OCT-12:50 47516.46 03-OCT-12:50 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.269561E+12 0.00 4098.93 0.200905E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.539631E+11 0.00 739.08 0.454764E+11 0.00 0.00 0.00 0.00 67963.16   64181.56   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 52117284.43 0.00 1.03 52117284.43 0.00 0.00 0.00 0.00 24147.22 09-JAN-09:04 24147.22 09-JAN-09:04 0.00 0.00 0.00
February 59420822.73 0.00 1.57 59357957.94 0.00 0.00 0.00 0.00 29692.34 11-FEB-09:01 29692.34 11-FEB-09:01 0.00 0.00 0.00
March 0.407010E+09 0.00 31.22 0.407010E+09 0.00 0.00 0.00 0.00 58522.73 22-MAR-18:02 58522.73 22-MAR-18:02 0.00 0.00 0.00
April 0.811985E+10 0.00 270.37 0.808531E+10 0.00 0.00 0.00 0.00 63911.09 30-APR-18:02 63911.09 30-APR-18:02 0.00 0.00 0.00
May 0.290708E+11 0.00 484.39 0.284965E+11 0.00 0.00 0.00 0.00 68395.94 31-MAY-15:02 68395.94 31-MAY-15:02 0.00 0.00 0.00
June 0.432211E+11 0.00 457.63 0.365669E+11 0.00 0.00 0.00 0.00 74566.11 30-JUN-21:51 72182.29 22-JUN-21:51 0.00 0.00 0.00
July 0.453224E+11 0.00 471.22 0.341936E+11 0.00 0.00 0.00 0.00 75214.67 18-JUL-21:51 69524.51 29-JUL-18:02 0.00 0.00 0.00
August 0.311017E+11 0.00 437.79 0.228834E+11 0.00 0.00 0.00 0.00 73200.55 12-AUG-21:52 67708.22 02-AUG-21:51 0.00 0.00 0.00
September 0.114475E+11 0.00 409.60 0.797220E+10 0.00 0.00 0.00 0.00 62657.50 07-SEP-18:01 62657.50 07-SEP-18:01 0.00 0.00 0.00
October 0.171337E+10 0.00 115.96 0.148887E+10 0.00 0.00 0.00 0.00 59758.09 04-OCT-18:02 59758.09 04-OCT-18:02 0.00 0.00 0.00
November 46571621.01 0.00 1.05 46571621.01 0.00 0.00 0.00 0.00 27234.34 14-NOV-19:04 27234.34 14-NOV-19:04 0.00 0.00 0.00
December 35155540.58 0.00 0.87 35155540.58 0.00 0.00 0.00 0.00 31937.80 24-DEC-09:01 31937.80 24-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.170597E+12 0.00 2682.69 0.140287E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 35155540.58 0.00 0.87 35155540.58 0.00 0.00 0.00 0.00 24147.22   24147.22   0.00 0.00 0.00
Maximum of Months 0.453224E+11 0.00 484.39 0.365669E+11 0.00 0.00 0.00 0.00 75214.67   72182.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2806730.70 0.00 0.40 2806730.70 0.00 0.00 0.00 0.00 3523.67 22-JAN-09:04 3523.67 22-JAN-09:04 0.00 0.00 0.00
February 13590458.02 0.00 1.86 13414853.22 0.00 0.00 0.00 0.00 4269.17 07-FEB-19:04 4269.17 07-FEB-19:04 0.00 0.00 0.00
March 0.409574E+09 0.00 84.52 0.394685E+09 0.00 0.00 0.00 0.00 12918.58 20-MAR-15:01 12918.58 20-MAR-15:01 0.00 0.00 0.00
April 0.284730E+10 0.00 370.52 0.275474E+10 0.00 0.00 0.00 0.00 12919.95 29-APR-18:01 12919.95 29-APR-18:01 0.00 0.00 0.00
May 0.730143E+10 0.00 678.87 0.687268E+10 0.00 0.00 0.00 0.00 13634.72 31-MAY-18:02 13634.72 31-MAY-18:02 0.00 0.00 0.00
June 0.901863E+10 0.00 686.53 0.695474E+10 0.00 0.00 0.00 0.00 13873.15 27-JUN-15:02 13856.32 22-JUN-18:02 0.00 0.00 0.00
July 0.966335E+10 0.00 712.90 0.671080E+10 0.00 0.00 0.00 0.00 13818.26 26-JUL-15:01 13520.60 29-JUL-18:02 0.00 0.00 0.00
August 0.704057E+10 0.00 680.00 0.478007E+10 0.00 0.00 0.00 0.00 13794.95 13-AUG-15:02 13389.74 23-AUG-18:02 0.00 0.00 0.00
September 0.196288E+10 0.00 343.52 0.127387E+10 0.00 0.00 0.00 0.00 12954.99 02-SEP-18:02 12954.99 02-SEP-18:02 0.00 0.00 0.00
October 0.179546E+09 0.00 51.29 0.132343E+09 0.00 0.00 0.00 0.00 12789.84 04-OCT-08:62 12789.84 04-OCT-08:62 0.00 0.00 0.00
November 2403495.36 0.00 0.43 2403495.36 0.00 0.00 0.00 0.00 3059.82 04-NOV-08:04 3059.82 04-NOV-08:04 0.00 0.00 0.00
December 1590622.10 0.00 0.21 1465744.91 0.00 0.00 0.00 0.00 3363.02 24-DEC-09:04 3091.45 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.384437E+11 0.00 3611.06 0.298940E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1590622.10 0.00 0.21 1465744.91 0.00 0.00 0.00 0.00 3059.82   3059.82   0.00 0.00 0.00
Maximum of Months 0.966335E+10 0.00 712.90 0.695474E+10 0.00 0.00 0.00 0.00 13873.15   13856.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1837742.01 0.00 0.26 1837742.01 0.00 0.00 0.00 0.00 3331.60 22-JAN-09:04 3331.60 22-JAN-09:04 0.00 0.00 0.00
February 7264750.64 0.00 0.88 7178868.61 0.00 0.00 0.00 0.00 3993.72 11-FEB-19:04 3993.72 11-FEB-19:04 0.00 0.00 0.00
March 0.104630E+09 0.00 20.74 98957766.06 0.00 0.00 0.00 0.00 10813.64 27-MAR-08:61 10813.64 27-MAR-08:61 0.00 0.00 0.00
April 0.126980E+10 0.00 233.90 0.121190E+10 0.00 0.00 0.00 0.00 11714.78 28-APR-15:02 11714.78 28-APR-15:02 0.00 0.00 0.00
May 0.524135E+10 0.00 580.91 0.488245E+10 0.00 0.00 0.00 0.00 12471.47 14-MAY-20:41 12471.47 14-MAY-20:41 0.00 0.00 0.00
June 0.677613E+10 0.00 528.83 0.516035E+10 0.00 0.00 0.00 0.00 14004.85 30-JUN-21:51 13592.29 29-JUN-08:32 0.00 0.00 0.00
July 0.709816E+10 0.00 550.17 0.491412E+10 0.00 0.00 0.00 0.00 15509.45 11-JUL-08:22 15170.90 11-JUL-08:22 0.00 0.00 0.00
August 0.455910E+10 0.00 529.54 0.294840E+10 0.00 0.00 0.00 0.00 13415.54 12-AUG-21:52 12479.30 10-AUG-21:51 0.00 0.00 0.00
September 0.940911E+09 0.00 228.08 0.578549E+09 0.00 0.00 0.00 0.00 11535.46 07-SEP-18:01 11535.46 07-SEP-18:01 0.00 0.00 0.00
October 45176043.37 0.00 14.23 32528541.08 0.00 0.00 0.00 0.00 11138.88 04-OCT-08:62 11138.88 04-OCT-08:62 0.00 0.00 0.00
November 909331.70 0.00 0.21 909331.70 0.00 0.00 0.00 0.00 3024.12 04-NOV-08:04 3024.12 04-NOV-08:04 0.00 0.00 0.00
December 1229432.66 0.00 0.19 1148899.79 0.00 0.00 0.00 0.00 3338.62 24-DEC-19:04 3338.62 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.260465E+11 0.00 2687.94 0.198383E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 909331.70 0.00 0.19 909331.70 0.00 0.00 0.00 0.00 3024.12   3024.12   0.00 0.00 0.00
Maximum of Months 0.709816E+10 0.00 580.91 0.516035E+10 0.00 0.00 0.00 0.00 15509.45   15170.90   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 146088.51 0.00 0.29 117842.74 0.00 0.00 0.00 0.00 291.85 22-JAN-09:04 216.63 20-JAN-09:04 0.00 0.00 0.00
February 1233426.58 0.00 0.93 1125484.95 0.00 0.00 0.00 0.00 771.48 09-FEB-19:04 756.63 13-FEB-16:04 0.00 0.00 0.00
March 44398467.36 0.00 22.43 43282675.32 0.00 0.00 0.00 0.00 3547.24 27-MAR-18:01 3547.24 27-MAR-18:01 0.00 0.00 0.00
April 0.716641E+09 0.00 268.18 0.699909E+09 0.00 0.00 0.00 0.00 3575.30 28-APR-15:02 3575.30 28-APR-15:02 0.00 0.00 0.00
May 0.124089E+10 0.00 557.07 0.113562E+10 0.00 0.00 0.00 0.00 3772.90 31-MAY-18:02 3772.90 31-MAY-18:02 0.00 0.00 0.00
June 0.195159E+10 0.00 653.23 0.143864E+10 0.00 0.00 0.00 0.00 3845.81 24-JUN-15:01 3834.13 22-JUN-18:02 0.00 0.00 0.00
July 0.193161E+10 0.00 672.64 0.121228E+10 0.00 0.00 0.00 0.00 3992.73 02-JUL-08:61 3699.13 07-JUL-18:02 0.00 0.00 0.00
August 0.138083E+10 0.00 603.26 0.893057E+09 0.00 0.00 0.00 0.00 4114.21 13-AUG-08:61 3817.01 10-AUG-18:02 0.00 0.00 0.00
September 0.303287E+09 0.00 181.97 0.214719E+09 0.00 0.00 0.00 0.00 3610.09 02-SEP-18:02 3610.09 02-SEP-18:02 0.00 0.00 0.00
October 13826183.21 0.00 11.13 9834766.70 0.00 0.00 0.00 0.00 3341.28 13-OCT-15:02 3341.28 13-OCT-15:02 0.00 0.00 0.00
November 159680.41 0.00 0.33 159680.41 0.00 0.00 0.00 0.00 290.20 08-NOV-16:04 290.20 08-NOV-16:04 0.00 0.00 0.00
December 137731.89 0.00 0.21 93612.51 0.00 0.00 0.00 0.00 560.92 24-DEC-09:04 299.28 24-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.758475E+10 0.00 2971.69 0.564884E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 137731.89 0.00 0.21 93612.51 0.00 0.00 0.00 0.00 290.20   216.63   0.00 0.00 0.00
Maximum of Months 0.195159E+10 0.00 672.64 0.143864E+10 0.00 0.00 0.00 0.00 4114.21   3834.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 173670.09 0.00 0.24 112167.29 0.00 0.00 0.00 0.00 370.15 22-JAN-09:04 294.69 21-JAN-09:04 0.00 0.00 0.00
February 796325.23 0.00 0.74 678278.04 0.00 0.00 0.00 0.00 682.33 09-FEB-09:04 519.65 08-FEB-19:04 0.00 0.00 0.00
March 3408816.74 0.00 2.37 3270803.40 0.00 0.00 0.00 0.00 1423.93 28-MAR-15:03 1423.93 28-MAR-15:03 0.00 0.00 0.00
April 0.350095E+09 0.00 152.76 0.345432E+09 0.00 0.00 0.00 0.00 3175.42 28-APR-15:02 3175.42 28-APR-15:02 0.00 0.00 0.00
May 0.685509E+09 0.00 414.08 0.616840E+09 0.00 0.00 0.00 0.00 4148.01 14-MAY-20:22 4148.01 14-MAY-20:22 0.00 0.00 0.00
June 0.134120E+10 0.00 504.44 0.905775E+09 0.00 0.00 0.00 0.00 4353.89 28-JUN-21:32 3909.15 28-JUN-21:32 0.00 0.00 0.00
July 0.132905E+10 0.00 510.39 0.804292E+09 0.00 0.00 0.00 0.00 4176.96 24-JUL-21:51 4099.24 06-JUL-17:32 0.00 0.00 0.00
August 0.729695E+09 0.00 427.11 0.396401E+09 0.00 0.00 0.00 0.00 3893.24 02-AUG-21:51 3393.88 09-AUG-21:51 0.00 0.00 0.00
September 98911381.87 0.00 86.12 64189273.39 0.00 0.00 0.00 0.00 3355.38 02-SEP-19:41 3355.38 02-SEP-19:41 0.00 0.00 0.00
October 4516792.09 0.00 2.38 3532129.72 0.00 0.00 0.00 0.00 1416.78 05-OCT-15:03 1237.69 05-OCT-15:03 0.00 0.00 0.00
November 67155.43 0.00 0.24 67155.43 0.00 0.00 0.00 0.00 314.48 04-NOV-08:04 314.48 04-NOV-08:04 0.00 0.00 0.00
December 136795.02 0.00 0.21 114374.37 0.00 0.00 0.00 0.00 526.80 24-DEC-09:04 349.46 24-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.454357E+10 0.00 2101.09 0.314070E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 67155.43 0.00 0.21 67155.43 0.00 0.00 0.00 0.00 314.48   294.69   0.00 0.00 0.00
Maximum of Months 0.134120E+10 0.00 510.39 0.905775E+09 0.00 0.00 0.00 0.00 4353.89   4148.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 8409693.45 0.00 1.14 8409693.45 0.00 0.00 0.00 0.00 4983.22 22-JAN-19:04 4983.22 22-JAN-19:04 0.00 0.00 0.00
February 0.279524E+09 0.00 36.00 0.256650E+09 0.00 0.00 0.00 0.00 21517.02 15-FEB-16:01 21517.02 15-FEB-16:01 0.00 0.00 0.00
March 0.245093E+10 0.00 162.86 0.241849E+10 0.00 0.00 0.00 0.00 21526.63 11-MAR-16:02 21526.63 11-MAR-16:02 0.00 0.00 0.00
April 0.698283E+10 0.00 443.87 0.682567E+10 0.00 0.00 0.00 0.00 21529.82 16-APR-15:02 21529.82 16-APR-15:02 0.00 0.00 0.00
May 0.917696E+10 0.00 653.16 0.840453E+10 0.00 0.00 0.00 0.00 22712.64 31-MAY-18:02 22712.64 31-MAY-18:02 0.00 0.00 0.00
June 0.111255E+11 0.00 665.02 0.797320E+10 0.00 0.00 0.00 0.00 23294.56 24-JUN-15:01 23082.09 22-JUN-18:02 0.00 0.00 0.00
July 0.122088E+11 0.00 689.48 0.765276E+10 0.00 0.00 0.00 0.00 23223.98 13-JUL-18:02 23223.98 13-JUL-18:02 0.00 0.00 0.00
August 0.106150E+11 0.00 666.75 0.708060E+10 0.00 0.00 0.00 0.00 22979.15 10-AUG-18:02 22979.15 10-AUG-18:02 0.00 0.00 0.00
September 0.459990E+10 0.00 434.94 0.326781E+10 0.00 0.00 0.00 0.00 21731.89 02-SEP-18:02 21731.89 02-SEP-18:02 0.00 0.00 0.00
October 0.117305E+10 0.00 128.12 0.106236E+10 0.00 0.00 0.00 0.00 21527.98 04-OCT-15:01 21527.98 04-OCT-15:01 0.00 0.00 0.00
November 29641570.50 0.00 4.82 29641570.50 0.00 0.00 0.00 0.00 20746.62 08-NOV-16:01 20746.62 08-NOV-16:01 0.00 0.00 0.00
December 3557625.53 0.00 0.43 3364208.95 0.00 0.00 0.00 0.00 4939.09 24-DEC-19:04 4273.04 25-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.586541E+11 0.00 3886.60 0.449835E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3557625.53 0.00 0.43 3364208.95 0.00 0.00 0.00 0.00 4939.09   4273.04   0.00 0.00 0.00
Maximum of Months 0.122088E+11 0.00 689.48 0.840453E+10 0.00 0.00 0.00 0.00 23294.56   23223.98   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 178.45 118.74 59.72 104.39 999.67 0.00 0.00 0.00
February 596.34 413.90 182.44 508.29 802.61 0.00 0.00 0.00
March 1010.02 683.17 326.84 1008.31 614.68 0.00 0.00 0.00
April 1238.14 770.52 467.62 1385.95 389.15 0.00 0.00 0.00
May 1022.70 531.05 491.65 1194.76 187.18 0.00 0.00 0.00
June 929.31 379.54 549.77 1129.00 86.82 0.00 0.00 0.00
July 893.91 387.23 506.68 1114.64 90.83 0.00 0.00 0.00
August 931.01 513.72 417.28 1132.04 146.58 0.00 0.00 0.00
September 742.98 444.06 298.93 813.28 289.94 0.00 0.00 0.00
October 549.94 348.73 201.21 509.31 521.20 0.00 0.00 0.00
November 298.10 209.99 88.10 195.30 933.49 0.00 0.00 0.00
December 52.71 37.13 15.58 9.31 1112.99 0.00 0.00 0.00
                 
Annual Sum or Average 703.44 402.54 300.90 759.43 513.21 0.00 0.00 0.00
Minimum of Months 52.71 37.13 15.58 9.31 86.82 0.00 0.00 0.00
Maximum of Months 1238.14 770.52 549.77 1385.95 1112.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 502.51 334.36 168.16 291.89 2800.06 0.00 0.00 0.00
February 1679.25 1165.53 513.73 1422.82 2248.23 0.00 0.00 0.00
March 2844.14 1923.77 920.37 2823.57 1733.33 0.00 0.00 0.00
April 3486.53 2169.73 1316.80 3883.00 1121.52 0.00 0.00 0.00
May 2879.86 1495.40 1384.46 3338.45 556.39 0.00 0.00 0.00
June 2616.88 1068.77 1548.11 3147.40 266.89 0.00 0.00 0.00
July 2517.19 1090.40 1426.79 3108.38 278.20 0.00 0.00 0.00
August 2621.65 1446.61 1175.04 3163.76 442.28 0.00 0.00 0.00
September 2092.19 1250.44 841.75 2273.48 840.78 0.00 0.00 0.00
October 1548.61 982.01 566.60 1423.08 1472.70 0.00 0.00 0.00
November 839.42 591.33 248.09 545.72 2611.52 0.00 0.00 0.00
December 148.43 104.57 43.86 25.90 3113.54 0.00 0.00 0.00
                 
Annual Sum or Average 1980.83 1133.52 847.32 2122.61 1453.32 0.00 0.00 0.00
Minimum of Months 148.43 104.57 43.86 25.90 266.89 0.00 0.00 0.00
Maximum of Months 3486.53 2169.73 1548.11 3883.00 3113.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 652.79 434.35 218.44 376.96 3799.80 0.00 0.00 0.00
February 2181.45 1514.09 667.36 1857.72 3044.39 0.00 0.00 0.00
March 3694.70 2499.09 1195.62 3709.52 2348.64 0.00 0.00 0.00
April 4529.20 2818.61 1710.60 5104.53 1528.19 0.00 0.00 0.00
May 3741.10 1942.61 1798.50 4376.09 778.05 0.00 0.00 0.00
June 3399.47 1388.39 2011.09 4118.45 381.47 0.00 0.00 0.00
July 3269.98 1416.50 1853.48 4063.97 399.21 0.00 0.00 0.00
August 3405.67 1879.23 1526.44 4136.83 625.87 0.00 0.00 0.00
September 2717.87 1624.39 1093.49 2968.83 1180.64 0.00 0.00 0.00
October 2011.73 1275.68 736.05 1854.61 2033.82 0.00 0.00 0.00
November 1090.46 768.17 322.29 707.59 3541.46 0.00 0.00 0.00
December 192.82 135.84 56.98 32.69 4209.92 0.00 0.00 0.00
                 
Annual Sum or Average 2573.21 1472.50 1100.71 2778.27 1984.25 0.00 0.00 0.00
Minimum of Months 192.82 135.84 56.98 32.69 381.47 0.00 0.00 0.00
Maximum of Months 4529.20 2818.61 2011.09 5104.53 4209.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.28 23.48 11.81 21.04 200.31 0.00 0.00 0.00
February 117.91 81.84 36.07 102.41 160.31 0.00 0.00 0.00
March 199.70 135.07 64.62 201.83 123.33 0.00 0.00 0.00
April 244.80 152.34 92.46 275.33 78.33 0.00 0.00 0.00
May 202.21 105.00 97.21 236.02 37.57 0.00 0.00 0.00
June 183.74 75.04 108.70 222.94 16.86 0.00 0.00 0.00
July 176.74 76.56 100.18 220.62 17.59 0.00 0.00 0.00
August 184.08 101.57 82.50 224.33 28.78 0.00 0.00 0.00
September 146.90 87.80 59.10 161.88 57.88 0.00 0.00 0.00
October 108.73 68.95 39.78 102.16 103.97 0.00 0.00 0.00
November 58.94 41.52 17.42 39.87 185.41 0.00 0.00 0.00
December 10.42 7.34 3.08 1.94 222.17 0.00 0.00 0.00
                 
Annual Sum or Average 139.08 79.59 59.49 151.00 102.44 0.00 0.00 0.00
Minimum of Months 10.42 7.34 3.08 1.94 16.86 0.00 0.00 0.00
Maximum of Months 244.80 152.34 108.70 275.33 222.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.28 1.24 6.03 0.00 413.00 0.00 0.00 0.00
February 43.35 15.12 28.23 8.66 351.84 0.00 0.00 0.00
March 130.37 56.31 74.05 74.77 255.54 0.00 0.00 0.00
April 308.78 160.28 148.51 300.98 142.20 0.00 0.00 0.00
May 299.56 136.64 162.92 316.68 64.43 0.00 0.00 0.00
June 328.13 140.06 188.07 382.02 29.08 0.00 0.00 0.00
July 274.11 103.55 170.56 324.19 31.11 0.00 0.00 0.00
August 226.16 96.14 130.02 251.09 51.78 0.00 0.00 0.00
September 136.09 56.74 79.36 115.86 110.85 0.00 0.00 0.00
October 53.38 16.00 37.38 19.62 222.48 0.00 0.00 0.00
November 21.59 7.93 13.66 2.23 390.94 0.00 0.00 0.00
December 1.91 0.20 1.72 0.00 435.09 0.00 0.00 0.00
                 
Annual Sum or Average 152.95 65.99 86.96 150.28 207.45 0.00 0.00 0.00
Minimum of Months 1.91 0.20 1.72 0.00 29.08 0.00 0.00 0.00
Maximum of Months 328.13 160.28 188.07 382.02 435.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.83 0.00 2.83 0.00 222.27 0.00 0.00 0.00
February 12.51 0.00 12.51 0.00 197.67 0.00 0.00 0.00
March 33.50 0.01 33.49 3.08 146.69 0.00 0.00 0.00
April 61.18 1.76 59.42 25.67 77.27 0.00 0.00 0.00
May 93.56 15.03 78.53 76.96 30.23 0.00 0.00 0.00
June 121.11 26.89 94.22 125.37 12.51 0.00 0.00 0.00
July 102.40 17.14 85.27 110.28 14.93 0.00 0.00 0.00
August 66.00 3.97 62.03 58.58 27.07 0.00 0.00 0.00
September 36.38 0.12 36.26 15.83 60.80 0.00 0.00 0.00
October 17.60 0.00 17.60 1.48 123.64 0.00 0.00 0.00
November 5.46 0.00 5.46 0.00 216.04 0.00 0.00 0.00
December 0.86 0.00 0.86 0.00 232.55 0.00 0.00 0.00
                 
Annual Sum or Average 46.28 5.43 40.85 34.98 113.02 0.00 0.00 0.00
Minimum of Months 0.86 0.00 0.86 0.00 12.51 0.00 0.00 0.00
Maximum of Months 121.11 26.89 94.22 125.37 232.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.28 1.24 6.03 0.00 413.03 0.00 0.00 0.00
February 43.35 15.12 28.23 9.23 350.99 0.00 0.00 0.00
March 130.37 56.31 74.05 77.81 252.68 0.00 0.00 0.00
April 308.78 160.28 148.51 306.64 140.23 0.00 0.00 0.00
May 299.56 136.64 162.92 316.90 64.20 0.00 0.00 0.00
June 328.13 140.06 188.07 376.36 29.68 0.00 0.00 0.00
July 274.11 103.55 170.56 320.59 32.09 0.00 0.00 0.00
August 226.16 96.14 130.02 250.41 53.04 0.00 0.00 0.00
September 136.09 56.74 79.36 118.70 109.37 0.00 0.00 0.00
October 53.38 16.00 37.38 20.98 220.85 0.00 0.00 0.00
November 21.59 7.93 13.66 2.36 390.73 0.00 0.00 0.00
December 1.91 0.20 1.72 0.00 435.05 0.00 0.00 0.00
                 
Annual Sum or Average 152.95 65.99 86.96 150.60 206.92 0.00 0.00 0.00
Minimum of Months 1.91 0.20 1.72 0.00 29.68 0.00 0.00 0.00
Maximum of Months 328.13 160.28 188.07 376.36 435.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 28.22 18.78 9.44 18.06 141.55 0.00 0.00 0.00
February 94.31 65.46 28.85 83.73 116.77 0.00 0.00 0.00
March 159.73 108.04 51.69 156.20 106.74 0.00 0.00 0.00
April 195.80 121.85 73.95 210.57 78.88 0.00 0.00 0.00
May 161.73 83.98 77.75 178.42 43.34 0.00 0.00 0.00
June 146.96 60.02 86.94 166.32 23.28 0.00 0.00 0.00
July 141.37 61.24 80.13 164.60 24.21 0.00 0.00 0.00
August 147.23 81.24 65.99 169.20 35.98 0.00 0.00 0.00
September 117.50 70.22 47.27 120.34 63.44 0.00 0.00 0.00
October 86.97 55.15 31.82 76.01 95.40 0.00 0.00 0.00
November 47.14 33.21 13.93 33.87 131.61 0.00 0.00 0.00
December 8.34 5.87 2.46 1.83 157.98 0.00 0.00 0.00
                 
Annual Sum or Average 111.24 63.66 47.59 114.99 84.79 0.00 0.00 0.00
Minimum of Months 8.34 5.87 2.46 1.83 23.28 0.00 0.00 0.00
Maximum of Months 195.80 121.85 86.94 210.57 157.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.26 0.00 2.26 0.00 182.65 0.00 0.00 0.00
February 10.01 0.00 10.01 0.00 162.97 0.00 0.00 0.00
March 26.80 0.00 26.80 2.08 120.94 0.00 0.00 0.00
April 48.95 1.41 47.54 21.12 62.02 0.00 0.00 0.00
May 74.86 12.02 62.83 64.28 23.67 0.00 0.00 0.00
June 96.90 21.52 75.38 104.81 9.41 0.00 0.00 0.00
July 81.93 13.71 68.22 91.49 11.34 0.00 0.00 0.00
August 52.81 3.18 49.63 49.09 20.82 0.00 0.00 0.00
September 29.11 0.10 29.01 12.49 49.66 0.00 0.00 0.00
October 14.09 0.00 14.09 0.96 102.99 0.00 0.00 0.00
November 4.37 0.00 4.37 0.00 177.79 0.00 0.00 0.00
December 0.69 0.00 0.69 0.00 190.88 0.00 0.00 0.00
                 
Annual Sum or Average 37.03 4.35 32.68 29.03 92.55 0.00 0.00 0.00
Minimum of Months 0.69 0.00 0.69 0.00 9.41 0.00 0.00 0.00
Maximum of Months 96.90 21.52 75.38 104.81 190.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.66 5.81 9.85 2.03 403.48 0.00 0.00 0.00
February 81.17 38.93 42.24 42.80 334.73 0.00 0.00 0.00
March 227.53 115.19 112.35 195.50 249.16 0.00 0.00 0.00
April 302.68 153.28 149.40 284.46 133.26 0.00 0.00 0.00
May 440.73 248.70 192.03 500.44 60.27 0.00 0.00 0.00
June 403.68 188.47 215.21 480.47 25.10 0.00 0.00 0.00
July 384.47 186.89 197.57 470.00 28.38 0.00 0.00 0.00
August 308.91 151.33 157.58 359.16 49.05 0.00 0.00 0.00
September 193.37 87.44 105.93 187.82 107.48 0.00 0.00 0.00
October 104.76 42.45 62.31 77.28 212.45 0.00 0.00 0.00
November 21.73 7.91 13.83 1.64 389.82 0.00 0.00 0.00
December 3.10 0.74 2.36 0.00 433.12 0.00 0.00 0.00
                 
Annual Sum or Average 208.10 102.71 105.40 217.99 201.52 0.00 0.00 0.00
Minimum of Months 3.10 0.74 2.36 0.00 25.10 0.00 0.00 0.00
Maximum of Months 440.73 248.70 215.21 500.44 433.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.28 23.48 11.81 20.96 200.36 0.00 0.00 0.00
February 117.91 81.84 36.07 101.80 160.51 0.00 0.00 0.00
March 199.70 135.07 64.62 199.50 123.95 0.00 0.00 0.00
April 244.80 152.34 92.46 274.27 77.94 0.00 0.00 0.00
May 202.21 105.00 97.21 234.15 37.12 0.00 0.00 0.00
June 183.74 75.04 108.70 222.02 16.02 0.00 0.00 0.00
July 176.74 76.56 100.18 219.33 17.17 0.00 0.00 0.00
August 184.08 101.57 82.50 223.21 28.71 0.00 0.00 0.00
September 146.90 87.80 59.10 160.61 58.15 0.00 0.00 0.00
October 108.73 68.95 39.78 101.06 104.38 0.00 0.00 0.00
November 58.94 41.52 17.42 39.82 185.40 0.00 0.00 0.00
December 10.42 7.34 3.08 1.94 222.19 0.00 0.00 0.00
                 
Annual Sum or Average 139.08 79.59 59.49 150.02 102.38 0.00 0.00 0.00
Minimum of Months 10.42 7.34 3.08 1.94 16.02 0.00 0.00 0.00
Maximum of Months 244.80 152.34 108.70 274.27 222.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.83 0.00 2.83 0.00 222.07 0.00 0.00 0.00
February 12.51 0.00 12.51 0.00 197.45 0.00 0.00 0.00
March 33.50 0.01 33.49 2.54 148.28 0.00 0.00 0.00
April 61.18 1.76 59.42 24.41 77.27 0.00 0.00 0.00
May 93.56 15.03 78.53 74.93 30.05 0.00 0.00 0.00
June 121.11 26.89 94.22 125.48 12.22 0.00 0.00 0.00
July 102.40 17.14 85.27 108.69 14.79 0.00 0.00 0.00
August 66.00 3.97 62.03 57.52 26.81 0.00 0.00 0.00
September 36.38 0.12 36.26 14.65 61.49 0.00 0.00 0.00
October 17.60 0.00 17.60 1.23 124.28 0.00 0.00 0.00
November 5.46 0.00 5.46 0.00 216.08 0.00 0.00 0.00
December 0.86 0.00 0.86 0.00 232.52 0.00 0.00 0.00
                 
Annual Sum or Average 46.28 5.43 40.85 34.32 113.16 0.00 0.00 0.00
Minimum of Months 0.86 0.00 0.86 0.00 12.22 0.00 0.00 0.00
Maximum of Months 121.11 26.89 94.22 125.48 232.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.66 5.81 9.85 2.08 403.03 0.00 0.00 0.00
February 81.17 38.93 42.24 43.43 332.72 0.00 0.00 0.00
March 227.53 115.19 112.35 197.83 244.71 0.00 0.00 0.00
April 302.68 153.28 149.40 288.72 130.76 0.00 0.00 0.00
May 440.73 248.70 192.03 501.68 60.54 0.00 0.00 0.00
June 403.68 188.47 215.21 478.00 26.70 0.00 0.00 0.00
July 384.47 186.89 197.57 466.90 30.08 0.00 0.00 0.00
August 308.91 151.33 157.58 359.63 50.28 0.00 0.00 0.00
September 193.37 87.44 105.93 189.95 105.84 0.00 0.00 0.00
October 104.76 42.45 62.31 78.49 210.08 0.00 0.00 0.00
November 21.73 7.91 13.83 1.68 389.52 0.00 0.00 0.00
December 3.10 0.74 2.36 0.00 432.98 0.00 0.00 0.00
                 
Annual Sum or Average 208.10 102.71 105.40 218.55 200.78 0.00 0.00 0.00
Minimum of Months 3.10 0.74 2.36 0.00 26.70 0.00 0.00 0.00
Maximum of Months 440.73 248.70 215.21 501.68 432.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.58 0.00 3.58 0.00 294.87 0.00 0.00 0.00
February 15.84 0.00 15.84 0.00 263.64 0.00 0.00 0.00
March 42.42 0.01 42.42 3.04 196.02 0.00 0.00 0.00
April 77.48 2.22 75.25 31.51 101.89 0.00 0.00 0.00
May 118.49 19.03 99.45 97.71 40.88 0.00 0.00 0.00
June 153.38 34.06 119.32 160.59 17.54 0.00 0.00 0.00
July 129.69 21.70 107.98 140.14 20.95 0.00 0.00 0.00
August 83.58 5.03 78.55 74.08 36.85 0.00 0.00 0.00
September 46.07 0.15 45.92 18.95 81.63 0.00 0.00 0.00
October 22.30 0.00 22.30 1.50 166.11 0.00 0.00 0.00
November 6.92 0.00 6.92 0.00 287.23 0.00 0.00 0.00
December 1.09 0.00 1.09 0.00 308.12 0.00 0.00 0.00
                 
Annual Sum or Average 58.61 6.88 51.73 44.22 150.71 0.00 0.00 0.00
Minimum of Months 1.09 0.00 1.09 0.00 17.54 0.00 0.00 0.00
Maximum of Months 153.38 34.06 119.32 160.59 308.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1.32 0.00 1.32 0.00 108.69 0.00 0.00 0.00
February 5.84 0.00 5.84 0.00 97.19 0.00 0.00 0.00
March 15.64 0.00 15.64 1.12 72.26 0.00 0.00 0.00
April 28.56 0.82 27.74 11.62 37.56 0.00 0.00 0.00
May 43.68 7.02 36.66 36.02 15.07 0.00 0.00 0.00
June 56.54 12.56 43.99 59.20 6.47 0.00 0.00 0.00
July 47.81 8.00 39.81 51.66 7.72 0.00 0.00 0.00
August 30.81 1.85 28.96 27.31 13.59 0.00 0.00 0.00
September 16.98 0.06 16.93 6.99 30.09 0.00 0.00 0.00
October 8.22 0.00 8.22 0.55 61.24 0.00 0.00 0.00
November 2.55 0.00 2.55 0.00 105.88 0.00 0.00 0.00
December 0.40 0.00 0.40 0.00 113.55 0.00 0.00 0.00
                 
Annual Sum or Average 21.61 2.54 19.07 16.30 55.55 0.00 0.00 0.00
Minimum of Months 0.40 0.00 0.40 0.00 6.47 0.00 0.00 0.00
Maximum of Months 56.54 12.56 43.99 59.20 113.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.46 10.95 5.51 9.40 97.79 0.00 0.00 0.00
February 55.01 38.18 16.83 46.88 77.85 0.00 0.00 0.00
March 93.18 63.03 30.15 93.79 59.29 0.00 0.00 0.00
April 114.22 71.08 43.14 129.48 37.42 0.00 0.00 0.00
May 94.35 48.99 45.36 110.58 19.01 0.00 0.00 0.00
June 85.73 35.01 50.72 103.64 9.41 0.00 0.00 0.00
July 82.47 35.72 46.74 102.51 9.78 0.00 0.00 0.00
August 85.89 47.39 38.50 104.81 15.07 0.00 0.00 0.00
September 68.54 40.97 27.58 75.84 28.14 0.00 0.00 0.00
October 50.73 32.17 18.56 47.14 50.50 0.00 0.00 0.00
November 27.50 19.37 8.13 17.85 90.26 0.00 0.00 0.00
December 4.86 3.43 1.44 0.81 108.56 0.00 0.00 0.00
                 
Annual Sum or Average 64.90 37.14 27.76 70.29 50.13 0.00 0.00 0.00
Minimum of Months 4.86 3.43 1.44 0.81 9.41 0.00 0.00 0.00
Maximum of Months 114.22 71.08 50.72 129.48 108.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 29.73 14.95 25.52 265.41 0.00 0.00 0.00
February 149.32 103.64 45.68 127.23 211.29 0.00 0.00 0.00
March 252.91 171.06 81.84 254.57 160.93 0.00 0.00 0.00
April 310.03 192.94 117.09 351.43 101.58 0.00 0.00 0.00
May 256.08 132.97 123.11 300.14 51.60 0.00 0.00 0.00
June 232.70 95.04 137.66 281.30 25.55 0.00 0.00 0.00
July 223.83 96.96 126.87 278.25 26.54 0.00 0.00 0.00
August 233.12 128.63 104.49 284.47 40.89 0.00 0.00 0.00
September 186.04 111.19 74.85 205.84 76.37 0.00 0.00 0.00
October 137.70 87.32 50.38 127.94 137.07 0.00 0.00 0.00
November 74.64 52.58 22.06 48.46 244.98 0.00 0.00 0.00
December 13.20 9.30 3.90 2.19 294.64 0.00 0.00 0.00
                 
Annual Sum or Average 176.14 100.79 75.34 190.79 136.06 0.00 0.00 0.00
Minimum of Months 13.20 9.30 3.90 2.19 25.55 0.00 0.00 0.00
Maximum of Months 310.03 192.94 137.66 351.43 294.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.28 23.48 11.81 21.15 198.97 0.00 0.00 0.00
February 117.91 81.84 36.07 102.88 159.14 0.00 0.00 0.00
March 199.70 135.07 64.62 202.22 122.63 0.00 0.00 0.00
April 244.80 152.34 92.46 274.85 77.97 0.00 0.00 0.00
May 202.21 105.00 97.21 235.26 37.24 0.00 0.00 0.00
June 183.74 75.04 108.70 222.04 16.63 0.00 0.00 0.00
July 176.74 76.56 100.18 219.82 17.34 0.00 0.00 0.00
August 184.08 101.57 82.50 223.75 28.43 0.00 0.00 0.00
September 146.90 87.80 59.10 161.98 57.22 0.00 0.00 0.00
October 108.73 68.95 39.78 102.55 103.17 0.00 0.00 0.00
November 58.94 41.52 17.42 40.22 183.63 0.00 0.00 0.00
December 10.42 7.34 3.08 1.97 220.71 0.00 0.00 0.00
                 
Annual Sum or Average 139.08 79.59 59.49 150.85 101.65 0.00 0.00 0.00
Minimum of Months 10.42 7.34 3.08 1.97 16.63 0.00 0.00 0.00
Maximum of Months 244.80 152.34 108.70 274.85 220.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.28 1.24 6.03 0.00 410.27 0.00 0.00 0.00
February 43.35 15.12 28.23 8.91 348.96 0.00 0.00 0.00
March 130.37 56.31 74.05 75.22 253.56 0.00 0.00 0.00
April 308.78 160.28 148.51 300.03 141.32 0.00 0.00 0.00
May 299.56 136.64 162.92 315.62 63.77 0.00 0.00 0.00
June 328.13 140.06 188.07 380.52 28.63 0.00 0.00 0.00
July 274.11 103.55 170.56 322.95 30.62 0.00 0.00 0.00
August 226.16 96.14 130.02 250.26 51.06 0.00 0.00 0.00
September 136.09 56.74 79.36 116.13 109.36 0.00 0.00 0.00
October 53.38 16.00 37.38 20.06 220.41 0.00 0.00 0.00
November 21.59 7.93 13.66 2.33 387.00 0.00 0.00 0.00
December 1.91 0.20 1.72 0.00 432.26 0.00 0.00 0.00
                 
Annual Sum or Average 152.95 65.99 86.96 149.94 205.70 0.00 0.00 0.00
Minimum of Months 1.91 0.20 1.72 0.00 28.63 0.00 0.00 0.00
Maximum of Months 328.13 160.28 188.07 380.52 432.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.83 0.00 2.83 0.00 220.91 0.00 0.00 0.00
February 12.51 0.00 12.51 0.00 196.32 0.00 0.00 0.00
March 33.50 0.01 33.49 3.22 145.78 0.00 0.00 0.00
April 61.18 1.76 59.42 25.99 76.81 0.00 0.00 0.00
May 93.56 15.03 78.53 76.75 30.12 0.00 0.00 0.00
June 121.11 26.89 94.22 124.34 12.59 0.00 0.00 0.00
July 102.40 17.14 85.27 109.55 14.98 0.00 0.00 0.00
August 66.00 3.97 62.03 58.40 27.04 0.00 0.00 0.00
September 36.38 0.12 36.26 16.28 59.83 0.00 0.00 0.00
October 17.60 0.00 17.60 1.63 122.61 0.00 0.00 0.00
November 5.46 0.00 5.46 0.00 214.03 0.00 0.00 0.00
December 0.86 0.00 0.86 0.00 231.07 0.00 0.00 0.00
                 
Annual Sum or Average 46.28 5.43 40.85 34.89 112.23 0.00 0.00 0.00
Minimum of Months 0.86 0.00 0.86 0.00 12.59 0.00 0.00 0.00
Maximum of Months 121.11 26.89 94.22 124.34 231.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.28 1.24 6.03 0.00 410.33 0.00 0.00 0.00
February 43.35 15.12 28.23 9.36 348.47 0.00 0.00 0.00
March 130.37 56.31 74.05 78.15 251.19 0.00 0.00 0.00
April 308.78 160.28 148.51 306.30 139.26 0.00 0.00 0.00
May 299.56 136.64 162.92 315.74 63.69 0.00 0.00 0.00
June 328.13 140.06 188.07 373.81 29.73 0.00 0.00 0.00
July 274.11 103.55 170.56 318.66 32.03 0.00 0.00 0.00
August 226.16 96.14 130.02 249.31 52.74 0.00 0.00 0.00
September 136.09 56.74 79.36 119.45 107.68 0.00 0.00 0.00
October 53.38 16.00 37.38 21.43 219.06 0.00 0.00 0.00
November 21.59 7.93 13.66 2.44 386.87 0.00 0.00 0.00
December 1.91 0.20 1.72 0.00 432.24 0.00 0.00 0.00
                 
Annual Sum or Average 152.95 65.99 86.96 150.15 205.38 0.00 0.00 0.00
Minimum of Months 1.91 0.20 1.72 0.00 29.73 0.00 0.00 0.00
Maximum of Months 328.13 160.28 188.07 373.81 432.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.75 34.43 17.32 30.01 296.28 0.00 0.00 0.00
February 172.92 120.02 52.90 146.02 238.74 0.00 0.00 0.00
March 292.88 198.10 94.78 289.42 184.75 0.00 0.00 0.00
April 359.03 223.43 135.60 399.04 115.93 0.00 0.00 0.00
May 296.56 153.99 142.57 343.81 54.65 0.00 0.00 0.00
June 269.47 110.06 159.42 326.36 23.94 0.00 0.00 0.00
July 259.21 112.28 146.92 322.54 25.16 0.00 0.00 0.00
August 269.97 148.97 121.00 326.99 41.79 0.00 0.00 0.00
September 215.44 128.76 86.68 233.97 86.22 0.00 0.00 0.00
October 159.47 101.12 58.35 145.61 155.80 0.00 0.00 0.00
November 86.44 60.89 25.55 57.01 273.71 0.00 0.00 0.00
December 15.28 10.77 4.52 2.76 328.11 0.00 0.00 0.00
                 
Annual Sum or Average 203.98 116.72 87.25 218.84 151.68 0.00 0.00 0.00
Minimum of Months 15.28 10.77 4.52 2.76 23.94 0.00 0.00 0.00
Maximum of Months 359.03 223.43 159.42 399.04 328.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.80 0.00 19.80 0.00 1636.66 0.00 0.00 0.00
February 87.53 0.00 87.53 0.00 1467.88 0.00 0.00 0.00
March 234.48 0.04 234.44 13.56 1118.38 0.00 0.00 0.00
April 428.23 12.29 415.94 159.47 596.55 0.00 0.00 0.00
May 654.88 105.19 549.69 518.68 232.22 0.00 0.00 0.00
June 847.73 188.24 659.49 879.34 96.55 0.00 0.00 0.00
July 716.79 119.95 596.84 766.27 115.15 0.00 0.00 0.00
August 461.98 27.81 434.18 397.04 206.90 0.00 0.00 0.00
September 254.65 0.84 253.81 92.12 486.43 0.00 0.00 0.00
October 123.23 0.00 123.23 5.39 972.29 0.00 0.00 0.00
November 38.24 0.00 38.24 0.00 1589.03 0.00 0.00 0.00
December 6.01 0.00 6.01 0.00 1698.49 0.00 0.00 0.00
                 
Annual Sum or Average 323.97 38.04 285.93 237.42 848.06 0.00 0.00 0.00
Minimum of Months 6.01 0.00 6.01 0.00 96.55 0.00 0.00 0.00
Maximum of Months 847.73 188.24 659.49 879.34 1698.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.80 0.00 19.80 0.00 1662.73 0.00 0.00 0.00
February 87.53 0.00 87.53 0.00 1492.91 0.00 0.00 0.00
March 234.48 0.04 234.44 11.82 1141.51 0.00 0.00 0.00
April 428.23 12.29 415.94 151.55 609.82 0.00 0.00 0.00
May 654.88 105.19 549.69 507.64 236.93 0.00 0.00 0.00
June 847.73 188.24 659.49 870.37 99.06 0.00 0.00 0.00
July 716.79 119.95 596.84 757.93 118.15 0.00 0.00 0.00
August 461.98 27.81 434.18 388.48 212.18 0.00 0.00 0.00
September 254.65 0.84 253.81 86.14 500.32 0.00 0.00 0.00
October 123.23 0.00 123.23 4.30 995.83 0.00 0.00 0.00
November 38.24 0.00 38.24 0.00 1615.24 0.00 0.00 0.00
December 6.01 0.00 6.01 0.00 1723.80 0.00 0.00 0.00
                 
Annual Sum or Average 323.97 38.04 285.93 232.92 864.00 0.00 0.00 0.00
Minimum of Months 6.01 0.00 6.01 0.00 99.06 0.00 0.00 0.00
Maximum of Months 847.73 188.24 659.49 870.37 1723.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2.83 0.00 2.83 0.00 189.85 0.00 0.00 0.00
February 12.51 0.00 12.51 0.01 166.19 0.00 0.00 0.00
March 33.50 0.01 33.49 8.41 123.46 0.00 0.00 0.00
April 61.18 1.76 59.42 49.09 68.20 0.00 0.00 0.00
May 93.56 15.03 78.53 114.59 29.03 0.00 0.00 0.00
June 121.11 26.89 94.22 171.68 12.62 0.00 0.00 0.00
July 102.40 17.14 85.27 154.95 14.51 0.00 0.00 0.00
August 66.00 3.97 62.03 97.58 23.88 0.00 0.00 0.00
September 36.38 0.12 36.26 37.09 48.07 0.00 0.00 0.00
October 17.60 0.00 17.60 5.88 99.93 0.00 0.00 0.00
November 5.46 0.00 5.46 0.00 182.93 0.00 0.00 0.00
December 0.86 0.00 0.86 0.00 199.58 0.00 0.00 0.00
                 
Annual Sum or Average 46.28 5.43 40.85 53.59 96.15 0.00 0.00 0.00
Minimum of Months 0.86 0.00 0.86 0.00 12.62 0.00 0.00 0.00
Maximum of Months 121.11 26.89 94.22 171.68 199.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.32 11.62 19.70 7.46 689.89 0.00 0.00 0.00
February 162.33 77.85 84.47 109.33 570.03 0.00 0.00 0.00
March 455.04 230.36 224.68 449.77 425.00 0.00 0.00 0.00
April 605.32 306.54 298.78 686.34 240.71 0.00 0.00 0.00
May 881.40 497.37 384.03 1148.04 111.95 0.00 0.00 0.00
June 807.30 376.92 430.38 1124.01 50.08 0.00 0.00 0.00
July 768.88 373.76 395.12 1103.92 55.88 0.00 0.00 0.00
August 617.77 302.63 315.14 870.55 89.46 0.00 0.00 0.00
September 386.71 174.87 211.84 480.84 176.05 0.00 0.00 0.00
October 209.51 84.89 124.62 198.23 350.96 0.00 0.00 0.00
November 43.47 15.81 27.65 7.00 658.98 0.00 0.00 0.00
December 6.19 1.47 4.72 0.00 744.33 0.00 0.00 0.00
                 
Annual Sum or Average 416.17 205.40 210.78 518.15 345.83 0.00 0.00 0.00
Minimum of Months 6.19 1.47 4.72 0.00 50.08 0.00 0.00 0.00
Maximum of Months 881.40 497.37 430.38 1148.04 744.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.28 23.48 11.81 25.41 172.11 0.00 0.00 0.00
February 117.91 81.84 36.07 114.20 139.11 0.00 0.00 0.00
March 199.70 135.07 64.62 221.52 109.57 0.00 0.00 0.00
April 244.80 152.34 92.46 305.22 69.33 0.00 0.00 0.00
May 202.21 105.00 97.21 272.66 33.84 0.00 0.00 0.00
June 183.74 75.04 108.70 265.63 16.55 0.00 0.00 0.00
July 176.74 76.56 100.18 263.05 17.12 0.00 0.00 0.00
August 184.08 101.57 82.50 262.53 25.15 0.00 0.00 0.00
September 146.90 87.80 59.10 189.27 47.64 0.00 0.00 0.00
October 108.73 68.95 39.78 117.80 88.86 0.00 0.00 0.00
November 58.94 41.52 17.42 47.09 158.78 0.00 0.00 0.00
December 10.42 7.34 3.08 3.11 190.47 0.00 0.00 0.00
                 
Annual Sum or Average 139.08 79.59 59.49 174.14 88.81 0.00 0.00 0.00
Minimum of Months 10.42 7.34 3.08 3.11 16.55 0.00 0.00 0.00
Maximum of Months 244.80 152.34 108.70 305.22 190.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.58 0.00 3.58 0.00 294.85 0.00 0.00 0.00
February 15.84 0.00 15.84 0.00 264.09 0.00 0.00 0.00
March 42.42 0.01 42.42 2.77 197.82 0.00 0.00 0.00
April 77.48 2.22 75.25 29.93 102.57 0.00 0.00 0.00
May 118.49 19.03 99.45 95.95 40.72 0.00 0.00 0.00
June 153.38 34.06 119.32 157.66 17.76 0.00 0.00 0.00
July 129.69 21.70 107.98 137.16 21.33 0.00 0.00 0.00
August 83.58 5.03 78.55 72.02 37.07 0.00 0.00 0.00
September 46.07 0.15 45.92 18.14 82.22 0.00 0.00 0.00
October 22.30 0.00 22.30 1.31 168.26 0.00 0.00 0.00
November 6.92 0.00 6.92 0.00 286.36 0.00 0.00 0.00
December 1.09 0.00 1.09 0.00 307.64 0.00 0.00 0.00
                 
Annual Sum or Average 58.61 6.88 51.73 43.17 151.12 0.00 0.00 0.00
Minimum of Months 1.09 0.00 1.09 0.00 17.76 0.00 0.00 0.00
Maximum of Months 153.38 34.06 119.32 157.66 307.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3.21 0.00 3.21 0.00 263.80 0.00 0.00 0.00
February 14.17 0.00 14.17 0.00 236.22 0.00 0.00 0.00
March 37.96 0.01 37.95 2.48 176.99 0.00 0.00 0.00
April 69.32 1.99 67.33 26.78 91.77 0.00 0.00 0.00
May 106.01 17.03 88.98 85.85 36.43 0.00 0.00 0.00
June 137.23 30.47 106.76 141.06 15.89 0.00 0.00 0.00
July 116.03 19.42 96.61 122.72 19.09 0.00 0.00 0.00
August 74.78 4.50 70.28 64.43 33.16 0.00 0.00 0.00
September 41.22 0.14 41.09 16.23 73.56 0.00 0.00 0.00
October 19.95 0.00 19.95 1.17 150.51 0.00 0.00 0.00
November 6.19 0.00 6.19 0.00 256.20 0.00 0.00 0.00
December 0.97 0.00 0.97 0.00 275.25 0.00 0.00 0.00
                 
Annual Sum or Average 52.44 6.16 46.29 38.63 135.20 0.00 0.00 0.00
Minimum of Months 0.97 0.00 0.97 0.00 15.89 0.00 0.00 0.00
Maximum of Months 137.23 30.47 106.76 141.06 275.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 131.72 87.64 44.08 74.97 782.64 0.00 0.00 0.00
February 440.18 305.52 134.66 373.72 623.62 0.00 0.00 0.00
March 745.53 504.28 241.26 745.46 477.43 0.00 0.00 0.00
April 913.92 568.75 345.17 1027.99 300.46 0.00 0.00 0.00
May 754.90 391.99 362.91 877.65 151.39 0.00 0.00 0.00
June 685.96 280.15 405.81 819.53 76.44 0.00 0.00 0.00
July 659.83 285.83 374.00 810.42 79.87 0.00 0.00 0.00
August 687.21 379.20 308.01 831.06 121.52 0.00 0.00 0.00
September 548.42 327.77 220.65 602.13 226.32 0.00 0.00 0.00
October 405.94 257.41 148.52 373.47 408.59 0.00 0.00 0.00
November 220.04 155.00 65.03 142.84 720.20 0.00 0.00 0.00
December 38.91 27.41 11.50 6.48 867.82 0.00 0.00 0.00
                 
Annual Sum or Average 519.23 297.13 222.11 557.65 402.00 0.00 0.00 0.00
Minimum of Months 38.91 27.41 11.50 6.48 76.44 0.00 0.00 0.00
Maximum of Months 913.92 568.75 405.81 1027.99 867.82 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.477969E+09 0.318027E+09 0.159942E+09 0.279606E+09 0.267752E+10
February 0.144266E+10 0.100132E+10 0.441347E+09 0.122965E+10 0.194168E+10
March 0.270523E+10 0.182981E+10 0.875421E+09 0.270065E+10 0.164635E+10
April 0.320927E+10 0.199719E+10 0.121208E+10 0.359238E+10 0.100867E+10
May 0.273921E+10 0.142236E+10 0.131684E+10 0.320004E+10 0.501355E+09
June 0.240877E+10 0.983773E+09 0.142500E+10 0.292637E+10 0.225039E+09
July 0.239425E+10 0.103715E+10 0.135710E+10 0.298546E+10 0.243274E+09
August 0.249361E+10 0.137596E+10 0.111765E+10 0.303206E+10 0.392605E+09
September 0.192581E+10 0.115100E+10 0.774815E+09 0.210803E+10 0.751531E+09
October 0.147297E+10 0.934043E+09 0.538928E+09 0.136414E+10 0.139597E+10
November 0.772670E+09 0.544306E+09 0.228364E+09 0.506214E+09 0.241962E+10
December 0.141180E+09 99460103.64 41719703.73 24938342.03 0.298104E+10
           
Annual Sum or Average 0.221836E+11 0.126944E+11 0.948921E+10 0.239495E+11 0.161846E+11
Minimum of Months 0.141180E+09 99460103.64 41719703.73 24938342.03 0.225039E+09
Maximum of Months 0.320927E+10 0.199719E+10 0.142500E+10 0.359238E+10 0.298104E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134593E+10 0.895543E+09 0.450387E+09 0.781804E+09 0.749969E+10
February 0.406245E+10 0.281964E+10 0.124281E+10 0.344208E+10 0.543893E+10
March 0.761775E+10 0.515262E+10 0.246513E+10 0.756266E+10 0.464255E+10
April 0.903709E+10 0.562395E+10 0.341314E+10 0.100647E+11 0.290699E+10
May 0.771342E+10 0.400528E+10 0.370815E+10 0.894170E+10 0.149025E+10
June 0.678295E+10 0.277024E+10 0.401271E+10 0.815805E+10 0.691776E+09
July 0.674205E+10 0.292054E+10 0.382151E+10 0.832547E+10 0.745137E+09
August 0.702183E+10 0.387461E+10 0.314722E+10 0.847381E+10 0.118460E+10
September 0.542296E+10 0.324113E+10 0.218183E+10 0.589286E+10 0.217929E+10
October 0.414779E+10 0.263020E+10 0.151759E+10 0.381159E+10 0.394447E+10
November 0.217579E+10 0.153273E+10 0.643057E+09 0.141449E+10 0.676905E+10
December 0.397553E+09 0.280073E+09 0.117480E+09 69364993.15 0.833930E+10
           
Annual Sum or Average 0.624676E+11 0.357466E+11 0.267210E+11 0.669386E+11 0.458320E+11
Minimum of Months 0.397553E+09 0.280073E+09 0.117480E+09 69364993.15 0.691776E+09
Maximum of Months 0.903709E+10 0.562395E+10 0.401271E+10 0.100647E+11 0.833930E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174844E+10 0.116336E+10 0.585078E+09 0.100964E+10 0.101774E+11
February 0.527735E+10 0.366288E+10 0.161447E+10 0.449420E+10 0.736499E+10
March 0.989589E+10 0.669355E+10 0.320234E+10 0.993558E+10 0.629061E+10
April 0.117397E+11 0.730582E+10 0.443386E+10 0.132310E+11 0.396107E+10
May 0.100202E+11 0.520308E+10 0.481709E+10 0.117209E+11 0.208392E+10
June 0.881144E+10 0.359870E+10 0.521274E+10 0.106750E+11 0.988771E+09
July 0.875830E+10 0.379395E+10 0.496436E+10 0.108849E+11 0.106924E+10
August 0.912176E+10 0.503334E+10 0.408842E+10 0.110801E+11 0.167632E+10
September 0.704473E+10 0.421041E+10 0.283432E+10 0.769521E+10 0.306021E+10
October 0.538822E+10 0.341678E+10 0.197143E+10 0.496738E+10 0.544738E+10
November 0.282647E+10 0.199110E+10 0.835368E+09 0.183408E+10 0.917947E+10
December 0.516444E+09 0.363831E+09 0.152613E+09 87559714.80 0.112758E+11
           
Annual Sum or Average 0.811489E+11 0.464368E+11 0.347121E+11 0.876155E+11 0.625752E+11
Minimum of Months 0.516444E+09 0.363831E+09 0.152613E+09 87559714.80 0.988771E+09
Maximum of Months 0.117397E+11 0.730582E+10 0.521274E+10 0.132310E+11 0.112758E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94502736.66 62879372.15 31623364.51 56350517.08 0.536510E+09
February 0.285240E+09 0.197978E+09 87262226.49 0.247750E+09 0.387826E+09
March 0.534871E+09 0.361785E+09 0.173087E+09 0.540579E+09 0.330335E+09
April 0.634529E+09 0.394878E+09 0.239651E+09 0.713667E+09 0.203034E+09
May 0.541590E+09 0.281225E+09 0.260365E+09 0.632169E+09 0.100638E+09
June 0.476258E+09 0.194509E+09 0.281749E+09 0.577857E+09 43707274.24
July 0.473386E+09 0.205062E+09 0.268324E+09 0.590911E+09 47102833.67
August 0.493030E+09 0.272051E+09 0.220980E+09 0.600832E+09 77088253.03
September 0.380767E+09 0.227572E+09 0.153195E+09 0.419584E+09 0.150023E+09
October 0.291232E+09 0.184676E+09 0.106556E+09 0.273626E+09 0.278482E+09
November 0.152770E+09 0.107619E+09 45151531.58 0.103331E+09 0.480588E+09
December 27913686.84 19664970.70 8248716.14 5196737.03 0.595068E+09
           
Annual Sum or Average 0.438609E+10 0.250990E+10 0.187619E+10 0.476185E+10 0.323040E+10
Minimum of Months 27913686.84 19664970.70 8248716.14 5196737.03 43707274.24
Maximum of Months 0.634529E+09 0.394878E+09 0.281749E+09 0.713667E+09 0.595068E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19486793.32 3327943.48 16158849.85 0.00 0.110619E+10
February 0.104877E+09 36576040.05 68300506.74 20943770.21 0.851180E+09
March 0.349173E+09 0.150831E+09 0.198342E+09 0.200251E+09 0.684449E+09
April 0.800370E+09 0.415440E+09 0.384929E+09 0.780132E+09 0.368584E+09
May 0.802333E+09 0.365965E+09 0.436368E+09 0.848196E+09 0.172559E+09
June 0.850519E+09 0.363039E+09 0.487480E+09 0.990200E+09 75374990.17
July 0.734165E+09 0.277339E+09 0.456826E+09 0.868316E+09 83329643.53
August 0.605748E+09 0.257506E+09 0.348242E+09 0.672512E+09 0.138688E+09
September 0.352757E+09 0.147061E+09 0.205696E+09 0.300321E+09 0.287321E+09
October 0.142970E+09 42849611.93 0.100120E+09 52553188.73 0.595896E+09
November 55952411.84 20544393.39 35408018.44 5790128.72 0.101331E+10
December 5123481.58 522824.73 4600656.85 0.00 0.116533E+10
           
Annual Sum or Average 0.482347E+10 0.208100E+10 0.274247E+10 0.473921E+10 0.654221E+10
Minimum of Months 5123481.58 522824.73 4600656.85 0.00 75374990.17
Maximum of Months 0.850519E+09 0.415440E+09 0.487480E+09 0.990200E+09 0.116533E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7577117.11 0.00 7577117.11 0.00 0.595333E+09
February 30253127.37 0.00 30253127.37 0.00 0.478191E+09
March 89721695.70 15520.03 89706175.66 8245737.05 0.392887E+09
April 0.158573E+09 4551800.57 0.154022E+09 66535924.48 0.200287E+09
May 0.250585E+09 40250733.32 0.210335E+09 0.206139E+09 80978113.94
June 0.313916E+09 69706027.16 0.244210E+09 0.324955E+09 32432335.33
July 0.274275E+09 45899189.55 0.228375E+09 0.295363E+09 39998703.97
August 0.176774E+09 10639562.35 0.166135E+09 0.156891E+09 72517206.78
September 94295413.67 309320.54 93986093.13 41030026.31 0.157602E+09
October 47152640.75 0.00 47152640.75 3969015.33 0.331154E+09
November 14161091.87 0.00 14161091.87 0.00 0.559979E+09
December 2298499.28 0.00 2298499.28 0.00 0.622853E+09
           
Annual Sum or Average 0.145958E+10 0.171372E+09 0.128821E+10 0.110313E+10 0.356421E+10
Minimum of Months 2298499.28 0.00 2298499.28 0.00 32432335.33
Maximum of Months 0.313916E+09 69706027.16 0.244210E+09 0.324955E+09 0.622853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19486793.32 3327943.48 16158849.85 0.00 0.110625E+10
February 0.104877E+09 36576040.05 68300506.74 22324717.89 0.849119E+09
March 0.349173E+09 0.150831E+09 0.198342E+09 0.208406E+09 0.676781E+09
April 0.800370E+09 0.415440E+09 0.384929E+09 0.794806E+09 0.363488E+09
May 0.802333E+09 0.365965E+09 0.436368E+09 0.848786E+09 0.171950E+09
June 0.850519E+09 0.363039E+09 0.487480E+09 0.975513E+09 76938022.60
July 0.734165E+09 0.277339E+09 0.456826E+09 0.858672E+09 85939409.90
August 0.605748E+09 0.257506E+09 0.348242E+09 0.670705E+09 0.142062E+09
September 0.352757E+09 0.147061E+09 0.205696E+09 0.307676E+09 0.283485E+09
October 0.142970E+09 42849611.93 0.100120E+09 56191446.64 0.591531E+09
November 55952411.84 20544393.39 35408018.44 6118014.26 0.101276E+10
December 5123481.58 522824.73 4600656.85 0.00 0.116524E+10
           
Annual Sum or Average 0.482347E+10 0.208100E+10 0.274247E+10 0.474920E+10 0.652555E+10
Minimum of Months 5123481.58 522824.73 4600656.85 0.00 76938022.60
Maximum of Months 0.850519E+09 0.415440E+09 0.487480E+09 0.975513E+09 0.116524E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 75587157.08 50293495.70 25293661.38 48379921.37 0.379130E+09
February 0.228147E+09 0.158351E+09 69795900.67 0.202571E+09 0.282488E+09
March 0.427812E+09 0.289370E+09 0.138442E+09 0.418367E+09 0.285886E+09
April 0.507522E+09 0.315840E+09 0.191683E+09 0.545800E+09 0.204468E+09
May 0.433186E+09 0.224936E+09 0.208250E+09 0.477876E+09 0.116077E+09
June 0.380931E+09 0.155576E+09 0.225355E+09 0.431103E+09 60347924.49
July 0.378634E+09 0.164017E+09 0.214617E+09 0.440872E+09 64855482.50
August 0.394346E+09 0.217597E+09 0.176749E+09 0.453191E+09 96362685.54
September 0.304553E+09 0.182021E+09 0.122532E+09 0.311916E+09 0.164426E+09
October 0.232939E+09 0.147712E+09 85227669.47 0.203584E+09 0.255518E+09
November 0.122192E+09 86077848.02 36114043.15 87793737.94 0.341126E+09
December 22326509.33 15728848.52 6597660.82 4911067.09 0.423135E+09
           
Annual Sum or Average 0.350818E+10 0.200752E+10 0.150066E+10 0.362636E+10 0.267382E+10
Minimum of Months 22326509.33 15728848.52 6597660.82 4911067.09 60347924.49
Maximum of Months 0.507522E+09 0.315840E+09 0.225355E+09 0.545800E+09 0.423135E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 6062497.20 0.00 6062497.20 0.00 0.489216E+09
February 24205710.07 0.00 24205710.07 0.00 0.394266E+09
March 71786871.05 12417.67 71774453.38 5580920.24 0.323918E+09
April 0.126876E+09 3641923.15 0.123234E+09 54744836.60 0.160760E+09
May 0.200495E+09 32204855.03 0.168290E+09 0.172162E+09 63387346.84
June 0.251166E+09 55772213.67 0.195394E+09 0.271659E+09 24387097.91
July 0.219449E+09 36724219.00 0.182725E+09 0.245040E+09 30383642.75
August 0.141438E+09 8512778.15 0.132926E+09 0.131486E+09 55770069.12
September 75446330.45 247489.23 75198841.21 32376635.22 0.128713E+09
October 37727112.88 0.00 37727112.88 2570903.27 0.275846E+09
November 11330375.20 0.00 11330375.20 0.00 0.460837E+09
December 1839043.17 0.00 1839043.17 0.00 0.511259E+09
           
Annual Sum or Average 0.116782E+10 0.137116E+09 0.103071E+10 0.915620E+09 0.291874E+10
Minimum of Months 1839043.17 0.00 1839043.17 0.00 24387097.91
Maximum of Months 0.251166E+09 55772213.67 0.195394E+09 0.271659E+09 0.511259E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41945160.70 15564344.25 26380816.45 5432305.48 0.108068E+10
February 0.196367E+09 94179516.98 0.102187E+09 0.103540E+09 0.809771E+09
March 0.609430E+09 0.308519E+09 0.300910E+09 0.523630E+09 0.667359E+09
April 0.784554E+09 0.397306E+09 0.387248E+09 0.737314E+09 0.345415E+09
May 0.118045E+10 0.666122E+09 0.514328E+09 0.134037E+10 0.161434E+09
June 0.104634E+10 0.488518E+09 0.557817E+09 0.124538E+10 65064246.89
July 0.102976E+10 0.500573E+09 0.529183E+09 0.125886E+10 76002569.07
August 0.827373E+09 0.405310E+09 0.422063E+09 0.961968E+09 0.131378E+09
September 0.501214E+09 0.226654E+09 0.274561E+09 0.486819E+09 0.278600E+09
October 0.280596E+09 0.113695E+09 0.166901E+09 0.206975E+09 0.569035E+09
November 56335260.54 20493623.86 35841636.68 4239047.01 0.101041E+10
December 8291630.75 1972674.86 6318955.89 0.00 0.116007E+10
           
Annual Sum or Average 0.656265E+10 0.323891E+10 0.332374E+10 0.687453E+10 0.635521E+10
Minimum of Months 8291630.75 1972674.86 6318955.89 0.00 65064246.89
Maximum of Months 0.118045E+10 0.666122E+09 0.557817E+09 0.134037E+10 0.116007E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94502736.66 62879372.15 31623364.51 56144461.15 0.536654E+09
February 0.285240E+09 0.197978E+09 87262226.49 0.246273E+09 0.388313E+09
March 0.534871E+09 0.361785E+09 0.173087E+09 0.534344E+09 0.331979E+09
April 0.634529E+09 0.394878E+09 0.239651E+09 0.710912E+09 0.202019E+09
May 0.541590E+09 0.281225E+09 0.260365E+09 0.627147E+09 99420447.65
June 0.476258E+09 0.194509E+09 0.281749E+09 0.575468E+09 41536207.00
July 0.473386E+09 0.205062E+09 0.268324E+09 0.587465E+09 45982338.04
August 0.493030E+09 0.272051E+09 0.220980E+09 0.597837E+09 76890705.02
September 0.380767E+09 0.227572E+09 0.153195E+09 0.416294E+09 0.150729E+09
October 0.291232E+09 0.184676E+09 0.106556E+09 0.270685E+09 0.279561E+09
November 0.152770E+09 0.107619E+09 45151531.58 0.103211E+09 0.480564E+09
December 27913686.84 19664970.70 8248716.14 5188192.34 0.595107E+09
           
Annual Sum or Average 0.438609E+10 0.250990E+10 0.187619E+10 0.473097E+10 0.322876E+10
Minimum of Months 27913686.84 19664970.70 8248716.14 5188192.34 41536207.00
Maximum of Months 0.634529E+09 0.394878E+09 0.281749E+09 0.710912E+09 0.595107E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7577117.11 0.00 7577117.11 0.00 0.594790E+09
February 30253127.37 0.00 30253127.37 0.00 0.477669E+09
March 89721695.70 15520.03 89706175.66 6802717.49 0.397149E+09
April 0.158573E+09 4551800.57 0.154022E+09 63263038.87 0.200280E+09
May 0.250585E+09 40250733.32 0.210335E+09 0.200703E+09 80477406.30
June 0.313916E+09 69706027.16 0.244210E+09 0.325245E+09 31672399.17
July 0.274275E+09 45899189.55 0.228375E+09 0.291118E+09 39606715.66
August 0.176774E+09 10639562.35 0.166135E+09 0.154072E+09 71796340.45
September 94295413.67 309320.54 93986093.13 37973908.75 0.159375E+09
October 47152640.75 0.00 47152640.75 3281734.48 0.332876E+09
November 14161091.87 0.00 14161091.87 0.00 0.560067E+09
December 2298499.28 0.00 2298499.28 0.00 0.622780E+09
           
Annual Sum or Average 0.145958E+10 0.171372E+09 0.128821E+10 0.108246E+10 0.356854E+10
Minimum of Months 2298499.28 0.00 2298499.28 0.00 31672399.17
Maximum of Months 0.313916E+09 69706027.16 0.244210E+09 0.325245E+09 0.622780E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41945160.70 15564344.25 26380816.45 5564510.74 0.107948E+10
February 0.196367E+09 94179516.98 0.102187E+09 0.105076E+09 0.804926E+09
March 0.609430E+09 0.308519E+09 0.300910E+09 0.529866E+09 0.655429E+09
April 0.784554E+09 0.397306E+09 0.387248E+09 0.748369E+09 0.338939E+09
May 0.118045E+10 0.666122E+09 0.514328E+09 0.134371E+10 0.162151E+09
June 0.104634E+10 0.488518E+09 0.557817E+09 0.123898E+10 69195507.81
July 0.102976E+10 0.500573E+09 0.529183E+09 0.125056E+10 80560861.84
August 0.827373E+09 0.405310E+09 0.422063E+09 0.963225E+09 0.134664E+09
September 0.501214E+09 0.226654E+09 0.274561E+09 0.492351E+09 0.274337E+09
October 0.280596E+09 0.113695E+09 0.166901E+09 0.210218E+09 0.562674E+09
November 56335260.54 20493623.86 35841636.68 4365800.65 0.100964E+10
December 8291630.75 1972674.86 6318955.89 0.00 0.115969E+10
           
Annual Sum or Average 0.656265E+10 0.323891E+10 0.332374E+10 0.689228E+10 0.633169E+10
Minimum of Months 8291630.75 1972674.86 6318955.89 0.00 69195507.81
Maximum of Months 0.118045E+10 0.666122E+09 0.557817E+09 0.134371E+10 0.115969E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 9595940.73 0.00 9595940.73 0.00 0.789785E+09
February 38313676.95 0.00 38313676.95 0.00 0.637806E+09
March 0.113627E+09 19655.14 0.113607E+09 8135475.56 0.525010E+09
April 0.200823E+09 5764568.21 0.195059E+09 81672978.55 0.264089E+09
May 0.317350E+09 50975014.07 0.266375E+09 0.261718E+09 0.109484E+09
June 0.397554E+09 88278285.19 0.309276E+09 0.416250E+09 45469860.42
July 0.347351E+09 58128427.49 0.289223E+09 0.375338E+09 56125683.94
August 0.223874E+09 13474334.39 0.210399E+09 0.198406E+09 98711720.31
September 0.119419E+09 391734.95 0.119027E+09 49125274.55 0.211577E+09
October 59715844.34 0.00 59715844.34 4006230.04 0.444920E+09
November 17934129.34 0.00 17934129.34 0.00 0.744488E+09
December 2910904.31 0.00 2910904.31 0.00 0.825257E+09
           
Annual Sum or Average 0.184847E+10 0.217032E+09 0.163144E+10 0.139465E+10 0.475272E+10
Minimum of Months 2910904.31 0.00 2910904.31 0.00 45469860.42
Maximum of Months 0.397554E+09 88278285.19 0.309276E+09 0.416250E+09 0.825257E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 3537461.09 0.00 3537461.09 0.00 0.291118E+09
February 14124007.77 0.00 14124007.77 0.00 0.235122E+09
March 41887567.90 7245.70 41880322.20 2999073.16 0.193541E+09
April 74031794.50 2125058.54 71906735.96 30108041.70 97354319.59
May 0.116988E+09 18791500.90 98196996.68 96480273.57 40360441.16
June 0.146555E+09 32543031.24 0.114012E+09 0.153447E+09 16762073.31
July 0.128048E+09 21428545.28 0.106620E+09 0.138365E+09 20690251.08
August 82529134.27 4967197.59 77561936.69 73140778.89 36389227.44
September 44022858.82 144409.72 43878449.10 18109610.32 77996155.62
October 22013732.86 0.00 22013732.86 1476862.28 0.164016E+09
November 6611262.67 0.00 6611262.67 0.00 0.274430E+09
December 1073079.86 0.00 1073079.86 0.00 0.304133E+09
           
Annual Sum or Average 0.681423E+09 80006988.96 0.601416E+09 0.514127E+09 0.175191E+10
Minimum of Months 1073079.86 0.00 1073079.86 0.00 16762073.31
Maximum of Months 0.146555E+09 32543031.24 0.114012E+09 0.153447E+09 0.304133E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44094596.11 29339261.66 14755334.45 25185578.68 0.261914E+09
February 0.133092E+09 92375560.58 40716203.24 0.113405E+09 0.188327E+09
March 0.249569E+09 0.168807E+09 80761524.82 0.251216E+09 0.158809E+09
April 0.296069E+09 0.184249E+09 0.111820E+09 0.335607E+09 97002184.65
May 0.252704E+09 0.131219E+09 0.121485E+09 0.296183E+09 50919046.00
June 0.222220E+09 90757038.88 0.131463E+09 0.268639E+09 24397337.65
July 0.220880E+09 95681062.38 0.125199E+09 0.274576E+09 26186163.55
August 0.230046E+09 0.126938E+09 0.103108E+09 0.280720E+09 40350594.16
September 0.177664E+09 0.106184E+09 71480204.43 0.196569E+09 72936017.08
October 0.135888E+09 86169245.54 49718494.62 0.126249E+09 0.135259E+09
November 71281978.28 50214455.59 21067522.69 46278131.18 0.233955E+09
December 13024413.80 9175596.09 3848817.71 2164604.04 0.290755E+09
           
Annual Sum or Average 0.204653E+10 0.117111E+10 0.875424E+09 0.221679E+10 0.158081E+10
Minimum of Months 13024413.80 9175596.09 3848817.71 2164604.04 24397337.65
Maximum of Months 0.296069E+09 0.184249E+09 0.131463E+09 0.335607E+09 0.290755E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119682E+09 79632757.36 40048995.83 68358812.13 0.710887E+09
February 0.361238E+09 0.250726E+09 0.110512E+09 0.307804E+09 0.511157E+09
March 0.677381E+09 0.458178E+09 0.219203E+09 0.681851E+09 0.431041E+09
April 0.803591E+09 0.500088E+09 0.303503E+09 0.910907E+09 0.263284E+09
May 0.685890E+09 0.356154E+09 0.329736E+09 0.803901E+09 0.138205E+09
June 0.603151E+09 0.246333E+09 0.356818E+09 0.729142E+09 66219364.76
July 0.599514E+09 0.259698E+09 0.339816E+09 0.745254E+09 71074604.14
August 0.624392E+09 0.344535E+09 0.279857E+09 0.761931E+09 0.109520E+09
September 0.482217E+09 0.288205E+09 0.194012E+09 0.533528E+09 0.197963E+09
October 0.368827E+09 0.233881E+09 0.134946E+09 0.342667E+09 0.367121E+09
November 0.193474E+09 0.136292E+09 57181565.84 0.125608E+09 0.635000E+09
December 35350923.13 24904444.60 10446478.53 5875178.12 0.789167E+09
           
Annual Sum or Average 0.555471E+10 0.317863E+10 0.237608E+10 0.601683E+10 0.429064E+10
Minimum of Months 35350923.13 24904444.60 10446478.53 5875178.12 66219364.76
Maximum of Months 0.803591E+09 0.500088E+09 0.356818E+09 0.910907E+09 0.789167E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94502736.66 62879372.15 31623364.51 56648308.90 0.532930E+09
February 0.285240E+09 0.197978E+09 87262226.49 0.248883E+09 0.384987E+09
March 0.534871E+09 0.361785E+09 0.173087E+09 0.541633E+09 0.328465E+09
April 0.634529E+09 0.394878E+09 0.239651E+09 0.712412E+09 0.202087E+09
May 0.541590E+09 0.281225E+09 0.260365E+09 0.630111E+09 99730843.07
June 0.476258E+09 0.194509E+09 0.281749E+09 0.575531E+09 43105113.26
July 0.473386E+09 0.205062E+09 0.268324E+09 0.588778E+09 46444752.52
August 0.493030E+09 0.272051E+09 0.220980E+09 0.599301E+09 76148217.41
September 0.380767E+09 0.227572E+09 0.153195E+09 0.419848E+09 0.148316E+09
October 0.291232E+09 0.184676E+09 0.106556E+09 0.274667E+09 0.276325E+09
November 0.152770E+09 0.107619E+09 45151531.58 0.104238E+09 0.475967E+09
December 27913686.84 19664970.70 8248716.14 5279374.08 0.591159E+09
           
Annual Sum or Average 0.438609E+10 0.250990E+10 0.187619E+10 0.475733E+10 0.320566E+10
Minimum of Months 27913686.84 19664970.70 8248716.14 5279374.08 43105113.26
Maximum of Months 0.634529E+09 0.394878E+09 0.281749E+09 0.712412E+09 0.591159E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19486793.32 3327943.48 16158849.85 0.00 0.109886E+10
February 0.104877E+09 36576040.05 68300506.74 21563116.69 0.844199E+09
March 0.349173E+09 0.150831E+09 0.198342E+09 0.201463E+09 0.679127E+09
April 0.800370E+09 0.415440E+09 0.384929E+09 0.777672E+09 0.366305E+09
May 0.802333E+09 0.365965E+09 0.436368E+09 0.845370E+09 0.170796E+09
June 0.850519E+09 0.363039E+09 0.487480E+09 0.986295E+09 74209080.81
July 0.734165E+09 0.277339E+09 0.456826E+09 0.864980E+09 82020215.93
August 0.605748E+09 0.257506E+09 0.348242E+09 0.670296E+09 0.136751E+09
September 0.352757E+09 0.147061E+09 0.205696E+09 0.301003E+09 0.283453E+09
October 0.142970E+09 42849611.93 0.100120E+09 53717907.07 0.590339E+09
November 55952411.84 20544393.39 35408018.44 6037173.43 0.100310E+10
December 5123481.58 522824.73 4600656.85 0.00 0.115777E+10
           
Annual Sum or Average 0.482347E+10 0.208100E+10 0.274247E+10 0.472840E+10 0.648693E+10
Minimum of Months 5123481.58 522824.73 4600656.85 0.00 74209080.81
Maximum of Months 0.850519E+09 0.415440E+09 0.487480E+09 0.986295E+09 0.115777E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7577117.11 0.00 7577117.11 0.00 0.591692E+09
February 30253127.37 0.00 30253127.37 0.00 0.474941E+09
March 89721695.70 15520.03 89706175.66 8635273.23 0.390465E+09
April 0.158573E+09 4551800.57 0.154022E+09 67363800.74 0.199099E+09
May 0.250585E+09 40250733.32 0.210335E+09 0.205564E+09 80674807.34
June 0.313916E+09 69706027.16 0.244210E+09 0.322287E+09 32620451.97
July 0.274275E+09 45899189.55 0.228375E+09 0.293407E+09 40122513.34
August 0.176774E+09 10639562.35 0.166135E+09 0.156414E+09 72435963.69
September 94295413.67 309320.54 93986093.13 42208042.94 0.155070E+09
October 47152640.75 0.00 47152640.75 4371493.34 0.328396E+09
November 14161091.87 0.00 14161091.87 0.00 0.554768E+09
December 2298499.28 0.00 2298499.28 0.00 0.618892E+09
           
Annual Sum or Average 0.145958E+10 0.171372E+09 0.128821E+10 0.110025E+10 0.353918E+10
Minimum of Months 2298499.28 0.00 2298499.28 0.00 32620451.97
Maximum of Months 0.313916E+09 69706027.16 0.244210E+09 0.322287E+09 0.618892E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19486793.32 3327943.48 16158849.85 0.00 0.109904E+10
February 0.104877E+09 36576040.05 68300506.74 22651762.74 0.843024E+09
March 0.349173E+09 0.150831E+09 0.198342E+09 0.209329E+09 0.672797E+09
April 0.800370E+09 0.415440E+09 0.384929E+09 0.793923E+09 0.360953E+09
May 0.802333E+09 0.365965E+09 0.436368E+09 0.845672E+09 0.170586E+09
June 0.850519E+09 0.363039E+09 0.487480E+09 0.968910E+09 77054220.78
July 0.734165E+09 0.277339E+09 0.456826E+09 0.853511E+09 85792833.01
August 0.605748E+09 0.257506E+09 0.348242E+09 0.667743E+09 0.141262E+09
September 0.352757E+09 0.147061E+09 0.205696E+09 0.309618E+09 0.279098E+09
October 0.142970E+09 42849611.93 0.100120E+09 57395662.96 0.586728E+09
November 55952411.84 20544393.39 35408018.44 6334855.59 0.100277E+10
December 5123481.58 522824.73 4600656.85 0.00 0.115771E+10
           
Annual Sum or Average 0.482347E+10 0.208100E+10 0.274247E+10 0.473509E+10 0.647681E+10
Minimum of Months 5123481.58 522824.73 4600656.85 0.00 77054220.78
Maximum of Months 0.850519E+09 0.415440E+09 0.487480E+09 0.968910E+09 0.115771E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138597E+09 92218633.81 46378698.96 80384615.70 0.793551E+09
February 0.418332E+09 0.290353E+09 0.127978E+09 0.353258E+09 0.577567E+09
March 0.784440E+09 0.530592E+09 0.253848E+09 0.775181E+09 0.494843E+09
April 0.930598E+09 0.579127E+09 0.351471E+09 0.103430E+10 0.300503E+09
May 0.794294E+09 0.412444E+09 0.381850E+09 0.920853E+09 0.146382E+09
June 0.698478E+09 0.285266E+09 0.413213E+09 0.845928E+09 62052231.31
July 0.694266E+09 0.300743E+09 0.393523E+09 0.863901E+09 67376693.26
August 0.723076E+09 0.398988E+09 0.324088E+09 0.875812E+09 0.111925E+09
September 0.558431E+09 0.333756E+09 0.224675E+09 0.606444E+09 0.223492E+09
October 0.427120E+09 0.270846E+09 0.156274E+09 0.390015E+09 0.417290E+09
November 0.224052E+09 0.157833E+09 66219054.27 0.147776E+09 0.709450E+09
December 40938100.64 28840566.79 12097533.86 7403500.21 0.878814E+09
           
Annual Sum or Average 0.643262E+10 0.368101E+10 0.275162E+10 0.690126E+10 0.478325E+10
Minimum of Months 40938100.64 28840566.79 12097533.86 7403500.21 62052231.31
Maximum of Months 0.930598E+09 0.579127E+09 0.413213E+09 0.103430E+10 0.878814E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53037810.99 0.00 53037810.99 0.00 0.438363E+10
February 0.211764E+09 0.00 0.211764E+09 0.00 0.355110E+10
March 0.628028E+09 108636.11 0.627919E+09 36320873.45 0.299546E+10
April 0.110997E+10 31861397.22 0.107811E+10 0.413338E+09 0.154627E+10
May 0.175403E+10 0.281744E+09 0.147229E+10 0.138923E+10 0.621982E+09
June 0.219733E+10 0.487924E+09 0.170940E+10 0.227925E+10 0.250265E+09
July 0.191985E+10 0.321282E+09 0.159857E+10 0.205237E+10 0.308413E+09
August 0.123737E+10 74474115.76 0.116290E+10 0.106343E+10 0.554150E+09
September 0.660043E+09 2165161.78 0.657878E+09 0.238784E+09 0.126084E+10
October 0.330056E+09 0.00 0.330056E+09 14423248.61 0.260418E+10
November 99123888.81 0.00 99123888.81 0.00 0.411877E+10
December 16088885.60 0.00 16088885.60 0.00 0.454923E+10
           
Annual Sum or Average 0.102167E+11 0.119956E+10 0.901713E+10 0.748715E+10 0.267443E+11
Minimum of Months 16088885.60 0.00 16088885.60 0.00 0.250265E+09
Maximum of Months 0.219733E+10 0.487924E+09 0.170940E+10 0.227925E+10 0.454923E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53037810.99 0.00 53037810.99 0.00 0.445346E+10
February 0.211764E+09 0.00 0.211764E+09 0.00 0.361164E+10
March 0.628028E+09 108636.11 0.627919E+09 31664141.86 0.305742E+10
April 0.110997E+10 31861397.22 0.107811E+10 0.392813E+09 0.158066E+10
May 0.175403E+10 0.281744E+09 0.147229E+10 0.135967E+10 0.634590E+09
June 0.219733E+10 0.487924E+09 0.170940E+10 0.225600E+10 0.256769E+09
July 0.191985E+10 0.321282E+09 0.159857E+10 0.203004E+10 0.316462E+09
August 0.123737E+10 74474115.76 0.116290E+10 0.104051E+10 0.568304E+09
September 0.660043E+09 2165161.78 0.657878E+09 0.223265E+09 0.129683E+10
October 0.330056E+09 0.00 0.330056E+09 11510893.98 0.266722E+10
November 99123888.81 0.00 99123888.81 0.00 0.418670E+10
December 16088885.60 0.00 16088885.60 0.00 0.461702E+10
           
Annual Sum or Average 0.102167E+11 0.119956E+10 0.901713E+10 0.734547E+10 0.272471E+11
Minimum of Months 16088885.60 0.00 16088885.60 0.00 0.256769E+09
Maximum of Months 0.219733E+10 0.487924E+09 0.170940E+10 0.225600E+10 0.461702E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 7577117.11 0.00 7577117.11 0.00 0.508484E+09
February 30253127.37 0.00 30253127.37 33464.59 0.402043E+09
March 89721695.70 15520.03 89706175.66 22522372.60 0.330684E+09
April 0.158573E+09 4551800.57 0.154022E+09 0.127235E+09 0.176776E+09
May 0.250585E+09 40250733.32 0.210335E+09 0.306919E+09 77753113.62
June 0.313916E+09 69706027.16 0.244210E+09 0.444983E+09 32723900.81
July 0.274275E+09 45899189.55 0.228375E+09 0.415018E+09 38872363.88
August 0.176774E+09 10639562.35 0.166135E+09 0.261368E+09 63970400.64
September 94295413.67 309320.54 93986093.13 96128146.54 0.124592E+09
October 47152640.75 0.00 47152640.75 15754366.43 0.267644E+09
November 14161091.87 0.00 14161091.87 0.00 0.474155E+09
December 2298499.28 0.00 2298499.28 0.00 0.534561E+09
           
Annual Sum or Average 0.145958E+10 0.171372E+09 0.128821E+10 0.168996E+10 0.303226E+10
Minimum of Months 2298499.28 0.00 2298499.28 0.00 32723900.81
Maximum of Months 0.313916E+09 69706027.16 0.244210E+09 0.444983E+09 0.534561E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 83884364.12 31126477.97 52757886.15 19968766.31 0.184781E+10
February 0.392706E+09 0.188346E+09 0.204360E+09 0.264494E+09 0.137903E+10
March 0.121877E+10 0.616995E+09 0.601778E+09 0.120465E+10 0.113831E+10
April 0.156900E+10 0.794556E+09 0.774441E+09 0.177900E+10 0.623908E+09
May 0.236073E+10 0.133215E+10 0.102858E+10 0.307491E+10 0.299850E+09
June 0.209252E+10 0.976966E+09 0.111556E+10 0.291343E+10 0.129807E+09
July 0.205937E+10 0.100108E+10 0.105829E+10 0.295673E+10 0.149658E+09
August 0.165463E+10 0.810563E+09 0.844066E+09 0.233169E+10 0.239607E+09
September 0.100236E+10 0.453276E+09 0.549082E+09 0.124634E+10 0.456311E+09
October 0.561153E+09 0.227374E+09 0.333779E+09 0.530949E+09 0.940017E+09
November 0.112663E+09 40984337.10 71678182.95 18139145.57 0.170807E+10
December 16582083.87 3945069.55 12637014.32 0.00 0.199361E+10
           
Annual Sum or Average 0.131244E+11 0.647736E+10 0.664701E+10 0.163403E+11 0.109060E+11
Minimum of Months 16582083.87 3945069.55 12637014.32 0.00 0.129807E+09
Maximum of Months 0.236073E+10 0.133215E+10 0.111556E+10 0.307491E+10 0.199361E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94502736.66 62879372.15 31623364.51 68047501.51 0.460981E+09
February 0.285240E+09 0.197978E+09 87262226.49 0.276273E+09 0.336528E+09
March 0.534871E+09 0.361785E+09 0.173087E+09 0.593322E+09 0.293462E+09
April 0.634529E+09 0.394878E+09 0.239651E+09 0.791124E+09 0.179696E+09
May 0.541590E+09 0.281225E+09 0.260365E+09 0.730300E+09 90645911.96
June 0.476258E+09 0.194509E+09 0.281749E+09 0.688515E+09 42896898.24
July 0.473386E+09 0.205062E+09 0.268324E+09 0.704565E+09 45856356.72
August 0.493030E+09 0.272051E+09 0.220980E+09 0.703166E+09 67368449.33
September 0.380767E+09 0.227572E+09 0.153195E+09 0.490598E+09 0.123475E+09
October 0.291232E+09 0.184676E+09 0.106556E+09 0.315519E+09 0.237991E+09
November 0.152770E+09 0.107619E+09 45151531.58 0.122054E+09 0.411547E+09
December 27913686.84 19664970.70 8248716.14 8333539.85 0.510158E+09
           
Annual Sum or Average 0.438609E+10 0.250990E+10 0.187619E+10 0.549182E+10 0.280060E+10
Minimum of Months 27913686.84 19664970.70 8248716.14 8333539.85 42896898.24
Maximum of Months 0.634529E+09 0.394878E+09 0.281749E+09 0.791124E+09 0.510158E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 9595940.73 0.00 9595940.73 0.00 0.789720E+09
February 38313676.95 0.00 38313676.95 0.00 0.638882E+09
March 0.113627E+09 19655.14 0.113607E+09 7418318.93 0.529853E+09
April 0.200823E+09 5764568.21 0.195059E+09 77568626.17 0.265867E+09
May 0.317350E+09 50975014.07 0.266375E+09 0.257005E+09 0.109066E+09
June 0.397554E+09 88278285.19 0.309276E+09 0.408655E+09 46022380.93
July 0.347351E+09 58128427.49 0.289223E+09 0.367370E+09 57142141.91
August 0.223874E+09 13474334.39 0.210399E+09 0.192892E+09 99275006.88
September 0.119419E+09 391734.95 0.119027E+09 47019437.15 0.213114E+09
October 59715844.34 0.00 59715844.34 3516665.89 0.450663E+09
November 17934129.34 0.00 17934129.34 0.00 0.742239E+09
December 2910904.31 0.00 2910904.31 0.00 0.823988E+09
           
Annual Sum or Average 0.184847E+10 0.217032E+09 0.163144E+10 0.136145E+10 0.476583E+10
Minimum of Months 2910904.31 0.00 2910904.31 0.00 46022380.93
Maximum of Months 0.397554E+09 88278285.19 0.309276E+09 0.408655E+09 0.823988E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 8585524.53 0.00 8585524.53 0.00 0.706565E+09
February 34279391.93 0.00 34279391.93 0.00 0.571467E+09
March 0.101662E+09 17585.53 0.101645E+09 6637198.06 0.474062E+09
April 0.179677E+09 5157581.02 0.174520E+09 69400943.74 0.237872E+09
May 0.283935E+09 45607538.23 0.238327E+09 0.229944E+09 97581412.03
June 0.355693E+09 78982916.25 0.276710E+09 0.365625E+09 41176398.60
July 0.310777E+09 52007724.32 0.258769E+09 0.328687E+09 51125290.88
August 0.200301E+09 12055538.04 0.188245E+09 0.172582E+09 88821724.80
September 0.106845E+09 350486.74 0.106494E+09 42068468.58 0.190674E+09
October 53427992.19 0.00 53427992.19 3146374.30 0.403132E+09
November 16045733.47 0.00 16045733.47 0.00 0.664083E+09
December 2604397.12 0.00 2604397.12 0.00 0.737225E+09
           
Annual Sum or Average 0.165383E+10 0.194179E+09 0.145965E+10 0.121809E+10 0.426378E+10
Minimum of Months 2604397.12 0.00 2604397.12 0.00 41176398.60
Maximum of Months 0.355693E+09 78982916.25 0.276710E+09 0.365625E+09 0.737225E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.352807E+09 0.234747E+09 0.118059E+09 0.200788E+09 0.209622E+10
February 0.106489E+10 0.739109E+09 0.325776E+09 0.904102E+09 0.150866E+10
March 0.199683E+10 0.135065E+10 0.646184E+09 0.199664E+10 0.127875E+10
April 0.236889E+10 0.147420E+10 0.894689E+09 0.266454E+10 0.778789E+09
May 0.202192E+10 0.104990E+10 0.972019E+09 0.235071E+10 0.405484E+09
June 0.177801E+10 0.726159E+09 0.105185E+10 0.212421E+10 0.198127E+09
July 0.176729E+10 0.765557E+09 0.100173E+10 0.217063E+10 0.213920E+09
August 0.184063E+10 0.101565E+10 0.824983E+09 0.222592E+10 0.325477E+09
September 0.142152E+10 0.849593E+09 0.571923E+09 0.156073E+10 0.586632E+09
October 0.108726E+10 0.689452E+09 0.397804E+09 0.100029E+10 0.109436E+10
November 0.570337E+09 0.401773E+09 0.168564E+09 0.370236E+09 0.186676E+10
December 0.104210E+09 73415195.49 30794915.36 17361581.62 0.232437E+10
           
Annual Sum or Average 0.163746E+11 0.937020E+10 0.700439E+10 0.175862E+11 0.126775E+11
Minimum of Months 0.104210E+09 73415195.49 30794915.36 17361581.62 0.198127E+09
Maximum of Months 0.236889E+10 0.147420E+10 0.105185E+10 0.266454E+10 0.232437E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 104.39 999.67 178.45 118.74 59.72 0.00 0.00
February 508.29 802.61 596.34 413.90 182.44 0.00 0.00
March 1008.31 614.68 1010.02 683.17 326.84 0.00 0.00
April 1385.95 389.15 1238.14 770.52 467.62 0.00 0.00
May 1194.76 187.18 1022.70 531.05 491.65 0.00 0.00
June 1129.00 86.82 929.31 379.54 549.77 0.00 0.00
July 1114.64 90.83 893.91 387.23 506.68 0.00 0.00
August 1132.04 146.58 931.01 513.72 417.28 0.00 0.00
September 813.28 289.94 742.98 444.06 298.93 0.00 0.00
October 509.31 521.20 549.94 348.73 201.21 0.00 0.00
November 195.30 933.49 298.10 209.99 88.10 0.00 0.00
December 9.31 1112.99 52.71 37.13 15.58 0.00 0.00
               
Annual Sum or Average 759.43 513.21 703.44 402.54 300.90 0.00 0.00
Minimum of Months 9.31 86.82 52.71 37.13 15.58 0.00 0.00
Maximum of Months 1385.95 1112.99 1238.14 770.52 549.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.89 2800.06 502.51 334.36 168.16 0.00 0.00
February 1422.82 2248.23 1679.25 1165.53 513.73 0.00 0.00
March 2823.57 1733.33 2844.14 1923.77 920.37 0.00 0.00
April 3883.00 1121.52 3486.53 2169.73 1316.80 0.00 0.00
May 3338.45 556.39 2879.86 1495.40 1384.46 0.00 0.00
June 3147.40 266.89 2616.88 1068.77 1548.11 0.00 0.00
July 3108.38 278.20 2517.19 1090.40 1426.79 0.00 0.00
August 3163.76 442.28 2621.65 1446.61 1175.04 0.00 0.00
September 2273.48 840.78 2092.19 1250.44 841.75 0.00 0.00
October 1423.08 1472.70 1548.61 982.01 566.60 0.00 0.00
November 545.72 2611.52 839.42 591.33 248.09 0.00 0.00
December 25.90 3113.54 148.43 104.57 43.86 0.00 0.00
               
Annual Sum or Average 2122.61 1453.32 1980.83 1133.52 847.32 0.00 0.00
Minimum of Months 25.90 266.89 148.43 104.57 43.86 0.00 0.00
Maximum of Months 3883.00 3113.54 3486.53 2169.73 1548.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 376.96 3799.80 652.79 434.35 218.44 0.00 0.00
February 1857.72 3044.39 2181.45 1514.09 667.36 0.00 0.00
March 3709.52 2348.64 3694.70 2499.09 1195.62 0.00 0.00
April 5104.53 1528.19 4529.20 2818.61 1710.60 0.00 0.00
May 4376.09 778.05 3741.10 1942.61 1798.50 0.00 0.00
June 4118.45 381.47 3399.47 1388.39 2011.09 0.00 0.00
July 4063.97 399.21 3269.98 1416.50 1853.48 0.00 0.00
August 4136.83 625.87 3405.67 1879.23 1526.44 0.00 0.00
September 2968.83 1180.64 2717.87 1624.39 1093.49 0.00 0.00
October 1854.61 2033.82 2011.73 1275.68 736.05 0.00 0.00
November 707.59 3541.46 1090.46 768.17 322.29 0.00 0.00
December 32.69 4209.92 192.82 135.84 56.98 0.00 0.00
               
Annual Sum or Average 2778.27 1984.25 2573.21 1472.50 1100.71 0.00 0.00
Minimum of Months 32.69 381.47 192.82 135.84 56.98 0.00 0.00
Maximum of Months 5104.53 4209.92 4529.20 2818.61 2011.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.68 597.95 42.56 24.72 17.84 0.00 0.00
February 74.97 476.06 161.26 96.96 64.30 0.00 0.00
March 254.31 356.59 330.06 191.39 138.68 0.00 0.00
April 568.63 212.85 553.59 312.62 240.96 0.00 0.00
May 550.70 100.00 501.76 241.63 260.13 0.00 0.00
June 604.19 45.18 511.87 215.10 296.77 0.00 0.00
July 544.32 48.20 450.85 180.11 270.74 0.00 0.00
August 474.39 79.53 410.24 197.71 212.52 0.00 0.00
September 274.12 165.11 283.00 144.53 138.46 0.00 0.00
October 102.11 306.78 162.11 84.95 77.16 0.00 0.00
November 21.69 555.94 80.53 49.45 31.08 0.00 0.00
December 0.00 655.32 12.33 7.54 4.80 0.00 0.00
               
Annual Sum or Average 290.51 299.12 292.03 145.58 146.46 0.00 0.00
Minimum of Months 0.00 45.18 12.33 7.54 4.80 0.00 0.00
Maximum of Months 604.19 655.32 553.59 312.62 296.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 635.30 10.10 1.24 8.86 0.00 0.00
February 4.38 543.81 55.86 15.12 40.74 0.00 0.00
March 72.33 390.81 163.86 56.32 107.54 0.00 0.00
April 327.80 213.00 369.96 162.03 207.93 0.00 0.00
May 385.94 86.51 393.11 151.66 241.45 0.00 0.00
June 496.82 37.29 449.24 166.95 282.29 0.00 0.00
July 427.71 43.86 376.51 120.68 255.82 0.00 0.00
August 305.41 76.53 292.16 100.11 192.05 0.00 0.00
September 132.23 167.87 172.47 56.86 115.62 0.00 0.00
October 19.32 341.35 70.98 16.00 54.99 0.00 0.00
November 0.87 605.28 27.05 7.93 19.12 0.00 0.00
December 0.00 667.60 2.77 0.20 2.58 0.00 0.00
               
Annual Sum or Average 181.88 316.25 199.23 71.42 127.81 0.00 0.00
Minimum of Months 0.00 37.29 2.77 0.20 2.58 0.00 0.00
Maximum of Months 496.82 667.60 449.24 166.95 282.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 18.06 141.55 28.22 18.78 9.44 0.00 0.00
February 83.73 116.77 94.31 65.46 28.85 0.00 0.00
March 156.20 106.74 159.73 108.04 51.69 0.00 0.00
April 210.57 78.88 195.80 121.85 73.95 0.00 0.00
May 178.42 43.34 161.73 83.98 77.75 0.00 0.00
June 166.32 23.28 146.96 60.02 86.94 0.00 0.00
July 164.60 24.21 141.37 61.24 80.13 0.00 0.00
August 169.20 35.98 147.23 81.24 65.99 0.00 0.00
September 120.34 63.44 117.50 70.22 47.27 0.00 0.00
October 76.01 95.40 86.97 55.15 31.82 0.00 0.00
November 33.87 131.61 47.14 33.21 13.93 0.00 0.00
December 1.83 157.98 8.34 5.87 2.46 0.00 0.00
               
Annual Sum or Average 114.99 84.79 111.24 63.66 47.59 0.00 0.00
Minimum of Months 1.83 23.28 8.34 5.87 2.46 0.00 0.00
Maximum of Months 210.57 157.98 195.80 121.85 86.94 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 182.65 2.26 0.00 2.26 0.00 0.00
February 0.00 162.97 10.01 0.00 10.01 0.00 0.00
March 2.08 120.94 26.80 0.00 26.80 0.00 0.00
April 21.12 62.02 48.95 1.41 47.54 0.00 0.00
May 64.28 23.67 74.86 12.02 62.83 0.00 0.00
June 104.81 9.41 96.90 21.52 75.38 0.00 0.00
July 91.49 11.34 81.93 13.71 68.22 0.00 0.00
August 49.09 20.82 52.81 3.18 49.63 0.00 0.00
September 12.49 49.66 29.11 0.10 29.01 0.00 0.00
October 0.96 102.99 14.09 0.00 14.09 0.00 0.00
November 0.00 177.79 4.37 0.00 4.37 0.00 0.00
December 0.00 190.88 0.69 0.00 0.69 0.00 0.00
               
Annual Sum or Average 29.03 92.55 37.03 4.35 32.68 0.00 0.00
Minimum of Months 0.00 9.41 0.69 0.00 0.69 0.00 0.00
Maximum of Months 104.81 190.88 96.90 21.52 75.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.36 593.21 50.94 29.29 21.66 0.00 0.00
February 121.09 471.73 199.08 120.77 78.31 0.00 0.00
March 376.33 354.43 427.23 250.26 176.97 0.00 0.00
April 549.63 202.10 547.49 305.63 241.86 0.00 0.00
May 729.97 92.77 642.94 353.70 289.24 0.00 0.00
June 700.36 38.99 587.42 263.51 323.91 0.00 0.00
July 687.81 44.02 561.21 263.45 297.76 0.00 0.00
August 579.76 75.16 492.98 252.90 240.08 0.00 0.00
September 343.74 160.95 340.27 175.24 165.03 0.00 0.00
October 167.26 305.75 213.50 111.40 102.10 0.00 0.00
November 20.33 554.09 80.67 49.43 31.25 0.00 0.00
December 0.00 653.37 13.52 8.08 5.44 0.00 0.00
               
Annual Sum or Average 358.82 294.72 347.18 182.29 164.89 0.00 0.00
Minimum of Months 0.00 38.99 13.52 8.08 5.44 0.00 0.00
Maximum of Months 729.97 653.37 642.94 353.70 323.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.73 623.76 18.49 5.81 12.68 0.00 0.00
February 29.66 516.40 93.68 38.93 54.75 0.00 0.00
March 183.32 375.94 261.03 115.19 145.84 0.00 0.00
April 304.88 199.79 363.86 155.04 208.82 0.00 0.00
May 575.18 89.15 534.29 263.73 270.56 0.00 0.00
June 601.99 37.42 524.79 215.36 309.42 0.00 0.00
July 574.83 44.10 486.87 204.03 282.84 0.00 0.00
August 416.47 76.40 374.91 155.30 219.61 0.00 0.00
September 199.83 162.56 229.75 87.56 142.19 0.00 0.00
October 69.78 324.43 122.37 42.45 79.92 0.00 0.00
November 0.51 604.43 27.20 7.91 19.29 0.00 0.00
December 0.00 665.50 3.95 0.74 3.22 0.00 0.00
               
Annual Sum or Average 247.88 308.94 254.38 108.14 146.24 0.00 0.00
Minimum of Months 0.00 37.42 3.95 0.74 3.22 0.00 0.00
Maximum of Months 601.99 665.50 534.29 263.73 309.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.92 747.76 66.05 40.69 25.37 0.00 0.00
February 121.78 597.65 226.01 141.82 84.19 0.00 0.00
March 316.58 452.56 404.15 234.10 170.05 0.00 0.00
April 517.50 271.91 530.29 267.06 263.23 0.00 0.00
May 534.00 116.10 512.59 208.01 304.58 0.00 0.00
June 596.53 50.76 528.35 176.66 351.69 0.00 0.00
July 567.54 59.98 483.79 162.39 321.41 0.00 0.00
August 486.56 102.29 433.41 182.91 250.50 0.00 0.00
September 302.25 210.87 317.64 152.36 165.28 0.00 0.00
October 148.35 386.14 218.95 119.49 99.46 0.00 0.00
November 33.87 695.90 111.61 71.95 39.66 0.00 0.00
December 0.12 821.98 19.55 12.72 6.82 0.00 0.00
               
Annual Sum or Average 304.26 375.09 321.26 147.35 173.91 0.00 0.00
Minimum of Months 0.12 50.76 19.55 12.72 6.82 0.00 0.00
Maximum of Months 596.53 821.98 530.29 267.06 351.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.83 593.92 42.56 24.72 17.84 0.00 0.00
February 76.19 472.50 161.26 96.96 64.30 0.00 0.00
March 255.76 354.51 330.06 191.39 138.68 0.00 0.00
April 567.25 211.65 553.59 312.62 240.96 0.00 0.00
May 548.85 98.97 501.76 241.63 260.13 0.00 0.00
June 601.79 44.49 511.87 215.10 296.77 0.00 0.00
July 542.27 47.46 450.85 180.11 270.74 0.00 0.00
August 472.99 78.46 410.24 197.71 212.52 0.00 0.00
September 274.58 163.06 283.00 144.53 138.46 0.00 0.00
October 103.34 304.31 162.11 84.95 77.16 0.00 0.00
November 22.22 550.30 80.53 49.45 31.08 0.00 0.00
December 0.00 651.00 12.33 7.54 4.80 0.00 0.00
               
Annual Sum or Average 290.16 296.72 292.03 145.58 146.46 0.00 0.00
Minimum of Months 0.00 44.49 12.33 7.54 4.80 0.00 0.00
Maximum of Months 601.79 651.00 553.59 312.62 296.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 631.25 10.10 1.24 8.86 0.00 0.00
February 4.54 539.97 55.86 15.12 40.74 0.00 0.00
March 72.96 388.55 163.86 56.32 107.54 0.00 0.00
April 327.79 211.57 369.96 162.03 207.93 0.00 0.00
May 384.74 86.06 393.11 151.66 241.45 0.00 0.00
June 493.33 37.49 449.24 166.95 282.29 0.00 0.00
July 425.13 43.93 376.51 120.68 255.82 0.00 0.00
August 304.13 76.21 292.16 100.11 192.05 0.00 0.00
September 133.51 165.28 172.47 56.86 115.62 0.00 0.00
October 20.00 338.60 70.98 16.00 54.99 0.00 0.00
November 0.90 599.36 27.05 7.93 19.12 0.00 0.00
December 0.00 663.31 2.77 0.20 2.58 0.00 0.00
               
Annual Sum or Average 181.39 313.96 199.23 71.42 127.81 0.00 0.00
Minimum of Months 0.00 37.49 2.77 0.20 2.58 0.00 0.00
Maximum of Months 493.33 663.31 449.24 166.95 282.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.01 296.28 51.75 34.43 17.32 0.00 0.00
February 146.02 238.74 172.92 120.02 52.90 0.00 0.00
March 289.42 184.75 292.88 198.10 94.78 0.00 0.00
April 399.04 115.93 359.03 223.43 135.60 0.00 0.00
May 343.81 54.65 296.56 153.99 142.57 0.00 0.00
June 326.36 23.94 269.47 110.06 159.42 0.00 0.00
July 322.54 25.16 259.21 112.28 146.92 0.00 0.00
August 326.99 41.79 269.97 148.97 121.00 0.00 0.00
September 233.97 86.22 215.44 128.76 86.68 0.00 0.00
October 145.61 155.80 159.47 101.12 58.35 0.00 0.00
November 57.01 273.71 86.44 60.89 25.55 0.00 0.00
December 2.76 328.11 15.28 10.77 4.52 0.00 0.00
               
Annual Sum or Average 218.84 151.68 203.98 116.72 87.25 0.00 0.00
Minimum of Months 2.76 23.94 15.28 10.77 4.52 0.00 0.00
Maximum of Months 399.04 328.11 359.03 223.43 159.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1636.66 19.80 0.00 19.80 0.00 0.00
February 0.00 1467.88 87.53 0.00 87.53 0.00 0.00
March 13.56 1118.38 234.48 0.04 234.44 0.00 0.00
April 159.47 596.55 428.23 12.29 415.94 0.00 0.00
May 518.68 232.22 654.88 105.19 549.69 0.00 0.00
June 879.34 96.55 847.73 188.24 659.49 0.00 0.00
July 766.27 115.15 716.79 119.95 596.84 0.00 0.00
August 397.04 206.90 461.98 27.81 434.18 0.00 0.00
September 92.12 486.43 254.65 0.84 253.81 0.00 0.00
October 5.39 972.29 123.23 0.00 123.23 0.00 0.00
November 0.00 1589.03 38.24 0.00 38.24 0.00 0.00
December 0.00 1698.49 6.01 0.00 6.01 0.00 0.00
               
Annual Sum or Average 237.42 848.06 323.97 38.04 285.93 0.00 0.00
Minimum of Months 0.00 96.55 6.01 0.00 6.01 0.00 0.00
Maximum of Months 879.34 1698.49 847.73 188.24 659.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1662.73 19.80 0.00 19.80 0.00 0.00
February 0.00 1492.91 87.53 0.00 87.53 0.00 0.00
March 11.82 1141.51 234.48 0.04 234.44 0.00 0.00
April 151.55 609.82 428.23 12.29 415.94 0.00 0.00
May 507.64 236.93 654.88 105.19 549.69 0.00 0.00
June 870.37 99.06 847.73 188.24 659.49 0.00 0.00
July 757.93 118.15 716.79 119.95 596.84 0.00 0.00
August 388.48 212.18 461.98 27.81 434.18 0.00 0.00
September 86.14 500.32 254.65 0.84 253.81 0.00 0.00
October 4.30 995.83 123.23 0.00 123.23 0.00 0.00
November 0.00 1615.24 38.24 0.00 38.24 0.00 0.00
December 0.00 1723.80 6.01 0.00 6.01 0.00 0.00
               
Annual Sum or Average 232.92 864.00 323.97 38.04 285.93 0.00 0.00
Minimum of Months 0.00 99.06 6.01 0.00 6.01 0.00 0.00
Maximum of Months 870.37 1723.80 847.73 188.24 659.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 14.79 1033.78 69.43 35.10 34.33 0.00 0.00
February 177.19 828.97 292.74 159.69 133.05 0.00 0.00
March 651.96 630.29 688.23 365.44 322.79 0.00 0.00
April 1031.26 368.85 911.30 460.64 450.66 0.00 0.00
May 1530.70 170.24 1177.16 617.39 559.77 0.00 0.00
June 1557.79 75.73 1112.15 478.85 633.30 0.00 0.00
July 1519.91 85.50 1048.02 467.46 580.57 0.00 0.00
August 1229.33 137.15 867.84 408.17 459.67 0.00 0.00
September 705.01 269.55 569.99 262.79 307.20 0.00 0.00
October 303.04 520.86 335.85 153.84 182.01 0.00 0.00
November 19.14 965.74 107.87 57.33 50.54 0.00 0.00
December 0.00 1131.27 17.47 8.81 8.66 0.00 0.00
               
Annual Sum or Average 731.78 516.68 601.54 290.42 311.12 0.00 0.00
Minimum of Months 0.00 75.73 17.47 8.81 8.66 0.00 0.00
Maximum of Months 1557.79 1131.27 1177.16 617.39 633.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 44.84 1311.16 138.51 87.64 50.87 0.00 0.00
February 297.46 1047.67 470.19 305.52 164.67 0.00 0.00
March 697.63 799.17 825.91 504.29 321.62 0.00 0.00
April 1074.71 484.83 1060.72 572.96 487.76 0.00 0.00
May 1038.59 207.67 979.39 428.05 551.34 0.00 0.00
June 1101.03 92.87 976.57 344.68 631.88 0.00 0.00
July 1059.69 109.68 905.55 326.95 578.60 0.00 0.00
August 959.53 183.76 845.58 388.73 456.85 0.00 0.00
September 628.07 373.67 635.72 328.06 307.66 0.00 0.00
October 333.31 684.71 448.18 257.41 190.77 0.00 0.00
November 92.22 1212.15 233.15 155.00 78.14 0.00 0.00
December 1.49 1445.72 40.97 27.41 13.56 0.00 0.00
               
Annual Sum or Average 612.05 660.93 630.29 310.17 320.13 0.00 0.00
Minimum of Months 1.49 92.87 40.97 27.41 13.56 0.00 0.00
Maximum of Months 1101.03 1445.72 1060.72 572.96 631.88 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.279606E+09 0.267752E+10 0.477969E+09 0.318027E+09 0.159942E+09 0.00 0.00
February 0.122965E+10 0.194168E+10 0.144266E+10 0.100132E+10 0.441347E+09 0.00 0.00
March 0.270065E+10 0.164635E+10 0.270523E+10 0.182981E+10 0.875421E+09 0.00 0.00
April 0.359238E+10 0.100867E+10 0.320927E+10 0.199719E+10 0.121208E+10 0.00 0.00
May 0.320004E+10 0.501355E+09 0.273921E+10 0.142236E+10 0.131684E+10 0.00 0.00
June 0.292637E+10 0.225039E+09 0.240877E+10 0.983773E+09 0.142500E+10 0.00 0.00
July 0.298546E+10 0.243274E+09 0.239425E+10 0.103715E+10 0.135710E+10 0.00 0.00
August 0.303206E+10 0.392605E+09 0.249361E+10 0.137596E+10 0.111765E+10 0.00 0.00
September 0.210803E+10 0.751531E+09 0.192581E+10 0.115100E+10 0.774815E+09 0.00 0.00
October 0.136414E+10 0.139597E+10 0.147297E+10 0.934043E+09 0.538928E+09 0.00 0.00
November 0.506214E+09 0.241962E+10 0.772670E+09 0.544306E+09 0.228364E+09 0.00 0.00
December 24938342.03 0.298104E+10 0.141180E+09 99460103.64 41719703.73 0.00 0.00
               
Annual Sum or Average 0.239495E+11 0.161846E+11 0.221836E+11 0.126944E+11 0.948921E+10 0.00 0.00
Minimum of Months 24938342.03 0.225039E+09 0.141180E+09 99460103.64 41719703.73 0.00 0.00
Maximum of Months 0.359238E+10 0.298104E+10 0.320927E+10 0.199719E+10 0.142500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.781804E+09 0.749969E+10 0.134593E+10 0.895543E+09 0.450387E+09 0.00 0.00
February 0.344208E+10 0.543893E+10 0.406245E+10 0.281964E+10 0.124281E+10 0.00 0.00
March 0.756266E+10 0.464255E+10 0.761775E+10 0.515262E+10 0.246513E+10 0.00 0.00
April 0.100647E+11 0.290699E+10 0.903709E+10 0.562395E+10 0.341314E+10 0.00 0.00
May 0.894170E+10 0.149025E+10 0.771342E+10 0.400528E+10 0.370815E+10 0.00 0.00
June 0.815805E+10 0.691776E+09 0.678295E+10 0.277024E+10 0.401271E+10 0.00 0.00
July 0.832547E+10 0.745137E+09 0.674205E+10 0.292054E+10 0.382151E+10 0.00 0.00
August 0.847381E+10 0.118460E+10 0.702183E+10 0.387461E+10 0.314722E+10 0.00 0.00
September 0.589286E+10 0.217929E+10 0.542296E+10 0.324113E+10 0.218183E+10 0.00 0.00
October 0.381159E+10 0.394447E+10 0.414779E+10 0.263020E+10 0.151759E+10 0.00 0.00
November 0.141449E+10 0.676905E+10 0.217579E+10 0.153273E+10 0.643057E+09 0.00 0.00
December 69364993.15 0.833930E+10 0.397553E+09 0.280073E+09 0.117480E+09 0.00 0.00
               
Annual Sum or Average 0.669386E+11 0.458320E+11 0.624676E+11 0.357466E+11 0.267210E+11 0.00 0.00
Minimum of Months 69364993.15 0.691776E+09 0.397553E+09 0.280073E+09 0.117480E+09 0.00 0.00
Maximum of Months 0.100647E+11 0.833930E+10 0.903709E+10 0.562395E+10 0.401271E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100964E+10 0.101774E+11 0.174844E+10 0.116336E+10 0.585078E+09 0.00 0.00
February 0.449420E+10 0.736499E+10 0.527735E+10 0.366288E+10 0.161447E+10 0.00 0.00
March 0.993558E+10 0.629061E+10 0.989589E+10 0.669355E+10 0.320234E+10 0.00 0.00
April 0.132310E+11 0.396107E+10 0.117397E+11 0.730582E+10 0.443386E+10 0.00 0.00
May 0.117209E+11 0.208392E+10 0.100202E+11 0.520308E+10 0.481709E+10 0.00 0.00
June 0.106750E+11 0.988771E+09 0.881144E+10 0.359870E+10 0.521274E+10 0.00 0.00
July 0.108849E+11 0.106924E+10 0.875830E+10 0.379395E+10 0.496436E+10 0.00 0.00
August 0.110801E+11 0.167632E+10 0.912176E+10 0.503334E+10 0.408842E+10 0.00 0.00
September 0.769521E+10 0.306021E+10 0.704473E+10 0.421041E+10 0.283432E+10 0.00 0.00
October 0.496738E+10 0.544738E+10 0.538822E+10 0.341678E+10 0.197143E+10 0.00 0.00
November 0.183408E+10 0.917947E+10 0.282647E+10 0.199110E+10 0.835368E+09 0.00 0.00
December 87559714.80 0.112758E+11 0.516444E+09 0.363831E+09 0.152613E+09 0.00 0.00
               
Annual Sum or Average 0.876155E+11 0.625752E+11 0.811489E+11 0.464368E+11 0.347121E+11 0.00 0.00
Minimum of Months 87559714.80 0.988771E+09 0.516444E+09 0.363831E+09 0.152613E+09 0.00 0.00
Maximum of Months 0.132310E+11 0.112758E+11 0.117397E+11 0.730582E+10 0.521274E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 15203732.51 0.160155E+10 0.113990E+09 66207315.62 47782214.36 0.00 0.00
February 0.181365E+09 0.115168E+10 0.390116E+09 0.234554E+09 0.155563E+09 0.00 0.00
March 0.681146E+09 0.955101E+09 0.884045E+09 0.512616E+09 0.371429E+09 0.00 0.00
April 0.147389E+10 0.551709E+09 0.143490E+10 0.810318E+09 0.624580E+09 0.00 0.00
May 0.147500E+10 0.267830E+09 0.134392E+10 0.647190E+09 0.696733E+09 0.00 0.00
June 0.156607E+10 0.117097E+09 0.132678E+10 0.557548E+09 0.769229E+09 0.00 0.00
July 0.145790E+10 0.129106E+09 0.120755E+10 0.482401E+09 0.725150E+09 0.00 0.00
August 0.127059E+10 0.213026E+09 0.109878E+10 0.529556E+09 0.569222E+09 0.00 0.00
September 0.710516E+09 0.427954E+09 0.733524E+09 0.374633E+09 0.358891E+09 0.00 0.00
October 0.273486E+09 0.821686E+09 0.434202E+09 0.227526E+09 0.206676E+09 0.00 0.00
November 56220115.98 0.144099E+10 0.208723E+09 0.128163E+09 80559550.02 0.00 0.00
December 0.00 0.175521E+10 33037168.42 20187795.43 12849372.99 0.00 0.00
               
Annual Sum or Average 0.916139E+10 0.943294E+10 0.920957E+10 0.459090E+10 0.461866E+10 0.00 0.00
Minimum of Months 0.00 0.117097E+09 33037168.42 20187795.43 12849372.99 0.00 0.00
Maximum of Months 0.156607E+10 0.175521E+10 0.143490E+10 0.810318E+09 0.769229E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.170158E+10 27063910.43 3327943.48 23735966.96 0.00 0.00
February 10606442.91 0.131559E+10 0.135130E+09 36576040.05 98553634.11 0.00 0.00
March 0.193742E+09 0.104676E+10 0.438895E+09 0.150847E+09 0.288048E+09 0.00 0.00
April 0.849662E+09 0.552095E+09 0.958943E+09 0.419992E+09 0.538951E+09 0.00 0.00
May 0.103369E+10 0.231695E+09 0.105292E+10 0.406216E+09 0.646703E+09 0.00 0.00
June 0.128775E+10 96651706.09 0.116443E+10 0.432745E+09 0.731690E+09 0.00 0.00
July 0.114558E+10 0.117485E+09 0.100844E+10 0.323239E+09 0.685201E+09 0.00 0.00
August 0.818005E+09 0.204988E+09 0.782523E+09 0.268145E+09 0.514377E+09 0.00 0.00
September 0.342739E+09 0.435120E+09 0.447053E+09 0.147371E+09 0.299682E+09 0.00 0.00
October 51753368.89 0.914278E+09 0.190123E+09 42849611.93 0.147273E+09 0.00 0.00
November 2259431.59 0.156888E+10 70113503.71 20544393.39 49569110.31 0.00 0.00
December 0.00 0.178810E+10 7421980.86 522824.73 6899156.13 0.00 0.00
               
Annual Sum or Average 0.573579E+10 0.997322E+10 0.628306E+10 0.225237E+10 0.403068E+10 0.00 0.00
Minimum of Months 0.00 96651706.09 7421980.86 522824.73 6899156.13 0.00 0.00
Maximum of Months 0.128775E+10 0.178810E+10 0.116443E+10 0.432745E+09 0.731690E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 48379921.37 0.379130E+09 75587157.08 50293495.70 25293661.38 0.00 0.00
February 0.202571E+09 0.282488E+09 0.228147E+09 0.158351E+09 69795900.67 0.00 0.00
March 0.418367E+09 0.285886E+09 0.427812E+09 0.289370E+09 0.138442E+09 0.00 0.00
April 0.545800E+09 0.204468E+09 0.507522E+09 0.315840E+09 0.191683E+09 0.00 0.00
May 0.477876E+09 0.116077E+09 0.433186E+09 0.224936E+09 0.208250E+09 0.00 0.00
June 0.431103E+09 60347924.49 0.380931E+09 0.155576E+09 0.225355E+09 0.00 0.00
July 0.440872E+09 64855482.50 0.378634E+09 0.164017E+09 0.214617E+09 0.00 0.00
August 0.453191E+09 96362685.54 0.394346E+09 0.217597E+09 0.176749E+09 0.00 0.00
September 0.311916E+09 0.164426E+09 0.304553E+09 0.182021E+09 0.122532E+09 0.00 0.00
October 0.203584E+09 0.255518E+09 0.232939E+09 0.147712E+09 85227669.47 0.00 0.00
November 87793737.94 0.341126E+09 0.122192E+09 86077848.02 36114043.15 0.00 0.00
December 4911067.09 0.423135E+09 22326509.33 15728848.52 6597660.82 0.00 0.00
               
Annual Sum or Average 0.362636E+10 0.267382E+10 0.350818E+10 0.200752E+10 0.150066E+10 0.00 0.00
Minimum of Months 4911067.09 60347924.49 22326509.33 15728848.52 6597660.82 0.00 0.00
Maximum of Months 0.545800E+09 0.423135E+09 0.507522E+09 0.315840E+09 0.225355E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.489216E+09 6062497.20 0.00 6062497.20 0.00 0.00
February 0.00 0.394266E+09 24205710.07 0.00 24205710.07 0.00 0.00
March 5580920.24 0.323918E+09 71786871.05 12417.67 71774453.38 0.00 0.00
April 54744836.60 0.160760E+09 0.126876E+09 3641923.15 0.123234E+09 0.00 0.00
May 0.172162E+09 63387346.84 0.200495E+09 32204855.03 0.168290E+09 0.00 0.00
June 0.271659E+09 24387097.91 0.251166E+09 55772213.67 0.195394E+09 0.00 0.00
July 0.245040E+09 30383642.75 0.219449E+09 36724219.00 0.182725E+09 0.00 0.00
August 0.131486E+09 55770069.12 0.141438E+09 8512778.15 0.132926E+09 0.00 0.00
September 32376635.22 0.128713E+09 75446330.45 247489.23 75198841.21 0.00 0.00
October 2570903.27 0.275846E+09 37727112.88 0.00 37727112.88 0.00 0.00
November 0.00 0.460837E+09 11330375.20 0.00 11330375.20 0.00 0.00
December 0.00 0.511259E+09 1839043.17 0.00 1839043.17 0.00 0.00
               
Annual Sum or Average 0.915620E+09 0.291874E+10 0.116782E+10 0.137116E+09 0.103071E+10 0.00 0.00
Minimum of Months 0.00 24387097.91 1839043.17 0.00 1839043.17 0.00 0.00
Maximum of Months 0.271659E+09 0.511259E+09 0.251166E+09 55772213.67 0.195394E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 33102665.11 0.158886E+10 0.136448E+09 78443716.40 58004180.96 0.00 0.00
February 0.292945E+09 0.114122E+10 0.481607E+09 0.292157E+09 0.189449E+09 0.00 0.00
March 0.100795E+10 0.949315E+09 0.114430E+10 0.670304E+09 0.473997E+09 0.00 0.00
April 0.142464E+10 0.523849E+09 0.141908E+10 0.792184E+09 0.626899E+09 0.00 0.00
May 0.195515E+10 0.248488E+09 0.172204E+10 0.947347E+09 0.774692E+09 0.00 0.00
June 0.181532E+10 0.101073E+09 0.152259E+10 0.683027E+09 0.839567E+09 0.00 0.00
July 0.184223E+10 0.117896E+09 0.150314E+10 0.705635E+09 0.797508E+09 0.00 0.00
August 0.155283E+10 0.201297E+09 0.132040E+10 0.677361E+09 0.643043E+09 0.00 0.00
September 0.890973E+09 0.417188E+09 0.881981E+09 0.454225E+09 0.427756E+09 0.00 0.00
October 0.447990E+09 0.818927E+09 0.571828E+09 0.298371E+09 0.273457E+09 0.00 0.00
November 52692413.81 0.143621E+10 0.209106E+09 0.128112E+09 80993168.26 0.00 0.00
December 0.00 0.174999E+10 36205317.59 21637645.56 14567672.03 0.00 0.00
               
Annual Sum or Average 0.113158E+11 0.929431E+10 0.109487E+11 0.574881E+10 0.519993E+10 0.00 0.00
Minimum of Months 0.00 0.101073E+09 36205317.59 21637645.56 14567672.03 0.00 0.00
Maximum of Months 0.195515E+10 0.174999E+10 0.172204E+10 0.947347E+09 0.839567E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 1968221.05 0.167067E+10 49522277.81 15564344.25 33957933.56 0.00 0.00
February 71749062.26 0.124927E+10 0.226620E+09 94179516.98 0.132440E+09 0.00 0.00
March 0.491007E+09 0.100692E+10 0.699151E+09 0.308535E+09 0.390616E+09 0.00 0.00
April 0.790261E+09 0.517848E+09 0.943127E+09 0.401858E+09 0.541270E+09 0.00 0.00
May 0.154057E+10 0.238779E+09 0.143103E+10 0.706373E+09 0.724662E+09 0.00 0.00
June 0.156036E+10 96999974.69 0.136025E+10 0.558224E+09 0.802027E+09 0.00 0.00
July 0.153964E+10 0.118131E+09 0.130403E+10 0.546472E+09 0.757559E+09 0.00 0.00
August 0.111547E+10 0.204630E+09 0.100415E+10 0.415950E+09 0.588198E+09 0.00 0.00
September 0.517957E+09 0.421343E+09 0.595510E+09 0.226963E+09 0.368547E+09 0.00 0.00
October 0.186893E+09 0.868943E+09 0.327749E+09 0.113695E+09 0.214054E+09 0.00 0.00
November 1328772.72 0.156667E+10 70496352.41 20493623.86 50002728.55 0.00 0.00
December 0.00 0.178247E+10 10590130.03 1972674.86 8617455.17 0.00 0.00
               
Annual Sum or Average 0.781719E+10 0.974267E+10 0.802223E+10 0.341028E+10 0.461195E+10 0.00 0.00
Minimum of Months 0.00 96999974.69 10590130.03 1972674.86 8617455.17 0.00 0.00
Maximum of Months 0.156036E+10 0.178247E+10 0.143103E+10 0.706373E+09 0.802027E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 42651471.69 0.200281E+10 0.176910E+09 0.108972E+09 67937732.10 0.00 0.00
February 0.294621E+09 0.144582E+10 0.546768E+09 0.343102E+09 0.203666E+09 0.00 0.00
March 0.847933E+09 0.121213E+10 0.108246E+10 0.627012E+09 0.455452E+09 0.00 0.00
April 0.134135E+10 0.704783E+09 0.137451E+10 0.692226E+09 0.682289E+09 0.00 0.00
May 0.143027E+10 0.310959E+09 0.137293E+10 0.557139E+09 0.815793E+09 0.00 0.00
June 0.154620E+10 0.131569E+09 0.136948E+10 0.457912E+09 0.911569E+09 0.00 0.00
July 0.152010E+10 0.160641E+09 0.129579E+10 0.434936E+09 0.860858E+09 0.00 0.00
August 0.130319E+10 0.273962E+09 0.116084E+10 0.489914E+09 0.670926E+09 0.00 0.00
September 0.783443E+09 0.546585E+09 0.823323E+09 0.394925E+09 0.428398E+09 0.00 0.00
October 0.397330E+09 0.103425E+10 0.586444E+09 0.320050E+09 0.266394E+09 0.00 0.00
November 87786904.26 0.180377E+10 0.289301E+09 0.186507E+09 0.102794E+09 0.00 0.00
December 321765.69 0.220159E+10 52359321.10 34080040.69 18279280.41 0.00 0.00
               
Annual Sum or Average 0.959520E+10 0.118289E+11 0.101311E+11 0.464678E+10 0.548436E+10 0.00 0.00
Minimum of Months 321765.69 0.131569E+09 52359321.10 34080040.69 18279280.41 0.00 0.00
Maximum of Months 0.154620E+10 0.220159E+10 0.137451E+10 0.692226E+09 0.911569E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 15607299.91 0.159075E+10 0.113990E+09 66207315.62 47782214.36 0.00 0.00
February 0.184327E+09 0.114307E+10 0.390116E+09 0.234554E+09 0.155563E+09 0.00 0.00
March 0.685018E+09 0.949514E+09 0.884045E+09 0.512616E+09 0.371429E+09 0.00 0.00
April 0.147030E+10 0.548607E+09 0.143490E+10 0.810318E+09 0.624580E+09 0.00 0.00
May 0.147005E+10 0.265094E+09 0.134392E+10 0.647190E+09 0.696733E+09 0.00 0.00
June 0.155983E+10 0.115317E+09 0.132678E+10 0.557548E+09 0.769229E+09 0.00 0.00
July 0.145241E+10 0.127115E+09 0.120755E+10 0.482401E+09 0.725150E+09 0.00 0.00
August 0.126685E+10 0.210148E+09 0.109878E+10 0.529556E+09 0.569222E+09 0.00 0.00
September 0.711723E+09 0.422641E+09 0.733524E+09 0.374633E+09 0.358891E+09 0.00 0.00
October 0.276791E+09 0.815069E+09 0.434202E+09 0.227526E+09 0.206676E+09 0.00 0.00
November 57601424.00 0.142639E+10 0.208723E+09 0.128163E+09 80559550.02 0.00 0.00
December 0.00 0.174365E+10 33037168.42 20187795.43 12849372.99 0.00 0.00
               
Annual Sum or Average 0.915050E+10 0.935737E+10 0.920957E+10 0.459090E+10 0.461866E+10 0.00 0.00
Minimum of Months 0.00 0.115317E+09 33037168.42 20187795.43 12849372.99 0.00 0.00
Maximum of Months 0.155983E+10 0.174365E+10 0.143490E+10 0.810318E+09 0.769229E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.169073E+10 27063910.43 3327943.48 23735966.96 0.00 0.00
February 10981426.42 0.130629E+10 0.135130E+09 36576040.05 98553634.11 0.00 0.00
March 0.195406E+09 0.104070E+10 0.438895E+09 0.150847E+09 0.288048E+09 0.00 0.00
April 0.849620E+09 0.548386E+09 0.958943E+09 0.419992E+09 0.538951E+09 0.00 0.00
May 0.103048E+10 0.230508E+09 0.105292E+10 0.406216E+09 0.646703E+09 0.00 0.00
June 0.127871E+10 97183768.10 0.116443E+10 0.432745E+09 0.731690E+09 0.00 0.00
July 0.113866E+10 0.117656E+09 0.100844E+10 0.323239E+09 0.685201E+09 0.00 0.00
August 0.814583E+09 0.204124E+09 0.782523E+09 0.268145E+09 0.514377E+09 0.00 0.00
September 0.346054E+09 0.428396E+09 0.447053E+09 0.147371E+09 0.299682E+09 0.00 0.00
October 53558490.09 0.906915E+09 0.190123E+09 42849611.93 0.147273E+09 0.00 0.00
November 2338009.32 0.155354E+10 70113503.71 20544393.39 49569110.31 0.00 0.00
December 0.00 0.177660E+10 7421980.86 522824.73 6899156.13 0.00 0.00
               
Annual Sum or Average 0.572039E+10 0.990104E+10 0.628306E+10 0.225237E+10 0.403068E+10 0.00 0.00
Minimum of Months 0.00 97183768.10 7421980.86 522824.73 6899156.13 0.00 0.00
Maximum of Months 0.127871E+10 0.177660E+10 0.116443E+10 0.432745E+09 0.731690E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 80384615.70 0.793551E+09 0.138597E+09 92218633.81 46378698.96 0.00 0.00
February 0.353258E+09 0.577567E+09 0.418332E+09 0.290353E+09 0.127978E+09 0.00 0.00
March 0.775181E+09 0.494843E+09 0.784440E+09 0.530592E+09 0.253848E+09 0.00 0.00
April 0.103430E+10 0.300503E+09 0.930598E+09 0.579127E+09 0.351471E+09 0.00 0.00
May 0.920853E+09 0.146382E+09 0.794294E+09 0.412444E+09 0.381850E+09 0.00 0.00
June 0.845928E+09 62052231.31 0.698478E+09 0.285266E+09 0.413213E+09 0.00 0.00
July 0.863901E+09 67376693.26 0.694266E+09 0.300743E+09 0.393523E+09 0.00 0.00
August 0.875812E+09 0.111925E+09 0.723076E+09 0.398988E+09 0.324088E+09 0.00 0.00
September 0.606444E+09 0.223492E+09 0.558431E+09 0.333756E+09 0.224675E+09 0.00 0.00
October 0.390015E+09 0.417290E+09 0.427120E+09 0.270846E+09 0.156274E+09 0.00 0.00
November 0.147776E+09 0.709450E+09 0.224052E+09 0.157833E+09 66219054.27 0.00 0.00
December 7403500.21 0.878814E+09 40938100.64 28840566.79 12097533.86 0.00 0.00
               
Annual Sum or Average 0.690126E+10 0.478325E+10 0.643262E+10 0.368101E+10 0.275162E+10 0.00 0.00
Minimum of Months 7403500.21 62052231.31 40938100.64 28840566.79 12097533.86 0.00 0.00
Maximum of Months 0.103430E+10 0.878814E+09 0.930598E+09 0.579127E+09 0.413213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.438363E+10 53037810.99 0.00 53037810.99 0.00 0.00
February 0.00 0.355110E+10 0.211764E+09 0.00 0.211764E+09 0.00 0.00
March 36320873.45 0.299546E+10 0.628028E+09 108636.11 0.627919E+09 0.00 0.00
April 0.413338E+09 0.154627E+10 0.110997E+10 31861397.22 0.107811E+10 0.00 0.00
May 0.138923E+10 0.621982E+09 0.175403E+10 0.281744E+09 0.147229E+10 0.00 0.00
June 0.227925E+10 0.250265E+09 0.219733E+10 0.487924E+09 0.170940E+10 0.00 0.00
July 0.205237E+10 0.308413E+09 0.191985E+10 0.321282E+09 0.159857E+10 0.00 0.00
August 0.106343E+10 0.554150E+09 0.123737E+10 74474115.76 0.116290E+10 0.00 0.00
September 0.238784E+09 0.126084E+10 0.660043E+09 2165161.78 0.657878E+09 0.00 0.00
October 14423248.61 0.260418E+10 0.330056E+09 0.00 0.330056E+09 0.00 0.00
November 0.00 0.411877E+10 99123888.81 0.00 99123888.81 0.00 0.00
December 0.00 0.454923E+10 16088885.60 0.00 16088885.60 0.00 0.00
               
Annual Sum or Average 0.748715E+10 0.267443E+11 0.102167E+11 0.119956E+10 0.901713E+10 0.00 0.00
Minimum of Months 0.00 0.250265E+09 16088885.60 0.00 16088885.60 0.00 0.00
Maximum of Months 0.227925E+10 0.454923E+10 0.219733E+10 0.487924E+09 0.170940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.445346E+10 53037810.99 0.00 53037810.99 0.00 0.00
February 0.00 0.361164E+10 0.211764E+09 0.00 0.211764E+09 0.00 0.00
March 31664141.86 0.305742E+10 0.628028E+09 108636.11 0.627919E+09 0.00 0.00
April 0.392813E+09 0.158066E+10 0.110997E+10 31861397.22 0.107811E+10 0.00 0.00
May 0.135967E+10 0.634590E+09 0.175403E+10 0.281744E+09 0.147229E+10 0.00 0.00
June 0.225600E+10 0.256769E+09 0.219733E+10 0.487924E+09 0.170940E+10 0.00 0.00
July 0.203004E+10 0.316462E+09 0.191985E+10 0.321282E+09 0.159857E+10 0.00 0.00
August 0.104051E+10 0.568304E+09 0.123737E+10 74474115.76 0.116290E+10 0.00 0.00
September 0.223265E+09 0.129683E+10 0.660043E+09 2165161.78 0.657878E+09 0.00 0.00
October 11510893.98 0.266722E+10 0.330056E+09 0.00 0.330056E+09 0.00 0.00
November 0.00 0.418670E+10 99123888.81 0.00 99123888.81 0.00 0.00
December 0.00 0.461702E+10 16088885.60 0.00 16088885.60 0.00 0.00
               
Annual Sum or Average 0.734547E+10 0.272471E+11 0.102167E+11 0.119956E+10 0.901713E+10 0.00 0.00
Minimum of Months 0.00 0.256769E+09 16088885.60 0.00 16088885.60 0.00 0.00
Maximum of Months 0.225600E+10 0.461702E+10 0.219733E+10 0.487924E+09 0.170940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 39624078.30 0.276888E+10 0.185964E+09 94005850.11 91958367.77 0.00 0.00
February 0.428658E+09 0.200545E+10 0.708199E+09 0.386323E+09 0.321875E+09 0.00 0.00
March 0.174620E+10 0.168817E+10 0.184337E+10 0.978795E+09 0.864570E+09 0.00 0.00
April 0.267303E+10 0.956051E+09 0.236210E+10 0.119399E+10 0.116811E+10 0.00 0.00
May 0.409984E+10 0.455960E+09 0.315291E+10 0.165363E+10 0.149928E+10 0.00 0.00
June 0.403780E+10 0.196299E+09 0.288270E+10 0.124118E+10 0.164151E+10 0.00 0.00
July 0.407093E+10 0.229010E+09 0.280703E+10 0.125204E+10 0.155499E+10 0.00 0.00
August 0.329263E+10 0.367354E+09 0.232443E+10 0.109325E+10 0.123118E+10 0.00 0.00
September 0.182737E+10 0.698684E+09 0.147742E+10 0.681156E+09 0.796263E+09 0.00 0.00
October 0.811650E+09 0.139508E+10 0.899537E+09 0.412050E+09 0.487487E+09 0.00 0.00
November 49622396.29 0.250320E+10 0.279594E+09 0.148603E+09 0.130991E+09 0.00 0.00
December 3755.69 0.303000E+10 46794270.00 23610040.25 23184229.74 0.00 0.00
               
Annual Sum or Average 0.230774E+11 0.162941E+11 0.189700E+11 0.915863E+10 0.981141E+10 0.00 0.00
Minimum of Months 3755.69 0.196299E+09 46794270.00 23610040.25 23184229.74 0.00 0.00
Maximum of Months 0.409984E+10 0.303000E+10 0.315291E+10 0.165363E+10 0.164151E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.120105E+09 0.351182E+10 0.370988E+09 0.234747E+09 0.136241E+09 0.00 0.00
February 0.719615E+09 0.253452E+10 0.113748E+10 0.739109E+09 0.398369E+09 0.00 0.00
March 0.186853E+10 0.214051E+10 0.221212E+10 0.135069E+10 0.861436E+09 0.00 0.00
April 0.278566E+10 0.125667E+10 0.274939E+10 0.148512E+10 0.126427E+10 0.00 0.00
May 0.278175E+10 0.556223E+09 0.262320E+10 0.114648E+10 0.147672E+10 0.00 0.00
June 0.285388E+10 0.240716E+09 0.253126E+10 0.893421E+09 0.163784E+10 0.00 0.00
July 0.283826E+10 0.293765E+09 0.242542E+10 0.875693E+09 0.154973E+10 0.00 0.00
August 0.257001E+10 0.492183E+09 0.226480E+10 0.104118E+10 0.122363E+10 0.00 0.00
September 0.162796E+10 0.968565E+09 0.164778E+10 0.850335E+09 0.797445E+09 0.00 0.00
October 0.892739E+09 0.183394E+10 0.120040E+10 0.689452E+09 0.510948E+09 0.00 0.00
November 0.239045E+09 0.314190E+10 0.604317E+09 0.401773E+09 0.202544E+09 0.00 0.00
December 3992018.14 0.387221E+10 0.109725E+09 73415195.49 36310216.78 0.00 0.00
               
Annual Sum or Average 0.193015E+11 0.208430E+11 0.198769E+11 0.978141E+10 0.100955E+11 0.00 0.00
Minimum of Months 3992018.14 0.240716E+09 0.109725E+09 73415195.49 36310216.78 0.00 0.00
Maximum of Months 0.285388E+10 0.387221E+10 0.274939E+10 0.148512E+10 0.163784E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -17.6 -17.9 -19.9 1.62 -32.2 4.20 17.57 0.00
February -15.4 -16.0 -18.9 1.58 -31.2 17.68 68.90 0.00
March -10.3 -11.6 -17.1 2.46 -25.4 47.11 147.56 0.00
April 0.73 -2.7 -8.8 3.74 -14.2 75.81 230.75 0.00
May 10.60 5.25 -1.5 3.99 -2.1 92.54 252.99 0.00
June 15.96 10.88 6.41 3.45 5.66 116.77 222.76 0.00
July 16.86 12.85 9.90 2.85 7.58 107.92 197.90 0.00
August 14.24 10.70 7.59 2.94 4.33 81.01 176.65 0.00
September 6.72 4.45 1.76 2.11 -4.1 51.38 110.92 0.00
October -3.1 -4.4 -7.1 2.79 -14.3 26.50 62.95 0.00
November -17.6 -18.1 -20.3 0.70 -32.8 8.03 31.72 0.00
December -19.3 -19.6 -21.9 1.25 -33.6 1.27 5.23 0.00
                 
Annual Sum or Average -1.4 -3.8 -7.4 2.46 -14.3 52.69 127.40 0.00
Minimum of Months -19.3 -19.6 -21.9 0.70 -33.6 1.27 5.23 0.00
Maximum of Months 16.86 12.85 9.90 3.99 7.58 116.77 252.99 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 21-JAN-20:00 -2.7 -5.6 0.00 -9.0 0.00 0.00
February 2.80 08-FEB-15:09 -0.7 -6.5 2.68 -7.9 21.67 32.33
March 6.70 20-MAR-14:09 2.60 -3.5 1.37 -7.5 138.33 487.67
April 15.60 22-APR-13:00 7.03 -3.3 4.10 -0.8 117.50 760.50
May 22.20 31-MAY-15:00 10.79 -1.1 3.10 7.75 143.50 516.50
June 28.30 30-JUN-14:00 17.30 10.60 6.20 17.57 223.50 277.50
July 30.00 29-JUL-16:19 18.34 11.70 4.67 18.88 163.67 322.83
August 25.60 11-AUG-15:00 14.77 6.70 6.20 12.22 99.50 604.00
September 17.20 07-SEP-15:00 8.91 0.00 1.50 2.64 77.00 480.50
October 13.90 01-OCT-14:00 8.01 1.70 2.60 1.58 78.50 227.50
November -3.9 18-NOV-03:00 -5.6 -8.9 1.50 -12.4 0.00 0.00
December 1.70 24-DEC-11:00 -0.1 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -3.9   -5.6 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 30.00   18.34 11.70 6.20 18.88 223.50 760.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -38.3 12-JAN-05:00 -38.4 -40.4 0.00 -60.9 0.00 0.00
February -36.1 27-FEB-04:00 -36.2 -39.4 0.00 -58.7 0.00 0.00
March -28.9 01-MAR-00:10 -29.2 -34.0 0.65 -51.0 0.00 0.00
April -21.7 03-APR-05:00 -22.3 -27.2 2.60 -42.7 0.00 0.00
May 0.00 27-MAY-03:00 -1.1 -2.8 6.20 -7.1 29.00 14.00
June 3.30 02-JUN-03:00 2.38 1.10 1.50 -11.2 45.50 266.00
July 7.20 31-JUL-03:49 6.67 6.10 2.18 -7.6 0.00 0.00
August -1.7 31-AUG-05:00 -2.9 -5.0 2.60 -18.6 25.00 538.50
September -5.6 29-SEP-06:00 -6.1 -7.2 2.60 -21.6 0.00 0.00
October -20.6 22-OCT-05:00 -20.8 -22.2 2.60 -40.2 0.00 0.00
November -30.0 29-NOV-09:00 -30.2 -33.3 0.00 -51.8 0.00 0.00
December -33.9 15-DEC-07:00 -34.0 -37.8 0.00 -56.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -38.3   -38.4 -40.4 0.00 -60.9 0.00 0.00
Maximum of Months 7.20   6.67 6.10 6.20 -7.1 45.50 538.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -2.7 21-JAN-20:00 -1.1 -5.6 0.00 -9.0 0.00 0.00
February 1.24 09-FEB-01:00 2.80 -1.1 8.80 -4.1 0.00 0.00
March 2.65 20-MAR-13:00 6.70 -3.3 0.00 -7.6 139.00 515.00
April 7.03 22-APR-13:00 15.60 -3.3 4.10 -0.8 117.50 760.50
May 10.97 31-MAY-17:00 21.70 0.00 2.60 11.07 73.50 187.00
June 18.33 30-JUN-11:00 25.60 14.40 1.50 15.21 221.00 616.00
July 18.36 29-JUL-17:19 29.07 12.23 3.10 19.29 141.00 225.33
August 16.14 04-AUG-19:00 21.70 12.80 3.10 14.28 25.50 28.50
September 10.82 01-SEP-15:00 15.60 6.70 2.60 4.31 145.50 176.00
October 8.01 01-OCT-14:00 13.90 1.70 2.60 1.58 78.50 227.50
November -5.6 18-NOV-03:00 -3.9 -8.9 1.50 -12.4 0.00 0.00
December -0.1 24-DEC-11:00 1.70 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -5.6   -3.9 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 18.36   29.07 14.40 8.80 19.29 221.00 760.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 06-JAN-19:00 -1.7 -2.7 2.60 -12.4 0.00 0.00
February -0.6 09-FEB-00:00 1.70 0.78 3.60 -5.0 0.00 0.00
March 0.00 21-MAR-15:00 1.10 0.62 2.10 -5.5 70.50 4.00
April 0.00 30-APR-07:00 3.30 1.91 2.60 -8.3 198.00 170.00
May 6.10 16-MAY-19:00 8.90 7.49 5.20 3.69 16.00 15.00
June 15.60 30-JUN-17:00 18.90 16.75 3.60 12.22 99.50 223.00
July 17.80 03-JUL-14:00 19.40 18.27 1.50 10.11 223.00 401.50
August 15.00 12-AUG-22:00 16.10 15.38 0.00 12.79 0.00 0.00
September 8.90 04-SEP-11:00 10.00 9.41 2.60 5.33 238.50 0.50
October 5.60 02-OCT-11:09 7.30 6.41 4.95 0.30 123.67 16.00
November -8.3 18-NOV-04:00 -5.0 -6.1 1.50 -13.4 0.00 0.00
December -2.8 24-DEC-09:00 1.10 -0.5 3.10 -6.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -8.3   -5.0 -6.1 0.00 -13.4 0.00 0.00
Maximum of Months 17.80   19.40 18.27 5.20 12.79 238.50 401.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 0.00 1.10 0.00
February 18.00 13.00 16.00 0.00 5.89 0.00
March 18.00 13.00 16.00 0.00 18.25 0.00
April 18.00 13.00 16.00 0.00 35.02 0.00
May 18.00 13.00 16.00 0.44 43.39 0.00
June 18.00 13.00 16.00 2.62 46.67 0.00
July 18.00 13.00 16.00 4.74 42.09 0.00
August 18.00 13.00 16.00 6.08 32.30 0.00
September 18.00 13.00 16.00 6.25 18.21 0.00
October 18.00 13.00 16.00 5.21 8.04 0.00
November 18.00 13.00 16.00 3.27 2.12 0.00
December 18.00 13.00 16.00 0.94 0.28 0.00
             
Annual Sum or Average 18.00 13.00 16.00 2.48 21.19 0.00
Minimum of Months 18.00 13.00 16.00 0.00 0.28 0.00
Maximum of Months 18.00 13.00 16.00 6.25 46.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770637E+10 -0.754277E+10 0.00 0.00 744.00 0.00 -163605664.3 81.21 0.00 0.00
February 0.696341E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -147456292.2 81.21 0.00 0.00
March 0.770419E+10 -0.754147E+10 0.00 0.00 744.00 0.00 -162719735.9 81.21 0.00 0.00
April 0.746554E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156945672.8 81.21 0.00 0.00
May 0.770465E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161856641.0 81.21 0.00 0.00
June 0.745698E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156458394.4 81.21 0.00 0.00
July 0.771253E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161682650.9 81.21 0.00 0.00
August 0.770457E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161768577.8 81.21 0.00 0.00
September 0.746672E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156774193.9 81.21 0.00 0.00
October 0.770375E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -162306292.3 81.21 0.00 0.00
November 0.745043E+10 -0.729244E+10 0.00 0.00 720.00 0.00 -157993300.7 81.21 0.00 0.00
December 0.771437E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -163515278.8 81.21 0.00 0.00
                     
Annual Sum or Average 0.907535E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.191308E+10 81.21 0.00 0.00
Minimum of Months 0.696341E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -163605664.3 81.21 0.00 0.00
Maximum of Months 0.771437E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -147456292.2 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYSLAUNDRY HPWH TANK

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.819268E+11 -0.810385E+11 0.00 0.00 744.00 0.00 -888285912.5 70.68 0.00 0.00
February 0.739858E+11 -0.731994E+11 0.00 0.00 672.00 0.00 -786409744.6 70.66 0.00 0.00
March 0.818195E+11 -0.810617E+11 0.00 0.00 744.00 0.00 -830847953.7 70.66 0.00 0.00
April 0.739688E+11 -0.121925E+12 0.00 0.00 720.00 0.00 -833668887.4 79.93 0.00 0.00
May 0.719928E+11 -0.135457E+12 0.00 0.00 744.00 0.00 -807415349.7 81.67 0.00 0.00
June 0.580105E+11 -0.127520E+12 0.00 0.00 720.00 0.00 -741736379.9 81.67 0.00 0.00
July 0.541566E+11 -0.128187E+12 0.00 0.00 744.00 0.00 -759041229.1 81.67 0.00 0.00
August 0.554851E+11 -0.125914E+12 0.00 0.00 744.00 0.00 -778975212.5 81.67 0.00 0.00
September 0.637725E+11 -0.121579E+12 0.00 0.00 720.00 0.00 -810405073.1 81.67 0.00 0.00
October 0.762001E+11 -0.121345E+12 0.00 0.00 744.00 0.00 -900395962.7 80.64 0.00 0.00
November 0.788244E+11 -0.779538E+11 0.00 0.00 720.00 0.00 -870694110.7 71.60 0.00 0.00
December 0.817957E+11 -0.808919E+11 0.00 0.00 744.00 0.00 -903808131.5 70.92 0.00 0.00
                     
Annual Sum or Average 0.851939E+12 -0.127607E+13 0.00 0.00 8760.00 0.00 -0.991168E+10 76.99 0.00 0.00
Minimum of Months 0.541566E+11 -0.135457E+12 0.00 0.00 672.00 0.00 -903808131.5 70.66 0.00 0.00
Maximum of Months 0.819268E+11 -0.731994E+11 0.00 0.00 744.00 0.00 -741736379.9 81.67 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 HPWH TANK

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.885731E+11 -0.871873E+11 0.00 0.00 744.00 0.00 -0.138587E+10 45.12 0.00 0.00
February 0.799792E+11 -0.787658E+11 0.00 0.00 672.00 0.00 -0.121346E+10 45.10 0.00 0.00
March 0.883199E+11 -0.872564E+11 0.00 0.00 744.00 0.00 -0.124177E+10 44.85 0.00 0.00
April 0.187768E+10 -0.846470E+11 0.00 0.00 720.00 0.00 -0.138690E+10 58.67 0.00 0.00
May -0.223324E+10 -0.869313E+11 0.00 0.00 744.00 0.00 -0.126133E+10 59.05 0.00 0.00
June -0.314254E+10 -0.811258E+11 0.00 0.00 720.00 0.00 -0.112715E+10 59.13 0.00 0.00
July -0.327427E+10 -0.806765E+11 0.00 0.00 744.00 0.00 -0.114802E+10 59.17 0.00 0.00
August -0.287075E+10 -0.787851E+11 0.00 0.00 744.00 0.00 -0.119586E+10 59.16 0.00 0.00
September -0.183779E+10 -0.759253E+11 0.00 0.00 720.00 0.00 -0.129197E+10 59.11 0.00 0.00
October 0.201156E+10 -0.798076E+11 0.00 0.00 744.00 0.00 -0.150890E+10 58.78 0.00 0.00
November 0.811306E+11 -0.797675E+11 0.00 0.00 720.00 0.00 -0.136311E+10 45.90 0.00 0.00
December 0.872366E+11 -0.858149E+11 0.00 0.00 744.00 0.00 -0.142169E+10 45.32 0.00 0.00
                     
Annual Sum or Average 0.415770E+12 -0.986690E+12 0.00 0.00 8760.00 0.00 -0.155460E+11 53.32 0.00 0.00
Minimum of Months -0.327427E+10 -0.872564E+11 0.00 0.00 672.00 0.00 -0.150890E+10 44.85 0.00 0.00
Maximum of Months 0.885731E+11 -0.759253E+11 0.00 0.00 744.00 0.00 -0.112715E+10 59.17 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.90 0.86 10-JAN-10:00 527.07 26.08 71.33 69.83 374.81 27.64 72.67 39.50
February 205.83 0.87 0.86 01-FEB-12:20 1968.45 34.93 190.00 180.00 1580.72 35.94 190.67 151.33
March 329.50 0.87 0.86 01-MAR-08:39 4656.05 33.04 281.67 305.83 2499.05 30.92 279.67 267.50
April 421.83 0.87 0.86 01-APR-07:00 6549.16 30.08 266.17 381.17 722.10 21.63 296.17 313.17
May 545.00 0.88 0.86 01-MAY-06:40 2940.44 21.18 140.67 448.67 532.97 20.28 308.50 347.83
June 583.50 0.88 0.86 01-JUN-05:49 1301.08 18.04 96.33 472.50 509.15 19.86 295.33 357.50
July 562.83 0.88 0.86 01-JUL-05:19 1614.97 18.69 105.50 469.33 518.95 19.97 298.67 352.17
August 467.17 0.88 0.86 01-AUG-06:19 4498.67 25.71 229.17 404.00 575.34 20.55 252.67 318.50
September 356.33 0.88 0.86 01-SEP-06:49 3817.19 30.66 274.83 320.50 1032.49 23.05 205.00 260.17
October 265.50 0.87 0.86 01-OCT-07:00 2071.53 32.65 240.33 236.50 1626.81 33.64 243.67 203.67
November 135.83 0.88 0.86 01-NOV-09:00 774.86 32.28 117.50 121.50 566.26 33.54 117.67 86.50
December 71.17 0.95 0.86 05-DEC-11:30 125.54 5.30 0.00 8.83 74.29 8.35 0.00 0.00
                         
Annual Sum or Average 4053.17 0.88     2999.13 25.30 2013.50 3418.67 869.59 23.56 2560.67 2697.83
Minimum of Months 71.17 0.87 0.86   125.54 5.30 0.00 8.83 74.29 8.35 0.00 0.00
Maximum of Months 583.50 0.95 0.86   6549.16 34.93 281.67 472.50 2499.05 35.94 308.50 357.50



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.38 0.22 08-JAN-11:30 619.61 26.55 72.00 83.17 465.87 28.08 72.67 57.67
February 205.83 0.28 0.22 01-FEB-11:20 2217.37 35.05 190.17 188.50 1828.92 36.05 191.50 171.67
March 329.50 0.26 0.22 01-MAR-08:30 5029.28 33.24 284.67 312.17 2873.10 30.97 272.83 291.67
April 421.83 0.27 0.22 01-APR-07:19 6940.67 30.50 281.33 398.50 1112.16 21.69 286.83 355.83
May 545.00 0.30 0.22 01-MAY-05:10 3214.91 21.73 177.50 474.83 806.39 20.57 319.50 418.67
June 583.50 0.31 0.22 01-JUN-04:00 1533.50 18.65 118.50 505.17 740.61 20.30 323.83 435.17
July 562.83 0.30 0.22 01-JUL-04:40 1853.36 19.31 133.50 499.50 756.71 20.38 306.33 423.33
August 467.17 0.28 0.22 01-AUG-05:40 4784.96 26.27 248.33 424.50 861.08 20.85 267.83 376.00
September 356.33 0.28 0.22 01-SEP-06:19 4087.67 30.93 279.83 333.50 1300.61 23.36 224.33 295.17
October 265.50 0.27 0.22 01-OCT-07:40 2291.74 32.78 241.17 246.67 1845.23 33.75 245.00 223.83
November 135.83 0.30 0.22 01-NOV-09:39 912.06 32.52 117.50 134.67 702.98 33.76 117.67 109.17
December 71.17 0.62 0.22 04-DEC-11:20 141.80 6.72 0.00 21.17 89.47 9.73 0.00 5.83
                         
Annual Sum or Average 4053.17 0.30     3264.89 25.76 2144.50 3622.33 1134.40 23.85 2628.33 3164.00
Minimum of Months 71.17 0.26 0.22   141.80 6.72 0.00 21.17 89.47 9.73 0.00 5.83
Maximum of Months 583.50 0.62 0.22   6940.67 35.05 284.67 505.17 2873.10 36.05 323.83 435.17



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.85 0.67 31-JAN-11:30 109.98 7.60 0.00 7.67 53.17 11.11 0.00 0.00
February 205.83 0.73 0.60 16-FEB-12:30 243.13 11.99 0.00 130.33 116.03 15.54 0.00 7.83
March 329.50 0.65 0.60 01-MAR-10:20 432.84 15.06 0.00 285.17 203.34 18.46 0.00 153.17
April 421.83 0.62 0.60 01-APR-07:00 547.44 17.26 10.17 403.67 272.15 20.59 41.83 327.00
May 545.00 0.63 0.60 01-MAY-04:49 690.57 19.35 88.83 502.67 332.49 22.93 185.83 451.50
June 583.50 0.63 0.60 01-JUN-03:00 861.14 20.91 148.67 542.50 404.73 23.22 244.83 495.33
July 562.83 0.63 0.60 01-JUL-03:39 777.69 20.15 124.17 531.50 349.99 22.45 188.83 459.67
August 467.17 0.63 0.60 01-AUG-04:49 583.29 17.55 34.67 431.00 278.00 21.15 86.00 334.50
September 356.33 0.66 0.60 01-SEP-05:00 424.56 14.95 0.00 311.83 193.15 18.21 3.33 152.33
October 265.50 0.70 0.60 01-OCT-08:20 302.88 13.00 0.00 201.67 132.54 16.34 0.00 12.17
November 135.83 0.81 0.65 06-NOV-13:30 149.02 9.50 0.00 37.17 70.24 13.30 0.00 0.00
December 71.17 0.94 0.83 04-DEC-11:30 40.46 2.93 0.00 0.00 20.19 5.93 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     562.37 16.80 406.50 3385.17 264.16 19.93 750.67 2393.50
Minimum of Months 71.17 0.62 0.60   40.46 2.93 0.00 0.00 20.19 5.93 0.00 0.00
Maximum of Months 583.50 0.94 0.83   861.14 20.91 148.67 542.50 404.73 23.22 244.83 495.33



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.85 0.67 31-JAN-11:30 109.98 7.60 0.00 7.67 53.17 11.11 0.00 0.00
February 205.83 0.73 0.60 16-FEB-12:30 243.13 11.99 0.00 130.33 116.03 15.54 0.00 7.83
March 329.50 0.65 0.60 01-MAR-10:20 432.84 15.06 0.00 285.17 203.34 18.46 0.00 153.17
April 421.83 0.62 0.60 01-APR-07:00 547.44 17.26 10.17 403.67 272.15 20.59 41.83 327.00
May 545.00 0.63 0.60 01-MAY-04:49 690.57 19.35 88.83 502.67 332.49 22.93 185.83 451.50
June 583.50 0.63 0.60 01-JUN-03:00 861.14 20.91 148.67 542.50 404.73 23.22 244.83 495.33
July 562.83 0.63 0.60 01-JUL-03:39 777.69 20.15 124.17 531.50 349.99 22.45 188.83 459.67
August 467.17 0.63 0.60 01-AUG-04:49 583.29 17.55 34.67 431.00 278.00 21.15 86.00 334.50
September 356.33 0.66 0.60 01-SEP-05:00 424.56 14.95 0.00 311.83 193.15 18.21 3.33 152.33
October 265.50 0.70 0.60 01-OCT-08:20 302.88 13.00 0.00 201.67 132.54 16.34 0.00 12.17
November 135.83 0.81 0.65 06-NOV-13:30 149.02 9.50 0.00 37.17 70.24 13.30 0.00 0.00
December 71.17 0.94 0.83 04-DEC-11:30 40.46 2.93 0.00 0.00 20.19 5.93 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     562.37 16.80 406.50 3385.17 264.16 19.93 750.67 2393.50
Minimum of Months 71.17 0.62 0.60   40.46 2.93 0.00 0.00 20.19 5.93 0.00 0.00
Maximum of Months 583.50 0.94 0.83   861.14 20.91 148.67 542.50 404.73 23.22 244.83 495.33



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.511320E+12 553466.65 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.437044E+12 546254.68 27-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.264905E+12 521742.06 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.742363E+11 157728.36 03-APR-06:20 0.00 0.00 0.00 0.00 0.00
May 0.485980E+11 120321.88 19-MAY-07:00 0.00 0.00 0.00 0.00 0.00
June 0.363342E+11 111679.75 01-JUN-06:20 0.00 0.00 0.00 0.00 0.00
July 0.366328E+11 103197.41 05-JUL-07:00 0.00 0.00 0.00 0.00 0.00
August 0.543205E+11 118910.57 31-AUG-10:00 0.00 0.00 0.00 0.00 0.00
September 0.501852E+11 122133.49 09-SEP-09:40 0.00 0.00 0.00 0.00 0.00
October 0.110843E+12 150831.05 27-OCT-09:00 0.00 0.00 0.00 0.00 0.00
November 0.487929E+12 525832.79 30-NOV-21:00 0.00 0.00 0.00 0.00 0.00
December 0.602592E+12 538892.85 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.271494E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.363342E+11 103197.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.602592E+12 553466.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.169659E+10 10814.34 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.222231E+10 10631.22 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.872761E+09 6987.46 01-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 807024.23 374.24 02-APR-15:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 42659690.73 3224.09 30-NOV-11:00 0.00 0.00 0.00 0.00 0.00
December 0.445736E+09 10113.91 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.528086E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.222231E+10 10814.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.787307E+10 5912.49 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.556268E+10 5810.21 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.360401E+10 5119.98 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.127128E+10 2095.77 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.560069E+09 1372.74 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.165041E+09 952.48 25-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.203333E+09 1041.67 05-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.393252E+09 1114.02 30-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.149550E+10 1702.31 30-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.348964E+10 2742.06 30-OCT-08:30 0.00 0.00 0.00 0.00 0.00
November 0.703586E+10 5524.39 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.867384E+10 5707.47 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.403276E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.165041E+09 952.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.867384E+10 5912.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104537E+10 2033.32 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.599397E+09 1963.45 27-FEB-09:50 0.00 0.00 0.00 0.00 0.00
March 0.151833E+09 1204.82 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 805774.17 130.78 04-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 42246363.71 389.75 29-OCT-15:00 0.00 0.00 0.00 0.00 0.00
November 0.726488E+09 1662.82 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.117067E+10 1953.84 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.373682E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117067E+10 2033.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.230265E+10 2823.17 12-JAN-10:02 0.00 0.00 0.00 0.00 0.00
February 0.169704E+10 2438.99 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.980723E+09 1777.12 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.106487E+09 627.95 03-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.368922E+09 686.25 31-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.190330E+10 1894.16 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.251828E+10 2352.28 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.987740E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.251828E+10 2823.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.198974E+10 1813.89 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.151785E+10 1646.91 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.102173E+10 1246.29 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.171303E+09 499.57 03-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 16386008.43 187.58 29-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.513976E+09 602.02 31-OCT-10:35 0.00 0.00 0.00 0.00 0.00
November 0.172830E+10 1399.73 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.214783E+10 1683.03 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.910712E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.214783E+10 1813.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.358130E+10 13744.33 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.244550E+10 13512.55 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.103643E+10 12679.65 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 57041245.40 1300.95 03-APR-03:50 0.00 0.00 0.00 0.00 0.00
May 4134289.17 515.05 27-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 341475.49 205.74 26-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 374732.00 206.51 05-JUL-04:00 0.00 0.00 0.00 0.00 0.00
August 910650.26 206.97 21-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 25633786.24 818.28 30-SEP-05:00 0.00 0.00 0.00 0.00 0.00
October 0.125326E+09 1485.25 30-OCT-03:50 0.00 0.00 0.00 0.00 0.00
November 0.247421E+10 12798.60 29-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.384698E+10 13215.64 15-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.135982E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 341475.49 205.74   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384698E+10 13744.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.140235E+11 17400.94 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.853679E+10 17077.96 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.330718E+10 13805.64 01-MAR-07:20 0.00 0.00 0.00 0.00 0.00
April 0.482771E+09 4647.21 04-APR-09:07 0.00 0.00 0.00 0.00 0.00
May 49698328.01 2855.61 27-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 38709588.93 1890.62 27-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 23179557.49 2820.38 05-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 53441555.95 2579.80 07-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.768733E+09 4404.67 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.305029E+10 6953.08 30-OCT-08:40 0.00 0.00 0.00 0.00 0.00
November 0.116715E+11 16269.05 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.159679E+11 16803.30 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.579737E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 23179557.49 1890.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159679E+11 17400.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.177317E+11 41173.60 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.930925E+10 40085.74 27-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.167640E+10 26062.59 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 6871976.30 2192.05 04-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.477763E+09 7415.68 29-OCT-15:00 0.00 0.00 0.00 0.00 0.00
November 0.121082E+11 37258.94 29-NOV-10:10 0.00 0.00 0.00 0.00 0.00
December 0.194682E+11 39764.16 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.607784E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.194682E+11 41173.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.220037E+11 19375.30 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.152044E+11 18686.72 27-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.825525E+10 14181.09 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.112247E+10 5553.12 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.894074E+09 4463.82 27-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.759431E+10 8321.29 30-OCT-08:30 0.00 0.00 0.00 0.00 0.00
November 0.192178E+11 17235.23 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.238494E+11 18698.46 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.981414E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.238494E+11 19375.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.147339E+11 13627.87 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.106673E+11 12861.81 27-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.659368E+10 10023.86 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.142645E+10 4170.45 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 5682601.47 688.25 28-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.708470E+09 2345.34 30-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.494042E+10 4870.90 27-OCT-08:20 0.00 0.00 0.00 0.00 0.00
November 0.133099E+11 11185.01 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.160825E+11 12906.73 15-DEC-11:09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.684684E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160825E+11 13627.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.263268E+10 17497.57 12-JAN-10:00 0.00 0.00 0.00 0.00 0.00
February 0.112070E+10 15034.34 27-FEB-09:40 0.00 0.00 0.00 0.00 0.00
March 0.130400E+09 7332.70 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.130931E+10 11379.06 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.201992E+10 15207.02 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.721301E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.263268E+10 17497.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.246152E+10 18043.10 12-JAN-10:00 0.00 0.00 0.00 0.00 0.00
February 0.957073E+09 14873.60 27-FEB-09:50 0.00 0.00 0.00 0.00 0.00
March 90299871.93 6697.08 01-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.112594E+10 11115.48 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.170884E+10 15117.62 15-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.634367E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.246152E+10 18043.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.176632E+10 12480.81 12-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.984118E+09 12269.46 27-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.405989E+09 8191.16 01-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.748526E+09 9528.50 29-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.124552E+10 11891.96 15-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.515047E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176632E+10 12480.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.337919E+11 54393.46 12-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.302154E+11 53675.47 27-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.164020E+11 51239.08 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.215662E+10 9215.67 03-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 13294.10 0.51 30-MAY-15:20 0.00 0.00 0.00 0.00 0.00
June 32189.03 0.51 30-JUN-20:45 0.00 0.00 0.00 0.00 0.00
July 31761.24 0.51 02-JUL-15:30 0.00 0.00 0.00 0.00 0.00
August 2803799.50 499.12 31-AUG-06:00 0.00 0.00 0.00 0.00 0.00
September 0.119726E+09 2206.27 29-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.418381E+10 9131.06 27-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.325190E+11 51610.98 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.408317E+11 52943.15 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160223E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13294.10 0.51   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.408317E+11 54393.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.107283E+11 12855.84 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.752455E+10 12855.19 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.477671E+10 12854.24 09-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.996792E+09 12852.86 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 50923000.14 4125.40 28-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 8745909.41 4518.39 24-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 11164539.75 4316.33 25-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 27736496.23 4791.75 29-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.751149E+09 12574.97 29-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.418124E+10 12855.07 21-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.957796E+10 12854.80 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.117369E+11 12855.14 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.503722E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8745909.41 4125.40   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117369E+11 12855.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111261E+11 12515.97 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.864169E+10 12515.25 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.625757E+10 12515.07 09-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.154858E+10 12514.06 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 71424297.52 4533.91 25-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 2808863.62 3659.20 25-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 5311674.40 3499.29 26-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 38256186.79 4233.43 19-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.107313E+10 12351.12 29-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.503315E+10 12515.14 21-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.102214E+11 12514.85 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.118837E+11 12515.20 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.559031E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2808863.62 3499.29   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118837E+11 12515.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.285866E+11 27680.43 12-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.608178E+10 18895.47 26-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.468770E+09 16590.47 01-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.188430E+11 21919.73 29-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.379122E+11 25979.60 15-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.918923E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379122E+11 27680.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.460573E+11 69342.91 16-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.358044E+11 69334.47 01-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.244354E+11 69317.17 02-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.507328E+10 67973.97 02-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 35931439.39 16837.10 06-MAY-15:07 0.00 0.00 0.00 0.00 0.00
June 5690006.31 12616.82 21-JUN-21:57 0.00 0.00 0.00 0.00 0.00
July 7950596.77 10345.14 31-JUL-21:57 0.00 0.00 0.00 0.00 0.00
August 33157924.22 25142.67 31-AUG-15:05 0.00 0.00 0.00 0.00 0.00
September 0.946242E+09 28789.55 26-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.138087E+11 69173.85 31-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.422631E+11 69337.48 24-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.501365E+11 69338.05 17-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.218608E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5690006.31 10345.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.501365E+11 69342.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106192E+11 12664.95 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.706959E+10 12664.28 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.390744E+10 12662.11 05-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.984244E+09 12585.93 04-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 31789685.88 4154.06 03-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 3744054.15 4162.79 27-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4380706.42 4470.29 01-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 20078002.73 4728.21 14-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 0.602611E+09 10787.03 27-SEP-15:01 0.00 0.00 0.00 0.00 0.00
October 0.369867E+10 12664.12 21-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.956898E+10 12663.88 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.117278E+11 12664.22 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.482385E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3744054.15 4154.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117278E+11 12664.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.109978E+11 12347.60 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.812408E+10 12346.87 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.520006E+10 12345.66 07-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.156061E+10 12343.43 04-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 47361739.64 3853.47 26-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 2043476.99 3679.76 25-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 1600883.56 2103.46 21-JUL-21:55 0.00 0.00 0.00 0.00 0.00
August 28184281.64 4107.95 20-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.857811E+09 11841.12 27-SEP-15:01 0.00 0.00 0.00 0.00 0.00
October 0.444499E+10 12346.73 21-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.102104E+11 12346.46 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.118679E+11 12346.81 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.533429E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1600883.56 2103.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118679E+11 12347.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.371274E+10 3937.53 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.269424E+10 3937.35 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.180468E+10 3937.42 19-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.461536E+09 3937.04 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 49370336.43 1008.01 07-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 2938639.01 1027.99 05-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4407011.11 1007.30 13-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 24627681.53 1503.05 30-AUG-08:62 0.00 0.00 0.00 0.00 0.00
September 0.375699E+09 3900.03 29-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.159572E+10 3937.23 25-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.337699E+10 3937.18 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.402607E+10 3937.23 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.181290E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2938639.01 1007.30   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402607E+10 3937.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.382395E+10 3804.13 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.302672E+10 3803.92 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.228823E+10 3804.00 19-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.671252E+09 3803.60 05-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 62078490.71 1036.41 08-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 1212989.36 944.31 15-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 2388592.20 1028.50 03-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 31922487.87 2072.70 31-AUG-08:62 0.00 0.00 0.00 0.00 0.00
September 0.510053E+09 3785.76 30-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.187134E+10 3803.80 25-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.356345E+10 3803.78 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.406672E+10 3803.83 25-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.199193E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1212989.36 944.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.406672E+10 3804.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150169E+11 20024.77 07-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.872480E+10 20024.52 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.466429E+10 20017.40 13-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.901297E+09 19911.70 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 60556546.04 5596.72 28-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 12777467.29 5222.51 16-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 13562485.81 5408.27 07-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 27547758.98 5544.56 18-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.563299E+09 14112.59 28-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.431923E+10 20023.94 25-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.128745E+11 20023.89 02-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.172478E+11 20023.65 25-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.644266E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 12777467.29 5222.51   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172478E+11 20024.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.197241E+10 0.197241E+10 36539.74 31-MAR-23:03 36539.74 0.00
April 0.00 0.00 0.620987E+11 0.620987E+11 50421.70 30-APR-23:20 50421.70 0.00
May 0.00 0.00 0.714947E+11 0.714947E+11 58188.26 31-MAY-23:05 58188.26 0.00
June 0.00 0.00 0.691695E+11 0.691624E+11 58643.99 01-JUN-05:15 58643.99 0.00
July 0.00 0.00 0.690349E+11 0.618016E+11 60476.66 01-JUL-05:13 53983.29 0.00
August 0.00 0.00 0.661186E+11 0.626988E+11 56481.89 01-AUG-07:00 53353.87 0.00
September 0.00 0.00 0.602229E+11 0.602229E+11 45764.68 30-SEP-05:15 45764.68 0.00
October 0.00 0.00 0.551998E+11 0.551998E+11 31633.74 31-OCT-05:30 31633.74 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.455311E+12 0.444651E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.714947E+11 0.714947E+11 60476.66   58643.99 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.228861E+10 0.228861E+10 46231.99 31-MAR-23:03 46231.99 0.00
April 0.00 0.00 0.358380E+11 0.358380E+11 63809.82 30-APR-23:03 63809.82 0.00
May 0.00 0.00 0.505395E+11 0.505395E+11 63809.82 01-MAY-17:23 63809.82 0.00
June 0.00 0.00 0.565989E+11 0.565976E+11 74221.18 01-JUN-16:10 74221.18 0.00
July 0.00 0.00 0.603495E+11 0.540421E+11 76541.78 01-JUL-20:10 68352.60 0.00
August 0.00 0.00 0.565249E+11 0.536150E+11 71483.46 01-AUG-16:10 67535.31 0.00
September 0.00 0.00 0.444114E+11 0.444114E+11 57912.94 30-SEP-16:05 57912.94 0.00
October 0.00 0.00 0.318854E+11 0.318854E+11 40019.83 31-OCT-16:40 40019.83 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.338436E+12 0.329218E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.603495E+11 0.565976E+11 76541.78   74221.18 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 0.478836E+09 0.478836E+09 21907.64 22-APR-16:10 21907.64 0.00
May 0.00 0.00 0.332680E+11 0.332680E+11 147431.63 31-MAY-18:03 147431.63 0.00
June 0.00 0.00 0.126537E+12 0.125554E+12 217466.52 29-JUN-20:00 210546.81 0.18
July 0.00 0.00 0.159515E+12 0.157099E+12 244676.48 29-JUL-18:03 210054.20 0.52
August 0.00 0.00 0.933007E+11 0.931520E+11 205710.39 11-AUG-19:10 205710.39 0.32
September 0.00 0.00 0.438856E+10 0.438856E+10 57277.58 02-SEP-18:00 57277.58 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.417488E+12 0.413940E+12       0.09
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.159515E+12 0.157099E+12 244676.48   210546.81 0.52



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 2616979.37 2616979.37 594.90 22-APR-14:20 594.90 0.00
May 0.00 0.00 0.187749E+10 0.187749E+10 14984.27 31-MAY-16:00 14984.27 0.00
June 0.00 0.00 0.875150E+10 0.866818E+10 20268.27 30-JUN-12:20 17681.75 0.13
July 0.00 0.00 0.107248E+11 0.105096E+11 19576.59 03-JUL-15:10 10122.63 0.39
August 0.00 0.00 0.644682E+10 0.640249E+10 17539.91 11-AUG-18:02 17539.91 0.23
September 0.00 0.00 0.192142E+09 0.192142E+09 4990.98 07-SEP-16:00 4990.98 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.279954E+11 0.276525E+11       0.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.107248E+11 0.105096E+11 20268.27   17681.75 0.39



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3002826.45 3002826.45 3456.20 22-JAN-09:04 3456.20 0.00
February 0.00 0.00 10943996.63 10705249.52 4196.49 11-FEB-19:04 4196.49 0.00
March 0.00 0.00 0.235378E+09 0.231857E+09 13665.12 28-MAR-15:02 13665.12 0.00
April 0.00 0.00 0.298456E+10 0.292097E+10 13681.20 18-APR-15:02 13681.20 0.04
May 0.00 0.00 0.534421E+10 0.493939E+10 14437.85 31-MAY-18:02 14437.85 0.21
June 0.00 0.00 0.797876E+10 0.585427E+10 14672.94 22-JUN-18:02 14672.94 0.78
July 0.00 0.00 0.790830E+10 0.492802E+10 14962.95 26-JUL-15:01 12706.94 0.92
August 0.00 0.00 0.586013E+10 0.370601E+10 14967.68 13-AUG-15:02 12707.02 0.81
September 0.00 0.00 0.141209E+10 0.944702E+09 13813.49 02-SEP-18:02 13813.49 0.32
October 0.00 0.00 77209575.93 59470141.29 13431.40 13-OCT-15:02 13431.40 0.01
November 0.00 0.00 3119513.88 3119513.88 2880.83 04-NOV-08:04 2880.83 0.00
December 0.00 0.00 1837285.95 1688269.36 3548.55 24-DEC-19:04 3548.55 0.00
                 
Annual Sum or Average 0.00 0.00 0.318195E+11 0.236032E+11       0.26
Minimum of Months 0.00 0.00 1837285.95 1688269.36 2880.83   2880.83 0.00
Maximum of Months 0.00 0.00 0.797876E+10 0.585427E+10 14967.68   14672.94 0.92



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2102655.24 2102655.24 3819.93 22-JAN-09:04 3819.93 0.00
February 0.00 0.00 7024243.77 6896742.40 4565.01 08-FEB-19:04 4565.01 0.00
March 0.00 0.00 31823022.88 30988473.96 9984.54 27-MAR-18:01 9984.54 0.00
April 0.00 0.00 0.153260E+10 0.150840E+10 12283.60 28-APR-15:02 12283.60 0.02
May 0.00 0.00 0.315291E+10 0.286982E+10 14150.08 09-MAY-20:01 14150.08 0.17
June 0.00 0.00 0.539385E+10 0.374820E+10 15446.04 28-JUN-21:51 13101.29 0.69
July 0.00 0.00 0.537998E+10 0.329496E+10 15953.38 06-JUL-17:32 15953.38 0.70
August 0.00 0.00 0.321582E+10 0.177348E+10 14134.02 01-AUG-21:51 12666.36 0.59
September 0.00 0.00 0.542942E+09 0.341978E+09 12677.01 02-SEP-19:41 12677.01 0.16
October 0.00 0.00 20797425.83 16424974.39 8895.12 03-OCT-15:02 8895.12 0.00
November 0.00 0.00 1226373.41 1226373.41 3159.45 04-NOV-08:04 3159.45 0.00
December 0.00 0.00 1391987.19 1281709.54 3195.98 24-DEC-19:04 3195.98 0.00
                 
Annual Sum or Average 0.00 0.00 0.192825E+11 0.135957E+11       0.20
Minimum of Months 0.00 0.00 1226373.41 1226373.41 3159.45   3159.45 0.00
Maximum of Months 0.00 0.00 0.539385E+10 0.374820E+10 15953.38   15953.38 0.70



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.422028E+10 0.422028E+10 40899.66 31-MAR-13:20 40899.66 0.00
April 0.00 0.00 0.351867E+11 0.351867E+11 64181.56 22-APR-13:20 64181.56 0.00
May 0.00 0.00 0.455757E+11 0.454764E+11 61116.90 12-MAY-13:15 61116.90 0.01
June 0.00 0.00 0.514512E+11 0.325493E+11 56929.73 30-JUN-12:30 49697.55 0.84
July 0.00 0.00 0.539631E+11 0.295432E+11 64460.04 23-JUL-13:30 49127.82 0.99
August 0.00 0.00 0.499388E+11 0.291545E+11 67963.16 25-AUG-13:30 54677.62 0.93
September 0.00 0.00 0.242808E+11 0.198310E+11 61022.06 09-SEP-13:10 52375.30 0.30
October 0.00 0.00 0.494406E+10 0.494406E+10 47516.46 03-OCT-12:50 47516.46 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.269561E+12 0.200905E+12       0.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.539631E+11 0.454764E+11 67963.16   64181.56 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 52117284.43 52117284.43 24147.22 09-JAN-09:04 24147.22 0.00
February 0.00 0.00 59420822.73 59357957.94 29692.34 11-FEB-09:01 29692.34 0.00
March 0.00 0.00 0.407010E+09 0.407010E+09 58522.73 22-MAR-18:02 58522.73 0.00
April 0.00 0.00 0.811985E+10 0.808531E+10 63911.09 30-APR-18:02 63911.09 0.01
May 0.00 0.00 0.290708E+11 0.284965E+11 68395.94 31-MAY-15:02 68395.94 0.06
June 0.00 0.00 0.432211E+11 0.365669E+11 74566.11 30-JUN-21:51 62404.54 0.55
July 0.00 0.00 0.453224E+11 0.341936E+11 75214.67 18-JUL-21:51 57829.79 0.63
August 0.00 0.00 0.311017E+11 0.228834E+11 73200.55 12-AUG-21:52 58354.26 0.53
September 0.00 0.00 0.114475E+11 0.797220E+10 62657.50 07-SEP-18:01 62657.50 0.40
October 0.00 0.00 0.171337E+10 0.148887E+10 59758.09 04-OCT-18:02 59758.09 0.03
November 0.00 0.00 46571621.01 46571621.01 27234.34 14-NOV-19:04 27234.34 0.00
December 0.00 0.00 35155540.58 35155540.58 31937.80 24-DEC-09:01 31937.80 0.00
                 
Annual Sum or Average 0.00 0.00 0.170597E+12 0.140287E+12       0.19
Minimum of Months 0.00 0.00 35155540.58 35155540.58 24147.22   24147.22 0.00
Maximum of Months 0.00 0.00 0.453224E+11 0.365669E+11 75214.67   68395.94 0.63



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2806730.70 2806730.70 3523.67 22-JAN-09:04 3523.67 0.00
February 0.00 0.00 13590458.02 13414853.22 4269.17 07-FEB-19:04 4269.17 0.00
March 0.00 0.00 0.409574E+09 0.394685E+09 12918.58 20-MAR-15:01 12918.58 0.01
April 0.00 0.00 0.284730E+10 0.275474E+10 12919.95 29-APR-18:01 12919.95 0.06
May 0.00 0.00 0.730143E+10 0.687268E+10 13634.72 31-MAY-18:02 13634.72 0.24
June 0.00 0.00 0.901863E+10 0.695474E+10 13873.15 27-JUN-15:02 11635.26 0.80
July 0.00 0.00 0.966335E+10 0.671080E+10 13818.26 26-JUL-15:01 12180.40 0.96
August 0.00 0.00 0.704057E+10 0.478007E+10 13794.95 13-AUG-15:02 12196.50 0.85
September 0.00 0.00 0.196288E+10 0.127387E+10 12954.99 02-SEP-18:02 12954.99 0.41
October 0.00 0.00 0.179546E+09 0.132343E+09 12789.84 04-OCT-08:62 12789.84 0.03
November 0.00 0.00 2403495.36 2403495.36 3059.82 04-NOV-08:04 3059.82 0.00
December 0.00 0.00 1590622.10 1465744.91 3363.02 24-DEC-09:04 2682.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.384437E+11 0.298940E+11       0.28
Minimum of Months 0.00 0.00 1590622.10 1465744.91 3059.82   2682.23 0.00
Maximum of Months 0.00 0.00 0.966335E+10 0.695474E+10 13873.15   13634.72 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1837742.01 1837742.01 3331.60 22-JAN-09:04 3331.60 0.00
February 0.00 0.00 7264750.64 7178868.61 3993.72 11-FEB-19:04 3993.72 0.00
March 0.00 0.00 0.104630E+09 98957766.06 10813.64 27-MAR-08:61 10813.64 0.00
April 0.00 0.00 0.126980E+10 0.121190E+10 11714.78 28-APR-15:02 11714.78 0.04
May 0.00 0.00 0.524135E+10 0.488245E+10 12471.47 14-MAY-20:41 12471.47 0.22
June 0.00 0.00 0.677613E+10 0.516035E+10 14004.85 30-JUN-21:51 11299.22 0.70
July 0.00 0.00 0.709816E+10 0.491412E+10 15509.45 11-JUL-08:22 15170.90 0.74
August 0.00 0.00 0.455910E+10 0.294840E+10 13415.54 12-AUG-21:52 10326.93 0.67
September 0.00 0.00 0.940911E+09 0.578549E+09 11535.46 07-SEP-18:01 11535.46 0.28
October 0.00 0.00 45176043.37 32528541.08 11138.88 04-OCT-08:62 11138.88 0.01
November 0.00 0.00 909331.70 909331.70 3024.12 04-NOV-08:04 3024.12 0.00
December 0.00 0.00 1229432.66 1148899.79 3338.62 24-DEC-19:04 3338.62 0.00
                 
Annual Sum or Average 0.00 0.00 0.260465E+11 0.198383E+11       0.22
Minimum of Months 0.00 0.00 909331.70 909331.70 3024.12   3024.12 0.00
Maximum of Months 0.00 0.00 0.709816E+10 0.516035E+10 15509.45   15170.90 0.74



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 146088.51 117842.74 291.85 22-JAN-09:04 102.81 0.00
February 0.00 0.00 1233426.58 1125484.95 771.48 09-FEB-19:04 521.94 0.00
March 0.00 0.00 44398467.36 43282675.32 3547.24 27-MAR-18:01 3547.24 0.00
April 0.00 0.00 0.716641E+09 0.699909E+09 3575.30 28-APR-15:02 3575.30 0.04
May 0.00 0.00 0.124089E+10 0.113562E+10 3772.90 31-MAY-18:02 3772.90 0.22
June 0.00 0.00 0.195159E+10 0.143864E+10 3845.81 24-JUN-15:01 3215.33 0.75
July 0.00 0.00 0.193161E+10 0.121228E+10 3992.73 02-JUL-08:61 3064.67 0.90
August 0.00 0.00 0.138083E+10 0.893057E+09 4114.21 13-AUG-08:61 3005.65 0.75
September 0.00 0.00 0.303287E+09 0.214719E+09 3610.09 02-SEP-18:02 3610.09 0.20
October 0.00 0.00 13826183.21 9834766.70 3341.28 13-OCT-15:02 3341.28 0.01
November 0.00 0.00 159680.41 159680.41 290.20 08-NOV-16:04 290.20 0.00
December 0.00 0.00 137731.89 93612.51 560.92 24-DEC-09:04 299.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.758475E+10 0.564884E+10       0.24
Minimum of Months 0.00 0.00 137731.89 93612.51 290.20   102.81 0.00
Maximum of Months 0.00 0.00 0.195159E+10 0.143864E+10 4114.21   3772.90 0.90



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 173670.09 112167.29 370.15 22-JAN-09:04 166.81 0.00
February 0.00 0.00 796325.23 678278.04 682.33 09-FEB-09:04 400.32 0.00
March 0.00 0.00 3408816.74 3270803.40 1423.93 28-MAR-15:03 1423.93 0.00
April 0.00 0.00 0.350095E+09 0.345432E+09 3175.42 28-APR-15:02 3175.42 0.01
May 0.00 0.00 0.685509E+09 0.616840E+09 4148.01 14-MAY-20:22 4148.01 0.17
June 0.00 0.00 0.134120E+10 0.905775E+09 4353.89 28-JUN-21:32 3909.15 0.69
July 0.00 0.00 0.132905E+10 0.804292E+09 4176.96 24-JUL-21:51 3222.24 0.69
August 0.00 0.00 0.729695E+09 0.396401E+09 3893.24 02-AUG-21:51 3380.74 0.56
September 0.00 0.00 98911381.87 64189273.39 3355.38 02-SEP-19:41 3355.38 0.09
October 0.00 0.00 4516792.09 3532129.72 1416.78 05-OCT-15:03 1237.69 0.00
November 0.00 0.00 67155.43 67155.43 314.48 04-NOV-08:04 314.48 0.00
December 0.00 0.00 136795.02 114374.37 526.80 24-DEC-09:04 292.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.454357E+10 0.314070E+10       0.19
Minimum of Months 0.00 0.00 67155.43 67155.43 314.48   166.81 0.00
Maximum of Months 0.00 0.00 0.134120E+10 0.905775E+09 4353.89   4148.01 0.69



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8409693.45 8409693.45 4983.22 22-JAN-19:04 4983.22 0.00
February 0.00 0.00 0.279524E+09 0.256650E+09 21517.02 15-FEB-16:01 21517.02 0.01
March 0.00 0.00 0.245093E+10 0.241849E+10 21526.63 11-MAR-16:02 21526.63 0.01
April 0.00 0.00 0.698283E+10 0.682567E+10 21529.82 16-APR-15:02 21529.82 0.06
May 0.00 0.00 0.917696E+10 0.840453E+10 22712.64 31-MAY-18:02 22712.64 0.26
June 0.00 0.00 0.111255E+11 0.797320E+10 23294.56 24-JUN-15:01 19291.30 0.76
July 0.00 0.00 0.122088E+11 0.765276E+10 23223.98 13-JUL-18:02 23223.98 0.92
August 0.00 0.00 0.106150E+11 0.708060E+10 22979.15 10-AUG-18:02 22979.15 0.82
September 0.00 0.00 0.459990E+10 0.326781E+10 21731.89 02-SEP-18:02 21731.89 0.52
October 0.00 0.00 0.117305E+10 0.106236E+10 21527.98 04-OCT-15:01 21527.98 0.05
November 0.00 0.00 29641570.50 29641570.50 20746.62 08-NOV-16:01 20746.62 0.00
December 0.00 0.00 3557625.53 3364208.95 4939.09 24-DEC-19:04 3713.42 0.00
                 
Annual Sum or Average 0.00 0.00 0.586541E+11 0.449835E+11       0.29
Minimum of Months 0.00 0.00 3557625.53 3364208.95 4939.09   3713.42 0.00
Maximum of Months 0.00 0.00 0.122088E+11 0.840453E+10 23294.56   23223.98 0.92



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 289400.80 938714.21 12-JAN-09:03
February 0.00 0.00 01-FEB-00:03 253085.67 883773.62 27-FEB-09:03
March 0.00 0.00 01-MAR-00:05 134880.24 781255.58 01-MAR-09:03
April 0.00 0.00 01-APR-00:10 35790.37 315578.24 03-APR-08:61
May 0.00 0.00 01-MAY-00:05 18427.65 125559.00 19-MAY-07:00
June 0.00 0.00 01-JUN-00:05 14044.99 114100.81 02-JUN-06:20
July 0.00 0.00 01-JUL-00:10 13717.36 127725.82 04-JUL-08:04
August 0.00 0.00 01-AUG-00:05 20438.76 139165.60 29-AUG-08:05
September 0.00 0.00 01-SEP-00:05 23023.63 136273.35 04-SEP-08:04
October 0.00 0.00 01-OCT-00:10 64851.56 308500.13 27-OCT-08:03
November 0.00 0.00 01-NOV-00:05 274033.95 843159.59 29-NOV-09:03
December 0.00 0.00 01-DEC-00:03 335254.77 898377.12 15-DEC-09:03
             
Annual Sum or Average 0.00     122409.02    
Minimum of Months 0.00 0.00   13717.36 114100.81  
Maximum of Months 0.00 0.00   335254.77 938714.21  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 34.91 27729.75 05-JAN-09:04 0.00 0.00 01-JAN-00:05
February 335.20 45067.10 08-FEB-16:04 0.00 0.00 01-FEB-00:03
March 3962.90 90592.65 22-MAR-15:01 0.00 0.00 01-MAR-00:05
April 26500.28 187921.09 22-APR-15:03 0.00 0.00 01-APR-00:10
May 57660.07 321511.18 31-MAY-15:03 0.00 0.00 01-MAY-00:05
June 110711.00 419566.85 21-JUN-15:05 0.00 0.00 01-JUN-00:05
July 122850.01 446965.72 29-JUL-18:03 0.00 0.00 01-JUL-00:10
August 84875.26 393262.12 11-AUG-18:03 0.00 0.00 01-AUG-00:05
September 22831.22 207945.00 02-SEP-15:03 0.00 0.00 01-SEP-00:05
October 4202.67 118386.79 03-OCT-15:02 0.00 0.00 01-OCT-00:10
November 57.08 30316.92 15-NOV-09:04 0.00 0.00 01-NOV-00:05
December 22.38 30544.97 24-DEC-16:04 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 36422.54     0.00    
Minimum of Months 22.38 27729.75   0.00 0.00  
Maximum of Months 122850.01 446965.72   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 32956.75 68429.44 11-JAN-08:00
February 0.00 0.00 01-FEB-00:03 32963.39 68429.36 03-FEB-08:00
March 0.00 0.00 01-MAR-00:05 32987.36 68443.19 13-MAR-07:00
April 0.00 0.00 01-APR-00:10 32809.74 68378.89 06-APR-06:20
May 0.00 0.00 01-MAY-00:05 32533.06 68507.71 08-MAY-07:00
June 0.00 0.00 01-JUN-00:05 31339.38 66781.25 01-JUN-06:40
July 0.00 0.00 01-JUL-00:10 30149.71 63898.83 03-JUL-06:20
August 0.00 0.00 01-AUG-00:05 29451.49 61958.36 01-AUG-07:00
September 0.00 0.00 01-SEP-00:05 29360.13 61562.20 29-SEP-06:40
October 0.00 0.00 01-OCT-00:10 29958.71 63360.81 31-OCT-06:15
November 0.00 0.00 01-NOV-00:05 31166.75 65934.97 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 32440.51 68426.44 29-DEC-08:00
             
Annual Sum or Average 0.00     31501.53    
Minimum of Months 0.00 0.00   29360.13 61562.20  
Maximum of Months 0.00 0.00   32987.36 68507.71  



Table of Contents

Report: FanReportMonthly

For: SWHSYS1 HPWH FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.148176E+10 0.10 553.22 01-MAR-00:05 0.10
April 0.955026E+09 0.07 553.22 01-APR-01:07 0.10
May 0.809860E+09 0.07 553.22 01-MAY-03:10 0.10
June 0.684162E+09 0.06 553.22 01-JUN-05:15 0.10
July 0.665144E+09 0.06 553.22 01-JUL-05:13 0.10
August 0.678910E+09 0.06 553.22 01-AUG-04:07 0.10
September 0.754182E+09 0.06 553.22 01-SEP-03:07 0.10
October 0.985779E+09 0.07 553.22 01-OCT-01:07 0.10
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.701482E+10 0.05      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.148176E+10 0.10 553.22   0.10



Table of Contents

Report: FanReportMonthly

For: SWHSYSLAUNDRY HPWH FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.187455E+10 0.10 700.51 01-MAR-00:05 0.10
April 0.545469E+09 0.06 700.51 01-APR-16:05 0.10
May 0.558189E+09 0.06 700.51 01-MAY-16:10 0.10
June 0.539093E+09 0.05 700.51 01-JUN-16:10 0.10
July 0.556892E+09 0.05 700.51 01-JUL-16:10 0.10
August 0.557232E+09 0.05 700.51 01-AUG-16:10 0.10
September 0.540295E+09 0.06 700.51 01-SEP-16:10 0.10
October 0.563595E+09 0.06 700.51 01-OCT-16:10 0.10
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.573532E+10 0.04      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.187455E+10 0.10 700.51   0.10



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.71 1299.30 01-JAN-00:05 0.89
February 0.244774E+10 0.71 1299.30 01-FEB-00:07 0.89
March 0.271000E+10 0.71 1299.30 01-MAR-00:05 0.90
April 0.262258E+10 0.71 1299.30 01-APR-00:40 0.89
May 0.271000E+10 0.71 1299.30 01-MAY-00:50 0.89
June 0.262258E+10 0.70 1299.30 01-JUN-02:30 0.89
July 0.271000E+10 0.70 1299.30 01-JUL-00:30 0.88
August 0.271000E+10 0.70 1299.30 01-AUG-00:50 0.88
September 0.262258E+10 0.70 1299.30 01-SEP-00:10 0.89
October 0.271000E+10 0.71 1299.30 01-OCT-00:10 0.89
November 0.262258E+10 0.71 1299.30 01-NOV-00:10 0.89
December 0.271000E+10 0.71 1299.30 01-DEC-00:03 0.90
           
Annual Sum or Average 0.319080E+11 0.71      
Minimum of Months 0.244774E+10 0.70 1299.30   0.88
Maximum of Months 0.271000E+10 0.71 1299.30   0.90



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.310356E+11 0.78 16545.48 19-JAN-21:20 0.96
February 0.284025E+11 0.79 17329.47 08-FEB-21:10 0.98
March 0.330165E+11 0.81 18501.42 22-MAR-21:10 1.02
April 0.337439E+11 0.83 22826.62 21-APR-21:10 1.16
May 0.368886E+11 0.86 23806.32 12-MAY-21:10 1.19
June 0.372904E+11 0.87 24227.56 12-JUN-21:10 1.19
July 0.383043E+11 0.87 24921.23 12-JUL-21:10 1.21
August 0.376084E+11 0.86 26051.86 25-AUG-21:10 1.24
September 0.343469E+11 0.84 22321.93 08-SEP-21:10 1.14
October 0.338241E+11 0.82 19837.62 03-OCT-21:10 1.06
November 0.301028E+11 0.78 17255.88 01-NOV-20:20 0.98
December 0.304991E+11 0.78 16237.05 24-DEC-20:10 0.94
           
Annual Sum or Average 0.405063E+12 0.82      
Minimum of Months 0.284025E+11 0.78 16237.05   0.94
Maximum of Months 0.383043E+11 0.87 26051.86   1.24



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:05 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:10 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:05 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.437273E+09 0.56 822.20 01-JAN-09:01 0.58
February 0.321388E+09 0.51 822.20 01-FEB-09:01 0.59
March 0.244639E+09 0.44 822.20 01-MAR-09:01 0.59
April 0.258396E+09 0.48 822.20 01-APR-08:61 0.58
May 0.354791E+09 0.53 822.20 01-MAY-08:62 0.58
June 0.481159E+09 0.54 822.20 01-JUN-08:61 0.58
July 0.437334E+09 0.54 822.20 01-JUL-08:61 0.58
August 0.348620E+09 0.52 822.20 01-AUG-08:61 0.58
September 0.156453E+09 0.45 822.20 01-SEP-08:62 0.58
October 0.220254E+09 0.45 822.20 01-OCT-15:02 0.58
November 0.397316E+09 0.56 822.20 01-NOV-08:61 0.58
December 0.466619E+09 0.57 822.20 01-DEC-09:01 0.59
           
Annual Sum or Average 0.412424E+10 0.51      
Minimum of Months 0.156453E+09 0.44 822.20   0.58
Maximum of Months 0.481159E+09 0.57 822.20   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.421020E+09 0.56 737.69 01-JAN-09:01 0.58
February 0.336377E+09 0.55 737.69 01-FEB-09:01 0.59
March 0.270419E+09 0.50 737.69 01-MAR-09:01 0.59
April 0.186272E+09 0.44 737.69 01-APR-08:61 0.58
May 0.220583E+09 0.42 737.69 01-MAY-08:62 0.58
June 0.312397E+09 0.41 737.69 01-JUN-08:61 0.58
July 0.291027E+09 0.41 737.69 01-JUL-08:61 0.58
August 0.190498E+09 0.38 737.69 01-AUG-08:61 0.58
September 0.110889E+09 0.41 737.69 01-SEP-15:02 0.58
October 0.233662E+09 0.48 737.69 03-OCT-08:61 0.58
November 0.389437E+09 0.56 737.69 01-NOV-08:61 0.58
December 0.438757E+09 0.57 737.69 01-DEC-09:01 0.59
           
Annual Sum or Average 0.340134E+10 0.47      
Minimum of Months 0.110889E+09 0.38 737.69   0.58
Maximum of Months 0.438757E+09 0.57 737.69   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.170205E+10 0.55 1223.83 12-JAN-16:00 0.59
February 0.419115E+09 0.21 958.76 26-FEB-06:00 0.59
March 0.238093E+09 0.08 1600.37 31-MAR-13:20 0.59
April 0.160749E+10 0.41 3019.14 22-APR-13:20 0.58
May 0.211465E+10 0.54 3205.40 31-MAY-13:30 0.58
June 0.235575E+10 0.58 1978.49 08-JUN-12:40 0.58
July 0.234005E+10 0.58 3072.36 23-JUL-13:30 0.58
August 0.228199E+10 0.56 3264.50 25-AUG-13:05 0.58
September 0.125097E+10 0.41 3459.98 09-SEP-13:10 0.58
October 0.269766E+09 0.11 1797.07 03-OCT-12:50 0.58
November 0.121240E+10 0.47 1053.53 29-NOV-05:00 0.59
December 0.210256E+10 0.58 1174.71 15-DEC-05:00 0.59
           
Annual Sum or Average 0.178949E+11 0.42      
Minimum of Months 0.238093E+09 0.08 958.76   0.58
Maximum of Months 0.235575E+10 0.58 3459.98   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.179842E+10 0.47 3809.96 01-JAN-09:01 0.59
February 0.137253E+10 0.44 3809.96 01-FEB-09:01 0.59
March 0.107382E+10 0.42 3809.96 01-MAR-09:01 0.59
April 0.816355E+09 0.41 3809.96 01-APR-15:02 0.59
May 0.179199E+10 0.38 3809.96 01-MAY-08:62 0.58
June 0.284006E+10 0.37 3809.96 01-JUN-08:61 0.58
July 0.267084E+10 0.37 3809.96 01-JUL-08:61 0.58
August 0.177518E+10 0.35 3809.96 01-AUG-08:61 0.58
September 0.846025E+09 0.40 3809.96 01-SEP-08:62 0.58
October 0.800405E+09 0.41 3809.96 01-OCT-08:62 0.58
November 0.160292E+10 0.45 3809.96 01-NOV-08:61 0.59
December 0.186530E+10 0.48 3809.96 01-DEC-09:01 0.59
           
Annual Sum or Average 0.192538E+11 0.41      
Minimum of Months 0.800405E+09 0.35 3809.96   0.58
Maximum of Months 0.284006E+10 0.48 3809.96   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.418727E+09 0.56 776.15 01-JAN-09:01 0.58
February 0.294656E+09 0.50 776.15 01-FEB-09:01 0.59
March 0.213604E+09 0.44 776.15 01-MAR-09:01 0.59
April 0.241932E+09 0.51 776.15 01-APR-15:02 0.58
May 0.469382E+09 0.55 776.15 01-MAY-08:62 0.58
June 0.537014E+09 0.56 776.15 01-JUN-08:61 0.58
July 0.532812E+09 0.56 776.15 01-JUL-08:61 0.58
August 0.410578E+09 0.54 776.15 01-AUG-08:61 0.58
September 0.177765E+09 0.47 776.15 01-SEP-08:62 0.58
October 0.198920E+09 0.45 776.15 01-OCT-08:62 0.58
November 0.382061E+09 0.55 776.15 01-NOV-08:61 0.58
December 0.449134E+09 0.57 776.15 01-DEC-09:01 0.59
           
Annual Sum or Average 0.432658E+10 0.52      
Minimum of Months 0.177765E+09 0.44 776.15   0.58
Maximum of Months 0.537014E+09 0.57 776.15   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.408077E+09 0.56 703.21 01-JAN-09:01 0.58
February 0.310796E+09 0.54 703.21 01-FEB-09:01 0.59
March 0.226997E+09 0.44 703.21 01-MAR-09:01 0.59
April 0.170226E+09 0.45 703.21 01-APR-08:61 0.58
May 0.353214E+09 0.49 703.21 01-MAY-08:62 0.58
June 0.416388E+09 0.43 703.21 01-JUN-08:61 0.58
July 0.393009E+09 0.43 703.21 01-JUL-08:61 0.58
August 0.274235E+09 0.43 703.21 01-AUG-08:61 0.58
September 0.123382E+09 0.43 703.21 01-SEP-08:62 0.58
October 0.206197E+09 0.46 703.21 01-OCT-08:62 0.58
November 0.377426E+09 0.56 703.21 01-NOV-08:61 0.58
December 0.425273E+09 0.57 703.21 01-DEC-09:01 0.59
           
Annual Sum or Average 0.368522E+10 0.48      
Minimum of Months 0.123382E+09 0.43 703.21   0.58
Maximum of Months 0.425273E+09 0.57 703.21   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.132246E+09 0.57 214.95 01-JAN-09:01 0.58
February 98553249.96 0.55 214.95 01-FEB-09:01 0.58
March 75777514.49 0.47 214.95 01-MAR-09:01 0.59
April 70577031.52 0.48 214.95 01-APR-08:61 0.58
May 85325018.67 0.52 214.95 01-MAY-15:02 0.58
June 0.119165E+09 0.54 214.95 01-JUN-08:61 0.58
July 0.108554E+09 0.53 214.95 01-JUL-08:61 0.58
August 84110720.86 0.51 214.95 01-AUG-08:61 0.58
September 43684199.98 0.44 214.95 01-SEP-15:02 0.58
October 69856798.80 0.48 214.95 03-OCT-08:61 0.58
November 0.119707E+09 0.57 214.95 01-NOV-08:61 0.58
December 0.137683E+09 0.57 214.95 01-DEC-09:01 0.59
           
Annual Sum or Average 0.114524E+10 0.52      
Minimum of Months 43684199.98 0.44 214.95   0.58
Maximum of Months 0.137683E+09 0.57 214.95   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.127746E+09 0.57 190.74 01-JAN-09:01 0.58
February 0.100877E+09 0.57 190.74 01-FEB-09:01 0.58
March 83439437.03 0.53 190.74 01-MAR-09:01 0.59
April 53636096.51 0.45 190.74 01-APR-08:61 0.58
May 51564919.29 0.42 190.74 01-MAY-15:02 0.58
June 78927610.02 0.41 190.74 01-JUN-08:61 0.58
July 72706402.28 0.41 190.74 01-JUL-08:61 0.58
August 45002418.14 0.38 190.74 01-AUG-08:61 0.58
September 34151980.41 0.41 190.74 01-SEP-15:02 0.58
October 73157289.29 0.51 190.74 03-OCT-08:61 0.58
November 0.116520E+09 0.57 190.74 01-NOV-08:61 0.58
December 0.129590E+09 0.57 190.74 01-DEC-09:01 0.59
           
Annual Sum or Average 0.967320E+09 0.48      
Minimum of Months 34151980.41 0.38 190.74   0.58
Maximum of Months 0.129590E+09 0.57 190.74   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.626546E+09 0.53 1288.93 01-JAN-09:01 0.58
February 0.412499E+09 0.48 1288.93 01-FEB-09:01 0.59
March 0.391729E+09 0.48 1288.93 01-MAR-09:01 0.59
April 0.494234E+09 0.52 1288.93 01-APR-15:02 0.58
May 0.580001E+09 0.54 1288.93 01-MAY-08:62 0.58
June 0.641470E+09 0.54 1288.93 01-JUN-08:61 0.58
July 0.654202E+09 0.54 1288.93 01-JUL-08:61 0.58
August 0.612569E+09 0.53 1288.93 01-AUG-08:61 0.58
September 0.349353E+09 0.49 1288.93 01-SEP-08:62 0.58
October 0.313321E+09 0.45 1288.93 01-OCT-08:62 0.58
November 0.551881E+09 0.52 1288.93 01-NOV-08:61 0.58
December 0.699656E+09 0.56 1288.93 01-DEC-09:01 0.59
           
Annual Sum or Average 0.632746E+10 0.52      
Minimum of Months 0.313321E+09 0.45 1288.93   0.58
Maximum of Months 0.699656E+09 0.56 1288.93   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.789587E+09 0.717735E+09 1979.65 12-JAN-09:13 1799.50 1799.50 49.20 6.74
February 0.611699E+09 0.556034E+09 1735.82 27-FEB-09:03 1577.86 1577.86 49.19 6.40
March 0.225203E+09 0.204710E+09 1328.73 01-MAR-05:00 1207.81 1207.81 51.50 5.75
April 8793869.42 7993627.30 70.21 03-APR-08:61 63.82 63.82 35.08 1.60
May 2899126.66 2635306.13 11.45 25-MAY-08:07 10.40 10.40 32.47 0.62
June 1911392.74 1737456.00 9.59 01-JUN-06:20 8.72 8.72 31.27 0.56
July 1968414.08 1789288.40 11.90 04-JUL-08:04 10.82 10.82 31.26 0.63
August 3106303.06 2823629.49 14.21 29-AUG-08:05 12.92 12.92 32.28 0.70
September 4310737.42 3918460.32 13.67 04-SEP-08:04 12.43 12.43 31.99 0.68
October 22627745.40 20568620.56 76.77 27-OCT-08:61 69.79 69.79 38.15 1.67
November 0.663843E+09 0.603433E+09 1638.74 29-NOV-10:20 1489.62 1489.62 51.54 6.25
December 0.959195E+09 0.871909E+09 1820.70 15-DEC-09:02 1655.02 1655.02 49.92 6.52
                 
Annual Sum or Average 0.329515E+10 0.299529E+10            
Minimum of Months 1911392.74 1737456.00 9.59   8.72 8.72 31.26 0.56
Maximum of Months 0.959195E+09 0.871909E+09 1979.65   1799.50 1799.50 51.54 6.74



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 4443781.77 4039397.63 1393.74 27-JAN-09:04 1266.91 1266.91 8.40 2.45
February 25291329.05 22989818.11 1986.39 08-FEB-16:04 1805.63 1805.63 8.40 3.82
March 0.414777E+09 0.377033E+09 2785.93 22-MAR-15:01 2532.41 2532.41 8.40 6.31
April 0.258591E+10 0.235060E+10 3185.74 13-APR-15:02 2895.84 2895.84 8.40 8.17
May 0.487400E+10 0.443047E+10 3578.24 31-MAY-15:03 3252.62 3252.62 7.55 11.12
June 0.627004E+10 0.569946E+10 3968.40 21-JUN-18:03 3607.28 3607.28 6.92 16.94
July 0.665550E+10 0.604985E+10 4000.12 12-JUL-18:03 3636.11 3636.11 7.11 17.38
August 0.562907E+10 0.511682E+10 3916.39 11-AUG-15:13 3560.00 3560.00 7.03 16.16
September 0.242548E+10 0.220476E+10 3348.62 02-SEP-15:03 3043.89 3043.89 8.24 9.18
October 0.492660E+09 0.447828E+09 2964.57 03-OCT-15:02 2694.80 2694.80 8.40 7.06
November 5540850.54 5036633.14 1388.73 18-NOV-19:04 1262.36 1262.36 8.40 2.44
December 2729747.82 2481340.77 1380.74 31-DEC-19:04 1255.09 1255.09 8.40 2.43
                 
Annual Sum or Average 0.293854E+11 0.267114E+11            
Minimum of Months 2729747.82 2481340.77 1380.74   1255.09 1255.09 6.92 2.43
Maximum of Months 0.665550E+10 0.604985E+10 4000.12   3636.11 3636.11 8.40 17.38



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 20474304.76 18611143.03 3340.80 01-JAN-09:03 3036.78 3036.78 8.57 23.65
February 0.449003E+09 0.408144E+09 3340.80 01-FEB-19:04 3036.78 3036.78 8.54 23.65
March 0.256208E+10 0.232893E+10 3340.80 01-MAR-09:04 3036.78 3036.78 8.48 23.65
April 0.646442E+10 0.587615E+10 3340.80 01-APR-08:03 3036.78 3036.78 8.46 23.65
May 0.892794E+10 0.811550E+10 3340.80 01-MAY-00:05 3036.78 3036.78 8.51 23.65
June 0.864732E+10 0.786041E+10 3340.80 01-JUN-00:05 3036.78 3036.78 8.92 23.65
July 0.894799E+10 0.813372E+10 3340.80 01-JUL-00:10 3036.78 3036.78 9.04 23.65
August 0.893195E+10 0.811914E+10 3340.80 01-AUG-00:05 3036.78 3036.78 9.20 23.65
September 0.749059E+10 0.680895E+10 3340.80 01-SEP-00:05 3036.78 3036.78 8.56 23.65
October 0.290637E+10 0.264189E+10 3340.80 01-OCT-06:40 3036.78 3036.78 8.42 23.65
November 63761471.23 57959177.35 3340.80 01-NOV-08:04 3036.78 3036.78 8.63 23.65
December 13983616.07 12711107.01 3340.80 01-DEC-09:06 3036.78 3036.78 8.48 23.65
                 
Annual Sum or Average 0.554259E+11 0.503821E+11            
Minimum of Months 13983616.07 12711107.01 3340.80   3036.78 3036.78 8.42 23.65
Maximum of Months 0.894799E+10 0.813372E+10 3340.80   3036.78 3036.78 9.20 23.65



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 45.91 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 46.93 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 47.20 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 50.53 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 50.39 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 50.64 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 51.28 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 51.29 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 51.41 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 50.58 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 50.87 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 47.39 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 45.91 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 51.41 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 47.88 82.20 289400.80 938714.21 12-JAN-09:03
February 0.00 0.00 01-FEB-00:03 46.77 82.20 253085.67 883773.62 27-FEB-09:03
March 0.00 0.00 01-MAR-00:05 51.34 82.20 134880.24 781255.58 01-MAR-09:03
April 0.00 0.00 01-APR-00:10 50.98 82.20 35790.37 315578.24 03-APR-08:61
May 0.00 0.00 01-MAY-00:05 45.13 79.95 18427.65 125559.00 19-MAY-07:00
June 0.00 0.00 01-JUN-00:05 26.13 79.40 14044.99 114100.81 02-JUN-06:20
July 0.00 0.00 01-JUL-00:10 26.75 26.75 13717.36 127725.82 04-JUL-08:04
August 0.00 0.00 01-AUG-00:05 30.45 30.45 20438.76 139165.60 29-AUG-08:05
September 0.00 0.00 01-SEP-00:05 31.92 79.72 23023.63 136273.35 04-SEP-08:04
October 0.00 0.00 01-OCT-00:10 65.46 80.84 64851.56 308500.13 27-OCT-08:03
November 0.00 0.00 01-NOV-00:05 51.67 82.20 274033.95 843159.59 29-NOV-09:03
December 0.00 0.00 01-DEC-00:03 52.19 82.20 335254.77 898377.12 15-DEC-09:03
                 
Annual Sum or Average 0.00         122409.02    
Minimum of Months 0.00 0.00   26.13 26.75 13717.36 114100.81  
Maximum of Months 0.00 0.00   65.46 82.20 335254.77 938714.21  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 34.91 27729.75 05-JAN-09:04 8.65 8.37 0.00 0.00 01-JAN-00:05
February 335.20 45067.10 08-FEB-16:04 8.82 8.37 0.00 0.00 01-FEB-00:03
March 3962.90 90592.65 22-MAR-15:01 9.28 8.37 0.00 0.00 01-MAR-00:05
April 26500.28 187921.09 22-APR-15:03 10.27 8.37 0.00 0.00 01-APR-00:10
May 57660.07 321511.18 31-MAY-15:03 10.76 7.51 0.00 0.00 01-MAY-00:05
June 110711.00 419566.85 21-JUN-15:05 11.18 6.94 0.00 0.00 01-JUN-00:05
July 122850.01 446965.72 29-JUL-18:03 11.21 6.70 0.00 0.00 01-JUL-00:10
August 84875.26 393262.12 11-AUG-18:03 10.85 6.88 0.00 0.00 01-AUG-00:05
September 22831.22 207945.00 02-SEP-15:03 10.30 8.20 0.00 0.00 01-SEP-00:05
October 4202.67 118386.79 03-OCT-15:02 9.56 8.37 0.00 0.00 01-OCT-00:10
November 57.08 30316.92 15-NOV-09:04 8.68 8.37 0.00 0.00 01-NOV-00:05
December 22.38 30544.97 24-DEC-16:04 8.68 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 36422.54         0.00    
Minimum of Months 22.38 27729.75   8.65 6.70 0.00 0.00  
Maximum of Months 122850.01 446965.72   11.21 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 45.91 59.99 32956.75 68429.44 11-JAN-08:00
February 0.00 0.00 01-FEB-00:03 46.93 59.73 32963.39 68429.36 03-FEB-08:00
March 0.00 0.00 01-MAR-00:05 47.20 59.74 32987.36 68443.19 13-MAR-07:00
April 0.00 0.00 01-APR-00:10 50.53 59.81 32809.74 68378.89 06-APR-06:20
May 0.00 0.00 01-MAY-00:05 50.39 59.97 32533.06 68507.71 08-MAY-07:00
June 0.00 0.00 01-JUN-00:05 50.64 60.00 31339.38 66781.25 01-JUN-06:40
July 0.00 0.00 01-JUL-00:10 51.28 59.99 30149.71 63898.83 03-JUL-06:20
August 0.00 0.00 01-AUG-00:05 51.29 59.97 29451.49 61958.36 01-AUG-07:00
September 0.00 0.00 01-SEP-00:05 51.41 59.97 29360.13 61562.20 29-SEP-06:40
October 0.00 0.00 01-OCT-00:10 50.58 59.95 29958.71 63360.81 31-OCT-06:15
November 0.00 0.00 01-NOV-00:05 50.87 59.74 31166.75 65934.97 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 47.39 59.74 32440.51 68426.44 29-DEC-08:00
                 
Annual Sum or Average 0.00         31501.53    
Minimum of Months 0.00 0.00   45.91 59.73 29360.13 61562.20  
Maximum of Months 0.00 0.00   51.41 60.00 32987.36 68507.71  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.605162E+12 0.00 0.00 0.310356E+11 0.00 0.00
February 0.497869E+12 0.00 0.00 0.284025E+11 0.00 0.00
March 0.293032E+12 0.00 0.00 0.330165E+11 0.00 0.00
April 0.788826E+11 0.00 0.478836E+09 0.337439E+11 0.00 0.00
May 0.492175E+11 0.00 0.332680E+11 0.368886E+11 0.00 0.00
June 0.365383E+11 0.00 0.126537E+12 0.372904E+11 0.00 0.00
July 0.368596E+11 0.00 0.159515E+12 0.383043E+11 0.00 0.00
August 0.547681E+11 0.00 0.933007E+11 0.376084E+11 0.00 0.00
September 0.540940E+11 0.00 0.438856E+10 0.343469E+11 0.00 0.00
October 0.131446E+12 0.00 0.00 0.338241E+11 0.00 0.00
November 0.561331E+12 0.00 0.00 0.301028E+11 0.00 0.00
December 0.701737E+12 0.00 0.00 0.304991E+11 0.00 0.00
             
Annual Sum or Average 0.310094E+13 0.00 0.417488E+12 0.405063E+12 0.00 0.00
Minimum of Months 0.365383E+11 0.00 0.00 0.284025E+11 0.00 0.00
Maximum of Months 0.701737E+12 0.00 0.159515E+12 0.383043E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.337919E+11 0.00 0.00 0.271000E+10 0.00 0.00
February 0.302154E+11 0.00 0.00 0.244774E+10 0.00 0.00
March 0.164020E+11 0.00 0.00 0.271000E+10 0.00 0.00
April 0.215662E+10 0.00 2616979.37 0.262258E+10 0.00 0.00
May 13294.10 0.00 0.187749E+10 0.271000E+10 0.00 0.00
June 32189.03 0.00 0.875150E+10 0.262258E+10 0.00 0.00
July 31761.24 0.00 0.107248E+11 0.271000E+10 0.00 0.00
August 2803799.50 0.00 0.644682E+10 0.271000E+10 0.00 0.00
September 0.119726E+09 0.00 0.192142E+09 0.262258E+10 0.00 0.00
October 0.418381E+10 0.00 0.00 0.271000E+10 0.00 0.00
November 0.325190E+11 0.00 0.00 0.262258E+10 0.00 0.00
December 0.408317E+11 0.00 0.00 0.271000E+10 0.00 0.00
             
Annual Sum or Average 0.160223E+12 0.00 0.279954E+11 0.319080E+11 0.00 0.00
Minimum of Months 13294.10 0.00 0.00 0.244774E+10 0.00 0.00
Maximum of Months 0.408317E+11 0.00 0.107248E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.310356E+11 0.00 0.605162E+12 0.804626E+12 0.00 0.00 0.00 0.00
February 0.284025E+11 0.00 0.497869E+12 0.682747E+12 0.00 0.00 0.00 0.00
March 0.330165E+11 0.00 0.293032E+12 0.839225E+12 0.00 0.00 0.00 0.00
April 0.337439E+11 0.478836E+09 0.788826E+11 0.571454E+12 0.00 0.00 0.00 0.00
May 0.368886E+11 0.332680E+11 0.492175E+11 0.179070E+12 0.00 0.00 0.00 0.00
June 0.372904E+11 0.126537E+12 0.365383E+11 0.193299E+11 0.178457E+09 0.00 0.00 0.00
July 0.383043E+11 0.159515E+12 0.368596E+11 0.123250E+11 0.865165E+09 0.00 0.00 0.00
August 0.376084E+11 0.933007E+11 0.547681E+11 0.494819E+11 0.00 0.00 0.00 0.00
September 0.343469E+11 0.438856E+10 0.540940E+11 0.334877E+12 0.00 0.00 0.00 0.00
October 0.338241E+11 0.00 0.131446E+12 0.724417E+12 0.00 0.00 0.00 0.00
November 0.301028E+11 0.00 0.561331E+12 0.802780E+12 0.00 0.00 0.00 0.00
December 0.304991E+11 0.00 0.701737E+12 0.759287E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.405063E+12 0.417488E+12 0.310094E+13 0.577962E+13 0.104362E+10 0.00 0.00 0.00
Minimum of Months 0.284025E+11 0.00 0.365383E+11 0.123250E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.383043E+11 0.159515E+12 0.701737E+12 0.839225E+12 0.865165E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.00 0.337919E+11 0.716220E+11 0.00 0.00 0.00 0.00
February 0.244774E+10 0.00 0.302154E+11 0.601875E+11 0.00 0.00 0.00 0.00
March 0.271000E+10 0.00 0.164020E+11 0.743703E+11 0.00 0.00 0.00 0.00
April 0.262258E+10 2616979.37 0.215662E+10 0.544391E+11 0.00 0.00 0.00 0.00
May 0.271000E+10 0.187749E+10 13294.10 0.225347E+11 0.00 0.00 0.00 0.00
June 0.262258E+10 0.875150E+10 32189.03 0.563671E+10 0.104584E+09 0.00 0.00 0.00
July 0.271000E+10 0.107248E+11 31761.24 0.479875E+10 0.278699E+09 0.00 0.00 0.00
August 0.271000E+10 0.644682E+10 2803799.50 0.103310E+11 20121095.44 0.00 0.00 0.00
September 0.262258E+10 0.192142E+09 0.119726E+09 0.342303E+11 0.00 0.00 0.00 0.00
October 0.271000E+10 0.00 0.418381E+10 0.657283E+11 0.00 0.00 0.00 0.00
November 0.262258E+10 0.00 0.325190E+11 0.713916E+11 0.00 0.00 0.00 0.00
December 0.271000E+10 0.00 0.408317E+11 0.681401E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.279954E+11 0.160223E+12 0.543410E+12 0.403405E+09 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.00 13294.10 0.479875E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.107248E+11 0.408317E+11 0.743703E+11 0.278699E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.310356E+11 0.605162E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.284025E+11 0.497869E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.330165E+11 0.293032E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.337439E+11 0.788826E+11 0.478836E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.368886E+11 0.492175E+11 0.332680E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.372904E+11 0.365383E+11 0.126537E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.383043E+11 0.368596E+11 0.159515E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.376084E+11 0.547681E+11 0.933007E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.343469E+11 0.540940E+11 0.438856E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.338241E+11 0.131446E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.301028E+11 0.561331E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.304991E+11 0.701737E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.405063E+12 0.310094E+13 0.417488E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.284025E+11 0.365383E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.383043E+11 0.701737E+12 0.159515E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 0.337919E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.302154E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.164020E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 0.215662E+10 2616979.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 13294.10 0.187749E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 32189.03 0.875150E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 31761.24 0.107248E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 2803799.50 0.644682E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 0.119726E+09 0.192142E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 0.418381E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.325190E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.408317E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 0.160223E+12 0.279954E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 13294.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.408317E+11 0.107248E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.790100E+11 0.00 0.00 0.00 0.00 0.226171E+10 0.00 0.00 0.80
February 0.689102E+11 0.00 0.00 0.00 0.00 0.186560E+10 0.00 0.00 0.79
March 0.578709E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.79
April 0.418639E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.80
May 0.399730E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.80
June 0.319016E+11 0.00 0.00 0.00 5092308.37 0.00 0.00 0.00 0.80
July 0.309063E+11 0.00 0.00 0.00 20072063.38 0.00 0.00 0.00 0.80
August 0.268273E+11 0.00 0.00 7446061.79 0.00 0.00 0.102322E+11 0.00 0.80
September 0.151320E+11 0.00 0.00 20027574.88 0.00 0.00 0.260282E+11 0.00 0.82
October 0.172847E+11 0.00 0.00 21579337.60 0.00 0.00 0.289134E+11 0.00 0.83
November 0.623950E+11 0.00 0.00 6991047.38 0.00 0.00 0.155629E+11 0.00 0.80
December 0.892453E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.80
                   
Annual Sum or Average 0.561320E+12 0.00 0.00 56044021.65 25164371.76 0.412731E+10 0.807366E+11 0.00 0.80
Minimum of Months 0.151320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.79
Maximum of Months 0.892453E+11 0.00 0.00 21579337.60 20072063.38 0.226171E+10 0.289134E+11 0.00 0.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.500226E+09 0.00 0.00 0.00 0.00 0.198459E+11 0.00 0.00 3.63
February 0.363165E+10 0.00 0.00 0.00 0.00 0.140869E+11 0.00 0.00 3.59
March 0.782323E+10 0.00 0.00 496167.69 0.00 0.584931E+10 0.822019E+09 0.00 3.60
April 0.849722E+10 0.00 0.00 1899298.46 0.00 0.338333E+09 0.178281E+10 0.00 3.68
May 0.895887E+10 0.00 0.00 1692129.32 0.00 0.00 0.110776E+10 0.00 3.66
June 0.734696E+10 1278029.84 0.00 1539154.62 33006.43 0.00 0.651799E+09 0.00 3.64
July 0.732867E+10 4780004.79 0.00 1813527.57 500695.88 0.00 0.419100E+09 0.00 3.68
August 0.848428E+10 0.00 0.00 2310795.80 0.00 0.00 0.860324E+09 0.00 3.68
September 0.939869E+10 0.00 0.00 751944.34 0.00 2833699.83 0.673488E+09 0.00 3.63
October 0.775400E+10 0.00 0.00 162995.08 0.00 0.327896E+10 0.215093E+09 0.00 3.62
November 0.862275E+09 0.00 0.00 0.00 0.00 0.185868E+11 0.00 0.00 3.61
December 31383090.43 0.00 0.00 0.00 0.00 0.223109E+11 0.00 0.00 3.62
                   
Annual Sum or Average 0.706175E+11 6058034.63 0.00 10666012.88 533702.31 0.843000E+11 0.653239E+10 0.00 3.64
Minimum of Months 31383090.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.59
Maximum of Months 0.939869E+10 4780004.79 0.00 2310795.80 500695.88 0.223109E+11 0.178281E+10 0.00 3.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.806916E+10 0.00 0.00 0.00 0.00 0.951974E+09 0.00 0.00 1.39
February 0.784206E+10 0.00 0.00 0.00 0.00 14035727.85 0.00 0.00 1.38
March 0.642365E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.38
April 0.411885E+10 0.00 0.00 283291.43 0.00 0.00 0.530482E+09 0.00 1.39
May 0.337586E+10 0.00 0.00 750669.17 0.00 0.00 0.106912E+10 0.00 1.40
June 0.196183E+10 0.00 0.00 1861554.18 565244.98 0.00 0.160212E+10 0.00 1.41
July 0.187705E+10 730910.15 0.00 1827377.80 1497083.95 0.00 0.157733E+10 0.00 1.42
August 0.259229E+10 0.00 0.00 1397486.02 0.00 0.00 0.153915E+10 0.00 1.40
September 0.400340E+10 0.00 0.00 147976.03 0.00 0.00 0.451309E+09 0.00 1.39
October 0.497025E+10 0.00 0.00 1495.15 0.00 0.00 15390510.30 0.00 1.39
November 0.862341E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.38
December 0.959194E+10 0.00 0.00 0.00 0.00 0.314260E+09 0.00 0.00 1.39
                   
Annual Sum or Average 0.634498E+11 730910.15 0.00 6269849.78 2062328.93 0.128027E+10 0.678491E+10 0.00 1.39
Minimum of Months 0.187705E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.38
Maximum of Months 0.959194E+10 730910.15 0.00 1861554.18 1497083.95 0.951974E+09 0.160212E+10 0.00 1.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.151475E+10 0.00 0.00 0.00 0.00 0.543166E+10 0.00 0.00 0.51
February 0.214995E+10 0.00 0.00 0.00 0.00 0.389936E+10 0.00 0.00 0.50
March 0.371495E+10 0.00 0.00 0.00 0.00 0.123136E+10 0.00 0.00 0.50
April 0.357817E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
May 0.341655E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
June 0.262705E+10 0.00 0.00 156017.16 435246.94 0.00 0.100031E+09 0.00 0.51
July 0.247458E+10 3115.73 0.00 300315.86 1712472.47 0.00 0.168902E+09 0.00 0.51
August 0.310722E+10 0.00 0.00 47136.35 0.00 0.00 55553151.93 0.00 0.50
September 0.343031E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
October 0.372443E+10 0.00 0.00 0.00 0.00 0.114590E+09 0.00 0.00 0.50
November 0.198910E+10 0.00 0.00 0.00 0.00 0.465105E+10 0.00 0.00 0.50
December 0.135390E+10 0.00 0.00 0.00 0.00 0.627402E+10 0.00 0.00 0.50
                   
Annual Sum or Average 0.330810E+11 3115.73 0.00 503469.36 2147719.41 0.216020E+11 0.324486E+09 0.00 0.51
Minimum of Months 0.135390E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
Maximum of Months 0.372443E+10 3115.73 0.00 300315.86 1712472.47 0.627402E+10 0.168902E+09 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26460104.31 0.00 0.00 0.00 0.00 0.371459E+10 0.00 0.00 0.47
February 0.214871E+09 0.00 0.00 0.00 0.00 0.304304E+10 0.00 0.00 0.47
March 0.859302E+09 0.00 0.00 0.00 0.00 0.180458E+10 0.00 0.00 0.47
April 0.175856E+10 0.00 0.00 0.00 0.00 0.168493E+09 0.00 0.00 0.47
May 0.184001E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
June 0.146739E+10 0.00 0.00 28.15 234406.00 0.00 1082579.47 0.00 0.47
July 0.141887E+10 0.00 0.00 919.83 923944.87 0.00 3792586.82 0.00 0.48
August 0.170337E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
September 0.184742E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
October 0.138438E+10 0.00 0.00 0.00 0.00 0.683162E+09 0.00 0.00 0.47
November 46157015.11 0.00 0.00 0.00 0.00 0.352995E+10 0.00 0.00 0.47
December 11167367.10 0.00 0.00 0.00 0.00 0.409692E+10 0.00 0.00 0.47
                   
Annual Sum or Average 0.125779E+11 0.00 0.00 947.98 1158350.87 0.170407E+11 4875166.29 0.00 0.47
Minimum of Months 11167367.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.184742E+10 0.00 0.00 919.83 923944.87 0.409692E+10 3792586.82 0.00 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.966928E+10 0.00 0.00 85206023.52 0.00 0.210308E+10 0.136617E+12 0.00 23.44
February 0.489502E+10 0.00 0.00 80517306.52 0.00 0.104496E+09 0.124254E+12 0.00 23.19
March 0.682962E+09 0.00 0.00 95485446.54 0.00 0.00 0.109038E+12 0.00 23.87
April 0.211118E+09 0.00 0.00 97262647.43 0.00 0.00 0.805565E+11 0.00 24.09
May 0.236444E+09 0.00 0.00 0.114024E+09 0.00 0.00 0.772954E+11 0.00 24.07
June 87325910.66 8475499.87 0.00 0.122727E+09 0.00 0.00 0.599110E+11 0.00 24.06
July 0.120040E+09 36816334.17 0.00 0.129100E+09 0.00 0.00 0.578672E+11 0.00 24.05
August 0.169656E+09 0.00 0.00 0.116556E+09 0.00 0.00 0.702823E+11 0.00 24.02
September 0.190963E+09 0.00 0.00 95584699.92 0.00 0.00 0.777693E+11 0.00 24.15
October 0.291072E+09 0.00 0.00 96297713.45 0.00 0.00 0.864939E+11 0.00 24.07
November 0.276841E+10 0.00 0.00 85575635.47 0.00 0.00 0.139390E+12 0.00 23.30
December 0.474639E+10 0.00 0.00 84889945.75 0.00 83901552.28 0.157363E+12 0.00 23.07
                   
Annual Sum or Average 0.240687E+11 45291834.04 0.00 0.120323E+10 0.00 0.229148E+10 0.117684E+13 0.00 23.78
Minimum of Months 87325910.66 0.00 0.00 80517306.52 0.00 0.00 0.578672E+11 0.00 23.07
Maximum of Months 0.966928E+10 36816334.17 0.00 0.129100E+09 0.00 0.210308E+10 0.157363E+12 0.00 24.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.591012E+11 0.00 0.00 0.00 0.00 0.202430E+11 0.00 0.00 5.04
February 0.665830E+11 0.00 0.00 23973.87 0.00 0.226980E+10 0.244397E+09 0.00 4.98
March 0.491895E+11 0.00 0.00 3579009.40 0.00 5363163.76 0.736157E+10 0.00 5.00
April 0.189659E+11 0.00 0.00 14082269.08 0.00 0.00 0.223669E+11 0.00 5.11
May 0.144983E+11 0.00 0.00 16685869.81 0.00 0.00 0.246900E+11 0.00 5.07
June 0.959451E+10 4921544.88 0.00 21486286.02 69827.78 0.00 0.215637E+11 0.00 5.06
July 0.967110E+10 19395882.06 0.00 21792343.20 908365.90 0.00 0.205115E+11 0.00 5.10
August 0.129083E+11 0.00 0.00 21637897.54 0.00 0.00 0.234388E+11 0.00 5.09
September 0.221239E+11 0.00 0.00 7716235.41 0.00 0.00 0.171699E+11 0.00 5.05
October 0.394996E+11 0.00 0.00 1492554.75 0.00 83745153.53 0.427659E+10 0.00 5.02
November 0.651596E+11 0.00 0.00 0.00 0.00 0.106865E+11 0.00 0.00 5.01
December 0.607466E+11 0.00 0.00 0.00 0.00 0.263821E+11 0.00 0.00 5.01
                   
Annual Sum or Average 0.428041E+12 24317426.94 0.00 0.108496E+09 978193.68 0.596705E+11 0.141623E+12 0.00 5.05
Minimum of Months 0.959451E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.98
Maximum of Months 0.665830E+11 19395882.06 0.00 21792343.20 908365.90 0.263821E+11 0.246900E+11 0.00 5.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.193914E+12 0.00 0.00 0.00 0.00 0.182284E+11 0.00 0.00 1.95
February 0.183669E+12 0.00 0.00 8155.72 0.00 0.913959E+09 0.162212E+09 0.00 1.93
March 0.143640E+12 0.00 0.00 1296149.56 0.00 0.00 0.741798E+10 0.00 1.93
April 0.656007E+11 0.00 0.00 25591060.65 0.00 0.00 0.438977E+11 0.00 1.95
May 0.443291E+11 0.00 0.00 53543755.39 0.00 0.00 0.608845E+11 0.00 1.96
June 0.231587E+11 10101288.83 0.00 84174949.99 3191092.33 0.00 0.618196E+11 0.00 2.00
July 0.203854E+11 47003447.14 0.00 86830681.25 5390378.48 0.00 0.620684E+11 0.00 2.01
August 0.304793E+11 0.00 0.00 78625211.44 0.00 0.00 0.678720E+11 0.00 1.98
September 0.567633E+11 0.00 0.00 25385636.03 0.00 0.00 0.481201E+11 0.00 1.95
October 0.104679E+12 0.00 0.00 3993121.10 0.00 0.00 0.125603E+11 0.00 1.94
November 0.202789E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.94
December 0.228361E+12 0.00 0.00 0.00 0.00 0.459439E+10 0.00 0.00 1.94
                   
Annual Sum or Average 0.129777E+13 57104735.96 0.00 0.359449E+09 8581470.81 0.237367E+11 0.364803E+12 0.00 1.96
Minimum of Months 0.203854E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.93
Maximum of Months 0.228361E+12 47003447.14 0.00 86830681.25 5390378.48 0.182284E+11 0.678720E+11 0.00 2.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 41124.34 0.00 0.342858E+10 1782194.73 0.00 0.36
February 29163832.26 0.00 0.00 141451.23 0.00 0.306902E+10 4543514.03 0.00 0.35
March 89269821.70 0.00 0.00 1231696.85 0.00 0.223836E+10 0.114710E+09 0.00 0.36
April 46135459.49 0.00 0.00 8365964.55 0.00 0.662277E+09 0.911365E+09 0.00 0.36
May 13869387.92 0.00 0.00 15798534.09 0.00 41681204.82 0.145684E+10 0.00 0.36
June 2832445.21 1253612.77 0.00 22230168.40 0.00 2584775.74 0.111632E+10 0.00 0.36
July 4370856.91 4796578.54 0.00 20463037.88 0.00 2641913.69 0.962672E+09 0.00 0.36
August 12969537.51 0.00 0.00 16387367.92 0.00 13262670.06 0.117272E+10 0.00 0.35
September 59087954.44 0.00 0.00 5164894.91 0.00 0.536062E+09 0.903793E+09 0.00 0.36
October 65393688.76 0.00 0.00 546126.00 0.00 0.157622E+10 0.105699E+09 0.00 0.36
November 3200088.67 0.00 0.00 43589.84 0.00 0.326107E+10 2164236.08 0.00 0.36
December 0.00 0.00 0.00 24103.73 0.00 0.377586E+10 715490.27 0.00 0.36
                   
Annual Sum or Average 0.326293E+09 6050191.31 0.00 90438059.74 0.00 0.186076E+11 0.675333E+10 0.00 0.36
Minimum of Months 0.00 0.00 0.00 24103.73 0.00 2584775.74 715490.27 0.00 0.35
Maximum of Months 89269821.70 4796578.54 0.00 22230168.40 0.00 0.377586E+10 0.145684E+10 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 29098.03 0.00 0.342868E+10 1289825.48 0.00 0.36
February 1306258.04 0.00 0.00 90010.27 0.00 0.309879E+10 2323271.95 0.00 0.35
March 23148206.09 0.00 0.00 308450.68 0.00 0.237307E+10 46757077.81 0.00 0.36
April 87486679.88 0.00 0.00 5237104.88 0.00 0.861536E+09 0.673692E+09 0.00 0.36
May 0.204690E+09 0.00 0.00 12290711.41 0.00 59219641.65 0.125181E+10 0.00 0.36
June 0.231093E+09 1114883.25 306.56 18759648.88 137871.11 1088407.70 0.892896E+09 404.98 0.36
July 0.198480E+09 4231798.68 0.00 16580209.72 564217.87 1748875.40 0.773223E+09 0.00 0.36
August 0.229824E+09 0.00 0.00 11246307.29 0.00 28114319.80 0.946016E+09 0.00 0.36
September 0.121972E+09 0.00 0.00 2790785.30 0.00 0.695869E+09 0.683299E+09 0.00 0.36
October 38067130.69 0.00 0.00 237588.22 0.00 0.168194E+10 27409808.60 0.00 0.36
November 0.00 0.00 0.00 18366.68 0.00 0.326492E+10 1160410.24 0.00 0.36
December 0.00 0.00 0.00 18803.01 0.00 0.377547E+10 663663.72 0.00 0.36
                   
Annual Sum or Average 0.113607E+10 5346681.93 306.56 67607084.37 702088.98 0.192704E+11 0.530054E+10 404.98 0.36
Minimum of Months 0.00 0.00 0.00 18366.68 0.00 1088407.70 663663.72 0.00 0.35
Maximum of Months 0.231093E+09 4231798.68 306.56 18759648.88 564217.87 0.377547E+10 0.125181E+10 404.98 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.160238E+09 0.00 0.00 0.00 0.00 0.160528E+10 0.00 0.00 0.02
February 0.880160E+09 0.00 0.00 0.00 0.00 0.337691E+09 0.00 0.00 0.02
March 0.966252E+09 0.00 0.00 1226150.10 0.00 0.00 0.458521E+09 0.00 0.02
April 90828918.28 0.00 0.00 6654669.67 0.00 0.00 0.165659E+10 0.00 0.02
May 0.00 0.00 0.00 6233072.23 0.00 0.00 0.175628E+10 0.00 0.02
June 15671953.41 1909380.08 0.00 6077583.89 0.00 0.00 0.123195E+10 0.00 0.02
July 0.00 7691744.39 0.00 6081020.28 0.00 0.00 0.819056E+09 0.00 0.02
August 0.00 0.00 0.00 6567867.29 0.00 0.00 0.120257E+10 0.00 0.02
September 0.397216E+09 0.00 0.00 3601832.17 0.00 0.00 0.130520E+10 0.00 0.02
October 0.994988E+09 0.00 0.00 919381.22 0.00 0.00 0.497373E+09 0.00 0.02
November 0.418463E+09 0.00 0.00 0.00 0.00 0.122724E+10 0.00 0.00 0.02
December 0.00 0.00 0.00 0.00 0.00 0.211008E+10 0.00 0.00 0.02
                   
Annual Sum or Average 0.392382E+10 9601124.47 0.00 37361576.86 0.00 0.528030E+10 0.892754E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.994988E+09 7691744.39 0.00 6654669.67 0.00 0.211008E+10 0.175628E+10 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.856117E+09 0.00 0.00 919474.28 0.00 0.454802E+11 0.188634E+09 0.00 0.41
February 0.100845E+10 0.00 0.00 1281298.14 0.00 0.402560E+11 0.817985E+09 0.00 0.40
March 0.124223E+10 0.00 0.00 4922873.46 0.00 0.276227E+11 0.427186E+10 0.00 0.40
April 0.127394E+10 0.00 0.00 45878520.09 0.00 0.496348E+10 0.157989E+11 0.00 0.41
May 0.312473E+10 0.00 0.00 0.145220E+09 0.00 23975020.66 0.174326E+11 0.00 0.40
June 0.379322E+10 15132374.03 0.00 0.218198E+09 1870138.85 2876183.06 0.115012E+11 0.00 0.41
July 0.306333E+10 57089203.89 0.00 0.218230E+09 7965883.48 2070648.11 0.101456E+11 0.00 0.41
August 0.340896E+10 0.00 0.00 0.152012E+09 0.00 11607265.79 0.129109E+11 0.00 0.40
September 0.165448E+10 0.00 0.00 60988991.79 0.00 0.614815E+09 0.180696E+11 0.00 0.41
October 0.122965E+10 0.00 0.00 13991450.93 0.00 0.131618E+11 0.930048E+10 0.00 0.41
November 0.111064E+10 0.00 0.00 896941.39 0.00 0.430718E+11 0.119379E+09 0.00 0.40
December 0.494236E+09 0.00 0.00 721652.78 0.00 0.505597E+11 0.166632E+09 0.00 0.41
                   
Annual Sum or Average 0.222600E+11 72221577.92 0.00 0.863261E+09 9836022.33 0.225771E+12 0.100724E+12 0.00 0.40
Minimum of Months 0.494236E+09 0.00 0.00 721652.78 0.00 2070648.11 0.119379E+09 0.00 0.40
Maximum of Months 0.379322E+10 57089203.89 0.00 0.218230E+09 7965883.48 0.505597E+11 0.180696E+11 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1133454.42 0.00 0.00 38308.54 0.00 0.342761E+10 1614506.35 0.00 0.36
February 35115073.29 0.00 0.00 178130.71 0.00 0.305092E+10 16663353.38 0.00 0.35
March 74767720.88 0.00 0.00 1638400.29 0.00 0.210228E+10 0.264880E+09 0.00 0.36
April 22862100.93 0.00 0.00 7756980.36 0.00 0.638025E+09 0.959499E+09 0.00 0.36
May 3412163.15 0.00 0.00 19574821.52 0.00 27661924.72 0.147754E+10 0.00 0.36
June 2832445.21 1253612.77 0.00 24201768.82 0.00 1079275.89 0.111586E+10 0.00 0.36
July 2973105.15 4796578.54 0.00 25357919.10 0.00 1183068.45 0.960634E+09 0.00 0.36
August 5042317.33 0.00 0.00 18205010.28 0.00 8821969.98 0.118327E+10 0.00 0.35
September 40456383.98 0.00 0.00 6205728.38 0.00 0.448358E+09 0.100909E+10 0.00 0.36
October 69866276.18 0.00 0.00 858392.67 0.00 0.148252E+10 0.194613E+09 0.00 0.36
November 3200088.67 0.00 0.00 33935.36 0.00 0.326154E+10 1710854.13 0.00 0.36
December 0.00 0.00 0.00 21228.21 0.00 0.377586E+10 718365.80 0.00 0.36
                   
Annual Sum or Average 0.261661E+09 6050191.31 0.00 0.104071E+09 0.00 0.182259E+11 0.718609E+10 0.00 0.36
Minimum of Months 0.00 0.00 0.00 21228.21 0.00 1079275.89 718365.80 0.00 0.35
Maximum of Months 74767720.88 4796578.54 0.00 25357919.10 0.00 0.377586E+10 0.147754E+10 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 25506.02 0.00 0.342885E+10 1126769.93 0.00 0.36
February 2653282.37 0.00 0.00 96375.79 0.00 0.309585E+10 3907827.30 0.00 0.35
March 75249326.76 0.00 0.00 572162.60 0.00 0.225850E+10 0.108964E+09 0.00 0.36
April 67437560.33 0.00 0.00 4561646.84 0.00 0.846695E+09 0.709259E+09 0.00 0.36
May 0.140060E+09 0.00 0.00 16347193.66 0.00 32477327.93 0.133913E+10 0.00 0.36
June 0.232938E+09 1115594.79 0.00 21489156.97 137871.11 709050.27 0.888701E+09 0.00 0.36
July 0.192473E+09 4231798.68 0.00 21038160.19 564217.87 1028580.67 0.775492E+09 0.00 0.36
August 0.199370E+09 0.00 0.00 13647565.02 0.00 20752936.29 0.981430E+09 0.00 0.36
September 0.108895E+09 0.00 0.00 3844418.92 0.00 0.629007E+09 0.762184E+09 0.00 0.36
October 54457971.38 0.00 0.00 358374.56 0.00 0.157480E+10 0.118043E+09 0.00 0.36
November 0.00 0.00 0.00 13946.50 0.00 0.326518E+10 906848.08 0.00 0.36
December 0.00 0.00 0.00 16949.18 0.00 0.377547E+10 665517.54 0.00 0.36
                   
Annual Sum or Average 0.107353E+10 5347393.47 0.00 82011456.26 702088.98 0.189293E+11 0.568980E+10 0.00 0.36
Minimum of Months 0.00 0.00 0.00 13946.50 0.00 709050.27 665517.54 0.00 0.35
Maximum of Months 0.232938E+09 4231798.68 0.00 21489156.97 564217.87 0.377547E+10 0.133913E+10 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.415295E+10 0.00 0.00 0.00 0.00 0.521793E+11 0.00 0.00 0.56
February 0.125214E+11 0.00 0.00 0.00 0.00 0.365358E+11 0.00 0.00 0.56
March 0.315577E+11 0.00 0.00 0.00 0.00 0.855462E+10 0.00 0.00 0.56
April 0.286977E+11 0.00 0.00 0.00 0.00 0.319590E+09 0.00 0.00 0.56
May 0.277067E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
June 0.217956E+11 0.00 0.00 191526.45 3529655.63 0.00 0.316318E+09 0.00 0.57
July 0.210004E+11 0.00 0.00 320843.19 13912643.60 0.00 0.421491E+09 0.00 0.57
August 0.256491E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
September 0.278182E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
October 0.249433E+11 0.00 0.00 0.00 0.00 0.618947E+10 0.00 0.00 0.56
November 0.531283E+10 0.00 0.00 0.00 0.00 0.485358E+11 0.00 0.00 0.56
December 0.139468E+10 0.00 0.00 0.00 0.00 0.604643E+11 0.00 0.00 0.56
                   
Annual Sum or Average 0.232550E+12 0.00 0.00 512369.64 17442299.23 0.212779E+12 0.737809E+09 0.00 0.56
Minimum of Months 0.139468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
Maximum of Months 0.315577E+11 0.00 0.00 320843.19 13912643.60 0.604643E+11 0.421491E+09 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2995.09 0.00 0.857270E+09 326774.43 0.00 0.36
February 1543613.03 0.00 0.00 17753.41 0.00 0.773224E+09 932820.72 0.00 0.35
March 16148983.79 0.00 0.00 224253.85 0.00 0.574716E+09 19802969.59 0.00 0.36
April 13198079.65 0.00 0.00 1966752.97 0.00 0.216529E+09 0.175342E+09 0.00 0.36
May 3716463.08 0.00 0.00 3692555.26 0.00 41189029.12 0.333449E+09 0.00 0.36
June 1178363.99 313403.19 0.00 5417992.01 0.00 659524.65 0.278737E+09 0.00 0.36
July 2023121.23 1199144.63 0.00 4940271.31 0.00 1003668.74 0.239570E+09 0.00 0.36
August 3365638.76 0.00 0.00 3865991.29 0.00 19069168.11 0.277535E+09 0.00 0.35
September 15836229.05 0.00 0.00 1093008.57 0.00 0.206663E+09 0.152435E+09 0.00 0.36
October 11418440.38 0.00 0.00 97858.20 0.00 0.412647E+09 12801731.64 0.00 0.36
November 0.00 0.00 0.00 3235.25 0.00 0.816283E+09 334893.03 0.00 0.36
December 0.00 0.00 0.00 2384.28 0.00 0.943979E+09 168252.39 0.00 0.36
                   
Annual Sum or Average 68428932.97 1512547.83 0.00 21325051.49 0.00 0.486323E+10 0.149144E+10 0.00 0.36
Minimum of Months 0.00 0.00 0.00 2384.28 0.00 659524.65 168252.39 0.00 0.35
Maximum of Months 16148983.79 1199144.63 0.00 5417992.01 0.00 0.943979E+09 0.333449E+09 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3123.57 0.00 0.857190E+09 306417.18 0.00 0.36
February 0.00 0.00 0.00 11896.93 0.00 0.774983E+09 632848.60 0.00 0.35
March 3976937.05 0.00 0.00 46602.29 0.00 0.599749E+09 7048234.36 0.00 0.36
April 19114464.64 0.00 0.00 1161145.07 0.00 0.266375E+09 0.120337E+09 0.00 0.36
May 48482443.30 0.00 0.00 2901102.89 0.00 50745519.83 0.279874E+09 0.00 0.36
June 56936179.35 278898.70 0.00 4869996.37 34467.78 436883.67 0.223716E+09 0.00 0.36
July 49114992.92 1057949.67 0.00 4165154.18 141054.47 493765.94 0.193734E+09 0.00 0.36
August 56391672.63 0.00 0.00 2661609.41 0.00 23756859.43 0.220990E+09 0.00 0.36
September 28654298.16 0.00 0.00 525969.62 0.00 0.258435E+09 88367522.45 0.00 0.36
October 5680775.02 0.00 0.00 52210.71 0.00 0.427210E+09 3970585.67 0.00 0.36
November 0.00 0.00 0.00 1945.61 0.00 0.816164E+09 358675.77 0.00 0.36
December 0.00 0.00 0.00 2380.47 0.00 0.943868E+09 168236.21 0.00 0.36
                   
Annual Sum or Average 0.268352E+09 1336848.37 0.00 16403137.11 175522.24 0.501941E+10 0.113950E+10 0.00 0.36
Minimum of Months 0.00 0.00 0.00 1945.61 0.00 436883.67 168236.21 0.00 0.35
Maximum of Months 56936179.35 1057949.67 0.00 4869996.37 141054.47 0.943868E+09 0.279874E+09 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 58147475.65 0.00 0.00 124515.18 0.00 0.544347E+10 7899726.59 0.00 0.41
February 0.114691E+09 0.00 0.00 993202.61 0.00 0.473937E+10 0.128540E+09 0.00 0.40
March 53447141.53 0.00 0.00 5608952.24 0.00 0.317357E+10 0.692047E+09 0.00 0.40
April 12743231.92 0.00 0.00 15687797.95 0.00 0.712843E+09 0.187372E+10 0.00 0.41
May 8868775.09 0.00 0.00 23888914.47 0.00 56664283.10 0.236504E+10 0.00 0.41
June 6048069.37 2013455.47 0.00 29436167.43 0.00 4161599.28 0.179771E+10 0.00 0.40
July 7020130.91 7703891.92 0.00 29420818.76 0.00 4016254.59 0.154984E+10 0.00 0.41
August 15504893.77 0.00 0.00 26170751.34 0.00 12949384.22 0.189736E+10 0.00 0.40
September 45428221.32 0.00 0.00 12516887.02 0.00 0.451264E+09 0.190657E+10 0.00 0.41
October 93737611.17 0.00 0.00 3309256.66 0.00 0.203904E+10 0.671192E+09 0.00 0.41
November 70887699.65 0.00 0.00 226749.86 0.00 0.515843E+10 16825404.31 0.00 0.40
December 0.00 0.00 0.00 52547.64 0.00 0.606219E+10 3430218.93 0.00 0.41
                   
Annual Sum or Average 0.486524E+09 9717347.40 0.00 0.147437E+09 0.00 0.278580E+11 0.129102E+11 0.00 0.41
Minimum of Months 0.00 0.00 0.00 52547.64 0.00 4016254.59 3430218.93 0.00 0.40
Maximum of Months 0.114691E+09 7703891.92 0.00 29436167.43 0.00 0.606219E+10 0.236504E+10 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.478151E+11 0.00 0.00 20716103.24 0.00 0.336279E+09 0.377800E+11 0.00 4.08
February 0.407288E+11 0.00 0.00 20749312.47 0.00 0.00 0.344759E+11 0.00 4.07
March 0.193930E+11 0.00 0.00 34287165.91 0.00 0.00 0.437384E+11 0.00 4.19
April 0.334888E+10 0.00 0.00 56261035.46 0.00 0.00 0.459380E+11 0.00 4.55
May 0.287355E+09 0.00 0.00 86766675.69 0.00 0.00 0.521204E+11 0.00 4.97
June 15575864.62 5376670.39 0.00 0.106751E+09 0.00 0.00 0.454513E+11 0.00 5.34
July 20642435.14 24817866.29 0.00 0.111032E+09 0.00 0.00 0.442871E+11 0.00 5.32
August 0.302400E+09 0.00 0.00 91714133.15 0.00 0.00 0.497162E+11 0.00 5.06
September 0.123721E+10 0.00 0.00 61411619.13 0.00 0.00 0.479047E+11 0.00 4.67
October 0.873270E+10 0.00 0.00 43756936.87 0.00 0.00 0.420043E+11 0.00 4.35
November 0.454014E+11 0.00 0.00 20081768.62 0.00 0.00 0.367897E+11 0.00 4.06
December 0.547431E+11 0.00 0.00 16019689.10 0.00 0.00 0.391718E+11 0.00 4.03
                   
Annual Sum or Average 0.222026E+12 30194536.68 0.00 0.669548E+09 0.00 0.336279E+09 0.519378E+12 0.00 4.56
Minimum of Months 15575864.62 0.00 0.00 16019689.10 0.00 0.00 0.344759E+11 0.00 4.03
Maximum of Months 0.547431E+11 24817866.29 0.00 0.111032E+09 0.00 0.336279E+09 0.521204E+11 0.00 5.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.437455E+11 0.00 0.00 29478492.33 0.00 0.216427E+09 0.472165E+11 0.00 4.36
February 0.346423E+11 0.00 0.00 29189675.62 0.00 0.00 0.453839E+11 0.00 4.37
March 0.131660E+11 0.00 0.00 47379679.08 0.00 0.00 0.549847E+11 0.00 4.55
April 0.103537E+10 0.00 0.00 70947499.58 0.00 0.00 0.528406E+11 0.00 4.97
May 32775061.27 0.00 0.00 0.100795E+09 0.00 0.00 0.570135E+11 0.00 5.41
June 0.00 5801561.14 0.00 0.118056E+09 0.00 0.00 0.488284E+11 0.00 5.75
July 0.00 26954794.96 0.00 0.122987E+09 0.00 0.00 0.475383E+11 0.00 5.72
August 58360641.41 0.00 0.00 0.104297E+09 0.00 0.00 0.539747E+11 0.00 5.47
September 0.221208E+09 0.00 0.00 75900303.72 0.00 0.00 0.537463E+11 0.00 5.13
October 0.437228E+10 0.00 0.00 58479999.82 0.00 0.00 0.511190E+11 0.00 4.77
November 0.405657E+11 0.00 0.00 28700941.58 0.00 0.00 0.467346E+11 0.00 4.34
December 0.475656E+11 0.00 0.00 23645749.43 0.00 0.00 0.516191E+11 0.00 4.28
                   
Annual Sum or Average 0.185405E+12 32756356.10 0.00 0.809858E+09 0.00 0.216427E+09 0.611000E+12 0.00 4.93
Minimum of Months 0.00 0.00 0.00 23645749.43 0.00 0.00 0.453839E+11 0.00 4.28
Maximum of Months 0.475656E+11 26954794.96 0.00 0.122987E+09 0.00 0.216427E+09 0.570135E+11 0.00 5.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.447735E+10 0.00 0.00 93661631.51 0.00 0.130281E+09 0.110332E+12 0.00 18.69
February 0.222028E+10 0.00 0.00 90861816.28 0.00 0.00 0.993242E+11 0.00 18.99
March 0.385425E+09 0.00 0.00 0.108849E+09 0.00 0.00 0.924103E+11 0.00 20.69
April 0.00 0.00 0.00 0.115868E+09 0.00 0.00 0.741716E+11 0.00 21.84
May 0.00 0.00 0.00 0.142661E+09 0.00 0.00 0.721335E+11 0.00 22.60
June 0.00 10950497.29 0.00 0.154675E+09 0.00 0.00 0.554738E+11 0.00 22.87
July 0.00 43149736.62 0.00 0.163359E+09 0.00 0.00 0.521966E+11 0.00 22.91
August 0.00 0.00 0.00 0.143824E+09 0.00 0.00 0.641116E+11 0.00 22.46
September 0.00 0.00 0.00 0.112762E+09 0.00 0.00 0.708751E+11 0.00 21.91
October 0.00 0.00 0.00 0.107677E+09 0.00 0.00 0.761760E+11 0.00 20.93
November 0.946963E+09 0.00 0.00 93417171.67 0.00 0.00 0.109498E+12 0.00 18.62
December 0.147979E+10 0.00 0.00 91955825.46 0.00 0.00 0.121145E+12 0.00 18.04
                   
Annual Sum or Average 0.950980E+10 54100233.91 0.00 0.141957E+10 0.00 0.130281E+09 0.997848E+12 0.00 20.89
Minimum of Months 0.00 0.00 0.00 90861816.28 0.00 0.00 0.521966E+11 0.00 18.04
Maximum of Months 0.447735E+10 43149736.62 0.00 0.163359E+09 0.00 0.130281E+09 0.121145E+12 0.00 22.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 97874945.27 0.00 0.00 0.00 0.00 0.305940E+11 0.00 0.00 1.16
February 0.258089E+10 0.00 0.00 0.00 0.00 0.241473E+11 0.00 0.00 1.15
March 0.109511E+11 0.00 0.00 0.00 0.00 0.109035E+11 0.00 0.00 1.15
April 0.147654E+11 0.00 0.00 0.00 0.00 0.104435E+10 0.00 0.00 1.16
May 0.150187E+11 0.00 0.00 60018.24 0.00 0.00 76872938.77 0.00 1.16
June 0.109868E+11 1890701.34 0.00 2428183.63 49789.76 0.00 0.106109E+10 0.00 1.16
July 0.107308E+11 7173042.30 0.00 2713508.44 501562.91 0.00 0.944033E+09 0.00 1.17
August 0.135945E+11 0.00 0.00 691364.51 0.00 0.00 0.379391E+09 0.00 1.15
September 0.151564E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.16
October 0.112914E+11 0.00 0.00 0.00 0.00 0.567084E+10 0.00 0.00 1.15
November 0.184955E+09 0.00 0.00 0.00 0.00 0.291538E+11 0.00 0.00 1.15
December 98879752.08 0.00 0.00 0.00 0.00 0.336042E+11 0.00 0.00 1.15
                   
Annual Sum or Average 0.105458E+12 9063743.64 0.00 5893074.82 551352.67 0.135118E+12 0.246138E+10 0.00 1.16
Minimum of Months 97874945.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.15
Maximum of Months 0.151564E+11 7173042.30 0.00 2713508.44 501562.91 0.336042E+11 0.106109E+10 0.00 1.17



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:45

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January -0.362493E+11 0.902590E+10 0.419852E+12 0.172910E+13 0.201986E+12
February 0.208529E+11 0.779002E+10 0.355315E+12 0.149377E+13 0.172046E+12
March 0.187560E+12 0.761464E+10 0.346092E+12 0.152476E+13 0.146866E+12
April 0.366875E+12 0.512324E+10 0.232114E+12 0.109482E+13 0.144733E+12
May 0.491482E+12 0.342831E+10 0.138765E+12 0.694713E+12 0.234070E+12
June 0.510632E+12 0.245340E+10 0.879920E+11 0.429080E+12 0.401144E+12
July 0.454629E+12 0.205956E+10 0.817568E+11 0.402083E+12 0.456538E+12
August 0.333671E+12 0.267593E+10 0.107955E+12 0.517421E+12 0.332548E+12
September 0.142894E+12 0.384538E+10 0.181046E+12 0.838466E+12 0.116582E+12
October 0.490607E+11 0.604268E+10 0.289065E+12 0.126772E+13 0.103558E+12
November -0.127786E+11 0.880095E+10 0.405161E+12 0.168791E+13 0.192445E+12
December -0.489366E+11 0.937791E+10 0.431426E+12 0.176893E+13 0.222574E+12
           
Annual Sum or Average 0.245969E+13 0.682379E+11 0.307654E+13 0.134488E+14 0.272509E+13
Minimum of Months -0.489366E+11 0.205956E+10 0.817568E+11 0.402083E+12 0.103558E+12
Maximum of Months 0.510632E+12 0.937791E+10 0.431426E+12 0.176893E+13 0.456538E+12